Uploaded by hai Tes

ElectromagChecklist

advertisement
ELECTROMAGNETIC LOCKS CHECKLIST
For compliance with Sentence 3.4.6.16.(4) of the MBC
Project Address: ______________________________________ Building Permit #: ______________
Completed by: _________________________________
Company: _________________________
Phone: __________________________
Qty. of Mag. Lock Locations for this Project: _______
1. Requirements For All Installations (except portions of Group B2 Occupancies where
unrestricted egress may compromise patient safety)
Electromagnetic locks are not installed on doors leading from F1 occupancy, 3.4.6.16.(4).
Building is equipped with a fire alarm system, 3.4.6.16.(4)(a) .............................................
Electromagnetic locks release on fire alarm signal, 3.4.6.16.(4)(b) ......................................
Electromagnetic locks release on power failure to locking mechanisms, 3.4.6.16.(4)(c) .....
A single manual switch is provided to release all locks in the building, 3.4.6.16.(4)(d) ......
Specify location ________________________________________________________
Switch is existing
or new*
Switch is accessible only to authorized persons ................................................
A single manual switch is provided to reset all electromagnetic locks in the building,
3.4.6.16.(4)(f) ........................................................................................................................
When released on emergency condition, electromagnetic locks are reset by the manual
switch only (not automatic), 3.4.6.16.(4)(f) ..........................................................................
Local Lock Release – Hardware Release (time delay):
Door releases within 15 seconds of 90 N of pressure being applied to the opening
hardware, 3.4.6.16.(4)(e) ................................................................................................
Upon initiation, opening process is irreversible; constant pressure on the opening
hardware is not required, 3.4.6.16.(4)(e) ........................................................................
Door does not re-lock until opened, 3.4.6.16.(4)(e) .......................................................
Sign posted on door indicating that the door will open within 15 seconds,
3.4.6.16.(4)(g) .................................................................................................................
*
If a new switch is to be provided in an existing building, confirm that all existing electromagnetic locks in the
building will be controlled by it.
1-Apr-2011
-2-
2. Requirements for portions of Group B2 Occupancies where unrestricted egress may
compromise patient safety
Building is equipped with a fire alarm system, 3.4.6.16.(4)(a) .............................................
Electromagnetic locks release on a fire alarm signal, 3.4.6.16.(4)(b) ...................................
Electromagnetic locks release on power failure to locking mechanisms, 3.4.6.16.(4)(c) .....
Single manual switch is provided to release all locks, 3.4.6.16.(4)(d) ..................................
Specify location _______________________________________________________
Switch is existing
or new*
Switch is accessible only to authorized persons .....................................
3. Electrical Code Requirements
Wiring methods suitable for Class 1 circuit (Rule 16-010)...................................................
Conductors extending from the fire alarm system comply with Rule 32-102 ......................
4. Fire Alarm System Verification (to be completed by inspector upon receipt of VI report)
Connections to fire alarm system verified.............................................................................
Release on signal from fire alarm system verified ................................................................
*
If a new switch is to be provided in an existing building, confirm that all existing electromagnetic locks in the
building will be controlled by it.
Personal information is collected under the authority of The City of Winnipeg Charter Act, and is used for the administration and enforcement of The City of Winnipeg
Building By-law No. 4555/87. This information will be disclosed publicly in accordance with the disclosure provisions of the Province of Manitoba - Freedom of
Information and Protection of Privacy Act. If you have questions about the collection, use, or disclosure of your information, contact the Corporate FIPPA Coordinator:
by mail to the City Clerk’s Department, Administration Building, 510 Main Street, Winnipeg, MB, R3B 1B9; by telephone to 311; or by email to FIPPA@winnipeg.ca.
Fax completed form to Electrical Plan Examination at 986-3045
1-Apr-2011
Download