HV Circuit Breakers PTHV-LTB Incoming line ABB Transformation - Training Module-I 1 CVT DS/ ES CT DS DS CT CB PI/SA Trans. High Voltage Circuit Breakers HV Circuit Breakers PTHV-LTB Incoming line ABB Transformation - Training Module-I 2 CVT DS/ ES CB CT DS DS CT CB PI/SA Trans. BUSBAR HV Circuit Breakers PTHV-LTB LTB Interrupter Line termination Insulating rod Mechanical Link ABB Transformation - Training Module-I 3 Mechanism HV Circuit Breakers PTHV-LTB Line termination Interrupter Line termination Insulating rod Mechanism ABB Transformation - Training Module-I 4 HV Circuit Breakers • What is a Circuit Breaker ? – Circuit Breakers are mechanical switching device, capable of making, carrying and breaking currents under normal circuit conditions and also making, carrying for a specified time and breaking currents under specified abnormal conditions such as those of short circuit (IEC 50 - 441). – It is a premium against damage of the equipment. – It is the only automatic moving equipment in the transmission system. – It is a slave of relay. ABB Transformation - Training Module-I 5 PTHV-LTB HV Circuit Breakers PTHV-LTB Fault Occurs Relay • Senses • Contact Closes Circuit Breaker • Trip Coil Energises • Operating Mechanism Starts • Contacts Separate • Arcing betn. Contacts • Arc Extinguishes • CB Fully Opens ABB Transformation - Training Module-I 6 Faulted Part Gets Isolated HV Circuit Breakers • Ratings – Rated voltage (U r) – Rated insulation level – Rated frequency (f r) – Rated normal current (I r) and temperature rise – Rated short time withstand current (I k) – Rated peak withstand current (I p) – Rated duration of short circuit (t k) – Rated supply voltage of closing and opening devices and of auxiliary and control circuits (U a) – Rated supply frequency of closing and opening devices and auxiliary circuits – Rated pressures of compressed gas for providing insulation, operation and/ or interruption. ABB Transformation - Training Module-I 7 PTHV-LTB HV Circuit Breakers • Classification of CBs – On principle of current interruption • SF6 (puffer, self blast), Vacuum, Bulk oil, Minimum oil, Air break, Air Blast CB etc. – On class of voltage • Medium voltage, High voltage, Extra High voltage etc. – Type of installation • Indoor, outdoor etc. – Application • Railway, Generator CB, Line CB, Transformer CB, Reactor CB, furnace CB, Bus coupler, etc. – Type of mechanism • Pneumatic, spring, Hydraulic, Hydro-mechanical, springpneumatic, solenoid, motor ABB Transformation - Training Module-I 8 PTHV-LTB HV Circuit Breakers PTHV-LTB • Classification of CBs – On principle of current interruption • SF6 (puffer, self blast) – Present day CBs for medium voltage and high voltage. – Uses SF6 gas as a interrupting media and insulation media – Meets almost all technical requirements • Vacuum • • • • – – – – Uses vacuum as interruption media Uses SF6 for 36 kV and 52 kV as insulation media Used mainly for medium voltages Offers good electrical life Bulk oil, Minimum oil, Air break, Air Blast CB ABB Transformation - Training Module-I 9 Name suggests the interruption media. They are now history. HV Circuit Breakers PTHV-LTB • Classification of CBs – On class of voltage • Medium voltage – – – – From above 1 kV up to 52 kV class voltage Generally used indoors Housed in a cubicle Outdoor is also getting popular in India • High voltage – From 72.5 kV up to 300 kV – short line fault requirement for this voltage and above • Extra High voltage – Above 300 kV – Switching Impulse withstand requirement Additional ABB Transformation - Training Module-I 10 SF6Circuit Breakers HV Breakers PTHV-LTB • Puffer In these breakers the continuous gas pressure can be kept at low enough levels, 0.5-0.7 Mpa (abs), to permit operations under most climatic conditions, without risk of liquefaction. The pressure difference and resulting gas flow required for interruption are obtained by compression of gas, by operating mechanism, in direct connection with opening of the contacts. • Auto-Puffer (Self-Blast) In self-blast breakers the gas blast that is required is mainly obtained by use of energy from the arc itself. The arc heats the gas in a compression volume, and the resulting differential pressure leads to the gas flow used for interruption. The operating mechanism can be kept smaller and simpler than for corresponding puffer breakers. ABB Transformation - Training Module-I 11 AutoCircuit - Puffer Principle HV Breakers PTHV-LTB Extinguishing Position Closed Position Small Current ABB Transformation - Training Module-I 12 SC Current Utilization Operating Energy HV Circuit of Breakers PTHV-LTB Compared with a conventional puffer breaker of the same rating, the energy demand of the self-blast breaker is only around 20 % ABB Transformation - Training Module-I 13 HV Circuit Breakers PTHV-LTB • Classification of CBs – Application • Railway – In India a standard 50 Hz CB – Outside India frequency 16 2/3 Hz – Class of voltage is 25 kV single phase • Generator CB – Connected at the terminals of Generator – High normal current and very high fault current – High dc component due to low L/R ratio. Missed current zeros. • Line CB – A standard CB – Fault currents can be low or high depending on network condition – Can be three phase closing or one phase closing. System stability requirement – Capacitive current of the line is to be interrupted • Transformer CB, Reactor CB – Three phase operation preferred – Reactive current chopping can cause system over voltages ABB Transformation - Training Module-I 14 HV Circuit Breakers PTHV-LTB • Classification of CBs – Application • Furnace CB – Large number of mechanical operations. Large number of fault operations • Bus coupler – Normally works as a switch. It operates generally on load currents • Station Auxiliary Breaker – – – – Used for switching of station auxiliary power supply. For example, boiler feed pump, coal handling plant etc. Normally motor switching. Inductive current. Over voltages due to switching is of great significance • HVDC Breaker ABB Transformation - Training Module-I 15 HV Circuit Single LineBreakers Diagram PTHV-LTB Capacitor Side Breaker Generator End Breaker Sending End Breaker Receiving End Breaker Load End Breaker ABB Transformation - Training Module-I 16 HV Circuit Breakers Current Zero Missed due to Large L/R • Initial fault current contains large DC component, which may cause missed current zero opportunities. C u r r e n t time ABB Transformation - Training Module-I 17 PTHV-LTB HV Circuit Breakers PTHV-LTB Type of Mechanism • Spring Charged – Spring charged using motor to store energy and transferred through mechanical links – Spring can be helical, spiral (clock), etc • Pneumatic – Energy stored by compressing air in a receiver. – Energy transmitted pneumatically and motion created using cylinder piston arrangement • Hydraulic, Hydro - mechanical – Energy stored either in compressed air or springs – Energy transmitted hydraulically and motion created using cylinder piston arrangement ABB Transformation - Training Module-I 18 HV Circuit Breakers ABB Transformation - Training Module-I 19 PTHV-LTB HV Circuit Breakers ABB Transformation - Training Module-I 20 PTHV-LTB HV Circuit Breakers ABB Transformation - Training Module-I 21 PTHV-LTB HV Circuit Breakers PTHV-LTB Type of Mechanism • Motor Mechanism – Servo motor used to deliver energy. – Electronics used for delivery of desired energy with respect to time. – Energy stored in capacitors – Used for High voltages also • Solenoid Mechanism – Like contactor , electromagnet is used to move contacts – Energy can be derived from battery or capacitors. – Used for medium voltages and vacuum CBs ABB Transformation - Training Module-I 22 HV Circuit Breakers PTHV-LTB ELF 1982 DLF 1974 DCF 1969 ABB Transformation - Training Module-I 23 HV Circuit Breakers PTHV-LTB Type Designation: ELF SL 6-2 Rating Voltage : 420 kV Current Short circuit : 40 kA Nominal : 3150 A Mechanism Quantities delivered (upto 2000) ABB Transformation - Training Module-I 24 : Pneumatic Type PKA : 391 HV Circuit Breakers PTHV-LTB Type Designation: ELF SL 4-1 Rating Voltage : 245 kV Current Short circuit : 40 kA Nominal : 3150 A Mechanism Quantities delivered (upto 2000) ABB Transformation - Training Module-I 25 : Pneumatic Type PKA : 2243 HV Circuit Breakers ABB Transformation - Training Module-I 26 PTHV-LTB Type Designation Rating - Voltage - Current Short Circuit Nominal Mechanism : ELF SF 2-1/(r) Quantities delivered (upto 2000) :3323 : 145-72.5 kV : 31.5kA : 2000 A : Pneumatic Type PKA HV Circuit Breakers PTHV-LTB Type Designation: LTB145D1/B Rating Voltage : 145 kV Current Short circuit : 40kA Nominal : 3150 A Mechanism charged BLK Quantities delivered (upto 2000) ABB Transformation - Training Module-I 27 : Spring Type : 702 HV Circuit Breakers PTHV-LTB Type Designation: EDF SK 1-1 Rating Voltage : 36-52-72.5 kV Current Short circuit : 31.5 kA Nominal : 2500 A Mechanism : Spring charged Type FSA Quantities delivered : 4699 (upto 2000) ABB Transformation - Training Module-I 28 HV Circuit Breakers PTHV-LTB A typical 2 - chamber breaker for 420 kV class of voltage ABB Transformation - Training Module-I 29 HV Circuit Breakers PTHV-LTB Cross section of a Interrupting chamber ABB Transformation - Training Module-I 30