ERCOT Dynamic Model Review Platform Development Yunzhi Cheng2, Shun-Hsien (Fred) Huang1, Yang Zhang2, and Jose Conto2 1 Member, IEEE 2Senior Member, IEEE Abstract—This paper presents a dynamic model review platform developed by ERCOT to evaluate the dynamic performance of the dynamic model associated with every type of generation. Based on a single power plant – infinity generator test system, the platform can be utilized to test the voltage and frequency responses for the purpose of dynamic model review and grid code compliance studies. It can also be utilized to assess the short circuit ratio (SCR) limit that the test generation resource can survive in dynamic simulation under a large disturbance and a small disturbance, respectively. ERCOT is currently utilizing the platform as the screening tool to assess the dynamic performance associated with generation resources with proprietary dynamic models. Index Terms—Dynamic model, voltage response, frequency response, short circuit ratio I. INTRODUCTION In the past decade, renewable power generation, especially wind and solar, has exponentially grown across the world. Numerous power electronics devices with various novel control methods have been installed in power systems. At the same time frame, power industry has been in the transition toward the electricity market deregulation. In deregulated regions, transmission & distribution (T&D) sector is split from the traditional vertically integrated utilities which were composed of generation, T&D, and load serving. Consequently, transmission systems are increasingly exposed to the operating limits, especially stability limits [1]. Currently, dynamic models play a critical role of determining the System Operating Limits (SOL) and Interconnection Reliability Operating Limits (IROL). Even more attention has been paid to model testing and calibration as North American Electric Reliability Corporation (NERC) proposed MOD-26, MOD-27, and MOD-33 standards that are mandatory to generator owners, transmission owners, and reliability coordinators [2]. In ERCOT, more than 19,000 MW wind generation has been built, and solar generation is currently booming at an unprecedented rate. EROCT wind generation has set a record of 54% penetration on October 27, 2017 [3]. Currently, there Yunzhi Cheng (yunzhi.cheng@ercot.com), S-H Huang, Yang Zhang and Jose Conto are with Electric Reliability Council of Texas (ERCOT Inc.), Taylor, TX 76574, USA is no requirement of using generic models for renewable generation modeling in ERCOT. Instead, most of ERCOT renewable generation resources are modeled with proprietary user-defined dynamic models. As a result, the number of proprietary dynamic generator models in ERCOT is more than double of that of standard generator models although the renewable generation capability accounts for less than 25% of the total generation capacity. It is a challenge for ERCOT to maintain so many kinds of dynamic models and build a whole system dynamic dataset. ERCOT is planning to review the dynamic model for each individual generation resource prior to integrating them into the system dynamic dataset. To authors’ knowledge, Siemens PTI PSSE’s ERUN (exciter simulation test) and GRUN (governor simulation test) can only be applied to synchronous generators with standard models [4]. There is no commercial software available to test the proprietary dynamic models. Many researchers have worked on model calibration using the field recording data to adjust the dynamic parameters such that the dynamic simulation could align well with the recordings [5] [6] [7]. A dynamic model review platform not only can be served as the simulation tool for model calibration, but also can be utilized as a screening tool to flag the suspect models to trigger the model calibration. Another challenge associated with renewable generation integration in ERCOT is the grid strength issue. Most of renewable generation resources in ERCOT are located at remote areas which are distant from ERCOT load centers. Currently, there are more than 3,000 MW wind generation resources installed and more wind generation resources are expected to come online in ERCOT Panhandle area. Without synchronous generators or loads, the Panhandle is located at the edge of the ERCOT system (300 miles from the ERCOT load centers) so the Panhandle grid is relatively weak. ERCOT proposed Weighted Short Circuit Ratio (WSCR) to measure the system strength and dispatch the Panhandle wind generation so that the real time WSCR value is no lower than the WSCR limit to maintain the system stability [8]. Testing the SCR limit for each individual model can help system operators and planners to address the reliability concerns associated with grid strength and manufacturers to improve the control performance based on the particular SCR range as observed at the specific project location. To evaluate the dynamic performance associated with all generation resources, irrespective of the generation type or model type, ERCOT developed a dynamic model review platform comprised of the following functions: No-disturbance flat start test Voltage response test Frequency response test SCR limit test While the platform can be utilized to facilitate grid code compliance studies, NERC compliance studies and any other voltage & frequency tests that users specify such as helping the manufacturer to optimize the control design, ERCOT is currently utilizing the platform as the screening tool to assess the dynamic performance associated with the generation resources with proprietary dynamic models. For any model with suspect response in the tests, ERCOT will communicate with the generation resource so the model can be re-visited, tuned and updated. The subsequent sections demonstrate the platform design and illustrate selected review experiences with wind and solar dynamic models that were provided to ERCOT. II. DYNAMIC MODEL REVIEW PLATFORM The dynamic model review platform is based on single power plant – infinity bus system to test each dynamic model individually. The power plant model includes every element in the power plant such as generators, pad-mount (PM) transformers, station transformers, medium voltage (MV) collection system, shunt devices, and tie line connecting the power plant to POI (Point of Interconnection) bus. Except for the SCR limit test, the line connecting the POI to the infinity bus is modeled as zero impedance branch. Fig. 1 demonstrates the scheme of the platform. The platform is developed in python with PSSE API functions. Users can build the test generation resource model in steady state and dynamics to evaluate the dynamic response of the actual generation resource. Alternatively, users can also take advantage of a prepared 200MW renewable resource power flow template case and plug into the dynamic model with proper parameters associated with the actual generation resource and then evaluate the response trend under test. In the latter case, the test results cannot be utilized as the grid code compliance study. However, the response trend can be utilized to check if the model is usable and has a reasonable response. Fig. 1 Dynamic Model Review Platform Scheme A. No-disturbance Flat Start Test A 10-second no-disturbance flat start (FS) test is firstly applied in the model review platform to identify if there is any initialization error or numerical stability issue which is mainly related to integration errors. Once the model passes the FS test, the following tests can be performed. B. Voltage & Frequency Response Test A time-domain voltage & frequency table (Table I as an example) is designed to model the point of interconnection (POI) profile for voltage and frequency response tests. The platform converts the table to dynamic parameters associated with the PSSE playback model (“PLBFVU1”) which is utilized to accurately controlling the POI voltage during the dynamic simulation tests. The voltage & frequency response tests include the following dynamic response tests: Generic ERUN test: to test the reactive power response of the dynamic model under the 0.1pu voltage deviation at the POI bus. To fulfill the grid code requirements, the reactive power is supposed to increase/decrease when the POI bus voltage goes down/up. Generic GRUN test: to test the active power response of the dynamic model under the 0.05Hz frequency deviation at the POI bus. To fulfill the grid code requirements, the active power is supposed to decrease when the POI bus frequency goes up. HVRT test: to test if the Intermittent Renewable Resources (IRRs) can remain interconnected to the system during the following high-voltage conditions as illustrated in Fig. 3. The generation resource shall not cease providing real or reactive power except to the extent needed to provide frequency support or aid in voltage recovery [9]. LVRT test: similar to HVRT test, the low voltage profile under LVRT test is illustrated in Fig 3. Multi-LVRT test: every two seconds, POI bus is subjected to a six-cycle (0.1 second) three phase fault. Ten (10) times of such consecutive faults are simulated in the test. The purpose of the test is to identify the limits of time duration or times associated with the generator modeled LVRT capability. MultiLVRT issue was brought to industry’s attention since a large amount of wind generation significantly reduced power output reacting to multiple voltage dips in South Australia (SA) system and caused transmission line overload and finally blackout occurred in SA on September 28, 2016 [10]. Any other voltage & frequency response: Users can create a voltage & frequency profile in time-domain to test the model response. For example, users can create a voltage & frequency profile derived from the recording data in a real disturbance event to run the model validation such as NERC MOD-26, MOD-27 and MOD-33 analysis. Where: X: reactance of the POI Bus – Infinity Bus line (pu) SCR: short-circuit ratio number P: active power output of the power plant under test (pu) Prior to the SCR limit test, the initial power flow solution is based on the zero impedance line model in FS test which means the infinity bus voltage and angle are the same as the POI bus. However, the infinity bus voltage and angle will be greatly deviated from POI bus when SCR is very low and sometimes the platform experiences a power flow convergence issue with the Newton-Raphson method under extremely low SCR. To overcome the convergence issue, the infinity bus voltage and angle are set up based on: ∗ sin ∗ ∗ ∗ Where: Fig. 2 System Configuration for Voltage and Frequency Test : Infinity bus voltage magnitude (pu) : Infinity bus voltage angle (radian) P: active power output of the power plant (pu) Q: reactive power output of the power plant (pu) VPOI: initial POI bus voltage (pu) X: reactance of the POI Bus – Infinity Bus line (pu) With the aforementioned setup, the power flow under any SCR value can reach to convergence within one step. Fig. 3 ERCOT Voltage Ride-Through Boundaries for IRRs Table I. Voltage & Frequency Profile table for HVRT test Time (sec) 5 5.2 5.2 5.5 5.5 6 6 25 Voltage (pu) 1.2 1.2 1.175 1.175 1.15 1.15 1.1 1.1 Frequency (Hz) 60 60 60 60 60 60 60 60 C. SCR Limit Test Instead of using zero impedance line, the platform set up the reactance (in per unit) associated with the line of POI Bus – Infinity Bus: ∗ Fig. 4 System Configuration for SCR limit Test III. MODEL REVIEW EXPERIENCES A. HVRT test As shown in Fig. 5 and 6, a solar generation model (Model A_01) initially failed in the HVRT test since the generator ceased the active power during the HVRT test, which is not allowed based on the ERCOT protocol. Based on the platform’s feedback, the manufacturer tuned the control parameters and the updated model (Model A_02) passed the HVRT test. Another HVRT test associated with a wind generation model (Model B_01) indicates the reactive power increases when the POI voltage is very high during HVRT test, as shown in Fig. 7. It is unreasonable and against the voltage control purpose. Based on the platform’s feedback, the manufacturer tuned the control parameters and the reactive power response with the updated model (Model B_02) is reasonable. 1.225 in 20 seconds. As shown in Fig. 8 and 9, the generator active power successfully recovered even after 10 times of 3 Phase bolted fault in 20 seconds. However, it may indicate that the model has not included the limit associated with the generator’s real VRT capability or the actual protection settings with the generator. ERCOT will confirm it with the manufacturer. 1.1 1.2 1 1.175 0.9 1.15 0.8 1.125 0.7 0.6 1.1 0.5 1.075 0.4 1.05 0.3 1.025 0.2 0.1 1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 Time (seconds) 0 5 10 15 20 25 30 35 Time (seconds) Fig. 5 POI voltage profile for HVT test (Model A and B) Fig. 8 POI Voltage Profile for Multi-LVRT test (Model C) 2.5 2.25 2.5 2 2.25 1.75 2 1.5 1.75 1.5 1.25 1.25 1 1 0.75 0.75 0.5 0.5 0.25 0.25 0 0 -0.25 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 -0.25 0 Time (seconds) 5 10 15 20 25 30 35 Time (seconds) Fig. 9 Active Power Response during Multi-LVRT test (Model C) Fig. 6 Active Power Response during HVT test (Model A) C. SCR test A wind generation model (Model D) survived with a large disturbance (3 Phase bolted fault) under extreme SCR value (0.7). ERCOT will investigate it in detailed PSCAD simulation. 0.5 0.4 0.3 0.2 0.1 1.3 0 1.2 1.1 -0.1 1 -0.2 0.9 0.8 -0.3 0.7 -0.4 0.6 -0.5 0.5 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Time (seconds) 0.4 0.3 Fig. 7 Reactive Power Response during HVT test (Model B) 0.2 0.1 0 0 1 2 3 4 5 Time (seconds) B. Multi-LVRT test A wind generation model (Model C) passed the MultiLVRT test with 10 times of 3 Phase bolted fault at the POI bus Fig. 10 Voltage Response during SCR test (SCR = 0.7, Model D) Channel Plot em_Incident_Reports/2017/Integrated-Final-Report-SA-Black-System28-September-2016.pdf, Mar. 2017 3 2.5 2 1.5 1 0.5 0 -0.5 -1 -1.5 0 1 2 3 4 5 Time (seconds) Fig. 11 Power Response during SCR test (SCR = 0.7, Model D) IV. CONCLUSIONS ERCOT developed a dynamic model review platform to evaluate the dynamic performance for all the generation resources. The tests include voltage and frequency response tests and SCR limit tests. The test results can be utilized for grid code compliance studies, NERC compliance studies, and help manufacturers to optimize the control behavior. ERCOT is currently utilizing the platform as the screening tool to assess the dynamic performance associated with the generation resources with proprietary dynamic models. In the future, ERCOT is considering to add optimization module to the platform so it could directly facilitate NERC MOD-33 studies. REFERENCES [1] W. Winter, K. Elkington, G. Bareux and J. Kostevc, "Pushing the Limits: Europe's New Grid: Innovative Tools to Combat Transmission Bottlenecks and Reduced Inertia," in IEEE Power and Energy Magazine, vol. 13, no. 1, pp. 60-74, Jan.-Feb. 2015. [2] NERC MOD (Modeling, Data, and Analysis) Standard, August 1, 2017, Available: http://www.nerc.com/pa/Stand/Reliability%20Standards%20Complete %20Set/RSCompleteSet.pdf [3] ERCOT Quick Facts, October 2017, available: http://www.ercot.com/content/wcm/lists/114739/ERCOT_Quick_Facts _102717.pdf [4] Siemens Power Technologies International, PSSE 33.10 Program Operation Manual, April 2017. [5] C. C. Tsai et al., "Practical Considerations to Calibrate Generator Model Parameters Using Phasor Measurements," in IEEE Transactions on Smart Grid, vol. 8, no. 5, pp. 2228-2238, Sept. 2017. [6] P. Venne, X. Guillaud and F. Sirois, "Testing power system controllers by real-time simulation," 2007 Large Engineering Systems Conference on Power Engineering, Montreal, Que., 2007, pp. 13-17. [7] T. H. S. Bossa, N. Martins, R. J. G. C. da Silva and P. C. Pellanda, "A Field Test to Determine PSS Effectiveness at Multigenerator Power Plants," in IEEE Transactions on Power Systems, vol. 26, no. 3, pp. 1522-1533, Aug. 2011. [8] Y. Zhang, S. H. F. Huang, J. Schmall, J. Conto, J. Billo and E. Rehman, "Evaluating system strength for large-scale wind plant integration," 2014 IEEE PES General Meeting | Conference & Exposition, National Harbor, MD, 2014, pp. 1-5. [9] ERCOT Nodal Operating Guide Chapter 2.9, July 1, 2107, available: http://www.ercot.com/mktrules/guides/noperating [10] AEMO, “Black System South Australia 28 September 2016 – Final Report”. [Online]. Available: https://www.aemo.com.au//media/Files/Electricity/NEM/Market_Notices_and_Events/Power_Syst