ANSI/IEEE C57.92-1981 guide for loading mineral-oil-immersed power transformers up to and including 100 MVA with 55°C or 65 °C winding rise .... <Xl C"l .... N � I' It) (.) w w w -CI) z « December 14,1981 SH06031 Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. An American National Standard IEEE Guide for Loading Mineral-Oil-Immersed Power Transformers Up to and Including 100 MV A with 55°C or 65°C Average Winding Rise 1. Scope 2. References 1.1 This guide covers general recommendations for loading mineral-oil-immersed power trans­ formers, manufactured in accordance with ANSI C57.12.10-1976 [1] 1 and ANSI C57.12.30-1977 [2] and other oil-insulated power transformers up to and including 100 MVA maximum nameplate rating. It is based mostly on aging of the winding insulation. [1] ANSI C57.12.10-1976, American National S t a ndard Requirements for Transformers 230 000 V and below, 833/958 through 8333/10417 kVA Single Phase, 750/862 through 60 000/80 000/100 000 kVA Three Phase 2 [2] ANSI C57 .12.30-1977, American National Standard Requirements Load-Tap-Changing Transformers 230 000 V and below, 3750/ 4687 through 60 000/80 000/100 000 kV A Three Phase Loading of transformers larger than 100 M VA may be limited by factors other than insulation aging such as stray flux, etc. When it is known that such limitations do not exist and insula­ tion aging rather than oil temperature, gassing, tank heating, etc is the controlling factor, this guide may be used. This guide may also be used for askarel filled transformers. [3] ANSI/IEEE C57 .12.00-1980, General Re­ quirements for Liquid-Immersed Distribution, Power, and Regulating Transformers [4 ] ANSI/IEEE C57.91-1981, Guide for Loading Mineral-Oil-Immersed Overhead-Type Distribution Transformers with 55°C or 65°c Average Winding Rise 1.2 Recommendations for transformers with an insulation system which conforms to the 65°C curve shown in Fig 1, those rated at an average winding temperature rise of 65°c and a hottest-spot temperature rise of 80°C, are contained in Section 4 of this guide. Recom­ mendations for transformers with an insulation system which conforms to the 55 °c curve shown in Fig 1, those rated at an average winding temperature rise of 55°C and a hottest-spot temperature rise of 65 DC, are contained in Section 5 of this guide. 3. General Limitations 3.1.1 It must be recognized that there may be limitations to loads above rating which a transformer can carry other than the capacity of the windings and cooling system. Among these limitations are: oil expansion, pressure in sealed units, bushings, leads, tap changers and stray flux heating as well as the thermal capability of associated equipment such as cables, reactors, circuit breakers, disconnecting switches, and current transformers. High am­ bient temperatures will also restrict a trans­ former's loadability. Any of these items may limit loading and manufacturers should be 3.1 1. 3 The method used for computer calculation of the Capability Tables for Normal and Moderate Sacrifice of Life in Section 4 and Section 5 of this guide and examples for developing them by hand calculations are contained in Section 6 and Section 7. 2 A NS I d oc uments are available from The American National Standards Institute, 1430 Broadway, New York, NY 10018. IThe numbers in brackets correspond to the refer­ ences listed in Section 2 of t his guide. 9 Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE C57.92-1981 IEEE GUIDE FOR LOADIN G MINERAL-OIL-IMMERSED POWER consulted for advice on such limitations. Any transformer that is expected to carry heavy loads where the top-oil temperature may reach limiting values should have good oil with a flash point of not less than 145°C since the oil in the cooling ducts adjacent to the windings may exceed the top-oil temperature by a number of degrees. Operation at hottest-spot temperatures above 140 C may cause gassing in the solid insula­ tion and oil. Gassing may produce a potential risk to the dielectric strength integrity of the transformer and this risk should be considered when the guide is applied. 3_1.2 Transformers are sometimes installed in indoor vaults with natural ventilation_ This type of installation results in a higher ambient temperature than the outdoor air. The increase in effective ambient temperature for expected transformer operation must be determined before loading limitations can be estimated. daily loss of insulation life which are in addition to normal loss of insulation life. 3.3 Transformer Rated Output 3.3.1 The terms rating, rated output, rated load and full load used in this guide refer to nameplate rating. 3.3.2 The temperature rise on which the rating of a transformer is based takes into consideration the experience of the industry regarding: (1) Insulation life as affected by operating temperatures (2) The ambient temperature assumed to exist throughout the life of the transformer 3.3.3 The actual output which a transformer can deliver at any time in service with normal life expectancy may be more or less than the nameplate rating, depending upon the ambient temperature and other operating conditions. ° 3.4 Aging of Insulation 3.4.1 Aging or deterioration of insulation is a function of time and temperature. Since, in most apparatus, the temperature distribution is not uniform, that part which is operating at the highest temperature will ordinarily undergo the greatest deterioration. Therefore, in aging studies it is usual to consider the aging effects produced by the highest (hottest-spot) temper­ ature. 3.4.2 Much of the fundamental data on aging of insulation at different temperatures has been based on laboratory and model tests in which the decrease in mechanical and electrical strength has been measured. Under the auspices of the IEEE, a series of life expectancy tests were made under controlled conditions on production. type distribution transformers. Data from these tests were used as the basis for the distribution transformer Life Expectancy Curves in ANSI/IEEE C57.91·1981. While these are the best insulation life data available at this time, they are not directly applicable to power transformers. Because the end point strength of insulation (the final strength of aged insulation) must be greater in power transformers and because model tests of power transformers have not yet been reported, the power transformer insulation life expectancy curves were selected to be more conservative than those used for distribution transformers. The transformer life expectancy predictions contained herein are based on the insulation life expectancy curves shown in Fig 1 and do 3.2 Transformer Life Expectancy 3.2.1 Recommendations in this guide are based on the life expectancy of transformer insulation as affected by temperature and time. 3.2.2 Transformer life expectancy at various operating temperatures is not accurately known, but the information given regarding loss of insulation life at elevated temperatures is considered to be conservative and the best that can be produced from present knowledge of the subject. The word conservative is used in the sense that the actual insulation life at any temperature is expected to be not less than indicated in this guide. The effects of tempera­ ture on insulation life are subject to further investigation and new data may affect future revisions of this guide. 3.2.3 In Tables 3(a)-3(u) and 5(a)-5(u) the normal loss of life loads are loadings which result in a daily loss of life equal to that of a continuous winding hottest-spot temperature of 110°C and 95 °c for 65°C rise and 55°c rise transformers, respectively . Normal life ex­ pectancy is 6.5 104 hours, a daily normal loss of life of 0.0369%. Aging at other than rated temperature is calculated using the equations for power transformer insulation life expect­ ancy in Fig 1. The actual life should be considerably greater than 6.5 104 hours for the reasons mentioned in 4.1.2.4. 3.2.4 In Tables 3(a)-3(u) and 5(a)-5(u) the moderate sacrifice of life expectancy values are • • 10 Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. TRANSFORMERS UP TO 100 ANSI/IEEE C57.92-1 981 ° MVA WITH 55 C OR 65 ° c AVERAGE WINDING RISE �/ II;.uV / ." '" <0 Ul '" ::J � i:' ::J -' / .,. .,. .,. 4 10 '" 0 z '" i% ,., '" ,., i ,- .:: <0I, � c.., &Q- --.J (!J� !J 10 2 300280 260 240 220 200 r1 .,. ,., 7%, {�/j '" '" '" <l lE 180 it' / I ;' (() /.,. � NATURAL LOG CONSTANTS � / '3 I . Ju 140 120 B A 65 °C RISE - 30 834 16054 0 II") (/� 160 '" 55 °C RISE-32 543 16054.0 80 100 60 40 HOTTEST- SPOT TEMPERATURE IN 'C RECIPROCAL OF ABSOLUTE TEMPERATURE SCALE Fig 1 Life Expectancy Curve not take into account deterioration of gaskets, rusting of tanks, etc which result from factors other than winding temperatures. While the life expectancy curves are believed to be conservative, any estimates of trans­ former life derived therefrom are intended only as a guide. 304_3 Because the cumulative effects of tem­ perature and time in causing deterioration of transformer insulation are not thoroughly es­ tablished, it is not possible to predict with any great degree of accuracy the length of life of a transformer even under constant or closely controlled conditions, much less under widely varying service conditions. 30404 The relation of insulation deterioration to changes in time and temperature is assumed to follow an adaptation of the Arrhenius reaction rate theory which states that the logarithm of insulation life is a function of the reciprocal of absolute temperature: LoglO (hours of life) = A+B T (Eq 1) where T = absolute temperature in degrees Kelvin (8hs + 273) 8hs = hottest-spot temperature, 0 C A and B = constants from desired life expectancy curve A and B values for both IOglO and loge are shown on Fig 1. 11 Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. ANSI/IE EE C57.92-1 981 IEEE GUIDE FOR LOADING M IN ERAL-OIL-IMM ERS ED POWER These ambients should be used as follows: for loads with normal life expectancy, use item (1) as the ambient for the month involved; for short-time loads with moderate sacrifice of life expectancy, use item (2) for the month in­ volved. During any one day the average or maximum temperatures may exceed the values derived from (1) or (2) above. To be conservative, it is recommended that these temperatures be in­ creased by 5 a C since aging at higher than average temperature is not fully compensated by decreased aging at lower than average temperature. With this margin the approxi­ mated temperature will not be exceeded on more than a few days per month and, where it is exceeded, the additional loss of life will not be serious. 3.5.2 Influence of Ambient on Loading for Normal Life Expectancy. Average ambient temperatures should cover periods of 24 h with maximum temperatures not more than 10 aC greater than average temperatures for air and 5°C for water. Table 1 gives the increase or decrease from rated loads for other than average daily ambients of 30°C for air and 25 a for water. It is recommended that the 5°C margin described in 3.5.1 be used when applying the factors from Table 1. It should be pointed out that the increase or decrease obtained from Table 1 is more conservative than the corresponding values shown in Table 3(a)-3(u) and 5(a)-5(u) which are based on Tables 2 and 4 (assumed transformer char-. acteristics), and therefore do not check these tabulations exactly. Table 1 is for quick ap­ proximations. Loading on the basis of ambient temperature with loads permitted in Table 1 will give approximately the same life expectancy as if transformers were operated at nameplate rating and standard ambient temperatures over the same period. Table 1 covers a range in ambients of 0 °c to 50°C for cooling air. A check should be made with the manufacturer before loading on the basis of ambient air less than 0 °c or greater than 50°C. Since ambient temperature is an important factor in determining the load capability of a transformer, it should be controlled for indoor installations by adequate ventilation and should always be considered in outdoor instal­ lations. 3.4.5 The many variables mentioned, and particularly the many varying conditions of load and ambient to which a transformer can be subjected in service, make it impossible to give definite rules for the loading of trans­ formers. It is possible to give only suggested loadings under specified conditions with the expectation that the user will adjust this information to suit his particular application. 3.5 Ambient Temperatures and Its Influence on Loading. Ambient temperature is an impor­ tant factor in determining the load capability of a transformer since the temperature rises for any load must be added to the ambient to determine operating temperatures. Transformer ratings are based on a 24 h average ambient of 30 aC. This is the standard ambient used in this guide. The ambient temperature to be used for water-cooled transformers is the cooling water temperature plus an added 5°C to allow for possible loss of cooling efficiency due to deposits on cooling coil surfaces of water­ cooled transformers in service. Whenever the actual ambient can be meas­ ured, such am bients should be used in deter­ mining the transformer's temperature and loadability. The ambient air temperature seen by a transformer is the air in contact with its radiators or heat exchangers. In some instal­ lations the transformer may be outdoors but surrounded by buildings or sound deadening walls. This may result in recirculation of heated air, the ambient should be adjusted accord­ ingly. 3.5.1 Approximating Ambient Temperature for Air-Cooled Transformers. It is often neces­ sary to predict the load which a transformer can safely carry at some future time in an unknown ambient. The probable ambient temperature for any month may be approximated as follows from reports prepared by the National Weather Service of the US Department of Commerce for various sections of the country: (1) Average Temperature. Use average daily temperature for the month involved averaged over a number of years. (2) Average of Maximum Daily Temper­ atures. Use average of the maximum daily temperatures for month involved averaged over several years. 12 Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. TRANSFORMERS UP TO 100 MVA WITH 55 a C OR 65 a C ANSI/IEEE AVERAGE WINDIN G RISE C57.92-1981 Table 1 Loading on Basis of Temperatures (Ambient other than 30 °C and Average Winding Rise Less than Limiting Values) (For Quick Approximation) (Ambient Temperature Range 0 ac to 50 ° C) % of R ating Ty pe of Cool ing Decrease Lo ad for E ach °c H igher Temperature Increase Load for a Each C Lower Temperature 1.5 1.5 1.0 1.0 1.0 1.0 0.75 0.75 Self-cooled - OA Water-cooled - OW Forced-air-cooled- OA/FA, OA/FA/FA Forced-oil-cooled - FOA, FOW and OA/FOA/FOA 3.6 Operation with Part or All of the Cooling Out of Service. Where forced-cooling equip­ ment, such as pumps or fans or both, is used to increase the cooling efficiency, the transformer may be required to operate for some time with this equipment inoperative. The permissible loading under such conditions is given in the following paragraphs. For multi-rated transformers (OA/F A, OAf FA/FA, OA/FOA/FOA) with all or part of the forced cooling inoperative, use the nameplate rating based on the cooling in operation and load on this basis. When either the pumps or the fans of a cooling unit are out of service, the entire cooling unit should be considered inop­ erative. For forced-oil-cooled (FOA or FOW) trans­ formers with all pumps or fans or both inoperative, heeding the following guidelines should prevent undue injury to the trans­ former: 3 (1) Rated load may be maintained for ap­ proximately 1 h following normal operation at nameplate rating in a 30 °C ambient (2) Rated load may be carried for approxi­ mately 2 h if started with windings and oil in a 30 °c ambient. (3) Rated voltage may be maintained for 6 h at no load, following continuous operation at nameplate rating in a 30 °C ambient with cool­ ing equipment in operation. (4) Rated voltage may be maintained for 12 h at no load starting with windings and oil in a 30 °C ambient For forced-oil-cooled transformer (FOA or FOW) ratings with part of the coolers in operation, use the following reductions in permissible loading: %of Total Coolers in Operation Permissible Load in % of Nameplate Rating 100 80 60 50 40 33 100 90 78 70 60 50 These permissible loads give approximately the same temperature rises as would full load with all cooling in operation. 3.7 Supplemental Cooling of Existing Self­ Cooled Transfonners. The load which can be carried on existing self-cooled transformers can usually be increased by adding auxiliary cool­ ing equipment such as fans, external forced-oil coolers, or water spray equipment. The amount of additional loading varies widely, depending upon: (1) (2) (3) (4) Design characteristics of the transformer Type of cooling equipment Permissible increase in voltage regulation Limitations in associated equipment No general rules ean be given for such supplemental cooling, and each transformer should be considered individually. 3 The oil temperature for large units may exceed a 110 C. Che ck with the m anufa cturer for l im itations. 13 Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE C57.92-1981 IEEE GUIDE FOR LOADING MINERAL-OIL·IMMERSED POWER 4. Transfonners Specified to have an Average It should be recognized that, due to thermal ° Winding Rise of Not More Than 65 C and Hottest-Spot Winding Rise of Not More Than 80 °c lag in oil rise, time is required for a transformer to reach a stable temperature following any change in load. Therefore, higher peak loads may be carried for short durations. This is reflected in the loading tables and the basic 4.1 Basic Loading for Normal Life Expectancy equations in 6.7.3. 4.1.1 Basic Conditions If (1) The basic loading of a transformer for the are not characteristics transformer normal life expectancy is continuous loading at accurately known, a maximum top-oil temper­ normal ature derived from Fig 2 may be used as an rated output service when operated under indicated conditions as approximation. Loading from Fig 2 is based on in 2.1.1 (1), ANSI/IEEE a difference of 25°C between the hottest-spot C57.1 2.00-1979 [3]. It is assumed that opera­ temperature and top-oil temperature at rated 2.1.1 and (2), 2.1.1 (3) of 30°C for load for self-cooled transformers, tion under these conditions is equivalent to transformers (133% and operation in a continuous ambient temperature forced-air-cooled of 30 °C for cooling air or 25 °C for cooling under) and 35°C for forced-oil-cooled trans­ water. Normal life expectancy will result from formers. operating with a continuous hottest-spot con­ 4.1.2.2 Continuous Loading on Basis of Average Winding Test Temperature Rise. For ductor temperature of 110°C (or equivalent each °c variable temperature with 120 °c maximum) in because of the A 5° margin is used t o provide a tolerance in the voltage hottest-spot temperature of rise. The which the temperature transformer can carry at 65°C rise. Since this location. The hottest-spot allow­ may increase the loading beyond that contem­ ances are based on tests of laboratory models. (3) The measurement loadability thus obtained is that hazard when placing a temperature detector at the proper 5° that the average rated load by the percentages given in Table 1 . temperature cannot be directly measured on designs of the transformer load may be increased above (2) The hottest-spot conductor temperature determines loss of life due to loading. This commercial excess in winding test temperature rise is below 65°C, any 24 h period. plated by the designer, the limitations given in at rated 3.1 load is usually taken as the sum of the average be should before checked taking full advantage of this increased loadability. winding temperature and a 15°C allowance4 Some transformers are designed to have the for the hottest spot. For mineral oil-immersed difference between the hottest-spot and aver­ transformers operating continuously under the age conductor temperatures greater than the foregoing conditions with normal life expect­ 15°C allowance. This will result in an average­ ancy, this temperature has been assumed to be winding temperature rise of less than 65 °C, a maximum of 1 1 0°C. 4.1.2 Loading for Nonnal Life Expectancy but the hottest-spot winding temperature rise under Specified Conditions 4.1.2.1 Loading by Oil Temperature. Oil transformers should not be loaded above their temperature alone should not be used as may be at the limiting value of 80 °C. Such rating as outlined in this section. The manu­ a facturer should be consulted for information guide for loading transformers. The hottest­ on the hottest-spot allowances used for these spot to top-oil gradient at full load should be designs. determined from factory tests using Eq 8 or, This condition may exist in trans­ formers with large differences (greater than lacking data, a value should be assumed. The 30°C) between top- and bottom-oil temper­ full-load hottest-spot to top-oil gradient should atures and may be checked approximately by be corrected to that for the actual load carried measuring the top and bottom radiator temper­ using Eq 7 or Fig 9. This gradient subtracted atures. Whenever possible, data on hottest-spot from 110°C will give the maximum permis­ and oil temperatures obtained from factory sible oil temperature for nonnal life expect­ temperature tests should be used in calculating ancy. transformer 4If cooler inlet and outlet temperatures are available, a better estimate of the h ottest-spot temperature is p ossible by making an adjustment in the 15 0 C allow­ ance. C onsult with the manufacturer. loadability or when calculating temperatures for loads above rating. 4.1.2.3 Loading on Basis of Short-Time Loads above Rating. Transformers may be 14 Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. TRANSFORMERS UP TO 1 00 MVA WITH 2.0 1.8 '" 0 0 ..J t: z :::> 0: 55 DC OR 6 5 ° C '" � � 1.6 b,. � "' a. � 1.4 SELF COOLED FORCED AIR C FORCED OIL "'- � � � " � 40 30 20 A B � 1.2 10 ANSI/IEEE C57.92·1981 AVERAGE WINDIN G RISE � � � � �� ��[\ 70 60 50 80 90 TOP, OIL TEMP "C Fig 2 Approximate Continuous Loading for Nonnal Life Expectancy D 65 C Rise Transfonners operated ature for above 110°C hottest-spot temper­ short periods provided they 4.1.2.5 Basis for Nonnal Loss o f Life Loading in Tables 3(a)-3(u). The transformer are operated for much longer p eriods at temper­ capabilities for nonnal loss of life in Tables that thermal aging is a cumulative process and atures that result in aging equ h;-alent to that for 3(a )-3( u) are based on operation at temper­ atures below 11 0°C. This is due to the fact thus permits loads above the rating to be safely carried under continuous operation at 110 many conditions without en­ croaching upon the nonnal life expectancy of the converted load cycle and ambient condi­ life expectancy are given in Tables 3 (a)-3( u ) . For conservative use of these tables, tions during a 24 h period. The 1 1 0 °C hot­ it is test-spot temperature is based on the hottest­ D C margin described in spot rise of 80°C plus the standard ambient 3.5.1 be used in detennining the ambient temperature of 30 temperature. 6.5 . 104 hours or over seven years. Actually a transfonner operating outdoors at rated ca­ vices are supplied, when specified, which indi­ a simulated hottest-spot D D C. At 110 C insulation temperature, Fig 1 indicates the life would be 4.1.2.4 Loading by Hottest-Spot Temper­ ature Indicator. Hottest-spot temperature de­ cate C hottest-sp ot temperature as detennined from Fig 1 and the hottest-spot temperature profile resulting from the transformer. Suggested loadings for nonnal suggested that the 5 0 pacity would have a much longer life because the annual average ambient air temperature in temperature. These devices may be used as a guide to limit most locations in the US does not exceed are calibrated for use with specific transformers ° 20°C by m ore than a few degrees. At 100 C ° (20 DC ambient temperature plus 80 C hot­ test-spot rise), Fig 1 indicates the life would be 2 lOS hours or over 22 years. If the loading and simulate the hottest-spot temperature by over weekends is lighter, as is normally the load and ambient temperature. Higher loads are years. loads. Thermal relays, when supplied, indicate tem­ peratures reached in the windings. These relays • taking into account preceding loading, existing permitted for short periods than for case, the total life could extend to over 30 long In periods of time because of the transfonner's areas where the annual mean ambient temperature time constant. exceeds 25°C, the capability values in the tables should be reduced 1.5% for 15 Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE C57.92-1981 every IEEE GUIDE FOR LOADING M INERAL-OIL-IMMERSED POWER degree exceeds 20 a the mean annual temperature and C. This reduction in peak loading the wide range in ratings covered are reasons why this loading guide is made conser­ is intended to compensate for the fact that vative in its suggested loadings. Some of the generally higher ambient temperatures through­ variables out temperature between localities; differences in the year temperatures, will for result in higher winding are: wide differences in ambient any assumed annual load elevation; restricted air circulation caused by cycle, causing greater insulation deterioration. buildings, fire walls, etc; previous emergency If this correction is made, no correction of the loading history which may not be known to ambient temperatures shown in the table will the operator; and variations in design character­ be necessary, and these should be the antici­ istics from those in Table 2. As a guide, an pated values associated with the occurrence of average loss of life of 1 % per year or 4% in any the peak load. one emergency operation is considered reason­ The method used to calculate Tables 3(a)- able by some users. 3(u) is given in Section 6. 4.2.2 Methods for Determining Loads above Rating with Some Sacrifice of Life Expectancy 4.2 Short-Time Loading with Moderate Sacri­ 4.2.2.1 Transformers with Known Specific fice of Life Expectancy Characteristics. If the specific characteristics of 4.2.1 Aging of Insulation Due to Operation a transformer are known and maximum recom­ above 110 °c Hottest-Spot Temperature (1) mended capability is required, the user may When the aging effect of one load cycle calculate the oil rise and hottest-spot temper­ or the cumulative aging effect of a number of ature using either the graphic solution illus­ load cycles is greater than the aging effect of trated in Section continuous operation at rated load over the same period of time, the insulation deteriorates at a faster rate than allowable load for his conditions by taking into account the ambient temperature, probable normal. The rate of deterioration is a function of time and temper­ number of such loads during the life of the ature and is commonly expressed as a percent­ age loss of life. transformer, and the approximate percentage Charts and tables showing of life he is willing to sacrifice. 4.2.2.2 Transformers with Unknown Spec­ percent loss of life for various combinations of time and continuous temperature are given in ific Fig 3. (2) It should be clearly understood that, not known various conditions, this 4.2.2.3 Assumed Characteristics for Trans­ formers which Allow the Loadings in Tables tion is generally characterized by a reduction in 3(a)-3(u). Transformers vary widely in the both mechanical and dielectric strength, but characteristics these characteristics may not necessarily be affect their short-time all transformers of a given class must be based charred condition will have sufficient strength on characteristics which give conservative re­ to withstand normal operating electrical and sults. The characteristics shown in Table 2 are mechanical stresses. A transformer having insu­ considered typical of a power transformer and lation in this condition may continue in service are for general use. for many months or even years if undisturbed. 4.2.2.4 Temperature and Load Limitations. On the other hand, any unusual movement of The following are recommended individually such as may be caused by limiting temperatures and loads and are used in expansion of the conductors, due to heating Tables 3(a)-3(u). (1) resulting from a heavy load or to large electro­ magnetic forces resulting from short circuit, Maximum top-oil temperature - (2) Maximum hottest-spot conductor may disturb the weakened insulation such that temperature - turn-to-turn or layer-to-layer failure will result. of which capabilities. Any general guide which applies to directly related. In some cases, insulation in a (3) The uncertainty or when conservative operation ing explicit preload conditions. former insulation life. Deterioration of insula­ conductors Loads. of permitted loads of various durations follow­ information can only be an indicator of trans­ the Conservative bility Tables, Table 3(a)-3(u), for tabulations estimating the relative loss of life due to loads under or above rating is satisfactory, refer to the Capa­ considered to be conservative and helpful in rating Characteristics When specific transformer characteristics are while the insulation aging information used is above 6 or the basic formulas in 6.7. With this data, the user may determine the 1100 C 180°C (3) Maximum short-time service conditions loading - 2 . rating 16 Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. TRANSFORMERS UP TO 100 MVA W ITH 55 ° C OR 65 ° c 5 ANSI/IEEE C57.92-1981 AVERAGE W INDING R ISE MAXIMUM PERCENT LOSS OF LIFE 65 C RISE TRANSFORMERS " 3 .... z w U 0:: W a. , w ... 2 :J ... a C/) 0.5 C/) a J � :::> 0.3 )( '" � 0.2 ! 0.1 �----��-----H�--�4---�--+-�--�---4- 0.05 L-L-__�__-L__-LL-__-L�__-L__�-L____L-____�______� 110 120 130 150 140 170 160 HOTTEST-SPOT TEMPERATURE IN ·C 180 *Expressed as percent loss of life for one occurrence of specified time duration for operation at temperature indicated. Hottest-Spot Temperature in Degrees Maximum Loss of Life (%) Duration Hours 0.1 1 1 2.00 4.00 0.25 0.50 161 172 180 153 163 172 2 145 155 163 172 180 4 138 147 155 163 172 180 8 131 140 147 155 163 172 24 120 129 136 143 150 158 2' 1.00 180 Fig 3 Maximum Loss of Life - 65°C Rise Transformers 17 Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE C57.92·19S1 IEEE GUIDE FOR LOADING MINERAL·OIL·IMMERSED POWER Table 2 65 DC Rise Transformers - Assumed Characteristics at Rated Load Effective Cooling Mode OA or OW FA 133% or Less FA** over 133% Directed FOA or FOW Non·Directed FOA or FOW Hottest·spot conductor t emperature rise (above D ambient) C 80 SO SO SO 80 Top·oil temp erature rise (above ambient) °c 55 50 45 45 45 Top-oil time constant, (h) 3.0 2. 0 1.25 1.25 1.25 Hottest·spot conductor time co nstant, (h) 0.08 0.08 0.08 0.08 0.08 Ratio of load to iron losses 3.2 4.5 6.5 6.5 6.5 *m (wi nding exponent) O.S 0.8 O.S O.S 1.0 *n (oil exponent) O.S 0.9 0.9 1.0 1.0 *m is the exponential power of winding loss versus winding temperature rise. *n is the exponential power of total loss versus top·oil temperature rise. The i nd icated values of m and n are approximate, p articularly in t he more complicated d esigns, and are subject to further study. **Some OA/FA/FA designs follow more closely the values for FA (133% or l ess). 4.2.2.5 Load Cycles. Transformers usually operate on a load cycle which repeats each 24 h. This load cycle may be constant or it may have one or more peaks during the 24 h period. The actual load cycle may be converted to a two-step cycle by the method given in 6.6. Where actual average loads before the peak load differ from those in the tabulations, sufficient accuracy can be obtained by inter­ polation. Index f o r Table 3 0 65 C Rise Transformers (A Tabulation of Loads for Normal and Moderate Loss of Life) Following initi al load of: Typ e of Cooling 4.2.2.6 Basis for Moderate Sacrifice of Life Loading in Tables 3(a)-3(u). Load values in Tables 3(a)-3(u) are based on the life expect­ ancy data shown in Fig 1, the assumed trans­ former characteristics from Table 2 and the calculated hottest-spot temperature profile for the daily load cycle and ambient temperature condition that exists during the 24 h period. The loss of life values shown in Tables 3(a)3(u) are in addition to the normal loss of life of 0.0369% per 24 h which would result from continuous operation at rated load in a con­ stant 30 DC ambient. 5 0% 70% 90% (c) (c ) ( d) (d ) 100% Self·cooled (OA) Water·cooled (OW) Forced ·air·coole d * (OA/FA) (a) (a ) (b) (b) (e ) (f) (g) (h) Forced ·oil·cooled, Directed flow, ( FOA, FOW, OA/FOA/FOA**) (i) (j) (k) (I) Forced·air·cooled** ( OA/FA/FA) (m) (n ) (p ) (q) Forced-oil·cooled, Non·directed flow, (FOA, FOW, OA/FOA/FOA**) (r) (s) (t) (u) *Ratings 133% or less of self·cooled rating **Ratings greater than 133% of self-cooled rating 18 Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. >-l Table 3(a) Capability Table for Normal and Moderate Sacrifice of Life 65 ° C Rise, Self-Cooled (OA) and Water-Cooled* (OW) Transformers Equivalent Load Before Peak Load 50% of Nameplate Rating ::c > z 00 "'i 0 ::c s: = Ambient ° c Hours of Peak Load 1 2 t-' (J:J 2 % R 24 s HotSpot 30 Peak Load Per n it) HotSpot Temp 46 2.00 131 56 2.00 141 66 60 2.00 146 70 1.95 2.00 152 156 79 80 T o pOil Temp HotSpot Temp Normal 0.25 0.50 1.00 2.00 4.00 2.00 121 Normal 0.25 0.50 1.00 2.00 4.00 2.00 136 N o rmal 0.25 0.50 1. 00 2.00 4.00 1.89 2.00 N o m al 0.25 0.50 1.00 2.00 4.00 1.63 1.82 1.89 1.95 140 154 172 191 85 99 103 108 1.54 1.73 l.80 1.87 139 163 171 180 89 102 107 112 1.45 1.65 1. 71 Normal 0.25 0.50 1.00 2.00 4.00 1.45 1.61 1.66 1.72 1.78 130 152 160 169 177 65 99 103 108 114 1.36 1.53 1.59 1.65 129 151 159 168 88 102 107 112 1.27 1.45 1.51 129 151 158 92 106 110 1.18 1.37 1.43 128 150 158 95 109 114 1.08 1.28 No rmal 0.25 0.50 1.00 2.00 4.00 1.28 1.44 1.48 1.54 1.59 1.65 113 133 140 147 155 163 76 88 93 97 102 107 1.20 1.36 1.41 1.46 1.52 1.58 113 133 140 147 154 163 79 92 96 101 106 111 1.11 1.28 1.34 1.39 1.45 1.50 113 133 140 147 154 162 83 96 100 105 109 114 1.02 1.20 1.25 1.31 1.37 113 132 139 147 1�4 87 99 103 108 113 - 0.92 1.11 1.17 1.23 J (o C) (o C) J t C) Top- Oil Temp (o C ) Peak Load (P e r Unit) Tsmp ( C) TopOil Temp tC) Peak Load (Per Unit) HotSpot HotSpo t Temp o TopOil Te mp Peak Load (Per Unit) 2.00 151 76 1.94 2.00 156 161 1.83 2.00 151 166 85 90 1.69 2.00 149 176 ( C) i:"1 40 Peak Load Per nit) Loss of Life r 4 20 10 0 (0 C ) Temp tC) 50 Top- Peak Loa d (Per Unit) HotSpot Temp 85 86 1.78 2.00 155 171 92 96 91 100 1.55 1.87 1.97 148 174 183 98 106 109 TopOil Temp o ( C) (o C ) r Oil Tem tc ::c 00 e::: "tl >-l 0 ...... 0 0 i:i:: <: > ::s >-< >-l ::r: "" "" 0 (") 0 ::c 147 159 78 84 1.79 2.00 147 169 83 94 1.69 1.92 2.00 146 171 179 138 162 170 88 100 104 93 106 III 1.57 1.82 1.90 1.98 1.34 1.56 145 170 178 187 137 162 93 105 109 112 97 111 1.45 1.72 1.80 144 169 177 98 110 114 1.31 1.60 141 168 102 114 a> "" 0 (") > <: i:"1 1.23 1.47 135 161 100 115 1.11 1.36 133 159 103 118 ::c > c;J i:"1 ::s 52 0 126 149 98 112 0.97 1.19 125 148 101 116 52 c;J ::c u:; i:"1 112 132 139 146 90 103 107 111 0.81 1.02 1.08 111 132 130 93 106 110 (") "" > :-'Z <0 00 NOTE: Underlined values, though beyond recommended limits (see 4.2.2.4), are given to assist in interpolation of the maximum limit. % lo s of life is in addition to normal loss of life. *AcLUal we.ter temperature should be 5 °c lower than the ambient temperatures shown above (see 3.5), and must be above zero °c. Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. ",,>-< , � ........... <oi:"1 oot:<:l ...... i:"1 C'J;I> o<Z :"00 "' ..... to:;:; ' trl Table 3(b) Capability Table for Normal and Moderate Sacrifice of Life 65 ° C Rise, Self-Cooled (OA) and Water-Cooled* (OW) Transformers Equivalent Load Before Peak Load 70 % of Nameplate Rating �trl = Hours of Peak Load ! 2 % Loss of Life Peak Load Per Jnit) HotSpot T8 mp ( C) Top- Oil Temp (o C ) Peak Load (Per Unit) HotSpot Temp o ( C) Normal 2 . 00 129 53 2.00 139 63 Normal 2 . 00 143 67 1 .98 151 77 0.25 0.50 1.00 2 .00 4.00 Normal 4 0 . 25 0.50 1.00 2.00 4.00 N o r ma l 8 0.25 0.50 1 .00 2 .00 4.00 Normal 24 Peak Load (Per Unit) 0.25 0 .5 0 1 .0 0 2 .00 4.00 1 .84 2.00 166 1 64 80 88 HotSpot T8mp ( C) 1 .8 6 2 . 00 150 163 83 87 Pe ak Load (Per Un i ) t Hot- Spot Temp o ( C) 40 Peak Load (Per Unit) Temp (Oq Temp TopOil (" C ) Peak Load (Per Top- 155 159 83 83 1 . 80 2.00 1 54 1 69 90 93 1 .72 2 . 00 148 173 89 97 1 . 56 1 . 91 2.00 146 1 74 183 95 1 04 1 07 85 97 98 1 .62 1 .87 1 .94 2 .0 0 144 1 70 1 77 1 84 90 102 1 05 1 08 1 . 50 1.77 1 .84 143 1 69 1 77 95 1 07 111 1 36 161 1 69 93 1 07 112 1 .30 1 .5 2 1 . 59 1 34 1 60 1 68 96 110 115 1 38 162 170 178 89 103 1 08 112 1 .4 1 1 .6 2 1.69 1 . 43 1 . 60 1 . 66 1 .71 129 152 159 167 175 84 98 103 1 08 113 1 . 31 1 .52 1 .5 8 1.63 1 28 151 1 58 166 88 102 106 111 1.25 1 .44 1 . 50 1 . 55 1 27 1 50 158 1 65 1.29 1 .44 1 .48 113 1 33 140 14 7 154 162 76 88 93 97 102 107 1 . 20 1 .3 6 1 .4 1 1 .4 6 1 .52 1 . 57 112 133 1 39 146 1 54 162 79 92 96 101 105 111 1.1 1 1 . 28 1 .33 1 . 38 1 . 45 1 .5 0 112 133 139 1 46 1 54 162 Hot- Spot 1 . 95 2.00 146 171 174 1 .51 1 .71 1 . 77 1 .84 50 Oil Temp (0 C ) 1 .73 1 . 97 2 .0 0 86 99 1 03 108 113 1 . 59 1 . 64 ( C) 73 139 163 170 1 79 188 1.114 TopO il Temp 0 149 1 . 60 1.80 1 .8 5 1 . 91 1 '. 9 3 1.77 30 2.00 0 . 25 0.50 1 .0 0 2 . 00 4 . 00 Norm al 2 Top- Oi l Temp (o C ) 0.25 0.50 1 .0 0 2 .0 0 4 .00 � 0 Ambient Cc 20 10 0 ootr1 I-' 1. 3 6 140 167 1.65 99 111 Hot- Top- Unit) Temp (" C ) Temp o 1 . 56 2 . 00 148 179 97 1 03 140 172 182 99 110 113 1 . 24 1.77 1 . 88 1.16 1.52 Spot 133 1 65 Oil ( C) 101 116 ..... trl trl trl Q c:: a trl "l 1 .1 7 1 .42 131 158 99 1 14 1.02 1.31 127 1 56 101 117 0 ::0 t"" 0 ;I> tJ ..... Z Q � 91 105 1 10 .l1.Q. 83 96 99 1 04 109 1 14 1.16 1 .3 5 1.41 1.02 1 . 20 1 . 25 1.30 1.37 1 26 149 1 57 112 1 32 139 1 46 1 54 94 1 08 113 86 99 103 1 07 113 1.05 1 24 1 48 1.27 97 112 0.91 1.16 119 1 46 98 115 Z trl ::0 ;I> t"" 111 0 . 91 1.1 1 1.16 1 . 23 132 1 38 146 89 1 03 1 07 111 NOTE : Underlined values, though beyond recommended limits (see 4.2.2 .4), are given to assist in interpolation of the maximum limit. % loss of life is in addition to normal loss of life. *Actual water temperature should be 5 °c lower than the ambient temperatures shown above (see 3 . 5), and must be above zero C. ° Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. 0.80 1 . 02 1.07 110 132 138 93 1 06 110 6 r � � trl ::0 00 trl tJ � 0 :;:; t::rJ ::0 Table 3(c) Capability Table for Normal and Moderate Sacrifice of Life 65 ° c Rise, Self-Cooled ( OA) and Water-Cooled* (OW) Transformers Equivalent Load Before Peak Load 90 % of Nameplate Rating >-3 ::0 > Z rn "Zj 0 ::0 = is: Ambient ° c a Hours of Peak Loa d % Loss of Life Normal 1 2 0.25 0.50 1 .00 2 . 00 4.00 Normal 0.25 0 . 50 1 . 00 2 . 00 4.00 t>:l Normal I-" 0.25 2 0 . 50 Pea k HotSpot Lo a d �Per T(�mp C) nit) 2.00 2 .0 0 1 .77 2.00 1 39 151 145 170 TopOil Temp eC) 63 75 83 94 1 . 00 2.00 Peak HotSpot Load (Pcr Temp Unit) 2.00 1 . 87 2.00 1 . 65 1 . 90 1 . 97 2.00 eC) 149 149 161 143 169 177 180 TopOil Temp eC) 73 81 85 87 99 103 104 Peak HotSpot Load (Per T(�mr Unit) 1.94 2 .0 0 1.72 2.00 1.52 1 .7 9 1 .8 7 1 .95 C 154 1 59 Toy- Oi Temp (0 C ) 82 83 147 171 87 95 91 1 04 1 08 112 1 40 1 67 175 185 40 30 20 10 Pe k Lo d a a (Per Unit) 1.73 2 .0 0 1.53 1 .91 2 .00 1 .34 1 . 67 1 .76 Hot- Spot Temp tCl 1 49 1 69 142 173 181 1 34 165 174 Toy- Oi T�mp ( C) 89 93 92 102 105 94 108 112 Peak Load (Per Unit) 1.00 1 . 98 Hot- Spot Te m p (0 C ) 115 2 .0 0 1 77 1 79 1 .0 0 1 .76 1 .8 8 180 0 .94 1 .54 115 170 112 162 l"l ::0 rn 50 TopOil Temp (o C) 90 103 103 90 1 08 111 90 112 Peak Load (Per Unit) HotSpot Temp (o C ) TopOil Temp ( oC ) 1.78 1 .94 17 2 184 110 112 - 1 . 56 164 113 0 .25 4 0.50 1 . 00 2 . 00 4 . 00 Normal 8 0.25 0 . 50 1 . 00 2 . 00 4 . 00 Normal 0 .2 5 0 . 50 24 1 . 00 2 . 00 4 . 00 1 .5 6 1 .7 6 1.82 1 .8 8 1 .95 1 78 187 1 .4 1 1 . 59 1 .64 1.70 1.76 127 1 50 158 166 175 1 . 27 1 .4 3 1 .4 8 1 . 53 1 .59 1 .64 137 161 1 69 112 132 139 146 1 54 162 89 1 04 86 100 104 109 114 1 . 46 1 . 67 1. 73 1 . 80 135 160 168 176 84 1 .32 1 . 51 1 . 56 1 .62 126 150 157 165 III 1 .1 9 1 . 36 1.41 1 . 46 1 .52 1.57 112 132 92 98 103 107 113 7 .5 88 92 97 10 2 107 1 39 146 154 162 108 112 87 101 106 79 96 101 105 110 1 .34 1 .5 8 1.64 132 1 59 167 92 1 07 111 is: <: > :a ...... >-3 ::r: '" '" ° 0 ::0 0> '" 1.36 156 115 ° (".) > <: l"l 1 . 20 1 .47 1.. 5 5 128 1 56 165 94 110 115 0. 9 4 1.36 1 13 1 54 90 ill 1 . 20 1 -1 8 114 ::0 > CJ l"l ::s Z tJ 1.22 1 .4 2 1 .48 1 .5 4 1.10 1 .27 1.33 1 .38 1 .4 4 1 .5 0 1 24 148 1 56 164 89 1 04 1 09 1 14 111 132 82 95 99 139 146 153 162 1 04 1 08 114 1 .1 0 1.33 1 .3 9 1 20 147 1 54 91 107 112 0 .9 1 1.23 1 .0 1 1 .1 9 1 . 24 1 .3 0 1 .3 6 111 131 138 146 153 86 98 103 107 112 0. 9 1 1.10 1.16 1.22 110 144 89 110 Z 1.10 140 111 CJ ::0 ...... 00 l"l 1 10 131 138 145 89 1 02 1 06 111 v NOTE : Underlined values, though beyond recommended limits (see 4 . 2 . 2 . 4 ), are gi en to assist in interpolation of the maximum limit. % l o of life is in addition to normal loss of life. *Actual water temperature should be 5 °c lower than the ambient temperatures shown above (see 3.5), and must be above zero D C . ss ..... 0 0 (".) 4.00 Normal e:: 't) >-3 0 Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. 0.79 1 .01 1.06 1.13 1 09 13 1 137 145 92 1 06 109 114 (".) "' > :-' Z "' 00 � ...... , � ..... ...... ", l"l oo l"l ..... l"l (') :> O1 Z :-' 00 00 .... � ;::; Table 3(d) Capability Table for Normal and Moderate Sacrifice of Life 65 ° C Rise, Self-Cooled (OA) and Water-Cooled* (OW) Transformers Equivalent Load Before Peak Load 1 00% of Nameplate Rating � � oo trJ = 0 Hours of Peak Load ! 2 % Loss of Life Peak Load Per nit) Normal 2 .00 0 .25 0 . 50 l .00 2.00 4 .0 0 Normal 2 0.25 0 .50 1.00 2.00 4.00 Normal 4 0.25 0 . 50 1 . 00 2 .00 4.00 Normal 8 0 . 25 0 . 50 1 .00 2.00 4 .00 Normal 24 20 HotSpot T �mp TopOil Temp Peak Load Per nit) HotSpot Temp TopOil T �mp 144 68 2.00 1 54 78 ( e) te) J te) ( C) 0.25 0.50 1 . 00 2.00 4 .00 Normal � � J Ambient ° e 10 0 . 25 0.50 1 .0 0 2.00 4 .00 1 .93 2 . 00 149 156 78 80 l .78 2 .00 14 6 1 66 83 90 � HotSpot T�mp T O' Te lIP J 80 :" . 0 0 1 49 1 64 a5 1 . 59 1 .97 2.00 1 41 173 176 88 99 1 00 Peak Load (Per Unit) ( e) tC) 88 30 50 40 r HotSpot T�mp TopOil T�mp Peak Load Per nit) HotSpot T 8mp To Oi Temp l .8 4 2 . 00 172 184 1 06 1 08 l .00 1 .7 2 130 173 1 05 1 14 164 175 1 09 1 13 1 . 00 1.50 138 164 105 1 16 Peak Load ( Per Unit) HotSpot T�mp l . 00 2.00 1 10 1 74 85 98 1 . 00 1 .8 1 1 .93 2 . 00 110 1 69 179 186 85 104 108 110 1 .63 1.77 1 .4 4 ( C) 1 .71 1 . 95 2 .00 142 1 68 173 83 95 98 l .59 l .8 5 1 .93 2.00 140 167 176 1 83 88 100 104 108 1 .4 2 1 .7 3 1 .8 2 1 .9 1 1 35 1 65 1 74 1 83 91 1 04 1 09 113 1 .00 1 .6 1 1 . 70 1 10 162 172 85 109 113 1 .5 3 1 .7 3 1 .80 l .8 6 1 .9 3 135 160 168 176 186 86 100 104 109 1 14 1.42 1 .64 1 .7 1 1 .7 8 133 1 58 167 176 89 103 lOS 113 1 .28 1 .5 5 1 .6 2 1 27 157 165 90 1 07 111 1 .00 1 .4 3 1 .5 2 1 10 153 163 85 1 09 115 1 .40 1 . 58 1 . 63 1 .69 1 . 75 126 1 50 1 57 165 173 83 98 1 02 107 112 1 . 30 1 . 49 1 .55 1 .6 1 1 .6 7 1 24 148 1 55 164 173 86 1 01 105 1 10 116 1.19 1 .4 1 1 .46 1 . 53 1 20 147 1 54 1 63 104 108 1H l .00 1 .3 0 1 .3 8 110 144 1 53 1 .27 1 .43 1 .48 1 .53 1 . 59 1 .64 112 132 139 146 1 54 162 75 88 92 97 1 02 107 1.19 1 .35 1 .4 1 1 .4 6 1 .52 1 . 57 111 132 1 39 146 154 1 62 78 91 96 100 105 110 1 . 09 1 . 27 1 . 32 1 .38 1 .44 1 . 50 1 10 1 32 1 38 146 1 53 161 81 95 99 1 04 1 08 114 � Peak Load Per nit) To Oi T�mp ( e) >-' � ( C) 156 ( e) 111 � l .0 0 l . 34 ( e) 130 1 58 (0C) 1 05 1 17 .... trJ trJ trJ 0 c: .... tl trJ "'J 0 ::0 t" 1 .28 1 . 39 147 1 59 110 117 1 . 00 1 .22 1 30 151 1 05 117 0 :> tl .... Z 0 � 8 :7 1 . 00 1 .19 1 . 24 1 . 30 1 .36 110 13 1 1 38 145 1 53 85 1 06 III 85 98 103 107 112 Z 1 .1 9 1 . 27 140 149 107 113 1 . 00 1.13 1 30 143 105 113 trJ ::0 :> t" 6 .... 0 .89 1 . 09 1 . 16 1 . 22 1 09 130 1 38 145 88 101 1 06 111 NOTE: Underlined values, though beyond recommended limits (see 4 . 2 . 2 . 4 ), are given to assist in interpolation of the maximum Iimit_ % loss of life is in addition to normal loss of life. *Actual water temperature should be 5 °c lower than the ambient temperatures shown above (see 3 . 5 ), and must be above zero ° e_ Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. 0.77 1 . 00 1 .06 1.13 1 08 130 1 37 144 91 1 05 1 09 1 14 t" .... � � trJ ::0 00 trJ tl "0 0 ::;; trJ ::0 >"I � > Z 00 "%J 0 � Table 3(e) Capability Table for Normal and Moderate Sacrifice of Life 65 ° C Rise, Forced-Air-Cooled (OA/FA) Transformers Rated 133% or Less of Self-Cooled Rating Equivalent Load Before Peak Load 50% of Maximum Nameplate Rating = s:: t<l Ambient ° c 0 Hours of P ak Load e 1 2 % Loss of Li f e Normal t-:) C<:> 0 . 25 0.50 1 .00 2 . 00 4 . 00 Normal 2 0.25 0.50 1 . 00 2.00 4 . 00 N ormal 4 0.25 0.50 1 .00 2.00 4 . 00 Normal 8 0.25 0 . 50 1 .00 2.00 4.00 Normal 24 H t- o Spot �Per T�m p nit) Load ( C) 2.00 140 ( C) Pea k Load (Per HotSpot Temp 0 50 2 .00 150 Topl Oi Temp o Unit) ( C ) TopOil T�mp ( C) 60 0.25 0.50 1 .00 2.00 4 .00 Normal 1 Peak 20 10 0.25 0.50 1 . 00 2 .00 4 . 00 y 30 Peak Load (Per Unit) HotSpot T�mp ( 1 .9 7 2.00 1 58 1 60 69 70 1 .8 7 2.13 1 57 184 1.74 1 .9 5 2.02 153 1 78 1 86 80 90 94 1 .6 4 1 .8 7 1 .9 4 152 178 186 C) To Oi T� mp ( e) Peak Load Per nit) � HotSpot y 40 50 HotTopOil Spot (Per Temp Temp (0 Peak Load HotSpot TopOil Peak Load Unit) C) C) Unit) (C) C) 76 84 1 .76 2.02 157 183 83 90 1 .63 1 .9 2 156 182 90 97 85 96 99 1 .54 1.77 1 .8 4 1 50 176 185 91 101 105 1 .4 2 1 .6 7 1.75 149 175 184 96 107 110 To Oi Temp T�mp ( e) e) t (Per Temp Temp (o (0 � 00 e:: "t:I >"I 0 .... 0 0 s:: <: > ::;; =3 1 .93 2.1 2 154 179 69 79 1 .8 3 2.04 153 178 74 84 !:I: 01 01 0 C':l 0 � 1 . 68 1 . 85 1 . 90 148 172 180 79 92 96 1 . 59 1 .77 1 .83 1 . 89 146 171 179 188 83 96 100 105 1.51 1 .70 1 .76 1 .82 146 170 179 188 88 1 00 1 05 1 09 1 .4 2 1 .62 1 . 68 1.75 145 170 178 187 92 105 109 114 1.33 1.53 1 .6 0 144 169 177 96 109 1 13 1 .22 1 .4 5 1 .4 8 1 . 63 1 . 68 1.73 1 .78 1 38 162 170 178 187 82 96 101 106 111 1 .4 1 1.57 1.61 1 .66 1 . 72 138 162 1 69 177 1 86 86 1 00 104 109 115 1 .33 1 .4 9 1.55 1 . 60 1 37 1 60 1 68 177 89 103 1 08 1 13 1 .25 1 .42 1.47 136 159 167 93 1 07 112 1.16 1 .3 4 135 1 59 97 1 .0 7 1 . 26 1 .35 1.49 1 . 54 1 . 59 1 . 63 1 . 68 127 149 156 164 172 181 78 92 96 101 106 112 1 . 28 1.43 1 .4 8 1 .52 1 . 58 126 148 1 56 163 172 82 95 100 104 110 1 .2 1 1 . 36 1 .41 1 .4 6 1 .5 1 1 26 1 48 155 1 63 171 85 99 103 108 113 1.13 1 . 29 1 .3 4 1 . 39 1 25 148 155 1 63 89 103 107 112 1 .05 1.21 1 .27 1 25 147 1 54 92 106 111 0.95 1.14 1.19 1 24 146 1 54 96 1 09 1 14 1 . 24 1 . 38 1 .4 2 1 .4 6 1 .51 1 .55 112 131 138 145 153 160 69 81 85 90 95 99 1.17 1 .3 1 1.35 1 .4 0 1 .4 5 1 .4 9 111 131 1 38 145 153 160 73 85 89 94 98 103 1 .09 1.24 1 .2 9 1 .3 3 1 .3 8 1 .43 111 131 1 38 145 152 160 76 89 93 97 102 1 07 1.01 1.17 1 . 22 1 .2 7 1 .3 2 1 .3 7 111 131 1 38 145 152 160 80 93 97 101 106 111 0.92 1 .0 9 1.14 1.19 1 .25 111 131 1 38 145 1 52 84 96 100 105 110 0.83 1 .0 1 1 .0 6 1.12 1.17 110 131 1 37 144 152 88 1 00 1 04 1 09 113 III 142 1 68 1 00 114 '" 01 0 C':l �t<l 133 1 58 100 114 � > 0 l"l ::;; Z NOTE: Underlined values, though beyond recommended limits (see 4.2.2. 4 ), are given to assist in interpolation of the maximum limit. % loss of life is in addition to normal loss of life. a H Z 0 � H 00 l"l C':l 01 > :-' Z 10 00 H Nl , .... .... 1O l"l oo l"l .... l'l Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. 0> O1 Z :-'1 00 co ...... 1:>:1 ;::; ' ttl Table 3(f) Capability Table for Normal and Moderate Sacrifice of Life 65 ° C Rise, Forced-Air-Cooled (OA/FA) Transformers Rated 133% or Less of Self-Cooled Rating Equivalent Load Before Peak Load 70% of Maximum Nameplate Rating � ttl 00 ttl .... = Hours of Peak Load 1 2 % Loss of Life 24 HotSpot Temp 0 ( C ) TopOil Temp (o C) Peak Load (Per Un it ) HotSpot T(li mp y To Oi Tli mp ( C) Peak Load (Per U n it ) HotSpot Temp (0 To Oi Tgmp r Peak Load (Per ( C) Unit) 57 2.00 158 67 1 .89 2.15 1 58 183 74 82 1 . 78 2 . 04 1 56 182 81 88 1.65 1.94 Normal 1 .87 2 . 07 153 178 72 82 1 .7 7 1 .9 9 2 .06 152 178 186 77 88 91 1 .6 7 1 .90 1 .9 7 151 177 185 - 82 93 97 1.57 1.81 1 .8 8 150 176 1 84 - 88 99 102 ( C ) 0 .25 0 .50 1 .00 2.00 4 .00 0.25 0 . 50 1 .00 2 .00 4 . 00 0.25 0 . 50 1 . 00 2 . 00 4 . 00 Normal 8 ( C ) Peak Load (Per U n it ) 148 Normal 4 Top· Oil Temp a 40 2.00 Normal 2 r .crni t ) HotSpot T!i mp 30 Normal 0 . 25 0 .50 1 .00 2 . 00 4 .00 t>:l ..,. Peak Load Ambient °c 20 10 0 C) 1 45 1. 71 1 .7 9 Spot Temp (o C) 50 TopOil Temp (o C) 1 55 182 88 96 148 1 75 184 93 1 04 1 08 Peak Load (Per Unit) Hot- Spot t C) Temp Top Oil Temp (C ) 1 .49 1.83 151 181 94 102 1 . 30 143 173 181 98 1 09 1 13 1 . 60 1 . 68 ...... ttl ttl ttl Q c:: 1 .64 1 .8 2 1 .88 l .9 3 1 47 171 179 188 80 93 97 1 02 1 . 56 1 .74 1 .80 1 . 86 1 .4 6 1 .6 2 1 .67 1 .7 2 1 . 77 137 161 169 177 186 82 96 101 106 111 1 . 39 1 .35 1 26 1 48 155 163 171 180 0 . 25 0 . 50 l .00 2 .00 4 .00 1 . 49 1 . 53 1 . 58 1 . 63 1 . 68 N ormal 1 . 24 l . 37 1 .4 1 1 .4 6 1 . 50 1 . 55 0.25 0 . 50 1 . 00 2.00 4 .00 C) HoL- III 131 1 37 145 152 1 60 1 45 170 179 187 84 97 1 02 106 1 .4 7 1 . 66 1 .7 2 1 .79 144 1 69 177 186 89 1 01 1 06 110 1 .37 1 .58 1 .64 1 . 60 1 . 65 85 1 00 104 110 1.31 1 .48 1.53 1 .59 1 35 1 59 1 67 1 76 89 103 1 08 1 13 1 .22 1 .4 0 1 .4 6 78 91 96 101 106 111 1 . 28 1 .43 1 . 47 1 . 52 1.57 1 .62 125 1 48 155 163 171 180 81 95 99 104 109 1 .2 0 1.35 1 .4 0 1 .45 1 . 50 1 25 147 1 54 1 62 1 70 85 98 103 1 08 113 1 .12 1 . 28 1.33 1 .38 69 81 85 90 94 99 1.17 1 . 30 1 . 35 1 .4 0 1.45 1 .50 73 85 89 94 98 103 1 . 09 111 1 31 1 37 1 45 1 52 1 60 76 89 93 97 102 1 07 1 . 01 1.17 III 131 1 38 145 152 1 61 lli 1 . 24 1 . 28 1 . 33 1.38 1.43 92 1 06 110 1.27 1.49 1 40 1 67 96 110 1 . 14 140 1 36 165 99 1 14 a ttl "<J 0 !:d t"" 136 160 168 177 1.55 142 1 68 176 1 34 1 58 166 92 1 07 III 1.13 1 .32 132 157 96 110 1 .0 1 1 .23 1 29 155 98 1 13 0 > 0 Z Q s::: Z 1 .21 1 . 26 1 .3 1 1 . 37 1 24 147 153 162 110 1 31 137 144 152 160 88 1 02 106 ill 80 93 97 101 100 111 1.03 1.21 1 . 26 1 23 146 153 91 105 110 0.92 1.12 1.18 1 20 145 152 94 109 113 t'l !:d > t;"' 0 ...... t'" ,!.., 0.92 1 .0 9 1.14 1.19 1 . 24 1 . 30 111 1 30 1 37 1 44 152 160 84 96 100 1 04 1 09 114 NOTE: Underlined values, though beyond recommended limits (see 4.2.2.4), are given to assist in interpolation of the maximum limit. % loss of life is in addition to normal loss of life. Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. 0.83 1 .00 1 .06 1.12 1 .17 110 1 30 136 144 152 88 1 00 1 04 108 1 13 s::: s::: t'l !:d tn t'l 0 "tI 0 :;J ttl !:d 0-3 ::>:I > 2 00 "'J 0 ::>:I Table 3(g) Capability Table for Normal and Moderate Sacrifice of Life 65 ° c Rise, Forced-Air-Cooled (OAjFA) Transformers Rated 133% or Less of Self-Cooled Rating E quivalent Load Before Peak Load 90% of Maximum Nameplate Rating = s:: Ambient ° c Hours of Peak Load % Loss of Life Normal ! 2 0.25 0.50 1 . 00 2.00 4.00 Normal 1 � 0.25 0.50 1.00 2.00 4.00 Normal 01 2 0 . 25 0.50 1.00 2.00 4.00 Normal 4 0.25 0.50 1 . 00 2.00 4.00 Normal 8 0.25 0.50 1.00 2.00 4.00 Normal 24 0.25 0.50 0.00 2 . 00 4.00 Peak Load Per nit) J 2.00 l . 79 2.01 1 . 59 1 . 78 1.83 1.90 Hot· Spot T�mp ( C) 1 57 1 51 177 144 1 69 177 1 87 Top· Oil Temp ( C) 67 75 86 81 94 98 103 Peak Load (Per Unit) Spot Temp (0 80 88 1.61 1 . 94 150 181 86 95 l . 23 l .81 1 .9 1 1 30 178 188 - 148 174 183 - 86 96 100 1.43 l. 72 l . 80 143 173 182 - 90 102 1 06 l . 10 1 . 60 1 . 69 1 23 171 180 140 167 175 184 89 103 107 1 . 28 1.53 1 . 59 1 36 166 174 91 107 111 1.03 1 .42 1 20 163 Peak Load (Per Unit) Hot· Spot T�mp 1 .88 2.15 -- 1 56 183 73 81 l .76 2.04 -- 1 54 � 1 .69 1.91 1.98 1 50 176 1 84 81 91 95 l . 57 l.81 l . 89 1.50 1.70 1.76 1.82 142 1 69 177 186 85 99 103 1 08 1 . 40 1 . 62 1.67 1.74 t C) ( C) 40 To Oir T�mp TopOil T�mp J 30 Hot· Spot T� mp Hot· Spot Tem p Peak Load Per nit) trJ 20 10 0 ( C) To Oi Temp (o Peak Load per ni t ) r e) .!l1 J ( e ) ( e) Hot· C) 50 Top· Oil Temp C C) Peak Load (Per Unit) Hot· Top- Temp (0 Temp o Sp o t C) Oil ( e) 88 101 104 l . 64 1 . 77 173 185 107 1 10 -- 88 1 07 l . 45 165 111 1 11 - 88 110 ::>:I 00 e::: '" 0-3 0 f-' 0 0 s:: <: > ::;:: ...... 0-3 :I: 01 01 ° 0 0 ::>:I 0'> 1.30 1 58 112 01 0 0 > <: trJ ::>:I > (,') 1 .44 1 . 60 1 . 64 1.70 1.75 1 36 159 1 67 176 184 82 96 100 105 111 1.36 1.53 1.58 1.63 1.69 1 34 1 58 1 66 175 1 84 85 99 1 04 1 09 115 1 . 27 1 . 45 1 . 50 l . 56 1 32 1 57 165 174 88 103 107 113 1.16 1 . 37 l.43 1.33 1.48 1.52 1 . 57 1.62 1.67 1 24 147 1 54 162 170 179 77 91 95 100 1 05 111 1.26 1.42 1.46 1.51 1.56 1.61 1 24 147 154 162 170 179 80 95 99 104 109 114 1 . 18 1 . 34 1 . 39 1 . 44 1 . 49 122 146 153 161 169 83 98 102 107 112 1 . 08 1 . 27 1.32 1.37 119 145 152 1 60 85 101 1 06 111 0.93 1 . 18 1 . 24 1 . 30 111 143 151 159 85 1 04 1 09 114 1 .09 1.16 140 149 106 112 t:l ...... 2 (,') ::>:I ...... 1 . 24 1.37 1.41 1 . 46 1.51 1.55 111 131 137 144 152 1 60 69 81 85 89 94 99 1.16 1.31 1.35 1 .40 1 . 44 1 . 49 110 1 31 1 37 145 1 52 1 60 72 85 89 93 98 103 1 . 08 1 . 24 1 . 28 1.33 1 . 38 1.43 110 131 137 145 152 159 76 88 92 97 102 106 1 . 00 1.16 1.21 1.26 1.31 1 . 36 110 130 1 37 144 151 1 59 80 92 96 101 1 05 110 0.92 1.08 1.13 1 .18 1 . 24 1 .29 1 10 1 30 1 36 143 152 1 59 84 96 100 104 109 114 1 . 00 1.05 1.11 1.17 1 30 1 36 143 151 100 1 04 108 113 0 128 1 56 1 63 90 1 06 110 0.97 1 .28 1.34 115 1 53 162 86 108 113 NOTE: Underlined values, though beyond recommended limits (see 4 . 2 . 2 . 4 ), are given to assist in interpolation of the maximum limit. % loss of life is in addition to normal loss of life. Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. 1.17 148 110 trJ ::;:: Z 00 trJ "' > :-> 2 <0 00 I>J ...... � "j::;j <o trJ oo trJ .... trJ 0> cn z :-' 00 "' ..... "" -;::; Table 3(h) Capability Table for Normal and M oderate Sacrifice of Life 65 DC Rise, Forced-Air-Cooled (OA/F A) Transformers Rated 1 33% or Less of Self-Cooled Rating Equivalent Load Before Peak Load 100% of Maximum Nameplate Rating ,:.. � � t;:j ..... = 0 Hours of Peak Load % Loss of Life N or mal ! 2 0.25 0.50 1.00 2.00 4.00 Normal 0.25 0.50 1 . 00 2.00 4 . 00 t-:) al Normal 2 0.25 0.50 1.00 2.00 4.00 N o rm al 4 0.25 0.50 1 . 00 2.00 4.00 Normal 8 0.25 0.50 1 . 00 2.00 4 . 00 Normal 24 0.25 0.50 1 . 00 2.00 4 . 00 Ambient ° c 20 10 r r Peak Load (Per Unit) Peak Load Per nit) HotSpot Tg mp To Oi Tg mp 77 85 1 . 64 1 .98 149 181 83 92 1 . 06 1 .8 4 1.95 114 178 188 147 175 183 82 93 96 1 . 47 1 . 76 1 . 84 141 173 182 86 98 102 1 . 03 1 . 65 1.73 1 .82 112 170 179 189 80 103 107 111 1.46 1 .66 1.73 1 . 79 140 166 176 184 85 99 103 1 08 1.33 1.57 1 . 65 1 .71 1 34 164 174 183 87 102 107 112 1 . 03 1 . 48 1 .5 5 112 162 171 81 95 1 00 105 111 1 . 34 1.51 1 . 56 1 . 62 1 . 68 132 1 57 165 174 183 84 99 1 04 1 09 114 1 . 23 1 .4 3 1 . 49 1.55 127 155 163 172 85 1 02 107 112 -- 1 . 02 1.34 1.41 111 1 53 161 76 91 95 100 105 122 145 153 161 170 178 79 94 99 1 03 1 09 1.16 1 .31 1 . 38 1 . 44 1 . 49 119 145 152 161 169 ill 1.25 1.41 1 .46 1.50 1 . 56 1.61 1 .01 1 . 25 1.31 1.36 1.42 110 142 151 159 168 l!1.. 82 97 1 02 107 112 - 80 99 105 1 09 115 -- 68 81 85 89 94 99 1 .16 1.30 1.35 1.40 1 . 44 1 .49 110 131 137 144 152 1 60 72 85 89 9 :, 98 1 03 1.08 1 .23 1.28 1.33 1 . 38 1 . 43 110 1 30 137 144 1 52 159 76 88 93 97 1 02 106 1.00 1.16 1.20 1 .26 1 .:1 1 1.36 1 10 1 30 1 36 144 151 1 59 80 92 96 1 00 105 110 HotSpot Ts mp ( C) HotSpot Temp TO Oi Temp 1 .9 3 2.19 156 183 70 78 1 . 80 2.08 1 54 1 82 1.73 1 . 96 2.03 149 176 184 77 88 91 1.63 1 . 87 1.93 1.55 1.75 1 .8 1 1 . 87 142 168 177 186 81 95 99 1 04 1 . 42 1 . 58 1 . 63 1 . 6R 1 . 74 1 34 158 1 66 1 74 184 1 . 33 1 . 48 1.52 1 . 57 1.62 1.67 124 147 154 162 170 179 1.23 1 . 37 1.41 1 . 46 1.51 1 .55 110 131 1 37 144 152 160 ( C) r 40 To Oi Temp Peak Load Per nit) J 30 HotSpo t Tsmp TopOil Ts mp Peak Load Per nit) J (DC) t C) ( C) (oC) J ( C) 50 Peak Load (Per Uni t) HotSpot Tsmp TopOil Temp 103 107 1 . 02 1 . 59 131 175 100 111 164 175 107 111 1 . 02 1.41 131 165 1 00 113 1 . 34 1.44 1 56 1 67 108 114 1 . 01 1 . 28 130 159 100 114 1 . 23 1.31 148 158 1 06 112 1 .00 1.17 130 150 100 111 ( C) Peak Load (Per Uni t) HotSpot Tg mp TopOil Temp 81 98 101 1 . 67 1 .81 172 1 84 1 . 50 1 .61 81 1 06 111 81 104 110 ( C) (DC) ( C) (oC) ..... t;:j t;:j t;:j C') c::: ..... t; t;:j '"<J 0 :;d t"' 0 > t; Z C') s:: Z t;:j :;d 1.16 1 .2 2 1 . 29 L OR 1.13 1 . 18 1 . 24 1 . 29 1 39 148 1 58 1 28 1 36 143 151 159 102 107 113 'l5 1 00 1 04 1 09 1 14 NOTE: Underlined values, though beyond recommended limits (see 4 . 2 . 2 . 4 ), are given to assist in interpolation of the maximum limit. % loss of life is in addition to normal loss of life. Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. 0.99 1.11 1 . 20 1 . 00 1.05 1.11 1 . 16 1 30 1 43 155 1 30 135 143 151 100 108 115 100 103 108 112 > �..... t"' ,.:... s:: s:: t;:j :;d 00 t;:j t; ." 0 � t;:j :;d "":l ::0 Table 3(i) Capability Table for Normal and Moderate Sacrifice of Life 65 ° C Rise, Forced-Oil-Cooled ( Directed Flow - FOA, FOA*, and OA/FOA/FOA) Transformers Equivalent Load Before Peak Load 50% of Maximum Nameplate Rating > z 00 "%j 0 ::0 = 0 Hours of Peak Load % Loss of Life Normal ! 2 0 . 25 0.50 1 . 00 2.00 4 . 00 Normal 0.25 0.50 1 .0 0 2.00 4 . 00 t.:> -l 2 4 8 24 r Peak Hot- To - T� mp ( C) Temp (0 Load Per nit) Temp (o C) Spot Oi Temp tC) Peak Load (Per Unit) T(�mp C) 1.76 1.91 160 186 - 52 59 1.70 1.84 160 185 59 66 1 .6 3 1 . 79 159 185 /l Oi C) J Hot- trl 20 Peak Load er nit) Spot s:: Ambient °c 10 r To - HotSpot 40 30 r To - Oi T!l mp ( C) 66 74 r Hot- To - Jnit) T( 0emp C) Tgmp Oi ( C) (Per Unit) 1.56 1.73 159 185 74 81 1.48 1 .66 Peak Load per Spot Hot- Peak Load Spot Te mp tC) 1 58 1M 50 T op Oil t c) Peak Load (Per Unit) 81 88 1.41 1 . 59 Temp Hot- Spot Temp t el 157 � TopOil ( C) "":l 0 88 95 s:: Temp o '1:1 >-' 0 0 <: > � 1.59 1.73 1.77 1 54 179 187 65 74 78 1 .5 4 1 .67 1.72 1 53 1 78 1 87 71 80 84 1 .4 7 1.62 1.66 152 178 186 ::3 77 87 90 1 .4 1 1.55 1 . 60 152 177 185 83 92 95 1 . 34 1.49 1.54 151 1 76 1 85 89 98 102 1 .26 1.43 1.48 150 176 184 94 1 04 107 Normal 0.25 0.50 1 .00 2 . 00 4 . 00 1 .45 1.57 1.61 1 .64 146 170 178 187 73 84 88 92 1 .3 9 1.52 1.55 1 .6 0 146 170 178 187 78 89 93 97 1 . 3 .1 1 .4 6 1 . 50 1 .55 145 1 69 177 1 86 83 94 98 102 1 .27 1.41 1 .4 5 1 .49 144 1 69 176 185 88 1 00 103 107 1 . 20 1 . 34 1 .39 1 . 44 143 1 67 176 185 93 1 04 108 112 1 .13 1 . 28 1 . 33 Normal 1.34 1.45 1.48 1 .52 1.56 136 158 166 174 183 73 85 89 93 98 1 . 28 1 .4 0 1.43 1.47 1.52 135 1 58 1 65 173 183 78 90 93 98 1 02 1 .22 1 .34 1 .38 1 . 42 82 94 98 102 1 07 1.16 1 . 29 1.33 1.37 1.41 1 34 157 164 173 181 87 99 102 107 III 1 . 09 1 . 23 1 . 27 1 .32 1 33 1 57 1 64 173 91 1 03 107 ill 1 . 02 1 . 17 1 . 21 l .46 135 157 165 173 182 Normal 0.25 0.50 1 . 00 2.00 4 .00 1 . 27 1.38 1.41 1.45 1 . 48 1.52 1 24 146 153 160 169 178 68 80 83 87 92 95 1 . 21 1.32 1.36 1.40 1.44 1.48 1 24 146 153 161 1 69 177 73 84 88 92 96 101 1.15 1.27 1. 31 1 . 35 1 . 39 1 .43 1 24 145 153 160 1 68 177 77 89 93 97 101 106 1 . 09 1 .21 1 . 25 1 . 29 1 . 34 1 . 38 123 145 152 160 168 177 82 93 97 101 1 06 110 1 . 02 1 .1 6 1 .20 1 . 24 1 . 28 1 23 1 45 152 1 59 167 87 98 1 02 1 06 110 0.95 1 . 09 1.14 1.18 1 . 23 1 23 144 152 159 167 91 103 106 110 115 Norm al 0.25 0.50 1 . 00 2.00 4 . 00 1.19 1 . 30 1.33 1.37 1 .4 1 1 . 44 111 131 137 144 152 160 61 72 75 79 83 87 1.13 1.25 1 . 28 1.32 1.36 1 .39 111 131 137 144 152 160 66 77 80 84 88 92 1 . 07 1.19 1 . 23 1 . 27 1.30 1 . 34 71 81 85 86 92 96 1 .01 1.13 1.17 1 .2 1 1 .2 5 1.29 111 131 1 38 145 152 1 60 76 86 90 93 97 101 0.94 1 .07 1.11 1.15 1 . 20 1 . 24 111 131 1 37 144 152 159 80 91 94 98 1 02 1 06 0.86 1 .00 1.05 1 .09 1 . 14 1.18 111 131 137 145 152 160 85 95 99 1 03 106 0.25 0.50 1.00 2.00 4.00 ::0 00 � III 131 1 37 1 45 1 52 160 142 167 175 97 1 09 ll3 :x: <:11 <:11 0 () 0 ::0 a> C1T 0 () > <: trl 1 32 156 163 96 1 08 112 ::0 > 0 trl � - Z 0 - NOTE : Underlined values, though beyond recommended limits (see 4 . 2 . 2.4 ), are given to assist in interpolation of the maximum limit. % loss of life is in addition to normal loss of life. * Actual water temperature should be 5 ° c lower than the ambient temperatures shown above (see 3.5), and must be above zero C. ° Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. !!! Z 0 ::0 00 trl () <:11 > ;-'l Z .0 00 t..:l . ..... - tO trl oo trl ..... trl n> O1 Z Table 3(j) Capability Table for Normal and Moderate Sacrifice of Life 65 ° C Rise, Forced-Oil-Cooled (Directed Flow - FOA, FOW * , and OA/FOA/FOA) Transformers E quivalent Load Before Peak Load 70% of Maximum Nameplate Rating :--' 00 .., ..... N) "j::; � g] oo trl = ,... Ambient ° c 0 Hours of Peak Load % Loss of Life Normal ! 2 0.25 0.50 1 .0 0 2 .0 0 4 .0 0 Normal 1 t-.:> 0.25 0.50 1 .00 2.00 4.00 Normal 00 2 0.25 0.50 1.00 2.00 4.00 Normal 4 0.25 0.50 l.00 2.00 4.00 Normal 8 0. 2 5 0.50 1 .00 2.00 4.00 Normal 24 0.25 0.50 1 .0 0 2.00 4.00 Peak Load �Per nit) HotSpot T�mp ( C) TopOil Temp Peak Load (Per Unit) HotSpot Temp (0C) t c) Peak Load (Per Unit) 1.71 1 . 87 159 185 57 64 1.65 1.80 159 184 64 71 1 . 58 1 . 74 1 58 184 71 78 1.51 1.68 157 184 l.56 1.70 1 .74 152 1 7H 186 67 77 80 1.50 1 . 64 1 . 69 152 1 77 185 73 83 86 1.44 1.59 1 . 63 151 177 185 79 89 92 1 .37 1.52 1 . 57 150 176 184 t C) 1 .1 3 1 . 55 1 . 59 1 . 63 145 1 70 178 186 73 85 89 93 1 .33 1.45 1 .48 1 .5 2 l . 55 1 35 158 165 173 1H2 73 85 88 93 97 1 . 26 1 . 38 1.41 1 .45 1 .48 1.52 1 24 l 46 152 160 1 68 177 68 80 83 87 91 96 1.19 1 .30 1.33 1.37 1.40 1.44 111 1 30 137 141 152 160 61 72 75 79 83 87 1 .37 TopOil Temp t e) Peak Load (Per Unit) HotSpot T�mp ( C) 144 1 69 176 185 78 90 94 98 1.31 l.45 1 . 48 l.53 1 44 l . 50 1 . 54 l.58 1 .27 1 . 39 1.43 1 .47 1.51 1 34 1 57 1 65 173 181 77 89 93 97 102 1 . 21 1 . 34 1 . 38 1.42 1.46 73 1 .21 TopOil Temp 1 . 24 HotSpot Temp te) TopOil Temp t C) Peak Load (Per Unit) HotSpot T8mp TopOil Temp 78 85 l .4 3 l .6 1 1 56 1 83 R5 92 l . 34 l . 54 154 182 92 99 85 94 98 1 . 29 1 .4 6 1.51 1 49 175 183 90 1 00 103 1 .20 1 . 39 1 ,45 146 174 183 96 1 06 1 09 TopOil Temp (0C) Peak Load (Per Unit) 142 1 67 175 184 - 88 100 103 1 08 1.17 l .33 l .3 7 1.42 141 166 1 74 1 84 - 1.15 l . 28 1.32 1.37 1.11 132 1 56 1 64 1 72 181 - 86 98 102 107 111 - 1 .0a 1 32 156 163 172 83 95 98 103 1.89 1 34 1 57 164 172 1 81 - 82 94 98 102 107 1 68 176 185 HotSpot Temp te) l .4 3 1 .4 8 50 40 30 20 10 1 .23 l . 27 l.31 93 1 05 108 113 - 91 103 107 111 - ( e) (0C ) 1 . 09 l . 26 l .3 1 1 39 165 174 97 109 112 l.00 l.16 l . 20 129 154 162 94 107 111 1 . 36 1 . 39 88 92 96 100 1.15 1 . 27 1.30 1 . 34 1 . 38 1 . 4:3 1 24 145 152 160 167 176 77 89 92 96 100 105 1 . 09 1.21 1 . 25 1 . 29 1 . 34 1 . 38 1 23 1 44 152 1 59 1 68 1 76 82 93 97 101 1 06 110 1 .0 2 1 .1 5 1 .2 0 1 .2 3 1 .2 8 1 .3 2 122 144 152 1 59 167 1 76 86 98 102 1 05 110 114 0.94 1 .09 1 .13 1 .18 121 144 151 159 90 102 1 06 110 l.43 1.47 1 24 145 153 160 168 1 76 1.13 1.25 1 . 28 1.32 1.36 1.39 111 1 31 137 144 152 160 66 77 80 84 88 92 1 . 07 l.19 l.23 1 . 27 1 . 30 l . 34 111 71 81 85 88 92 96 1 . 00 111 131 137 145 152 160 75 86 89 93 97 101 0.93 1 .07 1.11 l.15 l .20 1 .2 6 110 131 137 1 44 152 1 59 80 91 94 98 102 106 0.86 1 .00 1 . 05 1 . 09 1.14 1.18 111 130 137 144 152 Hi9 85 95 99 102 1 06 110 1 . :12 84 1 :W l :n 145 152 160 1.13 l.17 1 .21 l . 25 1 . 29 NOTE: Underlined values, though beyond recommended limits (see 4 . 2 . 2 . 4 ) , are given to assist in interpolation of the maximum limit. % loss of life is in addition to normal loss of life. *Actual water temperature should be 5 °e lower than the ambient temperatures shown above (see 3.5), and must be above zero °e. Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. t:;J trl trl 0 C ..... t:) trl "l 0 � t"" 0 > t:) Z 0 � ..... Z trl � > t"" 6 ..... s: � � trl � 00 trl t:) '" 0 � trl � >-3 ::x:J > Table 3(k) Capability Table for Normal and Moderate Sacrifice of Life 65 ° C Rise, Forced-Oil-Cooled (Directed Flow - FOA, FOW*, and OA/FOA/FOA) Transformers E quivalent Load Before Peak Load 90% of Maximum Nameplate Rating Z 00 "%j 0 ::x:J = s:: t:rJ Ambient C c 0 Hours of Peak Loa d % 2 4 1 . 59 1 . 75 151 177 185 70 80 83 1.41 1.53 1.57 1.61 143 167 175 184 1.32 1 .4 3 1.47 1.51 1.55 1.52 1 . 66 1.71 Normal 0.25 0.50 1 . 00 2.00 4.00 Normal 0.25 0.50 1 . 00 2.00 4.00 0.25 0.50 1.00 2.00 4.00 0. 2 5 0.50 1.00 2 . 00 4 . 00 Normal 24 62 69 158 184 Normal 8 (C) JPer ni t ) 1 . 66 1 .81 0.25 0.50 1 . 00 2.00 4.00 2 Peak T�mp Normal t-:l to Top- HotSpot J Normal ! Peak Load Per nit) Loss of Life 0.25 0.50 1.00 2 . 00 4.00 Oil Temp Hot- To p- Oi l Temp Peak HotSpot (cc) Load (Per Unit) T�mp 1 57 1 84 70 77 1.51 1 .68 1 56 182 1 . 45 1 .6 1 1.65 149 176 1 84 76 86 89 1 . 38 1 . 54 1 . 59 74 85 89 93 1.34 1 .48 1.52 1.56 142 1 67 175 1 84 79 90 94 98 1 34 156 163 172 181 73 84 88 92 97 1 . 26 1.38 1.42 1 .46 1.50 1 32 156 1 64 172 1 80 1.26 1.37 1.41 1.44 1.48 1.52 1 23 145 152 1 60 167 176 68 79 83 87 91 95 1 . 20 1.32 1.35 1 . 39 1.43 1.47 1.19 1 . 30 1.33 1 . 37 1 .40 1 . 44 111 130 137 144 152 1 60 61 72 75 79 83 87 1.13 1 . 24 1 . 28 1.32 1 . 36 1 . 39 ( C) Load Spot Temp 30 20 10 To r Oi Peak Load HotSpot 40 To r Oi T�mp Load (Per Uni t) HotSpot Temp (oC) Peak 50 TopOil Peak Loa d HotSpot T� mp ( C) Oil Temp ("C) Top- (Per Unit) Temp (0C) Jni t ) 76 83 1.41 1.61 1 53 181 83 90 1 . 25 1.53 1 . 59 142 179 189 87 97 100 1 .44 1.52 176 187 104 1 07 148 175 184 81 91 95 1 .30 1 .48 1.53 145 173 182 86 97 100 1.14 1.41 1.46 1 34 172 181 88 103 1 06 1 . 31 1 . 38 167 178 107 111 1.28 1 .4 2 1 .4 6 1 .5 1 140 166 174 1 83 83 95 99 103 1 .2 0 1.36 1.41 1 .4 5 137 165 173 1 82 87 1 00 104 108 1.06 1 . 29 1 . 34 1 . 39 1 27 162 172 180 88 104 109 113 1 . 20 1.27 76 89 93 97 1 01 1 .20 1.33 1 . 37 1.41 1 .45 131 155 163 170 180 81 93 97 101 1 06 1.12 1 .27 1 .31 1.36 1 . 40 1 28 1 54 162 170 179 84 98 1 02 106 110 1.01 1 . 20 1 . 25 1 . :10 1 . 34 121 1 52 160 1 69 178 85 101 1 06 no 115 1.13 1 . 18 1.23 149 158 168 105 109 1 14 123 144 151 159 167 1 76 72 84 87 91 96 100 1.14 1.27 1 . 30 1 . 34 1 . 38 1 .42 122 144 151 1 59 167 176 77 88 92 96 1 01 1 05 1.07 1 . 20 1 . 25 1 . 29 1 . 33 1.37 1 20 14a 151 159 166 175 80 92 97 101 105 109 0.97 1.14 1 . 19 1.23 1 . 27 1 .3 2 115 142 150 158 166 175 83 97 101 1 05 1 09 114 1.07 1.12 1.17 1 .22 141 148 1 57 166 101 105 1 09 114 111 1 30 1 37 144 1 52 1 59 66 76 80 84 88 91 1 . 07 1 .19 1 . 23 1 . 26 1.30 1 . 34 111 130 137 144 152 160 71 81 85 88 92 96 1 . 00 1.13 1.17 1 .2 1 1.25 1 . 29 110 1 30 137 144 152 159 75 86 89 93 97 101 0.93 1 . 07 1.11 1.15 1.20 1 . 24 110 1 30 1 37 144 152 1 59 80 90 94 97 102 1 06 0.85 1 . 00 1 .04 1 .09 1.1 3 1.18 110 130 1 36 1 43 151 1 59 Fl4 95 98 102 1 06 110 (0C) ( C) Temp (cC) (c C) ( C) Temp NOTE: Underlined values, though beyond recommended limits (see 4 . 2 . 2 . 4 ) , are given to assist in interpolation of the maximum limit. % loss of life is in addition to norm al loss of life. • Actual wRter temperature should be 5 °c lower than the ambient temperatures shown above (see 3.5), and must be above zero C. ° Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. Per ::x:J 00 e >1;1 >-3 0 ..... 0 0 s:: <: > � ...... >-3 ::t: c.n c.n ° 0 0 ::x:J '" 01 158 1 68 1 07 1 12 0° > <: t:rJ ::x:J > 0 t:rJ �.. .... Z t:l ...... Z 0 ::x:J Ul t:rJ 0 01 > :-' Z tC oo � .... , � ..... ...... tC t:rJ oo t:rJ ..... t:rJ 0> Table 3(1) Capability Table for Normal and Moderate Sacrifice of Life 65 DC Rise, Forced-Oil-Cooled (Directed Flow - FOA, FOW*, and OA/FOA/FOA) Transformers Equivalent Load Before Peak Load 100% of Maximum Nameplate Rating "' Z :-" 00 "' .... .., ';::; �� = oo trJ .... Ambient ° c Hours of P ak Load e % Loss of Life Normal I 2" 0.25 0.50 1 .00 2 .00 4 .00 Norm al 0.25 0.50 1 . 00 2 . 00 4 . 00 or a 0.25 c.:> N m l 0 2 0.50 1 . 00 2 . 00 4 . 00 Nurmal 4 0.25 0 . 50 1 .00 2 .00 4 .00 Normal 8 0.25 0_50 1 .00 2 .00 4 . 00 Normal 24 0.25 0.50 1 .00 2 . 00 4 . 00 ek � 0 20 10 TopOil Temp t e) P a Load Per nit) HotSpot T( �mp C) 1.61 1. 77 157 182 66 73 1 .49 1 .64 1 . 68 149 176 184 71 81 84 HotSpot Temp (o C) TopOil Temp (0 C ) 1 .53 1 . 71 1 54 UI2 72 80 1 .4 2 1.58 1 .6 3 148 174 183 - 77 87 90 Peak Load Per nit) J 30 HotSpot T� mp TopOil Temp 1.43 1 .64 1 50 181 1.32 1.52 1 .56 142 173 181 Peak Load (P r Unit) e ( C) Peak Load Per nit) HotSpot Temp 78 87 81 93 96 t Cl 81 1 .3 9 1 .5 2 1 . 56 1 .60 142 167 1 75 183 74 86 89 94 1.32 1 .46 1 . 50 1 . 55 139 165 173 182 -- 78 90 94 98 1 .23 1.40 1.45 1.49 1 35 1 64 172 181 - 95 99 1 03 1 . 31 1 .4 3 1 . 46 l . 50 1 .54 132 156 163 171 180 72 84 88 92 97 1.25 1 . 38 1.41 1.45 1 . 50 130 154 162 170 180 76 88 92 97 101 1.17 1.32 1 .36 1.40 1 .45 1 . 49 1 26 1 54 161 1 70 179 188 - 1 . 25 1 . 37 1 .4 0 1 .44 1 .48 1 .52 122 1 44 151 1 59 1 67 176 67 79 83 87 91 96 1 . 20 1.31 1 .35 1 .3 9 1 .4 3 1 .4 7 122 143 151 159 167 176 72 83 87 91 96 1 00 1.12 1 . 26 1 . 30 1 . 34 1 . 38 1.42 119 143 1 50 1 58 167 176 1.19 1 . 30 1 . 33 1 .3 7 1 .4 0 1 .44 110 1 30 137 144 152 160 61 72 75 79 83 87 1.13 1 . 24 1 . 28 1 .3 2 1 .35 1 . 39 110 130 137 144 151 159 66 76 80 84 87 91 1 . 07 1.19 1 .22 1.26 1 . 30 1 . 34 llO 1 30 1 37 1 44 151 1 60 40 r 50 t C) To Oi Temp tC) Peak Load Per nit) HotSpot Temp (o e) TopOil T� mp Peak Load (Per Unit) HotSpot Tg mp ( e) TopOil Temp (o e) 1 .00 1 . 56 1 .63 110 179 188 75 94 96 1 .4 5 1.53 173 1 84 99 102 1 .00 1 .39 1 .52 1 30 175 191 95 107 112 1 .00 1 .44 1 .49 1 .5 5 110 170 179 190 75 98 101 105 1 . 34 1.41 1 .4 8 164 176 187 102 106 110 1 .00 1 .28 1 . 39 130 166 183 95 1 09 115 � � ( C) 110 162 1 70 180 75 99 103 108 1.26 1.31 1 . 37 1 56 168 177 1 02 1 07 112 1 .00 1 . 20 1 . 29 100 1 58 174 95 1 08 1 16 79 93 97 101 106 110 1 . 00 1.25 1 . 30 1 . 34 1 . 39 llO 151 159 168 1 78 75 96 101 105 110 1.17 1 .23 1 . 28 1 .34 147 157 166 177 99 1 04 1 09 1 14 1 .00 1 .1 3 1.21 1 30 151 1 64 95 1 06 112 75 1 . 00 1 . 20 1 . 24 1 . 28 1 . 33 1.37 110 142 149 157 166 174 75 92 96 100 105 109 1.12 1.17 1.22 1.27 1 .3 2 139 148 157 165 1 74 95 100 1 04 109 1 14 1 .00 1 .0 9 1.15 1 . 21 1 30 143 1 54 1 64 95 102 107 113 1 10 1 30 136 144 151 1 59 80 90 94 97 101 105 0.85 1 .00 1 .04 1 .0 9 1.13 1.18 109 1 30 1 36 143 151 1 59 84 95 98 102 1 06 1 10 70 81 84 88 92 96 1 . 00 1.13 1 .16 1.21 1.25 1 . 29 110 130 136 144 152 1 59 75 86 89 93 97 101 trJ tzJ Cl c::: 1 .00 1 .34 1 . 38 1.43 88 92 96 1 00 105 .... tzJ 8 trJ '""l 0 ::0 t"' 0 > 0 Z Cl s::: .... Z 0.93 1.06 1.11 1.15 1.19 1 . 23 NOTE: Underlined values, though beyond recommended limits (see 4.2.2.4), are given to assist in interpolation of the maximum limit. % loss of life is in addition to normal loss of Iife_ *Actual water temperature should be 5 °C lower than the ambient temperatures shown above (see 3 . 5 ) , and must be above zero °C_ Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. trJ ::0 > t"' 6 ..... t"' �s::: trJ ::0 00 trJ 0 '"I:l 0 ::e tzJ ::0 Table 3(m) Capability Table for Normal and Moderate Sacrifice of Life 65 ° C Rise, Forced-Air-Cooled (OA/F A/F A) Transformers Rated Over 133% of Self-Cooled Rating Equivalent Load Before Peak Load 50% of Maximum Nameplate Rating >oj ::0 > z 00 "'l 0 ::0 = 0 Hours of Peak Load I 2 1 % Loss of Life 2 Peak Load (Per Unit) Spot Temp o Hot- Top- ( C) Temp o Peak Load (Per Oil ( C) Unit) Hot- f C y To - Oi Spot T!im ( Temp t Cl Peak Load (Per Unit) HotS pot Te m p tC) Toy- Hot- Oi Ts mp Peak Load ( Pe r Unit) S pot Temp (o ( C) C) TopOi l Temp ( C) Load (Per Ho t Spo t T5 mp Peak Unit) ( C) Top- Oil ( C Temp o ) 1 .8 8 2.09 1 59 185 63 72 1 .7 9 2.00 1 59 185 70 78 l . 70 1 .9 2 1 59 1 84 77 85 l .60 1 .83 1 58 1 84 83 92 l .50 1.74 1 56 1 83 90 98 Normal l . 74 1 .9 1 1 .9 7 1 54 179 188 69 80 84 l .66 1 .8 4 l .9 0 153 1 78 186 74 85 89 1 .5 8 1.77 1 .8 3 1 52 178 1 86 80 91 95 1 . 50 1 .69 1.75 152 177 185 85 96 100 l .40 l .6 1 l .67 1 50 176 1 84 90 101 105 1.31 1 .53 1 . 59 1 50 176 1 84 96 107 110 0.25 0.50 l .00 2.00 4.00 0.25 0.50 1 . 00 2.00 4.00 0.25 0.50 1 . 00 2.00 4 . 00 0.25 0 . 50 l . 00 2 . 00 4 .00 Normal 24 Oil ( C) 57 65 Normal 8 C) To pTemp o 50 160 1 86 Normal 4 ) Hot- Spot T!imp ( t:rJ 40 l .96 2.17 0_25 0.50 1 .00 2 .00 4 .00 No mal I-' (yPer n it 10 30 Normal r C;.:> Peak Load � Ambient ° c 20 0.25 0 . 50 l . 00 2.00 4 .0 0 ::0 00 e::: '"d >oj 0 >-' 0 0 � <: > :IE ::3 ::c Q1 Q1 ° 0 0 ::0 O"l l . 54 1 . 70 1 .7 4 1 .80 146 1 70 178 187 76 89 93 98 1 .4 7 l .6 3 1 .6 8 1.73 1 .4 0 1 . 54 l . 59 1 . 63 l .68 135 H i8 166 174 182 75 88 92 97 102 1 .33 1 . 48 1 .52 1 . 58 1 .63 1 .32 1 .45 l . 49 l . 54 1 . 59 1 . 63 1 24 145 152 160 168 177 69 82 86 90 95 100 1 . 23 l . 36 1 .40 1 .44 l . 49 1 . 53 111 131 137 144 151 159 62 73 77 81 85 90 145 170 177 186 1 45 1 69 177 1 86 - 142 1 67 176 93 1 06 111 -- 1 .1 4 1 . 34 141 1 66 98 111 144 1 68 176 185 89 102 106 111 - l.23 1 .42 1 .47 1 .19 1 .35 1 .39 1 .4 5 1 .5 0 133 1 56 1 64 172 181 - 87 1 00 104 1 09 1 14 1.11 1 . 28 1 . 33 1 . 38 133 156 163 172 91 1 04 108 113 1 . 03 1 . 20 1.26 132 155 163 78 90 94 98 1 03 1 08 1.11 1 .25 l . 30 1 .3 5 1 .4 0 1 .45 123 1 44 1 52 1 59 1 68 176 82 94 98 102 1 07 112 l .03 1.19 1 . 23 1 . 28 1 . 34 1 23 144 151 159 167 86 98 102 107 111 0.94 l.11 1.16 l . 22 122 144 151 159 90 1 03 107 111 71 82 85 89 94 98 1 .0 1 1.15 1 . 20 1 . 25 1 .30 1 .35 110 1 30 136 144 151 1 59 75 86 90 94 98 103 0.92 1 .08 1.13 1 . 18 1 . 23 1 . 29 110 1 30 137 143 151 1 59 79 90 94 98 102 107 0.84 1 .00 1 . 06 1.1 1 1.16 1 . 21 110 1 30 137 144 151 159 84 95 99 1 03 107 111 85 98 101 1 06 80 93 97 102 1 .4 0 1 .5 6 1.61 1 .67 135 157 165 174 182 - 79 92 96 101 106 1 . 26 1.42 1 .4 6 1.51 1.57 1 34 1 57 1 64 1 73 1 82 - 83 96 1 00 1 05 110 1 . 25 1 . 39 1 .4 3 1 . 48 1 .53 1 . 58 1 23 145 152 160 168 176 74 86 90 95 99 1 04 1.18 1.32 1 .3 7 1 .4 2 1 .4 7 l.52 1 23 145 1 52 160 1 68 177 1 .16 1 . 29 1 . 34 l .38 1 .4 3 1 .4 7 111 130 137 144 1 52 159 66 78 81 85 90 94 1 .0 9 1.23 1.27 1.31 1 .36 1 .4 1 111 130 137 143 151 1 59 1 .32 1 .4 9 1 . 54 1 . 60 CJ1 a 0 > <: t:rJ NOTE: Underlined values, though beyond recommended limits (see 4 . 2 _ 2 . 4 ), are given to assist in interpolation of the maximum limit. % loss of life is in addition to normal loss of life. Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. 95 108 ill ::0 > 0 t:rJ :IE Z 9 Z 0 ::0 .., 00 t:rJ 0 Q1 > :-' Z <0 00 ", .., � -;::. <o t:rJ oo t:rJ ..... t:rJ 0> Ol Z :-" 00 Table 3(n) Capability Table for Normal and Moderate Sacrifice of Life 65 ° C Rise, Forced-Air-Cooled (OA/FA/FA) Transformers Rated Over 133% of Self-Cooled Rating Equivalent Load Before Peak Load 70% of Maximum Nameplate Rating <0 ""' t-o "j;;:j ' tzj � tzj ex> tzj ..... = Ambient ° c 0 Hours of Peak Load ! 2 % Loss of Life � 1 59 185 61 69 1 .82 2.03 Normal 1 . 70 1 .88 1 . 94 152 178 187 71 82 86 1 .62 1 . 80 1 . 87 0 ,25 0 . 50 1 .00 2 .00 4 .00 0.25 0.50 1 .00 2 . 00 4 .00 N 0orm a .25 8 l 0.50 1 .00 2 . 00 1 . 00 Normal 24 Peak Load (Per Unit) 2.1 1 Normal 4 TopOil Temp tCl 1 .91 0.25 0.50 1 . 00 2 .0 0 4 . 00 Normal 2 /-Init) er HotSpot T� mp ( C) Normal 0 . 25 0 , 50 1 . 00 2 ,00 4 , 00 CO Peak Load 0 , 25 0.50 1 . 00 2,00 4 , 00 1 . 52 1 . 68 1 .73 1 . 78 1 .40 1 .54 1 . 58 1 . 63 1 . 68 145 1 69 177 1 86 76 89 93 98 1 .45 1 .6 1 1 . 66 1.71 1 34 158 165 173 182 75 88 92 97 102 69 82 86 90 95 1.25 1 .3 9 1.43 1 .4 8 1 ,6:1 124 145 152 160 168 176 1 .2 3 1 . 36 1.40 1.44 1 . 48 1 .53 110 130 137 144 151 1 59 1 .32 1 .4 5 1.49 1 . 54 1 . 58 20 10 1 .3 2 1 .4 7 Hot· Spot Temp (0G ) TopOil Temp tC) Peak Load (Per Unit) Hot· Spot Tsmp ( C) y To Oi Temp tCl 30 Peak Load (Per Unit) 159 67 76 1 .72 1 . 95 1 57 183 74 82 1 .63 1 .8 6 152 177 186 - 76 87 91 1 .54 1 51 1.73 1.79 81 93 96 1 .45 1 . 65 1.71 .!§.!. 144 169 177 185 1 33 1 57 1 64 177 185 Hot· Spot Temp tC) y To Oi Temp tC) 40 Peak Load Per it ) Hot· Spot Temp (oC) � n 50 Top· Oil Temp (oC) Peak Load (Per Unit) HotSpot Temp (C ) Top· Oil Temp (0G ) 1 56 80 89 1.53 1.77 1 56 182 87 95 1 .3 9 1 .6 7 152 181 93 102 150 175 184 87 98 102 1.35 1.57 1 . 63 148 175 183 92 103 107 1 .23 1 .4 8 1 .54 145 173 182 96 1 08 112 183 - 81 94 98 102 78 92 96 1.37 1 . 54 1 . 59 1 .65 143 1 68 1 76 1 85 - 85 98 102 107 133 82 96 1 00 1 . 29 1 .4 7 1 . 52 1 . 58 142 1 67 175 183 - 105 110 1.18 1 . 34 1 . 39 1 .44 1 .4 9 132 156 1 63 172 180 89 1 02 106 111 86 1 . 20 1 . 39 1.45 140 1 66 1 74 93 106 111 1.10 1.31 1.10 1 31 1 54 90 103 108 113 - 1 . 00 1.19 1 .25 101 105 1 00 74 86 90 94 99 104 1.18 1.32 1 .37 1 .4 2 1 .4 6 1.51 1 23 145 1 52 1 60 1 67 1 76 78 90 94 99 103 1 08 1 . 10 1 . 25 1 . 30 1 . 35 1 .40 1 .4 5 1 22 144 151 1 59 167 1 76 81 94 98 1 02 1 07 112 1.01 1 .18 1.23 1 . 28 1 . 34 121 144 151 1 58 1 67 85 98 102 106 11 1 0,92 1.10 1 .52 1.57 123 145 151 1 60 1 67 176 62 73 77 81 85 90 1.16 1 .29 1 .33 1 . 38 1.42 1 .47 111 131 137 144 151 1 59 66 78 81 85 89 94 1 .0 8 1 . 23 1.27 1 .3 1 1 . 36 1 .4 1 1 10 1 30 137 144 151 1 59 70 82 86 89 94 98 1 .01 1.16 1 .20 1 . 25 1 . 30 1 .35 1 10 1 30 1 37 1 44 151 159 75 0,92 1 . 08 1.13 1 . 18 1.23 1 . 28 1 10 1 30 1 36 143 1 51 1 58 79 90 94 98 102 106 156 1 64 172 ill 1 00 1 04 1 09 ll± 86 90 94 98 102 1 37 164 1 96 10 c::: ""' t;I tzj "%j 0 :;Q t" 1 73 181 1 .6 2 tzj tzj tzj Q 1.25 1.41 1 .46 1 .50 1 . 56 1 .5 2 1 .57 ""' 1 . 26 1.32 1 . 38 162 171 1 28 1 54 1 62 94 108 1 12 - 0 > t;I ..... Z Q � Z tzj s NOTE: Underlined values, though beyond recommended limits ( ee 4 . 2 .2.4), are given to assist in interpolation of the maximum limit. % loss of life is in addition to normal loss of life. Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. 1.15 1 . 21 119 1 43 1 50 1 58 89 102 106 111 0,83 1 . 00 1 . 06 1 .10 1 .16 1.21 1 10 1 30 1 37 143 1 51 1 59 84 95 99 102 107 111 :;Q > t" 6. .... t" .:.. � � tzj :;Q 00 tzj t;I "C 0 ::;:J tzj :;Q .., Table 3(p) Capability Table for Normal and Moderate Sacrifice of Life 65 °C Rise, Forced-Air-Cooled (OA/FA/FA) Transformers Rated Over 133% of Self-Cooled Rating Equivalent Load Before Peak Load 90% of Maximum Nameplate Rating ::0 � 00 "'l = Hours of Peak Load % �Load Per nit) Spot Tg mp Temp Peak Load Per Normal l .8 4 2 . 04 158 H l3 66 74 l . 74 1 .96 0.25 0.50 1 .0 0 2.00 4 .00 Normal 1 � � 0.25 0.50 1 . 00 2.00 4.00 Normal 2 0.25 0.50 l .00 2.00 4.00 No rmal 4 0.25 0.50 1 .00 2 .00 4 .00 Normal 8 0.25 0.50 l . 00 2.00 4.00 N or ma l 24 Top· Loss of Life 0.25 0.50 1 . 00 2 . 00 4.00 Peak Hot- ( e) Ambient °c 20 10 0 Oil (oe) � nit) Hot· Spot Temp (oe) TopOil T� mp ( e) Peak Load (Per Unit) 72 81 1.63 1 .87 157 1 83 - Hot· Spot T�mp ( C) 155 182 y To Oi T� mp trJ 30 ( C) Peak Load (Per Unit) 78 87 1.51 1 .78 Hot· Spot Temp t c) 0 ::0 � y To Oi Tg mp ( C) 151 181 - 84 94 40 Peak Hot· Spot Load �Per nit T� mp ( C) 1 . 23 1 . 67 1.75 134 179 188 ) 50 Top- Oil T� mp Peak Load Hot· ( e) �Per nit) Spo t Tll mp 86 99 102 1 .54 1 .6 4 175 185 ( C) Top Oil T16mp ( C) 1 05 1 08 ::0 00 e "d .., 0 .... 0 0 � <: > ::e � 1 .6 5 1 .8 3 1 .8 9 151 176 185 73 84 88 1 . 56 1 . 76 1 . 82 150 176 1 85 - 78 89 93 1.47 1 . 68 1.74 147 175 1 83 - 83 95 98 1 . 35 1 . 59 1 . 66 144 173 182 87 99 1 04 1.10 1 . 49 1 . 57 1 26 171 180 85 1 04 1 08 143 168 176 185 76 89 94 98 1 .42 1 .5 8 1 .6 4 1 .6 9 142 167 175 183 80 93 98 102 1 . 33 1. 51 1 . 57 1 .62 140 166 174 182 84 98 102 107 1.23 1 . 44 1.49 1 . 56 136 1 64 173 182 87 102 1 06 111 1 . 03 1.35 1 .42 122 162 171 85 1 05 110 1 . 38 1 . 53 1.57 1 .6 2 1 .67 133 1 56 164 172 181 74 87 92 96 101 1 .3 1 1 .4 6 1 .51 1 .56 1 .6 1 132 1 56 163 171 180 78 91 95 1 00 105 1.23 1.40 1.44 1 .4 9 1.55 1 .6 0 130 155 162 171 179 189 81 95 99 1 04 109 114 1 . 14 1.32 1 . 37 1.43 1 . 48 1 27 153 162 170 179 84 99 103 1 08 113 0.98 1 . 24 1.30 1.35 1 17 152 160 168 83 102 1 07 111 1 .31 1 . 44 1 .4 9 1.53 1.58 1 .6 3 1 23 144 152 1 59 1 67 176 69 81 85 90 94 99 1 .24 1 .3 8 1 .4 2 1 .47 1 .52 1 . 57 122 144 151 159 167 176 73 85 89 94 98 1 04 1.16 1.32 1 . 36 1.41 1 .4 6 1.51 121 144 151 1 58 1 67 175 77 90 93 98 103 108 1 . 07 1 . 24 1 . 29 1 . 34 1 .4 0 1 .45 119 143 150 1 58 167 175 80 93 98 102 1 07 111 0.95 1 .17 1 . 22 1 . 28 1 . 33 113 142 149 158 166 81 97 101 1 06 110 1 .22 1 .3 6 1 .4 0 1 .44 1.49 1 .53 1 10 130 137 143 151 1 59 62 73 77 81 85 90 1.15 1 .29 1 .3 3 1.38 1 .4 2 1 .4 7 110 130 136 144 1 51 1 59 66 77 81 85 89 94 1 .08 1 .22 1.27 1.31 1 .36 1.41 110 130 1 36 143 151 1 58 70 82 85 89 93 98 1.00 1.15 1 . 20 1 . 25 1 .30 1 .35 110 130 1 37 1 44 1 51 1 59 75 86 90 94 98 102 0.92 1 . 08 1.12 1.18 1 . 23 1 . 29 1 09 130 136 143 151 1 59 79 90 94 98 102 107 (see 4.2.2.4), are given to assist in interpolation of 166 177 1 08 1 13 ° (1 0 ::0 1 .49 1 . 66 1. 71 1.76 NOTE: U nd erlined values, though beyond recommended limits % l oss of life is in addition to normal loss of life. ::c 1.37 l . 46 C11 C11 the maximum limit. Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. 1 .24 1 . 32 158 168 1 08 1 13 1 . 14 1 . 22 147 1 58 1 04 1 10 a> C11 0 (') > <: trJ ::0 > 0 trJ ::e ..... Z t;;1 Z 1 . 08 1.14 1 .20 1 40 148 1 57 1 00 1 05 110 l . 00 l . 05 1.11 1.16 1 .22 1 29 136 143 151 159 94 98 1 02 1 06 111 0 ::0 ..... 00 trJ ("l 01 > :-' Z "' 00 t-:> .... . .... .... ", trJ ao trJ .... trJ n> Ol Z ;-J oo Table 3(q) Capability Table for Normal and Moderate Sacrifice of Life 65 DC Rise , Forced-Air-Cooled (OA/FA/FA) Transformers Rates Over 133% of Self-Cooled Rating Equivalent Load Before Peak Load 100% of Maximum Nameplate Rating te ..... t-:> ;::; � � oo trl ,... = 0 Hours of Peak Lo ad % Loss of Life Normal ! 2 156 183 68 77 Normal 1 .6 2 1.81 1.86 150 176 184 74 86 89 0.25 0.50 1 . 00 2.00 4.00 Normal 4 0.25 0.50 1 . 00 2.00 4.00 Normal 8 0.25 0.50 l .0 0 2.00 4.00 Normal 24 (oC) TopOil Temp (C) 1.78 2 .00 Normal 2 �Per nit) I HotSpot Temp 0. 25 0.50 1 .00 2.00 4.00 0.25 0.50 1 . 00 2.00 4 . 00 !;.j � Peak Load 0.25 0.50 1 .0 0 2 .0 0 4 . 00 1 .48 1 .64 1 .6 9 1 .74 P ea k Load (Per Unit) l .6 8 l.91 l .52 1 .73 1 . 79 Ambient ° c 20 10 HotSpot Temp (oC) TopOil T!i mp ( C) HotSpot Temp tC) 40 Tor Oi Temp te) Peak 1I0t- (Per Spot Temp (C ) Load Uni t) 50 TopOil Temp Peak (oC) (Per Unit) Load HotSpot T� mp TopOil Temp ( C) (DC) 149 181 80 90 1 . 06 1.71 1 . 80 ll5 178 188 76 96 99 1.56 1.67 172 184 100 1 04 1 . 02 1 .50 l.65 1 31 175 192 95 1 08 114 147 1 74 183 79 91 94 1 .40 l . 64 l. 7 1 142 173 182 82 96 100 1 .03 l.55 l.62 ll2 171 180 76 1 00 1 04 l . 52 l.41 164 177 1 88 - 103 1 09 1 13 - 1 . 02 l . 34 131 1 66 95 110 1 . 30 1 . 38 1.45 156 167 103 109 114 1.01 1 . 23 1 . 34 1 30 158 173 95 1 09 1 16 1 . 38 1 . 52 1 .57 1.61 1 . 66 132 1 56 163 171 1 80 74 87 91 96 101 1 .30 1 .4 6 1 .50 l.55 1 .60 l . 66 130 155 162 171 179 189 77 91 95 1 00 105 110 1 . 30 1 .45 1 . 49 1 .53 1 .58 l .62 122 1 44 1 51 159 167 175 68 81 85 90 94 99 1 .23 1 .3 8 1.42 1 .4 7 1.52 l .57 121 144 150 1 59 1 66 175 62 73 77 81 85 90 l.15 l . 29 1 . 33 l .38 l .4 2 l .47 110 130 137 143 151 159 130 1 37 143 151 1 59 (0C) 30 Peak Load (Per Uni t) 1 . 54 1.82 1 . 39 l . 57 1.62 llO ( C) y To Oi Temp 74 83 76 89 94 98 1 . 23 1 . 36 1 .4 0 1 .44 1 .4 8 l .53 Hot· Spot T8 mp 155 182 142 167 175 1 8 4- l .68 Peak Load (Per Unit) 139 166 174 183 l.28 l .60 1 34 1 64 172 182 82 97 102 107 1 . 02 1.41 1 . 47 1 . 53 1 .43 1 . 49 1 . 54 1 . 59 1 26 1 53 161 170 178 188 79 94 99 1 04 109 l . 02 1 . 30 1 . 36 1 . 42 1 . 47 72 85 89 94 98 103 1 . 14 1.31 1 . 36 1 .40 1 .46 1 .51 118 143 150 1 57 166 175 75 A9 93 97 102 107 1 .01 66 77 81 85 89 94 l . 08 110 130 1 36 143 151 1 59 70 82 85 89 93 98 AO 94 98 103 NOTE: Underlined values, though beyond recommended limits (see % loss of life is in addition to normal loss of life. 1.49 l . 54 1.61 1 . 20 l .38 l. 22 1 . 27 1 .31 1 . 36 1.41 4 . 2 . 2 . 4 ), l 14 III 161 171 1 80 111 75 101 1 06 111 151 159 1 69 178 76 98 1 02 1 08 l12 1 . 29 l . 34 1 . 39 1.45 110 142 149 157 166 175 75 92 97 101 106 112 1 . 00 1.15 1.20 1.25 1.30 1.35 110 1 29 1 36 143 151 1 59 75 86 89 94 98 1 02 177 ..... trl trl trl C'l C ..... t::I trl I'%j 0 :x:J t"" 0 >1.20 1 .27 1 . 34 146 156 167 99 105 III 1 . 00 1.16 1 . 25 1 30 150 163 95 106 l13 t::I ..... Z C'l � trl l.23 1.14 1 . 20 1.27 1 .32 138 147 156 164 95 1 00 105 110 l . 08 l.13 1.18 1 . 23 l .28 130 1 36 143 150 159 90 94 98 1 02 1 06 are given to assist in interpolation of the maximum limit. Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. 1.25 130 143 154 164 95 102 1 08 114 1 .0 5 l.10 l.16 1 .2 1 136 143 1 50 158 98 102 1 06 1 .00 1.10 1.18 ::tI >t;'" 0 ..... t"" � trl III � trl t::I "tI 0 ::;: trl :x:J '"'l :;l:l Table 3(r) Capability Table for Normal and Moderate Sacrifice of Life 65 ° C Rise, Forced-Oil-Cooled (Non-Directed Flow - FOA, FOW*, and OA/FOA/FOA) Transformers Equivalent Load Before Peak Load 50% of Maximum Nameplate Rating � 00 "'l 0 :;l:l � = 0 Hours of Peak Load % Loss of Life Normal 1 2 0.25 0.50 1 .00 2.00 4 .0 0 Normal 1 � 0.25 0.50 1 . 00 2 . 00 4.00 Normal 01 2 0 25 0 . 50 1 . 00 2.00 4.00 Normal 4 0 .2 5 0.50 1 .0 0 2 . 00 4 . 00 Normal 8 0.25 0.50 1 .00 2.00 4 .00 Normal 24 0.25 0.50 1 .00 2 .0 0 4 .0 0 Peak Ho t · JPer nit ) Spot Ts m p 1 .9 4 2.12 161 187 Load ( C) Ambient DC 20 10 Top- Oil Temp (0 C) 60 70 Pea k Load Per ni t ) J 1 .85 2 . 05 Hot· Spot Temp o ( C) 160 186 -- TopOil Temp (D C) 66 76 Peak Load (Per Unit) 1 .77 1.97 Hot· Spot T� mp ( C) 1 59 185 --- y To Oi Tem p t C) 72 82 30 Peak Load (Per Uni t ) 168 189 y ( C) Peak Load (Per Unit) Ho tSpot Temp (0 78 88 1 . 59 1.81 158 184 Hot· Spot Te (o mp To Oi Ts mp 159 C) 185 -- 50 40 C) Top· Oil T� mp ( C) 84 94 � Peak Load (Per Unit) HotSpot Temp To ' Oi Temp (0 1 .4 9 1.72 1 56 1 84 90 1 00 (C ) C) t'l :;l:l 00 c::: "'C '"'l 0 ..... 0 0 a: -< > :e ::3 l.71 1.87 1 55 1 80 72 85 1 .63 1.80 1 . 85 1 54 179 188 77 89 94 1.55 1.73 1.79 153 178 1 87 82 94 98 1 . 48 1 . 66 1.72 152 178 186 87 99 103 139 1.59 1 . 64 151 177 185 92 104 108 1.30 1. 5 1 1 . 57 1 50 176 185 96 1 09 113 :I: 01 01 ° n 0 :;l:l 1 .5 1 1 .6 5 1.70 1 .7 5 146 171 178 188 - 79 93 97 102 1.45 l .6 0 1 .64 1 . 69 146 171 178 187 - 83 97 101 106 1 . 38 1.53 1 . 58 1.63 145 169 178 186 - 87 100 105 110 1.31 1 . 47 1.51 1 . 57 144 169 177 186 - 1 . 38 1.51 l.55 l . 59 1 .63 136 158 1 66 174 183 77 91 96 101 106 1 .32 1 .45 1 .49 1 .54 1 . 58 135 158 166 174 182 81 95 99 104 110 1.25 1 . 39 1.43 1 .4 8 1.53 134 157 165 173 84 98 1 03 1 07 113 1.18 1.33 1 . 37 l.42 1 33 1 57 165 173 � 91 1 04 109 1 14 - 1 . 23 1.40 1.45 143 168 176 94 108 113 1.14 1 . 32 88 102 107 112 1.11 1.26 1.31 133 157 164 92 106 110 1 .03 l.19 1 .24 142 166 98 112 '" 01 ° n > -< t'l :;l:l 132 1 55 163 95 109 113 > Q t'l :e Z t::I 1 . 30 1 .4 2 1 . 46 l . 50 1 . 54 1 . 59 1 24 146 152 160 168 177 71 84 88 93 98 104 1 .2 3 1 . 37 1 .4 0 1 .4 5 1 .4 9 1 . 53 1 24 146 152 160 168 177 75 88 92 97 102 1 07 l.17 l .30 1.35 1 .3 9 1.43 1 .4 8 1 24 145 1 53 1 60 168 176 79 91 96 1 00 106 111 1.10 l . 24 1 . 29 1.33 1 . 38 123 145 152 1 60 1 68 82 96 100 1 05 110 1.02 1.17 1.22 1.27 1.32 122 145 1 52 1 59 167 86 99 104 1 08 113 0.94 1 .1 0 1.15 1 . 20 122 144 152 1 59 90 1 03 107 112 1.21 1 .33 1 . 37 1 .4 1 1 . 45 1 . 50 111 130 1 37 144 151 159 63 75 79 83 88 93 1.15 1.27 1.31 1 .35 1 .4 0 1 .4 4 111 130 137 144 151 159 67 79 83 87 91 96 1 .0 8 1.21 1.25 1.30 1 . 34 1 .39 110 130 1 37 144 151 1 59 71 82 87 91 95 100 1 .01 1.15 1.19 1 .23 1 .2 8 1 . 33 111 130 1 37 144 151 160 75 87 91 95 99 1 04 0.93 1.08 1.12 1.17 1.21 1 . 26 110 130 1 37 143 151 1 59 79 91 95 99 103 108 0.84 1.01 1 . 05 1.10 1.15 1.20 110 1 30 1 37 1 44 1 51 1 59 83 95 99 103 1 07 112 NOTE: Underlined valup.s, though beyond recommended limits (see 4 . 2 . 2 . 4 ), are given to assist in interpolation of the maximum limit. % loss o f life is i n addition to normal loss o f life. *Actual wllter temperature should be 5 °c lower than the ambient temperatures shown above (see 3.5), and must be above zero °c. Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. Z Q :;l:l H 00 trl �> :-" '2: ", 00 � H ;. � ", trl oo trl ..... trl n ;.- tll z :-' tIJ � ", ,;::; Table 3(8) Capability Table for Normal and M oderate Sacrifice of Life 65 ° C Rise, Forced-Oil-Cooled (Non-Directed Flow - FOA, FOW*, and OA/FOA/FOA) Transformers Equivalent Load Before Peak Load 70% Maximum Nameplate Rating � gJ oo l'J = ..... Ambient ° c 0 Hours of Peak Load % 1 .80 2.00 1 59 185 1 .6 7 1 .8 3 1 . 89 1 54 179 187 74 86 91 1 . 59 1 .77 1.82 1 52 178 186 1 .4 9 1 . 64 1 .68 1.73 145 170 178 187 79 93 97 103 1 .43 1 . 57 1 .6 2 1 .6 7 Normal 0.25 0 . 50 1 . 00 2 .00 4 .00 0.25 0.50 1 .00 2.00 4 .0 0 Normal 0.25 0.50 1 .00 2.00 4 . 00 Normal 24 64 73 1 .8 8 2 . 07 Normal 8 1 59 185 Normal Normal 4 /;nit) HotSpot Temp (0C) /;nit) 0.25 0.50 1 . 00 2.00 4 . 00 2 Peak Load Per HotSpot T!;mp ( C) 0.25 0.50 1 . 00 2.00 4 .00 0.;, 0) TopOil Temp ( oC) Peak Load Per Loss of Life 0.25 0.50 1 . 00 2.00 4 . 00 10 145 169 177 186 30 20 Peak Load (Per Unit) HotSpot T!;mp ( C) 70 80 1.7 1 1.92 1 58 1 84 79 91 95 1 .52 1 . 70 1 .7 5 TopOil Temp (oC) 83 96 101 106 1.36 1.51 1 . 56 1 .61 TopOil T!lmp ( C) Peak Load (Per Hot- y To Oi Temp tC) 40 Peak Load (Per Hot- 50 TopOil Temp tc) Peak Load (Per Hot- TopOil Unit) Spot Temp tc) 76 86 1 .6 2 1 .8 3 157 184 82 91 1.52 1.75 1 56 183 88 98 1.39 1.66 1 53 182 93 1 04 152 177 186 84 96 1 00 1 .4 3 1 .6 2 1 .68 1 50 177 185 88 101 105 1.34 1 . 54 1.61 148 175 1 84 93 105 110 1.23 1 .4 6 145 174 97 1 10 144 168 177 185 87 100 105 110 140 166 175 94 1 08 113 1 .10 1.30 1 37 165 97 112 1 .2 8 1 . 44 1.49 1.55 142 167 176 184 90 1 04 109 1 14 Unit) 1.19 1.37 1.43 Spot Temp (0C) Unit) Spot Temp t C) Temp (oC) - l'J l'J l'J 0 c: 8 l'J "l:J 0 ::0 t'" 1 .37 1 . 50 1 . 54 1 . 59 1.63 1 34 1 58 165 1 74 1 82 76 91 95 101 1 06 1 .3 1 1 .44 1.48 1 .53 1.58 1 34 157 164 173 182 80 94 99 1 04 109 1 . 24 1.38 1 .42 1 .47 1.52 1 33 1 56 164 173 181 8 ·1 9H 102 108 113 1.17 1.32 1 . 36 1 .4 1 132 1 56 163 172 87 101 106 111 1.09 1.25 1 . 30 1.35 131 155 162 171 91 105 109 115 1 . 00 1 .1 8 1 . 23 1 28 1 54 161 93 108 113 1 . 29 1 .4 2 1 .4 6 1 .5 0 1 .5 4 1 .5 9 1 23 145 1 52 1 60 1 68 177 71 84 88 93 98 104 1.23 1.36 1 .4 0 1 . 44 1.49 1 .53 123 145 152 1 59 168 176 74 88 92 97 102 107 1.16 1 . 30 1 . 34 1.39 1 . 43 1 . 48 1 23 145 151 159 168 176 78 91 95 1 00 105 llO 1.10 1 . 24 1 . 28 1 . 33 1 . 37 1 . 42 1 23 144 1 51 1 59 1 67 175 82 95 99 1 04 109 114 1.01 1.17 1.22 1 . 26 1.31 121 144 151 158 167 86 99 103 107 113 0.92 1.10 1.15 1.20 1 20 143 1 50 1 58 89 102 1 07 111 1 .2 1 1 . 33 1 .3 7 1.41 1 .4 5 1 .49 110 130 137 144 152 1 59 63 75 79 83 88 1.14 1 . 27 1 .3 1 1 .3 5 1 .4 0 1 . 44 110 130 1 37 1 44 151 1 59 67 79 83 87 92 96 1 . 08 1.21 1 . 25 1.29 1 .34 1 . 38 110 130 137 144 151 159 71 83 87 91 96 100 1.01 1.14 1.19 1 . 23 1 . 28 1 . 33 110 130 136 1 44 151 159 75 87 90 95 99 1 04 0.92 1 . 08 1.12 1 .17 1 . 21 1 . 26 110 1 30 1 36 143 151 158 79 91 94 99 103 108 0.84 1 . 00 1.05 1.10 1.15 1.20 110 130 136 143 151 1 59 83 95 99 1 03 107 112 93 0 ;.t:l Z 0 s= - NOTE: Underlined values, though beyond recommended limits (see 4 . 2 . 2 . 4 ), are given to assist in interpolation of the maximum limit. % loss of life is in addition to normal loss of life. *Actual water temperature should be 5 °c lower than the ambient temperatures shown above (see 3.5), and must be above zero °c. Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. Z l'J ::0 ;.t'" 0 t:: ,:... s= s= l'J ::0 tIJ l'J t:l ..", 0 ::6 tr:I ::0 Table 3(t) Capability Table for N onnal and Moderate Sacrifice of Life 65 ° c Rise, Forced-Oil-Cooled (Non-Directed Flow - FOA, FOW*, and OA/FOA/FOA) Transformers Equivalent Load Before Peak Load 90% of Maximum Nameplate Rating '"'l ::0 :> Z 00 "%j 0 ::0 = Ambient 10 0 Hours of Peak Load % Loss of Life Normal 1 2 0. 2 5 0.50 1 . 00 2 . 00 4 . 00 Norm al 0.25 0.50 1 . 00 2 . 00 4.00 1 CJ:> ...::J Normal 2 0.25 0.50 1 . 00 2.00 4.00 N orm al 4 0 . 25 0.50 1 .0 0 2 . 00 4 .00 Normal 8 24 Peak �Per nit) Load Top· Oil Temp Peak Load �Per Hot· Spot Temp Top· O il T�mp Peak Load Hot· Spot T�mp s:: °e 30 r To Oi Temp Peak Load (Per Unit) Hot· Spot Temp 40 r Peak To · Oi Temp Load 50 Hot· S pot Temp Top· Oil Te mp te) (Per Un i t ) 1.80 2.01 1 58 185 68 78 1.71 1.92 157 1 84 74 84 1.61 1 .8 4 155 183 80 90 1 . 49 1 .7 5 151 182 85 96 1 . 26 1 .65 138 180 87 1 02 1 . 62 1.79 1 .8 5 151 1 78 186 76 89 93 1 . 54 1.72 1.77 150 177 185 81 93 97 1 .4 5 1 . 64 1.70 1 48 175 184 85 98 102 1 . 34 Ui 6 1 .6 3 145 1 74 183 8H 1 02 107 1.13 1 .4 8 1 . 54 130 172 181 87 106 ( C) te ) nit) te) ( e) (Per Unit) ( e) te) te) tC) ( C) Pe a k Load (Per Ho t · Spot Temp Top· Oil Temp 1 .5 2 1.62 1 75 186 106 110 Unit) tC ) (oC) t'l ::0 00 e:: "tI '"'l 0 ...... 0 0 s:: <: :> ::!l ::3 III ::r: 1 .36 167 110 en en ° C':l 0 ::0 1.47 1 .62 1 . 66 1 .71 143 1 69 176 185 79 93 97 1 03 1.39 1.55 1 . 60 1 .6 5 142 167 1 75 184 82 97 101 1 06 1 .32 1.48 1.53 1 .59 140 166 174 184 86 1 00 105 110 1.22 1 .4 1 1.46 1.52 136 165 173 182 88 1 01 1 09 114 1.05 1.33 1 . 39 1 24 1 62 171 86 1 07 ll2 en CJl 1 . 23 1 . 30 1 57 168 1 09 115 ° ("J :> <: t<:! 1.36 1 . 49 1.53 1 . 58 1 . 62 0.25 0.50 1 . 00 2 . 00 4 . 00 1 . 29 1 .42 1 .45 1 . 49 1.54 1.58 Normal 1 .21 0 . 25 0.50 1 .00 2 . 00 4 . 00 Hot· Spot T�mp 20 1.33 1.37 1.41 1 . 45 1 . 49 133 156 1 64 172 76 90 95 1 00 105 1 . 29 1.43 1.48 1.52 1.57 123 145 152 159 168 176 70 84 88 93 98 103 110 130 137 144 151 159 63 75 79 83 88 93 ill ::0 > 132 156 1 64 172 79 94 98 1 03 1 09 1.22 1 . 37 1 .42 1 .4 6 1 .5 1 131 155 1 63 171 180 82 97 1 02 1 07 112 1.13 1.30 1.35 1 .4 0 1 27 154 162 170 85 1 00 1 05 110 1 . 00 1 . 23 1.28 1 . 33 119 152 1 60 1 69 84 103 1 08 l l3 1.14 1.20 149 1 58 105 1.22 1.36 1.40 1.44 1.48 1.53 122 1 44 151 1 59 1 67 175 74 87 92 96 101 106 1.15 1 . 30 1 . 34 1 .3R 77 91 95 1 00 105 110 1 . 07 1 . 23 1 . 28 1.32 1.37 1 .4 2 119 143 151 158 1 66 1 75 80 94 99 1 04 1 08 114 0.96 1 . 16 1 . 20 1 . 26 1 .31 114 142 149 158 166 81 98 102 107 112 1 . 07 1 .13 1 . 19 1 39 148 157 100 1 05 110 1 . 43 1 . 4R 121 144 151 159 167 176 1.15 1 . 27 1.31 1.35 1 . 39 1.44 110 1 30 137 1 44 151 159 67 79 83 87 91 96 1 . 08 1 .21 1 . 25 1 . 29 1 . 34 1 . 38 110 1 30 1 37 1 44 151 1 59 71 83 87 91 95 100 1 . 00 1 . 14 1.18 1.23 1.28 1 . 33 110 1 29 1 36 144 151 159 75 86 90 95 99 1 04 0.92 1 . 07 1.12 1.17 1.21 1 .26 1 10 1 29 136 143 1 51 1 59 79 90 94 99 1 03 1 08 1 . 00 1 . 05 1 .10 1.15 1 . 20 1 29 1 36 143 151 159 94 98 102 107 112 ill NOTE: Underlined values, though beyond recommended limits (see 4 . 2 . 2 . 4 ) , are given to assist in interpolation of the maximum limit. % loss of li fe is in addition to normal loss of life. 0 *Actual water temperature should be 5 °c lower than the ambient temperatures shown above (see 3.5) , and must be above zero e . Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. III 0 t<:! ::!l ""' Z 0 ""' Z 0 ::0 ...... 00 t<:! ("J 01 > :" Z 10 00 1<> ""' , ...... ""' IO tJi co t<:! >-' t<:! ('J > "' Z Table 3(u) Capability Table for Normal and Moderate Sacrifice of Life 65 ° C Rise, Forced-Oil-Cooled (Non-Directed Flow - FOA, FOW * , and OA/FOA/FOA) Transformers Equivalent Load Before Peak Load 100% of Maximum Nameplate Rating :--' 00 <Ll ""' "" -;:; � � oo tz:! = ..... Ambient °c 0 Hours of Pea k Load % Peak of Per Loss 2 00 2 4 8 24 1.75 1 . 96 Load Hot- ( C) Unit ) 1 57 183 71 81 1 .6 5 1 .88 1 54 183 1.59 1 .7 6 1 .81 150 176 184 77 90 94 1.19 1.69 1.75 Normal 0.25 0.50 1 . 00 2 . 00 4 . 00 1 .4 5 1.60 1 . 65 1.70 141 1 67 175 184 78 93 98 103 Normal 0 . 25 0.50 1 . 00 2 . 00 4 .00 1.35 1 .4 8 1 .53 1.57 1 . 62 132 155 163 171 181 Normal 0.25 0.50 1 . 00 2.00 4.00 l . 29 l .4 1 l .45 1 . 49 1.54 1 . 58 Normal 1.21 Life 0.25 0.50 1 . 00 2.00 4.00 0.25 0.50 1 . 00 2 . 00 4.00 C>:l Spot Temp Peak Spot Temp (o Normal 1 �Load nit) To pOil Temp o (Per Normal ! Hot- 10 0.25 0.50 1 . 00 2.00 4 . 00 30 20 T opOil Hot- TopOil Temp ( C) Unit) 1 . 06 1 . 69 l.76 115 179 188 76 98 102 1 .66 1. 55 173 185 84 99 1 03 1 .03 1.52 1 .59 1 13 170 180 76 102 107 1 . 39 1 .4 9 164 177 134 164 172 182 83 100 105 110 1 .02 1 . 38 1 .4 4 1 .5 0 111 162 170 HlO 75 l oa 1 08 113 l .19 l . 36 1.41 1.45 1.51 1 26 1 53 162 170 179 80 96 1 01 106 1 12 - 1 .0 1 1 .29 l . 34 1 . 39 111 152 160 169 75 99 1 04 110 fl 7 91 96 101 1 06 1 .1 3 1 . 29 1 . 33 1.38 1 .43 1 .47 118 143 1 50 158 167 175 76 90 95 1 00 105 110 l . 00 l . 22 1.27 1.32 1.36 1.41 110 141 149 1 57 1 65 175 75 93 98 103 1 08 1 14 67 79 83 87 91 96 1 .07 1 .21 1 . 25 1 . 29 1 . 34 1.38 110 130 136 143 151 159 71 82 86 91 95 1 00 1 . 00 1.14 1.18 1.23 1 . 28 1.32 11 0 1 29 136 143 151 1 58 75 86 90 95 99 1 04 Load Spot ( Per T� mp 77 87 1.52 1 .79 1 49 181 81 93 147 175 184 81 94 99 1 . 38 1 .6 1 1 .67 142 173 182 1.37 1.54 1.58 1.63 1 39 1 66 174 183 - 82 97 101 1 06 1 . 27 1 . 46 1.51 1.57 75 89 94 99 105 1 .2 8 1.42 l .1 7 1.51 1.56 130 155 162 171 180 78 93 98 1 03 1 08 1 22 144 151 1 59 1 67 176 70 83 88 92 98 103 l .22 l.35 1 . 39 1.43 1.48 1 .53 121 143 151 1 58 1 67 175 110 1 :30 1 36 1 44 1 52 1 59 63 75 79 83 88 92 1.14 1 . 27 1.31 1 . 35 1.39 1 .44 1 10 130 1 37 144 151 1 59 (C ) C) 40 Hot- TopOil Temp Peak T( �mp C) Unit) ( C) Temp tCl Peak Load (P er Uni t ) Hot- Spot (C ) Peak Load (Per 50 TopOi l Spot Temp (o Temp C) Peak Load Hot- Spot TopOil r Tem ( (Per Temp ( 102 107 1 . 02 l.47 1 . 62 1 :1 1 1 74 191 95 109 115 1 05 111 1.02 1 . 33 131 1 66 95 111 ( C) Unit) 0 e ) oe ;; tz:! tz:! Q c:: ...... 1 . 28 1 . 35 157 1 67 104 110 1.01 1 .22 1 30 1 58 95 110 I:;j tzJ "%j 0 � t"' 1 . :3:3 1 . 37 1.41 1 .45 1 . 49 7:3 0 1.20 1 . 26 1.32 1 47 1 57 167 1 01 1 06 112 l . 00 1.15 1 . 23 130 1 50 163 95 106 114 > I:;j H Z Q S:: ...... Z 1 . 1 :1 1 .2 0 1 . 2.'; 1 . 30 1 :3R 1 48 1 56 165 96 101 106 112 1 . 00 1 .09 1.17 1 .2 3 130 143 154 164 95 102 1 09 115 tz:! � > t"' 6 t=: H 1 .0 7 1.12 1 . 16 1 .21 1 . 26 1 29 1 36 143 1 50 158 90 94 98 103 108 NOTE: U nderli n ed values, though beyond recommended limits (see 4 . 2 . 2 . 4 ), are given to assis t in interpolation of the maximum limit. % loss of life is in addition to normal loss of life. * Actual w�ter temperature should be 5 ° c lo we than the ambient temperatures shown above (see 3.5), and must be above zero DC. r Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. 1.05 1 . 09 1.15 1 . 20 136 143 151 1 58 98 1 02 107 112 S:: S:: tz:! � 00 tz:! I:;j '"C 0 :;; tzJ � TRANSFORMERS UP TO 1 00 M V A WITH 55 ° C OR 65 °c AVERAGE WINDING RISE in oil rise, time is required for a transformer to reach a stable temperature following any change in load. Therefore, higher peak loads may be carried for short durations . This is reflected in the Loading Tables and the basic equations in 6.7.3. If the transformer characteristics are not accurately known, a maximum top-oil te mper­ ature derived from Fig 4 may be used as an approximate guide. Loading from Fig 4 is based on a difference of 20 ° C between the hottest-spot temperature and top-oil te mper­ ature at rated load for self-cooled transformers, 25 ° c for forced-air-cooled transformers ( 133% and under), and 28 ° C for forced-oil-cooled transformers. 5 . 1 . 2 . 2 Continuous Loading on Basis of Average Winding Test Temperature R ise . For each ° c in excess of 5° that the average winding test temperature rise is below 55 ° C the transformer load may be increased above rated load by the percentage given in Table 1 . A 5 ° margin is taken to provide a tolerance in the measurement of temperature rise. The load­ ability thus obtained is that which the trans­ former can carry at 55 ° C rise. Since this may increase the loading beyond that contemplated by the designer, the limitations given in 3 .1 should be checked before taking full advantage of this increased loadability. Some transformers are designed to have the differences between the hottest-spot and aver­ age conductor temperatures greater than the 10 ° C allowance. This will result in an average­ winding temperature rise of less than 55 °C, but the hottest-spot winding temperature rise may be at the limiting value of 65 D C. Such transformers should not be loaded above their rating as outlined in this section. The manu­ facturer should be consulted for information on the hottest-spot allowances used for these designs. This condition may exist in trans­ formers with large differences (greater than 20 ° C) between top- and bottom-oil temper­ atures and may be checked approximately by measuring the top and bottom radiator temper­ atures . Whenever possible, data on hottest-spot and oil temperatures obtained from factory temperature tests sh ould be used in calculating transformer loadability or when calculating temperatures for loads above rating. 5.1 . 2.3 Loading on Basis of Short-Time Loads above Rating. Transformers may be operated above 95 ° C hottest-spot temperature 5 . Transformers Specified to have an Average Winding Rise of Not More Than 55 °C and Hottest-Spot Winding Rise of Not More Than 65 ° c 5.1 Basi c Loading for Normal Life Expectancy 5 .1.1 Basic Conditions (1) The basic loading of a transformer for normal life expectancy is continuous loading at rated output when operated under normal service conditions as indicated in 2.1.1 ( 1 ) , 2.1 . 1 (2), 2.1.1 (3) o f ANSI/IEEE C5 7.1 2.00-1979 [ 3] . It is assumed that opera­ tion under these conditions is equivalent to operation in a continuous ambient temperature of 30 ° C for cooling air or 25 ° C for cooling water. Normal life expectancy will result from operating with a continuous hottest-spot tem­ perature of 95 ° C (or equivalent variable tem­ perature with 105 ° C maximum) in any 24 h period. (2) The hottest-spot winding temperature determines loss of life due to loading. This temperature cannot be directly measured on commercial designs because of the voltage hazard when placing a temperature detector at the proper location. The hottest-spot allow­ ances are based on tests of laboratory models. (3) The hottest-spot temperature at rated load is usually taken as the sum of the average winding temperature and a 1 0 ° C allowances for the hottest spot. For mineral-oil-immersed transformers operating continuously under the foregoing conditions with normal life expect­ ancy, this temperature has been assumed to be a m aximum of 95 ° C . 5 . 1 . 2 Loading for Normal Life Expectancy under Spec ified C onditi ons 5 . 1 . 2. 1 Loading by Oil Temperature. Oil temperature alone should not be used as a guide for loading transformers. The hottest­ spot to top-oil gradient at full load should be determined from factory tests using Eq 8 or, lacking data, a value should be assumed. The full-load h ottest-spot to top -oil gradient should be corrected to that for the actual load carried using Eq 7 or Fig 9. This gradient subtracted from 95 ° C will give the maximum permissible oil temperature for normal life expectancy. It should be recognized that, due to thermal lag 5 If cooler inlet and outlet temperatures are available, better e stimate of the h o t test ·spot temperature is poss i ble by making an adjustment in the 1 0 0 C allow· ance. Consult with the manufacturer. a ANSI/IEEE C57.92·1981 39 Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE C57.92·1981 2.0 IEEE GUIDE FOR LOADING MINERAL·OIL·IMMERSED POWER �"" � � � �'\. � � � � '\\ I�0� . A SELF COOLED B C 1.6 '" a 0 ..J >Z ::> c:: LU <l. 1.6 1 .4 1 2 1 .0 FORCED AIR FORCE D OIL "'- r---.., I r"\. b... '" o 10 20 30 50 40 TOp · O IL TEMP ·C �1\ 60 70 80 90 F ig 4 Approximate Continuous Loading for Nonnal Life Expectancy° 5 5 C Rise Transformers for short periods provided they are operated for much longer periods at temperatures below 95 ° C. This is due to the fact that thermal aging is a cumulative process and thus permits loads above the rating to be safely carried under many conditions without encroaching upon the normal life expectancy of the trans· former. Suggested loadings for normal life expectancy are given in Tables 5(a)-5(u). For conservative use of these tables, it is suggested that the 5 ° C margin described in 3 . 5 . 1 be used in determining the ambient temperature. 5.1 .2.4 Loading by Hottest-spot Temper­ ature Indicator. Hottest-spot temperature de· vices are supplied, when specified, which indi­ cate a simulated hottest-spot temperature. These devices may be used as a guide to limit loads. Thermal relays, when supplied, indicate tem­ peratures reached in the windings. These relays are calibrated for use with specific transformers and simulate the hottest-spot temperature by taking into account preceding loading, existing load and ambient temperature. Higher loads are permitted for short periods than for long periods of time because of the transformer's time-constant. 5.1 .2.5 Basis for Normal Loss of Life Loading in Tables 5(a)-5(u). The transformer capabilities for normal loss of life in Tables 5(a)-5(u) are based on operation at temper­ atures that result in aging equivalent to that for continuous operation at 9 5°C hottest-spot temperature as determined from Fig 1 and the hottest-spot temperature profile resulting from the converted load cycle and ambient condi­ tions during a 24 h period . The 95 ° C hottest­ spot temperature is based on the hottest-spot rise of 6 5 ° C plus the standard ambient temper­ ature of 30 DC. At 95 ° C insulation temper­ ature, Fig 1 indicates the life would be 6.5 1 04 hours or over seven years. Actually a transformer operating outdoors at rated ca­ pacity would have a much longer life because the annual average ambient air temperature in most locations in the US does not exceed ° 20 C by more than a few degrees. At 85 ° c ° (20 C ambient temperature plus 6 5 ° C hot­ test-spot rise), Fig 1 indicates the life would be 2 105 hours or over 22 years. If the loading over weekends is lighter, as is normally the case, the total life could extend to over 30 years. In areas where the annual mean ambient • . 40 Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. TRANSFORMERS UP TO 100 MVA WITH 55 °C OR 65 ° c AVERAGE WINDING RISE ANSI/IEEE C57.92·1981 2.0 �----+-----+---4---��---r�---+�--� 0.5 1------+-----+---____+-----�--_+ 0. 3 1------+---+--I---j,I"'--,4 0.2 1------+---..Jt---+--1 0.1 �----+-�--+-�--�--��____���--_+----� 0 .05 L-__-L�__�J_�__�__-L_L__L__L____�____� 130 1 20 110 100 90 HOTTEST�SPOT TEMPERATURE IN ·C 140 150 *Expressed as percent loss of life for one occurrence of specified ti me duration for operation at temperature indicated. Hottest-Spot Temperature in Degrees Maximum Loss of Life (%) Duration Hours ! 2 1 2 4 8 24 0.1 0.25 0.50 1.00 2.00 4.00 141 134 127 120 113 104 151 143 1 36 1 29 1 22 112 151 143 136 129 118 151 143 1 36 1 25 151 143 1 32 ill 139 Fig 5 Maximum Percent Loss of Life - 55 °c Rise Transformers temperature exceeds 25 ° C the capability values in the tables should be reduced 1 . 5% for every degree the mean annual temperature exceeds 20 ° C . (See 3.1 .2 .5 for explanation). The method used to calculate Tables 5(a)5(u) is given in Section 7. 5.2 Short-Time Loading with Moderate Sacri­ or the cumulative aging effect of a number of load cycles is greater than the aging effect of continuous operation at rated load over the same period of time, the insulation deteriorates at a faster rate than normal. The rate of deterioration is a function of time and temper­ ature and is commonly expressed as a percent­ age loss of life. Charts and tables showing percent loss of life for various combinations of time and continuous temperature are given in Fig 5. fice of Life Expectancy 5.2.1 Aging of Insulation Due to Operation above 95 ° C Hottest-Spot Temperature ( 1 ) When the aging effect of one load cycle 41 Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE C57.92-19S1 IEEE GUIDE FOR LOADING MINERAL-OIL·IMMERSED POWER ( 2) It should be clearly understood that, restricted air circulation caused by buildings, while the insulation aging information used is fire considered to be conservative and helpful in history estimating the relative loss of life due to loads operator; and variations in design character­ above rating an etc ; which previous may emergency loading be to not known the 4. As a guide, an 1% per year or 4% in any istics from those in Table under various conditions, this information can only be walls, average loss of life of indicator of trans­ former insulation life. Deterioration of insula­ one emergency operation is considered reason­ tion is generally characterized by a reduction in able by some users. both 5 . 2. 2 Methods for Determining Loads above mechanical and dielectric strength, but these characteristics m ay not necessarily Rating with Some Sacrifice of Life Expectancy be directly related. In some cases, insulation in a 5.2 . 2. 1 Transformers with Known Specific charred condition will have sufficient strength Characteristics. If the specific characteristics of to withstand normal operating electrical and a transformer are known and maximum recom­ mechanical stresses. A transformer having insu­ mended capability is required , the user may lation in this condition may continue in service calculate the oil-rise and hottest-spot temper­ for many months or even years if undisturbed. ature using either the graphic solution illus­ On the other hand, any unusual m ovement of trated in Section 6, or the basic formulas in the conductors, caused by 6 . 7 . With this data, the user may determine the of the conductors due to heating allowable load for his conditions by taking into expansion such as may be resulting from a h eavy load or to large electro­ account magnetic forces resulting from short circuit, number of such loads during the life of the may disturb the weakened insulation such that transformer, and the approximate percentage tum-to-tum or layer-to-layer failure will result. of life he is willing to sacrifice. ( 3 ) The uncertainty of service the ambient temperature, probable 5.2.2.2 Transformers with Unknown Spec­ conditions and wide range in ratings covered are reasons ific why this loading guide is made conservative in When its suggested loadings. not Some of the variables Characteristics or Conservative Loads. spec ific transformer characteristics are known or when conservative operation are : wide differences in ambient temperature above rating is satisfactory, refer to the Capa­ between bility Tables , Tables 5(a)-5( u), for tabulations localities ; differences in elevation ; Table 4 5 5°C Rise Transformers - Assumed Characteristics at Rated Load OA or OW Hottest-spot conductor temperature rise (above ambient) °c Top·oil temperature rise (above amb ie nt) ° c Top-oil time constant, (h) Hottest-spot conductor time constant, ( h ) of load to iron losses *m (winding exponent) *n (oil exponent) Ratio FA 1 3 3% or Less FA** over 133% Non·Directed FOA or FOW Directe d FOA or FOW 65 65 65 65 65 45 3.0 40 37 1.25 37 1.25 37 1 .25 0.08 5.0 O.OS 5.0 0.8 1.0 0.08 5.0 1 .0 1 .0 O.OS 3.0 0.8 0.8 2.0 0.08 3.5 0.8 0.9 O.S 0.9 *m is the exponential power of winding loss versus winding temperature rise. *n is the exponential power of total loss versus top-oil temperature rise. The indicated values of m and n are approximate, particularly in the more complicated designs, and are subject to further study . * *Some OA/F A/F A designs follow more closely the values for FA (133% or less). 42 Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE C57.92-1981 TRANSFORMERS UP TO 1 00 MVA WITH 55 ° C OR 6 5 ° c AVERAGE WINDING RISE data shown in Fig 1, the assumed transformer characteristics from Table 4 and the calculated hottest-spot temperature profile for the daily load cycle and ambient temperature condition that exists during a 24 h period_ The loss of life values shown in Tables 5(a)-5(u) are in addi­ tion to the normal loss of life of 0.0369% per 24 h which would result from continuous operation at rated load in a constant 30 °C ambient. of permitted loads of various durations follow­ ing explicit preload conditions. 5 _2.2.3 Assumed Characteristics for Trans­ formers which Allow the Loadings in Tables 5(a)-5(u). Transformers vary widely in the characteristics which affect their short-time capabilities. Any general guide which applies to all transformers of a given class must be based on characteristics which give conservative re­ sults. The characteristics shown in Table 4 are considered typical of a p ower transformer and are for general use. Index for Table 5 55 ° c Rise Transformers 5.2.2.4 Temperature and Load Limitations. The following are recommended individually limiting temperatures and loads and are used in Tables 5(a)-5(u). (1) Maximum top-oil 1 00 ° C temperature ( 2 ) Maximum hottest-spot 1 50 °C conductor temperature (3) Maximum short-time loading 2 . rating 5.2.2.5 Load Cycles. Transformers usually operate on a load cycle which repeats each 24 h. This load cycle may be constant or it may have one or more peaks during the 24 h period. The actual load cycle may be converted to a two-step cycle by the method given in 6 .6 . Where actual average loads before the peak load differ from those in the tabulations, sufficient accuracy can be obtained by inter­ polation. ( A Tabulation of Loads for Normal and Moderate Loss of Life) Type of Cooling (a) (a) (b) (b) (c) (c) (d) (d) (e) ( f) (g) (h) Forced-ail-cooled, Directed flow, (FOA, FOW, OA/FOA/FOA * * ) (i ) (j ) (k ) (I) Forced·air·cooled * * (OA/FA/FA) (m ) (n) (p) (q) Forced·oil·cooled, Non·directed flow, (FOA, FOW, OA/FOA/FOA * * ) (r) (s ) (t) (u ) Self·cooled (OA) Water-cooled (OW) Forced-air·cooled* (OA/FA) 5.2.2.6 Basis for Moderate Sacrifice of Life in Tables 5(ar-5 (u). Load values in Tables Following initial load of: 50% 70% 90% 100% * Ratings 1 33% or less of self-cooled rating **Ratings greater than 1 3 3% of self-cooled rating 5(a)-5(u) are based on the life expectancy 43 Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. 0> O1 Z :-' 00 <L) ..... "" -;:. Table 5(a) Capability Table for Normal and Moderate Sacrifice of Life 5 5 ° C Rise, Self-Cooled (OA) and Water-Cooled* (OW) Transformers Equivalent Load Before Peak Load 50% of Nameplate Rating � � oo t"l = ..... Ambient °c Hours of Peak Load 1 2 1 � % 2 Hot· Spot Tsmp To r Oi T� mp Peak Load ( Per Unit ) Hot· Spot Ts mp To r Oi T�mp Peak Load ( Pe r Unit ) Hot· Spot Temp Top· Oil Temp Hot· Spot Tgmp Top· Oil Temp tC) 98 38 2.00 1 08 48 2.00 118 58 2.00 1 28 68 1 .97 2.00 1 36 1 38 77 78 1.75 2.00 1 34 14B 85 88 Normal 2.00 110 49 2.00 120 59 2.00 130 69 1 .8B 2.00 132 140 77 79 1.70 2.00 1 30 1 50 83 89 1.50 1 .9 1 127 153 89 97 Peak Load J Per nit) Hot· Spot T!! mp ( C) Top· Oil Temp t C) Peak Load J Per nit) (oC) t c) (Per Unit ) ( C) ( C) ( C) ( C) 0.25 0.50 1 .00 2 . 00 4 . 00 0 . 25 0.50 1 . 00 2.00 4 . 00 0.25 0.50 1 . 00 2.00 4 . 00 0.25 0.50 1 . 00 2.00 4 . 00 0.25 0.50 LOO 2.00 4 . 00 (C) ( C) (0C) tij t"l t"l 2 . 00 128 67 0.25 0.50 1 . 00 2.00 4 . 00 Normal 24 Peak Load 2.00 Life Normal 8 TopOil Temp Normal Normal 4 Hot· Spot Temp 50 40 30 Peak Load (Per Unit) Loss of Normal � 20 10 0 1 .8 9 2.00 1 28 1 38 73 77 1.76 2.00 1 27 148 78 87 1 .6 2 1.91 1.98 1 26 1 50 156 83 94 97 1 .45 1 . 77 1 .86 1 24 148 1 56 87 98 1 02 1 . 27 1.63 1.38 1 .6 3 1 .7 0 119 142 149 86 98 1.23 1 .5 0 117 140 89 1 02 - 1 .0 6 1.38 121 147 92 103 0 c:: ..... t:l t"l '"%j 0 ::>:I t""' 74 86 89 1.73 1 .9 5 2.00 122 144 150 1.53 1.72 1 .7 8 1.84 1.91 113 134 141 148 155 73 86 90 95 99 1.43 1.63 1.69 1.75 1.82 113 133 140 1 47 155 77 90 94 98 1 03 1.31 1 .5 2 1 .59 1 .66 111 1 32 1 39 1 46 BO 93 97 1 02 1 . 20 1 .4 2 1 .4 5 110 132 138 B4 97 100 1 .06 1 .3 0 1.35 1 .5 3 1 .5 9 L64 1.70 1 .7 7 98 117 123 129 1 36 144 65 77 81 85 89 94 1.25 1.43 1.49 1.55 1.61 1.68 98 116 1 22 128 1 35 143 69 81 84 88 93 98 1 .l 4 1 .3 4 1 . 39 1 . 45 1.52 1 .5 9 97 116 1 22 1 28 136 143 73 84 88 92 97 101 1.02 1 .23 1 . 29 1 .36 1.43 97 115 121 1 28 1 36 76 88 91 96 100 0.89 1.12 1.19 1 . 26 1.33 1.63 1 .84 1.91 122 143 151 78 90 94 1 .9 0 1 .73 1 .8 1 1 20 142 1 50 82 94 98 � 114 139 92 106 0 > t:l Z 0 s:: ...... 1 09 130 87 1 00 0.91 1.19 106 1 29 89 1 03 - Z t%J ::Ii > t""' " � 96 115 122 1 28 135 80 91 95 99 1 04 - NOTE: Underlined values, though beyond recommended limits (see 5 .2 .2 .4 ) , are given to assist in interpolation of the maximum limit. % loss of life is in addition to normal loss of life. • Actual water temperature should be 5 °c lower than the ambient temperatures shown above (see 3 . 5 ), and must be above zero °C. Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. 0.75 1 .00 1 .07 1.15 96 115 121 1 28 83 95 99 103 §: s:: t%J ::Ii 00 t%J t:l '"C 0 :;: t%J ::Ii t-3 ?:I > Z 00 '7J 0 ?:I Table 5(b) Capability Table for Normal and Moderate Sacrifice of Life 5 5 ° C Rise, Self-Cooled (OA) and Water-Cooled* (OW) Transformers Equivalent Load Before Peak Load 70% of Nameplate Rating = Ambient 0 Hours of Peak Load o/c Loss of Life Normal Peak Load (Per Unit) 2 . 00 Hot- Spot Temp C C) 104 Hot Load Spot Temp (Per Tem p (DC) Unit) (0C) Top- Oil 44 Peak 2 . 00 0.25 0 . 50 1 .00 2.00 4.00 ! 2 Normal 2.00 115 54 2.00 0.25 0.50 1 . 00 2.00 4.00 1 Normal ..,. CJ1 0.25 0.50 1 . 00 2.00 4 . 00 2 Normal 0.25 0.50 1 . 00 2 . 00 4 . 00 4 N or mal 0.25 0.5 0 1 . 00 2. 0 0 4 . 00 8 Normal 0.25 0.50 1.00 2.00 4.00 24 114 1 25 E::: °c TopOil Te mp Peak 54 2 . 00 ee) 64 Load (Per Unit) 1 .9 5 2 . 00 Hot- Top· Peak Hot Oil Load Spot Temp Temp (Per Temp Unit) c" C ) c"C) tC) Spot 1 24 132 135 40 30 20 10 64 73 74 2.00 1.78 2.00 1 34 1 30 145 Top· Oil Temp Peak Load (Per (o C) Unit) 74 1.81 2 . 00 79 84 1 .56 1 .9 7 l>:l ?:I 00 50 Spot Temp (C) Top· Oil Temp Peak L ad (Per o Ho Spot Temp Temp 133 144 81 84 1.31 2 . 00 117 154 86 94 Hot- 126 1 53 (DC) 85 94 Unit ) 1.13 1 . 80 t (C) 111 151 TopOil (o C ) 87 100 e: "tj t-3 0 >-' 0 0 E::: -< > � t-3 � 01 01 ° 0 0 ?:I 1.95 2.00 1.70 1.92 1 .9 8 128 131 121 143 150 69 71 74 86 90 1.84 2.00 1 .59 1.81 1.89 127 141 1 20 142 150 74 81 78 90 95 1 .70 1 .9 7 2 . 00 1.47 1 . 70 1 .78 1 .86 126 1 49 151 1 19 141 149 157 79 90 91 82 94 98 103 1 .1, 4 1 .8 4 1 .9 4 1 .33 1.59 1 .6 7 124 148 156 117 140 1 48 84 95 98 85 98 1 02 1 . 34 1 .7 0 1 .16 1 .4 6 120 146 113 138 88 1 00 88 102 0.97 1. 53 0.88 1.31 1 06 143 103 135 87 1 04 87 104 '" 01 ° 0 > -< l>:l ?:I > Q l>:l � ...... Z t:J 1 .5 2 1.71 1 .77 1.83 1 .9 0 112 133 139 147 155 73 86 90 94 99 1.41 1.61 1 .35 1.52 1 .58 1 . 64 1.70 1.76 98 116 1 22 1 29 1 35 143 65 77 80 85 89 93 1. 24 1.43 1.49 1.55 1.61 1 . 67 1.67 1. 7 4 1 . 80 1 11 132 1 39 147 1 54 77 89 93 98 1 02 97 116 68 80 122 84 143 88 93 97 1 28 135 1 . 30 110 1 . 58 1 .64 131 1 38 1 45 1 .51 1.13 1.33 1.39 1.45 1.52 1 . 59 97 115 1 22 128 1 35 143 80 92 97 101 1.17 1.41 1 .47 72 84 88 92 96 101 1.02 1.23 1 .29 1 . 36 1.42 1 09 131 137 96 115 121 1 28 135 83 96 100 1 .0 2 1 . 29 1 .36 76 88 91 96 1 00 0.88 1 .1 2 1.18 1.25 1 .3 2 105 129 1 36 85 99 1 03 0.78 1 .1 6 96 79 91 95 99 103 0.73 0.99 1.06 1.14 115 121 128 1 34 NOTE: % loss Underlined values, t h o u gh beyond recommended limits (see 5 .2 .2.4), are given to assis t i n interpolation of the maximum limit. of life is in addition to normal loss of life. *Actual water temperature should be 5 D C lower than the ambient temperatures shown above (see 3 . 5 ) , and must be above zero DC. Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. 98 1 27 95 114 120 127 84 1 02 Z Q ::0 ...... r:n l>:l 83 95 98 1 03 0 01 > :-' Z <0 00 ",, - �� <o l>:l oo l>:l >-' l>:l C"l > Ol Z :-" 00 <.0 ..... l>:) "j::; Table 5 (c) Capability Table for Normal and Moderate Sacrifice of Life 55 D C Rise, Self-Cooled (OA) and Water-Cooled* (OW) Transformers Equivalent Load Before Peak Load 90% of Nameplate Rating "' [i5 � t>:J >-' = Ambient ° c " Hours of Peak Load ! 2 1 >l:>m % Loss of Life Normal 2_00 24 not- jpot (�C\P l12 TopOil Temp ,oC) 51 Peak Load ( Pe r Unit) 2.00 1I 0 t - Spot Temp te) 1 22 TopOil Temp tC ) 61 Hot- Top- t C) Temp ee) Peak Load (Per Un it ) Spot Temp 2.00 132 Oil 71 0. 25 0.50 1 . 00 2.00 4.00 1 21 61 2.00 131 71 0.25 0.50 1 . 00 2.00 4.00 0.25 0.50 1 .00 2.00 4.00 1 .8 9 2.00 1 26 1 36 71 75 1 25 1 46 76 85 40 Hot- Hot- Spot Temp e Cl TopOil Temp (oC) 1 . 80 2.00 1 30 142 79 81 122 1.81 2.00 1 28 141 76 81 1.56 2_00 1 51 81 91 1 . 59 1 .9 1 1 .98 122 148 155 80 92 95 1 . 38 1.76 1 .8 6 l16 145 1 54 83 96 100 Peak Load (Per Unit) Spot Temp eC) 50 TopOil Te mp ( C) Peak Load (Per Unit) Hot- Spot Te m p (D C ) Top- Oil Temp tC) 2.00 1 52 91 1.75 1 . 98 147 161 98 101 1 .83 1.95 1 49 1 58 97 99 1 . 53 140 101 1 . 59 142 1 00 1 . 34 1 34 1 02 72 1.41 1.66 1.74 1 .82 116 1 39 147 1 55 81 94 99 103 1.22 1.54 1 .6 3 110 138 1 46 83 98 1 02 0.63 1 . 39 81 1 34 1 00 1 .19 128 101 1.92 78 91 95 99 73 85 90 94 99 1.39 1 . 59 1.66 1.73 1 .80 110 1 31 1 38 1 45 1 54 76 89 93 98 102 1 . 27 1 . 49 1.55 1 .63 1 08 1 30 1 37 144 79 92 96 101 1.11 1 . 38 1 .45 1 04 1 28 136 80 95 100 0.81 1 . 25 1 . 33 91 126 134 76 98 102 1 . 08 1.19 121 131 98 104 65 77 80 84 89 9 :1 1 . 24 1 .43 1 . 48 1.55 1 .6 1 1 . 67 97 1 16 1 22 1 25 1 35 143 68 80 84 88 93 97 1.13 1 . 33 1 . 39 1 .45 1.52 1 . 58 119 142 149 1 54 74 87 91 93 U;O 0.25 0.50 1 . 00 2.00 4.00 1 .7 0 1 .7 6 1 . 82 1 . 88 l11 132 1 39 146 154 Normal 1 . 3·1 1 . 52 1 . 58 1.63 1 .70 1.76 97 116 122 1 28 135 143 0.25 0. 5 0 1 . 00 2.00 4 . 00 1.75 2.00 Peak Load (Per Unit) 30 118 141 148 1 56 1 .6 6 1 . 89 1 .95 2.00 0.25 0.50 1 . 00 2.00 4 . 00 Normal 8 'Jnitl 2.00 Normal 4 , Pe r Normal Normal 2 i'eak f--load 20 10 1 .55 1.78 1 .H 5 ..... t>:J t>:J t>:J Cl e: ..... t::::l t>:J � 0 � t'" 0 > t::::l . .... Z Cl E: ...... Z t>:J � > t'" " ..... t'" 96 115 122 128 135 142 72 84 88 92 96 1 00 1 .0 1 1 .22 1 . 28 1.35 1 .4 2 96 115 1 21 128 135 75 87 91 95 100 0.88 1.11 1.17 1 .25 1.32 95 1 14 1 20 1 28 134 79 91 94 99 1 03 NOTE: Underlined values, though beyond re co m men ded limits (see 5 .2 .2 .4 ), are given to assist in interpolation of the maximum limit. % loss of life is in addition to normal loss of life. *Actual water temperature should be 5 °c lower than the ambient temperatures shown above (see 3 . 5 ) , and must be above zero DC. Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. 0.72 0.98 1.05 1.13 94 1 14 1 20 1 27 82 94 98 102 - �E: t>:J � rll t>:J t::::l "0 � t>:J � 0-,3 ::0 > Z 00 "'1 0 ::0 == Table 5(d) Capability Table for Normal and Moderate Sacrifice of Life 55 ° C Rise, Self-Cooled (OA) and Water-Cooled* (OW) Transformers Equivalent Load Before Peak Load 100% of Nameplate Rating = Hours of Peak Load % Loss of Life Normal 1 2 Pea k Load Per nit) HotSpot Ts mp ( C) 2 . 00 116 J TopOil Temp (oC) Peak Load (Per Unit) HotSpot Temp (0C) 55 2.00 126 2.00 125 64 0_25 0 . 50 1.00 2 . 00 4.00 � 2 4 1.92 2.00 1 29 1 35 72 74 HotSpot T� mp ( C) 1 . 92 2.00 1 31 1 36 TopOil Temp (0C) 74 75 Peak Load (Per Unit) HotSpot Temp l . 00 2.00 95 146 t e) t:':! 40 To r " Oi T� mp ( C) 75 85 Peak Load (Per Unit) HotSpot Temp tc ) 1 .91 150 50 TopOil Temp (C) Peak Load (Per Unit) HotSpot Tl5mp TopOil Tem p 1. 72 1 49 102 ( C) tC) 94 124 145 78 84 95 149 1 55 75 92 94 1 . 69 1 . 86 143 155 97 101 - 1 . 50 142 103 72 78 1 .7 0 2.00 1 23 148 77 88 1 . 50 l . 86 1 .95 118 146 154 80 92 96 1 . 00 1 . 69 1 . 80 95 142 151 75 96 100 1.47 1 . 63 1 36 147 99 1 04 0.50 1.31 92 135 85 104 Normal 1 . 64 1.87 1 . 94 2 . 00 118 141 1 49 155 74 87 91 95 1.51 1.76 1 .8 3 1.91 1 16 1 40 147 1 55 77 91 95 99 1 . 34 1 . 63 1 .72 1 . 80 112 1 38 146 154 80 94 99 1 0 3 - 1 . 00 1 . 50 1 . 59 95 135 143 75 97 101 1 . 31 1 . 44 1 29 140 98 1 04 0.81 1 . 10 103 1 29 88 103 1 .48 1 . 69 1 . 75 1.81 1 . 83 110 131 1 38 146 153 72 85 90 94 98 1.37 1.59 1 .6 5 1.72 1.78 108 130 137 145 1 52 75 88 93 97 1 02 1.23 1 .48 1 . 55 1 .62 104 1 29 136 144 77 91 96 100 1 . 00 1 . 36 1.43 1.51 95 127 1 34 142 75 94 99 1 03 - 1 . 34 1.52 1 . 58 1.63 1.70 1.76 97 116 122 1 28 1 35 143 65 77 80 84 89 93 1 . 23 1.42 1 .48 1.54 1.61 1 .67 96 115 122 1 28 135 1 43 68 80 84 88 93 97 1.13 1.32 1 . 38 1 .45 1 . 52 1.58 96 114 121 1 27 135 142 72 83 87 91 96 100 1 .00 9 fi 115 121 1 28 134 142 75 87 91 95 99 1 04 0.25 0.50 1.00 2 . 00 1 . 00 0.25 0.50 1 . 00 2.00 4.00 ..... 0 0 == < > ::;; ...... :r: 1 . 00 1 .92 2.00 1 25 138 0.25 0.50 1 . 00 2.00 4.00 ::0 00 e:: "tI 0-,3 0 0-,3 1.70 2 . 00 1 . 01 2.00 0.25 0.50 l . 00 2.00 4 . 00 Normal 24 65 Peak Load (Per Unit) 30 Normal Normal 8 TopOil Temp (oC) 0.25 0.50 1.00 2.00 4.00 Normal -l Ambient °e 20 10 0 01 01 ° C':l 0 ::0 O'l on ° C':l > < t:':! ::0 > 0 t:':! ::;; Z t:I 1.22 1.28 1.35 1.41 1 . 48 Z 1 . 20 1 . 30 1 22 131 95 101 0.94 1.13 110 125 0.86 1 .1 0 94 1 14 1 20 127 1 34 78 90 94 98 1 03 0.70 0.98 1 . 05 1.13 93 113 119 126 1 .17 1.24 1.31 NOTE: Underlined values, though beyond recommended limits (see 5 .2 .2 .4), are given to assist in interpolation of the maximum limit. % loss o f life is in addition to normal loss o f life. *Actual water temperature should be 5 °C lower than the ambient temperatures shown above (see 3.5), and must be above zero °e. Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. 92 101 0 ::0 00 ...... t:':! 81 94 97 1 02 C':l 01 > :-> z � oo "" ...... �� � t:':! oo t:':! .... t:':! (J � "" Z :-' 00 <1:> .... 1>:> -;::' Table 5(e) Capability Table for Normal and Moderate Sacrifice of Life 55 ° C Rise, Forced-Air-Cooled (OA/FA) Transformers Rated 133% or Less of Self-Cooled Rating Equivalent Load Before Peak Load 50% of Maximum Nameplate Rating � gj Ct> t<:I I-' = Ambient °c Hours of Peak Load I 2 1 � 00 % Loss of Life 4 24 nit) 2.00 Normal 2 . 00 2.25 0.25 0.50 1 . 00 2.00 4.00 0.25 0. 50 1 .00 2.00 4 . 00 0.25 0.50 1.00 2.00 4.00 N ormal 0.25 0 . 50 1 .00 2. 00 4.00 Normal 8 Load �Per Normal Normal 2 Peak 0 . 25 0.50 1 . 00 2.0 0 4.00 Normal 0. 2 5 0.50 1 . 00 2 . 00 4.00 1.76 1.95 Hot- Spot Tg mp ( C) TopOil Temp (oC) 114 40 1 33 1 58 57 67 1 29 151 20 10 0 67 78 Peak Load (Per Unit) 2.00 1.91 2.14 1.66 1.87 HotSpot Temp (0C) TopOil T�mp ( C) HotSpot T�mp 1 34 60 1 33 70 Unit) 1 24 50 2.00 1 34 63 73 1 .8 0 2 .04 1 57 - 1 28 151 71 83 y Peak Load (Per 1.56 1 . 77 ( C) 1 57 - 127 1 50 To Oi Temp t C) 79 76 87 30 Peak Load (Pe r Unit) Hot- Spot T�mp ( C) y 40 To Oi Tgmp �Per ( C) Peak Load nit) Hot- Spot Temp (0C) 50 TopOil T�mp ( C) Peak Load (Per Unit) Spot Temp Hot· (0C) TopOil Temp tC l 1.91 1 38 144 68 70 1 .77 2 . 00 137 154 75 80 1.61 1.94 1 36 160 82 88 1 .67 1 32 1 56 75 84 1 . 54 1 .81 131 1 55 81 90 1 . 39 1 . 69 1 28 153 86 96 2.00 1.93 1 . 45 1 . 68 1.74 1 26 149 1 57 80 92 96 1 . 33 1 . 57 1 . 64 124 148 155 85 96 1 00 1 .1 9 1 .46 122 147 89 101 til t<:I t<:I 0 c:: .... 0 t<:I '>j 0 ::0 t"' 1 . 55 1.73 1.78 1 .84 1 20 142 149 1 57 69 82 86 91 1 .47 1 . 65 1 .70 1 . 76 1 20 1 42 148 1 10 1 30 1 37 144 151 70 82 86 96 115 121 127 1 34 141 62 73 77 81 156 73 86 90 94 1 18 14 1 147 1 . 37 1 . 56 1 .61 1 . 68 1 56 1 .24 1 09 77 90 94 98 1 .27 1 . 47 1 . 53 1.59 1.14 1 . 33 1 . 38 1.44 1.50 1 . 01 118 1 40 147 81 94 98 1.16 1 . 37 1 . 44 116 139 146 85 97 .!.Ql 1 . 03 1 . 27 114 1 38 88 101 0 � 0 .... Z 0 s:: 1 54 - 102 1 09 77 89 93 98 102 1 .0 4 1 . 23 1.30 1 08 1 28 135 142 81 93 97 102 0 .91 1.13 1 . 20 106 1 28 134 84 97 101 70 81 84 88 93 97 0.90 95 114 1 20 1 26 1 33 141 74 85 88 92 96 101 0.78 0.99 1 .05 1 .1 2 1 .1 9 95 114 1 20 1 26 1 34 78 89 93 96 1 01 .... Z t<:I 1.42 1 . 58 1 . 63 1 . 68 1 .73 110 1 30 137 144 151 87 91 1.33 1 . 50 1.55 1 .61 1 . 66 1.30 1.45 96 114 121 1 27 1 34 141 58 69 73 77 81 85 1.21 1.37 1 .42 1.47 1.52 1.57 1.50 1 .55 1 . 60 1 .65 66 78 82 91 95 85 89 1 .5 9 151 74 86 90 94 99 1.12 1 . 28 1 . 33 1 .3 9 1 .44 96 1 14 120 1 27 1 34 141 66 77 81 85 89 93 1.41 1.47 1 .52 1 .50 1 29 1 36 143 1.19 1 . 24 1 .3 0 1.36 1 .4 2 1 29 1 35 143 1 50 95 114 1 20 126 133 141 1 . 36 1 . 09 1.15 1 .21 1.27 1 . 34 NOTE: Underlined values, though beyond recommended limits (see 5 .2 .2 .4 ) , are given to assist in interpolation of the maximum limit. % loss of life is in addition to normal loss of life. Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. � � t"' 0 8 ,:.. s:: s:: t<:I ::0 rn t<:I 0 "d 0 � t<:I ::0 >-3 Table 5 (f) Capability Table for Normal and Moderate Sacrifice of Life 55 D C Rise, Forced-Air-Cooled (OAjFA) Transformers Rated 133% or Less of Self-Cooled Rating Equivalent Load Before Peak Load 70% of Maximum Nameplate Rating ;Ii > Z 00 »J 0 ;Ii is: = Ambient 10 0 % Hours of Loss Load Life Peak of Normal 0.25 0.50 1 . 00 2 . 00 4 . 00 .,.. � 2 4 8 24 Peak Load JPer nit ) 2.00 Hot- Spot T!imp ( C) 1 20 TopOil Temp (0 C) 45 Peak Load Per Unit) ( 2.00 HotSpot Temp t C) 1 30 °c 30 20 TopOil Temp t C) 55 Peak Load (Per Unit) 1 . 96 2.24 HotSpot T!imp ( C) 1 38 162 TopOil Temp tc) 64 71 Peak Load (Per HotSpot Temp 1 .B1 2.12 136 1 61 Unit) t C) 40 TopOil Temp tC ) 71 78 Peak Load JPer nit) 1 . 65 1 .99 HotSpot Temp (o C ) 1 34 160 t:rl 50 TopOil Temp (0 C ) 78 85 Peak nit) JPer Load 1 . 38 1 . 84 HotSpot Temp (o C ) 126 158 TopOil Tem p tC) 84 92 ;Ii 00 e ." >-3 0 ..... 0 0 is: <: > ::,:j 1.85 2.09 132 155 1 30 1 54 1.45 1.75 Normal 0.25 0.50 1 . 00 2.00 4.00 1 .97 2.19 Normal 0.25 0.50 1 .00 2.00 4.00 1 .7 3 1 .93 1 28 151 6B 79 1.63 1.84 1 27 1 50 72 84 1.53 1 .74 1.81 1 26 149 157 77 88 92 1.40 1 . 64 1 .7 0 1 24 148 155 81 93 96 1.f;:� 1 . 60 121 146 154 Normal 0.25 0.50 1 .00 2.00 4.00 1 . 54 1.71 1.77 1.82 1 20 141 148 1 56 70 82 86 90 1.45 1.63 1 . 69 1.75 1 19 1 40 1 48 1 56 73 86 90 95 1 .35 1 . 55 1 . 60 1 .67 117 1 40 147 1 55 77 90 94 98 1 .2 5 1 .4 5 1.51 1 . 57 l16 1 39 146 1 53 81 94 98 102 1.11 1 . 35 1.42 113 1 38 145 Normal 0.25 0.50 1 .00 2.00 4.00 1 .4 1 1 .57 1 . 62 1 .6 8 1 .73 1 09 1 30 1 36 144 151 66 7B 82 87 91 1.33 1 .49 1.55 1 .60 1 .66 1 09 1 29 1 36 143 151 70 82 86 90 95 1 . 23 1.41 1 .46 1.52 1 . 58 1 08 128 136 143 150 73 85 90 94 98 1.13 1.32 1 . 38 1.43 1 . 50 1 07 1 28 135 142 150 77 89 93 97 1 02 1 . 01 1 . 22 1 . 29 1 . 35 Normal 0.25 0 . 50 1 . 00 2.00 4.00 1.29 1.45 1.50 1 . 54 1 . 60 1 . 65 96 114 121 127 1 34 141 58 69 73 77 81 85 1 . 20 1 . 36 1.41 1.47 1 . 52 1 . 58 95 114 1 20 1 27 1 34 141 62 73 76 81 85 89 1.11 1 . 28 1.33 1 . 39 1 . 44 1 . 50 96 114 120 127 1 34 141 66 77 81 84 89 93 1 .0 1 1 .1 9 1 .25 1 . 30 1 . 36 1.42 95 114 1 20 1 27 133 141 70 B1 85 89 92 97 0.90 ] .09 1.15 1 . 21 1.27 1 . 34 1 34 1 57 60 69 133 156 66 75 NOTE: Underlined values, though beyond recommended limits (see % loss of life is in addition to normal loss of life. 1.73 1 .9 B 72 81 5 . 2 .2.4), are given to 1 .60 1.87 77 86 1 .27 1 28 1 54 83 92 85 1.20 1.61 1 19 151 85 97 114 144 86 101 83 97 101 0.93 1 . 24 107 1 36 84 1 00 106 127 1 34 142 80 93 97 1 01 0.85 1.12 1.18 101 1 26 133 82 96 100 95 1 14 1 19 1 26 133 141 74 85 88 92 97 101 0.77 0.99 1 . 05 1.11 1.18 94 113 119 1 26 1 33 78 89 92 96 101 ill assist in interpolation of the maximum limit. Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. 01 01 D (":I 0 ;Ii 1 .06 1 .4 1 97 ::3 :::r:: a> 01 ° (":I > <: trl ;:tl > 0 trl ::,:j Z t!.. .... Z 0 ;:tl ...... 00 trl �> :--' Z "' 00 1.:> ...... , � ..... ...... ", trl oo trl ..... trl n> O1 Z :-J oo to "" ;:; Table 5(g) Capability Table for Normal and Moderate Sacrifice of Life 5 5 ° C Rise, Forced-Air-Cooled (OA/FA) Transformers Rated 133% or Less of Self-Cooled Rating Equivalent Load Before Peak Load 90% of Maximwn Nameplate Rating ' = Ambient °c 0 Hours of Peak Load % Loss of Life Normal 1 2 0.25 0.50 1 . 00 2 . 00 4.00 Normal 1 Ql 0 0. 25 0.50 1 . 00 2.00 4.00 Normal 2 0.25 0. 5 0 1 . 00 2.00 4.00 Normal 4 0.25 0.50 1 .0 0 2.00 4.00 Normal 8 0.25 0.50 1 . 00 2.00 4.00 Normal 24 0.25 0.50 1 .00 2 . 00 4.00 Peak Load Per nit) J Hot· Spot T!i mp ( C) Top· Oil Temp ("C) 2.00 2 . 39 -- 1 28 162 53 62 1.89 2.13 132 1 56 63 72 1.69 1.89 1.95 1 26 1 49 1 57 20 10 69 80 84 Peak Load (Per Unit) 1 .98 2.27 1.77 2.02 -- 1.58 1.79 1.86 Hot· Spot Temp (0C) Top· Oil Temp (0C) Peak Load (Per Unit) Hot· Spot T!i mp ( C) y To Oi Temp t C) Peak Load (Per Unit) 1 37 161 62 69 1.84 2.15 -- 135 161 -- 69 76 1.64 2.01 131 68 78 1.64 1.91 129 1 54 74 83 1 .4 6 1.79 155 - 1 25 148 155 73 84 88 1.46 1 . 69 1.76 122 147 1M 77 89 93 40 30 1 . 29 1.59 1.66 Hot· Spot Temp (oC) TopOil T� mp ( C) 130 1 59 -- 75 83 1 24 78 89 152 - 117 146 ill 79 93 97 Peak Load (Per Unit) Hot· Spot Temp ( 0 C) 50 Top· Oil Temp (oC) Peak Load (Per Unit) HotSpot T8mp ( C) Top· Oil Temp (oC) 1.86 157 90 1 . 62 I. 79 149 161 95 98 1 .6 4 1 .74 1 49 1 58 - 94 97 1 .4 3 1 . 58 142 154 97 102 142 151 96 1 45 1 . 54 sa t:<:! t:<:! 0 c:: 0 !Q!. 1.28 1.40 1 36 146 99 1 04 t:<:! "'l 0 � t""' 1 . 52 1 . 69 1.75 1.81 118 140 147 155 69 82 86 91 1.43 1.61 1 .66 1.72 117 139 146 1 54 73 85 90 94 1.31 1.52 1 . 58 1 . 64 114 1 38 146 154 76 89 94 98 1.1 8 1 .4 2 1.49 1 . 55 111 1 37 144 1 52 78 93 97 102 1 . 30 1 . 38 134 142 95 100 1.15 1 . 26 1 28 138 96 102 1 .4 1 1 . 57 1.62 1.67 1.72 109 1 29 135 143 1 50 66 78 82 86 91 1.31 1.48 1.54 1 . 59 1.65 1 08 128 1 35 142 1 50 69 81 85 90 94 1.21 1.40 1.46 1.51 1.57 1 . 63 1 06 128 135 142 149 1 58 72 85 89 94 98 103 1.09 1.30 1 . 36 1 .43 1.49 103 126 133 141 149 74 88 92 97 102 1.20 1 . 27 1 . 33 1 25 132 140 91 96 100 1.07 1.15 1.23 121 1 29 1 38 93 98 103 -- 1.29 1 . 45 1 . 49 1 .54 1.60 1 . 65 96 114 120 127 1 34 141 58 69 73 77 81 85 1 . 20 1.36 1.41 1.46 1.52 1.57 95 1 14 120 1 26 1 33 141 62 73 77 80 85 89 1.11 1 . 28 1.33 1 .3 8 1.44 1.50 95 114 1 20 1 26 1 33 141 66 77 80 84 89 93 1.01 LIB 1 . 24 1 . 29 1.35 1.42 95 113 1 20 1 26 1 33 140 70 B1 85 88 92 97 0 > 0 Z 0 s:: .... Z t:<:! � > t;" 0 .... t""' ,!.., s:: 1 .09 1 .1 5 1.21 1.27 1.33 113 120 1 26 133 140 B5 88 92 96 101 NOTE: Underlined values, though beyond recommended limits ( see 5.2.2 .4 ), are given to assist in interpolation of the maximum limit. % loss of life is in addition to normal loss of life. Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. t:<:! ..... t:<:! � t:<:! ..... 0.99 1.05 1.11 1.18 113 119 1 26 1 32 89 92 96 1 00 s:: t:<:! ::xl 00 t:<:! 0 '"C 0 � t:<:! � >-3 � > Z 00 "'J 0 � Table 5(h) Capability Table for Normal and Moderate Sacrifice of Life 55 C Rise, Forced-Air-Cooled (OA/F A) Transformers Rated 133% or Less of Self-Cooled Rating Equivalent Load Before Peak Load 100% of Maximum Nameplate Rating 0 = is: Ambient ° c 10 0 Hours of Peak Load % Loss of Life Normal 1 2 0.25 0.50 1 . 00 2 . 00 4.00 Normal 1 0. 25 0.50 1 . 00 2.00 4.0 0 Normal 01 I-' 2 0.25 0.50 1 . 00 2.00 4.00 Normal 4 0.25 0 .50 1 .00 2.00 4.00 Normal 8 0_25 0.50 1 .00 2.00 4_00 Normal 24 0_25 0.50 1 . 00 2 . 00 4_00 Peak Load Per J nit) 2_00 L84 2.09 HotSpot T� mp ( C) 133 131 155 20 TopOil Temp tC ) 57 64 74 Peak Load per nit) J HotSpot Temp (o C) TopOil Temp ("C) Peak Load (Per Unit ) 1.92 2.22 1 36 161 - 65 72 L73 2.08 -- 1.72 1.98 1 29 1 54 - 70 80 1 .5 5 1.86 HotS po t T� mp ( e) y To Oi Temp te) 30 Peak Load (Per Unit ) HotSpot Temp (0 C) r 40 (0C) Peak Load ( Per Unit) HotSpot Temp ("C) To Oi Temp t:r:J � 50 TopOil T� mp ( e) 132 159 -- 71 79 L06 1.94 98 ill 70 85 L72 1 50 91 124 153 74 85 1 . 06 1.72 1.82 98 149 1 59 71 90 94 1.53 1 . 67 143 1 55 94 98 Peak Load (Pe r 00 Unit) HotSpot T� mp ( C) Temp 1 . 56 1.82 149 1 68 98 103 1 .4 1 143 100 TopOil (oC ) e:: "0 >-3 0 .... 0 0 is: <: > ::e ..... >-3 ::c 01 01 0 0 0 � Q> 1 . 66 1.86 1.93 125 148 1 56 69 80 84 1 . 54 1.77 1.83 1 23 147 1 54 73 85 89 1.39 1 .66 1.73 118 146 1 53 -- 76 89 93 1 . 03 L54 1 . 62 97 143 151 - 71 93 97 1 . 38 1.49 1 36 147 95 100 1.50 1 . 68 1 .7 4 1 .80 116 139 1 46 154 69 82 86 90 1.40 1 . 59 1.65 1.71 115 1 38 145 1 53 72 85 89 94 1.27 1.50 1 . 56 1 .6 2 111 1 36 144 152 - 74 89 93 97 1.02 1.39 1.46 1 .54 96 134 142 151 70 91 96 101 - 1.25 1.34 1.43 129 139 148 93 99 1 0 4 -- 1 . 40 1 . 56 1.61 1.67 1.72 108 1 29 135 143 150 65 78 81 86 90 1 . 30 1.48 1.53 1.59 1 .64 1. 7 0 1 07 1 28 134 142 1 49 1 57 68 81 85 89 94 99 1.19 1.39 1 .4 5 1 .5 1 1.57 1.62 104 1 27 1 34 141 149 157 71 84 89 93 98 102 L01 1.29 1 .35 1 .42 1 . 48 95 125 1 32 140 148 70 87 92 96 101 1.17 1 . 25 1.32 1 . 39 122 130 1 38 146 90 95 99 1 04 l .09 1 .20 1 24 135 95 102 1.29 1.45 1.49 1.54 1.59 1.65 95 114 1 20 127 133 1 41 58 69 1.20 1.36 1.41 1.46 1.52 1.57 95 113 1 20 1 27 133 140 62 73 77 80 85 89 1.10 1 .2 7 L33 L38 L44 1.50 95 113 120 1 26 133 141 65 77 80 84 88 93 LOO 95 113 119 126 133 140 70 81 84 88 92 96 1.09 1.14 1 . 20 1.27 1.33 113 1 19 1 25 132 140 84 88 92 96 100 1 .04 L11 1.17 118 125 132 92 96 1 00 73 77 81 85 1.18 1 . 24 L30 L36 L41 01 0 1.25 1 .4 2 135 151 99 107 L16 1.30 1 29 144 98 106 Cl > <: t:r:J � > P t:r:J ::e ..... Z I;;j Z NOTE: Underlined values. though beyond recommended limits (see 5 .2 _2 .4 ) , are given to assist in interpolation of the maximum limit_ % loss of life is in addition to normal loss of life. Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. P � ..... 00 t"l 0 01 > :-" Z <0 00 t.:> .... . .... .... <o t:r:J oo t"l .... t"l 0> O1 Z :-' 00 "' .!:::' Table 5(i) Capability Table for Normal and Moderate Sacrifice of Life 55 ° C Rise, Forced-Oil-Cooled ( Directed Flow - FOA, FOW*, and OA/FOA/FOA) Transformers Equivalent Load Before Peak Load 50% of Maximum Nameplate Rating "" ...... .:.. � � trl ..... = Ambient °c Hours of Peak Load 1 1 % Loss of Life J nit) Hot· Spot Tl1mp ( C) Top· Oil Temp ( o C) Peak Load Per nit) J H o t· Spot Temp (C) Top· Oil Temp 0 ( C) Peak Load (Per Unit) Hot· Spot Tl1mp ( C) y To ' Oi Temp tC) 30 Peak Loa d (Per Uni t) H o t· Spot Tl1 mp ( C) 40 50 To rOi T� mp ( C) Peak Loa d Per nit) Hot· Spot Temp Top· Oil Temp Peak Load (Per Spot Temp Top· Oil T '6mp J (C) (oC) Uni t) Hot· ( oC) ( C) Normal 1.84 2.00 141 1 64 - 46 52 1.77 1.93 140 1 64 53 59 1 . 69 1.86 140 163 - 60 60 1 . 60 1 .7 9 1 39 163 - 67 74 1.51 1.70 138 162 75 81 1 .4 1 1 .6 3 1 38 162 82 88 Normal 1 . 67 1.82 135 1 58 57 66 1 .60 1.75 134 1 57 63 72 1.52 1 . 68 !.§l 1 34 69 78 1.44 1.61 133 1 56 75 84 1 . 35 1 . 53 132 1 55 81 89 1.26 1.45 131 15§ 86 95 0. 25 0.5 0 1 . 00 2.00 4.00 0.25 0.50 1 Peak Load Per 20 10 0 L OO Ol t-:I Normal trl 2 8 24 1.29 1 .4 5 1 . 50 1 26 1 48 155 79 89 93 1 . 21 1 . 38 1 . 63 117 138 145 73 84 88 91 1 .18 1 . 33 1 . 37 1.42 117 1 38 145 152 78 89 92 96 1.09 1 . 26 1 . 30 1 . 35 l.18 1 .3 1 1 .3 5 1 .4 0 1 .4 4 1 .4 8 107 1 27 134 141 148 156 69 79 82 86 90 94 1.10 1.24 1 . 29 1 . 33 1 . 38 1.43 108 127 134 140 148 1 56 74 84 87 91 95 99 1 .09 1 .22 1 . 27 1 . 30 1.35 1.39 96 114 1 20 126 134 141 63 72 76 79 82 86 1.01 1.15 1 . 20 1.24 1 . 29 1.33 96 114 120 126 1 33 141 67 77 80 83 87 91 128 150 158 64 74 78 1.45 1.58 1 .63 1 28 149 1 57 69 79 83 1.37 1.52 1.56 1.39 1.52 1.56 1.60 118 139 146 1 53 64 75 78 82 1.33 1 .46 1 . 50 l.54 1 18 1 39 1 46 1 53 69 79 83 87 1.25 1 . 39 1.44 1 .48 Normal 0.25 0.50 l . 00 2.00 4 . 00 1.32 1.44 1 . 48 1.52 1.56 1 . 60 108 1 28 134 141 1 49 157 68 70 73 77 81 85 1.25 l . 38 1.41 1 . 46 1.50 l.54 1 08 127 1 34 141 148 156 64 74 78 82 85 89 Normal 1.23 1.36 1 . 39 1.43 1 . 47 1.50 96 114 1 20 126 1 34 141 53 63 66 69 73 77 1.16 1 . 29 L33 1.37 1.41 1 .4 5 96 114 1 20 1 27 1 34 140 58 67 71 74 78 81 Normal 4 74 84 88 1.51 1.64 1.69 0.25 0.50 1 . 00 2 . 00 4.00 0.25 0.50 1 .00 2.00 4.00 0.25 0. 5 0 1 . 00 2.00 4.00 t;:j trl 2.00 4.00 127 149 � � 84 94 98 1.12 1 . 30 1.35 123 146 1 56 83 99 103 115 1 38 144 1 52 82 93 97 101 1 .01 1 . 18 1.23 115 1 37 143 87 98 101 1 . 02 1.17 1.22 1 .27 1.31 1.36 1 07 127 1 33 140 147 155 78 88 92 95 99 103 0.92 1 .09 1.14 1.20 106 126 133 140 82 93 96 100 0.91 1 .07 1.12 1.17 1.22 1.27 95 1 14 120 1 26 1 34 1 40 72 82 85 88 92 96 0.82 0 . 99 1 . 04 1 .09 1.14 1 . 20 96 114 120 1 27 1 33 140 77 87 89 93 97 100 1 25 147 ill NOTE: Underlined values, though beyond recommended limits (see 5 .2 . 2.4), are given to assist in interpolation of the maximum limit. % loss of life is in addition to normal loss of life. ° *Actual water temperature should be 5 C lower than the ambient temperatures shown above (see 3 . 5 ) , and must be above zero °c. Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. (l c:: .... t::I trl "l 0 � t'" 0 > t::I ...... Z (l s: ...... Z trl � > t'" 6 F ,:... s: s: trl � r:n trl t::I '"d 0 � trl � >-3 :::0 Table 5(j ) Capability Table for Nonnal and Moderate Sacrifice of Life 55 ° C Rise, Forced-Oil-Cooled (Directed Flow - FOA, FOW*, and OA/FOA/FOA) Transfonners Equivalent Load Before Peak Load 70% of Maximum Nameplate Rating > Z 00 "%j 0 :::0 = Hours of Peak Load % Loss of Life No rmal 1 2 0_ 2 5 0.50 1 . 00 2.00 4.00 Normal 0.25 0.50 1 . 00 2 . 00 4.00 Norm al C)l W 2 24 1.80 1 .9 7 Spot T�mp ( C) 140 164 To pOil Temp (oC) 49 57 �Load Pe r nit) HotSpot Temp (C) 1.73 1 .90 1 40 1 64 TopOil Temp (C) 57 63 Peak Un i t ) HotSpot T8mp ( C) 1 . 64 1 _82 1 39 163 Load (Per TopOil Temp (C) 64 70 Peak Load (Per Un it ) HotSpot Temp (C) 1.55 1.74 1 38 1 62 s:: y To Oi Temp (0C) 71 77 40 Peak Load (Per Unit) Spot Temp (oC) 1 .45 1 . 66 1 37 161 Hot- t"l 50 TopOil Temp (C) 78 84 Peak Load (Per Unit) Spot Temp (C) 1.31 1.57 1 32 1 60 Hot- TopOil Temp (0C) 84 91 :::0 00 e::: "tI >-3 0 .... 0 0 s:: <: ::;:; ...... 1.64 1.79 1 34 157 59 67 1.57 1.73 1 33 157 65 74 1 . 49 1.66 133 156 71 80 1.40 1.58 131 155 76 85 1 . 30 1 .5 0 1 30 1 54 - 82 91 1.17 1.41 125 1 53 86 97 >-3 ::I: '" '" ° C':l 0 :::0 64 75 78 1.39 1.52 1.55 1.59 118 1 39 146 153 64 75 78 82 0.25 0.50 1.00 2.00 4.00 1.31 1.44 1.48 1.52 1.55 1.60 107 128 134 141 148 156 Normal 0.25 0.50 1 . 00 2.00 4.00 1 .23 1.36 1 . 39 1.43 1 .47 1.51 96 114 1 20 1 26 1 33 141 0.25 0.50 1 . 00 2.00 4.00 Peak 30 20 > 127 149 1 56 Normal 8 (lnit) er Ho t- 1 . 50 1.63 1.67 0.25 0.50 1 . 00 2.00 3.00 Normal 4 Peak Load Ambient °c 10 0 O'l � 74 85 88 1 .2 7 1 .43 1 .4 8 125 147 155 79 90 93 1.18 1 .3 6 1.41 1 22 146 153 83 95 98 1 .0 6 1 . 27 1.33 119 145 152 87 99 103 1.25 1 . 39 1 .43 1 . 48 1 16 1 38 144 152 73 R4 87 91 1.17 1.32 1.36 1 .4 1 115 137 144 1 51 - 77 88 92 96 1 .03 1 .25 1 . 29 1 . 34 114 1 36 143 151 81 93 96 1 00 0.97 1.16 1.22 111 135 142 85 97 64 74 78 82 85 89 1.17 1.31 1 .35 l . 39 1.44 1.48 107 127 134 141 148 1 .09 l .24 1 . 29 1.33 1.38 1 .4 2 107 127 133 140 147 73 84 87 90 94 98 1 .0 1 1 .1 6 1.21 1 . 26 77 88 91 95 99 103 104 1 24 133 1 30 81 92 96 1 00 0 :::0 00 1 .3 6 106 1 26 132 1 40 1 47 155 0.90 1 . 09 1.14 1.19 .l.Q.Q. 68 79 82 86 90 94 58 67 71 74 78 81 1.09 1.22 1 . 26 1 . 30 l.35 1.39 96 114 1 20 126 1 34 141 63 72 75 79 82 86 1 .0 0 1.15 1 .20 1 .24 1.29 1 . 33 95 114 120 126 133 141 67 77 80 83 87 91 0.91 1 .0 7 1.12 1.17 1 . 22 1 .27 95 1 14 1 20 1 26 1 34 1 40 72 81 85 88 92 96 0.81 0.99 1 .0 4 1 .09 1.14 1 . 20 95 114 1 20 127 133 1 40 77 87 89 93 96 100 C':l 126 149 155 69 80 83 1.35 1 . 50 1.55 1 . 32 1 . 45 1 .49 1 . 54 1 17 138 145 1 52 68 79 83 86 59 70 73 77 81 85 1.25 1.38 1.41 1.46 1 . 50 1.54 107 1 27 1 34 141 1 48 156 53 63 66 69 73 77 1.16 1.29 1.33 1.37 1.41 1 .45 96 114 1 20 127 1 34 1 40 1.43 1.57 1.61 125 1 48 !.QQ. 1 .31 NOTE: Underlined values, though beyond recommended limits (see 5 .2 .2.4 ), are given to assist in interpolation of the maximum limit. % loss of life is in addition to normal loss of life. *Actual water temperature should be 5 °c lower than the ambient temperatures shown above (see 3. 5 ) , and must be above zero ° C. Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. ill '" ° C':l > <: 1:':1 :::0 > 0 1:':1 ::;:; H Z a H Z t"l 01 > :-' Z 0000 t.:> ...... , - oo t"l .... ...... oo t"l ..... 1:':1 ("» Ol Z :-' 00 to ...... "" ;::. Table 5(k) Capability Table for Normal and Moderate Sacrifice of Life 55 ° C Rise, Forced-Oil-Cooled ( Directed Flow - FOA, FOW*, and OA/FOA/FOA) Transformers Equivalent Load Before Peak Load 90% of Maximum Nameplate Rating � gJ oo l':! = ... Ambient °c 0 Hours of Peak Load % Loss of Life Normal 0.25 0.50 1 .0 0 2.00 4.00 1 2 Normal 0.25 0.50 1 . 00 2_00 4 . 00 01 Normal � (oC) Hot- Spot Temp CC ) Peak Load (Per Unit) 1.57 HotSpot T8mp ( C) To r Oi Temp tc) Peak Load (Pe r Unit ) 1 . 74 1.91 1 39 163 54 60 1.66 1.84 1 38 1 62 61 67 1.77 137 162 68 75 1.45 1 . 68 1 . 60 1.76 1 33 156 61 70 1.52 1 . 69 1 32 155 67 76 1 .44 1.61 1 30 1 54 72 1.32 1.53 1 24 147 155 69 80 84 Normal 1.38 1.50 1.55 1.59 116 137 145 152 63 74 78 82 1 . 30 1.44 1.48 1.53 115 1 37 144 151 - 68 79 82 86 Normal 1 . 31 107 127 1 34 141 148 156 59 69 73 77 81 84 1.24 1.37 1.41 1.45 1 . 50 1.54 107 1 27 1 33 140 148 155 96 114 120 126 53 63 66 69 73 77 1.16 1 . 29 1.33 1 . 37 1.41 1.45 96 114 1 20 1 26 1 33 140 0.25 0 . 50 1.00 2.00 1.00 30 20 TopOil Temp (DC) 1.40 1.55 1.59 Normal 24 Temp Peak Load (Per Unit) 65 75 79 0.25 0.50 1 . 00 2.00 4.00 8 Spot Temp tc ) TopOil 125 148 156 0.25 0.50 1.00 2.00 4 . 00 4 � Ho t- 1.47 1.61 1.66 0.25 0.50 1 . 00 2.00 4 . 00 2 Peak Load Per nit) 10 1 . 32 1 .4 8 81 40 To - y Oi Temp (DC) 74 82 1 . 13 1 . 58 126 77 87 1 .06 1 .44 153 - Hot- Spot Temp ("C) 111 1 58 1 08 150 50 TopOil Temp t C) 76 88 77 92 Peak Load (Per Unit) HotSpot Temp (oC) TopOil Temp (DC ) 1.45 153 94 1.31 1.41 145 156 97 101 1 .32 1 . 38 104 143 151 76 94 98 75 88 91 95 0.95 1.23 1 . 27 1 . 33 1.38 99 1 34 141 149 1 57 74 92 95 99 1 04 1.12 1 .19 1 . 25 1 29 138 147 94 99 103 1 39 147 155 71 83 87 90 94 98 0.92 1.16 1.20 1.26 1.30 1 . 36 96 125 131 1 39 1 46 72 87 91 95 99 103 1 .05 1.12 1.18 1.23 1 22 130 1 38 146 90 95 99 103 95 114 1 20 1 26 1 33 140 67 77 80 83 87 91 0.91 1 .0 7 1.12 1 .1 6 1 . 21 1.27 95 114 1 20 1 26 1 33 140 72 81 85 88 92 96 0 .8 1 0 .9 8 1 .0 4 1 .09 1.14 1 . 20 95 113 1 20 1 26 1 33 140 77 86 89 93 96 100 74 85 88 1.22 1.41 1.45 119 145 152 78 90 93 1 .2 3 1.38 1.42 1.46 114 136 144 1 51 - 72 83 87 91 1.13 1.30 1.35 1 .4 0 111 1 35 142 150 64 74 77 81 85 89 1.16 1 . 30 1.35 1 . 39 1 .44 1.48 106 1 26 1 33 140 68 79 1 04 126 1 48 155 86 90 94 1.07 1.23 1.28 1 . 32 1 . 38 1 .42 58 67 71 74 77 81 1 . 09 1.22 1 .26 1 .30 1.35 1.39 96 114 1 20 126 133 141 63 72 75 79 82 86 1.00 1.15 1.19 1.24 1.28 1 .33 1 .52 Peak Load (Per Unit ) 1 33 1 60 123 146 153 1 .00 1.20 1 .2 8 137 148 97 102 ...... l':! l':! l':! 0 c:: ...... tj l':! ""1 0 � t"' 1.43 1 .47 1.51 1.55 1.59 1 . 23 1.36 1.39 1.43 1.47 1.51 133 141 82 1 33 � are given to assist in interpolation of the maximum limit. Underlined values, though beyond recommended limits (see 5 . 2 . 2 .4 ), % loss of life is in addition to normal loss of life. * Actual water temperature should be 5 °c lower than the ambient temperatures shown above (see NOTE: HolSpot Temp t C) 3 . 5 ), and must be above zero D C. Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. 0 > tj ...... Z 0 s::: ...... Z l':! � > t"' 0 ? .:... s::: s::: t:J � CIl t:J tj '" 0 ::;:J l':! � >-3 ::>:l :>- Table 5(1) Capability Table for Normal and Moderate Sacrifice of Life 55 ° C Rise, Forced-Oil-Cooled ( Directed Flow - FOA, FOW*, and OA/FOA/FOA) Transformers Equivalent Load Before Peak Load 100% of Maximum Nameplate Rating Z 00 "'1 0 = Ambient DC Ho ur s of Pea k Load % Loss of Life N o r m al ! 2 0.25 0.50 1 . 00 2 . 00 4 . 00 Normal 0.25 0.50 1 . 00 2 . 00 4 .00 Ql Normal Ql 2 0.25 0.50 1.00 2.00 4 . 00 Normal 4 0.25 0.50 1 .00 2.00 4 .0 0 Normal 8 0 . 25 0.50 l . 00 2.00 4 . 00 Normal 24 0 . 25 0.50 l . 00 2 .00 4 .00 Pea k Lo a d �Per nit) 1 .7 1 1 . 88 l .57 1 .73 Hot· Spot T�mp ( C) 138 162 131 155 1 .46 1 24 1 .6 0 1 .64 147 154 1 .3 7 1 .5 0 1 .54 1 . 58 Top· Oil Temp (DC) 57 63 62 71 65 76 79 Peak (Per Hot· Spot Temp 1 .6 2 1 .R O 1 37 161 Load Unit) 1 .4 9 1 .66 1 .38 1 .53 1 .5 8 1 15 137 1 44 152 81 1 . 52 1 . 55 l . 59 1 06 1 26 1 33 140 148 156 59 69 73 76 80 84 1 . 23 l .35 1 .3 9 1 .4 3 l .47 1.51 96 1 14 120 1 26 133 14 1 53 62 66 69 73 77 63 74 77 1 .30 1 .44 (D C) 130 154 - 122 146 153 - To pO il Temp Pea k Loa d TopO il Te mp 40 Peak Load (P e r Un i t ) Temp t C) T� mp ( C) (Per Hot· Spot T�mp 63 70 1.50 1 .73 133 160 70 77 1 . 00 1 .6 3 95 1 58 67 68 77 1 .38 1.59 125 72 83 1 .00 1 .4 9 95 150 67 88 tC) 69 80 84 Unit) 1 .28 1 .4 6 1.51 1 14 136 143 151 - 67 79 82 86 l . 20 l .3 7 1.41 1.16 1 .23 l .37 141 145 1 .4 9 l . 54 1 06 1 26 132 14 0 147 1 55 63 74 l .16 l . 29 1 .33 l . 37 1 .4 1 1 .4 5 95 114 120 1 .18 30 20 10 0 ( C) 153 - 119 145 1 52 t C) 73 85 88 1 . 00 1 .38 1 .43 1 .00 l .29 Hot· Spot 95 142 151 95 TopOi l 84 67 89 93 67 150 70 83 87 91 l.15 1 .3 0 1 .34 l . 39 1 .43 1 .4 8 1 04 1 26 132 139 147 154 67 78 82 85 89 93 1 .0 0 1 . 23 1 .27 1.32 1.37 1 .42 95 1 25 132 1 39 1 46 1 54 83 86 90 94 98 1 . 09 1 . 22 1 . 26 1 . 30 1 .35 l . 39 96 114 120 1 26 133 140 63 72 75 79 82 86 1.00 95 1 14 120 1 26 1 33 140 67 77 80 83 87 91 111 135 143 1 33 87 l .3 9 l .4 4 141 1 49 1 57 - 91 95 99 67 1 .34 �t:J Peak Load (Per Unit) 1 . 49 Hot· Spot Temp tC) TopOil Temp t C) ] 52 1.37 l .4 5 144 1 .27 1 . 34 l .4 1 1 :17 1 47 155 ::>:l 00 50 89 92 96 Hot· Spot T� mp TopOil Temp 1. 4 1 152 97 1 . 28 1 .4 2 144 161 98 1 04 0.50 l .19 1 .30 76 137 152 60 97 1 04 Peak Load (Per Unit) ( C) (DC) c::: "d >-3 0 >-' 0 0 s::: <: :>::E I-< >-3 :r: 01 01 ° (') 0 ::>:l a> 01 1.19 l.26 1 .31 1.38 156 129 139 147 156 92 97 101 89 94 98 1 03 0.75 l .1 3 1 .2 2 90 130 143 76 95 101 ° (') :><: t:J ::>:l :>0 t:J ::E I-< Z t:l .... Z 1.30 l .43 l .4 7 l.51 77 81 85 89 1 26 58 67 71 74 133 140 81 77 1.15 1 .19 1 . 23 l . 28 l .33 1.13 1.19 1 .25 l .30 1.35 0.91 1 . 07 1.12 1 . 16 l . 21 1 . 27 1 22 1 29 13R 146 154 86 90 94 98 102 0.94 1 . 08 1.16 1.22 1 08 1 25 135 144 94 114 71 81 85 88 91 96 0.80 0.98 1 .0 4 1 .09 l.14 1 .20 94 113 1 19 1 26 133 140 120 126 132 140 NOTE: U nderl i ned values, though beyond recommended limits (see 5 .2 .2.4), are given to assist in interpolation of the maximum limit. % l oss of life is in addition to normal loss of life. *Actual water temperature should be 5 D C lower than the ambient temperatures shown above (see 3.5), and must be above zero D C. Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. 83 92 97 lQe. 76 86 89 93 96 1 00 0 ::>:l .... 00 t:J (') 01 :>- :-> Z 0:> 00 t<> .... � t:::i 0:> t:J oo t:J .-. t;r1 n ;l> <:i' Z :-' 00 .., ...... t-:> -;::; ' t:IJ Table 5(m) Capability Table for Normal and Moderate Sacrifice of Life 55 ° C Rise , Forced-Air-Cooled (OA/FA/FA) Transformers Rated Over 1 33% of Self-Cooled Rating Equivalent Load Before Peak Load 50% of Maximum Nameplate Rating � t:IJ oo t:IJ I-' = Ambient °c Hours of Pea k Load I '2 c;n � 2 % Loss of Life Normal 0.25 0.50 1 .00 2 .00 4 .00 1 . 84 2 . 04 Normal 0.25 0.50 1 .00 2 .00 4 .00 1 .6 2 1 .8 0 0.25 0.50 1 . 00 2 .00 4 .00 0.25 0.50 1 . 00 2 .00 4 . 00 Normal 0.25 �4 JPer nit) 2 .00 Norm al 8 Load Normal 0.25 0.50 1 . 00 2.00 4.00 N orm al 4 Pea k O liO 1 . 00 2 . 00 4 . 00 HotSpot T( � mp C) 1 33 135 159 TopOil Temp (0 C) 48 61 71 P ea k Load (P e r Unit) HotSpot Temp (o C) TopOil Te mp ("C ) Peak Load (Per Unit) 1 .97 2.21 140 1 64 57 64 1 . 87 2.1 1 1 .7 4 l .9 5 134 1 58 66 76 1 .6 4 1 .85 HotSpot T( �mp C) Top Oil Temp o ( C ) Peak Load (Per Unit) HotSpot Temp (o C) 40 TopOil Temp (0 C) Pe a k Load (Per Unit) Hot- Spot Temp ("C) 50 TopOil Temp (0 C) Peak Load (Per Unit) HotSpot Temp TopOil (0 Temp tC ) C 1 6:, 63 71 1 .7 6 2.00 139 163 70 78 1 . 63 1.89 138 162 76 84 1 .5 0 1 .78 1 36 161 83 91 133 1 57 71 82 1 .54 1 .7 6 132 1 56 77 87 1 .43 1 .6 6 132 155 82 92 1.30 1.55 130 1 54 87 97 1 39 ) ...... t:IJ t:IJ t:IJ Q 1 27 150 67 79 1.54 1.72 1 .7 7 1 27 149 157 71 83 87 1 .45 1 .6 3 1 .6 9 1 26 149 1 56 76 87 91 1 .3 5 1 . 54 1 .6 1 1 25 148 1 55 80 91 95 1 . 24 1 .45 1 .52 1 24 147 1 55 84 96 100 1.1 3 1 .36 1 22 146 88 1 00 C ...... t:J t:IJ "'j 0 � t"' 1 . 5 :1 1 . 58 1 16 1 :1 8 145 152 74 86 90 94 1.21 1 . 39 1 . 45 1 .50 1 16 138 145 151 78 90 94 98 1.12 1 . 30 1 . 36 1 .42 115 137 144 151 82 94 98 102 1 . 00 1 .21 1.28 113 1 36 143 86 91l 1 02 65 76 80 84 88 93 1.21 1 . 37 1 . 42 1 . 48 1.53 1 . 59 107 1 27 133 141 148 155 69 80 84 88 92 97 1.12 1 . 29 1 . 35 1 40 1 . 46 1 . 52 106 1 27 133 140 148 1 55 73 85 88 92 96 101 1 . 02 1.21 1 .2 6 1 .32 1 . 38 1 06 1 27 133 140 148 77 89 92 96 0.91 1.11 1 .1 7 1 .23 105 1 26 1 32 140 81 93 96 101 58 68 72 76 79 84 1.11 1 .26 L3 2 1 .3 7 1 .4 2 1 .4 8 95 114 1 20 1 26 133 140 63 73 76 80 84 88 1 . 01 1.18 1 .23 1 .28 1 . 34 1.4 0 95 114 1 20 1 26 133 140 67 77 81 84 88 92 0.90 1 . 09 1 .1 4 1 . 20 1 .26 1.32 95 113 1 19 1 26 133 140 71 81 85 88 92 96 0.78 0.98 1 .0 4 1.11 1 . 17 1 .23 95 113 1 19 1 26 1 :13 140 76 86 89 93 97 101 1 .6 3 1 .68 l .7 3 1 18 139 146 153 66 78 82 86 1 .3 9 1 . 55 1 .6 1 1 .6 6 117 138 146 152 70 82 86 90 1 . 30 1 .4 7 l . 38 1 .53 1 . 58 1 .63 1 . 68 1 .7 3 1 07 1 27 134 141 148 1 56 61 72 76 80 84 119 1 .3 0 1 .4 6 1 .50 1 .6 1 1 . 66 1 07 1 27 1 33 140 148 1 56 1 .28 1 . 4 :> 1 .47 1 .52 1 .57 l .B 2 96 1 14 1 20 1 26 133 140 54 64 68 71 75 79 1 . 19 1 .35 1 . 39 1 .44 1 .4 9 1 . 55 95 114 1 20 1 26 133 140 1 .48 0 ;I> t:J Z Cl s:: ...... Z t:IJ U, 5 NOTJ<.;; Underlined values, though beyond recommended is in addition to normal loss of life. % loss of life 30 20 10 0 limits (see 5_2.2.4 ), are given to ill assist in interpolation of the maximum limit. Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. � ;I> t"' 6 F ,:... s:: s:: t:IJ � 00 t:IJ t:J "C 0 ::E t:IJ ::tI >-3 � > Z Table 5(n) Capability Table for Nonnal and Moderate Sacrifice of Life 55 ° C Rise, Forced-Air-Cooled (OA/FA/FA) Transformers Rated Over 133% of Self-Cooled Rating Equivalent Load Before Peak Load 70% of Maximum Nameplate Rating 00 "lj 0 ::0 = 0 Hours of Peak Load 1 2' Cl1 -;J 2 4 8 24 % Loss of Life Peak Load Per � 1 nit) Normal 0.25 0.50 1 . 00 2.00 4.00 2.00 Normal 0.25 0.50 1 . 00 2.00 4 . 00 1.81 2.00 Normal 0.25 0.50 1 .00 2.00 4.00 1 .61 1 .78 1 . 83 tc) 1 40 Top- Oil Temp (o e ) 53 Peak Load (Per ni ) U t 1 .9 2 2.16 HotSpot Temp (oC) 1 39 1 63 20 Top- Oil Temp t C) 60 68 1 34 157 62 72 1.71 1 .9 1 1 33 156 68 78 U un 2 .0 6 HotSpot T�mp ( e) 1 38 1 63 To p· Oil Temp (oe) 66 74 Peak Load (Per HotSpot Temp 1.69 1 .95 1 37 1 62 Unit) (o C ) Top· Oil Temp tC) 73 81 Hot- Peak Load (Per Uni t ) Spot Temp 1 . 54 1 . 83 135 1 60 (C) 5: tzl � 50 Top· Oil Temp (oC) 79 87 Peak Load (Per Unit) Hot· Spot T5m p 1.35 1.71 1 29 159 ( C) 00 Top· Oil Temp (oC ) 84 93 e:: '1:1 >-3 0 >-' 0 0 5: <: 1 . 60 1 .8 2 132 156 73 83 1 .49 1.72 131 155 78 88 1 . 36 1.62 129 1 54 83 94 1.17 1 .50 121 152 85 98 � ...... >-3 :::r: '-" '-" 0 (") 0 � 1 .4 6 1.63 1.67 1.73 Normal 0.25 0.50 1 .00 2 . 00 4 . 00 1 . 38 1.53 1.57 1.62 1 . 67 1.73 1 27 149 1 57 67 79 83 1 .5 2 1 .7 0 1.76 1 26 148 1 S6 71 R :l 87 1.42 1.61 1 . 67 1 25 148 155 116 1 37 144 152 1.38 1.55 1 . 60 1.65 116 138 145 152 69 81 86 89 1 . 29 1 . 47 1 .52 1 . 58 61 72 76 80 84 89 1 . 29 1.45 1.50 1.55 1 . 60 1 6 fi 1 07 1 27 1 33 141 148 156 65 76 80 84 88 9 :1 1 . 20 1 . 37 1 .42 1 . 47 1 .53 l S9 106 1 26 133 140 1 48 1 55 54 64 68 71 75 79 1 . 19 1.35 1 .40 1.44 1.50 1.55 1 14 95 58 68 72 76 80 84 1 . 10 1 . 26 1.31 1.37 1 . 42 9 1) 113 1 20 126 132 1 40 117 1 38 145 153 65 77 81 86 107 127 133 141 148 1 56 76 H7 91 73 85 89 94 1 .32 1 .5 2 1 .59 1 23 147 1 54 80 92 96 1 . 20 1 . 43 1 . 50 1.19 1 . 38 1 .44 1 . 50 111 137 144 151 77 90 94 98 1 . 09 1 . 29 1 . 35 1.41 1 21 145 154 83 96 100 1 . 04 1.33 113 1 36 143 1 50 81 93 97 102 0.93 1.19 1 . 26 1 15 144 85 100 a> '-" 0 (") > <: tzl � 108 134 142 82 97 101 > CJ tzl � ...... Z t:l 12R 1.42 1.47 1.52 1 . 57 1.62 95 113 119 126 1 33 140 1 20 1 26 1 33 140 NOTE: Underlined values, though be yond recommended limits loss of life is in addition to normal loss of life. % Peak Load (Per ni t ) 40 30 > Normal 0.25 0 . 50 1 . 00 2 . 00 4 . 00 Normal 0 . 2S 0.50 l . OO 2 . 00 4 . 00 HotSpot Tem p Ambient °c 10 1.17 88 92 97 1.11 1 . 28 1.34 1 . 40 1 .46 1 S1 106 126 132 1 40 147 1 55 73 84 88 92 96 101 1 .01 1 .20 1.25 1.32 1 . 38 lOS 1 26 132 140 1 47 77 88 92 96 1 00 0.R6 1 .10 1.16 1 . 22 101 1 24 132 139 79 92 96 1 00 63 73 76 80 83 88 1 .01 1 . 18 1 . 23 1 . 29 1 . 34 1 . 40 95 113 119 1 26 132 140 67 77 80 84 88 92 0 .90 1 .0 8 1.14 1 .2 0 1.26 1 .31 95 113 119 125 133 1 39 71 81 85 88 92 96 0.78 0.98 1 . 04 1.11 1.17 1.23 94 1 13 1 19 1 26 1 33 1 40 75 86 89 93 97 1 00 69 80 H4 (see 5 .2.2.4 ) , are given to assist i n interpolation of the maximum l imit. Z CJ � FiJ tzl (") '-" > :-' Z "' 00 "" ...... �� ", tzl oo tzl ...... tzl Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. C':l ;'c.n z :-' 00 to ..... "" ;::. Table 5(p) Capability Table for Normal and Moderate Sacrifice of Life 55 ° C Rise, Forced-Air-Cooled (OA/FA/FA) Transformers Rated Over 1 33% of Self-Cooled Rating Equivalent Load Before Peak Load 90% of Maximum Nameplate Rating � � oo tzl .... = Ambient ° c 0 Hours of Peak Load % Loss of Life Normal I 2 0.25 0.50 1 . 00 2 . 00 4.00 Normal 1 I:.l1 00 0 . 25 0.50 1 . 00 2.00 4 . 00 Normal 2 0.25 0.50 1 . 00 2.00 4.00 Normal 4 0.25 0 . 50 1 .00 2.00 4 . 00 Normal 8 0.25 0.50 1 . 00 2.00 4.00 Normal 24 0.25 0.50 1 . 00 2.00 4.00 Pe ak Load Per nit ) Ho t· Spot T!/mp ( C) Top· Oil T�mp ( e) 1 .96 2.19 139 163 1.75 1.96 � 133 J 1 . 58 1 .7 6 1 .81 125 148 1 56 20 10 Peak Load Per nit) Hot· Spot T�mp 57 65 1 .84 2.09 1 38 162 64 71 1.72 1.98 64 74 1.65 1 .87 131 1 56 69 80 1.53 1 .7 7 67 79 83 � 1 .49 1.67 1.73 ( C) 1 24 1 47 1 55 -- TopOil T�mp ( e) 71 83 87 Peak Load (Per Unit) 1 . 38 1 . 58 1 . 65 Hot· S po t T!/mp ( e) , 30 To Oi Temp t e) Peak Load (Per Unit) 1 37 161 70 78 1 . 56 1 .8 6 1 32 160 1 29 74 85 1 .38 1 .66 � 1 25 ll.! 122 1 46 1 54 75 87 92 1 .24 1 .49 1 . 56 Hot· Spot T� mp ( C) 117 144 152 , 40 , 50 Peak Load (Per Unit ) Hot· Spot Temp t e) To Oi Temp 0 Peak Lo ad (Per Unit ) Hot· Spot T�mp ( e) Top· Oil Temp e e) 75 84 1 .7 3 157 90 1.54 1 50 95 78 90 1 . 54 150 94 1 . 36 1.49 To Oi T�mp ( e) 77 91 96 1 . 38 1 . 45 142 1 50 ( C) 95 99 1.23 1 .34 143 97 155 - 102 -- 135 147 96 103 ..... tzl tzl tzl P c:: ..... t:! tzl ""l 0 :Xl t'" 1 .46 1.61 1 . 66 1.71 116 137 144 151 65 77 81 85 1.37 1 . 54 1 . 59 1 . 64 115 1 37 144 1 51 69 81 85 89 1 . 27 1.45 1.51 1 . 56 113 1 36 143 1 50 72 85 89 93 1.15 1 . 37 1.42 1.48 1.55 110 135 142 1 49 158 75 89 93 97 102 1 . 26 1 .33 1 .4 0 1 . 37 1.53 1 . 57 1.62 1 .6 7 1 .72 1 07 1 27 133 140 148 1 55 60 72 76 79 84 88 1 . 29 1 . 44 1.50 1.55 1.60 1.66 1 06 1 26 133 1 40 148 1 55 64 75 79 84 88 92 1 .2 0 1.37 1 .4 2 1 .47 1 .53 1 .5 8 105 126 132 140 147 155 68 80 83 88 92 96 1 .0 8 1 . 28 1.33 1 . 39 1.45 1.51 103 125 131 1 39 146 1 54 71 84 87 92 96 1 00 1 . 18 1 . 24 1.31 1 . 37 1 24 1 31 1 39 1.28 1 .4 2 1.47 1 .52 95 113 119 126 1 32 140 54 64 67 71 75 80 1.19 1 . 34 1 . 39 1 .4 4 1 .4 9 1.55 95 113 1 19 126 1 32 1 40 58 68 72 75 79 83 1.10 1 . 26 1 .31 1.37 1 .42 1.47 95 113 119 1 26 133 140 62 73 76 80 84 88 1.00 1.18 1.23 1 . 29 1 . 34 1.40 94 113 119 1 26 132 140 66 77 80 84 88 92 1 . 08 1.14 1.19 1 .2 5 1 . 32 1 . 57 1.62 132 141 1 49 92 96 101 1.13 1 .22 1 . 30 1 28 137 147 94 99 104 0 ;.t:I ..... Z 0 s:: ..... Z tzl 146 87 91 96 1 00 1 . 05 1.14 1.21 1 . 28 1 20 1 29 137 145 90 95 99 104 113 119 125 1 32 140 81 85 88 92 96 0.99 1.04 1.11 1.17 1.23 113 119 126 1 32 140 86 89 93 96 101 NOTE: Underlined values, though beyond recommended limits (see 5.2.2.4 ), are given to assist in interpolation of the maximum limit. % loss of life is in addition to normal loss of life. Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. :Xl ;.t'" " t'" �s:: tzl � tzl t:I "C 0 :::1 tzl :Xl ..., � � Table 5(q) Capability Table for Normal and Moderate Sacrifice of Life 55 ° C Rise, Forced-Air-Cooled (OA/FA/FA) Transformers Over 133% of Self-Cooled Rating Equivalent Load Before Peak Load 100% of Maximum Nameplate Rating til ":1 0 � is: l'l � = Ambient 0 Hours of Peak Load % Loss of Life Normal ! 2 0.25 0.50 1 .00 2.00 4 . 00 Normal 1 01 CO 0.25 0.50 1 .00 2.00 4.00 Normal 2 0.25 0.50 1 . 00 2.00 4 . 00 Normal 4 0.25 0.50 1 .00 2.00 4 . 00 Normal 8 0.25 0.50 1 . 00 2.00 4 . 00 Normal 24 0.25 0.50 1 .00 2.00 4.00 Peak Load iJPer nit) 1.91 2.15 Hot· Spot T� mp ( C) 138 162 10 Top· Oil Temp (C) 59 67 Peak Load (Per Unit) 1.79 2.05 -- Hot· Spot Temp e C) 1 36 161 til °c 20 TopOil Temp (oC) 65 73 Peak Load (Per Unit) Hot· Spot Tsmp 1 . 63 1 . 93 132 160 ( C) y To Oi Temp C C) 71 80 30 40 Peak Load (Per Unit) Hot· Spot Temp TopOil Temp 1 .06 1 .8 0 99 1 57 C C) (C ) Peak Load (Per Unit) Hot· Spot Temp (DC) 68 86 1 .63 152 c:: "C 50 Top· Oi l Tsmp ( C) Unit) (Per Hot· Spot T� mp ( C) 1 . 50 151 Peak Load TopOil T'6m p ( C) 91 97 ..., 0 .... 0 0 is: <: > ::a =3 ::c 1 .7 2 1 . 93 131 156 - 65 75 1 .6 1 1.83 1 30 1 54 - 70 80 1.47 1 .73 125 153 74 85 1 . 06 1 .62 99 150 68 90 01 01 1 . 45 1 . 57 144 156 93 98 ° 1 . 3 -1 1 .5 1 143 1 59 98 105 · n 0 � a> 01 ° 1.56 1.74 1 . 80 124 147 155 67 79 83 1.46 1 . 66 1.71 1 22 1 46 153 71 83 87 1 . 34 1 . 56 1 . 63 118 1 44 152 73 87 91 1 .03 1.46 1 . 54 97 142 151 68 91 95 1.45 1.61 1 . 66 1.71 115 1 37 143 151 64 77 81 85 1.35 1.53 1 . 58 1 .63 113 136 143 1 50 68 81 84 89 1 . 24 1.45 1.50 1.56 110 135 142 1 50 71 84 88 93 1 .02 1 . 34 1 .41 1 .48 1 . 54 96 1 32 141 1 49 157 1 . 37 1.52 1.57 1 .62 1.67 1.73 1 06 126 133 140 147 156 60 71 75 79 83 88 1.28 l.45 l.49 1 . 55 1 . 60 1.65 105 1 26 1 32 1 40 1 47 155 64 76 79 83 88 92 l . 28 1 .4 2 1 .47 1.52 1 . 57 1 . 62 95 113 1 20 126 1 33 140 54 64 68 71 75 79 1.19 1 . 34 1 . 39 1 .44 1 . 49 1 . 54 95 113 1 19 126 132 1 40 58 68 72 75 79 83 1 .1 7 1 .31 1 .42 1 . 50 135 147 157 92 98 103 1.22 1 . 38 135 152 97 1 06 67 87 92 97 101 1.22 1 .30 1 .38 1 28 138 146 89 95 100 1.14 1.27 1 29 1 43 94 102 l .1 6 1 . 23 1 . 30 1 . 36 121 129 137 146 86 90 95 1 00 1 .09 1.19 1 .27 1 24 135 144 92 98 103 1 .08 1.13 1 . 20 1 .25 1 . 31 113 118 1 25 132 139 81 84 88 92 96 1 .04 1.10 1.16 1 .23 118 1 25 132 1 39 89 92 96 100 1 .36 1 .41 1.46 1.52 1 .58 103 125 132 1 39 147 1 54 67 79 83 87 92 96 1 .0 1 1 . 27 1 . 33 1.38 1.45 1 . 50 95 1 24 131 1 38 1 46 1 54 67 83 87 91 96 100 1.10 1 .2 6 1.31 1.37 1 .4 2 1 .4 8 95 113 119 1 26 133 140 62 73 76 80 84 88 1 .00 1.17 1.23 1 . 28 1.34 1 . 39 95 113 119 1 26 133 140 67 77 80 84 88 92 NOTE: Underlined values, though beyond recommended limits (see 5.2 . 2 .4 ), are given to % loss of life is in addition to normal loss of life. assist in interpolation of n > <: l:IJ � > 0 l:IJ ::a Z 9 Z the maximum limit. Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. 0 � 53 l:IJ n 01 ):-' Z ([) tIl � ..... , � .... ..... ([) l:IJ oo l:IJ .... l:IJ 0 ;'- "" Z ;--1 00 Table 5(r) Capability Table for Normal and Moderate Sacrifice of Life 55 ° C Rise, Forced-Oil-Cooled (Non-Directed Flow - FOA, FOW*, and OA/FOA/FOA) Transformers Equivalent Load Before Peak Load 50% of Maximum Nameplate Rating \0 .... � -;::. ' t<J .... t<J � t<J .... = Hours of Peak Load % Loss of Life Nor ma l Peak Load �Per t: n i t ) 2.00 1.80 1.97 Hot - Sp ot T� mp ( C) To yOi Temp (C) 0.25 0.50 1 . 00 2 . 00 4 . 00 Normal en 0 2 0.25 0.50 1 . 00 2.00 4 . 00 Nor m al 4 0. 2 5 0.50 1 . 00 2.00 4 . 00 Normal 8 0.25 0 . 50 1 . 00 2 . 00 4.00 Normal 24 NOTE: 0.25 0. 5 0 1.00 2.00 4 . 00 (Per Unit) 1 37 1.95 2.16 1 36 1 58 64 75 1.71 1.90 Hot- Spot Temp ( oC ) TopOil Temp t C) Pea k Load (Per U n it ) Hot- Spot Tsmp ( C) 40 30 To y Oi Temp t e) Peak Load (Per Unit) Hot- Spot Temp t e) TopOil Temp t e) 140 165 59 68 1.85 2.07 140 163 66 74 1.74 1.97 1 :39 1 63 72 80 1 35 1 58 69 80 1 .62 1.81 134 157 74 85 1 . 52 1.72 1 33 156 78 90 Peak Load (Per Unit) Ho t - Spot Temp (C) 1 .62 1.87 1 38 163 1 . 42 1 . 64 132 156 50 To pOil Temp ( oC) Pea k Load (Per U n it) Hot- Spot Temp ("C ) To p Oil Temp eC ) 78 86 1 . 50 1 .76 137 161 84 92 83 95 1.30 1 . 53 131 155 88 99 .... t<J t<J t<J 1 .59 1.74 1 28 1 50 69 82 1.51 1.67 1 28 1 50 73 86 1.43 1.60 1 . 65 1 27 149 157 1 . 44 1.59 1.63 1 .68 118 140 146 1 54 68 81 85 89 1.37 1.52 1 . 56 1.61 1 18 1 39 145 1 53 71 84 88 93 1 .29 1 .44 1 . 50 1 . fi 4 117 1 38 145 153 92 97 1 .35 1.49 1 .54 1 . 58 1 . 63 1 .6 8 1 08 1 28 134 141 149 157 62 79 8 :3 87 92 1 . 28 1 .4 3 1.47 1 .5 1 1.56 1.61 1 08 1 28 1 34 141 1 48 66 78 82 86 91 96 1 . 20 1 .3 5 1 . 40 1 .4 5 1 .50 1.55 107 127 1 33 141 148 1 56 1 . 26 1.40 1.44 1.48 1.53 1.57 95 1 14 1 20 1 26 1 33 140 55 66 70 74 78 82 1.18 1.32 1.37 1.41 1.46 1.51 96 113 1 20 1 26 133 140 59 70 74 77 82 86 1.10 1.25 1 . 29 1 . 34 1 . 39 1 .44 95 114 119 126 133 140 74 � Underlined values, though beyo nd recommended is in addition to normal loss of life. % loss of life '"Actual Peak Loa d 52 0.25 0.50 1 . 00 2 . 00 4.00 Nor mal Ambient aC 20 10 0 88 102 77 90 94 1.33 1.51 1.57 1 26 148 156 81 94 98 1 . 24 1 . 43 1 . 49 1 24 1 48 155 85 98 102 1.13 1 . 34 1 22 147 75 1 . 20 1 . 37 1 .42 79 91 95 1 00 1.11 1 . 29 1 . 34 1 . 39 115 137 1 44 151 82 95 99 103 1 .0 0 1 . 20 1 . 26 1 14 1 36 143 1.47 116 138 1 44 152 70 82 86 90 95 100 1.11 1.27 1 .32 1 .38 1 .4 2 1 .48 107 126 133 141 147 156 74 85 89 94 98 1 03 1 .0 2 1.19 1 . 24 1 . 30 1.35 106 1 26 133 1 40 1 48 78 89 93 97 102 -- 0.91 1.11 1.16 1 .2 2 105 126 132 1 40 81 93 97 101 63 74 77 81 85 90 1.01 1.17 1 .2 2 1 .27 1.32 1 . 37 95 1 14 1 20 1 26 133 140 67 78 81 85 89 94 0.91 1.08 1.13 1.19 1 . 24 1 . 30 95 113 119 126 133 140 71 82 85 89 93 97 0.80 0.99 1 . 05 1 . 10 1.16 1.22 95 113 120 126 132 139 75 86 89 93 97 101 88 limits ( see 5.2.2.4 ), are given to assist in interpolation of the maximum limit. water temperature should be 5 aC lower than the ambient temperatures shown above (see 3 .5 ) , and m ust be above zero a C . Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. 86 98 !N 0 c::: ...... tl t<J ""J 0 .., t"' 0 ;..tl ...... Z 0 s:: ...... Z t<J .., ;.t"' 0 .... t"' �s:: t<J .., 00 t<J tl "<l � t<J .., � � Table 5(8) Capability Table for Normal and Moderate Sacrifice of Life 55 ° C Rise, Forced-Oil-Cooled (Non-Directed Flow - FOA, FOW*, and OA/FOA/FOA) Transformers Equivalent Load Before Peak Load 70% of Maximum Nameplate Rating �00 = Hours of Peak Load % Loss of Life Normal ! 2 0.25 0.50 1 . 00 2.00 4 . 00 Normal 1 0.25 0.50 1 . 00 2.00 4.00 Normal m f-' 2 4 0.25 0.50 1 . 00 2.00 4.00 Normal 0.25 0.50 1 . 00 2.00 4.00 Normal 8 24 Peak Load �Per nit) 1 .99 2.21 0 10 HotSpot Tsmp H ot- ( C) 141 165 TopOil Temp (0C) Peak Load (Per Unit) 56 65 1.89 2.11 Ambient °c 20 Spot Temp TopOil Temp Peak Load (Per HotSpot T8mp 1 40 163 62 71 1.79 2.02 139 163 t C) (0C) Unit) ( C) 30 TopOil Temp Peak Load (Per HotSpot Temp 68 77 1.67 1 .9 2 138 163 t C) Unit) tC ) 40 50 To rOi Temp (oC) Peak Load (Per Unit) HotSpot Temp TopOil Temp (C) Peak Load (Per Unit) Spot Temp Temp 74 83 1.54 1.81 136 162 80 89 1.35 1 . 69 129 160 84 95 (C) Hot- (C) TopOil (0 C ) "'l 0 � is: t'i � 00 e::: "C � 0 f-' 0 0 is: <: » ::is 1.76 1 .95 1 34 1 58 65 77 1.67 1.87 1 33 1 58 70 82 1 .58 1.78 133 156 75 86 1 . 47 1 . 68 131 155 79 91 1 . 36 1 . 59 129 1 54 84 96 1.19 1.18 1 23 152 86 100 ::3 ::c 01 01 ° C1 0 � 1.57 1.73 127 150 69 83 1 .49 1 . 66 1.71 1 26 149 1 57 73 86 91 1 .40 1 . 58 1 . 63 125 148 1 56 77 90 94 1.31 1.50 1.55 1 24 148 155 81 94 98 1.20 1.41 1.47 122 146 1 54 84 97 1 02 1 . 05 1.31 116 144 86 101 m 01 ° C1 » <: t'i � 1 . 44 1.58 1 . 63 1 . 6R 117 139 146 1 54 67 80 85 89 1.36 1.51 1.56 1.61 117 138 145 152 71 84 88 93 1.28 1 .44 1 .49 1.54 74 87 92 96 1.19 1 .36 1.41 1 .47 115 137 1 44 152 78 91 95 1 00 1 .09 1 . 28 1 . 33 1 . 39 113 136 143 1 51 81 94 98 1 03 1 . 50 1.55 1. 44 107 1 27 133 140 148 156 70 82 86 90 95 1 00 1.10 1.27 1.32 1.37 1.43 1.48 1 06 1 26 133 140 148 155 73 85 89 94 98 103 1 .0 1 1.19 1 . 24 1 . 29 1 . 35 105 1 26 133 139 147 1.10 1.25 1 .29 1 . 34 1 . 39 1.44 95 113 119 126 133 140 63 74 77 81 85 90 1 .0 1 1.17 1.21 1.27 1.32 1 . 37 95 113 1 19 1 26 133 1 40 67 78 81 85 89 94 0.91 1 . 08 1.13 1 .1 9 1 . 24 1 . 30 95 113 1 20 1 26 1 33 140 71 82 85 89 93 98 1 . 35 1 . 49 1 . 54 1 . 58 1 . 63 1.67 107 127 1 34 141 149 156 62 74 78 83 87 92 1 .28 1 .42 1 .4 7 1.51 1.56 1.61 107 127 1 33 141 1 48 1 56 66 78 82 86 91 96 1.19 1.35 1.40 Normal 0.25 0.50 1.00 2.00 4.00 1 . 26 1 .40 1 .44 1 . 48 1 . 53 1 . 57 95 114 120 1 26 1 33 140 55 66 70 74 78 1.18 1 . 33 1.37 1.41 1.46 1.51 95 114 1 19 1 26 133 140 59 70 73 77 82 86 0.95 1.19 1.25 83 98 � » Cl t'i ::is Ii t:l 77 89 93 97 1 02 0.25 0. 5 0 1 . 00 2.00 ·1 . 0 0 82 116 138 144 152 109 135 142 NOTE: Underlined values, though beyond recommended limits (see 5.2.2.4 ), are given to assist in interpolation of the maximum limit. % loss of life is in addition to normal loss of life. "Actual water temperature should be 5 °c lower than the ambient temperatures shown above (see 3.5), and must be above zero °c. Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. 0.88 1.10 1.15 1.21 102 125 132 139 80 93 97 101 0.80 0.98 1 .04 1 .1 0 1.16 1.22 95 113 119 1 2 1) 133 140 75 R6 89 93 97 101 Ii Cl � ...... 00 t'i Q» :-' Z a;> 00 t-:> ...... � j::;; a;> t'i ao trl f-' t'i C"l > O1 Z :-" 00 co ..... "" ;:; Table 5(t) Capability Table for Nonnal and Moderate Sacrifice of Life ° 55 C Rise, Forced.()il·Cooled (Non.Directed Flow - FOA, FOW*, and OA/FOA/FOA) Transfonners Equivalent Load Before Peak Load 90% of Maximum Nameplate Rating ':' gJ g; t:EJ .... = 10 0 Hours of Peak Load 1. 2 1 � t-:) % Loss of Life �Per nit) Load · Hot Spot Temp (o C) Top· Oil Tsmp ( e) Peak Load (Per Unit) Hot· Spot Tsmp ( e) y To Oi Temp tc) 30 Peak Load (Per Unit) Hot· Spot Tg mp ( e) 40 To r Oi Temp (o e ) · Peak Load (Per Unit) Ho t Spot Temp (oC) 50 Top· Oil Temp (o e ) 60 69 1.81 2.04 1 38 1 63 66 75 1.70 1 .9 4 137 161 72 81 1 .54 1.83 1 32 1 60 77 87 1 .03 1.71 103 158 73 92 Normal 1.71 1.91 133 1 57 67 79 1 .6 2 1.82 1 32 1 56 72 83 1.52 1.73 1 30 154 76 87 1 . 38 1 .6 3 1 26 1 53 79 92 0.97 1 . 52 99 151 73 96 0.25 0.50 1.00 2.00 4.00 0.25 0.50 1 .00 2.00 4 . 00 0.25 0 . 50 1 . 00 2.00 4 . 00 0.25 0.50 1 . 00 2 . 00 4 . 00 Normal 24 Peak 139 163 Normal 8 ( e) Top· Oil Temp (oC) 1 .9 2 2. 1 4 0 . 25 0.50 1 . 00 2 . 00 4 . 00 Normal 4 {lnit) Hot· Spot Tsmp Normal Normal 2 Peak Load er Ambient °c 20 0.25 0.50 1 .00 2.00 4.00 1.55 1.71 1 .76 126 148 156 70 82 87 1 .4 6 1.63 1 . 69 124 147 1 55 73 86 91 1 . 36 1 . 55 1 . 61 122 147 154 76 90 94 1 . 24 1 . 46 1.52 119 145 152 79 93 98 0.93 1 . 36 1 . 43 97 143 151 72 96 101 1 .43 1 . 57 1 . 62 1 . 67 116 1 37 145 152 67 80 84 89 1 . 34 1 . 50 1.55 1.60 115 137 144 151 - 70 83 87 92 1 .26 1.42 1.48 1 .5 3 114 136 143 151 - 73 87 91 96 1.15 1 . 34 1.40 1.45 110 135 142 1 50 76 90 94 99 0.92 1 .2 5 1 .31 1.37 96 133 141 148 72 93 97 102 -- 1 .35 1 .4 9 1 . 53 1 .58 1 .6 2 1 .6 7 107 1 27 134 140 148 156 62 74 82 87 92 1.27 1.42 1.46 1.51 1.56 1.61 106 1 27 1 33 1 40 1 48 1 55 65 78 81 86 91 95 1 . 18 1.34 1 . 39 1.44 1 .49 1 . 54 105 1 26 1 32 1 39 147 155 69 81 85 89 94 99 1 .08 1 . 26 1 .3 1 1 .37 1.42 1.47 103 125 132 139 147 1 54 72 85 89 93 98 0.91 1.18 1.23 1 .29 1 . 34 95 1 24 131 1 38 1 46 71 88 92 97 101 1.26 1 . 40 1.44 1.48 1 .53 1 . 57 95 1 14 1 20 126 133 140 55 66 70 73 78 82 1.18 1.32 1.36 1.41 1.46 1.51 95 114 119 1 26 133 1 40 59 70 73 77 82 86 1 . 09 1 . 24 1 . 29 1 . 34 1 . 39 1 . 44 95 113 120 1 26 132 140 62 73 77 81 85 90 1 . 00 1.17 1.21 1 . 26 1.31 1 . 37 94 113 119 126 132 140 66 78 81 85 89 93 0.90 1 . 08 1.13 1 .18 1 . 24 1 . 29 94 113 119 1 26 132 1 40 71 82 85 89 93 97 Peak Load (Per Unit) Hot· Spot T5mp ( C) 1 .54 152 96 1.36 1.48 144 156 98 104 Top· Oil Temp tC ) t;j t:EJ t:EJ 0 c:: ..... 1 . 23 1 .31 137 147 98 103 1.12 1.21 128 138 94 100 t:I t:EJ "2j 0 � t" 0 > t:I Z (.) s::. .... Z 78 1.Q£ 1 . 05 1.13 1 . 20 1 20 1 29 1 38 90 95 1 00 0.99 1 . 04 1.10 1.16 1 .2 2 113 119 125 132 140 86 89 93 97 101 NOTE: Underlined values, though beyond recommended limits (see 5 .2.2.4 ), are given to assist in interpolation of the maximum limit. % loss of life is in addition to nonnal loss of life. '" Actual water temperature should be 5 °c lower than the ambient temperatures shown above (see 3.5), and must be above zero ° e. Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. t:EJ � > t;" 0 F � s:: tzJ � t:EJ t:I "1:1 0 � t."l � >-3 � > z 00 "1j 0 � Table 5(u) Capability Table for Nonnal and Moderate Sacrifice of Life 55 °c Rise Forced-Oil-Cooled ( Non-Directed Flow - FOA, FOW*, and OA/FOA/FOA) Transfonners Equivalent Load Before Peak Load 1 00% of Maximum Nameplate Rating = 10 0 Hours of Peak Load % Loss of Life Normal I 2 0.25 0.50 1 . 00 2.00 4.00 a 0 . 25 N or m l 1 m 0.50 1.00 2.00 4 . 00 Normal w 2 0.25 0.50 1 . 00 2.00 4.00 Normal 4 0.25 0.50 1 . 00 2 . 00 4.00 Normal 8 0.25 0.50 1 . 00 2 . 00 4.00 Normal 24 0.25 0.50 1 . 00 2 . 00 4.00 Peak Load er !lnit) HotSpot T�mp ( C) TopOil Temp (0C) Peak Load Per Jnit) HotSpot Temp (DC) 20 TopOil T�mp ( C) 1.88 2.10 1 39 162 -- 62 71 1.76 2.00 - � 68 77 1 . 68 1 . 88 132 156 67 79 1 . 58 1.79 - 72 84 - 137 130 155 is: Ambient °c tz:J 30 To y Oi T� mp ( C) 40 To y Oi T!5 mp ( C) Unit) HotS pot T�mp ( C) 1.61 1 . 89 1 33 lQQ. 73 83 1.06 1 . 77 99 157 68 88 1.44 1.70 125 154 75 88 1.03 1 .59 97 151 - 68 92 97 143 150 68 93 97 Peak Load (Per - Peak Load (P e r Unit) HotSpot Temp (DC) Peak Hot- Load (Per Unit) Spot Temp (DC) 1 . 59 151 � 00 50 To y Oi Temp ( C) 92 Peak Load Hot- Unit) Spot Temp ( C) 1.47 150 (Per TopOil Temp ee) 98 e:: "d >-3 0 ..... 0 0 is: <: > :::;:J ::3 1 .4 4 1 . 54 145 156 95 1 00 ::.: 1.31 1.49 142 160 99 !Ql 01 01 ° 0 0 � IS> 74 89 94 1 .23 1.41 1.46 1.52 110 135 142 150 71 86 90 95 1.02 1.33 1.38 1.45 1 .50 96 133 140 149 158 67 89 93 99 1 04 155 65 77 81 86 90 95 1.16 1 . 34 1 . 38 1 .44 1.49 1 .54 103 1 25 1 :3 2 1 39 147 155 67 81 85 89 94 99 1.01 1.25 1 . 30 1.36 1.41 1.47 95 124 131 1 38 146 1 54 95 113 1 19 1 26 133 1 40 59 69 73 77 82 86 1 .09 1.24 1.29 1 . 34 1.39 1 .4 4 95 113 119 1 26 133 140 63 73 77 81 85 89 1.00 1.16 1.21 1 . 27 1.31 1.37 95 113 119 1 26 132 1 39 73 86 91 1.31 1 . 53 1. 5 9 1.33 1.50 1.54 1.59 114 1 36 143 151 69 83 87 92 61 74 78 82 87 92 1.26 1.41 1.46 1.51 1.55 1.61 1 05 126 132 140 147 54 66 69 73 77 82 1.18 1.32 1.37 1.41 1.46 1.51 69 82 87 1.44 1.61 1.67 1.42 1.57 1.61 1.66 115 137 144 152 66 80 84 89 1.34 1.49 1.53 1.58 1.62 1.67 106 1 27 133 140 1 48 1 56 1.26 1.39 1.44 1.48 1.53 1.58 95 113 119 126 132 140 - 118 145 153 123 146 154 124 147 155 1.53 1 .69 1.74 1 .0 3 1 .44 1.50 - - 1 . 30 1 . 39 1.47 136 147 158 93 99 1 05 1.22 1. 34 137 151 98 106 1.21 1 .29 1.35 1 28 1 38 147 90 96 101 1.14 1 .25 130 143 95 103 67 84 88 92 97 1 .1 4 1 .21 1.27 1 . 34 120 1 29 137 145 86 91 96 101 1 . 09 1.17 1.25 124 1 34 144 92 98 104 67 77 81 85 89 93 1 . 08 1 .13 1.18 1.23 1 . 29 113 118 125 132 1 39 82 85 89 93 97 1 . 04 1 . 09 1 . 16 1.21 119 1 25 132 1 39 89 93 97 101 � NOTE: Underlined values, though beyond recommended limits (see 5 . 2 . 2 . 4 ), are given to assist in interpolation of the maximum limit. % loss of life is in addition to normal loss of life. • Actual water temperature should be 5 °c lower than the ambient temperatures shown above (see 3.5), and must be above zero D C . Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. "" ° 0 > <: tz:J � > C) tz:J -:::;:JZ 0 -Z C) � Ul trl 0 01 > :-> z "" -- co 00 . .... � co trl oo trl .... trl ANSI/IEEE C57.92-1981 IEEE GUIDE FOR LOADING MINERAL-OIL-IMMERSED POWER line so determined and the vertical line through the intersection of line for the desired time (2 h ) and time constant ( 3 . 5 h), determine the top-oil temperature rise ( 54 ° e) at the end of the short-time period (2 h). 6. Calculation of Temperature and Loss of Life for Short-Time Loads above Transformer Rating The calculations shown in this section are for 65 ° C rise transformers. These methods can be used for 5 5 ° C rise transformers. 6.3 Hottest-Spot Conductor Rise to Top Oil Gradient. On Fig 9(a), start at percent load ( 1 67%) on the horizontal scale and go up the curve for full-load hottest-spot conductor rise (30 o e). Go to the left and read hottest-spot conductor rise over top oil (68 ° C) for the short-time load. - 6.1 General. Short-time loads above the rating which use up different amounts of insulation life for transformers having the characteristics shown in Table 2 are given in Tables 3 (a)-3(u). Transformers which have other characteristics will have different load capabilities than those indicated in this guide. Section 6 gives informa­ tion from which similar values can be derived for those transformers. Where a graphical solution is desired, use may be made of Figs 6-9. As an example of the use of these figures, consider an OA transformer with a short-time load of 167% for 2 h follow­ ing a 33% load. Assumed transformer char­ acteristics at nameplate rating are : Ratio of losses (R) 3.2 Top-oil rise over ambient temperature at rated load 50 ° C Time constant 3.5 h Hottest-spot conductor rise over oil 30 ° C n (oil exponent) 0.8 m (winding exponent) 0.8 6.4 Hottest-Spot Conductor Temperature. Ob­ tain the hottest-spot conductor temperature by adding ambient temperature (30 ° e) , top-oil rise ( 54 ° C) and hottest-spot rise over top oil (68 ° e ) giving 1 5 2 ° C . 6.5 Percent Loss o f Life. From Fig 3, obtain the loss of life (0.19%) for the hottest-spot temperature ( 1 52 °e) and the duration of the load (2 h). In using this simplified procedure, it is assumed that the hottest-spot temperature is constant at its final value throughout the peak load period. When this assumption is made, the loss of life during the cooling period and during the period prior to the peak load can be ignored . This is only a convenient and sim­ plified procedure for approximating the loss o f life for short-time loading conditions. A more mathematically precise procedure was used in preparing the values in Tables 3(a)-3(u) and 5(a)-5(u), wherein a computer program used the 24 h hottest-spot conductor temperature profile developed from various two-step load cycles, the transformer characteristics and am­ bient temperatures shown in these tables. 6.2 Top-oil Rise Determination ( 1 ) On Fig 6(a), start at initial percent rating ( 33%) and move horizontally to the ratio of losses curve (R 3. 2). Go down to the line for full-load oil rise ( 50 ° C). Move horizontally to read initial oil rise ( 2 1 ° C). ( 2 ) Determine the ultimate top-oil temper­ ature rise for the short-time load ( 167%). On Fig 8(a), locate 167% on right side o f the graph and m ove horizontally across to the ratio of losses curve (R 3. 2). Move down to the fUll-load oil-rise curve (50 ° C). Move horizon­ tally and read the ultimate oil rise (99 ° C) at left of graph. (3) On Fig 7(a) , set a straight edge at the initial oil-temperature rise on the left scale (21 ° C) and at the ultimate top-oil rise on the right scale (99 ° C). At the intersection o f the 6.6 Method of C onverting Actual to Equivalent Load Cycle 6.6.1 Permissible loading as obtained from Tables 3(a)-3(u) and 5 (a)-5(u) is a function of the initial load and the peak load and their durations. Each loading combination in the tables is the result of a simple two-step load cycle consisting of a constant initial load of 50%, 70%, 90% or 1 00% of rating followed by a rectangular peak of the magnitude and duration given in the table. The assumed loading for the calculations in the tables is illustrated by Fig 10. 6.6.2 Ordinarily the daily load cycle is not so simple but is like the cycle represented by the solid line in Fig 1 1 consisting of load fluctua- = = 64 Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. TRANSFORMERS UP TO 100 MVA WITH 55 ° C OR 65 °c AVERAGE WINDING RISE 200 140 120 'BO 1--+-+-I--I-+�-+- +----j-+--T':.6.:l�-t--1 I---+--+--I---- +i-+--+- -+--+---+--,.ti,j�-I ! 100 - --t �2 160 1 10 1-- --+--+--+_+_ 1- 90 .... z .. 4 V -�6 8 "' .... V 70 1---+--+--- '¥I'-¥--+t-- +-+--o 60 40 f--+ ---t----I'--t-i; 30 ����-L-LL-�-L�L-�_�-L� O �� 100 1 1 0 90 80 70 o 10 20 30 40 60 50 / - 1 o V 120 1 10 90 - - .,.l-- I , , 54· ! I , , ! I , 1 'i<4&/' " �� ..... _ f:J� 0(, v� ' -�� ���;>--� I . 50 40 a WI � � I 60 'a r- - /': V"� ��JP I 70 t;cj . 1\, -f- '; ., o 30 I �� 10 f- .5' ...e% ���__f-" f::: ::= � Fi 100 1 1 0 90 80 70 60 50 40 PERCENT OF FULL-LOAD OIL RISE n = 1.0 180 f-- 2 f- f- • 1 60 140 1 20 100 Z " o IH / u "' '" B t- .... f- 1 20 I 130 140 V / Rj ;! 8 f- � 0 'a V / I BO o .. o � 6 g V - g � � g 0 0 6 6 - ( -t) l -e T V V ,./f-',..,.,..,.V /' V k.-" � / I /' 5V V 8 V/V ' '''- V/ V V Vj i I o � 6 I , f5 f2 � � g 0 16 2 / - I 2 /I j / + 20 '2 o ,/ 'V I i 40 / V // i I 60 a ;:::: f-I- .-f.I--' "/I--': .,- i <:> _ �\J" �� 20 VV -- -- - 2 'V 200 � � -T ! AfJ;11"/ I $/ V �V L�:::-/.W( ,j I.���..�-= � BO f--- 20 ! -- - - -- 100 30 - ! / .,-i-": VV V (a ) r--f-- / 1 1 1 (a) 130 y / t VALUE OF T IN 140 /" ....f.- I 2 6 o /" V Vvr. - o PERCENT OF FULL-LOAD OIL RISE ./ ,..,.- 5 /V 4 y,- VlJ - ./" 1 1 --- .- 7!" i' 40 20 V 2 j 80 50 .7 r- '- 10 100 - - -- 1 Hy' 120 - ,! 8 I---+- -+--f- -+ 80 140 - V 0 0 0 - " N g iil 8 888 N N rt'l 'Ct1n t VALUE OF T IN (b) (b) Fig 6 Initial Oil Rise Fig 7 Top-Oil Temperature at End of Specified Load �eriod 65 Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE C57 .92·1981 IEEE GUIDE FOR LOADING MINERAL·OIL·IMMERSED POWER 180 ,..--..--..-----.--..,.---.---...... � � �--+---�---+---4----r-� = 140 1--+---+----1I--+-I-� z o Q. 1 20 � 100 1--+---+---11-- lLI (f) a: I­ o Q. � I­ o :r 1---+--+--1--" � 140 1--+--�-_+--+_�� � 120 1--+---+---t--hH-l ::: '" � 100 w Ul 80 1--+--+--+ 40 120 80 160 200 PERCENT RATED kVA 80 1---+---+-----1 � '" 60 I---+---+_- � 40 1---+--+��f7��-� Q. '" w ... ... 40 1--+--�����4 1--+---+---t- it b -+-�"4-�.f-:If-��"""7I c:' 60 �-+- I­ (f) 160 � ..J 1--+---+----11---1 � a: lLI 180 r--'----,---,r---, o ���--�--� 240 40 120 80 160 200 PERCENT RATED kVA m = 0.8 m = 1 .0 (b) (a) Fig 9 Hottest-Spot Conductor To Top-Oil Gradient I�O 137% PEAK LOA D TRANSFORMER RATING 2 HOURS �% INITIAL LOAD O L-____L-____�_____�____� 12 6PM 12M 6AM 12 ASSUMED LOAD CYCLE Fig 1 0 Assumed Load Cycle 66 Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE C57.92-1 981 ° ° TRANSFORMERS UP TO 1 00 MVA WITH 5 5 C OR 65 C AVERAGE WINDING RISE I� o L-________�________�__________�________� 12 6 AM 6PM 12M 12 ACTUAL LOAD CYCLE Fig 1 1 Actual Load Cycle tions throughout the day. There is usually one period in the daily load cycle when the load builds up to a considerably greater value than any reached at other times. Generally, the maximum value or peak load is not reached and passed suddenly, but builds up and falls off gradually. 6.6.3 To use the loading recommendations, the actual fluctuating load cycle should be converted to a thermally equivalent two·step load cycle such as is represented by the dashed line in Fig 1 1 . A transformer supplying a fluctuating load generates a fluctuating loss, the effect of which is about the same as that of an intermediate load held constant for the same period of time. This is due to the heat storage characteristics of the materials in the transformer. A constant load which generates losses at the same rate as the average rate caused by the fluctuating load is an equivalent load from a temperature standpoint. Equiva· lent load for any part of a daily·load cycle may be expressed by Eq 2. Equivalent load or rms value ) L 1 2 t l + L2 2 t respective durations of these loads 6.6.4 Equivalent initial load is the rms load obtained by Eq 2 over a chosen period pre­ ceding the peak load. Experience with this method indicates that quite satisfactory results are obtained by considering only the 12 h period preceding the peak in determining the equivalent initial load. Time intervals ( t ) of 1 h are suggested as a further simplification of the equation which, for a 1 2 h period, becomes Eq 3. Equivalent initial load 0.29 . . etc = L2 2 + L3 2 + . . . LI 2 2 ( Eq 3 ) = average load by inspection for each 1 h interval of the 12 h period preced­ ing peak load 6.6.5 Equivalent peak load of a load cycle is the rms load obtained using Eq 2 for the limited period over which the major part of the actual irregular peak seems to exist. The estimated duration of the peak has consider­ able influence over the rms peak value. If the duration is overestimated, that is, if the time period to which Eq 2 is applied is too long, the rms peak value may be considerably below the maximum peak demand. To guard against ( Eq 2 ) where : LI , L , L3, 2 + L1 , L , . . . L12 2 = . tn LI 2 where : + L3 2 t3 + . . . Ln 2 tn 2 tl + t2 + t3 + J = various load steps in %, per unit, or in actual kV A or current 67 Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE C57 .92-1 981 IEEE GUIDE FOR LOADING MINERAL-OIL-IMMERSED POWER T() overheating due to brief, high loads during the thermal time constant of transformer for any load L and for any specific peak period, the rms value for the peak load period should not be less than 90% of the tem perature 6.6.6 The above method may be used to an convert To Th s continuous part is 7 0% and the peak 1 4 0% of rated load. Table 3(b) shows that in a 30 D C = C (8 u - 8 i ) /P hottest-spot time constant P ambient temperature the permissible 1 h load change in total loss in watts due to change in load 70% load is 1 7 2%, therefore, the transformer between initial top-oil rise, or irregular load cycle as shown in Fig 11 to a two-step load cycle . In this case the following differential the ultimate top-oil rise and the integrated h alf-hour maximum demand. can carry this load cycle daily time Tr without sacrifice of normal life expectancy. constant of transformer temperature rise of zero D C 6.7 Equations for Calculating Transient Heat­ ing of Oil-Immersed Transformers 6.7 . 1 General. The loading tables in this P{l total loss in watts at rated load C thermal guide are based on average characteristics of a capacity of transformer (Wh t c ) wide range of transformer ratings. Tables 2 and 4 give the characteristics used in calculating the 6 .7.3 Temperature De termination Equations loadings in the Tables 3(a)-3 (u) and 5(a)- 5(u). When the characteristics of a particular Hottest-spot temperature : transformer vary appreciably from those in the (Eq 4 ) tables or when more accurate loading capa­ bilities are desired, the basic equation s in this section may be used. List 6.7.2 Transient heating equation for top-oil rise over ambient temperature : of Symbols. Unless otherwise expressed, all temperatures are in D C and all 80 times are in hours. 8a ambient temperature 8g 8g (fl) 8 hs = (8u - 8d + 8i (1 - e ;t� ( Eq 5 ) Ultimate top-oil rise for load L : hottest-spot conductor rise over top- 8u oil tern perature = = 8 hottest-spot conductor rise over top­ oil temperature at rated load f(K2 R + 1 L (R + 1 ) {l l] n ( Eq 6 ) Ultimate hottest-spot conductor rise over top­ oil for load L : hottest-spot winding temperature ( Eq 7 ) top-oil rise over ambient temperature 8g (fl) top-oil rise over ambient temperature at rated load initial top-oil rise for t K L = under consideration, rise over top oil6 any n units R ratio of load loss at rated load to e 2 . 7 1 8 2 8 (base of natural logarithm) t duration of load in hours 1 5 °C7 ( Eq 8 ) FOA, FOW, OA/FAj 1.0 for directed flow FOA, FOW = n + FOA, OA/FOA/FOA m in average conductor non-directed L ratio of load L to rated load load = 0.8 for OA, OA/ F A, OA/F A / FA and m 0 ultimate top-oil rise for load for rated load beginning with initial 0.8 for OA 0.9 for OA/F A, OA/F A/F A 6 At rated kV A from manufacturer's test. Hottest.spot conductor rise over averagl' con­ ° ° ductor rise is assumed to be 1 5 C for 65 c rise ° ° transformer, 1 0 C for 55 c rise transformers. (Values are usually lower than the 15 ° C and 10 0 C, but may be higher for a few designs). 7 no-load loss 68 Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. TRANSFORMERS UP TO 100 MVA WITH n = n = m 55 ° C OR 6 5 °c AVERAGE WINDING RISE ature rise and ultimate temperature rise. If n is not unity , the percentage varies and is a func­ tion of both i nitial temperature rise and ultimate temperature rise . In particular, if n equals 0 . 8 , the percentage of 67 if the initial temperature rise is zero . If the initial temperature rise is greater than zero, the percentage is lower than 67 and decreases as the initial temperature rise ap­ proaches a given ultimate temperature rise. If the initial temperature is approximately equal to the final temperature, whether just above or just below it, the percentage is approximately 63. If the initial temperature is greater than the ultim ate temperature, the percentage is less than 6 3 . Since evaluation of the exact percentage for cases where n is not unity and where the initial temperature rise is not zero becomes very laborious, it is frequently advisable to use the approximate value of 63%. In the more fre­ quently encountered cases where n is approxi­ mately 0.8, the error resulting from this procedure is not large compared to the ex­ pected error in input data. If n 1.0, Eq 9 is correct for any load and any starting temperature . If n or m is less than 1 .0 , Eq 9 holds only for full-rating starting cold . If n is less than 1 , the time constant for any load and for any starting temperature for either a heating cycle or cooling cycle is given in Eqs 10 and 1 1 . 1.0 for FOA, FOW, OA/F A/FDA, OAf FOA/FOA the exponential power of total loss versus top-oil temperature rise the exponential power of winding loss versus winding temperature rise Time constant at rated kVA : _ Tr - C8 n p n ( Eq 9) For non-directed flow transformers : C = ANSI/IEEE C57.92-1981 0.06 (weight of core and coil assembly in pounds) + 0 . 04 ( weight of tank and fittings in pounds) + 1.33 (gal­ lons of oil) For directed flow transformers : C 0 .06 (weight of core and coil assembly in pounds) + 0 .0 6 (weight of tank and fittings in pounds) + 1.93 (gallons of oil) 6.7.4 Equation Corrections. Theoretically, several corrections should be made when using the foregoing equations in calculating transient oil rises, such as corrections for change in : ( 1 ) Time constant for load above rating ( 2 ) Ultimate conductor loss at end of load period ( 3 ) Oil viscosity In making general calculations based on assumptions of transformer characteristics and maximum hottest-spot conductor temperatures which generally have a large factor of safety, results close enough for all practical purposes are obtained if all of these corrections are omitted, and the simpler formulas are used. Using these corrections implies greater ac­ curacy than is present in the basic data, therefore the load values shown in Tables 3(a)-3(u) and 5(a)-5(u) were calculated using the equations without corrections. 6.7.5 Time Constant. The time constant is the length of time which would be required for the temperature of the oil to change from initial value to the ultimate value if the initial rate of change were continued until the ulti­ mate temperature was reached. If n (the exponential power of total loss versus top-oil temperature rise ) equals unity , 63% of the temperature change occurs in a length of time equal to the time constant regardless of the relationship of initial temper= = ( Eq 10) If starting cold, as 8 ; = (1 _ ! ) n 0, Eq 10 reduces to : ( Eq 1 1 ) 6.7.6 Winding Loss ( Load Loss ) . As the resistance of the winding for ultimate condi­ tions is greater when the temperature is greater for loads above rating than it is for rated load conditions, a resistance correction factor may be applied to Eqs 6 and 7 . The correction factor is a multiplier to be applied to the K2 in each equation to reflect the change in winding loss due to the increase in winding resistance. 69 Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE IEEE GUIDE FOR LOADING MINERAL·OIL-IMMERSED POWER C57.92-1981 The values of the exponents, m and n, used in top-oil rise, hottest-spot rise, and time con­ ance corrections are applied . The manufacturer constants stant, all at rated load), (2) the aging curve the equation may not be correct when resist­ should be consulted when such corrections are for the insulation system (from Fig 1 ) , ( 3) ambient temperatures, ( 4 ) initial to be included. continuous load, ( 5 ) peak load durations and the specified daily percent loss of life. 6.7.7 Viscosity of Oil. The ultimate temper­ The loss of life indicated in the tables is ature rise of oil for a constant heat input decreases slightly as the temperature of the oil based on a 24 h load cycle. For 65 °c units it is increases. This is due to a decrease in the the loss in excess of the 0.0369% per day to offset the effect of increased resistance. For 55 ° C units it is the loss in excess of the viscosity of the oil. The viscosity change tends produced by continuous operation at 1 1 0 ° c. 0. 0369% per day operation at 95 ° C. produced by continuous A systematic convergence process is used to 7. Method Used for Computer Calculation obtain the highest of Loading Capability Tables allowable peak load. An initial trial is made with an assumed peak load midway between the minimum (continuous) The methods and calculations described in load and the maximum permitted peak load 6.6.3 through 6 . 7 . 5 were used in developing a (200%). Using this peak load, aging calculations computer program designed to provide more are made at varying time intervals (depending 5(a)-5(u) than would be possible using the the 24 h, to determine the total daily insula­ accurate values for Tables 3(a)-3(u) and on the time duration of the peak load) during hand method covered in 6 . 2 - 6 . 5 of this tion guide. See ANSI/IEEE C57.91- 1 9 81 [ 4 ] for a aging, imposed by the load cycle. A comparison is made between the calculated and more complete explanation of the computer the specified percent loss of life. program . Depending on the results the peak value is changed and the calculation repeated until the The program computes and prints the max­ calculated value of total percent loss of life is power transformer and meet specified loss of the peak load and corresponding values of peak within ±4% of the desired value. At this point imum peak load that can be impressed on a life limitations within a ±4% tolerance . hottest-spot temperature, peak top-oil temper­ ing: ( 1 ) transformer characteristics (loss ratio, specified percent loss of life are printed out. Input to the program consists of the follow­ ature, total percent loss of life, and the 70 Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply. Appendix (Th is Appendix is not a p art of ANSI/IEEE C 5 7 .92-1 981 , IEEE Gu ide for Loading Mineral-O il-Immersed Power Transformers Up To and Including 1 00 mVA with 5 5 ° C or 65 ° c Average Wind ing Rise . ) Unusual Temperature and Altitude Conditions Table Al Maximwn Allowable Average Temperature. of Cooling Air for Carrying Rated kVA 3000 � (9900 Feet) 4 000 Meters ( 13 200 Feet) Method of Cooling Apparatus 1 000 Meters (3300 Feet ) 2 000 Meters (6600 Feet) Liquid -Immersed Self-Cooled 30 28 25 23 Liqui d-Immersed Forced-Air-Cooled 30 26 23 20 Liquid-Immersed Forced-Oil-Cooled with O il-to -Air Cooler 30 26 23 20 Degrees C * It is recommended that the average temperature o f the cooling a ir be calculated by averaging 24 consecutive hourly read ings. When the outdoor air is the cooling me dium, the average of the maximum and minimum daily temperatures may be used. The value o btained in this manner is usually sl ightly h igher, b y not more th an 0 . 3 °C, than the true daily average. At . Unusual Temperatures and Altitude NOTES: ( 1) See ANSI/IEEE C57.1 2.00- 1 98 0, 4 . 3 . 2 for transformer insul ation capability at altitudes a bove 3300 ft ( 1 000 m). ( 2 ) Operation in low ambient temperature with the top liquid at a temperature lower th an -20 ° C may reduce dielectric strength between internal energized components below design levels. Service Conditions Transformers may be applied at higher ambi­ ent temperatures or at higher altitudes than specified in ANSI C57.12 .00-1980, but perfor­ mance may be affected and special considera­ tion should be given to these applications. A4. Operation at Less than Rated kVA Transformers may be operated at altitudes greater than 3300 ft ( 1 000 m) without exceed­ ing temperature limits, provided the load to be carried is reduced below rating by the percen­ tages given in Table A2 for each 330 ft ( 1 00 m ) that the altitude i s above 3300 ft (1000 m ) . A2. Effect of Altitude on Temperature Rise The effect of the decreased air density due to high altitude is to increase the temperature rise of transformers since they are dependent upon air for the dissipation of heat losses. Table A2 Rated kVA Correction Factors for Altitudes Greater than 3300 ft (1000 m ) A3. Operation at Rated kVA Types af Cool ing Derating Factor (% ) Liquid-immersed air-cooled 0.4 Transformers may be operated at rated kVA at altitudes greater than 3300 ft ( 1000 m) with­ Liquid-immersed water-cooled 0.0 Liqu id-immersed forced-air-cooled 0.5 out exceeding temperature limits, provided the average temperature of the cooling air does Liquid·immersed forced -l iquid-cooled with l iquid·to-a ir cooler 0.5 not exceed the values of Table Al for the re­ spective altitudes. Liquid-immersed forced -liquid -cooled with I iqu id·to-water cooler 0.0 71 Authorized licensed use limited to: UNIVERSITY OF CONNECTICUT. Downloaded on June 26,2014 at 21:59:20 UTC from IEEE Xplore. Restrictions apply.