STREAMFLOW MEASUREMENT THE VELOCITY-AREA METHOD VOLUME 1 JULY 2002 STREAMFLOW MEASUREMENT THE VELOCITY - AREA METHOD VOLUME 1 COMPILED: M.C.BRIGGS J.C.CAMERON L.J.TEPPER TABLE OF CONTENTS INTRODUCTION ................................................. 1 1.0 METHODS OF STREAMFLOW MEASUREMENT ........................ 2 1.1 Velocity - Area Method.................................. 2 1.2 Float Gauging........................................... 2 1.3 Slope - Area Method..................................... 2 1.4 Stage - Fall - Discharge Method......................... 2 1.5 Weirs and Flumes........................................ 3 1.6 Dilution Method......................................... 3 1.7 Moving boat Method...................................... 3 1.8 Volumetric Measurement.................................. 3 1.9 Continuously recording Flow Meters...................... 4 1.9.1. Mechanical ......................................... 4 1.9.2. Ultrasonic ......................................... 5 1.9.3 Acoustic Doppler .................................... 5 1.9.4 Electromagnetic .................................... 6 1.10 Flow Measurement Units................................. 6 2.0 THE VELOCITY-AREA METHOD OF STREAM FLOW MEASUREMENT ..... 10 2.1 Spacing of Verticals................................... 10 2.1.1 Segments of equal flow ............................. 10 2.1.2 Bed profile. ....................................... 10 2.1.3 Equidistant ........................................ 10 2.2 Measurement of Velocity................................ 11 2.2.1 Vertical velocity curve method ..................... 12 2.2.2 The one-point or six-tenths method ................. 15 2.2.3 Two-point method ................................... 15 2.2.4 Three-point method ................................. 15 2.2.5 Five point method .................................. 16 2.2.6 Six point method ................................... 16 2.2.7 Surface Velocity Measurement ....................... 16 2.2.8 Bed Velocity Measurement ........................... 17 2.3 Computation of Current Meter Measurements.............. 17 2.3.1 Mid-section method ................................. 17 2.3.2 Mean section method ................................ 19 2.3.3 Velocity – Depth Integration method ................ 20 2.3.4 Velocity – Contour method .......................... 21 2.4 Procedure for Measurement of Discharge by Current Meter 22 2.4.1 Selection of gauging site. ......................... 22 2.4.2 Current meter measurement by wading ................ 23 2.4.3 Current meter measurement from cableways ........... 25 2.4.4 Current meter measurement from bridges ............. 28 2.4.5 Current meter measurement from boats ............... 28 2.4.6 Other current meter methods ........................ 29 2.4.6.1 Two-tenths depth method......................... 29 2.4.6.2 Sub-surface velocity method..................... 30 2.4.6.3 Integration method.............................. 30 2.4.6.4 Interpolation method............................ 30 2.4.7 Sounding weights.................................. 30 2.4.7.1 Sounding weight hanger bar...................... 31 2.5 Special Problems in Streamflow measurement............. 31 2.5.1 Depth corrections for sounding line and weight ..... 32 2.5.1.1 Positioning the Meter in the Vertical........... 32 2.5.2 Oblique flows (Angled Flow) ........................ 39 2.5.3 Pulsations in flow ................................. 40 2.5.4 Mean gauge height for current meter measurements ... 42 2.5.4.1 Discharge weighting............................. 42 2.5.4.2 Time weighting.................................. 43 2.5.5.1 Large Streams................................... 44 2.5.5.2 Small streams................................... 44 2.5.6 Correction of discharge measurement for storage... 46 2.5.7 Correction of discharge measurement for travel time ........................................................ 47 2.5.8 Measurement of discharge with sections of dead water 49 2.5.9 Measurement of discharge with sections of reverse flow ......................................................... 52 2.5.10 Measurement of discharge with variable backwater .. 52 2.5.11 Measurement of discharge with tributary inflow .... 54 2.5.12 Overflow (out-of-bank flow) ....................... 54 2.5.13 Velocity measurement to a vertical wall ........... 55 2.6.1 Human Error ........................................ 59 2.6.2 Instrument Error ................................... 59 2.6.3 Method Error ....................................... 60 2.6.4 Sounding Error ..................................... 61 2.6.5 Width Errors ....................................... 62 3.0 CURRENT METERS .......................................... 64 3.1 Cup-type current meter................................. 64 3.2 Propeller - type current meter......................... 65 3.3 Rating of Current Meters............................... 68 3.4 Care of Current Meters................................. 68 3.5 Maintenance and repair of the Gurley Current Meter..... 69 TABLE OF TABLES TABLE TABLE TABLE TABLE TABLE TABLE TABLE TABLE TABLE TABLE 1 - COMMON METRIC UNITS AND SYMBOLS ............................ 8 2 - COMMON CONVERSION FACTORS .................................. 9 3 - CURRENT METER - ADOPTED MINIMUM DEPTH SETTING ............. 11 4 - VERTICAL VELOCITY CURVE - STANDARD CO-EFFICIENTS .......... 12 5 - AIR-LINE CORRECTION - PERCENTAGE TYPE ..................... 34 6 - WET-LINE CORRECTION - PERCENTAGE TYPE ..................... 35 7 - AIR-LINE CORRECTION ....................................... 35 8 - WET-LINE CORRECTION ....................................... 36 9 - VELOCITY CO-EFFICIENTS IN VICINITY OF A VERTICAL WALL ..... 56 10 - CURRENT METER PERFORMANCE ................................ 59 TABLE Of FIGURES FIGURE FIGURE FIGURE FIGURE FIGURE FIGURE FIGURE FIGURE FIGURE FIGURE FIGURE FIGURE FIGURE FIGURE FIGURE FIGURE FIGURE FIGURE FIGURE FIGURE FIGURE FIGURE FIGURE FIGURE FIGURE 1 - CONTINUOUSLY RECORDING CURRENT METER ...................... 5 3 - VERTICAL VELOCITY CURVE METHOD ........................... 14 4 - TYPICAL VERTICAL VELOCITY CURVE .......................... 14 5 - THE MID-SECTION METHOD OF COMPUTING MEASUREMENTS ......... 18 6 - MID-SECTION METHOD WORKED EXAMPLE ........................ 18 7 - THE MEAN-SECTION METHOD OF COMPUTING MEASUREMENTS ........ 19 8 - MEAN-SECTION METHOD - WORKED EXAMPLE ..................... 20 9 - THE VELOCITY-DEPTH INTEGRATION METHOD .................... 21 10 - THE VELOCITY CONTOUR METHOD OF COMPUTING MEASUREMENTS ... 22 11 - SCHEMATIC ARRANGEMENT OF AN UNMANNED CABLEWAY ........... 27 12 - "TATURA" UNIVERSAL HANGER BAR ........................... 33 13 - POSITION OF THE SOUNDING WEIGHT IN A DEEP SWIFT STREAM .. 34 14 - CONVENTIONAL CURRENT METER .............................. 40 15 - COMPONENT PROPELLER METER ............................... 40 16 - DISCHARGE FIELD SHEET - CORRECTION FOR OBLIQUE FLOW ..... 41 17 - TIME & DISCHARGE WEIGHTED MEAN GAUGE HEIGHT COMPUTATION . 45 18 - CORRECTION OF DISCHARGE MEASUREMENT FOR STORAGE ......... 49 19 - CORRECTION OF MEASUREMENT GAUGE HEIGHT FOR TRAVEL-TIME .. 50 20 - CORRECTION OF DISCHARGE MEASUREMENT FOR DEAD WATER ...... 51 21 - CORRECTION OF DISCHARGE MEASUREMENT FOR REVERSE FLOW .... 53 22 - VELOCITY ADJUSTMENT AT A WALL – SAMPLE CROSS SECTION .... 56 23 - VELOCITY ADJUSTMENT AT A WALL. SAMPLE MEASUREMENT ....... 57 24 - GAUGING WEIGHT ZEROING LINE ............................. 62 25 - CUP TYPE CURRENT METER .................................. 66 26 - PROPELLOR TYPE CURRENT METER ............................ 67 STREAMFLOW MEASUREMENT INTRODUCTION Streamflow is the combined result of all climatological and geographical factors that operate in a drainage basin. It is the only phase of the hydrological cycle in which water is confined in well-defined channels, which permit accurate measurements to be made of the quantities involved. Good water management is founded on reliable streamflow information and the final reliability of the information depends on the initial field measurements. The hydrographer making these measurements has the responsibility of ensuring raw data of acceptable quality are collected. The accuracy and subsequent usefulness of the published data depends entirely on the quality of the field measurements and the reliability of the stage-discharge relation over the entire life of the station. Measurements are not an end in themselves but are an integral part of the development of a stage-discharge relation. There are many different uses of streamflow data, such as water supply, irrigation, flood control, pollution control, energy generation and industrial water use. The importance placed on any one of these purposes may vary from area to area as well as from state to state. The emphasis for any one need may also change over a period of time. Discharge measurements made at each gauging station determine the stage-discharge relation for that site. This may be a simple relationship between stage and discharge, or a more complex one in which discharge is a function of stage slope, rate of change of stage or other factors. Initially the discharge measurements are made at various stages at the station in order to define the discharge ratings. Measurements are then made at periodic intervals, generally monthly to verify the rating or to define any changes in the rating caused by changes in stream channel conditions. Streamflow, or discharge, is defined as the volume rate of flow of water. Discharge is expressed in megalitres per day (ML/d.) -1- 1.0 METHODS OF STREAMFLOW MEASUREMENT A summary of various methods of discussed in the following section. streamflow measurement is 1.1 Velocity - Area Method A discharge derived by current meter is equal to the summation of the products of the partial areas of the stream cross-section and their respective mean velocities. Since most methods of stream gauging utilise a velocity-area computation it could be inferred that all are velocity area methods. Throughout this manual, however, the velocity-area method infers the use of a current meter. 1.2 Float Gauging Float gauging is basically a direct Velocity-Area method of determining instantaneous flow. The mean velocity is calculated using surface velocities as indicated by a floating object timed over a pre-determined length of channel and at different positions across the channel. Velocities obtained will usually be greater than the mean velocity in the vertical and are therefore subject to a correction factor. The area for any gauge height is obtained from a plot of the mean cross-section of the length of channel over which the velocities are measured. The discharge is derived from the sum of the products of corrected velocity multiplied by the area. Generally, this method is used only when the flow is either too fast or too slow to use a current meter. It is only a fair substitute for current meter gauging but, given accurate field data, it can be a more accurate means of computing a high stage discharge than using empirical formula. 1.3 Slope - Area Method The discharge is derived from the measurement of the slope of the water surface, the cross-section of the channel over a fairly straight reach, and by selecting a roughness coefficient for the channel boundaries. 1.4 Stage - Fall - Discharge Method If variable backwater exists at a site, the energy gradient is variable at a given stage and the discharge rating cannot be defined by stage alone. This is most commonly caused by a downstream confluence or structure. The discharge under these conditions is a function of stage and the slope of the energy gradient. This situation is that of a natural flood where the flow maintains a stable wave profile as it moves down the channel. This type of wave often produces a loop rating. -2- 1.5 Weirs and Flumes The relation between stage (or head) and discharge over a weir or through a flume is established from laboratory or field calibration. The discharge is derived from this rating equation. When shallow depths and low velocities are encountered in a stream it is sometimes impossible to carry out a satisfactory discharge measurement using a current meter. In this situation a portable weir plate or flume is a useful device for measuring the flow. Each weir or flume should be supplied with installation procedures and a theoretical rating to aid in compiling the stage-discharge relation from actual field discharge measurements. 1.6 Dilution Method A tracer liquid is injected into the channel and the water is sampled at a point downstream where turbulence has mixed the trace uniformly throughout the cross-section. The change in concentration between the solution injected and the water at the sampling station is converted into a measure of the discharge. 1.7 Moving boat Method A current meter is suspended from a boat that traverses the river normal to the stream flow. The component of the velocity in the direction of the stream is computed from the resultant velocity and the angle of this resultant. The discharge is the sum of the products of the subsections of the stream crosssectional areas and their respective average velocity. 1.8 Volumetric Measurement The most accurate method of measuring small discharges is the volumetric method. Observing the time required to fill a container of known capacity or the time required to partly fill a calibrated container to a known volume does this. The equipment required is a calibrated container and a stopwatch. Calibration can be achieved by weighing the container with varying amounts of water in it, noting the level in the container and then using the following formula. V = W2 – W1 where V = volume of water in container, in litres W2 = weight of container with water, in kilograms W1 = weight of empty container, in kilograms -3- A container can also be calibrated by adding known volumes of water, by increments, and noting the levels on the container. Volumetric measurements should be made where the flow is concentrated into a narrow stream or at an artificial control where the flow is confined to a notch or narrow width of a shaped weir crest. Sometimes it is necessary to place a trough or funnel against the artificial control to carry the water to the calibrated container. The measurement should be carried out three or four times to be certain that errors have not been made and that the results are consistent. It is good practice to then mean all the accepted readings. 1.9 Continuously recording Flow Meters There numerous instances where continuous flow data is required and the option of using a conventional stage / discharge rating or a calibrated hydraulic structure is not possible or practical. Such instances may require continuous flow associated with the operation pumps, channel flow, sewerage or in manufacturing and production type environments. In addition, velocity measuring devices can be used in larger waterway applications where tail water or tidal effects limit the use of a more conventional approach. 1.9.1. Mechanical Continuously recording flow meters, such as the Sparling and Davis-Shepherd types (see figure 1) are used by the irrigation and water supply districts of this state. These meters are designed to continuously record the flow in pipelines and open channels. They are suspended, facing the centre of flow, in a pipe of known cross-sectional area or in the centre of a stream with flow brought through a tube. Water passes through the pipe, and the rotational speed of the propeller is known to be proportional to the average flow velocity. A simple gear train links the propeller to the register, reading directly in standard volumetric units. The two basic requirements for correct operation are that the pipe must always remain full and the flow must exceed the minimum rated range. -4- FIGURE 1 - CONTINUOUSLY RECORDING CURRENT METER 1.9.2 Ultrasonic The ultrasonic (acoustic) velocity sensor is a device that utilises acoustic transmission to measure the average velocity along a line between one or more opposing sets of transducers. The velocity of flow is determined from the travel time of sound pulses moving in both directions along a path diagonal to the flow. In practice, the application of these sensors is limited to “pipe full” flow situations or in streams where there is always sufficient depth of water, above and below the sensors, to facilitate optimum operating conditions. 1.9.3 Acoustic Doppler The acoustic doppler system measures velocity magnitude and direction using the Doppler shift of acoustic energy reflected by material suspended in the water column. Systems using the Doppler principle range from a small single sensor, which can be installed in a pipe or concrete channel, to a portable system which is used from boat to measure river flows. The latter application is generally safer and quicker than the more conventional boat gauging using a current meter. The accuracy and reliability of these measurements is also consistent with the results obtained with a current meter. -5- 1.9.4 Electromagnetic The discharge is found by measuring the electromagnetic force (EMF) produced by a moving conductor (the flowing water) through a magnetic field produced by a coil around the flow conduit. This application requires a pipe full condition for satisfactory operation. 1.10 Flow Measurement Units Streamflow or discharge is defined as the volume rate of flow of water. The flow rate unit that is generally used by Thiess Services is the Megalitre per day (ML/d). This flow rate is derived from the MEGALITRE (ML) which is equivalent to 1,000,000 litres. A megalitre is best explained by using a diagram. This is illustrated below: One of the reasons this unit was chosen is that the premetric unit, the acre-foot, is very similar to a Megalitre. A flow rate of 1 ML/d for 24 hours will cover an area of 1 hectare to a depth of 0.10 metres. For a discharge measurement, the cross-sectional area is measured in square metres and the velocity is expressed in kilometres per day (km/d) to obtain the discharge in Megalitres per day. Many other authorities, generally non-irrigation, do not use the ML/d but rather the cubic metre per second (m3/sec). Area is measured in square metres and the velocity is expressed in metres per second. The relationship between the ML/d and the CUMEC is: 1 m3/sec (cumec) = 86.4 ML/d The relationship between Km/d and m/sec. is: l m/sec = 86.4 Km/d When using the discharge unit, ML/d, and the velocity unit, Km/d, care should be taken when transposing these units into flow formulae because, almost without exception, these formulae require the units to be in cumecs and m/sec. -6- For example: The formula for discharge through a submerged orifice is: Q = Cd x A x 2 x g x h. in cumecs To determine becomes: the theoretical discharge in ML/d the formula Q = 86.4 x Cd x A x 2 x g x h. Similarly, where computations involving velocity are carried out, a conversion from Km/d to m/sec should be made prior to use in the formulae. A table of common metric units and their symbols is listed as Table 1 and frequently used conversions is listed as Table 2. -7- ITEM UNIT SYMBOL Length Millimetre Metre Kilometre mm m km Area square millimetres square metres square kilometres Hectare mm2 m2 km2 ha Volume cubic metres Litre(1) Kilolitre Megalitre m3 L kL ML Flow Rate megalitres per day cubic metres per second litres per minute litres per second ML/d m3/s L/min L/s Velocity metres per second kilometres per day m/s km/d Mass Kilogram Gram Milligram Tonne kg g mg T Density kilograms per cubic metre tonnes per cubic metre kg/m3 t/m3 Force newton, kilonewton, meganewton N, kN, MN Pressure, stress pascal, kilopascal, megapascal (also metres head of water) Pa, kPa, MPa Energy Joule newton metre J Nm Power Kilowatt kW Temperature degree Celsius 0C TABLE 1 - COMMON METRIC UNITS AND SYMBOLS -8- TO CONVERT INTO MULTIPLY BY : Millimetres : Metres : Kilometres : Inches : Feet : Miles : 0.0393701 : 3.280840 : 0.621371 : Square metres : Square Kilometres : Hectares : Square yards : Square miles : Acres : 1.19599 : 0.386102 : 2.4710538 : : : : Cubic metres Cubic metres Litres Megalitres : : : : Cubic Yards Cubic feet Gallons Acre feet : : : : 1.30795 35.3147 0.219969 0.8107132 : : : : : : : Litres per second Litres per second Cubic metres per second Megalitres per day Megalitres per day Megalitres per day Cubic metres per second : : : : : : : Gallons per minute Millon gallons per day Cubic feet per second Cubic feet per second Gallons per minute Cubic metres per second Megalitres per day : : : : : : : 13.198155 0.0190053 35.3147 0.4087346 152.75642 0.011574 86.4 LENGTH AREA VOLUME FLOW RATES MASS : Kilogram : Tonne : Pound : Ton : 2.20462 : 0.984207 : Kilometres per day : Kilometres per day : Feet per second : Metres per second : 0.037973 : 0.011574 : Kilogram per cubic metre : Tonnes per cubic metre : Pound per cubic foot : Pound per cubic foot : 0.062428 : 62.428 : Kilopascal : Pound per square inch : 0.145038 VELOCITY DENSITY PRESSURE TABLE 2 - COMMON CONVERSION FACTORS -9- 2.0 THE VELOCITY-AREA METHOD OF STREAM FLOW MEASUREMENT The velocity-area method used for the determination of discharge in open channels requires the measurement of stream velocity, depth of flow and the distance across the channel between observation verticals. The velocity is measured at one or more points in each vertical, by current meter, and an average velocity determined in each vertical. (See section 2.2.) The discharge is equal to the summation of the products of the partial areas of the stream cross-section and their respective average velocities. The discharge obtained is normally used to establish a relation between stage (water level) and stream flow, which is referred to as the stage-discharge relation. 2.1 Spacing of Verticals In order to determine bed shape and horizontal and vertical velocity distribution accurately, an infinite number of verticals would be necessary, however, for practical reasons only a finite number is possible. The cross-section is divided into segments at a sufficient number of locations across the channel to ensure an adequate sample of both velocity distribution and bed profile. The spacing and number of verticals are crucial for the accurate measurement of discharge and for this reason between 20 and 30 verticals should be used. This applies to streams of all widths, except where the channel is so narrow that this would be impractical. Verticals should be spaced on the basis of the following criteria and will depend largely on the flow conditions, the geometry of the cross-section and the width of the stream. 2.1.1 Segments of equal flow For streams having a variable velocity distribution, or a significant variation in the horizontal velocity distribution, it is advisable to space the verticals to achieve segments of equal flow over the required distance rather than segments of equal widths. 2.1.2 Bed profile. For streams having abnormalities in the bed profile, the verticals are spaced to make allowance for depressions or obtrusions and general irregularities of the bed. 2.1.3 Equidistant For very wide rivers, over 300 metres, it is sometimes convenient to make the verticals equidistant. A general rule for current meter measurements is to make the width of the segments less as the depth and velocities become greater. Irrespective of which criterion is used, the spacing of the verticals must be arranged so that no segment contains more than 10% of the total flow. If the stage is steady the ideal - 10 - measurement is one having no segment with more than 5% of the total flow. 2.2 Measurement of Velocity The current meter measures velocity at a point. To carry out a discharge measurement at a cross section requires determination of the mean velocity in each of the selected verticals. The mean velocity in a vertical is obtained by observing the velocity at many points in that vertical but it can be approximated by taking a few velocity observations and using a known relation between those velocities and the mean in the vertical as per Table 4 or as calculated from previous observation records. The following Table sets out the Thiess Services standard as adopted against the International Standard, for minimum recommended depth settings for gaugings. It was necessary to vary from the International Standard to allow for measurement of small flows that are often encountered in Victoria. The adopted standard is based on the assumption "For a current meter to perform at an acceptable level for wading measurements, the minimum distance from the horizontal axis through the current meter or propeller to the bed should never be less than the width of the cup or the diameter of the propeller" ADOPTED Thiess Services STANDARD FOR: CUP WIDTH OR MINIMUM DEPTH RECOMMENDED PROPELLER FOR DIAMETER 1 Point 2 Point Method Method GURLEY-PYCMY 20 mm 5 cm 10 cm OSS-PCI 50 mm 12 cm 25 cm GURLEY 50 mm 12 cm 25 cm 100 mm 25 cm 50 cm 120 mm 30 cm 60 cm 125 mm 31 cm 62 cm OTT-C31 OSS-B1 SIAP OTT-C31 OSS-B1 TABLE 3 - CURRENT METER - ADOPTED MINIMUM DEPTH SETTING - 11 - The more commonly used methods of determining the mean velocity in the vertical are: 2.2.1 Vertical velocity curve method In this method velocity observations are made in each vertical at a sufficient number of points, distributed between the water surface and the bed, to effectively define the vertical velocity curve. The mean velocity is obtained by measuring the area between the curve and the ordinate axis with a planimeter and dividing the area by the length of the ordinate axis. (See Figures 2 and 3 for an example). The number of points required depends on the degree of curvature, particularly in the lower part of the curve, and usually varies between six and ten (See Figure 4). Observations should normally include velocities at 0.2, 0.6 and 0.8 of the depth from the surface so that the results from the curve can be compared with various combinations of reduced point methods, and the higher and lower points should be located as near to the water surface and bed as possible. (Refer to sections 2.2.7 and 2.2.8.) This method is valuable in determining coefficients for application to the results obtained by other methods, but is generally not adapted to routine discharge measurements due to the extra time required to collect field data and to compute the mean velocity. Table 4 shows average ordinates taken from the standard vertical velocity curve. Ratio of observation depth to depth of water Ratio of point velocity to mean velocity in the vertical 0.05 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 0.95 1.160 1.160 1.149 1.130 1.108 1.067 1.020 0.953 0.871 0.746 0.648 TABLE 4 - VERTICAL VELOCITY CURVE - STANDARD CO-EFFICIENTS - 12 - Murray River below Rufus River Junction. Measurement No. 87/8 1 2 3 Ch = 8m Area = 90 Ch = 14m Area = 112 Ch = 20m Area = 138 Ch = 26m Area = 194 Ch = 32m Area = 236 Ch = 38m Area = 244 Ch = 44m Area = 262 Ch = 50m Area = 238 Ch = 56m Area = 226 Ch = 62m Area = 242 Ch = 68m Area = 230 Ch = 74m Area = 212 Ch = 80m Area = 198 Ch = 86m Area = 168 Ch = 92m Area = 188 Ch = 98m Area = 182 60 Ch = 104m Area = 190 Ch = 110m Area = 184 4 1 2 3 4 1 2 DEPTH IN METRES 3 4 1 2 3 4 1 2 3 4 1 2 3 40 80 20 40 Velocity in Km/Day 0 80 20 40 60 0 80 20 40 60 FIGURE 2 - VERTICAL VELOCITY CURVE METHOD – GRAPH REPRESENTATION OF VELOCITY DISTRIBUTION - 13 - Murray River below Rufus River Junction - Measurement No. 87/8 300 250 200 150 100 Area = 21 687 ∴Discharge = 21 687 Ml/d 50 120 10 20 30 40 50 60 70 80 90 WIDTH IN METRES FIGURE 3 - VERTICAL VELOCITY CURVE METHOD FIGURE 4 - TYPICAL VERTICAL VELOCITY CURVE - 14 - 100 110 2.2.2 The one-point or six-tenths method In the one-point method a single velocity observation is taken 0.6 of the depth below the surface and the value obtained is accepted as the mean for the vertical. (See Table 4.) This method is generally used under the following conditions. a) Whenever the depth precludes multiple observations for the meter being used. b) When the distance between the meter and sounding weight is too great to permit placing the meter at the 0.8 depth. (This prevents the use of the two-point method.) c) When the stage is changing rapidly and a measurement must be made quickly. 2.2.3 Two-point method Velocity observations are made in each vertical at 0.2 and 0.8 of the depth below the surface and the average of the two readings is taken as the mean for the vertical. Here again this assumption is based on theory and on the study of vertical velocity curves and experience has confirmed its essential accuracy. The World Standard suggests a minimum depth of 0.75 m for this method, however we have adopted lesser minimum depths, (provided bed condition are suitable), to adequately cater for the measurement of predominantly small shallow streams. (Refer Table 3). Overhanging vegetation that is in contact with the water, or submerged objects such as large rocks and aquatic weed growth that are in close proximity, either upstream or downstream, to the vertical will distort the vertical velocity curve. Where that occurs, this method will not give a reliable mean velocity value and an additional reading at 0.6 of the depth should be made. A rough test of whether or not the velocities at 0.2 and 0.8 are sufficient for determining the mean vertical velocity is, "that the 0.2 depth velocity should be greater than the 0.8 depth velocity", but less than twice as great”. 2.2.4 Three-point method Velocity observations are made in each vertical at 0.2, 0.6 and 0.8 of the depth. The mean velocity is calculated by averaging the 0.2 and 0.8 depth observations and then averaging that result with the 0.6 depth observation. This method is used when the velocities in the vertical are abnormally distributed. The velocities can also be obtained from this equation. - 15 - V = V 0.2 + 2*(V 0.6) + V 0.8 4 2.2.5 Five point method Velocity observations are made in each vertical at 0.2, 0.6 and 0.8 of the depth and as close to the streambed and the surface as practical. (Refer sect ions 2.2.7 to 2.2.8) The mean velocity is obtained from this equation V = V surface + (3*V 0.2)+ (3*V 0.6) + (2*V 0.8) + V Bed 10 2.2.6 Six point method The six-point method should be used in situations where a distorted vertical velocity distribution is known or suspected, for example, where there is aquatic growth. Velocity observations are made in each vertical at 0.2, 0.4, 0.6 and 0.8 of the depth and as close to the streambed and surface as practical. (Refer sections 2.2.7 and 2.2.8). The mean velocity is obtained from this equation V = V surface + (2*V 0.2)+ (2*V 0.4)+ (2*V 0.6)+ (2*V 0.8)+ V Bed 10 2.2.7 Surface Velocity Measurement The setting for all surface velocities is based on which states "The horizontal axis of the current meter placed at a depth of not less than one and a half rotor height from the water surface and no part of shall break the water surface." I.S.O 748 should be times the the meter In suspension measurements, the zone between the water surface and a depth of 0.15 m, current meters can give erratic results, so for uniformity a depth of 0.35 m below the water surface has been adopted as standard for all surface velocities. (This depth caters for Gurley and OTT current meters.) If a surface velocity is used to calculate the mean velocity in a section of a natural channel, a co-efficient of 0.85 or 0.86 may be adopted if no co-efficient has been developed from previous field surface velocity measurements. These are the reciprocal of the values in Table 4. - 16 - 2.2.8 Bed Velocity Measurement The setting for bed velocities is based on I.S.O 748, which states. "The current meter should be placed at a distance of not less than three times the rotor height from the bed". In suspension measurements this distance is also dependent on the size of the sounding weight, so, for uniformity when using different sounding weights and current meters a distance of 0.35 m from the bed has been adopted. 2.3 Computation of Current Meter Measurements The computed discharge is the summation of the products of the partial areas of the stream cross-section and their respective average velocities. The formula Q = Where (AV) represents the computation Q = total discharge A = individual partial cross-section area V = mean velocity of the flow normal to the partial area. 2.3.1 Mid-section method In this method it is assumed that the velocity sampled at each vertical represents the mean velocity in a particular rectangular segment. The area extends laterally from half the distance from the preceding observation vertical to half the distance to the next and vertically from the water surface to the sounded depth, as shown by the hatched area. (See Figure 5). The segment discharge is then computed for each segment and these are summed to obtain the total discharge. (See Figure 6) - 17 - 1, 2, 3, ,n, Number of verticals; b1, b2, b3,..., n, distance from initial point; d1, d2, d3, n, depth of flow at verticals; , average velocity in verticals. FIGURE 5 - THE MID-SECTION METHOD OF COMPUTING MEASUREMENTS FIGURE 6 - MID-SECTION METHOD WORKED EXAMPLE - 18 - 2.3.2 Mean section method The mean section method differs from the mid-section method in its computation procedure. Segment discharges are computed between successive verticals. The velocities and depths at successive verticals are each averaged. The section extends laterally from one observation vertical to the next. Discharge is the product of the average of two mean velocities, the average of two depths and the distance between observation verticals. (See Figure 7.) A worked example is shown in Figure 8. Experiments have shown that the mid-section method is slightly more accurate, however the mean-section method has been adopted as the standard by the Thiess Services. Segments. 1, 2, 3, ...,n, Number of verticals; b1, b2, b3, ..., n, distance from initial point; d1, d2, d3, ...n, depth of flow at verticals; , average velocity in verticals. FIGURE 7 - THE MEAN-SECTION METHOD OF COMPUTING MEASUREMENTS - 19 - HYDROGRAPHIC SERVICES Conditions : Weather: Cloudy Stream: Steady Time 14:5 15:21 E.S.T. 9 Gauge 0.982 0.982 Height Rec Height 0.982 0.982 Mean Gauge Height: 0.982 DISCHARGE MEASUREMENT Stream: ALBERT RIVER Meas. No: Station: HIAWATHA Date: 5.3.84 Point of Measurement: . Party: Method: Meter A1559 Weight: No: Wad Rod No: Tape No: REMARKS OBSERVATIONS Time Distan Depth Vert Adj Revs ce Ang Depth Waters Edge Stream Temp:18.5 Sample No: EC @ 25 deg: Weighted Mean: Counter No: Time Seconds 0.5 0.00 WE RB 0.8 0.14 4 41.0 1.2 0.15 8 43.0 1.6 0.14 10 45.0 2.0 0.12 8 48.5 2.4 0.12 6 57.5 2.8 0.13 6 47.0 3.2 0.14 4 52.5 3.6 0.10 4 48.0 4.0 0.18 2 40.0 4.4 0.13 2 42.0 4.6 0.20 5.0 0.18 2 4 4 48.0 55.0 49.0 Velocity Point Mean Mean Vert Sect 0.0 3.25 6.5 9.05 11.6 12.65 13.7 12.05 10.4 8.60 6.8 7.50 8.2 6.70 5.2 5.45 5.7 4.70 3.7 3.40 3.1 3.65 4.2 4.90 5.6 Area Area COMPUTATIONS Mean Adj Horiz Depth Wid Ang Width Discharge 0.021 0.07 0.3 0.068 0.057 0.142 0.4 0.516 0.056 0.14 0.4 0.708 0.051 0.1275 0.4 0.615 0.048 0.12 0.4 0.413 0.050 0.125 0.4 0.375 0.054 0.135 0.4 0.362 0.048 0.12 0.4 0.262 0.056 0.14 0.4 0.263 0.062 0.155 0.4 0.211 0.033 0.165 0.2 0.120 0.076 0.19 0.4 0.372 Disch. 4.285 0.612 FIGURE 8 - MEAN-SECTION METHOD - WORKED EXAMPLE 2.3.3 Velocity – Depth Integration method The velocity-depth integration method is a graphical method of computing discharge. If sufficient velocity observations have been made in the verticals, a curve of mean velocity and depth of flow (area of vertical velocity curve) may be drawn over the cross-section. The area of this curve represents the total discharge. The areas contained by the curves should be measured by planimeter. (See figure 9.) - 20 - FIGURE 9 - THE VELOCITY-DEPTH INTEGRATION METHOD 2.3.4 Velocity – Contour method The velocity – contour method is a graphical method of computing discharge. If sufficient velocity observations have been made in the verticals then the procedure is as follows: 1. Vertical vertical. velocity distribution curves are drawn for each 2. Interpolate the curves for convenient intervals of velocity e.g. 20 km/d, 40 Km/d etc. 3. Curves or contours of equal velocity (isovels) are drawn. (See figure 10). 4. Starting from the maximum, the areas enclosed by successive velocity contours are measured by planimeter and plotted on a diagram with the ordinate indicating velocity and the abscissa indicating the corresponding area enclosed by the respective velocity contour. The summation of the area enclosed by this curve represents the total discharge. - 21 - FIGURE 10 - THE VELOCITY CONTOUR METHOD OF COMPUTING MEASUREMENTS 2.4 Procedure for Measurement of Discharge by Current Meter Current meter measurements should be classified in terms of the means used to traverse the river during the measurement. These are normally by wading, cableway, boat or bridge. The actual method used depends mainly on the depth of flow and the velocity. No matter which method is used or how the current meter is suspended, the principles of measurement described in the previous section are the same. 2.4.1 Selection of gauging site. For a gauging station, the selection of the site is often dictated by the needs of water management or by the requirements of the hydrometric network. In fulfilling water management needs there is little or no freedom of choice in selecting gauging sites, and frequently records need to be obtained under extremely adverse hydraulic conditions. This is often the case where spot measurements are required at specified locations. Ideally a site is selected to meet the design requirements that will provide reliable stream flow data. It is often useful, if possible, to inspect potential sites during different flow conditions. Generally however, the aim is to select a reach of stream containing the following characteristics: a. The channel should be straight and of uniform cross-section and slope in order to avoid abnormal velocity distribution. b. The depth of water in the selected reach should be sufficient to allow effective immersion of the current meter. c. The measuring site and the reach upstream should be clear and unobstructed by trees and other obstacles so that the field of view enables floating debris to be seen in sufficient time to permit the removal of the instrument from the stream. - 22 - d. The bed of the reach should not be subject to changes during the period of a measurement. (i.e. siltation or scouring etc.) e. All discharges should be contained within a well-defined channel having substantially stable boundaries with well-defined geometric dimensions. f. To avoid disturbance of the flow the site should be remote from any bend or natural or artificial obstruction. g. The gauging site should be kept clear of aquatic growth. h. Sites at which vortices, reverse flow or dead water occur should be avoided. i. A measuring section with converging and more so diverging flow over an oblique measuring section should be avoided as it is difficult to make allowance for the systematic errors that can occur. j. The orientation of the reach should be such that the direction of the flow is normal to that of the prevailing wind. k. To facilitate gauge reading during a measurement and to avoid the effect of storage between the measuring site and the gauges the measuring site should be situated relatively close to the gauges. 1. The measuring site should be situated in close proximity to the gauging station to avoid the effect of tributary inflow. m. The measuring site should be readily accessible, where possible, to provide safe passage at all stages of flow and in all conditions for personnel and vehicles. n. Permanent markers should be established at each measuring section to facilitate the repetition of levels or soundings. o. The distance from the measuring section to the station gauge should be accurately defined to evaluate measurements and identify any change in cross-section. p. When the length of straight channel is restricted, it is recommended that for current meter measurements the straight length of channel upstream of the measuring section should be twice the length of that downstream. (Generally, one hundred metres should be regarded as the minimum straight length upstream). 2.4.2 Current meter measurement by wading Current meter measurements by wading are preferred against other methods because they are generally less time consuming and permit the selection of the most suitable site for a particular stage. They also allow more control over the gauging procedure. This is particularly the case in the selection of a cross- 23 - section which may not be at the usual station measuring section and when selecting verticals and measuring depths. If natural conditions for measuring (with respect to depths and velocities) are not ideal the section may be modified to provide acceptable conditions. After any modifications, flow must be allowed to stabilise before starting the gauging. A measuring tape or tagged line is strung across the river at right angles to the direction of flow. Using a minimum of 15 verticals, the spacing is determined so that no segment contains more than 10% of the total discharge (See section 2.1.) Usually an approximate discharge can be obtained for this purpose from the stage discharge curve, the current rating table or from previous measurements. The position of successive verticals are located by horizontal measurements from a reference marker (initial point) on the bank. The gauging starts at the waters edge, where depth and velocity may or may not be zero. At each chosen vertical the depth is measured and the value used to compute the setting/s of the current meter (usually 0.6 or 0.2 and 0.8 depth). After the meter is in position the rotor is allowed to adjust to the stream velocity before the revolution count is started. This may take only a few seconds where velocities are over 25 Km/d but a longer period is necessary for slower velocities. A revolution count is then taken at each selected point for a minimum of 40 seconds, but where the velocity is known to be subject to short period variations or pulsations it is advisable to continue the observations for at least 60 seconds. Start the stop watch simultaneously with the first signal or click, counting zero not one. End the count on a convenient number given in the column heading of the meter rating table. (i.e. 2, 4, 6, 8, 10, 15, 20 .... 100, 150). Read the time to the nearest half second. Revolutions may also be counted over a fixed time period (40 seconds, 60 seconds, 80 seconds etc) using a counter, however this can lead to an error in the observation at low velocities because only full revolutions are counted. Consideration must also be given to the direction of flow, because it is the component of velocity normal to the measurement section that must be determined. (See section 2.5.2 on oblique flows). Tail fins are provided to assist this process and must be used when appropriate. Limitations on wading are imposed by the combination of depth and velocity and by the quality of foothold on the bed. The advisability of wading must be judged by the operator at each site. The position of the operator is important to ensure that the operator’s body does not effect the flow pattern at or approaching the current meter. The best position is to stand facing one or other of the banks, slightly downstream of the meter and at arm's length from it. The rod is kept vertical throughout the measurement with the meter parallel to the direction of flow. Avoid standing in the water if feet and legs would occupy a considerable percentage of the cross-section of a - 24 - narrow stream. In a small stream where the width permits, stand on a plank or other support rather than in the water. 2.4.3 Current meter measurement from cableways Cableways are normally used when the depth of flow is too deep for wading, when wading in a swift current is considered dangerous, or when the section is too wide to string a tape or tagged line. There are two basic types of cableway: a. Those with the instrument carriage controlled from the bank by means of a winch, either manually or electrically operated. (See figure 11). b. Those with a manned personnel carriage. The general gauging procedure is similar for both except that in the case of the non-manned cableway the instrument carriage, suspended from the top cable, moves the current meter and sounding weight across the stream between the cable supports. The operator remains on the bank and operates the gauging winch that is provided with a depth counter for placing the current meter at the desired position. Tags can also be placed on the sounding line as an aid in determining depth. The electrical impulses from the current meter are returned through the core conductor of the suspension cable and registered on a counter or by an audible signal. The gauging procedure is as follows: a. The waters edge is identified in relation to a permanent initial point (i.e the operational post) on the bank by means of a tagged endless wire which is also used for spacing the verticals. b. The current meter and weight are lowered at the first vertical until the predetermined displacement mark on the weight touches the water surface and then the depth counter is set to zero. (See section 2.6.4) If a tagged line is used, the depth is read directly off the tags. c. Scour is likely to be less on the upstream side. The advantages of using the downstream side are: a. Vertical angles are more easily measured on the downstream side as the sounding line will move away from the bridge. b. The flow lines of the stream may be straightened out by passing through a bridge opening with piers. Utilising the upstream or downstream side of a bridge for a current meter measurement should be decided on site for each - 25 - individual bridge. This is done after considering the above and the physical conditions at the bridge such as walkway locations, traffic hazards and accumulation of debris. The meter is controlled by a gauging winch mounted on a bridge crane or bridgeboard. A hand line may be used with small weights. c. The current meter assembly is then lowered until the weight touches the streambed and the sounded depth is recorded. d. The velocities are measured at the selected depths in the vertical. e. The current meter should be checked between verticals for obstruction or damage, particularly if there is a sudden variation in the velocity indicated by the counter, or through the audible signal. The channel, upstream from the section, should be watched closely for any debris that could damage the meter. f. If measurements are made where the river is deep and swift, the sounding weight may not be sufficient to maintain the suspension cable in the vertical. In this instance, the angle of divergence from the vertical is measured by protractor, and the soundings corrected to obtain the actual vertical depth. (See section 2.5.1.) g. The remoteness of the observer horizontal angles difficult to determine therefore essential that cableways are possible location at right angles to errors caused by undetected horizontal angles are encountered the procedure in adopted. - 26 - from the meter makes from a cableway. It is installed in the best the flow, to minimise angles. If horizontal Section 2.5.2 should be FIGURE 11 - SCHEMATIC ARRANGEMENT OF AN UNMANNED CABLEWAY - 27 - 2.4.4 Current meter measurement from bridges Although cableways are generally preferred to bridges for current meter measurements, highway or railway bridges can often be used to advantage. Bridges rarely offer the right conditions for stream gauging but measurements from them may be necessary where suitable sites for wading or for a cableway are not available. As contracted sections, piers and other obstructions effect the distribution of velocities it is necessary to use a larger number of verticals and more velocity observations in each vertical, especially, close to the bridge piers and banks. No set rule can be given for selecting the upstream or downstream side of a bridge for obtaining discharge measurements, however the advantage of each are set out below. The advantages of using the upstream side of the bridge are: a. The hydraulic conditions of the upstream side of the bridge opening are usually more favourable. b. Approaching debris can be seen and avoided more easily. Another method that may be utilised is the "Side Suspension". A temporary cross-line is erected upstream or downstream of the bridge with the gauging equipment attached by pulleys and operated from the bridge. A wire or rope is attached to the pulley system to aid in traversing the sounding equipment. The advantages of this method are: a. Discharge measurements can be made at a distance from debris build up or the effects of piers or other obstructions. b. The cross line can be erected at right angles to the flow to eliminate potential angular corrections that may be required if the bridge were to be used. 2.4.5 Current meter measurement from boats Where the river is too wide for a cableway installation and too deep to wade, discharge measurements are made from boats. Boat use is limited by high water velocity during floods, especially as personal safety must be of primary consideration. Note: "Gaugings made on any streams are to be made in accordance with the requirements of the Maritime Services Board Regulations or any applicable local regulations". A tagged line is used to span the river at the measuring section. The tagged line serves the dual purpose of holding the boat in position during the measurement and locating the verticals laterally. If there is any likelihood of traffic on the stream, one alert person must be positioned on the bank to lower the line to allow traffic to pass safely. - 28 - The procedure for and cable is the cableway once the for traversing the gauging from a boat using a sounding weight same as that for measuring from a bridge or tagged line has been erected and the method boat has been determined. The advantages of boat gauging are: a. Flexibility in the selection of measuring sites. b. Close proximity of the observer to the current meter allows an accurate evaluation of conditions at each vertical and quick repair to gauging equipment. The disadvantages of boat gauging are: a. Difficulties in erecting a tagged line streams or streams with snags on the bed. in debris laden b. Vertical angle of the sounding line is difficult to determine due to the position of the observer directly behind the sounding line and the limited length of dry line. c. If the section is subjected to wind action and stream velocities are less than 25 km/d boat measurements are not recommended. 2.4.6 Other current meter methods There are several other methods that are sometimes used to measure discharge using current meters. These methods are useful when a full current meter gauging is inappropriate because time is limited, high velocities are experienced or stage is changing rapidly. A loss of accuracy, however, must be expected. These methods are only described in brief as they are not in general use in Victoria. 2.4.6.1 Two-tenths depth method In this method the velocity is observed at 0.2 of the depth below the surface and a coefficient applied to the observed velocity to obtain the mean in the vertical. When it is impossible to obtain soundings, a standard cross-section at the site is used to compute the 0.2 depth. A measurement made by this method is normally computed by using the 0.2 depth observations (without coefficients,) as though each were a mean in vertical. The result obtained is then divided by the area of the measuring section to give the mean value of the 0.2 depth velocity. The plotting of the true mean velocity versus the mean 0.2 depth velocity for each measurement will give a velocity relation curve for use in adjusting the mean velocity for measurements made by the 0.2 depth method. If too few measurements have been made to establish the vertical velocity curve, the coefficient to adjust the 0.2 depth to the mean velocity is about 0.87. - 29 - 2.4.6.2 Sub-surface velocity method In this method the velocity is observed at some arbitrary distance below the water surface. The distance should be at least 0.6 m, and preferably more in deep swift streams to avoid the effects of surface disturbances. The sub-surface velocity method is used, when it is impossible to obtain soundings and the depths cannot be estimated with enough reliability to even approximate a 0.2 depth setting. Coefficients are necessary to convert the observed velocities to the mean velocity in the vertical. The coefficients are determined by measuring the depths after the stage has receded sufficiently. The coefficients to be used with the sub-surface observations can then be computed by obtaining vertical velocity curves at the reduced stage of the stream. 2.4.6.3 Integration method In this method the meter is lowered to the streambed and then raised to the surface at a uniform rate. The total number of revolutions and the total elapsed time are used to obtain the mean velocity in the vertical. This method cannot be used with a vertical axis current meter as the vertical movement of the meter effects the motion of the rotor. The accuracy of the measurement is largely dependent on the hydrographer maintaining a uniform rate of movement of the meter. 2.4.6.4 Interpolation method This method has been devised for use on wide rivers where there is limited time available. The velocity is measured in only three verticals and the average velocity is interpolated for the remaining verticals or sub-sections. 2.4.7 Sounding weights If a stream is too deep or swift to wade, the current meter is suspended in the water by cable from a cableway, boat or bridge. The sounding weight is suspended below the current meter to keep it stationary in the water and in an approximately vertical position. The weight also prevents damage to the meter when the assembly is lowered to the streambed to measure depth. The sounding weights now commonly used are the Columbus type or their equivalent. These weights are stream lined, with tail fins, to align them with the current and to cause minimum interference to the flow. Each weight has a vertical slot and a drilled horizontal hole to accommodate a weight hanger bar and securing pin. Some sounding weights have a ground sensor that produces a signal when the weight touches the bed. The distance between the centre-line of the current meter and the bottom of the weight must be considered when setting the meter at the velocity observation points. - 30 - Columbus sounding weights are manufactured in a variety of sizes. These are 7, 15, 23, 34, 45, 68, 75, 100, 125 and 150 kilograms. The size of the sounding weight used in current meter measurements depends on the depth and velocity in the crosssection. As a rule of thumb the size of the weight in kilograms should be greater than five times the maximum product of velocity and depth in the cross-section, divided by 86.4. The formula is: Sounding weight required (kg) = 5 x Velocity x Maximum Depth 86.4 For example, The maximum velocity at a gauging station is estimated at 225 kilometres per day and the maximum depth to be measured is estimated at 4.7 metres. Therefore: Sounding weight required = = 5 x 225 x 4.7 86.4 61 kg So, a sounding weight of 68 kilograms would be required measure the estimated maximum discharge at this site. to 2.4.7.1 Sounding weight hanger bar The "Tatura" universal hanger bar has been adopted as standard hanger bar for use within Thiess Services. It designed to overcome the shortcomings of existing hanger sounding weight and current meter combinations and has following advantages. the was bar, the a. A single hanger bar with suspension pin configurations to suit sounding weights from 15 to 68 kilograms. b. A sounding and meter setting accuracy of ±0.01 metres. c. Eliminates the need for a thread within the sounding weight d. Compatible with Gurley, OTT and Oss current meters. e. Allows a comparison between sounding line if required. the winch counter and tagged Figure 12 shows a detailed drawing of the hanger; bar and pin arrangements. 2.5 Special Problems in Streamflow measurement When current meter measurements are carried out under adverse conditions normal procedures must sometimes be altered. The most common of these procedures are covered below: - 31 - 2.5.1 Depth corrections for sounding line and weight When suspended current meter measurements are obtained in deep swift water, the current meter and the sounding weight may be carried downstream for a certain distance before the weight touches the bottom. In such cases, corrections must be applied in order to determine the correct depth and the depth of the current meter setting. Figure 13 shows the position assumed by the sounding line when the weight is just off the bed of the stream, and supported by the line only. It can be seen that from the length of the line AF, the distance AE and the difference between the length of EF and BC must be deducted in order to determine the depth BC, (assuming the stream bed is horizontal.) Both these corrections are functions of the vertical angle and are given in tables 5 and 6. The values in these tables are based on the assumption that the drag force on the weight in the comparatively still water near the bottom can he neglected and that the sounding line and weight are designed to offer little resistance to the flow of water. The uncertainties in these assumptions are such that significant errors may be introduced if the vertical angle is more than 30 degrees. If the direction of flow is not normal to the measuring cross-section, the corrections in the table will be too small due to underestimation of the angle. 2.5.1.1 Positioning the Meter in the Vertical The conditions that cause errors in sounding also cause errors in placing the current meter at selected positions in the vertical. The amount of drift experienced by the meter is not constant but varies with depth. The wet-line tables therefore are not strictly applicable when setting the meter at the observation depths. - 32 - Material: STAINLESS STEEL 304 GENERAL NOTES: This hanger bar can be used with weights from 15kg to 68kg. Tagged winch lines must be adjusted from 400mm bar. Some weights must be reslotted and drilled to fit this new bar. 10mm ∅ hole 6mm ∅ hole To suit both Gurley & Ott Meter set with axis ≈ 0.35m above bottom of weight 6mm ∅ hole To suit both Gurley & Ott Meter set with axis ≈ 0.3m above bottom of weight 6mm ∅ hole To suit both Gurley & Ott Meter set with axis ≈ 0.2m above bottom of weight 9mm ∅ 3/8" BSF threaded for 68kg with sensor 9mm ∅ 3/8" BSF threaded for 68kg without sensor 9mm ∅ 3/8" BSF threaded for 22kg 15kg FIGURE 12 - "TATURA" UNIVERSAL HANGER BAR - 33 - FIGURE 13 - POSITION OF THE SOUNDING WEIGHT IN A DEEP SWIFT STREAM Air-Line Correction Vertical angle (degrees) Correction % Vertical angle (degrees) Correction % 4 6 8 10 12 14 16 0.24 0.55 0.98 1.54 2.23 3.06 4.03 18 20 22 24 26 28 30 5.15 6.42 7.85 9.46 11.26 13.26 15.47 TABLE 5 - AIR-LINE CORRECTION - PERCENTAGE TYPE - 34 - Wet-Line Correction Vertical angle (degrees) Correction % Vertical angle (degrees) Correction % 4 6 8 10 12 14 16 0.06 0.16 0.32 0.50 0.72 0.98 1.28 18 20 22 24 26 28 30 1.64 2.04 2.48 2.96 3.50 4.08 4.72 TABLE 6 - WET-LINE CORRECTION - PERCENTAGE TYPE AIR LINE CORRECTION AIR LINE in METRES 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0 8.5 9.0 9.5 10.0 VERTICAL ANGLE (DEGREES) 4 6 8 10 12 14 16 CORRECTION IN CM 18 20 22 24 26 28 30 35 1 2 2 3 4 5 5 6 7 8 8 9 10 11 12 12 13 14 15 15 3 5 8 10 13 15 18 21 23 26 28 31 33 36 39 41 44 46 49 51 3 6 10 13 16 19 22 26 29 32 35 39 42 45 48 51 55 58 61 64 4 8 12 16 20 24 27 31 35 39 43 47 51 55 59 63 67 71 75 79 5 9 14 19 24 28 33 38 43 47 52 57 61 66 71 76 80 85 90 95 6 11 17 23 28 34 39 45 51 56 62 68 73 79 84 90 96 102 107 118 7 13 20 27 33 40 46 53 60 66 73 80 86 93 99 106 113 119 126 133 8 15 23 31 39 46 54 62 70 77 85 93 100 108 116 124 131 139 147 155 11 22 33 44 55 66 77 88 99 110 121 132 143 154 155 176 187 198 209 220 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 1 1 1 2 2 2 2 3 3 3 4 4 4 4 5 5 5 6 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9 10 1 2 3 4 6 7 8 9 10 11 12 13 14 16 17 18 19 20 21 22 2 3 5 6 8 9 11 12 14 15 17 18 20 21 23 24 26 28 29 31 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 TABLE 7 - AIR-LINE CORRECTION - 35 - WET - LINE CORRECTION WET LINE IN METRES 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 VERTICAL ANGLE (DEGREES) 4 6 8 10 12 14 16 18 20 22 1 1 2 3 4 4 5 6 6 7 7 9 9 10 11 12 12 13 14 14 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 2 3 4 5 6 8 9 10 12 13 14 15 17 18 19 20 22 23 24 26 2 3 5 7 8 10 11 13 15 16 18 20 21 23 25 26 28 30 31 33 2 4 6 8 10 12 14 16 18 20 22 24 27 29 31 33 35 37 39 41 2 5 7 10 12 15 17 20 22 25 27 30 32 35 37 40 42 45 47 50 24 26 28 30 35 CORRECTION IN CM 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 3 3 3 3 3 1 1 1 2 2 2 3 3 3 4 4 4 4 5 5 5 6 6 6 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9 10 10 3 6 9 12 15 18 21 24 27 30 33 36 38 41 44 47 50 53 56 59 4 7 11 14 18 21 25 28 32 35 39 42 46 49 53 56 60 63 67 70 4 8 12 16 20 24 29 33 37 41 45 49 53 57 61 65 69 73 78 82 5 9 14 19 24 28 33 38 42 47 52 57 61 66 71 76 80 85 90 94 7 13 20 27 33 40 46 53 60 66 73 80 86 93 99 106 113 119 126 133 TABLE 8 - WET-LINE CORRECTION A workable system to overcome the problem is to set the meter at factors of the wet-line length rather than the true depth. As the largest vertical angle is normally at the full depth, by factorizing the wet-line length EF (Figure 13) the true settings will be more closely approximated than if wet-line correction tables and the true depth are used. Eg. using the 0.2 & 0.8 method. If the observed wet-line depth = 20 m, the meter is placed at a measured depth of 4.00 m for the 0.2 position and 16.00 m for the 0.8 position. The procedure for applying depth meter positions is as follows: corrections and determining a. Measure the vertical distance A B from the guide pulley/traveller to the water surface. This will give the vertical distance to be used with the airline correction table (Table 7). This table will only be used when depths are read from a counter on the gauging winch and not when depths are read from a tagged sounding line. - 36 - b. Align the displacement mark on the weight with the water surface and zero the depth counter on the gauging winch c. Lower the sounding weight to the bed of the stream. Read and record the sounded depth DF and the vertical angle . These tables have also been produced in an expanded form for use in the field (See tables 7 and 8.) d. With the aid of the tables compute and record: (i) the air correction, D.E. from Table 7 (if applicable) (ii) the wet line depth EF = DF - DE (iii) the wet line correction for length EF and angle Table 8 from (iv) add both corrections together and subtract them from the sounded depth DF, this will give the actual depth. BC. Example 1 a. In gauging a deep swift stream from a cableway, the total depth measured by the gauging winch counter from the guide pulley to the surface was measured as 3.00 m. The observed depth of water (after zeroing the counter with the displacement mark at water surface) was measured as 4.55 m and the vertical angle was 200. Find the true depth and the current meter positions using the 0.2 and 0.8 depth method. The distance from the centre line of the current meter to the bottom of the weight was 0.30 metre. From Figure 13. AB = 3.00 m =200 DF = 4.55 m Air-line correction, DE, from Table 7, for 200 and 3.00 m Therefore DE = 0.19 m Wet-line depth EF = DF-DE = 4.55 - 0.19 = 4.36 m Wet-line correction from table 8 for 200 and 4.36 m Therefore Wet-line correction = 0.09 m Therefore true depth BC = 4.36 – 0.09 = 4.27 m b. To place the current meter at the 0.8 depth position in the vertical. 0.8 x wet-line = 0.8 x 4.36 = 3.49 m. - 37 - Therefore the current meter should be raised and set at a depth of (3.49 + 0.30 + 0.19) = 3.98 m on the counter. (Airline correction = 0.19) To place the current meter at the 0.2 depth position in the vertical. 0.2 x wet-line depth = 0.2 x 4.36 = 0.87 m. Therefore the current meter should be raised and set at a depth of (0.87 + 0.30 + 0.19) = 1.36 m on the counter. Example 2 In gauging a deep swift stream from a cableway the depth measured using a tagged sounding line was 4-36 m and the vertical angle was 200. = 200 EF = 4.36 m Wet-line correction from table 8 for 200 and 4.36 m = 0.09 m Therefore the true depth BC = 4.36 – 0.09 = 4.27 m The current meter positions in the vertical as per example 1 minus the airline correction. I.e. 0.8 depth setting = 3.79, 0.2 depth setting = 1.17.) USE OF METER DEPTH SETTING TABLES These tables can be used under the following circumstances. 1. If no significant drift angle is observed, tables can be used directly for the setting of the meter in the vertical whether using tags or a depth counter. The meter position relative to the bottom of the weight is taken into account on individual tables. (Check use of correct table). 2. If significant drift angle carried out utilizing a counter, is observed and depthing is Procedures "A" or "B" may be used. (A) The tables procedure. may be used by complying with the following 1. Subtract the airline correction fro the counter reading to derive wet-line length. 2. Refer to the appropriate meter setting table and ascertain the appropriate counter reading. 3. Add the airline correction to the table result. - 38 - (B) Calculations may be made manually as follows. 1. Subtract the airline correction from the counter reading to derive the wet-line length. 2. Multiply the wet-line length by the required meter setting factor e.g. 0.2 or 0.8 then 3. Add distance of meter above weight bottom and 4. Add the airline correction. The procedures outlined in this section should be carried out with care to avoid magnifying the errors involved. The two main difficulties in measuring from a cableway are: a. Employing an adequate sounding sounding line in a vertical position. weight to maintain the b. Measuring the vertical angle. 2.5.2 Oblique flows (Angled Flow) Oblique or angled flow is flow that is not at 900 to the measuring section. The angle of flow is that angle between a 0 line at 90 to the section and the direction of current. To eliminate errors introduced by such angles it is necessary to obtain the component of the velocity normal to the crosssection. To make the correction for oblique flow for a rod supported meter, the current meter is rigidly held in line with the direction of flow. (Tail fins must be used to ensure correct alignment.) (See Figure 14). For a current meter suspended from a line, the meter will automatically take up the direction of the current. The velocity in the direction of the current and the angle of deflection are measured. The measured velocity, when multiplied by the cosine of the angle of the current, gives the velocity component normal to the measuring cross-section. For small angles of less than 8 0 the correction is negligible. The assumption is made that the point velocity corrections apply to the whole vertical or between velocity points in the vertical. When a correction has to be applied for oblique flow, the velocity observations on the measurement field sheet should be adjusted by the cosine of the angle of flow to the normal. The field sheet does not allow for this adjustment to velocities, so the correction is applied to the section width by booking the angle in the "horizontal angle" column. The resulting discharge in the section is the same but because incorrect area readings are used to obtain the discharge potential problems exist for users of the data. However, unless the field computation sheet is modified the corrections should be booked in this way and appropriate comments made in the remarks section. A worked example is shown in Figure 16. - 39 - Propeller type current meters with a "component propeller" measure the velocity component normal to the measuring section in oblique flow up to an angle of 450, depending on type, and no correction is necessary if the current meter is held rigidly at right angles to the measuring section. (See Figure 15). FIGURE 14 - Conventional Current Meter FIGURE 15 - Component Propeller Meter CORRECTION FOR OBLIQUE FLOW 2.5.3 Pulsations in flow The phenomenon of pulsation has an effect on the measurement of point velocities and therefore on current meter gauging in general. The velocity at any point in the stream is continuously fluctuating with time even when the discharge is constant and when the surface is apparently smooth and free from surges and eddies. This pulsation is caused by secondary currents developed by hydraulic conditions upstream of the gauging site. For example; obstructions in the approach channel, by surging produced at riffles or rapids being continued through pooled reaches, or by the acceleration of the water at bends. Generally, the velocity at any point changes in cycles that can vary from a few seconds to possibly more than 1 hour. Lower velocities have a pulsation of a greater magnitude and should therefore be observed over a longer period than higher velocities. Whilst it is customary to observe velocity at a point for a period of 40 to 120 seconds, it should be recognized that this time range is not long enough to ensure the accuracy of a single point velocity observation. However, because the pulsations are random and because observations are made at in excess of 16 verticals, usually with two observations being made in each vertical, there is little likelihood that the pulsations will bias the total discharge measurement in each stream. Longer observation periods should not be used if there is a likelihood of a significant stage change during the measurement period. Longer observation periods also increase the operating cost when a large number of gauging stations are considered. - 40 - THIESS SERVICES FIGURE 16 - DISCHARGE FIELD SHEET - CORRECTION FOR OBLIQUE FLOW - 41 - 2.5.4 Mean gauge height for current meter measurements The mean gauge height of a discharge measurement represents the mean stage of the stream during the measurement period. The mean gauge height is one of the two co-ordinates used in plotting the discharge-rating curve for gauging stations. An accurate gauge height is as important as an accurate measurement of the discharge. There is no difficulty in determining the gauge height that corresponds with the measured discharge during constant or nearly constant stream stage. If the change in stage is minimal and the discharge distribution is uniform the arithmetic mean of the start and end gauge height can usually be taken as the mean gauge height. However, measurements are often made during periods when the change in stage is neither uniform nor slight and the discharge distribution is not uniform. The correct gauge height is obtained by computing the weighted mean gauge height which requires additional observations of stage between the start and end of the measurement. The readings are made at regular intervals or as required depending on the rate of change of stage. The assistance of a gauge reader is usually necessary for obtaining the readings and noting the time of observations. The weighting is done by using partial discharge, time, or a combination of both as the weighting factor. Studies have shown that discharge weighting tends to over estimate the mean gauge height, whereas time weighting tends to under estimate the mean gauge height. Ideally both methods should be used and the result averaged, however either method may be used if the average result is considered unsatisfactory. Where weighting has been used the method adopted should be indicated on the measurement note sheet. A description of the two methods follows. (See Figure 17) 2.5.4.1 Discharge weighting In this process the partial discharges measured between observations of gauge height are used with the mean gauge heights for the periods when the partial discharges were measured. The formula used to compute the mean gauge height is: H = q1 x h1 + q2 x h2 + q3 x h3.....+qn x hn Q where H = mean gauge height in metres. Q = total measured discharge in megalitres/day q1, q2, q3, qn = discharge measured during the time interval 1,2,3,n in megalitres per day. h1, h2, h3, hn = average gauge height during the time interval 1,2,3, n in metres. - 42 - Figure 17 shows the computation of a discharge weighted mean gauge height This has been done using a standard form. 2.5.4.2 Time weighting In this process the arithmetic mean gauge heights between observation times are used with the duration of those time periods. The formula used to compute the mean gauge height is: H = t1 x h1 + t2 x h2 + t3 x h3.....+tn x hn T where H = mean gauge height in metres. T = total time for the measurement in minutes t1, t2, t3, tn = duration of observation times, in minutes, between stage reading. h1, h2, h3, hn = average gauge height, in metres during the time period 1,2,3,n The computation of the weighted mean gauge height using both methods is shown in Figure 17. 2.5.5 Rapidly changing stage When extremely rapid changes in stage occur during a measurement, the weighted mean gauge height is not truly applicable to the discharge measured. Measurements made under these conditions should be completed more rapidly than those made under constant or slowly changing stage to reduce the range in stage. Shortcuts in the measurement procedure usually reduce the accuracy of the measured discharge, therefore procedures during rapidly changing stage must be optimized to minimise the combined error in measured discharge and mean gauge height. The reduction in measurement time makes it possible to obtain a gauge height value that is representative of the measured discharge. The procedure for measuring discharge on large and small streams also varies due to the different behaviour of flood and peak flows on each type. The procedure to be followed for each is: - 43 - 2.5.5.1 Large Streams During periods of rapidly changing stage on large streams the discharge measurement time may be reduced by modifying the standard measurement procedure in the following way: a. Use the 0.6 depth method (See section 2.2.2.). The 0.2 depth method (See section 2.4.6.1) or the sub-surface method (See section 2.4.6.2) may be used if placing the meter at the 0.6 depth creates vertical angles requiring time consuming corrections, or if the vertical angle increases because of drift collecting on the sounding line. b. Reduce the velocity observation time. c. Reduce the number of verticals taken. d. By taking velocities at every second vertical only. This is a valuable method in cases of changing sections. An accurate profile and area is obtained with little extra time. By incorporating the above procedures a measurement can be made in 15 to 20 minutes. The standard error using a 25 second observation period and the 0.6 depth method with velocity observations at 16 verticals is 8%. The error created when using the short cut method is generally less than the error caused by shifting flow patterns during rapidly changing stage. 2.5.5.2 Small streams To obtain discharge measurements of flash floods on small streams, advance warning of the event is required to enable the hydrographer to be on site and prepared before the stream starts to rise. The measurement procedure is as follows: a. Use 6 to 10 verticals in the measurement cross-section. The actual number depends on the width and uniformity of the crosssection. b. Current meter observations are commenced as soon as the stream starts to rise and are continued until the flow returns to near normal. After completing one traverse of the crosssection, the next traverse is started immediately in the opposite direction, and observations are continued back and forth. c. Single velocity observations should be taken in each vertical using the 0.6 depth method (See section 2.2.2) or the 0.2 depth method (See section 2.4.6.1). d. Staff or auxiliary gauge readings at the measuring section are made at the start and finish of each traverse. Intermediate readings are made at a minimum of every third vertical and the time is recorded for each. - 44 - FIGURE 17 - TIME & DISCHARGE WEIGHTED MEAN GAUGE HEIGHT COMPUTATION - 45 - When the stream has receded the stream bed elevations in the vertical are checked to determine if any changes have occurred. The most reliable results are obtained where the streambed is relatively stable. Because of the rapid change of stage that occurs during each traverse, the conventional computation procedure cannot be applied. The alternative to follow is to construct an individual relation of mean velocity to stage for each observation vertical. The mean velocity is obtained by applying the appropriate coefficient to each observed value. For each vertical, mean velocity is plotted against stage and each point is identified by time. A single smooth curve is fitted to the points, but a scatter may indicate the need for a curve for the rising limb of the hydrograph and another for the falling limb of the hydrograph. With this information a stage-discharge relation can be constructed for the station. The section widths are known, the mean velocities are known and for any stage the corresponding depths are known. These data can then be used in the conventional manner, to compute the total discharge corresponding to a selected stage. By repeating the operation for several stages, a stage discharge relation for the entire stream is constructed. If necessary, one for the rising and one for the falling limb of the hydrograph can be compiled. 2.5.6 Correction of discharge measurement for storage If a discharge measurement is taken some distance from the gauge during a change in stage, the discharge passing the gauging station control will not be the same as the discharge at the measuring section due to the effects of channel storage between the two sites. Adjustment for channel storage is made using a figure obtained by multiplying the channel surface area by the average rate of change in the reach to the measured discharge. A reference gauge set at the measuring site is required to enable the necessary calculations to be carried out. The water surface elevation at the measuring section and at the gauging station is determined before and after the measurement to compute h. If the measurement is made above the control, the adjustment will be added for a falling stage and subtracted for a rising stage and conversely if the measurement is made below the control the adjustment will be subtracted for a falling stage and added for a rising stage. The adjustment for storage is separate and distinct adjustments required for changing stage and variable slope. - 46 - from The formula for storage adjustment is: h x 86.4 t Qg = Qm ± W x L Where Qg = Discharge going over the control in megalitres per day. QM = Measured discharge in megalitres per day. W = Average width of the stream between section and control, in metres. L = Length of reach between the measuring section and control, in metres. measurement h = Average change in stage in the reach, L, during the measurement in metres. t = Elapsed time during the measurement in seconds. A worked example of adjustment for storage is shown in figure 18. The adjusted discharge figure is the one used for defining the stage - discharge relation. 2.5.7 Correction of discharge measurement for travel time It is also possible to approximate the effect of storage by computing the time of travel of the flood wave between the measuring section and the control and then adjusting the gauge height for the travel time to correspond to the measured discharge. Adjustment can be made by applying a correction to the observed gauge at the gauging station control using the following formula. S = R x L x 1440 1.3 V Where S = Stage difference at the control gauge in metres. R = rate of change of stage, = = L = length kilometres of reach between difference (in metres) time (minutes) metres/minute measuring site and gauges, in V = mean velocity of measurement, in kilometres per day. If the measurement is made upstream from the control, the stage difference (S) will be subtracted from the control gauge heights - 47 - on a falling stage and added on a rising stage. Conversely, if the measurement is made downstream from the control, the stage difference (S) will be added to the control gauge height on a falling stage and subtracted on a rising stage. A worked example is shown in Figure 19. height is the figure used for defining relation. The adjusted gauge the stage–discharge STORAGE When the measuring section is remote from the gauging station. Measuring section 1.2 Km Direction of flow Gauging Station/Control QG = Discharge going over the control = ? ML/d QM = Discharge measured. ML/d = 7780 Stage at control during measurement ∴Change in stage at control = 2.20m at 15:00 hours = 1.80m at 17:10 hours = -0.40m Stage at measuring section during measurement= 3.62 m at 15:00 hours = 3.14 m at 17:10 hours ∴Change in stage at measuring section = -0.48 m h = Average change in stage = (0.40 + 0.48) = 0.44 2 t = Elapsed time during measurement = = 2 hours 10 min 7800 seconds L = Distance between measuring section and control = 1200 metres W = Average width between measuring section and control = 65.2 metres The measuring section is upstream of the control and the stage is falling, therefore the correction will be positive. USING: QG = QM + W * L * h*86.4 t Ml/d - 48 - ∴QG = 7780 + 65.2 * 1200 * 0.44 * 86.4 7800 ∴QG = 8161 ML/d FIGURE 18 - CORRECTION OF DISCHARGE MEASUREMENT FOR STORAGE 2.5.8 Measurement of discharge with sections of dead water When discharge measurements are carried out in natural channels, flow conditions may vary with stage and create less than ideal conditions. These problems can be overcome by utilizing alternative measuring sites where better conditions predominate. However, alternative sites are not always available and these problems have to be identified and compensated for within the discharge measurement. One such problem is an area of no flow commonly called dead water, adjacent to one or both of the stream banks. If a discharge measurement has to be carried out and this problem is evident, the following procedure should be adopted. a. The complete cross-section should be gauged from waters edge to waters edge. This includes all sections where dead water occurs. b. Soundings should be taken at regular intervals through the section of dead water. c. Velocity observations first detected. should commence from where flow is d. The discharge measurement is then carried out as normal. This procedure has been adopted so that the bed profile, area and mean velocity for a particular stage can be accurately identified. This is essential when measurements are compared for rating purposes to validate measurements and to extrapolate rating curves. Figure 20 shows the booking procedure to be followed. - 49 - FIGURE 19 - CORRECTION OF MEASUREMENT GAUGE HEIGHT FOR TRAVELTIME - 50 - DEAD WATER No velocity 3m No velocity No velocity Dead water between 3.0 and 9.0 metres 4m 6m 8m Left Bank 10m To gauge this section correctly, the complete cross-section must be sounded and the point where flow starts should be where readings commence. THIESS SERVICES FIGURE 20 - CORRECTION OF DISCHARGE MEASUREMENT FOR DEAD WATER - 51 - 2.5.9 Measurement of discharge with sections of reverse flow When discharge measurements are carried out in natural channels, flow conditions may vary with stage thus creating less than ideal conditions. These problems should be overcome by having alternative measuring sites where better conditions predominate. However, alternative sites are not always available and these problems have to be identified and compensated for within the discharge measurement. One such problem is reverse flow adjacent to one or both of the stream banks. If a discharge measurement has to be carried out and this problem is evident, the following procedure should be adopted, a. The complete cross-section should be gauged from waters edge to waters edge. This includes all sections where reverse flow occur. b. The sections where reverse flow starts and ends should be identified and noted in the remarks column. c. The sections with reverse flow should be gauged as normal. d. The sections where reverse flow ends and normal flow commence should be kept as small as possible to minimise errors. e. When the measurement has been completed, the total discharge of the sections with reverse flow should be subtracted from the total discharge of the sections with normal flow. f. The mean velocity is calculated from sectional area and the adjusted discharge. the total cross- This procedure has been adopted so that the bed profile, area and mean velocity for a particular stage can be accurately identified. This is essential when measurements are validated and compared for rating purposes. Figure 21 shows the booking procedure to be followed. 2.5.10 Measurement of discharge with variable backwater Several factors can cause scatter of discharge observations about the stage discharge relation at a station. Backwater is one of these factors. The velocity is retarded resulting in higher stage for the same discharge. Backwater is caused by constrictions such as narrow reaches of a stream channel or artificial structures downstream such as dams or bridges or downstream tributaries. All these factors can increase or decrease the energy gradient for a given discharge and can cause variable backwater conditions. Regulated streams may have variable backwater most of the time, whilst other streams will have only occasional backwater from downstream tributaries or from the return of over bank flow. - 52 - 3.0 4.5 5.0 Left Bank 6.0 7.0 Right Bank 9.0 8.0 Reverse flow between 3.0 and 7.0 metres HYDROGRAPHIC SERVICES DISCHARGE MEASUREMENT Meas. No: 83/7 Weighted Mean: 1.953 COMPUTATIONS 16:50 3.0 N.D. NO VEL REVERSE 4.5 0.80 REVERSE 5.0 1.40 REVERSE 6.0 1.60 17:00 7.0 1.70 17:04 8.0 1.74 9.0 1.68 9.5 1.70 10.0 1.70 17:15 10.5 1.66 11.0 1.60 11.5 1.50 12.0 1.30 12.5 0.80 17:25 13.0 N.D. 5 6 8 8 6 6 NO NO 6 6 15 15 20 20 20 20 20 20 20 20 25 20 20 15 10 8 NO 43.0 50.0 42.0 46.0 43.0 51.0 VEL VEL 42.0 47.0 47.0 54.0 41.0 47.0 50.0 55.5 42.5 44.0 48.0 50.5 50.5 42.0 54.5 58.5 47.0 53.5 VEL NO FLOW NO FLOW FORWARD FORWARD FORWARD FORWARD FORWARD FORWARD FORWARD FORWARD FORWARD FORWARD FORWARD FORWARD FORWARD FORWARD FORWARD FORWARD FORWARD FORWARD 1.952 1.948 Counter No: Area Disch arge Velocity Point Waters Edge L/B 1.958 Mean Gauge Height: 1.954. Time (Seco nds) Distan ce Vert Angle Adjust ed Depth Revs Meter TR2073 Weight: 23Kg No: Tape No: OBSERVATIONS Wad Rod No: REMARKS Time Method: SUSP 2P 1.958 17:1 17:2 5 5 1.952 1.948 Sample No: Adjust ed Horiz. Angle Width 30m u/s of gauges Depth Point of Measurement: Party: FY/GR Date: 24/10/1983 17:04 Mean Depth Station: DARTMOUTH Stream Temp: 7 EC @ 25 deg: 50 Mean Vert Mean Sect Stream: PLURRY RIVER Conditions : Weather: Fine Stream: Falling Time 16:5 17:00 E.S.T. 0 Gauge 1.960 1.958 Height Rec Height 1.960 1.958 0.0 7.5 7.7 11.8 10.8 8.8 7.6 0.0 0.0 9.0 8.2 19.2 16.8 29.0 25.4 24.0 21.6 28.0 27.2 25.0 23.8 29.4 29.0 22.0 15.6 13.0 9.4 3.80 0.600 0.400 1.5 2.280 9.45 0.550 1.100 0.5 5.198 9.75 1.500 1.500 1 14.625 4.10 1.650 1.650 1 4.30 1.720 1.720 1 6.765 28.868 7.396 13.30 1.710 1.710 1 22.743 22.60 0.845 1.690 0.5 19.097 25.00 0.850 1.700 0.5 21.250 25.20 0.840 1.680 0.5 21.168 26.00 0.815 1.630 0.5 21.190 26.80 0.775 1.550 0.5 20.770 24.00 0.700 1.400 0.5 16.800 15.00 0.525 1.050 0.5 7.875 5.60 0.200 0.400 0.5 1.120 159.409 130.542 7.6 11.3 8.2 0.0 8.6 18.0 27.2 22.8 27.6 24.4 29.2 18.8 11.2 0.0 Disch. FIGURE 21 - CORRECTION OF DISCHARGE MEASUREMENT FOR REVERSE FLOW - 53 - Many sites can be operated by utilizing the stage-fall-discharge method using the control gauge, at which stage is measured continuously, and current meter measurements made occasionally. An auxiliary reference gauge should be installed some distance downstream from where stage is measured continuously. When the gauges are set to the same datum, the difference between the two stage records is the water surface fall and provides a measure of the water slope. Precise time synchronisation between the gauge sets is very important if stage changes rapidly or when fall is small. Reliable records can usually be computed when the fall exceeds 0.1 metre. Under backwater conditions the fall measured between the two gauge sets is used as a third parameter and the rating becomes a stage-fall-discharge relation. 2.5.11 Measurement of discharge with tributary inflow If a discharge measurement is made at a site some distance from the gauging station control it is necessary to determine whether there is additional inflow between the measuring site and the station control. When a significant inflow has been identified it must be measured, or if the flow is insignificant compared to the mainstream flow it may be estimated. This discharge is then used to determine the actual flow at the gauging station. If inflow occurs upstream of the gauging station and downstream of the measuring site then the tributary inflow is added to the measured discharge. If an inflow occurs downstream of the station control and upstream of the measuring site then the tributary inflow is subtracted from the measured discharge. 2.5.12 Overflow (out-of-bank flow) Streams with large overflow or out of bank flow present many complications in stream flow measurement and in the determination of the stage-discharge relation, particularly during rising and falling stage. It is possible to establish separate discharge rating curves for flow in the main channel and in the overflow area with the total discharge being the sum of these. There are two distinct types of overflows. a. Anabranch flow Anabranch flow is flow that is separate to, but derived from the mainstream. If anabranch flow is encountered it should be measured first as this is generally where the greatest change in discharge is occurring. Mainstream flow in this case generally changes far less and can be measured later or estimated from a mainstream only stage-discharge relation by extrapolating the curve from earlier measurements. No significant loss in accuracy occurs. Auxiliary gauges should be placed at the anabranch to assist in establishing a stage-discharge relation separate from the mainstream. The gauges should also be set to the same datum as the main stream gauges. - 54 - b. Flood plain flow Flood plain flow is part of the mainstream flow that has spilled onto the adjoining flood plain. Any stage change in the flood plain is reflected by a similar stage change in the main stream. 2.5.13 Velocity measurement to a vertical wall It is usually necessary to estimate the velocity at an end vertical as some percentage of the adjacent vertical because it is not possible to measure the velocity accurately with the current meter close to a vertical wall. Laboratory tests suggest that the mean velocity in the vertical in the vicinity of a smooth sidewall of a rectangular channel can be related to the mean velocity in the vertical at a distance from the wall equal to the depth. When velocity observations are taken at a distance from a vertical boundary, which is less than the depth, the results should be treated with caution. In many cases we are required to take velocity readings within this area. For this reason Table 9 has been produced to enable an estimation of the velocity, within this area and at the vertical boundary, relative to the adjacent observed velocity. Example 1 The last from the i.e., at boundary. actual velocity observations were taken at a distance vertical boundary equal to the depth at the boundary, chainage 21.5 m that is a distance of 4.0 m from the (See Figure 22) Given a depth at the wall of 4.0 m and a mean velocity of 62.64 Km/d at chainage 21.5 m. To calculate the mean velocity at 23.5 m. Ratio of distance to depth at known velocity = 4/4 = 1 Ratio of distance to depth at required vertical = 2/4 = 0.5 From Table 9 the multiplication factor = 0.95 The Mean Velocity at chainage 23.5 m = 0.95 x 62.64 = 59.51 Km/d - 55 - TABLE 9 - VELOCITY CO-EFFICIENTS IN VICINITY OF A VERTICAL WALL FIGURE 22 - VELOCITY ADJUSTMENT AT A WALL – SAMPLE CROSS SECTION - 56 - Waters Edge L/B Conditions : Weather: Fine Stream Temp:18.5 Sample No: Stream: Steady EC @ 25 deg: Time E.S.T. 12:00 13:20 Gauge Height 1.735 1.735 Rec Height Mean Gauge Height: 1.735 Weighted Mean: Counter No: Disch Adj Widt Horiz . Wid Mean Dept Area COMPUTATIONS Vel Time Sec Revs Vert Angl Adj Dept Dept h Dist Time HYDROGRAPHIC SERVICES DISCHARGE MEASUREMENT Stream: GOULBURN RIVER Meas. No: 1 Station: MADDOGS Date: 29.12.87 Point of Measurement: 100m d/s Method: W Party: JB RC Meter 5973 Weight: No: 2 Wad Rod No: Tape No: REMARKS OBSERVATIONS Point Mean Mean Vert Sect 0.0 12:00 2.5 3.5 0.50 15 50.0 17.9 17.9 4.5 1.20 6.0 2.30 12:20 8.5 3.70 30 40 90 50 90 60 40 60 40 60 50 60 50 60 90 60 40 60 42.0 43.0 42.0 49.5 42.0 95.0 45.0 45.0 41.0 41.0 48.0 61.0 49.0 93.0 90.0 93.0 43.0 98.0 41.3 53.5 54.8 58.0 54.8 76.3 51.2 76.3 56.1 83.6 59.8 83.6 58.6 79.8 57.4 79.8 53.5 71.6 8.95 0.250 0.250 1 2.238 32.65 0.850 0.850 1 27.753 51.90 2.625 1.750 1.5 136.238 60.98 7.500 3.000 2.5 457.313 64.65 9.750 3.900 2.5 630.338 66.80 10.375 4.150 2.5 693.050 70.78 8.400 4.200 2 594.510 70.45 8.500 4.250 2 598.825 68.90 9.000 4.500 2 620.100 65.58 8.860 4.430 2 580.995 61.03 8.260 4.130 2 504.067 57.90 4.050 234.495 48.50 4.000 194.000 47.4 56.4 65.6 11.0 4.10 63.8 13.5 4.20 15.5 4.20 17.5 4.30 19.5 4.70 13:00 21.5 4.16 23.5 4.10 59.5 24.5 4.00 56.3 13:20 25.5 4.00 40.7 69.9 71.7 69.2 68.6 62.6 Disch FIGURE 23 - VELOCITY ADJUSTMENT AT A WALL. SAMPLE MEASUREMENT To calculate the mean velocity at chainage 24.5 m Ratio of distance to depth at known velocity 4/4 = 1 Ratio of distance to depth at required vertical = 1/4 = 0.25 From table 9 the multiplication factor = 0.90 The mean velocity at chainage 24.5 m = 0.90 x 62.64 = 56.38 Km/d To calculate the mean velocity at chainage 25.5 m (wall). Ratio of distance to depth at known velocity = 4/4 = 1 - 57 - 5273.919 Ratio of distance to depth at required vertical = 0/4 = 0 From Table 9 the multiplication factor = 0.65 The mean velocity at chainage 25.5 m = 0.65 x 62.64 = 40.72 Km/day It may however have been possible, without undue risk of damage to the meter, to take velocity observations at a distance from the vertical wall of half the depth at the boundary, i.e., at chainage 23.5 m. If this is the case it should be done bearing in mind what is written in the first paragraph of this section. Example 2: Using Figure 22, if a current meter observation was taken at chainage 23.5 m the resultant actual mean velocity would be in the vicinity of 59.5 Km/d. (as obtained by calculation in the previous example). The velocity at chainages 24.5 m and 25.5 m would then be calculated using Table 9 in the following manner. To calculate the mean velocity at chainage 24.5 m. Ratio of distance to depth at known velocity = 2/4 = 0.5 Ratio of distance to depth at required vertical = 1/4 = 0.25. From Table 9 the multiplication factor = 0.947 The mean velocity at chainage 24.5 m = 0.947 x 59.5 = 56.4 km/d To calculate the mean velocity at chainage 25.5 m (wall). Ratio of distance to depth at known velocity = 2/4 = 0.5 Ratio of distance to depth at required vertical = 0/4 = 0 From Table 9 the multiplication factor = 0.684 - 58 - The mean velocity at chainage 25.5 m = 0.684 x 59.5 = 40.7 Km/d 2.6 Errors in Streamflow Measurement There are three main sources of error that accuracy of a discharge measurement. They are: can reduce the 2.6.1 Human Error Human errors are those made by the observer in reading instruments or tags, making biased observations by reading high or low consistently or by actually booking incorrectly. Many factors such as weather conditions, inadequate training, mental attitude and equipment condition contribute to such errors. These errors can be reduced and their effect minimised by proper training, by creating and maintaining high morale through involvement and by appropriate maintenance and development of equipment 2.6.2 Instrument Error The condition and type of instruments used and their calibration effect the accuracy of the discharge measurement. The instruments used in making discharge measurements include the current meter, depth and revolution counter, stop watch, depth indicator and width indicator. It is difficult to evaluate instrument error but investigations generally indicate an error of less than 1% if all instruments are in good condition. Current meters are usually accurate to within 2% of a standard rating providing the meter is undamaged and the velocities being measured are within the limitations of the meter. (See Table 10) Gurley Pygmy OTT. C31 OSS. OSS. SIAP PC1 PC1 B1 Prop Prop Prop Prop Prop Prop Prop TABLE MIN. VEL. 2.6 Km/d 1.3 Km/d 1 2.6 Km/d 3 4.8 Km/d 1 2.2 Km/d 3 3.0 Km/d 2 3.5 Km/d 4 3.5 Km/d 1 4.3 Km/d 10 - CURRENT METER PERFORMANCE - 59 - MAX. 526 109 432 860 172 518 865 345 865 VEL. Km/d Km/d Km/d Km/d Km/d Km/d Km/d Km/d Km/d It is important that if suspect or damaged bucket wheels or propellers are used, appropriate notes should be made on the measurement and that the meter be rated in that condition in order to derive correct velocities. The meter must then be repaired and re rated prior to further use. All equipment should be treated carefully, be well maintained and regularly checked for malfunction. Typical checks that can be carried out are: (a) Stop watch checked against wrist watch (b) Rev. counters checked visually and against watch (c) Depth counters checked against tags (d) Tags checked against a tape (e) Observe and listen for an irregular beat in counter or headphones that could indicate contact maladjustment or failure. 2.6.3 Method Error (a) Velocity Error This is the error due to the assumption that the mean of the point velocity observations taken equals the mean velocity in the vertical. This error is minimised by increasing the number of observations in the vertical. (b) Pulsation Error This error is due to the assumption that the mean of the point velocity observations taken does not vary with time. This error is minimised by increasing the observation time period. (c) Velocity - Depth Error This is the error due to the assumption that the velocity and depth vary uniformly from one observation to the next. This error is related to the number of verticals used in the measurement. Assuming that 100 verticals would result in no error, a study carried out by the U.S.G.S indicates that the error in two out of three cases wou1d be less than: 4.5% for 10 verticals 3.0% for 15 verticals 2.5% for 20 verticals 1.2% for 40 verticals - 60 - 2.6.4 Sounding Error Sounding errors. errors can be due to method, human and instrument For a wading measurement, there should not be any error in the depth sounding. An error, however, in meter setting at a partial depth can occur when the wading rod must be lifted off the bed to set the meter. As a result the rod may not be replaced in the same position. Ideally the wading rod should not be lifted off the bed during observations in the vertical. Cableway and endless wire sounding errors will arise if the equipment is not properly maintained or due care is not taken. Errors may be due to: (a) Buoyancy of the meter and weight, causing the main support cable to rise and the horizontal section of the meter support (elseworth) cable to sag, when the weight and meter are completely immersed after zeroing the depth counter. For example a 45 kg gauging weight displaces approximately 5.5 kg of water resulting in an error in the vicinity of + 40 to 60 mm if sounding by depth counter. This effect is minimized by zeroing the depth counter when a pre-determined calibration mark on the weight corresponds with the water surface and by tensioning the main support cable to specification. It should be noted here that the light "Endless Wire" configuration as used at many gauging stations may be subject to greater error due to buoyancy than is the case with the heavier cableway. If soundings are made from an endless wire using a depth counter, a check must always be made on the buoyancy effect of the weight and meter at the particular site before commencing a measurement in order to ascertain the zeroing point. Cableways on the other hand if strained to specification should be more consistent therefore allowing pre-calibration and permanent marking of weights. The following method may be used to check the buoyancy effect on the soundings mark using a depth counter from an endless wire, cableway or boat: 1. Mark two points on the suspension cable at a known distant above the bottom of the weight. (Say 1.0 and 2.0 m). 2. With all equipment ready to commence gauging, including correct tensioning of the traversing cable, lower the gauging weight and meter assembly into the water until the predetermined mark (2.0 m) corresponds with the water surface level. (Ensure the weight is not on bed). 3. Zero the depth counter. 4. Raise gauging weight/meter assembly one metre and ensure that the second mark and counter agree. - 61 - 5. Raise the gauging weight and meter assembly until the depth counter reads negative 2.0 metres. 6. Note where the water surface cuts the weight in line with the hanger bar and mark if possible. FIGURE 24 - GAUGING WEIGHT ZEROING LINE (For depth counter use) This point becomes the zeroing point for that weight at that particular installation or for that particular boat. Note: The above error source only applies when sounding are made by depth counter. 2.6.4 Cont: (b) The uplifting force applied to the weight by the river bed in order to activate any mechanical sounding mechanism such as a bed feeler. This again causes the main support cable to rise and the horizontal section of the meter support cable to sag. (c) Drift of the meter and cable that has not been compensated for by measuring the drift angle. (d) Inaccuracies being horizontal be made in line angles not being in zeroing the counter due to the weight not (hence the suggestion that any calibration mark with the hanger bar), or turbulence and drift measured. (e) Inaccuracies in determining the bed due to poor sounding conditions such as moving sand bed, soft bed and steep banks. (f) Incorrect observations by the observer. (g) Incorrect booking of observations. The error due to (c) is covered in section 2.5.1. Increasing the weight and so reducing the drift angle can reduce this error. This correction however may increase the error due to (a) and in some cases could increase the overall error. 2.6.5 Width Errors Width errors can be both instrument and human. due to: - 62 - Errors may be (a) Mismarking or misinterpretation of marks on the traversing cable. (b) Malfunctioning or incorrectly calibrated width counters. (c) Distances not being measured from the standard distance datum. This gives errors in individual measurements where depths must be taken from a cross-section and when combining measurements for extrapolation at a particular vertical. Note: In order to minimise width errors the booker must check distances with the observer periodically throughout the measurement and at the end of the measurement. - 63 - 3.0 CURRENT METERS The current meter is still the most common instrument used to determine velocity. The principle is based upon the relation between the water velocity and the resulting angular velocity of the rotor. By placing a current meter at a point in a stream and counting the number of revolutions of the rotor during a measured time interval, the velocity of the water at that point can be determined. The number of revolutions of the rotor is obtained by various means, depending on the design of the meter, but normally this is achieved by an electric circuit through the contact chamber. In all types of design the electrical impulse produces a signal which either registers a unit on a counting device or an audible signal. A stop watch or an automatic timing device measures intervals of time. Current meters can generally be classified into two main types, those meters which have vertical axis rotors and are commonly known as cup type meters (Figure 25) and those which have horizontal axis rotors and are commonly called propeller - type meters. (Figure 26). Comparative tests of the performance of vertical axis and horizontal axis meters under favourable conditions indicate that almost identical results will be obtained. 3.1 Cup-type current meter. The cup-type current meter consists of a rotor revolving about a vertical shaft and hub assembly, bearings, main frame, a contact chamber containing the electrical contact, tail fin and a means of attaching the instrument to rod or cable suspension equipment. The rotor is generally constructed of six conical cups fixed at equal angles on a ring mounted on the vertical shaft. This assembly is retained in the main frame by means of an upper shaft bearing and a lower pivot bearing. The contact chamber houses the upper part of the shaft and an eccentric contact that wipes a platinum wire attached to the binding post. A separate reduction gear, wire and binding post provide a contact each time the rotor makes five revolutions. A tailpiece keeps the meter pointing into the current. Vertical axis current meters do not register velocities accurately when placed close to a vertical wall. When held close to a right bank vertical wall the cup-type meter will under register because the slower water velocities near the wall strike the effective concave face of the cups. The converse is true at a left bank vertical wall. The cup-type meter also under registers when positioned close to the water surface or close to the streambed. - 64 - The characteristics of this type of meter are summarized below: a. Robust instrument requiring little specialised maintenance. The rotor is replaceable in the field without affecting performance. b. The bearings are well protected from silty water by virtue of the fact that they operate in air pockets. c. A single velocities. rotor serves throughout the entire range of 3.2 Propeller - type current meter The propeller-type current meter consists of a propeller revolving about a horizontal shaft, ball bearings in an oil chamber, the body containing the electrical contact, a tailpiece with or without a vane and a means for attaching the instrument to suspension equipment. The meter may be supplied with one or more propellers, which differ in pitch and diameter and may be used for various velocity ranges. Also available are component propellers which automatically compensates for the velocity projection normal to the measuring section for angles up to 450 and velocities up to 260 km/day. However each propeller must be checked to ascertain the component it will measure. The characteristics of this type of meter are summarized below: a. The propeller disturbs flow less than the cup-type meter because of axial symmetry with flow direction. b. The propeller is less likely to become entangled with debris than the cup-type meter. c. Bearing friction is less than for vertical shaft because any bending moment on the rotor is eliminated. rotors d. A propeller-type current meter is not so susceptible to vertical currents as cup-type meter and therefore give better results when used for boat measurements. - 65 - FIGURE 25 - CUP TYPE CURRENT METER - 66 - FIGURE 26 - PROPELLOR TYPE CURRENT METER - 67 - 3.3 Rating of Current Meters. In order to determine the velocity of the water from the revolutions of the rotor of the current meter, a relation is established between the angular speed of the rotor and the speed of the water that causes it to turn. This relation is known as the current meter rating. The usual method of rating a current meter is to tow it through still water in a rating tank and observe the time of travel and the number of revolutions in a given distance. The number of revolutions per second and the corresponding velocity are then computed. When these two quantities are plotted against each other an equation is derived by establishing a line of best fit "through" all the plotted points. A rating table is prepared by using this equation. Thiess Services uses the Hydrological Services rating tank at Liverpool, NSW to rate each current meter. Meters are re rated every two years or more often if required. 3.4 Care of Current Meters To ensure reliable observations of velocity are obtained it is necessary to maintain the current meter in good condition. Good maintenance practices may be summarised as follows, a. Before and after each discharge measurement, examine the meter cups or propeller, pivot, bearing and shaft for damage, wear and faulty alignment. b. Clean and oil meters after use. (See section 3.5) c. Clean the meter immediately after each measurement, especially if it is used in sediment laden water. For cup type meters the surfaces to be cleaned and oiled are the pivot bearing, pentagear teeth and shaft, cylindrical shaft bearing and thrust bearing at the cap. (See section 3.5) d. After oiling and adjusting, spin the rotor to make sure that it operates freely. Identify and correct the trouble if the rotor stops abruptly. e. Record the duration of spin for a cup-type meter. A significant decrease in the duration of the spin indicates that the pivot or pivot bearing require replacement. f. Keep the pivot and pivot bearing separate when the meter is not in use. g. Replace worn pivots h. Limit on-site repairs to minor damage only. This is particularly the case with a propeller where small changes in shape can effect the rating. In cup-type meters minor dents in the cups can often be straightened - 68 - i. Repairs to badly sprung yokes, bent yoke stems, misaligned bearing tailpieces and propellers should be carried out in the workshop. j. Damaged plastic propellers should be replaced. k. If a suspension measurement is being carried out, check the meters balance on the hanger bar and the alignment of the rotor when the meter is on the hanger bar. Note: The balance should be observed with the meter submerged. The calibration and maintenance of vertical axis type current meters is presented in detail in a U.S.G.S. publication by "Smoot and Novak". A copy of this publication is available in the appendix. Also available are manuals for each propeller type meter, however these are not as detailed as the U.S.G.S. publication. 3.5 Maintenance and repair of the Gurley Current Meter. This section has been prepared by Andy Keep to provide information on variations to recommended procedure, as described by "Smoot and Novak" which have of necessity become accepted practice within Thiess Services. "The current meter is undoubtedly the Hydrographers tool of trade. It is the one indispensable item upon which the information he provides will ultimately depend. An inaccurate current meter, whether rendered so by neglect, damage, incorrect adjustment or any other cause, must yield incorrect data. At best this will result in delay, wasted effort and consequent expense and at worst could have far reaching effects involving considerable cost, inappropriate action and inconvenience in many quarters." The current meter is more prone to the development of error due to neglect or inexpert operation than virtually any other item that is used in conjunction with it. This comparatively delicate instrument should be treated at all times with the care and respect that it undoubtedly deserves and it is the aim of this section to ensure that this is the case. Referring now to Messrs. Smoot and Novak's "Calibration and Maintenance of Vertical Axis type Current Meters", pages 1 to 8 contain many interesting facts and useful information which any person involved in the operation of the Gurley meter would do well to read and digest. Points made in the Introduction on Page 1 are pertinent, and are worthy of even greater emphasis. Under the heading "Description of the Small Price Current Meter", sub-heading "Pivot", page 5, it should be stated that not many, if any, pivots currently in use in Commission meters are of stainless steel. Many are instead made of silver steel, whilst others have been made form 3/16" diam. high tensile steel - 69 - bolts. Both these materials are liable to rust, therefore care must be taken to remove the pivot, wipe it dry and either apply a penetrating oil or spray it with C.R.C., Formula 4 or similar fluid, immediately after the measurement is concluded. Some operators then prefer to place the oiled pivot in its rack in the meter box, which appears preferable to replacing it in the meter, the more so if the party is to travel some distance before the meter is next used. Then, under sub-heading "Pivot Bearing", page 5. Tungsten carbide, the material of which the pivot bearing is made, is second only to diamond in its degree of hardness. It can be refaced only using precision equipment which, paradoxically, employs a small, high-revving arbor of soft material to restore the bearing surface. Those who feel moved to clean out the pivot bearing of their meter with a needle or a long pin need have no fears that they will damage the surface. Tungsten carbide is, however, an alloy of steel and is therefore vulnerable to rust, so the pivot bearing must also be oiled or sprayed immediately after use. "Binding Posts", page 5. The type of brush contact described here was fitted to all SR&WSC Gurley meters prior to the late 1950's, at which stage it was identified as the reason for signal difficulties in some streams, mainly in the north of the State, due to the formation of silver nitrate on the contacts through electrolytic action. The stainless steel-silver combination was then replaced by a platinum wire that solved the problem. "Assembly and Disassembly of the Small Price Current Meter". A few points in this section are worthy of comment, e.g. Step 3. The letter "S" mentioned here seems to have been replaced by the letter "5" on most Gurley meters operating in Victoria. Step 4. Everybody should now know why there is a hole in the shaft of the Gurley meter, and hopefully the question will not be asked again for some years. Unfortunately there are also grooves and scores on some of these shafts where pliers have been used with rather too much enthusiasm in the absence of a tightening pin. There is absolutely no need to screw this shaft in as if it was a cylinder head bolt. It will remain in place if tightened with just enough tension to make sure that it is right home, and if this recommendation is followed there will be no need to get out the Stillsons when it next requires to be removed. Step 9. Here again, there is no need to apply the contact chamber cap with unnecessary force. The cap, in its original condition is knurled, indicating that it is to be tightened by hand, and as the thread is very fine, it should be possible to obtain ample pressure to seal the joint without the aid of pliers. "Disassembly". - 70 - The authors have made two extremely valid points in this section, which should be carefully observed to avoid damage as described. A sound alternative practice is to commence disassembly by removing the contact chamber complete with cap. "Inspection and Repair of Current Meters". It will be noted that the phrase "should be replaced with a new one" keeps recurring throughout this section, which we may take as an indication that the authors are blissfully unaware of the financial drought which has quite recently overtaken Hydrographic activities in this State. It is probably fair comment to suggest that if the advice offered here were to be taken literally, the only original part remaining on some current meters may be the contact chamber cap. Fortunately for the continuation of our activities it has been proved repeatedly that, contrary to the recommendations contained in this section of the text, almost any component of a Gurley current meter can be satisfactorily reconditioned or repaired without any serious detrimental effect to the original sensitivity of the meter, and with minimal effect as regards it's ratings, which of course must always be re-established in such cases. Rotor and Shaft Alignment The text specifically describes procedures for identifying this fault. Should the shaft be bent in its thinner top section as will be more commonly the case, it is best straightened by gripping the full length of this section in a 3 jaw drill chuck and exerting gentle pressure in the appropriate direction, from time to time checking alignment by operating the drill momentarily. Alternatively a 1/8* diameter hole of sufficient length to fully accommodate the narrow portion of the shaft may be drilled in a metal block in which the narrow section can be inserted for full support, and pressure exerted to restore alignment, the shaft being rotated by hand in order to check on progress. A bend in the heavier section of the shaft may be dealt with in much the same manner, however as the repair must be perfect it is strongly suggested that it be placed in experienced hands. Eccentricity, presumably meaning a buckle, in the bucket wheel can usually be corrected but repairs must not be attempted whilst the wheel is still fitted to the meter or a bent shaft will probably result. Remove the wheel from the meter, then remove its hub assembly and mount the wheel between two nuts on the threaded end of a long 3/8" diameter precision bolt. The buckle can then be removed using both long nose and standard pliers. Sprung Yoke A sprung yoke is usually indicated if the screwed sleeve, which raises the cup bearing from the pivot, appears to screw down 1/8" or more before it lifts the wheel assembly. A check can be carried out using a straight piece of 3/16" diameter steel rod. - 71 - Strip the yoke, and insert the rod through the pivot hole so that its other end passes through the hole vacated by the contact chamber. If the rod is located centrally in the contact chamber hole, all is well. If not, the yoke may be either sprung or twisted, and the position of the rod in the hole will indicate which way the yoke must be bent to correct the situation. Controlled leverage should be used rather than impact, in other words don't belt it back into line with the hammer. Damaged Cups. This is a common problem which can and should receive regular attention. Techniques and tools which can be used to re-shape damaged cups are available in each centre. Statements have been made that minor damage to the bucket wheel of the Gurley meter has negligible effect on the rating. The authors of the text do not appear to agree, and as accuracy is a prime consideration the risk should not be taken when with a little effort it can be avoided. Contact Chamber. The text is self-explanatory and deals with the component and its contents quite fully, therefore little additional comment is necessary. It may be worthy of mention that the upper bearing can be re-bushed very easily and at little expense if an undue amount of wear should occur at that point. Pivot and Bearings. It seems from the text that the meter pivot should be changed at an earlier stage of wear than some operators may have believed. There is said to be ample evidence to suggest that a worn pivot has quite minimal effect on sensitivity in velocities between about 15 Km/day and 40 Km/day, and no effect above that stage, but this should not be used as an excuse for failing to change the pivot when wear exceeds the specified limit. Whereas use of a worn pivot will do little harm to the pivot bearing, persistence with a worn pivot bearing will rapidly destroy the pivot, and in cases where a meter appears to be consuming pivots at a fast rate the pivot bearing should be immediately suspected and inspected. A quick and usually accurate check can be carried out without fully dismantling the meter by feeling the bearing surface with the point of a needle or a long pin. If roughness or pitting can be felt, the bearing should be replaced. Here again, Hydrographic procedure is of damage to the authors do not appear to favour long-standing practice of replacing the cup bearing, although the simple and can be followed with absolutely no risk any component. Lubrication. - 72 - Again a self-explanatory text which requires little elaboration. There are numerous lubricating fluids which have proved most satisfactory in this regard, notably penetrating oils such as Penetrene, Three-in-One, Burrsthred etc. and, more recently, spray can products C.R.C., Formula 4 etc. which also dispel residual water and assist electrical efficiency. Spin Tests. Earlier papers provided by the makers, W. & L.E. Gurley, are recalled in which the practice of spin-testing meters is heartily condemned as pointless, indicative of nothing and damaging to the meter. The authors obviously do not agree, however it should be noted that later in this section they also describe the meter test recommended by Gurley in the papers referred to, i.e. by rotating the yoke and watching for movement in the bucket wheel. No opinion is therefore put forward on this matter, and the choice of test is left to individual operators. Routine Cleaning and Oiling of Current Meters. This section is quite comprehensive and contains much useful information that should be noted and observed. General Bearing wear both above and below the bucket wheel is promoted by the undesirable practice of allowing the wheel to spin freely in the wind. There are two reasons (a) the "wear per rev" rate of any bearing increases as the rotation rate increases, and (b) the effective weight of the wheel assembly in such a situation is greater than when immersed, as it lacks the buoyancy effect produced by immersion, thus the load on the lower bearings, normally many tonnes/sq. cm., is increased. Do not allow the meter to spin uncontrolled during a pause in the measurement. Lower it into the water or lay it gently on its side. Apart from the obvious indications of shaft bearing wear, other signs are (a) uneven signal duration or missed signal impulses, and (b) a buzzing or vibration when the meter is spun briefly. The effect of this wear on the rating can be minimised by keeping the bearing well lubricated until repairs can be done. NEVER dump the meter assembly on the ground or subject it to any other form of suddenly arrested downward motion. See note above re. phenomenal load which normally exists at the support point, then imagine how many times that load will be multiplied by any such treatment. - 73 - REFERENCES W.M.O. Manual on Stream Gauging HERSCHY, R.W. Streamflow Measurement I.S.O. 748 Liquid Flow Measurement in Open Channels I.S.O. 100 Establishment and Operation of a Gauging Station PUBLIC ORKS DEPARTMENT, Measurement and Rating W.A. Bulletin No. 1 Discharge U.S.G.S. Calibration and Maintenance of Vertical - Axis Type Current Meters OTT. Bulletin No. HLe 120/4 - OTT C31 Current Meter HYDROLOGICAL SERVICES. Instruction Manual - OSS Meter. - 74 - B1 Current