Fire and Life Safety Report Building Name: Performing Arts Center California Polytechnic State University, Building 6 1 Grand Ave., San Luis Obispo, CA 93407 Prepared by: Kristen Dentici Cal Poly Fire Protection Engineering FPE 521: Egress Analysis and Design December 1, 2020 Table of Contents Introduction .................................................................................................................................................. 3 Building Description .................................................................................................................................. 4 Applicable Codes and Standards ............................................................................................................... 5 Fire Protection Systems ............................................................................................................................ 6 Occupancy Analysis ....................................................................................................................................... 6 Occupant Load Factor ............................................................................................................................... 6 Occupant Load .......................................................................................................................................... 7 Prescriptive Egress Analysis ........................................................................................................................ 13 Egress from Rooms ................................................................................................................................. 13 Egress from Floors................................................................................................................................... 16 Number and Arrangement of Exits ......................................................................................................... 23 Travel Distance, Common Path, and Dead-End Corridors .................................................................. 23 Number and Spacing of Exits .............................................................................................................. 26 Other Miscellaneous requirements ........................................................................................................ 32 Boiler room ......................................................................................................................................... 32 Assembly Fixed Seating ....................................................................................................................... 33 Exit Signage ............................................................................................................................................. 33 Fire Resistance and Interior Finish .............................................................................................................. 37 Fire Resistance Requirements................................................................................................................. 37 Interior Finish Requirements .................................................................................................................. 37 Performance-Based Egress Analysis ........................................................................................................... 40 Pre-Movement Time ............................................................................................................................... 41 The Protective Action Decision Model (PADM) .................................................................................. 41 Factors That Influence Occupant Behavior ......................................................................................... 42 Pre-Movement Time ........................................................................................................................... 43 Movement Time...................................................................................................................................... 43 Tenability Analysis Criteria ...................................................................................................................... 51 2|Page Introduction This report is intended to discuss and analyze the fire and life safety systems of the Cal Poly Performing Arts Center. This report will cover the egress requirements for the building. First, the occupant loads of rooms and floors are determined which will later be used to determine whether the provided exits are enough by a code-based analysis and a performance-based analysis. Additionally, locations of exit signs, interior finish and fire resistance requirements, and tenability performance criteria are discussed. Figure 1. Performing Arts Center from Southeast direction https://pactech.calpoly.edu/ 3|Page Building Description The Performing Arts Center (PAC) is located on the California Polytechnic State University, San Luis Obispo campus. The building is located west of Grand Ave. and is near a large parking garage and another smaller theater as shown below. Figure 2. Satellite View of PAC (circled in red) with surrounding buildings and roads The PAC opened in September of 1996 and includes The Christopher Cohan Center including Harman Hall, a 180-seat classroom Philips Hall, and the Rehearsal/Multi-purpose Pavilion. Alex and Faye Spanos theater is located in the back of the PAC, and the Christopher Cohan Center is located adjacent to the Davidson Music Center but neither are included in this report as they are considered separate buildings. The following provides more information on the construction of the building: • • • Number of stories: 4 total, 1 below grade Date of Construction: 1996 Construction Type: IB The building consists of multiple occupancy classifications, with the main occupancy being A-1 in Harman Hall. The following tables specify all the occupancy types found in the building and a summary of the occupant load on each floor. 4|Page Table 1. Occupancy Classifications Occupancy Classification Theater Lecture Halls Exhibition Halls Name A-1 A-3 A-3 Rooms Included Harman hall Philips Hall Lobby, Rehearsal Pavilion Business B Accessory areas (dressing rooms, security, communications) Storage S-2 Storage Areas, Lift Pit Table 2. Occupant load by floor Floor Trap Room/Pit Level Orchestra Main Entry/Lobby Level Lower Balcony Level Upper Balcony Level Use Storage, Equipment, Chair Wagon Lift Occupant Load Main Hall, Loggias, Stage, Dressing Rooms, Rehearsal Pavilion, Classroom Dress Circle, Lobby, Reception, Concessions Balcony, Lounge, Control and Sound Room Balcony, Storage Total: 33 1901 774 244 158 3110 The building construction is considered Type IB. The following fire resistance hour ratings are required for building elements (other requirements for stairs and corridors discussed later in report): • • • • • Primary Structural Frame: 2 Bearing Walls (exterior and interior): 2 Nonbearing walls and partitions: 0 Floor construction: 2 Roof construction: 1 These requirements do not relate specifically to this report, however they have an impact on requirements for enclosed shafts. Applicable Codes and Standards The PAC was built to the required codes at the time of permitting, as follows: • • • • California Building Code (1992) California Fire Code (1992) California Electrical Code (1991) California Mechanical Code (1992) 5|Page • California Plumbing Code (1991) While the building was built to these specifications, they will not be referenced for this report. For the purposes of this report, the current version (2018) of the International Building Code (IBC) will be used. Fire Protection Systems In order to perform an egress analysis of the Performing Arts Center, some of the basic fire protection systems must be addressed as they affect design specifications. The PAC includes an automatic sprinkler system, fire alarm and voice communications system, and smoke protected assembly seating. The fire sprinkler system for the building is based on the hazard groups present. The office areas and auditorium are classified as Light Hazard Occupancies; the storage areas, kitchen, and mechanical equipment areas are classified as Ordinary Hazard Group 1; and the stage and orchestra pit are classified as Ordinary Hazard Group 2. The building is equipped with a fire detection and alarm system. The fire alarm system consists of the following detection devices: manual pull stations, automatic sprinkler water flow indicators, automatic smoke detectors, and automatic heat detectors. Manual pull stations are located adjacent to all stair doors and stage exits and within 200 feet along each exit path. Upon alarm activation, a pre-recorded message announcement will be played. Additionally, strobe devices (visual warning devices) are placed in restrooms, corridors, lobbies, meeting rooms, and other public areas. Finally, the building is equipped with assembly smoke protected seating in the form of stage smoke removal and fire barrier. The fire barrier is provided by a proscenium wall with 2-hour fire rated construction. It should be noted that only two openings of less than 25 sq. ft. are allowed into the auditorium from the stage. In addition to the fire barrier, smoke removal is provided through gravity vents located near the center and at the highest point above the stage. The vents are activated by a fusible link and cover more than 5% of the stage area, as required by code. These fire protection systems will be discussed further in their role in the design of egress and life safety systems. Occupancy Analysis In order to perform both the prescriptive and performance analysis, the occupant load of each room and floor must be calculated. The occupant load of each room is calculated by one of two methods: occupant load factor and area, or number of fixed seats. Occupant Load Factor The occupant load factor for each room is based on Table 1004.5 in the IBC. There are two types of floor areas that can be used in calculations: net and gross. Gross floor area refers to “the floor area within the inside perimeter of the exterior walls of the building under consideration, exclusive of vent shafts and courts, without deduction for corridors, stairways, ramps, closets, the thickness of interior walls, columns or other features.” Net floor area refers to “the actual occupied area not including unoccupied accessory areas such as corridors, stairways, ramps, toilet rooms, mechanical rooms, and closets.” When there is multiple occupant load factors in a building that combine net and gross, the following calculations are made: 6|Page • • Apply the gross area figure to the gross area of the portion of the building devoted to the use for which the gross area figure is specified, and Apply the net area figure to the net area of the portion of the building devoted to the use for which the net area figure is applied. The following occupant load factors were used: • • • • • • • Main Hall, loggias, Dress Circle, balconies, classrooms: Assembly with fixed seating, number of fixed seats Storage, machine rooms/electrical/mechanical, etc. (where included), equipment room: Accessory storage areas, mechanical equipment room, 300 gross sq.ft/person Piano, stage: Stage, 15 net sq.ft./person Lobby, founder’s lounge: Unconcentrated assembly, 15 net sq.ft./person Restrooms (where included), wardrobe, service, workroom, reception: Business, 150 gross sq.ft./person Concession, communications: Concentrated business, 100 gross sq.ft./person Dressing Rooms: Locker room, 50 gross sq.ft./person Rooms that are not included in net calculations but are included in gross calculations were included or not included based on the nearest adjacent occupancy. For bathrooms connected/adjacent to areas such as dressing rooms, they were included in the calculation. However, for bathrooms located near the Main Hall areas, they were not included because they were considered part of the net occupancy area. Similarly, mechanical rooms, electrical rooms, etc. were included if they were separated from any other occupancy, or if they were in the area with gross area measurements. Occupant Load The occupant load for each room was calculated by dividing the appropriate floor area by the occupant load factor and rounding up. Rounding up provides a more conservative approach to simply rounding or rounding down. The occupancies and occupant loads for each room as well as stairs and corridors are shown in the following figures by floor. To obtain floor occupant loads, the room occupancies were summed. 7|Page Figure 3. Trap room/lift pit level room occupancies. 8|Page Figure 4. Orchestra level room occupancies. Note: Restrooms adjacent to cast prep areas are included in those rooms occupant load. 9|Page Figure 5. Main Entry/Lobby level room occupancies. 10 | P a g e Figure 6. Lower Balcony level room occupancies. 11 | P a g e Figure 7. Upper Balcony level room occupancies. 12 | P a g e Prescriptive Egress Analysis The prescriptive egress analysis for this building is based on the IBC Chapter 10. In order to meet the requirements of the IBC, egress capacity is compared to occupant load for each room and for each floor as a whole. In addition, arrangement of exits in order to account for acceptable common path distance, travel distance, dead end length, and separation of exits is checked. In certain areas and on certain floors, a specific number of exits are required, and this was checked as well. Finally, recommendations for the placement of exit signage will be included. Prescriptive egress capacity is based on the size of egress components such as doors, corridors, ramps, and stairs. Since the building is equipped with an automatic sprinkler system throughout and voice alarm communication, the egress capacities are allowed to be increased per IBC Chapter 10. Stairway capacity is calculated with a capacity factor of 0.2 inch per occupant and other egress components such as door capacities are calculated with a capacity factor of 0.15 inch per occupant. Egress from Rooms The calculation of room occupant load was discussed earlier in this report. Next, the doors in each room were measured and divided by the capacity factor to determine the egress capacity for each room. The capacity of egress from each room must be equal to or greater than the occupant load for the room. The following tables summarize the egress capacity of each room and whether the capacity is enough. Additionally, in spaces where one form of egress led to another, the egress component with lower capacity was used. Table 3. Room egress capacity for trap room and pit level. Floor Room Use 10 Trap Room (Below) 11 Trap Room 12A/B Trap Room and Lift Pit Capacity Occupant Egress Factor Exit Load in Sufficient? Available (in./perso Capacity Room Notes n) Need to egress room 10&room 11. 8 2 X 36" Doors 0.15 480 YES Capacity needed: 19 11 132",36" Doors 0.15 1120 YES 12 Storage 1 36" Door 0.15 240 YES Machine Room 13 Pump Room 14 Electrical 1 36" Door 1 36" Door 2 36" Door 0.15 0.15 0.15 240 YES 240 YES 240 YES 15 Electrical 1 72" Door 0.15 480 YES 16 Mech. Room 1 36" Door 0.15 240 YES 17 Plumbing Room 2 72" Door 0.15 480 YES 18 Mech. Room 3 72" Door 0.15 480 YES 19 Electrical 2 36" Door 0.15 240 YES Room 11 egress through room 10 Need to egress room 12 & 12A/B. Capacity needed: 2 Room 12A/B egress through room 12 Egress directly to public way. Not included in floor level calculation Egress directly to public way. Not included in floor level calculation Egress directly to public way. Not included in floor level calculation Egress directly to public way. Not included in floor level calculation Egress directly to public way. Not included in floor level calculation 13 | P a g e Table 4. Room egress capacity for orchestra level. Floor Room 100 101 101A 101B 101C 101D 102 103 104 105 106 107 108 109 110 110A 111 111A 112 113 113A Orchestra 114 115 116 117 118 119 120 120A/B 121 122 123 Use Lounge/Galleries Occupant Egress Load in Available Room 0 Main Hall Storage Loggia East Loggia West Piano Stage Restroom Electrical Storage Storage Storage Food Handling Green Room Dressing Room Dressing Room Dressing Room Dressing Room Manager/Receiving Security Security Wardrobe Dressing Room Wardrobe Dressing Room Dressing Room Dressing Room Dressing Room Restroom Dressing Room Wardrobe Janitor 846 1 10 11 12 270 6 1 1 3 1 5 4 2 2 2 2 1 1 1 4 6 5 13 8 13 9 2 4 4 1 124 Classroom 180 124B 125 126 127 Classroom Restroom Restroom Storage 1 1 1 1 128 129 130 131 132 133/134 Rehearsal Pavilion Janitor Electrical Storage Restroom Restroom 455 1 1 1 3 5 60" Door, 2X 144" Stair, 2 X 66" Doors 2 X 36" Door, 2 X 72" Door 72" Door 39" Stair 39" Stair 72" Door 5 X 36" Door 36" Door 32" Door 32" Door 32" Door 32" Door 32" Door 32" Door 32" Door 32" Door 32" Door 32" Door 32" Door 32" Door 32" Door 90" Door 32" Door 2 X 90" Door 32" Door 32" Door 32" Door 32" Door 32" Door 32" Door 90" Door 32" Door 32" Door, 72" Door 90" Door, 66" Door 32" Door 32" Door 32" Door 108" Door, 4 X 42" Door 32" Door 32" Door 32" Door 32" Door 32" Door Capacity Factor Exit Sufficient? (in./perso Capacity n) Notes See floor Where doors/corridors lead to level stairs, the most conservative calculation capacity along path is used 0.15 0.15 0.2 0.2 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15 1440 480 195 195 480 1200 240 213 213 213 213 213 213 213 213 213 213 213 213 213 600 213 1200 213 213 213 213 213 213 600 213 YES YES YES YES YES YES YES YES YES YES YES YES YES YES YES YES YES YES YES YES YES YES YES YES YES YES YES YES YES YES YES 693 YES 0.15 0.15 0.15 0.15 1040 213 213 213 YES YES YES YES 0.15 0.15 0.15 0.15 0.15 0.15 1840 213 213 213 213 213 YES YES YES YES YES YES Egress through main hall Egress shared with main hall Egress shared with main hall Egress through main hall Required capacity includes 110A Egress through 110 Required capacity includes 111A Egress through 111 Required capacity includes 113A Egress through 113 Required capacity includes 124B Egress through 124 14 | P a g e Table 5. Room egress capacity for entry and lobby level. Floor Room Entry Lobby Use 200 Lobby 593 201 201A 201B Dress Circle Organ Royal Box 133 1 6 202 203 203A 204 Concession Boiler Room Boiler Room Electrical Communications Room 205 206 207 207A 208 (A,B,C,D) Capacity Factor Exit Sufficient? (in./perso Capacity n) Occupant Load in Egress Available Room Mech. Room Electrical Electrical Reception 9 X 60" Door, 32" Door 2 X 32" Door 32" Door 32" Door 0.15 3813 YES 0.15 0.15 0.15 426 YES 213 YES 213 YES 32" Door 3 3 72" Door 2 2 X 32" Door 4 72" Door 0.15 213 YES 0.15 0.15 0.15 480 YES 426 YES 480 YES 32" Door 0.15 213 YES 0.15 613 YES 0.15 0.15 0.15 426 YES 426 YES 360 YES 4 6 9 3 7 60" Door, 32" Door 2 X 32" Door 2 X 32" Door 2 X 36" Door Notes Egress capacity including 203A Egress through 203 Converge into 2 stairs (44" and 36"), capacity 400 (acceptable) A,B,C,D converge into main room Table 6. Room egress capacity for lower balcony level. Floor Room Use 300 Circulation 301 Lower Balcony Control/ Sound Room 303 Storage 302 Balcony Level 304 Founder's Lodge 305 306 307 308 309 310 311 312 313 314 Service Restroom Storage Main Communication Room Organ Blower Room Electrical Storage Workroom Restroom Storage Capacity Occupant Egress Factor Exit Load in Sufficient? Available (in./perso Capacity Room n) 172 4 X 32" Door 0.15 5 30" Door 0.15 1 30" Door 0.15 Notes See floor 350 level Door leads to stair but calculation stairs are limiting factor Doors connect to stairs 852 YES but doors are limiting factor Stairs lead to door but 200 YES door is limiting factor 200 YES 45 66" Door 0.15 440 YES 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.2 0.15 0.15 200 200 200 200 200 480 200 210 200 200 0 70" Stair 2 3 1 2 1 1 1 6 3 1 30" Door 30" Door 30" Door 30" Door 30" Door 2 X 36" Door 30" Door 42" Stair 30" Door 30" Door 0.2 YES YES YES YES YES YES YES YES YES YES 15 | P a g e Table 7. Room egress capacity for gallery (upper balcony) level. Floor Room Use 400 Circulation Gallery 401 402 403 404 405 406 Upper Balcony Storage Storage Storage Equipment Room Equipment Room Capacity Occupant Egress Factor Exit Load in Sufficient? Notes Available (in./perso Capacity Room n) 0 32" Door 152 2 1 1 1 1 4 X 30" Doors 30" Door 30" Door 30" Door 30" Door 30" Door 0.15 0.15 0.15 0.15 0.15 0.15 0.15 See floor level 213 calculation 800 200 200 200 200 200 YES YES YES YES YES YES Doors lead to stairs but doors are limiting factor As seen in the above tables, the PAC meets the 2018 IBC requirements for room egress capacity. However, it should be noted that the IBC has a minimum door clear width of 32” (IBC 1010.1.1) and a minimum stair width of 44” (IBC 1011.12). Some doors in this building are equipped with 30” doors, so while they serve a sufficient capacity for the rooms, they are not large enough to meet the overall door requirement. Additionally, some rooms may require a minimum number of doors and door separation, which will be discussed later in this report. Egress from Floors In addition to requiring sufficient capacity for egress from each room, each floor is required to provide sufficient capacity for the total occupant load on that floor. The following figures show the egress paths from main occupied areas to floor level exits. 16 | P a g e Figure 8. Floor level exits for pit level and trap room level. 17 | P a g e Figure 9. Floor level exits for orchestra level. 18 | P a g e Figure 10. Floor level exits for main entry and lobby level. 19 | P a g e Figure 11. Floor level exits for balcony level. 20 | P a g e Figure 12. Floor level exits for gallery (upper balcony) level. Next, the floor level exit capacity was found by calculating the individual capacity of each floor level exit and summing the capacities. Where there were two egress components in series, the lowest capacity was used. The following table summarize the occupant load of each floor and the egress capacity that is available. Additionally, some floors will require a certain number and spacing of exits which will be addressed in the following section. Table 8. Floor egress capacity for trap room and pit level. Floor Trap Room and Lift Pit Door/ Occupant Doors/ Corridor Stairs Load Corridors Capacity 24 2 X 36" 480 2 X 48" Floor Capacity Stair (Smallest value Capacity between doors, corridors, stairs) 480 480 Sufficient? YES 21 | P a g e Table 9. Floor egress capacity for orchestra level. Occupant Load Floor Orchestra 1901 Egress Available Floor Exit (Smallest Sufficient? Capacity capacity along path) 3 X 72" Door, 32" Door, 2 X 66" Door, 90" Stair 2983 YES Table 10. Floor egress capacity for main/entry level. Egress Available Occupant (Smallest Load capacity along path) Floor Main/Entry Level 774 Floor Exit Sufficient? Capacity 9 X 60" Door, 32" Door 3813 YES Table 11. Floor egress capacity for balcony level. Floor Balcony Level Egress Available Occupant (Smallest Load capacity along path) 244 3 X 70" Stair Floor Exit Sufficient? Capacity 1050 YES Table 12. Floor egress capacity for gallery (upper balcony) level. Floor Gallery (Upper Balcony) Level Egress Available Occupant (Smallest Load capacity along path) 244 3 X 32" Door Floor Exit Sufficient? Capacity 639 YES 22 | P a g e As seen in the tables above, the exit capacity of each floor was found to be sufficient. In addition to the requirement for each floor to have sufficient egress, since this building’s main occupancy is assembly, the main exit is required to meet half of the occupant load for the building (IBC 1029.2). This building has multiple main exits spread along the perimeter of the building which serve a capacity of 3813 occupants. This exceeds the total building occupancy of 3110 occupants and therefore meets the requirement. Number and Arrangement of Exits In addition to the exits being sufficient for the capacity of occupants in the building, the locations and numbers of exits must be considered in the following manners: travel distances, common paths, and dead ends; minimum number of exits from highly occupied spaces; and spacing of multiple exits. Travel Distance, Common Path, and Dead-End Corridors Chapter 10 of the IBC specifies maximum lengths for travel distance to an exit, common path lengths, and dead-end corridor lengths based on the occupancy and other factors for the building. A common path of egress travel is defined by the IBC as “that portion of exit access travel distance measured from the most remote point of each room, area, or space to that point where the occupants have separate and distinct access to two exits or exit access doorways.” Therefore, common path requirements only apply to spaces with one exit. The travel distance is the distance that it takes an occupant to reach the exterior of the building or a protected path of egress travel (such as a smoke protected stairway). Since this building does not separate the occupancies on each floor, the most restrictive requirements must be met which are those for an assembly occupancy except for the trap room and pit level which is storage occupancy. The following table provides the requirements for the three types of measurements considered for assembly occupancies. Table 13. Travel distance requirements for assembly occupancy. Measurement Requirement Code Section Common Path 75 feet 1006.2.1 Travel Distance 250 feet 1017.2 Dead End 20 feet 1020.4 For smoke protected assembly seating, the requirements for travel distance are slightly different. The total exit distance must be less than 400 feet, with up to 200 feet to reach a vomitory or concourse and up to 200 feet to reach an exit. For the trap room and pit level, the largest travel distance is shown below. Figure 13. Trap room and pit level longest travel distance. 23 | P a g e The trap room and pit level is subject to the requirements for a storage occupancy which are as follows: common path, 100 feet; and travel distance, 250 feet. There are no dead-end corridors on this floor. As seen in the above figure, the largest travel distance in the trap room and pit level is 145 feet, which is acceptable. The largest common path in this room is 84 feet which is also acceptable. Figure 14. Orchestra level longest common path and travel distance. On the orchestra level, the longest travel distance is 199 feet which originates in the main hall and exits near the classroom. This is shorter than the maximum allowed travel distance for smoke-protected assembly seating of 400 feet. The longest common path is found in the restroom in the lower left corner and is 60 feet which is lower than the maximum allowed. There are no dead ends on this level. 24 | P a g e Figure 15. Main/entry level longest travel distance. On the main lobby level, there are not many long egress paths. There are no large rooms with a single exit, so the common path requirement is met. The longest travel distance on this level is from the dress circle seating, which is 142 feet in length and less than the maximum of 400 feet. There are no dead ends on this level. Figure 16. Balcony level longest travel distances. On the balcony level, there are no lengthy common paths and no dead-end corridors. The longest travel distance is from the lower balcony seating and is 139 feet, which is less than the 400-foot maximum. 25 | P a g e The gallery (upper balcony) level is very similar in construction to the lower balcony level and none of the three requirements were exceeded on this level either. Therefore, each level of the PAC meets the requirements for travel distance, common path, and dead-end corridors. Number and Spacing of Exits In addition to limiting the travel distances, there are requirements for the number and spacing of exits within areas of floors and on floors. For rooms of assembly occupancy and less than 50 occupants, one exit per room is permitted so long as the common path does not exceed 75 feet. For business and storage occupancies that are sprinkler protected, one exit is permitted so long as the common path does not exceed 100 feet. All common paths were already checked and did not exceed 75 feet. Additionally, all spaces with one exit had occupant loads of less than 50. For occupant loads greater than this and up to 500, 2 exits are required. For occupant loads between 501 and 1,000 three exits are required and four are required for occupant loads greater than 1,000 (IBC 1006.2). Balconies, galleries or press boxes having more than 50 seats must have two means of egress with one from each side (1029.5). In addition to providing multiple exits, two of the exits must be placed at least one third of the overall diagonal of the space apart. When there are three or more exits, the additional exits must be spaced reasonably. The following spaces require more than one exit. The list gives the number of exits supplied and the number of exits (required), as well as figures with exit spacing: • Main Hall: 4 provided (3 required) • Stage: 5 provided (2 required) 26 | P a g e • Rehearsal Pavilion: 4 provided (2 required) • Classroom: 2 provided (2 required) • Dress Circle: 2 provided (2 required) 27 | P a g e • Lobby: 5 provided (3 required, however more will likely be required for egress from floor, see next section) • Lower Balcony: 4 provided (2 required) • Upper Balcony: 4 provided (2 required) 28 | P a g e All of the areas have a proper number and spacing of exits. Chapter 10 of the IBC also states requirements for the amount and spacing of floor level exits. The table below shows the required number of exits based on the floor occupant load. Table 14. IBC Table 1006.3.2. Number of exits required from each story. Additionally, a single exit may be allowed in certain occupancies with low loads. For this building, this applies to the trap room and pit level, based on IBC Table 1006.3.3(2). The same separation of exits requirement as above are required on a floor level as well. Based on this information, the following is the required number of exits from each story along with the number provided and a figure showing separation distance: • 29 | P a g e • Trap room/pit level: 2 provided (1 required) • Orchestra level: 7 provided (4 required) 30 | P a g e • Main/entry level: 10 provided (3 required) • Lower balcony level: 3 provided (2 required) 31 | P a g e • Gallery (upper balcony) level: 3 provided (2 required) As seen, each story of the PAC meets the requirement for number of exits and exit separation. Other Miscellaneous requirements Boiler room In addition to other requirements, boiler rooms are required to have two exit doors when the area is over 500 square feet and any fuel-fire equipment exceeds 400,000 BTU. One of the exits can be a fixed ladder and the exits must be at least half the diagonal of the space apart. The figure below shows that the boiler room located on the entry/lobby level of the building meets these requirements. Figure 17. Boiler room exit layout. 32 | P a g e Assembly Fixed Seating In assembly occupancy with fixed seating, IBC Chapter 10 specifies a capacity of the aisles, similarly to how the capacity of a door is calculated. The capacity of the aisle is determined by multiplying the width of the aisle by a factor from IBC table 1029.6.2 (See table below) because the assembly seating is smoke protected. The factor used is based on total number of seats within the space exposed to smoke-protected environment and the type of aisles. Table 15. IBC Table 1029.6.2, capacity factor for aisles in assembly smoke-protected seating. Since the Main Hall seats less than 5,000 persons and the aisles have a slope of 1:12, the capacity factor of 0.15 inches/person is used. In the main hall seating area, the aisles are 44 inches wide on each side of the seating areas, therefore each aisle can serve a capacity of 293 occupants. These aisles must also comply with the requirements of 1029.9.1 which specifies a minimum aisle width for aisles leading to an exit to be 42”, which is met. For seating in rows, there is also a requirement for the clear width of the aisles between the rows. The required width of the aisle is based on the number of seats and whether there are aisles or doorways at one or both ends of the row. For rows where there is an aisle at both ends, the minimum clear width is 12 inches, and the row width must be increased by 0.3 inch per seat beyond 14 seats. For rows where there is only an aisle or door at one end, the row width is increased by 0.3 inches from 12 inches for each seat in addition to 7. The minimum clear width is not required to exceed 22 inches, however. In the PAC, the balcony and dress circle seating have 22” clear widths and therefore meet the requirement. In the orchestra level, the longest row is 42 seats, which means that the required clear width is 20.4 inches. The orchestra seating has 21-inch clear width aisles, so this requirement is met. Exit Signage Chapter 10 of the IBC provides requirements for the locations of exit signs within a building. According to IBC 1013.1, exit signs must be placed in the following locations: • • • • Exit and exit access doors Path of egress travel to exits and within exits to indicate direction of travel when path/exit are not immediately visible Must be placed such that at any point in an exit access corridor, there is an exit sign within 100 feet or the listed viewing distance (whichever is less). Not required in rooms or areas that only require one exit or exit access. Following these requirements, suggest locations for exit signs are provided in the figures following. 33 | P a g e Figure 18. Exit sign locations for lift pit and trap room level. Figure 19. Exit sign locations for orchestra level. 34 | P a g e . Figure 20. Exit sign locations for main entry/lobby level. 35 | P a g e Figure 21. Exit sign locations for lower balcony level. Figure 22. Exit sign locations for gallery (upper balcony) level. 36 | P a g e Fire Resistance and Interior Finish Fire Resistance Requirements The fire resistance requirements for egress components is given in Chapter 10 of the IBC. The required corridor fire resistance is given by the table below. Table 16. (IBC Table 1020.1) Required fire-resistance rating for corridors. Based on this, the PAC is not required to have a fire resistance rating in corridors since it is assembly occupancy and equipped by an automatic sprinkler system. The stairways and shafts in this building are required to be protected by a fire resistance rating of at least 2 hours according to IBC 713.3 because they connect 4 stories or more. Per IBC Table 716.1 (2), the doors connecting to the 2-hour shafts must be 1 ½ hour rated. Interior Finish Requirements The interior finish requirements for this building are based on IBC Chapter 8. There are some general and some occupancy specific requirements. Floor and wall finishes are tested using the following methods: • • NFPA 286: o Description of test: Full-scale room-corner test, wall materials installed on walls or ceiling material installed on ceiling. 40 kW gas burner is placed in corner for first five minutes, then 160 kW fire for additional 10 minutes o Acceptance criteria (IBC 803.1.1.1): ▪ During the 40 kW exposure, flames shall not spread to ceiling. ▪ The flame shall not spread to the outer extremity of the sample on any wall or ceiling. ▪ Flashover, as defined in NFPA 286, shall not occur. ▪ The peak heat release rate throughout the test shall not exceed 800 kW. ▪ The total smoke released throughout the test shall not exceed 1,000 m2. o Acceptance above is considered to also comply with Class A requirements of ASTM E84/UL 723. NFPA 265: o Description of test: Room-corner test for textile wall covering installed on walls. Gas burner is placed in corner at 40 kW for 5 minutes then 150 kW for an additional 10 minutes. 37 | P a g e o • Acceptance criteria (IBC 803.5.1.1): ▪ During the 40 kW exposure, flames shall not spread to the ceiling. ▪ The flame shall not spread to the outer extremities of the samples on the 8-foot by 12-foot walls. ▪ Flashover, as defined in NFPA 265, shall not occur. ▪ The total smoke release throughout the test shall not exceed 1,000 m2. ASTM E84/UL 723: o Description of test: Steiner tunnel test. Horizontal test specimen is placed in a tunnel and the flame spread down the tunnel is recorded. Smoke-developed index is also measured. Results are in terms of Class A, B, or C with A being the lowest flame spread. o Description of classes (IBC 803.1.2): ▪ Class A: Flame spread index 0-25; smoke-developed index 0-450. ▪ Class B: Flame spread index 26-75; smoke-developed index 0-450. ▪ Class C: Flame spread index 76-200; smoke-developed index 0-450. Certain interior finishes, such as high-density polyethylene (HDPE), have specific requirements that are held across all occupancies. This is summarized in the table below. 38 | P a g e Table 17. Interior ceiling and wall finish requirements for all occupancies Finish Material/Type Test Standard (Requirement) Material less than 0.036 Not required to be tested inch thick Foam plastics Not allowed (Exception: IBC 2603.9) NFPA 265: Meet all requirements listed in IBC 803.5.1.1 (see above) NFPA 286: Meet all requirements listed in IBC Textile wall covering 803.1.1.1 (see above) ASTM E84/UL 723: Class A and must be protected with automatic sprinkler system NFPA 286: Meet all requirements listed in IBC 803.1.1.1 (see above) Textile ceiling coverings ASTM E84/UL 723: Class A and must be protected with automatic sprinkler system NFPA 265: Meet all requirements listed in IBC 803.5.1.1 (see above) Expanded vinyl wall NFPA 286: Meet all requirements listed in IBC coverings 803.1.1.1 (see above) ASTM E84/UL 723: Class A and must be protected with automatic sprinkler system NFPA 286: Meet all requirements listed in IBC Expanded vinyl ceiling 803.1.1.1 (see above) coverings ASTM E84/UL 723: Class A and must be protected with automatic sprinkler system High-density NFPA 286: Meet all requirements listed in IBC polyethylene and 803.1.1.1 (see above) polypropylene NFPA 286: Meet all requirements listed in IBC Site-fabricated Stretch 803.1.1.1 (see above) Systems ASTM E84/UL 723: Class A, B, or C NFPA 286: Meet all requirements listed in IBC Laminated products with 803.1.1.1 (see above) wood Substrate ASTM E84/UL 723: Class A, B, or C NFPA 286: Meet all requirements listed in IBC Facing or veneer applied 803.1.1.1 (see above) over Wood substrate ASTM E84/UL 723: Class A, B, or C In addition to these requirements, there are specific requirements for individual occupancies. For the PAC, A-1 occupancy is used since there is no occupancy separation, however the requirements are the same for A-3 and B occupancies, which are the other two that are present in the building. There is also accessory S occupancies however the requirements for S occupancies are lower than the others. Where a requirement specific to the occupancy is greater than the requirements stated above, the more stringent requirement must be met. The following are the requirements for interior finishes for walls and ceilings 39 | P a g e tested with ASTM E84/UL 723 (materials that comply with requirements in IBC 803.1.1.1, see above, are considered Class A) for A-1 occupancies that are sprinklered (IBC Table 803.13): • • • Interior exit stairways and ramps and exit passageways: Class B Corridors and enclosure for exit access stairways and ramps: Class B Rooms and enclosed spaces: Class C Additionally, interior finish material that are applied to fire-resistance-rated or noncombustible building elements must meet the requirements of Class A unless they are protected by an automatic sprinkler system on both sides, are attached to noncombustible backing or furring strips, or where the combustible void is filled with a noncombustible material (IBC 803.15). There are some other minor requirements for walls and ceilings finishes that are not likely to apply to this building that can be found in IBC Chapter 8. The interior floor finish and floor covering materials are also subject to the requirements of IBC Chapter 8. Interior floor finishes and covering materials are tested to ASTM E648 or NFPA 253 and are required to be not less than Class II rating for assembly, business, and storage occupancies. In addition, floor covering materials must comply with the requirements of the DOC FF-1 “pill test” or ASTM D2859. Since the building is equipped with automatic sprinkler’s, materials tested with the DOC FF-1 “pill test” or ASTM D2859 are permitted where Class II materials are required. Performance-Based Egress Analysis The performance-based aspect of this egress analysis is largely based on Chapter 14 of the SFPE Handbook 3rd edition called “Emergency Movement.” For prescriptive design, the movement time of occupants is indirectly accounted for through the sizing of egress components. However, in performance-based egress design, the movement and total evacuation time of the occupants is calculated directly. The time that is calculated for the time it takes for occupants to evacuate a space or building is called the required safe egress time (RSET). This time is compared to the available safe egress time (ASET) which is the time it takes for the fire-induced conditions in a space or building to reach the point of untenability. The ASET is calculated based off of design fires and modeling to determine time to untenability by smoke, heat, structural stability, etc. The tenability limits for smoke inhalation will be discussed in a later section, however, the actual ASET will not be calculated as part of this report. Commonly, the RSET is divided into five categories as follows: 𝑅𝑆𝐸𝑇 = 𝑡𝑑 + 𝑡𝑎 +𝑡𝑜 +𝑡𝑖 + 𝑡𝑒 Where 𝑡𝑑 = time from fire ignition to detection 𝑡𝑎 = time from detection to notification of occupants 𝑡𝑜 = time from notification until occupants decide to take action 𝑡𝑖 = time from decision to take action until evacuation commences 𝑡𝑒 = time from the start of evacuation until it is completed (source: SFPE HB 3rd edition) The time from fire ignition to detection depends on the fire size, smoke production, environmental characteristics, and detection devices. The time from detection to notification depends on the system 40 | P a g e used but should be a short period of time. While these are very important aspects of the RSET calculation, they are much more related to detection and alarm systems and will not be discussed at length here. The time it takes for occupants to take action and to begin evacuating is dependent on human behavioral response. People can be influenced by many factors such as social interactions, environmental conditions, the built environment, leadership (or lack thereof), and demographics. The two factors that correspond with the concept of human behavior are 𝑡𝑜 and 𝑡𝑖 and will usually be lumped into one “pre-movement” time. This will be discussed at length in the next section. The last component of RSET is 𝑡𝑒 , which is the time for the occupants to evacuate once they have started moving. This time may be the time for occupants to reach a protected stairwell or the time for occupants to full exit the building, depending on the circumstance. There have been numerous studies into movement times for people walking, moving through doors and corridors, and moving up and down stairs. Pre-Movement Time Pre-movement time in an emergency is most influenced by human behavior. As Dr. Kuligowski states in Chapter 58 of the SFPE Handbook (5th edition), “Human behavior in fire is the study of human response, including people’s awareness, beliefs, attitudes, motivations, decisions, behaviors, and coping strategies in exposure to fire and other similar emergencies in buildings.” It is important to understand how occupants will react, because in certain situations the time to get people moving can be less than the time for them to evacuate. Placing a flat time on pre-movement for all buildings would likely not properly account for the differences in occupant characteristics and would not end up being a correct estimation. Since it is so important to occupant safety to maintain that occupants leave a space or building before untenable conditions are reached, a large emphasis should be placed on trying to correctly calculate the pre-movement and movement time. To understand how people will behave in a fire, Dr. Kuligowski states that it is important to understand how people will likely not behave. Panic used to be a widely accepted theory for how humans will behave with fire, but it has largely been proven not to be true. For example, in studies and survivor interviews of the 2001 WTC attack stated that people were overall calm and altruistic, rather than panicking or competing. Another previously accepted theory to human behavior in fire was disaster shock. Disaster shock suggests that people will either panic or go into shock and not respond in a fire situation. Again, multiple studies including those on the WTC found that occupants helped others and took initiative in their response. Finally, group mind is an oversimplification stating that individuals in a disaster will think as a group and act together in response to the danger. While people may be influenced by those around them, they are still making individual decisions. The Protective Action Decision Model (PADM) The Protective Action Decision Model (PADM) is based off empirical studies of past hazards and disasters and can help layout the framework for understanding human behavior in fire. The model states that the physical and social environment can cause an occupant to perceive threat and act. Whether they act and how quickly depends on how they perceive the threat. How people perceive a threat can depend on the pre-event beliefs about the disaster. People may have different beliefs about the likelihood and seriousness of a fire, which can change how they respond to cues from their surroundings. Additionally, whether people view those giving directions as trustworthy or unreliable will change their reaction. 41 | P a g e After receiving cues from their surroundings and running through pre-event perceptions, the occupant will either return to life as usual, or begin the decision-making process. They will likely think and gather more information about the threat and whether they should respond to it. If they decide there is a credible threat, they will begin to seek for protection and decide how to best protect themselves with the resources available. Finally, the individual must decide if the protective actions should take place now or wait. This decision-making process can be influenced by notifying occupants in the following ways: • • • • At a high enough level such that all occupants can hear the alarm or message With visual cues to aide in perception, and for those with hearing disabilities Message that is specific, repetitive, consistent, and credible Addresses the needs of those making decisions: information providing credibility, actions to take, timeliness, locations of fire, and descriptions of hazard The PAC helps address some of the aspects of the PADM by providing a voice alarm communication system and crowd managers. The EVAC system will play a prerecorded message notifying occupant of a hazard and providing them with directions on how to respond. Then, crowd managers will aide in addressing occupant questions and concerns, while encouraging calm and effective evacuations. Ideally, these aspects would reduce the pre-movement time. This will be discussed at length in the next sections. Factors That Influence Occupant Behavior Dr. Kuligowski states five main factors that influence occupant’s behavior in a fire: social influence, stress, the built environment, leadership, and demographics. Social influence in fire generally states that individuals are influenced by those around them. As stated earlier, this does not mean that every person in a group will respond the same, but rather that they will take in other’s actions as an additional piece of information in addition to other cues. Studies have found that occupants may not report a fire if others around them also do not. If others do not seem to view the fire as an emergency, an individual may be less likely to perceive threat. In the situation of a theater, this could happen if the performance continues or the lights do not turn on when there is an emergency. If either of these situations were to happen people would either not know there was an emergency or would perceive it as a false alarm. On the other hand, if in the middle of an event the lights came on, alarms went off, and the performance stopped, it would be hard for an occupant not to perceive a threat. Another factor that can influence occupant behavior is stress. Stress can be brought on due to the threat of harm from the fire, but can also be brought on by uncertainty, information overload, and time pressure. If the occupants receive too little or too much information or may begin to feel there is not enough time to exit the building. Stress can lead to occupants not making connections between information, making decisions that are not optimal, or ignoring some information. If a fire were to occur in the large Main Hall in a visible location, this could cause a significant amount of stress for occupants. Leaving theater seating is a process that requires patience and trust that other occupants are moving as quickly as possible. If occupants start to believe that they will not be able to exit in time because people in their row are slow, they could begin to make rash decisions. On the other hand, there is an opportunity to give very thorough information to occupants since they are all already in one area focused on one aspect. If proper control is taken, occupants will be assured that they are being protected and they will stay calm. The built environment can also influence occupant decision making. Most occupants in the PAC are unfamiliar with their surroundings. Therefore, they are likely to try to exit in the same manner that they 42 | P a g e came in unless they are influenced by their surroundings. Without influence, occupants may take routes that are optimal for normal operations but may not be the fastest route out of the building. Since the building is equipped with crowd managers, they should be utilized to direct occupants towards exits that are less crowded. Additionally, the use of strobes, exit signs and voice communications should also help direct occupants in the proper route. The built environment should be utilized to ensure that occupants will understand that there is a danger and that they should begin evacuating at the direction of crowd managers. This should help reduce the overall pre-movement time. Leadership can also help shape how occupants will respond to a fire situation. In buildings where there are leaders prior to the event, occupants are more likely to take directions from them. In the King’s Cross Disaster, which was a fire in a transit station, occupants were likely to follow the directions of police officers even when the directions were confusing or incorrect. By this logic, the introduction of crowd managers should provide a pre-event leadership. However, the occupants must view the crowd managers as trustworthy for them to be effective. If the crowd managers are used when filling the building to direct occupants, they will likely view them as more trustworthy than a crowd manager that only appears once there is an emergency. If crowd managers fail to keep the crowd directed early in the evacuation, there are no other pre-event leaders to take over. Therefore, it is pertinent that the crowd managers begin assisting early in the evacuation to establish leadership. If they do so, the premovement time should stay low. Pre-Movement Time Based on the PADM and the occupant characteristics that affect behavior in an emergency, a premovement time must be decided on. Chapter 64 of the SFPE Handbook provides data from research on pre-evacuation time for various occupancies. Two studies were done on occupancies like that of the PAC (cinema and theater). These studies saw a range of 8 to 36 seconds of pre-evacuation time. It is not unlikely that these pre-movement times could occur if the occupants in the theater are properly notified and the performance stops immediately. However, there could be some delay in the building going into alarm and the occupants understanding that there is a threat and moving due to the behavioral factors addressed earlier. In order to provide a conservative analysis, assume that it takes one minute from the time the alarm sounds for the performance to stop and lights to come on. Since occupants will probably not begin moving until these events happen, the pre-movement time should be at least one minute. After the performance stops and the lights come on, the occupants must recognize where they need to go and decide to leave. Based on the research data provided in the SFPE Handbook, assume this may take 40 seconds. Therefore, the overall pre-movement time after the fire has been detected and the alarms sound is 100 seconds. Movement Time The movement time is the final part of the ASET calculation. Since the building’s largest portion of occupants is in the Main Hall area, this calculation will assume that a phased evacuation does not occur, and the entire building begins evacuating at once. The evacuation time will be considered complete when every occupant has completely exited the building. The calculation assumes that occupants will equally utilize all exits that are available to them. When occupants travel through one egress component slower than the component leading to it, a queue will form. When a queue forms, the occupants are “dosed” through the door, and it is assumed that they move through the door at the optimal flux rate. 43 | P a g e The first step in calculating egress time is figuring out where occupants will egress. Figure 23. Pit Level egress distribution. For the pit level, the occupants in the main area were distributed evenly between the two exits. The occupants on the left side rooms egress directly to public way and are not considered in the calculation since their egress will be shorter than at other locations. 44 | P a g e Figure 24. Orchestra level egress distribution. The orchestra level has one of the more complicated egress distributions. All occupants who used the three main stairs to exit on other levels will exit the building on this level. The occupants in the main hall were distributed evenly between the four exits, except the loggia only used the back exits. All occupants exiting from the main hall are assumed to use the gallery and then exit through the lobby on the next level. The stage was divided evenly between the five exits, then distributed between the three nearest exits. The dressing rooms in the back all used the exit that connects to the corridor. The most loaded exit 45 | P a g e on this level is the exit near the classroom as it receives most of the classroom occupants, the rehearsal pavilion occupants, and some occupants from the stage and upper floors. Figure 25. Main/lobby level egress distribution. On the lobby level, most occupants use the main lobby doors to exit. Some occupants go downstairs and exit on the orchestra level. The lobby has a total of 1026 occupants who egress evenly through the 9 doors that are available. 46 | P a g e Figure 26. Balcony level egress distribution. Occupants in the balcony are distributed evenly to the four exits available. Those nearest to the stage use the top two exits and exit on the orchestra level. Occupants located further from the stage and in the founder’s lounge use the front stairway and exit on the orchestra level. None of the occupants on this floor will use the main exits in the lobby as the stairs leading there are not used for egress. 47 | P a g e Figure 27. Gallery (upper balcony) level egress distribution. On the gallery level, occupants exit similarly to the lower balcony level. The occupants in the balconies are distributed evenly, with those in the front of the stage using the top stairways. The other half of the balcony occupants use the bottom stair, and none will exit through the main lobby doors. It is likely that queueing will occur at multiple locations throughout the building. In order to find the total evacuation time for the building, the queueing locations must be found and the one that takes the longest to evacuate will be the total evacuation time. The following locations will be checked for queueing: 3 main stairs, main lobby doors, and exit door near classroom. 48 | P a g e The three main stairs will be referred to as stairs 1,2, and 3 from this point on as shown below: The longest queue at Stairs 1&2 will occur on the orchestra level at the exit door. The total time to evacuate each stair will therefore be the amount of time it takes for the first occupants to reach each door and the amount of time it will take for the occupants to exit through the door at the orchestra level. For Stair 1, there are 101 occupants exiting with a 72” door. Accounting for the effective width of the door, and if the occupants exit at the optimal flux (24 persons/min/foot), it will take 51 seconds for occupants to exit once they have reached the door. The stairs in this building have a 7-inch rise and 11-inch run, and there are 12 feet between floors. Based on this, it will take 22 seconds for the first occupants to reach the stairway door once they have entered the stairs. The occupants on the pit level will reach the stairs after 49 seconds. Adding these three figures, the total evacuation time for Stair 1 is 122 seconds. Similarly, for Stair 2 the total evacuation time is 130 seconds. In Stair 3, queueing does not occur at the orchestra level. Instead, queueing occurs at the gallery level. Here, the door entering the stair is only 30”, with an effective width of 18”. The flowrate through this door will be 36 occupants per minute which is slower than at the other floors. It will take the furthest occupant 70 seconds to reach the stair door. Based on these figures, it will take 204 seconds for the occupants to egress through the stairs. Then, they must travel 3 floors, which gives the total evacuation time for Stair 3 to be 270 seconds. This is much longer than the egress times for the other main stairs. At the exit door near the classroom, queueing will occur. Although there is queuing at other doors leading to this exit, there are 4 egress paths with large loads that all lead to this door, causing the longest queue there. This door is 66” clear width, which gives a 54” effective width available for egress. Using the optimal flux rate through this door, the flow rate will be 108 occupants per a minute. A total of 826 occupants use this door, so it will take 459 seconds for all occupants to exit the door. The queue will begin after occupants from the rehearsal pavilion and classroom begin to exit, and the travel time for the occupants to begin queueing is 18 seconds. Therefore, the total egress time through the door near the classroom is 477 seconds. 49 | P a g e Finally, queueing may occur at the main lobby exit doors. It will take 71 seconds for occupants from the dress circle to reach the exit doors. The doors each have a clear width of 60” with corresponds to an effective width of 48” and a flow rate of 96 occupants per minute. There are only 133 occupants coming from the dress circle, so they will not cause queueing on their own. Factoring in the occupants who came from the main hall, they will take 104 seconds to reach the doors. Since the total flow for the nine doors is 864 occupants per a minute, the occupants will be able to exit through the doors before a queue occurs. Without a queue, these occupants will be able to exit much faster than the occupants at the door near the classroom, so the calculation was halted. There were quite a few assumptions that went in to calculating the evacuation movement times. First, it is assumed that all occupants begin evacuating at the same time. This assumption is worked mainly into the aspects of travel time to doors and queueing/load at doors. If everyone is assumed to move at the same time, the time for the furthest occupant to reach the door is simplified to only the time it takes them to walk and does not consider that another occupant may take longer if they wait longer to start moving. Next, it is assumed that occupants don’t influence other’s decisions and ability to egress. This would remove the possibility of a group not exiting because of social influence and that an occupant will not turn around to go back for something or to help others. These remove variables from travel times and flow rates through doors that would complicate the calculation significantly. Another rather large assumption is that people will move through doors at the optimal flow rate as specified in the SFPE Handbook. Although an individual will move through a door or stair faster on their own, the flux of the flow is much higher when there is queueing. This makes some sense because the door will be used to its maximum capacity at any point in time even though individuals may have to wait longer in a queue. There is truth to this assumption, however studies have found that the flow rates that are commonly used are higher than what has been found in actual egress studies. Finally, the calculations assume that no stairs or doors are blocked by a fire and that occupants use the exits equally. These assumptions can be true in some cases, but it has been found that people are more likely to use an exit that they are familiar with. Additionally, if a fire blocks any exit, the density of the occupants could exceed the optimal density and cause flow fluxes to decrease since it is too crowded for people to move. Overall, these assumptions work out to probably not providing a conservative approximation. There is a likelihood that at least one assumption will not be true causing some of the following effects: occupants observe others not leaving and decide to wait, occupants behave altruistically and go back to help others, occupants move through doors and stairs slower than optimal flux, or a stair is blocked causing occupants to circle back or overcrowd one exit. Therefore, in order to produce a conservative analysis, a margin of error or a safety factor should be added. With such large assumptions, a safety factor of 1.5 to 2 would probably be appropriate. After checking all the egress options for queueing, it was found that the longest exit time occurs at the door near the classroom with a total egress time of 477 seconds. This figure is used for the total movement time and added to the earlier decided pre-movement time. However, there are a quite a few assumptions that went into calculating the movement time as discussed above, so a safety factor of 1.5 is added to the movement time. This brings the movement time to 716 seconds and the pre-movement time to 100 seconds. The entire building will then be evacuated in just under 12 minutes. 50 | P a g e Tenability Analysis Criteria As discussed earlier, the available safe egress time must be compared to the required safe egress time to determine whether occupants will be able to exit the building safety. Tenability determines the available egress time. While there are a few factors that can lead to untenable conditions, smoke inhalation is one of the main causes of untenability. Smoke can cause two types of damage to occupants: irritation and asphyxiation. Smoke products such as HCl, HBr, and HF (acid gases) cause occupants’ irritation while CO and HCN can cause asphyxiations. Additionally, elevated levels of carbon dioxide can increase the uptake of air and speed the process of asphyxiation from CO and HCN. Since asphyxiants cause the most direct harm to occupants in most fire situations, they will be addressed here. The concept that is usually used to calculate harm to occupants due to smoke products is the fractional effective dose (FED). The FED is the dose received at time compared to the dose that will cause incapacitation or death. Substances like carbon monoxide have a linear uptake of the toxic substance, meaning that the amount of the toxic substance that is received at any point in time does not depend on the amount of toxin already in the body. For HCN, however, the uptake is not linear, and the toxin will be taken in slower once the body already has high levels of the toxin. This concept is shown below in the figure. Figure 28. Incapacitation by CO (left) is constant while HCN (right) decreases with uptake. In the left graph, if the ppm of CO is multiplied by the corresponding time to incapacitation, the value will stay approximately constant. However, as seen in the graph on the right, the HCN concentration multiplied by the time to incapacitation is not constant. When calculating the FED of CO, the dose to cause incapacitation or death will remain constant while the HCN FED will change as time goes on. Carbon monoxide toxicity can be represented by either the parts per million in the air or by the %COHb in the blood. The following equation can be used to convert from CO levels to %COHb: 51 | P a g e This equation applies to a constant CO level but can be integrated to account for the CO level increasing or decreasing over time. The FED model assumes that CO and HCN are additive in their effects. Additionally, since carbon dioxide is present in all fires, it is added to the model by increasing the breathing rates of occupants as the oxygen levels in the space decrease. Irritancy is independent from asphyxiation but can be calculated in a similar method. The equation used for FED is shown below from the SFPE Handbook: In order to solve the FED model, appropriate values for the ventilation rate (breathing rate) and the exposure dose for incapacitation (or death) from asphyxiants and irritants. Since most fires don’t have large amounts of acid gases produced, the lethal does for irritants is calculated using optical density which will be solved during the design fire stage. The ventilation rate is mostly dependent on how the occupant is moving. For occupants moving downstairs or walking, a typical ventilation rate is 25 L/min per the SFPE Handbook. For occupants moving upstairs or running, the ventilation rate is 50 L/min. The ventilation rate of a subject at rest is usually used to calculate the time to death from smoke inhalation. After an occupant becomes incapacitated, they will 52 | P a g e stop moving which will cause their breathing rate to decrease to that of a subject at rest, which is about 8.5 L/min. The exposure dose for carbon monoxide is also dependent on how the occupant is moving. For occupants that are moving more, not only will they breathe in more carbon monoxide, they will also be incapacitated or die at a lower carbon monoxide level in their blood. For occupants doing light work, they will be incapacitated at 30%COHb, based on values provided by the SFPE Handbook Chapter 63. When death occurs, occupants will have likely already been incapacitated, so the value used for death is 50% COHb. The exposure dose for HCl and irritants are provided in the SFPE Handbook in Table 63.7, which can be seen below. Table 18. (SFPE HB Table 63.7) Exposure doses for incapacitation and lethal lung damage. The AEGL values provide a much more conservative calculation than the SFPE values and therefore should be used for this calculation. 53 | P a g e