Pipe Flow Problems-III Example 1 A centrifugal pump has a 100 mm diameter suction pipe and a 75 mm diameter delivery pipe. When discharging 15 l/s of water, the inlet water mercury manometer with one limb exposed to the atmosphere recorded a vacuum deflection of 198 mm; the mercury level on the suction side was 100 mm below the pipe centerline. The delivery pressure gauge, 200 mm above the pump inlet, recorded a pressure of 0.95 bar. The measured in put power was 3.2 kW. Calculate the pump efficiency. (See fig.1) Solution; Manometric head = rise in total head p1 V12 p2 V22 1bar 10.198m of water Hm z g 2 g g 2 g p2 0.95 *10.198 9.65m of water g V2 3.39m / s; V22 0.588m 2g V12 0.186m 2g Then Hm 9.69 0.588 0.2 - (-2.793 0.186) 13.09m V1 1.91m / s; output power gQHm ( watts) input power 3200( watts) 3.2 0.015 13.09 0.602 (60.2 percent ) 3 .2 Efficiency ( ) Fig 1. Example 2 (Pipeline selection in pumping system design) As existing pump, having the tabulated characteristics is to be used to pump raw sewage to a treatment plant through a static lift of 20 m. An uPVC pipeline 10 km long is to be used. Allowing for minor losses totaling 10 V2/2g and taking an effective roughness of 0.15 mm because of sliming, select a suitable commercially available pipe size to achieve a discharge of 60 l/s. Calculate this power consumption. Discharge (l/s) Total head (m) Overall efficiency (per cent) 0 45 10 44.7 20 43.7 30 42.5 40 40.6 50 38 60 35 70 31 35 50 57 60 60 53 40 Solution; At 60 l/s, total head = 35.0 m, therefore the sum of the static lift and pipeline losses must not exceed 35.0 m. Try 300 mm diameter: A=0.0707 m2 Re = 2.25*100000 ; k/D = 0.0005 V=0.85 m/s =0.019= f 2 Friction head loss 0.019 10000 0.85 23 .32 m 0.3 19 .62 Hs + hf = 43.32 (> 35) pipe diameter too small Try 300 mm diameter: A=0.0962 m2 Re = 1.93*100000 ; k/D = 0.00043 Hf=10.48m; hm V=0.624 m/s; =0.0185 10 0.624 2 0.2m 19 .612 Hs + hf + hm =30.68 (< 35 m) O.K The pump would deliver approximately 70 l/s through the 350 mm pipe and to regulate the flow to 60 l/s an additional head loss of 4.32 m by valve closure would be required. Power consumption P 1000 9.81 0.06 35 38.85kW 0.55 1000 Example 3 (Pumps in parallel and series) Two identical pumps having the tabulated characteristics are to be installed in a pumping station to deliver sewage to a settling tank through a 200 mm uPVC pipeline 2.5 km long. The static lift is 15 m. Allowing for minor head losses of 10.0V2/2g and assuming an effective roughness of 0.15 mm calculate the discharge and power consumption if the pumps were to be connected: (a) in parallel, and (b) in series. Pump Characteristics discharge (l/s) Total head (m) Overall efficiency (per cent) 0 30 10 27.5 44 20 23.5 58 30 17 50 40 7.5 18 Solution; The ‘system curve’ is computed as in the previous examples; this is, of course , independent of the pump characteristics. Calculated system heads (H) are tabulated below for discrete discharges (Q) H HsT h f hm Q (l/s) H (m) 10 16.53 20 20.8 30 27.37 40 36.48 (a) Parallel operation The predicted head v. discharge curve for dual pump operation in parallel mode is obtained as described,.i.e. by doubling she discharge over the range of heads (since the pumps are identical in this case). The system and efficiency curves are added as shown in fig. 2. From the intersection of the characteristic and system curves the following results are obtained: Fig. 2 Parallel operation Single pimp operation; Q = 22.5 l/S; Hm = 24 m ; = 0.58 Power consumption = 9.13 kW Parallel operation, Q = 28.5 l/S; Hm = 26 m ; = 0.51 (Corresponding with 14.25 l/s per pump) Power input = 14.11 kW (b) Series operation Using the method described in section 6.3 (b) and plotting the dual-pump characteristic curve, intersection with the system curve yields (see Fig 3) Fig 3. Series operation Q=32.5 l/S; Hm = 28 m ; = 0.41 Power input = 21.77kW Note that for this particular pipe system, comparing the relative power consumptions the parallel operation is more efficient in producing an increase in discharge than the series operation. Example 4 A laboratory test on a pump revealed that the onset of cavitations occurred at a discharge of 35 l/s, when the total head at inlet was reduced to 2.5m and the total head across the pump was 32 m. Barometric pressure was 760 mm Hg and the vapor pressure 17 mm Hg. Calculate the Thoma cavitation number. The pump is to be installed in a situation where the atmospheric pressure is 650 mm Hg and water temperature 10C (Vapor Pressure 9.22 mmHg) to give the same total head and discharge. The losses and velocity head in the suction pipe are estimated to be 0.55 m of water. What is the maximum height of the suction lift? Solution; H suc 2.5m H suc pv 2.5 0.23 2.27 2.27 0.071 32 p5 V52 p1 V12 z 5 hL z1 2g 2g p5 pv p1 V52 z 5 z1 hL NPSH 2g pv 0.55 z 5 z1 p1 pv 0.55 NPSH 8.84 0.1254 0.55 2.27 5.89m Example 4 The pump of Fig 4a.is placed in a 10-in- diameter pipe (f=0.020), 1300 ft long, which is used to lift water from one reservoir to another. The difference in water surface elevations between the reservoirs fluctuates from 20ft to 100ft. Plot a curve showing delivery rate versus water surface elevation difference. Plot also the corresponding efficiencies. The pump is operated at a constant speed of 1450 rpm. Neglect minor losses. Solution; Plot the pump characteristic curve and pipe system curves for a variety of z’s. z,ft 20 40 60 80 100 110 See plotted curves in fig 4b Q, gpm 2500 2320 2100 1860 1350 940 efficiency, % 68 76 81 84 77 66 Example 5 Suppose a pump is to pump water at a head of 130ft, the water temperature being 100F and the barometric pressure being 14.3 psia. At intake the pressures is a vacuum of 17 in Hg and the velocity is 12 fps. What are the values of NPSH and ? Solution; NPSH p s abs / Vs2 / 2 g p v / p s abs p0 / p s / 14.3144 / 62.0 17 / 12847.3 / 62.0 13.85 ft Vs2 / 2 g 12 2 / 2 * 32.2 2.24 ft p v / 135 / 62 2.18 ft NPSH 13.85 2.24 2.18 13.91 ft 13.91 / 130 0.107 Example 6 A pump is delivering 7500 gpm of water at 140 F at a head of 240 ft, and the barometric pressure is 13.8 psia. Determine the reading on a pressure gage in inches of mercury vacuum at the suction flange when cavitation is incipient. Assume the suction pipe diameter equals 2 ft and neglect the effects of prerotation. Take c=0.085 Solution; p s abs / Vs2 / 2 g p v / / h let p gage pressure at suction flange p s abs p atm p 13.8 p Vs Q / As 7500 0.002228 / 2 2 / 4 5.319 ft p v / 416 / 61.4 6.775 ft 0.085 13.8 p 144 / 61.4 5.319 2 /( 2 * 32.2) 6.775 / 240 p 2.400 lb / in 2.400 29.9 / 14.7 4.88 inHg 2 or 4.88 in Hg vacuum Example 7 Water is being pumped from a reservoir to the top of a hill, where it is discharged, as shown in Fig. The pump, which is 70 % efficient, is rated at 150kW. Find the flow rate at which water is being discharged from the pipe. Neglect minor losses Solution; p1 / V12 / 2 g z1 E p p 2 / V22 / 2 g z 2 hL E P P / Q 1500.7 / Q9.79 10.725 / Q V Q/ A 500 2 V2 Q / / 4 5.093Q 1000 hL h f f L / D V 2 / 2 g Assume 500 2 2 f 0.018, hL 0.018 975 / 5.093Q) / 2 * 9.807 46.42Q 1000 . 0 0 111.0 10.725 / Q 0 5.093Q) 2 / 2 * 9.807 150.2 46.42Q 2 Q 0.254 m 3 / s (by trial and error) This solution was based on the assumed value of f of 0.018. However, the value of f is dependent on the Reynolds number and relative roughness. Therefore a new value of f should be determined based on the computed value of Q of 0.254 m3/s. / D 0.00030 / 500 / 1000 0.00060 V Q / A 0.254 / 500 / 1000 / 4 1.294 m / s 2 N R DV / v 500 / 10001.294 / 1.02 *10 6 6.34 *10 5 From Fig, f=0.018. Hence, the computed flow rate of 0.254 m3/s is correct. Example 8 Oil with a specific gravity of 0.87 is being pumped from a lower reservoir to an elevated tank as shown in Fig. The pump in the system is 78% efficient and is rated at 185 KW. Determine the flow rate of the oil in the pipe if the total head loss from point 1 to 2 is 12 of oil. Solution; p1 / v12 / 2 g z1 E p p 2 / v 22 / 2 g z 2 hL p1 / p 2 / v 22 / 2 g 0 z1 150m 0.78185 Q * 0.87 * 9.79E P EP 2 2 2 v 22 / 2 g Q / A / 2 g Q / 0.160 / 4 /( 2 * 9.807) 126.12Q 2 P QE P z 2 200m hL 12m 16.94 / Q 0 0 150 16.94 / Q 0 126.12Q 2 200 12 126.12Q 2 16.94 / Q 62 0 By trial and error solution, Q= 0.244 m3/s