Exhibit E: SRB HVAC Deficiency Report Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Issue ID: Equipment: Issue Description: 0001 EF 2.31 DATE: CONTACT: AUTHOR: Status: Fan is not operating. The drive belt's not installed. Issue Type: Role Assignment: User Assignment: Issue Photos: Inoperable Building Owner Steven Mullins Name: Captured: Fan is not operating. The drive belt's not install.jpg 6/17/2019 9:42:48 AM Issue ID: 0001 Pro-Tech Diversified Services, Inc. Open Issue Priority: 10/10/2019 Steven Mullins Critical Created Date: 17-Jun-19 Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Issue ID: Equipment: Issue Description: 0002 EF 2.31 DATE: CONTACT: AUTHOR: Status: Fan disconnect device is not operating or broken. Issue Type: Role Assignment: User Assignment: Issue Photos: Inoperable Building Owner Roddy Quinones Name: Captured: Fan disconnect device is not operating. .jpg 6/17/2019 1:19:45 PM Issue ID: 0002 Pro-Tech Diversified Services, Inc. Open Issue Priority: 10/10/2019 Steven Mullins Critical Created Date: 17-Jun-19 Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Issue ID: Equipment: Issue Description: 0003 EF 3.47 Fan is not operating. Issue Type: Role Assignment: User Assignment: Issue Photos: Inoperable Building Owner Roddy Quinones Name: Captured: Fan is not operating..jpg 6/17/2019 1:23:39 PM Issue ID: 0003 Pro-Tech Diversified Services, Inc. DATE: CONTACT: AUTHOR: Status: Open Issue Priority: 10/10/2019 Steven Mullins Critical Created Date: 17-Jun-19 Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Issue ID: Equipment: Issue Description: 0004 EF 3.29E DATE: CONTACT: AUTHOR: 10/10/2019 Steven Mullins Status: Open Issue Priority: Critical Created Date: 17-Jun-19 Status: Open Issue Priority: Critical Created Date: 18-Jun-19 Fan is not operating. Issue Type: Role Assignment: User Assignment: Inoperable Building Owner Roddy Quinones Issue ID: Equipment: Issue Description: 0005 EF 3.28E The duct supports have punctured the exhaust duct. Issue Type: Role Assignment: User Assignment: Issue Photos: Observation Building Owner Steven Mullins Name: Captured: EF 3.28E.jpg 6/18/2019 8:11:15 AM Issue ID: 0005 Pro-Tech Diversified Services, Inc. Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Name: Captured: EF 3.28E.jpg 6/18/2019 8:11:15 AM Issue ID: 0005 Pro-Tech Diversified Services, Inc. DATE: CONTACT: AUTHOR: 10/10/2019 Steven Mullins Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Issue ID: Equipment: Issue Description: 0006 EF 3.28E The weld for the access panel has broken loose. Issue Type: Role Assignment: User Assignment: Issue Photos: Observation Building Owner Steven Mullins Name: Captured: EF 3.28E.jpg 6/18/2019 8:12:42 AM Issue ID: 0006 Pro-Tech Diversified Services, Inc. DATE: CONTACT: AUTHOR: Status: Open Issue Priority: 10/10/2019 Steven Mullins Critical Created Date: 18-Jun-19 Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Issue ID: Equipment: Issue Description: 0008 EF 2.20 DATE: CONTACT: AUTHOR: 10/10/2019 Steven Mullins Status: Open Issue Priority: Critical Created Date: 18-Jun-19 Status: Open Issue Priority: Critical Created Date: 18-Jun-19 Fan disconnect device on roof is not installed. Issue Type: Role Assignment: User Assignment: Observation Building Owner Roddy Quinones Issue ID: Equipment: Issue Description: 0009 EF 3.30 The canvas connection’s torn open. Issue Type: Role Assignment: User Assignment: Issue Photos: Observation Building Owner Steven Mullins Name: Captured: EF 3.30.jpg 6/18/2019 9:11:04 AM Issue ID: 0009 Pro-Tech Diversified Services, Inc. Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Issue ID: Equipment: Issue Description: 0010 EF 3.26V DATE: CONTACT: AUTHOR: 10/10/2019 Steven Mullins Status: Open Issue Priority: Critical Created Date: 18-Jun-19 Status: Open Issue Priority: Critical Created Date: 18-Jun-19 Fan is not operating. Issue Type: Role Assignment: User Assignment: Observation Building Owner Roddy Quinones Issue ID: Equipment: Issue Description: 0011 EF 3.23 The bearing for the fan shaft's broken. The fan's still operating. Continued operation will result in catastrophic failure of the fan. Issue Type: Role Assignment: User Assignment: Observation Building Owner Steven Mullins Issue ID: Equipment: Issue Description: 0012 EF 3.21 Status: Open Issue Priority: Created Date: 18-Jun-19 This fan isn't installed. Issue Type: Role Assignment: User Assignment: Observation My Company Users Steven Mullins Issue ID: Equipment: Issue Description: 0013 EF 3.22 Status: Open Issue Priority: Created Date: 18-Jun-19 This fan isn't installed. Issue Type: Role Assignment: User Assignment: Observation My Company Users Steven Mullins Issue ID: Equipment: Issue Description: 0014 EF 3.31E Status: Open Issue Priority: Created Date: 18-Jun-19 EF 3.31 isn't installed. The fan in it's place, is labeled EF 2.31. Issue Type: Role Assignment: User Assignment: Observation My Company Users Steven Mullins Issue ID: Equipment: Issue Description: 0015 EF 3.37E Status: Open Issue Priority: Critical Created Date: 18-Jun-19 Status: Open Issue Priority: Critical Created Date: 18-Jun-19 Fan is not operating Issue Type: Role Assignment: User Assignment: Observation Building Owner Roddy Quinones Issue ID: Equipment: Issue Description: 0018 EF 3.39E Fan is not operating Issue Type: Role Assignment: User Assignment: Observation Building Owner Roddy Quinones Pro-Tech Diversified Services, Inc. Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Issue ID: Equipment: Issue Description: 0019 EF 3.36E DATE: CONTACT: AUTHOR: Status: Open Issue Priority: Emergency exhaust fan intake is blocked with boxes. No access to fan information. Issue Type: Role Assignment: Issue Photos: Observation Building Owner Name: Captured: Emergency exhaust fan intake is blocked with boxes 6/18/2019 12:41:43 PM Issue ID: 0019 Pro-Tech Diversified Services, Inc. 10/10/2019 Steven Mullins Created Date: 18-Jun-19 Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Name: Captured: Emergency exhaust fan intake is blocked with boxes 6/18/2019 12:41:43 PM Issue ID: 0019 Pro-Tech Diversified Services, Inc. DATE: CONTACT: AUTHOR: 10/10/2019 Steven Mullins Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Issue ID: Equipment: Issue Description: 0020 EF 3.38E DATE: CONTACT: AUTHOR: Status: Open Issue Priority: Status: Open Issue Priority: 10/10/2019 Steven Mullins Critical Created Date: 18-Jun-19 Fan is not operating Issue Type: Role Assignment: User Assignment: Observation Building Owner Roddy Quinones Issue ID: Equipment: Issue Description: 0021 EF 3.43E Fan is not operating Issue Type: Role Assignment: Observation Building Owner Pro-Tech Diversified Services, Inc. Created Date: 18-Jun-19 Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Issue ID: Equipment: Issue Description: 0022 EF 3.40E DATE: CONTACT: AUTHOR: Status: No Access to the fan or motor information. Issue Type: Role Assignment: User Assignment: Issue Photos: Observation Building Owner Roddy Quinones Name: Captured: No Access to the fan or motor information..jpg 6/18/2019 12:57:36 PM Issue ID: 0022 Pro-Tech Diversified Services, Inc. Open Issue Priority: 10/10/2019 Steven Mullins Critical Created Date: 18-Jun-19 Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Issue ID: Equipment: Issue Description: 0023 EF 3.41E No Access to the fan or motor information. Issue Type: Role Assignment: User Assignment: Observation Building Owner Roddy Quinones Pro-Tech Diversified Services, Inc. DATE: CONTACT: AUTHOR: Status: Open Issue Priority: 10/10/2019 Steven Mullins Critical Created Date: 18-Jun-19 Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Issue Photos: Name: Captured: No Access to the fan or motor information..jpg 6/18/2019 12:58:53 PM Issue ID: 0023 Pro-Tech Diversified Services, Inc. DATE: CONTACT: AUTHOR: 10/10/2019 Steven Mullins Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Issue ID: Equipment: Issue Description: 0024 EF 3.42E DATE: CONTACT: AUTHOR: Status: No Access to the fan or motor information. Issue Type: Role Assignment: User Assignment: Issue Photos: Observation Building Owner Roddy Quinones Name: Captured: No Access to the fan or motor information..jpg 6/18/2019 1:02:52 PM Issue ID: 0024 Pro-Tech Diversified Services, Inc. Open Issue Priority: 10/10/2019 Steven Mullins Critical Created Date: 18-Jun-19 Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Issue ID: Equipment: Issue Description: 0025 AHU 2.20 DATE: CONTACT: AUTHOR: Status: Open Issue Priority: 10/10/2019 Steven Mullins Critical Created Date: 20-Jun-19 The supply discharge isolation damper’s are 90% closed. Both of the damper actuators are broken and do not function. Issue Type: Role Assignment: User Assignment: Issue Photos: Observation Building Owner Roddy Quinones Name: Captured: The supply discharge isolation damper’s are 90% cl.jpg 6/20/2019 2:03:10 PM Issue ID: 0025 Pro-Tech Diversified Services, Inc. Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Name: Captured: The supply discharge isolation damper’s are 90% cl.jpg 6/20/2019 2:03:10 PM Issue ID: 0025 Pro-Tech Diversified Services, Inc. DATE: CONTACT: AUTHOR: 10/10/2019 Steven Mullins Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Name: Captured: The supply discharge isolation damper’s are 90% cl.jpg 6/20/2019 2:03:10 PM Issue ID: 0025 Pro-Tech Diversified Services, Inc. DATE: CONTACT: AUTHOR: 10/10/2019 Steven Mullins Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Issue ID: Equipment: Issue Description: 0026 AHU 2.21 DATE: CONTACT: AUTHOR: Status: Open Issue Priority: 10/10/2019 Steven Mullins Critical Created Date: 20-Jun-19 The actuator for the supply isolation damper is not installed. Damper is 100% open. It has been propped open with a piece of sheet metal. Issue Type: Role Assignment: User Assignment: Issue Photos: Inoperable Building Owner Roddy Quinones Name: Captured: AHU 2.21.jpg 6/20/2019 2:15:46 PM Issue ID: 0026 Pro-Tech Diversified Services, Inc. Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Name: Captured: AHU 2.21.jpg 6/20/2019 2:15:45 PM Issue ID: 0026 Pro-Tech Diversified Services, Inc. DATE: CONTACT: AUTHOR: 10/10/2019 Steven Mullins Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Issue ID: Equipment: Issue Description: 0027 RF 3.23 DATE: CONTACT: AUTHOR: Status: Open Issue Priority: 10/10/2019 Steven Mullins Critical Created Date: 24-Jun-19 Motor Sheave key way is not installed properly. The back side of the adjustable sheave as opened. The back side fan belt is loose. Issue Type: Role Assignment: User Assignment: Issue Photos: Observation Building Owner Roddy Quinones Name: Captured: RF 3.23.jpg 6/24/2019 8:41:23 AM Issue ID: 0027 Pro-Tech Diversified Services, Inc. Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Issue ID: Equipment: 0028 AHU 3.27/SF Filter Bank DATE: CONTACT: AUTHOR: Status: Fixed Issue Description: The filters are dirty and damaged. They have started to cave into the coil. Issue Type: Role Assignment: User Assignment: Inoperable Building Owner Roddy Quinones Pro-Tech Diversified Services, Inc. Issue Priority: 10/10/2019 Steven Mullins Critical Created Date: 24-Jun-19 Completed Date: 16-Jul-19 Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Issue Photos: Name: Captured: The filters are damaged..jpg 6/24/2019 10:27:02 AM Issue ID: 0028 Pro-Tech Diversified Services, Inc. DATE: CONTACT: AUTHOR: 10/10/2019 Steven Mullins Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Issue ID: Equipment: 0029 AHU 3.28/SF Filter Bank Issue Description: The filters are dirty. Issue Type: Role Assignment: User Assignment: Issue Photos: Inoperable Building Owner Roddy Quinones Name: Captured: The filters are dirty..jpg 6/24/2019 10:29:12 AM Issue ID: 0029 Pro-Tech Diversified Services, Inc. DATE: CONTACT: AUTHOR: Status: Fixed Issue Priority: 10/10/2019 Steven Mullins Critical Created Date: 24-Jun-19 Completed Date: 16-Jul-19 Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Issue ID: Equipment: 0030 AHU 3.32E/SF Filter Bank DATE: CONTACT: AUTHOR: Status: Fixed Issue Description: The filters are dirty and damaged. The filters have caved into the coil. Issue Type: Role Assignment: User Assignment: Inoperable Building Owner Roddy Quinones Pro-Tech Diversified Services, Inc. Issue Priority: 10/10/2019 Steven Mullins Critical Created Date: 24-Jun-19 Completed Date: 16-Jul-19 Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Issue Photos: Name: Captured: The filters are damaged..jpg 6/24/2019 10:33:08 AM Issue ID: 0030 Pro-Tech Diversified Services, Inc. DATE: CONTACT: AUTHOR: 10/10/2019 Steven Mullins Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Issue ID: Equipment: Issue Description: 0031 FCU 3.40 DATE: CONTACT: AUTHOR: Status: The fan belt’s cracked and needs to be replaced. Issue Type: Role Assignment: User Assignment: Issue Photos: Observation Building Owner Steven Mullins Name: Captured: The fan belt’s cracked and needs to be replaced..jpg 6/26/2019 9:59:52 AM Issue ID: 0031 Pro-Tech Diversified Services, Inc. Open Issue Priority: 10/10/2019 Steven Mullins Critical Created Date: 26-Jun-19 Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Issue ID: Equipment: Issue Description: 0032 FCU 3.33 DATE: CONTACT: AUTHOR: 10/10/2019 Steven Mullins Status: Open Issue Priority: Critical Created Date: 26-Jun-19 Status: Open Issue Priority: Critical Created Date: 02-Jul-19 This unit’s not operating. Issue Type: Role Assignment: User Assignment: Observation Building Owner Steven Mullins Issue ID: Equipment: Issue Description: 0033 AHU 3.23E Fan Motor Frame or base broken. Issue Type: Role Assignment: Issue Photos: Work In Progress Building Owner Name: Captured: Fan Motor Frame or base broken..jpg 7/2/2019 10:18:36 AM Issue ID: 0033 Pro-Tech Diversified Services, Inc. Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Issue ID: Equipment: Issue Description: 0034 FCU 3.32 DATE: CONTACT: AUTHOR: Status: Open Issue Priority: 10/10/2019 Steven Mullins Critical Created Date: 10-Jul-19 We’re unable to obtain the unit serial number. The unit tag’s covered with duct sealer. Issue Type: Role Assignment: User Assignment: Observation Building Owner Roddy Quinones Issue ID: Equipment: Area: Issue Description: 0035 EF 12/Inlet-04 20041 Status: Open Issue Priority: Critical Created Date: 10-Jul-19 The duct serving room 20041 has been disconnected from the main exhaust duct and has been capped. Issue Type: Role Assignment: Issue Photos: Observation Building Owner Name: Captured: The duct serving the room is not attached or cappe.jpg 7/10/2019 1:26:53 PM Issue ID: 0035 Pro-Tech Diversified Services, Inc. Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Name: Captured: The duct serving the room is not attached or cappe.jpg 7/10/2019 1:26:53 PM Issue ID: 0035 Pro-Tech Diversified Services, Inc. DATE: CONTACT: AUTHOR: 10/10/2019 Steven Mullins Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Issue ID: Equipment: Issue Description: 0036 EF 12 DATE: CONTACT: AUTHOR: Status: Open We’re unable to obtain motor data. Access to the fan has been blocked. Issue Type: Role Assignment: User Assignment: Issue Photos: Observation Building Owner Roddy Quinones Name: Captured: EF 12.jpg 7/10/2019 1:56:12 PM Issue ID: 0036 Pro-Tech Diversified Services, Inc. Issue Priority: 10/10/2019 Steven Mullins Critical Created Date: 10-Jul-19 Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Issue ID: Equipment: 0037 AHU 3.26E DATE: CONTACT: AUTHOR: Status: Fixed Issue Priority: 10/10/2019 Steven Mullins Critical Created Date: 16-Jul-19 Completed Date: 31-Jul-19 Issue Description: Unit operating at 60.0Hz with the discharge isolation damper partially open, restricting the airflow and increasing the pressure in the unit. Issue Type: Role Assignment: User Assignment: Inoperable Building Owner Roddy Quinones Pro-Tech Diversified Services, Inc. Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Issue Photos: Name: Captured: Unit operating at 60.0Hz with the discharge isolat.jpg 7/16/2019 8:59:14 AM Issue ID: 0037 Pro-Tech Diversified Services, Inc. DATE: CONTACT: AUTHOR: 10/10/2019 Steven Mullins Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Issue ID: Equipment: Issue Description: 0038 AHU 3.27 DATE: CONTACT: AUTHOR: Status: Open Issue Priority: 10/10/2019 Steven Mullins Critical Created Date: 16-Jul-19 Unit is not operating at this moment. Southern Equipment is currently working on this unit. Issue Type: Role Assignment: User Assignment: Observation Building Owner Roddy Quinones Issue ID: Equipment: Issue Description: 0039 AHU 3.28 Status: Open Issue Priority: Unit operating with the supply southwest branch damper in the closed position. Issue Type: Role Assignment: User Assignment: Issue Photos: Observation Building Owner Roddy Quinones Pro-Tech Diversified Services, Inc. Critical Created Date: 16-Jul-19 Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Name: Captured: Unit operating with the supply southwest branch da.jpg 7/16/2019 1:47:11 PM Issue ID: 0039 Pro-Tech Diversified Services, Inc. DATE: CONTACT: AUTHOR: 10/10/2019 Steven Mullins Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Name: Captured: Unit operating with the supply southwest branch da.jpg 7/16/2019 1:47:11 PM Issue ID: 0039 Pro-Tech Diversified Services, Inc. DATE: CONTACT: AUTHOR: 10/10/2019 Steven Mullins Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Name: Captured: Unit operating with the supply southwest branch da.jpg 7/16/2019 1:47:11 PM Issue ID: 0039 Pro-Tech Diversified Services, Inc. DATE: CONTACT: AUTHOR: 10/10/2019 Steven Mullins Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Issue ID: Equipment: Issue Description: 0040 AHU 3.32E DATE: CONTACT: AUTHOR: Status: Open Issue Priority: 10/10/2019 Steven Mullins Critical Created Date: 23-Jul-19 The filters were changed. However, the new filters have collapsed into the coil. The filters have been damaged and need be replace. Issue Type: Role Assignment: User Assignment: Issue Photos: Observation Building Owner Roddy Quinones Pro-Tech Diversified Services, Inc. Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Name: Captured: The filters were changed. However, the new filters.jpg 7/23/2019 8:19:02 AM Issue ID: 0040 Pro-Tech Diversified Services, Inc. DATE: CONTACT: AUTHOR: 10/10/2019 Steven Mullins Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Name: Captured: The filters were changed. However, the new filters.jpg 7/23/2019 8:19:02 AM Issue ID: 0040 Pro-Tech Diversified Services, Inc. DATE: CONTACT: AUTHOR: 10/10/2019 Steven Mullins Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Issue ID: Equipment: 0041 DATE: CONTACT: AUTHOR: Status: Fixed Issue Priority: 10/10/2019 Steven Mullins Critical Created Date: 26-Jul-19 Completed Date: 13-Aug-19 Issue Description: Fire smoke damper serving the SRB Vivarium supply north branch is partially closed creating high static duct pressure and airflow restrictions. Damper is located at Storage Room 21245, inside of ( Conference 2) Room 21243. Issue Type: Role Assignment: User Assignment: Observation Building Owner Roddy Quinones Issue ID: Equipment: Issue Description: 0042 EF 2.20/Inlet-20 The grille is covered with plastic and tape. Issue Type: Role Assignment: User Assignment: Issue Photos: Observation Building Owner Roddy Quinones Pro-Tech Diversified Services, Inc. Status: Open Issue Priority: Critical Created Date: 13-Aug-19 Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Name: Captured: The grille is covered with plastic and tape..jpg 8/13/2019 9:39:37 AM Issue ID: 0042 Pro-Tech Diversified Services, Inc. DATE: CONTACT: AUTHOR: 10/10/2019 Steven Mullins Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Name: Captured: The grille is covered with plastic and tape..jpg 8/13/2019 9:39:37 AM Issue ID: 0042 Pro-Tech Diversified Services, Inc. DATE: CONTACT: AUTHOR: 10/10/2019 Steven Mullins Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Name: Captured: The grille is covered with plastic and tape..jpg 8/13/2019 9:39:37 AM Issue ID: 0042 Pro-Tech Diversified Services, Inc. DATE: CONTACT: AUTHOR: 10/10/2019 Steven Mullins Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Issue ID: Equipment: Issue Description: 0043 FCU 3.27 DATE: CONTACT: AUTHOR: Status: 10/10/2019 Steven Mullins Open Issue Priority: Critical Created Date: 23-Aug-19 Open Issue Priority: Critical Created Date: 28-Aug-19 Unit is not operating. Disconnect in the off position. Issue Type: Role Assignment: User Assignment: Observation Building Owner Roddy Quinones Issue ID: Equipment: Issue Description: 0044 FCU 3.28E Unit is not operating at this moment. Issue Type: Role Assignment: User Assignment: Issue Photos: Observation Building Owner Roddy Quinones Name: Captured: Unit is not operating at this moment..jpg 8/28/2019 10:15:32 AM Issue ID: 0044 Pro-Tech Diversified Services, Inc. Status: Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Issue ID: Equipment: Issue Description: 0045 FCU 3.30 DATE: CONTACT: AUTHOR: Status: Drain pan block the access panel to the motor information. Issue Type: Role Assignment: User Assignment: Issue Photos: Observation Building Owner Roddy Quinones Name: Captured: Drain pan block the access panel to the motor info.jpg 8/28/2019 10:44:52 AM Issue ID: 0045 Pro-Tech Diversified Services, Inc. Open Issue Priority: 10/10/2019 Steven Mullins Critical Created Date: 28-Aug-19 Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Issue ID: Equipment: Issue Description: 0046 DATE: CONTACT: AUTHOR: Status: Open Issue Priority: 10/10/2019 Steven Mullins Critical Created Date: 30-Sep-19 There's a 10" open tap above the ceiling in Rm. 24205. This tap's served by the exhaust air system. Issue Type: Role Assignment: User Assignment: Issue Photos: Observation Building Owner Steven Mullins Pro-Tech Diversified Services, Inc. Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Name: Captured: There's a 10" open tap above the ceiling in Rm. 24.jpg 9/30/2019 10:27:10 PM Issue ID: 0046 Pro-Tech Diversified Services, Inc. DATE: CONTACT: AUTHOR: 10/10/2019 Steven Mullins Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Name: Captured: There's a 10" open tap above the ceiling in Rm. 24.jpg 9/30/2019 10:27:10 PM Issue ID: 0046 Pro-Tech Diversified Services, Inc. DATE: CONTACT: AUTHOR: 10/10/2019 Steven Mullins Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Issue ID: Equipment: Issue Description: 0047 DATE: CONTACT: AUTHOR: Status: Open Issue Priority: 10/10/2019 Steven Mullins Critical Created Date: 01-Oct-19 GEV-25-31 (4th Flr.), the inlet served by this air valve's not installed. The duct's open above the ceiling. Issue Type: Role Assignment: User Assignment: Issue Photos: Observation Building Owner Steven Mullins Name: Captured: GEV-25-31, the inlet's not installed. The duct's o.jpg 10/1/2019 12:52:05 AM Issue ID: 0047 Pro-Tech Diversified Services, Inc. Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Issue ID: Equipment: Issue Description: 0048 DATE: CONTACT: AUTHOR: Status: Open Issue Priority: 10/10/2019 Steven Mullins Critical Created Date: 10-Oct-19 The manual volume damper installed in the main 54x36 exhaust duct, located on the roof and serving the entire NE side of the SRB lab areas, was found in the closed position. Our test indicates there's zero airflow on this side of the Bldg. from the 4th floor down to the 1st floor. Static pressures taken across this damper resulted in a 3" pressure loss, indicating that the damper's closed. Issue Type: Role Assignment: User Assignment: Observation Building Owner Steven Mullins Pro-Tech Diversified Services, Inc. Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Issue ID: Equipment: Issue Description: 0049 DATE: CONTACT: AUTHOR: Status: Open 10/10/2019 Steven Mullins Issue Priority: Created Date: 10-Oct-19 SAV-25-1 (3rd Flr.) has three outlets installed in Work Rm. 23205. However, one of these outlets isn't installed. The duct tap for this outlet's open above the ceiling. Issue Type: Role Assignment: Issue Photos: Not Assigned My Company Users Name: Captured: SAV-25-1 has three outlets installed in Work Rm. 2.jpg 10/10/2019 11:30:46 AM Issue ID: 0049 Pro-Tech Diversified Services, Inc. Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Issue ID: Equipment: Issue Description: 0050 DATE: CONTACT: AUTHOR: Status: Open Issue Priority: 10/10/2019 Steven Mullins Critical Created Date: 10-Oct-19 SAV-25-33 (4th Flr.) serves three supply outlets. One of these outlets is no longer connected to the air valve. This outlet's been connected to the medium pressure duct. This makes the outlet a constant volume outlet and is no longer regulated by the air valve. This installation could have adverse results on the room pressures. Issue Type: Role Assignment: User Assignment: Observation Building Owner Steven Mullins Issue ID: Equipment: Issue Description: 0051 Status: Open Issue Priority: Critical Created Date: 10-Oct-19 GEV-25-32 (4th Flr.) serves two inlets. The inlet shown to be installed in room 24208 has been installed in the open area outside of this room. The duct serving this inlet has been removed and the tap's open above the ceiling. Issue Type: Role Assignment: User Assignment: Issue Photos: Observation Building Owner Steven Mullins Pro-Tech Diversified Services, Inc. Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Name: Captured: GEV-25-32 (4th Flr.) serves two inlets. The inlet .jpg 10/10/2019 1:01:32 PM Issue ID: 0051 Pro-Tech Diversified Services, Inc. DATE: CONTACT: AUTHOR: 10/10/2019 Steven Mullins Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Name: Captured: GEV-25-32 (4th Flr.) serves two inlets. The inlet .jpg 10/10/2019 1:01:33 PM Issue ID: 0051 Pro-Tech Diversified Services, Inc. DATE: CONTACT: AUTHOR: 10/10/2019 Steven Mullins Deficiency Report PROJECT: LOCATION: PROJECT #: MCC SRB HVAC Roof Survey Tampa, FL P2767 Name: Captured: GEV-25-32 (4th Flr.) serves two inlets. The inlet .jpg 10/10/2019 1:01:33 PM Issue ID: 0051 Pro-Tech Diversified Services, Inc. DATE: CONTACT: AUTHOR: 10/10/2019 Steven Mullins