Three-Phase AC Power Calculations & Power Factor Correction

advertisement
2/4/2016
ET 332a Ac Motors, Generators and Power
Systems
Lesson 5_et332b.pptx
1
After this presentation you will be able to:





Compute the active power absorbed by a threephase load.
Compute the reactive power absorbed by a threephase load.
Compute total three-phase apparent power.
Compute the total power several loads absorb.
Compute reactive power necessary to correct
power factor in a three-phase system.
Lesson 5_et332b.pptx
2
1
2/4/2016
Load can be either wye or delta
connected.
Assume wye connected load and
compute power on per phase basis
Phase Power
Total Three-phase Power
PT
3 Vp I p cos( )
ST
3 Vp I p
P
Vp I p cos( )
S
Vp I p
Using line quantities…for wye connected
loads
IL
Ip
VLL
3 Vp
Vp
VLL
3
Lesson 5_et332b.pptx
3
Total three-phase power using line quantities
Active Power PT
Where is the angle
between line voltage and
line current
3 VLL I L cos( )
Apparent Power ST
3 VLL I L
Three-phase reactive power formulas
Phase Reactive
Qp
Vp I p sin( p )
Total Reactive
QT
3 Vp I p sin( )
Also ST
PT
2
Where p is the angle between
phase voltage and phase
current
QT
2
and
Fp
Lesson 5_et332b.pptx
PT
ST
3 power
factor
4
2
2/4/2016
Example 5-1: A balanced delta connected three-phase
load draws 200 A per phase with a leading power factor
of 0.85 from a 12.47 kV line to line system. Determine
the following :
a) The line current magnitude of the load
b) the phase voltage magnitude of the load
c) the total apparent power of the load
d) the total real power drawn by the load
e) the total reactive power drawn by the load
f) the total complex power of the load
Lesson 5_et332b.pptx
5
a) Delta connected load so |VL|=|Vp| and |IL|= 3 |Ip|
Ans
b) Line voltage
Ans
c) Find the total apparent power, ST
Using line quantities
Using phase quantities
Ans
Ans
Lesson 5_et332b.pptx
6
3
2/4/2016
d) Active or real power
Ans
e) Reactive power
Find
Ans
Lesson 5_et332b.pptx
7
f) Complex power. Assume VL angle is zero degrees
Polar form
Rectangular form
P
Q
Lesson 5_et332b.pptx
8
4
2/4/2016
Example 5-2: For the system below find the ammeter reading, IA.
Eab = 460 0o V Ebc = 460 -120o V Eca = 460 120º V
Z1 = 10 30o
Z2 = 15 10o
Z3 = 20+j20
Ia2
Ia1
Ia3
Z3
Z1
Z2
Lesson 5_et332b.pptx
9
Lesson 5_et332b.pptx
10
Meter reading is
sum of load currents
Z1 is a balanced wye connected load
5
2/4/2016
Z2 balanced delta load. Find Ip then compute IL.
Eab=Vab
Lesson 5_et332b.pptx
11
Find the single phase current
Ia3
Eca
Lesson 5_et332b.pptx
12
6
2/4/2016
Sum currents to find meter reading
Ans
Lesson 5_et332b.pptx
13
Example 5-3: A 440 V 60 Hz 3-phase source supplies three loads:
1) Delta connected 3-phase 60 hp induction motor operating at 3/4
of rated output with an efficiency of 90% and a power factor of
94%
2) A wye connected 3-phase 75 hp induction motor operating at half
of its rated output with an efficiency of 88% and a power factor of
74%
3) A delta connect resistive heater drawing 20 kW.
Find:
a) total active, reactive, and apparent power supplied by the source
b) the power factor of the combined loads
c) the magnitude of the line current
d) the capacitance and voltage rating for a wye connected capacitor
bank that will correct the system power factor to 0.95 lagging
Lesson 5_et332b.pptx
14
7
2/4/2016
Find the total active and reactive power absorbed by each load,
using the power factor and the efficiency, then construct power
triangle for total load.
Use the following formulas
PT
LF
3 VLL I L cos( )
P0
100%
Prated
ST
PT
2
tan( )
QT
2
Fp
PT
ST
cos( )
P0
Pi
100%
QT
PT
Where: Po = machine mechanical shaft output (W)
Pi = machine electrical input (W)
Prated = machine rated shaft power (W)
PT = total 3-phase active power (W)
ST = total 3-phase apparent power (VA)
QT = total 3-phase reactive power (VARs)
= machine efficiency
LF = load factor
Lesson 5_et332b.pptx
15
a) Load 1: 60 Hp induction motor
Find power factor angle
Induction motor-Fp lagging QT
positive
Lesson 5_et332b.pptx
16
8
2/4/2016
Find QT1
Load 2: 75 hp induction motor
Lesson 5_et332b.pptx
17
Find the power factor angle then find QT2
Load 3; Resistance heater
Only absorbs watts
Sum the total active and reactive power of each load to find the total
system power absorbed.
Lesson 5_et332b.pptx
18
9
2/4/2016
Ans
Ans
Ans
Lesson 5_et332b.pptx
19
b) Find the power factor of the combined load
Ans
c) Find the load current magnitude
Ans
Lesson 5_et332b.pptx
20
10
2/4/2016
d) Find the capacitance and voltage rating of a capacitor that
corrects the system power factor to 0.95 lagging.
QT=42,434 VAR
Where
angle
is system power factor
PT=89,090 W
Construct new triangle
Lesson 5_et332b.pptx
21
This is the value of the total 3phase VARs required to correct
Fp to 0.95 lagging
The capacitor bank power, Qc,
is the difference between Qsys
and QTnew
Qc
QTnew
Qsys=42,434 VAR
Psys=89,090 W
Lesson 5_et332b.pptx
22
11
2/4/2016
Use the one-step formula to check result
Compares to previous
Lesson 5_et332b.pptx
23
Qc is the total bank power required, find the phase power
Bank is wye connected so capacitors see Vpn not VL
Ans
Find the capacitor value
Ans
Lesson 5_et332b.pptx
24
12
2/4/2016
ET 332a Ac Motors,
Generators and Power
Systems
Lesson 5_et332b.pptx
25
13