Uploaded by Auggi Gelacio

Daikin O&M

advertisement
Installation and Maintenance Manual
IM 1139-8
Group: WSHP
Document PN: 910191715
Date: September 2016
SmartSource® Horizontal Water Source Heat Pump
Model GSH - Single Stage Horizontal Unit (Sizes 007-070)
Model GTH - Two-Stage Horizontal Unit (Sizes 026-072)
Contents
Model Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Information for Initial Start-up . . . . . . . . . . . . . . . . . . 39
Safety, Receiving and Storage . . . . . . . . . . . . . . . . . . 6
Check, Test & Start Procedure . . . . . . . . . . . . . . . . . 39
Pre-Installation Checklist . . . . . . . . . . . . . . . . . . . . . . 6
Typical Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . 40
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
MicroTech III Unit Control with BACnet Communication
Module (HGRH) - 265-277V, 1-Phase . . . . . . . . . . . 40
System Applications . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Water Loop Application . . . . . . . . . . . . . . . . . . . . . . . 8
Ground-Loop Application . . . . . . . . . . . . . . . . . . . . . . 8
Ground-Water Application . . . . . . . . . . . . . . . . . . . . 10
Water System Quality . . . . . . . . . . . . . . . . . . . . . . . . 12
Supply & Return Piping . . . . . . . . . . . . . . . . . . . . . . 14
Discharge Air Conversion . . . . . . . . . . . . . . . . . . . . . 15
Hanger Brackets . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Ductwork and Attenuation . . . . . . . . . . . . . . . . . . . . 18
Duct Location Dimensions . . . . . . . . . . . . . . . . . . . . 19
Return Air Filter Rack Assembly & Duct Collar
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Unit Piping and Electrical Connections Dimensions 20
Waterside Economizer Piping Connections . . . . . . . 21
Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . 22
GSH/GTH Unit With Non-Fused Disconnect Switch 23
Line Voltage Electrical Connections With Disconnect –
115-460V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Low Voltage Wire Connections . . . . . . . . . . . . . . . . 24
Typical Connections For Thermostats & Temperature
Sensors Applications . . . . . . . . . . . . . . . . . . . . . . . . 25
Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Condensate Drain Connection . . . . . . . . . . . . . . . . . 28
Cleaning & Flushing System . . . . . . . . . . . . . . . . . . 29
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Jumper Configuration Settings . . . . . . . . . . . . . . . . 32
MicroTech® III SmartSource Unit Controller . . . . . . . 33
MicroTech SmartSource Controller with LonWorks®
Communication Module . . . . . . . . . . . . . . . . . . . . . . 34
MicroTech III Unit Control with BACnet Communication
Module (WSE & DSH) - 208-230V, 1-Phase with 115V
Loop Pumps and 20kW Electric Heat . . . . . . . . . . . 41
MicroTech III Unit Control with LonWorks
Communication Module . . . . . . . . . . . . . . . . . . . . . . 42
208-230V, 3-Phase with 230V Loop Pumps and 5kW
Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
MicroTech III Unit Control with BACnet Communication
Module (WSE) 460V, 3-Phase with 230V Loop Pumps
and 20kW Electric Heat . . . . . . . . . . . . . . . . . . . . . . 43
MicroTech III Unit Control with Hydronic Heat (HYH) –
208-230V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Motor Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Typical Refrigeration Cycles . . . . . . . . . . . . . . . . . . . 46
Operating Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Motorized Isolation Valve . . . . . . . . . . . . . . . . . . . . . 48
MicroTech III Unit Control with BACnet Communication
Module (HGRH)- 265-277V, 1-Phase, Service &
Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
MicroTech III Unit Control with BACnet Communication
Module (WSE & DSH) Service & Disconnect - 208230V, 1-Phase with 115V Loop Pumps and 20kW
Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
MicroTech III Unit Control with LonWorks
Communication Module Service & Disconnect 208230V, 3-Phase with 230V Loop Pumps and 5kW
Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
MicroTech III Unit Control with BACnet Communication
Module (WSE) Service & Disconnect - 460V, 3-Phase
with 230V Loop Pumps and 20kW Electric Heat . . . 52
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
MicroTech SmartSource Controller with BACnet®
General Maintenance . . . . . . . . . . . . . . . . . . . . . . . . 53
Communication Module . . . . . . . . . . . . . . . . . . . . . . 34
Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Constant Torque EC Motor . . . . . . . . . . . . . . . . . . . . 35
Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Constant CFM Type EC Motor Fan Settings . . . . . . 36
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Fan Performance For Constant CFM EC Motor (Sizes
015–072) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Water Source Heat Pump Equipment Check, Test and
Start Form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Fan Speed Selector Switch . . . . . . . . . . . . . . . . . . . 38
Fan CFM Settings & Performance . . . . . . . . . . . . . . 38
www.DaikinApplied.com
3
IM 1139-8
Model Nomenclature
2-3
4
5-7
8
9
10 11-12 13
14
14
15
17
19
20
24
25
26
27
28
29
W GS
1
H
007
B
1
E
E
4
B
A
C
S
B
3
A
E
P
B
GL
L
Product Category
W - Water Source Heat Pump
Control Secondary Heat Type
B - Boilerless Electric Heat
E - Emergency Electric Heat
P - Primary Electric Heat
(No Heat Pump Heating)
S - Supplemental Heat
Y - None
P - Control for Electric Heat, Single 24V
Signal (Field-installed Duct Heater
by others)
Y - None
Model Type
GS - High Efficiency Single Stage
*GT - High Efficiency Two Stage
Configuration
H - Horizontal
Nominal Capacity
007, 009, 012, 015, 019, 024, *026, 030, *032,
036, *038, 042, *044, 048, *049, 060, *064, 070,
*072
Electric Heating
P - Control for Electric Heat, Single 24V
Signal (Field-installed Duct Heater
by others)
Y - None
Unit Control
B - MicroTech III SmartSource Unit Controller
Design Series (Vintage)
1 - Revision / Design Series 1
WSE
E - Waterside Economizer
Y - None
Voltage
A - 115/60/1 (007-015)
E - 208-230/60/1 (007-072)
F - 208-230/60/3 (024-072)
J - 265/60/1 (007-036)
K - 460/60/3 (024-072)
Filter Type
A - Disposable
E - Merv 8 Factory-Installed
G - Merv 13 (4-inch thick) Factory-Installed
Y - None
Range for Entering Water/Glycol Temp.
GW -Ground Water
WL- Water Loop
GL - Groune Loop
Filter Rack
2 - 4-Sided, 2" w/Duct Collar & Door
3 - 4-Sided, 2" w/Duct Collar, Door, Hi-Merv
Seal
4 - 4-Sided, 4" w/Duct Collar, Door, Hi-Merv
Seal
Y - None
Return Air Location
L - Left-Hand Return & Right-Hand Piping
R - Right-Hand Return & Right-Hand Piping
Communication Module
B - BACnet
L - LonWorks
Y - None
Discharge Air Location
E - End (Horizontal Unit Only)
S - Straight (Horizontal Unit Only)
Fan Motor
4 - ECM Constant CFM
5 - ECM Constant Torque
Primary Air Coil Option
S - Standard
E - E-Coated
Coaxial Heat Exchanger Construction
(Supply Liquid / Refrigerant)
C = Copper Inner Tube - Steel Outer Tube
S = Cupronickel Inner Tube - Steel Outer Tube
Sound Package
Y - None
A - Premium
Dehumidification Option
B - Hot Gas Reheat Smart Dehumidification
(Unit Sizes 015-070)
C - Simplified Dehumidification (Lower CFM
no HGRH or no Humidistat)
D - Humidistat Controlled Dehumidification
(No HGRH)
E - Humidistat Only
Y = None
IM 1139-8
4
www.DaikinApplied.com
Model Nomenclature
31-32 33
1S
Y
34
41
45
47
48
49
51
53
54
56
60
62
63
82
B
A
S
B
B
S
B
A
C
S
B
3
A
E
Loop Pump
1S - One Low Head 230 Volt Pump
1L - One High Head 230 Volt Pump
2S - Two Low Head 230 Volt Pumps
2L - Two High Head 230 Volt Pumps
3S - One Low Head 115 Volt Pump
4S - Two Low Head 115 Volt Pumps
YY - None
1E
Alarm Relay
A - Alarm Relay (Dry Contacts)
Y - None
Expansion Device
A - Thermal Expansion Valve Thermal Bulb
Auto Flow Control 4.0 GPM
Auto Flow Control 5.0 GPM
Auto Flow Control 6.0 GPM
Auto Flow Control 8.0 GPM
Auto Flow Control 9.0 GPM
Auto Flow Control 10.0 GPM
Auto Flow Control 11.0 GPM
Auto Flow Control 12.0 GPM
Auto Flow Control 13.0 GPM
Auto Flow Control 15.0 GPM
Auto Flow Control 18.0 GPM
None
and Equalizer Tube
Thermostat/Sensor Control
T - Thermostat Control
S - Sensor Control
Control Transformer
1 - 50VA Control Transformer
2 - 75VA Control Transformer
Disconnect Switch
Y - None
N - Non-Fused
Fan Motor Control
C - Various Speeds with 4 Adjustment
Settings
Water Coil Piping Package Options
(Hot Water or Waterside Economizer)
A - 3-Way Motorized - 24V Valve Control, NO to Coax
Cabinet Color
Y =None
W = Off White
T - Textured Charcoal Bronze
Primary Drain Pan Material
S - Stainless Steek
Compressor Insulation
B - Compressor Insulation Sound Blanket
(024-072)
Y - None
Cabinet Finish
A - Powder Coat
Y - None
Insulation - Piping
A - Insulated Piping
Y = None
Compressor Isolation
B - Isolated base
Unit Cabinet Insulation
S - 1/2" Fiberglass Skin-Face in Compressor
Section, 1/2" Fiberglass
Foil-Face Insulation in Airside Section
I - Indoor Air Quality Insulation Package 3/8" Closed Cell Foam in Compressor
Section, 3/8" Closed Cell Foam Insulation
in Airside Section
R - Sound Reduction Package – 3/4" Sound
Insulation in Compressor Section and Air
Section (Unit Sizes 007 - 019)*
1/2" Fiberglass Skin-Face in Compressor
Section with Compressor Sound
Blanket, 3/4" Sound Insulation in Airside
Section (Unit Sizes 024 - 072)
www.DaikinApplied.com
FF
Freeze Fault
FF - Freeze Fault Protection
YY - None
Coaxial Coil Supply Liquid Auto Flow Reg
A - Auto Flow Control 1.5 GPM
B - Auto Flow Control 2.0 GPM
C - Auto Flow Control 2.5 GPM
D - Auto Flow Control 3.0GPM
-
C
Extended Warranty, Parts Only
YY - None
1E - 1-Year, Entire Unit Parts Only
2C - 2-Year Parts (Compressor Only)
2R - 2-Year Parts (Refrigerant Circuit)
3C - 3-Year Parts (Compressor Only)
3R - 3-Year Parts (Refrigerant Circuit)
4C - 4-Year Parts (Compressor Only)
4R - 4-Year Parts (Refrigerant Circuit)
Coaxial Coil Supply Liquid Flow Control
B - 2-Way, Motorized - 24v Valve Control, NO
Y - None
E
G
H
I
J
K
L
M
N
P
S
Y
83 90-91 105-106
5
IM 1139-8
General Information
Safety, Receiving and Storage
CAUTION
Sharp edges can cause personal injury. Avoid contact with them.
Upon receipt of the equipment, check carton for visible
damage. Make a notation on the shipper’s delivery
ticket before signing. If there is any evidence of rough
handling, immediately open the cartons to check for
concealed damage. If any damage is found, notify
the carrier within 48 hours to establish your claim and
request their inspection and a report. The Warranty
Claims Department should then be contacted.
For storing, each carton is marked with “up” arrows.
The unit should be shipped or stored in the normal upright position. Do not operate the machine until it has
been in the normal upright position for at least 24 hours.
Temporary storage at the job site must be indoor,
completely sheltered from rain, snow, etc. Units should
not be installed in environments that fall below freezing
or exceed 140°F ambient.
IMPORTANT
This product was carefully packed and thoroughly inspected
before leaving the factory. Responsibility for its safe delivery was
assumed by the carrier upon acceptance of the shipment. Claims
for loss or damage sustained in transit must therefore be made
upon the carrier as follows:
VISIBLE LOSS OR DAMAGE
Any external evidence of loss or damage must be noted on the
freight bill or carrier’s receipt, and signed by the carrier’s agent.
Failure to adequately describe such external evidence of loss or
damage may result in the carrier’s refusal to honor a damage
claim. The form required to file such a claim will be supplied by
the carrier.
CONCEALED LOSS OR DAMAGE
Concealed loss or damage means loss or damage which does
not become apparent until the product has been unpacked. The
contents may be damaged in transit due to rough handling even
though the carton may not show external damages. When the
damage is discovered upon unpacking, make a written request
for inspection by the carrier’s agent within fifteen (15) days of the
delivery date and file a claim with the carrier.
Pre-Installation Checklist
Check all that apply:
□
□
□
To prevent damage, do not operate this equipment
for supplementary ventilation, heating and cooling
during the construction period.
Inspect the carton for any specific tagging numbers
indicated by the factory per a request from the
installing contractor.
Check the unit data plate for correct voltage, phase
and capacity with the plans before installing the
equipment. Also, make sure all electrical ground
connections are made in accordance with local code.
Table 1: Operating Voltages
Voltage
Minimum
Maximum
115/60/1
103
126
208-230/60/1
197
253
265/60/1
238
292
208-230/60/3
197
253
460/60/3
414
506
Note: Three-phase system imbalance shall not exceed 2%.
□
□
□
□
□
□
□
If 460/60/3 unit includes a constant CFM EC motor
verify that a 4-wire power supply is provided that
includes a neutral wire providing 265 volt power to
the fan motor.
Check the unit size against the plans to verify that
the unit is being installed in the correct location.
Before installation, check the available ceiling height
versus the height of the unit.
Note the location and routing of water piping,
condensate drain piping, and electrical wiring. The
locations of these items are clearly marked on
submittal drawings.
The installing contractor will find it beneficial to
confer with piping, sheet metal, and electrical
foremen before installing any unit.
The contractor shall cover the units to protect the
machines during building construction. This is
critical while spraying fireproofing material on bar
joists, sandblasting, spray painting and plastering. If
plastic film is not available, the shipping carton may
be modified to cover the units during construction.
Remove shipping brackets securing unit to skid.
WARNING
The installer must determine and follow all applicable local and
national codes and regulations. This equipment presents hazards
of electricity, rotating parts, sharp edges, heat and weight. Failure
to read and follow these instructions can result in property
damage, severe personal injury or death. This equipment must
be installed by experienced, trained personnel only.
IM 1139-8
6
www.DaikinApplied.com
Physical Data
Table 2: Unit sizes 007 through 032
Unit Sizes 007 through 032
Description
Compressor Type
007
009
012
015
019
024/026
030/032
Rotary
Rotary
Rotary
Rotary
Rotary
Scroll
Scroll
Refrigeration Charge (Oz.)
26
26
29
42
42
56
54
Fan Wheel (D x W)
6" x 8"
6" x 8"
6" x 8"
9" x 7"
9" x 7"
9" x 7"
9" x 7"
Fan Motor HP
1/10
1/10
1/10
1/3
1/3
1/3
1/2
Water Connection Size (FPT)
1/2"
1/2"
1/2"
3/4"
3/4"
3/4"
3/4"
Coax & Water Piping Volume
(Gal. @ 70ºF)
0.2
0.2
0.2
0.5
0.5
0.5
0.5
Condensate Connection Size (FPT)
3/4
3/4
3/4
3/4
3/4
3/4
3/4
Air Coil Face Area (Sq Ft.)
2.1
2.1
2.1
2.5
2.5
4.1
Waterside Economizer Coil Volume (Gal.)
0.64
0.85
4.1
1.28
Filter Size
15.5" x 20.0"
15.5" x 20.0"
15.5" x 20.0"
18.0" x 20.0"
18.0" x 20.0"
16.75" x 34"
16.75" x 34"
Operating Weight
148
151
154
200
214
254
256
Shipping Weight
165
168
171
214
228
289
291
Table 3: Unit sizes 036 through 072
Unit Sizes 036 through 072
Description
036/038
042/044
048/049
060/064
070/072
Scroll
Compressor Type
Scroll
Scroll
Scroll
Scroll
Refrigeration Charge (Oz.)
72
90
88
120
122
Fan Wheel (D x W)
11" x 10"
11" x 10"
11" x 10"
11" x 10"
11" x 10"
Fan Motor HP
1/2
3/4
3/4
1
1
Water Connection Size (FPT)
3/4"
1"
1"
1"
1"
Coax & Water Piping Volume (Gal. @ 70ºF)
1.1
1.2
1.2
2.1
2.1
Condensate Connection Size (FPT)
3/4
3/4
3/4
3/4
3/4
Air Coil Face Area (Sq Ft.)
5.0
5.6
5.6
Waterside Economizer Coil Volume (Gal.)
1.59
6.4
6.4
1.84
2.09
Filter Size
18.75" x 37.25"
18.75" x 42.62"
18.75" x 42.62"
18.75" x 48"
18.75" x 48"
Operating Weight
329
365
367
472
478
Shipping Weight
361
408
410
514
521
Table 4: Horizontal unit corner weights, percentage of total operating weight (Base unit only)
007
148
009
151
012
154
015
200
019
214
024/026
254
030/032
256
036/038
329
042/044
365
048/049
367
060
472
070/072
478
www.DaikinApplied.com
Corner Weight % of Total Operating Weight
A
B
C
D
D
C
Water Connections
Compressor
30%
20%
20%
30%
B
7
Unit Front
Total
Operating Weight (lbs.)
Control Box
Unit
Size
A
IM 1139-8
System Applications
Water Loop Application
Commercial systems typically include a number of
units connected to a common piping system. Any unit
plumbing maintenance work can introduce air into the
piping system; therefore air elimination equipment is a
major portion of the mechanical room plumbing. In piping
systems expected to utilize water temperatures below
50°F [10°C], closed cell insulation is recommended on
all piping surfaces to eliminate condensation (extended
range units required). Metal to plastic threaded joints
should never be used due to their tendency to leak over
time. All SmartSource units include flush mounted FPT
water connections integral to the unit corner post, which
do not require a backup wrench.
A thread sealant is recommended to minimize internal
fouling of the heat exchanger. Do not over tighten
connections and route piping so as not to interfere with
service or maintenance access. Hose kits are available
from Daikin in different configurations for connection
between the unit and the piping system. Depending
upon selection, hose kits may include shut off valves,
P/T plugs for performance measurement, high pressure
stainless steel braided hose, “Y” type strainer with blow
down valve, and/or “J” type swivel connection. Balancing
valves and an external low pressure drop solenoid valve
for use in variable speed pumping systems may also be
included in the hose kit.
The piping system should be flushed to remove dirt,
piping chips, and other foreign material prior to operation
(see "Cleaning & Flushing System" on page 29. The
water flow rates should be kept at approximately 3 GPM
per nominal cooling ton (a 10°F temperature rise in
cooling). To ensure proper maintenance and servicing,
P/T ports are imperative for temperature and flow
verification, as well as performance checks.
Water loop heat pump (cooling tower/boiler) systems
typically utilize a common loop, maintained between 60 90°F [16 - 32°C]. The use of a closed circuit evaporative
cooling tower with a secondary heat exchanger between
the tower and the water loop is recommended. If an
open type cooling tower is used continuously, chemical
treatment and filtering may be necessary.
Ground-Loop Application
CAUTION
The following instructions represent industry accepted
installation practices for closed loop earth coupled heat pump
systems. Instructions are provided to assist the contractor in
installing trouble free ground loops. These instructions are
recommendations only. State/provincial and local codes MUST be
followed and installation MUST conform to ALL applicable codes.
It is the responsibility of the installing contractor to determine and
comply with ALL applicable codes and regulations.
CAUTION
Ground loop applications require extended range equipment and
optional refrigerant/water circuit insulation.
Pre-Installation
Prior to installation, locate and mark all existing
underground utilities, piping, etc. Install loops for new
construction before sidewalks, patios, driveways, and
other construction has begun. During construction,
accurately mark all ground loop piping on the plot plan
as an aid in avoiding potential future damage to the
installation.
Piping Installation
The typical closed loop ground source system is shown
in Figure 2 on page 9. All earth loop piping materials
should be limited to polyethylene or equivalent per
International Ground Source Heat Pump Association
(IGSHPA)
Figure 1: Polyethylene fused piping
Galvanized or steel fittings should not be used at any
time due to their tendency to corrode. All plastic to metal
threaded fittings should be avoided due to their potential
to leak in earth coupled applications. A flanged fitting
should be substituted. P/T plugs should be used so that
flow can be measured using the pressure drop of the
unit heat exchanger.
IM 1139-8
8
www.DaikinApplied.com
System Applications
Figure 2: Typical water loop application (with optional unit-mounted loop pumps)
Supply & Return
To Ground
Loop Piping
Power
Disconnect
Line Voltage
Wiring
Loop Fluid
Temperature Gauges
Low Voltage Wiring
Factory Mounted Loop Pumps
Shutoff Ball Valves with P/T Ports
Flexible Hoses
Earth loop temperatures can range between 25 and
110°F [-4 to 43°C]. The water flow rates should be kept
at approximately 3 GPM per nominal cooling ton (a 10°F
temperature rise in cooling).
Test individual horizontal loop circuits before backfilling.
Test vertical U-bends and pond loop assemblies prior to
installation. Pressures of at least 100 psi [689 kPa] should
be used when testing. Do not exceed the pipe pressure
rating. Test entire system when all loops are assembled.
Calculate the total volume of fluid in the piping system.
Then use the percentage by volume shown in Table 6 on
page 10 for the amount of antifreeze needed. Antifreeze
concentration should be checked from a well mixed sample
using a hydrometer to measure specific gravity.
Figure 3: Flushing the loop
Flushing the Earth Loop
Upon completion of system installation and testing, flush
the system to remove all foreign objects and purge to
remove all air.
Antifreeze
In areas where minimum entering loop temperatures
drop below 50°F [10°C] or where piping will be routed
through areas subject to freezing, antifreeze is required.
Alcohols and glycols are commonly used as antifreeze;
however your local sales office should be consulted
to determine the antifreeze best suited to your area.
Freeze protection should be maintained to 15°F [9°C]
below the lowest expected entering loop temperature.
For example, if 30°F [-1°C] is the minimum expected
entering loop temperature, the leaving loop temperature
would be 22 to 25°F [-6 to -4°C] and freeze protection
should be at 15°F [-10°C]. Calculation is as follows: 30°F
- 15°F = 15°F [-1°C - 9°C = -10°C].
All alcohols should be premixed and pumped from
a reservoir outside of the building when possible or
introduced under the water level to prevent fumes.
www.DaikinApplied.com
9
IM 1139-8
System Applications
Table 5: Antifreeze percentage by volume
Minimum Temperature for Low Temperature Protection
Type
Note:
1
10°F [-12.2°C]
15°F [-9.4°C]
20°F [-6.7°C]
25°F [-3.9°C]
Methanol
25%
21%
16%
10%
100% USP food grade Propylene Glycol
38%
25%
22%
15%
Ethanol1
29%
25%
20%
14%
Must not be denatured with any petroleum product.
Table 6: Antifreeze correction factors (for heat pump operation only)
Antifreeze % By Weight
15%
25%
35%
45%
Ethanol
Cooling Capacity
0.985
–
–
–
Heating Capacity
0.9825
–
–
–
Pressure Drop
1.04
–
–
–
Ethylene Glycol
Cooling Capacity
0.9935
0.9895
0.985
0.981
Heating Capacity
0.9865
0.9795
0.973
0.965
Pressure Drop
1.10
1.16
1.22
1.27
Methanol
Cooling Capacity
0.985
–
–
–
Heating Capacity
0.9825
–
–
–
Pressure Drop
1.04
–
–
–
Propylene Glycol
Cooling Capacity
0.985
0.975
0.965
0.955
Heating Capacity
0.981
0.9685
0.952
0.936
Pressure Drop
1.11
1.20
1.31
1.40
Ground-Water Application
Open Loop - Ground Water Systems - Typical open
loop piping is shown in Figure 4. Shut off valves should
be included for ease of servicing. Boiler drains or other
valves should be installed in the supply and return lines
to allow cleaning of the heat exchanger. Shut off valves
should be positioned to allow flow through the coax via
the boiler drains without allowing flow into the piping
system. P/T plugs should be used so that pressure drop
and temperature can be measured. Piping materials
should be limited to copper.
WARNING
PVC or CPVC should not be used as they are not compatible
with the POE oils used in HFC-410A products and piping system
failure and property damage may result.
IM 1139-8
Water quantity should be plentiful and of good quality.
See "Water impurities, result & recommended water
system application" on page 13 for water quality
guidelines. The unit can be ordered with either a
copper or cupro-nickel water heat exchanger. Consult
Table 8 on page 13 for recommendations. Copper
is recommended for open loop ground water systems
that are not high in mineral content or corrosiveness.
In conditions anticipating heavy scale formation or
in brackish water, a cupro-nickel heat exchanger is
recommended. In ground water situations where scaling
could be heavy or where biological growth such as iron
bacteria will be present, an open loop system is not
recommended. Heat exchanger coils may over time lose
heat exchange capabilities due to build up of mineral
deposits. Heat exchangers must only be serviced by
a qualified technician, as acid cleaning and special
pumping equipment may be required.
10
www.DaikinApplied.com
System Applications
Figure 4: Typical open loop application
Boiler Drains
Return
Supply
Shutoff Valve
Flow
Regulator
Optional
(Field-Installed) Water Control Valve
Supply from Loop
Optional Filter
Power Disconnect
Water Hose Valves
with P/T Plugs
Water Quality Standards - Table 8, Water impurities,
result & recommended water system application"
on page 13 should be consulted for water quality
requirements. Scaling potential should be assessed
using the pH/Calcium hardness method. If the pH
<7.5 and the calcium hardness is less than 100 ppm,
scaling potential is low. If this method yields numbers
out of range of those listed, the Ryznar Stability and
Langelier Saturation indices should be calculated. Use
the appropriate scaling surface temperature for the
application, 150°F [66°C] for direct use (well water/
open loop); 90°F [32°F] for indirect use. A monitoring
plan should be implemented in these probable scaling
situations. Other water quality issues such as iron
fouling, corrosion prevention and erosion and clogging
should be referenced in Table 8 on page 13.
Expansion Tank and Pump - Use a closed, bladder
type expansion tank to minimize mineral formation due
to air exposure. The expansion tank should be sized to
provide at least one minute continuous run time of the
pump using its draw-down capacity rating to prevent
pump short cycling. Discharge water from the unit is not
contaminated in any manner and can be disposed of in
various ways, depending on local building codes (e.g.
recharge well, storm sewer, drain field, adjacent stream
or pond, etc.). Most local codes forbid the use of sanitary
sewer for disposal. Consult your local building and
zoning department to assure compliance in your area.
www.DaikinApplied.com
11
Water Control Valve - Note the placement of the
water control valve in Figure 4. Always maintain water
pressure in the heat exchanger by placing the water
control valve(s) on the return line to prevent mineral
precipitation during the off-cycle. Pilot operated slow
closing valves are recommended to reduce water
hammer. If water hammer persists, a mini-expansion
tank can be mounted on the piping to help absorb the
excess hammer shock. If a field provided motorized
valve and actuator is utilized, ensure that the total
‘VA’ draw of the valve can be supplied by the unit
transformer. For instance, a slow closing valve can draw
up to 35VA. Units are furnished with a factory-installed
50 VA transformer. An optional 75VA transformer is also
available. A typical pilot operated solenoid valve draws
approximately 15VA (see Figure 45 on page 48).
IM 1139-8
System Applications
Flow Control - Flow control can be accomplished by
two methods. One method involves simply adjusting
the field-provided ball valve or flow control valve on
the return line. Measure the pressure drop through
the unit heat exchanger, and determine flow rate from
Table 7. Since the pressure is constantly varying, two
pressure gauges may be needed. Adjust the valve until
the desired flow of 1.5 to 4 gpm, per ton [5.7 to 15.1 l/m,
per kW] is achieved. A second method of flow control
requires a flow control device mounted on the outlet of
the flow control valve. This device is typically a brass
fitting with an orifice of rubber or plastic material that is
designed to allow a specified flow rate. On occasion,
flow control devices may produce velocity noise that
can be reduced by applying some back pressure from
the ball valve located on the discharge line. Slightly
closing the valve will spread the pressure drop over both
devices, reducing the velocity noise.
Table 7: Water pressure drop
Unit Size
007
009
012
015
019
024/026
030/032
036/038
042/044
048/049
IM 1139-8
GPM
Pressure Drop, psi (kPa)
50ºF
70ºF
90ºF
1.0
0.7
1.6
0.7
1.5
1.4
3.0
1.3
2.0
2.2
4.8
2.0
1.9
2.0
1.9
1.8
2.3
2.7
2.6
2.5
3.4
3.4
3.3
3.2
2.0
5.1
2.1
2.0
3.0
9.7
4.1
3.9
4.0
15.4
6.4
6.2
2.5
1.2
1.1
1.1
3.8
2.6
2.5
2.4
5.0
4.5
4.3
4.2
3.8
2.5
2.4
2.3
4.5
3.6
3.4
3.3
5.3
4.9
4.7
4.5
4.0
1.1
1.0
1.0
6.0
2.3
2.2
2.1
8.0
3.9
3.7
3.6
5.0
1.6
1.6
1.5
7.5
3.4
3.3
3.2
10.0
5.8
5.5
5.3
6.0
1.9
1.8
1.8
9.0
4.0
3.9
3.7
12.0
6.8
6.5
6.3
7.0
1.0
1.0
0.9
10.5
2.1
2.1
2.0
14.0
3.7
3.5
3.4
10.0
2.0
1.9
1.8
12.0
2.8
2.6
2.5
14.0
3.7
3.5
3.4
060/064
070/072
10.0
2.0
2.0
1.9
15.0
4.4
4.2
4.1
20.0
7.7
7.3
7.1
15.0
4.4
4.2
4.1
18.0
6.3
6.0
5.8
21.0
8.4
8.1
7.8
Water System Quality
The cleaning, flushing and chemical treatment of a water
source heat pump system is fundamental to efficient
operation and the life expectancy of the system.
Potential system problems produced by the use of water
fall into three general categories:
1. Scale formation – Mineral deposits which result from
the crystallization and precipitation of dissolved salts
in the water. The deposits form an insulating barrier,
reducing the heat transfer rate and impeding the
circulation of fluids due to increased pressure drop.
2. Corrosion – Decomposition of the metal caused
by absorption of gases from the air. Corrosion may
occur in any metal component of the system.
3. Organic growths – Slime and algae which form
under certain environmental conditions, and
can reduce the heat transfer rate by forming an
insulating coating or can promote corrosion by
pitting.
The system water should be evaluated for degrees of
impurity, with testing available from independent testing
labs, health departments or state agencies.
Table 8 on page 13 is a list of water characteristics,
the potential impurities and their results and the
recommended treatment.
Avoiding Potential Problems
As shown in Table 8 on page 13, all water contains
some degree of impurities which may affect the
performance of a heat pump system. The use of a cupronickel coil can help avoid potential problems. Water flow
rates should:
• Be high enough that the temperature rise through
the heat exchanger does not exceed 12° F when
operating in the cooling mode.
•
12
Not exceed 4 GPM per nominal ton. Flow rates that
have velocities of 10 feet per second or more may
cause pipe erosion and heat exchanger failure.
www.DaikinApplied.com
System Applications
Table 8: Water impurities, result & recommended water system application
Impurity
Copper Coils
Cupro-nickel Coils
Calcium &
Magnesium Salts
(hardness)
Less than
350 ppm
350 ppm
Sea Water
Iron oxide
Low levels only
Moderate levels
pH
7-9
5 – 10
Hydrogen Sulfide
Less than 10 ppm
10 – 50 ppm
CO2
Less than 50 ppm
50 – 75 ppm
Chloride
Less than 300 ppm
300 – 600 ppm
Total Dissolved
Solids
Less than 1000 ppm
1000 – 1500 ppm
Slime & Algae
Slime and algae can form under
certain environmental conditions
Result
Scaling
Corrosion
Reduced heat
transfer due
to forming of
insulating coating, or
pitting due to
corrosion
Application
Open Recirculating
1. Bleed-off
2. Surface active agents such as
polyphosphates.
3. Addition of acid.
4. pH adjustment.
Other considerations:
▪ Adequate fouling factor
▪ Surface temperature
▪ Water temperature
▪ Clean system
1. Corrosion inhibitors in high concentrations (200 to 500 ppm).
2. Corrosion inhibitors in low concentrations (20 to 80 ppm).
3. pH control.
4. Proper materials of construction.
Chlorinated phenols.
Other biocides.
Chlorine by hypochlorites or by
liquid chlorine
Closed Recirculating
No treatment required
Corrosion inhibitors in high concentrations.
Proper materials of
construction.
No treatment required
Notes: 1. The tremendous variety in water quality around the country makes the recommendation of a single best method of treatment
impossible. Consult a local water treatment specialist for specific treatment recommendations.
2. Cupro-nickel is recommended if iron bacteria is high, suspended solids or dissolved oxygen levels are high.
3. If the concentration of these corrosives exceeds the maximum tabulated in the cupro-nickel column, then the potential for serious
corrosion problems exists.
www.DaikinApplied.com
13
IM 1139-8
System Applications
Supply & Return Piping
Pre-Installation Considerations
All units should be connected to supply and return piping
in a two-pipe reverse return configuration. A reverse
return system is inherently self-balancing and requires
only trim balancing where multiple quantities of units with
different flow and pressure drop characteristics exist in
the same loop.
A direct return system may also work acceptably, but
proper water flow balancing is more difficult to achieve
and maintain.
• The piping can be steel or copper.
Note: Polyolester Oil, commonly know as POE oil is a
synthetic oil used in many refrigeration systems.
POE oil, if ever in contact with PVC/CPVC will
coat the inside wall of PVC/CPVC pipe causing
environmental stress fractures.
It is recommended that PVC/CPVC piping is not
used in the installation of the loop system, as system failure and property damage could result.
Supply and return runouts usually join the unit via short
lengths of high pressure flexible hose which are sound
and vibration isolators for both unit operating noise and
hydraulic pumping noise.
•
One end of the hose should have a swivel fitting to
facilitate removal for service.
Note: 1. No unit should be connected to the supply
and return piping until the water system has
been cleaned and flushed completely, see
"Cleaning & Flushing System" on page 29.
After the cleaning and flushing has taken
place, the initial connection should have all
valves wide open in preparation for water
system flushing.
2. Hard piping is not recommended since no
vibration or noise attenuation can be accomplished.
3. Supply and return shutoff valves are required
at each unit. The return valve can be used
for balancing. When used it should have a
“memory stop” so that it can be closed off,
and reopened to the proper position for the
required flow.
4. Do not over-torque fittings. The maximum
torque without damage to fittings is 30 foot
pounds. If a torque wrench is not available,
use as a rule of thumb, finger tight plus one
quarter turn.
Figure 5: Example of a reverse return piping system
IM 1139-8
14
www.DaikinApplied.com
System Applications
Discharge Air Conversion
Installation Considerations
1. Locate the unit in conditioned space and avoid
installation in corrosive environments. Allow
clearance for easy removal of the filter and access
panels, and enough space for service personnel to
perform maintenance or repair.
2. Remove the Styrofoam shipping block under the fan
housing before start-up. Figure 6.
3. Make sure that sufficient access has been provided
for installing and removing the unit, including
clearance for duct collars and fittings at water and
electrical connections (see Figure 10).
A straight discharge unit may be converted to an end
discharge by doing the following:
Note: The information covered in this section of the
blower assembly orientation is typical of Daikin
units. Regardless, if you are changing end to
straight or straight to end the blower assembly
has to turn 90 degrees and simultaneously rotate
180 degrees to achieve the proper orientation.
Not all Daikin units will have the same air discharge location but will have the same general
results when following the instructions.
DANGER
4. Unit condensate drains are not internally trapped.
External trap is required. Allow adequate room around
the unit for condensate piping.
Hazardous Voltage! Disconnect all electric power
including remote disconnects before servicing.
Failure to disconnect power before servicing can
cause severe personal injury or death.
5. If the unit is installed in a confined space, provisions
must be made for return air to freely enter the face of
the unit’s air coil.
Figure 6: Horizontal unit foam shipping block
CAUTION
Sharp edges can cause personal injury. Avoid contact with them.
6. Turn off power to the unit at the breaker box.
7. Remove the top panel by removing the screws
around the perimeter of the top securing it to the
lower cabinet (Figure 7 on page 15).
Remove foam
shipping block
Note: Retain all screws for reinstalling.
8. Remove the access panel to the fan motor by
loosening the two (2) screws at the bottom holding
the panel (Figure 7 on page 15). Remove the
piece of insulation at the bottom on the side of the
bottom panel.
Figure 7: Remove top and access panel to fan motor
Remove Top
Remove screws around
the perimeter of top
Remove Access Panel to
Fan Assembly
Fan Discharge Panel Assembly
(Bottom-Horizontal Orientation)
Remove two (2) screws at bottom of access panel to access fan motor
www.DaikinApplied.com
15
IM 1139-8
System Applications
Discharge Air Conversion (Continued)
10. Secure the fan assembly to the unit frame with the
screws removed previously.
Remove the screws securing the fan discharge panel
assembly (Figure 7).
9. Lift the fan assembly out rotating it 180 degrees and
position it within the opening at the end of the unit
(Figure 8). With the fan motor in the end discharge
position the fan and housing orientation is tophorizontal. In a straight air discharge arrangement
the housing is in the bottom-horizontal orientation.
11. Reinstall the access panel in the fan motor access
opening (Figure 9 on page 16).
12. Reinstall the top panel and secure with screws
removed previously.
Note: If installed correctly the fan motor should be
accessible when the fan motor access panel is
removed.
Figure 8: Lift out the fan assembly, turn 90 degrees and rotate 180 degrees
Rotate the Fan Assembly 180 degrees
End Discharge
Arrangement
(Top-Horizontal) Orientation
Position the fan assembly in the
end opening with the fan in the
“top-horizontal” orientation
Straight Discharge Arrangement
(Bottom-Horizontal) Orientation
Remove screws securing the fan assembly
to the cabinet. Note bottom-horizontal
orientation of fan assembly
Figure 9: Reinstall the top and access panel
Reinstall Top
Reinstall Access Panel
to Fan Motor
IM 1139-8
16
www.DaikinApplied.com
System Applications
Figure 10: Recommended minimum & optimum unit clearances
Hanger Brackets
Figure 12: Hanger bracket details (sizes 007-019)
Figure 11: Hanger bracket locations - sizes 026-072
3/8" Threaded Rod
(By Others)
X
Y
Bolt & Lock
Washer
Vibration Isolator
Washer
Hex Nuts (Double)
(By Others)
W
Table 9: Hanger bracket location dimensions, in inches (mm)
Unit Size
W
X
Y
007, 009, 012
44.67 (1135)
23.60 (599)
19.10 (485)
015, 019
50.06 (1272)
24.40 (620)
19.90 (505)
024, 026, 030, 032
62.16 (1579)
23.90 (607)
18.64 (474)
036, 038
72.16" (1833)
27" (686)
21.24" (539)
042, 044, 048
77.57" (1970)
27" (686)
21.24" (539)
060, 064, 070, 072
82.97" (2107)
27" (686)
21.24" (539)
Figure 13: Heavy-duty hanger brackets (sizes 024-072)
3/8"
Threaded Rod
(By Others)
Heavy-Duty Bracket
Note: All dimensions within ± 0.10 inches (2.5 mm).
Vibration Isolator
Bolt & Lock Washer
Hex Nuts (Double)
(By Others)
Horizontal unit sizes 024 through 072 are provided with
heavy-duty hanger brackets, fastening bolts, vibration
isolators and washers. Do not subsitute these brackets
for others, for unit sizes 024 through 072. 3/8" threaded
rods and hex nuts (doubled) are provided by others.
www.DaikinApplied.com
17
IM 1139-8
System Applications
WARNING
Clearance should be maintained to meet local and national code requirements.
Figure 14: Typical ducting of horizontal unit
Acoustically
Insulated Return
Air Duct
Trunk Duct
Room Air
Supply Diffuser
Flexible (Boot)
Connector
Acoustically Insulated
Duct (approximately 10')
Trunk Duct Tee
Branch Duct
Room Air Supply Diffuser
Branch Duct
Room Air Supply Diffuser
Ductwork and Attenuation
Discharge ductwork is normally used with these
conditioners. Return air ductwork may also be required.
All ductwork should conform to industry standards of
good practice as described in the ASHRAE Systems
Guide.
A field supplied discharge duct system will normally
consist of:
• a flexible connector at the unit
•
a 10 ft. length of insulted duct
•
and a trunk duct teeing into a branch duct with
discharge diffusers as shown in Figure 14
With metal duct material, the entire branch duct should
be internally lined with acoustic fibrous insulation for
sound attenuation. Glass fiber duct board material is
more absorbing and may permit omission of the flexible
boot connector.
As a general recommendation, the acoustic fibrous
insulation should be at least 1/2 inch thick over the
entire duct run (Figure 14). For better sound attenuation,
line the last five diameters of duct before each register
IM 1139-8
with a one-inch thick sound blanket. Elbows, tees and
dampers can create turbulence or distortion in the
airflow. Place a straight length of duct, 5 to 10 times the
duct width, before the next fitting to smooth out airflow.
Diffusers that are located in the bottom of a trunk duct
can also produce noise. For this same reason, volume
control dampers should be located several duct widths
upstream from an air outlet.
For Hotel, Motel, Dormitory or Nursing Home
applications that use a single duct discharge, a velocity
of 500 to 600 fpm is suggested. These applications
typically have static pressures as low as 0.05 inches of
water and duct lengths approximately six feet in length.
The discharge duct must be fully lined and have a
square elbow without turning vanes. Return air for these
applications should enter through a “low” sidewall filter
grille and route up the stud space to a ceiling plenum.
For horizontal heat pumps mounted from the ceiling,
an insulated return plenum is sometimes placed at the
return air opening to further attenuate line-of-sight sound
transmission through return openings.
18
www.DaikinApplied.com
Installation
Duct Location Dimensions
Figure 15: Discharge duct collar location
P
P
FM AP
FM AP
O
O
R
R
Q
G
G
Left Return - End Discharge
Q
Right Return - End Discharge
FM AP
O
Front
N
P
N
M
M
Left Return - Straight Discharge View
Legend:
Front
O
P
Right Return - Straight Discharge View
FM AP = Fan Motor Access Panel
Table 10: Discharge duct collar dimensions, in inches (mm)
Discharge Air Duct Connection in inches (mm)
GSH
Horizontal Unit
M
007, 009, 012
015, 019
N
O
P
Q
8.09 (206)
4.89 (124 )
9.45 (240)
5.75 (146)
3.15 (80)
10.46 (266)
9.33 (237)
4.41 (112)
6.20 (157)
2.71 (69)
10.39 (264)
4.88 (124)
4.74 (120)
2.81 (71)
13.75 (349)
4.88 (124)
4.74 (120)
2.81 (71)
13.75 (349)
4.88 (124)
4.74 (120)
2.81 (71)
13.75 (349)
Left-hand
Right-hand
6.18 (157)
4.25 (108)
4.64 (118)
024, 026, 030, 032
036, 038
042, 044, 048, 049
060, 064, 070, 072
R
Left-hand
Right-hand
6.12 (156)
8.09 (206)
4.25 (108)
4.63 (118)
3.15 (80)
5.75 (146)
9.32 (237)
4.41 (112)
2.71 (69)
6.20 (157)
13.25 (337)
4.88 (124)
2.81 (71)
4.74 (120)
13.25 (337)
4.88 (124)
2.81 (71)
4.74 (120)
13.25 (337)
4.88 (124)
2.81 (71)
4.74 (120)
Note: All duct dimensions are referenced from the outside edge of the flange.
Figure 16: Return air duct collar location
.839" (21.3 mm)
ZH
.839"
(21.3 mm)
* 2.10" (53 mm)
See Note
2.125" (54 mm)
ZW
.839"
(21.3 mm)
.839"
(21.3 mm)
.839" (21.3 mm)
Table 11: GSH horizontal unit 2" (51mm) filter rack assembly & duct collar dimensions, in inches (mm)
Unit Size
Dimension
Note:
007, 009, 012
015, 019
024, 026, 030,
032
ZH
13.91 (353)
16.49 (419)
15.45 (392)
17.45" (443)
17.45 (443)
17.45 (443)
ZW
19.35 (491)
23.38 (594)
32.51 (826)
35.76" (908)
41.15" (1045)
46.55" (1182)
036, 038
042, 044, 048,
049
060, 064, 070,
072
* Optional 4" filter rack = 4.10" (104 m
www.DaikinApplied.com
19
IM 1139-8
Installation
Return Air Filter Rack Assembly &
Duct Collar Connections
Return air ductwork can be connected to the standard
filter rack, see Figure 16 on page 19. The unit comes
standard with a 2" (51mm) thick factory-installed
throwaway filter, mounted in a 4-sided combination
filter rack and return air duct collar. Filters can be
easily removed from either side by interchanging the
removable filter door to the right or left side and rotating
the filter rack assembly 180 degrees. Do not use sheet
metal screws directly into the unit cabinet for connection
of supply or return air ductwork, especially return air
ductwork which can hit the drain pan or the air coil.
Unit Piping and Electrical
Connections Dimensions
Figure 18: Piping & electrical connections locations
Line Voltage
(3/4" Conduit Connection)
Low Voltage
(1/2" Conduit Connection)
C AP
Figure 17: Filter rack filter door removal
L
K
E
D
J
H
F
Front View
Threaded
access door
knobs
Filter rack
Filter access door
Ventilation Air
Ventilation may require outside air. The temperature of
the ventilation air must be controlled so that mixture of
outside air and return air entering the conditioner does
not exceed conditioner application limits. It is also typical
to close off the ventilation air system during unoccupied
periods (night setback).
The ventilation air system is generally a separate
building subsystem with distribution ductwork. Simple
introduction of the outside air into each return air plenum
chamber reasonably close to the conditioner air inlet is
recommended. Do not duct outside air directly to the
conditioner inlet. Provide sufficient distance for thorough
mixing of outside and return air. See "Operating Limits"
on page 48.
11/16"
G
Condensate Drain End View
Legend:
C AP = Control Access Panel
Table 12: Piping & electrical connections dimensions, in inches (mm)
Piping Connections in inches (mm)
GSH / GTH
Horizontal Unit
D
E
Electrical Connections in inches (mm)
K
L
F
Condensate
Drain 3/4" FPT
G
H
Low
Voltage
J
Between
Line
Voltage
Supply
Return
Supply & Return
Connections
FPT
007, 009, 012
2.65 (67)
5.65 (144)
1/2"
1.47 (37)
3.76 (96)
1.98 (50)
2.08” (53)
7.06 (179)
9.14 (232)
9.14 (232)
015, 019
2.95 (75)
5.95 (151)
3/4"
1.47 (37)
4.07 (103)
1.98 (50)
2.08 (53)
7.06 (179)
024, 026, 030
2.58 (66)
13.39 (340)
3/4"
1.57 (40)
4.29 (109)
1.94 (49)
2.57 (65)
7.36 (187)
9.93 (252)
036, 038
2.76 (70)
13.57 (345)
3/4"
1.57 (40)
4.36 (111)
1.94 (49)
3.57 (91)
8.23 (209)
11.81 (300)
042, 044, 048, 049,
3.07 (78)
13.88 (353)
1"
1.57 (40)
4.36 (111)
1.94 (49)
3.57 (91)
8.23 (209)
11.81 (300)
060, 064, 070, 072,
3.07 (78)
13.88 (353)
1"
1.57 (40)
4.36 (111)
1.94 (49)
3.57 (91)
8.23 (209)
11.81 (300)
IM 1139-8
20
www.DaikinApplied.com
Installation
Waterside Economizer Piping Connections
Figure 19: Waterside economizer unit descriptions
WSE return
Water return
Unit condensate drain connection
Factory installed internal 3-way
motorized valve access
WSE supply
*WSE condensate drain connection
Field installed jumper hose
(reference Daikin hose kit option # 8 for recommended sizes)
Water supply
Note:
*The economizer package incorporates its own drain pan to collect condensate from the coil. This pan MUST be independently trapped
and piped into the drain line for the heat pump.
Figure 20: Waterside economizer piping location dimensions
GSH / GTH Horizontal Unit
Supply & Return Connections
Unit Size
A
Condensate Connections
B
C
FPT
D
E
FPT
F
007, 009, 012
3.50
9.29
6.36
1/2"
1.38
4.25
22.58
015, 019
3.50
10.88
6.89
3/4"
0.88
4.25
24.94
024, 026, 030, 032
3.36
9.38
7.23
3/4"
1.70
4.25
036, 038
2.94
14.07
7.42
3/4"
1.70
4.25
042, 044, 048, 049
2.94
14.07
7.42
1"
1.70
4.25
33.65
060, 064, 070, 072
2.94
14.07
7.42
1"
1.70
4.25
33.67
www.DaikinApplied.com
21
3/4"
27.19
33.93
IM 1139-8
Electrical Connections
Electrical Connections
Figure 21: Route line voltage wires to terminal screws.
5
WARNING
4
All field installed wiring must comply with local and national
electric codes. This equipment presents hazards of electricity,
rotating parts, sharp edges, heat and weight. Failure to read and
follow these instructions can result in property damage, severe
personal injury or death. This equipment must be installed by
experienced, trained personnel only.
3
CAUTION
Fasteners should not be screwed into and penetrate the unit enclosure
to avoid damage to internal electrical and mechanical components.
2
1
WARNING
Use copper conductors only. Conductors must be minimum 75°C.
Table 13: Operating voltages
Voltage
Minimum
Maximum
115/60/1
103
126
208-230/60/1
197
253
265/60/1
238
292
208-230/60/3
197
253
460/60/3
414
506
Note: Three-phase system imbalance shall not exceed 2%.
•
Use a short length of flexible conduit at the unit
connection to minimize and isolate vibration to the
building. All conduit should be supported to avoid
contact with unit cabinet or immediate building
structure to prevent unnecessary noise.
CAUTION
Note: Units without constant EC motor will not include a
neutral conductor. For clarity, not all unit wires are
shown in the unit line voltage connection area.
Line Voltage – 115V
1. Route line voltage supply wiring through the upper
1-1/8" diameter electrical knockout in the left corner
post. Figure 22.
2. Continue to route wires into the control box.
3. Connect and wire nut the supply wires to provided
unit leads as shown in Figure 22.
4. Secure ground wire to (green) ground screw.
Figure 22: Line voltage wiring route to wire connections
All electrical connections should be checked for tightness as
they may come loose during shipment.
Line Voltage – 208-230, 460
Note: 460V units require a neutral conductor. See Figure 21.
1. Route line voltage supply wiring through the upper
1-1/8" diameter knockout in the left corner post.
1
2. Remove and discard the factory provided stripped
wire leads from the bottom unit contactor screw
terminals (not shown).
3. Connect the field supplied wires to the lower
contactor screw terminals as shown in Figure 21.
3
4. Twist neutral wires and wire nut (460V units only)
5. Connect ground wire to provided (green) ground screw
2
230 Volt Operation
All 208-230 volt single-phase and three-phase units
are factory wired for 208 volt operation. For 230 phase
operation, the line voltage tap on the 24 volt transformer
must be changed. Disconnect and cap the red lead
wire and interchange it with the orange lead wire on the
primary of the 24 volt transformer
IM 1139-8
4
22
www.DaikinApplied.com
Electrical Connections
GSH/GTH Unit With Non-Fused
Disconnect Switch
Line Voltage Electrical Connections
With Disconnect – 115-460V
Figure 23: Unit with optional non-fused disconnect switch
3/4" dia. Conduit
Connection
When units are equipped with the optional non-fused
disconnect switch, the line voltage supply is brought in
through the top of the junction box. Disconnect location
and dimension details are provided in Figure 23.
Note: *460V units require a neutral conductor. See #6
in Figure 24.
1. Remove screws from the top and bottom locations
on the disconnect switch cover.
2. These are the factory-installed wires from the switch
to the line voltage terminals in the unit control box.
3. Connect wires to the upper unused terminals.
4. Tighten terminal screws to secure wires.
Right-Hand Unit - Front View
5. Connect ground wire to provided green ground screw.
6. Twist and wire nut field provided neutral conductor.
Replace cover and secure with screws.
3/4" dia. Conduit
Connection
Figure 24: 460V wiring with neutral wire to the non-fused
disconnect switch
1
Left-Hand Unit - Front View
3
5
Table 14: Letter dimensions for Figure 23.
Unit Size
007, 009, 012
015, 019
024, 026, 030, 032
A
*6
16-1/4""
17-3/4"
036, 038, 042, 044
048, 049, 060, 064,
070, 072
4
B
1-1/2"
19-1/4"
2
1
www.DaikinApplied.com
23
IM 1139-8
Electrical Connections
Low Voltage Wire Connections
Figure 25: Low voltage wiring route & connections
Procedure
Note: 1. Never install relays coils in series with the thermostat inputs.
2. Units equipped with HGRH and using thermostat control require installation of a factory supplied return air sensor connected to H9 terminal.
See Figure 29 on page 25 for details.
1. Remove front access panel to allow access to the
control box.
3
2. Route the field-supplied low voltage wiring through
the lower knockout in the left corner post and into
the control box section as shown in Figure 25.
2
3. Secure the low voltage wire connections to the main
board terminals on TB2
3
4. Secure wire to TB1-1 on the I/O expansion module.
5. Reinstall the access panel after connections are
complete and wire terminals have been checked for
tightness.
2
4
Figure 26: Terminal connections to TB1 (sensor control) on the MTIII board
IM 1139-8
24
www.DaikinApplied.com
Electrical Connections
Typical Connections For
Thermostats & Temperature
Sensors Applications
Figure 29: Units that utilize thermostat control, a factory
supplied return air sensor connects to the H9 terminal.
Figure 27: Wiring example for two-stage thermostat with
electrical heat and hot gas reheat. (Y2 connection on
Microtech III controller should be used to achieve rated
capacity)
I/O Expansion
Module TB1
A
O
A
TB3
E
2
1
R
Y1 Y2 W1 W2
Y2
G
G
Y1
C
O
R
W2
MicroTech III Controller Terminals TB2
U
Yellow H9 terminal on MicroTech III controller
C
RC RH
G
Y
Y2 W1 W2 W3 W4
D/A
L
Figure 30: Return Air Temperature sensor (RAT) locations
Programmable Touch Screen (Part No. 910121750)
Note: Terminal TB1-1 is used for optional dehumidification or WSE operation.
Figure 28: Wiring example of typical heat/cool thermostat
connections (Part No.s 910121746 and 910121748)
MicroTech III Controller
Terminals TB1
O
A
G
A
1
R
Y2
G
W1 Y1 W2 Y2
Y1
C
O
R
W2
MicroTech III Controller
Terminals TB2
2
3
4
5
Suggested Location for RAT
Sensor (Ducted Applications)
(See Caution below)
Suggested Location for RAT Sensor (Non-ducted)
(See Caution below)
CAUTION
R
C
W1 Y1 W2 Y2
G
A
L
When an optional wall-mounted room temperature sensor is
connected to the unit controller, the Return Air Temperature
(RAT) sensor must not be installed. A wall-mounted room
temperature sensor and the return air temperature sensor
must not be connected simultaneously or the unit will not
operate properly.
O
Typical Heat/Cool Thermostat
(Part No. 910121746 & 910121748)
Note: When remote reset of a lockout condition is required at the wall thermostat, it will be necessary to
utilize a conductor between terminal "O" on the wall
thermostat to "TB1 terminal 4" on the MicroTech III
unit controller (non-programmable stat only).
www.DaikinApplied.com
25
Note: For single stage operation wire Y1 from thermostat
to Y2 terminal on the Microtech III control board.
IM 1139-8
Electrical Connections
Figure 31: Basic room sensor wiring
MicroTech III Controller Terminals TB1
1
1
2
2
3
3
4
4
Figure 33: Room sensor with temperature adjustment
wiring
MicroTech III Controller Terminals TB1
5
1
2
3
4
5
1
2
3
4
5
5
Basic Room Sensor (Part No.s 669529001, 910152149)
Room Sensor with Temperature Adjustment
(Part No. 669529101, 669529201, 910121753)
Figure 32: Example wiring of SmartSource MicroTech III
board to basic temperature sensor wiring
MicroTech III Controller Terminals TB1
1
2
3
4
5
1
2
3
4
5
Basic Room Sensor with Cool to Warm Adjustment
(Part No. 910171464)
IM 1139-8
26
www.DaikinApplied.com
Electrical Connections
Figure 34: Digitally adjustable room temperature sensor wiring
MicroTech III Controller
Terminals TB1
A
R
3
4
5
Y1 Y2 W1 W2
Y2
G
G
Y1
C
O
R
W2
MicroTech III Controller
Terminals TB2
R
1
2
O
A
1
6
E
2
3
4
MicroTech III Controller
Terminals TB3
5
E
U
U
Digitally Adjustable Room Temperature Sensor
(Part No. 910152147)
Figure 35: Digitally adjustable room temperature and humidity sensor wiring
A
1
R
O
A
W2
Y2
Y1 Y2 W1 W2
Y1
G
G
C
O
R
MicroTech III Controller
Terminals TB3
MicroTech III Controller
Terminals TB1
MicroTech III Controller
Terminals TB2
2
3
4
5
E
U
I/O Expansion Module
Terminals TB1
1
R
1
2
3
4
5
6
E
U
2
DH
Digitally Adjustable Room Temperature Sensor
(Part No. 910121754)
Note: Terminal TB1-1 is used for optional dehumidification operation.
www.DaikinApplied.com
27
IM 1139-8
Piping
Condensate Drain Connection
A field provided condensate trap must be installed on
each water source heat pump. Condensate removal
piping must be pitched away from the unit not less than
1/4" per foot. The vent should extend at least 1-1/4"
above the unit condensate fitting. A vent is required after
the trap so that the condensate will drain away from
the unit. The vent can also act as a clean out if the trap
becomes clogged. To avoid having waste gases entering
the building, the condensate drain should not be directly
piped to a drain/waste/vent stack. See local codes for
the correct application of condensate piping to drains
Figure 36: Unit condensate drain pipe trap detail
1-1⁄2" (38mm)
2. Do not locate any point in the drain system above
the condensate drain connection of any unit.
It may be necessary to manually fill the trap at system
startup, or to run the unit for sufficient time to build a
condensate seal. The condensate trap and condensate
piping drainage should be free of any foreign debris.
Debris can prevent proper drainage and unit operation
and result in condensate buildup.
Optional
Field- Installed Vent
1⁄4" Per Foot
(21mm Per Meter)
1-1⁄2"
(38mm)
Note: Improper trapping can lead to several problems. If the trap is too tall, negative pressure will
prevent drainage, causing condensate backup. If
the trap is too short the seal will be destroyed or
nonexistent, producing the same effect as a nontrapped system.
1. Each water source heat pump is provided with
a 3/4" FPT flush mount fitting for connection of
a condensate drain. A complete copper or PVC
condensate system can be used. Copper or steel
condensate piping should be insulated to prevent
sweating. In most applications the use of PVC
prevents sweating of condensate drain.
Figure 37: Unit condensate drain pipe detail with waterside
economizer option
Vent
Unit Drain
To building drain
Vent
Waterside
Economizer Drain
IM 1139-8
28
www.DaikinApplied.com
Piping
Cleaning & Flushing System
3. Shut off supplemental heater and circulator pump
and open all drains and vents to completely drain
down the system. Short circuited supply and return
runouts should now be connected to the conditioner
supply and return connections. Do not use sealers
at the swivel flare connections of hoses.
1. Prior to first operation of any conditioner, the water
circulating system must be cleaned and flushed of
all construction dirt and debris.
If the conditioners are equipped with water shutoff
valves, either electric or pressure operated, the
supply and return runouts must be connected
together at each conditioner location. This will
prevent the introduction of dirt into the unit. See
Figure 38.
4. Trisodium phosphate was formerly recommended
as a cleaning agent during flushing. However,
many states and localities ban the introduction of
phosphates into their sewage systems. The current
recommendation is to simply flush longer with warm
80°F (27°C) water.
Figure 38: Supply & return runouts connected together
Return Runout
Supply Runout
Mains
Flexible
Hose
Runouts Initially
Connected Together
2. Fill the system at the city water makeup connection
with all air vents open. After filling, close all air
vents.
The contractor should start main circulator with
the pressure reducing valve open. Check vents
in sequence to bleed off any trapped air, ensuring
circulation through all components of the system.
Power to the heat rejector unit should be off, and
the supplementary heat control set at 80°F (27°C).
While circulating water, the contractor should check
and repair any leaks in the piping. Drains at the
lowest point(s) in the system should be opened for
initial flush and blowdown, making sure city water
fill valves are set to make up water at the same
rate. Check the pressure gauge at pump suction
and manually adjust the makeup to hold the same
positive steady pressure both before and after
opening the drain valves. Flush should continue for
at least two hours, or longer if required, to see clear,
clean drain water.
www.DaikinApplied.com
29
5. Refill the system with clean water. Test the water
using litmus paper for acidity, and treat as required
to leave the water slightly alkaline (pH 7.5 to 8.5).
The specified percentage of antifreeze may also be
added at this time. Use commercial grade antifreeze
designed for HVAC systems only. Do not use
automotive grade antifreeze.
Once the system has been filled with clean water
and antifreeze (if used), precautions should
be taken to protect the system from dirty water
conditions. Dirty water will result in system wide
degradation of performance and solids may clog
valves, strainers, flow regulators, etc. Additionally,
the heat exchanger may become clogged which
reduces compressor service life or causes
premature failure.
6. Set the loop water controller heat add setpoint
to 70°F (21°C) and the heat rejection setpoint to
85°F (29°C). Supply power to all motors and start
the circulating pumps. After full flow has been
established through all components including the
heat rejector (regardless of season) and air vented
and loop temperatures stabilized, each of the
conditioners will be ready for check, test and startup, air balancing, and water balancing.
IM 1139-8
Controls
Table 15: MicroTech III SmartSource unit controller
terminals & descriptions
TB2 – 8
O
Thermostat – Heat Stage #3 (W3) Input
TB2 – 9
C
24 VAC Common
H1 – 1
24
24 VAC Power Input
TB3 – 1
E
Emergency Shutdown Input
H1 – 2
C
24 VAC common
TB3 – 2
U
Unoccupied Input
H2 – 1
SL1
Fan Main Required Output – Switched L1
L1 – 1
L1 - 1
Line Voltage Terminal 1
Blank Terminal
L1 – 2
L1 - 2
Line Voltage Terminal 2
Fan Main Required Output – Neutral
L1 – 3
L1 - 3
Line Voltage Terminal 3
H3 – 1 HP1-1 Comp High Pressure Switch (HP1) Input Terminal 1
N1
N1
Neutral Terminal 1
H3 – 2 HP1-2 Comp High Pressure Switch (HP1) Input Terminal 2
N2
N2
Neutral Terminal 2
N3
N3
Neutral Terminal 3
H2 – 2
H2 – 3
H4 – 1
N
1
Discharge Air Temp Sensor – Common
H4 – 2
Discharge Air Temp Sensor – Signal
H4 – 3
Leaving Water Temp Sensor – Common
H4 – 4
Leaving Water Temp Sensor – Signal
H5 – 1
1
I/O expansion module connectors/terminals
H1 – 1
H5 – 2
H1 – 3
H5 – 3
H1 – 4
H5 – 4
H1 – 5
H5 – 5
H1 – 6
H5 – 6
Connections to I/O Expansion Board
H5 – 7
1
H1 – 2
H1 – 8
H5 – 8
H1 – 9
H5 – 9
H1 – 10
H5 – 10
H1 – 11
H5 – 11
H1 – 12
H5 – 12
Connections to Main Board
H1 – 7
H2 – 1
1
Auxiliary Heat Stage #2 Output – N/O
Condensate Overflow Signal Input
H2 – 2
H6 – 2
Compressor Suction Temp Sensor (LT1) – Common
H2 – 3
H6 – 3
Compressor Suction Temp Sensor (LT1) – Signal
H3 – 1
H6 – 4
Compressor Low Pressure Switch (LP1) – Source Voltage
H3 – 2
Ext. 24 VAC Common In
H6 – 5
Compressor Low Pressure Switch (LP1) – Signal
H3 – 3
HGR / Waterside Economizer Output – N/O
H6 – 6
Reversing Valve – Common
H3 – 4
Ext. 24 VAC Common
H6 – 7
Reversing Valve – Output
H3 – 5
ECM Fan Motor Variable Speed Signal Output
No Connection
H3 – 6
H7 – 2
No Connection
H4 – 1
H7 – 3
Red LED Output
H4 – 2
H7 – 4
Green LED Output
H5 – 1
H7 – 5
Yellow LED Output
H5 – 2
No Connection
H7 – 6
Red-Green-Yellow LED Common
H5 – 3
Red LED Output
Isolation Valve/Pump Request Relay N/O
H5 – 4
Green LED Output
H8 – 2
Isolation Valve/Pump Request Relay N/C
H5 – 5
Yellow LED Output
H8 – 3
24 VAC Common
H5 – 6
Red-Green-Yellow LED Common
Return Air Sensor – Signal
H6 – 1 HP2-1 Jumper Wire Connection
H6 – 1
H7 – 1
H8 – 1
H9 – 1
1
1
1
1
H9 – 2
No Connection
24 VAC Common
1
Ext. 24 VAC In
ECM Fan Motor Variable Speed Signal – Common
1
Entering Water Temp Sensor – Signal
Entering Water Temp Sensor – Common
1
No Connection
Return Air Sensor – Common
H6 – 2 HP2-2 Jumper Wire Connection
TB1 – 1
1
Room Sensor – Status LED Output
H7 – 1
Fan Speed Table Row Select – Signal
TB1 – 2
2
Room Sensor – Fan Mode & Unit Mode Switches
H7 – 2
Fan Speed Table Row Select – Common
TB1 – 3
3
Room Sensor – Setpoint Adjust Potentiometer
H7 – 3
Thermostat – Heat Stage #4 (W4) Input – Signal
TB1 – 4
4
Room Sensor – Room Temp Sensor & Tenant Override
H7 – 4
TB1 – 5
5
Room Sensor – DC Signal Common
H8 – 1
TB2 – 1
R
24 VAC
H8 – 2
24 VAC Common
TB2 – 2
A
Thermostat – Alarm Output
H8 – 3
No Connection
TB2 – 3
W2
Thermostat – Heat Stage #2 (W2) Input
H8 – 4
Auxiliary Heat Stage #1 / Hydronic Heat Output N/O (24 VAC)
TB2 – 4
W1
Thermostat – Heat Stage #1 (W1) Input
H8 – 5
24 VAC Common
TB2 – 5
Y2
Thermostat – Cool Stage #2 (Y2) Input
TB1 – 1
1
Humidistat Signal Input
TB2 – 6
Y1
Thermostat – Cool Stage #1 (Y1) Input
TB1 – 2
2
Thermostat - Heat Stage #4 (W4) Input – Signal
TB2 – 7
G
Thermostat – Fan Input
IM 1139-8
30
Auxiliary 24 VAC Out
1
Compressor – High Capacity Output – N/O
www.DaikinApplied.com
Controls
Figure 39: MicroTech SmartSource unit controller & I/O expansion module
Note: Refer to Table 15 on page 30 for terminal descriptions
www.DaikinApplied.com
31
IM 1139-8
Controls
Jumper Configuration Settings
WARNING
Figure 40: Configuration jumpers location
Proper antifreeze/water solution is required to minimize the
potential of fluid freeze-up. Jumper JP3 is factory set for water
freeze protection with the jumper open. Operation at fluid
temperatures below 32°F with anti-freeze protection requires JP3
to be field configured for the jumper closed. If unit is employing
a fresh water system (no anti-freeze protection), it is extremely
important that JP3 jumper setting remains in the open position
(factory default setting) in order to shut down the unit at the
appropriate water temperature to protect your heat pump from
freezing. Failure to do so can result in unit damage, property
damage and will void unit warranty.
Table 16: Jumper settings and descriptions
Jumper
Description
JP1
Mode
JP2
Fan operation
JP3
(See Warning)
Freeze Protection
JP4
Freeze Fault Protection
JP5
Set point adjustment range only applies to network controls with a room temperature sensor
JP6
Room control type
JP7
Compressor heating source
JP8
I/O expansion module
Options
Open for normal operation mode
Shorted for service/test operation mode
Open for continuous fan operation, when not in unoccupied mode.
Shorted for cycling fan operation
Open for water freeze protection
Shorted for systems with anti-freeze protection (15°F (9°C)
Open for none
Shorted to enable freeze fault protection based on Leaving Water Temperature (LWT)
Open for adjustment range of -5.0° to +5.0° F
Shorted for 55° to 95° F adjustment range
Open for thermostatic room control
Shorted for room temperature sensor control, MicroTech III only.
Open to enable compressor heating
Shorted to disable compressor heating
Open when I/O expansion module is not needed
Shorted when I/O expansion module is required
Table 17: I/O expansion module jumper settings
I/O Expansion Description
Fan Row Select for Operating Modes:
▪ Fan Only
▪ Hydronic Heating
▪ Waterside Economizer
Jumper(s)
JP1 & JP2
Setting
Fan Row #1 Selected
JP1 = Shorted
JP2 = Open
Fan Row #2 Selected
JP1 = Open
JP2 = Shorted
Fan Row #3 Selected
JP1 = Shorted
JP2 = Shorted
Fan Row #4 Selected
JP3 = Open
JP4 = Open
Secondary Heating Options
JP3 & JP4
JP5 & JP6
Supplemental Electric Heat
JP3 = Open
JP4 = Shorted
Boilerless Electric Heat
JP3 = Shorted
JP4 = Shorted
Hydronic Heat
Hot Gas/Water Reheat (HGR)
JP5 = Open
JP6 = Shorted
Waterside Economizer
JP7
JP7 = Open
Compressor Capacity Option
JP8
JP8 = Open
JP8 = Shorted
32
None
JP5 = Shorted
JP6 = Open
Not Used
IM 1139-8
None
JP3 = Shorted
JP4 = Open
JP5 = Open
JP6 = Open
Dehumidification Options / Waterside Economizer
Model
JP1 = Open
JP2 = Open
–
Single-Stage Capacity
Dual-Stage Capacity
www.DaikinApplied.com
Controls
MicroTech® III SmartSource Unit
Controller
Table 18: MicroTech III SmartSource unit controller fault &
status LED's
The MicroTech III SmartSource unit controller allows
thermostat, Daikin sensor and DDC standalone operation.
The R (24VAC) terminal is used to operate thermostat
inputs G, Y1, Y2, W1, W2, W3, W4 and TB1-1. The C
(0VAC) terminal is used to control inputs U, E and O.
No external power sources may be used to operate
the MicroTech III controller. All units must be properly
grounded per local code requirements.
NOTICE
For information on sequence of operation and troubleshooting refer to OM 1149-xx.
Remote Reset of Automatic Lockouts
The Remote Reset feature provides the means to
remotely reset automatic lockouts. There are (3) means
to reset an automatic lockout condition:
• Using the thermostat create 2 demands for capacity
within 30 seconds
•
Press the Room Sensor or Thermostat Timed
Override/Reset Button for more than 10 seconds
•
Turn the unit power off
Type
Yellow
Green
Red
I/O Expansion Communication Fail
Invalid Configuration
Fault
ON
Flash
Flash
Fault
Flash
Flash
OFF
Low Voltage Brownout
Fault
OFF
Flash
OFF
Emergency Shutdown
Mode
OFF
Flash
OFF
Compressor High Pressure
Fault
OFF
OFF
Flash
Compressor Low Pressure
Fault
OFF
OFF
ON
Compressor Suction Temp Sensor
Fail
Fault
Flash
Flash
ON
Compressor Low Suction Temp
Fault
Flash
OFF
OFF
Freeze Fault Detect
Fault
Flash
OFF
Flash
Room Temp Sensor Fail (Room
Sensor Control Only)
Fault
Flash
Flash
ON
Leaving Water Temp Sensor Fail
Fault
Flash
Flash
ON
Condensate Overflow
Fault
ON
OFF
OFF
Serial EEPROM Corrupted
Fault
ON
ON
ON
Waterside Economizer Low Temp
Cutout (WSE Control & Call for
Cooling)
Mode
Flash
ON
Flash
Service Test Mode Enabled
Mode
Flash
Flash
Flash
Unoccupied Mode
Mode
ON
ON
OFF
Occupied, Bypass, Standby, or
Tenant Override Modes
Mode
OFF
ON
OFF
Note: Mode/faults are listed in order of priority.
When the cause of the fault condition has been cleared,
and the unit transitions from not requiring any capacity
to needing any capacity twice within 30 seconds
(accomplished by user manipulation of the Heat/Cool/
Auto/Off switch on the thermostat), an alarm reset
equivalent to a tenant override button reset is generated.
The intelligent reset counter and the 24 hour timer are
cleared when this type of alarm reset is generated.
Note: This feature only applies to thermostat controlled
systems.
For room sensor controlled units, pressing the “Override”
or “Reset” button for more than 10 seconds will apply a
ground signal to the tenant override in(screw terminal
connection at TB1 pin 4) will clear the lockout alarm
once the cause of the fault condition has been cleared.
A unit power cycle can also be used to clear an
automatic lockout if the conditions causing the fault have
been cleared.
www.DaikinApplied.com
Description
33
Table 19: I/O expansion module fault & status LED's
Description
Type
Yellow
Green
Red
Baseboard Communication Fail
Fault
Flash
OFF
Flash
Entering Water Temp Sensor
Fail
(Boilerless Electric Heat or
Waterside Economizer Only or
Hydronic Heat)
Fault
ON
OFF
Flash
Low Entering Water
Temperature
(No Display On Boilerless
Electric Heat)
Fault
OFF
ON
Flash
Fan is OFF
Mode
OFF
ON
OFF
Fan Running at Low Speed (0
to 33%) Duty Cycle
Mode
OFF
Flash
OFF
Fan Running at Medium Speed
(34 to 66%) Duty Cycle
Mode
ON
Flash
OFF
Fan Running at High Speed (67
to 100%) Duty Cycle
Mode
Flash
Flash
OFF
IM 1139-8
Controls
Table 20: Fault recovery and reset
Auto
Recovery
Tenant
Override
Button
Reset
Network
Reset
Yes
No
No
Invalid Configuration
No
No
No
Low Voltage Brownout
Yes
No
Yes
All Sensor Failures
No
No
Yes
Compressor High Pressure
No
Yes
Yes
Compressor Low Pressure
No
Yes
Yes
Compressor Low Suction Temp or
Freeze Fault Detect (Heating and Cooling Modes)
Yes1
Yes
Yes
Compressor Low Suction Temp or
Freeze Fault Detect
(Dehumidification Mode)
Yes
Yes
Yes
Condensate Overflow
Yes
No
Yes
Low Entering Water Temp
Yes
No
No
Serial EEPROM Corrupted
No
No
No
Waterside Economizer Low Temp Cutout
Yes
No
No
Fault Description
I/O Expansion
Communication Fail
Note:
1
MicroTech SmartSource Controller
with BACnet® Communication
Module
For installation and operation information on MicroTech
III SmartSource unit controller and other ancillary
components, see:
•
IM 928 - MicroTech III BACnet Communication
Module
•
OM 931 - MicroTech III SmartSource Unit Controller
for Water Source Heat Pumps Operation and
Maintenance Manual
•
IM 955 - MicroTech III Wall Sensor For use with
MicroTech III SmartSource Unit Controller
Figure 42: MicroTech III BACnet water source heat pump
snap-in communication module
Indicates auto recover is subject to intelligent alarm reset.
Alarm auto recovers on first two occurrences, locked out on
third within 24 hour period.
See "Intelligent Alarm Reset" on page 32 for further details.
MicroTech SmartSource Controller
with LonWorks® Communication
Module
For installation and operation information on LonWorks
Communication Module and other ancillary control
components, see:
• IM 927 - MicroTech III Water Source Heat Pump
LonWorks Communication Module
•
IM 933 - LonMaker Integration Plug-in Tool: For use
with the MicroTech III SmartSource Unit Controller
•
IM 955 - MicroTech III Wall Sensor for use with
MicroTech III SmartSource Unit Controller
Figure 41: LonWorks communication module
IM 1139-8
34
www.DaikinApplied.com
Controls
Constant Torque EC Motor
Table 21: Constant torque EC motor CFM values
Unit
Size
Setting
Function
.15
.20
.25
.30
.35
.40
.45
.50
.55
.60
.65
368
352
336
320
304
288
272
256
240
224
206
188
341
324
306
289
271
253
235
217
198
180
162
145
312
294
275
256
236
216
195
174
152
Setting 1 (Low)
312
294
275
256
236
216
195
174
152
Setting 4 (High)
394
378
363
348
333
319
304
290
276
262
244
Setting 3 (Standard)
368
352
336
320
304
288
272
256
240
Setting 4 (High)
Setting 3 (Standard)
Setting 2 (Medium)
007
Setting 2 (Medium)
Stage 2
341
324
306
289
271
253
235
217
198
312
294
275
256
236
216
195
174
152
Setting 4 (High)
312
294
275
256
236
216
195
174
152
Setting 3 (Standard)
312
294
275
256
236
216
195
174
152
264
244
222
199
176
151
125
98
Fan Only
Setting 1 (Low)
264
244
222
199
176
151
125
98
408
393
378
364
349
335
321
308
294
281
Setting 3 (Standard)
372
356
340
324
308
292
276
261
245
229
211
Stage 1
.70
145
Setting 4 (High)
Setting 2 (Medium)
264
246
337
320
302
284
266
248
230
Setting 1 (Low)
337
320
302
284
266
248
230
211
Setting 4 (High)
437
423
409
395
382
368
355
342
330
317
301
285
Setting 3 (Standard)
408
393
378
364
349
335
321
308
294
281
264
246
245
229
309
294
Setting 2 (Medium)
Stage 2
372
356
340
324
308
292
276
261
Setting 1 (Low)
337
320
302
284
266
248
230
211
Setting 4 (High)
337
320
302
284
266
248
230
211
192
Setting 3 (Standard)
337
320
302
284
266
248
230
211
192
278
258
237
215
193
169
145
120
Setting 1 (Low)
278
258
237
215
193
169
145
120
Setting 4 (High)
459
445
431
417
404
390
377
364
351
339
324
428
413
399
385
371
358
345
331
319
306
290
394
378
363
348
333
319
304
290
Setting 2 (Medium)
Setting 3 (Standard)
Setting 2 (Medium)
012
Stage 1
Setting 1 (Low)
Setting 2 (Medium)
009
External Static Pressure (inches of water column)
.10
Fan Only
Stage 1
Setting 1 (Low)
394
378
363
348
333
319
304
290
Setting 4 (High)
486
473
459
445
431
417
402
388
374
359
348
337
326
Setting 3 (Standard)
459
445
431
417
404
390
377
364
351
339
324
309
294
428
413
399
385
371
358
345
331
319
306
290
Setting 1 (Low)
394
378
363
348
333
319
304
290
Setting 4 (High)
394
378
363
348
333
319
304
290
276
262
244
226
Setting 3 (Standard)
394
378
363
348
333
319
304
290
276
262
244
226
337
320
302
284
266
248
230
211
192
173
155
337
320
302
284
266
248
230
211
192
173
155
Setting 2 (Medium)
Setting 2 (Medium)
Setting 1 (Low)
Stage 2
Fan Only
Note: Gray tinted areas, outside recommended operating range.
www.DaikinApplied.com
35
IM 1139-8
Controls
Constant CFM Type EC Motor Fan Settings
Table 22: Single stage units with constant CFM type EC motor
Unit
Size
015
019
024/026
030/032
036/038
042/044
048/049
060/064
070/072
Notes:
Setting
Maximum
ESP
(in. wg.)2
1Low
CFM
Heat
1High
CFM
Heat
1Low
CFM
Cool
1High
CFM
Cool
Fan
Only
Dehumidification
Electric
Heat
Setting 4 (High)
.70
500
560
500
560
375
375
560
Setting 3 (Standard)
.70
440
500
440
500
375
375
560
Setting 2 (Medium)
.70
375
440
375
440
280
375
560
Setting 1 (Low)
.70
375
375
375
375
280
375
560
Setting 4 (High)
.70
600
675
600
675
450
450
675
Setting 3 (Standard)
.70
525
600
525
600
450
450
675
Setting 2 (Medium)
.70
450
525
450
525
340
450
675
Setting 1 (Low)
.70
450
450
450
450
340
450
675
Setting 4 (High)
.70
800
900
800
900
600
600
900
Setting 3 (Standard)
.70
700
800
700
800
600
600
900
Setting 2 (Medium)
.70
600
700
600
700
450
600
900
Setting 1 (Low)
.70
600
600
600
600
450
600
900
Setting 4 (High)
.70
1000
1125
1000
1125
750
750
1125
Setting 3 (Standard)
.70
875
1000
875
1000
750
750
1125
Setting 2 (Medium)
.70
750
875
750
875
560
750
1125
Setting 1 (Low)
.70
750
750
750
750
560
750
1125
Setting 4 (High)
.70
1250
1400
1250
1400
940
938
1400
Setting 3 (Standard)
.70
1090
1250
1090
1250
940
938
1400
Setting 2 (Medium)
.70
940
1090
940
1090
700
938
1400
Setting 1 (Low)
.70
940
940
940
940
700
938
1400
Setting 4 (High)
.70
1400
1575
1400
1575
1050
1050
1575
Setting 3 (Standard)
.70
1225
1400
1225
1400
1050
1050
1575
Setting 2 (Medium)
.70
1050
1225
1050
1225
785
1050
1575
Setting 1 (Low)
.70
1050
1050
1050
1050
785
1050
1575
Setting 4 (High)
.70
1600
1800
1600
1800
1200
1200
1800
Setting 3 (Standard)
.70
1400
1600
1400
1600
1200
1200
1800
Setting 2 (Medium)
.70
1200
1400
1200
1400
900
1200
1800
Setting 1 (Low)
.70
1200
1200
1200
1200
900
1200
1800
Setting 4 (High)
.70
2000
2250
2000
2250
1500
1500
2250
Setting 3 (Standard)
.70
1750
2000
1750
2000
1500
1500
2250
Setting 2 (Medium)
.70
1500
1750
1500
1750
1120
1500
2250
Setting 1 (Low)
.70
1500
1500
1500
1500
1120
1500
2250
Setting 4 (High)
.70
2160
2400
2160
2400
1710
1710
2400
Setting 3 (Standard)
.70
1920
2160
1920
2160
1710
1710
2400
Setting 2 (Medium)
.70
1710
1920
1710
1920
1330
1710
2400
Setting 1 (Low)
.70
1710
1710
1710
1710
1330
1710
2400
1. The unit is capable of high-low fan performance through the use of a 2-stage thermostat wired to specific
terminals for High-Low CFM fan performance. Standard operation with a 1-stage thermostat is indicated as
High CFM fan performance.
2. Applications up to 1.0" ESP (in. wg.) are possible. However, increased fan noise should be anticipated and
appropriate noise attenuation should be considered.
IM 1139-8
36
www.DaikinApplied.com
Controls
Fan Performance For Constant
CFM EC Motor (Sizes 015–072)
Table 24: I/O expansion module jumper configuration
I/O Expansion board configuration
Table 23: Fan settings and performance
Unit
Size
015
019
024/026
030/032
036/038
042/044
048/049
060/064
070/072
Setting
Fan Only
Hydronic
Heat
Waterside
Economizer
A
500
500
500
B
440
440
440
C
375
375
375
D
280
280
375
A
600
600
600
B
525
525
525
C
450
450
450
D
340
340
450
A
800
800
800
B
700
700
700
C
600
600
600
D
450
450
600
A
1000
1000
1000
B
875
875
875
C
750
750
750
D
560
560
750
A
1250
1250
1250
B
1090
1090
1090
C
940
940
940
D
700
700
940
A
1400
1400
1400
B
1225
1225
1225
C
1050
1050
1050
D
785
785
785
A
1600
1600
1600
B
1400
1400
1400
C
1200
1200
1200
D
900
900
1200
A
2000
2000
2000
B
1750
1750
1750
C
1500
1500
1500
D
1120
1120
1500
A
2160
2160
2160
B
1920
1920
1920
C
1710
1710
1710
D
1330
1330
1710
www.DaikinApplied.com
Setting
JP1
JP2
A
Open
Open
B
Shorted
Open
C
Open
Shorted
D
Shorted
Shorted
Figure 43: JP1 & JP2 location on the I/O expansion module
JP1
JP2
37
IM 1139-8
Controls
Fan Speed Selector Switch
Figure 44: 4-position fan speed selector switch
A 4-position fan speed selector switch located in the
control box allows CFM settings to be field adjustable.
Fan speed control optimizes unit fan speed based on
thermostat/room sensor inputs. The fan speed switch
allows for manually setting an optimal fan speed specific
to the application requirements. Each position on the
fan speed switch represents settings 1-4. See Table 25
below for the complete list of fan speed selector switch
settngs.
Fan CFM Settings & Performance
Table 25: 2-Stage units with constant cfm type EC motor
Unit
Size
024, 026
030, 032
036, 038
042, 044
048, 049
060, 064
070, 072
Setting
Maximum
ESP
(in. wg.)
Part Load
Stage 1
Heat
Full Load
Stage 2
Heat
Part Load
Stage 1
Cool
Full Load
Stage 2
Cool
Fan
Only
Dehumidification
Electric
Heat
Setting 4 (High)
.70
800
900
800
900
600
600
900
Setting 3 (Standard)
.70
700
800
700
800
600
600
900
Setting 2 (Medium)
.70
600
700
600
700
450
600
900
Setting 1 (Low)
.70
600
600
600
600
450
600
900
Setting 4 (High)
.70
1000
1125
1000
1125
750
750
1125
Setting 3 (Standard)
.70
875
1000
875
1000
750
750
1125
Setting 2 (Medium)
.70
750
875
750
875
560
750
1125
Setting 1 (Low)
.70
750
750
750
750
560
750
1125
Setting 4 (High)
.70
1250
1400
1250
1400
940
938
1400
Setting 3 (Standard)
.70
1090
1250
1090
1250
940
938
1400
Setting 2 (Medium)
.70
940
1090
940
1090
700
938
1400
Setting 1 (Low)
.70
940
940
940
940
700
938
1400
Setting 4 (High)
.70
1400
1575
1400
1575
1050
1050
1575
Setting 3 (Standard)
.70
1225
1400
1225
1400
1050
1050
1575
Setting 2 (Medium)
.70
1050
1225
1050
1225
785
1050
1575
Setting 1 (Low)
.70
1050
1050
1050
1050
785
1050
1575
Setting 4 (High)
.70
1600
1800
1600
1800
1200
1200
1800
Setting 3 (Standard)
.70
1400
1600
1400
1600
1200
1200
1800
Setting 2 (Medium)
.70
1200
1400
1200
1400
900
1200
1800
Setting 1 (Low)
.70
1200
1200
1200
1200
900
1200
1800
Setting 4 (High)
.70
2000
2250
2000
2250
1500
1500
2250
Setting 3 (Standard)
.70
1750
2000
1750
2000
1500
1500
2250
Setting 2 (Medium)
.70
1500
1750
1500
1750
1120
1500
2250
Setting 1 (Low)
.70
1500
1500
1500
1500
1120
1500
2250
Setting 4 (High)
.70
2400
2700
2160
2400
1800
1710
2400
Setting 3 (Standard)
.70
2100
2400
1920
2160
1800
1710
2400
Setting 2 (Medium)
.70
1800
2100
1710
1920
1340
1710
2400
Setting 1 (Low)
.70
1800
1800
1710
1710
1340
1710
2400
Note: Applications up to 1.0" ESP (in. wg.) are possible. However, increased fan noise should be anticipated and appropriate noise attenuation
should be considered.
IM 1139-8
38
www.DaikinApplied.com
Start-up
Information for Initial Start-up
†† Set thermostat to “Heat.” If the thermostat is the
automatic changeover type, set system switch to
the “Auto” position and depress the heat setting
to the warmest selection. Some units have built-in
time delays which prevent the compressor from
immediately starting. With most control schemes,
the fan will start immediately. After a few minutes of
compressor operation, check for warm air delivery
at discharge grille. If this is a “cold building” start-up,
leave unit running until return air to the unit is at least
65°F (18°C).
Measure the temperature difference between
entering and leaving air and entering and leaving
water. With entering water of 60°F to 80°F (16°C to
27°C), leaving water should be 6°F to 12°F (3.3°C to
6.6°C) cooler, and the air temperature rise through
the machine should not exceed 35°F (19°C). If the
air temperature exceeds 35°F (19°C), then the water
flow rate is inadequate.
CAUTION
Units must be checked for water leaks upon initial water system
start-up. Water leaks may be a result of mishandling or damage
during shipping. Failure by the installing contractor to check for
leaks upon start-up of the water system could result in property
damage.
Check, Test & Start Procedure
NOTICE
Complete the "Water Source Heat Pump Equipment Check, Test
and Start Form" on page 38.
Check As Completed:
†† Open all valves to full open position and turn on
power to the unit.
†† Set thermostat for “Fan Only” operation by selecting
“Off” at the system switch and “On” at the fan switch.
If “Auto” fan operation is selected, the fan will cycle
with the compressor. Check for proper air delivery.
†† Set thermostat to “Cool.” If the thermostat is an
automatic changeover type, simply set the cooling
temperature to the coolest position. On manual
changeover types additionally select “Cool” at the
system switch.
Again, many units have time delays which protect
the compressor(s) against short cycling. After a few
minutes of operation, check the discharge grilles for
cool air delivery. To insure proper water flow, measure
the temperature difference between entering and
leaving water. The temperature differential should be
10°F to 14°F (5°C to 8°C) for units in cooling mode. It
should be approximately 1½ times greater than the
heating mode temperature difference. For example,
if the cooling temperature difference is 15°F (8°C),
the heating temperature difference should have been
10°F (5°C).
Without automatic flow control valves, target a
cooling temperature difference of 10°F to 14°F (5°C
to 8°C). Adjust the combination shutoff/balancing
valve in the return line to a water flow rate which will
result in the 10˚F to 14°F (5°C to 8°C) difference
www.DaikinApplied.com
39
†† Check the elevation and cleanliness of the
condensate line. If the air is too dry for sufficient
dehumidification, slowly pour enough water into the
condensate pan to ensure proper drainage.
†† If the unit does not operate, check the following
points:
a. Is supply voltage to the machine compatible?
b. Is thermostat type appropriate?
c. Is thermostat wiring correct?
†† If the unit operates but stops after a brief period:
a. Is there proper airflow? Check for dirty filter, incorrect fan rotation (3-phase fan motors only), or incorrect ductwork.
b. Is there proper water flow rate within temperature limits? Check water balancing; back
flush unit if dirt-clogged.
†† Check for vibrating refrigerant piping, fan wheels, etc.
IM 1139-8
Typical Wiring Diagrams
MicroTech III Unit Control with BACnet Communication Module (HGRH) 265-277V, 1-Phase
See service & disconnect portion of wiring diagram on page 49.
IM 1139-8
40
www.DaikinApplied.com
Typical Wiring Diagrams
MicroTech III Unit Control with BACnet Communication Module (WSE &
DSH) - 208-230V, 1-Phase with 115V Loop Pumps and 20kW Electric Heat
See service & disconnect portion of wiring diagram on page 50.
www.DaikinApplied.com
41
IM 1139-8
Typical Wiring Diagrams
MicroTech III Unit Control with LonWorks Communication Module
208-230V, 3-Phase with 230V Loop Pumps and 5kW Electric Heat
See service & disconnect portion of wiring diagram on page 51.
IM 1139-8
42
www.DaikinApplied.com
Typical Wiring Diagrams
MicroTech III Unit Control with BACnet Communication Module (WSE)
460V, 3-Phase with 230V Loop Pumps and 20kW Electric Heat
See service & disconnect portion of wiring diagram on page 52.
www.DaikinApplied.com
43
IM 1139-8
Typical Wiring Diagrams
MicroTech III Unit Control with Hydronic Heat (HYH) – 208-230V
MicroTech III
Unit Controller
I/O Expansion
Module
Hydronic
Heat
HYH
IM 1139-8
44
www.DaikinApplied.com
Maintenance
Motor Removal
Figure 46: Disassemble motor orifice ring & motor mount screws from fan housing
When reinstalling motor
locate plug on motor down
3 The fan wheel is
removed from the motor
shaft by loosening the
set screw
Torque screws for motor
mount brackets to fan
housing at 42 ± 3 in lbs.
When reinstalling the
fan wheel center it
inside the fan housing
2 Remove four (4)
bolts securing motor
to orifice ring
Fan housing
Fan wheel
Motor mount orifice ring
1 Remove four (4) screws securing orifice ring and motor assembly to fan housing
Motor
www.DaikinApplied.com
45
IM 1139-8
Troubleshooting
Typical Refrigeration Cycles
Figure 47: Cooling mode
Thermal
Expansion
Valve
Return Air
Co-Axial Heat
Exchanger
Water In
Coil – Air to Refrigerant
Heat Exchanger
Water Out
Sensing Bulb and
Capillary Tube
Compressor
Blower
Reversing Valve
Conditioned Air – (Cooling)
Cooling Refrigeration Cycle
When the wall thermostat is calling for COOLING, the reversing valve is energized and directs the flow of the
refrigerant (hot gas) leaving the compressor to the water-to-refrigerant heat exchanger. Here the heat is removed by
the water and the hot gas condenses to become a liquid. The liquid then flows through a thermal expansion valve
(TXV) and then to the air-to-refrigerant heat exchanger coil. The liquid then evaporates becoming a gas, at the same
time absorbing heat and cooling the air passing over the surfaces of the coil. The refrigerant then flows as a low
pressure gas through the reversing valve and back to the suction side of the compressor to complete the cycle.
Figure 48: Heating mode
Thermal
Expansion
Valve
Return Air
Co-Axial Heat
Exchanger
Water In
Coil – Air to Refrigerant
Heat Exchanger
Water Out
Sensing Bulb
and Capillary
Tube
Compressor
Blower
Reversing Valve
Conditioned Air – (Heating)
Heating Refrigeration Cycle
When the wall thermostat is calling for HEATING, the reversing valve is energized and directs the flow of the
refrigerant (hot gas) leaving the compressor to the air-to-refrigerant heat exchanger coil. Here the heat is removed
by the air passing over the surfaces of the coil and the hot gas condenses to become a liquid. The liquid then flows
through a thermal expansion valve (TXV) then to the water-to-refrigerant heat exchanger. The liquid then evaporates
becoming a gas, at the same time absorbing heat and cooling the water. The refrigerant then flows as a low pressure
gas through the reversing valve and back to the suction side of the compressor to complete the cycle.
IM 1139-8
46
www.DaikinApplied.com

Unit Check / Equipment Data
Installation Data
Job Name____________________________________________________ Check Test Date:___________________________
City ___________________________________________________________ State________________ Zip_______________
Daikin Model #_______________________________________________________
Daikin Serial #________________________________________ Job site Unit ID # (HP #)______________________________
General Contractor:______________________________________ Mechanical Contractor:______________________________
Technician Performing Start-Up: Name_______________________________ Employer:______________________________
Complete equipment data from measurements taken at the locations indicated on the drawing below.
Equipment Data
Flow Rate
EWP - LWP = ∆P
1 EWP - PSI In__________________minus
2 LWP - PSI Out___________ equals ∆P_____________
The first step in finding GPM is to subtract leaving water pressure from entering water pressure. The difference between the two
is referred to as ∆P. ∆P can be converted to GPM by looking in the equipment specification catalog. Caution ∆P ≠ GPM
Note: A conversion table must be used to find GPM from (Delta) ∆P measurements.
Loop Fluid Temperature Rise / Drop through Coaxial Heat Exchanger EWT - LWT = ∆T
4 LWT - °F Out___________________ equals Fluid ∆T________________
3 EWT - °F Out__________________ minus
∆T is the rise or drop in the fluid temperature as it passes through the Coaxial.
Air Temperature Rise / Drop through the air coil
∆T x CFM x 1.08 = BTUH Sensible
6 LAT - °F Out____________________ equals Air ∆T__________________
5 EAT - °F In____________________ minus
Note: Perform Check, Test and Start-Up in the Cooling Mode Only.
EWT - Entering Water Temperature
EWP - Entering Water Pressure
EAT - Entering Air Temperature
∆- Delta (Differential)
LWT - Leaving Water Temperature
LWP - Leaving Water Pressure
LAT - Leaving Air Temperature
CFM - Cubic Feet/Minute
BTUH - British Thermal Units/Hour
Check, Test & Start
LAT
V
Discharge
Hot Gas
V
C
O
I
L
Reversing Valve
6
V
V
EAT
Air Temperature °F
OUT
V
5
A
I
R
Suction
COAX
Expansion
Valve
Compressor
Loop Fluid Pressure (In PSI)
EWP
1
Loop Fluid Temperature °F
EWT
3
V
IN
IN
OUT
V
2
LWP
4
LWT
Form No._____________________________
www.DaikinApplied.com
47
IM 1139-8
Operating Limits
Environment
extremes in temperature and/or humidity, and equipment
performance, reliability, and service life may be
adversely affected.
This equipment is designed for indoor installation
only. Sheltered locations such as attics, garages, etc.,
generally will not provide sufficient protection against
Table 26: Air limits in °F (°C)
Standard Range Units
Air Limits
Minimum Ambient
Air1
Extended Range (Geothermal) Units
Cooling (DB/WB)
Heating
Cooling (DB/WB)
Heating
50°F (10°C)
50°F (10°C)
40°F (4°C)
40°F (4°C)
Maximum Ambient Air2
100°F/77°F (38°C/25°C)
85°F (29°C)
100°F/77°F (38°C/25°C)
85°F (29°C)
Minimum Entering Air1
65°F/55°F (18°C/13°C)
50°F (10°C)
65°F/55°F (18°C/13°C)
50°F (10°C)
Common Design Entering Air
75°F/63°F (24°C/17°C)
70°F (21°C)
75°F/63°F (24°C/17°C)
70°F (21°C)
85°F/71°F (29°C/22°C)
80°F (27°C)
85°F/71°F (29°C/22°C)
80°F (27°C)
Maximum Entering
Air2
Table 27: Fluid limits
Fluid Limits
Standard Range Units
Extended Range (Geothermal) Units
Cooling
Heating
Cooling
Heating
Minimum Entering Fluid
55°F (13°C)
55°F (13°C)
30°F (-1°C)
20°F (-6°C)
Common Design Entering
Fluid
85-90°F (29-32°C)
70°F (21°C)
90°F (32°C)
35-60°F (1.5-16°C)
Maximum Entering Fluid
120°F (43°C)
90°F (32°C)
120°F (43°C)
90°F (32°C)
Minimum GPM/Ton
1.5
Nominal GPM/Ton
3.0
Maximum GPM/Ton
4.0
Notes: 1. Maximum and minimum values may not be combined. If one value is at maximum or minimum, the other two conditions may not exceed
the normal condition for standard units. Extended range units may combine any two maximum conditions, but not more than two, with all
other conditions being normal conditions.
2. This is not a normal or continuous operating condition. It is assumed that such a start-up is for the purpose of bringing the building space
up to occupancy temperature.
Motorized Isolation Valve
The motorized valve kit is available as a factory-installed
and wired option or may be ordered as a field-installed
accessory.
Wired as shown in Figure 45, the motorized valve will open
on a call for compressor operation.
The motorized isolation valve actuator (ISO) has both a
24V power connection and a 24V end switch connection.
Install the supplied wire harness into plug H8 on the
main control board. Run wires between the ISO actuator
and the supplied wire harness ends.
Connect N.O. & N.C. actuators as shown on the
schematic. The end switch should be wired in series with
the 24V compressor signal wire. Connect the end switch
wires as shown in the schematic. The end switch will
close when the valve is fully open.
Note: For detailed installation instructions for the fieldinstalled motorized valve, refer to IM 1151.
Figure 45: Motorized valve wiring
IM 1139-8
48
www.DaikinApplied.com
Typical Wiring Diagrams
MicroTech III Unit Control with BACnet Communication Module (HGRH)265-277V, 1-Phase, Service & Disconnect
HP1,2
HUM
ISO
LAT
LP1,2
LT1,2
LWT
M01-04
M11-1
M70, 71
MCB
NCB
OLP
PL1,2
R15
R20
RAT
RV1,2
TB1
TB2
TB3
TR1
TR2
TR3
TSL
TSW
W0001-^
WH001-^
WN1-^
WP001-^
WPCP1
WPT01
WSE
Legend:
Note: Devices in legend may or may not be on unit.
ADR
AHL
AN1,2
CO1-04
C11-12
CP1,2
COS
DAT
DCS
DSH
DSS
EB1
EB2
EH1
EWT
FM1-4
GND
HG1,2
HHT
Aquastat, Discharge Refrigerant
Aquastat, High Limit
LED Annunicator, circuit 1, 2
Fan Motor 1-4 Capacitor
Compressor 1,2 Capacitor
Compressor 1, 2
Condensate Overflow Protection Sensor
Discharge Air Temperature Sensor
Disconnect Switch
Desuperheater Pump
Desuperheater Shutoff Switch
Expansion Control Board 1
Expansion Control Board 2 - fan speed ctrl
Electric Heat
Entering Water Temperature Sensor
Fan Motor 1-4
Ground
Hot Gas Reheat Valve Acutator
Hot Water Heat Valve Actuator
www.DaikinApplied.com
49
High Pressure Switch 1, 2
Humidistat Sensor
Water Flow Isolation Valve Actuator
Leaving Air Temperature Sensor
Low Pressure Switch 1, 2
Compressor Suction Line Temperature Sensor 1, 2
Leaving Water Temperature Sensor
Fan Motor 4 Contactor
Compressor 1, 2 Contactor
Secondary Heat Contactor
Main Control Board
Network Control Board
Overload Protector - Compressor Motor
Loop Pump 1, 2
Relay, Field Contacts, Alarm Output
Relay, Loop Pump
Return Air Temperature Sensor
Reversing Valve 1, 2
Terminal Block, Line Voltage
Terminal Block, 24V
Terminal Block, EH1 Line Voltage
Transformer - Control
Transformer - Fan Motor
Transformer - Loop Pump
Thermostat, Wireless
Thermostat, Wired (Unit-mounted)
Wire
Wire Harness
Wire Nut
Wire Plug
Wire Plug Assy - Compressor Power
Wire Plug Assy - 2-stage Comp Ctrl
Waterside Economizer Actuator
IM 1139-8
Typical Wiring Diagrams
MicroTech III Unit Control with BACnet Communication Module (WSE &
DSH) Service & Disconnect - 208-230V, 1-Phase with 115V Loop Pumps
and 20kW Electric Heat
IM 1139-8
50
www.DaikinApplied.com
Typical Wiring Diagrams
MicroTech III Unit Control with LonWorks Communication Module Service
& Disconnect 208-230V, 3-Phase with 230V Loop Pumps and 5kW Electric
Heat
www.DaikinApplied.com
51
IM 1139-8
Typical Wiring Diagrams
MicroTech III Unit Control with BACnet Communication Module (WSE)
Service & Disconnect - 460V, 3-Phase with 230V Loop Pumps and 20kW
Electric Heat
IM 1139-8
52
www.DaikinApplied.com
Maintenance
General Maintenance
1. Normal maintenance on all units is generally
limited to filter changes. Units are provided with
permanently lubricated motors and require no oiling
even though oil caps may be provided.
2. Filter changes are required at regular intervals. The
time period between changes will depend upon
the project requirements. Some applications such
as motels produce a lot of lint from carpeting and
linen changes, and will require more frequent filter
changes. Check filters at 60-day intervals for the
first year until experience is acquired. If light cannot
be seen through the filter when held up to sunlight
or a bright light, it should be changed. A more critical
standard may be desirable.
3. The condensate drain pan should be checked
annually and cleaned and flushed as required.
4. Record performance measurements of volts, amps,
and water temperature differences (both heating
and cooling). A comparison of logged data with
start-up and other annual data is useful as an
indicator of general equipment condition.
Charging
Due to the zeotropic nature of R-­410A, it should be
charged as a liquid. In situations where vapor is normally
charged into a system, a valve should be installed in the
charging line to flash the liquid to vapor while charging.
Note: Because a water source heat pump operates
under a wide range of water and air temperatures, the values printed below are to be taken
as suggested pressure and temperatures. All
Daikin water source heat pumps are designed for
commercial use. The units are designed for both
heating and cooling operation and fail safe to
cooling. The reversing valve is energized for the
heating mode of operation
Superheat
Head Pressure
Water Delta T
8 to 14 degrees
335-355 PSIG
10° to 14°
Notes: 1. All information above is based on ISO standard 13256-1
and tested at these conditions.
2. Operating conditions shall be within the limits established in
Table 26, and Table 27 on page 48.
5. Periodic lockouts almost always are caused by
air or water problems. The lockout (shutdown) of
the unit is a normal protective result. Check for
dirt in the water system, water flow rates, water
temperatures, airflow rates (may be a dirty filter),
and air temperatures. If the lockout occurs in the
morning following a return from night setback,
entering air below machine limits may be the cause.
Lubrication
R-410A should be used only with polyester (POE)
oil. The HFC refrigerant components in R-410A will
not be compatible with mineral oil or alkylbenzene
lubricants. R-410A systems will be charged with the
OEM recommended lubricant, ready for use with R-410A.
www.DaikinApplied.com
53
IM 1139-8
Troubleshooting
Table 28: Troubleshooting refrigeration circuit
Head
Pressure
Suction
Pressure
Compressor
Amp Draw
Super Heat
Subcooling
Air Temp
Differential
Water (Loops)
Temp
Differential
Safety Lock
Out
Undercharge System
(Possible Leak)
Low
Low
Low
High
Low
Low
Low
Low Pressure
Overcharge System
High
High
High
Normal
High
Normal
High Pressure
Low Air Flow Heating
High
High
High
Low Air Flow Cooling
Low
Low
Low
Symptom
Charge
Low Water Flow
Heating
Low
Low
Normal
Normal
High
Normal
Low
Normal
Normal
Low
Low
High
Low
High Pressure
High
High
Low
Low Temp
Low
Low
High
Low
High
Low Temp
Low Water Flow
Cooling
High
High
High
High
Low
Low
High
High Pressure
High Air Flow Heating
Low
Low
Low
Low
High
Low
Low
Low Temp
High Air Flow
Cooling
Low
High
Normal
High
Low
Low
Normal
High Pressure
High Water Flow
Heating
Normal
Low
Normal
High
Normal
Normal
Low
High Pressure
High Water Flow
Cooling
Low
Low
Low
Low
High
Normal
Low
Low Temp
TXV Restricted
High
Low
High
High
Low
Low
IM 1139-8
Normal
Low
54
www.DaikinApplied.com

Water Source Heat Pump Equipment Check, Test and Start Form
This form must be completed and submitted within ten (10) days of start‑up to comply with the terms of the Daikin warranty. Forms should
be returned to Daikin Warranty Department.
Installation Data
Job Name __________________________________________________________ Check, Test & Start Date _________________
City or Town___________________________________________ State__________________________ Zip_________________
Equipment Type (Check all that apply)
□Closed Loop □Open Loop
□Geothermal □Other (specify)______________
Who is Performing CTS______________________________________
General Contractor__________________________________________
Essential Items Check of System – Note: “No” answers below require notice to installer by memorandum (attached copy.)
Essential Items Check
A. Voltage Check___________ Volts
Loop Temp.____________ °F Heating
System Water P.H. Levels___________
Set For____________ °F Cooling
B. Yes
□
□
□
□
□
□
□
□
□
□
□
No
□
□
□
□
□
□
□
□
□
□
□
Condition
Comments
Loop Water Flushed Clean __________________________________________________________________
Closed Type Cooling Tower __________________________________________________________________
Water Flow Rate to Heat Pump Balanced _______________________________________________________
Standby Pump Installed ____________________________________________________________________
System Controls Functioning ________________________________________________________________
Outdoor Portion of Water System Freeze Protected _______________________________________________
Loop System Free of Air ____________________________________________________________________
Filters Clean _____________________________________________________________________________
Condensate Traps Installed __________________________________________________________________
Note: “No” answers below require notice to installer by memorandum (attached copy.)
Outdoor Air to Heat Pumps: _________________________________________________________________
Other Conditions Found: ____________________________________________________________________
Please include any suggestions or comments for Daikin Applied:____________________________________________________
_______________________________________________________________________________________________________
_______________________________________________________________________________________________________
_______________________________________________________________________________________________________
Above System is in Proper Working Order
Note: This form must be filled out and sent to the warranty administrator
before any service money can be released.
For Internal Use
Release:
SM _________________________
CTS _________________________
Date
T _________________________
Signature for Sales Representative
Service Manager Approval
Signature for Customer
www.DaikinApplied.com
55
Date
Form WS-CTS-00.01 (Rev. 4/14)
IM 1139-8

Commercial Check, Test and Start Worksheet
(Complete all equipment measurements indicated for each unit per installation on previous page)
Model
Serial #
H.P. #
EWT
3
LWT
4
EWP
1
LWP
2
EAT
5
LAT
6
Volts
Amps
Cooling
Check
Air
Filter
and
Coil
Comments
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
32.
33.
34.
35.
36.
37.
38.
39.
40.
41.
42.
Part No.______________________________
IM 1139-8
56
www.DaikinApplied.com
Daikin Applied Training and Development
Now that you have made an investment in modern, efficient Daikin equipment, its care should be a high
priority. For training information on all Daikin HVAC products, please visit us at www.DaikinApplied.com
and click on Training, or call 540-248-9646 and ask for the Training Department.
Warranty
All Daikin equipment is sold pursuant to its standard terms and conditions of sale, including Limited
Product Warranty. Consult your local Daikin Applied representative for warranty details. Refer to Form
933-430285Y. To find your local Daikin Applied representative, go to www.DaikinApplied.com.
Aftermarket Services
To find your local parts office, visit www.DaikinApplied.com or call 800-37PARTS (800-377-2787).
To find your local service office, visit www.DaikinApplied.com or call 800-432-1342.
This document contains the most current product information as of this printing. For the most up-to-date
product information, please go to www.DaikinApplied.com.
Products manufactured in an ISO Certified Facility.
IM 1139-8
©2016 Daikin Applied (09/16) | (800) 432–1342 | www.DaikinApplied.com
®
Damper Maintenance
Greenheck’s dampers are designed to be trouble free
and hassle free under normal operation. Dampers are
to be installed square and straight so as to prevent
binding during operation. The following annual damper
maintenance suggestions will help to insure proper
damper operation and increase the life expectancy of
the damper.
Foreign Matter
Over the course of time, dirt and grime may collect
on damper surfaces. The damper surfaces should be
cleaned to prevent hindrance to airflow.
Moving Parts
Make sure that parts such as linkage, bearings, blades,
etc. that are intended to move freely, can do so.
Lubricating these components can prevent possible
rusting and unnecessary friction increase. Use only a
moli-spray oil or similar graphite based oil as regular
lubricating oil will attract dirt.
Bearings. Synthetic, oil impregnated , and ball bearings
without grease fittings require only minimal grease.
Closure
Remove foreign materials that may be interfering with
blade closure or effective sealing of the blades with
each other or with the frame.
Operation
While operating the damper through its full cycle, check
to see that the blades open and close properly. If there
is a problem, check for loose linkage, especially at the
actuator. Tighten the linkage where required.
Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com
• Damper Maintenance Rev 2, November 2016
Copyright 2016 © Greenheck Fan Corporation
Installation, Operation and
Maintenance Manuals
Job Title:
Howard Hughes District Renovations
Customer PO#: S1815-0032-LOU
Elevation: (ft) 325
Date:
11/01/2018
Submitted By: Andrew McDonald
Agent Order#: 95123
NORMAN S WRIGHT CLIMATEC
3325 E LA PALMA AVE
ANAHEIM, CA 92806
US
Phone:
(714)632-9800
Fax:
Email Address: lpara@nswcla.com
P.O. Box 410
CAPS 4.27.1793
Schofield, WI 54476
(715) 359-6171
FAX (715) 355-2399
F:\Caps\Jobs\DOUG\Howard Hughes District Renovations.gfcj
www.greenheck.com
Page 1 of 2
Howard Hughes District Renovations
Product IOMs
Mark Name
Model Name
Bldg 6601 EF-1, Bldg 6601 OAF-1, Bldg 6080 EF-1, Bldg 6080 OAF-1
CSP
Bldg 6601 louvers, Bldg 6080 louvers
ESD-435
(No IOMs)
Vari-Green Motor and Controls IOMs
Mark Name
IOM Name
Bldg 6080 EF-1, Bldg 6080 OAF-1, Bldg 6601 EF-1, Bldg 6601 OAF-1
VG Motors
Vari-Green Controls IOMs
Mark Name
IOM Name
Bldg 6080 EF-1, Bldg 6080 OAF-1, Bldg 6601 EF-1, Bldg 6601 OAF-1
VG Controls - Universal
Assemblies
Accessory IOMs
Accessory IOM Name
Mark Names
Install Operation Maint
Manual
RDC_8_453380
Bldg 6601 OAF-1
Install Operation Maint
Manual SP Fan with
CRD Plaster Flange...
Bldg 6080 EF-1, Bldg 6080 OAF-1, Bldg 6601 EF-1, Bldg 6601 OAF-1
CAPS 4.27.1793
F:\Caps\Jobs\DOUG\Howard Hughes District Renovations.gfcj
Page 2 of 2
Document 474680
Model SP and CSP
Ceiling Exhaust and Inline Fans
®
Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,
operate or maintain the product described. Protect yourself and others by observing all safety information. Failure
to comply with these instructions will result in voiding of the product warranty and may result in personal injury
and/or property damage.
Direct Drive
Ceiling Exhaust Fan
Direct Drive
Inline Exhaust Fan
Designed for clean air applications
where low sound levels are required.
Many options and accessories are
available such as lights, motion
detectors, ceiling radiation dampers
and speed controls. Capacities
range from 25 to 1,600 cfm (42 to 2,718 m3/hr) and
1 in. wg (248 Pa). AMCA Licensed for Sound and
Air Performance.
Designed for clean air applications
where low sound levels are required.
Capacities range from 70 to
3,800 cfm (119 to 6,456 m3/hr)
and 1 in. wg (248 Pa). AMCA
Licensed for Air Performance.
WARNING!
To reduce the risk of fire, electric shock, or injury to persons,
observe the following:
• Suitable for use with solid state speed controls.
• Use this unit only in the manner intended by the manufacturer. If
you have questions, contact the manufacturer.
• Before servicing or cleaning unit, switch power off at service panel
and lock service disconnecting means to prevent power from
being switched on accidentally. When the service disconnecting
means cannot be locked, securely fasten a prominent warning
device, such as a tag, to the service panel.
• Installation work and electrical wiring must be done by qualified
person(s) in accordance with all applicable codes and standards,
including fire-rated construction.
• Sufficient air is needed for proper combustion and exhausting
of gases through the flue (chimney) of fuel burning equipment
to prevent back drafting. Follow the heating equipment
manufacturer’s guideline and safety standards such as those
published by the National Fire Protection Association (NFPA),
and the American Society for Heating, Refrigeration and Air
Conditioning Engineers (ASHRAE) and the local code authorities.
• When cutting or drilling into wall or ceiling, do not damage
electrical wiring or other hidden utilities.
• Acceptable for use over a bathtub or shower when installed
in a GFCI protected branch circuit. (Up through size SP-A390)
• Never place a switch where it can be reached from a tub or
shower.
• Ducted fans must always be vented to the outdoors.
• These fans are not recommended for cooking exhaust
applications. They are designed primarily for low temperature,
clean air applications only. The diagram shows the minimum
distance these fans should be placed in relation to cooking
equipment.
• Fan/Light combination not to be installed in a ceiling thermally
insulated to a value greater than R40.
CAUTION!
• For general ventilating use only. Do not use to exhaust
hazardous or explosive materials and vapors.
®
AVERTISSEMENT!
Pour réduire le risque d’incendie, de choc électrique ou de
blessure corporelle, respecter cd qui suit:
• Appareil pouvant être utilisé avec un régulateur de vitesse à semiconducteurs.
• Utiliser cet appareil exclusivement comme prévu par le fabricant. En
cas de questions, communiquer avec le fabricant à l’adresse ou au
numéro de téléphone figurant dans la garantie.
• Avant tout entretien ou nettoyage de l’appareil, couper l’alimentation
sur le tableau électrique et verrouiller le dispositif de sectionnement
pour empêcher toute mise sous tension accidentelle. Si le dispositif
de sectionnement ne peut pas être verrouillé, attacher un moyen
de mise en garde bien visible, tel qu’un panonceau, au tableau
électrique.
• La pose et le câblage électrique doivent être effectués par des
personnes qualifiées en conformité avec les codes et normes en
vigueur, y compris pour la résistance au feu du bâtiment.
• Une quantité d’air suffisante est nécessaire pour la bonne
combustion et l’extraction des gaz brûlés par le conduit d’évacuation
(cheminée) d’appareils à combustible afin d’éviter le refoulement.
Veiller à suivre les indications du fabricant du matériel de chauffe,
les normes de sécurité telles que celles publiées par la National Fire
Protection Association (NFPA) et l’American Society for Heating,
Refrigeration and Air Conditioning Engineers (ASHRAE) et la
réglementation en vigueur.
• Lors de la découpe ou du perçage de murs ou plafonds, ne pas
endommager les câbles électriques et autres conduites masquées.
• Pose admissible au-dessus d’une baignoire ou d’une douche sous
réserve de raccordement à un circuit de dérivation à protection GFCI
(disjoncteur différentiel). (Jusqu’à la taille SP-A390 incluse)
• Ne jamais placer d’interrupteur à un emplacement à portée d’une
baignoire ou d’une douche.
• Les caissons d’extraction à gaine doivent toujours être évacués vers
l’extérieur.
• Ces caissons ne sont pas conseillés pour les applications
d’aspiration de vapeurs de cuisson. Ils sont conçus essentiellement
pour l’aspiration d’air propre à basse température. Le schéma
indique la distance minimale de placement de ces caissons par
rapport à l’équipement de cuisson.
• Le combiné ventilateur/luminaire ne devra pas être installé dans un
plafond ayant une isolation thermique d’une valeur supérieure à R40.
ATTENTION!
• À utiliser pour la ventilation générale uniquement. Ne pas utiliser pour
l’aspiration de matières et vapeurs dangereuses ou explosives.
Ceiling Exhaust and Inline Fans
1
Prepare the Fan
Power Assembly
Remove Wiring Knockout
If power assembly (motor, wheel, and scroll) is not
installed in housing, insert the electrical plug into fan
socket, then slide scroll end of power assembly into
fan housing. Attach by using two sheet metal
screws provided.
Remove either top or side wiring knockout,
depending on wiring
direction, by
Electrical
Access
bending it back
Panel
and forth to
break tabs.
A Model
B Model
Knockouts
Ductwork
Airflow
Check ductwork to see if the fan’s discharge requires
rotation from horizontal to vertical discharge.
Airflow
Fan Rotation
To rotate from horizontal to vertical discharge
A Models Only
A50-500, 710, 780 Models
Remove the two screws holding the power assembly
in and pull power assembly out. Rotate power
assembly 180 degrees and put back into fan. Use
the same screws to reattach power assembly to fan
housing. Flip fan over and remove the four screws
holding the discharge duct and damper assembly.
Exchange the assembly with plate mounted on top of
fan, as shown in these illustrations.
A700, 900-1500 Models
Remove the eight screws
holding the access panel or
collar as shown in picture.
Rotate the fan housing so
the discharge is facing up.
Replace access panel or
collar and screws.
2
Ceiling Exhaust and Inline Fans
Access
Panel
Access
Panel
®
Ceiling Radiation Damper (CRD)
If fan is to be used in a fire resistive membrane
ceiling, a ceiling radiation damper must be used.
If the ceiling radiation damper is already mounted to
the fan from the factory, proceed to Install the Fan.
To mount the ceiling radiation damper to fan, make sure
grille attachment tabs are facing down. Then place the inlet
part of the fan into the ceiling radiation damper collar, and
use self-tapping sheet metal screws (by others) to screw
through the damper collar and into the fan housing. If the
fan/light combination is being used, make sure ceiling
radiation damper has
an electrical plug in it.
The electrical plug must
be inserted into the fan.
Make sure the electrical
wire will not interfere with
damper operation as
shown in figure below.
Wires to ceiling fan
Attachment Tabs
A50-510, 710, 780 Models
B Models
Do not allow
interference
in this area
A700, 900-1550 Models
Wires from lighted grille
Discharge Installation A50-90 Models
1
2
Insert plastic duct tab into box slots.
Rotate plastic duct adapter (PN 473388)
until the screw tabs meet the box.
Sheet Metal Screw #10x3/8
Phillips Head (PN 415838)
Box
Sheet Metal Screw #10x3/8
Phillips Head (PN 415838)
Box
Box Slot
Plastic Duct
Adapter Tabs
Plastic Duct
Adapter (PN 473388)
3
Plastic Duct
Adapter (PN 473388)
Screw Tabs
Install screws provided to secure discharge.
Screw holes
Sheet Metal Screw #10x3/8
Phillips Head (PN 415838)
®
Ceiling Exhaust and Inline Fans
3
Discharge Installation for Ceiling and Inline Exhaust Models Sizes B50-200
1
Insert box scroll tab into box scroll slots.
2
Rotate plastic duct adapter (PN 474433)
until the two mounting tabs fully engage
into the two box mounting slots.
Box Scroll Tabs
Box Mounting Slots
Box Scroll Slots
Box Mounting Tabs
3
OPTIONAL
Align the pins on the TR 6x4 adaptor to the duct pin hole on
the 6-inch duct. Push until the adaptor snaps into place.
TR 6x4 Pin
Plastic Duct Pin Hole
TR 6x4
(PN 473324)
4
Ceiling Exhaust and Inline Fans
6-inch
Plastic Duct
(PN 474433)
®
Install the Fan
1. For best
performance,
choose a location
with the shortest
possible duct run
and minimum
number of elbows.
Do not mount near
cooking equipment, as
shown in Fig. 1.
Do not install
fan in this area
45°
Fig. 1
Bottom Mount
2. Attach adjustable
mounting brackets
to fan, but leave the
screws loose until
proper height is
determined, shown
in Fig. 2. Cut hole to
dimensions shown
in table below:
45°
Brackets can be
used in either
position to adapt to
most mounting
situations
Bottom Mount
Top Mount
Fig. 2
Ceiling Openings
Ceiling Exhaust Sizes
A50, A70, A90
A110, A125, A190
A200, A250, A290, A390
Fan/CRD
107⁄8 x 133⁄8
111⁄8 x 137⁄16
121⁄8 x 141⁄4
121⁄4 x 143⁄8
A700
233⁄4 x 113⁄4
241⁄8 x 121⁄4
A410, A510, A710, A780
3
14 ⁄4 x 18 ⁄8
147⁄8 x 187⁄16
143⁄4 x 24
147⁄8 x 241⁄8
14 ⁄8 x 11 ⁄4
143⁄8 x 121⁄4
3
A900, A1050, A1410, A1550
B50 - 200
1
3
NOTE
Model sizes A50-90 are standard with a round duct.
Should any model A110-190 require a round duct,
Model RDC (Round Duct Connector) may be ordered
from manufacturer for field installation.
For Hanging
Installations:
Use manufacturer’s
optional vibration
isolator kit Part Number
VI Kit. Using the fan’s
standard adjustable
mounting brackets and
10 by 32 threaded rod
(by others), hang unit as
shown in Fig. 4.
Slots in the
brackets
allow fine
adjustment
for flush
fit with
wall/ceiling
opening
Fig. 3
Fig. 4
3. Installation of ductwork
is critical to the performance
of the fan, shown in Fig. 5.
Straight ductwork (1) or
ductwork that turns in
the same direction as the
wheel (2) is recommended.
Ductwork turning opposite
the wheel direction (3) will
cause turbulence and back
pressure resulting in poor
performance.
Fig. 5
1
(GOOD)
3
(POOR)
2
(GOOD)
AIRFLOW
Fan or Fan/Light
For Frame Construction:
Position unit between
joists. Position brackets
such that bottom
edge of housing will
be flush with finished
ceiling, and tighten the
adjustable mounting
brackets, shown in
Fig. 3.
4. Slide ductwork over the fan’s discharge collar and
securely attach it with sheet metal screws.
Make sure the screws do not interfere with damper
operation. Check damper to make sure it opens freely.
Wire the Fan
1. Remove wiring cover.
If fan/light combination
is being used, make
sure the fan plug is
connected to the fan
receptacle and the light
Fan Outlet (top)
plug is connected to
the light receptacle,
Light Outlet (bottom)
Fig. 6
shown in Fig. 6.
Using proper wire
connectors, wire the fan as shown in Fig. 7a.
For wiring of light proceed to Fig. 7b.
Fan
Light
Fig. 7a
Fig. 7b
115 & 277 Volt
220 - 240 Volt
Black wire is “Hot”
White wire is “Neutral”
Green wire is “Ground”
Black wire is “Hot”
White wire is “Hot”
Green wire is “Neutral/Ground”
2. Push all wiring into the unit’s cover and replace
wiring cover.
®
Ceiling Exhaust and Inline Fans
5
A50-90-VG and A90-130-VG fan models.
These fan models utilize an internal switch to set the fan
to run at one of three flows. Please set three position
switch to desired airflow when installing unit.
FAN
9 0 11
0 130
A 9 0 -1
30
A50
5 0 7 0-9 0
90
90 110 130
A90-130
A50-90
50 70
90
FAN
Attach the Grille
1. If lighted grille is being used, plug wire into fan
socket.
If lighted grille and ceiling radiation damper are being
used, plug wire from lighted grille into ceiling radiation
damper socket. Do not plug wire directly into the fan
socket. Make sure the wire does not interfere with the
ceiling radiation damper operation.
2. Attach grille with two screws provided. Make sure not
to over tighten; over tightening will damage grille.
3. Slide attachment screw covers over the attachment
screws, shown in Figure 8 and 9.
Fig. 8
4. If lighted grille is being used, install light bulb(s)
into light socket(s). For fluorescent lights, use 27W
GU24 bulbs. For LED lights, use 10W GU24 bulbs.
Manufacturer has replacement 27W GU24 bulbs, call
1-800-355-5354 to order.
5. If lighted grille is being used, snap lens into place, by
pushing on the outside edges of lens, shown in Fig. 9.
To remove lens, use small screw driver and pry on
one side of lens.
6. Turn on power and check fan and light operation.
Fig. 9
Squeeze
tabs to
insert/remove lens
6
Ceiling Exhaust and Inline Fans
®
Converting from Ceiling to Cabinet Design for Ceiling Exhaust Fans
All convertible sizes will be shipped with grille and duct
collar cover. Note, this applies only to fans originally
ordered as convertible.
B
A
Conversion Kit Parts List
• Qty. of 1 Blower Box Cover
Tools Required
• Phillips Head Screwdriver
Step 1: Remove grille (A) by removing the two grille
screws (B).
C
D
D
F
E
Step 2: Remove duct collar cover (C) by removing the
four duct collar screws (D).
Step 3: Discard grille (A), two grille screws (B), and
duct collar cover (C).
Step 4: Remove the six (6) tinnerman clips (E) by
twisting them to one side and pulling straight
out. Discard two of the six tinnerman clips.
Step 5: Insert the remaining four tinnerman clips (E) on
grille opening side.
Step 6: Place blower box cover (F) over tinnerman clips
(E), which were inserted in step 5.
E
Step 7: Screw the blower box cover (F) into place with
four blower box cover screws (D).
Other Installation Considerations
Ductwork and Noise
Flex Duct
Connections
Fiberglass ductboard is a better choice than metal
ductwork for reducing fan noise and is highly
recommended for low sound applications. Where metal
duct is used, sound transmission can be reduced with
flexible duct connections between the fan and the duct.
Sound and Location
The location of these fans must be taken into
consideration before installation. In critical sound
installations, insulated ductwork, flexible duct
connections or placing the fan in a remote section of
ductwork are solutions to meeting the required fan
sound levels.
Filters
The addition of an intake filter is highly recommended
for these fans, even in clean air environments excess
dirt can accumulate on wheels and motors causing
reduced performance and imbalance.
Remote
Mounted
Fan Converted
to Inline
Fiberglass
Ductboard
Fan Mounted
Directly Overhead
Filters, once installed, should be checked and cleaned
periodically to maintain performance.
Washable aluminum mesh filters specifically designed
for these fans are available, please consult your
representative for more information.
Correct Low
Sound Installation
Incorrect
®
Ceiling Exhaust and Inline Fans
7
Typical Installation
INSULATION*
(Place around and over Fan Housing.)
ROOF CAP*
(with built-in damper)
FAN HOUSING
POWER CABLE*
Seal gaps around
Housing.
Keep duct runs short.
OR
ROUND
DUCT*
Seal duct joints
with tape. ROUND
ELBOWS*
*Purchase separately.
General Maintenance Suggestions
Ceiling exhaust fans require very little maintenance, but
since small problems over time left unchecked could
lead to loss of performance or early motor failure, we do
recommend that the unit be inspected periodically (once
or twice a year).
WALL CAP*
(with built-in damper)
ENERGY STAR® Models
ENERGY STAR® Certified models include:
SP-A70, 90, 110, 125, 190, 200 and 250,
SP-A50-90-VG and SP-A90-130-VG,
SP-B70, 80 and 90.
The fan motor and wheel should be checked for dust
and dirt accumulations. Dirt buildup can lead to loss of
performance and motor overheating. Cleaning can be
accomplished by brushing off any dust that may have
accumulated. Even filtered units can accumulate buildup and should be checked when cleaning filters.
The motor should be checked for lubrication at this
time. Lubricate only those motors which have an oil hole
provided. A few drops of all purpose oil (SAE 20) will be
sufficient.
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.
Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the
Library under Warranties.
Greenheck’s Centrifugal Ceiling and Cabinet Exhaust Fans
)catalog provides additional information describing the
equipment, fan performance, available accessories, and
specification data.
AMCA Publication 410-96, Safety Practices for Users and
Installers of Industrial and Commercial Fans, provides
additional safety information. This publication can be
obtained from AMCA International, Inc. at www.amca.org.
®
Phone: 715.359.6171 • Fax: 715.355.2399 • Parts: 800.355.5354 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com
8
474680 • SP CSP, Rev. 4, March 2018
Copyright 2018 © Greenheck Fan Corporation
Document 473681
Vari-Green® Motor and Controls
®
Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,
operate or maintain the product described. Protect yourself and others by observing all safety information. Failure
to comply with these instructions will result in voiding of the product warranty and may result in personal injury
and/or property damage.
Table of Contents
Reference part number listed in chart to locate specific motor
information page number.
HP
Voltage
* RPM
Encl.
FLA
Control
Method
Motor
Part No.
Pg.
1/10
115
300-1725
TENV
1.5
Pot/0-10V
318003
4
1/10
1/6
1/6
Range
115/208300-1750
230/277
ODP
115/208300-1750
230/277
ODP
115
300-1725
TENV
1.38/
0.84/0.73
Pot/0-10v
2.2/1.3/
1.1
Pot/0-10v
319357
4
2.6
Pot/0-10V
318004
4
3.1
0-10V Only
311352
3.1
Pot Only
311353
3.4
Pot/0-10V
319356
4
3
312359
3
0-10V Only
309026
10.1
Pot Only
309029
10.6
Pot/0-10V
311388
312619
3
3
3/4
208-240
300-1725
ODP
6.6
Pot/0-10V
314534
3
3/4
277
300-1725
OPD
5.4
Pot/0-10V
316498
3
11.3
0-10V Only
310306
11.3
Pot Only
310475
11.3
Pot/0-10V
312361
3
5.6
Pot/0-10V
317708
3
3
3/4
115
300-2200
ODP
3/4
208-240
350-2200
OPD
277
350-2200
OPD
4.7
Pot/0-10V
317709
3
115/208300-1725
230/277
OPD
8.8/5.45.0/4.8
Pot/0-10V
320589
4
3/4
ODP
12.4
Pot/0-10V
Pot/0-10V
318013
4
1
TEFC
12.0/6.0
Pot/0-10V
311156
5
0-10V Only
310107
115/
208-240
300-1725
3.9
3.9
Pot Only
310108
3
1
208-240
300-1725
ODP
8.6
Pot/0-10V
314945
3
3
1
277
300-1725
ODP
7.3
Pot/0-10V
316499
3
1
115/208300-1725
230/277
ODP
11.5/7.06.5/5.8
Pot/0-10V
320590
4
2
208-240 300 - 1725 TEFC
12.0
Pot/0-10V
310420
5
277
300-1725
TENV
1.15
Pot/0-10V
115/208300-1725
230/277
ODP
2.85/
1.7/1.5
1/3
10.1
Pg.
300-1725
1/6
3.7
Pot/0-10V
2.3
Pot/0-10V
313713
311377
313714
313234
208-240
300-1725
ODP
277
300-1725
OPD
1.8
Pot/0-10V
316496
3
ODP
4.4/2.62.4/2.2
Pot/0-10V
320587
4
6.2
0-10V Only
309025
6.2
Pot Only
309028
115/208300-1725
230/277
Motor
Part No.
115
Pot/0-10V
1/4
313233
Control
Method
1
1.6
1/4
ODP
FLA
3
TENV
ODP
300-1725
Encl.
316495
300-1725
300-1725
Range
3
208-240
115
115
* RPM
3/4
1/6
1/4
3/4
Voltage
311731
313712
1/4
HP
313715
3
310359
312362
3
*Actual maximum RPM may vary. See RPM column in chart on
page 11 for specific motor and fan combinations.
3
1/2
115
300-1725
ODP
6.7
Pot/0-10V
311812
3
1/2
208-240
300-1725
ODP
4.2
Pot/0-10V
313235
3
1/2
277
300-1725
ODP
3.3
Pot/0-10V
316497
3
6.5
0-10V Only
310307
6.5
Pot Only
310476
3
1/2
115
300-2500
ODP
6.5
Pot/0-10V
312360
3
1/2
208-240
350-2500
ODP
4.9
Pot/0-10V
317706
3
1/2
277
3500-2500
ODP
3.27
Pot/0-10V
317707
3
Controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-11
ODP
6.4/3.83.6/3.2
Pot/0-10V
320588
4
Maximum RPM Table . . . . . . . . . . . . . . . . . . . . . . . . 12
1/2
®
115/208300-1725
230/277
Vari-Green Motor and Controls
1
Vari-Green® Motor
The Vari-Green Motor is an electronically commutated
(EC) motor that uses AC input power and internally
converts it to a DC power supply which provides an
80% turndown capability and increased energy savings.
Features, Operation and Wiring, and
Troubleshooting
Features
Soft start – All motors
feature soft-start
technology which
eliminates inrush current
at start-up. The motors
will reliably start at any
speed setting.
Overload protection – If the motor becomes
overloaded, it will automatically reduce its speed until it
is no longer overloaded. This means that the motor will
never operate in the “service factor” which is possible
with many AC motors.
Locked rotor protection – If the motor ever encounters
a locked-rotor scenario, the motor will automatically
shut itself down. It will try to restart up to 3 times, and if
after the 3rd time the motor will still not rotate, the motor
will not attempt to start again until power is cycled.
NOTE
When using a clamp meter to measure input amp
draw, the meter must be capable of reading a
non-linear current. Erroneous readings will occur
otherwise.
Thermal protection – The motors have a one-shot fuse
thermal protector. This is meant to protect the motor
from a severe temperature rise. Additionally, the motors
have on-board temperature sensors which will reduce
the speed of the motor should it become too hot. The
fuse is used as a last resort to prevent a fire.
WARNING
To reduce the risk of fire or electric shock, do not use
this motor with any solid-state speed control device.
RPM measurement – The motors have a small shaft
extension on the end of the motor to measure motor
RPM with either a contact or optical tachometer.
Fig. 1
0-10 VDC External connection with factory mounted transformer (See page 4 for details)
Transformer Assembly
100 ft. or less
White
Black
Red
COM
24V
0-10V
COM
24V
0-10V
Low voltage, route away
from high voltage lines
and/or use shielded cable
N.C.
COM.
N.O.
TO REMOTE DEVICE
PROVIDED BY
OTHERS
Auxiliary
Contact
Control
Motor
Trip Point = 1.85VDC
Contact Rating:
10A @ 24-240VAC
5A @ 30VDC
Green indiator light
—Power present
TRANSFORMER
2x4
Junction
Box
Factory Wiring
Field Wiring
115/230 VAC input
to match motor name plate
2
Vari-Green Motor and Controls
®
Operation and Wiring
- Potentiometer Dial Only
Part Numbers Covered in this Section
309028
309029
310108
310475
310476
311353
These motors feature a potentiometer dial on the motor
for speed adjustment. A small screwdriver can be used
to make the speed adjustment. To increase the speed,
rotate the dial clockwise. To decrease the speed, rotate
the dial counterclockwise.
The motor is pre-wired at the factory and cannot be
changed inside the motor. Connect single-phase power
at the voltage listed on the nameplate.
These motors cannot be converted to receive a remote
control signal – a different motor is needed. Please
consult the factory.
Operation and Wiring
- 0-10V Input Only
Part Numbers Covered in this Section
309025
309026
310107
310306
310307
311352
These motors will accept a 0-10 VDC control signal for
speed control. From 0-1.9V, the motor will be off, and
will operate in the 2-10V range. 24 VAC/DC power is
also required for operation. The motor will consume
0.7VA at 24 VAC or 25mA at 24 VDC. A factory mounted
transformer is available to supply this voltage.
(See Fig. 1)
Dial on Motor – A small screwdriver can be used to
make the speed adjustment. To increase the speed,
rotate the dial clockwise. To decrease the speed, rotate
the dial counterclockwise. There is no need to connect
the control wires.
0-10 VDC signal – The dial on the motor must be
rotated fully clockwise to achieve the full speed range.
If this is not done, the dial will act as a maximum speed
limiter.
From 0-1.9V, the motor will be off, and will operate in
the 2-10V range. 24 VAC/DC power is also required for
operation. The motor will consume 0.7VA at 24 VAC
or 25mA at 24 VDC. A factory mounted transformer is
available to supply this voltage. (See Fig. 1, page 2)
A low voltage wiring harness is needed to supply the
0-10V signal to the motor. This harness is available from
the factory if conversion is necessary.
Low Voltage Harness Part Numbers
Type
Use with Motor
18 in. long
36 in. long
3-pin
311731, 310359
384431
384432
9-pin
312359, 311377,
311812, 311388,
312360, 312361,
312362, 312619,
313233, 313234,
313235, 313712,
313713, 313714,
313715, 314534,
314945, 316495,
316496, 316497,
316498, 316499,
317706, 317707,
317708, 317709
384804
384805
The motor is pre-wired at the factory and cannot be
changed inside the motor. Connect single-phase power
at the voltage listed on the nameplate, along with the
0-10 VDC and 24V signal for speed control.
NOTE: The motor will not operate without the proper
control voltages.
Operation and Wiring
- Potentiometer Dial and 0-10V Input
Part Numbers Covered in this Section
310359
311731
311377
311388
311812
312359
312360
312361
312362
312619
313233
313234
313235
313712
313713
313714
313715
314534
314945
316495
316496
316497
316498
316499
317706
317707
317708
317709
These motors have both a potentiometer dial on the
motor for speed adjustment AND have the ability to
accept a 0-10 VDC signal for remote speed control.
NOTE
The 9-pin connector on the motor contains 6 wires.
The red, black and white wires are used for the
external control signal and the other three are used for
factory initialization and programing.
0-10V Analog input connection
Red
+ 0-10 VDC
White
Common*
Black
+24 VAC/DC
*Common is shared between both 24V power
and 0-10V signal.
The impedance of 0-10V circuit is 12KΩ
There is a 4 second delay between the application of
power and the motor starting.
The motor is pre-wired at the factory and cannot be
changed inside the motor. Connect single-phase power
at the voltage listed on the nameplate. If remote control
is desired, connect the 0-10 VDC and 24V signal for
remote speed control.
®
Vari-Green Motor and Controls
3
Troubleshooting
Operation and Wiring
Motor does not operate
- Potentiometer and 0-10V Input
1. Check all wiring connections to ensure they are
correct and secure.
2. Verify that all voltages are present at the motor,
including 24V and 0-10 VDC, if applicable.
3. Make sure that the fan wheel will rotate freely and
there are no foreign objects in the wheel. If fan wheel
does not rotate freely, disconnect power from the
motor and adjust the wheel or housing until the
wheel can freely rotate. Apply power and the motor
should restart.
4. If motor has both the dial on the motor and 0-10 VDC
control option, control wiring issues can be tested
by disconnecting the control wires from the motor.
The motor should then operate using the dial on the
motor for speed control.
Motor will not reach maximum speed
1. Make sure dial is rotated full clockwise, if applicable.
2. Make sure motor is receiving 10 VDC, if applicable.
3. There are some motor/fan combinations
where the motor may not reach nameplate
RPM. See Max RPM table on page 11 for the
maximum motor speed for your application.
Factory Mounted Transformer (Fig. 1, page 2)
A factory mounted transformer is available to supply
24 VDC power to the motor when the 0-10V signal
is by others. This transformer has the capability to
power a remote device if desired. The power available
to a remote device is 400mA at 24 VDC. If the remote
device is powered by a different source, connect the
analog output to the 0-10V and COM terminals of the
transformer. This will pass the signal through to the
motor.
Part Numbers Covered in this Section
318003
318004
318013
319356
319357
320587
320588
320589
320590
These motors have the ability to accept a plug in
potentiometer for speed adjustment AND the ability to
accept a 0-10V signal for remote control.
There is a 4 second delay between the application of
power and the motor starting.
Motor part numbers 318003, 318004 – The motor is
prewired at the factory and cannot be changed inside
the motor. Connect single-phase power at the voltage
listed on the nameplate.
Motor part numbers 318013, 319356, 319357, 320587,
320588, 320589 and 320590 – The motor is prewired
at the factory and can operate on 115v up to 277v.
Operating voltage is changed via voltage jumper wire.
Voltage jumper – For 115v the red jumper wire on
the side of the motor must be connected (closed).
For 208v-277v operation the red jumper must be
disconnected (open).
Dial on Motor – A potentiometer (p/n 385806) can
be plugged into the 9-pin connector of the motor. To
increase speed, rotate the dial clockwise. To decrease
speed, rotate the dial counterclockwise.
0-10 VDC Signal – From 0-1.9V, the motor will be off,
and will operate in the 2-10V range. A low voltage
wiring harness is needed to supply the 0-10V signal to
the motor. The harness is available from the factory if
conversion is necessary.
Low Voltage Harness Part Numbers
Type
Use with Motor
18 in. long
36 in. long
9-pin
318003, 318004,
318013, 319356,
319357, 320587,
320588, 320589,
320590
385821
385822
WARNING
Do not connect an external 24V supply to the
transformer's control terminal labeled 24V. If the
external device providing the 0-10V signal is powered
elsewhere, this terminal can remain unused.
NOTE
The 9-pin connector on the motor contains 6 wires.
The yellow, orange, red and white wires are used for
external control. The other two wires are used for
factory initialization and programming.
0-10V Analog Input Connection
4
Vari-Green Motor and Controls
Red
+ 0-10 VDC
White
Common
®
Troubleshooting
Motor does not operate
1. Verify the motor is wired correctly and all connections
are secure.
2. If using dial on motor, verify the potentiometer is fully
seated in the 9-pin connector.
3. If using 0-10 VDC, verify that all voltages are present
at the motor.
Motor does not reach maximum speed
1. Make sure dial is rotated full clockwise, if applicable.
2. Make sure motor is receiving 10 VDC, if applicable.
3. There are some motor/fan combinations where the
motor may not reach nameplate RPM. See Max
RPM table on page 11 for the maximum motor speed
for your application.
Part Numbers Covered in this Section
310420
311156
Features
Speed control These motors can be
controlled by either
a dial on the motor
or a 0-10 VDC signal
for remote control.
Soft start – All motors feature soft-start technology
which eliminates inrush current at start-up. The motors
will reliably start at any speed setting. There will be up
to a 30 second delay between the application of power
and the motor starting. The motor will "rock" back and
forth upon startup as part of its normal operation.
Overload protection – If the motor becomes
overloaded, it will automatically shut itself down. The
maximum programmed motor speeds have been
selected to prevent this from happening in normal
operation.
Locked rotor protection – If the motor encounters a
locked-rotor scenario, it will automatically shut itself
down. It will try to restart up to 3 times, and if after the
3rd time the motor will still not rotate, the motor will not
attempt to start again until power is cycled.
Thermal protection – The motors have an automatic
reset thermal protector. This is meant to protect the
motor from a severe temperature rise.
RPM measurement – The motor RPM can be
measured by removing the cooling fan cover and using
a contact or optical tachometer. Be sure to replace the
cooling fan cover when finished.
Reversible rotation – The motor direction has been
pre-set at the factory for the rotation of the fan but can
be reversed if necessary.
Operation and Wiring
These motors can be controlled by either a dial on the
motor or a 0-10 VDC signal for remote control. The
motor will be supplied from the factory with the correct
accessory depending on what was ordered.
Dial on Motor - Turn the dial with your fingers to adjust.
To increase the speed, rotate the dial clockwise. To
decrease the speed, rotate the dial counterclockwise.
Turning the dial full Counter Clock Wise will turn the
motor off.
0-10 VDC Signal - From 0-1.9V, the motor will be off,
and will operate in the 2-10V range. This motor does not
require 24V power for operation.
®
Vari-Green Motor and Controls
5
0-10V Analog Input Connection
Red
+ 0-10 VDC
White
Ground
Wiring
1. All high and low voltage wiring connections are made
inside the motor control box at the factory. Normally,
there is no reason to enter the control box of the
motor. If there is a need to enter the control box,
disconnect power and wait at least five minutes to
allow the capacitors to discharge.
2. The motors are factory wired for the ordered voltage.
If the factory wired voltage does not match the
desired voltage, the voltage can be changed, with
exception of the 2HP motor (310420), which is
208‑240V only.
115V: Connect 115 VAC to L1, connect Neutral to N.
The L2 terminal remains empty. Connect ground to
grounding stud.
Dial on Motor - the dial
is factory-wired into the
low voltage terminal block
inside the control box.
The wires are connected
as shown.
Dial on motor connection inside control box
0-10 VDC Signal - a two-wire
pigtail is factory-wired into the
low voltage terminal block.
The wires are connected
as shown.
0-10 VDC signal connection inside control box
If the motor needs to be tested before the 0-10 VDC
signal is available, a jumper can be placed between
terminals 1 and 2. This will force the motor to run at
full speed.
Motor Rotation
115V Connection inside control box
To reverse the rotation of the motor, swap any two of
the red, black and blue wires connecting the control
board to the motor at terminals T1, T2 and T3. Note
that motor warranty is void if motor is rotating in the
wrong direction. See fan instruction manual for correct
rotation direction.
208-240V - Connect line voltage to L1 and L2. The N
terminal remains empty. Connect the ground to the
grounding stud.
T3
Rotation selection wires inside control box
208-240V Connection inside control box
6
Vari-Green Motor and Controls
®
Troubleshooting
These motors have a diagnostic red LED on the circuit
board inside the control box, or on the exterior of the
control box, that will be solid (not flashing) when power
is applied to the motor and the motor is operating
normally. The LED may be solid even if the motor is not
spinning, such as when power is applied but the motor
may be commanded to be off with a 0-1.9V VDC signal.
1. If external LED is not present, to view the status of
the LED the control box cover must be removed
while power is applied to the motor. If the control
box cover is removed while power is applied,
extreme care must be taken not to touch any of the
components inside the box.
2. If a fault occurs, the LED will blink a specific number
of times to identify the fault that has occurred. The
fault indications are as follows:
Controls: Operation,
Wiring and Troubleshooting
Remote Dial/Touch Remote and
2-Speed Control
Remote Dial
Installation Overview: The remote dial is provided
with the fan, shipped loose for remote installation.
It also includes a factory mounted 24 VDC transformer.
1. Disconnect power to the fan.
2. Identify where the remote dial will be mounted.
3. Mount a standard single-gang 2x4 junction box.
4. Run a 3-wire control cable from the remote dial to
the fan motor compartment. The maximum distance
from the fan to the remote dial is 100 feet. If a greater
distance is required, signal loss may occur and cause
the fan to operate erratically.
Number of Blinks
Indicated Fault
2
Hardware Fault
3
Overvoltage
5. Connect control cable to transformer mounted inside
fan motor compartment. Connect control cable to
remote dial.
4
Undervoltage
6. Secure remote dial to 2x4 junction box.
5
Communication Error
6
Sync Loss
7
Spin Fault
8
Motor Overload
9
Motor Over Temperature
3. When the LED is blinking, it will consecutively blink
from 2 to 9 times, followed by a pause, and repeat
the blink sequence. It is best to count the number
of flashes 2 or 3 times to ensure accuracy.
4. Under most fault conditions the motor will
automatically restart. If a motor overload fault occurs
more than 10 times in one hour, the motor will shut
down and require a power cycle to reset.
5. If the fault persists, consult the factory.
Remote Dial with Min/Max Setting
Remote dials (P/N 385803) are capable of setting
minimum and maximum voltage limits. Setting voltage
limits will require a multi-meter. To set a voltage span:
1. Install and wire remote dial as previously instructed.
2. Install multi-meter probes into the red (0-10v) and
black (ground) connectors.
3. To set maximum voltage limit, apply power to the
motor, transformer and remote dial. With remote dial
set to zero (0), hold the Upper Limit button down and
turn the dial until the desired voltage is displayed on
your multi-meter. Release button to save max voltage
setting.
1. Verify the motor is wired for the correct voltage.
4. To set lower voltage, turn remote dial back to zero
(0). Hold down Lower Limit button while turning
dial to desired voltage on your multi-meter. Release
button to set minimum voltage limit.
2. Verify that the dial on the motor is properly
connected to the control board - or - verify that
the 0-10 VDC wires are properly connected to the
control board.
5. To reset to default (0-10v) limits, hold both Upper
and Lower limit buttons down simultaneously until
the LED indicator lights up. Then release buttons and
default levels will be restored.
Motor does not operate
3. Verify that the Status LED is solid red.
4. Verify that a jumper is in place between terminals
9 and 10. The motor will not run without this jumper
in place.
NOTE: Upper voltage limit must be set prior to
setting lower voltage limit. Upper and lower limits
can only be within 0.5v of each other.
5. Verify that the two yellow wires coming from the
motor are in place on terminals 5 and 6.
®
Vari-Green Motor and Controls
7
Touch Remote
Follow installation instructions for remote dial above.
After power is applied to the system, operate as follows:
1. Touch power button to turn fan on.
Other Vari-Green® controls, such as the Constant
Pressure and Air Quality families of controls, have their
own manual that ship with the controller. They can also
be found on Greenheck.com. See table on page 10 for
document numbers.
2. Touch UP/DOWN arrow to increase/decrease speed.
3. Subsequent touches of the power button will start
the countdown timer of 90, 60, 30 or 10 minutes.
CAUTION
Even though the motor may not be operating, high
voltage power may still be present at the motor. Make
sure to disconnect power to the fan before servicing.
4. LED's will turn off after a period of inactivity.
5. To lock/unlock buttons, hold the UP and DOWN
arrows for 3 seconds. When locked, the power
button will light up red.
Remote Dial/Touch Remote Assembly
Remote Dial/Touch Remote Assembly
100 ft. or less
COM
White
Black*
Red
24V
0-10V
N.C.
COM.
N.O.
COM
24V
0-10V
COM
24V
0-10V
0-10V
24V
COM
Auxiliary
Contact
Control
Motor
*NOTE: Black wire not
used on some motors
Green indiator light
—Power present
Trip Point = 1.85VDC
Contact Rating:
10A @ 24-240VAC
5A @ 30VDC
REMOTE DIAL/
TOUCH REMOTE
TRANSFORMER
Low voltage, route away
from high voltage lines
and/or use shielded cable
2x4
Junction
Box
Factory Wiring
Field Wiring
115/230 VAC input
to match motor name plate
Troubleshooting Remote Dial/Touch Remote
Remote Dial with Min/Max Setting
Remote Dial does not adjust motor RPM
1.Check voltage to ensure the motor and transformer
are receiving the correct line voltage.
Upper Limit Button
Lower Limit Button
2.Check voltage at the remote dial. 24 VDC should be
present across the 24V and COM terminals. 0-10 VDC
should be present across the 0-10V and COM
terminals.
3.Verify all of the connections at the transformer and
make certain that they are secure.
4.Touch remote: Verify that the touch remote is unlocked.
LED Indicator
5.To reset to default (0-10v) limits, hold both Upper and
Lower limit buttons down simultaneously until the LED
indicator lights up. Then release buttons and default
levels will be restored.
Terminals
24V-COM
0-10V-COM
8
Vari-Green Motor and Controls
Desired Voltage
24 VDC Nominal
0-10 VDC
(varies with dial position)
®
Two Speed Assembly
115-230 VAC
115-230 VAC
NEUTRAL
SPDT
Switch/Relay
by others
Factory Wiring
Field Wiring
Low voltage (<10V), route
away from high voltage lines
and/or use shielded cable
100' or less
Red
Black*
White
FACTORY MOUNTED
2 SPEED CONTROL
Motor
Out
Dry
Contact
Input
COM
24V
0-10V
COM
A
B
NEUTRAL
L2(115V-230V)
L1(115V-230V)
Digital
Input
®
Speed A
Adjustment
Green indicator light
—Power present
Speed B
Adjustment
*NOTE:
Black wire not used
on some motors
Digital Input Logic
L1 or L2 = Speed B
L1 and L2 = Speed A
No input = Off
2x4
Junction
Box
115/230 VAC Input
to match motor name plate
Two Speed Control
Troubleshooting - Two Speed Control
Installation Overview: The two speed control is factory
mounted to the fan and may be set to provide any
two speeds the application requires. It also includes a
24 VDC transformer. A green LED will be illuminated
when the 2-speed control is powered.
1. Check all wiring connections to ensure they are
correct and secure.
1. There are two methods of toggling between speed A
and speed B:
a. Dry contact input - this utilizes an external
switching device such as a relay or SPDT switch
to toggle between the two speeds.
• Connect terminal “A” to “COM” for speed A.
• Connect terminal “B” to “COM” for speed B.
If no contact is made between either terminal the
motor will be off.
2. Verify AC line voltage is present at the motor and
2-speed control.
3. Verify 24 `VDC is present at the 24V and COM
terminals of the "Motor" terminal block.
4. Measure DC voltage between the 0-10V and COM
terminals of the "Motor" terminal block. This voltage
should match the dial position of the active dial.
a. If using dry contact input - ensure contact closure
is connecting the proper terminals.
b. If using AC digital input - disconnect connector
from 2-speed control and measure voltage
between L1 and Neutral or L2 and Neutral.
b. AC digital input - this input allows an AC voltage
signal to be fed directly into the 2-speed control
to change speeds.
• Send 115-230V AC to L1 OR L2 for speed B.
• Send 115-230V AC to L1 AND L2 for speed A.
If no voltage is applied to either terminal, the
motor will be off.
c. DO NOT CONNECT BOTH DRY CONTACT AND
DIGITAL INPUTS SIMULTANEOUSLY.
2. To test fan operation before the external control
devices are installed, a jumper wire can be
connected between the COM and A or B terminal on
the dry contact input for fan operation.
®
Vari-Green Motor and Controls
9
Motorized Backdraft
Damper Control
Motorized Damper
Motorized damper operation
with Vari-Green® Control
(Motor/control wiring omitted for clarity)
The available factory mounted transformer
(PN 385253) has the ability to signal a
motorized back draft damper to open/close
as the motor starts/stops.
To control
To motor
A N.O./N.C. set of contacts is provided
which will change state when above or
below a control voltage of 1.85 VDC. See
wiring diagram for example.
Contact Rating:
• 10A @ 24-240 VAC
N.C.
COM
N.O.
COM
24V
0-10V
COM
24V
0-10V
• 5A @ 30 VDC
Auxiliary
Contact
Control
Motor
Trip Point = 1.85VDC
Contact Rating:
10A @ 24-240VAC
5A @ 30VDC
Green indicator light
—Power present
FACTORY MOUNTED
TRANSFORMER
Neutral
Line
(Damper Power Source)
Fans Where Dial on Motor
is Not Accessible
A control is available to mount on the outside of a fan
where the dial on motor may be difficult to access
(model SQ). This control is powered by the line voltage
entering the fan and will send 24 VDC and 0-10 VDC to
the motor. Control Part Number is 385611
Factory Wiring
Field Wiring
®
FACTORY MOUNTED
SPEED CONTROL
Voltage
Present
Input: 85-265VAC
Output: 24VDC, 0-10VDC
COM 24V 0-10V
*NOTE: Black wire not
used on some motors
Red
Black *
White
2x4
Junction
Box
115/230 VAC Input
to match motor name plate
10
Vari-Green Motor and Controls
®
Multiple Motors on One Control
See the table below for the recommended number of
motors to be driven from one controller. Note that the
controllers do not have the ability to distinguish between
more than one motor, therefore all motors will receive
the same control voltage. Control voltage must be wired
in parallel to all motors.
Controls
Max. Motor Quantity
Remote Dial
4
2-speed
6
Constant Pressure/Airflow
4
Temperature/Humidity
2
VOC
2
Maintenance
Vari-Green® motors use brushless technology with
sealed bearings. No routine maintenance is required
other than keeping any debris from accumulating on the
motor and controls.
Other Vari-Green® Control
Instruction Manuals
Description
Document Number
Indoor Air Quality - VOC
475407
Indoor Air Quality Temperature/Humidity
475573
Constant Pressure Control
474766
Generation 2 Constant
Pressure/Airflow Control
479653
®
Vari-Green Motor and Controls
11
Maximum RPM Table
SWD
This table will show the available motor and fan
combinations with the correlating maximum motor
RPM for each combination.
CUE/CW Max RPM Motor HP
60-90
1725
1/10
95
1725
1/6
99
1725
1/4
101
1725
1/4
1725
1/4
101HP
2500
1/2
1400
1/4
121
1725
1/2
1200
1/4
131
1450
1/2
1725
3/4
1000
1/4
1300
1/2
141
1550
3/4
1725
1
1450
1/4
141HP
1725
1/2
2200
3/4
1000
1/2
1200
3/4
161
1300
1
1725
2
1300
1/2
161HP
1650
3/4
1725
1
875
3/4
180
1000
1
1325
2
SQ
60-90
95
Max RPM Motor HP
1725
1/10
1725
1/6
1725
1/4
97
2500
1/2
1725
1/4
98
2200
3/4
1725
1/4
99
2200
3/4
100
1725
1/4
120
1725
1/2
130
1725
3/4
1250
1/4
130HP
1450
1/2
1950
3/4
1500
3/4
140
1725
1
1100
1/2
140HP
1450
3/4
1725
1
1140
3/4
160
1300
1
1725
2
850
1/2
1000
3/4
160HP
1600
1
1725
2
SFD
6
7.5
Max RPM Motor HP
1725
1/4
1725
1/2
7
8
10
13
15
16
18
Max RPM Motor HP
1725
1/4
2500
1/2
1725
1/4
2500
1/2
1725
1/4
2200
3/4
1200
1/4
1550
1/2
1725
3/4
1150
1/2
1400
3/4
1725
1
900
3/4
1300
1
1725
2
850
3/4
950
1
1300
2
SE1/SS1 Max RPM Motor HP
8-440*
1725
1/10
10-440*
1725
1/6
12-426
1725
1/4
12-432
1725
1/4
12-436
1725
1/4
14-432
1725
1/4
14-436
1725
1/2
14-440
1725
1/2
16-421
1725
1/2
16-426
1725
1/2
16-428
1725
3/4
16-436
1725
3/4
18-424
1725
3/4
18-429
1725
3/4
20-420
1725
1
G
60-90
95
97-99
103
103HP
123
133
143
143HP
163
183
LD/LDP
80-90
95
100
120
Max RPM Motor HP
1725
1/10
1725
1/6
1725
1/4
1725
1/4
1725
1/4
2500
1/2
1200
1/4
1725
1/2
1150
1/4
1550
1/2
1725
3/4
900
1/4
1200
1/2
1300
3/4
1725
1
1500
1/4
1725
1/2
2200
3/4
750
3/4
1200
1
1725
2
900
3/4
1000
1
1325
2
Max RPM Motor HP
1725
1/10
1725
1/6
1725
1/4
1725
1/2
SP/CSP Max RPM Motor HP
510
1200
1/6
710
1510
1/4
*SE1 Model Only
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.
Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the
Library under Warranties.
AMCA Publication 410-96, Safety Practices for Users and Installers of Industrial and Commercial Fans, provides additional safety
information. This publication can be obtained from AMCA International, Inc. at www.amca.org.
®
Phone: 715.359.6171 • Fax: 715.355.2399 • Parts: 800.355.5354 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com
12
473681 • Vari-Green Motor and Controls, Rev. 13, September 2017
Copyright 2017 © Greenheck Fan Corporation
Document 475699
Universal Vari-Green®
Control Assemblies
®
Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,
operate or maintain the product described. Protect yourself and others by observing all safety information. Failure
to comply with instructions could result in personal injury and/or property damage!
This document is for transformer/2-speed controller mounting only. Reference the Vari-Green Motor
Document No. 473681 for wiring details.
NOTE
There will be extra hardware and parts included
with this kit that may not be used for your specific
application.
Section 1
For Motor Part Numbers
309025
309026
310107
310359
311377
311388
312359
312360
312361
313233
313234
313235
316495
316496
316497
317706
317707
317708
End of Motor Mounting (Fig. 2)
For use on SE/SS Sidewall Prop units and SFD units
• Fasten transformer to mounting bracket via
(4) supplied screws (#10 x 1/2).
• Attach bracket to end of motor via motor thru bolts.
Fasten down with supplied nuts.
• For a SFD make sure transformer is mounted under
weatherhood.
Fan Housing Mounting
310306
311731
312362
314534
316498
317709
310307
311812
312619
314945
316499
Side of Motor Mounting (Fig. 1)
For use on SQ units
• Fasten transformer directly to outside of unit via
(4) supplied screws (#10 x 1/2).
For use on SWD units
• Fasten transformer to Drive Frame Angles
using the pre-exisiting holes and the (4) supplied
screws (#10 x ½)
For use on G, CUE, CW, LD, and LDP units
• Fasten transformer to mounting bracket via
(4) supplied screws (#10 x 1/2).
• Bend top of bracket away from transformer, by hand,
along laser stitched line, forming a 90 degree angle.
SWD-7 THRU 10
with transformer
and switch
• Attach bracket to top of motor via (2) motor thru-bolts.
Fasten down with supplied nuts.
Fig. 2
Fig. 1
®
Universal Vari-Green Control Assemblies
1
Section 2
For Motor Part Numbers
310420
311156
Drive Frame Mounting
For use on G, CUE and CW units
• Fasten transformer to
mounting bracket via
(4) supplied screws (#10 x 1/2).
• Bend top of bracket away from
transformer, by hand, along laser
stitched line, forming a
90 degree angle.
G/CUE with
transformer mounted
• Attach bracket to drive frame
angles, using the pre-exisiting
holes and the (2) supplied
screws (#10 x ½).
Fan Housing Mounting
For use on SQ units
• Fasten transformer directly to
outside of unit via (4) supplied
screws (#10 x 1/2).
For use on SWD units
• Fasten transformer to Drive
Frame Angles using the
pre-existing holes and the
(4) supplied screws (#10 x 1/2).
SWD-13
with transformer and switch
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.
Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the
Library under Warranties.
AMCA Publication 410-96, Safety Practices for Users and Installers of Industrial and Commercial Fans, provides additional safety
information. This publication can be obtained from AMCA International, Inc. at www.amca.org.
®
Phone: 715.359.6171 • Fax: 715.355.2399 • Parts: 800.355.5354 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com
2
475699 • Universal Vari-Green Control Assemblise, Rev. 4, February 2015
Copyright 2015 © Greenheck Fan Corporation
Document 481307
SP Fan with CRD
Plaster Flange Assembly
®
Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting to assemble,
install, operate or maintain the product described. Protect yourself and others by observing all safety
information. Failure to comply with instructions could result in personal injury and/or property damage!
Plaster Flange Assembly
Note: This plaster flange assembly is only
required when the damper is installed in a
combustible (wood) floor/ceiling assembly.
Figure 1
Tek Screws
14 PLCS
Plaster Flanges
When the damper is installed in a non-combustible
(steel/concrete) ceiling/floor assembly, the plaster
flange kit should be discarded.
CRD Damper
Plaster
Flanges
For applications where the damper is installed in a
combustible (wood) floor/ceiling assembly, the plaster
flanges must be installed onto the damper as shown
in Figure 1.
Width
Height
1. Note the orientation of the plaster flanges to the
damper as shown in Figure 1.
2. Align the edge of the short leg of the plaster flange
with the bottom edge of the damper frame and
center it along the length of the frame.
3. Clamp the plaster flange to the damper frame.
When the damper is installed in a combustible (wood)
floor/ceiling assembly, the flange will lay on top of the
drywall ceiling membrane; as shown in Figure 2.
4. Using the holes in the plaster flange as a guide,
secure the flange to the damper frame using the
supplied self-drilling Tek screws.
Figure 2
5. Repeat this process on all four sides of the damper.
1
2
5
6
4
3
4
1. Fan/Damper Assembly
2. Mounting Angle
3. Plaster Flange
4. Gypsum Board
5. Grille
6. RC Channel
5
®
Phone: 715.359.6171 • Fax: 715.355.2399 • Parts: 800.355.5354 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com
481307• SP Fan with CRD, Rev. 1, October 2015
Copyright 2015 © Greenheck Fan Corporation
PN 453380
RDC-8 - Duct Conversion
®
Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Report any damaged equipment to the
shipper immediately. Read carefully before attempting to assemble, install, operate or maintain the
product described. Protect yourself and others by observing all safety information. Failure to comply
with instructions could result in personal injury and/or property damage!
Removal of Original Rectangular Outlet:
Attachment of New Round Outlet:
1. Remove the four (4) sheet metal screws that hold
the duct connector to the blower box assembly
on the discharge side. Refer to Figure 1.
2. Attach the round duct connector to the blower
box assembly using the four (4) original sheet
metal screws. Refer to Figure 2.
Sheet
Metal
Screws
Discharge Side
Figure 1
Sheet
Metal
Screws
Figure 2
Discharge Side
Warranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period
of one year from the purchase date. Any units or parts which prove defective during the warranty
period will be replaced at our option when returned to our factory, transportation prepaid. Motors are
warranted by the motor manufacturer for a period of one year. Should motors furnished by Greenheck
prove defective during this period, they should be returned to the nearest authorized motor service
station. Greenheck will not be responsible for any removal or installation costs.
As a result of our commitment to continuous improvement, Greenheck reserves the right to change
specifications without notice.
Greenheck Catalogs for inline fans provides additional information describing the
equipment, fan performance, available accessories, and specification data.
®
AMCA Publication 410-96, Safety Practices for Users and Installers of Industrial
and Commercial Fans, provides additional safety information. This publication can
be obtained from AMCA International, Inc. at: www.amca.org.
Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com
453380 • RDC-8 Duct Conversion, Rev. 3, September 2008
Copyright 2008 © Greenheck Fan Corp
1
model FSD-142-OP
11/2 hour • UL class 2 — combination fire smoke damper
actuator in the airstream — out-of-partition
Maximum UL555S Rated Pressure: 4 in.wg. (1.0 kPa)
Maximum Temperature: 350°F (177°C)
Listings
Meets NFPA Standards: 90A, 92A, 92B and 101
E
AT
R
A
New York City MEA listing: 295-98-E
TIN
I SOF CALIFO G
E
TE
F IR
E MAR
SH
E
CSFM listing: 3225-0368:110 and 3230-0368:111
L
UL 555 and 555S listing: R11767
NI
Sleeve: 20 gauge (1.0) galvanized steel with 1" (25) flange and
factory installed thermal insulation on four sides.
Maximum Dynamic Closure Velocity: 2,000 fpm (10.2 m/s)
S
Blades: 6" ¥ 16 gauge (152 ¥ 1.5) galvanized steel — triple-V.
UL 555S Leakage Class: 2 [20 cfm/sq.ft. @ 4 in.wg.]
[(0.10 m3/s/m2 @ 1.0 kPa)]
A
ST
Frame: 5" ¥ 1" (127 ¥ 25) galvanized steel hat channel with
interlocking corner gusset. Equivalent to 13 gauge (2.4)
channel frame. Low profile head and sill are used on sizes
less than 13" (330) high.
UL 555 Fire Resistance Rating: 11/2 hour (vertical and horizontal)
ST
Standard Construction
Ratings
L
The FSD-142-OP combination fire smoke damper employs
triple-V blades for point-of-origin control of fire and smoke in
static and dynamic smoke management systems. These
specialty dampers are approved for installation with the closed
plane of the blades up to 141/2" (368) outside the fire rated
partition and come standard with the actuator in the airstream
allowing for direct service access from the face of the damper
through the HVAC grille. The FSD-142-OP is qualified to 2,000
ft/min (10.2 m/s) and 4 in.wg. (1.0 kPa) and may be installed in
vertical walls and partitions, or horizontally in floors or
assemblies with fire resistance ratings up to 2 hours.
AL
Application
R VI C
Meets Building Code Standards: IBC, NBC, NFPA, SBC and UBC
Axles: 1/2" (13) diameter plated steel hex.
Linkage: Concealed in frame.
Bearings: Stainless steel oilite, sleeve-type.
Seals: Silicone blade edge seals and flexible metal jamb seals.
Actuator: 120 VAC, power-open, spring-close, internal mount.
Fire Closure Device: HS-10 (electric actuators)
PFV (pneumatic actuators)
Fire Closure Temperature: 165°F (75°C).
Minimum Size: 10" ¥ 6" (254 ¥ 152)
Maximum Size: 36" ¥ 48" (914 ¥ 1219)
Options
Fire Smoke Dampers FSD142OP (1/2) November 2017
o Alternate actuator:
o External Mount
o Pneumatic
o 24 VAC o 230 VAC
o DRS-30 — Two temperature fire closure device.
(Includes PI-50 switch package)
o PI-50 — Dual position indicator switch package.
o Alternate factory installed sleeve:
Gauge: o 18 (1.3) o 16 (1.6) o 14 (2.0) o 10 (3.5)
o Transitions: o Round o Oval
o Duct connections: o 1" (25) S-clip
o DM25 o DM35 o WARD
o Alternate fire closure temperature:
o 212°F (100°C) o 250°F (121°C)
o 350°F (177°C).
Model FSD-142-OP
(standard)
*Standard sleeve O.D. including thermal
blanket wrap, is approximately 3/8" (9)
over nominal duct size. Standard sleeve
I.D. is approximately nominal duct size.
NOTE: The opening for the
damper assembly in the fire wall
must be sized appropriately. If
not, serious damage to the
thermal blanket wrap could occur
and this will nullify the U.L. rating.
Contact the factory if necessary
for additional information.
o Duct smoke detector factory mounted and wired:
o 2151 (0-3,000 fpm [0-15.2 m/s])
o Remote control stations:
o RCP-1 (single) o RCP-1K (single, key controlled)
o RCP-1M (single, momentary switch)
Information is subject to change without notice or obligation.
POTTORFF ®
5101 Blue Mound Road, Fort Worth, Texas 76106
NOTE: Dimensions in parentheses ( ) are millimeters.
www.pottorff.com
Actuator and Sleeve Dimensional Data
The drawings and corresponding table show the position of the damper when mounted in a
factory sleeve and the relative space required for a given actuator. The standard mounting
locations provide enough space for installation of retaining angles and duct connections.
Actuator
Model
X Dimension
Minimum
Damper Size (w x h)
FSTF120
10" (254)
(H < 15")
6" (152)
(H ≥ 15")
FSLF120/24
11" (279)
(H < 15")
6" (152)
(H ≥ 15")
(254 x 152)
FSNF120/24
14" (356)
(H < 18")
11" (279)
(H ≥ 18")
(254 x 254)
ML4115/8115
MS4209/8209
101/2" (267)
(H < 13")
71/2" (191)
(H ≥ 13")
(254 x 203)
331-4826
N/A
8" (203)
(H ≥ 20")
(254 x 508)
NOTE:
14-1/2"
(368)
Max.
10" x 6"
(254 x 152)
10" x 6"
10" x 10"
10" x 8"
10" x 20"
3-1/4"
(83)
X
5"
(127)
1. Damper may be rotated 180° to position actuator on right side.
2. For dimensions on actuators not shown above, contact factory.
3. If actuator is ordered with optional external mount, sleeve
flange should be ordered loose, for field assembly.
Sleeve Length
10" (254) + X
1-3/4"
(44)
3/4"
(19)
Airflow Performance Data
Pressure Loss vs. Velocity
Figure 5.2 — Ducted Inlet
Figure 5.5 Plenum Mount
Pressure drop testing was performed
in accordance with AMCA Standard
500-D using the three configurations
shown. All data has been corrected to
represent air density of 0.075 lb/ft.
Actual pressure drop in any ducted
HVAC system is a combination of
many elements. This information,
along with analysis of other system
influences, should be used to
estimate actual pressure losses for a
damper installed in a given HVAC
system.
5D
5D
6D
Ducted Inlet and Outlet
AMCA Figure 5.3 Illustrates a fully ducted
damper. This configuration represents the
lowest pressure drop of the three test
configurations because entrance and exit
losses are minimized by straight duct runs
upstream and downstream of the damper.
Ducted Inlet
AMCA Figure 5.2 Illustrates a ducted
damper exhausting air into an open area.
This configuration has a lower pressure
drop than Figure 5.5 because entrance
losses are minimized by a straight duct run
upstream of the damper.
Information is subject to change without notice or obligation.
POTTORFF ®
5101 Blue Mound Road, Fort Worth, Texas 76106
Plenum Mount
AMCA Figure 5.5 Illustrates a plenum
mounted damper. This configuration has
the highest pressure drop because of
extremely high entrance and exit losses
due to the sudden changes of area in the
system.
NOTE: Dimensions in parentheses ( ) are millimeters.
www.pottorff.com
Fire Smoke Dampers FSD142OP (2/2) November 2017
Figure 5.3 — Ducted Inlet and Outlet
I N STALL AT ION &
O PERATIO N MANUAL
SINGLE DUCT
TERMINAL
Redefine your comfort zone. ™ | www.titus-hvac.com
IOM
S IN G LE DUC T T E RMI N A L
IM P ORTAN T !
R EAD B E F O R E P R O C E E DI N G !
G E NE R A L S AFE T Y G U ID E L IN E S
This equipment is a relatively complicated apparatus. During installation,
operation maintenance or service, individuals may be exposed to certain
components or conditions including, but not limited to: refrigerants, UV,
materials under pressure, rotating components, and both high and low
voltage. Each of these items has the potential, if misused or handled
improperly, to cause bodily injury or death. It is the obligation and
responsibility of operating/service personnel to identify and recognize
these inherent hazards, protect themselves, and proceed safely in
completing their tasks. Failure to comply with any of these requirements
could result in serious damage to the equipment and the property in
which it is situated, as well as severe personal injury or death to
themselves and people at the site.
This document is intended for use by owner-authorized operating/
service personnel. It is expected that these individuals possess
independent training that will enable them to perform their assigned
tasks properly and safely. It is essential that, prior to performing any
task on this equipment, this individual shall have read and understood
this document and any referenced materials. This individual shall also
be familiar with and comply with all applicable governmental standards
and regulations pertaining to the task in question.
Safety Symbols
The following symbols are used in this document to alert the reader to areas of potential hazard:
danger
caution
indicates an imminently hazardous situation which, if not avoided,
will result in death or serious injury.
identifies a hazard which could lead to damage to the machine,
damage to other equipment and or environmental pollution.
Usually an instruction will be given, together with a brief explanation.
warning
note
indicates a potentially hazardous situation which, if not avoided,
could result in death or serious injury.
2
IOM - Single Duct Terminal
is used to highlight additional information which may be
helpful to you.
Redefine your comfort zone. ™ | www.titus-hvac.com
C HA NGE A BI L IT Y OF T H IS D OCU M E N T
In complying with Titus’ policy for continuous product improvement, the
information contained in this document is subject to change without
notice. Titus makes no commitment to update or provide current
information automatically to the manual owner. Updated manuals, if
applicable, can be obtained by contacting the nearest Titus office or
accessing the Titus website.
CHANGE BARS
Revisions made to this document are indicated with a line along the left
or right hand column in the area the revision was made. These revisions
are to technical information and any other changes in spelling, grammar
or formatting are not included.
Operating/service personnel maintain responsibility for the applicability of
these documents to the equipment. If there is any question regarding the
applicability of these documents, the technician should verify whether the
equipment has been modified and if current literature is available from the
owner of the equipment prior to performing any work on the unit.
Redefine your comfort zone. ™ | www.titus-hvac.com
IOM - Single Duct Terminal
3
IOM
S IN G LE DUC T T E RMI N A L
Table of Contents
General Safety Guidelines...............................................................................................................................................2
Safety Symbols................................................................................................................................................................2
Changeability of this Document......................................................................................................................................3
Table of Contents.............................................................................................................................................................4
Figure(s) .........................................................................................................................................................................4
Table(s) .........................................................................................................................................................................4
Section 1
Receiving Inspection.......................................................................................................................................................5
Supporting the Assembly................................................................................................................................................5
Duct Connections............................................................................................................................................................5
Field Wiring......................................................................................................................................................................6
Control Start-up, Operation.............................................................................................................................................6
Calibration Instructions...................................................................................................................................................6
Replacement Parts...........................................................................................................................................................6
Figure(s)
Figure 1 - Single Duct Recommended Hanger Bracket Locations...............................................................................5
Table(s)
Table 1 - Replacement Parts..........................................................................................................................................6
4
IOM - Single Duct Terminal
Redefine your comfort zone. ™ | www.titus-hvac.com
Section 1
Receiving Inspection
After unpacking the terminal, check it for shipping damage. If any shipping
damage is found, report it immediately to the delivering carrier. Store units
in a clean, dry location prior to installation.
Also, inspect damper rotation of the unit by rotating the damper by hand
to check for free movement, and ensure there is no damage or binding of
the damper. If controls are connected to the damper, release the manual
clutch (most controls are equipped with this) and rotate the damper by
hand. If there is any restriction to the rotation of the damper, contact your
Titus rep and inform them of this issue.
caution
Do not use the flow sensor, connecting tubing, or damper
shaft linkage as a handle to lift or move assembly. Damage
to the flow sensor or controls may result.
Supporting the Assembly
The diameter of the inlet duct “D” in inches must be equal to the listed size
of the terminal; e.g. a duct that actually measures 8 inches must be fitted
to a size 8 terminal. The inlet collar of the terminal is made 1/8 inch smaller
than listed size in order to fit inside the duct (see Figure 1).
note
Do not insert duct work inside the inlet collar of the
assembly.Inlet duct should be installed in accordance
with SMACNA guidelines.
The outlet end of the terminal is designed for use with slip and drive
duct connections. A rectangular duct the size of the terminal outlet
should be attached.
Inspect the Aerocross inlet flow sensor for shipping damage, and
ensure that the high (green) and low (red) tubes are attached. Provide
at least 1½times the inlet duct diameter of straight duct for optimum
control accuracy. For more information on our Aerocross, see the
Aerocross Flow Sensor Application Guide.
AssemblyMany basic single duct terminals are
light enough to be supported by the duct work
itself. Where heavier accessory modules, such as
DDC controls, coils, attenuators, or multiple outlets
are included, the terminal should be supported
directly. Straps screwed directly into the side of the
terminal, threaded rod through the optional hanger
brackets (see Figure 1), or the method prescribed
for the rectangular duct on the job specifications
may be used.
Important: If equipped with pneumatic controls,
the terminal must be mounted right side up. It must
be level within+ or -10 degrees of horizontal, both
parallel to the air flow and at the right angle of air
flow. The control side of the terminal is labeled with
an arrow indicating UP. The first letter of the model
number (P) indicates pneumatic controls. Most
electronic units (A-analog controls and D-digital
controls) can be installed in any orientation. Check
with the local TITUS representative for verification.
Duct Connections
Slip each inlet duct over the inlet collar of the terminal.
Fasten and seal the connection by the method
prescribed by the job specification.
Redefine your comfort zone. ™ | www.titus-hvac.com
Figure 1 - Single Duct Recommended Hanger Bracket Locations
IOM - Single Duct Terminal
5
IOM
S IN G LE DUC T T E RMI N A L
Section 1 - General Information
Field Wiring
All field wiring must comply with the local codes and with the National
Electrical Code (ANSI/NFPA 70-1981). Electrical, control and piping
diagrams are shown on the exterior labeling or on the diagram on the
inside of control enclosure cover. All electric heaters if provided by TITUS
are balanced by kW per stage. The installing electrician should rotate these
heater stages by phase in order to help balance the building electric load.
Control Start-up, Operation
Detailed information regarding power, accessory and communications
connections, start-up and operating procedures for the controls
provided by TITUS are available from your local TITUS representative.
For specific information on controls by other manufacturers, contact that
manufacturer’s local branch or dealer.
Important: Units with digital controllers may incorporate specific
communication addresses based on Building Management Systems
Architecture, and original engineering drawings. Installing the
terminal in a different location than noted on unit label may result in
excessive start-up labor.
Calibration Instructions
Size 4-5-6”
Size 7”
Size 8”
Size 9”
Size 10”
Size 12”
Size 14”
Size 16”
31171301
31171302
31171303
31171304
31171305
31171306
31171307
31171308
Damper Shaft Extension
Short Stub all sizes
Long Ext. Sz. 4-6, 14, 16
Long Ext. Sz. 7-12
Shaft Bearing - All
70300301
70300302
70300303
70324901
Control Tube
Red Stripe 1/4” O.D.
Green Stripe 1/4” O.D.
Red Stripe 3/8” O.D.
Green Stripe 3/8” O.D.
Yellow Stripe 1/4” O.D.
White Stripe 1/4” O.D.
Blue Stripe 1/4” O.D.
Plastic 1/4"
Plastic 3/8”
For Analog Controls: Titus TA1, see ANA-IOM:
Analog Controller Calibration.
61510035
61510234
61510279
61510280
61510260
61510261
61510262
42150011
42150020
Plugs for tees
1/4"
3/8”
For Digital Controls:
see control manufacturer’s manualReplacement
42160081
10015601
AeroCross™ Multipoint Velocity Sensors
Table 1 - Replacement Parts
IOM - Single Duct Terminal
Part Number
Tees for sensor taps
For Pneumatic Controls, see PNEU-IOM:
Operations Manual for Pneumatic Controls.
6
Description
Primary Damper Assembly
Size 4"
Size 5”
Size 6”
Size 7”
Size 8”
Size 9”
Size 10”
Size 12”
Size 14”
Size 16”
Size 24” x 16”
3151520001
3151520001
3151520002
3151520003
3151520004
3151520005
3151520006
3151520007
3151520008
3151520009
3151520009
Redefine your comfort zone. ™ | www.titus-hvac.com
Notes
Redefine your comfort zone. ™ | www.titus-hvac.com
IOM - Single Duct Terminal
7
605 Shiloh Rd
Plano TX 75074
ofc: 972.212.4800
fax: 972.212.4884
Redefine your comfort zone. ™ | www.titus-hvac.com
Download