PCS-902 Line Distance Relay Instruction Manual NR Electric Co., Ltd. Preface Preface Introduction This guide and the relevant operating or service manual documentation for the equipment provide full information on safe handling, commissioning and testing of this equipment. Documentation for equipment ordered from NR is dispatched separately from manufactured goods and may not be received at the same time. Therefore, this guide is provided to ensure that printed information normally present on equipment is fully understood by the recipient. Before carrying out any work on the equipment, the user should be familiar with the contents of this manual, and read relevant chapter carefully. This chapter describes the safety precautions recommended when using the equipment. Before installing and using the equipment, this chapter must be thoroughly read and understood. Health and Safety The information in this chapter of the equipment documentation is intended to ensure that equipment is properly installed and handled in order to maintain it in a safe condition. When electrical equipment is in operation, dangerous voltages will be present in certain parts of the equipment. Failure to observe warning notices, incorrect use, or improper use may endanger personnel and equipment and cause personal injury or physical damage. Before working in the terminal strip area, the equipment must be isolated. Proper and safe operation of the equipment depends on appropriate shipping and handling, proper storage, installation and commissioning, and on careful operation, maintenance and servicing. For this reason, only qualified personnel may work on or operate the equipment. Qualified personnel are individuals who: Are familiar with the installation, commissioning, and operation of the equipment and of the system to which it is being connected; Are able to safely perform switching operations in accordance with accepted safety engineering practices and are authorized to energize and de-energize equipment and to isolate, ground, and label it; Are trained in the care and use of safety apparatus in accordance with safety engineering practices; Are trained in emergency procedures (first aid). Instructions and Warnings The following indicators and standard definitions are used: PCS-902 Line Distance Relay i Date: 2019-03-01 Preface DANGER! means that death, severe personal injury and considerable equipment damage will occur if safety precautions are disregarded. WARNING! means that death, severe personal and considerable equipment damage could occur if safety precautions are disregarded. CAUTION! means that light personal injury or equipment damage may occur if safety precautions are disregarded. NOTICE! is particularly applies to damage to device and to resulting damage of the protected equipment. DANGER! NEVER allow a open current transformer (CT) secondary circuit connected to this device while the primary system is live. Open CT circuit will produce a dangerously high voltage that cause death. WARNING! ONLY qualified personnel should work on or in the vicinity of this device. This personnel MUST be familiar with all safety regulations and service procedures described in this manual. During operating of electrical device, certain part of the device is under high voltage. Severe personal injury and significant device damage could result from improper behavior. WARNING! Do NOT touch the exposed terminals of this device while the power supply is on. The generated high voltage causes death, injury, and device damage. WARNING! Thirty seconds is NECESSARY for discharging the voltage. Hazardous voltage can be present in the DC circuit just after switching off the DC power supply. CAUTION! Earthing Securely earthed the earthing terminal of the device. Operating environment ONLY use the device within the range of ambient environment and in an ii PCS-902 Line Distance Relay Date: 2019-03-01 Preface environment free of abnormal vibration. Ratings Check the input ratings BEFORE applying AC voltage/current and power supply to the device. Printed circuit board Do NOT attach or remove printed circuit board if the device is powered on. External circuit Check the supply voltage used when connecting the device output contacts to external circuits, in order to prevent overheating. Connection cable Carefully handle connection cables without applying excessive force. NOTICE! The firmware may be upgraded to add new features or enhance/modify existing features, please MAKE SURE that the version of this manual is compatible with the product in your hand. Copyright © 2019 NR. All rights reserved. We reserve all rights to this document and to the information contained herein. Improper use in particular reproduction and dissemination to third parties is strictly forbidden except where expressly authorized. The information in this manual is carefully checked periodically, and necessary corrections will be included in future editions. If nevertheless any errors are detected, suggestions for correction or improvement are greatly appreciated. We reserve the rights to make technical improvements without notice. NR ELECTRIC CO., LTD. Tel: +86-25-87178888 Headquarters: 69, Suyuan Avenue, Jiangning, Nanjing 211102, China Manufactory: 18, Xinfeng Road, Jiangning, Nanjing 211111, China P/N: ZL_PCS-902_X_Instruction Manual_EN_Overseas General_X PCS-902 Line Distance Relay Fax: +86-25-87178999 Website: www.nrec.com/en Version: R3.10 iii Date: 2019-03-01 Preface Documentation Structure The manual provides a functional and technical description of this relay and a comprehensive set of instructions for the relay’s use and application. All contents provided by this manual are summarized as below: 1 Introduction Briefly introduce the application, functions and features about this device. 2 Technical Data Introduce the technical data about this device, such as electrical specifications, mechanical specifications, ambient temperature and humidity range, communication port parameters, type tests, setting ranges and accuracy limits and the certifications that our products have passed. 3 Operation Theory Introduce a comprehensive and detailed functional description of all protective elements. 4 Supervision Introduce the automatic self-supervision function of this device. 5 Management Introduce the management function (measurement and recording) of this device. 6 Hardware Introduce the main function carried out by each plug-in module of this device and providing the definition of pins of each plug-in module. 7 Settings List settings including system settings, communication settings, label settings, logic links and etc., and some notes about the setting application. 8 Human Machine Interface Introduce the hardware of the human machine interface (HMI) module and a detailed guide for the user how to use this device through HMI. It also lists all the information which can be view through HMI, such as settings, measurements, all kinds of reports etc. 9 Configurable Function Introduce configurable function of the device and all configurable signals are listed. 10 Communication Introduce the communication port and protocol which this device can support, IEC60970-5-103, IEC61850 and DNP3.0 protocols are introduced in details. iv PCS-902 Line Distance Relay Date: 2019-03-01 Preface 11 Installation Introduce the recommendations on unpacking, handling, inspection and storage of this device. A guide to the mechanical and electrical installation of this device is also provided, incorporating earthing recommendations. A typical wiring connection to this device is indicated. 12 Commissioning Introduce how to commission this device, comprising checks on the calibration and functionality of this device. 13 Maintenance A general maintenance policy for this device is outlined. 14 Decommissioning and Disposal A general decommissioning and disposal policy for this device is outlined. 15 Manual Version History List the instruction manual version and the modification history records. Typographic and Graphical Conventions Deviations may be permitted in drawings and tables when the type of designator can be obviously derived from the illustration. The following symbols are used in drawings: & AND gate ≥1 OR gate Comparator BI SET EN Binary signal via opto-coupler I> Input signal from comparator with setting Input signal of logic setting for function enabling PCS-902 Line Distance Relay v Date: 2019-03-01 Preface SIG Input of binary signal except those signals via opto-coupler XXX Output signal Timer t t Timer (optional definite-time or inverse-time characteristic) 10ms 0ms Timer [delay pickup (10ms), delay dropoff (0ms), non-settable] [XXX] 0ms Timer (delay pickup, settable) 0ms [XXX] Timer (delay dropoff, settable) [XXX] [XXX] Timer (delay pickup, delay dropoff, settable) IDMT Timer (inverse-time characteristic) ---xxx is the symbol Symbol Corresponding Relationship Basic A, B, C L1, L2, L3 R, Y, B AN, BN, CN L1N, L2N, L3N RN,YN, BN ABC L123 RYB U (voltage) V U Example Ia, Ib, Ic, I0 IL1, IL2, IL3, IN IR, IY, IB, IN Ua, Ub, Uc VL1, VL2, VL3 UR, UY, UB Uab, Ubc, Uca VL12, VL23, VL31 URY, UYB, UBR U0, U1, U2 VN, V1, V2 UN, U1, U2 vi PCS-902 Line Distance Relay Date: 2019-03-01 1 Introduction 1 Introduction Table of Contents 1 Introduction ....................................................................................... 1-a 1.1 Application....................................................................................................... 1-1 1.2 Function ........................................................................................................... 1-4 1.3 Features ........................................................................................................... 1-7 List of Figures Figure 1.1-1 Typical application of PCS-902 for single circuit breaker ................................. 1-1 Figure 1.1-2 Typical application of PCS-902 for double circuit breakers .............................. 1-2 Figure 1.1-3 Functional diagram of PCS-902............................................................................ 1-3 PCS-902 Line Distance Relay 1-a Date: 2018-02-12 1 Introduction PCS-902 Line Distance Relay 1-b Date: 2018-02-12 -02-27 1 Introduction 1.1 Application PCS-902 is a digital line distance protection with the main and back-up protection functions, which is designed for overhead line or cables and hybrid transmission lines of various voltage levels. 52 52 PCS-902 Optical fibre channel or PLC channel PCS-902 Communication channel via direct dedicated fibre, MUX or PLC Figure 1.1-1 Typical application of PCS-902 for single circuit breaker In the case of main protection, PCS-902 provides dual-channels pilot distance protection (PUTT, POTT, blocking and unblocking) and pilot directional earth-fault protection (selectable for independent communication channel or sharing channel with POTT), which can clear any internal fault instantaneously for the whole line with the aid of protection signal. Deviation of power frequency component (DPFC) distance protection with fixed forward direction can perform extremely high speed operation for close-up faults. There is direct transfer trip (DTT) feature incorporated in the device. PCS-902 also includes distance protection (1 forward zones and 4 settable forward or reverse zone distance protection with selectable mho or quadrilateral characteristic, dedicated pilot distance zone for pilot distance protection), out-of-step protection, 4 stages directional earth fault protection, 4 stages directional phase overcurrent protection, 4 stages directional negative-sequence overcurrent protection, 3 stages voltage protection (under/over voltage protection), 3 stages residual overvoltage protection, 1 stage negative-sequence overvoltage protection, 4 stages frequency protection (under/over frequency protection), broken conductor protection, reverse power protection, pole discrepancy protection, breaker failure protection, thermal overload protection, and dead zone protection etc. Moreover, a backup overcurrent and earth fault protection will be automatically enabled when VT circuit fails. In addition, stub differential protection is provided for one and a half breakers arrangement when transmission line is put into maintenance. PCS-902 can be configured to support single circuit breaker application or double circuit breakers application by PCS-Explorer. If the device is applied to double circuit breakers mode, all protection functions related to the number of circuit breaker will be affected, including circuit breaker position supervision, breaker failure protection, dead zone protection, pole discrepancy protection, synchrocheck, automatic reclosure, trip logic, CT circuit supervision, control and synchrocheck for manual closing. PCS-902 Line Distance Relay 1-1 Date: 2018-02-12 1 Introduction Bus1 Single-phase voltage 52 PCS-902 Line 1 Three-phase voltage 52 Line 2 Single-phase voltage 52 Bus2 Figure 1.1-2 Typical application of PCS-902 for double circuit breakers PCS-902 has selectable mode of single-phase tripping or three-phase tripping and configurable auto-reclosing mode for 1-pole, 3-poles and 1/3-pole operation. PCS-902 with appropriate selection of integrated protection functions can be applied for various voltage levels and primary equipment such as cables, overhead lines, interconnectors and transformer feeder, etc. It also supports configurable binary inputs, binary outputs, LEDs and IEC 61850 protocol. PCS-902 Line Distance Relay 1-2 Date: 2018-02-12 -02-27 1 Introduction BUS 52 81 85 21 50/51P 50/51G 50/51Q 50GVT 50PVT 50BF 49 46BC 32R 62PD FR 59Q 21D 59G 78 59P FL Data Transmit/Receive 27P 50DZ 87STB (Only for one and a half breakers arrangement) SOTF 25 79 LINE Figure 1.1-3 Functional diagram of PCS-902 No. Function ANSI 1 Pilot protection 85 2 DPFC distance protection 21D 3 Distance protection 21 4 Out-of-step protection 78 5 Phase overcurrent protection 50/51P 6 Earth fault protection 50/51G 7 Negative-sequence overcurrent protection 50/51Q 8 Overvoltage protection 59P 9 Negative-sequence overvoltage protection 59Q 10 Residual overvoltage protection 59G 11 Undervoltage protection 27P 12 Frequency protection 81 13 Broken conductor protection 46BC 14 Reverse power protection 32R 15 Breaker failure protection 50BF 16 Thermal overload protection 49 17 Stub differential protection 87STB 18 Dead zone protection 50DZ 19 Pole discrepancy protection 62PD 20 Switch onto fault SOTF 21 Phase overcurrent protection when VT circuit failure 50PVT 22 Earth fault protection when VT circuit failure 50GVT 23 Synchronism check 25 24 Automatic reclosure 79 25 Fault recorder FR PCS-902 Line Distance Relay 1-3 Date: 2018-02-12 1 Introduction 26 Fault location FL 1.2 Function 1. Protection Function Distance protection (including eight zones) One zone DPFC distance protection with fixed forward direction One zone distance protection with fixed forward direction (including phase-to-ground and phase-to-phase, mho or quadrilateral characteristic) One zone pilot distance protection with fixed forward direction (including phase-to-ground and phase-to-phase, mho or quadrilateral characteristic) One zone pilot distance protection with fixed reverse direction (including phase-to-ground and phase-to-phase, mho or quadrilateral characteristic) Four zones distance protection with settable forward or reverse direction (including phase-to-ground and phase-to-phase, mho or quadrilateral characteristic) Load encroachment for mho and quadrilateral characteristic distance element Power swing blocking releasing, selectable for each of above mentioned zones Out-of-step protection Overcurrent protection Four stages phase overcurrent protection, selectable time characteristic (definite-time or inverse-time) and directionality (forward direction, reverse direction or non-directional) Four stages directional earth fault protection, selectable time characteristic (definite-time or inverse-time) and directionality (forward direction, reverse direction or non-directional) Four stages negative-sequence overcurrent protection, selectable time characteristic (definite-time or inverse-time) and directionality (forward direction, reverse direction or non-directional) Breaker failure protection Optional instantaneously re-tripping One stage with two delay timers Thermal overload protection Stub differential protection Dead zone protection Pole discrepancy protection Broken conductor protection PCS-902 Line Distance Relay 1-4 Date: 2018-02-12 -02-27 1 Introduction Reverse power protection Switch onto fault (SOTF) Via distance measurement elements Via dedicated earth fault element Via phase overcurrent element Backup protection when VT circuit failure Phase overcurrent protection when VT circuit failure Ground overcurrent protection when VT circuit failure Voltage protection Three stages overvoltage protection Three stages undervoltage protection Three stages residual overvoltage protection One stage negative-sequence overvoltage protection Frequency protection Four stages overfrequency protection Four stages underfrequency protection df/dt block criterion for underfrequency protection Control function Synchro-checking Automatic reclosure (single shot or multi-shot (max. 4) for 1-pole AR and 3-pole AR) Pilot scheme logic Phase-segregated communication logic of distance protection Weak infeed logic of pilot distance protection Weak infeed logic of pilot directional earth fault protection Communication scheme of optical pilot channel (Optional) Direct optical link Connection to a communication network, support G.703 and C37.94 protocol Dual-channels redundancy 2. Measurement and control function Remote control (open and closing) PCS-902 Line Distance Relay 1-5 Date: 2018-02-12 1 Introduction Synchronism check for remote and manual closing Energy metering (active and reactive energy are calculated in import respectively export direction) 3. Logic User programmable logic 4. Additional function Fault location Fault phase selection Parallel line compensation for fault location VT circuit supervision CT circuit supervision Self diagnostic DC power supply supervision Event Recorder including 1024 disturbance records, 1024 binary events, 1024 supervision events, 256 control logs and 1024 device logs. Disturbance recorder including 32 disturbance records with waveforms (The file format of disturbance recorder is compatible with international COMTRADE file.) Four kinds of clock synchronization methods Conventional PPS (RS-485): Pulse per second (PPS) via RS-485 differential level IRIG-B (RS-485): IRIG-B via RS-485 differential level PPM (DIN): Pulse per minute (PPM) via the optical coupler PPS (DIN): Pulse per second (PPS) via the optical coupler SAS SNTP (PTP): Unicast (point-to-point) SNTP mode via Ethernet network SNTP (BC): Broadcast SNTP mode via Ethernet network Message (IEC103): Clock messages through IEC103 protocol Advanced IEEE1588: Clock message via IEEE1588 IRIG-B (Fiber): IRIG-B via optical-fibre interface PPS (Fiber): Pulse per second (PPS) via optical-fibre interface PCS-902 Line Distance Relay 1-6 Date: 2018-02-12 -02-27 1 Introduction 5. NoTimeSync Monitoring Number of circuit breaker operation (single-phase tripping, three-phase tripping and reclosing) Channel status Frequency 6. Communication Optional 2 RS-485 communication rear ports conform to IEC 60870-5-103 protocol 1 RS-485 communication rear ports for clock synchronization Optional 2 or 4 Ethernet ports (depend on the chosen type of MON plug-in module) conform to IEC 61850 protocol, DNP3.0 protocol or IEC 60870-5-103 protocol over TCP/IP Optional 2 Ethernet ports via optic fiber (ST interface) conform to IEC 61850 protocol, DNP3.0 protocol or IEC 60870-5-103 protocol over TCP/IP GOOSE and SV communication function (optional NET-DSP plug-in module) 7. User Interface Friendly HMI interface with LCD and 9-button keypad on the front panel. 1 front multiplex RJ45 port for testing and setting 1 RS-232 or RS-485 rear ports for printer Language switchover—English+ selected language Auxiliary software—PCS-Explorer 1.3 Features The intelligent device integrated with protection, control and monitor provides powerful protection function, flexible protection configuration, user programmable logic and configurable binary input and binary output, which can meet with various application requirements. High-performance hardware platform and modularized design, fault detector DSP+protection DSP. Fault detector DSP manages fault detector and protection DSP manages protection calculation. Their data acquisition system is completely independent in electronic circuit. DC power supply of output relay is controlled by the operation of fault detector element, which prevents maloperation due to error from ADC or damage of any apparatus. Fast fault clearance for faults within the protected line, the operating time is less than 10 ms for close-up faults, less than 15ms for faults in the middle of protected line and less than 25ms for remote end faults. PCS-902 Line Distance Relay 1-7 Date: 2018-02-12 1 Introduction The unique DPFC distance element integrated in the protective device provides extremely high speed operation and insensitive to power swing. Self-adaptive floating threshold which only reflects deviation of power frequency component improves the protection sensitivity and stability under the condition of load fluctuation and system disturbance. Advanced and reliable power swing blocking releasing feature which ensure distance protection operate correctly for internal fault during power swing and prevent distance protection from maloperation during power swing Flexible automatic reclosure supports various initiation modes and check modes Multiple setting groups with password protection and setting value saved permanently before modification Powerful PC tool software can fulfill protection function configuration, modify setting and waveform analysis. PCS-902 Line Distance Relay 1-8 Date: 2018-02-12 -02-27 2 Technical Data 2 Technical Data Table of Contents 2 Technical Data ................................................................................... 2-a 2.1 Electrical Specifications ................................................................................. 2-1 2.1.1 AC Current Input .................................................................................................................. 2-1 2.1.2 AC Voltage Input .................................................................................................................. 2-1 2.1.3 Power Supply ....................................................................................................................... 2-1 2.1.4 Binary Input .......................................................................................................................... 2-2 2.1.5 Binary Output ....................................................................................................................... 2-2 2.2 Mechanical Specifications.............................................................................. 2-3 2.3 Ambient Temperature and Humidity Range .................................................. 2-4 2.4 Communication Port ....................................................................................... 2-4 2.4.1 EIA-485 Port ........................................................................................................................ 2-4 2.4.2 Ethernet Port ........................................................................................................................ 2-4 2.4.3 Optical Fibre Port ................................................................................................................. 2-4 2.4.4 Print Port .............................................................................................................................. 2-5 2.4.5 Clock Synchronization Port ................................................................................................. 2-5 2.5 Type Tests ........................................................................................................ 2-5 2.5.1 Environmental Tests............................................................................................................. 2-5 2.5.2 Mechanical Tests ................................................................................................................. 2-6 2.5.3 Electrical Tests ..................................................................................................................... 2-6 2.5.4 Electromagnetic Compatibility ............................................................................................. 2-6 2.6 Certifications ................................................................................................... 2-7 2.7 Terminals ......................................................................................................... 2-7 2.8 Measurement Scope and Accuracy ............................................................... 2-7 2.9 Management Function .................................................................................... 2-8 2.9.1 Control Performance............................................................................................................ 2-8 PCS-902 Line Distance Relay 2-a Date: 2019-03-01 2 Technical Data 2.9.2 Clock Performance .............................................................................................................. 2-8 2.9.3 Fault and Disturbance Recording ........................................................................................ 2-8 2.9.4 Binary Input Signal............................................................................................................... 2-8 2.10 Protective Functions..................................................................................... 2-8 2.10.1 Fault Detector .................................................................................................................... 2-8 2.10.2 Distance Protection ............................................................................................................ 2-8 2.10.3 Phase Overcurrent Protection ........................................................................................... 2-9 2.10.4 Earth Fault Protection ........................................................................................................ 2-9 2.10.5 Negative-sequence Overcurrent Protection ...................................................................... 2-9 2.10.6 Overvoltage Protection ...................................................................................................... 2-9 2.10.7 Negative-sequence Overvoltage Protection ...................................................................... 2-9 2.10.8 Residual Overvoltage Protection ..................................................................................... 2-10 2.10.9 Undervoltage Protection .................................................................................................. 2-10 2.10.10 Overfrequency Protection .............................................................................................. 2-10 2.10.11 Underfrequency Protection ............................................................................................ 2-10 2.10.12 Breaker Failure Protection ............................................................................................. 2-10 2.10.13 Thermal Overload Protection ..........................................................................................2-11 2.10.14 Stub Differential Protection .............................................................................................2-11 2.10.15 Dead Zone Protection .....................................................................................................2-11 2.10.16 Pole Discrepancy Protection ..........................................................................................2-11 2.10.17 Broken Conductor Protection .........................................................................................2-11 2.10.18 Reverse Power Protection ............................................................................................. 2-12 2.10.19 Auto-reclosing ................................................................................................................ 2-12 2.10.20 Transient Overreach ...................................................................................................... 2-12 2.10.21 Fault Locator .................................................................................................................. 2-12 PCS-902 Line Distance Relay 2-b Date: 2019-03-01 2 Technical Data 2.1 Electrical Specifications NOTICE! “System phase sequence”, which can be set by PCS-Explorer, this setting informs the device of the actual system phase sequence, either ABC or ACB. CT and VT inputs on the device, labeled as A, B and C, must be connected to system phase A, B and C for correct operation. 2.1.1 AC Current Input Phase rotation ABC or ACB Nominal frequency (fn) 50Hz, 60Hz Rated current (In) 1A Linear to 5A 0.05In~40In (It should measure current without beyond full scale against 20 times of related current and value of DC offset by 100%.) Thermal withstand -continuously 4In -for 10s 30In -for 1s 100In -for half a cycle 250In Burden < 0.15VA/phase @In Number Up to 7 current input according to various applications < 0.25VA/phase @In 2.1.2 AC Voltage Input Phase rotation ABC or ACB Nominal frequency (fn) 50Hz, 60Hz Rated voltage (Un) 100V~130V Linear to 1V~170V Thermal withstand Phase-to-ground Phase-to-phase -continuously 200V 346V -10s 260V 450V -1s 300V 519V Burden at rated < 0.20VA/phase @Un Number Up to 6 voltage input according to various applications 2.1.3 Power Supply Standard IEC 60255-11:2008 Rated voltage 110Vdc/125Vdc/220Vdc/250Vdc 110Vac/220Vac Permissible voltage range 88~300Vdc 88~264Vac Permissible AC ripple voltage ≤15% of the nominal auxiliary voltage Burden Quiescent condition <30W Operating condition <35W PCS-902 Line Distance Relay 2-1 Date: 2019-03-01 2 Technical Data 2.1.4 Binary Input 1. Settable pickup voltage and dropoff voltage Rated voltage 110Vdc 220Vdc Rated current drain 1.1mA 2.2mA On value 85-132Vdc (default set) 170-264Vdc (default set) Off value <66Vdc <132Vdc Maximum permissible voltage 300Vdc Withstand voltage 2000Vac, 2800Vdc (continuously) Response time for logic input ≤1ms Number Up to 54 binary input according to various hardware configurations 2. Fixed pickup voltage and dropoff voltage Rated voltage 110Vdc 125Vdc 220Vdc 220Vdc Rated current drain 1.1mA 1.25mA 2.2mA 2.85mA On value 77-132Vdc 87.5-150Vdc 154-264Vdc 176-264Vdc Off value <55Vdc <62.5Vdc <110Vdc <140Vdc Maximum permissible voltage 300Vdc Withstand voltage 2000Vac, 2800Vdc (continuously) Response time for logic input ≤1ms Number Up to 54 binary input according to various hardware configurations 2.1.5 Binary Output 1. Tripping/signaling contact Output mode Potential free contact Maximal system voltage 380Vac, 250Vdc Continuous carry 8A Pickup time (Typical Value) <5ms Dropoff time <5ms 0.65A@48Vdc 0.35A@110Vdc Breaking capacity (L/R=40ms) 0.30A@125Vdc 0.20A@220Vdc 0.15A@250Vdc 12A@3s Short duration current 18A@1s 24A@0.5s 40A@0.2s Durability (Loaded contact) 10000 operations Number Up to 55 binary output according to various hardware configurations 2. Heavy-capacity tripping contact Output mode Potential free contact PCS-902 Line Distance Relay 2-2 Date: 2019-03-01 2 Technical Data Maximal system voltage 250Vdc Continuous carry 10A Pickup time <1ms Dropoff time <10ms Breaking capacity (L/R=40ms) 10A Short duration current 15A@3s 30A@1s Durability (Loaded contact) 10000 operations Number Up to 30 binary output according to various hardware configurations 3. Fast signaling contact Output mode Potential free contact Maximal system voltage 380Vac, 250Vdc Continuous carry 5A Pickup time <1ms Dropoff time <5ms 0.65A@48Vdc 0.35A@110Vdc Breaking capacity (L/R=0ms) 0.30A@125Vdc 0.20A@220Vdc 0.15A@250Vdc 8A@3s Short duration current 12A@1s 16A@0.5s 30A@0.2s Durability (Loaded contact) 10000 operations Number Up to 20 binary output according to various hardware configurations 2.2 Mechanical Specifications Mounting Way Flush mounted Chassis color Silver grey Weight per device Approx. 15kg Chassis material Aluminum alloy Location of terminal Rear panel of the device Device structure Plug-in modular type @ rear side, integrated frontplate Protection class Standard IEC 60255-1:2009 Front side IP51 Other sides IP30 Rear side, connection terminals IP20 PCS-902 Line Distance Relay 2-3 Date: 2019-03-01 2 Technical Data 2.3 Ambient Temperature and Humidity Range Standard IEC 60255-1:2009 Operating temperature -40°C to +70°C (Readability of display may be impaired below -20°C) Transport and storage temperature range -40°C to +70°C Permissible humidity 5%-95%, without condensation Pollution degree Ⅱ Altitude <3000m 2.4 Communication Port 2.4.1 EIA-485 Port Baud rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s Protocol IEC 60870-5-103:1997 Maximal capacity 32 Max. transmission distance 500m Safety level Isolation to ELV level Twisted pair Screened twisted pair cable 2.4.2 Ethernet Port Connector type RJ-45 ST (Multi mode) Transmission rate 100Mbits/s Transmission standard 100Base-TX 100Base-FX Max. transmission distance 100m 2km (1310nm) Protocol IEC 60870-5-103:1997, DNP 3.0 or IEC 61850 Safety level Isolation to ELV level 2.4.3 Optical Fibre Port 2.4.3.1 For Station Level Characteristic Glass optical fiber Connector type ST Fibre type Multi mode Max. transmission distance 2km Wave length 1310nm Transmission power Min. -20.0dBm Minimum receiving power Min. -30.0dBm Margin Min +3.0dB 2.4.3.2 For Process Level Characteristic Glass optical fiber Connector type LC Fibre type Multi mode PCS-902 Line Distance Relay 2-4 Date: 2019-03-01 2 Technical Data Max. transmission distance 2km Wave length 1310nm Transmission power Min. -20.0dBm Minimum receiving power Min. -30.0dBm Margin Min +3.0dB 2.4.3.3 For Pilot Channel (only for Dedicated Optical Channel) Characteristic Glass optical fiber Connector type FC ST Fibre type Single mode Multi mode Wave length 1310nm 1550nm 850nm Max. transmission distance 60km 110km 2km Transmission power -11.0dBm ~ -7.0dBm -5.0dBm ~ 0dBm -20dBm ~ -12dBm Minimum receiving power Min. -36dBm Min. -36dBm Min. -30dBm 2.4.3.4 For Synchronization Port Characteristic Glass optical fiber Connector type ST Fibre type Multi mode Wave length 850nm Minimum receiving power Min. -25.0dBm Margin Min +3.0dB 2.4.4 Print Port Type RS-232 Baud Rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s Printer type EPSON® 300K printer Safety level Isolation to ELV level 2.4.5 Clock Synchronization Port Type RS-485 Max. transmission distance 500m Maximal capacity 32 Timing standard PPS, IRIG-B Safety level Isolation to ELV level 2.5 Type Tests 2.5.1 Environmental Tests Dry cold test IEC60068-2-1:2007 Dry heat test IEC60068-2-2:2007 Damp heat test, cyclic IEC60068-2-30:2005 PCS-902 Line Distance Relay 2-5 Date: 2019-03-01 2 Technical Data 2.5.2 Mechanical Tests Vibration IEC 60255-21-1:1988 Class Ⅰ Shock and bump IEC 60255-21-2:1988 Class Ⅰ 2.5.3 Electrical Tests Standard IEC 60255-27:2013 Dielectric tests Test voltage 2kV, 50Hz, 1min Impulse voltage tests Test voltage 5kV Overvoltage category Ⅲ Insulation resistance measurements Isolation resistance >100MΩ@500VDC 2.5.4 Electromagnetic Compatibility IEC 60255-26:2013 1MHz burst disturbance test Common mode: class Ⅲ 2.5kV Differential mode: class Ⅲ 1.0kV IEC 60255-26:2013 class Ⅳ Electrostatic discharge test For contact discharge: 8kV For air discharge: 15kV IEC 60255-26:2013 class Ⅲ Frequency sweep Radiated amplitude-modulated 10V/m (rms), f=80~1000MHz Radio frequency interference tests Spot frequency Radiated amplitude-modulated 10V/m (rms), f=80MHz/160MHz/450MHz/900MHz Radiated pulse-modulated 10V/m (rms), f=900MHz IEC 60255-26:2013 Fast transient disturbance tests Power supply, I/O, Earth: class Ⅳ, 4kV, 2.5kHz, 5/50ns Communication terminals: class Ⅳ, 2kV, 5kHz, 5/50ns IEC 60255-26:2013 Surge immunity test Power supply, AC input, I/O port: class Ⅳ, 1.2/50us Common mode: 4kV Differential mode: 2kV Conducted RF Electromagnetic Disturbance IEC 60255-26:2013 Power supply, AC, I/O, Comm. Terminal: Class Ⅲ , 10Vrms, 150 kHz~80MHz Power Frequency Magnetic Field IEC 61000-4-8:2001 Immunity class Ⅴ, 100A/m for 1min, 1000A/m for 3s Pulse Magnetic Field Immunity Damped oscillatory magnetic field IEC 61000-4-9:2001 class Ⅴ, 6.4/16μs, 1000A/m for 3s IEC 61000-4-10:2001 PCS-902 Line Distance Relay 2-6 Date: 2019-03-01 2 Technical Data immunity class Ⅴ, 100kHz & 1MHz–100A/m Auxiliary power supply performance IEC 60255-26:2013 - Voltage dips Up to 200ms for dips to 40% of rated voltage without reset -Voltage short interruptions 100ms for interruption without rebooting 2.6 Certifications ISO9001:2008 ISO14001:2004 OHSAS18001:2007 ISO10012:2003 CMMI L5 EMC: 2014/30/EU, EN60255-26:2013 Products safety (LVD): 2014/35/EU, EN60255-27:2014 2.7 Terminals Connection Type Wire Size Screw Type 2 AC current Screw terminals, 2.5mm lead 2 AC voltage Screw terminals, 1.5mm lead Power supply 0.6~1.3N·m M3 0.6~1.3N·m 2 M2.5 0.3~0.6N·m 2 2 M2.5 0.3~0.6N·m M4 1.6~1.8N·m Screw terminals, 1.0mm ~2.5mm lead Grounding (Earthing) Connection M3 2 Screw terminals, 1.0mm ~2.5mm lead Contact I/O Torque 2 BVR type, 2.5mm²~6.0mm lead 2.8 Measurement Scope and Accuracy Item Range Accuracy Phase range 0°~ 360° ≤±3° Frequency fn±3 Hz ≤ 0.02Hz Currents from protection measurement current transformers Current 0.05~5.00In Voltage 0.05~1.50Un Active power (W) Reactive power (VAr) Apparent power (VA) Energy (Wh) ≤ 2.0% of rating (0.05~1.00In) ≤ 2.0% of applied quantities (1.00~5.00In) ≤ 1.0% of rating (0.05~1.00Un) ≤ 1.0% of applied quantities (1.00~1.50Un) 0.05~1.50Un ≤ 3.0% of rating (0.05~1.00In, 0.05~1.00Un) 0.05~5.00In ≤ 3.0% of applied quantities (1.00~5.00In, 1.00~1.50Un) 0.05~1.50Un ≤ 3.0% of rating (0.05~1.00In, 0.05~1.00Un) 0.05~5.00In ≤ 3.0% of applied quantities (1.00~5.00In, 1.00~1.50Un) 0.05~1.50Un ≤ 3.0% of rating (0.05~1.00In, 0.05~1.00Un) 0.05~5.00In ≤ 3.0% of applied quantities (1.00~5.00In, 1.00~1.50Un) 0.05~1.50Un ≤ 3.0% of rating (0.05~1.00In, 0.05~1.00Un) 0.05~5.00In ≤ 3.0% of applied quantities (1.00~5.00In, 1.00~1.50Un) PCS-902 Line Distance Relay 2-7 Date: 2019-03-01 2 Technical Data Energy (VAh) 0.05~1.50Un ≤ 3.0% of rating (0.05~1.00In, 0.05~1.00Un) 0.05~5.00In ≤ 3.0% of applied quantities (1.00~5.00In, 1.00~1.50Un) 2.9 Management Function 2.9.1 Control Performance Control mode Local or remote Accuracy of local control ≤ 1s Accuracy of remote control ≤ 3s 2.9.2 Clock Performance Real time clock accuracy ≤ 3s/day Accuracy of GPS synchronization ≤ 1ms External time synchronization IRIG-B (200-98), PPS, IEEE1588 or SNTP protocol 2.9.3 Fault and Disturbance Recording Maximum duration 10000 sampled points (24 sampled points per cycle) Recording position 10 cycles before pickup of trigger element 2.9.4 Binary Input Signal Resolution of binary input signal ≤1ms Binary input mode Potential-free contact 2.10 Protective Functions 2.10.1 Fault Detector 2.10.1.1 DPFC Current Element Setting range 0.050In~30.000In (A) Accuracy ≤2.5% of setting or 0.02In, whichever is greater 2.10.1.2 Residual Current Element Setting range 0.050In~30.000In (A) Accuracy ≤2.5% of setting or 0.02In, whichever is greater 2.10.1.3 Overvoltage Element Setting range Un~2Unn (V) Accuracy ≤2.5% of setting or 0.01Un, whichever is greater 2.10.2 Distance Protection Setting range (0.000~4Unn)/In (ohm) Accuracy ≤2.5% of setting or 0.1Ω/In, whichever is greater Resetting ratio 105% PCS-902 Line Distance Relay 2-8 Date: 2019-03-01 2 Technical Data Time delay 0.000~10.000 (s) Accuracy ≤1%×Setting+30ms 2.10.3 Phase Overcurrent Protection Setting range 0.050In~30.000In (A) Accuracy ≤2.5% of setting or 0.02In, whichever is greater Resetting ratio 97% Time delay 0.000~20.000 (s) Accuracy (definite-time characteristic) ≤1%×Setting+30ms (at 2 times current setting) Accuracy (inverse-time characteristic) ≤5% of operating time or 30ms, whichever is greater (for current between 1.2 and 20 multiples of pickup) 2.10.4 Earth Fault Protection Setting range 0.050In~30.000In (A) Accuracy ≤2.5% of setting or 0.02In, whichever is greater Resetting ratio 97% Time delay 0.000~20.000 (s) Accuracy (definite-time characteristic) ≤1%×Setting+30ms (at 2 times current setting) Accuracy (inverse-time characteristic) ≤5% of operating time or 30ms, whichever is greater (for current between 1.2 and 20 multiples of pickup) 2.10.5 Negative-sequence Overcurrent Protection Setting range 0.050In~30.000In (A) Accuracy ≤2.5% of setting or 0.02In, whichever is greater Resetting ratio 97% Time delay 0.000~20.000 (s) Accuracy (definite-time characteristic) ≤1%×Setting+30ms (at 2 times current setting) Accuracy (inverse-time characteristic) ≤2.5% of operating time or 30ms, whichever is greater (for current between 1.2 and 20 multiples of pickup) 2.10.6 Overvoltage Protection Setting range Un~2Unn (V) Accuracy ≤2.5% of setting or 0.01Un, whichever is greater Resetting ratio 98% Time delay 0.000~30.000 (s) Accuracy (definite-time characteristic) ≤1%×Setting+30ms (at 1.2 times voltage setting) Accuracy (inverse-time characteristic) ≤2.5% of operating time or 30ms, whichever is greater (for voltage between 1.2 and 2 multiples of pickup) 2.10.7 Negative-sequence Overvoltage Protection Setting range 0~Un (V) Accuracy ≤2.5% of setting or 0.01Un, whichever is greater Resetting ratio 95% PCS-902 Line Distance Relay 2-9 Date: 2019-03-01 2 Technical Data Time delay 0.000~30.000 (s) Accuracy (definite-time characteristic) ≤1%×Setting+30ms (at 1.2 times voltage setting) 2.10.8 Residual Overvoltage Protection Setting range 0~2Unn (V) Accuracy ≤2.5% of setting or 0.1V, whichever is greater Resetting ratio 95% Time delay 0.000~3600.000 (s) Accuracy (definite-time characteristic) ≤1%×Setting+30ms (at 1.2 times voltage setting) ≤2.5% of operating time or 30ms, whichever is greater Accuracy (inverse-time characteristic) (for residual voltage between 1.2 and 2 multiples of pickup) 2.10.9 Undervoltage Protection Setting range 0~Unn (V) Accuracy ≤2.5% of setting or 0.01Un, whichever is greater Resetting ratio 102% Time delay 0.000~30.000 (s) Accuracy (definite-time characteristic) ≤1%×Setting+30ms (at 0.8 times voltage setting) Accuracy (inverse-time characteristic) ≤2.5% of operating time or 30ms, whichever is greater (for voltage between 0.5 and 0.8 multiples of pickup) 2.10.10 Overfrequency Protection Setting range 50.00~65.00 (Hz) Accuracy ≤ 0.02Hz Resetting value Setting-0.05Hz Time delay 0.000~100.000 (s) Accuracy ≤1%×Setting+30ms (at 1.2 times frequency setting) 2.10.11 Underfrequency Protection Setting range 45.00~60.00 (Hz) Accuracy ≤ 0.02Hz Resetting value Setting+0.05Hz Time delay 0.000~100.000 (s) Accuracy ≤1%×Setting+30ms (at 0.8 times frequency setting) df/dt blocking setting range 0.200~20.000 (Hz/s) Accuracy ≤ 0.02Hz/s 2.10.12 Breaker Failure Protection Pick-up time <25ms Drop-off time <20ms Setting range of phase current 0.050In~30.000In (A) Setting range of zero-sequence current 0.050In~30.000In (A) PCS-902 Line Distance Relay 2-10 Date: 2019-03-01 2 Technical Data Setting range of negative-sequence current 0.050In~30.000In (A) Accuracy ≤2.5% of setting or 0.02In, whichever is greater Time delay (first) 0.000~10.000 (s) Time delay (second) 0.000~10.000 (s) 2.10.13 Thermal Overload Protection Base current setting range 0.050In~30.000In (A) Accuracy ≤2.5% of setting or 0.02In, whichever is greater Line thermal time constant 0.100~100.000 (min) Thermal overload coefficient for trip 1.000~3.000 Thermal overload coefficient for alarm 1.000~3.000 Resetting ratio 95% Drop-off time <30ms ≤2.5% of operating time or 30ms, whichever is greater Time accuracy (for current between 1.2 and 20 multiples of pickup) 2.10.14 Stub Differential Protection Setting range 0.050In~30.000In (A) Accuracy ≤2.5% of setting or 0.02In, whichever is greater Resetting ratio 95% Time delay 0.000~10.000 (s) Accuracy ≤1%×Setting+30ms (at 2 times current setting) 2.10.15 Dead Zone Protection Setting range 0.050In~30.000In Accuracy ≤2.5% of setting or 0.02In, whichever is greater Resetting ratio 95% Time delay 0.000~10.000s Accuracy ≤1%×Setting+30ms 2.10.16 Pole Discrepancy Protection Setting range (zero-sequence current) 0.050In~30.000In (A) Setting range (negative-sequence current) 0.050In~30.000In (A) Accuracy ≤2.5% of setting or 0.02In, whichever is greater Resetting ratio 95% Time delay 0.000~600.000 (s) Accuracy ≤1%×Setting+30ms (at 2 times current setting) 2.10.17 Broken Conductor Protection Setting range (I2/I1) 0.20~1.00 Accuracy ≤2.5% of setting Resetting ratio 95% Time delay 0.000~600.000 (s) PCS-902 Line Distance Relay 2-11 Date: 2019-03-01 2 Technical Data Accuracy ≤1%×Setting+30ms 2.10.18 Reverse Power Protection Setting range 0.100In~50.000In Accuracy ≤2% of setting or 0.5W, whichever is greater Resetting ratio 95% Time delay 0.010~300.000 (s) Accuracy ≤1%×Setting+30ms 2.10.19 Auto-reclosing Phase difference setting range 0~89 (Deg) Accuracy 2.0Deg Voltage difference setting range 0.02Un~0.8Un (V) Accuracy Max(0.01Un, 2.5%) Frequency difference setting range 0.02~1 (Hz) Accuracy 0.01Hz Operating time of synchronism check ≤1%×Setting+20ms Operating time of energizing check ≤1%×Setting+20ms Operating time of auto-reclosing ≤1%×Setting+20ms 2.10.20 Transient Overreach Tolerance for all high-speed protection ≤2% 2.10.21 Fault Locator Accuracy for multi-phase faults with single end feed < ±2.5% Tolerance will be higher in case of single-phase fault with high ground resistance. PCS-902 Line Distance Relay 2-12 Date: 2019-03-01 3 Operation Theory 3 Operation Theory Table of Contents 3 Operation Theory .............................................................................. 3-a 3.1 System Parameters ......................................................................................... 3-1 3.1.1 General Application.............................................................................................................. 3-1 3.1.2 Function Description ............................................................................................................ 3-1 3.1.3 Settings ................................................................................................................................ 3-1 3.2 Line Parameters .............................................................................................. 3-2 3.2.1 General Application.............................................................................................................. 3-2 3.2.2 Function Description ............................................................................................................ 3-2 3.2.3 Settings ................................................................................................................................ 3-2 3.3 Frequency Calculation.................................................................................... 3-2 3.3.1 General Application.............................................................................................................. 3-2 3.3.2 Function Description ............................................................................................................ 3-3 3.3.3 Function Block Diagram ...................................................................................................... 3-3 3.3.4 I/O Signal ............................................................................................................................. 3-3 3.3.5 Logic .................................................................................................................................... 3-4 3.4 Circuit Breaker Position Supervision ............................................................ 3-4 3.4.1 General Application.............................................................................................................. 3-4 3.4.2 Function Description ............................................................................................................ 3-4 3.4.3 Function Block Diagram ...................................................................................................... 3-4 3.4.4 I/O Signals ........................................................................................................................... 3-5 3.4.5 Logic .................................................................................................................................... 3-6 3.4.6 Settings ................................................................................................................................ 3-8 3.5 Fault Detector (FD) .......................................................................................... 3-8 3.5.1 Application............................................................................................................................ 3-8 3.5.2 Fault Detector in Fault Detector DSP .................................................................................. 3-9 3-a PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.5.3 Protection Fault Detector in Protection Calculation DSP .................................................. 3-12 3.5.4 Function Block Diagram .................................................................................................... 3-13 3.5.5 I/O Signals ......................................................................................................................... 3-13 3.5.6 Logic .................................................................................................................................. 3-13 3.5.7 Settings .............................................................................................................................. 3-13 3.6 Auxiliary Element .......................................................................................... 3-14 3.6.1 General Application............................................................................................................ 3-14 3.6.2 Function Description .......................................................................................................... 3-14 3.6.3 Function Block Diagram .................................................................................................... 3-16 3.6.4 I/O Signals ......................................................................................................................... 3-17 3.6.5 Logic .................................................................................................................................. 3-18 3.6.6 Settings .............................................................................................................................. 3-21 3.7 Distance Protection....................................................................................... 3-22 3.7.1 General Application............................................................................................................ 3-22 3.7.2 Function Description .......................................................................................................... 3-22 3.7.3 DPFC Distance Protection ................................................................................................. 3-30 3.7.4 Load Encroachment........................................................................................................... 3-34 3.7.5 Mho Distance Protection.................................................................................................... 3-36 3.7.6 Quadrilateral Distance Protection ...................................................................................... 3-48 3.7.7 Pilot Distance Zone ............................................................................................................ 3-55 3.7.8 Out-of-step Protection........................................................................................................ 3-58 3.7.9 Power Swing Blocking Releasing ...................................................................................... 3-65 3.7.10 Distance SOTF Protection ............................................................................................... 3-72 3.8 Optical Pilot Channel (Option) ..................................................................... 3-80 3.8.1 General Application............................................................................................................ 3-80 3.8.2 Function Description .......................................................................................................... 3-80 3.8.3 Function Block Diagram .................................................................................................... 3-86 3.8.4 I/O Signals ......................................................................................................................... 3-86 3.8.5 Logic .................................................................................................................................. 3-87 3.8.6 Settings .............................................................................................................................. 3-87 3-b PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.9 Pilot Distance Protection .............................................................................. 3-88 3.9.1 General Application............................................................................................................ 3-88 3.9.2 Function Description .......................................................................................................... 3-88 3.9.3 Function Block Diagram .................................................................................................. 3-104 3.9.4 I/O Signals ....................................................................................................................... 3-104 3.9.5 Settings ............................................................................................................................ 3-106 3.10 Pilot Directional Earth-fault Protection ................................................... 3-107 3.10.1 General Application........................................................................................................ 3-107 3.10.2 Function Description ...................................................................................................... 3-107 3.10.3 Function Block Diagram .................................................................................................3-116 3.10.4 I/O Signals ......................................................................................................................3-116 3.10.5 Settings ...........................................................................................................................3-117 3.11 Current Direction ........................................................................................ 3-118 3.11.1 General Application .........................................................................................................3-118 3.11.2 Function Description .......................................................................................................3-119 3.11.3 Function Block Diagram ................................................................................................. 3-124 3.11.4 I/O Signals ...................................................................................................................... 3-124 3.11.5 Settings .......................................................................................................................... 3-125 3.12 Phase Overcurrent Protection ................................................................. 3-125 3.12.1 General Application........................................................................................................ 3-125 3.12.2 Function Description ...................................................................................................... 3-125 3.12.3 Function Block Diagram ................................................................................................ 3-128 3.12.4 I/O Signals ..................................................................................................................... 3-128 3.12.5 Logic .............................................................................................................................. 3-129 3.12.6 Settings .......................................................................................................................... 3-130 3.13 Earth Fault Protection............................................................................... 3-131 3.13.1 General Application........................................................................................................ 3-131 3.13.2 Function Description ...................................................................................................... 3-131 3.13.3 Function Block Diagram ................................................................................................ 3-134 3.13.4 I/O Signals ..................................................................................................................... 3-134 3-c PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.13.5 Logic .............................................................................................................................. 3-135 3.13.6 Settings .......................................................................................................................... 3-137 3.14 Negative-sequence Overcurrent Protection ........................................... 3-139 3.14.1 General Application........................................................................................................ 3-139 3.14.2 Function Description ...................................................................................................... 3-139 3.14.3 Function Block Diagram ................................................................................................ 3-142 3.14.4 I/O Signals ..................................................................................................................... 3-142 3.14.5 Logic .............................................................................................................................. 3-143 3.14.6 Settings .......................................................................................................................... 3-144 3.15 Overcurrent Protection for VT Circuit Failure......................................... 3-146 3.15.1 General Application........................................................................................................ 3-146 3.15.2 Function Description ...................................................................................................... 3-146 3.15.3 Function Block Diagram ................................................................................................ 3-148 3.15.4 I/O Signals ..................................................................................................................... 3-148 3.15.5 Logic .............................................................................................................................. 3-149 3.15.6 Settings .......................................................................................................................... 3-150 3.16 Phase Current SOTF Protection .............................................................. 3-152 3.16.1 General Application........................................................................................................ 3-152 3.16.2 Function Description ...................................................................................................... 3-152 3.16.3 Function Block Diagram ................................................................................................ 3-153 3.16.4 I/O Signals ..................................................................................................................... 3-153 3.16.5 Logic .............................................................................................................................. 3-154 3.16.6 Settings .......................................................................................................................... 3-155 3.17 Residual Current SOTF Protection .......................................................... 3-156 3.17.1 General Application........................................................................................................ 3-156 3.17.2 Function Description ...................................................................................................... 3-156 3.17.3 Function Block Diagram ................................................................................................ 3-157 3.17.4 I/O Signals ..................................................................................................................... 3-157 3.17.5 Logic .............................................................................................................................. 3-158 3.17.6 Settings .......................................................................................................................... 3-158 3-d PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.18 Voltage Protection ..................................................................................... 3-158 3.18.1 Overvoltage Protection .................................................................................................. 3-159 3.18.2 Negative-sequence Overvoltage Protection .................................................................. 3-165 3.18.3 Residual Overvoltage Protection ................................................................................... 3-166 3.18.4 Undervoltage Protection ................................................................................................ 3-171 3.19 Frequency Protection ............................................................................... 3-178 3.19.1 Overfrequency Protection .............................................................................................. 3-178 3.19.2 Underfrequency Protection ............................................................................................ 3-180 3.20 Breaker Failure Protection ....................................................................... 3-183 3.20.1 General Application........................................................................................................ 3-183 3.20.2 Function Description ...................................................................................................... 3-183 3.20.3 Function Block Diagram ................................................................................................ 3-184 3.20.4 I/O Signals ..................................................................................................................... 3-185 3.20.5 Logic .............................................................................................................................. 3-186 3.20.6 Settings .......................................................................................................................... 3-187 3.21 Thermal Overload Protection ................................................................... 3-188 3.21.1 General Application........................................................................................................ 3-188 3.21.2 Function Description ...................................................................................................... 3-188 3.21.3 Function Block Diagram ................................................................................................ 3-189 3.21.4 I/O Signals ..................................................................................................................... 3-189 3.21.5 Logic .............................................................................................................................. 3-190 3.21.6 Settings .......................................................................................................................... 3-190 3.22 Stub Differential Protection ...................................................................... 3-191 3.22.1 General Application........................................................................................................ 3-191 3.22.2 Function Description ...................................................................................................... 3-191 3.22.3 Function Block Diagram ................................................................................................ 3-192 3.22.4 I/O Signals ..................................................................................................................... 3-193 3.22.5 Logic .............................................................................................................................. 3-193 3.22.6 Settings .......................................................................................................................... 3-194 3.23 Dead Zone Protection ............................................................................... 3-195 3-e PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.23.1 General Application........................................................................................................ 3-195 3.23.2 Function Description ...................................................................................................... 3-195 3.23.3 Function Block Diagram ................................................................................................ 3-196 3.23.4 I/O Signal ....................................................................................................................... 3-196 3.23.5 Logic .............................................................................................................................. 3-197 3.23.6 Settings .......................................................................................................................... 3-197 3.24 Pole Discrepancy Protection .................................................................... 3-197 3.24.1 General Application........................................................................................................ 3-197 3.24.2 Function Description ...................................................................................................... 3-198 3.24.3 Function Block Diagram ................................................................................................ 3-198 3.24.4 I/O Signals ..................................................................................................................... 3-198 3.24.5 Logic .............................................................................................................................. 3-198 3.24.6 Settings .......................................................................................................................... 3-199 3.25 Broken Conductor Protection .................................................................. 3-200 3.25.1 General Application........................................................................................................ 3-200 3.25.2 Function Description ...................................................................................................... 3-200 3.25.3 Function Block Diagram ................................................................................................ 3-201 3.25.4 I/O Signals ..................................................................................................................... 3-201 3.25.5 Logic .............................................................................................................................. 3-201 3.25.6 Settings .......................................................................................................................... 3-202 3.26 Reverse Power Protection ........................................................................ 3-202 3.26.1 General Application........................................................................................................ 3-202 3.26.2 Function Description ...................................................................................................... 3-202 3.26.3 Function Block Diagram ................................................................................................ 3-203 3.26.4 I/O Signals ..................................................................................................................... 3-203 3.26.5 Logic .............................................................................................................................. 3-204 3.26.6 Settings .......................................................................................................................... 3-205 3.27 Synchrocheck............................................................................................ 3-205 3.27.1 General Application........................................................................................................ 3-205 3.27.2 Function Description ...................................................................................................... 3-205 3-f PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.27.3 Function Block Diagram ................................................................................................ 3-214 3.27.4 I/O Signals ..................................................................................................................... 3-215 3.27.5 Logic .............................................................................................................................. 3-216 3.27.6 Settings .......................................................................................................................... 3-219 3.28 Automatic Reclosure ................................................................................ 3-221 3.28.1 General Application........................................................................................................ 3-221 3.28.2 Function Description ...................................................................................................... 3-221 3.28.3 Function Block Diagram ................................................................................................ 3-223 3.28.4 I/O Signals ..................................................................................................................... 3-223 3.28.5 Logic .............................................................................................................................. 3-225 3.28.6 Settings .......................................................................................................................... 3-237 3.29 Transfer Trip .............................................................................................. 3-239 3.29.1 General Application........................................................................................................ 3-239 3.29.2 Function Description ...................................................................................................... 3-239 3.29.3 Function Block Diagram ................................................................................................ 3-239 3.29.4 I/O Signals ..................................................................................................................... 3-240 3.29.5 Logic .............................................................................................................................. 3-240 3.29.6 Settings .......................................................................................................................... 3-240 3.30 Trip Logic ................................................................................................... 3-241 3.30.1 General Application........................................................................................................ 3-241 3.30.2 Function Description ...................................................................................................... 3-241 3.30.3 Function Block Diagram ................................................................................................ 3-241 3.30.4 I/O Signals ..................................................................................................................... 3-242 3.30.5 Logic .............................................................................................................................. 3-242 3.30.6 Settings .......................................................................................................................... 3-248 3.31 VT Circuit Supervision .............................................................................. 3-248 3.31.1 General Application........................................................................................................ 3-248 3.31.2 Function Description ...................................................................................................... 3-249 3.31.3 Function Block Diagram ................................................................................................ 3-249 3.31.4 I/O Signals ..................................................................................................................... 3-249 3-g PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.31.5 Logic .............................................................................................................................. 3-250 3.31.6 Settings .......................................................................................................................... 3-251 3.32 CT Circuit Supervision ............................................................................. 3-251 3.32.1 General Application........................................................................................................ 3-251 3.32.2 Function Description ...................................................................................................... 3-252 3.32.3 Function Block Diagram ................................................................................................ 3-252 3.32.4 I/O Signals ..................................................................................................................... 3-252 3.32.5 Logic .............................................................................................................................. 3-252 3.33 Control and Synchrocheck for Manual Closing ..................................... 3-252 3.33.1 General Application........................................................................................................ 3-252 3.33.2 Function Description ...................................................................................................... 3-253 3.33.3 Function Block Diagram ................................................................................................ 3-264 3.33.4 I/O Signals ..................................................................................................................... 3-265 3.33.5 Settings .......................................................................................................................... 3-266 3.34 Faulty Phase Selection ............................................................................. 3-270 3.34.1 General Application........................................................................................................ 3-270 3.34.2 Function Description ...................................................................................................... 3-270 3.34.3 Function Block Diagram ................................................................................................ 3-273 3.34.4 I/O Signals ..................................................................................................................... 3-273 3.35 Fault Location............................................................................................ 3-274 3.35.1 Application...................................................................................................................... 3-274 3.35.2 Function Description ...................................................................................................... 3-274 3.35.3 Function Block Diagram ................................................................................................ 3-277 3.35.4 I/O Signals ..................................................................................................................... 3-278 List of Figures Figure 3.3-1 Logic diagram of frequency calculation.............................................................. 3-4 Figure 3.4-1 Logic diagram of CB position supervision ......................................................... 3-6 Figure 3.4-2 Logic diagram of trip&closing circuit supervision ............................................ 3-7 Figure 3.4-3 Logic diagram of circuit breaker position ........................................................... 3-7 3-h PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Figure 3.4-4 Logic diagram of pole open states ...................................................................... 3-8 Figure 3.5-1 Flow chart of protection program ...................................................................... 3-12 Figure 3.5-2 Logic diagram of fault detector .......................................................................... 3-13 Figure 3.6-1 Logic diagram of auxiliary element (ROC) ........................................................ 3-18 Figure 3.6-2 Logic diagram of auxiliary element (ROV) ........................................................ 3-18 Figure 3.6-3 Logic diagram of auxiliary element (OC)........................................................... 3-19 Figure 3.6-4 Logic diagram of auxiliary element (UVG) ........................................................ 3-19 Figure 3.6-5 Logic diagram of auxiliary element (UVS)......................................................... 3-20 Figure 3.6-6 Logic diagram of auxiliary element (UVD) ........................................................ 3-20 Figure 3.6-7 Logic diagram of auxiliary element (OCD) ........................................................ 3-20 Figure 3.6-8 Logic diagram of auxiliary element (Startup) ................................................... 3-21 Figure 3.7-1 Operating time of single-phase fault (50Hz, SIR=1) ......................................... 3-25 Figure 3.7-2 Operating time of single-phase fault (60Hz, SIR=1) ......................................... 3-25 Figure 3.7-3 Operating time of two-phase fault (50Hz, SIR=1) ............................................. 3-26 Figure 3.7-4 Operating time of two-phase fault (60Hz, SIR=1) ............................................. 3-26 Figure 3.7-5 Operating time of three-phase fault (50Hz, SIR=1) ........................................... 3-27 Figure 3.7-6 Operating time of three-phase fault (60Hz, SIR=1) ........................................... 3-27 Figure 3.7-7 Operating time of single-phase fault (50Hz, SIR=30) ....................................... 3-28 Figure 3.7-8 Operating time of single-phase fault (60Hz, SIR=30) ....................................... 3-28 Figure 3.7-9 Operating time of two-phase fault (50Hz, SIR=30) ........................................... 3-29 Figure 3.7-10 Operating time of two-phase fault (60Hz, SIR=30) ......................................... 3-29 Figure 3.7-11 Operating time of three-phase fault (50Hz, SIR=30) ....................................... 3-30 Figure 3.7-12 Operating time of three-phase fault (60Hz, SIR=30) ....................................... 3-30 Figure 3.7-13 Operation characteristic for forward fault....................................................... 3-31 Figure 3.7-14 Operation characteristic for reverse fault ....................................................... 3-32 Figure 3.7-15 Logic diagram of DPFC distance protection................................................... 3-33 Figure 3.7-16 Distance element with load trapezoid.............................................................. 3-34 Figure 3.7-17 Phase-to-ground operation characteristic for forward fault ......................... 3-36 Figure 3.7-18 Operation Characteristic of quadrilateral distance element ......................... 3-38 Figure 3.7-19 Phase-to-phase operation characteristic for forward fault ........................... 3-38 3-i PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Figure 3.7-20 Operation characteristic for reverse fault ....................................................... 3-39 Figure 3.7-21 Steady-state characteristic of three-phase short-circuit fault ...................... 3-40 Figure 3.7-22 Operation characteristic of three-phase close up short-circuit fault........... 3-40 Figure 3.7-23 Shift impedance characteristic of zone 1 and zone 2 .................................... 3-41 Figure 3.7-24 Logic diagram of enabling distance protection (Mho)................................... 3-43 Figure 3.7-25 Logic diagram of distance protection (Mho zone 1) ...................................... 3-44 Figure 3.7-26 Logic diagram of distance protection (Mho zone i) ....................................... 3-45 Figure 3.7-27 Quadrilateral forward distance element characteristics ............................... 3-48 Figure 3.7-28 Quadrilateral reverse distance element characteristic .................................. 3-49 Figure 3.7-29 Logic diagram of enabling distance protection (Quad) ................................. 3-51 Figure 3.7-30 Logic diagram of distance protection (Quad zone 1) .................................... 3-51 Figure 3.7-31 Logic diagram of distance protection (Quad zone i) ..................................... 3-53 Figure 3.7-32 Protected zone of pilot distance protection.................................................... 3-55 Figure 3.7-33 Pilot reverse weak infeed element ................................................................... 3-56 Figure 3.7-34 Logic diagram of pilot distance zone (Mho characteristic) ........................... 3-56 Figure 3.7-35 Logic diagram of pilot distance zone (Quad characteristic) ......................... 3-57 Figure 3.7-36 Dual-machine equivalent system ..................................................................... 3-59 Figure 3.7-37 Dual-machine equivalent system ..................................................................... 3-59 Figure 3.7-38 Variation curve of oscillation center voltage .................................................. 3-61 Figure 3.7-39 The variation rule of oscillation center voltage .............................................. 3-61 Figure 3.7-40 Vector diagram of the oscillation center voltage ........................................... 3-62 Figure 3.7-41 Operation characteristic of zone detector element........................................ 3-63 Figure 3.7-42 Logic diagram of out-of-step protection ......................................................... 3-64 Figure 3.7-43 Logic diagram of PSBR ..................................................................................... 3-71 Figure 3.7-44 Logic diagram of enabling distance SOTF protection ................................... 3-73 Figure 3.7-45 Logic diagram of manual closing signal ......................................................... 3-74 Figure 3.7-46 Logic diagram of manual closing signal ......................................................... 3-75 Figure 3.7-47 Logic diagram of distance SOTF protection by manual closing signal ...... 3-76 Figure 3.7-48 Logic diagram of distance SOTF protection by 1-pole or 3-pole AR ........... 3-77 Figure 3.7-49 Logic diagram of distance SOTF protection by PD condition ...................... 3-78 3-j PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Figure 3.7-50 Logic diagram of distance SOTF protection ................................................... 3-78 Figure 3.8-1 Direct optical link up to 2km with 850nm .......................................................... 3-81 Figure 3.8-2 Direct optical link up to 60km with1310nm or 110km with 1550nm ............... 3-81 Figure 3.8-3 Connect to a communication network via communication convertor........... 3-82 Figure 3.8-4 Connect to a communication network via MUX-64 .......................................... 3-82 Figure 3.8-5 Connect to a communication network via MUX-2M ......................................... 3-83 Figure 3.8-6 Schematic diagram of communication channel time ...................................... 3-85 Figure 3.8-7 Logic diagram of receiving signal i.................................................................... 3-87 Figure 3.9-1 Enabling/disabling logic of pilot distance protection ...................................... 3-89 Figure 3.9-2 Logic diagram of receiving signal...................................................................... 3-90 Figure 3.9-3 Zone extension ..................................................................................................... 3-91 Figure 3.9-4 Simple schematic of PUTT .................................................................................. 3-92 Figure 3.9-5 Logic diagram of pilot distance protection (PUTT) .......................................... 3-93 Figure 3.9-6 Simple schematic of POTT.................................................................................. 3-94 Figure 3.9-7 Logic diagram of pilot distance protection (POTT) .......................................... 3-96 Figure 3.9-8 Simple schematic of system fault ...................................................................... 3-97 Figure 3.9-9 Simple schematic of blocking ............................................................................ 3-97 Figure 3.9-10 Logic diagram of pilot distance protection (Blocking) .................................. 3-98 Figure 3.9-11 Logic diagram of pilot distance protection (Unblocking) .............................. 3-99 Figure 3.9-12 Current reversal ................................................................................................. 3-99 Figure 3.9-13 Logic diagram of current reversal blocking.................................................. 3-100 Figure 3.9-14 Line fault description ....................................................................................... 3-101 Figure 3.9-15 Weak infeed logic during pickup .................................................................... 3-102 Figure 3.9-16 Weak infeed echo logic without pickup ........................................................ 3-102 Figure 3.9-17 Weak infeed trip logic without pickup ........................................................... 3-103 Figure 3.9-18 Simplified CB echo logic for POTT ................................................................ 3-103 Figure 3.10-1 Enabling/disabling logic of pilot directional earth-fault protection ........... 3-108 Figure 3.10-2 Logic diagram of receiving signal.................................................................. 3-108 Figure 3.10-3 Forward/reverse direction of zero-sequence power .................................... 3-108 Figure 3.10-4 Simple schematic of DEF (permissive scheme) ........................................... 3-109 3-k PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Figure 3.10-5 Logic diagram of DEF (permissive scheme) ................................................. 3-110 Figure 3.10-6 Simple schematic of blocking .........................................................................3-111 Figure 3.10-7 Logic diagram of DEF (Blocking scheme) .................................................... 3-112 Figure 3.10-8 Logic diagram for unblocking ........................................................................ 3-113 Figure 3.10-9 Current reversal ............................................................................................... 3-114 Figure 3.10-10 Logic diagram of current reversal blocking ............................................... 3-114 Figure 3.10-11 Simplified CB Echo logic for POTT .............................................................. 3-115 Figure 3.11-1 Line fault description ....................................................................................... 3-118 Figure 3.11-2 Vector diagram of current and voltage .......................................................... 3-119 Figure 3.11-3 Vector diagram of zero-sequence power....................................................... 3-121 Figure 3.12-1 Logic diagram of phase overcurrent protection .......................................... 3-129 Figure 3.13-1 Logic diagram of stage 1 of earth fault protection ....................................... 3-135 Figure 3.13-2 Logic diagram of stage i of earth fault protection ........................................ 3-136 Figure 3.14-1 Logic diagram of stage i of negative-sequence overcurrent protection ... 3-143 Figure 3.14-2 Logic diagram of stage 4 of negative-sequence overcurrent protection .. 3-144 Figure 3.15-1 Logic diagram of overcurrent protection for VT circuit failure................... 3-150 Figure 3.16-1 Logic diagram of phase current SOTF protection ....................................... 3-154 Figure 3.17-1 Logic diagram of residual current SOTF protection .................................... 3-158 Figure 3.18-1 Logic diagram of stage i of overvoltage protection ..................................... 3-163 Figure 3.18-2 Logic diagram of negative-sequence overvoltage protection .................... 3-166 Figure 3.18-3 Logic diagram of stage 1 of residual overvoltage protection ..................... 3-169 Figure 3.18-4 Logic diagram of stage 2 of residual overvoltage protection ..................... 3-169 Figure 3.18-5 Logic diagram of stage 3 of residual overvoltage protection ..................... 3-169 Figure 3.18-6 Blocking logic of undervoltage protection ................................................... 3-175 Figure 3.18-7 Enabling logic of undervoltage protection ................................................... 3-175 Figure 3.18-8 Current releasing logic of undervoltage protection ..................................... 3-175 Figure 3.18-9 Logic diagram of stage i of undervoltage protection................................... 3-176 Figure 3.19-1 Logic diagram of overfrequency protection (start) ...................................... 3-179 Figure 3.19-2 Logic diagram of stage i of overfrequency protection ................................ 3-179 Figure 3.19-3 Logic diagram of underfrequency protection (start) ................................... 3-182 3-l PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Figure 3.19-4 Logic diagram of stage i of underfrequency protection .............................. 3-182 Figure 3.20-1 Logic diagram of breaker failure protection ................................................. 3-186 Figure 3.21-1 Characteristic curve of thermal overload model .......................................... 3-189 Figure 3.21-2 Logic diagram of stage i of thermal overload protection ............................ 3-190 Figure 3.22-1 3/2 breakers arrangement ............................................................................... 3-191 Figure 3.22-2 Logic diagram of stub differential protection ............................................... 3-194 Figure 3.23-1 Dead zone protection ...................................................................................... 3-197 Figure 3.24-1 Logic diagram of pole discrepancy protection............................................. 3-199 Figure 3.25-1 Logic diagram of broken conductor protection ........................................... 3-201 Figure 3.26-1 Logic diagram of stage 1 of reverse power protection................................ 3-204 Figure 3.26-2 Logic diagram of stage 2 of reverse power protection................................ 3-204 Figure 3.27-1 Relationship between reference voltage and synchronism voltage .......... 3-206 Figure 3.27-2 Voltage connection for single busbar arrangement..................................... 3-208 Figure 3.27-3 Voltage connection for single busbar arrangement..................................... 3-208 Figure 3.27-4 Voltage connection for double busbars arrangement ................................. 3-209 Figure 3.27-5 Voltage selection for double busbars arrangement ..................................... 3-209 Figure 3.27-6 Voltage connection for one and a half breakers arrangement ................... 3-210 Figure 3.27-7 Voltage selection for one and a half breakers arrangement ....................... 3-211 Figure 3.27-8 Voltage selection for one and a half breakers arrangement ....................... 3-212 Figure 3.27-9 Reference voltage circuit failure supervision logic ..................................... 3-213 Figure 3.27-10 Synchronism voltage circuit failure supervision logic .............................. 3-213 Figure 3.27-11 Synchrocheck mode selection ..................................................................... 3-217 Figure 3.27-12 Synchronism check ....................................................................................... 3-217 Figure 3.27-13 Dead charge check logic ............................................................................... 3-218 Figure 3.27-14 Synchrocheck logic ....................................................................................... 3-218 Figure 3.28-1 Logic diagram of AR block ............................................................................. 3-226 Figure 3.28-2 Logic diagram of AR ready ............................................................................. 3-227 Figure 3.28-3 Logic diagram of tripping condition output .................................................. 3-228 Figure 3.28-4 Single-phase tripping initiating AR ................................................................ 3-229 Figure 3.28-5 Three-phase tripping initiating AR ................................................................. 3-229 3-m PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Figure 3.28-6 1-pole AR initiation .......................................................................................... 3-230 Figure 3.28-7 3-pole AR initiation .......................................................................................... 3-230 Figure 3.28-8 One-shot AR ..................................................................................................... 3-231 Figure 3.28-9 Extra time delay of AR ..................................................................................... 3-231 Figure 3.28-10 Reclosing output logic .................................................................................. 3-232 Figure 3.28-11 Wait to slave signal ........................................................................................ 3-232 Figure 3.28-12 Reclosing failure and success ..................................................................... 3-233 Figure 3.28-13 Single-phase transient fault .......................................................................... 3-236 Figure 3.28-14 Single-phase permanent fault ([CBx.79.N_Rcls]=2) ................................... 3-236 Figure 3.29-1 Logic diagram of transfer trip......................................................................... 3-240 Figure 3.30-1 Tripping logic.................................................................................................... 3-245 Figure 3.30-2 Breaker failure initiation logic ........................................................................ 3-246 Figure 3.30-3 Blocking AR logic ............................................................................................ 3-247 Figure 3.31-1 Logic of VT circuit supervision ...................................................................... 3-250 Figure 3.31-2 Logic of VT neutral point supervision ........................................................... 3-250 Figure 3.32-1 Logic diagram of CT circuit failure ................................................................ 3-252 Figure 3.33-1 Synchrocheck mode selection for manual closing...................................... 3-254 Figure 3.33-2 Logic diagram of closing circuit breaker 1 ................................................... 3-255 Figure 3.33-3 Logic diagram of closing circuit breaker 2 ................................................... 3-255 Figure 3.33-4 Logic diagram of closing switch (xx=02~15) ................................................ 3-256 Figure 3.33-5 Logic diagram of open circuit breaker .......................................................... 3-257 Figure 3.33-6 Logic diagram of open switch (xx=02~15) .................................................... 3-258 Figure 3.33-7 Configuration page of control output 01 (default configuration) ............... 3-260 Figure 3.33-8 Configuration page of control output 02 (default configuration) ............... 3-261 Figure 3.34-1 The region of faulty phase selection ............................................................. 3-271 Figure 3.34-2 The logic of faulty phase selection ................................................................ 3-273 Figure 3.35-1 Equivalent sequence network ........................................................................ 3-275 List of Tables Table 3.1-1 System parameters .................................................................................................. 3-1 3-n PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Table 3.2-1 Line parameters ....................................................................................................... 3-2 Table 3.3-1 I/O signals of frequency calculation ...................................................................... 3-3 Table 3.4-1 I/O signals of CB position supervision.................................................................. 3-5 Table 3.4-2 Internal settings of CB position supervision ........................................................ 3-8 Table 3.5-1 I/O signals of fault detector .................................................................................. 3-13 Table 3.5-2 Settings of fault detector ...................................................................................... 3-13 Table 3.6-1 I/O signals of auxiliary element ............................................................................ 3-17 Table 3.6-2 Settings of auxiliary element ................................................................................ 3-21 Table 3.7-1 I/O signals of DPFC distance protection ............................................................. 3-33 Table 3.7-2 Settings of DPFC distance protection ................................................................. 3-34 Table 3.7-3 I/O signals of load encroachment ........................................................................ 3-35 Table 3.7-4 Settings of load encroachment ............................................................................ 3-35 Table 3.7-5 I/O signals of distance protection (Mho) ............................................................. 3-42 Table 3.7-6 Settings of distance protection (Mho) ................................................................. 3-46 Table 3.7-7 I/O signals of distance protection (Quad) ........................................................... 3-50 Table 3.7-8 Settings of distance protection (Quad) ............................................................... 3-53 Table 3.7-9 Settings of pilot distance zone ............................................................................. 3-57 Table 3.7-10 I/O signals of out-of-step protection.................................................................. 3-63 Table 3.7-11 Settings of out-of-step protection ...................................................................... 3-65 Table 3.7-12 I/O signals of PSBR ............................................................................................. 3-69 Table 3.7-13 Settings of PSBR ................................................................................................. 3-72 Table 3.7-14 I/O signals of distance SOTF protection ........................................................... 3-73 Table 3.7-15 Settings of distance SOTF protection ............................................................... 3-78 Table 3.7-16 Internal settings of distance SOTF protection ................................................. 3-80 Table 3.8-1 I/O signals of pilot channel ................................................................................... 3-86 Table 3.8-2 Settings of pilot channel ....................................................................................... 3-87 Table 3.9-1 I/O signals of pilot distance protection ............................................................. 3-104 Table 3.9-2 Settings of pilot distance protection ................................................................. 3-106 Table 3.9-3 Internal settings of pilot distance protection.................................................... 3-107 Table 3.10-1 I/O signals of pilot directional earth-fault protection..................................... 3-116 3-o PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Table 3.10-2 Settings of pilot directional earth-fault protection ......................................... 3-117 Table 3.10-3 Internal settings of pilot distance protection.................................................. 3-118 Table 3.11-1 Direction description ......................................................................................... 3-120 Table 3.11-2 I/O signals of current direction ......................................................................... 3-124 Table 3.11-3 Settings of current direction ............................................................................. 3-125 Table 3.13-1 Inverse-time curve parameters......................................................................... 3-127 Table 3.13-2 I/O signals of phase overcurrent protection ................................................... 3-128 Table 3.13-3 Settings of phase overcurrent protection ....................................................... 3-130 Table 3.14-1 Inverse-time curve parameters......................................................................... 3-133 Table 3.14-2 I/O signals of earth fault protection ................................................................. 3-134 Table 3.14-3 Settings of earth fault protection ..................................................................... 3-137 Table 3.15-1 Inverse-time curve parameters......................................................................... 3-141 Table 3.15-2 I/O signals of negative-sequence overcurrent protection............................. 3-142 Table 3.15-3 Settings of negative-sequence overcurrent protection................................. 3-144 Table 3.16-1 Inverse-time curve parameters......................................................................... 3-147 Table 3.16-2 I/O signals of overcurrent protection for VT circuit failure ........................... 3-148 Table 3.16-3 Settings of overcurrent protection for VT circuit failure ............................... 3-150 Table 3.17-1 I/O signals of residual SOTF protection .......................................................... 3-153 Table 3.17-2 Settings of phase current SOTF protection .................................................... 3-155 Table 3.16-1 I/O signals of residual SOTF protection .......................................................... 3-157 Table 3.16-2 Settings of residual current SOTF protection ................................................ 3-158 Table 3.17-1 Inverse-time curve parameters......................................................................... 3-161 Table 3.17-2 I/O signals of overvoltage protection .............................................................. 3-162 Table 3.17-3 Settings of overvoltage protection .................................................................. 3-164 Table 3.17-4 I/O signals of negative-sequence overvoltage protection ............................ 3-165 Table 3.17-5 Settings of negative-sequence overvoltage protection ................................ 3-166 Table 3.19-6 Inverse-time curve parameters of residual overvoltage protection ............. 3-167 Table 3.19-7 I/O signals of residual overvoltage protection ............................................... 3-168 Table 3.19-8 Settings of residual overvoltage protection ................................................... 3-170 Table 3.19-9 Inverse-time curve parameters of phase undervoltage protection .............. 3-173 3-p PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Table 3.19-10 I/O signals of undervoltage protection .......................................................... 3-173 Table 3.19-11 Settings of undervoltage protection .............................................................. 3-176 Table 3.18-1 I/O signals of overfrequency protection.......................................................... 3-179 Table 3.18-2 Settings of overfrequency protection.............................................................. 3-180 Table 3.18-3 I/O signals of underfrequency protection ....................................................... 3-181 Table 3.18-4 Settings of underfrequency protection ........................................................... 3-182 Table 3.21-1 I/O signals of breaker failure protection.......................................................... 3-185 Table 3.21-2 Settings of breaker failure protection.............................................................. 3-187 Table 3.20-1 I/O signals of thermal overload protection ..................................................... 3-189 Table 3.20-2 Settings of thermal overload protection ......................................................... 3-190 Table 3.21-1 I/O signals of stub differential protection ....................................................... 3-193 Table 3.21-2 Settings of stub differential protection ........................................................... 3-194 Table 3.22-1 I/O signals of dead zone protection ................................................................. 3-196 Table 3.22-2 Settings of dead zone protection ..................................................................... 3-197 Table 3.23-1 I/O signals of pole discrepancy protection ..................................................... 3-198 Table 3.23-2 Settings of pole discrepancy protection ......................................................... 3-199 Table 3.24-1 I/O signals of broken conductor protection .................................................... 3-201 Table 3.24-2 Settings of broken conductor protection ........................................................ 3-202 Table 3.25-1 I/O signals of reverse power protection .......................................................... 3-203 Table 3.25-2 Settings of broken conductor protection ........................................................ 3-205 Table 3.28-1 I/O signals of synchrocheck ............................................................................. 3-215 Table 3.28-2 Synchrocheck settings ..................................................................................... 3-219 Table 3.29-1 I/O signals of auto-reclosing ............................................................................ 3-223 Table 3.29-2 Reclosing number.............................................................................................. 3-235 Table 3.29-3 Auto-reclosing settings ..................................................................................... 3-237 Table 3.28-1 I/O signals of transfer trip ................................................................................. 3-240 Table 3.28-2 Settings of transfer trip ..................................................................................... 3-240 Table 3.29-1 I/O signals of trip logic ...................................................................................... 3-242 Table 3.29-2 Settings of trip logic .......................................................................................... 3-248 Table 3.30-1 I/O signals of VT circuit supervision ............................................................... 3-249 3-q PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Table 3.30-2 VTS settings ....................................................................................................... 3-251 Table 3.31-1 I/O signals of CT circuit supervision ............................................................... 3-252 Table 3.32-1 I/O signals of control ......................................................................................... 3-265 Table 3.32-2 Function settings ............................................................................................... 3-266 Table 3.32-3 Synchrocheck settings ..................................................................................... 3-266 Table 3.32-4 Dual point binary input settings....................................................................... 3-269 Table 3.32-5 Control settings ................................................................................................. 3-269 Table 3.32-6 Interlock settings ............................................................................................... 3-269 Table 3.33-1 Relation between ΔUOΦMAX and faulty phase.............................................. 3-271 Table 3.33-2 I/O signals of faulty phase selection ............................................................... 3-273 Table 3.34-1 I/O signals of fault location ............................................................................... 3-278 3-r PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.1 System Parameters 3.1.1 General Application The device performs various protection functions by respective algorithms with the information (currents and voltages) acquired from primary system through current transformer and voltage transformer, so it is important to configure analog input channels correctly. Further to correct configuration of analog input channels, other protected system information, such as the parameters of voltage transformer and current transformer are also required. 3.1.2 Function Description The device generally considers transmission line as its protected object, current flows from busbar to line is considered as the forward direction. The device uses a sampling rate of 24 samples per cycle, and the amplitudes of voltage and current are calculated through fourier filter algorithm. The data window is 1 cycle, and the actual amplitude can be achieved when the cycle is expired. Two cycles of pre-fault voltage are memorized when three-phase voltage drops suddenly due to a close up symmetrical solid fault. 3.1.3 Settings Table 3.1-1 System parameters No. Name Range Step Unit 1 Active_Grp 1~20 1 2 Opt_SysFreq 50 or 60 3 PrimaryEquip_Name 4 U1n 10.00~65500.00 0.01 kV 5 U2n 80.00~220.00 0.01 V 6 CBx.I1n 100~30000 1 A Remark Active setting group Hz System frequency The name of primary equipment Primary rated value of VT (phase to phase) Secondary rated value of VT (phase to phase) Primary rated value of CT corresponding to circuit breaker No.x Primary calculation base rated current of 7 I1n_Base 100~30000 1 A CT, and generally set as same as [CB1.I1n] 8 I2n_Base 1 or 5 A Secondary calculation base rated current of CT Frequency upper limit setting 9 f_High_FreqAlm 50~65 1 Hz The device will issue an alarm [Alm_Freq], when system frequency is higher than the setting. Frequency lower limit setting 10 f_Low_FreqAlm 45~60 1 Hz The device will issue an alarm [Alm_Freq], when system frequency is 3-1 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory No. Name Range Step Unit Remark lower than the setting. 3.2 Line Parameters 3.2.1 General Application When the device equips with line protection functions, line parameters of protected line are required, especially for fault location, precise line parameters are the basic criterion for accurate fault location. 3.2.2 Function Description Line parameters mainly include positive-sequence reactance, positive-sequence resistance, zero-sequence reactance, zero-sequence resistance, mutual zero-sequence reactance, mutual zero-sequence resistance and line length. The positive-sequence reactance, zero-sequence reactance, positive-sequence resistance and zero-sequence resistance are the reactance and resistance value of the whole line. In general, the device locates the fault through calculating the impedance value from the location of the device to fault point. 3.2.3 Settings Table 3.2-1 Line parameters No. Name Range Step Unit 1 X1L (0.000~4Unn)/In 0.001 ohm 2 R1L (0.000~4Unn)/In 0.001 ohm 3 X0L (0.000~4Unn)/In 0.001 ohm 4 R0L (0.000~4Unn)/In 0.010 ohm 5 X0M (0.000~4Unn)/In 0.001 ohm 6 R0M (0.000~4Unn)/In 0.001 ohm 7 LineLength 0.00~655.35 0.01 km Remark Positive-sequence reactance of the whole line (secondary value) Positive-sequence resistance of the whole line (secondary value) Zero-sequence reactance of the whole line (secondary value) Zero-sequence resistance of the whole line (secondary value) Zero-sequence mutual reactance (secondary value) Zero-sequence mutual resistance of the whole line (secondary value) Total length of the whole line 3.3 Frequency Calculation 3.3.1 General Application System frequency is an important parameter to characterize power system, and the measurement and calculation of system frequency are the basis of many protection functions. The frequency calculation module can accurately calculate the frequency of voltage component. 3-2 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.3.2 Function Description The device can be applied to the power system within frequency range of 40Hz~63Hz, the reference frequency can be set as 50Hz or 60Hz via the system setting [Opt_SysFreq]. The device provide frequency track function, which can improve the accuracy of protection algorithms and the performance of protection functions. For the power system using 50Hz or 60Hz as reference frequency, the frequency track function can be disabled if the fluctuation of the frequency range is not great. For the power system that the fluctuation of the frequency range is great, the frequency track function can be enabled to improve protection performance. It adopts the positive-sequence voltage which derived from protection used voltage as the calculation reference, the positive-sequence voltage can be calculated as following: U1 (U a U b e j120 U c e j 240) / 3 When no VT is connected to the device, the frequency track function is disabled automatically, and then the device calculates protection algorithm using the system reference frequency. When the device detects a fault happening to the power system or the voltage is smaller than 0.15Un, the frequency track function is disabled. 3.3.3 Function Block Diagram FreqCal FreqTrack fn f Alm_Freq 3.3.4 I/O Signal Table 3.3-1 I/O signals of frequency calculation No. Input Signal 1 FreqTrack 2 fn No. Description It is used to enabled or disable frequency track function by the configuration software PCS-Explorer. It is the system frequency, which is decided by the setting [Opt_SysFreq]. Output Signal Description 1 f Frequency calculation result 2 Alm_Freq Frequency abnormality alarm 3-3 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.3.5 Logic SIG U3P Frequency calculation SIG fn f SIG FreqTrack SIG f<[f_Low_FreqAlm] >=1 Alm_Freq SIG f>[f_High_FreqAlm] Figure 3.3-1 Logic diagram of frequency calculation 3.4 Circuit Breaker Position Supervision 3.4.1 General Application The status of circuit breaker (CB) position is applied for protection and control functions in this device, such as, SOTF protection, auto-reclose and VT circuit supervision, etc. The status of CB position can be applied as input signals for other features configured by user. 3.4.2 Function Description The signal reflecting CB position is acquired via opto-coupler with settable delay pickup and dropoff, and forms digital signal used by protection functions. CB position can reflect the status of each phase by means of phase-segregated inputs. In order to prevent that wrong status of CB position is input into the device via binary input, appropriate monitor method is used to check the rationality of the binary input. When the binary input of CB open position is detected, the status of CB position will be thought as incorrect and an alarm [Alm_52b] will be issued if there is current detected in the line. Together with the status of circuit breaker and the information of external circuit, this function can be used to supervise control circuit of circuit breaker. External manual closing binary input (ManCls) is only used for SOTF logic application, the control of circuit breaker (CB) closing or opening should refer to section 3.29 (Control and Synchrocheck for Manual Closing). 3.4.3 Function Block Diagram 1. For phase-segregated circuit breaker 3-4 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory CB Position Supervision CBx.52b_PhA CBx.Alm_52b CBx.52b_PhB CBx.52b_PhC CBx.ManCls CBx.Test 2. For non-phase segregated circuit breaker CB Position Supervision CBx.52b CBx.Alm_52b CBx.ManCls CBx.Test 3. Trip&closing circuit supervision (TCCS) TCCS CBx.52a CBx.TCCS.Alm CBx.52b CBx.TCCS.Input CBx.ManCls CBx.Test TCCS will be disabled automatically when it is used for phase-segregated circuit breaker. x=1 or 2 3.4.4 I/O Signals Table 3.4-1 I/O signals of CB position supervision No. Input Signal Description 1 CBx.52b_PhA Normally closed contact of A-phase of circuit breaker No.x 2 CBx.52b_PhB Normally closed contact of B-phase of circuit breaker No.x 3 CBx.52b_PhC Normally closed contact of C-phase of circuit breaker No.x Maintenance status binary input of circuit breaker No.x 4 CBx.Test If any circuit breaker is in maintenance and out of service, CBx.52b or CBx.Test should be set as “1” in fixed, and CB No.x will not be take effect in corresponding protection logics. (CB position supervision is still kept.) It is only available for 3-5 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory double circuit breakers mode. External manual closing binary input of circuit breaker No.x, it is only applied to 5 CBx.ManCls 6 CBx.52b Normally closed contact of three-phase of circuit breaker No.x 7 CBx.52a Normally open contact of three-phase of circuit breaker No.x SOTF logic Control circuit failure of circuit breaker No.x (normally closed contacts of tripping 8 CBx.TCCS.Input position (52b) and closing position (52a) of three-phase circuit breaker are all de-energized due to DC power loss of control circuit) No. Output Signal Description 1 CBx.Alm_52b Circuit breaker No.x position is abnormal 2 CBx.TCCS.Alm Control circuit of circuit breaker No.x is abnormal NOTICE! The signal [CBx.52a] only take effect in the tripping/closing circuit supervision and not affect any protection function. Only if tripping/closing circuit supervision is configured, this signal needs to be connected to the device. 3.4.5 Logic BI [CBx.52b_PhA] >=1 & & BI [CBx.52b_PhB] >=1 & & >=1 10s BI [CBx.52b_PhC] BI [CBx.52b] >=1 >=1 10s CBx.Alm_52b & & SIG CBx.Ia>I_Line & >=1 SIG CBx.Ib>I_Line & SIG CBx.Ic>I_Line Figure 3.4-1 Logic diagram of CB position supervision 3-6 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory BI [CBx.52a] BI [CBx.52b] BI [CBx.TCCS.Input] >=1 >=1 [CBx.TCCS.t_DPU] [CBx.TCCS.t_DDO] CBx.TCCS.Alm Figure 3.4-2 Logic diagram of trip&closing circuit supervision BI [CB1.52b_PhA] >=1 & 52b_PhA BI [CB1.52b_PhB] BI [CB1.52b_PhC] BI [CB1.52b] BI [CB1.Test] BI [CB2.52b_PhA] >=1 BI [CB2.52b_PhB] >=1 BI [CB2.52b_PhC] BI [CB2.52b] BI [CB2.Test] >=1 >=1 & 52b_PhB & >=1 52b_PhC Figure 3.4-3 Logic diagram of circuit breaker position x=1 or 2 I_Line is threshold value used to determine whether line is on-load or no-load. Default value 0.06In. If there is any single phase tripping or breaker status [52b_Phx]=1 (x can be A, B or C) and corresponding phase current is smaller than 0.06IN, then single pole open state is confirmed by the device. If there is three pole tripping or breaker status of three phases are all open and three phase currents are all smaller than 0.06IN, then three pole open state is confirmed by the device. 3-7 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory & SIG 52b_PhA 50ms 0ms 50ms 0ms 50ms 0ms SIG Ia<I_Line SIG 52b_PhB & SIG Ib<I_Line SIG 52b_PhC & SIG Ic<I_Line >=1 SIG Trp A S SET Pole A open & Q 50ms SIG FD.Pkp R CLR 0ms Q SIG Ia<I_Line >=1 SIG Trp B S SET Q Pole B open & 50ms R CLR 0ms Q SIG Ib<I_Line >=1 SIG Trp C S SET Pole C open & Q 50ms R CLR 0ms Q SIG Ic<I_Line Figure 3.4-4 Logic diagram of pole open states Where: TrpA, TrpB and TrpC are the tripping signals of the device. 3.4.6 Settings Table 3.4-2 Internal settings of CB position supervision No. Name Default Value Unit 1 CBx.TCCS.t_DPU 0.5 s 2 CBx.TCCS.t_DDO 0.5 s Remark Pickup delay time of control circuit failure alarm for circuit breaker No.x (x=1 or 2) Dropoff delay time of control circuit failure alarm for circuit breaker No.x (x=1 or 2) 3.5 Fault Detector (FD) 3.5.1 Application The device has one DSP module with fault detector DSP and protection DSP for fault detector and protection calculation respectively. Protection DSP with protection fault detector element is responsible for calculation of protection elements, and fault detector DSP is responsible to determine fault appearance on the protected power system. Fault detector in fault detector DSP 3-8 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory picks up to provide positive supply to output relays. The output relays can only operate when both the fault detector in fault detector DSP and a protection element operate simultaneously. Otherwise, the output relays would not operate. An alarm message will be issued with blocking outputs if a protection element operates while the fault detector does not operate. 3.5.2 Fault Detector in Fault Detector DSP Main part of FD is DPFC current detector element that detects the change of phase-to-phase power frequency current, and residual current fault detector element that calculates the vector sum of 3 phase currents as supplementary. They are continuously calculating the analog input signals. All fault detectors in this device include: 1. Fault detector based on DPFC current: DPFC current is greater than the setting value 2. Fault detector based on residual current: Residual current is greater than the setting value 3. Fault detector based on negative-sequence current: Negative-sequence current is greater than the setting value 4. Fault detector based on phase current: Phase current is greater than the setting value 5. Fault detector based on voltage: Phase voltage or phase-to-phase voltage is greater than the setting value 6. Fault detector based on circuit breaker position: Circuit breaker position discrepancy 7. Fault detector based on thermal overload logic: Thermal overload pickup 8. Fault detector based on protection elements: Frequency element pickup, broken conductor element pickup, reverse power element pickup, power swing element pickup, breaker failure element pickup, phase overcurrent with VT failure element pickup and transfer trip element pickup. If any of the above conditions is complied, FD will operate to activate the output circuit providing DC power supply to the output relays. The fault detector based on DPFC current and the fault detector based on residual current are always enabled, and all protection functions are permitted to operate when they operate. 3.5.2.1 Fault Detector Based on DPFC Current DPFC phase-to-phase current is obtained by subtracting the phase-to-phase current from that of a cycle before. I(k) is the sampling value at a point. I(k-24) is the value of a sampling point before a cycle, 24 is the sampling points in one cycle. 3-9 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 200 100 0 -100 -200 0 20 40 60 Original Current 80 100 120 0 20 40 60 DPFC current 80 100 120 100 50 0 -50 -100 From above figures, it is concluded that DPFC can reflect the sudden change of current at the initial stage of a fault and has a perfect performance of fault detection. It is used to determine whether this pickup condition is met according to Equation 3.5-1. For multi-phase short-circuit fault, DPFC phase-to-phase current has high sensitivity to ensure the pickup of protection device. For usual single phase to earth fault, it also has sufficient sensitivity to pick up except the earth fault with very large fault resistance. Under this condition, DPFC current is relative small, however, residual current is also used to judge pickup condition. This element adopts adaptive floating threshold varied with the change of load current continuously. The change of load current is small and steady under normal or power swing condition, the adaptive floating threshold with the ΔI Set is higher than the change of current under these conditions and hence maintains the element stability. The criterion is: ΔIΦΦMAX>1.25ΔITh+ΔISet Equation 3.5-1 Where: ΔIΦΦMAX: The maximum half-wave integration value of phase-to-phase current (ΦΦ=AB, BC, CA) ΔISet: The fixed threshold value (i.e. the setting [FD.DPFC.I_Set]) ΔITh: The floating threshold value The coefficient, 1.25, is an empirical value which ensures the threshold always higher than the unbalance output value of the system. If operation condition is met, the fault detector based on DPFC current will operate to provide DC power supply for output relays, the pickup signal will maintain 5s after the fault detector based on DPFC current drops off. 3-10 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.5.2.2 Fault Detector Based on Residual Current The operation condition will be met when 3I0 is greater than the setting [FD.ROC.3I0_Set]. The fault detector based on residual current is always in service. Where: 3I0: residual current calculates from the vector sum of Ia, Ib and Ic When the fault detector based on residual current operates and lasts for longer than 10 seconds, an alarm [Alm_Pkp_I0] will be issued. If operation condition is met, the fault detector based on residual current will operate to provide DC power supply for output relay, and the pickup signal will maintain 5s after the fault detector based on residual current drops off. 3.5.2.3 Fault Detector Based on Negative-sequence Current The operation condition will be met when negative-sequence current (I2) is greater than the setting [FD.NOC.I2_Set]. It can be enabled or disabled by the logic setting [FD.NOC.En]. If operation condition is met, the fault detector based on negative-sequence current will operate to provide DC power supply for output relay, and the pickup signal will maintain 5s after the fault detector based on negative-sequence current drops off. 3.5.2.4 Fault Detector Based on Phase Current The fault detector based on phase current will operate to provide DC power supply for output relay when phase overcurrent protection is enabled and meets the operation condition, and the pickup signal will maintain 500ms after the fault detector based on phase current drops off. 3.5.2.5 Fault Detector Based on Voltage This fault detector based on voltage includes the fault detectors of overvoltage protection, undervoltage protection and frequency protection. The fault detector based on voltage will operate to provide DC power supply for output relay when corresponding voltage element is enabled and meets the operation condition, and the pickup signal will maintain 500ms after the fault detector based on voltage drops off. 3.5.2.6 Fault Detector Based on Circuit Breaker Position When pole discrepancy protection is enabled, i.e. the logic setting [62PD.En] is set as “1”, and if three phases of circuit breaker are not in the same status, the fault detector based on circuit breaker position will operate to provide DC power supply for output relays, and the pickup signal will maintain 500ms after the fault detector based on circuit breaker position drops off. 3.5.2.7 Fault Detector Based on Thermal Overload Logic The fault detector based on thermal overload logic will operate to provide DC power supply for output relay when tripping logic of thermal overload protection meets the operation condition, and the pickup signal will maintain 500ms after the fault detector based on thermal overload logic drops off. 3-11 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.5.2.8 Fault Detector Based on Protection Element The fault detector based on protection element will operate to provide DC power supply for output relay when these protection element are enabled and meet the operation condition, and the pickup signal will maintain 500ms after the fault detector based on protection element drops off. 3.5.3 Protection Fault Detector in Protection Calculation DSP The protection device is running either of the two programs: one is “Regular program” for normal state, and the other is “Fault calculation program” after protection fault detector picks up. Under the normal state, the protection device will perform the following tasks: 1. Calculate analog quantity 2. Read binary input 3. Hardware self-check 4. Circuit breaker position supervision 5. Analog quantity input supervision 6. Channel supervision Once the protection fault detector element in protection calculation DSP picks up, the protection device will switch to fault calculation program, for example the calculation of distance protection, and to determine logic. If the fault is within the protected zone, the protection device will send tripping command. The protection program flow chart is shown as Figure 3.5-1. Main program Sampling program No Regular program Yes Pickup? Fault calculation program Figure 3.5-1 Flow chart of protection program The protection FD pickup conditions are the same as the FD in fault detector DSP as shown below. The operation criteria for the conditions are also the same as that in fault detector DSP. Please refer to section 3.5.2 for details. 3-12 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.5.4 Function Block Diagram FD FD.Pkp FD.DPFC.Pkp FD.ROC.Pkp FD.NOC.Pkp 3.5.5 I/O Signals Table 3.5-1 I/O signals of fault detector No. Output Signal Description 1 FD.Pkp The device picks up 2 FD.DPFC.Pkp DPFC current fault detector element operates. 3 FD.ROC.Pkp Residual current fault detector element operates. 4 FD.NOC.Pkp Negative-sequence fault detector element operates. 3.5.6 Logic SIG Ia SIG Ib SIG Ic Calculate DPFC phase-tophase current: Δ Iab=Δ (Ia-Ib) Δ Ibc=Δ (Ib-Ic) Δ Ica=Δ (Ic-Ia) Δ Iab>[FD.DPFC.I_Set] >=1 Δ Ibc>[FD.DPFC.I_Set] FD.DPFC.Pkp Δ Ica>[FD.DPFC.I_Set] >=1 0s Calculate residual current: 3I0=Ia+Ib+Ic 3I0>[FD.ROC.3I0_Set] Calculate negativesequence current: I2 I2>[FD.NOC.I2_Set] 5s FD.Pkp FD.ROC.Pkp & FD.NOC.Pkp EN FD.NOC.En Figure 3.5-2 Logic diagram of fault detector 3.5.7 Settings Table 3.5-2 Settings of fault detector No. Name Range Step Unit 1 FD.DPFC.I_Set (0.050~30.000)×In 0.001 A 2 FD.ROC.3I0_Set (0.050~30.000)×In 0.001 A 3 FD.NOC.I2_Set (0.050~30.000)×In 0.001 A Remark Current setting of DPFC current fault detector element Current setting of residual current fault detector element Current setting of negative-sequence 3-13 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory No. Name Range Step Unit Remark current fault detector element Enabling/disabling negative-sequence 4 FD.NOC.En current fault detector element 0 or 1 0: disable 1: enable 3.6 Auxiliary Element 3.6.1 General Application Auxiliary element (AuxE) is mainly used to program logics to meet users’ applications or further improve operating reliability of protection elements. Reliability of protective elements (such as distance element or current differential element) is assured, auxiliary element is usually not required to configure. Auxiliary elements including current change auxiliary element (AuxE.OCD), residual current auxiliary element (AuxE.ROC), phase current auxiliary element (AuxE.OC), voltage change auxiliary element (AuxE.UVD), phase under voltage auxiliary element (AuxE.UVG), phase-to-phase under voltage auxiliary element (AuxE.UVS) and residual voltage auxiliary element (AuxE.ROV), and they can be enabled or disabled by corresponding logic setting or binary inputs. Users can configure them according to applications via PCS-Explorer software. 3.6.2 Function Description 1. Current change auxiliary element AuxE.OCD It shares DPFC current element of DPFC fault detector. If DPFC fault detector operates (FD.DPFC.Pkp=1) and current change auxiliary element is enabled, current change auxiliary element operates. 2. Residual current auxiliary element AuxE.ROC There are 3 stages for residual current auxiliary element (AuxE.ROC1, AuxE.ROC2 and AuxE.ROC3). Each residual current auxiliary element will operate instantly if calculated residual current amplitude is larger than corresponding current setting The criteria are: AuxE.ROC1: 3I0>[AuxE.ROC1.3I0_Set] AuxE.ROC2: 3I0>[AuxE.ROC2.3I0_Set] AuxE.ROC3: 3I0>[AuxE.ROC3.3I0_Set] Where: 3I0: The calculated residual current 3. Phase current auxiliary element AuxE.OC There are 3 stages for phase current auxiliary element (AuxE.OC1, AuxE.OC2 and AuxE.OC3). Each phase current auxiliary element will operate instantly if phase current amplitude is larger than 3-14 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory corresponding current setting. The criteria are: AuxE.OC1: IΦMAX>[AuxE.OC1.I_Set] AuxE.OC2: IΦMAX>[AuxE.OC2.I_Set] AuxE.OC3: IΦMAX>[AuxE.OC3.I_Set] Where: IΦMAX: The maximum phase current among three phases 4. Voltage change auxiliary element AuxE.UVD AuxE.UVD is based on phase-to-ground voltage change measured in all three phases. The criterion is: Δ UΦMAX>[AuxE.UVD.U_Set] Where: ΔUΦMAX: The maximum phase-to-ground voltage change among three phases 5. Phase under voltage auxiliary element AuxE.UVG AuxE.UVG will operate instantly if any phase-to-ground voltage is lower than corresponding voltage setting. The criterion is: UΦMIN<[AuxE.UVG.U_Set] Where: UΦMIN: The minimum value among three phase-to-ground voltages 6. Phase-to-phase under voltage auxiliary element AuxE.UVS AuxE.UVS will operate instantly if any phase-to-phase voltage is lower than corresponding voltage setting. The criterion is: UΦΦMIN<[AuxE.UVS.U_Set] Where: UΦΦMIN: The minimum value among three phase-to-phase voltages 7. Residual voltage auxiliary element AuxE.ROV AuxE.ROV will operate instantly if calculated residual voltage is larger than corresponding voltage setting. The criterion is: 3-15 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3U0>[AuxE.ROV.3U0_Set] Where: 3U0: The calculated residual voltage 3.6.3 Function Block Diagram AuxE AuxE.OCD.En AuxE.St AuxE.OCD.Blk AuxE.OCD.St_DDO AuxE.ROCi.En AuxE.OCD.On AuxE.ROCi.Blk AuxE.ROCi.St AuxE.OCi.En AuxE.ROCi.On AuxE.OCi.Blk AuxE.OCi.St AuxE.UVD.En AuxE.OCi.StA AuxE.UVD.Blk AuxE.OCi.StB AuxE.UVG.En AuxE.OCi.StC AuxE.UVG.Blk AuxE.OCi.On AuxE.UVS.En AuxE.UVD.St AuxE.UVS.Blk AuxE.UVD.St_DDO AuxE.ROV.En AuxE.UVD.On AuxE.ROV.Blk AuxE.UVG.St AuxE.UVG.StA AuxE.UVG.StB AuxE.UVG.StC AuxE.UVG.On AuxE.UVS.St AuxE.UVS.StAB AuxE.UVS.StBC AuxE.UVS.StCA AuxE.UVS.On AuxE.ROV.St AuxE.ROV.On 3-16 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.6.4 I/O Signals Table 3.6-1 I/O signals of auxiliary element No. Input Signal 1 AuxE.OCD.En 2 AuxE.OCD.Blk 3 AuxE.ROCi.En 4 AuxE.ROCi.Blk 5 AuxE.OCi.En 6 AuxE.OCi.Blk 7 AuxE.UVD.En 8 AuxE.UVD.Blk 9 AuxE.UVG.En 10 AuxE.UVG.Blk 11 AuxE.UVS.En 12 AuxE.UVS.Blk 13 AuxE.ROV.En 14 AuxE.ROV.Blk No. Output Signal Description Current change auxiliary element enabling input, it is triggered from binary input or programmable logic etc. Current change auxiliary element blocking input, it is triggered from binary input or programmable logic etc. Stage i of residual current auxiliary element enabling input, it is triggered from binary input or programmable logic etc. (i=1, 2, 3) Stage i of residual current auxiliary element blocking input, it is triggered from binary input or programmable logic etc. (i=1, 2, 3) Stage 1 of phase current auxiliary element enabling input, it is triggered from binary input or programmable logic etc. (i=1, 2, 3) Stage 1 of phase current auxiliary element blocking input, it is triggered from binary input or programmable logic etc. (i=1, 2, 3) Voltage change auxiliary element enabling input, it is triggered from binary input or programmable logic etc. Voltage change auxiliary element blocking input, it is triggered from binary input or programmable logic etc. Phase-to-ground under voltage auxiliary element enabling input, it is triggered from binary input or programmable logic etc. Phase-to-ground under voltage auxiliary element blocking input, it is triggered from binary input or programmable logic etc. Phase-to-phase under voltage auxiliary element enabling input, it is triggered from binary input or programmable logic etc. Phase-to-phase under voltage auxiliary element blocking input, it is triggered from binary input or programmable logic etc. Residual voltage auxiliary element enabling input, it is triggered from binary input or programmable logic etc. Residual voltage auxiliary element blocking input, it is triggered from binary input or programmable logic etc. Description 1 AuxE.St Any auxiliary element of the device operates. 2 AuxE.OCD.St_DDO Current change auxiliary element operates. 3 AuxE.OCD.On Current change auxiliary element is enabled. 4 AuxE.ROCi.St Stage 1 of residual current auxiliary element operates. (i=1, 2, 3) 5 AuxE.ROCi.On Stage 1 of residual current auxiliary element is enabled. (i=1, 2, 3) 6 AuxE.OCi.St Stage 1 of phase current auxiliary element operates. (i=1, 2, 3) 7 AuxE.OCi.StA Stage 1 of phase current auxiliary element operates (phase A). (i=1, 2, 3) 8 AuxE.OCi.StB Stage 1 of phase current auxiliary element operates (phase B). (i=1, 2, 3) 9 AuxE.OCi.StC Stage 1 of phase current auxiliary element operates (phase C). (i=1, 2, 3) 10 AuxE.OCi.On Stage 1 of phase current auxiliary element is enabled. (i=1, 2, 3) 3-17 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 11 AuxE.UVD.St Voltage change auxiliary element operates. 12 AuxE.UVD.St_DDO Voltage change auxiliary element operates. 13 AuxE.UVD.On Voltage change auxiliary element is enabled. 14 AuxE.UVG.St Phase-to-ground under voltage auxiliary element operates. 15 AuxE.UVG.StA Phase-to-ground under voltage auxiliary element operates (phase A). 16 AuxE.UVG.StB Phase-to-ground under voltage auxiliary element operates (phase B). 17 AuxE.UVG.StC Phase-to-ground under voltage auxiliary element operates (phase C). 18 AuxE.UVG.On Phase-to-ground under voltage auxiliary element is enabled. 19 AuxE.UVS.St Phase-to-phase under voltage auxiliary element operates. 20 AuxE.UVS.StAB Phase-to-phase under voltage auxiliary element operates (phase AB). 21 AuxE.UVS.StBC Phase-to-phase under voltage auxiliary element operates (phase BC). 22 AuxE.UVS.StCA Phase-to-phase under voltage auxiliary element operates (phase CA). 23 AuxE.UVS.On Phase-to-phase under voltage auxiliary element is enabled. 24 AuxE.ROV.St Residual voltage auxiliary element operates. 25 AuxE.ROV.On Residual voltage auxiliary element is enabled. 3.6.5 Logic SET 3I0>[AuxE.ROCi.3I0_Set] SIG AuxE.ROCi.En SIG AuxE.ROCi.Blk EN AuxE.ROCi.En & AuxE.ROCi.St & AuxE.ROCi.On Figure 3.6-1 Logic diagram of auxiliary element (ROC) SIG 3U0>[AuxE.ROV.3U0_Set] SIG AuxE.ROV.En SIG AuxE.ROV.Blk EN AuxE.ROV.En & AuxE.ROV.St & AuxE.ROV.On Figure 3.6-2 Logic diagram of auxiliary element (ROV) 3-18 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory SIG AuxE.OCi.En SIG AuxE.OCi.Blk EN AuxE.OCi.En & AuxE.OCi.On SET Ia>[AuxE.OCi.I_Set] & AuxE.OCi.StA SET Ib>[AuxE.OCi.I_Set] & AuxE.OCi.StB SET Ic>[AuxE.OCi.I_Set] & AuxE.OCi.StC SET Ia>[AuxE.OCi.I_Set] & AuxE.OCi.St >=1 SET Ib>[AuxE.OCi.I_Set] SET Ic>[AuxE.OCi.I_Set] Figure 3.6-3 Logic diagram of auxiliary element (OC) SIG AuxE.UVG.En SIG AuxE.UVG.Blk EN AuxE.UVG.En SET UA<[AuxE.UVG.U_Set] & AuxE.UVG.On & AuxE.UVG.StA SET UB<[AuxE.UVG.U_Set] & AuxE.UVG.StB SET UC<[AuxE.UVG.U_Set] & AuxE.UVG.StC SET UA<[AuxE.UVG.U_Set] SET UB<[AuxE.UVG.U_Set] SET UC<[AuxE.UVG.U_Set] & >=1 AuxE.UVG.St Figure 3.6-4 Logic diagram of auxiliary element (UVG) 3-19 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory SIG AuxE.UVS.En SIG AuxE.UVS.Blk EN AuxE.UVS.En SET UA<[AuxE.UVS.U_Set] & AuxE.UVS.On & AuxE.UVS.StA SET UB<[AuxE.UVS.U_Set] & AuxE.UVS.StB SET UC<[AuxE.UVS.U_Set] & AuxE.UVS.StC SET UA<[AuxE.UVS.U_Set] SET UB<[AuxE.UVS.U_Set] SET UC<[AuxE.UVS.U_Set] & AuxE.UVS.St >=1 Figure 3.6-5 Logic diagram of auxiliary element (UVS) SET Δ Ua>[AuxE.UVD.U_Set] SET Δ Ub>[AuxE.UVD.U_Set] SET Δ Uc>[AuxE.UVD.U_Set] SIG AuxE.UVD.En SIG AuxE.UVD.Blk EN AuxE.UVD.En >=1 & AuxE.UVD.St 0s [AuxE.UVD.t_DDO] AuxE.UVD.St_DDO & AuxE.UVD.On Figure 3.6-6 Logic diagram of auxiliary element (UVD) SIG AuxE.OCD.En SIG AuxE.OCD.Blk AuxE.OCD.On EN AuxE.OCD.En & & 0s [AuxE.OCD.t_DDO] SIG AuxE.OCD.St_DDO FD.DPFC.Pkp Figure 3.6-7 Logic diagram of auxiliary element (OCD) 3-20 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory SIG AuxE.OCD.St_DDO SIG AuxE.ROC1.St SIG AuxE.ROC2.St SIG AuxE.ROC3.St SIG AuxE.OC1.St SIG AuxE.OC2.St SIG AuxE.OC3.St SIG AuxE.UVD.St_DDO SIG AuxE.UVG.St SIG AuxE.UVS.St SIG AuxE.ROV.St >=1 >=1 >=1 AuxE.St >=1 >=1 >=1 >=1 Figure 3.6-8 Logic diagram of auxiliary element (Startup) Where: i=1, 2, 3 Calculate residual current: 3I0=Ia+Ib+Ic Calculate DPFC phase voltage: △Ua=△(Ua-Ufa), △Ub=△(Ub-Ufb), △Uc=△(Uc-Ufc) Calculate residual voltage: 3U0=Ua+Ub+Uc 3.6.6 Settings Table 3.6-2 Settings of auxiliary element No. 1 Name AuxE.OCD.t_DDO Range 0.000~10.000 Step Unit 0.001 s Remark Drop-off time delay of current change auxiliary element Enabling/disabling 2 AuxE.OCD.En current change auxiliary element 0 or 1 0: disable 1: enable 3 AuxE.ROCi.3I0_Set (0.050~30.000)×In 0.001 A Current setting of stage i residual current auxiliary element (i=1, 2, 3) Enabling/disabling 4 AuxE.ROCi.En stage i residual current auxiliary element (i=1, 2, 3) 0 or 1 0: disable 1: enable 5 AuxE.OCi.I_Set (0.050~30.000)×In Current setting of stage i phase current 3-21 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory No. Name Range Step Unit Remark auxiliary element (i=1, 2, 3) Enabling/disabling 6 AuxE.OCi.En stage i phase current auxiliary element (i=1, 2, 3) 0 or 1 0: disable 1: enable 7 AuxE.UVD.U_Set 0~Un 0.001 V 8 AuxE.UVD.t_DDO 0.000~10.000 0.001 s Voltage setting for voltage change auxiliary element Drop-off time delay of voltage change auxiliary element Enabling/disabling 9 AuxE.UVD.En voltage change auxiliary element 0 or 1 0: disable 1: enable 10 AuxE.UVG.U_Set 0~Un 0.001 V Voltage setting for phase-to-ground under voltage auxiliary element Enabling/disabling 11 AuxE.UVG.En phase-to-ground under voltage auxiliary element 0 or 1 0: disable 1: enable 12 AuxE.UVS.U_Set 0~Unn 0.001 V Voltage setting for under voltage auxiliary element Enabling/disabling 13 AuxE.UVS.En phase-to-phase phase-to-phase under voltage auxiliary element 0 or 1 0: disable 1: enable 14 AuxE.ROV.3U0_Set 0~Un 0.001 V Voltage setting for residual voltage auxiliary element Enabling/disabling 15 AuxE.ROV.En residual voltage auxiliary element 0 or 1 0: disable 1: enable 3.7 Distance Protection 3.7.1 General Application When a fault happens on a power system, distance protection will trip circuit breaker to isolate the fault from power system with its specific time delay if the fault is within the protected zone of distance protection. 3.7.2 Function Description The device provide various distance elements, including 1 DPFC distance zone with fixed forward direction, 1 forward zones, 4 settable forward or reverse zone, and 1 forward zone and 1 reverse zone dedicated for pilot distance protection. For each independent distance element zone, full 3-22 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory scheme design provides continuous measurement of impedance separately in each independent phase-to-phase measuring loops as well as in each independent phase-to-ground measuring loops. Selection of zone characteristic between mho and quadrilateral is available. Distance protection includes: 1. DPFC distance protection It is independent fast protection providing extremely fast speed to clear close up fault especially on long line and thus improves system stability. 2. Mho phase-to-phase distance protection Zone 1: forward direction Zone 2~5: settable forward or reverse direction 3. Mho phase-to-ground distance protection Zone 1: forward direction Zone 2~5: settable forward or reverse direction 4. Quadrilateral phase-to-phase distance protection Zone 1: forward direction Zone 2~5: settable forward or reverse direction 5. Quadrilateral phase-to-ground distance protection Zone 1: forward direction Zone 2~5: settable forward or reverse direction 6. Pilot distance protection The pilot zone is for PUTT, POTT and blocking scheme. The forward direction element is for sending signal for POTT and tripping upon receiving permissive signal for both PUTT and POTT scheme. The forward direction element for blocking scheme is used to stop sending blocking signal. The reverse direction element is only for POTT scheme with weak infeed condition. 7. Load encroachment It is used to prevent all distance elements from undesired trip due to load encroachment under heavy load condition especially for long lines. 8. Out-of-step protection (OOS) 9. Power swing blocking releasing (PSBR) For power swing with external fault, distance protection is always blocked, but for power swing with internal fault, PSBR will operate to release the blocking for distance protection. 10. SOTF distance protection 3-23 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory For manual closing or automatic closing on to a fault, zone 2, 3 or 4 of distance protection will accelerate to trip. When VT circuit fails, VT circuit supervision logic will output a blocking signal to block all distance protection except DPFC distance protection. The operating threshold will be increased to 1.5U N to enhance stability. Distance protection can select line VT or bus VT for protection algorithm by a setting [VTS.En_LineVT]. When no VT is provided, logic setting [VTS.En_Out_VT] should be set as “1”, all distance protection will be blocked automatically. The choice of impedance reach is as follow. (only for reference) The zone 1 impedance reach setting should be set to cover as much the protected line as possible but not to respond faults beyond the protected line. The accuracy of the relay distance elements is ±2.5% in general applications, however, the error could be much larger due to errors of current transformer, voltage transformer and inaccuracies of line parameter from which the relay settings are calculated. It is recommended the zone 1 reach is set to 80%~85% of the protected line in consideration the aforesaid errors and safety margin to prevent instantaneously tripping for faults on adjacent lines. The remaining 20% of the protected line relies on the zone 2 distance elements. With the pilot scheme distance protection, fast fault clearance could also be achieved for end zone faults at both ends of the protected line. The general rule for zone 2 impedance reach setting is set to cover the protected line plus 20% of the adjacent line. However, the coverage of adjacent line should be extended in the presence of additional infeed at the remote end of the protected line to ensure 20% coverage of adjacent line. This assures the fast operation of zone 2 distance element for faults at the remote end of the protected line since the fault is well within zone 2 reach. This is important for pilot protection as the impedance reach of pilot zone is the same as that of zone 2 distance element. In a parallel line situation, a fault cleared sequentially on a line may cause current reversal in the healthy line. If the pilot zone settings are set to cover 50% of adjacent line and the POTT or Blocking scheme is used, the current reversal in the healthy line could cause relay mal-operation. Therefore, current reversal logic is required and explained in section 3.9.2.6. For different system impedance ratio (SIR), the operating time of distance protection for different fault location are shown as the following figures. 3-24 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 35 30 25 Operating Time (ms) 20 15 10 5 0 0 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% Fault Location (% of relay setting) Figure 3.7-1 Operating time of single-phase fault (50Hz, SIR=1) 30 25 Operating Time (ms) 20 15 10 5 0 0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% Fault Location (% of relay setting) Figure 3.7-2 Operating time of single-phase fault (60Hz, SIR=1) 3-25 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 35 30 25 Operating Time (ms) 20 15 10 5 0 0 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% Fault Location (% of relay setting) Figure 3.7-3 Operating time of two-phase fault (50Hz, SIR=1) 30 25 Operating Time (ms) 20 15 10 5 0 0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% Fault Location (% of relay setting) Figure 3.7-4 Operating time of two-phase fault (60Hz, SIR=1) 3-26 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 35 30 25 Operating Time (ms) 20 15 10 5 0 0 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% Fault Location (% of relay setting) Figure 3.7-5 Operating time of three-phase fault (50Hz, SIR=1) 30 25 Operating Time (ms) 20 15 10 5 0 0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% Fault Location (% of relay setting) Figure 3.7-6 Operating time of three-phase fault (60Hz, SIR=1) 3-27 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 33 32.5 32 Operating Time (ms) 31.5 31 30.5 30 29.5 29 0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% Fault Location (% of relay setting) Figure 3.7-7 Operating time of single-phase fault (50Hz, SIR=30) 27.5 27 Operating Time (ms) 26.5 26 25.5 25 24.5 24 0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% Fault Location (% of relay setting) Figure 3.7-8 Operating time of single-phase fault (60Hz, SIR=30) 3-28 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 45 40 35 Operating Time (ms) 30 25 20 15 10 5 0 0 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% Fault Location (% of relay setting) Figure 3.7-9 Operating time of two-phase fault (50Hz, SIR=30) 35 30 Operating Time (ms) 25 20 15 10 5 0 0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% Fault Location (% of relay setting) Figure 3.7-10 Operating time of two-phase fault (60Hz, SIR=30) 3-29 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 33 32 Operating Time (ms) 31 30 29 28 27 0 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% Fault Location (% of relay setting) Figure 3.7-11 Operating time of three-phase fault (50Hz, SIR=30) 27.5 27 Operating Time (ms) 26.5 26 25.5 25 24.5 24 23.5 0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% Fault Location (% of relay setting) Figure 3.7-12 Operating time of three-phase fault (60Hz, SIR=30) 3.7.3 DPFC Distance Protection The power system is normally treated as a balanced symmetrical three-phase network. When a fault occurs in the power system, by applying the principle of superposition, the load current and voltage can be calculated in the system prior to the fault and the pure fault component can be calculated by fault current or voltage subtracted by pre-fault load current or voltage. DPFC distance protection concerns change of current and voltage at power frequency, therefore, DPFC distance protection is not influenced by load current. As an independent fast protection, DPFC distance protection is mainly used to clear close up fault of long line quickly, its protected range can set as 80%~85% of the whole line. 3-30 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Since DPFC distance protection only reflects fault component and is not influenced by current change due to load variation and power swing, power swing blocking (PSB) is this not required. Moreover, there is no transient overreaching due to infeed current from the remote power supply because it is not influenced by load current. DPFC distance protection may not overreach, and its protected zone will be inverse-proportion reduced with system impedance behind it, i.e. the protected zone will be less than setting if the system impedance is greater. The protected zone will be close to setting value if the system impedance is smaller. Therefore, DPFC distance protection is usually used for long transmission line with large power source and it is recommended to disable DPFC distance protection for short line or the line with weak power source. 3.7.3.1 Impedance Characteristic ZZD M EM F Z N EN ∆I ZS ZK jX Zzd Zk Φ Zs+Zk R -Zs Figure 3.7-13 Operation characteristic for forward fault Where: ZZD: the setting of DPFC distance protection ZS: total impedance between local system and device location ZK: measurement impedance 3-31 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Φ: positive-sequence sensitive angle, i.e. [21-1.phi1_Reach] Figure 3.7-13 shows the operation characteristic of DPFC distance protection on R-X plane when a fault occurs in forward direction, which is the circle with the –Zs as the center and the│Zs+Zzd│ as the radius. When measured impedance Z k is in the circle, DPFC distance protection will operate. DPFC distance protection has a larger capability of enduring fault resistance than distance protection using positive-sequence as polarized voltage. ZZD F M EM N Z EN ∆I ZK Z′S jX Z's Zzd Φ R -Zk Figure 3.7-14 Operation characteristic for reverse fault Z'S:total impedance between remote system and protective device location Figure 3.7-14 shows the operation characteristic of the DPFC distance element on R-X plane when a fault occurs in reverse direction, which is the circle with the Z′S as the center and the│Z′S-Zzd│as the radius. The region of operation is in the quadrant 1 but the measured impedance -Zk is always in the quadrant 3, the DPFC distance protection will not operate. The DPFC distance protection can be enabled or disabled by logic setting and binary input. 3-32 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.7.3.2 Function Block Diagram 21D 21D.En 21D.Op 21D.Blk 21D.On 3.7.3.3 I/O Signals Table 3.7-1 I/O signals of DPFC distance protection No. Input Signal 1 21D.En 2 21D.Blk No. Description DPFC distance protection enabling input, it is triggered from binary input or programmable logic etc. DPFC distance protection blocking input, it is triggered from binary input or programmable logic etc. Output Signal Description 1 21D.Op DPFC distance protection operates. 2 21D.On DPFC distance protection is enabled. 3.7.3.4 Logic EN [21D.En] SIG 21D.En SIG 21D.Blk SIG FD.Pkp EN [VTS.En_Out_VT] SIG Manual closing signal SIG 3-pole reclosing signal SET [21D.Z_Set]<0.05Ω/In SET ZΦ<[21D.Z_Set] SIG UP<0.85Un SET ZΦΦ<[21D.Z_Set] SIG UPP<0.85Unn SIG Pole open & 21D.On & >=1 & >=1 & & 21D.Op & Figure 3.7-15 Logic diagram of DPFC distance protection 3-33 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory NOTICE! Pole open signal blocks DPFC distance element of corresponding phase-to-earth and phase-to-phase DPFC distance protection, and healthy phases (operation phases) are not affected. For example, if phase A open is confirmed, DPFC distance element of phase A, phase AB and phase AC are blocked. 3.7.3.5 Settings Table 3.7-2 Settings of DPFC distance protection No. 1 Name 21D.Z_Set Range Step Unit (0.000~4Unn)/In 0.001 ohm Remark Impedance setting of DPFC distance protection Enabling/disabling 2 21D.En DPFC distance protection 0 or 1 0: disable 1: enable 3.7.4 Load Encroachment 3.7.4.1 Impedance Characteristic When distance protection is used to protect long, heavily loaded lines, the risk of encroachment of the load impedance into the tripping characteristic of the distance protection may exist. A load trapezoid characteristic for all zones is used to exclude the risk of unwanted fault detection by the distance protection during heavy load flow. As shown below, if the measured impedance into the load area, distance elements need to be blocked. jX φLoad φLoad Load Area Load Area R RLoad RLoad Figure 3.7-16 Distance element with load trapezoid Two settings are equipped to exclude the encroachment of the load impedance: 3-34 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory RLoad: the minimum load resistance φLoad: the load area angle These values are common for all zones. 3.7.4.2 Function Block Diagram LoadEnch LoadEnch.En LoadEnch.St LoadEnch.Blk LoadEnch.On 3.7.4.3 I/O Signals Table 3.7-3 I/O signals of load encroachment No. Input Signal 1 LoadEnch.En 2 LoadEnch.Blk No. Description Load trapezoid characteristic enabling input, it is triggered from binary input or programmable logic etc. Load trapezoid characteristic blocking input, it is triggered from binary input or programmable logic etc. Output Signal Description Measured impedance is inside the load area. If load trapezoid characteristic is enabled and measured impedance is inside the 1 LoadEnch.St load area, LoadEnch.St=1 If load trapezoid characteristic is disabled or measured impedance is outside the load area, LoadEnch.St=0 2 LoadEnch.On Load trapezoid characteristic is enabled. 3.7.4.4 Settings Table 3.7-4 Settings of load encroachment No. Name Range Step Unit Remark Angle setting characteristic, 1 LoadEnch.phi 0~45 1 deg of it load should trapezoid be set according to the maximum load area angle (φLoad_Max), φLoad_Max+5° is recommended. Impedance setting of load trapezoid 2 LoadEnch.Z_Set (0.05~200)/In 0.01 ohm characteristic, it according the to should be minimum set load resistance, 70%~90% minimum load resistance is recommended. 3-35 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Enabling/disabling 3 LoadEnch.En load trapezoid characteristic 0,1 0: disable 1: enable 3.7.5 Mho Distance Protection 3.7.5.1 Impedance Characteristic 1. Phase-to-ground distance element ZZD M EM F Z N IN EN I ZS ZK jX ZZD ZK Φ R -2ZS/3 Figure 3.7-17 Phase-to-ground operation characteristic for forward fault Where: ZZD: the setting of distance protection ZS: total impedance between local system and protective device location ZK: measurement impedance Φ: positive-sequence sensitive angle, i.e. [21-i.phi1_Reach] (i=1, 2, 3, 4, 5) Phase-to-neutral positive sequence voltage is used as polarized signal for phase-to-ground distance protection. Phase-to-ground distance protection is controlled by the fault detector based on residual current. 3-36 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Operation voltage: Polarized voltage: UPΦ uses phase positive-sequence voltage as polarized voltage. For earth fault, positive-sequence voltage is mainly formed from healthy phases, basically retaining the phase of the positive-sequence voltage before fault. Phase comparison equation is: The operation characteristic is shown in Figure 3.7-17. Operation characteristic of ZK on R-X plane is a circle with line connecting ends of ZZD and -2ZS/3 as the diameter. The origin is enclosed in the circle. In short line, phase shift θ1 could be applied to the polarized voltage to improve the performance against high resistance fault. The device provides an angle-shift setting, [21Mx.ZG.phi_Shift], to set value of θ1 among 0°, 15°and 30°. Their impedance shift characteristics towards quadrant 1 are respectively shown as the impedance circle A, B and C in Figure 3.7-23. The sensitivity of phase-to-ground distance element with Mho characteristic may be not enough during ground fault with extreme high resistance. So additional quadrilateral characteristic for phase-to-ground distance element is adopted in the equipment to compensate the sensitivity of Mho characteristic. The logic relationship between quadrilateral distance element and Mho distance element is OR. It means that any ground fault in one of the two operation zones will be cleared. The quadrilateral phase-to-ground distance element can significantly improve the sensitivity to clear ground fault with extreme high resistance. The five zones of quadrilateral characteristic can be enabled or disabled by the logic setting [21Mi.ZGQ.En]. (i=1, 2, 3, 4, 5) The operation characteristic of quadrilateral distance element is shown in Figure 3.7-18. When the characteristic of mho & quadrilateral is enabled by PCS-Explorer, the settings [21Mi.ZG.phi_Shift] will be hidden automatically. (i=1, 2, 3, 4, 5) 3-37 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory jX [21Mi.ZG.Z_Set] [21Mi.ZGQ.RCA] Φ Φ R 15° [21Mi.ZGQ.R_Set] Figure 3.7-18 Operation Characteristic of quadrilateral distance element Where: i=1, 2, 3, 4, 5 Φ is the phase angle of positive sequence line impedance The quadrilateral characteristic is a supplement to Mho characteristic for phase-to-ground distance protection. It is used to improve sensitivity for ground fault with high resistance. 2. Phase-to-phase distance element jX ZZD ZK Φ R -ZS/2 Figure 3.7-19 Phase-to-phase operation characteristic for forward fault Phase-to-phase positive sequence voltage is used as polarized signal for phase-to-phase distance protection. Operation voltage: 3-38 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Polarized voltage: Phase comparison equation is: The operation characteristic of phase-to-phase distance element is shown in Figure 3.7-19. Operation characteristic of ZK on R-X plane is a circle with line connecting ends of Z ZD and -ZS/2 as the diameter. The origin is enclosed in the circle. Phase shift θ2 could be applied to polarized voltage just like θ1 in phase-to-ground distance element. It is also used for improving performance against high resistance fault in short line. The device provides an angle-shift setting, [21Mx.ZP.phi_Shift], to set value of θ2 among 0°, 15°and 30°. Their impedance shift characteristics towards quadrant 1 are respectively shown as the impedance circle A, B and C in Figure 3.7-23. Figure 3.7-20 shows operation characteristic of measured impedance -ZK on R-X plane when an asymmetric reverse fault occurs. This characteristic is a circle with line connecting ends of Z ZD and Z'S as the diameter. It will operate only when -ZK is in the circle. Therefore, directionality of the distanced protection is achieved. ZZD F EM M N Z EN IΦ ZK Z′S jX Z'S ZZD Φ R -ZK Figure 3.7-20 Operation characteristic for reverse fault Z'S: total impedance between remote system and protective device location 3-39 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory jX ZZD ZK Φ R Figure 3.7-21 Steady-state characteristic of three-phase short-circuit fault Phase-to-phase distance protection is also used for three-phase short-circuit fault. The operation characteristic is shown in Figure 3.7-21. Operation characteristic of ZK on R-X plane is a circle with setting impedance ZZD as the diameter. jX ZZD ZK Φ R Circle C -ZS Circle B Circle A Figure 3.7-22 Operation characteristic of three-phase close up short-circuit fault Where: ZZD: the setting of distance protection (zone i) ZS: total impedance between local system and protective device location ZK: measured impedance Φ: positive-sequence characteristic angle, i.e. [21-i.phi1_Reach] (i=1, 2, 3, 4, 5) Circle A: transient characteristic Circle B: steady-state characteristic shifting towards quadrant Ⅲ 3-40 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Circle C: steady-state characteristic shifting towards quadrant Ⅰ As shown in Figure 3.7-22, the characteristic of the distance protection for a three-phase fault on a system is an impedance circle cross the origin, and there is a voltage dead zone around the origin. In order to eliminate the dead zone of the distance protection for a close up three-phase fault memorized positive-sequence voltage is adopted as polarized voltage when the positive-sequence voltage drops down to 15%Un or below. The memorized positive-sequence voltages adopts 2 cycles pre-fault positvie-sequence voltage. The transient (during process of memory) operation characteristic is shown as the impedance circle A in the above figure. The circle takes Z ZD and -ZZS as diameter and thus the origin is within the impedance circle. When three-phase fault happens in reverse direction, its transient characteristic is shown in Figure 3.7-20, i.e. the distance protection has a clearly defined directionality and no dead zone during the process of memory. For phase-to-phase distance protection, if distance protection operates with memorized polarizing voltage, this means a close up forward fault. When the memory fades out, the operation characteristic will be reverse offset a little to enclose the origin as impedance circle B shown in Figure 3.7-22 to ensure keeping operating of distance protection until the fault being cleared. If distance protection does not operate with memorized polarizing voltage, it will be a close up reverse fault. When the memory fades out, the operation characteristic will be forward offset not to enclose the origin as impedance circle C shown in Figure 3.7-22, and the distance protection will not mal-operate even if voltage is zero. The distance protection with such design thoroughly eliminates the dead zone when three-phase close up fault occurs. It also has favorable directivity and will not operate for a reverse three-phase fault at busbar. When receiving manual closing signal or 3-pole reclosing signal, the operation characteristic of phase to phase distance protection will always shift in reverse direction. It is ensured to enclose the origin of impedance and without dead zone for three-phase fault, i.e. the reverse shift impedance circle B shown in Figure 3.7-22. jX B: 15° C: 30° ZZD A: 0° D R -ZS Figure 3.7-23 Shift impedance characteristic of zone 1 and zone 2 3-41 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory The impedance characteristic of phase-to-ground distance protection is the circle with line connecting ends of ZZD and -2ZS/3 as the diameter and that of phase-to-phase distance is the circle with line connecting ends of ZZD and -ZS/2 as the diameter. In order to prevent the transient overreach caused by the infeed power supply from the remote end, the zero-sequence reactance line D is added. These measures have enhanced the capacity against fault resistance when using distance protection in short lines. NOTICE! Phase current direction element is used as auxiliary direction element of distance protection. Hence, the setting [RCA_OC] should be set correctly according to actual system parameters if distance protection is enabled even if phase overcurrent protection is disabled. Zero-sequence current direction element is used as auxiliary direction element of phase-to-ground distance element (mho characteristic). In order to prevent phase-to-ground distance element from undesired operation due to revese direction fault, the setting [RCA_ROC] should be set correctly according to actual system parameters if phase-to-ground distance element is enabled even if earth fault protection is disabled. 3.7.5.2 Function Block Diagram 21M 21.En 21Mi.On 21.Blk 21Mi.Op 21Mi.ZG.En 21Mi.ZP.En 21Mi.ZG.Blk 21Mi.ZP.Blk 21Mi.En_ShortDly 21Mi.Blk_ShortDly 21M1.En_Instant 3.7.5.3 I/O Signals Table 3.7-5 I/O signals of distance protection (Mho) No. Input Signal 1 21.En 2 21.Blk Description Distance protection enabling input, it is triggered from binary input or programmable logic etc. Distance protection blocking input, it is triggered from binary input or 3-42 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory programmable logic etc. Zone i of phase-to-ground distance protection enabling input, default value is 3 21Mi.ZG.En 4 21Mi.ZG.Blk 5 21Mi.ZP.En 6 21Mi.ZP.Blk 7 21Mi.En_ShortDly Enable accelerating zone i of distance protection (i=2, 3, 4, 5) 8 21Mi.Blk_ShortDly Accelerating zone i of distance protection is disabled (i=2, 3, 4, 5) 9 21M1.En_Instant Enable zone 1 of distance protection operates without time delay No. “1” (i=1, 2, 3, 4, 5) Zone i of phase-to-ground distance protection blocking input, default value is “0” (i=1, 2, 3, 4, 5) Zone i of phase-to-phase distance protection enabling input, default value is “1” (i=1, 2, 3, 4, 5) Zone i of phase-to-phase distance protection blocking input, default value is “0” (i=1, 2, 3, 4, 5) Output Signal Description 1 21Mi.On Zone i of distance protection is enabled (i=1, 2, 3, 4, 5) 2 21Mi.Op Zone i of distance protection operates (i=1, 2, 3, 4, 5) 3.7.5.4 Logic SIG 21.En & 21.Enable SIG 21.Blk Figure 3.7-24 Logic diagram of enabling distance protection (Mho) 3-43 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory SIG 21.Enable EN & & [21M1.ZG.En] 21M1.ZG.Enable & SIG 21M1.ZG.En SIG 21M1.ZG.Blk EN >=1 21M1.On & [21M1.ZP.En] & SIG 21M1.ZP.En SIG 21M1.ZP.Blk & SIG VTS.Alm EN 21M1.ZP.Enable >=1 [VTS.En_Out_VT] SIG 21M1.Rls_PSBR SIG FD.Pkp & & [21M1.ZG.t_Op] SIG 21M1.ZG.Enable SIG Flag.21M1.ZG & SIG LoadEnch.St (PG) 21M1.ZG.Op & >=1 21M1.Flg_PSBR & SIG LoadEnch.St (PP) SIG FD.Pkp >=1 & SET 3I0>[FD.ROC.3I0_Set] SIG Flag.21M1.ZP 0 & [21M1.ZP.t_Op] & 0 >=1 21M1.ZP.Op & SIG 21M1.ZP.Enable SIG 21M1.En_Instant SIG 21M1.ZG.Op >=1 21M1.Op SIG 21M1.ZP.Op Figure 3.7-25 Logic diagram of distance protection (Mho zone 1) Where: 21M1.Rls_PSBR: is the signal of power swing blocking releasing signal, please refer to Figure 3.7-43. Flag.21M1.ZG means that measured impedance by zone 1 of phase-to-ground distance protection is within the range determined by the setting [21M1.ZG.Z_Set]. Flag.21M1.ZP means that measured impedance by zone 1 of phase-to-phase distance protection is within the range determined by the setting [21M1.ZP.Z_Set]. LoadEnch.St (PG) means that load trapezoid characteristic for distance element is enabled and 3-44 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory measured phase-to-ground impedance into the load area. LoadEnch.St (PP) means that load trapezoid characteristic for distance element is enabled and measured phase-to-phase impedance into the load area. SIG 21.Enable EN [21Mi.ZG.En] SIG 21Mi.ZG.En SIG 21Mi.ZG.Blk EN [21Mi.ZP.En] SIG 21Mi.ZP.En SIG 21Mi.ZP.Blk SIG VTS.Alm EN [VTS.En_Out_VT] SIG 21Mi.En_ShortDly SIG 21Mi.Blk_ShortDly EN [21Mi.En_ShortDly] SIG 21Mi.On SIG 21Mi.Enable_ShortDly SIG 21Mi.Rls_PSBR SIG 21Mi.ZG.Enable SIG FD.Pkp SIG Flag.21Mi.ZG SIG LoadEnch.St (PG) SET 3I0>[FD.ROC.3I0_Set] SIG Flag.21Mi.ZP SIG LoadEnch.St (PP) SIG 21Mi.ZP.Enable & & 21Mi.ZG.Enable & >=1 21Mi.On & & & 21Mi.ZP.Enable >=1 & & 21Mi.Enable_ShortDly & [21Mi.ZG.t_ShortDly] 0 >=1 21Mi.ZG.Op & & [21Mi.ZG.t_Op] 0 & >=1 & 21Mi.Flg_PSBR & & [21Mi.ZP.t_Op] & 0 >=1 21Mi.ZP.Op & SIG FD.Pkp SIG 21Mi.Enable_ShortDly SIG 21Mi.ZG.Op SIG 21Mi.ZP.Op [21Mi.ZP.t_ShortDly] 0 >=1 21Mi.Op Figure 3.7-26 Logic diagram of distance protection (Mho zone i) 3-45 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Where: i=2, 3, 4, 5 21Mi.Rls_PSBR: is the signal of power swing blocking releasing signal, please refer to Figure 3.7-43. Flag.21Mi.ZG means that measured impedance by zone x of phase-to-ground distance protection is within the range determined by the setting [21Mi.ZG.Z_Set]. Flag.21Mi.ZP means that measured impedance by zone x of phase-to-phase distance protection is within the range determined by the setting [21Mi.ZP.Z_Set]. 3.7.5.5 Settings Table 3.7-6 Settings of distance protection (Mho) No. Name Range Step Unit Remark Direction option for zone i of distance 1 21-i.DirMode 0 or 1 protection (i=2, 3, 4, 5) 0 0: Forward 1: Reverse Real component of zero-sequence 2 21-i.Real_K0 -4.000~4.000 0.001 compensation coefficient for zone i (i=1, 2, 3, 4, 5) Imaginary 3 21-i.Imag_K0 -4.000~4.000 0.001 component zero-sequence of compensation coefficient for zone i (i=1, 2, 3, 4, 5) 4 21-i.phi1_Reach 30~89 1 deg Phase angle of impedance for zone i (i=1, 2, 3, 4, 5) Downward 5 21Mi.ZGQ.RCA 0~45 1 deg positive-sequence reactance offset line angle for of zone the i of phase-to-ground distance protection (i=1, 2, 3, 4, 5) Phase 6 21Mi.ZG.phi_Shift 0, 15 or 30 deg shift of phase-to-ground distance protection for zone i (i=1, 2, 3, 4, 5) 7 21Mi.ZP.phi_Shift 0, 15 or 30 deg Phase shift of phase-to-phase distance protection for zone i (i=1, 2, 3, 4, 5) Impedance 8 21Mi.ZG.Z_Set (0.000~4Unn)/In 0.001 ohm setting of zone i of phase-to-ground distance protection (i=1, 2, 3, 4, 5) Resistance 9 21Mi.ZGQ.R_Set (0.000~4Unn)/In 0.001 ohm setting of zone i of phase-to-ground distance protection (i=1, 2, 3, 4, 5) 10 21Mi.ZG.t_Op 0.000~10.000 0.001 s 3-46 Time delay of zone i of phase-to-ground distance protection PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory No. Name Range Step Unit Remark (i=1, 2, 3, 4, 5) Short 11 21Mi.ZG.t_ShortDly 0.000~10.000 0.001 s time delay of zone i of phase-to-ground distance protection (i=2, 3, 4, 5) Enabling/disabling zone i of phase-to-ground distance protection 12 21Mi.ZG.En 0 or 1 (i=1, 2, 3, 4, 5) 0: disable 1: enable Enabling/disabling zone i of quadrilateral phase-to-ground distance 13 21Mi.ZGQ.En 0 or 1 protection (i=1, 2, 3, 4, 5) 0: disable 1: enable Enabling/disabling phase-to-ground zone i of distance protection operation 14 21Mi.ZG.En_BlkAR 0 or 1 to block AR (i=1, 2, 3, 4, 5) 0: disable 1: enable Impedance 15 21Mi.ZP.Z_Set (0.000~4Unn)/In 0.001 ohm setting phase-to-phase of zone distance i of protection (i=1, 2, 3, 4, 5) 16 21Mi.ZP.t_Op 0.000~10.000 0.001 s Time delay of zone i of phase-to-phase distance protection (i=1, 2, 3, 4, 5) Short 17 21Mi.ZP.t_ShortDly 0.000~10.000 0.001 s time delay phase-to-phase of zone distance i of protection (i=2, 3, 4, 5) Enabling/disabling phase-to-phase 18 21Mi.ZP.En 0 or 1 zone distance i of protection (i=1, 2, 3, 4, 5) 0: disable 1: enable Enabling/disabling phase-to-phase zone i of distance protection operation 19 21Mi.ZP.En_BlkAR 0 or 1 to block AR (i=1, 2, 3, 4, 5) 0: disable 1: enable Enabling/disabling fixed accelerate zone i of distance protection (i=2, 3, 4, 20 21Mi.En_ShortDly 0 or 1 5) 0: disable 1: enable 3-47 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.7.6 Quadrilateral Distance Protection 3.7.6.1 Impedance Characteristic Features available with quadrilateral distance protection include 1 forward zone (zone 1) phase-to-ground or phase-to-phase distance elements and 4 settable forward or reverse zones (zone 2~5) phase-to-ground or phase-to-phase distance element. Each zone can respectively enable or disable power swing blocking releasing. Quadrilateral distance protection will be disabled when VT circuit fails. 1. Forward distance element Quadrilateral forward distance element characteristic is shown as follows: jX A ZZD θ B α φ φ O β RZD C R Figure 3.7-27 Quadrilateral forward distance element characteristics Where: ZZD: impedance setting in forward direction RZD: resistance setting in forward direction φ: line positive-sequence characteristic angle α: the angle of directional line in the second quadrant, set by the setting [21Q.Ang_Alpha] β: the angle of directional line in the fourth quadrant, fixed at 15 ° θ: downward offset angle of the reactance line AB 2. Reverse distance element Zone 2, 3, 4, 5 can be set as reverse direction by the setting [21-i.DirMode] (i=2, 3, 4, 5). When a fault occurs on the busbar at the back, reverse distance element is provided to clear it with definite time delay and is used as backup protection for reverse busbar fault. 3-48 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory jX C RZD O β φ R φ α B θ ZZD A Figure 3.7-28 Quadrilateral reverse distance element characteristic Where: ZZD: impedance setting in reverse direction RZD: resistance setting in reverse direction φ: line positive-sequence characteristic angle α: the angle of directional line, set by the setting [21Q.Ang_Alpha] β: the angle of directional line, fixed at 15° θ: downward offset angle of the reactance line AB For quadrilateral distance protection, the reactance line should consider downward offset angle θ as shown in Figure 3.7-27 and Figure 3.7-28. According to system status, the downward offset angle can be independently set for phase-to-ground distance element and phase-to-phase distance element. The downward offset angle of all zones can be settable by the corresponding settings [21Qi.ZG.RCA] and [21Qi.ZP.RCA]. (i=1, 2, 3, 4, 5). Phase-to-ground distance protection is controlled by the fault detector based on residual current. NOTICE! Phase current direction element is used as auxiliary direction element of distance protection. Hence, the setting [RCA_OC] should be set correctly according to actual system parameters if distance protection is enabled even if phase overcurrent protection is disabled. Zero-sequence current direction element is used as auxiliary direction element of zone 1 of phase-to-ground distance element (quad characteristic). In order to prevent zone 1 of phase-to-ground distance element from undesired operation due to revese direction fault, the setting [RCA_ROC] should be set correctly according to actual system parameters if zone 1 of phase-to-ground distance element is enabled even if earth fault protection is disabled. Negative-sequence current direction element is used as the direction element of phase-to-ground and phase-to-phase distance element (quad characteristic) for 3-49 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory asymmetric fault. In order to prevent phase-to-ground and phase-to-phase distance element from undesired operation due to revese direction fault, the setting [RCA_NegOC] should be set correctly according to actual system parameters. 3.7.6.2 Function Block Diagram 21Q 21.En 21Qi.On 21.Blk 21Qi.Op 21Qi.ZG.En 21Qi.ZP.En 21Qi.ZG.Blk 21Qi.ZP.Blk 21Qi.En_ShortDly 21Qi.Blk_ShortDly 21Q1.En_Instant 3.7.6.3 I/O Signals Table 3.7-7 I/O signals of distance protection (Quad) No. Input Signal Description Distance protection enabling input, it is triggered from binary input or 1 21.En 2 21.Blk 3 21Qi.ZG.En 4 21Qi.ZG.Blk 5 21Qi.ZP.En 6 21Qi.ZP.Blk 7 21Qi.En_ShortDly Enable accelerating zone i of distance protection (i=2, 3, 4, 5) 8 21Qi.Blk_ShortDly Accelerating zone i of distance protection is disabled (i=2, 3, 4, 5) 9 21Q1.En_Instant Enable zone 1 of distance protection operates without time delay No. programmable logic etc. Distance protection blocking input, it is triggered from binary input or programmable logic etc. Zone i of phase-to-ground distance protection enabling input, default value is “1” (i=1, 2, 3, 4, 5) Zone i of phase-to-ground distance protection blocking input, default value is “0” (i=1, 2, 3, 4, 5) Zone i of phase-to-phase distance protection enabling input, default value is “1” (i=1, 2, 3, 4, 5) Zone i of phase-to-phase distance protection blocking input, default value is “0” Output Signal (i=1, 2, 3, 4, 5) Description 1 21Qi.On Zone i of distance protection is enabled (i=1, 2, 3, 4, 5) 2 21Qi.Op Zone i of distance protection operates (i=1, 2, 3, 4, 5) 3-50 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.7.6.4 Logic SIG 21.En & 21.Enable SIG 21.Blk Figure 3.7-29 Logic diagram of enabling distance protection (Quad) SIG 21.Enable EN [21Q1.ZG.En] SIG 21Q1.ZG.En SIG 21Q1.ZG.Blk & & 21Q1.ZG.Enable & >=1 21Q1.On & EN [21Q1.ZP.En] SIG 21Q1.ZP.En SIG 21Q1.ZP.Blk SIG VTS.Alm EN [VTS.En_Out_VT] SIG 21Q1.ZG.Enable SIG FD.Pkp SIG LoadEnch.St (PG) SET 3I0>[FD.ROC.3I0_Set] SIG Flag.21Q1.ZG SIG 21Q1.Rls_PSBR SIG FD.Pkp SIG 21Q1.ZP.Enable SIG LoadEnch.St (PP) SIG Flag.21Q1.ZP SIG 21Q1.En_Instant SIG 21Q1.ZG.Op SIG 21Q1.ZP.Op & & 21Q1.ZP.Enable >=1 & & & [21Q1.ZG.t_Op] & 0 >=1 21Q1.ZG.Op & >=1 21Q1.Flg_PSBR & & & & [21Q1.ZP.t_Op] 0 >=1 & 21Q1.ZP.Op >=1 21Q1.Op Figure 3.7-30 Logic diagram of distance protection (Quad zone 1) Where: 21Q1. Rls_PSBR: is the signal of power swing blocking releasing signal, please refer to Figure 3.7-43. 3-51 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Flag.21Q1.ZG means that measured impedance by zone 1 of phase-to-ground distance protection is within the range determined by the settings [21Q1.ZG.Z_Set] and [21Q1.ZG.R_Set]. Flag.21Q1.ZP means that measured impedance by zone 1 of phase-to-phase distance protection is within the range determined by the settings [21Q1.ZP.Z_Set] and [21Q1.ZP.R_Set]. LoadEnch.St (PG) means that load trapezoid characteristic for distance element is enabled and measured phase-to-ground impedance into the load area. LoadEnch.St (PP) means that load trapezoid characteristic for distance element is enabled and measured phase-to-phase impedance into the load area. SIG 21.Enable EN [21Qi.ZG.En] SIG 21Qi.ZG.En SIG 21Qi.ZG.Blk EN [21Qi.ZP.En] SIG 21Qi.ZP.En SIG 21Qi.ZP.Blk SIG VTS.Alm EN [VTS.En_Out_VT] SIG 21Qi.En_ShortDly SIG 21Qi.Blk_ShortDly EN [21Qi.En_ShortDly] SIG 21Qi.On & & 21Qi.ZG.Enable & >=1 21Qi.On & & & 21Qi.ZP.Enable >=1 & & 21Qi.Enable_ShortDly 3-52 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory SIG 21Qi.Enable_ShortDly SIG 21Qi.ZG.Enable & & SIG FD.Pkp [21Qi.ZG.t_ShortDly] 0 & >=1 21Qi.ZG.Op & SET 3I0>[FD.ROC.3I0_Set] & [21Qi.ZG.t_Op] 0 SIG LoadEnch.St (PG) SIG Flag.21Qi.ZG >=1 SIG 21Qi.Rls_PSBR 21Qi.Flg_PSBR SIG LoadEnch.St (PP) & & SIG Flag.21Qi.ZP & [21Qi.ZP.t_ShortDly] 0 & SIG 21Qi.ZP.Enable >=1 21Qi.ZP.Op & [21Qi.ZP.t_Op] 0 SIG FD.Pkp SIG 21Qi.ZG.Op >=1 21Qi.Op SIG 21Qi.ZP.Op Figure 3.7-31 Logic diagram of distance protection (Quad zone i) Where: i=2, 3, 4, 5 21Qi.Z.Rls_PSBR: is the signal of power swing blocking releasing signal, please refer to Figure 3.7-43. Flag.21Qi.ZG means that measured impedance by zone x of phase-to-ground distance protection is within the range determined by the settings [21Qi.ZG.Z_Set] and [21Qi.ZG.R_Set]. Flag.21Qi.ZP means that measured impedance by zone x of phase-to-phase distance protection is within the range determined by the settings [21Qi.ZP.Z_Set] and [21Qi.ZP.R_Set]. 3.7.6.5 Settings Table 3.7-8 Settings of distance protection (Quad) No. 1 Name 21Q.Ang_Alpha Range 5~30 Step Unit 1 deg Remark The angle of directional line Direction option for zone i of distance 2 21-i.DirMode 0 or 1 0 protection (i=2, 3, 4, 5) 0: Forward 1: Reverse Real component of zero-sequence 3 21-i.Real_K0 -4.000~4.000 0.001 compensation coefficient for zone i (i=1, 2, 3, 4, 5) 3-53 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory No. Name Range Step Unit Remark Imaginary 4 21-i.Imag_K0 -4.000~4.000 0.001 component zero-sequence of compensation coefficient for zone i (i=1, 2, 3, 4, 5) 5 21-i.phi1_Reach 30~89 1 deg Phase angle of positive-sequence impedance for zone i (i=1, 2, 3, 4, 5) Downward 6 21Qi.ZG.RCA 0~45 1 deg reactance offset line angle for of zone the i of phase-to-ground distance protection (i=1, 2, 3, 4, 5) Impedance 7 21Qi.ZG.Z_Set (0.000~4Unn)/In 0.001 ohm setting of zone i of phase-to-ground distance protection (i=1, 2, 3, 4, 5) Resistance 8 21Qi.ZG.R_Set (0.000~4Unn)/In 0.001 ohm setting of zone i of phase-to-ground distance protection (i=1, 2, 3, 4, 5) Time 9 21Qi.ZG.t_Op 0.000~10.000 0.001 s delay of zone i of phase-to-ground distance protection (i=1, 2, 3, 4, 5) Short 10 21Qi.ZG.t_ShortDly 0.000~10.000 0.001 s time delay of zone i of phase-to-ground distance protection (i=2, 3, 4, 5) Enabling/disabling zone i of phase-to-ground distance protection 11 21Qi.ZG.En 0 or 1 (i=1, 2, 3, 4, 5) 0: disable 1: enable Enabling/disabling phase-to-ground zone i of distance protection operation 12 21Qi.ZG.En_BlkAR 0 or 1 to block AR (i=1, 2, 3, 4, 5) 0: disable 1: enable Downward 13 21Qi.ZP.RCA 0~45 1 deg reactance offset line phase-to-phase angle for of zone distance the i of protection (i=1, 2, 3, 4, 5) Impedance 14 21Qi.ZP.Z_Set (0.000~4Unn)/In 0.001 ohm setting phase-to-phase of distance zone i of protection (i=1, 2, 3, 4, 5) Resistance 15 21Qi.ZP.R_Set (0.000~4Unn)/In 0.001 ohm setting phase-to-phase of distance zone i of protection (i=1, 2, 3, 4, 5) 16 21Qi.ZP.t_Op 0.000~10.000 0.001 s 3-54 Time delay of zone i of phase-to-phase distance protection (i=1, 2, 3, 4, 5) PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory No. Name Range Step Unit Remark Short 17 21Qi.ZP.t_ShortDly 0.000~10.000 0.001 s time delay of zone i of phase-to-ground distance protection (i=2, 3, 4, 5) Enabling/disabling phase-to-phase 18 21Qi.ZP.En 0 or 1 zone distance i of protection (i=1, 2, 3, 4, 5) 0: disable 1: enable Enabling/disabling phase-to-phase zone i of distance protection operation 19 21Qi.ZP.En_BlkAR 0 or 1 to block AR (i=1, 2, 3, 4, 5) 0: disable 1: enable Enabling/disabling fixed accelerate zone i of distance protection (i=2, 3, 4, 20 21Qi.En_ShortDly 0 or 1 5) 0: disable 1: enable 3.7.7 Pilot Distance Zone 3.7.7.1 Impedance Characteristic An independent pilot zone distance protection is used for PUTT and POTT scheme. There is also a reverse pilot distance element available as an option for application of POTT on weak power source system. Pilot.Z_Rev_B Pilot.Z_Set_B M EM Pilot.Z_Rev_A A B N C D Pilot.Z_Set_A Figure 3.7-32 Protected zone of pilot distance protection The operation characteristic of pilot zone is same as that of zone 2, including mho and quadrilateral characteristic. When an internal fault occurs, distance protection at weak source end may not operate due to small fault current. Thus, a reverse distance element is provided to coordinate with the independent pilot distance protection to implement weak infeed logic, ensure pilot distance protection can operate to send signal or trip in the weak end. The operation characteristic is shown in Figure 3.7-33. The reverse weak infeed distance element is forward offset with 1/4 of the 3-55 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory reverse setting to enclose the origin. Operation characteristics of pilot reverse weak infeed element distance are shown as below. jX jX B β 21Q.Pilot.Z_Rev/4 21M.Pilot.Z_Rev/4 21Q.Pilot.R_Rev o Φ φ R φ R α C θ 21Q.Pilot.Z_Rev 21M.Pilot.Z_Rev A Figure 3.7-33 Pilot reverse weak infeed element Where: Φ: positive-sequence characteristic angle, i.e. [21.Pilot.phi1_Reach] α: the angle of directional line, set by the setting [21Q.Ang_Alpha] β: the angle of directional line, fixed at 15° θ: tilted angle of the reactance line AC, fixed at 12° 3.7.7.2 Logic SIG FD.Pkp SIG 21.Enable SIG 21M.Pilot.Rls_PSBR SET Flag.21M.Pilot.Z (PG) SIG LoadEnch.St (PG) SET Flag.21M.Pilot.Z (PP) SIG LoadEnch.St (PP) & & & ZPilotP & >=1 21M.Zpilot.Flag_PSBR & Figure 3.7-34 Logic diagram of pilot distance zone (Mho characteristic) 3-56 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory SIG FD.Pkp SIG 21.Enable SIG 21Q.Pilot.Rls_PSBR SET Flag.21Q.Pilot.Z (PG) SIG LoadEnch.St (PG) SET Flag.21Q.Pilot.Z (PP) SIG LoadEnch.St (PP) & & & ZPilotP & >=1 21Q.Zpilot.Flag_PSBR & Figure 3.7-35 Logic diagram of pilot distance zone (Quad characteristic) Where: 21M.Pilot.Rls_PSBR, 21Q.Pilot.Rls_PSBR: Please refer to Figure 3.7-43. LoadEnch.St (PG) means that load trapezoid characteristic for distance element is enabled and measured phase-to-ground impedance into the load area. LoadEnch.St (PP) means that load trapezoid characteristic for distance element is enabled and measured phase-to-phase impedance into the load area. Flag.21Q.Pilot.Z (PG) means that measured impedance by phase-to-ground distance element is within the range determined by the setting [21Q.Pilot.Z_Set]. (Quad characteristic) Flag.21Q.Pilot.Z (PP) means that measured impedance by phase-to-phase distance element is within the range determined by the setting [21Q.Pilot.Z_Set]. (Quad characteristic) Flag.21M.Pilot.Z (PG) means that measured impedance by phase-to-ground distance element is within the range determined by the setting [21M.Pilot.Z_Set]. (Mho characteristic) Flag.21M.Pilot.Z (PP) means that measured impedance by phase-to-phase distance element is within the range determined by the setting [21M.Pilot.Z_Set]. (Mho characteristic) 3.7.7.3 Settings Table 3.7-9 Settings of pilot distance zone No. Name Range Step Unit Remark Real component of zero-sequence 1 21.Pilot.Real_K0 30.00~89.00 0.01 deg compensation coefficient for pilot distance protection Imaginary 2 21.Pilot.Imag_K0 -4.000~4.000 0.001 component zero-sequence of compensation coefficient for pilot distance protection Phase angle of positive-sequence 3 21.Pilot.phi1_Reach -4.000~4.000 0.001 impedance for pilot distance protection 3-57 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory No. Name Range Step Unit 4 21M.Pilot.Z_Set (0.000~4Unn)/In 0.001 ohm 5 21M.Pilot.R_Set_Quad (0.000~4Unn)/In 0.001 ohm 6 21Q.Pilot.Z_Set (0.000~4Unn)/In 0.001 ohm Remark Impedance setting of pilot distance protection (Mho characteristic) Resistance setting of pilot distance protection (Mho characteristic) Impedance setting of pilot distance protection (Quad characteristic) Impedance setting of pilot distance 7 21M.Pilot.Z_Rev (0.000~4Unn)/In 0.001 ohm protection in reverse direction (Mho characteristic) Enabling/disabling characteristic 8 21M.Pilot.En_Z_Quad 0 or 1 of quadrilateral phase-to-ground distance protection 0: disable 1: enable Impedance setting of pilot distance 9 21Q.Pilot.Z_Rev (0.000~4Unn)/In 0.001 ohm protection in reverse direction (Quad characteristic) 10 21Q.Pilot.R_Set (0.000~4Unn)/In 0.001 ohm Resistance setting of pilot distance protection (Quad characteristic) Resistance setting of pilot distance 11 21Q.Pilot.R_Rev (0.000~4Unn)/In 0.001 ohm protection in reverse direction (Quad characteristic) 3.7.8 Out-of-step Protection 3.7.8.1 General Application When the disturbance happens to the power system because of some reason (such as short circuit, fault clear, power supply injecting or separating, etc.), the phase angle difference of the electric potential between the synchronous generators of parallel operation will change with time, and the voltage of each node and the current of each circuit in the system also change with time, this phenomenon is called oscillation. The oscillation that can keep system stably and synchronously operate is called synchronous oscillation, and that leads to lose synchronization and that the system can't normally operate is called asynchronous oscillation. For the power grid of loss synchronous, the voltage of each node in the tie line that synchronous or asynchronous oscillation happens to will oscillate periodically, and where the voltage oscillation is the most violent in each tie line is the center of synchronous or asynchronous oscillation. In general, the voltage oscillation is more violent more close to the oscillation center. Out-of-step center is the point where the lowest voltage appears in the tie line of asynchronous oscillation in the process of out-of-step oscillation, i.e., the oscillation center of the tie line of asynchronous oscillation. The phase angle of bus voltage difference on either side of out-of-step center will change within 0°~180°~360° periodically. Considering the selectivity, the separation should be performed within 2~3 out-of-step period or the corresponding time delay after the system is out of step, otherwise the out-of-step oscillation among multiple generators may is developed, further 3-58 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory expanding the accident, so as to cause system separation even collapse accident. So when the out-of-step operation time or oscillation times is greater than specified value, out-of-step protection should operate to separate. 3.7.8.2 Function Description In the event that the interconnected system is out-of-step, the system can be reduced as a dual-machine system as shown in Figure 3.7-36. EM U EN I ZLine Figure 3.7-36 Dual-machine equivalent system For the sake of easy analysis, assumptions have to be made as follows: 1. The potential of the two machines are E M and EN respectively, and their amplitude are both equal to E1. 2. The equivalent impedance angle of system is 90° Taking EN as reference vector, whose initial phase angle is 0°and angle velocity is ω. At the side M, the initial phase angle of equivalent potential E M is α (i.e., during normal operation condition, the system′s power angle δ is α), whose increment of the angle velocity is Δω relative to side N, so EN E1 cos( t ) EM E1 cos(( ) t ) Suppose the power angle between both sides of the system is t The equivalent system vector diagram of Figure 3.7-36 is illustrated in Figure 3.7-37. I U EM U cos EN U SCV E1 E1 2 Figure 3.7-37 Dual-machine equivalent system 3-59 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Where: USCV is the voltage of oscillation center U is the measured voltage by the device As shown in Figure 3.7-37, the voltage of oscillation center USCV is: U SCV U cos E1 cos( ) 2 In the case that the system is in synchronous condition, Δω=0, the voltage of oscillation center maintains be unchanged, that is: U SCV cos( ) 2 Make calculus for the voltage of oscillation center, d (U SCV ) E d ( ) 1 sin( ) dt 2 2 dt The above equation describe the relationship between the voltage change rate of oscillation center and system slip frequency d ( ) , which indicates the voltage variation of oscillation center dt is independent of system impedance. When the power angle is 180°, the voltage variation of oscillation center is maximum, and when the power angle is 0°, the voltage variation of oscillation center is minimum. In the case that the system is in out-of-step condition, the voltage of oscillation center varies periodically with the oscillation cycle as 180°, that is: If the value of Δω is larger than 0, namely accelerating out-of-step condition, the variation trend of δ is 0°-360°(0°)-360°, the variation curve of oscillation center voltage is shown in Figure 3.7-38 (a) If the value of Δω is less than 0, namely decelerating out-of-step condition, the variation trend of δ is 360°-0°(360°)-0°, the variation curve of oscillation center voltage is shown in Figure 3.7-38 (b) 3-60 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory U U 1 1 t 0 -1 t 0 -1 (a) (b) Figure 3.7-38 Variation curve of oscillation center voltage According to the above analysis, it can be shown that there is certain functional relation between the oscillation center voltage and power angle δ, thus the oscillation center voltage (Ucosφ) can be used to reflect the variation of power angle. Power angle varies continuously as an electrical quantity. As a result, the oscillation center voltage varies continuously during out-of-step oscillation, crossing the zero point. However, sudden variation or discontinuous change is a distinguished feature of oscillation center voltage during fault occurrence or clearance. During synchronous oscillation, the oscillation center voltage also varies continuously but it does not cross the zero point. Therefore, the oscillation center voltage can be used to discriminate among out-of-step oscillation, short-circuit fault and synchronous oscillation. The variation range of oscillation center voltage (Ucosφ) can be divided into seven zones on the variation plane, as shown in Figure 3.7-39. From the above analysis, the variation rules of oscillation center voltage (Ucosφ) during out-of-step oscillation are as follows: 1. During accelerating out-of-step condition, the variation rule of Ucosφ is 0 – 1 – 2 – 3 – 4 – 5 – 6–0 2. During decelerating out-of-step condition, the variation rule of Ucosφ is 0 – 6 – 5 – 4 – 3 – 2 – 1–0 U 1 U 1 0 2 3 0 -1 4 0 1 1 2 3 t 0 5 5 6 6 0 -1 t 4 0 Figure 3.7-39 The variation rule of oscillation center voltage 3-61 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory If the oscillation center voltage varies as the above mentioned rules, the relay consider it as out-of-step condition and issues tripping command after the time delay (i.e., the setting [78.N_Limit]), performing separation. The above analysis is based on the assumption that system impedance angle is 90°, while in practical system it is not, thus angle compensation is required. As shown in Figure 3.7-40, setting the system impedance angle φ L in the device, the angle compensation is made to the oscillation center voltage, U SCV U cos( 90 L ) I' EM EN U U cos 2 Figure 3.7-40 Vector diagram of the oscillation center voltage In order to locate the distance between the oscillation center and where the device is equipped, setting impedance measurement element is used to confirm the operation range of separation device, the operation characteristic of zone relay based on impedance discrimination is shown in Figure 3.7-41. EM ZM Z L ine ZN EN I Z Re v Relay U Z Fwd 3-62 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory ZN jX Z Fwd R δ Z Re v O ZM Figure 3.7-41 Operation characteristic of zone detector element Where: ZM and ZN are respective system impedances. ZFwd is the impedance from zone relay location to side-N system ZRev is the impedance from zone relay location to side-M system The measured impedance is the impedance of phase-BC, zone relay meet the operation criterion when the measured impedance is within the range of operation characteristic. Out-of-step protection will operate when both zone relay and out-of-step relay operate. In order to prevent out-of-step protection from being initiated under normal conditions, the device calculates in real-time the voltage vector of two points (ZFwd and ZRev) based on measured voltage and current, so as to calculate the phase angle between two voltage (δ), which participates in logic discrimination of out-of-step protection. 3.7.8.3 Function Block Diagram 78 78.En 78.On 78.Blk 78.St 78.Clr_Counter 78.St_Zone 78.Op 3.7.8.4 I/O Signals Table 3.7-10 I/O signals of out-of-step protection No. 1 Input Signal 78.En Description Out-of-step protection enabling input, it is triggered from binary input or programmable logic etc. 3-63 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 2 78.Blk 3 78.Clr_Counter No. Out-of-step protection blocking input, it is triggered from binary input or programmable logic etc. Clear the counter Output Signal Description 1 78.On Out-of-step protection is enabled. 2 78.St Out-of-step protection starts. 3 78.St_Zone 4 78.Op Zone detector element of out-of-step protection starts, whose operation characteristic is shown as Figure 3.7-41. Out-of-step protection operates. 3.7.8.5 Logic SIG 78.En EN [78.En] SIG 78.Blk SIG VTS.Alm SIG Ia>0.12In SIG Ib>0.12In SIG Ic>0.12In & & 78.On & t1 t2 78.St & & & SIG |δ|>[78.phi_Start] SIG U1<0.95Un SIG 8>dδ/dt>0.2 SIG Ucosφ from + to - & & Counter>[78.N_Limit] >=1 SIG 78.Clr_Counter & Counter>[78.N_Limit] SIG Ucosφ - to + EN [78.En_Trp] SIG δ<[78.phi_Trp] & 78.Op & >=1 SIG 78.St_Zone SIG 78.St & Figure 3.7-42 Logic diagram of out-of-step protection Where: U1 is positive-sequence voltage. t1 is the pickup time delay of discriminating oscillation, internal fixed value is 40ms t2 is the dropoff time delay of discriminating oscillation, internal fixed value is 3s 3-64 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory In order to prevent out-of-step protection from maloperation under normal conditions or faulty conditions, the system will be think as oscillation only the following conditions are all met. 1. Measured positive-sequence voltage (U1) is smaller than 0.95Un. 2. Three phase currents are all greater than 0.12In. 3. The change rate of power angle (dδ/dt) is within 0.2~8. 4. The power angle (δ) is greater than the minimum start angle ([78.Phi_Start]). 3.7.8.6 Settings Table 3.7-11 Settings of out-of-step protection No. Name Range Step Unit Remark Enabling/disabling out-of-step protection 1 78.En 0 or 1 0: disable 1: enable Enabling/disabling out-of-step protection 2 78.En_Trp operate to trip 0 or 1 0: disable 1: enable 3 78.Z_Fwd (0.000~4Unn)/In 0.001 ohm 4 78.Z_Rev (0.000~4Unn)/In 0.001 ohm 5 78.phi1_Reach 30.00~89.00 0.01 deg The forward impedance setting of zone detector element The reversal impedance setting of zone detector element The system impedance angle The minimum start angle, which generally 6 78.phi_Start 0~180 1 deg should be greater than maximum load angle. It is the maximum tripping angle after out-of-step protection operating, which is 7 78.phi_Trp 0~180.00 0.01 deg used to prevent the circuit breaker from incorrect operation due to too large current during tripping. It is generally set based on the breaking capacity of circuit breaker. 8 78.N_Limit 1~20 The number setting of out-of-step cycle, 1 and it is set as 2~3 generally 3.7.9 Power Swing Blocking Releasing When power swing occurs on the power system, the impedance measured by the distance measuring element may vary from the load impedance area into the operating zone of the distance element. The distance measuring element may operate due to the power swing occurs in many points of interconnected power systems. To keep the stability of whole power system, tripping due to operation of the distance measuring element during a power swing is generally not allowed. Our distance protection adopts power swing blocking releasing to avoid maloperation 3-65 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory resulting from power swing. In another word, distance protection is blocked all along under the normal condition and power swing when the respective logic settings are enabled. Only when fault (internal fault or power swing with internal fault) is detected, power swing blocking for distance protection is released by PSBR element. Power swing blocking for distance element will be released if any of the following PSBR elements operates. Each distance zone elements has respective setting for selection this function. Fault detector PSBR element (FD PSBR) Unsymmetrical fault PSBR element (UF PSBR) Symmetrical fault PSBR element (SF PSBR) 1. Fault detector PSBR element If any of the following condition is matched, FD PSBR will operate for 160ms. Positive sequence current is lower than the setting [21M.I_PSBR] or [21Q.I_PSBR] before general fault detector element operates. As shown in figure below, assuming that normal load impedance locates at position 1 and the impedance locates at position 2 when positive-sequence current is lower than the setting [21M.I_PSBR] or [21Q.I_PSBR], it means FD operates between point 1 and point 2 if operation condition for FD PSBR mentioned above is fulfilled (point 3 as an example), and then FD PSBR will operate for 160ms. [21.I_PSBR] FD Normal load impedance Point 1 Point 3 Point 2 2. Unsymmetrical fault PSBR element The operation criterion: I0+I2>m×I1 The “m”, an empirical value, is internal fixed coefficient which can ensure UF PSBR operation during power swing with internal unsymmetrical fault, while no operation during power swing or power swing with external fault. This decision mainly utilizes the "discrepancy" that there is no negative-sequence or zero-sequence current during power swing, and there are negative-sequence and zero-sequence currents in case of asymmetric fault. In addition, value of m is used to differentiate internal asymmetric fault and external asymmetric fault in case of power swing. 3-66 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory In case of power swing or both power swing and external fault, asymmetric fault discriminating element will not operate and distance protection will be blocked: In case of power swing but no fault, I0 and I2 are near zero, but I1 is very large. Asymmetric fault discriminating element will not operate. In case of both power swing and external fault, if center of power swing is in scope of protection, both phase-to-phase and grounding impedance relays may operate. At this time, selection of value of m is used to ensure no operation of asymmetric fault discriminating element, blocking of distance protection, and no incorrect operation without selectivity. If power swing center is not on this line, distance protection will not operate incorrectly without selectivity due to power swing. In case of internal asymmetric fault, asymmetric fault discriminating element operates and distance protection will be release to clear internal fault: In case of both power swing and internal fault, if at the instant of short circuit, system electric potential angle is not laid out, asymmetric fault discriminating element will operate at once. If at the instant of short circuit, system electric potential angle is laid out, asymmetric fault discriminating element will operate when system angle gradually decreases, or local side tripping may be activated after immediate operation of opposite side asymmetric fault discriminating element and releasing of distance protection tripping. In case of normal internal asymmetric phase-to-phase or grounding fault in the system, relatively large zero-sequence or negative-sequence component will exist. At this time, the above equation is true and distance protection will be released. 3. Symmetrical fault PSBR element If a three-phase fault occurs and FD PSBR is invalid (160ms after FD operates), neither FD PSBR nor UF PSBR will be able to release the distance protection. Thus, SF PSBR is provided for this case specially. This detection is based on measuring the voltage at power swing center, during power swing, U1cosΦ will constantly change periodically. UOS=U1×COSΦ Where: Φ: the angle between positive sequence voltage and current U1: the positive sequence voltage As shown in the figure below, assume system connection impedance angle of 90°, current vector will be perpendicular to the line connecting E M and EN, and have the same phase as power swing center voltage. During normal operation of system or power swing, U1cosΦ just reflects positive-sequence voltage of power swing center. In case of 3-phase short circuit, U1cosΦ is voltage drop on arc resistor, transition resistance is arc resistance, and voltage drop on arc resistor is less than 5%UN. In actual system, line impedance angle is not 90°. Through compensation of angle Φ, power swing center voltage can be measured accurately. After compensation, power swing center voltage is U1cos(Φ+90o-ΦL), where ΦL is line impedance angle. 3-67 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory EM I U EN UOS Φ During power swing, power swing center voltage U 1cosΦ has the following characteristics: When electric potential phase angle difference between power supplies at two sides is 180o, U1cosΦ=0 and change rate dU1cosΦ/dt is the maximum. When this phase angle difference is near 0 o, power swing center voltage change rate dU 1cosΦ/dt is the minimum. During short circuit, U 1cosΦ remains unchanged and dU1cosΦ/dt=0. However, in early stage of short circuit when normal state enters short circuit state, dU1cosΦ/dt is very large. Therefore, use of dU 1cosΦ/dt solely to differentiate power swing and short circuit is not complete. For these reasons, the method to release distance protection on condition that power swing center voltage U1cosΦ is less than a setting and after a short delay can be used as symmetric fault discriminating element. This element can accurately differentiate power swing and 3-phase short circuit fault, and constitute a complete power swing blocking scheme with other elements. The element to open distance protection if U 1cosΦ is less than a certain setting and after a delay is easy to realize and has short delay, and can trip fault more quickly and accurately trip 3-phase short circuit fault during power swing. The criterion of SF PSBR element comprises the following two parts: when -0.03UN<UOS<0.08UN, the SF PSBR element will operate after 150ms. when -0.1UN<UOS<0.25UN, the SF PSBR element will operate after 500ms. The second criterion is a backup of the first criterion allowing longer monitoring period of voltage variation. To reduce the time delay for SF PSBR element during power swing, the change rate of voltage at power swing center is also used which can release SF PSBR element quickly for the fault occurred during power swing. The typical release time is less than 60ms. 3.7.9.1 Function Block Diagram 21Mi 21Mi.En_PSBR 21Mi.Rls_PSBR 21Mi.Blk_PSBR 21M.Pilot.Rls_PSBR 21M.Pilot.En_PSBR 21M.Pilot.Blk_PSBR 3-68 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 21Qi 21Qi.En_PSBR 21Qi.Rls_PSBR 21Qi.Blk_PSBR 21Q.Pilot.Rls_PSBR 21Q.Pilot.En_PSBR 21Q.Pilot.Blk_PSBR 3.7.9.2 I/O Signals Table 3.7-12 I/O signals of PSBR No. Input Signal 1 21Mi.En_PSBR 2 21Qi.En_PSBR 3 21Mi.Blk_PSBR 4 21Qi.Blk_PSBR 5 21M.Pilot.En_PSBR 6 21M.Pilot.Blk_PSBR 7 21Q.Pilot.En_PSBR 8 21Q.Pilot.Blk_PSBR No. Output Signal Description Enabling power swing blocking releasing of zone i (Mho characteristic, i=1, 2, 3, 4, 5) Enabling power swing blocking releasing of zone i (Quad characteristic, i=1, 2, 3, 4, 5) Blocking power swing blocking releasing of zone i (Mho characteristic, i=1, 2, 3, 4, 5) Blocking power swing blocking releasing of zone i (Quad characteristic, i=1, 2, 3, 4, 5) Enabling power swing blocking releasing of pilot distance zone (Mho characteristic) Blocking power swing blocking releasing of pilot distance zone (Mho characteristic) Enabling power swing blocking releasing of pilot distance zone (Quad characteristic) Blocking power swing blocking releasing of pilot distance zone (Quad characteristic) Description 1 21Mi.Rls_PSBR PSBR operates to release zone i (Mho characteristic, i=1, 2, 3, 4, 5) 2 21Qi.Rls_PSBR PSBR operates to release zone i (Quad characteristic, i=1, 2, 3, 4, 5) 3 21M.Pilot.Rls_PSBR PSBR operates to release pilot distance zone (Mho characteristic) 4 21Q.Pilot.Rls_PSBR PSBR operates to release pilot distance zone (Quad characteristic) 3-69 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.7.9.3 Logic SIG 21Mi.En_PSBR SIG 21Mi.Blk_PSBR SIG FD.Pkp SIG 21Mi.Flg_PSBR SIG 21Mi.Enable_PSBR EN [21Mi.En_PSBR] SIG Symmetrical |U1cosΦ |< & 21Mi.Enable_PSBR & & >=1 & t 0ms Unblocking for SF 21Mi.Rls_PSBR >=1 >=1 & SIG Unsymmetrical |I0|+|I2|> Unblocking for UF SIG 21Mi.Flg_PSBR SET I1>[21M.I_PSBR] 0 3s & & 0 SIG FD.Pkp SIG 21Qi.En_PSBR SIG 21Qi.Blk_PSBR SIG FD.Pkp SIG 21Qi.Flg_PSBR SIG 21Qi.Enable_PSBR EN [21Qi.En_PSBR] SIG Symmetrical |U1cosΦ |< 160ms >=1 & 21Qi.Enable_PSBR & & >=1 & t 0ms Unblocking for SF >=1 21Qi.Rls_PSBR >=1 & SIG Unsymmetrical |I0|+|I2|> Unblocking for UF SIG 21Qi.Flg_PSBR SET I1>[21Q.I_PSBR] 0 3s & & 0 SIG 160ms >=1 FD.Pkp 3-70 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory SIG 21M.Pilot.En_PSBR SIG 21M.Pilot.Blk_PSBR SIG FD.Pkp SIG 21M.Pilot.Flg_PSBR SIG 21M.Pilot.Enable_PSBR EN [21M.Pilot.En_PSBR] SIG Symmetrical |U1cosΦ |< & 21M.Pilot.Enable_PSBR & & >=1 & t 0ms Unblocking for SF 21M.Pilot.Rls_PSBR >=1 >=1 & SIG Unsymmetrical |I0|+|I2|> Unblocking for UF SIG 21M.Pilot.Flg_PSBR SET I1>[21M.I_PSBR] 0 3s & & 0 SIG FD.Pkp SIG 21Q.Pilot.En_PSBR SIG 21Q.Pilot.Blk_PSBR SIG FD.Pkp SIG 21Q.Pilot.Flg_PSBR SIG 21Q.Pilot.Enable_PSBR EN [21Q.Pilot.En_PSBR] SIG Symmetrical |U1cosΦ |< 160ms >=1 & 21Q.Pilot.Enable_PSBR & & >=1 & t 0ms Unblocking for SF >=1 21Q.Pilot.Rls_PSBR >=1 & SIG Unsymmetrical |I0|+|I2|> Unblocking for UF SIG 21Q.Pilot.Flg_PSBR SET I1>[21Q.I_PSBR] 0 3s & & 0 SIG 160ms >=1 FD.Pkp Figure 3.7-43 Logic diagram of PSBR Where: i=1, 2, 3, 4, 5 21Mi.Flg_PSBR: Please refer to Figure 3.7-25 and Figure 3.7-26 3-71 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 21Qi.Flg_PSBR: Please refer to Figure 3.7-30 and Figure 3.7-31 21M.Pilot.Flg_PSBR and 21Q.Pilot.Flg_PSBR: Please refer to Figure 3.7-34 and Figure 3.7-35 3.7.9.4 Settings Table 3.7-13 Settings of PSBR No. Name Range Step Unit Remark Enabling/disabling zone i of distance protection controlled by PSBR (Mho 1 21Mi.En_PSBR 0 or 1 characteristic, i=1, 2, 3, 4, 5) 0: disable 1: enable Enabling/disabling zone i of distance protection controlled by PSBR (Quad 2 21Qi.En_PSBR 0 or 1 characteristic, i=1, 2, 3, 4, 5) 0: disable 1: enable Enabling/disabling pilot distance zone controlled by PSBR (Mho 3 21M.Pilot.En_PSBR 0 or 1 characteristic) 0: disable 1: enable Enabling/disabling pilot distance zone controlled by PSBR (Quad 4 21Q.Pilot.En_PSBR 0 or 1 characteristic) 0: disable 1: enable 5 21M.I_PSBR (0.050~30.000)×In 0.001 A 6 21Q.I_PSBR (0.050~30.000)×In 0.001 A Current setting for power swing blocking (Mho characteristic) Current setting for power swing blocking (Quad characteristic) 3.7.10 Distance SOTF Protection When the circuit breaker is closed manually or automatically, it is possible to switch on to a fault. This is especially critical if the line in the remote station is grounded, since the distance protection would not clear the fault until overreach zones (zone 2 and/or zone 3) time delays have elapsed. In this situation, however, the fastest possible clearance is required. The SOTF (switch onto fault) protection is a complementary function to the distance protection. With distance SOTF protection, a fast trip is achieved for a fault on the whole line, when the line is being energized. It shall be responsive to all types of faults anywhere within the protected line. Distance SOTF protection can be initiated by several cases, including manual closing signal, 3-pole reclosing, 1-pole reclosing and pole discrepancy conditions. 3-72 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.7.10.1 Function Block Diagram 21SOTF 21SOTF.En 21SOTF.On 21SOTF.Blk 21SOTF.Op 21SOTF.Op_PDF 3.7.10.2 I/O Signals Table 3.7-14 I/O signals of distance SOTF protection No. Input Signal 1 21SOTF.En 2 21SOTF.Blk No. Description Distance SOTF protection enabling input, it is triggered from binary input or programmable logic etc. Distance SOTF protection blocking input, it is triggered from binary input or programmable logic etc. Output Signal Description Accelerate distance protection to trip when manual closing or auto-reclosing to 1 21SOTF.Op 2 21SOTF.Op_PDF 3 21SOTF.On fault Accelerate distance protection to trip when another fault happened under pole discrepancy conditions Accelerate distance protection is enabled. 3.7.10.3 Logic SIG 21SOTF.En SIG 21SOTF.Blk EN [21SOTF.En] & & 21SOTF.On Figure 3.7-44 Logic diagram of enabling distance SOTF protection 1. For single circuit breaker mode 3-73 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory SIG CB1.52b_PhA SIG CB1.52b_PhB SIG CB1.52b_PhC SIG FD.Pkp SET [SOTF.Opt_Mode_ManCls]=CBPos SET [SOTF.Opt_Mode_ManCls]=ManClsBI/CBPos SET [SOTF.Opt_Mode_ManCls]=All SET [SOTF.Opt_Mode_ManCls]=ManClsBI SET [SOTF.Opt_Mode_ManCls]=ManClsBI/CBPos SET [SOTF.Opt_Mode_ManCls]=All SIG CB1.ManCls SET [SOTF.Opt_Mode_ManCls]=All SET [SOTF.Opt_Mode_ManCls]=AutoInit SIG Ua<[SOTF.U_Ddl] SIG Ub<[SOTF.U_Ddl] SIG Uc<[SOTF.U_Ddl] SIG FD.Pkp >=1 & >=1 >=1 & >=1 0ms [SOTF.t_En] Manual closing signal >=1 & & >=1 & [SOTF.t_DdL] 0ms SIG VTS.Alm SIG Ia<0.06In SIG Ib<0.06In SIG Ic<0.06In SIG 79.Close (3P) 0ms [SOTF.t_En] 3-pole reclosing signal SIG 79.Close (1P) 0ms [SOTF.t_En] 1-pole reclosing signal Dead line & Figure 3.7-45 Logic diagram of manual closing signal For double circuit breakers mode, the phase's open status corresponding to the line is invalid unless both circuit breakers are in open position. 2. For double circuit breakers mode 3-74 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory BI [CB1.52b_PhA] BI [CB2.52b_PhA] BI [CB1.52b_PhB] BI [CB2.52b_PhB] BI [CB1.52b_PhC] BI [CB2.52b_PhC] SIG FD.Pkp SET [SOTF.Opt_Mode_ManCls]=CBPos SET [SOTF.Opt_Mode_ManCls]=ManClsBI/CBPos SET [SOTF.Opt_Mode_ManCls]=All SET [SOTF.Opt_Mode_ManCls]=ManClsBI SET [SOTF.Opt_Mode_ManCls]=ManClsBI/CBPos SET [SOTF.Opt_Mode_ManCls]=All SIG CBx.ManCls SET [SOTF.Opt_Mode_ManCls]=All SET [SOTF.Opt_Mode_ManCls]=AutoInit SIG Ua<[SOTF.U_Ddl] SIG Ub<[SOTF.U_Ddl] SIG Uc<[SOTF.U_Ddl] SIG FD.Pkp & & >=1 & & >=1 >=1 & >=1 0ms [SOTF.t_En] Manual closing signal >=1 & & >=1 & [SOTF.t_DdL] SIG VTS.Alm SIG Ia<0.06In SIG Ib<0.06In SIG Ic<0.06In 0ms Dead line & Figure 3.7-46 Logic diagram of manual closing signal For accelerated tripping mode by manual closing signal, manual closing signal can be from circuit breaker position, external binary signal of manual closing or dead line check. When the circuit breaker is in open position while the device does not pick up, or external manual closing binary input is energized, then manual closing signal will be kept for the setting [SOTF.t_En], which will enable SOTF logic. When the initiation mode of SOTF protection is set as “AutoInit” (i.e., [SOTF.Opt_Mode_ManCls] is set as “AutoInit”), distance SOTF protection will be initiated by dead line check. When three phases currents are all smaller than 0.06In and no fault detector element operates, SOTF logic will be enabled only for the setting [SOTF.t_En] if three phase voltages are all smaller than the setting [SOTF.U_Ddl] with the time delay [SOTF.t_Ddl]. 3-75 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory It is selectable among zone 2, 3 or 4 of ditance protection which is accelerated to trip by manual closing signal, and they are not controlled by power swing blocking. SIG Manual closing signal SIG 21SOTF.On SIG FD.Pkp EN [21SOTF.En_ManCls] EN [21SOTF.Z2.En_ManCls] SIG 21M(21Q)2.Flg_PSBR EN [21SOTF.Z3.En_ManCls] SIG 21M(21Q)3.Flg_PSBR EN [21SOTF.Z4.En_ManCls] SIG 21M(21Q)4.Flg_PSBR & & & [21SOTF.t_ManCls] 0 21SOTF.Op_ManCls & & >=1 & Figure 3.7-47 Logic diagram of distance SOTF protection by manual closing signal 3-76 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory SIG FD.Pkp SIG 21SOTF.On EN [21SOTF.En_3PAR] SIG 3-pole reclosing signal EN [21SOTF.Z2.En_3PAR] SIG 21M(21Q)2.Flg_PSBR EN [21SOTF.Z2.En_PSBR] SIG 21M(21Q)2.Rls_PSBR EN [21SOTF.Z3.En_3PAR] SIG 21M(21Q)3.Flg_PSBR EN [21SOTF.Z3.En_PSBR] SIG 21M(21Q)3.Rls_PSBR EN [21SOTF.Z4.En_3PAR] SIG 21M(21Q)4.Flg_PSBR EN [21SOTF.Z4.En_PSBR] SIG 21M(21Q)4.Rls_PSBR EN [21SOTF.En_1PAR] SIG 52b_PhA SIG 21M(21Q)2.Rls_PSBR(A) SIG 52b_PhB SIG 21M(21Q)2.Rls_PSBR(B) SIG 52b_PhC SIG 21M(21Q)2.Rls_PSBR(C) & & [21SOTF.t_3PAR] 0 >=1 21SOTF.Op_AR & & >=1 & & & >=1 >=1 & & >=1 & & [21SOTF.t_1PAR] 50ms 0 & 50ms 0 & 50ms 0 & 0 >=1 Figure 3.7-48 Logic diagram of distance SOTF protection by 1-pole or 3-pole AR It is selectable among zone 2, 3 or 4 of ditance protection which is accelerated to trip by 3-pole AR signal, and it is settable whether they are controlled by power swing blocking. Zone 2 of distance protection is always accelerated to trip by 1-pole AR signal, and it is controlled by power swing blocking. For single-phase permanent fault, distance SOTF protection for 1-pole reclosing onto the faulty phase will trip three-phase circuit breaker. 3-77 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory SIG 52b_PhA SIG 21M(21Q)2.Rls_PSBR(A) SIG 52b_PhB SIG 21M(21Q)2.Rls_PSBR(B) SIG 52b_PhC SIG 21M(21Q)2.Rls_PSBR(C) 50ms 0 & 50ms 0 & 50ms 0 & >=1 >=1 SIG 21M(21Q)2.Rls_PSBR SIG 21SOTF.On SIG FD.Pkp EN [21SOTF.En_PDF] & & & [21SOTF.t_PDF] 0 21SOTF.Op_PDF Figure 3.7-49 Logic diagram of distance SOTF protection by PD condition Under pole discrepancy condition after single-phase tripping, distance SOTF protection will accelerate to operate if another fault happens to the healthy phase. SIG 21SOTF.Op_ManCls >=1 21SOTF.Op SIG 21SOTF.Op_AR Figure 3.7-50 Logic diagram of distance SOTF protection 3.7.10.4 Settings Table 3.7-15 Settings of distance SOTF protection No. Name Range Step Unit Remark Time delay of enabling SOTF protection (shared by distance 1 SOTF.t_En 0.000~10.000 0.001 s SOTF protection, phase current SOTF protection and residual current SOTF protection) Enabling/disabling distance SOTF 2 21SOTF.En protection 0 or 1 0: disable 1: enable Enabling/disabling distance 3 21SOTF.Zi.En_ManCls 0 or 1 SOTF i of protection zone for manual closing (i=2, 3, 4) 1: enable 0: disable 4 21SOTF.t_ManCls 0.000~10.000 0.001 3-78 s Time delay of distance protection PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory No. Name Range Step Unit Remark accelerating to trip when manual closing Enabling/disabling distance 5 21SOTF.Zi.En_3PAR 0 or 1 SOTF zone i of protection for 3-pole reclosing (i=2, 3, 4) 1: enable 0: disable Enabling/disabling zone i controlled by PSB of distance 6 21SOTF.Zi.En_PSBR SOTF 0 or 1 protection for 3-pole reclosing (i=2, 3, 4) 1: enable 0: disable Time delay of distance protection 7 21SOTF.t_3PAR 0.000~10.000 0.001 s accelerating to trip when 3-pole reclosing Enabling/disabling distance SOTF 8 21SOTF.En_1PAR 0 or 1 protection for 1-pole reclosing 1 0: disable 1: enable Time delay of distance protection 9 21SOTF.t_1PAR 0.000~10.000 0.001 s accelerating to trip when 1-pole reclosing Enabling/disabling distance SOTF protection under pole discrepancy 10 21SOTF.En_PDF 0 or 1 conditions 1: enable 0: disable Time delay of distance protection 11 21SOTF.t_PDF 0.000~10.000 0.001 s operating under pole discrepancy conditions 12 SOTF.U_Ddl 0~Unn 0.001 V 13 SOTF.t_Ddl 0.000~600.000 0.001 s Undervoltage setting of deadline detection Time delay of deadline detection Option of manual SOTF mode ManClsBI: initiated by input signal ManClsBI of manual closing CBPos 14 SOTF.Opt_Mode_ManCls CBPos: initiated by CB position ManClsBI/ ManClsBI/CBPos: CBPos initiated by either input signal of manual AutoInit closing or CB position All AutoInit: initiated by no voltage detection 3-79 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory No. Name Range Step Unit Remark All: initiated by both binary input and no voltage detection Table 3.7-16 Internal settings of distance SOTF protection No. Name Default Value Unit Remark Enabling/disabling distance SOTF protection for 1 21SOTF.En_ManCls manual closing 1 0: disable 1: enable Enabling/disabling distance SOTF protection for 2 21SOTF.En_3PAR 3-pole reclosing 1 0: disable 1: enable 3.8 Optical Pilot Channel (Option) 3.8.1 General Application When fibre optical channel is available between the devices at both ends, the devices have an optional module to transmit permissive signal or blocking signal (subject to the scheme selected), transfer signal and transfer trip via the fibre ports of the module. The communication rate can be 64kbits/s or 2048kbits/s via optional dedicated optical fibre channel or multiplex channel. By the setting [FO.Protocol], the device can support G.703 or C37.94. 3.8.2 Function Description 12 digital bits are integrated in each frame of transmission message for various applications. Each received message frame via fibre optical channel will pass through security check to ensure the integrity of the message consistently. The last four digital bits of the 12 have been assigned for pilot scheme protection. The communication channel can be configured as single channel mode or as dual channels mode. (FOx, x can be 1 or 2) according to the optical pilot channel module selected. 3.8.2.1 Channel Interface The modules can communicate in two modes via multiplexer or dedicated optical fibre. Communication through dedicated fibre is usually recommended unless the received power does not meet with the requirement. Channel of 64kbits/s or 2048kbits/s via dedicated fibre is shown in Figure 3.8-1 and Figure 3.8-2. Two fibre cores of optical cable are dedicated to pilot scheme protection. For dual firbre optical channels application, two fibre cores of optical cable are normally in service, and all data are exchanged via the other healthy core if one core is failed. 3-80 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Max 2km for 62.5/125um multi-mode FO C37.94 (N*64kbits/s) TX RX RX TX PCS-902 PCS-902 ST connectors ST connectors Max 2km for 62.5/125um multi-mode FO C37.94 (N*64kbits/s) ST connectors (FO1) PCS-902 ST connectors (FO1) TX RX RX TX TX RX RX TX PCS-902 ST connectors (FO2) ST connectors (FO2) Figure 3.8-1 Direct optical link up to 2km with 850nm Max 60km/110km for 9/125um single-mode FO TX RX RX TX PCS-902 PCS-902 FC connectors FC connectors Max 60km/110km for 9/125um single-mode FO FC connectors (FO1) FC connectors (FO1) TX RX RX TX TX RX RX TX PCS-902 PCS-902 FC connectors (FO2) FC connectors (FO2) Figure 3.8-2 Direct optical link up to 60km with1310nm or 110km with 1550nm Channel of 64kbits/s or 2048kbits/s via multiplexer is shown in Figure 3.8-3, Figure 3.8-4 and Figure 3.8-5. 3-81 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory C37.94 (N*64kbits/s) Multi-mode FO Communication convertor TX RX RX TX E Interface Link to communicate device PCS-902 ST connectors ST connectors Multi-mode FO ST connectors (FO1) O C37.94 (N*64kbits/s) ST connectors (FO1) Communication convertor TX RX RX TX TX RX RX TX E Interface Link to communicate device PCS-902 ST connectors (FO2) O ST connectors (FO2) Figure 3.8-3 Connect to a communication network via communication convertor G.703 (64kbits/s) Single-mode FO MUX-64 TX RX RX TX E Interface Link to communicate device PCS-902 FC connectors O FC connectors G.703 (64kbits/s) Single-mode FO FC connectors (FO1) FC connectors (FO1) TX RX RX TX TX RX RX TX MUX-64 E Interface Link to communicate device PCS-902 FC connectors (FO2) O FC connectors (FO2) Figure 3.8-4 Connect to a communication network via MUX-64 3-82 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory G.703-E1 (2048kbits/s) MUX-2M Single-mode FO TX RX RX TX E Interface Link to communicate device PCS-902 FC connectors O FC connectors Single-mode FO G.703-E1 (2048kbits/s) FC connectors (FO1) MUX-2M TX RX E RX TX TX RX RX TX FC connectors (FO1) Interface Link to communicate device PCS-902 FC connectors (FO2) O FC connectors (FO2) Figure 3.8-5 Connect to a communication network via MUX-2M The protection transmission data format is shown as following table. Bit High low Data Frame Description Format The header of transmission data format LocID The identity code of local device Time Time for synchronizing FOx.Send1~FOx.Send12 The twelve signals sent by channel No.x CRC 3.8.2.2 Communication Clock Valid messages exchange is key factor for digital pilot scheme protection. The device transmits and receives messages based on respective clocks, which are called transmit clock (i.e. clock TX) and receive clock (i.e. clock RX) respectively. Clock RX is fixed to be extracted from message frame, which can ensure no slip frame and no error message received. Clock TX has two options: 1. Use internal crystal clock, which is called internal clock. (master clock) 2. Use external clock. (slave clock) Depend on the clock used by the device at both ends, there are three modes. 1. Master-master mode 3-83 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Both ends use internal clock. 2. Slave-slave mode Both ends use external clock. 3. Master-slave mode One of them uses internal clock, the other uses external clock The logic setting [FOx.En_IntClock] is used in pilot scheme protection to select the communication clock. The internal clock is enabled automatically when the logic setting [FOx.En_IntClock] is set as “1”. Contrarily, the external clock is enabled automatically when the logic setting [FOx.En_IntClock] is set to “0”. If the device uses multiplex PCM channel, logic setting [FOx.En_IntClock] at both ends should be set as “0” (Mode 2). If the device uses dedicated optical fibre channel, clock Mode 1 and Mode 3 can be used. Mode 1 is recommended in considering simplification to user, i.e. logic setting [FOx.En_IntClock] at both ends should be set as “1”. 3.8.2.3 Identity Code In order to ensure reliability of the device when digital communication channel is applied, settings [FO.LocID] and [FO.RmtID] are provided as identity code to distinguish uniquely the device at remote end using same channel. Under normal conditions, the identity code of the device at local end should be different with that at remote end. In addition, it is recommended that the identity code of all devices, i.e., the setting [FO.LocID], should be unique in the power grid. The setting range is from 0 to 65535. Only for loop test, they are set as the same. The setting [FO.LocID] of the device at an end should be the same as the setting [FO.RmtID] of the device at opposite end and the greater [FO.LocID] between the two ends is chosen as a master end for sampling synchronism, the smaller [FO.LocID] is slave end. If the setting [FO.LocID] is set the same as [FO.RmtID], that implies the device in loopback testing state. The setting [FO.LocID] is packaged in the message frame and transmitted to the remote end. When the [FO.LocID] of the device at remote end received by local device is same to the setting [FO.RmtID] of local device, the message received from the remote end is valid, and protection information involved in message is read. When these settings are not matched, the message is considered as invalid and protection information involved in message is ignored, corresponding alarms will be issued. 3.8.2.4 Channel Statistics The device has the function of on-line channel monitoring and channel statistics. It can produce channel statistic report automatically at 9:00 every day and the report can be printed for operator to check the channel quality. The monitoring contents of channel status are shown as follows, and they can be viewed by the menu “Main Menu→Test→Prot Ch Counter→Chx Counter”. 1. FOx.StartTime (starting time) 3-84 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory It shows the starting time of the channel status statistics of the device at local end. 2. FO.RmtID (ID code of the remote end) It shows the ID information received by the device at local end now. 3. FOx.t_ChLag (propagation delay of channel x) It shows the calculated communication channel time delay of the device at local end now (unit: us). The calculation is based on the assumption of same channel path for to and from remote end. The device measures propagation delay of communication channel based on the below principle. Side S transmits a frame of message to side M, and meanwhile records the transmitting time “tss” on the basis of clock on side S. When side M receives the message, it will record receiving time “tmr” of the message with its own clock, and return a frame of message to side S at next fixed transmitting time, meanwhile data of “tms-tmr” is included in the frame of message. Side S will receive the message from side M at the time “tsr” and obtain the data of “tms-tmr”. Therefore, the propagation delay of the channel “Td” is obtained through calculation: Td (ts r t s s ) (tms t mr ) 2 By using the above calculated “Td”, the device automatically compensate time synchronization of sampling data at each end and transmission time lag. T1 tss tsr tmr Td tms "S" "M" T2 Figure 3.8-6 Schematic diagram of communication channel time 4. FOx.N_CRCFail (total number of error frame of channel x) It shows the total number of the error frames of the device at local end from starting time of channel statistics until now. Error frame means that this frame fails in CRC check. 5. FOx.N_FramErr (total number of abnormal messages of channel x) It shows the total number of abnormal messages of the device at local end from starting time of channel statistics until now. 3-85 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 6. FOx.N_FramLoss (total number of lost frames of channel x) It shows the total number of the lost frames of the device at local end from starting time of channel statistics until now. 7. FOx.N_RmtAbnor (total number of abnormal messages from the remote end of channel x) It shows the total number of abnormal messages received from the remote end from starting time of channel statistics until now. 8. FOx.N_CRCFailSec (total number of serious error frames of channel x) It shows the total number of serious error frame seconds of the device at local end from starting time of the channel statistics until now. 9. FOx.N_LossSyn (total number of loss synchronous of channel x) It shows the total number of loss synchronous of the device at local end from starting time of the channel statistics until now. 3.8.3 Function Block Diagram FOx FOx.En FOx.On FOx.Sendi FOx.Recvi FOx.Alm FOx.Alm_ID 3.8.4 I/O Signals Table 3.8-1 I/O signals of pilot channel No. Input Signal Description 1 FOx.En Enabling channel x 2 FOx.Sendi Sending signal i of channel x (i=1, 2, 3, ......, 8) 3 FOx.Send9 Sending signal 9 of channel x (it is configured by default as sending permissive signal 1 or sending A-phase permissive signal (only for phase-segregated command scheme)) 4 FOx.Send10 5 FOx.Send11 Sending signal 10 of channel x (it is configured by default as sending B-phase permissive signal (only for phase-segregated command scheme)) Sending signal 11 of channel x (it is configured by default as sending C-phase permissive signal (only for phase-segregated command scheme)) Sending signal 12 of channel x (it is configured by default as sending 6 FOx.Send12 permissive signal 2 only for pilot directional earth-fault protection adopting independent pilot channel 2) No. Output Signal Description 3-86 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 1 FOx.On Channel x is enabled. 2 FOx.Recvi Receiving signal i of channel x (i=1, 2, 3, ......, 8) Receiving signal 9 of channel x (it is configured by default as receiving 3 FOx.Recv9 permissive signal via pilot channel 1, or receiving permissive signal of A-phase via channel No.1 (only for phase-segregated command scheme)) Receiving signal 10 of channel x (it is configured by default as receiving 4 FOx.Recv10 permissive signal of B-phase via pilot channel 1 (only for phase-segregated command scheme)) Receiving signal 11 of channel x (it is configured by default as receiving 5 FOx.Recv11 permissive signal of C-phase via pilot channel 1 (only for phase-segregated command scheme)) Receiving signal 12 of channel x (it is configured by default as receiving 6 FOx.Recv12 permissive signal 2 only for pilot directional earth-fault protection adopting independent pilot channel 2) 7 FOx.Alm Channel x is abnormal 8 FOx.Alm_ID Received ID from the remote end is not as same as the setting [FO.RmtID] of the device in local end 3.8.5 Logic SIG Receiving transfer signal i from remote side & FOx.Recvi SIG FOx.Alm >=1 SIG FOx.Alm_ID SIG FOx.En & FOx.On EN FOx.En Figure 3.8-7 Logic diagram of receiving signal i i can be 1, 2, 3, ......, 12 3.8.6 Settings Table 3.8-2 Settings of pilot channel No. Name Range Step Unit Remark 1 FO.LocID 0-65535 1 Identity code of the device at local end 2 FO.RmtID 0-65535 1 Identity code of the device at remote end 3 FO.BaudRate 64 or 2048 4 FO.Protocol 5 FOx.Nx64k_C37.94 kbps Baud rate of optical pilot channel G.703 It is used to select protocol type, G.703 or C37.94 C37.94 1-12 1 The setting for the times of 64kbits/s, which 3-87 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory No. Name Range Step Unit Remark is an N*64kbits/s standard defined by IEEE C37.94 standard Option of internal clock or external clock 6 FOx.En_IntClock 0 or 1 0: external clock 1: internal clock Enabling/disabling channel x 7 FOx.En 0: disable 0 or 1 1: enable 3.9 Pilot Distance Protection 3.9.1 General Application The instant distance protection with underreaching setting is impossible to isolate the fault at remote end of the line, while distance protection with overreaching setting needs a time delay to grade with downstream protection to maintain discrimination. Pilot distance protection that exchanges distance protection information at both ends of the line can remove the fault within this line quickly, and will not operate for external fault. Pilot distance protection requires communication channel to exchange protection information at both ends. The channel may be dedicated or multiplexed channel through optical fiber or any other communication media. Pilot distance protection has schemes of permissive underreaching transfer trip (PUTT), permissive overreaching transfer trip (POTT) and blocking. The device provides duplicated pilot distance protections with dual channels. The communication media and mode can be independent each other. 3.9.2 Function Description Pilot distance protection determines whether it will send the signal to the remote end according to the discrimination result of the distance element or direction element. Pilot distance protection can be divided into permissive scheme and blocking scheme according to whether the signal sent is used to permit tripping or block tripping. For permissive scheme, it can be divided into overreaching mode or underreaching mode according to the setting of distance element and scheme selected, furthermore, it will provide the unblocking scheme as auxiliary function. For overreaching mode, current reversal logic and weak infeed logic are available for parallel line operation and weak power source situation respectively. Pilot distance protection is used to protect the whole line, and its setting is set as 1.2 times the line length at least, so the problem of overreaching does not exist and pilot distance protection, compared with the distance protection, it is not required to coordinate with other zones. In order to simplify setting calculation, the downward offset angle of the reactance of pilot distance protection with quadrilateral characteristic is fixed 12 °without setting, which has been well proved to be a reliable angle by large project experience and test data. The angle of directional line in the second quadrant (α) and the angle of directional line in the fourth quadrant (β) are as same as those of distance protection with quadrilateral characteristic. 3-88 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Pilot distance protection with permissive scheme receives permissive signal from the remote end, so as to combine with local discrimination condition to accelerate tripping, so it has high security. Blocking scheme will operate with a short time delay [85.t_DPU_Blocking1] if forward pilot zone element operates and not receiving blocking signal before the short time delay expired. Pilot distance protection can be enabled or disabled by input signals, logic setting and blocking signal, as shown in Figure 3.9-1. SIG 85-x.Z.En1 SIG 85-x.Z.En2 EN [85.Z.En] SIG 85-x.Z.Blk & & 85-x.Z.On Figure 3.9-1 Enabling/disabling logic of pilot distance protection Pilot distance protection receives and sends signals via pilot channel, and the logic of receiving signal is shown in Figure 3.9-2. NOTICE! For non-phase segregation mode, "85-x.Recv1" means that permissive signal of any phase is received from the remote end. However, for phase segregation mode, "85-x.Recv1" means that permissive signal of phase A is received from the remote end. 1. Non-phase segregated mode SET [85.Opt_PilotMode]=Blocking & >=1 2. SIG 85-x.Recv1 SIG 85-x.Abnor_Ch1 SIG 85-x.Unblocking1 Valid SET [85.Opt_PilotMode]=PUTT SET [85.Opt_PilotMode]=POTT SET [85.Opt_Ch_PhSeg]=0 & >=1 & >=1 & 85-x.Valid_Recv1 Phase segregated mode 3-89 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory SIG 85-x.Recv1 SIG 85-x.Abnor_Ch1 SIG 85-x.Unblocking1 Valid (Phase A) SET [85.Opt_PilotMode]=PUTT SET [85.Opt_PilotMode]=POTT SET [85.Opt_Ch_PhSeg]=1 SIG 85-x.RecvB SIG 85-x.Abnor_Ch1 SIG 85-x.Unblocking1 Valid (Phase B) SET [85.Opt_PilotMode]=PUTT SET [85.Opt_PilotMode]=POTT SET [85.Opt_Ch_PhSeg]=1 SIG 85-x.RecvC SIG 85-x.Abnor_Ch1 SIG 85-x.Unblocking1 Valid (Phase C) SET [85.Opt_PilotMode]=PUTT SET [85.Opt_PilotMode]=POTT SET [85.Opt_Ch_PhSeg]=1 & >=1 & >=1 & 85-x.Valid_Recv1 (Phase A) & >=1 & >=1 & 85-x.Valid_RecvB (Phase B) & >=1 & >=1 & 85-x.Valid_RecvC (Phase C) Figure 3.9-2 Logic diagram of receiving signal Pilot distance protection has the following application modes: 3.9.2.1 Zone Extension When pilot scheme protection is out of service due to pilot channel failure or no pilot scheme protection is provided. The fault outside zone 1 only can be cleared by zone 2 with a time delay. It can not ensure that all faults within protected line are cleared instantaneously. As a supplement of pilot scheme protection, zone extension can clear the fault within the whole line instantaneously. Different with pilot distance protection, zone extension can also operate for external close up fault in parallel line, but power supply can be restored by AR. So zone extension should be blocked when AR is out of service and is not ready. In order to prevent too many lines from disconnecting with system due to zone extension operate when the circuit breaker is closed into permanent fault, zone extension should be blocked when AR operates. For temporary fault, the line can be into service again after AR operates successfully. For permanent fault in either local line or parallel line, distance protection with a time delay will operate. 3-90 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory SIG FD.Pkp & SIG 85-x.ZX.En1 & SIG 85-x.ZX.En2 EN & 85-x.ZX.On [85.ZX.En] SIG 85-x.ZX.Blk1 >=1 SIG 85-x.ZX.Blk2 & SIG 79.Ready [85.t_DPU_ZX] & 0ms 85-x.Op_ZX SIG Zpilot Figure 3.9-3 Zone extension Zone extension uses the setting of pilot zone (ZPilot), and its operation characteristic can be Mho or Quad. 3.9.2.2 Permissive Underreaching Transfer Trip (PUTT) Distance elements zone 1 (Z1) with underreaching setting and pilot zone (ZPilot) with overreaching setting are used for this scheme. Z1 element will send permissive signal to the remote end and release tripping after Z1 time delay expired. After receiving permissive signal with ZPilot element pickup, a tripping signal will be released. The signal transmission element for PUTT is set according to underreaching mode, so current reversal need not be considered. For PUTT, there may be a dead zone under weak power source condition. If the fault occurs outside Z1 zone at strong power source side, Z1 at weak power supply side may not operate to trip and transmit permissive signal, and pilot distance protection will not operate. Therefore, the system fault can only be removed by Z2 at strong power source side with time delay. ZPilot Z2 Z1 EM M A Fault B Z1 EN N Z2 ZPilot 3-91 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Relay A Relay B Z1 Z1 & & 85-x.Op_Z 85-x.Op_Z ZPilot ZPilot Figure 3.9-4 Simple schematic of PUTT Pilot distance protection always adopts pilot channel 1, and the logic of PUTT is shown in Figure 3.9-5. NOTICE! For non-phase segregation mode, "85-x.Send1" means that permissive signal of any phase is sent to the remote end. However, for phase segregation mode, "85-x.Send1" means that permissive signal of phase A is sent to the remote end. 1. Non-phase segregated mode SIG 21M1(21Q1).Op 0ms 100ms SIG 85-x.ExTrp 0ms 150ms >=1 & SET [85.Opt_PilotMode]=PUTT 85-x.Send1 & & SIG 85-x.Z.On SIG FD.Pkp SIG 85-x.Valid_Recv1 & & 8ms 0ms 85-x.Op_Z SET [85.Opt_Ch_PhSeg]=0 SIG ZPilot 2. Phase segregated mode 3-92 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory SIG 21M1(21Q1).Op (Phase A) 0ms 100ms SIG 85-x.ExTrp 0ms 150ms >=1 & SET [85.Opt_PilotMode]=PUTT 85-x.Send1 (Phase A) & SIG 85-x.Z.On & SIG FD.Pkp SIG 85-x.Valid_Recv (Phase A) & & 8ms 0ms 85-x.Op_Z (Phase A) SET [85.Opt_Ch_PhSeg]=1 SIG Zpilot (Phase A) SIG 21M1(21Q1).Op (Phase B) 0ms 100ms SIG 85-x.ExTrp 0ms 150ms >=1 & SET [85.Opt_PilotMode]=PUTT 85-x.SendB (Phase B) & SIG 85-x.Z.On & SIG FD.Pkp SIG 85-x.Valid_Recv (Phase B) & & 8ms 0ms 85-x.Op_Z (Phase B) SET [85.Opt_Ch_PhSeg]=1 SIG Zpilot (Phase B) SIG 21M1(21Q1).Op (Phase C) 0ms 100ms SIG 85-x.ExTrp 0ms 150ms >=1 & SET [85.Opt_PilotMode]=PUTT 85-x.SendC (Phase C) & SIG 85-x.Z.On & SIG FD.Pkp SIG 85-x.Valid_Recv (Phase C) & & 8ms 0ms 85-x.Op_Z (Phase C) SET [85.Opt_Ch_PhSeg]=1 SIG Zpilot (Phase C) Figure 3.9-5 Logic diagram of pilot distance protection (PUTT) 3.9.2.3 Permissive Overreaching Transfer Trip (POTT) ZPilot will send permissive signal to remote end once it picks up and release tripping signal upon receiving permissive signal from the remote end. 3-93 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory When POTT is applied on parallel lines arrangement and the ZPilot setting covers 50% of the parallel line, there may be a problem under current reversal condition, settings for current reversal condition should be considered, please refer to section 3.9.2.6 for details. Under weak power source condition, the problem of dead zone at weak power source end is eliminated by the weak infeed logic, please refers to section 3.9.2.7 for details. ZPilot Z2 M EM Zpilot_Rev A Fault B EN N Zpilot_Rev Z2 ZPilot Relay A ZPilot & >=1 Relay B & 85-x.Op_Z 85-x.Op_Z WI >=1 ZPilot WI Figure 3.9-6 Simple schematic of POTT 1. Non-phase segregated mode 3-94 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory SIG Trp 0ms 100ms SIG 85-x.ExTrp 0ms 150ms SIG 52b_PhA >=1 & SIG 52b_PhB & & SIG 52b_PhC SET [85.Opt_Ch_PhSeg]=0 200ms & >=1 0ms SIG 85-x.Valid_Recv1 & SIG FD.Pkp 85-x.Send1 SET [85.Opt_PilotMode]=POTT SIG 85-x.Z.FwdDir & & >=1 8ms & SIG 85-x.Z.On 0ms 85-x.Op_Z & SIG WI SIG Current reversal blocking 2. Phase segregated mode SIG Trp 0ms 150ms SIG 85-x.ExTrp 0ms 150ms SIG 52b_PhA >=1 & SIG 52b_PhB & >=1 & 200ms 0ms SIG 52b_PhC SET [85.Opt_Ch_PhSeg]=1 & SIG 85-x.Valid_Recv(Phase A) & SIG FD.Pkp 85-x.Send1 (Phase A) SET [85.Opt_PilotMode]=POTT SIG 85-x.Z.FwdDir (Phase A) & & >=1 SIG 85-x.Z.On & 8ms 0ms 85-x.Op_Z (Phase A) & SIG WI (Phase A) SIG Current reversal blocking (Phase A) 3-95 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory SIG Trp 0ms 150ms SIG 85-x.ExTrp 0ms 150ms SIG 52b_PhA >=1 & SIG 52b_PhB & >=1 & 200ms 0ms SIG 52b_PhC SET [85.Opt_Ch_PhSeg]=1 & SIG 85-x.Valid_Recv(Phase B) & SIG FD.Pkp 85-x.SendB (Phase B) SET [85.Opt_PilotMode]=POTT SIG 85-x.Z.FwdDir (Phase B) & & >=1 SIG 85-x.Z.On 8ms & 0ms 85-x.Op_Z (Phase B) & SIG WI (Phase B) SIG Current reversal blocking (Phase B) SIG Trp 0ms 150ms SIG 85-x.ExTrp 0ms 150ms SIG 52b_PhA >=1 & SIG 52b_PhB & >=1 & 200ms 0ms SIG 52b_PhC SET [85.Opt_Ch_PhSeg]=1 & SIG 85-x.Valid_Recv(Phase C) & SIG FD.Pkp 85-x.SendB (Phase C) SET [85.Opt_PilotMode]=POTT SIG 85-x.Z.FwdDir (Phase C) & & >=1 SIG 85-x.Z.On & 8ms 0ms 85-x.Op_Z (Phase C) & SIG WI (Phase C) SIG Current reversal blocking (Phase C) Figure 3.9-7 Logic diagram of pilot distance protection (POTT) For current reversal blocking, please refer to section 3.9.2.6 for detail. 3.9.2.4 Blocking Permissive scheme has high security, but it relies on pilot channel seriously. Pilot distance protection will not operate when there is an internal fault with abnormal channel. Blocking scheme could be considered as an alternative. 3-96 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Blocking scheme takes use of pilot distance element Zpilot operation to terminate sending of blocking signal. Blocking signal will be sent once fault detector picks up without pilot zone Zpilot operation. Pilot distance protection will operate with a short time delay if pilot distance element operates and not receiving blocking signal after timer expired. The setting of pilot zone element Zpilot in Blocking scheme is overreaching, so current reversal condition should be considered. However, the short time delay of pilot distance protection has an enough margin for current reversal, that this problem has been resolved. The short time delay must consider channel delay and with a certain margin to set. As shown in Figure 3.9-8, an external fault happens to line MN. The fault is behind the device at M side, for blocking scheme, the device at M side will send blocking signal to the device at N side. If channel delay is too long, the device at side N has operated before receiving blocking signal. Hence, the time delay of pilot distance protection adopted in blocking scheme should be set according to channel delay. Blocking signal EM Fault M A N B EN Figure 3.9-8 Simple schematic of system fault For blocking scheme, pilot distance protection will operate when there is an internal fault with abnormal channel, however, it is possible that pilot distance protection issue an undesired trip when there is an external fault with abnormal channel. ZPilot EM M Zpilot_Rev A Fault B EN N Zpilot_Rev ZPilot Relay A Relay B FD.Pkp & Zpilot & [85.t_DPU_Blocking1] 85-x.Op_Z 85-x.Op_Z & FD.Pkp & Zpilot [85.t_DPU_Blocking1] Figure 3.9-9 Simple schematic of blocking 3-97 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory SIG Trp 0ms 100ms SIG 0ms 150ms 85-x.ExTrp SIG 52b_PhB >=1 & SIG 52b_PhA & >=1 & SIG 52b_PhC 200ms 0ms & SIG 85-x.Valid_Recv1 85-x.Send1 & SIG 85-x.Z.FwdDir >=1 SIG WI & [85.t_DPU_Blocking1] SIG FD.Pkp SET [85.Opt_PilotMode]=Blocking 85-x.Op_Z & SIG 85-x.Z.On Figure 3.9-10 Logic diagram of pilot distance protection (Blocking) Current reversal logic is only used for permissive scheme. For blocking scheme, the time delay of pilot distance protection has enough margin for current reversal, so current reversal need not be considered. 3.9.2.5 Unblocking Permissive scheme will trip only when it receives permissive signal from the remote end. However, it may not receive permissive signal from the remote end when pilot channel fails. For this case, pilot distance protection can adopt unblocking scheme. Under normal conditions, the signaling equipment works in the pilot frequency, and when the device operates to send permissive signal, the signaling equipment will be switched to high frequency. While pilot channel is blocked, the signaling equipment will receive neither pilot frequency signal nor high frequency signal. The signaling equipment will provide a contact to the device as unblocking signal. When the device receives unblocking signal from the signaling equipment, it will recognize channel failure, and unblocking signal will be taken as permissive signal temporarily. The unblocking function can only be used together with PUTT and POTT. 3-98 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory EN [85.En_Unblocking1] SIG 85-x.Unblocking1 & & [85.t_Unblocking1] 0ms SIG Detecting multi-phase fault >=1 & SET [85.Opt_PilotCh1] 85-x.Unblocking1 Valid SIG Pilot distance forward element Figure 3.9-11 Logic diagram of pilot distance protection (Unblocking) 3.9.2.6 Current Reversal When there is a fault in one of the parallel lines, the direction of the fault current may change during the sequence tripping of the circuit breaker at both ends as shown in Figure 3.9-12: When a fault occurs on line C–D near breaker D, the fault current through line A-B to D will flow from A to B. When breaker D is tripped, but breaker C is not tripped, the fault current in line A-B will then flow from B to A. This process is the current reversal. M Strong source EM N A B C M Weak source EN N A B EN EM D C Direction of fault current flow before CB‘D’open D Direction of fault current flow after CB‘D’open Figure 3.9-12 Current reversal As shown above, the device A judges a forward fault while the device B judges a reverse fault before break D is tripped. However, the device A judges a reverse fault while the device B judges a forward fault after breaker D is tripped. There is a competition between pickup and drop off of pilot zones in the device A and the device B when the fault measured by the device A changes from forward direction into reverse direction and vice versa for the device B. There may be maloperation for the device in line A-B if the forward direction of the device B has operated but the forward direction of the device A drops off slightly slower or the forward direction of the device B has operated but the forward direction information of the device A is still received due to the channel delay (the permissive signal is received). In general, the following two methods shall be adopted to solve the problem of current reversal: 1. The fault shall be measured by means of the reverse element of the device B. Once the reverse element of the device B operates, the send signals and the tripping circuit will be blocked for a period of time after a short time delay. This method can effectively solve the problem of competition between the device A and the device B, but there shall be a precondition. The reverse element of the device B must be in cooperation with the forward element of the device A, i.e. in case of a fault in adjacent lines, if the forward element of the device A operates, and the reverse element of the device B must also operate. Once the 3-99 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory bilateral cooperation fails, the anticipated function cannot be achieved. In addition, the blocking time for sending signals and the tripping circuit after the reverse element of the device B operates shall be set in combination with the channel time delay. 2. Considering the pickup and drop off time difference of distance elements and the channel time delay between the device A and the device B, the maloperation due to current reversal shall be eliminated by setting the time delay. The reverse direction element of the device is not required for this method, the channel time delay and the tripping time of adjacent breaker shall be taken into account comprehensively. This protection device adopts the second method to eliminate the maloperation due to current reversal. SIG Pilot forward zone start condition & t1 t2 Current reversal blocking SIG Signal received conditon Figure 3.9-13 Logic diagram of current reversal blocking t1: [85.t_DPU_CR1] t2: [85.t_DDO_CR1] Referring to above figure, when signal from the remote end is received without pilot forward zone pickup, the current reversal blocking logic is enabled after t1 delay. The time delay of t1 [85.t_DPU_CR1] shall be set the shortest possible but allowing sufficient time for pilot forward zone pickup, generally set as 25ms. Once the current reversal logic is enabled, the healthy line device B transfer tripping is blocked. The logic will be disabled by either the dropoff of signal or the pickup of pilot forward zone. A time delay t2 [85.t_DDO_CR1] is required to avoid maloperation for the case that the pilot forward zone (or forward element of pilot directional earth-fault protection) of device B picks up before the signal from device A drops off. Considering the channel propagation delay and the pickup and drop-off time difference of pilot forward zone (or pilot directional earth-fault element) with margin, t2 is generally set between 25ms~40ms. Because the time delay of pilot distance protection has an enough margin to current reversal, current reversal blocking only used for permissive scheme not blocking scheme. 3.9.2.7 Weak Infeed In case of a fault in line at one end of which there is a weak power source, the fault current supplied to the fault point from the weak power source is very small or even nil, and the conventional distance element could not operate. The weak infeed logic combines the protection information from the strong power source end and the electric feature of the local end to cope with the case. The weak infeed logic can be only applied for BOTT and POTT. The weak infeed logic has options for echo or both echo and tripping. 3-100 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory ZPilot Z1 M EM Zpilot_Rev A Fault Zpilot_Rev B Z1 EN N ZPilot Load Figure 3.9-14 Line fault description Both forward direction element and reverse direction element of pilot distance protection are used to discriminate weak infeed logic. When the weak infeed logic is enabled, distance forward and reverse element and direction element of directional earth-fault protection do not operate with the voltage lower than the setting [85.U_UV_WI] after the device picks up, upon receiving signal from remote end, the weak infeed logic will echo the signal back to remote end for 200ms if the weak infeed echo is enabled, the weak infeed end will echo signal and release tripping according to the logic. ZPilot_Rev at weak source end must coordinate with ZPilot_Set of the remote end. The coverage of ZPilot_Rev must exceed that of ZPilot_Set of the remote end. ZPilot_Rev only activates in the protection calculation when the weak infeed logic is enabled. In case of the weak infeed logic not enabled, the setting coordination is not required. If the device does not pick up, and the weak infeed logic is enabled, upon receiving signal from remote end with the voltage lower than the setting [85.U_UV_WI], the weak infeed logic will echo back to remote end for 200ms. When either weak infeed echo or weak infeed tripping is enabled, then the weak infeed logic is deemed to be enabled. During the device picking up, the weak infeed logic is shown in Figure 3.9-15. 3-101 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory SIG FwdDir_ROC & 85-x.DEF.FwdDir SET 3I0>[85.DEF.3I0_Set] SIG RevDir_ROC SIG FD.ROC.Pkp SIG Pilot distance forward direction 85-x.Z.FwdDir SIG Pilot distance reverse direction 85-x.Z.RevDir & 85-x.DEF.RevDir >=1 >=1 SIG Valid_Recv1 SIG FD.Pkp EN [85.En_WI] SET Up<[85.U_UV_WI] & & 85-x.WI >=1 & 200ms SET 0ms 85-x.UV_WI Upp<[85.U_UV_WI] Figure 3.9-15 Weak infeed logic during pickup For weak infeed end, the device may not pick up when a fault happens to the protected line. If the device does not pick up, the logic setting [85.En_WI_Pkp] is used to determine that weak infeed echo logic without pickup (as shown in Figure 3.9-16) or weak infeed trip logic without pickup (as shown in Figure 3.9-17) is executed. EN [85.En_WI_Pkp] SIG Signal receive condition EN [85.En_WI] & SET Up<[85.U_UV_WI] WI echo >=1 & 200ms 0ms 85-x.UV_WI SET Upp<[85.U_UV_WI] Figure 3.9-16 Weak infeed echo logic without pickup 3-102 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory SIG FwdDir_ROC & 85-x.DEF.FwdDir SET 3I0>[85.DEF.3I0_Set] SIG RevDir_ROC SIG FD.ROC.Pkp SIG Pilot distance forward direction SIG Pilot distance reverse direction & 85-x.DEF.RevDir 85-x.Z.FwdDir 85-x.Z.RevDir >=1 >=1 SIG Signal receive condition EN [85.En_WI_Pkp] EN [85.En_WI] SET Up<[85.U_UV_WI] & 85-x.WI >=1 & 200ms SET & 0ms 85-x.UV_WI Upp<[85.U_UV_WI] Figure 3.9-17 Weak infeed trip logic without pickup For permissive scheme, the signal receive condition means that the permissive signal is received or the unblocking signal is valid. 3.9.2.8 CB Echo A feature is also provided which enables fast tripping to be maintained along the whole length of the protected line, even when one terminal is open. The device will initiate sending a pulse of 200ms permissive signal when signal receive condition is met during CB is in open position. SIG FD.Pkp & & SIG 52b_PhA 200ms >=1 0ms & SIG 52b_PhB Send permissive signal SIG 52b_PhC SIG 85-x.Valid_Recv1 & SET [85.Opt_PilotMode]=POTT Figure 3.9-18 Simplified CB echo logic for POTT 3-103 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory CB Echo logic is only applied to permissive overreach mode not underreach mode, and it is processed without the device pickup. This logic will be terminated immediately once the device picks up. 3.9.3 Function Block Diagram 85 85-x.Z.En1 85-x.Z.On 85-x.Z.En2 85-x.ZX.On 85-x.Z.Blk 85.Op_Z 85-x.Abnor_Ch1 85.Z.On 85-x.Rcv1 85.ZX.On 85-x.RcvB 85-x.Op_Z 85-x.RcvC 85-x.Send1 85-x.ExTrp 85-x.SendB 85-x.Unblocking1 85-x.SendC 85-x.ZX.En1 85-x.Op_ZX 85-x.ZX.En2 85-x.ZX_St 85-x.ZX.Blk1 85-x.Z.FwdDir 85-x.ZX.Blk2 85-x.Z.RevDir 79.Ready 85-x.DEF.FwdDir 85-x.DEF.RevDir 85-x.WI 85-x.UV_WI 3.9.4 I/O Signals Table 3.9-1 I/O signals of pilot distance protection No. Input Signal 1 85-x.Z.En1 2 85-x.Z.En2 3 85-x.Z.Blk 4 85-x.Abnor_Ch1 Description Pilot distance protection x enabling input 1, it is triggered from binary input or programmable logic etc. (x=1 or 2) Pilot distance protection x enabling input 2, it is triggered from binary input or programmable logic etc. (x=1 or 2) Pilot distance protection x blocking input, it is triggered from binary input or programmable logic etc. (x=1 or 2) Input signal of indicating that pilot channel 1 is abnormal for pilot distance protection x (x=1 or 2) 3-104 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Input signal of receiving permissive signal via channel No.1 for pilot distance 5 85-x.Recv1 protection x, or input signal of receiving permissive signal of A-phase via channel No.1 for pilot distance protection x (only for phase-segregated command scheme, x=1 or 2) 6 85-x.RecvB 7 85-x.RecvC 8 85-x.ExTrp 9 85-x.Unblocking1 10 85-x.ZX.En1 11 85-x.ZX.En2 12 85-x.ZX.Blk1 13 85-x.ZX.Blk2 14 79.Ready No. Input signal of receiving permissive signal of B-phase via channel No.1 for pilot distance protection x (only for phase-segregated command scheme, x=1 or 2) Input signal of receiving permissive signal of C-phase via channel No.1 for pilot distance protection x (only for phase-segregated command scheme, x=1 or 2) Input signal of initiating sending permissive signal from external tripping signal for pilot distance protection x (x=1 or 2) Unblocking signal 1 of pilot distance protection x (x=1 or 2) Zone Extension enabling input 1 of pilot distance protection x, it is triggered from binary input or programmable logic etc. (x=1 or 2) Zone Extension enabling input 2 of pilot distance protection x, it is triggered from binary input or programmable logic etc. (x=1 or 2) Zone Extension blocking input 1 of pilot distance protection x, it is triggered from binary input or programmable logic etc. (x=1 or 2) Zone Extension blocking input 2 of pilot distance protection x, it is triggered from binary input or programmable logic etc. (x=1 or 2) AR has been ready for reclosing cycle. Output Signal Description 1 85-x.Z.On Pilot distance protection x is enabled. (x=1 or 2) 2 85-x.ZX.On Zone extension protection of pilot distance protection x is enabled. (x=1 or 2) 3 85-x.Op_Z Pilot distance protection x operates. (x=1 or 2) 4 85.Z.On 5 85.ZX.On 6 85.Op_Z General pilot distance protection is enabled. Which is OR operation between 85-1.Z.On and 85-2.Z.On General zone extension protection is enabled, which is OR operation between 85-1.ZX.On and 85-2.ZX.On General pilot distance protection operates, which is OR operation between 85-1.Op_Z and 85-2.Op_Z Output signal of sending permissive signal 1 or sending A-phase permissive 7 85-x.Send1 signal of pilot distance protection x (only for phase-segregated command scheme, x=1 or 2) Output signal of sending B-phase permissive signal of pilot distance protection x 8 85-x.SendB 9 85-x.SendC 10 85-x.Op_ZX Zone extension protection of pilot distance protection x operates. (x=1 or 2) 11 85-x.ZX_St Zone extension protection of pilot distance protection x starts (x=1 or 2) 12 85-x.Z.FwdDir Forward direction signal of pilot distance protection x (x=1 or 2) 13 85-x.Z.RevDir Reverse direction signal of pilot distance protection x (x=1 or 2) 14 85-x.DEF.FwdDir Forward direction signal of pilot directional earth-fault protection x (x=1 or 2) 15 85-x.DEF.RevDir Reverse direction signal of pilot directional earth-fault protection x (x=1 or 2) (only for phase-segregated command scheme, x=1 or 2) Output signal of sending C-phase permissive signal of pilot distance protection x (only for phase-segregated command scheme, x=1 or 2) 3-105 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 16 85-x.WI Operation signal of weak infeed logic of pilot distance protection x (x=1 or 2) 17 85-x.UV_WI Undervoltage signal of weak infeed logic of pilot distance protection x (x=1 or 2) 3.9.5 Settings Table 3.9-2 Settings of pilot distance protection No. Name Range Step Unit Remark POTT 1 85.Opt_PilotMode PUTT 1 Option of pilot scheme Blocking Option of phase-segregated signal scheme or single signal 2 85.Opt_Ch_PhSeg scheme 0 or 1 0: single signal scheme 1: phase-segregated signal scheme Enabling/disabling weak infeed 3 85.En_WI scheme 0 or 1 0: disable 1: enable For weak infeed end, If the device does not pick up for 4 85.En_WI_Pkp internal fault, it is used to 0 or 1 enable the device pick up. 0: disable 1: enable 5 85.U_UV_WI 0~Unn 0.001 V Undervoltage setting of weak infeed logic Enabling/disabling 6 85.Z.En pilot distance protection 0 or 1 0: disable 1: enable Enabling/disabling unblocking 7 85.En_Unblocking1 scheme 0 or 1 0: disable 1: enable Time 8 85.t_DPU_Blocking1 0.000~1.000 0.001 s scheme delay of for blocking pilot distance protection operation 9 85.t_DDO_CR1 0.000~1.000 0.001 s 10 85.t_DPU_CR1 0.000~1.000 0.001 s 11 85.ZX.En 0 or 1 Time delay dropoff for current reversal logic Time delay pickup for current reversal logic Enabling/disabling 3-106 zone PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory No. Name Range Step Unit Remark extension protection 0: disable 1: enable 12 85.t_DPU_ZX 0.000~10.000 0.001 s Pickup time delay for zone extension protection operation Table 3.9-3 Internal settings of pilot distance protection No. 1 Name 85.t_Unblocking1 Default Value 0.1 Unit s Remark Pickup time delay of unblocking scheme for pilot channel 1 Option of PLC channel for pilot channel 1 2 85.Opt_PilotCh1 1 0: phase-to-phase channel 1: phase-to-ground channel 3.10 Pilot Directional Earth-fault Protection 3.10.1 General Application Directional earth fault protection needs to coordinate with downstream protection with definite or inverse time delay so it cannot clear an internal fault quickly. Pilot directional earth-fault protection takes use of directional earth fault elements on both ends, it can detect high resistance fault and maintain high-speed operation. Pilot protection requires communication channel to exchange the protection information at both ends. The channel may be dedicated or multiplexed channel through optical fiber or any other communication media. Pilot directional earth-fault protection can be used independently, for example, no distance protection is equipped with the device but fast operation is required for the whole line, or it is used as backup protection of pilot distance protection to enhance the sensitivity for an earth fault with high fault resistance. 3.10.2 Function Description Sending permissive signal (or terminating sending signal) to the opposite end is controlled by forward direction element. Current reversal logic is available for parallel line operation and CB echo logic is provided once pilot directional earth fault protection is enabled. Current reversal logic is only used for permissive scheme. For blocking scheme, current reversal need not be considered because there is a settable time delay in pilot directional earth-fault protection. Pilot directional earth-fault protection can be enabled or disabled by input signals, logic setting and blocking signal, as shown in Figure 3.10-1. 3-107 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory SIG 85-x.DEF.En1 SIG 85-x.DEF.En2 EN [85.DEF.En] SIG 85-x.DEF.Blk & & 85-x.DEF.On Figure 3.10-1 Enabling/disabling logic of pilot directional earth-fault protection Pilot directional earth-fault protection comprises permissive scheme and blocking scheme. It can share pilot channel 1 ([85.DEF.En_IndepCh]=0) with pilot distance protection, or uses independent pilot channel 2 ([85.DEF.En_IndepCh]=1) by setting logic setting [85.DEF.En_IndepCh]. For underreach mode, pilot directional earth-fault always adopts independent pilot channel 2. The logic of receiving signal is shown in Figure 3.10-2. SET [85.Opt_PilotMode]=Blocking & >=1 SIG 85-x.Recv1 & SIG 85-x.Abnor_Ch1 SIG 85-x.Unblocking1 Valid & SET [85.Opt_PilotMode]=PUTT >=1 >=1 85-x.Valid_Recv_DEF EN [85.DEF.En_IndepCh] SET [85.Opt_PilotMode]=Blocking & & >=1 SIG 85-x.Recv2 & SIG 85-x.Abnor_Ch2 SIG 85-x.Unblocking2 Valid Figure 3.10-2 Logic diagram of receiving signal SIG FwdDir_ROC & 85-x.FwdDir_DEF_Pilot SIG 3I0>[85.DEF.3I0_Set] SIG RevDir_ROC & 85-x.RevDir_DEF_Pilot SIG FD.ROC.Pkp Figure 3.10-3 Forward/reverse direction of zero-sequence power 3-108 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.10.2.1 Permissive Transfer Trip (PTT) Pilot protection with permissive scheme receives permissive signal from the device of remote end, so as to combine with local discrimination condition to accelerate tripping, so it has high security. Operation of forward directional earth fault element is used to send permissive signal to the remote end when the protection is enabled and will release tripping signal upon receiving permissive signal from the remote end with further guarded by no operation of reverse directional earth fault element. This ensures the security of the protection. The following figure shows the schematic of permissive transfer trip. 85-x.FwdDir_DEF_Pilot M EM 85-x.RevDir_DEF_Pilot A Fault B EN N 85-x.RevDir_DEF_Pilot 85-x.FwdDir_DEF_Pilot Relay A 85-x.FwdDir_DEF_Pilot & & [85.DEF.t_DPU] 85-x.Op_DEF 85-x.Op_DEF [85.DEF.t_DPU] 85-x.FwdDir_DEF_Pilot Relay B Figure 3.10-4 Simple schematic of DEF (permissive scheme) 1. Independent channel mode 3-109 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 0ms SIG Trp [85.DEF.t_DPU]+200ms 0ms SIG 85-x.ExTrp SIG 52b_PhA >=1 150ms & SIG 52b_PhB & >=1 & & [85.DEF.t_DPU]+200ms 0ms 85-x.Send2 SIG 52b_PhC SIG 85-x.Valid_Recv2 EN & [85.DEF.En_IndepCh]=1 SIG FD.Pkp & SET [85.Opt_PilotMode]=PUTT >=1 & SET [85.Opt_PilotMode]=POTT SIG 85-x.DEF.On & SIG 85-x.FwdDir_DEF_Pilot & [85.DEF.t_DPU] & 85-x.Op_DEF & SIG 85-x.RevDir_DEF_Pilot SIG Current reversal blocking 2. Shared channel mode 0ms SIG Trp [85.DEF.t_DPU]+200ms 0ms SIG 85-x.ExTrp SIG 52b_PhA 150ms & SIG 52b_PhB >=1 & >=1 & [85.DEF.t_DPU]+200ms 0ms SIG 52b_PhC SIG 85-x.Valid_Recv1 EN & [85.DEF.En_IndepCh]=0 & SIG FD.Pkp SET [85.Opt_PilotMode]=POTT 85-x.Send1 & SIG 85-x.DEF.On & SIG 85-x.FwdDir_DEF_Pilot & & 85-x.Op_DEF & SIG 85-x.RevDir_DEF_Pilot SIG Current reversal blocking Figure 3.10-5 Logic diagram of DEF (permissive scheme) For current reversal blocking, please refer to section 3.10.2.4 for detail. 3.10.2.2 Blocking Permissive scheme has high security, but it relies on pilot channel seriously. Pilot directional 3-110 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory earth-fault protection will not operate when there is an internal fault with abnormal channel. Blocking scheme could be considered as an alternative. Blocking scheme sends blocking signal when fault detector picks up and zero-sequence forward element does not operate or both zero-sequence forward element and zero-sequence reverse element do not operate. Pilot directional earth-fault protection will operate if forward directional zero-sequence overcurrent element operates and not receiving blocking signal. 85-x.FwdDir_DEF_Pilot EM 85-x.RevDir_DEF_Pilot M A Fault B EN N 85-x.RevDir_DEF_Pilot 85-x.FwdDir_DEF_Pilot Relay A Relay B FD.Pkp FD.Pkp & 85-x.RevDir_DEF_Pilot & & & 85-x.FwdDir_DEF_Pilot 85-x.RevDir_DEF_Pilot 85-x.FwdDir_DEF_Pilot & & 85-x.Op_DEF & 85-x.Op_DEF [85.DEF.t_DPU] & [85.DEF.t_DPU] Figure 3.10-6 Simple schematic of blocking 1. Independent channel mode 3-111 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory SIG Trp 0ms [85.DEF.t_DPU]+200ms SIG 85-x.ExTrp 0ms 150ms SIG 52b_PhA >=1 & >=1 SIG 52b_PhB & SIG 52b_PhC 85-x.Send2 SIG 85-x.FwdDir_DEF_Pilot & SIG 85-x.RevDir_DEF_Pilot & SIG 85-x.Valid_Recv2 & EN [85.DEF.En_IndepCh]=1 & [85.DEF.t_DPU] SIG FD.Pkp SET [85.Opt_PilotMode]=Blocking 85-x.Op_DEF & SIG 85-x.DEF.On 2. Shared channel mode SIG Trp 0ms [85.DEF.t_DPU]+200ms SIG 85-x.ExTrp 0ms 150ms SIG 52b_PhA >=1 & >=1 SIG 52b_PhB & SIG 52b_PhC 85-x.Send1 SIG 85-x.FwdDir_DEF_Pilot & SIG 85-x.RevDir_DEF_Pilot & SIG 85-x.Valid_Recv1 & EN [85.DEF.En_IndepCh]=0 & [85.t_DPU_Blocking1] SIG FD.Pkp SET [85.Opt_PilotMode]=Blocking 85-x.Op_DEF & SIG 85-x.DEF.On Figure 3.10-7 Logic diagram of DEF (Blocking scheme) When DEF shares pilot channel 1 with pilot distance protection, time delay of pilot directional earth-fault protection will change from the setting [85.DEF.t_DPU] to the setting [85.t_DPU_Blocking1]. 3-112 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Because the time delay of pilot directional earth-fault protection has enough margin for current reversal, so blocking scheme should not consider the current reversal condition. For blocking scheme, pilot directional earth-fault protection will operate when there is an internal fault with abnormal channel, however, it is possible that pilot directional earth-fault protection issue an undesired trip when there is an external fault with abnormal channel. 3.10.2.3 Unblocking Permissive scheme will operate only when it receives permissive signal from the remote end. However, it may not receive permissive signal from the remote end when pilot channel fails. For this case, pilot directional earth-fault protection can adopt unblocking scheme. Under normal conditions, the signaling equipment works in the pilot frequency, and when the device operates to send permissive signal, the signaling equipment will be switched to high frequency. While the channel is blocked, the signaling equipment will receive neither pilot frequency signal nor high frequency signal. The signaling equipment will provide a contact to the device as unblocking signal. When the device receives unblocking signal from the signaling equipment, it will recognize channel failure, and unblocking signal will be taken as permissive signal temporarily. The unblocking scheme can only be used together with permissive scheme. EN [85.En_Unblocking2] & & SIG 85-x.Unblocking2 & [85.t_Unblocking2] SIG Selection of multi-phase EN 85-x.Unblocking2 Valid 0ms >=1 [85.Opt_PilotCh2] SIG Pilot DEF forward detection Figure 3.10-8 Logic diagram for unblocking 3.10.2.4 Current Reversal The reach of directional earth-fault protection is difficult to define. There may have problem for pilot direction earth-fault protection applied on parallel line arrangement due to current reversal phenomenon. When there is a fault in one of the parallel lines, the direction of the fault current may change during the sequence tripping of the circuit breaker at both ends as shown in Figure 3.10-9: When a fault occurs on line C–D near breaker D, the fault current through line A-B to D will flow from A to B. When breaker D is tripped, but breaker C is not tripped, the fault current in line A-B will then flow from B to A. This process is the current reversal. 3-113 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory M Strong source EM N A B C M Weak source EN N A B EN EM D C Direction of fault current flow before CB‘D’open D Direction of fault current flow after CB‘D’open Figure 3.10-9 Current reversal As shown above, the device A judges a forward fault while the device B judges a reverse fault before break D is tripped. However, the device A judges a reverse fault while the device B judges a forward fault after breaker D is tripped. There is a competition between pickup and drop off of pilot zones in the device A and the device B when the fault measured by the device A changes from forward direction into reverse direction and vice versa for the device B. There may be maloperation for the device in line A-B if the forward direction of the device B has operated but the forward direction of the device A drops off slightly slower or the forward direction of the device B has operated but the forward direction information of the device A is still received due to the channel delay (the permissive signal is received). In general, the following two methods shall be adopted to solve the problem of current reversal: 1. The fault shall be measured by means of the reverse element of the device B. Once the reverse element of the device B operates, the send signals and the tripping circuit will be blocked for a period of time after a short time delay. This method can effectively solve the problem of competition between the device A and the device B, but there shall be a precondition. The reverse element of the device B must be in cooperation with the forward element of the device A, i.e. in case of a fault in adjacent lines, if the forward element of the device A operates, and the reverse element of the device B must also operate. Once the bilateral cooperation fails, the anticipated function cannot be achieved. In addition, the blocking time for sending signals and the tripping circuit after the reverse element of the device B operates shall be set in combination with the channel time delay. 2. Considering the pickup and drop off time difference of distance elements and the channel time delay between the device A and the device B, the maloperation due to current reversal shall be eliminated by setting the time delay. The reverse direction element of the device is not required for this method, the channel time delay and the tripping time of adjacent breaker shall be taken into account comprehensively. This protection device adopts the second method to eliminate the maloperation due to current reversal. SIG 85-x.FwdDir_DEF_Pilot & t1 SIG t2 Current reversal blocking Signal received conditon Figure 3.10-10 Logic diagram of current reversal blocking 3-114 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory t1: pickup time delay of current reversal t2: dropoff time delay of current reversal When adopting independent pilot channel 2, t1 and t2 are the settings [85.t_DPU_CR2] and [85.t_DDO_CR2] respectively, which should be considered individually from channel 1. When sharing pilot channel 1 with pilot distance protection, t1 and t2 are the settings [85.t_DPU_CR1] and [85.t_DDO_CR1] respectively. Referring to above figure, when signal from the remote end is received without the operation of forward element of pilot directional earth-fault protection, the current reversal blocking logic is enabled after t1. t1 shall be set the shortest possible but allowing sufficient time for the operation of forward element of pilot directional earth-fault protection, generally set as 25ms. Once the current reversal logic is enabled, the healthy line device B transfer tripping is blocked. The logic will be disabled by either the dropoff of signal or the operation of forward element of pilot directional earth-fault protection. t2 is required to avoid maloperation for the case that the forward element of pilot directional earth-fault protection of device B picks up before the signal from device A drops off. Considering the channel propagation delay and the pickup and drop-off time difference of the forward element of pilot directional earth-fault protection with margin, t2 is generally set between 25ms~40ms. Because the time delay of pilot directional earth-fault protection has an enough margin to current reversal, current reversal blocking only used for permissive scheme not blocking scheme. 3.10.2.5 CB Echo When CB Echo logic is applied for DEF, the device will initiate sending a pulse of permissive signal if signal receive condition is met during CB is in open position. SIG FD.Pkp SIG 52b_PhA SIG 52b_PhB SIG 52b_PhC SIG 85-x Valid_Recv_DEF EN 85-x.DEF.On EN 85.DEF.En_IndepCh & >=1 & & [85.DEF.t_DPU]+200ms 0ms & 85-x Send_DEF Figure 3.10-11 Simplified CB Echo logic for POTT 3-115 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.10.3 Function Block Diagram 85 85-x.DEF.En1 85-x.DEF.On 85-x.DEF.En2 85-x.Op_DEF 85-x.DEF.Blk 85-x.DEF_BlkAR 85-x.Abnor_Ch1 85.DEF.On 85-x.Abnor_Ch2 85.Op_DEF 85-x.Rcv1 85.DEF_BlkAR 85-x.Rcv2 85-x.Send1 85-x.ExTrp 85-x.Send2 85-x.Unblocking1 85-x.Unblocking2 3.10.4 I/O Signals Table 3.10-1 I/O signals of pilot directional earth-fault protection No. Input Signal Description Pilot directional earth-fault protection x enabling input 1, it is triggered from binary 1 85-x.DEF.En1 2 85-x.DEF.En2 3 85-x.DEF.Blk 4 85-x.Abnor_Ch1 5 85-x.Abnor_Ch2 6 85-x.Recv1 7 85-x.Recv2 8 85-x.ExTrp 9 85-x.Unblocking1 Unblocking signal 1 for pilot directional earth-fault protection x (x=1 or 2) 10 85-x.Unblocking2 Unblocking signal 2 for pilot directional earth-fault protection x (x=1 or 2) No. Output Signal input or programmable logic etc. (x=1 or 2) Pilot directional earth-fault protection x enabling input 2, it is triggered from binary input or programmable logic etc. (x=1 or 2) Pilot directional earth-fault protection x blocking input, it is triggered from binary input or programmable logic etc. (x=1 or 2) Input signal of indicating that pilot channel 1 is abnormal for pilot directional earth-fault protection x (x=1 or 2) Input signal of indicating that pilot channel 2 is abnormal for pilot directional earth-fault protection x (x=1 or 2) Input signal of receiving permissive signal via channel 1 for pilot directional earth-fault protection x (x=1 or 2) Input signal of receiving permissive signal via channel 2 for pilot directional earth-fault protection x (x=1 or 2) Input signal of initiating sending permissive signal from external tripping signal (x=1 or 2) Description 1 85-x.DEF.On Pilot directional earth-fault protection x is enabled. (x=1 or 2) 2 85-x.Op_DEF Pilot directional earth-fault protection x operates. (x=1 or 2) 3-116 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3 85-x.DEF_BlkAR 4 85.DEF.On 5 85.Op_DEF 6 85.DEF_BlkAR Pilot directional earth-fault protection x operates to block AR. (x=1 or 2) General pilot directional earth-fault protection is enabled. It is OR operation between 85-1.DEF.On and 85-2.DEF.On General pilot directional earth-fault protection operates. It is OR operation between 85-1.Op_DEF and 85-2.Op_DEF General pilot directional earth-fault protection operates to block AR. It is OR operation between 85-1.DEF_BlkAR and 85-2.DEF_BlkAR Output signal of sending permissive signal 1 for pilot directional earth-fault 7 85-x.Send1 protection x when pilot directional earth-fault protection sharing pilot channel 1 with pilot distance protection (x=1 or 2) Output signal of sending permissive signal 2 for pilot directional earth-fault 8 85-x.Send2 protection x when pilot directional earth-fault protection adopting independent pilot channel 2 (x=1 or 2) 3.10.5 Settings Table 3.10-2 Settings of pilot directional earth-fault protection No. Name Range Step Unit Remark Enabling/disabling pilot directional 1 85.DEF.En earth-fault protection 0 or 1 0: disable 1: enable Enabling/disabling pilot directional earth-fault protection operate to block AR 2 85.DEF.En_BlkAR 0 or 1 0: selective phase tripping and not blocking AR 1: three-phase tripping and blocking AR Enabling/disabling channel for pilot independent directional earth-fault protection 3 85.DEF.En_IndepCh 0: 0 or 1 pilot directional earth-fault protection sharing same channel with pilot distance protection 1: pilot directional earth-fault adopting independent pilot channel Enabling/disabling unblocking scheme for pilot DEF via pilot 4 85.En_Unblocking2 0 or 1 channel 2 0: disable 1: enable 5 85.DEF.3I0_Set (0.050~30.000)×In 0.001 A Current setting of pilot directional earth-fault protection 3-117 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory No. 6 Name Range 85.DEF.t_DPU Step 0.001~10.000 Unit 0.001 s Remark Time delay of 85.t_DPU_CR2 0.000~1.000 0.001 s directional earth-fault protection Time 7 pilot delay pickup for current reversal logic when pilot directional earth-fault protection adopts independent pilot channel 2 Time delay dropoff for current 8 85.t_DDO_CR2 0.000~1.000 0.001 s reversal logic when pilot directional earth-fault protection adopts independent pilot channel 2 Table 3.10-3 Internal settings of pilot distance protection No. 1 Name Default Value 85.t_Unblocking2 Unit 0.2 s Remark Pickup time delay of unblocking scheme for pilot channel 2 Option of PLC channel for pilot channel 2 2 85.Opt_PilotCh2 1 0: phase-to-phase channel 1: phase-to-ground channel 3.11 Current Direction 3.11.1 General Application Overcurrent protection is widely used in the power system as backup protection, but in some cases, the direction of current is necessary to aid to complete the selective tripping. As shown below: L EM M C Fault D N A B EN Figure 3.11-1 Line fault description When line LM has an earth fault, the fault currents flowing through the relay A and the relay D are of similar magnitude in most cases. It is desirable that the fault is isolated from the power system by tripping the circuit breaker C and circuit breaker D. Hence, the overcurrent protection of relay A and relay D require to associate with current direction to fulfill selective tripping. Directional earth fault protection has a time delay due to coordinate with that of downstream so it cannot clear the fault quickly. Pilot directional earth-fault protection, which is fulfilled by directional earth fault element on both ends, it can maintain fast operation and achieve high sensitivity to detect high resistance fault. 3-118 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.11.2 Function Description The module computes direction of phase current and phase-to-phase current, zero-sequence current and negative-sequence current. The direction of phase current and phase-to-phase current equips with an under-voltage direction function to ensure that phase or phase-to-phase overcurrent protection has explicit directionality when the polarized voltage is too low for close up fault. The direction of zero-sequence current and negative-sequence current direction equips with an impedance compensation function to ensure that zero-sequence or negative-sequence overcurrent protection has explicit directionality when the zero-sequence voltage or the negative-sequence voltage is too low. 3.11.2.1 Phase/Phase-to-phase Current Direction By setting the characteristic angle [RCA_OC] to determine the most sensitive forward angle of phase current and phase-to-phase current, power value is calculated using phase current with phase polarized voltage or phase-to-phase current with phase-to-phase polarized voltage to determine the direction of phase current or phase-to-phase current respectively in forward direction or reverse direction. When the power value is zero, neither forward direction nor reverse direction is considered. As shown below: jX U φ θ I R O Forward direction Reverse direction Figure 3.11-2 Vector diagram of current and voltage Where: φ is the setting [RCA_OC] θ is the phase angle between polarized voltage and current The power value is calculated as below: 3-119 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory P=U×[I×COS(θ-φ)] 1. If P>0, the current direction polarized by U is forward direction 2. If P<0, the current direction polarized by U is reverse direction From above diagram can be seen, when θ=φ, P reaches to the maximum value. It is considered as the most sensitive forward direction. Hence, φ is called as sensitivity angle of phase overcurrent protection. 1. Polarized voltage of phase or phase-to-phase current direction In the event of asymmetrical fault, because phase or phase-to-phase voltage may decrease to very low voltage whereas positive-sequence voltage does not, the polarized voltage of phase or phase-to-phase current direction uses positive-sequence voltage to avoid wrong direction due to too low polarized voltage. Therefore, using positive-sequence voltage as polarized voltage can ensure that the direction determination has no dead zone for asymmetrical fault. For symmetric fault, if positive-sequence voltage decreases to 15%Un, the device uses memorized positive-sequence voltage as polarized voltage, the memorized positive-sequence voltage is 1.5 cycles pre-fault positive-sequence voltage. 2. Phase or phase-to-phase current direction under normal polarized voltage condition When using normal polarized voltage to calculate phase and phase-to-phase current direction, there are total twelve direction determination algorithm including forward direction and reverse direction. Table 3.11-1 Direction description Direction Phase A Phase B Phase C Phase AB Phase BC Phase CA 3. Polarized Voltage Current Forward direction U1a Ia Reverse direction U1a Ia Forward direction U1b Ib Reverse direction U1b Ib Forward direction U1c Ic Reverse direction U1c Ic Forward direction U1ab Iab Reverse direction U1ab Iab Forward direction U1bc Ibc Reverse direction U1bc Ibc Forward direction U1ca Ica Reverse direction U1ca Ica Phase or phase-to-phase current direction for under-voltage conditions When the symmetrical fault occurs on a power system, positive-sequence voltage may reduce to less than 0.15Un, the device will switch to phase or phase-to-phase current direction for under-voltage condition. The 1.5 cycle pre-fault positive-sequence voltage is used as polarized voltage with reverse threshold to ensure stable direction decision when three-phase voltage goes 3-120 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory to approximately zero due to close up fault. At first, the threshold is forward offset before direction is determined, and the threshold will be reversed offset after direction is determined. 3.11.2.2 Zero-sequence/Negative-sequence Current Direction By setting the characteristic angle [RCA_ROC] and [RCA_NegOC] to determine the most sensitive forward angle of zero-sequence current and negative-sequence current, power value is calculated using zero-sequence current with zero-sequence voltage or negative-sequence current with negative-sequence voltage to determine the direction of zero-sequence current and negative-sequence current respectively in forward direction or reverse direction. When the power value is between 0 and -0.1In, neither forward direction nor reverse direction is considered. jX 3U0 θ-180° -3I0 φ R O 3I0 θ Reverse direction Forward direction Figure 3.11-3 Vector diagram of zero-sequence power Vector diagram of negative-sequence power is similar to that of zero-sequence power. Where: φ is the setting [RCA_ROC] or the setting [RCA_NegOC] θ is the phase angle between zero/negative-sequence voltage and zero/negative-sequence current 3I0: calculated zero-sequence current by vector sum of Ia, Ib and Ic The power value is calculated as below: P=U×[I×COS(θ-φ)] If P>0, the direction of zero /negative-sequence current is reverse direction 3-121 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory If P<-0.1InVA, the direction of zero /negative-sequence current is forward direction 1. The direction of zero-sequence current Calculating the power value using zero-sequence current (3I0) and zero-sequence voltage (3U0) to determine the direction of zero-sequence current According to the equation: The zero-sequence current and the zero-sequence voltage can be gained by calculation Zero-sequence power is: P=3U0×[3I0×COS(θ-φ)] 2. The direction of negative-sequence current Calculating the power value using negative-sequence current (3I2) and negative-sequence voltage (3U2) to determine the direction of negative-sequence current According to the equation: The negative-sequence current and the negative-sequence voltage can be gained by calculation Negative-sequence power is: P=3U2×[3I2×COS(θ-φ)] 3. The direction of zero-sequence/negative-sequence current with impedance compensation When zero-sequence impedance or negative-sequence impedance behind the device is very small, if the fault in forward direction happens, the measured zero-sequence voltage or negative-sequence voltage by the device may be relatively small to determine correct direction. In order to solve this problem, compensated zero-sequence voltage and negative-sequence voltage are used for power calculation. The compensation formula is as follows: is the setting [Z0_Comp], which cannot exceed the total zero-sequence impedance of the protected line, and a half of the total zero-sequence impedance of the protected line is 3-122 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory recommended. is the setting [Z2_Comp], which cannot exceed the total negative-sequence impedance of the protected line. NOTICE! Phase current direction element is used as the direction element of phase overcurrent protection and auxiliary direction element of distance protection. It is required to set according to actual system parameters. Hence, the setting [RCA_OC] should be set correctly according to actual system parameters if distance protection is enabled even if phase overcurrent protection is disabled. Zero-sequence current direction element is used as the direction element of earth fault protection and auxiliary direction element of zone 1 of distance protection. It is required to set according to actual system parameters. Hence, the setting [RCA_ROC] should be set correctly according to actual system parameters if distance protection is enabled even if earth fault protection is disabled. Negative-sequence current direction element is used as the direction element of negative-sequence overcurrent protection and auxiliary direction element of distance protection and phase overcurrent protection for asymmetric fault. It is required to set according to actual system parameters. Hence, the setting [RCA_NegOC] should be set correctly according to actual system parameters if any of distance protection and phase overcurrent protection is enabled even if negative-sequence overcurrent protection is disabled. 3-123 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.11.3 Function Block Diagram DIR FwdDir_ROC RevDir_ROC FwdDir_NegOC RevDir_NegOC FwdDir_A FwdDir_B FwdDir_C RevDir_A RevDir_B RevDir_C FwdDir_AB FwdDir_BC FwdDir_CA RevDir_AB RevDir_BC RevDir_CA 3.11.4 I/O Signals Table 3.11-2 I/O signals of current direction No. Output Signal Description 1 FwdDir_ROC The forward direction of zero-sequence power 2 RevDir_ROC The reverse direction of zero-sequence power 3 FwdDir_NegOC The forward direction of negative-sequence power 4 RevDir_NegOC The reverse direction of negative-sequence power 5 FwdDir_A The forward direction of phase-A current 6 FwdDir_B The forward direction of phase-B current 7 FwdDir_C The forward direction of phase-C current 8 RevDir_A The reverse direction of phase-A current 9 RevDir_B The reverse direction of phase-B current 10 RevDir_C The reverse direction of phase-C current 11 FwdDir_AB The forward direction of phase-AB current 12 FwdDir_BC The forward direction of phase-BC current 13 FwdDir_CA The forward direction of phase-CA current 3-124 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 14 RevDir_AB The reverse direction of phase-AB current 15 RevDir_BC The reverse direction of phase-BC current 16 RevDir_CA The reverse direction of phase-CA current 3.11.5 Settings Table 3.11-3 Settings of current direction No. Name Range Step Unit 1 RCA_OC 30.00~89.00 0.01 deg 2 RCA_ROC 30.00~89.00 0.01 deg 3 RCA_NegOC 30.00~89.00 0.01 deg 4 Z0_Comp (0.000~4Unn)/In 0.001 ohm 5 Z2_Comp (0.000~4Unn)/In 0.001 ohm Remark The characteristic angle of directional phase overcurrent element The characteristic angle of directional earth fault element The characteristic angle of directional negative-sequence overcurrent element The compensated zero-sequence impedance The compensated negative-sequence impedance 3.12 Phase Overcurrent Protection 3.12.1 General Application When a fault occurs in power system, usually the fault current would be very large and phase overcurrent protection operates monitoring fault current is then adopted to avoid further damage to protected equipment. Directional element can be selected to improve the sensitivity and selectivity of the protection. For application on feeder-transformer circuits, second harmonic can also be selected to block phase overcurrent protection to avoid the effect of inrush current on the protection. 3.12.2 Function Description Phase overcurrent protection has following functions: 1. Four-stage phase overcurrent protection with independent logic, current and time delay settings. 2. All stages can be selected as definite-time or inverse-time characteristic. The inverse-time characteristic is selectable among IEC and ANSI/IEEE standard inverse-time characteristics, and a user-defined inverse-time curve is available for stage 1 of phase overcurrent protection. 3. Direction control element can be selected to control each stage phase overcurrent protection with three options: no direction, forward direction and reverse direction. 4. Second harmonic can be selected to block each stage of phase overcurrent protection. 3.12.2.1 Overview Phase overcurrent protection consists of following three elements: 3-125 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 1. Overcurrent element: each stage is independent overcurrent element. 2. Direction control element: one direction control element shared by all overcurrent elements, and each overcurrent element can individually select protection direction. When phase overcurrent protection is controlled by direction control element, negative-sequence current direction element is also effective to ensure correct operation, especially for phase-to-phase fault. 3. Harmonic blocking element: one harmonic blocking element shared by all overcurrent elements and each phase overcurrent element can individually enable the output signal from harmonic element as a blocking input. 3.12.2.2 Phase Overcurrent Element The operation criterion for each stage of overcurrent element is: Ip> [50/51Pi.I_Set] Equation 3.12-1 Where: Ip is measured phase current. [50/51Pi.I_Set] is the current setting of stage i of overcurrent element. (i=1, 2, 3, or 4) 3.12.2.3 Direction Control Element In order to prevent phase current direction element from overreaching operation characteristic for phase-to-phase fault, negative-sequence current direction element is also used as auxiliary direction criterion of phase overcurrent protection for asymmetric fault. Please refer to section 3.11 for details. 3.12.2.4 Harmonic Blocking Element When phase overcurrent protection is used to protect feeder-transformer circuits harmonic blocking function can be selected for each stage of phase overcurrent element by configuring logic setting [50/51Pi.En_Hm2_Blk] to prevent maloperation due to inrush current. When the percentage of second harmonic component to fundamental component of any phase current is greater than the setting [50/51P.K_Hm2], harmonic blocking element operates to block stage x overcurrent element if corresponding logic setting [50/51Pi.En_Hm2_Blk] enabled. Operation criterion: IP_2nd>[50/51P. K_Hm2]×IP Equation 3.12-2 Where: is second harmonic of phase current is fundamental component of phase current. 3-126 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory [50/51P.K_Hm2] is harmonic blocking coefficient. If fundamental component of any phase current is lower than the minimum operating current (0.1In), then harmonic calculation is not carried out and harmonic blocking element does not operate. 3.12.2.5 Characteristic Curve All stages can be selected as definite-time or inverse-time characteristic, inverse-time operating characteristic is as follows. Equation 3.12-3 Where: Iset is current setting [50/51Pi.I_Set]. Tp is time multiplier setting [50/51Pi.TMS]. α is a constant. K is a constant. C is a constant. I is measured phase current from line CT The user can select the operating characteristic from various inverse-time characteristic curves by setting [50/51Pi.Opt_Curve], and parameters of available characteristics for selection are shown in the following table. Table 3.12-1 Inverse-time curve parameters 50/51Pi.Opt_Curve α K Time Characteristic C DefTime Definite time IECN IEC Normal inverse 0.14 0.02 0 IECV IEC Very inverse 13.5 1.0 0 IECE IEC Extremely inverse 80.0 2.0 0 IECST IEC Short-time inverse 0.05 0.04 0 IECLT IEC Long-time inverse 120.0 1.0 0 ANSIE ANSI Extremely inverse 28.2 2.0 0.1217 ANSIV ANSI Very inverse 19.61 2.0 0.491 ANSI ANSI Inverse 0.0086 0.02 0.0185 ANSIM ANSI Moderately inverse 0.0515 0.02 0.114 ANSILTE ANSI Long-time extremely inverse 64.07 2.0 0.25 ANSILTV ANSI Long-time very inverse 28.55 2.0 0.712 ANSILT ANSI Long-time inverse 0.086 0.02 0.185 UserDefine Programmable user-defined 3-127 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory If all available curves do not comply with user application, user may set [50/51Pi.Opt_Curve] as “UserDefine” to customize the inverse-time curve characteristic with constants α, K and C. (only stage 1) When inverse-time characteristic is selected, if calculated operating time is less than setting [50/51Pi.tmin], then the operating time of the protection changes to the value of setting [50/51Pi.tmin] automatically. Define-time or inverse-time phase overcurrent protection drops off instantaneously after fault current disappears. 3.12.3 Function Block Diagram 50/51Pi 50/51Pi.En1 50/51Pi.On 50/51Pi.En2 50/51Pi.StA 50/51Pi.Blk 50/51Pi.StB 50/51Pi.StC 50/51Pi.St 50/51Pi.Op 3.12.4 I/O Signals Table 3.12-2 I/O signals of phase overcurrent protection No. Input Signal 1 50/51Pi.En1 2 50/51Pi.En2 3 50/51Pi.Blk No. Output Signal Description Stage i of phase overcurrent protection enabling input 1, it is triggered from binary input or programmable logic etc. (i=1, 2, 3, 4) Stage i of phase overcurrent protection enabling input 2, it is triggered from binary input or programmable logic etc. (i=1, 2, 3, 4) Stage i of phase overcurrent protection blocking input, it is triggered from binary input or programmable logic etc. (i=1, 2, 3, 4) Description 1 50/51Pi.On Stage i of phase overcurrent protection is enabled. (i=1, 2, 3, 4) 2 50/51Pi.Op Stage i of phase overcurrent protection operates. (i=1, 2, 3, 4) 3 50/51Pi.St Stage i of phase overcurrent protection starts. (i=1, 2, 3, 4) 4 50/51Pi.StA Stage i of phase overcurrent protection starts (A-Phase, i=1, 2, 3, 4). 5 50/51Pi.StB Stage i of phase overcurrent protection starts (B-Phase, i=1, 2, 3, 4). 6 50/51Pi.StC Stage i of phase overcurrent protection starts (C-Phase, i=1, 2, 3, 4). 3-128 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.12.5 Logic EN [50/51Pi.En] & SIG 50/51Pi.En1 & 50/51Pi.On SIG 50/51Pi.En2 >=1 SIG 50/51Pi.Blk 50/51Pi.St SET Ia>[50/51Pi.I_Set] & 50/51Pi.StA SET Ib>[50/51Pi.I_Set] & 50/51Pi.StB SET Ic>[50/51Pi.I_Set] & 50/51Pi.StC SET [50/51Pi.Opt_Dir]=Forward & SIG Forward DIR SET [50/51Pi.Opt_Dir]=Reverse & >=1 >=1 SIG Reverse DIR SIG VTS.Alm EN & [50/51Pi.En_VTS_Blk] SET [50/51Pi.Opt_Dir]=Non_Directional SIG Three phase currents 2nd Hm Detect & & SIG IP_2nd>[ 50/51P.K_Hm2]×IP SET [50/51Pi.En_Hm2_Blk] SIG 50/51Pi.On & SIG FD.Pkp SET [50/51Pi.Opt_Curve]=DefTime & [50/51Pi.t_Op] 0 >=1 50/51Pi.Op & Timer t SIG 50/51Pi.St Figure 3.12-1 Logic diagram of phase overcurrent protection i=1, 2, 3, 4 3-129 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.12.6 Settings Table 3.12-3 Settings of phase overcurrent protection No. Name Range Step Unit Remark Setting 1 50/51P.K_Hm2 0.000~1.000 0.001 of component second for harmonic blocking phase overcurrent elements 2 50/51Pi.I_Set (0.050~30.000)×In 0.001 A 3 50/51Pi.t_Op 0.000~20.000 0.001 s Current setting for stage i of phase overcurrent protection (i=1, 2, 3, 4) Time delay for stage i of phase overcurrent protection (i=1, 2, 3, 4) Enabling/disabling stage i of phase 4 50/51Pi.En overcurrent protection (i=1, 2, 3, 4) 0 or 1 0: disable 1: enable Enabling/Disabling auto-reclosing blocked when stage i of phase 5 50/51Pi.En_BlkAR overcurrent protection operates (i=1, 0 or 1 2, 3, 4) 0: disable 1: enable Enabling/Disabling stage i of phase overcurrent protection is blocked by 6 50/51Pi.En_VTS_Blk 0 or 1 VT circuit failure (i=1, 2, 3, 4) 0: disable 1: enable Non_Directional 7 50/51Pi.Opt_Dir Direction option for stage i of phase Forward overcurrent protection (i=1, 2, 3, 4) Reverse Enabling/disabling second harmonic blocking for 8 50/51Pi.En_Hm2_Blk 0 or 1 stage i of phase overcurrent protection (i=1, 2, 3, 4) 0: disable 1: enable DefTime IECN IECV IECE 9 50/51Pi.Opt_Curve Option of characteristic curve for IECST stage IECLT i of phase overcurrent protection (i=1, 2, 3, 4) ANSIE ANSIV ANSI ANSIM 3-130 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory No. Name Range Step Unit Remark ANSILTE ANSILTV ANSILT UserDefine Time multiplier setting for stage i of 10 50/51Pi.TMS 0.010~200.000 0.001 inverse-time phase overcurrent protection (i=1, 2, 3, 4) Minimum operating time for stage i 11 50/51Pi.tmin 0.000~20.000 0.001 s of inverse-time phase overcurrent protection (i=1, 2, 3, 4) Constant 12 50/51P1.Alpha 0.010~5.000 0.001 “α” for customized stage 1 of inverse-time characteristic phase overcurrent protection Constant 13 50/51P1.C 0.000~20.000 0.001 “C” for customized stage 1 of inverse-time characteristic phase overcurrent protection Constant 14 50/51P1.K 0.050~20.000 0.001 “K” for customized characteristic stage 1 of inverse-time phase overcurrent protection 3.13 Earth Fault Protection 3.13.1 General Application During normal operation of power system, there is trace residual current, whereas a fault current flows to earth will result in greater residual current. Therefore, residual current is adopted for the calculation of earth fault protection. In order to improve the selectivity of earth fault protection in power grid with multiple power sources, directional element can be selected to control earth fault protection. For application on line-transformer unit, second harmonic also can be selected to block earth fault protection to avoid the effect of sympathetic current on the protection. 3.13.2 Function Description Earth fault protection has following functions: 1. Four-stage earth fault protection with independent logic, current and time delay settings. 2. All stages can be selected as definite-time or inverse-time characteristic. The inverse-time characteristic is selectable, among IEC and ANSI/IEEE standard inverse-time characteristics, and a user-defined inverse-time curve is available for stage 1 of earth fault protection. 3. Directional element can be selected to control each stage of earth fault protection with three 3-131 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory options: no direction, forward direction and reverse direction. 4. Second harmonic can be selected to block each stage of earth fault protection. 5. Stage 2, 3, 4 of earth fault protection can enable short time delay to improve operation speed. 3.13.2.1 Overview Earth fault protection consists of following three elements: 1. Overcurrent element: each stage equipped with one independent overcurrent element. 2. Directional control element: one direction control element shared by all overcurrent elements, and each overcurrent element can individually select protection direction. 3. Harmonic blocking element: one harmonic blocking element shared by all overcurrent elements and each overcurrent element can individually enable the output signal of harmonic blocking element as a blocking input. 3.13.2.2 Zero-sequence Overcurrent Element The operation criterion for each stage of earth fault protection is: 3I0>[50/51Gi.3I0_Set] Equation 3.13-1 Where: 3I0 is the calculated residual current. [50/51Gi.3I0_Set] is the current setting of stage i of earth fault protection. (i=1, 2, 3, or 4) 3.13.2.3 Direction Control Element Please refer to section 3.11 for details. 3.13.2.4 Harmonic Blocking Element In order to prevent effects of inrush current on earth fault protection, harmonic blocking function can be selected for each stage of earth fault element by configuring logic setting [50/51Gx.En_Hm2_Blk]. When the percentage of second harmonic component to fundamental component of residual current is greater than the setting [50/51G.K_Hm2], harmonic blocking element operates to block stage x of earth fault protection if corresponding logic setting [50/51Gx.En_Hm2_Blk] is enabled. Operation criterion: I0_2nd>[50/51G. K_Hm2]×I0 Equation 3.13-2 Where: is second harmonic of residual current 3-132 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory is fundamental component of residual current. [50/51G.K_Hm2] is harmonic blocking coefficient. If fundamental component of residual current is lower than the minimum operating current (0.1In) then harmonic calculation is not carried out and harmonic blocking element does not operate. 3.13.2.5 Characteristic Curve All 4 stages earth fault protection can be selected as definite-time or inverse-time characteristic, and inverse-time operating time curve is as follows. Equation 3.13-3 Where: Iset is residual current setting [50/51Gi.3I0_Set]. Tp is time multiplier setting [50/51Gi.TMS]. K is a constant C is a constant. α is a constant. 3I0 is the calculated residual current. The user can select the operating characteristic from various inverse-time characteristic curves by setting [50/51Gi.Opt_Curve], and parameters of available characteristics for selection are shown in the following table. Table 3.13-1 Inverse-time curve parameters 50/51Gi.Opt_Curve Time Characteristic α K C DefTime Definite time IECN IEC Normal inverse 0.14 0.02 0 IECV IEC Very inverse 13.5 1.0 0 IECE IEC Extremely inverse 80.0 2.0 0 IECST IEC Short-time inverse 0.05 0.04 0 IECLT IEC Long-time inverse 120.0 1.0 0 ANSIE ANSI Extremely inverse 28.2 2.0 0.1217 ANSIV ANSI Very inverse 19.61 2.0 0.491 ANSI ANSI Inverse 0.0086 0.02 0.0185 ANSIM ANSI Moderately inverse 0.0515 0.02 0.114 ANSILTE ANSI Long-time extremely inverse 64.07 2.0 0.25 ANSILTV ANSI Long-time very inverse 28.55 2.0 0.712 3-133 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 50/51Gi.Opt_Curve K Time Characteristic ANSILT ANSI Long-time inverse UserDefine Programmable User-defined 0.086 α 0.02 C 0.185 If all available curves do not comply with user application, user may set [50/51Gi.Opt_Curve] as “UserDefine” to customize the inverse-time curve characteristic, and constants K, α and C with configuration tool software. (only stage 1) When inverse-time characteristic is selected, if calculated operating time is less than setting [50/51Gi.tmin], then the operating time of the protection changes to the value of setting [50/51Gi.tmin] automatically. Define-time or inverse-time directional earth-fault protection drops off instantaneously after fault current disappears. 3.13.3 Function Block Diagram 50/51Gi 50/51Gi.En1 50/51Gi.On 50/51Gi.En2 50/51Gi.On_ShortDly 50/51Gi.Blk 50/51Gi.St 50/51Gi.En_ShortDly 50/51Gi.Op 50/51Gi.Blk_ShortDly 3.13.4 I/O Signals Table 3.13-2 I/O signals of earth fault protection No. Input Signal 1 50/51Gi.En1 2 50/51Gi.En2 3 50/51Gi.Blk 4 50/51Gi.En_ShortDly 5 50/51Gi.Blk_ShortDly No. Output Signal Description Stage i of earth fault protection enabling input 1, it is triggered from binary input or programmable logic etc. (i=1, 2, 3, 4) Stage i of earth fault protection enabling input 2, it is triggered from binary input or programmable logic etc. (i=1, 2, 3, 4) Stage i of earth fault protection blocking input, it is triggered from binary input or programmable logic etc. (i=1, 2, 3, 4) Short time delay for stage i of earth fault protection enabling input, it is triggered from binary input or programmable logic etc. (i=2, 3, 4) Short time delay for stage i of earth fault protection blocking input, it is triggered from binary input or programmable logic etc. (i=2, 3, 4) Description 1 50/51Gi.On Stage i of earth fault protection is enabled. (i=1, 2, 3, 4) 2 50/51Gi.On_ShortDly Short time delay for stage i of earth fault protection is enabled. (i=2, 3, 4) 3 50/51Gi.St Stage i of earth fault protection starts. (i=1, 2, 3, 4) 4 50/51Gi.Op Stage i of earth fault protection operates. (i=1, 2, 3, 4) 3-134 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.13.5 Logic EN [50/51G1.En] & SIG 50/51G1.En1 & 50/51G1.On SIG 50/51G1.En2 & SIG 50/51G1.Blk SIG FD.Pkp SET 3I0>[50/51G1.3I0_Set] EN [50/51G1.En_Abnor_Blk] >=1 SIG No abnormal conditions & SET [50/51G1.Opt_Dir]=Forward & SIG Forward DIR SET [50/51G1.Opt_Dir]=Reverse & >=1 >=1 & & & 50/51G1.St SIG Reverse DIR SET [50/51G1.Opt_Dir]=Non_Directional & EN [50/51G1.En_VTS_Blk] >=1 SIG VTS.Alm & SIG CTS.Alm & EN [50/51G1.En_CTS_Blk] SIG I3P >=1 2nd Hm Detect & SET [50/51G1.En_Hm2_Blk] & SIG 50/51G1.St Timer t >=1 & 50/51G1.Op [50/51G1.t_Op] 0 SET [50/51G1.Opt_Curve]=DefTime Figure 3.13-1 Logic diagram of stage 1 of earth fault protection 3-135 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory EN [50/51Gi.En_ShortDly] & SIG 50/51Gi.En_ShortDly 50/51Gi.On_ShortDly SIG 50/51Gi.Blk_ShortDly EN [50/51Gi.En] & & SIG 50/51Gi.En1 50/51Gi.On SIG 50/51Gi.En2 & SIG 50/51Gi.Blk SIG FD.Pkp SET 3I0>[50/51Gi.3I0_Set] EN [50/51Gi.En_Abnor_Blk] >=1 SIG No abnormal conditions & SET [50/51Gi.Opt_Dir]=Forward & SIG Forward DIR SET [50/51Gi.Opt_Dir]=Reverse & >=1 >=1 & & & 50/51Gi.St SIG Reverse DIR SET [50/51Gi.Opt_Dir]=Non_Directional EN & [50/51Gi.En_VTS_Blk] >=1 SIG VTS.Alm & SIG CTS.Alm EN & [50/51Gi.En_CTS_Blk] SIG I3P >=1 2nd Hm Detect & SET [50/51Gi.En_Hm2_Blk] & SIG 50/51Gi.St Timer t & >=1 [50/51Gi.t_Op] 0 [50/51Gi.t_ShortDly] 0 50/51Gi.Op SET [50/51Gi.Opt_Curve]=DefTime & SIG 50/51Gi.On_ShortDly Figure 3.13-2 Logic diagram of stage i of earth fault protection 3-136 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory i=2, 3, 4 Abnormal condition 1: when the system is under pole disagreement condition, for 1-pole AR, earth fault protection will operate. If the logic setting [50/51Gx.En_Abnor_Blk] is set as “1”, the stage x of earth fault protection will be blocked. If the logic setting [50/51Gx.En_Abnor_Blk] is set as “0”, earth fault protection is not controlled by direction element. Abnormal condition 2: When manually closing circuit breaker, three phases of the circuit breaker maybe not operate simultaneously, and SOTF protection should operate. If the logic setting [50/51Gx.En_Abnor_Blk] is set as “1”, the stage x of earth fault protection will be blocked. If the logic setting [50/51Gx.En_Abnor_Blk] is set as “0”, earth fault protection is not controlled by direction element. VTS.Alm (VT circuit failure): If the logic setting [50/51Gx.En_VTS_Blk] is set as “1”, the stage x of earth fault protection will be blocked. If the logic setting [50/51Gx.En_VTS_Blk] is set as “0”, earth fault protection is not controlled by direction element. 3.13.6 Settings Table 3.13-3 Settings of earth fault protection No. Name Range Step Unit Remark Setting 1 50/51G.K_Hm2 0.000~1.000 0.001 of second harmonic component for blocking earth fault elements 2 50/51Gi.3I0_Set (0.050~30.000)×In 0.001 A 3 50/51Gi.t_Op 0.000~20.000 0.001 s Current setting for stage i of earth fault protection (i=1, 2, 3, 4) Time delay for stage i of earth fault protection (i=1, 2, 3, 4) Enabling/disabling stage i of earth 4 50/51Gi.En fault protection (i=1, 2, 3, 4) 0 or 1 0: disable 1: enable Enabling/Disabling auto-reclosing blocked when stage i of earth fault 5 50/51Gi.En_BlkAR 0 or 1 protection operates (i=1, 2, 3, 4) 0: disable 1: enable Non_Directional 6 50/51Gi.Opt_Dir Forward Direction option for stage i of earth fault protection (i=1, 2, 3, 4) Reverse Enabling/disabling second harmonic blocking for stage i of 7 50/51Gi.En_Hm2_Blk 0 or 1 earth fault protection (i=1, 2, 3, 4) 0: disable 1: enable 8 50/51Gi.En_Abnor_Blk 0 or 1 Enabling/disabling blocking for 3-137 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory No. Name Range Step Unit Remark stage i of earth fault protection under abnormal conditions (i=1, 2, 3, 4) 0: disable 1: enable Enabling/disabling blocking for stage i of earth fault protection 9 50/51Gi.En_VTS_Blk under VT failure conditions (i=1, 0 or 1 2, 3, 4) 0: disable 1: enable Enabling/disabling blocking for stage i of earth fault protection 10 50/51Gi.En_CTS_Blk under CT failure conditions (i=1, 0 or 1 2, 3, 4) 0: disable 1: enable DefTime IECN IECV IECE IECST IECLT 11 50/51Gi.Opt_Curve Option of characteristic curve for ANSIE stage i of earth fault protection ANSIV (i=1, 2, 3, 4) ANSI ANSIM ANSILTE ANSILTV ANSILT UserDefine Time multiplier setting for stage i 12 50/51Gi.TMS 0.010~200.000 0.001 of inverse-time earth fault protection (i=1, 2, 3, 4) Minimum operating time for stage 13 50/51Gi.tmin 0.050~20.000 0.001 s i of inverse-time earth fault protection (i=1, 2, 3, 4) Constant “α” for stage 1 of 14 50/51G1.Alpha 0.010~5.000 0.001 customized characteristic inverse-time earth fault protection 15 50/51G1.C 0.000~20.000 0.001 3-138 Constant “C” for stage 1 of customized inverse-time PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory No. Name Range Step Unit Remark characteristic earth fault protection Constant “K” for stage 1 of 16 50/51G1.K 0.050~20.000 customized 0.001 characteristic inverse-time earth fault protection 17 50/51Gi.t_ShortDly 0.000~20.000 0.001 s Short time delay for stage i of earth fault protection (i=2, 3, 4) Enabling/disabling short time delay for stage i of earth fault 18 50/51Gi.En_ShortDly 0 or 1 protection (i=2, 3, 4) 0: disable 1: enable 3.14 Negative-sequence Overcurrent Protection 3.14.1 General Application When an asymmetric short-circuit fault happens to the power system or the power system is under asymmetrical three-phase operation, the power system will generate negative-sequence current. Negative-sequence overcurrent will cause generator, motor and other equipments serious damage, so negative-sequence overcurrent protection is used to prevent them. In order to make negative-sequence overcurrent protection own selectivity in multiplex power supply system, negative-sequence overcurrent protection can be controlled by direction control element. 3.14.2 Function Description Negative-sequence overcurrent has following functions: 1. Four-stage negative-sequence overcurrent protection with independent logic, current and time delay settings. 2. Each stage can be selected to block AR by the setting and stage 4 of negative-sequence overcurrent protection can be selected to operate to trip or alarm. 3. All stages can be selected as definite-time or inverse-time characteristic. The inverse-time characteristic is selectable, among IEC and ANSI/IEEE standard inverse-time characteristics, and a user-defined inverse-time curve is available for stage 1 of negative-sequence overcurrent protection. 4. Directional element can be selected to control each stage of negative-sequence overcurrent protection with three options: no direction, forward direction and reverse direction. 5. CT circuit failure can be selected to block each stage of negative-sequence overcurrent protection. 6. Each stage can select independent releasing threshold based on the ratio of negative-sequence current to positive-sequence current to prevent negative-sequence 3-139 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory overcurrent protection from undesired operation for three-phase fault with asymmetrical position exchange of three-phase. 3.14.2.1 Overview Negative-sequence overcurrent protection consists of following three elements: 1. Fault detector: each stage is controlled by the fault detector based on negative-sequence current. Negative-sequence overcurrent protection can operate when the fault detector based on negative-sequence current operate and it is enabled. 2. Overcurrent element: each stage is equipped with one independent overcurrent element. 3. Directional control element: one direction control element is shared by all overcurrent elements, and each overcurrent element can individually select protection direction. 4. Ratio element: each stage is equipped with one independent ratio element (I2/I1), usually the same setting is applied for all stages. 3.14.2.2 Negative-sequence Overcurrent Element The operation criterion for each stage of negative-sequence overcurrent protection is: I2>[50/51Qi.I2_Set] & Equation 3.14-1 I2/I1>[50/51Qi.I2/I1_Set] Where: I2 is the calculated negative-sequence current. I1 is the calculated positive-sequence current. [50/51Qi.I2_Set] is the current setting of stage i of negative-sequence overcurrent protection. (i=1, 2, 3 or 4) 3.14.2.3 Direction Control Element Please refer to section 3.11 for details. 3.14.2.4 Characteristic Curve All 4 stages negative-sequence overcurrent protection can be selected as definite-time or inverse-time characteristic, and inverse-time operating time curve is as follows. Equation 3.14-2 3-140 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Where: Iset is negative-sequence current setting [50/51Qi.I2_Set]. Tp is time multiplier setting [50/51Qi.TMS]. K is a constant C is a constant. α is a constant. I2 is the calculated negative-sequence current. The user can select the operating characteristic from various inverse-time characteristic curves by setting [50/51Qi.Opt_Curve], and parameters of available characteristics for selection are shown in the following table. Table 3.14-1 Inverse-time curve parameters 50/51Qi.Opt_Curve Time Characteristic α K C DefTime Definite time IECN IEC Normal inverse 0.14 0.02 0 IECV IEC Very inverse 13.5 1.0 0 IECE IEC Extremely inverse 80.0 2.0 0 IECST IEC Short-time inverse 0.05 0.04 0 IECLT IEC Long-time inverse 120.0 1.0 0 ANSIE ANSI Extremely inverse 28.2 2.0 0.1217 ANSIV ANSI Very inverse 19.61 2.0 0.491 ANSI ANSI Inverse 0.0086 0.02 0.0185 ANSIM ANSI Moderately inverse 0.0515 0.02 0.114 ANSILTE ANSI Long-time extremely inverse 64.07 2.0 0.25 ANSILTV ANSI Long-time very inverse 28.55 2.0 0.712 ANSILT ANSI Long-time inverse 0.086 0.02 0.185 UserDefine Programmable User-defined If all available curves do not comply with user application, user may set [50/51Qi.Opt_Curve] as “UserDefine” to customize the inverse-time curve characteristic, and constants K, α and C with configuration tool software. (only stage 1) When inverse-time characteristic is selected, if calculated operating time is less than setting [50/51Qi.tmin], then the operating time of the protection changes to the value of setting [50/51Qi.tmin] automatically. Define-time or inverse-time directional negative-sequence overcurrent protection drops off instantaneously after fault current disappears. 3-141 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.14.3 Function Block Diagram 50/51Qi 50/51Gi.En1 50/51Qi.On 50/51Gi.En2 50/51Qi.St 50/51Qi.Blk 50/51Qi.Op 50/51Q4.Alm 3.14.4 I/O Signals Table 3.14-2 I/O signals of negative-sequence overcurrent protection No. Input Signal 1 50/51Qi.En1 2 50/51Qi.En2 3 50/51Qi.Blk No. Output Signal Description Stage i of negative-sequence overcurrent protection enabling input 1, it is triggered from binary input or programmable logic etc. (i=1, 2, 3, 4) Stage i of negative-sequence overcurrent protection enabling input 2, it is triggered from binary input or programmable logic etc. (i=1, 2, 3, 4) Stage i of negative-sequence overcurrent protection blocking input, it is triggered from binary input or programmable logic etc. (i=1, 2, 3, 4) Description 1 50/51Qi.On Stage i of negative-sequence overcurrent protection is enabled. (i=1, 2, 3, 4) 2 50/51Qi.St Stage i of negative-sequence overcurrent protection starts. (i=1, 2, 3, 4) 3 50/51Qi.Op Stage i of negative-sequence overcurrent protection operates. (i=1, 2, 3, 4) 4 50/51Q4.Alm Stage 4 of negative-sequence overcurrent protection operates to alarm. 3-142 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.14.5 Logic EN [50/51Qx.En] SIG 50/51Qx.En1 SIG 50/51Qx.En2 SIG 50/51Qx.Blk SET I2/I1>[50/51Qx.I2/I1_Set] SET I2>[50/51Qx.I2_Set] EN [50/51Qx.En_Abnor_Blk] SIG No abnormal conditions & & 50/51Qx.On & >=1 & SET [50/51Qx.Opt_Dir]=Forward SIG Forward DIR SET [50/51Qx.Opt_Dir]=Reverse SIG Reverse DIR SET [50/51Qx.Opt_Dir]=Non_Directional & & >=1 >=1 & & & 50/51Qx.St Timer t 50/51Qx.Op t & EN [50/51Qx.En_VTS_Blk] SIG VTS.Alm SIG CTS.Alm EN [50/51Qx.En_CTS_Blk] SIG FD.NOC.Pkp >=1 & Figure 3.14-1 Logic diagram of stage i of negative-sequence overcurrent protection i=1, 2, 3 Abnormal condition 1: when the system is under pole disagreement condition, for 1-pole AR, negative-sequence overcurrent protection will operate. If the logic setting [50/51Qx.En_Abnor_Blk] is set as “1”, the stage x of negative-sequence overcurrent protection will be blocked. If the logic setting [50/51Qx.En_Abnor_Blk] is set as “0”, negative-sequence overcurrent protection is not controlled by direction element. Abnormal condition 2: When manually closing circuit breaker, three phases of the circuit breaker maybe not operate simultaneously, and SOTF protection should operate. If the logic setting [50/51Qx.En_Abnor_Blk] is set as “1”, the stage x of negative-sequence overcurrent protection will be blocked. If the logic setting [50/51Qx.En_Abnor_Blk] is set as “0”, negative-sequence 3-143 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory overcurrent protection is not controlled by direction element. VTS.Alm (VT circuit failure): If the logic setting [50/51Qx.En_VTS_Blk] is set as “1”, the stage x of negative-sequence overcurrent protection will be blocked. If the logic setting [50/51Qx.En_VTS_Blk] is set as “0”, negative-sequence overcurrent protection is not controlled by direction element. EN [50/51Q4.En] SIG 50/51Q4.En1 SIG 50/51Q4.En2 SIG 50/51Q4.Blk SET I2/I1>[50/51Q4.I2/I1_Set] SET I2>[50/51Q4.I2_Set] EN [50/51Q4.En_Abnor_Blk] SIG No abnormal conditions & & 50/51Q4.On & >=1 & SET [50/51Q4.Opt_Dir]=Forward SIG Forward DIR SET [50/51Q4.Opt_Dir]=Reverse SIG Reverse DIR SET [50/51Q4.Opt_Dir]=Non_Directional & & >=1 >=1 & & & 50/51Q4.St & EN [50/51Q4.En_VTS_Blk] SIG VTS.Alm SIG CTS.Alm EN [50/51Q4.En_CTS_Blk] SIG FD.NOC.Pkp EN [50/51Q4.En_Trp] >=1 Timer t & 50/51Q4.Alm t & Timer t & 50/51Q4.Op t Figure 3.14-2 Logic diagram of stage 4 of negative-sequence overcurrent protection 3.14.6 Settings Table 3.14-3 Settings of negative-sequence overcurrent protection No. 1 Name 50/51Qi.I2_Set Range Step Unit (0.050~30.000)×In 0.001 A 3-144 Remark Current setting for stage i of negative-sequence overcurrent PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory No. Name Range Step Unit Remark protection (i=1, 2, 3, 4) Ratio coefficient (I2/I1) for stage i of 2 50/51Qi.I2/I1_Set 0.00~1.00 0.01 negative-sequence overcurrent protection (i=1, 2, 3, 4) Time 3 50/51Qi.t_Op 0.000~20.000 0.001 s delay for stage negative-sequence i of overcurrent protection (i=1, 2, 3, 4) Enabling/disabling stage negative-sequence 4 50/51Qi.En 0 or 1 i of overcurrent protection (i=1, 2, 3, 4) 0: disable 1: enable Enabling/Disabling blocked 5 50/51Qi.En_BlkAR when auto-reclosing stage negative-sequence 0 or 1 i of overcurrent protection operates (i=1, 2, 3, 4) 0: disable 1: enable 6 50/51Qi.Opt_Dir Non_Directional Direction option for stage i of Forward negative-sequence Reverse protection (i=1, 2, 3, 4) Enabling/disabling stage 7 50/51Qi.En_Abnor_Blk i of overcurrent 0 or 1 overcurrent blocking for negative-sequence protection under abnormal conditions (i=1, 2, 3, 4) 0: disable 1: enable Enabling/disabling stage 8 50/51Qi.En_VTS_Blk i of blocking for negative-sequence overcurrent protection under VT 0 or 1 failure conditions (i=1, 2, 3, 4) 0: disable 1: enable Enabling/disabling stage 9 50/51Qi.En_CTS_Blk i of blocking for negative-sequence overcurrent protection under CT 0 or 1 failure conditions (i=1, 2, 3, 4) 0: disable 1: enable DefTime 10 50/51Qi.Opt_Curve Option of characteristic curve for IECN stage IECV i of negative-sequence overcurrent protection (i=1, 2, 3, 4) IECE 3-145 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory No. Name Range Step Unit Remark IECST IECLT ANSIE ANSIV ANSI ANSIM ANSILTE ANSILTV ANSILT UserDefine Time multiplier setting for stage i of 11 50/51Qi.TMS 0.010~200.000 0.001 inverse-time negative-sequence overcurrent protection (i=1, 2, 3, 4) Minimum operating time for stage i 12 50/51Qi.tmin 0.050~20.000 0.001 s of inverse-time negative-sequence overcurrent protection (i=1, 2, 3, 4) “α” Constant 13 50/51Q1.Alpha 0.010~5.000 0.001 for stage customized 1 of inverse-time characteristic negative-sequence overcurrent protection Constant 14 50/51Q1.C 0.000~20.000 0.001 “C” for stage customized 1 of inverse-time characteristic negative-sequence overcurrent protection Constant 15 50/51Q1.K 0.050~20.000 0.001 “K” for stage customized characteristic 1 of inverse-time negative-sequence overcurrent protection Enabling/Disabling negative-sequence 16 50/51Q4.En_Trp 0 or 1 stage 4 of overcurrent protection operate to trip or alarm. 0: alarm 1: trip 3.15 Overcurrent Protection for VT Circuit Failure 3.15.1 General Application When protection VT circuit fails, distance protection will be disabled. As a substitute, definite-time or inverse-time phase overcurrent protection and ground overcurrent protection will be enabled automatically, if selected, as backup protection of distance protection. 3.15.2 Function Description Two stages phase overcurrent protection and two stages ground overcurrent protection with 3-146 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory independent logic, current and time delay settings. Stage 2 of phase overcurrent protection and two stages ground overcurrent protection can be selected as definite-time or inverse-time characteristic. The inverse-time characteristic is selectable among IEC and ANSI/IEEE standard inverse-time characteristics, and a user-defined inverse-time curve. Define-time or inverse-time phase overcurrent protection drops off instantaneously after fault current disappears. The inverse-time operating characteristic is as follows. Equation 3.15-1 Where: Iset is current setting [50PVT2.I_Set] or [50GVT2.3I0_Set]. Tp is time multiplier setting [50PVT2.TMS] or [50GVT2.TMS]. α is a constant. K is a constant. C is a constant. I is measured phase current from line CT The user can select the operating characteristic from various inverse-time characteristic curves by setting [50PVT2.Opt_Curve] and [50GVT2.Opt_Curve], and parameters of available characteristics for selection are shown in the following table. Table 3.15-1 Inverse-time curve parameters [50PVT2.Opt_Curve]/[50GVT2.Opt_Curve] Time Characteristic K α C DefTime Definite time IECN IEC Normal inverse 0.14 0.02 0 IECV IEC Very inverse 13.5 1.0 0 IECE IEC Extremely inverse 80.0 2.0 0 IECST IEC Short-time inverse 0.05 0.04 0 IECLT IEC Long-time inverse 120.0 1.0 0 ANSIE ANSI Extremely inverse 28.2 2.0 0.1217 ANSIV ANSI Very inverse 19.61 2.0 0.491 ANSI ANSI Inverse 0.0086 0.02 0.0185 ANSIM ANSI Moderately inverse 0.0515 0.02 0.114 ANSILTE ANSI Long-time extremely inverse 64.07 2.0 0.25 ANSILTV ANSI Long-time very inverse 28.55 2.0 0.712 ANSILT ANSI Long-time inverse 0.086 0.02 0.185 UserDefine Programmable user-defined If all available curves do not comply with user application, user may set [50PVT2.Opt_Curve] and 3-147 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory [50GVT2.Opt_Curve] as “UserDefine” to customize the inverse-time curve characteristic with constants α, K and C. When inverse-time characteristic is selected, if calculated operating time is less than setting [50PVT2.tmin] or [50GVT2.tmin], then the operating time of the protection changes to the value of setting [50PVT2.tmin] or [50GVT2.tmin] automatically. 3.15.3 Function Block Diagram 50PVTi/50GVTi 50PVTi.En1 50PVTi.On 50PVTi.En2 50PVTi.Op 50PVTi.Blk 50PVTi.St 50GVTi.En1 50PVTi.StA 50GVTi.En2 50PVTi.StB 50GVTi.Blk 50PVTi.StC 50GVTi.On 50GVTi.Op 50GVTi.St 3.15.4 I/O Signals Table 3.15-2 I/O signals of overcurrent protection for VT circuit failure No. Input Signal 1 50PVTi.En1 2 50PVTi.En2 3 50PVTi.Blk 4 50GVTi.En1 5 50GVTi.En2 6 50GVTi.Blk No. Output Signal Description Stage i of phase overcurrent protection for VT circuit failure enabling input 1, it is triggered from binary input or programmable logic etc. (i=1, 2) Stage i of phase overcurrent protection for VT circuit failure enabling input 2, it is triggered from binary input or programmable logic etc. (i=1, 2) Stage i of phase overcurrent protection for VT circuit failure blocking input, it is triggered from binary input or programmable logic etc. (i=1, 2) Stage i of ground overcurrent protection for VT circuit failure enabling input 1, it is triggered from binary input or programmable logic etc. (i=1, 2) Stage i of ground overcurrent protection for VT circuit failure enabling input 2, it is triggered from binary input or programmable logic etc. (i=1, 2) Stage i of ground overcurrent protection for VT circuit failure blocking input, it is triggered from binary input or programmable logic etc. (i=1, 2) Description 1 50PVTi.On Stage i of phase overcurrent protection for VT circuit failure is enabled. (i=1, 2) 2 50PVTi.Op Stage i of phase overcurrent protection for VT circuit failure operates. (i=1, 2) 3 50PVTi.St Stage i of phase overcurrent protection for VT circuit failure starts. (i=1, 2) 3-148 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Stage i of phase overcurrent protection for VT circuit failure starts (A-Phase). (i=1, 4 50PVTi.StA 5 50PVTi.StB 6 50PVTi.StC 7 50GVTi.On Stage i of ground overcurrent protection for VT circuit failure is enabled. (i=1, 2) 8 50GVTi.Op Stage i of ground overcurrent protection for VT circuit failure operates. (i=1, 2) 9 50GVTi.St Stage i of ground overcurrent protection for VT circuit failure starts. (i=1, 2) 2) Stage i of phase overcurrent protection for VT circuit failure starts (B-Phase). (i=1, 2) Stage i of phase overcurrent protection for VT circuit failure starts (C-Phase). (i=1, 2) 3.15.5 Logic SIG 50PVTx.En1 & SIG 50PVTx.En2 EN & 50PVTx.On [50PVTx.En] >=1 & SIG 50PVTx.Blk 50PVTx.St & SIG FD.Pkp & SIG VTS.Alm 50PVTx.StA SET Ia>[50PVTx.I_Set] & 50PVTx.StB SET Ib>[50PVTx.I_Set] & 50PVTx.StC SET Ic>[50PVTx.I_Set] SIG 50PVT1.St [50PVT1.t_Op] SIG 50PVT2.St 0ms & 50PVT1.Op Timer t >=1 & 50PVT2.Op [50PVT2.t_Op] 0 SET [50PVT2.Opt_Curve]=DefTime 3-149 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory SIG 50GVTx.En1 & SIG 50GVTx.En2 EN & 50GVTx.On [50GVTx.En] & SIG 50GVTx.Blk SIG FD.Pkp & SET 3I0>[50GVTx.3I0_Set] 50GVTx.St SIG FD.ROC.Pkp & SIG VTS.Alm [50GVT1.t_Op] SIG 50GVT1.St & SIG 50GVT2.St 0ms 50GVT1.Op Timer t >=1 & 50GVT2.Op [50GVT2.t_Op] 0 SET [50GVT2.Opt_Curve]=DefTime Figure 3.15-1 Logic diagram of overcurrent protection for VT circuit failure 3.15.6 Settings Table 3.15-3 Settings of overcurrent protection for VT circuit failure No. Name Range Step Unit Remark Current setting for stage i of phase 1 50PVTi.I_Set (0.050~30.000)×In 0.001 A overcurrent protection when VT circuit failure (i=1, 2) Time delay for stage i of phase 2 50PVTi.t_Op 0.000~10.000 0.001 s overcurrent protection when VT circuit failure (i=1, 2) Enabling/disabling stage i of phase overcurrent protection when VT 3 50PVTi.En 0 or 1 circuit failure (i=1, 2) 0: disable 1: enable DefTime IECN Option of inverse-time characteristic IECV 4 50PVT2.Opt_Curve curve IECE for stage 2 of phase overcurrent protection when VT IECST circuit failure IECLT ANSIE 3-150 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory No. Name Range Step Unit Remark ANSIV ANSI ANSIM ANSILTE ANSILTV ANSILT Time multiplier setting for stage 2 5 50PVT2.TMS 0.010~200.000 0.001 of phase overcurrent protection when VT circuit failure Minimum operating time for stage 2 6 50PVT2.tmin 0.000~20.000 0.001 s of phase overcurrent protection when VT circuit failure Constant 7 50PVT2.Alpha 0.010~5.000 “α” for stage customized 0.001 2 of inverse-time characteristic phase overcurrent protection when VT circuit failure Constant 8 50PVT2.C 0.000~20.000 “C” for stage customized 0.001 2 of inverse-time characteristic phase overcurrent protection when VT circuit failure Constant 9 50PVT2.K 0.050~20.000 “K” for stage customized 0.001 2 of inverse-time characteristic phase overcurrent protection when VT circuit failure Current setting for stage i of ground 10 50GVTi.3I0_Set (0.050~30.000)×In 0.001 A overcurrent protection when VT circuit failure (i=1, 2) Time delay for stage i of ground 11 50GVTi.t_Op 0.000~10.000 0.001 s overcurrent protection when VT circuit failure (i=1, 2) Enabling/disabling stage i of ground overcurrent protection when VT 12 50GVTi.En 0 or 1 circuit failure (i=1, 2) 0: disable 1: enable DefTime IECN 13 50GVT2.Opt_Curve IECV Option of inverse-time characteristic IECE curve IECST overcurrent protection when VT IECLT circuit failure for stage 2 of ground ANSIE ANSIV 3-151 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory No. Name Range Step Unit Remark ANSI ANSIM ANSILTE ANSILTV ANSILT Time multiplier setting for stage 2 of 14 50GVT2.TMS 0.010~200.000 0.001 ground overcurrent protection when VT circuit failure Minimum operating time for stage 2 15 50GVT2.tmin 0.000~20.000 0.001 s of ground overcurrent protection when VT circuit failure Constant 16 50GVT2.Alpha 0.010~5.000 0.001 “α” for customized stage 2 of inverse-time characteristic ground overcurrent protection when VT circuit failure Constant 17 50GVT2.C 0.000~20.000 0.001 “C” for customized stage 2 of inverse-time characteristic ground overcurrent protection when VT circuit failure Constant 18 50GVT2.K 0.050~20.000 0.001 customized “K” for stage 2 of inverse-time characteristic ground overcurrent protection when VT circuit failure 3.16 Phase Current SOTF Protection 3.16.1 General Application When the circuit breaker is closed manually or automatically, it is possible to switch on to an existing fault. This is especially critical if the line in the remote station is grounded, since earth fault protection would not clear the fault until their time delays had elapsed. In this situation, however, the fastest possible clearance is desired. For application on line-transformer unit, second harmonic also can be selected to block phase overcurrent protection to avoid the effect of inrush current on the protection. With phase current SOTF protection, a fast trip is achieved for a fault on the line when the line is being energized. It shall be responsive to all types of earth faults anywhere within the protected line, and it shall be enabled for the setting [SOTF.t_En] when the circuit is energized either manually or via an auto-reclosing system. 3.16.2 Function Description Phase current SOTF protection will operate to trip three-phase circuit breaker with a time delay of [50PSOTF.t_Op] when auto-reclosing or closing manually. Second harmonic can be selected to block phase overcurrent SOTF protection. When phase 3-152 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory overcurrent SOTF protection is used to protect line-transformer unit, harmonic blocking function can be selected by configuring logic setting [50PSOTF.En_Hm2_Blk] to prevent maloperation due to inrush current. When the percentage of second harmonic component to fundamental component of any phase current is greater than the setting [50/51P.K_Hm2], harmonic blocking element operates to block phase overcurrent SOTF element if corresponding logic setting [50PSOTF.En_Hm2_Blk] enabled. Operation criterion: IP_2nd=[50/51P.K_Hm2]×IP Equation 3.16-1 Where: IP_2nd is second harmonic of phase current IP is fundamental component of phase current. [50/51P.K_Hm2] is harmonic blocking coefficient. If fundamental component of any phase current is lower than the minimum operating current (0.1In), then harmonic calculation is not carried out and harmonic blocking element does not operate. 3.16.3 Function Block Diagram 50PSOTF 50PSOTF.En1 50PSOTF.On 50PSOTF.En2 50PSOTF.Op 50PSOTF.Blk 50PSOTF.St 3.16.4 I/O Signals Table 3.16-1 I/O signals of residual SOTF protection No. Input Signal 1 50PSOTF.En1 2 50PSOTF.En2 3 50PSOTF.Blk No. Description Phase current SOTF protection enabling input 1, it is triggered from binary input or programmable logic etc. Phase current SOTF protection enabling input 2, it is triggered from binary input or programmable logic etc. Phase current SOTF protection blocking input, it is triggered from binary input or programmable logic etc. Output Signal Description 1 50PSOTF.On Phase current SOTF protection is enabled. 2 50PSOTF.Op Phase current SOTF protection operates. 3-153 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3 50PSOTF.St Phase current SOTF protection starts. 3.16.5 Logic SIG I3P 2nd Hm Detect & SET [50PSOTF.En_Hm2_Blk] SIG 3-pole reclosing signal & >=1 SIG 1-pole reclosing signal SIG Manual closing signal SET Ia>[50PSOTF.I_Set] >=1 SET Ib>[50PSOTF.I_Set] SET Ic>[50PSOTF.I_Set] SET Ua<[50PSOTF.Up_Set] >=1 SET Ub<[50PSOTF.Up_Set] & SET Uc<[50PSOTF.Up_Set] EN [50PSOTF.En_Up_UV] SET Uab<[50PSOTF.Upp_Set] >=1 SET Ubc<[50PSOTF.Upp_Set] >=1 & >=1 & >=1 SET Uca<[50PSOTF.Upp_Set] EN [50PSOTF.En_Upp_UV] SET U2>[50PSOTF.U2_Set] EN [50PSOTF.En_U2_OV] SET 3U0>[50PSOTF.3U0_Set] EN & & [50PSOTF.En_3U0_OV] >=1 >=1 EN [50PSOTF.En_Up_UV] EN [50PSOTF.En_Upp_UV] & [50PSOTF.t_Op] SIG FD.Pkp SIG 50PSOTF.En1 50PSOTF.St 0ms 50PSOTF.Op & SIG 50PSOTF.En2 SIG 50PSOTF.Blk EN & 50PSOTF.On [50PSOTF.En] Figure 3.16-1 Logic diagram of phase current SOTF protection 3-154 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.16.6 Settings Table 3.16-2 Settings of phase current SOTF protection No. Name Range Step Unit 1 50PSOTF.I_Set (0.050~30.000)×In 0.001 A 2 50PSOTF.t_Op 0.000~10.000 0.001 s Remark Current setting of phase current SOTF protection Time delay for phase current SOTF protection Enabling/disabling 3 50PSOTF.En phase current SOTF protection 0 or 1 0: disable 1: enable Enabling/disabling second harmonic blocking for phase 4 50PSOTF.En_Hm2_Blk 0 or 1 overcurrent SOTF protection 0: disable 1: enable 5 50PSOTF.Up_Set (0~1) ×Un 0.001 V 6 50PSOTF.Upp_Set (0~1) ×Un 0.001 V Voltage setting 50PSOTF.U2_Set (0~1) ×Un 0.001 V phase Voltage setting for phase-phase undervoltage supervision logic Voltage 7 for undervoltage supervision logic setting for negative-sequence overvoltage supervision logic Voltage 8 50PSOTF.3U0_Set (0~1) ×Un 0.001 V setting zero-sequence for overvoltage supervision logic Enabling/disabling phase undervoltage supervision logic 9 50PSOTF.En_Up_UV for 0 or 1 phase current SOTF protection 0: disable 1: enable Enabling/disabling phase-phase undervoltage supervision logic 10 50PSOTF.En_Upp_UV for 0 or 1 phase current SOTF protection 0: disable 1: enable Enabling/disabling negative-sequence overvoltage 11 50PSOTF.En_U2_OV 0 or 1 supervision logic for phase current SOTF protection 0: disable 3-155 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory No. Name Range Step Unit Remark 1: enable Enabling/disabling 12 50PSOTF.En_3U0_OV 0 or 1 zero-sequence overvoltage supervision for logic phase current SOTF protection 0: disable 1: enable 3.17 Residual Current SOTF Protection 3.17.1 General Application When the circuit breaker is closed manually or automatically, it is possible to switch on to an existing fault. This is especially critical if the line in the remote station is grounded, since earth fault protection would not clear the fault until their time delays had elapsed. In this situation, however, the fastest possible clearance is desired. For application on line-transformer unit, second harmonic also can be selected to block earth fault protection to avoid the effect of inrush current on the protection. Residual current SOTF (switch onto fault) protection is a complementary function to earth fault protection. With residual current SOTF protection, a fast trip is achieved for a fault on the line, when the line is being energized. It shall be responsive to all types of earth faults anywhere within the protected line, and it shall be enabled for the setting [SOTF.t_En] when the circuit is energized either manually or via an auto-reclosing system. 3.17.2 Function Description Residual current SOTF protection will operate to trip three-phase circuit breaker with a time delay of [50GSOTF.t_Op_1P] when 1-pole auto-reclosing. Residual current SOTF protection will operate to trip three-phase circuit breaker with a time delay of [50GSOTF.t_Op_3P] when 3-pole auto-reclosing or closing manually. Second harmonic can be selected to block residual current SOTF protection. When residual current SOTF protection is used to protect line-transformer unit, harmonic blocking function can be selected by configuring logic setting [50GSOTF.En_Hm2_Blk] to prevent maloperation due to inrush current. When the percentage of second harmonic component to fundamental component of residual current is greater than the setting [50/51G.K_Hm2], harmonic blocking element operates to block residual overcurrent SOTF element if corresponding logic setting [50GSOTF.En_Hm2_Blk] enabled. Operation criterion: I0_2nd=[50/51G.K_Hm2]×I0 Equation 3.17-1 3-156 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Where: I0_2nd is second harmonic of residual current I0 is fundamental component of residual current. [50/51G.K_Hm2] is harmonic blocking coefficient. If fundamental component of residual current is lower than the minimum operating current (0.1In) then harmonic calculation is not carried out and harmonic blocking element does not operate. 3.17.3 Function Block Diagram 50GSOTF 50GSOTF.En1 50GSOTF.On 50GSOTF.En2 50GSOTF.Op 50GSOTF.Blk 50GSOTF.St 3.17.4 I/O Signals Table 3.17-1 I/O signals of residual SOTF protection No. Input Signal 1 50GSOTF.En1 2 50GSOTF.En2 3 50GSOTF.Blk No. Description Residual current SOTF protection enabling input 1, it is triggered from binary input or programmable logic etc. Residual current SOTF protection enabling input 2, it is triggered from binary input or programmable logic etc. Residual current SOTF protection blocking input, it is triggered from binary input or programmable logic etc. Output Signal Description 1 50GSOTF.On Residual current SOTF protection is enabled. 2 50GSOTF.Op Residual current SOTF protection operates. 3 50GSOTF.St Residual current SOTF protection starts. 3-157 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.17.5 Logic SIG I3P 2nd Hm Detect & SET [50/51G1.En_Hm2_Blk] SIG 3-pole AR signal >=1 & [50GSOTF.t_Op_3P] SIG Manual closing signal SET 3I0>[50GSOTF.3I0_Set] & >=1 50GSOTF.Op & SIG FD.ROC.Pkp [50GSOTF.t_Op_1P] SIG 1-pole AR signal 0ms >=1 SIG 50GSOTF.En1 50GSOTF.St & SIG 50GSOTF.En2 & 50GSOTF.On SIG 50GSOTF.Blk EN 0ms [50GSOTF.En] Figure 3.17-1 Logic diagram of residual current SOTF protection 3.17.6 Settings Table 3.17-2 Settings of residual current SOTF protection No. 1 Name 50GSOTF.3I0_Set Range Step Unit (0.050~30.000)×In 0.001 A Remark Current setting of residual current SOTF protection Time delay for residual current 2 50GSOTF.t_Op_3P 0.000~10.000 0.001 s SOTF protection when 3 pole closed Time delay for residual current 3 50GSOTF.t_Op_1P 0.000~10.000 0.001 s SOTF protection when 1 pole closed Enabling/disabling 4 50GSOTF.En residual current SOTF protection 0 or 1 0: disable 1: enable Enabling/disabling current 5 50GSOTF.En_Hm2_Blk 0 or 1 SOTF residual protection blocked by harmonic 0: disable 1: enable 3.18 Voltage Protection Voltage protection has the function of protecting device against undervoltage and overvoltage. Both operational states are unfavorable as overvoltage may cause insulation breakdown while undervoltage may cause stability problem. Each voltage protection function has three individual 3-158 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory stages with respective time delay, but only one stage negative-sequence overvoltage protection is available. These voltage protection functions can be switched on or off separately. Selectable definite-time characteristic and multiple inverse-time characteristics are available. 3.18.1 Overvoltage Protection 3.18.1.1 General Application Abnormal high voltages often occur e.g. in low loaded, long distance transmission lines, in islanded systems when generator voltage regulation fails, or load rejection of a generator. Even if compensation reactors are provided to avoid line overvoltage by compensation of the line capacitance and thus reduction of the overvoltage, the overvoltage will endanger the insulation if the reactors fail. The line must be de-energized within a very short time. The overvoltage protection in this device detects the phase voltages Ua, Ub and Uc or the phase-to-phase voltages Uab, Ubc and Uca with an option of any phase or all phases operation for output. The overvoltage protection can be used for tripping purpose as well as to initiate transfer trip, which selectable controlled by local circuit breaker. 3.18.1.2 Function Description Phase overvoltage protection has following functions: 1. Three stages phase overvoltage protection with independent logic, voltage and time delay settings. 2. Overvoltage protection can be selected as definite-time or inverse-time characteristic. The inverse-time characteristic is selectable, among IEC and ANSI/IEEE standard inverse-time characteristics. 3. Phase voltage or phase-to-phase voltage can be selected for protection calculation. 4. “1-out-of-3” or “3-out-of-3” logic can be selected for protection criterion. (1-out-of-3 means any of three phase voltages, 3-out-of-3 means all three phase voltages) 1. Operation Criterion Users can select phase voltage or phase-to-phase voltage for the protection calculation. If setting [59Pi.Opt_Up/Upp] is set to “0”, phase voltage criterion is selected and if [59Pi.Opt_Up/Upp] is set to “1”, phase-to-phase voltage criterion is selected. When phase voltage or phase-to-phase voltage is greater than any enabled stage voltage setting, the stage protection picks up and operates after delay, which will drop off instantaneously when fault voltage disappears. Phase voltage criterion Two operation criteria of definite-time overvoltage protection are shown as follows, which of them is applied depending on the logic setting [59Pi.Opt_1P/3P]. UΦ_max>[ 59Pi.U_Set] Equation 3.18-1 3-159 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory or Ua>[59Pi.U_Set] & Ub>[59Pi.U_Set] & Uc>[59Pi.U_Set] Equation 3.18-2 Where: UΦ_max is the maximum value among three phase-voltage. Ua, Ub, Uc are three phase voltages. [59Pi.U_Set] is the setting of stage i of overvoltage protection. (i=1, 2, 3) When [59Pi.Opt_1P/3P] is set as “1”, “1-out-of-3” logic (Equation 3.18-1) is selected as operation criterion, and when set as “0”, “3-out-of-3” logic (Equation 3.18-2) is selected. Phase-to-phase voltage criterion Two operation criteria of definite-time overvoltage protection are shown as follows, which of them is applied depending on the logic setting [59Pi.Opt_1P/3P]. UΦΦ_max>[ 59Pi.U_Set] Equation 3.18-3 or Uab>[59Pi.U_Set] & Ubc>[59Pi.U_Set] & Uca>[59Pi.U_Set] Equation 3.18-4 [59Pi.U_Set] is the setting of stage i of overvoltage protection. When [59Pi.Opt_1P/3P] is set as “1”, “1-out-of-3” logic (Equation 3.18-3) is selected as operation criterion, and when set as “0”, “3-out-of-3” logic (Equation 3.18-4) is selected. 2. Characteristic Curve Phase overvoltage protection can be selected as definite-time or inverse-time characteristic, and inverse-time operating time curve is as follows. Equation 3.18-5 Where: Uset is the voltage setting [59Pi.U_Set]. Tp is time multiplier setting [59Pi.TMS]. K is a constant. C is a constant. α is a constant. 3-160 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory U is the measured voltage Operating characteristic of overvoltage protection, can be chosen from definite-time characteristic and 12 inverse-time characteristics by setting the logic setting [59Pi.Opt_Curve]. The parameters of each characteristic are listed in the following table. Table 3.18-1 Inverse-time curve parameters 59Pi.Opt_Curve α K Time Characteristic C DefTime Definite time IECN IEC Normal inverse 0.14 0.02 0 IECV IEC Very inverse 13.5 1.0 0 IECE IEC Extremely inverse 80.0 2.0 0 IECST IEC Short-time inverse 0.05 0.04 0 IECLT IEC Long-time inverse 120.0 1.0 0 ANSIE ANSI Extremely inverse 28.2 2.0 0.1217 ANSIV ANSI Very inverse 19.61 2.0 0.491 ANSI ANSI Inverse 0.0086 0.02 0.0185 ANSIM ANSI Moderately inverse 0.0515 0.02 0.114 ANSILTE ANSI Long-time extremely inverse 64.07 2.0 0.25 ANSILTV ANSI Long-time very inverse 28.55 2.0 0.712 ANSILT ANSI Long-time inverse 0.086 0.02 0.185 When inverse-time characteristic is selected, if calculated operating time is less than setting [59Pi.tmin], then the operating time changes to the value of setting [59Pi.tmin] automatically. Define-time or inverse-time phase overvoltage protection drops off instantaneously when measured voltage is lower than reset voltage. 3.18.1.3 Function Block Diagram 59Pi 59Pi.En1 59Pi.On 59Pi.En2 59Pi.St 59Pi.Blk 59Pi.St1 59Pi.St2 59Pi.St3 59Pi.Op 59Pi.Alm 59Pi.Op_InitTT 3-161 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.18.1.4 I/O Signals Table 3.18-2 I/O signals of overvoltage protection No. Input Signal 1 59Pi.En1 2 59Pi.En2 3 59Pi.Blk No. Output Signal Description Stage i of overvoltage protection enabling input 1, it is triggered from binary input or programmable logic etc. (i=1, 2, 3) Stage i of overvoltage protection enabling input 2, it is triggered from binary input or programmable logic etc. (i=1, 2, 3) Stage i of overvoltage protection blocking input, it is triggered from binary input or programmable logic etc. (i=1, 2, 3) Description 1 59Pi.On Stage i of overvoltage protection is enabled. (i=1, 2, 3) 2 59Pi.Op Stage i of overvoltage protection operates. (i=1, 2, 3) 3 59Pi.St Stage i of overvoltage protection starts. (i=1, 2, 3) 4 59Pi.St1 Stage i of overvoltage protection starts (A or AB). (i=1, 2, 3) 5 59Pi.St2 Stage i of overvoltage protection starts (B or BC). (i=1, 2, 3) 6 59Pi.St3 Stage i of overvoltage protection starts (C or CA). (i=1, 2, 3) 7 59Pi.Op_InitTT Stage i of overvoltage protection operates to initiate transfer trip. (i=1, 2, 3) 8 59Pi.Alm Stage i of overvoltage protection alarms. (i=1, 2, 3) 3-162 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.18.1.5 Logic EN [59Pi.En] & SIG 59Pi.En1 & 59Pi.On SIG 59Pi.En2 SIG 59Pi.Blk SIG 52b_PhA & SIG 52b_PhB & & >=1 SIG 52b_PhC EN [59Pi.En_52b_TT] EN [59Pi.En_TT] EN [59Pi.Opt_1P/3P] SIG FD.Pkp 59Pi.Op_InitTT & & SIG 59Pi.On EN [59Pi.Opt_Up/Upp] & & >=1 Timer t & t SET UA>[59Pi.U_Set] & & SET UAB>[59Pi.U_Set] & & >=1 Timer t t SET UB>[59Pi.U_Set] & SET UBC>[59Pi.U_Set] >=1 & & >=1 SET UC>[59Pi.U_Set] Timer t t & 59Pi.St1 59Pi.Op 59Pi.St3 [59Pi.En_Alm] SIG 59Pi.St1 & 59Pi.St2 SET UCA>[59Pi.U_Set] EN >=1 & & 59Pi.Alm >=1 SIG 59Pi.St2 59Pi.St SIG 59Pi.St3 Figure 3.18-1 Logic diagram of stage i of overvoltage protection Where: i=1, 2, 3 52b_PhA, 52b_PhB and 52b_PhC: Please refer to section 3.4. 3-163 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.18.1.6 Settings Table 3.18-3 Settings of overvoltage protection No. Name Range Step Unit 1 59Pi.U_Set Un~2Unn 0.001 V 2 59Pi.t_Op 0.000~30.000 0.001 s Remark Voltage setting for stage i of overvoltage protection (i=1, 2, 3) Time delay for stage i of overvoltage protection (i=1, 2, 3) Enabling/disabling stage i of overvoltage 3 59Pi.En protection (i=1, 2, 3) 0 or 1 0: disable 1: enable Option of 1-out-of-3 mode or 3-out-of-3 mode for stage i of overvoltage protection 4 59Pi.Opt_1P/3P 0 or 1 (i=1, 2, 3) 0: 3-out-of-3 mode 1: 1-out-of-3 mode Option of phase-to-phase voltage or phase voltage for stage i of overvoltage protection 5 59Pi.Opt_Up/Upp 0 or 1 (i=1, 2, 3) 0: phase voltage 1: phase-to-phase voltage Enabling/disabling stage i of overvoltage 6 59Pi.En_Alm protection for alarm purpose (i=1, 2, 3) 0 or 1 0: disable 1: enable Enabling/disabling transfer trip controlled by CB open position for stage i of 7 59Pi.En_52b_TT 0 or 1 overvoltage protection (i=1, 2, 3) 0: disable 1: enable Enabling/disabling stage i of overvoltage protection operate to initiate transfer trip 8 59Pi.En_TT 0 or 1 (i=1, 2, 3) 0: disable 1: enable DefTime IECN IECV 9 59Pi.Opt_Curve IECE Option of characteristic curve for stage i of IECST overvoltage protection (i=1, 2, 3) IECLT ANSIE ANSIV 3-164 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory No. Name Range Step Unit Remark ANSI ANSIM ANSILTE ANSILTV ANSILT Time multiplier setting for stage i of 10 59Pi.TMS 0.010~200.000 0.001 inverse-time overvoltage protection (i=1, 2, 3) 11 59Pi.tmin 0.050~20.000 0.001 Minimum delay for stage i of inverse-time s overvoltage protection (i=1, 2, 3) 3.18.2 Negative-sequence Overvoltage Protection 3.18.2.1 General Application On a healthy three-phase power system, negative-sequence voltage is nominally zero. However, when an unbalance situation occurs on the primary system, the negative-sequence voltage is produced. The device provides a one-stage negative-sequence overvoltage protection with definite time delay characteristic. 3.18.2.2 Function Block Diagram 59Q 59Q.En1 59Q.On 59Q.En2 59Q.Op 59Q.Blk 59Q.St 3.18.2.3 I/O Signals Table 3.18-4 I/O signals of negative-sequence overvoltage protection No. Input Signal 1 59Q.En1 2 59Q.En2 3 59Q.Blk No. Description Negative-sequence overvoltage protection enabling input 1, it is triggered from binary input or programmable logic etc. Negative-sequence overvoltage protection enabling input 2, it is triggered from binary input or programmable logic etc. Negative-sequence overvoltage protection blocking input, it is triggered from binary input or programmable logic etc. Output Signal Description 1 59Q.On Negative-sequence overvoltage protection is enabled. 2 59Q.Op Negative-sequence overvoltage protection operates. 3 59Q.St Negative-sequence overvoltage protection starts. 3-165 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.18.2.4 Logic SIG 59Q.En1 SIG 59Q.En2 EN [59Q.En] SIG 59Q.Blk & & 59Q.On [59Q.t_Op] 59Q.Op & 59Q.St SET U2>[59Q.U_Set] Figure 3.18-2 Logic diagram of negative-sequence overvoltage protection 3.18.2.5 Settings Table 3.18-5 Settings of negative-sequence overvoltage protection No. Name Range Step Unit 1 59Q.U_Set 0~Un 0.001 V 2 59Q.t_Op 0.000~30.000 0.001 s Remark Voltage setting for negative-sequence overvoltage protection Time delay for overvoltage protection Enabling/disabling 3 59Q.En negative-sequence negative-sequence overvoltage protection 0 or 1 0: disable 1: enable 3.18.3 Residual Overvoltage Protection 3.18.3.1 General Application A single phase earth fault occurrence in ungrounded system or Peterson coil grounded system will result in residual overvoltage, so residual overvoltage protection is equipped to prevent protected equipment being damaged by residual overvoltage in this condition. 3.18.3.2 Function Description Residual overvoltage protection has following functions 1. Three-stage residual overvoltage protection with independent logic, voltage and time delay settings. 2. Stage 1 is definite-time characteristic, stage 2 and 3 can be selected as definite-time or inverse-time characteristic, only stage 3 can be defined for trip purpose or alarm purpose. The inverse-time characteristic is selectable among IEC and ANSI/IEEE standard inverse-time characteristics and a user-defined inverse-time curve. 3. Define-time or inverse-time residual overvoltage protection drops off instantaneously. 3-166 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 1. Operation Criterion 3U0> [59Gi.3U0_Set] Equation 3.18-6 Where: 3U0 is calculated residual voltage. [59Gi.3U0_Set] is the voltage setting of stage i of residual overvoltage protection. (i=1, 2 or 3) If residual voltage is greater than the setting of any stage enabled residual overvoltage protection, the stage residual overvoltage protection will operate after time delay and the stage protection will drop off instantaneously after fault voltage disappears. 2. Time Curve Stage 1 of residual overvoltage protection is definite-time characteristic and can perform instantaneous operation with the corresponding time delay being set as “0”. Stage 2 and 3 can be selected as definite-time or inverse-time characteristic, and inverse-time operating time curve is as follows. Equation 3.18-7 Where: Uset is residual voltage setting [59Gi.3U0_Set]. Tp is time setting [59Gi.TMS]. K and C are constants. α is a constant. U is actual measured residual voltage. The user can select the operating characteristic from various inverse-time characteristic curves by setting [59Gi.Opt_Curve], and parameters of available characteristics for selection are shown in the following table. Table 3.18-6 Inverse-time curve parameters of residual overvoltage protection 59Gi.Opt_Curve (i=2 or 3) α K Time Characteristic C DefTime Definite time IECN IEC Normal inverse 0.14 0.02 0 IECV IEC Very inverse 13.5 1.0 0 IECE IEC Extremely inverse 80.0 2.0 0 IECST IEC Short-time inverse 0.05 0.04 0 IECLT IEC Long-time inverse 120.0 1.0 0 3-167 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 59Gi.Opt_Curve (i=2 or 3) α K Time Characteristic C ANSIE ANSI Extremely inverse 28.2 2.0 0.1217 ANSIV ANSI Very inverse 19.61 2.0 0.491 ANSI ANSI Inverse 0.0086 0.02 0.0185 ANSIM ANSI Moderately inverse 0.0515 0.02 0.114 ANSILTE ANSI Long-time extremely inverse 64.07 2.0 0.25 ANSILTV ANSI Long-time very inverse 28.55 2.0 0.712 ANSILT ANSI Long-time inverse 0.086 0.02 0.185 UserDefine Programmable user-defined If all available curves do not comply with user application, user may configure setting [59Gi.Opt_Curve] to “UserDefine” to customize the inverse-time curve characteristic, and constants K, α and C. 3.18.3.3 Function Block Diagram 59Gi 59Gi.En1 59Gi.On 59Gi.En2 59Gi.St 59Gi.Blk 59Gi.Op 59G3.Alm 3.18.3.4 I/O Signals Table 3.18-7 I/O signals of residual overvoltage protection No. Signal 1 59Gi.En1 2 59Gi.En2 3 59Gi.Blk No. Signal Description Stage i of residual overvoltage protection enabling input 1, it is triggered from binary input or programmable logic etc. (i=1, 2, 3) Stage i of residual overvoltage protection enabling input 2, it is triggered from binary input or programmable logic etc. (i=1, 2, 3) Stage i of overvoltage protection blocking input, it is triggered from binary input or programmable logic etc. (i=1, 2, 3) Description 1 59Gi.On Stage i of residual overvoltage protection is enabled. (i=1, 2, 3) 2 59Gi.Op Stage i of residual overvoltage protection operates. (i=1, 2, 3) 3 59Gi.St Stage i of residual overvoltage protection start. (i=1, 2, 3) 4 59G3.Alm Stage 3 of residual overvoltage protection operates to alarm. 3-168 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.18.3.5 Logic EN [59G1.En] SIG 59G1.En1 SIG 59G1.En2 SIG 59G1.Blk SET 3U0>[59G1.3U0_Set] & & 59G1.On 59G1.St & [59G1.t_Op] 0 59G1.Op Figure 3.18-3 Logic diagram of stage 1 of residual overvoltage protection EN [59G2.En] SIG 59G2.En1 SIG 59G2.En2 SIG 59G2.Blk SET 3U0>[59G2.3U0_Set] & & 59G2.On & 59G2.St Timer t & t >=1 59G2.Op & [59G2.t_Op] SET 0 [59G2.Opt_Curve]=DefTime Figure 3.18-4 Logic diagram of stage 2 of residual overvoltage protection EN [59G3.En] SIG 59G3.En1 SIG 59G3.En2 SIG 59G3.Blk SET 3U0>[59G3.3U0_Set] & & 59G3.On & 59G3.St & Timer t t >=1 & [59G3.t_Op] SET [59G3.Opt_Curve]=DefTime EN [59G3.En_Trp] 0 & 59G3.Op & 59G3.Alm Figure 3.18-5 Logic diagram of stage 3 of residual overvoltage protection 3-169 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.18.3.6 Settings Table 3.18-8 Settings of residual overvoltage protection No. Name Range Step Unit 1 59Gi.3U0_Set 0~2Unn 0.001 V 2 59Gi.t_Op 0.000~3600.000 0.001 s Remark Voltage setting of stage i of residual overvoltage protection. (i=1, 2, 3) Time delay of stage i of residual overvoltage protection. (i=1, 2, 3) Enabling/disabling stage i of residual 3 59Gi.En overvoltage protection (i=1, 2, 3) 0 or 1 0: disable 1: enable DefTime IECN IECV IECE IECST IECLT 4 59Gi.Opt_Curve ANSIE Option of characteristic curve for stage i ANSIV of residual overvoltage protection (i=2, 3) ANSI ANSIM ANSILTE ANSILTV ANSILT UserDefine 5 59Gi.TMS 0.050~3.200 0.001 6 59Gi.tmin 0.000~20.000 0.001 Time multiplier setting for stage i of residual overvoltage protection (i=2, 3) s Minimum operating time for stage i of residual overvoltage protection (i=2, 3) Constant “α” for stage i of customized 7 59Gi.Alpha 0.020~5.000 0.001 inverse-time characteristic residual overvoltage protection (i=2, 3) Constant “C” for stage i of customized 8 59Gi.C 0.000~20.000 0.001 inverse-time characteristic residual overvoltage protection (i=2, 3) Constant “K” for stage i of customized 9 59Gi.K 0.000~120.000 0.001 inverse-time characteristic residual overvoltage protection (i=2, 3) Enabling/disabling stage 3 of residual 10 59G3.En_Trp overvoltage protection for trip purpose 0 or 1 0: disable 1: enable 3-170 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.18.4 Undervoltage Protection 3.18.4.1 General Application The undervoltage protection can be applied to trip when fault occurs in a system. Two stages of undervoltage protection are available measuring phase voltages U A, UB and UC or phase-to-phase voltages UAB, UBC and UCA. The protection output can be selected for either any phase or all phases operation. The undervoltage protection is normally used as decoupling system rather than load shedding. 3.18.4.2 Function Description Phase undervoltage protection has following functions: 1. Three stages phase undervoltage protection with independent logic, voltage and time delay settings. 2. Undervoltage protection can be selected as definite-time or inverse-time characteristic. The inverse-time characteristic is selectable, among IEC and ANSI/IEEE standard inverse-time characteristics. 3. Phase voltage or phase-to-phase voltage can be selected for protection calculation. 4. “1-out-of-3” or “3-out-of-3” logic can be selected for protection criterion. (1-out-of-3 means any of three phase voltages, 3-out-of-3 means all three phase voltages) 1. Operation Criterion Users can select phase voltage or phase-to-phase voltage for the protection calculation. If setting [27Pi.Opt_Up/Upp] is set to “0”, phase voltage criterion is selected and if [27Pi.Opt_Up/Upp] is set to “1”, phase-to-phase voltage criterion is selected. When phase voltage or phase-to-phase voltage is less than any enabled stage voltage setting, the stage protection picks up and operates after delay, which will drop off instantaneously when fault voltage disappears. Phase voltage criterion Two operation criteria of definite-time undervoltage protection are shown as follows, which of them is applied depending on the logic setting [27Pi.Opt_1P/3P]. UΦ_min<[ 27Pi.U_Set] Equation 3.18-8 or Ua<[ 27Pi.U_Set] & Ub<[27Pi.U_Set] & Uc<[27Pi.U_Set] Equation 3.18-9 Where: UΦ_min is the minimum value among three phase voltages. Ua, Ub and Uc are three phase voltages. 3-171 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory [27Pi.U_Set] is the setting of stage i of undervoltage protection. When [27Pi.Opt_1P/3P] is set as “1”, “1-out-of-3” logic (Equation 3.18-8) is selected as operation criterion, and when set as “0”, “3-out-of-3” logic (Equation 3.18-9) is selected. Phase-to-phase voltage criterion Two operation criteria of definite-time undervoltage protection are shown as follows, which of them is applied depending on the logic setting [27Pi.Opt_Up/Upp]. UΦΦ_min<[ 27Pi.U_Set] Equation 3.18-10 or Uab<[27Pi.U_Set] & Ubc<[27Pi.U_Set] & Uca<[27Pi.U_Set] Equation 3.18-11 Where: UΦΦ_min is the minimum value among three phase-to-phase voltages. Uab, Ubc and Uca are three phase-to-phase voltages. [27Pi.U_Set] is the setting of stage i of undervoltage protection. When the setting [27Pi.Opt_1P/3P] is set as “1”, “1-out-of-3” logic (Equation 3.18-10) is selected as operation criterion, and when it is set as “0”, “3-out-of-3” logic (Equation 3.18-11) is selected. 2. Characteristic Curve Undervoltage protection can be selected as definite-time or inverse-time characteristic, and inverse-time operating time curve is as follows. Equation 3.18-12 Where: Uset is the setting [27Pi.U_Set]. Tp is time multiplier setting [27Pi.TMS]. K is a constant. C is a constant. α is a constant. U is the measured voltage Operating characteristic of undervoltage protection can be chosen from definite-time characteristic and twelve inverse-time characteristics by setting the logic setting [27Pi.Opt_Curve]. The 3-172 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory parameters of each characteristic are listed in the following table. Table 3.18-9 Inverse-time curve parameters of phase undervoltage protection 27Pi.Opt_Curve α K Time Characteristic C DefTime Definite time IECN IEC Normal inverse 0.14 0.02 0 IECV IEC Very inverse 13.5 1.0 0 IECE IEC Extremely inverse 80.0 2.0 0 IECST IEC Short-time inverse 0.05 0.04 0 IECLT IEC Long-time inverse 120.0 1.0 0 ANSIE ANSI Extremely inverse 28.2 2.0 0.1217 ANSIV ANSI Very inverse 19.61 2.0 0.491 ANSI ANSI Inverse 0.0086 0.02 0.0185 ANSIM ANSI Moderately inverse 0.0515 0.02 0.114 ANSILTE ANSI Long-time extremely inverse 64.07 2.0 0.25 ANSILTV ANSI Long-time very inverse 28.55 2.0 0.712 ANSILT ANSI Long-time inverse 0.086 0.02 0.185 When inverse-time characteristic is selected, if calculated operating time is less than setting [27Pi.tmin], then the operating time changes to the value of setting [27Pi.tmin] automatically. Define-time or inverse-time phase under voltage protection drops off instantaneously when measured voltage is higher than reset voltage. 3.18.4.3 Function Block Diagram 27Pi 27Pi.En1 27Pi.On 27Pi.En2 27Pi.Alm 27Pi.Blk 27Pi.Op 27Pi.St 27Pi.St1 27Pi.St2 27Pi.St3 27Pi.U_Absent 3.18.4.4 I/O Signals Table 3.18-10 I/O signals of undervoltage protection No. 1 Input Signal 27Pi.En1 Description Stage i of undervoltage protection enabling input 1, it is triggered from binary input or programmable logic etc. (i=1, 2, 3) 3-173 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 2 27Pi.En2 3 27Pi.Blk No. Stage i of undervoltage protection enabling input 2, it is triggered from binary input or programmable logic etc. (i=1, 2, 3) Stage i of undervoltage protection blocking input, it is triggered from binary input or programmable logic etc. (i=1, 2, 3) Output Signal Description 1 27Pi.On Stage i of undervoltage protection is enabled. (i=1, 2, 3) 2 27Pi.Op Stage i of undervoltage protection operates. (i=1, 2, 3) 3 27Pi.Alm Stage i of undervoltage protection alarms. (i=1, 2, 3) 4 27Pi.St Stage i of undervoltage protection starts. (i=1, 2, 3) 5 27Pi.St1 Stage i of undervoltage protection starts (A or AB). (i=1, 2, 3) 6 27Pi.St2 Stage i of undervoltage protection starts (B or BC). (i=1, 2, 3) 7 27Pi.St3 Stage i of undervoltage protection starts (C or CA). (i=1, 2, 3) 8 27Pi.U_Absent No AC voltage input after the device powered on for stage i of undervoltage protection (i=1, 2, 3) 3.18.4.5 Logic In order to prevent undervoltage protection from undesired operation, after the device powered on, if any phase current is greater than 0.06In or circuit breaker is in closed position, undervoltage protection will be in service with a time delay of 100ms when the corresponding phase voltage is greater than 0.1Un. Otherwise, undervoltage protection will be blocked by the signal “27Pi.U_Absent” Through settings these logic settings [27Pi.En_FD_Ctrl], [27Pi.En_Curr_Ctrl] and [27Pi.En_VTS_Blk], undervoltage protection optionally can be controlled by FD element reflecting current (including DPFC current element and residual current element), current condition and VT circuit failure When the setting [27Pi.En_FD_Ctrl] is set as “1”, undervoltage protection will be blocked if FD element reflecting current does not operate. When the setting [27Pi.En_Curr_Ctrl] is set as “1”, undervoltage protection will be blocked if current condition (>0.06In) is not met. When the setting [27Pi.En_VTS_Blk] is set as “1”, undervoltage protection will be blocked if VT circuit fails. If any phase of circuit breaker is open (binary input of normal close contact of breaker is energized) and the corresponding phase current is smaller than 0.06In, undervoltage protection will be blocked. 3-174 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory SIG VTS.Alm >=1 & SIG VTS.Inst EN [27Pi.En_VTS_Blk] EN [27Pi.En_FD_Ctrl] SIG FD.Pkp SIG CB Open SIG 27Pi.U_Absent & >=1 Block UV >=1 Figure 3.18-6 Blocking logic of undervoltage protection EN [27Pi.En] & SIG 27Pi.En1 & 27Pi.On SIG 27Pi.En2 SIG 27Pi.Blk Figure 3.18-7 Enabling logic of undervoltage protection SIG Ia>0.06In >=1 UV_PhA_Curr_Rls SIG Ib>0.06In >=1 UV_PhB_Curr_Rls SIG Ic>0.06In >=1 UV_PhC_Curr_Rls & >=1 UV_PhAB_Curr_Rls & >=1 UV_PhBC_Curr_Rls & >=1 UV_PhCA_Curr_Rls EN [27Pi.En_Curr_Ctrl] Figure 3.18-8 Current releasing logic of undervoltage protection 3-175 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory EN [27Pi.En_Alm] SET [27Pi.Opt_1P/3P] SIG 27Pi.On SIG Block UV SET [27Pi.Opt_Up/Upp] & Timer t & SIG UV_PhA_Curr_Rls >=1 & & t SET UA<[27Pi.U_Set] & SIG UV_PhAB_Curr_Rls SET UAB<[27Pi.U_Set] & SIG UV_PhB_Curr_Rls & Timer t & >=1 27Pi.Op t SET UB<[27Pi.U_Set] & & >=1 SIG UV_PhBC_Curr_Rls 27Pi.Alm & SET UBC<[27Pi.U_Set] >=1 & Timer t & SIG UV_PhC_Curr_Rls >=1 t SET UC<[27Pi.U_Set] 27Pi.St1 & 27Pi.St2 SIG UV_PhCA_Curr_Rls 27Pi.St3 SET UCA<[27Pi.U_Set] >=1 27Pi.St Figure 3.18-9 Logic diagram of stage i of undervoltage protection i=1, 2, 3 3.18.4.6 Settings Table 3.18-11 Settings of undervoltage protection No. Name Range Step Unit 1 27Pi.U_Set 0~Unn 0.001 V 2 27Pi.t_Op 0.000~30.000 0.001 s Remark Voltage setting for stage i of undervoltage protection (i=1, 2, 3) Time delay for stage i of undervoltage protection (i=1, 2, 3) Enabling/disabling stage i of undervoltage 3 27Pi.En protection (i=1, 2, 3) 0 or 1 0: disable 1: enable Enabling/disabling stage i of undervoltage protection controlled by FD element 4 27Pi.En_FD_Ctrl 0 or 1 reflecting current (i=1, 2, 3) 0: disable 1: enable 3-176 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory No. Name Range Step Unit Remark Enabling/disabling stage i of undervoltage protection controlled by current condition 5 27Pi.En_Curr_Ctrl 0 or 1 (i=1, 2, 3) 0: disable 1: enable Enabling/disabling stage i of undervoltage protection controlled by VT circuit failure 6 27Pi.En_VTS_Blk 0 or 1 (i=1, 2, 3) 0: disable 1: enable Option of 1-out-of-3 mode or 3-out-of-3 mode 7 27Pi.Opt_1P/3P 0 or 1 for stage i of undervoltage protection (i=1, 2, 3) 0: 3-out-of-3 mode 1: 1-out-of-3 mode Option of voltage criterion adopting phase-to-phase voltage or phase voltage 8 27Pi.Opt_Up/Upp for stage i of undervoltage protection (i=1, 0 or 1 2, 3) 0: phase voltage 1: phase-to-phase voltage Enabling/disabling stage i of undervoltage 9 27Pi.En_Alm protection operate to alarm (i=1, 2, 3) 0 or 1 0: disable 1: enable DefTime IECN IECV IECE IECST IECLT 10 27Pi.Opt_Curve Option of characteristic curve for stage i of ANSIE undervoltage protection (i=1, 2, 3) ANSIV ANSI ANSIM ANSILTE ANSILTV ANSILT Time multiplier setting for stage i of 11 27Pi.TMS 0.010~200.000 0.001 inverse-time undervoltage protection (i=1, 2, 3) 12 27Pi.tmin 0.050~20.000 0.001 s Minimum delay for stage i of inverse-time undervoltage protection (i=1, 2, 3) 3-177 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.19 Frequency Protection 3.19.1 Overfrequency Protection 3.19.1.1 General Application If the power frequency of regional rises due to the active power excess demand, overfrequency protection operates to perform generator rejection to shed part of the generators automatically according to the rising frequency so that power supply and the load are re-balanced. 3.19.1.2 Function Description The device provides four stages overfrequency protection. When system frequency is greater than the setting [81O.f_Pkp], overfrequency protection will put into service. In order to prevent possible maloperation of overfreqency protection in conditions of high harmonics, voltage circuit failures and so on, such blocking measures are carried out as follows: 1. Blocking in undervoltage condition If the positive voltage U1<0.15Un, the calculation of protection is not carried out and the output relay will be blocked. 2. Frequency abnormality condition When f<40Hz or f>65Hz, overfrequency protection will be blocked Operation criteria of overfrequency protection is shown in the following equation. f>[81O.OFi.f_Set] Equation 3.19-1 Where: f is system frequency. [81O.OFi.f_Set] is the frequency setting of stage i of overfrequency protection. (i=1, 2, 3, 4) 3.19.1.3 Function Block Diagram 81O.OFi 81O.En1 81O.OFi.On 81O.En2 81O.St 81O.Blk 81O.OFi.Op 3-178 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.19.1.4 I/O Signals Table 3.19-1 I/O signals of overfrequency protection No. Input Signal 1 81O.En1 2 81O.En2 3 81O.Blk No. Description Overfrequency protection enabling input 1, it is triggered from binary input or programmable logic etc. Overfrequency protection enabling input 2, it is triggered from binary input or programmable logic etc. Overfrequency protection blocking input, it is triggered from binary input or programmable logic etc. Output Signal Description 1 81O.OFi.On Stage i of overfrequency protection is enabled (i=1, 2, 3, 4). 2 81O.OFi.Op Stage i of overfrequency protection operates (i=1, 2, 3, 4). 3 81O.St Overfrequency protection starts. 3.19.1.5 Logic SIG 81O.St1 SIG 81O.St2 SIG 81O.St3 SIG 81O.St4 >=1 >=1 81O.St >=1 Figure 3.19-1 Logic diagram of overfrequency protection (start) SIG 81O.En1 SIG 81O.En2 EN [81O.OFi.En] SIG 81O.Blk SIG FD.Pkp SIG U1<0.15Un SIG f<40 or f>65 SET f>[81O.f_Pkp] & & 81O.OFi.On & >=1 & 50ms 0ms 81O.Sti & SET f>[81O.OFi.f_Set] EN [81O.OFi.En] SIG VTS.Alm [81O.OFi.t_Op] & 0ms 81O.OFi.Op Figure 3.19-2 Logic diagram of stage i of overfrequency protection i=1, 2, 3, 4 3-179 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.19.1.6 Settings Table 3.19-2 Settings of overfrequency protection No. 1 Name 81O.f_Pkp Range 50.000~65.000 Step Unit 0.001 Hz Remark Frequency pickup setting for overfrequency protection Frequency setting for stage i of 2 81O.OFi.f_Set 50.000~65.000 0.001 Hz overfrequency protection (i=1, 2, 3, 4) Time 3 81O.OFi.t_Op 0.000~20.000 0.001 s delay for stage i of overfrequency protection (i=1, 2, 3, 4) Enabling/disabling stage i of overfrequency protection (i=1, 2, 3, 4 81O.OFi.En 0 or 1 4) 0: disable 1: enable 3.19.2 Underfrequency Protection 3.19.2.1 General Application In case of frequency decline due to lack of active power in the power system, underfrequency protection operates to shed part of the load according to the declined value of frequency to re-balance the power supply and the load. 3.19.2.2 Function Description The device provides four stages underfrequency protection. When system frequency is smaller than the setting [81U.f_Pkp], underfrequency protection will put into service. In order to prevent possible maloperation of underfrequency protection in conditions of high harmonics, voltage circuit failures and so on, such blocking measures are carried out as follows: 1. Blocking in undervoltage condition If the positive voltage U1<0.15Un, the calculation of protection is not carried out and the output relay will be blocked. 2. df/dt blocking element If -df/dt≥[81U.df/dt_Blk], the calculation of protection is not carried out and the output relay will be blocked. The blocking element will not be released automatically until the system frequency recovers to be greater than the setting [81U.f_Pkp]. 3. Frequency abnormality condition When f<40Hz or f>65Hz, underfrequency protection will be blocked Operation criteria of underfrequency protection is shown in the following equation. 3-180 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory f<[81U.UFi.f_Set] Equation 3.19-2 Where: f is system frequency. [81U.UFi.f_Set] is the frequency settings of stage i of underfrequency protection. (i=1, 2, 3, 4) The equation of df/dt blocking function is as follows. -df/dt>[81U.df/dt_Blk] Equation 3.19-3 Where: df/dt is the frequency slip speed and the time step (i.e. dt) for the calculation is equal to 5 cycle. [81U.df/dt_Blk] is the setting of df/dt blocking underfrequency protection. Underfrequency protection can be blocked by the frequency slip speed (df/dt). If the logic setting [81U.UFi.En_df/dt_Blk] is set as “1”, when Equation 3.19-2 and Equation 3.19-3 are met, it is decided that a fault occurred and the corresponding stage underfrequency protection is blocked at the same time for the purpose of waiting for operation of other related protection. The blocking signal will not reset until the system frequency recovers, i.e. the system frequency is greater than the setting [81U.f_Pkp]. If the logic setting is set as “0”, when Equation 3.19-2 and Equation 3.19-3 are met, the stage underfrequency protection will be released to operate. 3.19.2.3 Function Block Diagram 81U.UFi 81U.En1 81U.UFi.On 81U.En2 81U.St 81U.Blk 81U.UFi.Op 3.19.2.4 I/O Signals Table 3.19-3 I/O signals of underfrequency protection No. Input Signal 1 81U.En1 2 81U.En2 3 81U.Blk No. Description Underfrequency protection enabling input 1, it is triggered from binary input or programmable logic etc. Underfrequency protection enabling input 2, it is triggered from binary input or programmable logic etc. Underfrequency protection blocking input, it is triggered from binary input or programmable logic etc. Output Signal Description 3-181 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 1 81U.UFi.On Stage i of underfrequency protection is enabled (i=1, 2, 3, 4). 2 81U.UFi.Op Stage i of underfrequency protection operates (i=1, 2, 3, 4). 3 81U.St Underfrequency protection starts. 3.19.2.5 Logic SIG 81U.St1 SIG 81U.St2 SIG 81U.St3 SIG 81U.St4 >=1 >=1 81U.St >=1 Figure 3.19-3 Logic diagram of underfrequency protection (start) SIG 81U.En1 & SIG 81U.En2 EN & [81U.UFi.En] 81U.UFi.On SIG 81U.Blk & SIG FD.Pkp & SIG U1<0.15Un >=1 SIG f<40 or f>65 SET f<[81U.f_Pkp] 50ms SET -df/dt<[81U.df/dt_Blk] >=1 EN [81U.UFi.En_df/dt_Blk] SET f<[81U.UFi.f_Set] EN 0ms & 81U.Sti & [81U.UFi.t_Op] & 0ms 81U.UFi.Op [81U.UFi.En] SIG VTS.Alm Figure 3.19-4 Logic diagram of stage i of underfrequency protection i=1, 2, 3, 4 3.19.2.6 Settings Table 3.19-4 Settings of underfrequency protection No. Name Range Step Unit 1 81U.f_Pkp 45.000~60.000 0.01 Hz 2 81U.df/dt_Blk 0.200~20.000 0.01 Hz/s 3 81U.UFi.f_Set 45.000~60.000 0.001 Hz 3-182 Remark Frequency pickup setting for underfrequency protection Rate of frequency change for blocking underfrequency protection Frequency setting for stage i of PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory No. Name Range Step Unit Remark underfrequency protection (i=1, 2, 3, 4) Time 4 81U.UFi.t_Op 0.000~30.000 0.01 s delay for stage i of underfrequency protection (i=1, 2, 3, 4) Enabling/disabling stage i of underfrequency protection (i=1, 2, 3, 5 81U.UFi.En 0 or 1 4) 0: disable 1: enable Enabling/disabling rate of frequency change 6 81U.UFi.En_df/dt_Blk to block stage i of underfrequency protection (i=1, 2, 3, 0 or 1 4) 0: disable 1: enable 3.20 Breaker Failure Protection 3.20.1 General Application Duplicated protection configurations are usually adopted for EHV power system, but the primary equipment, circuit breaker, is not duplicated. Breaker failure protection is adopted to cater circuit breaker tripping failure. Breaker failure protection issues a back-up trip command to trip adjacent circuit breakers in case of a tripping failure of the circuit breaker, and clears the fault as requested by the device. To utilize the protection information of faulty equipment and the electrical information of failure circuit breaker to constitute the criterion of breaker failure protection, it can ensure that the adjacent circuit breakers of failure circuit breaker are tripped with a shorter time delay, so that the affected area is minimized, and ensure stable operation of the entire power grid to prevent generators, transformers and other components from seriously damaged. NOTICE! For double circuit breakers mode, the device will provide independent breaker failure protection for CB1 and CB2 respectively. Both breaker failure protections have the same logic. The difference is that the prefix “CBx.” is added to all signals and settings for circuit breaker No.x (x=1 or 2). 3.20.2 Function Description The instantaneous re-tripping function, after receiving tripping signal from other device and the corresponding phase overcurrent element operating, is available and provides phase-segregated binary output contact, which can ensure the circuit breaker is still tripped in case the secondary circuit between the device and the circuit breaker is abnormal, to avoid undesired tripping of 3-183 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory breaker failure protection and the expansion of the affected area. Instantaneous re-tripping function does not block AR. When both the phase-segregated tripping contact from line protection and the corresponding phase overcurrent element operate, or both the three-phase tripping contact and any phase overcurrent element operate, breaker failure protection will send three-phase tripping command to trip local circuit breaker after time delay of [CBx.50BF.t1_Op] and trip all adjacent circuit breakers after time delay of [CBx.50BF.t2_Op]. When the protection element except undervoltage element within this device operates and issues tripping signal, breaker failure protection will also be initiated. Taking into account that the faulty current is too small for generator or transformer fault, the sensitivity of phase current element may not meet the requirements, zero-sequence current criterion and negative-sequence current criterion are provided in addition to the phase overcurrent element for breaker failure protection initiated by input signal [CBx.50BF.ExTrp3P_GT] from generator and transformer protection. They can be enabled or disabled by logic settings [CBx.50BF.En_3I0_3P] and [CBx.50BF.En_I2_3P] respectively. For some special fault (for example, mechanical protection or overvoltage protection operating), maybe faulty current is very small and current criterion of breaker failure protection is not met, in order to make breaker failure protection can also operate under the above situation, an input signal [CBx.50BF.ExTrp_WOI] is equipped to initiate breaker failure protection, once the input signal is energized, normally closed auxiliary contact of circuit breaker is chosen in addition to breaker failure current check to trigger breaker failure timer. The device takes current as priority with CB auxiliary contact (52b) as an option criterion for breaker failure check. 3.20.3 Function Block Diagram 50BF CBx.50BF.ExTrp3P_L CBx.50BF.On CBx.50BF.ExTrp3P_GT CBx.50BF.Op_ReTrpA CBx.50BF.ExTrp_WOI CBx.50BF.Op_ReTrpB CBx.50BF.ExTrpA CBx.50BF.Op_ReTrpC CBx.50BF.ExTrpB CBx.50BF.Op_ReTrp3P CBx.50BF.ExTrpC CBx.50BF.Op_t1 CBx.50BF.En CBx.50BF.Op_t2 CBx.50BF.Blk 3-184 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.20.4 I/O Signals Table 3.20-1 I/O signals of breaker failure protection No. Input Signal Description 1 CBx.50BF.ExTrp3P_L Input signal of three-phase tripping contact from line protection 2 CBx.50BF.ExTrp3P_GT 3 CBx.50BF.ExTrpA Input signal of phase-A tripping contact from external device 4 CBx.50BF.ExTrpB Input signal of phase-B tripping contact from external device 5 CBx.50BF.ExTrpC Input signal of phase-C tripping contact from external device Input signal of three-phase tripping contact from generator or transformer protection Input signal of three-phase tripping contact from external device. Once it is 6 CBx.50BF.ExTrp_WOI energized, normally closed auxiliary contact of circuit breaker is chosen in addition to breaker failure current check to trigger breaker failure timers. 7 CBx.50BF.En Input signal of enabling breaker failure protection Breaker failure protection blocking input, such as function blocking binary 8 CBx.50BF.Blk input. When the input is 1, breaker failure protection is reset and time delay is cleared. No. Output Signal Description 1 CBx.50BF.On Breaker failure protection is enabled 2 CBx.50BF.Op_ReTrpA Breaker failure protection operates to re-trip phase-A circuit breaker 3 CBx.50BF.Op_ReTrpB Breaker failure protection operates to re-trip phase-B circuit breaker 4 CBx.50BF.Op_ReTrpC Breaker failure protection operates to re-trip phase-C circuit breaker 5 CBx.50BF.Op_ReTrp3P Breaker failure protection operates to re-trip three-phase circuit breaker 6 CBx.50BF.Op_t1 Stage 1 of breaker failure protection operates 7 CBx.50BF.Op_t2 Stage 2 of breaker failure protection operates 3-185 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.20.5 Logic SIG CBx.50BF.En EN & [CBx.50BF.En] CBx.50BF.On SIG CBx.50BF.Blk SIG CBx.50BF.On & SIG FD.Pkp EN [CBx.50BF.En_ReTrp] EN [CBx.50BF.En_3I0_1P] >=1 SET 3I0>[CBx.50BF.3I0_Set] SIG CBx.BFI_A BI & >=1 & >=1 & >=1 & SIG CBx.BFI_B [CBx.50BF.t_ReTrp] 0ms CBx.50BF.Op_ReTrpB [CBx.50BF.t_ReTrp] 0ms CBx.50BF.Op_ReTrpC & [CBx.50BF.ExTrpB] SET IB>[CBx.50BF.I_Set] SIG CBx.BFI_C BI CBx.50BF.Op_ReTrpA [CBx.50BF.ExTrpA] SET IA>[CBx.50BF.I_Set] BI [CBx.50BF.t_ReTrp] 0ms & [CBx.50BF.ExTrpC] >=1 SET IC>[CBx.50BF.I_Set] SIG CBx.BFI_3P BI [CBx.50BF.ExTrp3P_L] BI [CBx.50BF.ExTrp3P_GT] BI [CBx.50BF.ExTrp_WOI] EN [CBx.50BF.En_3I0_3P] >=1 >=1 >=1 [CBx.50BF.t_ReTrp] 0ms >=1 >=1 [CBx.50BF.Op_ReTrp3P] & & & SET 3I0>[CBx.50BF.3I0_Set] EN [CBx.50BF.En_I2_3P] & & & & >=1 >=1 [CBx.50BF.t1_Op] 0ms CBx.50BF.Op_t1 [CBx.50BF.t2_Op] 0ms CBx.50BF.Op_t2 & SET I2>[CBx.50BF.I2_Set] & EN [CBx.50BF.En_CB_Ctrl] BI [CBx.52b_PhA] BI [CBx.52b_PhB] BI [CBx.52b_PhC] SIG CBx.50BF.On & & SIG FD.Pkp Figure 3.20-1 Logic diagram of breaker failure protection 3-186 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.20.6 Settings Table 3.20-2 Settings of breaker failure protection No. Name Range Step Unit Remark Current setting of phase current criterion for BFP 1 CBx.50BF.I_Set (0.050~30.000 )×In 0.001 A 2 CBx.50BF.3I0_Set (0.050~30.000 )×In 0.001 A 3 CBx.50BF.I2_Set (0.050~30.000 )×In 0.001 A 4 CBx.50BF.t_ReTrp 0.000~10.000 0.001 s Time delay of re-tripping for BFP 5 CBx.50BF.t1_Op 0.000~10.000 0.001 s Time delay of stage 1 for BFP 6 CBx.50BF.t2_Op 0.000~10.000 0.001 s Time delay of stage 2 for BFP 7 CBx.50BF.En 0 or 1 8 CBx.50BF.En_ReTrp 0 or 1 9 CBx.50BF.En_3I0_1P 0 or 1 10 CBx.50BF.En_3I0_3P 0 or 1 11 CBx.50BF.En_I2_3P 0 or 1 12 CBx.50BF.En_CB_Ctrl 0 or 1 Current setting of zero-sequence current criterion for BFP Current setting of negative-sequence current criterion for BFP Enabling/disabling breaker failure protection 0: disable 1: enable Enabling/disabling re-trip function for BFP 0: disable 1: enable Enabling/disabling zero-sequence current criterion for BFP initiated by single-phase tripping contact 0: disable 1: enable Enabling/disabling zero-sequence current criterion for BFP initiated by three-phase tripping contact 0: disable 1: enable Enabling/disabling negative-sequence current criterion for BFP initiated by three-phase tripping contact 0: disable 1: enable Enabling/disabling breaker failure protection can be initiated by normally closed contact of circuit breaker 0: disable 1: enable 3-187 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.21 Thermal Overload Protection 3.21.1 General Application During overload operation of a transmission line (specially for cable), great current results in greater heat to lead temperature increase and if the temperature reaches too high values the equipment might be damaged. Thermal overload protection estimates the internal heat content (temperature) continuously. This estimation is made by using a thermal model with two time constants, which is based on current measurement. When the temperature increases to the alarm value, the protection issues alarm signals to remind the operator for attention, and if the temperature continues to increase to the trip value, the protection sends trip command to disconnect the protected line. 3.21.2 Function Description Thermal overload protection has following functions: Thermal time characteristic adopting IEC 60255-8 Two stages for alarm purpose and two stages for trip purpose Thermal accumulation can be cleared by external input signal The device provides a thermal overload model which is based on the IEC60255-8 standard. The thermal overload formulas are shown as below. 1. Cold start characteristic: 2. Hot start characteristic: Where: T = Time to operate (in seconds) = Thermal time constant of the equipment to be protected, the setting [49.Tau] IB = Full load current rating, the setting [49.Ib_Set] I = The RMS value of the largest phase current IP = Steady state pre-loading before application of the overload k = Factor associated to the thermal state formula, the setting [49.K] 3-188 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory ln = Natural logarithm The characteristic curve of thermal overload model is shown in Figure 3.21-1. Refer to IEC60255-8 t Ip P=— IB P = 0.0 P = 0.6 P = 0.8 P = 0.9 kIB I Figure 3.21-1 Characteristic curve of thermal overload model The hot start characteristic is adopted in the device. The calculation is carried out at zero of Ip, so users need not to set the value of Ip. Tripping outputs of the protection is controlled by current, even if the thermal accumulation value is greater than the setting for tripping, the protection drops off instantaneously when current disappears. Alarm outputs of the protection is not controlled by current, and only if the thermal accumulation value is greater than the setting for alarm, alarm output contacts, which can be connected to block the auto-reclosure, will operate. 3.21.3 Function Block Diagram 49 49.Clr_Cmd 49.On 49.En 49.St 49.Blk 49-i.Alm 49-i.Op 3.21.4 I/O Signals Table 3.21-1 I/O signals of thermal overload protection No. Input Signal 1 49.Clr_Cmd 2 49.En 3 49.Blk Description Input signal of clear thermal accumulation value Thermal overload protection enabling input, it is triggered from binary input or programmable logic etc. Thermal overload protection blocking input, it is triggered from binary input or 3-189 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory programmable logic etc. No. Output Signal Description 1 49.On Thermal overload protection is enabled. 2 49.St Thermal overload protection starts. 3 49-i.Op Stage i of thermal overload protection operates to trip. (i=1, 2) 4 49-i.Alm Stage i of thermal overload protection operates to alarm. (i=1, 2) 3.21.5 Logic SIG 49.En & & SIG 49.Blk 49.On EN [49-i.En_Trp] EN [49-i.En_Alm] >=1 & SIG FD.Pkp 49.St Timer t & 49-i.Op t SIG I3P Timer t & SET [49.Ib_Set] BI 49-i.Alm t [49.Clr_Cmd] Figure 3.21-2 Logic diagram of stage i of thermal overload protection i=1, 2 3.21.6 Settings Table 3.21-2 Settings of thermal overload protection No. Name Range Step Unit Remark The factor setting for stage i of 1 49-i.K 1.000~3.000 0.001 % thermal overload protection which is associated to the thermal state formula (i=1, 2) 2 49.Ib_Set (0.050~30.000 )×In 0.001 A 3 49.Tau 0.100~100.000 0.001 min The reference current setting of the thermal overload protection The time constant setting of the IDMT overload protection Enabling/disabling stage i of thermal overload 4 49-i.En_Alm 0 or 1 protection for alarm purpose (i=1, 2) 0: disable 1: enable 3-190 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory No. Name Range Step Unit Remark Enabling/disabling stage i of thermal overload protection for trip purpose 5 49-i.En_Trp 0 or 1 (i=1, 2) 0: disable 1: enable 3.22 Stub Differential Protection 3.22.1 General Application Stub differential protection is mainly designed for one and a half breakers arrangement. When line disconnector is open and transmission line is put into maintenance, line VT is no voltage. Distance protection is disabled, and stub differential protection is enabled. It is used to protect stub section among two circuit breakers and line disconnector. Usually, stub differential protection is enabled automatically by normally closed auxiliary contact of line disconnector. CT1 CT2 Bus Bus To the device Line Line Figure 3.22-1 3/2 breakers arrangement 3.22.2 Function Description 3.22.2.1 Stub Differential Element Stub differential element is composed of percentage differential principle. Stub differential element can be controlled by normally closed auxiliary contact of line disconnector to enabled or disabled. The normally closed auxiliary contact of line disconnector is closed when line disconnector is open. The operation criterion is: I 1 I 2 [87STB.I_Pkp] I I 1 2 [87STB.Slop e] I 1 I 2 3-191 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Where: I 1 、 I 2 are secondary phase currents corresponding to both circuit breakers, are formed by phase A, B, C 3.22.2.2 Differential Current Alarm Under normal conditions, when stub differential protection is enabled, the device will issue the alarm signal [87STB.Alm_Diff] with the time delay if the following operation criterion is met. I 1 I 2 [87STB.I_Alm] I I 1 2 0.15 I 1 I 2 3.22.2.3 Disconnector Position Alarm The device will issue the alarm signal [87STB.Alm_89b_DS] with the time delay of 10s if the signal [87STB.89b_DS] is energized and the line is live, and the alarm signal will drop off with the time delay of 10s after the abnormality disappears. When the alarm signal of disconnector position appears, the operator should confirm the status of disconnector position in time. The user can use programmable logic to determine whether the disconnector position alarm will blocked stub differential protection. 3.22.2.4 CT Saturation When there is an external fault, transient CT saturation may be happened. In order to prevent stub differential protection from undesired operation, the floating technology of adaptive restraint current is adopted to ensure that the device does not maloperate due to the serious saturation. 3.22.3 Function Block Diagram 87STB 87STB.En1 87STB.On 87STB.En2 87STB.On_Local 87STB.Blk 87STB.Op 87STB.89b_DS 87STB.St 87STB.89b_DS_Rmt 87STB.StA 87STB.StB 87STB.StC 87STB.Alm_Diff 87STB.Alm_89b_DS 3-192 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.22.4 I/O Signals Table 3.22-1 I/O signals of stub differential protection No. Input Signal 1 87STB.En1 2 87STB.En2 3 87STB.Blk 4 87STB.89b_DS Description Stub differential protection enabling input 1, it is triggered from binary input or programmable logic etc. Stub differential protection enabling input 2, it is triggered from binary input or programmable logic etc. Stub differential protection blocking input, it is triggered from binary input or programmable logic etc. Normally closed auxiliary contact of line disconnector Normally closed auxiliary contact of line disconnector in remote end 5 87STB.89b_DS_Rmt In general, it is configured as receiving the signal [87STB.On_Local] from the remote end. No. Output Signal Description Stub differential protection is enabled. (Based on disconnector position signal 1 87STB.On 2 87STB.On_Local 3 87STB.Op Stub differential protection operates. 4 87STB.St Stub differential protection starts. 5 87STB.StA Phase A of stub differential protection starts. 6 87STB.StB Phase B of stub differential protection starts. 7 87STB.StC Phase C of stub differential protection starts. 8 87STB.Alm_Diff The alarm signal of differential current abnormality 9 87STB.Alm_89b_DS The alarm signal of disconnector position abnormality in both local end and remote end) Stub differential protection is enabled. (Based on disconnector position signal in local end) 3.22.5 Logic Based on calculating vector summation of currents from dual CTs, the logic scheme of stub differential protection is shown as Figure 3.22-2. 3-193 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory SIG Idiff>0.06In SIG 87STB.89b_DS SIG 87STB.En1 SIG 87STB.En2 EN [87STB.En] SIG 87STB.Blk SIG Enable 87STB SIG 87STB.89b_DS & 10s 10s 87STB.Alm_89b_DS & & Enable 87STB & 87STB.On_Local >=1 & SIG 87STB.89b_DS_Rmt SET Idiffa>[87STB.I_Alm] SET IdiffA>0.15×IBiasA SET Idiffb>[87STB.I_Alm] SET IdiffB>0.15×IBiasB SET Idiffc>[87STB.I_Alm] SET IdiffC>0.15×IBiasC EN [87STB.En_Alm] SIG 87STB.Alm_Diff SIG 87STB.En_CTS_Blk SET Idiffa>[87STB.I_Pkp] SET IdiffA>[87STB.Slope]×IBiasA SET Idiffb>[87STB.I_Pkp] SET IdiffB>[87STB.Slope]×IBiasB SET Idiffc>[87STB.I_Pkp] SET IdiffC>[87STB.Slope]×IBiasC 87STB.On & & & >=1 & & 10s 10s 87STB.Alm_Diff & & >=1 >=1 87STB.St [87STB.t_Op] 87STB.Op & 87STB.StA & & 87STB.StB & & 87STB.StC & Figure 3.22-2 Logic diagram of stub differential protection 3.22.6 Settings Table 3.22-2 Settings of stub differential protection No. 1 Name 87STB.I_Pkp Range Step Unit (0.050~30.000)×In 0.001 A 3-194 Remark Pickup current setting of stub differential protection PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory No. Name Range Step Unit A 2 87STB.I_ Alm (0.050~30.000)×In 0.001 3 87STB.Slope 0.5~1 0.001 4 87STB.t_Op 0.000~10.000 0.001 Remark Current setting of differential current differential current alarm Slope of protection s Time delay of stub differential protection Enabling/disabling stub differential 5 87STB.En protection 0 or 1 1: enable 0: disable Enabling/disabling 6 87STB.En_Alm differential current alarm function 0 or 1 1: enable 0: disable Enabling/disabling stub differential protection controlled by CT circuit 7 87STB.En_CTS_Blk 0 or 1 failure 1: enable 0: disable 3.23 Dead Zone Protection 3.23.1 General Application Generally, fault current is very large when multi-phase fault occurs between CT and circuit breaker (i.e. dead zone) and it will have a greater impact on the system. Breaker failure protection can operate after a longer time delay, in order to clear the dead zone fault quickly and improve the system stability, dead zone protection with shorter time delay (compared with breaker failure protection) is adopted. NOTICE! For double circuit breakers mode, the device will provide independent dead zone protection for CB1 and CB2 respectively. Both dead zone protections have the same logic. The difference is that the prefix “CBx.” is added to all signals and settings for circuit breaker No.x (x=1 or 2). 3.23.2 Function Description For some wiring arrangement (for example, circuit breaker is located between CT and the line), if fault occurs between CT and circuit breaker, line protection can operate to trip circuit breaker quickly, but the fault have not been cleared since local circuit breaker is tripped. Here dead zone protection is needed in order to trip relevant circuit breaker. The criterion for dead zone protection is: when dead zone protection is enabled, binary input of initiating dead zone protection is energized (by default, three-phase tripping signal is used to 3-195 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory initiate dead zone protection), if overcurrent element for dead zone protection operates, then corresponding circuit breaker is tripped and three phases normally closed contact of the circuit breaker are energized, dead zone protection will operate to trip adjacent circuit breaker after a time delay. 3.23.3 Function Block Diagram 50DZ CBx.50DZ.En1 CBx.50DZ.On CBx.50DZ.En2 CBx.50DZ.Op CBx.50DZ.Blk CBx.50DZ.St CBx.50DZ.Init 3.23.4 I/O Signal Table 3.23-1 I/O signals of dead zone protection No. Input Signal Description 1 CBx.50DZ.En1 Dead zone protection enabling input 1, it can be binary inputs or logic link. 2 CBx.50DZ.En2 Dead zone protection enabling input 2, it can be binary inputs or logic link. 3 CBx.50DZ.Blk 4 CBx.50DZ.Init No. Dead zone protection blocking input, such as function blocking binary input. When the input is 1, dead zone protection is reset and time delay is cleared. Initiation signal input of the dead zone protection. Output Signal Description 1 CBx.50DZ.On Dead zone protection is enabled. 2 CBx.50DZ.St Dead zone protection starts. 3 CBx.50DZ.Op Dead zone protection operates. 3-196 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.23.5 Logic EN [CBx.50DZ.En] SIG CBx.50DZ.En1 SIG CBx.50DZ.En2 SIG CBx.50DZ.Blk & & CBx.50DZ.On & CBx.50DZ.St & [CBx.50DZ.t_Op] SIG FD.Pkp SIG CBx.52b_PhA SIG CBx.52b_PhB SIG CBx.52b_PhC SET Ia > [CBx.50DZ.I_Set] SET Ib > [CBx.50DZ.I_Set] SET Ic > [CBx.50DZ.I_Set] SIG CBx.50DZ.Init SIG CBx.Trp 0ms CBx.50DZ.Op & >=1 & >=1 Figure 3.23-1 Dead zone protection 3.23.6 Settings Table 3.23-2 Settings of dead zone protection No. Name Range Step Unit Remark Current 1 CBx.50DZ.I_Set (0.050~30.000)×In 0.001 A setting for dead zone protection. This setting shall ensure the protection being sensitive enough if dead zone fault occurs. 2 CBx.50DZ.t_Op 0.000~10.000 0.001 s Time delay of dead zone protection. Enabling/disabling 3 CBx.50DZ.En 0 or 1 - dead zone protection. 1: enable 0: disable 3.24 Pole Discrepancy Protection 3.24.1 General Application The pole discrepancy of circuit breaker may occur during operation of a breaker with segregated operating gears for the three phases. The reason could be an interruption in the tripping/closing circuits, or mechanical failure. A pole discrepancy can only be tolerated for a limited period. When there is loading, zero-sequence or negative-sequence current will be generated in the power system, which will result in overheat of the generator or the motor. With the load current increasing, overcurrent elements based on zero-sequence current or negative-sequence current may operate. 3-197 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Pole discrepancy protection is required to operate before the operation of these overcurrent elements. NOTICE! For double circuit breakers mode, the device will provide independent pole discrepancy protection for CB1 and CB2 respectively. Both pole discrepancy protections have the same logic. The difference is that the prefix “CBx.” is added to all signals and settings for circuit breaker No.x (x=1 or 2). 3.24.2 Function Description Pole discrepancy protection determines three-phase breaker pole discrepancy condition by its phase segregated CB auxiliary contacts. In order to improve the reliability of pole discrepancy protection, the asymmetrical current component can be selected as addition criteria when needed. 3.24.3 Function Block Diagram 62PD CBx.62PD.En1 CBx.62PD.On CBx.62PD.En2 CBx.62PD.Op CBx.62PD.Blk CBx.62PD.St 3.24.4 I/O Signals Table 3.24-1 I/O signals of pole discrepancy protection No. Input Signal 1 CBx.62PD.En1 2 CBx.62PD.En2 3 CBx.62PD.Blk No. Description Pole discrepancy protection enabling input 1, it is triggered from binary input or programmable logic etc. Pole discrepancy protection enabling input 2, it is triggered from binary input or programmable logic etc. Pole discrepancy protection blocking input, it is triggered from binary input or programmable logic etc. Output Signal Description 1 CBx.62PD.On Pole discrepancy protection is enabled. 2 CBx.62PD.Op Pole discrepancy protection operates to trip 3 CBx.62PD.St Pole discrepancy protection starts 3.24.5 Logic Phase-segregated circuit breaker auxiliary contacts are connected to the device. When the state of three phase-segregated circuit breaker auxiliary contacts are inconsistent, pole discrepancy protection will be started and initiate output after a time delay [CBx.62PD.t_Op]. 3-198 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Pole discrepancy protection can be blocked by external input signal [62PD.Blk]. In general, this input signal is usually from the output of 1-pole AR initiation, so as to prevent pole discrepancy protection from operation during 1-pole AR initiation. SIG CBx.62PD.En1 SIG CBx.62PD.En2 EN [CBx.62PD.En] & & 62PD.On & SIG CBx.62PD.Blk SIG FD.Pkp EN [CBx.62PD.En_3I0/I2_Ctrl] SET 3I0>[CBx.62PD.3I0_Set] >=1 >=1 SET I2>[CBx.62PD.I2_Set] BI [CBx.52b_PhA] & & SIG CBx.Ia<0.06In BI [CBx.52b_PhB] SIG CBx.Ib<0.06In BI [CBx.52b_PhC] SIG CBx.Ic<0.06In & 62PD.St [62PD.t_Op] & 0ms 62PD.Op & >=1 & Figure 3.24-1 Logic diagram of pole discrepancy protection Where: CBx.52b_PhA, CBx.52b_PhB and CBx.52b_PhC: Please refer to section 3.4. 3.24.6 Settings Table 3.24-2 Settings of pole discrepancy protection No. Name Range Step Unit 1 CBx.62PD.3I0_Set (0.050~30.000 )×In 0.001 A 2 CBx.62PD.I2_Set (0.050~30.000 )×In 0.001 A 3 CBx.62PD.t_Op 0.000~600.000 0.001 s 4 CBx.62PD.En 0 or 1 Remark Current setting of residual current criterion for pole discrepancy protection Current setting of negative-sequence current criterion for pole discrepancy protection Time delay of pole discrepancy protection Enabling/disabling pole discrepancy protection 0: disable 3-199 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory No. 5 Name CBx.62PD.En_3I0/I2_Ctrl Range Step Unit Remark 1: enable Enabling/disabling residual current criterion and negative-sequence current criterion for pole discrepancy protection 0: disable 1: enable 0 or 1 3.25 Broken Conductor Protection 3.25.1 General Application Single-phase earthing fault and two-phases earthing fault are the most common fault on circuits, the fault is easy to detect because the fault current will increase obviously. Broken-conductor fault is difficult to detect since there is no increase of current but negative-sequence current, so negative-sequence overcurrent protection can be considered to clear broken-conductor fault. However, under heavy load condition, negative-sequence current is relative large due to unbalance loading, but negative-sequence current because of broken-conductor fault under light load condition is relative small. If negative-sequence current protection is set larger than maximum negative-sequence current under loading, the protection may be failure to operate if broken-conductor fault happens under light load condition, negative-sequence overcurrent protection is therefore not suitable to apply for broken-conductor fault. The network of single-phase broken condition is similar to that of two-phases earthing fault, positive-sequence, negative-sequence and zero-sequence network is connected in parallel, I2/I1= Z0/(Z0+Z2), generally, zero-sequence impedance is larger than positive-sequence impedance, i.e. I2/I1>0.5. The network of two-phases broken condition is similar to that of single-phase earthing fault, positive-sequence, negative-sequence and zero-sequence network is connected in series, so I2/I1=1. 3.25.2 Function Description Broken-conductor fault mainly is single-phase broken or two-phases broken. According to the ratio of negative-sequence current to positive-sequence current (I2/I1), it is used to judge whether there is an broken-conductor fault. Negative-sequence current under normal operating condition (i.e. unbalance current) is due to CT error and unbalance load, so the ratio of negative-sequence current to positive-sequence current (amplitude) is relative steady. The value with margin can then be used as the setting of broken conductor protection. It is mainly used to detect broken-conductor fault and CT circuit failure as well. 3-200 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.25.3 Function Block Diagram 46BC 46BC.En1 46BC.On 46BC.En2 46BC.St 46BC.Blk 46BC.Op 46BC.Alm 3.25.4 I/O Signals Table 3.25-1 I/O signals of broken conductor protection No. Input Signal 1 46BC.En1 2 46BC.En2 3 46BC.Blk No. Description Enable broken conductor protection input 1, it is triggered from binary input or programmable logic etc. Enable broken conductor protection input 2, it is triggered from binary input or programmable logic etc. Broken conductor protection blocking input, it is triggered from binary input or programmable logic etc. Output Signal Description 1 46BC.On Broken-conductor protection is enabled. 2 46BC.St Broken-conductor protection starts. 3 46BC.Op Broken-conductor protection operates to trip. 4 46BC.Alm Broken-conductor protection operates to alarm. 3.25.5 Logic SIG 46BC.En1 SIG 46BC.En2 SIG 46BC.Blk & & 46BC.On 46BC.St & [46BC.t_Op] 0ms SET Ia>[46BC.I_Min] >=1 SET Ib>[46BC.I_Min] SET Ic>[46BC.I_Min] & SET I2/I1>[46BC.I2/I1_Set] EN 46BC.Op [46BC.En_Trp] & 46BC.Alm EN [46BC.En_Alm] Figure 3.25-1 Logic diagram of broken conductor protection 3-201 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.25.6 Settings Table 3.25-2 Settings of broken conductor protection No. Name Range 1 46BC.I2/I1_Set 0.20~1.00 0.001 2 46BC.t_Op 0.000~600.000 0.001 s 3 46BC.I_Min (0.050~30.000)×In 0.001 A 4 46BC.En_Trp 0 or 1 5 46BC.En_Alm 0 or 1 Step Unit Remark Ratio setting (negative-sequence current to positive-sequence current) of broken conductor protection Time delay of broken conductor protection Minimum operation current of broken conductor protection Enabling/disabling broken conductor protection to operate to trip 0: disable 1: enable Enabling/disabling broken conductor protection to operate to alarm 0: disable 1: enable 3.26 Reverse Power Protection 3.26.1 General Application Due to various reasons lead to lose motivity, synchronous generator is changed to run as a motor state, Absorbing energy from the power grid to drive a turbine (gas turbine) operation. In order to prevent turbine blade or gas turbine gear from being damaged, reverse power protection (reversal direction) should be configured. 3.26.2 Function Description Reverse power protection provides two stages: stage 1 can be set as alarm purpose or tripping purpose, and stage 2 is only for tripping purpose. When reverse power value of the generator detected is greater than reverse power protection setting ([32R1.P_Set]), reverse power protection can operate to alarm or trip with the time delay. After overload protection, over-excitation protection or loss-of-excitation protection, such as abnormal operation protection operates, the generator needs sequential tripping. The steam valve of turbine has to be closed firstly, and sequential tripping reverse power protection blocked by position contact of steam valve and circuit breaker operates to trip with the time delay. Generator power is calculated by three-phase voltage and three-phase current of generator terminal. Positive sequence component of active power is calculated by fundamental wave of the voltage and current. The benefits is that reverse power protection is independent of the asymmetric component, so as to truly reflect the load of the engine power system. The level of generator absorbing the active power will depend on the need to overcome the friction loss, according to different types of generator units, the settings of reverse power protection will be different. During testing in the primary side of the generator unit, the active power absorbed by the generator can be measured by the device. 3-202 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory When the device is equipped with power plant side, reverse power is negative value, and reverse power is positive value when it is equipped with substation side. The operation criterion: [32R.Opt_Dir]=Reverse & P<-[32Ri.P_Set] or [32R.Opt_Dir]=Forward & P>[32Ri.P_Set] 3.26.3 Function Block Diagram 32R 32Ri.En P1 32Ri.Blk 32Ri.On 32Ri.St 32Ri.Op 32R1.Alm 3.26.4 I/O Signals Table 3.26-1 I/O signals of reverse power protection No. Input Signal 1 32Ri.En 2 32Ri.Blk No. Description Enable stage i of reverse power protection input 1, it is triggered from binary input or programmable logic etc. (i=1, 2) Stage i of reverse power protection blocking input, it is triggered from binary input or programmable logic etc. (i=1, 2) Output Signal Description 1 P1 Positive-sequence active power 2 32Ri.On Stage i of reverse power protection is enabled. (i=1, 2) 3 32Ri.St Stage i of reverse power protection starts. (i=1, 2) 4 32Ri.Op Stage i of reverse power protection operates to trip. (i=1, 2) 5 32R1.Alm Stage 1 of reverse power protection operates to alarm. (i=1, 2) 3-203 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.26.5 Logic SIG 32R1.En & SIG 32R1.Blk & EN [32R1.En_Alm] EN [32R1.En_Trp] 32R1.On >=1 SIG 32R1.On SET [32R.Opt_Dir]=Reverse & & SIG P1<-[32R1.P_Set] SET [32R.Opt_Dir]=Forward 32R1.St >=1 & SIG P1>[32R1.P_Set] & EN [32R1.t_Alm] 0s 32R1.Alm [32R1.t_Trp] 0s 32R1.Op [32R1.En_Alm] & EN [32R1.En_Trp] Figure 3.26-1 Logic diagram of stage 1 of reverse power protection SIG 32R2.En & & SIG 32R2.Blk EN 32R2.On [32R2.En_Trp] SIG 32R2.On & SET [32R.Opt_Dir]=Reverse 32R2.St & >=1 SIG P1<-[32R2.P_Set] SET [32R.Opt_Dir]=Forward & SIG P1>[32R2.P_Set] & [32R2.t_Trp] EN 0s 32R2.Op [32R2.En_Trp] Figure 3.26-2 Logic diagram of stage 2 of reverse power protection When stage 2 of reverse power protection is used as sequential tripping reverse power protection, it can be selectable to be controlled by position contact of steam valve and circuit breaker 3-204 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.26.6 Settings Table 3.26-2 Settings of broken conductor protection No. Name Range Step Unit Remark Power setting of stage i of reverse 1 32Ri.P_Set (0.100~50.000)×In 0.01 W power protection (i=1, 2) It should be greater 0.5 times the measured value of reverse power. 2 32Ri.t_Trp 0.100~3000.000 0.01 s 3 32R1.t_Alm 0.100~3000.000 0.01 s Time delay of stage i of reverse power protection for tripping purpose (i=1, 2) Time delay of stage 1 of reverse power protection for alarm purpose Enabling/disabling stage i of reverse power protection to operate to trip (i=1, 4 32Ri.En_Trp 0 or 1 2) 0: disable 1: enable Enabling/disabling stage 1 of reverse 5 32R1.En_Alm power protection to operate to alarm 0 or 1 0: disable 1: enable 6 32R.Opt_Dir The Forward directionality direction Reverse or option reverse (forward direction) of reverse power protection 3.27 Synchrocheck 3.27.1 General Application The purpose of synchrocheck is to ensure two systems are synchronism before they are going to be connected. When two asynchronous systems are connected together, due to phase difference between the two systems, larger impact will be led to the system during closing. Thus auto-reclosing and manual closing are applied with the synchrocheck to avoid this situation and maintain the system stability. The synchrocheck includes synchronism check and dead charge check. NOTICE! For double circuit breakers mode, the device will provide independent synchrocheck function for CB1 and CB2 respectively. Both synchrocheck functions have the same logic. The difference is that the prefix “CBx.” is added to all signals and settings for circuit breaker No.x (x=1 or 2). 3.27.2 Function Description The synchronism check function is mainly to measure the electrical quantities between both sides 3-205 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory of the circuit breaker and compares them with the corresponding settings. The output is only given if all measured quantities are simultaneously within their set limits. The dead charge check function measures the amplitude of line voltage and bus voltage between both sides of the circuit breaker, and then compare them with the live check setting [CBx.25.U_Lv] and the dead check setting [CBx.25.U_Dd]. The output is only given when the measured quantities comply with the criteria. The synchrocheck in this device can be used for auto-reclosing and manual closing for both single circuit breaker and dual circuit breakers. When applied for single circuit breaker, the comparison relationship between reference voltage (CBx.Uref) and synchronism voltage (CBx.Usyn) for synchronism check is as shown in Figure 3.27-1. CBx.Uref CBx.Usyn Figure 3.27-1 Relationship between reference voltage and synchronism voltage When both line and busbar are live, the synchronism check element operates if voltage difference, phase angle difference and frequency difference are all within their setting values. 1. The voltage difference is checked by the following equations. CBx.Usyn≥[CBx.25.U_Lv] CBx.Uref≥[CBx.25.U_Lv] [CBx.25.U_Diff]≥|CBx.Usyn-CBx.Uref| 2. The phase difference is checked by the following equations. CBx.Usyn×CBx.Uref×cosØ≥0 CBx.Usyn×CBx.Uref×sin([CBx.25.phi_Diff])≥CBx.Usyn×CBx.Uref×|sinØ| Where, Ø is phase difference between Usyn and Uref 3. The frequency difference is checked by the following equations. |f(CBx.Usyn)-f(CBx.Uref)|≤[CBx.25.f_Diff] If frequency check is disabled (i.e. [CBx.25.En_fDiffChk] is set as “0”), a detected maximum slip cycle can also be determined by the following equation based on phase difference setting and the 3-206 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory synchronism check time setting: f =[CBx.25.phi_Diff]/(180×[CBx.25.t_SynChk]) Where: f is slip cycle If frequency check is enabled (i.e. [CBx.25.En_fDiffChk] is set as “1”), [CBx.25.t_SynChk] can be set to be a very small value (default value is 50ms). This function module supports voltage switching. In general, voltage switching is fulfilled by external circuit, and the busbar arrangement should be determined, including three options, single busbar arrangement, double busbars arrangement and 1½ breakers arrangement, if using this module to fulfill voltage switching. Analog input defines four voltage inputs, UL1, UB1, UL2, UB2, and their usage are as follow: UL1: it connects with three-phase protection voltages (from line or busbar), which mainly are used by distance protection, voltage protection and so on. UB1: it connects with single synchronism voltage (from line or busbar). UL2: it connects with single synchronism voltage (from the other line of the same diameter in 1½ breakers arrangement). When voltage switching is available, it is only used by 1½ breakers arrangement. UB2: it connects with single synchronism voltage (from busbar). When voltage switching is available, it is only used by double busbars arrangement and 1½ breakers arrangement. The reference voltage (Uref) is determined to use phase voltage or phase-to-phase voltage (UL1) from three-phase protection voltages and by the setting [CBx.25.Opt_Source_UL1]. The synchronism voltage (Usyn) always connects with UB1 if not adopting voltage switching. It connects with one of UB1, UL2 and UB2 according to the result of voltage switching if adopting voltage switching. 3.27.2.1 Single Busbar Arrangement Voltage selection function is not required for this busbar arrangement, the connection of the voltage signals and respective VT MCB auxiliary contacts to the device is shown in the Figure 3.27-2 and Figure 3.27-3. 1. Three-phase bus voltage used for protection ([VTS.En_LineVT]=0) 3-207 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Bus Ua UL1 CB Ub Uc 25.MCB_VT_UL1 UB1 25.MCB_VT_UB1 Line Figure 3.27-2 Voltage connection for single busbar arrangement 2. Three-phase line voltage used for protection ([VTS.En_LineVT]=1) Bus CB UB1 25.MCB_VT_UB1 Ua UL1 Ub Uc 25.MCB_VT_UL1 Line Figure 3.27-3 Voltage connection for single busbar arrangement In the figures, the setting [VTS.En_LineVT] is used to determine protection voltage signals (Ua, Ub, Uc) from line VT or bus VT according to the condition. 3-208 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.27.2.2 Double Busbars Arrangement Bus2 Bus1 B1D B2D UB1 25.MCB_VT_UB1 UB2 25.MCB_VT_UB2 25.NC_UB1DS 25.NO_UB1DS CB 25.NC_UB2DS 25.NO_UB2DS Ua UL1 Ub Line Uc 25.MCB_VT_UL1 Figure 3.27-4 Voltage connection for double busbars arrangement For double busbars arrangement, selection of appropriate voltage signals from Bus 1 and Bus 2 for synchronizing are required. Line VT signal is taken as reference to check synchronizing with the voltage after voltage selection function. Selection approach is as follows. For the disconnector positions, the normally open (NO) and normally closed (NC) contacts of the disconnector for bus 1 and bus 2 are required to determine the disconnector open and closed positions. The voltage selection logic is as follows. BI 25.NO_UB1DS & CBx.UB1_Sel BI 25.NC_UB1DS BI 25.NO_UB2DS BI 25.NC_UB2DS & CBx.UB2_Sel & CBx.Alm_Invalid_Sel UB1 CBx.Usyn UB2 Figure 3.27-5 Voltage selection for double busbars arrangement After acquiring the disconnector open and closed positions of double busbars, use the following 3-209 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory logic to acquire the feeder voltage of double busbars. DS2 CLOSED DS2 OPEN DS1 CLOSED Keep original value Voltage from Bus 1 VT (CBx.UB1_Sel=1) DS1 OPEN Voltage from Bus 2 VT (CBx.UB2_Sel=1) Keep original value DS1 is disconnector of Bus 1 DS2 is disconnector of Bus 2 If voltage selection is invalid (CBx.Alm_Invalid_Sel=1), keep original selection and without switchover. 3.27.2.3 One and A Half Breakers Arrangement For one and a half breakers arrangement, selection of appropriate voltage signals among Line1 VT, Line2 VT and Bus 2 VT as reference voltage to check synchronizing with Bus 1 voltage signal for closing breaker at Bus 1 side. Bus1 UB1 25.MCB_VT_UB1 25.NC_UB1DS B1D 25.NO_UB1DS Ua UL1 Line 1 Ub Uc 25.MCB_VT_UL1 L1D 25.NC_UL1DS 25.NO_UL1DS Line 2 UL2 25.MCB_VT_UL2 25.NC_UL2DS 25.NO_UL2DS L2D 25.NC_UB2DS 25.NO_UB2DS UB2 25.MCB_VT_UB2 B2D Bus2 Figure 3.27-6 Voltage connection for one and a half breakers arrangement For the circuit breaker at bus side (take bus breaker of bus 1 as an example), the device acquires 3-210 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory the disconnector open and closed positions of two feeders and bus 2. The voltage selection logic is as follows. BI 25.NO_UL1DS & CBx.UL1_Sel BI 25.NC_UL1DS BI 25.NO_UL2DS BI 25.NC_UL2DS BI 25.NO_UB2DS BI 25.NC_UB2DS & CBx.UL2_Sel & & CBx.UB2_Sel & & CBx.Alm_Invalid_Sel UL1 CBx.Uref UL2 UB2 UB1 CBx.Usyn Figure 3.27-7 Voltage selection for one and a half breakers arrangement For the tie breaker, the device acquires the disconnector open and closed positions of two feeders and two busbars. Either Line 1 VT or Bus 1 VT signal is selected as reference voltage to check synchronizing with the selected voltage between Line 2 VT and Bus 2 VT. The voltage selection logic is as follows. 3-211 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory BI 25.NO_UL1DS & CBx.UL1_Sel BI 25.NC_UL1DS BI 25.NO_UB1DS BI 25.NC_UB1DS & CBx.UB1_Sel & & UL1 CBx.Uref UB1 BI 25.NO_UL2DS BI 25.NC_UL2DS BI 25.NO_UB2DS BI 25.NC_UB2DS & CBx.UL2_Sel & CBx.UB2_Sel & >=1 & UL2 CBx.Alm_Invalid_Sel CBx.Usyn UB2 Figure 3.27-8 Voltage selection for one and a half breakers arrangement When the voltage selection fails (including VT circuit failure and MCB failure), the device will issue the corresponding failure signal. If the voltage selection is invalid (CBx.Alm_Invalid_Sel=1), keep original selection and without switchover. In order to simplify description, one of the two voltages used in the synchrocheck (synchronism check and dead charge check) which obtained after voltage selection function is regarded as line voltage, and another is bus voltage. 3.27.2.4 Synchronism Voltage Circuit Failure Supervision If synchronism voltage and reference voltage are used for auto-reclosing with synchronism or dead line or busbar check, the VT circuit of synchronism voltage and reference voltage are monitored. Under normal conditions, the circuit breaker is in closed position but the synchronism voltage is lower than the setting [CBx.25.U_Lv], it means that synchronism voltage circuit fails and an alarm [CBx.25.Alm_VTS_Usyn] or [CBx.25.Alm_VTS_Uref] will be issued with a time delay [VTS.t_DPU]. If MCB of synchronism voltage or reference voltage is open, an alarm [CBx.25.Alm_VTS_Usyn] or [CBx.25.Alm_VTS_Uref] will be issued instantaneously. After synchronism voltage reverted to normal condition, the alarm will be reset automatically with a time delay [VTS.t_DDO]. When synchronism voltage circuit failure is detected, dead check in auto-reclosing logic will be disabled. If the logic setting [CBx.25.En_NoChk] is set as “1”, synchronism voltage circuit failure supervision 3-212 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory will be disabled. & SIG FD.Pkp >=1 SIG CBx.79.Inprog >=1 SIG CBx.52b_PhA >=1 & SIG CBx.52b_PhB SIG CBx.52b_PhC If the signal [FD.Pkp] or [CBx.79.Inprog] operates, the circuit of time delay will be interrupted. SIG CBx.Uref<[CBx.25.U_Lv] [VTS.t_DPU] [VTS.t_DDO] >=1 >=1 CBx.25.Alm_VTS_Uref & BI 25.MCB_VT_Uref SIG CBx.25.On_NoChk & SIG CBx.25.On_SynChk >=1 SIG CBx.25.On_DdL_DdB >=1 SIG CBx.25.On_DdL_LvB & SIG CBx.25.On_LvL_DdB SIG CBx.25.Blk_VTS_UL Figure 3.27-9 Reference voltage circuit failure supervision logic & SIG FD.Pkp >=1 SIG CBx.79.Inprog >=1 SIG CBx.52b_PhA >=1 & SIG CBx.52b_PhB If the signal [FD.Pkp] or [CBx.79.Inprog] operates, the circuit of time delay will be interrupted. SIG CBx.52b_PhC [VTS.t_DPU] [VTS.t_DDO] SIG CBx.Usyn<[CBx.25.U_Lv] >=1 >=1 & CBx.25.Alm_VTS_Usyn BI 25.MCB_VT_Usyn SIG CBx.25.On_NoChk & SIG CBx.25.On_SynChk SIG CBx.25.On_DdL_DdB >=1 >=1 SIG CBx.25.On_DdL_LvB & SIG CBx.25.On_LvL_DdB SIG CBx.25.Blk_VTS_UL Figure 3.27-10 Synchronism voltage circuit failure supervision logic As shown in Figure 3.27-9 and Figure 3.27-10, 25.MCB_VT_Uref is MCB signal corresponding to reference voltage after switching and 25.MCB_VT_Usyn is MCB signal corresponding to synchronism voltage after switching. 3-213 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.27.3 Function Block Diagram 25 CBx.25.Blk_Chk CBx.UL1_Sel CBx.25.Blk_SynChk CBx.UL2_Sel CBx.25.Blk_DdChk CBx.UB1_Sel CBx.25.Start_Chk CBx.UB2_Sel CBx.25.Start_3PLvChk CBx.25.Sel_SynChk CBx.Alm_Invalid_Sel CBx.25.Ok_fDiffChk CBx.25.Sel_DdL_DdB CBx.25.Ok_UDiffChk CBx.25.Sel_DdL_LvB CBx.25.Ok_phiDiffChk CBx.25.Sel_LvL_DdB CBx.25.Ok_DdL_DdB CBx.25.Sel_NoChk CBx.25.Ok_DdL_LvB CBx.25.Blk_VTS_Uref CBx.25.Ok_LvL_DdB CBx.25.Blk_VTS_Usyn CBx.25.Chk_LvL 25.MCB_VT_UL1 CBx.25.Chk_DdL 25.MCB_VT_UL2 CBx.25.Chk_LvB 25.MCB_VT_UB1 CBx.25.Chk_DdB 25.MCB_VT_UB2 CBx.25.Ok_DdChk 25.NC_UL1DS CBx.25.Ok_SynChk 25.NO_UL1DS CBx.25.Ok_Chk 25.NC_UB1DS CBx.25.Ok_3PLvChk 25.NO_UB1DS CBx.25.Alm_VTS_Uref 25.NC_UL2DS CBx.25.Alm_VTS_Usyn 25.NO_UL2DS CBx.25.f_Ref 25.NC_UB2DS CBx.25.f_Syn 25.NO_UB2DS CBx.25.U_Diff CBx.25.f_Diff CBx.25.Phi_Diff 3-214 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.27.4 I/O Signals Table 3.27-1 I/O signals of synchrocheck No. Input Signal Description 1 CBx.25.Blk_Chk 2 CBx.25.Blk_SynChk 3 CBx.25.Blk_DdChk 4 CBx.25.Start_Chk 5 CBx.25.Start_3PLvChk 6 CBx.25.Sel_SynChk Synchronism check is selected. 7 CBx.25.Sel_DdL_DdB Dead line and dead bus check is selected. 8 CBx.25.Sel_DdL_LvB Dead line and live bus check is selected. 9 CBx.25.Sel_LvL_DdB Live line and live bus check is selected. 10 CBx.25.Sel_NoChk No check is selected. 11 CBx.25.Blk_VTS_Usyn VT circuit supervision (Usyn) is blocked 12 CBx.25.Blk_VTS_Uref VT circuit supervision (Uref) is blocked 13 25.MCB_VT_UL1 Binary input for VT MCB auxiliary contact (UL1) 14 25.MCB_VT_UL2 Binary input for VT MCB auxiliary contact (UL2) 15 25.MCB_VT_UB1 Binary input for VT MCB auxiliary contact (UB1) 16 25.MCB_VT_UB2 Binary input for VT MCB auxiliary contact (UB2) 17 25.NC_UL1DS Normally closed contact of disconnector (UL1) 18 25.NO_UL1DS Normally open contact of disconnector (UL1) 19 25.NC_UB1DS Normally closed contact of disconnector (UB1) 20 25.NO_UB1DS Normally open contact of disconnector (UB1) 21 25.NC_UL2DS Normally closed contact of disconnector (UL2) 22 25.NO_UL2DS Normally open contact of disconnector (UL2) 23 25.NC_UB2DS Normally closed contact of disconnector (UB2) 24 25.NO_UB2DS Normally open contact of disconnector (UB2) No. Input signal of blocking synchrocheck function for AR. Input signal of blocking synchronism check for AR. If the value is “1”, the output of synchronism check is “0”. Input signal of blocking dead charge check for AR. Input signal of starting synchronism check, usually it was starting signal of AR from auto-reclosing module. Input signal of starting live three-phase check, usually it was starting signal of 1-pole AR Output Signal Description 1 CBx.UL1_Sel To select voltage of Line 1 2 CBx.UL2_Sel To select voltage of Line 2 3 CBx.UB1_Sel To select voltage of Bus 1 4 CBx.UB2_Sel To select voltage of Bus 2 5 CBx.Alm_Invalid_Sel Voltage selection is invalid. 6 CBx.25.Ok_fDiffChk 7 CBx.25.Ok_UDiffChk 8 CBx.25.Ok_phiDiffChk To indicate that frequency difference condition for synchronism check of AR is met, frequency difference between UB and UL is smaller than [25.f_Diff]. To indicate that voltage difference condition for synchronism check of AR is met, voltage difference between UB and UL is smaller than [25.U_Diff] To indicate phase difference condition for synchronism check of AR is met, phase difference between UB and UL is smaller than [25.phi_Diff]. 3-215 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 9 CBx.25.Ok_DdL_DdB Dead line and dead bus condition is met 10 CBx.25.Ok_DdL_LvB Dead line and live bus condition is met 11 CBx.25.Ok_LvL_DdB Live line and dead bus condition is met 12 CBx.25.Chk_LvL Line voltage is greater than the voltage setting [25.U_Lv] 13 CBx.25.Chk_DdL Line voltage is smaller than the voltage setting [25.U_Dd] 14 CBx.25.Chk_LvB Bus voltage is greater than the voltage setting [25.U_Lv] 15 CBx.25.Chk_DdB Bus voltage is smaller than the voltage setting [25.U_Dd] 16 CBx.25.Ok_DdChk To indicate that dead charge check condition of AR is met 17 CBx.25.Ok_SynChk To indicate that synchronism check condition of AR is met 18 CBx.25.Ok_Chk To indicate that synchrocheck condition of AR is met 19 CBx.25.Ok_3PLvChk To indicate that live three-phase check condition is met 20 CBx.25.Alm_VTS_Uref Reference voltage circuit is abnormal 21 CBx.25.Alm_VTS_Usyn Synchronism voltage circuit is abnormal 22 CBx.25.f_Ref Frequency of the voltage used by protection calculation 23 CBx.25.f_Syn Frequency of the voltage used by synchrocheck 24 CBx.25.U_Diff Voltage difference for synchronism check 25 CBx.25.f_Diff Frequency difference for synchronism check 26 CBx.25.phi_Diff Phase difference for synchronism check 3.27.5 Logic 3.27.5.1 Synchronism Check Logic The frequency difference, voltage difference, and phase difference of voltages from both sides of the circuit breaker are calculated in the device, they are used as input conditions of the synchronism check. When the synchronism check function is enabled and the voltages of both ends meets the requirements of the voltage difference, phase difference, and frequency difference, and there is no synchronism check blocking signal, it is regarded that the synchronism check conditions are met. Synchronism check logic is usually used for 3-pole AR, and 1-pole AR usually adopts no check logic. However, the circuit breaker at local end can not reclosed unless the circuit breaker at remote end is reclosed successfully. In order to meet this requirement, live three-phase check can be used for 1-pole AR, determined by the setting [CBx.25.En_3PLvChk], ensure that three-phase voltages is restored to normal at local end after the circuit breaker at remote end is reclosed. Synchrocheck mode can be determined by the setting [CBx.25.SetOpt] or external signal. As shown in Figure 3.27-11, when the setting [CBx.25.SetOpt] is set as “1”, synchrocheck mode is determined by the setting. Otherwise, synchrocheck mode is determined by external signal. 3-216 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 1 EN [CBx.25.En_SynChk] SIG CBx.25.Sel_SynChk EN [CBx.25.SetOpt] EN [CBx.25.En_DdL_DdB] SIG CBx.25.Sel_SynChk EN [CBx.25.SetOpt] EN [CBx.25.En_LvL_DdB] SIG CBx.25.Sel_LvL_DdB EN [CBx.25.SetOpt] EN [CBx.25.En_DdL_LvB] CBx.25.On_SynChk 0 1 CBx.25.On_DdL_DdB 0 1 CBx.25.On_LvL_DdB 0 1 CBx.25.On_DdL_LvB SIG CBx.25.Sel_DdL_LvB EN [CBx.25.SetOpt] EN [CBx.25.En_NoChk] SIG CBx.25.Sel_NoChk EN [CBx.25.SetOpt] 0 1 CBx.25.On_NoChk 0 Figure 3.27-11 Synchrocheck mode selection EN [CBx.25.En_3PLvChk] SIG CBx.Uref.a>[CBx.25.U_Lv] >=1 & SIG CBx.Uref.b>[CBx.25.U_Lv] SIG CBx.Uref.c>[CBx.25.U_Lv] & 200ms SIG CBx.25.Start_3PLvChk SIG CBx.25.Blk_Chk 0ms CBx.25.Ok_3PLvChk >=1 & SIG CBx.25.Blk_SynChk & SIG CBx.25.On_SynChk SIG CBx.25.Start_Chk SIG CBx.Usyn>[CBx.25.U_Lv] SIG CBx.Uref>[CBx.25.U_Lv] & & 50ms 0ms & [CBx.25.t_SynChk] 0ms CBx.25.Ok_SynChk SIG CBx.25.Ok_UdiffChk SIG CBx.25.Ok_phiDiffChk SIG CBx.25.Ok_fDiffChk Figure 3.27-12 Synchronism check 3-217 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.27.5.2 Dead Charge Check Logic The dead charge check conditions have three types, namely, live-bus and dead-line check, dead-bus and live-line check and dead-bus and dead-line check. The above three modes can be enabled and disabled by the corresponding logic settings. The device can calculate the measured bus voltage and line voltage at both sides of the circuit breaker and compare them with the settings [CBx.25.U_Lv] and [CBx.25.U_Dd]. When the voltage is higher than [CBx.25.U_Lv], the bus/line is regarded as live. When the voltage is lower than [CBx.25.U_Dd], the bus/line is regarded as dead. SIG CBx.25.Blk_Chk SIG CBx.25.Blk_DdChk SIG CBx.25.Start_Chk SIG CBx.25.On_DdL_DdB SIG CBx.Uref<[CBx.25.U_Dd] SIG CBx.Usyn<[CBx.25.U_Dd] SIG CBx.25.On_DdL_LvB SIG CBx.Uref<[CBx.25.U_Dd] SIG CBx.Usyn>[CBx.25.U_Lv] SIG CBx.25.On_LvL_DdB SIG CBx.Uref>[CBx.25.U_Lv] SIG CBx.Usyn<[CBx.25.U_Dd] SIG CBx.25.Alm_VTS_Usyn SIG CBx.25.Alm_VTS_Uref >=1 & >=1 & [CBx.25.t_DdChk] 0 CBx.25.Ok_DdChk & CBx.25.Ok_DdL_DdB & & CBx.25.Ok_DdL_LvB & & CBx.25.Ok_LvL_DdB & >=1 Figure 3.27-13 Dead charge check logic 3.27.5.3 Synchrocheck Logic SIG CBx.25.Ok_SynChk SIG CBx.25.On_NoChk SIG CBx.25.Ok_DdChk >=1 CBx.25.Ok_Chk Figure 3.27-14 Synchrocheck logic 3-218 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.27.6 Settings Table 3.27-2 Synchrocheck settings No. Name Range Step Ua: A-phase voltage Ub CBx.25.Opt_Source_UL1 Ub: B-phase voltage Uc Uc: C-phase voltage Uab Uab: AB-phase voltage Ubc Ubc: BC-phase voltage Uca Uca: CA-phase voltage Voltage selecting mode of bus 1. Ua Ua: A-phase voltage Ub 2 CBx.25.Opt_Source_UB1 Ub: B-phase voltage Uc Uc: C-phase voltage Uab Uab: AB-phase voltage Ubc Ubc: BC-phase voltage Uca Uca: CA-phase voltage Voltage selecting mode of line 2. Ua Ua: A-phase voltage Ub 3 CBx.25.Opt_Source_UL2 Ub: B-phase voltage Uc Uc: C-phase voltage Uab Uab: AB-phase voltage Ubc Ubc: BC-phase voltage Uca Uca: CA-phase voltage Voltage selecting mode of bus 2. Ua Ua: A-phase voltage Ub 4 CBx.25.Opt_Source_UB2 Remark Voltage selecting mode of line 1. Ua 1 Unit Ub: B-phase voltage Uc Uc: C-phase voltage Uab Uab: AB-phase voltage Ubc Ubc: BC-phase voltage Uca Uca: CA-phase voltage Option of circuit breaker configuration, and it should be set as “NoVoltSel” if no voltage selection is adopted. NoVoltSel DblBusOneCB 5 CBx.CBConfigMode DblBusOneCB: one circuit breaker for double busbar 3/2BusCB 3/2BusCB: 3/2TieCB bus side circuit breaker for one and a half breakers 3/2TieCB: line side circuit 3-219 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory No. Name Range Step Unit Remark breaker for one and a half breakers 6 CBx.25.U_Dd 0.05Un~0.8Un 0.001 V Voltage threshold of dead check 7 CBx.25.U_Lv 0.5Un~Un 0.001 V Voltage threshold of live check 8 CBx.25.K_Usyn 0.20-5.00 9 CBx.25.phi_Diff 0~ 89 1 deg 10 CBx.25.phi_Comp 0~359 1 deg Compensation coefficient for synchronism voltage Phase difference limit of synchronism check for AR Compensation difference for phase between two synchronism voltages 11 CBx.25.f_Diff 0.02~1.00 0.01 Hz 12 CBx.25.U_Diff 0.02Un~0.8Un V 13 CBx.25.t_DdChk 0.010~25.000 s 14 CBx.25.t_SynChk 0.010~25.000 s Frequency difference limit of synchronism check for AR Voltage difference CBx.25.En_fDiffChk of synchronism check for AR Time delay to confirm dead check condition Time delay to confirm synchronism check condition Enabling/disabling 15 limit frequency difference check 0 or 1 0: disable 1: enable Synchrocheck mode selection 16 CBx.25.SetOpt 0, 1 1 0: determined by external signal 1: determined by the setting Enabling/disabling synchronism 17 CBx.25.En_SynChk check 0 or 1 0: disable 1: enable Enabling/disabling dead line and 18 CBx.25.En_DdL_DdB dead bus (DLDB) check 0 or 1 0: disable 1: enable Enabling/disabling dead line and 19 CBx.25.En_DdL_LvB live bus (DLLB) check 0 or 1 0: disable 1: enable Enabling/disabling live line and 20 CBx.25.En_LvL_DdB dead bus (LLDB) check 0 or 1 0: disable 1: enable 3-220 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory No. Name Range Step Unit Remark Enabling/disabling AR without 21 CBx.25.En_NoChk any check 0 or 1 0: disable 1: enable Enabling/disabling 22 CBx.25.En_3PLvChk live three-phase check of line 0 or 1 0: disable 1: enable 3.28 Automatic Reclosure 3.28.1 General Application To maintain the integrity of the overall electrical transmission system, the device is installed on the transmission system to isolate faulted segments during system disturbances. Faults caused by lightning, wind, or tree branches could be transient in nature and may disappear once the circuit is de-energized. According to statistics, for overhead transmission line, 80%~90% of the faults on overhead lines are the transient faults. Auto-reclosing systems are installed to restore the faulted section of the transmission system once the fault is extinguished (providing it is a transient fault). For certain transmission systems, auto-reclosure is used to improve system stability by restoring critical transmission paths as soon as possible. Besides overhead lines, other equipment failure, such as cables, busbar, transformer fault and so on, are generally permanent fault, and auto-reclosing is not initiated after faulty feeder is tripped. For some mixed circuits, such as overhead line with a transformer unit, hybrid transmission lines, etc., it is required to ensure that auto-reclosing is only initiated for faults overhead line section, or make a choice according to the situation. NOTICE! For double circuit breakers mode, the device will provide independent automatic reclosure function for CB1 and CB2 respectively. Both automatic reclosure functions have the same logic. The difference is that the prefix “CBx.” is added to all signals and settings for circuit breaker No.x (x=1 or 2). 3.28.2 Function Description This auto-reclosing logic can be used with either integrated device or external device. When the auto-reclosure is used with integrated device, the internal protection logic can initiate AR, moreover, a tripping contact from external device can be connected to the device via opto-coupler input to initiate integrated AR function. When external auto-reclosure is used, the device can output some configurable output to initiate external AR, such as, contact of initiating AR, phase-segregated tripping contact, single-phase tripping contact, three-phase tripping contact and contact of blocking AR. According to requirement, these contacts can be selectively connected to external auto-reclosure device to initiate AR. 3-221 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory For phase-segregated circuit breaker, AR mode can be 1-pole AR for single-phase fault and 3-pole AR for multi-phase fault, or always 3-pole AR for any kinds of fault according to system requirement. For persistent fault or multi-shot AR number preset value is reached, the device will send final tripping command. The device will provide appropriate tripping command based on faulty phase selection if adopting 1-pole AR. AR can be enabled or disabled by logic setting or external signal via binary input. When AR is enabled, the device will output contact [CBx.79.On], otherwise, output contact [CBx.79.Off]. After some reclosing conditions, such as, CB position, CB pressure and so on, is satisfied, the device will output contact [CBx.79.Ready]. According to requirement, the device can be set as one-shot or multi-shot AR. When adopting multi-shot AR, the AR mode of first time reclosing can be set as 1-pole AR, 3-pole AR or 1/3-pole AR. The rest AR mode is only 3-pole AR and its number is determined by the maximum 3-pole reclosing number. For one-shot AR or first reclosing of multi-shot AR, AR mode can be selected by logic setting [CBx.79.En_1PAR], [CBx.79.En_3PAR] and [CBx.79.En_1P/3PAR] or external signal via binary inputs. When 3-pole or 1/3-pole AR mode is selected, the following three types of check modes can be selected: dead charge check, synchronism check and no check. 3-222 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.28.3 Function Block Diagram 79 CBx.79.En CBx.79.On CBx.79.Blk CBx.79.Off CBx.79.Sel_1PAR CBx.79.Close CBx.79.Sel_3PAR CBx.79.Ready CBx.79.Sel_1P/3PAR CBx.79.AR_Blkd CBx.79.Trp CBx.79.Active CBx.79.Trp3P CBx.79.Inprog CBx.79.TrpA CBx.79.Inprog_1P CBx.79.TrpB CBx.79.Inprog_3P CBx.79.TrpC CBx.79.Inprog_3PS1 CBx.79.LockOut CBx.79.Inprog_3PS2 CBx.79.PLC_Lost CBx.79.Inprog_3PS3 CBx.79.WaitMaster CBx.79.Inprog_3PS4 CBx.79.CB_Healthy CBx.79.WaitToSlave CBx.79.Clr_Counter CBx.79.Perm_Trp1P CBx.79.Ok_Chk CBx.79.Perm_Trp3P CBx.79.Ok_3PLvChk CBx.79.Rcls_Status CBx.79.Fail_Rcls CBx.79.Succ_Rcls CBx.79.Fail_Chk CBx.79.Mode_1PAR CBx.79.Mode_3PAR CBx.79.Mode_1/3PAR 3.28.4 I/O Signals Table 3.28-1 I/O signals of auto-reclosing No. Input Signal 1 CBx.79.En 2 CBx.79.Blk Description Binary input for enabling AR. If the logic setting [79.En_ExtCtrl]=1, enabling AR will be controlled by the external signal via binary input Binary input for disabling AR. If the logic setting [79.En_ExtCtrl]=1, disabling AR will be controlled by the external input 3-223 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Input signal for selecting 1-pole AR mode of corresponding circuit 3 CBx.79.Sel_1PAR 4 CBx.79.Sel_3PAR 5 CBx.79.Sel_1P/3PAR 6 CBx.79.Trp Input signal of single-phase tripping from line protection to initiate AR 7 CBx.79.Trp3P Input signal of three-phase tripping from line protection to initiate AR 8 CBx.79.TrpA Input signal of A-phase tripping from line protection to initiate AR 9 CBx.79.TrpB Input signal of B-phase tripping from line protection to initiate AR 10 CBx.79.TrpC Input signal of C-phase tripping from line protection to initiate AR breaker Input signal for selecting 3-pole AR mode of corresponding circuit breaker Input signal for selecting 1/3-pole AR mode of corresponding circuit breaker Input signal of blocking reclosing, usually it is connected with the 11 CBx.79.LockOut operating signals of definite-time protection, transformer protection and busbar differential protection, etc. 12 CBx.79.PLC_Lost 13 CBx.79.WaitMaster 14 CBx.79.CB_Healthy 15 CBx.79.Clr_Counter Clear the reclosing counter 16 CBx.79.Ok_Chk Synchrocheck condition of AR is met 17 CBx.79.Ok_3PLvChk Live three-phase check condition of AR is met No. Input signal of indicating the alarm signal that signal channel is lost Input signal of waiting for reclosing permissive signal from master AR (when reclosing multiple circuit breakers) The input for indicating whether circuit breaker has enough energy to perform the close function Output Signal Description 1 CBx.79.On Automatic reclosure is enabled 2 CBx.79.Off Automatic reclosure is disabled 3 CBx.79.Close Output of auto-reclosing signal 4 CBx.79.Ready Automatic reclosure have been ready for reclosing cycle 5 CBx.79.AR_Blkd Automatic reclosure is blocked 6 CBx.79.Active Automatic reclosing logic is actived 7 CBx.79.Inprog Automatic reclosing cycle is in progress 8 CBx.79.Inprog_1P The first 1-pole AR cycle is in progress 9 CBx.79.Inprog_3P 3-pole AR cycle is in progress 10 CBx.79.Inprog_3PS1 First 3-pole AR cycle is in progress 11 CBx.79.Inprog_3PS2 Second 3-pole AR cycle is in progress 12 CBx.79.Inprog_3PS3 Third 3-pole AR cycle is in progress 13 CBx.79.Inprog_3PS4 Fourth 3-pole AR cycle is in progress 14 CBx.79.WaitToSlave 15 CBx.79.Perm_Trp1P 16 CBx.79.Perm_Trp3P 17 CBx.79.Rcls_Status Waiting signal of automatic reclosing which will be sent to slave (when reclosing multiple circuit breakers) Single-phase circuit breaker will be tripped once protection device operates Three-phase circuit breaker will be tripped once protection device operates Automatic reclosure status 3-224 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 0: AR is ready. 1: AR is in progress. 2: AR is successful. 18 CBx.79.Fail_Rcls Auto-reclosing fails 19 CBx.79.Succ_Rcls Auto-reclosing is successful 20 CBx.79.Fail_Chk Synchrocheck for AR fails 21 CBx.79.Mode_1PAR Output of 1-pole AR mode 22 CBx.79.Mode_3PAR Output of 3-pole AR mode 23 CBx.79.Mode_1/3PAR Output of 1/3-pole AR mode Automatic reclosure counter 24 CBx.79.N_Total_Rcls Recorded number of all reclosing attempts 25 CBx.79.N_1PS1 Recorded number of first 1-pole reclosing attempts 26 CBx.79.N_3PS1 Recorded number of first 3-pole reclosing attempts 27 CBx.79.N_3PS2 Recorded number of second 3-pole reclosing attempts 28 CBx.79.N_3PS3 Recorded number of third 3-pole reclosing attempts 29 CBx.79.N_3PS4 Recorded number of fourth 3-pole reclosing attempts 3.28.5 Logic 3.28.5.1 AR Ready For the first reclosing of multi-shot AR, AR mode can be 1-pole AR or 3-pole AR, however, the selection is valid only to the first reclosing, after that it can only be 3-pole AR. When logic setting [CBx.79.SetOpt] is set as “1”, AR mode is determined by logic settings. When logic setting [CBx.79.SetOpt] is set as “0”, AR mode is determined by external signal via binary inputs. An auto-reclosure must be ready to operate before performing reclosing. The output signal [CBx.79.Ready] means that the auto-reclosure can perform at least one time of reclosing function, i.e., breaker open-close-open. When the device is energized or after the settings are modified, AR can not be ready unless the following conditions are met: 1. AR function is enabled. 2. The circuit breaker is ready, such as, normal storage energy and no low pressure signal. 3. The duration of the circuit breaker in closed position before fault occurrence is not less than the setting [CBx.79.t_CBClsd]. 4. There is no block signal of auto-reclosing. After the auto-reclosure operates, the auto-reclosure must reset, i.e., [CBx.79.Active]=0, in addition to the above conditions for reclosing again. When there is a fault on an overhead line, the concerned circuit breakers will be tripped normally. After fault is cleared, the tripping command will drop off immediately. In case the circuit breaker is in failure, etc., and the tripping signal of the circuit breaker maintains and in excess of the time delay [CBx.79.t_PersistTrp], AR will be blocked, as shown in Figure 3.28-1. 3-225 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory SIG Any tripping signal SIG CBx.79.LockOut SIG 1-pole AR Initiation SIG Any tripping signal EN [CBx.79.En_PDF_Blk] SIG CBx.79.Sel_1PAR EN [CBx.79.N_Rcls]=1 SIG Three phase trip SIG Phase A open SIG Phase B open [CBx.79.t_PersistTrp] 0ms >=1 0ms [CBx.79.t_DDO_BlkAR] [CBx.79.t_SecFault] 0ms >=1 CBx.79.AR_Blkd & & & >=1 & & >=1 & SIG Phase C open Figure 3.28-1 Logic diagram of AR block The input signal [CBx.79.CB_Healthy] must be energized before auto-reclosure gets ready. Because most circuit breakers can finish one complete process: open-closed-open, it is necessary that circuit breaker has enough energy before reclosing. When the time delay of AR is exhausted, AR will be blocked if the input signal [CBx.79.CB_Healthy] is still not energized within time delay [CBx.79.t_CBReady]. If this function is not required, the input signal [CBx.79.CB_Healthy] can be not to configure, and its state will be thought as “1” by default. In order to block AR reliably even if the signal of manually open circuit breaker not connected to the input of blocking AR, when the circuit breaker is open by manually and there is CB position input under normal conditions, AR will be blocked with the time delay of 100ms if AR is not initiated and no any trip signal. When auto-reclosure is blocked, auto-reclosing failure, synchrocheck failure or last shot is reached, or when the internal blocking condition of AR is met (such as, zone 3 of distance protection operates, the device operates for multi-phase fault, three-phase fault and so on. These flags of blocking AR have been configured in the device, additional configuration is not required.), auto-reclosure will be discharged immediately and next auto-reclosing will be disabled. When the input signal [CBx.79.LockOut] is energized, auto-reclosure will be blocked immediately. The blocking flag of AR will be also controlled by the internal blocking condition of AR. When the blocking flag of AR is valid, auto-reclosure will be blocked immediately. The logic of AR ready is shown in Figure 3.28-2. 3-226 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory >=1 SIG 3 CB closed [CBx.79.t_CBClsd] SIG CBx.79.Active >=1 SIG Any tripping signal 100ms & & & 100ms SIG CBx.79.Inprog SIG [CBx.79.CB_Healthy] 0ms SIG CBx.79.AR_Blkd >=1 SIG CBx.TRP.BlkAR SIG CBx.79.Fail_Rcls SIG CBx.79.Fail_Chk SIG Last shot is made EN [CBx.79.En] EN [CBx.79.En_ExtCtrl] SIG CBx.79.En SIG CBx.79.Blk [CBx.79.t_CBReady] 0 CBx.79.Ready & >=1 & >=1 & >=1 CBx.79.On & & Figure 3.28-2 Logic diagram of AR ready When a fault occurs under pole disagreement condition, blocking AR can be enabled or disabled. The time delay [CBx.79.t_SecFault] is used to discriminate another fault which begins after 1-pole AR initiated. AR will be blocked if another fault happens after this time delay if the logic setting [CBx.79.En_PDF_Blk] is set as “1”, and 3-pole AR will be initiated if [CBx.79.En_PDF_Blk] is set as “1”. AR will be blocked immediately once the blocking condition of AR appears, but the blocking condition of AR will drop off with a time delay [CBx.79.t_DDO_BlkAR] after blocking signal disappears. When one-shot and 1-pole AR is enabled, auto-reclosure will be blocked immediately if there are binary inputs of multi-phase CB position is energized. When any protection element operates to trip, the device will output a signal [CBx.79.Active] until AR drop off (Reset Command). Any tripping signal can be from external protection device or internal protection element. AR function can be enabled by internal logic settings of AR mode or external signal via binary inputs in addition to internal logic setting [CBx.79.En]. When logic setting [CBx.79.En_ExtCtrl] is set as “1”, AR enable are determined by external signal via binary inputs and logic settings. When logic setting [CBx.79.En_ExtCtrl] set as “0”, AR enable are determined only by logic settings. 3-227 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory For one-shot reclosing, if 1-pole AR mode is selected, auto-reclosure will reset when there is three-phase tripping signal or input signal of multi-phase open position. SIG CBx.79.On SIG CBx.79.Mode_3PAR SIG CBx.79.Ready SIG CBx.79.Trp SIG CBx.79.Trp3P SIG CBx.79.TrpA SIG CBx.79.TrpB SIG CBx.79.TrpC SIG Phase A open SIG Phase B open SIG Phase C open Logic CBx.79.Perm_Trp3P CBx.79.Perm_Trp1P Figure 3.28-3 Logic diagram of tripping condition output When AR is enabled, the device will output the signal [CBx.79.Perm_Trp3P] if AR is not ready, or AR mode is set as 3-Pole AR, or another fault occurs after the circuit breaker is open. 3.28.5.2 AR Initiation AR mode can be selected by external signal via binary inputs or internal logic settings. If the logic setting [CBx.79.SetOpt] set as “1”, AR mode is determined by the internal logic settings. If the logic settings [CBx.79.SetOpt] set as “0”, AR mode is determined by the external inputs. 1. AR initiated by tripping signal of line protection AR can be initiated by tripping signal of line protection, and the tripping signal may be from internal trip signal or external trip signal. When selecting 1-pole AR or 1/3-pole AR, line single-phase fault will trigger 1-pole AR. When AR is ready to reclosing (“CBx.79.Ready”=1) and the single-phase tripping command is received, this single-phase tripping command will be kept in the device, and 1-pole AR will be initiated after the single-phase tripping command drops off. The single-phase tripping command kept in the device will be cleared after the completion of auto-reclosing sequence (Reset Command). Its logic is shown in Figure 3.28-4. 3-228 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory SIG Reset Command & >=1 SIG Single-phase Trip & & SIG CBx.79.Ready 1-pole AR Initiation SIG CBx.79.Sel_1PAR SIG CBx.79.Sel_1P/3PAR >=1 Figure 3.28-4 Single-phase tripping initiating AR When selecting 3-pole AR or 1/3-pole AR, three-phase tripping will trigger 3-pole AR. When AR is ready to reclosing (“CBx.79.Ready”=1) and the three-phase tripping command is received, this three-phase tripping command will be kept in the device, and 3-pole AR will be initiated after the three-phase tripping command drops off. The three-phase tripping command kept in the device will be cleared after the completion of auto-reclosing sequence (Reset Command). Its logic is shown in Figure 3.28-5. SIG Reset Command & >=1 SIG Three-phase Trip & & SIG CBx.79.Ready 3-pole AR Initiation SIG CBx.79.Sel_3PAR SIG CBx.79.Sel_1P/3PAR >=1 Figure 3.28-5 Three-phase tripping initiating AR 2. AR initiated by CB state A logic setting [CBx.79.En_CBInit] is available for selection that AR is initiated by CB state. Under normal conditions, when AR is ready to reclosing (“CBx.79.Ready”=1), AR will be initiated if circuit breaker is open and corresponding phase current is nil. AR initiated by CB state can be divided into initiating 1-pole AR and 3-pole AR, their logics are shown in Figure 3.28-6 and Figure 3.28-7 respectively. Usually normally closed contact of circuit breaker is used to reflect CB state. 3-229 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory SIG Phase A open SIG Phase B open >=1 & & SIG Phase C open EN [CBx.79.En_CBInit] SIG CBx.79.Ready SIG CBx.79.Sel_1PAR SIG CBx.79.Sel_1P/3PAR & & 1-pole AR Initiation >=1 Figure 3.28-6 1-pole AR initiation SIG Phase A open SIG Phase B open SIG Phase C open EN [CBx.79.En_CBInit] & & & 3-pole AR Initiation SIG CBx.79.Ready EN [CBx.79.Sel_3PAR] EN [CBx.79.Sel_1P/3PAR] >=1 Figure 3.28-7 3-pole AR initiation 3.28.5.3 AR Reclosing After AR is initiated, the device will output the initiating contact of AR. For 1-pole AR, in order to prevent pole discrepancy protection from maloperation under pole discrepancy conditions, the contact of “1-pole AR initiation” can be used to block pole discrepancy protection. When the dead time delay of AR expires after AR is initiated, as for 1-pole AR, when the setting [CBx.25.En_3PLvChk] is set as “0”, the result of synchronism check will not be judged, and reclosing command will be output directly. When the setting [CBx.25.En_3PLvChk] is set as “1”, the reclosing is not permissible unless live three-phase check is met. As far as the 3-pole AR, if the synchronism check is enabled, the release of reclosing command shall be subject to the result of synchronism check. After the dead time delay of AR expires, if the synchronism check is still unsuccessful within the time delay [CBx.79.t_wait_Chk], the signal of synchronism check failure (CBx.79.Fail_Syn) will be output and the AR will be blocked. If 3-pole AR with no-check is enabled, the condition of synchronism check success (CBx.25.Ok_Chk) will always be established. And the signal of synchronism check success (CBx.25.Ok_Chk) from the synchronism check logic can be applied by auto-reclosing function inside the device or external auto-reclosure device. 3-230 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory CBx.79.Inprog_1P SIG 1-pole AR Initiation SIG 3-pole AR Initiation >=1 CBx.79.Inprog CBx.79.Inprog_3P SIG 1-pole AR Initiation [CBx.79.t_Dd_1PS1] 0ms & >=1 AR Pulse & SIG CBx.79.Ok_3PLvChk SIG 3-pole AR Initiation [CBx.79.t_Dd_3PS1] 0ms & >=1 [CBx.79.t_Wait_Chk] 0ms & SIG CBx.79.Fail_Chk CBx.79.Ok_Chk Figure 3.28-8 One-shot AR In the process of channel abnormality, an internal fault occurs on the transmission line, backup protection at both ends of line will operate to trip the circuit breaker of each end. The operation time of backup protection at both ends of the line is possibly non-accordant, whilst the time delay of AR needs to consider the arc-extinguishing and insulation recovery ability for transient fault, so the time delay of AR shall be considered comprehensively according to the operation time of the device at both ends. When the communication channel of main protection is abnormal (input signal [CBx.79.PLC_Lost] is energized), and the logic setting [CBx.79.En_AddDly] is set as “1”, then the dead time delay of AR shall be equal to the original dead time delay of AR plus the extra time delay [CBx.79.t_AddDly], so as to ensure the recovery of insulation intensity of fault point when reclosing after transient fault. This extra time delay [CBx.79.t_AddDly] is only valid for the first shot AR. >=1 SIG Any tripping signal SIG CBx.79.PLC_Lost SIG CBx.79.Active EN [CBx.79.En_AddDly] & & & Extend AR time Figure 3.28-9 Extra time delay of AR Reclosing pulse length may be set through the setting [CBx.79.t_PW_AR]. For the circuit breaker without anti-pump interlock, a logic setting [CBx.79.En_CutPulse] is available to control the reclosing pulse. When this function is enabled, if the device operates to trip during reclosing, the 3-231 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory reclosing pulse will drop off immediately, so as to prevent multi-shot reclosing onto fault. After the reclosing command is issued, AR will drop off with time delay [CBx.79.t_Reclaim], and can carry out next reclosing. SIG SIG WaitMasterValid & 0ms 50ms 0ms [CBx.79.t_PW_AR] AR Pulse SIG Single-phase Trip SIG Three-phase Trip EN [CBx.79.En_CutPulse] >=1 CBx.79.AR_Out & >=1 & >=1 & SIG [CBx.79.t_Reclaim] CBx.79.AR_Out 0ms Reset Command Figure 3.28-10 Reclosing output logic The reclaim timer defines a time from the issue of the reclosing command, after which the reclosing function resets. Should a new trip occur during this time, it is treated as a continuation of the first fault. The reclaim timer is started when the CB closing command is given. SIG 1-pole AR Initiation >=1 0ms SIG 3-pole AR Initiation SIG CBx.79.Fail_Rcls SET [CBx.79.Opt_Priority]=High [CBx.79.t_Fail] >=1 & CBx.79.WaitToSlave Figure 3.28-11 Wait to slave signal The output signal “CBx.79.WaitToSlave” is usually configured to the signal “CBx.79.WaitMaster” of slave AR. Slave AR is permissible to reclosing only if master AR is reclosed successfully. 3.28.5.4 Reclosing Failure and Success For transient fault, the fault will be cleared after the device operates to trip. After the reclosing command is issued, AR will drop off after time delay [CBx.79.t_Reclaim], and can carry out next reclosing. When the reclosing is unsuccessful or the reclosing condition is not met after AR initiated, the reclosing will be considered as unsuccessful, including the following cases. 1. If any protection element operates to trip when AR is enabled ([CBx.79.On]=1) and AR is not ready ([CBx.79.Ready]=0), the device will output the signal (CBx.79.Fail_Rcls). 2. For one-shot AR, if the tripping command is received again within reclaim time after the 3-232 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory reclosing pulse is issued, the reclosing shall be considered as unsuccessful. 3. For multi-shot AR, if the reclosing times are equal to the setting value of AR number and the tripping command is received again after the last reclosing pulse is issued, the reclosing shall be considered as unsuccessful. 4. The logic setting [CBx.79.En_FailCheck] is available to judge whether the reclosing is successful by CB state, when it is set as “1”. If CB is still in open position with a time delay [CBx.79.t_Fail] after the reclosing pulse is issued, the reclosing shall be considered as unsuccessful. For this case, the device will issue a signal (CBx.79.Fail_Rcls) to indicate that the reclosing is unsuccessful, and this signal will drop off after (Reset Command). AR will be blocked if the reclosing shall be considered as unsuccessful. SET [CBx.79.Opt_Priority]=Low & WaitMaster Valid SIG CBx.79.WaitMaster SIG CBx.79.On SIG CBx.79.Ready SIG Any tripping command SIG Last shot is made SIG CBx.79.Inprog SIG CBx.79.AR_Blkd SIG WaitMasterValid & & >=1 0ms 200ms >=1 CBx.79.Fail_Rcls & & [CBx.79.t_WaitMaster] 0ms >=1 SIG AR Pulse SIG WaitMasterValid EN [CBx.79.En_FailCheck] SIG 3 CB closed & [CBx.79.t_Fail] 0ms & & & CBx.79.Succ_Rcls 0ms [CBx.79.t_Fail] Figure 3.28-12 Reclosing failure and success After unsuccessful AR is confirmed, AR will be blocked. AR will not enter into the ready state unless the circuit breaker position drops off , and can only begin to enter into the ready state again after the circuit breaker is closed. 3.28.5.5 Reclosing Numbers Control The device may be set up into one-shot or multi-shot AR. Through the setting [CBx.79.N_Rcls], the maximum number of reclosing attempts may be set up to 4 times. Generally, only one-shot AR 3-233 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory is selected. Some corresponding settings may be hidden if one-shot AR is selected. 1. 1-pole AR [CBx.79.N_Rcls]=1 means one-shot reclosing. For one-shot 1-pole AR mode, 1-pole AR will be initiated only for single-phase fault and respective faulty phase selected, otherwise, AR will be blocked. For single-phase transient fault on the line, line protection device will operate to trip and 1-pole AR is initiated. After the dead time delay for 1-pole AR is expired, the device will send reclosing pulse, and then the auto-reclosure will drop off after the time delay [CBx.79.t_Reclaim] to ready for the next reclosing. For permanent fault, the device will operate to trip again after the reclosing is performed, and the device will output the signal of reclosing failure [CBx.79.Fail_Rcls]. [CBx.79.N_Rcls]>1 means multi-shot reclosing. For multi-shot reclosing in 1-pole AR mode, the first reclosing is 1-pole AR, and the subsequent reclosing can only be 3-pole AR. For single-phase transient fault on the line, line protection device will operate to trip and then 1-pole AR is initiated. After the dead time delay of the first reclosing is expired, the device will send reclosing pulse, and then the auto-reclosure will drop off after the time delay [CBx.79.t_Reclaim] to ready for the next reclosing. For permanent fault, the device will operate to trip again after the reclosing is performed, and then 3-pole AR is initiated. At this time, the time delay applies the setting [CBx.79.t_Dd_3PS2]. After the time delay is expired, if the reclosing condition is met, the device will send reclosing pulse. The sequence is repeated until the reclosing is successful or the maximum permit reclosing number [CBx.79.N_Rcls] is reached. If the first fault is multi-phase fault, the device operates to trip three-phase and initiate 3-pole AR. At this time, the time delay applies the setting [CBx.79.t_Dd_3PS1]. For the possible reclosing times of 3-pole AR in 1-pole AR mode, please refer to Table 3.28-2. 2. 3-pole AR [CBx.79.N_Rcls]=1 means one-shot reclosing. For one-shot 3-pole AR mode, line protection device will operate to trip when a transient fault occurs on the line and 3-pole AR will be initiated. After the dead time delay for 3-pole AR is expired, the device will send reclosing pulse, and then the auto-reclosure will drop off after the time delay [CBx.79.t_Reclaim] to ready for the next reclosing. For permanent fault, the device will operate to trip again after the reclosing is performed, and the device will output the signal of reclosing failure [CBx.79.Fail_Rcls]. [CBx.79.N_Rcls]>1 means multi-shot reclosing. For multi-shot reclosing in 3-pole AR mode, line protection device will operate to trip when a transient fault occurs on the line and 3-pole AR will be initiated. After the dead time delay of the first reclosing is expired, the device will send reclosing pulse, and then the auto-reclosure will drop off after the time delay [CBx.79.t_Reclaim] to ready for the next reclosing. For permanent fault, the device will operate to trip again after the reclosing is performed, and then 3-pole AR is initiated after the tripping contact drops off. After the time delay for AR is expired, the device will send reclosing pulse. The sequence is repeated until the reclosing is successful or the maximum permit reclosing number [CBx.79.N_Rcls] is reached. 3. 1/3-pole AR [CBx.79.N_Rcls]=1 means one-shot reclosing. For one-shot 1/3-pole AR mode, line protection device will operate to trip when a transient fault occurs on the line and 1-pole AR will be initiated 3-234 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory for single-phase fault and 3-pole AR will be initiated for multi-phase fault. After respective dead time delay for AR is expired, the device will send reclosing pulse, and then the auto-reclosure will drop off after the time delay [CBx.79.t_Reclaim] to ready for the next reclosing. For permanent fault, the device will operate to trip again after the reclosing is performed, and the device will output the signal of reclosing failure [CBx.79.Fail_Rcls]. [CBx.79.N_Rcls]>1 means multi-shot reclosing. For multi-shot reclosing in 1/3-pole AR mode, line protection device will operate to trip when a transient fault occurs on the line and AR will be initiated. After the dead time delay of the first reclosing is expired, the device will send reclosing pulse, and then the auto-reclosure will drop off after the time delay [CBx.79.t_Reclaim] to ready for the next reclosing. For permanent fault, the device will operate to trip again after the reclosing is performed, and then 3-pole AR is initiated after the tripping contact drops off. After the time delay for AR is expired, the device will send reclosing pulse. The sequence is repeated until the reclosing is successful or the maximum permit reclosing number [CBx.79.N_Rcls] is reached. For the possible reclosing times of 3-pole AR in 1/3-pole AR mode, please refer to Table 3.28-2. The table below shows the number of reclose attempts with respect to the settings and AR modes. Table 3.28-2 Reclosing number Setting Value 1-pole AR 3-pole AR 1/3-pole AR N-1AR N-3AR N-1AR N-3AR N-1AR N-3AR 1 1 0 0 1 1 1 2 1 1 0 2 1 2 3 1 2 0 3 1 3 4 1 3 0 4 1 4 N-1AR: the reclosing number of 1-pole AR N-3AR: the reclosing number of 3-pole AR 4. Coordination between dual auto-reclosures Duplicated protection configurations are normally applied for UHV lines. If reclosing function is integrated within line protections, the auto-reclosing function can be enabled in any or both of the line protections without coordination. If both sets of reclosing functions are enabled, when one of them first recloses onto a permanent fault, the other will block the reclosing pulse according to the latest condition of the faulty phase. For one-shot AR mode, if the current is detected in the faulty phase, AR will be blocked immediately to prevent the circuit breaker from repetitive reclosing. For multi-shot AR mode, if the current is detected in the faulty phase, the current reclosing pulse will be blocked and go into the next reclosing pulse logic automatically. If the maximum permitted reclosing number [CBx.79.N_Rcls] is reached, the auto-reclosure will drop off after the time delay [CBx.79.t_Reclaim]. For one-shot or multi-shot AR, there is a corresponding reclosing counter at each stage. After reclosing pulse is sent, the corresponding reclosing counter will plus 1 and the reclosing counter may be cleared by the submenu “Clear Counter”. If the circuit breaker is reclosed by other devices during AR initiation, the auto-reclosure will go into the next reclosing pulse logic. 3-235 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.28.5.6 AR Time Sequence Diagram The following two examples indicate typical time sequence of AR process for transient fault and permanent fault respectively. Signal Fault Trip CB 52b Open [CBx.79.t_Reclaim] CBx.79.t_Reclaim CBx.79.Active CBx.79.Inprog [CBx.79.t_Dd_1PS1] CBx.79.Inprog_1P [CBx.79.t_Dd_1PS1] CBx.79.Ok_Chk AR Out [CBx.79.t_PW_AR] CBx.79.Perm_Trp3P CBx.79.Fail_Rcls Time Figure 3.28-13 Single-phase transient fault Signal Fault Trip 52b Open Open [CBx.79.t_Reclaim] CBx.79.t_Reclaim CBx.79.Active CBx.79.Inprog CBx.79.Inprog_1P CBx.79.Inprog_3PS2 [CBx.79.t_Dd_1PS1] [CBx.79.t_Dd_3PS2] CBx.79.Ok_Chk AR Out [CBx.79.t_PW_AR] [CBx.79.t_PW_AR] CBx.79.Perm_Trp3P CBx.79.Fail_Rcls 200ms Time Figure 3.28-14 Single-phase permanent fault ([CBx.79.N_Rcls]=2) 3-236 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.28.6 Settings Table 3.28-3 Auto-reclosing settings No. Name Range Step Unit Remark Maximum 1 CBx.79.N_Rcls 1~4 1 2 CBx.79.t_Dd_1PS1 0.000~600.000 0.001 s 3 CBx.79.t_Dd_3PS1 0.000~600.000 0.001 s 4 CBx.79.t_Dd_3PS2 0.000~600.000 0.001 s 5 CBx.79.t_Dd_3PS3 0.000~600.000 0.001 s 6 CBx.79.t_Dd_3PS4 0.000~600.000 0.001 s 7 CBx.79.t_CBClsd 0.000~600.000 0.001 s number of reclosing attempts Dead time of first shot 1-pole reclosing Dead time of first shot 3-pole reclosing Dead time of second shot 3-pole reclosing Dead time of third shot 3-pole reclosing Dead time of fourth shot 3-pole reclosing Time delay of circuit breaker in closed position before reclosing Time delay to wait for CB healthy, and begin to timing when the input 8 CBx.79.t_CBReady 0.000~600.000 0.001 s signal [79.CB_Healthy] de-energized and if it is is not energized within this time delay, AR will be blocked. 9 CBx.79.t_Wait_Chk 0.000~600.000 0.001 s Maximum wait time for synchronism check Time delay allow for CB status 10 CBx.79.t_Fail 0.000~600.000 0.001 s change to conform reclosing successful 11 CBx.79.t_PW_AR 0.000~600.000 0.001 s Pulse width of AR closing signal 12 CBx.79.t_Reclaim 0.000~600.000 0.001 s Reclaim time of AR 13 CBx.79.t_PersistTrp 0.000~600.000 0.001 s Time delay of excessive trip signal to block auto-reclosing Drop-off time delay of blocking AR, 14 CBx.79.t_DDO_BlkAR 0.000~600.000 0.001 s when blocking signal for AR disappears, AR blocking condition drops off after this time delay 15 CBx.79.t_AddDly 0.000~600.000 0.001 s 16 CBx.79.t_WaitMaster 0.000~600.000 0.001 s 17 CBx.79.t_SecFault 0.000~600.000 0.001 s Additional time delay for auto-reclosing Maximum wait time for reclosing permissive signal from master AR Time delay of discriminating another fault, and begin to times after 1-pole 3-237 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory No. Name Range Step Unit Remark AR initiated, 3-pole AR will be initiated if another fault happens during this time delay. AR will be blocked if another fault happens after that. Enabling/disabling auto-reclosing blocked when a fault occurs under 18 CBx.79.En_PDF_Blk 0 or 1 pole disagreement condition 0: disable 1: enable Enabling/disabling 19 CBx.79.En_AddDly auto-reclosing with an additional dead time delay 0 or 1 0: disable 1: enable Enabling/disabling adjust the length 20 CBx.79.En_CutPulse of reclosing pulse 0 or 1 0: disable 1: enable Enabling/disabling confirm whether AR is successful by checking CB 21 CBx.79.En_FailCheck 0 or 1 state 0: disable 1: enable Enabling/disabling auto-reclosing 22 CBx.79.En 0 or 1 0: disable 1: enable Enabling/disabling AR by external input signal besides logic setting 23 CBx.79.En_ExtCtrl [79.En] 0 or 1 0: only logic setting 1: logic setting and external input signal Enabling/disabling AR be initiated by 24 CBx.79.En_CBInit open state of circuit breaker 0 or 1 0: disable 1: enable Option of AR priority None: single-breaker arrangement 25 CBx.79.Opt_Priority None, High or High: master AR of multi-breaker Low arrangement Low: slave AR of multi-breaker arrangement 26 CBx.79.SetOpt 0 or 1 Control option of AR mode 3-238 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory No. Name Range Step Unit Remark 1: select AR mode by internal logic settings 0: select AR mode by external input signals Enabling/disabling 1-pole AR mode 27 CBx.79.En_1PAR 0 or 1 0: disable 1: enable Enabling/disabling 3-pole AR mode 28 CBx.79.En_3PAR 0 or 1 0: disable 1: enable Enabling/disabling 29 CBx.79.En_1P/3PAR 1/3-pole AR mode 0 or 1 0: disable 1: enable 3.29 Transfer Trip 3.29.1 General Application This function module provides a binary input [TT.Init] for receiving transfer trip from the remote end. This feature ensures simultaneous tripping at both ends. 3.29.2 Function Description Transfer trip can be controlled by local fault detector by logic settings [TT.En_FD_Ctrl]. In addition, the binary input [TT.Init] is always supervised, and the device will issue an alarm [TT.Alm] and block transfer trip once the binary input is energized for longer than [TT.t_Op]+5s and drop off after resumed to normal with a time delay of 10s. 3.29.3 Function Block Diagram TT TT.Init TT.Alm TT.En TT.Op TT.Blk TT.On 3-239 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.29.4 I/O Signals Table 3.29-1 I/O signals of transfer trip No. Input Signal 1 TT.Init 2 TT.En 3 TT.Blk No. Description Input signal of initiating transfer trip after receiving transfer trip Transfer trip enabling input, it is triggered from binary input or programmable logic etc. Transfer trip blocking input, it is triggered from binary input or programmable logic etc. Output Signal Description 1 TT.Alm Input signal of receiving transfer trip is abnormal 2 TT.Op Transfer trip operates 3 TT.On Transfer trip is enabled 3.29.5 Logic SIG TT.En SIG TT.Blk SIG TT.Alm EN [TT.En_FD_Ctrl] SIG FD.Pkp BI TT.Init & TT.On & [TT.t_Op] >=1 0ms & [TT.t_Op]+5s 10s TT.Op TT.Alm Figure 3.29-1 Logic diagram of transfer trip 3.29.6 Settings Table 3.29-2 Settings of transfer trip No. 1 Name TT.t_Op Range Step Unit 0.000~600.000 0.001 s 2 TT.En_FD_Ctrl 0 or 1 3 TT.En_BlkAR 0 or 1 Remark Time delay of transfer trip Transfer trip controlled by local fault detector element 0: not controlled by local fault detector element 1: controlled by local fault detector element Enabling/disabling transfer trip operate to block AR 0: disable 1: enable 3-240 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.30 Trip Logic 3.30.1 General Application For any enabled protection tripping elements, their operation signal will convert to appropriate tripping signals through trip logics and then trigger output contacts by configuration. NOTICE! For double circuit breakers mode, the device will provide independent trip logic for CB1 and CB2 respectively. Both trip logics have the same logic. The difference is that the prefix “CBx.” is added to all signals for circuit breaker No.x (x=1 or 2). For trip logic settings, only the setting [En_Trp3P] will be added the prefix “CBx.” for circuit breaker No.x, which means that both circuit breakers corresponding to the same line protection can be set different trip mode. 3.30.2 Function Description This module gathers signals from phase selection and protection tripping elements and then converts the operation signal from protection tripping elements to appropriate tripping signals. The device can implement phase-segregated tripping or three-phase tripping, and may output the contact of blocking AR and the contact of initiating breaker failure protection. 3.30.3 Function Block Diagram TRP Line.Enable Line.Trp3P_PSFail Line.Block CBx.TRP.On CBx.TRP.En CBx.TrpA CBx.TRP.Blk CBx.TrpB Faulty phase selection CBx.TrpC CBx.PrepTrp3P CBx.Trp Line tripping element CBx.Trp3P Breaker tripping element CBx.BFI_A Initiating BFP element CBx.BFI_B CBx.BFI_C CBx.BFI CBx.TRP.BlkAR 3-241 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.30.4 I/O Signals Table 3.30-1 I/O signals of trip logic No. Input Signal Description 1 Line.Enable Input signal of enabling line trip logic 2 Line.Block Input signal of blocking line trip logic 3 CBx.Enable Input signal of enabling trip logic of circuit breaker No.x 4 CBx.Block Input signal of blocking trip logic of circuit breaker No.x Faulty phase selection (phase The result of fault phase selection A, phase B, phase C) If multi-phase is selected, three-phase breakers will be tripped. 5 Input signal of permitting three-phase tripping 6 CBx.PrepTrp3P When this signal is valid, three-phase tripping will be adopted for any kind of faults. 7 Line tripping element 8 Breaker tripping element 9 Initiating BFP element All operation signals of various line protection tripping elements, such as distance protection, overcurrent protection, etc. All protection tripping elements concerned with breaker, such as pole discrepancy protection, etc. Tripping element to initiate BFP, except undervoltage protection, tripping elements of all protections initiate BFP No. Output Signal Description 1 Line.Trp3P_PSFail Initiating three-phase tripping due to failure in fault phase selection 2 CBx.TRP.On Tripping logic is enabled. 3 CBx.TrpA Tripping A-phase circuit breaker 4 CBx.TrpB Tripping B-phase circuit breaker 5 CBx.TrpC Tripping C-phase circuit breaker 6 CBx.Trp Tripping any phase circuit breaker 7 CBx.Trp3P Tripping three-phase circuit breaker 8 CBx.BFI_A 9 CBx.BFI_B 10 CBx.BFI_ C 11 CBx.BFI 12 CBx.TRP.BlkAR Protection tripping signal of A-phase configured to initiate BFP, BFI signal shall be reset immediately after tripping signal drops off. Protection tripping signal of B-phase configured to initiate BFP, BFI signal shall be reset immediately after tripping signal drops off. Protection tripping signal of C-phase configured to initiate BFP, BFI signal shall be reset immediately after tripping signal drops off. Protection tripping signal configured to initiate BFP, BFI signal shall be reset immediately after tripping signal drops off. Blocking auto-reclosing 3.30.5 Logic After tripping signal is issued, the tripping pulse will be kept as same as the setting [t_Dwell_Trp] at least. When the time delay is expired, for phase-segregated tripping, the tripping signal will drop off immediately if the faulty current of corresponding phase is less than 0.06In (In is secondary rated current), otherwise the tripping signal will be always kept until the faulty current of corresponding phase is less than 0.06In. For three-phase tripping, the tripping signal will drop off 3-242 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory immediately if three-phase currents are all less than 0.06In, otherwise the tripping signal will be always kept until three-phase currents are all less than 0.06In. NOTICE! The line trip command was sent to the circuit breaker, and the circuit breaker will be tripped. And then the circuit breaker will be in open position and its current will be zero. Hence, under this condition, there is on need to trip second time in the duration of the device picking up. 3-243 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory SIG Line tripping element without FPS SIG FPS (phase A) >=1 & & Line trip command (phase A) SIG Line tripping element with FPS SIG Ia<0.06In [t_Dwell_Trp] & 0 SIG Line tripping element without FPS SIG FPS (phase B) >=1 & & Line trip command (phase B) SIG Line tripping element with FPS SIG Ib<0.06In [t_Dwell_Trp] & 0 SIG Line tripping element without FPS SIG FPS (phase C) >=1 & & Line trip command (phase C) SIG Line tripping element with FPS SIG Ic<0.06In [t_Dwell_Trp] & 0 SIG Line trip command (phase A) & SIG Line trip command (phase B) SIG Line trip command (phase C) SIG Line trip command (phase A) & SIG Line trip command (phase B) >=1 >=1 Line trip 3P command SIG Line trip command (phase C) SIG Line trip command (phase A) & SIG Line trip command (phase B) SIG Line trip command (phase C) SIG Line trip command (phase A) & SIG Line trip command (phase B) SIG Line trip command (phase C) 3-244 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory SIG FPS (phase A) >=1 SIG FPS (phase B) & 200ms 0ms Line.Trp3P_PSFail SIG FPS (phase C) SIG Line tripping element with FPS SIG CBx.TRP.En & CBx.TRP.On SIG CBx.TRP.Blk >=1 SIG Breaker tripping element SIG Ia<0.06In & & SIG Ib<0.06In & SIG Ic<0.06In [t_Dwell_Trp] CB No.x Trip Command & 0 SIG CBx.TRP.On & CBx.TrpA SIG Line trip command (phase A) & CBx.TrpB SIG Line trip command (phase B) & CBx.TrpC SIG Line trip command (phase C) >=1 & SIG CBx.PrepTrp3P EN >=1 [CBX.En_3PTrp] SIG Line.Trip 3P Command & >=1 CBx.Trp3P >=1 SIG Line.Trp3P_PSFail SIG CB No.x Trip Command Figure 3.30-1 Tripping logic 3-245 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory >=1 & Except undervoltage protection, tripping elements of all protections all initiate BFP CBx.BFI SIG Initiating BFP element & CBx.BFI_A SIG CBx.TrpA & CBx.BFI_B SIG CBx.TrpB & CBx.BFI_C SIG CBx.TrpC Figure 3.30-2 Breaker failure initiation logic 3-246 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory SIG 85-1.Op_DEF SIG 85-2.Op_DEF EN [85.DEF.En_BlkAR] SIG 78.Op SIG Yi.ZP.Op >=1 & & >=1 >=1 >=1 EN [Yi.ZP.En_BlkAR] SIG Yi.ZG.Op EN [Yi.ZG.En_BlkAR] SIG 50/51Pm.Op EN [50/51Pm.En_BlkAR] SIG 50/51Gm.Op EN [50/51Gm.En_BlkAR] SIG 50/51Qm.Op EN [50/51Qm.En_BlkAR] SIG 50PVT1(2).Op SIG 50GVT1(2).Op SIG 46BC.Op SIG 81O.OFm.Op SIG 81U.UFm.Op SIG TT.Op EN [TT.En_BlkAR] SIG CBx.50BF.Op_t1 SIG CBx.50BF.Op_t2 SIG CBx.50DZ.Op SIG 49-1.Op SIG 49-2.Op SIG 87STB.Op SIG 32R1.Op SIG 32R2.Op SIG CBx.62PD.Op SIG 59Pz.Op SIG 59Gz.Op SIG 59Q.Op SIG 27Pz.Op EN En_MPF_Blk_AR SIG Multi-phase fault EN En_3PF_Blk_AR SIG Three-phase fault EN En_PhSF_Blk_AR SIG Phase selection failure SIG 21SOTF.Op SIG 50PSOTF.Op SIG 50GSOTF.Op SIG Manual closing signal & & & >=1 & >=1 >=1 >=1 & >=1 >=1 >=1 >=1 >=1 CBx.BlkAR >=1 >=1 >=1 & & >=1 & >=1 >=1 & Figure 3.30-3 Blocking AR logic 3-247 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Y can be 21M or 21Q i can be 1, 2, 3, 4 or 5 m can be 1, 2, 3 or 4 z can be 1, 2 or 3 x can be 1 or 2 3.30.6 Settings Table 3.30-2 Settings of trip logic No. Name Range Step Unit Remark Enabling/disabling 1 En_MPF_Blk_AR auto-reclosing blocked when multi-phase fault happens 0 or 1 0: disable 1: enable Enabling/disabling 2 En_3PF_Blk_AR auto-reclosing blocked when three-phase fault happens 0 or 1 0: disable 1: enable Enabling/disabling 3 En_PhSF_Blk_AR auto-reclosing blocked when faulty phase selection fails 0 or 1 0: disable 1: enable The dwell time of tripping command, empirical value is 0.04 4 t_Dwell_Trp 0.000~10.000 0.001 s The tripping contact shall drop off under conditions of no current or protection tripping element drop-off. Enabling/disabling three-phase tripping mode 5 CBx.En_Trp3P 0 or 1 for any fault conditions 0: disable 1: enable 3.31 VT Circuit Supervision 3.31.1 General Application The purpose of VT circuit supervision is to detect whether VT circuit is normal. Because some protection functions, such as distance protection, under-voltage protection and so on, will be influenced by VT circuit failure, these protection functions should be disabled when VT circuit fails. VT circuit failure can be caused by many reasons, such as fuse blown due to short-circuit fault, poor contact of VT circuit, VT maintenance and so on. The device can detect them and issue an alarm signal to block relevant protection functions. However, the alarm of VT circuit failure should not be issued when the following cases happen. 3-248 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 1. Line VT is used as protection VT and the protected line is out of service. 2. Only current protection functions are enabled and VT is not connected to the device. 3.31.2 Function Description VT circuit supervision can detect failure of single-phase, two-phase and three-phase on protection VT. Under normal condition, the device continuously supervises input voltage from VT, VT circuit failure signal will be activated if residual voltage exceeds the threshold value or positive-sequence voltage is lower than the threshold value. If the device is under pickup state due to system fault or other abnormality, VT circuit supervision will be disabled. Under normal conditions, the device detect residual voltage greater than the setting [VTS.3U0_Set] to determine single-phase or two-phase VT circuit failure, and detect positive-sequence voltage less than the setting [VTS.U1_Set] to determine three-phase VT circuit failure. Upon detecting abnormality on VT circuit, an alarm will comes up with the time delay [VTS.t_DPU] and drop off with the time delay [VTS.t_DDO] after VT circuit restored to normal. VT (secondary circuit) MCB auxiliary contact as a binary input can be connected to the binary input circuit of the device. If MCB is open (i.e. [VTS.MCB_VT] is energized), the device will consider the VT circuit is not in a good condition and issues an alarm without a time delay. When VT is not connected into the device, the alarm will be not issued if the logic setting [VTS.En_Out_VT] is set as “1”. However, the alarm is still issued if the binary input [VTS.MCB_VT] is energized, no matter that the logic setting [VTS.En_Out_VT] is set as “1” or “0”. When VT neutral point fails, third harmonic of residual voltage is comparatively large. If third harmonic amplitude of residual voltage is larger than the setting [VTNS.3U0_Hm3] and without operation of fault detector element, VT neutral point failure alarm signal [VTNS.Alm] will be issued with the time delay [VTS.t_DPU] and drop off with the time delay [VTS.t_DDO] after three phases voltage restored to normal. 3.31.3 Function Block Diagram VTS VTS.En VTNS VTS.Alm VTNS.En VTS.Blk VTNS.Alm VTNS.Blk VTS.MCB_VT 3.31.4 I/O Signals Table 3.31-1 I/O signals of VT circuit supervision No. 1 Input Signal VTS.En Description VT supervision enabling input, it is triggered from binary input or programmable 3-249 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory logic etc. VT supervision blocking input, it is triggered from binary input or programmable 2 VTS.Blk 3 VTNS.En 4 VTNS.Blk 5 VTS.MCB_VT No. logic etc. VT neutral point supervision enabling input, it is triggered from binary input or programmable logic etc. VT neutral point supervision blocking input, it is triggered from binary input or programmable logic etc. Binary input for VT MCB auxiliary contact Output Signal Description 1 VTS.Alm Alarm signal to indicate VT circuit fails 2 VTNS.Alm Alarm signal to indicate VT neutral point fails 3.31.5 Logic SIG FD.Pkp SIG 79.Inprog SIG 3U0>[VTS.3U0_Set] SIG U1<[VTS.U1_Set] EN [VTS.En_LineVT] SIG 52b_PhA SIG 52b_PhB SIG 52b_PhC EN [VTS.En_Out_VT] BI >=1 & >=1 & If the signal [FD.Pkp] or [CBx.79.Inprog] operates, the circuit of time delay will be interrupted. >=1 & & [VTS.t_DPU] [VTS.t_DDO ] & >=1 >=1 & VTS.Alm [VTS.MCB_VT] EN [VTS.En] SIG [VTS.En] SIG [VTS.Blk] & Figure 3.31-1 Logic of VT circuit supervision & SIG FD.Pkp >=1 SIG 79.Inprog If the signal [FD.Pkp] or [CBx.79.Inprog] operates, the circuit of time delay will be interrupted. SIG U03>[VTNS.3U0_Hm3_Set] & >=1 [VTS.t_DPU] EN [VTS.En_Out_VT] EN [VTS.En] SIG [VTS.t_DDO] & VTNS.Alm & [VTNS.En] SIG [VTNS.Blk] Figure 3.31-2 Logic of VT neutral point supervision U03 is third harmonic amplitude of neutral point residual voltage 3-250 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory If there is already a VTS alarm before FD operated, VTS will continue to block distance protection, that is VTS will be latched when FD operates. 3.31.6 Settings Table 3.31-2 VTS settings No. Name Range Step Unit 1 VTS.3U0_Set 0.000~220.000 0.001 V 2 VTS.U1_Set 22.000~110.000 0.001 V 3 VTNS.3U0_Hm3_Set 0.000~220.000 0.001 V 4 VTS.t_DPU 0.200~100.000 0.001 s 5 VTS.t_DDO 0.200~100.000 0.001 s Remark Zero-sequence voltage setting of VT circuit supervison Positive-sequence voltage setting of VT circuit supervison Third harmonic setting of zero-sequence voltage of VT circuit supervision Pickup time delay of VT circuit delay of VT circuit used for supervision Dropoff time supervision No voltage protection calculation 1: enable 6 VTS.En_Out_VT 0 or 1 0: disable In general, when VT is not connected to the device, this logic setting should be set as “1” Voltage 7 VTS.En_LineVT selection for protection calculation from busbar VT or line VT 0 or 1 1: line VT 0: busbar VT Enabling/disabling alarm function of VT 8 VTS.En circuit supervision 0 or 1 1: enable 0: disable 3.32 CT Circuit Supervision 3.32.1 General Application The purpose of the CT circuit supervision is to detect any abnormality on CT secondary circuit. NOTICE! For double circuit breakers mode, the device will provide independent CT circuit supervision function for CB1 and CB2 respectively. Both CT circuit supervision functions have the same logic. The difference is that the prefix “CBx.” is added to all signals for circuit breaker No.x (x=1 or 2). 3-251 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.32.2 Function Description Under normal conditions, CT secondary signal is continuously supervised by detecting the residual current and voltage. If residual current is larger than 10%In whereas residual voltage is less than 3V, an error in CT circuit is considered, the concerned protection functions are blocked and an alarm is issued with a time delay of 10s and drop off with a time delay of 10s after CT circuit is restored to normal condition. 3.32.3 Function Block Diagram CTS CBx.CTS.En CBx.CTS.Alm CBx.CTS.Blk 3.32.4 I/O Signals Table 3.32-1 I/O signals of CT circuit supervision No. Input Signal 1 CBx.CTS.En 2 CBx.CTS.Blk No. 1 Description CT circuit supervision enabling input, it is triggered from binary input or programmable logic etc. CT circuit supervision blocking input, it is triggered from binary input or programmable logic etc. Output Signal CBx.CTS.Alm Description Alarm signal to indicate CT circuit fails 3.32.5 Logic SIG CBx.CTS.En SIG CBx.CTS.Blk SIG 3I0>0.1In SIG 3U0<3V SIG IA<0.06In SIG IB<0.06In SIG IC<0.06In & & 10s 10s CBx.CTS.Alm & >=1 Figure 3.32-1 Logic diagram of CT circuit failure 3.33 Control and Synchrocheck for Manual Closing 3.33.1 General Application The purpose of control is to open or close primary equipment, including circuit breaker (CB), disconnector (DS) and earth switch (ES), or to issue outputs for signaling purpose. Synchronism 3-252 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory check and dead check are also provided for the control processes as below: 1. Local manual closing CB 2. Local closing CB by access the menu “Local Cmd→Control” 3. Remote closing CB from SCADA (i.e., local HMI system) or control center (CC) Programmable interlocking logics within a bay and amongst different bays are provided by using PCS-Explorer. NOTICE! For double circuit breakers mode, the device will provide independent control and synchrocheck function of manual closing for CB1 and CB2 respectively. Both control and synchrocheck for manual closing functions have the same logic. The difference is that the prefix “CBx.” is added to all signals and settings for circuit breaker No.x (x=1 or 2). 3.33.2 Function Description 1. Control High reliability is ensured by adopting the principle of selection before operation (abbreviated SBO). When the binary input [BI_Maintenance] is energized as “1”, remote control from SCADA/CC will be disabled, but local control will not be influenced. The integrated control process is as follow: 1) The control source (SCADA/CC, or local LCD control operation, or manual control operation) sends control selection command to this device 2) This device sends back the control selection result (success or failure) to the control source after logic judgment 3) The control source sends control operation command to this device if the control selection result is “success”. The control source will send control cancellation command to this device if the control selection result is “failure”. 4) This device sends back the control operation result (success or failure) to the control source after logic judgment. Logic calculation result of interlocking is input to the remote control module as a criterion of remote operation. When the enabling parameter of remote open/close interlock is “1”, remote control module determines whether it can be output according to the calculation result of interlocking. If the current breaker position or programmable part can meet the interlocking condition, remote control can be output normally, otherwise remote operation is blocked. When the enabling parameter of remote open/close interlock is “0”, interlocking function is disabled and remote control will be output directly without the judgment of interlocking. Holding time of each binary output contact can be set by configuring corresponding settings and is often configured as 250ms. However, for the control circuits without latched relays, the holding 3-253 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory time must be longer to ensure successful control operation. EN 1 [MCBrd.CBx.25.En_SynChk] MCBrd.CBx.25.On_SynChk SIG MCBrd.CBx.25.Sel_SynChk EN [MCBrd.CBx.25.SetOpt] EN [MCBrd.CBx.25.En_NoChk] SIG MCBrd.CBx.25.Sel_NoChk EN [MCBrd.CBx.25.SetOpt] 0 1 MCBrd.CBx.25.On_NoChk 0 Figure 3.33-1 Synchrocheck mode selection for manual closing SIG CSWI01.CILO.Disable >=1 SIG BIinput.CILO.Disable >=1 EN [CSWI01.En_Cls_Blk] SIG CSWI01.CILO.EnCls SIG CSWI01.RmtCtrl >=1 & SIG BIinput.RmtCtrl >=1 & [CSWI01.t_PW_Cls] SIG CSWI01.Cmd_RmtCtrl SIG CSWI01.LocCtrl CSWI01.Op_Cls >=1 & SIG BIinput.LocCtrl SIG CSWI01.ManSynCls 0ms >=1 SIG CSWI01.Cmd_LocCtrl SIG MCBrd.CB1.25.On_SynChk >=1 SIG MCBrd.CB1.25.Ok_Chk SIG MCBrd.CB1.Alm_VTS & & & EN [MCBrd.CB1.En_Alm_VTS] EN [MCBrd.CB1.25.En_VTS_Blk_SynChk] EN [MCBrd.CB1.En_Alm_VTS] & & SIG MCBrd.CB1.Alm_VTS EN [MCBrd.CB1.25.En_VTS_Blk_DdChk] EN [MCBrd.CB1.25.En_LvL_DdB] EN [MCBrd.CB1.25.En_DdL_LvB] EN [MCBrd.CB1.25.En_DdL_DdB] >=1 & >=1 >=1 SIG MCBrd.CB1.25.Ok_Chk SIG MCBrd.CB1.25.On_NoChk 3-254 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Figure 3.33-2 Logic diagram of closing circuit breaker 1 SIG CSWI02.CILO.Disable >=1 SIG BIinput.CILO.Disable >=1 EN [CSWI02.En_Cls_Blk] SIG CSWI02.CILO.EnCls SIG CSWI02.RmtCtrl >=1 & SIG BIinput.RmtCtrl >=1 & [CSWI02.t_PW_Cls] SIG CSWI02.Cmd_RmtCtrl SIG CSWI02.LocCtrl 0ms CSWI02.Op_Cls >=1 & SIG BIinput.LocCtrl SIG CSWI02.ManSynCls >=1 SIG CSWI02.Cmd_LocCtrl SIG MCBrd.CB2.25.On_SynChk >=1 SIG MCBrd.CB2.25.Ok_Chk SIG MCBrd.CB2.Alm_VTS & & & EN [MCBrd.CB2.En_Alm_VTS] EN [MCBrd.CB2.25.En_VTS_Blk_SynChk] EN [MCBrd.CB2.En_Alm_VTS] & & SIG MCBrd.CB2.Alm_VTS EN [MCBrd.CB2.25.En_VTS_Blk_DdChk] EN [MCBrd.CB2.25.En_LvL_DdB] EN [MCBrd.CB2.25.En_DdL_LvB] EN [MCBrd.CB2.25.En_DdL_DdB] >=1 & >=1 >=1 SIG MCBrd.CB2.25.Ok_Chk SIG MCBrd.CB2.25.On_NoChk Figure 3.33-3 Logic diagram of closing circuit breaker 2 As shown in Figure 3.33-3, for double circuit breakers application, both the first closing command “CSWI01.Op_Cls” and the second closing command “CSWI02.Op_Cls”, which are controlled by synchrocheck logic, can be used for CB closing, otherwise, the logic of the second closing command “CSWI02.Op_Cls” should comply with Figure 3.33-4. After receiving a closing command, this device will continuously check whether the 2 voltages (Incoming voltage and reference voltage) involved in synchronism check (or dead check) can meet the criteria. Within the duration of [MCBrd.CBx.25.t_Wait_Chk], if the synchronism check (or dead check) criteria are not met, the signal “MCBrd.CBx.25.Ok_Chk” will be set as “0”; if the synchronism check (or dead check) criteria are met, the signal “MCBrd.CBx.25.Ok_Chk” will be 3-255 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory set as “1”. When any of the following criteria is fulfilled, an alarm signal [MCBrd.CBx.Alm_VTS] will be issued with a time delay of 1.25s, and drop off with a time delay of 10s after three phases voltage restored to normal. The alarm signal will block the closing command for circuit breaker. 1. The negative-sequence voltage is greater than 8V. 2. The positive-sequence voltage is smaller than 30V, and any phase current is greater than 0.04In. SIG CSWIxx.CILO.Disable SIG BIinput.CILO.Disable EN [CSWIxx.En_Cls_Blk] SIG CSWIxx.CILO.EnCls SIG CSWIxx.RmtCtrl SIG BIinput.RmtCtrl SIG CSWIxx.Cmd_RmtCtrl SIG CSWIxx.LocCtrl SIG BIinput.LocCtrl SIG CSWIxx.Cmd_LocCtrl >=1 >=1 & [CSWIxx.t_PW_Cls] 0ms [CSWIxx.Op_Cls] >=1 & >=1 >=1 & Figure 3.33-4 Logic diagram of closing switch (xx=02~15) Access the menu “Local Cmd→Control” to issue control command locally, and this signal “CSWIxx.Cmd_LocCtrl” will be set as “1”. Remote control commands from SCADA/CC can be transmitted via IEC 60870-5-103 protocol or IEC 61850 protocol, and this signal “CSWIxx.Cmd_RmtCtrl” will be set as “1”. 3-256 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory SIG CSWI01.CILO.Disable >=1 SIG BIinput.CILO.Disable >=1 EN [CSWI01.En_Opn_Blk] & [CSWI01.t_PW_Opn] 0ms CSWI01.Op_Opn [CSWI02.t_PW_Opn] 0ms CSWI02.Op_Opn SIG CSWI01.CILO.EnOpn SIG CSWI01.RmtCtrl >=1 & SIG BIinput.RmtCtrl >=1 SIG CSWI01.Cmd_RmtCtrl SIG CSWI01.LocCtrl >=1 & SIG BIinput.LocCtrl SIG CSWI01.ManOpn >=1 SIG CSWI01.Cmd_LocCtrl SIG CSWI02.CILO.Disable >=1 SIG BIinput.CILO.Disable >=1 EN [CSWI02.En_Opn_Blk] & SIG CSWI02.CILO.EnOpn SIG CSWI02.RmtCtrl >=1 & SIG BIinput.RmtCtrl >=1 SIG CSWI02.Cmd_RmtCtrl SIG CSWI02.LocCtrl >=1 & SIG BIinput.LocCtrl SIG CSWI02.ManOpn >=1 SIG CSWI02.Cmd_LocCtrl Figure 3.33-5 Logic diagram of open circuit breaker 3-257 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory SIG CSWIxx.CILO.Disable >=1 SIG BIinput.CILO.Disable >=1 EN [CSWIxx.En_Opn_Blk] & [CSWIxx.t_PW_Opn] SIG CSWIxx.CILO.EnOpn SIG CSWIxx.RmtCtrl 0ms CSWIxx.Op_Opn >=1 & SIG BIinput.RmtCtrl >=1 SIG CSWIxx.Cmd_RmtCtrl SIG CSWIxx.LocCtrl >=1 & SIG BIinput.LocCtrl SIG CSWIxx.Cmd_LocCtrl Figure 3.33-6 Logic diagram of open switch (xx=02~15) The control output fulfills signal output circuit, and opens or closes circuit breaker, disconnector and earth switch according to the control command. Object manipulation strictly performs three steps: selection, check and execute, and perform output relay check, to ensure that the remote control can be executed safely and reliably. When logic interlock is enabled, the device can receive the programmable interlock logic. The device can automatically initiate the interlock logic to determine whether to allow control operations. The device provides corresponding settings ([CSWIxx.En_Opn_Blk] and [CSWIxx.En_Cls_Blk]) for each control object. When they are set as “1”, the interlock function of the corresponding control object is enabled. The interlock logic can be configured by using PCS-Explorer, and downloaded to the device via the Ethernet port. If the interlock function is enabled, but it is not configured the interlock logic, the result of the logic output is 0. The control record is a file which is used to store remote control command records of this device circularly. If the record number is to 256, the storage area of the control record will be full. If this device has received a new remote command, this device will delete the oldest remote control record, and then store the latest remote control record. There are 15 configuration pages corresponding to 15 control outputs in total respectively. Each configuration page can finish some signals configuration, including remote control, local control, disable interlock blocking, and so on. In order to conveniently configure control output, the same output signals, including “BIinput.RmtCtrl”, “BIinput.LocCtrl” and “BIinput.CILO.Disable”, are available after processing binary signals internally, as shown in figure below. 3-258 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3-259 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Figure 3.33-7 Configuration page of control output 01 (default configuration) 3-260 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory Figure 3.33-8 Configuration page of control output 02 (default configuration) Control output 03~15 is as same as control output 02. The configuration rule about remote control and local control to binary outputs is as bellow: X means that it is not configured. Remote Local CSWIxx. BIinput. CSWIxx. BIinput. RmtCtrl RmtCtrl LocCtrl LocCtrl X X X X 0 X X X X 0 X X 1 X X X X 1 X X X X 0 X X X X 0 X X 1 X X X X 1 0 X 0 X 0 X X 0 X 0 0 X X 0 X 0 0 X 1 X X 0 1 X 0 X X 1 Control Mode Neither Local control nor remote control are permissible. Only local control is permissible. Only remote control is permissible. Only remote control is permissible. Only local control is permissible. Neither Local control nor remote control are permissible. Only local control is permissible. 3-261 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory X 0 X 1 1 X 0 X 1 X X 0 X 1 0 X X 1 X 0 1 X 1 X 1 X X 1 X 1 1 X X 1 X 1 Only remote control is permissible. Both Local control and remote control are permissible. For remote control or local control, they can be configured by either of “CSWIxx.RmtCtrl” and “BIinput.RmtCtrl”, or either of “CSWIxx.LocCtrl” and “BIinput.LocCtrl”. 2. Synchrocheck Three synchrocheck modes are designed for CB closing: no check mode, dead check mode and synchronism check mode, if any one of the condition of three synchrocheck modes satisfied, then synchrocheck signal “MCBrd.CBx.25.Ok_Chk” will be asserted. The synchronism check function measures the conditions across the circuit breaker and compares them with the corresponding settings. The output is only given if all measured quantities are simultaneously within their set limits. Compared to the synchronism check for auto-reclosing, an additional criterion is applied to check the rate of frequency change (df/dt) between both sides of the CB. When the following four conditions are all met, the synchronism check is successful. 1) Phase angle difference between incoming voltage and reference voltage is less than the setting [MCBrd.CBx.25.phi_Diff] 2) Frequency difference between incoming voltage and reference voltage is less than [MCBrd.CBx.25.f_Diff] 3) Voltage difference between incoming voltage and reference voltage is less than [MCBrd.CBx.25.U_Diff] 4) Rate of frequency change between incoming voltage and reference voltage is less than [MCBrd.CBx.25.df/dt] The dead check function measures the amplitude of line voltage and bus voltage at both sides of the circuit breaker, and then compare them with the live check setting [MCBrd.CBx.25.U_Lv] and the dead check setting [MCBrd.CBx.25.U_Dd]. The dead check is successful when the measured quantities comply with the criteria. When this device is set to work in no check mode and receives a closing command, CB will be closed without synchronism check and dead check. Synchrocheck for manual closing also supports voltage switching. In general, voltage switching is fulfilled by external circuit ([CBx.CBConfigMode]=NoVoltSel). If using this module to fulfill voltage switching, the busbar arrangement should be determined by the setting [CBx.CBConfigMode], 3-262 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory including: Double busbars arrangement ([CBx.CBConfigMode]=DblBusOneCB) 1½ breakers arrangement ([CBx.CBConfigMode]=3/2BusCB or 3/2TieCB) Analog input defines four voltage inputs, UL1, UB1, UL2, UB2, and their usage are as follow: UL1: it connects with three-phase protection voltages (from line or busbar), which mainly are used by distance protection, voltage protection and so on. According to the voltage switching result, synchrocheck logic choose one voltage to be used for synchrocheck function, synchrocheck function requires to judgment the phase identification information of the voltage, which is determined by the setting [MCBrd.CBx.25.Opt_Source_UL1]. If voltage switching function is not used, the reference voltage will be selected from UL1 fixedly. UB1: according to the voltage switching result, synchrocheck logic determined whether the voltage is used for synchrocheck function. Synchrocheck function requires to judgment the phase identification information of the voltage, which is determined by the setting [MCBrd.CBx.25.Opt_Source_UB1]. If voltage switching function is not used, UB1 will be taken as the synchronism voltage. UL2: according to the voltage switching result, synchrocheck logic determined whether the voltage is used for synchrocheck function. Synchrocheck function requires to judgment the phase identification information of the voltage, which is determined by the setting [MCBrd.CBx.25.Opt_Source_UL2]. When voltage switching is available, it is only available for 1½ breakers arrangement, it is fixedly connected to the voltage of the other line of the same diameter in 1½ breakers arrangement. UB2: according to the voltage switching result, synchrocheck logic determined whether the voltage is used for synchrocheck function. Synchrocheck function requires to judgment the phase identification information of the voltage, which is determined by the setting [MCBrd.CBx.25.Opt_Source_UB2]. When voltage switching is available, it is connected to synchronism voltage for double busbars arrangement or 1½ breakers arrangement. Synchrocheck for manual closing supports voltage switching function, and the switching logic is as same as that of synchrocheck for protection closing. The setting [CBx.CBConfigMode] should be set according to the actual primary busbar arrangement, otherwise, the voltage switching of synchrocheck for manual closing will fail, so as to block manual closing with synchrocheck. During dead charge check, when only single-phase voltage is connected to UL1, live voltage is valid if the setting [VTS.En] should be set as “0” and the connected single-phase voltage is higher than the setting [MCBrd.CBx.25.U_Lv], otherwise, live voltage is regarded as live only when three phases voltages are all higher than [MCBrd.CBx.25.U_Lv]. 3-263 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.33.3 Function Block Diagram CSWI01 CSWI01.CILO.EnOpn CSWI01.Op_Opn CSWI01.CILO.EnCls CSWI01.Op_Cls CSWI01.RmtCtrl CSWI01.LocCtrl CSWI01.CILO.Disable CSWI02 CSWI02.CILO.EnOpn CSWI02.Op_Opn CSWI02.CILO.EnCls CSWI02.Op_Cls CSWI02.RmtCtrl CSWI02.LocCtrl CSWI02.CILO.Disable CSWIxx CSWIxx.CILO.EnOpn CSWIxx.Op_Opn CSWIxx.CILO.EnCls CSWIxx.Op_Cls CSWIxx.RmtCtrl CSWIxx.LocCtrl CSWIxx.CILO.Disable BIinput BIinput.RmtCtrl BIinput.RmtCtrl BIinput.LocCtrl BIinput.LocCtrl BIinput.CILO.Disable BIinput.CILO.Disable CSWI01.ManSynCls CSWI01.ManOpn CSWI02.ManSynCls CSWI02.ManOpn xx can be from 02 or 03 to 15 3-264 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.33.4 I/O Signals Table 3.33-1 I/O signals of control No. Input Signal Description From receiving a closing command, this device will continuously check whether the 2 voltages (Incoming voltage and reference voltage) involved in synchronism check (or dead check) can meet the criteria. 1 MCBrd.CBx.25.Ok_Chk Within the duration of [MCBrd.CBx.25.t_Wait_Chk], if the synchronism check (or dead check) criteria are not met, [MCBrd.CBx.25.Ok_Chk] will be set as “0”; if the synchronism check (or dead check) criteria are met, [MCBrd.CBx.25.Ok_Chk] will be set as “1”. 2 CSWIxx.CILO.EnOpn 3 CSWIxx.CILO.EnCls It is used to indicate the interlock status of open output for binary output No.xx. (xx=01~15) It is used to indicate the interlock status of closing output for binary output No.xx. (xx=01~15) It is used to select the local control to binary output No.xx. When the 4 CSWIxx.LocCtrl local control is active, binary output No.xx can only be locally controlled. (xx=01~15) It is used to select the remote control to binary output No.xx. When the 5 CSWIxx.RmtCtrl remote control is active, binary output No.xx can only be remotely controlled from SCADA or control centers. (xx=01~15) It is used to disable the interlock blocking function for control output. If 6 CSWIxx.CILO.Disable the signal “CSWIxx.CILO.Disable” is “1”, binary output No.xx will not be blocked by interlock conditions. (xx=01~15) 7 BIinput.LocCtrl It is used to select the local control to all binary outputs. When the local control is active, all binary outputs can only be locally controlled. It is used to select the remote control to all binary outputs. When the 8 BIinput.RmtCtrl remote control is active, all binary outputs can only be remotely controlled from SCADA or control centers. It is used to disable the interlock blocking function for control output. If 9 BIinput.CILO.Disable the signal “BIinput.CILO.Disable” is “1”, all binary outputs will not be blocked by interlock conditions. When the condition of local control is met and the signal 10 CSWI01.ManSynCls “CSWI01.ManSynCls” is “1”, the output contact [BO_CtrlCls01] is closed to execute manually closing the circuit breaker with synchrocheck. When the condition of local control is met and the signal 11 CSWI01.ManOpn “CSWI01.ManOpn” is “1”, the output contact [BO_CtrlOpn01] is closed to execute manually open the circuit breaker. When the condition of local control is met and the signal 12 CSWI02.ManSynCls “CSWI02.ManSynCls” is “1”, the output contact [BO_CtrlCls02] is closed to execute manually closing the circuit breaker with synchrocheck. (for double circuit breakers application) 13 CSWI02.ManOpn When the condition of local control is met and the signal “CSWI02.ManOpn” is “1”, the output contact [BO_CtrlOpn02] is closed 3-265 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory to execute manually open the circuit breaker. (for double circuit breakers application) 14 MCBrd.CBx.25.Sel_SynChk Synchronism check for manual closing is selected. 15 MCBrd.CBx.25.Sel_NoChk No check for manual closing is selected. No. Output Signal Description 1 CSWIxx.Op_Opn Open output of binary output No.xx. (xx=01~15) 2 CSWIxx.Op_Cls Closing output of binary output No.xx. (xx=01~15) 3 BIinput.LocCtrl In order to be convenient to user configure control output, three same 4 BIinput.RmtCtrl output signals with input signals are available. The relationship with 15 binary output have been configured inside the device. The user only assigns a specific binary input to input signal, the relevant function can 5 BIinput.CILO.Disable be gained. If some binary output need not be controlled by three signals, please cancel the configuration by PCS-Explorer, and configure it independently. 6 MCBrd.CBx.Alm_VTS VT circuit of circuit breaker No.x is abnormal. 3.33.5 Settings Table 3.33-2 Function settings No. Name Range Step Unit Remark Enabling/disabling alarm function 1 MCBrd.CBx.En_Alm_VTS when VT circuit is abnormal 0 or 1 0: disable 1: enable Table 3.33-3 Synchrocheck settings No. Name Range Step Unit Remark Voltage selecting mode of 1 MCBrd.CBx.25.Opt_Source_UL1 Ua line 1 Ub Ua: A-phase voltage Uc Ub: B-phase voltage Uab Uc: C-phase voltage Ubc Uab: AB-phase voltage Uca Ubc: BC-phase voltage Uca: CA-phase voltage Voltage selecting mode of 2 MCBrd.CBx.25.Opt_Source_UB1 Ua bus 1 Ub Ua: A-phase voltage Uc Ub: B-phase voltage Uab Uc: C-phase voltage Ubc Uab: AB-phase voltage Uca Ubc: BC-phase voltage Uca: CA-phase voltage 3 MCBrd.CBx.25.Opt_Source_UL2 Ua Voltage selecting mode for 3-266 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory No. Name Range Step Unit Remark Ub line 2 Uc Ua: A-phase voltage Uab Ub: B-phase voltage Ubc Uc: C-phase voltage Uca Uab: AB-phase voltage Ubc: BC-phase voltage Uca: CA-phase voltage Voltage selecting mode for 4 MCBrd.CBx.25.Opt_Source_UB2 Ua bus 2 Ub Ua: A-phase voltage Uc Ub: B-phase voltage Uab Uc: C-phase voltage Ubc Uab: AB-phase voltage Uca Ubc: BC-phase voltage Uca: CA-phase voltage 5 MCBrd.CBx.25.U_Dd 0.05Un~0.8Un 0.001 V 6 MCBrd.CBx.25.U_Lv 0.5Un~Un 0.001 V Voltage threshold of dead check for manual closing Voltage threshold of live check for manual closing Compensation coefficient of 7 MCBrd.CBx.25.K_Usyn 0.20-5.00 synchronism voltage for manual closing Phase difference limit 8 MCBrd.CBx.25.phi_Diff 0~ 89 1 deg synchronism check of for manual closing Compensation 9 MCBrd.CBx.25.phi_Comp 0~359 difference 1 of phase between synchronous two voltages for manual closing Frequency difference limit of 10 MCBrd.CBx.25.f_Diff 0.02~1.00 0.01 Hz synchronism check for manual closing Voltage difference limit of 11 MCBrd.CBx.25.U_Diff 0.02Un~0.8Un 0.01 V synchronism check for manual closing Synchrocheck mode selection for manual closing 12 MCBrd.CBx.25.SetOpt 0, 1 1 0: determined by external signal 1: determined by the setting Enabling/disabling 13 MCBrd.CBx.25.En_SynChk 0 or 1 synchronism check for manual closing 3-267 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory No. Name Range Step Unit Remark 0: disable 1: enable Enabling/disabling dead line and dead bus (DLDB) check 14 MCBrd.CBx.25.En_DdL_DdB 0 or 1 for manual closing 0: disable 1: enable Enabling/disabling dead line and live bus (DLLB) check 15 MCBrd.CBx.25.En_DdL_LvB 0 or 1 for manual closing 0: disable 1: enable Enabling/disabling live line and dead bus (LLDB) check 16 MCBrd.CBx.25.En_LvL_DdB 0 or 1 for manual closing 0: disable 1: enable Enabling/disabling 17 MCBrd.CBx.25.En_NoChk manual closing without any check 0 or 1 0: disable 1: enable Threshold of rate of frequency change between 18 MCBrd.CBx.25.df/dt 0.00~3.00 0.01 Hz/s both sides synchronism of CB for check of manual closing Enabling/disabling frequency 19 MCBrd.CBx.25.En_df/dtChk slip check for manual closing 0 or 1 0: disable 1: enable Circuit breaker closing time for manual closing 20 MCBrd.CBx.25.t_Close_CB 20~1000 1 ms It is the time from receiving closing command pulse till the CB is completely closed. From receiving a closing command, this device will continuously check whether 21 MCBrd.CBx.25.t_Wait_Chk 5~30 0.001 s between incoming voltage and reference involved in voltage synchronism check (or dead check) can meet 3-268 the criteria. If the PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory No. Name Range Step Unit Remark synchronism check (or dead check) criteria are not met within the duration of this time delay, the failure of synchronism-check (or dead check) will be confirmed. Enabling/disabling synchronism 22 MCBrd.CBx.25.En_VTS_Blk_SynChk block check for manual closing when VT 0 or 1 circuit is abnormal 0: disable 1: enable Enabling/disabling dead 23 MCBrd.CBx.25.En_VTS_Blk_DdChk check for block manual closing when VT circuit is 0 or 1 abnormal 0: disable 1: enable Table 3.33-4 Dual point binary input settings No. Name Range Step Unit Remark It is applied to configure the debouncing time 1 CSWIxx.t_DPU_DPS 0~60000 1 ms for dual-point binary input No.xx. (xx=01, 02….15) Table 3.33-5 Control settings No. Name Range Step Unit Remark It is applied to configure the holding time to 1 CSWIxx.t_PW_Opn 0~60000 1 ms open CB or disconnector for binary output No.xx. (xx=01, 02….15) It is applied to configure the holding time to 2 CSWIxx.t_PW_Cls 0~60000 1 ms close CB or disconnector for binary output No.xx. (xx=01, 02….15) Table 3.33-6 Interlock settings No. Name Range Step Unit Remark Enabling/disabling open output of binary output No.xx controlled by the interlocking 1 CSWIxx.En_Opn_Blk 0 or 1 logic (xx=01, 02….15) 0: disable 1: enable 2 CSWIxx.En_Cls_Blk Enabling/disabling closing output of binary 0 or 1 output No.xx controlled by the interlocking 3-269 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory No. Name Range Step Unit Remark logic (xx=01, 02….15) 0: disable 1: enable 3.34 Faulty Phase Selection 3.34.1 General Application Faulty phase selection is used to discriminate faulty phase for all kinds of fault type. If protection element operates, faulty phase selection is succeeded and the device output tripping command. Faulty phase selection is adaptive to both earthed system and unearthed system. For unearthed system, earthed protection elements should be disabled, such as phase-to-ground distance protection, earth fault protection, and only phase-to-phase protection elements are enabled, such as phase-to-phase distance protection, phase overcurrent protection. 1. Detecting the variation of operating voltage 2. Detecting the phase difference between I0 and I2A 3. When phase overcurrent element operates, pickup phase due to overcurrent is judged as faulty phase. 4. When phase overvoltage element operates, pickup phase due to overvoltage is judged as faulty phase. 5. When phase undervoltage element operates, pickup phase due to undervoltage is judged as faulty phase. 3.34.2 Function Description 3.34.2.1 Variation of Operating Voltage (Faulty Phase Selection Element 1) 1. Variation of phase operating voltage 1) Phase A: ΔUOPA 2) Phase B: ΔUOPB 3) Phase C: ΔUOPC 2. Variation of phase-to-phase operating voltage 1) Phase AB: ΔUOPAB 2) Phase BC: ΔUOPBC 3) Phase CA: ΔUOPCA ΔUOΦMAX=Max(ΔUOPA, ΔUOPB, ΔUOPC) ΔUOΦΦMAX=Max(ΔUOPAB, ΔUOPBC, ΔUOPCA) If ΔUOΦMAX is several times higher than the variation of operating voltages of other two phases, the 3-270 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory single-phase fault is ensured, otherwise, the multi-phase fault is ensured. Table 3.34-1 Relation between ΔUOΦMAX and faulty phase ΔUOΦMAX or ΔUOΦΦMAX Fault phase ΔUOPA Phase A ΔUOPB Phase B ΔUOPC Phase C ΔUOPAB Phase AB ΔUOPBC Phase BC ΔUOPCA Phase CA 3.34.2.2 I0 and I2A (Faulty Phase Selection Element 2) The phase selection algorithm uses the angle relation between I 0 and I2A of the device. As shown in Figure 3.34-1, there are three faulty phase selection regions. Region A 60° -60° Region B Region C 180° Figure 3.34-1 The region of faulty phase selection Depended on the phase relation between I0 and I2A, the faulty phase can be determined. 1. -60º<Arg(I0/I2A)<60º, region A is selected, possible faulty phase is phase A or phase BC. 2. 60º<Arg(I0/I2A)<180º, region B is selected, possible faulty phase is phase B or phase CA. 3. 180º<Arg(I0/I2A)<300º, region C is selected, possible faulty phase is phase C or phase AB. For single-phase earth fault, I0 and I2 of faulty phase are in-phase and its distance element operates. For phase-to-phase earth fault, I0 and I2 of non-faulty phase are in-phase but its distance element does not operate. 3-271 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.34.2.3 Phase Current or Phase Voltage (Faulty Phase Selection Element 3) When phase overcurrent element or phase voltage element, the corresponding phase which is overcurrent, overvoltage or undervoltage will be judged as faulty phase. SIG 50/51Pi.Op SIG 50/51Pi.StA SIG 87STB.Op SIG 87STB.StA SIG 50PVT.Op SIG 50PVT.StA SIG 27Pz.Op SIG 27Pz.St1 SIG 59Pz.Op SIG 59Pz.St1 SIG 50/51Pi.Op SIG 50/51Pi.StB SIG 87STB.Op SIG 87STB.StB SIG 50PVT.Op SIG 50PVT.StB SIG 27Pz.Op SIG 27Pz.St2 SIG 59Pz.Op SIG 59Pz.St2 & & >=1 >=1 Phase A & & >=1 & & & >=1 >=1 Phase B & & >=1 & 3-272 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory SIG 50/51Pi.Op SIG 50/51Pi.StC SIG 87STB.Op SIG 87STB.StC SIG 50PVT.Op SIG 50PVT.StC SIG 27Pz.Op SIG 27Pz.St3 SIG 59Pz.Op SIG 59Pz.St3 & & >=1 >=1 Phase C & & >=1 & Figure 3.34-2 The logic of faulty phase selection i= 1, 2, 3, 4 z=1, 2, 3 3.34.3 Function Block Diagram PhSel PhSA PhSB PhSC GndFlt 3.34.4 I/O Signals Table 3.34-2 I/O signals of faulty phase selection No. Output Signal Description 1 PhSA Phase-A is selected as faulty phase 2 PhSB Phase-B is selected as faulty phase 3 PhSC Phase-C is selected as faulty phase 4 GndFlt Earth fault NOTICE! For single phase earth fault, for example phase-A earth fault, PhsA” and “GndFlt” operate. For phase-to-phase fault, for example phase-BC short-circuit fault, “PhsB” 3-273 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory and “PhsC” operate. For two phase earth fault, for example phase-BC earth fault, “PhsB”, “PhsC” and “GndFlt” operate. For three phases fault, “PhsA”, “PhsB” and “PhsC” operate. 3.35 Fault Location 3.35.1 Application The main objective of line protection is fast, selective and reliable operation for faults on a protected line section. Besides this, information on distance to fault is very important for those involved in operation and maintenance. Reliable information on the fault location greatly decreases the outage of the protected lines and increases the total availability of a power system. This fault location function cannot be used for the transmission line with series compensation. 3.35.2 Function Description 3.35.2.1 Fundamental Principle The fault location is an essential function to various line protection devices, after selecting faulty phase, it measures and indicates the distance to the fault with high accuracy. Thus, the fault can be quickly located for repairs. The calculation algorithm considers the effect of load currents, double-end infeed and additional fault resistance. Both double-end fault location and single-end fault location are available in line differential relay, but only single-end fault location is provided in other relays. The calculation equation is: Where: Dist: The distance of fault location according to the Zcalc (km) Zcalc: The impedance value calculated from the location of protection device to fault point Zl: The impedance value of the whole line + mutual impedance Length: The input length of transmission line (km) 3.35.2.2 Mutual Compensation When an earth fault occurred on a line of parallel lines arrangement, a distance relay at one end of the faulty line will tend to underreach whilst the distance relay at the other end will tend to overreach. Usually the degree of underreach or overreach is acceptable, however, for cases where precise fault location is required for long lines with high mutual coupling, mutual compensation is then required to improve the distance measurement. Practically, the mutual effect between the parallel lines is insignificant to positive and negative sequence and thus the mutual compensation is only for zero sequence 3-274 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory A Ia B ZM k C Ic ZS D (1-k)ZL kZL ZL The principle in the application of mutual compensation is shown as follows with the aid of following sequence network diagram figure. The diagram indicates a parallel lines arrangement with an earth fault at location k on line CD. The equivalent sequence network for an earth fault on a parallel lines arrangement with single source is shown as below. Ia1 ZL1 ZS1 kZL1 (1-k)ZL1 Ic1 Ia2 ZL2 ZS2 kZL2 (1-k)ZL2 Ic2 Ia0 ZL0 ZS0 Z0M kZL0 (1-k)ZL0 Ic0 Figure 3.35-1 Equivalent sequence network The device at location C without mutual compensation will have voltage URC and current IRC measured as shown in the expression URC is the voltage of the device at location C. If the line is fully transposed, ZL1=ZL2, Then 3-275 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory The impedance presented to the device is: For an earth fault, , With the mutual compensation enabled, (Actual distance of the fault) The residual current from the parallel line should be added to the device. It should be connected to terminal 08 and star point of the parallel line CT connected to terminal 07 as shown in the following figure. Please note the connection diagram and the terminal numbers are for reference only. The final connection terminals are subject to the device configuration at site. 3-276 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory A B C P2 S2 P2 S2 P1 S1 P1 S1 02 01 02 01 04 03 04 03 06 05 06 05 08 07 08 07 NOTICE! The mutual compensation only is to improve the accuracy of fault location for parallel lines arrangement, and it is not used by settings calculation of earth fault protections. 3.35.3 Function Block Diagram FL FPS_Fault FD.Pkp Fault_Location Fault_Phase Fault_Phase_Curr Fault_Resid_Curr 3-277 PCS-902 Line Distance Relay Date: 2019-03-01 3 Operation Theory 3.35.4 I/O Signals Table 3.35-1 I/O signals of fault location No. Input Signal Description 1 FPS_Fault Faulty phase selection 2 FD.Pkp The device picks up No. Output Signal Description 1 Fault_Location The result of fault location 2 Faulty_Phase The selected faulty phase 3 Fault_Phase_Curr Maximum faulty current 4 Fault_Resid_Curr Maximum residual current 3-278 PCS-902 Line Distance Relay Date: 2019-03-01 4 Supervision 4 Supervision Table of Contents 4 Supervision ........................................................................................ 4-a 4.1 Overview .......................................................................................................... 4-1 4.2 Supervision Alarms ......................................................................................... 4-1 4.3 Relay Self-supervision.................................................................................... 4-8 4.3.1 Relay Hardware Monitoring ................................................................................................. 4-8 4.3.2 Fault Detector Monitoring .................................................................................................... 4-8 4.3.3 Check Setting ...................................................................................................................... 4-8 4.4 AC Input Monitoring ........................................................................................ 4-9 4.4.1 Voltage/current Drift Monitoring and Auto-adjustment......................................................... 4-9 4.4.2 Sampling Monitoring ............................................................................................................ 4-9 4.5 Secondary Circuit Monitoring ........................................................................ 4-9 4.5.1 Opto-coupler Power Supervision ......................................................................................... 4-9 4.5.2 Circuit Breaker Supervision ................................................................................................. 4-9 List of Tables Table 4.2-1 Alarm description..................................................................................................... 4-1 Table 4.2-2 Troubleshooting ....................................................................................................... 4-6 PCS-902 Line Distance Relay 4-a Date: 2019-03-01 4 Supervision 4-b PCS-902 Line Distance Relay Date: 2019-03-01 4 Supervision 4.1 Overview Protection system is in quiescent state under normal conditions, and it is required to respond promptly for faults occurred on power system. When the device is in energizing process before the LED “HEALTHY” is on, the device need to be checked to ensure no abnormality. Therefore, the automatic supervision function, which checks the health of the protection system when startup and during normal operation, plays an important role. The numerical relay based on the microprocessor operations is suitable for implementing this automatic supervision function of the protection system. In case a defect is detected during initialization when DC power supply is provided to the device, the device will be blocked with indication and alarm of relay out of service. It is suggested a trial recovery of the device by re-energization. Please contact supplier if the device is still failure. When a failure is detected by the automatic supervision, it is followed by a LCD message, LED indication and alarm contact outputs. The failure alarm is also recorded in event recording report and can be printed If required. 4.2 Supervision Alarms Hardware circuit and operation status of the device are self-supervised continuously. If any abnormal condition is detected, information or report will be displayed and a corresponding alarm will be issued. A minor abnormality may block a certain number of protections functions while the other functions can still work. However, if severe hardware failure or abnormality, such as PWR module failure, DC converter failure and so on, are detected, all protection functions will be blocked and the LED “HEALTHY” will be extinguished and blocking output contacts BO_FAIL will be given. The protective device then can not work normally and maintenance is required to eliminate the failure. All the alarm signals and the corresponding handling suggestions are listed below. NOTICE! If the device is blocked or alarm signal is sent during operation, please do find out its reason with the help of self-diagnostic record. If the reason can not be found at site, please notify the factory NR. Please do not simply press button “TARGET RESET” on the protection panel or re-energize on the device. Table 4.2-1 Alarm description No. Item Description Blocking Device Fail Signals The device fails. 1 Fail_Device This signal will be pick up if any fail signal picks up and it Blocked will drop off when all fail signals drop off. 2 Fail_Setting_OvRange Set value of any setting is out of scope. This signal will pick up instantaneously and will be PCS-902 Line Distance Relay Blocked 4-1 Date: 2019-03-01 4 Supervision No. Item Description Blocking Device latched unless the recommended handling suggestion is adopted. 3 Fail_BoardConfig Mismatch between the configuration of plug-in modules and the designing drawing of an applied-specific project. Blocked After configuration file is updated, settings of the file and settings saved on the device are not matched. 4 Fail_SettingItem_Chgd This signal will pick up instantaneously and will be Blocked latched unless the recommended handling suggestion is adopted. Error is found during checking memory data. 5 Fail_Memory This signal will pick up instantaneously and will be latched unless the recommended handling suggestion is Blocked adopted. Error is found during checking settings. 6 Fail_Settings This signal will pick up instantaneously and will be latched unless the recommended handling suggestion is Blocked adopted. DSP chip is damaged. 7 Fail_DSP This signal will pick up instantaneously and will be latched unless the recommended handling suggestion is Blocked adopted. Communication between two DSP chips is abnormal 8 Fail_DSP_Comm This signal will pick up instantaneously and will drop off Blocked instantaneously. Software configuration is incorrect. 9 Fail_Config This signal will pick up instantaneously and will be latched unless the recommended handling suggestion is Blocked adopted. AC current and voltage samplings are abnormal. 10 Fail_Sample This signal will pick up with a time delay of 200ms and will be latched unless the recommended handling Blocked suggestion is adopted. 11 MCBrd.Fail_Sample 12 MCBrd.Fail_Settings For DSP plug-in module for measurement and control in slot 06, AC current and voltage samplings are abnormal Error is found during checking the settings of DSP plug-in module for measurement and control in slot 06. Blocked Blocked Alarm Signals The device is abnormal. 13 Alm_Device This signal will be pick up if any alarm signal picks up Unblocked and it will drop off when all alarm signals drop off. 14 Alm_Insuf_Memory 15 Alm_CommTest The memory of MON plug-in module is insufficient. The device is in the communication test mode. This signal will pick up instantaneously and will drop off 4-2 Unblocked Unblocked PCS-902 Line Distance Relay Date: 2019-03-01 4 Supervision No. Item Description Blocking Device instantaneously. The error is found during MON module checking 16 Alm_Settings_MON settings of device. This signal will pick up with a time delay of 10s and will Unblocked be latched unless re-powering or rebooting the device. The error is found during checking the version of 17 Alm_Version software downloaded to the device. This signal will pick up instantaneously and will drop off Unblocked instantaneously. The active group set by settings in device and that set 18 Alm_BI_SettingGrp by binary input are not matched. This signal will pick up instantaneously and will drop off Unblocked instantaneously. Data frame is abnormal between two DSP modules. 19 Alm_DSP_Frame This signal will pick up instantaneously and will drop off Unblocked instantaneously. The power supply of BI plug-in module in slot xx is 20 Bxx.Alm_OptoDC abnormal. This signal will pick up with a time delay of 10s and will Unblocked drop off with a time delay of 10s. Fault detector element operates for longer than 50s. 21 Alm_Pkp_FD This signal will pick up with a time delay of 50s and will Unblocked drop off with a time delay of 10s. Neutral current fault detector element operates for 22 Alm_Pkp_I0 longer than 10s. This signal will pick up with a time delay of 10s and will Unblocked drop off with a time delay of 10s. Protection VT circuit fails. 23 VTS.Alm This signal will pick up with a time delay [VTS.t_DPU] Unblocked and will drop off with a time delay [VTS.t_DDO]. Protection VT circuit of neutral point fails. 24 VTNS.Alm This signal will pick up with a time delay [VTS.t_DPU] Unblocked and will drop off with a time delay [VTS.t_DDO]. VT circuit of circuit breaker No.x is abnormal. 25 MCBrd.CBx.Alm_VTS This signal will pick up with a time delay of 1.25s and will Unblocked drop off with a time delay of 10s. CT circuit of corresponding circuit breaker No.x fails. 26 CBx.CTS.Alm This signal will pick up with a time delay of 10s and will Unblocked drop off with a time delay of 10s. The 27 CBx.Alm_52b auxiliary normally closed contact (52b) of corresponding circuit breaker No.x is abnormal. This signal will pick up with a time delay of 10s and will Unblocked drop off with a time delay of 10s. PCS-902 Line Distance Relay 4-3 Date: 2019-03-01 4 Supervision No. Item Description Blocking Device The device is in maintenance state. 28 BI_Maintenance This signal will pick up with a time delay of 150ms and Unblocked will drop off with a time delay of 150ms. 29 Alm_TimeSyn Unblocked Time synchronization abnormality alarm. It is an overall alarm signal and will be issued if any of the following abnormalities is generated: 1. A network storm exists in the GOOSE network A or GOOSE network B. 30 Alm_StatGOOSE 2. The GOOSE configuration file is incorrect. 3. The connection of GOOSE network A or GOOSE Unblocked network B is disconnected. 4. Between GOOSE control blocks received on network and GOOSE control blocks defined in GOOSE configuration file are unmatched. Frequency of the system is higher than 65Hz or lower 31 Alm_Freq than 45Hz. This signal will pick up with a time delay of 100ms and Unblocked will drop off with a time delay of 10s. 32 Alm_Sparexx (xx=01~08) Spare alarm signals The time delay of pickup and dropoff for these alarm Unblocked signals can be set by PCS-Explorer. Protection Element Alarm Signals Channel x is abnormal 33 FOx.Alm This signal will pick up with a time delay of 100ms and Unblocked will drop off with a time delay of 1s. Received ID from the remote end is not as same as the 34 FOx.Alm_ID setting [FOx.RmtID] of the device in local end This signal will pick up with a time delay of 100ms and Unblocked will drop off with a time delay of 1s. No valid frame of channel x is received. 35 FOx.Alm_NoValFram This signal will pick up with a time delay of 100ms and Unblocked will drop off with a time delay of 1s. Rate of error code of channel x is larger than 40 error 36 FOx.Alm_CRC codes per second. This signal will pick up instantaneously and will drop off Unblocked with a time delay of 10s. Channel x is out of service due to receive error codes 37 FOx.Alm_Off after device picking up. This signal will pick up instantaneously and will drop off Unblocked instantaneously. 38 FOx.Alm_Connect Optical fibre of channel x is connected wrongly. This signal will pick up with a time delay of 100ms and 4-4 Unblocked PCS-902 Line Distance Relay Date: 2019-03-01 4 Supervision No. Item Description Blocking Device will drop off with a time delay of 1s. Stage 3 of negative-sequence overcurrent protection 39 50/51Q3.Alm 40 59P1.Alm Stage 1 of overvoltage protection alarms. Unblocked 41 59P2.Alm Stage 2 of overvoltage protection alarms. Unblocked 42 59P3.Alm Stage 3 of overvoltage protection alarms. Unblocked 43 59G3.Alm 44 27P1.Alm Stage 1 of undervoltage protection alarms. Unblocked 45 27P2.Alm Stage 2 of undervoltage protection alarms. Unblocked 46 27P3.Alm Stage 3 of undervoltage protection alarms. Unblocked 47 49-1.Alm 48 49-2.Alm operates to alarm. Stage 3 of residual overvoltage protection operates to alarm. Stage 1 of thermal overload protection operates to alarm. Stage 2 of thermal overload protection operates to alarm. Unblocked Unblocked Unblocked Unblocked Differential current is abnormal. 49 87STB.Alm_Diff This signal will pick up with a time delay of 1s and will Unblocked drop off with a time delay of 10s. disconnector position is abnormal. 50 87STB.Alm_89b_DS This signal will pick up with a time delay of 1s and will Unblocked drop off with a time delay of 10s. 51 46BC.Alm 52 CBx.Alm_Invalid_Sel Broken-conductor protection operates to alarm. Voltage selection corresponding to circuit breaker No.x is invalid. Unblocked Unblocked Synchronism voltage circuit corresponding to circuit 53 CBx.25.Alm_VTS_Usyn breaker No.x is abnormal. This signal will pick up with a time delay of 1.25s and will Unblocked drop off with a time delay of 10s. Reference voltage circuit corresponding to circuit 54 CBx.25.Alm_VTS_Uref breaker No.x is abnormal. This signal will pick up with a time delay of 1.25s and will Unblocked drop off with a time delay of 10s. 55 CBx.79.Fail_Rcls 56 CBx.79.Fail_Chk Auto-reclosing corresponding to circuit breaker No.x fails. Synchrocheck for AR corresponding to circuit breaker No.x fails. Unblocked Unblocked Input signal of receiving transfer trip is energized for 57 TT.Alm longer than [TT.t_Op]+5s and it will drop off with a time Unblocked delay of 10s. PCS-902 Line Distance Relay 4-5 Date: 2019-03-01 4 Supervision Table 4.2-2 Troubleshooting No. Item Handling suggestion Fail Signals 1 Fail_Device The signal is issued with other specific fail signals, and please refer to the handling suggestion other specific alarm signals. Please reset setting values according to the range described in the instruction 2 Fail_Setting_OvRange manual, then re-power or reboot the device and the device will restore to normal operation state. 5. Go to the menu “Information→Borad Info”, check the abnormality information. 3 Fail_BoardConfig 6. For the abnormality board, if the board is not used, then remove, and if the board is used, then check whether the board is installed properly and work normally. Please check the settings mentioned in the prompt message on the LCD, and 4 Fail_SettingItem_Chgd go to the menu “Settings” and select “Confirm_Settings” item to confirm settings. Then, the device will restore to normal operation stage. 5 Fail_Memory Please inform the manufacture or the agent for repair. 6 Fail_Settings Please inform the manufacture or the agent for repair. 7 Fail_DSP 8 Fail_DSP_Comm 9 Fail_Config Chips are damaged and please inform the manufacture or the agent replacing the module. Please inform the manufacture or the agent for repair. Please inform configuration engineers to check and confirm visualization functions of the device 1. Please make the device out of service. 10 Fail_Sample 2. Then check if the analog input modules and wiring connectors connected to those modules are installed at the position. 3. Re-power the device and the device will restore to normal operation state. 1. Please make the device out of service. 11 MCBrd.Fail_Sample 2. Then check if analog input modules and wiring connectors connected to those modules are installed at the position. 3. Re-power the device and the device will restore to normal operation state. 12 MCBrd.Fail_Settings Please inform the manufacturer or the agent for repair. Alarm Signals 13 Alm_Device 14 Alm_Insuf_Memory 15 Alm_CommTest 16 Alm_Settings_MON The signal is issued with other specific alarm signals, and please refer to the handling suggestion other specific alarm signals. Please replace MON plug-in module. No special treatment is needed, and disable the communication test function after the completion of the test. Please inform the manufacture or the agent for repair. Users may pay no attention to the alarm signal in the project commissioning 17 Alm_Version stage, but it is needed to download the latest package file (including correct version checksum file) provided by R&D engineer to make the alarm signal disappear. Then users get the correct software version. It is not allowed that 4-6 PCS-902 Line Distance Relay Date: 2019-03-01 4 Supervision No. Item Handling suggestion the alarm signal is issued on the device already has been put into service. the devices having being put into service so that the alarm signal disappears. Please check the value of setting [Active_Grp] and binary input of indicating 18 Alm_BI_SettingGrp active group, and make them matched. Then the “ALARM” LED will be extinguished and the corresponding alarm message will disappear and the device will restore to normal operation state. 19 Alm_DSP_Frame Please inform the manufacture or the agent for repair. 1. check whether the binary input module is connected to the power supply. 2. check whether the voltage of power supply is in the required range. 20 Bxx.Alm_OptoDC 3. After the voltage for binary input module restores to normal range, the “ALARM” LED will be extinguished and the corresponding alarm message will disappear and the device will restore to normal operation state. Please check secondary values and protection settings. If settings are not set 21 Alm_Pkp_FD reasonable to make fault detectors pick up, please reset settings, and then the alarm message will disappear and the device will restore to normal operation state. Please check secondary values and protection settings. If settings are not set 22 Alm_Pkp_I0 reasonable to make fault detectors pick up, please reset settings, and then the alarm message will disappear and the device will restore to normal operation state. 23 VTS.Alm 24 VTNS.Alm 25 MCBrd.CBx.Alm_VTS 26 CBx.CTS.Alm 27 CBx.Alm_52b Please check the corresponding VT secondary circuit. After the abnormality is eliminated, the device returns to normal operation state. Please check the corresponding VT secondary circuit of neutral point. After the abnormality is eliminated, the device returns to normal operation state. Please check the corresponding VT secondary circuit. After the abnormality is eliminated, the device returns to normal operation state. Please check the corresponding CT secondary circuit. After the abnormality is eliminated, the device returns to normal operation state. Please check the auxiliary contact of CB. After the abnormality is eliminated, the device returns to normal operation state. After maintenance is finished, please de-energized the binary input 28 BI_Maintenance [BI_Maintenance] and then the alarm will disappear and the device restore to normal operation state. 1. check whether the selected clock synchronization mode matches the clock synchronization source; 2. check whether the wiring connection between the device and the clock 29 Alm_TimeSyn synchronization source is correct 3. check whether the setting for selecting clock synchronization (i.e. [Opt_TimeSyn]) is set correctly. If there is no clock synchronization, please set the setting [Opt_TimeSyn] as ”No TimeSyn”. 4. After the abnormality is removed, the “ALARM” LED will be extinguished PCS-902 Line Distance Relay 4-7 Date: 2019-03-01 4 Supervision No. Item Handling suggestion and the corresponding alarm message will disappear and the device will restore to normal operation state. Please check Ethernet switch of GOOSE network, GOOSE configuration file 30 Alm_StatGOOSE 31 Alm_Freq Adjust the system operating mode Alm_Sparexx Find the reason according to specific problem. (These signals are (xx=01~08) user-defined.) 32 and GOOSE network. Operation Alarm Signals 33 FOx.Alm Please check the connection of optical fibre channel. 34 FOx.Alm_ID Please check the connection of optical fibre channel. 35 FOx.Alm_NoValFram Please check the connection of optical fibre channel. 36 FOx.Alm_CRC Please check the connection of optical fibre channel. 37 FOx.Alm_Off Please check the connection of optical fibre channel. 38 FOx.Alm_Connect Please check the connection of optical fibre channel. (For example, receiving and sending are inconsistent, or channel 1 and channel 2 are inconsistent) Please check the corresponding current circuit. After the abnormality is 39 87STB.Alm_Diff eliminated, “ALARM” LED will go off automatically and device returns to normal operation state with a time delay of 10s. Please check the corresponding binary input secondary circuit. After the 40 87STB.Alm_89b_DS abnormality is eliminated, “ALARM” LED will go off automatically and device returns to normal operation state with a time delay of 10s. Please check the corresponding binary input secondary circuit. After the 41 TT.Alm abnormality is eliminated, “ALARM” LED will go off automatically and device returns to normal operation state with a time delay of 10s. 4.3 Relay Self-supervision 4.3.1 Relay Hardware Monitoring All chips on DSP module are monitored to ensure whether they are damaged or having errors. If any one of them is detected damaged or having error, the alarm signal [Fail_DSP] is issued with the device being blocked. 4.3.2 Fault Detector Monitoring When neutral current fault detector picks up and lasts for longer than 20 seconds, an alarm [Alm_Pkp_I0] will be issued without the device blocked. When any fault detector picks up for longer than 50s, an alarm will be issued [Alm_Pkp_FD] without the device blocked. 4.3.3 Check Setting This relay has 10 setting groups, only one Setting group could be activated (is active) at a time. The settings of active setting group are checked to ensure they are reasonable. If settings are checked to be unreasonable or out of setting scopes, a corresponding alarm signal will be issued, and the device is also blocked. 4-8 PCS-902 Line Distance Relay Date: 2019-03-01 4 Supervision 4.4 AC Input Monitoring 4.4.1 Voltage/current Drift Monitoring and Auto-adjustment Zero point of voltage and current may drift due to variation of temperature or other environment factors. The device continually traces the drift and adjust it to normal value automatically. 4.4.2 Sampling Monitoring AC current and voltage samplings of protection DSP and fault detector DSP are monitored and if the samples of protection DSP and fault detector DSP are detected to be wrong or inconsistent between them, the alarm signal [Fail_Sample] will be issued and the device will be blocked. 4.5 Secondary Circuit Monitoring 4.5.1 Opto-coupler Power Supervision Positive power supply of opto-coupler is continually monitored. If an error or damage has occurred, an alarm [Bxx.Alm_OptoDC] will be issued. 4.5.2 Circuit Breaker Supervision If 52b of three phases are energized ,which indicates circuit breaker is open and there is no current detected in the line, the line will be considered to be out of service. SOTF protection will be enabled after 50ms. If 52b of three phases are energized that indicates circuit breaker is open but there is still current detected in the line (the measured current is greater than a settable threshold value) or three-phase circuit breaker is in pole disagreement, an alarm signal [Alm_52b] will be issued after 10 seconds. PCS-902 Line Distance Relay 4-9 Date: 2019-03-01 4 Supervision 4-10 PCS-902 Line Distance Relay Date: 2019-03-01 5 Management 5 Management Table of Contents 5 Management ...................................................................................... 5-a 5.1 Measurement ................................................................................................... 5-1 5.1.1 Measurement Values ........................................................................................................... 5-1 5.1.2 Metering Value ..................................................................................................................... 5-6 5.2 Recording ........................................................................................................ 5-6 5.2.1 Overview .............................................................................................................................. 5-6 5.2.2 Event Recording .................................................................................................................. 5-7 5.2.3 Disturbance Recording ........................................................................................................ 5-7 5.2.4 Present Recording ............................................................................................................... 5-9 PCS-902 Line Distance Relay 5-a Date: 2019-03-01 5 Management 5-b PCS-902 Line Distance Relay Date: 2019-03-01 5 Management 5.1 Measurement PCS-902 performs continuous measurement of the analogue input quantities. The current full scale of relay is 40 times of rated current, and there is no effect to the performance of IED due to overflowing of current full scale. The device samples 24 points per cycle and calculates the RMS value in each interval and updated the LCD display in every 0.5 second. The measurement data can be displayed on the LCD of the relay front panel or on the local/remote PC via software tool. Navigate the menu to view the sampling value through LCD screen. NOTICE! This device can be configured to support single circuit breaker application or double circuit breakers application by PCS-Explorer. For double circuit breakers mode, the prefix “CBx.” is added to related measurement quantities for circuit breaker No.x (x=1 or 2). 5.1.1 Measurement Values Access path: MainMenu “Measurements” “Measurements1” “Measurements1” is used to display measured values from protection calculation DSP. The measurement values can be displayed in primary value or secondary value by the setting [Opt_Display_Status]. No. Symbol Definition Resolution Unit 1 CBx.Ia Phase-A current corresponding to circuit breaker No.x 0.000 A 2 CBx.Ib Phase-B current corresponding to circuit breaker No.x 0.000 A 3 CBx.Ic Phase-C current corresponding to circuit breaker No.x 0.000 A 4 CBx.3I0 Residual current corresponding to circuit breaker No.x 0.000 A 5 Ia 0.000 A 6 Ib 0.000 A 7 Ic 0.000 A 8 I1 The positive-sequence current 0.000 A 9 I2 The negative-sequence current 0.000 A 10 3I0 0.000 A 11 3I0Adj Residual current from parallel line 0.000 A 12 Ua Phase-A protection voltage 0.000 V 13 Ub Phase-B protection voltage 0.000 V 14 Uc Phase-C protection voltage 0.000 V 15 Uab Phase-AB protection voltage 0.000 V Phase-A current (summation current for double circuit breakers mode) Phase-B current (summation current for double circuit breakers mode) Phase-C current (summation current for double circuit breakers mode) Residual current (summation current for double circuit breakers mode) PCS-902 Line Distance Relay 5-1 Date: 2019-03-01 5 Management No. Symbol Definition Resolution Unit 16 Ubc Phase-BC protection voltage 0.000 V 17 Uca Phase-CA protection voltage 0.000 V 18 UB1 The voltage of busbar No.1 0.000 V 19 UL2 The voltage of line No.2 0.000 V 20 UB2 The voltage of busbar No.2 0.000 V 21 U1 The positive-sequence voltage 0.000 V 22 U2 The negative-sequence voltage 0.000 V 23 3U0 The calculated residual voltage 0.000 V 24 Ang (Ua-Ub) 0 deg 25 Ang (Ub-Uc) 0 deg 26 Ang (Uc-Ua) 0 deg 27 Ang (Ua-Ia) 0 deg 28 Ang (Ub-Ib) 0 deg 29 Ang (Uc-Ic) 0 deg 30 CBx.Ang (Ia-Ib) 0 deg 31 CBx.Ang (Ib-Ic) 0 deg 0 deg 0 deg 0 deg 0 deg 0 deg 0 deg Phase angle between phase-A voltage and phase-B voltage Phase angle between phase-B voltage and phase-C voltage Phase angle between phase-C voltage and phase-A voltage Phase angle between phase-A voltage and phase-A current Phase angle between phase-B voltage and phase-B current Phase angle between phase-C voltage and phase-C current Phase angle between phase-A current and phase-B current corresponding to circuit breaker No.x Phase angle between phase-B current and phase-C current corresponding to circuit breaker No.x Phase angle of reference vector, which can be set as 32 AngRef positive-sequence voltage, positive-sequence current of circuit breaker No.1 or positve-sequence current of circuit breaker No.2 33 CBx.Ang (Ia) 34 CBx.Ang (Ib) 35 CBx.Ang (Ic) Phase angle between reference vector and phase-A current corresponding to circuit breaker No.x Phase angle between reference vector and phase-B current corresponding to circuit breaker No.x Phase angle between reference vector and phase-C current corresponding to circuit breaker No.x Phase angle between reference vector and phase-A 36 Ang (Ia) current (summation current for double circuit breakers mode) 37 Ang (Ib) Phase angle between reference vector and phase-B 5-2 PCS-902 Line Distance Relay Date: 2019-03-01 5 Management No. Symbol Definition Resolution Unit 0 deg 0 deg 0 deg 0 deg 0 deg 0 deg 0 deg 0 deg current (summation current for double circuit breakers mode) Phase angle between reference vector and phase-C 38 Ang (Ic) current (summation current for double circuit breakers mode) Phase angle between reference vector and residual 39 Ang (3I0Adj) 40 Ang (Ua) 41 Ang (Ub) 42 Ang (Uc) 43 Ang (UB1) 44 Ang (UL2) 45 Ang (UB2) 46 f Frequency of protection voltage 0.000 Hz 47 P1 The positive-sequence active power 0.000 W 48 CBx.25.f_Ref 0.000 Hz 49 CBx.25.f_Syn 0.000 Hz 0.000 Hz 0 V 0.000 V current from parallel line Phase angle between reference vector and phase-A voltage Phase angle between reference vector and phase-B voltage Phase angle between reference vector and phase-C voltage Phase angle between reference vector and the voltage of busbar No.1 Phase angle between reference vector and the voltage of line No.2 Phase angle between reference vector and the voltage of busbar No.2 Frequency of reference voltage corresponding to circuit breaker No.x Frequency of synchronism voltage corresponding to circuit breaker No.x Frequency difference between protection voltage and 50 CBx.25.f_Diff synchronism voltages corresponding to circuit breaker No.x Phase angle difference between protection voltage and 51 CBx.25.phi_Diff synchronism voltages corresponding to circuit breaker No.x Voltage difference between protection voltage and 52 CBx.25.U_Diff synchronism voltages corresponding to circuit breaker No.x Access path: MainMenu “Measurements” “Measurements2” “Measurements2” is used to display measured values from fault detector DSP. The measurement values can be displayed in primary value or secondary value by the setting [Opt_Display_Status]. PCS-902 Line Distance Relay 5-3 Date: 2019-03-01 5 Management No. Symbol Definition Resolution Unit 1 CBx.Ia Phase-A current corresponding to circuit breaker No.x 0.000 A 2 CBx.Ib Phase-B current corresponding to circuit breaker No.x 0.000 A 3 CBx.Ic Phase-C current corresponding to circuit breaker No.x 0.000 A 4 Ia 0.000 A 5 Ib 0.000 A 6 Ic 0.000 A 7 49-1.Accu_A 0.000 % 8 49-1.Accu_B 0.000 % 9 49-1.Accu_C 0.000 % 10 49-2.Accu_A 0.000 % 11 49-2.Accu_B 0.000 % 12 49-2.Accu_C 0.000 % Phase-A current (summation current for double circuit breakers mode) Phase-B current (summation current for double circuit breakers mode) Phase-C current (summation current for double circuit breakers mode) Phase-A thermal accumulation of stage 1 of thermal overload protection Phase-B thermal accumulation of stage 1 of thermal overload protection Phase-C thermal accumulation of stage 1 of thermal overload protection Phase-A thermal accumulation of stage 2 of thermal overload protection Phase-B thermal accumulation of stage 2 of thermal overload protection Phase-C thermal accumulation of stage 2 of thermal overload protection Access path: MainMenu “Measurements” “Measurements3” “Measurements3” is used to display measured values of other calculated quantities related to the measurement and control. The measurement values are always displayed in primary value. No. Symbol 1 CBx.Ia 2 CBx.Ib 3 CBx.Ic 4 CBx.I1 5 CBx.I2 6 CBx.3I0 Definition The primary value of phase-A current corresponding to circuit breaker No.x The primary value of phase-B current corresponding to circuit breaker No.x The primary value of phase-C current corresponding to circuit breaker No.x The primary value of positive-sequence current corresponding to circuit breaker No.x The primary value of negative-sequence current corresponding to circuit breaker No.x The primary value of calculated corresponding to circuit breaker No.x 5-4 residual current Resolution Unit 0.000 A 0.000 A 0.000 A 0.000 A 0.000 A 0.000 A PCS-902 Line Distance Relay Date: 2019-03-01 5 Management No. Symbol Definition The primary value of phase-A current (summation current Resolution Unit 0.000 A 0.000 A 0.000 A 7 Ia 8 Ib 9 Ic 10 Ua The primary value of phase-A voltage 0.000 kV 11 Ub The primary value of phase-B voltage 0.000 kV 12 Uc The primary value of phase-C voltage 0.000 kV 13 Uab The primary value of phase-AB voltage 0.000 kV 14 Ubc The primary value of phase-BC voltage 0.000 kV 15 Uca The primary value of phase-CA voltage 0.000 kV 16 U1 The primary value of positive-sequence voltage 0.000 kV 17 U2 The primary value of negative-sequence voltage 0.000 kV 18 3U0 The primary value of calculated residual voltage 0.000 kV 19 UB1 The primary value of voltage of busbar No.1 0.000 kV 20 UL2 The primary value of voltage of line No.2 0.000 kV 21 UB2 The primary value of voltage of busbar No.2 0.000 kV 22 f Frequency of protection voltage 0.000 Hz 23 UB1.f Frequency of busbar 1 voltage 0.000 Hz 24 UL2.f Frequency of line 2 voltage 0.000 Hz 25 UB2.f Frequency of busbar 2 voltage 0.000 Hz 26 CBx.P 0.000 MW 27 CBx.Q 0.000 MVAr 28 CBx.S 0.000 MVA 29 CBx.Cos 0.000 - 30 CBx.Pa 0.000 MW 31 CBx.Pb 0.000 MW 32 CBx.Pc 0.000 MW 33 CBx.Qa 0.000 MVAr for double circuit breakers mode) The primary value of phase-B current (summation current for double circuit breakers mode) The primary value of phase-C current (summation current for double circuit breakers mode) The primary value of active power corresponding to circuit breaker No.x The primary value of reactive power corresponding to circuit breaker No.x The primary value of apparent power corresponding to circuit breaker No.x The value of power factor corresponding to circuit breaker No.x The primary value of phase-A active power corresponding to circuit breaker No.x The primary value of phase-B active power corresponding to circuit breaker No.x The primary value of phase-C active power reactive power corresponding to circuit breaker No.x The primary value of phase-A PCS-902 Line Distance Relay 5-5 Date: 2019-03-01 5 Management No. Symbol Definition Resolution Unit 0.000 MVAr 0.000 MVAr 0.000 - 0.000 - 0.000 - 0.000 Hz 0.000 Hz/s 0.00 deg 0.000 kV corresponding to circuit breaker No.x 34 CBx.Qb 35 CBx.Qc 36 CBx.Cosa 37 CBx.Cosb 38 CBx.Cosc The primary value of phase-B reactive power reactive power corresponding to circuit breaker No.x The primary value of phase-C corresponding to circuit breaker No.x The value of phase-A power factor corresponding to circuit breaker No.x The value of phase-B power factor corresponding to circuit breaker No.x The value of phase-C power factor corresponding to circuit breaker No.x The frequency difference between reference side and 39 CBx.f_Diff incoming side for manual closing synchrocheck corresponding to circuit breaker No.x The rate of frequency change between reference side and 40 CBx.df/dt incoming side for manual closing synchrocheck corresponding to circuit breaker No.x Phase angle difference between reference side and 41 CBx.phi_Diff incoming side for manual closing synchrocheck corresponding to circuit breaker No.x The primary value of voltage difference between 42 CBx.U_Diff reference side and incoming side for manual closing synchrocheck corresponding to circuit breaker No.x 5.1.2 Metering Value Access path: MainMenu “Measurements” “Metering” “Metering” is used to display metering values of active and reactive energy. The metering values are always displayed in primary value. No. Symbol Definition Resolution Unit 1 PHr+_Pri The primary positive active energy 0.000 MWh 2 PHr-_Pri The primary negative active energy 0.000 MWh 3 QHr+_Pri The primary positive reactive energy 0.000 MVAh 4 QHr-_Pri The primary negative reactive energy 0.000 MVAh 5.2 Recording 5.2.1 Overview PCS-902 provides the following recording functions: 5-6 PCS-902 Line Distance Relay Date: 2019-03-01 5 Management 1. Event recording 2. Disturbance recording 3. Present recording All the recording information except waveform can be viewed on local LCD or by printing. Waveform could only be printed or extracted with PCS-Explorer software tool and a waveform analysis software. 5.2.2 Event Recording 5.2.2.1 Overview The device can store the latest 1024 disturbance records, 1024 binary events, 1024 supervision events, 256 control logs and 1024 device logs. All the records are stored in non-volatile memory, and when the available space is exhausted, the oldest record is automatically overwritten by the latest one. 5.2.2.2 Disturbance Records When any protection element operates or drops off, such as fault detector, distance protection etc., they will be logged in event records. 5.2.2.3 Supervision Events The device is under automatic supervision all the time. If there are any failure or abnormal condition detected, such as, chip damaged, VT circuit failure and so on, it will be logged in event records. 5.2.2.4 Binary Events When there is a binary input is energized or de-energized, i.e., its state has changed from “0” to “1” or from “1” to “0”, it will be logged in event records. 5.2.2.5 Control Logs When the total number of control command records reaches 256, “Control_Logs” memory area will be full. If the device receives a new control command now, the oldest control command record will be deleted, and then the latest control command record will be stored and displayed. 5.2.2.6 Device Logs If an operator implements some operations on the device, such as reboot protective device, modify setting, etc., they will be logged in event records. 5.2.3 Disturbance Recording 5.2.3.1 Application Disturbance records can be used to have a better understanding of the behavior of the power network and related primary and secondary equipment during and after a disturbance. Analysis of the recorded data provides valuable information that can be used to improve existing equipment. This information can also be used when planning for and designing new installations. PCS-902 Line Distance Relay 5-7 Date: 2019-03-01 5 Management 5.2.3.2 Design A disturbance record consists of fault record and fault waveform. The disturbance record can be initiated by fault detector element, tripping element, reclosing element or configurable signal [BI_TrigDFR]. 5.2.3.3 Capacity and Information of Disturbance Records The device can store up to 32 disturbance records with waveform in non-volatile memory. It is based on first in first out queue that the oldest disturbance record will be overwritten by the latest one. For each disturbance record, the following items are included: 1. Sequence number Each operation will be recorded with a sequence number in the record and displayed on LCD screen. 2. Date and time of fault occurrence The time resolution is 1ms using the relay internal clock synchronized via clock synchronized device if connected. The date and time is recorded when a system fault is detected. 3. Relative operating time An operating time (not including the operating time of output relays) is recorded in the record. 4. Faulty phase 5. Fault location To get accurate result of fault location, the following settings shall be set correctly: 1) Positive-sequence line reactance [X1L] 2) Positive-sequence line resistance [R1L] 3) Zero-sequence line reactance [X0L] 4) Zero-sequence line resistance [R0L] 5) Zero-sequence line mutual reactance [X0M] 6) Zero-sequence line mutual resistance [R0M] 7) Line positive-sequence sensitive angle [21-x.phi1_Reach] or [21.Pilot.phi1_Reach] 8) Line zero-sequence sensitive angle [21-x.Real_K0] and [21-x.Imag_K0] 9) Line length in km [LineLength] 6. Protection elements 5.2.3.4 Capacity and Information of Fault Waveform MON module can store 32 pieces of fault waveform oscillogram in non-volatile memory. If a new 5-8 PCS-902 Line Distance Relay Date: 2019-03-01 5 Management fault occurs when 32 fault waveform have been stored, the oldest will be overwritten by the latest one. Each fault record consists of all analog and digital quantities related to protection, such as original current and voltage, alarm elements, and binary inputs and etc. Each time recording includes pre-disturbance waveform and post-disturbance waveform, the pre-disturbance waveform recorded duration is configured via the communication setting [RecDur_PreTrigDFR], the waveform recorded duration after the fault disappears is configured via the communication setting [RecDur_PostFault], the maximum post-disturbance waveform recorded duration is configured via the communication setting [MaxRecDur_PostTrigDFR]. Trig point 1 Limit time 2 3 1. Pre-fault recording time. Use the setting [RecDur_PreTrigDFR] to set this time. 2. Fault time of the recording. The fault time cannot be set. It continues as long as any valid trigger condition, binary or analog, persists (unless limited by the limit time, which is determined by the setting [MaxRecDur_PostTrigDFR]). 3. Post fault recording time. The time the disturbance recording continues afterall activated triggers are reset. Use the setting [RecDur_PostFault] to set this time. 5.2.4 Present Recording Present recording is a waveform triggered manually on on the device′s LCD or remotely through PCS-Explorer software. Recording content of present recording is same to that of disturbance recording. Each time recording includes several-cycle waveform before triggering and several-cycle waveform after triggering, the waveform recorded duration before triggering is configured via the communication setting [RecDur_PreTrigDFR], the waveform recorded duration after triggering is 150ms+[RecDur_PostFault], but the waveform recorded duration after triggering must be less than [MaxRecDur_PostTrigDFR]. PCS-902 Line Distance Relay 5-9 Date: 2019-03-01 5 Management 5-10 PCS-902 Line Distance Relay Date: 2019-03-01 6 Hardware 6 Hardware Table of Contents 6 Hardware ............................................................................................ 6-a 6.1 Overview .......................................................................................................... 6-1 6.2 Typical Wiring .................................................................................................. 6-4 6.2.1 Conventional CT/VT (For reference only) ........................................................................... 6-4 6.2.2 ECT/EVT (For reference only) ............................................................................................. 6-6 6.2.3 CT Requirement .................................................................................................................. 6-8 6.3 Plug-in Module Description ............................................................................ 6-9 6.3.1 PWR Plug-in Module (Power Supply) ................................................................................. 6-9 6.3.2 MON Plug-in Module (Monitor) ...........................................................................................6-11 6.3.3 AI Plug-in Module (Analog Input) ....................................................................................... 6-15 6.3.4 DSP Plug-in Module (Logic Process) ................................................................................ 6-28 6.3.5 NET-DSP Plug-in Module (GOOSE and SV) .................................................................... 6-28 6.3.6 CH Plug-in Module (Fibre Optical Channel Interface) ....................................................... 6-33 6.3.7 BI Plug-in Module (Binary Input)........................................................................................ 6-35 6.3.8 BO Plug-in Module (Binary Output) ................................................................................... 6-44 6.3.9 HMI Module........................................................................................................................ 6-48 List of Figures Figure 6.1-1 Rear view of fixed module position ..................................................................... 6-1 Figure 6.1-2 Hardware diagram .................................................................................................. 6-2 Figure 6.1-3 Front view of PCS-902 ........................................................................................... 6-3 Figure 6.1-4 Typical rear view of PCS-902 ................................................................................ 6-4 Figure 6.2-1 Typical wiring of PCS-902 (conventional CT/VT) ................................................ 6-5 Figure 6.2-2 Typical wiring of PCS-902 (ECT/EVT) .................................................................. 6-7 Figure 6.3-1 View of PWR plug-in module .............................................................................. 6-10 Figure 6.3-2 Output contacts of PWR plug-in module........................................................... 6-10 PCS-902 Line Distance Relay 6-a Date: 2018-02-13 6 Hardware Figure 6.3-3 View of MON plug-in module .............................................................................. 6-12 Figure 6.3-4 Connection of communication terminal ............................................................ 6-14 Figure 6.3-5 Jumpers of clock synchronization port ............................................................ 6-14 Figure 6.3-6 Schematic diagram of CT circuit automatically closed ....................................... 6-15 Figure 6.3-7 Current connection of AI plug-in module (NR1401) ......................................... 6-16 Figure 6.3-8 Voltage connection 1 of AI plug-in module (NR1401) ...................................... 6-17 Figure 6.3-9 Voltage connection 2 of AI plug-in module (NR1401) ...................................... 6-17 Figure 6.3-10 View of AI plug-in module for one CT group input (NR1401) ........................ 6-18 Figure 6.3-11 Current connection of AI plug-in module (NR1408) ....................................... 6-20 Figure 6.3-12 Voltage connection 1 of AI plug-in module (NR1408) .................................... 6-20 Figure 6.3-13 Voltage connection 2 of AI plug-in module (NR1408) .................................... 6-21 Figure 6.3-14 View of AI plug-in module for one CT group input (NR1408) ........................ 6-21 Figure 6.3-15 Current connection of AI plug-in module (NR1401) ....................................... 6-23 Figure 6.3-16 Voltage connection of AI plug-in module (NR1401) ....................................... 6-23 Figure 6.3-17 View of AI plug-in module for two CT group input (NR1401) ........................ 6-24 Figure 6.3-18 Current connection of AI plug-in module (NR1401) ....................................... 6-25 Figure 6.3-19 Voltage connection of AI plug-in module (NR1401) ....................................... 6-26 Figure 6.3-20 View of AI plug-in module for two CT group input (NR1401) ........................ 6-26 Figure 6.3-21 View of DSP plug-in module ............................................................................. 6-28 Figure 6.3-22 View of NET-DSP plug-in module ..................................................................... 6-29 Figure 6.3-23 View of CH plug-in module ............................................................................... 6-33 Figure 6.3-24 Voltage dependence for binary inputs ............................................................. 6-35 Figure 6.3-25 Debounce technique.......................................................................................... 6-36 Figure 6.3-26 View of BI plug-in module (NR1503) ................................................................ 6-38 Figure 6.3-27 View of BI plug-in module (NR1504) ................................................................ 6-40 Figure 6.3-28 View of BI plug-in module (NR1508A).............................................................. 6-41 Figure 6.3-29 View of BO plug-in module (NR1521A) ............................................................ 6-45 Figure 6.3-30 View of BO plug-in module (NR1521C) ............................................................ 6-45 Figure 6.3-31 View of BO plug-in module (NR1521F) ............................................................ 6-46 Figure 6.3-32 View of BO plug-in module (NR1521G) ........................................................... 6-47 6-b PCS-902 Line Distance Relay Date: 2018-02-13 6 Hardware Figure 6.3-33 View of BO plug-in module (NR1580A) ............................................................ 6-47 List of Tables Table 6.3-1 Terminal definition and description of PWR plug-in module ............................ 6-10 Table 6.3-2 Terminal definition of AI module (NR1401) ......................................................... 6-18 Table 6.3-3 Terminal definition of AI module (NR1408) ......................................................... 6-21 Table 6.3-4 Terminal definition of AI module (NR1401) ......................................................... 6-24 Table 6.3-5 Terminal definition of AI module (NR1401) ......................................................... 6-27 Table 6.3-6 Encoding of IEC 61850-7-3 quality .......................................................................... 6-30 PCS-902 Line Distance Relay 6-c Date: 2018-02-13 6 Hardware 6-d PCS-902 Line Distance Relay Date: 2018-02-13 6 Hardware 6.1 Overview PCS-902 adopts 32-bit microchip processor CPU produced by FREESCALE as control core for management and monitoring function, meanwhile, adopts high-speed digital signal processor DSP for all the protection calculation. 24 points are sampled in every cycle and parallel processing of sampled data can be realized in each sampling interval to ensure ultrahigh reliability and safety of the device. 12 13 PWR module 11 BO module 09 BO module 08 BO module 06 BO module DSP module 05 BI module CH Module 04 BI module DSP module AI module MON module PCS-902 is comprised of intelligent plug-in modules, except that few particular plug-in modules’ position cannot be changed in the whole device (gray plug-in modules as shown in Figure 6.1-1), other plug-in modules like AI (analog input) and IO (binary input and binary output) can be flexibly configured in the remaining slot positions. 15 P1 Slot No. 01 02 03 07 10 14 Figure 6.1-1 Rear view of fixed module position PCS-902 has 16 slots, PWR plug-in module, MON plug-in module, DSP plug-in module and CH plug-in module are assigned at fixed slots. Besides 5 fixed modules are shown in above figure, there are 12 slots can be flexibly configured. AI plug-in module, BI plug-in module and BO plug-in module can be configured at position between slot 02, 03 and 06~15. It should be pay attention that AI plug-in module will occupy two slots. This device is developed on the basis of our latest software and hardware platform, and the new platform major characteristics are of high reliability, networking and great capability in anti-interference. See Figure 6.1-2 for hardware diagram. PCS-902 Line Distance Relay 6-1 Date: 2018-02-13 A/D Protection Calculation DSP A/D Fault Detector DSP Output Relay Conventional CT/VT External Binary Input 6 Hardware ECVT Pickup Relay ECVT ETHERNET LCD Power Supply Uaux +E Clock SYN LED CPU RJ45 Keypad PRINT Figure 6.1-2 Hardware diagram The working process of the device is as shown in above figure: current and voltage from conventional CT/VT are converted into small voltage signal and sent to DSP module after filtered and A/D conversion for protection calculation and fault detector respectively (ECVT signal is sent to the device without small signal and A/D conversion). When DSP module completes all the protection calculation, the result will be recorded in 32-bit CPU on MON module. DSP module carries out fault detector, protection logic calculation, tripping output, and MON module performs SOE (sequence of event) record, waveform recording, printing, communication between the device and SAS and communication between HMI and CPU. When fault detector detects a fault and picks up, positive power supply for output relay is provided. The items can be flexibly configured depending on the situations like sampling method of the device (conventional CT/VT or ECT/EVT), and the mode of binary output (conventional binary output or GOOSE binary output). The configurations for PCS-900 series based on microcomputer are classified into standard and optional modules. Table 6.1-1 PCS-902 module configuration Module ID Module description Remark NR1101/NR1102 Management and monitor module (MON module) standard NR1401/NR1408 Analog input module (AI module) standard NR1161 Protection calculation and fault detector module (DSP module) standard NR1213/NR1214 Protection communication channel module (CH module) option NR1503/NR1504/NR1508 Binary input module (BI module) standard NR1521/NR1580 Binary output module (BO module) standard NR1301 Power supply module (PWR module) standard 6-2 PCS-902 Line Distance Relay Date: 2018-02-13 6 Hardware Module ID Module description Remark GOOSE and SV from merging unit by IEC61850-9-2 (NET-DSP NR1136 module) Human machine interface module (HMI module) option standard MON module provides functions like communication with SAS, event record, setting management etc. AI module converts AC current and voltage from current transformers and voltage transformers respectively to small voltage signal. DSP module performs filtering, sampling, protection calculation and fault detector calculation. CH module performs information exchange with the remote device through a dedicated optical fibre channel, multiplex optical fibre channel or PLC channel. BI module provides binary inputs via opto-couplers with rating voltage among 24V/110V/125V/220V/250V (configurable). BO module provides output contacts for tripping, and signal output contact for annunciation signal, remote signal, fault and disturbance signal, operation abnormal signal etc. PWR module converts DC 250/220/125/110V into various DC voltage levels for modules of the device. NET-DSP module receives and sends GOOSE messages, sampled values (SV) from merging unit by IEC61850-9-2 protocol. HMI module is comprised of LCD, keypad, LED indicators and multiplex RJ45 ports for user as human-machine interface. PCS-902 is made of a 4U height 19” chassis for flush mounting. Components mounted on its front include a 320×240 dot matrix LCD, a 9 button keypad, 20 LED indicators and a multiplex RJ45 port. A monolithic micro controller is installed in the equipment for these functions. Following figures show front and rear views of PCS-902 respectively. ALARM 11 PCS-902 12 13 4 14 5 15 6 16 7 17 8 18 9 19 10 20 GRP 3 HEALTHY ESC 1 2 ENT Figure 6.1-3 Front view of PCS-902 PCS-902 Line Distance Relay 6-3 Date: 2018-02-13 6 Hardware 20 LED indicators are, from top to bottom, operation (HEALTHY), self-supervision (ALARM), others are configurable. For the 9-button keypad, “ENT” is “enter”, “GRP” is “group number” and “ESC” is “escape”. NR1102 NR1401 NR1161 NR1161 NR1213 NR1504 NR1504 NR1521 NR1521 NR1521 NR1521 NR1301 5V OK ALM TX BO_ALM BO_FAIL RX ON TX OFF RX DANGER 1 BO_COM1 2 BO_FAIL 3 BO_ALM 4 BO_COM2 5 BO_FAIL 6 BO_ALM 7 OPTO+ 8 OPTO- 9 10 PWR+ 11 PWR- 12 GND Figure 6.1-4 Typical rear view of PCS-902 6.2 Typical Wiring 6.2.1 Conventional CT/VT (For reference only) 12 13 PWR module 11 NR1521F NR1301 BO module BO module 06 BO module 05 NR1521A NR1521C NR1521C BO module 04 NR1504 BI module NR1161 DSP module NR1213 CH Module AI module NR1161 DSP module NR1401 MON module NR1102 15 P1 Slot No. 01 02 03 07 08 09 10 14 The following typical wiring is given based on above hardware configuration 6-4 PCS-902 Line Distance Relay Date: 2018-02-13 6 Hardware Power supply supervision 0801 CH-TX CH-RX BI_01 or CH-TX CH-RX Fibre Optic FC/PC Type (Rear) 0201 Ia 0203 Ib 0204 0205 To parallel line Ic 0206 0207 From parallel line IM0 0208 0215 Ub 0216 0217 0221 UL2 0222 0223 Power supply for opto-coupler (24V) P110 PWR- P111 OPTO+ P107 OPTO- P108 BO_ALM P101 COM P105 BO_FAIL P106 BO_ALM P104 COM Not used 0815 + 0816 + 0821 0822 1101 BO_01 1102 1103 BO_02 1104 BO_11 1121 1122 1201 BO_01 1202 1203 BO_02 1204 BO_11 1221 1222 1301 BO_01 1302 1303 BO_02 1304 … BO_FAIL P103 0814 - Power Supply P102 + BI_13 Signal Binary Output (option) PWR+ 0809 … External DC power supply + BI_12 Signal Binary Output UB2 0224 0808 … UB1 0220 Not used BI_18 Synchronism Voltage 0219 0807 BI_07 Controlled by fault detector element Uc 0218 + BI_06 … Ua 0214 Protection Voltage 0213 0802 … 0202 + … *BI plug-in module can be independent common terminal Dedicated Channel Or Telecom Equipment BO_11 1321 1322 1501 B 0102 SGND 0103 BO_CtrlOpn1 0104 0101 SYN- 0102 SGND 0103 0104 Clock SYN SYN+ 1502 1503 BO_CtrlCls1 1504 … Signal Binary Output (option) 0101 COM To the screen of other coaxial cable with single point earthing A 1517 BO_CtrlOpn5 1518 1519 BO_CtrlCls5 1520 1521 0105 TXD 0106 SGND 0107 PRINT PRINTER RTS BO_Ctrl Multiplex RJ45 (Front) 1522 P112 0225 Grounding Bus Figure 6.2-1 Typical wiring of PCS-902 (conventional CT/VT) PCS-902 Line Distance Relay 6-5 Date: 2018-02-13 6 Hardware PCS-902 (conventional CT/VT and conventional binary input and binary output) Slot No. 01 04 05 08 09 11 12 13 15 P1 Module ID NR1102 02 NR1401 03 NR1161 NR1213 06 07 NR1504 NR1504 10 NR1521 NR1521 NR1521 14 NR1521 NR1301 MON AI DSP CH BI BI BO BO BO BO PWR 08 09 11 12 13 PCS-902 (conventional CT/VT and GOOSE binary input and binary output) Slot No. 01 04 05 06 Module ID NR1102 02 NR1401 03 NR1161 NR1213 NR1136 07 NR1504 10 14 15 NR1301 P1 MON AI DSP CH NETDSP BI PWR 6.2.2 ECT/EVT (For reference only) 06 07 08 11 12 NR1301 PWR module 05 BO module 04 NR1521A NR1521C BO module BI module NR1503 NET-DSP Module NR1136 DSP module NR1161 CH Module NR1213 DSP module NR1161 MON module NR1102 Slot No. 01 02 03 09 10 13 14 15 P1 The following typical wiring is given based on above hardware configuration 6-6 PCS-902 Line Distance Relay Date: 2018-02-13 6 Hardware CH-RX Dedicated Channel Or Telecom Equipment or CH-TX CH-RX Fibre Optic MU Phase B RX TX … P111 OPTO+ P107 OPTO- P108 Power Supply BO_FAIL P103 BO_ALM P101 COM P105 BO_FAIL P106 BO_ALM P104 COM B 0102 SGND 0103 0104 0101 SYN- 0102 SGND 0103 0104 0105 TXD 0106 SGND 0107 0804 + 0805 - 0806 + 0821 - 0822 1101 1102 1103 BO_02 1104 BO_11 1121 1122 1201 BO_01 1202 1203 BO_02 1204 BO_11 1221 1222 1502 1503 BO_CtrlCls1 1504 1517 BO_CtrlOpn5 1518 1519 BO_CtrlCls5 1520 1521 BO_Ctrl 1522 IRIG-B PRINT PRINTER RTS - BO_01 Clock SYN SYN+ 0803 … 0101 + 1501 COM To the screen of other coaxial cable with single point earthing A 0802 BO_CtrlOpn1 Signal Binary Output (option) P102 - … PWR- 0801 … Power supply for opto-coupler (24V) P110 BI_11 Signal Binary Output External DC power supply PWR+ BI_03 Controlled by fault detector element Phase C BI_02 + … Phase A FC/PC Type (Rear) FO interface for SV channel Up to 8 (LC Type) SV from ECT/EVT BI_01 *BI plug-in module can be common negative terminal CH-TX P112 Multiplex RJ45 (Front) 0225 Grounding Bus Figure 6.2-2 Typical wiring of PCS-902 (ECT/EVT) PCS-902 ECT/EVT, GOOSE binary input and binary output Slot No. 01 04 05 06 Module ID NR1102 02 03 NR1161 NR1213 NR1136 07 NR1504 08 09 10 11 12 13 14 15 NR1301 P1 MON DSP CH NETDSP BI PWR PCS-902 ECT/EVT, conventional binary input and binary output Slot No. 01 Module ID 02 03 04 05 06 NR1102 NR1161 NR1213 MON DSP CH 07 08 09 NR1136 NR1504 NETDSP BI 11 12 13 NR1504 NR1521 NR1521 BI BO BO PCS-902 Line Distance Relay 10 14 15 P1 NR1521 NR1521 NR1301 BO BO PWR 6-7 Date: 2018-02-13 6 Hardware In the protection system adopting electronic current and voltage transformer (ECT/EVT), the merging unit will merge the sample data from ECT/EVT, and then send it to the device through multi-mode optical fibre. DSP module receives the data from merging unit through the optical-fibre interface to complete the protection calculation and fault detector. The difference between the hardware platform based on ECT/EVT and the hardware platform based on conventional CT/VT lies in the receiving module of sampled values only, and the device receives the sampled value from merging unit through multi-mode optical fibre. 6.2.3 CT Requirement -Rated primary current Ipn: According to the rated current or maximum load current of primary apparatus. -Rated continuous thermal current Icth: According to the maximum load current. -Rated short-time thermal current Ith and rated dynamic current Idyn: According to the maximum fault current. -Rated secondary current Isn -Accuracy limit factor Kalf: Ipn Rated primary current (amps) Icth Rated continuous thermal current (amps) Ith Rated short-time thermal current (amps) Idyn Rated dynamic current (amps) Isn Rated secondary current (amps) Kalf Accuracy limit factor Kalf=Ipal/Ipn IPal Rated accuracy limit primary current (amps) Performance verification Esl > Esl′ Esl Rated secondary limiting e.m.f (volts) Esl = kalf×Isn×(Rct+Rbn) Kalf Accuracy limit factor (Kalf=Ipal/Ipn) IPal Rated accuracy limit primary current (amps) Ipn Rated primary current (amps) Isn Rated secondary current (amps) Rct Current transformer secondary winding resistance. (ohms) Rbn Rated resistance burden (ohms) 2 Rbn=Sbn/Isn Sbn Rated burden (VAs) Esl′ Required secondary limiting e.m.f (volts) 6-8 PCS-902 Line Distance Relay Date: 2018-02-13 6 Hardware Esl′ = k×Ipcf ×Isn×(Rct+Rb)/Ipn k Ipcf stability factor = 2 Protective checking factor current (amps) Same as the maximum prospective fault current Isn Rated secondary current (amps) Rct Current transformer secondary winding resistance. (ohms) Rb Real resistance burden (ohms) Rb=Rr+2×RL+Rc Rc Contact resistance, 0.05-0.1 ohm (ohms) RL Resistance of a single lead from relay to current transformer (ohms) Rr Impedance of relay phase current input (ohms) Ipn Rated primary current (amps) For example: 1. Kalf=30, Isn=5A, Rct=1ohm, Sbn=60VA Esl = kalf×Isn×(Rct+Rbn) = kalf×Isn×(Rct+ Sbn/ Isn2) = 30×5×(1+60/25)=510V 2. Ipcf=40000A, RL=0.5ohm, Rr=0.1ohm, Rc=0.1ohm, Ipn=2000A Esl′ = 2×Ipcf×Isn×(Rct+Rb)/Ipn = 2×Ipcf ×Isn×(Rct+(Rr+2×RL+Rc))/Ipn = 2×40000×5×(1+(0.1+2×0.5+0.1))/2000=440V Thus, Esl > Esl′ 6.3 Plug-in Module Description The device consists of PWR plug-in module, MON plug-in module, DSP plug-in module, AI plug-in module, BI plug-in module, BO plug-in module, CH plug-in module and NET-DSP plug-in module. Terminal definitions and application of each plug-in module are introduced as follows. 6.3.1 PWR Plug-in Module (Power Supply) PWR module is a DC/DC converter with electrical insulation between input and output. It has an input voltage range as described in Chapter 2 “Technical Data”. The standardized output voltages are +5V and +24V DC. The tolerances of the output voltages are continuously monitored. The +5V DC output provides power supply for all the electrical elements that need +5V DC power supply in this device. The use of an external miniature circuit breaker is recommended. The miniature circuit breaker must be in the on position when the device is in operation and in the off position when the device is in cold reserve. A 12-pin connector is fixed on PWR module. The terminal definition of the connector is described PCS-902 Line Distance Relay 6-9 Date: 2018-02-13 6 Hardware as below. NR1301 5V OK ALM BO_ALM BO_FAIL ON OFF 1 BO_COM1 2 BO_FAIL 3 BO_ALM 4 BO_COM2 5 BO_FAIL 6 BO_ALM 7 OPTO+ 8 OPTO- 9 10 PWR+ 11 PWR12 GND Figure 6.3-1 View of PWR plug-in module The power switch in the dotted box of above figure maybe is not existed. 01 BO_FAIL 02 BO_ALM 03 04 BO_FAIL 05 BO_ALM 06 Figure 6.3-2 Output contacts of PWR plug-in module Terminal definition and description is shown as follows: Table 6.3-1 Terminal definition and description of PWR plug-in module Terminal No. Symbol Description 01 BO_COM1 Common terminal 1 02 BO_FAIL Device failure output 1 (01-02, NC) 03 BO_ALM Device abnormality alarm output 1 (01-03, NO) 04 BO_COM2 Common terminal 2 05 BO_FAIL Device failure output 2 (04-05, NC) 6-10 PCS-902 Line Distance Relay Date: 2018-02-13 6 Hardware Terminal No. Symbol Description 06 BO_ALM Device abnormality alarm output 2 (04-06, NO) 07 OPTO+ Positive power supply for BI module (24V) 08 OPTO- Negative power supply for BI module (24V) 09 Blank Not used 10 PWR+ Positive input of power supply for the device (250V/220V/125V/110V) 11 PWR- Negative input of power supply for the device (250V/220V/125V/110V) 12 GND Grounded connection of the power supply NOTICE! The standard rated voltage of PWR module is self-adaptive to 88~300 Vdc. If input voltage is out of range, an alarm signal (Fail_Device) will be issued. For non-standard rated voltage power supply module please specify when place order, and check if the rated voltage of power supply module is the same as the voltage of power source before the device being put into service. PWR module provides terminal 12 and grounding screw for device grounding. Terminal 12 shall be connected to grounding screw and then connected to the earth copper bar of panel via dedicated grounding wire. Effective grounding is the most important measure for a device to prevent EMI, so effective grounding must be ensured before the device is put into service. PCS-902, like almost all electronic relays, contains electrolytic capacitors. These capacitors are well known to be subject to deterioration over time if voltage is not applied periodically. Deterioration can be avoided by powering the relays up once a year. 6.3.2 MON Plug-in Module (Monitor) MON module consists of high-performance built-in processor, FLASH, SRAM, SDRAM, Ethernet controller and other peripherals. Its functions include management of the complete device, human machine interface, communication and waveform recording etc. MON module uses the internal bus to receive the data from other modules of the device. It communicates with the LCD module by RS-485 bus. This module comprises 100BaseT Ethernet interfaces, RS-485 communication interfaces that exchange information with above system by using IEC 61850, PPS/IRIG-B differential time synchronization interface and RS-232 printing interface. Modules with various combinations of memory and interface are available as shown in the table below. PCS-902 Line Distance Relay 6-11 Date: 2018-02-13 6 Hardware CAUTION! Do NOT look into the end of an optical fiber connected to an optical port. Do NOT look into an optical port/connector. A direct sight to laser light may cause temporary or permanent blindness. NR1102D NR1102I NR1101E NR1102N TX TX RX RX TX TX NR1101F ETHERNET ETHERNET ETHERNET RX ETHERNET RX ETHERNET Figure 6.3-3 View of MON plug-in module Module ID Memory Interface Terminal No. 4 RJ45 Ethernet RS-485 NR1102D 128M DDR 128M DDR Physical Layer To SCADA 01 SYN+ 02 SYN- To 03 SGND synchronization clock Twisted pair wire 04 RS-232 NR1102I Usage 05 RTS 06 TXD 07 SGND To printer Cable 2 RJ45 Ethernet To SCADA Twisted pair wire 2 FO Ethernet To SCADA Optical fibre ST RS-485 01 SYN+ 02 SYN- To 03 SGND synchronization RTS To printer clock Twisted pair wire 04 RS-232 05 6-12 Cable PCS-902 Line Distance Relay Date: 2018-02-13 6 Hardware independent 256M DDR TXD 07 SGND 2 RJ45 Ethernet To SCADA Twisted pair wire 2 FO Ethernet To SCADA Optical fiber ST NR1102N (Support 06 RS-485/TTL 01 SYN+ 02 SYN- To SGND synchronization 03 clock Twisted pair wire 04 MAC) RS-232 05 RTS 06 TXD 07 SGND 2 RJ45 Ethernet RS-485 To printer Cable To SCADA 01 A 02 B 03 SGND To SCADA 04 RS-485 NR1101E 128M DDR 05 A 06 B 07 SGND Twisted pair wire To SCADA 08 RS-485 09 SYN+ 10 SYN- To 11 SGND synchronization clock 12 RS-232 13 RTS 14 TXD 15 SGND To printer Cable 16 3 RJ45 Ethernet RS-485 To SCADA 01 A 02 B 03 SGND To SCADA 04 NR1101F (Support independent 256M DDR RS-485 05 A 06 B 07 SGND Twisted pair wire To SCADA 08 MAC) RS-485/TTL 09 SYN+ 10 SYN- To 11 SGND synchronization clock 12 RS-232 13 RTS 14 TXD PCS-902 Line Distance Relay To printer Cable 6-13 Date: 2018-02-13 6 Hardware 15 SGND 16 The correct connection is shown in Figure 6.3-4. Generally, the shielded cable with two pairs of twisted pairs inside shall be applied. One pair of the twisted pairs are respectively used to connect the “+” and “–” terminals of difference signal. The other pair of twisted pairs are used to connect the signal ground of the communication interface. The module reserves a free terminal for all the communication ports. The free terminal has no connection with any signal of the device, and it is used to connect the external shields of the cable when connecting multiple devices in series. The external shield of the cable shall be grounded at one of the ends only. Twisted pair wire 01 B 02 SGND 03 COM A Twisted pair wire SYN+ 01 SYN- 02 SGND 03 Clock SYN To the screen of other coaxial cable with single point earthing 04 04 Cable 05 TXD 06 SGND 07 PRINT RTS Figure 6.3-4 Connection of communication terminal Pin1 Pin2 Pin3 Figure 6.3-5 Jumpers of clock synchronization port NOTICE! As shown in Figure 6.3-5, the external receiving mode of IRIG-B differential time 6-14 PCS-902 Line Distance Relay Date: 2018-02-13 6 Hardware synchronization interface can be set by the jumper J8&J9. Jumper RS-485 TTL J8 Pin-1 and Pin-2 are connected. (RS-485+) Pin-2 and Pin-3 are connected. (TTL+) J9 Pin-1 and Pin-2 are connected. (RS-485-) Pin-2 and Pin-3 are connected. (TTL-) 6.3.3 AI Plug-in Module (Analog Input) AI module is applicable for power plant or substation with conventional VT and CT. It is assigned to slot numbers 02 and 03. However, the module is not required if the device is used with ECT/EVT. For AI module, if the plug is not put in the socket, external CT circuit is closed itself. Just shown as below. Plug Socket In Out plug is not put in the socket In Out Put the plug in the socket Figure 6.3-6 Schematic diagram of CT circuit automatically closed There are three types of AI module with rating 1A (NR1401), 5A (NR1401) or 1A/5A (NR1408). Please declare which kind of AI module is needed before ordering. Maximum linear range of the current converter is 40In. 1. One CT group input without synchronism voltage switchover (optional NR1401 or NR1408) NR1401 For one CT group input, three phase currents (Ia, Ib and Ic) and residual current from parallel line (for mutual compensation) are input to AI module separately. Terminal 01, 03, 05 and 07 are PCS-902 Line Distance Relay 6-15 Date: 2018-02-13 6 Hardware polarity marks. It is assumed that polarity mark of CT installed on line is at line side. Three phase voltages (Ua, Ub, and Uc) for protection calculation and one synchronism voltage are input to AI module. The synchronism voltage could be any phase-to-ground voltage or phase-to-phase voltage. If the auto-reclosing is enabled but synchronism check is not required, the synchronism voltage should be disconnected. In order to accurately locate the fault for parallel lines arrangement, residual current from parallel line is required to be connected to the device to eliminate the mutual effect between the parallel lines. Otherwise, residual current from parallel line is not necessary. Relevant description about parallel line to refer to section “Fault Location”. A B C P2 S2 P2 S2 P1 S1 P1 S1 02 01 02 01 04 03 04 03 06 05 06 05 08 07 08 07 Figure 6.3-7 Current connection of AI plug-in module (NR1401) 6-16 PCS-902 Line Distance Relay Date: 2018-02-13 6 Hardware A B C 13 14 15 16 17 18 19 20 Figure 6.3-8 Voltage connection 1 of AI plug-in module (NR1401) A B C 13 14 15 16 17 18 19 20 Figure 6.3-9 Voltage connection 2 of AI plug-in module (NR1401) PCS-902 Line Distance Relay 6-17 Date: 2018-02-13 6 Hardware Ia 01 Ian 02 Ib 03 Ibn 04 Ic 05 Icn 06 IM0 07 IM0n 08 NR1401 09 10 11 12 Ua 13 Uan 14 Ub 15 Ubn 16 Uc 17 Ucn 18 Us 19 Usn 20 21 22 23 24 Figure 6.3-10 View of AI plug-in module for one CT group input (NR1401) Table 6.3-2 lists the terminal number and definition of AI module. Table 6.3-2 Terminal definition of AI module (NR1401) Terminal No. Definition Definition 01 Ia The current of A-phase (Polarity mark) 02 Ian The current of A-phase 03 Ib The current of B-phase (Polarity mark) 04 Ibn The current of B-phase 05 Ic The current of C-phase (Polarity mark) 06 Icn The current of C-phase 07 IM0 Residual current of parallel line (Polarity mark) 08 IM0n Residual current of parallel line 09 Reserve 10 Reserve 11 Reserve 12 Reserve 13 Ua The voltage of A-phase (Polarity mark) 14 Uan The voltage of A-phase 15 Ub The voltage of B-phase (Polarity mark) 16 Ubn The voltage of B-phase 17 Uc The voltage of C-phase (Polarity mark) 18 Ucn The voltage of C-phase 19 Us Synchronism voltage (Polarity mark) 20 Usn Synchronism voltage 6-18 PCS-902 Line Distance Relay Date: 2018-02-13 6 Hardware Terminal No. Definition 21 Reserve 22 Reserve 23 Reserve 24 Reserve 25 GND Definition Ground NR1408 For one CT group input, three phase currents (Ia, Ib and Ic) and residual current from parallel line (for mutual compensation) are input to AI module separately. Terminal 01 (or 03), 05 (or 07), 09 (or 11) and 13 (or 15) are polarity marks. It is assumed that polarity mark of CT installed on line is at line side. Three phase voltages (Ua, Ub, and Uc) for protection calculation and one synchronism voltage are input to AI module. The synchronism voltage could be any phase-to-ground voltage or phase-to-phase voltage. If the auto-reclosing is enabled but synchronism check is not required, the synchronism voltage should be disconnected. In order to accurately locate the fault for parallel lines arrangement, residual current from parallel line is required to be connected to the device to eliminate the mutual effect between the parallel lines. Otherwise, residual current from parallel line is not necessary. Relevant description about parallel line to refer to section “Fault Location”. PCS-902 Line Distance Relay 6-19 Date: 2018-02-13 6 Hardware A B C P2 S2 P2 S2 P1 S1 P1 S1 02/04 01/03 02/04 01/03 06/08 05/07 06/08 05/07 10/12 09/11 10/12 09/11 14/16 13/15 14/16 13/15 Figure 6.3-11 Current connection of AI plug-in module (NR1408) A B C 17 18 19 20 21 22 23 24 Figure 6.3-12 Voltage connection 1 of AI plug-in module (NR1408) 6-20 PCS-902 Line Distance Relay Date: 2018-02-13 6 Hardware A B C 17 18 19 20 21 22 23 24 Figure 6.3-13 Voltage connection 2 of AI plug-in module (NR1408) Ia-1A 01 Ian-1A 02 Ia-5A 03 Ian-5A 04 Ib-1A 05 Ibn-1A 06 Ib-5A 07 Ibn-5A 08 Ic-1A 09 Icn-1A 10 Ic-5A 11 Icn-5A 12 IM0-1A 13 IM0n-1A 14 IM0-5A 15 IM0n-5A 16 Ua 17 Uan 18 Ub 19 Ubn 20 Uc 21 Ucn 22 Us 23 Usn 24 NR1408 Figure 6.3-14 View of AI plug-in module for one CT group input (NR1408) Table 6.3-3 lists the terminal number and definition of AI module. Table 6.3-3 Terminal definition of AI module (NR1408) Terminal No. 01 Definition Ia-1A Definition The current of A-phase (Polarity mark) PCS-902 Line Distance Relay 6-21 Date: 2018-02-13 6 Hardware Terminal No. 2. Definition Definition 02 Ian-1A The current of A-phase 03 Ia-5A The current of A-phase (Polarity mark) 04 Ian-5A The current of A-phase 05 Ib-1A The current of B-phase (Polarity mark) 06 Ibn-1A The current of B-phase 07 Ib-5A The current of B-phase (Polarity mark) 08 Ibn-5A The current of B-phase 09 Ic-1A The current of C-phase (Polarity mark) 10 Icn-1A The current of C-phase 11 Ic-5A The current of C-phase (Polarity mark) 12 Icn-5A The current of C-phase 13 IM0-1A Residual current of parallel line (Polarity mark) 14 IM0n-1A Residual current of parallel line 15 IM0-5A Residual current of parallel line (Polarity mark) 16 IM0n-5A Residual current of parallel line 17 Ua The voltage of A-phase (Polarity mark) 18 Uan The voltage of A-phase 19 Ub The voltage of B-phase (Polarity mark) 20 Ubn The voltage of B-phase 21 Uc The voltage of C-phase (Polarity mark) 22 Ucn The voltage of C-phase 23 Us Synchronism voltage (Polarity mark) 24 Usn Synchronism voltage 25 GND Ground Two CT groups input with synchronism voltage switchover (only NR1401) For two circuit breakers configuration with two CT groups input, three phase currents corresponding to CB1 and CB2 respectively (Ia1, Ib1, Ic1 and Ia2, Ib2, Ic2) are input to AI module. Terminal 01, 03, 05, 07, 09 and 11 are polarity marks. It is assumed that polarity mark of CT installed on line is at line side. Three phase voltages (Ua, Ub, and Uc) are input to AI module. UB1, UB2 and UL2 are the synchronism voltage from bus VT and line VT used for synchrocheck, it could be any phase-to-ground voltage or phase-to-phase voltage. The device can automatically switch synchronism voltage according to auxiliary contact of CB position or DS position. If the auto-reclosing is enabled but synchronism check is not required, the synchronism voltage should be disconnected. 6-22 PCS-902 Line Distance Relay Date: 2018-02-13 6 Hardware P2 P1 P1 P2 S1 S2 A B S2 S1 02 01 04 03 06 05 08 07 10 09 12 11 C Figure 6.3-15 Current connection of AI plug-in module (NR1401) A B C A 13 14 15 16 17 18 19 20 21 22 23 24 B C Figure 6.3-16 Voltage connection of AI plug-in module (NR1401) PCS-902 Line Distance Relay 6-23 Date: 2018-02-13 6 Hardware Ia1 01 Ia1n 02 Ib1 03 Ib1n 04 Ic1 05 Ic1n 06 Ia2 07 Ia2n 08 Ib2 09 Ib2n 10 Ic2 11 Ic2n 12 Ua 13 Uan 14 Ub 15 Ubn 16 Uc 17 Ucn 18 UB1 19 UB1n 20 UL2 21 UL2n 22 UB2 23 UB2n 24 NR1401 Figure 6.3-17 View of AI plug-in module for two CT group input (NR1401) Table 6.3-4 lists the terminal number and definition of AI module. Table 6.3-4 Terminal definition of AI module (NR1401) Terminal No. Definition Definition 01 Ia1 The current of A-phase (Polarity mark) 02 Ia1n The current of A-phase 03 Ib1 The current of B-phase (Polarity mark) 04 Ib1n The current of B-phase 05 Ic1 The current of C-phase (Polarity mark) 06 Ic1n The current of C-phase 07 Ia2 The current of A-phase (Polarity mark) 08 Ia2n The current of A-phase 09 Ib2 The current of B-phase (Polarity mark) 10 Ib2n The current of B-phase 11 Ic2 The current of C-phase (Polarity mark) 12 Ic2n The current of C-phase 13 Ua The voltage of A-phase (Polarity mark) 14 Uan The voltage of A-phase 15 Ub The voltage of B-phase (Polarity mark) 16 Ubn The voltage of B-phase 17 Uc The voltage of C-phase (Polarity mark) 18 Ucn The voltage of C-phase 19 UB1 The voltage of bus 1 (Polarity mark) 20 UB1n The voltage of bus 1 6-24 PCS-902 Line Distance Relay Date: 2018-02-13 6 Hardware Terminal No. 3. Definition Definition 21 UL2 The voltage of line 2 (Polarity mark) 22 UL2n The voltage of line 2 23 UB2 The voltage of bus 2 (Polarity mark) 24 UB2n The voltage of bus 2 25 GND Ground Two CT groups input without synchronism voltage switchover (only NR1401) For two circuit breakers configuration with two CT groups input, three phase currents corresponding to CB1 and CB2 respectively (Ia1, Ib1, Ic1 and Ia2, Ib2, Ic2), and residual current from parallel line (for mutual compensation) are input to AI module. Terminal 01, 03, 05, 07, 09, 11 and 13 are polarity marks. It is assumed that polarity mark of CT installed on line is at line side. Three phase voltages (Ua, Ub, and Uc) for protection calculation and one synchronism voltage are input to AI module. The synchronism voltage could be any phase-to-ground voltage or phase-to-phase voltage. If the auto-reclosing is enabled but synchronism check is not required, the synchronism voltage should be disconnected. P2 P1 P1 P2 A B S2 S1 S1 02 01 04 03 06 05 08 07 10 09 12 11 14 13 S2 C To parallel line From parallel line Figure 6.3-18 Current connection of AI plug-in module (NR1401) PCS-902 Line Distance Relay 6-25 Date: 2018-02-13 6 Hardware A B C A 15 16 17 18 19 20 21 22 23 24 B C Figure 6.3-19 Voltage connection of AI plug-in module (NR1401) Ia1 01 Ia1n 02 Ib1 03 Ib1n 04 Ic1 05 Ic1n 06 Ia2 07 Ia2n 08 Ib2 09 Ib2n 10 Ic2 11 Ic2n 12 IM0 13 IM0n 14 Ua 15 Uan 16 Ub 17 Ubn 18 Uc 19 Ucn 20 Us 21 Usn 22 NR1401 23 24 Figure 6.3-20 View of AI plug-in module for two CT group input (NR1401) Table 6.3-5 lists the terminal number and definition of AI module. 6-26 PCS-902 Line Distance Relay Date: 2018-02-13 6 Hardware Table 6.3-5 Terminal definition of AI module (NR1401) Terminal No. Definition Definition 01 Ia1 The current of A-phase (Polarity mark) 02 Ia1n The current of A-phase 03 Ib1 The current of B-phase (Polarity mark) 04 Ib1n The current of B-phase 05 Ic1 The current of C-phase (Polarity mark) 06 Ic1n The current of C-phase 07 Ia2 The current of A-phase (Polarity mark) 08 Ia2n The current of A-phase 09 Ib2 The current of B-phase (Polarity mark) 10 Ib2n The current of B-phase 11 Ic2 The current of C-phase (Polarity mark) 12 Ic2n The current of C-phase 13 IM0 Residual current of parallel line (Polarity mark) 14 IM0n Residual current of parallel line 15 Ua The voltage of A-phase (Polarity mark) 16 Uan The voltage of A-phase 17 Ub The voltage of B-phase (Polarity mark) 18 Ubn The voltage of B-phase 19 Uc The voltage of C-phase (Polarity mark) 20 Ucn The voltage of C-phase 21 Us Synchronism voltage (Polarity mark) 22 Usn Synchronism voltage 23 Reserve 24 Reserve 25 GND Ground PCS-902 Line Distance Relay 6-27 Date: 2018-02-13 6 Hardware 6.3.4 DSP Plug-in Module (Logic Process) NR1161 Figure 6.3-21 View of DSP plug-in module This device can be equipped with 2 DSP plug-in modules at most and 1 DSP plug-in module at least. The default DSP plug-in module is necessary, which mainly is responsible for protection function including fault detector and protection calculation. The default module consists of high-performance double DSP (digital signal processor),16-digit high-accuracy ADC that can perform synchronous sampling and manage other peripherals. One of double DSP is responsible for protection calculation, and can fulfill analog data acquisition, protection logic calculation and tripping output. The other is responsible for fault detector, and can fulfill analog data acquisition, fault detector and providing power supply to output relay. When the module is connected with conventional CT/VT, it can perform the synchronous data acquisition through AI plug-in module. When the module is connected with ECT/EVT, it can receive the real-time synchronous sampled value from merging unit through NET-DSP plug-in module. The other module is optional and it is not required unless control and manual closing with synchronism check are equipped with this device. The default DSP plug-in module is fixed at slot 04 and the option DSP plug-in module is fixed at slot 06. 6.3.5 NET-DSP Plug-in Module (GOOSE and SV) NOTICE! NET-DSP plug-in module is only applied in process level of digital substation. 6-28 PCS-902 Line Distance Relay Date: 2018-02-13 6 Hardware NR1136A NR1136C RX Figure 6.3-22 View of NET-DSP plug-in module This module consists of high-performance DSP (digital signal processor), 2~8 100Mbit/s optical-fibre interface (LC type) and selectable IRIG-B interface (ST type). It supports GOOSE and SV by IEC 61850-9-2 protocols. It can receive and send GOOSE messages to intelligent control device, and receive SV from MU (merging unit). This module supports IEEE1588 network time protocol, E2E and P2P defined in IEEE1588 protocol can be selected. This module supports Ethernet IEEE802.3 time adjustment message format, UDP time adjustment message format and GMRP. CAUTION! Do NOT look into the end of an optical fiber connected to an optical port. Do NOT look into an optical port/connector. A direct sight to laser light may cause temporary or permanent blindness. The device can output q data by GOOSE, and an output signal is provided “Output_q”. This signal is used to indicate the quality of all output signals. According to the standard definition about the quality by IEC 61850, the value of this signal is “0” under normal conditions, and it will be “2048” (Bit1 is “1”, and other bits is “0”) when the device is under maintenance condition. The definition of each bit about quality signal by IEC 61850 is as below. PCS-902 Line Distance Relay 6-29 Date: 2018-02-13 6 Hardware Table 6.3-6 Encoding of IEC 61850-7-3 quality Bit (s) IEC 61850-7-3 Bit 0-1 Attribute name Validity Bit-String Attribute value Value Good 00 Invalid 01 Reserved 10 Questionable 11 Default 00 2 Overflow TRUE FALSE 3 OutofRange TRUE FALSE 4 BadReference TRUE FALSE 5 Oscillatory TRUE FALSE 6 Failure TRUE FALSE 7 OldData TRUE FALSE 8 Inconsistent TRUE FALSE 9 Inaccurate TRUE FALSE 10 Source Process 0 0 Subsituted 1 11 Test TRUE FALSE 12 OperatorBlocked TRUE FALSE The method of adding q data is as bellow steps. 1. Step1: Open the DEV file and find “MMS_GOOSE_Out” page. 2. Step2: Taking “PTRC_out” module as an example, which can be found in “Symbol Library” and instanced as bellow. 6-30 PCS-902 Line Distance Relay Date: 2018-02-13 6 Hardware 3. Step3: Double click the instanced module, the parameter list is displayed as bellow. Tr1~Tr8 are used for sending signals, q1~q8 are used for q data, the relationship between them is one to one. Only one total q data can be added to all 8 sending signals by “batch_q”. 4. Step4: The output q data, named “Output_q” in variable library, is used for all sending signals. The path is shown as bellow which is marked in red color. PCS-902 Line Distance Relay 6-31 Date: 2018-02-13 6 Hardware 5. Step5: Put the mouse on the “Output_q” signal, hold the left button of the mouse and drag it to the corresponding position, and then release. The detail is as bellow. After the above steps, save the modifications and compress driver file. Check the latest GOOSE and CID file. 6-32 PCS-902 Line Distance Relay Date: 2018-02-13 6 Hardware 6.3.6 CH Plug-in Module (Fibre Optical Channel Interface) NR1213 NR1213 NR1213 NR1213 TX TX TX TX RX RX RX RX TX TX RX RX NR1213A NR1213 NR1213A-100 NR1213B NR1213 NR1214 TX TX RX RX NR1213B-100 NR1214 TX1 TX1 RX1 RX1 TX1 TX1 TX1 RX1 RX1 RX1 NR1213F NR1213F-100 NR1214A NR1214B Figure 6.3-23 View of CH plug-in module PCS-902 Line Distance Relay 6-33 Date: 2018-02-13 6 Hardware Type Wavelength Application NR1213A 1310nm Single-mode, single channel, transmission distance <60 km NR1213A-100 1550nm Single-mode, single channel, transmission distance <110 km NR1213B 1310nm Single-mode, dual channels, transmission distance <60 km NR1213B-100 1550nm Single-mode, dual channels, transmission distance <110 km 1310nm Single-mode, single channel, transmission distance <60 km 850nm Multi-mode, single channel, transmission distance <2 km 1550nm Single-mode, single channel, transmission distance <110 km 850nm Multi-mode, single channel, transmission distance <2 km NR1214A 850nm Multi-mode, single channel, transmission distance <2 km NR1214B 850nm Multi-mode, dual channels, transmission distance <2 km NR1213F NR1213F-100 PCS-902 series can exchange information with the device at the remote end through a dedicated optical fibre channel or multiplex channel. The module transmits and receives optical signal using FC/PC or ST optical connector. The parameters are shown as follows: Item Type1 Type2 Type3 Fiber Optic Single mode, Rec.G652 Single mode, Rec.G652 Multi mode, Rec.G652 Wavelength 1310nm 1550nm 850nm Transmission power -13.0±3.0 dBm -5.0 dBm±3.0 dBm -12dBm~-20 dBm Receiving sensitivity Min.-37 dBm Min.-36 dBm Min.-30 dBm Transmission distance Max.60 km Max.110 km Max.2 km Optical overload point Min.-3 dBm Min.-3 dBm Min.-8 dBm NOTICE! When using dedicated optical fibre channel, if the transmission distance is longer than 50km, the transmitted power may be enhanced to ensure received power larger than receiving sensitivity. Please notify supplier before ordering and it will be considered as special project using 1550nm laser diode. When using multiplex channel, the sending power of the device is fixed. When using channel multiplexing equipment, the parameters are shown as follows: 1. Channel type: digital optical fibre or digital microwave. 2. Interface standard: 2048kbit/s E1 The device′s requirements on the channel are shown as follows: 1. The routine of both direction shall be same to each other, so the time delays of both direction are the same. 2. The maximum one-way channel propagation delay shall be less than 15 ms. 6-34 PCS-902 Line Distance Relay Date: 2018-02-13 6 Hardware CAUTION! Do NOT look into the end of an optical fiber connected to an optical port. Do NOT look into an optical port/connector. A direct sight to laser light may cause temporary or permanent blindness. 6.3.7 BI Plug-in Module (Binary Input) There are five kinds of BI modules available, NR1503A, NR1503AR, NR1504A, NR1504AR and NR1508A. Up to 3 BI modules can be equipped with one device. Voltage 264 176 154 140 110 87.5 77 62.5 55 Operation Operation uncertain No operation 0 110V 125V 220V 220V Figure 6.3-24 Voltage dependence for binary inputs The well-designed debounce technique is adopted in this device, and the state change of binary input within “Debounce time” will be ignored. As shown in Figure 6.3-25. All binary inputs should setup necessary debounce time to prevent the device from undesired operation due to transient interference or mixed connection of AC system and DC system. When the duration of binary input is less than the debounce time, the state of the binary input will be ignored. When the duration of binary input is greater than the debounce time, the state of the binary input will be validated and wrote into SOE. PCS-902 Line Distance Relay 6-35 Date: 2018-02-13 6 Hardware Binary input state Validate binary input state change & write it into SOE record 1 0 Debounce time of delayed pickup Debounce time of delayed dropout Time Figure 6.3-25 Debounce technique In order to meet flexible configurable requirement for different project feild, all binary inputs provided by the device are configurable. The device provide two parameters to setup debounce time of delayed pickup and debounce time of delayed dropout based on specific binary signal. The configurable binary signals can be classified as follows: 1. Type 1 This type of binary inputs include enable/disable of protection functions, AR mode selection, "BI_Print", "BI_RstTarg", "BI_Maintenance", disconnector position, settings group switch, open and close command of circuit breaker and disconnector, enable/disable of auxiliary functions (for example, manually trigger recording). They is on the premise of reliability, and the debounce time of delayed pickup and delayed dropout is recommended to set as 100ms at least. 2. Type 2 This type of binary inputs include "85-x.Recv1", "85-x.RecvB", "85-x.RecvC", "85-x.Recv2" and "BI_TimeSyn", the debounce time of delayed pickup and delayed dropout is usually set as 0ms. 3. Type 3 This type of binary inputs include "BI_BFI_1", "BI_BFI_2", "TT.Init", "CSWIxx.Cmd_LocCtrl", "CSWIxx.Cmd_RmtCtrl". Debounce time BI Input Signal.X1 t1 t2 & Time delay Output SIG Operation condition Time delay is equal to 0 The debounce time of delayed pickup and delayed dropout is recommended to set as 15ms, in 6-36 PCS-902 Line Distance Relay Date: 2018-02-13 6 Hardware order to prevent binary signals from misoperation due to mixed connection of AC system and DC system. Time delay is not equal to 0 The debounce time of delayed pickup and delayed dropout is recommended to set as (-t1+ t2+Time delay)≥15ms, in order to prevent binary signals from misoperation due to mixed connection of AC system and DC system. ti is the debounce time of delayed pickup. t2 is the debounce time of delayed dropout. 4. Type 4 This type of binary inputs are usually used as auxiliary input condition, and include the following signals. No. Binary input 1 CBx.52b_PhA 2 CBx.52b_PhB 3 CBx.52b_PhC 4 CBx.52b 5 CBx.52a 6 CBx.TCCS.Input 7 85-x.Abnor_Ch1 8 85-x.Abnor_Ch2 9 85-x.ExTrp 10 85-x.Unblocking1 11 85-x.Unblocking2 12 CBx.50DZ.Init 13 PrepTrp3P 14 CBx.50BF.ExTrp3P_L 15 CBx.50BF.ExTrp3P_GT 16 CBx.50BF.ExTrpA 17 CBx.50BF.ExTrpB 18 CBx.50BF.ExTrpC 19 CBx.50BF.ExTrp_WOI 20 CBx.25.MCB_VT_UL1 21 CBx.25.MCB_VT_UL2 22 CBx.25.MCB_VT_UB1 23 CBx.25.MCB_VT_UB2 24 79.Trp 25 79.Trp3P 26 79.TrpA 27 79.TrpB 28 79.TrpC PCS-902 Line Distance Relay 6-37 Date: 2018-02-13 6 Hardware 29 79.WaitMaster 30 79.CB_Healthy 31 79.Clr_Counter 32 79.Ok_Chk 33 79.Lockout 34 79.PLC_Lost 35 VTS.MCB_VT The debounce time of delayed pickup and delayed dropout is recommended to set as 5ms. 1. NR1503 Each BI module is with a 22-pin connector for 11 binary inputs, and its rated voltage can be selected to be 110Vdc, 125Vdc, 220Vdc. Each binary input of NR1503A and NR1503AR has independent negative power input of opto-coupler and can be configurable. NR1503A′s pickup voltage and dropoff voltage are fixed value, and the range is from 55%Un to 70%Un. NR1503AR′s pickup voltage and dropoff voltage are settable by the setting [xx.U_Pickup_BI] and [xx.U_Dropoff_BI] from 55%Un to 80%Un. NR1503 BI_01 01 Opto01- 02 BI_02 03 Opto02- 04 BI_03 05 Opto03- 06 BI_04 07 Opto04- 08 BI_05 09 Opto05- 10 BI_06 11 Opto06- 12 BI_07 13 Opto07- 14 BI_08 15 Opto08- 16 BI_09 17 Opto09- 18 BI_10 19 Opto10- 20 BI_11 21 Opto11- 22 Figure 6.3-26 View of BI plug-in module (NR1503) [BI_n] can be configured as a specified binary input by PCS-Explorer software (n=01, 02, ……). Terminal description for NR1503 is shown as follows. Terminal No. Symbol Description 01 BI_01 Configurable binary input 1 02 Opto01- Negative supply of configurable binary input 1 6-38 PCS-902 Line Distance Relay Date: 2018-02-13 6 Hardware Terminal No. Symbol Description 03 BI_02 Configurable binary input 2 04 Opto02- Negative supply of configurable binary input 2 05 BI_03 Configurable binary input 3 06 Opto03- Negative supply of configurable binary input 3 07 BI_04 Configurable binary input 4 08 Opto04- Negative supply of configurable binary input 4 09 BI_05 Configurable binary input 5 10 Opto05- Negative supply of configurable binary input 5 11 BI_06 Configurable binary input 6 12 Opto06- Negative supply of configurable binary input 6 13 BI_07 Configurable binary input 7 14 Opto07- Negative supply of configurable binary input 7 15 BI_08 Configurable binary input 8 16 Opto08- Negative supply of configurable binary input 8 17 BI_09 Configurable binary input 9 18 Opto09- Negative supply of configurable binary input 9 19 BI_10 Configurable binary input 10 20 Opto10- Negative supply of configurable binary input 10 21 BI_11 Configurable binary input 11 22 Opto11- Negative supply of configurable binary input 11 2. NR1504 Each BI module is with a 22-pin connector for 18 binary inputs, and its rated voltage can be selected to be 110Vdc, 125Vdc, 220Vdc. All binary inputs of NR1504A and NR1504AR share one common negative power input and can be configurable. NR1504A′s pickup voltage and dropoff voltage are fixed value, and the range is from 55%Un to 70%Un. NR1504AR′s pickup voltage and dropoff voltage are settable by the setting [xx.U_Pickup_BI] and [xx.U_Dropoff_BI] from 55%Un to 80%Un. PCS-902 Line Distance Relay 6-39 Date: 2018-02-13 6 Hardware NR1504 Opto+ 01 BI_01 02 BI_02 03 BI_03 04 BI_04 05 BI_05 06 BI_06 07 08 BI_07 09 BI_08 10 BI_09 11 BI_10 12 BI_11 13 BI_12 14 15 BI_13 16 BI_14 17 BI_15 18 BI_16 19 BI_17 20 BI_18 21 COM- 22 Figure 6.3-27 View of BI plug-in module (NR1504) [BI_n] can be configured as a specified binary input by PCS-Explorer software (n=01, 02, ……). Terminal description for NR1504 is shown as follows. Terminal No. Symbol Description 01 Opto+ Positive supply of power supply of the module 02 BI_01 Configurable binary input 1 03 BI_02 Configurable binary input 2 04 BI_03 Configurable binary input 3 05 BI_04 Configurable binary input 4 06 BI_05 Configurable binary input 5 07 BI_06 Configurable binary input 6 08 Blank Not used 09 BI_07 Configurable binary input 7 10 BI_08 Configurable binary input 8 11 BI_09 Configurable binary input 9 12 BI_10 Configurable binary input 10 13 BI_11 Configurable binary input 11 14 BI_12 Configurable binary input 12 15 Blank Not used 16 BI_13 Configurable binary input 13 17 BI_14 Configurable binary input 14 18 BI_15 Configurable binary input 15 19 BI_16 Configurable binary input 16 6-40 PCS-902 Line Distance Relay Date: 2018-02-13 6 Hardware Terminal No. Symbol Description 20 BI_17 Configurable binary input 17 21 BI_18 Configurable binary input 18 22 COM- Common terminal of negative supply of binary inputs 3. NR1508 NR1508A is with a 22-pin connector for 11 binary inputs, and its rated voltage is 220Vdc. Each binary input of NR1508A has independent negative power input of opto-coupler and can be configurable. NR1508A′s pickup voltage and dropoff voltage are fixed value, and the range is from 75%Un to 80%Un. NR1508A BI_01 01 Opto01- 02 BI_02 03 Opto02- 04 BI_03 05 Opto03- 06 BI_04 07 Opto04- 08 BI_05 09 Opto05- 10 BI_06 11 Opto06- 12 BI_07 13 Opto07- 14 BI_08 15 Opto08- 16 BI_09 17 Opto09- 18 BI_10 19 Opto10- 20 BI_11 21 Opto11- 22 Figure 6.3-28 View of BI plug-in module (NR1508A) [BI_n] can be configured as a specified binary input by PCS-Explorer software (n=01, 02, ……). Terminal description for NR 1508A is shown as follows. Terminal No. Symbol Description 01 BI_01 Configurable binary input 1 02 Opto01- Negative supply of configurable binary input 1 03 BI_02 Configurable binary input 2 04 Opto02- Negative supply of configurable binary input 2 05 BI_03 Configurable binary input 3 06 Opto03- Negative supply of configurable binary input 3 07 BI_04 Configurable binary input 4 08 Opto04- Negative supply of configurable binary input 4 09 BI_05 Configurable binary input 5 PCS-902 Line Distance Relay 6-41 Date: 2018-02-13 6 Hardware Terminal No. Symbol Description 10 Opto05- Negative supply of configurable binary input 5 11 BI_06 Configurable binary input 6 12 Opto06- Negative supply of configurable binary input 6 13 BI_07 Configurable binary input 7 14 Opto07- Negative supply of configurable binary input 7 15 BI_08 Configurable binary input 8 16 Opto08- Negative supply of configurable binary input 8 17 BI_09 Configurable binary input 9 18 Opto09- Negative supply of configurable binary input 9 19 BI_10 Configurable binary input 10 20 Opto10- Negative supply of configurable binary input 10 21 BI_11 Configurable binary input 11 22 Opto11- Negative supply of configurable binary input 11 NOTICE! A default configuration is given for first four binary signals (BI_01, BI_02, BI_03, BI_04) in BI plug-in module at slot 12, and they are [BI_TimeSyn], [BI_Print], [BI_Maintenance] and [BI_RstTarg] respectively. Only BI_02 and BI_04 can be configured as other signals. 1. Binary input: [BI_TimeSyn] It is used to receive clock synchronization signal from clock synchronization device, the binary input [BI_TimeSyn] will change from “0” to “1” once pulse signal is received. When the device adopts “Conventional” mode as clock synchronization mode (refer to section “Communication Settings”), the device can receives PPM (pulse per minute) and PPS (pulse per second). If the setting [Opt_TimeSyn] is set as other values, this binary input is invalid. 2. Binary input: [BI_Print] It is used to manually trigger printing latest report when the equipment is configured as manual printing mode by logic setting [En_AutoPrint]=0. The printer button is located on the panel usually. If the equipment is configured as automatic printing mode ([En_AutoPrint]=1), report will be printed automatically as soon as it is formed. 3. Binary input: [BI_Maintenance] It is used to block communication export when this binary input is energized. During device maintenance or testing, this binary input is then energized not to send reports via communication port, local display and printing still work as usual. This binary input should be de-energized when the device is restored back to normal. The application of the binary input [BI_Maintenance] for digital substation communication adopting IEC61850 protocol is given as follows. 1) Processing mechanism for MMS (Manufacturing Message Specification) message 6-42 PCS-902 Line Distance Relay Date: 2018-02-13 6 Hardware a) The protection device should send the state of this binary input to client. b) When this binary input is energized, the bit “Test” of quality (Q) in the sent message changes to “1”. c) When this binary input is energized, the client cannot control the isolator link and circuit breaker, modify settings and switch setting group remotely. d) According to the value of the bit “Test” of quality (Q) in the message sent, the client discriminate whether this message is maintenance message, and then deal with it correspondingly. If the message is the maintenance message, the content of the message will not be displayed on real-time message window, audio alarm not issued, but the picture is refreshed so as to ensure that the state of the picture is in step with the actual state. The maintenance message will be stored, and can be inquired, in independent window. 2) Processing mechanism for GOOSE message a) When this binary input is energized, the bit “Test” in the GOOSE message sent by the protection device changes to “1”. b) For the receiving end of GOOSE message, it will compare the value of the bit “Test” in the GOOSE message received by it with the state of its own binary input (i.e., [BI_Maintenance]), the message will be thought as invalid unless they are conformable. 3) Processing mechanism for SV (Sampling Value) message a) When this binary input of merging unit is energized, the bit “Test” of quality (Q) of sampling data in the SV message sent change “1”. b) For the receiving end of SV message, if the value of bit “Test” of quality (Q) of sampling data in the SV message received is “1”, the relevant protection functions will be disabled, but under maintenance state, the protection device should calculate and display the magnitude of sampling data. c) For duplicated protection function configurations, all merging units of control module configured to receive sampling should be also duplicated. Both dual protection devices and dual merging units should be fully independent each other, and one of them is in maintenance state will not affect the normal operation of the other. 4. Binary input: [BI_RstTarg] It is used to reset latching signal relay and LCD displaying. The reset is done by pressing a button on the panel. NOTICE! The rated voltage of binary input is optional: 110V, 125V, 220V or 250V, which must be specified when placed order. It is necessary to check whether the rated voltage of BI module complies with site DC supply rating before put the relay in service. There three binary signals are fixed for measurement functions, they are [BI_Rmt/Loc], [BI_ManSynCls] and [BI_ManOpen] respectively. PCS-902 Line Distance Relay 6-43 Date: 2018-02-13 6 Hardware 5. Binary input: [BI_Rmt/Loc] It is used to select the remote control or the local control. “1”: the remote control, all the binary outputs can only be remotely controlled by SCADA or control centers. “0” the local control, each binary output can only be applied to open/close CB/DS/ES locally. Each binary output can also be applied issue a signal locally. 6. Binary input: [BI_ManSynCls] When the device is under local control condition (i.e. [BI_Rmt/Loc] is de-energized), the manual synchronism check for closing circuit breaker will be initiated if it is energized. 7. Binary input: [BI_ManOpen] When the device is under local control condition (i.e. [BI_Rmt/Loc] is de-energized), the manual control for open circuit breaker will be initiated if it is energized. 6.3.8 BO Plug-in Module (Binary Output) Three standard binary output modules, NR1521A, NR1521C and NR1521G, and two optional binary output module, NR1521F and NR1580A, can be selected. The contacts provided by NR1521A, NR1521C, NR1521G, NR1521F and NR1580A are all normally open (NO) contacts. Output contact can be configured as a specified tripping output contact and a signal output contact respectively by PCS-Explorer software according to user requirement. The following signals can be configured to output contacts controlled by fault detector or output contacts without controlled by fault detector. Pickup signals of fault detector elements (FD) Operation signals of protection elements (Op) Start signals of protection elements (St) Tripping signals, reclosing signal, AR failure signal, breaker failure signal However, the signals which will be control the circuit breaker directly or initiate breaker failure protection must be configured to output contacts controlled by fault detector. The following signals must be configured to output contacts without controlled by fault detector. Enable signals of protection elements (On) Alarm signals of protection elements (Alm) Blocking signals of protection elements (Fail) Related signals with voltage switchover and synchrocheck and related signals with AR except reclosing signal and AR failure signal. NR1521A can provide 11 output contacts controlled by fault detector. 6-44 PCS-902 Line Distance Relay Date: 2018-02-13 6 Hardware BO_01 NR1521A BO_02 BO_03 BO_04 BO_05 BO_06 BO_07 BO_08 BO_09 BO_10 BO_11 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 Figure 6.3-29 View of BO plug-in module (NR1521A) NR1521C can provide 11 output contacts without controlled by fault detector. BO_01 NR1521C BO_02 BO_03 BO_04 BO_05 BO_06 BO_07 BO_08 BO_09 BO_10 BO_11 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 Figure 6.3-30 View of BO plug-in module (NR1521C) PCS-902 Line Distance Relay 6-45 Date: 2018-02-13 6 Hardware BO plug-in module (NR1521F) is dedicatedly for remote/manual open or closing to circuit breaker, disconnector and earth switch. 5 pairs of binary outputs (one for open and the other for closing) can be provided by this BO plug-in module configured in slot 15 if measurement and control function is equipped with the device. More binary outputs can be provided by another BO plug-in modules that can be configured in slot 11, 12, 13, 14 if open or closing contacts is not enough. First pair of binary outputs are used to remote/manual open or close circuit breaker, and second pair of binary outputs are also used to remote/manual open or close circuit breaker for double circuit breakers application. A normally open contact is presented via terminal 21-22 designated as ROS (i.e. remote operation signal). Whenever any of binary output contacts for open or closing is closed, ROS contact will close to issue a signal indicating that this device is undergoing a remote operation. BO plug-in module (NR1521F) is displayed as shown in the following figure. BO_CtrlOpn01 NR1521F BO_CtrlCls01 BO_CtrlOpn02 BO_CtrlCls02 BO_CtrlOpn03 BO_CtrlCls03 BO_CtrlOpn04 BO_CtrlCls04 BO_CtrlOpn05 BO_CtrlCls05 BO_Ctrl 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 Figure 6.3-31 View of BO plug-in module (NR1521F) NR1521G can provide 11 output contacts without controlled by fault detector. The first four output contacts are in parallel with instantaneous operating contacts which are recommended to be configured as fast signaling contacts to send PLC signal. 6-46 PCS-902 Line Distance Relay Date: 2018-02-13 6 Hardware BO_01 NR1521G BO_02 BO_03 BO_04 BO_05 BO_06 BO_07 BO_08 BO_09 BO_10 BO_11 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 Figure 6.3-32 View of BO plug-in module (NR1521G) NR1580A can provide 6 output contacts with controlled by fault detector. It is a heavy-capacity binary output plug-in module, which can be used to control the circuit breaker directly. + 01 BO_01 NR1580A - 02 03 04 + 05 BO_02 - 06 07 08 + 09 BO_03 - 10 11 12 + 13 BO_04 - 14 15 16 + 17 BO_05 - 18 19 20 + BO_06 - 21 22 Figure 6.3-33 View of BO plug-in module (NR1580A) PCS-902 Line Distance Relay 6-47 Date: 2018-02-13 6 Hardware 6.3.9 HMI Module The display panel consists of liquid crystal display module, keyboard, LED and ARM processor. The functions of ARM processor include display control of the liquid crystal display module, keyboard processing, and exchanging data with the CPU through LAN port etc. The liquid crystal display module is a high-performance grand liquid crystal panel with soft back lighting, which has a user-friendly interface and an extensive display range. 6-48 PCS-902 Line Distance Relay Date: 2018-02-13 7 Settings 7 Settings Table of Contents 7 Settings .............................................................................................. 7-a 7.1 System Settings .............................................................................................. 7-1 7.1.1 Setting Description............................................................................................................... 7-1 7.1.2 Access Path ......................................................................................................................... 7-2 7.2 Device Setup.................................................................................................... 7-2 7.2.1 Setting Description............................................................................................................... 7-2 7.2.2 Access Path ...................................................................................................................... 7-13 7.3 Protection Settings ....................................................................................... 7-14 7.3.1 Setting Description............................................................................................................. 7-14 7.3.2 Access Path ....................................................................................................................... 7-56 7.4 Logic Link Settings ....................................................................................... 7-57 7.4.1 Setting Description............................................................................................................. 7-57 7.4.2 Access Path ....................................................................................................................... 7-57 7.5 Control and Synchrocheck for Manual Closing Settings .......................... 7-57 7.5.1 Setting Description............................................................................................................. 7-57 7.5.2 Access Path ....................................................................................................................... 7-63 List of Tables Table 7.1-1 System settings ....................................................................................................... 7-1 Table 7.2-1 Device settings......................................................................................................... 7-2 Table 7.2-2 Communication settings ........................................................................................... 7-4 PCS-902 Line Distance Relay 7-a Date: 2019-03-01 -09-07 7 Settings 7-b PCS-902 Line Distance Relay Date: 2019-03-01 -11-23 7 Settings The device has some setting groups for protection to coordinate with the mode of power system operation, one of which is assigned to be active. However, communication settings, system settings, device settings, logic link settings and measurement and control settings are common for all protection setting groups. NOTICE! All current settings in this chapter are secondary current converted from primary current by CT ratio. Zero-sequence current or voltage setting is configured according to 3I0 or 3U0 and negative sequence current setting according to I2 or U2. 7.1 System Settings 7.1.1 Setting Description Table 7.1-1 System settings No. Item Range Unit 1 Active_Grp 1~20 2 Opt_SysFreq 50 or 60 3 PrimaryEquip_Name Maximum 12 character 4 U1n 10.00~65500.00 kV 5 U2n 80.00~220.00 V 6 CBx.I1n 100~30000 A 7 I1n_Base 100~30000 A 8 I2n_Base 1 or 5 A 9 f_High_FreqAlm 50~65 Hz 10 f_Low_FreqAlm 45~60 Hz 11 Measmt.CBx.I1n 100~30000 A 12 Measmt.I1n_Base 100~30000 A 13 Measmt.I2n_Base 1 or 5 A 1. Hz Active_Grp The number of active setting group, 20 setting groups can be configured for protection settings, and only one is active at a time 2. PrimaryEquip_Name It is recognized by the device automatically. Such setting is used for printing messages 3. Opt_SysFreq It is option of system frequency, and can be set as 50Hz or 60Hz 4. Un1 Primary rated voltage of VT PCS-902 Line Distance Relay 7-1 Date: 2019-03-01 -09-07 7 Settings 5. Un2 Secondary rated voltage of VT 6. CBx.I1n Primary rated value of CT corresponding to circuit breaker No.x 7. I1n_Base Primary calculation base rated current of CT 8. I2n_Base Secondary calculation base rated current of CT 9. f_High_FreqAlm It is frequency upper limit setting. The device will issue an alarm [Alm_Freq], when system frequency is higher than the setting. 10. f_Low_FreqAlm It is frequency lower limit setting. The device will issue an alarm [Alm_Freq], when system frequency is lower than the setting. 11. Measmt.CBx.I1n Primary rated value of measurement CT corresponding to circuit breaker No.x (available only in digital substation application) 12. Measmt.I1n_Base Primary calculation base rated current of measurement CT (available only in digital substation application) 13. Measmt.I2n_Base Secondary calculation base rated current of measurement CT (available only in digital substation application) 7.1.2 Access Path MainMenu“Settings”“System Settings” 7.2 Device Setup 7.2.1 Setting Description 7.2.1.1 Device Settings Table 7.2-1 Device settings No. 1 Item Opt_Caption_103 Range Current_language, Fixed_Chinese, Fixed_English 7-2 PCS-902 Line Distance Relay Date: 2019-03-01 -11-23 7 Settings 1. No. Item Range 2 En_Send_MMS_Qual_Chg Disable or Enable 3 Opt_DualNetMode_MMS 0, 1 or 2 4 Bxx.Un_BinaryInput 24V, 30V, 48V, 110V, 125V, 220V 5 Bxx.U_Pickup_BI 55%Un~80%Un 6 Bxx.U_Dropoff_BI 55%Un~80%Un 7 CBx.En_RevCT Disable or Enable 8 3I0Adj.En_RevCT Disable or Enable 9 Ctrl_Password 0~999 10 En_NoCtrlPwd Disable or Enable 11 En_PopupRecord_Blkd Disable or Enable Opt_Caption_103 Select the caption language sent to SAS via IEC103 protocol Default value of [Opt_Caption_103] is “Current_language”, and please set it to “Fixed_Chinese” if the SAS is supplied by China Manufacturer. 2. En_Send_MMS_Qual_Chg It is used to enable or disable that IEC 61850 communication program uploads the variation of data quality. 3. Opt_DualNetMode_MM It is used to select network mode of MMS network for the communication with SCADA 0: Single network 1: Hot standby mode (always two ports in service) 2: Cold standby mode (only one port in service) 4. Bxx.Un_BinaryInput This setting is used to set voltage level of binary input module. If low-voltage BI module is equipped, 24V, 30V or 48V can be set according to the actual requirement, and if high-voltage BI module is equipped, 110V, 125V or 220V can be set according to the actual requirement. Bxx: this plug-in module is inserted in slot xx. 5. Bxx.U_Pickup_BI This setting is used to set pickup voltage of binary input module. Bxx: this plug-in module is inserted in slot xx. Only NR1503AR or NR1504AR is equipped, the setting is valid. 6. Bxx.U_Dropoff_BI This setting is used to set dropoff voltage of binary input module. Bxx: this plug-in module is inserted in slot xx. Only NR1503AR or NR1504AR is equipped, the setting is valid. PCS-902 Line Distance Relay 7-3 Date: 2019-03-01 -09-07 7 Settings 7. CBx.En_RevCT It is used to adjust the current polarity corresponding to circuit breaker No.x. Disable: keep connected current polarity unchanged Enable: make connected current polarity reversed 8. 3I0Adj.En_RevCT It is used to adjust residual current polarity from parallel line. Disable: keep connected current polarity unchanged Enable: make connected current polarity reversed 9. Ctrl_Password It is used to set local control password. 10. En_NoCtrlPwd It is used to enable or disable the bypass function of local control password. 11. En_PopupRecord_Blkd This setting is used to enable or disable the auto-popup function of event report in the device LCD. 7.2.1.2 Communication Settings Table 7.2-2 Communication settings No. Item Range 1 IEDNAME 2 IP_LAN1 000.000.000.000~255.255.255.255 3 Mask_LAN1 000.000.000.000~255.255.255.255 4 IP_LAN2 000.000.000.000~255.255.255.255 5 Mask_LAN2 000.000.000.000~255.255.255.255 6 En_LAN2 Disable or enable 7 IP_LAN3 000.000.000.000~255.255.255.255 8 Mask_LAN3 000.000.000.000~255.255.255.255 9 En_LAN3 Disable or enable 10 IP_LAN4 000.000.000.000~255.255.255.255 11 Mask_LAN4 000.000.000.000~255.255.255.255 12 En_LAN4 Disable or enable 13 Gateway 000.000.000.000~255.255.255.255 14 En_Broadcast Disable or enable 15 Cfg_NetPorts_Bond 0~12 16 Addr_RS485A 0~255 17 Baud_RS485A 4800,9600,19200,38400,57600,115200 (bps) 7-4 PCS-902 Line Distance Relay Date: 2019-03-01 -11-23 7 Settings No. Item Range 18 Protocol_RS485A IEC103, Modbus, Resv1 19 Addr_RS485B 0~255 20 Baud_RS485B 4800,9600,19200,38400,57600,115200 (bps) 21 Protocol_RS485B IEC103, Modbus, Resv1 22 En_BICheckBO Disable or enable 23 En_BICheckLinkCtrl Disable or enable 24 Threshold_Measmt_Net 0~100% 25 Period_Measmt_Net 0~65535s 26 Format_Measmt 0, 1 27 Baud_Printer 4800,9600,19200,38400,57600,115200 (bps) 28 En_AutoPrint Disable or enable 29 Opt_TimeSyn Conventional, SAS, Advanced or NoTImeSyn 30 IP_Server_SNTP 000.000.000.000~255.255.255.255 31 IP_StandbyServer_SNTP 000.000.000.000~255.255.255.255 32 OffsetHour_UTC -12~+12 (hrs) 33 OffsetMinute_UTC 0~60 (min) 34 Opt_Display_Status PriValue, SecValue 35 RecDur_PreTrigDFR 0~1s 36 RecDur_PostFault 0~10s 37 MaxRecDur_PostTrigDFR 0~10s 38 B01.En_DualNet_GOOSE Disable or enable 39 En_TCPx_DNP Disable or enable 40 Addr_Slave_TCPx_DNP 0~65519 41 Addr_Master_TCPx_DNP 0~65519 42 IP_Master_TCPx_DNP 000.000.000.000~255.255.255.255 43 Opt_Map_TCPx_DNP 0~4 44 Obj01DefltVar_TCPx_DNP BISingleBit BIWithStatus BIChWoutT 45 Obj02DefltVar_TCPx_DNP BIChWithAbsTime BIChWithRelTime AI32Int AI16Int 46 Obj30DefltVar_TCPx_DNP AI32IntWoutF AI16IntWoutF AI32Flt AI32IntEvWoutT 47 Obj32DefltVar_TCPx_DNP AI16IntEvWoutT AI32FltEvWoutT 48 Obj40DefltVar_TCPx_DNP AO32Int PCS-902 Line Distance Relay 7-5 Date: 2019-03-01 -09-07 7 Settings No. Item Range AO16Int AO32Flt 49 t_AppLayer_TCPx_DNP 0~5 (s) 50 t_KeepAlive_TCPx_DNP 0~7200 (s) 51 En_UR_TCPx_DNP Disable or enable 52 Num_URRetry_TCPx_DNP 2~10 53 t_UROfflRetry_TCPx_DNP 1~5000 (s) 54 Class_BI_TCPx_DNP 0~3 55 Class_AI_TCPx_DNP 0~3 56 t_Select_TCPx_DNP 0~240 (s) 57 t_TimeSynIntvl_TCPx_DNP 0~3600 (s) 1. IEDNAME IED name of this device. If this setting is modified, the IED name in ".cid" file will be changed simultaneously and vice versa. 2. IP_LAN1, IP_LAN2, IP_LAN3, IP_LAN4 IP address of Ethernet port 1, Ethernet port 2, Ethernet port 3 and Ethernet port 4 3. Mask_LAN1, Mask_LAN2, Mask_LAN3, Mask_LAN4 Subnet mask of Ethernet port 1, Ethernet port 2, Ethernet port 3 and Ethernet port 4 4. En_LAN2, En_LAN3, En_LAN4 Put Ethernet port 2, Ethernet port 3 and Ethernet port 4 in service They are used for Ethernet communication based on the IEC 60870-5-103 protocol. When the IEC 61850 protocol is applied, the IP address of Ethernet A will be GOOSE source MAC address. Ethernet port 1 is always in service by default. 5. Gateway IP address of Gateway (router) 6. En_Broadcast This setting is only used only for IEC 60870-5-103 protocol. If NR network IEC 60870-5-103 protocol is used, the setting must be set as “Enable”. Disable: the device does not send UDP messages through network Enable: the device sends UDP messages through network 7. Cfg_NetPorts_Bond The setting is used to configure dual-networks switching, and it means that no dual-networks switching is created when the setting is set as “0”. The device support a bond between any two 7-6 PCS-902 Line Distance Relay Date: 2019-03-01 -11-23 7 Settings Ethernet ports, and the bond among three or above Ethernet ports is impermissible. The devices communicate with SAS by station level network. In order to ensure reliable communication, dual networks (i.e., network 1 and network 2) are adopted. Another special communication mode based on dual networks is that Ethernet port 1 and Ethernet port 2 of the device own the same IP address and MAC address, and network 1 and network 2 are used as hot standby each other. When both network 1 and network 2 are normal, any of them is used to communicate between the device and SAS. The device will automatically switch to the other healthy network when one network is abnormal, which will not affect normal communication. Taking NR1102D (with four Ethernet ports) as an example, each bit is corresponding with an Ethernet port, i.e., Bit0, Bit1, Bit2 and Bit3 are corresponding with Ethernet port 1, Ethernet port 2, Ethernet port 3 and Ethernet port 4 respectively. If a bond between Ethernet port 1 and Ethernet 2 is created, the setting [Cfg_NetPorts_Bond] is set as “3”. The specific setting is as below. Bonding Ethernet port 1 Bonding Ethernet port 2 Ethernet port 1 Bonding Ethernet port 3 Ethernet port 1 Ethernet port 4 Bit3 Bit2 Bit1 Bit0 Setting Value Bit3 Bit2 Bit1 Bit0 Setting Value Bit3 Bit2 Bit1 Bit0 Setting Value 0 0 1 1 3 0 1 0 1 5 1 0 0 1 9 Bonding Ethernet port 2 Bonding Ethernet port 3 Ethernet port 2 Bonding Ethernet port 4 Ethernet port 3 Ethernet port 4 Bit3 Bit2 Bit1 Bit0 Setting Value Bit3 Bit2 Bit1 Bit0 Setting Value Bit3 Bit2 Bit1 Bit0 Setting Value 0 1 1 0 6 1 0 1 0 10 1 1 0 0 12 Ethernet port 1: Bit0, Ethernet port 2: Bit1, Ethernet port 3: Bit2, Ethernet port 4: Bit3 The switching logic is as below. After the device is powered on, network 1 is selected when the link status of both network 1 and network 2 are normal. When the link status of network 1 is abnormal, network 2 is selected if network 2 is normal. When the link status of network 1 is abnormal, network 1 is kept to work if network 2 is also abnormal. When network 2 is working, network 2 is kept to work even if network 1 has been restored to normal. The device will be switched to network 1 only if network 2 is abnormal. PCS-902 Line Distance Relay 7-7 Date: 2019-03-01 -09-07 7 Settings 8. Addr_RS485A, Addr_RS485B They are the device′s communication address used to communicate with the SCADA or RTU via serial ports (port A and port B). 9. Baud_RS485A, Baud_RS485B Baud rate of rear RS-485 serial port A or B 10. Protocol_RS485A, Protocol_RS485B Communication protocol of rear RS-485 serial port A or B IEC103: IEC 60870-5-103 protocol Modbus: Modbus Protocol Resv1: Reserved 1 NOTICE! Above table listed all the communication settings, the device delivered to the user maybe only show some settings of them according to the communication interface configuration. If only the Ethernet ports are applied, the settings about the serial ports (port A and port B) are not listed in this submenu. And the settings about the Ethernet ports only listed in this submenu according to the actual number of Ethernet ports. The standard arrangement of the Ethernet port is two, at most four (predetermined when ordering). Set the IP address according to actual arrangement of Ethernet numbers and the un-useful port/ports need not be configured. If PCS-Explorer configuration tool auxiliary software is connected with this device through the Ethernet, the IP address of PCS-Explorer must be set as one of the available IP address of this device. 11. En_BICheckBO This setting is used to set the relationship between the positon signal of the circuit breaker and the operation of the control. Only remote control to close can be implemented if the circuit breaker is in open position, and only remote control to open can be implemented if the circuit breaker is in closed position. The remote control is not controlled by the circuit breaker position. 12. En_BICheckLinkCtrl This setting is used to set the relationship between the positon signal of the circuit breaker and the operation of the control via link. Only remote control to close can be implemented if the circuit breaker is in open position, and only remote control to open can be implemented if the circuit breaker is in closed position. Otherwise, the remote control is not controlled by the circuit breaker position. 13. Threshold_Measmt_Net Threshold value of sending measurement values to SCADA through IEC 60870-5-103 or IEC61850 protocol via Ethernet port. 7-8 PCS-902 Line Distance Relay Date: 2019-03-01 -11-23 7 Settings Default value: “1%” 14. Period_Measmt_Net The time period for equipment sends measurement data to SCADA through IEC 60870-5-103 protocol via Ethernet port. Default value: “60” 15. Format_Measmt The setting is used to select the format of measurement data sent to SCADA through IEC 60870-5-103 protocol. 0: GDD data type through IEC103 protocol is 12 1: GDD data type through IEC103 protocol is 7, i.e. 754 short real number of IEEE standard 16. Baud_Printer Baud rate of printer port 17. En_AutoPrint If automatic print is required for fault report after protection operating, it is set as “Enable”. Otherwise, it should be set to “Disable”. 18. Opt_TimeSyn There are four selections for clock synchronization of device shown as follow. Conventional PPS (RS-485): Pulse per second (PPS) via RS-485 differential level IRIG-B (RS-485): IRIG-B via RS-485 differential level PPM (DIN): Pulse per minute (PPM) via the binary input [BI_TimeSyn] PPS (DIN): Pulse per second (PPS) via the binary input [BI_TimeSyn] SAS SNTP (PTP): Unicast (point-to-point) SNTP mode via Ethernet network SNTP (BC): Broadcast SNTP mode via Ethernet network Message (IEC103): Clock messages through IEC103 protocol Advanced IEEE1588: Clock message via IEEE1588 IRIG-B (Fiber): IRIG-B via optical-fibre interface PPS (Fiber) PPS: Pulse per second (PPS) via optical-fibre interface NoTimeSync PCS-902 Line Distance Relay 7-9 Date: 2019-03-01 -09-07 7 Settings When no time synchronization signal is connected to the device, please select this option and the alarm message [Alm_TimeSyn] will not be issued anymore. “Conventional” mode and “SAS” mode are always be supported by the device, but “Advanced” mode is only supported when NET-DSP module is equipped. The alarm signal [Alm_TimeSyn] may be issued to remind user loss of time synchronization signals. 1) When “SAS” is selected, if there is no conventional clock synchronization signal, the device will not send the alarm signal [Alm_TimeSyn]. When “Conventional” mode is selected, if there is no conventional clock synchronization signal, “SAS” mode will be enabled automatically with the alarm signal [Alm_TimeSyn] issued simultaneously. 2) When “Advanced” mode is selected, if there is no conventional clock synchronization signal connected to NET-DSP module, “SAS” mode is enabled automatically with the alarm signal [Alm_TimeSyn] issued simultaneously. 3) When “NoTimeSyn” mode is selected, the device will not send alarm signals without time synchronization signal. But the device can be still synchronized if receiving time synchronization signal. NOTICE! The clock message via IEC 60870-5-103 protocol is invalid when the device receives the IRIG-B signal through RCS-485 port. 19. IP_Server_SNTP It is the address of the SNTP time synchronization server which sends SNTP timing messages to the relay or BCU. 20. IP_StandbyServer_SNTP Both [IP_Server_SNTP] and [IP_StandbyServer_SNTP] are ineffective unless SNTP clock synchronization is valid. When both [IP_Server_SNTP] and [IP_StandbyServer_SNTP] are set as "000.000.000.000", the device receives broadcast SNTP synchronization message. When either [IP_Server_SNTP] or [IP_StandbyServer_SNTP] is set as "000.000.000.000", the device adopts the setting whose value is not equal to "000.000.000.000" as SNTP server address and receives unicast SNTP synchronization message. If neither [IP_Server_SNTP] nor [IP_StandbyServer_SNTP] is set as "000.000.000.000", the device adopts the setting [IP_Server_SNTP] as SNTP server address to receive unicast SNTP synchronization message. If the device does not receive any server response after 30s, it adopts the setting [IP_StandbyServer_SNTP] as SNTP server address to receive unicast SNTP synchronization message. The device will switch between [IP_Server_SNTP] and [IP_StandbyServer_SNTP] repeatedly if it does not receive any server response in 30s. 7-10 PCS-902 Line Distance Relay Date: 2019-03-01 -11-23 7 Settings 21. OffsetHour_UTC, OffsetMinute_UTC If the IEC61850 protocol is adopted in substations, the time tags of communication messages are required according to UTC (Universal Time Coordinated) time. The setting [OffsetHour_UTC] is used to set the hour offset of the current time zone to the GMT (Greenwich Mean Time) zone; for example, if a relay is applied in China, the time zone of China is east 8th time zone, so this setting is set as “8”. The setting [OffsetMinute_UTC] is used to set the minute offset of the current time zone to the GMT zone. Time zone East 1 0 1 Setting Time zone th Setting Time zone East 7 6 7 th West 1 12/-12 -1 East 8 West 2 East 9 rd West 3 -3 th th East 4 4 th 9 nd -2 th rd East 3 3 th 8 st East/West 12 th nd East 2 2 th East 6 Setting Time zone st GMT zone 5 th East 10 East 11th 10 11 th West 4 -4 th th East 5 th West 5 -5 th th West 6 West 7 West 8 West 9 West 10 West 11 -6 -7 -8 -9 -10 -11 Setting 22. Opt_Display_Status This setting is used to set display mode of current and voltage in fault records, primary value or secondary value. The sampled values of current and voltage are displayed as secondary value by default. When it is set as primary value, both secondary voltage and secondary current are converted into primary voltage and primary current according to rated secondary and primary value of VT and CT respectively. 23. RecDur_PreTrigDFR The setting is used to set waveform recorded duration before the trigger element operating. 24. RecDur_PostFault The setting is used to set waveform recorded duration after the fault happens. 25. MaxRecDur_PostTrigDFR The setting is used to set the maximum waveform recorded duration after the trigger element operating. 26. B01.En_DualNet_GOOSE This setting is used to enable/disable dual GOOSE networks (including GOOSE network A and GOOSE network B). 27. En_TCPx_DNP The logic setting is used to enable or disable network No.x DNP client. (x=1, 2, 3, 4) When network No.x DNP client is not configured to be in service by PCS-Explorer, DNP client settings corresponding to network No.x will be hidden. PCS-902 Line Distance Relay 7-11 Date: 2019-03-01 -09-07 7 Settings 28. Addr_Slave_TCPx_DNP It is the slave address of network No.x DNP client. (x=1, 2, 3, 4) 29. Addr_Master_TCPx_DNP It is the master address of network No.x DNP client. (x=1, 2, 3, 4) 30. IP_Master_TCPx_DNP It is the IP address of network No.x DNP client. (x=1, 2, 3, 4) 31. Opt_Map_TCPx_DNP It is the communication map number of network No.x DNP client. (x=1, 2, 3, 4) 32. Obj01DefltVar_TCPx_DNP It is the “OBJ1” default variation of network No.x DNP client. (x=1, 2, 3, 4) BISingleBit: Binary Input format is packed with single bit BIWithStatus: Binary Input with status flag 33. Obj02DefltVar_TCPx_DNP It is the “OBJ2” default variation of network No.x DNP client. (x=1, 2, 3, 4) BIChWoutT: Binary Input Event without time-of-occurrence BIChWithAbsTime: Binary Input Event with absolute time-of-occurrence BIChWithRelTime: Binary Input Event with relative time-of-occurrence 34. Obj30DefltVar_TCPx_DNP It is the “OBJ30” default variation of network No.x DNP client. (x=1, 2, 3, 4) AI32Int: Analog Input with a flag octet and a 32-bit, signed integer value AI16Int: Analog Input with a flag octet and a 16-bit, signed integer value AI32IntWoutF: Analog Input with a 32-bit (but without flags) AI16IntWoutF: Analog Input with a 16-bit (but without flags) AI32Flt: Analog Input with a flag octet and a single-precision, floating-point value 35. Obj32DefltVar_TCPx_DNP It is the “OBJ32” default variation of network No.x DNP client. (x=1, 2, 3, 4) AI32IntEvWoutT: Analog Input Event with a flag octet and a 32-bit, signed integer value (but without time-of-occurrence) AI16IntEvWoutT: Analog Input Event with a flag octet and a 16-bit, signed integer value (but without time-of-occurrence) 7-12 PCS-902 Line Distance Relay Date: 2019-03-01 -11-23 7 Settings AI32FltEvWoutT: Analog Input Event with single-precision, floating-point value (but without time-of-occurrence) 36. Obj40DefltVar_TCPx_DNP It is the “OBJ40” default variation of network No.x DNP client. (x=1, 2, 3, 4) AO32Int: Analog Output with a flag octet and a 32-bit, signed integer value AO16Int: Analog Output with a flag octet and a 16-bit, signed integer value AO32Flt: Analog Output with a flag octet and a single-precision, floating-point value 37. t_AppLayer_TCPx_DNP It is the timeout of application layer of network No.x DNP client. (x=1, 2, 3, 4) 38. t_KeepAlive_TCPx_DNP It is the heartbeat time interval of network No.x DNP client. (x=1, 2, 3, 4) 39. En_UR_TCPx_DNP The logic setting is used to enable or disable the unsolicited message function of network No.x DNP client. (x=1, 2, 3, 4) 40. Num_URRetry_TCPx_DNP It is the online retransmission number of the unsolicited message of network No.x DNP client. (x=1, 2, 3, 4) 41. t_UROfflRetry_TCPx_DNP It is the offline timeout of the unsolicited message of network No.x DNP client. (x=1, 2, 3, 4) 42. Class_BI_TCPx_DNP It is the class level of the “Binary Input” of network No.x DNP client. (x=1, 2, 3, 4) 43. Class_AI_TCPx_DNP It is the class level of the “Analog Input” of network No.x DNP client. (x=1, 2, 3, 4) 44. t_Select_TCPx_DNP It is the selection timeout of network No.x DNP client. (x=1, 2, 3, 4) 45. t_TimeSynIntvl_TCPx_DNP It is the time interval of the time synchronization function of network No.x DNP client. (x=1, 2, 3, 4) 7.2.2 Access Path MainMenu“Settings”“Device Setup” PCS-902 Line Distance Relay 7-13 Date: 2019-03-01 -09-07 7 Settings 7.3 Protection Settings All protection settings are based on secondary ratings of VT and CT. Unn: rated secondary phase-to-phase voltage Un: rated secondary phase-to-ground voltage In: rated secondary current 7.3.1 Setting Description 7.3.1.1 Line Parameters Settings No. Item Remark Range 1 X1L Positive sequence reactance of the line (0.000~4Unn)/In (ohm) 2 R1L Positive sequence resistance of the line (0.000~4Unn)/In (ohm) 3 X0L Zero-sequence reactance of the line (0.000~4Unn)/In (ohm) 4 R0L Zero-sequence resistance of the line (0.000~4Unn)/In (ohm) 5 X0M Line mutual zero-sequence reactance (0.000~4Unn)/In (ohm) 6 R0M Line mutual zero-sequence resistance (0.000~4Unn)/In (ohm) 7 LineLength Total length of the line 0.00~655.35 (km) 7.3.1.2 Fault Detector Settings (FD) No. Item 1 FD.DPFC.I_Set 2 FD.ROC.3I0_Set 3 FD.NOC.I2_Set 4 FD.NOC.En Remark Range Current setting of DPFC current fault detector element Current setting of residual current fault detector element Current setting of negative-sequence current fault detector element Enable negative-sequence current fault detector element (0.050~30.000)×In (A) (0.050~30.000)×In (A) (0.050~30.000)×In (A) 0 or 1 7.3.1.3 Auxiliary Element Settings (AuxE) No. Item 1 AuxE.OCD.t_DDO 2 AuxE.OCD.En 3 AuxE.ROC1.3I0_Set 4 AuxE.ROC1.En 5 AuxE.ROC2.3I0_Set 6 AuxE.ROC2.En Remark Range Drop-off time delay of current change auxiliary element Enable current change auxiliary element 0 or 1 Current setting of stage 1 residual current auxiliary element Enable stage 1 residual current auxiliary element Current setting of stage 2 residual current Enable stage 2 residual current auxiliary element (0.050~30.000)×In (A) 0 or 1 auxiliary element 7-14 0.000~10.000 (s) (0.050~30.000)×In (A) 0 or 1 PCS-902 Line Distance Relay Date: 2019-03-01 -11-23 7 Settings 7 AuxE.ROC3.3I0_Set 8 AuxE.ROC3.En 9 AuxE.OC1.I_Set Current setting of stage 3 residual current auxiliary element Enable stage 3 residual current auxiliary element Current setting of stage 1 phase current auxiliary element Enable stage 1 phase current auxiliary element (0.050~30.000)×In (A) 0 or 1 (0.050~30.000)×In (A) 10 AuxE.OC1.En 11 AuxE.OC2.I_Set 12 AuxE.OC2.En 13 AuxE.OC3.I_Set 14 AuxE.OC3.En Enable stage 3 phase current auxiliary element 0 or 1 15 AuxE.UVD.U_Set Voltage setting for voltage change auxiliary element 0~Un (V) 16 AuxE.UVD.t_DDO 17 AuxE.UVD.En 18 AuxE.UVG.U_Set 19 AuxE.UVG.En 20 AuxE.UVS.U_Set 21 AuxE.UVS.En 22 AuxE.ROV.3U0_Set Voltage setting for residual voltage auxiliary element 0~Un (V) 23 AuxE.ROV.En Enable residual voltage auxiliary element 0 or 1 Current setting of stage 2 phase current auxiliary element Enable stage 2 phase current auxiliary element Current setting of stage 3 phase current auxiliary element Drop-off time delay of voltage change auxiliary element Enable voltage change auxiliary element Voltage setting for phase-to-ground under voltage auxiliary element Enable phase-to-ground under voltage auxiliary element Voltage setting for phase-to-phase under voltage auxiliary element Enable phase-to-phase under voltage auxiliary element 0 or 1 (0.050~30.000)×In (A) 0 or 1 (0.050~30.000)×In (A) 0.000~10.000 (s) 0 or 1 0~Un (V) 0 or 1 0~Unn (V) 0 or 1 7.3.1.4 DPFC Distance Protection Settings (21D) No. Item Remark Range 1 21D.Z_Set Impedance setting of DPFC distance protection (0.000~4Unn)/In (ohm) 2 21D.En Enable DPFC distance protection 0 or 1 7.3.1.5 Load Encroachment Settings (LoadEnch) No. Item Remark Range Angle setting of load trapezoid characteristic, it should 1 LoadEnch.phi be set according to the maximum load area angle 0~45 (deg) (φLoad_Max), φLoad_Max+5°is recommended. Impedance setting of load trapezoid characteristic, it 2 LoadEnch.Z_Set should be set according to the minimum load resistance, 70%~90% minimum load resistance is (0.05~200)/In (ohm) recommended. 3 LoadEnch.En Enable load trapezoid characteristic PCS-902 Line Distance Relay 0 or 1 7-15 Date: 2019-03-01 -09-07 7 Settings 7.3.1.6 Distance Protection Settings with Mho Characteristic (21M) No. Item 1 21-1.Real_K0 2 21-1.Imag_K0 3 21-1.phi1_Reach 4 21M1.ZGQ.RCA 5 21M1.ZG.phi_Shift 6 21M1.ZP.phi_Shift 7 21M1.ZG.Z_Set 8 21M1.ZGQ.R_Set 9 21M1.ZG.t_Op 10 21M1.ZG.En 11 21M1.ZGQ.En 12 21M1.ZG.En_BlkAR 13 21M1.ZP.Z_Set 14 21M1.ZP.t_Op 15 21M1.ZP.En 16 21M1.ZP.En_BlkAR 17 21-2. DirMode 18 21-2.Real_K0 19 21-2.Imag_K0 20 21-2.phi1_Reach 21 21M2.ZGQ.RCA Remark Range Real component of zero-sequence compensation coefficient for zone 1 Imaginary component of zero-sequence compensation coefficient for zone 1 Phase angle of positive-sequence impedance for zone 1 Downward offset angle of the reactance line for zone 1 of phase-to-ground distance protection Phase shift of phase-to-ground distance protection for zone 1 Phase shift of phase-to-phase distance protection for zone 1 Impedance setting of zone 1 of phase-to-ground distance protection Resistance setting of zone 1 of phase-to-ground distance protection Time delay of zone 1 of phase-to-ground distance protection -4.000~4.000 -4.000~4.000 30~89 (deg) 0~45 (deg) 0, 15 or 30 (deg) 0, 15 or 30 (deg) (0.000~4Unn)/In (ohm) (0.000~4Unn)/In (ohm) 0.000~10.000 (s) Enable zone 1 of phase-to-ground distance protection 0 or 1 Enable zone 1 of quadrilateral phase-to-ground distance protection Enable phase-to-ground zone 1 of distance protection operation to block AR Impedance setting of zone 1 of phase-to-phase distance protection Time delay of zone 1 of phase-to-phase distance protection Enable zone 1 of phase-to-phase distance protection Enable phase-to-phase zone 1 of distance protection operation to block AR Direction option for zone 2 of distance protection coefficient for zone 2 component of zero-sequence compensation coefficient for zone 2 Phase angle of positive-sequence impedance for zone 2 Downward offset angle of the reactance line for zone 2 of phase-to-ground distance protection 7-16 0 or 1 (0.000~4Unn)/In (ohm) 0.000~10.000 (s) 0 or 1 0 or 1 0 or 1 Real component of zero-sequence compensation Imaginary 0 or 1 -4.000~4.000 -4.000~4.000 30~89 (deg) 0~45 (deg) PCS-902 Line Distance Relay Date: 2019-03-01 -11-23 7 Settings Phase shift of phase-to-ground distance protection for 22 21M2.ZG.phi_Shift 23 21M2.ZP.phi_Shift 24 21M2.ZG.Z_Set 25 21M2.ZGQ.R_Set 26 21M2.ZG.t_Op 27 21M2.ZG.t_ShortDly 28 21M2.ZG.En 29 21M2.ZGQ.En 30 21M2.ZG.En_BlkAR 31 21M2.ZP.Z_Set 32 21M2.ZP.t_Op 33 21M2.ZP.t_ShortDly 34 21M2.ZP.En 35 21M2.ZP.En_BlkAR 36 21M2.En_ShortDly Enable fixed accelerate zone 2 of distance protection 0 or 1 37 21-3. DirMode Direction option for zone 3 of distance protection 38 21-3.Real_K0 39 21-3.Imag_K0 40 21-3.phi1_Reach 41 21M3.ZGQ.RCA 42 21M3.ZG.phi_Shift 43 21M3.ZP.phi_Shift 44 21M3.ZG.Z_Set zone 2 Phase shift of phase-to-phase distance protection for zone 2 Impedance setting of zone 2 of phase-to-ground distance protection Resistance setting of zone 2 of phase-to-ground distance protection Time delay of zone 2 of phase-to-ground distance protection Short time delay of zone 2 of phase-to-ground distance protection 0, 15 or 30 (deg) 0, 15 or 30 (deg) (0.000~4Unn)/In (ohm) (0.000~4Unn)/In (ohm) 0.000~10.000 (s) 0.000~10.000 (s) Enable zone 2 of phase-to-ground distance protection 0 or 1 Enable zone 2 of quadrilateral phase-to-ground distance protection Enable phase-to-ground zone 2 of distance protection operation to block AR Impedance setting of zone 2 of phase-to-phase distance protection Time delay of zone 2 of phase-to-phase distance protection Short time delay of zone 2 of phase-to-phase distance protection Enable zone 2 of phase-to-phase distance protection Enable phase-to-phase zone 2 of distance protection operation to block AR Real component of zero-sequence compensation coefficient for zone 3 Imaginary component of zero-sequence compensation coefficient for zone 3 Phase angle of positive-sequence impedance for zone 3 Downward offset angle of the reactance line for zone 3 of phase-to-ground distance protection Phase shift of phase-to-ground distance protection for zone 3 Phase shift of phase-to-phase distance protection for zone 3 Impedance setting of zone 3 of phase-to-ground distance protection PCS-902 Line Distance Relay 0 or 1 0 or 1 (0.000~4Unn)/In (ohm) 0.000~10.000 (s) 0.000~10.000 (s) 0 or 1 0 or 1 0 or 1 -4.000~4.000 -4.000~4.000 30~89 (deg) 0~45 (deg) 0, 15 or 30 (deg) 0, 15 or 30 (deg) (0.000~4Unn)/In (ohm) 7-17 Date: 2019-03-01 -09-07 7 Settings Resistance setting of zone 3 of phase-to-ground 45 21M3.ZGQ.R_Set 46 21M3.ZG.t_Op 47 21M3.ZG.t_ShortDly 48 21M3.ZG.En 49 21M3.ZGQ.En 50 21M3.ZG.En_BlkAR 51 21M3.ZP.Z_Set 52 21M3.ZP.t_Op 53 21M3.ZP.t_ShortDly 54 21M3.ZP.En 55 21M3.ZP.En_BlkAR 56 21M3.En_ShortDly Enable fixed accelerate zone 3 of distance protection 0 or 1 57 21-4. DirMode Direction option for zone 4 of distance protection 58 21-4.Real_K0 59 21-4.Imag_K0 60 21-4.phi1_Reach 61 21M4.ZGQ.RCA 62 21M4.ZG.phi_Shift 63 21M4.ZP.phi_Shift 64 21M4.ZG.Z_Set 65 21M4.ZGQ.R_Set 66 21M4.ZG.t_Op 67 21M4.ZG.t_ShortDly distance protection Time delay of zone 3 of phase-to-ground distance protection Short time delay of zone 3 of phase-to-ground distance protection (0.000~4Unn)/In (ohm) 0.000~10.000 (s) 0.000~10.000 (s) Enable zone 3 of phase-to-ground distance protection 0 or 1 Enable zone 3 of quadrilateral phase-to-ground distance protection Enable phase-to-ground zone 3 of distance protection operation to block AR Impedance setting of zone 3 of phase-to-phase distance protection Time delay of zone 3 of phase-to-phase distance protection Short time delay of zone 3 of phase-to-phase distance protection Enable zone 3 of phase-to-phase distance protection Enable phase-to-phase zone 3 of distance protection operation to block AR coefficient for zone 4 component of zero-sequence compensation coefficient for zone 4 Phase angle of positive-sequence impedance for zone 4 Downward offset angle of the reactance line for zone 4 of phase-to-ground distance protection Phase shift of phase-to-ground distance protection for zone 4 Phase shift of phase-to-phase distance protection for zone 4 Impedance setting of zone 4 of phase-to-ground distance protection Resistance setting of zone 4 of phase-to-ground distance protection Time delay of zone 4 of phase-to-ground distance protection Short time delay of zone 4 of phase-to-ground distance protection 7-18 0 or 1 (0.000~4Unn)/In (ohm) 0.000~10.000 (s) 0.000~10.000 (s) 0 or 1 0 or 1 0 or 1 Real component of zero-sequence compensation Imaginary 0 or 1 -4.000~4.000 -4.000~4.000 30~89 (deg) 0~45 (deg) 0, 15 or 30 (deg) 0, 15 or 30 (deg) (0.000~4Unn)/In (ohm) (0.000~4Unn)/In (ohm) 0.000~10.000 (s) 0.000~10.000 (s) PCS-902 Line Distance Relay Date: 2019-03-01 -11-23 7 Settings 68 21M4.ZG.En Enable zone 4 of phase-to-ground distance protection 0 or 1 69 21M4.ZGQ.En 70 21M4.ZG.En_BlkAR 71 21M4.ZP.Z_Set 72 21M4.ZP.t_Op 73 21M4.ZP.t_ShortDly 74 21M4.ZP.En 75 21M4.ZP.En_BlkAR 76 21M4.En_ShortDly Enable fixed accelerate zone 4 of distance protection 0 or 1 77 21-5. DirMode Direction option for zone 5 of distance protection 78 21-5.Real_K0 79 21-5.Imag_K0 80 21-5.phi1_Reach 81 21M5.ZGQ.RCA 82 21M5.ZG.phi_Shift 83 21M5.ZP.phi_Shift 84 21M5.ZG.Z_Set 85 21M5.ZGQ.R_Set 86 21M5.ZG.t_Op 87 21M5.ZG.t_ShortDly 88 21M5.ZG.En 89 21M5.ZGQ.En 90 21M5.ZG.En_BlkAR Enable zone 4 of quadrilateral phase-to-ground distance protection Enable phase-to-ground zone 4 of distance protection operation to block AR Impedance setting of zone 4 of phase-to-phase distance protection Time delay of zone 4 of phase-to-phase distance protection Short time delay of zone 4 of phase-to-phase distance protection Enable zone 4 of phase-to-phase distance protection Enable phase-to-phase zone 4 of distance protection operation to block AR Real component of zero-sequence compensation coefficient for zone 5 Imaginary component of zero-sequence compensation coefficient for zone 5 Phase angle of positive-sequence impedance for zone 5 Downward offset angle of the reactance line for zone 5 of phase-to-ground distance protection Phase shift of phase-to-ground distance protection for zone 5 Phase shift of phase-to-phase distance protection for zone 5 Impedance setting of zone 5 of phase-to-ground distance protection Resistance setting of zone 5 of phase-to-ground distance protection Time delay of zone 5 of phase-to-ground distance protection Short time delay of zone 5 of phase-to-ground distance protection 0 or 1 0 or 1 (0.000~4Unn)/In (ohm) 0.000~10.000 (s) 0.000~10.000 (s) 0 or 1 0 or 1 0 or 1 -4.000~4.000 -4.000~4.000 30~89 (deg) 0~45 (deg) 0, 15 or 30 (deg) 0, 15 or 30 (deg) (0.000~4Unn)/In (ohm) (0.000~4Unn)/In (ohm) 0.000~10.000 (s) 0.000~10.000 (s) Enable zone 5 of phase-to-ground distance protection 0 or 1 Enable zone 5 of quadrilateral phase-to-ground distance protection Enable phase-to-ground zone 5 of distance protection operation to block AR PCS-902 Line Distance Relay 0 or 1 0 or 1 7-19 Date: 2019-03-01 -09-07 7 Settings 91 21M5.ZP.Z_Set 92 21M5.ZP.t_Op 93 21M5.ZP.t_ShortDly 94 21M5.ZP.En 95 21M5.ZP.En_BlkAR 96 21M5.En_ShortDly Impedance setting of zone 5 of phase-to-phase distance protection Time delay of zone 5 of phase-to-phase distance protection Short time delay of zone 5 of phase-to-phase distance protection Enable zone 5 of phase-to-phase distance protection Enable phase-to-phase zone 5 of distance protection operation to block AR (0.000~4Unn)/In (ohm) 0.000~10.000 (s) 0.000~10.000 (s) 0 or 1 0 or 1 Enable fixed accelerate zone 5 of distance protection 0 or 1 7.3.1.7 Distance Protection Settings with Quad Characteristic (21Q) No. Item 1 21Q.Ang_Alpha 2 21-1.Real_K0 3 21-1.Imag_K0 4 21-1.phi1_Reach 5 21Q1.ZG.RCA 6 21Q1.ZG.Z_Set 7 21Q1.ZG.R_Set 8 21Q1.ZG.t_Op 9 21Q1.ZG.En 10 21Q1.ZG.En_BlkAR 11 21Q1.ZP.RCA 12 21Q1.ZP.Z_Set 13 21Q1.ZP.R_Set 14 21Q1.ZP.t_Op 15 21Q1.ZP.En 16 21Q1.ZP.En_BlkAR 17 21-2. DirMode Remark Range The angle of directional line 5~30 (deg) Real component of zero-sequence compensation coefficient for zone 1 Imaginary component of zero-sequence compensation coefficient for zone 1 Phase angle of positive-sequence impedance for zone 1 Downward offset angle of the reactance line for zone 1 of phase-to-ground distance protection Impedance setting of zone 1 of phase-to-ground distance protection Resistance setting of zone 1 of phase-to-ground distance protection Time delay of zone 1 of phase-to-ground distance protection -4.000~4.000 -4.000~4.000 30~89 (deg) 0~45 (deg) (0.000~4Unn)/In (ohm) (0.000~4Unn)/In (ohm) 0.000~10.000 (s) Enable zone 1 of phase-to-ground distance protection 0 or 1 Enable phase-to-ground zone 1 of distance protection operation to block AR Downward offset angle of the reactance line for zone 1 of phase-to-phase distance protection Impedance setting of zone 1 of phase-to-phase distance protection Resistance setting of zone 1 of phase-to-phase distance protection Time delay of zone 1 of phase-to-phase distance protection Enable zone 1 of phase-to-phase distance protection Enable phase-to-phase zone 1 of distance protection operation to block AR Direction option for zone 2 of distance protection 7-20 0 or 1 0~45 (0.000~4Unn)/In (ohm) (0.000~4Unn)/In (ohm) 0.000~10.000 (s) 0 or 1 0 or 1 0 or 1 PCS-902 Line Distance Relay Date: 2019-03-01 -11-23 7 Settings Real component of zero-sequence compensation 18 21-2.Real_K0 19 21-2.Imag_K0 20 21-2.phi1_Reach 21 21Q2.ZG.RCA 22 21Q2.ZG.Z_Set 23 21Q2.ZG.R_Set 24 21Q2.ZG.t_Op 25 21Q2.ZG.t_ShortDly 26 21Q2.ZG.En 27 21Q2.ZG.En_BlkAR 28 21Q2.ZP.RCA 29 21Q2.ZP.Z_Set 30 21Q2.ZP.R_Set 31 21Q2.ZP.t_Op 32 21Q2.ZP.t_ShortDly 33 21Q2.ZP.En 34 21Q2.ZP.En_BlkAR 35 21Q2.En_ShortDly Enable fixed accelerate zone 2 of distance protection 0 or 1 36 21-3. DirMode Direction option for zone 3 of distance protection 0 or 1 37 21-3.Real_K0 38 21-3.Imag_K0 39 21-3.phi1_Reach 40 21Q3.ZG.RCA coefficient for zone 2 Imaginary component of zero-sequence compensation coefficient for zone 2 Phase angle of positive-sequence impedance for zone 2 Downward offset angle of the reactance line for zone 2 of phase-to-ground distance protection Impedance setting of zone 2 of phase-to-ground distance protection Resistance setting of zone 2 of phase-to-ground distance protection Time delay of zone 2 of phase-to-ground distance protection Short time delay of zone 2 of phase-to-ground distance protection -4.000~4.000 -4.000~4.000 30~89 (deg) 0~45 (deg) (0.000~4Unn)/In (ohm) (0.000~4Unn)/In (ohm) 0.000~10.000 (s) 0.000~10.000 (s) Enable zone 2 of phase-to-ground distance protection 0 or 1 Enable phase-to-ground zone 2 of distance protection operation to block AR Downward offset angle of the reactance line for zone 2 of phase-to-phase distance protection Impedance setting of zone 2 of phase-to-phase distance protection Resistance setting of zone 2 of phase-to-phase distance protection Time delay of zone 2 of phase-to-phase distance protection Short time delay of zone 2 of phase-to-ground distance protection Enable zone 2 of phase-to-phase distance protection Enable phase-to-phase zone 2 of distance protection operation to block AR Real component of zero-sequence compensation coefficient for zone 3 Imaginary component of zero-sequence compensation coefficient for zone 3 Phase angle of positive-sequence impedance for zone 3 Downward offset angle of the reactance line for zone 3 of phase-to-ground distance protection PCS-902 Line Distance Relay 0 or 1 0~45 (0.000~4Unn)/In (ohm) (0.000~4Unn)/In (ohm) 0.000~10.000 (s) 0.000~10.000 (s) 0 or 1 0 or 1 -4.000~4.000 -4.000~4.000 30~89 (deg) 0~45 (deg) 7-21 Date: 2019-03-01 -09-07 7 Settings Impedance setting of zone 3 of phase-to-ground 41 21Q3.ZG.Z_Set 42 21Q3.ZG.R_Set 43 21Q3.ZG.t_Op 44 21Q3.ZG.t_ShortDly 45 21Q3.ZG.En 46 21Q3.ZG.En_BlkAR 47 21Q3.ZP.RCA 48 21Q3.ZP.Z_Set 49 21Q3.ZP.R_Set 50 21Q3.ZP.t_Op 51 21Q3.ZP.t_ShortDly 52 21Q3.ZP.En 53 21Q3.ZP.En_BlkAR 54 21Q3.En_ShortDly Enable fixed accelerate zone 3 of distance protection 0 or 1 55 21-4. DirMode Direction option for zone 4 of distance protection 0 or 1 56 21-4.Real_K0 57 21-4.Imag_K0 58 21-4.phi1_Reach 59 21Q4.ZG.RCA 60 21Q4.ZG.Z_Set 61 21Q4.ZG.R_Set 62 21Q4.ZG.t_Op 63 21Q4.ZG.t_ShortDly distance protection Resistance setting of zone 3 of phase-to-ground distance protection Time delay of zone 3 of phase-to-ground distance protection Short time delay of zone 3 of phase-to-ground distance protection (0.000~4Unn)/In (ohm) (0.000~4Unn)/In (ohm) 0.000~10.000 (s) 0.000~10.000 (s) Enable zone 3 of phase-to-ground distance protection 0 or 1 Enable phase-to-ground zone 3 of distance protection operation to block AR Downward offset angle of the reactance line for zone 3 of phase-to-phase distance protection Impedance setting of zone 3 of phase-to-phase distance protection Resistance setting of zone 3 of phase-to-phase distance protection Time delay of zone 3 of phase-to-phase distance protection Short time delay of zone 3 of phase-to-ground distance protection Enable zone 3 of phase-to-phase distance protection Enable phase-to-phase zone 3 of distance protection operation to block AR Real component of zero-sequence compensation coefficient for zone 4 Imaginary component of zero-sequence compensation coefficient for zone 4 Phase angle of positive-sequence impedance for zone 4 Downward offset angle of the reactance line for zone 4 of phase-to-ground distance protection Impedance setting of zone 4 of phase-to-ground distance protection Resistance setting of zone 4 of phase-to-ground distance protection Time delay of zone 4 of phase-to-ground distance protection Short time delay of zone 4 of phase-to-ground distance protection 7-22 0 or 1 0~45 (0.000~4Unn)/In (ohm) (0.000~4Unn)/In (ohm) 0.000~10.000 (s) 0.000~10.000 (s) 0 or 1 0 or 1 -4.000~4.000 -4.000~4.000 30~89 (deg) 0~45 (deg) (0.000~4Unn)/In (ohm) (0.000~4Unn)/In (ohm) 0.000~10.000 (s) 0.000~10.000 (s) PCS-902 Line Distance Relay Date: 2019-03-01 -11-23 7 Settings 64 21Q4.ZG.En Enable zone 4 of phase-to-ground distance protection 0 or 1 65 21Q4.ZG.En_BlkAR 66 21Q4.ZP.RCA 67 21Q4.ZP.Z_Set 68 21Q4.ZP.R_Set 69 21Q4.ZP.t_Op 70 21Q4.ZP.t_ShortDly 71 21Q4.ZP.En 72 21Q4.ZP.En_BlkAR 73 21Q4.En_ShortDly Enable fixed accelerate zone 4 of distance protection 0 or 1 74 21-5. DirMode Direction option for zone 5 of distance protection 0 or 1 75 21-5.Real_K0 76 21-5.Imag_K0 77 21-5.phi1_Reach 78 21Q5.ZG.RCA 79 21Q5.ZG.Z_Set 80 21Q5.ZG.R_Set 81 21Q5.ZG.t_Op 82 21Q5.ZG.t_ShortDly 83 21Q5.ZG.En 84 21Q5.ZG.En_BlkAR 85 21Q5.ZP.RCA 86 21Q5.ZP.Z_Set Enable phase-to-ground zone 4 of distance protection operation to block AR Downward offset angle of the reactance line for zone 4 of phase-to-phase distance protection Impedance setting of zone 4 of phase-to-phase distance protection Resistance setting of zone 4 of phase-to-phase distance protection Time delay of zone 4 of phase-to-phase distance protection Short time delay of zone 4 of phase-to-ground distance protection Enable zone 4 of phase-to-phase distance protection Enable phase-to-phase zone 4 of distance protection operation to block AR Real component of zero-sequence compensation coefficient for zone 5 Imaginary component of zero-sequence compensation coefficient for zone 5 Phase angle of positive-sequence impedance for zone 5 Downward offset angle of the reactance line for zone 5 of phase-to-ground distance protection Impedance setting of zone 5 of phase-to-ground distance protection Resistance setting of zone 5 of phase-to-ground distance protection Time delay of zone 5 of phase-to-ground distance protection Short time delay of zone 5 of phase-to-ground distance protection 0 or 1 0~45 (0.000~4Unn)/In (ohm) (0.000~4Unn)/In (ohm) 0.000~10.000 (s) 0.000~10.000 (s) 0 or 1 0 or 1 -4.000~4.000 -4.000~4.000 30~89 (deg) 0~45 (deg) (0.000~4Unn)/In (ohm) (0.000~4Unn)/In (ohm) 0.000~10.000 (s) 0.000~10.000 (s) Enable zone 5 of phase-to-ground distance protection 0 or 1 Enable phase-to-ground zone 5 of distance protection operation to block AR Downward offset angle of the reactance line for zone 5 of phase-to-phase distance protection Impedance setting of zone 5 of phase-to-phase distance protection PCS-902 Line Distance Relay 0 or 1 0~45 (0.000~4Unn)/In (ohm) 7-23 Date: 2019-03-01 -09-07 7 Settings 87 21Q5.ZP.R_Set 88 21Q5.ZP.t_Op 89 21Q5.ZP.t_ShortDly 90 21Q5.ZP.En 91 21Q5.ZP.En_BlkAR 92 21Q5.En_ShortDly Resistance setting of zone 5 of phase-to-phase distance protection Time delay of zone 5 of phase-to-phase distance protection Short time delay of zone 5 of phase-to-ground distance protection Enable zone x of phase-to-phase distance protection Enable phase-to-phase zone 5 of distance protection operation to block AR Enable fixed accelerate zone 5 of distance protection (0.000~4Unn)/In (ohm) 0.000~10.000 (s) 0.000~10.000 (s) 0 or 1 0 or 1 0 or 1 7.3.1.8 Pilot Distance Zone Settings No. Item 1 21.Pilot.Real_K0 2 21.Pilot.Imag_K0 3 21.Pilot.phi1_Reach 4 21M.Pilot.Z_Set 5 21M.Pilot.R_Set_Quad 6 21Q.Pilot.Z_Set 7 21M.Pilot.Z_Rev 8 21M.Pilot.En_Z_Quad 9 21Q.Pilot.Z_Rev 10 21Q.Pilot.R_Set 11 21Q.Pilot.R_Rev Remark Range Real component of zero-sequence compensation coefficient for pilot distance protection Imaginary component of zero-sequence compensation coefficient for pilot distance protection Phase angle of positive-sequence impedance for pilot distance protection Impedance setting of pilot distance protection (Mho characteristic) Resistance setting of pilot distance protection (Mho characteristic) Impedance setting of pilot distance protection (Quad characteristic) Impedance setting of pilot distance protection in reverse direction (Mho characteristic) Enable quadrilateral characteristic of phase-to-ground distance protection Impedance setting of pilot distance protection in reverse direction (Quad characteristic) Resistance setting of pilot distance protection (Quad characteristic) Resistance setting of pilot distance protection in reverse direction (Quad characteristic) 30.00~89.00 (deg) -4.000~4.000 -4.000~4.000 (0.000~4Unn)/In (ohm) (0.000~4Unn)/In (ohm) (0.000~4Unn)/In (ohm) (0.000~4Unn)/In (ohm) 0 or 1 (0.000~4Unn)/In (ohm) (0.000~4Unn)/In (ohm) (0.000~4Unn)/In (ohm) 7.3.1.9 Out-of-step Protection Settings (78) No. Item Remark Range 1 78.En Enable out-of-step protection 0 or 1 2 78.En_Trp Enable out-of-step protection operate to trip 0 or 1 3 78.Z_Fwd The forward impedance setting of zone detector element 7-24 (0.000~4Unn)/In (ohm) PCS-902 Line Distance Relay Date: 2019-03-01 -11-23 7 Settings 4 78.Z_Rev 5 78.phi1_Reach 6 78.phi_Start The reversal impedance setting of zone detector element The system impedance angle The minimum start angle, which generally should be greater than maximum load angle. (0.000~4Unn)/In (ohm) 30.00~89.00 (deg) 0~180 (deg) It is the maximum tripping angle after out-of-step protection operating, which is used to prevent the 7 78.phi_Trp circuit breaker from incorrect operation due to too 0~180.00 (deg) large current during tripping. It is generally set based on the breaking capacity of circuit breaker. 8 78.N_Limit The number setting of out-of-step cycle, and it is set as 2~3 generally 1~20 7.3.1.10 Power Swing Blocking Releasing Settings (PSBR) No. Item 1 21M1.En_PSBR 2 21Q1.En_PSBR 3 21M2.En_PSBR 4 21Q2.En_PSBR 5 21M3.En_PSBR 6 21Q3.En_PSBR 7 21M4.En_PSBR 8 21Q4.En_PSBR 9 21M5.En_PSBR 10 21Q5.En_PSBR 11 21M.Pilot.En_PSBR 12 21Q.Pilot.En_PSBR 13 21M.I_PSBR 14 21Q.I_PSBR Remark Enable zone 1 of distance protection controlled by PSBR (Mho characteristic) Enable zone 1 of distance protection controlled by PSBR (Quad characteristic) Enable zone 2 of distance protection controlled by PSBR (Mho characteristic) Enable zone 2 of distance protection controlled by PSBR (Quad characteristic) Enable zone 3 of distance protection controlled by PSBR (Mho characteristic) Enable zone 3 of distance protection controlled by PSBR (Quad characteristic) Enable zone 4 of distance protection controlled by PSBR (Mho characteristic) Enable zone 4 of distance protection controlled by PSBR (Quad characteristic) Enable zone 5 of distance protection controlled by PSBR (Mho characteristic) Enable zone 5 of distance protection controlled by PSBR (Quad characteristic) Enable pilot distance zone controlled by PSBR (Mho characteristic) Enable pilot distance zone controlled by PSBR (Quad characteristic) Current setting for power swing blocking (Mho characteristic) Current setting for power swing blocking (Quad characteristic) PCS-902 Line Distance Relay Range 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 (0.050~30.000)×In (ohm) (0.050~30.000)×In (ohm) 7-25 Date: 2019-03-01 -09-07 7 Settings 7.3.1.11 Distance SOTF Protection Settings (21SOTF) No. Item Remark Range Time delay of enabling SOTF protection (shared 1 SOTF.t_En by distance SOTF protection, phase current SOTF 0.000~10.000 (s) protection and residual current SOTF protection) 2 21SOTF.En Enable distance SOTF protection 0 or 1 3 21SOTF.Z2.En_ManCls 4 21SOTF.Z3.En_ManCls 5 21SOTF.Z4.En_ManCls 6 21SOTF.t_ManCls 7 21SOTF.Z2.En_3PAR 8 21SOTF.Z3.En_3PAR 9 21SOTF.Z4.En_3PAR 10 21SOTF.Z2.En_PSBR 11 21SOTF.Z3.En_PSBR 12 21SOTF.Z4.En_PSBR 13 21SOTF.t_3PAR 14 21SOTF.En_1PAR 15 21SOTF.t_1PAR 16 21SOTF.En_PDF 17 21SOTF.t_PDF 18 SOTF.U_Ddl Undervoltage setting of deadline detection 0~Unn (V) 19 SOTF.t_Ddl Time delay of deadline detection 0.000~600.000 (s) Enable zone 2 of distance SOTF protection for manual closing Enabling/disabling zone 3 of distance SOTF protection for manual closing Enable zone 4 of distance SOTF protection for manual closing Time delay of distance protection accelerating to trip when manual closing Enable zone 2 of distance SOTF protection for 3-pole reclosing Enable zone 3 of distance SOTF protection for 3-pole reclosing Enable zone 4 of distance SOTF protection for 3-pole reclosing Enable zone 2 controlled by PSB of distance SOTF protection for 3-pole reclosing Enable zone 3 controlled by PSB of distance SOTF protection for 3-pole reclosing Enable zone 4 controlled by PSB of distance SOTF protection for 3-pole reclosing Time delay of distance protection accelerating to trip when 3-pole reclosing Enable distance SOTF protection for 1-pole reclosing Time delay of distance protection accelerating to trip when 1-pole reclosing Enable distance SOTF protection under pole discrepancy conditions Time delay of distance protection operating under pole discrepancy conditions 7-26 0 or 1 0 or 1 0 or 1 0.000~10.000 (s) 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 0.000~10.000 (s) 0 or 1 0.000~10.000 (s) 0 or 1 0.000~10.000 (s) PCS-902 Line Distance Relay Date: 2019-03-01 -11-23 7 Settings ManClsBI CBPos 20 SOTF.Opt_Mode_ManCls Option of manual SOTF mode ManClsBI/ CBPos AutoInit All 7.3.1.12 Optical Pilot Channel Settings No. Item Remark Range 1 FO.LocID Identity code of the device at local end 0-65535 2 FO.RmtID Identity code of the device at remote end 0-65535 3 FO.BaudRate Baud rate of optical pilot channel 64 or 2048 4 FO.Protocol It is used to select protocol type, G.703 or C37.94 G.703 or C37.94 5 FOx.Nx64k_C37.94 6 FOx.En_IntClock Option of internal clock or external clock 0 or 1 7 FOx.En Enable channel x 0 or 1 The setting for the times of 64kbits/s, which is an N*64kbits/s standard defined by IEEE C37.94 standard 1-12 7.3.1.13 Pilot Distance Protection Settings (85) No. Item Remark Range POTT 1 85.Opt_PilotMode Option of pilot scheme PUTT Blocking Option of phase-segregated signal scheme or single 2 85.Opt_Ch_PhSeg 3 85.En_WI 4 85.En_WI_Pkp 5 85.U_UV_WI Undervoltage setting of weak infeed logic 0~Unn (V) 6 85.Z.En Enable pilot distance protection 0 or 1 7 85.En_Unblocking1 Enable unblocking scheme 0 or 1 8 85.t_DPU_Blocking1 9 85.t_DPU_CR1 Time delay pickup for current reversal logic 0.000~1.000 (s) 10 85.t_DDO_CR1 Time delay dropoff for current reversal logic 0.000~1.000 (s) 11 85.ZX.En Enable zone extension protection 0 or 1 12 85.t_DPU_ZX signal scheme Enable weak infeed scheme For weak infeed end, If the device does not pick up for internal fault, it is used to enable the device pick up. Time delay for blocking scheme of pilot distance protection operation Pickup time delay for zone extension protection operation 0 or 1 0 or 1 0 or 1 0.000~1.000 (s) 0.000~10.000 (s) 7.3.1.14 Pilot Directional Earth-fault Protection Settings (85) No. 1 Item 85.DEF.En Remark Enable pilot directional earth-fault protection PCS-902 Line Distance Relay Range 0 or 1 7-27 Date: 2019-03-01 -09-07 7 Settings 2 85.DEF.En_BlkAR 3 85.DEF.En_IndepCh 4 85.En_Unblocking2 5 85.DEF.3I0_Set 6 85.DEF.t_DPU Enable pilot directional earth-fault protection operate to block AR Enable independent pilot channel for pilot directional earth-fault protection Enable unblocking scheme for pilot DEF via pilot channel 2 Current setting of pilot directional earth-fault protection Time delay of pilot directional earth-fault protection 0 or 1 0 or 1 0 or 1 (0.050~30.000)×In (A) 0.001~10.000 (s) Time delay pickup for current reversal logic when pilot 7 85.t_DPU_CR2 directional earth-fault protection adopts independent 0.000~1.000 (s) pilot channel 2 Time delay dropoff for current reversal logic when 8 85.t_DDO_CR2 pilot directional earth-fault protection adopts 0.000~1.000 (s) independent pilot channel 2 7.3.1.15 Current Direction Settings No. Item Remark The characteristic angle Range of directional phase 1 RCA_OC 2 RCA_ROC 3 RCA_NegOC 4 Z0_Comp Zero-sequence compensation impedance setting (0.000~4Unn)/In (ohm) 5 Z2_Comp Negative-sequence compensation impedance setting (0.000~4Unn)/In (ohm) overcurrent element The characteristic angle of directional earth fault element The characteristic angle of directional negative-sequence overcurrent element 30.00~89.00 (deg) 30.00~89.00 (deg) 30.00~89.00 (deg) 7.3.1.16 Phase Overcurrent Protection Settings (50/51P) No. Item 1 50/51P.K_Hm2 2 50/51P1.I_Set 3 50/51P1.t_Op 4 50/51P1.En 5 50/51P1.En_BlkAR 6 50/51P1.En_VTS_Blk 7 50/51P1.Opt_Dir Remark Range Setting of second harmonic component for blocking phase overcurrent elements Current setting for stage 1 of phase overcurrent protection Time delay for stage 1 of phase overcurrent protection Enable stage 1 of phase overcurrent protection (0.050~30.000)×In (A) 0.000~20.000 (s) 0 or 1 Enable auto-reclosing blocked when stage 1 of phase overcurrent protection operates Enable stage 1 of phase overcurrent protection is blocked by VT circuit failure Direction option for stage 1 of phase overcurrent protection 0.000~1.000 0 or 1 0 or 1 Non_Directional Forward Reverse 7-28 PCS-902 Line Distance Relay Date: 2019-03-01 -11-23 7 Settings 8 50/51P1.En_Hm2_Blk Enable second harmonic blocking for stage 1 of phase overcurrent protection 0 or 1 DefTime IECN IECV IECE IECST IECLT 9 50/51P1.Opt_Curve Option of characteristic curve for stage 1 of phase ANSIE overcurrent protection ANSIV ANSI ANSIM ANSILTE ANSILTV ANSILT UserDefine 10 50/51P1.TMS 11 50/51P1.tmin 12 50/51P1.Alpha 13 50/51P1.C 14 50/51P1.K 15 50/51P2.I_Set 16 50/51P2.t_Op 17 50/51P2.En 18 50/51P2.En_BlkAR 19 50/51P2.En_VTS_Blk 20 21 50/51P2.Opt_Dir 50/51P2.En_Hm2_Blk Time multiplier setting for stage 1 of inverse-time phase overcurrent protection Minimum operating time for stage 1 of inverse-time phase overcurrent protection Constant “α” for stage 1 of customized inverse-time characteristic phase overcurrent protection Constant “C” for stage 1 of customized inverse-time characteristic phase overcurrent protection Constant “K” for stage 1 of customized inverse-time characteristic phase overcurrent protection Current setting for stage 2 of phase overcurrent protection Time delay for stage 2 of phase overcurrent protection Enable stage 2 of phase overcurrent protection Enable auto-reclosing blocked when stage 2 of phase overcurrent protection operates Enable stage 2 of phase overcurrent protection is blocked by VT circuit failure Direction option for stage 2 of phase overcurrent protection 0.010~200.000 0.000~20.000 (s) 0.010~5.000 0.000~20.000 0.050~20.000 (0.050~30.000)×In (A) 0.000~20.000 (s) 0 or 1 0 or 1 0 or 1 Non_Directional Forward Reverse Enable second harmonic blocking for stage 2 of phase overcurrent protection PCS-902 Line Distance Relay 0 or 1 7-29 Date: 2019-03-01 -09-07 7 Settings DefTime IECN IECV IECE IECST 22 50/51P2.Opt_Curve Option of characteristic curve for stage 2 of phase overcurrent protection IECLT ANSIE ANSIV ANSI ANSIM ANSILTE ANSILTV ANSILT 23 50/51P2.TMS 24 50/51P2.tmin 25 50/51P3.I_Set 26 50/51P3.t_Op 27 50/51P3.En 28 50/51P3.En_BlkAR 29 50/51P3.En_VTS_Blk 30 31 50/51P3.Opt_Dir 50/51P3.En_Hm2_Blk Time multiplier setting for stage 2 of inverse-time phase overcurrent protection. Minimum operating time for stage 2 of inverse-time phase overcurrent protection Current setting for stage 3 of phase overcurrent protection Time delay for stage 3 of phase overcurrent protection Enable stage 3 of phase overcurrent protection 0.010~200.000 0.000~20.000 (s) (0.050~30.000)×In (A) 0.000~20.000 (s) 0 or 1 Enable auto-reclosing blocked when stage 3 of phase overcurrent protection operates Enable stage 3 of phase overcurrent protection is blocked by VT circuit failure Direction option for stage 3 of phase overcurrent protection 0 or 1 0 or 1 Non_Directional Forward Reverse Enable second harmonic blocking for stage 3 of phase overcurrent protection 0 or 1 DefTime IECN IECV IECE IECST 32 50/51P3.Opt_Curve Option of characteristic curve for stage 3 of phase overcurrent protection IECLT ANSIE ANSIV ANSI ANSIM ANSILTE ANSILTV ANSILT 7-30 PCS-902 Line Distance Relay Date: 2019-03-01 -11-23 7 Settings 33 50/51P3.TMS 34 50/51P3.tmin 35 50/51P4.I_Set 36 50/51P4.t_Op 37 50/51P4.En 38 50/51P4.En_BlkAR 39 50/51P4.En_VTS_Blk 40 41 50/51P4.Opt_Dir 50/51P4.En_Hm2_Blk Time multiplier setting for stage 3 of inverse-time phase overcurrent protection. Minimum operating time for stage 3 of inverse-time phase overcurrent protection Current setting for stage 4 of phase overcurrent protection Time delay for stage 4 of phase overcurrent protection Enable stage 4 of phase overcurrent protection Enable auto-reclosing blocked when stage 4 of phase overcurrent protection operates Enable stage 4 of phase overcurrent protection is blocked by VT circuit failure Direction option for stage 4 of phase overcurrent protection 0.010~200.000 0.000~20.000 (s) (0.050~30.000)×In (A) 0.000~20.000 (s) 0 or 1 0 or 1 0 or 1 Non_Directional Forward Reverse Enable second harmonic blocking for stage 4 of phase overcurrent protection 0 or 1 DefTime IECN IECV IECE IECST 42 50/51P4.Opt_Curve Option of characteristic curve for stage 4 of phase overcurrent protection IECLT ANSIE ANSIV ANSI ANSIM ANSILTE ANSILTV ANSILT 43 50/51P4.TMS 44 50/51P4.tmin Time multiplier setting for stage 4 of inverse-time phase overcurrent protection. Minimum operating time for stage 4 of inverse-time phase overcurrent protection 0.010~200.000 0.010~20.000 (s) 7.3.1.17 Earth Fault Protection Settings (50/51G) No. Item Remark Setting of second harmonic component for blocking Range 1 50/51G.K_Hm2 2 50/51G1.3I0_Set Current setting for stage 1 of earth fault protection (0.050~30.000)×In (A) 3 50/51G1.t_Op Time delay for stage 1 of earth fault protection 0.000~20.000 (s) 4 50/51G1.En Enable stage 1 of earth fault protection 0 or 1 earth fault elements PCS-902 Line Distance Relay 0.000~1.000 7-31 Date: 2019-03-01 -09-07 7 Settings 5 50/51G1.En_BlkAR Enable auto-reclosing blocked when stage 1 of earth fault protection operates 0 or 1 Non_Directional 6 50/51G1.Opt_Dir Direction option for stage 1 of earth fault protection Forward Reverse 7 50/51G1.En_Hm2_Blk 8 50/51G1.En_Abnor_Blk 9 50/51G1.En_VTS_Blk 10 50/51G1.En_CTS_Blk Enable second harmonic blocking for stage 1 of earth fault protection Enable blocking for stage 1 of earth fault protection under abnormal conditions Enable blocking for stage 1 of earth fault protection under VT failure conditions Enable blocking for stage 1 of earth fault protection under CT failure conditions 0 or 1 0 or 1 0 or 1 0 or 1 DefTime IECN IECV IECE IECST IECLT 11 50/51G1.Opt_Curve Option of characteristic curve for stage 1 of earth ANSIE fault protection ANSIV ANSI ANSIM ANSILTE ANSILTV ANSILT UserDefine Time multiplier setting for stage 1 of inverse-time 12 50/51G1.TMS 13 50/51G1.tmin 14 50/51G1.Alpha 15 50/51G1.C 16 50/51G1.K 17 50/51G2.3I0_Set Current setting for stage 2 of earth fault protection (0.050~30.000)×In (A) 18 50/51G2.t_Op Time delay for stage 2 of earth fault protection 0.000~20.000 (s) 19 50/51G2.t_ShortDly Short time delay for stage 2 of earth fault protection 0.000~20.000 (s) 20 50/51G2.En Enable stage 2 of earth fault protection 21 50/51G2.En_ShortDly earth fault protection Minimum operating time for stage 1 of inverse-time earth fault protection Constant “α” for stage 1 of customized inverse-time characteristic earth fault protection Constant “C” for stage 1 of customized inverse-time characteristic earth fault protection Constant “K” for stage 1 of customized inverse-time characteristic earth fault protection 7-32 0.050~20.000 (t) 0.010~5.000 0.000~20.000 0.050~20.000 0 or 1 Enable short time delay for stage 2 of earth fault protection 0.010~200.000 0 or 1 PCS-902 Line Distance Relay Date: 2019-03-01 -11-23 7 Settings 22 50/51G2.En_BlkAR Enable auto-reclosing blocked when stage 2 of earth fault protection operates 0 or 1 Non_Directional 23 50/51G2.Opt_Dir Direction option for stage 2 of earth fault protection Forward Reverse 24 50/51G2.En_Hm2_Blk 25 50/51G2.En_Abnor_Blk 26 50/51G2.En_VTS_Blk 27 50/51G2.En_CTS_Blk Enable second harmonic blocking for stage 2 of earth fault protection Enable blocking for stage 2 of earth fault protection under abnormal conditions Enable blocking for stage 2 of earth fault protection under VT failure conditions Enable blocking for stage 2 of earth fault protection under CT failure conditions 0 or 1 0 or 1 0 or 1 0 or 1 DefTime IECN IECV IECE IECST 28 50/51G2.Opt_Curve Option of characteristic curve for stage 2 of earth fault protection IECLT ANSIE ANSIV ANSI ANSIM ANSILTE ANSILTV ANSILT Time multiplier setting for stage 2 of inverse-time 29 50/51G2.TMS 30 50/51G2.tmin 31 50/51G3.3I0_Set Current setting for stage 3 of earth fault protection (0.050~30.000)×In (A) 32 50/51G3.t_Op Time delay for stage 3 of earth fault protection 0.000~20.000 (s) 33 50/51G3.t_ShortDly Short time delay for stage 3 of earth fault protection 0.000~20.000 (s) 34 50/51G3.En Enable stage 3 of earth fault protection 35 50/51G3.En_ShortDly 36 50/51G3.En_BlkAR earth fault protection Minimum operating time for stage 2 of inverse-time earth fault protection Enable short time delay for stage 3 of earth fault protection Enable auto-reclosing blocked when stage 3 of earth fault protection operates 0.010~200.000 0.050~20.000 (s) 0 or 1 0 or 1 0 or 1 Non_Directional 37 50/51G3.Opt_Dir Direction option for stage 3 of earth fault protection Forward Reverse 38 50/51G3.En_Hm2_Blk Enable second harmonic blocking for stage 3 of earth fault protection PCS-902 Line Distance Relay 0 or 1 7-33 Date: 2019-03-01 -09-07 7 Settings 39 50/51G3.En_Abnor_Blk 40 50/51G3.En_VTS_Blk 41 50/51G3.En_CTS_Blk Enable blocking for stage 3 of earth fault protection under abnormal conditions Enable blocking for stage 3 of earth fault protection under VT failure conditions Enable blocking for stage 3 of earth fault protection under CT failure conditions 0 or 1 0 or 1 0 or 1 DefTime IECN IECV IECE IECST 42 50/51G3.Opt_Curve Option of characteristic curve for stage 3 of earth fault protection IECLT ANSIE ANSIV ANSI ANSIM ANSILTE ANSILTV ANSILT Time multiplier setting for stage 3 of inverse-time 43 50/51G3.TMS 44 50/51G3.tmin 45 50/51G4.3I0_Set Current setting for stage 4 of earth fault protection (0.050~30.000)×In (A) 46 50/51G4.t_Op Time delay for stage 4 of earth fault protection 0.000~20.000 (s) 47 50/51G4.t_ShortDly Short time delay for stage 4 of earth fault protection 0.000~20.000 (s) 48 50/51G4.En Enable stage 4 of earth fault protection 49 50/51G4.En_ShortDly 50 50/51G4.En_BlkAR earth fault protection Minimum operating time for stage 3 of inverse-time earth fault protection 0.010~200.000 0.050~20.000 (s) 0 or 1 Enable short time delay for stage 4 of earth fault protection Enable auto-reclosing blocked when stage 4 of earth fault protection operates 0 or 1 0 or 1 Non_Directional 51 50/51G4.Opt_Dir Direction option for stage 4 of earth fault protection Forward Reverse 52 50/51G4.En_Hm2_Blk 53 50/51G4.En_Abnor_Blk 54 50/51G4.En_VTS_Blk 55 50/51G4.En_CTS_Blk Enable second harmonic blocking for stage 4 of earth fault protection Enable blocking for stage 4 of earth fault protection under abnormal conditions Enable blocking for stage 4 of earth fault protection under VT failure conditions Enable blocking for stage 4 of earth fault protection under CT failure conditions 7-34 0 or 1 0 or 1 0 or 1 0 or 1 PCS-902 Line Distance Relay Date: 2019-03-01 -11-23 7 Settings DefTime IECN IECV IECE IECST 56 50/51G4.Opt_Curve Option of characteristic curve for stage 4 of earth fault protection IECLT ANSIE ANSIV ANSI ANSIM ANSILTE ANSILTV ANSILT 57 50/51G4.TMS 58 50/51G4.tmin Time multiplier setting for stage 4 of inverse-time earth fault protection Minimum operating time for stage 4 of inverse-time earth fault protection 0.010~200.000 0.050~20.000 (s) 7.3.1.18 Negative-sequence Overcurrent Protection Settings (50/51Q) No. Item 1 50/51Q1.I2_Set 2 50/51Q1.I2/I1_Set 3 50/51Q1.t_Op 4 50/51Q1.En 5 50/51Q1.En_BlkAR 6 50/51Q1.Opt_Dir 7 50/51Q1.En_Abnor_Blk 8 50/51Q1.En_VTS_Blk 9 50/51Q1.En_CTS_Blk Remark Range Current setting for stage 1 of negative-sequence overcurrent protection Ratio coefficient (I2/I1) for stage 1 of negative-sequence overcurrent protection Time delay for stage 1 of negative-sequence overcurrent protection Enable stage 1 of negative-sequence overcurrent protection Enable auto-reclosing blocked when stage 1 of negative-sequence overcurrent protection operates Direction option for stage 1 of negative-sequence overcurrent protection Enable blocking for stage 1 of negative-sequence overcurrent protection under abnormal conditions Enable blocking for stage 1 of negative-sequence overcurrent protection under VT failure conditions Enable blocking for stage 1 of negative-sequence overcurrent protection under CT failure conditions PCS-902 Line Distance Relay (0.050~30.000)×In (A) 0.00~1.00 0.000~20.000 (s) 0 or 1 0 or 1 Non_Directional Forward Reverse 0 or 1 0 or 1 0 or 1 7-35 Date: 2019-03-01 -09-07 7 Settings DefTime IECN IECV IECE IECST IECLT 10 50/51Q1.Opt_Curve Option of characteristic curve for stage 1 of ANSIE negative-sequence overcurrent protection ANSIV ANSI ANSIM ANSILTE ANSILTV ANSILT UserDefine 11 50/51Q1.TMS 12 50/51Q1.tmin Time multiplier setting for stage 1 of inverse-time negative-sequence overcurrent protection Minimum operating time for stage 1 of inverse-time negative-sequence overcurrent protection 0.010~200.000 0.050~20.000 (s) Constant “α” for stage 1 of customized inverse-time 13 50/51Q1.Alpha characteristic negative-sequence overcurrent 0.010~5.000 protection Constant “C” for stage 1 of customized inverse-time 14 50/51Q1.C characteristic negative-sequence overcurrent 0.000~20.000 protection Constant “K” for stage 1 of customized inverse-time 15 50/51Q1.K characteristic negative-sequence overcurrent 0.050~20.000 protection 16 50/51Q2.I2_Set 17 50/51Q2.I2/I1_Set 18 50/51Q2.t_Op 19 50/51Q2.En 20 50/51Q2.En_BlkAR 21 22 50/51Q2.Opt_Dir 50/51Q2.En_Abnor_Blk Current setting for stage 2 of negative-sequence overcurrent protection Ratio coefficient (I2/I1) for stage 2 of negative-sequence overcurrent protection Time delay for stage 2 of negative-sequence overcurrent protection Enable stage 2 of negative-sequence overcurrent protection Enable auto-reclosing blocked when stage 2 of negative-sequence overcurrent protection operates Direction option for stage 2 of negative-sequence overcurrent protection 0.00~1.00 0.000~20.000 (s) 0 or 1 0 or 1 Non_Directional Forward Reverse Enable blocking for stage 2 of negative-sequence overcurrent protection under abnormal conditions 7-36 (0.050~30.000)×In (A) 0 or 1 PCS-902 Line Distance Relay Date: 2019-03-01 -11-23 7 Settings 23 50/51Q2.En_VTS_Blk 24 50/51Q2.En_CTS_Blk Enable blocking for stage 2 of negative-sequence overcurrent protection under VT failure conditions Enable blocking for stage 2 of negative-sequence overcurrent protection under CT failure conditions 0 or 1 0 or 1 DefTime IECN IECV IECE IECST 25 50/51Q2.Opt_Curve Option of characteristic curve for stage 2 of negative-sequence overcurrent protection IECLT ANSIE ANSIV ANSI ANSIM ANSILTE ANSILTV ANSILT 26 50/51Q2.TMS 27 50/51Q2.tmin 28 50/51Q3.I2_Set 29 50/51Q3.I2/I1_Set 30 50/51Q3.t_Op 31 50/51Q3.En 32 50/51Q3.En_BlkAR 33 50/51Q3.Opt_Dir 34 50/51Q3.En_Abnor_Blk 35 50/51Q3.En_VTS_Blk 36 50/51Q3.En_CTS_Blk Time multiplier setting for stage 2 of inverse-time negative-sequence overcurrent protection Minimum operating time for stage 2 of inverse-time negative-sequence overcurrent protection Current setting for stage 3 of negative-sequence overcurrent protection Ratio coefficient (I2/I1) for stage 3 of negative-sequence overcurrent protection Time delay for stage 3 of negative-sequence overcurrent protection Enable stage 3 of negative-sequence overcurrent protection Enable auto-reclosing blocked when stage 3 of negative-sequence overcurrent protection operates Direction option for stage 3 of negative-sequence overcurrent protection Enable blocking for stage 3 of negative-sequence overcurrent protection under abnormal conditions Enable blocking for stage 3 of negative-sequence overcurrent protection under VT failure conditions Enable blocking for stage 3 of negative-sequence overcurrent protection under CT failure conditions PCS-902 Line Distance Relay 0.010~200.000 0.050~20.000 (s) (0.050~30.000)×In (A) 0.00~1.00 0.000~20.000 (s) 0 or 1 0 or 1 Non_Directional Forward Reverse 0 or 1 0 or 1 0 or 1 7-37 Date: 2019-03-01 -09-07 7 Settings DefTime IECN IECV IECE IECST 37 50/51Q3.Opt_Curve Option of characteristic curve for stage 3 of negative-sequence overcurrent protection IECLT ANSIE ANSIV ANSI ANSIM ANSILTE ANSILTV ANSILT 38 50/51Q3.TMS 39 50/51Q3.tmin 40 50/51Q4.I2_Set 41 50/51Q4.I2/I1_Set 42 50/51Q4.t_Op 43 50/51Q4.En 44 50/51Q4.En_Trp 45 50/51Q4.En_BlkAR 46 50/51Q4.Opt_Dir 47 50/51Q4.En_Abnor_Blk 48 50/51Q4.En_VTS_Blk 49 50/51Q4.En_CTS_Blk Time multiplier setting for stage 3 of inverse-time negative-sequence overcurrent protection Minimum operating time for stage 3 of inverse-time negative-sequence overcurrent protection Current setting for stage 4 of negative-sequence overcurrent protection Ratio coefficient (I2/I1) for stage 4 of negative-sequence overcurrent protection Time delay for stage 4 of negative-sequence overcurrent protection Enable stage 4 of negative-sequence overcurrent protection Enable stage 4 of negative-sequence overcurrent protection operate to trip or alarm. Enable auto-reclosing blocked when stage 4 of negative-sequence overcurrent protection operates Direction option for stage 4 of negative-sequence overcurrent protection 0.050~20.000 (s) (0.050~30.000)×In (A) 0.00~1.00 0.000~20.000 (s) 0 or 1 0 or 1 0 or 1 Non_Directional Forward Reverse Enable blocking for stage 4 of negative-sequence overcurrent protection under abnormal conditions Enable blocking for stage 4 of negative-sequence overcurrent protection under VT failure conditions Enable blocking for stage 4 of negative-sequence overcurrent protection under CT failure conditions 7-38 0.010~200.000 0 or 1 0 or 1 0 or 1 PCS-902 Line Distance Relay Date: 2019-03-01 -11-23 7 Settings DefTime IECN IECV IECE IECST 50 50/51Q4.Opt_Curve Option of characteristic curve for stage 4 of negative-sequence overcurrent protection IECLT ANSIE ANSIV ANSI ANSIM ANSILTE ANSILTV ANSILT 51 50/51Q4.TMS 52 50/51Q4.tmin Time multiplier setting for stage 4 of inverse-time negative-sequence overcurrent protection Minimum operating time for stage 4 of inverse-time negative-sequence overcurrent protection 0.010~200.000 0.050~20.000 (s) 7.3.1.19 Overcurrent Protection Settings for VT Circuit Failure (50PVT/50GVT) No. Item 1 50PVT1.I_Set 2 50PVT1.t_Op 3 50PVT1.En 4 50PVT2.I_Set 5 50PVT2.t_Op 6 50PVT2.En Remark Current setting for stage 1 of phase overcurrent protection when VT circuit failure Time delay for stage 1 of phase overcurrent protection when VT circuit failure Enable stage 1 of phase overcurrent protection when VT circuit failure Current setting for stage 2 of phase overcurrent protection when VT circuit failure Time delay for stage 2 of phase overcurrent protection when VT circuit failure Enable stage 2 of phase overcurrent protection when VT circuit failure Range (0.050~30.000)×In (A) 0.000~10.000 (s) 0 or 1 (0.050~30.000)×In (A) 0.000~10.000 (s) 0 or 1 DefTime IECN IECV IECE Option of inverse-time characteristic curve for 7 50PVT2.Opt_Curve stage 2 of phase overcurrent protection when VT circuit failure IECST IECLT ANSIE ANSIV ANSI ANSIM ANSILTE ANSILTV PCS-902 Line Distance Relay 7-39 Date: 2019-03-01 -09-07 7 Settings ANSILT 8 50PVT2.TMS 9 50PVT2.tmin Time multiplier setting for overcurrent protection when VT circuit failure Minimum operating time for stage 2 50PVT2.Alpha of phase overcurrent protection when VT circuit failure Constant 10 stage 2 of phase “α” inverse-time for stage characteristic 2 of customized phase overcurrent 0.010~200.000 0.000~20.000 (s) 0.010~5.000 protection when VT circuit failure Constant 11 50PVT2.C “C” inverse-time for stage characteristic 2 of customized phase overcurrent 0.000~20.000 protection when VT circuit failure Constant 12 50PVT2.K “K” inverse-time for stage characteristic 2 of customized phase overcurrent 0.050~20.000 protection when VT circuit failure 13 50GVT1.3I0_Set 14 50GVT1.t_Op 15 50GVT1.En 16 50GVT2.3I0_Set 17 50GVT2.t_Op 18 50GVT2.En Current setting for stage 1 of ground overcurrent protection when VT circuit failure Time delay for stage 1 of ground overcurrent protection when VT circuit failure Enable stage 1 of ground overcurrent protection when VT circuit failure Current setting for stage 2 of ground overcurrent protection when VT circuit failure Time delay for stage 2 of ground overcurrent protection when VT circuit failure Enable stage 2 of ground overcurrent protection when VT circuit failure (0.050~30.000)×In (A) 0.000~10.000 (s) 0 or 1 (0.050~30.000)×In (A) 0.000~10.000 (s) 0 or 1 DefTime IECN IECV IECE IECST 19 50GVT2.Opt_Curve Option of inverse-time characteristic curve for IECLT stage 2 of ground overcurrent protection when VT ANSIE circuit failure ANSIV ANSI ANSIM ANSILTE ANSILTV ANSILT 20 50GVT2.TMS 21 50GVT2.tmin 22 50GVT2.Alpha Time multiplier setting for stage 2 of ground overcurrent protection when VT circuit failure Minimum operating time for stage 2 of ground overcurrent protection when VT circuit failure Constant “α” for stage 2 7-40 of customized 0.010~200.000 0.000~20.000 (s) 0.010~5.000 PCS-902 Line Distance Relay Date: 2019-03-01 -11-23 7 Settings inverse-time characteristic ground overcurrent protection when VT circuit failure Constant 23 50GVT2.C “C” for stage 2 of customized inverse-time characteristic ground overcurrent 0.000~20.000 protection when VT circuit failure Constant 24 50GVT2.K “K” for stage 2 of customized inverse-time characteristic ground overcurrent 0.050~20.000 protection when VT circuit failure 7.3.1.20 Phase Current SOTF Protection Settings (50PSOTF) No. Item Remark Range 1 50PSOTF.I_Set Current setting of phase current SOTF protection (0.050~30.000)×In (A) 2 50PSOTF.t_Op Time delay for phase current SOTF protection 0.000~10.000 (s) 3 50PSOTF.En Enable phase current SOTF protection 0 or 1 4 50PSOTF.En_Hm2_Blk 5 50PSOTF.Up_Set 6 50PSOTF.Upp_Set 7 50PSOTF.U2_Set 8 50PSOTF.3U0_Set 9 50PSOTF.En_Up_UV 10 50PSOTF.En_Upp_UV 11 50PSOTF.En_U2_OV 12 50PSOTF.En_3U0_OV Enable second harmonic blocking for phase overcurrent SOTF protection Voltage setting for phase undervoltage supervision logic Voltage setting for phase-phase undervoltage supervision logic Voltage setting for negative-sequence overvoltage supervision logic Voltage setting for zero-sequence overvoltage supervision logic Enable phase undervoltage supervision logic for phase current SOTF protection Enable phase-phase undervoltage supervision logic for phase current SOTF protection Enable negative-sequence overvoltage supervision logic for phase current SOTF protection Enable zero-sequence overvoltage supervision logic for phase current SOTF protection 0 or 1 (0~1) ×Un (V) (0~1) ×Un (V) (0~1) ×Un (V) (0~1) ×Un (V) 0 or 1 0 or 1 0 or 1 0 or 1 7.3.1.21 Residual Current SOTF Protection Settings (50GSOTF) No. Item 1 50GSOTF.3I0_Set 2 50GSOTF.t_Op_3P 3 50GSOTF.t_Op_1P 4 50GSOTF.En 5 50GSOTF.En_Hm2_Blk Remark Current setting of residual current SOTF protection Time delay for residual current SOTF protection when 3 pole closed Time delay for residual current SOTF protection when 1 pole closed Enable residual current SOTF protection Enable residual current SOTF protection blocked by harmonic PCS-902 Line Distance Relay Range (0.050~30.000)×In (A) 0.000~10.000 (s) 0.000~10.000 (s) 0 or 1 0 or 1 7-41 Date: 2019-03-01 -09-07 7 Settings 7.3.1.22 Overvoltage Protection Settings (59P) No. Item Remark Range 1 59P1.U_Set Voltage setting for stage 1 of overvoltage protection Un~2Unn (V) 2 59P1.t_Op Time delay for stage 1 of overvoltage protection 0.000~30.000 (s) 3 59P1.En Enable stage 1 of overvoltage protection 0 or 1 4 59P1.Opt_1P/3P 5 59P1.Opt_Up/Upp 6 59P1.En_Alm 7 59P1.En_52b_TT 8 59P1.En_TT Option of 1-out-of-3 mode or 3-out-of-3 mode for stage 1 of overvoltage protection Option of phase-to-phase voltage or phase voltage for stage 1 of overvoltage protection Enable stage 1 of overvoltage protection for alarm purpose Enable transfer trip controlled by CB open position for stage 1 of overvoltage protection Enable stage 1 of overvoltage protection operate to initiate transfer trip 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 DefTime IECN IECV IECE IECST 9 59P1.Opt_Curve Option of characteristic curve for stage 1 of overvoltage protection IECLT ANSIE ANSIV ANSI ANSIM ANSILTE ANSILTV ANSILT Time multiplier setting for stage 1 of inverse-time 10 59P1.TMS 11 59P1.tmin 12 59P2.U_Set Voltage setting for stage 2 of overvoltage protection Un~2Unn (V) 13 59P2.t_Op Time delay for stage 2 of overvoltage protection 0.000~30.000 (s) 14 59P2.En Enable stage x of overvoltage protection 0 or 1 15 59P2.Opt_1P/3P 16 59P2.Opt_Up/Upp 17 59P2.En_Alm overvoltage protection Minimum delay for stage 1 of inverse-time overvoltage protection Option of 1-out-of-3 mode or 3-out-of-3 mode for stage 2 of overvoltage protection Option of phase-to-phase voltage or phase voltage for stage 2 of overvoltage protection Enable stage 2 of overvoltage protection for alarm purpose 7-42 0.010~200.000 0.050~20.000 (s) 0 or 1 0 or 1 0 or 1 PCS-902 Line Distance Relay Date: 2019-03-01 -11-23 7 Settings 18 59P2.En_52b_TT 19 59P2.En_TT Enable transfer trip controlled by CB open position for stage 2 of overvoltage protection Enable stage 2 of overvoltage protection operate to initiate transfer trip 0 or 1 0 or 1 DefTime IECN IECV IECE IECST 20 59P2.Opt_Curve Option of characteristic curve for stage 2 of overvoltage protection IECLT ANSIE ANSIV ANSI ANSIM ANSILTE ANSILTV ANSILT Time multiplier setting for stage 2 of inverse-time 21 59P2.TMS 22 59P2.tmin 23 59P3.U_Set Voltage setting for stage 3 of overvoltage protection Un~2Unn (V) 24 59P3.t_Op Time delay for stage 3 of overvoltage protection 0.000~30.000 (s) 25 59P3.En Enable stage 3 of overvoltage protection 0 or 1 26 59P3.Opt_1P/3P 27 59P3.Opt_Up/Upp 28 59Px.En_Alm 29 59P3.En_52b_TT 30 59P3.En_TT overvoltage protection Minimum delay for stage 2 of inverse-time overvoltage protection Option of 1-out-of-3 mode or 3-out-of-3 mode for stage 3 of overvoltage protection Option of phase-to-phase voltage or phase voltage for stage 3 of overvoltage protection Enable stage 3 of overvoltage protection for alarm purpose Enable transfer trip controlled by CB open position for stage 3 of overvoltage protection Enable stage 3 of overvoltage protection operate to initiate transfer trip PCS-902 Line Distance Relay 0.010~200.000 0.050~20.000 (s) 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 7-43 Date: 2019-03-01 -09-07 7 Settings DefTime IECN IECV IECE IECST 31 59P3.Opt_Curve Option of characteristic curve for stage 3 of overvoltage protection IECLT ANSIE ANSIV ANSI ANSIM ANSILTE ANSILTV ANSILT 32 59P3.TMS 33 59P3.tmin Time multiplier setting for stage 3 of inverse-time overvoltage protection Minimum delay for stage 3 of inverse-time overvoltage protection 0.010~200.000 0.050~20.000 (s) 7.3.1.23 Negative-sequence Overvoltage Protection Settings (59Q) No. Item 1 59Q.U_Set 2 59Q.t_Op 3 59Q.En Remark Range Voltage setting for negative-sequence overvoltage protection Time delay for negative-sequence overvoltage protection Enable negative-sequence overvoltage protection 0~Un (V) 0.000~30.000 (s) 0 or 1 7.3.1.24 Residual Overvoltage Protection Settings (59G) No. Item 1 59G1.3U0_Set 2 59G1.t_Op 3 59G1.En 4 59G2.3U0_Set 5 59G2.t_Op 6 59G2.En Remark Range Voltage setting of stage 1 of residual overvoltage protection. Time delay of stage 1 of residual overvoltage protection. Enable stage 1 of residual overvoltage protection. Voltage setting of stage 2 of residual overvoltage protection. Time delay of stage 2 of residual overvoltage protection. Enable stage 2 of residual overvoltage protection. 7-44 0~2Unn (V) 0.000~3600.000 (s) 0 or 1 0~2Unn (V) 0.000~3600.000 (s) 0 or 1 PCS-902 Line Distance Relay Date: 2019-03-01 -11-23 7 Settings DefTime IECN IECV IECE IECST IECLT 7 59G2.Opt_Curve Option of characteristic curve for stage 2 of residual ANSIE overvoltage protection ANSIV ANSI ANSIM ANSILTE ANSILTV ANSILT UserDefine 8 59G2.TMS 9 59G2.tmin 10 59G2.Alpha 11 59G2.C 12 59G2.K 13 59G3.3U0_Set 14 59G3.t_Op 15 59G3.En 16 59G3.En_Trp Time multiplier setting for stage 2 of residual overvoltage protection Minimum operating time for stage 2 of residual overvoltage protection Constant “α” for stage 2 of customized inverse-time characteristic residual overvoltage protection Constant “C” for stage 2 of customized inverse-time characteristic residual overvoltage protection Constant “K” for stage 2 of customized inverse-time characteristic residual overvoltage protection Voltage setting of stage 3 of residual overvoltage protection. Time delay of stage 3 of residual overvoltage protection. Enable stage 3 of residual overvoltage protection. Enable stage 3 of residual overvoltage protection for trip purpose. PCS-902 Line Distance Relay 0.050~3.200 0.000~20.000 (s) 0.020~5.000 0.000~20.000 0.000~120.000 0~2Unn (V) 0.000~3600.000 (s) 0 or 1 0 or 1 7-45 Date: 2019-03-01 -09-07 7 Settings DefTime IECN IECV IECE IECST IECLT 17 59G3.Opt_Curve Option of characteristic curve for stage 3 of residual ANSIE overvoltage protection ANSIV ANSI ANSIM ANSILTE ANSILTV ANSILT UserDefine 18 59G3.TMS 19 59G3.tmin 20 59G3.Alpha 21 59G3.C 22 59G3.K Time multiplier setting for stage 3 of residual overvoltage protection Minimum operating time for stage 3 of residual overvoltage protection Constant “α” for stage 3 of customized inverse-time characteristic residual overvoltage protection Constant “C” for stage 3 of customized inverse-time characteristic residual overvoltage protection Constant “K” for stage 3 of customized inverse-time characteristic residual overvoltage protection 0.050~3.200 0.000~20.000 (s) 0.020~5.000 0.000~20.000 0.000~120.000 7.3.1.25 Undervoltage Protection Settings (27P) No. Item Remark Range 1 27P1.U_Set Voltage setting for stage 1 of undervoltage protection 0~Unn (V) 2 27P1.t_Op Time delay for stage 1 of undervoltage protection 0.000~30.000 (s) 3 27P1.En Enable stage 1 of undervoltage protection 0 or 1 4 27P1.En_FD_Ctrl 5 27P1.En_Curr_Ctrl 6 27P1.En_VTS_Blk 7 27P1.Opt_1P/3P Enable stage 1 of undervoltage protection controlled by FD element reflecting current Enable stage 1 of undervoltage protection controlled by current condition Enable stage 1 of undervoltage protection controlled by VT circuit failure Option of 1-out-of-3 mode or 3-out-of-3 mode for stage 1 of undervoltage protection 0 or 1 0 or 1 0 or 1 0 or 1 Option of voltage criterion adopting phase-to-phase 8 27P1.Opt_Up/Upp voltage or phase voltage for stage 1 of undervoltage 0 or 1 protection 9 27P1.En_Alm Enable stage 1 of undervoltage protection operate to alarm 7-46 0 or 1 PCS-902 Line Distance Relay Date: 2019-03-01 -11-23 7 Settings DefTime IECN IECV IECE IECST 10 27P1.Opt_Curve Option of characteristic curve for stage 1 of undervoltage protection IECLT ANSIE ANSIV ANSI ANSIM ANSILTE ANSILTV ANSILT Time multiplier setting for stage 1 of inverse-time 11 27P1.TMS 12 27P1.tmin 13 27P2.U_Set Voltage setting for stage 2 of undervoltage protection 0~Unn (V) 14 27P2.t_Op Time delay for stage 2 of undervoltage protection 0.000~30.000 (s) 15 27P2.En Enable stage 2 of undervoltage protection 0 or 1 16 27P2.En_FD_Ctrl 17 27P2.En_Curr_Ctrl 18 27P2.En_VTS_Blk 19 27P2.Opt_1P/3P undervoltage protection Minimum delay for stage 1 of inverse-time undervoltage protection Enable stage 2 of undervoltage protection controlled by FD element reflecting current Enable stage 2 of undervoltage protection controlled by current condition Enable stage 2 of undervoltage protection controlled by VT circuit failure Option of 1-out-of-3 mode or 3-out-of-3 mode for stage 2 of undervoltage protection 0.010~200.000 0.050~20.000 (s) 0 or 1 0 or 1 0 or 1 0 or 1 Option of voltage criterion adopting phase-to-phase 20 27P2.Opt_Up/Upp voltage or phase voltage for stage 2 of undervoltage 0 or 1 protection 21 27P2.En_Alm Enable stage 2 of undervoltage protection operate to alarm PCS-902 Line Distance Relay 0 or 1 7-47 Date: 2019-03-01 -09-07 7 Settings DefTime IECN IECV IECE IECST 22 27P2.Opt_Curve Option of characteristic curve for stage 2 of undervoltage protection IECLT ANSIE ANSIV ANSI ANSIM ANSILTE ANSILTV ANSILT Time multiplier setting for stage 2 of inverse-time 23 27P2.TMS 24 27P2.tmin 25 27P3.U_Set Voltage setting for stage 3 of undervoltage protection 0~Unn (V) 26 27P3.t_Op Time delay for stage 3 of undervoltage protection 0.000~30.000 (s) 27 27P3.En Enable stage 3 of undervoltage protection 0 or 1 28 27P3.En_FD_Ctrl 29 27P3.En_Curr_Ctrl 30 27P3.En_VTS_Blk 31 27P3.Opt_1P/3P undervoltage protection Minimum delay for stage 2 of inverse-time undervoltage protection Enable stage 3 of undervoltage protection controlled by FD element reflecting current Enable stage 3 of undervoltage protection controlled by current condition Enable stage 3 of undervoltage protection controlled by VT circuit failure Option of 1-out-of-3 mode or 3-out-of-3 mode for stage 3 of undervoltage protection 0.010~200.000 0.050~20.000 (s) 0 or 1 0 or 1 0 or 1 0 or 1 Option of voltage criterion adopting phase-to-phase 32 27P3.Opt_Up/Upp voltage or phase voltage for stage 3 of undervoltage 0 or 1 protection 33 27P3.En_Alm Enable stage 3 of undervoltage protection operate to alarm 7-48 0 or 1 PCS-902 Line Distance Relay Date: 2019-03-01 -11-23 7 Settings DefTime IECN IECV IECE IECST 34 27P3.Opt_Curve Option of characteristic curve for stage 3 of undervoltage protection IECLT ANSIE ANSIV ANSI ANSIM ANSILTE ANSILTV ANSILT 35 27P3.TMS 36 27P3.tmin Time multiplier setting for stage 3 of inverse-time undervoltage protection Minimum delay for stage 3 of inverse-time undervoltage protection 0.010~200.000 0.050~20.000 (s) 7.3.1.26 Frequency Protection Settings (81O and 81U) No. Item Remark Range 1 81O.f_Pkp Frequency pickup setting for overfrequency protection 50.000~65.000 (Hz) 2 81O.OF1.f_Set 3 81O.OF1.t_Op Time delay for stage 1 of overfrequency protection 0.000~20.000 (s) 4 81O.OF1.En Enable stage 1 of overfrequency protection 0 or 1 5 81O.OF2.f_Set 6 81O.OF2.t_Op Time delay for stage 2 of overfrequency protection 0.000~20.000 (s) 7 81O.OF2.En Enable stage 2 of overfrequency protection 0 or 1 8 81O.OF3.f_Set 9 81O.OF3.t_Op Time delay for stage 3 of overfrequency protection 0.000~20.000 (s) 10 81O.OF3.En Enable stage 3 of overfrequency protection 0 or 1 11 81O.OF4.f_Set 12 81O.OF4.t_Op Time delay for stage 4 of overfrequency protection 0.000~20.000 (s) 13 81O.OF4.En Enable stage 4 of overfrequency protection 0 or 1 14 81U.f_Pkp 15 81U.df/dt_Blk 16 81U.UF1.f_Set Frequency setting for stage 1 of overfrequency protection Frequency setting for stage 2 of overfrequency protection Frequency setting for stage 3 of overfrequency protection Frequency setting for stage 4 of overfrequency protection Frequency pickup setting for underfrequency protection Rate of frequency change for blocking underfrequency protection Frequency setting for stage 1 of underfrequency protection PCS-902 Line Distance Relay 50.000~65.000 (Hz) 50.000~65.000 (Hz) 50.000~65.000 (Hz) 50.000~65.000 (Hz) 45.000~60.000 (Hz) 0.200~20.000 (Hz/s) 45.000~60.000 (Hz) 7-49 Date: 2019-03-01 -09-07 7 Settings 17 81U.UF1.t_Op Time delay for stage 1 of underfrequency protection 0.000~30.000 (s) 18 81U.UF1.En Enable stage 1 of underfrequency protection 0 or 1 19 81U.UF1.En_df/dt_Blk 20 81U.UF2.f_Set 21 81U.UF2.t_Op Time delay for stage 2 of underfrequency protection 0.000~30.000 (s) 22 81U.UF2.En Enable stage 2 of underfrequency protection 0 or 1 23 81U.UF2.En_df/dt_Blk 24 81U.UF3.f_Set 25 81U.UF3.t_Op Time delay for stage 3 of underfrequency protection 0.000~30.000 (s) 26 81U.UF3.En Enable stage 3 of underfrequency protection 0 or 1 27 81U.UF3.En_df/dt_Blk 28 81U.UF4.f_Set 29 81U.UF4.t_Op Time delay for stage 4 of underfrequency protection 0.000~30.000 (s) 30 81U.UF4.En Enable stage 4 of underfrequency protection 0 or 1 31 81U.UF4.En_df/dt_Blk Enable rate of frequency change to block stage 1 of underfrequency protection Frequency setting for stage 2 of underfrequency protection Enable rate of frequency change to block stage 2 of underfrequency protection Frequency setting for stage 3 of underfrequency protection Enable rate of frequency change to block stage 3 of underfrequency protection Frequency setting for stage 4 of underfrequency protection Enable rate of frequency change to block stage 4 of underfrequency protection 0 or 1 45.000~60.000 (Hz) 0 or 1 45.000~60.000 (Hz) 0 or 1 45.000~60.000 (Hz) 0 or 1 7.3.1.27 Breaker Failure Protection Settings (50BF) NOTICE! PCS-902 can be configured to support single circuit breaker application or double circuit breakers application by PCS-Explorer. The prefix “CBx.” is added to all settings for circuit breaker No.x (x=1 or 2). No. Item Remark Range 1 CBx.50BF.I_Set Current setting of phase current criterion for BFP 2 CBx.50BF.3I0_Set Current setting of zero-sequence current criterion (0.050~30.000 )×In (A) for BFP 3 CBx.50BF.I2_Set Current setting of negative-sequence current (0.050~30.000 )×In (A) criterion for BFP 4 CBx.50BF.t_ReTrp Time delay of re-tripping for BFP 0.000~10.000 (s) 5 CBx.50BF.t1_Op Time delay of stage 1 for BFP 0.000~10.000 (s) 6 CBx.50BF.t2_Op Time delay of stage 2 for BFP 0.000~10.000 (s) 7 CBx.50BF.En Enable breaker failure protection 0 or 1 8 CBx.50BF.En_ReTrp Enable re-trip function for BFP 0 or 1 9 CBx.50BF.En_3I0_1P Enable zero-sequence current criterion for BFP 0 or 1 initiated by single-phase tripping contact 7-50 (0.050~30.000 )×In (A) PCS-902 Line Distance Relay Date: 2019-03-01 -11-23 7 Settings 10 CBx.50BF.En_3I0_3P 11 CBx.50BF.En_I2_3P 12 CBx.50BF.En_CB_Ctrl Enable zero-sequence current criterion for BFP 0 or 1 initiated by three-phase tripping contact Enable negative-sequence current criterion for BFP 0 or 1 initiated by three-phase tripping contact Enable breaker failure protection can be initiated by 0 or 1 normally closed contact of circuit breaker 7.3.1.28 Thermal Overload Protection Settings (49) No. Item Remark Range 49-1.K The factor setting for stage 1 of thermal overload protection which is associated to the thermal state 1.000~3.000 formula 2 49-2.K The factor setting for stage 2 of thermal overload protection which is associated to the thermal state 1.000~3.000 formula 3 49.Ib_Set 4 49.Tau 5 49-1.En_Alm 6 49-1.En_Trp 7 49-2.En_Alm 8 49-2.En_Trp 1 The reference current setting of the thermal (0.050~30.000 )×In (A) overload protection The time constant setting of the IDMT overload 0.100~100.000 (min) protection Enable stage 1 of thermal overload protection for 0 or 1 alarm purpose Enable stage 1 of thermal overload protection for 0 or 1 trip purpose Enable stage 2 of thermal overload protection for 0 or 1 alarm purpose Enable stage 2 of thermal overload protection for 0 or 1 trip purpose 7.3.1.29 Stub Differential Protection Settings (87STB) No. Name Remark Range 1 87STB.I_Pkp Pickup current setting of stub differential protection (0.050~30.000)×In (A) 2 87STB.I_ Alm Current setting of differential current alarm (0.050~30.000)×In (A) 3 87STB.Slope Slope of current differential protection 0.5~1 4 87STB.t_Op Time delay of stub differential protection 0.000~10.000 (s) 5 87STB.En Enable stub differential protection 0 or 1 6 87STB.En_Alm Enable differential current alarm function 0 or 1 7 87STB.En_CTS_Blk Enable stub differential protection controlled by CT circuit failure 0 or 1 7.3.1.30 Dead Zone Protection Settings (50DZ) NOTICE! PCS-902 can be configured to support single circuit breaker application or double circuit breakers application by PCS-Explorer. The prefix “CBx.” is added to all settings for circuit breaker No.x (x=1 or 2). No. 1 Name CBx.50DZ.I_Set Remark Current setting of dead zone protection PCS-902 Line Distance Relay Range (0.050~30.000)×In (A) 7-51 Date: 2019-03-01 -09-07 7 Settings 2 CBx.50DZ.t_Op Time delay of dead zone protection 0.000~10.000 (s) 3 CBx.50DZ.En Enable dead zone protection 0 or 1 7.3.1.31 Pole Discrepancy Protection Settings (62PD) NOTICE! PCS-902 can be configured to support single circuit breaker application or double circuit breakers application by PCS-Explorer. The prefix “CBx.” is added to all settings for circuit breaker No.x (x=1 or 2). No. Item Remark Range 1 CBx.62PD.3I0_Set Current setting of residual current criterion for (0.050~30.000 )×In (A) pole discrepancy protection 2 CBx.62PD.I2_Set Current setting of negative-sequence current (0.050~30.000 )×In (A) criterion for pole discrepancy protection 3 CBx.62PD.t_Op Time delay of pole discrepancy protection 0.000~600.000 (s) 4 CBx.62PD.En Enable pole discrepancy protection 0 or 1 5 CBx.62PD.En_3I0/I2_Ctrl Enable residual current criterion and negative-sequence current criterion for pole 0 or 1 discrepancy protection 7.3.1.32 Broken Conductor Protection Settings (46BC) No. Item Remark Range 1 46BC.I2/I1_Set Ratio setting (negative-sequence current to positive-sequence current) of broken conductor 0.20~1.00 protection 2 46BC.t_Op Time delay of broken conductor protection 3 46BC.I_Min Minimum operation current of broken conductor (0.050~30.000)×In (A) protection 4 46BC.En_Trp Enable broken conductor protection to operate to 0 or 1 trip 5 46BC.En_Alm Enable broken conductor protection to operate to 0 or 1 alarm 0.000~600.000 (s) 7.3.1.33 Reverse Power Protection Settings (32R) No. Item Remark Range Power setting of stage 1 of reverse power 1 32R1.P_Set 2 32R1.t_Trp 3 32R1.t_Alm 4 32R1.En_Trp 5 32R1.En_Alm (0.100~50.000)×In (W) protection Time delay of stage 1 of reverse power protection 0.100~3000.000 (s) for tripping purpose Time delay of stage 1 of reverse power protection 0.100~3000.000 (s) for alarm purpose Enable stage 1 of reverse power protection to 0 or 1 operate to trip Enable stage 1 of reverse power protection to operate to alarm 7-52 0 or 1 PCS-902 Line Distance Relay Date: 2019-03-01 -11-23 7 Settings Power setting of stage 2 of reverse power 6 32R2.P_Set 7 32R2.t_Trp 8 32R2.En_Trp 9 32R.Opt_Dir (0.100~50.000)×In (W) protection Time delay of stage 2 of reverse power protection 0.100~3000.000 (s) Enable stage 2 of reverse power protection to 0 or 1 operate to trip The directionality option of protection reverse power Forward direction Reverse direction 7.3.1.34 Synchrocheck Settings (25) NOTICE! PCS-902 can be configured to support single circuit breaker application or double circuit breakers application by PCS-Explorer. The prefix “CBx.” is added to all settings for circuit breaker No.x (x=1 or 2). No. Item Remark Range Ua Ub 1 CBx.25.Opt_Source_UL1 Voltage selecting mode of line 1. Uc Uab Ubc Uca Ua Ub 2 CBx.25.Opt_Source_UB1 Voltage selecting mode of bus 1. Uc Uab Ubc Uca Ua Ub 3 CBx.25.Opt_Source_UL2 Voltage selecting mode of line 2. Uc Uab Ubc Uca Ua Ub 4 CBx.25.Opt_Source_UB2 Voltage selecting mode of bus 2. Uc Uab Ubc Uca PCS-902 Line Distance Relay 7-53 Date: 2019-03-01 -09-07 7 Settings NoVoltSel Option of circuit breaker configuration, and it 5 CBx.CBConfigMode should be set as “NoVoltSel” if no voltage selection DblBusOneCB 3/2BusCB is adopted. 3/2TieCB 6 CBx.25.U_Dd Voltage threshold of dead check 0.05Un~0.8Un (V) 7 CBx.25.U_Lv Voltage threshold of live check 0.5Un~Un (V) 8 CBx.25.K_Usyn Compensation coefficient for synchronism voltage 0.20-5.00 9 CBx.25.phi_Diff Phase difference limit of synchronism check for AR Compensation for phase difference between two 0~ 89 (deg) 10 CBx.25.phi_Comp 11 CBx.25.f_Diff 12 CBx.25.U_Diff 13 CBx.25.t_DdChk 14 CBx.25.t_SynChk 15 CBx.25.En_fDiffChk Enable frequency difference check 0 or 1 16 CBx.25.SetOpt Synchrocheck mode selection 0, 1 17 CBx.25.En_SynChk Enable synchronism check 0 or 1 18 CBx.25.En_DdL_DdB Enable dead line and dead bus (DLDB) check 0 or 1 19 CBx.25.En_DdL_LvB Enable dead line and live bus (DLLB) check 0 or 1 20 CBx.25.En_LvL_DdB Enable live line and dead bus (LLDB) check 0 or 1 21 CBx.25.En_NoChk Enable AR without any check 0 or 1 22 CBx.25.En_3PLvChk Enable live three-phase check of line 0 or 1 synchronism voltages Frequency difference limit of synchronism check for AR Voltage difference limit of synchronism check for AR Time delay to confirm dead check condition Time delay to confirm synchronism 0~359 (deg) 0.02~1.00 (Hz) 0.02Un~0.8Un (V) 0.010~25.000 (s) check condition 0.010~25.000 (s) 7.3.1.35 Auto-reclosing Settings (79) NOTICE! PCS-902 can be configured to support single circuit breaker application or double circuit breakers application by PCS-Explorer. The prefix “CBx.” is added to all settings for circuit breaker No.x (x=1 or 2). No. Item Remark Range 1 CBx.79.N_Rcls Maximum number of reclosing attempts 1~4 2 CBx.79.t_Dd_1PS1 Dead time of first shot 1-pole reclosing 0.000~600.000 (s) 3 CBx.79.t_Dd_3PS1 Dead time of first shot 3-pole reclosing 0.000~600.000 (s) 4 CBx.79.t_Dd_3PS2 Dead time of second shot 3-pole reclosing 0.000~600.000 (s) 5 CBx.79.t_Dd_3PS3 Dead time of third shot 3-pole reclosing 0.000~600.000 (s) 6 CBx.79.t_Dd_3PS4 Dead time of fourth shot 3-pole reclosing 0.000~600.000 (s) 7-54 PCS-902 Line Distance Relay Date: 2019-03-01 -11-23 7 Settings 7 CBx.79.t_CBClsd Time delay of circuit breaker in closed position before reclosing 0.000~600.000 (s) Time delay to wait for CB healthy, and begin to 8 CBx.79.t_CBReady timing when the input signal [79.CB_Healthy] is de-energized and if it is not energized within this 0.000~600.000 (s) time delay, AR will be blocked. 9 CBx.79.t_Wait_Chk Maximum wait time for synchronism check Time delay allow for CB status change to conform 0.000~600.000 (s) 10 CBx.79.t_Fail 11 CBx.79.t_PW_AR Pulse width of AR closing signal 0.000~600.000 (s) 12 CBx.79.t_Reclaim Reclaim time of AR 0.000~600.000 (s) 13 CBx.79.t_PersistTrp reclosing successful Time delay of excessive trip signal to block auto-reclosing 0.000~600.000 (s) 0.000~600.000 (s) Drop-off time delay of blocking AR, when blocking 14 CBx.79.t_DDO_BlkAR signal for AR disappears, AR blocking condition 0.000~600.000 (s) drops off after this time delay 15 CBx.79.t_AddDly 16 CBx.79.t_WaitMaster Additional time delay for auto-reclosing Maximum wait time for reclosing permissive signal from master AR 0.000~600.000 (s) 0.000~600.000 (s) Time delay of discriminating another fault, and begin to times after 1-pole AR initiated, 3-pole AR will be 17 CBx.79.t_SecFault initiated if another fault happens during this time 0.000~600.000 (s) delay. AR will be blocked if another fault happens after that. Enable auto-reclosing blocked when a fault occurs 18 CBx.79.En_PDF_Blk 19 CBx.79.En_AddDly 20 CBx.79.En_CutPulse 21 CBx.79.En_FailCheck 22 CBx.79.En 23 CBx.79.En_ExtCtrl 24 CBx.79.En_CBInit 25 CBx.79.Opt_Priority Option of AR priority None, High or Low 26 CBx.79.SetOpt Control option of AR mode 0 or 1 27 CBx.79.En_1PAR Enable 1-pole AR mode 0 or 1 28 CBx.79.En_3PAR Enable 3-pole AR mode 0 or 1 29 CBx.79.En_1P/3PAR Enable 1/3-pole AR mode 0 or 1 under pole disagreement condition Enable auto-reclosing with an additional dead time delay Enable adjust the length of reclosing pulse Enable confirm whether AR is successful by checking CB state Enable auto-reclosing Enable AR by external input signal besides logic setting [79.En] Enable AR be initiated by open state of circuit breaker PCS-902 Line Distance Relay 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 7-55 Date: 2019-03-01 -09-07 7 Settings 7.3.1.36 Transfer Trip Settings (TT) No. Item Remark Range 1 TT.t_Op Time delay of transfer trip 0.000~600.000 (s) 2 TT.En_FD_Ctrl Enable transfer trip controlled by local fault detector 0 or 1 3 TT.En_BlkAR Enable transfer trip operate to block AR 0 or 1 7.3.1.37 Tripping Logic Settings NOTICE! PCS-902 can be configured to support single circuit breaker application or double circuit breakers application by PCS-Explorer. The prefix “CBx.” is added to all settings for circuit breaker No.x (x=1 or 2). No. Item 1 En_MPF_Blk_AR 2 En_3PF_Blk_AR 3 En_PhSF_Blk_AR 4 t_Dwell_Trp 5 CBx.En_Trp3P Remark Range Enable auto-reclosing blocked when multi-phase fault happens Enable auto-reclosing blocked when three-phase fault happens Enable auto-reclosing blocked when selection of faulty phase fails The dwell time of tripping command, empirical value is 0.04 Enable three-phase tripping mode for any fault conditions 0 or 1 0 or 1 0 or 1 0.000~10.000 (s) 0 or 1 7.3.1.38 VT Circuit Supervision Settings (VTS) No. Item Remark Range 1 VTS.3U0_Set Zero-sequence voltage setting of VT circuit supervison 2 VTS.U1_Set 3 VTNS.3U0_Hm3_Set 4 VTS.t_DPU Pickup time delay of VT circuit supervision 0.200~100.000 (s) 5 VTS.t_DDO Dropoff time delay of VT circuit supervision 0.200~100.000 (S) 6 VTS.En_Out_VT VT is not connected to the protection device 0 or 1 Positive-sequence voltage setting of VT circuit supervison Third harmonic setting of zero-sequence voltage of VT circuit supervision 0.000~220.000 (V) 22.000~110.000 (V) 0.000~220.000 (V) If three-phase voltage used for protection measurement 7 VTS.En_LineVT comes from line side (for example, 3/2 breaker), it should be set as “1”. If three-phase voltage comes from 0 or 1 busbar side, it should be set as “0”. 8 VTS.En Enable alarm function of VT circuit supervision 0 or 1 7.3.2 Access Path MainMenu“Settings”“Prot Settings” 7-56 PCS-902 Line Distance Relay Date: 2019-03-01 -11-23 7 Settings 7.4 Logic Link Settings The logic link settings are used to determine whether the relevant function of this device is enabled or disabled. If this device supports the logic link function, it will have a corresponding submenu in the submenu “Logic Links” for the logic link settings. Each logic link settings is an “AND” condition of enabling the relevant function with the corresponding binary input and logic setting. Through SAS or RTU, logic link settings can be set as “1” or “0”; and it means that the relevant function can be in service or out of service through remote command. It provides convenience for operation management. 7.4.1 Setting Description 7.4.1.1 Function Link Settings The function link settings can be defined according to project specification through the configuration tool, PCS-Explorer. No. Item Remark Range 1 Link_01 Function link setting 01 0 or 1 2 Link_02 Function link setting 02 0 or 1 3 Link_03 Function link setting 03 0 or 1 4 Link_04 Function link setting 04 0 or 1 5 Link_05 Function link setting 05 0 or 1 6 Link_06 Function link setting 06 0 or 1 7 Link_07 Function link setting 07 0 or 1 8 Link_08 Function link setting 08 0 or 1 7.4.2 Access Path MainMenu“Settings”“Logic Links” 7.5 Control and Synchrocheck for Manual Closing Settings NOTICE! PCS-902 can be configured to support single circuit breaker application or double circuit breakers application by PCS-Explorer. The prefix “CBx.” is added to all settings for circuit breaker No.x (x=1 or 2). 7.5.1 Setting Description 7.5.1.1 Function Settings No. 1 Item MCBrd.CBx.En_Alm_VTS Remark Enable alarm function when VT circuit is abnormal PCS-902 Line Distance Relay Range 0 or 1 7-57 Date: 2019-03-01 -09-07 7 Settings 7.5.1.2 Synchronism Settings No. Item Remark Range Ua Ub 1 MCBrd.CBx.25.Opt_Source_UL1 Uc Voltage selecting mode for line 1 Uab Ubc Uca Ua Ub 2 MCBrd.CBx.25.Opt_Source_UB1 Uc Voltage selecting mode for bus 1 Uab Ubc Uca Ua Ub 3 MCBrd.CBx.25.Opt_Source_UL2 Uc Voltage selecting mode for line 2 Uab Ubc Uca Ua Ub 4 MCBrd.CBx.25.Opt_Source_UB2 Uc Voltage selecting mode for bus 2 Uab Ubc Uca 5 MCBrd.CBx.25.U_Dd Voltage threshold of dead check 1.000~100.000 (V) 6 MCBrd.CBx.25.U_Lv Voltage threshold of live check 1.000~100.000 (V) 7 MCBrd.CBx.25.K_Usyn 8 MCBrd.CBx.25.phi_Diff 9 MCBrd.CBx.25.phi_Comp 10 MCBrd.CBx.25.f_Diff 11 MCBrd.CBx.25.U_Diff 12 MCBrd.CBx.25.SetOpt 13 MCBrd.CBx.25.En_SynChk 14 MCBrd.CBx.25.En_DdL_DdB Compensation coefficient for synchronism voltage Phase difference limit of synchronism check for manual closing Compensation for phase difference between two synchronous voltages Frequency difference limit of synchronism check for manual closing Voltage difference limit of synchronism check for manual closing Synchrocheck mode selection for manual closing Enable synchronism check 7-58 0.10~ 180.00 (deg) 0~360 (deg) 0.00~3.00 (Hz) 1.000~100.000 (V) 0, 1 0 or 1 Enable dead line and dead bus (DLDB) check 0.20-5.00 0 or 1 PCS-902 Line Distance Relay Date: 2019-03-01 -11-23 7 Settings 15 MCBrd.CBx.25.En_DdL_LvB 16 MCBrd.CBx.25.En_LvL_DdB 17 MCBrd.CBx.25.En_NoChk Enable dead line and live bus (DLLB) check Enable live line and dead bus (LLDB) check 0 or 1 0 or 1 Enable manual closing without any check 0 or 1 Threshold of rate of frequency change 18 MCBrd.CBx.25.df/dt between both sides of CB for 0.10~5.00 (Hz/s) synchronism-check. 19 MCBrd.CBx.25.En_df/dtChk Enable frequency slip check for manual closing 0 or 1 Circuit breaker closing time. It is the time 20 MCBrd.CBx.25.t_Close_CB from receiving closing command pulse till 0~1000 (ms) the CB is completely closed. From receiving a closing command, this device will continuously check whether between incoming voltage and reference voltage involved in synchronism check 21 MCBrd.CBx.25.t_Wait_Chk (or dead check) can meet the criteria. If the synchronism check (or dead check) 5.000~30.000 (s) criteria are not met within the duration of this time delay, the failure of synchronism-check (or dead check) will be confirmed. Enable block synchronism check for 22 MCBrd.CBx.25.En_VTS_Blk_SynChk manual closing when VT circuit is 0 or 1 abnormal 23 MCBrd.CBx.25.En_VTS_Blk_DdChk Enable block dead check for manual closing when VT circuit is abnormal 0 or 1 7.5.1.3 Dual Point Binary Input Settings These settings are applied to configure the status change confirmation time for No.xx double point binary inputs. Up to 15 virtual double point binary inputs are provided in this device. If a double point binary input changes from normal status to invalid status, i.e.: double point error occurs, [CSWIxx.t_DPU_DPS] will be applied as the debouncing time for No.xx double point binary input. (xx=01, 02….15) No. Name 1 CSWI01.t_DPU_DPS 2 CSWI02.t_DPU_DPS 3 CSWI03.t_DPU_DPS Remark It is applied to configure the debouncing time for dual-point binary input No.01. It is applied to configure the debouncing time for dual-point binary input No.02. It is applied to configure the debouncing time for dual-point binary input No.03. PCS-902 Line Distance Relay Range 0~60000 (ms) 0~60000 (ms) 0~60000 (ms) 7-59 Date: 2019-03-01 -09-07 7 Settings No. Name 4 CSWI04.t_DPU_DPS 5 CSWI05.t_DPU_DPS 6 CSWI06.t_DPU_DPS 7 CSWI07.t_DPU_DPS 8 CSWI08.t_DPU_DPS 9 CSWI09.t_DPU_DPS 10 CSWI10.t_DPU_DPS 11 CSWI11.t_DPU_DPS 12 CSWI12.t_DPU_DPS 13 CSWI13.t_DPU_DPS 14 CSWI14.t_DPU_DPS 15 CSWI15.t_DPU_DPS Remark Range It is applied to configure the debouncing time for dual-point binary input No.04. It is applied to configure the debouncing time for dual-point binary input No.05. It is applied to configure the debouncing time for dual-point binary input No.06. It is applied to configure the debouncing time for dual-point binary input No.07. It is applied to configure the debouncing time for dual-point binary input No.08. It is applied to configure the debouncing time for dual-point binary input No.09. It is applied to configure the debouncing time for dual-point binary input No.10. It is applied to configure the debouncing time for dual-point binary input No.11. It is applied to configure the debouncing time for dual-point binary input No.12. It is applied to configure the debouncing time for dual-point binary input No.13. It is applied to configure the debouncing time for dual-point binary input No.14. It is applied to configure the debouncing time for dual-point binary input No.15. 0~60000 (ms) 0~60000 (ms) 0~60000 (ms) 0~60000 (ms) 0~60000 (ms) 0~60000 (ms) 0~60000 (ms) 0~60000 (ms) 0~60000 (ms) 0~60000 (ms) 0~60000 (ms) 0~60000 (ms) 7.5.1.4 Control Settings No. Name 1 CSWI01.t_PW_Opn 2 CSWI01.t_PW_Cls 3 CSWI02.t_PW_Opn 4 CSWI02.t_PW_Cls 5 CSWI03.t_PW_Opn 6 CSWI03.t_PW_Cls Remark Range It is applied to configure the holding time to open CB or disconnector for binary output No.01. It is applied to configure the holding time to close CB or disconnector for binary output No.01. It is applied to configure the holding time to open CB or disconnector for binary output No.02. It is applied to configure the holding time to close CB or disconnector for binary output No.02. It is applied to configure the holding time to open CB or disconnector for binary output No.03. It is applied to configure the holding time to close CB or disconnector for binary output No.03. 7-60 0~60000 (ms) 0~60000 (ms) 0~60000 (ms) 0~60000 (ms) 0~60000 (ms) 0~60000 (ms) PCS-902 Line Distance Relay Date: 2019-03-01 -11-23 7 Settings No. Name 7 CSWI04.t_PW_Opn 8 CSWI04.t_PW_Cls 9 CSWI05.t_PW_Opn 10 CSWI05.t_PW_Cls 11 CSWI06.t_PW_Opn 12 CSWI06.t_PW_Cls 13 CSWI07.t_PW_Opn 14 CSWI07.t_PW_Cls 15 CSWI08.t_PW_Opn 16 CSWI08.t_PW_Cls 17 CSWI09.t_PW_Opn 18 CSWI09.t_PW_Cls 19 CSWI10.t_PW_Opn 20 CSWI10.t_PW_Cls 21 CSWI11.t_PW_Opn 22 CSWI11.t_PW_Cls 23 CSWI12.t_PW_Opn 24 CSWI12.t_PW_Cls 25 CSWI13.t_PW_Opn 26 CSWI13.t_PW_Cls Remark It is applied to configure the holding time to open CB or disconnector for binary output No.04. It is applied to configure the holding time to close CB or disconnector for binary output No.04. It is applied to configure the holding time to open CB or disconnector for binary output No.05. It is applied to configure the holding time to close CB or disconnector for binary output No.05. It is applied to configure the holding time to open CB or disconnector for binary output No.06. It is applied to configure the holding time to close CB or disconnector for binary output No.06. It is applied to configure the holding time to open CB or disconnector for binary output No.07. It is applied to configure the holding time to close CB or disconnector for binary output No.07. It is applied to configure the holding time to open CB or disconnector for binary output No.08. It is applied to configure the holding time to close CB or disconnector for binary output No.08. It is applied to configure the holding time to open CB or disconnector for binary output No.09. It is applied to configure the holding time to close CB or disconnector for binary output No.09. It is applied to configure the holding time to open CB or disconnector for binary output No.10. It is applied to configure the holding time of close CB or disconnector for binary output No.10. It is applied to configure the holding time to open CB or disconnector for binary output No.11. It is applied to configure the holding time to close CB or disconnector for binary output No.11. It is applied to configure the holding time to open CB or disconnector for binary output No.12. It is applied to configure the holding time to close CB or disconnector for binary output No.12. It is applied to configure the holding time to open CB or disconnector for binary output No.13. It is applied to configure the holding time to close CB or PCS-902 Line Distance Relay Range 0~60000 (ms) 0~60000 (ms) 0~60000 (ms) 0~60000 (ms) 0~60000 (ms) 0~60000 (ms) 0~60000 (ms) 0~60000 (ms) 0~60000 (ms) 0~60000 (ms) 0~60000 (ms) 0~60000 (ms) 0~60000 (ms) 0~60000 (ms) 0~60000 (ms) 0~60000 (ms) 0~60000 (ms) 0~60000 (ms) 0~60000 (ms) 0~60000 (ms) 7-61 Date: 2019-03-01 -09-07 7 Settings No. Name Remark Range disconnector for binary output No.13. 27 CSWI14.t_PW_Opn 28 CSWI14.t_PW_Cls 29 CSWI15.t_PW_Opn 30 CSWI15.t_PW_Cls It is applied to configure the holding time to open CB or disconnector for binary output No.14. It is applied to configure the holding time to close CB or disconnector for binary output No.14. It is applied to configure the holding time to open CB or disconnector for binary output No.15. It is applied to configure the holding time to close CB or disconnector for binary output No.15. 0~60000 (ms) 0~60000 (ms) 0~60000 (ms) 0~60000 (ms) 7.5.1.5 Interlock Settings No. Name 1 CSWI01.En_Opn_Blk 2 CSWI01.En_Cls_Blk 3 CSWI02.En_Opn_Blk 4 CSWI02.En_Cls_Blk 5 CSWI03.En_Opn_Blk 6 CSWI03.En_Cls_Blk 7 CSWI04.En_Opn_Blk 8 CSWI04.En_Cls_Blk 9 CSWI05.En_Opn_Blk 10 CSWI05.En_Cls_Blk 11 CSWI06.En_Opn_Blk 12 CSWI06.En_Cls_Blk 13 CSWI07.En_Opn_Blk 14 CSWI07.En_Cls_Blk Remark Range Enable open output of binary output No.01 controlled by the interlocking logic Enable closing output of binary output No.01 controlled by the interlocking logic Enable open output of binary output No.02 controlled by the interlocking logic Enable closing output of binary output No.02 controlled by the interlocking logic Enable open output of binary output No.03 controlled by the interlocking logic Enable closing output of binary output No.03 controlled by the interlocking logic Enable open output of binary output No.04 controlled by the interlocking logic Enable closing output of binary output No.04 controlled by the interlocking logic Enable open output of binary output No.05 controlled by the interlocking logic Enable closing output of binary output No.05 controlled by the interlocking logic Enable open output of binary output No.06 controlled by the interlocking logic Enable closing output of binary output No.06 controlled by the interlocking logic Enable open output of binary output No.07 controlled by the interlocking logic Enable closing output of binary output No.07 controlled by 7-62 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 PCS-902 Line Distance Relay Date: 2019-03-01 -11-23 7 Settings No. Name Remark Range the interlocking logic 15 CSWI08.En_Opn_Blk 16 CSWI08.En_Cls_Blk 17 CSWI09.En_Opn_Blk 18 CSWI09.En_Cls_Blk 19 CSWI10.En_Opn_Blk 20 CSWI10.En_Cls_Blk 21 CSWI11.En_Opn_Blk 22 CSWI11.En_Cls_Blk 23 CSWI12.En_Opn_Blk 24 CSWI12.En_Cls_Blk 25 CSWI13.En_Opn_Blk 26 CSWI13.En_Cls_Blk 27 CSWI14.En_Opn_Blk 28 CSWI14.En_Cls_Blk 29 CSWI15.En_Opn_Blk 30 CSWI15.En_Cls_Blk Enable open output of binary output No.08 controlled by the interlocking logic Enable closing output of binary output No.08 controlled by the interlocking logic Enable open output of binary output No.09 controlled by the interlocking logic Enable closing output of binary output No.09 controlled by the interlocking logic Enable open output of binary output No.10 controlled by the interlocking logic Enable closing output of binary output No.10 controlled by the interlocking logic Enable open output of binary output No.11 controlled by the interlocking logic Enable closing output of binary output No.11 controlled by the interlocking logic Enable open output of binary output No.12 controlled by the interlocking logic Enable closing output of binary output No.12 controlled by the interlocking logic Enable open output of binary output No.13 controlled by the interlocking logic Enable closing output of binary output No.13 controlled by the interlocking logic Enable open output of binary output No.14 controlled by the interlocking logic Enable closing output of binary output No.14 controlled by the interlocking logic Enable open output of binary output No.15 controlled by the interlocking logic Enable closing output of binary output No.15 controlled by the interlocking logic 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 0 or 1 7.5.2 Access Path MainMenu“Settings”“BCU Settings” PCS-902 Line Distance Relay 7-63 Date: 2019-03-01 -09-07 7 Settings 7-64 PCS-902 Line Distance Relay Date: 2019-03-01 -11-23 8 Human Machine Interface 8 Human Machine Interface Table of Contents 8 Human Machine Interface ................................................................ 8-a 8.1 Overview .......................................................................................................... 8-1 8.1.1 Keypad Operation ................................................................................................................ 8-2 8.1.2 LED Indications .................................................................................................................... 8-3 8.1.3 Front Communication Port ................................................................................................... 8-4 8.1.4 Ethernet Port Setup ............................................................................................................. 8-4 8.2 Menu Tree ........................................................................................................ 8-5 8.2.1 Overview .............................................................................................................................. 8-5 8.2.2 Main Menus ......................................................................................................................... 8-6 8.2.3 Sub Menus ........................................................................................................................... 8-7 8.3 Access Authority Management .................................................................... 8-27 8.3.1 Authority Classification ...................................................................................................... 8-28 8.3.2 Authority Identification........................................................................................................ 8-29 8.4 LCD Display ................................................................................................... 8-30 8.4.1 Overview ............................................................................................................................ 8-30 8.4.2 Function Shortcuts Key...................................................................................................... 8-31 8.4.3 Normal Display .................................................................................................................. 8-34 8.4.4 Display Disturbance Records ............................................................................................ 8-35 8.4.5 Display Supervision Event ................................................................................................. 8-37 8.4.6 Display IO Events .............................................................................................................. 8-38 8.4.7 Display Device Logs .......................................................................................................... 8-38 8.5 Keypad Operation ......................................................................................... 8-39 8.5.1 View Device Measurements .............................................................................................. 8-39 8.5.2 View Device Status ............................................................................................................ 8-40 8.5.3 View Device Records......................................................................................................... 8-40 PCS-902 Line Distance Relay 8-a Date: 2019-03-01 8 Human Machine Interface 8.5.4 Print Device Records ......................................................................................................... 8-40 8.5.5 View Device Setting ........................................................................................................... 8-41 8.5.6 Modify Device Setting ........................................................................................................ 8-42 8.5.7 Copy Device Setting .......................................................................................................... 8-45 8.5.8 Switch Setting Group ......................................................................................................... 8-45 8.5.9 Delete Device Records ...................................................................................................... 8-46 8.5.10 Remote Control via Menu ................................................................................................ 8-47 8.5.11 Remote Control via SLD .................................................................................................. 8-50 8.5.12 Control with Open/Close Buttons (if Available) ............................................................... 8-53 8.5.13 Modify Device Clock ........................................................................................................ 8-55 8.5.14 View Module Information ................................................................................................. 8-56 8.5.15 Check Software Version .................................................................................................. 8-56 8.5.16 Communication Test ........................................................................................................ 8-57 8.5.17 Select Language .............................................................................................................. 8-57 List of Figures Figure 8.1-1 Front panel .............................................................................................................. 8-1 Figure 8.1-2 Keypad buttons ...................................................................................................... 8-2 Figure 8.1-3 LED indications ...................................................................................................... 8-3 Figure 8.1-4 Corresponding cable of the RJ45 port in the front panel .................................. 8-4 Figure 8.1-5 Rear view and terminal definition of NR1102D ................................................... 8-5 Figure 8.2-1 Menu tree ................................................................................................................ 8-7 List of Tables Table 8.1-1 Definition of the 8-core cable ................................................................................. 8-4 Table 8.4-1 Tripping report messages ..................................................................................... 8-37 Table 8.4-2 User operating event list ....................................................................................... 8-39 Table 8.5-1 Primary equipment symbols in SLD .................................................................... 8-50 8-b PCS-902 Line Distance Relay Date: 2019-03-01 8 Human Machine Interface The operator can access the protective device from the front panel. Local communication with the protective device is possible using a computer via a multiplex RJ45 port on the front panel. Furthermore, remote communication is also possible using a PC with the substation automation system via rear RS485 port or rear Ethernet port. The operator is able to check the protective device status at any time. This chapter describes human machine interface (HMI), and give operator an instruction about how to display or print event report, setting and so on through HMI menu tree and display metering value, including r.m.s. current, voltage and frequency etc. through LCD. Procedures to change active setting group or a settable parameter value through keypad is also described in details. NOTICE! About the measurements and metering in menu “Measurements”, please refer to the following description: “Measurements1” is used to display measured values from protection calculation DSP. The measurement values can be displayed in primary value or secondary value by the setting [Opt_Display_Status]. “Measurements2” is used to display measured values from fault detector DSP. The measurement values can be displayed in primary value or secondary value by the setting [Opt_Display_Status]. “Measurements3” is used to display measured values of other calculated quantities related to the measurement and control. The measurement values are always displayed in primary value. “Metering” is used to display metering values of active and reactive energy. The metering values are always displayed in primary value. 8.1 Overview The human-machine interface consists of a human-machine interface (HMI) module which allows a communication to be as simple as possible for the user. HEALTHY 11 13 4 14 5 15 6 16 7 17 8 18 9 19 10 20 GRP 3 PCS-902 5 12 ALARM ESC 1 2 ENT 1 4 3 2 Figure 8.1-1 Front panel PCS-902 Line Distance Relay 8-1 Date: 2019-03-01 8 Human Machine Interface The HMI module helps to draw your attention to something that has occurred which may activate a LED or a report displayed on the LCD. Operator can locate the data of interest by navigating the keypad. The function of HMI module: No. Item Description A 320×240 dot matrix backlight LCD display is visible in dim lighting 1 LCD conditions. The corresponding messages are displayed when there is operation implemented. 20 status indication LEDs, 2 LEDs are fixed as the signals of “HEALTHY” 2 LED (green) and “ALARM” (yellow), 18 LEDs are configurable with selectable color among green, yellow and red. 3 Keypad Navigation keypad and command keys for full access to device 4 Communication port a multiplex RJ45 port for local communication with a PC 5 Logo Type and designation and manufacturer of device GR P 8.1.1 Keypad Operation ENT ESC Figure 8.1-2 Keypad buttons 1. 2. 3. “ESC”: Cancel the operation Quit the current menu “ENT”: Execute the operation Confirm the interface “GRP” 4. 5. Activate the switching interface of setting group leftward and rightward direction keys (“◄” and “►”): Move the cursor horizontally Enter the next menu or return to the previous menu upward and downward direction keys (“▲” and “▼”) Move the cursor vertically Select command menu within the same level of menu 8-2 PCS-902 Line Distance Relay Date: 2019-03-01 8 Human Machine Interface 6. plus and minus sign keys (“+” and “-”) Modify the value Modify and display the message number Page up/down 8.1.2 LED Indications HEALTHY ALARM Figure 8.1-3 LED indications A brief explanation has been made as bellow. LED Display Off HEALTHY Steady Green Off Description When the equipment is out of service or any hardware error is defected during self-check. Lit when the equipment is in service and ready for operation. When equipment in normal operating condition. ALARM Steady Yellow Lit when VT circuit failure, CT circuit failure or other abnormal alarm is issued. NOTICE! “HEALTHY” LED can only be turned on by energizing the device and no abnormality detected. “ALARM” LED is turned on when abnormalities of device occurs like above mentioned and can be turned off after abnormalities are removed except alarm report [CTS.Alm] which can only be reset only when the failure is removed and the device is rebooted or re-energized. Other LED indicators with no labels are configurable and user can configure them to be lit by signals of operation element, alarm element and binary output contact according to requirement through PCS-Explorer software, but as drawn in figure, 2 LEDs are fixed as the signals of “HEALTHY” (green) and “ALARM” (yellow), 18 LEDs are configurable with selectable color among green, yellow and red. PCS-902 Line Distance Relay 8-3 Date: 2019-03-01 8 Human Machine Interface 8.1.3 Front Communication Port There is a multiplex RJ45 port on the front panel. This port can be used as an RS-232 serial port as well as a twisted-pair ethernet port. As shown in the following figure, a customized cable is applied for debugging via this multiplex RJ45 port. P2 P1 P3 Figure 8.1-4 Corresponding cable of the RJ45 port in the front panel In the above figure and the following table: P1: To connect the multiplex RJ45 port. An 8-core cable is applied here. P2: To connect the twisted-pair ethernet port of the computer. P3: To connect the RS-232 serial port of the computer. The definition of the 8-core cable in the above figure is introduced in the following table. Table 8.1-1 Definition of the 8-core cable Terminal No. Core color Function Device side Computer side (Left) (Right) 1 Orange & white TX+ of the ethernet port P1-1 P2-1 2 Orange TX- of the ethernet port P1-2 P2-2 3 Green & white RX+ of the ethernet port P1-3 P2-3 4 Blue TXD of the RS-232 serial port P1-4 P3-2 5 Brown & white RXD of the RS-232 serial port P1-5 P3-3 6 Green RX- for the ethernet port P1-6 P2-6 7 Blue & white 8 Brown The ground connection of the RS-232 port. P1-7 P1-8 P3-5 8.1.4 Ethernet Port Setup MON plug-in module is equipped with two or four 100Base-TX Ethernet interface, take NR1102D as an example, as shown in Figure 8.1-5. Its rear view and the definition of terminals. The Ethernet port can be used to communication with PC via auxiliary software (PCS-Explorer) after connecting the protection device with PC, so as to fulfill on-line function (please refer to the instruction manual of PCS-Explorer). At first, the connection between the protection device and PC 8-4 PCS-902 Line Distance Relay Date: 2019-03-01 8 Human Machine Interface must be established. Through setting the IP address and subnet mask of corresponding Ethernet interface in the menu “Settings→Device Setup→Comm Settings”, it should be ensured that the protection device and PC are in the same network segment. For example, setting the IP address and subnet mask of network A. (using network A to connect with PC) PC: IP address is set as “198.87.96.102”, subnet mask is set as “255.255.255.0” The IP address and subnet mask of protection device should be [IP_LAN1]= 198.87.96.XXX, [Mask_LAN1]=255.255.255.0, [En_LAN1]=1. (XXX can be any value from 0 to 255 except 102) If the logic setting [En_LAN1] is non-available, it means that network A is always enabled. NR1102D ETHERNET Network A Network B Network C Network D Figure 8.1-5 Rear view and terminal definition of NR1102D NOTICE! If using other Ethernet port, for example, Ethernet B, the logic setting [En_LAN2] must be set as “1”. 8.2 Menu Tree 8.2.1 Overview Press “▲” of any running interface and enter the main menu. Select different submenu by “▲” and “▼”. Enter the selected submenu by pressing “ENT” or “►”. Press “◄” and return to the previous menu. Press “ESC” back to main menu directly. For sake of entering the command menu again, a command menu will be recorded in the quick menu after its execution. Five latest command menus can be recorded in the quick menu. When five command menus are recorded, the latest command menu will cover the earliest one, adopting the “first in first out” principle. It is arranged from top to bottom and in accordance with the execution order of command menus. PCS-902 Line Distance Relay 8-5 Date: 2019-03-01 8 Human Machine Interface Press “▲” to enter the main menu with the interface as shown in the following diagram: MainMenu Language Clock Quick Menu For the first powered device, there is no record in quick menu. Press “▲” to enter the main menu with the interface as shown in the following diagram: Measurements Status Records Settings Print Local Cmd Information Test Clock Language The descriptions about menu are based on the maximized configuration, for a specific project, if some function is not available, the corresponding submenu will hidden. 8.2.2 Main Menus The menu of PCS-902 is organized into main menu and submenus, much like a PC directory structure. The menu of PCS-902 is divided into 10 sections: 8-6 PCS-902 Line Distance Relay Date: 2019-03-01 8 Human Machine Interface Main Menu Measurements Status Records Settings Print Local Cmd Information Test Clock Language Figure 8.2-1 Menu tree Under main interface, press “▲” to enter main menu, and select submenu by pressing “▲”, “▼” and “ENT”. The command menu adopts a tree shaped content structure. The above diagram provides the integral structure and all main menus (first-level menus) under menu tree of the device. 8.2.3 Sub Menus 8.2.3.1 Measurements Main Menu Measurements Measurements1 Measurements2 Measurements3 Metering This menu is used to display real-time measured values, including AC voltage, AC current, phase angle and calculated quantities. These data can help users to acquaint the device′s status. This menu comprises following submenus. Please refer to section “Measurement” about the detailed measured values. PCS-902 Line Distance Relay 8-7 Date: 2019-03-01 8 Human Machine Interface No. Item Function description 1 Measurements1 Display measured values from protection calculation DSP 2 Measurements2 Display measured values from fault detector DSP 3 Measurements3 4 Metering Display measured values of other calculated quantities related to the measurement and control Display metering values of active and reactive energy 8.2.3.2 Status Main Menu Status Inputs Outputs Superv State Running Status This menu is used to display real time input signals, output signals, alarm signals and running status of the device. These data can help users to acquaint the device′s status. This menu comprises following submenus. Please respectively refer to section “Signal List” about the detailed introduction of input signals and output signals, and section “Supervision Alarms” about the detailed introduction of alarm signals. No. Item Function description 1 Inputs Display all input signal states 2 Outputs Display all output signal states 3 Superv State Display supervision alarm states 4 Running Status Display running status The submenu “Inputs” comprises the following command menus. Main Menu Status Inputs Contact Inputs GOOSE Inputs Prot Ch Inputs 8-8 PCS-902 Line Distance Relay Date: 2019-03-01 8 Human Machine Interface No. Item Function description 1 Contact Inputs Display states of binary inputs derived from opto-isolated channels 2 GOOSE Inputs Display states of GOOSE binary inputs. 3 Prot Ch Inputs Display states of binary inputs received from protection channel. The submenu “Outputs” comprises the following command menus. Main Menu Status Outputs Contact Outputs GOOSE Outputs Interlock Status Prot Ch Outputs No. Item Function description 1 Contact Outputs Display states of contact binary outputs 2 GOOSE Outputs Display states of GOOSE binary outputs 3 Interlock Status Display states of interlock result of each remote control. 4 Prot Ch Outputs Display states of channel outputs The submenu “Superv State” comprises the following command menus. Main Menu Status Superv State Prot Superv FD Superv GOOSE Superv SV Superv BCU Superv NetPort Superv PCS-902 Line Distance Relay 8-9 Date: 2019-03-01 8 Human Machine Interface No. Item Function description 1 Prot Superv Display states of self-supervision signals from protection calculation DSP 2 FD Superv Display states of self-supervision signals from fault detector DSP 3 GOOSE Superv Display states of GOOSE self-supervision signals 4 SV Superv Display states of SV self-supervision signals 5 BCU Superv Display states of measurement and control self-supervision signals 6 NetPort Superv Display working status (0: abnormal, 1: normal), link status (0: disconnection, 1: connection) and bonding status of Ethernet ports The submenu “Running Status” comprises the following command menus. Main Menu Status Running Status Net Port No. Item Function description Display working state (0: abnormal, 1: normal) and link state (0: 1 Net Port disconnection, 1: connection) of Ethernet port 1, 2, 3, 4 and bonding ports 8.2.3.3 Records Main Menu Records Disturb Records Superv Events IO Events Device Logs Control Logs Clear Records This menu is used to display all kinds of records, including the disturbance records, supervision events, binary events and device logs, so that the operator can load to view and use as the reference of analyzing accidents and repairing the device. All records are stored in non-volatile memory, it can still record them even if it loses its power. This menu comprises the following submenus. 8-10 PCS-902 Line Distance Relay Date: 2019-03-01 8 Human Machine Interface No. Item Function description 1 Disturb Records Display disturbance records of the device 2 Superv Events Display supervision events of the device 3 IO Events Display binary events of the device 4 Device Logs Display device logs of the device 5 Control Logs Display control logs of the device 6 Clear Records Clear all records. 8.2.3.4 Settings Main Menu Settings System Settings Prot Settings BCU Settings Logic Links Device Setup This menu is used to check the device setup, system parameters, protection settings and logic links settings, as well as modifying any of the above setting items. Moreover, it can also execute the setting copy between different setting groups. This menu comprises the following submenus. No. Item Function description 1 System Settings Check or modify the system parameters 2 Prot Settings Check or modify the protection settings 3 BCU Settings Check or modify the measurement and control settings 4 Logic Links 5 Device Setup Check or modify the logic links settings, including function links, SV links, GOOSE links and spare links Check or modify the device setup The submenu “Prot Settings” includes the following command menus. PCS-902 Line Distance Relay 8-11 Date: 2019-03-01 8 Human Machine Interface Main Menu Settings Prot Settings No. Line Settings BFP Settings FD Settings Deadzone Settings AuxE Settings OV Settings Direction Settings UV Settings Pilot Scheme Settings NegOV Settings Rmt CommCh Settings ThOvld Settings DPFC Dist Settings PD Settings LoadEnch Settings Stub Settings Dist Settings FreqProt Settings ROC Settings OOS Settings NegOC Settings MiscProt Settings SOTF Settings Superv Settings OC Settings Trip Logic Settings VTF OC Settings CB1 AR/Syn Settings RevPower Settings CB2 AR/Syn Settings BRC Settings Copy Settings Item Function description 1 Line Settings Check or modify line parameters 2 FD Settings Check or modify fault detector element settings 3 AuxE Settings Check or modify auxiliary element settings 4 Direction Settings Check or modify direction control element settings 5 Pilot Scheme Settings 6 Rmt CommCh Settings Check or modify optical pilot channel settings 7 DPFC Dist Settings Check or modify DPFC distance protection settings 8 LoadEnch Settings Check or modify load encroachment settings 9 Dist Settings Check or modify distance protection settings 10 ROC Settings Check or modify directional earth-fault protection settings 11 NegOC Settings Check or modify negative-sequence overcurrent protection settings Check or modify pilot distance protection and pilot directional earth-fault protection settings 8-12 PCS-902 Line Distance Relay Date: 2019-03-01 8 Human Machine Interface 12 SOTF Settings Check or modify SOTF distance and overcurrent protection settings 13 OC Settings Check or modify phase overcurrent protection settings 14 VTF OC Settings Check or modify overcurrent protection settings for VT circuit failure 15 RevPower Settings Check or modify reverse power protection settings 16 BRC Settings Check or modify broken conductor protection settings 17 BFP Settings Check or modify breaker failure protection settings 18 Deadzone Settings Check or modify dead zone settings 19 OV Settings Check or modify overvoltage protection settings 20 UV Settings Check or modify undervoltage protection settings 21 NegOV Settings Check or modify negative-sequence overvoltage protection settings 22 ThOvld Settings Check or modify thermal overload protection settings 23 PD Settings Check or modify pole discrepancy protection settings 24 Stub Settings Check or modify stub overcurrent protection settings 25 FreqProt Settings Check or modify frequency protection settings 26 OOS Settings Check or modify out-of-step protection settings 27 MiscProt Settings Check or modify miscellaneous settings 28 Superv Settings Check or modify VT circuit supervision and CT circuit supervision settings 29 Trip Logic Settings Check or modify trippling logic settings 30 CB1 AR/Syn Settings 31 CB2 AR/Syn Settings 32 Copy Settings Check or modify synchronism check and auto-reclosing settings of circuit breaker No.1 Check or modify synchronism check and auto-reclosing settings of circuit breaker No.2 Copy setting between different setting groups The submenu “BCU Settings” includes the following command menus. Main Menu Settings BCU Settings FUN Settings CB1 Syn Settings CB2 Syn Settings BI Settings Control Settings Interlock Settings PCS-902 Line Distance Relay 8-13 Date: 2019-03-01 8 Human Machine Interface No. Item Function description 1 FUN Settings Check or modify function settings 2 CB1 Syn Settings Check or modify manual synchronism check settings for circuit breaker 1 3 CB2 Syn Settings Check or modify manual synchronism check settings for circuit breaker 2 4 BI Settings Check or modify binary input settings 5 Control Settings Check or modify control settings 6 Interlock Settings Check or modify interlock settings The submenu “Logic Links” comprises the following command menus. Main Menu Settings Logic Links Function Links GOOSE Send Links GOOSE Recv Links SV Links No. Item Function description 1 Function Links Check or modify function links settings 2 GOOSE Send Links Check or modify GOOSE sending links settings 3 GOOSE Recv Links Check or modify GOOSE receiving links settings 4 SV Links Check or modify SV links settings The submenu “Device Setup” comprises the following command menus. Main Menu Settings Device Setup Device Settings Comm Settings Label Settings 8-14 PCS-902 Line Distance Relay Date: 2019-03-01 8 Human Machine Interface No. Item Function description 1 Device Settings Check or modify the device settings. 2 Comm Settings Check or modify the communication settings. 3 Label Settings Check or modify the label settings of each protection element. 8.2.3.5 Print Main Menu Print Device Info Settings Disturb Records Superv Events IO Events Prot Ch Superv Prot Ch Statistics Device Status Waveforms IEC103 Info Cancel Print This menu is used to print device description, settings, all kinds of records, waveforms, information related with IEC60870-5-103 protocol, channel state and channel statistic. This menu comprises the following submenus. No. 1 Item Device Info Function description Print the description information of the device, including software version. Print device setup, system parameters, protection settings and logic 2 Settings links settings. It can print by different classifications as well as printing all settings of the device. Besides, it can also print the latest modified settings. 3 Disturb Records Print the disturbance records 4 Superv Events Print the supervision events 5 IO Events Print the binary events 6 Prot Ch Superv Print the self-check information of optical fibre channel, which is made of some hexadecimal characters and used to developer analyze channel PCS-902 Line Distance Relay 8-15 Date: 2019-03-01 8 Human Machine Interface state 7 Prot Ch Statistics 8 Device Status 9 Waveforms Print the statistic report of optical fibre channel, which is formed A.M. 9:00 every day Print the current state of the device, including the sampled value of voltage and current, the state of binary inputs, setting and so on Print the recorded waveforms Print 103 Protocol information, including function type (FUN), 10 IEC103 Info information serial number (INF), general classification service group number, and channel number (ACC) 11 Cancel Print Cancel the print command The submenu “Settings” comprises the following submenus. Main Menu Print Settings System Settings Prot Settings BCU Settings Logic Links Device Setup All Settings Latest Chgd Settings No. Item Function description 1 System Settings Print the system parameters 2 Prot Settings Print the protection settings 3 BCU Settings Print the measurement and control settings 4 Logic Links Print the logic links settings 5 Device Setup Print the settings related to device setup 6 All Settings 7 Latest Chgd Settings Print all settings including device setup, system parameters, protection settings and logic links settings Print the setting latest modified The submenu “Prot Settings” comprises the following command menus. 8-16 PCS-902 Line Distance Relay Date: 2019-03-01 8 Human Machine Interface Main Menu Print Settings Prot Settings No. Line Settings BFP Settings FD Settings Deadzone Settings AuxE Settings OV Settings Direction Settings UV Settings Pilot Scheme Settings NegOV Settings Rmt CommCh Settings ThOvld Settings DPFC Dist Settings PD Settings LoadEnch Settings Stub Settings Dist Settings FreqProt Settings ROC Settings OOS Settings NegOC Settings MiscProt Settings SOTF Settings Superv Settings OC Settings Trip Logic Settings VTF OC Settings CB1 AR/Syn Settings RevPower Settings CB2 AR/Syn Settings BRC Settings All Settings Item Function description 1 Line Settings Print line parameters 2 FD Settings Print fault detector element settings 3 AuxE Settings Print auxiliary element settings 4 Direction Settings Print direction control element settings 5 Pilot Scheme Settings 6 Rmt CommCh Settings Print optical pilot channel settings 7 DPFC Dist Settings Print y DPFC distance protection settings 8 LoadEnch Settings Print load encroachment settings 9 Dist Settings Print distance protection settings 10 ROC Settings Print directional earth-fault protection settings 11 NegOC Settings Print negative-sequence overcurrent protection settings 12 SOTF Settings Print SOTF distance and overcurrent protection settings Print pilot distance protection and pilot directional earth-fault protection settings PCS-902 Line Distance Relay 8-17 Date: 2019-03-01 8 Human Machine Interface 13 OC Settings Print phase overcurrent protection settings 14 VTF OC Settings Print overcurrent protection settings for VT circuit failure 15 RevPower Settings Print reverse power protection settings 16 BRC Settings Print broken conductor protection settings 17 BFP Settings Print breaker failure protection settings 18 Deadzone Settings Print dead zone settings 19 OV Settings Print overvoltage protection settings 20 UV Settings Print undervoltage protection settings 21 NegOV Settings Print negative-sequence overvoltage protection settings 22 ThOvld Settings Print thermal overload protection settings 23 PD Settings Print pole discrepancy protection settings 24 Stub Settings Print stub overcurrent protection settings 25 FreqProt Settings Print frequency protection settings 26 OOS Settings Print out-of-step protection settings 27 MiscProt Settings Print miscellaneous settings 28 Superv Settings Print VT circuit supervision and CT circuit supervision settings 29 Trip Logic Settings Print trippling logic settings 30 CB1 AR/Syn Settings 31 CB2 AR/Syn Settings 32 All Settings Print synchronism check and auto-reclosing settings of circuit breaker No.1 Print synchronism check and auto-reclosing settings of circuit breaker No.2 Print all settings included in “Prot Settings” submenu The submenu “BCU Settings” includes the following command menus. 8-18 PCS-902 Line Distance Relay Date: 2019-03-01 8 Human Machine Interface Main Menu Print Settings BCU Settings FUN Settings CB1 Syn Settings CB2 Syn Settings BI Settings Control Settings Interlock Settings All Settings No. Item Function description 1 FUN Settings Print function settings 2 CB1 Syn Settings Print manual synchronism check settings for circuit breaker 1 3 CB2 Syn Settings Print manual synchronism check settings for circuit breaker 2 4 BI Settings Print binary input settings 5 Control Settings Print control settings 6 Interlock Settings Print interlock settings 7 All Settings Print all settings included in “BCU Settings” submenu The submenu “Logic Links” comprises the following command menus. PCS-902 Line Distance Relay 8-19 Date: 2019-03-01 8 Human Machine Interface Main Menu Print Settings Logic Links Function Links GOOSE Send Links GOOSE Recv Links SV Links All Settings No. Item Function description 1 Function Links Print function links settings 2 GOOSE Send Links Print GOOSE sending links settings 3 GOOSE Recv Links Print GOOSE receiving links settings 4 SV Links Print SV links settings 5 All Settings Print all settings included in “Logic Links” submenu The submenu “Device Setup” comprises the following command menus. Main Menu Print Settings Device Setup Device Settings Comm Settings Label Settings All Settings No. Item Function description 1 Device Settings Print the device settings. 2 Comm Settings Print the communication settings. 3 Label Settings Print the label settings of each protection element. 8-20 PCS-902 Line Distance Relay Date: 2019-03-01 8 Human Machine Interface 4 Print all settings included in “Device Setup” submenu All Settings The submenu “Prot Ch Superv” comprises the following command menus. Main Menu Print Prot Ch Superv Channel 1 Channel 2 No. Item 1 Channel 1 2 Channel 2 Function description Print the self-check information of optical fibre channel 1, which is made of some hexadecimal characters and used to developer analyze channel state Print the self-check information of optical fibre channel 2, which is made of some hexadecimal characters and used to developer analyze channel state The submenu “Prot Ch Statistics” includes the following command menus. Main Menu Print Prot Ch Statistics Channel 1 Channel 2 No. Item 1 Channel 1 2 Channel 2 Function description Print the statistic report of optical fibre channel 1, which is formed A.M. 9:00 every day Print the statistic report of optical fibre channel 2, which is formed A.M. 9:00 every day The submenu “Waveforms” includes the following command menus. PCS-902 Line Distance Relay 8-21 Date: 2019-03-01 8 Human Machine Interface Main Menu Print Waveforms Wave No. 1 Item Function description Wave Print the recorded current and voltage waveforms 8.2.3.6 Local Cmd Main Menu Local Cmd Reset Target Trig Oscillograph Control Download Clear Counter Clear CB1 AR Counter Clear CB2 AR Counter Clear Energy Counter This menu is used to reset the tripping relay with latch, indicator LED, LCD display, and as same as the reset function of binary inputs. This menu provides a method of manually recording the current waveform data of the device under normal condition for printing and uploading SAS. Besides, it can send out the request of program download, clear statistic information about GOOSE, SV, AR, FO channel and energy. This menu comprises the following submenus. No. Item Function description 1 Reset Target Reset the local signal, indicator LED, LCD display and so on 2 Trig Oscillograph Trigger waveform recording 3 Control Manually operating to trip, close output or for signaling purpose 4 Download Send out the request of downloading program 5 Clear Counter Clear GOOSE, SV and FO channel statistic data 6 Clear CB1 AR Counter Clear AR statistic data of circuit breaker No.1 8-22 PCS-902 Line Distance Relay Date: 2019-03-01 8 Human Machine Interface 7 Clear CB2 AR Counter 8 Clear Energy Counter Clear AR statistic data of circuit breaker No.2 Clear all energy metering values (i.e., PHr+_Pri, PHr-_Pri, Qr+_Pri, QHr-_Pri) 8.2.3.7 Information Main Menu Information Version Info Board Info MOT Info In this menu, LCD can display software information of all kinds of intelligent plug-in modules, which consists of version, creating time of software, CRC codes and management sequence number. Besides, plug-in module information and MOT information can also be viewed. This menu comprises the following command menus. No. Item Function description Display software information of DSP module, MON module and HMI module, 1 Version Info which consists of version, creating time of software, CRC codes and management sequence number. 2 Board Info Monitor the current working state of each intelligent module. 3 MOT Info Display ordering code 8.2.3.8 Test Main Menu Test Prot Ch Counter GOOSE Comm Counter SV Comm Counter Device Test Internal Signal AR Counter HMI Setup This menu is mainly used for developers to debug the program and for engineers to maintain the device. It can be used to fulfill the communication test function. It is also used to generate all kinds PCS-902 Line Distance Relay 8-23 Date: 2019-03-01 8 Human Machine Interface of reports or events to transmit to the SAS without any external input, so as to debug the communication on site. Besides, it can also display statistic information about GOOSE, SV, AR and FO channel. This menu comprises the following submenus. No. Item Function description 1 Prot Ch Counter Check communication statistics data of protection FO channel 2 GOOSE Comm Counter Check communication statistics data of GOOSE 3 SV Comm Counter Check communication statistics data of SV (Sampled Values) Automatically generate all kinds of reports or events to transmit to SCADA, 4 including disturbance records, self-supervision events and binary events. It Device Test can realize the report uploading by different classification, as well as the uploading of all kinds of reports 5 Internal Signal This submenu is only reserved for the manufacturer 6 AR Counter Check AR counters 7 HMI Setup Configure LCD display and check LCD display and LED indicators The submenu “Prot Ch Counter” comprises the following command menus. Main Menu Test Prot Ch Counter Ch1 Counter Ch2 Counter No. Item Function description 1 Ch1 Counter Check communication statistic information of channel 1 2 Ch2 Counter Check communication statistic information of channel 2 The submenu “Device Test” comprises the following submenus. 8-24 PCS-902 Line Distance Relay Date: 2019-03-01 8 Human Machine Interface Main Menu Test Device Test Disturb Events Superv Events IO Events No. Item 1 Disturb Events 2 Superv Events 3 IO Events Function description View the relevant information about disturbance records (only used for debugging persons) View the relevant information about supervision events (only used for debugging persons) View the relevant information about binary events (only used for debugging persons) Users can respectively execute the test automatically or manually by selecting commands “All Test” or “Select Test”. The submenu “Disturb Events” comprises the following command menus. Main Menu Test Device Test Disturb Events All Test Select Test No. Item Description 1 All Test Ordinal test of all protection elements 2 Select Test Selective test of corresponding classification The submenu “Superv Events” comprises the following command menus. PCS-902 Line Distance Relay 8-25 Date: 2019-03-01 8 Human Machine Interface Main Menu Test Device Test Superv Events All Test Select Test No. Item Description 1 All Test Ordinal test of all self-supervisions 2 Select Test Selective test of corresponding classification The submenu “IO Events” comprises the following command menus. Main Menu Test Device Test IO Events All Test Select Test No. Item Description 1 All Test Ordinal test of change of all binary inputs 2 Select Test Selective test of corresponding classification The submenu “AR Counter” comprises the following command menus. Main Menu Test AR Counter CB1 AR Counter CB2 AR Counter 8-26 PCS-902 Line Distance Relay Date: 2019-03-01 8 Human Machine Interface No. Item Function description 1 CB1 AR Counter Check AR counters of circuit breaker No.1 2 CB2 AR Counter Check AR counters of circuit breaker No.2 The submenu “HMI Setup” comprises the following command menus. Main Menu Test HMI Setup Contrast BacklitDur LgtIntnsty SupervLCD SupervLED No. Item Function description 1 Contrast To adjust the contrast of LCD display 2 BacklitDur To adjust the duration of LCD backlight 3 Lgtlntnsty To adjust the brightness of LCD display 4 SupervLCD To find out dead pixel of LCD display 5 SupervLED To find out broken LED indicator 03~20 8.2.3.9 Clock The current time of internal clock can be viewed here. The time is displayed in the form YY-MM-DD and hh:mm:ss. All values are presented with digits and can be modified. 8.2.3.10 Language This menu is mainly used to set LCD display language. 8.3 Access Authority Management In order to conveniently manage access authority, the device support setup up to 40 users and allow each user to own different password (user password can support 8 characters at most and must include one lowercase letter, one capital letter and one number at least) and access authority (such as modify settings, view records, remote control) According to different access authority, the corresponding operations to the device by LCD panel can be allowed to perform. For the operation that requires authorization, the corresponding user PCS-902 Line Distance Relay 8-27 Date: 2019-03-01 8 Human Machine Interface logs in and the correct password must be input after the operation can be performed. 8.3.1 Authority Classification The device provide four kinds of authorities: View, Control, Setting, Project. The default configuration of the device is no multi-users. Each item of different authority class can be enabled or disabled independently, and the operation without access authority can be performed directly no password provided. The valid time of the password can be set, and the password need not be input again within the valid time ,which ensure both security and convenience. Taking “User1” as an example, four kinds of authorities: View, Control, Setting, Project are shown as below. 8-28 PCS-902 Line Distance Relay Date: 2019-03-01 8 Human Machine Interface 8.3.2 Authority Identification The operation is as follows: 1. Press the “▲” to enter the main menu, the following interface will be shown when performing an operation. (Multi-users have been configured in advance) 2. Press the “◄” or “►” to select username, and press the “ESC” to exit this menu Username User1 Password 3. Press the “ENT” or “▼” to move, and the following interface will be shown after the username is confirmed. Username User1 Password ****** 0 1 2 3 4 5 6 7 8 9 [OK] 4. Press the “◄” or “►” to select number or letter, and press “ENT” to ensure selected character. 5. Press the “▲” or “▼” to page up/down to select previous group or next group characters. 6. Press the “GRP” to switch uppercase or lowercase to be chosen characters. 7. When the password reaches to 8 bits, the device will verify whether the username and PCS-902 Line Distance Relay 8-29 Date: 2019-03-01 8 Human Machine Interface password are correctly. If the password is shorter than 8 bits, select and press “OK” to begin to verify whether the username and password are correctly. 8. Press the “ESC” to cancel entered character during entering password, and the password will be cleared if the password check fails. When the password is cleared, press the “ESC” to select the username again. 9. The device provides the function of password memory, the following interface will be shown if the valid time of the password is set and last entered password is no timeout. Username User1 Password ******* 10. Press the “ENT” to verify the password, press the “◄” or “►” to switch the username and the password will be cleared, and press the “ESC” to exit the interface. 11. If the password is correct and the user owns the authority of the operation performed, the operation will be performed. If the password is incorrect, the device will issue an alarm signal “Password Error”. If the password is correct but the user has no the authority of the operation performed, the device will issue an alarm signal “Unauthorized”. If the password is incorrect or the user has no the authority of the operation performed more than three times, the device will issue an alarm signal “PWD Error or Unauthorized, Screen Locked” and the device will return to main interface after the screen is locked for 1 minutes, which will be recorded in device log. 8.4 LCD Display 8.4.1 Overview There are some kinds of LCD display, SLD (single line diagram) display, disturbance records, supervision events, IO events, control logs and device logs. Disturbance records and supervision events will not disappear until them are acknowledged by pressing the “RESET” button in the protection panel (i.e. energizing the binary input [BI_RstTarg]). If any event is detected, the corresponding event display will pop up automatically, and user can keep pressing “ENT” and then press “ESC” to switch between normal display and event display. IO events will be displayed for 5s 8-30 PCS-902 Line Distance Relay Date: 2019-03-01 8 Human Machine Interface and then it will return to the previous display interface automatically. Device logs will not pop up and can only be viewed by navigating the corresponding menu. 8.4.2 Function Shortcuts Key The device provide some function shortcuts key, which can be configured by PCS-Explorer and be fulfilled by combination key of devices' keypad, to execute some operation quickly. 8.4.2.1 Shortcuts Key Configuration 1. Right-click the menu “LCD Graph”, and select the menu item “Edit Shortcut Key” to display the configuration interface of function key shortcuts as shown below. 2. In configuration interface, double-click the table item in the list of “Extend Command” to select LCD extend command of dropdown list corresponding with keypads in front panel as shown below. Select the first blank item in dropdown list to cancel the setup. PCS-902 Line Distance Relay 8-31 Date: 2019-03-01 8 Human Machine Interface 3. Double-click the table item in the list of “Attribute” to edit the attribute of keypad in front panel as shown below. When the attribute is set as “1”, the corresponding operation can not execute unless input correct password. When the attribute is set as “0” or blank, password is not required. After finishing configuration, click the button “OK”. 4. The name description of extend command can be modified in signal setup interface, the operation “Refresh” in the interface of “Source” must be execute at first before configuring function shortcuts key or generating drive file package. 5. Right-click device node and execute the menu “Compress Driver File” to generate drive file package of the device. The file “LCDConfig.txt” in drive file package of the device records related contents about shortcuts key. If shortcuts keys are not required, set “Extend Command” corresponding with function shortcuts key as blank, and generate drive file package of the device again. 8-32 PCS-902 Line Distance Relay Date: 2019-03-01 8 Human Machine Interface 8.4.2.2 Function Description In general, the function of “GRP” is switch setting group, however, the original function of “GRP” is blocked when configuring function shortcuts key. (the setting group can be switched by shortcuts key, binary input or modifying the setting) Under main interface, press “GRP” to display the interface of function shortcuts key and press “ESC” to return to main interface. Shortcut keys [ ] LCD.ExtCmd04 [ ] LCD.ExtCmd05 [ ] LCD.ExtCmd06 [ ] LCD.ExtCmd07 [ + ] LCD.ExtCmd08 [ ] LCD.ExtCmd09 [ ENT ] LCD.ExtCmd10 - The device support 10 extended command, LCD.ExtCmd01~LCD.ExtCmd10, and the name can be modified by PCS-Explorer. The first three extend command is fixed in program, so only LCD.ExtCmd04~LCD.ExtCmd10 are configurable, and configured as any of seven function shortcuts key (“▲”, “▼”, “◄”, “►”, “+”, “-” and “ENT”). PCS-902 Line Distance Relay 8-33 Date: 2019-03-01 8 Human Machine Interface Password: 000 Under the interface of function shortcuts key, press a shortcuts key to execute corresponding operation. If the attribute of the extend command is set as “1”, the corresponding operation can not execute unless input correct password. The extend command executed by shortcuts key outputs a pulse signal with 500ms, and for the operation requiring latching signal, the device provides “T_FF” and “RS_FF” to fulfill the application, which can be configured by PCS-Explorer. 8.4.3 Normal Display After the device is powered and entered into the initiating interface, it takes tens of seconds to complete the initialization of the device. During the initialization of the device, the “HEALTHY” indicator lamp of the device goes out. The device can display single line diagram (SLD) and primary operation information, it can support wiring configuration function. LCD configuration file can be downloaded via the network. Remote control operation through single line diagram is also supported. Under normal condition, LCD will display the following interface. LCD adopts white color as its backlight that is activated if once there is any keyboard operation, moreover, the backlight will be extinguished automatically if no keyboard operation is detected for a duration. 8-34 PCS-902 Line Distance Relay Date: 2019-03-01 8 Human Machine Interface S 2010-06-08 10:10:00 Ia 0.00A Ib 0.00A Ic 0.00A 3I0 0.00A Ua 0.02V Ub 0.00V Uc 0.00V 3U0 0.02V U_Syn 0.00V f 50.00Hz Addr 24343 Group 01 The content displayed on the screen contains: the current date and time of the device (with a format of yyyy-mm-dd hh:mm:ss:), the active setting group number, three-phase current sampling value, residual current sampling value, three-phase voltage sampling value, residual voltage sampling value, the synchronism voltage sampling value, line frequency and the address relevant to IP address of Ethernet A. If all the sampling values of the voltage and the current can’t be fully displayed within one screen, they will be scrolling-displayed automatically from the top to the bottom. If IP address of Ethernet A is “xxx.xxx.a.b”, the displayed address equals to (a×256+b). For example, If IP address of Ethernet A is “198.087.095.023”, the displayed address will be “95× 256+23=24343”. If the device has detected any abnormal state, it′ll display the self-check alarm information. “S” indicates that device clock is synchronized. If “S” disappears, it means that device clock is not synchronized. 8.4.4 Display Disturbance Records This device can store up to 32 groups of disturbance records with fault waveform. Each group consists of disturbance records of operation elements and corresponding fault detector elements. Up to 1024 disturbance records can be stored in this device. If there is protection element operation, LCD will automatically display the latest group of disturbance records, and two kinds of LCD display interfaces will be available depending on whether there are supervision events or not. For the situation that the disturbance records and the supervision events coexist, the upper half part is the disturbance record, and the lower half part is the supervision event. The following items are listed in the upper half part: record No., record name, generation time of the disturbance record. If there is protection element operation, faulty phase and relative operation time (with reference to the corresponding fault detector element) will be displayed. If the disturbance records can not be displayed in one page, they will be displayed in several pages alternately. PCS-902 Line Distance Relay 8-35 Date: 2019-03-01 8 Human Machine Interface If there is no supervision event, disturbance records will be displayed as shown in the following figure. 2013-01-15 13:22:23:669 NO.001 0000ms Disturb FD.DPFC.Pkp 0024ms AB 21Q.Z1.Op If the device has the supervision event, the display interface will show the disturbance record and the supervision event at the same time. 2013-01-15 13:22:23:669 NO.001 0000ms Disturb FD.DPFC.Pkp 0024ms AB 21Q.Z1.Op Superv Events Alm_Device NO.001 shows the SOE No. of the disturbance record. 2013-01-15 13:22:23:669 shows the time of the disturbance record, the format is “yyyy-mm-dd hh:mm:ss:fff”. Disturb shows the title of the disturbance record. 8-36 PCS-902 Line Distance Relay Date: 2019-03-01 8 Human Machine Interface 0000ms FD.DPFC.Pkp shows fault detector element and its operation time (set as “0000ms” fixedly). 0024ms AB shows operation element and its relative operation time (with 21Q.Z1.Op reference to the corresponding fault detector element). All the protection elements have been listed in chapter “Operation Theory”, and please refer to each protection element for details. The reports related to oscillography function are showed in the following table. Table 8.4-1 Tripping report messages No. Message Description 1 TrigDFR_Man Oscillography function is triggered manually. 2 TrigDFR_Rmt Oscillography function is triggered remotely. Oscillography function is triggered by binary input [BI_TrigDFR]. The 3 TrigDFR_BI binary input [BI_TrigDFR] is configurable, and it can be designated to internal signal or external input. 8.4.5 Display Supervision Event This device can store 1024 pieces of supervision events. During the running of the device, the supervision event of hardware self-check errors or system running abnormity will be displayed immediately. S Superv Events Alm_Device Alm_Version S indicates that device clock is synchronized. If “S” disappears, it means that device clock is not synchronized. Superv Events shows the title of the supervision events. Alm_Device shows the contents of supervision events. PCS-902 Line Distance Relay 8-37 Date: 2019-03-01 8 Human Machine Interface Alm_Version 8.4.6 Display IO Events This device can store 1024 pieces of binary events. During the running of the device, the binary input will be displayed once its state has changed, i.e. from “0” to “1” or from “1” to “0”. NO.001 2013-01-15 13:31:23:669 IO Chg BI_Maintenance 0 1 NO.001 shows the No. of the binary event. 2013-01-15 13:31:23:669 shows date and time when the report occurred, the format is “yyyy-mm-dd hh:mm:ss:fff”. IO Chg shows the title of the binary event. BI_Maintenance 0→1 shows the state change of binary input, including binary input name, original state and final state. 8.4.7 Display Device Logs This device can store 1024 pieces of device logs. Please refer to section “8.5.3” for LCD operation 8-38 PCS-902 Line Distance Relay Date: 2019-03-01 8 Human Machine Interface 4. Device Logs NO.4 2008-11-28 10:18:47:569ms Reboot Device Logs NO. 4 shows the title and the number of the device log 2008-11-28 10:18:47:569 shows date and time when the report occurred, the format is year–month-date and hour:minute:second:millisecond Reboot shows the manipulation content of the device log User operating information listed below may be displayed. Table 8.4-2 User operating event list No. Message Description 1 Reboot The device has been reboot. 2 Settings_Chgd The device′s settings have been changed. 3 ActiveGrp_Chgd Active setting group has been changed. 4 Report_Cleared All reports have been deleted. (Device logs can not be deleted) 5 Waveform_Cleared All waveforms have been deleted. 6 Process_Exit A process has exited. 7 Counter_Cleared Clear counter It will be displayed on LCD before disturbance records and supervision events are confirmed. Only pressing both “ENT” and “ESC” at the same time can switch among disturbance records, supervision events and the normal running state of the device to display it. IO events will be displayed for 5s and then it will return to the previous display interface automatically. 8.5 Keypad Operation 8.5.1 View Device Measurements The operation is as follows: 1. Press the “▲” to enter the main menu; 2. Press the “▲” or “▼” to move the cursor to the “Measurements” menu, and then press PCS-902 Line Distance Relay 8-39 Date: 2019-03-01 8 Human Machine Interface the “ENT” or “►” to enter the menu; 3. Press the “▲” or “▼” to move the cursor to any command menu, and then press the “ENT” to enter the menu; 4. Press the “▲” or “▼” to page up/down (if all information cannot be displayed in one display screen, one screen can display 14 lines of information at most); 5. Press the “◄” or “►” to select pervious or next command menu; 6. Press the “ENT” or “ESC” to exit this menu (returning to the “Measurements” menu); 8.5.2 View Device Status The operation is as follows: 1. Press the key “▲” to enter the main menu. 2. Press the key “▲” or “▼” to move the cursor to the “Status” menu, and then press the “ENT” or “►” to enter the menu. 3. Press the key “▲” or “▼” to move the cursor to any command menu item, and then press the key “ENT” to enter the submenu. 4. Press the “▲” or “▼” to page up/down (if all information cannot be displayed in one display screen, one screen can display 14 lines of information at most). 5. Press the key “◄” or “►” to select pervious or next command menu. 6. Press the key “ENT” or “ESC” to exit this menu (returning to the “Status” menu). 8.5.3 View Device Records The operation is as follows: 1. Press the “▲” to enter the main menu; 2. Press the “▲” or “▼” to move the cursor to the “Records” menu, and then press the “ENT” or “►” to enter the menu; 3. Press the “▲” or “▼” to move the cursor to any command menu, and then press the “ENT” to enter the menu; 4. Press the “▲” or “▼” to page up/down; 5. Press the “+” or “-” to select pervious or next record; 6. Press the “◄” or “►” to select pervious or next command menu; 7. Press the “ENT” or “ESC” to exit this menu (returning to the “Records” menu); 8.5.4 Print Device Records The operation is as follows: 1. Press the “▲” to enter the main menu; 8-40 PCS-902 Line Distance Relay Date: 2019-03-01 8 Human Machine Interface 2. Press the “▲” or “▼” to move the cursor to the “Print” menu, and then press the “ENT” or “►” to enter the menu; 3. Press the “▲” or “▼” to move the cursor to any command menu, and then press the “ENT” to enter the menu; Selecting the “Disturb Records”, and then press the “+” or “-” to select pervious or next record. After pressing the key “ENT”, the LCD will display “Start Printing... ”, and then automatically exit this menu (returning to the menu “Print”). If the printer doesn’t complete its current print task and re-start it for printing, and the LCD will display “Printer Busy…”. Press the key “ESC” to exit this menu (returning to the menu “Print”). Selecting the command menu “Superv Events” or “IO Events”, and then press the key “▲” or “▼” to move the cursor. Press the “+” or “-” to select the starting and ending numbers of printing message. After pressing the key “ENT”, the LCD will display “Start Printing…”, and then automatically exit this menu (returning to the menu “Print”). Press the key “ESC” to exit this menu (returning to the menu “Print”). 4. If selecting the command menu “Device Info”, “Device Status“ or “IEC103 Info”, press the key “ENT”, the LCD will display “Start printing..”, and then automatically exit this menu (returning to the menu “Print”). 5. If selecting the “Settings”, press the key “ENT” or “►” to enter the next level of menu. 6. After entering the submenu “Settings”, press the key “▲” or “▼” to move the cursor, and then press the key “ENT” to print the corresponding default value. If selecting any item to printing: Press the key “+” or “-” to select the setting group to be printed. After pressing the key “ENT”, the LCD will display “Start Printing…”, and then automatically exit this menu (returning to the menu “Settings”). Press the key “ESC” to exit this menu (returning to the menu “Settings”). 7. After entering the submenu “Waveforms”, press the “+” or “-” to select the waveform item to be printed and press ”ENT” to enter. If there is no any waveform data, the LCD will display “No Waveform Data!” (Before executing the command menu “Waveforms”, it is necessary to execute the command menu “Trig Oscillograph” in the menu “Local Cmd”, otherwise the LCD will display “No Waveform Data!”). With waveform data existing: Press the key “+” or “-” to select pervious or next record. After pressing the key “ENT”, the LCD will display “Start Printing…”, and then automatically exit this menu (returning to the menu “Waveforms”). If the printer does not complete its current print task and re-start it for printing, and the LCD will display “Printer Busy…”. Press the key “ESC” to exit this menu (returning to the menu “Waveforms”). 8.5.5 View Device Setting The operation is as follows: PCS-902 Line Distance Relay 8-41 Date: 2019-03-01 8 Human Machine Interface 1. Press the “▲” to enter the main menu; 2. Press the “▲” or “▼” to move the cursor to the “Settings” menu, and then press the “ENT” or “►” to enter the menu; 3. Press the “▲” or “▼” to move the cursor to any command menu, and then press the “ENT” to enter the menu; 4. Press the “▲” or “▼” to move the cursor; 5. Press the “+” or “-” to page up/down; 6. Press the “◄” or “►” to select pervious or next command menu; 7. Press the “ESC” to exit this menu (returning to the menu “Settings”). NOTICE! If the displayed information exceeds 14 lines, the scroll bar will appear on the right side of the LCD to indicate the quantity of all displayed information of the command menu and the relative location of information where the current cursor points at. 8.5.6 Modify Device Setting The operation is as follows: 1. Press the “▲” to enter the main menu; 2. Press the “▲” or “▼” to move the cursor to the “Settings” menu, and then press the “ENT” or “►” to enter the menu; 3. Press the “▲” or “▼” to move the cursor to any command menu, and then press the “ENT” to enter the menu; 4. Press the “▲” or “▼” to move the cursor; 5. Press the “+” or “-” to page up/down; 6. Press the “◄” or “►” to select pervious or next command menu; 7. Press the “ESC” to exit this menu (returning to the menu “Settings” ); 8. If selecting the command menu “System Settings”, move the cursor to the setting item to be modified, and then press the “ENT”; Press the “+” or “-” to modify the value (if the modified value is of multi-bit, press the “◄” or “►” to move the cursor to the digit bit, and then press the “+” or “-” to modify the value), press the “ESC” to cancel the modification and return to the displayed interface of the command menu “System Settings”. Press the “ENT” to automatically exit this menu (returning to the displayed interface of the command menu “System Settings”). Move the cursor to continue modifying other setting items. After all setting values are modified, press the “◄”, “►” or “ESC”, and the LCD will display “Save or Not?”. Directly press the “ESC” or press the “◄” or “►” to move the cursor. Select the “Cancel”, and then press the “ENT” to 8-42 PCS-902 Line Distance Relay Date: 2019-03-01 8 Human Machine Interface automatically exit this menu (returning to the displayed interface of the command menu “System Settings”). Press the “◄” or “►” to move the cursor. Select “No” and press the “ENT”, all modified setting item will restore to its original value, exit this menu (returning to the menu “Settings”). Press the “◄” or “►” to move the cursor to select “Yes”, and then press the “ENT”, the LCD will display password input interface. Password: ____ Input a 4-bit password (“+”, “◄”, “▲” and “-”). If the password is incorrect, continue inputting it, and then press the “ESC” to exit the password input interface and return to the displayed interface of the command menu “System Settings”. If the password is correct, LCD will display “Save Setting Now…”, and then exit this menu (returning to the displayed interface of the command menu “System Settings”), with all modified setting items as modified values. NOTICE! For different setting items, their displayed interfaces are different but their modification methods are the same. The following is ditto. 9. If selecting the submenu “Prot Settings”, and press “ENT” to enter. After selecting different command menu, the LCD will display the following interface: (take “FD Settings” as an example) PCS-902 Line Distance Relay 8-43 Date: 2019-03-01 8 Human Machine Interface FD Settings Please Select Group for Config Active Group: 01 Selected Group: 02 Press the “+” or “-” to modify the value, and then press the “ENT” to enter it. Move the cursor to the setting item to be modified, press the “ENT” to enter. Take the setting [FD.DPFC.I_Set] as an example is selected to modify, then press the “ENT” to enter and the LCD will display the following interface. Press “+” or “-” to modify the value and then press the “ENT” to confirm. FD.DPFC.I_Set Current Value 0.200 Modified Value 0.202 Min Value 0.050 Max Value 30.000 NOTICE! After modifying protection settings in current active setting group or system parameters of the device, the “HEALTHY” LED indicator the device will be lit off, and the MON module will check the new settings. If the abnormality is detected during the setting check, corresponding alarm signals will be issued. Moreover, if the critical error is detected, the device will be blocked. 8-44 PCS-902 Line Distance Relay Date: 2019-03-01 8 Human Machine Interface 8.5.7 Copy Device Setting The operation is as follows: 1. Press the “▲” to enter the main menu; 2. Press the “▲” or “▼” to move the cursor to the “Settings” menu, and then press the “ENT” or “►” to enter the menu; 3. Press the “▲” or “▼” to move the cursor to the command menu “Copy Settings”, and then press the “ENT” to enter the menu. Copy Settings Active Group: 01 Copy To Group: 02 Press the “+” or “-” to modify the value. Press the “ESC”, and return to the menu “Settings”. Press the “ENT”, the LCD will display the interface for password input, if the password is incorrect, continue inputting it, press the “ESC” to exit the password input interface and return to the menu “Settings”. If the password is correct, the LCD will display “Settings Copied!”, and exit this menu (returning to the menu “Settings”). 8.5.8 Switch Setting Group The operation is as follows: 1. Exit the main menu; 2. Press the “GRP” PCS-902 Line Distance Relay 8-45 Date: 2019-03-01 8 Human Machine Interface Change Active Group Active Group: 01 Change To Group: 02 Press the “+” or “-” to modify the value, and then press the “ESC” to exit this menu (returning to the main menu). After pressing the “ENT”, the LCD will display the password input interface. If the password is incorrect, continue inputting it, and then press the “ESC” to exit the password input interface and return to its original state. If the password is correct, the “HEALTHY” indicator lamp of the protection device will go out, and the protection device will re-check the protection setting. If the check doesn’t pass, the protection device will be blocked. If the check is successful, the LCD will return to its original state. 8.5.9 Delete Device Records The operation is as follows: 1. Exit the main menu; 2. Press the “+”, “-”, “+”, “-” and “ENT”; Press the “ESC” to exit this menu (returning to the original state). Press the “ENT” to carry out the deletion. Press <ENT> To Clear Press <ESC> To Exit 8-46 PCS-902 Line Distance Relay Date: 2019-03-01 8 Human Machine Interface NOTICE! The operation of deleting device message will delete all messages saved by the protection device, including disturbance records, supervision events, binary events, but not including device logs. Furthermore, the message is irrecoverable after deletion, so the application of the function shall be cautious. 8.5.10 Remote Control via Menu Control operation method is introduced as below: 1. Press the key “▲” to enter the main menu. 2. Press the key “▲” or “▼” to move the cursor to the command menu “Local Cmd”, and then press the key “ENT” to enter submenus. Press the key “▲” or “▼” to move the cursor to the command menu “Control”, and then press the key “ENT” to enter and the following display will be shown on LCD. Password: 000 Input a 3-bit password (“111”). If the password is incorrect, continue inputting it, and then press the “ESC” to exit the password input interface and return to the displayed interface of the command menu “Control”. If the password is correct, it will go to the following step. 3. Press the key “▲” or “▼” to move the cursor to the control object and press the key “ENT” to select control object. PCS-902 Line Distance Relay 8-47 Date: 2019-03-01 8 Human Machine Interface Control 4. 1. Step1: select Control Object CSWI01 2. CSWI02 3. CSWI03 4. CSWI04 5. CSWI05 6. CSWI06 7. CSWI07 8. CSWI08 9. CSWI09 10. CSWI10 Press the key “◄” or “►” to select control command press the key “ENT” to the next step. Three control commands are optional: 1) Open (Lower): Remote open 2) Close (Raise): Remote close 3) (Stop): Reserved CSWI01 Step2: select Control Command Open(Lower) Close(Raise) NoCheck SynchroCheck LoopCheck EF Line Selection InterlockChk InterlockNotChk Select Execute (Stop) DeadCheck Cancel Result 5. Press the key “◄” or “►” to select synchronism check mode and press the key “ENT” to the next step. Five synchronism check modes are optional: 1) NoCheck: Without any check 2) SynchroCheck: Synchronism-check mode 8-48 PCS-902 Line Distance Relay Date: 2019-03-01 8 Human Machine Interface 3) DeadCheck: Dead check mode 4) LoopCheck: Reserved 5) EF Line Selection: Reserved CSWI01 Step3: select Execution Condition Open(Lower) Close(Raise) NoCheck SynchroCheck LoopCheck EF Line Selection InterlockChk InterlockNotChk Select Execute (Stop) DeadCheck Cancel Result 6. Press the key “◄” or “►” to select interlock mode and press the key “ENT” to next step. Two interlock check modes are optional: 1) InterlockChk: Check interlocking criteria 2) InterlockNotChk: Not check interlocking criteria CSWI01 Step4: select Interlock Condition Open(Lower) Close(Raise) NoCheck SynchroCheck LoopCheck EF Line Selection InterlockChk InterLockNotChk Select Execute (Stop) DeadCheck Cancel Result 7. Press the key “◄” or “►” to select control type and press the key “ENT”. As shown in the following figure, operation results will be shown after “Result” at the bottom of the LCD. PCS-902 Line Distance Relay 8-49 Date: 2019-03-01 8 Human Machine Interface Three synchronism control types are optional: 1) Select: Select control object 2) Execute: Execute control operation 3) Cancel: Cancel control operation CSWI01 Step5: select Control Type Open(Lower) Close(Raise) NoCheck SynchroCheck LoopCheck EF Line Selection InterlockChk InterLockNotChk Select Execute (Stop) DeadCheck Cancel Result NOTICE! “Execute” operation must be operated after “Select” operation. 8.5.11 Remote Control via SLD The control operation (close or open) also can be executed on the single line diagram (SLD) of the default display under normal operation condition. The signs of the circuit breaker (abbreviated as CB) and switch (DS or ES) are listed in the following table. Table 8.5-1 Primary equipment symbols in SLD Sign Explanation Sign Explanation Position of CB: Open Position of switch: Open Position of CB: Closed Position of switch: Closed ? Position of CB: Intermediate state ? Position of switch: Intermediate state × Position of CB: Bad state × Position of switch: Bad state An example of normal display with SLD is shown in the following figure. The single line diagram of the default display on the LCD is shown as below when the device is in normal situation, if this device adopts the single line diagram as default display. 8-50 PCS-902 Line Distance Relay Date: 2019-03-01 8 Human Machine Interface S Addr:150 2008-11-28 10:10:00 Group 01 Bus1 Bus2 M011 M0112 M0131 M01 M0151 M0171 Feeder M01 In SLD display, press "▲" or "▼" to select a switchgear to be opened/closed, and then press key "ENT" to control selected CB/switch. After the selection of an open or close operation, the confirmation window will be valid for a short duration after inputting the correct control password. This password is configurable by the setting [Ctrl_Password] in the menu “Device Settings”. A control operation result of success or fail will be returned at last. 1) The selected object will be framed in a dotted line. Step 1: Select the control object 2) Note: From the last step, press “ENT” to popup this operation selection window. PCS-902 Line Distance Relay 8-51 Date: 2019-03-01 8 Human Machine Interface Step 1: Select the control object CSWI** Open 3) Close Consult or modify the password through [Ctrl_Password] in "Device Settings". Step 3: Enter the control password CSWI** open/close Password: xxx 4) Use "←", "→" and "ENT" to confirm or cancel the control operation. 8-52 PCS-902 Line Distance Relay Date: 2019-03-01 8 Human Machine Interface Step 4: Confirm/Cancel the control operation CSWI** open/close Open 5) Close Check the operation success or fail result from the control report. Step 5: Check the control operation result CSWI** open/close Op success (or Op fail) 8.5.12 Control with Open/Close Buttons (if Available) In SLD display, press "▲" or "▼" to select a switchgear to be opened/closed, and then press key "ENT" to control selected CB/switch. Press the open or close button on the HMI panel and the confirmation window will be valid for a short duration after inputting the correct control password. This password is configurable by the setting [Ctrl_Password] in the menu “Device Settings”. A control operation result of success or fail will be returned at last. 1) The selected object will be framed in a dotted line. PCS-902 Line Distance Relay 8-53 Date: 2019-03-01 8 Human Machine Interface Step 1: Select the control object 2) From the last step, press a control button to popup this window. Consult or modify the password through [Ctrl_Password] in "Device Settings". Step 3: Enter the control password CSWI** open/close Password: xxx 3) Use "←", "→" and "ENT" to confirm or cancel the control operation. 8-54 PCS-902 Line Distance Relay Date: 2019-03-01 8 Human Machine Interface Step 4: Confirm/Cancel the control operation CSWI** open/close Open 4) Close Check the operation success or fail result from the control report. Step 5: Check the control operation result CSWI** open/close Op success (or Op fail) 8.5.13 Modify Device Clock The operation is as follows: 1. Press the “▲” to enter the main menu; 2. Press the “▲” or “▼” to move the cursor to the “Clock” menu, and then press the “ENT” to enter clock display 3. Press the “▲” or “▼” to move the cursor to the date or time to be modified; 4. Press the “+” or “-” to modify value, and then press the “ENT” to save the modification and return to the main menu; 5. Press the “ESC” to cancel the modification and return to the main menu. PCS-902 Line Distance Relay 8-55 Date: 2019-03-01 8 Human Machine Interface NOTICE! Move the cursor to select the item “Format” to setup time display format. Press the “+” or “-” to modify from the following options. 1. YYYY-MM-DD (Default display format) 2. YYYY/MM/dd 3. DD-MM-YYYY 4. DD/MM/YYYY 5. MM-DD-YYYY 6. MM/DD/YYYY Clock Year: 2008 Month: 11 Day: 28 Hour: 20 Minute: 59 Format: YYYY/MM/DD 8.5.14 View Module Information The operation is as follows: 1. Press the “▲” to enter the main menu; 2. Press the “▲” or “▼” to move the cursor to the “Information” menu, and then press the “ENT” or “►” to enter the menu; 3. Press the “▲” or “▼” to move the cursor to the command menu “Board Info”, and then press the “ENT” to enter the menu; 4. Press the “▲” or “▼” to move the scroll bar; 5. Press the “ENT” or “ESC” to exit this menu (returning to the “Information” menu). 8.5.15 Check Software Version The operation is as follows: 1. Press the “▲” to enter the main menu. 8-56 PCS-902 Line Distance Relay Date: 2019-03-01 8 Human Machine Interface 2. Press the “▲” or “▼” to move the cursor to the “Information” menu, and then press the “ENT” to enter the submenu. 3. Press the key “▲” or “▼” to move the cursor to the command menu “Version Info”, and then press the key “ENT” to display the software version. 4. Press the “ESC” to return to the main menu. 8.5.16 Communication Test The operation is as follows: 1. Press the key “▲” to enter the main menu. 2. Press the key “▲” or “▼” to move the cursor to the “Test” menu, and then press the key “ENT” or “►” to enter the menu. 3. Press the key “▲” or “▼” to move the cursor to the submenu “Device Test”, and then press the key “ENT” to enter the submenu, to select test item. If “Disturb Events” “Superv Events” or “IO Events” is selected, two options “All Test” and “Select Test” are provided. 4. Press the key “▲” or “▼” to move the cursor to select the corresponding command menu “All Test” or “Select Test”. If selecting the “All Test”, press the “ENT”, and the device will successively carry out all operation element message test one by one. 5. If “Select Test” is selected, press the key “ENT”. Press the “+” or “-” to page up/down, and then press the key “▲” or “▼” to move the scroll bar. Move the cursor to select the corresponding protection element. Press the key “ENT” to execute the communication test of this protection element, the substation automatic system (SAS) will receive the corresponding message. NOTICE! If no input operation is carried out within 60s, exit the communication transmission and return to the “Test” menu, at this moment, the LCD will display “Communication Test Timeout and Exiting...”. Press the key “ESC” to exit this menu (returning to the menu “Test”, at this moment, the LCD will display “Communication Test Exiting…”. 8.5.17 Select Language The operation is as follows: 1. Press the key “▲” to enter the main menu. 2. Press the key “▲” or “▼” to move the cursor to the command menu “Language”, and then press the key “ENT” to enter the menu and the following display will be shown on LCD. PCS-902 Line Distance Relay 8-57 Date: 2019-03-01 8 Human Machine Interface Please Select Language: 1 中文 2 English 3 XXXX Third language selected by the user 3. Press the key “▲” or “▼” to move the cursor to the language user preferred and press the key “ENT” to execute language switching. After language switching is finished, LCD will return to the menu “Language”, and the display language is changed. Otherwise, press the key “ESC” to cancel language switching and return to the menu “Language”. NOTICE! LCD interface provided in this chapter is only a reference and available for explaining specific definition of LCD. The displayed interface of the actual device may be some different from it, so you shall be subject to the actual protection device. 8-58 PCS-902 Line Distance Relay Date: 2019-03-01 9 Configurable Function 9 Configurable Function Table of Contents 9 Configurable Function ...................................................................... 9-a 9.1 Overview .......................................................................................................... 9-1 9.2 Introduction on PCS-Explorer Software ........................................................ 9-1 9.3 Signal List ........................................................................................................ 9-2 9.3.1 Input Signal .......................................................................................................................... 9-2 9.3.2 Output Signal ..................................................................................................................... 9-22 List of Tables Table 9.3-1 Input signals ............................................................................................................. 9-2 Table 9.3-2 Output signals ........................................................................................................ 9-22 PCS-902 Line Distance Relay 9-a Date: 2019-03-01 9 Configurable Function 9-b PCS-902 Line Distance Relay Date: 2019-03-01 9 Configurable Function 9.1 Overview By adoption of PCS-Explorer software, it is able to make device configuration, function configuration, LCD configuration, binary input and binary output configuration, LED indicator configuration and programming logic for PCS-902. 9.2 Introduction on PCS-Explorer Software PCS-Explorer software is developed in order to meet customer’s demand on functions of UAPC platform device such as device configuration and programmable design. It selects substation as the core of data management and the device as fundamental unit, supporting one substation to govern many devices. The software provides on-line and off-line functions: on-line mode: Ethernet connected with the device supporting IEC60870-5-103 and capable of uploading and downloading configuration files through Ethernet net; off-line mode: off-line setting configuration. In addition, it also supports programmable logic to meet customer’s demand. After function configuration is finished, disabled protection function will be hidden in the device and in setting configuration list of PCS-Explorer Software. The user can select to show or hide some setting by this way, and modify the setting value. Please refer to the instruction manual “PCS-Explorer Auxiliary Software” for details. Overall functions: Programmable logic Device configuration Function configuration LCD configuration LED indicators configuration Binary signals configuration Setting configuration Real-time display of analogue and digital quantity of device Display of sequence of report (SOE) Analysis of waveform File downloading/uploading LCD function shortcut keys configuration DNP communication information map configuration Export RIO file PCS-902 Line Distance Relay 9-1 Date: 2019-03-01 9 Configurable Function Multi-user access authority management 9.3 Signal List If an input signal or output signal is gray in PCS-Explorer, it means that the input signal or output signal is not configurable. Otherwise, it is configurable signal. NOTICE! PCS-902 can be configured to support single circuit breaker application or double circuit breakers application by PCS-Explorer. The prefix “CBx.” is added to all signals for circuit breaker No.x (x=1 or 2). The related protection functions include circuit breaker position supervision, breaker failure protection, dead zone protection, pole discrepancy protection, synchrocheck, automatic reclosure, trip logic, CT circuit supervision, control and synchrocheck for manual closing. 9.3.1 Input Signal All input signals of this device are listed in the following table. Table 9.3-1 Input signals No. Item Description Circuit breaker position supervision 1 CBx.52b_PhA Normally closed contact of A-phase of circuit breaker No.x 2 CBx.52b_PhB Normally closed contact of B-phase of circuit breaker No.x 3 CBx.52b_PhC Normally closed contact of C-phase of circuit breaker No.x Maintenance status binary input of circuit breaker No.x If any circuit breaker is in maintenance and out of service, CBx.52b or 4 CBx.Test CBx.Test should be set as “1” in fixed, and CB No.x will be not take effect in corresponding protection logics. (CB position supervision is still kept.) It is only available for double circuit breakers mode. External manual closing binary input of circuit breaker No.x, it is only 5 CBx.ManCls 6 CBx.52b Normally closed contact of three-phase of circuit breaker No.x 7 CBx.52a Normally open contact of three-phase of circuit breaker No.x applied to SOTF logic Control circuit failure of circuit breaker No.x (normally closed contacts of 8 CBx.TCCS.Input tripping position (52b) and closing position (52a) of three-phase circuit breaker are all de-energized due to DC power loss of control circuit) Auxiliary element 9 AuxE.OCD.En 10 AuxE.OCD.Blk 11 AuxE.ROC1.En Current change auxiliary element enabling input, it is triggered from binary input or programmable logic etc. Current change auxiliary element blocking input, it is triggered from binary input or programmable logic etc. Stage 1 of residual current auxiliary element enabling input, it is triggered from binary input or programmable logic etc. 9-2 PCS-902 Line Distance Relay Date: 2019-03-01 9 Configurable Function No. Item 12 AuxE.ROC1.Blk 13 AuxE.ROC2.En 14 AuxE.ROC2.Blk 15 AuxE.ROC3.En 16 AuxE.ROC3.Blk 17 AuxE.OC1.En 18 AuxE.OC1.Blk 19 AuxE.OC2.En 20 AuxE.OC2.Blk 21 AuxE.OC3.En 22 AuxE.OC3.Blk 23 AuxE.UVD.En 24 AuxE.UVD.Blk 25 AuxE.UVG.En 26 AuxE.UVG.Blk 27 AuxE.UVS.En 28 AuxE.UVS.Blk 29 AuxE.ROV.En 30 AuxE.ROV.Blk Description Stage 1 of residual current auxiliary element blocking input, it is triggered from binary input or programmable logic etc. Stage 2 of residual current auxiliary element enabling input, it is triggered from binary input or programmable logic etc. Stage 2 of residual current auxiliary element blocking input, it is triggered from binary input or programmable logic etc. Stage 3 of residual current auxiliary element enabling input, it is triggered from binary input or programmable logic etc. Stage 3 of residual current auxiliary element blocking input, it is triggered from binary input or programmable logic etc. Stage 1 of phase current auxiliary element enabling input, it is triggered from binary input or programmable logic etc. Stage 1 of phase current auxiliary element blocking input, it is triggered from binary input or programmable logic etc. Stage 2 of phase current auxiliary element enabling input, it is triggered from binary input or programmable logic etc. Stage 2 of phase current auxiliary element blocking input, it is triggered from binary input or programmable logic etc. Stage 3 of phase current auxiliary element enabling input, it is triggered from binary input or programmable logic etc. Stage 3 of phase current auxiliary element blocking input, it is triggered from binary input or programmable logic etc. Voltage change auxiliary element enabling input, it is triggered from binary input or programmable logic etc. Voltage change auxiliary element blocking input, it is triggered from binary input or programmable logic etc. Phase-to-ground under voltage auxiliary element enabling input, it is triggered from binary input or programmable logic etc. Phase-to-ground under voltage auxiliary element blocking input, it is triggered from binary input or programmable logic etc. Phase-to-phase under voltage auxiliary element enabling input, it is triggered from binary input or programmable logic etc. Phase-to-phase under voltage auxiliary element blocking input, it is triggered from binary input or programmable logic etc. Residual voltage auxiliary element enabling input, it is triggered from binary input or programmable logic etc. Residual voltage auxiliary element blocking input, it is triggered from binary input or programmable logic etc. Distance protection 31 21D.En 32 21D.Blk DPFC distance protection enabling input, it is triggered from binary input or programmable logic etc. DPFC distance protection blocking input, it is triggered from binary input PCS-902 Line Distance Relay 9-3 Date: 2019-03-01 9 Configurable Function No. Item Description or programmable logic etc. Load trapezoid characteristic enabling input, it is triggered from binary 33 LoadEnch.En 34 LoadEnch.Blk 35 21.En 36 21.Blk 37 21M1.ZG.En 38 21M1.ZG.Blk 39 21M1.ZP.En 40 21M1.ZP.Blk 41 21M1.En_Instant 42 21M2.ZG.En 43 21M2.ZG.Blk 44 21M2.ZP.En 45 21M2.ZP.Blk 46 21M2.En_ShortDly Enable accelerating zone 2 of distance protection 47 21M2.Blk_ShortDly Accelerating zone 2 of distance protection is disabled 48 21M3.ZG.En 49 21M3.ZG.Blk 50 21M3.ZP.En 51 21M3.ZP.Blk 52 21M3.En_ShortDly Enable accelerating zone 3 of distance protection 53 21M3.Blk_ShortDly Accelerating zone 3 of distance protection is disabled 54 21M4.ZG.En 55 21M4.ZG.Blk input or programmable logic etc. Load trapezoid characteristic blocking input, it is triggered from binary input or programmable logic etc. Distance protection enabling input, it is triggered from binary input or programmable logic etc. Distance protection blocking input, it is triggered from binary input or programmable logic etc. Zone 1 of phase-to-ground distance protection enabling input, default value is “1” Zone 1 of phase-to-ground distance protection blocking input, default value is “0” Zone 1 of phase-to-phase distance protection enabling input, default value is “1” Zone 1 of phase-to-phase distance protection blocking input, default value is “0” Enable zone 1 of distance protection operates without time delay Zone 2 of phase-to-ground distance protection enabling input, default value is “1” Zone 2 of phase-to-ground distance protection blocking input, default value is “0” Zone 2 of phase-to-phase distance protection enabling input, default value is “1” Zone 2 of phase-to-phase distance protection blocking input, default value is “0” Zone 3 of phase-to-ground distance protection enabling input, default value is “1” Zone 3 of phase-to-ground distance protection blocking input, default value is “0” Zone 3 of phase-to-phase distance protection enabling input, default value is “1” Zone 3 of phase-to-phase distance protection blocking input, default value is “0” Zone 4 of phase-to-ground distance protection enabling input, default value is “1” Zone 4 of phase-to-ground distance protection blocking input, default value is “0” 9-4 PCS-902 Line Distance Relay Date: 2019-03-01 9 Configurable Function No. Item Description Zone 4 of phase-to-phase distance protection enabling input, default 56 21M4.ZP.En 57 21M4.ZP.Blk 58 21M4.En_ShortDly Enable accelerating zone 4 of distance protection 59 21M4.Blk_ShortDly Accelerating zone 4 of distance protection is disabled 60 21M5.ZG.En 61 21M5.ZG.Blk 62 21M5.ZP.En 63 21M5.ZP.Blk 64 21M5.En_ShortDly Enable accelerating zone 5 of distance protection 65 21M5.Blk_ShortDly Accelerating zone 5 of distance protection is disabled 66 21Q1.ZG.En 67 21Q1.ZG.Blk 68 21Q1.ZP.En 69 21Q1.ZP.Blk 70 21Q1.En_Instant 71 21Q2.ZG.En 72 21Q2.ZG.Blk 73 21Q2.ZP.En 74 21Q2.ZP.Blk 75 21Q2.En_ShortDly Enable accelerating zone 2 of distance protection 76 21Q2.Blk_ShortDly Accelerating zone 2 of distance protection is disabled 77 21Q3.ZG.En 78 21Q3.ZG.Blk 79 21Q3.ZP.En 80 21Q3.ZP.Blk value is “1” Zone 4 of phase-to-phase distance protection blocking input, default value is “0” Zone 5 of phase-to-ground distance protection enabling input, default value is “1” Zone 5 of phase-to-ground distance protection blocking input, default value is “0” Zone 5 of phase-to-phase distance protection enabling input, default value is “1” Zone 5 of phase-to-phase distance protection blocking input, default value is “0” Zone 1 of phase-to-ground distance protection enabling input, default value is “1” Zone 1 of phase-to-ground distance protection blocking input, default value is “0” Zone 1 of phase-to-phase distance protection enabling input, default value is “1” Zone 1 of phase-to-phase distance protection blocking input, default value is “0” Enable zone 1 of distance protection operates without time delay Zone 2 of phase-to-ground distance protection enabling input, default value is “1” Zone 2 of phase-to-ground distance protection blocking input, default value is “0” Zone 2 of phase-to-phase distance protection enabling input, default value is “1” Zone 2 of phase-to-phase distance protection blocking input, default value is “0” Zone 3 of phase-to-ground distance protection enabling input, default value is “1” (x=1, 2, 3, 4, 5) Zone 3 of phase-to-ground distance protection blocking input, default value is “0” (x=1, 2, 3, 4, 5) Zone 3 of phase-to-phase distance protection enabling input, default value is “1” (x=1, 2, 3, 4, 5) Zone 3 of phase-to-phase distance protection blocking input, default PCS-902 Line Distance Relay 9-5 Date: 2019-03-01 9 Configurable Function No. Item Description value is “0” (x=1, 2, 3, 4, 5) 81 21Q3.En_ShortDly Enable accelerating zone 3 of distance protection (x=2, 3, 4, 5) 82 21Q3.Blk_ShortDly Accelerating zone 3 of distance protection is disabled (x=2, 3, 4, 5) 83 21Q4.ZG.En 84 21Q4.ZG.Blk 85 21Q4.ZP.En 86 21Q4.ZP.Blk 87 21Q4.En_ShortDly Enable accelerating zone 4 of distance protection 88 21Q4.Blk_ShortDly Accelerating zone 4 of distance protection is disabled 89 21Q5.ZG.En 90 21Q5.ZG.Blk 91 21Q5.ZP.En 92 21Q5.ZP.Blk 93 21Q5.En_ShortDly Enable accelerating zone 5 of distance protection 94 21Q5.Blk_ShortDly Accelerating zone 5 of distance protection is disabled 95 78.En 96 78.Blk 97 78.Clr_Counter Clear the counter 98 21M1.En_PSBR Enabling power swing blocking releasing of zone 1 (Mho characteristic) 99 21Q1.En_PSBR Enabling power swing blocking releasing of zone 1 (Quad characteristic) 100 21M1.Blk_PSBR Blocking power swing blocking releasing of zone 1 (Mho characteristic) 101 21Q1.Blk_PSBR Blocking power swing blocking releasing of zone 1 (Quad characteristic) 102 21M2.En_PSBR Enabling power swing blocking releasing of zone 2 (Mho characteristic) 103 21Q2.En_PSBR Enabling power swing blocking releasing of zone 2 (Quad characteristic) 104 21M2.Blk_PSBR Blocking power swing blocking releasing of zone 2 (Mho characteristic) 105 21Q2.Blk_PSBR Blocking power swing blocking releasing of zone 2 (Quad characteristic) 106 21M3.En_PSBR Enabling power swing blocking releasing of zone 3 (Mho characteristic) 107 21Q3.En_PSBR Enabling power swing blocking releasing of zone 3 (Quad characteristic) 108 21M3.Blk_PSBR Blocking power swing blocking releasing of zone 3 (Mho characteristic) 109 21Q3.Blk_PSBR Blocking power swing blocking releasing of zone 3 (Quad characteristic) 110 21M4.En_PSBR Enabling power swing blocking releasing of zone 4 (Mho characteristic) 111 21Q4.En_PSBR Enabling power swing blocking releasing of zone 4 (Quad characteristic) Zone 4 of phase-to-ground distance protection enabling input, default value is “1” Zone 4 of phase-to-ground distance protection blocking input, default value is “0” Zone 4 of phase-to-phase distance protection enabling input, default value is “1” Zone 4 of phase-to-phase distance protection blocking input, default value is “0” Zone 5 of phase-to-ground distance protection enabling input, default value is “1” Zone 5 of phase-to-ground distance protection blocking input, default value is “0” Zone 5 of phase-to-phase distance protection enabling input, default value is “1” Zone 5 of phase-to-phase distance protection blocking input, default value is “0” Out-of-step protection enabling input, it is triggered from binary input or programmable logic etc. Out-of-step protection blocking input, it is triggered from binary input or programmable logic etc. 9-6 PCS-902 Line Distance Relay Date: 2019-03-01 9 Configurable Function No. Item Description 112 21M4.Blk_PSBR Blocking power swing blocking releasing of zone 4 (Mho characteristic) 113 21Q4.Blk_PSBR Blocking power swing blocking releasing of zone 4 (Quad characteristic) 114 21M5.En_PSBR Enabling power swing blocking releasing of zone 5 (Mho characteristic) 115 21Q5.En_PSBR Enabling power swing blocking releasing of zone 5 (Quad characteristic) 116 21M5.Blk_PSBR Blocking power swing blocking releasing of zone 5 (Mho characteristic) 117 21Q5.Blk_PSBR Blocking power swing blocking releasing of zone 5 (Quad characteristic) 118 21M.Pilot.En_PSBR 119 21M.Pilot.Blk_PSBR 120 21Q.Pilot.En_PSBR 121 21Q.Pilot.Blk_PSBR 122 21SOTF.En 123 21SOTF.Blk Enabling power swing blocking releasing of pilot distance zone (Mho characteristic) Blocking power swing blocking releasing of pilot distance zone (Mho characteristic) Enabling power swing blocking releasing of pilot distance zone (Quad characteristic) Blocking power swing blocking releasing of pilot distance zone (Quad characteristic) Distance SOTF protection enabling input, it is triggered from binary input or programmable logic etc. Distance SOTF protection blocking input, it is triggered from binary input or programmable logic etc. Optical pilot channel 124 FOx.En Enabling channel x 125 FOx.Send1 Sending signal 1 of channel x 126 FOx.Send2 Sending signal 2 of channel x 127 FOx.Send3 Sending signal 3 of channel x 128 FOx.Send4 Sending signal 4 of channel x 129 FOx.Send5 Sending signal 5 of channel x 130 FOx.Send6 Sending signal 6 of channel x 131 FOx.Send7 Sending signal 7 of channel x 132 FOx.Send8 Sending signal 8 of channel x Sending signal 9 of channel x (it is configured by fault as sending 133 FOx.Send9 permissive signal 1 or sending A-phase permissive signal (only for phase-segregated command scheme)) Sending signal 10 of channel x (it is configured by fault as sending 134 FOx.Send10 B-phase permissive signal (only for phase-segregated command scheme)) Sending signal 11 of channel x (it is configured by fault as sending 135 FOx.Send11 C-phase permissive signal (only for phase-segregated command scheme)) Sending signal 12 of channel x (it is configured by fault as sending 136 FOx.Send12 permissive signal 2 only for pilot directional earth-fault protection adopting independent pilot channel 2) Pilot distance protection and pilot directional earth-fault protection 137 85-x.Z.En1 Pilot distance protection x enabling input 1, it is triggered from binary PCS-902 Line Distance Relay 9-7 Date: 2019-03-01 9 Configurable Function No. Item Description input or programmable logic etc. (x=1 or 2) 138 85-x.Z.En2 139 85-x.Z.Blk 140 85-x.Abnor_Ch1 Pilot distance protection x enabling input 2, it is triggered from binary input or programmable logic etc. (x=1 or 2) Pilot distance protection x blocking input, it is triggered from binary input or programmable logic etc. (x=1 or 2) Input signal of indicating that pilot channel 1 is abnormal for pilot distance protection x (x=1 or 2) Input signal of receiving permissive signal via channel No.1 for pilot 141 85-x.Recv1 distance protection x, or input signal of receiving permissive signal of A-phase via channel No.1 for pilot distance protection x (only for phase-segregated command scheme, x=1 or 2) Input signal of receiving permissive signal of B-phase via channel No.1 142 85-x.RecvB for pilot distance protection x (only for phase-segregated command scheme, x=1 or 2) Input signal of receiving permissive signal of C-phase via channel No.1 143 85-x.RecvC for pilot distance protection x (only for phase-segregated command scheme, x=1 or 2) 144 85-x.ExTrp 145 85-x.Unblocking1 146 85-x.ZX.En1 147 85-x.ZX.En2 148 85-x.ZX.Blk1 149 85-x.ZX.Blk2 150 85-x.DEF.En1 151 85-x.DEF.En2 152 85-x.DEF.Blk 153 85-x.Abnor_Ch1 154 85-x.Abnor_Ch2 155 85-x.Recv1 156 85-x.Recv2 157 85-x.ExTrp Input signal of initiating sending permissive signal from external tripping signal for pilot distance protection x (x=1 or 2) Unblocking signal 1 of pilot distance protection x (x=1 or 2) Zone Extension enabling input 1 of pilot distance protection x, it is triggered from binary input or programmable logic etc. (x=1 or 2) Zone Extension enabling input 2 of pilot distance protection x, it is triggered from binary input or programmable logic etc. (x=1 or 2) Zone Extension blocking input 1 of pilot distance protection x, it is triggered from binary input or programmable logic etc. (x=1 or 2) Zone Extension blocking input 2 of pilot distance protection x, it is triggered from binary input or programmable logic etc. (x=1 or 2) Pilot directional earth-fault protection x enabling input 1, it is triggered from binary input or programmable logic etc. (x=1 or 2) Pilot directional earth-fault protection x enabling input 2, it is triggered from binary input or programmable logic etc. (x=1 or 2) Pilot directional earth-fault protection x blocking input, it is triggered from binary input or programmable logic etc. (x=1 or 2) Input signal of indicating that pilot channel 1 is abnormal for pilot directional earth-fault protection x (x=1 or 2) Input signal of indicating that pilot channel 2 is abnormal for pilot directional earth-fault protection x (x=1 or 2) Input signal of receiving permissive signal via channel 1 for pilot directional earth-fault protection x (x=1 or 2) Input signal of receiving permissive signal via channel 2 for pilot directional earth-fault protection x (x=1 or 2) Input signal of initiating sending permissive signal from external tripping 9-8 PCS-902 Line Distance Relay Date: 2019-03-01 9 Configurable Function No. Item Description signal (x=1 or 2) 158 85-x.Unblocking1 Unblocking signal 1 for pilot directional earth-fault protection x (x=1 or 2) 159 85-x.Unblocking2 Unblocking signal 2 for pilot directional earth-fault protection x (x=1 or 2) Phase overcurrent protection 160 50/51P1.En1 161 50/51P1.En2 162 50/51P1.Blk 163 50/51P2.En1 164 50/51P2.En2 165 50/51P2.Blk 166 50/51P3.En1 167 50/51P3.En2 168 50/51P3.Blk 169 50/51P4.En1 170 50/51P4.En2 171 50/51P4.Blk Stage 1 of phase overcurrent protection enabling input 1, it is triggered from binary input or programmable logic etc. Stage 1 of phase overcurrent protection enabling input 2, it is triggered from binary input or programmable logic etc. Stage 1 of phase overcurrent protection blocking input, it is triggered from binary input or programmable logic etc. Stage 2 of phase overcurrent protection enabling input 1, it is triggered from binary input or programmable logic etc. Stage 2 of phase overcurrent protection enabling input 2, it is triggered from binary input or programmable logic etc. Stage 2 of phase overcurrent protection blocking input, it is triggered from binary input or programmable logic etc. Stage 3 of phase overcurrent protection enabling input 1, it is triggered from binary input or programmable logic etc. Stage 3 of phase overcurrent protection enabling input 2, it is triggered from binary input or programmable logic etc. Stage 3 of phase overcurrent protection blocking input, it is triggered from binary input or programmable logic etc. Stage 4 of phase overcurrent protection enabling input 1, it is triggered from binary input or programmable logic etc. Stage 4 of phase overcurrent protection enabling input 2, it is triggered from binary input or programmable logic etc. Stage 4 of phase overcurrent protection blocking input, it is triggered from binary input or programmable logic etc. Earth fault protection 172 50/51G1.En1 173 50/51G1.En2 174 50/51G1.Blk 175 50/51G2.En1 176 50/51G2.En2 177 50/51G2.Blk 178 50/51G2.En_ShortDly Stage 1 of earth fault protection enabling input 1, it is triggered from binary input or programmable logic etc. Stage 1 of earth fault protection enabling input 2, it is triggered from binary input or programmable logic etc. Stage 1 of earth fault protection blocking input, it is triggered from binary input or programmable logic etc. Stage 2 of earth fault protection enabling input 1, it is triggered from binary input or programmable logic etc. Stage 2 of earth fault protection enabling input 2, it is triggered from binary input or programmable logic etc. Stage 2 of earth fault protection blocking input, it is triggered from binary input or programmable logic etc. Short time delay for stage 2 of earth fault protection enabling input, it is PCS-902 Line Distance Relay 9-9 Date: 2019-03-01 9 Configurable Function No. Item Description triggered from binary input or programmable logic etc. 179 50/51G2.Blk_ShortDly 180 50/51G3.En1 181 50/51G3.En2 182 50/51G3.Blk 183 50/51G3.En_ShortDly 184 50/51G3.Blk_ShortDly 185 50/51G4.En1 186 50/51G4.En2 187 50/51G4.Blk 188 50/51G4.En_ShortDly 189 50/51G4.Blk_ShortDly Short time delay for stage 2 of earth fault protection blocking input, it is triggered from binary input or programmable logic etc. Stage 3 of earth fault protection enabling input 1, it is triggered from binary input or programmable logic etc. Stage 3 of earth fault protection enabling input 2, it is triggered from binary input or programmable logic etc. Stage 3 of earth fault protection blocking input, it is triggered from binary input or programmable logic etc. Short time delay for stage 3 of earth fault protection enabling input, it is triggered from binary input or programmable logic etc. Short time delay for stage 3 of earth fault protection blocking input, it is triggered from binary input or programmable logic etc. Stage 4 of earth fault protection enabling input 1, it is triggered from binary input or programmable logic etc. Stage 4 of earth fault protection enabling input 2, it is triggered from binary input or programmable logic etc. Stage 4 of earth fault protection blocking input, it is triggered from binary input or programmable logic etc. Short time delay for stage 4 of earth fault protection enabling input, it is triggered from binary input or programmable logic etc. Short time delay for stage 4 of earth fault protection blocking input, it is triggered from binary input or programmable logic etc. Negative-sequence overcurrent protection 190 50/51Q1.En1 191 50/51Q1.En2 192 50/51Q1.Blk 193 50/51Q2.En1 194 50/51Q2.En2 195 50/51Q2.Blk 196 50/51Q3.En1 197 50/51Q3.En2 198 50/51Q3.Blk Stage 1 of negative-sequence overcurrent protection enabling input 1, it is triggered from binary input or programmable logic etc. Stage 1 of negative-sequence overcurrent protection enabling input 2, it is triggered from binary input or programmable logic etc. Stage 1 of negative-sequence overcurrent protection blocking input, it is triggered from binary input or programmable logic etc. Stage 2 of negative-sequence overcurrent protection enabling input 1, it is triggered from binary input or programmable logic etc. Stage 2 of negative-sequence overcurrent protection enabling input 2, it is triggered from binary input or programmable logic etc. Stage 2 of negative-sequence overcurrent protection blocking input, it is triggered from binary input or programmable logic etc. Stage 3 of negative-sequence overcurrent protection enabling input 1, it is triggered from binary input or programmable logic etc. Stage 3 of negative-sequence overcurrent protection enabling input 2, it is triggered from binary input or programmable logic etc. Stage 3 of negative-sequence overcurrent protection blocking input, it is triggered from binary input or programmable logic etc. 9-10 PCS-902 Line Distance Relay Date: 2019-03-01 9 Configurable Function No. Item 199 50/51Q4.En1 200 50/51Q4.En2 201 50/51Q4.Blk Description Stage 4 of negative-sequence overcurrent protection enabling input 1, it is triggered from binary input or programmable logic etc. Stage 4 of negative-sequence overcurrent protection enabling input 2, it is triggered from binary input or programmable logic etc. Stage 4 of negative-sequence overcurrent protection blocking input, it is triggered from binary input or programmable logic etc. Overcurrent protection for VT circuit failure 202 50PVT1.En1 203 50PVT1.En2 204 50PVT1.Blk 205 50PVT2.En1 206 50PVT2.En2 207 50PVT2.Blk 208 50GVT1.En1 209 50GVT1.En2 210 50GVT1.Blk 211 50GVT2.En1 212 50GVT2.En2 213 50GVT2.Blk Stage 1 of phase overcurrent protection for VT circuit failure enabling input 1, it is triggered from binary input or programmable logic etc. Stage 1 of phase overcurrent protection for VT circuit failure enabling input 2, it is triggered from binary input or programmable logic etc. Stage 1 of phase overcurrent protection for VT circuit failure blocking input, it is triggered from binary input or programmable logic etc. Stage 2 of phase overcurrent protection for VT circuit failure enabling input 1, it is triggered from binary input or programmable logic etc. Stage 2 of phase overcurrent protection for VT circuit failure enabling input 2, it is triggered from binary input or programmable logic etc. Stage 2 of phase overcurrent protection for VT circuit failure blocking input, it is triggered from binary input or programmable logic etc. Stage 1 of ground overcurrent protection for VT circuit failure enabling input 1, it is triggered from binary input or programmable logic etc. Stage 1 of ground overcurrent protection for VT circuit failure enabling input 2, it is triggered from binary input or programmable logic etc. Stage 1 of ground overcurrent protection for VT circuit failure blocking input, it is triggered from binary input or programmable logic etc. Stage 2 of ground overcurrent protection for VT circuit failure enabling input 1, it is triggered from binary input or programmable logic etc. Stage 2 of ground overcurrent protection for VT circuit failure enabling input 2, it is triggered from binary input or programmable logic etc. Stage 2 of ground overcurrent protection for VT circuit failure blocking input, it is triggered from binary input or programmable logic etc. Phase current SOTF protection 214 50PSOTF.En1 215 50PSOTF.En2 216 50PSOTF.Blk Phase current SOTF protection enabling input 1, it is triggered from binary input or programmable logic etc. Phase current SOTF protection enabling input 2, it is triggered from binary input or programmable logic etc. Phase current SOTF protection blocking input, it is triggered from binary input or programmable logic etc. Residual SOTF protection 217 50GSOTF.En1 218 50GSOTF.En2 Residual current SOTF protection enabling input 1, it is triggered from binary input or programmable logic etc. Residual current SOTF protection enabling input 2, it is triggered from PCS-902 Line Distance Relay 9-11 Date: 2019-03-01 9 Configurable Function No. Item Description binary input or programmable logic etc. 219 50GSOTF.Blk Residual current SOTF protection blocking input, it is triggered from binary input or programmable logic etc. Voltage protection 220 59P1.En1 221 59P1.En2 222 59P1.Blk 223 59P2.En1 224 59P2.En2 225 59P2.Blk 226 59P3.En1 227 59P3.En2 228 59P3.Blk 229 59Q.En1 230 59Q.En2 231 59Q.Blk 232 59G1.En1 233 59G1.En2 234 59G1.Blk 235 59G2.En1 236 59G2.En2 237 59G2.Blk 238 59G3.En1 Stage 1 of overvoltage protection enabling input 1, it is triggered from binary input or programmable logic etc. Stage 1 of overvoltage protection enabling input 2, it is triggered from binary input or programmable logic etc. Stage 1 of overvoltage protection blocking input, it is triggered from binary input or programmable logic etc. Stage 2 of overvoltage protection enabling input 1, it is triggered from binary input or programmable logic etc. Stage 2 of overvoltage protection enabling input 2, it is triggered from binary input or programmable logic etc. Stage 2 of overvoltage protection blocking input, it is triggered from binary input or programmable logic etc. Stage 3 of overvoltage protection enabling input 1, it is triggered from binary input or programmable logic etc. Stage 3 of overvoltage protection enabling input 2, it is triggered from binary input or programmable logic etc. Stage 3 of overvoltage protection blocking input, it is triggered from binary input or programmable logic etc. Negative-sequence overvoltage protection enabling input 1, it is triggered from binary input or programmable logic etc. Negative-sequence overvoltage protection enabling input 2, it is triggered from binary input or programmable logic etc. Negative-sequence overvoltage protection blocking input, it is triggered from binary input or programmable logic etc. Stage 1 of residual overvoltage protection enabling input 1, it is triggered from binary input or programmable logic etc. Stage 1 of residual overvoltage protection enabling input 2, it is triggered from binary input or programmable logic etc. Stage 1 of overvoltage protection blocking input, it is triggered from binary input or programmable logic etc.) Stage 2 of residual overvoltage protection enabling input 1, it is triggered from binary input or programmable logic etc. Stage 2 of residual overvoltage protection enabling input 2, it is triggered from binary input or programmable logic etc. Stage 2 of overvoltage protection blocking input, it is triggered from binary input or programmable logic etc.) Stage 3 of residual overvoltage protection enabling input 1, it is triggered from binary input or programmable logic etc. 9-12 PCS-902 Line Distance Relay Date: 2019-03-01 9 Configurable Function No. Item 239 59G3.En2 240 59G3.Blk 241 27P1.En1 242 27P1.En2 243 27P1.Blk 244 27P2.En1 245 27P2.En2 246 27P2.Blk 247 27P3.En1 248 27P3.En2 249 27P3.Blk Description Stage 3 of residual overvoltage protection enabling input 2, it is triggered from binary input or programmable logic etc. Stage 3 of overvoltage protection blocking input, it is triggered from binary input or programmable logic etc.) Stage 1 of undervoltage protection enabling input 1, it is triggered from binary input or programmable logic etc. Stage 1 of undervoltage protection enabling input 2, it is triggered from binary input or programmable logic etc. Stage 1 of undervoltage protection blocking input, it is triggered from binary input or programmable logic etc. Stage 2 of undervoltage protection enabling input 1, it is triggered from binary input or programmable logic etc. Stage 2 of undervoltage protection enabling input 2, it is triggered from binary input or programmable logic etc. Stage 2 of undervoltage protection blocking input, it is triggered from binary input or programmable logic etc. Stage 3 of undervoltage protection enabling input 1, it is triggered from binary input or programmable logic etc. Stage 3 of undervoltage protection enabling input 2, it is triggered from binary input or programmable logic etc. Stage 3 of undervoltage protection blocking input, it is triggered from binary input or programmable logic etc. Frequency protection 250 81O.En1 251 81O.En2 252 81O.Blk 253 81U.En1 254 81U.En2 255 81U.Blk Overfrequency protection enabling input 1, it is triggered from binary input or programmable logic etc. Overfrequency protection enabling input 2, it is triggered from binary input or programmable logic etc. Overfrequency protection blocking input, it is triggered from binary input or programmable logic etc. Underfrequency protection enabling input 1, it is triggered from binary input or programmable logic etc. Underfrequency protection enabling input 2, it is triggered from binary input or programmable logic etc. Underfrequency protection blocking input, it is triggered from binary input or programmable logic etc. Breaker failure protection 256 CBx.50BF.ExTrp3P_L Input signal of three-phase tripping contact from line protection 257 CBx.50BF.ExTrp3P_GT 258 CBx.50BF.ExTrpA Input signal of phase-A tripping contact from external device 259 CBx.50BF.ExTrpB Input signal of phase-B tripping contact from external device 260 CBx.50BF.ExTrpC Input signal of phase-C tripping contact from external device Input signal of three-phase tripping contact from generator or transformer protection PCS-902 Line Distance Relay 9-13 Date: 2019-03-01 9 Configurable Function No. Item Description Input signal of three-phase tripping contact from external device. Once it 261 CBx.50BF.ExTrp_WOI is energized, normally closed auxiliary contact of circuit breaker is chosen in addition to breaker failure current check to trigger breaker failure timers. 262 CBx.50BF.En Input signal of enabling breaker failure protection Breaker failure protection blocking input, such as function blocking 263 CBx.50BF.Blk binary input. When the input is 1, breaker failure protection is reset and time delay is cleared. Thermal overload protection 264 49.Clr_Cmd 265 49.En 266 49.Blk Input signal of clear thermal accumulation value Thermal overload protection enabling input, it is triggered from binary input or programmable logic etc. Thermal overload protection blocking input, it is triggered from binary input or programmable logic etc. Stub differential protection 267 87STB.En1 268 87STB.En2 269 87STB.Blk 270 87STB.89b_DS 271 87STB.89b_DS_Rmt Stub differential protection enabling input 1, it is triggered from binary input or programmable logic etc. Stub differential protection enabling input 2, it is triggered from binary input or programmable logic etc. Stub differential protection blocking input, it is triggered from binary input or programmable logic etc. Normally closed auxiliary contact of line disconnector Normally closed auxiliary contact of line disconnector in remote end In general, it is configured as receiving the signal [87STB.On_Local] from the remote end. Dead zone protection 272 CBx.50DZ.En1 273 CBx.50DZ.En2 Dead zone protection enabling input 1, it can be binary inputs or logic link. Dead zone protection enabling input 2, it can be binary inputs or logic link. Dead zone protection blocking input, such as function blocking binary 274 CBx.50DZ.Blk input. When the input is 1, dead zone protection is reset and time delay is cleared. 275 CBx.50DZ.Init Initiation signal input of the dead zone protection. Pole discrepancy protection 276 CBx.62PD.En1 277 CBx.62PD.En2 278 CBx.62PD.Blk Pole discrepancy protection enabling input 1, it is triggered from binary input or programmable logic etc. Pole discrepancy protection enabling input 2, it is triggered from binary input or programmable logic etc. Pole discrepancy protection blocking input, it is triggered from binary input or programmable logic etc. 9-14 PCS-902 Line Distance Relay Date: 2019-03-01 9 Configurable Function No. Item Description Broken conductor protection 279 46BC.En1 280 46BC.En2 281 46BC.Blk Enable broken conductor protection input 1, it is triggered from binary input or programmable logic etc. Enable broken conductor protection input 2, it is triggered from binary input or programmable logic etc. Broken conductor protection blocking input, it is triggered from binary input or programmable logic etc. Reverse power protection 282 32R1.En 283 32R1.Blk 284 32R2.En 285 32R2.Blk Enable stage 1 of reverse power protection input 1, it is triggered from binary input or programmable logic etc. Stage 1 of reverse power protection blocking input, it is triggered from binary input or programmable logic etc. Enable stage 2 of reverse power protection input 2, it is triggered from binary input or programmable logic etc. Stage 2 of reverse power protection blocking input, it is triggered from binary input or programmable logic etc. Synchrocheck 286 CBx.25.Blk_Chk Input signal of blocking synchrocheck function for AR. 287 CBx.25.Blk_SynChk 288 CBx.25.Blk_DdChk 289 CBx.25.Start_Chk 290 CBx.25.Start_3PLvChk 291 CBx.25.Sel_SynChk Synchronism check is selected. 292 CBx.25.Sel_DdL_DdB Dead line and dead bus check is selected. 293 CBx.25.Sel_DdL_LvB Dead line and live bus check is selected. 294 CBx.25.Sel_LvL_DdB Live line and live bus check is selected. 295 CBx.25.Sel_NoChk No check is selected. 296 CBx.25.Blk_VTS_Usyn VT circuit supervision (Usyn) is blocked 297 CBx.25.Blk_VTS_Uref VT circuit supervision (Uref) is blocked 298 25.MCB_VT_UL1 Binary input for VT MCB auxiliary contact (UL1) 299 25.MCB_VT_UL2 Binary input for VT MCB auxiliary contact (UL2) 300 25.MCB_VT_UB1 Binary input for VT MCB auxiliary contact (UB1) 301 25.MCB_VT_UB2 Binary input for VT MCB auxiliary contact (UB2) 302 25.NC_UL1DS Normally closed contact of disconnector (UL1) 303 25.NO_UL1DS Normally open contact of disconnector (UL1) 304 25.NC_UB1DS Normally closed contact of disconnector (UB1) 305 25.NO_UB1DS Normally open contact of disconnector (UB1) 306 25.NC_UL2DS Normally closed contact of disconnector (UL2) 307 25.NO_UL2DS Normally open contact of disconnector (UL2) Input signal of blocking synchronism check for AR. If the value is “1”, the output of synchronism check is “0”. Input signal of blocking dead charge check for AR. Input signal of starting synchronism check, usually it was starting signal of AR from auto-reclosing module. Input signal of starting live three-phase check, usually it was starting signal of 1-pole AR PCS-902 Line Distance Relay 9-15 Date: 2019-03-01 9 Configurable Function No. Item Description 308 25.NC_UB2DS Normally closed contact of disconnector (UB2) 309 25.NO_UB2DS Normally open contact of disconnector (UB2) Auto-reclosing Binary input for enabling AR. If the logic setting [79.En_ExtCtrl]=1, 310 CBx.79.En 311 CBx.79.Blk 312 CBx.79.Sel_1PAR 313 CBx.79.Sel_3PAR 314 CBx.79.Sel_1P/3PAR 315 CBx.79.Trp Input signal of single-phase tripping from line protection to initiate AR 316 CBx.79.Trp3P Input signal of three-phase tripping from line protection to initiate AR 317 CBx.79.TrpA Input signal of A-phase tripping from line protection to initiate AR 318 CBx.79.TrpB Input signal of B-phase tripping from line protection to initiate AR 319 CBx.79.TrpC Input signal of C-phase tripping from line protection to initiate AR enabling AR will be controlled by the external signal via binary input Binary input for disabling AR. If the logic setting [79.En_ExtCtrl]=1, disabling AR will be controlled by the external input Input signal for selecting 1-pole AR mode of corresponding circuit breaker Input signal for selecting 3-pole AR mode of corresponding circuit breaker Input signal for selecting 1/3-pole AR mode of corresponding circuit breaker Input signal of blocking reclosing, usually it is connected with the 320 CBx.79.LockOut operating signals of definite-time protection, transformer protection and busbar differential protection, etc. 321 CBx.79.PLC_Lost Input signal of indicating the alarm signal that signal channel is lost 322 CBx.79.WaitMaster 323 CBx.79.CB_Healthy 324 CBx.79.Clr_Counter Clear the reclosing counter 325 CBx.79.Ok_Chk Synchrocheck condition of AR is met 326 CBx.79.Ok_3PLvChk Live three-phase check condition of AR is met Input signal of waiting for reclosing permissive signal from master AR (when reclosing multiple circuit breakers) The input for indicating whether circuit breaker has enough energy to perform the close function Transfer trip 327 TT.Init 328 TT.En 329 TT.Blk Input signal of initiating transfer trip after receiving transfer trip Transfer trip enabling input, it is triggered from binary input or programmable logic etc. Transfer trip blocking input, it is triggered from binary input or programmable logic etc. Trip logic 330 Line.Enable Input signal of enabling line trip logic 331 Line.Block Input signal of blocking line trip logic 332 CBx.TRP.En Trip enabling input, it is triggered from binary input or programmable logic etc. 333 CBx.TRP.Blk Trip blocking input, it is triggered from binary input or programmable 9-16 PCS-902 Line Distance Relay Date: 2019-03-01 9 Configurable Function No. Item Description logic etc. Input signal of permitting three-phase tripping 334 CBx.PrepTrp3P When this signal is valid, three-phase tripping will be adopted for any kind of faults. VT circuit supervision 335 VTS.En 336 VTS.Blk 337 VTNS.En 338 VTNS.Blk 339 VTS.MCB_VT VT supervision enabling input, it is triggered from binary input or programmable logic etc. VT supervision blocking input, it is triggered from binary input or programmable logic etc. VT neutral point supervision enabling input, it is triggered from binary input or programmable logic etc. VT neutral point supervision blocking input, it is triggered from binary input or programmable logic etc. Binary input for VT MCB auxiliary contact CT circuit supervision 340 CBx.CTS.En 341 CBx.CTS.Blk CT circuit supervision enabling input, it is triggered from binary input or programmable logic etc. CT circuit supervision blocking input, it is triggered from binary input or programmable logic etc. Control and synchrocheck for manual closing From receiving a closing command, this device will continuously check whether the 2 voltages (Incoming voltage and reference voltage) involved in synchronism check (or dead check) can meet the criteria. 342 MCBrd.CBx.25.Ok_Chk Within the duration of [MCBrd.CBx.25.t_Wait_Chk], if the synchronism check (or dead check) criteria are not met, [MCBrd.CBx.25.Ok_Chk] will be set as “0”; if the synchronism check (or dead check) criteria are met, [MCBrd.CBx.25.Ok_Chk] will be set as “1”. 343 CSWI01.CILO.EnOpn 344 CSWI01.CILO.EnCls 345 CSWI01.LocCtrl It is used to indicate the interlock status of open output for binary output No.01. It is used to indicate the interlock status of closing output for binary output No.01. It is used to select the local control to binary output No.01. When the local control is active, binary output No.01 can only be locally controlled. It is used to select the remote control to binary output No.01. When the 346 CSWI01.RmtCtrl remote control is active, binary output No.01 can only be remotely controlled from SCADA or control centers. It is used to disable the interlock blocking function for control output. If 347 CSWI01.CILO.Disable the signal “CSWI01.CILO.Disable” is “1”, binary output No.01 will not be blocked by interlock conditions. 348 CSWI02.CILO.EnOpn 349 CSWI02.CILO.EnCls It is used to indicate the interlock status of open output for binary output No.02. It is used to indicate the interlock status of closing output for binary PCS-902 Line Distance Relay 9-17 Date: 2019-03-01 9 Configurable Function No. Item Description output No.02. 350 CSWI02.LocCtrl It is used to select the local control to binary output No.02. When the local control is active, binary output No.02 can only be locally controlled. It is used to select the remote control to binary output No.02. When the 351 CSWI02.RmtCtrl remote control is active, binary output No.02 can only be remotely controlled from SCADA or control centers. It is used to disable the interlock blocking function for control output. If 352 CSWI02.CILO.Disable the signal “CSWI02.CILO.Disable” is “1”, binary output No.02 will not be blocked by interlock conditions. 353 CSWI03.CILO.EnOpn 354 CSWI03.CILO.EnCls 355 CSWI03.LocCtrl It is used to indicate the interlock status of open output for binary output No.03. It is used to indicate the interlock status of closing output for binary output No.03. It is used to select the local control to binary output No.03. When the local control is active, binary output No.03 can only be locally controlled. It is used to select the remote control to binary output No.03. When the 356 CSWI03.RmtCtrl remote control is active, binary output No.03 can only be remotely controlled from SCADA or control centers. It is used to disable the interlock blocking function for control output. If 357 CSWI03.CILO.Disable the signal “CSWI03.CILO.Disable” is “1”, binary output No.03 will not be blocked by interlock conditions. 358 CSWI04.CILO.EnOpn 359 CSWI04.CILO.EnCls 360 CSWI04.LocCtrl It is used to indicate the interlock status of open output for binary output No.05. It is used to indicate the interlock status of closing output for binary output No.05. It is used to select the local control to binary output No.04. When the local control is active, binary output No.04 can only be locally controlled. It is used to select the remote control to binary output No.04. When the 361 CSWI04.RmtCtrl remote control is active, binary output No.04 can only be remotely controlled from SCADA or control centers. It is used to disable the interlock blocking function for control output. If 362 CSWI04.CILO.Disable the signal “CSWI04.CILO.Disable” is “1”, binary output No.04 will not be blocked by interlock conditions. 363 CSWI05.CILO.EnOpn 364 CSWI05.CILO.EnCls 365 CSWI05.LocCtrl It is used to indicate the interlock status of open output for binary output No.05. It is used to indicate the interlock status of closing output for binary output No.05. It is used to select the local control to binary output No.05. When the local control is active, binary output No.05 can only be locally controlled. It is used to select the remote control to binary output No.05. When the 366 CSWI05.RmtCtrl remote control is active, binary output No.05 can only be remotely controlled from SCADA or control centers. 9-18 PCS-902 Line Distance Relay Date: 2019-03-01 9 Configurable Function No. Item Description It is used to disable the interlock blocking function for control output. If 367 CSWI05.CILO.Disable the signal “CSWI05.CILO.Disable” is “1”, binary output No.05 will not be blocked by interlock conditions. 368 CSWI06.CILO.EnOpn 369 CSWI06.CILO.EnCls 370 CSWI06.LocCtrl It is used to indicate the interlock status of open output for binary output No.06. It is used to indicate the interlock status of closing output for binary output No.06. It is used to select the local control to binary output No.06. When the local control is active, binary output No.01 can only be locally controlled. It is used to select the remote control to binary output No.06. When the 371 CSWI06.RmtCtrl remote control is active, binary output No.06 can only be remotely controlled from SCADA or control centers. It is used to disable the interlock blocking function for control output. If 372 CSWI06.CILO.Disable the signal “CSWI06.CILO.Disable” is “1”, binary output No.06 will not be blocked by interlock conditions. 373 CSWI07.CILO.EnOpn 374 CSWI07.CILO.EnCls 375 CSWI07.LocCtrl It is used to indicate the interlock status of open output for binary output No.07. It is used to indicate the interlock status of closing output for binary output No.07. It is used to select the local control to binary output No.07. When the local control is active, binary output No.07 can only be locally controlled. It is used to select the remote control to binary output No.07. When the 376 CSWI07.RmtCtrl remote control is active, binary output No.07 can only be remotely controlled from SCADA or control centers. It is used to disable the interlock blocking function for control output. If 377 CSWI07.CILO.Disable the signal “CSWI07.CILO.Disable” is “1”, binary output No.07 will not be blocked by interlock conditions. 378 CSWI08.CILO.EnOpn 379 CSWI08.CILO.EnCls 380 CSWI08.LocCtrl It is used to indicate the interlock status of open output for binary output No.08. It is used to indicate the interlock status of closing output for binary output No.08. It is used to select the local control to binary output No.08. When the local control is active, binary output No.08 can only be locally controlled. It is used to select the remote control to binary output No.08. When the 381 CSWI08.RmtCtrl remote control is active, binary output No.08 can only be remotely controlled from SCADA or control centers. It is used to disable the interlock blocking function for control output. If 382 CSWI08.CILO.Disable the signal “CSWI08.CILO.Disable” is “1”, binary output No.08 will not be blocked by interlock conditions. 383 CSWI09.CILO.EnOpn 384 CSWI09.CILO.EnCls It is used to indicate the interlock status of open output for binary output No.09. It is used to indicate the interlock status of closing output for binary output No.09. PCS-902 Line Distance Relay 9-19 Date: 2019-03-01 9 Configurable Function No. 385 Item CSWI09.LocCtrl Description It is used to select the local control to binary output No.09. When the local control is active, binary output No.09 can only be locally controlled. It is used to select the remote control to binary output No.09. When the 386 CSWI09.RmtCtrl remote control is active, binary output No.09 can only be remotely controlled from SCADA or control centers. It is used to disable the interlock blocking function for control output. If 387 CSWI09.CILO.Disable the signal “CSWI09.CILO.Disable” is “1”, binary output No.09 will not be blocked by interlock conditions. 388 CSWI10.CILO.EnOpn 389 CSWI10.CILO.EnCls 390 CSWI10.LocCtrl It is used to indicate the interlock status of open output for binary output No.10. It is used to indicate the interlock status of closing output for binary output No.10. It is used to select the local control to binary output No.10. When the local control is active, binary output No.10 can only be locally controlled. It is used to select the remote control to binary output No.10. When the 391 CSWI10.RmtCtrl remote control is active, binary output No.10 can only be remotely controlled from SCADA or control centers. It is used to disable the interlock blocking function for control output. If 392 CSWI10.CILO.Disable the signal “CSWI10.CILO.Disable” is “1”, binary output No.10 will not be blocked by interlock conditions. 393 CSWI11.CILO.EnOpn 394 CSWI11.CILO.EnCls 395 CSWI11.LocCtrl It is used to indicate the interlock status of open output for binary output No.11. It is used to indicate the interlock status of closing output for binary output No.11. It is used to select the local control to binary output No.11. When the local control is active, binary output No.11 can only be locally controlled. It is used to select the remote control to binary output No.11. When the 396 CSWI11.RmtCtrl remote control is active, binary output No.11 can only be remotely controlled from SCADA or control centers. It is used to disable the interlock blocking function for control output. If 397 CSWI11.CILO.Disable the signal “CSWI11.CILO.Disable” is “1”, binary output No.11 will not be blocked by interlock conditions. 398 CSWI12.CILO.EnOpn 399 CSWI12.CILO.EnCls 400 CSWI12.LocCtrl It is used to indicate the interlock status of open output for binary output No.12. It is used to indicate the interlock status of closing output for binary output No.12. It is used to select the local control to binary output No.12. When the local control is active, binary output No.12 can only be locally controlled. It is used to select the remote control to binary output No.12. When the 401 CSWI12.RmtCtrl remote control is active, binary output No.12 can only be remotely controlled from SCADA or control centers. 402 CSWI12.CILO.Disable It is used to disable the interlock blocking function for control output. If the signal “CSWI12.CILO.Disable” is “1”, binary output No.12 will not be 9-20 PCS-902 Line Distance Relay Date: 2019-03-01 9 Configurable Function No. Item Description blocked by interlock conditions. 403 CSWI13.CILO.EnOpn 404 CSWI13.CILO.EnCls 405 CSWI13.LocCtrl It is used to indicate the interlock status of open output for binary output No.13. It is used to indicate the interlock status of closing output for binary output No.13. It is used to select the local control to binary output No.13. When the local control is active, binary output No.13 can only be locally controlled. It is used to select the remote control to binary output No.13. When the 406 CSWI13.RmtCtrl remote control is active, binary output No.13 can only be remotely controlled from SCADA or control centers. It is used to disable the interlock blocking function for control output. If 407 CSWI13.CILO.Disable the signal “CSWI13.CILO.Disable” is “1”, binary output No.13 will not be blocked by interlock conditions. 408 CSWI14.CILO.EnOpn 409 CSWI14.CILO.EnCls 410 CSWI14.LocCtrl It is used to indicate the interlock status of open output for binary output No.14. It is used to indicate the interlock status of closing output for binary output No.14. It is used to select the local control to binary output No.14. When the local control is active, binary output No.14 can only be locally controlled. It is used to select the remote control to binary output No.14. When the 411 CSWI14.RmtCtrl remote control is active, binary output No.14 can only be remotely controlled from SCADA or control centers. It is used to disable the interlock blocking function for control output. If 412 CSWI14.CILO.Disable the signal “CSWI14.CILO.Disable” is “1”, binary output No.14 will not be blocked by interlock conditions. 413 CSWI15.CILO.EnOpn 414 CSWI15.CILO.EnCls 415 CSWI15.LocCtrl It is used to indicate the interlock status of open output for binary output No.15. It is used to indicate the interlock status of closing output for binary output No.15. It is used to select the local control to binary output No.15. When the local control is active, binary output No.15 can only be locally controlled. It is used to select the remote control to binary output No.15. When the 416 CSWI15.RmtCtrl remote control is active, binary output No.15 can only be remotely controlled from SCADA or control centers. It is used to disable the interlock blocking function for control output. If 417 CSWI15.CILO.Disable the signal “CSWI15.CILO.Disable” is “1”, binary output No.15 will not be blocked by interlock conditions. 418 BIinput.LocCtrl It is used to select the local control to all binary outputs. When the local control is active, all binary outputs can only be locally controlled. It is used to select the remote control to all binary outputs. When the 419 BIinput.RmtCtrl remote control is active, all binary outputs can only be remotely controlled from SCADA or control centers. PCS-902 Line Distance Relay 9-21 Date: 2019-03-01 9 Configurable Function No. Item Description It is used to disable the interlock blocking function for control output. If 420 BIinput.CILO.Disable the signal “BIinput.CILO.Disable” is “1”, all binary outputs will not be blocked by interlock conditions. When the condition of local 421 CSWI01.ManSynCls control is met and the signal “CSWI01.ManSynCls” is “1”, the output contact [BO_CtrlCls01] is closed to execute manually closing the circuit breaker with synchrocheck. When the condition of local 422 CSWI01.ManOpn control is met and the signal “CSWI01.ManOpn” is “1”, the output contact [BO_CtrlOpn01] is closed to execute manually open the circuit breaker. When the condition of local 423 CSWI02.ManSynCls control is met and the signal “CSWI02.ManSynCls” is “1”, the output contact [BO_CtrlCls02] is closed to execute manually closing the circuit breaker with synchrocheck. (for double circuit breakers application) When the condition of local 424 CSWI02.ManOpn control is met and the signal “CSWI02.ManOpn” is “1”, the output contact [BO_CtrlOpn02] is closed to execute manually open the circuit breaker. (for double circuit breakers application) 425 MCBrd.CBx.25.Sel_SynChk Synchronism check for manual closing is selected. 426 MCBrd.CBx.25.Sel_NoChk No check for manual closing is selected. 9.3.2 Output Signal All output signals of this device have been listed in the following table. Table 9.3-2 Output signals No. Signal Description Circuit breaker position supervision 1 CBx.Alm_52b Circuit breaker No.x position is abnormal 2 CBx.TCCS.Alm Control circuit of circuit breaker No.x is abnormal Fault detector 3 FD.Pkp The device picks up 4 FD.DPFC.Pkp DPFC current fault detector element operates. 5 FD.ROC.Pkp Residual current fault detector element operates. 6 FD.NOC.Pkp Negative-sequence fault detector element operates. Auxiliary element 7 AuxE.St Any auxiliary element of the device operates. 8 AuxE.OCD.St_DDO Current change auxiliary element operates. 9 AuxE.OCD.On Current change auxiliary element is enabled. 10 AuxE.ROC1.St Stage 1 of residual current auxiliary element operates. 11 AuxE.ROC1.On Stage 1 of residual current auxiliary element is enabled. 12 AuxE.ROC2.St Stage 2 of residual current auxiliary element operates. 13 AuxE.ROC2.On Stage 2 of residual current auxiliary element is enabled. 14 AuxE.ROC3.St Stage 3 of residual current auxiliary element operates. 9-22 PCS-902 Line Distance Relay Date: 2019-03-01 9 Configurable Function No. Signal Description 15 AuxE.ROC3.On Stage 3 of residual current auxiliary element is enabled. 16 AuxE.OC1.St Stage 1 of phase current auxiliary element operates. 17 AuxE.OC1.StA Stage 1 of phase current auxiliary element operates (phase A). 18 AuxE.OC1.StB Stage 1 of phase current auxiliary element operates (phase B). 19 AuxE.OC1.StC Stage 1 of phase current auxiliary element operates (phase C). 20 AuxE.OC1.On Stage 1 of phase current auxiliary element is enabled. 21 AuxE.OC2.St Stage 2 of phase current auxiliary element operates. 22 AuxE.OC2.StA Stage 2 of phase current auxiliary element operates (phase A). 23 AuxE.OC2.StB Stage 2 of phase current auxiliary element operates (phase B). 24 AuxE.OC2.StC Stage 2 of phase current auxiliary element operates (phase C). 25 AuxE.OC2.On Stage 2 of phase current auxiliary element is enabled. 26 AuxE.OC3.St Stage 3 of phase current auxiliary element operates. 27 AuxE.OC3.StA Stage 1 of phase current auxiliary element operates (phase A). 28 AuxE.OC3.StB Stage 1 of phase current auxiliary element operates (phase B). 29 AuxE.OC3.StC Stage 1 of phase current auxiliary element operates (phase C). 30 AuxE.OC3.On Stage 3 of phase current auxiliary element is enabled. 31 AuxE.UVD.St Voltage change auxiliary element operates. 32 AuxE.UVD.St_DDO Voltage change auxiliary element operates. 33 AuxE.UVD.On Voltage change auxiliary element is enabled. 34 AuxE.UVG.St Phase-to-ground under voltage auxiliary element operates. 35 AuxE.UVG.StA Phase-to-ground under voltage auxiliary element operates (phase A). 36 AuxE.UVG.StB Phase-to-ground under voltage auxiliary element operates (phase B). 37 AuxE.UVG.StC Phase-to-ground under voltage auxiliary element operates (phase C). 38 AuxE.UVG.On Phase-to-ground under voltage auxiliary element is enabled. 39 AuxE.UVS.St Phase-to-phase under voltage auxiliary element operates. 40 AuxE.UVS.StAB Phase-to-phase under voltage auxiliary element operates (phase AB). 41 AuxE.UVS.StBC Phase-to-phase under voltage auxiliary element operates (phase BC). 42 AuxE.UVS.StCA Phase-to-phase under voltage auxiliary element operates (phase CA). 43 AuxE.UVS.On Phase-to-phase under voltage auxiliary element is enabled. 44 AuxE.ROV.St Residual voltage auxiliary element operates. 45 AuxE.ROV.On Residual voltage auxiliary element is enabled. Distance protection 46 21D.Op DPFC distance protection operates. 47 21D.On DPFC distance protection is enabled. 48 LoadEnch.St Measured impedance into the load area 49 LoadEnch.On Load trapezoid characteristic is enabled. 50 21M1.On Zone 1 of distance protection is enabled 51 21M1.Op Zone 1 of distance protection operates 52 21Q1.On Zone 1 of distance protection is enabled 53 21Q1.Op Zone 1 of distance protection operates 54 21M2.On Zone 2 of distance protection is enabled 55 21M2.Op Zone 2 of distance protection operates PCS-902 Line Distance Relay 9-23 Date: 2019-03-01 9 Configurable Function No. Signal Description 56 21Q2.On Zone 2 of distance protection is enabled 57 21Q2.Op Zone 2 of distance protection operates 58 21M3.On Zone 3 of distance protection is enabled 59 21M3.Op Zone 3 of distance protection operates 60 21Q3.On Zone 3 of distance protection is enabled 61 21Q3.Op Zone 3 of distance protection operates 62 21M4.On Zone 4 of distance protection is enabled 63 21M4.Op Zone 4 of distance protection operates 64 21Q4.On Zone 4 of distance protection is enabled 65 21Q4.Op Zone 4 of distance protection operates 66 21M5.On Zone 5 of distance protection is enabled 67 21M5.Op Zone 5 of distance protection operates 68 21Q5.On Zone 5 of distance protection is enabled 69 21Q5.Op Zone 5 of distance protection operates 70 78.On Out-of-step protection is enabled. 71 78.St Out-of-step protection starts. 72 78.St_Zone Zone detector element of out-of-step protection starts. 73 78.Op Out-of-step protection operates. 74 21M1.Rls_PSBR PSBR operates to release zone 1 (Mho characteristic) 75 21Q1.Rls_PSBR PSBR operates to release zone 1 (Quad characteristic) 76 21M2.Rls_PSBR PSBR operates to release zone 2 (Mho characteristic) 77 21Q2.Rls_PSBR PSBR operates to release zone 2 (Quad characteristic) 78 21M3.Rls_PSBR PSBR operates to release zone 3 (Mho characteristic) 79 21Q3.Rls_PSBR PSBR operates to release zone 3 (Quad characteristic) 80 21M4.Rls_PSBR PSBR operates to release zone 4 (Mho characteristic) 81 21Q4.Rls_PSBR PSBR operates to release zone 4 (Quad characteristic) 82 21M5.Rls_PSBR PSBR operates to release zone 5 (Mho characteristic) 83 21Q5.Rls_PSBR PSBR operates to release zone 5 (Quad characteristic) 84 21M.Pilot.Rls_PSBR PSBR operates to release pilot distance zone (Mho characteristic) 85 21Q.Pilot.Rls_PSBR PSBR operates to release pilot distance zone (Quad characteristic) 86 21SOTF.Op 87 21SOTF.On 88 21SOTF.Op_PDF Accelerate distance protection to trip when manual closing or auto-reclosing to fault Accelerate distance protection is enabled. Accelerate distance protection to trip when another fault happening under pole discrepancy conditions Optical pilot channel 89 FOx.On Channel x is enabled. 90 FOx.Recv1 Receiving signal 1 of channel x 91 FOx.Recv2 Receiving signal 2 of channel x 92 FOx.Recv3 Receiving signal 3 of channel x 93 FOx.Recv4 Receiving signal 4 of channel x 94 FOx.Recv5 Receiving signal 5 of channel x 9-24 PCS-902 Line Distance Relay Date: 2019-03-01 9 Configurable Function No. Signal Description 95 FOx.Recv6 Receiving signal 6 of channel x 96 FOx.Recv7 Receiving signal 7 of channel x 97 FOx.Recv8 Receiving signal 8 of channel x Receiving signal 9 of channel x (it is configured by fault as receiving 98 permissive signal via channel No.1, or receiving permissive signal of FOx.Recv9 A-phase via channel No.1 (only for phase-segregated command scheme)) Receiving signal 10 of channel x (it is configured by fault as receiving 99 FOx.Recv10 permissive signal of B-phase via channel No.1 (only for phase-segregated command scheme)) Receiving signal 11 of channel x (it is configured by fault as receiving 100 FOx.Recv11 permissive signal of C-phase via channel No.1 (only for phase-segregated command scheme)) Receiving signal 12 of channel x (it is configured by fault as receiving 101 FOx.Recv12 permissive signal 2 only for pilot directional earth-fault protection adopting independent pilot channel 2) 102 FOx.Alm Channel x is abnormal 103 FOx.Alm_ID Received ID from the remote end is not as same as the setting [FO.RmtID] of the device in local end Pilot distance protection and pilot directional earth-fault protection 104 85-x.Z.On 105 85-x.ZX.On 106 85-x.Op_Z 107 85.Z.On 108 85.ZX.On 109 85.Op_Z Pilot distance protection x is enabled. (x=1 or 2) Zone extension protection of pilot distance protection x is enabled. (x=1 or 2) Pilot distance protection x operates. (x=1 or 2) General pilot distance protection is enabled. Which is OR operation between 85-1.Z.On and 85-2.Z.On General zone extension protection is enabled, which is OR operation between 85-1.ZX.On and 85-2.ZX.On General pilot distance protection operates, which is OR operation between 85-1.Op_Z and 85-2. Op_Z Output signal of sending permissive signal 1 or sending A-phase 110 85-x.Send1 permissive signal of pilot distance protection x (only for phase-segregated command scheme, x=1 or 2) 111 85-x.SendB 112 85-x.SendC 113 85-x.Op_ZX 114 85-x.ZX_St 115 85-x.Z.FwdDir Output signal of sending B-phase permissive signal of pilot distance protection x (only for phase-segregated command scheme, x=1 or 2) Output signal of sending C-phase permissive signal of pilot distance protection x (only for phase-segregated command scheme, x=1 or 2) Zone extension protection of pilot distance protection x operates. (x=1 or 2) Zone extension protection of pilot distance protection x starts (x=1 or 2) Forward direction signal of pilot distance protection x (x=1 or 2) PCS-902 Line Distance Relay 9-25 Date: 2019-03-01 9 Configurable Function No. Signal Description 116 85-x.Z.RevDir Reverse direction signal of pilot distance protection x (x=1 or 2) 117 85-x.DEF.FwdDir 118 85-x.DEF.RevDir 119 85-x.WI 120 85-x.UV_WI 121 85.DEF.On 122 85.Op_DEF 123 85.DEF_BlkAR 124 85-x.DEF.On Pilot directional earth-fault protection x is enabled. (x=1 or 2) 125 85-x.Op_DEF Pilot directional earth-fault protection x operates. (x=1 or 2) 126 85-x.DEF_BlkAR Forward direction signal of pilot directional earth-fault protection x (x=1 or 2) Reverse direction signal of pilot directional earth-fault protection x (x=1 or 2) Operation signal of weak infeed logic of pilot distance protection x (x=1 or 2) Undervoltage signal of weak infeed logic of pilot distance protection x (x=1 or 2) General pilot directional earth-fault protection is enabled. It is OR operation between 85-1.DEF.On and 85-2.DEF.On General pilot directional earth-fault protection operates. It is OR operation between 85-1.Op_DEF and 85-2.Op_DEF General pilot directional earth-fault protection operates to block AR. It is OR operation between 85-1.DEF_BlkAR and 85-2.DEF_BlkAR Pilot directional earth-fault protection x operates to block AR. (x=1 or 2) Output signal of sending permissive signal 1 for pilot directional 127 85-x.Send1 earth-fault protection x when pilot directional earth-fault protection sharing pilot channel 1 with pilot distance protection (x=1 or 2) Output signal of sending permissive signal 2 for pilot directional 128 85-x.Send2 earth-fault protection x when pilot directional earth-fault protection adopting independent pilot channel 2 (x=1 or 2) Current direction 129 FwdDir_ROC The forward direction of zero-sequence power 130 RevDir_ROC The reverse direction of zero-sequence power 131 FwdDir_NegOC The forward direction of negative-sequence power 132 RevDir_NegOC The reverse direction of negative-sequence power 133 FwdDir_A The forward direction of phase-A current 134 FwdDir_B The forward direction of phase-B current 135 FwdDir_C The forward direction of phase-C current 136 RevDir_A The reverse direction of phase-A current 137 RevDir_B The reverse direction of phase-B current 138 RevDir_C The reverse direction of phase-C current 139 FwdDir_AB The forward direction of phase-AB current 140 FwdDir_BC The forward direction of phase-BC current 141 FwdDir_CA The forward direction of phase-CA current 142 RevDir_AB The reverse direction of phase-AB current 143 RevDir_BC The reverse direction of phase-BC current 144 RevDir_CA The reverse direction of phase-CA current 9-26 PCS-902 Line Distance Relay Date: 2019-03-01 9 Configurable Function No. Signal Description Phase overcurrent protection 145 50/51P1.On Stage x of phase overcurrent protection is enabled. 146 50/51P1.Op Stage x of phase overcurrent protection operates. 147 50/51P1.St Stage x of phase overcurrent protection starts. 148 50/51P1.StA Stage x of phase overcurrent protection starts (A-Phase). 149 50/51P1.StB Stage x of phase overcurrent protection starts (B-Phase). 150 50/51P1.StC Stage x of phase overcurrent protection starts (C-Phase). 151 50/51P2.On Stage x of phase overcurrent protection is enabled. 152 50/51P2.Op Stage x of phase overcurrent protection operates. 153 50/51P2.St Stage x of phase overcurrent protection starts. 154 50/51P2.StA Stage x of phase overcurrent protection starts (A-Phase). 155 50/51P2.StB Stage 2 of phase overcurrent protection starts (B-Phase). 156 50/51P2.StC Stage 2 of phase overcurrent protection starts (C-Phase). 157 50/51P3.On Stage 3 of phase overcurrent protection is enabled. 158 50/51P3.Op Stage 3 of phase overcurrent protection operates. 159 50/51P3.St Stage 3 of phase overcurrent protection starts. 160 50/51P3.StA Stage 3 of phase overcurrent protection starts (A-Phase). 161 50/51P3.StB Stage 3 of phase overcurrent protection starts (B-Phase). 162 50/51P3.StC Stage 3 of phase overcurrent protection starts (C-Phase). 163 50/51P4.On Stage 4 of phase overcurrent protection is enabled. 164 50/51P4.Op Stage 4 of phase overcurrent protection operates. 165 50/51P4.St Stage 4 of phase overcurrent protection starts. 166 50/51P4.StA Stage 4 of phase overcurrent protection starts (A-Phase). 167 50/51P4.StB Stage 4 of phase overcurrent protection starts (B-Phase). 168 50/51P4.StC Stage 4 of phase overcurrent protection starts (C-Phase). Earth fault protection 169 50/51G1.On Stage 1 of earth fault protection is enabled. 170 50/51G1.St Stage 1 of earth fault protection starts. 171 50/51G1.Op Stage 1 of earth fault protection operates. 172 50/51G2.On Stage 2 of earth fault protection is enabled. 173 50/51G2.On_ShortDly Short time delay for stage 2 of earth fault protection is enabled. 174 50/51G2.St Stage 2 of earth fault protection starts. 175 50/51G2.Op Stage 2 of earth fault protection operates. 176 50/51G3.On Stage 3 of earth fault protection is enabled. 177 50/51G3.On_ShortDly Short time delay for stage 3 of earth fault protection is enabled. 178 50/51G3.St Stage 3 of earth fault protection starts. 179 50/51G3.Op Stage 3 of earth fault protection operates. 180 50/51G4.On Stage 4 of earth fault protection is enabled. 181 50/51G4.On_ShortDly Short time delay for stage 4 of earth fault protection is enabled. 182 50/51G4.St Stage 4 of earth fault protection starts. 183 50/51G4.Op Stage 4 of earth fault protection operates. Negative-sequence overcurrent protection PCS-902 Line Distance Relay 9-27 Date: 2019-03-01 9 Configurable Function No. Signal Description 184 50/51Q1.On Stage 1 of negative-sequence overcurrent protection is enabled. 185 50/51Q1.St Stage 1 of negative-sequence overcurrent protection starts. 186 50/51Q1.Op Stage 1 of negative-sequence overcurrent protection operates. 187 50/51Q2.On Stage 2 of negative-sequence overcurrent protection is enabled. 188 50/51Q2.St Stage 2 of negative-sequence overcurrent protection starts. 189 50/51Q2.Op Stage 2 of negative-sequence overcurrent protection operates. 190 50/51Q3.On Stage 3 of negative-sequence overcurrent protection is enabled. 191 50/51Q3.St Stage 3 of negative-sequence overcurrent protection starts. 192 50/51Q3.Op Stage 3 of negative-sequence overcurrent protection operates. 193 50/51Q4.On Stage 4 of negative-sequence overcurrent protection is enabled. 194 50/51Q4.St Stage 4 of negative-sequence overcurrent protection starts. 195 50/51Q4.Op Stage 4 of negative-sequence overcurrent protection operates. 196 50/51Q4.Alm Stage 4 of negative-sequence overcurrent protection operates to alarm. Overcurrent protection for VT circuit failure Stage 1 of phase overcurrent protection for VT circuit failure is 197 50PVT1.On 198 50PVT1.Op Stage 1 of phase overcurrent protection for VT circuit failure operates. 199 50PVT1.St Stage 1 of phase overcurrent protection for VT circuit failure starts. 200 50PVT1.StA 201 50PVT1.StB 202 50PVT1.StC 203 50PVT2.On 204 50PVT2.Op Stage 2 of phase overcurrent protection for VT circuit failure operates. 205 50PVT2.St Stage 2 of phase overcurrent protection for VT circuit failure starts. 206 50PVT2.StA 207 50PVT2.StB 208 50PVT2.StC 209 50GVT1.On 210 50GVT1.Op Stage 1 of ground overcurrent protection for VT circuit failure operates. 211 50GVT1.St Stage 1 of ground overcurrent protection for VT circuit failure starts. 212 50GVT2.On 213 50GVT2.Op enabled. Stage 1 of phase overcurrent protection for VT circuit failure starts (A-Phase). Stage 1 of phase overcurrent protection for VT circuit failure starts (B-Phase). Stage 1 of phase overcurrent protection for VT circuit failure starts (C-Phase). Stage 2 of phase overcurrent protection for VT circuit failure is enabled. Stage 2 of phase overcurrent protection for VT circuit failure starts (A-Phase). Stage 2 of phase overcurrent protection for VT circuit failure starts (B-Phase). Stage 2 of phase overcurrent protection for VT circuit failure starts (C-Phase). Stage 1 of ground overcurrent protection for VT circuit failure is enabled. Stage 2 of ground overcurrent protection for VT circuit failure is enabled. Stage 2 of ground overcurrent protection for VT circuit failure operates. 9-28 PCS-902 Line Distance Relay Date: 2019-03-01 9 Configurable Function No. 214 Signal 50GVT2.St Description Stage 2 of ground overcurrent protection for VT circuit failure starts. Phase current SOTF protection 215 50PSOTF.On Phase current SOTF protection is enabled. 216 50PSOTF.Op Phase current SOTF protection operates. 217 50PSOTF.St Phase current SOTF protection starts. Residual SOTF protection 218 50GSOTF.On Residual current SOTF protection is enabled. 219 50GSOTF.Op Residual current SOTF protection operates. 220 50GSOTF.St Residual current SOTF protection starts. Voltage protection 221 59P1.On Stage 1 of overvoltage protection is enabled. 222 59P1.Op Stage 1 of overvoltage protection operates. 223 59P1.St Stage 1 of overvoltage protection starts. 224 59P1.St1 Stage 1 of overvoltage protection starts (A or AB). 225 59P1.St2 Stage 1 of overvoltage protection starts (B or BC). 226 59P1.St3 Stage 1 of overvoltage protection starts (C or CA). 227 59P1.Op_InitTT Stage 1 of overvoltage protection operates to initiate transfer trip. 228 59P1.Alm Stage 1 of overvoltage protection alarms. 229 59P2.On Stage 2 of overvoltage protection is enabled. 230 59P2.Op Stage 2 of overvoltage protection operates. 231 59P2.St Stage 2 of overvoltage protection starts. 232 59P2.St1 Stage 2 of overvoltage protection starts (A or AB). 233 59P2.St2 Stage 2 of overvoltage protection starts (B or BC). 234 59P2.St3 Stage 2 of overvoltage protection starts (C or CA). 235 59P2.Op_InitTT Stage 2 of overvoltage protection operates to initiate transfer trip. 236 59P2.Alm Stage 2 of overvoltage protection alarms. 237 59P3.On Stage 3 of overvoltage protection is enabled. 238 59P3.Op Stage 3 of overvoltage protection operates. 239 59P3.St Stage 3 of overvoltage protection starts. 240 59P3.St1 Stage 3 of overvoltage protection starts (A or AB). 241 59P3.St2 Stage 3 of overvoltage protection starts (B or BC). 242 59P3.St3 Stage 3 of overvoltage protection starts (C or CA). 243 59P3.Op_InitTT Stage 3 of overvoltage protection operates to initiate transfer trip. 244 59P3.Alm Stage 3 of overvoltage protection alarms. 245 59Q.On Negative-sequence overvoltage protection is enabled. 246 59Q.Op Negative-sequence overvoltage protection operates. 247 59Q.St Negative-sequence overvoltage protection starts. 248 59G1.On Stage 1 of residual overvoltage protection is enabled. 249 59G1.Op Stage 1 of residual overvoltage protection operates. 250 59G1.St Stage 1 of residual overvoltage protection start. 251 59G2.On Stage 2 of residual overvoltage protection is enabled. 252 59G2.Op Stage 2 of residual overvoltage protection operates. PCS-902 Line Distance Relay 9-29 Date: 2019-03-01 9 Configurable Function No. Signal Description 253 59G2.St Stage 2 of residual overvoltage protection start. 254 59G3.On Stage 3 of residual overvoltage protection is enabled. 255 59G3.Op Stage 3 of residual overvoltage protection operates. 256 59G3.St Stage 3 of residual overvoltage protection start. 257 59G3.Alm Stage 3 of residual overvoltage protection operates to alarm. 258 27P1.On Stage 1 of undervoltage protection is enabled. 259 27P1.Op Stage 1 of undervoltage protection operates. 260 27P1.Alm Stage 1 of undervoltage protection alarms. 261 27P1.St Stage 1 of undervoltage protection starts. 262 27P1.St1 Stage 1 of undervoltage protection starts (A or AB). 263 27P1.St2 Stage 1 of undervoltage protection starts (B or BC). 264 27P1.St3 Stage 1 of undervoltage protection starts (C or CA). 265 27P1.U_Absent 266 27P2.On Stage 2 of undervoltage protection is enabled. 267 27P2.Op Stage 2 of undervoltage protection operates. 268 27P2.Alm Stage 2 of undervoltage protection alarms. 269 27P2.St Stage 2 of undervoltage protection starts. 270 27P2.St1 Stage 2 of undervoltage protection starts (A or AB). 271 27P2.St2 Stage 2 of undervoltage protection starts (B or BC). 272 27P2.St3 Stage 2 of undervoltage protection starts (C or CA). 273 27P2.U_Absent 274 27P3.On Stage 3 of undervoltage protection is enabled. 275 27P3.Op Stage 3 of undervoltage protection operates. 276 27P3.Alm Stage 3 of undervoltage protection alarms. 277 27P3.St Stage 3 of undervoltage protection starts. 278 27P3.St1 Stage 3 of undervoltage protection starts (A or AB). 279 27P3.St2 Stage 3 of undervoltage protection starts (B or BC). 280 27P3.St3 Stage 3 of undervoltage protection starts (C or CA). 281 27P3.U_Absent No AC voltage input after the device powered on for stage 1 of undervoltage protection No AC voltage input after the device powered on for stage 2 of undervoltage protection No AC voltage input after the device powered on for stage 3 of undervoltage protection Frequency protection 282 81O.OF1.On Stage 1 of overfrequency protection is enabled. 283 81O.OF1.Op Stage 1 of overfrequency protection operates. 284 81O.OF2.On Stage 2 of overfrequency protection is enabled. 285 81O.OF2.Op Stage 2 of overfrequency protection operates. 286 81O.OF3.On Stage 3 of overfrequency protection is enabled. 287 81O.OF3.Op Stage 3 of overfrequency protection operates. 288 81O.OF4.On Stage 4 of overfrequency protection is enabled. 289 81O.OF4.Op Stage 4 of overfrequency protection operates. 290 81O.St Overfrequency protection starts. 9-30 PCS-902 Line Distance Relay Date: 2019-03-01 9 Configurable Function No. Signal Description 291 81U.UF1.On Stage 1 of underfrequency protection is enabled. 292 81U.UF1.Op Stage 1 of underfrequency protection operates. 293 81U.UF2.On Stage 2 of underfrequency protection is enabled. 294 81U.UF2.Op Stage 2 of underfrequency protection operates. 295 81U.UF3.On Stage 3 of underfrequency protection is enabled. 296 81U.UF3.Op Stage 3 of underfrequency protection operates. 297 81U.UF4.On Stage 4 of underfrequency protection is enabled. 298 81U.UF4.Op Stage 4 of underfrequency protection operates. 299 81U.St Underfrequency protection starts. Breaker failure protection 300 CBx.50BF.On Breaker failure protection is enabled 301 CBx.50BF.Op_ReTrpA Breaker failure protection operates to re-trip phase-A circuit breaker 302 CBx.50BF.Op_ReTrpB Breaker failure protection operates to re-trip phase-B circuit breaker 303 CBx.50BF.Op_ReTrpC Breaker failure protection operates to re-trip phase-C circuit breaker 304 CBx.50BF.Op_ReTrp3P 305 CBx.50BF.Op_t1 Stage 1 of breaker failure protection operates 306 CBx.50BF.Op_t2 Stage 2 of breaker failure protection operates Breaker failure protection operates to re-trip three-phase circuit breaker Thermal overload protection 307 49.On Thermal overload protection is enabled. 308 49.St Thermal overload protection starts. 309 49-1.Op Stage 1 of thermal overload protection operates to trip. 310 49-2.Op Stage 2 of thermal overload protection operates to trip. 311 49-1.Alm Stage 1 of thermal overload protection operates to alarm. 312 49-2.Alm Stage 2 of thermal overload protection operates to alarm. Stub differential protection Stub differential protection is enabled. (Based on disconnector position 313 87STB.On 314 87STB.On_Local 315 87STB.Op Stub differential protection operates. 316 87STB.St Stub differential protection starts. 317 87STB.StA Phase A of stub differential protection starts. 318 87STB.StB Phase B of stub differential protection starts. 319 87STB.StC Phase C of stub differential protection starts. 320 87STB.Alm_Diff The alarm signal of differential current abnormality 321 87STB.Alm_DS The alarm signal of disconnector position abnormality signal in both local end and remote end) Stub differential protection is enabled. (Based on disconnector position signal in local end) Dead zone protection 322 CBx.50DZ.On Dead zone protection is enabled. 323 CBx.50DZ.St Dead zone protection starts. 324 CBx.50DZ.Op Dead zone protection operates. Pole discrepancy protection PCS-902 Line Distance Relay 9-31 Date: 2019-03-01 9 Configurable Function No. Signal Description 325 CBx.62PD.On Pole discrepancy protection is enabled. 326 CBx.62PD.Op Pole discrepancy protection operates to trip 327 CBx.62PD.St Pole discrepancy protection starts Broken conductor protection 328 46BC.On Broken-conductor protection is enabled. 329 46BC.St Broken-conductor protection starts 330 46BC.Op Broken-conductor protection operates to trip. 331 46BC.Alm Broken-conductor protection operates to alarm. Reverse power protection 332 32R1.On Stage 1 of reverse power protection is enabled. 333 32R1.St Stage 1 of reverse power protection starts. 334 32R1.Op Stage 1 of reverse power protection operates to trip. 335 32R1.Alm Stage 1 of reverse power protection operates to alarm. 336 32R2.On Stage 2 of reverse power protection is enabled. 337 32R2.St Stage 2 of reverse power protection starts. 338 32R2.Op Stage 2 of reverse power protection operates to trip. Synchrocheck 339 CBx.UL1_Sel To select voltage of Line 1 340 CBx.UL2_Sel To select voltage of Line 2 341 CBx.UB1_Sel To select voltage of Bus 1 342 CBx.UB2_Sel To select voltage of Bus 2 343 CBx.Alm_Invalid_Sel Voltage selection is invalid. To indicate that frequency difference condition for synchronism check 344 CBx.25.Ok_fDiffChk of AR is met, frequency difference between UB and UL is smaller than [25.f_Diff]. To indicate that voltage difference condition for synchronism check of 345 CBx.25.Ok_UDiffChk AR is met, voltage difference between UB and UL is smaller than [25.U_Diff] To indicate phase difference condition for synchronism check of AR is 346 CBx.25.Ok_phiDiffChk met, phase difference between UB and UL is smaller than [25.phi_Diff]. 347 CBx.25.Ok_DdL_DdB Dead line and dead bus condition is met 348 CBx.25.Ok_DdL_LvB Dead line and live bus condition is met 349 CBx.25.Ok_LvL_DdB Live line and dead bus condition is met 350 CBx.25.Chk_LvL Line voltage is greater than the voltage setting [25.U_Lv] 351 CBx.25.Chk_DdL Line voltage is smaller than the voltage setting [25.U_Dd] 352 CBx.25.Chk_LvB Bus voltage is greater than the voltage setting [25.U_Lv] 353 CBx.25.Chk_DdB Bus voltage is smaller than the voltage setting [25.U_Dd] 354 CBx.25.Ok_DdChk To indicate that dead charge check condition of AR is met 355 CBx.25.Ok_SynChk To indicate that synchronism check condition of AR is met 356 CBx.25.Ok_Chk To indicate that synchrocheck condition of AR is met 357 CBx.25.Ok_3PLvChk To indicate that live three-phase check condition is met 9-32 PCS-902 Line Distance Relay Date: 2019-03-01 9 Configurable Function No. Signal Description 358 CBx.25.Alm_VTS_Uref Reference voltage circuit is abnormal 359 CBx.25.Alm_VTS_Usyn Synchronism voltage circuit is abnormal 360 CBx.25.f_Ref Frequency of the voltage used by protection calculation 361 CBx.25.f_Syn Frequency of the voltage used by synchrocheck 362 CBx.25.U_Diff Voltage difference for synchronism check 363 CBx.25.f_Diff Frequency difference for synchronism check 364 CBx.25.phi_Diff Phase difference for synchronism check Auto-reclosing 365 CBx.79.On Automatic reclosure is enabled 366 CBx.79.Off Automatic reclosure is disabled 367 CBx.79.Close Output of auto-reclosing signal 368 CBx.79.Ready Automatic reclosure have been ready for reclosing cycle 369 CBx.79.AR_Blkd Automatic reclosure is blocked 370 CBx.79.Active Automatic reclosing logic is actived 371 CBx.79.Inprog Automatic reclosing cycle is in progress 372 CBx.79.Inprog_1P The first 1-pole AR cycle is in progress 373 CBx.79.Inprog_3P 3-pole AR cycle is in progress 374 CBx.79.Inprog_3PS1 First 3-pole AR cycle is in progress 375 CBx.79.Inprog_3PS2 Second 3-pole AR cycle is in progress 376 CBx.79.Inprog_3PS3 Third 3-pole AR cycle is in progress 377 CBx.79.Inprog_3PS4 Fourth 3-pole AR cycle is in progress 378 CBx.79.WaitToSlave 379 CBx.79.Perm_Trp1P 380 CBx.79.Perm_Trp3P Waiting signal of automatic reclosing which will be sent to slave (when reclosing multiple circuit breakers) Single-phase circuit breaker will be tripped once protection device operates Three-phase circuit breaker will be tripped once protection device operates Automatic reclosure status 381 CBx.79.Rcls_Status 0: AR is ready. 1: AR is in progress. 2: AR is successful. 382 CBx.79.Fail_Rcls Auto-reclosing fails 383 CBx.79.Succ_Rcls Auto-reclosing is successful 384 CBx.79.Fail_Chk Synchrocheck for AR fails 385 CBx.79.Mode_1PAR Output of 1-pole AR mode 386 CBx.79.Mode_3PAR Output of 3-pole AR mode 387 CBx.79.Mode_1/3PAR Output of 1/3-pole AR mode Transfer trip 388 TT.Alm Input signal of receiving transfer trip is abnormal 389 TT.Op Transfer trip operates 390 TT.On Transfer trip is enabled Trip logic PCS-902 Line Distance Relay 9-33 Date: 2019-03-01 9 Configurable Function No. Signal Description 391 Line.Trp3P_PSFail Initiating three-phase tripping due to failure in fault phase selection 392 CBx.TRP.On Tripping logic is enabled. 393 CBx.TrpA Tripping A-phase circuit breaker 394 CBx.TrpB Tripping B-phase circuit breaker 395 CBx.TrpC Tripping C-phase circuit breaker 396 CBx.Trp Tripping any phase circuit breaker 397 CBx.Trp3P Tripping three-phase circuit breaker 398 CBx.BFI_A 399 CBx.BFI_B 400 CBx.BFI_ C 401 CBx.BFI 402 CBx.TRP.BlkAR Protection tripping signal of A-phase configured to initiate BFP, BFI signal shall be reset immediately after tripping signal drops off. Protection tripping signal of B-phase configured to initiate BFP, BFI signal shall be reset immediately after tripping signal drops off. Protection tripping signal of C-phase configured to initiate BFP, BFI signal shall be reset immediately after tripping signal drops off. Protection tripping signal configured to initiate BFP, BFI signal shall be reset immediately after tripping signal drops off. Blocking auto-reclosing VT circuit supervision 403 VTS.Alm Alarm signal to indicate VT circuit fails 404 VTNS.Alm Alarm signal to indicate VT neutral point fails CT circuit supervision 405 CBx.CTS.Alm Alarm signal to indicate CT circuit fails Control and synchrocheck for manual closing 406 CSWI01.Op_Opn Open output of binary output No.01. 407 CSWI01.Op_Cls Closing output of binary output No.01. 408 CSWI02.Op_Opn Open output of binary output No.02. 409 CSWI02.Op_Cls Closing output of binary output No.02. 410 CSWI03.Op_Opn Open output of binary output No.03. 411 CSWI03.Op_Cls Closing output of binary output No.03. 412 CSWI04.Op_Opn Open output of binary output No.04. 413 CSWI04.Op_Cls Closing output of binary output No.04. 414 CSWI05.Op_Opn Open output of binary output No.05. 415 CSWI05.Op_Cls Closing output of binary output No.05. 416 CSWI06.Op_Opn Open output of binary output No.06. 417 CSWI06.Op_Cls Closing output of binary output No.06. 418 CSWI07.Op_Opn Open output of binary output No.07. 419 CSWI07.Op_Cls Closing output of binary output No.07. 420 CSWI08.Op_Opn Open output of binary output No.08. 421 CSWI08.Op_Cls Closing output of binary output No.08. 422 CSWI09.Op_Opn Open output of binary output No.09. 423 CSWI09.Op_Cls Closing output of binary output No.09. 424 CSWI10.Op_Opn Open output of binary output No.10. 425 CSWI10.Op_Cls Closing output of binary output No.10. 9-34 PCS-902 Line Distance Relay Date: 2019-03-01 9 Configurable Function No. Signal Description 426 CSWI11.Op_Opn Open output of binary output No.11. 427 CSWI11.Op_Cls Closing output of binary output No.11. 428 CSWI12.Op_Opn Open output of binary output No.12. 429 CSWI12.Op_Cls Closing output of binary output No.12. 430 CSWI13.Op_Opn Open output of binary output No.13. 431 CSWI13.Op_Cls Closing output of binary output No.13. 432 CSWI14.Op_Opn Open output of binary output No.14. 433 CSWI14.Op_Cls Closing output of binary output No.14. 434 CSWI15.Op_Opn Open output of binary output No.15. 435 CSWI15.Op_Cls Closing output of binary output No.15. 436 BIinput.LocCtrl In order to be convenient to user configure control output, three same 437 BIinput.RmtCtrl output signals with input signals are available. The relationship with 15 binary output have been configured inside the device. The user only assigns a specific binary input to input signal, the relevant function can 438 BIinput.CILO.Disable be gained. If some binary output need not be controlled by three signals, please cancel the configuration by PCS-Explorer, and configure it independently. 439 MCBrd.CBx.Alm_VTS VT circuit of circuit breaker No.x is abnormal. Faulty phase selection 440 PhSA Phase-A is selected as faulty phase 441 PhSB Phase-B is selected as faulty phase 442 PhSC Phase-C is selected as faulty phase 443 GndFlt Earth fault PCS-902 Line Distance Relay 9-35 Date: 2019-03-01 9 Configurable Function 9-36 PCS-902 Line Distance Relay Date: 2019-03-01 10 Communication 10 Communication Table of Contents 10 Communication ............................................................................. 10-a 10.1 Overview ...................................................................................................... 10-1 10.2 Rear Communication Port Information ..................................................... 10-1 10.2.1 RS-485 Interface.............................................................................................................. 10-1 10.2.2 Ethernet Interface ............................................................................................................ 10-3 10.2.3 IEC60870-5-103 Communication .................................................................................... 10-4 10.2.4 DNP3.0 Communication .................................................................................................. 10-4 10.3 IEC60870-5-103 Interface over Serial Port ................................................ 10-4 10.3.1 Physical Connection and Link Layer ............................................................................... 10-5 10.3.2 Initialization ...................................................................................................................... 10-5 10.3.3 Time Synchronization ...................................................................................................... 10-5 10.3.4 Spontaneous Events ........................................................................................................ 10-5 10.3.5 General Interrogation ....................................................................................................... 10-6 10.3.6 General Service ............................................................................................................... 10-6 10.3.7 Disturbance Records ....................................................................................................... 10-6 10.4 Messages Description for IEC61850 Protocol .......................................... 10-6 10.4.1 Overview .......................................................................................................................... 10-6 10.4.2 Communication Profiles ................................................................................................... 10-7 10.4.3 MMS Communication Network Deployment ................................................................... 10-8 10.4.4 Server Data Organization ...............................................................................................10-11 10.4.5 Server Features and Configuration ............................................................................... 10-14 10.4.6 ACSI Conformance ........................................................................................................ 10-16 10.4.7 Logical Nodes ................................................................................................................ 10-19 10.5 DNP3.0 Interface........................................................................................ 10-22 10.5.1 Overview ........................................................................................................................ 10-22 PCS-902 Line Distance Relay 10-a Date: 2015-05-19 10 Communication 10.5.2 Link Layer Functions...................................................................................................... 10-22 10.5.3 Transport Functions ....................................................................................................... 10-22 10.5.4 Application Layer Functions........................................................................................... 10-22 List of Figures Figure 10.2-1 EIA RS-485 bus connection arrangements ..................................................... 10-2 Figure 10.2-2 Ethernet communication cable ........................................................................ 10-3 Figure 10.2-3 Ethernet communication structure .................................................................. 10-4 Figure 10.4-1 Dual-net full duplex mode sharing the RCB block instance ......................... 10-9 Figure 10.4-2 Dual-net hot-standby mode sharing the same RCB instance ..................... 10-10 Figure 10.4-3 Dual-net full duplex mode with 2 independent RCB instances .................. 10-11 10-b PCS-902 Line Distance Relay Date: 2015-05-19 10 Communication 10.1 Overview This section outlines the remote communications interfaces of NR Relays. The protective device supports a choice of three protocols via the rear communication interface (RS-485 or Ethernet), selected via the model number by setting. The protocol provided by the protective device is indicated in the menu “Settings→Device Setup→Comm Settings”. The rear EIA RS-485 interface is isolated and is suitable for permanent connection of whichever protocol is selected. The advantage of this type of connection is that up to 32 protective devices can be “daisy chained” together using a simple twisted pair electrical connection. It should be noted that the descriptions contained within this section do not aim to fully detail the protocol itself. The relevant documentation for the protocol should be referred to for this information. This section serves to describe the specific implementation of the protocol in the relay. 10.2 Rear Communication Port Information 10.2.1 RS-485 Interface This protective device provides two rear RS-485 communication ports, and each port has three terminals in the 12-terminal screw connector located on the back of the relay and each port has a ground terminal for the earth shield of the communication cable. The rear ports provide RS-485 serial data communication and are intended for use with a permanently wired connection to a remote control center. 10.2.1.1 EIA RS-485 Standardized Bus The EIA RS-485 two-wire connection provides a half-duplex fully isolated serial connection to the product. The connection is polarized and whilst the product’s connection diagrams indicate the polarization of the connection terminals it should be borne in mind that there is no agreed definition of which terminal is which. If the master is unable to communicate with the product, and the communication parameters match, then it is possible that the two-wire connection is reversed. 10.2.1.2 Bus Termination The EIA RS-485 bus must have 120Ω (Ohm) ½ Watt terminating resistors fitted at either end across the signal wires (refer to Figure 10.2-1). Some devices may be able to provide the bus terminating resistors by different connection or configuration arrangements, in which case separate external components will not be required. However, this product does not provide such a facility, so if it is located at the bus terminus then an external termination resistor will be required. PCS-902 Line Distance Relay 10-1 Date: 2015-05-19 Master EIA RS-485 10 Communication 120 Ohm 120 Ohm Slave Slave Slave Figure 10.2-1 EIA RS-485 bus connection arrangements 10.2.1.3 Bus Connections & Topologies The EIA RS-485 standard requires that each device is directly connected to the physical cable that is the communications bus. Stubs and tees are expressly forbidden, such as star topologies. Loop bus topologies are not part of the EIA RS-485 standard and are forbidden by it also. Two-core screened cable is recommended. The specification of the cable will be dependent on the application, although a multi-strand 0.5mm 2 per core is normally adequate. Total cable length must not exceed 500m. The screen must be continuous and connected to ground at one end, normally at the master connection point; it is important to avoid circulating currents, especially when the cable runs between buildings, for both safety and noise reasons. This product does not provide a signal ground connection. If a signal ground connection is present in the bus cable then it must be ignored, although it must have continuity for the benefit of other devices connected to the bus. At no stage must the signal ground be connected to the cables screen or to the product’s chassis. This is for both safety and noise reasons. 10.2.1.4 Biasing It may also be necessary to bias the signal wires to prevent jabber. Jabber occurs when the signal level has an indeterminate state because the bus is not being actively driven. This can occur when all the slaves are in receive mode and the master is slow to turn from receive mode to transmit mode. This may be because the master purposefully waits in receive mode, or even in a high impedance state, until it has something to transmit. Jabber causes the receiving device(s) to miss the first bits of the first character in the packet, which results in the slave rejecting the message and consequentially not responding. Symptoms of these are poor response times (due to retries), increasing message error counters, erratic communications, and even a complete failure to communicate. Biasing requires that the signal lines be weakly pulled to a defined voltage level of about 1V. There should only be one bias point on the bus, which is best situated at the master connection point. The DC source used for the bias must be clean; otherwise noise will be injected. Note that some devices may (optionally) be able to provide the bus bias, in which case external components will not be required. 10-2 PCS-902 Line Distance Relay Date: 2015-05-19 10 Communication NOTICE! It is extremely important that the 120Ω termination resistors are fitted. Failure to do so will result in an excessive bias voltage that may damage the devices connected to the bus. As the field voltage is much higher than that required, NR cannot assume responsibility for any damage that may occur to a device connected to the network as a result of incorrect application of this voltage. Ensure that the field voltage is not being used for other purposes (i.e. powering logic inputs) as this may cause noise to be passed to the communication network. 10.2.2 Ethernet Interface This protective device can provide four rear Ethernet interfaces (optional) and they are unattached each other. Parameters of each Ethernet port can be configured in the menu “Settings→Device Setup→Comm Settings”. 10.2.2.1 Ethernet Standardized Communication Cable It is recommended to use twisted screened eight-core cable as the communication cable. A picture is shown bellow. Figure 10.2-2 Ethernet communication cable 10.2.2.2 Connections and Topologies Each equipment is connected with an exchanger via communication cable, and thereby it forms a star structure network. Dual-network is recommended in order to increase reliability. SCADA is also connected to the exchanger and will play a role of master station, so the every equipment which has been connected to the exchanger will play a role of slave unit. PCS-902 Line Distance Relay 10-3 Date: 2015-05-19 10 Communication SCADA Switch: Net A Switch: Net B …… Figure 10.2-3 Ethernet communication structure 10.2.3 IEC60870-5-103 Communication The IEC specification IEC60870-5-103: Telecontrol Equipment and Systems, Part 5: Transmission Protocols Section 103 defines the use of standards IEC60870-5-1 to IEC60870-5-5 to perform communication with protective device. The standard configuration for the IEC60870-5-103 protocol is to use a twisted pair EIA RS-485 connection over distances up to 500m. It also supports to use an Ethernet connection. The relay operates as a slave in the system, responding to commands from a master station. To use the rear port with IEC60870-5-103 communication, the relevant settings to the protective device must be configured. 10.2.4 DNP3.0 Communication The DNP3.0 (Distributed Network Protocol) protocol can support the OSI/EPA model of the ISO (International Organization for Standards), and it includes four parts: application layer protocol, transport functions, data link layer protocol and data object library. The DNP3.0 protocol is recommended to use the Ethernet network. This relay operates as a slave in the system, responding to commands from a master station. 10.3 IEC60870-5-103 Interface over Serial Port The IEC60870-5-103 interface over serial port (RS-485) is a master/slave interface with the protective device as the slave device. It is properly developed by NR. The protective device conforms to compatibility level 3. The following IEC60870-5-103 facilities are supported by this interface: Initialization (reset) 10-4 PCS-902 Line Distance Relay Date: 2015-05-19 10 Communication Time synchronization Event record extraction General interrogation General commands Disturbance records 10.3.1 Physical Connection and Link Layer Two EIA RS-485 standardized ports are available for IEC60870-5-103 in this protective device. The transmission speed is optional: 4800 bit/s, 9600 bit/s, 19200 bit/s or 38400 bit/s. The link layer strictly abides by the rules defined in the IEC60870-5-103. 10.3.2 Initialization Whenever the protective device has been powered up, or if the communication parameters have been changed, a reset command is required to initialize the communications. The protective device will respond to either of the two reset commands (Reset CU or Reset FCB), the difference is that the Reset CU will clear any unsent messages in the transmit buffer. The protective device will respond to the reset command with an identification message ASDU 5, the COT (Cause Of Transmission) of this response will be either Reset CU or Reset FCB depending on the nature of the reset command. 10.3.3 Time Synchronization The protective device time and date can be set using the time synchronization feature of the IEC60870-5-103 protocol. The protective device will correct for the transmission delay as specified in IEC60870-5-103. If the time synchronization message is sent as a send/confirm message then the protective device will respond with a confirmation. Whether the time-synchronization message is sent as a send confirmation or a broadcast (send/no reply) message, a time synchronization class 1 event will be generated/produced. If the protective device clock is synchronized using the IRIG-B input then it will not be possible to set the protective device time using the IEC60870-5-103 interface. An attempt to set the time via the interface will cause the protective device to create an event with the current date and time taken from the IRIG-B synchronized internal clock. 10.3.4 Spontaneous Events Events are categorized using the following information: Type identification (TYP) Function type (FUN) Information number (INF) Messages sent to substation automation system are grouped according to IEC60870-5-103 protocol. Operating elements are sent by ASDU2 (time-tagged message with relative time), and PCS-902 Line Distance Relay 10-5 Date: 2015-05-19 10 Communication status of binary signal and alarm element are sent by ASDU1 (time-tagged message). The cause of transmission (COT) of these responses is 1. All spontaneous events can be gained by printing, implementing submenu “IEC103 Info” in the menu “Print”. 10.3.5 General Interrogation The GI can be used to read the status of the relay, the function numbers, and information numbers that will be returned during the GI cycle. The GI cycle strictly abides by the rules defined in the IEC60870-5-103. Refer the IEC60870-5-103 standard can get the enough details about general interrogation. 10.3.6 General Service The generic functions can be used to read the setting and protection measurement of the protective device, and modify the setting. Two supported type identifications are ASDU 21 and ASDU 10. For more details about generic functions, see the IEC60870-5-103 standard. All general classification service group numbers can be gained by printing, implementing submenu “IEC103 Info” in the menu “Print”. 10.3.7 Disturbance Records This protective device can store up to 32 disturbance records in its memory. A pickup of the fault detector or an operation of the relay can make the protective device store the disturbance records. The disturbance records are stored in uncompressed format and can be extracted using the standard mechanisms described in IEC60870-5-103. All channel numbers (ACC) of disturbance data can be gained by printing, implementing submenu “IEC103 Info” in the menu “Print”. 10.4 Messages Description for IEC61850 Protocol 10.4.1 Overview The IEC 61850 standard is the result of years of work by electric utilities and vendors of electronic equipment to produce standardized communications systems. IEC 61850 is a series of standards describing client/server and peer-to-peer communications, substation design and configuration, testing, environmental and project standards. The complete set includes: IEC 61850-1: Introduction and overview IEC 61850-2: Glossary IEC 61850-3: General requirements IEC 61850-4: System and project management IEC 61850-5: Communications and requirements for functions and device models 10-6 PCS-902 Line Distance Relay Date: 2015-05-19 10 Communication IEC 61850-6: Configuration description language for communication in electrical substations related to IEDs IEC 61850-7-1: Basic communication structure for substation and feeder equipment– Principles and models IEC 61850-7-2: Basic communication structure for substation and feeder equipment - Abstract communication service interface (ACSI) IEC 61850-7-3: Basic communication structure for substation and feeder equipment– Common data classes IEC 61850-7-4: Basic communication structure for substation and feeder equipment– Compatible logical node classes and data classes IEC 61850-8-1: Specific Communication Service Mapping (SCSM) – Mappings to MMS (ISO 9506-1 and ISO 9506-2) and to ISO/IEC 8802-3 IEC 61850-9-1: Specific Communication Service Mapping (SCSM) – Sampled values over serial unidirectional multidrop point to point link IEC 61850-9-2: Specific Communication Service Mapping (SCSM) – Sampled values over ISO/IEC 8802-3 IEC 61850-10: Conformance testing These documents can be obtained from the IEC (http://www.iec.ch). It is strongly recommended that all those involved with any IEC 61850 implementation obtain this document set. 10.4.2 Communication Profiles The PCS-900 series relay supports IEC 61850 server services over TCP/IP communication protocol stacks. The TCP/IP profile requires the PCS-900 series to have an IP address to establish communications. These addresses are located in the menu “Settings→Device Setup→Comm Settings”. 1. MMS protocol IEC 61850 specifies the use of the Manufacturing Message Specification (MMS) at the upper (application) layer for transfer of real-time data. This protocol has been in existence for a number of years and provides a set of services suitable for the transfer of data within a substation LAN environment. IEC 61850-7-2 abstract services and objects are mapped to actual MMS protocol services in IEC61850-8-1. 2. Client/server This is a connection-oriented type of communication. The connection is initiated by the client, and communication activity is controlled by the client. IEC61850 clients are often substation computers running HMI programs or SOE logging software. Servers are usually substation equipment such as protection relays, meters, RTUs, transformer, tap changers, or bay controllers. 3. Peer-to-peer PCS-902 Line Distance Relay 10-7 Date: 2015-05-19 10 Communication This is a non-connection-oriented, high speed type of communication usually between substation equipment, such as protection relays, intelligent terminal. GOOSE is the method of peer-to-peer communication. 4. Substation configuration language (SCL) A substation configuration language is a number of files used to describe IED configurations and communication systems according to IEC 61850-5 and IEC 61850-7. Each configured device has an IED Capability Description (ICD) file and a Configured IED Description (CID) file. The substation single line information is stored in a System Specification Description (SSD) file. The entire substation configuration is stored in a Substation Configuration Description (SCD) file. The SCD file is the combination of the individual ICD files and the SSD file, moreover, add communication system parameters (MMS, GOOSE, control block, SV control block) and the connection relationship of GOOSE and SV to SCD file. 10.4.3 MMS Communication Network Deployment In order to enhance the stability and reliability of SAS, dual-MMS Ethernet is widely adopted. This section is applied to introduce the details of dual-MMS Ethernet technology. Generally, single-MMS Ethernet is recommended to be adopted in the SAS of 110kV and lower voltage levels, while dual-MMS Ethernet is recommended to be adopted in the SAS of voltage levels above 110kV. Client-server mode is adopted: clients (SCADA, control center and etc.) communicate with the IEDs via MMS communication network, and the IEDs operate as the servers. IEDs are connected to clients passively, and they can interact with the clients according to the configuration and the issued command of the clients. Three modes for dual-MMS Ethernet (abbreviated as dual-net) are provided as below. NOTICE! Hereinafter, the normal operation status of net means the physical link and TCP link are both ok. The abnormal operation status of net means physical link or TCP link is broken. 10-8 PCS-902 Line Distance Relay Date: 2015-05-19 10 Communication 10.4.3.1 Dual-net Full Duplex Mode Sharing the Same RCB Instance Client Client Net A Net B Net A Net B Report Instance 1 RptEna = true Report Instance 1 RptEna = true Report Control Block Report Control Block IED (Server) IED (Server) Normal operation status Abnormal operation status TCP Link MMS Link Figure 10.4-1 Dual-net full duplex mode sharing the RCB block instance Net A and Net B share the same report control block (abbreviated as RCB) enabled by the client. IED sends undifferentiated date through dual-net to the clients. If one net is physically disconnected, the flag of RCB instance (i.e.: “RptEna” in above figure) is still “true”. Only when both Net A and Net B are disconnected, the flag of the RCB instance will automatically change to “false”. In normal operation status of this mode, IED provides the same MMS service for Net A and Net B. If one net is physically disconnected (i.e.: “Abnormal operation status” in above figure), the working mode will switch to single-net mode seamlessly and immediately. Network communication supervision is unnecessary here, and Buffered Report Control Block (abbreviated as BRCB) need not to be used. On the other net, date alternation works normally. Therefore, MMS service can interact normally without interruption. This mode ensures no data loss during one net is in abnormal operation status. In this mode, one report will be transmitted twice via dual nets for the same report instance, so the client needs to distinguish whether two reports are same according to corresponding EntryIDs. PCS-902 Line Distance Relay 10-9 Date: 2015-05-19 10 Communication 10.4.3.2 Dual-net Hot-standby Mode Sharing the Same RCB Instance Client Net A Client Net B Net A Net B Report Instance 1 RptEna = true Report Instance 1 RptEna = true Report Control Block Report Control Block IED (Server) IED (Server) Normal operation status Abnormal operation status TCP Link Main MMS Link Standby MMS Link Figure 10.4-2 Dual-net hot-standby mode sharing the same RCB instance In this mode, the MMS service is provided on main MMS link, no MMS service interacts on the standby MMS link. The definitions of two links are as follows: Main MMS Link: Physically connected, TCP level connected, MMS report service available. Standby MMS Link: Physically connected, TCP level connected, MMS report service not available. If the main net fails to operate (i.e.: “Abnormal operation status” in the above figure), the IED will set “RptEna” to “false”. Meanwhile the client will detect the failure by heartbeat message or “keep-alive”, it will automatically enable the RCB instance by setting “RptEna” back to “true” through standby MMS link. By the buffer function of BRCB, the IED can provide uninterrupted MMS service on the standby net. However, the differences of BRCB standards among different manufacturers may cause data loss. Moreover, if duration of net switch is too long, the data loss is positively as the capacity of BRCB’s buffer function is limited. NOTICE! The first mode and second mode, Net A IED host address and Net B IED host address must be the same. For example, if the subnet mask is “255.255.0.0”, network prefix of Net A is “198.120.0.0”, network prefix of Net B is “198.121.0.0”, Net A IP address of the IED is “198.120.1.2”, and then Net B IP address of the IED must be configured as “198.121.1.2”, i.e., Net A IED host address =1x256+2=258, Net B IED host address =1x256+2=258, Net A IED host address equals to Net B IED host address. 10-10 PCS-902 Line Distance Relay Date: 2015-05-19 10 Communication 10.4.3.3 Dual-net Full Duplex Mode with 2 Independent RCB Instances Client Net A Client Net B Report Instance 1 RptEna = true Report Instance 2 RptEna = true Net A Net B Report Instance 1 RptEna = true Report Instance 2 RptEna = true Report Control Block Report Control Block IED (Server) IED (Server) Normal operation status Abnormal operation status TCP Link MMS Link Figure 10.4-3 Dual-net full duplex mode with 2 independent RCB instances In this mode, IED provides 2 report instances for each RCB, Net A and Net B work independently from each other, failures of any net will not affect the other net at all. Tow report instances are required for each client. Therefore, the IED may be unable to provide enough report instances if there are too many clients. Net A and Net B send the same report separately when they operates normally, To ensure no repeated data is saved into database, massive calculation is required for the client. Moreover, accurate clock synchronization of the IED is required to distinguish whether 2 reports are the same report according to the timestamps. Clock synchronization error of the IED may lead to report loss/redundancy. As a conclusion, for the second mode, it’s difficult to realize seamless switchover between dual nets, however, for the third mode, the IED may be unable to provide enough report instances if too many clients are applied on site. Considering client treatment and IED implementation, the first mode (Dual-net full duplex mode sharing the same report instance) is recommended for MMS communication network deployment. 10.4.4 Server Data Organization IEC61850 defines an object-oriented approach to data and services. An IEC61850 physical device can contain one or more logical device(s) (for proxy). Each logical device can contain many logical nodes. Each logical node can contain many data objects. Each data object is composed of data attributes and data attribute components. Services are available at each level for performing various functions, such as reading, writing, control commands, and reporting. Each IED represents one IEC61850 physical device. The physical device contains one or more logical device(s), and the logical device contains many logical nodes. The logical node LPHD contains information about the IED physical device. The logical node LLN0 contains common PCS-902 Line Distance Relay 10-11 Date: 2015-05-19 10 Communication information about the IED logical device. 10.4.4.1 Digital Status Values The GGIO logical node is available in the PCS-900 series relays to provide access to digital status points (including general I/O inputs and warnings) and associated timestamps and quality flags. The data content must be configured before the data can be used. GGIO provides digital status points for access by clients. It is intended that clients use GGIO in order to access digital status values from the PCS-900 series relays. Clients can utilize the IEC61850 buffered reporting features available from GGIO in order to build sequence of events (SOE) logs and HMI display screens. Buffered reporting should generally be used for SOE logs since the buffering capability reduces the chances of missing data state changes. All needed status data objects are transmitted to HMI clients via buffered reporting, and the corresponding buffered reporting control block (BRCB) is defined in LLN0. 10.4.4.2 Analog Values Most of analog measured values are available through the MMXU logical nodes, and metering values in MMTR, the else in MMXN, MSQI and so on. Each MMXU logical node provides data from a IED current/voltage “source”. There is one MMXU available for each configurable source. MMXU1 provides data from CT/VT source 1(usually for protection purpose), and MMXU2 provides data from CT/VT source 2 (usually for monitor and display purpose). All these analog data objects are transmitted to HMI clients via unbuffered reporting periodically, and the corresponding unbuffered reporting control block (URCB) is defined in LLN0. MMXUx logical nodes provide the following data for each source: MMXU.MX.Hz: frequency MMXU.MX.PPV.phsAB: phase AB voltage magnitude and angle MMXU.MX.PPV.phsBC: phase BC voltage magnitude and angle MMXU.MX.PPV.phsCA: Phase CA voltage magnitude and angle MMXU.MX.PhV.phsA: phase AG voltage magnitude and angle MMXU.MX.PhV.phsB: phase BG voltage magnitude and angle MMXU.MX.PhV.phsC: phase CG voltage magnitude and angle MMXU.MX.A.phsA: phase A current magnitude and angle MMXU.MX.A.phsB: phase B current magnitude and angle MMXU.MX.A.phsC: phase C current magnitude and angle 10.4.4.3 Protection Logical Nodes The following list describes the protection elements for PCS-902 series relays. The specified relay will contain a subset of protection elements from this list. PDIS: Phase-to-phase distance, phase-to-ground distance and SOTF distance 10-12 PCS-902 Line Distance Relay Date: 2015-05-19 10 Communication PTUC: Undercurrent PTOC: Phase overcurrent, zero-sequence overcurrent and overcurrent when VT circuit failure PTTR: Thermal overload PTUV: Undervoltage PTOV: Overvoltage and auxiliary overvoltage PTOF: Overfrequency PTUF: Underfrequency PPDP: Pole discrepancy PSCH: Protection scheme RBRF: Breaker failure RPSB: Power swing detection/blocking RREC: Automatic reclosing RSYN: Synchronism-check RFLO: Fault location The protection elements listed above contain start (pickup) and operate flags, instead of any element has its own start (pickup) flag separately, all the elements share a common start (pickup) flags “PTRC.ST.Str.general”. The operate flag for PTOC1 is “PTOC1.ST.Op.general”. For PCS-902 series relays protection elements, these flags take their values from related module for the corresponding element. Similar to digital status values, the protection trip information is reported via BRCB, and BRCB also locates in LLN0. 10.4.4.4 LLN0 and Other Logical Nodes Logical node LLN0 is essential for an IEC61850 based IED. This LN shall be used to address common issues for Logical Devices. Most of the public services, the common settings, control values and some device oriented data objects are available here. The public services may be BRCB, URCB and GSE control blocks and similar global defines for the whole device; the common settings include all the setting items of communication settings, system settings and some of the protection setting items, which can be configured to two or more protection elements (logical nodes). In LLN0, the item Loc is a device control object, this Do item indicates the local operation for complete logical device, when it is true, all the remote control commands to the IED will be blocked and those commands make effective until the item Loc is changed to false. In PCS-900 series relays, besides the logical nodes we describe above, there are some other logical nodes below in the IEDs: MMXU: This LN shall be used to acquire values from CTs and VTs and calculate measurands such as r.m.s. values for current and voltage or power flows out of the acquired voltage and current samples. These values are normally used for operational purposes such as power flow supervision and management, screen displays, state estimation, etc. The requested PCS-902 Line Distance Relay 10-13 Date: 2015-05-19 10 Communication accuracy for these functions has to be provided. LPHD: Physical device information, the logical node to model common issues for physical device. PTRC: Protection trip conditioning, it shall be used to connect the “operate” outputs of one or more protection functions to a common “trip” to be transmitted to XCBR. In addition or alternatively, any combination of “operate” outputs of protection functions may be combined to a new “operate” of PTRC. RDRE: Disturbance recorder function. It triggers the fault wave recorder and its output refers to the “IEEE Standard Format for Transient Data Exchange (COMTRADE) for Power System” (IEC 60255-24). All enabled channels are included in the recording, independently of the trigger mode. 10.4.5 Server Features and Configuration 10.4.5.1 Buffered/unbuffered Reporting IEC61850 buffered and unbuffered reporting control blocks locate in LLN0, they can be configured to transmit information of protection trip information (in the Protection logical nodes), binary status values (in GGIO) and analog measured/calculated values (in MMXU, MMTR and MSQI). The reporting control blocks can be configured in CID files, and then be sent to the IED via an IEC61850 client. The following items can be configured. TrgOps: Trigger options. The following bits are supported by the PCS-900 series relays: - Bit 1: Data-change - Bit 4: Integrity - Bit 5: General interrogation OptFlds: Option Fields. The following bits are supported by the PCS-900 series relays: - Bit 1: Sequence-number - Bit 2: Report-time-stamp - Bit 3: Reason-for-inclusion - Bit 4: Data-set-name - Bit 5: Data-reference - Bit 7: EntryID (for buffered reports only) - Bit 8: Conf-revision - Bit 9: Segmentation 10-14 PCS-902 Line Distance Relay Date: 2015-05-19 10 Communication IntgPd: Integrity period. 10.4.5.2 File Transfer MMS file services are supported to allow transfer of oscillography, event record or other files from a PCS-900 series relay. 10.4.5.3 Timestamps The Universal Time Coordinated(UTC for short) timestamp associated with all IEC61850 data items represents the latest change time of either the value or quality flags of the data item. 10.4.5.4 Logical Node Name Prefixes IEC61850 specifies that each logical node can have a name with a total length of 11 characters. The name is composed of: A five or six-character name prefix. A four-character standard name (for example, MMXU, GGIO, PIOC, etc.). A one or two-character instantiation index. Complete names are of the form xxxxxxPTOC1, where the xxxxxx character string is configurable. Details regarding the logical node naming rules are given in IEC61850 parts 6 and 7-2. It is recommended that a consistent naming convention be used for an entire substation project. 10.4.5.5 GOOSE Services IEC61850 specifies the type of broadcast data transfer services: Generic Object Oriented Substation Events (GOOSE). IEC61850 GOOSE services provide virtual LAN (VLAN) support, Ethernet priority tagging, and Ether-type Application ID configuration. The support for VLANs and priority tagging allows for the optimization of Ethernet network traffic. GOOSE messages can be given a higher priority than standard Ethernet traffic, and they can be separated onto specific VLANs. Devices that transmit GOOSE messages also function as servers. Each GOOSE publisher contains a “GOOSE control block” to configure and control the transmission. The GOOSE transmission (including subscribing and publishing) is controlled by GOOSE logic link settings in device. The PCS-900 series relays support IEC61850 Generic Object Oriented Substation Event (GOOSE) communication. All GOOSE messages contain IEC61850 data collected into a dataset. It is this dataset that is transferred using GOOSE message services. The GOOSE related dataset is configured in the CID file and it is recommended that the fixed GOOSE be used for implementations that require GOOSE data transfer between PCS-900 series relays. IEC61850 GOOSE messaging contains a number of configurable parameters, all of which must be correct to achieve the successful transfer of data. It is critical that the configured datasets at the transmission and reception devices are an exact match in terms of data structure, and that the GOOSE addresses and name strings match exactly. PCS-902 Line Distance Relay 10-15 Date: 2015-05-19 10 Communication 10.4.6 ACSI Conformance 10.4.6.1 ACSI Basic Conformance Statement Services Client Server PCS-900 Series B11 Server side (of Two-party Application-Association) - C1 Y B12 Client side (of Two-party Application-Association) C1 - N Client-Server Roles SCSMS Supported B21 SCSM: IEC 61850-8-1 used Y Y Y B22 SCSM: IEC 61850-9-1 used N N N B23 SCSM: IEC 61850-9-2 used Y N Y B24 SCSM: other N N N Generic Substation Event Model (GSE) B31 Publisher side - O Y B32 Subscriber side O - Y Transmission Of Sampled Value Model (SVC) B41 Publisher side - O N B42 Subscriber side O - N Where: C1: Shall be "M" if support for LOGICAL-DEVICE model has been declared O: Optional M: Mandatory Y: Supported by PCS-900 series relays N: Currently not supported by PCS-900 series relays 10.4.6.2 ACSI Models Conformance Statement Services Client Server PCS-900 Series M1 Logical device C2 C2 Y M2 Logical node C3 C3 Y M3 Data C4 C4 Y M4 Data set C5 C5 Y M5 Substitution O O Y M6 Setting group control O O Y M7 Buffered report control O O Y M7-1 sequence-number Y Y Y M7-2 report-time-stamp Y Y Y M7-3 reason-for-inclusion Y Y Y M7-4 data-set-name Y Y Y M7-5 data-reference Y Y Y Reporting 10-16 PCS-902 Line Distance Relay Date: 2015-05-19 10 Communication M7-6 buffer-overflow Y Y N M7-7 entryID Y Y Y M7-8 BufTm N N N M7-9 IntgPd Y Y Y M7-10 GI Y Y Y M8 Unbuffered report control M M Y M8-1 sequence-number Y Y Y M8-2 report-time-stamp Y Y Y M8-3 reason-for-inclusion Y Y Y M8-4 data-set-name Y Y Y M8-5 data-reference Y Y Y M8-6 BufTm N N N M8-7 IntgPd N Y Y M9 Log control O O N M9-1 IntgPd N N N M10 Log O O N M12 GOOSE O O Y M13 GSSE O O N M14 Multicast SVC O O N M15 Unicast SVC O O N M16 Time M M Y M17 File transfer O O Y Logging GSE Where: C2: Shall be "M" if support for LOGICAL-NODE model has been declared C3: Shall be "M" if support for DATA model has been declared C4: Shall be "M" if support for DATA-SET, Substitution, Report, Log Control, or Time models has been declared C5: Shall be "M" if support for Report, GSE, or SMV models has been declared M: Mandatory Y: Supported by PCS-900 series relays N: Currently not supported by PCS-900 series relays 10.4.6.3 ACSI Services Conformance Statement Services Server/Publisher PCS-902 M Y Server S1 ServerDirectory Application association PCS-902 Line Distance Relay 10-17 Date: 2015-05-19 10 Communication S2 Associate M Y S3 Abort M Y S4 Release M Y M Y Logical device S5 LogicalDeviceDirectory Logical node S6 LogicalNodeDirectory M Y S7 GetAllDataValues M Y S8 GetDataValues M Y S9 SetDataValues M Y S10 GetDataDirectory M Y S11 GetDataDefinition M Y S12 GetDataSetValues M Y S13 SetDataSetValues O Y S14 CreateDataSet O N S15 DeleteDataSet O N S16 GetDataSetDirectory M Y M Y Data Data set Substitution S17 SetDataValues Setting group control S18 SelectActiveSG M/O Y S19 SelectEditSG M/O Y S20 SetSGValuess M/O Y S21 ConfirmEditSGValues M/O Y S22 GetSGValues M/O Y S23 GetSGCBValues M/O Y Reporting Buffered report control block S24 Report M Y S24-1 data-change M Y S24-2 qchg-change M N S24-3 data-update M N S25 GetBRCBValues M Y S26 SetBRCBValues M Y Unbuffered report control block S27 Report M Y S27-1 data-change M Y S27-2 qchg-change M N S27-3 data-update M N S28 GetURCBValues M Y 10-18 PCS-902 Line Distance Relay Date: 2015-05-19 10 Communication S29 SetURCBValues M Y Logging Log control block S30 GetLCBValues O N S31 SetLCBValues O N S32 QueryLogByTime O N S33 QueryLogAfter O N S34 GetLogStatusValues O N Log Generic substation event model (GSE) GOOSE control block S35 SendGOOSEMessage M Y S36 GetGoReference O Y S37 GetGOOSEElementNumber O N S38 GetGoCBValues M Y S39 SetGoCBValuess M N S51 Select O N S52 SelectWithValue M Y S53 Cancel M Y S54 Operate M Y S55 Command-Termination O Y S56 TimeActivated-Operate O N Control File transfer S57 GetFile M/O Y S58 SetFile O N S59 DeleteFile O N S60 GetFileAttributeValues M/O Y M Y Time SNTP 10.4.7 Logical Nodes 10.4.7.1 Logical Nodes Table The PCS-902 series relays support IEC61850 logical nodes as indicated in the following table. Note that the actual instantiation of each logical node is determined by the product order code. Nodes PCS-902 L: System Logical Nodes LPHD: Physical device information YES LLN0: Logical node zero YES P: Logical Nodes For Protection Functions - PDIF: Differential PCS-902 Line Distance Relay 10-19 Date: 2015-05-19 10 Communication - PDIR: Direction comparison PDIS: Distance YES PDOP: Directional overpower - PDUP: Directional underpower - PFRC: Rate of change of frequency - PHAR: Harmonic restraint - PHIZ: Ground detector - PIOC: Instantaneous overcurrent - PMRI: Motor restart inhibition - PMSS: Motor starting time supervision - POPF: Over power factor - PPAM: Phase angle measuring - PSCH: Protection scheme YES PSDE: Sensitive directional earth fault - PTEF: Transient earth fault - PTOC: Time overcurrent YES PTOF: Overfrequency YES PTOV: Overvoltage YES PTRC: Protection trip conditioning YES PTTR: Thermal overload YES - PTUC: Undercurrent PPDP: Pole discrepancy YES PTUV: Undervoltage YES - PUPF: Underpower factor PTUF: Underfrequency YES PVOC: Voltage controlled time overcurrent - PVPH: Volts per Hz - PZSU: Zero speed or underspeed - R: Logical Nodes For Protection Related Functions RDRE: Disturbance recorder function YES RADR: Disturbance recorder channel analogue - RBDR: Disturbance recorder channel binary - RDRS: Disturbance record handling - RBRF: Breaker failure YES - RDIR: Directional element RFLO: Fault locator YES RPSB: Power swing detection/blocking YES RREC: Autoreclosing YES RSYN: Synchronism-check or synchronizing YES C: Logical Nodes For Control CALH: Alarm handling - CCGR: Cooling group control - 10-20 PCS-902 Line Distance Relay Date: 2015-05-19 10 Communication CILO: Interlocking YES - CPOW: Point-on-wave switching CSWI: Switch controller YES G: Logical Nodes For Generic References GAPC: Generic automatic process control YES GGIO: Generic process I/O YES - GSAL: Generic security application I: Logical Nodes For Interfacing And Archiving IARC: Archiving - IHMI: Human machine interface - ITCI: Telecontrol interface - ITMI: Telemonitoring interface - A: Logical Nodes For Automatic Control ANCR: Neutral current regulator - ARCO: Reactive power control - ATCC: Automatic tap changer controller - AVCO: Voltage control - M: Logical Nodes For Metering And Measurement MDIF: Differential measurements - MHAI: Harmonics or interharmonics - MHAN: Non phase related harmonics or interharmonic - MMTR: Metering YES MMXN: Non phase related measurement YES MMXU: Measurement YES MSQI: Sequence and imbalance YES - MSTA: Metering statistics S: Logical Nodes For Sensors And Monitoring SARC: Monitoring and diagnostics for arcs - SIMG: Insulation medium supervision (gas) - SIML: Insulation medium supervision (liquid) - SPDC: Monitoring and diagnostics for partial discharges - X: Logical Nodes For Switchgear TCTR: Current transformer YES TVTR: Voltage transformer YES Y: Logical Nodes For Power Transformers YEFN: Earth fault neutralizer (Peterson coil) - YLTC: Tap changer - YPSH: Power shunt - YPTR: Power transformer - Z: Logical Nodes For Further Power System Equipment ZAXN: Auxiliary network - ZBAT: Battery - PCS-902 Line Distance Relay 10-21 Date: 2015-05-19 10 Communication ZBSH: Bushing - ZCAB: Power cable - ZCAP: Capacitor bank - ZCON: Converter - ZGEN: Generator - ZGIL: Gas insulated line - ZLIN: Power overhead line - ZMOT: Motor - ZREA: Reactor - ZRRC: Rotating reactive component - ZSAR: Surge arrestor - ZTCF: Thyristor controlled frequency converter - ZTRC: Thyristor controlled reactive component - 10.5 DNP3.0 Interface 10.5.1 Overview The descriptions given here are intended to accompany this relay. The DNP3.0 protocol is not described here; please refer to the DNP3.0 protocol standard for the details about the DNP3.0 implementation. This manual only specifies which objects, variations and qualifiers are supported in this relay, and also specifies what data is available from this relay via DNP3.0. The relay operates as a DNP3.0 slave and supports subset level 3 of the protocol, plus some of the features from level 4. The DNP3.0 communication uses the Ethernet ports (electrical or optical) at the rear side of this relay. 10.5.2 Link Layer Functions Please see the DNP3.0 protocol standard for the details about the linker layer functions. 10.5.3 Transport Functions Please see the DNP3.0 protocol standard for the details about the transport functions. 10.5.4 Application Layer Functions 10.5.4.1 Function Code Function Code Function 0 (0x00) Confirm 1 (0x01) Read 2 (0x02) Write 3 (0x03) Select 4 (0x04) Operate 5 (0x05) Direct Operate 6 (0x06) Direct Operate No Acknowledgment 10-22 PCS-902 Line Distance Relay Date: 2015-05-19 10 Communication Function Code Function 13 (0x0D) Cold Restart 14 (0x0E) Warm Restart 20 (0x14) Enable Unsolicited Responses 21 (0x15) Disable Unsolicited Responses 22 (0x16) Assign Class 23 (0x17) Delay Measurement 10.5.4.2 Supported Object List The supported object groups and object variations are show in the following table. Request: Master may issue/Outstation shall parse Function code: decimalism Qualifier code: hexadecimal OBJECT GROUP & VARIATION Group/Variation REQUEST Description No. Function code Qualifier code 1 (read) 00, 01 (start ~ stop) 22 (assign class) 06 (no range, or all) 1 0 Binary Input: Any Variation 1 1 Binary Input: Packed format 1 (read) 1 2 Binary Input: With flags 1 (read) 2 0 Binary Input Event: Any Variation 1 (read) 2 1 Binary Input Event: Without time 1 (read) 2 2 Binary Input Event: With absolute time 1 (read) 2 3 Binary Input Event: With relative time 1 (read) 10 0 Binary output: Any Variation 1 (read) 10 0 Binary output: Any Variation 1 (read) 10 1 Binary output: Packed format 2 (write) 00, 01 (start ~ stop) 06 (no range, or all) 00, 01 (start ~ stop) 06 (no range, or all) 06 (no range, or all) 07, 08 (limited qty) 06 (no range, or all) 07, 08 (limited qty) 06 (no range, or all) 07, 08 (limited qty) 06 (no range, or all) 07, 08 (limited qty) 00, 01 (start ~ stop) 06 (no range, or all) 00, 01 (start ~ stop) 06 (no range, or all) 00, 01 (start ~ stop) 3 (select) 12 30 1 0 Binary Command: Control relay output block 4 (operate) (CROB) 5 (direct op) Analog Input: Any Variation PCS-902 Line Distance Relay 17, 28 (index) 6 (dir. op, no ack) 17, 28 (index) 1 (read) 00, 01 (start ~ stop) 22 (assign class) 06 (no range, or all) 10-23 Date: 2015-05-19 10 Communication OBJECT GROUP & VARIATION Group/Variation REQUEST Description No. Function code 30 1 Analog Input: 32 ~ bit with flag 1 (read) 30 2 Analog Input: 16 ~ bit with flag 1 (read) 30 3 Analog Input: 32 ~ bit without flag 1 (read) 30 4 Analog Input: 16 ~ bit without flag 1 (read) 30 5 Analog Input: Single ~ prec flt ~ pt with flag 1 (read) 32 0 Analog Input Event: Any Variation 1 (read) 32 1 Analog Input Event: 32 ~ bit without time 1 (read) 32 2 Analog Input Event: 16 ~ bit without time 1 (read) 32 5 34 0 Analog Input Event: Single ~ prec flt ~ pt without time Analog Input Deadband: Any Variation 1 (read) 1 (read) 1 (read) 34 1 Analog Input Deadband: 16 ~ bit 2 (write) 1 (read) 34 2 Analog Input Deadband: 32 ~ bit 2 (write) 1 (read) 34 3 Analog Input Deadband: Single ~ prec flt ~ pt 2 (write) 40 0 Analog Output Status: Any Variation 1 (read) 40 1 Analog Output Status: 32 ~ bit with flag 1 (read) 40 2 Analog Output Status: 16 ~ bit with flag 1 (read) 40 3 Analog Output Status: single ~ prec flt ~ pt with flag 10-24 1 (read) Qualifier code 00, 01 (start ~ stop) 06 (no range, or all) 00, 01 (start ~ stop) 06 (no range, or all) 00, 01 (start ~ stop) 06 (no range, or all) 00, 01 (start ~ stop) 06 (no range, or all) 00, 01 (start ~ stop) 06 (no range, or all) 06 (no range, or all) 07,08 (limited qty) 06 (no range, or all) 07,08 (limited qty) 06 (no range, or all) 07,08 (limited qty) 06 (no range, or all) 07,08 (limited qty) 00, 01 (start ~ stop) 06 (no range, or all) 00, 01 (start ~ stop) 06 (no range, or all) 00, 01 (start ~ stop) 17,28 (index) 00, 01 (start ~ stop) 06 (no range, or all) 00, 01 (start ~ stop) 17,28 (index) 00, 01 (start ~ stop) 06 (no range, or all) 00, 01 (start ~ stop) 17,28 (index) 00, 01 (start ~ stop) 06 (no range, or all) 00, 01 (start ~ stop) 06 (no range, or all) 00, 01 (start ~ stop) 06 (no range, or all) 00, 01 (start ~ stop) 06 (no range, or all) PCS-902 Line Distance Relay Date: 2015-05-19 10 Communication OBJECT GROUP & VARIATION Group/Variation REQUEST Description No. Function code Qualifier code 3 (select) 41 1 4 (operate) Analog Output: 32 ~ bit 17,28 (index) 5 (direct op) 6 (dir. Op, no ack) 17,28 (index) 3 (select) 41 2 4 (operate) Analog Output: 16 ~ bit 17,28 (index) 5 (direct op) 6 (dir. Op, no ack) 17,28 (index) 3 (select) 41 3 50 1 50 3 51 1 51 2 60 1 Analog Output: Single ~ prec ft ~ pt Time and Data: Absolute time Time and Data: Absolute time at last recorded time 4 (operate) 5 (direct op) 6 (dir. Op, no ack) 17,28 (index) 1 (read) 07 (limited qty = 1) 2 (write) 07 (limited qty = 1) 2 (write) 07 (limited qty = 1) Time and Data CTO: Absolute time, synchronized Time and Data CTO: Absolute time, unsynchronized 1 (read) Class Objects: Class 0 data 22 (assign class) 1 (read) 60 2 17,28 (index) Class Objects: Class 1 data 06 (no range, or all) 06 (no range, or all) 07,08 (limited qty) 20 (enable unsol.) 21 (disable unsol.) 06 (no range, or all) 22 (assign class) 1 (read) 60 3 Class Objects: Class 2 data 06 (no range, or all) 07,08 (limited qty) 20 (enable unsol.) 21 (disable unsol.) 06 (no range, or all) 22 (assign class) 1 (read) 60 4 Class Objects : Class 3 data 06 (no range, or all) 07,08 (limited qty) 20 (enable unsol.) 21 (disable unsol.) 06 (no range, or all) 22 (assign class) Response: Master shall parse\Outstation may issue Function code: decimalism PCS-902 Line Distance Relay 10-25 Date: 2015-05-19 10 Communication Qualifier code: hexadecimal OBJECT GROUP & VARIATION Group/Variation RESPONSE Description No. Function code Qualifier code 1 0 Binary Input: Any Variation 1 1 Binary Input: Packed format 129 (response) 00, 01 (start ~ stop) 1 2 Binary Input: With flags 129 (response) 00, 01 (start ~ stop) 2 0 Binary Input Event: Any Variation 2 1 Binary Input Event: Without time 2 2 Binary Input Event: With absolute time 2 3 Binary Input Event: With relative time 10 0 Binary output: Any Variation 10 0 Binary output: Any Variation 10 1 Binary output: Packed format 12 1 30 0 Analog Input: Any Variation 30 1 30 129 (response) 130 (unsol. resp) 129 (response) 130 (unsol. resp) 129 (response) 130 (unsol. resp) 17, 28 (index) 17, 28 (index) 17, 28 (index) 129 (response) echo of request Analog Input: 32 ~ bit with flag 129 (response) 00, 01 (start ~ stop) 2 Analog Input: 16 ~ bit with flag 129 (response) 00, 01 (start ~ stop) 30 3 Analog Input: 32 ~ bit without flag 129 (response) 00, 01 (start ~ stop) 30 4 Analog Input: 16 ~ bit without flag 129 (response) 00, 01 (start ~ stop) 30 5 Analog Input: Single ~ prec flt ~ pt with flag 129 (response) 00, 01 (start ~ stop) 32 0 Analog Input Event: Any Variation 32 1 Analog Input Event: 32 ~ bit without time 32 2 Analog Input Event: 16 ~ bit without time 32 5 34 0 Analog Input Deadband: Any Variation 34 1 Analog Input Deadband: 16 ~ bit 34 2 Analog Input Deadband: 32 ~ bit 34 3 Analog Input Deadband: Single ~ prec flt ~ pt 40 0 Analog Output Status: Any Variation 40 1 40 2 Binary Command: Control relay output block (CROB) 129 (response) 130 (unsol. resp) 129 (response) 130 (unsol. resp) Analog Input Event: Single ~ prec flt ~ pt without 129 (response) time 130 (unsol. resp) 17,28 (index) 17,28 (index) 17,28 (index) 129 (response) 00, 01 (start ~ stop) 129 (response) 00, 01 (start ~ stop) 129 (response) 00, 01 (start ~ stop) Analog Output Status: 32 ~ bit with flag 129 (response) 00, 01 (start ~ stop) Analog Output Status: 16 ~ bit with flag 129 (response) 00, 01 (start ~ stop) 10-26 PCS-902 Line Distance Relay Date: 2015-05-19 10 Communication OBJECT GROUP & VARIATION Group/Variation Description No. Function code Analog Output Status: single ~ prec flt ~ pt with 40 3 41 1 41 2 41 3 50 1 50 3 51 1 51 2 60 1 Class Objects: Class 0 data 60 2 Class Objects: Class 1 data 60 3 Class Objects: Class 2 data 60 4 Class Objects : Class 3 data RESPONSE flag Analog Output: Qualifier code 129 (response) 00, 01 (start ~ stop) 129 (response) echo of request 129 (response) echo of request 129 (response) echo of request 129 (response) 07 (limited qty = 1) 32 ~ bit Analog Output: 16 ~ bit Analog Output: Single ~ prec ft ~ pt Time and Data: Absolute time Time and Data: Absolute time at last recorded time Time and Data CTO: Absolute time, 129 (response) synchronized 130 (unsol. resp) Time and Data CTO: Absolute time, 129 (response) unsynchronized 130 (unsol. resp) 07 (limited qty = 1) 07 (limited qty = 1) 10.5.4.3 Communication Table Configuration This relay now supports 4 Ethernet clients and 2 serial port clients. Each client can be set the DNP related communication parameters respectively and be selected the user-defined communication table. This relay supports a default communication table and 4 user-defined communication tables, and the default communication table is fixed by the manufacturer and not permitted to configure by the user. The user can configure the user-defined communication table through the PCS-Explorer configuration tool auxiliary software. The object groups “Binary Input”, “Binary Output”, “Analog Input” and “Analog Output” can be configured according to the practical engineering demand. 10.5.4.4 Analog Input and Output Configuration To the analog inputs, the attributes “deadband” and “factor” of each analog input can be configured independently. To the analog outputs, only the attribute “factor” of each analog output needs to be configured. If the integer mode is adopted for the data formats of analog values (to “Analog Input”, “Object Variation” is 1, 2 and 3; to “Analog Output”, “Object Variation” is 1 and 2.), the analog values will be multiplied by the “factor” respectively to ensure their accuracy. And if the float mode PCS-902 Line Distance Relay 10-27 Date: 2015-05-19 10 Communication is adopted for the data formats of analog values, the actual float analog values will be sent directly. The judgment method of the analog input change is as below: Calculate the difference between the current new value and the stored history value and make the difference value multiply by the “factor”, then compare the result with the “deadband” value. If the result is greater than the “deadband” value, then an event message of corresponding analog input change will be created. In normal communication process, the master can online read or modify a “deadband” value by reading or modifying the variation in “Group34”. 10.5.4.5 Binary Output Configuration The remote control signals, logic links and external extended output commands can be configured into the “Binary Output” group. The supported control functions are listed as below. Information Point Pulse On/Null Pulse On/Close Pulse On/Trip Latch On/Null Latch Off/Null Remote Control Not supported Close Trip Close Trip Logic Link Not supported Set Clear Set Clear Extended Output See following description To an extended output command, if a selected command is controlled remotely, this command point will output a high ~ level pulse. The pulse width can be decided by the “On ~ time” in the related “Binary Command” which is from the DNP3.0 master. If the “On ~ time” is set as “0”, the default pulse width is 500ms. 10.5.4.6 Unsolicited Messages This relay does not transmit the unsolicited messages if the related logic setting is set as “0”. If the unsolicited messages want to be transmitted, the related logic setting should be set as “1” or the DNP3.0 master will transmit “Enable Unsolicited” command to this relay through “Function Code 20” (Enable Unsolicited Messages). If the “Binary Input” state changes or the difference value of the “Analog Input” is greater than the “deadband” value, this device will transmit unsolicited messages. If the DNP3.0 master needs not to receive the unsolicited messages, it should forbid this relay to transmit the unsolicited messages by setting the related logic setting as “0” or through the “Function Code 21” (Disable Unsolicited Messages). 10.5.4.7 Class Configuration If the DNP3.0 master calls the Class0 data, this relay will transmit all actual values of the “Analog Input”, “Binary Input” and “Analog Output”. The classes of the “Analog Input” and “Binary Input” can be defined by modifying relevant settings. In communication process, the DNP3.0 master can online modify the class of an “Analog Input” or a “Binary Input” through “Function Code 22” (Assign Class). 10-28 PCS-902 Line Distance Relay Date: 2015-05-19 11 Installation 11 Installation Table of Contents 11 Installation ...................................................................................... 11-a 11.1 Overview ....................................................................................................... 11-1 11.2 Safety Information ........................................................................................ 11-1 11.3 Checking Shipment ...................................................................................... 11-2 11.4 Material and Tools Required ........................................................................ 11-2 11.5 Device Location and Ambient Conditions .................................................. 11-2 11.6 Mechanical Installation ................................................................................ 11-3 11.7 Electrical Installation and Wiring ................................................................ 11-4 11.7.1 Grounding Guidelines .......................................................................................................11-4 11.7.2 Cubicle Grounding ............................................................................................................11-4 11.7.3 Ground Connection on the Device ...................................................................................11-5 11.7.4 Grounding Strips and their Installation ..............................................................................11-5 11.7.5 Guidelines for Wiring.........................................................................................................11-6 11.7.6 Wiring for Electrical Cables ...............................................................................................11-6 List of Figures Figure 11.6-1 Dimensions and panel cut-out of PCS-902 ..................................................... 11-3 Figure 11.6-2 Demonstration of plugging a board into its corresponding slot .................. 11-3 Figure 11.7-1 Cubicle grounding system ................................................................................ 11-5 Figure 11.7-2 Ground terminal of this relay ............................................................................ 11-5 Figure 11.7-3 Ground strip and termination ........................................................................... 11-6 Figure 11.7-4 Glancing demo about the wiring for electrical cables ................................... 11-7 PCS-902 Line Distance Relay 11-a Date: 2015-05-19 11 Installation 11-b PCS-902 Line Distance Relay Date: 2015-05-19 11 Installation 11.1 Overview The device must be shipped, stored and installed with the greatest care. Choose the place of installation such that the communication interface and the controls on the front of the device are easily accessible. Air must circulate freely around the equipment. Observe all the requirements regarding place of installation and ambient conditions given in this instruction manual. Take care that the external wiring is properly brought into the equipment and terminated correctly and pay special attention to grounding. Strictly observe the corresponding guidelines contained in this section. 11.2 Safety Information Modules and units may only be replaced by correspondingly trained personnel. Always observe the basic precautions to avoid damage due to electrostatic discharge when handling the equipment. In certain cases, the settings have to be configured according to the demands of the engineering configuration after replacement. It is therefore assumed that the personnel who replace modules and units are familiar with the use of the operator program on the service PC. WARNING! ONLY insert or withdraw a module while the device power supply is switched off. To this end, disconnect the power supply cable that connects with the PWR module. NOTICE! Industry packs and ribbon cables may ONLY be replaced on a workbench for electronic equipment. Electronic components are sensitive to electrostatic discharge when not in the unit's housing. Jumper links may ONLY be changed on a workbench for electronic equipment. Electronic components are sensitive to electrostatic discharge when not in the unit's housing. A module can ONLY be inserted in the slot designated in the chapter 6. Components can be damaged or destroyed by inserting module in a wrong slot. The basic precautions to guard against electrostatic discharge are as follows: 1. Should boards have to be removed from this relay installed in a grounded cubicle in an HV switchgear installation, please discharge yourself by touching station ground (the cubicle) beforehand. 2. Only hold electronic boards at the edges, taking care not to touch the components. 3. Only works on boards that have been removed from the cubicle on a workbench designed for PCS-902 Line Distance Relay 11-1 Date: 2015-05-19 11 Installation electronic equipment and wear a grounded wristband. Do not wear a grounded wristband, however, while inserting or withdrawing units. 4. Always store and ship the electronic boards in their original packing. Place electronic parts in electrostatic screened packing materials. 11.3 Checking Shipment Check that the consignment is complete immediately upon receipt. Notify the nearest NR Company or agent, should departures from the delivery note, the shipping papers or the order be found. Visually inspect all the material when unpacking it. When there is evidence of transport damage, lodge a claim immediately in writing with the last carrier and notify the nearest NR Company or agent. If the equipment is not going to be installed immediately, store all the parts in their original packing in a clean dry place at a moderate temperature. The humidity at a maximum temperature and the permissible storage temperature range in dry air are listed in Chapter “Technical Data”. 11.4 Material and Tools Required The necessary mounting kits will be provided, including screws, pincers and assembly instructions. A suitable drill and spanners are required to secure the cubicles to the floor using the plugs provided (if this relay is mounted in cubicles). 11.5 Device Location and Ambient Conditions NOTICE! Excessively high temperature can appreciably reduce the operating life of this device. The place of installation should permit easy access especially to front of the device, i.e. to the human machine interface of the equipment. There should also be free access at the rear of the equipment for additions and replacement of electronic boards. Since every piece of technical equipment can be damaged or destroyed by inadmissible ambient conditions, such as: 1. The location should not be exposed to excessive air pollution (dust, aggressive substances). 2. Severe vibration, extreme changes of temperature, high levels of humidity, surge voltages of high amplitude and short rise time and strong induced magnetic fields should be avoided as far as possible. 3. Air must not be allowed to circulate freely around the equipment. The equipment can in principle be mounted in any attitude, but it is normally mounted vertically 11-2 PCS-902 Line Distance Relay Date: 2015-05-19 11 Installation (visibility of markings). 11.6 Mechanical Installation NOTICE! It is necessary to leave enough space top and bottom of the cut-out in the cubicle for heat emission of this device. The device adopts IEC standard chassis and is rack with modular structure. It uses an integral faceplate and plug terminal block on backboard for external connections. PCS-902 series is IEC 4U high, and Figure 11.6-1 shows its dimensions and panel cut-out. Front Side Cut-Out Figure 11.6-1 Dimensions and panel cut-out of PCS-902 The safety instructions must be abided by when installing the boards, please see Section 11.2 for the details. Following figure shows the installation way of a module being plugged into a corresponding slot. Figure 11.6-2 Demonstration of plugging a board into its corresponding slot PCS-902 Line Distance Relay 11-3 Date: 2015-05-19 11 Installation In the case of equipment supplied in cubicles, place the cubicles on the foundations that have been prepared. Take care while doing so not to jam or otherwise damage any of the cables that have already been installed. Secure the cubicles to the foundations. 11.7 Electrical Installation and Wiring 11.7.1 Grounding Guidelines NOTICE! All these precautions can only be effective if the station ground is of good quality. Switching operations in HV installations generate transient over voltages on control signal cables. There is also a background of electromagnetic RF fields in electrical installations that can induce spurious currents in the devices themselves or the leads connected to them. All these influences can influence the operation of electronic apparatus. On the other hand, electronic apparatus can transmit interference that can disrupt the operation of other apparatus. In order to minimize these influences as far as possible, certain standards have to be observed with respect to grounding, wiring and screening. 11.7.2 Cubicle Grounding The cubicle must be designed and fitted out such that the impedance for RF interference of the ground path from the electronic device to the cubicle ground terminal is as low as possible. Metal accessories such as side plates, blanking plates etc., must be effectively connected surface-to-surface to the grounded frame to ensure a low-impedance path to ground for RF interference. The contact surfaces must not only conduct well, they must also be non-corroding. NOTICE! If the above conditions are not fulfilled, there is a possibility of the cubicle or parts of it forming a resonant circuit at certain frequencies that would amplify the transmission of interference by the devices installed and also reduce their immunity to induced interference. Movable parts of the cubicle such as doors (front and back) or hinged equipment frames must be effectively grounded to the frame by three braided copper strips (see Figure 11.7-1). The metal parts of the cubicle housing and the ground rail are interconnected electrically conducting and corrosion proof. The contact surfaces shall be as large as possible. NOTICE! For metallic connections please observe the voltage difference of both materials according to the electrochemical code. The cubicle ground rail must be effectively connected to the station ground rail by a grounding strip (braided copper). 11-4 PCS-902 Line Distance Relay Date: 2015-05-19 11 Installation Door or hinged equipment frame Cubicle ground rail close to floor Braided copper strip Station ground Conducting connection Figure 11.7-1 Cubicle grounding system 11.7.3 Ground Connection on the Device There is a ground terminal on the rear panel, and the ground braided copper strip can be connected with it. Take care that the grounding strip is always as short as possible. The main thing is that the device is only grounded at one point. Grounding loops from unit to unit are not allowed. There are some ground terminals on some connectors of this relay, and the sign is “GND”. All the ground terminals are connected in the cabinet of this relay. So, the ground terminal on the rear panel (see Figure 11.7-2) is the only ground terminal of this device. Figure 11.7-2 Ground terminal of this relay 11.7.4 Grounding Strips and their Installation High frequency currents are produced by interference in the ground connections and because of skin effect at these frequencies, only the surface region of the grounding strips is of consequence. The grounding strips must therefore be of (preferably tinned) braided copper and not round copper conductors, as the cross-section of round copper would have to be too large. Proper terminations must be fitted to both ends (press/pinch fit and tinned) with a hole for bolting them firmly to the items to be connected. The surfaces to which the grounding strips are bolted must be electrically conducting and non-corroding. PCS-902 Line Distance Relay 11-5 Date: 2015-05-19 11 Installation The following figure shows the ground strip and termination. Press/pinch fit cable terminal Braided copper strip Terminal bolt Contact surface Figure 11.7-3 Ground strip and termination 11.7.5 Guidelines for Wiring There are several types of cables that are used in the connection of this relay: braided copper cable, serial communication cable etc. Recommendation of each cable: Grounding: braided copper cable, 2.5mm2 ~ 6.0mm 2 Power supply, binary inputs & outputs: stranded conductor, 1.0mm 2 ~ 2.5mm 2 AC voltage inputs: stranded conductor, 1.5mm 2 AC current inputs: stranded conductor, 2.5mm 2 Serial communication: 4-core shielded cable Ethernet communication: 4-pair twisted shielded cable (category 5E) 11.7.6 Wiring for Electrical Cables DANGER! NEVER allow a open current transformer (CT) secondary circuit connected to this device while the primary system is live. Open CT circuit will produce a dangerously high voltage that cause death. A female connector is used for connecting the wires with it, and then a female connector plugs into a corresponding male connector that is in the front of one board. See Chapter “Hardware” for further details about the pin defines of these connectors. The following figure shows the glancing demo about the wiring for the electrical cables. 11-6 PCS-902 Line Distance Relay Date: 2015-05-19 11 Installation Tighten 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 01 Figure 11.7-4 Glancing demo about the wiring for electrical cables PCS-902 Line Distance Relay 11-7 Date: 2015-05-19 11 Installation 11-8 PCS-902 Line Distance Relay Date: 2015-05-19 12 Commissioning 12 Commissioning Table of Contents 12 Commissioning ............................................................................. 12-a 12.1 Overview ...................................................................................................... 12-1 12.2 Safety Instructions ...................................................................................... 12-1 12.3 Commission Tools ...................................................................................... 12-2 12.3.1 Minimum Equipment Required ........................................................................................ 12-2 12.3.2 Optional Equipment ......................................................................................................... 12-2 12.4 Setting Familiarization ................................................................................ 12-2 12.5 Product Checks ........................................................................................... 12-3 12.5.1 With the Relay De-energized........................................................................................... 12-3 12.5.2 With the Relay Energized ................................................................................................ 12-5 12.5.3 Print Fault Report............................................................................................................. 12-8 12.5.4 On-load Checks ............................................................................................................... 12-8 12.6 Final Checks ................................................................................................ 12-9 PCS-902 Line Distance Relay 12-a Date: 2015-05-19 12 Commissioning 12-b PCS-902 Line Distance Relay Date: 2015-05-19 12 Commissioning 12.1 Overview This device is fully numerical in their design, implementing all protection and non-protection functions in software. The relay employs a high degree of self-checking and in the unlikely event of a failure, will give an alarm. As a result of this, the commissioning test does not need to be as extensive as with non-numeric electronic or electro-mechanical relays. To commission numerical relays, it is only necessary to verify that the hardware is functioning correctly and the application-specific software settings have been applied to the relay. Blank commissioning test and setting records are provided at the end of this manual for completion as required. Before carrying out any work on the equipment, the user should be familiar with the contents of the safety and technical data sections and the ratings on the equipment’s rating label. 12.2 Safety Instructions DANGER! Current transformer secondary circuits MUST be short-circuited BEFORE the current leads to the device are disconnected. WARNING! ONLY qualified personnel should work on or in the vicinity of this device. This personnel MUST be familiar with all safety regulations and service procedures described in this manual. During operating of electrical device, certain part of the device is under high voltage. Severe personal injury and significant device damage could result from improper behavior. Particular attention must be drawn to the following: 1. The earthing screw of the device must be connected solidly to the protective earth conductor before any other electrical connection is made. 2. Hazardous voltages can be present on all circuits and components connected to the supply voltage or to the measuring and test quantities. 3. Hazardous voltages can be present in the device even after disconnection of the supply voltage (storage capacitors!) 4. The limit values stated in the Chapter “Technical Data” must not be exceeded at all, not even during testing and commissioning. 5. When testing the device with secondary test equipment, make sure that no other measurement quantities are connected. Take also into consideration that the trip circuits and maybe also close commands to the circuit breakers and other primary switches are disconnected from the device unless expressly stated. PCS-902 Line Distance Relay 12-1 Date: 2015-05-19 12 Commissioning 12.3 Commission Tools NOTICE! Modern test set may contain many of the above features in one unit. 12.3.1 Minimum Equipment Required 1. Multifunctional dynamic current and voltage injection test set with interval timer. 2. Multimeter with suitable AC current range and AC/DC voltage ranges of 0~440Vac and 0~250Vdc respectively. 3. Continuity tester (if not included in the multimeter). 4. Phase angle meter. 5. Phase rotation meter. 12.3.2 Optional Equipment 1. An electronic or brushless insulation tester with a DC output not exceeding 500V (for insulation resistance test when required). 2. A portable PC, with appropriate software (this enables the rear communications port to be tested, if this is to be used, and will also save considerable time during commissioning). 3. EIA RS-485 to EIA RS-232 converter (if EIA RS-485 IEC60870-5-103 port is being tested). 4. PCS-900 serials dedicated protection tester HELP-9000. 12.4 Setting Familiarization When commissioning this device for the first time, sufficient time should be allowed to become familiar with the method by which the settings are applied. A detailed description of the menu structure of this relay is contained in Chapter “Operation Theory” and Chapter “Settings”. With the front cover in place all keys are accessible. All menu cells can be read. The LED indicators and alarms can be reset. Protection or configuration settings can be changed, or fault and event records cleared. However, menu cells will require the appropriate password to be entered before changes can be made. Alternatively, if a portable PC is available together with suitable setting software (such as PCS-9700 HMI software), the menu can be viewed one page at a time to display a full column of data and text. This PC software also allows settings to be entered more easily, saved to a file on disk for future reference or printed to produce a setting record. Refer to the PC software user manual for details. If the software is being used for the first time, allow sufficient time to become familiar with its operation. 12-2 PCS-902 Line Distance Relay Date: 2015-05-19 12 Commissioning 12.5 Product Checks These product checks cover all aspects of the relay which should be checked to ensure that it has not been physically damaged prior to commissioning, is functioning correctly and all input quantity measurements are within the stated tolerances. If the application-specific settings have been applied to the relay prior to commissioning, it is advisable to make a copy of the settings so as to allow them restoration later. This could be done by extracting the settings from the relay itself via printer or manually creating a setting record. 12.5.1 With the Relay De-energized This relay is fully numerical and the hardware is continuously monitored. Commissioning tests can be kept to a minimum and need only include hardware tests and conjunctive tests. The function tests are carried out according to user’s correlative regulations. The following tests are necessary to ensure the normal operation of the equipment before it is first put into service. 1. Hardware tests These tests are performed for the following hardware to ensure that there is no hardware defect. Defects of hardware circuits other than the following can be detected by self-monitoring when the DC power is supplied. 2. User interfaces test 3. Binary input circuits and output circuits test 4. AC input circuits test 5. Function tests These tests are performed for the following functions that are fully software-based. Tests of the protection schemes and fault locator require a dynamic test set. 6. Measuring elements test 7. Timers test 8. Measurement and recording test 9. Conjunctive tests The tests are performed after the relay is connected with the primary equipment and other external equipment. 10. On load test 11. Phase sequence check and polarity check PCS-902 Line Distance Relay 12-3 Date: 2015-05-19 12 Commissioning 12.5.1.1 Visual Inspection After unpacking the product, check for any damage to the relay case. If there is any damage, the internal module might also have been affected, contact the vendor. The following items listed is necessary. 1. Protection panel Carefully examine the protection panel, protection equipment inside and other parts inside to see that no physical damage has occurred since installation. The rated information of other auxiliary protections should be checked to ensure it is correct for the particular installation. 2. Panel wiring Check the conducting wire which is used in the panel to assure that their cross section meeting the requirement. Carefully examine the wiring to see that they are no connection failure exists. 3. Label Check all the isolator binary inputs, terminal blocks, indicators, switches and push buttons to make sure that their labels meet the requirements of this project. 4. Device plug-in modules Check each plug-in module of the device on the panel to make sure that they are well installed into the equipment without any screw loosened. 5. Earthing cable Check whether the earthing cable from the panel terminal block is safely screwed to the panel steel sheet. 6. Switch, keypad, isolator binary inputs and push button Check whether all the switches, equipment keypad, isolator binary inputs and push buttons work normally and smoothly. 12.5.1.2 Insulation Test Insulation resistance tests are only necessary during commissioning if it is required for them to be done and they have not been performed during installation. Isolate all wiring from the earth and test the isolation with an electronic or brushless insulation tester at a DC voltage not exceeding 500V, The circuits need to be tested should include: 1. Voltage transformer circuits 2. Current transformer circuits 3. DC power supply 12-4 PCS-902 Line Distance Relay Date: 2015-05-19 12 Commissioning 4. Optic-isolated control inputs 5. Output contacts 6. Communication ports The insulation resistance should be greater than 100MΩ at 500V. Test method: To unplug all the terminals sockets of this relay, and do the Insulation resistance test for each circuit above with an electronic or brushless insulation tester. On completion of the insulation resistance tests, ensure all external wiring is correctly reconnected to the protection. 12.5.1.3 External Wiring Check that the external wiring is correct to the relevant relay diagram and scheme diagram. Ensure as far as practical that phasing/phase rotation appears to be as expected. Check the wiring against the schematic diagram for the installation to ensure compliance with the customer’s normal practice. 12.5.1.4 Auxiliary Power Supply WARNING! Energize this device ONLY if the power supply is within the specified operating range in Chapter “Technical Data”. The relay only can be operated under the auxiliary power supply depending on the relay’s nominal power supply rating. The incoming voltage must be within the operating range specified in Chapter “Technical Data”, before energizing the relay, measure the auxiliary supply to ensure it within the operating range. Other requirements to the auxiliary power supply are specified in Chapter “Technical Data”. See this section for further details about the parameters of the power supply. 12.5.2 With the Relay Energized The following groups of checks verify that the relay hardware and software is functioning correctly and should be carried out with the auxiliary supply applied to the relay. The current and voltage transformer connections must remain isolated from the relay for these checks. The trip circuit should also remain isolated to prevent accidental operation of the associated circuit breaker. 12.5.2.1 Front Panel LCD Display Connect the relay to DC power supply correctly and turn the relay on. Check program version and forming time displayed in command menu to ensure that are corresponding to what ordered. PCS-902 Line Distance Relay 12-5 Date: 2015-05-19 12 Commissioning 12.5.2.2 Date and Time If the time and date is not being maintained by substation automation system, the date and time should be set manually. Set the date and time to the correct local time and date using menu item “Clock”. In the event of the auxiliary supply failing, with a super capacitor fitted on MON board, the time and date will be maintained. Therefore when the auxiliary supply is restored the time and date will be correct and not need to set again. To test this, remove the auxiliary supply from the relay for approximately 30s. After being re-energized, the time and date should be correct. 12.5.2.3 Light Emitting Diodes (LEDs) On power up, the green LED “HEALTHY” should have illuminated and stayed on indicating that the relay is healthy. The relay has latched signal relays which remember the state of the trip, auto-reclose when the relay was last energized from an auxiliary supply. Therefore these indicators may also illuminate when the auxiliary supply is applied. If any of these LEDs are on then they should be reset before proceeding with further testing. If the LED successfully reset, the LED goes out. There is no testing required for that that LED because it is known to be operational. It is likely that alarms related to voltage transformer supervision will not reset at this stage. 12.5.2.4 Testing HEALTHY and ALARM LEDs Apply the rated DC power supply and check that the “HEALTHY” LED is lighting in green. We need to emphasize that the “HEALTHY” LED is always lighting in operation course except that the equipment find serious errors in it. Produce one of the abnormal conditions listed in Chapter “Supervision”, the “ALARM” LED will light in yellow. When abnormal condition reset, the “ALARM” LED extinguishes. 12.5.2.5 Testing AC Current Inputs NOTICE! The closing circuit should remain isolated during these checks to prevent accidental operation of the associated circuit breaker. This test verified that the accuracy of current measurement is within the acceptable tolerances. Apply rated current to each current transformer input in turn; checking its magnitude using a multimeter/test set readout. The corresponding reading can then be checked in the relays menu. The verification of measurement accuracy shall be coincided with the required technical data. However, an additional allowance must be made for the accuracy of the test equipment being used. Group No. Item Input Value Input Angle 12-6 Display Value Display Angle PCS-902 Line Distance Relay Date: 2015-05-19 12 Commissioning Group No. Item Input Value Input Angle Display Value Display Angle Ia Three-phase current 1 Ib Ic Ia Three-phase current 2 Ib Ic Ia Three-phase current 3 Ib Ic Ia Three-phase current …… Ib Ic Residual current 1 3I0 Residual current 2 3I0 Residual current 3 3I0 Residual current …… 3I0 12.5.2.6 Testing AC Voltage Inputs NOTICE! The closing circuit should remain isolated during these checks to prevent accidental operation of the associated circuit breaker. This test verified that the accuracy of voltage measurement is within the acceptable tolerances. Apply rated voltage to each voltage transformer input in turn; checking its magnitude using a multimeter/test set readout. The corresponding reading can then be checked in the relays menu. The verification of measurement accuracy shall be coincided with the required technical data. However an additional allowance must be made for the accuracy of the test equipment being used. Group No. Item Input Value Input Angle Display Value Display Angle Ua Three-phase voltage 1 Ub Uc Ua Three-phase voltage 2 Ub Uc Ua Three-phase voltage 3 Ub Uc PCS-902 Line Distance Relay 12-7 Date: 2015-05-19 12 Commissioning Group No. Item Input Value Input Angle Display Value Display Angle Ua Three-phase voltage…… Ub Uc Residual voltage 1 3U0 Residual voltage 2 3U0 Residual voltage 3 3U0 Residual voltage …… 3U0 12.5.2.7 Testing Binary Inputs This test checks that all the binary inputs on the device are functioning correctly. The binary inputs should be energized one at a time, see external connection diagrams for terminal numbers. Ensure that the voltage applied on the binary input must be within the operating range. The status of each binary input can be viewed using relay menu. Sign “1” denotes an energized input and sign “0” denotes a de-energized input. Terminal No. Signal Name BI Status on LCD Correct? 12.5.3 Print Fault Report In order to acquire the details of protection operation, it is convenient to print the fault report of protection device. The printing work can be easily finished when operator presses the print button on panel of protection device to energize binary input [BI_Print] or operate control menu. What should be noticed is that only the latest fault report can be printed if operator presses the print button. A complete fault report includes the content shown as follows. 1. Trip event report 2. Binary input when protection devices start 3. Self-check and the transition of binary input in the process of devices start 4. Fault wave forms compatible with COMTRADE 5. The setting value when the protection device trips 12.5.4 On-load Checks The objectives of the on-load checks are: 1. Confirm the external wiring to the current and voltage inputs is correct. 2. Measure the magnitude of on-load current and voltage (if applicable). 3. Check the polarity of each current transformer. 12-8 PCS-902 Line Distance Relay Date: 2015-05-19 12 Commissioning However, these checks can only be carried out if there are no restrictions preventing the tenderization of the plant being protected. Remove all test leads, temporary shorting leads, etc. and replace any external wiring that has been removed to allow testing. If it has been necessary to disconnect any of the external wiring from the protection in order to perform any of the foregoing tests, it should be ensured that all connections are replaced in accordance with the relevant external connection or scheme diagram. Confirm current and voltage transformer wiring. 12.6 Final Checks After the above tests are completed, remove all test or temporary shorting leads, etc. If it has been necessary to disconnect any of the external wiring from the protection in order to perform the wiring verification tests, it should be ensured that all connections are replaced in accordance with the relevant external connection or scheme diagram. Ensure that the protection has been restored to service. If the protection is in a new installation or the circuit breaker has just been maintained, the circuit breaker maintenance and current counters should be zero. If a test block is installed, remove the test plug and replace the cover so that the protection is put into service. Ensure that all event records, fault records, disturbance records and alarms have been cleared and LED’s has been reset before leaving the protection. PCS-902 Line Distance Relay 12-9 Date: 2015-05-19 12 Commissioning 12-10 PCS-902 Line Distance Relay Date: 2015-05-19 13 Maintenance 13 Maintenance Table of Contents 13 Maintenance .................................................................................. 13-a 13.1 Overview ...................................................................................................... 13-1 13.2 Appearance Check ...................................................................................... 13-1 13.3 Failure Tracing and