INSULATION RESISTANCE TEST RESULTS OF POWER TRANSFORMER HAVING AGE 25 YEARS & ABOVE) UNDER SS&TL DIVISION ISLAMABAD Sr. No. Name of Grid Station P/T.F No. MVA Manuf. Date Make Description of Connections 2 3 4 5 6 7 8 132KV Murree 132KV E-8 132KV Trarrkhel 132KV Kahuta City 132KV Khoi Ratta 132KV Khoi Ratta 132KV Bagh 132KV Bagh T-1 T-1 T-1 T-2 T-2 T-3 T-1 T-2 20/26 20/26 10/13 20/26 10/13 10/13 10/13 10/13 1993 1969 1989 1984 1984 1982 1972 1974 China TrafoUnion Siemens TrafoUnion ElpromEnergo Maiden -Sha ELTA RedConcur 2017-18 2018-19 2019-20 2020-21 HV/E 15 Sec 1500 60 Sec 2500 15 Sec 3200 60 Sec 4600 15 Sec 6200 60 Sec 8000 15 Sec 5470 60 Sec 8500 15 Sec - 60 Sec - LV/E 1000 1800 2200 3800 4700 7900 3870 7070 - - HV/LV 2000 4000 2800 5000 5900 8100 4800 8450 - - HV/E 300 450 2200 3300 2500 3500 3000 4500 2200 3200 LV/E 150 250 1300 2000 1400 2400 1400 2500 1400 2000 HV/LV 250 400 2200 3500 2400 3900 2800 4500 2000 3000 HV/E - - 500 600 375 470 650 857 - - LV/E - - 300 400 220 262 351 484 - - HV/LV - - 400 600 365 460 617 879 - - HV/E 1000 1400 - - 450 730 850 1270 - - LV/E 500 950 - - 390 580 450 950 - - HV/LV 960 1500 - - 520 800 800 1420 - - HV/E 900 980 130 160 100 120 210 250 138.2 156.6 LV/E 400 700 55 70 60 80 108 135 79.6 84.1 HV/LV 950 1050 120 150 110 130 194 246 133.1 159.2 HV/E 200 250 490 7000 460 650 590 910 885 1324 LV/E 100 150 410 630 380 590 400 780 550 1013 HV/LV 200 300 600 1000 580 920 580 1130 777 1489 Applied 5 KV 1 2016-17 HV/E LV/E HV/LV HV/E LV/E HV/LV INSULATION RESISTANCE TEST RESULTS OF POWER TRANSFORMER HAVING AGE 25 YEARS & ABOVE) UNDER SS&TL DIVISION ISLAMABAD Sr. No. Name of Grid Station P/T.F No. MVA Manuf. Date Make Description of Connections 9 T-1 10/13 1996 132KV Chaint 10 11 T-2 132KV Minhasa 12 T-2 T-1 10/13 10/13 4 1988 1983 1984 ElectroPuter Siemens Siemens 33KV Fatehpur 13 T-2 4 1984 Siemens 2017-18 2018-19 2019-20 2020-21 15 Sec 60 Sec 15 Sec 60 Sec 15 Sec 60 Sec 15 Sec 60 Sec 15 Sec 60 Sec HV/E - - 140 200 480 500 90 115 57 65 LV/E - - 80 100 300 320 58 70 39 45 HV/LV - - 130 180 400 450 80 110 53 58 HV/E 450 600 - - - - - - 420 600 LV/E 350 500 - - - - - - 375 520 HV/LV 400 550 - - - - - - 410 560 HV/E 300 450 - - - - - - 300 440 LV/E 250 350 - - - - - - 260 335 HV/LV 300 450 - - - - - - 295 438 Applied 5 KV ElectroPuter 2016-17 HV/E LV/E HV/LV HV/E LV/E HV/LV