nd 2 complete, non-project related edition th Basis VGB 4 Edition Revision b, Condition-Date: January 20, 1999 Identification System for Power Plants Function key Equipment unit key Component key Proj.-Code. UA Contents Code ZEN000 DA01 383 Consec. No. UNID Index 970404 1 000 822 159 b KKS Identification System for Power Plants Change notification No. 2 Revision „b“ of 20.01.99 Please print out the pages and update your KKS Manual according to the following table. For print-out on both sides the pages HA1 of HA1, HN1 of HN1 and HS1 of HS2 have been added. Page Index H1 of H1 HR1 of HR2 HR2 of HR2 b a a KWU OI42 Hünecke Tel. +49 (0)69/807-2078 Revision date 20.01.99 20.01.99 20.01.99 Exchange Addition Deletion Remarks X X X 31.07.98 KKS Identification System for Power Plants Change notification No. 1 Revision „a“ of 31.07.98 To update your KKS Manual you find the revised pages in the Intranet: KWU-Homepage/Handbücher, Regelwerke/KKS Documentation. Please print out the pages and update your KKS Manual according to the following table. Page Index HA1 of HA1 MB1 of MB2 MF1 of MF1 MG1 of MG1 MK1 of MK1 X1 of X1 XG1 of XG1 XK1 of XK1 a a a a a a a a KWU OI42 Hünecke Tel. +49 (0)69/807-2078 Revision date 31.07.98 31.07.98 31.07.98 31.07.98 31.07.98 31.07.98 31.07.98 31.07.98 Exchange Addition Deletion Remarks X X X X X X X X 31.07.98 Siemens 2 nd complete, non-project related edition Identification System for Power Plants General view Function key Condition-Date: 04.04.97 A Grid and distribution systems B Power transmission and auxiliary power supply C Instrumentation and control equipment D Instrumentation and control equipment E Conventional fuel supply and residues disposal F Handling of nuclear equipment G Water supply and disposal H Conventional heat generation J Nuclear heat generation K Reactor auxiliary systems L Steam, water, gas cycles M Main machine sets N Process energy supply for external users (e. g. district heating) P Cooling water systems Q Auxiliary systems R Gas generation and treatment S Ancillary systems U Structures W Renewable energy plants X Heavy machinery (not main machine sets) Z Workshop and office equipment Printout date: 12. Sep. 01 Page 1 of 1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : A 04.04.97 A Grid and distribution systems AB > 420 kV systems AC 380 - (420) kV systems AD 220 - (245) kV systems AE 110 - (150) kV systems AF 60 - (72) kV systems AG 45 - (50) kV systems AH 30 - (35) kV systems AJ 20 - (25) kV systems AK 10 - (15) kV systems AL 6 - (5) kV systems AM 1 - 3 kV systems AN < 1 kV systems AP Control consoles AQ Measuring and metering equipment AR Protection equipment AS Decentralized panels and cabinets AT Transformer equipment AU Open-loop control, checkback and auxiliary equipment AV Marshalling racks AW Instrument panels AX Central equipment AY Communication equipment Printout date 14. Mrz. 01 Page A1 of A1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : AB 04.04.97 A Grid and distribution systems AB > 420 kV systems Printout date 14. Mrz. 01 Page AB1 of AB1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : AC 04.04.97 A Grid and distribution systems AC 380 - (420) kV systems Printout date 14. Mrz. 01 Page AC1 of AC1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : AD 04.04.97 A Grid and distribution systems AD 220 - (245) kV systems Printout date 14. Mrz. 01 Page AD1 of AD1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : AE 04.04.97 A Grid and distribution systems AE 110 - (150) kV systems Printout date 14. Mrz. 01 Page AE1 of AE1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : AF 04.04.97 A Grid and distribution systems AF 60 - (72) kV systems Printout date 14. Mrz. 01 Page AF1 of AF1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : AG 04.04.97 A Grid and distribution systems AG 45 - (50) kV systems Printout date 14. Mrz. 01 Page AG1 of AG1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : AH 04.04.97 A Grid and distribution systems AH 30 - (35) kV systems Printout date 14. Mrz. 01 Page AH1 of AH1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : AJ 04.04.97 A Grid and distribution systems AJ 20 - (25) kV systems Printout date 14. Mrz. 01 Page AJ1 of AJ1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : AK 04.04.97 A Grid and distribution systems AK 10 - (15) kV systems Printout date 14. Mrz. 01 Page AK1 of AK1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : AL 04.04.97 A Grid and distribution systems AL 6 - (5) kV systems Printout date 14. Mrz. 01 Page AL1 of AL1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : AM 04.04.97 A Grid and distribution systems AM 1 - 3 kV systems Printout date 14. Mrz. 01 Page AM1 of AM1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : AN 04.04.97 A Grid and distribution systems AN < 1 kV systems ANA Low voltage switchgear 500-1000 V, AC ANB Low voltage switchgear 500-1000 V, AC ANC Low voltage switchgear 500-1000 V, AC ANE Low voltage switchgear 380/220 V, AC ANF Low voltage switchgear 380/220 V, AC ANG Low voltage switchgear 380/220 V, AC ANH Low voltage switchgear 380/220 V, AC ANK DC switchgear 220/110 V ANL DC switchgear 220/110 V ANM DC switchgear 220/110 V ANN DC switchgear 220/110 V ANQ DC switchgear 60/48 V ANR DC switchgear 60/48 V ANS DC switchgear 60/48 V ANU DC switchgear 24/12 V ANV DC switchgear 24/12 V ANW DC switchgear 24/12 V Printout date 14. Mrz. 01 Page AN1 of AN1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : AP 04.04.97 A Grid and distribution systems AP Control consoles Printout date 14. Mrz. 01 Page AP1 of AP1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : AQ 04.04.97 A Grid and distribution systems AQ Measuring and metering equipment Printout date 14. Mrz. 01 Page AQ1 of AQ1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : AR 04.04.97 A Grid and distribution systems AR Protection equipment Printout date 14. Mrz. 01 Page AR1 of AR1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : AS 04.04.97 A Grid and distribution systems AS Decentralized panels and cabinets ASA Circuit breaker appurtenances ASB Multiplication, conversion, decoupling ASC Transducer appurtenances ASD Compressed air, hydraulics ASJ Automated controls, closed-loop control ASL Grid simulation, voltage group selection ASM Measuring equipment ASN Auxiliary power supply ASP Recording ASQ Metering ASR Protection ASS Synchronization AST Transformation ASU Panels and cabinets for auxiliary equipment ASV Group, intermediate and general terminal blocks ASW Indication, manual operation, monitoring ASX Alarm annunciation Printout date 14. Mrz. 01 Page AS1 of AS1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : AT 04.04.97 A Grid and distribution systems AT Transformer equipment Printout date 14. Mrz. 01 Page AT1 of AT1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : AU 04.04.97 A Grid and distribution systems AU Open-loop control, checkback and auxiliary equipment Printout date 14. Mrz. 01 Page AU1 of AU1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : AV 04.04.97 A Grid and distribution systems AV Marshalling racks Printout date 14. Mrz. 01 Page AV1 of AV1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : AW 04.04.97 A Grid and distribution systems AW Instrument panels Printout date 14. Mrz. 01 Page AW1 of AW1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : AX 04.04.97 A Grid and distribution systems AX Central equipment Printout date 14. Mrz. 01 Page AX1 of AX1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : AY 04.04.97 A Grid and distribution systems AY Communication equipment AYA Telephone system (PABX) AYB Control console telephone system AYC Alarm system (acoustic) AYD Alarm system (optical) AYE Fire alarm system AYF Clock system AYG Remote control system AYH Telemetry system AYJ Remote metering system AYK HF carrier telephone system AYL Staff paging system, wireless AYM Staff paging system, inductive AYN Staff paging system, hardwired AYP Optical monitoring system AYQ General gas detection system (if not assigned to specific system) AYS Radiotelephone system Printout date 14. Mrz. 01 Page AY1 of AY1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : B 04.04.97 B Power transmission and auxiliary power supply BA Power transmission BB Medium-voltage distribution boards and transformers, normal system BC Medium-voltage distribution boards and transformers, general-purpose BD Medium-voltage emergency distribution boards and transformers, (diesel) emergency power system 1 BF Low-voltage main distribution boards and transformers, normal system BG Low-voltage distribution boards and transformers, (may be used in addition to *BF*, *BH*, *BJ*, *BK* and *BL*) BH Low-voltage main distribution boards and transformers, general-purpose BJ Low-voltage subdistribution boards and transformers, normal system BK Low-voltage distribution boards and transformers, (may be used in addition to *BF*, *BG*, *BH*, *BJ* and *BL*) BL Low-voltage subdistribution boards and transformers, general-purpose (local switchgear) BM Low-voltage distribution boards and transformers, (diesel) emergency power system 1 BN Low-voltage distribution boards and transformers, (diesel) emergency power system 2 (protection against external impact) BP Power installations for variable-speed drives (e. g. for feedwater pump, excitation equipment, not power adjusters in switchgear) BR Low-voltage distribution boards, uninterruptible (converter) power supply BT Battery systems BU DC distribution boards, normal system BV DC distribution boards, emergency power system 1 BW DC distribution boards, emergency power system 2 (protection against external impact) BX Fluid supply system for control and protection equipment BY Control and protection equipment Printout date 14. Mrz. 01 Page B1 of B1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : BA 04.04.97 B Power transmission and auxiliary power supply BA Power transmission BAA Generator leads Limit: from excl. generator bushings, incl. current and voltage transformers, cooling and ventilation systems to excl. generator transformer low side bushings or to excl. auxiliary power transformer high side bushings BAB Foundation cabinets BAC Generator circuit breaker, also commutating pole circuit breaker, incl. cooling system BAT Generator transformers, including cooling system BAU Earthing and lightning protection systems BAX Control air supply system BAY Control and protection equipment Printout date 14. Mrz. 01 Page BA1 of BA1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : BB 04.04.97 B Power transmission and auxiliary power supply BB Medium-voltage distribution boards and transformers, normal system BBA MV distribution board BBB MV distribution board BBC MV distribution board BBD MV distribution board BBE MV distribution board BBF MV distribution board BBG MV distribution board BBH MV distribution board BBJ MV distribution board BBK MV distribution board BBL MV distribution board BBM MV distribution board BBN MV distribution board BBP MV distribution board BBQ MV distribution board BBR MV distribution board BBS MV distribution board BBT MV auxiliary power transformers BBX Fluid supply system for control and protection equipment BBY Control and protection equipment Printout date 14. Mrz. 01 Page BB1 of BB1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : BC 04.04.97 B Power transmission and auxiliary power supply BC Medium-voltage distribution boards and transformers, general-purpose BCA MV start-up distribution board BCB MV start-up distribution board BCC MV start-up distribution board BCD MV start-up distribution board BCE MV start-up distribution board BCF MV start-up distribution board BCG MV start-up distribution board BCH MV start-up distribution board BCJ MV start-up distribution board BCK MV start-up distribution board BCL MV start-up distribution board BCM MV start-up distribution board BCN MV start-up distribution board BCP MV start-up distribution board BCQ MV start-up distribution board BCR MV start-up distribution board BCS MV start-up distribution board BCT Start-up, offsite, general-purpose transformers BCX Fluid supply system for control and protection equipment BCY Control and protection equipment Printout date 14. Mrz. 01 Page BC1 of BC1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : BD 04.04.97 B Power transmission and auxiliary power supply BD Medium-voltage emergency distribution boards and transformers, (diesel) emergency power system 1 BDA MV emergency distribution board BDB MV emergency distribution board BDC MV emergency distribution board BDD MV emergency distribution board BDE MV emergency distribution board BDF MV emergency distribution board BDG MV emergency distribution board BDH MV emergency distribution board BDJ MV emergency distribution board BDK MV emergency distribution board BDL MV emergency distribution board BDM MV emergency distribution board BDN MV emergency distribution board BDP MV emergency distribution board BDQ MV emergency distribution board BDR MV emergency distribution board BDS MV emergency distribution board BDT MV transformator BDX Fluid supply system for control and protection equipment BDY Control and protection equipment Printout date 14. Mrz. 01 Page BD1 of BD1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : BF 04.04.97 B Power transmission and auxiliary power supply BF Low-voltage main distribution boards and transformers, normal system BFA LV main distribution board BFB LV main distribution board BFC LV main distribution board BFD LV main distribution board BFE LV main distribution board BFF LV main distribution board BFG LV main distribution board BFH LV main distribution board BFJ LV main distribution board BFK LV main distribution board BFL LV main distribution board BFM LV main distribution board BFN LV main distribution board BFP LV main distribution board BFQ LV main distribution board BFR LV main distribution board BFS LV main distribution board BFT LV auxiliary power transformer BFU LV auxiliary power transformer BFV LV auxiliary power transformer BFW LV auxiliary power transformer BFX Fluid supply system for control and protection equipment BFY Control and protection equipment Printout date 14. Mrz. 01 Page BF1 of BF1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : BG 04.04.97 B Power transmission and auxiliary power supply BG Low-voltage distribution boards and transformers, (may be used in addition to *BF*, *BH*, *BJ*, *BK* and *BL*) BGA LV distribution board BGB LV distribution board BGC LV distribution board BGD LV distribution board BGE LV distribution board BGF LV distribution board BGG LV distribution board BGH LV distribution board BGJ LV distribution board BGK LV distribution board BGL LV distribution board BGM LV distribution board BGN LV distribution board BGP LV distribution board BGQ LV distribution board BGR LV distribution board BGS LV distribution board BGT LV auxiliary power transformer BGU LV auxiliary power transformer BGV LV auxiliary power transformer BGW LV auxiliary power transformer BGX Fluid supply system for control and protection equipment BGY Control and protection equipment Printout date 14. Mrz. 01 Page BG1 of BG1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : BH 04.04.97 B Power transmission and auxiliary power supply BH Low-voltage main distribution boards and transformers, general-purpose BHA LV main distribution board BHB LV main distribution board BHC LV main distribution board BHD LV main distribution board BHE LV main distribution board BHF LV main distribution board BHG LV main distribution board BHH LV main distribution board BHJ LV main distribution board BHK LV main distribution board BHL LV main distribution board BHM LV main distribution board BHN LV main distribution board BHP LV main distribution board BHQ LV main distribution board BHR LV main distribution board BHS LV main distribution board BHT LV auxiliary power transformer BHU LV auxiliary power transformer BHV LV auxiliary power transformer BHW LV auxiliary power transformer BHX Fluid supply system for control and protection equipment BHY Control and protection equipment Printout date 14. Mrz. 01 Page BH1 of BH1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : BJ 04.04.97 B Power transmission and auxiliary power supply BJ Low-voltage subdistribution boards and transformers, normal system BJA LV sudistribution board BJB LV sudistribution board BJC LV sudistribution board BJD LV sudistribution board BJE LV sudistribution board BJF LV sudistribution board BJG LV sudistribution board BJH LV sudistribution board BJJ LV sudistribution board BJK LV sudistribution board BJL LV sudistribution board BJM LV sudistribution board BJN LV sudistribution board BJP LV sudistribution board BJQ LV sudistribution board BJR LV sudistribution board BJS LV sudistribution board BJT LV auxiliary power transformer BJX Fluid supply system for control and protection equipment BJY Control and protection equipment Printout date 14. Mrz. 01 Page BJ1 of BJ1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : BK 04.04.97 B Power transmission and auxiliary power supply BK Low-voltage distribution boards and transformers, (may be used in addition to *BF*, *BG*, *BH*, *BJ* and *BL*) BKA LV distribution board BKB LV distribution board BKC LV distribution board BKD LV distribution board BKE LV distribution board BKF LV distribution board BKG LV distribution board BKH LV distribution board BKJ LV distribution board BKK LV distribution board BKL LV distribution board BKM LV distribution board BKN LV distribution board BKP LV distribution board BKQ LV distribution board BKR LV distribution board BKS LV distribution board BKT LV auxiliary power transformer BKU LV auxiliary power transformer BKV LV auxiliary power transformer BKW LV auxiliary power transformer BKX Fluid supply system for control and protection equipment BKY Control and protection equipment Printout date 14. Mrz. 01 Page BK1 of BK1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : BL 04.04.97 B Power transmission and auxiliary power supply BL Low-voltage subdistribution boards and transformers, general-purpose (local switchgear) BLA LV subdistribution board BLB LV subdistribution board BLC LV subdistribution board BLD LV subdistribution board BLE LV subdistribution board BLF LV subdistribution board BLG LV subdistribution board BLH LV subdistribution board BLJ LV subdistribution board BLK LV subdistribution board BLL LV subdistribution board BLM LV subdistribution board BLN LV subdistribution board BLP LV subdistribution board BLQ LV subdistribution board BLR LV subdistribution board BLS LV subdistribution board BLT LV auxiliary power transformer BLX Fluid supply system for control and protection equipment BLY Control and protection equipment Printout date 14. Mrz. 01 Page BL1 of BL1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : BM 04.04.97 B Power transmission and auxiliary power supply BM Low-voltage distribution boards and transformers, (diesel) emergency power system 1 BMA LV emergency distribution board BMB LV emergency distribution board BMC LV emergency distribution board BMD LV emergency distribution board BME LV emergency distribution board BMF LV emergency distribution board BMG LV emergency distribution board BMH LV emergency distribution board BMJ LV emergency distribution board BMK LV emergency distribution board BML LV emergency distribution board BMM LV emergency distribution board BMN LV emergency distribution board BMP LV emergency distribution board BMQ LV emergency distribution board BMR LV emergency distribution board BMS LV emergency distribution board BMT LV auxiliary power transformer BMU LV auxiliary power transformer BMV LV auxiliary power transformer BMW LV auxiliary power transformer BMX Fluid supply system for control and protection equipment BMY Control and protection equipment Printout date 14. Mrz. 01 Page BM1 of BM1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : BN 04.04.97 B Power transmission and auxiliary power supply BN Low-voltage distribution boards and transformers, (diesel) emergency power system 2 (protection against external impact) BNA LV distribution board BNB LV distribution board BNC LV distribution board BND LV distribution board BNE LV distribution board BNF LV distribution board BNG LV distribution board BNH LV distribution board BNJ LV distribution board BNK LV distribution board BNL LV distribution board BNM LV distribution board BNN LV distribution board BNP LV distribution board BNQ LV distribution board BNR LV distribution board BNS LV distribution board BNT LV auxiliary power transformer BNU LV auxiliary power transformer BNV LV auxiliary power transformer BNW LV auxiliary power transformer BNX Fluid supply system for control and protection equipment BNY Control and protection equipment Printout date 14. Mrz. 01 Page BN1 of BN1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : BP 04.04.97 B Power transmission and auxiliary power supply BP Power installations for variable-speed drives (e. g. for feedwater pump, excitation equipment, not power adjusters in switchgear) BPA Power installations for variable-speed drives BPB Power installations for variable-speed drives BPC Power installations for variable-speed drives BPD Power installations for variable-speed drives BPE Power installations for variable-speed drives BPF Power installations for variable-speed drives BPG Power installations for variable-speed drives BPH Power installations for variable-speed drives BPJ Power installations for variable-speed drives BPK Power installations for variable-speed drives BPL Power installations for variable-speed drives BPM Power installations for variable-speed drives BPN Power installations for variable-speed drives BPP Power installations for variable-speed drives BPQ Power installations for variable-speed drives BPR Power installations for variable-speed drives BPS Power installations for variable-speed drives BPT Power installations for variable-speed drives BPU Power installations for variable-speed drives BPX Fluid supply system for control and protection equipment BPY Control and protection equipment Printout date 14. Mrz. 01 Page BP1 of BP1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : BR 04.04.97 B Power transmission and auxiliary power supply BR Low-voltage distribution boards, uninterruptible (converter) power supply BRA LV distribution board, uninterruptible (converter) power supply BRB LV distribution board, uninterruptible (converter) power supply BRC LV distribution board, uninterruptible (converter) power supply BRD LV distribution board, uninterruptible (converter) power supply BRE LV distribution board, uninterruptible (converter) power supply BRF LV distribution board, uninterruptible (converter) power supply BRG LV distribution board, uninterruptible (converter) power supply BRH LV distribution board, uninterruptible (converter) power supply BRJ LV distribution board, uninterruptible (converter) power supply BRK LV distribution board, uninterruptible (converter) power supply BRL LV distribution board, uninterruptible (converter) power supply BRM LV distribution board, uninterruptible (converter) power supply BRN LV distribution board, uninterruptible (converter) power supply BRP LV distribution board, uninterruptible (converter) power supply BRQ LV distribution board, uninterruptible (converter) power supply BRR LV distribution board, uninterruptible (converter) power supply BRS LV distribution board, uninterruptible (converter) power supply BRT Converter (rotary) BRU Converter (static), inverter BRV Emergency power generating equipment (if not under *X* = Heavy Machinery) BRX Fluid supply system for control and protection equipment BRY Control and protection equipment Printout date 14. Mrz. 01 Page BR1 of BR1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : BT 04.04.97 B Power transmission and auxiliary power supply BT Battery systems BTA Batteries BTB Batteries BTC Batteries BTD Batteries BTE Batteries BTF Batteries BTG Batteries BTH Batteries BTJ Batteries BTK Batteries BTL Rectifiers, battery chargers BTM Rectifiers, battery chargers BTN Rectifiers, battery chargers BTP Rectifiers, battery chargers BTQ Rectifiers, battery chargers BTR Rectifiers, battery chargers BTS Rectifiers, battery chargers BTT Rectifiers, battery chargers BTU Rectifiers, battery chargers BTV Rectifiers, battery chargers BTW Common equipment BTX Common equipment BTY Common equipment BTZ Common equipment Printout date 14. Mrz. 01 Page BT1 of BT1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : BU 04.04.97 B Power transmission and auxiliary power supply BU DC distribution boards, normal system BUA DC distribution board BUB DC distribution board BUC DC distribution board BUD DC distribution board BUE DC distribution board BUF DC distribution board BUG DC distribution board BUH DC distribution board BUJ DC distribution board BUK DC distribution board BUL DC distribution board BUM DC distribution board BUN DC distribution board BUP DC distribution board BUQ DC distribution board BUR DC distribution board BUS DC distribution board BUX Fluid supply system for control and protection equipment BUY Control and protection equipment Printout date 14. Mrz. 01 Page BU1 of BU1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : BV 04.04.97 B Power transmission and auxiliary power supply BV DC distribution boards, emergency power system 1 BVA DC distribution board BVB DC distribution board BVC DC distribution board BVD DC distribution board BVE DC distribution board BVF DC distribution board BVG DC distribution board BVH DC distribution board BVJ DC distribution board BVK DC distribution board BVL DC distribution board BVM DC distribution board BVN DC distribution board BVP DC distribution board BVQ DC distribution board BVR DC distribution board BVS DC distribution board BVX Fluid supply system for control and protection equipment BVY Control and protection equipment Printout date 14. Mrz. 01 Page BV1 of BV1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : BW 04.04.97 B Power transmission and auxiliary power supply BW DC distribution boards, emergency power system 2 (protection against external impact) BWA DC distribution board BWB DC distribution board BWC DC distribution board BWD DC distribution board BWE DC distribution board BWF DC distribution board BWG DC distribution board BWH DC distribution board BWJ DC distribution board BWK DC distribution board BWL DC distribution board BWM DC distribution board BWN DC distribution board BWP DC distribution board BWQ DC distribution board BWR DC distribution board BWS DC distribution board BWX Fluid supply system for control and protection equipment BWY Control and protection equipment Printout date 14. Mrz. 01 Page BW1 of BW1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : BX 04.04.97 B Power transmission and auxiliary power supply BX Fluid supply system for control and protection equipment BXA Fluid supply system for control and protection equipment BXB Fluid supply system for control and protection equipment BXC Fluid supply system for control and protection equipment BXD Fluid supply system for control and protection equipment BXE Fluid supply system for control and protection equipment BXF Fluid supply system for control and protection equipment BXG Fluid supply system for control and protection equipment BXH Fluid supply system for control and protection equipment BXJ Fluid supply system for control and protection equipment BXK Fluid supply system for control and protection equipment BXL Fluid supply system for control and protection equipment BXM Fluid supply system for control and protection equipment BXN Fluid supply system for control and protection equipment BXP Fluid supply system for control and protection equipment BXQ Fluid supply system for control and protection equipment BXR Fluid supply system for control and protection equipment BXS Fluid supply system for control and protection equipment BXT Fluid supply system for control and protection equipment BXU Fluid supply system for control and protection equipment Printout date 14. Mrz. 01 Page BX1 of BX1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : BY 04.04.97 B Power transmission and auxiliary power supply BY Control and protection equipment BYA Control and protection equipment BYB Control and protection equipment BYC Control and protection equipment BYD Control and protection equipment BYE Control and protection equipment BYF Control and protection equipment BYG Control and protection equipment BYH Control and protection equipment BYJ Control and protection equipment BYK Control and protection equipment BYL Control and protection equipment BYM Control and protection equipment BYN Control and protection equipment BYP Control and protection equipment BYQ Control and protection equipment BYR Control and protection equipment BYS Control and protection equipment BYT Control and protection equipment BYU Control and protection equipment Printout date 14. Mrz. 01 Page BY1 of BY1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : C 04.04.97 C Instrumentation and control equipment CA Protective interlocks CB Functional group control, subloop control CC Binary signal conditioning CD Drive control interface CE Annunciation CF Measurement, recording CG Closed-loop control (excl. power section) CH Protection (excl. reactor protection) CJ Unit coordination level CK Process computer system CL Reactor protection CR Programmable process control systems and associated cabinets CU Closed-loop control (power section) CV Marshalling racks CW Control rooms CX Local control stations (e. g. for solid fuel supply system, ash removal system, cooling water system, diesel engine plant, monitoring of generator cooling, emergency control station) CY Communication equipment Printout date 14. Mrz. 01 Page C1 of C1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : CA 04.04.97 C Instrumentation and control equipment CA Protective interlocks CAA Cabinets for protective interlocks CAB Cabinets for protective interlocks CAC Cabinets for protective interlocks CAD Cabinets for protective interlocks CAE Cabinets for protective interlocks CAF Cabinets for protective interlocks CAG Cabinets for protective interlocks CAH Cabinets for protective interlocks CAJ Cabinets for protective interlocks CAK Cabinets for protective interlocks CAL Cabinets for protective interlocks CAM Cabinets for protective interlocks CAN Cabinets for protective interlocks CAP Cabinets for protective interlocks CAQ Cabinets for protective interlocks CAR Cabinets for protective interlocks, installation in the secured area (of nuclear power plant) CAS Cabinets for protective interlocks, installation in the secured area (of nuclear power plant) CAT Cabinets for protective interlocks, installation in the secured area (of nuclear power plant) CAU Cabinets for protective interlocks, installation in the secured area (of nuclear power plant) CAV Cabinets for protective interlocks, installation in the secured area (of nuclear power plant) CAW Cabinets for protective interlocks, installation in the secured area (of nuclear power plant) CAX Cabinets for protective interlocks, installation in the secured area (of nuclear power plant) CAY Cabinets for protective interlocks, installation in the secured area (of nuclear power plant) Printout date 14. Mrz. 01 Page CA1 of CA1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : CB 04.04.97 C Instrumentation and control equipment CB Functional group control, subloop control CBA Cabinets for functional group control CBB Cabinets for functional group control CBC Cabinets for functional group control CBD Cabinets for functional group control CBE Cabinets for functional group control CBF Cabinets for functional group control CBG Cabinets for functional group control CBH Cabinets for functional group control CBJ Cabinets for functional group control CBK Cabinets for functional group control CBL Cabinets for functional group control CBM Cabinets for functional group control CBN Cabinets for functional group control CBP Cabinets for synchronization CBQ Cabinets for auxiliary power changeover CBR Cabinets for functional group control, installation in the secured area (of nuclear power plant) CBS Cabinets for functional group control, installation in the secured area (of nuclear power plant) CBT Cabinets for functional group control, installation in the secured area (of nuclear power plant) CBU Cabinets for functional group control, installation in the secured area (of nuclear power plant) CBV Cabinets for functional group control, installation in the secured area (of nuclear power plant) CBW Cabinets for functional group control, installation in the secured area (of nuclear power plant) CBX Cabinets for functional group control, installation in the secured area (of nuclear power plant) CBY Cabinets for functional group control, installation in the secured area (of nuclear power plant) Printout date 14. Mrz. 01 Page CB1 of CB1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : CC 04.04.97 C Instrumentation and control equipment CC Binary signal conditioning CCA Cabinets for binary signal conditioning CCB Cabinets for binary signal conditioning CCC Cabinets for binary signal conditioning CCD Cabinets for binary signal conditioning CCE Cabinets for binary signal conditioning CCF Cabinets for binary signal conditioning CCG Cabinets for binary signal conditioning CCH Cabinets for binary signal conditioning CCJ Cabinets for binary signal conditioning CCK Cabinets for binary signal conditioning CCL Cabinets for binary signal conditioning CCM Cabinets for binary signal conditioning CCN Cabinets for binary signal conditioning CCP Cabinets for binary signal conditioning CCQ Cabinets for binary signal conditioning CCR Cabinets for binary signal conditioning, installation in the secured area (of nuclear power plant) CCS Cabinets for binary signal conditioning, installation in the secured area (of nuclear power plant) CCT Cabinets for binary signal conditioning, installation in the secured area (of nuclear power plant) CCU Cabinets for binary signal conditioning, installation in the secured area (of nuclear power plant) CCV Cabinets for binary signal conditioning, installation in the secured area (of nuclear power plant) CCW Cabinets for binary signal conditioning, installation in the secured area (of nuclear power plant) CCX Cabinets for binary signal conditioning, installation in the secured area (of nuclear power plant) CCY Cabinets for binary signal conditioning, installation in the secured area (of nuclear power plant) Printout date 14. Mrz. 01 Page CC1 of CC1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : CD 04.04.97 C Instrumentation and control equipment CD Drive control interface CDA Cabinets for drive control interface CDB Cabinets for drive control interface CDC Cabinets for drive control interface CDD Cabinets for drive control interface CDE Cabinets for drive control interface CDF Cabinets for drive control interface CDG Cabinets for drive control interface CDH Cabinets for drive control interface CDJ Cabinets for drive control interface CDK Cabinets for drive control interface CDL Cabinets for drive control interface CDM Cabinets for drive control interface CDN Cabinets for drive control interface CDP Cabinets for drive control interface CDQ Cabinets for drive control interface CDR Cabinets for drive control interface, installation in the secured area (of nuclear power plant) CDS Cabinets for drive control interface, installation in the secured area (of nuclear power plant) CDT Cabinets for drive control interface, installation in the secured area (of nuclear power plant) CDU Cabinets for drive control interface, installation in the secured area (of nuclear power plant) CDV Cabinets for drive control interface, installation in the secured area (of nuclear power plant) CDW Cabinets for drive control interface, installation in the secured area (of nuclear power plant) CDX Cabinets for drive control interface, installation in the secured area (of nuclear power plant) CDY Cabinets for drive control interface, installation in the secured area (of nuclear power plant) Printout date 14. Mrz. 01 Page CD1 of CD1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : CE 04.04.97 C Instrumentation and control equipment CE Annunciation CEA Cabinets for annunciation systems CEB Cabinets for annunciation systems CEC Cabinets for annunciation systems CED Cabinets for annunciation systems CEE Cabinets for annunciation systems CEF Cabinets for annunciation systems CEG Cabinets for annunciation systems CEH Cabinets for annunciation systems CEJ Fault recording CEK Fault recording CEL Fault recording CEM Fault recording CEN Fault recording CEP Fault recording CEQ Fault recording CER Cabinets for annunciation systems, installation in the secured area (of nuclear power plant) CES Cabinets for annunciation systems, installation in the secured area (of nuclear power plant) CET Cabinets for annunciation systems, installation in the secured area (of nuclear power plant) CEU Cabinets for annunciation systems, installation in the secured area (of nuclear power plant) CEV Cabinets for annunciation systems, installation in the secured area (of nuclear power plant) CEW Cabinets for annunciation systems, installation in the secured area (of nuclear power plant) CEX Cabinets for annunciation systems, installation in the secured area (of nuclear power plant) CEY Cabinets for annunciation systems, installation in the secured area (of nuclear power plant) Printout date 14. Mrz. 01 Page CE1 of CE1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : CF 04.04.97 C Instrumentation and control equipment CF Measurement, recording CFA Cabinets for measurement CFB Cabinets for measurement CFC Cabinets for measurement CFD Cabinets for measurement CFE Cabinets for measurement CFF Cabinets for measurement CFG Cabinets for reactor instrumentation CFH Cabinets for reactor instrumentation CFJ Cabinets for reactor instrumentation CFK Cabinets for reactor instrumentation CFL Cabinets for radiation measurement CFM Cabinets for radiation measurement CFN Cabinets for radiation measurement CFP Cabinets for radiation measurement CFQ Cabinets for recording (meters, pen recorders) CFR Cabinets for measurement, installation in the secured area (of nuclear power plant) CFS Cabinets for measurement, installation in the secured area (of nuclear power plant) CFT Cabinets for measurement, installation in the secured area (of nuclear power plant) CFU Cabinets for measurement, installation in the secured area (of nuclear power plant) CFV Cabinets for measurement, installation in the secured area (of nuclear power plant) CFW Cabinets for measurement, installation in the secured area (of nuclear power plant) CFX Cabinets for measurement, installation in the secured area (of nuclear power plant) CFY Cabinets for measurement, installation in the secured area (of nuclear power plant) Printout date 14. Mrz. 01 Page CF1 of CF1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : CG 04.04.97 C Instrumentation and control equipment CG Closed-loop control (excl. power section) CGA Cabinets for closed-loop control CGB Cabinets for closed-loop control CGC Cabinets for closed-loop control CGD Cabinets for closed-loop control CGE Cabinets for closed-loop control CGF Cabinets for closed-loop control CGG Cabinets for closed-loop control CGH Cabinets for closed-loop control CGJ Cabinets for reactor control CGK Cabinets for reactor control CGL Cabinets for reactor control CGM Cabinets for reactor control CGN Cabinets for reactor control CGP Cabinets for reactor control CGQ Cabinets for reactor control CGR Cabinets for closed-loop control, installation in the secured area (of nuclear power plant) CGS Cabinets for closed-loop control, installation in the secured area (of nuclear power plant) CGT Cabinets for closed-loop control, installation in the secured area (of nuclear power plant) CGU Cabinets for closed-loop control, installation in the secured area (of nuclear power plant) CGV Cabinets for closed-loop control, installation in the secured area (of nuclear power plant) CGW Cabinets for closed-loop control, installation in the secured area (of nuclear power plant) CGX Cabinets for closed-loop control, installation in the secured area (of nuclear power plant) CGY Cabinets for closed-loop control, installation in the secured area (of nuclear power plant) Printout date 14. Mrz. 01 Page CG1 of CG1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : CH 04.04.97 C Instrumentation and control equipment CH Protection (excl. reactor protection) CHA Cabinets for generator and transformer protection CHB Cabinets for generator and transformer protection CHC Cabinets for generator and transformer protection CHD Cabinets for generator and transformer protection CHE Cabinets for protection (excl. reactor protection) CHF Cabinets for protection (excl. reactor protection) CHG Cabinets for protection (excl. reactor protection) CHH Cabinets for protection (excl. reactor protection) CHJ Cabinets for protection (excl. reactor protection) CHK Cabinets for protection (excl. reactor protection) CHL Cabinets for protection (excl. reactor protection) CHM Cabinets for protection (excl. reactor protection) CHN Cabinets for protection (excl. reactor protection) CHP Cabinets for protection (excl. reactor protection) CHQ Cabinets for protection (excl. reactor protection) CHR Cabinets for protection (excl. reactor protection) CHS Cabinets for protection (excl. reactor protection) CHT Cabinets for protection (excl. reactor protection) CHU Cabinets for protection (excl. reactor protection) CHV Cabinets for protection (excl. reactor protection) CHW Cabinets for protection (excl. reactor protection) CHX Cabinets for protection (excl. reactor protection) CHY Cabinets for protection (excl. reactor protection) Printout date 14. Mrz. 01 Page CH1 of CH1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : CJ 04.04.97 C Instrumentation and control equipment CJ Unit coordination level CJA Unit control system (including cabinets) CJD Start-up control, setpoint control (unit) (incl. cabinets) CJF Boiler control system (incl. cabinets) CJJ Instrumentation and control cabinets for steam turbine set CJK Instrumentation and control cabinets for steam turbine set CJL Instrumentation and control cabinets for steam turbine set CJM Instrumentation and control cabinets for steam turbine set CJN Instrumentation and control cabinets for steam turbine set CJP Instrumentation and control cabinets for gas turbine set CJQ Instrumentation and control cabinets for gas turbine set CJR Instrumentation and control cabinets for gas turbine set CJS Instrumentation and control cabinets for gas turbine set CJT Instrumentation and control cabinets for gas turbine set CJU Instrumentation and control cabinets for other main and heavy machinery CJV Instrumentation and control cabinets for other main and heavy machinery CJW Instrumentation and control cabinets for other main and heavy machinery CJX Instrumentation and control cabinets for other main and heavy machinery CJY Instrumentation and control cabinets for other main and heavy machinery Printout date 14. Mrz. 01 Page CJ1 of CJ1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : CK 04.04.97 C Instrumentation and control equipment CK Process computer system CKA Online supervisory and diagnostic computer CKB Online supervisory and diagnostic computer CKC Online supervisory and diagnostic computer CKD Online supervisory and diagnostic computer CKE Online supervisory and diagnostic computer CKF Online supervisory and diagnostic computer CKG Online supervisory and diagnostic computer CKH Online supervisory and diagnostic computer CKJ Access control computer CKK Access control computer CKL Access control computer CKM Access control computer CKN Process computer system CKP Process computer system CKQ Process computer system CKR Process computer system CKS Process computer system CKT Process computer system CKU Process computer system CKV Process computer system CKW Process computer system CKX Process computer system CKY Process computer system Printout date 14. Mrz. 01 Page CK1 of CK1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : CL 04.04.97 C Instrumentation and control equipment CL Reactor protection CLA Cabinets for reactor protection CLB Cabinets for reactor protection CLC Cabinets for reactor protection CLD Cabinets for reactor protection CLE Cabinets for reactor protection CLF Cabinets for reactor protection CLG Cabinets for reactor protection CLH Cabinets for reactor protection CLJ Cabinets for reactor protection CLK Cabinets for reactor protection CLL Cabinets for reactor protection CLM Cabinets for reactor protection CLN Cabinets for reactor protection CLP Cabinets for reactor protection CLQ Cabinets for reactor protection CLR Cabinets for reactor protection CLS Cabinets for reactor protection CLT Cabinets for reactor protection CLU Cabinets for reactor protection CLV Cabinets for reactor protection CLW Cabinets for reactor protection CLX Cabinets for reactor protection CLY Cabinets for reactor protection Printout date 14. Mrz. 01 Page CL1 of CL1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : CR 04.04.97 C Instrumentation and control equipment CR Programmable process control systems and associated cabinets CRA Cabinets for automation systems, e. g. unit control level, function unit 1 CRB Cabinets for automation systems, function unit 2 CRC Cabinets for automation systems, function unit 3 CRD Cabinets for automation systems, function unit 4 CRE Cabinets for automation systems, function unit 5 CRF Cabinets for automation systems, function unit 6 CRG Cabinets for automation systems, function unit 7 CRK Cabinets for automation systems, e. g. several function units CRN Automation systems, e. g. operational CRP Automation systems, e. g. fail-safe CRQ Automation systems, e. g. AS620-T CRR Communications systems, e. g. terminal bus system CRS Communications systems, e. g. plant bus system CRT Communications systems, e. g. field bus system CRU Process control and information system, e. g. OM650 CRV Configuring system, e. g. ES680 CRW Diagnostics system, e. g. DS670 CRY Common superordinate systems Printout date 14. Mrz. 01 Page CR1 of CR1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : CU 04.04.97 C Instrumentation and control equipment CU Closed-loop control (power section) CUA Cabinets for power adjuster 400V AC, e. g. function unit 1 CUB Cabinets for power adjuster 400V AC, e. g. function unit 2 CUC Cabinets for power adjuster 400V AC, e. g. function unit 3 CUD Cabinets for power adjuster 400V AC, e. g. function unit 4 CUE Cabinets for power adjuster 400V AC, e. g. function unit 5 CUF Cabinets for power adjuster 400V AC, e. g. function unit 6 CUG Cabinets for power adjuster 400V AC, e. g. function unit 7 CUH Cabinets for power adjuster CUJ Cabinets for power adjuster CUK Cabinets for power adjuster CUL Cabinets for interposing relays for 24 V DC solenoid valves CUM Cabinets for power supply of hardwired control room CUN Cabinets for 24 V DC fuses CUP Cabinets for 230 V DC fuses CUQ Cabinets for power adjuster CUR Cabinets for power adjuster, installation in the secured area (of nuclear power plant) CUS Cabinets for power adjuster, installation in the secured area (of nuclear power plant) CUT Cabinets for power adjuster, installation in the secured area (of nuclear power plant) CUU Cabinets for power adjuster, installation in the secured area (of nuclear power plant) CUV Cabinets for power adjuster, installation in the secured area (of nuclear power plant) CUW Cabinets for power adjuster, installation in the secured area (of nuclear power plant) CUX Cabinets for power adjuster, installation in the secured area (of nuclear power plant) CUY Cabinets for power adjuster, installation in the secured area (of nuclear power plant) Printout date 14. Mrz. 01 Page CU1 of CU1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : CV 04.04.97 C Instrumentation and control equipment CV Marshalling racks CVA Marshalling racks CVB Marshalling racks CVC Marshalling racks CVD Marshalling racks CVE Marshalling racks CVF Marshalling racks CVG Marshalling racks CVH Marshalling racks CVJ Marshalling racks CVK Marshalling racks CVL Marshalling racks CVM Marshalling racks CVN Marshalling racks CVP Marshalling racks CVQ Marshalling racks CVR Marshalling racks CVS Marshalling racks CVT Marshalling racks CVU Marshalling racks CVV Marshalling racks CVW Marshalling racks CVX Marshalling racks CVY Marshalling racks Printout date 14. Mrz. 01 Page CV1 of CV1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : CW 04.04.97 C Instrumentation and control equipment CW Control rooms CWA Main control consoles CWB Main control consoles CWC Main control consoles CWD Main control consoles CWE Main control consoles CWF Main control panels CWG Main control panels CWH Main control panels CWJ Main control panels CWK Main control panels CWL Main control panels CWM Main control panels CWN Main control panels CWP Main control panels CWQ Consoles and panels in control rooms CWR Consoles and panels in control rooms CWS Consoles and panels in control rooms CWT Consoles and panels in control rooms CWU Consoles and panels in control rooms CWV Consoles and panels in control rooms CWW Consoles and panels in control rooms CWX Consoles and panels in control rooms CWY Consoles and panels in control rooms Printout date 14. Mrz. 01 Page CW1 of CW1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : CX 04.04.97 C Instrumentation and control equipment CX Local control stations (e. g. for solid fuel supply system, ash removal system, cooling water system, diesel engine plant, monitoring of generator cooling, emergency control station) CXA Local control station CXB Local control station CXC Local control station CXD Local control station CXE Local control station CXF Local control station CXG Local control station CXH Local control station CXJ Local control station CXK Local control station CXL Local control station CXM Local control station CXN Local control station CXP Local control station CXQ Local control station CXR Local control station CXS Local control station CXT Local control station CXU Local control station CXV Local control station CXW Local control station CXX Local control station CXY Local control station Printout date 14. Mrz. 01 Page CX1 of CX1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : CY 04.04.97 C Instrumentation and control equipment CY Communication equipment CYA Telephone system (PABX) CYB Control console telephone system CYC Alarm system (acoustic) CYD Alarm system (optical) CYE Fire alarm system CYF Clock system CYG Remote control system CYH Telemetry system CYJ Remote metering system CYK HF carrier telephone system CYL Staff paging system, wireless CYM Staff paging system, inductive CYN Staff paging system, hardwired CYP Optical monitoring system (Plant TV system) CYQ General gas detection system (if not assigned to specific system) CYR Pneumatic tube conveyor CYS Radiotelephone system CYY Telephone system for commissioning Printout date 14. Mrz. 01 Page CY1 of CY1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : D 04.04.97 D Instrumentation and control equipment DA Instrumentation and control equipment DB Instrumentation and control equipment DC Instrumentation and control equipment DD Instrumentation and control equipment DE Instrumentation and control equipment DF Instrumentation and control equipment DG Instrumentation and control equipment DH Instrumentation and control equipment DJ Instrumentation and control equipment DK Instrumentation and control equipment DL Instrumentation and control equipment DM Instrumentation and control equipment DN Instrumentation and control equipment DP Instrumentation and control equipment DQ Instrumentation and control equipment DR Instrumentation and control equipment DS Instrumentation and control equipment DT Instrumentation and control equipment DU Instrumentation and control equipment DV Instrumentation and control equipment DW Instrumentation and control equipment DX Instrumentation and control equipment DY Instrumentation and control equipment DZ Instrumentation and control equipment Printout date 14. Mrz. 01 Page D1 of D1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : E 04.04.97 E Conventional fuel supply and residues disposal EA Unloading and storage of solid fuels EB Mechanical treatment of solid fuels (also for gas generation and treatment) (crushing, mixing, drying etc.) EC Distribution of solid fuels Limit: from incl. receiving point to excl. discharge into other systems ED Chemical treatment of solid fuels incl. residues removal (e. g. desulfurization plant) EE Conversion of solid fuels (gas generation and treatment see function key *R*) EG Supply of liquid fuels EH Chemical treatment of liquid fuels incl. residues removal EK Supply of gaseous fuels EL Chemical treatment of gaseous fuels incl. residues removal EM Supply and treatment of fluxing agents EN Supply of other fuels (only for combinations of different fuel types) EP Treatment of other fuels (only for combinations of different fuel types) EQ Conversion of other fuels (only for combiations of different fuel types) ER Ignition fuel supply ET Ash and slag removal system (from excl. removal equipment) EU Treatment and transport system for combustion, fuel treatment, fuel conversion, flue gas cleaning, gas generation residues EV Lubricant supply system EW Sealing fluid supply system EX Fluid supply system for control and protection equipment EY Control and protection equipment Printout date 14. Mrz. 01 Page E1 of E1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : EA 04.04.97 E Conventional fuel supply and residues disposal EA Unloading and storage of solid fuels EAA Ship unloading system Limit: from incl. unloading equipment to excl. transport or storage plant EAB Rail wagon and truck unloading bay Limit: from incl. unloading equipment to excl. transport or storage plant EAC Transport system Limit: from incl. receiving point to excl. storage incl. internal transport system within unloading and storage plant to excl. stacker EAD Stacking system Limit: from excl. transport system to excl. storage plant EAE Bunker system, storage area (stockyard) Limit: from excl. unloading equipment or transport system to excl. transport or bucket wheel or reclaimer or stacking system EAF Bucket wheel system, reclaimer system Limit: from excl. bunker system or stockyard to excl. transport system EAT Weighing equipment EAU Sampling equipment EAV Lubricant supply system EAX Fluid supply system for control and protection equipment EAY Control and protection equipment Printout date 14. Mrz. 01 Page EA1 of EA1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : EB 04.04.97 E Conventional fuel supply and residues disposal EB Mechanical treatment of solid fuels (also for gas generation and treatment) (crushing, mixing, drying etc.) EBA Transport system Limit: from incl. receiving point to excl. discharge into treatment or mixing system EBB Mixing system Limit: from incl. receiving point to excl. discharge into other system EBC Crushing system, pulverizing system Limit: from incl. receiving point to excl. discharge into other system EBD Screening system Limit: from incl. receiving point to excl. discharge into other system EBE Separator system and discharge equipment thereof Hint: unless not structural part of one of the former systems (*EBA* to *EBD) Limit: from incl. receiving point to excl. discharge into other system EBF Temporary storage system for milled raw coal Limit: from incl. receiving point to excl. discharge into other system EBG Predrying system Limit: from incl. receiving point to excl. discharge into other system EBH Main drying system Limit: from incl. receiving point to excl. discharge into other system EBJ Dried coal transport system incl. aftercooling Limit: from incl. receiving point to excl. discharge into other system EBK Dried coal temporary storage system Limit: from incl. receiving point to excl. discharge into other system EBL Vapor compressor system Limit: from incl. receiving point to excl. discharge into other system EBM Exhaust system Limit: from incl. receiving point to excl. discharge into other system EBR Residues removal system EBT Weighing equipment EBU Sampling equipment EBV Lubricant supply system Printout date 14. Mrz. 01 Page EB1 of EB2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : EB 04.04.97 EBX Fluid supply system for control and protection equipment EBY Control and protection equipment Printout date 14. Mrz. 01 Page EB2 of EB2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : EC 04.04.97 E Conventional fuel supply and residues disposal EC Distribution of solid fuels Limit: from incl. receiving point to excl. discharge into other systems ECA Distribution of solid fuels ECB Distribution of solid fuels ECC Distribution of solid fuels ECD Distribution of solid fuels ECE Distribution of solid fuels ECF Distribution of solid fuels ECG Distribution of solid fuels ECH Distribution of solid fuels ECJ Distribution of solid fuels ECK Distribution of solid fuels ECL Distribution of solid fuels ECM Distribution of solid fuels ECN Distribution of solid fuels ECP Distribution of solid fuels ECQ Distribution of solid fuels ECR Distribution of solid fuels ECS Distribution of solid fuels ECT Weighing equipment ECU Sampling equipment ECX Fluid supply system for control and protection equipment ECY Control and protection equipment Printout date 14. Mrz. 01 Page EC1 of EC1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : ED 04.04.97 E Conventional fuel supply and residues disposal ED Chemical treatment of solid fuels incl. residues removal (e. g. desulfurization plant) EDA Chemical treatment of solid fuels incl. residues removal EDB Chemical treatment of solid fuels incl. residues removal EDC Chemical treatment of solid fuels incl. residues removal EDD Chemical treatment of solid fuels incl. residues removal EDE Chemical treatment of solid fuels incl. residues removal EDF Chemical treatment of solid fuels incl. residues removal EDG Chemical treatment of solid fuels incl. residues removal EDH Chemical treatment of solid fuels incl. residues removal EDJ Chemical treatment of solid fuels incl. residues removal EDK Chemical treatment of solid fuels incl. residues removal EDL Chemical treatment of solid fuels incl. residues removal EDM Chemical treatment of solid fuels incl. residues removal EDN Chemical treatment of solid fuels incl. residues removal EDP Chemical treatment of solid fuels incl. residues removal EDQ Chemical treatment of solid fuels incl. residues removal EDR Chemical treatment of solid fuels incl. residues removal EDS Chemical treatment of solid fuels incl. residues removal EDT Chemical treatment of solid fuels incl. residues removal EDU Chemical treatment of solid fuels incl. residues removal EDV Lubricant supply system EDX Fluid supply system for control and protection equipment EDY Control and protection equipment Printout date 14. Mrz. 01 Page ED1 of ED1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : EE 04.04.97 E Conventional fuel supply and residues disposal EE Conversion of solid fuels (gas generation and treatment see function key *R*) EEA Conversion of solid fuels EEB Conversion of solid fuels EEC Conversion of solid fuels EED Conversion of solid fuels EEE Conversion of solid fuels EEF Conversion of solid fuels EEG Conversion of solid fuels EEH Conversion of solid fuels EEJ Conversion of solid fuels EEK Conversion of solid fuels EEL Conversion of solid fuels EEM Conversion of solid fuels EEN Conversion of solid fuels EEP Conversion of solid fuels EEQ Conversion of solid fuels EER Conversion of solid fuels EES Conversion of solid fuels EET Conversion of solid fuels EEU Conversion of solid fuels EEV Lubricant supply system EEX Fluid supply system for control and protection equipment EEY Control and protection equipment Printout date 14. Mrz. 01 Page EE1 of EE1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : EG 04.04.97 E Conventional fuel supply and residues disposal EG Supply of liquid fuels EGA Receiving equipment incl. pipeline Limit: from excl. receiving point to excl. tank, incl. pump EGB Tank farm Limit: from incl. tank inlet to incl. tank outlet EGC Pump system Limit: from incl. pump system suction nozzle to incl. pump system discharge nozzle EGD Piping system Limit: from excl. tank outlet to excl. temporary storage system or branch to user EGR Residues removal system EGT Heating medium system Limit: from excl. branch off supply system to excl. user and from excl. user to excl. inlet to other system EGV Lubricant supply system EGX Fluid supply system for control and protection equipment EGY Control and protection equipment Printout date 14. Mrz. 01 Page EG1 of EG1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : EH 04.04.97 E Conventional fuel supply and residues disposal EH Chemical treatment of liquid fuels incl. residues removal EHA Chemical treatment of liquid fuels EHB Chemical treatment of liquid fuels EHC Additive dosing system EHD Chemical treatment of liquid fuels EHE Chemical treatment of liquid fuels EHF Chemical treatment of liquid fuels EHG Chemical treatment of light fuel oil EHH Chemical treatment of liquid fuels EHJ Chemical treatment of liquid fuels EHK Chemical treatment of liquid fuels EHL Chemical treatment of liquid fuels EHM Chemical treatment of liquid fuels EHN Chemical treatment of heavy fuel oil EHP Chemical treatment of liquid fuels EHQ Chemical treatment of liquid fuels EHR Chemical treatment of liquid fuels EHS Chemical treatment of liquid fuels EHT Heating medium system Limit: from excl. branch off supply system to excl. user and from excl. user to excl. inlet to other system EHU Chemical treatment of liquid fuels EHV Lubricant supply system EHX Fluid supply system for control and protection equipment EHY Control and protection equipment Printout date 14. Mrz. 01 Page EH1 of EH1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : EK 04.04.97 E Conventional fuel supply and residues disposal EK Supply of gaseous fuels EKA Receiving equipment incl. pipeline Limit: from excl. receiving point to incl. inlet to other system EKB Moisture separation system Limit: from incl. moisture separator inlet to incl. moisture separator outlet EKC Heating system Limit: from incl. heater inlet to incl. heater outlet EKD Main reducing station, expansion turbine Limit: from incl. main reducing station inlet, expansion turbine inlet to incl. main reducing station outlet, expansion turbine outlet EKE Mechanical cleaning, scrubbing Limit: from incl. inlet of mechanical cleaning, scrubbing system to incl. outlet mechanical cleaning, scrubbing system EKF Storage system Limit: from incl. storage system inlet to incl. storage system outlet EKG Piping system Limit: from excl. receiving point to excl. branch to user EKH Main pressure boosting system Limit: from incl. pump system suction nozzle to incl. pump system discharge nozzle EKR Residues removal system EKT Heating medium system Limit: from excl. branch off supply system to excl. user and from excl. user to excl. inlet to other system EKV Lubricant supply system EKW Sealing fluid supply system EKX Fluid supply system for control and protection equipment EKY Control and protection equipment Printout date 14. Mrz. 01 Page EK1 of EK1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : EL 04.04.97 E Conventional fuel supply and residues disposal EL Chemical treatment of gaseous fuels incl. residues removal ELA Chemical treatment of gaseous fuels incl. residues removal ELB Chemical treatment of gaseous fuels incl. residues removal ELC Chemical treatment of gaseous fuels incl. residues removal ELD Chemical treatment of gaseous fuels incl. residues removal ELE Chemical treatment of gaseous fuels incl. residues removal ELF Chemical treatment of gaseous fuels incl. residues removal ELG Chemical treatment of gaseous fuels incl. residues removal ELH Chemical treatment of gaseous fuels incl. residues removal ELJ Chemical treatment of gaseous fuels incl. residues removal ELK Chemical treatment of gaseous fuels incl. residues removal ELL Chemical treatment of gaseous fuels incl. residues removal ELM Chemical treatment of gaseous fuels incl. residues removal ELN Chemical treatment of gaseous fuels incl. residues removal ELP Chemical treatment of gaseous fuels incl. residues removal ELQ Chemical treatment of gaseous fuels incl. residues removal ELR Chemical treatment of gaseous fuels incl. residues removal ELS Chemical treatment of gaseous fuels incl. residues removal ELT Chemical treatment of gaseous fuels incl. residues removal ELU Chemical treatment of gaseous fuels incl. residues removal ELV Lubricant supply system ELW Sealing fluid supply system ELX Fluid supply system for control and protection equipment ELY Control and protection equipment Printout date 14. Mrz. 01 Page EL1 of EL1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : EM 04.04.97 E Conventional fuel supply and residues disposal EM Supply and treatment of fluxing agents EMA Supply and treatment of fluxing agents EMB Supply and treatment of fluxing agents EMC Supply and treatment of fluxing agents EMD Supply and treatment of fluxing agents EME Supply and treatment of fluxing agents EMF Supply and treatment of fluxing agents EMG Supply and treatment of fluxing agents EMH Supply and treatment of fluxing agents EMJ Supply and treatment of fluxing agents EMK Supply and treatment of fluxing agents EML Supply and treatment of fluxing agents EMM Supply and treatment of fluxing agents EMN Supply and treatment of fluxing agents EMP Supply and treatment of fluxing agents EMQ Supply and treatment of fluxing agents EMR Supply and treatment of fluxing agents EMS Supply and treatment of fluxing agents EMT Supply and treatment of fluxing agents EMU Supply and treatment of fluxing agents EMV Lubricant supply system EMX Fluid supply system for control and protection equipment EMY Control and protection equipment Printout date 14. Mrz. 01 Page EM1 of EM1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : EN 04.04.97 E Conventional fuel supply and residues disposal EN Supply of other fuels (only for combinations of different fuel types) ENA Receiving equipment incl. pipeline Limit: from excl. receiving point to excl. tank, incl. pump ENB Tank farm Limit: from incl. tank inlet to incl. tank outlet ENC Pump system Limit: from incl. pump system suction nozzle to incl. pump system discharge nozzle END Piping system Limit: from excl. tank outlet to excl. temporary storage system or branch to user ENR Residues removal system ENT Heating medium system Limit: from excl. branch off supply system to excl. user and from excl. user to excl. inlet to other system ENV Lubricant supply system ENX Fluid supply system for control and protection equipment ENY Control and protection equipment Printout date 14. Mrz. 01 Page EN1 of EN1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : EP 04.04.97 E Conventional fuel supply and residues disposal EP Treatment of other fuels (only for combinations of different fuel types) EPC Pump system Limit: from incl. pump system suction nozzle to incl. pump system discharge nozzle EPG Physical treatment of light fuel oil EPN Physical treatment of heavy fuel oil EPT Heating medium system Limit: from excl. branch off supply system to excl. user and from excl. user to excl. inlet to other system EPV Lubricant supply system EPX Fluid supply system for control and protection equipment EPY Control and protection equipment Printout date 14. Mrz. 01 Page EP1 of EP1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : EQ 04.04.97 E Conventional fuel supply and residues disposal EQ Conversion of other fuels (only for combiations of different fuel types) EQA Conversion of other fuels EQB Conversion of other fuels EQC Conversion of other fuels EQD Conversion of other fuels EQE Conversion of other fuels EQF Conversion of other fuels EQG Conversion of other fuels EQH Conversion of other fuels EQJ Conversion of other fuels EQK Conversion of other fuels EQL Conversion of other fuels EQM Conversion of other fuels EQN Conversion of other fuels EQP Conversion of other fuels EQQ Conversion of other fuels EQR Conversion of other fuels EQS Conversion of other fuels EQT Conversion of other fuels EQU Conversion of other fuels EQV Lubricant supply system EQX Fluid supply system for control and protection equipment EQY Control and protection equipment Printout date 14. Mrz. 01 Page EQ1 of EQ1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : ER 04.04.97 E Conventional fuel supply and residues disposal ER Ignition fuel supply ERA Pulverized coal supply system Limit: from excl. receiving point to excl. branch to boiler or to excl. other users ERB Oil supply system Limit: from excl. receiving point to excl. branch to boiler or to excl. other users ERC Gas supply system Limit: from excl. receiving point to excl. branch to boiler or to excl. other users ERV Lubricant supply system ERX Fluid supply system for control and protection equipment ERY Control and protection equipment Printout date 14. Mrz. 01 Page ER1 of ER1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : ET 04.04.97 E Conventional fuel supply and residues disposal ET Ash and slag removal system (from excl. removal equipment) ETA Wet ash conveying system Limit: from excl. removal equipment or from excl. receiving point to excl. storage facility or to excl. discharge into other system ETB Storage or settling pond for wet ash Limit: from excl. receiving point to incl. removal equipment ETC Wet ash dredger Limit: from excl. receiving point to excl. discharge into other system ETD Conveying system for granulate Limit: from excl. removal equipment to excl. storage facility or to excl. discharge into other system ETE Storage system for granulate Limit: from excl. receiving point to incl. removal equipment ETG Conveying system for dry ash Limit: from excl. removal equipment (boiler, electrostatic precipitator) to excl. storage facilities or to excl. discharge into other system ETH Storage system for dry ash Limit: from excl. receiving point to incl. removal equipment ETK Common conveying system for wet and dry ash Limit: from excl. receiving point to excl. storage facility or to excl. discharge into other system ETL Common storage system for wet and dry ash Limit: from excl. receiving point to incl. removal equipment ETM Settling plant for wet and dry ash Limit: from excl. receiving point from conveying system to excl. pit or to excl. discharge into other system ETN Forwarding, distribution, recovery and disposal systems for flushing and ash water Limit: from excl. inlet or from incl. branch to excl. inlet to other system ETP Generation and distribution systems for carrier air Limit: from excl. branch or from incl. compressor system to excl. inlet to conveying system ETV Lubricant supply system ETX Fluid supply system for control and protection equipment Printout date 14. Mrz. 01 Page ET1 of ET2 Siemens 2 nd complete, non-project related edition Condition-Date: ETY KKS Identification System for Power Plants Function key : ET 04.04.97 Control and protection equipment Printout date 14. Mrz. 01 Page ET2 of ET2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : EU 04.04.97 E Conventional fuel supply and residues disposal EU Treatment and transport system for combustion, fuel treatment, fuel conversion, flue gas cleaning, gas generation residues EUA Treatment system for fuel treatment residues Limit: from incl. inlet to incl. outlet EUB Treatment system for fuel conversion residues Limit: from incl. inlet to incl. outlet EUC Treatment system for fuel combustion residues Limit: from incl. inlet to incl. outlet EUD Treatment system for flue gas cleaning residues Limit: from incl. inlet to incl. outlet EUE Treatment system for gas generation and treatment residues Limit: from incl. inlet to incl. outlet EUF Treatment system for fuel treatment residues Hint: only if *EUA* is not sufficient for identification Limit: from incl. inlet to incl. outlet EUG Treatment system for fuel treatment residues Hint: only if *EUA* and *EUF* are not sufficient for identification Limit: from incl. inlet to incl. outlet EUH Treatment system for fuel conversion residues Hint: only if *EUB* is not sufficient for identification Limit: from incl. inlet to incl. outlet EUJ Treatment system for fuel conversion residues Hint: only if *EUB* and *EUH* are not sufficient for identification Limit: from incl. inlet to incl. outlet EUK Treatment system for fuel combustion residues Hint: only if *EUC* is not sufficient for identification Limit: from incl. inlet to incl. outlet EUL Treatment system for fuel combustion residues Hint: only if *EUC* and *EUK* are not sufficient for identification Limit: from incl. inlet to incl. outlet EUM Treatment system for flue gas cleaning residues Hint: only if *EUD* is not sufficient for identification Limit: from incl. inlet to incl. outlet Printout date 14. Mrz. 01 Page EU1 of EU2 Siemens 2 nd complete, non-project related edition Condition-Date: EUN KKS Identification System for Power Plants Function key : EU 04.04.97 Treatment system for flue gas cleaning residues Hint: only if *EUD* and *EUM* are not sufficient for identification Limit: from incl. inlet to incl. outlet EUP Treatment system for gas generation and treatment residues Hint: only if *EUE* is not sufficient for identification Limit: from incl. inlet to incl. outlet EUQ Treatment system for gas generation and treatment residues Hint: only if *EUE* and *EUP* are not sufficient for identification Limit: from incl. inlet to incl. outlet EUV Lubricant supply system EUX Fluid supply system for control and protection equipment EUY Control and protection equipment Printout date 14. Mrz. 01 Page EU2 of EU2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : EV 04.04.97 E Conventional fuel supply and residues disposal EV Lubricant supply system EVA Lubricant supply system EVB Lubricant supply system EVC Lubricant supply system EVD Lubricant supply system EVE Lubricant supply system EVF Lubricant supply system EVG Lubricant supply system EVH Lubricant supply system EVJ Lubricant supply system EVK Lubricant supply system EVL Lubricant supply system EVM Lubricant supply system EVN Lubricant supply system EVP Lubricant supply system EVQ Lubricant supply system EVR Lubricant supply system EVS Lubricant supply system EVT Lubricant supply system EVU Lubricant supply system Printout date 14. Mrz. 01 Page EV1 of EV1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : EW 04.04.97 E Conventional fuel supply and residues disposal EW Sealing fluid supply system EWA Sealing fluid supply system EWB Sealing fluid supply system EWC Sealing fluid supply system EWD Sealing fluid supply system EWE Sealing fluid supply system EWF Sealing fluid supply system EWG Sealing fluid supply system EWH Sealing fluid supply system EWJ Sealing fluid supply system EWK Sealing fluid supply system EWL Sealing fluid supply system EWM Sealing fluid supply system EWN Sealing fluid supply system EWP Sealing fluid supply system EWQ Sealing fluid supply system EWR Sealing fluid supply system EWS Sealing fluid supply system EWT Sealing fluid supply system EWU Sealing fluid supply system Printout date 14. Mrz. 01 Page EW1 of EW1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : EX 04.04.97 E Conventional fuel supply and residues disposal EX Fluid supply system for control and protection equipment EXA Fluid supply system for control and protection equipment EXB Fluid supply system for control and protection equipment EXC Fluid supply system for control and protection equipment EXD Fluid supply system for control and protection equipment EXE Fluid supply system for control and protection equipment EXF Fluid supply system for control and protection equipment EXG Fluid supply system for control and protection equipment EXH Fluid supply system for control and protection equipment EXJ Fluid supply system for control and protection equipment EXK Fluid supply system for control and protection equipment EXL Fluid supply system for control and protection equipment EXM Fluid supply system for control and protection equipment EXN Fluid supply system for control and protection equipment EXP Fluid supply system for control and protection equipment EXQ Fluid supply system for control and protection equipment EXR Fluid supply system for control and protection equipment EXS Fluid supply system for control and protection equipment EXT Fluid supply system for control and protection equipment EXU Fluid supply system for control and protection equipment Printout date 14. Mrz. 01 Page EX1 of EX1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : EY 04.04.97 E Conventional fuel supply and residues disposal EY Control and protection equipment EYA Control and protection equipment EYB Control and protection equipment EYC Control and protection equipment EYD Control and protection equipment EYE Control and protection equipment EYF Control and protection equipment EYG Control and protection equipment EYH Control and protection equipment EYJ Control and protection equipment EYK Control and protection equipment EYL Control and protection equipment EYM Control and protection equipment EYN Control and protection equipment EYP Control and protection equipment EYQ Control and protection equipment EYR Control and protection equipment EYS Control and protection equipment EYT Control and protection equipment EYU Control and protection equipment Printout date 14. Mrz. 01 Page EY1 of EY1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : F 04.04.97 F Handling of nuclear equipment FA Storage of fuel assemblies (also includes breeder and reflector assemblies) and other radioactive components FB Handling of fuel assemblies (also includes breeder and reflector assemblies) and other reactor core internals FC Refueling and transport equipment for fuel assemblies (also includes breeder and reflector assemblies) and other reactor core internals FJ Erection and in-service inspection equipment FK Decontamination equipment (excluding cleaning equipment for fuel assemblies store *FAM* and fuel assemblies *FBC*) FV Lubricant supply system FW Sealing fluid supply system FX Fluid supply system for control and protection equipment FY Control and protection equipment Printout date 14. Mrz. 01 Page F1 of F1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : FA 04.04.97 F Handling of nuclear equipment FA Storage of fuel assemblies (also includes breeder and reflector assemblies) and other radioactive components FAA New fuel assemblies store Task: to accommodate fuel assemblies and other radioactive components, associated tools for storage and, where applicable, manipulation Scope: lining and support structure, leakage monitoring equipment and internals FAB Irradiated fuel assemblies store (fuel pool) Task: to accommodate fuel assemblies and other radioactive components, associated tools for storage and, where applicable, manipulation Scope: lining and support structure, leakage monitoring equipment and internals FAC Irradiated breeder assemblies store (not internal store) Task: to accommodate breeder assemblies and the associated tools for storage and, where applicable, manipulation Scope: lining and support structure, leakage monitoring equipment and internals FAD Additional fuel assemblies store FAE Reactor well equipment Scope: lining and support structure, leakage monitoring equipment and internals FAF Setdown area equipment Task: temporary storage of reactor internals Scope: lining and support structure, leakage monitoring equipment and internals FAH Reusable activated components store FAK Fuel assemblies store cooling system (also fuel pool cooling system) Task: to remove heat from the fuel assemblies store FAL Fuel assemblies store coolant cleaning system (also fuel pool cleaning system) Task: to remove contaminants from the fuel assemblies store coolant FAM Fuel assemblies store cleaning system Task: to remove contaminants from the fuel assemblies store FAN Emergency fuel assemblies store cooling system Task: to remove heat from the fuel assemblies store in emergencies FAR Dedicated blanket gas system for fuel assemblies store Task: to protect fuel assemblies against oxidation FAT Heating, cooling, flushing distribution system (also evacuation) FAV Lubricant supply system FAW Sealing fluid supply system FAX Fluid supply system for control and protection equipment FAY Control and protection equipment Printout date 14. Mrz. 01 Page FA1 of FA1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : FB 04.04.97 F Handling of nuclear equipment FB Handling of fuel assemblies (also includes breeder and reflector assemblies) and other reactor core internals FBA Fuel assemblies and other reactor core internals testing equipment Task: to establish the condition of reactor core internals FBB Fuel assemblies and other reactor core internals repair equipment Task: to repair reactor core internals FBC Fuel assemblies and other reactor core internals cleaning equipment Task: to clean reactor core internals (for decontamination equipment see *FK*) FBD Size reduction equipment for fuel assemblies and other reactor core internals, excl. components classified under *J..* FBT Heating, cooling, flushing distribution system (also evacuation) FBV Lubricant supply system FBW Sealing fluid supply system FBX Fluid supply system for control and protection equipment FBY Control and protection equipment Printout date 14. Mrz. 01 Page FB1 of FB1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : FC 04.04.97 F Handling of nuclear equipment FC Refueling and transport equipment for fuel assemblies (also includes breeder and reflector assemblies) and other reactor core internals FCA Charge and discharge equipment Task: to insert fuel absorber assemblies and similar components into and to remove same from the reactor core with the aid of a carrier fluid FCB Refueling equipment at reactor Task: to exchange and reshuffle fuel assemblies and other reactor core internals FCC Reshuffling equipment for reactor core internals Hint: only if separate from *FCA* and *FCB* Task: to reshuffle fuel assemblies and other reactor core internals FCD Refueling equipment in store for fuel assemblies and other reactor core internals Task: to manipulate fuel assemblies and other reactor core internals within the store FCF Fuel transfer equipment Task: to enable transfer between compartments subject to different operating conditions, only for fuel assemblies and other reactor core internals FCJ Transport equipment Task: to transfer fuel assemblies and other reactor core internals between different stores Scope: equipment for the transport of fuel assemblies and other reactor core internals between different stores FCL Pressurizing and cooling system for fuel assemblies transport equipment FCT Heating, cooling, flushing distribution system (also evacuation) FCV Lubricant supply system FCW Sealing fluid supply system FCX Fluid supply system for control and protection equipment FCY Control and protection equipment Printout date 14. Mrz. 01 Page FC1 of FC1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : FJ 04.04.97 F Handling of nuclear equipment FJ Erection and in-service inspection equipment FJA Tools and erection equipment for the reactor pressure vessel and closure head FJB Tools and erection equipment for reactor pressure vessel internals FJC In-service inspection equipment for the reactor pressure vessel and closure head FJE Tools and erection equipment for reactor coolant system components FJF In-service inspection equipment for reactor coolant system components FJM Equipment for reactor containment FJN Handling equipment for sodium-wetted parts FJP Washing and decontamination equipment FJQ Hot cell equipment Printout date 14. Mrz. 01 Page FJ1 of FJ1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : FK 04.04.97 F Handling of nuclear equipment FK Decontamination equipment (excluding cleaning equipment for fuel assemblies store *FAM* and fuel assemblies *FBC*) FKA Decontamination equipment for primary system components FKB Decontamination equipment for spent fuel shipping cask FKE Decontamination equipment for apparatus and vessels FKJ Decontamination equipment for fabrics FKK Decontamination equipment for machine components FKN Mobile decontamination equipment FKT Heating, cooling, flushing distribution system (also evacuation) FKV Lubricant supply system FKW Sealing fluid supply system FKX Fluid supply system for control and protection equipment FKY Control and protection equipment Printout date 14. Mrz. 01 Page FK1 of FK1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : FV 04.04.97 F Handling of nuclear equipment FV Lubricant supply system FVA Lubricant supply system FVB Lubricant supply system FVC Lubricant supply system FVD Lubricant supply system FVE Lubricant supply system FVF Lubricant supply system FVG Lubricant supply system FVH Lubricant supply system FVJ Lubricant supply system FVK Lubricant supply system FVL Lubricant supply system FVM Lubricant supply system FVN Lubricant supply system FVP Lubricant supply system FVQ Lubricant supply system FVR Lubricant supply system FVS Lubricant supply system FVT Lubricant supply system FVU Lubricant supply system Printout date 14. Mrz. 01 Page FV1 of FV1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : FW 04.04.97 F Handling of nuclear equipment FW Sealing fluid supply system FWA Sealing fluid supply system FWB Sealing fluid supply system FWC Sealing fluid supply system FWD Sealing fluid supply system FWE Sealing fluid supply system FWF Sealing fluid supply system FWG Sealing fluid supply system FWH Sealing fluid supply system FWJ Sealing fluid supply system FWK Sealing fluid supply system FWL Sealing fluid supply system FWM Sealing fluid supply system FWN Sealing fluid supply system FWP Sealing fluid supply system FWQ Sealing fluid supply system FWR Sealing fluid supply system FWS Sealing fluid supply system FWT Sealing fluid supply system FWU Sealing fluid supply system Printout date 14. Mrz. 01 Page FW1 of FW1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : FX 04.04.97 F Handling of nuclear equipment FX Fluid supply system for control and protection equipment FXA Fluid supply system for control and protection equipment FXB Fluid supply system for control and protection equipment FXC Fluid supply system for control and protection equipment FXD Fluid supply system for control and protection equipment FXE Fluid supply system for control and protection equipment FXF Fluid supply system for control and protection equipment FXG Fluid supply system for control and protection equipment FXH Fluid supply system for control and protection equipment FXJ Fluid supply system for control and protection equipment FXK Fluid supply system for control and protection equipment FXL Fluid supply system for control and protection equipment FXM Fluid supply system for control and protection equipment FXN Fluid supply system for control and protection equipment FXP Fluid supply system for control and protection equipment FXQ Fluid supply system for control and protection equipment FXR Fluid supply system for control and protection equipment FXS Fluid supply system for control and protection equipment FXT Fluid supply system for control and protection equipment FXU Fluid supply system for control and protection equipment Printout date 14. Mrz. 01 Page FX1 of FX1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : FY 04.04.97 F Handling of nuclear equipment FY Control and protection equipment FYA Control and protection equipment FYB Control and protection equipment FYC Control and protection equipment FYD Control and protection equipment FYE Control and protection equipment FYF Control and protection equipment FYG Control and protection equipment FYH Control and protection equipment FYJ Control and protection equipment FYK Control and protection equipment FYL Control and protection equipment FYM Control and protection equipment FYN Control and protection equipment FYP Control and protection equipment FYQ Control and protection equipment FYR Control and protection equipment FYS Control and protection equipment FYT Control and protection equipment FYU Control and protection equipment Printout date 14. Mrz. 01 Page FY1 of FY1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : G 04.04.97 G Water supply and disposal GA Raw water supply GB Treatment system (carbonate hardness removal) incl. cooling tower make-up water treatment system GC Treatment system (demineralization) GD Treatment system (others), blowdown demineralizing system GH Distribution systems (not drinking water) GK Drinking water supply GM Plant drainage system GN Plant drains treatment system GQ Domestic waste water collection and drainage systems GR Domestic waste water treatment system GT Water recovery from waste water GU Rainwater collection and drainage systems incl. treatment system GV Lubricant supply system GW Sealing fluid supply system GX Fluid supply system for control and protection equipment GY Control and protection equipment Printout date 14. Mrz. 01 Page G1 of G1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : GA 04.04.97 G Water supply and disposal GA Raw water supply GAA Extraction, mechanical cleaning Limit: from incl. intake to incl. mechanical cleaning system outlet GAC Piping and channel system Limit: from excl. intake or from excl. outlet of other system to excl. inlet to other system GAD Storage system Limit: from incl. storage system inlet to incl. storage system outlet, incl. intake and outfall GAF Pump system Limit: from incl. pump system suction nozzle to incl. pump system discharge nozzle GAV Lubricant supply system GAX Fluid supply system for control and protection equipment GAY Control and protection equipment Printout date 14. Mrz. 01 Page GA1 of GA1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : GB 04.04.97 G Water supply and disposal GB Treatment system (carbonate hardness removal) incl. cooling tower make-up water treatment system GBB Filtering, mechanical cleaning system Limit: from incl. separation equipment inlet to incl. separation equipment outlet GBC Aeration, gas injection system Limit: from excl. atmosphere or from incl. gas supply GBD Precipitation system (e. g. for carbonate hardness removal) Limit: from incl. precipitation equipment inlet to incl. precipitation equipment outlet GBE Acid proportioning system (e. g. for carbonate hardness removal) Limit: from incl. acid proportioning equipment from excl. branch off chemicals supply system to excl. inlet to other system GBF Ion exchange, reverse osmosis system (e. g. for carbonate hardness removal) Limit: from incl. ion exchanger inlet or from incl. isolating valve of chemicals supply system or auxiliary fluid supply system upstream of ion exchanger GBG Evaporation system (e. g. for carbonate hardness removal) Limit: from incl. feedwater inlet to incl. steam outlet and from incl. heating steam inlet to incl. condensate outlet GBH Deaeration, drying system Limit: from incl. deaerator or tank inlet to incl. tank outlet incl. warm-up equipment of vapour condenser GBJ Preheating, cooling system Limit: from incl. preheater or cooler inlet to incl. preheater or cooler outlet GBK Piping system, temporary storage system, pump system for main fluid Limit: Piping system: from excl. intake or from excl. outlet of other system to excl. inlet to other system to incl. fluid treatment system outlet Temporary storage system: from incl. temporary storage system inlet to incl. temporary storage system outlet Pump system: from incl. pump system suction nozzle to incl. pump system discharge nozzle GBL Storage system outside fluid treatment system (if not part of another system) Limit: from incl. inlet storage system to excl. outlet storage system incl. intake and outfall GBN Chemicals supply system Limit: from incl. intake or from incl. storage tank to excl. discharge into other system Printout date 14. Mrz. 01 Page GB1 of GB2 Siemens 2 nd complete, non-project related edition Condition-Date: GBP KKS Identification System for Power Plants Function key : GB 04.04.97 Regeneration, flushing equipment Limit: from incl. system inlet to excl. inlet to other system from excl. chemicals or auxiliary fluid supply system and flushing air supply system to incl. regenerating, flushing equipment GBQ Injection system for main fluid (for hardness stablization) Limit: from incl. injection equipment from excl. branch off chemicals supply system to excl. inlet to other system GBR Flushing water and residues removal system incl. neutralization Limit: from excl. outlet of respective system to excl. discharge into disposal system GBS Sludge thickening system Limit: from excl. outlet of respective system to excl. discharge into other system GBT Heating, cooling and flushing fluid distribution system Limit: from incl. heating, cooling, flushing fluid generation equipment or from excl. branch off heating, cooling, flushing fluid supply system to excl. user and from excl. user GBV Lubricant supply system GBX Fluid supply system for control and protection equipment GBY Control and protection equipment Printout date 14. Mrz. 01 Page GB2 of GB2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : GC 04.04.97 G Water supply and disposal GC Treatment system (demineralization) GCB Filtering, mechanical cleaning system Limit: from incl. separation equipment inlet to incl. separation equipment outlet GCC Aeration, gas injection system Limit: from excl. atmosphere or from incl. gas supply GCD Precipitation system (e. g. for carbonate hardness removal) Limit: from incl. precipitation equipment inlet to incl. precipitation equipment outlet GCE Acid proportioning system (e. g. for carbonate hardness removal) Limit: from incl. acid proportioning equipment or from excl. branch off chemicals supply system to excl. inlet to other system GCF Ion exchange, reverse osmosis system (e. g. for demineralization) Limit: from incl. ion exchanger inlet from incl. isolating valve of chemicals supply system or auxiliary fluid supply system upstream of ion exchanger GCG Evaporation system (e. g. for demineralization) Limit: from incl. feedwater inlet to incl. steam outlet and from incl. heating steam inlet to incl. condensate outlet GCH Deaeration, drying system Limit: from incl. deaerator or tank inlet to incl. tank outlet incl. warm-up equipment of vapour condenser GCJ Preheating, cooling system Limit: from incl. preheater or cooler inlet to incl. preheater or cooler outlet GCK Piping system, temporary storage system, pump system for main fluid Limit: Piping system: from excl. intake or from excl. outlet of other system to excl. inlet to other system to incl. fluid treatment system outlet Temporary storage system: from incl. temporary storage system inlet to incl. temporary storage system outlet Pump system: from incl. pump system suction nozzle to incl. pump system discharge nozzle GCL Storage system outside fluid treatment system (if not part of another system) Limit: from incl. inlet storage system to incl. outlet storage system incl. intake and outfall GCN Chemicals supply system Limit: from incl. intake or from incl. storage tank to excl. discharge into other system Printout date 14. Mrz. 01 Page GC1 of GC2 Siemens 2 nd complete, non-project related edition Condition-Date: GCP KKS Identification System for Power Plants Function key : GC 04.04.97 Regeneration, flushing equipment Limit: from incl. system inlet to excl. inlet to other system from excl. chemicals or auxiliary fluid supply system and flushing air supply system to incl. regenerating, flushing equipment GCQ Injection system for main fluid Limit: from incl. injection equipment or from excl. branch off chemicals supply system to excl. inlet to other system GCR Flushing water and residues removal system incl. neutralization Limit: from excl. outlet of respective system to excl. discharge into disposal system GCS Sludge thickening system Limit: from excl. outlet of respective system to excl. discharge into other system GCT Heating, cooling and flushing fluid distribution system Limit: from incl. heating, cooling and flushing fluid generation equipment or from excl. branch off heating, cooling, flushing fluid supply system to excl. user and from excl. user GCV Lubricant supply system GCX Fluid supply system for control and protection equipment GCY Control and protection equipment Printout date 14. Mrz. 01 Page GC2 of GC2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : GD 04.04.97 G Water supply and disposal GD Treatment system (others), blowdown demineralizing system GDB Filtering, mechanical cleaning system Limit: from incl. separation equipment inlet to incl. separation equipment outlet GDC Aearation, gas injection system Limit: from excl. atmosphere or from incl. gas supply GDD Precipitation system (e. g. for carbonate hardness removal) Limit: from incl. precipitation equipment inlet to incl. precipitation equipment outlet GDE Acid proportioning system (e. g. for carbonate hardness removal) Limit: from incl. acid proportioning equipment or from excl. branch off chemicals supply system to excl. inlet to other system GDF Ion exchange, reverse osmosis system (e. g. for demineralization) Limit: from incl. ion exchanger inlet or from incl. isolating valve of chemicals supply system or auxiliary fluid supply system upstream of ion exchanger GDG Evaporation system (e. g. for demineralization) Limit: from incl. feedwater inlet to incl. steam outlet and from incl. heating steam inlet to incl. condensate outlet GDH Deaeration, drying system Limit: from incl. deaerator or tank inlet to incl. tank outlet incl. warm-up equipment of vapour condenser GDJ Preheating, cooling system Limit: from incl. preheater or cooler inlet to incl. preheater or cooler outlet GDK Piping system, temporary storage system, pump system for main fluid Limit: Piping system: from excl. intake or from excl. outlet of other system to excl. inlet to other system to incl. fluid treatment system outlet Temporary storage system: from incl. temporary storage system inlet to incl. temporary storage system outlet Pump system: from incl. pump system suction nozzle to incl. pump system discharge nozzle GDL Storage system outside fluid treatment system (if not part of another system) Limit: from incl. inlet storage system to incl. outlet storage system incl. intake and outfall GDN Chemicals supply system Limit: from incl. intake or from incl. storage tank to excl. discharge into other system Printout date 14. Mrz. 01 Page GD1 of GD2 Siemens 2 nd complete, non-project related edition Condition-Date: GDP KKS Identification System for Power Plants Function key : GD 04.04.97 Regeneration, flushing equipment Limit: from incl. system inlet to excl. inlet to other system from excl. chemicals or auxiliary fluid supply system and flushing air supply system to incl. regenerating, flushing equipment GDQ Injection system for main fluid Limit: from incl. injection equipment or from excl. branch off chemicals supply system to excl. inlet to other system GDR Flushing water and residues removal system incl. neutralization Limit: from excl. outlet of respective system to excl. discharge into disposal system GDS Sludge thickening system Limit: from excl. outlet of respective system to excl. discharge into other system GDT Heating, cooling and flushing fluid distribution system Limit: from incl. heating, cooling, flushing fluid generation equipment or from excl. branch off heating, cooling, flushing fluid supply system to excl. user and from excl. user GDV Lubricant supply system GDX Fluid supply system for control and protection equipment GDY Control and protection equipment Printout date 14. Mrz. 01 Page GD2 of GD2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : GH 04.04.97 G Water supply and disposal GH Distribution systems (not drinking water) GHB Distribution system after treatment (carbonate hardness removal) Limit: to excl. GHC Distribution system after treatment (demineralization) (demineralized water supply system) Limit: to excl. GHD inlet to other system inlet to other system Distribution system after treatment (others) (stand-by water supply) Limit: to excl. inlet to other system GHE Distribution system (not drinking water) GHF Distribution system (not drinking water) GHG Distribution system (not drinking water) GHH Distribution system (not drinking water) GHJ Distribution system (not drinking water) GHK Distribution system (not drinking water) GHL Distribution system (not drinking water) GHM Distribution system (not drinking water) GHN Distribution system (not drinking water) GHP Distribution system (not drinking water) GHQ Distribution system (not drinking water) GHR Distribution system (not drinking water) GHS Distribution system (not drinking water) GHT Distribution system (not drinking water) GHU Distribution system (not drinking water) GHX Fluid supply system for control and protection equipment GHY Control and protection equipment Printout date 14. Mrz. 01 Page GH1 of GH1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : GK 04.04.97 G Water supply and disposal GK Drinking water supply GKA Receiving point GKB Storage, forwarding, distribution system GKC Drinking water supply (e. g. assigned to structures) GKD Drinking water supply (e. g. assigned to structures) GKE Drinking water supply (e. g. assigned to structures) GKF Drinking water supply (e. g. assigned to structures) GKG Drinking water supply (e. g. assigned to structures) GKH Drinking water supply (e. g. assigned to structures) GKJ Drinking water supply (e. g. assigned to structures) GKK Drinking water supply (e. g. assigned to structures) GKL Drinking water supply (e. g. assigned to structures) GKM Drinking water supply (e. g. assigned to structures) GKN Drinking water supply (e. g. assigned to structures) GKP Drinking water supply (e. g. assigned to structures) GKQ Drinking water supply (e. g. assigned to structures) GKR Drinking water supply (e. g. assigned to structures) GKS Drinking water supply (e. g. assigned to structures) GKT Drinking water supply (e. g. assigned to structures) GKU Drinking water supply (e. g. assigned to structures) GKX Fluid supply system for control and protection equipment GKY Control and protection equipment Printout date 14. Mrz. 01 Page GK1 of GK1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : GM 04.04.97 G Water supply and disposal GM Plant drainage system GMA Plant drainage system (e. g. assigned to structures) GMB Plant drainage system (e. g. assigned to structures) GMC Plant drainage system (e. g. assigned to structures) GMD Plant drainage system (e. g. assigned to structures) GME Plant drainage system (e. g. assigned to structures) GMF Plant drainage system (e. g. assigned to structures) GMG Plant drainage system (e. g. assigned to structures) GMH Plant drainage system (e. g. assigned to structures) GMJ Plant drainage system (e. g. assigned to structures) GMK Plant drainage system (e. g. assigned to structures) GML Plant drainage system (e. g. assigned to structures) GMM Plant drainage system (e. g. assigned to structures) GMN Plant drainage system (e. g. assigned to structures) GMP Plant drainage system (e. g. assigned to structures) GMQ Plant drainage system (e. g. assigned to structures) GMR Plant drainage system (e. g. assigned to structures) GMS Plant drainage system (e. g. assigned to structures) GMT Plant drainage system (e. g. assigned to structures) GMU Plant drainage system (e. g. assigned to structures) GMX Fluid supply system for control and protection equipment GMY Control and protection equipment Printout date 14. Mrz. 01 Page GM1 of GM1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : GN 04.04.97 G Water supply and disposal GN Plant drains treatment system GNB Filtering, mechanical cleaning system Limit: from incl. separation equipment inlet to incl. separation equipment outlet GNC Aeration, gas injection system Limit: from excl. atmosphere or from incl. gas supply GND Precipitation system (e. g. for carbonate hardness removal) Limit: from incl. precipitation equipment inlet to incl. precipitation equipment outlet GNE Acid proportioning system (e. g. for carbonate hardness removal) Limit: from incl. acid proportioning equipment or from excl. branch off chemicals supply system to excl. inlet to other system GNF Ion exchange system (e. g. for demineralization) Limit: from incl. ion exchanger inlet from incl. isolating valve of chemicals supply system or auxiliary fluid supply system upstream of ion exchanger GNG Evaporation system (e. g. for demineralization) Limit: from incl. feedwater inlet to incl. steam outlet and from incl. heating steam inlet to incl. condensate outlet GNH Deaeration, drying system Limit: from incl. deaerator or tank inlet to incl. tank outlet incl. warm-up equipment of vapour condenser GNJ Preheating, cooling system Limit: from incl. preheater or cooler inlet to incl. preheater or cooler outlet GNK Piping system, temporary storage system, pump system for main fluid Limit: Piping system: from excl. intake or from excl. outlet of other system to excl. inlet to other system to incl. fluid treatment system outlet Temporary storage system: from incl. temporary storage system inlet to incl. temporary storage system outlet Pump system: from incl. pump system suction nozzle to incl. pump system discharge nozzle GNL Storage system outside fluid treatment system (if not part of another system) Limit: from incl. inlet storage system to incl. outlet storage system incl. intake and outfall GNN Chemicals supply system Limit: from incl. intake or from incl. storage tank to excl. discharge into other system Printout date 14. Mrz. 01 Page GN1 of GN2 Siemens 2 nd complete, non-project related edition Condition-Date: GNP KKS Identification System for Power Plants Function key : GN 04.04.97 Regeneration, flushing equipment Limit: from incl. system inlet to excl. inlet to other system from excl. chemicals or auxiliary fluid supply system and flushing air supply system to incl. regenerating, flushing equipment GNQ Injection system for main fluid Limit: from incl. injection equipment or from excl. branch off chemicals supply system to excl. inlet to other system GNR Flushing water and residues removal system incl. neutralization Limit: from excl. outlet of respective system to excl. discharge into disposal system GNS Sludge thickening system Limit: from excl. outlet of respective system to excl. discharge into other system GNT Heating, cooling and flushing fluid distribution system Limit: from incl. heating, cooling, flushing fluid generation equipment or from excl. branch off heating, cooling, flushing fluid supply system to excl. user and from excl. user GNV Lubricant supply system GNX Fluid supply system for control and protection equipment GNY Control and protection equipment Printout date 14. Mrz. 01 Page GN2 of GN2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : GQ 04.04.97 G Water supply and disposal GQ Domestic waste water collection and drainage systems GQA Domestic waste water collection and drainage system (e. g. assigned to structures) GQB Domestic waste water collection and drainage system (e. g. assigned to structures) GQC Domestic waste water collection and drainage system (e. g. assigned to structures) GQD Domestic waste water collection and drainage system (e. g. assigned to structures) GQE Domestic waste water collection and drainage system (e. g. assigned to structures) GQF Domestic waste water collection and drainage system (e. g. assigned to structures) GQG Domestic waste water collection and drainage system (e. g. assigned to structures) GQH Domestic waste water collection and drainage system (e. g. assigned to structures) GQJ Domestic waste water collection and drainage system (e. g. assigned to structures) GQK Domestic waste water collection and drainage system (e. g. assigned to structures) GQL Domestic waste water collection and drainage system (e. g. assigned to structures) GQM Domestic waste water collection and drainage system (e. g. assigned to structures) GQN Domestic waste water collection and drainage system (e. g. assigned to structures) GQP Domestic waste water collection and drainage system (e. g. assigned to structures) GQQ Domestic waste water collection and drainage system (e. g. assigned to structures) GQR Domestic waste water collection and drainage system (e. g. assigned to structures) GQS Domestic waste water collection and drainage system (e. g. assigned to structures) GQT Domestic waste water collection and drainage system (e. g. assigned to structures) GQU Domestic waste water collection and drainage system (e. g. assigned to structures) GQX Fluid supply system for control and protection equipment Printout date 14. Mrz. 01 Page GQ1 of GQ2 Siemens 2 nd complete, non-project related edition Condition-Date: GQY KKS Identification System for Power Plants Function key : GQ 04.04.97 Control and protection equipment Printout date 14. Mrz. 01 Page GQ2 of GQ2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : GR 04.04.97 G Water supply and disposal GR Domestic waste water treatment system GRB Filtering, mechanical cleaning system Limit: from incl. separation equipment inlet to incl. separation equipment outlet GRC Aeration, gas injection system Limit: from excl. atmosphere or from incl. gas supply GRD Precipitation system (e. g. for carbonate hardness removal) Limit: from incl. precipitation equipment inlet to incl. precipitation equipment outlet GRE Acid proportioning system (e. g. for carbonate hardness removal) Limit: from incl. acid proportioning equipment or from excl. branch off chemicals supply system to excl. inlet to other system GRF Ion exchange system (e. g. for demineralization) Limit: from incl. ion exchanger inlet or from incl. isolating valve of chemicals supply system or auxiliary fluid supply system upstream of ion exchanger GRG Evaporation system (e. g. for demineralization) Limit: from incl. feedwater inlet to incl. steam outlet and from incl. heating steam inlet to incl. condensate outlet GRH Deaeration, drying system Limit: from incl. deaerator or tank inlet to incl. tank outlet incl. warm-up equipment of vapour condenser GRJ Preheating, cooling system Limit: from incl. preheater or cooler inlet to incl. preheater or cooler outlet GRK Piping system, temporary storage system, pump system for main fluid Limit: Piping system: from excl. intake or from excl. outlet of other system to excl. inlet to other system to incl. fluid treatment system outlet Temporary storage system: from incl. temporary storage system inlet to incl. temporary storage system outlet Pump system: from incl. pump system suction nozzle to incl. pump system discharge nozzle GRL Storage system outside fluid treatment system (if not part of another system) Limit: from incl. inlet storage system to incl. outlet storage system incl. intake and outfall GRN Chemicals supply system Limit: from incl. intake or from incl. storage tank to excl. discharge into other system Printout date 14. Mrz. 01 Page GR1 of GR2 Siemens 2 nd complete, non-project related edition Condition-Date: GRP KKS Identification System for Power Plants Function key : GR 04.04.97 Regeneration,flushing equipment Limit: from incl. system inlet to excl. inlet to other system from excl. chemicals or auxiliary fluid supply system and flushing air supply system to incl. regenerating, flushing equipment GRQ Injection system for main fluid Limit: from incl. injection equipment or from excl. branch off chemicals supply system to excl. inlet to other system GRR Flushing water and residues removal system incl. neutralization Limit: from excl. outlet of respective system to excl. discharge into disposal system GRS Sludge thickening system Limit: from excl. outlet of respective system to excl. discharge into other system GRT Heating, cooling and flushing fluid distribution system Limit: from incl. heating, cooling, flushing fluid generation equipment or from excl. branch off heating, cooling, flushing fluid supply system to excl. user and from excl. user GRV Lubricant supply system GRX Fluid supply system for control and protection equipment GRY Control and protection equipment Printout date 14. Mrz. 01 Page GR2 of GR2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : GT 04.04.97 G Water supply and disposal GT Water recovery from waste water GTA Water recovery from waste water GTB Water recovery from waste water GTC Water recovery from waste water GTD Water recovery from waste water GTE Water recovery from waste water GTF Water recovery from waste water GTG Water recovery from waste water GTH Water recovery from waste water GTJ Water recovery from waste water GTK Water recovery from waste water GTL Water recovery from waste water GTM Water recovery from waste water GTN Water recovery from waste water GTP Water recovery from waste water GTQ Water recovery from waste water GTR Water recovery from waste water GTS Water recovery from waste water GTT Water recovery from waste water GTU Water recovery from waste water GTX Fluid supply system for control and protection equipment GTY Control and protection equipment Printout date 14. Mrz. 01 Page GT1 of GT1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : GU 04.04.97 G Water supply and disposal GU Rainwater collection and drainage systems incl. treatment system GUA Rainwater collection and drainage systems incl. treatment system (e. g. assigned to structures) GUB Rainwater collection and drainage systems incl. treatment system (e. g. assigned to structures) GUC Rainwater collection and drainage systems incl. treatment system (e. g. assigned to structures) GUD Rainwater collection and drainage systems incl. treatment system (e. g. assigned to structures) GUE Rainwater collection and drainage systems incl. treatment system (e. g. assigned to structures) GUF Rainwater collection and drainage systems incl. treatment system (e. g. assigned to structures) GUG Rainwater collection and drainage systems incl. treatment system (e. g. assigned to structures) GUH Rainwater collection and drainage systems incl. treatment system (e. g. assigned to structures) GUJ Rainwater collection and drainage systems incl. treatment system (e. g. assigned to structures) GUK Rainwater collection and drainage systems incl. treatment system (e. g. assigned to structures) GUL Rainwater collection and drainage systems incl. treatment system (e. g. assigned to structures) GUM Rainwater collection and drainage systems incl. treatment system (e. g. assigned to structures) GUN Rainwater collection and drainage systems incl. treatment system (e. g. assigned to structures) GUP Rainwater collection and drainage systems incl. treatment system (e. g. assigned to structures) GUQ Rainwater collection and drainage systems incl. treatment system (e. g. assigned to structures) GUR Rainwater collection and drainage systems incl. treatment system (e. g. assigned to structures) GUS Rainwater collection and drainage systems incl. treatment system (e. g. assigned to structures) GUT Rainwater collection and drainage systems incl. treatment system (e. g. assigned to structures) GUU Rainwater collection and drainage systems incl. treatment system (e. g. assigned to structures) GUX Fluid supply system for control and protection equipment Printout date 14. Mrz. 01 Page GU1 of GU2 Siemens 2 nd complete, non-project related edition Condition-Date: GUY KKS Identification System for Power Plants Function key : GU 04.04.97 Control and protection equipment Printout date 14. Mrz. 01 Page GU2 of GU2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : GV 04.04.97 G Water supply and disposal GV Lubricant supply system GVA Lubricant supply system GVB Lubricant supply system GVC Lubricant supply system GVD Lubricant supply system GVE Lubricant supply system GVF Lubricant supply system GVG Lubricant supply system GVH Lubricant supply system GVJ Lubricant supply system GVK Lubricant supply system GVL Lubricant supply system GVM Lubricant supply system GVN Lubricant supply system GVP Lubricant supply system GVQ Lubricant supply system GVR Lubricant supply system GVS Lubricant supply system GVT Lubricant supply system GVU Lubricant supply system Printout date 14. Mrz. 01 Page GV1 of GV1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : GW 04.04.97 G Water supply and disposal GW Sealing fluid supply system GWA Sealing fluid supply system GWB Sealing fluid supply system GWC Sealing fluid supply system GWD Sealing fluid supply system GWE Sealing fluid supply system GWF Sealing fluid supply system GWG Sealing fluid supply system GWH Sealing fluid supply system GWJ Sealing fluid supply system GWK Sealing fluid supply system GWL Sealing fluid supply system GWM Sealing fluid supply system GWN Sealing fluid supply system GWP Sealing fluid supply system GWQ Sealing fluid supply system GWR Sealing fluid supply system GWS Sealing fluid supply system GWT Sealing fluid supply system GWU Sealing fluid supply system Printout date 14. Mrz. 01 Page GW1 of GW1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : GX 04.04.97 G Water supply and disposal GX Fluid supply system for control and protection equipment GXA Fluid supply system for control and protection equipment GXB Fluid supply system for control and protection equipment GXC Fluid supply system for control and protection equipment GXD Fluid supply system for control and protection equipment GXE Fluid supply system for control and protection equipment GXF Fluid supply system for control and protection equipment GXG Fluid supply system for control and protection equipment GXH Fluid supply system for control and protection equipment GXJ Fluid supply system for control and protection equipment GXK Fluid supply system for control and protection equipment GXL Fluid supply system for control and protection equipment GXM Fluid supply system for control and protection equipment GXN Fluid supply system for control and protection equipment GXP Fluid supply system for control and protection equipment GXQ Fluid supply system for control and protection equipment GXR Fluid supply system for control and protection equipment GXS Fluid supply system for control and protection equipment GXT Fluid supply system for control and protection equipment GXU Fluid supply system for control and protection equipment Printout date 14. Mrz. 01 Page GX1 of GX1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : GY 04.04.97 G Water supply and disposal GY Control and protection equipment GYA Control and protection equipment GYB Control and protection equipment GYC Control and protection equipment GYD Control and protection equipment GYE Control and protection equipment GYF Control and protection equipment GYG Control and protection equipment GYH Control and protection equipment GYJ Control and protection equipment GYK Control and protection equipment GYL Control and protection equipment GYM Control and protection equipment GYN Control and protection equipment GYP Control and protection equipment GYQ Control and protection equipment GYR Control and protection equipment GYS Control and protection equipment GYT Control and protection equipment GYU Control and protection equipment Printout date 14. Mrz. 01 Page GY1 of GY1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : H 04.04.97 H Conventional heat generation HA Pressure system, feedwater and steam sections HB Support structure, enclosure, steam generator interior HC Fireside heat transfer surface cleaning equipment HD Ash and slag removal, particulate removal HF Bunker, feeder and pulverizing system HH Main firing system (electric-powered as well) HJ Ignition firing equipment (if separate) HL Combustion air system (primary air, secondary air) HM Gas heating system (for closed cycle) HN Flue gas exhaust (without flue gas treatment) HR Chemical flue gas treatment system incl. residues removal, adsorptive process HS Chemical flue gas treatment system incl. residues removal, catalytic process (e. g. DENOX) HT Chemical flue gas treatment system incl. residues removal, absorptive process (e. g. flue gas desulfurization plants) HU Flue gas reheating system HV Lubricant supply system HW Sealing fluid supply system HX Fluid supply system for control and protection equipment HY Control and protection equipment Printout date 14. Mrz. 01 b Page H1 of H1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : HA 04.04.97 H Conventional heat generation HA Pressure system, feedwater and steam sections HAA LP part-flow feed heating system (flue-gas-heated) Limit: from incl. LP part-flow feed heating system inlet to incl. LP part-flow feed heating system outlet HAB HP part-flow feed heating system (flue-gas-heated) Limit: from incl. HP part-flow feed heating system inlet to incl. HP part-flow feed heating system outlet HAC Economizer system Limit: from incl. oiler inlet header to excl. evaporator inlet incl. control and auxiliary heat transfer surfaces HAD Evaporator system a Limit: from incl. evaporator system inlet to incl. evaporator system outlet and to incl. water/steam separator and water collecting vessel HAG Circulation system a Limit: from excl. water/steam separator and water collecting vessel to excl. inlet to heat transfer surface system (removal systems are classified under *L..*) or to excl. feedwater system HAH HP superheater system Limit: from excl. evaporator system outlet to incl. boiler outlet header HAJ Reheat system Limit: from incl. reheater inlet header to incl. reheater outlet header HAK Secondary reheat system Limit: from incl. second reheater inlet header to incl. second reheater outlet header HAM Triflux system Limit: from incl. triflux system inlet to incl. triflux system outlet HAN Pressure system drainage and venting systems Limit: from incl. collecting point or from excl. final drain/vent valve to excl. discharge into other system HAV Lubricant supply system HAW Sealing fluid supply system HAX Fluid supply system for control and protection equipment HAY Control and protection equipment Printout date 14. Mrz. 01 Page HA1 of HA1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : HB 04.04.97 H Conventional heat generation HB Support structure, enclosure, steam generator interior HBA Frame incl. foundations HBB Enclosures HBC Brick linings incl. insulating brickwork HBD Platforms, stairways HBE Pressure vessel (supercharged boiler) HBK Steam generator interior Limit: from excl. furnace to excl. flue gas exhaust Printout date 14. Mrz. 01 Page HB1 of HB1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : HC 04.04.97 H Conventional heat generation HC Fireside heat transfer surface cleaning equipment HCA Air sootblowing system Limit: from excl. branch off supply system HCB Steam sootblowing system Limit: from excl. branch off supply system HCC Water sootblowing system Limit: from excl. branch off supply system HCD Flushing equipment Limit: from excl. branch off supply system HCE Rapping gear HCF Shot cleaning system HCG Soundwave system HCV Lubricant supply system HCW Sealing fluid supply system HCX Fluid supply system for control and protection equipment HCY Control and protection equipment Printout date 14. Mrz. 01 Page HC1 of HC1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : HD 04.04.97 H Conventional heat generation HD Ash and slag removal, particulate removal HDA Furnace ash removal, furnace slag removal, bed ash removal Limit: from incl. removal equipment to excl. discharge into disposal system or to incl. pressure vessel outlet or to excl. ash return system HDB Bed ash return system Limit: from excl. furnace outlet or from excl. bed ash removal outlet to excl. furnace inlet HDC Ash return system incl. temporary storage Limit: from incl. removal equipment for heat recovery surfaces or from excl. *HDD*, *HDE*, *HDF* to excl. ash disposal system *ETG* or to excl. inlet to other system HDD Mechanical dust handling and return system Limit: from excl. flue gas duct inlet to excl. flue gas duct outlet or to excl. discharge to other system HDE Electrostatic precipitator and return system Limit: from excl. flue gas duct inlet to excl. flue gas duct outlet or to excl. discharge to other system HDF Cyclone dust removal and return system Limit: from excl. flue gas duct inlet to excl. flue gas duct outlet or to excl. discharge to other system HDT Fluid supply system for ash, slag and dust moistening Limit: from excl. intake to excl. user HDU Carrier air supply system Limit: from excl. branch off or from incl. compressor system to excl. inlet to carrier air system HDV Lubricant supply system HDW Sealing fluid supply system HDX Fluid supply system for control and protection equipment HDY Control and protection equipment Printout date 14. Mrz. 01 Page HD1 of HD1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : HF 04.04.97 H Conventional heat generation HF Bunker, feeder and pulverizing system HFA Bunker for pulverizing system Limit: from excl. receiving point to incl. outlet HFB Feeder system Limit: from excl. bunker outlet to excl. oversize reject shaft or pulverizing system HFC Pulverizing system (incl. classifier) Limit: from incl. pulverizing system inlet to excl. pulverized coal line HFD Flue gas return system Limit: from excl. outlet of other system to excl. pulverizing system HFE Mill air system, carrier air system Limit: from incl. from excl. to excl. to excl. to excl. HFF air inlet or branch off *HLA* downcomer shaft or pulverizing system or flue gas recirculation system Vapour/exhaust gas system Limit: from excl. separation equipment to excl. other system HFG Pulverized coal temporary storage bunker after central pulverizing system (indirect firing) Limit: from excl. pulverizing system outlet to incl. temporary storage bunker outlet, incl. rotary vane feeder HFV Lubricant supply system HFW Sealing fluid supply system HFX Fluid supply system for control and protection equipment HFY Control and protection equipment Printout date 14. Mrz. 01 Page HF1 of HF1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS 04.04.97 H Conventional heat generation HH Main firing system (electric-powered as well) HHA Main burners Limit: from incl. HHB Identification System for Power Plants Function key : HH respective fuel-side and air-side burner inlet Retarded combustion grate Limit: from incl. retarded combustion grate inlet to excl. inlet to other system HHC Grate combustion system Limit: from incl. fuel receiving point or from incl. grate combustion inlet to excl. inlet to other system HHD Other burner equipment (e. g. vapour burner, flue dust burner) Limit: from incl. inlet to incl. outlet HHE Pulverized coal bin, forwarding and distribution system Limit: from excl. pulverizing system outlet or from excl. pulverized coal bin outlet after central pulverizing system (indirect feed) *HFG* or from excl. outlet of other system to excl. main burner equipment HHF Oil temporary storage, pump and distribution system Limit: from excl. branch off main supply line or from incl. temporary storage tank to excl. main burner equipment HHG Gas pressure reduction, distribution system Limit: from excl. branch off main supply line to excl. main burner equipment HHH Temporary storage, forwarding and distribution system for other fuels, fluid 1 HHJ Temporary storage, forwarding and distribution system for other fuels, fluid 2 HHK Temporary storage, forwarding and distribution system for other fuels, fluid 3 HHL Combustion air supply system Limit: from incl. branch off ducting system (*HLA*) to excl. user HHM Atomizer medium supply system (steam) Limit: from excl. branch off supply system to excl. user HHN Atomizer medium supply system (air) Limit: from excl. branch off supply system to excl. user HHP Coolant supply system (steam) Limit: from excl. branch off supply system to excl. user HHQ Coolant supply system (air) Limit: from excl. branch off supply system to excl. user Printout date 14. Mrz. 01 Page HH1 of HH2 Siemens 2 nd complete, non-project related edition Condition-Date: HHR KKS Identification System for Power Plants Function key : HH 04.04.97 Purging medium supply system (steam) Limit: from excl. branch off supply system to excl. user HHS Purging medium supply system (air) Limit: from excl. branch off supply system to excl. user HHT Heating medium supply system (steam) Limit: from excl. branch off supply system to excl. user and from excl. user to excl. inlet to other system HHU Heating medium supply system (hot water) Limit: from excl. branch off supply system to excl. user and from excl. user to excl. inlet to other system HHV Lubricant supply system HHW Sealing fluid supply system HHX Fluid supply system for control and protection equipment HHY Control and protection equipment HHZ Electric heating system Printout date 14. Mrz. 01 Page HH2 of HH2 Siemens 2 nd complete, non-project related edition Condition-Date: 04.04.97 H Conventional heat generation HJ Ignition firing equipment (if separate) HJA Ignition burners Limit: from incl. HJE KKS Identification System for Power Plants Function key : HJ resp. fuel-side and air-side burner inlet Pulverized coal bin, forwarding and distribution system Limit: from excl. pulverizing system outlet or from excl. pulverized coal temporary storage bunker outlet (if central pulverizing system,* HFG*) or from excl. outlet of other system to excl. ignition burner equipment HJF Oil temporary storage, pump and distribution system Limit: from excl. branch off main supply line or from incl. temporary storage tank to excl. ignition burner equipment HJG Gas pressure reduction, distribution system Limit: from excl. branch off main supply line to excl. lignition burner equipment HJL Combustion air supply system Limit: from incl. branch off ducting system (*HLA*) or from incl. air inlet, incl. fan to excl. user HJM Atomizer medium supply system (steam) Limit: from excl. branch off supply system to excl. user HJN Atomizer medium supply system (air) Limit: from excl. branch off supply system to excl. user HJP Cooling supply system (steam) Limit: from excl. branch off supply system to excl. user HJQ Cooling supply system (air) Limit: from excl. branch off supply system to excl. user HJR Purging medium supply system (steam) Limit: from excl. branch off supply system to excl. user HJS Purging medium supply system (air) Limit: from excl. branch off supply system to excl. user HJT Heating medium supply system (steam) Limit: from excl. branch off supply system to excl. user and from excl. user to excl. inlet to other system HJU Heating medium supply system (hot water) Limit: from excl. branch off supply system to excl. user and from excl. user to excl. inlet to other system Printout date 14. Mrz. 01 Page HJ1 of HJ2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : HJ 04.04.97 HJV Lubricant supply system HJW Sealing fluid supply system HJX Fluid supply system for control and protection equipment HJY Control and protection equipment Printout date 14. Mrz. 01 Page HJ2 of HJ2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : HL 04.04.97 H Conventional heat generation HL Combustion air system (primary air, secondary air) HLA Ducting system Limit: from incl. air inlet to excl. branch off firing system or mill air system, carrier air system or to excl. branch to *HFE*, excl. fan system, air heater system and gas turbine exhaust gas system HLB Fan system, forced-draught fan system Limit: from incl. fan system inlet to excl. fan system outlet HLC External air heating system (not flue-gas-heated) Limit: from incl. heater inlet to incl. heater outlet HLD Air heating system (flue-gas-heated) Limit: from incl. heater inlet to incl. heater outlet HLU Air pressure relief system Task: to relief pressure in air system HLV Lubricant supply system HLW Sealing fluid supply system HLX Fluid supply system for control and protection equipment HLY Control and protection equipment Printout date 14. Mrz. 01 Page HL1 of HL1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : HM 04.04.97 H Conventional heat generation HM Gas heating system (for closed cycle) HMA Primary heater (primary convection section) Limit: from incl. cold gas inlet header or from excl. heat exchanger cold gas outlet to incl. primary heater outlet or to excl. mixing header inlet HMB Radiation section Limit: from incl. mixing header inlet to incl. radiation section outlet or to excl. secondary heater inlet header HMC Secondary heater (second convection section) Limit: from incl. inlet header to incl. hot gas outlet header HMD Reheat system Limit: from incl. reheater inlet header to incl. reheater outlet header HMV Lubricant supply system HMW Sealing fluid supply system HMX Fluid supply system for control and protection equipment HMY Control and protection equipment Printout date 14. Mrz. 01 Page HM1 of HM1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : HN 04.04.97 H Conventional heat generation HN Flue gas exhaust (without flue gas treatment) HNA Ducting system Limit: from excl. boiler outlet or from excl. outlet of other system to excl. smoke stack, excl. air heater, flue gas dust handling system, induced-draught fan system, gas scrubber system, chemical flue gas treatment system HNC Induced-draught fan system Limit: from incl. induced-draught fan system inlet to incl. induced-draught fan system outlet HNE Smoke stack system (chimney) Limit: from incl. HNF inlet Flue gas recirculation system Limit: from excl. branch off main flue gas exhaust system to excl. inlet to other system, incl. fan system HNU Flue gas pressure relief system Task: to relief pressure in flue gas system HNV Lubricant supply system HNW Sealing fluid supply system HNX Fluid supply system for control and protection equipment HNY Control and protection equipment Printout date 14. Mrz. 01 Page HN1 of HN1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : HR 20.01.99 H Conventional heat generation HR Chemical flue gas treatment system incl. residues removal, adsorptive process b HRA Flue gas ducting system within *HR.* b Limit: from excl. *HNA* to excl. inlet to *HNA* HRB Flue gas-side heat exchanger b Limit: from incl. inlet to incl. outlet HRC Flue gas fan system b Limit: from incl. inlet to incl. outlet HRD Adsorption system (reactor) b Limit: from incl. inlet to incl. outlet HRE Flue gas-side cleaning equipment b Limit: from excl. branch off supply system HRH Residues separation b Limit: from incl. inlet to incl. outlet HRJ Fresh coke supply incl. storage b Limit: from excl. receiving point to excl. fresh coke distribution system or to excl. fresh coke treatment HRK Fresh coke treatment and distribution b Limit: from excl. fresh coke supply to excl. reactor HRL Water supply and disposal system b HRM Coke removal system b Limit: from excl. reactor to excl. spent coke handling or to excl. spent coke treatment HRN Spent coke handling incl. storage b Limit: from excl. coke removal or from excl. spent coke treatment to incl. discharge HRP Spent coke treatment and disposal b Limit: from excl. spent coke handling to excl. spent coke handling or to incl. discharge HRQ Dust extraction and disposal b Limit: from incl. inlet to incl. discharge HRR Inerting system b Limit: from incl. storage to excl. inlet to other system Printout date 19. Mrz. 01 Page HR1 of HR2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : HR 20.01.99 HRV Lubricant supply system HRW Sealing fluid supply system HRX Fluid supply system for control and protection equipment HRY Control and protection equipment Printout date 19. Mrz. 01 Page HR2 of HR2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : HS 04.04.97 H Conventional heat generation HS Chemical flue gas treatment system incl. residues removal, catalytic process (e. g. DENOX) HSA Flue gas ducting system within *HS.* Limit: from excl. *HNA* to incl. evaporator system outlet and to excl. inlet to *HNA* HSB Flue gas-side heat exchanger, gas heater (not *HU.*) Limit: from incl. inlet to incl. outlet HSC Flue gas fan system Limit: from incl. inlet to incl. outlet HSD Reactor (reduction) Limit: from incl. inlet to incl. outlet HSE Converter (oxidation) Limit: from incl. inlet to incl. outlet HSF Flue gas-side cleaning equipment for reactor Limit: from excl. branch off supply system HSG Reduction agent dilution system Limit: from excl. outlet of other system or from incl. supply system to excl. reduction agent treatment system HSH (Residues) separator Limit: from incl. inlet to incl. outlet HSJ Reduction agent supply system incl. storage HSK Reduction agent treatment and distribution system Limit: from excl. reduction agent supply to incl. reduction agent injection incl. coolant inlet HSL Water supply and disposal system HSM Chemicals and additives supply system HSN Drainage systems Task: water collecting, storage, return HSP Flyash collecting system (incl. filtering) and removal system Limit: from incl. separator/filter or from excl. flue gas ducting system to excl. inlet to disposal system HSQ Sprinkler system incl. drainage Limit: from incl. inlet to excl. inlet to other system HSR Oxidizing agent treatment and distribution system Limit: from excl. outlet converter to excl. inlet converter Printout date 14. Mrz. 01 Page HS1 of HS2 Siemens 2 nd complete, non-project related edition Condition-Date: HSS KKS Identification System for Power Plants Function key : HS 04.04.97 (Residues) forwarding, storage, loading system Limit: from excl. outlet residues separator HST Flushing fluid system incl. supply Task: flushing of reducing agent systems HSU Heating fluid system Limit: from excl. heating fluid supply to excl. evaporator inlet from excl. evaporator outlet to excl. inlet to other system HSV Lubricant supply system HSW Sealing fluid supply system HSX Fluid supply system for control and protection equipment HSY Control and protection equipment Printout date 14. Mrz. 01 Page HS2 of HS2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : HT 04.04.97 H Conventional heat generation HT Chemical flue gas treatment system incl. residues removal, absorptive process (e. g. flue gas desulfurization plants) HTA Flue gas ducting system within *HT.* Limit: from excl. *HNA* to excl. inlet to *HNA* HTB Flue gas-side heat exchanger, gas heater (not *HU.*) Limit: from incl. inlet to incl. outlet HTC Flue gas fan system Limit: from incl. inlet to incl. outlet HTD Flue gas scrubbing system Limit: from incl. flue gas inlet to incl. moisture separator outlet HTE Flue gas cleaning and filtering system HTF Absorption cycle Limit: from incl. inlet to incl. outlet HTG Oxidation system incl. supply system Limit: to excl. HTH user or scrubber Flue gas cooling system Limit: from incl. inlet flue gas cooler incl. heat dissipation system without second heat sink to incl. outlet flue gas cooler HTJ Absorbent supply system incl. storage system Limit: to excl. HTK mashing (*HTK*) Absorbent preparation and distribution system Limit: from incl. mashing, slaking to excl. user or scrubber HTL Piping system for discharge of solids incl. water removal and return excl. thickening and solids dewatering systems HTM Thickening and solids dewatering system Limit: from incl. inlet to incl. outlet HTN Solids drying, compacting system HTP (Solids/ product) forwarding, storage, loading system HTQ Water supply and disposal system HTS Chemicals and additives supply system HTT Drainage systems Task: water collecting, storage, return HTV Lubricant supply system HTW Sealing fluid supply system Printout date 14. Mrz. 01 Page HT1 of HT2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : HT 04.04.97 HTX Fluid supply system for control and protection equipment HTY Control and protection equipment Printout date 14. Mrz. 01 Page HT2 of HT2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : HU 04.04.97 H Conventional heat generation HU Flue gas reheating system HUA Flue gas reheating system HUB Flue gas reheating system HUC Flue gas reheating system HUD Flue gas reheating system HUE Flue gas reheating system HUF Flue gas reheating system HUG Flue gas reheating system HUH Flue gas reheating system HUJ Flue gas reheating system HUK Flue gas reheating system HUL Flue gas reheating system HUM Flue gas reheating system HUN Flue gas reheating system HUP Flue gas reheating system HUQ Flue gas reheating system HUR Flue gas reheating system HUS Flue gas reheating system HUT Flue gas reheating system HUU Flue gas reheating system HUV Lubricant supply system HUW Sealing fluid supply system HUX Fluid supply system for control and protection equipment HUY Control and protection equipment Printout date 14. Mrz. 01 Page HU1 of HU1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : HV 04.04.97 H Conventional heat generation HV Lubricant supply system HVA Lubricant supply system HVB Lubricant supply system HVC Lubricant supply system HVD Lubricant supply system HVE Lubricant supply system HVF Lubricant supply system HVG Lubricant supply system HVH Lubricant supply system HVJ Lubricant supply system HVK Lubricant supply system HVL Lubricant supply system HVM Lubricant supply system HVN Lubricant supply system HVP Lubricant supply system HVQ Lubricant supply system HVR Lubricant supply system HVS Lubricant supply system HVT Lubricant supply system HVU Lubricant supply system Printout date 14. Mrz. 01 Page HV1 of HV1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : HW 04.04.97 H Conventional heat generation HW Sealing fluid supply system HWA Sealing fluid supply system HWB Sealing fluid supply system HWC Sealing fluid supply system HWD Sealing fluid supply system HWE Sealing fluid supply system HWF Sealing fluid supply system HWG Sealing fluid supply system HWH Sealing fluid supply system HWJ Sealing fluid supply system HWK Sealing fluid supply system HWL Sealing fluid supply system HWM Sealing fluid supply system HWN Sealing fluid supply system HWP Sealing fluid supply system HWQ Sealing fluid supply system HWR Sealing fluid supply system HWS Sealing fluid supply system HWT Sealing fluid supply system HWU Sealing fluid supply system Printout date 14. Mrz. 01 Page HW1 of HW1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : HX 04.04.97 H Conventional heat generation HX Fluid supply system for control and protection equipment HXA Fluid supply system for control and protection equipment HXB Fluid supply system for control and protection equipment HXC Fluid supply system for control and protection equipment HXD Fluid supply system for control and protection equipment HXE Fluid supply system for control and protection equipment HXF Fluid supply system for control and protection equipment HXG Fluid supply system for control and protection equipment HXH Fluid supply system for control and protection equipment HXJ Fluid supply system for control and protection equipment HXK Fluid supply system for control and protection equipment HXL Fluid supply system for control and protection equipment HXM Fluid supply system for control and protection equipment HXN Fluid supply system for control and protection equipment HXP Fluid supply system for control and protection equipment HXQ Fluid supply system for control and protection equipment HXR Fluid supply system for control and protection equipment HXS Fluid supply system for control and protection equipment HXT Fluid supply system for control and protection equipment HXU Fluid supply system for control and protection equipment Printout date 14. Mrz. 01 Page HX1 of HX1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : HY 04.04.97 H Conventional heat generation HY Control and protection equipment HYA Control and protection equipment HYB Control and protection equipment HYC Control and protection equipment HYD Control and protection equipment HYE Control and protection equipment HYF Control and protection equipment HYG Control and protection equipment HYH Control and protection equipment HYJ Control and protection equipment HYK Control and protection equipment HYL Control and protection equipment HYM Control and protection equipment HYN Control and protection equipment HYP Control and protection equipment HYQ Control and protection equipment HYR Control and protection equipment HYS Control and protection equipment HYT Control and protection equipment HYU Control and protection equipment Printout date 14. Mrz. 01 Page HY1 of HY1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : J 04.04.97 J Nuclear heat generation JA Reactor system JB Reactor vessel internals (use *JB* only if *JAC *is not sufficient for identification) JD Reactor control and shutdown equipment JE Reactor coolant system JF Moderator system JG Secondary coolant system (applicable only to three-cycle plants) JK Reactor core with appurtenances Task: energy conversion Scope: components to be removed during refueling JM Containment and internals JN Residual heat removal systems for reactor coolant system JR Reactor protection system Task: to detect and identify accident conditions and to actuate protective actions to contain and control accidents JS Reactor control system Task: to control reactor state variables in normal operation JT Reactor operational, protective and status limitation system JV Lubricant supply system JW Sealing fluid supply system JX Fluid supply system for control and protection equipment JY Control and protection equipment (other than *JR*, *JS*, *JT*) Printout date 14. Mrz. 01 Page J1 of J1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : JA 04.04.97 J Nuclear heat generation JA Reactor system JAA Reactor pressure vessel Scope: reactor pressure vessel including nozzles and parts welded directly to the vessel JAB Reactor pressure vessel closure head (use only if *JAA* is not sufficient for identification) Scope: includes flanges, seals and bolts; for rotating plugs incl. drives JAC Reactor pressure vessel internals (code reactor vessel internals under *JB* if *JAC* not sufficient for identification) JAD Reactor vessel liner Limit: liner anchor; for liners with attachment-welded piping: to excl. liner cooling system JAE Liner cooling system Limit: connection to liner cooling system or header thereof; otherwise incl. piping Task: to remove heat from the liner JAF Reactor vessel prestressing equipment Task: to maintain and monitor tension of prestressing cables of reactor pressure vessel JAG Reactor internal insulation Limit: associated fasterners, incl. closure head insulation JAH Reactor external insulation Limit: associated fasterners, incl. closure head insulation JAJ Reactor vessel cooling system (only if separate from liner cooling system) Task: to remove heat from reactor vessel wall JAT Leak-off system and leakage detection system JAV Lubricant supply system JAW Sealing fluid supply system JAX Fluid supply system for control and protection equipment JAY Control and protection equipment Printout date 14. Mrz. 01 Page JA1 of JA1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : JB 04.04.97 J Nuclear heat generation JB Reactor vessel internals (use *JB* only if *JAC *is not sufficient for identification) JBA Reactor vessel internals JBB Reactor vessel internals JBC Reactor vessel internals JBD Reactor vessel internals JBE Reactor vessel internals JBF Reactor vessel internals JBG Reactor vessel internals JBH Reactor vessel internals JBJ Reactor vessel internals JBK Reactor vessel internals JBL Reactor vessel internals JBM Reactor vessel internals JBN Reactor vessel internals JBP Reactor vessel internals JBQ Reactor vessel internals JBR Reactor vessel internals JBS Reactor vessel internals JBT Reactor vessel internals JBU Reactor vessel internals Printout date 14. Mrz. 01 Page JB1 of JB1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : JD 04.04.97 J Nuclear heat generation JD Reactor control and shutdown equipment JDA Control rod drive mechanism (control drive) Limit: coupling to control assembly; connectors to power supply Task: to move control assemblies Scope: components that have to be removed when the reactor vessel is opened up. Guide components welded onto the reactor vessel to be identified under *JAC*. JDC Mechanical control equipment for coolant flow rate Task: to control coolant flow rate during operation JDE Solid neutron absorber shutdown system Task: to render and maintain the reactor core subcritical JDH Liquid neutron absorber shutdown system (extra borating system) Task: to render and maintain the reactor core subcritical JDJ 2nd backup liquid neutron absorber shutdown system (boron shutdown system) Task: to render and maintain the reactor core subcritical during specific transients JDK Emergency shutdown system Task: to render and maintain the reactor core subcritical in case of emergencies JDM Gaseous neutron absorber shutdown system Task: to render and maintain the reactor core subcritical JDP Power supply for shutdown system JDT Leak-off collecting system JDV Lubricant supply system JDW Sealing fluid supply system JDX Fluid supply system for control and protection equipment JDY Control and protection equipment Printout date 14. Mrz. 01 Page JD1 of JD1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : JE 04.04.97 J Nuclear heat generation JE Reactor coolant system JEA Reactor coolant heat exchanger (in dual-cycle plants: steam generation system) Limit: on primary and secondary sides from incl. inlet heat exchanger to incl. outlet JEB Reactor coolant circulation pump system Limit: from incl. suction nozzle to incl. discharge nozzle If circulation pumps inside the reactor vessel: to excl. connection flange on reactor vessel JEC Reactor coolant piping system (not at direct-cycle plants) Limit: from excl. reactor coolant heat exchanger to excl. reactor coolant pumps from excl. reactor coolant pump outlet to excl. reactor pressure vessel from excl. reactor pressure vessel to excl. reactor coolant heat exchanger JEF Reactor coolant pressurizing system Limit: In dual-cycle plants: from excl. reactor coolant piping system to incl. relief and safety valves JEG Reactor coolant pressure relief system (at direct-cycle plants see *LBK*) Limit: In dual-cycle plants: from excl. relief and safety valves to incl. relief tank and the associated recirculation cooling equipment In direct-cycle plants: from excl. reactor pressure vessel to excl. pressure suppression system Task: to relieve impermissble pressures in the reactor coolant system JET Reactor coolant leak-off system JEV Lubricant supply system JEW Sealing fluid supply system JEX Fluid supply system for control and protection equipment JEY Control and protection equipment Printout date 14. Mrz. 01 Page JE1 of JE1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : JF 04.04.97 J Nuclear heat generation JF Moderator system JFA Moderator heat exchanger Limit: on primary and secondary sides from incl. inlet to incl. outlet JFB Moderator circulation system Limit: from incl. inlet nozzle to incl. outlet nozzle JFC Moderator piping system Limit: from excl. moderator heat exchanger to excl. moderator circulating system from excl. moderator circulating system to excl. moderator tank from incl. reactor pressure vessel to excl. moderator heat exchanger JFD Moderator tank Task: to surround the reactor core with moderator. If enclosed in the reactor pressure vessel: identification under reactor pressure vessel internals. JFF Moderator pressurizing system Limit: from excl. moderator piping system to incl. relief and safety valves JFG Moderator pressure relief system Limit: from excl. relief and safety valves to incl. recirculation cooling system Task: to relieve impermissible pressures in the moderator system JFT Moderator leak-off system JFV Lubricant supply system JFW Sealing fluid supply system JFX Fluid supply system for control and protection equipment JFY Control and protection equipment Printout date 14. Mrz. 01 Page JF1 of JF1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : JG 04.04.97 J Nuclear heat generation JG Secondary coolant system (applicable only to three-cycle plants) JGA Secondary coolant heat exchanger (steam generation system) Limit: on primary and secondary sides from incl. inlet to incl. outlet JGB Secondary coolant circulation system Limit: from incl. inlet nozzle to incl. outlet nozzle JGC Secondary coolant piping system Limit: excl. circulation system and heat exchangers JGF Secondary coolant pressurizing system Limit: from excl. secondary coolant piping system to incl. relief and safety valves JGG Secondary coolant pressure relief system Limit: from excl. safety valve to incl. transfer point Task: to relief impermissible pressures in the secondary coolant system JGT Secondary coolant leak-off system JGV Lubricant supply system JGW Sealing fluid supply system JGX Fluid supply system for control and protection equipment JGY Control and protection equipment Printout date 14. Mrz. 01 Page JG1 of JG1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : JK 04.04.97 J Nuclear heat generation JK Reactor core with appurtenances Task: energy conversion Scope: components to be removed during refueling JKA Reactor core JKB Reactor core JKC Reactor core JKD Reactor core JKE Reactor core JKF Reactor core JKG Reactor core JKH Reactor core JKJ Reactor core JKK Reactor core JKL Reactor core JKM Reactor core JKN Reactor core JKP Reactor core JKQ Aeroball system Task: to measure the flux distribution in the core by means of mobile, activatable probes JKS In-core instrumentation system Task: to measure temperature and neutron flux in the core JKT Ex-core instrumentation system Task: to measure temperature and neutron flux outside the core JKU Failed fuel assemblies detection system Task: to detect leaks in fuel assemblies cladding tubes Printout date 14. Mrz. 01 Page JK1 of JK1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : JM 04.04.97 J Nuclear heat generation JM Containment and internals JMA Containment Task: to retain activity released from the reactor coolant system JMC Annulus leak-off system Task: controlled removal of leakages from the containment JME Equipment airlock Limit: weld between airlock enclosure and containment Task: passage from compartments within the containment to the exterior whilst maintaining the various operating conditions JMF Personnel airlock (motor-operated) Limit: weld between airlock enclosure and containment Task: passage from compartments within the containment to the exterior whilst maintaining the various operating conditions JMG Emergency airlock (hand-operated) Limit: weld between airlock enclosure and containment Task: passage from compartments within the containment to the exterior whilst maintaining the various operating conditions JMH Construction opening Limit: weld between construction opening and containment Task: passage from compartments within the containment to the exterior JMJ Structural components inside containment (for point of installation coding only) JMK Piping penetration (for point of installation coding only) JML Cable penetration (for point of installation coding only) JMM Leakage monitoring and leak-off system Task: detection and controlled removal of leakages through penetrations and other points JMN Containment spray system Limit: from incl. storage tank to incl. nozzle outlet Task: to reduce pressure in containment JMP Pressure suppression system Task: to limit pressure build-up in containment by condensation Scope: suppression chamber incl. steam vent pipes, excl. parts in common with the containment JMT Hydrogen reduction system (if separate from *JMU*) Task: to reduce hydrogen concentration inside containment JMU Hydrogen monitoring system (also reduction and mixing if only one system) Task: to measure hydrogen concentration in the containment atmosphere JMV Lubricant supply system JMW Sealing fluid supply system JMX Fluid supply system for control and protection equipment JMY Control and protection equipment Printout date 14. Mrz. 01 Page JM1 of JM2 Siemens 2 nd complete, non-project related edition Condition-Date: JMZ KKS Identification System for Power Plants Function key : JM 04.04.97 Hydrogen mixing system (if separate from *JMU*) Task: to mix containment atmosphere Printout date 14. Mrz. 01 Page JM2 of JM2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : JN 04.04.97 J Nuclear heat generation JN Residual heat removal systems for reactor coolant system JNA Residual heat removal system Task: to remove residual heat from shutdown reactor core JNB Emergency residual heat removal system Task: to remove residual heat from shutdown reactor core in case of emergencies JND HP safety injection system (if separate from *JNA*) Limit: connection to reactor coolant system Task: to compensate small and medium size loss of coolant JNG LP safety injection system (if separate from *JNA*), core flooding system Limit: connection to reactor coolant system Task: to flood the reactor core in the event of large loss of coolant JNK Borated water storage system Task: to provide borated water for residual heat removal purposes JNP Function testing system Task: function testing of residual heat removal system during operation JNV Lubricant supply system JNW Sealing fluid supply system JNX Fluid supply system for control and protection equipment JNY Control and protection equipment Printout date 14. Mrz. 01 Page JN1 of JN1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : JR 04.04.97 J Nuclear heat generation JR Reactor protection system Task: to detect and identify accident conditions and to actuate protective actions to contain and control accidents JRA Reactor protection system JRB Reactor protection system JRC Reactor protection system JRD Reactor protection system JRE Reactor protection system JRF Reactor protection system JRG Reactor protection system JRH Reactor protection system JRJ Reactor protection system JRK Reactor protection system JRL Reactor protection system JRM Reactor protection system JRN Reactor protection system JRP Reactor protection system JRQ Reactor protection system JRR Reactor protection system JRS Reactor protection system JRT Reactor protection system JRU Reactor protection system Printout date 14. Mrz. 01 Page JR1 of JR1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : JS 04.04.97 J Nuclear heat generation JS Reactor control system Task: to control reactor state variables in normal operation JSA Reactor control system JSB Reactor control system JSC Reactor control system JSD Reactor control system JSE Reactor control system JSF Reactor control system JSG Reactor control system JSH Reactor control system JSJ Reactor control system JSK Reactor control system JSL Reactor control system JSM Reactor control system JSN Reactor control system JSP Reactor control system JSQ Reactor control system JSR Reactor control system JSS Reactor control system JST Reactor control system JSU Reactor control system Printout date 14. Mrz. 01 Page JS1 of JS1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : JT 04.04.97 J Nuclear heat generation JT Reactor operational, protective and status limitation system JTA Reactor operational, protective and status limitation system JTB Reactor operational, protective and status limitation system JTC Reactor operational, protective and status limitation system JTD Reactor operational, protective and status limitation system JTE Reactor operational, protective and status limitation system JTF Reactor operational, protective and status limitation system JTG Reactor operational, protective and status limitation system JTH Reactor operational, protective and status limitation system JTJ Reactor operational, protective and status limitation system JTK Reactor operational, protective and status limitation system JTL Reactor operational, protective and status limitation system JTM Reactor operational, protective and status limitation system JTN Reactor operational, protective and status limitation system JTP Reactor operational, protective and status limitation system JTQ Reactor operational, protective and status limitation system JTR Reactor operational, protective and status limitation system JTS Reactor operational, protective and status limitation system JTT Reactor operational, protective and status limitation system JTU Reactor operational, protective and status limitation system Printout date 14. Mrz. 01 Page JT1 of JT1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : JV 04.04.97 J Nuclear heat generation JV Lubricant supply system JVA Lubricant supply system JVB Lubricant supply system JVC Lubricant supply system JVD Lubricant supply system JVE Lubricant supply system JVF Lubricant supply system JVG Lubricant supply system JVH Lubricant supply system JVJ Lubricant supply system JVK Lubricant supply system JVL Lubricant supply system JVM Lubricant supply system JVN Lubricant supply system JVP Lubricant supply system JVQ Lubricant supply system JVR Lubricant supply system JVS Lubricant supply system JVT Lubricant supply system JVU Lubricant supply system Printout date 14. Mrz. 01 Page JV1 of JV1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : JW 04.04.97 J Nuclear heat generation JW Sealing fluid supply system JWA Sealing fluid supply system JWB Sealing fluid supply system JWC Sealing fluid supply system JWD Sealing fluid supply system JWE Sealing fluid supply system JWF Sealing fluid supply system JWG Sealing fluid supply system JWH Sealing fluid supply system JWJ Sealing fluid supply system JWK Sealing fluid supply system JWL Sealing fluid supply system JWM Sealing fluid supply system JWN Sealing fluid supply system JWP Sealing fluid supply system JWQ Sealing fluid supply system JWR Sealing fluid supply system JWS Sealing fluid supply system JWT Sealing fluid supply system JWU Sealing fluid supply system Printout date 14. Mrz. 01 Page JW1 of JW1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : JX 04.04.97 J Nuclear heat generation JX Fluid supply system for control and protection equipment JXA Fluid supply system for control and protection equipment JXB Fluid supply system for control and protection equipment JXC Fluid supply system for control and protection equipment JXD Fluid supply system for control and protection equipment JXE Fluid supply system for control and protection equipment JXF Fluid supply system for control and protection equipment JXG Fluid supply system for control and protection equipment JXH Fluid supply system for control and protection equipment JXJ Fluid supply system for control and protection equipment JXK Fluid supply system for control and protection equipment JXL Fluid supply system for control and protection equipment JXM Fluid supply system for control and protection equipment JXN Fluid supply system for control and protection equipment JXP Fluid supply system for control and protection equipment JXQ Fluid supply system for control and protection equipment JXR Fluid supply system for control and protection equipment JXS Fluid supply system for control and protection equipment JXT Fluid supply system for control and protection equipment JXU Fluid supply system for control and protection equipment Printout date 14. Mrz. 01 Page JX1 of JX1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : JY 04.04.97 J Nuclear heat generation JY Control and protection equipment (other than *JR*, *JS*, *JT*) JYF Loose parts monitoring system Task: to detect loose and circulating parts by measurement of structure-borne noise JYG Vibration monitoring system Task: to measure and monitor operational vibrations JYH Leakage monitoring system JYK Radioactivity monitoring system JYL Fatigue monitoring system for components as separate system Task: to record and process operational data for the purpose of fatigue monitoring Printout date 14. Mrz. 01 Page JY1 of JY1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : K 04.04.97 K Reactor auxiliary systems KA Component cooling systems KB Coolant treatment KH Nuclear heat tracing systems (not electric) Task: external heating to keep systems at operating temperature KJ Nuclear refrigerant systems KL Heating, ventilation, air-conditioning (HVAC) system in controlled areas and exclusion areas KP Radioactive waste processing KR Nuclear gas supply and disposal (see *SE* for welding blanket gas systems) KT Nuclear collecting and disposal systems (also venting systems) Limit: from incl. cheader to excl. radioactive waste processing or coolant treatment systems Task: controlled collection and disposal of fluids KU Nuclear sampling systems Task: to extract and supply samples of fluids for measurement purposes KV Lubricant supply system KW Nuclear sealing and flushing fluid supply system Limit: from incl. storage tank to excl. fed system Task: to supply fluids for sealing and flushing KX Fluid supply system for control and protection equipment KY Control and protection equipment Printout date 14. Mrz. 01 Page K1 of K1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : KA 04.04.97 K Reactor auxiliary systems KA Component cooling systems KAA Component cooling system for safety-related cooling loads Limit: from excl. heat exchanger and to excl. heat exchanger in system to be cooled Task: to absorb and remove waste heat in a separate cooling circuit, to prevent transfer of radioactivity to other cooling circuits KAB Component cooling system for process-related cooling loads Limit: from excl. heat exchanger and to excl. heat exchanger in system to be cooled Task: to absorb and remove waste heat in a separate cooling circuit, to prevent transfer of radioactivity to other cooling circuits KAC Component cooling system for fuel pool cooler Limit: from excl. heat exchanger and to excl. heat exchanger in system to be cooled Task: to absorb and remove waste heat in a separate cooling circuit, to prevent transfer of radioactivity to other cooling circuits KAD Emergency component cooling system Limit: from excl. heat exchanger and to excl. heat exchanger in system to be cooled Task: to absorb and remove waste heat in case of emergencies in a separate cooling circuit, to prevent transfer of radioactivity to other cooling circuits KAV Lubricant supply system KAW Sealing fluid supply system KAX Fluid supply system for control and protection equipment KAY Control and protection equipment Printout date 14. Mrz. 01 Page KA1 of KA1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : KB 04.04.97 K Reactor auxiliary systems KB Coolant treatment KBA Level and volume control system Task: In reactor with set liquid level: to maintain liquid level. In reactor without set liquid level: to compensate volume. KBB Coolant supply system Limit: from incl. storage tank to excl. fed system Task: to store and inject process-grade coolant KBC Boric acid and demineralized water control system Limit: from incl. demineralized water tank and from incl. boric acid storage tank to excl. connection to fed system KBD Chemical control system Limit: from incl. chemical mixing tank to excl. fed system Task: to condition coolant KBE Coolant purification system Task: to limit coolant impurities in the coolant system KBF Coolant treatment system (also evaporation) KBG Coolant degasification, drying system KBH Coolant purification regenerating system KBJ Tritium extraction system KBK Secondary coolant purification system (applicable only to three-cycle plants) KBL D2O/H2O purification system KBM D2O upgrading and distribution system KBV Lubricant supply system KBW Sealing fluid supply system KBX Fluid supply system for control and protection equipment KBY Control and protection equipment Printout date 14. Mrz. 01 Page KB1 of KB1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : KH 04.04.97 K Reactor auxiliary systems KH Nuclear heat tracing systems (not electric) Task: external heating to keep systems at operating temperature KHA Heat tracing system for reactor coolant system KHB Heat tracing system for secondary coolant system KHC Heat tracing system for other systems KHW Sealing fluid supply system KHX Fluid supply system for control and protection equipment KHY Control and protection equipment Printout date 14. Mrz. 01 Page KH1 of KH1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : KJ 04.04.97 K Reactor auxiliary systems KJ Nuclear refrigerant systems KJA Low temperature system for coolant treatment Task: to supply refrigerants below 0 °C for coolant treatment KJB Low temperature system for gaseous radioactive waste processing Task: to supply refrigerants below 0 °C for gaseous radioactive waste processing KJL Chilled water system for coolant treatment Task: to supply water at about 0 °C for coolant treatment KJM Chilled water system for gaseous radioactive waste processing Task: to supply water at about 0 °C for gaseous radioactive waste processing KJN Chilled water system for back-up coolers Task: to supply water at a lower temperature than that in the component cooling system KJP Chilled water system for back-up coolers KJQ Chilled water system for back-up coolers KJW Sealing fluid supply system KJX Fluid supply system for control and protection equipment KJY Control and protection equipment Printout date 14. Mrz. 01 Page KJ1 of KJ1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : KL 04.04.97 K Reactor auxiliary systems KL Heating, ventilation, air-conditioning (HVAC) system in controlled areas and exclusion areas KLA Heating, ventilation, air-conditioning systems KLB Heating, ventilation, air-conditioning systems KLC Heating, ventilation, air-conditioning systems KLD Heating, ventilation, air-conditioning systems KLE Heating, ventilation, air-conditioning systems KLF Heating, ventilation, air-conditioning systems KLG Heating, ventilation, air-conditioning systems KLH Heating, ventilation, air-conditioning systems KLJ Heating, ventilation, air-conditioning systems KLK Heating, ventilation, air-conditioning systems KLL Heating, ventilation, air-conditioning systems KLM Heating, ventilation, air-conditioning systems KLN Heating, ventilation, air-conditioning systems KLP Heating, ventilation, air-conditioning systems KLQ Heating, ventilation, air-conditioning systems KLR Heating, ventilation, air-conditioning systems KLS Heating, ventilation, air-conditioning systems KLT Heating, ventilation, air-conditioning systems KLU Heating, ventilation, air-conditioning systems KLV Lubricant supply system KLW Sealing fluid supply system KLX Fluid supply system for control and protection equipment KLY Control and protection equipment Printout date 14. Mrz. 01 Page KL1 of KL1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : KP 04.04.97 K Reactor auxiliary systems KP Radioactive waste processing KPA Solid radioactive waste processing system KPB Solid radioactive waste processing system KPC Solid radioactive waste processing system KPD Solid radioactive waste processing system KPE Solid radioactive waste storage system KPF Liquid radioactive waste processing system KPG Liquid radioactive waste processing system KPH Liquid radioactive waste processing system KPJ Liquid radioactive waste processing system KPK Liquid radioactive waste storage system KPL Gaseous radioactive waste processing system KPM Gaseous radioactive waste processing system KPN Gaseous radioactive waste processing system KPP Gaseous radioactive waste processing system KPQ Gaseous radioactive waste storage system KPV Lubricant supply system KPW Sealing fluid supply system KPX Fluid supply system for control and protection equipment KPY Control and protection equipment Printout date 14. Mrz. 01 Page KP1 of KP1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : KR 04.04.97 K Reactor auxiliary systems KR Nuclear gas supply and disposal (see *SE* for welding blanket gas systems) KRA Blanket gas supply KRB Blanket gas supply KRC Blanket gas supply KRJ Inert gas supply KRK Inert gas supply KRL Inert gas supply KRP Gas supply KRQ Gas supply KRR Gas supply KRV Lubricant supply system KRW Sealing fluid supply system KRX Fluid supply system for control and protection equipment KRY Control and protection equipment Printout date 14. Mrz. 01 Page KR1 of KR1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : KT 04.04.97 K Reactor auxiliary systems KT Nuclear collecting and disposal systems (also venting systems) Limit: from incl. cheader to excl. radioactive waste processing or coolant treatment systems Task: controlled collection and disposal of fluids KTA Collecting systems for disposal (drained and vented fluids) KTB Collecting systems for disposal (drained and vented fluids) KTC Collecting systems for disposal (drained and vented fluids) KTD Collecting systems for disposal (drained and vented fluids) KTE Collecting systems for disposal (drained and vented fluids) KTF Collecting systems for disposal (drained and vented fluids) KTG Collecting systems for disposal (drained and vented fluids) KTH Collecting systems for disposal (drained and vented fluids) KTJ Collecting systems for disposal (drained and vented fluids) KTK Collecting systems for disposal (drained and vented fluids) KTL Collecting systems for disposal (drained and vented fluids) KTM Collecting systems for disposal (drained and vented fluids) KTN Collecting systems for disposal (drained and vented fluids) KTP Collecting systems for disposal (drained and vented fluids) KTQ Collecting systems for disposal (drained and vented fluids) KTR Collecting systems for disposal (drained and vented fluids) KTS Collecting systems for disposal (drained and vented fluids) KTT Collecting systems for disposal (drained and vented fluids) KTU Collecting systems for disposal (drained and vented fluids) KTX Fluid supply system for control and protection equipment KTY Control and protection equipment Printout date 14. Mrz. 01 Page KT1 of KT1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : KU 04.04.97 K Reactor auxiliary systems KU Nuclear sampling systems Task: to extract and supply samples of fluids for measurement purposes KUA Sampling system (liquid) KUB Sampling system (liquid) KUC Sampling system (liquid) KUD Sampling system (liquid) KUE Sampling system (liquid) KUF Sampling system (gaseous) KUG Sampling system (gaseous) KUH Sampling system (gaseous) KUJ Sampling system (gaseous) KUK Sampling system (gaseous) KUL Fault sampling system Task: to extract samples after reactor fault out of the reactor containment KUM Fault sampling system Task: to extract samples after reactor fault out of the reactor containment KUN Fault sampling system Task: to extract samples after reactor fault out of the reactor containment KUX Fluid supply system for control and protection equipment KUY Control and protection equipment Printout date 14. Mrz. 01 Page KU1 of KU1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : KV 04.04.97 K Reactor auxiliary systems KV Lubricant supply system KVA Lubricant supply system KVB Lubricant supply system KVC Lubricant supply system KVD Lubricant supply system KVE Lubricant supply system KVF Lubricant supply system KVG Lubricant supply system KVH Lubricant supply system KVJ Lubricant supply system KVK Lubricant supply system KVL Lubricant supply system KVM Lubricant supply system KVN Lubricant supply system KVP Lubricant supply system KVQ Lubricant supply system KVR Lubricant supply system KVS Lubricant supply system KVT Lubricant supply system KVU Lubricant supply system Printout date 14. Mrz. 01 Page KV1 of KV1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : KW 04.04.97 K Reactor auxiliary systems KW Nuclear sealing and flushing fluid supply system Limit: from incl. storage tank to excl. fed system Task: to supply fluids for sealing and flushing KWA Nuclear sealing and flushing fluid supply system KWB Nuclear sealing and flushing fluid supply system KWC Nuclear sealing and flushing fluid supply system KWD Nuclear sealing and flushing fluid supply system KWE Nuclear sealing and flushing fluid supply system KWF Nuclear sealing and flushing fluid supply system KWG Nuclear sealing and flushing fluid supply system KWH Nuclear sealing and flushing fluid supply system KWJ Nuclear sealing and flushing fluid supply system KWK Nuclear sealing and flushing fluid supply system KWL Nuclear sealing and flushing fluid supply system KWM Nuclear sealing and flushing fluid supply system KWN Nuclear sealing and flushing fluid supply system KWP Nuclear sealing and flushing fluid supply system KWQ Nuclear sealing and flushing fluid supply system KWR Nuclear sealing and flushing fluid supply system KWS Nuclear sealing and flushing fluid supply system KWT Nuclear sealing and flushing fluid supply system KWU Nuclear sealing and flushing fluid supply system KWX Fluid supply system for control and protection equipment KWY Control and protection equipment Printout date 14. Mrz. 01 Page KW1 of KW1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : KX 04.04.97 K Reactor auxiliary systems KX Fluid supply system for control and protection equipment KXA Fluid supply system for control and protection equipment KXB Fluid supply system for control and protection equipment KXC Fluid supply system for control and protection equipment KXD Fluid supply system for control and protection equipment KXE Fluid supply system for control and protection equipment KXF Fluid supply system for control and protection equipment KXG Fluid supply system for control and protection equipment KXH Fluid supply system for control and protection equipment KXJ Fluid supply system for control and protection equipment KXK Fluid supply system for control and protection equipment KXL Fluid supply system for control and protection equipment KXM Fluid supply system for control and protection equipment KXN Fluid supply system for control and protection equipment KXP Fluid supply system for control and protection equipment KXQ Fluid supply system for control and protection equipment KXR Fluid supply system for control and protection equipment KXS Fluid supply system for control and protection equipment KXT Fluid supply system for control and protection equipment KXU Fluid supply system for control and protection equipment Printout date 14. Mrz. 01 Page KX1 of KX1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : KY 04.04.97 K Reactor auxiliary systems KY Control and protection equipment KYA Control and protection equipment KYB Control and protection equipment KYC Control and protection equipment KYD Control and protection equipment KYE Control and protection equipment KYF Control and protection equipment KYG Control and protection equipment KYH Control and protection equipment KYJ Control and protection equipment KYK Control and protection equipment KYL Control and protection equipment KYM Control and protection equipment KYN Control and protection equipment KYP Control and protection equipment KYQ Control and protection equipment KYR Control and protection equipment KYS Control and protection equipment KYT Control and protection equipment KYU Control and protection equipment Printout date 14. Mrz. 01 Page KY1 of KY1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : L 04.04.97 L Steam, water, gas cycles LA Feedwater system LB Steam system LC Condensate system LD Condensate polishing plant LF Common installations for steam, water, gas cycles LK Gas system (closed cycle) LL Gas cleaning system (only for closed cycle) LN Water impounding works for hydroelectric power plant LP Intake system, upperwater system for hydroelectric power plant LQ Tail-race system, underwater system for hydroelectric power plant LS Common installations for hydroelectric power plant LV Lubricant supply system LW Sealing fluid supply system for steam, water, gas cycles LX Fluid supply system for control and protection equipment LY Control and protection equipment Printout date 14. Mrz. 01 Page L1 of L1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : LA 04.04.97 L Steam, water, gas cycles LA Feedwater system LAA Storage, deaeration (incl. feedwater tank) Limit: from incl. deaerator or tank inlet to incl. tank outlet incl. warm-up equipment and vapour condenser LAB Feedwater piping system (excl. feedwater pump and feedwater heating system) Limit: from excl. feedwater tank outlet to excl. boiler inlet header or heat exchanger LAC Feedwater pump system Limit: from incl. pump system suction nozzle to incl. pump system discharge nozzle LAD HP feedwater heating system Limit: from incl. respective feed heater inlet to incl. respective feed heater outlet incl. desuperheater and cooler LAE HP desuperheating spray system Limit: from excl. branch off feedwater piping system to excl. user LAF IP desuperheating spray system Limit: from excl. pump system discharge nozzle or from excl. branch off other system to excl. user LAH Start-up and shutdown piping system Limit: from excl. outlet of or branch off feedwater system to excl. feedwater piping system or other system LAJ Start-up and shutdown pump system Limit: from incl. pump system suction nozzle to incl. pump system discharge nozzle LAR Emergency feedwater piping system incl. storage (excl. emergency feedwater pump system) Limit: from excl. branch off other system to excl. feedwater piping system inlet LAS Emergency feedwater pump system Limit: from incl. pump system suction nozzle to incl. pump system discharge nozzle LAT Back-up emergency feedwater system Limit: from excl. branch off other system to excl. feedwater piping system inlet LAV Lubricant supply system LAW Feedwater sealing water system LAX Fluid supply system for control and protection equipment LAY Control and protection equipment Printout date 14. Mrz. 01 Page LA1 of LA1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : LB 04.04.97 L Steam, water, gas cycles LB Steam system LBA Main steam piping system Limit: from excl. boiler outlet or from excl. heat exchanger to excl. turbine main stop valve or HP reducing station or turbine bypass or other user (system) LBB Hot reheat piping system Limit: from excl. reheater or moisture separator/reheater outlet to excl. intercept valve or turbine inlet or turbine bypass or other user (system) LBC Cold reheat piping system Limit: from excl. turbine outlet or high pressure reducing station to excl. reheater inlet excl. moisture separator or user (system) LBD Extraction piping system Limit: from excl. branch off crossover line to excl. user (system) LBE Back-pressure piping system Limit: from excl. turbine outlet to excl. user (system) LBF Overpressure suppression and safety device incl. injection and hydraulic station for safety function Limit: from excl. inlet to incl. outlet LBG Auxiliary steam piping system Limit: from excl. receiving point from other system to excl. user (system) LBH Start-up steam system, shutdown steam system Limit: from excl. boiler outlet or from excl. branch off main steam line, incl. start-up condenser or from excl. outlet of other system to excl. inlet to other systems LBJ Moisture separator/reheater (MSR) Limit: from incl. inlet to incl. outlet LBK Main steam safety/relief system inside reactor containment for single-cycle plants Limit: from excl. main steam piping system to excl. pressure suppression system Task: pressure limitation in main steam piping system *LBA* LBQ Extraction steam piping system for HP feedwater heating Limit: from excl. turbine outlet or branch off other system to excl. feedwater heating system or user (system) LBR Piping system for branch or auxiliary turbine Limit: from excl. branch off main turbine or from excl. branch off other system or from excl. branch or auxiliary turbine outlet to excl. branch or auxiliary turbine isolating valve or to excl. inlet to other system Printout date 14. Mrz. 01 Page LB1 of LB2 Siemens 2 nd complete, non-project related edition Condition-Date: LBS KKS Identification System for Power Plants Function key : LB 04.04.97 Extraction steam piping system for LP feedwater heating (main condensate) Limit: from excl. turbine outlet or branch off other system to excl. LP feedwater heating system ot deaerator or user (system) LBT Emergency condensing system Limit: from excl. steam generator outlet or from excl. branch off main steam piping system incl. condenser to excl. inlet to other system LBU Common dump line LBV Lubricant supply system LBW Sealing steam system LBX Fluid supply system for control and protection equipment LBY Control and protection equipment Printout date 14. Mrz. 01 Page LB2 of LB2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : LC 04.04.97 L Steam, water, gas cycles LC Condensate system LCA Main condensate piping system (excl. main condensate pump system, LP feedwater heating system, condensate polishing plant) Limit: from excl. condenser outlet to excl. deaerator inlet or to excl. feedwater pump system (in plants without feedwater tank) LCB Main condensate pump system Limit: from incl. pump system suction nozzle to incl. pump system discharge nozzle LCC Main condensate heating system Limit: from incl. heater inlet to incl. heater outlet incl.desuperheater and cooler LCE Condensate desuperheating spray system Limit: from excl. branch off main condensate piping system or from excl. branch off branch turbine condensate piping system to excl. user LCF Branch turbine condensate piping system Limit: from excl. condenser outlet to excl. inlet to other system, excl. branch turbine condensate pump system LCG Branch turbine condensate pump system Limit: from incl. pump system suction nozzle to incl. pump system discharge nozzle LCH HP heater drains system Limit: from excl. heater outlet to excl. inlet to other systems LCJ LP heater drains system Limit: from excl. heater outlet to excl. inlet to other systems LCL Steam generator drains system Limit: from excl. branch off pressure system or from incl. start-up flash tank to excl. inlet to other systems LCM Clean drains system (collecting and return system) Limit: from incl. collecting tank or from excl. final drain valve or from excl. inlet from other collecting system to excl. inlet to other systems LCN Auxiliary steam condensate system (collecting and return system) Limit: from excl. (steam) user to excl. inlet to other systems LCP Standby condensate system, incl. storage and pump system Limit: from excl. branch off other system to excl. inlet to other systems LCQ Steam generator blowdown system Limit: from excl. steam generator outlet from incl. blowdown flash tank (caustic flash tank) to excl. inlet to other systems Printout date 14. Mrz. 01 Page LC1 of LC2 Siemens 2 nd complete, non-project related edition Condition-Date: LCR KKS Identification System for Power Plants Function key : LC 04.04.97 Standby condensate distribution system Limit: from excl. branch off other system to excl. inlet to other systems LCS Reheater drains system (moisture separator/reheater) Limit: from excl. reheater to excl. inlet to other systems LCT Moisture separator drains system (moisture separator/reheater) Limit: from excl. moisture separator to excl. inlet to other systems LCV Lubricant supply system LCW Sealing and cooling drains system Limit: from excl. branch off other system to excl. user, incl. recirculation LCX Fluid supply system for control and protection equipment LCY Control and protection equipment Printout date 14. Mrz. 01 Page LC2 of LC2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : LD 04.04.97 L Steam, water, gas cycles LD Condensate polishing plant LDA Fluid treatment extraction system (if not part of another system) Limit: from excl. fluid treatment system outlet to excl. inlet into other system LDB Filtering, mechanical cleaning Limit: from incl. separation equipment inlet to incl. separation equipment outlet LDC Aeration, gas injection system Limit: from excl. atmosphere or from incl. gas supply LDD Electromagnetic polishing system Limit: from incl. electromagnetic polishing system inlet to incl. electromagnetic polishing system outlet LDE Acid proportioning system (e. g. for carbonate hardness removal) Limit: from incl. acid proportioning equipment or from excl. branch off chemicals supply system to excl. inlet to other system LDF Ion exchange, reverse osmosis system (e. g. demineralization) Limit: from incl. ion exchanger inlet to incl. ion exchanger outlet LDG Evaporation system (e. g. demineralization) Limit: from incl. feedwater inlet to incl. steam outlet and from incl. heating steam inlet to incl. condensate outlet LDH Deaeration, drying system Limit: from incl. deaerator or tank inlet to incl. tank outlet, incl. warm-up equipment of vapour condenser LDJ Preheating, cooling system Limit: from incl. preheater or cooler inlet to incl. preheater or cooler outlet LDK Piping system, temporary storage system, pump system for main fluid Limit: Piping system: from excl. intake or from excl. outlet of other system to excl. inlet to other system to incl. fluid treatment system outlet Temporary storage system: from incl. temporary storage system inlet to incl. temporary storage system outlet Pump system: from incl. pump system suction nozzle to incl. pump system discharge nozzle LDL Storage system outside fluid treatment system (if not part of another system) Limit: from incl. storage system inlet to incl. storage system outlet, incl. intake and outfall Printout date 14. Mrz. 01 Page LD1 of LD2 Siemens 2 nd complete, non-project related edition Condition-Date: LDN KKS Identification System for Power Plants Function key : LD 04.04.97 Chemicals supply system Limit: from incl. intake or from incl. storage tank to excl. discharge into other system LDP Regeneration, flushing equipment Limit: from incl. system inlet to excl. inlet to other system from excl. chemicals or auxiliary fluid supply system and flushing air supply system to incl. regeneration, flushing equipment LDQ Injection system for main fluid Limit: from incl. injection equipment or from excl. branch off chemicals supply system to excl. inlet to other system LDR Flushing water and residues removal system incl. neutralization Limit: from excl. outlet of respective system to excl. discharge into disposal system LDS Sludge thickening system Limit: from excl. outlet of respective system to excl. discharge into disposal system LDT Heating, cooling and flushing fluid distribution system Limit: from incl. heating, cooling, flushing fluid generation equipment or from excl. branch off heating, cooling, flushing fluid supply system to excl. user and from excl. user LDV Lubricant supply system LDX Fluid supply system for control and protection equipment LDY Control and protection equipment Printout date 14. Mrz. 01 Page LD2 of LD2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : LF 04.04.97 L Steam, water, gas cycles LF Common installations for steam, water, gas cycles LFC Common drain and vent systems LFG Secondary-side steam generator tubesheet lancing system Limit: from excl. primary coolant heat exchanger outlet to excl. primary coolant heat exchanger inlet LFJ Steam generator layup system LFN Proportioning system for feedwater, condensate system, incl. proportioning in boiler and turbine area Printout date 14. Mrz. 01 Page LF1 of LF1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : LK 04.04.97 L Steam, water, gas cycles LK Gas system (closed cycle) LKA Storage system Limit: from excl. receiving point from gas supply system to excl. piping system inlet LKB Piping system Limit: from excl. gas heater outlet to excl. gas heater inlet, excl. turbine, compressor, preheater, cooler LKC Compressor system (if separate from gas turbine) Limit: from incl. compressor inlet to incl. compressor outlet LKD Preheating system Limit: from incl. preheater inlet to incl. preheater outlet LKE Precooling system Limit: from incl. precooler inlet to incl. precooler outlet LKF Intercooling system Limit: from incl. intercooler inlet to incl. intercooler outlet LKG Pressurizing system Limit: from incl. pressurizing system inlet to excl. discharge into piping system LKV Lubricant supply system LKW Sealing fluid supply system LKX Fluid supply system for control and protection equipment LKY Control and protection equipment Printout date 14. Mrz. 01 Page LK1 of LK1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : LL 04.04.97 L Steam, water, gas cycles LL Gas cleaning system (only for closed cycle) LLA Gas cleaning system (only for closed cycle) LLB Gas cleaning system (only for closed cycle) LLC Gas cleaning system (only for closed cycle) LLD Gas cleaning system (only for closed cycle) LLE Gas cleaning system (only for closed cycle) LLF Gas cleaning system (only for closed cycle) LLG Gas cleaning system (only for closed cycle) LLH Gas cleaning system (only for closed cycle) LLJ Gas cleaning system (only for closed cycle) LLK Gas cleaning system (only for closed cycle) LLL Gas cleaning system (only for closed cycle) LLM Gas cleaning system (only for closed cycle) LLN Gas cleaning system (only for closed cycle) LLP Gas cleaning system (only for closed cycle) LLQ Gas cleaning system (only for closed cycle) LLR Gas cleaning system (only for closed cycle) LLS Gas cleaning system (only for closed cycle) LLT Gas cleaning system (only for closed cycle) LLU Gas cleaning system (only for closed cycle) LLW Sealing fluid supply system LLX Fluid supply system for control and protection equipment LLY Control and protection equipment Printout date 14. Mrz. 01 Page LL1 of LL1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : LN 04.04.97 L Steam, water, gas cycles LN Water impounding works for hydroelectric power plant LNA Head and tail race system, storage system Limit: from incl. water intake incl. transfer conduit and pump system to excl. dam (incl. measuring equipment) or to excl. headwater piping system or to excl. headrace system LNB Trash rack, trash/fish barrier Limit: to excl. LNC inlet to other system Dam, weir system Limit: Dam: from incl. foundation to incl. crest, incl. inspection and instrumentation equipment Weir system: from incl. inlet to incl. outlet to other system LND Spillway LNE Drainage system LNF Pump system Task: pumping of the water within the head and tail race system LNV Lubricant supply system LNW Sealing fluid supply system LNX Fluid supply system for control and protection equipment LNY Control and protection equipment Printout date 14. Mrz. 01 Page LN1 of LN1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : LP 04.04.97 L Steam, water, gas cycles LP Intake system, upperwater system for hydroelectric power plant LPA Rake and rake cleaning system Task: separate out and collect floating matter from headrace LPB Isolating equipment Limit: from incl. isolating equipment inlet to incl. outlet to other system LPC Piping and penstock system Limit: from incl. receiving point to incl. discharge into turbine system, incl. connecting piping for pump system LPE Surge tank LPV Lubricant supply system LPW Sealing fluid supply system LPX Fluid supply system for control and protection equipment LPY Control and protection equipment Printout date 14. Mrz. 01 Page LP1 of LP1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : LQ 04.04.97 L Steam, water, gas cycles LQ Tail-race system, underwater system for hydroelectric power plant LQA Underwater piping and culvert system Limit: from excl. main machine set *ME.*, *MF.*, *MG.* inlet to incl. outlet to other system LQB Surge tank LQC Isolating equipment Limit: from incl. isolating equipment inlet to incl. outlet to other system LQE Rake and rake cleaning system for pumped-storage operation Task: separate out and collect floating matter from tailrace LQV Lubricant supply system LQW Sealing fluid supply system LQX Fluid supply system for control and protection equipment LQY Control and protection equipment Printout date 14. Mrz. 01 Page LQ1 of LQ1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : LS 04.04.97 L Steam, water, gas cycles LS Common installations for hydroelectric power plant LSA Common installations for hydroelectric power plant LSB Common installations for hydroelectric power plant LSC Common installations for hydroelectric power plant LSD Common installations for hydroelectric power plant LSE Common installations for hydroelectric power plant LSF Common installations for hydroelectric power plant LSG Common installations for hydroelectric power plant LSH Common installations for hydroelectric power plant LSJ Common installations for hydroelectric power plant LSK Common installations for hydroelectric power plant LSL Drainage system LSM Common installations for hydroelectric power plant LSN Common installations for hydroelectric power plant LSP Common installations for hydroelectric power plant LSQ Common installations for hydroelectric power plant LSR Common installations for hydroelectric power plant LSS Common installations for hydroelectric power plant LST Common installations for hydroelectric power plant LSU Common installations for hydroelectric power plant Printout date 14. Mrz. 01 Page LS1 of LS1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : LV 04.04.97 L Steam, water, gas cycles LV Lubricant supply system LVA Lubricant supply system LVB Lubricant supply system LVC Lubricant supply system LVD Lubricant supply system LVE Lubricant supply system LVF Lubricant supply system LVG Lubricant supply system LVH Lubricant supply system LVJ Lubricant supply system LVK Lubricant supply system LVL Lubricant supply system LVM Lubricant supply system LVN Lubricant supply system LVP Lubricant supply system LVQ Lubricant supply system LVR Lubricant supply system LVS Lubricant supply system LVT Lubricant supply system LVU Lubricant supply system Printout date 14. Mrz. 01 Page LV1 of LV1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : LW 04.04.97 L Steam, water, gas cycles LW Sealing fluid supply system for steam, water, gas cycles LWA Sealing fluid supply system for steam, water, gas cycles LWB Sealing fluid supply system for steam, water, gas cycles LWC Sealing fluid supply system for steam, water, gas cycles LWD Sealing fluid supply system for steam, water, gas cycles LWE Sealing fluid supply system for steam, water, gas cycles LWF Sealing fluid supply system for steam, water, gas cycles LWG Sealing fluid supply system for steam, water, gas cycles LWH Sealing fluid supply system for steam, water, gas cycles LWJ Sealing fluid supply system for steam, water, gas cycles LWK Sealing fluid supply system for steam, water, gas cycles LWL Sealing fluid supply system for steam, water, gas cycles LWM Sealing fluid supply system for steam, water, gas cycles LWN Sealing fluid supply system for steam, water, gas cycles LWP Sealing fluid supply system for steam, water, gas cycles LWQ Sealing fluid supply system for steam, water, gas cycles LWR Sealing fluid supply system for steam, water, gas cycles LWS Sealing fluid supply system for steam, water, gas cycles LWT Sealing fluid supply system for steam, water, gas cycles LWU Sealing fluid supply system for steam, water, gas cycles Printout date 14. Mrz. 01 Page LW1 of LW1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : LX 04.04.97 L Steam, water, gas cycles LX Fluid supply system for control and protection equipment LXA Fluid supply system for control and protection equipment LXB Fluid supply system for control and protection equipment LXC Fluid supply system for control and protection equipment LXD Fluid supply system for control and protection equipment LXE Fluid supply system for control and protection equipment LXF Fluid supply system for control and protection equipment LXG Fluid supply system for control and protection equipment LXH Fluid supply system for control and protection equipment LXJ Fluid supply system for control and protection equipment LXK Fluid supply system for control and protection equipment LXL Fluid supply system for control and protection equipment LXM Fluid supply system for control and protection equipment LXN Fluid supply system for control and protection equipment LXP Fluid supply system for control and protection equipment LXQ Fluid supply system for control and protection equipment LXR Fluid supply system for control and protection equipment LXS Fluid supply system for control and protection equipment LXT Fluid supply system for control and protection equipment LXU Fluid supply system for control and protection equipment Printout date 14. Mrz. 01 Page LX1 of LX1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : LY 04.04.97 L Steam, water, gas cycles LY Control and protection equipment LYA Control and protection equipment LYB Control and protection equipment LYC Control and protection equipment LYD Control and protection equipment LYE Control and protection equipment LYF Control and protection equipment LYG Control and protection equipment LYH Control and protection equipment LYJ Control and protection equipment LYK Control and protection equipment LYL Control and protection equipment LYM Control and protection equipment LYN Control and protection equipment LYP Control and protection equipment LYQ Control and protection equipment LYR Control and protection equipment LYS Control and protection equipment LYT Control and protection equipment LYU Control and protection equipment Printout date 14. Mrz. 01 Page LY1 of LY1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : M 04.04.97 M Main machine sets MA Steam turbine plant MB Gas turbine plant MD Wind turbine plant ME Hydraulic turbine plant MF Pumping turbine plant in pumped-storage power plants MG Pumped-storage plant MJ Diesel engine plant MK Generator plant ML Electro-motive plant (incl. motor generator) MM Compressor plant MP Common installations for main machine sets MR Gas engine plant MV Lubricant supply system MW Sealing fluid supply system MX Fluid supply system for control and protection equipment MY Control and protection equipment Printout date 14. Mrz. 01 Page M1 of M1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : MA 04.04.97 M Main machine sets MA Steam turbine plant MAA HP turbine Limit: from incl. steam admission (main stop valve) or combined main stop and control valve to incl. automatic/non-automatic extraction and exhaust nozzles and to incl. the interfaces with other turbine-internal systems MAB IP turbine Limit: from incl. crossover line, incl. control element or from incl. intercept valve to incl. automatic/non-automatic extraction and exhaust nozzles and to incl. the interfaces with other turbine-internal systems MAC LP turbine Limit: from incl. crossover line, incl. control element or from incl. intercept valve or steam inlet nozzle (in reheat system without intercept valve) to incl. automatic/non-automatic extraction and exhaust nozzles and to incl. the interfaces with other turbine-internal systems MAD Bearings MAG Condensing system Limit: from incl. condenser neck or inlet nozzle to incl. condenser outlet nozzle, incl. connected flash tanks, incl. instrumentation equipment associated with condenser MAH Motive water system (if separate from *MAJ*) Limit: from excl. outlet of other system to excl. water-operated air ejector inlet MAJ Air removal system Limit: from excl. condenser outlet to excl. inlet atmosphere MAK Transmission gear between prime mover and driven machine, incl. turning gear MAL Drain and vent systems Limit: from incl. collector point or from incl. final drain to excl. discharge into other system MAM Leak-off steam system Limit: from excl. branch off seal leak-off to excl. discharge into other system MAN Turbine bypass station, incl. desuperheating spray system Limit: from incl. bypass valve and from incl. desuperheating spray valve to incl. steam inlet to condenser MAP LP turbine bypass Limit: from excl. bypass valve and from excl. branch off steam system to excl. condenser Printout date 14. Mrz. 01 Page MA1 of MA2 Siemens 2 nd complete, non-project related edition Condition-Date: MAQ KKS Identification System for Power Plants Function key : MA 04.04.97 Vent system (if separate from *MAL*) Limit: from incl. venting point to excl. discharge into other system MAV Lubricant supply system Limit: from incl. dedicated lubricant tank or common lubricant and control fluid tank or from excl. branch off lubricant supply system to excl. user and from excl. user MAW Sealing, heating and cooling steam system Limit: from excl. branch to excl. casing nozzle of seal steam user and leak-off to excl. condenser or to incl. gland steam condenser or to excl. heating/cooling steam user MAX Non-electric control and protection equipment, incl. fluid supply system MAY Electrical control and protection equipment Printout date 14. Mrz. 01 Page MA2 of MA2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : MB 04.04.97 M Main machine sets MB Gas turbine plant MBA Turbine, compressor rotor with common casing Limit: from incl. compressor inlet to incl. compressor outlet from incl. turbine inlet to incl. turbine outlet, incl. exhaust gas diffuser MBB Turbine casing and rotor Limit: from incl. turbine inlet to incl. turbine outlet, incl. exhaust gas diffuser MBC Compressor casing and rotor Limit: from incl. compressor inlet to incl. compressor outlet MBD Bearings MBE Coolant system for gas turbine plant a Limit: from excl. branch off coolant to excl. user MBH Cooling and sealing gas system Limit: from incl. extraction point to excl. user and from excl. user, incl. leak-off to incl. inlet to other system MBJ Start-up unit MBK Transmission gear between prime mover and driven machine, incl. turning gear, barring gear MBL Intake air, cold gas system (open cycle) Limit: from excl. atmosphere to excl. combustion chamber or to excl. compressor inlet or to incl. exhaust gas heat exchanger, excl. compressor MBM Combustion chamber (gas heating, combustion) Limit: from incl. cold gas, fuel inlet to incl. hot gas outlet MBN Fuel supply system (liquid) Limit: from excl. branch off main supply line or from incl. temporary (day) tank to excl. combustion chamber or to excl. motive gas generating unit, incl. fuel return system MBP Fuel supply system (gaseous) Limit: from excl. branch off main supply line to excl. combustion chamber or to excl. motive gas generating unit MBQ Ignition fuel supply system (if separate) Limit: from excl. branch off main supply line or from incl. storage tank to excl. combustion chamber or to excl. motive gas generating unit Printout date 14. Mrz. 01 Page MB1 of MB2 Siemens 2 nd complete, non-project related edition Condition-Date: MBR KKS Identification System for Power Plants Function key : MB 04.04.97 Exhaust gas system (open cycle) Limit: from excl. combustion chamber or from excl. exhaust gas diffuser to excl. discharge into atmosphere, excl. turbine or to excl. inlet to other system (e. g. combustion air system) MBS Storage system Limit: to excl. connection to main system and from excl. connection to main system MBT Motive gas generator unit, incl. combustion chamber Limit: from incl. air/fuel inlet to incl. motive gas outlet of motive gas generating unit MBU Additive system Limit: from incl. supply to incl. injection MBV Lubricant supply system Limit: from incl. dedicated lubricant tank or common lubricant and control fluid tank or from excl. branch off control fluid supply system to excl. user and from excl. user MBW Sealing oil supply system Limit: from incl. dedicated seal oil tank or from excl. seal oil pump suction line to excl. user and from excl. user MBX Non-electric control and protection equipment, incl. fluid supply system MBY Electrical control and protection equipment MBZ Lubricant and control fluid treatment system Printout date 14. Mrz. 01 Page MB2 of MB2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : MD 04.04.97 M Main machine sets MD Wind turbine plant MDA Rotor (incl. hub) MDB Blade pitch regulating system MDD Rotor bearings MDK Transmission gear (gearbox, propeller shaft, brake) MDL Yaw control system MDV Lubricant supply system MDX Non-electric control and protection equipment, incl. fluid supply system MDY Electrical control and protection equipment Printout date 14. Mrz. 01 Page MD1 of MD1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : ME 04.04.97 M Main machine sets ME Hydraulic turbine plant MEA Turbine (casing, shaft, runner, draft tube etc.) Limit: from excl. turbine inlet or from excl. isolating valve to incl. turbine outlet or to excl. isolating valve MEB Isolating valve Task: to isolate headwater from turbine *MEA* and/or to control headwater flow to turbine *MEA* MED Bearings MEG Stabilizing air system Limit: from incl. air compressor to incl. outlet to turbine MEK Transmission gear between prime mover and driven machine MEL Water depression air supply system Limit: from incl. air compressor to incl. outlet to turbine MES Shaft gland cooling water system MEV Lubricant supply system Limit: from incl. lubricant tank to excl. user and from excl. user MEW Sealing water supply system Limit: from incl. sealing water supply main isolating valve to excl. casing nozzle of sealing water user MEX Non-electric control and protection equipment, incl. fluid supply system MEY Electrical control and protection equipment Printout date 14. Mrz. 01 Page ME1 of ME1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : MF 04.04.97 M Main machine sets MF Pumping turbine plant in pumped-storage power plants MFA Pumping turbine, pump and turbine as integral unit a Limit: from excl. connection to pumping turbine or from excl. isolating valve to incl. connection to pumping turbine or to excl. isolating valve Task: An integral unit that at different times fulfils the task of a prime mover (turbine) resp. a driven machine (pump) MFB Isolating valve Task: to isolate water from pumping turbine *MFA* and/or to control water flow to pumping turbine *MFA* MFD Bearings MFG Stabilizing air system Limit: from incl. air compressor to incl. inlet to turbine MFK Transmission gear between motor generator set and pumping turbine a MFL Water depression air supply system a Limit: from incl. air compressor to incl. inlet to pumping turbine MFM Start-up unit MFS Shaft gland cooling water system MFV Lubricant supply system Limit: from incl. lubricant tank to excl. user and from excl. user MFW Sealing water supply system Limit: from incl. sealing water supply main isolating valve to excl. casing nozzle of sealing water user MFX Non-electric control and protection equipment, incl. fluid supply system MFY Electrical control and protection equipment Printout date 14. Mrz. 01 Page MF1 of MF1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : MG 04.04.97 M Main machine sets MG Pumped-storage plant MGA Storage pump (casing, shaft, runner etc.) Limit: from excl. storage pump inlet or from excl. isolating valve to incl. storage pump outlet or to excl. isolating valve MGB Isolating valve Task: to isolate water from storage pump *MGA* and/or to control water flow to storage pump *MGA* MGD Bearings MGK Transmission gear between motor generator set and storage pump MGL Water depression air supply system a Limit: from incl. air compressor to incl. inlet to storage pump MGM Start-up unit MGS Shaft gland cooling water system MGV Lubricant supply system Limit: from incl. lubricant tank to excl. user and from excl. user MGW Sealing water supply system Limit: from incl. sealing water supply main isolating valve to excl. casing nozzle of sealing water user MGX Non-electric control and protection equipment, incl. fluid supply system MGY Electrical control and protection equipment Printout date 14. Mrz. 01 Page MG1 of MG1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : MJ 04.04.97 M Main machine sets MJ Diesel engine plant MJA Engine Limit: from incl. fuel injection nozzle inlet or from incl. air intake nozzles or from incl. cooling water inlet nozzles to incl. exhaust nozzle outlet or to incl. cooling water nozzle outlet, incl. engine-internal systems MJB Turbocharger, blower Limit: from incl. turbocharger or blower inlet to incl. turbocharger or blower outlet MJG Liquid cooling system Limit: from excl. engine cooling water nozzle outlet or from incl. turbocharger air cooling system inlet to excl. engine cooling water nozzle inlet or to incl. turbocharger air cooler outlet MJH Air intercooling system Limit: from incl. intercooler inlet to incl. intercooler outlet to excl. outlet to other cooling systems MJK Transmission gear between prime mover and driven machine MJN Fuel systems Limit: from incl. temporary (day) tank or from excl. branch off piping system to excl. fuel injection nozzle inlet MJP Start-up unit (incl. flywheel) MJQ Air intake system Limit: from excl. atmosphere to excl. turbocharger or to excl. engine air intake nozzles MJR Exhaust gas system Limit: from excl. engine exhaust nozzle outlet to excl. discharge into atmosphere MJV Lubricant supply system Limit: from incl. dedicated lubricant tank or common lubricant and control fluid tank or from excl. branch off control fluid supply system to excl. user from excl. user MJW Sealing fluid supply system MJX Fluid supply system for control and protection equipment MJY Control and protection equipment Printout date 14. Mrz. 01 Page MJ1 of MJ1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : MK 04.04.97 M Main machine sets MK Generator plant MKA Generator, complete, incl. stator, rotor and all integral cooling equipment Limit: to incl. generator bushing MKB Generator exciter set, including set with electrical breaking system (use only if *MKC* is not sufficient for identification) MKC Generator exciter set, including set with electrical breaking system, complete (10 auxiliary excitation, 20 main excitation unit) MKD Bearings MKF Stator/rotor liquid cooling system, incl. coolant supply system Hint: for cooling oil see *MKU* Limit: from excl. stator/rotor outlet to excl. stator/rotor inlet Task: dissipate heat produced by stator/rotor to liquid coolant MKG Stator/rotor hydrogen (H2) cooling system, incl. coolant supply system a Hint: for nitrogen / carbon dioxyde cooling see *MKH* Limit: from excl. stator/rotor outlet to excl. stator/rotor inlet Task: dissipate heat produced by stator/rotor to hydrogen coolant MKH Stator/rotor nitrogen (N2) / carbon dioxyde (CO2) cooling system, incl. coolant supply system a Hint: for other gas cooling see *MKG* Limit: from excl. stator/rotor outlet to excl. stator/rotor inlet Task: dissipate heat produced by stator/rotor to nitrogen / carbon dioxyde coolant MKJ Stator/rotor air cooling system, incl. coolant supply system Hint: for other gas cooling see *MKG* and *MKH* Limit: from excl. stator/rotor outlet to excl. stator/rotor inlet Task: dissipate heat produced by stator/rotor to air coolant MKQ Exhaust gas system (if separate from *MKG* and *MKH*) MKU Stator/rotor cooling oil cooling system, incl. coolant supply system Hint: for other liquid cooling see *MKF* Limit: from excl. stator/rotor outlet to excl. stator/rotor inlet Task: dissipate heat produced by stator/rotor to cooling oil coolant MKV Lubricant supply system (if separate system for generator) MKW Sealing oil system, incl. supply and treatment Limit: from excl. branch off sealing oil supply system to excl. stator inlet and from excl. stator outlet to excl. inlet to other system or in closed systems from excl. stator outlet to excl. stator inlet MKX Fluid supply system for control and protection equipment Printout date 14. Mrz. 01 Page MK1 of MK2 Siemens 2 nd complete, non-project related edition Condition-Date: MKY KKS Identification System for Power Plants Function key : MK 04.04.97 Control and protection equipment Printout date 14. Mrz. 01 Page MK2 of MK2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : ML 04.04.97 M Main machine sets ML Electro-motive plant (incl. motor generator) MLA Motor frame, motor generator frame, incl. stator, rotor and all integral cooling equipment Limit: to incl. motor or generator bushing MLC Exciter set MLD Bearings MLF Stator/rotor liquid cooling system, incl. coolant supply system Hint: for cooling oil see *MLU* Limit: from excl. stator/rotor outlet to excl. stator/rotor inlet Task: dissipate heat produced by stator/rotor to coolant MLG Stator/rotor gas cooling system, incl. coolant supply system Hint: for nitrogen cooling see *MLH* Limit: from excl. stator/rotor outlet to excl. stator/rotor inlet Task: dissipate heat produced by stator/rotor to coolant MLH Stator/rotor nitrogen cooling system, incl. coolant supply system Hint: for other gas cooling see *MLG* Limit: from excl. stator/rotor outlet to excl. stator/rotor inlet Task: dissipate heat produced by stator/rotor to coolant MLQ Exhaust gas system (if separate from *MLG* and *MLH*) MLU Stator/rotor cooling oil cooling system, incl. coolant supply system Hint: for other liquid cooling see *MLF* Limit: from excl. stator/rotor outlet to excl. stator/rotor inlet Task: dissipate heat produced by stator/rotor to coolant MLV Lubricant supply system (if separate system for electro-motive units) MLW Sealing oil system, incl. supply and treatment Limit: from excl. branch off sealing oil supply system to excl. stator inlet or from excl. stator outlet to excl. inlet to other system or in closed systems from excl. stator outlet to excl. stator inlet MLX Fluid supply system for control and protection equipment MLY Control and protection equipment Printout date 14. Mrz. 01 Page ML1 of ML1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : MM 04.04.97 M Main machine sets MM Compressor plant MMA Compressor incl. internal systems Limit: from incl. air, cooling fluid inlet to incl. air, cooling fluid outlet MMC Air intake piping system Limit: from excl. atmosphere to excl. compressor inlet MMD Bearings MME Intercooling system MMF Aftercooling system MMG Final cooling system MMH Discharge piping system Limit: from excl. compressor outlet to excl. inlet to other system MMV Lubricant supply system MMW Sealing fluid supply system MMX Fluid supply system for control and protection equipment MMY Control and protection equipment Printout date 14. Mrz. 01 Page MM1 of MM1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : MP 04.04.97 M Main machine sets MP Common installations for main machine sets MPA Foundation MPB Sheating MPG Frame, support structure MPR Forced cooling system MPS Drying and layup system Printout date 14. Mrz. 01 Page MP1 of MP1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : MR 04.04.97 M Main machine sets MR Gas engine plant MRA Gas engine plant MRB Gas engine plant MRC Gas engine plant MRD Gas engine plant MRE Gas engine plant MRF Gas engine plant MRG Gas engine plant MRH Gas engine plant MRJ Gas engine plant MRK Gas engine plant MRL Gas engine plant MRM Gas engine plant MRN Gas engine plant MRP Gas engine plant MRQ Gas engine plant MRR Gas engine plant MRS Gas engine plant MRT Gas engine plant MRU Gas engine plant MRV Lubricant supply system MRW Sealing fluid supply system MRX Fluid supply system for control and protection equipment MRY Control and protection equipment Printout date 14. Mrz. 01 Page MR1 of MR1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : MV 04.04.97 M Main machine sets MV Lubricant supply system MVA Lubricant supply system MVB Lubricant supply system MVC Lubricant supply system MVD Lubricant supply system MVE Lubricant supply system MVF Lubricant supply system MVG Lubricant supply system MVH Lubricant supply system MVJ Lubricant supply system MVK Lubricant supply system MVL Lubricant supply system MVM Lubricant supply system MVN Lubricant supply system MVP Lubricant supply system MVQ Lubricant supply system MVR Lubricant supply system MVS Lubricant supply system MVT Lubricant supply system MVU Lubricant supply system Printout date 14. Mrz. 01 Page MV1 of MV1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : MW 04.04.97 M Main machine sets MW Sealing fluid supply system MWA Sealing fluid supply system MWB Sealing fluid supply system MWC Sealing fluid supply system MWD Sealing fluid supply system MWE Sealing fluid supply system MWF Sealing fluid supply system MWG Sealing fluid supply system MWH Sealing fluid supply system MWJ Sealing fluid supply system MWK Sealing fluid supply system MWL Sealing fluid supply system MWM Sealing fluid supply system MWN Sealing fluid supply system MWP Sealing fluid supply system MWQ Sealing fluid supply system MWR Sealing fluid supply system MWS Sealing fluid supply system MWT Sealing fluid supply system MWU Sealing fluid supply system Printout date 14. Mrz. 01 Page MW1 of MW1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : MX 04.04.97 M Main machine sets MX Fluid supply system for control and protection equipment MXA Fluid supply system for control and protection equipment MXB Fluid supply system for control and protection equipment MXC Fluid supply system for control and protection equipment MXD Fluid supply system for control and protection equipment MXE Fluid supply system for control and protection equipment MXF Fluid supply system for control and protection equipment MXG Fluid supply system for control and protection equipment MXH Fluid supply system for control and protection equipment MXJ Fluid supply system for control and protection equipment MXK Fluid supply system for control and protection equipment MXL Fluid supply system for control and protection equipment MXM Fluid supply system for control and protection equipment MXN Fluid supply system for control and protection equipment MXP Fluid supply system for control and protection equipment MXQ Fluid supply system for control and protection equipment MXR Fluid supply system for control and protection equipment MXS Fluid supply system for control and protection equipment MXT Fluid supply system for control and protection equipment MXU Fluid supply system for control and protection equipment Printout date 14. Mrz. 01 Page MX1 of MX1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : MY 04.04.97 M Main machine sets MY Control and protection equipment MYA Control and protection equipment MYB Control and protection equipment MYC Control and protection equipment MYD Control and protection equipment MYE Control and protection equipment MYF Control and protection equipment MYG Control and protection equipment MYH Control and protection equipment MYJ Control and protection equipment MYK Control and protection equipment MYL Control and protection equipment MYM Control and protection equipment MYN Control and protection equipment MYP Control and protection equipment MYQ Control and protection equipment MYR Control and protection equipment MYS Control and protection equipment MYT Control and protection equipment MYU Control and protection equipment Printout date 14. Mrz. 01 Page MY1 of MY1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : N 04.04.97 N Process energy supply for external users (e. g. district heating) NA Process steam system (incl. condensate return) ND Process hot water system NG Process air system NK Process gas system Printout date 14. Mrz. 01 Page N1 of N1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : NA 04.04.97 N Process energy supply for external users (e. g. district heating) NA Process steam system (incl. condensate return) NAA Piping system (steam) NAB Piping system (condensate) NAD Process heat transmission system Limit: from incl. heat exchanger inlet to incl. heat exchanger outlet NAE Piping system (steam) (only to be used if *NAA* is not sufficient for identification) NAF Piping system (steam) (only to be used if *NAA* is not sufficient for identification) NAG Piping system (steam) (only to be used if *NAA* is not sufficient for identification) NAH Piping system (steam) (only to be used if *NAA* is not sufficient for identification) NAJ Piping system (steam) (only to be used if *NAA* is not sufficient for identification) NAK Piping system (condensate) (only to be used if *NAB* is not sufficient for identification) NAL Piping system (condensate) (only to be used if *NAB* is not sufficient for identification) NAM Piping system (condensate) (only to be used if *NAB* is not sufficient for identification) NAX Fluid supply system for control and protection equipment NAY Control and protection equipment Printout date 14. Mrz. 01 Page NA1 of NA1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : ND 04.04.97 N Process energy supply for external users (e. g. district heating) ND Process hot water system NDA Piping system (forward) NDB Piping system (return) NDC Process hot water pump system NDD Process heat transfer Limit: from incl. heat exchanger inlet to incl. heat exchanger outlet NDE Hot water storage system Limit: from incl. tank inlet to incl. tank outlet NDF Distribution system NDG Distribution system NDH Distribution system NDJ Distribution system NDK Pressurizing system NDV Lubricant supply system NDX Fluid supply system for control and protection equipment NDY Control and protection equipment Printout date 14. Mrz. 01 Page ND1 of ND1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : NG 04.04.97 N Process energy supply for external users (e. g. district heating) NG Process air system NGB Piping system NGC Forwarding system NGW Sealing fluid supply system NGX Fluid supply system for control and protection equipment NGY Control and protection equipment Printout date 14. Mrz. 01 Page NG1 of NG1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : NK 04.04.97 N Process energy supply for external users (e. g. district heating) NK Process gas system NKB Piping system NKW Sealing fluid supply system NKX Fluid supply system for control and protection equipment NKY Control and protection equipment Printout date 14. Mrz. 01 Page NK1 of NK1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : P 04.04.97 P Cooling water systems PA Circulating (main cooling) water system PB Circulating (main cooling) water treatment system PC Service (secondary cooling) water system for conventional area PD Service (secondary cooling) water treatment system, conventional area PE Service (secondary cooling) water system for secured area PF Service (secondary cooling) water treatment system for secured area PG Closed cooling water system for conventional area PH Closed cooling water treatment system for conventional area PJ Closed cooling water system for secured area PK Closed cooling water treatment system for secured area PM Closed cooling water system for transformers (if separate closed cooling water system) PS Cooling tower blowdown system (if separate from *PAB*) PU Common equipment for cooling water systems PV Lubricant supply system PW Sealing fluid supply system PX Fluid supply system for control and protection equipment PY Control and protection equipment Printout date 14. Mrz. 01 Page P1 of P1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : PA 04.04.97 P Cooling water systems PA Circulating (main cooling) water system PAA Extraction, mechanical cleaning for direct cooling Limit: from incl. intake system to incl. mechanical cleaning system outlet PAB Circulating (main cooling) water piping and culvert system Limit: from excl. outlet of circulating (main cooling) water extraction system (excl. any user) to incl. outfall in direct cooling system or from excl. cooling tower outlet to excl. cooling tower inlet in recirculation cooling system PAC Circulating (main cooling) water pump system Limit: from incl. pump system suction nozzle to incl. pump system discharge nozzle PAD Recirculating cooling system, outfall cooling system Limit: from incl. hot water riser to incl. basin outlet PAE Cooling tower pump system (if separate) PAH Condenser cleaning system, incl. all appurtenances PAR Make-up water piping system Limit: from excl. intake to excl. inlet to other system PAS Make-up water pump system Limit: from incl. pump system suction nozzle to incl. pump system discharge nozzle PAV Lubricant supply system PAX Fluid supply system for control and protection equipment PAY Control and protection equipment Printout date 14. Mrz. 01 Page PA1 of PA1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : PB 04.04.97 P Cooling water systems PB Circulating (main cooling) water treatment system PBA Discharge from fluid treatment system (if not part of another system) Limit: from excl. fluid treatment system outlet to excl. inlet to other system PBB Filtering, mechanical cleaning system Limit: from incl. separation equipment inlet to incl. separation equipment outlet PBC Aeration, gas injection system Limit: from excl. atmosphere or from incl. gas supply PBD Precipitation system (e. g. for carbonate hardness removal) Limit: from incl. precipitation equipment inlet to incl. precipitation equipment outlet PBE Acid proportioning system (e. g. for carbonate hardness removal) Limit: from incl. acid dosing equipment or from excl. branch off chemicals supply system to excl. inlet to other system PBF Ion exchange system (e. g. for demineralization) Limit: from incl. ion exchanger inlet and from incl. isolating valve of chemicals supply system or auxiliary fluid supply system upstream of ion exchanger PBG Evaporation system (e. g. for demineralisation) Limit: from incl. feedwater inlet to incl. steam outlet and from incl. heating steam inlet to incl. condensate outlet PBH Deaeration, drying system Limit: from incl. deaerator or tank inlet to incl. tank outlet incl. warm-up equipment of vapour condenser PBJ Preheating, cooling system Limit: from incl. preheater or cooler inlet to incl. preheater or cooler outlet PBK Piping system, temporary storage system, pump system for main fluid Limit: Piping system: from excl. intake or from excl. outlet of other system to excl. inlet to other system to incl. fluid treatment system outlet Temporary storage system: from incl. temporary storage system inlet to incl. temporary storage system outlet Pump system: from incl. pump system suction nozzle to incl. pump system discharge nozzle PBL Storage system outside fluid treatment system (if not part of another system) Limit: from incl. storage system inlet to incl. storage system outlet incl. intake and outfall Printout date 14. Mrz. 01 Page PB1 of PB2 Siemens 2 nd complete, non-project related edition Condition-Date: PBN KKS Identification System for Power Plants Function key : PB 04.04.97 Chemicals supply system Limit: from incl. intake or from incl. storage tank to excl. discharge into other system PBP Regeneration, flushing equipment Limit: from incl. system inlet to excl. inlet to other system from excl. chemicals or auxiliary fluid supply system and flushing air supply system to incl. regenerating, flushing equipment PBQ Injection system for main fluid Limit: from incl. injection equipment or from excl. branch off chemicals supply system to excl. inlet to other system PBR Flushing water and residues removal system, incl. neutralization Limit: from excl. outlet of respective system to excl. discharge into disposal system PBS Sludge thickening system Limit: from excl. outlet of respective system to excl. discharge into other system PBT Heating, cooling and flushing fluid distribution system Limit: from incl. heating, cooling, flushing fluid generation equipment or from excl. branch off heating, cooling, flushing fluid supply system to excl. user and from excl. user PBV Lubricant supply system PBX Fluid supply system for control and protection equipment PBY Control and protection equipment Printout date 14. Mrz. 01 Page PB2 of PB2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : PC 04.04.97 P Cooling water systems PC Service (secondary cooling) water system for conventional area PCA Extraction, mechanical cleaning for direct cooling Limit: from incl. intake system to incl. mechanical cleaning system outlet PCB Piping and culvert system Limit: from excl. outlet of service (secondary cooling) water extraction system or from excl. branch off circulating water system to excl. inlet to other system, excl. respective user and from excl. make-up water treatment and distribution system PCC Pump system Limit: from incl. pump system suction nozzle to incl. pump system discharge nozzle PCD Recirculation cooling system, outfall cooling system Limit: from incl. hot water riser to incl. basin outlet PCH Heat exchanger cleaning system PCM Service (secondary cooling) water system for generator, motor generator cooling Limit: from excl. branch off *PCB* to excl. generator cooler and from excl. generator cooler to excl. inlet to *PCB* or other systems PCV Lubricant supply system PCX Fluid supply system for control and protection equipment PCY Control and protection equipment Printout date 14. Mrz. 01 Page PC1 of PC1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : PD 04.04.97 P Cooling water systems PD Service (secondary cooling) water treatment system, conventional area PDA Discharge from fluid treatment system (if not part of another system) Limit: from excl. fluid treatment system outlet to excl. inlet to other system PDB Filtering, mechanical cleaning system Limit: from incl. separation equipment inlet to incl. separation equipment outlet PDC Aeration, gas injection system Limit: from excl. atmosphere or from incl. gas supply PDD Precipitation system (e. g. for carbonate hardness removal) Limit: from incl. precipitation equipment inlet to incl. precipitation equipment outlet PDE Acid proportioning system (e. g. for carbonate hardness removal) Limit: from incl. acid proportioning equipment or from excl. branch off chemicals supply system to excl. inlet to other system PDF Ion exchange system (e. g. for demineralization) Limit: from incl. ion exchanger inlet and from incl. isolating valve of chemicals supply system or auxiliary fluid supply system upstream of ion exchanger PDG Evaporation system (e. g. for demineralization) Limit: from incl. feedwater inlet to incl. steam outlet and from incl. heating steam inlet to incl. condensate outlet PDH Deaeration, drying system Limit: from incl. deaerator or tank inlet to incl. tank outlet incl. warm-up equipment of vapour condenser PDJ Preheating, cooling system Limit: from incl. preheater or cooler inlet to incl. preheater or cooler outlet PDK Piping system, temporary storage system, pump system for main fluid Limit: Piping system: from excl. intake or from excl. outlet of other system to excl. inlet to other system to incl. fluid treatment system outlet Temporary storage system: from incl. temporary storage system inlet to incl. temporary storage system outlet Pump system: from incl. pump system suction nozzle to incl. pump system discharge nozzle PDL Storage system outside fluid treatment system (if not part of another system) Limit: from incl. storage system inlet to incl. storage system outlet incl. intake and outfall Printout date 14. Mrz. 01 Page PD1 of PD2 Siemens 2 nd complete, non-project related edition Condition-Date: PDN KKS Identification System for Power Plants Function key : PD 04.04.97 Chemicals supply system Limit: from incl. intake or from incl. storage tank to excl. discharge into other system PDP Regeneration, flushing equipment Limit: from incl. system inlet to excl. inlet to other system from excl. chemicals or auxiliary fluid supply system and flushing air supply system to incl. regenerating, flushing equipment PDQ Injection system for main fluid Limit: from incl. injection equipment or from excl. branch off chemicals supply system to excl. inlet to other system PDR Flushing water and residues removal system, incl. neutralization Limit: from excl. outlet of respective system to excl. discharge into disposal system PDS Sludge thickening system Limit: from excl. outlet of respective system to excl. discharge into other system PDT Heating, cooling and flushing fluid distribution system Limit: from incl. heating, cooling, flushing fluid generation equipment or from excl. branch off heating, cooling, flushing fluid supply system to excl. user and from excl. user PDV Lubricant supply system PDX Fluid supply system for control and protection equipment PDY Control and protection equipment Printout date 14. Mrz. 01 Page PD2 of PD2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : PE 04.04.97 P Cooling water systems PE Service (secondary cooling) water system for secured area PEA Extraction, mechanical cleaning for direct cooling Limit: from incl. intake works to incl. mechanical cleaning system outlet PEB Piping and culvert system Limit: from excl. outlet of service (secondary cooling) water extraction system or from excl. cooling tower outlet with surge pond and return to excl. inlet to other system, excl. respective user and from excl. make-up water treatment and distribution system PEC Pump system Limit: from incl. pump system suction nozzle to incl. pump system discharge nozzle PED Recirculation cooling system, outfall cooling system Limit: from incl. hot water riser to incl. basin outlet PEH Secured component cooler cleaning system PEV Lubricant supply system PEX Fluid supply system for control and protection equipment PEY Control and protection equipment Printout date 14. Mrz. 01 Page PE1 of PE1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : PF 04.04.97 P Cooling water systems PF Service (secondary cooling) water treatment system for secured area PFA Discharge from fluid treatment system (if not part of another system) Limit: from excl. fluid treatment system outlet to excl. inlet to other system PFB Filtering, mechanical cleaning system Limit: from incl. separation equipment inlet to incl. separation equipment outlet PFC Aeration, gas injection system Limit: from excl. atmosphere or from incl. gas supply PFD Precipitation system (e. g. for carbonate hardness removal) Limit: from incl. precipitation equipment inlet to incl. precipitation equipment outlet PFE Acid proportioning system (e. g. for carbonate hardness removal) Limit: from incl. acid dosing equipment or from excl. branch off chemicals supply system to excl. inlet to other system PFF Ion exchange system (e. g. for demineralization) Limit: from incl. ion exchanger inlet and from incl. isolating valve of chemicals supply system or auxiliary fluid supply system upstream of ion exchanger PFG Evaporation system (e. g. for demineralization) Limit: from incl. feedwater inlet to incl. steam outlet and from incl. heating steam inlet to incl. condensate outlet PFH Deaeration, drying system Limit: from incl. deaerator or tank inlet to incl. tank outlet incl. warm-up equipment of vapour condenser PFJ Preheating, cooling system Limit: from incl. preheater or cooler inlet to incl. preheater or cooler outlet PFK Piping system, temporary storage system, pump system for main fluid Limit: Piping system: from excl. intake or from excl. outlet of other system to excl. inlet to other system to incl. fluid treatment system outlet Temporary storage system: from incl. temporary storage system inlet to incl. temporary storage system outlet Pump system: from incl. pump system suction nozzle to incl. pump system discharge nozzle PFL Storage system outside fluid treatment system (if not part of another system) Limit: from incl. storage system inlet to incl. storage system outlet incl. intake and outfall Printout date 14. Mrz. 01 Page PF1 of PF2 Siemens 2 nd complete, non-project related edition Condition-Date: PFN KKS Identification System for Power Plants Function key : PF 04.04.97 Chemicals supply system Limit: from incl. intake or from incl. storage tank to excl. discharge into other system PFP Regeneration, flushing equipment Limit: from incl. system inlet to excl. inlet to other system from excl. chemicals or auxiliary fluid supply system and flushing air supply system to incl. regenerating, flushing equipment PFQ Injection system for main fluid Limit: from incl. injection equipment or from excl. branch off chemicals supply system to excl. inlet to other system PFR Flushing water and residues removal system, incl. neutralization Limit: from excl. outlet of respective system to excl. discharge into disposal system PFS Sludge thickening system Limit: from excl. outlet of respective system to excl. discharge into other system PFT Heating, cooling and flushing fluid distribution system Limit: from incl. heating, cooling, flushing fluid generation equipment or from excl. branch off heating, cooling, flushing fluid supply system to excl. user and from excl. user PFV Lubricant supply system PFX Fluid supply system for control and protection equipment PFY Control and protection equipment Printout date 14. Mrz. 01 Page PF2 of PF2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : PG 04.04.97 P Cooling water systems PG Closed cooling water system for conventional area PGA Closed cooling water system for conventional area PGB Closed cooling water system for conventional area PGC Closed cooling water system for conventional area PGD Closed cooling water system for conventional area PGE Closed cooling water system for conventional area PGF Closed cooling water system for conventional area PGG Closed cooling water system for conventional area PGH Closed cooling water system for conventional area PGJ Closed cooling water system for conventional area PGK Closed cooling water system for conventional area PGL Closed cooling water system for conventional area PGM Closed cooling water system for conventional area PGN Closed cooling water system for conventional area PGP Closed cooling water system for conventional area PGQ Closed cooling water system for conventional area PGR Closed cooling water system for conventional area PGS Closed cooling water system for conventional area PGT Closed cooling water system for conventional area PGU Closed cooling water system for conventional area PGV Lubricant supply system PGX Fluid supply system for control and protection equipment PGY Control and protection equipment Printout date 14. Mrz. 01 Page PG1 of PG1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : PH 04.04.97 P Cooling water systems PH Closed cooling water treatment system for conventional area PHA Discharge from fluid treatment system (if not part of another system) Limit: from excl. fluid treatment system outlet to excl. inlet to other system PHB Filtering, mechanical cleaning system Limit: from incl. separation equipment inlet to incl. separation equipment outlet PHC Aeration, gas injection system Limit: from excl. atmospere or from incl. gas supply PHD Precipitation system (e. g. for carbonate hardness removal) Limit: from incl. precipitation equipment inlet to incl. precipitation equipment outlet PHE Acid proportioning system (e. g. for carbonate hardness removal) Limit: from incl. acid proportioning equipment or from excl. branch off chemicals supply system to excl. inlet to other system PHF Ion exchangesystem (e. g. for demineralization) Limit: from incl. ion exchanger inlet and from incl. isolating valve of chemicals supply system or auxiliary fluid supply system upstream of ion exchanger PHG Evaporation system (e. g. for demineralization) Limit: from incl. feedwater inlet to incl. steam outlet and from incl. heating steam inlet to incl. condensate outlet PHH Deaeration, drying system Limit: from incl. deaerator or tank inlet to incl. tank outlet, incl. warm-up equipment of vapour condenser PHJ Preheating, cooling system Limit: from incl. preheater or cooler inlet to incl. preheater or cooler outlet PHK Piping system, temporary storage system, pump system for main fluid Limit: Piping system: from excl. intake or from excl. outlet of other system to excl. inlet to other system to incl. fluid treatment system outlet Temporary storage system: from incl. temporary storage system inlet to incl. temporary storage system outlet Pump system: from incl. pump system suction nozzle to incl. pump system discharge nozzle PHL Storage system outside fluid treatment system (if not part of another system) Limit: from incl. storage system inlet to incl. storage system outlet, incl. intake and outfall Printout date 14. Mrz. 01 Page PH1 of PH2 Siemens 2 nd complete, non-project related edition Condition-Date: PHN KKS Identification System for Power Plants Function key : PH 04.04.97 Chemicals supply system Limit: from incl. intake or from incl. storage tank to excl. discharge into other system PHP Regeneration, flushing equipment Limit: from incl. system inlet to excl. inlet to other system from excl. chemicals or auxiliary fluid supply system and flushing air supply system to incl. regenerating, flushing equipment PHQ Injection system for main fluid Limit: from incl. injection equipment or from excl. branch off chemicals supply system to excl. inlet to other system PHR Flushing water and residues removal system, incl. neutralization Limit: from excl. outlet of respective system to excl. discharge into disposal system PHS Sludge thickening system Limit: from excl. outlet of respective system to excl. discharge into other system PHT Heating, cooling and flushing fluid distribution system Limit: from incl. heating, cooling, flushing fluid generation equipment or from excl. branch off heating, cooling, flushing fluid supply system to excl. user and from excl. user PHV Lubricant supply system PHX Fluid supply system for control and protection equipment PHY Control and protection equipment Printout date 14. Mrz. 01 Page PH2 of PH2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : PJ 04.04.97 P Cooling water systems PJ Closed cooling water system for secured area PJA Closed cooling water system for secured area PJB Closed cooling water system for secured area PJC Closed cooling water system for secured area PJD Closed cooling water system for secured area PJE Closed cooling water system for secured area PJF Closed cooling water system for secured area PJG Closed cooling water system for secured area PJH Closed cooling water system for secured area PJJ Closed cooling water system for secured area PJK Closed cooling water system for secured area PJL Closed cooling water system for secured area PJM Closed cooling water system for secured area PJN Closed cooling water system for secured area PJP Closed cooling water system for secured area PJQ Closed cooling water system for secured area PJR Closed cooling water system for secured area PJS Closed cooling water system for secured area PJT Closed cooling water system for secured area PJU Closed cooling water system for secured area PJV Lubricant supply system PJX Fluid supply system for control and protection equipment PJY Control and protection equipment Printout date 14. Mrz. 01 Page PJ1 of PJ1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : PK 04.04.97 P Cooling water systems PK Closed cooling water treatment system for secured area PKA Discharge from fluid treatment system (if not part of another system) Limit: from excl. fluid treatment system outlet to excl. inlet to other system PKB Filtering, mechanical cleaning system Limit: from incl. separation equipment inlet to incl. separation equipment outlet PKC Aeration, gas injection system Limit: from excl. atmosphere or from incl. gas supply PKD Precipitation system (e. g. for carbonate hardness removal) Limit: from incl. precipitation equipment inlet to incl. precipitation equipment outlet PKE Acid proportioning system (e. g. for carbonate hardness removal) Limit: from incl. acid proportioning equipment or from excl. branch off chemicals supply system to excl. inlet to other system PKF Ion exchange system (e. g. for demineralization) Limit: from incl. ion exchanger inlet and from incl. isolating valve of chemicals supply system or auxiliary fluid supply system upstream of ion exchanger PKG Evaporation system (e. g. for demineralization) Limit: from incl. feedwater inlet to incl. steam outlet and from incl. heating steam inlet to incl. condensate outlet PKH Deaeration, drying system Limit: from incl. deaerator or tank inlet to incl. tank outlet, incl. warm-up equipment of vapour condenser PKJ Preheating, cooling system Limit: from incl. preheater or cooler inlet to incl. preheater or cooler outlet PKK Piping system, temporary storage system, pump system for main fluid Limit: Piping system: from excl. intake or from excl. outlet of other system to excl. inlet to other system to incl. fluid treatment system outlet Temporary storage system: from incl. temporary storage system inlet to incl. temporary storage system outlet Pump system: from incl. pump system suction nozzle to incl. pump system discharge nozzle PKL Storage system outside fluid treatment system (if not part of another system) Limit: from incl. storage system inlet to incl. storage system outlet, incl. intake and outfall Printout date 14. Mrz. 01 Page PK1 of PK2 Siemens 2 nd complete, non-project related edition Condition-Date: PKN KKS Identification System for Power Plants Function key : PK 04.04.97 Chemicals supply system Limit: from incl. intake or from incl. storage tank to excl. discharge into other system PKP Regeneration, flushing equipment Limit: from incl. system inlet to excl. inlet to other system from excl. chemicals or auxiliary fluid supply system and flushing air supply system to incl. regenerating, flushing equipment PKQ Injection system for main fluid Limit: from incl. injection equipment or from excl. branch off chemicals supply system to excl. inlet to other system PKR Flushing water and residues removal system, incl. neutralization Limit: from excl. outlet of respective system to excl. discharge into disposal system PKS Sludge thickening system Limit: from excl. outlet of respective system to excl. discharge into other system PKT Heating, cooling and flushing fluid distribution system Limit: from incl. heating, cooling, flushing fluid generation equipment or from excl. branch off heating, cooling, flushing fluid supply system to excl. user and from excl. user PKV Lubricant supply system PKX Fluid supply system for control and protection equipment PKY Control and protection equipment Printout date 14. Mrz. 01 Page PK2 of PK2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : PM 04.04.97 P Cooling water systems PM Closed cooling water system for transformers (if separate closed cooling water system) PMA Closed cooling water system for transformers PMB Closed cooling water system for transformers PMC Closed cooling water system for transformers PMD Closed cooling water system for transformers PME Closed cooling water system for transformers PMF Closed cooling water system for transformers PMG Closed cooling water system for transformers PMH Closed cooling water system for transformers PMJ Closed cooling water system for transformers PMK Closed cooling water system for transformers PML Closed cooling water system for transformers PMM Closed cooling water system for transformers PMN Closed cooling water system for transformers PMP Closed cooling water system for transformers PMQ Closed cooling water system for transformers PMR Closed cooling water system for transformers PMS Closed cooling water system for transformers PMT Closed cooling water system for transformers PMU Closed cooling water system for transformers PMV Lubricant supply system PMX Fluid supply system for control and protection equipment PMY Control and protection equipment Printout date 14. Mrz. 01 Page PM1 of PM1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : PS 04.04.97 P Cooling water systems PS Cooling tower blowdown system (if separate from *PAB*) PSA Cooling tower blowdown system PSB Cooling tower blowdown system PSC Cooling tower blowdown system PSD Cooling tower blowdown system PSE Cooling tower blowdown system PSF Cooling tower blowdown system PSG Cooling tower blowdown system PSH Cooling tower blowdown system PSJ Cooling tower blowdown system PSK Cooling tower blowdown system PSL Cooling tower blowdown system PSM Cooling tower blowdown system PSN Cooling tower blowdown system PSP Cooling tower blowdown system PSQ Cooling tower blowdown system PSR Cooling tower blowdown system PSS Cooling tower blowdown system PST Cooling tower blowdown system PSU Cooling tower blowdown system PSV Lubricant supply system PSX Fluid supply system for control and protection equipment PSY Control and protection equipment Printout date 14. Mrz. 01 Page PS1 of PS1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : PU 04.04.97 P Cooling water systems PU Common equipment for cooling water systems PUA Common equipment for cooling water systems PUB Common equipment for cooling water systems PUC Common equipment for cooling water systems PUD Common equipment for cooling water systems PUE Common equipment for cooling water systems PUF Common equipment for cooling water systems PUG Common equipment for cooling water systems PUH Common equipment for cooling water systems PUJ Common equipment for cooling water systems PUK Common equipment for cooling water systems PUL Common equipment for cooling water systems PUM Common equipment for cooling water systems PUN Proportioning equipment PUP Common equipment for cooling water systems PUQ Common equipment for cooling water systems PUR Impressed current cathodic protection for mechanical equipment within the cooling water system PUS Common equipment for cooling water systems PUT Common equipment for cooling water systems PUU Common equipment for cooling water systems Printout date 14. Mrz. 01 Page PU1 of PU1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : PV 04.04.97 P Cooling water systems PV Lubricant supply system PVA Lubricant supply system PVB Lubricant supply system PVC Lubricant supply system PVD Lubricant supply system PVE Lubricant supply system PVF Lubricant supply system PVG Lubricant supply system PVH Lubricant supply system PVJ Lubricant supply system PVK Lubricant supply system PVL Lubricant supply system PVM Lubricant supply system PVN Lubricant supply system PVP Lubricant supply system PVQ Lubricant supply system PVR Lubricant supply system PVS Lubricant supply system PVT Lubricant supply system PVU Lubricant supply system Printout date 14. Mrz. 01 Page PV1 of PV1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : PW 04.04.97 P Cooling water systems PW Sealing fluid supply system PWA Sealing fluid supply system PWB Sealing fluid supply system PWC Sealing fluid supply system PWD Sealing fluid supply system PWE Sealing fluid supply system PWF Sealing fluid supply system PWG Sealing fluid supply system PWH Sealing fluid supply system PWJ Sealing fluid supply system PWK Sealing fluid supply system PWL Sealing fluid supply system PWM Sealing fluid supply system PWN Sealing fluid supply system PWP Sealing fluid supply system PWQ Sealing fluid supply system PWR Sealing fluid supply system PWS Sealing fluid supply system PWT Sealing fluid supply system PWU Sealing fluid supply system Printout date 14. Mrz. 01 Page PW1 of PW1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : PX 04.04.97 P Cooling water systems PX Fluid supply system for control and protection equipment PXA Fluid supply system for control and protection equipment PXB Fluid supply system for control and protection equipment PXC Fluid supply system for control and protection equipment PXD Fluid supply system for control and protection equipment PXE Fluid supply system for control and protection equipment PXF Fluid supply system for control and protection equipment PXG Fluid supply system for control and protection equipment PXH Fluid supply system for control and protection equipment PXJ Fluid supply system for control and protection equipment PXK Fluid supply system for control and protection equipment PXL Fluid supply system for control and protection equipment PXM Fluid supply system for control and protection equipment PXN Fluid supply system for control and protection equipment PXP Fluid supply system for control and protection equipment PXQ Fluid supply system for control and protection equipment PXR Fluid supply system for control and protection equipment PXS Fluid supply system for control and protection equipment PXT Fluid supply system for control and protection equipment PXU Fluid supply system for control and protection equipment Printout date 14. Mrz. 01 Page PX1 of PX1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : PY 04.04.97 P Cooling water systems PY Control and protection equipment PYA Control and protection equipment PYB Control and protection equipment PYC Control and protection equipment PYD Control and protection equipment PYE Control and protection equipment PYF Control and protection equipment PYG Control and protection equipment PYH Control and protection equipment PYJ Control and protection equipment PYK Control and protection equipment PYL Control and protection equipment PYM Control and protection equipment PYN Control and protection equipment PYP Control and protection equipment PYQ Control and protection equipment PYR Control and protection equipment PYS Control and protection equipment PYT Control and protection equipment PYU Control and protection equipment Printout date 14. Mrz. 01 Page PY1 of PY1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : Q 04.04.97 Q Auxiliary systems QC Central chemicals supply QE General compressed air and carrier air supply QF General control air supply QG Central gas supply for closed gas cycles (as working fluid) QH Auxiliary steam generating system QJ Central gas supply, also inert gas (see *SE* for welding blanket gas supply systems, see *MK*, *ML*, *XK*, *XL* for central gas supply systems for main and heavy machinery) QK Chilled water systems for conventional area QL Feedwater, steam, condensate cycle of auxiliary steam generating and distribution system QM Air humidifying system QS Central oil supply and disposal system (for systems assignable to more than one F1-function) QU Sampling systems for conventional area Printout date 14. Mrz. 01 Page Q1 of Q1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : QC 04.04.97 Q Auxiliary systems QC Central chemicals supply QCA Central chemicals supply QCB Central chemicals supply QCC Central chemicals supply QCD Central chemicals supply QCE Central chemicals supply QCF Central chemicals supply QCG Central chemicals supply QCH Central chemicals supply QCJ Central chemicals supply QCK Central chemicals supply QCL Central chemicals supply QCM Central chemicals supply QCN Central chemicals supply QCP Central chemicals supply QCQ Central chemicals supply QCR Central chemicals supply QCS Central chemicals supply QCT Central chemicals supply QCU Central chemicals supply QCV Lubricant supply system QCX Fluid supply system for control and protection equipment QCY Control and protection equipment Printout date 14. Mrz. 01 Page QC1 of QC1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : QE 04.04.97 Q Auxiliary systems QE General compressed air and carrier air supply QEA Central compressed air and carrier air generation system QEB Central compressed air and carrier air distribution system QEC General compressed air and carrier air supply QED General compressed air and carrier air supply QEE General compressed air and carrier air supply QEF General compressed air and carrier air supply QEG General compressed air and carrier air supply QEH General compressed air and carrier air supply QEJ General compressed air and carrier air supply QEK General compressed air and carrier air supply QEL General compressed air and carrier air supply QEM General compressed air and carrier air supply QEN General compressed air and carrier air supply QEP General compressed air and carrier air supply QEQ General compressed air and carrier air supply QER General compressed air and carrier air supply QES General compressed air and carrier air supply QET General compressed air and carrier air supply QEU General compressed air and carrier air supply QEV Lubricant supply system QEW Sealing fluid supply system QEX Fluid supply system for control and protection equipment QEY Control and protection equipment Printout date 14. Mrz. 01 Page QE1 of QE1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : QF 04.04.97 Q Auxiliary systems QF General control air supply QFA Central control air generation system QFB Central control air distribution system QFC General control air supply QFD General control air supply QFE General control air supply QFF General control air supply QFG General control air supply QFH General control air supply QFJ General control air supply QFK General control air supply QFL General control air supply QFM General control air supply QFN General control air supply QFP General control air supply QFQ General control air supply QFR General control air supply QFS General control air supply QFT General control air supply QFU General control air supply QFV Lubricant supply system QFW Sealing fluid supply system QFX Fluid supply system for control and protection equipment QFY Control and protection equipment Printout date 14. Mrz. 01 Page QF1 of QF1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : QG 04.04.97 Q Auxiliary systems QG Central gas supply for closed gas cycles (as working fluid) QGA Central gas supply for closed gas cycles (as working fluid) QGB Central gas supply for closed gas cycles (as working fluid) QGC Central gas supply for closed gas cycles (as working fluid) QGD Central gas supply for closed gas cycles (as working fluid) QGE Central gas supply for closed gas cycles (as working fluid) QGF Central gas supply for closed gas cycles (as working fluid) QGG Central gas supply for closed gas cycles (as working fluid) QGH Central gas supply for closed gas cycles (as working fluid) QGJ Central gas supply for closed gas cycles (as working fluid) QGK Central gas supply for closed gas cycles (as working fluid) QGL Central gas supply for closed gas cycles (as working fluid) QGM Central gas supply for closed gas cycles (as working fluid) QGN Central gas supply for closed gas cycles (as working fluid) QGP Central gas supply for closed gas cycles (as working fluid) QGQ Central gas supply for closed gas cycles (as working fluid) QGR Central gas supply for closed gas cycles (as working fluid) QGS Central gas supply for closed gas cycles (as working fluid) QGT Central gas supply for closed gas cycles (as working fluid) QGU Central gas supply for closed gas cycles (as working fluid) QGV Lubricant supply system QGW Sealing fluid supply system QGX Fluid supply system for control and protection equipment QGY Control and protection equipment Printout date 14. Mrz. 01 Page QG1 of QG1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : QH 04.04.97 Q Auxiliary systems QH Auxiliary steam generating system QHA Pressure system QHB Support structure, enclosure, steam generator interior QHC Fireside heat transfer surface cleaning equipment QHD Ash and slag removal QHE Blowdown system, flash drain system QHF Bunker, feeder and pulverizing system QHG Boiler water circulation system (also for electrode steam boiler) QHH Main firing system (electric-powered as well) QHJ Ignition firing equipment (if separate) QHL Combustion air system (primary air, secondary air) QHM Gas heating system (for closed cycle) QHN Flue gas exhaust (without flue gas treatment) QHP Mechanical dust handling system QHQ Electrostatic precipitator QHR Chemical flue gas treatment system, incl. residues removal, adsorptive process QHS Chemical flue gas treatment system, incl. residues removal, catalytic process QHT Chemical flue gas treatment system, incl. residues removal, absorptive process QHU Flue gas reheating system QHV Lubricant supply system QHX Fluid supply system for control and protection equipment QHY Control and protection equipment Printout date 14. Mrz. 01 Page QH1 of QH1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : QJ 04.04.97 Q Auxiliary systems QJ Central gas supply, also inert gas (see *SE* for welding blanket gas supply systems, see *MK*, *ML*, *XK*, *XL* for central gas supply systems for main and heavy machinery) QJA Central gas supply, also inert gas QJB Central gas supply, also inert gas QJC Central gas supply, also inert gas QJD Central gas supply, also inert gas QJE Central gas supply, also inert gas QJF Central gas supply, also inert gas QJG Central gas supply, also inert gas QJH Central gas supply, also inert gas QJJ Central gas supply, also inert gas QJK Central gas supply, also inert gas QJL Central gas supply, also inert gas QJM Central gas supply, also inert gas QJN Central gas supply, also inert gas QJP Central gas supply, also inert gas QJQ Central gas supply, also inert gas QJR Central gas supply, also inert gas QJV Lubricant supply system QJW Sealing fluid supply system QJX Fluid supply system for control and protection equipment QJY Control and protection equipment Printout date 14. Mrz. 01 Page QJ1 of QJ1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : QK 04.04.97 Q Auxiliary systems QK Chilled water systems for conventional area QKA Chilled water systems for conventional area QKB Chilled water systems for conventional area QKC Chilled water systems for conventional area QKD Chilled water systems for conventional area QKE Chilled water systems for conventional area QKF Chilled water systems for conventional area QKG Chilled water systems for conventional area QKH Chilled water systems for conventional area QKJ Chilled water systems for conventional area QKK Chilled water systems for conventional area QKL Chilled water systems for conventional area QKM Chilled water systems for conventional area QKN Chilled water systems for conventional area QKP Chilled water systems for conventional area QKQ Chilled water systems for conventional area QKR Chilled water systems for conventional area QKS Chilled water systems for conventional area QKT Chilled water systems for conventional area QKU Chilled water systems for conventional area QKV Lubricant supply system QKX Fluid supply system for control and protection equipment QKY Control and protection equipment Printout date 14. Mrz. 01 Page QK1 of QK1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : QL 04.04.97 Q Auxiliary systems QL Feedwater, steam, condensate cycle of auxiliary steam generating and distribution system QLA Feedwater system QLB Steam system QLC Condensate system QLD Condensate polishing plant QLF Common equipment for auxiliary steam generation and distribution systems QLV Lubricant supply system QLX Fluid supply system for control and protection equipment QLY Control and protection equipment Printout date 14. Mrz. 01 Page QL1 of QL1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : QM 04.04.97 Q Auxiliary systems QM Air humidifying system QMA Air humidifying system QMB Air humidifying system QMC Air humidifying system QMD Air humidifying system QME Air humidifying system QMF Air humidifying system QMG Air humidifying system QMH Air humidifying system QMJ Air humidifying system QMK Air humidifying system QML Air humidifying system QMM Air humidifying system QMN Air humidifying system QMP Air humidifying system QMQ Air humidifying system QMR Air humidifying system QMS Air humidifying system QMT Air humidifying system QMU Air humidifying system QMV Lubricant supply system QMX Fluid supply system for control and protection equipment QMY Control and protection equipment Printout date 14. Mrz. 01 Page QM1 of QM1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : QS 04.04.97 Q Auxiliary systems QS Central oil supply and disposal system (for systems assignable to more than one F1-function) QSA Central oil supply and disposal system QSB Central oil supply and disposal system QSC Central oil supply and disposal system QSD Central oil supply and disposal system QSE Central oil supply and disposal system QSF Central oil supply and disposal system QSG Central oil supply and disposal system QSH Central oil supply and disposal system QSJ Central oil supply and disposal system QSK Central oil supply and disposal system QSL Central oil supply and disposal system QSM Central oil supply and disposal system QSN Central oil supply and disposal system QSP Central oil supply and disposal system QSQ Central oil supply and disposal system QSR Central oil supply and disposal system QSS Central oil supply and disposal system QST Central oil supply and disposal system QSU Central oil supply and disposal system QSV Lubricant supply system QSX Fluid supply system for control and protection equipment QSY Control and protection equipment Printout date 14. Mrz. 01 Page QS1 of QS1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : QU 04.04.97 Q Auxiliary systems QU Sampling systems for conventional area QUA Sampling systems for conventional area QUB Sampling systems for conventional area QUC Sampling systems for conventional area QUD Sampling systems for conventional area QUE Sampling systems for conventional area QUF Sampling systems for conventional area QUG Sampling systems for conventional area QUH Sampling systems for conventional area QUJ Sampling systems for conventional area QUK Sampling systems for conventional area QUL Sampling systems for conventional area QUM Sampling systems for conventional area QUN Sampling systems for conventional area QUP Sampling systems for conventional area QUQ Sampling systems for conventional area QUR Sampling systems for conventional area QUS Sampling systems for conventional area QUT Sampling systems for conventional area QUU Sampling systems for conventional area QUX Fluid supply system for control and protection equipment QUY Control and protection equipment Printout date 14. Mrz. 01 Page QU1 of QU1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : R 04.04.97 R Gas generation and treatment RA Gas generation RB Support structure RC Feedstock systems RD Discharge systems for gasification residues RE Gasifying agent generation and distribution RG Main gas cooling systems (if not *RA*) RH Main gas piping systems, storage, compression, expansion RJ Main gas precipitator RK Main gas clean-up (not *RJ*) including regeneration RL Acid gas, including treatment systems RM Gas recycle, storage and compression systems RN Collection, storage and recycle systems for gas condensate RP Inert gas, including recovery systems RS Supply and removal systems for water, steam and condensate RT Waste water collection and drainage systems RU Waste water treatment systems RV Lubricant supply systems RW Sealing fluid supply systems RX Fluid supply systems for control and protection equipment RY Control and protection equipment RZ Injection and proportioning systems Printout date 14. Mrz. 01 Page R1 of R1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : RA 04.04.97 R Gas generation and treatment RA Gas generation RAA Gas generator Limit: from incl. fuel, ignition fuel and fluxing agent inlet or from excl. burner and nozzle system to excl. removal system or to excl. solids separator and reycle system or to excl. gas generator quench gas section or to incl. main gas outlet RAB Gas generator interior RAC Gas generator internals RAD Lining and refractory brickwork RAE Cooling system Limit: from incl. gas generator cooling system inlet to incl. gas generator cooling system outlet RAF Solids separator and recycle system Limit: from excl. gas generator outlet to excl. gas generator inlet to incl. main gas outlet RAG Gas generator quench gas section Limit: from incl. quench gas section inlet to incl. quench gas section outlet RAH Main burner system Limit: from excl. feedstock system or from excl. gasifying agent generation and distribution system to excl. gas generator interior RAJ Pilot burner system Limit: from excl. pilot burner fuel storage and distribution system or from excl. gasifying agent generation and distribution system to excl. gas generator interior RAK Gas generator ignition and standby burner system incl. combustion air system Limit: from excl. ignition fuel storage and distribution system or from incl. combustion air inlet to excl. gas generator interior RAL Ignition and standby hot gas generation and feed system incl. combustion air system Limit: from excl. ignition fuel storage and distribution system or from incl. combustion air inlet to excl. gas generator interior RAM Separate gasifying agent injection system Limit: from excl. gasifying agent generation and distribution system to excl. gas generator interior RAN Injection from gas recycle system Limit: from excl. gas recycle system to excl. gas generator interior RAP Gas condensate injection system Limit: from excl. gas recycle system for gas condensate to excl. gas generator interior Printout date 14. Mrz. 01 Page RA1 of RA2 Siemens 2 nd complete, non-project related edition Condition-Date: RAQ KKS Identification System for Power Plants Function key : RA 04.04.97 Injection system for other feedstock Limit: from excl. other feedstock system to excl. gas generator interior RAR Fluxing agent injection system Limit: from excl. feed system for fluxing agents to excl. gas generator interior RAS Filter cleaning system Limit: from excl. branch off supply system RAT Fluidizing air injection system Limit: from excl. fluidizing gas piping system to excl. gas generator interior RAV Lubricant supply system RAW Sealing fluid supply system RAX Fluid supply system for control and protection equipment RAY Control and protection equipment Printout date 14. Mrz. 01 Page RA2 of RA2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : RB 04.04.97 R Gas generation and treatment RB Support structure RBA Frame including foundations RBB Enclosures, insulations RBD Platforms and stairways RBE Support structure (available for use as process demands) RBF Support structure (available for use as process demands) Printout date 14. Mrz. 01 Page RB1 of RB1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : RC 04.04.97 R Gas generation and treatment RC Feedstock systems RCA Fuel storage bunker, hopper (atmospheric pressure) Limit: from excl. receiving point to excl. distribution and transport system (atmospheric pressure) RCB Distribution and transport system (atmospheric pressure) Limit: from excl. fuel storage bunker, hopper outlet to excl. pulverizing and mixing system (slurry) or to excl. air lock system, slurry pump system RCC Pulverizing and mixing system (slurry) Limit: from excl. distribution and transport system (atmospheric pressure) to excl. airlock system, slurry pump system RCE Airlock system, slurry pump system Limit: from excl. distribution and transport system (atmospheric pressure) or from excl. pulverizing and mixing system (slurry) to excl. fuel hopper (pressurized) RCF Fuel storage bunker, container (pressurized) Limit: from excl. airlock system, slurry pump system to excl. distribution and transport system (pressurized) RCG Distribution and transport system (pressurized) Limit: from excl. fuel hopper (pressurized) to excl. gas generator or to excl. main burner system RCJ Ignition fuel storage and distribution system Limit: from excl. ignition fuel supply system to excl. gas generator or to excl. gas generator ignition and standby burner system or to excl. ignition and standby hot gas generation and feed system or to excl. feedstock system RCK Pilot burner fuel storage and distribution system Limit: from excl. fuel supply system to excl. pilot burner system RCL Proportioning system for other feedstock Limit: from excl. supply system to excl. gas generator or to excl. feedstock system RCM Proportioning system for fluxing agents Limit: from excl. supply system to excl. gas generator or to excl. feed system for fluxing agents RCS Filter cleaning system Limit: from excl. branch off supply system RCV Lubricant supply system RCW Sealing fluid supply system RCX Fluid supply system for control and protection equipment RCY Control and protection equipment Printout date 14. Mrz. 01 Page RC1 of RC1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : RD 04.04.97 R Gas generation and treatment RD Discharge systems for gasification residues RDA Collection, transport and treatment system (pressurized) (system 1) Limit: from excl. receiving point to excl. gas generator or to excl. pressure relief system RDB Pressure relief system (system 1) Limit: from excl. collection, transport and treatment system (pressurized) to excl. collection, transport and treatment system (atmospheric pressure) RDC Collection, transport and treatment system (atmospheric pressure) (system 1) Limit: from excl. pressure relief system to excl. transport and treatment system for fuel conversion residues or to excl. feedstock system RDE Collection, transport and treatment system (pressurized) (system 2) Limit: from excl. receiving point to excl. gas generator or to excl. pressure relief system RDF Pressure relief system (system 2) Limit: from excl. collection, transport and treatment system (pressurized) to excl. collection, transport and treatment system (atmospheric pressure) RDG Collection, transport and treatment system (atmospheric pressure) (system 2) Limit: from excl. pressure relief system to excl. transport and treatment system for fuel conversion residues or to excl. feedstock system RDJ Collection, transport and treatment system (pressurized) (system 3) Limit: from excl. receiving point to excl. gas generator or to excl. pressure relief system RDK Pressure relief system (system 3) Limit: from excl. collection, transport and treatment system (pressurized) to excl. collection, transport and treatment system (atmospheric pressure) RDL Collection, transport and treatment system (atmospheric pressure) (system 3) Limit: from excl. pressure relief system to excl. transport and treatment system for fuel conversion residues or to excl. feedstock system RDN Collection, transport and treatment system (pressurized) (system 4) Limit: from excl. receiving point to excl. gas generator or to excl. pressure relief system RDP Pressure relief system (system 4) Limit: from excl. collection, transport and treatment system (pressurized) to excl. collection, transport and treatment system (atmospheric pressure) RDQ Collection, transport and treatment system (atmospheric pressure) (system 4) Limit: from excl. pressure relief system to excl. transport and treatment system for fuel conversion residues or to excl. feedstock system Printout date 14. Mrz. 01 Page RD1 of RD2 Siemens 2 nd complete, non-project related edition Condition-Date: RDS KKS Identification System for Power Plants Function key : RD 04.04.97 Filter cleaning system Limit: from excl. branch off supply system RDV Lubricant supply system RDW Sealing fluid supply system RDX Fluid supply system for control and protection equipment RDY Control and protection equipment Printout date 14. Mrz. 01 Page RD2 of RD2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : RE 04.04.97 R Gas generation and treatment RE Gasifying agent generation and distribution REA Air (gasifying agent) compression and supercompression system Limit: from excl. atmosphere or from excl. compressor casing outlet of gas turbine to excl. compressed air distribution system or to excl. gasifying agent heater REB Gasifying agent heater (other than *RGC*) Limit: from incl. preheater inlet to incl. preheater outlet or to incl. preheater outlet incl. desuperheater REC Compressed air distribution system (incl. oxygen-enriched air) Limit: from excl. air (gasifying agent) compression and supercompression system outlet or from excl. oxygen piping system (pressurized) or from excl. other system to excl. other system or to excl. main burner system or to excl. pilot burner system or to excl. separate gasifying agent injection system REE Air compression and supercompression system upstream of air separation plant Limit: from excl. atmosphere or from excl. compressor casing outlet of gas turbine to incl. air compression and supercompression system outlet upstream of air separation plant REF Air separation plant Limit: from excl. air (gasifying agent) compression and supercompression system outlet upstream of air separation plant to excl. oxygen piping system (pressurized) or to excl. oxygen compression and supercompression system or to excl. liquid oxygen discharge system or to excl. discharge system for other gases (inert gases) from air separation plant or to excl. liquid nitrogen discharge system or to excl. inert gas, including recovery system or to excl. nitrogen piping system (*RPG*) REG Oxygen compression and supercompression system Limit: from incl. oxygen compression and supercompression system inlet to incl. oxygen compression and supercompression system outlet REH Oxygen piping system (pressurized) Limit: from excl. air separation plant or from excl. oxygen compression and supercompression system or from excl. other system to excl. other system or to excl. main burner system or to excl. pilot burner system or to excl. separate gasifying agent injection system REJ Liquid oxygen outlet system Limit: from excl. air separation plant to excl. oxygen piping system (pressurized) or to excl. other system Printout date 14. Mrz. 01 Page RE1 of RE2 Siemens 2 nd complete, non-project related edition Condition-Date: REK KKS Identification System for Power Plants Function key : RE 04.04.97 Discharge system for other gases from air separation plant (inert gases) Limit: from excl. air separation plant to incl. dispatch facility or to excl. other system REL Liquid nitrogen discharge system Limit: from excl. air separation plant to excl. inert gas, including recovery system or to excl. other system or to incl. dispatch facility REP External oxygen supply system Limit: from excl. receiving point to excl. oxygen compression and supercompression system or to excl. oxygen piping system (pressurized) RER Gasifying steam system Limit: from excl. water/steam system or from excl. other system to excl. main burner system or to excl. pilot burner system or to excl. separate gasifying agent injection system REV Lubricant supply system REW Sealing fluid supply system REX Fluid supply system for control and protection equipment REY Control and protection equipment Printout date 14. Mrz. 01 Page RE2 of RE2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : RG 04.04.97 R Gas generation and treatment RG Main gas cooling systems (if not *RA*) RGA Indirect heat transfer to water/steam cycle Limit: from incl. main gas inlet or from incl. water/steam inlet to incl. main gas outlet or to incl. water/steam outlet or to incl. gas condensate outlet RGB Indirect heat transfer to gas Limit: from incl. from incl. from incl. to incl. to incl. to incl. to incl. RGC main gas inlet or gas recycle system inlet or inert gas inlet main gas outlet or gas recycle system outlet or inert gas outlet or gas condensate outlet Indirect heat transfer to gasifying agent Limit: from incl. main gas inlet or from incl. gasifying agent inlet to incl. main gas outlet or to incl. gasifying agent outlet or to incl. gas condensate outlet RGD Indirect heat transfer to combustion air Limit: from incl. main gas inlet or from incl. combustion air inlet to incl. main gas outlet or to incl. combustion air outlet or to incl. gas condensate outlet RGE Indirect heat transfer to cooling water Limit: from incl. main gas inlet or from incl. cooling water inlet to incl. main gas outlet or to incl. cooling water outlet or to incl. gas condensate outlet RGJ Direct heat transfer (quench) to gas Limit: from incl. main gas inlet or from incl. coolant inlet from excl. coolant supply line to incl. main gas outlet RGK Direct heat transfer (quench, saturation) to steam RGL Direct heat transfer (quench, saturation) to water RGM Direct heat transfer (quench) to other fluids RGS Filter cleaning system Limit: from excl. branch off supply system RGV Lubricant supply system RGW Sealing fluid supply system RGX Fluid supply system for control and protection equipment RGY Control and protection equipment Printout date 14. Mrz. 01 Page RG1 of RG2 Siemens 2 nd complete, non-project related edition Condition-Date: RGZ KKS Identification System for Power Plants Function key : RG 04.04.97 Injection and proportioning system Printout date 14. Mrz. 01 Page RG2 of RG2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : RH 04.04.97 R Gas generation and treatment RH Main gas piping systems, storage, compression, expansion RHA Main gas piping system Limit: from excl. other system to excl. other system RHE Humidification system Limit: from excl. main gas piping system or from excl. water/steam cycle or from excl. collection, storage and recycle system for gas condensate to excl. main gas piping system or to excl. water/steam cycle or to excl. collection, storage and recycle system for gas condensate RHF Conditioning system 1 Limit: from excl. branch off supply system or from incl. unloading facility RHG Conditioning system 2 Limit: from excl. branch off supply system or from incl. unloading facility RHK Gas storage system Limit: from excl. main gas piping system or from excl. gas compression system to excl. main gas piping system or to excl. gas pressure reducing system RHM Gas compression system Limit: from excl. main gas piping system to excl. main gas piping system or to excl. gas storage system or to excl. gas recycle system RHN Gas pressure reducing system Limit: from excl. main gas piping system or from excl. gas storage system to excl. main gas piping system or to excl. other system RHP Flare system 1 Limit: from excl. main gas piping system to incl. flare system outlet RHQ Flare system 2 Limit: from excl. main gas piping system to incl. flare system outlet RHS Filter cleaning system Limit: from excl. branch off supply system RHV Lubricant supply system RHW Sealing fluid supply system RHX Fluid supply system for control and protection equipment RHY Control and protection equipment RHZ Injection and proportioning system Printout date 14. Mrz. 01 Page RH1 of RH1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : RJ 04.04.97 R Gas generation and treatment RJ Main gas precipitator RJA Cartridge filter system Limit: from incl. cartridge filter inlet from excl. filter cleaning system to incl. cartridge filter outlet to excl. gasification residues removal system RJB Cyclone filter system Limit: from incl. cyclone filter inlet from excl. filter cleaning system to incl. cyclone filter outlet to excl. gasification residues removal system RJC Bag filter system Limit: from incl. bag filter inlet from excl. filter cleaning system to incl. bag filter outlet to excl. gasification residues removal system RJD Packed-bed filter system Limit: from incl. packed-bed filter inlet from excl. filter cleaning system to incl. packed-bed filter outlet to excl. gasification residues removal system RJE Electrostatic precipitator system Limit: from incl. electrostatic precipitator inlet from excl. filter cleaning system to incl. electrostatic precipitator outlet to excl. gasification residues removal system RJS Filter cleaning system Limit: from excl. branch off supply system RJV Lubricant supply system RJW Sealing fluid supply system RJX Fluid supply system for control and protection equipment RJY Control and protection equipment Printout date 14. Mrz. 01 Page RJ1 of RJ1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : RK 04.04.97 R Gas generation and treatment RK Main gas clean-up (not *RJ*) including regeneration RKA Scrubber system Limit: from incl. inlet to incl. outlet RKB Conversion system including hydrolysis Limit: from incl. inlet to incl. outlet RKC Gas purification system Limit: from incl. inlet to incl. outlet RKG Scrubber regeneration system 1 Limit: from incl. inlet to incl. outlet RKH Scrubber regeneration system 2 Limit: from incl. inlet to incl. outlet RKJ Scrubber regeneration system 3 Limit: from incl. inlet to incl. outlet RKL Regeneration system 1 for purification system Limit: from incl. inlet to incl. outlet RKM Regeneration system 2 for purification system Limit: from incl. inlet to incl. outlet RKN Regeneration system 3 for purification system Limit: from incl. inlet to incl. outlet RKQ Refrigeration system Limit: from incl. inlet to incl. outlet RKV Lubricant supply system RKW Sealing fluid supply system RKX Fluid supply system for control and protection equipment RKY Control and protection equipment RKZ Injection and proportioning system Printout date 14. Mrz. 01 Page RK1 of RK1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : RL 04.04.97 R Gas generation and treatment RL Acid gas, including treatment systems RLA Thermal treatment (Claus process) Limit: from incl. inlet to incl. outlet RLB Catalytic treatment (Claus process) Limit: from incl. inlet to incl. outlet RLE Absorber, wet oxidation system Limit: from incl. inlet to incl. outlet RLH Thermal treatment (tail gas) Limit: from incl. inlet to incl. outlet RLJ Catalytic treatment (tail gas) Limit: from incl. inlet to incl. outlet RLK Absorption treatment (tail gas) Limit: from incl. inlet to incl. outlet RLN Sulphur treatment system Limit: from incl. inlet to incl. outlet RLP Sulphur forwarding and storage system Limit: from incl. inlet to incl. outlet RLR Sulphuric acid system Limit: from incl. inlet to incl. outlet RLS Sulphuric acid storage system Limit: from incl. inlet to incl. outlet RLW Sealing fluid supply system RLX Fluid supply system for control and protection equipment RLY Control and protection equipment RLZ Injection and proportioning system Printout date 14. Mrz. 01 Page RL1 of RL1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : RM 04.04.97 R Gas generation and treatment RM Gas recycle, storage and compression systems RMA Quench gas piping system Limit: from excl. main gas piping system or from excl. branch off other system to excl. direct heat transfer (quench) to gas or to excl. gas generator quench gas section RMB Piping system for expanded gas (not from airlock system) Limit: from excl. pressure reducing valve to excl. other system (excl. quench gas compressor) RMC Acid gas piping system Limit: from excl. regeneration system to excl. acid gas, incl. treatment system RMD Fluidizing gas piping system Limit: from excl. main gas piping system to excl. fluidizing air injection system or to excl. load system (excl. fluidizing gas compressor) RME Airlock gas piping system (not inert gas) Limit: from excl. branch off other system to excl. airlocks (excl. airlock gas compressor) RMF Other gas piping system Limit: from excl. branch off other system to excl. other system RMH Storage system 1 Limit: from excl. store inlet to excl. other gas piping system RMJ Storage system 2 Limit: from excl. store inlet to excl. other gas piping system RMM Quench gas compressor system Limit: from incl. compressor system inlet to incl. compressor system outlet RMN Expanded gas compressor system Limit: from incl. compressor system inlet to incl. compressor system outlet RMP Acid gas compressor system Limit: from incl. compressor system inlet to incl. compressor system outlet RMQ Fluidizing gas compressor system Limit: from incl. compressor system inlet to incl. compressor system outlet RMR Airlock gas compressor system (not inert gas) Limit: from incl. compressor system inlet to incl. compressor system outlet RMS Compressor system for other gases Limit: from incl. compressor system inlet to incl. compressor system outlet Printout date 14. Mrz. 01 Page RM1 of RM2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : RM 04.04.97 RMV Lubricant supply system RMW Sealing fluid supply system RMX Fluid supply system for control and protection equipment RMY Control and protection equipment RMZ Injection and proportioning system Printout date 14. Mrz. 01 Page RM2 of RM2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : RN 04.04.97 R Gas generation and treatment RN Collection, storage and recycle systems for gas condensate RNA Collection, storage and recycle systems for gas condensate RNB Collection, storage and recycle systems for gas condensate RNC Collection, storage and recycle systems for gas condensate RND Collection, storage and recycle systems for gas condensate RNE Collection, storage and recycle systems for gas condensate RNF Collection, storage and recycle systems for gas condensate RNG Collection, storage and recycle systems for gas condensate RNH Collection, storage and recycle systems for gas condensate RNJ Collection, storage and recycle systems for gas condensate RNK Collection, storage and recycle systems for gas condensate RNL Collection, storage and recycle systems for gas condensate RNM Collection, storage and recycle systems for gas condensate RNN Collection, storage and recycle systems for gas condensate RNP Collection, storage and recycle systems for gas condensate RNQ Collection, storage and recycle systems for gas condensate RNR Collection, storage and recycle systems for gas condensate RNS Collection, storage and recycle systems for gas condensate RNT Collection, storage and recycle systems for gas condensate RNU Collection, storage and recycle systems for gas condensate RNV Lubricant supply system RNW Sealing fluid supply system RNX Fluid supply system for control and protection equipment RNY Control and protection equipment Printout date 14. Mrz. 01 Page RN1 of RN1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : RP 04.04.97 R Gas generation and treatment RP Inert gas, including recovery systems RPA Inert gas generation by air fractionation Limit: from excl. atmosphere to incl. inert gas distribution system inlet RPB Inert gas generation by molecular sieving Limit: from excl. atmosphere to incl. inert gas distribution system inlet RPC Inert gas generation by combustion Limit: from excl. atmosphere to incl. inert gas distribution system inlet RPG Nitrogen piping system for addition ahead of burner gas turbine Limit: from excl. air separation plant outlet or from excl. compressor outlet to excl. compressor inlet or to excl. combustion chamber inlet RPH Supercompression of nitrogen from *RPG* Limit: from incl. compressor inlet to incl. compressor outlet RPJ Inert gas distribution system including storage system Limit: from excl. inert gas generator outlet or from excl. air separation plant *REF* outlet or from excl. compressor outlet to excl. compressor inlet or to excl. inert gas load system inlet RPK Inert gas distribution system including storage system Limit: from excl. inert gas generator outlet or from excl. air separation plant *REF* outlet or from excl. compressor outlet to excl. compressor inlet or to excl. inert gas load system inlet RPL Inert gas distribution system including storage system Limit: from excl. inert gas generator outlet or from excl. air separation plant *REF* outlet or from excl. compressor outlet to excl. compressor inlet or to excl. inert gas load system inlet RPM Inert gas distribution system including storage system Limit: from excl. inert gas generator outlet or from excl. air separation plant *REF* outlet or from excl. compressor outlet to excl. compressor inlet or to excl. inert gas load system inlet RPN Inert gas distribution system including storage system Limit: from excl. inert gas generator outlet or from excl. air separation plant *REF* outlet or from excl. compressor outlet to excl. compressor inlet or to excl. inert gas load system inlet Printout date 14. Mrz. 01 Page RP1 of RP2 Siemens 2 nd complete, non-project related edition Condition-Date: RPP KKS Identification System for Power Plants Function key : RP 04.04.97 Inert gas compressor system Limit: from incl. compressor inlet to incl. compressor outlet RPQ Inert gas compressor system Limit: from incl. compressor inlet to incl. compressor outlet RPR Inert gas compressor system Limit: from incl. compressor inlet to incl. compressor outlet RPS Inert gas compressor system Limit: from incl. compressor inlet to incl. compressor outlet RPW Sealing fluid supply system RPX Fluid supply system for control and protection equipment RPY Control and protection equipment Printout date 14. Mrz. 01 Page RP2 of RP2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : RS 04.04.97 R Gas generation and treatment RS Supply and removal systems for water, steam and condensate RSA Supply and removal systems for water, steam and condensate Limit: The following applies to supply systems : from excl. branch off other system to excl. user The following applies to removal systems : from excl. producer to excl. discharge into other system RSB Supply and removal systems for water, steam and condensate Limit: The following applies to supply systems : from excl. branch off other system to excl. user The following applies to removal systems : from excl. producer to excl. discharge into other system RSC Supply and removal systems for water, steam and condensate Limit: The following applies to supply systems : from excl. branch off other system to excl. user The following applies to removal systems : from excl. producer to excl. discharge into other system RSD Supply and removal systems for water, steam and condensate Limit: The following applies to supply systems : from excl. branch off other system to excl. user The following applies to removal systems : from excl. producer to excl. discharge into other system RSE Supply and removal systems for water, steam and condensate Limit: The following applies to supply systems : from excl. branch off other system to excl. user The following applies to removal systems : from excl. producer to excl. discharge into other system RSF Supply and removal systems for water, steam and condensate Limit: The following applies to supply systems : from excl. branch off other system to excl. user The following applies to removal systems : from excl. producer to excl. discharge into other system RSG Supply and removal systems for water, steam and condensate Limit: The following applies to supply systems : from excl. branch off other system to excl. user The following applies to removal systems : from excl. producer to excl. discharge into other system Printout date 14. Mrz. 01 Page RS1 of RS3 Siemens 2 nd complete, non-project related edition Condition-Date: RSH KKS Identification System for Power Plants Function key : RS 04.04.97 Supply and removal systems for water, steam and condensate Limit: The following applies to supply systems : from excl. branch off other system to excl. user The following applies to removal systems : from excl. producer to excl. discharge into other system RSJ Supply and removal systems for water, steam and condensate Limit: The following applies to supply systems : from excl. branch off other system to excl. user The following applies to removal systems : from excl. producer to excl. discharge into other system RSK Supply and removal systems for water, steam and condensate Limit: The following applies to supply systems : from excl. branch off other system to excl. user The following applies to removal systems : from excl. producer to excl. discharge into other system RSL Supply and removal systems for water, steam and condensate Limit: The following applies to supply systems : from excl. branch off other system to excl. user The following applies to removal systems : from excl. producer to excl. discharge into other system RSM Supply and removal systems for water, steam and condensate Limit: The following applies to supply systems : from excl. branch off other system to excl. user The following applies to removal systems : from excl. producer to excl. discharge into other system RSN Supply and removal systems for water, steam and condensate Limit: The following applies to supply systems : from excl. branch off other system to excl. user The following applies to removal systems : from excl. producer to excl. discharge into other system RSP Supply and removal systems for water, steam and condensate Limit: The following applies to supply systems : from excl. branch off other system to excl. user The following applies to removal systems : from excl. producer to excl. discharge into other system Printout date 14. Mrz. 01 Page RS2 of RS3 Siemens 2 nd complete, non-project related edition Condition-Date: RSQ KKS Identification System for Power Plants Function key : RS 04.04.97 Supply and removal systems for water, steam and condensate Limit: The following applies to supply systems : from excl. branch off other system to excl. user The following applies to removal systems : from excl. producer to excl. discharge into other system RSR Supply and removal systems for water, steam and condensate Limit: The following applies to supply systems : from excl. branch off other system to excl. user The following applies to removal systems : from excl. producer to excl. discharge into other system RSS Supply and removal systems for water, steam and condensate Limit: The following applies to supply systems : from excl. branch off other system to excl. user The following applies to removal systems : from excl. producer to excl. discharge into other system RST Supply and removal systems for water, steam and condensate Limit: The following applies to supply systems : from excl. branch off other system to excl. user The following applies to removal systems : from excl. producer to excl. discharge into other system RSU Supply and removal systems for water, steam and condensate Limit: The following applies to supply systems : from excl. branch off other system to excl. user The following applies to removal systems : from excl. producer to excl. discharge into other system RSV Lubricant supply system RSW Sealing fluid supply system RSX Fluid supply system for control and protection equipment RSY Control and protection equipment RSZ Injection and proportioning system Printout date 14. Mrz. 01 Page RS3 of RS3 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : RT 04.04.97 R Gas generation and treatment RT Waste water collection and drainage systems RTA Waste water collection and drainage systems Limit: from excl. producer to excl. discharge into other system RTB Waste water collection and drainage systems Limit: from excl. producer to excl. discharge into other system RTC Waste water collection and drainage systems Limit: from excl. producer to excl. discharge into other system RTD Waste water collection and drainage systems Limit: from excl. producer to excl. discharge into other system RTE Waste water collection and drainage systems Limit: from excl. producer to excl. discharge into other system RTF Waste water collection and drainage systems Limit: from excl. producer to excl. discharge into other system RTG Waste water collection and drainage systems Limit: from excl. producer to excl. discharge into other system RTH Waste water collection and drainage systems Limit: from excl. producer to excl. discharge into other system RTJ Waste water collection and drainage systems Limit: from excl. producer to excl. discharge into other system RTK Waste water collection and drainage systems Limit: from excl. producer to excl. discharge into other system RTL Waste water collection and drainage systems Limit: from excl. producer to excl. discharge into other system RTM Waste water collection and drainage systems Limit: from excl. producer to excl. discharge into other system RTN Waste water collection and drainage systems Limit: from excl. producer to excl. discharge into other system RTP Waste water collection and drainage systems Limit: from excl. producer to excl. discharge into other system RTQ Waste water collection and drainage systems Limit: from excl. producer to excl. discharge into other system Printout date 14. Mrz. 01 Page RT1 of RT2 Siemens 2 nd complete, non-project related edition Condition-Date: RTR KKS Identification System for Power Plants Function key : RT 04.04.97 Waste water collection and drainage systems Limit: from excl. producer to excl. discharge into other system RTS Waste water collection and drainage systems Limit: from excl. producer to excl. discharge into other system RTT Waste water collection and drainage systems Limit: from excl. producer to excl. discharge into other system RTU Waste water collection and drainage systems Limit: from excl. producer to excl. discharge into other system RTV Lubricant supply system RTW Sealing fluid supply system RTX Fluid supply system for control and protection equipment RTY Control and protection equipment RTZ Injection and proportioning system Printout date 14. Mrz. 01 Page RT2 of RT2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : RU 04.04.97 R Gas generation and treatment RU Waste water treatment systems RUA Waste water treatment system Limit: from excl. inlet to incl. outlet RUB Waste water treatment system Limit: from excl. inlet to incl. outlet RUC Waste water treatment system Limit: from excl. inlet to incl. outlet RUD Waste water treatment system Limit: from excl. inlet to incl. outlet RUE Waste water treatment system Limit: from excl. inlet to incl. outlet RUF Waste water treatment system Limit: from excl. inlet to incl. outlet RUG Waste water treatment system Limit: from excl. inlet to incl. outlet RUJ Processing material system Limit: from incl. receiving point to excl. discharge RUK Processing material system Limit: from incl. receiving point to excl. discharge RUL Processing material system Limit: from incl. receiving point to excl. discharge RUM Waste water treatment system Limit: from excl. inlet to incl. outlet RUN Waste water treatment system Limit: from excl. inlet to incl. outlet RUP Waste water treatment system Limit: from excl. inlet to incl. outlet RUQ Waste water treatment system Limit: from excl. inlet to incl. outlet RUR Waste water treatment system Limit: from excl. inlet to incl. outlet Printout date 14. Mrz. 01 Page RU1 of RU2 Siemens 2 nd complete, non-project related edition Condition-Date: RUS KKS Identification System for Power Plants Function key : RU 04.04.97 Residues treatment and removal system Limit: from excl. receiving point to excl. discharge RUT Residues treatment and removal system Limit: from excl. receiving point to excl. discharge RUU Residues treatment and removal system Limit: from excl. receiving point to excl. discharge RUV Lubricant supply system RUW Sealing fluid supply system RUX Fluid supply system for control and protection equipment RUY Control and protection equipment RUZ Injection and proportioning system Printout date 14. Mrz. 01 Page RU2 of RU2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : RV 04.04.97 R Gas generation and treatment RV Lubricant supply systems RVA Lubricant supply systems RVB Lubricant supply systems RVC Lubricant supply systems RVD Lubricant supply systems RVE Lubricant supply systems RVF Lubricant supply systems RVG Lubricant supply systems RVH Lubricant supply systems RVJ Lubricant supply systems RVK Lubricant supply systems RVL Lubricant supply systems RVM Lubricant supply systems RVN Lubricant supply systems RVP Lubricant supply systems RVQ Lubricant supply systems RVR Lubricant supply systems RVS Lubricant supply systems RVT Lubricant supply systems RVU Lubricant supply systems Printout date 14. Mrz. 01 Page RV1 of RV1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : RW 04.04.97 R Gas generation and treatment RW Sealing fluid supply systems RWA Sealing fluid supply systems RWB Sealing fluid supply systems RWC Sealing fluid supply systems RWD Sealing fluid supply systems RWE Sealing fluid supply systems RWF Sealing fluid supply systems RWG Sealing fluid supply systems RWH Sealing fluid supply systems RWJ Sealing fluid supply systems RWK Sealing fluid supply systems RWL Sealing fluid supply systems RWM Sealing fluid supply systems RWN Sealing fluid supply systems RWP Sealing fluid supply systems RWQ Sealing fluid supply systems RWR Sealing fluid supply systems RWS Sealing fluid supply systems RWT Sealing fluid supply systems RWU Sealing fluid supply systems Printout date 14. Mrz. 01 Page RW1 of RW1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : RX 04.04.97 R Gas generation and treatment RX Fluid supply systems for control and protection equipment RXA Fluid supply systems for control and protection equipment RXB Fluid supply systems for control and protection equipment RXC Fluid supply systems for control and protection equipment RXD Fluid supply systems for control and protection equipment RXE Fluid supply systems for control and protection equipment RXF Fluid supply systems for control and protection equipment RXG Fluid supply systems for control and protection equipment RXH Fluid supply systems for control and protection equipment RXJ Fluid supply systems for control and protection equipment RXK Fluid supply systems for control and protection equipment RXL Fluid supply systems for control and protection equipment RXM Fluid supply systems for control and protection equipment RXN Fluid supply systems for control and protection equipment RXP Fluid supply systems for control and protection equipment RXQ Fluid supply systems for control and protection equipment RXR Fluid supply systems for control and protection equipment RXS Fluid supply systems for control and protection equipment RXT Fluid supply systems for control and protection equipment RXU Fluid supply systems for control and protection equipment Printout date 14. Mrz. 01 Page RX1 of RX1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : RY 04.04.97 R Gas generation and treatment RY Control and protection equipment RYA Control and protection equipment RYB Control and protection equipment RYC Control and protection equipment RYD Control and protection equipment RYE Control and protection equipment RYF Control and protection equipment RYG Control and protection equipment RYH Control and protection equipment RYJ Control and protection equipment RYK Control and protection equipment RYL Control and protection equipment RYM Control and protection equipment RYN Control and protection equipment RYP Control and protection equipment RYQ Control and protection equipment RYR Control and protection equipment RYS Control and protection equipment RYT Control and protection equipment RYU Control and protection equipment Printout date 14. Mrz. 01 Page RY1 of RY1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : RZ 04.04.97 R Gas generation and treatment RZ Injection and proportioning systems RZA Injection and proportioning systems RZB Injection and proportioning systems RZC Injection and proportioning systems RZD Injection and proportioning systems RZE Injection and proportioning systems RZF Injection and proportioning systems RZG Injection and proportioning systems RZH Injection and proportioning systems RZJ Injection and proportioning systems RZK Injection and proportioning systems RZL Injection and proportioning systems RZM Injection and proportioning systems RZN Injection and proportioning systems RZP Injection and proportioning systems RZQ Injection and proportioning systems RZR Injection and proportioning systems RZS Injection and proportioning systems RZT Injection and proportioning systems RZU Injection and proportioning systems Printout date 14. Mrz. 01 Page RZ1 of RZ1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : S 04.04.97 S Ancillary systems SA Heating, ventilation, air-conditioning (HVAC) systems for conventional area SB Space heating systems SC Stationary compressed air supplies SD Stationary cleaning systems (see *FK.* for decontamination systems) SE Stationary welding gas systems SF Heating and fuel gas systems SG Stationary fire protection systems SH Waterway facilities SM Cranes, stationary hoists and conveying appliances SN Elevators SP Railway installations SQ Road installations SR Workshop, stores, laboratory equipment and staff amenities inside controlled area ST Workshop, stores, laboratory equipment and staff amenities outside controlled area Printout date 14. Mrz. 01 Page S1 of S1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : SA 04.04.97 S Ancillary systems SA Heating, ventilation, air-conditioning (HVAC) systems for conventional area SAA Heating, ventilation, air-conditioning (HVAC) systems for conventional area SAB Heating, ventilation, air-conditioning (HVAC) systems for conventional area SAC Heating, ventilation, air-conditioning (HVAC) systems for conventional area SAD Heating, ventilation, air-conditioning (HVAC) systems for conventional area SAE Heating, ventilation, air-conditioning (HVAC) systems for conventional area SAF Heating, ventilation, air-conditioning (HVAC) systems for conventional area SAG Heating, ventilation, air-conditioning (HVAC) systems for conventional area SAH Heating, ventilation, air-conditioning (HVAC) systems for conventional area SAJ Heating, ventilation, air-conditioning (HVAC) systems for conventional area SAK Heating, ventilation, air-conditioning (HVAC) systems for conventional area SAL Heating, ventilation, air-conditioning (HVAC) systems for conventional area SAM Heating, ventilation, air-conditioning (HVAC) systems for conventional area SAN Heating, ventilation, air-conditioning (HVAC) systems for conventional area SAP Heating, ventilation, air-conditioning (HVAC) systems for conventional area SAQ Heating, ventilation, air-conditioning (HVAC) systems for conventional area SAR Heating, ventilation, air-conditioning (HVAC) systems for conventional area SAS Heating, ventilation, air-conditioning (HVAC) systems for conventional area SAT Heating, ventilation, air-conditioning (HVAC) systems for conventional area SAU Heating, ventilation, air-conditioning (HVAC) systems for conventional area SAV Lubricant supply system SAX Fluid supply system for control and protection equipment SAY Control and protection equipment Printout date 14. Mrz. 01 Page SA1 of SA1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : SB 04.04.97 S Ancillary systems SB Space heating systems SBA Space heating systems SBB Space heating systems SBC Space heating systems SBD Space heating systems SBE Space heating systems SBF Space heating systems SBG Space heating systems SBH Space heating systems SBJ Space heating systems SBK Space heating systems SBL Space heating systems SBM Space heating systems SBN Space heating systems SBP Space heating systems SBQ Space heating systems SBR Space heating systems SBS Space heating systems SBT Space heating systems SBU Space heating systems SBX Fluid supply system for control and protection equipment SBY Control and protection equipment Printout date 14. Mrz. 01 Page SB1 of SB1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : SC 04.04.97 S Ancillary systems SC Stationary compressed air supplies SCA Compressed air generation system SCB Compressed air distribution system SCC Stationary compressed air supplies SCD Stationary compressed air supplies SCE Stationary compressed air supplies SCF Stationary compressed air supplies SCG Stationary compressed air supplies SCH Stationary compressed air supplies SCJ Stationary compressed air supplies SCK Stationary compressed air supplies SCL Stationary compressed air supplies SCM Stationary compressed air supplies SCN Stationary compressed air supplies SCP Stationary compressed air supplies SCQ Stationary compressed air supplies SCR Stationary compressed air supplies SCS Stationary compressed air supplies SCT Stationary compressed air supplies SCU Stationary compressed air supplies SCV Lubricant supply system SCX Fluid supply system for control and protection equipment SCY Control and protection equipment Printout date 14. Mrz. 01 Page SC1 of SC1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : SD 04.04.97 S Ancillary systems SD Stationary cleaning systems (see *FK.* for decontamination systems) SDA Stationary cleaning systems SDB Stationary cleaning systems SDC Stationary cleaning systems SDD Stationary cleaning systems SDE Stationary cleaning systems SDF Stationary cleaning systems SDG Stationary cleaning systems SDH Stationary cleaning systems SDJ Stationary cleaning systems SDK Stationary cleaning systems SDL Stationary cleaning systems SDM Stationary cleaning systems SDN Stationary cleaning systems SDP Stationary cleaning systems SDQ Stationary cleaning systems SDR Stationary cleaning systems SDS Stationary cleaning systems SDT Stationary cleaning systems SDU Stationary cleaning systems SDX Fluid supply system for control and protection equipment SDY Control and protection equipment Printout date 14. Mrz. 01 Page SD1 of SD1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : SE 04.04.97 S Ancillary systems SE Stationary welding gas systems SEA Stationary welding gas systems SEB Stationary welding gas systems SEC Stationary welding gas systems SED Stationary welding gas systems SEE Stationary welding gas systems SEF Stationary welding gas systems SEG Stationary welding gas systems SEH Stationary welding gas systems SEJ Stationary welding gas systems SEK Stationary welding gas systems SEL Stationary welding gas systems SEM Stationary welding gas systems SEN Stationary welding gas systems SEP Stationary welding gas systems SEQ Stationary welding gas systems SER Stationary welding gas systems SES Stationary welding gas systems SET Stationary welding gas systems SEU Stationary welding gas systems Printout date 14. Mrz. 01 Page SE1 of SE1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : SF 04.04.97 S Ancillary systems SF Heating and fuel gas systems SFA Heating and fuel gas systems SFB Heating and fuel gas systems SFC Heating and fuel gas systems SFD Heating and fuel gas systems SFE Heating and fuel gas systems SFF Heating and fuel gas systems SFG Heating and fuel gas systems SFH Heating and fuel gas systems SFJ Heating and fuel gas systems SFK Heating and fuel gas systems SFL Heating and fuel gas systems SFM Heating and fuel gas systems SFN Heating and fuel gas systems SFP Heating and fuel gas systems SFQ Heating and fuel gas systems SFR Heating and fuel gas systems SFS Heating and fuel gas systems SFT Heating and fuel gas systems SFU Heating and fuel gas systems SFY Control and protection equipment Printout date 14. Mrz. 01 Page SF1 of SF1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : SG 04.04.97 S Ancillary systems SG Stationary fire protection systems SGA Fire water system, conventional area SGB Fire water system, nuclear area SGC Spray deluge systems, conventional area SGD Spray deluge systems, nuclear area SGE Sprinkler systems SGF Foam fire-fighting systems SGG Tank roof, tank shell cooling systems SGJ CO2 fire-fighting systems SGK Halon fire-fighting systems SGL Powder fire-fighting systems SGM Inergen fire-fighting systems SGV Lubricant supply system SGX Fluid supply system for control and protection equipment SGY Control and protection equipment Printout date 14. Mrz. 01 Page SG1 of SG1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : SH 04.04.97 S Ancillary systems SH Waterway facilities SHA Intake system (upper pound) Limit: to excl. lock chamber gate (upstream) SHB Lock chamber incl. chamber filling and emptying system SHC Lock chamber gate (upstream) SHD Lock chamber gate (intermediate) SHE Lock chamber gate (downstream) SHF Discharge system (lower pound) Limit: from excl. lock chamber gate (downstream) SHJ Anti-icing system SHK Ship impact system SHL Leakage drain system SHM Draining system SHS Minimum water system SHT Fish ladder SHU Raft canal SHV Lubricant supply system SHW Sealing fluid supply system SHX Fluid supply system for control and protection equipment SHY Control and protection equipment Printout date 14. Mrz. 01 Page SH1 of SH1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : SM 04.04.97 S Ancillary systems SM Cranes, stationary hoists and conveying appliances SMA Cranes, stationary hoists and conveying appliances SMB Cranes, stationary hoists and conveying appliances SMC Cranes, stationary hoists and conveying appliances SMD Cranes, stationary hoists and conveying appliances SME Cranes, stationary hoists and conveying appliances SMF Cranes, stationary hoists and conveying appliances SMG Cranes, stationary hoists and conveying appliances SMH Cranes, stationary hoists and conveying appliances SMJ Cranes, stationary hoists and conveying appliances SMK Cranes, stationary hoists and conveying appliances SML Cranes, stationary hoists and conveying appliances SMM Cranes, stationary hoists and conveying appliances SMN Cranes, stationary hoists and conveying appliances SMP Cranes, stationary hoists and conveying appliances SMQ Cranes, stationary hoists and conveying appliances SMR Cranes, stationary hoists and conveying appliances SMS Cranes, stationary hoists and conveying appliances SMT Cranes, stationary hoists and conveying appliances SMU Cranes, stationary hoists and conveying appliances SMX Fluid supply system for control and protection equipment SMY Control and protection equipment Printout date 14. Mrz. 01 Page SM1 of SM1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : SN 04.04.97 S Ancillary systems SN Elevators SNA Elevators SNB Elevators SNC Elevators SND Elevators SNE Elevators SNF Elevators SNG Elevators SNH Elevators SNJ Elevators SNK Elevators SNL Elevators SNM Elevators SNN Elevators SNP Elevators SNQ Elevators SNR Elevators SNS Elevators SNT Elevators SNU Elevators SNY Control and protection equipment Printout date 14. Mrz. 01 Page SN1 of SN1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : SP 04.04.97 S Ancillary systems SP Railway installations SPA Railway installations SPB Railway installations SPC Railway installations SPD Railway installations SPE Railway installations SPF Railway installations SPG Railway installations SPH Railway installations SPJ Railway installations SPK Railway installations SPL Railway installations SPM Railway installations SPN Railway installations SPP Railway installations SPQ Railway installations SPR Railway installations SPS Railway installations SPT Railway installations SPU Railway installations SPY Control and protection equipment Printout date 14. Mrz. 01 Page SP1 of SP1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : SQ 04.04.97 S Ancillary systems SQ Road installations SQA Road installations SQB Road installations SQC Road installations SQD Road installations SQE Road installations SQF Road installations SQG Road installations SQH Road installations SQJ Road installations SQK Road installations SQL Road installations SQM Road installations SQN Road installations SQP Road installations SQQ Road installations SQR Road installations SQS Road installations SQT Road installations SQU Road installations SQY Control and protection equipment Printout date 14. Mrz. 01 Page SQ1 of SQ1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : SR 04.04.97 S Ancillary systems SR Workshop, stores, laboratory equipment and staff amenities inside controlled area SRA Hot workshop equipment SRC Maintenance areas in controlled area SRG Hot laboratory equipment SRH Health physics laboratory equipment SRP Staff amenities in controlled area SRY Control and protection equipment Printout date 14. Mrz. 01 Page SR1 of SR1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : ST 04.04.97 S Ancillary systems ST Workshop, stores, laboratory equipment and staff amenities outside controlled area STA Workshop equipment outside controlled area STC Maintenance areas outside controlled area STE Stores and filling station equipment STG Laboratory equipment STP Staff amenities STY Control and protection equipment Printout date 14. Mrz. 01 Page ST1 of ST1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : U 04.04.97 U Structures UA Structures for grid and distribution systems UB Structures for power transmission and auxiliary power supply UC Structures for instrumentation and control UE Structures for conventional fuel supply and residues disposal UF Structures for the handling of nuclear equipment UG Structures for water supply and disposal UH Structures for conventional heat generation UJ Structures for nuclear heat generation UK Structures for reactor auxiliary systems UL Structures for steam-, water-, gas-cycles UM Structures for main machine sets UN Structures for process energy supply UP Structures for circulating (cooling) water systems (e. g. circulating water intake) UQ Structures for circulating (cooling) water systems (e. g. circulating water pumps and outfall) UR Structures for circulating (cooling) water systems (e. g. recirculation cooling) US Structures for ancillary systems UT Structures for auxiliary systems UU Shaft structures UV Structures for chemical flue gas treatment incl. residues removal (for *HR.*, *HS.*, *HT.*) UX Structures for external systems (power plant-specific) UY General service structures UZ Structures for transport, traffic, fencing, gardens and other purposes Printout date 14. Mrz. 01 Page U1 of U1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : UA 04.04.97 U Structures UA Structures for grid and distribution systems UAA Switchyard structure UAB Grid systems switchgear building UAC Grid systems control building UAE Structure for pneumatic control system UAG Structure for transformers UAH Structure for supports and equipment UAX Special structure (plant-specific) UAY Bridge structure UAZ Ducting structure Printout date 14. Mrz. 01 Page UA1 of UA1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : UB 04.04.97 U Structures UB Structures for power transmission and auxiliary power supply UBA Switchgear building UBC Structure for offsite system transformers UBD Structure for low-voltage auxiliary power transformers UBE Structure for medium-voltage auxiliary power transformers UBF Structure for generator transformers UBG Structure for start-up transformers UBH Structure for oil collecting pits UBJ Structure for transformer tracks UBK Transformer assembly building UBL Structure for busbars UBM Structure for transformer cooling systems UBN Structure for emergency power generating sets (without central water chiller) UBP Emergency power generating and central water chiller building UBQ Structure for emergency power generator fuel supply system UBX Special structure (plant-specific) UBY Bridge structure UBZ Ducting structure Printout date 14. Mrz. 01 Page UB1 of UB1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : UC 04.04.97 U Structures UC Structures for instrumentation and control UCA Unit control room building UCB Control station building UCL Structure for measuring equipment UCP Cooling water monitoring structure UCX Special structure (plant-specific) UCY Bridge structure UCZ Ducting structure Printout date 14. Mrz. 01 Page UC1 of UC1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : UE 04.04.97 U Structures UE Structures for conventional fuel supply and residues disposal UEA Structure for unloading of solid fuels UEB Structure for storage of solid fuels UED Structure for transport of solid fuels UEE Structure for treatment of solid fuels UEF Structure for transfer (e. g. junction tower) UEG Structure for conversion of solid fuels UEH Structure for unloading and reception of liquid fuels UEJ Structure for storage of liquid fuels UEL Structure for forwarding of liquid fuels (e. g. pump house) UEM Structure for treatment and handling of liquid fuels UEN Structure for transfer, conversion, storage of gaseous fuels UER Structure for forwarding of gaseous fuels UET Structure for ash storage UEU Structure for ash transport UEV Structure for ash settling pond UEW Structure for combustion residues handling UEX Special structure (plant-specific) UEY Bridge structure UEZ Ducting structure Printout date 14. Mrz. 01 Page UE1 of UE1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : UF 04.04.97 U Structures UF Structures for the handling of nuclear equipment UFA Fuel pool building UFB Fuel handling building UFC Fuel storage building UFJ Structure for hot cell UFX Special structure (plant-specific) UFY Bridge structure UFZ Ducting structure Printout date 14. Mrz. 01 Page UF1 of UF1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : UG 04.04.97 U Structures UG Structures for water supply and disposal UGA Structure for raw water supply UGD Structure for demineralization system UGE Structure for neutralization system UGF Structure for fire water supply UGG Structure for drinking water supply UGH Structure for rainwater UGJ Structure for cooling tower make-up water treatment UGK Flocculant mixing chamber UGL Flocculator structure, flocculator UGN Treated water basin UGP Sludge thickener UGQ Sludge dewatering building UGR Sludge storage structure UGU Structure for effluent disposal UGV Structure for sewerage plant UGX Special structure (plant-specific) UGY Bridge structure UGZ Ducting structure Printout date 14. Mrz. 01 Page UG1 of UG1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : UH 04.04.97 U Structures UH Structures for conventional heat generation UHA Steam generator enclosure, steam generator building (boiler house) UHF Bunker bay UHL Structure for boiler compressed air supply UHN Smoke stack, incl. structure for flue gas circulation (e. g. for induced draft fan) UHQ Structure for flue gas filtering system UHU Structure for flue gas reheating system UHV Structure for combustion air circulation (e. g. for forced draft fan) UHW Boiler blowdown structure UHX Special structure (plant-specific) UHY Bridge structure UHZ Ducting structure Printout date 14. Mrz. 01 Page UH1 of UH1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : UJ 04.04.97 U Structures UJ Structures for nuclear heat generation UJA Reactor building, containment interior (when separate from *UJB*) UJB Reactor building annulus (when separate from *UJA*) UJC Heat exchanger building (not for light water reactors) UJD Steam generator building (not for light water reactors) UJE Main steam and feedwater valve compartment UJF Equipment air lock enclosure UJG Gantry (reactor building) UJX Special structure (plant-specific) UJY Bridge structure UJZ Ducting structure Printout date 14. Mrz. 01 Page UJ1 of UJ1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : UK 04.04.97 U Structures UK Structures for reactor auxiliary systems UKA Reactor auxiliary building UKB Reactor ancillary systems building (e. g. for BWR plants) UKC Nuclear services building (not for light water reactors) UKD Emergency standby structure (not for light water reactors) UKH Structure for air exhaust (vent stack) UKJ Tritium extraction system building UKS Radioactive waste processing building UKT Structure for radioactive waste storage UKX Special structure (plant-specific) UKY Bridge structure UKZ Ducting structure Printout date 14. Mrz. 01 Page UK1 of UK1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : UL 04.04.97 U Structures UL Structures for steam-, water-, gas-cycles ULA Feedwater pump house ULB Emergency feed building ULC Structure for condensate system ULD Structure for condensate polishing plant (if separate) ULE Structure for emergency supply systems (if separate) ULN Structure for hydroelectric power plant water impounding works ULP Structure for hydroelectric power plant intake systems ULQ Structure for hydroelectric power plant tail-race systems ULX Special structure (plant-specific) ULY Bridge structure ULZ Ducting structure Printout date 14. Mrz. 01 Page UL1 of UL1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : UM 04.04.97 U Structures UM Structures for main machine sets UMA Steam turbine building UMB Gas turbine building UMC Gas and steam turbine building (tandem arrangement) UME Hydraulic turbine building UMG Pumped storage turbine building UMJ Diesel engine building UMM Compressor system building UMR Gas engine plant building UMX Special structure (plant-specific) UMY Bridge structure UMZ Ducting structure Printout date 14. Mrz. 01 Page UM1 of UM1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : UN 04.04.97 U Structures UN Structures for process energy supply UNX Special structure (plant-specific) UNY Bridge structure UNZ Ducting structure Printout date 14. Mrz. 01 Page UN1 of UN1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : UP 04.04.97 U Structures UP Structures for circulating (cooling) water systems (e. g. circulating water intake) UPA Circulating (cooling) water intake culvert UPB Service (secondary cooling) water intake culvert UPC Circulating (cooling) water intake structure UPD Service (secondary cooling) water intake structure UPH Circulating (cooling) water treatment structure UPJ Service (secondary cooling) water treatment structure UPN Circulating (cooling) water inlet culvert UPP Service (secondary cooling) water inlet culvert UPQ Biocide treatment building UPS Debris trough UPT Screen wash water cleaning structure UPX Special structure (plant-specific) UPY Bridge structure UPZ Ducting structure Printout date 14. Mrz. 01 Page UP1 of UP1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : UQ 04.04.97 U Structures UQ Structures for circulating (cooling) water systems (e. g. circulating water pumps and outfall) UQA Circulating (cooling) water pump building UQB Service (secondary cooling) water pump building UQG Circulating (cooling) water overflow structure, surge tank UQH Screen wash water discharge culvert UQJ Circulating (cooling) water seal pit, incl. circulating (cooling) water aeration structure UQK Circulating (cooling) water venting structure UQL Service (secondary cooling) water surge pond UQM Service (secondary cooling) water collecting pond UQN Circulating (cooling) water outfall culvert UQP Service (secondary cooling) water outfall culvert UQQ Circulating (cooling) water outfall structure UQR Service (secondary cooling) water outfall structure UQS Circulating (cooling) water discharge culvert UQT Service (secondary cooling) water discharge culvert UQU Circulating (cooling) water spillway structure, incl. circulating (cooling) water aeration structure UQV Structure for artificial circulating (cooling) water aeration UQW Routing structure for circulating (cooling) water discharge UQX Special structure (plant-specific) UQY Bridge structure UQZ Ducting structure Printout date 14. Mrz. 01 Page UQ1 of UQ1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : UR 04.04.97 U Structures UR Structures for circulating (cooling) water systems (e. g. recirculation cooling) URA Cooling tower structure (circulating/main cooling water) URB Cooling tower structure (service/secondary cooling water) URD Cooling tower pump building (circulating/main cooling water) URE Cooling tower pump building (service/secondary cooling water) URG Cooling tower connecting structure URH Cooling tower outlet structure URJ Cooling tower outfall culvert URK Cooling tower return structure URL Cooling tower return culvert URM Circulating (cooling) water distribution building URN Cooling tower bypass structure URP Cooling tower blowdown structure URQ Cooling tower blowdown culvert URX Special structure (plant-specific) URY Bridge structure URZ Ducting structure Printout date 14. Mrz. 01 Page UR1 of UR1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : US 04.04.97 U Structures US Structures for ancillary systems USA Structure for heating, ventilation, air-conditioning (HVAC) systems USB Structure for space heating systems USC Structure for stationary compressed air supply system USG Fire pump house USH Structure for waterway facilities USR Structure for conventional waste treatment UST Workshop and stores building USU Consumables storage building USV Laboratory building USX Special structure (plant-specific) USY Bridge structure USZ Ducting structure Printout date 14. Mrz. 01 Page US1 of US1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : UT 04.04.97 U Structures UT Structures for auxiliary systems UTA Supply systems building UTB Central water chiller building, conventional area UTC Central water chiller building, nuclear area UTF Compressed air system building UTG Central gas supply systems building (no fuel supply) UTH Auxiliary steam generator building UTJ Smoke stack UTS Chemical storage tank pit UTX Special structure (plant-specific) UTY Bridge structure UTZ Ducting structure Printout date 14. Mrz. 01 Page UT1 of UT1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : UU 04.04.97 U Structures UU Shaft structures Printout date 14. Mrz. 01 Page UU1 of UU1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : UV 04.04.97 U Structures UV Structures for chemical flue gas treatment incl. residues removal (for *HR.*, *HS.*, *HT.*) UVA Structure for flue gas-side heat exchanger UVB Structure for flue gas fan system UVC Structure for flue gas scrubber, reactor UVD Structure for adsorbent/absorbent circuit UVE Structure for reagent supply, incl. preparation/treatment, storage, forwarding UVF Structure for thickening and solids dewatering, solids drying and compacting system UVG Structure for chemical flue gas treatment UVH Structure for (solids/product) forwarding, storage, loading UVM Structure for catalyst handling and storage UVX Special structure (plant-specific) UVY Bridge structure UVZ Ducting structure Printout date 14. Mrz. 01 Page UV1 of UV1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : UX 04.04.97 U Structures UX Structures for external systems (power plant-specific) UXA Structure for seawater desalination plant UXX Special structure (plant-specific) UXY Bridge structure UXZ Ducting structure Printout date 14. Mrz. 01 Page UX1 of UX1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : UY 04.04.97 U Structures UY General service structures UYA Office and staff amenities building UYB Staff amenities building UYC Administration building UYD Canteen UYE Gate house UYF Security gate house UYG Information center UYH Training facilities UYJ Medical center UYN Railway engine shed UYP Fire station UYQ Garage UYR Automobile workshop UYS Filling station UYX Special structure (plant-specific) UYY Bridge structure UYZ Ducting structure Printout date 14. Mrz. 01 Page UY1 of UY1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : UZ 04.04.97 U Structures UZ Structures for transport, traffic, fencing, gardens and other purposes UZA Works roadways, paths, incl. associated structures UZC Yards UZD Parking areas, incl. associated structures UZE Railway structures UZF Lifting gear structures UZJ Fencing and gates UZK Gardens, incl. structures UZL Noise abatement structures UZM Protective structures against external impact (EI) UZN Structure for flood protection UZP Structure for bank/shoreline stabilization UZQ Structure for river regulation UZR Jetty, quay UZS Breakwaters UZT Outdoor area, plots of land and land rights UZU Site security structure UZW Residential buildings, residential area UZX Special structure (plant-specific), scrap yard UZY Bridge structure UZZ Ducting structure Printout date 14. Mrz. 01 Page UZ1 of UZ1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : W 04.04.97 W Renewable energy plants WA Solar system (for coordinates) WB Solar system (for coordinates) WC Solar system (for coordinates) WD Solar system (for coordinates) WE Solar system (for coordinates) WF Solar system (for coordinates) WG Solar system (for coordinates) WH Solar system (for coordinates) WJ Solar system (for coordinates) WK Solar system (for coordinates) WL Solar system (for coordinates) WM Solar system (for coordinates) WN Solar system (for coordinates) WP Solar system (for coordinates) WQ Solar system (for coordinates) WR Solar system (for coordinates) WS Solar system (for coordinates) WT Solar heating system WV Lubricant supply system WW Sealing fluid supply system WX Fluid supply system for control and protection equipment WY Control and protection equipment Printout date 14. Mrz. 01 Page W1 of W1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : WT 04.04.97 W Renewable energy plants WT Solar heating system WTA Solar heating system WTB Solar heating system WTC Solar heating system WTD Solar heating system WTE Solar heating system WTF Solar heating system WTG Solar heating system WTH Solar heating system WTJ Solar heating system WTK Solar heating system WTL Solar heating system WTM Solar heating system WTN Solar heating system WTP Solar heating system WTQ Solar heating system WTR Solar heating system WTS Solar heating system WTT Solar heating system WTU Solar heating system WTX Fluid supply system for control and protection equipment WTY Control and protection equipment Printout date 14. Mrz. 01 Page WT1 of WT1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : WV 04.04.97 W Renewable energy plants WV Lubricant supply system WVA Lubricant supply system WVB Lubricant supply system WVC Lubricant supply system WVD Lubricant supply system WVE Lubricant supply system WVF Lubricant supply system WVG Lubricant supply system WVH Lubricant supply system WVJ Lubricant supply system WVK Lubricant supply system WVL Lubricant supply system WVM Lubricant supply system WVN Lubricant supply system WVP Lubricant supply system WVQ Lubricant supply system WVR Lubricant supply system WVS Lubricant supply system WVT Lubricant supply system WVU Lubricant supply system Printout date 14. Mrz. 01 Page WV1 of WV1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : WW 04.04.97 W Renewable energy plants WW Sealing fluid supply system WWA Sealing fluid supply system WWB Sealing fluid supply system WWC Sealing fluid supply system WWD Sealing fluid supply system WWE Sealing fluid supply system WWF Sealing fluid supply system WWG Sealing fluid supply system WWH Sealing fluid supply system WWJ Sealing fluid supply system WWK Sealing fluid supply system WWL Sealing fluid supply system WWM Sealing fluid supply system WWN Sealing fluid supply system WWP Sealing fluid supply system WWQ Sealing fluid supply system WWR Sealing fluid supply system WWS Sealing fluid supply system WWT Sealing fluid supply system WWU Sealing fluid supply system Printout date 14. Mrz. 01 Page WW1 of WW1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : WX 04.04.97 W Renewable energy plants WX Fluid supply system for control and protection equipment WXA Fluid supply system for control and protection equipment WXB Fluid supply system for control and protection equipment WXC Fluid supply system for control and protection equipment WXD Fluid supply system for control and protection equipment WXE Fluid supply system for control and protection equipment WXF Fluid supply system for control and protection equipment WXG Fluid supply system for control and protection equipment WXH Fluid supply system for control and protection equipment WXJ Fluid supply system for control and protection equipment WXK Fluid supply system for control and protection equipment WXL Fluid supply system for control and protection equipment WXM Fluid supply system for control and protection equipment WXN Fluid supply system for control and protection equipment WXP Fluid supply system for control and protection equipment WXQ Fluid supply system for control and protection equipment WXR Fluid supply system for control and protection equipment WXS Fluid supply system for control and protection equipment WXT Fluid supply system for control and protection equipment WXU Fluid supply system for control and protection equipment Printout date 14. Mrz. 01 Page WX1 of WX1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : WY 04.04.97 W Renewable energy plants WY Control and protection equipment WYA Control and protection equipment WYB Control and protection equipment WYC Control and protection equipment WYD Control and protection equipment WYE Control and protection equipment WYF Control and protection equipment WYG Control and protection equipment WYH Control and protection equipment WYJ Control and protection equipment WYK Control and protection equipment WYL Control and protection equipment WYM Control and protection equipment WYN Control and protection equipment WYP Control and protection equipment WYQ Control and protection equipment WYR Control and protection equipment WYS Control and protection equipment WYT Control and protection equipment WYU Control and protection equipment Printout date 14. Mrz. 01 Page WY1 of WY1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : X 04.04.97 X Heavy machinery (not main machine sets) XA Steam turbuine plant XB Gas turbine plant XE Hydraulic turbine plant XG Pumped-storage plant XJ Diesel engine plant XK Generator plant XL Electro-motive plant (incl. motor generator) XP Common installations for heavy machinery XR Gas engine plant XV Lubricant supply system XW Sealing fluid supply system XX Fluid supply system for control and protection equipment XY Control and protection equipment Printout date 14. Mrz. 01 a Page X1 of X1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : XA 04.04.97 X Heavy machinery (not main machine sets) XA Steam turbuine plant XAA HP turbine Limit: from incl. steam admission (main stop valve) or combined main stop and control valve to incl. automatic/non-automatic extraction and exhaust nozzles and to incl. the interfaces with other turbine internal systems XAB IP turbine Limit: from incl. crossover line, incl. control element or from incl. intercept valve to incl. automatic/non-automatic extraction and exhaust nozzles and to incl. the interfaces with other turbine internal systems XAC LP turbine Limit: from incl. crossover line, incl. control element or from incl. intercept valve or steam inlet nozzle (in reheat system without intercept valve) to incl. automatic/non-automatic extraction and exhaust nozzles and to incl. the interfaces with other turbine XAD Bearings XAG Condensing system Limit: from incl. condenser neck or inlet nozzle to incl. condenser outlet nozzle, incl. connected flash tanks, incl. instrumentation equipment associated with condenser XAH Motive water system (if separate from *XAJ*) Limit: from excl. outlet of other system to excl. water-operated air ejector inlet XAJ Air removal system Limit: from excl. condenser outlet to excl. atmosphere XAK Transmission gear between prime mover and driven machine, incl. turning gear XAL Drain and vent systems Limit: from incl. collector point or from incl. final drain to excl. discharge into other system XAM Leak-off steam system Limit: from excl. branch from seal leak-off to excl. discharge into other system XAN Turbine bypass station, incl. desuperheating spray system Limit: from incl. bypass valve and from incl. desuperheating spray valve to incl. steam inlet to condenser XAP LP turbine bypass Limit: from excl. bypass valve and from excl. branch off steam system to excl. condenser Printout date 14. Mrz. 01 Page XA1 of XA2 Siemens 2 nd complete, non-project related edition Condition-Date: XAQ KKS Identification System for Power Plants Function key : XA 04.04.97 Vent system (if separate from *XAL*) Limit: from incl. venting point to excl. discharge into other system XAV Lubricant supply system Limit: from incl. dedicated lubricant tank or common lubricant and control fluid tank or from excl. branch off lubricant fluid supply system to excl. user and from excl. user XAW Sealing, heating and cooling steam system Limit: from excl. branch to excl. casing nozzle of steam user and leak-off to excl. condenser or to incl. gland steam condenser or to excl. heating/cooling steam user XAX Non-electric control and protection equipment, incl. fluid supply system XAY Electrical control and protection equipment Printout date 14. Mrz. 01 Page XA2 of XA2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : XB 04.04.97 X Heavy machinery (not main machine sets) XB Gas turbine plant XBA Turbine, compressor rotor with common casing Limit: from incl. compressor inlet to incl. compressor outlet from incl. turbine inlet to incl. turbine outlet, incl. exhaust gas diffuser XBB Turbine casing and rotor Limit: from incl. turbine inlet to incl. turbine outlet, incl. exhaust gas diffuser XBC Compressor casing and rotor Limit: from incl. compressor inlet to incl. compressor outlet XBD Bearings XBH Cooling and sealing gas system Limit: from incl. extraction point to excl. user and from excl. user, incl. leak-off to incl. inlet to other system XBJ Start-up unit XBK Transmission gear between prime mover and driven machine, incl. turning gear, barring gear XBL Intake air, cold gas system (open cycle) Limit: from excl. atmosphere to excl. combustion chamber or to excl. compressor inlet or to incl. exhaust gas heat exchanger, excl. compressor XBM Combustion chamber (gas heating, combustion) Limit: from incl. cold gas, fuel inlet to incl. hot gas outlet XBN Fuel supply system (liquid) Limit: from excl. branch off main supply line or from incl. temporary (day) tank to excl. combustion chamber or to excl. motive gas generating unit, incl. fuel return system XBP Fuel supply system (gaseous) Limit: from excl. branch off main supply line to excl. combustion chamber or to excl. motive gas generating unit XBQ Ignition fuel supply system (if separate) Limit: from excl. branch off main supply line or from incl. storage tank to excl. combustion chamber or to excl. motive gas generating unit XBR Exhaust gas system (open cycle) Limit: from excl. combustion chamber or from excl. exhaust gas diffuser to excl. discharge into atmosphere, excl. turbine, or to excl. inlet to other system (e. g. combustion air system) Printout date 14. Mrz. 01 Page XB1 of XB2 Siemens 2 nd complete, non-project related edition Condition-Date: XBS KKS Identification System for Power Plants Function key : XB 04.04.97 Storage system Limit: to excl. connection to main system and from excl. connection to main system XBT Motive gas generator unit, incl. combustion chamber Limit: from incl. air/fuel inlet to incl. motive gas outlet of motive gas generating unit XBU Additive system Limit: from incl. supply to incl. injection XBV Lubricant supply system Limit: from incl. dedicated lubricant tank or common lubricant and control fluid tank or from excl. branch off control fluid supply system to excl. user and from excl. user XBW Seal oil supply Limit: from incl. dedicated sealing oil tank or from excl. sealing oil pump suction line to excl. user and from excl. user XBX Non-electric control and protection equipment, incl. fluid supply system XBY Electrical control and protection equipment XBZ Lubricant and control fluid treatment system Printout date 14. Mrz. 01 Page XB2 of XB2 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : XE 04.04.97 X Heavy machinery (not main machine sets) XE Hydraulic turbine plant XEA Turbine (casing, shaft, runner, draft tube etc.) Limit: from excl. turbine inlet or from excl. isolating valve to incl. turbine outlet or to excl. isolating valve XEB Isolating valve Task: to isolate headwater from turbine *XEA* and/or to control headwater flow to turbine *XEA* XED Bearings XEG Stabilizing air system Limit: from incl. air compressor to incl. outlet to turbine XEK Transmission gear between prime mover and driven machine XEL Water depression air supply system Limit: from incl. air compressor to incl. outlet to turbine XES Shaft gland cooling water system XEV Lubricant supply system Limit: from incl. lubricant tank to excl. user and from excl. user XEW Sealing water supply system Limit: from incl. sealing water supply main isolating valve to excl. casing nozzle of sealing water user XEX Non-electric control and protection equipment, incl. fluid supply system XEY Electrical control and protection equipment Printout date 14. Mrz. 01 Page XE1 of XE1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : XG 31.07.98 X Heavy machinery (not main machine sets) XG Pumped-storage plant a XGA Storage pump (casing, shaft, runner etc.) a Limit: from excl. storage pump inlet or from excl. isolating valve to incl. storage pump outlet or to excl. isolating valve XGB Isolating valve a Task: to isolate water from storage pump *XGA* and/or to control water flow to storage pump *XGA* XGD Bearings a XGK Transmission gear between motor generator set and storage pump a XGL Water depression air supply system a Limit: from incl. air compressor to incl. inlet to storage pump XGM Start-up unit a XGS Shaft gland cooling water system a XGV Lubricant supply system a Limit: from incl. lubricant tank to excl. user and from excl. user XGW Sealing water supply system a Limit: from incl. sealing water supply main isolating valve to excl. casing nozzle of sealing water user XGX Non-electric control and protection equipment, incl. fluid supply system a XGY Electrical control and protection equipment a Printout date 19. Mrz. 01 Page XG1 of XG1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : XJ 04.04.97 X Heavy machinery (not main machine sets) XJ Diesel engine plant XJA Engine Limit: from incl. fuel injection nozzle inlet or from incl. air intake nozzles or from incl. cooling water inlet nozzles to incl. exhaust nozzle outlet or to incl. cooling water nozzle outlet, incl. engine-internal systems XJB Turbocharger, blower Limit: from incl. turbocharger or blower inlet to incl. turbocharger or blower outlet XJG Liquid cooling system Limit: from excl. engine cooling water nozzle outlet or from incl. turbocharger air cooling system inlet to excl. engine cooling water nozzle inlet or to incl. turbocharger air cooler outlet XJH Air intercooling system Limit: from incl. intercooler inlet to incl. intercooler outlet to excl. outlet to other cooling systems XJK Transmission gear between prime mover and driven machine XJN Fuel systems Limit: from incl. temporary (day) tank or from excl. branch off piping system to excl. fuel injection nozzle inlet XJP Start-up unit, (incl. flywheel) XJQ Air intake system Limit: from excl. atmosphere to excl. turbocharger or to excl. engine air intake nozzles XJR Exhaust gas system Limit: from excl. engine exhaust nozzle outlet to excl. discharge to atmosphere XJV Lubricant supply system Limit: from incl. dedicated lubricant tank or common lubricant and control fluid tank or from excl. branch off control fluid supply system to excl. user and from excl. user XJW Sealing fluid supply system XJX Fluid supply system for control and protection equipment XJY Control and protection equipment Printout date 14. Mrz. 01 Page XJ1 of XJ1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : XK 04.04.97 X Heavy machinery (not main machine sets) XK Generator plant XKA Generator frame, incl. stator, rotor and all integral cooling equipment Limit: to incl. generator bushing XKB Generator exciter set, including set with electrical braking system (use only if *XKC* is not sufficient for identification) XKC Generator exciter set, including set with electrical braking system XKD Bearings XKF Stator/rotor liquid cooling system, incl. coolant supply system Hint: for cooling oil see *XKU* Limit: from excl. stator/rotor outlet to excl. stator/rotor inlet Task: dissipate heat produced by stator/rotor to liquid coolant XKG Stator/rotor hydrogen (H2) cooling system, incl. coolant supply system a Hint: for nitrogen / carbon dioxyde cooling see *XKH* Limit: from excl. stator/rotor outlet to excl. stator/rotor inlet Task: dissipate heat produced by stator/rotor to hydrogen coolant XKH Stator/rotor nitrogen (N2) / carbon dioxyde (CO2) cooling system, incl. coolant supply system a Hint: for other gas cooling see *XKG* Limit: from excl. stator/rotor outlet to excl. stator/rotor inlet Task: dissipate heat produced by stator/rotor to nitrogen / carbon dioxyde coolant XKJ Stator/rotor air cooling system, incl. coolant supply system Hint: for other gas cooling see *XKG* and *XKH* Limit: from excl. stator/rotor outlet to excl. stator/rotor inlet Task: dissipate heat produced by stator/rotor to air coolant XKQ Exhaust gas system (if separate from *XKG* and *XKH*) XKU Stator/rotor cooling oil cooling system, incl. coolant supply system Hint: for other liquid cooling see *XKF* Limit: from excl. stator/rotor outlet to excl. stator/rotor inlet Task: dissipate heat produced by stator/rotor to cooling oil coolant XKV Lubricant supply system (if separate system for generator) XKW Sealing oil system, incl. supply and treatment Limit: from excl. branch off sealing oil supply system to excl. stator inlet and from excl. stator outlet to excl. inlet to other system or in closed systems from excl. stator outlet to excl. stator inlet XKX Fluid supply system for control and protection equipment XKY Control and protection equipment Printout date 14. Mrz. 01 Page XK1 of XK1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : XL 04.04.97 X Heavy machinery (not main machine sets) XL Electro-motive plant (incl. motor generator) XLA Motor frame, motor generator frame, incl. stator, rotor and all integral cooling equipment Limit: to incl. motor or generator bushing XLC Exciter set XLD Bearings XLF Stator/rotor liquid cooling system, incl. coolant supply system Hint: for cooling oil see *XLU* Limit: from excl. stator/rotor outlet to excl. stator/rotor inlet Task: dissipate heat produced by stator/rotor to coolant XLG Stator/rotor gas cooling system, incl. coolant supply system Hint: for nitrogen cooling see *XLH* Limit: from excl. stator/rotor outlet to excl. stator/rotor inlet Task: dissipate heat produced by stator/rotor to coolant XLH Stator/rotor nitrogen cooling system, incl. coolant supply system Hint: for other gas cooling see *XLG* Limit: from excl. stator/rotor outlet to excl. stator/rotor inlet Task: dissipate heat produced by stator/rotor to coolant XLQ Exhaust gas system (if separate from *XLG* and *XLH*) XLU Stator/rotor cooling oil cooling system, incl. coolant supply system Hint: for other liquid cooling see *XLF* Limit: from excl. stator/rotor outlet to excl. stator/rotor inlet Task: dissipate heat produced by stator/rotor to coolant XLV Lubricant supply system (if separate system for electro-motive units) XLW Sealing oil system, incl. supply and treatment Limit: from excl. branch off sealing oil supply system to excl. stator inlet and from excl. stator outlet to excl. inlet to other system or in closed systems from excl. stator outlet to excl. stator inlet XLX Fluid supply system for control and protection equipment XLY Control and protection equipment Printout date 14. Mrz. 01 Page XL1 of XL1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : XP 04.04.97 X Heavy machinery (not main machine sets) XP Common installations for heavy machinery XPA Foundations XPB Sheating XPG Frame, support structure XPR Forced cooling system XPS Drying and layup system Printout date 14. Mrz. 01 Page XP1 of XP1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : XR 04.04.97 X Heavy machinery (not main machine sets) XR Gas engine plant XRA Gas engine plant XRB Gas engine plant XRC Gas engine plant XRD Gas engine plant XRE Gas engine plant XRF Gas engine plant XRG Gas engine plant XRH Gas engine plant XRJ Gas engine plant XRK Gas engine plant XRL Gas engine plant XRM Gas engine plant XRN Gas engine plant XRP Gas engine plant XRQ Gas engine plant XRR Gas engine plant XRS Gas engine plant XRT Gas engine plant XRU Gas engine plant XRV Lubricant supply system XRW Sealing fluid supply system XRX Fluid supply system for control and protection equipment XRY Control and protection equipment Printout date 14. Mrz. 01 Page XR1 of XR1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : XV 04.04.97 X Heavy machinery (not main machine sets) XV Lubricant supply system XVA Lubricant supply system XVB Lubricant supply system XVC Lubricant supply system XVD Lubricant supply system XVE Lubricant supply system XVF Lubricant supply system XVG Lubricant supply system XVH Lubricant supply system XVJ Lubricant supply system XVK Lubricant supply system XVL Lubricant supply system XVM Lubricant supply system XVN Lubricant supply system XVP Lubricant supply system XVQ Lubricant supply system XVR Lubricant supply system XVS Lubricant supply system XVT Lubricant supply system XVU Lubricant supply system Printout date 14. Mrz. 01 Page XV1 of XV1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : XW 04.04.97 X Heavy machinery (not main machine sets) XW Sealing fluid supply system XWA Sealing fluid supply system XWB Sealing fluid supply system XWC Sealing fluid supply system XWD Sealing fluid supply system XWE Sealing fluid supply system XWF Sealing fluid supply system XWG Sealing fluid supply system XWH Sealing fluid supply system XWJ Sealing fluid supply system XWK Sealing fluid supply system XWL Sealing fluid supply system XWM Sealing fluid supply system XWN Sealing fluid supply system XWP Sealing fluid supply system XWQ Sealing fluid supply system XWR Sealing fluid supply system XWS Sealing fluid supply system XWT Sealing fluid supply system XWU Sealing fluid supply system Printout date 14. Mrz. 01 Page XW1 of XW1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : XX 04.04.97 X Heavy machinery (not main machine sets) XX Fluid supply system for control and protection equipment XXA Fluid supply system for control and protection equipment XXB Fluid supply system for control and protection equipment XXC Fluid supply system for control and protection equipment XXD Fluid supply system for control and protection equipment XXE Fluid supply system for control and protection equipment XXF Fluid supply system for control and protection equipment XXG Fluid supply system for control and protection equipment XXH Fluid supply system for control and protection equipment XXJ Fluid supply system for control and protection equipment XXK Fluid supply system for control and protection equipment XXL Fluid supply system for control and protection equipment XXM Fluid supply system for control and protection equipment XXN Fluid supply system for control and protection equipment XXP Fluid supply system for control and protection equipment XXQ Fluid supply system for control and protection equipment XXR Fluid supply system for control and protection equipment XXS Fluid supply system for control and protection equipment XXT Fluid supply system for control and protection equipment XXU Fluid supply system for control and protection equipment Printout date 14. Mrz. 01 Page XX1 of XX1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Function key : XY 04.04.97 X Heavy machinery (not main machine sets) XY Control and protection equipment XYA Control and protection equipment XYB Control and protection equipment XYC Control and protection equipment XYD Control and protection equipment XYE Control and protection equipment XYF Control and protection equipment XYG Control and protection equipment XYH Control and protection equipment XYJ Control and protection equipment XYK Control and protection equipment XYL Control and protection equipment XYM Control and protection equipment XYN Control and protection equipment XYP Control and protection equipment XYQ Control and protection equipment XYR Control and protection equipment XYS Control and protection equipment XYT Control and protection equipment XYU Control and protection equipment Printout date 14. Mrz. 01 Page XY1 of XY1 Siemens 2 nd complete, non-project related edition Condition-Date: Z KKS Identification System for Power Plants Function key : Z 04.04.97 Workshop and office equipment Printout date 14. Mrz. 01 Page Z1 of Z1 Siemens 2 nd complete, non-project related edition Identification System for Power Plants General view Equipment unit key Condition-Date: 04.04.97 A Mechanical equipment B Mechanical equipment C Direct measuring circuits D Closed loop control circuits E Analog and binary signal conditioning F Indirect measuring circuits (gated, corrected, suppressed, calculated) G Electrical equipment H Subassemblies of main and heavy machinery J Nuclear assemblies Printout date: 12. Sep. 01 Page 1 of 1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Equipment unit key 04.04.97 A Mechanical equipment AA Valves, dampers, etc., incl. actuators, also manual, rupture disk equipment AB Isolating elements, air locks AC Heat exchangers, heat transfer surfaces AE Turning, driving, lifting and slewing gear (also manipulators) AF Continuous conveyors, feeders (escalators) AG Generator units AH Heating, cooling and air conditioning units AJ Size reduction equipment, only as part of process AK Compacting and packaging equipment, only as part of process AM Mixers, agitators AN Compressor units, fans AP Pump units AS Adjusting and tensioning equipment for non-electrical variables AT Cleaning, drying, filtering and separating equipment, excl. *BT* AU Braking, gearbox, coupling equipment, non-electrical converters AV Combustion equipment AW Stationary tooling, treatment equipment AX Test and monitoring equipment for plant maintenance Printout date 14. Mrz. 01 Page 1 of 9 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Equipment unit key 04.04.97 B Mechanical equipment BB Storage equipment (vessels, tanks) BE Shafts (for erection and maintenance only) BF Foundations BN Jet pumps, ejectors, injectors BP Flow restrictors, limiters, orifices (not metering orifices) BQ Hangers, supports, racks, piping penetrations BR Piping, ductwork, chutes BS Silencers BT Flue gas catalytic converter modules BU Insulation, sheathing Printout date 14. Mrz. 01 Page 2 of 9 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Equipment unit key 04.04.97 C Direct measuring circuits CB Radiation variables, e. g. thermal radiation, flame monitoring (other than *CR* and *CQ*) CD Density CE Electrical variables (e. g. current, voltage, power, electr. frequency) CF Flow, rate CG Distance, length, position, direction of rotation CH Manual input (as manually operated sensor) (e. g. fire detector) CJ Power (mechanical, thermal) CK Time CL Level (also for dividing line) CM Moisture, humidity CP Pressure CQ Quality variables (analysis, material properties other than *CD*, *CM*, *CV*) CR Radiation variables CS Velocity, speed, frequency (mechanical), acceleration CT Temperature CU Combined and other variables CV Viscosity CW Weight, mass CY Vibration, expansion Printout date 14. Mrz. 01 Page 3 of 9 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Equipment unit key 04.04.97 D Closed loop control circuits DB Radiation variables, e. g. thermal radiation, flame monitoring (other than *DR* and *DQ*) DD Density DE Electrical variables (e. g. current, voltage, power, electr. frequency) DF Flow, rate DG Distance, length, position, direction of rotation DJ Power (mechanical, thermal) DK Time DL Level (also for dividing line) DM Moisture, humidity DP Pressure DQ Quality variables (analysis, material properties other than *DD*, *DM*, *DV*) DR Radiation variables DS Velocity, speed, frequency (mechanical), acceleration DT Temperature DU Combined and other variables DV Viscosity DW Weight, mass DY Vibration, expansion Printout date 14. Mrz. 01 Page 4 of 9 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Equipment unit key 04.04.97 E Analog and binary signal conditioning EA Open loop control, unit control EB Open loop control, group control EC Open loop control, subgroup control EE Open loop control, subloop control, equipment unit changeover EG Alarm, annunciation, alarm logics EH Alarm, annunciation, hard-wired alarm annunciation system EJ Alarm, annunciation, visualization of operation and monitoring displays EK Alarm, annunciation, alarm logics EM Process computer, access control EN Process computer, status-display computer, criterion display EP Process computer, supervisory computer EQ Process computer, internal automation (signal processing) ES Process computer, internal automation (signal conditioning) EU Combined analog and binary signal conditioning EV Signal transmission, bus coupling EY Protection, protective logics, priority, non-equipment-unit-related EZ Protection, equipment unit protection (superordinate equipment unit protection) Printout date 14. Mrz. 01 Page 5 of 9 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Equipment unit key 04.04.97 F Indirect measuring circuits (gated, corrected, suppressed, calculated) FB Radiation variables, e. g. thermal radiation, flame monitoring (other than *FR* and *FQ*) FD Density FE Electrical variables (e. g. electr. efficiency, power) FF Flow, rate FG Distance, length, position, direction of rotation FJ Power (mechanical, thermal) FK Time FL Level (also for dividing line) FM Moisture, humidity FP Pressure FQ Quality variables (analysis, material properties other than *FD*, *FM*, *FV*) FR Radiation variables FS Velocity, speed, frequency (mechanical), acceleration FT Temperature FU Combined and other variables FV Viscosity FW Weight, mass FY Vibration, expansion Printout date 14. Mrz. 01 Page 6 of 9 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Equipment unit key 04.04.97 G Electrical equipment GA Junction boxes for analog measured data GB Junction boxes for binary signals GC Junction boxes for analog safety I&C (SILT) measured data GD Junction boxes for power cables > 1 kV GE Junction boxes for power cables < 1 kV GF Junction boxes for operational I&C (BELT) measured data GG Junction boxes for thermocouples GH Electrical and instrumentation and control installation units (e. g. cubicles, boxes) GJ Processing and storage equipment for process computers and automation systems (automation equipment and servers, etc.) GK Information display and operator control equipment for process computers and automation systems (keyboards, monitors, printers) GM Junction boxes for light-current systems of national telecommunications services GN Networking equipment (bus couplers and optic transceivers, etc.) GP Subdistribution/junction boxes for lighting GQ Subdistribution/junction boxes for power sockets GR DC generating equipment, batteries GS Switchgear equipment if not identified under process equipment GT Transformer equipment GU Converter equipment GV Structure-related earthing and lightning protection equipment, surge arrestors GW Cabinet power supply equipment GX Actuating equipment for electrical variables GY Junction boxes for light-current systems (not of national telecommunications services) GZ Hangers, supports and racks for electrical and instrumentation and control equipment Printout date 14. Mrz. 01 Page 7 of 9 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Equipment unit key 04.04.97 H Subassemblies of main and heavy machinery HA Machine stationary assembly HB Machine rotating assembly HD Bearing assembly Printout date 14. Mrz. 01 Page 8 of 9 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Equipment unit key 04.04.97 J Nuclear assemblies JA Absorber assemblies JB Fuel assemblies (also includes block-type, cluster-type and spherical fuel elements) JC Breeder assemblies JD Flow restrictors (assemblies) JE Burnable absorber assemblies JF Reflector assemblies JG Plenum assemblies JM Moderator assemblies JN Neutron sources JS Shielding equipment JZ Special assemblies Printout date 14. Mrz. 01 Page 9 of 9 Siemens 2 nd complete, non-project related edition Identification System for Power Plants General view Component key Condition-Date: 04.04.97 - Electrical components K Mechanical components M Mechanical components Q Instrumentation and control components (non-electrical) X Signal origins Y Signal applications Printout date: 12. Sep. 01 Page 1 of 1 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Component key 04.04.97 - Electrical components -A Assemblies and subassemblies -B Transducers for non-electrical to electrical variables and vice-versa -C Capacitors -D Binary elements, delay devices, memory devices -E Special components -F Protective devices -G Generators, power supplies -H Signalling devices -K Relays, contactors -L Inductors -M Motors -N Amplifiers, controllers -P Measuring instruments, testing equipment -Q Power switchgear -R Resistors -S Switches, selectors -T Transformers -U Modulators, convertors from electrical to other electrical variables -V Tubes, semiconductors -W Transmission paths, waveguides, aerials -X Terminals, plugs, sockets -Y Electrical positioners, e. g. solenoids (not motors) -Z Terminations, balancing equipment, filters, limiters, cable terminations, equalizers, hybrid transformers Printout date 14. Mrz. 01 Page 1 of 6 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Component key 04.04.97 K Mechanical components KA Gate valves, globe valves, dampers, cocks, rupture disks, orifices KB Gates, doors, dam boards KC Heat exchangers, coolers KD Vessels/tanks, pools, surge tanks (fluid systems) KE Turning, driving, lifting and slewing gear KF Continuous conveyors, feeders KJ Size reduction machines KK Compacting, packaging machines KM Mixers, agitators KN Compressors, blowers, fans KP Pumps KT Cleaning machines, dryers, separators, filters KV Burners, grates KW Stationary tooling and treatment machines for maintenance Printout date 14. Mrz. 01 Page 2 of 6 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Component key 04.04.97 M Mechanical components MB Brakes MF Foundations MG Gearboxes MK Clutches, couplings MM Engines, not electrical MR Piping components, ductwork components MS Positioners, not electrical MT Turbines MU Transmission gear, non electrical, converters and boosters other than couplings and gearboxes Printout date 14. Mrz. 01 Page 3 of 6 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Component key 04.04.97 Q Instrumentation and control components (non-electrical) QA Enclosures (for I&C component protection only) QB Sensors if not structurally integral with *QP*, metering orifices QH Signalling devices QN Controllers, flybolt governor QP Measuring instruments, testing equipment QR Instrument piping QS Condensation chambers (datum reservoir) in measuring circuits QT Thermowells and pockets for protection of sensors Printout date 14. Mrz. 01 Page 4 of 6 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Component key 04.04.97 X Signal origins XA Functional group control/subloop control XB Control interface XC Closed-loop control XD Reactor protection, signals in binary signal processing section XE Reactor protection, signals in analog and binary sections XF Priority control XG Binary process signals conditioned by binary signal conditioning modules XH Binary limit signals derived from analog process signals XJ Signals from non-standard areas (e. g. black box, dedicated I&C) XK Equipment unit/component protection XL Control room and control stations, signals not assigned to specific control systems (e. g. control interface tiles) XM Alarm signals XN Status-display computer/criterion display XP Supervisory computer (process computer) XQ Analog signals XR Priority control and limitation function (controls other than *XC* and *XT*,*YC* and *YT*) XS Functional group control step signals XT Turbine generator I&C, binary signals XU Non-floating dynamic alarm signals XW Hardwired alarm annunciation system Printout date 14. Mrz. 01 Page 5 of 6 Siemens 2 nd complete, non-project related edition Condition-Date: KKS Identification System for Power Plants Component key 04.04.97 Y Signal applications YA Functional group control/subloop control YB Control interface YC Closed-loop control YD Reactor protection, signals in binary signal processing section YE Reactor protection, signals in analog and binary sections YF Priority control YJ Signals from non-standard areas (e. g. black box, dedicated I&C) YL Control room and control stations, signals not assigned to specific control systems (e. g. control interface tiles) YN Status-display computer/criterion display YP Supervisory computer (process computer) YQ Analog signals YR Priority control and limitation function (controls other than *XC* and *XT*,*YC* and *YT*) YT Turbine generator I&C, binary signals YV Signal gating (protective logic, alarm logic, etc.) YW Hardwired alarm annunciation system Printout date 14. Mrz. 01 Page 6 of 6