UL LISTED SHORT CIRCUIT RATINGS AND IEC QUALIFIED SHORT CIRCUIT RATINGS FOR FREEDOM NEMA, FREEDOM IEC AND ADVANTAGE PRODUCTS Published By: J. K. Hastings T. A. Wilsdon CMS Name 465-1001 Approval Date 1/24/97 Revision Date 12/16/98 Revision No. A Revision Control This document must be modified through CMS. CMS Name 465-1001 Approval Date 1/24/97 Revision Date 12/16/98 Revision No. A Revision Control This document must be modified through CMS. UL LISTED SHORT CIRCUIT RATINGS AND IEC QUALIFIED SHORT CIRCUIT RATINGS FOR FREEDOM NEMA, FREEDOM IEC AND ADVANTAGE PRODUCTS (All statements made in this paper as to the UL listing of products with short circuit levels and short circuit qualification to IEC are supported by UL files or IEC test certificates.) PURPOSE: The purpose of this white paper is to present the short circuit qualifications for the Freedom and Advantage product lines in a single document that can be used for marketing and sale of these products worldwide. It is also intended to serve as a factual foundation for planning of tests at higher levels as short circuit protection designs and starter designs advance. IN BRIEF: • The Freedom and Advantage product lines are fully listed to UL508. They meet and exceed safety requirements. • The Freedom and Advantage products have been tested with fuses and have passed the IEC 9474-1 short circuit requirements for the mandatory “r” level currents and the optional “Iq” level currents. IEC 947-4-1 TYPE 2 performance was observed and established. • The Freedom and Advantage have been tested to IEC 947-4-1 TYPE 2 short circuit requirements with the HMCP. Consult the attached chart to identify those protection devices and starters that are qualified as TYPE 2 at the “r” and Iq short circuit levels. • The Freedom and Advantage products are presently being tested with newly developed EF style HMCP and thermal magnetic breaker designs. Look for these to be released in the near future. • Specified product ratings are shown in Table B, Pages 1 through 6. • IEC makes no requirement for testing at 50 or 60 Hz. Results at either frequency qualify at the other, however, certain customer sensitivities are recognized and some frequency-specific testing is done on request. UL BACKGROUND: SHORT CIRCUIT TEST STANDARDS AND LEVELS UL SHORT CIRCUIT TESTS A UL listed starter must pass a “UL Standard short circuit” test. The test currents range from 5,000 amps to 85,000 amps depending on starter horsepower (kW). Fuses, HMCP, thermal mag breakers can be used as the SCPD. A safe interruption is the criteria to pass. Damage to the motor control components is allowed. There are two levels of short circuit tests for UL listed products. 1. UL508 STANDARD SHORT CIRCUIT TESTS. THIS IS A MANDATORY TEST. Short circuit currents levels are determined by UL508. (See Table A, Required Short Circuit Tests.) 2. UL508 HIGH FAULT TESTS. THIS IS AN OPTIONAL TEST. Short circuit current levels are selected by the manufacturer. IEC SHORT CIRCUIT TESTS There are two levels of short circuit tests for products tested to IEC 947-4-1. 1. CONDITIONAL SHORT CIRCUIT CURRENT, “r”. THIS IS MANDATORY. Interruption levels are defined in IEC 947-4-1. This is similar to the UL508 “Standard” short circuit test. 2. CONDITIONAL SHORT CIRCUIT CURRENT, “Iq”. THIS IS AN OPTIONAL TEST. Short circuit current levels are selected by the manufacturer. This is similar to the UL508 “High Fault” test. DETERMINATION OF TYPE 1 OR TYPE 2 PERFORMANCE Following the conditional short circuit tests at “r” and at “Iq”, the products are examined to determine if the products meet TYPE 1 or TYPE 2 performance. TYPE 1 or TYPE 2 results can be claimed at either “r”, or both r and Iq. IEC 947-4-1 defines a TYPE 1 short circuit performance to be similar to UL508. It allows the same level of damage to the control and requires the same level of personnel safety. IEC 947-4-1 defines a TYPE 2 short circuit performance. It requires that the control components will be serviceable after they experience a short circuit event. UL defines the TYPE 2 performance in UL508 “Subject E” (not to be confused with Type E starters or Design E motors). Requirements are equivalent to IEC 947-4-1 TYPE 2. “SHORT CIRCUIT PROTECTION DEVICES” (SCPD). Four types of product are used. 1. FUSES Fuses are available in several designs providing interruption with no current limiting capability up to high current limiting capability and high fault interruption capability. Fuses consume the internal elements during the interruption and thereby can provide fast response and current limiting sufficient to protect motor control components as well as the motor feed wires. The TYPE 2 protection level described in the IEC 947-4-1 performance specification for starters was first accomplished using current limiting fuses. Not all fuses provide TYPE 2 protection. Fuse and control manufacturers publish information on fuses in combination with specified starters that are witnessed by UL for TYPE 2 protection. 2. THERMAL MAGNETIC BREAKERS A thermal magnetic breaker provides a fixed magnetic trip that responds to peak currents and a thermal or electronic simulation of an inverse current-time thermal trip behavior. The magnetic trip is intended for short circuit levels above 16 times the breaker rating while the thermal behavior protects below the magnetic trip level. Some interchangeable trip units are available with adjustable magnetic trips between 10X and 5X the breaker rating. The thermal mag breakers offer less TYPE 2 capability than HMCP, however, the breaker’s higher magnetic trip levels offer better high efficiency motor starting capability. 3. HMCP These are circuit breakers with an adjustable magnetic trip designed specifically for motor circuits. They do not have a thermal trip mechanism. The thermal protection for the circuit wires that is typically provided by the bimetal in the thermal magnetic breakers, is provided by the thermal or electronic behavior of the overload relay. By NEC code, the wires serving a motor will always have a higher current limit than the motor. The overload relay protects the motor and therefore provides thermal protection for the feed wires. The magnetic trip level of the HMCP is set at 13X the adjustable set point. HMCP can be adjusted to trip at lower peak currents than the fixed magnetic trip found in thermal magnetic breakers. The HMCP can provide short circuit protection at lower current levels. For these reasons HMCP can provide better protection for motor circuits and can only be used in combination with a listed contactor and overload relay. The HMCP has demonstrated a better capability in achieving the TYPE 2 performance than thermal magnetic breakers. 4. HYBRID In UL508 the construction Type E starter product listed under combination motor controller defines the hybrid. They combine a highly current limiting breaker structure with a manual disconnecting mechanism, and overload relay. Some designs include a magnetic contactor. They contain an adjustable thermal trip for motor overload protection and some models offer an adjustable magnetic trip to meet the requirement written for the HMCP products. Products listed by UL meet the minimum UL508E requirements. Some claim IEC 947-4-1 TYPE 2 at specific voltages and currents. Short circuit levels are dependent on current rating. At low current ratings the resistance of the heater is sufficiently high to limit the let through current to a level that provides “intrinsic self protection”. These products are sensitive to the available short circuit current, the system voltage, and the current rating. REQUIRED SHORT CIRCUIT TESTS TABLE A UL 508 STANDARD SHORT CIRCUIT TEST LEVELS STANDARD SHORT CIRCUIT NEMA TEST HP KW SIZE CURRENT 1 - 1.5 2 - 50 51 - 200 201 - 400 401 - 600 601 - 900 901 - 1600 1601-More .7 - 1.1 1.4 - 37.3 39 - 149 150 - 298 299 - 447 448 - 671 672 - 1193 1194-More NEMA 00 NEMA 3 NEMA 5 NEMA 6 NEMA 7 NEMA 8 NEMA 9 1,000 5,000 10,000 18,000 30,000 42,000 85,000 100,000 125,000 150,000 200,000 IEC 947-4-1 SHORT CIRCUIT TEST LEVELS AC3 CURRENT RATING Ie IN AMPS CONDITIONAL TEST CURRENT “r” IN AMPS 0 - 16 16 - 63 63 - 125 125 - 315 315 - 630 630 - 1000 1000 - 1600 1,000 3,000 5,000 10,000 18,000 30,000 42,000 UL508 STANDARD SHORT CIRCUIT LISTED CURRENT AND VOLTAGE LEVELS BY SIZE FUSES NEMA SIZES FREEDOM NEMA WITH C306 UL508 STANDARD SHORT CIRCUIT UL508 SUBJECT E TYPE 1 OR TYPE 2 IEC 947 REQUIRED SHORT CIRCUIT CURRENT LEVEL "r" IEC 947 TYPE 1 OR TYPE 2 AT "r" CURRENT 00 5,000A 600V TYPE 2 1000A 600V TYPE 2 FREEDOM IEC SIZE C306 AND C316 - AC3 Ie AT 480V A, B, C 4.8, 7.8, 11 QUALIFIED AT UL STANDARD 5,000A SHORT CIRCUIT LEVEL 600V IEC 947 REQUIRED SHORT CIRCUIT 1000 A CURRENT LEVEL "r" 600V IEC 947 TYPE 1 OR TYPE 2 AT "r" CURRENT TYPE 2 0 1 2 3 4 5,000A 5,000A 5,000A 5,000A 10,000A 600V 600V 600V 600V 600V TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 5 10,000A 600V TYPE 2 6 7 8 9 18,000 30,000A 42,000A 85,000A 600V A 600V 600V 600V TYPE TYPE 1 TYPE 1 TYPE 1 1 3000A 3000A 5000A 10,000A 10,000A 18,000A 18,000 30,000A 42,000A 600V 600V 600V 600V 600V 600V A 600V 600V 600V TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE TYPE 1 TYPE 1 1 D, E, F G, H, J K L, M N P, R, S T U V W X Z 14, 21, 34, 40, 65 86, 106 140 170,200,300 450 550 700 700 860 1200 27 52 5,000A 5,000A 5,000A 10,000A 10,000A 10,000A 18,000 18,000A 30,000A 30,000A 30,000A 42,000A 600V 600V 600V 600V 600V 600V A 600V 600V 600V 600V 600V 600V 3000A 3000A 5000A 5000A 10,000A 10,000A 18,000 18,000A 30,000A 30,000A 30,000A 42,000A 600V 600V 600V 600V 600V 600V A 600V 600V 600V 600V 600V 600V TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 1 CONTACTOR ONLY. IEC STARTERS ARE NOT CATALOGED. HMCP with C306 TEST CERTIFICATE OR UL FILE NUMBER FREEDOM NEMA SIZES LISTED SHORT-CIRCUIT CURRENT AND VOLTAGE LEVELS BY SIZE FOR BOTH NEMA & I.E.C. DEVICES 00 UL508 STANDARD SHORT CMS460-1038 CIRCUIT E176513,VOL.. LISTED BY VIRTUE OF PASSING 1 RPT.DATE: THE HMCP HIGH FAULT & STD 7/30/97 TESTS ON THERMAL-MAG BREAKERS 1,000A 480V 60Hz UL508 HIGH FAULT CURRENT E1491,VOL.3 RPT.DATE: 6/19/75 FREEDOM IEC SIZE AC3 Ie AT 480V UL 508,sub E, (I.E.C. 947-4-1) REQUIRED STANDARD SHORT CIRCUIT CURRENT LEVEL "r" CMS460-1038 E176513,VOL.. 1 RPT.DATE: 7/30/97 0 2 3 4 5 6 5,000A 5,000A 5,000A 10,000 10,000A 10,000 18,000 600V 600V 600V A 480V 600V A 600V A 600V 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 100,000A 100,000 100,000 100,000 100,000 100,000 100,000 18,000A A A A A A A 600V 480V 7 8 9 NO HMCP AVAILABLE ABOVE THIS SIZE 60Hz 60Hz 60Hz 60Hz 60Hz NO HMCP AVAILABLE ABOVE THIS SIZE 480V 480V 480V 480V 480V 480V 25,000A 25,000A 25,000A 25,000A 25,000A 25,000A 600V 600V 600V 600V 600V 600V 60Hz A, B, C,D 4.8, 7.8, 11,14 1000A 480V 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz E, F G, H, J K L, M N P, R, S 21, 27 34, 40, 65 86, 106 140 170,20 52 0,300 3000A 3000A 5000A 5000A 10,000A 10,000A 480V 480V 480V 480V 480V 480V 60Hz 60Hz TYPE 2 TYPE 1 UL 508,sub E, (I.E.C. 947-4-1) - CMS460-1038 100,000A 100,000 A OPTIONAL SHORT CIRCUIT E176513,VOL.. 480V 480V CURRENT LEVEL "Iq" 1 RPT.DATE: 25,000A 7/30/97 600V CMS460-1038 E176513,VOL.. 1 RPT.DATE: 7/30/97 1 60Hz TYPE 1 1,000A 480V 60Hz 60Hz TYPE 2 60Hz 60Hz T 450 60Hz U 550 60Hz V 700 60Hz W 700 60Hz X 860 60Hz Z 1200 18,000A 480V 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 1 TYPE 1 60Hz 60Hz 60Hz 60Hz 60Hz N/A N/A N/A N/A N/A 100,000 100,000 100,000 100,000 100,000 18,000A NO HMCP AVAILABLE ABOVE THIS A A A A A 600V SIZE 480V 480V 480V 480V 480V 25,000A 25,000A 25,000A 25,000A 25,000A 600V 600V 600V 600V 600V 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 3000A 5000A 25,000A 25,000A 480V 480V 480V 480V 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz NO HMCP AVAILABLE ABOVE THIS SIZE 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz HMCP with C316 FREEDOM NEMA SIZES UL508 STANDARD SHORT CIRCUIT LISTED BY VIRTUE OF PASSING THE HMCP HIGH FAULT & STD TESTS ON THERMAL-MAG BREAKERS TEST CERTIFICATE OR UL FILE NUMBER LISTED SHORT-CIRCUIT CURRENT AND VOLTAGE LEVELS BY SIZE FOR BOTH NEMA & I.E.C. DEVICES 00 CMS460-1037 1,000A E176513,VOL.1 480V RPT.DATE: 7/30/97 60Hz 0 1 2 3 4 5 6 5,000A 5,000A 5,000A 10,000 10,000A 10,000 18,000 600V 600V 600V A 480V 600V A 600V A 600V 60Hz 60Hz 60Hz 60Hz 60Hz UL508 HIGH FAULT CURRENT E1491,VOL. 3 100KA 100KA 100KA 100KA RPT.DATE: 25KA 25KA 480V 480V 480V 480V 6/19/75 600V 600V 25KA 25KA 25KA 25KA 600V 600V 600V 600V 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz FREEDOM IEC SIZE A, B, C,D E, F G, H, J K L, M N AC3 Ie AT 480V 4.8, 7.8, 21, 27 34, 40, 65 86, 106 140 11,14 52 UL 508,sub E, (I.E.C. 947-4-1) CMS460-1037 1,000A 3000A 3000A 5000A 5000A 10,000A REQUIRED STANDARD SHORT E176513,VOL.1 480V 480V 480V 480V 480V 480V CIRCUIT CURRENT LEVEL "r" RPT.DATE: 7/30/97 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz TYPE 1 TYPE 1 TYPE TYPE TYPE TYPE 2 2 2 2 UL 508,sub E, (I.E.C. 947-4-1) CMS460-1037 25,000A 25,000 100,000 100,000 100,000 100,000A A A A 480V OPTIONAL SHORT CIRCUIT E176513,VOL.1 480V A 480V 480V 480V CURRENT LEVEL "Iq" RPT.DATE: 480V 7/30/97 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz TYPE 1 25,000A 25,000A 25,000A 25,000A CMS460-1037 480V 480V 480V E176513,VOL.1 480V RPT.DATE: 7/30/97 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz TYPE 2 60Hz 100KA 480V 25KA 600V 60Hz P, R, S 170,20 0,300 10,000 A 480V 8 9 NO HMCP AVAILABLE ABOVE THIS SIZE 60Hz 18KA 600V NO HMCP AVAILABLE ABOVE THIS SIZE 60Hz T 450 U 550 18,000 A 480V 60Hz 60Hz TYPE N/A 1 100,00 18KA 0A 600V 480V 60Hz 7 V 700 W 700 X 860 Z 1200 NO HMCP AVAILABLE ABOVE THIS SIZE NO HMCP AVAILABLE ABOVE THIS SIZE 60Hz NO HMCP AVAILABLE ABOVE THIS SIZE 60Hz 60Hz THERMAL-MAG BREAKERS UL508 STANDARD SHORT CIRCUIT LISTED CURRENT AND VOLTAGE LEVELS BY SIZE NEMA SIZES 00 FREEDOM WITH C306 5,000A UL508 STANDARD SHORT CIRCUIT 600V UL508 SUBJECT E TYPE 1 OR TYPE1 TYPE 2 FREEDOM IEC SIZE A, B, C C306 - AC3 Ie AT 480V 4.8, 7.8, 11 QUALIFIED AT UL STANDARD 5,000A SHORT 600V CIRCUIT LEVEL IEC 947 REQUIRED SHORT CIRCUIT 1000 A CURRENT LEVEL "r" 600V IEC 947 TYPE 1 OR TYPE 2 AT "r" TYPE 1 0 1 2 3 4 5,000A 5,000A 5,000A 5,000A 10,000A 600V 600V 600V 600V 600V TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 D, E, F 14, 21, 27 5,000A 600V G, H, J 34, 40, 52 5,000A 600V K 65 L, M 86, 106 N 140 5 10,000A 600V TYPE 1 P, R, S 170,200,300 6 7 8 9 18,000 30,000 42,000 85,000 A 600V A 600V A 600V A 600V TYPE 1 TYPE 1 TYPE 1 TYPE 1 T 450 U 550 V 700 W 700 X 860 Z 1200 5,000A 10,000A 10,000A 600V 600V 600V 10,000A 600V 18,000A 18,000A 30,000A 30,000A 30,000A 42,000A 600V 600V 600V 600V 600V 600V 3000A 3000A 5000A 5000A 10,000A 600V 600V 600V 600V 600V TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 10,000A 600V TYPE 1 18,000A 18,000A 30,000A 30,000A 30,000A 42000A 600V 600V 600V 600V 600V 600V TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 CURRENT FREEDOM IEC SIZE C316 - AC3 Ie AT 480V QUALIFIED AT UL STANDARD SHORT CIRCUIT LEVEL IEC 947 REQUIRED SHORT CIRCUIT CURRENT LEVEL "r" IEC 947 TYPE 1 OR TYPE 2 AT "r" CURRENT A, B, C 4.8, 7.8, 11 NOT LISTED D, E, F G, H, J 14, 21, 34, 40, 27 52 NOT 5,000A LISTED 600V K 65 L, M 86, 106 N 140 CONTACTOR ONLY. IEC STARTERS ARE NOT CATALOGED. P, R, S T U V W X Z 170,200,300 450 550 700 700 860 1200 5,000A 10,000A 10,000A 600V 600V 600V 10,000A 600V 18,000A 18,000A 30,000A 30,000A 30,000A 42,000A 600V 600V 600V 600V 600V 600V 3000A 5000A 5000A 10,000A 600V 600V 600V 600V TYPE 1 TYPE 1 TYPE 1 TYPE 1 10,000A 600V TYPE 1 18,000A 18,000A 30,000A 30,000A 30,000A 42,000A 600V 600V 600V 600V 600V 600V TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 CONTACTOR ONLY. IEC STARTERS ARE NOT CATALOGED. UL508 STANDARD SHORT CIRCUIT LISTED CURRENT AND VOLTAGE LEVELS BY SIZE HMCPS NEMA SIZES FREEDOM WITH C306 UL508 STANDARD SHORT CIRCUIT 00 5,000A 480V 0 5,000A 480V 1 5,000A 480V 2 5,000A 480V 3 4 6 7 8 9 ** NO HMCPS AVAILABLE ABOVE THIS CURRENT *** UL508 SUBJECT E TYPE 1 OR TYPE 2 FREEDOM IEC SIZE C306 AND C316 - AC3 Ie AT 480V 5 TYPE 1 TYPE 1 TYPE 1 TYPE 1 A, B, C 4.8, 7.8, 11 IEC 947 REQUIRED SHORT CIRCUIT 1,000A 480V CURRENT LEVEL "r" * D, E, F 14, 21, 27 3,000A 480V IEC 947 TYPE 1 OR TYPE 2 AT "r" CURRENT TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 G, H, J 34, 40, 52 3,000A 480V K 65 L, M 86, 106 N 140 5,000A 480V 5,000A 480V 5,000A 480V * COMPLETION OF TYPE 2 CONFORMANCE TESTING IS PLANNED FOR APRIL, 1997. ** TESTING PLANNED FOR APRIL, 1997. *** QUALIFIED BY VIRTUE OF PASSING THE 100,000A/480V HIGH FAULT TEST. P, R, S 170,200,300 T 450 U 550 V 700 W 700 X 860 NO HMCPS AVAILABLE ABOVE THIS CURRENT Z 1200 GMCP with C306 TEST CERTIFICATE OR UL FILE NUMBER NEMA SIZES UL508 STANDARD SHORT CIRCUIT LISTED BY VIRTUE OF PASSING THE GMCP HIGH FAULT LISTED SHORT-CIRCUIT CURRENT AND VOLTAGE LEVELS BY SIZE FOR BOTH NEMA & I.E.C. DEVICES 00 CMS460-1036 E176513,VOL. 1 1,000A 480V 0 1 5,000A 5,000A 480V 480V 2 5,000A 480V 3 4 5 6 7 8 GMCP PRODUCT NOT AVAILABLE ABOVE THIS SIZE 60Hz 60Hz 60Hz 60Hz 42,000A 42,000 42,000A 42,000A 480V 480V A 480V 480V 60Hz 60Hz 60Hz 60Hz FREEDOM IEC SIZE A, B, C,D E, F G, H, J K L, M N P, R, S T U V AC3 Ie AT 480V 4.8, 7.8, 11,14 21, 27 34, 40, 65 86, 140 170,200, 450 550 700 52 106 300 UL 508,sub E, (I.E.C. 947-4-1) - CMS460-1036 1,000A 3,000A 3,000A 5,000A GMCP PRODUCT NOT AVAILABLE ABOVE REQUIRED STANDARD SHORT E176513,VOL. 480V 480V 480V 480V THIS SIZE CIRCUIT CURRENT LEVEL "r" 1 60Hz 60Hz 60Hz 60Hz TYPE 2 TYPE 2 TYPE 2 TYPE 2 UL 508,sub E, (I.E.C. 947-4-1) - CMS460-1036 42,000A 42,000 42,000A 42,000A OPTIONAL SHORT CIRCUIT E176513,VOL. 480V A 480V 480V CURRENT LEVEL "Iq" 1 480V 60Hz 60Hz 60Hz 60Hz TYPE 1 CMS460-1036 1,000A 3,000A 3,000A 5,000A E176513,VOL. 480V 480V 480V 480V 1 60Hz 60Hz 60Hz 60Hz TYPE 2 UL508 HIGH FAULT CURRENT 9 E176513,VOL. 1 W 700 X 860 Z 1200 UL508 STANDARD SHORT CIRCUIT LISTED CURRENT AND VOLTAGE LEVELS BY SIZE HMCPE NEMA SIZES FREEDOM WITH C306 UL508 STANDARD SHORT CIRCUIT FREEDOM IEC SIZE C306 AND C316 - AC3 Ie AT 480V QUALIFIED AT UL STANDARD SHORT CIRCUIT LEVEL AND IEC CONDITIONAL "r" LEVEL 00 0 1 2 3 4 5 NO PRODUCT AVAILABLE. NO TESTING PERFORMED AT THIS TIME. A, B, C D, E, F G, H, J K L, M N P, R, S 4.8, 7.8, 14, 21, 34, 40, 65 86, 106 140 170,200, 11 27 52 300 NO PRODUCT AVAILABLE. NO TESTING PERFORMED AT THIS TIME. IEC 947 REQUIRED SHORT CIRCUIT CURRENT LEVEL "r" 1,000 3,000 3,000 5,000 10,000 10,000 18,000 IEC 947 TYPE 1 OR TYPE 2 AT "r" CURRENT NO PRODUCT AVAILABLE. NO TESTING PERFORMED AT THIS TIME. 6 7 8 9 T 450 U 550 V 700 W 700 18,000 30,000 X 860 Z 1200 FUSES HIGH FAULT UL508 SHORT CIRCUIT CURRENT AND VOLTAGE LISTING BY SIZE. TYPE 1 OR TYPE 2 PERFORMANCE. QUALIFICATION TO IEC 947 CONDITIONAL SHORT CIRCUIT CURRENT Iq. TYPE 1 OR TYPE 2 PERFORMANCE. NEMA SIZES 00 FREEDOM NEMA WITH C306 UL508 HIGH FAULT CURRENT UL 508 SUBJECT E TYPE 1 OR TYPE 2 FREEDOM IEC SIZE A, B, C C306 AND C316 - AC3 Ie AT 480V 4.8, 7.8, 11 Iq SHORT CIRCUIT QUALIFICATION LEVEL IEC 947 TYPE 1 OR TYPE 2 AT Iq LEVEL 0 1 2 3 4 100KA 100KA 100KA 100KA 100KA 600V 600V 600V 600V 600V TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 5 100KA 600V TYPE 2 D, E, F G, H, J K L, M N 14, 21, 34, 40, 65 86, 106 140 27 52 100KA 100KA 100KA 100KA 100KA 600V 600V 600V 600V 600V TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 P, R, S 170, 200, 300 100KA 600V TYPE 2 6 7 8 9 100KA 100KA 42KA 85KA 600V 600V 600V 600V TYPE 1 TYPE 1 TYPE 1 TYPE 1 T U V W X 450 550 700 700 860 100KA 100KA 100KA 100KA 100KA 600V 600V 600V 600V 600V TYPE 1 TYPE 1 TYPE 1 TYPE TYPE 1 1 Z 1200 42KA 600V TYPE 1 THERMAL-MAG BREAKERS HIGH FAULT UL508 SHORT CIRCUIT CURRENT AND VOLTAGE LISTING BY SIZE. TYPE 1 OR TYPE 2 PERFORMANCE. QUALIFICATION TO IEC 947 CONDITIONAL SHORT CIRCUIT CURRENT Iq. TYPE 1 OR TYPE 2 PERFORMANCE. NEMA SIZES 00 FREEDOM NEMA WITH C306 UL508 HIGH FAULT CURRENT UL508 SUBJECT E TYPE 1 OR TYPE 2 FREEDOM IEC SIZE A, B, C C306 AND C316 - AC3 Ie AT 480V 4.8, 7.8, 11 Iq SHORT CIRCUIT QUALIFICATION LEVEL IEC 947 TYPE 1 OR TYPE 2 AT Iq LEVEL 0 1 2 SAME AS HMCP 3 4 5 UL LISTED BY ASSOCIATION WITH THE HMCP TESTS D, E, F 14, 21, 27 G, H, J K L, M 34, 40, 65 86, 106 52 SAME AS HMCP N 140 P, R, S 170,200,300 UL LISTED BY ASSOCIATION WITH THE HMCP TESTS 6 7 8 18,000A 600V 30,000A 600V 42,000A 600V 9 85,000A 600V TYPE 1 TYPE 1 TYPE 1 TYPE 1 T 450 U 550 V 700 W 700 X 860 Z 1200 18,000A 18,000A 30,000A 30,000A 30,000A 42,000A 600V 600V 600V 600V 600V 600V TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 HMCPS HIGH FAULT UL508 SHORT CIRCUIT CURRENT AND VOLTAGE LISTING BY SIZE. TYPE 1 OR TYPE 2 PERFORMANCE. QUALIFICATION TO IEC 947 CONDITIONAL SHORT CIRCUIT CURRENT Iq. TYPE 1 OR TYPE 2 PERFORMANCE. NEMA SIZES 00 0 FREEDOM NEMA WITH C306 100,000A 100,000 UL508 HIGH FAULT CURRENT 480V A 480V UL508 SUBJECT E TYPE 1 OR TYPE 1 TYPE 1 TYPE 2 FREEDOM IEC SIZE A, B, C D, E, F C306 AND C316 - AC3 Ie AT 480V 4.8, 7.8, 14, 21, 11 27 Iq SHORT CIRCUIT QUALIFICATION 100,000A 100,000 LEVEL 480V A 480V IEC 947 TYPE 1 OR TYPE 2 AT Iq TYPE 1 TYPE 1 1 2 100,000 100,000 A A 480V 480V TYPE 1 TYPE 1 3 4 5 6 7 8 9 * NO HMCPS AVAILABLE ABOVE THIS CURRENT G, H, J K L, M 34, 40, 65 86, 106 52 100,000 100,000 A A 480V 480V TYPE 1 TYPE 1 N 140 P, R, S 170,200, 300 T 450 U 550 V 700 W 700 X 860 * LEVEL * HIGH FAULT TESTING AT 100,000A/480V TO BE COMPLETED IN APRIL, 1997. NO HMCPS AVAILABLE ABOVE THIS CURRENT Z 1200 HMCPE HIGH FAULT UL508 SHORT CIRCUIT CURRENT AND VOLTAGE LISTING BY SIZE. TYPE 1 OR TYPE 2 PERFORMANCE. QUALIFICATION TO IEC 947 CONDITIONAL SHORT CIRCUIT CURRENT Iq. TYPE 1 OR TYPE 2 PERFORMANCE. NEMA SIZES 00 0 1 2 3 4 TESTING IS SUBJECT TO CONFIGURATION DECISION FOR HMCPE, FREEDOM NEMA WITH C306 GMCP OR HMCPS. EXPLORATORY TESTING IS PLANNED FOR 1997 UL508 HIGH FAULT CURRENT UL508 SUBJECT E TYPE 1 OR TYPE 2 FREEDOM IEC SIZE A, B, C D, E, F G, H, J K L, M N C306 AND C316 - AC3 Ie AT 480V 4.8, 7.8, 14, 21, 34, 40, 65 86, 106 140 11 27 52 TESTING IS SUBJECT TO CONFIGURATION DECISION FOR HMCPE, Iq SHORT CIRCUIT QUALIFICATION GMCP OR HMCPS. EXPLORATORY TESTING IS PLANNED FOR 1997 LEVEL IEC 947 TYPE 1 OR TYPE 2 AT Iq LEVEL 5 6 7 8 9 P, R, S 170,200, 300 T 450 U 550 V 700 W 700 X 860 Z 1200 UL 508 STANDARD SHORT CIRCUIT LISTED CURRENT AND VOLTAGE LEVELS BY SIZE FUSES NEMA SIZES 00 0 1 ADVANTAGE SEE SIZE 1L 5,000A UL508 STANDARD SHORT CIRCUIT SIZE 1L 5,000A 600V # 600V UL508 SUBJECT E TYPE 1 OR TYPE 2 TYPE 1 TYPE 1 IEC 947 REQUIRED SHORT SEE SIZE 1L 3,000A CIRCUIT SIZE 1L 1,000A 600V CURRENT LEVEL "r" 600V IEC 947 TYPE 1 OR TYPE 2 TYPE 2 TYPE 2 2 5,000A 600V 3 4 5,000A 10,000A 600V 600V 5 10,000A 600V 6 18,000A 600V TYPE 1 TYPE 2 TYPE 2 3,000A 5,000A 10,000A 600V 600V 600V TYPE 2 10,000A 600V TYPE 2 18,000A 600V TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 7 8 9 NO ADVANTAGE AVAILABLE IN THESE SIZES # Qualified Size 1 & 2 frame using 175A K5 fuse; Size 3 to 6 qualified by 3 cycle "ON" test. HMCP UL 508 STANDARD SHORT CIRCUIT LISTED CURRENT AND VOLTAGE LEVELS BY SIZE NEMA SIZES 00 0 1 2 3 4 ADVANTAGE SEE SIZE 1L 5,000A 5,000A 5,000A 10,000A UL508 STANDARD SHORT CIRCUIT SIZE 1L 5,000A 600V 600V 600V 600V * 600V UL 508 SUBJECT E TYPE 1 OR TYPE 2 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 IEC 947 REQUIRED SHORT CIRCUIT SEE HMCPS CURRENT LEVEL "r" IEC 947 TYPE 1 OR TYPE 2 * Qualified Size 1 & 2 frame using 175A T/M breaker; Size 3 to 6 qualified by 3 cycle "ON" test. 5 10,000A 600V 6 18,000A 600V TYPE 1 10,000A 480V TYPE 1 18000A 600V TYPE 2 TYPE 1 7 8 9 NO ADVANTAGE AVAILABLE IN THESE SIZES THERMAL-MAG BREAKERS UL 508 STANDARD SHORT CIRCUIT LISTED CURRENT AND VOLTAGE LEVELS BY SIZE NEMA SIZES 00 ADVANTAGE SEE UL508 STANDARD SHORT CIRCUIT SIZE 1L * UL508 SUBJECT E TYPE 1 OR TYPE 2 IEC 947 REQUIRED SHORT SEE CIRCUIT SIZE 1L CURRENT LEVEL "r" IEC 947 TYPE 1 OR TYPE 2 0 SIZE 1L 5,000A 600V TYPE 1 SIZE 1L 1,000A 600V TYPE 1 1 5,000A 600V 2 5,000A 600V 3 4 5,000A 10,000A 600V 600V 5 10,000A 600V 6 18,000A 600V TYPE 1 TYPE 1 TYPE 1 TYPE 1 3,000A 3,000A 5,000A 10,000A 600V 600V 600V 600V TYPE 1 10,000A 600V TYPE 1 18,000A 600V TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 7 8 9 NO ADVANTAGE AVAILABLE IN THESE SIZES * Qualified Size 1 & 2 frame using 175A T/M breaker; Size 3 to 6 qualified by 3 cycle "ON" test. UL 508 STANDARD SHORT CIRCUIT LISTED CURRENT AND VOLTAGE LEVELS BY SIZE HMCPS NEMA SIZES 00 0 1 ADVANTAGE SEE SIZE 1L 5,000A UL508 STANDARD SHORT CIRCUIT SIZE 1L 5,000A 600V * 600V UL508 SUBJECT E TYPE 1 OR TYPE 2 TYPE 1 TYPE 1 IEC 947 REQUIRED SHORT SEE SIZE 1L 3,000A CIRCUIT SIZE 1L 1,000A 480V CURRENT LEVEL "r" 480V IEC 947 TYPE 1 OR TYPE 2 TYPE 2 TYPE 2 2 5,000A 600V TYPE 1 3,000A 480V 3 4 5 SEE HMCP 5,000A 480V ** 5,000A 480V TYPE 2 TYPE 2 TYPE 2 * Qualified Size 1 & 2 frame using 175A T/M breaker; Size 3 to 6 qualified by 3 cycle "ON" test. ** Size 4 hp ratings 60hp max covered by 100A HMCPS. *** Size 5 hp ratings up to and including 100hp covered by 150A HMCPS. *** 10,000A 480V TYPE 2 6 7 8 9 NO ADVANTAGE AVAIL-ABLE IN THESE SIZES NO HMCPS AVAILABLE IN THESE SIZES UL 508 STANDARD SHORT CIRCUIT LISTED CURRENT AND VOLTAGE LEVELS BY SIZE GMCP NEMA SIZES 00 0 1 ADVANTAGE SEE SIZE 1L 5,000A UL508 STANDARD SHORT CIRCUIT SIZE 1L 5,000A 480V * 480V UL508 SUBJECT E TYPE 1 OR TYPE 2 TYPE 1 TYPE 1 IEC 947 REQUIRED SHORT SEE SIZE 1L 3,000A CIRCUIT CURRENT LEVEL "r" SIZE 1L 1,000A 480V 480V IEC 947 TYPE 1 OR TYPE 2 TYPE 1 TYPE 1 2 5,000A 480V 3 4 5 6 7 8 9 8 9 NO GMCP AVAILABLE IN THESE SIZES TYPE 1 3,000A 480V TYPE 1 * Qualified Size 1 & 2 frame using 175A T/M breaker. HMCPE NEMA SIZES ADVANTAGE UL508 STANDARD SHORT CIRCUIT UL508 SUBJECT E TYPE 1 OR TYPE 2 IEC 947 REQUIRED SHORT CIRCUIT CURRENT LEVEL "r" IEC 947 TYPE 1 OR TYPE 2 UL 508 STANDARD SHORT CIRCUIT LISTED CURRENT AND VOLTAGE LEVELS BY SIZE 00 0 1 2 3 4 5 6 7 NO PRODUCT AVAILABLE. NO TESTING PERFORMED AT THIS TIME. FUSES HIGH FAULT UL 508 SHORT CIRCUIT CURRENT AND VOLTAGE LISTING BY SIZE. TYPE 1 OR TYPE 2 PERFORMANCE QUALIFICATION TO IEC 947 CONDITIONAL SHORT CIRCUIT CURRENT Iq . TYPE 1 OR TYPE 2 PERFORMANCE NEMA SIZES 00 0 ADVANTAGE SEE SIZE 1L UL508 HIGH FAULT CURRENT SIZE 1L 100,000 A 600V UL508 SUBJECT E TYPE 1 OR TYPE 2 TYPE 2 IEC 947 REQUIRED SHORT SEE SIZE 1L CIRCUIT SIZE 1L 100,000 CURRENT LEVEL Iq A 600V IEC 947 TYPE 1 OR TYPE 2 TYPE 2 HMCP 1 2 3 4 5 6 100,000 100,000 100,000 100,000 100,000A 100,000 A 600V A 600V A 600V A 600V 600V A 600V TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 100,000 100,000 100,000 100,000 100,000A 100,000 A A A A 600V A 600V 600V 600V 600V 600V TYPE 2 TYPE 2 TYPE 2 TYPE 2 TYPE 2 7 8 9 NO ADVANTAGE AVAILABLE IN THESE SIZES TYPE 2 HIGH FAULT UL 508 SHORT CIRCUIT CURRENT AND VOLTAGE LISTING BY SIZE. TYPE 1 OR TYPE 2 PERFORMANCE QUALIFICATION TO IEC 947 CONDITIONAL SHORT CIRCUIT CURRENT Iq . TYPE 1 OR TYPE 2 PERFORMANCE NEMA SIZES 00 0 ADVANTAGE SEE SIZE 1L UL508 HIGH FAULT CURRENT SIZE 1L 100,000 A 480V 25,000A 600V UL508 SUBJECT E TYPE 1 OR TYPE 2 TYPE 1 IEC 947 REQUIRED SHORT CIRCUIT CURRENT LEVEL Iq IEC 947 TYPE 1 OR TYPE 2 1 2 3 4 5 6 100,000 100,000 100,000 100,000 100,000A 100,000 A 480V A 480V A 480V A 480V 480V A 480V 25,000A 25,000A 50,000A 50,000A 50,000A 50,000A 600V 600V 600V 600V 600V 600V TYPE 1 TYPE 1 TYPE 1 TYPE 1 SEE HMCPS TYPE 1 TYPE 1 100,000A 18,000A 480V 600V TYPE 2 TYPE 1 7 8 9 NO ADVANTAGE AVAILABLE IN THESE SIZES THERMAL-MAG BREAKERS HIGH FAULT UL 508 SHORT CIRCUIT CURRENT AND VOLTAGE LISTING BY SIZE. TYPE 1 OR TYPE 2 PERFORMANCE QUALIFICATION TO IEC 947 CONDITIONAL SHORT CIRCUIT CURRENT Iq . TYPE 1 OR TYPE 2 PERFORMANCE NEMA SIZES 00 0 ADVANTAGE SEE SIZE 1L UL508 HIGH FAULT CURRENT SIZE 1L 100,000 A 480V 35,000A 600V UL508 SUBJECT E TYPE 1 OR TYPE 2 TYPE 1 IEC 947 REQUIRED SHORT SEE SIZE 1L CIRCUIT SIZE 1L 100,000 CURRENT LEVEL Iq A 480V 35,000A 600V IEC 947 TYPE 1 OR TYPE 2 TYPE 1 1 2 3 4 5 6 100,000 100,000 100,000 100,000 100,000A 100,000 A 480V A 480V A 480V A 480V 600V A 600V 35,000A 35,000A 35,000A 50,000A 600V 600V 600V 600V TYPE 1 100,000 A 480V 35,000A 600V TYPE 1 100,000 A 480V 35,000A 600V TYPE 1 100,000 A 480V 35,000A 600V TYPE 1 TYPE 1 TYPE 1 100,000 100,000A 100,000 A 480V 600V A 50,000A 600V 600V TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 TYPE 1 7 8 9 NO ADVANTAGE AVAILABLE IN THESE SIZES HMCPS HIGH FAULT UL 508 SHORT CIRCUIT CURRENT AND VOLTAGE LISTING BY SIZE. TYPE 1 OR TYPE 2 PERFORMANCE QUALIFICATION TO IEC 947 CONDITIONAL SHORT CIRCUIT CURRENT Iq . TYPE 1 OR TYPE 2 PERFORMANCE NEMA SIZES 00 0 ADVANTAGE SEE SIZE 1L UL508 HIGH FAULT CURRENT SIZE 1L 50,000A 600V UL508 SUBJECT E TYPE 1 OR TYPE 2 TYPE 1 IEC 947 REQUIRED SHORT SEE SIZE 1L CIRCUIT SIZE 1L 100,000 CURRENT LEVEL Iq A 480V IEC 947 TYPE 1 OR TYPE 2 TYPE 2 1 2 50,000A 50,000A 600V 600V 3 4 SEE HMCP 5 7 8 9 NO HMCPS AVAILABLE IN THESE SIZES TYPE 1 TYPE 1 100,000 100,000 100,000 100,000 100,000A A 480V A 480V A 480V A 480V * 480V ** TYPE 2 TYPE 2 TYPE 2 TYPE 2 6 NO HMCPS AVAILABLE IN THESE SIZES TYPE 2 * 100 AMP HMCPS MAX (60HP) ** 150 AMP HMCPS MAX (100HP) GMCP HIGH FAULT UL 508 SHORT CIRCUIT LISTED CURRENT AND VOLTAGE LEVELS BY SIZE QUALIFICATION TO IEC 947 CONDITIONAL SHORT CIRCUIT CURRENT Iq AND TYPE 2 PERFORMANCE NEMA SIZES 00 0 ADVANTAGE SEE SIZE 1L UL508 HIGH FAULT CURRENT SIZE 1L 25,000A 480V UL508 SUBJECT E TYPE 1 OR TYPE 2 TYPE 1 IEC 947 REQUIRED SHORT SEE SIZE 1L CIRCUIT CURRENT LEVEL Iq SIZE 1L 25,000A 480V IEC 947 TYPE 1 OR TYPE 2 TYPE 1 1 2 25,000A 25,000A 480V 480V TYPE 1 TYPE 1 25,000A 25,000A 480V 480V TYPE 1 TYPE 1 3 4 5 6 7 NO GMCP AVAILABLE IN THESE SIZES 8 9 HMCPE NEMA SIZES ADVANTAGE UL508 HIGH FAULT CURRENT UL508 SUBJECT E TYPE 1 OR TYPE 2 IEC 947 REQUIRED SHORT CIRCUIT CURRENT LEVEL Iq IEC 947 TYPE 1 OR TYPE 2 HIGH FAULT UL 508 SHORT CIRCUIT CURRENT AND VOLTAGE LISTING BY SIZE. TYPE 1 OR TYPE 2 PERFORMANCE QUALIFICATION TO IEC 947 CONDITIONAL SHORT CIRCUIT CURRENT Iq . TYPE 1 OR TYPE 2 PERFORMANCE 00 0 1 2 3 4 5 NO PRODUCT AVAILABLE 6 7 8 9