ABB Motors and Generators Technical Data Sheet - DOL Project Location Department/Author Customer name Customer ref. Our ref. Rev/ChangedDate by of issueSaving ident A 1/15/2021 untitled.xlsm No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Definition Product Product code Type/Frame Mounting Rated output PN Service factor Type of duty Rated voltage UN Rated frequency f N Rated speed nN Rated current IN No-load current Starting current Is/IN Nominal torque TN Locked rotor torque TS/TN Maximum torque Tmax/TN Minimum torque Tmin/TN Speed at minimum torque Load characteristics (IEC 60034-2-1:2014) PLL determined from residual loss Data Unit Remarks TEFC, 3-phase, squirrel cage induction motor 3GBP 252 220-ADG Calc. ref. 3GZF021025-146 M3BP 250SMB 4 IM1001, B3(foot) 75 kW 1 S1(IEC) 100% 380 VD ± 5 % (IEC 60034-1) 50 Hz ± 2 % (IEC 60034-1) 1474 r/min 140 A 44 A 6.6 Meet IEC 60034-12, N,(H at 60 Hz) 486 Nm 2.5 2.8 2.3 1050 r/min Load % Current A Efficiency % Power factor 100 140 94.0 / IE2 0.86 75 107 94.9 0.84 50 77.5 95 0.77 Start 924 0.43 15 s 27 s F/F 40 °C 1000 m.a.s.l. IP55 IC411 self ventilated 6315/C3 - 6213/C3 19 20 21 22 23 Maximum starting time from hot 24 Maximum starting time from cold 25 Insulation class / Temperature class 26 Ambient temperature 27 Altitude 28 Enclosure 29 Cooling system 30 Bearing DE/NDE 31 Type of Grease 32 Sound pressure level (LP dB(A) 1m) 67 dB(A) 33 Moment of inertia J = ¼ GD2 0.866 kg-m2 34 Balancing 35 Vibration class 36 Position of terminal box Top 37 Terminal box entries; no, dimens. 38 Number of power terminals 39 Direction of rotation CW or CCW 40 Weight of rotor 114 kg 41 Total weight of motor 450 kg 42 Dimension drawing no. 43 44 45 Ex-motors 46 47 48 Option Variant Codes / Definition 49 +002 Restamping voltage, frequency and output, continuous duty 50 51 52 Remarks: Data based on situation 4/22/2020 All data subject to tolerances in accordance with IEC Guaranteed values on request Item name 1.00001 Pages 1(3) at load ABB Motors and Generators Load Curves Project Location Department/Author Customer name Customer ref. Our ref. Rev/Changed by Date of issue A 1/15/2021 Saving ident untitled.xlsm Product TEFC, 3-phase, squirrel cage induction motor Type/Frame Product code Rated output PN Type of duty M3BP 250SMB 4 3GBP 252 220-ADG 75 kW S1(IEC) 100% Voltage (V) Frequency (Hz) 380 50 Current IN (A) Speed (r/min) Item name 1.00001 Pages 2(3) Calc. ref. 3GZF021025-146 140 1474 Power factor at PN 0.86 Efficiency (%) at PN 94 1.4 1.3 PF / Efficiency,Current%(*100) 1.2 1.1 1 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 0 0.1 0.2 0.3 0.4 0.5 Current 0.6 0.7 P2/Pn 0.8 0.9 1 Efficiency Load characteristics (IEC 60034-2-1:2014) Data based on situation 4/22/2020 All data subject to tolerances in accordance with IEC 1.1 1.2 Cosinus 1.3 1.4 ABB Motors and Generators Starting Curves Department/Author Our ref. Type of product Type/Frame Product code Rated output PN Type of duty Project Location Customer name Customer ref. Rev/Changed byDate of issue Saving ident A 1/15/2021 untitled.xlsm TEFC, 3-phase, squirrel cage induction motor M3BP 250SMB 4 Calc. ref. 3GBP 252 220-ADG Frequency (Hz) Rated current IN 75 kW S1(IEC) 100% Voltage (V) 100% Tstart/TN Starting time (s) Speed (r/min) Is/In Tmax/Tn 380 2.5 0 6.6 2.8 3GZF021025-146 50 140 A Voltage (V) Tstart/TN Starting time (s) Speed (r/min) Is/In Tmax/Tn 380V(100%) 2.5 0 6.6 2.8 4 8 3.5 7 3 6 2.5 5 2 4 1.5 3 1 2 0.5 1 Is/In Ts/Tn Jmotor (kgm2) 0.87 Jload (kgm2) 1474 Speed (r/min) TN (Nm) 486 Tload (Nm) Nbr. of Consecutive Starts at UN Item name 1.00001 Pages 3(3) 0 0 250 500 TMotorUn 380V IMotorUn 380V 750 1000 Speed (r/min) 1250 1500 TMotorU2 380V(100%) IMotorU2 380V(100%) Load characteristics (IEC 60034-2-1:2014) Data based on situation 4/22/2020 All data subject to tolerances in accordance with IEC 0 1750