1294 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 20, NO. 6, NOVEMBER 2005 Active-Clamp Snubbers for Isolated Half-Bridge DC–DC Converters Hong Mao, Songquan Deng, Jaber Abu-Qahouq, Member, IEEE, and Issa Batarseh, Senior Member, IEEE Abstract—In conventional isolated half-bridge dc–dc converters, the leakage-inductance-related losses degrade converter efficiency and limit the ability to increase the converters’ switching frequencies. In this paper, a novel active-clamp snubber circuit for halfbridge dc–dc converters is proposed to recycle the energy stored in the leakage inductance by transferring this energy to a capacitor with zero-voltage zero-current-switching switched auxiliary switches, such that body-diode conduction of primary-side main switches are prevented and primary side ringing are attenuated resulting in improved converter efficiency. Principles of operation and simulation analysis are presented and supported by experimental results that show significant improvement in efficiency. Index Terms—Active-clamp, converter, dc–dc, half-bridge, isolation, leakage inductance, reverse recovery, snubber, topology, transformer. I. INTRODUCTION I N ISOLATED dc–dc converters, the isolation transformer leakage inductance is an important factor that affects the performance of converters. A variety of topologies and control methods are proposed to improve the converter performance by utilizing the transformer leakage inductance [1]–[7]. The phaseshifted full-bridge [1] and the active-clamp forward [2] dc–dc converters are good examples to utilize the transformer leakage inductance to achieve zero-voltage-switching (ZVS) and further reduce electromagnetic interference (EMI) noise. There are two conventional control schemes for half-bridge dc–dc converters, namely, asymmetric control [3]–[5] and symmetric control [6]–[8]. Symmetric controlled half-bridge dc–dc converter [6]–[10] has simple configuration and operates with symmetric components stresses. However, the two primary switches operate at hard switching condition and there exist leakage-inductance-related ringing losses and problems. To damp such ringing, usually, dissipative snubber circuits are employed across switches, resulting in leakage inductance energy dissipated in the snubber circuits. Consequently, the efficiency is degraded and the power level is limited. Asymmetric control scheme applies two complementary signals to the two half-bridge switches. Due to the small dead time Manuscript received September 17, 2004; revised March 24, 2005. Recommended by Associate Editor C. K. Tse. H. Mao is with the Astec Power Advanced Technology Division, Emerson Network Power, Andover, MA 01810 USA (e-mail: hongmao@astec.com). S. Deng is with Synqor, Inc., Boxboro, MA 01719 USA. J. Abu-Qahouq was with the Department of Electrical and Computer Engineering, University of Central Florida, Orlando, FL 32816 USA. He is now with Intel Corporation, Hillsboro, OR 97124 USA. I. Batarseh is with the Department of Electrical and Computer Engineering, University of Central Florida, Orlando, FL 32816 USA. Digital Object Identifier 10.1109/TPEL.2005.857529 between two switches, the primary-side ringing problem is eliminated and ZVS for both switches can be achieved with the help of the transformer leakage inductance [3]–[5]. However, asymmetric half-bridge converter suffers from the asymmetric components stresses distribution in the corresponding components and a dc bias in the transformer. Therefore, it is not suitable for applications with wide input-voltage range [3], [5]. Furthermore, the dc gain of the asymmetric-controlled half-bridge converter is nonlinear [5], resulting in lower duty cycle at high line voltage compared to the symmetric-controlled half-bridge converter, which results in degrading the converter performance at high line input. An active current clamping method was proposed in [6], [7] to achieve ZVS of switches and to attenuate the ringing. During the off-time interval (when both switches are turned off), the leakage inductance current freewheels through the auxiliary circuits. Before turning on the main switches, auxiliary switches interrupt the freewheeling path, such that the energy in the leakage inductance is released to create ZVS condition for main switches. However, this method has two main demerits: The first is that the value of the leakage inductance should be high enough, and the other is that high circulating current exists especially at low duty cycle. This means that this scheme is not suited for applications with wide-range of input voltage. In [8] and [10], duty-cycle-shift (DCS) controlled ZVS half-bridge topologies are proposed. However, it has similar disadvantage, which is that circulating conduction loss increases significantly at high line input due to long freewheeling time. In this paper, a new active-clamp snubber circuit is proposed to clamp the leakage inductance current and damp the ringing during the off-time interval. In the proposed circuit, the energy in the transformer leakage inductance is transferred to a capacitor during the off-time interval, hence, the ringing is eliminated and the switches’ body diodes never conduct. As a result, there is no body diodes’ reverse recovery and the ringing losses are minimized. As the current-transferring interval accounts for a small part of the switching period, the conduction loss during the off-time interval is reduced significantly. The next section presents the proposed active-clamp snubber topology and discusses the modes of operation. The main features and design considerations of the converter are provided in Section III. Section IV gives simulation and experimental verification, and conclusions are given in Section V. II. PROPOSED ACTIVE-CLAMP LOSSLESS SNUBBER A. The Ringing Issue and the Principle of Snubber Circuits Fig. 1 shows the conventional half-bridge dc–dc converter is the transformer with current doubler rectification, where leakage inductance and and are junction capacitances 0885-8993/$20.00 © 2005 IEEE Authorized licensed use limited to: ULAKBIM UASL - YILDIZ TEKNIK UNIVERSITESI. Downloaded on August 03,2010 at 12:53:39 UTC from IEEE Xplore. Restrictions apply. MAO et al.: ACTIVE-CLAMP SNUBBERS Fig. 1. 1295 Half-bridge isolated dc–dc converter. Fig. 3. Proposed active-clamp snubber circuits in half-bridge dc–dc converters: (a) topology A and (b) topology B. termined by the junction capacitances and input voltage as follows: (1) Fig. 2. Equivalent circuits during the freewheeling period: (a) without snubber and (b) with clamp circuit. of metal-oxide semiconductor field-effect transistor (MOSFET) switches and , respectively. and During the freewheeling period, when both switches are off, the transformer secondary is shorted by the two conducting diodes. By neglecting other parasitic capacitances and stray inductances, the equivalent circuit of the freewheeling mode is shown in Fig. 2(a). It should be noted that the switches’ junction capacitance values are smaller than and capacitance values, and the voltages across and can be assumed constant during the modes. If the two body diodes are ideal, the energy in the leakage inductance will be recycled to the dc bus through the two body diodes with undamped oscillation between the transformer leakage inductance and the junction capacitances. The energy involved in the oscillation is de- where is the individual MOSFET’s junction capacitance. However, body diodes of the MOSFETs have undesirable reverse-recovery characteristics, especially for high voltage rating MOSFETs, which results in more energy involved in the oscillation. As a result, the ringing is more severe and there are more reverse-recovery and ringing losses due to the nonideality of MOSFETs’ body diodes. Moreover, the ringing and reverse recovery may lead to EMI problems. Usually, snubber circuits are added to damp such ringing. The ) series snubber across a switch or transresistor–capacitor ( former primary windings is the most common snubber circuit. Depending on the size of the snubbers, the energy remained in the leakage inductance may be partly recycled to the dc bus, or totally dissipated in the snubbers. For a small snubber, body diodes conduct to partly recycle the energy with part of energy dissipated in the snubber. For a large snubber, the energy in the leakage inductance may be fully dissipated in the snubber without recycling through MOSFETs’ body diodes. In the later case, the power losses increase significantly with the increase of primary-side peak current, input voltage and switching frequency. B. Proposed Active-Clamp Snubber A clamping concept is proposed as shown in the dashedline frame of Fig. 2(b). With the proposed clamping snubber, Authorized licensed use limited to: ULAKBIM UASL - YILDIZ TEKNIK UNIVERSITESI. Downloaded on August 03,2010 at 12:53:39 UTC from IEEE Xplore. Restrictions apply. 1296 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 20, NO. 6, NOVEMBER 2005 and is blocked. Considering the possibility to through use Schottky diode for , the diode reverse recovery can be eliminated. However, with zero current leakage inductance current and 0, the circuit does not reach steady state and the voltage across will cause the voltage to oscillate until . Since the voltage across is much smaller than half of the input voltage, the MOSFETs’ body diodes will not be involved in the oscillation, and thus, the ringing is negligible. Therefore, there are no body-diode-related losses and , since both the voltage the ringing loss is very small. At across and the current through are zero, can be turned off with ZVZCS. Mode 3 : is turned on at causing the leakage inductance current to start charging from zero at the following slope: (2) Fig. 4. Key theoretical waveforms of the proposed topology. the energy in the leakage inductance can be recycled into the voltage sources. It is important to note that the diodes used in the snubber circuits have better characteristics than body diodes of the MOSFETs. Employing this clamping concept, a variety of practical active-clamp snubber circuits are proposed as shown in Fig. 3, where the capacitor acts as a voltage source to be used to absorb the energy in the leakage inductance and damp the ringing. In Fig. 3(a), the diodes and are external fast-recovery diodes, to simplify the circuit, body diodes of switch and can replace diodes and as shown in Fig. 3(b). Both topologies have the same drive timing and principle of operation. Basically, during the freewheeling period when both switches are off, since the transformer secondary side is shorted, the leakage inductance energy cannot be delivered to output, and the middle branch provide paths to transfer the leakage induc. tance energy to the capacitor The topology of Fig. 3(a) is taken here as an example to analyze the principle of operation, with the key operational waveforms shown in Fig. 4. To simplify the analysis of the operation modes, components are considered ideal except otherwise indicated. The main equivalent operation modes are shown in Fig. 5, and described as follows. Mode 1 : Initially, it is assumed that was conducting and was turned on at zero-voltage-zero-current-switching (ZVZCS). At , is turned off, causing the primary current to charge the junction capacitance and discharge . When the voltage across is charged to a half of the input voltage V , the leakage inductance current will flow through , , and . Considering the fact that the transformer secondary is shorted and there is a dc voltage across , the leakage current continues to charge the capacitor until the current resets to zero at . At the end of this mode, all the energy in the leakage inductance is transferred to the capacitor . : Since the diode blocks any poMode 2 tential reverse current in its branch, the reverse oscillation path where is the voltage across the capacitor . The smaller the leakage inductance is, the faster its current charge-up will be, until it becomes equal to the reflected inductor current, causing the diode to be blocked and the converter to start transferring energy from the primary-side to the secondary-side. This current will continue to charge at a slope of (3) where is the secondary inductor, and are the transformer primary number of turns and secondary number of turns, respectively, and is the output voltage. During this interval, the inductor current is charged and the capacitor is discharged. The polarity of the voltage across the capacitor will reverse during this interval. The auxiliary switch is turned on with ZVZCS since the diode block the current. During this mode, the capacitor is charged linearly by the reflected output current. Assuming that the output current is constant during this mode, the reflected current through the is given by capacitor (4) The capacitor voltage changes during this mode and is given by (5) where ; and are transformer primary and secondary number of winding turns, respectively. Ignoring the capacitor voltage change due to resetting leakage inductance current, the capacitor voltage can be described as follows: (6) Mode 4 : This mode is similar to mode 1. is turned off at , causing the primary current to charge and to discharge . When the voltage across is Authorized licensed use limited to: ULAKBIM UASL - YILDIZ TEKNIK UNIVERSITESI. Downloaded on August 03,2010 at 12:53:39 UTC from IEEE Xplore. Restrictions apply. MAO et al.: ACTIVE-CLAMP SNUBBERS 1297 Fig. 5. Modes of operation: equivalent circuits. charged to half of the input voltage, the leakage inductance current flows through , , and . Considering the fact thatthe transformer is shorted and there is a dc voltage across , the until the leakage current continues to charge the capacitor current resets to zero at . At the end of this mode, all the energy in the leakage inductance is transferred to the capacitor . At the end of Mode 3, the capacitor voltage is : This mode is similar to mode 2. After Mode 5 minor oscillation, this mode will end with (7) (10) is large enough and the Assuming that the capacitor leakage inductance current is linearly reset to zero, the capacitor voltage stays almost constant during this mode. The leakage inductance current at is equal to the reflected output current and is given by (11) (8) The duration time of this mode can be obtained as (9) 0. At , the switch can be turned off where with ZVZCS in the same manner described in mode 2 for . will be derived in Section III. : This mode is similar to mode 3. Mode 6 The switch is turned on and the converter starts to deliver Authorized licensed use limited to: ULAKBIM UASL - YILDIZ TEKNIK UNIVERSITESI. Downloaded on August 03,2010 at 12:53:39 UTC from IEEE Xplore. Restrictions apply. 1298 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 20, NO. 6, NOVEMBER 2005 energy from the primary-side to the secondary-side. At is turned on with ZVZCS. the auxiliary switch , III. MAIN FEATURES AND DESIGN CONSIDERATIONS A. Main Features As discussed earlier, with the proposed active-clamp snubber, the energy in the leakage inductance is transferred to the capacitor instead of being dissipated in dissipative snubbers. Furthermore, the body diodes of main switches are not involved in the oscillations, such that the switches’ body-diodes conduction losses and reverse-recovery losses are eliminated. and are turned on with ZVZCS The auxiliary switches and turned off with ZVZCS. Therefore, the switching losses are minimized. Since the conduction intervals of the auxiliary circuit only account for a very short portion of the whole period, the auxiliary switches and diodes conduction losses are negligible. In addition, all components’ voltage stresses in the middle branches are half of the input voltage. Therefore, lower voltage and current rated components with lower gate charge can be chosen for auxiliary components. The auxiliary circuits losses are limited compared to the leakage inductance ringing losses. When the main switches are turned off, the leakage inductance current starts to reset toward zero as shown in Fig. 6(a), where is reset time of leakage inductance current, and and are the on-time and off-time of the two main , the operation is the same switches, respectively. If as described earlier, and the primary voltage and current are as shown in Fig. 6(a). However, if , there is not enough time for the leakage inductance to transfer the energy to the capacitor . When the auxiliary switches are turned off, the remained leakage inductance energy is used to charge/discharge the main switches junction capacitance. In this case, ZVS may be achieved for the main switches, and the corresponding waveforms of the primary voltages and currents are shown in Fig. 6(b). In other words, depending on the duty cycle width, the proposed snubber topology has two possible operation cases: The small-duty-cycle case, where the converter operates with the active-clamp mode to reduce ringing problem, and the large-dutycycle case, where the active-clamp interval is reduced, such that the energy in the leakage inductance will be directly used to achieve ZVS for the main switches instead of being transferred into the capacitor . Therefore, this topology is suited for wide input voltage range. At high line, the converter reduces the energy circulation conduction losses, and at low line, the converter reduces the switching losses. can be written as The reset time Fig. 6. Two possible operation schemes for the proposed converter: (a) and (b) . T T <T T > where is the converter output current. value can be designed to approximately achieve V 10 20 V at full load. can be removed. At this case, As a matter of fact, capacitor the leakage inductance energy is trapped in the middle branch and the main switches have higher possibilities to achieve ZVS using the trapped energy compared to the first case with the capacitor . However, conduction loss may be significant at low duty cycle operation. In order to determine if the capacitor is better to be added or not, an appropriate loss comparison can be made based on this following analysis. , assuming the leakage inFor the case without capacitor ductance current keeps constant during the freewheeling times (1-2D) T, the conduction loss can be estimated as follows: (14) (12) is the duty cycle that where is the switching period and satisfies . As shown in (12), is independent of the load, which simplifies the design for the capacitance . The voltage stress in is given by (13) is the leakage inductance current value during the where freewheeling mode when two main switches are off, is the on-resistance of Switch or , V is forward voltage drop across body diodes of Switch or . By substituting (8) into (14), the conduction loss can be written as (15) Authorized licensed use limited to: ULAKBIM UASL - YILDIZ TEKNIK UNIVERSITESI. Downloaded on August 03,2010 at 12:53:39 UTC from IEEE Xplore. Restrictions apply. MAO et al.: ACTIVE-CLAMP SNUBBERS 1299 In the proposed converter, when , the main switches operate at hard switching, and the switching loss is calculated as follows: (16) is the transition time of switches. The total where switching loss of the two switches can be approximated by (17) and values at certain converter Depending on operating points, the tradeoff between using or not can be made accordingly under the guidance of the above equations. It should be noted that it is difficult to estimate the switching loss accurately and the equations given above are only for rough estimation. Compared to the phase-shift full bridge dc–dc converter, in the proposed converter stand only half of Switches and the input voltage versus the full input voltage in the full bridge converter, and they act as auxiliary switches and carry smaller RMS currents. Moreover, both switches and operate at soft switching. In addition, the proposed half-bridge dc–dc converter has options to make design tradeoff of choosing various capacitor value which provide design flexibility according to specific applications. B. Converter dc Voltage Gain In the previous analysis, the voltage increase across capacitor is ignored in Mode 1 and Mode 4, and the converter dc voltage gain is assumed to be the same as it is for the conventional half-bridge dc–dc converter, which is given by (18) However, the voltage increase has effect on the converter dc voltage gain. In Mode 4, assuming all the energy stored in the leakage inductance at the end of Mode 3 is transferred to the without additional loss and voltage change across capacitor the capacitor in Mode 4 is , the energy balance equation is expressed by Fig. 7. Simulation waveforms comparison (top traces: voltages V ; bottom traces: transformer primary currents): (a) without snubber, (b) with conventional dissipative RC series snubber (R = 30 , C = 2 nF), and (c) with active-clamp snubber (C = 3 F). Ignoring the duty cycle loss due to the leakage inductance, the transformer primary voltage in the power delivery modes can be described as (19) where is the voltage value at the end of Mode 3 which is given by (7). Substituting (7) into (19) yields , (20) (22) where V is the voltage change in power delivery modes that is expressed in (5). In power delivery modes, transformer primary voltage is reflected to the secondary side to charge the inductors. Applying the volt-seconds balance across the inductors, we have The capacitor voltage value at the end of Mode 4 and 5 is (23) (21) Authorized licensed use limited to: ULAKBIM UASL - YILDIZ TEKNIK UNIVERSITESI. Downloaded on August 03,2010 at 12:53:39 UTC from IEEE Xplore. Restrictions apply. 1300 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 20, NO. 6, NOVEMBER 2005 Fig. 8. ZVZCS waveforms of auxiliary switches. Fig. 10. Experimental waveforms of transformer primary voltage and current (D = 0.37; top trace Vab: 20 V/div; bottom trace i : 5 A/div): (a) with the conventional RC series snubber and (b) with the proposed active-clamp snubber (C = 3 F). From (24), it can be observed that the proposed converter has higher dc gain than the conventional half-bridge dc–dc converter. The increase of dc gain is proportional to the load current. For typical applications, numerical analysis shows that the dc addition is small and ignorable compared with output voltage. IV. SIMULATION AND EXPERIMENTAL VERIFICATION Fig. 9. Waveforms under the condition of T < T : (a) primary voltage V and transformer current and (b) ZVS waveforms of the switch S and S , and (c) switching waveforms of switch S and S . Substituting (5) into (22) and then substituting (22) into (23), and solving for , yield (24) The proposed topology with the active-clamp snubber of Fig. 3(a) was first simulated with Pspice using Spice models of Si7456DP and Si7892DP for primary-side and secondary-side MOSFETs, respectively. Experimental prototype is built and 36 75 V, tested with the following specifications: V V 3.3 V, 25 A, switching frequency of 200 kHz, isolation transformer turns ratio of 4:2 with leakage inductance of 220 nH as reflected to the primary-side, value of 3 F, and output inductances values of 2.3 H. In both the simulation and the experimental work, the conventional series snubber and the proposed active-clamp snubber werecomparedwiththesamespecificationsandconditionsforthe half-bridge dc–dc converter. Figs. 7 and 8 show simulation wave48 V, V 3.3 V and forms at the operating point of 25 A. Fig. 7 shows primary voltage V and transformer Authorized licensed use limited to: ULAKBIM UASL - YILDIZ TEKNIK UNIVERSITESI. Downloaded on August 03,2010 at 12:53:39 UTC from IEEE Xplore. Restrictions apply. MAO et al.: ACTIVE-CLAMP SNUBBERS 1301 Fig. 12. Experimental waveforms of transformer primary voltage and current (C = 6.6 F; top trace Vab: 40 V/div; bottom trace i : 5 A/div). Fig. 13. Efficiency comparison between the proposed active-clamp snubber and the conventional RC snubber. Fig. 11. Experimental waveforms of transformer primary voltage and current (D = 0.28; top trace Vab: 20 V/div; bottom trace i : 5 A/div): (a) with the conventional R/C series snubber and (b) with the proposed active-clamp snubber (C = 3 F). primary current waveforms for different snubber circuit cases. If thereisnoanysnubberontheprimaryside,theleakageinductance and MOSFET junction capacitanceoscillateduring the interval of freewheeling when both switches are off as analyzed in Section II. The oscillation involves body-diode reverse recovery and leads to EMI issues. The corresponding oscillation waveforms are shown snubber across transformer primary in Fig. 7(a). With series side winding,the oscillation isdamped as shownin Fig. 7(b), however, leakage inductance energy is dissipated which degrades efficiency. With the proposed active-clamp snubber, the ringing is eliminated and clean waveforms are observed in Fig. 7(c). As analyzed in Section II, both auxiliary switches and turn on and turn off under ZVZCS conditions. Fig. 8 shows the waveforms of both switches drive voltages, drain-to-source voltages, and drain currents. It is clearly observed that both switches turn on with zero voltage and zero current, and turn off with zero voltage and zero current. Thus, the switching loss of the auxiliary switches is nearly zero. Moreover, at low line input, the duty cycle is maximized and the freewheeling period is minimized such that the energy trapped in the transformer leakage inductance cannot be completely transferred to the capacitor. With the turn-off of auxiliary switches and , the remained leakage inductance energy will be released to charge/discharge MOSFETs junction capacitance, such that ZVS may be achieved for the switches and , as shown in the waveforms of Fig. 9. The primary voltage VAB and transformer current waveforms are shown in Fig. 9(a), it can be seen that no ringing occurs during the freewheeling time. The ZVS switching waveforms of the switch and are shown in Fig. 9(b). and switching waveforms are shown in Fig. 9(c), where and turn on with ZVZCS. In the experimental prototype, three MOSFETs (Si4420DY) are paralleled in each of the two channels of synchronous rectifiers in the current-doubler secondary side. IRFS59N10D MOSFETs are used for the main primary-side switches and , 30CTQ060S Schottky diodes are selected for and , and Si4470EY MOSFETs are used for and . The MOSFET drive IC HIP2100 is used to drive the switch and . LTC4440 high-side driver can be used for driving the and . However, as an alternative driving scheme switch in the prototype, a simple self-driven circuitry based on the transformer windings is used to drive switches and without adding additional IC driver. Experimental waveforms at two different duty cycles are shown in Figs. 10 and 11 compared with conventional snubber. It can be observed that the ringing is attenuated with the help of the proposed active-clamp snubber circuit and the body diodes of the main switches was not involved in the operation. Compared with the conventional snubber, the body-diodes reverse recovery and snubber losses are eliminated. As discussed in Section III, depending on the capacitance value of , the freewheeling time is adjustable. For 6.6 F, the experimental waveforms of transformer Authorized licensed use limited to: ULAKBIM UASL - YILDIZ TEKNIK UNIVERSITESI. Downloaded on August 03,2010 at 12:53:39 UTC from IEEE Xplore. Restrictions apply. 1302 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 20, NO. 6, NOVEMBER 2005 voltage and current are shown in Fig. 12. Efficiency comparison curves are shown in Fig. 13 with three cases of snubber snubber, active-clamp snubber with 3 F, circuits: and active-clamp snubber with short circuit. It is shown that higher overall efficiencies are achieved with the proposed active-clamp converter. V. CONCLUSION An active-clamp snubber circuit is presented for isolated halfbridge dc–dc converters. Theoretical analysis, simulation, and experimental results show that the proposed snubber attenuates transformer-leakage-inductance-related ringing and eliminates MOSFETs’ body-diode reverse recovery, resulting in improved converter efficiencies compared to the conventional series snubber circuit. The half-bridge dc–dc converter with the proposed active-clamp snubber topology is a strong candidate for applications requiring a wide range of input voltage. ACKNOWLEDGMENT The authors would like to thank G. Potter and B. Higgins, Astec Power, for their thoughtful insight and helpful discussions. REFERENCES [1] R. Redl, N. O. Sokal, and L. Balogh, “A novel soft-switching full-bridge converter: analysis, design considerations, and experimental results at 1.5 kW, 100 kHz,” in Proc. IEEE PESC’90, 1990, pp. 162–172. [2] H. K. Ji and H. J. Kim, “Active-clamp forward converter with MOSFET synchronous rectification,” in Proc. IEEE PESC’94, 1994, pp. 895–901. [3] J. Feng, Y. Hu, W. Chen, and C.-C. Wen, “ZVS analysis of asymmetrical half-bridge converter,” in Proc. IEEE PESC’01, 2001, pp. 243–247. [4] O. Garcia, J. A. Cobos, J. Uceda, and J. Sebastian, “Zero voltage switching in the PWM half-bridge topology with complementary control and synchronous rectification,” in Proc. PESC’95, 1995, pp. 286–291. [5] W. Chen, P. Xu, and F. C. Lee, “The optimization of asymmetric halfbridge converter,” in Proc. Applied Power Electronics Conf., 2001, pp. 703–707. [6] K. Yoshida, T. Maeoka, T. Ishii, and T. Ninomiya, “A novel zero-voltage-switched half-bridged converter with active current-clamped transformer,” in Proc. IEEE PESC’96, 1996, pp. 632–637. [7] , “ZVS-PWM half-bridge using active current clamping with an auxiliary of a transformer,” in Proc. IEEE PESC’98, 1998, pp. 942–947. [8] H. Mao, J. Abu-Qahouq, S. Luo, and I. Batarseh, “Zero-voltageswitching half-bridge dc–dc converter with modified PWM control method,” IEEE Trans. Power Electron., vol. 19, no. 4, pp. 947–958, Jul. 2004. [9] H. Mao, S. Deng, and I. Batarseh, “An active-clamp snubber for isolated half-bridge dc–dc converters,” in Proc. 29th Annu. Conf. IEEE Industrial Electronics Soc. IECON’03, 2003, pp. 42–48. [10] H. Mao, J. Abu-Qahouq, S. Luo, and I. Batarseh, “New zero-voltageswitching half-bridge dc–dc converter and PWM control method,” in Proc. 18th Annu. IEEE Applied Power Electronics Conf. Expo (APEC’03), vol. 2, Feb. 2003, pp. 635–640. Hong Mao received the B.S. degree from the Sichuan University of Science and Technology, Chengdu, China, in 1992, M.S. degree from Chongqing University, Chongqing, China, in 1997, and Ph.D. degree from Zhejiang University, Hangzhou, China, in 2000, all in electrical engineering. He is currently a Senior Design Engineer with Astec Power, Andover, MA. From 1992 to 1994, he was an Assistant Professor with the Department of Electrical Engineering, Sichuan University of Science and Technology. From 1999 to 2000, he was a Project Leader with Zhongxing (ZTE) Telecom Corporation, China. From 2000 to 2001, he was a Senior Engineer and Division Manager with PI Electronics, China, where he led a team to develop adaptors for SONY laptop computers. From 2001 to 2002, he was with the Center for Power Electronics Systems, Virginia Polytechnic Institute and State University, Blacksburg, focusing on high-efficiency front-end dc–dc converters. In 2002, he joined the University of Central Florida, Orlando, working on low-profile low-voltage dc–dc converters. He was an Assistant Director with the Florida Power Electronics Center, University of Central Florida. His current research interests include soft-switching dc–dc power conversion, power factor correction, and modeling of power electronics systems. Songquan Deng received the B.S. degree in mechanical engineering from Xihua University, Chengdu, China, in 1998, the M.S. degree in electrical engineering from Chongqing University, Chongqing, China, in 2001, and is currently pursuing the Ph.D. degree in electrical engineering at the Florida Power Electronics Center, University of Central Florida, Orlando. He is a Design Engineer with Synqor, Inc., Boxboro, MA. His research interests include low-voltage high-current dc–dc converters, soft switching techniques, and power converter topology, and control schemes. Jaber Abu-Qahouq (M’98) received the B.Sc. degree (with first class honors) from Princess Sumaya University/Royal Scientific Society, Amman, Jordan, in 1998, and the M.S. and Ph.D. degrees from the University of Central Florida (UCF), Orlando, in 2000 and 2003, respectively, all in electrical engineering/electronics. He is currently a Senior Power Electronics/Power Management Engineer with Intel Corporation, Hillsboro, OR. From January 2004 to August 2005, he was a Faculty Member of the School of Electrical Engineering and Computer Science, UCF, and from January 2002 to December 2003, and was a member of the Adjunct Faculty. He was a Research Assistant/Associate with the Florida Power Electronics Center, UCF, from 1999 to 2003. From 1998 to 1999, he was with the Royal Scientific Society (RSS), Electronic Services and Training Center (ESTC), Amman. He led and worked on several projects funded by the Florida Space Consortium, NASA, NSF, ASTEC Power, INTEL, and the University of Central Florida. His research interests include soft-switching power conversion, low-profile high-density low-voltage high-current fast-transient dc–dc converters, power factor correction converters, digital control in power electronics, and dc–ac inverters. Dr. Abu-Qahouq has received several awards and is a member of Eta Kappa Nu and Phi Kappa Phi. Issa Batarseh (SM’91) received the B.S. degree in computer engineering and the M.S. and Ph.D. degrees in electrical engineering from the University of Illinois, Chicago, in 1983, 1985, and 1990, respectively. He is a Professor and Chair with the Department of Electrical and Computer Engineering, University of Central Florida (UCF), Orlando. He was a Visiting Assistant Professor of Electrical Engineering at Purdue University, Calumet City, IN, from 1989 to 1990 before joining the Department of Electrical and Computer Engineering, UCF, in 1991. He has more than 11 U.S. patents, and more than 50 refereed journal and 200 conference publications. His research work has been sponsored by Federal agencies and private sector. He published Power Electronic Circuits (New York: Wiley, 2003). His major research interests are power electronics, focusing on high frequency dc–dc conversion, soft-switching and dynamic modeling of dc-to-dc converters, harmonic analysis, and power factor correction. Dr. Batarseh received many national and international teaching, research, and service awards. He served as Session Chair and Committee Member for APEC and PESC conferences. He will be the general chair for PESC’07 conference in Orlando. He has served as a Chairman of the IEEE Orlando Power Engineering Chapter, Chairman of the IEEE Orlando Section, and Faculty Advisor for the IEEE Student Branch, and Eta Kappa Nu. He is a Registered Professional Engineer in Florida. Authorized licensed use limited to: ULAKBIM UASL - YILDIZ TEKNIK UNIVERSITESI. Downloaded on August 03,2010 at 12:53:39 UTC from IEEE Xplore. Restrictions apply.