ELECTRICAL LOAD WORKSHEET PROPOSED single storey residential building OWNER : Toshinori Yagi ADDRESS: sinsuat ave., cotabato city LIGHTING LOAD PER ROOM Room bedroom Total area of habitable living area : 3 m x 4m = 12 m2 @ 24 watts /m2 Number of Lamps : 3 = 288 watts @ 100 watts each = 300 watts Lighting Load Subtotal = 300 watts LIGHTING LOAD TOTAL = 300 watts LOAD AMPACITY = 300 watts / 230 V = 1.304 AMPS 2.0 mm2 , TW Cu.WIRE SIZE OF CONDUCTORS = MINIMUM SIZE OF CIRCUIT BREAKER = 15 AT, SIZE OF CONDUIT Room 13 mm2 , = DIA. PVC PIPE master bedroom Total area of habitable living area : watts Number of Lamps : 5 4 m x 5m = 20 m2 @ 24 watts /m2 @ 100 watts each = 500 watts Lighting Load Subtotal = 500 watts LIGHTING LOAD TOTAL = 500 watts LOAD AMPACITY = 500 watts / 230 V =2.173 AMPS 2.0 mm2 , TW Cu.WIRE SIZE OF CONDUCTORS = MINIMUM SIZE OF CIRCUIT BREAKER = 15 AT, SIZE OF CONDUIT = 13 mm2 , DIA. PVC PIPE Page 1 = 480 ELECTRICAL LOAD WORKSHEET LIGHTING LOAD PER ROOM Room living Total area of habitable living area : 5 m x 5m = 25 m2 @ 24 watts /m2 Number of Lamps : 6 = 600 watts @ 100 watts each = 600 watts Lighting Load Subtotal = 600 watts LIGHTING LOAD TOTAL = 600 watts LOAD AMPACITY = 600 watts / 230 V = 2.608 AMPS 2.0 mm2 , TW Cu.WIRE SIZE OF CONDUCTORS = MINIMUM SIZE OF CIRCUIT BREAKER = 15 AT, SIZE OF CONDUIT Room = 13 mm2 , DIA. PVC PIPE kitchen/ dining Total area of habitable living area : 4 m x 4m = 20 m2 @ 24 watts /m2 Number of Lamps : 5 @ 100 watts each = 500 watts Lighting Load Subtotal = 500 watts LIGHTING LOAD TOTAL = 500 watts LOAD AMPACITY = 500 watts / 230 V =2.173 AMPS 2.0 mm2 , TW Cu.WIRE SIZE OF CONDUCTORS = MINIMUM SIZE OF CIRCUIT BREAKER = 15 AT, SIZE OF CONDUIT = 13 mm2 , DIA. PVC PIPE Page 2 = 480 watts ELECTRICAL LOAD WORKSHEET Room C.R. Total area of habitable living area : 2 m x 3 m = 8 m2 @ 24 watts /m2 Number of Lamps : 2 @ 100 watts each = 200 watts Lighting Load Subtotal = 100 watts LIGHTING LOAD TOTAL = 100 watts LOAD AMPACITY = 200 watts / 230 V =0.869 AMPS 2.0 mm2 , TW Cu.WIRE SIZE OF CONDUCTORS = MINIMUM SIZE OF CIRCUIT BREAKER = 15 AT, SIZE OF CONDUIT = 13 mm2 , DIA. PVC PIPE Page 3 = 144 watts ELECTRICAL LOAD WORKSHEET CONVENIENCE Type of Convenience Outlet OUTLET LOAD [ USE 180 watts per outlet ] Room _master bedroom 1.1 gang C.O. 2. 2 gang C.O. 3. 3 gang C.O. - ____ sets X - _2_ sets X - _1_ sets X 1 X 180 W =__ ___watts 2 X 180 W =__720 watts 3 X 180 W =_540_watts C.O. LOAD AMPACITY = Subtotal =__1260___watts ___1260__ watts / 230 V =____5.748____ AMPS SIZE OF CONDUCTORS =_____3.5______mm2 , ___TW___ Cu.WIRE MINIMUM SIZE OF CIRCUIT BREAKER = SIZE OF CONDUIT = __13____ mm2 , ____20____AT, DIA. PVC PIPE Room _bedroom 1.1 gang C.O. 2. 2 gang C.O. 3. 3 gang C.O. - ____ sets X 1 X 180 W =__ ___watts - _2_ sets X 2 X 180 W =__720 watts - __ sets X 3 X 180 W =______watts C.O. LOAD AMPACITY = Subtotal =__720___watts ___720__ watts / 230 V =____3.130____ AMPS SIZE OF CONDUCTORS =_____3.5______mm2 , ___TW___ Cu.WIRE MINIMUM SIZE OF CIRCUIT BREAKER = ____20____AT, mm2 , DIA. PVC PIPE SIZE OF CONDUIT = __13____ Page 4 ELECTRICAL LOAD WORKSHEET CONVENIENCE Type of Convenience Outlet OUTLET LOAD [ USE 180 watts per outlet ] Room _kitchen/dining 1.1 gang C.O. 2. 2 gang C.O. 3. 3 gang C.O. - ____ sets X 1 X 180 W =__ ___watts - _3_ sets X 2 X 180 W =__1080 watts - __ sets X 3 X 180 W =__watts C.O. LOAD AMPACITY = Subtotal =_1080__watts ___1080__ watts / 230 V =____4.695____ AMPS SIZE OF CONDUCTORS =_____3.5______mm2 , ___TW___ Cu.WIRE MINIMUM SIZE OF CIRCUIT BREAKER = SIZE OF CONDUIT = __13____ mm2 , ____20____AT, DIA. PVC PIPE Room _living 1.1 gang C.O. 2. 2 gang C.O. 3. 3 gang C.O. - ____ sets X 1 X 180 W =__ ___watts - _2_ sets X 2 X 180 W =__720 watts - __ sets X 3 X 180 W =______watts C.O. LOAD AMPACITY = Subtotal =__720___watts ___720__ watts / 230 V =____3.130____ AMPS SIZE OF CONDUCTORS =_____3.5______mm2 , ___TW___ Cu.WIRE MINIMUM SIZE OF CIRCUIT BREAKER = SIZE OF CONDUIT = __13____ mm2 , Page 5 ____20____AT, DIA. PVC PIPE ELECTRICAL LOAD WORKSHEET HOUSEHOLD COOKING EQUIPMENT (if any) Cooking Units - Includes ranges, wall mounted ovens, countertop units, and other household cooking units. Number of Units ________unit use ________units use ________units use ________units use ________units use VA per unit Load in watts 8,000 watts: 11,000 watts: 14,000 watts: 17,000 watts: 20,000 watts: Subtotal ___n/a__________ watts _____________ watts _____________ watts _____________ watts _____________ watts COOKING TOTAL =____________watts LOAD AMPACITY =________________ watts / 230 V =______________ SIZE OF CONDUCTORS =___________mm2 , _______ Cu.WIRE MINIMUM SIZE OF CIRCUIT BREAKER = SIZE OF CONDUIT = _____________ mm2 , Page 6 _____________AT, DIA. PVC PIPE AMPS ELECTRICAL LOAD WORKSHEET SPACE HEATING / AIR CONDITIONING (if any) Note : each unit must have a separate circuit breaker and conductor feeder. Use 746 W for 1 Hp 1. Air conditioner nameplate rating :___1.5 hp x 746= 1119___watts X____1__ pc = __1119________watts SIZE OF WIRE AND BREAKER OF _1.5 hp__ACU. LOAD AMPACITY = _1119___ watts / 230 V X 125% =___6.081__ AMPS SIZE OF CONDUCTORS =__5.5_______mm2 , __TW_ Cu.WIRE SIZE OF CONDUIT = ____13________ mm2 , MINIMUM SIZE OF CIRCUIT BREAKER LOAD AMPACITY =_1119___ watts / 230 X 250 % MINIMUM SIZE OF CIRCUIT BREAKER = Page 7 DIA. PVC PIPE OF 1.5 hp_ACU =____12.16___ ______30_______AT, AMPS ELECTRICAL LOAD WORKSHEET HEAT PUMP 2. Largest condensing unit nameplate :___N/A_____watts X______ pc =__________watts AND Supplementary heat (resistance) : ________watts X______ pc = __________watts SIZE OF WIRE AND BREAKER OF ________________. LOAD AMPACITY = _______ watts / 230 V X 125% =______________ AMPS SIZE OF CONDUCTORS =___________mm2 , _______ Cu.WIRE SIZE OF CIRCUIT BREAKER= _______ watts / 230 V X 250 % =_________AMPS MINIMUM SIZE OF CIRCUIT BREAKER = SIZE OF CONDUIT = _____________ _____________AT, mm2 , DIA. PVC VOLT Page 8 ELECTRICAL LOAD WORKSHEET NUMBER CIRCUIT TO BE INSTALLED NOTE: IDENTIFY THE ROOMS AND THE NUMBER OF LAMPS TO BE CONNECTED IN ONE CIRCUIT. CIRC UIT NO. 1 2 ROOM NAME NO. OF LAMPS I VA / 230 V bedroom 3 1.304 Kitchen/dining 4 2.173 C.R. 2 0.869 Master bedroom 4 2.173 Living 6 2.608 CURRENT AMPS 4.346 4.781 DETERMINE THE SIZE OF WIRE, CONDUIT AND OVERLOAD PROTECTIVE DEVICE OF EACH CIRCUIT. CIRCUIT NO. SIZE OF WIRE AND CONDUIT SIZE OF OVERLOAD PROTECTIVE DEVICE 1 2-2.0 sq. mm TW copper wire 2 2-2.0 sq. mm TW copper wire 15 AT 15 AT Page 9 ELECTRICAL LOAD WORKSHEET NUMBER CIRCUIT TO BE INSTALLED NOTE: IDENTIFY THE ROOMS AND THE NUMBER OF CONVENIENCE OUTLET NOT INCLUDING LARGE MOTOR LOADS,ACU, AND HEATING LOADS 8000 W AND ABOVE TO BE CONNECTED IN ONE CIRCUIT. CIRC UIT NO. 3 ROOM NAME NO. OF C.O. VA / 230 V CURRENT AMPS bedroom 2 - 2 gang 3.130 7.825 Kitchen/dining 3 - 2 gang 4.695 2 - 2 gang 1-3 gang 2 - 2 gang 5.714 C.R. Master bedroom Living 8.844 3.130 16.669 DETERMINE THE SIZE OF WIRE, CONDUIT AND OVERLOAD PROTECTIVE DEVICE OF EACH CIRCUIT. CIRCUIT NO. 3 SIZE OF WIRE AND CONDUIT 3.5 sq. mm TW copper wire Page 10 SIZE OF OVERLOAD PROTECTIVE DEVICE 20 AT ELECTRICAL LOAD WORKSHEET NUMBER CIRCUIT TO BE INSTALLED NOTE: IDENTIFY THE ROOMS AND THE NUMBER OF LARGE MOTOR LOADS,ACU, AND HEATING LOADS 8000 W AND ABOVE TO BE CONNECTED . EACH LOAD MUST HAVE A SEPARATE OVERLOAD PROTECTIVE DEVICE. CIRCUIT NO. 4 LOAD CURRENT AMPS 6.081 1119 W DETERMINE THE SIZE OF WIRE, CONDUIT AND OVERLOAD PROTECTIVE DEVICE OF EACH CIRCUIT. CIRCUIT NO. SIZE OF WIRE AND CONDUIT SIZE OF OVERLOAD PROTECTIVE DEVICE 4 5.5 sq. mm TW copper wire 30 AT Page 11 ELECTRICAL LOAD WORKSHEET TOTAL DEMAND ON SYSTEM ( WITH AIRCONS AND MOTOR LOADS) Sum of all totals : = _____1900____watts 1. LIGHTING LOAD TOTAL 2. 3. 4. 5. CONVENIENCE OUTLET TOTAL =___3780______watts WATER HEATER TOTAL (if any) =_________________watts COOKING TOTAL (if any) = _______________watts MISCELLANEOUS EQUIPMENT TOTAL =__________________watts ( If any ) SPACE HEATING/AIR CONDITIONING TOTAL =___1119_________watts 6. TOTAL LOAD = _______6799________watts MAIN SERVICE SIZING ( WITH AIRCONS AND MOTOR LOADS) 1. LOAD AMPACITY = ( ___6799_watts / 230 V ) X LOAD AMPACITY 125 % =_____29.56 x 1.25_= 36.95_ I = 36.95 x demand factor (80%) = 29.56 AMPS A 2. SIZE OF CONDUCTORS =____8.0_______mm2 , ___THW__ Cu.WIRE 3. MINIMUM SIZE OF CIRCUIT BREAKER USE _40 ___ AT 4. SIZE OF CONDUIT 5. SIZE OF GROUND CONDUCTORS =___________mm2,_______ Cu.WIRE ATTACHED WITH ARE 1. 2. 3. 4. 5. = ______25____ mm2 , : FLOOR PLAN LIGHTING LAYOUT POWER LAYOUT SCHEDULE OF LOADS ONE LINE DIAGRAM Page 12 DIA. ____RSC___PIPE