Amendment 1 IEEE Power and Energy Society STANDARDS IEEE Guide for the Application of Capacitance Current Switching for AC High-Voltage Circuit Breakers Above 1000 V Developed by the Switchgear Committee IEEE Std C37.012a™-2020 (Amendment to IEEE Std C37.012-2014) Authorized licensed use limited to: University of Liverpool. Downloaded on September 29,2021 at 11:12:11 UTC from IEEE Xplore. Restrictions apply. IEEE Std C37.012a™-2020 (Amendment to IEEE Std C37.012-2014) IEEE Guide for the Application of Capacitance Current Switching for AC High-Voltage Circuit Breakers Above 1000 V Amendment 1 Developed by the Switchgear Committee of the IEEE Power and Energy Society Approved 4 June 2020 IEEE SA Standards Board Authorized licensed use limited to: University of Liverpool. Downloaded on September 29,2021 at 11:12:11 UTC from IEEE Xplore. Restrictions apply. IEEE Std C37.012a™-2020 (Amendment to IEEE Std C37.012-2014) Abstract: Covered in this amendment are changes in di/dt limitations for non-oil circuit breakers. A section has been added describing possible delayed current zeros when doing a rapid close— open of a line circuit breaker (CO) when shunt reactors are connected to a line or cable. Some minor errors have been corrected and references have been updated. Keywords: capacitive current switching, circuit breaker capacitive inrush/outrush limitations, IEEE C37.012a, switching reactor compensated lines • The Institute of Electrical and Electronics Engineers, Inc. 3 Park Avenue, New York, NY 10016-5997, USA Copyright © 2020 by The Institute of Electrical and Electronics Engineers, Inc. All rights reserved. Published 7 August 2020. Printed in the United States of America. IEEE is a registered trademark in the U.S. Patent & Trademark Office, owned by The Institute of Electrical and Electronics Engineers, Incorporated. PDF: Print: ISBN 978-1-5044-6762-9 ISBN 978-1-5044-6763-6 STD24217 STDPD24217 IEEE prohibits discrimination, harassment and bullying. For more information, visit http://www.ieee.org/web/aboutus/whatis/policies/p9-26.html. No part of this publication may be reproduced in any form, in an electronic retrieval system or otherwise, without the prior written permission of the publisher. Authorized licensed use limited to: University of Liverpool. Downloaded on September 29,2021 at 11:12:11 UTC from IEEE Xplore. Restrictions apply. IEEE Std C37.012a™-2020 (Amendment to IEEE Std C37.012-2014) Important Notices and Disclaimers Concerning IEEE Standards Documents IEEE Standards documents are made available for use subject to important notices and legal disclaimers. These notices and disclaimers, or a reference to this page (https://standards.ieee.org/ipr/disclaimers.html), appear in all standards and may be found under the heading “Important Notices and Disclaimers Concerning IEEE Standards Documents.” Notice and Disclaimer of Liability Concerning the Use of IEEE Standards Documents IEEE Standards documents are developed within the IEEE Societies and the Standards Coordinating Committees of the IEEE Standards Association (IEEE SA) Standards Board. IEEE develops its standards through an accredited consensus development process, which brings together volunteers representing varied viewpoints and interests to achieve the final product. IEEE Standards are documents developed by volunteers with scientific, academic, and industry-based expertise in technical working groups. Volunteers are not necessarily members of IEEE or IEEE SA, and participate without compensation from IEEE. While IEEE administers the process and establishes rules to promote fairness in the consensus development process, IEEE does not independently evaluate, test, or verify the accuracy of any of the information or the soundness of any judgments contained in its standards. IEEE does not warrant or represent the accuracy or completeness of the material contained in its standards, and expressly disclaims all warranties (express, implied and statutory) not included in this or any other document relating to the standard, including, but not limited to, the warranties of: merchantability; fitness for a particular purpose; non-infringement; and quality, accuracy, effectiveness, currency, or completeness of material. In addition, IEEE disclaims any and all conditions relating to results and workmanlike effort. In addition, IEEE does not warrant or represent that the use of the material contained in its standards is free from patent infringement. IEEE Standards documents are supplied “AS IS” and “WITH ALL FAULTS.” Use of an IEEE standard is wholly voluntary. The existence of an IEEE Standard does not imply that there are no other ways to produce, test, measure, purchase, market, or provide other goods and services related to the scope of the IEEE standard. Furthermore, the viewpoint expressed at the time a standard is approved and issued is subject to change brought about through developments in the state of the art and comments received from users of the standard. In publishing and making its standards available, IEEE is not suggesting or rendering professional or other services for, or on behalf of, any person or entity, nor is IEEE undertaking to perform any duty owed by any other person or entity to another. Any person utilizing any IEEE Standards document, should rely upon his or her own independent judgment in the exercise of reasonable care in any given circumstances or, as appropriate, seek the advice of a competent professional in determining the appropriateness of a given IEEE standard. IN NO EVENT SHALL IEEE BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL, EXEMPLARY, OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO: THE NEED TO PROCURE SUBSTITUTE GOODS OR SERVICES; LOSS OF USE, DATA, OR PROFITS; OR BUSINESS INTERRUPTION) HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY, WHETHER IN CONTRACT, STRICT LIABILITY, OR TORT (INCLUDING NEGLIGENCE OR OTHERWISE) ARISING IN ANY WAY OUT OF THE PUBLICATION, USE OF, OR RELIANCE UPON ANY STANDARD, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE AND REGARDLESS OF WHETHER SUCH DAMAGE WAS FORESEEABLE. Authorized licensed use limited to: University of Liverpool. Downloaded on September 29,2021 at 11:12:11 UTC from IEEE Xplore. Restrictions apply. IEEE Std C37.012a™-2020 (Amendment to IEEE Std C37.012-2014) Translations The IEEE consensus development process involves the review of documents in English only. In the event that an IEEE standard is translated, only the English version published by IEEE is the approved IEEE standard. Official statements A statement, written or oral, that is not processed in accordance with the IEEE SA Standards Board Operations Manual shall not be considered or inferred to be the official position of IEEE or any of its committees and shall not be considered to be, nor be relied upon as, a formal position of IEEE. At lectures, symposia, seminars, or educational courses, an individual presenting information on IEEE standards shall make it clear that the presenter’s views should be considered the personal views of that individual rather than the formal position of IEEE, IEEE SA, the Standards Committee, or the Working Group. Comments on standards Comments for revision of IEEE Standards documents are welcome from any interested party, regardless of membership affiliation with IEEE or IEEE SA. However, IEEE does not provide interpretations, consulting information, or advice pertaining to IEEE Standards documents. Suggestions for changes in documents should be in the form of a proposed change of text, together with appropriate supporting comments. Since IEEE standards represent a consensus of concerned interests, it is important that any responses to comments and questions also receive the concurrence of a balance of interests. For this reason, IEEE and the members of its Societies and Standards Coordinating Committees are not able to provide an instant response to comments, or questions except in those cases where the matter has previously been addressed. For the same reason, IEEE does not respond to interpretation requests. Any person who would like to participate in evaluating comments or in revisions to an IEEE standard is welcome to join the relevant IEEE working group. You can indicate interest in a working group using the Interests tab in the Manage Profile & Interests area of the IEEE SA myProject system. An IEEE Account is needed to access the application. Comments on standards should be submitted using the Contact Us form. Laws and regulations Users of IEEE Standards documents should consult all applicable laws and regulations. Compliance with the provisions of any IEEE Standards document does not constitute compliance to any applicable regulatory requirements. Implementers of the standard are responsible for observing or referring to the applicable regulatory requirements. IEEE does not, by the publication of its standards, intend to urge action that is not in compliance with applicable laws, and these documents may not be construed as doing so. Data privacy Users of IEEE Standards documents should evaluate the standards for considerations of data privacy and data ownership in the context of assessing and using the standards in compliance with applicable laws and regulations. Authorized licensed use limited to: University of Liverpool. Downloaded on September 29,2021 at 11:12:11 UTC from IEEE Xplore. Restrictions apply. IEEE Std C37.012a™-2020 (Amendment to IEEE Std C37.012-2014) Copyrights IEEE draft and approved standards are copyrighted by IEEE under US and international copyright laws. They are made available by IEEE and are adopted for a wide variety of both public and private uses. These include both use, by reference, in laws and regulations, and use in private self-regulation, standardization, and the promotion of engineering practices and methods. By making these documents available for use and adoption by public authorities and private users, IEEE does not waive any rights in copyright to the documents. Photocopies Subject to payment of the appropriate licensing fees, IEEE will grant users a limited, non-exclusive license to photocopy portions of any individual standard for company or organizational internal use or individual, non-commercial use only. To arrange for payment of licensing fees, please contact Copyright Clearance Center, Customer Service, 222 Rosewood Drive, Danvers, MA 01923 USA; +1 978 750 8400; https://www.copyright.com/. Permission to photocopy portions of any individual standard for educational classroom use can also be obtained through the Copyright Clearance Center. Updating of IEEE Standards documents Users of IEEE Standards documents should be aware that these documents may be superseded at any time by the issuance of new editions or may be amended from time to time through the issuance of amendments, corrigenda, or errata. An official IEEE document at any point in time consists of the current edition of the document together with any amendments, corrigenda, or errata then in effect. Every IEEE standard is subjected to review at least every 10 years. When a document is more than 10 years old and has not undergone a revision process, it is reasonable to conclude that its contents, although still of some value, do not wholly reflect the present state of the art. Users are cautioned to check to determine that they have the latest edition of any IEEE standard. In order to determine whether a given document is the current edition and whether it has been amended through the issuance of amendments, corrigenda, or errata, visit IEEE Xplore or contact IEEE. For more information about the IEEE SA or IEEE’s standards development process, visit the IEEE SA Website. Errata Errata, if any, for all IEEE standards can be accessed on the IEEE SA Website. Search for standard number and year of approval to access the web page of the published standard. Errata links are located under the Additional Resources Details section. Errata are also available in IEEE Xplore. Users are encouraged to periodically check for errata. Authorized licensed use limited to: University of Liverpool. Downloaded on September 29,2021 at 11:12:11 UTC from IEEE Xplore. Restrictions apply. IEEE Std C37.012a™-2020 (Amendment to IEEE Std C37.012-2014) Patents IEEE Standards are developed in compliance with the IEEE SA Patent Policy. Attention is called to the possibility that implementation of this standard may require use of subject matter covered by patent rights. By publication of this standard, no position is taken by the IEEE with respect to the existence or validity of any patent rights in connection therewith. If a patent holder or patent applicant has filed a statement of assurance via an Accepted Letter of Assurance, then the statement is listed on the IEEE SA Website at https://standards.ieee.org/about/sasb/patcom/patents.html. Letters of Assurance may indicate whether the Submitter is willing or unwilling to grant licenses under patent rights without compensation or under reasonable rates, with reasonable terms and conditions that are demonstrably free of any unfair discrimination to applicants desiring to obtain such licenses. Essential Patent Claims may exist for which a Letter of Assurance has not been received. The IEEE is not responsible for identifying Essential Patent Claims for which a license may be required, for conducting inquiries into the legal validity or scope of Patents Claims, or determining whether any licensing terms or conditions provided in connection with submission of a Letter of Assurance, if any, or in any licensing agreements are reasonable or non-discriminatory. Users of this standard are expressly advised that determination of the validity of any patent rights, and the risk of infringement of such rights, is entirely their own responsibility. Further information may be obtained from the IEEE Standards Association. IMPORTANT NOTICE IEEE Standards do not guarantee or ensure safety, security, health, or environmental protection, or ensure against interference with or from other devices or networks. IEEE Standards development activities consider research and information presented to the standards development group in developing any safety recommendations. Other information about safety practices, changes in technology or technology implementation, or impact by peripheral systems also may be pertinent to safety considerations during implementation of the standard. Implementers and users of IEEE Standards documents are responsible for determining and complying with all appropriate safety, security, environmental, health, and interference protection practices and all applicable laws and regulations. Authorized licensed use limited to: University of Liverpool. Downloaded on September 29,2021 at 11:12:11 UTC from IEEE Xplore. Restrictions apply. IEEE Std C37.012a™-2020 (Amendment to IEEE Std C37.012-2014) Participants At the time this draft guide was completed, the C37.012a Working Group had the following membership: Roy Alexander, Chair Brian Roberts, Vice Chair Lucas Collette, Secretary Anne Bosma Arben Bufi David Caverly Michael Christian Jason Cunningham Raymond Frazier John Hall Helmut Heiermeier Victor Hermosillo Edward Hester Roy Hutchins Hua Ying Liu Steven May Neil McCord Dave Mitchell Craig Polchinski Jon Rogers Carl Schuetz Sushil Shinde Michael Skidmore James van de Ligt John Webb Casey Weeks Jan Weisker Marcus Young Wei Zhang Jim Zhong The following members of the individual Standards Association balloting group voted on this guide. Balloters may have voted for approval, disapproval, or abstention. Roy Alexander Thomas Barnes Anne Bosma Demetrio Bucaneg Jr. Arben Bufi Ted Burse Eldridge Byron Paul Cardinal Steven Chen Lucas Collette Sergio Flores Edwin Goodwin Lou Grahor John Hall John Harley Helmut Heiermeier Victor Hermosillo Werner Hoelzl Robert Hoerauf Todd Irwin Richard Jackson Joseph Jasinski Laszlo Kadar Thomas Keels Peter Kelly Yuri Khersonsky James Kinney Boris Kogan Jim Kulchisky R. Long Omar Mazzoni Neil McCord Charles Morse Thomas Mulcahy Dennis Neitzel Arthur Neubauer Joe Nims Mary Owens Bansi Patel John Phouminh Reynaldo Ramos Samala Santosh Reddy Charles Rogers Surya Santoso Bartien Sayogo Daniel Schiffbauer Carl Schuetz Nikunj Shah Devki Sharma Michael Sharp Sushil Shinde Gary Smullin Jon Spencer Gary Stoedter Donald Swing James van de Ligt John Vergis Keith Waters John Webb Jan Weisker Terry Woodyard Jian Yu Wei Zhang Xi Zhu Authorized licensed use limited to: University of Liverpool. Downloaded on September 29,2021 at 11:12:11 UTC from IEEE Xplore. Restrictions apply. IEEE Std C37.012a™-2020 (Amendment to IEEE Std C37.012-2014) When the IEEE SA Standards Board approved this guide on 4 June 2020, it had the following membership: Gary Hoffman, Chair Jon Walter Rosdahl, Vice Chair Jean-Philippe Faure, Past Chair Konstantinos Karachalios, Secretary Ted Burse J. Travis Griffith Grace Gu Guido R. Hiertz Joseph L. Koepfinger* John D. Kulick David J. Law Howard Li Dong Liu Kevin Lu Paul Nikolich Damir Novosel Dorothy Stanley Mehmet Ulema Lei Wang Sha Wei Philip B. Winston Daidi Zhong Jingyi Zhou *Member Emeritus Authorized licensed use limited to: University of Liverpool. Downloaded on September 29,2021 at 11:12:11 UTC from IEEE Xplore. Restrictions apply. IEEE Std C37.012a™-2020 (Amendment to IEEE Std C37.012-2014) Introduction This introduction is not part of IEEE Std C37.012a-2020, IEEE Guide for the Application of Capacitance Current Switching for AC High-Voltage Circuit Breakers Above 1000 V. Recent work has demonstrated that for vacuum, SF6 and other gas switchgear, the inrush current frequency on capacitor energization or restrike is much less important than the current magnitude and often does not need to be limited. Also, the inrush current magnitude alone may not need to be limited. The limiting parameter is the ICI (Inrush Current Integral) during the pre-arc time of a making operation, before galvanic contact of the contacts is achieved. As a result, the formerly used i × f product (or di/dt) as a limitation for switchgear is less of a concern. Therefore, IEEE Std C37.012 has been amended to provide guidance in applications where the formerly used i × f limitation is exceeded. At this time, it is deemed appropriate to retain the inrush current magnitude limits with less emphasis on the importance of the natural frequency of the inrush current until such time as the impact of the ICI is better understood and reducible to an easily computed form suitable for an application guide. Also, a few other corrections have been addressed (i.e., Ferranti rise numbers, added clauses on reactor compensated lines and cables, delayed current zero possibility, and the discharge capability of capacitor units with no internal fuses, etc.). References have been updated, and IEEE Std C37.100.2 was added to the normative references. 7 Copyright © 2020 IEEE. All rights reserved. Authorized licensed use limited to: University of Liverpool. Downloaded on September 29,2021 at 11:12:11 UTC from IEEE Xplore. Restrictions apply. IEEE Std C37.012a™-2020 (Amendment to IEEE Std C37.012-2014) Contents 2. Normative references.................................................................................................................................. 9 4. Capacitor bank switching ..........................................................................................................................10 4.3 Energizing capacitor banks .................................................................................................................10 5. Unloaded cable switching ..........................................................................................................................11 5.2 De-energizing unloaded cables ...........................................................................................................11 5.3 Energizing unloaded cables ................................................................................................................11 6. Switching of no-load transmission lines ....................................................................................................11 6.1 De-energizing uncompensated transmission lines ..............................................................................11 6.4 Switching the charging current of long transmission lines .................................................................12 6.5 Switching of reactor compensated lines and cables ............................................................................12 7. Voltage factors for capacitive current switching tests ...............................................................................12 8. General application considerations ............................................................................................................12 9. Capacitance current switching application considerations ........................................................................12 9.1 General ...............................................................................................................................................12 9.4 Rated capacitive current .....................................................................................................................13 9.5 Voltage and grounding conditions of the network ..............................................................................13 9.6 Restrike probability ............................................................................................................................13 9.7 Class of circuit breaker .......................................................................................................................14 9.10 No-load transmission lines ...............................................................................................................15 9.11 Capacitor banks ................................................................................................................................16 9.12 Insulated cables.................................................................................................................................21 9.14 Unusual circuits ................................................................................................................................22 10. Considerations of capacitive currents and recovery voltages under fault conditions ..............................23 10.1 Voltage and current factors ...............................................................................................................23 10.4 Switching transmission lines under faulted conditions .....................................................................23 10.5 Switching capacitor banks under faulted conditions.........................................................................23 10.7 Examples of application alternatives ................................................................................................24 Annex A (informative) Bibliography ............................................................................................................25 8 Copyright © 2020 IEEE. All rights reserved. Authorized licensed use limited to: University of Liverpool. Downloaded on September 29,2021 at 11:12:11 UTC from IEEE Xplore. Restrictions apply. IEEE Std C37.012a-2020 IEEE Guide for the Application of Capacitance Current Switching for AC High-Voltage Circuit Breakers Above 1000 V Amendment 1 IEEE Guide for the Application of Capacitance Current Switching for AC High-Voltage Circuit Breakers Above 1000 V Amendment 1 NOTE—The editing instructions contained in this amendment define how to merge the material contained therein into the existing base standard and its amendments to form the comprehensive standard. The editing instructions are shown in bold italic. Four editing instructions are used: change, delete, insert, and replace. Change is used to make corrections in existing text or tables. The editing instruction specifies the location of the change and describes what is being changed by using strikethrough (to remove old material) and underscore (to add new material). Delete removes existing material. Insert adds new material without disturbing the existing material. Insertions may require renumbering. If so, renumbering instructions are given in the editing instruction. Replace is used to make large changes in text, subclauses, tables, figures, or equations by removing the existing material and replacing it with new material. Editing instructions, change markings, and this NOTE will not be carried over into future editions because the changes will be incorporated into the base standard. 2. Normative references Change the following references in Clause 2: IEEE Std C37.04™, IEEE Standard Rating Structure for AC High-Voltage Circuit Breakers for Ratings and Requirements for AC High-Voltage Circuit Breakers with Rated Maximum Voltage Above 1000 V.2,3 IEEE Std C37.09a™-2005, IEEE Standard Test Procedures for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis — Amendment 1: Capacitance Current Switching with Rated Maximum Voltage Above 1000 V. IEEE Std C37.010™, IEEE Application Guide for AC High-Voltage Circuit Breakers > 1000 Vac Rated on a Symmetrical Current Basis. Delete the following references in Clause 2: IEEE Std C37.04a™-2003, IEEE Standard Rating Structure for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis Amendment 1: Capacitance Current Switching. 9 Copyright © 2020 IEEE. All rights reserved. Authorized licensed use limited to: University of Liverpool. Downloaded on September 29,2021 at 11:12:11 UTC from IEEE Xplore. Restrictions apply. IEEE Std C37.012a-2020 IEEE Guide for the Application of Capacitance Current Switching for AC High-Voltage Circuit Breakers Above 1000 V Amendment 1 IEEE Std C37.06™, IEEE Standard for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis—Preferred Ratings and Related Required Capabilities for Voltages Above 1000 V. Insert the following reference in Clause 2 in alphanumeric order: IEEE Std C37.100.2™, IEEE Standard for Common Requirements for Testing of AC Capacitive Current Switching Devices over 1000 V. 4. Capacitor bank switching 4.3 Energizing capacitor banks 4.3.3 Back-to-back energization Change the following paragraphs in sublause 4.3.3: Typical amplitudes of the inrush currents for back-to-back energization of capacitor banks are several tens of kiloamperes with frequencies of from 2 kHz to 5 kHz (distribution banks) to 15 kHz (EHV transmission banks).Higher frequencies may be possible for compact capacitor bank designs. Typical values are given in IEEE Std C37.06. Capacitors can normally withstand amplitudes up to 100 times their charging current Banks with internally fused capacitors can withstand inrush currents up to 100 times the bank charging current. Capacitor units without internal fuses can withstand inrush currents of 10 kA (300 kvar and smaller capacitor units), 15 kA for units 301 kvar – 599 kvar, or 20 kA (capacitor units 600 kvar and larger). The bank inrush/outrush current capability can be determined by multiplying the inrush capability of one unit by the number of units or strings in parallel in one phase of the capacitor bank. See IEEE Std 1036 for guidance. If the inrush current amplitude and frequency exceed those stated in IEEE Std C37.06 C37.04, it may be necessary to limit them. However, for vacuum, SF6, and other gas switchgear if the inrush current magnitude (i) is within that stated in IEEE Std C37.04 (ibb) it is acceptable for the inrush current frequency (f) to exceed the tested frequency (fbb) as long as the product of i × f is less than 4 times the product of ibb × fbb. Also if i < 0.1 × (ibb) (i.e. less than 10% of ibb) there is no need for an upper limit on the inrush current frequency. If the inrush current magnitude is greater than that stated in IEEE Std C37.04, the manufacturer could be consulted to determine if a higher inrush current is acceptable. Such limitation can be done by insertion of additional series inductance in the circuit (reactor or pre-insertion inductor), or by using preinsertion resistors (see 6.3, and NOTE below). Another possibility is to use controlled Limitation of the inrush current can be accomplished with a fixed transient limiting inductor (TLI), preinsertion inductor, preinsertion resistor, or controlled switching. Detailed studies are necessary to evaluate the effectiveness of inrush current mitigation measures. 10 Copyright © 2020 IEEE. All rights reserved. Authorized licensed use limited to: University of Liverpool. Downloaded on September 29,2021 at 11:12:11 UTC from IEEE Xplore. Restrictions apply. IEEE Std C37.012a-2020 IEEE Guide for the Application of Capacitance Current Switching for AC High-Voltage Circuit Breakers Above 1000 V Amendment 1 5. Unloaded cable switching 5.2 De-energizing unloaded cables 5.2.1 Cable charging current Change the following in subclause 5.2.1: Using the shunt capacitive reactance, the cable charging current can be calculated and compared with the rated cable charging current of the circuit breaker given in IEEE Std C37.06 C37.04. If the calculation exceeds the rating, the manufacturer should be consulted. Before an application can be made, the inrush current rating should also be checked (see 9.12.1 9.12.2). 5.3 Energizing unloaded cables 5.3.2 Energizing single cables 5.3.2.2 Single cable inrush current Change the following in subclause 5.3.2.2: The initial rate-of-rise of the inrush current (dii/dt at t = 0) is [um-ut]/L. For application purposes ii peak should be compared to the value given in IEEE Std C37.06 C37.04. If the value is higher than given in C47.04, the manufacturer should be consulted to see if the higher value is acceptable. 6. Switching of no-load transmission lines 6.1 De-energizing uncompensated transmission lines 6.1.1 Line charging current Change the following in subclause 6.1.1: Due to the distributed nature of the inductance and the capacitance of the line, the peak value of the power frequency voltage at the remote (or receiving) end is higher than that at the circuit breaker (sending) end of the line. This effect is called the Ferranti effect. For a 500 kV line with a length of 500 km the voltage increase is approximately 4 approximately 24%, and for a line length of 200 km the voltage increase is approximately 1 approximately 4%. That is why the Ferranti effect is not considered for line lengths below 200 km. The small magnitude of the Ferranti effect for line lengths less than 200 km justifies it not being considered in these cases. 11 Copyright © 2020 IEEE. All rights reserved. Authorized licensed use limited to: University of Liverpool. Downloaded on September 29,2021 at 11:12:11 UTC from IEEE Xplore. Restrictions apply. IEEE Std C37.012a-2020 IEEE Guide for the Application of Capacitance Current Switching for AC High-Voltage Circuit Breakers Above 1000 V Amendment 1 6.4 Switching the charging current of long transmission lines Change the following in subclause 6.4: Transmission lines in excess of 300 km, even those of simple design, present a special case not covered by the requirements of 4.10.7 of IEEE Std C37.09a-2005 C37.09-2018 or its notes. Where such long lines are to be switched, consideration should be given to the higher value of peak recovery voltage present on interruption. If the circuit breaker was tested for switching an ungrounded capacitor in the presence of a fault (kc = 1.7) test data will provide insight on the capability of the circuit breaker to switch a long transmission line. Additional testing, such as completing the capacitive current switching requirements of 4.10 of IEEE Std C37.09a-2005 C37.09-2018, but to the elevated values required by the specific application may be desired. Insert subclause 6.5 after 6.4: 6.5 Switching of reactor compensated lines and cables When switching a line or cable whose charging current is more than 50% compensated with shunt reactors, and those shunt reactors are connected to the line or cable before it is energized, it needs to be understood that a rapid opening (within a few seconds) after a closing operation can result in delayed current zeros, and should be avoided by the operator This can be a simple switching operation or a fault reclose operation. Several reports of circuit breaker failure have been attributed to this phenomenon. 7. Voltage factors for capacitive current switching tests Change the following in Clause 7: In 4.10.7 of IEEE Std C37.09a-2005 C37.09-2018 the voltage factors (shown in Table 1, below) are given for single-phase tests. IEEE Std C37.09a-2005 C37.09-2018 requires that the test voltage measured at the circuit breaker location prior to interruption shall not be less than the product of the rated voltage Ur/√3 and the voltage factors given in Table 1. 8. General application considerations Change the following in Clause 8: See Clause 5 Clause 4 of IEEE Std C37.010-2016. 9. Capacitance current switching application considerations 9.1 General Change the following in subclause 9.1: Caution should be exercised when applying older circuit breakers that have not been tested to IEEE Std C37.09a-2005 C37.09-2018 or IEEE Std C37.100.2. 12 Copyright © 2020 IEEE. All rights reserved. Authorized licensed use limited to: University of Liverpool. Downloaded on September 29,2021 at 11:12:11 UTC from IEEE Xplore. Restrictions apply. IEEE Std C37.012a-2020 IEEE Guide for the Application of Capacitance Current Switching for AC High-Voltage Circuit Breakers Above 1000 V Amendment 1 9.4 Rated capacitive current Change the following in subclause 9.4: The preferred values of the rated capacitive switching current are given in IEEE Std C37.06 C37.04. Not all actual cases of capacitive current switching are covered by IEEE Std C37.06 C37.04. The values for lines and cables cover most cases, the values of the current for capacitor banks (single and back-to-back) are typical and representative of actual values in service are presented as a preferred value and three alternate values. These are intended to cover the majority of in service values, but cannot cover every case. 9.4.1 Transmission lines and cables Change the following in subclause 9.4.1: When very long lines and cables are considered, the no-load current may exceed that given in IEEE Std C37.06 C37.04. The manufacturer should be consulted in such cases. Often currents up to the continuous current rating of the breaker are acceptable. The following may serve as an example: The no-load current of a 550 kV transmission line is approximately 1.1 A/km at 50 Hz and 1.3 A/km for 60 Hz. Without considering the Ferranti effect (see 6.1.1), the charging current of a 500 km line would be 605 A at 50 Hz and 715 A at 60 Hz. Ferranti rise on a 500 km on the line would increase the charging current by about 4% at 50 Hz and 6% at 60 Hz. This which is not covered by IEEE Std C37.06 C37.04. 9.4.2 Capacitor and filter banks Change the following in subclause 9.4.2: The same remark as given under 9.4.1 applies to capacitor and filter bank currents. The current is depending on the size of the capacitor bank and in certain cases the capacitor bank considered may have a current rating higher than that given in IEEE Std C37.06 C37.04. The current is dependent on the size of the capacitor banks and line lengths to the capacitors are often short, so Ferranti effect is negligible. In certain cases, the capacitor bank considered may have a current rating higher than that given in IEEE Std C37.04. Experience has shown that capacitive current is not a limiting parameter for circuit breakers up to the continuous current rating. 9.5 Voltage and grounding conditions of the network Change the following in subclause 9.5: 4.10.7 of IEEE Std C37.09a-2005 C37.09-2018 gives the multiplication factors for single-phase tests for the different conditions (see also Clause 7). They range from 1.0 for effectively grounded systems to 1.7 for ungrounded systems in the presence of single- or two-phase-to-ground faults. 9.6 Restrike probability Change the following in subclause 9.6: As all circuit breakers have a certain some restrike probability in service, it is not possible to define a restrike-free circuit breaker. It is more logical to introduce the notion of a restrike classification associated 13 Copyright © 2020 IEEE. All rights reserved. Authorized licensed use limited to: University of Liverpool. Downloaded on September 29,2021 at 11:12:11 UTC from IEEE Xplore. Restrictions apply. IEEE Std C37.012a-2020 IEEE Guide for the Application of Capacitance Current Switching for AC High-Voltage Circuit Breakers Above 1000 V Amendment 1 with a dedicated specific test procedure (see IEEE Std C37.04a-2003 C37.04-2018 and IEEE Std C37.100.2). The level of the restrike probability depends also on the service conditions (e.g., number of operations per year, network condition, maintenance policy of the user). Therefore, it is impossible to introduce a common probability level related to service condition. A restrike classification has been introduced is included in IEEE Std C37.04a-2003 C37.04-2018 as follows: class C0 (undetermined probability of restrike), class C1 (low probability of restrike), and class C2 (very low probability of restrike). NOTE—It is anticipated that a class C0 will be introduced in a future revision of IEEE Std C37.04. Class C0 corresponds to the General Purpose circuit breaker specified in IEEE Std C37.06. 9.7 Class of circuit breaker Change the following in subclause 9.7: TwoThree classes of circuit breakers are defined for capacitive current switching in 3.4 and 3.5 5.8 of IEEE Std C37.04a-2003 C37.04-2018. a) Class C0: Undetermined probability of restrike b) Class C1: Low probability of restrike c) Class C2: Very low probability of restrike The standard introduces the term of restrike probability during the design tests, corresponding to a certain probability of restrike in service, which depends on many parameters. For this reason, the term cannot be quantified in service. The intent is for class C2 to have an order of magnitude lower probability of restrike than C1. The main differences between the design tests and criteria for the two classes are given in 4.10.9.1 and 4.10.9.2 of IEEE Std C37.09a-2005 C37.09-2018 as well as IEEE Std C37.100.2. Tests in accordance with class C2 are performed on preconditioned contacts. Preconditioning consists of three interruptions with 60% of the rated short-circuit current. The number of tests for class C2 is higher than that of class C1. The number of tests conducted near minimum arcing time are much higher for the C2 test program compared to the C1 test program. It must be noted that the behavior of the circuit breaker after the first restrike during design test may be different than under real network conditions since the energies involved in a laboratory test circuit will be different compared to the real network conditions. The overvoltage protection on the capacitor bank used for the type test may be different from the overvoltage protection in the network. This may result in different voltage stresses to the test object. This may also influence possible damages within the interrupting unit. The choices for the user betweenIt must be noted that selection by the user among classes C0, C1, and C2 depends on the following: The service conditions The number of capacitive current switching operations expected per year The operating frequency 14 Copyright © 2020 IEEE. All rights reserved. Authorized licensed use limited to: University of Liverpool. Downloaded on September 29,2021 at 11:12:11 UTC from IEEE Xplore. Restrictions apply. IEEE Std C37.012a-2020 IEEE Guide for the Application of Capacitance Current Switching for AC High-Voltage Circuit Breakers Above 1000 V Amendment 1 The number of circuit breakers in service, for system stability The consequences of any restrike for: The network (for cable distribution systems, the influence of restrikes is usually negligible compared to the influence of restrikes in transmission lines systems) For the circuit breaker (very difficult to evaluate in service) Class C0 may be acceptable where restrikes are not a concern. Class C1 is often considered acceptable for circuit-breakers with a voltage rating of 52 kV 100 kV and below and circuit-breakers applied for infrequent switching of transmission lines and cables. Class C2 is recommended for capacitor bank circuit-breakers and those used on frequently switched transmission lines and cables. NOTE—The class C0 anticipated to be introduced in a future revision of IEEE Std C37.04 is considered acceptable for applications at rated voltages of 52 kV and below where restrikes are not a concern. 9.10 No-load transmission lines 9.10.3 Compensated transmission lines Change the following in subclause 9.10.3: As described in 6.2, very long transmission lines (> 200 km) and underground cables are often may be compensated with shunt reactors to reduce the amount of charging current required of the system. If the circuit breaker rating is chosen based on the compensated line charging current Ilc, the line could not be switched without the compensating reactor(s) connected. The voltage rise caused by the Ferranti effect and also the location of the reactor(s) will change the line current slightly. Insert the following at the end of subclause 9.10.3: When switching a line or cable whose charging current is more than 50% compensated with shunt reactors, and those shunt reactors are connected to the line or cable before it is energized, it needs to be understood that a rapid opening (within a few seconds) after a closing operation can result in delayed current zeros. This can either be a switching operation or a reclose after fault clearing. When an alternating-current (ac) circuit breaker opens a current zero must exist within a certain time after contact parting for successful current interruption to occur. The delayed current zeros associated with switching lines and reactors together can potentially lead to a failure for the circuit breaker to interrupt which can result in equipment damage or other system related concerns. Such a rapid opening after closing should be avoided by a tripping delay, or the shunt reactor should be disconnected before the line circuit breaker is opened. An appropriately sized preinsertion resistor may be another solution. Figure 21a shows an example for a case where an 80 km overhead line (43.3 Mvar charging at 345 kV) and shunt reactor (25 Mvar at 345 kV) are energized together. When energizing the line/reactor at a voltage zero point on wave, the transient inrush current from the capacitance of the line will be a high frequency current that damps quickly to a steady-state current that is 90° out of phase (leading) with the voltage with a magnitude equal to the charging current of the line. The inrush current through the shunt reactor will have a dc offset which slowly decays based on the X/R ratio of the reactor and is 90° out of phase (lagging) with the voltage. Because of the dc offset, the peak of the inrush current through the reactor can be up to two times the shunt reactor rated current. 15 Copyright © 2020 IEEE. All rights reserved. Authorized licensed use limited to: University of Liverpool. Downloaded on September 29,2021 at 11:12:11 UTC from IEEE Xplore. Restrictions apply. IEEE Std C37.012a-2020 IEEE Guide for the Application of Capacitance Current Switching for AC High-Voltage Circuit Breakers Above 1000 V Amendment 1 The total current through the line breaker which closed to energize the line/reactor combination will be a sum of the capacitive current from the line and the inductive current through the reactor which will be approximately 180° out-of-phase with each other (i.e., capacitive current is 90° leading and inductive current is 90° lagging). If the shunt reactor compensates the line charging by 50% or more, a potential concern exists for delayed current zeros because with the dc offset in the shunt reactor current (which will now be greater than the capacitive current) will more than offset the capacitive current as shown in Figure 21a which results in no current zeros because the inductive component magnitude will be greater than the capacitive component. It is important to note that if no current zeros exist within a certain time period after contact parting (i.e., within the interrupting time window of the concerned breaker), the breaker may fail to interrupt the current. Detailed studies are often required to determine the recommended mitigation solution for delayed current zeros. Example solutions include adding a delay to tripping or utilizing circuit breakers with pre-insertion resistors. Figure 21a—Example of delayed current zeros from energizing a compensated line 9.11 Capacitor banks 9.11.2 Methods for calculating transient inrush currents 9.11.2.3 Considerations for transient inrush currents Replace subclause 9.11.2.3 with the following: The inrush currents of different types of compact multi-section banks with minimum spacing between the individual sections may differ by as much as 20%. These inrush currents can be reduced significantly by increasing the lengths (i.e., inductance) of the circuits between the sections. 16 Copyright © 2020 IEEE. All rights reserved. Authorized licensed use limited to: University of Liverpool. Downloaded on September 29,2021 at 11:12:11 UTC from IEEE Xplore. Restrictions apply. IEEE Std C37.012a-2020 IEEE Guide for the Application of Capacitance Current Switching for AC High-Voltage Circuit Breakers Above 1000 V Amendment 1 Another effective measure to reduce transient inrush currents is to add fixed inductance TLIs in the circuit between the capacitor banks and the circuit breaker. Traditionally, the capability of circuit breakers to handle inrush current had been expressed as the inrush current peak times the natural frequency of the inrush current (i × f). The i × f (or di/dt) limit for back-toback switching was developed for shock wave limited devices such as oil circuit breakers as described in 5.8.5 of IEEE Std C37.04-2018. During closing, the breaker experiences a prestrike arc in which current flows before galvanic contact is made between the contacts. In devices with an incompressible dielectric medium, such as oil circuit breakers, this rapidly increasing current (high di/dt) creates a shock wave that can damage the interrupter. Recent work and 40 years of experience with SF6 and vacuum circuit breakers has shown these technologies are much less sensitive to shock waves than the formerly used oil circuit breakers which had determined the i × f limits used before 2009. The i × f limits for class C2 circuit breakers had been accepted to be approximately 100 kA × kHz. A set of tests with 2400 operations with discharge currents of 100 kA @ 25 kHz (2500 kA × kHz) on a 72.5 kV SF6 breaker showed no indication of shock wave damage. A series of capacitive inrush tests was also done on a 12 kV vacuum breaker with inrush frequencies as high as 23.8 kHz, one pole had an inrush with 69 kA peak at 14.7 kHz. It appeared that the ICI was the quantity that needed to be limited, not so much the peak current, and definitely not the frequency. This supports the understanding that the natural frequency of the inrush current is a lesser concern with SF6 and vacuum interrupters. CIGRE WG A3.38 arrived at the same conclusion that for vacuum and gas interrupters, higher frequency of the inrush current is a lesser concern. In some cases, frequency below the tested value can be more damaging in terms of contact erosion. Another set of tests was done with 20 kA inrush currents at 81 kHz (1620 kA × kHz), 22 kHz (440 kA × kHz), and 6 kHz (120 kA × kHz). Each of the tests was performed with 2500 operations. None of these showed evidence of shock wave damage, however, contact erosion was more evident at the lower frequencies due to the larger inrush current integral (ICI). SF6 and vacuum circuit breakers do not require the degree of inrush current mitigation as oil circuit breakers. The limitation seems to be more with control system transients, and in some cases the capacitors themselves. If the peak currents in IEEE Std C37.04 are exceeded, the circuit breaker manufacturer should be consulted to see if their breaker can withstand the higher inrush current peak. NOTE—In determining the inrush current peak and frequency, the currents i1 and i2 as used in Table 2 should include the effect of operating the capacitor bank at a voltage above nominal operating voltage and the effect of a positive tolerance of the capacitance. However, because inrush current depends on the inductive reactance in the circuit, the presence of higher frequency harmonics will only serve to decrease the inrush current slightly and thus can be conservatively ignored. The following example will illustrate the use of the equations in Table 2. 17 Copyright © 2020 IEEE. All rights reserved. Authorized licensed use limited to: University of Liverpool. Downloaded on September 29,2021 at 11:12:11 UTC from IEEE Xplore. Restrictions apply. IEEE Std C37.012a-2020 IEEE Guide for the Application of Capacitance Current Switching for AC High-Voltage Circuit Breakers Above 1000 V Amendment 1 Figure 23—Example of 138 kV system The capacitor banks shown in Figure 23 have a nominal rating of 32.4 Mvar. Nominal current per bank is 136 A. In determining the continuous current rating of the circuit breaker required, the increase in current due to applied voltage, capacitance tolerance, and harmonics should be considered. The increase in current at maximum rated voltage is: maximum voltage to capacitor rated voltage = 145/138 = 1.05. Assume a positive tolerance of capacitors of +10%, yielding a multiplier to the current of 1.1, and a multiplier for harmonic content for an effectively grounded neutral bank of 1.1. The total multiplier used to determine the single and back-to-back continuous current rating is 1.05 × 1.1 × 1.1 = 1.27, giving a current of 1.27 × 136 = 173 A. With capacitor banks 2 and 3 energized, the current through CB2 is 346 A. The circuit breakers intended for this duty have the following ratings: rated voltage 145 kV, rated current 1600 A, rated short circuit current 40 kA, rated single and back-to-back capacitive switching current 400 A. The transient inrush current and frequency can be calculated using the equations in Table 2. In the example, L1', L2', and L3' are the inductances between the respective capacitor banks and the circuit breakers, including the inductance of the capacitor bank. Lbus is the inductance of the bus between the circuit breakers. The inductance values in Table 3 can be used, or values can be calculated for the actual bus configuration used. In the example given below, the added inductance between the circuit breaker and capacitor bank is: L1' = L2' = L3' = 15.2 µH The inductance of the busbar Lbus = 15.6 µH 18 Copyright © 2020 IEEE. All rights reserved. Authorized licensed use limited to: University of Liverpool. Downloaded on September 29,2021 at 11:12:11 UTC from IEEE Xplore. Restrictions apply. IEEE Std C37.012a-2020 IEEE Guide for the Application of Capacitance Current Switching for AC High-Voltage Circuit Breakers Above 1000 V Amendment 1 In determining inrush current and frequency, the currents i1 and i2 as used in Table 2 should include the effect of operating the capacitor bank at a voltage above nominal rating of the capacitors and the effect of a positive tolerance of capacitance. The multiplier for harmonics should not be included in the inrush current calculation. In the example, the multiplier to be used is 1.051.1 1.155 . The currents are i1 1361.155 157 A and i2 = 157 A or 314 A, depending on whether bank 2 or bank 3 or both banks are energized. Case I. Energization of capacitor bank 1 with bank 2 and bank 3 not energized (single or single bank switching). ii peak 1.4142 I sc i1 1.4142 18 000157 1.4142 282.6104 2377 A I sc 18 000 60 642 Hz i1 157 fi fs The calculated rate of change of current for the single bank switching is dii dt 2π f i ii peak 2π (642 Hz) (2377 A) 10106 A/s 9.6 A/μs max This value is less than the maximum rate of change for a rated short-circuit current of 40 kA, which is equal to 2π f s 2 I sc 21.3 A/μs , and therefore meets the requirements of single capacitor bank switching. Case II. Energization of bank 1 with bank 2 energized on the bus (back-to-back switching against an equal-size bank). ii peak 9545 U r i1 f s Leq The equivalent inductance Leq is the sum of L1 Lbus L2 15.2 15.6 15.2 μH = 46.0 μH . ii peak 9545 f i 13.5 145157 9545 8.248 27413 A peak 60 46 f sU r 60145 13.5 14.8 kHz Leq i1 46157 The calculations above are a simple way to estimate the inrush current peak and frequency for a back-toback capacitor bank switching application. Another method to obtain the inrush current is through the means of detailed simulations in an electromagnetic transients software. For illustration, the capacitor bank shown in Figure 23 was modeled in an electromagnetic transients program at a 138 kV substation with four connected transmission lines and four connected step-down transformers as shown in Figure 23a. Note the values for Ur, Ls, L1’, L2’, L3’, and Lbus shown in Figure 23 were used for the detailed simulations. Figure 23b shows a plot of the inrush current through circuit breaker CB1 when energizing bank 1 with bank 2 energized and bank 3 offline. 19 Copyright © 2020 IEEE. All rights reserved. Authorized licensed use limited to: University of Liverpool. Downloaded on September 29,2021 at 11:12:11 UTC from IEEE Xplore. Restrictions apply. IEEE Std C37.012a-2020 IEEE Guide for the Application of Capacitance Current Switching for AC High-Voltage Circuit Breakers Above 1000 V Amendment 1 Figure 23a—Example 138 kV system used for simulation Figure 23b—Example plot of inrush current from simulation The calculated or simulated back-to-back inrush current amplitude must be compared to the back-to-back current (ibb) listed in IEEE Std C37.04 or found on the breaker nameplate. The simulated inrush current peak is 26.5 kA, which exceeds the preferred rating peak value of inrush current of 16 kA, thus some form of mitigation is needed. Possible forms of mitigation may include the addition of a fixed inductor in series with the capacitor bank and/or utilizing a switching device equipped with pre-insertion resistors/inductors or controlled closing. Table 3a shows a comparison of the inrush current for different mitigation solutions quantified through simulation using the model shown in Figure 23a. 20 Copyright © 2020 IEEE. All rights reserved. Authorized licensed use limited to: University of Liverpool. Downloaded on September 29,2021 at 11:12:11 UTC from IEEE Xplore. Restrictions apply. IEEE Std C37.012a-2020 IEEE Guide for the Application of Capacitance Current Switching for AC High-Voltage Circuit Breakers Above 1000 V Amendment 1 Table 3a—Example comparison of inrush current mitigation solutions Inrush current through CB1 Mitigation solution ii peak (kApeak) fi (kHz) i×f (kA × kHz) Multiple of tested i×f No mitigation 26.5 15.6 41.3 6.0 Fixed inductor (45 µH each bank) 15.6 9.1 14.2 2.1 Pre-insertion resistor (150 Ω, 6 ms insertion time) 6.4 15.6 10.0 1.5 Controlled closing (RDDS = 90 kV/ms, +/- 0.5 ms scatter) 6.0 15.6 9 1.4 NOTE 1—RDDS = rate of decay of dielectric strength for the switching device. NOTE 2—As described in 4.4.2.1 of IEEE Std C37.011-2019, the addition of a fixed inductor to limit inrush current may result in a high-frequency transient recovery voltage, which could exceed the standardized TRV values. Case III. Energization of bank 1 with bank 2 and bank 3 energized on the bus. For this case, assume the equivalent inductance of bank 2 and bank 3 equal to one half of L2' or (15.2)/2 = 7.6 µH. The total current of bank 2 and bank 3 is 314 A, which is under the assumed single bank switching capability of 400 A as listed in IEEE Std C37.04. For this case, i1 = 157 A, i2 = 314 A, and the equivalent inductance between the capacitor bank being energized and the banks already energized is the sum of: L2 / 2 Lbus L1 7.6 15.6 15.2 38.4 μH . ii peak 13 500 U r i1i2 145157 314 13 500 34648A peak f s Leq (i1 i2 ) 6038.4 471 and f i 9.5 f sU r (i1 i2 ) 60145 471 9.5 14.0 kHz Leq i1i2 38.4157 314 The calculated values of inrush current and frequency of 34.6 kA and 14.0 kHz exceed the preferred backto-back switching capability of 16 kA and 4.3 kHz listed in IEEE Std C37.04. While the 14 kHz frequency is not a concern on its own, the peak current of 34.65 kA exceeds the preferred rated ibb value of 16 kA. As in the previous case of switching identical banks, mitigation solutions should be considered to reduce the inrush current peak. Change the title of subclause 9.12 as follows: 9.12 Insulated cables Delete the following paragraph from subclause 9.12: 21 Copyright © 2020 IEEE. All rights reserved. Authorized licensed use limited to: University of Liverpool. Downloaded on September 29,2021 at 11:12:11 UTC from IEEE Xplore. Restrictions apply. IEEE Std C37.012a-2020 IEEE Guide for the Application of Capacitance Current Switching for AC High-Voltage Circuit Breakers Above 1000 V Amendment 1 In the application of circuit breakers for cable switching duty, consideration must be given to the rated single cable switching current, the rated back-to-back cable switching current, and the rated transient inrush current, both amplitude and frequency. Insert subclause 9.12.1 as follows: 9.12.1 General Insert the following paragraph in subclause 9.12.1: In the application of circuit breakers for cable switching duty, consideration must be given to the rated single cable switching current, the rated back-to-back cable switching current, and the rated transient inrush current amplitude and frequency. In extreme cases with high transient inrush currents, as long as the ibb is below the rated value, the i × f product is acceptable up to four times the tested value for vacuum, SF6, and other gas switchgear. Renumber subclause 9.12.1 as follows: 9.12.2 9.12.1 Cable inrush current Delete the following paragraph from subclause 9.12.1: For proper circuit breaker application, feq should be less than the rated inrush current frequency. Additional inductance may be added in series with the inductances making up L to meet the rated inrush frequency requirement. Such inrush reactors are common. Renumber subclause 9.12.2 as follows: 9.12.3 9.12.2 Alternate configurations 9.14 Unusual circuits 9.14.2 Exposure to total capacitor bank discharge current (outrush current) Change subclause 9.14.2 as follows: For class C0 circuit breakers exposed to capacitor bank discharge current, in addition to the checking of the crest current, it may be necessary also to check the rate of change of the discharge current with the manufacturer (generally oil circuit breakers should be treated as class C0). For class C1 and class C2 circuit breakers as long as the peak current does not exceed the close and latch peak current rating of the breaker such a discharge is permissible up to two times in the life of the breaker without additional maintenance being required. Generally, the ringing frequency of the discharge is not a concern for the circuit breaker, but this should be confirmed with the manufacturer. The transient discharge current passing through a circuit breaker must also be examined for its effects upon the linear couplers and bushing current transformers. The discharge currents may substantially exceed the magnitudes and the frequency of the inrush currents given in IEEE Std C37.06 C37.04. This occurs because the contribution may come from a number of capacitor banks and is not limited by the inrush impedance seen when energizing a bank of capacitors. Determination of the induced voltages in the linear couplers or 22 Copyright © 2020 IEEE. All rights reserved. Authorized licensed use limited to: University of Liverpool. Downloaded on September 29,2021 at 11:12:11 UTC from IEEE Xplore. Restrictions apply. IEEE Std C37.012a-2020 IEEE Guide for the Application of Capacitance Current Switching for AC High-Voltage Circuit Breakers Above 1000 V Amendment 1 in bushing current transformers also may be used for assessing the effects of the discharge currents. Induced voltages in high-voltage current transformer or linear coupler circuits can be mitigated with metal oxide varistors [B2]. 10. Considerations of capacitive currents and recovery voltages under fault conditions 10.1 Voltage and current factors Change subclause 10.1 as follows: Some requirements, general ratings, and tests for capacitive current switching are based on switching operations in the absence of faults. The presence of a fault can increase the value of both the capacitive switching current and recovery voltage. This is recognized in 4.10.7 of IEEE Std C37.09a-2005 C37.092018, by the specification of two voltage factors when breaking in the presence of faults. These voltage factors apply to single-phase tests as a substitute of three-phase tests and are given in Clause 7. They are 1.4 for effectively grounded systems and 1.7 for ungrounded systems. Tests for these conditions are not mandatory. An example of such a fault is a circuit breaker switching a transmission line that interrupts fault current in one phase and capacitive current in the other two phases. The fact that the capacitive switching current increases in the presence of ground faults is recognized in 4.10.9.3 of IEEE Std C37.09a-2005 4.10.9.4 of IEEE Std C37.09-2018, where the line and cable charging currents are multiplied by 1.25 for effectively grounded neutral systems and 1.7 for ungrounded systems. The number of tests is reduced to reflect the fact that such operations do not occur frequently. 10.4 Switching transmission lines under faulted conditions Change subclause 10.4 as follows: The voltages and currents that occur when switching a faulted transmission line are affected by the circuit parameters and the sequence in which the three phases interrupt. IEEE Std C37.09a-2005 C37.09-2018 lists the maximum value of recovery voltage for switching an unfaulted transmission line as 21.2 Ur 2 3 2.4 p.u. When switching a faulted line this value may be exceeded, as may be the rated capacitive switching current value as listed in IEEE Std C37.06 C37.04 (see also [B5]). 10.5 Switching capacitor banks under faulted conditions Change subclause 10.5 as follows: The voltages and currents that can occur when switching a faulted capacitor bank depend upon the grounding conditions, whether the fault is to the bank neutral or to ground, and on the sequence in which the three phases interrupt. IEEE Std C37.09a-2005 C37.09-2018 lists the maximum value of recovery voltage in switching an unfaulted shunt capacitor bank as 2.8 p.u. When switching a faulted bank, this value may be exceeded, as may the rated capacitive switching current value. In the sections below, a 23 Copyright © 2020 IEEE. All rights reserved. Authorized licensed use limited to: University of Liverpool. Downloaded on September 29,2021 at 11:12:11 UTC from IEEE Xplore. Restrictions apply. IEEE Std C37.012a-2020 IEEE Guide for the Application of Capacitance Current Switching for AC High-Voltage Circuit Breakers Above 1000 V Amendment 1 comparison is given between the recovery voltages and currents of a reference condition and two faulted conditions: a fault to neutral in the capacitor bank and a fault to ground in one phase. It is also possible to have an evolving fault where the capacitor bank faults in the process of being switched off, and the circuit breaker then cannot interrupt. The factor 2.8 for the maximum recovery voltage specified in IEEE Std C37.09-2018 is valid when switching an ungrounded capacitor bank where the second and third phases clear 90° after the first. This is true for modern circuit breakers. For certain older circuit breakers (or other switching devices), where the second and third phases do not clear 90° after the first, this factor is 4.1. NOTE— The factor 2.8 for the maximum recovery voltage specified in IEEE Std C37.09a-2005 is valid when switching an ungrounded capacitor bank where the second and third phases clear 90 o after the first. This is true for modern circuit breakers. For older circuit breakers, where the second and third phases do not clear 90o after the first, this factor is 3.0. 10.5.1 Reference condition 10.5.1.1 Recovery voltage Change subclause 10.5.1.1 as follows: The voltages and currents obtained with this reference condition (i.e., unfaulted balanced system) agree with the 2.8 p.u. voltage listed in IEEE Std C37.09a-2005 C37.09-2018. Although the voltage across the last poles to interrupt when at least one of the neutrals (source or bank) is ungrounded can reach 2 × Ur √2 = 2.828 × Ur = 3.46 p.u., the two phases are in series so that neither is stressed to much more than 1.73 p.u. 10.5.2 Fault to neutral in one phase (one capacitor bank phase short-circuited) 10.5.2.1 Recovery voltage Change subclause 10.5.2.1 as follows: The highest recovery voltage (i.e., 2 × Ur √2 = 3.46 p.u.) is obtained when at least one neutral is ungrounded and the first pole-to-clear clears a healthy phase. This is in agreement with the voltage factor of 1.7 specified in 4.10.7 of IEEE Std C37.09a-2005 C37.09-2018. If the first pole-to-clear interrupts an unfaulted phase, it is subjected to a recovery voltage of 3.46 p.u. until the second and third phases interrupt. 10.7 Examples of application alternatives Change subclause 10.7 as follows: Other application options available are as follows: Use a circuit breaker of a higher rating in those cases of ground faults on ungrounded systems where the recovery voltage and current, or both, exceed the requirements of IEEE Std C37.09a2005 C37.09-2018. Reduce the capacitance of the existing capacitor bank size so that the current under faulted conditions does not exceed the rated capacitive switching current of the circuit breaker. Use a high-speed switch to ground the source or capacitor bank neutral before switching the capacitor bank under faulted conditions. 24 Copyright © 2020 IEEE. All rights reserved. Authorized licensed use limited to: University of Liverpool. Downloaded on September 29,2021 at 11:12:11 UTC from IEEE Xplore. Restrictions apply. IEEE Std C37.012a-2020 IEEE Guide for the Application of Capacitance Current Switching for AC High-Voltage Circuit Breakers Above 1000 V Amendment 1 Annex A (informative) Bibliography Insert the following references and footnote in Annex A in alphanumeric order: [B1] CIGRÉ Technical Brochure 624, “Influence of Shunt Capacitor Banks on Circuit Breaker Fault Interruption Duties,” June 2015. [B2] CIGRE Technical Brochure, “Shunt Capacitor Switching in Distribution and Transmission Systems: Verification by Tests and Performance in Service,” 2020. 1 [B3] IEEE PES-TR16, “Transient Limiting Inductor Application in Shunt Capacitor Banks.” 1 A brochure is expected to be published by the end of 2020 documenting the work of CIGRE WG A3.38. 25 Copyright © 2020 IEEE. All rights reserved. Authorized licensed use limited to: University of Liverpool. Downloaded on September 29,2021 at 11:12:11 UTC from IEEE Xplore. Restrictions apply. RAISING THE WORLD’S STANDARDS Connect with us on: Twitter: twitter.com/ieeesa Facebook: facebook.com/ieeesa LinkedIn: linkedin.com/groups/1791118 Beyond Standards blog: beyondstandards.ieee.org YouTube: youtube.com/ieeesa standards.ieee.org Phone: +1 732 981 0060 Authorized licensed use limited to: University of Liverpool. Downloaded on September 29,2021 at 11:12:11 UTC from IEEE Xplore. Restrictions apply.