Rules of thumb 1. Space & Volume Criteria 1a. Space allowances for office & commercial building Item i. ii. Usage General - Net average space - Gross average space - Large scale business, including conference, canteen, storage and work space Specific - Executive office - Open plan office - Full time professional - Secretarial staff - Clerical staff - Restaurant - Department Stores Area (m2 per person) 10 12-14 17-18 13-20 9 6-7 6-7 4-5 1.5 1-1.5 1b. Space allowance for building services plant room The space allowance for building service plant room is estimated below:i. Space allowance in terms of percentage of the occupied floor area:Usage - Simple factory - Typical building - High technology building - Central computer facilities (Occupied area < 9300 m2) Percentage of occupied floor area 4% 6-10% 15% 3-4% Page 1 of 12 ii. Space allowance of HVAC plant room:Usage - Air handling plant room • up to 10 m3/s • 10 – 40 m3/s • Greater than 40 m3/s - Heating plant room • for 100kW boiler • for 200kW boiler • for 1000kW boiler • for 4000kW boiler - Central refrigeration plant (excluding cooling tower) - Cooling towers - Air-cooled condenser Area in m2 10 m2 8 m2 per m3/s 4 m2 per m3/s 15 m2 x 3m (H) 25-30 m2 x 3m (H) 80 m2 x 4m (H) 130-150 m2 x 4.5m (H) 1–2% of building floor area 25 + (cooling tower in kW) /66 25 + (condenser in kW) / 200 1c. Space allowance for service duct In general, the total service duct area is about 2% of gross floor area. One service duct serves about 15-23 m radius. For air ducting system, the service duct is 0.2 m2 per m3/s of air. 1d. Space allowance for raised floor The raised floor design facilitates the specialist cabling system to be installed under the raised floor for intelligent building. The optimum raised floor is proposed below:Usage - Traditional office - Cellular / private office - Open plan office - Trading rooms or dealer desk in finance company - EDP rooms - Electronic equipment Optimum raised floor depth in mm 150 150 200 300 600 600 In general, the raised floor to ceiling space in working area should be 2400 mm when the raised floor is installed. Page 2 of 12 1e. Space allowance for restaurant The minimum area for food room is tabulated below as referred to “A guide to application for restaurant licences”, Food and Environment Hygiene Department, HKSARG. i. General Restaurant Gross floor area of the premises in m2 Minimum kitchen area in m2 100 or less 6 101 – 150 10 151 – 250 10 251 or above 14 Minimum aggregate area of kitchen, food preparation room and scullery accommodation in m2 30% of gross floor area, but not less than 9m2 25% of gross floor area, but not less than 27m2 23% of gross floor area, but not less than 36m2 21% of gross floor area, but not less than 54m2 ii. Light Refreshment Restaurants Gross floor area of the premises in m2 22 or less 23 – 35 36 – 55 56 – 95 96 – 185 186 or above Minimum aggregate area of kitchen, food preparation room and scullery accommodation in m2 Not less than 5m2 20% of gross floor area or 7m2, whichever is the less 18% of gross floor area or 8m2, whichever is the less 14% of gross floor area or 12m2, whichever is the less 13% of gross floor area or 17m2, whichever is the less 9% of gross floor area or 28m2, whichever is the more The above space allowance excludes the space for food refrigeration plant and food storage area. Page 3 of 12 2. Thermal Transmittance It is difficult to produce common U-values for wall and for roof as the U-value is dependent on the combination of materials of a building. In general, the following U-values can be used as reference for heat gain calculation applicable in Hong Kong:• U-value for composite wall panel = 2.32 W/ m2°C (non-structural wall) (For 5mm white mosaic tiles + 10mm cement/sand render + 100mm concrete panel + 10mm gypsum plaster) • U-value for composite structural wall panel =1.91 W/ m2°C (For 5mm white mosaic tiles + 10mm cement/sand render + 300mm concrete panel + 10mm gypsum plaster) • U-value for composite curtain wall panel = 0.41 W/ m2°C (For 8mm black glass + 75mm mineral wool felt insulation + 50mm air space resistance + 2mm pressed steel panel) • U-value for roof panel = 0.37 W/ m2°C (For 25mm concrete tiles + 20mm asphalt + 50mm cement/sand screed + 50mm polystyrene insulation + 600 mm re-enforcement concrete + 10mm gypsum plaster) Regarding the glass panel, the following shading coefficient can be used as reference for heat gain calculation:• • The shading coefficient of tinted glass = 0.7 The shading coefficient of single clear glass = 0.95 2a. Overall Thermal Transfer Value (OTTV) requirements of Hong Kong The external walls and roofs of a building should be designed and constructed to the following requirements:• • For a building tower, the OTTV should not exceed 30W/m2 (revised in 2000, previously 35W/m2) For a podium, the OTTV should not exceed 70W/m2 (revised in 2000, previously 80W/m2) The following can be exempted from the OTTV requirement:• • • • an external wall of a refuge floor an external wall or roof of a carparking floor an external wall of a lightwell having an area on plan not exceeding 21 m2 any wall on any roof Page 4 of 12 3. Environmental Aspects 3a. Indoor condition Based on the Code of Practice for Energy Efficiency of Air Conditioning Installations, Summer Office and Classroom Minimum dry bulb temperature Minimum relative humidity 23°C 50% Other Applications except Office and Classroom Minimum dry bulb temperature 22°C Minimum relative humidity 50% Winter Hotel Maximum dry bulb temperature Maximum relative humidity 24°C 50% Other Applications except Hotel Maximum dry bulb temperature Maximum relative humidity 22°C 50% 3b. Outdoor condition Based on the Code of Practice for Energy Efficiency of Air Conditioning Installations, Summer Maximum dry bulb temperature Maximum relative humidity 33.5°C 68% Winter Minimum dry bulb temperature Minimum relative humidity 7°C 40% Page 5 of 12 3c. Occupancy gain Activity level at 22°C Seated at rest Office work Standing Eating in restaurant Factory Dancing Sensible gain 80W 90W 95W 100W 115W 125W Latent gain 35W 50W 55W 60W 120W 140W Total gain 115W 140W 150W 160W 235W 265W 3d. Lighting gain For fluorescent lighting fitting = Total watts x 1.25 For Incandescent lighting fitting = Total watts In general, lighting load is assumed to 33W/m2 for producing a lighting standard of around 540 Lumen/ m2. The minimum assumption of lighting load is 20W/ m2 for low lighting standard. 3e. Equipment gain The office machinery = 20 – 50 W/ m2 4. Ventilation requirements 4a. Outside air supply Building Application Office Hotel Restaurant Smoking lounge Toilet Classroom Theatre Shopping mall Corridor & utilities Outside air supply rate (l/s per person) 8 – 10 8 – 10 10 30 25 8 – 10 8 – 10 1 l/s per m2 0.25 l/s per m2 4b. Air infiltration Building Application Office Hotel room Restaurant Shopping mall Classroom library Air infiltration rates 1 air change per hour 1 air change per hour 1 air change per hour 0.5 - 1 air change per hour 2 air changes per hour 0.5 – 0.75 air change per hour Page 6 of 12 4c. Air ventilation The air change rate of different building applications are as follows:Building Application for air-conditioned space General Office Conference Room Factory Restaurant General sport hall Squash courts Theatre Shopping mall Classroom library Building Application for mechanical ventilation Office toilet Pantry or print room Pump room Refuse collection chamber Kitchen (Chinese) Generator Room E&M Plant Room Air change rates 4 – 6 air changes per hour 6 – 10 air changes per hour 6 air changes per hour 10 – 15 air changes per hour 1 air change per hour 4 air changes per hour 6 - 10 air changes per hour 4 - 6 air changes per hour 2 air changes per hour 3 – 4 air changes per hour Air change rates 15 air changes per hour 15 air changes per hour 10 – 15 air changes per hour 15 air changes per hour (Exhaust) 10 air changes per hour (Supply) 60 air changes per hour (Exhaust) 50 air changes per hour (Supply) 10 air changes per hour 10 air changes per hour 5. Comfort Air Movement Maximum recommended mean air velocities in the occupied space:In winter In summer at 21°C at 22°C at 23°C at 24°C on back of neck 0.15 m/s 0.25 m/s 0.15 m/s 0.2 m/s 0.25 m/s 0.3 m/s 0.2 m/s If the mean air velocity exceeds 0.8 m/s, papers will be lifted on the table. Page 7 of 12 6. Building Global Loads Building Application Office Recommended cooling load (m2/kW or ft2/TR) 4.9 – 5.7 m2/kW or 190 – 220 ft2/TR Shop 3.9 m2/kW or 150 ft2/TR Shopping arcade (Common areas) Lift lobby 6.5 m2/kW or 250 ft2/TR Hotel (Function areas) Hotel (Guest room) Classroom Residential Auditorium/theatre Restaurant (Chinese) Restaurant (Western) 3.9 m2/kW or 150 ft2/TR 6.5 m2/kW or 250 ft2/TR 7.8 m2/kW or 300 ft2/TR 3.9 m2/kW or 150 ft2/TR 5.7 m2/kW or 220 ft2/TR 3.9 m2/kW or 150 ft2/TR 2 – 2.6 m2/kW or 80 – 100 ft2/TR 2.6 – 3.1 m2/kW or 100 – 120 ft2/TR Page 8 of 12 7. Ductwork System In general, the pressure drop of straight duct is around 1 Pa/m and 8 Pa/m for low velocity system and for high velocity system respectively. • Low pressure system is the fan pressure up to 1000Pa. • Medium pressure system is the fan pressure between 1000Pa and 1700Pa • High pressure system is the fan pressure between 1700Pa and 3000Pa • Low velocity system is the air velocity up to 12.7 m/s • High velocity system is the air velocity above 12.7 m/s • In general, the low pressure and low velocity system operates at 10 m/s or less. • The high pressure and high velocity system operates at 10 – 20 m/s. Duct velocities Building application Quiet public buildings, hotel Busy public buildings Factories For quiet situations Cinema, assembly halls Office, shops, exhibition areas Main Duct (m/s) 5–8 8 – 11 12 – 20 5 7–6 9 Branch Duct (m/s) 4–6 4–6 10 – 20 3 5 6 • The pressure loss of louvre is around 50Pa. • The pressure loss of air filter at rated capacity, reasonably clean is around 70Pa. • The pressure loss of air heater, two rows of grilled tubes, is around 50Pa. • The pressure loss of multi-blade damper operating its face velocity of 5m/s and 10m/s is maximum of 250Pa and maximum of 1000Pa respectively. • The pressure loss of silencer is around 100Pa. • The pressure loss of cooling coil is 120Pa maximum. • The outlet velocity of supply air louvre is 2.5 m/s through free area • The inlet velocity of return air louvre is 2 m/s through free area. Page 9 of 12 8. Piping System In general, the minimum velocity of the flow of water is 0.75 m/s. • For 15 – 50mm pipe diameter, the water velocity is 0.75 – 1.5 m/s • For over 50mm pipe diameter, the water velocity is 1.25 – 3 m/s The frictional loss of straight pipe is maximum of 990Pa/m (10 ft of water per 100 ft of straight pipe) in large air conditioning system, in general, 500Pa/m is used in the frictional loss of straight pipe. For central heating system is maximum of 360Pa/m, in general, 280Pa/m is used for the frictional loss of straight pipe in consideration of expansion of water volume. The frictional loss of cooling coil for air-conditioning plants is 20-30kPa. Recommended water velocities Service Velocity Range (m/s) Pump discharge 2.5 – 3.6 Pump suction 1.3 – 2.1 Drain line 1.3 – 2.1 Header 1.3 – 4.5 Riser 1–3 General service 1.5 – 3 City water 1 - 2.1 In general, the allowable flow rates of black steel pipe BS1387 operating at a nominal 75°C in the heating system are as follows:Diameter (mm) 15 20 25 32 40 50 65 80 100 125 150 Water (kg/s) 0.1 0.2 0.4 0.8 1.25 2.5 4 7 15 25 40 Page 10 of 12 9. Piping System (Cont’d) The expansion of water in the heating system is tabulated below:Temperature °C 38 52 66 79 93 107 121 135 149 163 177 191 205 Volume increase (%) 0.6 1.2 1.8 2.8 3.5 4.5 5.6 6.8 8.3 9.8 11.5 13.0 15.0 The expansion of water is in % of increase of total volume of water in the system. Page 11 of 12 10. Noise & Vibration Control The comfort noise levels are shown below:Recommended maximum background noise levels:Building Application Very quite rooms, e.g. concert halls, sound studios Quiet rooms, e.g. bedrooms, theatre, churches Private rooms, e.g. small offices, libraries, living rooms Public rooms, e.g. general offices, classrooms, small shops General areas, e.g. reception areas, restaurants Work areas, e.g. kitchens, computer rooms, large shops Industrial areas, e.g. factories Noise Rating (NR) NR 20 NR 25 NR 30 NR 35 NR 40 NR 45 NR 50 or above Influence of external noise levels:Criterion for new noise If more than 10 dBA above background noise If less than 5 dBA above background noise Comments Compliant expected Marginal 11. Electrical Load for air-conditioning equipment In general, the electrical load for air-conditioning installation in an office building is around 130 – 150W/m2. Such electrical load includes the power consumption of chiller, chilled water pump, air handling unit and control system. References : - N. Pavey, BSRIA, Technical Note TN 17/95 Rules of Thumb, 2nd Edition - EMSD, Code of Practice for Energy Efficiency of Air Conditioning Installations, 2002 - ASHRAE, Fundamentals Handbook - Carrier Air Conditioning Company, Handbook of Air-conditioning System Design Page 12 of 12