Influence of High Voltage Bundle Configurations on Human Exposure Alexandru Salceanu1, Silviu Vornicu1, Eduard Lunca1 1 Marcel Istrate2 Department of Electrical Measurements and Materials 1 “Gheorghe Asachi” Technical University of Iasi 1 Iasi, Romania asalcean@tuiasi.ro Abstract—The paper is mainly dedicated to determining the influence of bundle conductors configurations on the electric and magnetic field levels determined at the standard height of 1 m above the ground. The technical-economic advantages are concisely presented, but also the inherent disadvantages of implementing such solutions. One of the main advantages is theoretically analyzed: the reduction of the risk of initiating corona discharges, as a result of the decrease of the potential gradient from the conductor surface, implicitly meaning the increase of the electric field strength near the ground. The theoretical approaches were reinforced by simulations performed with the help of ANSYS and EMFACDC software. It was considered the real case of a 400 kV network through which phase currents of 1050 A are transported, in three distinct variants: single conductor, double bundle and triple bundle. Electric field increases were found by 37% in the case of triple bundles, taking as reference a single conductor per phase. If the same total current is considered, the chosen bundle configurations have no influence on the generated magnetic field. Keywords—bundle conductors, electric and magnetic fields I. GENERAL CONSIDERATIONS ON THE OPPORTUNITY OF „BUNDLE CONDUCTORS” SOLUTION There is a general concern about techniques and methods for reducing human exposure to extremely low frequency electric fields (50-60 Hz, power frequency), [1], [2]. Due to the large number of stakeholders, cheap, widely accessible measurement techniques [3], respecting the European Union legislation in force, need to be developed [4]. Some of the possible solutions are relatively expensive and should be used only in special cases, when the values of the generated fields are critical, [5], [6]. The values of the generated fields are all higher as the voltage (and implicitly the currents) have higher values, of over 400 kV and 1000 A, respectively. From the point of view of human exposure assessment, the difficulty lies in establishing the most accurate and rigorous correspondence between the ambient values of the electric and magnetic fields (so-called reference values) and the actual induced electric field in the human body (so-called basic restrictions), [9], [10], [11]. The use of several sub-conductors (placed parallel to each other) is an almost mandatory solution, when you want to 2 2 Department of Power Engineering “Gheorghe Asachi” Technical University of Iasi 2 Iasi, Romania increase the current capacity (ampere capacity, abbreviated ampacity) of a High Voltage Overhead Power Transmission Line (OhHVPL), [12]. Mainly due to the skin effect, the central part of the cross section of a conductor is not traversed by power lines, so it is practically unused. One solution (theoretical, never applied to the transmission of electricity), would be the use of empty conductors (without any central area), the so-called hollow conductors. In reality, a completely different solution with increased economic efficiency is applied, namely the use of several thinner sub-conductors, mounted in parallel for the same phase, instead of a single thicker conductor. First of all for technological reasons, being easier to bend, for transport and assembly, these conductors are not massive, but consist of several twisted wires (stranding wires), on the same principle of hemp rope woven from several wires. They have round cross-section and consist of several concentric layers. The diameter of an Al core wire is (approximately) between 2 and 4 mm. We present an edifying example, taking as reference the standards [13], [14] that applies to conductors which have a core of zinc-coated steel wires surrounded by aluminum wires, the so-called ACSR (Aluminum Conductors Steel Reinforced).The following eloquent comparison could be extracted. A current of 1050 A (50Hz) might be carried: using a single conductor ACSR 570/40, having a real cross section of 571.2 mm2 Al (overall radius 16.1 mm). using 2 parallel sub-conductors type ACSR 185/30, each having a real cross section of 183.8 mm2 Al, meaning a total of 367.6 mm2Al (overall radius 9.5 mm). using 3 parallel sub-conductors type ACSR 95/15, each having a real cross section of 94.4 mm2 Al, meaning a total of 283.2 mm2 Al (overall radius 6.8 mm). In other words, for the transport of the same alternative current of more than 1000 A, with a frequency of 50 Hz, as a result of the application of “double or triple bundle” solutions, cross sections reduced by 40% and 50%, respectively, can be used. This is primarily due to the more efficient use of the entire cross section, or, in other words, a limitation of the consequences of the skin effect. A clarification should be done. Obtaining this very significant reduction of the cross section (40-50%) required for the transport of a current over 1000 A was calculated on the condition of imposing the same maximum conductor temperature of 80oC. In other words, in the calculation of the current carrying capacity, the increase of the electrical resistance per km of conductor was also taken into account. The three parallel conductors ACSR 95/15 have a resistance (expressed in Ω/km) approximately twice the resistance of the conductor 570/40. Also, the surface in direct contact with the air, which allows the release of heat accumulated due to the Joule effect is almost double at conductor 570/40 compared to that of the three parallel sub-conductors 95/15. In conclusion, taking as a reference for comparison the same maximum actual carrying current on each of the three phases, the use of bundle conductors has several definite advantages: reduction of Al mass, with significant economic effects, but also with technological installation facilities; reduction of inductive reactance of the line [15]; surge impedance reduction (also obtained due to the increase of the capacitive reactance of the line); one of the most frequently mentioned advantages of using bundle conductors is the reduction of the risk of initiating corona discharges (meaning, implicitly, the reduction of corona losses, but also of the related radio-frequency electromagnetic disturbances) [16], [17]. There are also disadvantages, the most important being the increase of thermal losses due to the Joule effect [18], the reduction of the heat evacuation surface in the air [19] or the torsional behavior of the bundle [20]. Last but not least, the increase of the electric field level generated by OhHVPL at the standard height of 1 m from the ground level. As always, the role of the design engineer is to establish the best compromise, for a certain concrete situation, between the advantages and the inherent disadvantages of the best chosen solution. II. INFLUENCE OF BUNDLE SOLUTION UPON THE GENERATED ELECTRIC AND MAGNETIC FIELDS The problem we want to address in this section is the influence that the adoption of a "conductors bundle" configuration has on ambient electric and magnetic fields in general, on human exposure in particular. Of course, the issue of human exposure concerns everyone, first of all from the perspective of respecting the maximum limits allowed by the international standards in force. But, in particular, it is a separate chapter of the environmental impact studies carried out for any OhHVPL that is either in operation or at the design stage which must receive the approval of the various authorities, including the Environment Agency [21], [22]. Surely the focus must be on the electric field. From the perspective of reducing the risk of initiating corona type discharges, it can be demonstrated theoretically that the adoption of the “bundle” phase conductor solution reduces the electric field around (or rather, even at the surface) conductors, precisely in order not to the priming threshold of the corona discharge is reached. In this situation, it is assumed that the value of the electric field at ground level (more correctly, at the conventional height of 1 m imposed by standards) would be higher. For our study to be relevant, the electric field values recorded at this level must be compared, for networks with the same rated voltage, the same transferred current (hence, the same power), and of course the same spatial configuration of the phases given by the use of the same tower type. The comparison should be done between the single phase conductor variant and the “bundle” variants, with 2, 3 or even 4 subconductors, using the same type of approved spacers. The electric field is a vector quantity and represents the potential gradient (potential is a scalar quantity). The gradient of a quantity is calculated by applying the differential vector operator ∇ (partial derivatives on the three coordinate axes). In other words, by multiplying a vector (the “nabla” or del ∇ operator) by a scalar (in our case the scalar electric potential) we obtain a vector, the electric field. In Cartesian coordinates (rectangular) we have the expression of the electric field: = −∇ = − ∙ + ∙ + ∙ (1) It would be useful to highlight some aspects related to OhHVPL- associated corona discharges, which we will later correlate with the effect that a “bundle” phase conductor configuration might have on the initiation of these discharges. At first glance, we have an apparent contradiction. The potential gradient (hence the electric field strength) at the surface of a conductor with circular cross section will be larger the smaller the radius of the circular section, which is easy to explain based on the formula: =− (2) The reduction of the potential gradient and implicitly the reduction of the risk of initiating a corona discharge must be explained in the context of the “bundle” type assembly, consisting of several (sub) conductors at the same potential and separated by spacers with side 300 or 500 mm. III. SIMULATIONS PERFORMED WITH ANSYSAND EMFACDCSOFTWARE There are a multitude of factors that influence the value of the electric and magnetic fields generated by OhHVPL. In this study we simulated these fields using two specialized software, ANSYS [23] and EMFACDC [24]. We have considered the concrete case of a deviation tower (corner tower), in Y, type ICy 400 136, pylon currently used for simple three-phase 400 kV networks. Due to the maximum allowable span between two consecutive towers (365 m) and the corresponding sag of 12000 mm (at the middle of this distance), we considered the tower height at elevation + 6m. Glass and Liquid Silicon Rubber insulation chains with a length of 4000 mm have been considered. We have simulated for the three cases (equivalent from the point of view of Ampacity), presented in Section I. Newer type spacers, with a height of 400 mm, have been adopted, representing a good balance between the standard options, having the size of 300 mm and 500 mm, respectively. Taking into account the conditions previously formulated, the coordinates of the centers of the cross sections, for the three cases discussed are summarized in Table I. TABLE I. CARTESIAN COORDINATES OF THE CROSS SECTIONS OF CONDUCTORS FOR THE THREE CASES STUDIED. [mm] 1 cond. 2 subcon. 3 subcon. R R-2 R-1 -18100, 12900 -18300, 12900 -18300, 12900 R-3 -17900, 12900 -17900, 12900 S-1 0 12900 -200, 12900 -200, 12900 -18100, 12550 S S-2 200, 12900 200, 12900 S-3 0, 12550 T-1 18100, 12900 17900, 12900 17900, 12900 T T-2 T-3 18300, 12900 18300, 12900 18100, 12550 The first simulations have been performed for the electric field generated at a height of 1 meter from the ground, Fig.1 with ANSYS software. As expected, the values of the electric field at this standardized height are the highest near the side phases (i.e. approx. + / - 18 m from the axis of symmetry of the Y-pole), for the case of bundle of three conductors, the smallest being registered for the case of the single conductor. More precisely, the maximum values recorded for the cases with 2 and 3 subconductors, respectively, are 5679 V/m and 5097 V/m, representing a slight exceeding of the acceptable limit for residential exposure, 5000 V/m. In the case of a single conductor, the maximum value is only 4129 V/m, below the limit allowed for general public exposure. In relative terms, the difference between the case with three sub-conductors and the case of a single conductor is about 37%. The significance of this percentage is considerable mainly due to the fact that it allows the transition from acceptable to unacceptable values. Fig. 2.a. Electric field, lateral profile, 1m height, single conductor, maximum value 3660 V/m We performed exactly the same simulation using EMFACDC software, Fig. 2. Electric field strength, E(V/m) ANSYS 1*1050 A ANSYS 2*525 ANSYS 3*350 6000 5000 4000 3000 2000 1000 0 -50 -40 -30 -20 -10 0 10 20 30 40 50 Lateral distance, d (m) Fig. 1. Comparative lateral profile of the Electric field generated by a 400 kV network (1, 2 and 3 conductors per phase) Fig. 2.b. Electric field, lateral profile, 1 m height, double conductors, maximum value 4710 V/m The maximum values are recorded as expected, next to the phase conductors. For the single conductor, the maximum electric field has the value of 337887 V/m, for the case with 2 sub-conductors, the maximum value is 228203 V/m and for the case with three sub-conductors per phase, the maximum value decreases to 199005V/m. These results confirm the theory. The smaller is the radius of the conductor (the sharper the conductor), the higher the potential gradient at its surface. In the case of conductors placed in parallel, at distances of the order of 30-50 cm, a compensating effect occurs. Specifically, in the case simulated in Fig. 3, the value of the electric field at the surface of the single conductor is about 70% higher than the value measured in the immediate vicinity of the triple-bundle. Fig. 2.c. Electric field, lateral profile, 1 m height, triple conductors, maximum value 5430 V/m The shape of these simulated graphics with the 2 software is very similar. However, the maximum values are a few percent lower in the case of simulations performed with EMFACDC. These differences can be explained by the different values of soil conductivity assumed for simulation [25]. An interesting result is the lateral profile of the electric field measured at a height of 12 meters from the ground, i.e. practically right on the surface of the conductors that form the power line, Fig. 3. The results shown in Fig. 3 are less directly relevant from the perspective of human exposure (it is very unlikely that the human subject is 13 m above the ground, just below the high voltage network). But it has an indirect influence: a larger electric field near the conductor surface means a smaller field near the ground (obviously, for the same phase voltage, measured between the line and ground). ANSYS 1*1050 A ANSYS 2*525 ANSYS 3*350 We also performed a necessary simulation for the magnetic field generated by this network, Fig. 4. For the relevance of the performed comparisons, we started from the hypothesis that for each phase, the total current is the same, 1050 A. The value of the magnetic field depends only on the current intensity. Naturally, the lateral profile of magnetic flux density is the same, for any of three cases. IV. Bundle conductors are a "sine qua non" solution for networks over 220 kV and 1000 A. Significant costs are involved but also the economic benefits are commensurate. Due to the reduction of the potential gradient at the surface of the conductors in the bundles, there is an increase of 30-40% of the electric fields at the standard height of 1 m above the ground. Such an increase, in an approximate value of 1000-2000 V/m, may mean exceeding the threshold of 5000 V/m imposed by the standards for the exposure of the general public, representing a cause for alarm in the case of residential areas, which should not be located in the immediate vicinity of voltage lines. Magnetic flux density, B(µT) Electric field strength, E(V/m) ANSYS 1 metru 20 350000 300000 250000 200000 150000 100000 50000 0 -25 -15 -5 5 15 25 Lateral distance, d (m) Fig. 3. Lateral profile of the Electric field in the very close vicinity of power lines (12 meters height). CONCLUSIONS 18 16 14 12 10 8 6 4 2 0 -50 -40 -30 -20 -10 0 10 20 30 40 Lateral distance, d (m) Fig. 4. Lateral profile of magnetic field. Identity for all three cases. 50 REFERENCES [1] C. L. Wadhwa, Electrical Power Systems, Fourth edition, New Age International Publisher, 2006. [2] E. Lunca, S. Ursache and A. Salceanu, “Computation and analysis of the extremely low frequency electric and magnetic fields generated by two designs of 400 kV overhead transmission lines,” Measurement Journal, Volume 124, pp. 197-204, August 2018. [3] Z. Liu, Ultra-High Voltage AC/DC Grids, Academic Elsevier Press, 2015. [4] A. Salceanu, E. Lunca and M. Paulet, “Affordable evaluation of low frequency electric fields from the standpoint of Directive 2013/35/EU,” ACTA IMEKO, E-Journal of the International Measurement Confederation (IMEKO),Vol. 6, No. 4, pp.37-45, 2017. [5] Design guidelines for development near high voltage overhead lines, National Grid Transco,UK, https://www.nationalgrid.com/sitesaccessed May 2020. [6] A. Salceanu, S. Ursache, O.M. Asiminicesei and C. Lazarescu, “Phasing Effect on the Electric Fields Generated by High Voltage Overhead Power Lines,” Proceedings of 10-th International Conference and Exposition on Electrical and Power Engineering, Iasi, Romania, pp. 0759-0764, 2018. [7] E. Lunca, S. Ursache, and A. Salceanu, “Characterization of the Electric and Magnetic Field Exposure from a 400 kV Overhead Power Transmission Line in Romania,” Proceedings of the 22-nd IMEKO TC4 International Symposium and 20-th International Workshop on ADC Modelling and Testing, Iasi, Romania, pp. 239-244, 2017. [8] A. Salceanu, M. M. Poenaru, M.A. Anghel, and M. Paulet, “Approach on the Evaluation of Exposure to Low Frequency Electric Fields,” Proceedings of the 21st IMEKO TC4 International Symposium and 19th International Workshop on ADC Modelling and Testing, Budapest, Hungary, pp. 32-36, 2016. [9] M. Paulet, C. Lazarescu and A. Salceanu, “Modeling the Currents Induced in the Human Body by an Overhead High Voltage Power Line,” Proceedings of 10-th International Conference and Exposition on Electrical and Power Engineering, Iasi, Romania, pp. 0189 – 0192, 2018. [10] M. Paulet, C. Lazarescu, O. Bejenaru and A. Salceanu, “Study on Induced Currents in an Elliptical Cylindrical Model by Overhead High Voltage Power Lines,” 11th International Symposium on Advanced Topics in Electrical Engineering (ATEE), Bucharest, Romania, 2019, pp. 1-5, 2019. [11] A. Salceanu, M. Paulet, S. Ursache, and M. M. Poenaru, “Evaluating the Cumulative Exposure to Low Frequency Electric Fields,” Proceedings of the 9-th International Conference and Exposition on Electrical and Power Engineering (EPE 2016), Iasi, Romania, pp.408-412, 2016. [12] A. M. Mousa, “Reducing the cost of power lines through the use of alternative conductor bundle configurations,” Proceedings of Canadian [13] [14] [15] [16] [17] [18] [19] [20] [21] [22] [23] [24] [25] Conference on Electrical and Computer Engineering, vol.1, Vancouver, BC, Canada, pp. 570-573, 1993. CEI-IEC 1089: 1991-05, International Electrotechnical Committee, TC 7, Standard of Aluminium conductors, steel-reinforced for overhead power transmission purposes. DIN 48204 : 1984, DIN EN 50182 : 2001, German Institute for Standardisation (Deutsches Institut für Normung), standard of Aluminium conductors, steel reinforced. V. V. Dan, “A rational choice of bundle conductors configuration,” Proceedings of 1998 International Symposium on Electrical Insulating Materials. 1998 Asian International Conference on Dielectrics and Electrical Insulation. 30th Symposium on Electrical Insulating Ma, Toyohashi, Japan, pp. 349-354, 1998. Y. Liu, S. You, F. Lu, Q. Wan, X. Bian and L. Wang, “500-kV EHV Bundle Conductors' Corona Onset Voltage Calculation and Analysis in Corona Cage at Different Altitudes,” in IEEE Transactions on Power Delivery, vol. 27, no. 4, pp. 2090-2097, 2012. Z. M. Al-Hamouz, “Corona power loss on bundled conductors: experimental and computational results,” IEEE Transactions on Industry Applications, vol. 35, no. 6, pp. 1277-1283, 1999. J. Liao, Z. Peng, L. Zhang, S. Zhang, N. Li and J. Li, “Electric Field distribution on four-bundle conductors in 750 kV AC substation,” 2012 IEEE 10th International Conference on the Properties and Applications of Dielectric Materials, Bangalore, pp. 1-4, 2012. S. A. Rahman and K. Kopsidas, “Thermal state analysis on bundled overhead line conductors,” Mediterranean Conference on Power Generation, Transmission, Distribution and Energy Conversion (MEDPOWER 2018), Dubrovnik, Croatia, pp. 1-5, 2018. G. Huang, B. Yan, J. Liu, C. Wu and Z. Lv, “Experimental Study on Torsional Behavior of Twin Bundle Conductor Lines,” IEEE Transactions on Power Delivery, vol. 35, no. 3, pp. 1423-1431, 2020. Environmental Impact Assessment and Report for the 400 kV GădălinSuceava Overhead Power Line, including the interconnection to the National Energy System: 2008, National Research and Development Institute for Environmental Protection Bucharest. E. Lunca, S. Vornicu, A. Salceanu, and O. Bejenaru, “2D Finite Element Model for computing the electric field strength-rms generated by overhead power lines,” Journal of Physics: Conf. Series 1065, 2018. Ansys: Engineering Simulation & 3D Design Software, https://www.ansys.com/I International Communications Union, Software "EMFACDC" v 2.0, https://www.itu.int/rec/T-REC-K.90-201905-I!Amd1 A. Salceanu, E. Lunca, B. D. Alistar and S. Ursache, “Upon the Influence of Charge Image on the Electric Field Intensity,” 2019 International Conference on Electromechanical and Energy Systems (SIELMEN), Craiova, Romania, pp. 1-6, 2019.