Board Exam Problems on POWER SYSTEM 1. The fact that the outer layer of the conductor carries more current as compared to core is known as . A. corona B. permeability C. fault D. skin effect 2. How many strands are there for a three-layer stranded conductor? A. 19 B. 37 C. 54 D. 27 Solution: # ๐๐ ๐ ๐ก๐๐๐๐๐ = ๐ฅ ๐ฅ = 3๐2 − 3๐ + 1 ๐ = ๐๐ข๐๐๐๐ ๐๐ ๐๐๐ฆ๐๐๐ @๐ =1 ๏ท ๐ฅ=1 @๐ =2 ๏ท ๐ฅ=7 @๐ =3 ๏ท ๐ = ๐๐ 3. An ACSR conductor having seven steel strands surrounded by 25 aluminum conductor is specified as . A. 7/25 B. 25/7 C. 14/50 D. 50/14 REE – May 2008 4. A single phase, 20 km line has a total inductance of 35 mH. The distance between the two conductors is 59 inches. Find the GMR of the conductor. A. 1.75 cm B. 1.89 cm C. 1.65 cm D. 1.99 cm Solution: ๐ฟ = (2 × 10−7 ) ๐๐( ๐บ๐๐ท ๐บ๐๐ ) → ๐ป/๐ ๏ท ๐บ๐๐ท = 59 ๐๐๐โ๐๐ ๐ฟ ๐ = (4 × 10−7 ) ๐๐( 35×10−3 4×10−3 = [๐๐ ( 4.735 = ๐๐( ๐บ๐๐ = ( 59 ๐ 4.735 ๐บ๐๐ ) )] (20, 000) ๐บ๐๐ 59 ๐๐๐โ๐๐ ๐บ๐๐ 59 ๐๐๐โ๐๐ ๐บ๐๐ท ) ) ๐บ๐๐ = (0.743 ๐๐๐โ๐๐ )( ๏ท ๐ฎ๐ด๐น = ๐. ๐๐ ๐๐ 2.54 ๐๐ 1 ๐๐๐โ ) REE – April 2011 5. A three-phase, 60 Hz, transmission line has its conductors arranged in a triangular configuration so that the two distances between conductors are 5m and the third is 8m. The conductors have an outside diameter of 0.25 inch. Find the inductive reactance in ohm per km per phase of the transmission line. A. 0.567 B. 0.283 C. 0.586 D. 0.293 Solution: 5m 5m 8m ๐บ๐๐ท = 6 √(52 )(52 )(82 ) ๏ท ๐บ๐๐ท = 5.84 ๐ ๐=( 0.25 ๐๐ 2 )( 2.54 ๐๐ 1 ๐๐ ) ๏ท ๐ = 0.3175 ๐๐ ๐บ๐๐ = 0.7788 ๐ ๐บ๐๐ = 0.7788(0.3175 ๐๐) ๏ท ๐บ๐๐ = 0.247 ๐๐ ๐ฟ = (2 × 10−7 ) ๐๐( ๐ฟ = (2 × 10−7 ) ๐๐( ๏ท ๐ฟ = 1.55 ๐๐ป ๐ ๐บ๐๐ท ) ๐บ๐๐ 5.84 ๐ 0.247 100 ) /∅ ๐๐ฟ = 2๐๐๐ฟ ๐๐ฟ = 2๐(60)(1.55 × 10−6 )(1, 000) ๏ท ๐ฟ๐ณ = ๐. ๐๐๐ โฆ ๐๐ /∅ REE – April 2007 6. A three-phase transposed distribution line is designed with equilateral spacing of 12 ft. It is decided to build the line with horizontal spacing (๐ท13 = 2๐ท12 = 2๐ท23 ). The conductors are transposed. What should be the spacing between adjacent conductors in order to obtain the same inductance as in the original design? A. 9.5246 B. 9.5056 C. 9.6437 D. 3.6190 Solution: ๐12 ๐23 ๐13 3 ๐บ๐๐ท1 = √12(12)(12) ๏ท ๐บ๐๐ท1 = 12 ๐๐ก ๐บ๐๐ท2 = 3√๐ท12 ๐ท23 ๐ท13 3 ๐บ๐๐ท2 = √(๐ท12 )2 2๐ท12 3 ๐บ๐๐ท2 = √2๐ท12 3 ๏ท ๐บ๐๐ท2 = √2 ๐ท12 ๐ฟ1 = ๐ฟ2 (2 × 10−7 ) ๐๐( ๐บ๐๐ท1 ๐บ๐๐ 1 = ๐บ๐๐ท1 ๐บ๐๐ 1 ) = (2 × 10−7 ) ๐๐( ๐บ๐๐ท2 ๐บ๐๐ 2 ) ๐บ๐๐ท2 ๐บ๐๐ 2 12 = (3√2)(๐ท12 ) ๏ท ๐ซ๐๐ = ๐. ๐๐๐ ๐๐ REE – April 2007 7. A three-phase circuit, 60 Hz, 230 kV transposed transmission line is composed of two 1, 272 ๐๐ถ๐ 54/19 conductors per phase with horizontal configuration. The bundle conductors are 50 cm in distance while phase spacing between the centers of the bundle is 10 meters. If the GMR of the ACSR conductors is 0.0466 ft., find the inductive reactance in ohm per km per phase of the transmission line. A. 0.3775 B. 0.3398 C. 0.3628 D. 0.3964 Solution: ๐บ๐๐ = 0.0466 ๐๐ก × 1๐ 3.281 ๐๐ก ๏ท ๐บ๐๐ = 0.0142 ๐ 3 ๐บ๐๐ท = √(102 )(20) ๏ท ๐บ๐๐ท = 12.6 ๐ 4 ๐บ๐๐ = √(0.0142)2 ( 50 2 ) 100 ๏ท ๐บ๐๐ = 0.0843 ๐ ๐ฟ = (2 × 10−7 ) ๐๐( ๐ฟ = (2 × 10−7 ) ๐๐( ๏ท ๐ฟ=1 ๐๐ป ๐ ๐บ๐๐ท ) ๐บ๐๐ 12.6 0.0843 ) ๐๐๐ ∅ ๐๐ฟ = 2๐๐๐ฟ ๐๐ฟ = 2๐(60)(1 × 10−6 )(1, 000) ๏ท ๐ฟ๐ณ = ๐. ๐๐๐ โฆ ๐๐ ๐๐๐ ∅ 8. A double circuit line consists of 300, 000 mil 26/6 ACSR Ostrich conductor arranged vertically with distances between phases of 15 ft, 15 ft and 30 ft. The horizontal distance between the circuits is 23 ft. Determine the inductive reactance of the line in milliohms per mile per phase if the GMR of each conductor is 0.0229 ft. A. 0.28 B. 0.46 C. 0.56 D. 0.39 Solution: a a’ 15 ft b b’ c 23 ft c’ ๐บ๐๐ = 0.0229 ๐๐ก ๐บ๐๐ท๐๐ = 4√๐๐๐ ๐๐′๐ ๐๐๐′ ๐๐′๐′ = 4 √(15)(15)(√152 + 232 )(√152 + 232 ) ๏ท ๐บ๐๐ท๐๐ = 20.295 ๐๐ก ๐บ๐๐ท๐๐ = 4√๐๐๐ ๐๐′๐ ๐๐๐′ ๐๐๐ ๐บ๐๐ท๐๐ = ๐บ๐๐ท๐๐ ๏ท ๐บ๐๐ท๐๐ = 20.295 ๐๐ก ๐บ๐๐ท๐๐ = 4√๐๐๐ ๐๐′๐ ๐๐๐′ ๐๐′๐′ = 4√(30)(30)(23)(23) ๏ท ๐บ๐๐ท๐๐ = 26.268 ๐๐ก ∴ ๐บ๐๐ท = 3√๐บ๐๐ท๐๐ ๐บ๐๐ท๐๐ ๐บ๐๐ท๐๐ = 3√20.295 (20.295 )(26.268) ๏ท ๐บ๐๐ท = 22.117 ๐๐ก 4 4 ๐บ๐๐ ๐ = √๐บ๐๐ 2 (๐๐′๐ ) = √0.02292 (√302 + 232 ) ๏ท ๐บ๐๐ ๐ = 0.93 ๐๐ก 4 4 ๐บ๐๐ ๐ = √๐บ๐๐ 2 (๐๐′๐ ) = √0.02292 (23) ๏ท ๐บ๐๐ ๐ = 0.726 ๐๐ก ๐บ๐๐ ๐ = ๐บ๐๐ ๐ ๏ท ๐บ๐๐ ๐ = 0.93 ๐๐ก ∴ ๐บ๐๐ = 3√๐บ๐๐ ๐ ๐บ๐๐ ๐ ๐บ๐๐ ๐ = 3√(0.93)(0726)(0.93) ๏ท ๐บ๐๐ = 0.856 ๐๐ก ๐ฟ = (2 × 10−7 ) ๐๐( ๐ฟ = (2 × 10−7 ) ๐๐( ๐บ๐๐ท ) ๐บ๐๐ 22.117 0.856 ) ๏ท ๐ฟ = 0.65 ๐๐ป ๐ ๐๐๐ ∅ ๐๐ฟ = 2๐๐๐ฟ ๐๐ฟ = 2๐(60)(0.65 × 10−6 )( ๏ท ๐ฟ๐ณ = ๐. ๐๐๐ ๐โฆ ๐ 1.6๐๐๐๐ 1๐ ) ๐๐๐ ∅ 9. The conductors are bundled primarily to A. increase reactance C. reduce reactance . B. reduce ratio interference D. reduce resistance REE – September 2010 10. A three-phase 60 Hz line has flat horizontal spacing. The conductors have an outside diameter of 3.28 cm with 12 m between conductors. Determine the capacitive reactance to neutral of the line in ohms if its length is 125 miles. A. 2, 023 โฆ B. 1, 619 โฆ C. 3, 238 โฆ D. 2, 605 โฆ Solution: ๐บ๐๐ท = 3√๐๐๐ ๐๐๐ ๐๐๐ = 3√(12)(12)(24) ๏ท ๐บ๐๐ท = 15.12 ๐ ๐บ๐๐ = ๐ 2 = 3.28 2 ๏ท ๐บ๐๐ = 1.64 ๐๐ 2๐๐๐ ๐ถ๐ = ๐๐( ๐บ๐๐ท ) ๐บ๐๐ = 2๐(8.85×10−12 ) 15.12 ) 0.164 ๐๐( ๏ท ๐ถ๐ = 8.15 ๐๐น/๐ ๐๐ถ = 1 ๐๐ถ = 1 2๐(8.15×10−12 ) 3.281 ๐๐ก ๐๐ถ = 325.49 ๐โฆ − ๐ ( 1๐ )( 1 ๐๐๐๐ 5280 ๐๐ก ) ๏ท ๐๐ถ = 202.198 ๐โฆ − ๐๐ ๐๐ถ๐ = 202,198 โฆ−๐๐ 125 ๐๐๐๐ ๏ท ๐ฟ๐ช๐ป = ๐, ๐๐๐ ๐๐๐๐ REE – September 2010 11. A string efficiency of 100% means that A. one of the insulator discs is shorted B. the potential across each disc is zero C. potential across each disc is the same D. potential across the large disc is very large . REE – May 2009 12. A three-phase, 60 Hz overhead line has a horizontal configuration. The conductors have an outside diameter of 3.28 cm. With 12 m distance between conductors, determine the capacitive reactance to neutral. A.0.2631 × 106 โฆ − ๐๐ ๐ก๐ ๐๐๐ข๐ก๐๐๐ B. 0.1864 × 106 โฆ − ๐๐ ๐ก๐ ๐๐๐ข๐ก๐๐๐ C. 0.1946 × 106 โฆ − ๐๐ ๐ก๐ ๐๐๐ข๐ก๐๐๐ D. ๐. ๐๐๐๐ × ๐๐๐ โฆ − ๐๐ ๐๐ ๐๐๐๐๐๐๐ Solution: 3 ๐บ๐๐ท = √12(12)(24) ๐บ๐๐ท = 15.12 ๐ ๐ถ๐ = 2๐๐๐ ๐๐( ๐บ๐๐ท ) ๐บ๐๐ = 2๐(8.85×10−12 ) 15.12 ) 0.164 ๐๐( ๏ท ๐ถ๐ = 8.15 ๐๐น/๐ 1 ๐๐ถ = = ๐๐ถ 1 2๐(8.15×10−12 ) 3.281 ๐๐ก ๐๐ถ = 325.49 ๐โฆ − ๐ ( 1๐ 6 )( 1 ๐๐๐๐ 5280 ๐๐ก ) ๏ท ๐๐ถ = 0.2022 × 10 โฆ − ๐๐ ๐ก๐ ๐๐๐ข๐ก๐๐๐ 13. Calculate the capacitive reactance in kโฆ-km of a bundled 60 Hz, three-phase line having three conductors per bundle with 45 cm between conductors of the bundle. The outside diameter is 0.175 in and the spacing between bundle centers is 10, 10 and 20 m. A. 243 B. 765 C. 486 D. 382 Solution: 10 m 45 cm ๐บ๐๐ท = 3√(10)(10)(20) ๏ท ๐บ๐๐ท = 12.6 ๐ ๐=( 0.175 ๐๐ ๏ท 2 )( 2.54 ๐๐ 1 ๐๐ ) ๐ = 0.22225 ๐๐ 9 ๐บ๐๐ = √(0.22225)3 (45)6 ๏ท ๐บ๐๐ = 7.6635 ๐๐ ๐ถ๐ = 2๐๐๐ ๐๐( ๐บ๐๐ท ) ๐บ๐๐ = 2๐(8.85×10−12 ) ๐๐( 12.6 ) 0.076635 ๏ท ๐ถ๐ = 10.9 ๐๐น/๐ 1 ๐๐ถ = ๐๐ถ = 1 ( 1 ๐๐ 377(10.9×10−12 ) 1,000 ๐ ) ๏ท ๐ฟ๐ช = ๐๐๐. ๐๐ ๐โฆ − ๐๐ REE – September 2008 14. A single circuit 745 kV, 60 Hz three-phase transposed transmission line is composed of four ACSR 1, 272, 000 cmils, 54/19. Pheasant conductors per phase with horizontal configuration. The phase spacing between the line center of the bundles is 14 m and the bundle spacing is 45 cm. The conductors have a diameter of 1.382 inch and a GMR of 0.5592 inch. Determine the capacitance per phase per km of the transmission line in microfarad per kilometer. A. 0.01424 B. 0.01266 C. 0.01583 D. 0.01234 Solution: 14 m 45 cm ๐ = 1.382 ๐๐ ๐บ๐๐ = 0.5592 ๐๐ ๐บ๐๐ท = 3√(14)(14)(28) ๏ท ๐บ๐๐ท = 17.64 ๐ ๐=( 1.382 ๐๐ 2 )( 2.54 ๐๐ 1 ๐๐ ) ๏ท ๐ = 1.76 ๐๐ 16 4 ๐บ๐๐ = √(1.76)4 (45)8 (45√2) ( ๏ท ๐บ๐๐ = 0.21823 ๐ ๐ถ๐ = 2๐๐๐ ๐บ๐๐ท ๐๐( ) ๐บ๐๐ = 2๐(8.85×10−12 ) ๐๐( ๏ท ๐ถ๐ = 0.01267 17.64 ) 0.21823 ๐๐น ๐๐ ๐๐๐ ∅ 1๐ 100 ๐๐ ) REE – September 2001 15. A 250 km transmission line has the following parameters: resistance per kilometer 0.05 ohm, capacitive reactance per kilometer 625, 000 ohms, and inductive reactance per kilometer 0.2 ohm. What is the series impedance? A. 37.5 + ๐150 โฆ B. 12.5 − ๐2, 450 โฆ C.๐๐. ๐ + ๐๐๐ โฆ D. 75.5 − ๐2, 450 โฆ Solution: โฆ ๐ ๐ก = (0.05 ๐๐ )(250 ๐๐) ๏ท ๐ ๐ก = 12.5 ๐โ๐๐ ๐๐ฟ = (0.2 โฆ ๐๐ )(250 ๐๐) ๏ท ๐๐ฟ = 50 ๐โ๐๐ ๐ = ๐ ๐ก + ๐๐๐ฟ ๏ท ๐ = ๐๐. ๐ + ๐๐๐ ๐๐๐๐ REE – April 2004 16. A 30-mile, three-phase transmission line is to deliver 20, 000 kW at 69 kV at 85% power factor. The line resistance is 0.324 ohm per mile and inductive reactance is 0.737 ohm per mile. What is the line loss? A. 1, 050 kW B. 376.7 kW C. 997 kW D. 1, 130.3 kW Solution: ๐ ๐ = (0.324 โฆ ๐๐๐๐ )(30 ๐๐๐๐) ๏ท ๐ ๐ = 9.72 ๐โ๐๐ ๐๐ฟ๐ = (0.737 โฆ ๐๐๐๐ )(30 ๐๐๐๐) ๏ท ๐๐ฟ๐ = 22.11 ๐โ๐๐ ๐ = ๐ ๐. ๐ ๐= (20,000)(103 ) 0.85 ๏ท ๐ = 23.529 ๐๐๐ด ๐ = √3๐๐ฟ ๐ผ๐ฟ ๐ผ๐ฟ = 23.529(106 ) √3(69,000) ๏ท ๐ผ๐ฟ = 196.876 ๐ด๐๐. ๐๐ฟ๐๐ ๐ = 3(๐ผ๐ฟ 2 )(๐ ๐ ) ๐๐ฟ๐๐ ๐ = 3(196.8762 )(9.72) ๏ท ๐ท๐ณ๐๐๐ = ๐, ๐๐๐. ๐๐ ๐พ๐๐๐๐ REE – September 2009 17. A 69 kV, three-phase transmission line is 50 km long. The resistance per phase is 0.3006 ohm per mile and the inductance per phase is 0.451 ohm per mile. Neglect the shunt capacitance. Using the short-line model, what is the voltage regulation when the line is supplying a three-phase load of 20 MVA at 0.80 lagging power factor at 69 kV? A. 6.7 % B. 7.2 % C. 7.6 % D. 6.3 % Solution: ๐ผ๐ = ๐ผ๐ = ๐∠๐๐๐ −1 ๐.๐ √3(๐๐ฟ ) 20(106 0∠๐๐๐ −1 0.8 √3(69,000) ๏ท ๐ผ๐ = 167.35∠ − 36.7° ๐ด ๐ ๐ = (0.3006 โฆ ๐๐๐๐ )( 1 ๐๐๐๐ 1.61 ๐๐ )(50 ๐๐) ๏ท ๐ ๐ = 9.3354 ๐โ๐๐ ๐๐ = (0.451 โฆ ๐๐๐๐ )( 1 ๐๐๐๐ 1.61 ๐๐ )(50 ๐๐) ๏ท ๐๐ = 14.01 ๐โ๐๐ ๐ = ๐ ๐ + ๐๐๐ ๏ท ๐ = 9.3354 + ๐14.01 ๐๐ ∅ = ๐๐ ∅ + ๐๐ผ๐ ๐๐ ∅ = 69,000 √3 + (9.3354 + ๐14.01)(167.35∠ − 36.7° ) ๏ท ๐๐ ∅ = 42, 501∠1.28° ๐๐๐๐ก๐ %๐๐ = ๐๐ ∅ = ๐๐๐ฟ −๐๐ ๐ฟ ๐๐ ๐ฟ 69,000 = ๐๐∅ −๐๐ ∅ ๐๐ ∅ √3 ๏ท ๐๐ ∅ = 39, 837. 17 ๐๐๐๐ก๐ %๐๐ = (42,504)−(39,837.17) 39,837.17 ๏ท %๐ฝ๐น = ๐. ๐ % 18. Shunt capacitance is neglected in A. short B. medium length transmission lines. C. long D. all of these REE – September 2007 19. A 69 kV, three-phase short transmission line is 16 km long. The line has a per phase series impedance of 0.125 + ๐0.4375 ๐โ๐ ๐๐๐ ๐๐. Determine the transmission efficiency when the line delivers 70 MVA, 0.80 lagging power factor at 64 kV. A. 98.75 % B. 96.36 % C. 94.67 % D. 95.90 % Solution: ๐๐๐ข๐ก = ๐ ๐. ๐ = (70)(106 )(0.8) ๏ท ๐๐๐ข๐ก = 56 ๐๐ ๐๐ = (0.125 + ๐0.4375 โฆ ๐๐ )(16 ๐๐) ๏ท ๐๐ = 2 + ๐6.97 ๐โ๐๐ ๐ผ๐ = ๐ผ๐ = ๐∠๐๐๐ −1 ๐.๐ √3(๐๐ฟ ) (70)(106 )∠๐๐๐ −1 0.8 √3(69,000) ๏ท ๐ผ๐ = 631.48∠ − 36.87° ๐ด๐๐. ๐๐ฟ๐๐๐ = 3(๐ผ๐ 2 )(๐ ) ๐๐ฟ๐๐๐ = 3(631.48)2 (2) ๏ท ๐๐ฟ๐๐๐ = 2.39 ๐๐ ษณ= ษณ= ๐๐๐ข๐ก ๐๐๐ข๐ก +๐๐๐๐ ๐ 56 ๐๐ 56 ๐๐+2.39 ๐๐ ๏ท ษณ = ๐๐. ๐๐ % REE – April 2001 20. The capacitive reactance of a 40 km, 34.5 kV line is 90, 000 ohms-kilometer. What is the total capacitive reactance of the line? A. 2, 250 โฆ B. 1.08 × 107 โฆ C. 6, 750 โฆ D. 3.6 × 106 โฆ Solution: ๐ = 40 ๐๐ ๐๐ถ = 90, 000 โฆ − ๐๐ ๐๐ถ๐ = ๐๐ถ๐ = ๐๐ถ ๐ 90,000 โฆ−๐๐ 40 ๐๐ ๏ท ๐ฟ๐ช๐ป = ๐, ๐๐๐ โฆ REE – September 2006 21. A three-phase short transmission line having per phase impedance of 2 + ๐4 ๐โ๐๐ has an equal line to line receiving end and sending end voltages of 115 kV, while supplying a load of 0.8 p.f leading. Find the power supplied by the line?...line to the load? A. 872.8 MW B. 860.2 MW C. 846.4 MW D. 822.4 MW Solution: ๐∅ = 115,000 √3 ๏ท ๐∅ = 66, 395.28 ๐๐๐๐ก๐ ๏ท ๐๐ ∅ = 66, 395.28 ∠0° ๐๐∅ = ๐๐ + ๐ผ๐ 66, 395.28∠0° = 66, 395.28 + (๐ผ๐ )(2 + ๐4) ๐๐ฟ = ๐๐๐ −1 ๐. ๐ = ๐๐๐ −1 (0.8) ๏ท ๐๐ฟ = 36.87° ๏ท ๐ผ๐ =/๐ผ๐ /∠36.87° ๐ด๐๐. ๏ท ๐ผ๐ =/๐ผ๐ /(1∠36.87°)๐ด๐๐. ๏ท ๐ผ๐ =/๐ผ๐ /(0.8 + ๐0.6) ๐ด๐๐. 66, 395.28∠0° = 66, 395.28 + (2 + ๐4)(0.8 + ๐0.6)(/๐ผ๐ /) (66, 395.28∠0°)2 = (66, 395.28 − 0.8/๐ผ๐ /)2 + (4.4/๐ผ๐ /)2 ๏ท /๐ผ๐ /= 5, 311.62 ๐ด๐๐. ๐๐ = √3๐๐ฟ ๐ผ๐ฟ ๐. ๐ = √3(115, 000)(5, 311.62)(0.8) ๏ท ๐ท๐น = ๐๐๐. ๐ ๐ด๐พ REE – May 2009 22. What is the maximum power that can be transmitted over a three-phase short transmission line having a per phase impedance of 0.3 + ๐0.4 โฆ if the receiving end voltage is 6, 351 volts per phase and the voltage regulation is not to exceed 5 percent? A. 103.5 MW B. 114.4 MW C. 108.9 MW D. 105.6 MW Solution: % ๐. ๐ = ๐๐ ∅ −๐๐ ∅ 0.05 = ๐๐ ∅ ๐๐ ∅ −6,351 6,351 ๏ท ๐๐ ∅ = 6, 668.55 ๐๐๐๐ก๐ ๐๐ ๐๐๐ฅ = 3(๐๐ ∅ ) ๐๐ ๐๐๐ฅ = ( ๐ 3๐๐ ∅ ๐2 (๐. ๐) = (๐๐ )(๐๐ ) )( ๐๐ ∅ ๐ ๐๐ ∅ − ๐ ๐๐๐๐ ) = ๏ท ๐ท๐น๐๐๐ = ๐๐๐. ๐๐ ๐ด๐พ 3(6,351)2 (6,668.55)(0.5) 0.52 [ 6351 − 0.3)] 23. When the load at the receiving end of a long transmission line is removed or the line is lightly loaded, the sending end voltage is less than the receiving end voltage. This phenomenon is called . A. Ferranti Effect B. Proximity Effect C. Kelvin Effect D. Skin Effect 24. Which of the following in not one of the classes of arresters? A. transmission class B. station class C. distribution class D. intermediate class REE – October 1996 25. A 60 Hz, three phase transmission line delivers 20 MVA to a load at 66 kV and 80 % power factor lagging. The total series impedance of each line is 15 + ๐75 ๐โ๐๐ . If nominal “pi” circuit is used, what would be the transmission efficiency if the admittance is ๐6 × 10−4 ๐โ๐๐ ? A. 90.8 % B. 91.7 % C. 93.5 % D. 92.6 % Solution: ๐ = ๐ ๐. ๐ ๐๐๐ข๐ก = (20)(106 )(0.8) ๏ท ๐๐๐ข๐ก = 16 ๐๐ ๐๐ ∅ = 66,000 √3 ๐๐ ∅ = 38.11 ๐๐ By KCL: ๐ผ๐ = ๐ผ๐ + ๐ผ๐ ๐ผ๐ = ๐∠๐๐๐ −1 ๐.๐ √3(๐๐ฟ ) = (20)(106 )∠๐๐๐ −1 0.8 √3(66,000) ๏ท ๐ผ๐ = 174.95∠ − 36.87° ๐ด๐๐. ๐ผ๐ = ๐ผ๐ = ๐๐ ∅ ๐๐ถ = ๐๐ ∅ ๐ 2 (38,110)(๐6×10−4 ) 2 ๏ท ๐ผ๐ = 11.43∠90° ๐ด๐๐. ๐ผ๐ = 174.95∠ − 36.87° + 11.43∠90° ๏ท ๐ผ๐ = 168.34∠ − 33.76° ๐ด๐๐. ๐๐๐๐ ๐ ๐๐ = 3(๐ผ๐ 2 )(๐ ) ๐๐๐๐ ๐ ๐๐ = 3(168.342 )(15) ๏ท ๐๐๐๐ ๐ ๐๐ = 1.275 ๐๐ ษณ= ๐๐๐ข๐ก ๐๐๐ข๐ก +๐๐๐๐ ๐ = 16 16+1.275 ๏ท ษณ = ๐๐. ๐๐ % 26. A single circuit, 60 Hz, three-phase transmission line is 300 miles long and has the โฆ ๐๐ป following parameters: ๐ = 0.30 ๐๐ , ๐ฟ = 2.10 ๐๐ , ๐ถ = 0.014 ๐๐น ๐๐ . What is the surge impedance loading of the line if the receiving end voltage is 132 kV? A. 45 MW B. 54 MW C. 15 MW D. 38 MW Solution: ๐๐ผ๐ฟ = ๐2 √ ๐ฟ ๐ถ 132,0002 ๐๐ผ๐ฟ = √ (2.1×10−3 ) (0.014×10−6 ) ๏ท ๐บ๐ฐ๐ณ = ๐๐. ๐๐ ๐ด๐พ REE – April 1997 27. In transmission lines, the most effective protection against lightning strikes is one of the following. Which one is this? A. lightning rods B. lightning arresters C. Peterson coils D. Overhead wires REE – September 2001 28. A combination of switch and fuse A. fuse cut-out B. relay C. safety switch D. circuit breaker REE – September 2007 29. A three-phase, 115 kV, 60 Hz, transmission line has a per phase series impedance of ๐ = 0.05 + ๐0.45 ๐โ๐/๐๐ and a per phase shunt admittance of −6 ๐ = ๐3.4 × 10 ๐ ๐๐๐๐๐๐ /๐๐. The line is 120 km long. Using the nominal “pi” line model. Determine the transmission line D constant. A. 0.999 + ๐0.001248 B. 0.968 + ๐0.001199 C. ๐. ๐๐๐ + ๐๐. ๐๐๐๐๐๐ D. 0.001212 Solution: ๐ท =1+ ๐ท =1+ ๐๐ 2 (๐3.4×10−6 )(120)(0.05+๐0.45)(120) 2 ๏ท ๐ซ = ๐. ๐๐๐ + ๐๐. ๐๐๐๐๐๐ REE – April 2011 30. A 132 kV, 60 Hz, three-phase transmission line delivers a load of 50 MW at 0.8 power factor lagging at the receiving end. The generalized constants of the transmission line are: ๐ด = ๐ท = 0.95∠1.4° ๐ต = 96∠78° ๐ถ = 0.0015∠90° Find the sending end line voltage. A. 160.9 kV B. 161.9 kV C. 162.9 kV D. 163.9 kV Solution: ๐๐∅ = ๐ด๐๐ ∅ + ๐ต๐ผ๐ ๐๐ ∅ = 132,000 √3 ๏ท ๐๐ ∅ = 76.21 ๐๐ ๐ผ๐ = ๐ผ๐ = ๐ ∠๐๐๐ −1 ๐.๐ ๐.๐ √3(๐๐ฟ ) 50(106 ) ∠๐๐๐ −1 0.8 0.8 √3(132,000) ๏ท ๐ผ๐ = 273.37∠ − 36.87° ๐ด๐๐ ๐๐∅ = (0.95∠1.4°)(76.21)(103 ) + (96∠78°)(273.37∠ − 36.87°) ๏ท ๐๐∅ = 94.09 ๐๐ ๐๐๐ฟ = √3(94.09) ๏ท ๐ฝ๐บ๐ณ = ๐๐๐. ๐ ๐๐ฝ 31. For a line terminated by its characteristic impedance, the reflected wave is equal to A. zero C. half of the incident wave . B. equal to incident wave D. twice of the incident wave 32. A three-core sheathed cable is being tested at 15 kV. The capacitance measured between any two conductors is 0.2 ๐๐น/๐๐. Determine the charging current per km of the cable at 60 Hz. A. 0.65 A B. 1.3 A C. 1.8 A D. 2.6 A Solution: ๐ถ๐ถ = ๐ถ๐ ๐๐ ๐ ๐๐๐๐๐ ๐ค๐๐กโ ๐ถ๐ ๐ถ๐ = 2๐ถ๐ถ = 2(0.2) ๏ท ๐ถ๐ = 0.4 ๐๐น/๐๐ ๐ผ๐โ๐๐๐๐๐๐ = ๏ท ๐∅ ๐๐ = 15,000 √3 1 2๐(60)(0.4)(10−6 ) ๐ฐ๐๐๐๐๐๐๐๐ = ๐. ๐ ๐จ๐๐. ๐ถ๐ถ = (๐ถ๐ )(๐ถ๐ ) ๐ถ๐ +๐ถ๐ = ๐ถ๐ 2 2๐ถ๐ = ๐ถ๐ 2 REE – October 1994 33. A lead sheath cable for underground service has a copper conductor (๐๐๐๐๐๐ก๐๐ = 0.35 ๐๐๐โ) surrounded by 0.2 inch wall of rubber insulation. Assuming a dielectric constant of 4.3 for rubber, calculate the capacitance of the cable. A. 1.01 ๐๐น/๐๐๐๐ B. 0.504 ๐๐ญ/๐๐๐๐ C. 0.76 ๐๐น/๐๐๐๐ D. 0.252 ๐๐น/๐๐๐๐ Solution: ๐ถ= 2๐๐๐ ๐๐ ๐ ln( ๐ ) ๐๐ ๐๐ = 0.35 2 = 0.175 ๐๐ ๏ท ๐๐ = 0.175 ๐๐ ๐๐ = ๐๐ + ๐ก = 0.175 + 0.2 ๏ท ๐๐ = 0.375 ๐๐ ๐ถ= 2๐(8.85×10−12 )(4.3) ๐๐( 0.375 ) 0.175 ๏ท ๐ถ = 3.14 × 10−10 ๐ถ๐ = 3.14 × ๐น ๐ 1๐ 5280 ๐๐ก −10 ๐น 10 ( )( ) ๐ 3.281 ๐๐ก 1 ๐๐๐๐ ๏ท ๐ช๐ป = ๐. ๐๐๐ ๐๐ญ/๐๐๐๐ REE – October 2000 34. What arrester rating shall be used to protect an 11 kV ungrounded system? A. 18 kV B. 16 kV C. 12 kV D. 9 kV Solution: ๐๐๐๐๐ ๐ก๐๐ ๐๐๐ก๐๐๐ = (๐๐๐๐ข๐๐๐ก๐๐๐ ๐๐๐๐ก๐๐)(๐ฃ๐๐๐ก๐๐๐ ๐๐๐ ๐ ๐๐๐๐ก๐๐)(๐∅ ) ๐๐๐๐ข๐๐๐ก๐๐๐ ๐๐๐๐ก๐๐ ๐๐๐ ๐ข๐๐๐๐๐ข๐๐๐๐: 1.05 ๐ด. ๐ = (1.05)(√3)( 11,000 √3 ) ๏ท ๐จ. ๐น = ๐๐. ๐๐ ๐๐ฝ REE – April 2002 35. The distribution system is 34.5 kV, grounded. Which arrester shall be installed to protect a distribution transformer on the system? A. 27 kV B. 30 kV C. 34.5 kV D. 38 kV Solution: ๐๐๐๐๐ ๐ก๐๐ ๐๐๐ก๐๐๐ = (๐๐๐๐ข๐๐๐ก๐๐๐ ๐๐๐๐ก๐๐)(๐∅ ) ๐๐๐๐ข๐๐๐ก๐๐๐ ๐๐๐๐ก๐๐ ๐๐๐ ๐๐๐๐ข๐๐๐๐: 1.35 ๐ด. ๐ = (1.35)( ๏ท 34,500 √3 ) ๐จ. ๐น = ๐๐. ๐๐ ๐๐ฝ 36. A transmission line delivers 1200 MW at 500 kV and 85 % power factor. The series impedance of the line 0.42 + ๐0.65 −๐0.12 × 106 ๐โ๐๐ ๐๐ 6 ๐โ๐๐ ๐๐ and the shunt impedance to neutral is . What is the velocity of propagation of the line? A. 560 × 10 ๐๐/โ๐ C. 750 × 106 ๐๐/โ๐ Solution: B. ๐๐๐ × ๐๐๐ ๐๐/๐๐ D. 510 × 106 ๐๐/โ๐ ๏ท ๐ฟ → ๐๐๐๐๐๐๐๐ก๐๐๐ ๐๐๐๐ ๐ก๐๐๐ก ๐ฟ = ๐ผ + ๐๐ฝ = √๐๐ ๏ท ๐ผ → ๐๐ก๐ก๐๐๐ข๐๐ก๐๐๐ ๐๐๐๐ ๐ก๐๐๐ก → ๐๐๐ก๐๐/๐๐๐๐ ๏ท ๐ฝ → ๐โ๐๐ ๐ ๐๐๐๐ ๐ก๐๐๐ก → ๐๐๐/๐๐๐๐ ๐๐ ๐ ๐ฟ = √๐๐ = √ ๐๐ โ 0.42+๐0.65 ๐ฟ=√ ๐(0.12×106 ) ๐ฟ = √6.45 × 106 ∠163.48° ๐ √/๐/∠๐ = (/๐/∠ 2 ) ๐ด √/๐/∠๐ = √/๐ด/∠๐ด๐ ๐บ 2 ๏ท ๐ฟ = 7.18 × 10−4 + ๐2.44 × 10−3 ๏ท ๐ผ = 7.18 × 10−4 ๐๐๐ก๐๐/๐๐๐๐ ๏ท ๐ฝ = 2.44 × 10−3 ๐๐๐/๐๐๐๐ ๐ ๐ฃ= ๐ฃ= ๐ฝ 2๐(60)(๐๐๐/๐ ๐๐) 1.61 ๐๐ ๐๐๐ 2.44×10−3 ๐๐๐๐ ( 1 ๐๐๐๐ )( 3,600 ๐ ๐๐ 1 โ๐ ) ๏ท ๐ = ๐๐๐ × ๐๐๐ ๐๐๐ 37. Which of the following protects a cable against mechanical injury during handling and laying? A. serving B. armouring C. sheath D. bedding 38. The transfer bus scheme has the following characteristics except one. Which one is this? A. It allows the disconnection of circuit breaker for maintenance without interrupting the service. B. It is more flexible. C. It allows better continuity of service as compared with the single bus D. It is more costly than that of the single bus system. 39. An overhead transmission line has a span of 300 m. it is supported by two towers of heights 20.5 m and 30.5 m, respectively. If the required clearance between the conductor and the ground midway between towers is 19 m and the weight of a conductor is 0.80 kg/m, what is the tension in the conductor? A. 1524 kg B. 1458 kg C. 1232 kg D. 1385 kg Solution: ๐ฅ ๐ด๐๐ด = ๐๐ ( ) − ๐(๐ฆ) 2 ๐๐ฅ 2 2 = ๐๐ฆ ๐๐ฅ 2 ๐ฆ= 2๐ ๏ท ๐1 = ๐๐ฅ1 2 2๐ ๏ท ๐ฅ1 = ๐ − ๐(๐−๐ฅ1 ) and ๐2 = and ๐ฅ2 = ๐ + โ๐ 2๐๐ 2๐ โ๐ 2๐๐ ๐ถ = โ1 − ๐1 + ๐2 19 = 20.5 − −1.5(2๐) 0.8 ๐๐ฅ1 2 2๐ 2 + ๐(๐−๐ฅ1 ) 2๐ = −๐1 + (150 − ๐1 )2 −3.75๐ = −๐1 2 + (1502 − 300๐1 + ๐1 2 ) −3.75๐ = 22, 500 − 300๐1 ๐1 = 150 − 3.75๐+22,500 300 (10)(๐) 2(0.8)(150) = 150 − 10(๐) 2(0.8)(150) ๏ท ๐ป = ๐๐๐๐. ๐๐ REE – September 2010 40. A system operates at 220 kVA and 11 kV. Using these quantities as base values, what is the base impedance of the system? A. 240 B. 220 C. 505 D. 550 Solution: ๐๐ = 220 ๐๐๐ด ๐๐ = 11 ๐๐ ๐๐ = ๐๐ = ๏ท ๐๐ 2 ๐๐ 11,0002 220,000 ๐๐ = ๐๐๐ 41. The conductor of a transmission line has a diameter of 19.6 mm and weighs 0.865 kg/m its ultimate strength is 8070 kg. If the permissible slant sag with a horizontal wind pressure of 3.91 ๐/๐๐2 is 6.28 m, calculate the maximum span between two consecutive level supports considering a factor of safety of 3. A. 171 m B. 296 m C. 342 m D. 592 m Solution: ๐.๐ ๐น. ๐ = 3= ๐= ๐ด.๐ 8,070 ๐ด.๐→๐ 8,070 3 ๏ท ๐ = 2, 690 ๐๐ค = ๐๐ ๐๐ค = ( 3.91 ๐ ๐๐2 )( 1 ๐๐ 1,000 ๐ )( 100 ๐๐ 2 ) (19.66 1๐ ๐๐)( 1๐ 1,000 ๐๐ ) ๏ท ๐๐ค = 0.766 ๐๐/๐ ๐๐ = √๐๐ค 2 + ๐๐ถ 2 ๐๐ = √0.7662 + 0.8652 ๏ท ๐๐ = 1.155 ๐๐/๐ ๐ฆ= ๐๐ ๐ 2 2๐ 1.155๐ 2 6.28 = ๐=√ 2(2,690) 6.28(2)(2,690) 1.155 ๏ท ๐ = 171 ๐ ๐๐๐ฅ ๐ ๐๐๐ = (๐ฅ)(2) = 2(171๐) ๏ท ๐๐๐ ๐๐๐๐ = ๐๐๐ ๐ 42. A string of three insulators is used to suspend one conductor of a 33 kV, three-phase overhead line. The air capacitance between each cap/pin junction and the tower is 1/10 of the capacitance of each unit. Determine the string efficiency. A. 86.8 % B. 88.6 % C. 68.8 % D. 78.6 % Solution: ๐ผ1 ′ ๐ถ๐ ๐1 ๐ผ1 a ๐ผ2 ′ ๐ผ2 ๐2 b ๐ผ3 ๐3 c ๐ถ๐ = 0.1 ๐ถ ๐พ๐ถ๐ฟ @ ๐: ๐ผ2 = ๐ผ1 + ๐ผ1′ ๐2 ๐๐ = ๐1 ๐๐ + ๐1 ๐๐๐ ; ๐๐ถ๐2 = ๐๐ถ๐1 + ๐๐ถ๐ ๐1 ๐ถ๐2 = ๐ถ๐1 + (0.1๐ถ)(๐1 ) ๏ท ๐2 = 1.1๐1 ๐พ๐ถ๐ฟ @ ๐: ๐ผ3 = ๐ผ2 + ๐ผ2′ ๐ถ๐3 = ๐ถ๐2 + (0.1๐ถ)(๐1 + ๐2 ) ๐3 = 1.1๐2 + 0.1๐1 ๐3 = (1. 1)2 ๐1 + 0.1๐1 ๏ท ๐3 = 1.31 ๐1 ษณ= ษณ= ๐1 +๐2 +๐3 3(๐3 ) ๐1 +1.1๐1 +1.31๐1 3(1.31๐1 ) ๏ท ษณ = ๐๐. ๐๐ % 43. A 500 kV line has a total corona loss of 280 kW. When energized at 230 kV, the corona loss is 42 kW. What will be the corona loss if used to transmit power at a voltage of 385 kV? A. 117 kW B. 153 kW C. 207 kW D. 183 kW Solution: ๐ถ๐๐ฟ๐ผ(๐∅ −๐0 )2 @ ๐๐๐ ๐ ๐ผ ๐ถ๐๐ฟ = ๐(๐∅1 −๐0 )2 @ ๐๐๐ ๐ ๐ผ๐ผ ๐ถ๐๐ฟ = ๐(๐∅2 −๐0 )2 ๐ถ๐๐ฟ1 ๐ถ๐๐ฟ2 = ๏ท ๐ถ๐๐ฟ3 ๐ถ๐๐ฟ1 ๐(๐∅1 −๐0 )2 ๐(๐∅2 −๐0 )2 42 = 500 −๐0 )2 √3 200 ๐( −๐0 )2 √3 ๐( ๐0 = 34.25 ๐๐ = ๐(๐∅3 −๐0 )2 ๐(๐∅1 −๐0 )2 ๐ถ๐๐ฟ3 = 280 ๏ท → 280 385 −34.25)2 ] √3 500 [( −34.25)2 ] √3 [( ๐ช๐ท๐ณ๐ = ๐๐๐. ๐๐ ๐๐พ REE – April 2001 44. The percent impedance of a line is 6 % at 34.5 kV and 100 MVA base. What is the ohmic impedance? A. 2.32 B. 3 C. 0.72 D. 1.2 Solution: ๐๐๐๐ ๐ = ๐๐๐๐ ๐ = ๐๐๐๐ ๐ 2 ๐๐๐๐ ๐ 34,5002 100(106 ) ๏ท ๐๐๐๐ ๐ = 11.9 ๐โ๐๐ ๐๐๐๐ก๐ข๐๐ = ๐๐.๐ข ๐๐๐๐ ๐ ๐๐๐๐ก๐ข๐๐ = (0.06)(11.9) ๏ท ๐๐๐๐๐๐๐ = ๐. ๐๐ REE – September 2009 45. A 20 kVA, 480 V, single phase generator supplies power to a load through a transmission line. The load impedance is 2 + ๐5 โฆ and the transmission line impedance is 1 + ๐3 โฆ. If a 1:2 step-up transformer is placed at the output of generator and a 10:1 step-down transformer is placed at the load of the transmission line, what is the per unit line current assuming transformers are ideal? A. 0.0862 p.u. B. 0.0953 p.u. C. 0.0851 p.u . D. 0.0970 p.u. Solution: 10 ๐2 = 1 ๏ท ๐2 = 10 ๐๐.๐ข = ๐2 (2 + ๐5) ๐๐.๐ข = 102 (2 + ๐5) ๏ท ๐๐.๐ข = 200 + ๐500 480 ๐๐ผ๐ผ = 1 2 ๏ท ๐๐ผ๐ผ = 960 ๐๐๐๐ก๐ ๐ผ๐ฟ = ๐๐ผ๐ผ ๐๐.๐ข ๐๐๐๐ ๐ = 960 (200+๐500)(1+๐3) ๏ท ๐ผ๐ฟ = 1.77∠ − 68.22° ๐ผ๐๐๐ ๐ = ๐๐๐๐ ๐ ๐๐๐๐ ๐ = 20,000 480 ๐ผ๐๐๐ ๐ = 20.83 ๐ด๐๐. ๐ผ๐.๐ข = ๏ท 1.77∠−68.22° 20.83 ๐ฐ๐.๐ = ๐. ๐๐๐ ๐. ๐. REE – April 2002 46. At a certain point in an electric network, the available fault MVA is 400. A 15 MVA, 34.5 kV, 2.5 % impedance, wye-grounded transformer is installed at that location. Determine the short circuit MVA at the secondary side of the transformer. A. 600 B. 625 C. 240 D. 500 Solution: ๐๐.๐ข = ๐๐.๐ข = ๐๐๐๐ ๐ ๐๐ ๐ 15 400 ๏ท ๐๐.๐ข = 0.0375 ๐. ๐ข. ๐๐.๐ข2 = ๐๐.๐ข1 + ๐๐.๐ข๐ ๐๐.๐ข2 = 0.0375 + 0.025 ๏ท ๐๐.๐ข2 = 0.0625 ๐. ๐ข. ๐๐ ๐2 = 15(106 ) 0.0625 ๏ท ๐บ๐๐๐ = ๐๐๐ ๐ด๐ฝ๐จ REE – April 2001 47. At a 34.5 kV substation, the available fault current is 10 p.u. What is the available fault MVA if the base is 50 MVA? A. 50 MVA B. 100 MVA C. 250 MVA D. 500 MVA Solution: ๐ผ๐น ๐.๐ข. = ๐ผ๐น ๐.๐ข. = 1 ๐1 ๐.๐ข 1 10 ๐.๐ข. ๏ท ๐ผ๐น ๐.๐ข. = 0.1 ๐. ๐ข ๐๐ ๐ = ๐๐ ๐ = ๐๐๐๐ ๐ ๐๐.๐ข 50,000,000 0.1 ๏ท ๐บ๐๐ = ๐๐๐ ๐ด๐ฝ๐จ 48. The causes of nearly all high voltage flashovers in transmission lines are due to one of the following. Which one is the following? A. high humidity B. dust and dirt C. corona D. lightning discharges REE – May 2010 49. Consider a system with sequence impedance of ๐(+) = ๐0.2577 ๐. ๐ข., ๐(−) = ๐0.2085 ๐. ๐ข., and ๐(0) = ๐0.14 ๐. ๐ข, determine the fault current at phase A for a single line to ground fault at A. A. – ๐6.4 ๐. ๐ข B. – ๐3 ๐. ๐ข C. – ๐11 ๐. ๐ข D. – ๐๐ ๐. ๐ Solution: ๐ผ๐น๐ถ = 3 (๐0.2577)(๐0.2085)(๐0.14) ๏ท ๐ฐ๐ญ๐ช = −๐๐ ๐. ๐ REE – April 2011 50. Consider a system with sequence impedances of ๐1 = ๐0.2577 ๐. ๐ข., ๐2 = ๐0.2085 ๐. ๐ข., and ๐0 = ๐0.14 ๐. ๐ข., determine the fault current ๐ผ๐1 for a single line to ground fault at A. A. – ๐2.13 ๐. ๐ข. B. – ๐1 ๐. ๐ข. C. – ๐3.67 ๐. ๐ข. D. – ๐๐. ๐๐ ๐. ๐. Solution: ๐ผ๐1 = ๐ผ๐2 = ๐ผ๐0 ๐ผ๐ = ๐ผ๐1 + ๐ผ๐2 + ๐ผ๐0 ๏ท ๐ผ๐ = 3๐ผ๐1 3 ๐ผ๐ = (๐0.2577)+(๐0.2085)+(๐0.14) ๏ท ๐ผ๐ = −๐4.9 ๐ผ๐1 = ๐ผ๐1 = ๐ผ๐ 3 −๐4.9 3 ๏ท ๐ฐ๐๐ = −๐๐. ๐๐ ๐. ๐ REE – September 2002 51. At a certain point in a 69 kV transmission line, the positive sequence impedance is ๐0.15 ๐. ๐ข., and the zero sequence impedance is ๐0.55 ๐. ๐ข. Calculate the fault current if a line to line fault occurs. The base is 50 MVA. A. 3, 511 A B. 1, 890 A C. 420 A D. 2, 414 A Solution: ๐ผ๐น๐ถ = ๐ผ๐น๐ถ = ๏ท ๐๐๐๐ ๐ (๐๐๐๐ ๐ )(๐1 ๐.๐ข +๐2 ๐.๐ข ) 50,000,000 (69,000)(−๐0.15+๐0.15) ๐ฐ๐ญ๐ช = ๐, ๐๐๐ ๐จ๐๐. 52. At a certain point in a system, the thevenin’s equivalent impedance of the network is 0.2 p.u. at a 100 MVA base. A 115/34.5 kV, 10 MVA transformer with 5 % impedance is tapped at this point. If a three-phase fault occurs at the secondary, find the fault current at the primary. A. 2390 B. 718 C. 1380 D. 1240 Solution: ๐๐ ๐.๐ข = (๐0.2)( 10 ๐๐๐ด 100 ๐๐๐ด ) ๏ท ๐๐ ๐.๐ข = ๐0.02 ๐1 ๐.๐ข = ๐0.02 + ๐0.05 ๏ท ๐1 ๐.๐ข = ๐0.07 1 ๐ผ๐น ๐.๐ข = ๐1 ๐.๐ข = 1 ๐0.07 ๐ผ๐น ๐.๐ข = 14.29 ๐. ๐ข ๐ผ๐ต ๐ = ๐๐ต √3๐๐ต ๐ = ๐๐ต √3(115,000) ๏ท ๐ผ๐ต ๐ = 50.20 ๐ด๐๐. ๐ผ๐น๐ถ ๐๐๐ = ๐ผ๐น ๐.๐ข + ๐ผ๐ต ๐ = (14.29)(50.2) ๏ท ๐ฐ๐ญ๐ช ๐๐๐ = ๐๐๐. ๐๐ ๐จ๐๐. REE – April 2001 53. The transformer used to serve a customer is rated 5 MVA, 13.8/0.48 kV, 5 % impedance. The cable connecting the breaker to the transformer has an impedance of 0.032 ohm per phase. What is the fault current if a three-phase fault occurs at the breaker? A. 8, 000 A B. 5, 000 A C. 6, 000 A D. 1, 200 A Solution: ๐๐๐๐ ๐ = ๐2 ๐๐๐๐ ๐ = 4802 5,000,000 ๏ท ๐๐๐๐ ๐ = 0.046 ๐. ๐ข ๐๐.๐ข = 0.032 0.046 ๐๐.๐ข = 0.7 ๐. ๐ข ๐๐.๐ข ๐ = 0.7 + 0.05 ๏ท ๐๐.๐ข ๐ = 0.75 ๐. ๐ข ๐ผ๐น๐ถ = ๏ท ๐๐ต √3๐๐ต ๐๐.๐ข ๐ = ๐๐ต √3(480)(0.75) ๐ฐ๐ญ๐ช = ๐๐๐๐. ๐๐ ๐จ๐๐. 54. NPC supplies energy to Clark Development Corporation at 69 kV from a 50 MVA transformer whose impedance is 4 %. The short circuit MVA at the primary of the transformer is 600 MVA. To limit the fault current, a three-phase limiting reactor is connected on the secondary of the transformer. What is the reactance of the reactor required to limit the short circuit MVA at the secondary to 200 MVA. A. 0.127 p.u. B. 0.167 p.u. C. 0.173 p.u. D. 0.139 p.u. Solution: ๐1 ๐.๐ข = ๐๐ต ๐๐๐ถ = ๐๐ต ๐๐๐ถ ๐๐๐ = 50 ๐๐๐ด 600 ๐๐๐ด ๏ท ๐1 ๐.๐ข = 0.083 ๐. ๐ข ๐1 ๐๐๐ = ๐1 ๐๐๐ = ๐๐ต ๐๐๐ถ 50 ๐๐๐ 200 ๐๐๐ด ๏ท ๐1 ๐๐๐ = 0.25 ๐. ๐ข ๐๐ ๐.๐ข = ๐1 ๐๐๐ − ๐1 ๐.๐ข − ๐๐.๐ข ๐ ๐๐ ๐.๐ข = 0.25 − 0.083 − 0.04 ๏ท ๐ฟ๐น ๐.๐ = ๐. ๐๐๐ ๐. ๐ REE – September 2009 55. A synchronous generator and motor are rated 30 MVA, 13.2 kV, and both have subtransient reactances of 20%. The line connecting them has a reactance of 12% on the base of the machine ratings. The motor is drawing 20, 000 kW at 80% power factor leading and a terminal voltage of 12.8 kV when a symmetrical three-phase fault occurs at the motor terminals. Find the three-phase fault current at the motor terminals. A. 10, 600 A B. 10, 150 A C. 10, 350 A D. 10, 800 A Solution: ๐0.12 ๐0.2 + - ๐0.2 + N ๐๐๐ป = 12,800 13,200 ๏ท ๐๐๐ป = 0.97 ๐ผ๐น ๐.๐ข = ๐ผ๐น ๐.๐ข = ๐๐๐ป ๐๐๐ป 0.97 ๐0.123 ๏ท ๐ผ๐น ๐.๐ข = −๐7.89 ๐. ๐ข ๐ผ๐น = ๐ผ๐น ๐.๐ข + ๐ผ๐๐๐ ๐ ๐ผ๐น = (7.89) + ( 30,000,000 √3(13,200) ๏ท ๐ฐ๐ญ = ๐๐, ๐๐๐. ๐๐ ๐จ๐๐.