Downloaded from ascelibrary.org by Dhaka University of Engineering & Technology (DUET) on 03/23/21. Copyright ASCE. For personal use only; all rights reserved. Experimental Investigation and Finite-Element Modeling of an Aluminum Energy Dissipater for Cross-Laminated Timber Walls under Reverse Cyclic Loading Kobir Hossain, A.M.ASCE 1; Sriram Aaleti, M.ASCE 2; and Thang N. Dao, M.ASCE 3 Abstract: Cross-laminated timber (CLT) panels with unbonded post-tensioning and a rocking mechanism can be used as a robust lateral load–resisting system (LLRS). The seismic performance of these systems can be improved further by incorporating external sacrificial energy dissipating elements. The additional damping provided by the energy dissipaters reduces the structural displacement demand during a designlevel earthquake, and the unbonded post-tensioning provides recentering ability. This study developed a surface mountable, easily replaceable sacrificial oval metallic element specific to the CLT walls using aluminum was. This connector contributes to the wall system lateral load capacity. Laboratory testing of the aluminum connectors under cyclic shear loading was performed to characterize the force–displacement behavior and energy dissipating capacity. A detailed three-dimensional (3D) finite-element analysis (FEA) of aluminum connectors was carried out to replicate the observed experimental behavior. The experimental results, analytical modeling, and design equations for connector force– displacement response based on first principles are presented in this paper. The test results showed that the O-connectors can be used as an effective energy-dissipating element with equivalent damping ratio varying between 20% and 40%. The simplified design equations calculated the response within 90% of the measured values. DOI: 10.1061/(ASCE)ST.1943-541X.0002978. © 2021 American Society of Civil Engineers. Introduction Cross-laminated timber (CLT) is an emerging building material in the North America, which is produced by laminating cross-oriented standard-dimension wood planks using glue. Wood structures generally have performed well when subjected to strong earthquakes (van de Lindt et al. 2018). In recent times, there is growing interest among the building construction community, especially in the Pacific Northwest of North America, to use this material for buildings up to 20 stories high (Pei et al. 2014). CLT has been used successfully as prefabricated walls, floor, and roofing elements in residential, nonresidential, and commercial structures across the globe (Iqbal et al. 2015). By taking advantages of CLT compressive strength, dimensional stability, and prefabrication, using existing designs in the precast concrete (Aaleti and Sritharan 2009; Sritharan et al. 2015; Rahman and Restrepo 2000; Restrepo and Rahman 2007) and steel industry for low-damage seismic-resilient systems, the wood engineering community is investigating the use of unbonded post-tensioning (PT) to develop a low-damage lateral load–resisting system with CLT. Pei et al. (2016) found that seismic resiliency can be achieved by using unbonded post-tensioned CLT rocking walls, which remain damage-free in moderate earthquakes and can be repaired easily after large-magnitude earthquakes. 1 Assistant Professor, Dept. of Civil Engineering, Dhaka Univ. of Engineering and Technology, Shimultoly Rd., Gazipur 1707, Bangladesh. Email: mkhossain@crimson.ua.edu 2 Associate Professor, Dept. of Civil, Construction and Environmental Engineering, Univ. of Alabama, Tuscaloosa, AL 35487 (corresponding author). Email: saaleti@eng.ua.edu 3 Associate Professor, Dept. of Civil, Construction and Environmental Engineering, Univ. of Alabama, Tuscaloosa, AL 35487. Email: tndao@ eng.ua.edu Note. This manuscript was submitted on December 13, 2019; approved on December 2, 2020; published online on January 26, 2021. Discussion period open until June 26, 2021; separate discussions must be submitted for individual papers. This paper is part of the Journal of Structural Engineering, © ASCE, ISSN 0733-9445. © ASCE Several researchers attempted to develop efficient, replaceable energy-dissipating elements in various forms using steel for post-tensioned coupled wall system (Fig. 1). Shultz and Magana (1996) developed a U-shape flexural plate (UFP) connector as part of the PREcast Seismic Structural Systems (PRESSS) program, to connect two or more unbonded post-tensioned precast concrete walls along their vertical joints to form a seismicresilient system called a jointed wall system (Priestley 1991). A similar concept can be adopted easily for CLT wall panels as well, in which two or more post-tensioned CLT walls are connected together with energy-dissipating connectors along the vertical joints. Ganey et al. (2017) used UFP connectors to test jointed CLT wall system as part of the Natural Hazards Engineering Research Infrastructure (NHERI) Tall Wood research project. As these PT walls rock under lateral loading, the connectors undergo a relative vertical deformation (Fig. 1), leading these connectors to experience yielding and provide energy dissipation. This UFP connector was made by bending a steel plate into a U-shape, which introduced residual stresses into the steel connector during the fabrication process. The residual stresses were difficult to estimate, and impacted the displacement capacity of connector and predictability of the failure displacement. Henry et al. (2010) studied different forms of externally mountable energy dissipaters such as slotted flexural plates, flexural plates with holes, J-shaped flexural plates, and oval flexural plates using finite-element modeling (FEM). Their study, and an experimental investigation by Aaleti (2009), found that an oval flexural plate, or O-connector, made by cutting the profile from a mild steel plate can serve as an efficient energydissipating element in a UFP connector. A modified version of the O-connector further was investigated experimentally by Twigden and Henry (2015) with different connector proportions (e.g., leg length to thickness ratio), steel grades, and steel plate cutting and welding techniques. They found that the strength and stiffness of the O-connector is affected by the leg length to thickness ratio, cutting and welding process, and the width at the connector base. Twigden and Henry also proposed simple design equations for yield, plastic, 04021025-1 J. Struct. Eng., 2021, 147(4): 04021025 J. Struct. Eng. Downloaded from ascelibrary.org by Dhaka University of Engineering & Technology (DUET) on 03/23/21. Copyright ASCE. For personal use only; all rights reserved. Fig. 1. Jointed rocking CLT wall system: (a) joint wall system; and (b) forces under lateral loads. and ultimate strength of the O-connector. However, no analytical equations were developed to estimate the maximum displacement capacity of the O-connector, which will be critical for the design of these resilient rocking systems. The present study primarily focused on the design and development of an efficient, cost-effective, easy-to-use, replaceable aluminum O-connector for CLT self-centering rocking wall systems. Elementary analytical equations were formed for different characteristic parameters of the O-connector using the principles of engineering mechanics. Based on the analytical formula and knowledge gathered in previous studies, an O-connector (Fig. 2) was fabricated and tested by connecting the CLT walls using different lag-screw connection configurations under reverse cyclic loading following a modified ACI ITG 5.1 (ACI 2007) loading protocol. Finite-element Fig. 2. Schematic of an O-connector, deflected shape, and forces. © ASCE 04021025-2 J. Struct. Eng., 2021, 147(4): 04021025 J. Struct. Eng. modeling in Abaqus CAE version 6.16 was performed to capture the observed experimental behavior. The results from the study are presented in subsequent sections. vertical yield displacement corresponding to the first yield can be calculated using ΔVy ¼ Downloaded from ascelibrary.org by Dhaka University of Engineering & Technology (DUET) on 03/23/21. Copyright ASCE. For personal use only; all rights reserved. Behavior of O-Connector: Elementary Analytical Equations The O-connector was made by cutting an oval profile with two rectangular wings out of a mild steel or aluminum plate. A schematic of the O-connector is shown in Fig. 2. The connector legs undergo flexural yielding as shown by the deformed shapes in Fig. 2, when they are subjected to a relative vertical deformation. Unlike the UFP connector, which is restrained to roll between two vertical surfaces, the O-connector is attached to the exterior faces of the wall panels, making it easier to install and repair. The O-connector also contributes to the system’s moment capacity by transferring shear force between adjacent CLT panels. The O-connector made from mild steel previously was used successfully in unbonded PT precast concrete wall systems (Sritharan et al. 2015; Twigden and Henry 2015). A relative vertical displacement across the connector legs results in a bending moment throughout the length of the connector with a maximum value along the entire length of each straight leg, and decreases to a zero moment at the vertex of the half-circular part. For an O-connector, this moment distribution is symmetric about the vertical centroidal axis. The first yielding occurs along the straight leg, closer to the base connection region. By applying the first principles, the moment and shear force corresponding to first yield can be obtained using Eqs. (1) and (2), respectively My ¼ σy tw2 6 2σy tw2 Fy ¼ 3D ð1Þ σy tw2 4 ð3Þ σy tw2 Fp ¼ D ð4Þ Mp ¼ The coupling shear force can be related to the relative vertical displacement between the connector legs using the Castigliano’s second theorem. Using this method, it can be found that no horizontal force develops at the panel–connector connection region when the connector legs are subjected to relative vertical displacement. The majority of the deformation of the O-connector comes from the flexural deformation of the connector legs. Therefore, when estimating the displacement corresponding to yield capacity and failure, the effects of axial and shear forces were neglected. The © ASCE ð5Þ where ΔVy = vertical displacement at first yield; and E = modulus of elasticity of material. The Supplemental Materials derive the formulas presented in this section. The initial stiffness (ki ) of the O-connector can be calculated by combining the Eqs. (2) and (5) as ki ¼ Fy 4 Etw3 ¼ ΔVy 3 πD3 ð6Þ The horizontal displacement ΔHy of the O-connector at the intersection of the straight leg and the semicircular part can be calculated using Eq. (7), which is same as the displacement at the free edge of a cantilever subjected to a constant moment throughout the entire length ΔHy ¼ M y L2 Fy DL2 3Fy DL2 σy L2 ¼ ¼ ¼ 2EI 4EI Ew Etw3 ð7Þ For materials which exhibit strain hardening behavior under cyclic loading, at the expected maximum strength of the connector, the stresses will be much higher than yield. In such cases, an estimate of the maximum strength (Fu ) of the connector can be obtained by multiplying the plastic load capacity (Fp ) by the material overstrength factor, which is defined as the ratio of ultimate stress (σu ) to the yield stress (σy ) [Eq. (8)]. The maximum displacement (Δmax Þ corresponding to the failure of the connector can be estimated using the Eq. (9), where εx is the failure strain of the material (see Supplemental Materials for derivation) Fu ¼ ð2Þ where σy = yield strength; w and t = width and thickness of O-connector legs, respectively; and D = mean diameter of semicircular part of the O-connector. As the relative vertical displacement between the two legs continues to increase, the strains along the width of the connector legs further increase beyond yielding, leading to majority of the connector leg cross section experiencing yielding. The moment capacity at this point is called the plastic moment, which can be calculated using a uniform compressive and tensile stress distribution equal to the yield stress of the material over one-half the width of the O-connector leg. The resulting equations for the plastic moment (Mp ) and corresponding shear force (Fp ) are πFy D3 3 πFy D3 π σy D2 ¼ ¼ 16EI 4 Etw3 4 Ew σu F ¼ σy p Δmax ¼ σu σy tw2 σy D π D2 εmax 4 w ð8Þ ð9Þ Experimental Program Three experimental tests consisting of 12 O-connectors were performed as part of the experimental program. In addition to characterizing the force–displacement response of the connectors, the effect of number of screws in the O-connector to CLT connection was investigated. O-Connector Specifications The O-connectors tested in the experimental investigation were fabricated from a 6.35-mm-thick (0.25 in.) 3003-H14 aluminum plate. The measured nominal yield and tensile strengths for this aluminum grade were 131 MPa (19 Ksi) and 145 MPa (21 Ksi), respectively. The O-connectors were extracted from the aluminum plate by cutting the profile using a water-jet. A schematic of the O-connector with detail dimensions and a fabricated O-connector are shown in Fig. 3. Twigden and Henry (2015) suggested a leg length to thickness ratio of less than 20 for steel O-connector in order to avoid the onset of premature buckling of the connector. Considering the lower strength and stiffness properties of aluminum compared with that of steel, for the design of the aluminum O-connector, the leg length to thickness ratio was 10, which was half 04021025-3 J. Struct. Eng., 2021, 147(4): 04021025 J. Struct. Eng. Downloaded from ascelibrary.org by Dhaka University of Engineering & Technology (DUET) on 03/23/21. Copyright ASCE. For personal use only; all rights reserved. Fig. 3. Schematic of the O-connector tested in the experimental program: (a) O-connector dimensions; and (b) fabricated O-connector. that recommended by Twigden and Henry for steel O-connectors. This resulted in an O-connector with overall width and height of 228.6 mm (9 in.) and 304.8 mm (12 in.), respectively. The width of the connector legs was 32 mm (1.25 in.), and the clear distance between two legs was 63.5 mm (2.5 in.). The O-connector had two rectangular wings at the centerline to facilitate the connection to CLT panels. The width and height of these wings were 112.7 mm (4.44 in.) and 50.8 mm (2 in.), respectively. The rectangular wings contained 6.35-mm-diameter (0.25 in.) holes spaced at 22.2 mm (0.875 in.) in horizontal direction and 25.4 mm (1 in.) vertical direction, which were used to connect the connectors to CLT using standard 6.25-mm-diameter (0.25 in.) lag screws. The diameter of the hole was kept the same as the diameter of lag screws to prevent any slipping during testing and to have a rigid connection. Material Properties The 0.61 × 0.61-m (2 × 2-ft) CLT panels used in this study were fabricated using graded Douglas fir timber boards in accordance with ANSI/APA PRG-320 (ANSI/APA 2012). The CLT panels consisted of five layers, each of which was 25.4 mm (1 in.) thick, resulting in a total thickness of 127 mm (5 in.). The moisture content at the time of production of the CLT was reported by the manufacturer to be 12% by weight, and the testing presented here was conducted without controlling the moisture content. The average compressive strength and modulus of elasticity in compression of the CLT were determined experimentally as 27.5 MPa (4,000 psi) and 6,200 MPa (900 Ksi), respectively. Two tensile dog-bone coupons from the same aluminum plate used for the O-connector were © ASCE extracted and tested following ASTM B557M-15 (ASTM 2015) specifications. The test setup, a failed aluminum dog-bone specimen, and the stress–strain diagrams are shown in Fig. 4. The material properties determined from the aluminum tensile coupon tests are presented in Table 1. O-Connector Test Setup A test setup was designed using 0.61 × 0.61-m (2 × 2-ft) CLT wall panels and steel plates to apply the desired vertical relative displacement to the O-connector legs using a hydraulic jack (Fig. 5). The test setup consisted of a steel reaction frame, hydraulic jack, and a total of three five-ply CLT panels, including two 0.61 × 0.61-m (2 × 2 ft) outer panels and one 0.61 × 0.305-m (2 × 1-ft) intermediate panel. The vertical reaction frame was post-tensioned to the strong floor using two 37-mm-diameter (1.5 in.) posttensioning bars tensioned to 266.9 kN (60 kip) each. In addition, a 2.13-m-long (7 ft), 406-mm-deep (16 in.) steel reaction beam was simply supported on 100-mm-thick (4 in.) steel plates and posttensioned to the strong floor using a 37-mm-diameter (1.5 in.) post-tensioning bar tensioned to 266.9 kN (60 kip). The steel reaction beam mimicked the foundation in a real structure and was used to anchor the outer CLT panels. A 25-mm-diameter (1 in.) hole was drilled at the center of the outer CLT panels through the entire height of the panel and a 19-mm-diameter (0.75 in.) B7 threaded rod in combination with a 550-kN (120-kip) centerhole hydraulic jack was used to anchor the panels to the steel reaction beam with a constant compression force of 133.4 kN (30 kips). The outer and intermediate CLT panels were connected 04021025-4 J. Struct. Eng., 2021, 147(4): 04021025 J. Struct. Eng. Downloaded from ascelibrary.org by Dhaka University of Engineering & Technology (DUET) on 03/23/21. Copyright ASCE. For personal use only; all rights reserved. Fig. 4. Aluminum coupon test setup and measured stress–strain response: (a) test setup; (b) tensile fracture; and (c) stress–strain response. Table 1. Aluminum tensile coupon test results Specimen ID 1 2 0.2% offset yield strength [MPa (Ksi)] 0.2% offset yield strain (mm/mm) Ultimate strength [MPa (Ksi)] Rupture strength [MPa (Ksi)] Modulus of elasticity [GPa (Ksi)] 132.4 (19.2) 131.7 (19.1) 0.0035 0.0040 148.0 (21.5) 147.9 (21.5) 115.6 (16.8) 113.4 (16.4) 75.25 (10913) 69.64 (10100) Fig. 5. O-connector test setup: (a) test setup for O-connector testing; and (b) close-up of Test specimen 1 and instrument. © ASCE 04021025-5 J. Struct. Eng., 2021, 147(4): 04021025 J. Struct. Eng. Downloaded from ascelibrary.org by Dhaka University of Engineering & Technology (DUET) on 03/23/21. Copyright ASCE. For personal use only; all rights reserved. Fig. 6. Loading protocol for O-connector test. together with O-connectors on both faces. The connectors were attached to the CLT panels with 6.35-mm-diameter (0.25 in.) standard lag screws driven symmetrically about the connector axes. The CLT–O-connector connection was designed following the NDS design specifications (AWC 2015). Details of this connection are provided in the next section. To apply a direct shear force to the O-connector without subjecting it to any eccentric loading, four O-connectors were tested together in aforementioned test setup. Additionally, this arrangement provided a more accurate average of the connector response, allowing for variations in the manufacturing process and producing a broader validation than testing a single connector. The double-acting hydraulic jack with a 445kN (100-kip) load cell was attached to the intermediate CLT panel using high-strength threaded rods. The intermediate panel was moved up and down using the hydraulic jack to apply a relative displacement between the two legs of the O-connector, emulating relative displacements expected for connectors in a typical jointed rocking CLT wall system. Small 25-mm-wide (1 in.) aluminum plates around the connector legs were used in Tests 2 and 3, providing restraint to prevent any out-of-plane buckling of the connector legs [Fig. 3(b)]. These plates did not constrain the in-plane movement of the connector. The displacement of the connectors was measured using two different instruments: LVDTs and an NDI (Waterloo, Ontario) Optotrak three-dimensional (3D) noncontact digital distance measurement system. In addition, in Test 2, two strain gauges were used on opposite sides of a straight leg of one connector to monitor the critical strains at the two extreme faces of the connector. In Test 3, five strain gauges were used, four of which were placed on opposite faces of two straight legs, and one of which was placed at the vertex of a connector. The total load carried by the four connectors was measured using a 445-kN (100-kips) load cell. Data from all the instruments was collected continuously at 20-Hz frequency using a standard data acquisition system. Loading Protocol CLT to O-Connector Connection The O-connectors were connected to CLT panels using 6.35 × 76.2-mm (¼ × 3-in:), hex-head lag screws [Fig. 7(c)]. The lag screw dimensions are listed in Table 2. The mechanical connections between O-connector and CLT panel using lag screws were designed following National Design Specification (NDS) 2015 (AWC 2015) and the CLT Design Handbook (CLT Handbook 2013). NDS treats lag screws as a dowel bearing–type fastener and uses the European Yield Limit Model to calculate the design capacity of a single fastener, known as the reference design value in shear. The Yield Limit Model considers different failure mechanisms, such as crushing in main member (CLT in this case), crushing in side member (aluminum O-connector base plate), rotation of fastener, plastic hinge and crushing in main member, plastic hinge and crushing in side member, and two plastic hinges per shear plane, for calculating the capacity of a wood–wood or wood–metal connection using a dowel bearing fastener. The lowest among the values given by these yield limit equations is considered as the reference design value. Each of the yield limit equations includes the dowel bearing strength of either a main member or a side member. The reference design value for each lag screw was calculated to be 578 N (130 lb). In Test 1, a total of eight lag screws were used at each base of the leg [Fig. 7(a)]. In Tests 2 and 3, a total of six lag screws were used at each base [Fig. 7(b)]. Test Observations and Results The O-connectors were tested under displacement control loading. The connectors were subjected to a displacement history, in which the peak connector displacements (Fig. 6) were selected following the ACI ITG 5.1 loading protocol for testing and validation of posttensioned rocking wall behaviors. The loading started with three © ASCE cycles of 2.54 mm (0.1 in.), after which each loading displacement was increased by almost 25% and each loading step was repeated for three complete cycles, except the last loading cycles. The hydraulic jack was operated using a manual hydraulic pump, and the rate of loading was controlled by observing the vertical displacement measured by LVDTs. The loading procedure was stopped several times during the test to observe condition of the connectors and to take pictures after a specified displacement had been applied. Reverse cyclic loading tests were conducted to obtain the force– displacement (F-Δ) response and energy dissipation capacity of the connectors and to verify the analytical equations for practical use. The hysteretic force–displacement responses from all the 04021025-6 J. Struct. Eng., 2021, 147(4): 04021025 J. Struct. Eng. Downloaded from ascelibrary.org by Dhaka University of Engineering & Technology (DUET) on 03/23/21. Copyright ASCE. For personal use only; all rights reserved. Fig. 7. Screw connections for O-connector tests: (a) eight-screw connection in Test 1; (b) six-screw connection in Tests 2 and 3; and (c) screw used for O-connector tests. (Images by authors.) Table 2. Lag screw dimensions Property Nominal diameter Root diameter Length Tapered tip length Height of head Value [mm (in.)] 6.35 4.40 76.2 4.06 4.36 (0.25) (0.173) (3.0) (0.16) (0.172) three tests are shown in Figs. 8–10. The deformed shapes of a connector at 12.5 mm (0.5 in.), 25.4 mm (1 in.), and at the displacement when the O-connector experienced significant out-of-plane buckling also are shown in these figures. In Test 1, the O-connectors experienced premature out-of-plane buckling at a displacement level of 12.7 mm (0.50 in.), and the test was terminated at that loading cycle. Based on the observations from Test 1, small aluminum plates were added as restraining plates in Tests 2 and 3 to Fig. 8. F-Δ response and deformed shape of O-connector Test 1: (a) force–displacement response; (b) deformed shape of O-connector at 7.5 mm; and (c) deformed shape of O-connector at 15 mm. © ASCE 04021025-7 J. Struct. Eng., 2021, 147(4): 04021025 J. Struct. Eng. Downloaded from ascelibrary.org by Dhaka University of Engineering & Technology (DUET) on 03/23/21. Copyright ASCE. For personal use only; all rights reserved. Fig. 9. F-Δ response and deformed shape of O-connector Test 2: (a) force–displacement response; (b) deformed shape of O-connector at 12.5 mm; (c) deformed shape of O-connector at 25.4 mm; and (d) deformed shape of O-connector at 31.75 mm. Fig. 10. F-Δ response and deformed shape of O-connector Test 3: (a) force–displacement response; (b) deformed shape of O-connector at 12.5 mm; (c) deformed shape of O-connector at 25.4 mm; and (d) deformed shape of O-connector at 35.5 mm. prevent the onset of local buckling [Figs. 9(b) and 10(b)]. With these restraining plates, the O-connectors in Tests 2 and 3 were able to undergo large displacement cycles up to 32 mm (1.25 in.) while reaching their ultimate load carrying capacities [Figs. 9(a) and 10(a)]. The F-Δ responses obtained from Tests 2 and 3 had stable hysteretic loops for each loading cycle until failure initiated by outward buckling of the unrestrained semicircular part of the Oconnector. However, no fracture occurred at this displacement level except signs of yielding on the surfaces. Yielding of O-connectors’ straight legs was observed at a vertical displacement of 19 mm (0.75 in.) (Fig. 11). Yielding occurred only in the straight legs of the O-connector, whereas the semicircular part remained elastic, supporting the expected the moment distribution along the Oconnector length used to derive the analytical equations. © ASCE Energy Dissipation The energy dissipation for a cycle of displacement is calculated by estimating the total area enclosed by the force–displacement response corresponding to that displacement cycle. Fig. 12(a) shows the energy dissipated by the connectors at different displacement cycles from all three tests. Because the connectors in Test 1 experienced out-of-plane buckling at small displacements, the calculated energy dissipation capacity of the O-connector from that test was lower than that obtained from other tests. The approximate total energy dissipation per connector before failure due to buckling was calculated to be 1,136 J (835 ft-lb), 3,854 J (2,843 ft-lb) and 4,235 J (3,124 ft-lb) for Tests 1, 2, and 3, respectively. The low energy-dissipation capacity of the O-connector in Test 1 compared 04021025-8 J. Struct. Eng., 2021, 147(4): 04021025 J. Struct. Eng. Downloaded from ascelibrary.org by Dhaka University of Engineering & Technology (DUET) on 03/23/21. Copyright ASCE. For personal use only; all rights reserved. Fig. 13. Calculation of equivalent damping ratio. Fig. 11. Yielding of O-connector at four legs in O-connector Test 3. to Tests 2 and 3 indicates the necessity of out-of-plane buckling restraint to enhance its energy dissipation capacity. The equivalent viscous damping ratio at each peak displacement cycle, defined as the ratio of energy dissipated by the connector in that displacement cycle to the available potential energy in that cycle multiplied by 4π (Fig. 13) (Blandon 2004) was calculated. The calculated equivalent damping ratios for the connectors in all the three tests are shown in Fig. 12(b). The damping ratio of the connector increased with displacement, and it varied between 18% and 42% depending on the vertical displacement level. Gavric et al. (2015) found the equivalent viscous damping ratio for standard hold-downs, such as WHT540 and WHT440 under shear loading to be 19.84% and 21.38% respectively. Similarly, Gavric et al. (2015) found that the equivalent viscous damping ratios for steel angle brackets, such as BMF90 × 116 × 48 × 3 and BMF100 × 100 × 90 × 3, was 22.75% and 17.49% respectively. The damping ratio of the O-connector was higher than those of the aforementioned standard hold-downs and angle brackets. Baird et al. (2014) tested a UFP connector made of 8-mm-thick (5=8 in:) 320-MPa (45-Ksi) steel plate with outer dimensions of 136 mm (5.35 in.), similar to the outer dimensions of the O-connector tested in this study. The measured yield and maximum force capacity of the UFP connector were 6.4 kN (1.41 k) and 12.5 kN (2.81 k), respectively. The UFP connector had equivalent viscous damping ratios between 3% and 47% depending on the vertical deflection. The maximum energy dissipation ratio of the O-connector was 10% lower than that of the UFP connector. However, at the lower displacements, for example, at 29 mm (1.15 in.) vertical displacement, the Oconnector had a higher damping ratio (42%) than the UFP connector (32%). The O-connector had similar performance in terms of energy dissipation capacity compared with that of a UFP connector with similar force capacities. Therefore, this O-connector can be used as a significant source of energy dissipation and damping for building construction with CLT. The seismic performance of CLT buildings with the O-connectors will be similar to that with UFP connectors. Discussion of Results Stiffness and Strength Calculations Using Eqs. (2), (7), and (8), the yield load capacity of the Oconnector calculated based on the determined material properties was 5.87 kN (1,320 lb) with a vertical (ΔVy ) and horizontal (ΔHy ) yield displacement of 0.81 mm (0.032 in.) and 0.46 mm (0.018 in.), respectively. The ratio of vertical to horizontal yield displacement Fig. 12. (a) Energy dissipation of O-connectors; and (b) equivalent damping ratio of O-connectors. © ASCE 04021025-9 J. Struct. Eng., 2021, 147(4): 04021025 J. Struct. Eng. Downloaded from ascelibrary.org by Dhaka University of Engineering & Technology (DUET) on 03/23/21. Copyright ASCE. For personal use only; all rights reserved. was calculated as 1.77, with the horizontal displacement calculated at the intersection of the straight leg and the half-circular part. The maximum load capacity of the O-connector was calculated based on a fully plastic section as 8.81 kN (1,980 lb); from the measured F-Δ behavior of Tests 2 and 3, the yielding of the O-connectors was found to occur at approximately 88% of the calculated yield force; however, the displacements at yield obtained from the tests were approximately 3 times higher than the calculated yield displacement. The yielding of the O-connectors occurred at the first cycle of displacement loading, which was 2.54 mm (0.1 in.), and this was confirmed with the measured strain in the straight legs. This difference in the yield displacement might be due to the base rotation and/or the connection slack between the lag screws and the holes. Although the diameter of the hole was same as the diameter of lag screw, some of the holes were not perfectly circular because they were tapped using a hand drill and some degree of inaccuracy was unavoidable in that process. However, once the gaps between the lag screws and cylindrical surface of the holes were closed, the connectors engaged themselves to carry force. The base rotation was associated with this connection slack as well because of the small vertical movement of lag screws. For Tests 2 and 3, the base rotations were found to be considerable. The base rotation increased the relative vertical displacement, and therefore should be incorporated in the analytically derived formula. In the tests, when the connectors were unloaded from a peak displacement level, the force decreased from its peak value to zero with a small change in vertical displacement compared with the total displacement, and the stiffness and strength decreased during the repeated loading cycles. This might have been due to the local buckling of the connector in addition to the repetition of loading (Bauschinger effect). When the cross section of straight legs became fully plastic, there was no increase in force, but the displacement increased until the legs reached failure strain. Therefore, analytically the force–displacement response after plastic hinge formation was a horizontal straight line. The peak force–peak vertical displacement responses at each loading cycle for Tests 2 and 3 are shown in Fig. 14. Based on the experimental results, a bilinear force–vertical displacement relationship (Fig. 14) is proposed for practical use. The bilinear elastic-plastic force–displacement model predicts the force developed in the connector for a design vertical displacement at the base of the connector. The inclined part of the model is formed by connecting the origin and the analytical yield point until it meets the backward projection of the horizontal ultimate load–displacement line. After the intersecting point, the force–displacement response is a horizontal line until it reaches the failure displacement value. This model is presented mathematically as Yield force; Fy ¼ Elastic vertical displacement; ΔV ¼ ð10Þ 3 πFv D3 4L 1 þ 4 Etw3 πD 3 for Fv < Fy 2 Plastic force; ΔVy < ΔV ≤ Δmax 3 for Fv ¼ Fp ¼ Fy 2 Maximum vertical displacement; Δmax ¼ π D2 εmax 4 w ð11Þ ð12Þ ð13Þ The strain at the legs of the O-connectors was measured in Tests 2 and 3. The peak strain versus peak vertical displacement at each displacement cycle of the connector is shown in Fig. 15. The measured strains beyond 0.03 mm=mm were not useful because the strain-measuring limit of the strain gauge was 0.03. Although these strain variations with respect to vertical displacement did not have a specific correlation, a linear relationship between strain and vertical displacement is useful to predict the ultimate displacement capacity of the O-connector. From the principle of engineering mechanics, the relationship between displacement and curvature for an elastic system was used to develop a relationship between plastic displacement and curvature. Because the curvature is obtained by dividing the strain by the depth of the neutral axis, the displacement can be calculated from the strain. The ultimate vertical displacement capacity calculated using Eq. (13) was 35.8 mm (1.41 in.), whereas the test results indicated no fracture at a vertical displacement of 32 mm (1.25 in.) while experiencing out-of-plane buckling. This design equation can be used to predict conservatively the maximum displacement capacity of O-connector before fracture. The yield Fig. 14. Peak force–vertical displacement plot. © ASCE 2σy tw2 3D Fig. 15. Peak strain versus peak vertical displacement plot. 04021025-10 J. Struct. Eng., 2021, 147(4): 04021025 J. Struct. Eng. Downloaded from ascelibrary.org by Dhaka University of Engineering & Technology (DUET) on 03/23/21. Copyright ASCE. For personal use only; all rights reserved. Fig. 17. FEM of the test configuration and the O-connectors: (a) FEM assembly; and (b) FEM at 38-mm (1.5-in.) vertical displacement. Fig. 16. Measured peak vertical displacement and measured corresponding horizontal displacement. force can be calculated from the material and cross-sectional properties of the connector using Eq. (10), and Eq. (11) can be used to calculate the yield displacement. Any displacement corresponding to a force smaller than 1.5Fy is calculated using Eq. (11) as well. Relationship between Vertical and Horizontal Displacement As one base of the O-connector moves up and down relative to the other base, the connector legs and the semicircular parts move in horizontal direction. Appropriate prediction of the horizontal displacement at the intersection of straight leg and half-circular part for a given relative vertical displacement of the O-connector is important before using the connection in building system. Knowing the associated horizontal displacement beforehand allows the designer to provide enough room for lateral movement that will occur during an earthquake or severe wind event. The relationship between vertical and horizontal displacement of the O-connector was determined. The ratio of the analytical vertical to horizontal yield displacements is ΔyV π D2 ¼ ΔyH 4 L2 ð14Þ which equaled 1.77 for the geometry of the O-connector tested in the experimental program. From the measured experimental results, this ratio was found to be very close to 1.77 (Fig. 16). This supports the validity of analytical equations derivation, and Eq. (14) provides an effective way to calculate the expected horizontal lateral displacement associated with the relative vertical displacement for a given connector. Three-Dimensional Finite-Element Analysis To better understand the observed hysteretic behavior of the aluminum O-connector tested in the experimental program, a detailed finite-element model for the test configuration was developed using Abaqus 2016 (Fig. 17). The FEM of the test configuration was constructed using three-dimensional deformable elements. Because no © ASCE damage was observed in the CLT panels during testing, the CLT panels were modeled with an elastic material using the measured properties of the CLT described in the section “Material Properties.” The material behavior of the O-connector was represented using a multilinear nonlinear material model with the stress–strain response obtained from the aluminum tensile coupon test results. A combined kinematic/ isotropic hardening property was used to simulate the material model. The material model parameters, such as modulus of elasticity, yield strength, failure stress, and corresponding strain, were taken from the measured properties from the coupon tests (Table 1). No failure criteria were used in the aluminum material definition, so the stress–strain response showed no strength loss beyond the ultimate strain of 0.16 mm=mm. This did not affect the results of the analysis, because a strain limit of 0.095 (60% of ultimate strain.) was used to determine the ultimate displacement capacity for each connector. The CLT panels were meshed using linear 3D stress elements with eight nodes (i.e., C3D8R in Abaqus) and one integration point per element. The mesh size was approximately 50.8 mm (2 in.). The O-connectors were meshed using a four-node 3D stress elements (C3D4), and the mesh size was 3.175 mm (0.125 in.). The restraint conditions were idealized to reduce computational time. The lag screw connections between CLT panels and O-connectors were modeled in finite element analysis (FEA) using tie constraints. Each screw was modeled using an equivalent square area, with each side 2 times the diameter of screw. The tie constraints were allowed to rotate to some degree to simulate the rotation of the connector wings observed in the experiments. This was done by defining a rotational constraint ratio (CR). The rotations of the connector wings at the connection region were measured using the NDI system, a noncontact 3D displacement measurement system in the experiments. Based on the measured rotation of the connector wings in Test 2, a rotational constraint ratio of 50% was used to simulate the observed rotation at the connection region. Similarly, for Test 3, a rotational constraint ratio of 25% was used, based on the experimental observations. The rotational constraint ratio was chosen by trial and error to match the measured rotation of the connector wings. The post-tensioned outer CLT panels were simulated by coupling the bottom surfaces of the CLT panels to a reference point, where the fixed boundary conditions were applied. The top face of the interior CLT panel was coupled in all degrees of 04021025-11 J. Struct. Eng., 2021, 147(4): 04021025 J. Struct. Eng. Downloaded from ascelibrary.org by Dhaka University of Engineering & Technology (DUET) on 03/23/21. Copyright ASCE. For personal use only; all rights reserved. Fig. 18. Experimental and FEA results for F-Δ response: (a) O-connector Test 2; and (b) O-connector Test 3. freedom to a reference point which was used to control the loading. The displacement-controlled loading was applied by defining a displacement boundary condition on the reference point and restraining movement of the intermediate CLT panel in all degrees of freedom except the vertical. The experimentally measured reversed cyclic loading history was applied on the reference point in the same increments as in the experimental testing. The FEM analyses produced force–displacement curves from the output at the reference point as well as the local stress and strain values for each element. The predicted force–displacement responses of a single connector from the FEA of Tests 2 and 3 configurations are plotted alongside the test results in Fig. 18. The F-Δ responses show the impact of the connection flexibility on the overall response of the connector. The FEM accurately predicted the connector response when the connection flexibility is considered. The FEM accurately predicted the loading and unloading stiffness and only marginally underestimated the connector strength. Fig. 19. Measured and calculated strains in a critical location of a connector. © ASCE The measured and FEA predicted peak strains in the connector from Tests 2 and 3 are plotted with connector vertical displacements in Fig. 19. The vertical displacement of the FEA results was related linearly to the strain beyond yielding of the connector, which was supported by the experimental results. The strain beyond 0.03 mm=mm in experimental results was not usable because it was beyond the strain-measuring limit of strain gauges. This observation about the linear relationship between strain and vertical displacement supports the analytical equation for calculating the ultimate displacement capacity of the O-connector. Conclusions This paper presented the development of an oval aluminum energy dissipater (O-connector) for coupled post-tensioned CLT wall systems. Three test specimens, each containing four O-connectors, were tested under reversed cyclic loading to characterize the response of the O-connectors. A detailed 3D finite-element model of the test configuration was developed in Abaqus and validated using the experimental results. The following conclusions were drawn based on the experimental and finite-element analysis results: 1. The aluminum O-connector has a stable hysteretic force– displacement response and can provide sufficient amount of energy dissipation by undergoing comparatively large vertical displacement. 2. The premature out-of-plane buckling of the O-connector legs have a significant influence on the force–displacement response of the connector, as shown by Test 1. This problem can be overcome easily by adding a simple restraining plate, as shown in the second and third tests. 3. A small amount of rotation in the O-connector–CLT connection is expected when they are connected together by means of lag screws. Metal–CLT (wood) connections with lag screws should not be considered as fixed; rather, they should be considered as flexible connections with a relative degree of fixity. This flexibility can be captured by defining the degree of rotational constraint for the connection region in finite-element models. A rotational constraint ratio of 0.25–0.5 seems to provide reasonable predictions for overall force–displacement response. 04021025-12 J. Struct. Eng., 2021, 147(4): 04021025 J. Struct. Eng. Downloaded from ascelibrary.org by Dhaka University of Engineering & Technology (DUET) on 03/23/21. Copyright ASCE. For personal use only; all rights reserved. 4. The finite-element analysis model accurately predicted both the connector strength and critical strains. The capacity of the connector predicted by the FEA model was 3% more than the measured response. 5. Analytical expressions based on the first principles for predicting the force–displacement response of the O-connector were developed. The values predicted using the analytical expressions were within 88%–92% of the measured O-connector forces. Thus, these analytical expressions can be used for designing O-connectors for coupled rocking wall systems. Data Availability Statement Some or all data, models, or code generated or used during the study are available in a repository online in accordance with funder data retention policies. The repository is accessible at https://www .designsafe-ci.org/data/browser/public/designsafe.storage.published// PRJ-2485. Acknowledgments The authors acknowledge the financial support from National Science Foundation (NSF) for this research under Grant No. CMMI 1537788. The authors thank Collin Sewell, research engineer at the Large Scale Structures Laboratory at The University of Alabama, and several undergraduate students for helping with test setup and testing. The opinions, findings, and conclusions expressed in the paper are those of the authors, and do not necessarily reflect the views of NSF. Supplemental Materials Figs. S1 and S2 are available online in the ASCE Library (www .ascelibrary.org). References Aaleti, S. 2009. “Behavior of rectangular concrete walls subjected to simulated seismic loading.” Ph.D. dissertation, Dept. of Civil, Construction and Environmental Engineering, Iowa State Univ. Aaleti, S., and S. Sritharan. 2009. “A simplified analysis method for characterizing unbonded post-tensioned precast wall systems.” Eng. Struct. 31 (12): 2966–2975. https://doi.org/10.1016/j.engstruct.2009.07.024. ACI (American Concrete Institute). 2007. Acceptance criteria for special unbonded post-tensioned precast structural walls based on validation testing. Farmington Hills, MI: ACI. ANSI/APA (American National Standards Institution/APA–The Engineered Wood Association). 2012. Standard for performance-rated cross-laminated timber. ANSI/APA PRG 320-2012. Tacoma, WA: ANSI/APA. ASTM. 2015. Standard test methods for tension testing of wrought and cast aluminum- and magnesium-alloy products. ASTM B557M. West Conshohocken, PA: ASTM. AWC (American Wood Council). 2015. National design specification for wood construction. ANSI/AWC NDS-2015. Leesburg, VA: AWC. © ASCE Baird, A., T. Smith, A. Palermo, and S. Pampanin. 2014. “Experimental and numerical study of U-shape flexural plate (UFP) dissipators.” In Proc., New Zealand Society for Earthquake Engineering (NZSEE) Annual Technical Conf. Auckland, New Zealand: Aotea Centre. Blandon, U. 2004. “Equivalent viscous damping for direct displacement based design.” M.Sc. thesis, Rose School, European School of Advanced Studies in Reduction of Seismic Risk. CLT Handbook. 2013. CLT handbook: Special publication SP-529E. Pointe-Claire, QC, Canada: FPInnovations. Ganey, R., J. Berman, T. Akbas, S. Loftus, J. D. Dolan, R. Sause, J. Ricles, S. Pei, J. van de Lindt, and H.-E. Blomgren. 2017. “Experimental investigation of self-centering cross-laminated timber walls.” J. Struct. Eng. 143 (10): 04017135. https://doi.org/10.1061/(ASCE)ST.1943 -541X.0001877. Gavric, I., M. Fragiacomo, and A. Ceccotti. 2015. “Cyclic behaviour of typical metal connectors for cross-laminated (CLT) structures.” Mater. Struct. 48 (6): 1841–1857. https://doi.org/10.1617/s11527-014-0278-7. Henry, R. S., S. Aaleti, S. Sritharan, and J. M. Ingham. 2010. “Concept and finite-element modeling of new steel shear connectors for self-centering wall systems.” J. Eng. Mech. 136 (2): 220–229. https://doi.org/10.1061 /(ASCE)EM.1943-7889.0000071. Iqbal, A., S. Pampanin, A. Palermo, and A. H. Buchanan. 2015. “Performance and design of LVL walls coupled with UFP dissipaters.” J. Earthquake Eng. 19 (3): 383–409. https://doi.org/10.1080/13632469 .2014.987406. Pei, S., J. Berman, D. Dolan, J. van de Lindt, J. Ricles, R. Sause, H.-E. Blomgren, M. Popovski, and D. Rammer. 2014. “Progress on the development of seismic resilient tall CLT buildings in the Pacific Northwest.” In Proc., World Conf. on Timber Engineering. Quebec City, Canada: World Conference on Timber Engineering. Pei, S., D. Rammer, M. Popovski, T. Williamson, P. Line, and J. W. van de Lindt. 2016. “An overview of CLT research and implementation in North America.” In Proc., World Conf. on Timber Engineering. Vienna, Austria: World Conference on Timber Engineering. Priestley, M. J. N. 1991. “Overview of PRESSS research program.” PCI J. 36 (4): 50–57. https://doi.org/10.15554/pcij.07011991.50.57. Rahman, A. M., and J. I. Restrepo. 2000. Earthquake resistant precast concrete buildings: Seismic performance of cantilever walls prestressed using unbonded tendons. Research Rep. 2000-5. Christchurch, New Zealand: Univ. of Canterbury. Restrepo, J. I., and A. Rahman. 2007. “Seismic performance of selfcentering structural walls incorporating energy dissipators.” J. Struct. Eng. 133 (11): 1560–1570. https://doi.org/10.1061/(ASCE)0733-9445 (2007)133:11(1560). Shultz, A. E., and R. A. Magana. 1996. “Seismic behavior of connections in precast concrete walls.” In Proc., Mete A. Sozen Symp., Farmington Hills, MI: American Concrete Institute. Sritharan, S., S. Aaleti, R. S. Henry, K.-Y. Liu, and K.-C. Tsai. 2015. “Precast concrete wall with end columns (PreWEC) for earthquake resistant design.” Earthquake Eng. Struct. Dyn. 44 (12): 2075–2092. https://doi .org/10.1002/eqe.2576. Twigden, K. M., and R. S. Henry. 2015. “Experimental response and design of O-connectors for rocking wall systems.” Structures 3 (Aug): 261– 271. https://doi.org/10.1016/j.istruc.2015.06.002. van de Lindt, J. W., J. Furley, M. O. Amini, S. Pei, G. Tamgnone, A. R. Barbosa, D. Rammer, P. Line, M. Fragiacomo, and M. Popovski. 2018. “Experimental seismic behavior of a two-story CLT platform building.” Eng. Struct. 183 (Mar): 408–422. https://doi.org/10.1016/j.engstruct .2018.12.079. 04021025-13 J. Struct. Eng., 2021, 147(4): 04021025 J. Struct. Eng.