FIRE ALARM CONTROL PANEL
(CONVENTIONAL)
FMS-P4-4-ABS
FMS-P4-8-ABS
Type
Conventional type
Spare Battery
24 VDC
Model
FMS-P4-4-ABS,
FMS-P4-8-ABS
( 380 x 270 x 80 mm)
End of Line Resistance
5.1 kΩ
Zone
4,8
Max.Amount of Smoke
detector
20 pcs/Zone
Input Voltage
220 VAC/50Hz
Alarm Verifying Time
7 seconds
Operation Voltage
24 VDC
Exterior Resistance
Round-trip under 56Ω
Mains Supply
220V AC 50/60 Hz
Spare Power (battery)
Charging Voltage protection
24V DC
Glass Fuse
Sounder Output
24v DC(End of Line Resistance 10kΩ)
Max.Output Current: 15mA amout
Amout of Smoke Detectors
Auxiliary Contacts
Main Supply Protection
Sounder Protection
Spare Power(Battery) Protection
Zone End of Line Resistance
Max.Amout of Connection: 20pcs/Zone
Null-Voltage Contact(24V DC,1A max.NO/NC
Glass Fuse
Glass Fuse
Glass Fuse
5.1 kΩ
FORMOSA FIRE ALARM CO.,LTD
.
Circuit Connection Diagram
Sounder Circuit
1.
2.
3.
4.
Two external sounder output circuit are provided
Amount of two sounder outputs is 150 mA
Each sounder circuit is protected by fuse 1A
Each sounder circuit should be with End of Line Resistance 10KΩ
to check if open circuit or short circuit
5. Press EVACUTE button can re-sound the external alarm (bell,buzzer)
6. Press the SILENCE button to mute the external sounder alarm
(bell,buzzer)
Fault Mode
1. Detector Fault (Detector Base loosened or without end of line
resistance 5.1 KΩ)
2. Zone Wiring Fault (Open circuit or short circuit)
3. AC Power Fault
4. Spare Power (battery) Fault (confirm the fuse)
5. Alarm Bell Output Wiring Fault (open circuit or short circuit or
without end
of line resistance 10KΩ)
Zone And Display
Each Zone is represented by three LED, one Red and two Orange
color
 FIRE (Red LED): Fire Alarm Signal
 O/C Fault (Orange LED): Open circuit
 S/C Fault (Orange LED): Short circuit
FORMOSA FIRE ALARM CO.,LTD
.