Section 8 Testing & Commissioning Section 8 Testing & Commissioning 8.1 Testing and Commissioning Reports 8.1.1 Electric & Jockey Fire Fighting Pumps Testing and Commissioning Reports Four Stars Hotel (Soligran) Verdun, Beirut LACECO Architects & Engineers GENECO sarl PREMIUM E.C Project Location Mech. Consultant Mech. Contractor Certification # 12-179-01 PUMP TEST REPORT Date of Test: Revisions: 5-Apr-13 0 Pump Designation Equipment location System & Area Served Equipment Manufacturer Model / Type Pump Serial Number FIRE PUMP-1 Basement-3 Pumproom Bloc "C" Fire Fighting System AURORA 485 BF 11-2123763-2 PUMP Specified (Units) Flow Head Pump Inlet Pressure Pump Outlet Pressure System Pressurization Pressure Pressure Vessel Size RPM Seal Type Stages Pump Efficiency 750 240 265 N/A N/A SHUT OFF HEAD MOTOR Motor Model Remark: Motor Power Motor Efficiency (CosØ) Motor Power Factor (PF) Voltage (L1/L2, L1/L3, L2/L3) Amperage (I1, I2, I3) Motor RPM Phase Insulation Class Protection (IP) Starting Mode Frequency Setting Suction Pressure Discharge Pressure Shut Off Head 750 260 GRAVITY 260 N/A N/A 2960 GLAND PACKING SINGLE 93.60 Specified Motor Manufacturer Actual (Units) GPM PSI bar bar bar Ltr % GPM PSI bar bar bar Ltr GLAND PACKING SINGLE Name Plate Actual NIDEC MOTOR NIDEC MOTOR % S-10-20111585-001-S-10-20111585-001R-0002 R-0002 149.2 KW 149.2 KW 0.89 89.40 380 385 268 A 220 A 2960 2950 50HZ/3Ø F 50HZ/3Ø Y∆ START N/A Y∆ START Amperage (I1, I2, I3) F N/A 220 O/L Range O/L Setting DUE TO THE HIGH DISCHARGE FLOW OF WATER, ACTUAL ELECTRICAL MEASUREMENTS WERE TAKEN FROM THE PUMPS CONTROL PANEL. PLEASE REFER TO THE ACTUAL DUTY POINTS AS MEASURED AND POINTED ON THE MANUFACTURER'S SUPPLIED TEST CURVE. PUMP TIMER WAS SET TO SWITCH OFF PUMPS AFTER 10 MINUTES FROM REACHING 260 PSI. PUMP-2B WAS SET TO START ONCE SYSTEM PRESSURE REACHES 200 PSI, AND WILL START WHETHER P1 IS STILL RUNNING OR FAIL TO RUN Four Stars Hotel (Soligran) Verdun, Beirut LACECO Architects & Engineers GENECO sarl PREMIUM E.C Project Location Mech. Consultant Mech. Contractor Certification # 12-179-01 PUMP TEST REPORT Date of Test: Revisions: 5-Apr-13 0 Pump Designation Equipment location System & Area Served Equipment Manufacturer Model / Type Pump Serial Number FIRE PUMP-2 Basement-3 Pumproom Bloc "C" Fire Fighting System AURORA 485 BF 11-2123763-1 PUMP Specified (Units) Flow Head Pump Inlet Pressure Pump Outlet Pressure System Pressurization Pressure Pressure Vessel Size RPM Seal Type Stages Pump Efficiency 750 240 265 N/A N/A SHUT OFF HEAD MOTOR Motor Model Remark: Motor Power Motor Efficiency (CosØ) Motor Power Factor (PF) Voltage (L1/L2, L1/L3, L2/L3) Amperage (I1, I2, I3) Motor RPM Phase Insulation Class Protection (IP) Starting Mode Frequency Setting Suction Pressure Discharge Pressure Shut Off Head 750 260 GRAVITY 260 N/A N/A 2960 GLAND PACKING SINGLE 93.60 Specified Motor Manufacturer Actual (Units) GPM PSI bar bar bar Ltr % GPM PSI bar bar bar Ltr GLAND PACKING SINGLE Name Plate Actual NIDEC MOTOR NIDEC MOTOR % S-10-20111585-001-S-10-20111585-001R-0001 R-0001 149.2 KW 149.2 KW 0.89 89.40 380 385 268 A 210 A 2960 2950 50HZ/3Ø F 50HZ/3Ø Y∆ START N/A Y∆ START Amperage (I1, I2, I3) F N/A 210 O/L Range O/L Setting DUE TO THE HIGH DISCHARGE FLOW OF WATER, ACTUAL ELECTRICAL MEASUREMENTS WERE TAKEN FROM THE PUMPS CONTROL PANEL. PLEASE REFER TO THE ACTUAL DUTY POINTS AS MEASURED AND POINTED ON THE MANUFACTURER'S SUPPLIED TEST CURVE. PUMP TIMER WAS SET TO SWITCH OFF PUMPS AFTER 10 MINUTES FROM REACHING 260 PSI. PUMP-1B WAS SET TO START ONCE SYSTEM PRESSURE REACHES 220 PSI Four Stars Hotel (Soligran) Verdun, Beirut LACECO Architects & Engineers GENECO sarl PREMIUM E.C Project Location Mech. Consultant Mech. Contractor Certification # 12-179-01 PUMP TEST REPORT Date of Test: Revisions: PUMP Pump Designation Equipment location System & Area Served Equipment Manufacturer Model / Type Pump Serial Number Flow Head Pump Inlet Pressure Pump Outlet Pressure System Pressurization Pressure Pressure Vessel Size RPM Seal Type Stages Pump Efficiency 5-Apr-13 0 JOCKEY FIRE PUMP - BLOC "C" Basement-3 Pumproom Bloc "C" Fire Fighting System GRUNDFOS CR 15-17 0040 Specified (Units) gpm 60 psi 307 psi 0 psi 265 psi N/A Ltr N/A 2923 MECHANICAL MULTISTAGE SHUT OFF HEAD MOTOR Specified Remark: Motor Manufacturer Motor Serial Number Motor Power Motor Efficiency (CosØ) Motor Power Factor (PF) Voltage (L1/L2, L1/L3, L2/L3) Amperage (I1, I2, I3) Motor RPM Phase Insulation Class Protection (IP) Starting Mode Frequency Setting Suction Pressure Discharge Pressure Shut Off Head Actual (Units) 265 0 265 N/A N/A % gpm psi psi psi psi Ltr MECHANICAL MULTI STAGE Name Plate GRUNDFOS 4975.00 15 KW 0.91-0.90 Actual 380 385 27.80 31.0-28.5 2930/2950 50HZ/3Ø 50HZ/3Ø F 55.00 Delta N/A F 55.00 Delta N/A Amperage (I1, I2, I3) O/L Range O/L Setting JOCKEY PUMP WAS SET TO START AT 240 PSI AND SWITCH OFF AT 265 PSI % ____________________ Certified By Sales Order: Size: Type: R.P.M.: Stage: Spec. Gravity: Imp. Dia.: WO/Serial No.: Curve No: Test No: Plotted By: Date: 11/01/2011 ____________ Date Bloc "C" Fire Pump-1 2450768-1 6-485-12 485 2950 2 1.0 10.625 2123763-2 215792 1111023 4646, TF 11/1/2011 SACOM Customer ACTUAL ON SITE TEST TDH 500 BHP Eff. % Eff #A #B #C Total Dynamic Head in PSI 450 1100GPM @ 190PSI - 232 AMPS 900GPM @ 210PSI - 224 AMPS 500GPM @ 270PSI - 199 AMPS 100 90 400 80 350 70 C 300 60 B 250 50 A 200 40 B.H.P. 400 150 30 300 100 20 200 50 10 100 0 0 0 0 125 250 375 500 625 750 CAPACITY - U.S. GALLONS PER MINUTE 875 1000 1125 1250 ____________________ Certified By Sales Order: Size: Type: R.P.M.: Stage: Spec. Gravity: Imp. Dia.: WO/Serial No.: Curve No: Test No: Plotted By: Date: 11/01/2011 ____________ Date Bloc "C" Fire Pump-2 2450768-2 6-485-12 485 2950 2 1.0 10.625 2123763-2 215793 1111021 4646, TF 11/1/2011 SACOM Customer ACTUAL ON SITE TEST TDH 500 BHP Eff. % Eff #A #B #C Total Dynamic Head in PSI 450 100 1100GPM @ 180PSI - 240 AMPS 900GPM @ 210PSI - 245 AMPS 500GPM @ 270PSI - 199 AMPS 90 400 80 350 70 300 60 C 250 50 B A 200 40 B.H.P. 400 150 30 300 100 20 200 50 10 100 0 0 0 0 125 250 375 500 625 750 CAPACITY - U.S. GALLONS PER MINUTE 875 1000 1125 1250