POWER YOUR MINE WITH TF Kable MINING CABLES AUSTRALIA Table of Contents rUBBER CABLES 2 TELE-FONIKA Kable 3 PRODUCTION POTENTIAL 5 PRODUCTION MATRIX 6 GENERAL UNDERGROUND COAL MINING CABLES 1 TYPE 209 1.1/11 kV TYPE 210 1.1/1.1 kV TYPE 275 1.1/1.1 kV TYPE 240 1.1/11 kV TYPE 241 1.1/11 kV UNDERGROUND METAL AND SURFACE MINING CABLES 10 13 15 17 20 TYPE 409 1.1/22 kV TYPE 440 1.1/22 kV TYPE 441 1.1/22 kV TYPE 450 3.3/33 kV TYPE 455 3.3/33 kV MACHINE CABLES 25 28 31 34 37 TYPE 1 1.1/1.1 kV TYPE 2S (IS) 1.2 kV TYPE XLPE SWA PVC 0.6/1 kV heavy duty industrial cables 42 44 52 TYPE EMV 0.6/1 kV TYPE SINGLE CONDUCTOR POWER CABLE 0.6/1 kV, 1100C TYPE H07RN-F 450/750 V SUB TYPE NSGAFÖU 0.6/1, 1.8/3, 3.6/6 kV TYPE 07RN-F-CY 450/750 V TYPE NSGAFÖU/CY 1.8/3.3 kV CABLE DRUMS 56 58 60 65 68 70 Sample data of wooden cable drums 71 PRINCIPAL ELASTOMERIC MATERIALS USED IN REELING AND TRAILING CABLES 72 RECOMMENDED LIMITS TO REELING AND TRAILING CABLE OPERATION 74 RUBBER cables TELE-FONIKA Kable is known as the Number One cable producer in Central and Eastern Europe and is recognised as the leader in rubber cable products. TF Kable has over a dozen rubber production lines, with triple head continuous vulcanization extruding machines, twisters, braiders, amongst other plant to call upon. With our state-of-art instrumentation, which continuously monitor and control the production processes, we can be assured that our products are of the highest standards and quality. TF Kable offers wide range of rubber cables, starting from nominal voltage of 100/100V up to 18/30kV and cross-sections from 0,75 mm2 up to 1000 mm2 and from 1 up to 56 cores. TF Kable manufacture cables to national harmonized standards such as DIN VDE (German), BS (British), ICEA i ASTM (American), CSA (Canadian), AS/NZ (Australian/New), NF C (French), SANS (South African), GOST (Russian), to name but a few. Rubber compounds used for manufacturing of rubber insulated and sheathed cables are based on the best synthetic elastomers the market can offer, including EPDM, EVA, SBR and Silicone. Depending on type and application, our rubber insulation compounds will guarantee continuous working temperatures from 60°C through 110°C up to 220°C. For other cables components production, TF Kable uses the following types of rubber compounds: chloroprene, chlorinated polyethylene, chlorosulfonated polyethylene and others, depending on application. 2 Many years of experience in cable production and processing, has allowed TF Kable to develop bespoke materials that meet the demanding installation environments. Cables working in hard conditions such as mines, have specialised polyurethane sheaths which are flame retardant, rending, tear and abrasion resistant, water, oils and other chemicals resistant. Cables are designed and manufactured to ensure the longest and the safest operation in heavy duty conditions in today’s mines and other demanding environments. TELE-FONIKA Kable The Group TELE-FONIKA Kable (TF Kable) is ranked in the forefront of the global cable industry. The Group is the third manufacturer of cables and wires in Europe with significant development potential, based entirely on Polish capital. TELE-FONIKA Kable Group’s considerable investment in research and development centers and multiskilled work teams, which have included eminent scientists working with our specialists, has been rewarded by the introduction of new-generation products and comprehensive services in the field of cable engineering. Products manufactured in our plants are sold in over 90 countries. Our product assortment includes 25 thousand cable types. The highest quality of our products is confirmed by over 460 certificates for groups of wares licensed by 34 renown centres of certifications worldwide. The company combines the good traditions of the cable industry in Poland and innovative technical solutions. TELE-FONIKA Kable Group consists of seven plants — five in Poland, one in Ukraine, and one in Serbia. We own over a dozen trade agencies abroad, reaching customers in several dozen countries around the world. TF Nordic Malmoe TELE-FONIKA Kable Central Europe Hilden TELE-FONIKA Cable Americas Bolingbrook IL TELE-FONIKA Kable Kraków, Bydgoszcz, Szczecin, Myślenice TELE-FONIKA Baltic Kaunas Copper Cable Co. Coalville TOW TF KABEL Chernihiv TF KABEL Kiev 3 TELE-FONIKA France Longvic TELE-FONIKA Kabely Zabreh TF KABLE FK Zajecar Serbia Experience and innovation PRODUCTION POTENTIAL Our chief asset is extensive technological know-how in the field of production of wide variety of cables and wires supported by our experienced personnel. Our products match to a great extent the general trends concerning ecology and maintenance safety of wares. Extremely strict legislation in these areas has become the indicator of the technological progress of the manufactured cables. Kraków-Wielicka Plant Kraków-Wielicka Plant was established in 1928. In 1992 it received the ISO 9002 certificate (now ISO 9001) and in 1998 the ISO 14001 given by the British certification body: BASEC. The plant specializes in the production of rubber insulated cables and wires for mining and industrial applications. All types of rubber mixes used for EPR, CR, EVA and CSP cables are based on an original prescription designed together with research and development centres. The production offer of the plant are also medium voltage cables made in XLPE technology, as well as signal and control wires for special purposes. Kraków-Bieżanów Plant Kraków-Bieżanów Plant was established in 2001. In 1992 it received the ISO 9001 certificate and 14001 given by the British certification body: BASEC. The plant specializes in the production of overhead conductors from alloyed aluminium, conductors for railway traction network from copper and its alloys and installation wires for general usage. 5 Bydgoszcz Plant Bydgoszcz Plant started production of cables and wires back in 1923. In 1992 it received the ISO 9002 certificate (now ISO 9001) and in 1998 the ISO 14001 given by the British certification body: BASEC. Bydgoszcz Plant specializes in power supply cables of medium and high voltage up to 400 kV. It is equipped with six modern chain lines for crosslinking polyethylene in XLPE technology. Complementary technological lines for producing the abovementioned cables ranging from thick wire drawing machines, cable stranding machines and screening machines to covering lines and two large-size high voltage laboratories called “Faraday cage” place the plant in the top of the list of the largest production centres of medium and high voltage cables in Europe. Myślenice Plant Myślenice Plant was established in April 1992 under the name Zakłady Kablowe TELE-FONIKA s.c. In 1995 it received the ISO 9001 certificate and in 1999 the ISO 14001 certificate. The certification body is BASEC. In September 2007 the plant received the ISO/TS 16949 certificate for automotive cables given by the certification body: SGS. Myślenice Plant specializes in the production of copper and fibre optic telecommunication cables, computer cables and automotive wires. Szczecin Plant Szczecin Plant was established in 1958. In 1992 it received the ISO 9002 certificate (now ISO 9001) and in 1998 the ISO 14001 given by the British certification body: BASEC. This Plant is also certified according to ISO/TS 16949 by SGS. It specializes in production of enamelled magnet wires. TOW TF Kabel (Ukraine) The plant was established in 2002. In 2007 the plant was joined into the TELE-FONIKA Kable Group. This Plant is certified according to ISO 9001 and 14001. It specializes in the production of overhead conductors and cables for voltage up to 1 kV, including halogenfree, fire resistant and flame retardant cables versions. TF Kable Fabrika Kablova Zajecar A.D. (Serbia) The plant was established in 1974. In 2007 the plant was joined into the TELE-FONIKA Kable Group. This plant is certified according to ISO 9001 and 14001 by DAS Certification Ltd. It specializes in the production of low and medium voltage cables, as well as halogen-free, fire resistant and flame retardant cables, telecommunication cables and PVC and polyethylenecoated conductors. PRODUCT MATRIX 6 Cable Type 209 210 275 240 241 409 Voltage-Range 1.1kV - 11kV 1.1kV 1.1kV 1.1kV - 11kV 1.1kV - 11kV 1.1kV - 22kV Conductor-Range 6 mm2 - 300 mm2 1.5 mm2 - 2.5 mm2 16 mm2 - 50 mm2 6 mm2 - 300 mm2 6 mm2 - 300 mm2 6 mm2 - 300 mm2 Conductor - Number 3 3 3 3 3 3 Conductor - Copper Tinned Tinned Tinned Tinned Tinned Tinned Conductor - Screen Semi-conductive Semi-conductive - Semi-conductive Semi-conductive Semi-conductive Insulation - Type EPR R-EP-90 EPR R-EP-90 EPR R-EP-90 EPR R-EP-90 EPR R-EP-90 EPR R-EP-90 Insulation - Screen 1 Semi-conductive Semi-conductive - Semi-conductive Semi-conductive Semi-conductive Insulation - Screen 2 CU braid/poly yarn CU braid/poly yarn - CU braid/poly yarn - CU braid/poly yarn Pilot Conductor - Type EPR central EPR central EPR central EPR interstitial EPR central EPR central Pilot Conductor Number 1 1 1 3 1 1 Earth Conductor - Type - - Elastometric interstitial - Elastometric interstitial - Earth Conductor Number - - 3 - 3 - Separators/Fillers/ Sheath Cradle separator Cradle separator Cradle separator Cradle separator Cradle separator Cradle separator Reinforcing Strength Members/Armour - - Polyamid braid yarn - Polyamid braid yarn - Jacket/Outer Sheath HD-85-PCP HD-85-PCP HD-90-CSP HD-85-PCP HD-90-CSP HD-85-PCP Core ID Red, White, Blue Red, White, Blue Red, White, Blue Red, White, Blue Red, White, Blue Red, White, Blue Applications Flexible feeder to machinery Hand held boring machines and srills Shuttle cars and pump applications General purposes Main feeder, mine power, pump applications General purposes underground metal and surface mining PRODUCT MATRIX 7 440 441 450 455 1 2S XLPE SWA PVC 1.1kV - 22kV 1.1kV - 22kV 3.3kV - 33kV 3.3kV - 33kV 1.1kV 1.1kV 0.6kV - 1.2kV 6 mm2 - 240 mm2 6 mm2 - 300 mm2 16 mm2 - 240 mm2 16 mm2 - 300 mm2 2.5 mm2 - 4 mm2 1.5 mm2 - 95 mm2 1.5 mm2 - 300 mm2 3 3 3 3 3 2 - 6 (16, 30) 2-4 Tinned Tinned Tinned Tinned Tinned Tinned Tinned Semi-conductive Semi-conductive Semi-conductive Semi-conductive - - - EPR R-EP-90 EPR XR-EP-90 EPR XR-EP-90 EPR XR-EP-90 V-90 (PVC) EPR R-EP-90 XLPE-90 Semi-conductive Semi-conductive Semi-conductive Semi-conductive Collective Collective/individually - CU braid/poly yarn - CU braid/poly yarn - Tinned copper braid CU braid/poly yarn - EPR interstitial EPR central EPR interstitial EPR interstitial - EPR interstitial - 3 1 1 1 - 3 - - Elastometric interstitial Elastometric interstitial Elastometric interstitial - - Interstitial XLPE - 3 2 2 - - 1 Cradle separator Cradle separator Center filler Center filler Non-hygroscopic fillers Center filler Inner sheath 5V-90 (PVC) - Polyamid braid yarn Polyamid braid yarn Polyamid braid yarn - - GSW hellical serve armour HD-85-PCP HD-90-CSP HD-85-PCP XHD-90-CSP 5V-90 (PVC) HD-90-CPE 5-V90 (PVC) Red, White, Blue 1 one, 2 two, 3 three Red, White, Blue Red, White, Blue 1 one, 2 two, 3 three 2 one, 2 two, 3 three Red, Black, Green/Yellow Power to machinery and equipment Trailing draglines, shovels, drills, reeling applications Trailing draglines, shovels, drills, reeling applications Stacker/reclamation Non-mobile machines and fixed apparatus Non-mobile machines and fixed apparatus Power networks, outdoors, underground and conduit Coal mining our future GENERAL UNDERGROUND COAL MINING Type 209 Copper Screened Three-core Cables Central Pilot Core Flexible Feeder to Machinery / Hand Held Tools Type 210 Copper Screened Three-core Cables Central Pilot Core Hand Held Boring Machines and Drills Type 275 Three-core Cables Central Pilot Core Interstitial Earth Conductors General Use, Shuttle Cars and Pump Cable Type 240 Copper Screened Three-core Cables Interstitial Pilot Conductors Mine Power / Main Feeder / Long Wall 9 Type 241 Three-core Cables Central Pilot Core Interstitial Earth Conductors Mine Power / Main Feeder / Continuous Miners / Pump Applications TYPE 209 1.1/11 kV TRAILING CABLES Type 209 1.1/11 kV Copper Screened Three-core Cables, Central Pilot Core Flexible Feeder to Machinery General Underground Coal Mining Construction Conductors Tinned annealed copper wires to AS/NZS 1125:2001 and AS/NZS 1802:2003 Conductor screen Semi-conductive thermosetting compound Insulation Ethylene propylene rubber R-EP-90 to AS/NZS 3808 Insulation screen Semi-conductive thermosetting compound and tinned copper/polyamide braid to AS/NZS 1802:2003 Cradle separator Semi-conductive thermosetting compound and EPR covered Pilot Core (grey) to AS/NZS 1802:2003 Cable assembly Three screened power conductors laid up with right hand direction on cradle separator with central pilot conductor Jacket Thermosetting compound HD-85-PCP heavy duty oil resistant and flame retardant Operating temp Minimum ambient temperature -25˚C Maximum conductor temperature + 90˚C Cable tests AS/NZS 1802:2003 Marking Type of cable, size, manufacturer, year Core ID Red, White, Blue FEATURES Crush resistant central cradle construction 10 Flexible EPR insulation Short circuit cafety - screened conductors/semi-conductive cradle Heavy duty jacket Oil resistant/flame retardant Rated -25˚C to +90˚C Specifications & Standards: AS/NZS 1802:2003, AS/NZS 1125:2001 TYPE 209.1 1.1/1.1 kV Power conductor Product code Core screen Nominal diam. over insulation Size Area of each screen Sheath thickness Nominal overall diameter Approx mass Nominal area Strand size Insulation thickness mm2 n/mm mm mm n/mm mm2 mm mm kg/100 m TF-20901-006 6 84/0.30 1.5 6.5 7/0.25 7.2 3.8 30.0 129 TF-20901-010 10 77/0.40 1.5 7.7 7/0.25 8.6 3.8 32.6 157 TF-20901-016 16 126/0.40 1.6 9.0 7/0.25 9.6 4.0 35.8 197 TF-20901-025 25 209/0.40 1.6 10.5 7/0.25 11.3 4.3 39.7 255 TF-20901-035 35 285/0.40 1.6 12.1 7/0.25 12.4 4.6 43.8 312 TF-20901-050 50 380/0.40 1.7 13.8 7/0.25 14.4 5.0 48.4 386 TF-20901-070 70 361/0.50 1.8 16.1 7/0.25 16.5 5.4 54.0 503 TF-20901-095 95 475/0.50 2.0 17.7 7/0.25 18.2 6.0 58.8 605 TF-20901-120 120 608/0.50 2.1 20.0 7/0.25 20.3 6.4 64.6 741 TF-20901-150 150 740/0.50 2.3 22.2 7/0.25 22.3 6.9 70.3 896 TF-20901-185 185 925/0.50 2.5 24.7 7/0.30 30.2 7.4 77.5 1092 TF-20901-240 240 1221/0.50 2.8 27.9 7/0.30 33.6 8.2 86.1 1365 TF-20901-300 300 1525/0.50 3.0 31.0 7/0.40 50.1 8.8 95.2 1715 Sheath thickness Nominal overall diameter Approx mass TYPE 209.3 3.3/3.3 kV Power conductor Product code 11 Core screen Nominal area Strand size Insulation thickness mm2 n/mm mm TF-20903-015 16 126/0.40 12.6 7/0.25 13.4 5.3 46.7 301 TF-20903-025 25 209/0.40 14.1 7/0.25 14.8 5.6 50.6 369 TF-20903-035 35 285/0.40 15.4 7/0.25 15.1 5.9 54.0 431 TF-20903-050 50 380/0.40 16.9 7/0.25 17.5 6.3 58.1 507 TF-20903-070 70 361/0.50 18.9 7/0.25 19.6 6.6 63.0 624 TF-20903-095 95 475/0.50 20.1 7/0.25 20.6 7.1 66.7 719 TF-20903-120 120 608/0.50 22.2 7/0.30 27.2 7.4 72.6 876 TF-20903-150 150 740/0.50 24.0 7/0.40 39.6 7.8 78.6 1072 TF-20903-185 185 925/0.50 26.1 7/0.40 43.1 8.2 83.8 1236 TF-20903-240 240 1221/0.50 28.7 7/0.40 46.6 8.8 90.8 1484 3.0 Nominal diam. over insulation Size Area of each screen mm n/mm mm2 mm mm kg/100 m TYPE 209.6 6.6/6.6 kV Power conductor Product code Core screen Sheath thickness Nominal overall diameter Approx mass Nominal area Strand size Insulation thickness mm2 n/mm mm TF-20906-006 16 126/0.40 16.6 7/0.25 17.2 6.4 57.9 435 TF-20906-010 25 209/0.40 18.1 7/0.25 18.9 6.7 61.7 512 TF-20906-016 35 285/0.40 19.4 7/0.25 19.9 7.0 65.2 582 TF-20906-025 50 380/0.40 20.9 7/0.25 21.6 7.3 69.0 668 TF-20906-035 70 361/0.50 22.9 7/0.25 23.4 7.7 74.3 799 TF-20906-050 95 475/0.50 24.1 7/0.25 29.7 8.1 78.3 876 TF-20906-070 120 608/0.50 25.2 7/0.30 32.2 8.5 83.5 1072 TF-20906-095 150 740/0.50 28.0 7/0.30 45.7 8.9 89.5 1290 TF-20906-120 185 925/0.50 30.1 7/0.40 49.3 9.3 95.1 1466 TF-20906-150 240 1221/0.50 32.7 7/0.40 52.8 9.9 101.8 1733 Sheath thickness Nominal overall diameter Approx mass 5.0 Nominal diam. over insulation Size Area of each screen mm n/mm mm2 mm mm kg/100 m TYPE 209.11 11/11 kV Power conductor Product code 12 Core screen Nominal area Strand size Insulation thickness Nominal diam. over insulation Size Area of each screen mm2 n/mm mm mm n/mm mm2 mm mm kg/100 m TF-20911-025 25 209/0.40 23.5 7/0.25 24.1 8.1 76.0 742 TF-20911-035 35 285/0.40 24.8 7/0.30 30.2 8.4 80.1 847 TF-20911-050 50 380/0.40 26.2 7/0.30 32.2 8.7 84.0 943 TF-20911-070 70 361/0.50 28.2 7/0.30 34.6 9.1 89.1 1093 TF-20911-095 95 475/0.50 29.5 7/0.40 48.4 9.6 94.1 1267 TF-20911-120 120 608/0.50 31.5 7/0.40 51.0 9.9 99.9 1436 TF-20911-150 150 740/0.50 33.3 7/0.40 54.5 10.3 104.0 1614 7.6 TYPE 210 1.1/1.1 kV TRAILING CABLES Type 210 1.1/11 kV Copper Screened Three-core Cables, Central Pilot Core Hand Held Boring Machines and Drills General Underground Coal Mining Construction Conductors Tinned annealed copper wires to AS/NZS 1125:2001 and AS/NZS 1802:2003 Conductor screen Semi-conductive thermosetting compound Insulation Ethylene propylene rubber R-EP-90 to AS/NZS 3808 Insulation screen Semi-conductive thermosetting compound and tinned copper/polyamide braid to AS/NZS 1802:2003 Cradle separator Semi-conductive thermosetting compound and EPR covered Pilot Core (grey) to AS/NZS 1802:2003 Cable assembly Three screened power conductors laid up with right hand direction on cradle separator with central pilot conductor Jacket Thermosetting compound HD-85-PCP heavy duty oil resistant and flame retardant Operating temp Minimum ambient temperature -25˚C Maximum conductor temperature + 90˚C Cable tests AS/NZS 1802:2003 Marking Type of cable, size, manufacturer, year Core ID Red, White, Blue FEATURES Crush resistant central cradle construction 13 Flexible EPR insulation Short circuit safety - screened conductors/semi-conductive cradle Heavy duty jacket Oil resistant/flame retardant Rated -25˚C to +90˚C Specifications & Standards: AS/NZS 1802:2003, AS/NZS 1125:2001 TYPE 210.1 Power conductor Product code 14 Core screen Nominal area Strand size Insulation thickness Nominal diam. over insulation Size Area of each screen mm2 n/mm mm mm n/mm mm2 TF-21001-001.5 1.5 30/0.25 1.4 4.4 TF-21001-002.5 2.5 50/0.25 1.5 5.0 7/0.25 5.2 Sheath thickness Nominal overall diameter Approx mass mm mm kg/100 m 23.2 76 23.6 88 3.0 TYPE 275 1.1/1.1 kV REELING AND TRAILING CABLES Type 275 1.1/1.1 kV Three-core Cables, Central Pilot Core Three Interstitial Earth Conductors Shuttle Cars and Pump Applications General Underground Coal Mining Construction 15 Conductors Tinned annealed copper wires to AS/NZS 1125:2001 and AS/NZS 1802:2003 Separator Synthetic tape under insulation Insulation Ethylene propylene rubber R-EP-90 AS/NZS 3808 Earth conductors Mechanically strong earth conductors with semi-conductive elastomeric covering Cradle separator Semi-conductive thermosetting compound and EPR covered Pilot Core (grey) to AS/NZS 1802:2003 Cable assembly Three screened power conductors and three earth conductors (black) laid up with right hand direction on cradle separator with central pilot conductor Filling/covering Semi-conductive thermosetting compound to AS/NZS 1802:2003 tables 6 and 7 Reinforcing braid Polyamide yarns Jacket Thermosetting compound HD-90-CSP extra heavy duty oil resistant and flame retardant Operating temp Minimum ambient temperature -25˚C Maximum conductor temperature + 90˚C Cable tests AS/NZS 1802:2003 Marking Type of cable, size, manufacturer, year Core ID Red, (black), White, (black), Blue, (black) FEATURES Crush resistant central cradle construction Flexible EPR insulation Short circuit safety - screened conductors/semi-conductive cradle Reinforced radial - strengthened heavy duty jacket Oil resistant/flame retardant Rated -25˚C to +90˚C Specifications & Standards: AS/NZS 1802:2003, AS/NZS 1125:2001 TYPE 275.1 Power conductor Product code Strand size Insulation thickness Nominal diameter of wires Thickness of semi-conducting covering mm2 n/mm mm n/mm n/mm TF-27501-016 16 126/0.40 1.6 60/0.30 TF-27501-025 25 209/0.40 1.6 100/0.30 Nominal area 16 Earth conductor TF-27501-035 35 285/0.40 1.6 140/0.30 TF-27501-050 50 380/0.40 1.7 99/0.40 1.0 Sheath thickness Nominal overall diam. Approx mass mm mm kg/100 m 3.8 30.2 145 4.0 33.9 204 4.3 38.5 270 4.7 43.1 333 TYPE 240 1.1/11 kV TRAILING CABLES Type 240 1.1/11 kV Copper Screened Three-core Cables Three Interstitial Pilot Conductors General and Underground Coal Mining Construction 17 Conductors Tinned annealed copper wires to AS/NZS 1125:2001 and AS/NZS 1802:2003 Conductor screen Semi-conductive thermosetting compound Insulation Ethylene propylene rubber R-EP-90 to AS/NZS 3808 Insulation screen Semi-conductive thermosetting compound, tinned copper/polyamide braid to AS/NZS 1802:2003 Cradle separator Semi-conductive thermosetting compound comply to AS/NZS 1802:2003 Cable assembly Three screened power conductors and three EPR insulated (grey) and textile taped pilot conductors laid up with right hand direction on cradle separator Jacket Thermosetting compound HD-85-PCP heavy duty oil resistant and flame retardant Reinforcing braid Polyamide yarns Jacket Thermosetting compound HD-90-CSP extra heavy duty oil resistant and flame retardant Operating temp Minimum ambient temperature -25˚C Maximum conductor temperature + 90˚C Cable tests AS/NZS 1802:2003 Marking Type of cable, size, manufacturer, year Core ID Red, (grey), White, (grey), Blue, (grey) FEATURES Crush resistant central cradle construction Flexible EPR insulation Short circuit safety - screened conductors/semi-conductive cradle Heavy duty jacket Oil resistant/flame retardant Rated -25˚C to +90˚C Specifications & Standards: AS/NZS 1802:2003, AS/NZS 1125:2001 TYPE 240.1 1.1/1.1 kV Power conductor Product code Core screen Nominal diam. over insulation Size Area of each screen Sheath thickness Nominal overall diameter Approx mass Nominal area Strand size Insulation thickness mm2 n/mm mm mm n/mm mm2 mm mm kg/100 m TF-24001-006 6 84/0.30 1.5 6.5 7/0.25 7.2 3.8 30.0 131 TF-24001-010 10 77/0.40 1.5 7.7 7/0.25 8.6 3.8 32.6 159 TF-24001-016 16 126/0.40 1.6 9.0 7/0.25 9.6 4.0 35.8 202 TF-24001-025 25 209/0.40 1.6 10.5 7/0.25 11.3 4.3 39.7 265 TF-24001-035 35 285/0.40 1.6 12.1 7/0.25 12.4 4.6 43.8 326 TF-24001-050 50 380/0.40 1.7 13.8 7/0.25 14.4 5.0 48.4 404 TF-24001-070 70 361/0.50 1.8 16.1 7/0.25 16.5 5.4 54.0 533 TF-24001-095 95 475/0.50 2.0 17.7 7/0.25 18.2 6.0 58.8 635 TF-24001-120 120 608/0.50 2.1 20.0 7/0.25 20.3 6.4 64.6 775 TF-24001-150 150 740/0.50 2.3 22.2 7/0.25 22.3 6.9 70.3 940 TF-24001-185 185 925/0.50 2.5 24.7 7/0.30 30.2 7.4 77.5 1140 TF-24001-240 240 1221/0.50 2.8 27.9 7/0.30 33.6 8.2 86.1 1410 TF-24001-300 300 1525/0.50 3.0 30.9 7/0.40 50.1 8.8 95.2 1775 Sheath thickness Nominal overall diameter Approx mass TYPE 240.3 3.3/3.3 kV Power conductor Product code 18 Core screen Nominal area Strand size Insulation thickness Nominal diam. over insulation Size Area of each screen mm2 n/mm mm mm n/mm mm2 mm mm kg/100 m TF-24003-016 16 126/0.40 12.6 7/0.25 13.4 5.3 46.7 306 TF-24003-025 25 209/0.40 14.1 7/0.25 14.8 5.6 50.6 379 TF-24003-035 35 285/0.40 15.4 7/0.25 15.1 5.9 54.0 444 TF-24003-050 50 380/0.40 16.9 7/0.25 17.5 6.3 58.1 525 TF-24003-070 70 361/0.50 18.9 7/0.25 19.6 6.6 63.0 656 TF-24003-095 95 475/0.50 20.1 7/0.25 20.6 7.1 66.7 750 TF-24003-120 120 608/0.50 22.2 7/0.30 27.2 7.4 72.6 910 TF-24003-150 150 740/0.50 24.0 7/0.40 39.6 7.8 78.6 1115 TF-24003-185 185 925/0.50 26.1 7/0.40 43.1 8.2 83.8 1280 TF-24003-240 240 1221/0.50 28.7 7/0.40 46.6 8.8 90.8 1540 3.0 TYPE 240.6 6.6/6.6 kV Power conductor Product code Core screen Size Area of each screen mm n/mm mm2 Nominal overall diameter Approx mass Nominal area Strand size Insulation thickness mm2 n/mm mm mm mm kg/100 m TF-24006-016 16 126/0.40 16.6 7/0.25 17.2 6.4 57.9 440 TF-24006-025 25 209/0.40 18.1 7/0.25 18.9 6.7 61.7 521 TF-24006-035 35 285/0.40 19.4 7/0.25 19.9 7.0 65.2 593 TF-24006-050 50 380/0.40 20.9 7/0.25 21.6 7.3 69.0 685 TF-24006-070 70 361/0.50 22.9 7/0.25 23.4 7.7 74.3 830 TF-24006-095 95 475/0.50 24.1 7/0.30 29.7 8.1 78.2 954 TF-24006-120 120 608/0.50 25.2 7/0.30 32.2 8.5 83.5 1111 TF-24006-150 150 740/0.50 28.0 7/0.40 45.7 8.9 89.5 1335 TF-24006-185 185 925/0.50 30.1 7/0.40 49.3 9.3 95.1 1515 TF-24006-240 240 1221/0.50 32.7 7/0.40 52.8 9.9 101.8 1788 Sheath thickness Nominal overall diameter Approx mass 5.0 Nominal diam. over insulation Sheath thickness TYPE 241.11 11/11 kV Power conductor Product code 19 Core screen Nominal area Strand size Insulation thickness Nominal diam. over insulation Size Area of each screen mm2 n/mm mm mm n/mm mm2 mm mm kg/100 m TF-24011-025 25 209/0.40 23.5 7/0.25 24.1 8.1 76.0 752 TF-24011-035 35 285/0.40 24.8 7/0.30 30.2 8.4 80.1 860 TF-24011-050 50 380/0.40 26.2 7/0.30 32.2 8.7 84.0 961 TF-24011-070 70 361/0.50 28.2 7/0.30 34.6 9.1 89.1 1125 TF-24011-095 95 475/0.50 29.5 7/0.40 48.4 9.6 94.1 1300 TF-24011-120 120 608/0.50 31.5 7/0.40 51.0 9.9 99.9 1470 TF-24011-150 150 740/0.50 33.3 7/0.40 54.5 10.3 104.0 1659 7.6 TYPE 241 1.1/11 kV REELING AND TRAILING CABLES Type 241 Class 1 1.1/11 kV Three-core Cables, Central Pilot Core Three Interstitial Earth Conductors Main Feeder/Mine Power/Pump Applications Construction 20 Conductors Tinned annealed copper wires to AS/NZS 1125:2001 and AS/NZS 1802:2003 Conductor screen Semi-conductive thermosetting compound Insulation Ethylene propylene rubber R-EP-90 to AS/NZS 3808 Insulation screen Semi-conductive thermosetting compound to AS/NZS 1802:2003 Table 7 Earth conductors Mechanically strong earth conductors with semi-conductive elastomeric covering Cradle separator Semi-conductive thermosetting compound and EPR covered Pilot Core (grey) to AS/NZS 1802:2003 Cable assembly Three screened power conductors and three earth conductors (black) laid up with right hand direction on cradle separator with central pilot conductor Filling/covering Semi-conductive thermosetting compound to AS/NZS 1802:2003 tables 6 and 7 Reinforcing braid Polyamide yarns Jacket Thermosetting compound HD-90-CSP extra heavy duty oil resistant and flame retardant Operating temp Minimum ambient temperature -25˚C Maximum conductor temperature + 90˚C Cable tests AS/NZS 1802:2003 Marking Type of cable, size, manufacturer, year Core ID Red, (black), White, (black), Blue, (black) FEATURES Crush resistant central cradle construction Flexible EPR insulation Short circuit safety - screened conductors/semi-conductive cradle Reinforced radial-strengthened heavy duty jacket Oil resistant/flame retardant Rated -25˚C to +90˚C Specifications & Standards: AS/NZS 1802:2003, AS/NZS 1125:2001 TYPE 241.1 Class 1 1.1/1.1 kV Power conductor Product code Earth conductor Strand size Thickness of semi-conducting covering Sheath thickness Nominal overall diam. Approx mass Nominal area Strand size Insulation thickness mm2 n/mm mm n/mm n/mm mm mm kg/100 m TF-24101-006 6 84/0.30 1.5 18/0.30 1.0 3.8 29.7 106 TF-24001-006 10 77/0.40 1.5 27/0.30 1.0 3.8 31.6 127 TF-24101-016 16 126/0.40 1.6 42/0.30 1.0 3.9 35.0 164 TF-24101-025 25 209/0.40 1.6 66/0.30 1.0 4.2 37.9 208 TF-24101-035 35 285/0.40 1.6 90/0.30 1.0 4.4 39.8 254 TF-24101-050 50 380/0.40 1.7 120/0.30 1.0 4.9 45.2 328 TF-24001-070 70 361/0.50 1.8 110/0.40 1.0 5.3 50.0 425 TF-24101-095 95 475/0.50 2.0 110/0.40 1.0 5.8 56.0 532 TF-24101-120 120 608/0.50 2.1 110/0.40 1.2 6.3 59.5 633 TF-24101-150 150 740/0.50 2.3 135/0.40 1.2 6.7 64.9 766 TF-24101-185 185 925/0.50 2.5 165/0.40 1.4 7.3 71.3 924 TF-24101-240 240 1221/0.50 2.8 216/0.40 1.4 8.0 76.6 1147 TF-24101-300 300 1525/0.50 3.0 275/0.40 1.4 8.7 86.4 1426 Sheath thickness Nominal overall diam. Approx mass TYPE 241.3 Class 1 3.3/3.3 kV Power conductor Product code 21 Earth conductor Nominal area Strand size Insulation thickness Strand size Thickness of semi-conducting covering mm2 n/mm mm mm n/mm mm mm kg/100 m TF-24103-016 16 126/0.40 42/0.30 1.0 5.0 44.0 249 TF-24103-025 25 209/0.40 66/0.30 1.0 5.3 47.9 315 TF-24103-035 35 285/0.40 90/0.30 1.0 5.6 51.3 376 TF-24103-050 50 380/0.40 120/0.30 1.0 6.0 55.4 450 TF-24103-070 70 361/0.50 110/0.40 1.0 6.4 60.7 576 TF-24103-095 95 475/0.50 135/0.40 1.0 6.8 64.1 675 3.0 TF-24103-120 120 608/0.50 165/0.40 1.2 7.2 69.2 810 TF-24103-150 150 740/0.50 216/0.40 1.2 7.6 74.0 952 TF-24103-185 185 925/0.50 252/0.40 1.4 8.0 79.3 1112 TF-24103-240 240 1221/0.50 324/0.40 1.4 8.6 86.1 1360 TF-24103-300 300 1525/0.50 259/0.50 1.4 9.1 92.7 1640 TYPE 241.6 Class 1 6.6/6.6 kV Power conductor Product code Earth conductor Sheath thickness Nominal overall diam. Approx mass mm mm kg/100 m 6.1 55.2 365 6.4 59.1 440 Strand size Insulation thickness Strand size Thickness of semi-conducting covering mm2 n/mm mm n/mm n/mm TF-24106-016-1 16 126/0.40 42/0.30 TF-24106-025-1 25 209/0.40 66/0.30 TF-24106-035-1 35 285/0.40 90/0.30 6.7 62.6 509 TF-24106-050-1 50 380/0.40 120/0.30 7.1 66.4 592 Nominal area TF-24106-070-1 70 361/0.50 TF-24106-095-1 95 475/0.50 7.4 71.3 727 7.9 75.0 835 TF-24106-120-1 120 608/0.50 165/0.40 8.3 80.3 990 TF-24106-150-1 150 TF-24106-185-1 185 740/0.50 216/0.40 8.6 84.8 1140 925/0.50 252/0.40 9.0 90.1 1311 TF-24106-240-1 240 1221/0.50 324/0.40 9.6 96.9 1576 Sheath thickness Nominal overall diam. Approx mass mm mm kg/100 m 5.0 110/0.40 1.4 135/0.40 TYPE 241.11 Class 1 11/11 kV Power conductor Product code 22 Earth conductor Nominal area Strand size Insulation thickness Strand size Thickness of semi-conducting covering mm2 n/mm mm mm n/mm TF-24111-025-1 25 209/0.40 66/0.3 7.8 73.4 645 TF-24111-035-1 35 285/0.40 90/0.30 8.1 76.7 724 TF-24111-050-1 50 380/0.40 120/0.30 8.5 80.7 825 TF-24111-070-1 70 361/0.50 TF-24111-095-1 95 475/0.50 8.9 85.9 975 9.3 89.2 1088 TF-24111-120-1 120 608/0.50 165/0.40 9.7 94.5 1258 TF-24111-150-1 150 TF-24111-185-1 185 740/0.50 216/0.40 10.0 99.0 1423 925/0.50 252/0.40 10.4 104.3 1610 7.6 110/0.40 135/0.40 1.8 Transforming the future mine UNDERGROUND METAL AND SURFACE MINING Type 409 Copper Screened Three-core Cables Central Pilot Core General Underground Metal / Surface Mining Type 440 Copper Screened Three-core Cables Interstitial Pilot Conductors Power to Machinery and Equipment Type 441 Three-core Cables Central Pilot Core / Interstitial Earth Conductors Trailing / Draglines / Shovels / Drills / Reeling Type450 Copper Screened Three-core Cables Two Earth and One Pilot Interstitial Conductors Dragline, Shovel, Drill Cable and Reeling 24 Type 455 Three-core Cables Two Earth and One Pilot Interstitial Conductors Stacker / Reclamation TYPE 409 1.1/22 kV TRAILING CABLES Type 409 Class 2 1.1/22 kV Copper Screened Three-core Cables, Central Pilot Core Underground Metal and Surface Mining Construction Conductors Tinned annealed copper wires to AS/NZS 1125:2001 and AS/NZS 2802:2000 Conductor screen Semi-conductive tape plus thermosetting compound Insulation Ethylene propylene rubber R-EP-90 to AS/NZS 3808 Insulation screen Semi-conductive thermosetting compound, tape, tinned copper/polyamide braid to AS/NZS 2802 12.4.1 Pilot core 1.5mm2 Cradle separator Semi-conductive thermosetting compound and EPR covered Pilot Core (grey) to AS/NZS 2802:2000 Cable assembly Three screened power conductors laid up with right hand direction on cradle separator with central pilot conductor Jacket Thermosetting compound HD-85-PCP heavy duty oil resistant and flame retardant Operating temp Minimum ambient temperature -25˚C Maximum conductor temperature + 90˚C Cable tests AS/NZS 2802:2000 Marking Type of cable, size, manufacturer, year Core ID Red, White, Blue FEATURES Crush resistant central cradle construction 25 Flexible EPR insulation Short circuit safety - screened conductors/semi-conductive cradle Heavy duty jacket Oil resistant/flame retardant Rated -25˚C to +90˚C Specifications & Standards: AS/NZS 2802:2000, AS/NZS 1125:2001 TYPE 409.1 Class 2 1.1/1.1 kV Power conductor Product code Core screen Nominal diam. over insulation Size Area of each screen Sheath thickness Nominal overall diameter Approx mass Nominal area Strand size Insulation thickness mm2 n/mm mm mm n/mm mm2 mm mm kg/100 m TF-40901-006-2 6 84/0.30 1.5 6.5 7/0.25 7.2 3.8 30.0 129 TF-40901-010-2 10 77/0.40 1.5 7.7 7/025 8.6 3.8 32.6 157 TF-40901-016-2 16 126/0.40 1.6 9.0 7/0.25 9.6 4.0 35.8 197 TF-40901-025-2 25 209/0.40 1.6 10.5 7/0.25 11.3 4.3 39.7 255 TF-40901-035-2 35 285/0.40 1.6 12.1 7/0.25 12.4 4.6 43.8 312 TF-40901-050-2 50 380/0.40 1.7 13.8 7/0.25 14.4 5.0 48.4 386 TF-40901-070-2 70 361/0.50 1.8 16.1 7/0.25 16.5 5.4 54.0 503 TF-40901-095-2 95 475/0.50 2.0 17.7 7/0.30 21.8 6.0 59.4 622 TF-40901-120-2 120 608/0.50 2.1 20.0 7/0.30 24.7 6.4 65.2 760 TF-40901-150-2 150 740/0.50 2.3 22.2 7/0.40 36.9 6.9 72.2 960 TF-40901-185-2 185 925/0.50 2.5 24.7 7/0.40 40.5 7.4 78.8 1139 TF-40901-240-2 240 1221/0.50 2.8 27.9 7/0.50 57.7 8.2 88.7 1465 TF-40901-300-2 300 1525/0.50 3.0 31.0 7/0.50 63.2 8.8 96.5 1790 Sheath thickness Nominal overall diameter Approx mass TYPE 409.3 Class 2 3.3/3.3 kV Power conductor Product code 26 Core screen Nominal area Strand size Insulation thickness Nominal diam. over insulation Size Area of each screen mm2 n/mm mm mm n/mm mm2 mm mm kg/100 m TF-40903-016-2 16 126/0.40 12.5 7/0.25 13.1 5.3 46.3 301 TF-40903-025-2 25 209/0.40 14.0 7/0.25 14.8 5.6 50.0 371 TF-40903-035-2 35 285/0.40 15.3 7/0.25 15.8 5.9 53.5 430 TF-40903-050-2 50 380/0.40 16.8 7/0.25 17.2 6.3 57.5 511 TF-40903-070-2 70 361/0.50 18.8 7/0.25 18.6 6.6 62.4 624 TF-40903-095-2 95 475/0.50 20.0 7/0.25 20.3 7.1 66.1 724 TF-40903-120-2 120 608/0.50 22.1 7/0.30 27.2 7.4 72.1 880 TF-40903-150-2 150 740/0.50 23.9 7/0.40 39.6 7.8 77.9 1079 TF-40903-185-2 185 925/0.50 26.0 7/0.40 42.2 8.2 83.5 1251 TF-40903-240-2 240 1221/0.50 28.6 7/0.40 46.6 8.8 90.3 1502 3.0 TYPE 409.6 Class 2 6.6/6.6 kV Power conductor Product code Core screen Size Area of each screen mm n/mm mm2 Nominal overall diameter Approx mass Nominal area Strand size Insulation thickness mm2 n/mm mm mm mm kg/100 m TF-40906-016-2 16 126/0.40 16.5 7/0.25 17.2 6.4 57.3 440 TF-40906-025-2 25 209/0.40 18.0 7/0.25 18.6 6.7 61.2 516 TF-40906-035-2 35 285/0.40 19.3 7/0.25 18.6 7.0 64.6 584 TF-40906-050-2 50 380/0.40 20.8 7/0.25 21.3 7.3 68.5 669 TF-40906-070-2 70 361/0.50 22.8 7/0.25 23.4 7.7 73.7 804 TF-40906-095-2 95 475/0.50 24.0 7/0.25 29.2 8.1 77.8 934 TF-40906-120-2 120 608/0.50 26.1 7/0.30 31.7 8.5 83.1 1090 TF-40906-150-2 150 740/0.50 27.9 7/0.40 45.7 8.9 89.1 1310 TF-40906-185-2 185 925/0.50 30.0 7/0.40 48.4 9.3 94.5 1479 TF-40906-240-2 240 1221/0.50 32.6 7/0.40 52.8 9.9 101.4 1749 Sheath thickness Nominal overall diameter Approx mass 5.0 Nominal diam. over insulation Sheath thickness TYPE 409.11 Class 2 11/11 kV Power conductor Product code Core screen Nominal area Strand size Insulation thickness Nominal diam. over insulation Size Area of each screen mm2 n/mm mm mm n/mm mm2 mm mm kg/100 m TF-40911-025-2 25 209/0.40 23.4 7/0.25 23.7 8.1 75.6 750 TF-40911-035-2 35 285/0.40 24.7 7/0.30 30.2 8.4 79.6 859 TF-40911-050-2 50 380/0.40 26.2 7/0.30 31.7 8.7 83.5 954 TF-40911-070-2 70 361/0.50 28.2 7/0.30 34.1 9.1 88.7 1105 TF-40911-095-2 95 475/0.50 29.4 7/0.40 47.5 9.6 93.6 1290 TF-40911-120-2 120 608/0.50 31.5 7/0.40 51.0 9.9 98.7 1460 TF-40911-150-2 150 740/0.50 33.3 7/0.40 53.7 10.3 103.4 1636 Sheath thickness Nominal overall diameter Approx mass 7.6 TYPE 409.22 Class 2 22/22 kV Power conductor Product code Nominal area Strand size Insulation thickness mm2 n/mm mm TF-40922-035-2 35 285/0.40 TF-40922-050-2 50 380/0.40 27 10.5 Core screen Nominal diam. over insulation Size Area of each screen mm n/mm mm2 mm mm kg/100 m 55.4 10.0 105.0 1405 58.1 10.3 108.8 1525 32.6 34.1 7/0.40 TYPE 440 1.1/22 kV TRAILING CABLES Type 440 Class 2 1.1/22 kV Copper Screened Three-core Cables Three Interstitial Pilot Conductors Power to Machinery and Equipment Applications Construction Conductors Tinned annealed copper wires to AS/NZS 1125:2001 and AS/NZS 2802:2000 Conductor screen Semi-conductive thermosetting compound Insulation Ethylene propylene rubber R-EP-90 to AS/NZS 3808 Insulation screen Semi-conductive thermosetting compound, tinned copper/polyamide braid to AS/NZS 2802:2000 Cradle separator Semi-conductive thermosetting compound comply to AS/NZS 2802:2000 Cable assembly Three screened power conductors and three EPR insulated (grey) and textile taped pilot conductors laid up with right hand direction on cradle separator Jacket Thermosetting compound HD-85-PCP heavy duty oil resistant and flame retardant Operating temp Minimum ambient temperature -25˚C Maximum conductor temperature + 90˚C Cable tests AS/NZS 2802:2000 Marking Type of cable, size, manufacturer, year Core ID Red, (grey), White, (grey), Blue, (grey) FEATURES Crush resistant central cradle construction 28 Flexible EPR insulation Short circuit safety - screened conductors/semi-conductive cradle Heavy duty jacket Oil resistant/flame retardant Rated -25˚C to +90˚C Specifications & Standards: AS/NZS 2802:2000, AS/NZS 1125:2001 TYPE 440.1 Class 2 1.1/1.1 kV Power conductor Product code Core screen Nominal diam. over insulation Size Area of each screen Sheath thickness Nominal overall diameter Approx mass Nominal area Strand size Insulation thickness mm2 n/mm mm mm n/mm mm2 mm mm kg/100 m TF-44001-006-2 6 84/0.30 1.5 6.5 7/0.25 7.2 3.8 30.0 135 TF-44001-010-2 10 77/0.40 1.5 7.7 7/0.25 8.6 3.8 32.6 166 TF-44001-016-2 16 126/0.40 1.6 9.0 7/0.25 9.6 4.0 35.8 204 TF-44001-025-2 25 209/0.40 1.6 10.5 7/0.25 11.3 4.3 39.7 269 TF-44001-035-2 35 285/0.40 1.6 12.1 7/0.25 12.4 4.6 43.8 324 TF-44001-050-2 50 380/0.40 1.7 13.8 7/0.25 14.4 5.0 48.4 403 TF-44001-070-2 70 361/0.50 1.8 16.1 7/0.25 16.5 5.4 54.0 539 TF-44001-095-2 95 475/0.50 2.0 17.7 7/0.30 21.8 6.0 59.4 659 TF-44001-120-2 120 608/0.50 2.1 20.0 7/0.30 24.7 6.4 65.2 802 TF-44001-150-2 150 740/0.50 2.3 22.2 7/0.40 36.9 6.9 72.2 1018 TF-44001-185-2 185 925/0.50 2.5 24.7 7/0.40 40.5 7.4 78.8 1198 TF-44001-240-2 240 1221/0.50 2.8 27.9 7/0.50 57.7 8.2 88.7 1549 Sheath thickness Nominal overall diameter Approx mass TYPE 440.3 Class 2 3.3/3.3 kV Power conductor Product code 29 Core screen Nominal area Strand size Insulation thickness Nominal diam. over insulation Size Area of each screen mm2 n/mm mm mm n/mm mm2 mm mm kg/100 m TF-44003-016-2 16 126/0.40 12.5 7/0.25 13.1 5.3 46.1 304 TF-44003-025-2 25 209/0.40 14.0 7/0.25 14.8 5.6 50.0 379 TF-44003-035-2 35 285/0.40 15.3 7/0.25 15.8 5.9 53.4 446 TF-44003-050-2 50 380/0.40 16.8 7/0.25 17.2 6.3 57.5 524 TF-44003-070-2 70 361/0.50 20.0 7/0.25 18.6 6.6 62.4 659 TF-44003-095-2 95 475/0.50 22.1 7/0.25 20.3 7.1 66.2 754 TF-44003-120-2 120 608/0.50 23.9 7/0.30 27.2 7.4 71.9 914 TF-44003-150-2 150 740/0.50 26.0 7/0.40 39.6 7.8 79.9 1119 TF-44003-185-2 185 925/0.50 28.6 7/0.40 42.2 8.2 83.4 1289 TF-44003-240-2 240 1221/0.50 31.2 7/0.40 46.6 8.8 90.2 1559 3.0 TYPE 440.6 Class 2 6.6/6.6 kV Power conductor Product code Core screen Size Area of each screen mm n/mm mm2 Nominal overall diameter Approx mass Nominal area Strand size Insulation thickness mm2 n/mm mm mm mm kg/100 m TF-44006-016-2 16 126/0.40 16.5 7/0.25 17.2 6.4 57.3 444 TF-44006-025-2 25 209/0.40 18.0 7/0.25 18.6 6.7 61.2 523 TF-44006-035-2 35 285/0.40 19.3 7/0.25 18.6 7.0 64.6 599 TF-44006-050-2 50 380/0.40 20.8 7/0.25 21.3 7.3 68.5 689 TF-44006-070-2 70 361/0.50 22.8 7/0.25 23.4 7.7 73.7 834 TF-44006-095-2 95 475/0.50 24.0 7/0.30 29.2 8.1 77.8 964 TF-44006-120-2 120 608/0.50 26.1 7/0.30 31.7 8.5 83.1 1119 TF-44006-150-2 150 740/0.50 27.9 7/0.40 45.7 8.9 89.1 1349 TF-44006-185-2 185 925/0.50 30.0 7/0.40 48.4 9.3 94.5 1529 Sheath thickness Nominal overall diameter Approx mass 5.0 Nominal siam. over insulation Sheath thickness TYPE 440.11 Class 2 11/11 kV Power conductor Product code Core screen Nominal area Strand size Insulation thickness mm2 n/mm mm mm mm kg/100 m TF-44011-025-2 25 209/0.40 23.4 7/0.25 23.7 8.1 75.6 759 TF-44011-035-2 35 285/0.40 24.7 7/0.30 30.2 8.4 79.6 869 TF-44011-050-2 50 380/0.40 26.2 7/0.30 31.7 8.7 83.5 974 TF-44011-070-2 70 361/0.50 28.2 7/0.30 34.1 9.1 88.7 1139 TF-44011-095-2 95 475/0.50 29.4 7/0.40 47.5 9.6 93.6 1319 TF-44011-120-2 120 608/0.50 31.5 7/0.40 51.0 9.9 98.7 1489 TF-44011-150-2 150 740/0.50 33.3 7/0.40 53.7 10.3 103.4 1679 Sheath thickness Nominal overall diameter Approx mass 7.6 Nominal diam. over insulation Size Area of each screen mm n/mm mm2 TYPE 440.22 Class 2 22/22 kV Power conductor Product code Core screen Nominal area Strand size Insulation thickness Nominal diam. over insulation Size Area of each screen mm2 n/mm mm mm n/mm mm2 mm mm kg/100 m TF-44022-035-2 35 285/0.40 55.4 10.0 104.9 1429 TF-44022-050-2 50 380/0.40 58.1 10.3 108.8 1549 30 10.5 32.6 34.1 7/0.40 TYPE 441 1.1/22 kV REELING AND TRAILING CABLES Type 441 Class 2 1.1 / 22 kV Three-core Cables Central Pilot Core Three Interstitial Earth Conductors Trailing / Draglines / Shovels / Drills / Reeling Applications Construction 31 Conductors Tinned annealed copper wires to AS/NZS 1125:2001 and AS/NZS 2802:2000 Conductor screen Semi-conductive thermosetting compound Insulation Ethylene propylene rubber R-EP-90 and XR-EP-90 AS/NZS 3808 Insulation screen Semi-conductive thermosetting compound to AS/NZS 2802:2000 Earth conductors Mechanically strong earth conductors with semi-conductive elastomeric covering Cradle separator Semi-conductive thermosetting compound and EPR covered Pilot Core (grey) to AS/NZS 2802:2000 Cable assembly Three screened power conductors and three earth conductors (black) laid up with right hand direction on cradle separator with central pilot conductors Filling/covering Semi-conductive thermosetting compound to AS/NZS 2802:2000 tables 6 and 7 Reinforcing braid Polyamide yarns Jacket Thermosetting compound HD-90-CSP heavy duty oil resistant and flame retardant Operating temp Minimum ambient temperature -25˚C Maximum conductor temperature + 90˚C Cable tests AS/NZS 2802:2000 Marking Type of cable, size, manufacturer, year Core ID "1 ONE, (black), 2 TWO, (black), 3 THREE, (black)" FEATURES Crush resistant central cradle construction Flexible EPR insulation Short circuit safety - interstitial earth conductors/semi-conductive cradle Reinforced radial-strengthened heavy duty jacket Oil resistant/flame retardant Rated -25˚C to +90˚C Specifications & Standards: AS/NZS 2802:2000, AS/NZS 1125:2001 TYPE 441.1 Class 2 1.1/1.1 kV Power conductor Product code Earth conductor Nominal diam. over insulation Strand size Nom. conduct. area Sheath thickness Nominal overall diam. Approx mass Nominal area Strand size Insulation thickness mm2 n/mm mm mm n/mm mm2 mm mm kg/100 m TF-44101-006-2 6 84/0.30 1.5 6.5 33/0.30 2.3 3.8 28.6 111 TF-44101-010-2 10 77/0.40 1.5 7.7 51/0.30 3.6 3.8 31.2 136 TF-44101-016-2 16 126/0.40 1.6 9.0 81/0.30 5.7 3.9 34.1 176 TF-44101-025-2 25 209/0.40 1.6 10.5 81/0.30 5.7 4.2 37.8 231 TF-44101-035-2 35 285/0.40 1.6 12.1 81/0.30 5.7 4.4 41.1 274 TF-44101-050-2 50 380/0.40 1.7 13.8 120/0.30 8.5 4.9 45.8 349 TF-44101-070-2 70 361/0.50 1.8 16.1 110/0.40 13.8 5.3 52.2 481 TF-44101-095-2 95 475/0.50 2.0 17.7 135/0.40 16.9 5.8 56.6 579 TF-44101-120-2 120 608/0.50 2.1 20.0 165/0.40 21.2 6.3 62.6 724 TF-44101-150-2 150 740/0.50 2.3 22.2 216/0.40 27.1 6.7 68.3 881 TF-44101-185-2 185 925/0.50 2.5 24.7 252/0.40 32.1 7.3 74.8 1049 TF-44101-249-2 240 1221/0.50 2.8 27.9 214/0.50 42.0 8.0 83.4 1329 TF-44101-300-2 300 1525/0.50 3.0 31.0 280/0.50 55.0 8.7 91.1 1629 Sheath thickness Nominal overall diam. Approx mass TYPE 441.3 Class 1 3.3/3.3 kV Power conductor Product code 32 Earth conductor Nominal area Strand size Insulation thickness Nominal diam. over insulation Strand size Nom. conduct. area mm2 n/mm mm mm n/mm mm2 mm mm kg/100 m TF-44103-016-1 16 126/0.40 2.2 12.4 81/0.30 5.7 4.6 43.0 241 TF-44103-025-1 25 209/0.40 2.2 14.0 81/0.30 5.7 4.9 46.8 304 TF-44103-035-1 35 285/0.40 2.2 15.3 81/0.30 5.7 5.2 50.2 359 TF-44103-050-1 50 380/0.40 2.4 17.1 120/0.30 8.5 5.7 55.4 446 TF-44103-070-1 70 361/0.50 2.4 19.1 110/0.40 13.8 6.0 60.3 571 TF-44103-095-1 95 475/0.50 2.4 20.3 135/0.40 16.9 6.4 63.5 659 TF-44103-120-1 120 608/0.50 2.4 22.4 165/0.40 21.2 6.5 68.5 794 TF-44103-150-1 150 740/0.50 2.4 24.2 216/0.40 27.1 6.6 72.6 931 TF-44103-185-1 185 925/0.50 2.4 26.3 252/0.40 32.1 6.7 77.4 1080 TF-44103-240-1 240 1221/0.50 2.4 28.9 214/0.50 42.0 6.9 83.3 1310 TF-44103-300-1 300 1525/0.50 2.4 31.5 280/0.50 55.0 7.0 89.2 1570 TYPE 441.6 Class 1 6.6/6.6 kV Power conductor Product code Earth conductor Sheath thickness Nominal overall diam. Approx mass mm2 Nominal area Strand size Insulation thickness mm2 n/mm mm mm mm kg/100 m TF-44106-016-1 16 126/0.40 14.0 81/0.30 5.7 5.0 47.4 241 TF-44106-025-1 25 209/0.40 15.5 81/0.30 5.7 5.3 51.2 304 TF-44106-035-1 35 285/0.40 16.8 81/0.30 5.7 5.6 54.7 359 TF-44106-050-1 50 380/0.40 18.3 120/0.30 8.5 6.0 58.8 446 TF-44106-070-1 70 361/0.50 19.1 110/0.40 13.8 6.3 63.8 571 TF-44106-095-1 95 475/0.50 20.3 135/0.40 16.9 6.4 66.4 659 TF-44106-120-1 120 608/0.50 21.5 165/0.40 21.2 6.6 71.3 794 TF-44106-150-1 150 740/0.50 23.6 216/0.40 27.1 6.7 75.4 931 TF-44106-185-1 185 925/0.50 25.4 252/0.40 32.1 6.8 80.1 1080 TF-44106-240-1 240 1221/0.50 27.5 214/0.50 42.0 7.0 86.1 1310 TF-44106-300-1 300 1525/0.50 30.1 280/0.50 55.0 7.1 91.9 1570 Sheath thickness Nominal overall diam. Approx mass 3.0 Nominal diam. over insulation Strand size Nom. conduct. area mm n/mm TYPE 441.11 Class 1 11/11 kV Power conductor Product code Earth conductor Nominal area Strand size Insulation thickness mm2 n/mm mm TF-44111-016-1 25 209/0.40 19.6 TF-44111-025-1 35 285/0.40 20.8 81/0.30 5.7 6.4 65.1 542 TF-44111-035-1 50 380/0.40 22.4 120/0.30 8.5 6.5 68.7 620 TF-44111-050-1 70 361/0.50 24.4 110/0.40 13.8 6.6 63.8 750 TF-44111-070-1 95 475/0.50 25.6 135/0.40 16.9 6.8 73.0 850 TF-44111-095-1 120 608/0.50 27.7 165/0.40 21.2 6.9 76.2 986 TF-44111-120-1 150 740/0.50 29.5 216/0.40 27.1 7.0 80.8 1129 TF-44111-150-1 185 925/0.50 31.6 252/0.40 32.1 7.1 85.0 1289 TF-44111-185-1 240 1221/0.50 34.2 214/0.50 42.0 7.3 89.6 1539 Sheath thickness Nominal overall diam. Approx mass 5.0 Nominal diam. over insulation Strand size Nom. conduct. area mm n/mm mm2 mm mm kg/100 m 81/0.30 5.7 6.3 62.1 481 TYPE 441.22 Class 1 22/22 kV 33 Power conductor Product code TF-44122-035-1 Nominal area Strand size Insulation thickness mm2 n/mm mm 35 285/0.40 Earth conductor Nominal diam. over insulation Strand size Nom. conduct. area mm n/mm mm2 mm mm kg/100 m 26.3 81/0.30 5.7 6.9 78.0 733 TF-44122-050-1 50 380/0.40 27.8 120/0.30 8.5 7.0 81.5 820 TF-44122-070-1 70 361/0.50 29.8 110/0.40 13.8 7.1 85.9 960 TF-44122-095-1 95 475/0.50 31.0 135/0.40 16.9 7.2 88.7 1070 TF-44122-120-1 120 608/0.50 33.1 165/0.40 21.2 7.3 93.6 1220 TF-44122-150-1 150 740/0.50 34.9 216/0.40 27.1 7.4 97.6 1380 TF-44122-185-1 185 925/0.50 37.0 252/0.40 32.1 7.6 102.6 1545 7.6 TYPE 450 3.3/33 kV REELING AND TRAILING CABLES Type 450 Class 1 3.3/33 kV Copper Screened Three-core Cables Two Earth and One Pilot Interstitial Conductors Dragline/Shovel/Drills/Reeling Applications Construction 34 Conductors Tinned annealed copper wires to AS/NZS 1125:2001 and AS/NZS 2802:2000 Conductor screen Semi-conductive thermosetting compound Insulation Ethylene propylene rubber XR-EP-90 to AS/NZS 3808 Insulation screen Semi-conductive thermosetting compound, tinned copper/polyamide braid to AS/NZS 2802:2000 12.4.1 Earth conductors Mechanically strong earth conductors with semi-conductive elastomeric covering Cable assembly Three screened power conductors, two Earth conductors (black) and one insulated Pilot conductor (grey) laid up in right hand direction with Elastomeric centre filler Inner jacket Thermosetting compound HD-85-CSP extra heavy duty oil resistant and flame retardant Reinforcing braid Open polyamide braid between Inner and Outer Jacket Outer jacket Thermosetting compound HD-85-PCP extra heavy duty oil resistant and flame retardant Operating temp Minimum ambient temperature -25˚C Maximum conductor temperature + 90˚C Cable tests AS/NZS 2802:2000 Marking Type of cable, size, manufacturer, year, type of insulation and jacket Core ID Red, (black), White, (black), Blue, (grey) FEATURES High grade flexible EPR conductors Short circuit safety/screened power conductors/interstitial earth conductors Interstitial pilot conductor Reinforced radial-strengthened heavy duty jacket Oil resistant/flame retardant Rated -25˚C to +90˚C Specifications & Standards: AS/NZS 2802:2000, AS/NZS 1125:2001 TYPE 450.3 Class 1 3.3/3.3 kV Power conductor Product code Core screen Nominal area Strand size Insulation thickness Nominal diam. over insulation Size Area of each screen mm2 n/mm mm mm n/mm TF-45003-016-1 16 126/0.40 2.2 12.4 TF-45003-025-1 25 209/0.40 2.2 14.0 Earth / pilot conductor Sheath thickness Nominal overall diam. Approx mass Strand Size Covering thickness mm2 n/mm mm mm mm kg/100 m 128/0.25 6.3 120/0.30 1.4 4.5 42.8 266 118/0.30 8.3 120/0.30 1.4 4.8 46.9 338 TF-45003-035-1 35 285/0.40 2.2 15.2 127/0.30 9.0 120/0.30 1.4 5.1 50.4 392 TF-45003-050-1 50 380/0.40 2.4 17.1 141/0.30 10.0 183/0.30 1.4 5.6 55.7 487 TF-45003-070-1 70 361/0.50 2.4 19.1 117/0.40 14.7 152/0.40 1.4 6.0 61.3 637 TF-45003-095-1 95 475/0.50 2.4 20.3 123/0.40 15.5 196/0.40 1.6 6.3 64.5 734 TF-45003-120-1 120 608/0.50 2.4 22.4 135/0.40 17.0 236/0.40 1.6 6.4 69.2 867 TF-45003-150-1 150 740/0.50 2.4 24.2 144/0.40 18.1 314/0.40 1.6 6.6 73.5 1022 TF-45003-185-1 185 925/0.50 2.4 26.3 144/0.40 26.7 237/0.50 1.6 6.7 78.3 1175 TF-45003-240-1 240 1221/0.50 2.4 28.9 136/0.50 28.3 302/0.50 1.6 6.9 84.7 1741 Sheath thickness Nominal overall diam. Approx mass TYPE 450.6 Class 1 6.6/6.6 kV Power conductor Product code TF-45006-016-1 35 Core screen Earth / pilot conductor Nominal area Strand size Insulation thickness Nominal diam. over insulation Size Area of each screen Strand size Covering thickness mm2 n/mm mm mm n/mm mm2 n/mm mm mm mm kg/100 m 16 126/0.40 14.0 118/0.30 8.3 120/0.30 1.4 5.0 47.7 317 TF-45006-025-1 25 209/0.40 15.5 129/0.30 9.1 120/0.30 1.6 5.2 51.3 382 TF-45006-035-1 35 285/0.40 16.8 139/0.30 9.8 120/0.30 1.6 5.5 54.8 443 TF-45006-050-1 50 380/0.40 18.4 149/0.30 10.5 177/0.30 1.6 5.9 58.9 534 TF-45006-070-1 70 361/0.50 TF-45006-095-1 95 475/0.50 TF-45006-120-1 120 608/0.50 3.0 20.3 123/0.40 15.5 152/0.40 1.6 6.3 64.3 682 21.5 130/0.40 16.3 196/0.40 1.8 6.4 67.1 771 23.6 141/0.40 17.7 236/0.40 1.8 6.5 71.9 912 TF-45006-150-1 150 740/0.50 25.4 144/0.40 18.1 314/0.40 1.8 6.6 76.2 1073 TF-45006-185-1 185 925/0.50 27.5 144/0.40 18.1 237/0.50 1.8 6.8 81.0 1222 TF-45006-240-1 240 1221/0.50 30.1 141/0.50 27.7 302/0.50 1.8 7.0 87.5 1502 TYPE 450.11 Class 1 11/11 kV Power conductor Product code Core screen Nominal area Strand size Insulation thickness Nominal diam. over insulation Size Area of each screen mm2 n/mm mm mm n/mm TF-45011-025-1 25 209/0.40 16.6 TF-45011-035-1 35 285/0.40 20.9 Earth / pilot conductor Sheath thickness Nominal overall diam. Approx mass Strand size Thickness of EPR covering mm2 n/mm mm mm mm kg/100 m 120/0.40 15.1 120/0.30 2.0 6.3 62.8 542 127/0.40 16.0 120/0.30 2.0 6.4 65.8 601 TF-45011-050-1 50 380/0.40 22.4 135/0.40 17.0 183/0.30 2.0 6.5 69.4 692 TF-45011-070-1 70 361/0.50 24.4 144/0.40 18.1 152/0.40 2.0 6.6 73.9 826 TF-45011-095-1 95 475/0.50 25.6 144/0.40 18.1 196/0.40 2.2 6.7 76.7 926 5.0 TF-45011-120-1 120 608/0.50 27.7 144/0.50 18.1 236/0.40 2.2 6.9 81.8 1082 TF-45011-150-1 150 740/0.50 29.5 139/0.50 27.3 314/0.40 2.2 7.0 86.2 1263 TF-45011-185-1 185 925/0.50 31.6 144/0.50 28.3 237/0.50 2.2 7.1 90.9 1433 TF-45011-240-1 240 1221/0.50 34.2 141/0.50 28.3 302/0.50 2.2 7.3 96.8 1695 Sheath thickness Nominal overall diam. Approx mass TYPE 450.22 Class 1 22/22 kV Power conductor Product code Core screen Nominal area Strand size Insulation thickness Nominal diam. over insulation Size Area of each screen mm2 n/mm mm mm n/mm TF-45022-035-1 35 285/0.40 26.3 TF-45022-050-1 50 380/0.40 27.8 TF-45022-070-1 70 203/0.50 TF-45022-095-1 95 259/0.50 TF-45022-120-1 120 TF-45022-150-1 150 Earth / pilot conductor Strand size Thickness of EPR covering mm2 n/mm mm mm mm kg/100 m 144/0.40 18.1 120/0.30 6.8 78.5 601 144/0.40 18.1 183/0.30 6.9 81.8 692 29.8 140/0.50 27.5 152/0.40 31.0 144/0.50 28.3 196/0.40 336/0.50 33.1 144/0.50 28.3 427/0.50 34.9 144/0.50 28.3 7.6 7.0 86.9 826 7.2 89.9 926 236/0.40 7.3 94.7 1082 314/0.40 7.4 103.4 1263 Sheath thickness Nominal overall diam. Approx mass mm kg/100 m 2.5 TYPE 450.33 Class 1 33/33 kV Power conductor Product code 36 Core screen Nominal area Strand size Insulation thickness Nominal diam. over insulation mm2 n/mm mm mm 10.5 36.1 TF-45033-050-1 50 380/0.40 TF-45033-070-1 70 361/0.50 TF-45033-095-1 95 475/0.50 Size Area of each screen Strand size Thickness of EPR covering n/mm mm2 n/mm mm mm 7.4 96.9 1222 144/0.50 28.3 152/0.40 2.5 7.5 101.4 385 7.7 104.4 1505 34.1 37.3 Earth / pilot conductor 183/0.30 196/0.40 TYPE 455 3.3/33 kV REELING AND TRAILING CABLES Type 455 Class 1 3.3/33 kV Three-core Cables Two Earth and One Pilot Interstitial Conductors Stacker/Reclamation Applications Construction 37 Conductors Tinned annealed copper wires to AS/NZS 1125:2001 and AS/NZS 2802:2000 Conductor screen Semi-conductive thermosetting compound Insulation Ethylene propylene rubber XR-EP-90 AS/NZS 3808 Insulation screen Semi-conductive thermosetting compound to AS/NZS 2802:2000 Earth conductors Mechanically strong earth conductors with semi-conductive elastomeric covering Cable assembly Three screened power conductors, two Earth (black) and one Pilot conductor (grey) laid up in right hand direction Filling/covering Semi-conductive thermosetting compound to AS/NZS 2802:2000 tables 6 and 7 Reinforcing braid Open polyamide braid Jacket Thermosetting compound XHD-90-CSP extra heavy duty oil resistant and flame retardant Operating temp Minimum ambient temperature -25˚C Maximum conductor temperature + 90˚C Cable tests AS/NZS 2802:2000 Marking Type of cable, size, manufacturer, year, type of insulation and jacket Core ID Red, (black), White, (black), Blue, (grey) FEATURES High grade flexible EPR conductors Short circuit safety - interstitial earth conductors/semi-conductive inner sheath Interstitial pilot conductor Reinforced radial-strengthened heavy duty jacket Oil resistant/flame retardant Rated -25˚C to +90˚C Specifications & Standards: AS/NZS 2802:2000, AS/NZS 1125:2001 TYPE 455.3 Class 1 3.3/3.3 kV Power conductor Product code Earth / pilot conductor Sheath thickness Nominal overall diam. Approx mass Nominal area Strand size Insulation thickness Nominal diam. over insulation Size Thickness of EPR covering mm2 n/mm mm mm n/mm mm mm mm kg/100 m TF-45503-016-1 16 126/0.40 2.2 12.4 120/0.30 1.4 4.2 39.5 224 TF-45503-025-1 25 209/0.40 2.2 14.0 120/0.30 1.4 4.5 43.4 281 TF-45503-035-1 35 285/0.40 2.2 15.2 120/0.30 1.4 4.8 46.8 336 TF-45503-050-1 50 380/0.40 2.4 17.1 183/0.30 1.4 5.3 52.0 424 TF-45503-070-1 70 361/0.50 2.4 19.1 152/0.40 1.4 5.7 57.0 556 TF-45503-095-1 95 475/0.50 2.4 20.3 196/0.40 1.6 6.1 60.5 646 TF-45503-120-1 120 608/0.50 2.4 22.4 236/0.40 1.6 6.4 65.6 786 TF-45503-150-1 150 740/0.50 2.4 24.2 314/0.40 1.6 6.5 69.6 931 TF-45503-185-1 185 925/0.50 2.4 26.3 237/0.50 1.6 6.6 74.5 1072 TF-45503-240-1 240 1221/0.50 2.4 28.9 302/0.50 1.6 6.8 80.4 1310 TF-45503-300-1 300 1525/0.50 2.4 31.5 409/0.50 1.6 6.9 86.2 1602 Sheath thickness Nominal overall diam. Approx mass TYPE 455.6 Class 1 6.6/6.6 kV Power conductor Product code TF-45506-016-1 38 Earth / pilot conductor Nominal area Strand size Insulation thickness Nominal diam. over insulation Size Thickness of EPR covering mm2 n/mm mm mm n/mm mm mm mm kg/100 m 16 126/0.40 14.0 120/0.30 1.6 4.7 44.0 266 TF-45506-025-1 25 209/0.40 15.5 120/0.30 1.6 5.0 47.9 332 TF-45506-035-1 35 285/0.40 16.8 120/0.30 1.6 5.3 51.4 387 TF-45506-050-1 50 380/0.40 18.3 183/0.30 1.6 5.6 55.1 466 TF-45506-070-1 70 361/0.50 20.3 152/0.40 1.8 6.0 60.2 597 TF-45506-095-1 95 475/0.50 21.5 196/0.40 1.8 6.3 63.4 692 3.0 TF-45506-120-1 120 608/0.50 23.6 236/0.40 1.8 6.5 68.4 826 TF-45506-150-1 150 740/0.50 25.4 314/0.40 1.8 6.6 72.5 977 TF-45506-185-1 185 925/0.50 27.5 237/0.50 1.8 6.7 77.2 1122 TF-45506-240-1 240 1221/0.50 30.1 302/0.50 1.8 6.9 83.2 1361 TF-45506-300-1 300 1525/0.50 32.7 409/0.50 1.8 7.0 89.0 1652 TYPE 455.11 Class 1 11/11 kV Power conductor Product code Earth / pilot conductor Nominal area Strand size Insulation thickness Nominal diam. over insulation Size Thickness of EPR covering mm2 n/mm mm mm n/mm mm Sheath thickness Nominal overall diam. Approx mass mm mm kg/100 m TF-45511-016-1 16 126/0.40 18.1 120/0.30 2.0 5.8 55.0 392 TF-45511-025-1 25 209/0.40 19.6 120/0.30 2.0 6.1 59.1 462 TF-45511-035-1 35 285/0.40 20.9 120/0.30 2.0 6.3 62.4 527 TF-45511-050-1 50 380/0.40 22.4 183/0.30 2.0 6.4 65.7 607 TF-45511-070-1 70 361/0.50 24.4 152/0.40 2.0 6.5 70.2 742 TF-45511-095-1 95 475/0.50 25.6 196/0.40 2.2 6.7 73.4 837 TF-45511-120-1 120 608/0.50 27.7 236/0.40 2.2 6.8 78.0 982 TF-45511-150-1 150 740/0.50 29.5 314/0.40 2.2 6.9 82.1 1143 5.0 TF-45511-185-1 185 925/0.50 31.6 237/0.50 2.2 7.0 86.9 1305 TF-45511-240-1 240 1221/0.50 34.2 302/0.50 2.2 7.2 92.9 1553 Sheath thickness Nominal overall diam. Approx mass TYPE 455.22 Class 1 22/22 kV Power conductor Product code Nominal area Earth / pilot conductor Strand size Insulation thickness Nominal diam. over insulation Size Thickness of EPR covering mm2 n/mm mm TF-45522-016-1 16 126/0.40 mm n/mm mm mm mm kg/100 m 23.5 120/0.30 6.6 68.5 578 TF-45522-025-1 25 209/0.40 25.0 120/0.30 6.6 71.7 653 TF-45522-035-1 35 285/0.40 26.3 120/0.30 6.7 74.8 719 TF-45522-050-1 50 380/0.40 27.8 183/0.30 6.8 78.3 810 TF-45522-070-1 70 361/0.50 29.8 152/0.40 7.0 83.0 956 7.6 2.5 TF-45522-095-1 95 475/0.50 31.0 196/0.40 7.1 85.8 1061 TF-45522-120-1 120 608/0.50 33.1 236/0.40 7.2 90.6 1221 TF-45522-150-1 150 740/0.50 34.9 314/0.40 7.3 94.7 1392 TF-45522-185-1 185 925/0.50 37.0 237/0.50 7.4 99.2 1564 Sheath thickness Nominal overall diam. Approx mass TYPE 455.33 Class 1 33/33 kV 39 Power conductor Product code Nominal area Earth / pilot conductor Strand size Insulation thickness Nominal diam. over insulation mm2 n/mm mm TF-45533-016-1 16 126/0.40 TF-45533-025-1 25 209/0.40 TF-45533-035-1 35 285/0.40 TF-45533-050-1 50 380/0.40 TF-45533-070-1 70 361/0.50 10.5 Size Thickness of EPR covering mm n/mm mm mm mm kg/100 m 29.8 120/0.30 7.0 83.0 822 31.3 120/0.30 7.1 86.4 920 32.6 120/0.30 34.1 183/0.30 7.2 89.4 993 7.3 92.8 1092 36.1 152/0.40 7.4 97.4 1254 2.5 TF-45533-095-1 95 475/0.50 37.3 196/0.40 7.6 100.5 1372 TF-45533-120-1 120 608/0.50 39.4 236/0.40 7.7 105.2 1543 Cutting edge machine cables MACHINE CABLES Type 1 Machine Cables 1.1 kV -30C to +90C V-90 PVC Insulated and 5V-90 Type 2S Machine Cables 1.1 kV -30C to +90C Collectively or Individually Screened AS 5000.1 TXLPE Insulated PVC Bedded GSW Serve Wire Armoured Cable / PVC Sheath 0.6 to 1 kV -5C to +90C 41 TYPE 1 1.1/1.1 kV MACHINE CABLES Type 1 1.1/1.1 kV V-90 PVC Insulated and 5V-90 Sheathed Individually Screened Machine Cables, Non – Mobile or Fixed Apparatus Control Boxes and Motors Construction Conductors Flexible tinned copper conductor to AS/NZS 1125 Dimensions of cables comply with Table 1a, 1b Colour of sheath Black or Transparent Insulation Special PVC compound type V-90 acc. To AS/NZS 3808, AS/NZS 5000.1 Insulation screen Braid made of 0.2mm tinned copper wires, coverage min 80%. A polyester tape may be applied over and under the screen Fillers Non-hygroscopic Covering Special PVC compound type 5V-90 to AS/NZS 3808, AS/NZS 1660 Operating temp Minimum ambient temperature -30˚C Maximum conductor temperature + 90˚C Cable tests AS/NZS 1125, AS/NZS 3808 Marking Type of cable, size, manufacturer, year Core ID Black - "1 ONE, 2 TWO, 3 THREE" FEATURES Special flexible PVC 42 Short circuit safety - earth screened conductors Resistant to chemical attack Rated -30˚C to +90˚C Specifications & Standards: AS/NZS 1972, AS/NZS 1125, AS/NZS 3808 TYPE 1 Product code TF-1-3x2.5-IS TF-1-3x4-IS 43 Approx. overall diameter Approx. net weight of cables Maximum conductor resistance at temperature 200C mm mm kg/km Ω/km 0.8 0.8 11.0 176 8.21 1.0 1.0 12.9 249 5.09 Number of conductor Cross section of conductor Maximum dia. of wires in conductor n/mm2 mm mm mm 2.5 0.26 4 0.31 3 Nominal Nominal thickness of thickness of insulation sheath TYPE 2S (IS) 1.2 kV MACHINE CABLES Type 2S 1.2 kV Flexible Multi-Core Individually Screened Machine Cables, Non – Mobile or Fixed Apparatus Construction Conductors Flexible tinned annealed copper wires to AS/NZS 1125 Insulation Ethylene propylene compound Type R-EP-90 to AS/NZS 3808 Screen Individual and collective braid of tinned copper wire and nylon yarns, covering minimum 80% under screen separator of polyester tape Outer sheath Thermosetting synthetic CPE compound equivalent HD-90-CPE, heavy duty, oil resistant and flame retardant Colour Black to AS/NZS 3808 Cable tests AS/NZS 1972: 2006 Marking Type of cable, year, size, metric scale Core ID “1 ONE, 2 TWO, 3 THREE” identification in accordance with AS 1979 FEATURES Flexible EPR insulation Short circuit safety - individually and collectively screened conductors Oil resistant/flame retardant Rated -30˚C to +90˚C Specifications & Standards: AS/NZS 1972: 2006 44 TYPE 2S Product code 45 Number of cores Power conductor strand size Thickness of insulation n mm mm 16 1.0 Type of screen Sheath thickness mm TF-2S-02x16-IS 2 TF-2S-03x16-IS 3 TF-2S-04x16-IS 4 TF-2S-06x16-IS 6 TF-2S-02x25-IS 2 TF-2S-03x25-IS 3 TF-2S-04x25-IS 4 TF-2S-06x25-IS 6 TF-2S-02x35-IS 2 TF-2S-03x35-IS 3 TF-2S-04x35-IS 4 TF-2S-02x50-IS 2 TF-2S-03x50-IS 3 TF-2S-04x50-IS 4 TF-2S-02x70-IS 2 TF-2S-03x70-IS 3 TF-2S-04x70-IS 4 2.1 TF-2S-02x95-IS 2 2.1 TF-2S-03x95-IS 3 TF-2S-04x95-IS 4 Individually 1.8 1.8 25 1.2 Individually 1.8 1.8 1.9 35 1.2 Individually 50 1.4 Individually 1.8 1.8 1.9 2.0 2.0 70 95 1.4 1.6 Individually Individually 2.0 2.2 2.3 TYPE 2S Product code Number of cores Size Insulation thickness n mm2 mm 1.5 0.8 Individually 1.8 2.5 1.0 Individually 1.8 4 1.0 Individually 1.8 6 1.0 Individually 1.8 10 1.0 Individually 1.8 TF-2S-02x1.5-IS 2 TF-2S-03x1.5-IS 3 TF-2S-04x1.5-IS 4 TF-2S-06x1.5-IS 6 TF-2S-16x1.5-IS 16 TF-2S-30x1.5-IS 30 TF-2S-02x2.5-IS 2 TF-2S-03x2.5-IS 3 TF-2S-04x2.5-IS 4 TF-2S-06x2.5-IS 6 TF-2S-02x4.0-IS 2 TF-2S-03x4.0-IS 3 TF-2S-04x4.0-IS 4 TF-2S-06x4.0-IS 6 TF-2S-02x6.0-IS 2 TF-2S-03x6.0-IS 3 TF-2S-04x6.0-IS 4 TF-2S-06x6.0-IS 6 TF-2S-02x10-IS 2 TF-2S-03x10-IS 3 TF-2S-04x10-IS 4 TF-2S-06x10-IS 6 Type of screen Sheath thickness mm Individually Screened (IS) Electrical Properties Size Max. resistance DC 20°C mm Ω/km 2 46 AC 90°C capacitance Rating current 2-core 3-core μF/km 4-core 6-core A 1.5 13.7 17.5 0.223 20 20 20 20 2.5 8.21 10.5 0.275 32 27 27 24 4 5.09 6.49 0.326 45 39 39 31 6 3.39 4.32 0.403 57 48 48 39 10 1.95 2.49 0.504 80 67 67 53 16 1.24 1.58 0.605 106 89 89 72 25 0.795 1.01 0.621 141 119 119 96 35 0.565 0.721 0.719 174 147 147 - 50 0.393 0.502 0.735 218 185 185 - 70 0.277 0.354 0.860 272 230 230 - 95 0.210 0.269 0.867 323 271 271 - Size Inductance 2-core 3-core 1.5 0.399 0.399 2.5 0.364 0.364 mm 6-core 2-core 3-core 0.501 0.598 0.125 0.456 0.545 0.114 Impedance at 90°C 4-core 6-core 2-core 3-core 0.125 0.157 0.188 17.5 0.114 0.143 0.171 10.5 mH/km 2 47 4-core Reactance 4-core 6-core 17.5 17.5 17.5 10.5 10.5 10.5 Ω/km Ω/km 4 0.339 0.339 0.425 0.508 0.106 0.106 0.134 0.159 6.49 6.49 6.49 6.49 6 0.313 0.313 0.393 0.469 0.098 0.098 0.123 0.147 4.32 4.32 4.32 4.33 10 0.290 0.290 0.364 0.434 0.091 0.091 0.114 0.136 2.49 2.49 2.49 2.49 16 0.274 0.274 0.344 0.411 0.086 0.086 0.108 0.129 1.58 1.58 1.58 1.59 25 0.267 0.267 0.335 0.401 0.084 0.084 0.105 0.126 1.02 1.02 1.02 1.02 35 0.257 0.257 0.323 - 0.081 0.081 0.101 - 0.725 0.725 0.728 - 50 0.253 0.253 0.317 - 0.079 0.079 0.100 - 0.508 0.508 0.512 - 70 0.244 0.244 0.306 - 0.077 0.077 0.096 - 0.362 0.362 0.367 - 95 0.241 0.241 0.303 - 0.076 0.076 0.095 - 0.280 0.280 0.285 - TYPE 2S (CS) 1.2 kV MACHINE CABLES Type 2S 1.2 kV Flexible Multi-Core Collectively Screened Machine Cables, Non – Mobile or Fixed Apparatus Construction Conductors Flexible tinned annealed copper wires to AS/NZS 1125 Insulation Ethylene propylene compound Type R-EP-90 to AS/NZS 3808 Screen Individual and collective braid of tinned copper wire and nylon yarns, covering minimum 80% under screen separator of polyester tape Outer sheath Thermosetting synthetic CPE compound equivalent HD-90-CPE, heavy duty, oil resistant and flame retardant Colour Black to AS/NZS 3808 Cable tests AS/NZS 1972: 2006 Marking Type of cable, year, size, metric scale Core ID “1 ONE, 2 TWO, 3 THREE” identification in accordance with AS 1979 FEATURES Flexible EPR insulation Short circuit safety - individually and collectively screened conductors Oil resistant/flame retardant Rated -30˚C to +90˚C Specifications & Standards: AS/NZS 1972: 2006 48 TYPE 2S Product code 49 Number of cores Power conductor strand size Thickness of insulation n mm mm 1.5 0.8 Collective 1.8 2.5 1.0 Collective 1.8 4 1.0 Collective 1.8 6 1.0 Collective 1.8 10 1.0 Collective 1.8 TF-2S-02x1.5-CS 2 TF-2S-03x1.5-CS 3 TF-2S-04x1.5-CS 4 TF-2S-06x1.5-CS 6 TF-2S-16x1.5-CS 16 TF-2S-30x1.5-CS 30 TF-2S-02x2.5-CS 2 TF-2S-03x2.5-CS 3 TF-2S-04x2.5-CS 4 TF-2S-06x2.5-CS 6 TF-2S-02x4.0-CS 2 TF-2S-03x4.0-CS 3 TF-2S-04x4.0-CS 4 TF-2S-06x4.0-CS 6 TF-2S-02x6.0-CS 2 TF-2S-03x6.0-CS 3 TF-2S-04x6.0-CS 4 TF-2S-06x6.0-CS 6 TF-2S-02x10-CS 2 TF-2S-03x10-CS 3 TF-2S-04x10-CS 4 TF-2S-06x10-CS 6 Type of screen Sheath thickness mm TYPE 2S Product code Number of cores Size Insulation thickness n mm2 mm 16 1.0 TF-2S-02x16-CS 2 TF-2S-03x16-CS 3 TF-2S-04x16-CS 4 TF-2S-06x16-CS 6 TF-2S-02x25-CS 2 TF-2S-03x25-CS 3 TF-2S-04x25-CS 4 TF-2S-06x25-CS 6 TF-2S-02x35-CS 2 TF-2S-03x35-CS 3 TF-2S-04x35-CS 4 TF-2S-02x50-CS 2 TF-2S-03x50-CS 3 TF-2S-04x50-CS 4 TF-2S-02x70-CS 2 TF-2S-03x70-CS 3 TF-2S-04x70-CS 4 TF-2S-02x95-CS 2 TF-2S-03x95-CS 3 TF-2S-04x95-CS 4 Type of screen Sheath thickness mm Collective 1.8 1.8 25 1.2 1.8 Collective 1.8 1.9 35 1.2 Collective 50 1.4 Collective 1.8 1.8 1.9 2.0 1.9 70 1.4 Collective 2.0 2.1 2.1 95 1.6 Collective 2.2 2.3 Individually Screened (CS) Electrical Properties Size Max. resistance DC 20°C mm 50 AC 90°C Ω/km 2 Capacitance Rating current 2-core 3-core μF/km 4-core 6-core A 1.5 13.7 17.5 0.159 20 20 20 20 2.5 8.21 10.5 0.192 32 27 27 24 4 5.09 6.49 0.224 45 39 39 31 6 3.39 4.32 0.271 57 48 48 39 10 1.95 2.49 0.332 80 67 67 53 16 1.24 1.58 0.394 106 89 89 72 25 0.795 1.01 0.409 141 119 119 96 35 0.565 0.72 0.470 174 147 147 - 50 0.393 0.50 0.484 218 185 185 - 70 0.277 0.35 0.562 272 230 230 - 95 0.210 0.27 0.571 323 271 271 - Size Inductance 2-core 3-core mm 6-core 2-core 3-core mH/km 2 51 4-core Reactance 4-core Impedance at 90°C 6-core 2-core 3-core Ω/km 4-core 6-core Ω/km 1.5 0.338 0.338 0.404 0.470 0.106 0.106 0.127 0.148 17.5 17.5 17.5 17.5 2.5 0.310 0.310 0.370 0.431 0.097 0.097 0.116 0.135 10.5 10.5 10.5 10.5 4 0.291 0.291 0.347 0.404 0.091 0.091 0.109 0.127 6.49 6.49 6.49 6.49 6 0.271 0.271 0.324 0.377 0.085 0.085 0.102 0.118 4.32 4.32 4.32 4.32 10 0.255 0.255 0.304 0.354 0.080 0.080 0.096 0.111 2.49 2.49 2.49 2.49 16 0.244 0.244 0.291 0.339 0.077 0.077 0.091 0.106 1.58 1.58 1.58 1.58 25 0.242 0.242 0.290 0.337 0.076 0.076 0.091 0.106 1.02 1.02 1.02 1.02 35 0.235 0.235 0.281 - 0.074 0.074 0.088 - 0.725 0.725 0.726 - 50 0.234 0.234 0.280 - 0.073 0.073 0.088 - 0.507 0.507 0.509 - 70 0.227 0.227 0.272 - 0.071 0.071 0.085 - 0.361 0.361 0.364 - 95 0.227 0.227 0.271 - 0.071 0.071 0.085 - 0.278 0.278 0.282 - TYPE XLPE SWA PVC 0.6/1 kV XLPE INSULATED PVC BEDDED 0.6 to 1 kV GSW Armoured Cable/PVC Sheath Power Networks, Outdoors, Underground and Conduit Construction Conductors Circular Stranded and circular compacted stranded conductor class 2 (RM and RMC) to AS/NZS 1125 Insulation Cross-linked polyethylene XLPE type X-90 to AS/NZS 3808 Inner sheath PVC compound type 5V-90 acc to AS/NZS 3808; colour white Armour Galvanized steel wires helically served Outer sheath PVC UV resistant compound type 5V-90 to AS/NZS 3808; colour orange RAL 2003 Min. bend radius 12 X D multi-core cables,” D = Overall diameter” Short Circuit Temp: 250C Core ID 2 Core + Earth - Red, Black, Green/Yellow FEATURES Flexible PVC insulation Crush resistant core Resistant to chemical attack UV resistant Armored - cut through resistant Rated +90˚C 52 Specifications & Standards: AS/NZS 5000.1 TYPE XLPE SWA PVC Nominal thickness insulation Nominal thickness inner sheath Nominal diameter armour wire Nominal thickness outer sheath Approx overall diameter Approx cable weight n x mm2 mm mm mm mm mm kg/km Ω/km TF-51-XLPE-2x1.5-SWA 2x1.5RM+1.5RM 0.7/0.7 1.0 0.9 1.8 13.8 353 12.1/12.1 TF-51-XLPE-2x2.5-SWA 2x2.5RM+2.5RM 0.7/0.7 1.0 0.9 1.8 14.7 412 7.41/7.41 Product code 53 Number and crosssectional area of conductor Max conductor resistance at 20oC TF-51-XLPE-2x04-SWA 2x4RM+2.5RM 0.7/0.7 1.0 0.9 1.8 15.3 472 4.61/7.41 TF-51-XLPE-2x06-SWA 2x6RMC+2.5RM 0.7/0.7 1.0 0.9 1.8 16.0 539 3.08/7.41 TF-51-XLPE-2x10-SWA 2x10RMC+4RM 0.7/0.7 1.0 1.25 1.8 18.3 796 1.83/4.61 TF-51-XLPE-2x16-SWA 2x16RMC+6RMC 0.7/0.7 1.0 1.25 1.8 20.1 1004 1.15/3.08 TF-51-XLPE-2x25-SWA 2x25RMC+6RMC 0.9/0.7 1.0 1.25 1.8 22.5 1330 0.727/3.08 TF-51-XLPE-2x35-SWA 2x35RMC+10RMC 0.9/0.7 1.0 1.6 1.8 25.4 1803 0.524/1.83 TF-51-XLPE-2x50-SWA 2x50RM+16RMC 1.0/0.7 1.0 1.6 1.8 28.3 2281 0.387/1.15 TF-51-XLPE-2x70-SWA 2x70RMC+25RMC 1.1/0.9 1.0 1.6 1.9 31.9 2991 0.268/0.727 TF-51-XLPE-2x90-SWA 2x95RMC+25RMC 1.1/0.9 1.0 1.6 2.0 34.9 3702 0.193/0.727 TF-51-XLPE-2x120-SWA 2x120RMC+35RMC 1.2/0.9 1.2 2.0 2.1 39.4 4818 0.153/0.524 Product code Number and crosssectional area of conductor Nominal thickness insulation Nominal thickness inner sheath Nominal diameter armour wire Nominal thickness outer sheath Approx overall diameter Approx cable weight Max conductor resistance at 20oC n x mm2 mm mm mm mm mm kg/km Ω/km TF-51-XLPE-3x1.5-SWA 3x1.5RM+1.5RM 0.7/0.7 1.0 0.9 1.8 14.5 393 12.1/12.1 TF-51-XLPE-3x2.5-SWA 3x2.5RM+2.5RM 0.7/0.7 1.0 0.9 1.8 15.6 465 7.41/7.41 TF-51-XLPE-3x04-SWA 3x4RM+2.5RM 0.7/0.7 1.0 0.9 1.8 16.4 546 4.61/7.41 TF-51-XLPE-3x06-SWA 3x6RMC+2.5RM 0.7/0.7 1.0 1.25 1.8 17.9 733 3.08/7.41 TF-51-XLPE-3x10-SWA 3x10RMC+4RM 0.7/0.7 1.0 1.25 1.8 19.8 939 1.83/4.61 TF-51-XLPE-3x16-SWA 3x16RMC+6RMC 0.7/0.7 1.0 1.25 1.8 21.9 1224 1.15/3.08 TF-51-XLPE-3x25-SWA 3x25RMC+6RMC 0.9/0.7 1.0 1.6 1.8 25.7 1810 0.727/3.08 TF-51-XLPE-3x35-SWA 3x35RMC+10RMC 0.9/0.7 1.0 1.6 1.8 28.1 2267 0.524/1.83 TF-51-XLPE-3x50-SWA 3x50RM+16RMC 1.0/0.7 1.0 1.6 1.9 31.7 2884 0.387/1.15 TF-51-XLPE-3x70-SWA 3x70RMC+25RMC 1.1/0.9 1.2 2.0 2.1 37.1 4119 0.268/0.727 TF-51-XLPE-3x95-SWA 3x95RMC+25RMC 1.1/0.9 1.2 2.0 2.2 40.8 5137 0.193/0.727 TF-51-XLPE-3x120-SWA 3x120RMC+35RMC 1.2/0.9 1.2 2.0 2.3 44.6 6225 0.153/0.524 TF-51-XLPE-3x150-SWA 3x150RMC+50RMC 1.4/1.0 1.4 2.5 2.5 51.0 8064 0.124/0.387 TF-51-XLPE-3x185-SWA 3x185RMC+70RMC 1.6/1.1 1.4 2.5 2.6 55.5 9725 0.0991/0.268 TF-51-XLPE-3x240-SWA 3x240RMC+95RMC 1.7/1.1 1.6 2.5 2.8 62.4 12265 0.0754/0.193 TF-51-XLPE-3x300-SWA 3x300RMC+120RMC 1.8/1.2 1.6 2.5 3.0 67.4 14742 0.0601/0.153 TYPE XLPE SWA PVC Number and crosssectional area of conductor Nominal thickness insulation Nominal thickness inner sheath Nominal diameter armour wire Nominal thickness outer sheath Approx overall diameter Approx cable weight Max conductor resistance at 20oC n x mm2 mm mm mm mm mm kg/km Ω/km TF-51-XLPE-4x1.5-SWA 4x1.5RM+1.5RM 0.7/0.7 1.0 0.9 1.8 15.4 441 12.1/12.1 TF-51-XLPE-4x2.5-SWA 4x2.5RM+2.5RM 0.7/0.7 1.0 0.9 1.8 16.6 529 7.41/7.41 TF-51-XLPE-4x04-SWA 4x4RM+2.5RM 0.7/0.7 1.0 1.25 1.8 18.3 746 4.61/7.41 TF-51-XLPE-4x06-SWA 4x6RMC+2.5RM 0.7/0.7 1.0 1.25 1.8 19.2 846 3.08/7.41 TF-51-XLPE-4x10-SWA 4x10RMC+4RM 0.7/0.7 1.0 1.25 1.8 21.4 1106 1.83/4.61 TF-51-XLPE-4x16-SWA 4x16RMC+6RMC 0.7/0.7 1.0 1.6 1.8 24.5 1602 1.15/3.08 TF-51-XLPE-4x25-SWA 4x25RMC+6RMC 0.9/0.7 1.0 1.6 1.8 28.2 2187 0.727/3.08 TF-51-XLPE-4x35-SWA 4x35RMC+10RMC 0.9/0.7 1.0 1.6 1.9 31.1 2748 0.524/0.268 TF-51-XLPE-4x50-SWA 4x50RM+16RMC 1.0/0.7 1.0 2.0 2.0 35.9 3778 0.387/1.15 Product code 54 TF-51-XLPE-4x70-SWA 4x70RMC+25RMC 1.1/0.9 1.2 2.0 2.2 41.0 5022 0.268/0.727 TF-51-XLPE-4x95-SWA 4x95RMC+25RMC 1.1/0.9 1.2 2.0 2.3 45.4 6333 0.193/0.727 TF-51-XLPE-4x120-SWA 4x120RMC+35RMC 1.2/0.9 1.4 2.5 2.5 51.2 8200 0.153/0.524 TF-51-XLPE-4x150-SWA 4x150RMC+50RMC 1.4/1.0 1.4 2.5 2.7 56.9 9942 0.124/0.387 TF-51-XLPE-4x185-SWA 4x185RMC+70RMC 1.6/1.1 1.6 2.5 2.8 62.4 12079 0.0991/0.268 TF-51-XLPE-4x240-SWA 4x240RMC+95RMC 1.7/1.1 1.6 2.5 3.0 69.7 15181 0.0754/0.193 TF-51-XLPE-4x300-SWA 4x300RMC+120RMC 1.8/1.2 1.6 2.5 3.2 75.3 18264 0.0601/0.153 Leader in heavy duty industrial cables TYPE EMV 0.6/1 kV EMV 0.6 to 1 kV Motor power supply flexible rubber cables (VSD) Other industrial applications Construction Conductors Annealed flexible stranded bare copper Class 6 or 5 to IEC 60228, HD 383 Separator A suitable tape separator between the conductor and insulation Insulation Ethylene-propylene rubber (EPR) type 3GI3 in accordance to DIN VDE 0207 p. 20 Circuit indetification white, blue, red, earth: green-yellow Assembly 3 power cores + one earth (for 4mm2) or 3 power cores and 3 earth cores laid up around rubber filler wrapped of polyester tape Internal jacket Ethylene propylene thermosetting compound type EI 4 acc. DIN VDE 0207 part 20. Color natural Concentric screen The wrap aluminium tape (one side polyester covered) + tinned copper wires (diameter 0.25, 0.30, 0.40 mm) applied in the form of braid. Covering min. 80% Outer jacket A synthetic thermosetting compound type 5GM3 acc. DIN VDE 0207 part 21 Colour of outer jacket Black Flame propagation IEC 60332-1-2:2004, EN 60332-1-2:2004 FEATURES Special composite concentric screen Flame retardant 56 Temperature range for mobile application -30 to +90˚C, for fixed -40˚C to +90˚C Heat, ozone, oil resistance Ink jet printed for easy identification 500m on drums. Other forms of packing and delivery are available on request Specifications & Standards: DIN VDE 0250 p. 812 TYPE EMV 0.6/1 kV Size 57 Stranding of power conductor Stranding of earth conductor Nominal diameter under screen Nominal outer diameter Approx. weight of cable mm mm kg/km 13.50 18.60 572 3x4+4 203/0.15 203/0.15 3x6+3x1.5 185/0.20 28/0.25 15.90 18.90 652 3x6 76/0.30 - 15.90 18.90 563 3x10+3x1.5 312/0.20 28/0.25 17.40 23.50 876 3x16+3x2.5 484/0.20 45/0.25 18.00 23.10 987 3x25+3x4 777/0.20 52/0.30 22.80 28.10 1434 3x35+3x6 1094/0.20 182/0.20 26.40 31.70 1860 3x50+3x10 1552/0.20 312/0.20 31.70 38.00 2710 3x70+3x10 2070/0.20 301/0.20 34.00 43.30 3810 3x95+3x16 2928/0.20 484/0.20 39.40 46.70 4526 3x120+3x16 1554/0.30 470/0.20 42.00 49.90 5689 3x150+3x25 1118/0.40 777/0.20 48.20 56.50 6846 TYPE SINGLE CONDUCTOR POWER CABLE 0.6/1 kV, 110˚C SINGLE CONDUCTOR POWER CABLE 0.6 to 1kV Wiring machine, screened, rubber insulated and sheathed cable Construction Conductors Annealed plain copper conductor Class 6 to IEC 60228 Separator If needed a suitable tape separator between the conductor and insulation Insulation EPR thermosetting compound type R-E-110 Outer sheath Halogen free, low smoke thermosetting compound E-110-R Colour of outer sheath Orange Standard marking Ink jet printed. For example: TF Kable 3 R-E-110 1x95 mm2 0.6/1kV 2012 FEATURES Halogen free, heat resistance Oil, chemical resistance, flame retardant UV and weather resistant Temperature range -25˚C to +110˚C Ink jet printed for easy identification 1000m on drums. Other forms of packing and delivery are available on request Specifications & Standards: AS/NZS 5000.1, IEC 60228, AS/NZS 3808, AS/NZS3008, AS/NZS3008, AS/NZS1660.5.2, AS/NZS 1660.5.3, IEC 61034-2, IEC 60754-2, IEC 60332-1 58 TYPE SINGLE CONDUCTOR POWER CABLE 59 Nominal O.D. over insulation Overall diameter Short circuit current Number and crosssection area Stranding mm2 n x mm mm 1x16 470x0.2 6.6 9.3 10.3 202 2.1 6.7 105 1x25 726x0.2 8.1 10.8 11.9 293 3.3 10.4 145 Approx. weight Min. Max. mm 1 sec. kg/km 0.1 sec. kA Current rating (Amps) A 1x35 1040x0.2 9.4 12.1 13.3 390 4.8 15.2 175 1x50 1499x0.2 11.0 13.7 15.0 535 6.6 20.9 215 1x70 2165x0.2 12.8 15.5 17.1 725 9.2 29.2 270 1x95 2745x0.2 15.0 17.9 19.5 870 12.5 39.7 340 1x120 1554x0.3 16.9 19.8 21.5 1205 15.8 50.1 395 1x150 1961x0.3 18.9 22.1 23.9 1500 19.8 62.6 455 1x185 2331x0.3 21.1 24.4 26.5 1840 24.4 77.2 530 1x240 3172x0.3 23.5 27.1 29.3 2350 31.7 100.2 630 1x300 3965x0.3 28.2 29.9 32.4 2915 39.8 125.9 730 1x400 5246x0.3 29.6 33.5 36.3 3817 52.8 167.0 850 1x500 6588x0.3 33.1 37.2 40.3 4805 66.0 208.7 980 1x630 4880x0.4 40.2 41.0 48.0 6480 83.2 263.0 1147 TYPE H07RN-F 450/750 V SUB H07RN-F SUB 450 to 750 V Flexible rubber insulated and sheathed cables Construction Conductors Annealed flexible stranded tin coated class 5 to EN 60228 Separator A suitable tape separator between the conductor and insulation Insulation Ethylene-propylene rubber (EPR) type EI4 in acc. to EN 50363-1 Circuit identification Twin 3-core 4-core 5-core Above 5-core Blue and brown Green-yellow, blue, brown Green-yellow, brown, black, grey Green-yellow, blue, brown black, grey Green-yellow, other cores black with white numbering Colour coding of power conductors comply to HD 308, DIN VDE 0293-308 Internal jacket A synthetic thermosetting compound type EM3 in acc. to EN 50363-2-1 (above 2, 3, 4, 5 x 6mm2 and 1 x 50mm2) Outer jacket A synthetic thermosetting compound type EM2 in acc. to EN 50363-2-1 Colour of outer jacket Black or other colours can be provided Flame propagation EN 60332-1-2:2004, IEC 60332-1-2:2004 FEATURES Excellent flexibility Flame retardant Temperature range -25˚C to +90˚C 60 For fixed protected installation -40˚C to +90˚C UV, sunlight, ozone and oil resistant Ink jest printed for easy identification 1000m on drums. Other forms of packing and delivery are available on request Specifications & Standards: EN 50525-2-21, BBJ HAR TYPE H07RN-F 450/750 V Nominal thickness of jacket Size 61 Number x maximum diameter of wire Nominal thickness of insulation Double layer Single Internal Outer Approx. O.D. of cable Voltage drop Approx. weight of cable Maximum conductor resistance at 20˚C n x mm2 mm mm mm mm mm mm V/A/km kg/km Ω/km 1x1.5 28x0.26 0.8 1.4 - - 5.7 23.73 49 13.7 1x2.5 45x0.26 0.9 1.4 - - 6.4 14.22 65 8.21 1x4 51x0.31 1.0 1.5 - - 7.3 8.82 89 5.09 1x6 76x0.31 1.0 1.6 - - 7.9 5.88 114 3.39 1x10 74x0.41 1.2 1.8 - - 9.8 3.38 178 1.95 1x16 116x0.41 1.2 1.9 - - 11.1 2.16 248 1.24 1x25 180x0.41 1.4 2.0 - - 12.9 1.39 356 0.795 1x35 254x0.41 1.4 2.2 - - 14.3 0.99 476 0.565 1x50 364x0.41 1.6 2.4 - - 16.8 0.70 657 0.393 1x70 514x0.51 1.6 - 1.0 1.6 19.0 0.51 884 0.277 1x95 684x0.51 1.8 - 1.1 1.7 21.9 0.40 1156 0.210 1x120 870x0.51 1.8 - 1.2 1.8 23.4 0.33 1420 0.164 1x150 1092x0.51 2.0 - 1.3 1.9 26.0 0.28 1762 0.132 1x185 1325x0.51 2.2 - 1.4 2.0 29.1 0.24 2145 0.108 1x240 1752x0.51 2.4 - 1.4 2.1 31.2 0.20 2720 0.0817 1x300 2203x0.51 2.6 - 1.4 2.2 35.4 0.19 3385 0.0654 1x400 2904x0.51 2.8 - 1.5 2.3 38.4 0.17 4196 0.0495 1x500 3679x0.61 3.0 - 1.6 2.4 43.5 0.16 5431 0.0391 1x630 4880x0.61 3.0 - 1.6 2.5 48.4 0.15 6300 0.0292 2x1 29x0.21 0.8 1.3 - - 7.9 40.00 89 20.0 2x1.5 28x0.26 0.8 1.5 - - 8.9 27.40 116 13.7 2x2.5 45x0.26 0.9 1.7 - - 10.6 16.42 167 8.21 2x0.75 22x0.20 0.8 1.3 - - 7.9 - 80 26.7 2x4 51x0.31 1.0 1.8 - - 12.8 10.18 227 5.09 2x6 76x0.31 1.0 2.0 - - 13.7 6.78 301 3.39 2x10 74x0.41 1.2 - 1.2 1.9 18.9 3.90 559 1.95 2x16 116x0.41 1.2 - 1.3 2.0 21.6 2.49 765 1.24 2x25 180x0.41 1.4 - 1.4 2.2 25.3 1.60 1092 0.795 3x1 29x0.21 0.8 1.4 - - 8.5 34.64 107 20.0 3x1.5 28x0.26 0.8 1.6 - - 9.5 23.73 137 13.7 3x2.5 45x0.26 0.9 1.8 - - 11.3 14.22 202 8.21 3x4 51x0.31 1.0 1.9 - - 13.8 8.82 292 5.09 3x6 76x0.31 1.0 2.1 - - 15.0 5.87 390 3.39 3x10 74x0.41 1.2 - 1.3 2.0 20.2 3.38 684 1.95 3x16 116x0.41 1.2 - 1.4 2.1 23.1 2.15 944 1.24 3x25 180x0.41 1.4 - 1.5 2.3 27.1 1.38 1355 0.795 3x35 254x0.41 1.4 - 1.6 2.5 29.3 0.99 1726 0.565 3x50 364x0.41 1.6 - 1.8 2.7 35.2 0.69 2452 0.393 3x70 514x0.51 1.6 - 1.9 2.9 39.7 0.50 3253 0.277 TYPE H07RN-F 450/750 V Nominal thickness of jacket Size 62 Number x maximum diameter of wire Nominal thickness of insulation Double layer Single Internal Outer Approx. O.D. of cable Voltage drop Approx. weight of cable Maximum conductor resistance at 20˚C n x mm2 mm mm mm mm mm mm V/A/km kg/km Ω/km 3x95 684x0.51 1.8 - 2.1 3.2 46.1 0.39 4303 0.210 3x120 870x0.51 1.8 - 2.2 3.4 49.0 0.31 5191 0.164 3x150 1092x0.51 2.0 - 2.4 3.6 54.7 0.26 6455 0.132 3x185 1325x0.51 2.2 - 2.5 3.9 61.1 0.23 7906 0.108 3x240 1752x0.51 2.4 - 2.8 4.3 66.6 0.18 10027 0.0817 3x300 2203x0.51 2.6 7.7 3.1 4.6 77.0 0.16 12300 0.0654 4x1 29x0.21 0.8 1.5 - - 9.4 34.64 131 20.0 4x1.5 28x0.26 0.8 1.7 - - 10.4 23.73 167 13.7 4x2.5 45x0.26 0.9 1.9 - - 12.5 14.22 247 8.21 4x4 51x0.31 1.0 2.0 - - 14.3 8.82 340 5.09 4x6 76x0.31 1.0 2.3 - - 16.3 5.87 463 3.39 4x10 74x0.41 1.2 - 1.4 2.0 22.1 3.38 831 1.95 4x16 116x0.41 1.2 - 1.4 2.2 25.3 2.15 1166 1.24 4x25 180x0.41 1.4 - 1.6 2.5 30.1 1.38 1711 0.795 4x35 254x0.41 1.4 - 1.7 2.7 32.5 0.99 2190 0.565 4x50 364x0.41 1.6 - 1.9 2.9 37.8 0.69 3101 0.393 4x70 514x0.51 1.6 - 2.0 3.2 44.2 0.50 4143 0.277 4x95 684x0.51 1.8 - 2.3 3.6 49.6 0.39 5517 0.210 4x120 870x0.51 1.8 - 2.4 3.6 54.4 0.31 6611 0.164 4x150 1092x0.51 2.0 - 2.6 3.9 60.9 0.26 82.44 0.132 4x185 1325x0.51 2.2 - 2.8 4.2 68.2 0.23 10113 0.108 4x240 1752x0.51 2.4 - 3.1 4.6 74.1 0.18 12838 0.0817 5x1 29x0.21 0.8 1.6 - - 10.3 34.64 159 20.0 5x1.5 28x0.26 0.8 1.8 - - 11.5 23.73 206 13.7 5x2.5 45x0.26 0.9 2.0 - - 13.7 14.22 304 8.21 5x4 51x0.31 1.0 2.2 - - 15.9 8.82 426 5.09 5x6 76x0.31 1.0 2.5 - - 18.1 5.87 579 3.39 5x10 74x0.41 1.2 - 1.4 2.2 24.3 3.38 1024 1.95 5x16 116x0.41 1.2 - 1.5 2.4 28.7 2.15 1440 1.24 5x25 180x0.41 1.4 - 1.7 2.7 33.3 1.38 2105 0.795 5x35 254x0.41 1.4 - 1.8 2.8 36.2 0.99 2618 0.565 5x50 364x0.41 1.6 - 2.0 3.2 43.9 0.69 3659 0.386 5x70 514x0.51 1.6 - 2.2 3.4 49.4 0.50 5031 0.277 5x95 684x0.51 1.8 - 2.6 3.9 58.0 0.39 6726 0.210 6x1.5 28x0.26 0.8 2.5 - - 13.9 27.40 288 13.7 6x2.5 45x0.26 0.9 2.7 - - 16.3 16.42 412 8.21 6x4 51x0.31 1.0 2.9 - - 18.8 10.18 567 5.09 TYPE H07RN-F 450/750 V Nominal thickness of jacket Size 63 Number x maximum diameter of wire Nominal thickness of insulation Double layer Single Internal Outer Approx. O.D. of cable Voltage drop Approx. weight of cable Maximum conductor resistance at 20˚C n x mm2 mm mm mm mm mm mm V/A/km kg/km Ω/km 7x1.5 28x0.26 0.8 2.5 - - 14.8 40.00 327 13.7 7x2.5 45x0.26 0.9 2.7 - - 17.5 27.40 471 8.21 7x4 51x0.31 1.0 2.9 - - 20.1 16.42 650 5.09 8x1.5 28x0.26 0.8 2.6 - - 16.2 27.40 395 13.7 8x2.5 45x0.26 0.9 2.8 - - 19.1 16.42 569 8.21 8x4 51x0.31 1.0 3.1 - - 22.2 10.18 795 5.09 9x1.5 28x0.26 0.8 2.7 - - 17.3 27.40 403 13.7 9x2.5 45x0.26 0.9 3.0 - - 20.60 16.42 587 8.21 10x1.5 28x0.26 0.8 2.8 - - 17.5 27.40 432 13.7 10x2.5 45x0.26 0.9 3.0 - - 20.6 16.42 620 8.21 10x4 51x0.31 1.0 3.3 - - 23.9 10.18 866 5.09 12x1.5 28x0.26 0.8 2.9 - - 18.2 27.40 484 13.7 12x2.5 45x0.26 0.9 3.1 - - 22.1 16.42 708 8.21 12x4 51x0.31 1.0 3.5 - - 25.0 10.18 988 5.09 14x1.5 28x0.26 0.8 2.9 - - 19.0 27.40 535 13.7 14x2.5 45x0.26 0.9 3.2 - - 22.6 16.42 785 8.21 15x2.5 45x0.26 0.9 3.3 - - 23.8 16.42 865 8.21 16x1.5 28x0.26 0.8 3.0 - - 20.0 27.40 603 13.7 16x2.5 45x0.26 0.9 3.3 - - 23.8 16.42 886 8.21 18x1.5 28x0.26 0.8 3.2 - - 22.3 27.40 684 13.7 18x2.5 45x0.26 0.9 3.5 - - 25.3 16.42 1001 8.21 18x4 51x0.31 1.0 3.9 - - 29.5 10.18 1417 5.09 19x1.5 28x0.26 0.8 3.1 - - 22.0 27.40 722 13.7 19x0.5 45x0.26 0.9 3.4 - - 26.2 16.42 1062 8.21 24x1.5 28x0.26 0.8 3.5 - - 24.9 27.40 888 13.7 24x2.5 45x0.26 0.9 3.9 - - 29.8 16.42 1313 8.21 27x1.5 28x0.26 0.8 3.5 - - 25.4 27.40 954 13.7 27x2.5 45x0.26 0.9 3.9 - - 30.4 16.42 1415 8.21 36x1.5 28x0.26 0.8 3.8 - - 28.5 27.40 1233 13.7 36x2.5 45x0.26 0.9 4.3 - - 34.3 16.42 1845 8.21 37x2.5 45x0.26 0.9 4.3 - - 34.8 16.42 1860 8.21 TYPE H07RN-F 450/750 V Current rating in free air at air temperature of 30˚C and conductor temperature of 85˚C Cross section Single core Two cores Three cores mm2 1.5 Four cores Five cores Seven cores 21 21 15 A 24 23 23 2.5 32 32 32 29 29 23 4 42 42 42 38 38 28 6 55 55 55 50 50 55 10 77 77 77 67 67 74 16 101 101 101 91 91 - 25 133 133 133 121 121 - 35 165 - 165 149 - - 50 202 - 202 183 - - 70 250 - 260 231 - - 95 300 - 310 280 - - 120 360 - 370 324 - - 150 412 - 430 372 - - 185 465 - 490 423 - - 240 550 - 580 501 - - 300 630 - 680 - - - 500 831 - - - - - Correction factor for ambient temperature 64 Temperature of air ˚C 35 40 45 50 55 60 65 70 75 80 Correct factor 0.95 0.90 0.85 0.82 0.76 0.70 0.64 0.57 0.50 0.40 TYPE NSGAFÖU 0.6/1, 1.8/3, 3.6/6 kV SINGLE CONDUCTOR RUBBER INSULATED AND SHEATED FLEXIBLE POWER CABLES 0.6/1, 1.8/3, 3.6/6 kV Heavy-duty flexible single core power cables for mobile and fixed applications Other industrial applications Construction Conductors Annealed flexible stranded tin coated or bare copper class 5 to IEC 60228, HD 383 Separator A suitable tape between the conductor and insulation Insulation Ethylene-propylene rubber (EPR) type 3GI3 to DIN VDE 0207 p. 20 Outer jacket A synthetic thermosetting compound type 5GM3 to DIN VDE 0207 p. 21 Colour of outer jacket Black or other colours can be provided FEATURES Excellent flexibility Water resistant and flame retardant Temperature range -25˚C to +90˚C. For fixed installation lowest temperature is -40˚C UV, sunlight, ozone and oil resistant Ink jet printed for easy indetification 1000m on drums. Other forms of packing and delivery are available on request Specifications & Standards: DIN VDE 0250 p. 602 65 TYPE NSGAFÖU 0.6/1, 1.8/3, 3.6/6 kV Number and cross-sectional area of conductor Nominal thickness of insulation Nominal thickness of sheath Approx. overall diameter Approx. net weight of cables Current-carrying capacity at 30˚C in air mm2 mm mm mm kg/km A 0.6/1 kV 1x1.5 0.8 0.8 4.7 35 30 1x2.5 0.9 0.8 5.4 49 41 1x4 1.0 0.8 6.1 67 55 1x6 1.0 0.8 6.6 88 70 1x10 1.2 0.8 8.0 137 98 1x16 1.2 0.8 10.1 207 132 1x25 1.4 0.8 11.7 298 176 1x35 1.4 1.0 12.8 399 218 1x50 1.6 1.0 15.2 560 276 1x70 1.6 1.0 17.0 754 347 1x95 1.8 1.0 19.5 983 416 1x120 1.8 1.0 20.6 1213 488 1x150 2.0 1.0 22.8 1501 566 1x185 2.2 1.2 25.9 184 644 1x240 2.4 1.2 27.8 2365 775 1x300 2.6 1.2 31.8 2945 898 1x400** 2.6 1.2 34.1 3794 1060 1.8/3 kV 66 1x1.5 1.3 0.8 6.0 44 30.26 1x2.5 1.3 0.8 6.2 57 18.13 1x4 1.3 0.8 6.7 74 11.24 1x6 1.3 0.8 7.3 99 7.49 1x10 1.5 0.8 8.6 150 4.31 1x16 1.5 0.8 10.1 215 2.74 1x25 1.8 1.0 12.3 323 1.76 1x35 1.8 1.0 13.0 413 1.26 1x50 1.8 1.0 15.0 566 0.88 1x70 1.8 1.0 16.8 761 0.63 1x95 2.2 1.0 19.7 1006 0.49 1x120 2.2 1.0 20.8 1235 0.39 1x150 2.2 1.2 23.6 1576 0.33 1x185 2.4 1.2 25.7 1853 0.28 1x240 2.6 1.2 29.4 2479 0.23 1x300 2.8 1.2 31.9 2953 0.21 1x400** 3.1 1.4 34.5 3853 0.18 1x500** 3.4 1.6 43.2 4974 0.16 0.8 7.9 78 3.6/6 kV 1x1** 0.26 2.6 1x1.5 0.26 2.6 0.8 8.0 84 1x2.5 0.26 2.6 0.8 8.8 99 1x4 0.31 2.6 0.8 9.8 74 1x6 0.31 2.6 0.8 10.8 99 1x10 0.41 2.6 0.8 11.5 150 TYPE NSGAFÖU 0.6/1, 1.8/3, 3.6/6 kV Number and cross-sectional area of conductor Nominal thickness of insulation Nominal thickness of sheath Approx. overall diameter Approx. net weight of cables Current-carrying capacity at 30˚C in air mm2 mm mm mm kg/km A 1.0 12.7 282 0.6/1 kV 1x16 2.6 1x25 0.41 2.9 1.0 14.5 400 1x35 0.41 2.9 1.0 16.5 600 1x50 0.41 2.9 1.0 18.0 740 1x70 0.51 2.9 1.0 22.0 861 1x95 0.51 3.2 1.0 24.0 1106 1x120 0.51 3.2 1.2 24.5 1335 1x150 0.51 3.2 1.2 25.3 1676 1x185 0.51 3.2 1.2 27.3 1947 1x240** 0.51 3.4 1.4 29.6 2571 1x400** 0.51 3.4 1.4 35.5 3909 **Based on DIN VDE 0250 p. 602 as (N)SGAFOU 67 0.41 TYPE 07RN-F/CY 450/750 V RUBBER INSULATED AND JACKETED CABLES WITH CONCENTRIC TINNED COPPER SCREEN 450/750 V In mines, quarries and industrial areas, indoors and outdoors, for higher mechanical stresses as flexible cable and as trailing cable for mobile current consumers Other industrial applications Construction Conductors Annealed flexible stranded tin coated class 5 to IEC 60228 Separator A suitable tape separator between the conductor and insulation Insulation EPR thermosetting compound exceed parameters of type EI4 in accordance to EN 50363-1 Circuit identification Colour coding of power conductors comply to HD 308 Internal jacket EPR thermosetting compound type EI4 in accordance to EN 50363-1 Concentric screen The wrap of aluminum tape (one side polyester coating) + the braid of tinned copper wires. Covering: minimum 82% Outer jacket Heavy duty thermosetting CPE compound type EM2 in accordance to EN 50363-2-1 Colour of outer jacket Black FEATURES Concentric copper screen between layer Flame retardant and oil resistant jacket Bending radius for fixed max. 10 x cable diameter, for mobile application 15 x cable diameter Temperature range -25˚C to +90˚C. For fixed installation lowest temperature is -30˚C 68 Ink jet printed for easy indetification 500m on drums. Other forms of packing and delivery are available on request Specifications & Standards: EN 50525-2-21 TYPE 07RN-F/CY 450/750 V Nominal thickness of jacket Size 69 Maximum diameter of wire Nominal thickness of insulation Double layer Single Internal Outer Approx. O.D. of cable Approx. weight of cable Maximum conductor resistance 20˚C n x mm2 mm mm mm mm mm mm kg/km Ω/km 5G1.5 0.26 0.8 - 1.0 2.4 16.2 432 13.7 5G2.5 0.26 0.9 - 1.0 2.4 18.0 526 8.21 5G4 0.31 1.0 - 1.3 3.0 22.4 734 5.09 5G6 0.31 1.2 - 1.3 3.0 23.7 877 3.39 5G10 0.41 1.2 - 1.4 3.0 28.2 1291 1.95 4G25 0.41 1.4 - 1.7 3.0 35.8 2323 0.795 4G35 0.41 1.4 - 1.8 2.8 37.5 2940 0.565 TYPE NSGAFÖU/CY 1.8/3.3 kV SINGLE CONDUCTOR EPR INSULATED, Cu SCREENED AND CPE SHEATHED POWER CABLES 1.8/3.3 kV Heavy-duty flexible single core power cable with concentric screen for mobile and fixed applications Other industrial applications Construction Conductors Annealed flexible stranded tin coated or bare copper class 5 to IEC 60228, HD 383 Separator A suitable tape separator between the conductor and insulation Insulation Ethylene-propylene rubber (EPR) type 3GI3 to DIN VDE 0207 p. 20 Concentric screen The braid of tinned copper wires. Covering 82% Outer jacket A synthetic thermosetting compound type 5GM3 to DIN VDE 0207 p. 21 Colour of outer jacket Black or other colours can be provided FEATURES Concentric copper screen between layer Flame retardant and oil resistant jacket Bending radius for fixed max. 10 x cable diameter, for mobile application 15 x cable diameter Temperature range -25˚C to +90˚C. For fixed installation lowest temperature is -30˚C Ink jet printed for easy indetification 500m on drums. Other forms of packing and delivery are available on request Specifications & Standards: DIN VDE 0250 p. 602 70 Number and crosssectional area of conductor Nominal thickness of insulation Nominal thickness of sheath Approx. overall diameter Approx. net weight of cables mm2 mm mm mm 1x120 2.2 1.4 23.0 1x150 2.2 1.4 1x185 2.4 1x240 2.6 1x400 3.1 Current-carrying capacity at 30˚C in air Conductor resistance at 20˚C kg/km A Ω/km 1446 488 0.164 24.8 1735 566 0.132 1.4 27.4 2082 644 0.108 1.4 29.3 2624 775 0.0817 2.0 37.1 4223 1060 0.0495 CABLE DRUMS SAMPLE DATA OF WOODEN CABLE DRUMS Sample data regarding wooden cable drums Type ØD Ø D1 B L Weight (kg) 060T 600 300 400 510 20 070T 700 350 400 510 26 080T 800 400 400 510 33 08AT 800 400 560 670 36 090T 900 450 560 690 54 100T 1000 500 560 700 71 10AT 1000 500 650 790 73 120T 1200 600 710 845 104 12AT 1200 630 710 845 120 140T 1400 700 710 865 153 150T 1500 800 710 870 180 160T 1600 800 900 1055 233 16AT 1600 1000 900 1055 280 180T 1800 1000 900 1070 311 200T 2000 1200 900 1090 442 20AT 2000 1000 900 1090 409 20BT 2000 1250 1100 1310 465 210T 2100 1100 1300 1540 554 220T 2200 1200 1100 1335 616 22AT 2200 1400 1250 1485 681 22BT 2200 1600 1250 1460 735 22MT 2200 1400 1100 1335 663 240T 2400 1400 1210 1440 754 24AT 2400 1200 1210 1440 706 24BT 2400 1000 1500 1755 762 250T 2500 1600 1250 1505 951 25AT 2500 1600 1250 1550 951 280T 2800 1800 1400 1675 1332 D D1 71 B L Note: Figures used are indicative and may vary due to manufacturing tolerances, so should only be used as guidance. Cable wooden drums are standardized, but we also offer special wooden drums with different dimensions on customer request. PRINCIPAL ELASTOMERIC MATERIALS USED IN REELING AND TRAILING CABLES INSULATION The elastomer used for the insulation of all reeling and trailing cables to AS/NZS 1802 and AS/NZS 2802 is a compound based on ethylene propylene rubber (EPR) known in the Australian Standards as R-EP-90 or, in the case of Class 1 cables to AS/NZS 2802, as XR-EP-90, the latter being an electrically superior grade material when compared with R-EP-90 and mechanically different. Typical properties of TF Kable Ethylene Propylene Rubber (EPR) insulation Test (per AS/NZS 1802/AS/NZS 2802) R-EP-90 Typical achieved Specified value XR-EP-90 Typical achieved Specified value 1. Tensile strength (MPa) 6.5 ≥ 4.2 10 ≥ 8.5 2. Elongation at rupture (percent) 400 ≥ 200 300 ≥ 200 1. Tensile strength (percentage of values found in unaged specimens) 100 ≥ 70 95 ≥ 75 2. Elongation at rupture (percentage of values found in unaged specimens) 90 ≥ 70 85 ≥ 75 1. Elongation under load (percent) 10 ≤ 175 20 ≤ 175 2. Residual elongation after cooling (percent) 0 ≤ 15 0 ≤ 15 A. Mechanical tests without ageing B. Mechanical tests after ageing in air oven C. Hot set test D. Electrical characteristics 1. Insulation resistance constant (ki) at room temperature (GΩ.m) ≤ 1.1/1.1kV ≥ 3.3/3.3kV 6000 ≥ 1500 ≥ 4000 60000 ≥ 4000 80 ≥ 1.5 ≥ 4.0 1600 ≥ 4.0 2. Insulation resistance constant (ki) at 90˚C (GΩ.m) SHEATH The elastomer used for the sheathing (inner and outer) of all reeling and trailing cables to AS/NZS 1802 and AS/NZS 2802 is a compound based on heavy/extra heavy duty polychloroprene (PCP). For all cables, in addition to the requirements specified in AS/NZS 1802, the PCP compound meets the most stringent requirements applicable for XHD-85-PCP specified for Class 1 cables in AS/NZS 2802. Black PCP sheath is recommended. Typical properties of TF Kable PCP sheath Test (except for D and E, per AS/NZS 1802/AS/NZS 2802) 72 Typical Achieved All Black PCP sheaths Specified value GP-85-PCP HD-85-PCP XHD-85-PCP A. Mechanical tests without ageing CSP PCP 1. Tensile strength (MPa) 18.5 18 ≥ 8.5 ≥ 11 ≥ 12.5 2. Elongation at rupture (percent) 330 500 ≥ 250 ≥ 250 ≥ 300 3. Tear resistance (N/mm) 12 12 - ≥5 ≥7 1. Tensile strength (MPa) 14.0 13 ≥ 6.2 ≥ 8.5 ≥ 8.5 2. Elongation at rupture (percent) 350 400 ≥ 125 ≥ 125 ≥ 150 1. Tensile strength (percentage of values found in unaged specimens) 80 80 ≥ 60 ≥ 60 ≥ 60 2. Elongation at rupture (percentage of values found in unaged specimens) 95 95 ≥ 60 ≥ 60 ≥ 60 D. Hardness (IRHD) 71 71 - - - E. Oxygen index 32 32 - - - B. Mechanical tests after ageing in air oven C. Oil immersion test SEMICONDUCTIVE CRADLE, EARTH COVERING AND SCREEN FOR CORE ASEMBLY The semiconductive elastomer used in the manufacture of the reeling and trailing cable cradle, the interstitial earth conductor covering (other than for Type 412) and the screen for core assembly (Types 241, 245, 275 and 441 only) is a compound based on polychloroprene (PCP) which, unlike in the case of the semiconductive materials in many imported cables, does not propagate flame and is oil and wear resistant. Typical properties of TF Kable semiconductive chlorosulphonated polyethylene (CSP) Test (except for D, per AS/NZS 1802/AS/NZS 2802) Typical Achieved Specified value 1. Tensile strength (MPa) 12 ≥ 8.5 2. Elongation at rupture (percent) 280 ≥ 200 5 ≤ 20 8 ≥ 6.2 A. Mechanical tests without ageing 3. Permanent set (percent) B. Mechanical tests after ageing in air oven 1. Tensile strength (MPa) 2. Elongation at rupture (percent) 73 200 ≥ 50 C. Volume resistivity at 23˚C (Ω.m) 0.05 ≤ 1.0 D. Oxygen index 26 - RECOMMENDED LIMITS TO REELING AND TRAILING CABLE OPERATION Although TELE-FONIKA Kable cables perform satisfactorily under more severe conditions, in the interest of ensuring good service life and reliability it is recommended that the following limits be observed: TEMPERATURE Maximum continuous conductor temperature: 90˚C Minimum continuous conductor temperature: -25˚C TENSION Maximum continuous working tension: 0.02kN/mm2 of total cross-sectional area of main conductors* BARREL SIZE OF REELS Often cables are reeled for storage or relocation and therefore are not energised while on the reel. The minimum diameter of the barrel of the reel, in multiples of cable overall diameter, shall be no less than: 1kV cables 12D Reeling and Trailing, 3.3kV & above 15D BENDING RADII AND CHANGES IN DIRECTION Reeling and trailing cable bending radii, in multiples of cable overall diameter, shall be not less than: Situation Fixed installation Cables rated 1.1/1.1kV Cables rated 3.3/3.3kV and above 4 6 Free flexing (not under tension) 6 10 Permanently repeating reeling 10 12 At deflection sheaves or rollers 15 20 Change in the cable axial direction when related to the cable drum axis, i.e. change from right angle to that parallel to the drum axis (or similar) should be avoided. Where unavoidable, the straigth section of cable between the deflection sheave or roller where change in axial direction takes place and the preceding bending point, shall be not less than 20 times the overall diameter of the cable. Same minimum straight section applies where cable is subjected to an "S" bend. 74 * Any reduced size conductors (e.g. any interstitial conductors), and screens do not effectively contribute to the strength of the cable and hence should not be included in the calculation. NOTES 75 TELE-FONIKA Kable cannot be held responsible for any printing errors, and reserves the right to change the contents of the information without prior notice. All Rights Reserved – TELE-FONIKA Kable Sp. z o.o. S.K.A. Edition II TELE-FONIKA Kable Sp. z o.o. S.K.A. Wielicka Street No. 114, 30-663 Cracow T: (+48) 12 652 51 02, (+48) 12 652 59 31, (+48) 12 652 59 37 F: (+48) 12 652 59 28 export@tfkable.pl www.tfkable.com