Installation and Maintenance Manual IM 1139-8 Group: WSHP Document PN: 910191715 Date: September 2016 SmartSource® Horizontal Water Source Heat Pump Model GSH - Single Stage Horizontal Unit (Sizes 007-070) Model GTH - Two-Stage Horizontal Unit (Sizes 026-072) Contents Model Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 General Information . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Information for Initial Start-up . . . . . . . . . . . . . . . . . . 39 Safety, Receiving and Storage . . . . . . . . . . . . . . . . . . 6 Check, Test & Start Procedure . . . . . . . . . . . . . . . . . 39 Pre-Installation Checklist . . . . . . . . . . . . . . . . . . . . . . 6 Typical Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . 40 Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 MicroTech III Unit Control with BACnet Communication Module (HGRH) - 265-277V, 1-Phase . . . . . . . . . . . 40 System Applications . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Water Loop Application . . . . . . . . . . . . . . . . . . . . . . . 8 Ground-Loop Application . . . . . . . . . . . . . . . . . . . . . . 8 Ground-Water Application . . . . . . . . . . . . . . . . . . . . 10 Water System Quality . . . . . . . . . . . . . . . . . . . . . . . . 12 Supply & Return Piping . . . . . . . . . . . . . . . . . . . . . . 14 Discharge Air Conversion . . . . . . . . . . . . . . . . . . . . . 15 Hanger Brackets . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Ductwork and Attenuation . . . . . . . . . . . . . . . . . . . . 18 Duct Location Dimensions . . . . . . . . . . . . . . . . . . . . 19 Return Air Filter Rack Assembly & Duct Collar Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Unit Piping and Electrical Connections Dimensions 20 Waterside Economizer Piping Connections . . . . . . . 21 Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . 22 GSH/GTH Unit With Non-Fused Disconnect Switch 23 Line Voltage Electrical Connections With Disconnect – 115-460V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Low Voltage Wire Connections . . . . . . . . . . . . . . . . 24 Typical Connections For Thermostats & Temperature Sensors Applications . . . . . . . . . . . . . . . . . . . . . . . . 25 Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Condensate Drain Connection . . . . . . . . . . . . . . . . . 28 Cleaning & Flushing System . . . . . . . . . . . . . . . . . . 29 Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Jumper Configuration Settings . . . . . . . . . . . . . . . . 32 MicroTech® III SmartSource Unit Controller . . . . . . . 33 MicroTech SmartSource Controller with LonWorks® Communication Module . . . . . . . . . . . . . . . . . . . . . . 34 MicroTech III Unit Control with BACnet Communication Module (WSE & DSH) - 208-230V, 1-Phase with 115V Loop Pumps and 20kW Electric Heat . . . . . . . . . . . 41 MicroTech III Unit Control with LonWorks Communication Module . . . . . . . . . . . . . . . . . . . . . . 42 208-230V, 3-Phase with 230V Loop Pumps and 5kW Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 MicroTech III Unit Control with BACnet Communication Module (WSE) 460V, 3-Phase with 230V Loop Pumps and 20kW Electric Heat . . . . . . . . . . . . . . . . . . . . . . 43 MicroTech III Unit Control with Hydronic Heat (HYH) – 208-230V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 Motor Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Typical Refrigeration Cycles . . . . . . . . . . . . . . . . . . . 46 Operating Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Motorized Isolation Valve . . . . . . . . . . . . . . . . . . . . . 48 MicroTech III Unit Control with BACnet Communication Module (HGRH)- 265-277V, 1-Phase, Service & Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 MicroTech III Unit Control with BACnet Communication Module (WSE & DSH) Service & Disconnect - 208230V, 1-Phase with 115V Loop Pumps and 20kW Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 MicroTech III Unit Control with LonWorks Communication Module Service & Disconnect 208230V, 3-Phase with 230V Loop Pumps and 5kW Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 MicroTech III Unit Control with BACnet Communication Module (WSE) Service & Disconnect - 460V, 3-Phase with 230V Loop Pumps and 20kW Electric Heat . . . 52 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 MicroTech SmartSource Controller with BACnet® General Maintenance . . . . . . . . . . . . . . . . . . . . . . . . 53 Communication Module . . . . . . . . . . . . . . . . . . . . . . 34 Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 Constant Torque EC Motor . . . . . . . . . . . . . . . . . . . . 35 Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 Constant CFM Type EC Motor Fan Settings . . . . . . 36 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 Fan Performance For Constant CFM EC Motor (Sizes 015–072) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Water Source Heat Pump Equipment Check, Test and Start Form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 Fan Speed Selector Switch . . . . . . . . . . . . . . . . . . . 38 Fan CFM Settings & Performance . . . . . . . . . . . . . . 38 www.DaikinApplied.com 3 IM 1139-8 Model Nomenclature 2-3 4 5-7 8 9 10 11-12 13 14 14 15 17 19 20 24 25 26 27 28 29 W GS 1 H 007 B 1 E E 4 B A C S B 3 A E P B GL L Product Category W - Water Source Heat Pump Control Secondary Heat Type B - Boilerless Electric Heat E - Emergency Electric Heat P - Primary Electric Heat (No Heat Pump Heating) S - Supplemental Heat Y - None P - Control for Electric Heat, Single 24V Signal (Field-installed Duct Heater by others) Y - None Model Type GS - High Efficiency Single Stage *GT - High Efficiency Two Stage Configuration H - Horizontal Nominal Capacity 007, 009, 012, 015, 019, 024, *026, 030, *032, 036, *038, 042, *044, 048, *049, 060, *064, 070, *072 Electric Heating P - Control for Electric Heat, Single 24V Signal (Field-installed Duct Heater by others) Y - None Unit Control B - MicroTech III SmartSource Unit Controller Design Series (Vintage) 1 - Revision / Design Series 1 WSE E - Waterside Economizer Y - None Voltage A - 115/60/1 (007-015) E - 208-230/60/1 (007-072) F - 208-230/60/3 (024-072) J - 265/60/1 (007-036) K - 460/60/3 (024-072) Filter Type A - Disposable E - Merv 8 Factory-Installed G - Merv 13 (4-inch thick) Factory-Installed Y - None Range for Entering Water/Glycol Temp. GW -Ground Water WL- Water Loop GL - Groune Loop Filter Rack 2 - 4-Sided, 2" w/Duct Collar & Door 3 - 4-Sided, 2" w/Duct Collar, Door, Hi-Merv Seal 4 - 4-Sided, 4" w/Duct Collar, Door, Hi-Merv Seal Y - None Return Air Location L - Left-Hand Return & Right-Hand Piping R - Right-Hand Return & Right-Hand Piping Communication Module B - BACnet L - LonWorks Y - None Discharge Air Location E - End (Horizontal Unit Only) S - Straight (Horizontal Unit Only) Fan Motor 4 - ECM Constant CFM 5 - ECM Constant Torque Primary Air Coil Option S - Standard E - E-Coated Coaxial Heat Exchanger Construction (Supply Liquid / Refrigerant) C = Copper Inner Tube - Steel Outer Tube S = Cupronickel Inner Tube - Steel Outer Tube Sound Package Y - None A - Premium Dehumidification Option B - Hot Gas Reheat Smart Dehumidification (Unit Sizes 015-070) C - Simplified Dehumidification (Lower CFM no HGRH or no Humidistat) D - Humidistat Controlled Dehumidification (No HGRH) E - Humidistat Only Y = None IM 1139-8 4 www.DaikinApplied.com Model Nomenclature 31-32 33 1S Y 34 41 45 47 48 49 51 53 54 56 60 62 63 82 B A S B B S B A C S B 3 A E Loop Pump 1S - One Low Head 230 Volt Pump 1L - One High Head 230 Volt Pump 2S - Two Low Head 230 Volt Pumps 2L - Two High Head 230 Volt Pumps 3S - One Low Head 115 Volt Pump 4S - Two Low Head 115 Volt Pumps YY - None 1E Alarm Relay A - Alarm Relay (Dry Contacts) Y - None Expansion Device A - Thermal Expansion Valve Thermal Bulb Auto Flow Control 4.0 GPM Auto Flow Control 5.0 GPM Auto Flow Control 6.0 GPM Auto Flow Control 8.0 GPM Auto Flow Control 9.0 GPM Auto Flow Control 10.0 GPM Auto Flow Control 11.0 GPM Auto Flow Control 12.0 GPM Auto Flow Control 13.0 GPM Auto Flow Control 15.0 GPM Auto Flow Control 18.0 GPM None and Equalizer Tube Thermostat/Sensor Control T - Thermostat Control S - Sensor Control Control Transformer 1 - 50VA Control Transformer 2 - 75VA Control Transformer Disconnect Switch Y - None N - Non-Fused Fan Motor Control C - Various Speeds with 4 Adjustment Settings Water Coil Piping Package Options (Hot Water or Waterside Economizer) A - 3-Way Motorized - 24V Valve Control, NO to Coax Cabinet Color Y =None W = Off White T - Textured Charcoal Bronze Primary Drain Pan Material S - Stainless Steek Compressor Insulation B - Compressor Insulation Sound Blanket (024-072) Y - None Cabinet Finish A - Powder Coat Y - None Insulation - Piping A - Insulated Piping Y = None Compressor Isolation B - Isolated base Unit Cabinet Insulation S - 1/2" Fiberglass Skin-Face in Compressor Section, 1/2" Fiberglass Foil-Face Insulation in Airside Section I - Indoor Air Quality Insulation Package 3/8" Closed Cell Foam in Compressor Section, 3/8" Closed Cell Foam Insulation in Airside Section R - Sound Reduction Package – 3/4" Sound Insulation in Compressor Section and Air Section (Unit Sizes 007 - 019)* 1/2" Fiberglass Skin-Face in Compressor Section with Compressor Sound Blanket, 3/4" Sound Insulation in Airside Section (Unit Sizes 024 - 072) www.DaikinApplied.com FF Freeze Fault FF - Freeze Fault Protection YY - None Coaxial Coil Supply Liquid Auto Flow Reg A - Auto Flow Control 1.5 GPM B - Auto Flow Control 2.0 GPM C - Auto Flow Control 2.5 GPM D - Auto Flow Control 3.0GPM - C Extended Warranty, Parts Only YY - None 1E - 1-Year, Entire Unit Parts Only 2C - 2-Year Parts (Compressor Only) 2R - 2-Year Parts (Refrigerant Circuit) 3C - 3-Year Parts (Compressor Only) 3R - 3-Year Parts (Refrigerant Circuit) 4C - 4-Year Parts (Compressor Only) 4R - 4-Year Parts (Refrigerant Circuit) Coaxial Coil Supply Liquid Flow Control B - 2-Way, Motorized - 24v Valve Control, NO Y - None E G H I J K L M N P S Y 83 90-91 105-106 5 IM 1139-8 General Information Safety, Receiving and Storage CAUTION Sharp edges can cause personal injury. Avoid contact with them. Upon receipt of the equipment, check carton for visible damage. Make a notation on the shipper’s delivery ticket before signing. If there is any evidence of rough handling, immediately open the cartons to check for concealed damage. If any damage is found, notify the carrier within 48 hours to establish your claim and request their inspection and a report. The Warranty Claims Department should then be contacted. For storing, each carton is marked with “up” arrows. The unit should be shipped or stored in the normal upright position. Do not operate the machine until it has been in the normal upright position for at least 24 hours. Temporary storage at the job site must be indoor, completely sheltered from rain, snow, etc. Units should not be installed in environments that fall below freezing or exceed 140°F ambient. IMPORTANT This product was carefully packed and thoroughly inspected before leaving the factory. Responsibility for its safe delivery was assumed by the carrier upon acceptance of the shipment. Claims for loss or damage sustained in transit must therefore be made upon the carrier as follows: VISIBLE LOSS OR DAMAGE Any external evidence of loss or damage must be noted on the freight bill or carrier’s receipt, and signed by the carrier’s agent. Failure to adequately describe such external evidence of loss or damage may result in the carrier’s refusal to honor a damage claim. The form required to file such a claim will be supplied by the carrier. CONCEALED LOSS OR DAMAGE Concealed loss or damage means loss or damage which does not become apparent until the product has been unpacked. The contents may be damaged in transit due to rough handling even though the carton may not show external damages. When the damage is discovered upon unpacking, make a written request for inspection by the carrier’s agent within fifteen (15) days of the delivery date and file a claim with the carrier. Pre-Installation Checklist Check all that apply: □ □ □ To prevent damage, do not operate this equipment for supplementary ventilation, heating and cooling during the construction period. Inspect the carton for any specific tagging numbers indicated by the factory per a request from the installing contractor. Check the unit data plate for correct voltage, phase and capacity with the plans before installing the equipment. Also, make sure all electrical ground connections are made in accordance with local code. Table 1: Operating Voltages Voltage Minimum Maximum 115/60/1 103 126 208-230/60/1 197 253 265/60/1 238 292 208-230/60/3 197 253 460/60/3 414 506 Note: Three-phase system imbalance shall not exceed 2%. □ □ □ □ □ □ □ If 460/60/3 unit includes a constant CFM EC motor verify that a 4-wire power supply is provided that includes a neutral wire providing 265 volt power to the fan motor. Check the unit size against the plans to verify that the unit is being installed in the correct location. Before installation, check the available ceiling height versus the height of the unit. Note the location and routing of water piping, condensate drain piping, and electrical wiring. The locations of these items are clearly marked on submittal drawings. The installing contractor will find it beneficial to confer with piping, sheet metal, and electrical foremen before installing any unit. The contractor shall cover the units to protect the machines during building construction. This is critical while spraying fireproofing material on bar joists, sandblasting, spray painting and plastering. If plastic film is not available, the shipping carton may be modified to cover the units during construction. Remove shipping brackets securing unit to skid. WARNING The installer must determine and follow all applicable local and national codes and regulations. This equipment presents hazards of electricity, rotating parts, sharp edges, heat and weight. Failure to read and follow these instructions can result in property damage, severe personal injury or death. This equipment must be installed by experienced, trained personnel only. IM 1139-8 6 www.DaikinApplied.com Physical Data Table 2: Unit sizes 007 through 032 Unit Sizes 007 through 032 Description Compressor Type 007 009 012 015 019 024/026 030/032 Rotary Rotary Rotary Rotary Rotary Scroll Scroll Refrigeration Charge (Oz.) 26 26 29 42 42 56 54 Fan Wheel (D x W) 6" x 8" 6" x 8" 6" x 8" 9" x 7" 9" x 7" 9" x 7" 9" x 7" Fan Motor HP 1/10 1/10 1/10 1/3 1/3 1/3 1/2 Water Connection Size (FPT) 1/2" 1/2" 1/2" 3/4" 3/4" 3/4" 3/4" Coax & Water Piping Volume (Gal. @ 70ºF) 0.2 0.2 0.2 0.5 0.5 0.5 0.5 Condensate Connection Size (FPT) 3/4 3/4 3/4 3/4 3/4 3/4 3/4 Air Coil Face Area (Sq Ft.) 2.1 2.1 2.1 2.5 2.5 4.1 Waterside Economizer Coil Volume (Gal.) 0.64 0.85 4.1 1.28 Filter Size 15.5" x 20.0" 15.5" x 20.0" 15.5" x 20.0" 18.0" x 20.0" 18.0" x 20.0" 16.75" x 34" 16.75" x 34" Operating Weight 148 151 154 200 214 254 256 Shipping Weight 165 168 171 214 228 289 291 Table 3: Unit sizes 036 through 072 Unit Sizes 036 through 072 Description 036/038 042/044 048/049 060/064 070/072 Scroll Compressor Type Scroll Scroll Scroll Scroll Refrigeration Charge (Oz.) 72 90 88 120 122 Fan Wheel (D x W) 11" x 10" 11" x 10" 11" x 10" 11" x 10" 11" x 10" Fan Motor HP 1/2 3/4 3/4 1 1 Water Connection Size (FPT) 3/4" 1" 1" 1" 1" Coax & Water Piping Volume (Gal. @ 70ºF) 1.1 1.2 1.2 2.1 2.1 Condensate Connection Size (FPT) 3/4 3/4 3/4 3/4 3/4 Air Coil Face Area (Sq Ft.) 5.0 5.6 5.6 Waterside Economizer Coil Volume (Gal.) 1.59 6.4 6.4 1.84 2.09 Filter Size 18.75" x 37.25" 18.75" x 42.62" 18.75" x 42.62" 18.75" x 48" 18.75" x 48" Operating Weight 329 365 367 472 478 Shipping Weight 361 408 410 514 521 Table 4: Horizontal unit corner weights, percentage of total operating weight (Base unit only) 007 148 009 151 012 154 015 200 019 214 024/026 254 030/032 256 036/038 329 042/044 365 048/049 367 060 472 070/072 478 www.DaikinApplied.com Corner Weight % of Total Operating Weight A B C D D C Water Connections Compressor 30% 20% 20% 30% B 7 Unit Front Total Operating Weight (lbs.) Control Box Unit Size A IM 1139-8 System Applications Water Loop Application Commercial systems typically include a number of units connected to a common piping system. Any unit plumbing maintenance work can introduce air into the piping system; therefore air elimination equipment is a major portion of the mechanical room plumbing. In piping systems expected to utilize water temperatures below 50°F [10°C], closed cell insulation is recommended on all piping surfaces to eliminate condensation (extended range units required). Metal to plastic threaded joints should never be used due to their tendency to leak over time. All SmartSource units include flush mounted FPT water connections integral to the unit corner post, which do not require a backup wrench. A thread sealant is recommended to minimize internal fouling of the heat exchanger. Do not over tighten connections and route piping so as not to interfere with service or maintenance access. Hose kits are available from Daikin in different configurations for connection between the unit and the piping system. Depending upon selection, hose kits may include shut off valves, P/T plugs for performance measurement, high pressure stainless steel braided hose, “Y” type strainer with blow down valve, and/or “J” type swivel connection. Balancing valves and an external low pressure drop solenoid valve for use in variable speed pumping systems may also be included in the hose kit. The piping system should be flushed to remove dirt, piping chips, and other foreign material prior to operation (see "Cleaning & Flushing System" on page 29. The water flow rates should be kept at approximately 3 GPM per nominal cooling ton (a 10°F temperature rise in cooling). To ensure proper maintenance and servicing, P/T ports are imperative for temperature and flow verification, as well as performance checks. Water loop heat pump (cooling tower/boiler) systems typically utilize a common loop, maintained between 60 90°F [16 - 32°C]. The use of a closed circuit evaporative cooling tower with a secondary heat exchanger between the tower and the water loop is recommended. If an open type cooling tower is used continuously, chemical treatment and filtering may be necessary. Ground-Loop Application CAUTION The following instructions represent industry accepted installation practices for closed loop earth coupled heat pump systems. Instructions are provided to assist the contractor in installing trouble free ground loops. These instructions are recommendations only. State/provincial and local codes MUST be followed and installation MUST conform to ALL applicable codes. It is the responsibility of the installing contractor to determine and comply with ALL applicable codes and regulations. CAUTION Ground loop applications require extended range equipment and optional refrigerant/water circuit insulation. Pre-Installation Prior to installation, locate and mark all existing underground utilities, piping, etc. Install loops for new construction before sidewalks, patios, driveways, and other construction has begun. During construction, accurately mark all ground loop piping on the plot plan as an aid in avoiding potential future damage to the installation. Piping Installation The typical closed loop ground source system is shown in Figure 2 on page 9. All earth loop piping materials should be limited to polyethylene or equivalent per International Ground Source Heat Pump Association (IGSHPA) Figure 1: Polyethylene fused piping Galvanized or steel fittings should not be used at any time due to their tendency to corrode. All plastic to metal threaded fittings should be avoided due to their potential to leak in earth coupled applications. A flanged fitting should be substituted. P/T plugs should be used so that flow can be measured using the pressure drop of the unit heat exchanger. IM 1139-8 8 www.DaikinApplied.com System Applications Figure 2: Typical water loop application (with optional unit-mounted loop pumps) Supply & Return To Ground Loop Piping Power Disconnect Line Voltage Wiring Loop Fluid Temperature Gauges Low Voltage Wiring Factory Mounted Loop Pumps Shutoff Ball Valves with P/T Ports Flexible Hoses Earth loop temperatures can range between 25 and 110°F [-4 to 43°C]. The water flow rates should be kept at approximately 3 GPM per nominal cooling ton (a 10°F temperature rise in cooling). Test individual horizontal loop circuits before backfilling. Test vertical U-bends and pond loop assemblies prior to installation. Pressures of at least 100 psi [689 kPa] should be used when testing. Do not exceed the pipe pressure rating. Test entire system when all loops are assembled. Calculate the total volume of fluid in the piping system. Then use the percentage by volume shown in Table 6 on page 10 for the amount of antifreeze needed. Antifreeze concentration should be checked from a well mixed sample using a hydrometer to measure specific gravity. Figure 3: Flushing the loop Flushing the Earth Loop Upon completion of system installation and testing, flush the system to remove all foreign objects and purge to remove all air. Antifreeze In areas where minimum entering loop temperatures drop below 50°F [10°C] or where piping will be routed through areas subject to freezing, antifreeze is required. Alcohols and glycols are commonly used as antifreeze; however your local sales office should be consulted to determine the antifreeze best suited to your area. Freeze protection should be maintained to 15°F [9°C] below the lowest expected entering loop temperature. For example, if 30°F [-1°C] is the minimum expected entering loop temperature, the leaving loop temperature would be 22 to 25°F [-6 to -4°C] and freeze protection should be at 15°F [-10°C]. Calculation is as follows: 30°F - 15°F = 15°F [-1°C - 9°C = -10°C]. All alcohols should be premixed and pumped from a reservoir outside of the building when possible or introduced under the water level to prevent fumes. www.DaikinApplied.com 9 IM 1139-8 System Applications Table 5: Antifreeze percentage by volume Minimum Temperature for Low Temperature Protection Type Note: 1 10°F [-12.2°C] 15°F [-9.4°C] 20°F [-6.7°C] 25°F [-3.9°C] Methanol 25% 21% 16% 10% 100% USP food grade Propylene Glycol 38% 25% 22% 15% Ethanol1 29% 25% 20% 14% Must not be denatured with any petroleum product. Table 6: Antifreeze correction factors (for heat pump operation only) Antifreeze % By Weight 15% 25% 35% 45% Ethanol Cooling Capacity 0.985 – – – Heating Capacity 0.9825 – – – Pressure Drop 1.04 – – – Ethylene Glycol Cooling Capacity 0.9935 0.9895 0.985 0.981 Heating Capacity 0.9865 0.9795 0.973 0.965 Pressure Drop 1.10 1.16 1.22 1.27 Methanol Cooling Capacity 0.985 – – – Heating Capacity 0.9825 – – – Pressure Drop 1.04 – – – Propylene Glycol Cooling Capacity 0.985 0.975 0.965 0.955 Heating Capacity 0.981 0.9685 0.952 0.936 Pressure Drop 1.11 1.20 1.31 1.40 Ground-Water Application Open Loop - Ground Water Systems - Typical open loop piping is shown in Figure 4. Shut off valves should be included for ease of servicing. Boiler drains or other valves should be installed in the supply and return lines to allow cleaning of the heat exchanger. Shut off valves should be positioned to allow flow through the coax via the boiler drains without allowing flow into the piping system. P/T plugs should be used so that pressure drop and temperature can be measured. Piping materials should be limited to copper. WARNING PVC or CPVC should not be used as they are not compatible with the POE oils used in HFC-410A products and piping system failure and property damage may result. IM 1139-8 Water quantity should be plentiful and of good quality. See "Water impurities, result & recommended water system application" on page 13 for water quality guidelines. The unit can be ordered with either a copper or cupro-nickel water heat exchanger. Consult Table 8 on page 13 for recommendations. Copper is recommended for open loop ground water systems that are not high in mineral content or corrosiveness. In conditions anticipating heavy scale formation or in brackish water, a cupro-nickel heat exchanger is recommended. In ground water situations where scaling could be heavy or where biological growth such as iron bacteria will be present, an open loop system is not recommended. Heat exchanger coils may over time lose heat exchange capabilities due to build up of mineral deposits. Heat exchangers must only be serviced by a qualified technician, as acid cleaning and special pumping equipment may be required. 10 www.DaikinApplied.com System Applications Figure 4: Typical open loop application Boiler Drains Return Supply Shutoff Valve Flow Regulator Optional (Field-Installed) Water Control Valve Supply from Loop Optional Filter Power Disconnect Water Hose Valves with P/T Plugs Water Quality Standards - Table 8, Water impurities, result & recommended water system application" on page 13 should be consulted for water quality requirements. Scaling potential should be assessed using the pH/Calcium hardness method. If the pH <7.5 and the calcium hardness is less than 100 ppm, scaling potential is low. If this method yields numbers out of range of those listed, the Ryznar Stability and Langelier Saturation indices should be calculated. Use the appropriate scaling surface temperature for the application, 150°F [66°C] for direct use (well water/ open loop); 90°F [32°F] for indirect use. A monitoring plan should be implemented in these probable scaling situations. Other water quality issues such as iron fouling, corrosion prevention and erosion and clogging should be referenced in Table 8 on page 13. Expansion Tank and Pump - Use a closed, bladder type expansion tank to minimize mineral formation due to air exposure. The expansion tank should be sized to provide at least one minute continuous run time of the pump using its draw-down capacity rating to prevent pump short cycling. Discharge water from the unit is not contaminated in any manner and can be disposed of in various ways, depending on local building codes (e.g. recharge well, storm sewer, drain field, adjacent stream or pond, etc.). Most local codes forbid the use of sanitary sewer for disposal. Consult your local building and zoning department to assure compliance in your area. www.DaikinApplied.com 11 Water Control Valve - Note the placement of the water control valve in Figure 4. Always maintain water pressure in the heat exchanger by placing the water control valve(s) on the return line to prevent mineral precipitation during the off-cycle. Pilot operated slow closing valves are recommended to reduce water hammer. If water hammer persists, a mini-expansion tank can be mounted on the piping to help absorb the excess hammer shock. If a field provided motorized valve and actuator is utilized, ensure that the total ‘VA’ draw of the valve can be supplied by the unit transformer. For instance, a slow closing valve can draw up to 35VA. Units are furnished with a factory-installed 50 VA transformer. An optional 75VA transformer is also available. A typical pilot operated solenoid valve draws approximately 15VA (see Figure 45 on page 48). IM 1139-8 System Applications Flow Control - Flow control can be accomplished by two methods. One method involves simply adjusting the field-provided ball valve or flow control valve on the return line. Measure the pressure drop through the unit heat exchanger, and determine flow rate from Table 7. Since the pressure is constantly varying, two pressure gauges may be needed. Adjust the valve until the desired flow of 1.5 to 4 gpm, per ton [5.7 to 15.1 l/m, per kW] is achieved. A second method of flow control requires a flow control device mounted on the outlet of the flow control valve. This device is typically a brass fitting with an orifice of rubber or plastic material that is designed to allow a specified flow rate. On occasion, flow control devices may produce velocity noise that can be reduced by applying some back pressure from the ball valve located on the discharge line. Slightly closing the valve will spread the pressure drop over both devices, reducing the velocity noise. Table 7: Water pressure drop Unit Size 007 009 012 015 019 024/026 030/032 036/038 042/044 048/049 IM 1139-8 GPM Pressure Drop, psi (kPa) 50ºF 70ºF 90ºF 1.0 0.7 1.6 0.7 1.5 1.4 3.0 1.3 2.0 2.2 4.8 2.0 1.9 2.0 1.9 1.8 2.3 2.7 2.6 2.5 3.4 3.4 3.3 3.2 2.0 5.1 2.1 2.0 3.0 9.7 4.1 3.9 4.0 15.4 6.4 6.2 2.5 1.2 1.1 1.1 3.8 2.6 2.5 2.4 5.0 4.5 4.3 4.2 3.8 2.5 2.4 2.3 4.5 3.6 3.4 3.3 5.3 4.9 4.7 4.5 4.0 1.1 1.0 1.0 6.0 2.3 2.2 2.1 8.0 3.9 3.7 3.6 5.0 1.6 1.6 1.5 7.5 3.4 3.3 3.2 10.0 5.8 5.5 5.3 6.0 1.9 1.8 1.8 9.0 4.0 3.9 3.7 12.0 6.8 6.5 6.3 7.0 1.0 1.0 0.9 10.5 2.1 2.1 2.0 14.0 3.7 3.5 3.4 10.0 2.0 1.9 1.8 12.0 2.8 2.6 2.5 14.0 3.7 3.5 3.4 060/064 070/072 10.0 2.0 2.0 1.9 15.0 4.4 4.2 4.1 20.0 7.7 7.3 7.1 15.0 4.4 4.2 4.1 18.0 6.3 6.0 5.8 21.0 8.4 8.1 7.8 Water System Quality The cleaning, flushing and chemical treatment of a water source heat pump system is fundamental to efficient operation and the life expectancy of the system. Potential system problems produced by the use of water fall into three general categories: 1. Scale formation – Mineral deposits which result from the crystallization and precipitation of dissolved salts in the water. The deposits form an insulating barrier, reducing the heat transfer rate and impeding the circulation of fluids due to increased pressure drop. 2. Corrosion – Decomposition of the metal caused by absorption of gases from the air. Corrosion may occur in any metal component of the system. 3. Organic growths – Slime and algae which form under certain environmental conditions, and can reduce the heat transfer rate by forming an insulating coating or can promote corrosion by pitting. The system water should be evaluated for degrees of impurity, with testing available from independent testing labs, health departments or state agencies. Table 8 on page 13 is a list of water characteristics, the potential impurities and their results and the recommended treatment. Avoiding Potential Problems As shown in Table 8 on page 13, all water contains some degree of impurities which may affect the performance of a heat pump system. The use of a cupronickel coil can help avoid potential problems. Water flow rates should: • Be high enough that the temperature rise through the heat exchanger does not exceed 12° F when operating in the cooling mode. • 12 Not exceed 4 GPM per nominal ton. Flow rates that have velocities of 10 feet per second or more may cause pipe erosion and heat exchanger failure. www.DaikinApplied.com System Applications Table 8: Water impurities, result & recommended water system application Impurity Copper Coils Cupro-nickel Coils Calcium & Magnesium Salts (hardness) Less than 350 ppm 350 ppm Sea Water Iron oxide Low levels only Moderate levels pH 7-9 5 – 10 Hydrogen Sulfide Less than 10 ppm 10 – 50 ppm CO2 Less than 50 ppm 50 – 75 ppm Chloride Less than 300 ppm 300 – 600 ppm Total Dissolved Solids Less than 1000 ppm 1000 – 1500 ppm Slime & Algae Slime and algae can form under certain environmental conditions Result Scaling Corrosion Reduced heat transfer due to forming of insulating coating, or pitting due to corrosion Application Open Recirculating 1. Bleed-off 2. Surface active agents such as polyphosphates. 3. Addition of acid. 4. pH adjustment. Other considerations: ▪ Adequate fouling factor ▪ Surface temperature ▪ Water temperature ▪ Clean system 1. Corrosion inhibitors in high concentrations (200 to 500 ppm). 2. Corrosion inhibitors in low concentrations (20 to 80 ppm). 3. pH control. 4. Proper materials of construction. Chlorinated phenols. Other biocides. Chlorine by hypochlorites or by liquid chlorine Closed Recirculating No treatment required Corrosion inhibitors in high concentrations. Proper materials of construction. No treatment required Notes: 1. The tremendous variety in water quality around the country makes the recommendation of a single best method of treatment impossible. Consult a local water treatment specialist for specific treatment recommendations. 2. Cupro-nickel is recommended if iron bacteria is high, suspended solids or dissolved oxygen levels are high. 3. If the concentration of these corrosives exceeds the maximum tabulated in the cupro-nickel column, then the potential for serious corrosion problems exists. www.DaikinApplied.com 13 IM 1139-8 System Applications Supply & Return Piping Pre-Installation Considerations All units should be connected to supply and return piping in a two-pipe reverse return configuration. A reverse return system is inherently self-balancing and requires only trim balancing where multiple quantities of units with different flow and pressure drop characteristics exist in the same loop. A direct return system may also work acceptably, but proper water flow balancing is more difficult to achieve and maintain. • The piping can be steel or copper. Note: Polyolester Oil, commonly know as POE oil is a synthetic oil used in many refrigeration systems. POE oil, if ever in contact with PVC/CPVC will coat the inside wall of PVC/CPVC pipe causing environmental stress fractures. It is recommended that PVC/CPVC piping is not used in the installation of the loop system, as system failure and property damage could result. Supply and return runouts usually join the unit via short lengths of high pressure flexible hose which are sound and vibration isolators for both unit operating noise and hydraulic pumping noise. • One end of the hose should have a swivel fitting to facilitate removal for service. Note: 1. No unit should be connected to the supply and return piping until the water system has been cleaned and flushed completely, see "Cleaning & Flushing System" on page 29. After the cleaning and flushing has taken place, the initial connection should have all valves wide open in preparation for water system flushing. 2. Hard piping is not recommended since no vibration or noise attenuation can be accomplished. 3. Supply and return shutoff valves are required at each unit. The return valve can be used for balancing. When used it should have a “memory stop” so that it can be closed off, and reopened to the proper position for the required flow. 4. Do not over-torque fittings. The maximum torque without damage to fittings is 30 foot pounds. If a torque wrench is not available, use as a rule of thumb, finger tight plus one quarter turn. Figure 5: Example of a reverse return piping system IM 1139-8 14 www.DaikinApplied.com System Applications Discharge Air Conversion Installation Considerations 1. Locate the unit in conditioned space and avoid installation in corrosive environments. Allow clearance for easy removal of the filter and access panels, and enough space for service personnel to perform maintenance or repair. 2. Remove the Styrofoam shipping block under the fan housing before start-up. Figure 6. 3. Make sure that sufficient access has been provided for installing and removing the unit, including clearance for duct collars and fittings at water and electrical connections (see Figure 10). A straight discharge unit may be converted to an end discharge by doing the following: Note: The information covered in this section of the blower assembly orientation is typical of Daikin units. Regardless, if you are changing end to straight or straight to end the blower assembly has to turn 90 degrees and simultaneously rotate 180 degrees to achieve the proper orientation. Not all Daikin units will have the same air discharge location but will have the same general results when following the instructions. DANGER 4. Unit condensate drains are not internally trapped. External trap is required. Allow adequate room around the unit for condensate piping. Hazardous Voltage! Disconnect all electric power including remote disconnects before servicing. Failure to disconnect power before servicing can cause severe personal injury or death. 5. If the unit is installed in a confined space, provisions must be made for return air to freely enter the face of the unit’s air coil. Figure 6: Horizontal unit foam shipping block CAUTION Sharp edges can cause personal injury. Avoid contact with them. 6. Turn off power to the unit at the breaker box. 7. Remove the top panel by removing the screws around the perimeter of the top securing it to the lower cabinet (Figure 7 on page 15). Remove foam shipping block Note: Retain all screws for reinstalling. 8. Remove the access panel to the fan motor by loosening the two (2) screws at the bottom holding the panel (Figure 7 on page 15). Remove the piece of insulation at the bottom on the side of the bottom panel. Figure 7: Remove top and access panel to fan motor Remove Top Remove screws around the perimeter of top Remove Access Panel to Fan Assembly Fan Discharge Panel Assembly (Bottom-Horizontal Orientation) Remove two (2) screws at bottom of access panel to access fan motor www.DaikinApplied.com 15 IM 1139-8 System Applications Discharge Air Conversion (Continued) 10. Secure the fan assembly to the unit frame with the screws removed previously. Remove the screws securing the fan discharge panel assembly (Figure 7). 9. Lift the fan assembly out rotating it 180 degrees and position it within the opening at the end of the unit (Figure 8). With the fan motor in the end discharge position the fan and housing orientation is tophorizontal. In a straight air discharge arrangement the housing is in the bottom-horizontal orientation. 11. Reinstall the access panel in the fan motor access opening (Figure 9 on page 16). 12. Reinstall the top panel and secure with screws removed previously. Note: If installed correctly the fan motor should be accessible when the fan motor access panel is removed. Figure 8: Lift out the fan assembly, turn 90 degrees and rotate 180 degrees Rotate the Fan Assembly 180 degrees End Discharge Arrangement (Top-Horizontal) Orientation Position the fan assembly in the end opening with the fan in the “top-horizontal” orientation Straight Discharge Arrangement (Bottom-Horizontal) Orientation Remove screws securing the fan assembly to the cabinet. Note bottom-horizontal orientation of fan assembly Figure 9: Reinstall the top and access panel Reinstall Top Reinstall Access Panel to Fan Motor IM 1139-8 16 www.DaikinApplied.com System Applications Figure 10: Recommended minimum & optimum unit clearances Hanger Brackets Figure 12: Hanger bracket details (sizes 007-019) Figure 11: Hanger bracket locations - sizes 026-072 3/8" Threaded Rod (By Others) X Y Bolt & Lock Washer Vibration Isolator Washer Hex Nuts (Double) (By Others) W Table 9: Hanger bracket location dimensions, in inches (mm) Unit Size W X Y 007, 009, 012 44.67 (1135) 23.60 (599) 19.10 (485) 015, 019 50.06 (1272) 24.40 (620) 19.90 (505) 024, 026, 030, 032 62.16 (1579) 23.90 (607) 18.64 (474) 036, 038 72.16" (1833) 27" (686) 21.24" (539) 042, 044, 048 77.57" (1970) 27" (686) 21.24" (539) 060, 064, 070, 072 82.97" (2107) 27" (686) 21.24" (539) Figure 13: Heavy-duty hanger brackets (sizes 024-072) 3/8" Threaded Rod (By Others) Heavy-Duty Bracket Note: All dimensions within ± 0.10 inches (2.5 mm). Vibration Isolator Bolt & Lock Washer Hex Nuts (Double) (By Others) Horizontal unit sizes 024 through 072 are provided with heavy-duty hanger brackets, fastening bolts, vibration isolators and washers. Do not subsitute these brackets for others, for unit sizes 024 through 072. 3/8" threaded rods and hex nuts (doubled) are provided by others. www.DaikinApplied.com 17 IM 1139-8 System Applications WARNING Clearance should be maintained to meet local and national code requirements. Figure 14: Typical ducting of horizontal unit Acoustically Insulated Return Air Duct Trunk Duct Room Air Supply Diffuser Flexible (Boot) Connector Acoustically Insulated Duct (approximately 10') Trunk Duct Tee Branch Duct Room Air Supply Diffuser Branch Duct Room Air Supply Diffuser Ductwork and Attenuation Discharge ductwork is normally used with these conditioners. Return air ductwork may also be required. All ductwork should conform to industry standards of good practice as described in the ASHRAE Systems Guide. A field supplied discharge duct system will normally consist of: • a flexible connector at the unit • a 10 ft. length of insulted duct • and a trunk duct teeing into a branch duct with discharge diffusers as shown in Figure 14 With metal duct material, the entire branch duct should be internally lined with acoustic fibrous insulation for sound attenuation. Glass fiber duct board material is more absorbing and may permit omission of the flexible boot connector. As a general recommendation, the acoustic fibrous insulation should be at least 1/2 inch thick over the entire duct run (Figure 14). For better sound attenuation, line the last five diameters of duct before each register IM 1139-8 with a one-inch thick sound blanket. Elbows, tees and dampers can create turbulence or distortion in the airflow. Place a straight length of duct, 5 to 10 times the duct width, before the next fitting to smooth out airflow. Diffusers that are located in the bottom of a trunk duct can also produce noise. For this same reason, volume control dampers should be located several duct widths upstream from an air outlet. For Hotel, Motel, Dormitory or Nursing Home applications that use a single duct discharge, a velocity of 500 to 600 fpm is suggested. These applications typically have static pressures as low as 0.05 inches of water and duct lengths approximately six feet in length. The discharge duct must be fully lined and have a square elbow without turning vanes. Return air for these applications should enter through a “low” sidewall filter grille and route up the stud space to a ceiling plenum. For horizontal heat pumps mounted from the ceiling, an insulated return plenum is sometimes placed at the return air opening to further attenuate line-of-sight sound transmission through return openings. 18 www.DaikinApplied.com Installation Duct Location Dimensions Figure 15: Discharge duct collar location P P FM AP FM AP O O R R Q G G Left Return - End Discharge Q Right Return - End Discharge FM AP O Front N P N M M Left Return - Straight Discharge View Legend: Front O P Right Return - Straight Discharge View FM AP = Fan Motor Access Panel Table 10: Discharge duct collar dimensions, in inches (mm) Discharge Air Duct Connection in inches (mm) GSH Horizontal Unit M 007, 009, 012 015, 019 N O P Q 8.09 (206) 4.89 (124 ) 9.45 (240) 5.75 (146) 3.15 (80) 10.46 (266) 9.33 (237) 4.41 (112) 6.20 (157) 2.71 (69) 10.39 (264) 4.88 (124) 4.74 (120) 2.81 (71) 13.75 (349) 4.88 (124) 4.74 (120) 2.81 (71) 13.75 (349) 4.88 (124) 4.74 (120) 2.81 (71) 13.75 (349) Left-hand Right-hand 6.18 (157) 4.25 (108) 4.64 (118) 024, 026, 030, 032 036, 038 042, 044, 048, 049 060, 064, 070, 072 R Left-hand Right-hand 6.12 (156) 8.09 (206) 4.25 (108) 4.63 (118) 3.15 (80) 5.75 (146) 9.32 (237) 4.41 (112) 2.71 (69) 6.20 (157) 13.25 (337) 4.88 (124) 2.81 (71) 4.74 (120) 13.25 (337) 4.88 (124) 2.81 (71) 4.74 (120) 13.25 (337) 4.88 (124) 2.81 (71) 4.74 (120) Note: All duct dimensions are referenced from the outside edge of the flange. Figure 16: Return air duct collar location .839" (21.3 mm) ZH .839" (21.3 mm) * 2.10" (53 mm) See Note 2.125" (54 mm) ZW .839" (21.3 mm) .839" (21.3 mm) .839" (21.3 mm) Table 11: GSH horizontal unit 2" (51mm) filter rack assembly & duct collar dimensions, in inches (mm) Unit Size Dimension Note: 007, 009, 012 015, 019 024, 026, 030, 032 ZH 13.91 (353) 16.49 (419) 15.45 (392) 17.45" (443) 17.45 (443) 17.45 (443) ZW 19.35 (491) 23.38 (594) 32.51 (826) 35.76" (908) 41.15" (1045) 46.55" (1182) 036, 038 042, 044, 048, 049 060, 064, 070, 072 * Optional 4" filter rack = 4.10" (104 m www.DaikinApplied.com 19 IM 1139-8 Installation Return Air Filter Rack Assembly & Duct Collar Connections Return air ductwork can be connected to the standard filter rack, see Figure 16 on page 19. The unit comes standard with a 2" (51mm) thick factory-installed throwaway filter, mounted in a 4-sided combination filter rack and return air duct collar. Filters can be easily removed from either side by interchanging the removable filter door to the right or left side and rotating the filter rack assembly 180 degrees. Do not use sheet metal screws directly into the unit cabinet for connection of supply or return air ductwork, especially return air ductwork which can hit the drain pan or the air coil. Unit Piping and Electrical Connections Dimensions Figure 18: Piping & electrical connections locations Line Voltage (3/4" Conduit Connection) Low Voltage (1/2" Conduit Connection) C AP Figure 17: Filter rack filter door removal L K E D J H F Front View Threaded access door knobs Filter rack Filter access door Ventilation Air Ventilation may require outside air. The temperature of the ventilation air must be controlled so that mixture of outside air and return air entering the conditioner does not exceed conditioner application limits. It is also typical to close off the ventilation air system during unoccupied periods (night setback). The ventilation air system is generally a separate building subsystem with distribution ductwork. Simple introduction of the outside air into each return air plenum chamber reasonably close to the conditioner air inlet is recommended. Do not duct outside air directly to the conditioner inlet. Provide sufficient distance for thorough mixing of outside and return air. See "Operating Limits" on page 48. 11/16" G Condensate Drain End View Legend: C AP = Control Access Panel Table 12: Piping & electrical connections dimensions, in inches (mm) Piping Connections in inches (mm) GSH / GTH Horizontal Unit D E Electrical Connections in inches (mm) K L F Condensate Drain 3/4" FPT G H Low Voltage J Between Line Voltage Supply Return Supply & Return Connections FPT 007, 009, 012 2.65 (67) 5.65 (144) 1/2" 1.47 (37) 3.76 (96) 1.98 (50) 2.08” (53) 7.06 (179) 9.14 (232) 9.14 (232) 015, 019 2.95 (75) 5.95 (151) 3/4" 1.47 (37) 4.07 (103) 1.98 (50) 2.08 (53) 7.06 (179) 024, 026, 030 2.58 (66) 13.39 (340) 3/4" 1.57 (40) 4.29 (109) 1.94 (49) 2.57 (65) 7.36 (187) 9.93 (252) 036, 038 2.76 (70) 13.57 (345) 3/4" 1.57 (40) 4.36 (111) 1.94 (49) 3.57 (91) 8.23 (209) 11.81 (300) 042, 044, 048, 049, 3.07 (78) 13.88 (353) 1" 1.57 (40) 4.36 (111) 1.94 (49) 3.57 (91) 8.23 (209) 11.81 (300) 060, 064, 070, 072, 3.07 (78) 13.88 (353) 1" 1.57 (40) 4.36 (111) 1.94 (49) 3.57 (91) 8.23 (209) 11.81 (300) IM 1139-8 20 www.DaikinApplied.com Installation Waterside Economizer Piping Connections Figure 19: Waterside economizer unit descriptions WSE return Water return Unit condensate drain connection Factory installed internal 3-way motorized valve access WSE supply *WSE condensate drain connection Field installed jumper hose (reference Daikin hose kit option # 8 for recommended sizes) Water supply Note: *The economizer package incorporates its own drain pan to collect condensate from the coil. This pan MUST be independently trapped and piped into the drain line for the heat pump. Figure 20: Waterside economizer piping location dimensions GSH / GTH Horizontal Unit Supply & Return Connections Unit Size A Condensate Connections B C FPT D E FPT F 007, 009, 012 3.50 9.29 6.36 1/2" 1.38 4.25 22.58 015, 019 3.50 10.88 6.89 3/4" 0.88 4.25 24.94 024, 026, 030, 032 3.36 9.38 7.23 3/4" 1.70 4.25 036, 038 2.94 14.07 7.42 3/4" 1.70 4.25 042, 044, 048, 049 2.94 14.07 7.42 1" 1.70 4.25 33.65 060, 064, 070, 072 2.94 14.07 7.42 1" 1.70 4.25 33.67 www.DaikinApplied.com 21 3/4" 27.19 33.93 IM 1139-8 Electrical Connections Electrical Connections Figure 21: Route line voltage wires to terminal screws. 5 WARNING 4 All field installed wiring must comply with local and national electric codes. This equipment presents hazards of electricity, rotating parts, sharp edges, heat and weight. Failure to read and follow these instructions can result in property damage, severe personal injury or death. This equipment must be installed by experienced, trained personnel only. 3 CAUTION Fasteners should not be screwed into and penetrate the unit enclosure to avoid damage to internal electrical and mechanical components. 2 1 WARNING Use copper conductors only. Conductors must be minimum 75°C. Table 13: Operating voltages Voltage Minimum Maximum 115/60/1 103 126 208-230/60/1 197 253 265/60/1 238 292 208-230/60/3 197 253 460/60/3 414 506 Note: Three-phase system imbalance shall not exceed 2%. • Use a short length of flexible conduit at the unit connection to minimize and isolate vibration to the building. All conduit should be supported to avoid contact with unit cabinet or immediate building structure to prevent unnecessary noise. CAUTION Note: Units without constant EC motor will not include a neutral conductor. For clarity, not all unit wires are shown in the unit line voltage connection area. Line Voltage – 115V 1. Route line voltage supply wiring through the upper 1-1/8" diameter electrical knockout in the left corner post. Figure 22. 2. Continue to route wires into the control box. 3. Connect and wire nut the supply wires to provided unit leads as shown in Figure 22. 4. Secure ground wire to (green) ground screw. Figure 22: Line voltage wiring route to wire connections All electrical connections should be checked for tightness as they may come loose during shipment. Line Voltage – 208-230, 460 Note: 460V units require a neutral conductor. See Figure 21. 1. Route line voltage supply wiring through the upper 1-1/8" diameter knockout in the left corner post. 1 2. Remove and discard the factory provided stripped wire leads from the bottom unit contactor screw terminals (not shown). 3. Connect the field supplied wires to the lower contactor screw terminals as shown in Figure 21. 3 4. Twist neutral wires and wire nut (460V units only) 5. Connect ground wire to provided (green) ground screw 2 230 Volt Operation All 208-230 volt single-phase and three-phase units are factory wired for 208 volt operation. For 230 phase operation, the line voltage tap on the 24 volt transformer must be changed. Disconnect and cap the red lead wire and interchange it with the orange lead wire on the primary of the 24 volt transformer IM 1139-8 4 22 www.DaikinApplied.com Electrical Connections GSH/GTH Unit With Non-Fused Disconnect Switch Line Voltage Electrical Connections With Disconnect – 115-460V Figure 23: Unit with optional non-fused disconnect switch 3/4" dia. Conduit Connection When units are equipped with the optional non-fused disconnect switch, the line voltage supply is brought in through the top of the junction box. Disconnect location and dimension details are provided in Figure 23. Note: *460V units require a neutral conductor. See #6 in Figure 24. 1. Remove screws from the top and bottom locations on the disconnect switch cover. 2. These are the factory-installed wires from the switch to the line voltage terminals in the unit control box. 3. Connect wires to the upper unused terminals. 4. Tighten terminal screws to secure wires. Right-Hand Unit - Front View 5. Connect ground wire to provided green ground screw. 6. Twist and wire nut field provided neutral conductor. Replace cover and secure with screws. 3/4" dia. Conduit Connection Figure 24: 460V wiring with neutral wire to the non-fused disconnect switch 1 Left-Hand Unit - Front View 3 5 Table 14: Letter dimensions for Figure 23. Unit Size 007, 009, 012 015, 019 024, 026, 030, 032 A *6 16-1/4"" 17-3/4" 036, 038, 042, 044 048, 049, 060, 064, 070, 072 4 B 1-1/2" 19-1/4" 2 1 www.DaikinApplied.com 23 IM 1139-8 Electrical Connections Low Voltage Wire Connections Figure 25: Low voltage wiring route & connections Procedure Note: 1. Never install relays coils in series with the thermostat inputs. 2. Units equipped with HGRH and using thermostat control require installation of a factory supplied return air sensor connected to H9 terminal. See Figure 29 on page 25 for details. 1. Remove front access panel to allow access to the control box. 3 2. Route the field-supplied low voltage wiring through the lower knockout in the left corner post and into the control box section as shown in Figure 25. 2 3. Secure the low voltage wire connections to the main board terminals on TB2 3 4. Secure wire to TB1-1 on the I/O expansion module. 5. Reinstall the access panel after connections are complete and wire terminals have been checked for tightness. 2 4 Figure 26: Terminal connections to TB1 (sensor control) on the MTIII board IM 1139-8 24 www.DaikinApplied.com Electrical Connections Typical Connections For Thermostats & Temperature Sensors Applications Figure 29: Units that utilize thermostat control, a factory supplied return air sensor connects to the H9 terminal. Figure 27: Wiring example for two-stage thermostat with electrical heat and hot gas reheat. (Y2 connection on Microtech III controller should be used to achieve rated capacity) I/O Expansion Module TB1 A O A TB3 E 2 1 R Y1 Y2 W1 W2 Y2 G G Y1 C O R W2 MicroTech III Controller Terminals TB2 U Yellow H9 terminal on MicroTech III controller C RC RH G Y Y2 W1 W2 W3 W4 D/A L Figure 30: Return Air Temperature sensor (RAT) locations Programmable Touch Screen (Part No. 910121750) Note: Terminal TB1-1 is used for optional dehumidification or WSE operation. Figure 28: Wiring example of typical heat/cool thermostat connections (Part No.s 910121746 and 910121748) MicroTech III Controller Terminals TB1 O A G A 1 R Y2 G W1 Y1 W2 Y2 Y1 C O R W2 MicroTech III Controller Terminals TB2 2 3 4 5 Suggested Location for RAT Sensor (Ducted Applications) (See Caution below) Suggested Location for RAT Sensor (Non-ducted) (See Caution below) CAUTION R C W1 Y1 W2 Y2 G A L When an optional wall-mounted room temperature sensor is connected to the unit controller, the Return Air Temperature (RAT) sensor must not be installed. A wall-mounted room temperature sensor and the return air temperature sensor must not be connected simultaneously or the unit will not operate properly. O Typical Heat/Cool Thermostat (Part No. 910121746 & 910121748) Note: When remote reset of a lockout condition is required at the wall thermostat, it will be necessary to utilize a conductor between terminal "O" on the wall thermostat to "TB1 terminal 4" on the MicroTech III unit controller (non-programmable stat only). www.DaikinApplied.com 25 Note: For single stage operation wire Y1 from thermostat to Y2 terminal on the Microtech III control board. IM 1139-8 Electrical Connections Figure 31: Basic room sensor wiring MicroTech III Controller Terminals TB1 1 1 2 2 3 3 4 4 Figure 33: Room sensor with temperature adjustment wiring MicroTech III Controller Terminals TB1 5 1 2 3 4 5 1 2 3 4 5 5 Basic Room Sensor (Part No.s 669529001, 910152149) Room Sensor with Temperature Adjustment (Part No. 669529101, 669529201, 910121753) Figure 32: Example wiring of SmartSource MicroTech III board to basic temperature sensor wiring MicroTech III Controller Terminals TB1 1 2 3 4 5 1 2 3 4 5 Basic Room Sensor with Cool to Warm Adjustment (Part No. 910171464) IM 1139-8 26 www.DaikinApplied.com Electrical Connections Figure 34: Digitally adjustable room temperature sensor wiring MicroTech III Controller Terminals TB1 A R 3 4 5 Y1 Y2 W1 W2 Y2 G G Y1 C O R W2 MicroTech III Controller Terminals TB2 R 1 2 O A 1 6 E 2 3 4 MicroTech III Controller Terminals TB3 5 E U U Digitally Adjustable Room Temperature Sensor (Part No. 910152147) Figure 35: Digitally adjustable room temperature and humidity sensor wiring A 1 R O A W2 Y2 Y1 Y2 W1 W2 Y1 G G C O R MicroTech III Controller Terminals TB3 MicroTech III Controller Terminals TB1 MicroTech III Controller Terminals TB2 2 3 4 5 E U I/O Expansion Module Terminals TB1 1 R 1 2 3 4 5 6 E U 2 DH Digitally Adjustable Room Temperature Sensor (Part No. 910121754) Note: Terminal TB1-1 is used for optional dehumidification operation. www.DaikinApplied.com 27 IM 1139-8 Piping Condensate Drain Connection A field provided condensate trap must be installed on each water source heat pump. Condensate removal piping must be pitched away from the unit not less than 1/4" per foot. The vent should extend at least 1-1/4" above the unit condensate fitting. A vent is required after the trap so that the condensate will drain away from the unit. The vent can also act as a clean out if the trap becomes clogged. To avoid having waste gases entering the building, the condensate drain should not be directly piped to a drain/waste/vent stack. See local codes for the correct application of condensate piping to drains Figure 36: Unit condensate drain pipe trap detail 1-1⁄2" (38mm) 2. Do not locate any point in the drain system above the condensate drain connection of any unit. It may be necessary to manually fill the trap at system startup, or to run the unit for sufficient time to build a condensate seal. The condensate trap and condensate piping drainage should be free of any foreign debris. Debris can prevent proper drainage and unit operation and result in condensate buildup. Optional Field- Installed Vent 1⁄4" Per Foot (21mm Per Meter) 1-1⁄2" (38mm) Note: Improper trapping can lead to several problems. If the trap is too tall, negative pressure will prevent drainage, causing condensate backup. If the trap is too short the seal will be destroyed or nonexistent, producing the same effect as a nontrapped system. 1. Each water source heat pump is provided with a 3/4" FPT flush mount fitting for connection of a condensate drain. A complete copper or PVC condensate system can be used. Copper or steel condensate piping should be insulated to prevent sweating. In most applications the use of PVC prevents sweating of condensate drain. Figure 37: Unit condensate drain pipe detail with waterside economizer option Vent Unit Drain To building drain Vent Waterside Economizer Drain IM 1139-8 28 www.DaikinApplied.com Piping Cleaning & Flushing System 3. Shut off supplemental heater and circulator pump and open all drains and vents to completely drain down the system. Short circuited supply and return runouts should now be connected to the conditioner supply and return connections. Do not use sealers at the swivel flare connections of hoses. 1. Prior to first operation of any conditioner, the water circulating system must be cleaned and flushed of all construction dirt and debris. If the conditioners are equipped with water shutoff valves, either electric or pressure operated, the supply and return runouts must be connected together at each conditioner location. This will prevent the introduction of dirt into the unit. See Figure 38. 4. Trisodium phosphate was formerly recommended as a cleaning agent during flushing. However, many states and localities ban the introduction of phosphates into their sewage systems. The current recommendation is to simply flush longer with warm 80°F (27°C) water. Figure 38: Supply & return runouts connected together Return Runout Supply Runout Mains Flexible Hose Runouts Initially Connected Together 2. Fill the system at the city water makeup connection with all air vents open. After filling, close all air vents. The contractor should start main circulator with the pressure reducing valve open. Check vents in sequence to bleed off any trapped air, ensuring circulation through all components of the system. Power to the heat rejector unit should be off, and the supplementary heat control set at 80°F (27°C). While circulating water, the contractor should check and repair any leaks in the piping. Drains at the lowest point(s) in the system should be opened for initial flush and blowdown, making sure city water fill valves are set to make up water at the same rate. Check the pressure gauge at pump suction and manually adjust the makeup to hold the same positive steady pressure both before and after opening the drain valves. Flush should continue for at least two hours, or longer if required, to see clear, clean drain water. www.DaikinApplied.com 29 5. Refill the system with clean water. Test the water using litmus paper for acidity, and treat as required to leave the water slightly alkaline (pH 7.5 to 8.5). The specified percentage of antifreeze may also be added at this time. Use commercial grade antifreeze designed for HVAC systems only. Do not use automotive grade antifreeze. Once the system has been filled with clean water and antifreeze (if used), precautions should be taken to protect the system from dirty water conditions. Dirty water will result in system wide degradation of performance and solids may clog valves, strainers, flow regulators, etc. Additionally, the heat exchanger may become clogged which reduces compressor service life or causes premature failure. 6. Set the loop water controller heat add setpoint to 70°F (21°C) and the heat rejection setpoint to 85°F (29°C). Supply power to all motors and start the circulating pumps. After full flow has been established through all components including the heat rejector (regardless of season) and air vented and loop temperatures stabilized, each of the conditioners will be ready for check, test and startup, air balancing, and water balancing. IM 1139-8 Controls Table 15: MicroTech III SmartSource unit controller terminals & descriptions TB2 – 8 O Thermostat – Heat Stage #3 (W3) Input TB2 – 9 C 24 VAC Common H1 – 1 24 24 VAC Power Input TB3 – 1 E Emergency Shutdown Input H1 – 2 C 24 VAC common TB3 – 2 U Unoccupied Input H2 – 1 SL1 Fan Main Required Output – Switched L1 L1 – 1 L1 - 1 Line Voltage Terminal 1 Blank Terminal L1 – 2 L1 - 2 Line Voltage Terminal 2 Fan Main Required Output – Neutral L1 – 3 L1 - 3 Line Voltage Terminal 3 H3 – 1 HP1-1 Comp High Pressure Switch (HP1) Input Terminal 1 N1 N1 Neutral Terminal 1 H3 – 2 HP1-2 Comp High Pressure Switch (HP1) Input Terminal 2 N2 N2 Neutral Terminal 2 N3 N3 Neutral Terminal 3 H2 – 2 H2 – 3 H4 – 1 N 1 Discharge Air Temp Sensor – Common H4 – 2 Discharge Air Temp Sensor – Signal H4 – 3 Leaving Water Temp Sensor – Common H4 – 4 Leaving Water Temp Sensor – Signal H5 – 1 1 I/O expansion module connectors/terminals H1 – 1 H5 – 2 H1 – 3 H5 – 3 H1 – 4 H5 – 4 H1 – 5 H5 – 5 H1 – 6 H5 – 6 Connections to I/O Expansion Board H5 – 7 1 H1 – 2 H1 – 8 H5 – 8 H1 – 9 H5 – 9 H1 – 10 H5 – 10 H1 – 11 H5 – 11 H1 – 12 H5 – 12 Connections to Main Board H1 – 7 H2 – 1 1 Auxiliary Heat Stage #2 Output – N/O Condensate Overflow Signal Input H2 – 2 H6 – 2 Compressor Suction Temp Sensor (LT1) – Common H2 – 3 H6 – 3 Compressor Suction Temp Sensor (LT1) – Signal H3 – 1 H6 – 4 Compressor Low Pressure Switch (LP1) – Source Voltage H3 – 2 Ext. 24 VAC Common In H6 – 5 Compressor Low Pressure Switch (LP1) – Signal H3 – 3 HGR / Waterside Economizer Output – N/O H6 – 6 Reversing Valve – Common H3 – 4 Ext. 24 VAC Common H6 – 7 Reversing Valve – Output H3 – 5 ECM Fan Motor Variable Speed Signal Output No Connection H3 – 6 H7 – 2 No Connection H4 – 1 H7 – 3 Red LED Output H4 – 2 H7 – 4 Green LED Output H5 – 1 H7 – 5 Yellow LED Output H5 – 2 No Connection H7 – 6 Red-Green-Yellow LED Common H5 – 3 Red LED Output Isolation Valve/Pump Request Relay N/O H5 – 4 Green LED Output H8 – 2 Isolation Valve/Pump Request Relay N/C H5 – 5 Yellow LED Output H8 – 3 24 VAC Common H5 – 6 Red-Green-Yellow LED Common Return Air Sensor – Signal H6 – 1 HP2-1 Jumper Wire Connection H6 – 1 H7 – 1 H8 – 1 H9 – 1 1 1 1 1 H9 – 2 No Connection 24 VAC Common 1 Ext. 24 VAC In ECM Fan Motor Variable Speed Signal – Common 1 Entering Water Temp Sensor – Signal Entering Water Temp Sensor – Common 1 No Connection Return Air Sensor – Common H6 – 2 HP2-2 Jumper Wire Connection TB1 – 1 1 Room Sensor – Status LED Output H7 – 1 Fan Speed Table Row Select – Signal TB1 – 2 2 Room Sensor – Fan Mode & Unit Mode Switches H7 – 2 Fan Speed Table Row Select – Common TB1 – 3 3 Room Sensor – Setpoint Adjust Potentiometer H7 – 3 Thermostat – Heat Stage #4 (W4) Input – Signal TB1 – 4 4 Room Sensor – Room Temp Sensor & Tenant Override H7 – 4 TB1 – 5 5 Room Sensor – DC Signal Common H8 – 1 TB2 – 1 R 24 VAC H8 – 2 24 VAC Common TB2 – 2 A Thermostat – Alarm Output H8 – 3 No Connection TB2 – 3 W2 Thermostat – Heat Stage #2 (W2) Input H8 – 4 Auxiliary Heat Stage #1 / Hydronic Heat Output N/O (24 VAC) TB2 – 4 W1 Thermostat – Heat Stage #1 (W1) Input H8 – 5 24 VAC Common TB2 – 5 Y2 Thermostat – Cool Stage #2 (Y2) Input TB1 – 1 1 Humidistat Signal Input TB2 – 6 Y1 Thermostat – Cool Stage #1 (Y1) Input TB1 – 2 2 Thermostat - Heat Stage #4 (W4) Input – Signal TB2 – 7 G Thermostat – Fan Input IM 1139-8 30 Auxiliary 24 VAC Out 1 Compressor – High Capacity Output – N/O www.DaikinApplied.com Controls Figure 39: MicroTech SmartSource unit controller & I/O expansion module Note: Refer to Table 15 on page 30 for terminal descriptions www.DaikinApplied.com 31 IM 1139-8 Controls Jumper Configuration Settings WARNING Figure 40: Configuration jumpers location Proper antifreeze/water solution is required to minimize the potential of fluid freeze-up. Jumper JP3 is factory set for water freeze protection with the jumper open. Operation at fluid temperatures below 32°F with anti-freeze protection requires JP3 to be field configured for the jumper closed. If unit is employing a fresh water system (no anti-freeze protection), it is extremely important that JP3 jumper setting remains in the open position (factory default setting) in order to shut down the unit at the appropriate water temperature to protect your heat pump from freezing. Failure to do so can result in unit damage, property damage and will void unit warranty. Table 16: Jumper settings and descriptions Jumper Description JP1 Mode JP2 Fan operation JP3 (See Warning) Freeze Protection JP4 Freeze Fault Protection JP5 Set point adjustment range only applies to network controls with a room temperature sensor JP6 Room control type JP7 Compressor heating source JP8 I/O expansion module Options Open for normal operation mode Shorted for service/test operation mode Open for continuous fan operation, when not in unoccupied mode. Shorted for cycling fan operation Open for water freeze protection Shorted for systems with anti-freeze protection (15°F (9°C) Open for none Shorted to enable freeze fault protection based on Leaving Water Temperature (LWT) Open for adjustment range of -5.0° to +5.0° F Shorted for 55° to 95° F adjustment range Open for thermostatic room control Shorted for room temperature sensor control, MicroTech III only. Open to enable compressor heating Shorted to disable compressor heating Open when I/O expansion module is not needed Shorted when I/O expansion module is required Table 17: I/O expansion module jumper settings I/O Expansion Description Fan Row Select for Operating Modes: ▪ Fan Only ▪ Hydronic Heating ▪ Waterside Economizer Jumper(s) JP1 & JP2 Setting Fan Row #1 Selected JP1 = Shorted JP2 = Open Fan Row #2 Selected JP1 = Open JP2 = Shorted Fan Row #3 Selected JP1 = Shorted JP2 = Shorted Fan Row #4 Selected JP3 = Open JP4 = Open Secondary Heating Options JP3 & JP4 JP5 & JP6 Supplemental Electric Heat JP3 = Open JP4 = Shorted Boilerless Electric Heat JP3 = Shorted JP4 = Shorted Hydronic Heat Hot Gas/Water Reheat (HGR) JP5 = Open JP6 = Shorted Waterside Economizer JP7 JP7 = Open Compressor Capacity Option JP8 JP8 = Open JP8 = Shorted 32 None JP5 = Shorted JP6 = Open Not Used IM 1139-8 None JP3 = Shorted JP4 = Open JP5 = Open JP6 = Open Dehumidification Options / Waterside Economizer Model JP1 = Open JP2 = Open – Single-Stage Capacity Dual-Stage Capacity www.DaikinApplied.com Controls MicroTech® III SmartSource Unit Controller Table 18: MicroTech III SmartSource unit controller fault & status LED's The MicroTech III SmartSource unit controller allows thermostat, Daikin sensor and DDC standalone operation. The R (24VAC) terminal is used to operate thermostat inputs G, Y1, Y2, W1, W2, W3, W4 and TB1-1. The C (0VAC) terminal is used to control inputs U, E and O. No external power sources may be used to operate the MicroTech III controller. All units must be properly grounded per local code requirements. NOTICE For information on sequence of operation and troubleshooting refer to OM 1149-xx. Remote Reset of Automatic Lockouts The Remote Reset feature provides the means to remotely reset automatic lockouts. There are (3) means to reset an automatic lockout condition: • Using the thermostat create 2 demands for capacity within 30 seconds • Press the Room Sensor or Thermostat Timed Override/Reset Button for more than 10 seconds • Turn the unit power off Type Yellow Green Red I/O Expansion Communication Fail Invalid Configuration Fault ON Flash Flash Fault Flash Flash OFF Low Voltage Brownout Fault OFF Flash OFF Emergency Shutdown Mode OFF Flash OFF Compressor High Pressure Fault OFF OFF Flash Compressor Low Pressure Fault OFF OFF ON Compressor Suction Temp Sensor Fail Fault Flash Flash ON Compressor Low Suction Temp Fault Flash OFF OFF Freeze Fault Detect Fault Flash OFF Flash Room Temp Sensor Fail (Room Sensor Control Only) Fault Flash Flash ON Leaving Water Temp Sensor Fail Fault Flash Flash ON Condensate Overflow Fault ON OFF OFF Serial EEPROM Corrupted Fault ON ON ON Waterside Economizer Low Temp Cutout (WSE Control & Call for Cooling) Mode Flash ON Flash Service Test Mode Enabled Mode Flash Flash Flash Unoccupied Mode Mode ON ON OFF Occupied, Bypass, Standby, or Tenant Override Modes Mode OFF ON OFF Note: Mode/faults are listed in order of priority. When the cause of the fault condition has been cleared, and the unit transitions from not requiring any capacity to needing any capacity twice within 30 seconds (accomplished by user manipulation of the Heat/Cool/ Auto/Off switch on the thermostat), an alarm reset equivalent to a tenant override button reset is generated. The intelligent reset counter and the 24 hour timer are cleared when this type of alarm reset is generated. Note: This feature only applies to thermostat controlled systems. For room sensor controlled units, pressing the “Override” or “Reset” button for more than 10 seconds will apply a ground signal to the tenant override in(screw terminal connection at TB1 pin 4) will clear the lockout alarm once the cause of the fault condition has been cleared. A unit power cycle can also be used to clear an automatic lockout if the conditions causing the fault have been cleared. www.DaikinApplied.com Description 33 Table 19: I/O expansion module fault & status LED's Description Type Yellow Green Red Baseboard Communication Fail Fault Flash OFF Flash Entering Water Temp Sensor Fail (Boilerless Electric Heat or Waterside Economizer Only or Hydronic Heat) Fault ON OFF Flash Low Entering Water Temperature (No Display On Boilerless Electric Heat) Fault OFF ON Flash Fan is OFF Mode OFF ON OFF Fan Running at Low Speed (0 to 33%) Duty Cycle Mode OFF Flash OFF Fan Running at Medium Speed (34 to 66%) Duty Cycle Mode ON Flash OFF Fan Running at High Speed (67 to 100%) Duty Cycle Mode Flash Flash OFF IM 1139-8 Controls Table 20: Fault recovery and reset Auto Recovery Tenant Override Button Reset Network Reset Yes No No Invalid Configuration No No No Low Voltage Brownout Yes No Yes All Sensor Failures No No Yes Compressor High Pressure No Yes Yes Compressor Low Pressure No Yes Yes Compressor Low Suction Temp or Freeze Fault Detect (Heating and Cooling Modes) Yes1 Yes Yes Compressor Low Suction Temp or Freeze Fault Detect (Dehumidification Mode) Yes Yes Yes Condensate Overflow Yes No Yes Low Entering Water Temp Yes No No Serial EEPROM Corrupted No No No Waterside Economizer Low Temp Cutout Yes No No Fault Description I/O Expansion Communication Fail Note: 1 MicroTech SmartSource Controller with BACnet® Communication Module For installation and operation information on MicroTech III SmartSource unit controller and other ancillary components, see: • IM 928 - MicroTech III BACnet Communication Module • OM 931 - MicroTech III SmartSource Unit Controller for Water Source Heat Pumps Operation and Maintenance Manual • IM 955 - MicroTech III Wall Sensor For use with MicroTech III SmartSource Unit Controller Figure 42: MicroTech III BACnet water source heat pump snap-in communication module Indicates auto recover is subject to intelligent alarm reset. Alarm auto recovers on first two occurrences, locked out on third within 24 hour period. See "Intelligent Alarm Reset" on page 32 for further details. MicroTech SmartSource Controller with LonWorks® Communication Module For installation and operation information on LonWorks Communication Module and other ancillary control components, see: • IM 927 - MicroTech III Water Source Heat Pump LonWorks Communication Module • IM 933 - LonMaker Integration Plug-in Tool: For use with the MicroTech III SmartSource Unit Controller • IM 955 - MicroTech III Wall Sensor for use with MicroTech III SmartSource Unit Controller Figure 41: LonWorks communication module IM 1139-8 34 www.DaikinApplied.com Controls Constant Torque EC Motor Table 21: Constant torque EC motor CFM values Unit Size Setting Function .15 .20 .25 .30 .35 .40 .45 .50 .55 .60 .65 368 352 336 320 304 288 272 256 240 224 206 188 341 324 306 289 271 253 235 217 198 180 162 145 312 294 275 256 236 216 195 174 152 Setting 1 (Low) 312 294 275 256 236 216 195 174 152 Setting 4 (High) 394 378 363 348 333 319 304 290 276 262 244 Setting 3 (Standard) 368 352 336 320 304 288 272 256 240 Setting 4 (High) Setting 3 (Standard) Setting 2 (Medium) 007 Setting 2 (Medium) Stage 2 341 324 306 289 271 253 235 217 198 312 294 275 256 236 216 195 174 152 Setting 4 (High) 312 294 275 256 236 216 195 174 152 Setting 3 (Standard) 312 294 275 256 236 216 195 174 152 264 244 222 199 176 151 125 98 Fan Only Setting 1 (Low) 264 244 222 199 176 151 125 98 408 393 378 364 349 335 321 308 294 281 Setting 3 (Standard) 372 356 340 324 308 292 276 261 245 229 211 Stage 1 .70 145 Setting 4 (High) Setting 2 (Medium) 264 246 337 320 302 284 266 248 230 Setting 1 (Low) 337 320 302 284 266 248 230 211 Setting 4 (High) 437 423 409 395 382 368 355 342 330 317 301 285 Setting 3 (Standard) 408 393 378 364 349 335 321 308 294 281 264 246 245 229 309 294 Setting 2 (Medium) Stage 2 372 356 340 324 308 292 276 261 Setting 1 (Low) 337 320 302 284 266 248 230 211 Setting 4 (High) 337 320 302 284 266 248 230 211 192 Setting 3 (Standard) 337 320 302 284 266 248 230 211 192 278 258 237 215 193 169 145 120 Setting 1 (Low) 278 258 237 215 193 169 145 120 Setting 4 (High) 459 445 431 417 404 390 377 364 351 339 324 428 413 399 385 371 358 345 331 319 306 290 394 378 363 348 333 319 304 290 Setting 2 (Medium) Setting 3 (Standard) Setting 2 (Medium) 012 Stage 1 Setting 1 (Low) Setting 2 (Medium) 009 External Static Pressure (inches of water column) .10 Fan Only Stage 1 Setting 1 (Low) 394 378 363 348 333 319 304 290 Setting 4 (High) 486 473 459 445 431 417 402 388 374 359 348 337 326 Setting 3 (Standard) 459 445 431 417 404 390 377 364 351 339 324 309 294 428 413 399 385 371 358 345 331 319 306 290 Setting 1 (Low) 394 378 363 348 333 319 304 290 Setting 4 (High) 394 378 363 348 333 319 304 290 276 262 244 226 Setting 3 (Standard) 394 378 363 348 333 319 304 290 276 262 244 226 337 320 302 284 266 248 230 211 192 173 155 337 320 302 284 266 248 230 211 192 173 155 Setting 2 (Medium) Setting 2 (Medium) Setting 1 (Low) Stage 2 Fan Only Note: Gray tinted areas, outside recommended operating range. www.DaikinApplied.com 35 IM 1139-8 Controls Constant CFM Type EC Motor Fan Settings Table 22: Single stage units with constant CFM type EC motor Unit Size 015 019 024/026 030/032 036/038 042/044 048/049 060/064 070/072 Notes: Setting Maximum ESP (in. wg.)2 1Low CFM Heat 1High CFM Heat 1Low CFM Cool 1High CFM Cool Fan Only Dehumidification Electric Heat Setting 4 (High) .70 500 560 500 560 375 375 560 Setting 3 (Standard) .70 440 500 440 500 375 375 560 Setting 2 (Medium) .70 375 440 375 440 280 375 560 Setting 1 (Low) .70 375 375 375 375 280 375 560 Setting 4 (High) .70 600 675 600 675 450 450 675 Setting 3 (Standard) .70 525 600 525 600 450 450 675 Setting 2 (Medium) .70 450 525 450 525 340 450 675 Setting 1 (Low) .70 450 450 450 450 340 450 675 Setting 4 (High) .70 800 900 800 900 600 600 900 Setting 3 (Standard) .70 700 800 700 800 600 600 900 Setting 2 (Medium) .70 600 700 600 700 450 600 900 Setting 1 (Low) .70 600 600 600 600 450 600 900 Setting 4 (High) .70 1000 1125 1000 1125 750 750 1125 Setting 3 (Standard) .70 875 1000 875 1000 750 750 1125 Setting 2 (Medium) .70 750 875 750 875 560 750 1125 Setting 1 (Low) .70 750 750 750 750 560 750 1125 Setting 4 (High) .70 1250 1400 1250 1400 940 938 1400 Setting 3 (Standard) .70 1090 1250 1090 1250 940 938 1400 Setting 2 (Medium) .70 940 1090 940 1090 700 938 1400 Setting 1 (Low) .70 940 940 940 940 700 938 1400 Setting 4 (High) .70 1400 1575 1400 1575 1050 1050 1575 Setting 3 (Standard) .70 1225 1400 1225 1400 1050 1050 1575 Setting 2 (Medium) .70 1050 1225 1050 1225 785 1050 1575 Setting 1 (Low) .70 1050 1050 1050 1050 785 1050 1575 Setting 4 (High) .70 1600 1800 1600 1800 1200 1200 1800 Setting 3 (Standard) .70 1400 1600 1400 1600 1200 1200 1800 Setting 2 (Medium) .70 1200 1400 1200 1400 900 1200 1800 Setting 1 (Low) .70 1200 1200 1200 1200 900 1200 1800 Setting 4 (High) .70 2000 2250 2000 2250 1500 1500 2250 Setting 3 (Standard) .70 1750 2000 1750 2000 1500 1500 2250 Setting 2 (Medium) .70 1500 1750 1500 1750 1120 1500 2250 Setting 1 (Low) .70 1500 1500 1500 1500 1120 1500 2250 Setting 4 (High) .70 2160 2400 2160 2400 1710 1710 2400 Setting 3 (Standard) .70 1920 2160 1920 2160 1710 1710 2400 Setting 2 (Medium) .70 1710 1920 1710 1920 1330 1710 2400 Setting 1 (Low) .70 1710 1710 1710 1710 1330 1710 2400 1. The unit is capable of high-low fan performance through the use of a 2-stage thermostat wired to specific terminals for High-Low CFM fan performance. Standard operation with a 1-stage thermostat is indicated as High CFM fan performance. 2. Applications up to 1.0" ESP (in. wg.) are possible. However, increased fan noise should be anticipated and appropriate noise attenuation should be considered. IM 1139-8 36 www.DaikinApplied.com Controls Fan Performance For Constant CFM EC Motor (Sizes 015–072) Table 24: I/O expansion module jumper configuration I/O Expansion board configuration Table 23: Fan settings and performance Unit Size 015 019 024/026 030/032 036/038 042/044 048/049 060/064 070/072 Setting Fan Only Hydronic Heat Waterside Economizer A 500 500 500 B 440 440 440 C 375 375 375 D 280 280 375 A 600 600 600 B 525 525 525 C 450 450 450 D 340 340 450 A 800 800 800 B 700 700 700 C 600 600 600 D 450 450 600 A 1000 1000 1000 B 875 875 875 C 750 750 750 D 560 560 750 A 1250 1250 1250 B 1090 1090 1090 C 940 940 940 D 700 700 940 A 1400 1400 1400 B 1225 1225 1225 C 1050 1050 1050 D 785 785 785 A 1600 1600 1600 B 1400 1400 1400 C 1200 1200 1200 D 900 900 1200 A 2000 2000 2000 B 1750 1750 1750 C 1500 1500 1500 D 1120 1120 1500 A 2160 2160 2160 B 1920 1920 1920 C 1710 1710 1710 D 1330 1330 1710 www.DaikinApplied.com Setting JP1 JP2 A Open Open B Shorted Open C Open Shorted D Shorted Shorted Figure 43: JP1 & JP2 location on the I/O expansion module JP1 JP2 37 IM 1139-8 Controls Fan Speed Selector Switch Figure 44: 4-position fan speed selector switch A 4-position fan speed selector switch located in the control box allows CFM settings to be field adjustable. Fan speed control optimizes unit fan speed based on thermostat/room sensor inputs. The fan speed switch allows for manually setting an optimal fan speed specific to the application requirements. Each position on the fan speed switch represents settings 1-4. See Table 25 below for the complete list of fan speed selector switch settngs. Fan CFM Settings & Performance Table 25: 2-Stage units with constant cfm type EC motor Unit Size 024, 026 030, 032 036, 038 042, 044 048, 049 060, 064 070, 072 Setting Maximum ESP (in. wg.) Part Load Stage 1 Heat Full Load Stage 2 Heat Part Load Stage 1 Cool Full Load Stage 2 Cool Fan Only Dehumidification Electric Heat Setting 4 (High) .70 800 900 800 900 600 600 900 Setting 3 (Standard) .70 700 800 700 800 600 600 900 Setting 2 (Medium) .70 600 700 600 700 450 600 900 Setting 1 (Low) .70 600 600 600 600 450 600 900 Setting 4 (High) .70 1000 1125 1000 1125 750 750 1125 Setting 3 (Standard) .70 875 1000 875 1000 750 750 1125 Setting 2 (Medium) .70 750 875 750 875 560 750 1125 Setting 1 (Low) .70 750 750 750 750 560 750 1125 Setting 4 (High) .70 1250 1400 1250 1400 940 938 1400 Setting 3 (Standard) .70 1090 1250 1090 1250 940 938 1400 Setting 2 (Medium) .70 940 1090 940 1090 700 938 1400 Setting 1 (Low) .70 940 940 940 940 700 938 1400 Setting 4 (High) .70 1400 1575 1400 1575 1050 1050 1575 Setting 3 (Standard) .70 1225 1400 1225 1400 1050 1050 1575 Setting 2 (Medium) .70 1050 1225 1050 1225 785 1050 1575 Setting 1 (Low) .70 1050 1050 1050 1050 785 1050 1575 Setting 4 (High) .70 1600 1800 1600 1800 1200 1200 1800 Setting 3 (Standard) .70 1400 1600 1400 1600 1200 1200 1800 Setting 2 (Medium) .70 1200 1400 1200 1400 900 1200 1800 Setting 1 (Low) .70 1200 1200 1200 1200 900 1200 1800 Setting 4 (High) .70 2000 2250 2000 2250 1500 1500 2250 Setting 3 (Standard) .70 1750 2000 1750 2000 1500 1500 2250 Setting 2 (Medium) .70 1500 1750 1500 1750 1120 1500 2250 Setting 1 (Low) .70 1500 1500 1500 1500 1120 1500 2250 Setting 4 (High) .70 2400 2700 2160 2400 1800 1710 2400 Setting 3 (Standard) .70 2100 2400 1920 2160 1800 1710 2400 Setting 2 (Medium) .70 1800 2100 1710 1920 1340 1710 2400 Setting 1 (Low) .70 1800 1800 1710 1710 1340 1710 2400 Note: Applications up to 1.0" ESP (in. wg.) are possible. However, increased fan noise should be anticipated and appropriate noise attenuation should be considered. IM 1139-8 38 www.DaikinApplied.com Start-up Information for Initial Start-up Set thermostat to “Heat.” If the thermostat is the automatic changeover type, set system switch to the “Auto” position and depress the heat setting to the warmest selection. Some units have built-in time delays which prevent the compressor from immediately starting. With most control schemes, the fan will start immediately. After a few minutes of compressor operation, check for warm air delivery at discharge grille. If this is a “cold building” start-up, leave unit running until return air to the unit is at least 65°F (18°C). Measure the temperature difference between entering and leaving air and entering and leaving water. With entering water of 60°F to 80°F (16°C to 27°C), leaving water should be 6°F to 12°F (3.3°C to 6.6°C) cooler, and the air temperature rise through the machine should not exceed 35°F (19°C). If the air temperature exceeds 35°F (19°C), then the water flow rate is inadequate. CAUTION Units must be checked for water leaks upon initial water system start-up. Water leaks may be a result of mishandling or damage during shipping. Failure by the installing contractor to check for leaks upon start-up of the water system could result in property damage. Check, Test & Start Procedure NOTICE Complete the "Water Source Heat Pump Equipment Check, Test and Start Form" on page 38. Check As Completed: Open all valves to full open position and turn on power to the unit. Set thermostat for “Fan Only” operation by selecting “Off” at the system switch and “On” at the fan switch. If “Auto” fan operation is selected, the fan will cycle with the compressor. Check for proper air delivery. Set thermostat to “Cool.” If the thermostat is an automatic changeover type, simply set the cooling temperature to the coolest position. On manual changeover types additionally select “Cool” at the system switch. Again, many units have time delays which protect the compressor(s) against short cycling. After a few minutes of operation, check the discharge grilles for cool air delivery. To insure proper water flow, measure the temperature difference between entering and leaving water. The temperature differential should be 10°F to 14°F (5°C to 8°C) for units in cooling mode. It should be approximately 1½ times greater than the heating mode temperature difference. For example, if the cooling temperature difference is 15°F (8°C), the heating temperature difference should have been 10°F (5°C). Without automatic flow control valves, target a cooling temperature difference of 10°F to 14°F (5°C to 8°C). Adjust the combination shutoff/balancing valve in the return line to a water flow rate which will result in the 10˚F to 14°F (5°C to 8°C) difference www.DaikinApplied.com 39 Check the elevation and cleanliness of the condensate line. If the air is too dry for sufficient dehumidification, slowly pour enough water into the condensate pan to ensure proper drainage. If the unit does not operate, check the following points: a. Is supply voltage to the machine compatible? b. Is thermostat type appropriate? c. Is thermostat wiring correct? If the unit operates but stops after a brief period: a. Is there proper airflow? Check for dirty filter, incorrect fan rotation (3-phase fan motors only), or incorrect ductwork. b. Is there proper water flow rate within temperature limits? Check water balancing; back flush unit if dirt-clogged. Check for vibrating refrigerant piping, fan wheels, etc. IM 1139-8 Typical Wiring Diagrams MicroTech III Unit Control with BACnet Communication Module (HGRH) 265-277V, 1-Phase See service & disconnect portion of wiring diagram on page 49. IM 1139-8 40 www.DaikinApplied.com Typical Wiring Diagrams MicroTech III Unit Control with BACnet Communication Module (WSE & DSH) - 208-230V, 1-Phase with 115V Loop Pumps and 20kW Electric Heat See service & disconnect portion of wiring diagram on page 50. www.DaikinApplied.com 41 IM 1139-8 Typical Wiring Diagrams MicroTech III Unit Control with LonWorks Communication Module 208-230V, 3-Phase with 230V Loop Pumps and 5kW Electric Heat See service & disconnect portion of wiring diagram on page 51. IM 1139-8 42 www.DaikinApplied.com Typical Wiring Diagrams MicroTech III Unit Control with BACnet Communication Module (WSE) 460V, 3-Phase with 230V Loop Pumps and 20kW Electric Heat See service & disconnect portion of wiring diagram on page 52. www.DaikinApplied.com 43 IM 1139-8 Typical Wiring Diagrams MicroTech III Unit Control with Hydronic Heat (HYH) – 208-230V MicroTech III Unit Controller I/O Expansion Module Hydronic Heat HYH IM 1139-8 44 www.DaikinApplied.com Maintenance Motor Removal Figure 46: Disassemble motor orifice ring & motor mount screws from fan housing When reinstalling motor locate plug on motor down 3 The fan wheel is removed from the motor shaft by loosening the set screw Torque screws for motor mount brackets to fan housing at 42 ± 3 in lbs. When reinstalling the fan wheel center it inside the fan housing 2 Remove four (4) bolts securing motor to orifice ring Fan housing Fan wheel Motor mount orifice ring 1 Remove four (4) screws securing orifice ring and motor assembly to fan housing Motor www.DaikinApplied.com 45 IM 1139-8 Troubleshooting Typical Refrigeration Cycles Figure 47: Cooling mode Thermal Expansion Valve Return Air Co-Axial Heat Exchanger Water In Coil – Air to Refrigerant Heat Exchanger Water Out Sensing Bulb and Capillary Tube Compressor Blower Reversing Valve Conditioned Air – (Cooling) Cooling Refrigeration Cycle When the wall thermostat is calling for COOLING, the reversing valve is energized and directs the flow of the refrigerant (hot gas) leaving the compressor to the water-to-refrigerant heat exchanger. Here the heat is removed by the water and the hot gas condenses to become a liquid. The liquid then flows through a thermal expansion valve (TXV) and then to the air-to-refrigerant heat exchanger coil. The liquid then evaporates becoming a gas, at the same time absorbing heat and cooling the air passing over the surfaces of the coil. The refrigerant then flows as a low pressure gas through the reversing valve and back to the suction side of the compressor to complete the cycle. Figure 48: Heating mode Thermal Expansion Valve Return Air Co-Axial Heat Exchanger Water In Coil – Air to Refrigerant Heat Exchanger Water Out Sensing Bulb and Capillary Tube Compressor Blower Reversing Valve Conditioned Air – (Heating) Heating Refrigeration Cycle When the wall thermostat is calling for HEATING, the reversing valve is energized and directs the flow of the refrigerant (hot gas) leaving the compressor to the air-to-refrigerant heat exchanger coil. Here the heat is removed by the air passing over the surfaces of the coil and the hot gas condenses to become a liquid. The liquid then flows through a thermal expansion valve (TXV) then to the water-to-refrigerant heat exchanger. The liquid then evaporates becoming a gas, at the same time absorbing heat and cooling the water. The refrigerant then flows as a low pressure gas through the reversing valve and back to the suction side of the compressor to complete the cycle. IM 1139-8 46 www.DaikinApplied.com Unit Check / Equipment Data Installation Data Job Name____________________________________________________ Check Test Date:___________________________ City ___________________________________________________________ State________________ Zip_______________ Daikin Model #_______________________________________________________ Daikin Serial #________________________________________ Job site Unit ID # (HP #)______________________________ General Contractor:______________________________________ Mechanical Contractor:______________________________ Technician Performing Start-Up: Name_______________________________ Employer:______________________________ Complete equipment data from measurements taken at the locations indicated on the drawing below. Equipment Data Flow Rate EWP - LWP = ∆P 1 EWP - PSI In__________________minus 2 LWP - PSI Out___________ equals ∆P_____________ The first step in finding GPM is to subtract leaving water pressure from entering water pressure. The difference between the two is referred to as ∆P. ∆P can be converted to GPM by looking in the equipment specification catalog. Caution ∆P ≠ GPM Note: A conversion table must be used to find GPM from (Delta) ∆P measurements. Loop Fluid Temperature Rise / Drop through Coaxial Heat Exchanger EWT - LWT = ∆T 4 LWT - °F Out___________________ equals Fluid ∆T________________ 3 EWT - °F Out__________________ minus ∆T is the rise or drop in the fluid temperature as it passes through the Coaxial. Air Temperature Rise / Drop through the air coil ∆T x CFM x 1.08 = BTUH Sensible 6 LAT - °F Out____________________ equals Air ∆T__________________ 5 EAT - °F In____________________ minus Note: Perform Check, Test and Start-Up in the Cooling Mode Only. EWT - Entering Water Temperature EWP - Entering Water Pressure EAT - Entering Air Temperature ∆- Delta (Differential) LWT - Leaving Water Temperature LWP - Leaving Water Pressure LAT - Leaving Air Temperature CFM - Cubic Feet/Minute BTUH - British Thermal Units/Hour Check, Test & Start LAT V Discharge Hot Gas V C O I L Reversing Valve 6 V V EAT Air Temperature °F OUT V 5 A I R Suction COAX Expansion Valve Compressor Loop Fluid Pressure (In PSI) EWP 1 Loop Fluid Temperature °F EWT 3 V IN IN OUT V 2 LWP 4 LWT Form No._____________________________ www.DaikinApplied.com 47 IM 1139-8 Operating Limits Environment extremes in temperature and/or humidity, and equipment performance, reliability, and service life may be adversely affected. This equipment is designed for indoor installation only. Sheltered locations such as attics, garages, etc., generally will not provide sufficient protection against Table 26: Air limits in °F (°C) Standard Range Units Air Limits Minimum Ambient Air1 Extended Range (Geothermal) Units Cooling (DB/WB) Heating Cooling (DB/WB) Heating 50°F (10°C) 50°F (10°C) 40°F (4°C) 40°F (4°C) Maximum Ambient Air2 100°F/77°F (38°C/25°C) 85°F (29°C) 100°F/77°F (38°C/25°C) 85°F (29°C) Minimum Entering Air1 65°F/55°F (18°C/13°C) 50°F (10°C) 65°F/55°F (18°C/13°C) 50°F (10°C) Common Design Entering Air 75°F/63°F (24°C/17°C) 70°F (21°C) 75°F/63°F (24°C/17°C) 70°F (21°C) 85°F/71°F (29°C/22°C) 80°F (27°C) 85°F/71°F (29°C/22°C) 80°F (27°C) Maximum Entering Air2 Table 27: Fluid limits Fluid Limits Standard Range Units Extended Range (Geothermal) Units Cooling Heating Cooling Heating Minimum Entering Fluid 55°F (13°C) 55°F (13°C) 30°F (-1°C) 20°F (-6°C) Common Design Entering Fluid 85-90°F (29-32°C) 70°F (21°C) 90°F (32°C) 35-60°F (1.5-16°C) Maximum Entering Fluid 120°F (43°C) 90°F (32°C) 120°F (43°C) 90°F (32°C) Minimum GPM/Ton 1.5 Nominal GPM/Ton 3.0 Maximum GPM/Ton 4.0 Notes: 1. Maximum and minimum values may not be combined. If one value is at maximum or minimum, the other two conditions may not exceed the normal condition for standard units. Extended range units may combine any two maximum conditions, but not more than two, with all other conditions being normal conditions. 2. This is not a normal or continuous operating condition. It is assumed that such a start-up is for the purpose of bringing the building space up to occupancy temperature. Motorized Isolation Valve The motorized valve kit is available as a factory-installed and wired option or may be ordered as a field-installed accessory. Wired as shown in Figure 45, the motorized valve will open on a call for compressor operation. The motorized isolation valve actuator (ISO) has both a 24V power connection and a 24V end switch connection. Install the supplied wire harness into plug H8 on the main control board. Run wires between the ISO actuator and the supplied wire harness ends. Connect N.O. & N.C. actuators as shown on the schematic. The end switch should be wired in series with the 24V compressor signal wire. Connect the end switch wires as shown in the schematic. The end switch will close when the valve is fully open. Note: For detailed installation instructions for the fieldinstalled motorized valve, refer to IM 1151. Figure 45: Motorized valve wiring IM 1139-8 48 www.DaikinApplied.com Typical Wiring Diagrams MicroTech III Unit Control with BACnet Communication Module (HGRH)265-277V, 1-Phase, Service & Disconnect HP1,2 HUM ISO LAT LP1,2 LT1,2 LWT M01-04 M11-1 M70, 71 MCB NCB OLP PL1,2 R15 R20 RAT RV1,2 TB1 TB2 TB3 TR1 TR2 TR3 TSL TSW W0001-^ WH001-^ WN1-^ WP001-^ WPCP1 WPT01 WSE Legend: Note: Devices in legend may or may not be on unit. ADR AHL AN1,2 CO1-04 C11-12 CP1,2 COS DAT DCS DSH DSS EB1 EB2 EH1 EWT FM1-4 GND HG1,2 HHT Aquastat, Discharge Refrigerant Aquastat, High Limit LED Annunicator, circuit 1, 2 Fan Motor 1-4 Capacitor Compressor 1,2 Capacitor Compressor 1, 2 Condensate Overflow Protection Sensor Discharge Air Temperature Sensor Disconnect Switch Desuperheater Pump Desuperheater Shutoff Switch Expansion Control Board 1 Expansion Control Board 2 - fan speed ctrl Electric Heat Entering Water Temperature Sensor Fan Motor 1-4 Ground Hot Gas Reheat Valve Acutator Hot Water Heat Valve Actuator www.DaikinApplied.com 49 High Pressure Switch 1, 2 Humidistat Sensor Water Flow Isolation Valve Actuator Leaving Air Temperature Sensor Low Pressure Switch 1, 2 Compressor Suction Line Temperature Sensor 1, 2 Leaving Water Temperature Sensor Fan Motor 4 Contactor Compressor 1, 2 Contactor Secondary Heat Contactor Main Control Board Network Control Board Overload Protector - Compressor Motor Loop Pump 1, 2 Relay, Field Contacts, Alarm Output Relay, Loop Pump Return Air Temperature Sensor Reversing Valve 1, 2 Terminal Block, Line Voltage Terminal Block, 24V Terminal Block, EH1 Line Voltage Transformer - Control Transformer - Fan Motor Transformer - Loop Pump Thermostat, Wireless Thermostat, Wired (Unit-mounted) Wire Wire Harness Wire Nut Wire Plug Wire Plug Assy - Compressor Power Wire Plug Assy - 2-stage Comp Ctrl Waterside Economizer Actuator IM 1139-8 Typical Wiring Diagrams MicroTech III Unit Control with BACnet Communication Module (WSE & DSH) Service & Disconnect - 208-230V, 1-Phase with 115V Loop Pumps and 20kW Electric Heat IM 1139-8 50 www.DaikinApplied.com Typical Wiring Diagrams MicroTech III Unit Control with LonWorks Communication Module Service & Disconnect 208-230V, 3-Phase with 230V Loop Pumps and 5kW Electric Heat www.DaikinApplied.com 51 IM 1139-8 Typical Wiring Diagrams MicroTech III Unit Control with BACnet Communication Module (WSE) Service & Disconnect - 460V, 3-Phase with 230V Loop Pumps and 20kW Electric Heat IM 1139-8 52 www.DaikinApplied.com Maintenance General Maintenance 1. Normal maintenance on all units is generally limited to filter changes. Units are provided with permanently lubricated motors and require no oiling even though oil caps may be provided. 2. Filter changes are required at regular intervals. The time period between changes will depend upon the project requirements. Some applications such as motels produce a lot of lint from carpeting and linen changes, and will require more frequent filter changes. Check filters at 60-day intervals for the first year until experience is acquired. If light cannot be seen through the filter when held up to sunlight or a bright light, it should be changed. A more critical standard may be desirable. 3. The condensate drain pan should be checked annually and cleaned and flushed as required. 4. Record performance measurements of volts, amps, and water temperature differences (both heating and cooling). A comparison of logged data with start-up and other annual data is useful as an indicator of general equipment condition. Charging Due to the zeotropic nature of R-­410A, it should be charged as a liquid. In situations where vapor is normally charged into a system, a valve should be installed in the charging line to flash the liquid to vapor while charging. Note: Because a water source heat pump operates under a wide range of water and air temperatures, the values printed below are to be taken as suggested pressure and temperatures. All Daikin water source heat pumps are designed for commercial use. The units are designed for both heating and cooling operation and fail safe to cooling. The reversing valve is energized for the heating mode of operation Superheat Head Pressure Water Delta T 8 to 14 degrees 335-355 PSIG 10° to 14° Notes: 1. All information above is based on ISO standard 13256-1 and tested at these conditions. 2. Operating conditions shall be within the limits established in Table 26, and Table 27 on page 48. 5. Periodic lockouts almost always are caused by air or water problems. The lockout (shutdown) of the unit is a normal protective result. Check for dirt in the water system, water flow rates, water temperatures, airflow rates (may be a dirty filter), and air temperatures. If the lockout occurs in the morning following a return from night setback, entering air below machine limits may be the cause. Lubrication R-410A should be used only with polyester (POE) oil. The HFC refrigerant components in R-410A will not be compatible with mineral oil or alkylbenzene lubricants. R-410A systems will be charged with the OEM recommended lubricant, ready for use with R-410A. www.DaikinApplied.com 53 IM 1139-8 Troubleshooting Table 28: Troubleshooting refrigeration circuit Head Pressure Suction Pressure Compressor Amp Draw Super Heat Subcooling Air Temp Differential Water (Loops) Temp Differential Safety Lock Out Undercharge System (Possible Leak) Low Low Low High Low Low Low Low Pressure Overcharge System High High High Normal High Normal High Pressure Low Air Flow Heating High High High Low Air Flow Cooling Low Low Low Symptom Charge Low Water Flow Heating Low Low Normal Normal High Normal Low Normal Normal Low Low High Low High Pressure High High Low Low Temp Low Low High Low High Low Temp Low Water Flow Cooling High High High High Low Low High High Pressure High Air Flow Heating Low Low Low Low High Low Low Low Temp High Air Flow Cooling Low High Normal High Low Low Normal High Pressure High Water Flow Heating Normal Low Normal High Normal Normal Low High Pressure High Water Flow Cooling Low Low Low Low High Normal Low Low Temp TXV Restricted High Low High High Low Low IM 1139-8 Normal Low 54 www.DaikinApplied.com Water Source Heat Pump Equipment Check, Test and Start Form This form must be completed and submitted within ten (10) days of start‑up to comply with the terms of the Daikin warranty. Forms should be returned to Daikin Warranty Department. Installation Data Job Name __________________________________________________________ Check, Test & Start Date _________________ City or Town___________________________________________ State__________________________ Zip_________________ Equipment Type (Check all that apply) □Closed Loop □Open Loop □Geothermal □Other (specify)______________ Who is Performing CTS______________________________________ General Contractor__________________________________________ Essential Items Check of System – Note: “No” answers below require notice to installer by memorandum (attached copy.) Essential Items Check A. Voltage Check___________ Volts Loop Temp.____________ °F Heating System Water P.H. Levels___________ Set For____________ °F Cooling B. Yes □ □ □ □ □ □ □ □ □ □ □ No □ □ □ □ □ □ □ □ □ □ □ Condition Comments Loop Water Flushed Clean __________________________________________________________________ Closed Type Cooling Tower __________________________________________________________________ Water Flow Rate to Heat Pump Balanced _______________________________________________________ Standby Pump Installed ____________________________________________________________________ System Controls Functioning ________________________________________________________________ Outdoor Portion of Water System Freeze Protected _______________________________________________ Loop System Free of Air ____________________________________________________________________ Filters Clean _____________________________________________________________________________ Condensate Traps Installed __________________________________________________________________ Note: “No” answers below require notice to installer by memorandum (attached copy.) Outdoor Air to Heat Pumps: _________________________________________________________________ Other Conditions Found: ____________________________________________________________________ Please include any suggestions or comments for Daikin Applied:____________________________________________________ _______________________________________________________________________________________________________ _______________________________________________________________________________________________________ _______________________________________________________________________________________________________ Above System is in Proper Working Order Note: This form must be filled out and sent to the warranty administrator before any service money can be released. For Internal Use Release: SM _________________________ CTS _________________________ Date T _________________________ Signature for Sales Representative Service Manager Approval Signature for Customer www.DaikinApplied.com 55 Date Form WS-CTS-00.01 (Rev. 4/14) IM 1139-8 Commercial Check, Test and Start Worksheet (Complete all equipment measurements indicated for each unit per installation on previous page) Model Serial # H.P. # EWT 3 LWT 4 EWP 1 LWP 2 EAT 5 LAT 6 Volts Amps Cooling Check Air Filter and Coil Comments 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 26. 27. 28. 29. 30. 31. 32. 33. 34. 35. 36. 37. 38. 39. 40. 41. 42. Part No.______________________________ IM 1139-8 56 www.DaikinApplied.com Daikin Applied Training and Development Now that you have made an investment in modern, efficient Daikin equipment, its care should be a high priority. For training information on all Daikin HVAC products, please visit us at www.DaikinApplied.com and click on Training, or call 540-248-9646 and ask for the Training Department. Warranty All Daikin equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product Warranty. Consult your local Daikin Applied representative for warranty details. Refer to Form 933-430285Y. To find your local Daikin Applied representative, go to www.DaikinApplied.com. Aftermarket Services To find your local parts office, visit www.DaikinApplied.com or call 800-37PARTS (800-377-2787). To find your local service office, visit www.DaikinApplied.com or call 800-432-1342. This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.DaikinApplied.com. Products manufactured in an ISO Certified Facility. IM 1139-8 ©2016 Daikin Applied (09/16) | (800) 432–1342 | www.DaikinApplied.com ® Damper Maintenance Greenheck’s dampers are designed to be trouble free and hassle free under normal operation. Dampers are to be installed square and straight so as to prevent binding during operation. The following annual damper maintenance suggestions will help to insure proper damper operation and increase the life expectancy of the damper. Foreign Matter Over the course of time, dirt and grime may collect on damper surfaces. The damper surfaces should be cleaned to prevent hindrance to airflow. Moving Parts Make sure that parts such as linkage, bearings, blades, etc. that are intended to move freely, can do so. Lubricating these components can prevent possible rusting and unnecessary friction increase. Use only a moli-spray oil or similar graphite based oil as regular lubricating oil will attract dirt. Bearings. Synthetic, oil impregnated , and ball bearings without grease fittings require only minimal grease. Closure Remove foreign materials that may be interfering with blade closure or effective sealing of the blades with each other or with the frame. Operation While operating the damper through its full cycle, check to see that the blades open and close properly. If there is a problem, check for loose linkage, especially at the actuator. Tighten the linkage where required. Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com • Damper Maintenance Rev 2, November 2016 Copyright 2016 © Greenheck Fan Corporation Installation, Operation and Maintenance Manuals Job Title: Howard Hughes District Renovations Customer PO#: S1815-0032-LOU Elevation: (ft) 325 Date: 11/01/2018 Submitted By: Andrew McDonald Agent Order#: 95123 NORMAN S WRIGHT CLIMATEC 3325 E LA PALMA AVE ANAHEIM, CA 92806 US Phone: (714)632-9800 Fax: Email Address: lpara@nswcla.com P.O. Box 410 CAPS 4.27.1793 Schofield, WI 54476 (715) 359-6171 FAX (715) 355-2399 F:\Caps\Jobs\DOUG\Howard Hughes District Renovations.gfcj www.greenheck.com Page 1 of 2 Howard Hughes District Renovations Product IOMs Mark Name Model Name Bldg 6601 EF-1, Bldg 6601 OAF-1, Bldg 6080 EF-1, Bldg 6080 OAF-1 CSP Bldg 6601 louvers, Bldg 6080 louvers ESD-435 (No IOMs) Vari-Green Motor and Controls IOMs Mark Name IOM Name Bldg 6080 EF-1, Bldg 6080 OAF-1, Bldg 6601 EF-1, Bldg 6601 OAF-1 VG Motors Vari-Green Controls IOMs Mark Name IOM Name Bldg 6080 EF-1, Bldg 6080 OAF-1, Bldg 6601 EF-1, Bldg 6601 OAF-1 VG Controls - Universal Assemblies Accessory IOMs Accessory IOM Name Mark Names Install Operation Maint Manual RDC_8_453380 Bldg 6601 OAF-1 Install Operation Maint Manual SP Fan with CRD Plaster Flange... Bldg 6080 EF-1, Bldg 6080 OAF-1, Bldg 6601 EF-1, Bldg 6601 OAF-1 CAPS 4.27.1793 F:\Caps\Jobs\DOUG\Howard Hughes District Renovations.gfcj Page 2 of 2 Document 474680 Model SP and CSP Ceiling Exhaust and Inline Fans ® Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with these instructions will result in voiding of the product warranty and may result in personal injury and/or property damage. Direct Drive Ceiling Exhaust Fan Direct Drive Inline Exhaust Fan Designed for clean air applications where low sound levels are required. Many options and accessories are available such as lights, motion detectors, ceiling radiation dampers and speed controls. Capacities range from 25 to 1,600 cfm (42 to 2,718 m3/hr) and 1 in. wg (248 Pa). AMCA Licensed for Sound and Air Performance. Designed for clean air applications where low sound levels are required. Capacities range from 70 to 3,800 cfm (119 to 6,456 m3/hr) and 1 in. wg (248 Pa). AMCA Licensed for Air Performance. WARNING! To reduce the risk of fire, electric shock, or injury to persons, observe the following: • Suitable for use with solid state speed controls. • Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer. • Before servicing or cleaning unit, switch power off at service panel and lock service disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel. • Installation work and electrical wiring must be done by qualified person(s) in accordance with all applicable codes and standards, including fire-rated construction. • Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning equipment to prevent back drafting. Follow the heating equipment manufacturer’s guideline and safety standards such as those published by the National Fire Protection Association (NFPA), and the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE) and the local code authorities. • When cutting or drilling into wall or ceiling, do not damage electrical wiring or other hidden utilities. • Acceptable for use over a bathtub or shower when installed in a GFCI protected branch circuit. (Up through size SP-A390) • Never place a switch where it can be reached from a tub or shower. • Ducted fans must always be vented to the outdoors. • These fans are not recommended for cooking exhaust applications. They are designed primarily for low temperature, clean air applications only. The diagram shows the minimum distance these fans should be placed in relation to cooking equipment. • Fan/Light combination not to be installed in a ceiling thermally insulated to a value greater than R40. CAUTION! • For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors. ® AVERTISSEMENT! Pour réduire le risque d’incendie, de choc électrique ou de blessure corporelle, respecter cd qui suit: • Appareil pouvant être utilisé avec un régulateur de vitesse à semiconducteurs. • Utiliser cet appareil exclusivement comme prévu par le fabricant. En cas de questions, communiquer avec le fabricant à l’adresse ou au numéro de téléphone figurant dans la garantie. • Avant tout entretien ou nettoyage de l’appareil, couper l’alimentation sur le tableau électrique et verrouiller le dispositif de sectionnement pour empêcher toute mise sous tension accidentelle. Si le dispositif de sectionnement ne peut pas être verrouillé, attacher un moyen de mise en garde bien visible, tel qu’un panonceau, au tableau électrique. • La pose et le câblage électrique doivent être effectués par des personnes qualifiées en conformité avec les codes et normes en vigueur, y compris pour la résistance au feu du bâtiment. • Une quantité d’air suffisante est nécessaire pour la bonne combustion et l’extraction des gaz brûlés par le conduit d’évacuation (cheminée) d’appareils à combustible afin d’éviter le refoulement. Veiller à suivre les indications du fabricant du matériel de chauffe, les normes de sécurité telles que celles publiées par la National Fire Protection Association (NFPA) et l’American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE) et la réglementation en vigueur. • Lors de la découpe ou du perçage de murs ou plafonds, ne pas endommager les câbles électriques et autres conduites masquées. • Pose admissible au-dessus d’une baignoire ou d’une douche sous réserve de raccordement à un circuit de dérivation à protection GFCI (disjoncteur différentiel). (Jusqu’à la taille SP-A390 incluse) • Ne jamais placer d’interrupteur à un emplacement à portée d’une baignoire ou d’une douche. • Les caissons d’extraction à gaine doivent toujours être évacués vers l’extérieur. • Ces caissons ne sont pas conseillés pour les applications d’aspiration de vapeurs de cuisson. Ils sont conçus essentiellement pour l’aspiration d’air propre à basse température. Le schéma indique la distance minimale de placement de ces caissons par rapport à l’équipement de cuisson. • Le combiné ventilateur/luminaire ne devra pas être installé dans un plafond ayant une isolation thermique d’une valeur supérieure à R40. ATTENTION! • À utiliser pour la ventilation générale uniquement. Ne pas utiliser pour l’aspiration de matières et vapeurs dangereuses ou explosives. Ceiling Exhaust and Inline Fans 1 Prepare the Fan Power Assembly Remove Wiring Knockout If power assembly (motor, wheel, and scroll) is not installed in housing, insert the electrical plug into fan socket, then slide scroll end of power assembly into fan housing. Attach by using two sheet metal screws provided. Remove either top or side wiring knockout, depending on wiring direction, by Electrical Access bending it back Panel and forth to break tabs. A Model B Model Knockouts Ductwork Airflow Check ductwork to see if the fan’s discharge requires rotation from horizontal to vertical discharge. Airflow Fan Rotation To rotate from horizontal to vertical discharge A Models Only A50-500, 710, 780 Models Remove the two screws holding the power assembly in and pull power assembly out. Rotate power assembly 180 degrees and put back into fan. Use the same screws to reattach power assembly to fan housing. Flip fan over and remove the four screws holding the discharge duct and damper assembly. Exchange the assembly with plate mounted on top of fan, as shown in these illustrations. A700, 900-1500 Models Remove the eight screws holding the access panel or collar as shown in picture. Rotate the fan housing so the discharge is facing up. Replace access panel or collar and screws. 2 Ceiling Exhaust and Inline Fans Access Panel Access Panel ® Ceiling Radiation Damper (CRD) If fan is to be used in a fire resistive membrane ceiling, a ceiling radiation damper must be used. If the ceiling radiation damper is already mounted to the fan from the factory, proceed to Install the Fan. To mount the ceiling radiation damper to fan, make sure grille attachment tabs are facing down. Then place the inlet part of the fan into the ceiling radiation damper collar, and use self-tapping sheet metal screws (by others) to screw through the damper collar and into the fan housing. If the fan/light combination is being used, make sure ceiling radiation damper has an electrical plug in it. The electrical plug must be inserted into the fan. Make sure the electrical wire will not interfere with damper operation as shown in figure below. Wires to ceiling fan Attachment Tabs A50-510, 710, 780 Models B Models Do not allow interference in this area A700, 900-1550 Models Wires from lighted grille Discharge Installation A50-90 Models 1 2 Insert plastic duct tab into box slots. Rotate plastic duct adapter (PN 473388) until the screw tabs meet the box. Sheet Metal Screw #10x3/8 Phillips Head (PN 415838) Box Sheet Metal Screw #10x3/8 Phillips Head (PN 415838) Box Box Slot Plastic Duct Adapter Tabs Plastic Duct Adapter (PN 473388) 3 Plastic Duct Adapter (PN 473388) Screw Tabs Install screws provided to secure discharge. Screw holes Sheet Metal Screw #10x3/8 Phillips Head (PN 415838) ® Ceiling Exhaust and Inline Fans 3 Discharge Installation for Ceiling and Inline Exhaust Models Sizes B50-200 1 Insert box scroll tab into box scroll slots. 2 Rotate plastic duct adapter (PN 474433) until the two mounting tabs fully engage into the two box mounting slots. Box Scroll Tabs Box Mounting Slots Box Scroll Slots Box Mounting Tabs 3 OPTIONAL Align the pins on the TR 6x4 adaptor to the duct pin hole on the 6-inch duct. Push until the adaptor snaps into place. TR 6x4 Pin Plastic Duct Pin Hole TR 6x4 (PN 473324) 4 Ceiling Exhaust and Inline Fans 6-inch Plastic Duct (PN 474433) ® Install the Fan 1. For best performance, choose a location with the shortest possible duct run and minimum number of elbows. Do not mount near cooking equipment, as shown in Fig. 1. Do not install fan in this area 45° Fig. 1 Bottom Mount 2. Attach adjustable mounting brackets to fan, but leave the screws loose until proper height is determined, shown in Fig. 2. Cut hole to dimensions shown in table below: 45° Brackets can be used in either position to adapt to most mounting situations Bottom Mount Top Mount Fig. 2 Ceiling Openings Ceiling Exhaust Sizes A50, A70, A90 A110, A125, A190 A200, A250, A290, A390 Fan/CRD 107⁄8 x 133⁄8 111⁄8 x 137⁄16 121⁄8 x 141⁄4 121⁄4 x 143⁄8 A700 233⁄4 x 113⁄4 241⁄8 x 121⁄4 A410, A510, A710, A780 3 14 ⁄4 x 18 ⁄8 147⁄8 x 187⁄16 143⁄4 x 24 147⁄8 x 241⁄8 14 ⁄8 x 11 ⁄4 143⁄8 x 121⁄4 3 A900, A1050, A1410, A1550 B50 - 200 1 3 NOTE Model sizes A50-90 are standard with a round duct. Should any model A110-190 require a round duct, Model RDC (Round Duct Connector) may be ordered from manufacturer for field installation. For Hanging Installations: Use manufacturer’s optional vibration isolator kit Part Number VI Kit. Using the fan’s standard adjustable mounting brackets and 10 by 32 threaded rod (by others), hang unit as shown in Fig. 4. Slots in the brackets allow fine adjustment for flush fit with wall/ceiling opening Fig. 3 Fig. 4 3. Installation of ductwork is critical to the performance of the fan, shown in Fig. 5. Straight ductwork (1) or ductwork that turns in the same direction as the wheel (2) is recommended. Ductwork turning opposite the wheel direction (3) will cause turbulence and back pressure resulting in poor performance. Fig. 5 1 (GOOD) 3 (POOR) 2 (GOOD) AIRFLOW Fan or Fan/Light For Frame Construction: Position unit between joists. Position brackets such that bottom edge of housing will be flush with finished ceiling, and tighten the adjustable mounting brackets, shown in Fig. 3. 4. Slide ductwork over the fan’s discharge collar and securely attach it with sheet metal screws. Make sure the screws do not interfere with damper operation. Check damper to make sure it opens freely. Wire the Fan 1. Remove wiring cover. If fan/light combination is being used, make sure the fan plug is connected to the fan receptacle and the light Fan Outlet (top) plug is connected to the light receptacle, Light Outlet (bottom) Fig. 6 shown in Fig. 6. Using proper wire connectors, wire the fan as shown in Fig. 7a. For wiring of light proceed to Fig. 7b. Fan Light Fig. 7a Fig. 7b 115 & 277 Volt 220 - 240 Volt Black wire is “Hot” White wire is “Neutral” Green wire is “Ground” Black wire is “Hot” White wire is “Hot” Green wire is “Neutral/Ground” 2. Push all wiring into the unit’s cover and replace wiring cover. ® Ceiling Exhaust and Inline Fans 5 A50-90-VG and A90-130-VG fan models. These fan models utilize an internal switch to set the fan to run at one of three flows. Please set three position switch to desired airflow when installing unit. FAN 9 0 11 0 130 A 9 0 -1 30 A50 5 0 7 0-9 0 90 90 110 130 A90-130 A50-90 50 70 90 FAN Attach the Grille 1. If lighted grille is being used, plug wire into fan socket. If lighted grille and ceiling radiation damper are being used, plug wire from lighted grille into ceiling radiation damper socket. Do not plug wire directly into the fan socket. Make sure the wire does not interfere with the ceiling radiation damper operation. 2. Attach grille with two screws provided. Make sure not to over tighten; over tightening will damage grille. 3. Slide attachment screw covers over the attachment screws, shown in Figure 8 and 9. Fig. 8 4. If lighted grille is being used, install light bulb(s) into light socket(s). For fluorescent lights, use 27W GU24 bulbs. For LED lights, use 10W GU24 bulbs. Manufacturer has replacement 27W GU24 bulbs, call 1-800-355-5354 to order. 5. If lighted grille is being used, snap lens into place, by pushing on the outside edges of lens, shown in Fig. 9. To remove lens, use small screw driver and pry on one side of lens. 6. Turn on power and check fan and light operation. Fig. 9 Squeeze tabs to insert/remove lens 6 Ceiling Exhaust and Inline Fans ® Converting from Ceiling to Cabinet Design for Ceiling Exhaust Fans All convertible sizes will be shipped with grille and duct collar cover. Note, this applies only to fans originally ordered as convertible. B A Conversion Kit Parts List • Qty. of 1 Blower Box Cover Tools Required • Phillips Head Screwdriver Step 1: Remove grille (A) by removing the two grille screws (B). C D D F E Step 2: Remove duct collar cover (C) by removing the four duct collar screws (D). Step 3: Discard grille (A), two grille screws (B), and duct collar cover (C). Step 4: Remove the six (6) tinnerman clips (E) by twisting them to one side and pulling straight out. Discard two of the six tinnerman clips. Step 5: Insert the remaining four tinnerman clips (E) on grille opening side. Step 6: Place blower box cover (F) over tinnerman clips (E), which were inserted in step 5. E Step 7: Screw the blower box cover (F) into place with four blower box cover screws (D). Other Installation Considerations Ductwork and Noise Flex Duct Connections Fiberglass ductboard is a better choice than metal ductwork for reducing fan noise and is highly recommended for low sound applications. Where metal duct is used, sound transmission can be reduced with flexible duct connections between the fan and the duct. Sound and Location The location of these fans must be taken into consideration before installation. In critical sound installations, insulated ductwork, flexible duct connections or placing the fan in a remote section of ductwork are solutions to meeting the required fan sound levels. Filters The addition of an intake filter is highly recommended for these fans, even in clean air environments excess dirt can accumulate on wheels and motors causing reduced performance and imbalance. Remote Mounted Fan Converted to Inline Fiberglass Ductboard Fan Mounted Directly Overhead Filters, once installed, should be checked and cleaned periodically to maintain performance. Washable aluminum mesh filters specifically designed for these fans are available, please consult your representative for more information. Correct Low Sound Installation Incorrect ® Ceiling Exhaust and Inline Fans 7 Typical Installation INSULATION* (Place around and over Fan Housing.) ROOF CAP* (with built-in damper) FAN HOUSING POWER CABLE* Seal gaps around Housing. Keep duct runs short. OR ROUND DUCT* Seal duct joints with tape. ROUND ELBOWS* *Purchase separately. General Maintenance Suggestions Ceiling exhaust fans require very little maintenance, but since small problems over time left unchecked could lead to loss of performance or early motor failure, we do recommend that the unit be inspected periodically (once or twice a year). WALL CAP* (with built-in damper) ENERGY STAR® Models ENERGY STAR® Certified models include: SP-A70, 90, 110, 125, 190, 200 and 250, SP-A50-90-VG and SP-A90-130-VG, SP-B70, 80 and 90. The fan motor and wheel should be checked for dust and dirt accumulations. Dirt buildup can lead to loss of performance and motor overheating. Cleaning can be accomplished by brushing off any dust that may have accumulated. Even filtered units can accumulate buildup and should be checked when cleaning filters. The motor should be checked for lubrication at this time. Lubricate only those motors which have an oil hole provided. A few drops of all purpose oil (SAE 20) will be sufficient. Our Commitment As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice. Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library under Warranties. Greenheck’s Centrifugal Ceiling and Cabinet Exhaust Fans )catalog provides additional information describing the equipment, fan performance, available accessories, and specification data. AMCA Publication 410-96, Safety Practices for Users and Installers of Industrial and Commercial Fans, provides additional safety information. This publication can be obtained from AMCA International, Inc. at www.amca.org. ® Phone: 715.359.6171 • Fax: 715.355.2399 • Parts: 800.355.5354 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com 8 474680 • SP CSP, Rev. 4, March 2018 Copyright 2018 © Greenheck Fan Corporation Document 473681 Vari-Green® Motor and Controls ® Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with these instructions will result in voiding of the product warranty and may result in personal injury and/or property damage. Table of Contents Reference part number listed in chart to locate specific motor information page number. HP Voltage * RPM Encl. FLA Control Method Motor Part No. Pg. 1/10 115 300-1725 TENV 1.5 Pot/0-10V 318003 4 1/10 1/6 1/6 Range 115/208300-1750 230/277 ODP 115/208300-1750 230/277 ODP 115 300-1725 TENV 1.38/ 0.84/0.73 Pot/0-10v 2.2/1.3/ 1.1 Pot/0-10v 319357 4 2.6 Pot/0-10V 318004 4 3.1 0-10V Only 311352 3.1 Pot Only 311353 3.4 Pot/0-10V 319356 4 3 312359 3 0-10V Only 309026 10.1 Pot Only 309029 10.6 Pot/0-10V 311388 312619 3 3 3/4 208-240 300-1725 ODP 6.6 Pot/0-10V 314534 3 3/4 277 300-1725 OPD 5.4 Pot/0-10V 316498 3 11.3 0-10V Only 310306 11.3 Pot Only 310475 11.3 Pot/0-10V 312361 3 5.6 Pot/0-10V 317708 3 3 3/4 115 300-2200 ODP 3/4 208-240 350-2200 OPD 277 350-2200 OPD 4.7 Pot/0-10V 317709 3 115/208300-1725 230/277 OPD 8.8/5.45.0/4.8 Pot/0-10V 320589 4 3/4 ODP 12.4 Pot/0-10V Pot/0-10V 318013 4 1 TEFC 12.0/6.0 Pot/0-10V 311156 5 0-10V Only 310107 115/ 208-240 300-1725 3.9 3.9 Pot Only 310108 3 1 208-240 300-1725 ODP 8.6 Pot/0-10V 314945 3 3 1 277 300-1725 ODP 7.3 Pot/0-10V 316499 3 1 115/208300-1725 230/277 ODP 11.5/7.06.5/5.8 Pot/0-10V 320590 4 2 208-240 300 - 1725 TEFC 12.0 Pot/0-10V 310420 5 277 300-1725 TENV 1.15 Pot/0-10V 115/208300-1725 230/277 ODP 2.85/ 1.7/1.5 1/3 10.1 Pg. 300-1725 1/6 3.7 Pot/0-10V 2.3 Pot/0-10V 313713 311377 313714 313234 208-240 300-1725 ODP 277 300-1725 OPD 1.8 Pot/0-10V 316496 3 ODP 4.4/2.62.4/2.2 Pot/0-10V 320587 4 6.2 0-10V Only 309025 6.2 Pot Only 309028 115/208300-1725 230/277 Motor Part No. 115 Pot/0-10V 1/4 313233 Control Method 1 1.6 1/4 ODP FLA 3 TENV ODP 300-1725 Encl. 316495 300-1725 300-1725 Range 3 208-240 115 115 * RPM 3/4 1/6 1/4 3/4 Voltage 311731 313712 1/4 HP 313715 3 310359 312362 3 *Actual maximum RPM may vary. See RPM column in chart on page 11 for specific motor and fan combinations. 3 1/2 115 300-1725 ODP 6.7 Pot/0-10V 311812 3 1/2 208-240 300-1725 ODP 4.2 Pot/0-10V 313235 3 1/2 277 300-1725 ODP 3.3 Pot/0-10V 316497 3 6.5 0-10V Only 310307 6.5 Pot Only 310476 3 1/2 115 300-2500 ODP 6.5 Pot/0-10V 312360 3 1/2 208-240 350-2500 ODP 4.9 Pot/0-10V 317706 3 1/2 277 3500-2500 ODP 3.27 Pot/0-10V 317707 3 Controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-11 ODP 6.4/3.83.6/3.2 Pot/0-10V 320588 4 Maximum RPM Table . . . . . . . . . . . . . . . . . . . . . . . . 12 1/2 ® 115/208300-1725 230/277 Vari-Green Motor and Controls 1 Vari-Green® Motor The Vari-Green Motor is an electronically commutated (EC) motor that uses AC input power and internally converts it to a DC power supply which provides an 80% turndown capability and increased energy savings. Features, Operation and Wiring, and Troubleshooting Features Soft start – All motors feature soft-start technology which eliminates inrush current at start-up. The motors will reliably start at any speed setting. Overload protection – If the motor becomes overloaded, it will automatically reduce its speed until it is no longer overloaded. This means that the motor will never operate in the “service factor” which is possible with many AC motors. Locked rotor protection – If the motor ever encounters a locked-rotor scenario, the motor will automatically shut itself down. It will try to restart up to 3 times, and if after the 3rd time the motor will still not rotate, the motor will not attempt to start again until power is cycled. NOTE When using a clamp meter to measure input amp draw, the meter must be capable of reading a non-linear current. Erroneous readings will occur otherwise. Thermal protection – The motors have a one-shot fuse thermal protector. This is meant to protect the motor from a severe temperature rise. Additionally, the motors have on-board temperature sensors which will reduce the speed of the motor should it become too hot. The fuse is used as a last resort to prevent a fire. WARNING To reduce the risk of fire or electric shock, do not use this motor with any solid-state speed control device. RPM measurement – The motors have a small shaft extension on the end of the motor to measure motor RPM with either a contact or optical tachometer. Fig. 1 0-10 VDC External connection with factory mounted transformer (See page 4 for details) Transformer Assembly 100 ft. or less White Black Red COM 24V 0-10V COM 24V 0-10V Low voltage, route away from high voltage lines and/or use shielded cable N.C. COM. N.O. TO REMOTE DEVICE PROVIDED BY OTHERS Auxiliary Contact Control Motor Trip Point = 1.85VDC Contact Rating: 10A @ 24-240VAC 5A @ 30VDC Green indiator light —Power present TRANSFORMER 2x4 Junction Box Factory Wiring Field Wiring 115/230 VAC input to match motor name plate 2 Vari-Green Motor and Controls ® Operation and Wiring - Potentiometer Dial Only Part Numbers Covered in this Section 309028 309029 310108 310475 310476 311353 These motors feature a potentiometer dial on the motor for speed adjustment. A small screwdriver can be used to make the speed adjustment. To increase the speed, rotate the dial clockwise. To decrease the speed, rotate the dial counterclockwise. The motor is pre-wired at the factory and cannot be changed inside the motor. Connect single-phase power at the voltage listed on the nameplate. These motors cannot be converted to receive a remote control signal – a different motor is needed. Please consult the factory. Operation and Wiring - 0-10V Input Only Part Numbers Covered in this Section 309025 309026 310107 310306 310307 311352 These motors will accept a 0-10 VDC control signal for speed control. From 0-1.9V, the motor will be off, and will operate in the 2-10V range. 24 VAC/DC power is also required for operation. The motor will consume 0.7VA at 24 VAC or 25mA at 24 VDC. A factory mounted transformer is available to supply this voltage. (See Fig. 1) Dial on Motor – A small screwdriver can be used to make the speed adjustment. To increase the speed, rotate the dial clockwise. To decrease the speed, rotate the dial counterclockwise. There is no need to connect the control wires. 0-10 VDC signal – The dial on the motor must be rotated fully clockwise to achieve the full speed range. If this is not done, the dial will act as a maximum speed limiter. From 0-1.9V, the motor will be off, and will operate in the 2-10V range. 24 VAC/DC power is also required for operation. The motor will consume 0.7VA at 24 VAC or 25mA at 24 VDC. A factory mounted transformer is available to supply this voltage. (See Fig. 1, page 2) A low voltage wiring harness is needed to supply the 0-10V signal to the motor. This harness is available from the factory if conversion is necessary. Low Voltage Harness Part Numbers Type Use with Motor 18 in. long 36 in. long 3-pin 311731, 310359 384431 384432 9-pin 312359, 311377, 311812, 311388, 312360, 312361, 312362, 312619, 313233, 313234, 313235, 313712, 313713, 313714, 313715, 314534, 314945, 316495, 316496, 316497, 316498, 316499, 317706, 317707, 317708, 317709 384804 384805 The motor is pre-wired at the factory and cannot be changed inside the motor. Connect single-phase power at the voltage listed on the nameplate, along with the 0-10 VDC and 24V signal for speed control. NOTE: The motor will not operate without the proper control voltages. Operation and Wiring - Potentiometer Dial and 0-10V Input Part Numbers Covered in this Section 310359 311731 311377 311388 311812 312359 312360 312361 312362 312619 313233 313234 313235 313712 313713 313714 313715 314534 314945 316495 316496 316497 316498 316499 317706 317707 317708 317709 These motors have both a potentiometer dial on the motor for speed adjustment AND have the ability to accept a 0-10 VDC signal for remote speed control. NOTE The 9-pin connector on the motor contains 6 wires. The red, black and white wires are used for the external control signal and the other three are used for factory initialization and programing. 0-10V Analog input connection Red + 0-10 VDC White Common* Black +24 VAC/DC *Common is shared between both 24V power and 0-10V signal. The impedance of 0-10V circuit is 12KΩ There is a 4 second delay between the application of power and the motor starting. The motor is pre-wired at the factory and cannot be changed inside the motor. Connect single-phase power at the voltage listed on the nameplate. If remote control is desired, connect the 0-10 VDC and 24V signal for remote speed control. ® Vari-Green Motor and Controls 3 Troubleshooting Operation and Wiring Motor does not operate - Potentiometer and 0-10V Input 1. Check all wiring connections to ensure they are correct and secure. 2. Verify that all voltages are present at the motor, including 24V and 0-10 VDC, if applicable. 3. Make sure that the fan wheel will rotate freely and there are no foreign objects in the wheel. If fan wheel does not rotate freely, disconnect power from the motor and adjust the wheel or housing until the wheel can freely rotate. Apply power and the motor should restart. 4. If motor has both the dial on the motor and 0-10 VDC control option, control wiring issues can be tested by disconnecting the control wires from the motor. The motor should then operate using the dial on the motor for speed control. Motor will not reach maximum speed 1. Make sure dial is rotated full clockwise, if applicable. 2. Make sure motor is receiving 10 VDC, if applicable. 3. There are some motor/fan combinations where the motor may not reach nameplate RPM. See Max RPM table on page 11 for the maximum motor speed for your application. Factory Mounted Transformer (Fig. 1, page 2) A factory mounted transformer is available to supply 24 VDC power to the motor when the 0-10V signal is by others. This transformer has the capability to power a remote device if desired. The power available to a remote device is 400mA at 24 VDC. If the remote device is powered by a different source, connect the analog output to the 0-10V and COM terminals of the transformer. This will pass the signal through to the motor. Part Numbers Covered in this Section 318003 318004 318013 319356 319357 320587 320588 320589 320590 These motors have the ability to accept a plug in potentiometer for speed adjustment AND the ability to accept a 0-10V signal for remote control. There is a 4 second delay between the application of power and the motor starting. Motor part numbers 318003, 318004 – The motor is prewired at the factory and cannot be changed inside the motor. Connect single-phase power at the voltage listed on the nameplate. Motor part numbers 318013, 319356, 319357, 320587, 320588, 320589 and 320590 – The motor is prewired at the factory and can operate on 115v up to 277v. Operating voltage is changed via voltage jumper wire. Voltage jumper – For 115v the red jumper wire on the side of the motor must be connected (closed). For 208v-277v operation the red jumper must be disconnected (open). Dial on Motor – A potentiometer (p/n 385806) can be plugged into the 9-pin connector of the motor. To increase speed, rotate the dial clockwise. To decrease speed, rotate the dial counterclockwise. 0-10 VDC Signal – From 0-1.9V, the motor will be off, and will operate in the 2-10V range. A low voltage wiring harness is needed to supply the 0-10V signal to the motor. The harness is available from the factory if conversion is necessary. Low Voltage Harness Part Numbers Type Use with Motor 18 in. long 36 in. long 9-pin 318003, 318004, 318013, 319356, 319357, 320587, 320588, 320589, 320590 385821 385822 WARNING Do not connect an external 24V supply to the transformer's control terminal labeled 24V. If the external device providing the 0-10V signal is powered elsewhere, this terminal can remain unused. NOTE The 9-pin connector on the motor contains 6 wires. The yellow, orange, red and white wires are used for external control. The other two wires are used for factory initialization and programming. 0-10V Analog Input Connection 4 Vari-Green Motor and Controls Red + 0-10 VDC White Common ® Troubleshooting Motor does not operate 1. Verify the motor is wired correctly and all connections are secure. 2. If using dial on motor, verify the potentiometer is fully seated in the 9-pin connector. 3. If using 0-10 VDC, verify that all voltages are present at the motor. Motor does not reach maximum speed 1. Make sure dial is rotated full clockwise, if applicable. 2. Make sure motor is receiving 10 VDC, if applicable. 3. There are some motor/fan combinations where the motor may not reach nameplate RPM. See Max RPM table on page 11 for the maximum motor speed for your application. Part Numbers Covered in this Section 310420 311156 Features Speed control These motors can be controlled by either a dial on the motor or a 0-10 VDC signal for remote control. Soft start – All motors feature soft-start technology which eliminates inrush current at start-up. The motors will reliably start at any speed setting. There will be up to a 30 second delay between the application of power and the motor starting. The motor will "rock" back and forth upon startup as part of its normal operation. Overload protection – If the motor becomes overloaded, it will automatically shut itself down. The maximum programmed motor speeds have been selected to prevent this from happening in normal operation. Locked rotor protection – If the motor encounters a locked-rotor scenario, it will automatically shut itself down. It will try to restart up to 3 times, and if after the 3rd time the motor will still not rotate, the motor will not attempt to start again until power is cycled. Thermal protection – The motors have an automatic reset thermal protector. This is meant to protect the motor from a severe temperature rise. RPM measurement – The motor RPM can be measured by removing the cooling fan cover and using a contact or optical tachometer. Be sure to replace the cooling fan cover when finished. Reversible rotation – The motor direction has been pre-set at the factory for the rotation of the fan but can be reversed if necessary. Operation and Wiring These motors can be controlled by either a dial on the motor or a 0-10 VDC signal for remote control. The motor will be supplied from the factory with the correct accessory depending on what was ordered. Dial on Motor - Turn the dial with your fingers to adjust. To increase the speed, rotate the dial clockwise. To decrease the speed, rotate the dial counterclockwise. Turning the dial full Counter Clock Wise will turn the motor off. 0-10 VDC Signal - From 0-1.9V, the motor will be off, and will operate in the 2-10V range. This motor does not require 24V power for operation. ® Vari-Green Motor and Controls 5 0-10V Analog Input Connection Red + 0-10 VDC White Ground Wiring 1. All high and low voltage wiring connections are made inside the motor control box at the factory. Normally, there is no reason to enter the control box of the motor. If there is a need to enter the control box, disconnect power and wait at least five minutes to allow the capacitors to discharge. 2. The motors are factory wired for the ordered voltage. If the factory wired voltage does not match the desired voltage, the voltage can be changed, with exception of the 2HP motor (310420), which is 208‑240V only. 115V: Connect 115 VAC to L1, connect Neutral to N. The L2 terminal remains empty. Connect ground to grounding stud. Dial on Motor - the dial is factory-wired into the low voltage terminal block inside the control box. The wires are connected as shown. Dial on motor connection inside control box 0-10 VDC Signal - a two-wire pigtail is factory-wired into the low voltage terminal block. The wires are connected as shown. 0-10 VDC signal connection inside control box If the motor needs to be tested before the 0-10 VDC signal is available, a jumper can be placed between terminals 1 and 2. This will force the motor to run at full speed. Motor Rotation 115V Connection inside control box To reverse the rotation of the motor, swap any two of the red, black and blue wires connecting the control board to the motor at terminals T1, T2 and T3. Note that motor warranty is void if motor is rotating in the wrong direction. See fan instruction manual for correct rotation direction. 208-240V - Connect line voltage to L1 and L2. The N terminal remains empty. Connect the ground to the grounding stud. T3 Rotation selection wires inside control box 208-240V Connection inside control box 6 Vari-Green Motor and Controls ® Troubleshooting These motors have a diagnostic red LED on the circuit board inside the control box, or on the exterior of the control box, that will be solid (not flashing) when power is applied to the motor and the motor is operating normally. The LED may be solid even if the motor is not spinning, such as when power is applied but the motor may be commanded to be off with a 0-1.9V VDC signal. 1. If external LED is not present, to view the status of the LED the control box cover must be removed while power is applied to the motor. If the control box cover is removed while power is applied, extreme care must be taken not to touch any of the components inside the box. 2. If a fault occurs, the LED will blink a specific number of times to identify the fault that has occurred. The fault indications are as follows: Controls: Operation, Wiring and Troubleshooting Remote Dial/Touch Remote and 2-Speed Control Remote Dial Installation Overview: The remote dial is provided with the fan, shipped loose for remote installation. It also includes a factory mounted 24 VDC transformer. 1. Disconnect power to the fan. 2. Identify where the remote dial will be mounted. 3. Mount a standard single-gang 2x4 junction box. 4. Run a 3-wire control cable from the remote dial to the fan motor compartment. The maximum distance from the fan to the remote dial is 100 feet. If a greater distance is required, signal loss may occur and cause the fan to operate erratically. Number of Blinks Indicated Fault 2 Hardware Fault 3 Overvoltage 5. Connect control cable to transformer mounted inside fan motor compartment. Connect control cable to remote dial. 4 Undervoltage 6. Secure remote dial to 2x4 junction box. 5 Communication Error 6 Sync Loss 7 Spin Fault 8 Motor Overload 9 Motor Over Temperature 3. When the LED is blinking, it will consecutively blink from 2 to 9 times, followed by a pause, and repeat the blink sequence. It is best to count the number of flashes 2 or 3 times to ensure accuracy. 4. Under most fault conditions the motor will automatically restart. If a motor overload fault occurs more than 10 times in one hour, the motor will shut down and require a power cycle to reset. 5. If the fault persists, consult the factory. Remote Dial with Min/Max Setting Remote dials (P/N 385803) are capable of setting minimum and maximum voltage limits. Setting voltage limits will require a multi-meter. To set a voltage span: 1. Install and wire remote dial as previously instructed. 2. Install multi-meter probes into the red (0-10v) and black (ground) connectors. 3. To set maximum voltage limit, apply power to the motor, transformer and remote dial. With remote dial set to zero (0), hold the Upper Limit button down and turn the dial until the desired voltage is displayed on your multi-meter. Release button to save max voltage setting. 1. Verify the motor is wired for the correct voltage. 4. To set lower voltage, turn remote dial back to zero (0). Hold down Lower Limit button while turning dial to desired voltage on your multi-meter. Release button to set minimum voltage limit. 2. Verify that the dial on the motor is properly connected to the control board - or - verify that the 0-10 VDC wires are properly connected to the control board. 5. To reset to default (0-10v) limits, hold both Upper and Lower limit buttons down simultaneously until the LED indicator lights up. Then release buttons and default levels will be restored. Motor does not operate 3. Verify that the Status LED is solid red. 4. Verify that a jumper is in place between terminals 9 and 10. The motor will not run without this jumper in place. NOTE: Upper voltage limit must be set prior to setting lower voltage limit. Upper and lower limits can only be within 0.5v of each other. 5. Verify that the two yellow wires coming from the motor are in place on terminals 5 and 6. ® Vari-Green Motor and Controls 7 Touch Remote Follow installation instructions for remote dial above. After power is applied to the system, operate as follows: 1. Touch power button to turn fan on. Other Vari-Green® controls, such as the Constant Pressure and Air Quality families of controls, have their own manual that ship with the controller. They can also be found on Greenheck.com. See table on page 10 for document numbers. 2. Touch UP/DOWN arrow to increase/decrease speed. 3. Subsequent touches of the power button will start the countdown timer of 90, 60, 30 or 10 minutes. CAUTION Even though the motor may not be operating, high voltage power may still be present at the motor. Make sure to disconnect power to the fan before servicing. 4. LED's will turn off after a period of inactivity. 5. To lock/unlock buttons, hold the UP and DOWN arrows for 3 seconds. When locked, the power button will light up red. Remote Dial/Touch Remote Assembly Remote Dial/Touch Remote Assembly 100 ft. or less COM White Black* Red 24V 0-10V N.C. COM. N.O. COM 24V 0-10V COM 24V 0-10V 0-10V 24V COM Auxiliary Contact Control Motor *NOTE: Black wire not used on some motors Green indiator light —Power present Trip Point = 1.85VDC Contact Rating: 10A @ 24-240VAC 5A @ 30VDC REMOTE DIAL/ TOUCH REMOTE TRANSFORMER Low voltage, route away from high voltage lines and/or use shielded cable 2x4 Junction Box Factory Wiring Field Wiring 115/230 VAC input to match motor name plate Troubleshooting Remote Dial/Touch Remote Remote Dial with Min/Max Setting Remote Dial does not adjust motor RPM 1.Check voltage to ensure the motor and transformer are receiving the correct line voltage. Upper Limit Button Lower Limit Button 2.Check voltage at the remote dial. 24 VDC should be present across the 24V and COM terminals. 0-10 VDC should be present across the 0-10V and COM terminals. 3.Verify all of the connections at the transformer and make certain that they are secure. 4.Touch remote: Verify that the touch remote is unlocked. LED Indicator 5.To reset to default (0-10v) limits, hold both Upper and Lower limit buttons down simultaneously until the LED indicator lights up. Then release buttons and default levels will be restored. Terminals 24V-COM 0-10V-COM 8 Vari-Green Motor and Controls Desired Voltage 24 VDC Nominal 0-10 VDC (varies with dial position) ® Two Speed Assembly 115-230 VAC 115-230 VAC NEUTRAL SPDT Switch/Relay by others Factory Wiring Field Wiring Low voltage (<10V), route away from high voltage lines and/or use shielded cable 100' or less Red Black* White FACTORY MOUNTED 2 SPEED CONTROL Motor Out Dry Contact Input COM 24V 0-10V COM A B NEUTRAL L2(115V-230V) L1(115V-230V) Digital Input ® Speed A Adjustment Green indicator light —Power present Speed B Adjustment *NOTE: Black wire not used on some motors Digital Input Logic L1 or L2 = Speed B L1 and L2 = Speed A No input = Off 2x4 Junction Box 115/230 VAC Input to match motor name plate Two Speed Control Troubleshooting - Two Speed Control Installation Overview: The two speed control is factory mounted to the fan and may be set to provide any two speeds the application requires. It also includes a 24 VDC transformer. A green LED will be illuminated when the 2-speed control is powered. 1. Check all wiring connections to ensure they are correct and secure. 1. There are two methods of toggling between speed A and speed B: a. Dry contact input - this utilizes an external switching device such as a relay or SPDT switch to toggle between the two speeds. • Connect terminal “A” to “COM” for speed A. • Connect terminal “B” to “COM” for speed B. If no contact is made between either terminal the motor will be off. 2. Verify AC line voltage is present at the motor and 2-speed control. 3. Verify 24 `VDC is present at the 24V and COM terminals of the "Motor" terminal block. 4. Measure DC voltage between the 0-10V and COM terminals of the "Motor" terminal block. This voltage should match the dial position of the active dial. a. If using dry contact input - ensure contact closure is connecting the proper terminals. b. If using AC digital input - disconnect connector from 2-speed control and measure voltage between L1 and Neutral or L2 and Neutral. b. AC digital input - this input allows an AC voltage signal to be fed directly into the 2-speed control to change speeds. • Send 115-230V AC to L1 OR L2 for speed B. • Send 115-230V AC to L1 AND L2 for speed A. If no voltage is applied to either terminal, the motor will be off. c. DO NOT CONNECT BOTH DRY CONTACT AND DIGITAL INPUTS SIMULTANEOUSLY. 2. To test fan operation before the external control devices are installed, a jumper wire can be connected between the COM and A or B terminal on the dry contact input for fan operation. ® Vari-Green Motor and Controls 9 Motorized Backdraft Damper Control Motorized Damper Motorized damper operation with Vari-Green® Control (Motor/control wiring omitted for clarity) The available factory mounted transformer (PN 385253) has the ability to signal a motorized back draft damper to open/close as the motor starts/stops. To control To motor A N.O./N.C. set of contacts is provided which will change state when above or below a control voltage of 1.85 VDC. See wiring diagram for example. Contact Rating: • 10A @ 24-240 VAC N.C. COM N.O. COM 24V 0-10V COM 24V 0-10V • 5A @ 30 VDC Auxiliary Contact Control Motor Trip Point = 1.85VDC Contact Rating: 10A @ 24-240VAC 5A @ 30VDC Green indicator light —Power present FACTORY MOUNTED TRANSFORMER Neutral Line (Damper Power Source) Fans Where Dial on Motor is Not Accessible A control is available to mount on the outside of a fan where the dial on motor may be difficult to access (model SQ). This control is powered by the line voltage entering the fan and will send 24 VDC and 0-10 VDC to the motor. Control Part Number is 385611 Factory Wiring Field Wiring ® FACTORY MOUNTED SPEED CONTROL Voltage Present Input: 85-265VAC Output: 24VDC, 0-10VDC COM 24V 0-10V *NOTE: Black wire not used on some motors Red Black * White 2x4 Junction Box 115/230 VAC Input to match motor name plate 10 Vari-Green Motor and Controls ® Multiple Motors on One Control See the table below for the recommended number of motors to be driven from one controller. Note that the controllers do not have the ability to distinguish between more than one motor, therefore all motors will receive the same control voltage. Control voltage must be wired in parallel to all motors. Controls Max. Motor Quantity Remote Dial 4 2-speed 6 Constant Pressure/Airflow 4 Temperature/Humidity 2 VOC 2 Maintenance Vari-Green® motors use brushless technology with sealed bearings. No routine maintenance is required other than keeping any debris from accumulating on the motor and controls. Other Vari-Green® Control Instruction Manuals Description Document Number Indoor Air Quality - VOC 475407 Indoor Air Quality Temperature/Humidity 475573 Constant Pressure Control 474766 Generation 2 Constant Pressure/Airflow Control 479653 ® Vari-Green Motor and Controls 11 Maximum RPM Table SWD This table will show the available motor and fan combinations with the correlating maximum motor RPM for each combination. CUE/CW Max RPM Motor HP 60-90 1725 1/10 95 1725 1/6 99 1725 1/4 101 1725 1/4 1725 1/4 101HP 2500 1/2 1400 1/4 121 1725 1/2 1200 1/4 131 1450 1/2 1725 3/4 1000 1/4 1300 1/2 141 1550 3/4 1725 1 1450 1/4 141HP 1725 1/2 2200 3/4 1000 1/2 1200 3/4 161 1300 1 1725 2 1300 1/2 161HP 1650 3/4 1725 1 875 3/4 180 1000 1 1325 2 SQ 60-90 95 Max RPM Motor HP 1725 1/10 1725 1/6 1725 1/4 97 2500 1/2 1725 1/4 98 2200 3/4 1725 1/4 99 2200 3/4 100 1725 1/4 120 1725 1/2 130 1725 3/4 1250 1/4 130HP 1450 1/2 1950 3/4 1500 3/4 140 1725 1 1100 1/2 140HP 1450 3/4 1725 1 1140 3/4 160 1300 1 1725 2 850 1/2 1000 3/4 160HP 1600 1 1725 2 SFD 6 7.5 Max RPM Motor HP 1725 1/4 1725 1/2 7 8 10 13 15 16 18 Max RPM Motor HP 1725 1/4 2500 1/2 1725 1/4 2500 1/2 1725 1/4 2200 3/4 1200 1/4 1550 1/2 1725 3/4 1150 1/2 1400 3/4 1725 1 900 3/4 1300 1 1725 2 850 3/4 950 1 1300 2 SE1/SS1 Max RPM Motor HP 8-440* 1725 1/10 10-440* 1725 1/6 12-426 1725 1/4 12-432 1725 1/4 12-436 1725 1/4 14-432 1725 1/4 14-436 1725 1/2 14-440 1725 1/2 16-421 1725 1/2 16-426 1725 1/2 16-428 1725 3/4 16-436 1725 3/4 18-424 1725 3/4 18-429 1725 3/4 20-420 1725 1 G 60-90 95 97-99 103 103HP 123 133 143 143HP 163 183 LD/LDP 80-90 95 100 120 Max RPM Motor HP 1725 1/10 1725 1/6 1725 1/4 1725 1/4 1725 1/4 2500 1/2 1200 1/4 1725 1/2 1150 1/4 1550 1/2 1725 3/4 900 1/4 1200 1/2 1300 3/4 1725 1 1500 1/4 1725 1/2 2200 3/4 750 3/4 1200 1 1725 2 900 3/4 1000 1 1325 2 Max RPM Motor HP 1725 1/10 1725 1/6 1725 1/4 1725 1/2 SP/CSP Max RPM Motor HP 510 1200 1/6 710 1510 1/4 *SE1 Model Only Our Commitment As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice. Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library under Warranties. AMCA Publication 410-96, Safety Practices for Users and Installers of Industrial and Commercial Fans, provides additional safety information. This publication can be obtained from AMCA International, Inc. at www.amca.org. ® Phone: 715.359.6171 • Fax: 715.355.2399 • Parts: 800.355.5354 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com 12 473681 • Vari-Green Motor and Controls, Rev. 13, September 2017 Copyright 2017 © Greenheck Fan Corporation Document 475699 Universal Vari-Green® Control Assemblies ® Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with instructions could result in personal injury and/or property damage! This document is for transformer/2-speed controller mounting only. Reference the Vari-Green Motor Document No. 473681 for wiring details. NOTE There will be extra hardware and parts included with this kit that may not be used for your specific application. Section 1 For Motor Part Numbers 309025 309026 310107 310359 311377 311388 312359 312360 312361 313233 313234 313235 316495 316496 316497 317706 317707 317708 End of Motor Mounting (Fig. 2) For use on SE/SS Sidewall Prop units and SFD units • Fasten transformer to mounting bracket via (4) supplied screws (#10 x 1/2). • Attach bracket to end of motor via motor thru bolts. Fasten down with supplied nuts. • For a SFD make sure transformer is mounted under weatherhood. Fan Housing Mounting 310306 311731 312362 314534 316498 317709 310307 311812 312619 314945 316499 Side of Motor Mounting (Fig. 1) For use on SQ units • Fasten transformer directly to outside of unit via (4) supplied screws (#10 x 1/2). For use on SWD units • Fasten transformer to Drive Frame Angles using the pre-exisiting holes and the (4) supplied screws (#10 x ½) For use on G, CUE, CW, LD, and LDP units • Fasten transformer to mounting bracket via (4) supplied screws (#10 x 1/2). • Bend top of bracket away from transformer, by hand, along laser stitched line, forming a 90 degree angle. SWD-7 THRU 10 with transformer and switch • Attach bracket to top of motor via (2) motor thru-bolts. Fasten down with supplied nuts. Fig. 2 Fig. 1 ® Universal Vari-Green Control Assemblies 1 Section 2 For Motor Part Numbers 310420 311156 Drive Frame Mounting For use on G, CUE and CW units • Fasten transformer to mounting bracket via (4) supplied screws (#10 x 1/2). • Bend top of bracket away from transformer, by hand, along laser stitched line, forming a 90 degree angle. G/CUE with transformer mounted • Attach bracket to drive frame angles, using the pre-exisiting holes and the (2) supplied screws (#10 x ½). Fan Housing Mounting For use on SQ units • Fasten transformer directly to outside of unit via (4) supplied screws (#10 x 1/2). For use on SWD units • Fasten transformer to Drive Frame Angles using the pre-existing holes and the (4) supplied screws (#10 x 1/2). SWD-13 with transformer and switch Our Commitment As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice. Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library under Warranties. AMCA Publication 410-96, Safety Practices for Users and Installers of Industrial and Commercial Fans, provides additional safety information. This publication can be obtained from AMCA International, Inc. at www.amca.org. ® Phone: 715.359.6171 • Fax: 715.355.2399 • Parts: 800.355.5354 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com 2 475699 • Universal Vari-Green Control Assemblise, Rev. 4, February 2015 Copyright 2015 © Greenheck Fan Corporation Document 481307 SP Fan with CRD Plaster Flange Assembly ® Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with instructions could result in personal injury and/or property damage! Plaster Flange Assembly Note: This plaster flange assembly is only required when the damper is installed in a combustible (wood) floor/ceiling assembly. Figure 1 Tek Screws 14 PLCS Plaster Flanges When the damper is installed in a non-combustible (steel/concrete) ceiling/floor assembly, the plaster flange kit should be discarded. CRD Damper Plaster Flanges For applications where the damper is installed in a combustible (wood) floor/ceiling assembly, the plaster flanges must be installed onto the damper as shown in Figure 1. Width Height 1. Note the orientation of the plaster flanges to the damper as shown in Figure 1. 2. Align the edge of the short leg of the plaster flange with the bottom edge of the damper frame and center it along the length of the frame. 3. Clamp the plaster flange to the damper frame. When the damper is installed in a combustible (wood) floor/ceiling assembly, the flange will lay on top of the drywall ceiling membrane; as shown in Figure 2. 4. Using the holes in the plaster flange as a guide, secure the flange to the damper frame using the supplied self-drilling Tek screws. Figure 2 5. Repeat this process on all four sides of the damper. 1 2 5 6 4 3 4 1. Fan/Damper Assembly 2. Mounting Angle 3. Plaster Flange 4. Gypsum Board 5. Grille 6. RC Channel 5 ® Phone: 715.359.6171 • Fax: 715.355.2399 • Parts: 800.355.5354 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com 481307• SP Fan with CRD, Rev. 1, October 2015 Copyright 2015 © Greenheck Fan Corporation PN 453380 RDC-8 - Duct Conversion ® Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Report any damaged equipment to the shipper immediately. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with instructions could result in personal injury and/or property damage! Removal of Original Rectangular Outlet: Attachment of New Round Outlet: 1. Remove the four (4) sheet metal screws that hold the duct connector to the blower box assembly on the discharge side. Refer to Figure 1. 2. Attach the round duct connector to the blower box assembly using the four (4) original sheet metal screws. Refer to Figure 2. Sheet Metal Screws Discharge Side Figure 1 Sheet Metal Screws Figure 2 Discharge Side Warranty Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the purchase date. Any units or parts which prove defective during the warranty period will be replaced at our option when returned to our factory, transportation prepaid. Motors are warranted by the motor manufacturer for a period of one year. Should motors furnished by Greenheck prove defective during this period, they should be returned to the nearest authorized motor service station. Greenheck will not be responsible for any removal or installation costs. As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice. Greenheck Catalogs for inline fans provides additional information describing the equipment, fan performance, available accessories, and specification data. ® AMCA Publication 410-96, Safety Practices for Users and Installers of Industrial and Commercial Fans, provides additional safety information. This publication can be obtained from AMCA International, Inc. at: www.amca.org. Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com 453380 • RDC-8 Duct Conversion, Rev. 3, September 2008 Copyright 2008 © Greenheck Fan Corp 1 model FSD-142-OP 11/2 hour • UL class 2 — combination fire smoke damper actuator in the airstream — out-of-partition Maximum UL555S Rated Pressure: 4 in.wg. (1.0 kPa) Maximum Temperature: 350°F (177°C) Listings Meets NFPA Standards: 90A, 92A, 92B and 101 E AT R A New York City MEA listing: 295-98-E TIN I SOF CALIFO G E TE F IR E MAR SH E CSFM listing: 3225-0368:110 and 3230-0368:111 L UL 555 and 555S listing: R11767 NI Sleeve: 20 gauge (1.0) galvanized steel with 1" (25) flange and factory installed thermal insulation on four sides. Maximum Dynamic Closure Velocity: 2,000 fpm (10.2 m/s) S Blades: 6" ¥ 16 gauge (152 ¥ 1.5) galvanized steel — triple-V. UL 555S Leakage Class: 2 [20 cfm/sq.ft. @ 4 in.wg.] [(0.10 m3/s/m2 @ 1.0 kPa)] A ST Frame: 5" ¥ 1" (127 ¥ 25) galvanized steel hat channel with interlocking corner gusset. Equivalent to 13 gauge (2.4) channel frame. Low profile head and sill are used on sizes less than 13" (330) high. UL 555 Fire Resistance Rating: 11/2 hour (vertical and horizontal) ST Standard Construction Ratings L The FSD-142-OP combination fire smoke damper employs triple-V blades for point-of-origin control of fire and smoke in static and dynamic smoke management systems. These specialty dampers are approved for installation with the closed plane of the blades up to 141/2" (368) outside the fire rated partition and come standard with the actuator in the airstream allowing for direct service access from the face of the damper through the HVAC grille. The FSD-142-OP is qualified to 2,000 ft/min (10.2 m/s) and 4 in.wg. (1.0 kPa) and may be installed in vertical walls and partitions, or horizontally in floors or assemblies with fire resistance ratings up to 2 hours. AL Application R VI C Meets Building Code Standards: IBC, NBC, NFPA, SBC and UBC Axles: 1/2" (13) diameter plated steel hex. Linkage: Concealed in frame. Bearings: Stainless steel oilite, sleeve-type. Seals: Silicone blade edge seals and flexible metal jamb seals. Actuator: 120 VAC, power-open, spring-close, internal mount. Fire Closure Device: HS-10 (electric actuators) PFV (pneumatic actuators) Fire Closure Temperature: 165°F (75°C). Minimum Size: 10" ¥ 6" (254 ¥ 152) Maximum Size: 36" ¥ 48" (914 ¥ 1219) Options Fire Smoke Dampers FSD142OP (1/2) November 2017 o Alternate actuator: o External Mount o Pneumatic o 24 VAC o 230 VAC o DRS-30 — Two temperature fire closure device. (Includes PI-50 switch package) o PI-50 — Dual position indicator switch package. o Alternate factory installed sleeve: Gauge: o 18 (1.3) o 16 (1.6) o 14 (2.0) o 10 (3.5) o Transitions: o Round o Oval o Duct connections: o 1" (25) S-clip o DM25 o DM35 o WARD o Alternate fire closure temperature: o 212°F (100°C) o 250°F (121°C) o 350°F (177°C). Model FSD-142-OP (standard) *Standard sleeve O.D. including thermal blanket wrap, is approximately 3/8" (9) over nominal duct size. Standard sleeve I.D. is approximately nominal duct size. NOTE: The opening for the damper assembly in the fire wall must be sized appropriately. If not, serious damage to the thermal blanket wrap could occur and this will nullify the U.L. rating. Contact the factory if necessary for additional information. o Duct smoke detector factory mounted and wired: o 2151 (0-3,000 fpm [0-15.2 m/s]) o Remote control stations: o RCP-1 (single) o RCP-1K (single, key controlled) o RCP-1M (single, momentary switch) Information is subject to change without notice or obligation. POTTORFF ® 5101 Blue Mound Road, Fort Worth, Texas 76106 NOTE: Dimensions in parentheses ( ) are millimeters. www.pottorff.com Actuator and Sleeve Dimensional Data The drawings and corresponding table show the position of the damper when mounted in a factory sleeve and the relative space required for a given actuator. The standard mounting locations provide enough space for installation of retaining angles and duct connections. Actuator Model X Dimension Minimum Damper Size (w x h) FSTF120 10" (254) (H < 15") 6" (152) (H ≥ 15") FSLF120/24 11" (279) (H < 15") 6" (152) (H ≥ 15") (254 x 152) FSNF120/24 14" (356) (H < 18") 11" (279) (H ≥ 18") (254 x 254) ML4115/8115 MS4209/8209 101/2" (267) (H < 13") 71/2" (191) (H ≥ 13") (254 x 203) 331-4826 N/A 8" (203) (H ≥ 20") (254 x 508) NOTE: 14-1/2" (368) Max. 10" x 6" (254 x 152) 10" x 6" 10" x 10" 10" x 8" 10" x 20" 3-1/4" (83) X 5" (127) 1. Damper may be rotated 180° to position actuator on right side. 2. For dimensions on actuators not shown above, contact factory. 3. If actuator is ordered with optional external mount, sleeve flange should be ordered loose, for field assembly. Sleeve Length 10" (254) + X 1-3/4" (44) 3/4" (19) Airflow Performance Data Pressure Loss vs. Velocity Figure 5.2 — Ducted Inlet Figure 5.5 Plenum Mount Pressure drop testing was performed in accordance with AMCA Standard 500-D using the three configurations shown. All data has been corrected to represent air density of 0.075 lb/ft. Actual pressure drop in any ducted HVAC system is a combination of many elements. This information, along with analysis of other system influences, should be used to estimate actual pressure losses for a damper installed in a given HVAC system. 5D 5D 6D Ducted Inlet and Outlet AMCA Figure 5.3 Illustrates a fully ducted damper. This configuration represents the lowest pressure drop of the three test configurations because entrance and exit losses are minimized by straight duct runs upstream and downstream of the damper. Ducted Inlet AMCA Figure 5.2 Illustrates a ducted damper exhausting air into an open area. This configuration has a lower pressure drop than Figure 5.5 because entrance losses are minimized by a straight duct run upstream of the damper. Information is subject to change without notice or obligation. POTTORFF ® 5101 Blue Mound Road, Fort Worth, Texas 76106 Plenum Mount AMCA Figure 5.5 Illustrates a plenum mounted damper. This configuration has the highest pressure drop because of extremely high entrance and exit losses due to the sudden changes of area in the system. NOTE: Dimensions in parentheses ( ) are millimeters. www.pottorff.com Fire Smoke Dampers FSD142OP (2/2) November 2017 Figure 5.3 — Ducted Inlet and Outlet I N STALL AT ION & O PERATIO N MANUAL SINGLE DUCT TERMINAL Redefine your comfort zone. ™ | www.titus-hvac.com IOM S IN G LE DUC T T E RMI N A L IM P ORTAN T ! R EAD B E F O R E P R O C E E DI N G ! G E NE R A L S AFE T Y G U ID E L IN E S This equipment is a relatively complicated apparatus. During installation, operation maintenance or service, individuals may be exposed to certain components or conditions including, but not limited to: refrigerants, UV, materials under pressure, rotating components, and both high and low voltage. Each of these items has the potential, if misused or handled improperly, to cause bodily injury or death. It is the obligation and responsibility of operating/service personnel to identify and recognize these inherent hazards, protect themselves, and proceed safely in completing their tasks. Failure to comply with any of these requirements could result in serious damage to the equipment and the property in which it is situated, as well as severe personal injury or death to themselves and people at the site. This document is intended for use by owner-authorized operating/ service personnel. It is expected that these individuals possess independent training that will enable them to perform their assigned tasks properly and safely. It is essential that, prior to performing any task on this equipment, this individual shall have read and understood this document and any referenced materials. This individual shall also be familiar with and comply with all applicable governmental standards and regulations pertaining to the task in question. Safety Symbols The following symbols are used in this document to alert the reader to areas of potential hazard: danger caution indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. identifies a hazard which could lead to damage to the machine, damage to other equipment and or environmental pollution. Usually an instruction will be given, together with a brief explanation. warning note indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. 2 IOM - Single Duct Terminal is used to highlight additional information which may be helpful to you. Redefine your comfort zone. ™ | www.titus-hvac.com C HA NGE A BI L IT Y OF T H IS D OCU M E N T In complying with Titus’ policy for continuous product improvement, the information contained in this document is subject to change without notice. Titus makes no commitment to update or provide current information automatically to the manual owner. Updated manuals, if applicable, can be obtained by contacting the nearest Titus office or accessing the Titus website. CHANGE BARS Revisions made to this document are indicated with a line along the left or right hand column in the area the revision was made. These revisions are to technical information and any other changes in spelling, grammar or formatting are not included. Operating/service personnel maintain responsibility for the applicability of these documents to the equipment. If there is any question regarding the applicability of these documents, the technician should verify whether the equipment has been modified and if current literature is available from the owner of the equipment prior to performing any work on the unit. Redefine your comfort zone. ™ | www.titus-hvac.com IOM - Single Duct Terminal 3 IOM S IN G LE DUC T T E RMI N A L Table of Contents General Safety Guidelines...............................................................................................................................................2 Safety Symbols................................................................................................................................................................2 Changeability of this Document......................................................................................................................................3 Table of Contents.............................................................................................................................................................4 Figure(s) .........................................................................................................................................................................4 Table(s) .........................................................................................................................................................................4 Section 1 Receiving Inspection.......................................................................................................................................................5 Supporting the Assembly................................................................................................................................................5 Duct Connections............................................................................................................................................................5 Field Wiring......................................................................................................................................................................6 Control Start-up, Operation.............................................................................................................................................6 Calibration Instructions...................................................................................................................................................6 Replacement Parts...........................................................................................................................................................6 Figure(s) Figure 1 - Single Duct Recommended Hanger Bracket Locations...............................................................................5 Table(s) Table 1 - Replacement Parts..........................................................................................................................................6 4 IOM - Single Duct Terminal Redefine your comfort zone. ™ | www.titus-hvac.com Section 1 Receiving Inspection After unpacking the terminal, check it for shipping damage. If any shipping damage is found, report it immediately to the delivering carrier. Store units in a clean, dry location prior to installation. Also, inspect damper rotation of the unit by rotating the damper by hand to check for free movement, and ensure there is no damage or binding of the damper. If controls are connected to the damper, release the manual clutch (most controls are equipped with this) and rotate the damper by hand. If there is any restriction to the rotation of the damper, contact your Titus rep and inform them of this issue. caution Do not use the flow sensor, connecting tubing, or damper shaft linkage as a handle to lift or move assembly. Damage to the flow sensor or controls may result. Supporting the Assembly The diameter of the inlet duct “D” in inches must be equal to the listed size of the terminal; e.g. a duct that actually measures 8 inches must be fitted to a size 8 terminal. The inlet collar of the terminal is made 1/8 inch smaller than listed size in order to fit inside the duct (see Figure 1). note Do not insert duct work inside the inlet collar of the assembly.Inlet duct should be installed in accordance with SMACNA guidelines. The outlet end of the terminal is designed for use with slip and drive duct connections. A rectangular duct the size of the terminal outlet should be attached. Inspect the Aerocross inlet flow sensor for shipping damage, and ensure that the high (green) and low (red) tubes are attached. Provide at least 1½times the inlet duct diameter of straight duct for optimum control accuracy. For more information on our Aerocross, see the Aerocross Flow Sensor Application Guide. AssemblyMany basic single duct terminals are light enough to be supported by the duct work itself. Where heavier accessory modules, such as DDC controls, coils, attenuators, or multiple outlets are included, the terminal should be supported directly. Straps screwed directly into the side of the terminal, threaded rod through the optional hanger brackets (see Figure 1), or the method prescribed for the rectangular duct on the job specifications may be used. Important: If equipped with pneumatic controls, the terminal must be mounted right side up. It must be level within+ or -10 degrees of horizontal, both parallel to the air flow and at the right angle of air flow. The control side of the terminal is labeled with an arrow indicating UP. The first letter of the model number (P) indicates pneumatic controls. Most electronic units (A-analog controls and D-digital controls) can be installed in any orientation. Check with the local TITUS representative for verification. Duct Connections Slip each inlet duct over the inlet collar of the terminal. Fasten and seal the connection by the method prescribed by the job specification. Redefine your comfort zone. ™ | www.titus-hvac.com Figure 1 - Single Duct Recommended Hanger Bracket Locations IOM - Single Duct Terminal 5 IOM S IN G LE DUC T T E RMI N A L Section 1 - General Information Field Wiring All field wiring must comply with the local codes and with the National Electrical Code (ANSI/NFPA 70-1981). Electrical, control and piping diagrams are shown on the exterior labeling or on the diagram on the inside of control enclosure cover. All electric heaters if provided by TITUS are balanced by kW per stage. The installing electrician should rotate these heater stages by phase in order to help balance the building electric load. Control Start-up, Operation Detailed information regarding power, accessory and communications connections, start-up and operating procedures for the controls provided by TITUS are available from your local TITUS representative. For specific information on controls by other manufacturers, contact that manufacturer’s local branch or dealer. Important: Units with digital controllers may incorporate specific communication addresses based on Building Management Systems Architecture, and original engineering drawings. Installing the terminal in a different location than noted on unit label may result in excessive start-up labor. Calibration Instructions Size 4-5-6” Size 7” Size 8” Size 9” Size 10” Size 12” Size 14” Size 16” 31171301 31171302 31171303 31171304 31171305 31171306 31171307 31171308 Damper Shaft Extension Short Stub all sizes Long Ext. Sz. 4-6, 14, 16 Long Ext. Sz. 7-12 Shaft Bearing - All 70300301 70300302 70300303 70324901 Control Tube Red Stripe 1/4” O.D. Green Stripe 1/4” O.D. Red Stripe 3/8” O.D. Green Stripe 3/8” O.D. Yellow Stripe 1/4” O.D. White Stripe 1/4” O.D. Blue Stripe 1/4” O.D. Plastic 1/4" Plastic 3/8” For Analog Controls: Titus TA1, see ANA-IOM: Analog Controller Calibration. 61510035 61510234 61510279 61510280 61510260 61510261 61510262 42150011 42150020 Plugs for tees 1/4" 3/8” For Digital Controls: see control manufacturer’s manualReplacement 42160081 10015601 AeroCross™ Multipoint Velocity Sensors Table 1 - Replacement Parts IOM - Single Duct Terminal Part Number Tees for sensor taps For Pneumatic Controls, see PNEU-IOM: Operations Manual for Pneumatic Controls. 6 Description Primary Damper Assembly Size 4" Size 5” Size 6” Size 7” Size 8” Size 9” Size 10” Size 12” Size 14” Size 16” Size 24” x 16” 3151520001 3151520001 3151520002 3151520003 3151520004 3151520005 3151520006 3151520007 3151520008 3151520009 3151520009 Redefine your comfort zone. ™ | www.titus-hvac.com Notes Redefine your comfort zone. ™ | www.titus-hvac.com IOM - Single Duct Terminal 7 605 Shiloh Rd Plano TX 75074 ofc: 972.212.4800 fax: 972.212.4884 Redefine your comfort zone. ™ | www.titus-hvac.com