Designing connections u 630 A between a device and busbars System M Electrical characteristics Compact NS630 to NS1600 Fixed Compact circuit breakers Fixed NS630b to NS1600 DD383544 Characteristics 1 Connection. 2 Horizontal link. Using the data below, it is possible to determine the size of the copper bars and the maximum permissible currents when making the connections to busbars for a vertical, fixed Compact NS630b / NS1600, taking into account the ambient temperature around the switchboard and the IP value. Connection Flat bars, 5 mm thick Device NS630b NS800 NS1000 NS1250 NS1600(1) Permissible current (A) Size per phase I (A) Size per phase I (A) Size per phase I (A) Size per phase I (A) Size per phase I (A) Average ambient temperature around the switchboard 25 °C 30 °C 35 °C IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 1b 50 x 5 1b 50 x 5 1b 50 x 5 1b 50 x 5 1b 50 x 5 1b 50 x 5 630 630 630 630 630 630 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 800 800 800 800 800 800 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 1000 1000 1000 1000 1000 1000 3b 50 x 5 3b 50 x 5 3b 50 x 5 3b 50 x 5 3b 50 x 5 3b 50 x 5 1250 1250 1250 1250 1250 1250 4b 50 x 5 4b 50 x 5 4b 50 x 5 4b 50 x 5 4b 50 x 5 4b 50 x 5 1600 1550 1600 1500 1550 1450 40 °C IP y 31 1b 50 x 5 630 2b 50 x 5 800 2b 50 x 5 1000 3b 50 x 5 1250 4b 50 x 5 1500 IP > 31 1b 50 x 5 630 2b 50 x 5 800 2b 50 x 5 1000 3b 50 x 5 1200 4b 50 x 5 1400 45 °C IP y 31 1b 50 x 5 630 2b 50 x 5 800 2b 50 x 5 1000 3b 50 x 5 1250 4b 50 x 5 1450 IP > 31 1b 50 x 5 630 2b 50 x 5 800 2b 50 x 5 970 3b 50 x 5 1150 4b 50 x 5 1350 50 °C IP y 31 1b 50 x 5 630 2b 50 x 5 800 2b 50 x 5 1000 3b 50 x 5 1200 4b 50 x 5 1400 IP > 31 1b 50 x 10 630 1b 50 x 10 800 1b 50 x 10 970 1b 50 x 10 1130 2b 50 x 10 1350 50 °C IP y 31 1b 50 x 10 630 1b 50 x 10 800 1b 50 x 10 1000 1b 50 x 10 1180 2b 50 x 10 1400 IP > 31 bb b b b b b connection not possible. (1) Make the neutral connection with two bars, 50 x 5 mm. Flat bars, 10 mm thick Device NS630b NS800 NS1000 NS1250 NS1600 (1) Permissible current (A) Size per phase I (A) Size per phase I (A) Size per phase I (A) Size per phase I (A) Size per phase I (A) Average ambient temperature around the switchboard 25 °C 30 °C 35 °C IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 630 630 630 630 630 630 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 800 800 800 800 800 800 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1000 1000 1000 1000 1000 1000 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1250 1250 1250 1250 1250 1250 2b 50 x 10 2b 50 x 10 2b 50 x 10 2b 50 x 10 2b 50 x 10 2b 50 x 10 1600 1550 1600 1500 1550 1450 40 °C IP y 31 1b 50 x 10 630 1b 50 x 10 800 1b 50 x 10 1000 1b 50 x 10 1250 2b 50 x 10 1500 IP > 31 1b 50 x 10 630 1b 50 x 10 800 1b 50 x 10 1000 1b 50 x 10 1180 2b 50 x 10 1400 45 °C IP y 31 1b 50 x 10 630 1b 50 x 10 800 1b 50 x 10 1000 1b 50 x 10 1230 2b 50 x 10 1450 b connection not possible. (1) Make the neutral connection with 2 bars, 50 x 10 mm. Note: The values indicated above have been validated for Prisma iPM switchboards. E-18 IP > 31 bb bb bb bb bb