Open Circuit Test of a 3-Phase Alternator Equipment: Three phase power supply VFD (Variable Frequency Drive) DC Field voltage Procedure: Three Phase generator Ammeter Voltmeter Circuit Diagrams: Open Circuit Test Calculation: Open Circuit: In Amps In Volts Graph: Plot Field Current (If) V/S Open Circuit Voltage (Voc) and explain the results. Result/Conclusion: What is importance of open circuits test in power generation system? Short Circuit Test of a 3-Phase Alternator Equipment: Three phase power supply VFD (Variable Frequency Drive) DC Field voltage Procedure: Three Phase generator Ammeter Voltmeter Circuit Diagrams: Short Circuit Test Calculation: In Amps In Amps Graph: Plot Field Current (If) V/S Short Circuit Current (Isc). Result/Conclusion: What is importance of Short circuit test in power generation system, does it relate to any losses? To find Regulation of a 3-Phase Alternator by Open Circuit and Short Circuit Tests Equipment: Three phase power supply Tachometer DC Motor as prime mover Three Phase alternator Ammeter (AC, DC) Voltmeter (AC, DC) Procedure: 1. Use the readings of O.C and S.C tests to synchronous impedance Zs. 2. The next step is to find synchronous reactance Xs. 3. Find the Voltage Regulation using formulas and conclude the results. Calculation: The open circuit characteristic (O.C.C.) and short circuit characteristic (S.C.C.) are drawn on the same curve sheet as shown in figure 01. Determine the value of Isc and field current If that gives the rated alternator voltage per phase. The synchronous impedance Zs will then be equal to the open circuit voltage divided by the short circuit current at the field current which gives the rated e.m.f per phase. For the same value of field current, the synchronous reactance is found as follows: √ Sr.no. Zs Zs (av) Xs Xs (av) Figure 01: Characteristic curves of Open-Circuit & Short-Circuit Test In figure 01, consider the field current If = OA that produces rated alternator voltage per phase. Corresponding to this field current the open circuit voltage is AB. Calculate the excitation e.m.f Eo and voltage regulation for full-load for these three conditions: 1. 0.8 lagging power factor (+ sign is for lagging pf load) 2. Unity power factor 3. 0.8 leading power factor (-sign is for leading pf load) √[( ) ( ) ] V = rated terminal voltage per phase of alternator Phasor Diagram: Draw phasor diagrams for above three loads and verify the calculated results. Result: Regulation of alternator at full load is found to be: At unity pf = -------------------------At 0.8 lagging = ---------------------At 0.8 leading = ---------------------- Synchronous Impedance varies for different values of excitation. Conclusion: To synchronize 3-Phase Alternator with Infinite Bus using Bright Lamp Method Equipment: Three phase power supply VFD (Variable Frequency Drive) Lamp bank Procedure: Three phase alternator DC shunt motor Voltmeter & Ammeter Circuit Diagram: Circuit (a): Synchronization of alternator (Synchronized) Circuit (b): Synchronization of alternator (Un-Synchronized) Result/Conclusion: To synchronize 3-Phase Alternator with Utility Supply using Synchroscope Equipment: Three phase power supply VFD (Variable Frequency Drive) Synchroscope Procedure: Three phase generator Ammeter Voltmeter Circuit Diagram: Result/Conclusion: