ASV111.1111 KMSTP110/001 Proposed wiring diagram for SA with 3-phase AC motor CLOSED Limit seating OPEN Limit seating Basic equipment KMSTP110/001 Limit switch tripping CLOSED OPEN DSR DOEL WSR WOEL Travel Contacts open Contacts closed DSR and DOEL act as overload protection for the whole travel; they are only tripped when exceeding the set torque. CLOSED Wiring diagram for standard version, multi-turn actuator closes valve clockwise. The wiring diagram shows the non-rotating multi-turn actuator in intermediate position. M S1 S2 S3 S4 S5 F1 Q1 S8 S9 S 10 K 1, K 2 F2-F5 H1 H2 H3 R1 DSR DOEL WSR WOEL BL TH H Motor (3-phase AC) Torque switch, closing, clockwise Torque switch, opening, counterclockwise Limit switch, closing, clockwise Limit switch, opening, counterclockwise Blinker transmitter Thermoswitch Main switch Push button STOP Push button CLOSE Push button OPEN Reversing contactors Fuses Indication light end position CLOSED Indication light end position OPEN Indication light FAULT Heater We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document. 1/2 Issue 1.08 Y001.931/002/en ASV111.1121 KMSTP110/001 Proposed wiring diagram for SA with 3-phase AC motor CLOSED Torque seating OPEN Limit seating Basic equipment KMSTP110/001 Limit switch tripping CLOSED OPEN DSR DOEL WSR WOEL Travel Contacts closed Contacts open DSR and DOEL act as overload protection for the whole travel. DSR interrupts the control circuit when reaching the set torque, the actuator is tripped. Set WSR as to ensure that it is tripped shortly before reaching the end position CLOSED. CLOSED Wiring diagram for standard version, multi-turn actuator closes valve clockwise. The wiring diagram shows the non-rotating multi-turn actuator in intermediate position. M S1 S2 S3 S4 S5 F1 Q1 S8 S9 S 10 K 1, K 2 F2-F5 H1 H2 H3 R1 DSR DOEL WSR WOEL BL TH H Motor (3-phase AC) Torque switch, closing, clockwise Torque switch, opening, counterclockwise Limit switch, closing, clockwise Limit switch, opening, counterclockwise Blinker transmitter Thermoswitch Main switch Push button STOP Push button CLOSE Push button OPEN Reversing contactors Fuses Indication light end position CLOSED Indication light end position OPEN Indication light FAULT Heater We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document. 2/2 Issue 1.08 Y001.931/002/en