Outdoor AIS Substation Design: MV & HV SS 1.0 Substation & Its Equipment Introduction to Substation A SUBSTATION Substation : From where comes from • According to CIGRE Green Book on Substations • When substations were first installed, they were considered to be associated with a single generating station; hence the name “substations” was first used. • In the modern network, substations play a key role in assuring network stability and safety by providing sensing and switching functions to detect line faults and rapidly isolate these faults to maintain overall grid stability. What is a substation • According to IEEE std 605 • Substation bus systems provide the following functions: • a) The means to allow more than one electric circuit to connect to the substation • b) The means for incoming and outgoing circuit termination • c) The means for electrically interconnecting switching and other equipment such as transformers, capacitors banks, reactors, and so on Functions of Substation • According to CIGRE Green Book on Substations • The transmission and distribution network performs three main functions: a) The transmission of electric power from generating stations (or other networks) to load centers b) The interconnection function, which improves security of supply and allows a reduction in generation costs c) The supply function, which consists of supplying the electric power to subtransmission or distribution transformers and in some cases to customers directly, connected to the transmission and distribution network These Functions are achieved by different types of Substations Functions : • From Alstom Substation Design/Application Guide • Substation provides interconnection of transmission circuits and transformation between network of different voltages. • The substation is connected to the network through overhead lines. In some cases it may not be possible to make connection to the substation directly by the overhead line and cable entry must be considered. Substation : Use • A substation is part of a system and not an entity to itself. Normally, a power system is designed so that the effects of an outage (caused by the failure of a single component such as a transformer, transmission line, or distribution line) will result in minimal interruption of service and affect the fewest customers possible. • Failure of one component in a system often forces a greater than normal load to be carried by other components of the system. • Such contingencies are normally planned for and incorporated into design criteria. USDA: • There are four major types of substations. • switchyard at a generating station • customer substation • system station • distribution station Substation type and use • Generating substation • The second type of substation, typically known as the customer substation, functions as the main source of electric power supply for one particular business customer. • The technical requirements and the business case for this type of facility depend highly on the customer’s requirements, more so than on utility needs. Parts of Substation • Primary Equipment /system : Equipment those are is in service at highest operating voltage of system/substation • Secondary Equipment /system : Those are used for control (local & remote) , protection, monitoring ,automation & measurement of primary equipment • Auxiliary system: Those are used for interconnection between Primary Equipment /system and Secondary Equipment /system or those are required to enable to operate Primary Equipment /system and Secondary Equipment /system Parts of Substation • Substation generally comprises the following : a) Switchgear b) Power Transformers c) Protection, Control and Monitoring of Equipment d) Busbars and Bays e) Reactive Power Compensation including Harmonic Filters f) Substation Lightning Protection System g) Substation Earthing System Other non-major parts • Internal & periphery roads • Security barak • Gates • Control Rooms • Fire-Fighting system • Security Boundary Wall • Fencing • Gantries • Equipment support structures Other non-major parts • Insulators • Indoor & Outdoor Lighting • Light post • Security guard post • Gardening , solar, diesel generators Substation comprises three main components • These are classified as Primary System, Secondary System and Auxiliary Supply System. i. Primary System Primary system comprises all equipment which are in service at the nominal voltage system. i. Secondary System • The secondary system comprises all equipments which are used for the control, protection, measurement and monitoring of primary equipment. • iii) Auxiliary Supply System AC supplies and DC supplies • Auxiliary supply system comprises all equipment such as AC supplies and DC supplies that enable protection, control, measurement and monitoring equipment to operate. • a) DC Supply and Distribution Systems – provided to ensure that a secure supply is available at all times to power protection systems, control equipment and initiate tripping of circuit breakers and comprise : • Batteries – either lead acid or nickel-alkali types at ratings from tens of ampere hours to hundreds of ampere hours at voltages of 30V, 50V, 125V and 250V depending on the application. • Battery Charger – usually constant voltage, current limited types with boost charge • facility to supply standing loads and maintain the battery fully charged whilst the auxiliary AC supply is available. • Distribution Board – as the name implies, provides a system of distribution, isolation and protection for DC supplies to all equipment within the substation. • b) LVAC Supplies – an auxiliary AC supply and distribution system which supports the operation of the substation by providing power for cooling fan motors, tap change motors, circuit breaker mechanism charging systems and disconnector drives in addition to the normal heating, lighting and domestic loads. CIGRE Green Book on Substations • The overall function of a substation within the network is to transform voltages from one level to another and also to provide switching functions to provide a connection between the sources of energy and the ultimate consumer providing protection for the grid and its components. In a power network, substations can be considered to be “nodes,” enabling connection between transmission and distribution lines and the safe connection and disconnection of one line to another. General functions of Components Transmission/Distribution Line: Delivers Load towards other end or Carries to this end Gantry Arrangement : a) To physically hold Circuits : Incoming or outgoing line /transformer b) To hold Busbar circuits Switchgear: Enable switching functions Transformer : Enables Transformation of Voltage for suitable purpose General functions of Components a) b) c) Surge Arrester : Provides protection from Lighting & Switching surge when suitably selected Instrument Transformer: Provides Instrumentation & Enables Monitoring functions Enables Measuring & Metering functions Enables Control & Protection functions Relay : Provides Protection functions in combination of IT & CB. Aux Transformer : Provides substation auxiliary & service power General functions of Components • LV Control Cable: enable instrumentation, control & protection functions • SAS: Provides automation of SS; works as back-bone of SCADA & remote communication • SCADA & Telecom device: enables remote communication for control & monitoring • Control Room : For operator for monitoring & operation • Roads: for operation & maintenance access & transportation of maintenance equipment SLD & Layout : • Single Line Diagram : Also called One line Diagram in the US/Canada • It describes the switchgear , other associated components symbolic representation and their interconnections • It shows rating of the components also • Layout • It shows the location of different equipment within the substation • It is the basis of electrical connections , all civil works and installation & erection works Substation Component Grounding system • Consists of grid mesh conductor, downward rod conductor, earth test terminals, equipment earthing terminals Lightning protection system • Switchyard & Building • For Switchyard best option is shield wire; if not possible Lightning mast is good option • For Building lighting rod is used Substation Protection system • Consists of main relays & auxiliary relay, panels • Functions is to sense faulty condition of system and send trip command to circuit breaker • Takes low power current & voltage from sensing equipment CT & PT Control & automation system & SCADA system • Control Mimic • Bay control unit • Automation PC • Ethernet switches • GPS clock • Gateway PC • Firewall : Hardware & software to block possible malware • Ethernet & Fiber optic cable Communication system • Two functions • Telecommunication & tele-protection • Two versions/technology • PLCCS & FOCS • PLCCS consists of Line Trap (HV side), CVT or CCV, Line matching unit , PLC terminal device for processing, analyzing, rx-tx of data • FOCS consists of Fiber optic multiplexer , fiber optic patch cables, Optical distribution boards DC system • Consists of DC battery, Charger DC Distribution Board • Typically 110V or 220V is used for power of Control , Protection & automation system and 48V is used for power of Communication & SCADA system • 110V or 220V DC is non-earthed system • 48V DC system is earthed : +ve is grounded to system earth • Ni-Cd battery is generally used Substation auxiliary or LV AC system • Consists of • 33/0.415kv or 11/0.415kV transformer • 415V XLPE power cable • AC distribution board • Lighting : Indoor & outdoor • Air condition system AIS , GIS and MTS • AIS : Air Insulated Switchgear , Around 70% of Substations in the world are AIS • GIS : Gas insulated switchgear , SF6 is pre-dominantly used as insulating gas; It takes less space, have longer life span, less construction time • MTS: Mixed Technology Switchgear Some switchgear are AIS and some are GIS