3.2. Seismic spectrum covered on Blokset 1908x0b

advertisement
SPECTRES SEISME COUVERTS POUR
LES ESSAIS RÉALISÉS SUR BLOKSET
SEISMIC SPECTRUMS COVERED BY
TESTS REALIZED ON BLOKSET
B
14/05/2008
Up-dated
J. REY
G. BONAZZI
A
23/08/2005
Emission originale / First issue
L. OTÁVIO
Ind /
Rev
Date / Date
Modification / Modification
Nom / Name
G. BONAZZI
Visa
Prépare / Issued by :
Projet / Projet:
Vérifié / Checked by:
Etabli par / Issued by:
BLOKSET
G. BONAZZI
L. OTAVIO
Dossier / Folder Visa:
Date/Date: Visa:
Nom / Name
Archiv. /
Microfil.
Vérifié / Checked by:
SPECTRES SEISME COUVERT POUR LES
ESSAIS RÉALIZÉS SUR BLOKSET
SEISMIC SPECTRUMS COVERED BY
TESTS REALIZED ON BLOKSET
Date/Date:
Code diff./Distrib.code:
Unité / Department
E&S
Visa
Ind
5
1
1
3
1
9
0
8
X
0
B
Ver Folio/Sheet
1/2
No 41 01 13 ind. AA Les informations techniques contenues dans ce document sont la propriété exclusive de SCHNEIDER ELECTRIC SA et ne peuvent être utilisées ou divulguées à des tiers quels qu’ils soient sans son accord écrit.
All technical information contained in this document is exclusive property of SCHNEIDER ELECTRIC SA and may not be used nor disclosed without its prior conset.
Original format A4
Blokset has run successfully tests
ensuring its compliance with the
following spectrums:
IBC 2000 et amendement ICBO AC 156
IBC 2000 and amendment ICBO AC 156
Spectrum Equivalence with
Richter scale, according to
IEC68-3-3
Site class B,C
and D
Floor level only
Zone 2A
Floor & roof
levels
Zone 2B
Floor & roof
levels
Zone 3
Floor & roof
levels
5.5 to 7.0
Zone 4
Floor level only
7.0 to 9.0
-
< 5.5
UBC 97 et amandement ICBO AC 156
UBC 97 and amendment ICBO AC 156
According to IEC68-3-3 standard, and considering the successful seismic tests, Blokset withstands:
•
Up to Richter 7 earthquakes, when installed
anywhere (basement, floor, top of a building)
•
Up to Richter 9 earthquakes, when installed at the
floor or basement level (not higher than the ground
level)
Important:
2- If your customer provides you with specific values
other than Richter (PGA, etc.) or documents regarding
the required seismic withstand (with spectra or
calculation), please inform him about UBC spectra
shown above, by showing him this document.
1- The above withstand can only be ensured by
strictly following the indications given in
Blokset transfer file DVD, latest version, chapter
3, Technical guide, item 5.10.
SPECT. SEISME COUV. POUR ESSAIS REAL. SUR BLOKSET / SEISMIC SPECTRUMS COV. BY TESTS REAL. ON BLOKSET
Unité / Department
E&S
Ind
5
1
1
3
1
9
0
8
X
0
B
Ver Folio/Sheet
2/2
No 41 01 13 ind. AA Les informations techniques contenues dans ce document sont la propriété exclusive de SCHNEIDER ELECTRIC SA et ne peuvent être utilisées ou divulguées à des tiers quels qu’ils soient sans son accord écrit.
All technical information contained in this document is exclusive property of SCHNEIDER ELECTRIC SA and may not be used nor disclosed without its prior conset.
Original format A4