Model 34788 Recovery/Recycling/Recharging Unit Shown: Model 34788 Rev C Associated Models Include: Matco (H234788), MAC (AC34788), and Cornwell (RA-C34788) Branded Units. 34788 Service Manual Disclaimer The information contained in this manual was considered accurate at the time of printing. Any corrections should be directed to: SPX Corporation 6475 Technology Drive Kalamazoo, MI 49009 Phone 269-544-5814 Fax 269-544-5832 This manual was made possible by the combined efforts of a number of individuals in the following departments: Technical Support, Engineering, Tech Pubs, and Marketing. I wish to express my gratitude to everyone that contributed to this manual. — Scott Parde © 2007, SPX Corporation. All rights reserved. No part of this publication may be reproduced, transmitted, transcribed, stored in a retrieval system, or translated into any language in any form by any means without the written permission of SPX Corporation. Printed in the USA. S.P. 09/2007 (Rev C) 2 34788 Service Manual TABLE OF CONTENTS Safety Warnings ................................................................................................... 4 General Information.............................................................................................. 5 Introduction ....................................................................................................................... 6 34788 Views ....................................................................................................................... 7 Operating Guidelines ....................................................................................................... 8 Unit Specifications ............................................................................................................ 11 Maintenance Schedule .................................................................................................... 12 Parts & Components............................................................................................ 15 34788 External Parts ......................................................................................................... 34788 Internal Parts .......................................................................................................... Component Assemblies .................................................................................................... Plumbing Diagram & Parts List ....................................................................................... 34788 Main Component Descriptions .............................................................................. Alphabetical Parts List ..................................................................................................... 16 18 20 27 28 30 Diagnostics .......................................................................................................... 37 Functional Check .............................................................................................................. 38 Service Center Menu Options .......................................................................................... 40 Output Step Test ................................................................................................................ 41 Depressurizing the Unit .................................................................................................... 42 12VDC Solenoid Test Procedure ...................................................................................... 43 Troubleshooting ................................................................................................................ 44 Service Instructions and Calibration ............................................................................... 54 System Wiring ................................................................................................................... 71 34788 Component Wiring ................................................................................................. 72 34788 Wiring Harnesses .................................................................................................... 75 Component Identification ............................................................................................... 86 Component Application Chart ......................................................................................... 87 Flow Diagrams .................................................................................................................. 88 Service Bulletins .................................................................................................. 97 Labor Rates .......................................................................................................... 103 Product Warranty ................................................................................................. 105 3 34788 Service Manual SAFETY WARNINGS It is extremely important to follow the instructions in this manual. DO NOT attach any hoses or accessories until prompted by the unit. Improper setup and failure of the unit will result. Use only ROBINAIR Designated Replacement Components when servicing your equipment. Refer to the operator’s manual or this service manual for correct replacement part number(s). Always wear eye protection and protective clothing when working with refrigerants. Refrigerant can cause injury. Read and follow all warnings in the operator’s manual and this service manual before operating the unit. When replacing components, make certain the new parts are connected exactly as your instruction sheet directs you to do. If an instruction sheet was not included, connect the replacement part just like the original. Mark or label wire and plumbing disconnections so replacing the new parts will confirm the previous configuration. Disconnect hoses and tubes with extreme caution as they may contain liquid refrigerant under pressure. Always disconnect the unit from the power source before making any repairs or replacements to the components. Risk of electrical shock! Avoid the use of extension cords because the extension cord may overheat. However, if you must use an extension cord, the cord must be No. 14 AWG minimum and should not exceed more than 25 feet in length. Always depressurize the machine before servicing or replacing any components. Pressurized tanks contain liquid refrigerant. Overfilling of the tank may cause violent explosion and possible injury or death. Do not recover refrigerants into a non-refillable storage container. Federal regulations require refrigerants to be transported only in containers meeting DOT spec. 4BW or DOT spec. 4BA. Be sure that the refrigerant level in the tank does not exceed 80% of the tank volume. Failure to monitor the level could result in excessive hydrostatic pressure, causing physical injury or death. If scale assembly and UL circuit are not calibrated, scale can overfill the tank, causing possible explosion and/or vehicle overcharge. 4 Warnings: Use this unit only with the specified refrigerants. Cross-contamination with other refrigerant types will cause severe damage to the A/C system and to service tools and equipment. Do not mix refrigerant types through a system or in the same container! Avoid breathing A/C refrigerant and lubricant vapor or mist. Exposure may irritate eyes, nose, and throat. When removing R-134a from the A/C system, use service equipment certified to meet the requirements of SAE J2210 (R-134a recycling equipment). If accidental system discharge occurs, ventilate work area before resuming service. Make sure there is adequate ventilation in the vehicle servicing area. Keep hands away from moving parts. HFC-134a service equipment or vehicle A/C systems should not be pressure tested or leak tested with compressed air. Some mixtures of air/HFC-134a have been shown to be combustible at elevated pressures. These mixtures are potentially dangerous and may result in fire or explosion causing injury or property damage. Additional health and safety information may be obtained from refrigerant and lubricant manufacturers. 34788 Service Manual 1 General Information G E N E R A L I N F O R M AT I O N Introduction .......................................................................................................... 6 Automatic Functions of the 34788 .................................................................................... 6 Additional Features of the 34788 ..................................................................................... 6 Optional Feature ............................................................................................................... 6 34788 Views .......................................................................................................... 7 Front View ......................................................................................................................... 7 Side View .......................................................................................................................... 7 Operating Guidelines ........................................................................................... 8 Using the Control Panel ................................................................................................... 8 Keypad Functions ............................................................................................................. 9 Menu Functions ................................................................................................................. 10 Unit Specifications ............................................................................................... 11 Maintenance Schedule ........................................................................................ 12 5 General Information 34788 Service Manual Introduction The Robinair 34788 recovers, recycles, evacuates, leak test, and recharges R-134a quickly and accurately. The 34788 recovers up to 20% more refrigerant and will recharge the vehicle to within ½ ounce of the charge capacity, complying with the new SAE J-2788 standard. New ergonomic cabinet design provides additional storage areas for tools, filters, and oil bottles, including a convenient fold-down control panel. Automatic Functions of the 34788 √ Automatic Operation – Allows the technician to program the unit to recover, recycle, evacuate, and recharge without user intervention. √ Vacuum Leak Test – Will monitor the vacuum level after an evacuation and inform the technician of a possible leak in the vehicle’s A/C system. √ Automatic Refrigerant Refill – With this latest advance, you never have to stop in the middle of a job to change refrigerant tanks. The unit maintains a user selectable amount of refrigerant in an internal vessel, and signals when it’s time to change the supply tank, so no monitoring is required. √ Automatic Air Purge – Eliminates damaging air without any monitoring of gauges or opening of valves. √ The Automatic Oil Drain – The unit automatically drains system oil captured during recover, and the display reminds you to empty the bottle. Graduations on the container clearly show you how much oil needs to be replaced. √ Refrigerant Charging – Select a charge mode from either the high side, low side, or both. Accuracy features eliminate guesswork. √ Refrigerant Management System – New and improved, system displays refrigerant use and monitors remaining filter life. Prompts appear when 1/3 of filter life remains. √ Vacuum Function – Defaults to 15 minutes, but is programmable up to 99 minutes. Remaining vacuum time is displayed on the screen. 6 Additional Features of the 34788 • Control panel offers flat storage feature when not in use. • New 2X larger display makes the 34788 easier than ever to use. • Two large tool storage areas. • Built-in storage for extra filter and compressor oils. • Change between traditional & hybrid vehicle systems without fear of cross contamination with improved oil injection. • Large Gauges that are easy to read. • Heavy-duty compressor pulls from both high and low sides during recovery. Optional Feature ♦ Database Expansion Slot – Makes it easier and faster to determine the charge capacity for refrigerant and oil. Included is the total system oil capacity as well as replacement oil amounts by component. The database (No. 34411) covers vehicles from 1994-2007. 34788 Unit General Information 34788 Service Manual 34788 VIEWS Control Panel FRONT VIEW Digital Display and Keyboard Shelves for tools and accessories Convenient Built-in Handle and Hose Storage Oil Inject Bottle Oil Drain Bottle Front Panel Database Expansion Slot Locking Casters Convenient Handle for moving unit Large Wheels for mobility across air lines, power cords, grates Low- and High-Side Hose Storage for Oil Inject Bottles/ Filter Drier Power Cord Oil Drain Bottle Electronic Scale & Calibration Device Fill Hose SIDE VIEW 7 General Information 34788 Service Manual OPERATING GUIDELINES Using the Control Panel Function Keys The function keys are used to start, stop, and select the service functions. These keys and their function are explained on the following page. Low-Side Gauge Shows the A/C system’s low-side pressure. High-Side Gauge Shows the A/C system’s high-side pressure. Low-Side Selection Indicator Illuminated blue light indicates low-side selection. Arrow Keys The UP and DOWN arrow keys are used for scrolling through menu items. High-Side Selection Indicator Illuminated red light indicates high-side selection. Digital Display Visual interface between the operator and the machine. Low-Side Gauge High-Side Gauge Numeric Keys Used to input numerical values, change evacuation time, vacuum levels, or recharge weight. Database Key Provides access to optional Vehicle/Refrigerant Database. Low-Side Selection Indicator High-Side Selection Indicator Digital Display Function Keys Arrow Keys Refrigerant Database Key Control Panel 8 Numeric Keys General Information 34788 Service Manual Keypad Functions Start / Yes Begins or resumes a function, or answers a query. Stop / No Terminates or pauses a function, or answers a query. Menu Displays the selection menu. (See Menu Functions on following page.) Arrows The UP and DOWN arrow keys are used for scrolling through menu items. Refrigerant Database Provides access to optional Vehicle/Refrigerant Database. Automatic Activates a menu which prompts the user through setting-up an automatic recover/vacuum/vacuum leak check/charge sequence. Recover Activates the recovery sequence. Vacuum Activates the vacuum and automatic recycling sequence, followed by an option to activate a vacuum leak check. Inject Oil Injects oil into the vehicle A/C system. Charge Charges the vehicle A/C system with a programmed amount of refrigerant. Start / Yes Stop / No START/ YES STOP/ NO Menu AUTOMATIC 1 Arrows Automatic MENU Refrigerant Database 2 3 ABC DEF 4 5 6 GHI JKL MNO 7 8 9 PQRS TUV WXYZ 0 Recover RECOVER VACUUM Vacuum INJECT OIL Inject Oil CHARGE SPACE Refrigerant Database Charge Keypad 9 General Information 34788 Service Manual Menu Functions 1. Press the MENU button on the keypad. 2. Press the UP or DOWN arrow key to scroll through the menu choices shown on the second line of the display: SELECT LANGUAGE SERVICE MENU CALIBRATION CHECK ADJUST TANK FILL LVL MANUAL REFILL REFRIG MANAGEMENT MAINTAIN FILTER MAINTAIN VACUUM OIL SELECT UNITS VERSION X.XX Menu Choice: Select Language Operator may choose to have prompts displayed in one of three languages: English, Spanish, or French. Menu Choice: Service Menu For Robinair service center use only. (See section 3.) Menu Choice: Calibration Check Use to verify internal scale calibration. Menu Choice: Adjust Tank Fill Lvl When connected to a refrigerant source, the unit maintains a pre-set amount of refrigerant in the internal storage vessel (default is 15 lbs.). This value may be adjusted up/down to suite the user’s needs. Menu Choice: Manual Refill Use to transfer refrigerant from the source tank to the internal storage vessel (ISV). Menu Choice: Refrig Management Displays the amount of refrigerant recovered, charged, and replenished (for the life of the unit), and filtered (since the last filter change). 10 3. Press START / YES to make a choice from the menu. Press STOP / NO to pause during any process, and STOP / NO a second time to exit a process. Start / Yes Button Stop / No Button Arrow Keys Menu Button Menu Choice: Maintain Filter The filter-drier removes acid, particulates, and moisture from the refrigerant. To meet the requirements of UL J-2788, it is mandatory to replace the filter-drier after 150 lbs. (68 kg) of refrigerant has been filtered. The menu item will show how much refrigerant has been filtered since the last filter change, and allows the user to reset the value once a filter change is complete. It will be necessary to enter a 10-digit code, which appears on the filter, to ensure compliance with UL J-2788. Menu Choice: Maintain Vacuum Oil For maximum vacuum pump performance, change vacuum pump oil after every 10 hours of operation. This menu item displays how long the vacuum pump has operated since the last oil change, and allows the user to reset the value once an oil change is complete. Menu Choice: Select Units Operator may choose to have test results displayed in Imperial (lbs.), Imperial (lbs. and oz.), or Metric (kg.). Menu Choice: Version X.XX Displays the revision level of the software in the unit. General Information 34788 Service Manual UNIT SPECIFICATIONS 34788 Unit - General Information Volts: 115V * Frequency: 60 Hz Amps: 12.0A R-134a 98 Class III, ARI 98 Class IV High - 377 psig Low - 171 psig 0 to 140°F (-18 to 60°C) Refrigerants: Design Pressure: Storage Temperature Range: 50 to 120°F (11 to 49°C) Operating Temperature Range: 43 cu. In spin-on type Recycling Filter-Drier: Unit Height: 49 in. (124.5 cm) Unit Width: 34 in. (86.4 cm) Unit Depth: 23 in. (58.4 cm) 235 lbs. (106.6 kg) UL Listed SAE-J2788 Shipping Weight: Certified: Hermetic Compressor (Cubigel) Volts: 115V * Frequency: 60 Hz 8.4A Running Amps: 30.0A Locked Rotor Amps: .55 CU IN Displacement: 5821 Capacity (BTU/HR): 13.5 oz/11.8 oz (400 cc/350 cc) Oil Charge Capacity (Initial/Recharge): ISO 22 POE Oil Type: Vacuum Pump Volts: 110V * Frequency: 60 Hz Running Amps: Locked Rotor Amps: 4.5A Contact Tech Support Motor: 1/3 HP Stages: 2 Flow Rate: 3 cfm (71 l/m) Oil Capacity: 7.4 oz. (219ml) * The voltage at the unit must be ±10% of the unit's rated voltage. Extension cords must be a minimum of 14 AWG and kept as short as possible. (25 ft./7.6 m. or less) 11 General Information 34788 Service Manual MAINTENANCE SCHEDULE Test Required Change vacuum pump oil. Recommended Frequency Every 10 hours of operation. Change the Filter/Drier. After recovering 150 lbs. (68 kg) of refrigerant or after recovering refrigerant from a burnedout system. Fiter/Drier Warning After recovering 100 lbs. (45 kg) of refrigerant. Check Scale (Refer to scale calibration instructions in Diagnostic Section if needed.) Monthly Check for Leaks. Monthly Clean (vacuum) condenser panel. Monthly Clean cabinet and control panel. Monthly Check casters and wheels for proper operation. Lubricate bearings and brake components if necessary. Monthly Inspect hoses and power cord for cuts and abrasions. Daily Due to normal wear and tear, the 34788 requires regular maintenance to guarantee safe operation and optimum performance. The above chart provides a schedule of the recommended maintenance tasks. 12 34788 Service Manual General Information NOTES ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ 13 General Information 14 34788 Service Manual P a r ts & C o m p o n e n ts 34788 Service Manual 2 PARTS & COMPONENTS 34788 External Parts ............................................................................................ 16 34788 Internal Parts.............................................................................................. 18 Component Assemblies ....................................................................................... 20 34788 Head Assembly ....................................................................................................... 34788 Head Assembly-Exploded View ............................................................................ Station Pump Assembly, 115V .......................................................................................... Compressor Assembly, 115V ............................................................................................. 34788 Manifold Assembly ................................................................................................. Internal Tank Assembly .................................................................................................... 20 21 22 23 24 26 Plumbing Diagram and Parts List ....................................................................... 27 34788 Main Component Descriptions ................................................................ 28 Alphabetical Parts List ......................................................................................... 30 Disclosure: Although most parts are listed, some part numbers are part of an assembly available only to manufacturing. Information and part numbers contained in this publication were accurate at the time it was written. Any discrepancies should be brought to the attention of Robinair Technical Support. 15 P a r ts & C o m p o n e n ts 34788 Service Manual 34788 EXTERNAL PARTS 5 11 1 6 7 2 9 10 3 12 8 3 4 34788 EXTERNAL PARTS No. 1 2 3 4 5 6 7 8 9 10 11 12 16 Description DECAL, FRONT, 34788 ENCLOSURE, HEAD-SHOULDER FRONT PANEL BASE ASSEMBLY HEAD ASSEMBLY POWER SWITCH SIDE SUPPORT ASSEMBLY OIL DRAIN BOTTLE HIGH SIDE HOSE SPUD LOW SIDE HOSE SPUD DECAL, 1-800 PHONE NUMBER REAR DOOR Qty. Part No. 1 1 1 122293 1 122206 1 1 RA19343 9 539750 1 17756 1 1 1 1 121575 P a r ts & C o m p o n e n ts 34788 Service Manual 1 3 4 5 2 6 34788 EXTERNAL PARTS No. 1 2 3 4 5 6 Description OPERATOR'S MANUAL WHEEL, PNEUMATIC, 10" OIL INJECT BOTTLE REAR DOOR DOOR LATCH KIT CASTER, 5" DIA X 2" WIDE Qty. Part No. 1 539602 2 19823 1 19867 1 121575 2 RA19632 2 RA19631 17 P a r ts & C o m p o n e n ts 34788 Service Manual 34788 INTERNAL PARTS SEE DETAIL C 34788 UNIT COMPONENTS No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Description BASE ASSY ASSY, SIDE SUPPORT CENTER DIVIDER SHELF, VACUUM PUMP SCALE ASSEMBLY & MAGNET GROMMET, COMPRESSOR COMPRESSOR, ASSEMBLY, 115V MANIFOLD, ASSEMBLY, ENCLOSURE, HEAD-SHOULDER PCB ASSEMBLY, RELAY BRD BRACKET, PUMP MOUNTING STATION PUMP, 115V, 3CFM ISV ASSEMBLY BOLT, 1/4-20 X 1/2" FAN ASSEMBLY, 115V SCREW, 10-24 X 5.8" Qty. 1 1 1 1 1 4 1 1 1 1 2 1 1 2 1 2 34788 UNIT COMPONENTS Part No. 122206 539750 RA20002 RA20020 RA20018 RA20013 RA20017 RA17416 No. 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 Description SLEEVE, COMPRESSOR WASHER, 1/4" ID FENDER BOLT, 1/4-20 X 2" SERR HEAR LOCKNUT, 1/4-20 STABILIZER BRACKET BOLT, 1/4-20 X 1.5" BOTTLE, OIL DRAIN PANEL, CONDENSER COVER NUT, 8-32 SEMS BRACKET, POWER CORD BUSHING, HEYCO BRACKET, CAPACITOR CAPACITOR, 115V COMP. CAP, 38MM METAL DRILLED NUT, NYLON FITTING, STRAIGHT THRU NOTE: The above parts listing may refer to parts located on unit diagrams on following page. 18 Qty. Part No. 1 12 4 10 1 1 1 17756 1 6 4 1 1 1 1 1 1 P a r ts & C o m p o n e n ts 34788 Service Manual SEE DETAIL A DETAIL B SEE DETAIL B DETAIL A 34788 UNIT COMPONENTS No. 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 Description BOTTLE, OIL INJECT CIRCUIT BREAKER, 15 AMP SCREW, 1/4"-20 X 3.4" SCREW, 8-32 X 3/8 SEMS "O" RING RUBBER BUMPER WASHER, 1/4" FLAT SCREW, 1/4 X 3/4" PLASTITE FRONT PANEL ASSEMBLY DOOR, REAR MAGNET (PART OF SCALE ASSY) SCREW, 1/4 -20 X 3.5 LONG SCREW, 1/4-20 X 1/2" LONG SWITCH, DPST (I/O) SCREW, 6-32 X 3/8 DOOR LATCH KIT Qty. 1 1 13 1 1 1 7 18 1 1 1 1 1 1 5 2 Part No. 19867 518638 DETAIL C 122293 121575 RA20002 RA19343 RA19631 34788 UNIT COMPONENTS No. 51 52 54 55 Description Qty. Part No. 1 HEAD ASSEMBLY, 34788 ENCLOSURE, HEAD-HINGE COVER 2 1 RA20014 POWER SUPPLY, 12 VOLT SCREW, SOCKET HD CAP M3-.5 X 5 4 NOTE: The above parts listing may refer to parts located on unit diagrams on previous page. 19 P a r ts & C o m p o n e n ts 34788 Service Manual COMPONENT ASSEMBLIES 34788 HEAD ASSEMBLY 34788 HEAD ASSEMBLY No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 22 23 24 25 20 Description Qty ENCLOSURE, SWIVEL TOP-FRONT 1 DECAL, FRONT, 34788 1 SCREW, MACH 6-32 X .188 6 GAUGE, LOW SIDE 1 GAUGE, HIGH SIDE 1 ELBOW, 1/8 MP X 1/8 PNEUMATIC 2 NUT, 10-32 HEX SEMS 4 ENCLOSURE, SWIVEL TOP-BACK 1 ENCLOSURE, SWIVEL TOP-POCKET 1 PCB ASS'Y, SD CARD, NGEN RRR 1 ENCLOSURE, SWIVEL TOP-SD COVER 1 SCREW, THD FORM, 4-20,.50, PHD, PH 4 SCREW, #6-19 X 1/2 EH TORX PLAST 6 BEZEL 1 KEYPAD 1 PCB ASS'Y, DISPLAY/CONTROL BRD 1 SCREW, 6-32 X 3/8 4 CABLE, INTERCONNECT 1 CABLE, SD BOARD 1 TUBE, 1/8" RED 4' TUBE, 1/8" BLUE 4' Part No. 539955 539956 RA20011 RA20001 RA20001 RA20012 539995 539996 RA20003 RA20004 P a r ts & C o m p o n e n ts 34788 Service Manual 34788 HEAD ASSEMBLY EXPLODED VIEW 23 22 Wiring Detail 21 P a r ts & C o m p o n e n ts 34788 Service Manual STATION PUMP ASSEMBLY, 115V RA20017 3 4 2 1 5 6 7 8 STATION PUMP ASSEMBLY, 115V No. 1 2 3 4 5 6 7 8 Description STATION PUMP ASSEMBLY RESERVOIR ASSEMBLY BRASE DISCHARGE FITTING * BRASS INLET FITTING * SIGHT GLASS NUT * OIL FILL PLUG * SIGHT GLASS ASSEMBLY W/O-RING * OIL DRAIN ASSEMBLY W/CAP * Qty 1 1 1 1 1 1 1 1 Part No. RA20017 RA19950 * Items followed by an asterisk are part of the Reservoir Assembly Kit (RA19950) and are not sold separately. 22 P a r ts & C o m p o n e n ts 34788 Service Manual COMPRESSOR ASSEMBLY, 115V RA20020 1 DISCHARGE SUCTION SUCTION SUCTION SUCTION DISCHARGE COMPRESSOR ASSEMBLY, 115V No. 1 Description COMPRESSOR, 115V RELAY PROTECTOR CAPACITOR COVER BAIL BRACKETS SCREW SLEEVE GROMMET CAPACITOR WIRE Qty 1 1 1 1 1 1 1 1 4 4 2 Part No. RA20020 INC INC INC INC INC INC INC INC INC INC 23 P a r ts & C o m p o n e n ts 34788 Service Manual 34788 MANIFOLD ASSEMBLY RA20018 See Note Next Page B 32 5 X 2X E See Note Next Page SERVICE PORT A See Note Next Page C See Note Next Page D 34788 MANIFOLD ASSEMBLY No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Description Qty. Part No. MANIFOLD BLOCK, TOP 1 MANIFOLD BLOCK, LOWER 1 ELBOW, 1/8 MP X 3/8 PNEU COMP 3 HEAT EXCHANGER 1 O-RING 2 ACCUMULATOR SHELL 1 O-RING, PKR #SB17-119-7N 1 O-RING, PKR #SB17-143-7N 1 SEPARATOR ELEMENT 1 OIL SEPARATOR BOWL(1.5-3.0 IN LB 1 UNION, 1/8 MP X 1/8 MP X .97 2 TUBE, MANIFOLD CONN,(75 IN LBS) 1 FITTING, 1/4 MFL X 1/8 NPTF 1 SCHRADER CORE, (1.5-3.0 IN LBS) 1 CAP, 1/4 FLARE W/ O-RING 1 F See Note Next Page See Note Next Page 34788 MANIFOLD ASSEMBLY No. 16 17 18 19 20 21 22 23 24 25 26 27 29 30 31 32 Description Qty. SOLENOID, 12V DC DISCRETE 2 SOLENOID, 12V DC MAN,(75 IN LBS) 12 NUT, COMPRESSION (1/8 TUBE) 2 ELBOW, 1/8 NPTF X 1/4 COMP 1 ACCUM TRANSDUCER 2 CHECK VALVE, (75 IN LBS) 6 TEE, MALE BRANCH 1/8 NPTF 1 CHECK VALVE 1 FITTING, 1/8 NPT X 1/4 COMP 2 O-RING, C0873 2-240 1 FILTER DRIER, SPIN-ON 1 ELBOW, 1/8 MP X 1/8 PNEU 1 FITTING, HALF UNION .12MP X .25 FL 2 SWITCH, HIGH PRESSURE CUT-OUT 1 SCREW, SOCKET, (30 IN LBS) 1 BALL, MANIFOLD PLUG 5 NOTE: The above parts listing may refer to manifold parts on following page. 24 6X Part No. RA20009 RA20010 RA20008 RA20016 RA20015 34724 RA19427 P a r ts & C o m p o n e n ts 34788 Service Manual 3X NOTE A. Torque Schrader Core (item 14) to 1.5-3.0 IN. LBS. B. Torque to 30 IN LBS ±5. C. Apply Loctite 242 to threads of Manifold Connection Tube (item 12) and torque to 75 IN. LBS. D. Torque Manifold Solenoid (item 17) to manifold with 75 IN. LBS. ±5. Torque Fastener to 30 IN LBS ±5. E. Press flush ±.030 with surface. F. Torque Checkvalve (item 21) to 75 IN. LBS. (6 places) G. Use (Loctite 565) on all pipe threads. H. Lubricate all O-rings on components before assembling. NOTE: The above notes may refer to the manifold diagram on previous page. 25 P a r ts & C o m p o n e n ts 34788 Service Manual INTERNAL TANK ASSEMBLY 3 4 9 5 10 8 11 2 7 12 6 13 1 Use Loctite 565 on all pipe threads. Tank Tare Weight: Worthington: 17.50 lbs. (7.94 kg.) Air Com: 20.50 lbs. (9.30 kg.) ISV ASSEMBLY No. 1 2 3 4 5 6 7 8 9 10 11 12 13 26 Description ISV, INTERNAL FITTING, STRAIGHT SOLENOID, 12V DC DISCRETE VALVE, BALL VALVE, BALL PRESSURE RELIEF, 450PSI FITTING, TEE, .25FP X .25FP X .25MP VALVE, BALL TEMPERATURE PROBE TRANSDUCER, AIR PURGE TEE, MALE BRANCH 1/8 NPTF ORIFICE, UNION .026 MUFFLER, AIR EXHAUST Qty 1 1 1 1 1 1 1 1 1 1 1 1 1 Part No. 539477 210312 RA20009 539799 539798 RA19499 508690 540322 539472 539229 539654 539804 519605 P a r ts & C o m p o n e n ts 34788 Service Manual PLUMBING DIAGRAM USE LOCTITE 242 OR EQUIVALENT ON THREADS USE LOCTITE 242 OR EQUIVALENT ON THREADS STA-STRAP TUBES TO SLOTS IN SIDE SUPPORT USE LOCTITE 242 OR EQUIVALENT ON THREADS CUT END OF TUBE AT 45° AND INSERT TO BOTTOM OF BOTTLE RED TUBE FROM HIGH SIDE GAUGE RED SERVICE HOSE ROUTE THROUGH HOLES IN SIDE SUPPORT VACUUM PUMP EXHAUST SHOULD PROTRUDE APPROX. 1.5” INTO OIL DRAIN BOTTLE BLUE SERVICE HOSE ROUTE THROUGH HOLES IN SIDE SUPPORT BLUE TUBE FROM LOW SIDE GAUGE USE LOCTITE 242 OR EQUIVALENT ON THREADS USE LOCTITE 242 OR EQUIVALENT ON THREADS BLACK TANK FILL HOSE ROUTE THROUGH HOLE IN SIDE SUPPORT Plumbing Diagram Parts List No. 1&2 Description HOSE SET, SERV (HI & LOW-SIDE) Qty. Part No. 1 34722 3 TUBE, 1/4 OD X 0.040 ID 19" 120225 4 TUBE, 3/8" HIGH PRESSURE 16" RA20005 5 HOSE, ISV LIQUID 1 541533 6 HOSE, VAPOR 1 539068 7 TUBE, 1/4 OD X 0.040 ID 23" 120225 8 HOSE, TANK FILL 1 539007 9 TUBE, 1/4 OD X 0.040 ID 28" 120225 10 TUBE, 3/8" HIGH PRESSURE 15" RA20005 11 TUBE, COMPRESSOR TO MANIFOLD 1 538469 12 TUBE, 3/8" HIGH PRESSURE 12" RA20005 13 TUBE, NYLON 1/8 OD X .070 ID 27" 121773 14 NUT, COMPRESSION (3/8 TUBE) 2 RA20006 15 O'RING (PKR #5-124) NEOPRENE 2 RA19916 16 NUT, COMPRESSION (1/4 TUBE) 1 RA20007 17 NUT, COMPRESSION (3/8 TUBE) 1 RA20006 18 STA-STRAP 8" LONE X .18" 2 Item # RA20005 (tube, 3/8” high pressure) comes in a length of 1.5’. Cut hose to proper length as indicated in plumbing parts list. 27 P a r ts & C o m p o n e n ts 34788 Service Manual 34788 MAIN COMPONENT DESCRIPTIONS 12V POWER SUPPLY — Provides 12 volts to power the circuit boards, manifold block components, and the ISV air purge solenoid. BOTTLE, OIL DRAIN — Recovers the used oil during the oil drain process. BOTTLE, OIL INJECT — Stores oil for injection into the A/C system. BREAKER, 15 AMP — Protects the unit from drawing to much current. If blown, unit is completely inoperative. CALIBRATION BALL — Calibration standard that attaches to magnet under scale assembly. Used to verify scale calibration. CASTER — 5” x 2” wheels used for maneuvering unit. CHECK VALVE — Allows flow in one direction only. GAUGE, LOW SIDE — Monitors low-side pressure of the vehicle being serviced. HEAD ASSEMBLY — User interface panel for controlling refrigerant recovery, recycling and recharging. HIGH PRESSURE CUTOUT SWITCH — Switch opens at 435 ± 10 psi (2999 ± 69 kPa) and resets at 320 ± 20 psi (2066 ± 137 kPa). If pressure in the high side of the system exceeds 435 psi (2999 kPa), the switch opens stopping all functions. INTERNAL STORAGE VESSEL (ISV) — Storage tank that the recovered and recycled refrigerant is stored. Vapor, liquid, and air purge access is on-top of tank. KEYPAD — Touch-pad cover for the front of the control board. COMPRESSOR — Moves refrigerant from the A/C system being serviced into the internal tank on the unit. MANIFOLD BLOCK ASSEMBLY — Internal block assembly that contains solenoids, check valves and switches. Refrigerant will flow through the manifold assembly for proper distribution. COMPRESSOR CAPACITOR — Used for starting the compressor. Helps reduce the initial high current demand required by the compressor on start-up. MUFFLER, AIR EXHAUST — Disperses excessive air from the ISV. Provides effective reduction of objectionable air exhaust noise. COMPRESSOR OIL SEPARATOR — Removes the compressor oil from the refrigerant that is leaving the compressor. The stored oil is returned to the compressor when the oil return solenoid receives power. ORIFICE, UNION— Fitting used to reduce the flow rate. POWER CORD — Supplies main power to the unit. DISPLAY/CONTROL BOARD — Front display panel and main control of the 34788. PRESSURE RELIEF VALVE, 450 PSI — Spring loaded safety valve use to releases pressure from internal tank assembly if pressure exceeds 450 psi. DOOR LATCH KIT — Used to replace spring-loaded latch, retainer, and door latch receptacle. RELAY BOARD — Relay control for all 12V and 115V components. FAN, 115V — Keeps the compressor’s electrical components cool. SCALE ASSEMBLY — Measures the amount of refrigerant being charged and recovered. FILTER DRIER, SPIN-ON — Used to remove moisture and particles from refrigerant. Must be changed every time 150 lbs of refrigerant is recovered. SD CARD PCB ASSEMBLY — Used to read information from Secure Digital (SD) memory cards. SIGHTGLASS – Used to view vacuum pump oil level. GAUGE, HIGH SIDE — Monitor high-side pressure of the vehicle being serviced. 28 34788 Service Manual SOLENOID (1), NORMAL DISCHARGE — When energized, allows refrigerant flow from the compressor to the system oil separator, then to the internal storage vessel. SOLENOID (2), HIGH-SIDE CLEAR — Energized during the high-side clearing process. SOLENOID (3), OIL INJECT — Energized during the Oil Inject process to allow A/C system oil to be replenished. SOLENOID (4), DEEP RECOVER — When energized, uses vacuum pump to perform “deep” recovery of refrigerant from the system being serviced. SOLENOID (5), HIGH-SIDE CHARGE — When energized, allows refrigerant from ISV to enter high-side of system being serviced. SOLENOID (6), LOW-SIDE CHARGE — When energized, allows refrigerant from ISV to enter low-side of system being serviced. SOLENOID (7), HIGH-SIDE INLET — Allows an open “pathway” for refrigerant flow and vacuum between the A/C system high side and the 34788 unit. This solenoid is powered during the Recover, Vacuum, and Leak Check process. SOLENOID (8), VACUUM — When energized, allows a vacuum or deep recovery to be pulled on the A/C system being serviced. SOLENOID (9), LOW-SIDE INLET — Allows an open “pathway” for refrigerant flow and vacuum between the A/C system low side and the 34788 unit. This solenoid is powered during the Recover, Vacuum and Flush process. SOLENOID (10), RECOVERY — When energized, provides the primary pathway of removing refrigerant from the system being serviced. This solenoid is also powered during the Flush process. SOLENOID (11), TANK FILL — When energized during the Tank Fill process, allows refrigerant to flow from the external supply tank to the ISV. P a r ts & C o m p o n e n ts SOLENOID (12), POWER CHARGE/FEEDBACK — Provides “feedback” pressure to assist the oil drain operation. Also, increases tank pressure to assist the charging function. SOLENOID (13), OIL RETURN — When energized, it returns compressor oil from the compressor oil separator to the compressor and equalizes the pressure on the high and low side of the compressor. SOLENOID (14), OIL DRAIN — Energized at the end of the Recover process to drain oil. SOLENOID (15), AIR PURGE — Energized to allow excessive air to be removed from the internal tank. SWITCH ON/OFF — Allows the unit to be turned ON and OFF. SYSTEM OIL SEPARATOR — Heat exchanger with highside coils that provide internal heat to the canister causing saturated vapor and accumulated liquid refrigerants to evaporate. This process prevents liquid refrigerant from entering the compressor and separates the refrigerant oil. TEMPERATURE PROBE — Monitors the temperature inside the internal storage vessel (ISV). TRANSDUCER, ACCUM (SYSTEM OIL SEPARATOR) — Measures the pressure within the system oil separator. TRANSDUCER, AIR PURGE — Measures the pressure within the internal storage vessel (ISV). TRANSDUCER, LOW-/HIGH-SIDE — Measures the pressure of incoming refrigerant from the A/C system. Pressure readings are then relayed to the control board. VACUUM PUMP — 115V pump designed to remove moisture and air from an A/C system. Also aids in the recovery process by performing a deep recovery of A/C system. WHEEL, PNEUMATIC 10” — Transport wheels. 29 P a r ts & C o m p o n e n ts 34788 Service Manual ALPHABETICAL PARTS LIST DESCRIPTION PART # 12 VOLT, POWER SUPPLY RA20014 34788 BASE, WHEELS & CASTORS ASSEMBLY 122206 34788 FRONT PANEL ASSEMBLY 122293 34788 REAR DOOR 121575 34788 SIDE SUPPORT ASSEMBLY 539750 AC POWER CORD 122770 AIR EXHAUST MUFFLER 519605 AIR PURGE TRANSDUCER 539229 BALL VALVE, AIR PURGE 539799 BALL VALVE, LIQUID 539798 BALL VALVE, VAPOR 540322 BOTTLE, OIL DRAIN 17756 BOTTLE, OIL INJECT 19867 CABLE, INTERCONNECT 539995 CABLE, SD BOARD 539996 CALIBRATION WEIGHT 540066 CAP AND FILLER TUBE 17191 CAP, OIL INJECT BOTTLE RA19914 CAPACITOR, 110V START (COMPRESSOR) RA19489 CASTER, 5” DIA X 2” WIDE RA19631 CHECK VALVE KIT, MANIFOLD RA20016 CHECK VALVE, VACUUM RELIEF RA20015 CIRCUIT BREAKER, 15 AMP 518638 COMPRESSOR ASSEMBLY, 115 VOLTS RA20020 30 NOTES Kit inc. 6 valves 34788 Service Manual DESCRIPTION P a r ts & C o m p o n e n ts PART # NOTES COMPRESSOR OIL, MSDS-POLYOL ESTER OIL RA17283 COMPRESSOR START KIT RA19489 CORE SCHRADER RA19916 COUPLER SET, SERVICE (HIGH & LOW-SIDE COUPLERS) 18192 DISPLAY/CONTROL BOARD RA20012 DOOR LATCH KIT RA19632 DUST COVER, VINYL (OPTIONAL) 17488 FAN, 115V RA17416 FILTER DRIER, SPIN-ON 34724 FITTING, STRAIGHT 210312 ISV Assembly FITTING, TEE, .25FP X .25FP X .25MP 508690 ISV Assembly GAUGE, HIGH SIDE 539956 GAUGE, LOW SIDE 539955 HARNESS, COMPRESSOR PIGTAIL 539991 HARNESS, FAN COMPRESSOR 539989 HARNESS, GROUND 539993 HARNESS, HIGH PRESSURE CUT-OUT 539992 HARNESS, MANIFOLD 1 539927 HARNESS, MANIFOLD 2 539987 HARNESS, POWER 539990 HARNESS, POWER SUPPLY 539994 HARNESS, TRANSDUCER 539988 HIGH PRESSURE CUT-OUT SWITCH RA19427 HOSE SET, SERVICE (HIGH & LOW-SIDE HOSES) 34722 Optional Less couplers 31 P a r ts & C o m p o n e n ts DESCRIPTION 34788 Service Manual PART # HOSE, LIQUID 541533 HOSE, TANK FILL 539007 HOSE, VAPOR 539068 ISV TANK, INTERNAL 539477 KEYPAD & BEZEL ASSEMBLY RA20001 MAGNET & SCALE ASSEMBLY RA20002 MAINTENANCE KIT 13172 MANIFOLD ASSEMBLY RA20018 MANUAL, OWNERS 34788 539602 MUFFLER, AIR EXHAUST 519605 NUT, COMPRESSION (1/4 TUBE) RA20007 NUT, COMPRESSION (1/8 TUBE) RA20008 NUT, COMPRESSION (3/8 TUBE) RA20006 OIL DRAIN BOTTLE 17756 OIL INJECT BOTTLE 19867 OIL INJECT BOTTLE CAP RA19914 OIL, VACUUM PUMP, CASE OF 12 PINTS 13119 OIL, VACUUM PUMP, CASE OF 12 QTS. 13203 OIL, VACUUM PUMP, CASE OF 4 GAL 13204 OIL, COMPRESSOR, MSDS-POLYOL ESTER OIL RA17283 ORIFICE, UNION .026 539804 PCB ASSEMBLY, DISPLAY/CONTROL BOARD RA20012 PCB ASSEMBLY, RELAY BOARD RA20013 PCB ASSEMBLY, SD CARD RA20011 32 NOTES ISV Assembly 34788 Service Manual DESCRIPTION P a r ts & C o m p o n e n ts PART # NOTES POWER SUPPLY, 12 VOLT RA20014 PRESSURE RELIEF, 450 PSI RA19499 PROTECTOR, 110V MOTOR OVERLOAD RA19489 RELAY, 110V STARTING RA19489 RELAY BOARD RA20013 SCALE ASSEMBLY & MAGNET RA20002 SD CARD, PCB ASSEMBLY RA20011 SERVICE COUPLER LOW SIDE (R134A) 18190A SERVICE COUPLER HIGH SIDE (R134A) 18191A SERVICE COUPLER SET (HIGH & LOW-SIDE COUPLERS) 18192 SERVICE HOSE SET (HIGH & LOW-SIDE HOSES) 34722 SOLENOID, 12V DC DISCRETE RA20009 SOLENOID, 12V DC MANIFOLD RA20010 SWITCH, HIGH PRESSURE CUT-OUT RA19427 SWITCH, ON-OFF, (I-O) RA19343 TEE, MALE BRANCH 1/8 NPTF 539654 TEMPERATURE PROBE 539472 TRANSDUCER, AIR PURGE 539229 TUBE, 1/4 OD X 0.040 WALL 120225 Ordered by the foot TUBE, 1/8" BLUE RA20004 3 ft. TUBE, 1/8" RED RA20003 3 ft. TUBE, 3/8" HIGH PRESSURE RA20005 TUBE, COMPRESSOR TO MANIFOLD 538469 TUBE, NYLON 1/8 OD X .075ID 121773 Less couplers ISV Assembly Ordered by the foot 33 P a r ts & C o m p o n e n ts DESCRIPTION 34788 Service Manual PART # VACUUM PUMP, 115V 3CFM RA20017 VACUUM PUMP OIL, CASE OF 12 PINTS 13119 VACUUM PUMP OIL, CASE OF 12 QTS. 13203 VACUUM PUMP OIL, CASE OF 4 GAL 13204 VACUUM PUMP RESERVOIR ASSEMBLY RA19950 WEIGHT, CALIBRATION 540066 WHEEL, CASTER, 5” DIA X 2” WIDE RA19631 WHEEL, PNEUMATIC, 10” 19823 WIRE HARNESS, COMPRESSOR PIGTAIL 539991 WIRE HARNESS, FAN COMPRESSOR 539989 WIRE HARNESS, GROUND 539993 WIRE HARNESS, HIGH PRESSURE CUT-OUT 539992 WIRE HARNESS, MANIFOLD 1 539927 WIRE HARNESS, MANIFOLD 2 539987 WIRE HARNESS, POWER 539990 WIRE HARNESS, POWER SUPPLY 539994 WIRE HARNESS, TRANSDUCER 539988 34 NOTES 34788 Service Manual P a r ts & C o m p o n e n ts NOTES ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ ____________________________________________________ 35 P a r ts & C o m p o n e n ts 36 34788 Service Manual 34788 Service Manual 3 Diagnostics DIAGNOSTICS Functional Check ................................................................................................. 38 Service Center Menu Options ............................................................................. 40 Output Step Test ................................................................................................... 41 Depressurizing the Unit ....................................................................................... 42 12VDC Solenoid Test Procedure ........................................................................ 43 Troubleshooting ................................................................................................... 44 Unit Will Not Power-Up, No Display ................................................................................ Will Not Tank Fill .............................................................................................................. Will Not Recover (First Stage) .......................................................................................... Will Not Deep Recover (Second Stage) .......................................................................... Will Not Perform Clearing ................................................................................................ Will Not Air Purge ............................................................................................................. Will Not Drain Oil .............................................................................................................. Will Not Evacuate (Vacuum) ............................................................................................. Fails Leak Test .................................................................................................................. Will Not Inject Oil .............................................................................................................. Will Not Charge ................................................................................................................. Miscellaneous Error Messages ......................................................................................... 44 45 46 47 48 49 49 50 51 51 52 53 Service Instructions and Calibration .................................................................. 54 Replacement Compressor (RA20020) Specifications & Service .................................... Replacement Vacuum Pump (RA20017) Specifications & Service ............................... Replacement High Pressure Cut-Out Switch (RA19427) ................................................. Replacement Scale Assembly/Magnet (RA20002) .......................................................... Replacement Manifold Block (RA20018) ......................................................................... Replacement Manifold Solenoid (RA20010) ................................................................... Replacement Display Board (RA20012) ........................................................................... Replacement Relay Board (RA20013) .............................................................................. Replacement Vacuum Relief Check Valve (RA20015) .................................................... Replacement Manifold Check Valve (RA20016) .............................................................. Replacement 3/8” High Pressure Tube (RA20005) .......................................................... 54 57 58 59 60 63 64 66 68 69 70 System Wiring ...................................................................................................... 71 34788 Component Wiring .................................................................................... 72 34788 Wiring Harnesses ...................................................................................... 75 Component Identification ................................................................................... 86 Component Application Chart ............................................................................. 87 Flow Diagrams ...................................................................................................... 88 37 Diagnostics 34788 Service Manual FUNCTIONAL CHECK Setup 1. Check to make sure all lines are correctly connected to tank and that all tank valves are open. 2. Connect the unit’s service hoses up to a test tank. 3. Plug unit into correct power source. 4. Turn main power on. 5. Unit will show “Version X.XXX” and “Relay Version X.XXX.” 6. Unit will display “Refrig XX.XX lbs, Select Function.” If low on refrigerant, unit may display “Low Refrigerant” ”Fill Tank.” 7. 8. 9. 10. Press the [Start] key so that No changes to Yes. Once it says Yes, press the [Stop] key. Unit will show “Display Acc Pressure.” Press the [Stop] key again to exit. Vacuum 1. Press the [Vacuum] key. 2. Unit will display “Checking Pressure.” 3. Program unit to pull a 2 ½ minute vacuum on the test tank. 4. Press the [Start] key. You will be asked if you want to do a leak test. Select “no” unless the complaint was for “unit fails leak test.” 5. Unit will display “Vacuum in Progress, Time Remaining XX.XX, Stop to Pause.” 6. Once the vacuum is complete, the unit will display “Vacuum Complete, Any Key Exits.” 7. Press the [Stop] key. 8. Unit will display “Refrig XX.XX, Select Function.” During the Vacuum process, you may hear the unit purging air, this is normal operation. Charging Test 34788 Keypad Set unit up to Display Accumulator Pressure 1. Press the [Menu] key. 2. Press the [Down Arrow] key two (2) times to display “Service Menu.” 3. Enter the service code by pressing the following keys individually: [2-2-0-0], and then press the [Start] key. 4. From the Service Menu, press the [Down Arrow] key until the display shows “Display Accumulator Pressure.” 5. Press the [Start] key. 6. Unit will display “Start Changes State, Display Acc Pressure, No, Stop to Exit.” 38 1. Press the [Charge] key. 2. Unit will display “Charge XX.XX, Mode xxxx Side, Charge Changes Mode, Arrow Key Change Unit.” 3. Enter 02.55 lbs charge using the keypad. 4. Press the [Charge] key two (2) times so both the red and blue lights are lit. To verify Oil Inject function, you will need to charge high-side only. 5. Press the [Start] key. “Charge in Progress” appears on the display. (“Purging Air Please Wait” may also show on display.) 6. “High and Low Side Charge in Progress Do Not Disturb” will show on display. When the unit gets towards the end of the charge, you will notice that it slows down and then pulses the last .10 lbs. in. This is done for charging accuracy. 34788 Service Manual 7. When charging is complete, the unit will display “Charged XX.XX lbs, Press Start to Equalize Hoses.” 8. Press the [Start] key. 9. Unit will display “Disconnect High Side HoseCouple and Connect the Low Side Hose and Start A/C Max, Start To Continue.” 10. Close both tank valves and press the [Start] key. 11. Unit will display “Equalizing Hoses Please Wait.” 12. When hose equalizing is completed, unit will display “Disconnect LS Hose Start to Continue.” 13. Leave all hoses connected to test tank and make sure that both tank valves are still closed. 14. Press the [Start] key. 15. Unit will display “Clearing Hoses Please Wait.” 16. When clearing is complete, unit will display “Charge Complete X.XX lbs.” 17. Press the [Stop] key. 18. Unit will display “Refrig XX.XX lbs, Select Function.” Recovery Test 1. 2. 3. 4. Open both tank valves and invert test tank. Press the [Recover] key. Unit will display “Checking Pressure.” Once the unit makes sure there is enough pressure, it will then display “Recovery Clearing.” • Once the recovery clearing in done, the unit will display the “Recovery in Progress, Recovered Amount X.XX, Accumulator Pressure XX psi, Stop to Pause.” • Accumulator pressure shows the amount of pressure (refrigerant) that is being allowed in during the recovery process. It should not exceed 38 psi. As the refrigerant is recovered this number will decrease and eventually go into a negative (inhg) number. • Once the calibrated low side gauge reaches “0”, the vacuum pump will start while the compressor is still running. The amount of vacuum time depends on how long it took for the unit to complete the recovery for the amount of refrigerant recovered. Diagnostics • Once the vacuum pump starts, you will notice that the Accumulator pressure rises back to “0” inhg*. This is accomplished by opening the oil return and/or pressure feedback solenoid. The reason for this is to keep the exhaust of the vacuum pump out of a negative pressure situation so that oil is not pulled out of the vacuum pump. *During the Vacuum process the pressure will float between 3 psi and 3 inhg. 5. When the vacuum pump timer times out, the unit displays “Recovery in Progress, Recovered X.XX lbs, Clearing Please Wait.” 6. When Clearing is complete, the unit will display “Draining Oil, Accumulator Pressure XX, Please Wait.” (Accumulator Pressure will rise to 16 psi.) 7. After the oil drain is complete, the unit will display “Recovery Complete, Recovered X.XX, Check Oil Bottle.” 8. When the vacuum process is complete, turn off the Display Accumulator Pressure. To turn off the Display Accumulator Pressure 1. Press the [Menu] key. 2. Press the [Down Arrow] key two (2) times to display “Service Menu.” 3. Enter the service code by pressing the following keys individually: [2-2-0-0], and then press the [Start] key. 4. From the Service Menu, press the [Down Arrow] key until the display shows “Display Accumulator Pressure.” 5. Press the [Start] key. 6. Unit will display “Start Changes State, Display Acc Pressure, Yes, Stop to Exit.” 7. Press the [Start] key so that Yes changes to No. 8. Once it says No, press the [Stop] key. 9. Unit will show “Display Acc Pressure.” 10. Press the [Stop] key again to exit. 39 Diagnostics 34788 Service Manual SERVICE CENTER MENU OPTIONS These are the Service Options at the time of printing this service manual. Some options may be added or deleted in future circuit board and software updates and revisions. Never change the default settings unless directed from the factory. Otherwise the unit may fail to operate properly. Never give the programming or service codes to customers. Service Menu At the time of writing this manual, the software version of the control board was 1.054 and the relay board was 1.006. Software and functions are subject to change without notice. To access the Change Defaults menu, turn ON unit and press the [MENU] button. Use the UP or DOWN arrow keys to scroll through the menu choices until “SERVICE MENU” is displayed. Press [2-2-0-0] on the keypad, then press [START] to enter Service Menu. Use the arrow keys to scroll through the Service Menu choices. To reset the highlighted item, press [7-6-9-1] on the keypad, then press [START]. Set UL — Follow the on-screen instructions to set the UL circuit. For the Worthington ISV, you should have 43-lb. and 2-lb. weights to perform UL calibration; for the Aircom ISV, you should have 45-lb. and 2-lb. weights. Pot adjustment is not required on this unit. Service Vacuum — This routine allows the service center to have the machine pull a vacuum on the entire circuit. Service Leak Check — Unit is pressurized and tested for leaks. Output Step Test — Sends power to the item listed on the display. (See Output Step Test on next page.) Menu Choices Keypad Test — Will run the operator through an process where every button on the keypad will be tested. Maintenance Count — This routine allows a service center to display and/or reset any of the service counters. Board Test — Production use only. Cal Tank Scale — Follow the on-screen instructions to re-calibrate the scale. Reset Board — This function will reset all board parameters and force re-calibration. Production Tests — Production use only. Display Pressure — Displays the low-side, ISV, and accumulator pressures. Air Purge Info — Displays the tank pressure, tank temperature, and calculated tank PSI. Prepare to Ship — Sets boot mode to first time customer power-on. When the unit is turned back on, the user will have to set language, operating units, date & time, clear unit, and perform an initial tank fill. Set Tank Tare — Aircom ISV = 20.50 lbs (9.30 kg), Worthington ISV = 17.50 lbs (7.94 kg.) Display Acc Pressure — Allows the accumulator pressure to be displayed on-screen. 40 Diagnostics 34788 Service Manual OUTPUT STEP TEST Refer to the 12VDC solenoid test procedure on page-43 to check solenoid operation during the output tests. The output test will turn on or turn off power to the specified component. Do not perform any test for an extended time period. 2. Press [2-2-0-0] on the keypad, then press [START] to enter Service Menu. 3. Use the UP or DOWN arrow keys to scroll through the menu choices until “OUTPUT TEST” is displayed. Press [START/YES] to enter. 1. To access the Output Test, turn ON unit and press the [MENU] button. Use the UP or DOWN arrow keys to scroll through the menu choices until “SERVICE MENU” is displayed. OUTPUTS – Use the UP or DOWN arrow keys to select the component, then press the [START/ YES] button to toggle power ON or OFF. OUTPUT STEP TEST Component Order Energized Component 1 High-Side Inlet Solenoid 2 Low-Side Inlet Solenoid 3 High-Side Charge Solenoid 4 Low-Side Charge Solenoid 5 High-Side Inject Solenoid 6 Deep Recover Solenoid 7 Vacuum Solenoid 8 Recover Solenoid 9 Tank Fill Solenoid 10 Oil Drain Solenoid 11 Oil Return Solenoid 12 Power/Charge Solenoid 13 Normal Discharge Solenoid 14 HS Clear Solenoid 15 Air Purge Solenoid 16 Compressor 17 Vacuum Pump 18 Fan 41 Diagnostics 34788 Service Manual DEPRESSURIZING THE UNIT Always wear safety goggles when working with refrigerants. Contact with refrigerant can cause eye injury. Disconnect lines and hoses with extreme caution! Pressurized refrigerant may be present in lines and hoses. Always point lines and hoses away from you and anyone nearby. Always unplug the station from the power source before removing any of the shrouding or beginning any service work. Unit is Functional 1. Perform Recovery function. Unit is NOT Functional 2. Close Liquid valve on ISV. 1. Disconnect the high and low side service hoses from vehicle. Make sure the coupler valves are closed. 3. Turn unit off when oil drain error is displayed. 2. Disconnect the fill hose from the source tank. 4. The only refrigerant present may be in the vapor hose between the ISV and manifold block. 3. Open the unit door and close the (3) ISV valves. 4. Connect an auxiliary recovery unit up to the manifold service port. 5. Start up the separate recovery unit and allow it to pull the unit into a 13” vacuum. 6. When the unit is pulled down to this level, turn off the auxiliary recovery unit, and disconnect from the manifold service port. 7. Carefully disconnect or remove components as there may be refrigerant present at these fittings. 42 Diagnostics 34788 Service Manual 12VDC SOLENOID TEST PROCEDURE The solenoids that are used in the 34788 unit cannot be tested using the P/N 17012 magnetic solenoid tester. The solenoids in this unit are activated from a 12VDC power source and have a duty cycle of 25%. Duty Cycle is the ratio of solenoid on-time to total cycle time. In this particular scenario, the solenoid is on 25% (250μs) of the total cycle and off for 75% (750μs) of the cycle. When the solenoid is ‘first’ activated, it receives a 12VDC, 125ms pulse to energize (turn on) the solenoid coil. The solenoid is then cycled on and off rapidly at a 50ms, 25% duty cycle. Although the power to the solenoid is cycling ON and OFF, the solenoid actually sustains the “ON” state because the cycling process is happening so quickly, the solenoid doesn’t have time to turn off until the power is completely removed. Using this process to power the solenoids requires less power and increases the component’s life expectancy. The best way to verify solenoid operation is to use an oscilloscope. Viewing the solenoid’s duty cycle pattern on the oscilloscope will provide the best information on how the solenoid coil is performing. Set oscilloscope to DC mode. Set the time to .2 ms/div and voltage range to 5 volts/div. Attach the scope probe to an energized solenoid. The pattern on the oscilloscope should look similar to the sample below with amplitude of 12V. If the amplitude is not 12V, check the power supply. If the pattern is irregular or doesn’t compare to the sample below, replace the solenoid coil. If an oscilloscope is not available, a digital volt meter may be used to check power applied to the solenoid. However, do NOT expect to see 12VDC on the DVM. Because most DVM’s use RMS to read voltages, the meter will read an average voltage of 2.8 VDC due to the continuous 25% on, 75% off cycling of the solenoid. An LED light may also be used to verify that a solenoid is receiving power. Attach the leads of the 12VDC LED light across the solenoid terminals. While watching the LED, activate the solenoid from the service menu. The LED should turn-on bright for a moment (initial 12VDC, 125ms activation pulse), then dim considerably when the 25% duty cycle begins. 1 Complete Cycle Sustain Pulse, 25% Duty Cycle, 1kHz Cycle (low part of pattern is “On” time) 12V 750µs 75% 750µs 25% 250µs 125ms Activation Pulse (not to scale) Off 250µs On 25% Duty Cycle 43 Diagnostics 34788 Service Manual TROUBLESHOOTING Will Not Power-Up, No Display 1. Verify that unit is not plugged into an extension cord. If it is, remove extension cord. 2. Verify AC power cord is properly connected to a good AC power source at receptacle. Verify that it is wired correctly and has a good ground. 3. Turn ON the main power switch. Verify that line voltage is present at the input and output terminals of the switch. • If line voltage is not present at power switch input, check connections between power switch and AC plug. • If line voltage is present at power switch input, but not at output with switch turned ON, replace power switch. • If line voltage is present at both input and output of switch, proceed to next step. 4. Verify line voltage is present across pins 2 and 3 of connector J1 on the relay board. • If line voltage is present, proceed to next step. • If line voltage is not present, check connections between the power switch and connector J1. 5. If unit does not power up, check if the 15A circuit breaker (located on back of unit) has tripped. 15A Breaker Not Tripped 1. Switch off unit and unplug AC power cord from receptacle. 2. Check the 15A breaker for continuity. • If there is no continuity, replace circuit breaker. • If there is continuity, plug the AC power cord into the receptacle and switch unit on. Continue to next step. 44 3. Perform the following voltage checks: • Verify line voltage is present across pins 3 and 4 of connector J3 on the relay board. • If line voltage is not present, check for continuity between the 15A circuit breaker and J3 on the relay board. Repair as needed. • If line voltage is present, replace the relay board. 4. If all the proceeding steps fail to repair the problem, replace the display/control board. 15A Breaker Tripped 1. Switch off unit and reset circuit breaker. Switch unit back on. If breaker trips after reset and AC power has been tested good, the circuit breaker needs to be replaced. 2. If breaker trips again after being replaced, switch off unit and unplug all connectors on the relay board except J1 (AC In) and J3 (Circuit Breaker). Switch unit back on. • If circuit breaker trips again, replace relay board. • If the circuit breaker doesn’t trip, turn off power, plug-in one connector at a time, and turn back on. Keep doing this until the circuit breaker trips. Check all components associated with the last connector attached to the relay board. 34788 Service Manual Diagnostics Will Not Tank Fill Compressor Running: 1. Check for proper power source, check circuit breakers and check electrical connectors for damage or corrosion. 2. If the unit is being run through an extension cord, eliminate its use. 10. Check the compressor for suction and discharge performance. 11. Remove the filter and inspect all fittings and gaskets to verify that no obstructions exist. Replace/ repair gaskets as needed and reinstall filter. 12. Verify that the scale is unobstructed and calibrated. 3. Verify the tank hoses are properly connected and threaded completely onto the ISV fittings. 4. Verify the ISV is not full or does not have excessive pressure. If excess pressure cannot be reduced with purging air, the refrigerant may be contaminated and should be handled appropriately. 5. Verify the fill hose is properly connected and threaded completely onto the source tank fitting. Check quick-seal on tank fill hose. 6. Verify that there is a minimum of 8 pounds (3.6 kilograms) of refrigerant in the source tank. 7. Verify the Tank Fill and Normal Discharge solenoids are receiving power and opening properly. • If not receiving power, check the continuity of the wiring between solenoid and relay board— repair as needed. • If the wiring is correct and no power is being applied to the solenoid, replace the relay board. • Verify the solenoid coil is opening the solenoid properly. • Verify the operation of the Tank Fill check valve—replace as needed. The Tank Fill solenoid is controlled to maintain 35 psi in the accumulator. 8. Check the Power Charge, Recover, Oil Return, Oil Drain, Deep Recover, and High-Side Clear solenoids for bleed-through—repair as needed. Compressor does not run: 1. Check for proper power source, check circuit breaker and check electrical connectors for damage or corrosion. 2. If the unit is being run through an extension cord, eliminate its use. 3. Verify that the ground wire between the compressor’s electrical box and chassis ground is securely fastened. 4. Check for 110 volts to the compressor. • If there is no voltage to the compressor’s start components, proceed to next step. • If voltage is present at the compressor, jumper the thermal overload. If the compressor runs, check the compressor amp draw. If it is drawing locked rotor amps or not running, replace the compressor. If the compressor is cool and drawing low amperage, replace the thermal overload. 5. Check for 110 volts from the relay board on connector J6, pins 3 and 4. • If voltage is present, check wiring between the relay board and the compressor’s start components. Repair as needed. • If voltage is not present, replace the relay board. • If after replacing the relay board, voltage is still not present, replace the display/control board. 6. Perform functional check and recalibrate unit. 9. Check the Clearing Discharge check valve for bleed-through—repair as needed. 45 Diagnostics 34788 Service Manual Will Not Recover (First Stage) Compressor running: 1. Check for proper power source, check circuit breakers and check electrical connectors for damage or corrosion. 2. Verify the service hoses are properly attached to the unit without any restrictions and coupler valves are open. 3. Verify that ISV valves are open and tank hoses are properly connected and threaded completely onto the ISV fittings. 4. Verify the ISV is not full or does not have excessive pressure. If excess pressure cannot be reduced with purging air, the refrigerant may be contaminated and should be handled appropriately. 5. Verify that the Normal Discharge, Recover, HighSide Inlet and Low-Side Inlet solenoids are receiving power and opening properly. • If not receiving power, check the continuity of the wiring between solenoid and relay board— repair as needed. • If the wiring is correct and no power is being applied to the solenoid, replace the relay board. • Verify the solenoid coil is opening the solenoid properly. The Recover solenoid is controlled to maintain 35 psi max in the accumulator. 6. Check the High-Side Charge, Low-Side Charge, Oil Inject, Oil Return, Vacuum, High-Side Clear, Tank Fill, and Power Charge solenoids for bleedthrough and proper operation —repair as needed. 7. Check the compressor for suction and discharge performance. 46 8. Remove the filter and inspect all fittings and gaskets to verify that no obstructions exist. Replace/ repair gaskets as needed and reinstall filter. 9. Verify that the accumulator transducer is functioning properly. 10. If all the proceeding steps fail to repair the problem, replace the display/control board. Compressor does not run: 1. Check for proper power source, check circuit breaker and check electrical connectors for damage or corrosion. 2. If the unit is being run through an extension cord, eliminate its use. 3. Verify that the ground wire between the compressor’s electrical box and chassis ground is securely fastened. 4. Check for 110 volts to the compressor. • If there is no voltage to the compressor’s start components, proceed to next step. • If voltage is present at the compressor, jumper the thermal overload. If the compressor runs, check the compressor amp draw. If it is drawing locked rotor amps or not running, replace the compressor. If the compressor is cool and drawing low amperage, replace the thermal overload. 5. Check for 110 volts from the relay board on connector J6, pins 3 and 4. • If voltage is present, check wiring between the relay board and the compressor’s start components. Repair as needed. • If voltage is not present, replace the relay board. • If after replacing the relay board, voltage is still not present, replace the display/control board. Diagnostics 34788 Service Manual Will Not Deep Recover (Second Stage) Vacuum pump running: 1. Check for proper power source, check circuit breakers and check electrical connectors for damage or corrosion. 2. If the unit is being run through an extension cord, eliminate its use. 3. Verify the service hoses are properly attached to the unit without any restrictions and coupler valves are open. 8. Check the Clearing Discharge checkvalve for bleed-through—repair as needed. 9. Check for suction at the intake of the pump. If there is none, replace the pump. 10. Remove the filter and inspect all fittings and gaskets to verify that no obstructions exist. Replace/ repair gaskets as needed and reinstall filter. 11. Verify that the accumulator transducer is functioning properly. 4. Verify that ISV valves are open and tank hoses are properly connected and threaded completely onto the ISV fittings. 12. If all the proceeding steps fail to repair the problem, replace the display/control board. 5. Verify the ISV is not full or does not have excessive pressure. If excess pressure cannot be reduced with purging air, the refrigerant may be contaminated and should be handled appropriately. Vacuum pump does not run: 1. Check for proper power source, check circuit breaker and check electrical connectors for damage or corrosion. 6. Verify that the Normal Discharge, High-Side Inlet, Low-Side Inlet, Vacuum, Deep Recover, and Power Charge (see note) solenoids are receiving power and opening properly. • If not receiving power, check the continuity of the wiring between solenoid and relay board— repair as needed. • If the wiring is correct and no power is being applied to the solenoid, replace the relay board. • Verify the solenoid coil is opening the solenoid properly. 2. If the unit is being run through an extension cord, eliminate its use. The Power Charge solenoid is controlled to maintain 0 to 3 psi in the accumulator. 7. Check the High-Side Charge, Low-Side Charge, Oil Inject, Oil Return, Recover, Tank Fill and High-Side Clear solenoids for bleed-through and proper operation—repair as needed. 3. Check for 110V at the vacuum pump connector, pins 2 and 3. • If voltage is present, replace vacuum pump assembly. • If voltage is not present, continue to next step. 4. Check for 110 volts from the relay board on connector J6, pins 1 and 2. • If voltage is present, check wiring between the relay board and the vacuum pump. Repair as needed. • If voltage is not present, replace the relay board. • If after replacing the relay board, voltage is still not present, replace the display/control board. 5. Perform functional check and recalibrate unit. 47 Diagnostics 34788 Service Manual Will Not Perform Clearing Compressor Running: 1. Check for proper power source, check circuit breakers and check electrical connectors for damage or corrosion. 2. If the unit is being run through an extension cord, eliminate its use. 9. Remove the filter and inspect all fittings and gaskets to verify that no obstructions exist. Replace/ repair gaskets as needed and reinstall filter. 10. If all the proceeding steps fail to repair the problem, replace the display/control board. 3. Verify the tank hoses are properly connected and threaded completely onto the ISV fittings. Compressor does not run: 1. Check for proper power source, check circuit breaker and check electrical connectors for damage or corrosion. 4. Verify the ISV is not full or does not have excessive pressure. If excess pressure cannot be reduced with purging air, the refrigerant may be contaminated and should be handled appropriately. 2. If the unit is being run through an extension cord, eliminate its use. 5. Verify the Normal Discharge, HS Clear, and Oil Return solenoids are receiving power and opening properly. • If not receiving power, check the continuity of the wiring between solenoid and relay board— repair as needed. • If the wiring is correct and no power is being applied to the solenoid, replace the relay board. • Verify the solenoid coil is opening the solenoid properly. • Verify the operation of the Tank Fill check valve—replace as needed. 6. Check the Power Charge, Recover, Oil Drain, Deep Recover, and Tank Fill solenoids for bleedthrough—repair as needed. 7. Check the Normal Discharge check valve for bleed-through—repair as needed. 8. Check the compressor for suction and discharge performance. 3. Verify that the ground wire between the compressor’s electrical box and chassis ground is securely fastened. 4. Check for 110 volts to the compressor. • If there is no voltage to the compressor’s start components, proceed to next step. • If voltage is present at the compressor, jumper the thermal overload. If the compressor runs, check the compressor amp draw. If it is drawing locked rotor amps or not running, replace the compressor. If the compressor is cool and drawing low amperage, replace the thermal overload. 5. Check for 110 volts from the relay board on connector J6, pins 3 and 4. • If voltage is present, check wiring between the relay board and the compressor’s start components. Repair as needed. • If voltage is not present, replace the relay board. • If after replacing the relay board, voltage is still not present, replace the display/control board. 6. Perform functional check and recalibrate unit. 48 34788 Service Manual Will Not Air Purge 1. Check for proper power source, check circuit breakers and check electrical connectors for damage or corrosion. 2. If the unit is being run through an extension cord, eliminate its use. 3. Check the 0.028” orifice between the ISV and air purge solenoid for debris. • If the orifice is contaminated or defective, repair or replace as needed. • If the orifice is operational, proceed to the next step. 4. Verify the Air Purge solenoid is receiving power and opening properly. • If not receiving power, check the continuity of the wiring between solenoid and relay board— repair as needed. • If the wiring is correct and no power is being applied to the solenoid, replace the relay board. • Verify the solenoid coil is opening the solenoid properly. 5. Verify that the tank temperature probe and pressure transducer are functioning properly. Diagnostics Will Not Drain Oil For dye usage, please refer to Limited Warranty Statement. 1. Check for proper power source, check circuit breakers and check electrical connectors for damage or corrosion. 2. If the unit is being run through an extension cord, eliminate its use. 3. Verify the Oil Drain solenoid is receiving power and opening properly. • If not receiving power, check the continuity of the wiring between solenoid and relay board— repair as needed. • If the wiring is correct and no power is being applied to the solenoid, replace the relay board. • Verify the solenoid coil is opening the solenoid properly. 4. Verify that the accumulator transducer is functioning properly. 5. If the proceeding steps fail to repair the problem, replace the display/control board. 6. If the proceeding steps fail to repair the problem, replace the display/control board. 49 Diagnostics 34788 Service Manual Will Not Evacuate (Vacuum) Vacuum pump running: 1. Check for proper power source, check circuit breakers and check electrical connectors for damage or corrosion. 9. Check plumbing between vacuum pump and service hoses for loose connections or fittings. 10. Replace vacuum pump. 2. If the unit is being run through an extension cord, eliminate its use. 11. If all the proceeding steps fail to repair the problem, replace the display/control board. 3. Verify the service hoses are properly attached to the unit (valves open) without any restrictions. Vacuum pump does not run: 1. Check for proper power source, check circuit breaker and check electrical connectors for damage or corrosion. 4. Be sure the two plastic vacuum lines are snug at both ends and not obstructed. Check the pneumatic fittings for leaks. 5. Check for proper vacuum oil level in the vacuum pump sight glass (oil level should be in the center of the sight glass while the pump is running). Replace vacuum pump oil if necessary. 6. Check for suction at the intake of the pump. If there is none, replace the pump. 7. Verify that the Vacuum, Low-Side Inlet and HighSide Inlet solenoids are receiving power and opening properly. • If not receiving power, check continuity of the wiring between the solenoid and relay board— repair as needed. • If the wiring is correct and no power is being applied to the solenoid, replace the relay board. • Verify the solenoid coil is opening the solenoid properly. 8. Check the High-Side Charge, Low-Side Charge, Oil Inject, Recover, and Deep Recover solenoids for bleed-through and proper operation—repair as needed. 50 2. If the unit is being run through an extension cord, eliminate its use. 3. Check for 110V at the vacuum pump connector, pins 2 and 3. • If voltage is present, replace vacuum pump assembly. • If voltage is not present, continue to next step. 4. Check for 110 volts from the relay board on connector J6, pins 1 and 2. • If voltage is present, check wiring between the relay board and the vacuum pump. Repair as needed. • If voltage is not present, replace the relay board. • If after replacing the relay board, voltage is still not present, replace the display/control board. 5. Perform functional check and recalibrate unit. Refer to vacuum pump service bulletin. 34788 Service Manual Fails Leak Test Diagnostics Will Not Inject Oil 1. Check for proper power source, check circuit breakers and check electrical connectors for damage or corrosion. 1. Check for proper power source, check circuit breakers and check electrical connectors for damage or corrosion. 2. If the unit is being run through an extension cord, eliminate its use. 2. If the unit is being run through an extension cord, eliminate its use. 3. Verify that the High-Side and Low Side Inlet solenoids are receiving power and opening properly. • If not receiving power, check continuity of the wiring between the solenoid and relay board— repair as needed. • If the wiring is correct and no power is being applied to the solenoid, replace the relay board. • Verify the solenoid coil is opening the solenoid properly. 3. Verify the high-side service hose is properly attached to the unit without any restrictions and coupler valve is open. 4. Check the High-Side Charge, Low-Side Charge, Oil Inject, Recover, and Vacuum solenoids for bleed-through—repair as needed. 5. Verify that the low-side pressure transducer is functioning properly. 6. If vacuum can not be maintained, use a refrigerant detector to check all plumbing hoses and fittings for leaks—repair as needed. Refer to the Leak Test flow diagram illustrated in the Flow Charts section. 7. If all the proceeding steps fail to repair the problem, replace the display/control board. 4. Verify a deep vacuum has been pulled on the system. 5. Verify the oil injector bottle is securely attached and contains an appropriate amount of oil. 6. Verify the Oil Inject solenoid is receiving power and opening properly when the Oil Inject Button is pressed on the keyboard. • If not receiving power, check the continuity of the wiring between solenoid and relay board— repair as needed. • If the wiring is correct and no power is being applied to the solenoid, replace the relay board. • Verify the solenoid coil is opening the solenoid properly. 7. Check the High-Side Inlet and High-Side Charge solenoids for bleed-through—repair as needed. 8. If the proceeding steps fail to repair the problem, replace the display/control board. 51 Diagnostics 34788 Service Manual Will Not Charge There is no component that "pumps" refrigerant into a system during the charge process. The refrigerant flows in by a pressure transfer. If the system is not in a vacuum, this unit will not charge. 1. Check for proper power source, check circuit breakers and check electrical connectors for damage or corrosion. 2. If the unit is being run through an extension cord, eliminate its use. 3. Verify the service hoses are properly attached to the unit without any restrictions and coupler valves are open. 4. Verify a deep vacuum has been pulled on the system being charged. 5. Check that all ISV hoses are properly installed and valves are open. Also verify that the scale is unobstructed. 6. If “INSUFFICIENT REFRIG AVAILABLE” is on the display, verify that there is a minimum of 8 pounds (3.6 kilograms) of refrigerant in the tank. If there is enough refrigerant in the tank check scale calibration and re-calibrate. 7. Verify that the control module has accepted the programmed amount. Test the operation of the keypad; replace if necessary. 8. Verify the Low-Side Charge and/or High-Side Charge solenoids (depending on user input) are receiving power and opening properly. • If not receiving power, check the continuity of the wiring between solenoid and relay board— repair as needed. • If the wiring is correct and no power is being applied to the solenoid, replace the relay board. • Verify the solenoid coil is opening the solenoid properly. 9. Check the Low-Side Inlet, High-Side Inlet, Oil Inject, and Power Charge solenoids for bleedthrough and proper operation—repair as needed. If the unit does not complete a full charge, the compressor, power charge and high-side clear solenoids are activated, then stop to build tank pressure. 10. If the proceeding steps fail to repair the problem, replace the display/control board. Slow Charge: 1. Check and ensure that there is a good vacuum in the vehicle being tested. 2. Verify that there is sufficient pressure in ISV to transfer refrigerant. 3. Ensure chargeable weight is greater than desired charge. 4. Verify the charge couplers are completely open and the vehicle ports are actuated. 5. Check for debris in any of the charging circuit solenoids. Clean or replace if necessary. 52 34788 Service Manual Diagnostics Miscellaneous Error Messages Low Recover Pressure, Check Connections During the recovery process, the unit is seeing less than 10 psi at the Low-Side Pressure Transducer. Verify all connections before continuing. Out of Range Error When entering the “tank fill level” amount during setup, you must enter a value between 4-20 lbs. If the value entered is outside this range, this error message will be displayed. Pressure too High for Vacuum If this message occurs during the evacuation process, the unit is seeing greater than 10 psi at the Low-Side Pressure Transducer. Perform recovery before continuing. If this message occurs during the clearing process, the unit is seeing greater than 10 psi at “any” pressure transducer. Insufficient Refrigerant Available The entered charge amount is greater than the amount in the ISV. Add additional refrigerant to the tank. Insufficient Refrigerant for Flush There is less than 10 lbs. of refrigerant in ISV. To perform the flush routine, there must be more than 10 lbs. of refrigerant available in the tank. Add refrigerant. Insufficient ISV Pressure for Test There is less than 50 psi of pressure in the ISV. To perform the leak test routine, the tank pressure must be higher than 50 psi. Calibration Error/Calibration Rejected When the calibration check is performed, the unit measures the scale weight before and after the calibration weight has been attached to the scale. If the difference in weight is 1.18 ± 0.03 lbs., the calibration check will pass. However, if the difference is anything else, the Calibration Error/Calibration Rejected message will be displayed. UL Cal Error, Check Cal Weight UL calibration failure has occurred. Verify that scale is unobstructed and calibration weight is 43 lbs. for Worthington ISV, or 45 lbs. for the Aircom ISV. Scale or control board not responding correctly. Serial Number Error The 10-digit serial number for the filter was entered incorrectly. Re-enter serial number. ISV Pressure Error L The ISV Pressure Transducer is reading tank pressure less than 30.54 inHg. ISV Pressure Error H The ISV Pressure Transducer is reading tank pressure greater than 460 PSI. LS Pressure Error L The Low-Side Pressure Transducer is reading low-side pressure less than 30.54 inHg. LS Pressure Error H The Low-Side Pressure Transducer is reading low-side pressure greater than 140 PSI. ACC Pressure Error L The ACC Pressure Transducer is reading accumulator pressure less than 30.54 inHg. ACC Pressure Error H The ACC Pressure Transducer is reading accumulator pressure greater than 140 PSI. ISV Temp Probe Error / Air Purge Not Working The ISV Temperature Probe is reading tank temperature that is either too low (less than 40° F) or too high (greater than 200° F). Check tank pressure and air purge functions. 53 Diagnostics 34788 Service Manual SERVICE INSTRUCTIONS & CALIBRATION Replacement Compressor (RA20020) Specifications & Service Specifications Compressor Fittings Make: Voltage: Capacity (BTU/HR): Running Amps: Speed: Locked Rotor Amps: Oil Charge Capacity: Refrigerants: POE Oil Type: Weight w/oil: Replacements: 1/3 HP Cubigel 115V / 60Hz 5821 8.4A 3500 RPM 30.0A Initial - 13.5 oz Recharge - 11.8 oz R-12, 22, 500, 502, 134a 404a ISO 22 23.8 lbs. 110V - RA20020 Oil Return (Intake) Suction Discharge Adding Oil to Compressor Troubleshooting Compressor Due to the configuration of the Cubigel suction and discharge fittings, there is no easy method of checking or removing oil from the compressor. Compressor Will Not Run The following procedure is the recommended method for changing oil in the Cubigel compressor: 1. Connect a refrigerant supply tank to one of the compressor’s suction ports. 2. Connect a portable recovery unit to the other suction port. 3. Cap the discharge port on the compressor. 4. Run the recovery unit to completely flush all oil from the compressor. 5. Disconnect everything and add 13.5 oz. of new oil (ISO 22) to the compressor. 54 1. Check for proper power source, check circuit breaker and check electrical connectors for damage or corrosion. 2. If the unit is being run through an extension cord, eliminate its use. 3. Verify that the ground wire between the compressor’s electrical box and chassis ground is securely fastened. 4. Check for 110 volts to the compressor. • If there is no voltage to the compressor’s start components, proceed to next step. • If voltage is present at the compressor, jumper the thermal overload. If the compressor runs, check the compressor amp draw. If it is drawing locked rotor amps or not running, replace the compressor. If the compressor is cool and 34788 Service Manual drawing low amperage, replace the thermal overload. 5. Check for 110 volts from the relay board on connector J6, pins 3 and 4. • If voltage is present, check wiring between the relay board and the compressor’s start components. Repair as needed. • If voltage is not present, replace the relay board. • If after replacing the relay board, voltage is still not present, replace the display/control board. Diagnostics 6. Shut off the compressor. The suction and discharge values should hold for 30 seconds to one minute. If not, proceed to step-7, then repeat test. If no improvement, replace the compressor. 7. If the compressor has weak suction or discharge, check the oil level and add oil if necessary. If the oil level is okay or oil was added with no improvement, replace the compressor. Removing the Compressor 1. Disconnect the unit from its power source. 6. Perform functional check and recalibrate unit. 2. Remove the unit’s door and front panel. Suction and Discharge Pressure Test 3. Depressurize the unit. 1. Disconnect all fittings from the compressor. 4. Disconnect the copper line from the compressor. 2. Cap the intake fitting. 5. Disconnect the two black tubes from the compressor. 3. Install a low side gauge on the suction fitting. The fitting used on the suction port is a 3/8” compression fitting. Use the appropriate fitting with an R-134a manifold set. 4. Install a high pressure gauge on the discharge fitting. The fittings used on the discharge port require an o-ring fitting to seal. Use a 120063 hose (1/4” flare o-ring X 1/2” ACME Q.S.) with an R-134a manifold set. 5. Start the compressor and monitor the readings. The discharge pressure should build to 250 psi (17.24 bar). The compressor should pull a 25” (.85 bar) vacuum. 6. Remove and save the four nuts and bolts that secure the compressor into the unit. 7. Disconnect the wires from the main wire harness. 8. Remove the compressor from the unit. 9. Remove the compressor electrical box cover by releasing the spring clamp that holds it on. 10. Disconnect the wires from the electrical components. Capacitor may still be energized, so remove wires with caution. 11. Disconnect the two black tubes from the main block, and discard. 55 Diagnostics 34788 Service Manual Replacement Compressor (RA20020) Specifications & Service (continued) Installing the Replacement Compressor (Refer to Figures 1 & 2 during this installation) RETAINER COMP. ELEC. BOX 1. Install the four rubber mounts (included in kit) into the base of the compressor. PROTECTOR RELAY 2. Install the electrical components. 3. Connect wiring to the compressor electrical components as shown in Figure 1. SCREW CAPACITOR LEADS 4. Install the compressor electrical box cover, and secure with the existing spring clamp. CAPACITOR 5. Place the compressor into the unit. Figure 1 – Compressor Wiring 6. Place one steel sleeve (included in kit) into each of the four rubber mounts in the base of the compressor. Manifold Assembly 7. Secure the compressor into place with the existing four nuts and bolts. 8. Reconnect the compressor to the wire harness. 15” 9. With the o-rings in place, connect the copper line to the discharge side of the unit. 10. Refer to Figure 2 and replace the two black tubes that connect the compressor to the main block (use tubing from kit RA20005 and ferrules from kit RA20006). 11. Plug unit into power source, perform a function test, and check for any leaks. 12. Replace the shrouding. 12” Compressor 538469 2X 105358 Use Loctite® 242 or equivalent on threads Figure 2 – Compressor Tubing Connections 56 Diagnostics 34788 Service Manual Replacement Vacuum Pump (RA20017) Specifications & Service Specifications 1/3 HP VacuMaster® Pump 110V 60Hz 4.5 A Call Tech Support 3 cfm 7.4 oz - 219 ml Premium Vacuum Pump Oil Make: Volts: Frequency: Running Amps: Locked Rotor Amps: Flow Rate: Oil Capacity: Oil Type: Vacuum Pump Not Running 1. Check for proper power source, check circuit breaker and check electrical connectors for damage or corrosion. 2. If the unit is being run through an extension cord, eliminate its use. 3. Check for 110V at the vacuum pump connector, pins 2 and 3 (see figure below). • If voltage is present, replace vacuum pump assembly. • If voltage is not present, continue to next step. 4. Check for 110 volts from the relay board on connector J6, pins 1 and 2. • If voltage is present, check wiring between the relay board and the vacuum pump. Repair as needed. • If voltage is not present, replace the relay board. • If after replacing the relay board, voltage is still not present, replace the display/control board. 5. Perform functional check and recalibrate unit. Removing the Vacuum Pump 1. Disconnect the unit from its power source. 2. Remove the unit’s door and front panel. 3. Install and secure the hood spacers. 4. Depressurize the unit. 5. Remove the two existing nylon lines from the vacuum pump. 6. Remove and save the bolts that fasten the vacuum pump to the unit. 7. Disconnect the vacuum pump connector from the main harness. 8. Remove the vacuum pump from the unit. Installing the Replacement Vacuum Pump 1. Insert the new vacuum pump into the unit. 2. Secure the vacuum pump to the unit with the bolts saved from the old pump. 3. Connect the electrical connector from the vacuum pump into the unit’s main harness. 4. Reconnect the two existing nylon lines. 5. Remove the brass plug from the vacuum pump oil fill port. 6. Add 5 oz. of oil to the vacuum pump. 7. Plug unit into power source, and perform the steps to start the vacuum pump. 8. While the vacuum pump is running, add more oil to the correct fill level in the sight gauge. 9. Replace the brass plug in the fill port. 10. Perform a function test, and check for any leaks. 11. Replace the shrouding, and remove the hood spacers. BLACK HOT NEUT GND WHITE FILL PORT GREEN Vacuum Pump Assembly 57 Diagnostics 34788 Service Manual Replacement High Pressure Cut-Out Switch (RA19427) Unplug the station before beginning service work. Incorrect use or connections can cause electrical shock. Wear safety goggles when working with refrigerants. Refrigerants can cause eye injury. Disconnect hoses using extreme caution! Pressurized refrigerant may be present in hoses. Point hoses away from you and anyone nearby. The high pressure cut-out is a normally closed sensor designed to shut off the unit if the discharge pressure reaches 435 ± 10 psi. The switch will reset and close at 320 ± 20 psi. The pressure is detected through an orifice in the base of the sensor. In the normal setting (less than 435 psi on the orifice), the 1 and 3 contacts are closed. When 435 psi is introduced to the orifice, the pressure forces up on the drive pin, which then forces the center contact to disengage the 1 and 3 contacts and engage the 1 and 2 contacts. When this happens, the unit halts operation and displays a high pressure warning on the display. Brown Wire Brown Wire Replacement Instructions Follow these steps to replace the high pressure cut-out switch on your unit. 1. Close the tank valves and depressurize the unit. 2. Turn off the MAIN POWER switch, and unplug the unit from the power source. 3. Remove the panel(s) or shroud to access the manifold block. 4. Disconnect the wires from the high pressure cutout switch. 5. Carefully remove the high pressure cut-out switch. 6. Clean the fitting by wiping away dirt, grease, and oil. Apply thread sealant to only the external pipe threads of the fittings. DO NOT apply thread sealant to any internal threads. Thread sealant contains ADHHM-128 anaerobic adhesive and methacrylic ester. If there is skin contact with the sealant, thoroughly was the skin with soap and water. 7. 8. 9. 10. 11. 12. Install the new high pressure cut-out switch. Reconnect the wires to the new switch. Plug the unit into the power source. Open the tank valves. Operate the unit and check for leaks. Replace the panel(s) or shroud. Troubleshooting the High Pressure Cut-Out High Pressure Cut-Out discontinues operation prematurely. 1. Verify that there are no discharge obstructions. 2. Replace the high pressure cut-out. High Pressure Cut-Out Switch 58 High Pressure CutOut does not discontinue operation of unit at or below designed pressure. 1. Check the wiring. 2. Replace the high pressure cut-out. 34788 Service Manual Diagnostics Replacement Scale Assembly/Magnet (RA20002) Unplug the station before beginning service work. Incorrect use or connections can cause electrical shock. Wear safety goggles when working with refrigerants. Refrigerants can cause eye injury. Disconnect hoses using extreme caution! Pressurized refrigerant may be present in hoses. Point hoses away from you and anyone nearby. If scale assembly and UL circuit are not calibrated, scale can overfill the tank, causing possible explosion and/or vehicle overcharge. Instructions These instructions outline the steps to replace the scale assembly. Removing the Scale Assembly 1. Disconnect the unit from its power source. 2. Remove the unit’s door and front panel. 3. Install and secure the hood spacers. 4. Close all three (3) tank valves. 5. Depressurize the unit. 6. Disconnect the liquid hose and vapor hose from the tank. 7. Disconnect the wires from the air purge solenoid, tank temperature probe, and pressure transducer. 8. Remove the two (2) bolts that secure the tank to the scale. 9. Remove the tank from the scale. 10. Remove the four (4) nuts that hold the scale in place. 11. Remove the ground wire connected to the center divider of the unit and the harness connected to the relay board. Installing the Replacement Scale Assembly 1. Connect the ground wire from the scale to the center divider. 2. Install the scale into the unit and secure with four (4) nuts. 3. Thread wire through the center panel, and connect to the relay board. 4. Connect the unit to its power source. 5. Turn the unit on to begin calibration steps. 6. Press the MENU key. 7. Press the DOWN arrow twice to SERVICE MENU. 8. Press 2-2-0-0. 9. Press the START key. 10. Press the UP arrow twice to CALIBRATE TANK SCALE. 11. Press the START key, and verify there is no weight on the scale or anything interfering with the scale. 12. Press the START key. 13. Place 20 pounds on the scale when prompted; then, press START. 14. Press the UP arrow to UL CALIBRATION. 15. Press the START key. 16. Place 43 pounds on the scale if using a Worthington tank, or 45 pounds if using an Aircom tank. 17. Press the START key. 18. Wait while the unit calibrates the UL circuit and stops. 19. Remove 2 pounds when the unit prompts you. 20. When the unit shows UL CALIBRATION COMPLETE, press the STOP key twice. 21. Install the tank on the scale, and secure with two (2) bolts. 22. Reconnect the air purge solenoid, tank temperature probe, and pressure transducer wires. 23. Reconnect the liquid hose and vapor hose to the tank. 24. Open all three (3) tank valves. 25. Perform a function test, and check for leaks. 26. Remove the hood spacers, and replace the shrouding. 59 Diagnostics 34788 Service Manual Replacement Manifold Block (RA20018) Unplug the station before beginning service work. Incorrect use or connections can cause electrical shock. Wear safety goggles when working with refrigerants. Refrigerants can cause eye injury. Disconnect hoses using extreme caution! Pressurized refrigerant may be present in hoses. Point hoses away from you and anyone nearby. Removing the Manifold Block 1. Disconnect the unit from its power source. 15. Remove the bolt located between the two solenoids on the top right side. 16. Remove the liquid, vapor, and tank fill hoses from the block and save. Installing the Replacement Manifold Block (Refer to Figures 1 & 2 during this installation) 1. Install the existing liquid, vapor, and tank fill hoses into the new block. 2. Install the existing bolt into the hole between the two solenoids on the top right side. 2. Remove the unit’s door and front panel. 3. Install the existing bolt into the hole in the left corner under the block. 3. Install and secure the hood spacers. 4. Reconnect all wiring as shown in Figure 1. 4. Close all three tank valves. 5. Reconnect the vacuum and vacuum bypass lines using new ferrules (use ferrules from kit RA20007). 5. Depressurize the unit. 7. Disconnect the three lines from the compressor. 6. Install a new tube for the oil drain line, and connect to the oil drain solenoid (use RA20005 tubing kit [cut to length], and ferrules from kit RA20006). 8. Disconnect the compressor oil return tube from the block and discard. 7. Install a new tube for the compressor suction tube, and connect it to the block. 9. Disconnect the compressor suction tube from the block and discard. 8. Reconnect the existing compressor discharge line to the block. 10. Remove the compressor discharge line from the block and save. 9. Reconnect the existing three lines to the compressor. 11. Disconnect the oil drain line from the oil drain solenoid. 10. Reconnect the existing tank liquid and vapor hoses to the block. 12. Disconnect the vacuum and vacuum bypass lines. 11. Open all three tank valves. 13. Disconnect all wires from the block. 12. Plug unit into power source, perform a function test, and check for any leaks. 6. Disconnect the tank liquid and vapor hoses from the tank. 14. Remove the bolt located in the left corner under the block. 60 13. Replace the shrouding, and remove the hood spacers. Diagnostics 34788 Service Manual Figure 1 – Electrical Connections to Manifold Block Connection Label Harness 539992 RB8 HPS 539991 COMP 64 66 76 539989 RB10 GND (2x) PUMP FAN FAN (2x) COMP 539990 RB9 RB6 CB (2x) GND 74 75 539994 RB7 PSJ1 PSJ2 539927 RB11 RB13 S1 S2 S5 S6 S10 S11 S15 539987 RB14 S3 S4 S7 S8 S9 S12 S13 S14 539993 GND 25 539988 RB1 Connection Relay Board J4 High Pressure Switch PT20 S5 S6 S7 S10 S3 S12 S1 539989 Comp Comp Start Relay Compressor Thermal Compressor Ground Relay Board J6 Unit Ground Stud Vacuum Pump Pigtail Fan Ground Fan Terminals 539991 Comp S11 S2 S4 Relay Board J3 Relay Board J1 Circuit Breaker Unit Ground Stud Power Switch Terminal 1 Power Switch Terminal 2 PT21 S9 S8 Manifold Assembly (Top View) HPS Relay Board J2 Power Supply J1 Power Supply J2 Relay Board J18 Relay Board J17 Normal Discharge Solenoid High Side Clear Solenoid High Side Charge Solenoid Low Side Charge Solenoid Recover Solenoid Tank Fill Solenoid Air Purge Solenoid Relay Board J11 Oil Inject Solenoid Deep Recover Solenoid High Side Inlet Solenoid Vacuum Solenoid Low Side Inlet Solenoid Power Charge Solenoid Oil Return Solenoid Oil Drain Solenoid S13 S14 Manifold Assembly (Front View) Unit Ground Stud Power Cord Bracket Relay Board J7 All wires must be clear of moving parts, pinch points, and sharp edges. 61 62 16” VACUUM PUMP BLUE TUBE FROM LOW SIDE GAUGE BLUE SERVICE HOSE ROUTE THROUGH HOLES IN SIDE SUPPORT RED SERVICE HOSE ROUTE THROUGH HOLES IN SIDE SUPPORT USE LOCTITE 242 OR EQUIVALENT ON THREADS 19” BLACK TANK FILL HOSE ROUTE THROUGH HOLE IN SIDE SUPPORT MANIFOLD ASSY USE LOCTITE 242 OR EQUIVALENT ON THREADS OIL INJECT BOTTLE RED TUBE FROM HIGH SIDE GAUGE ISV ASSEMBLY USE LOCTITE 242 OR EQUIVALENT ON THREADS 27” 12” OIL DRAIN BOTTLE VACUUM PUMP EXHAUST SHOULD PROTRUDE APPROX. 1.5” INTO OIL DRAIN BOTTLE 23” - CUT END OF TUBE AT 45° AND INSERT TO BOTTOM OF BOTTLE STA-STRAP TUBES TO SLOTS IN SIDE SUPPORT WITH (2) 102338 USE LOCTITE 242 OR EQUIVALENT ON THREADS 28” MANIFOLD ASSY 538469 2X 105358 USE LOCTITE 242 OR EQUIVALENT ON THREADS 15” Diagnostics 34788 Service Manual Replacement Manifold Block (RA20018) (continued) Figure 2 – Plumbing Connections to Manifold Block Diagnostics 34788 Service Manual Replacement Manifold Solenoid (RA20010) Unplug the station before beginning service work. Incorrect use or connections can cause electrical shock. Wear safety goggles when working with refrigerants. Refrigerants can cause eye injury. Disconnect hoses using extreme caution! Pressurized refrigerant may be present in hoses. Point hoses away from you and anyone nearby. Instructions These instructions outline the steps to replace the existing manifold solenoid. Installing the Replacement Manifold Solenoid 1. Lubricate the o-rings and threads on the new solenoid assembly. 2. Install the new solenoid assembly into the main block and hand-tighten. 3. Using a torque wrench, tighten the solenoid assembly to a torque of 75 in. lbs. (±5 in. lbs.). 4. Install the new coil on the new solenoid assembly, and secure with the fastener that holds the coil in place. 5. Using a torque wrench, tighten the coil retaining bolt to a torque of 30 in. lbs. (±5 in. lbs.). Removing the Manifold Solenoid 1. Disconnect the unit from its power source. 6. Reconnect the wires that were disconnected when removing the old solenoid assembly. 2. Remove the unit’s door and front panel. 3. Install and secure the hood spacers. 4. Depressurize the unit. 7. Plug unit into power source, perform a function test, and check for any leaks. 8. Replace the shrouding, and remove the hood spacers. 5. Disconnect the two wires connected to the solenoid that is being replaced. 6. Remove the fastener that holds the coil on the solenoid, and remove the coil. 7. Remove the solenoid assembly from the manifold block. 8. Check the manifold block for any debris before beginning the installation of a new solenoid. 63 Diagnostics 34788 Service Manual Replacement Display Board (RA20012) Unplug the station before beginning service work. Incorrect use or connections can cause electrical shock. Wear safety goggles when working with refrigerants. Refrigerants can cause eye injury. Disconnect hoses using extreme caution! Pressurized refrigerant may be present in hoses. Point hoses away from you and anyone nearby. Instructions These instructions outline the steps to replace the existing display board. Removing the Display Board 1. Disconnect the unit from its power source. 2. Rotate the unit’s head assembly into a face down position. 3. Remove the shoulder brackets and the six (6) screws securing the back of the head assembly (see diagram below). Lift the back off. 4. Disconnect all wires from the display board. 5. Remove the four (4) screws holding the display board in place. Head Assembly Diagram 64 Installing the Replacement Display Board 1. Install the display board, and secure with four (4) screws. 2. Connect all wires as shown in diagram on back of this form. 3. Replace and secure the head assembly’s back with six (6) screws. 4. Replace the shoulder brackets. 5. Remove the unit’s front panel. 6. Connect the unit to its power source. 7. Turn the unit on to begin calibration steps. 8. Press the MENU key. 9. Press the DOWN arrow twice to SERVICE MENU. 10. Press 2-2-0-0. 11. Press the START key. 12. Press the UP arrow twice to CALIBRATE TANK SCALE. 13. Press the START key. 14. Close all three (3) tank valves. 15. Depressurize the unit. 16. Disconnnect the liquid hose and vapor hose from the tank. 17. Disconnect the wires from the air purge solenoid, tank temperature probe, and pressure transducer. 18. Remove the two (2) bolts that secure the tank in place. 19. Remove the tank from the scale, and verify there is no weight on the scale or anything interfering with the scale. 20. Press the START key. 21. Place 20 pounds on the scale when prompted; then, press START. 22. When CALIBRATE TANK SCALE appears, press the UP arrow to UL CALIBRATION. 23. Press the START key. 24. Place 43 pounds on the scale if using a Worthington tank, or 45 pounds if using an Aircom tank. 25. Press the START key. Continued . . . Diagnostics 34788 Service Manual Installing the Replacement Display Board Continued 26. Wait while the unit calibrates the UL circuit and stops. 27. Remove 2 pounds when the unit prompts you. 28. When the unit shows UL CALIBRATION COMPLETE, press the STOP key twice. 29. Place the tank on the scale, and secure with two (2) bolts. 30. Reconnect the tank temperature probe, air purge solenoid, and pressure transducer wires. 31. Reconnect the liquid hose and vapor hose to the tank. 32. Open all three (3) tank valves. 33. Perform a function test, and check for leaks. 34. Replace the unit’s front panel. Display Board Wiring Diagram 65 Diagnostics 34788 Service Manual Replacement Relay Board (RA20013) Unplug the station before beginning service work. Incorrect use or connections can cause electrical shock. Wear safety goggles when working with refrigerants. Refrigerants can cause eye injury. Removing the Relay Board 1. Disconnect the unit from its power source. 2. Remove the unit’s door and front panel. 3. Install and secure the hood spacers. Disconnect hoses using extreme caution! Pressurized refrigerant may be present in hoses. Point hoses away from you and anyone nearby. 4. Disconnect all wires from the relay board. 5. Remove the screws that secure the relay board in place. Instructions These instructions outline the steps to replace the relay board. Relay Board Wiring Diagram 66 34788 Service Manual Diagnostics Installing the Replacement Relay Board 1. Install the new relay board, and secure in place with screws. 2. Connect all wires as shown in diagram. 3. Connect the unit to its power source. 17. Press the START key. 18. Place 20 pounds on the scale when prompted; then, press START. 19. When CALIBRATE TANK SCALE appears, press the UP arrow to UL CALIBRATION. 4. Turn the unit on to begin calibration steps. 20. Press the START key. 5. Press the MENU key. 6. Press the DOWN arrow twice to SERVICE MENU. 21. Place 43 pounds on the scale if using a Worthington tank, or 45 pounds if using an Aircom tank. 7. Press 2-2-0-0. 22. Press the START key. 8. Press the START key. 23. Wait while the unit calibrates the UL circuit and stops. 9. Press the UP arrow twice to CALIBRATE TANK SCALE. 10. Press the START key. 24. Remove 2 pounds when the unit prompts you. 25. When the unit shows UL CALIBRATION COMPLETE, press the STOP key twice. 11. Close all three (3) tank valves. 12. Depressurize the unit. 26 . Place the tank on the scale, and secure with two (2) bolts. 13. Disconnnect the liquid hose and vapor hose from the tank. 27. Reconnect the tank temperature probe, air purge solenoid, and pressure transducer wires. 14. Disconnect the wires from the air purge solenoid, tank temperature probe, and pressure transducer. 28. Reconnect the liquid hose and vapor hose to the tank. 15. Remove the two (2) bolts that secure the tank in place. 29. Open all three (3) tank valves. 30. Perform a function test, and check for leaks. 16. Remove the tank from the scale, and verify there is no weight on the scale or anything interfering with the scale. 31. Remove the hood spacers, and replace the shrouding. 67 Diagnostics 34788 Service Manual Replacement Vacuum Relief Check Valve (RA20015) Unplug the station before beginning service work. Incorrect use or connections can cause electrical shock. Wear safety goggles when working with refrigerants. Refrigerants can cause eye injury. Disconnect hoses using extreme caution! Pressurized refrigerant may be present in hoses. Point hoses away from you and anyone nearby. Instructions These instructions outline the steps to replace the existing vacuum relief check valve. Removing the Vacuum Relief Check Valve 1. Disconnect the unit from its power source. 2. Remove the unit’s door and front panel. Installing the Replacement Vacuum Relief Check Valve Use a thread sealant that is compatible with refrigerants such as Loctite® 565 or equivalent. 1. Install the compression fitting into the discharge side of the new check valve. 2. Install the check valve onto the tee fitting that is connected to the main block. 3. Connect the nylon line that was removed from the old vacuum relief check valve. 4. Plug unit into power source, perform a function test, and check for any leaks. 5. Replace the shrouding, and remove the hood spacers. 3. Install and secure the hood spacers. 4. Depressurize the unit. 5. Remove the nylon line from the fitting connected to the check valve. Main Block 6. Remove the check valve connected to the tee fitting. 7. Remove the compression fitting from the check valve. Tee Fitting Vacuum Relief Check Valve (Note direction of flow arrow) Vacuum Relief Check Valve Location 68 Diagnostics 34788 Service Manual Replacement Manifold Check Valve (RA20016) Unplug the station before beginning service work. Incorrect use or connections can cause electrical shock. Installing the Replacement Manifold Check Valve 1. Lubricate the o-rings on the new check valve. Wear safety goggles when working with refrigerants. Refrigerants can cause eye injury. 2. Install the new check valve into the main block and hand-tighten. Disconnect hoses using extreme caution! Pressurized refrigerant may be present in hoses. Point hoses away from you and anyone nearby. 3. Using a torque wrench, tighten the check valve to a torque of 75 in. lbs. (±5 in. lbs.). 4. Plug unit into power source, perform a function test, and check for any leaks. Instructions These instructions outline the steps to replace the existing check valve manifold. 5. Replace the shrouding and remove the hood spacers. Removing the Manifold Check Valve 1. Disconnect the unit from its power source. 2. Remove the unit’s door and front panel. 3. Install and secure the hood spacers. 4. Depressurize the unit. 5. Remove the existing manifold check valve that needs to be replaced. 69 Diagnostics Replacement 3/8” High Pressure Tube (RA20005) Unplug the station before beginning service work. Incorrect use or connections can cause electrical shock. Wear safety goggles when working with refrigerants. Refrigerants can cause eye injury. Disconnect hoses using extreme caution! Pressurized refrigerant may be present in hoses. Point hoses away from you and anyone nearby. Instructions These instructions outline the steps to replace the three black 3/8” high pressure tubes. To prevent personal injury and/or equipment damage, always replace tubing that has been removed from the compressor. The process of installing and removing the tubes can stress them, causing them to leak or fail. 1. Depressurize unit. 2. Disconnect and discard the old tube and ferrule nuts. 3. Using the old tube as a guide, cut a piece of new tubing the same length. 4. With new ferrule nuts (from kit RA20006), install the new tube into the unit. Tighten the nuts until no leaks are detected. 70 34788 Service Manual J9 Keyboard J11 SD Card PCB J1 Display/Control PCB Development Use Only Scale Ass’y S15-Air Purge Temp Probe J2 539988 539927 539988 539995 Power Switch J1 Relay PCB J2 Circuit Breaker 539990 Air Purge Trans Future Use Power Supply 34788 INTERCONNECT DIAGRAM 539927 539927 539987 539989 539994 539988 539988 ISV Ass’y 539996 539990 122770 539992 539991 Fan Compressor Vacuum Pump HP Switch S1-N Discharge S2-HS Clear S5-HS Charge S6-LS Charge S10-Recover S11-Tank Fill S3-Oil Inject S4-Dp Recover S7-HS Inlet S8-Vacuum S9-LS Inlet S12-Pwr Charge S13-Oil Return S14-Oil Drain Low-Side Trans Accum Trans Manifold Ass’y 34788 Service Manual Diagnostics SYSTEM WIRING 71 Diagnostics 34788 Service Manual 34788 COMPONENT WIRING 3A CIRCUIT BREAKER FAN SCALE ASSEMBLY POWER CORD BRACKET ISV ASSEMBLY CB 15 AMP CIRCUIT BREAKER MAIN POWER SWITCH 72 34788 CHASSIS Diagnostics 34788 Service Manual RETAINER COMP. ELEC. BOX PROTECTOR RELAY SCREW PUMP CAPACITOR LEADS VACUUM PUMP ASSEMBLY CAPACITOR COMPRESSOR Future Use DB2 Development Use Only Keyboard DB1 DISPLAY/CONTROL BOARD SD1 RELAY BOARD SD SLOT (SD2) SD ADAPTER BOARD POWER SUPPLY 73 Diagnostics MANIFOLD BLOCK ASSEMBLY – TOP VIEW MANIFOLD BLOCK ASSEMBLY – FRONT VIEW 74 34788 Service Manual Diagnostics 34788 Service Manual 34788 WIRING HARNESSES Relay Board Connector Pin-outs The following chart describes the pinouts for each connector on the relay board. The connector descriptions are: J1from power switch, J2-to 12 volt power supply, J3-to circuit breaker, J4-to high pressure switch, J5-to display/control board, J6-to vacuum pump, compressor, and fan, J7-to low-side transducer, J8-to temperature probe, J11-to manifold solenoids, J13-to accumulator transducer, J14- to air pressure transducer, J16-to scale assembly, J17-to manifold solenoids, J18-to normal discharge solenoid. Conn Pin1 Pin2 Pin3 J1 Earth Ground AC Neutral in AC Line in Pin4 J2 AC 110V to 12VPS Neutral to 12VPS Earth Ground 12V from 12VPS DC GND J3 Circuit Breaker Circuit Breaker 12V fuse 12V fuse J4 HP Switch HP Switch J5 Ground SPI SPI SPI J6 110V Output Pump Neutral Pump 110V Output Comp Neutral Comp J7 5V to LS Xducer Output from Xducer Ground J8 Temp Probe Temp Probe J11 Pwr Charge Sol Vacuum Sol J13 5V to Acc Xducer Output from Xducer Ground J14 5V to AP Xducer Output from Xducer Ground J16 Exc V to scale Diff out from scale Diff out from scale Ground J17 Tank Fill Sol Recover Sol LS Charge Sol HS Charge Sol J18 Norm Discharge Sol Aux Aux Aux LS Inlet Sol HS Inlet Sol Pin5 SPI Pin6 Pin7 Pin8 Deep Rec Sol Oil Inject Sol 12V to Ctrl Board 110V Output Fan Neutral Fan Oil Return Sol Oil Drain Sol Air Purge Sol HS Clear Sol AC Power Cord (122770) AC POWER CORD (122770) CONNECTOR # 71 72 73 CONNECTS TO: Main Pow er SW1 - 2A Main Ground Stud Main Pow er SW1 - 1A 75 Manifold 1 Harness (539927) 76 CONNECTS TO: J-17 Relay Board J-18 Relay Board Solenoid - S1 (Tan Wires) Solenoid - S2 (Black Wires) Solenoid - S5 (Orange Wires) Solenoid - S6 (Purple Wires) Solenoid - S10 (Yellow Wires) Solenoid - S11 (Pink Wires) Solenoid - S15 (Gray Wires) MANIFOLD 1 WIRE HARNESS (539927) CONNECTOR # RB13 RB11 S1 S2 S5 S6 S10 S11 S15 Diagnostics Manifold 1 Harness (539927) 34788 Service Manual Manifold 2 Harness (539987) CONNECTOR # RB14 S3 S4 S7 S8 S9 S12 S13 S14 CONNECTS TO: J-11 Relay Board Solenoid - S3 (Blue Wires) Solenoid - S4 (Light Blue Wires) Solenoid - S7 (Yellow Wires) Solenoid - S8 (Red Wires) Solenoid - S9 (Gray Wires) Solenoid - S12 (White Wires) Solenoid - S13 (Purple Wires) Solenoid - S14 (Orange Wires) MANIFOLD 2 WIRE HARNESS (539987) 34788 Service Manual Diagnostics Manifold 2 Harness (539987) 77 Transducer Wire Harness (539988) 78 CONNECTOR # RB1 RB2 RB3 RB4 TS PT20 PT21 PT22 CONNECTS TO: J-7 Relay Board J-13 Relay Board J-14 Relay Board J-8 Relay Board Temperature Probe - ISV Low -Side Transducer - Manifold Accum Transducer - Manifold Air Purge Transducer - ISV TRANSDUCER WIRE HARNESS (539988) Detail A Diagnostics 34788 Service Manual Transducer Wire Harness (539988) Light Blue Brown Green/Yellow Brown Compressor/Fan Wire Harness (539989) Dark Blue Dark Blue CONNECTOR # RB10 COMP FAN FAN GND PUMP GND Green/Yellow CONNECTS TO: J-6 Relay Board To Compress Harness (539991) Fan Fan Ground Vacuum Pump Assembly Chassis Ground Brown Green/Yellow COMPRESSOR/FAN WIRE HARNESS (539989) 34788 Service Manual Diagnostics Compressor/Fan Wire Harness (539989) 79 80 Brown Brown Green/Yellow Power Wire Harness (539990) Light Blue Brown CONNECTS TO: J-3 Relay Board J-1 Relay Board 15A Circuit Breaker Ground Pow er Sw itch #1 Pow er Sw itch #2 POWER WIRE HARNESS (539990) CONNECTOR # RB9 RB6 CB GRN 74 75 Diagnostics 34788 Service Manual Power Wire Harness (539990) Brown Compressor Pigtail Wire Harness (539991) CONNECTS TO: To Compressor/Fan Wire Harness (539989) Compressor Relay Compressor Protector Compressor Ground Green/Yellow Blue CONNECTOR # COMP 64 66 76 COMPRESSOR/FAN WIRE HARNESS (539991) 34788 Service Manual Diagnostics Compressor Pigtail Wire Harness (539991) 81 High Pressure Cutout Harness (539992) 82 Brown CONNECTOR # CONNECTS TO: RB8 J-4 Relay Board HPS High Pressure Cutout Sw itch - Manifold HIGH PRESSURE CUTOUT SWITCH (539992) Diagnostics 34788 Service Manual High Pressure Cutout Harness (539992) Gray Brown Power Supply Harness (539994) Red CONNECTOR # RB7 PSJ1 PSJ2 CONNECTS TO: J-2 Relay Board J-1 Pow er Supply J-2 Pow er Supply Blue POWER SUPPLY HARNESS (539994) 34788 Service Manual Diagnostics Power Supply Harness (539994) 83 Diagnostics 34788 Service Manual Interconnect Cable (539995) INTERCONNECT CABLE (539995) CONNECTOR # CONNECTS TO: RB12 J-5 Relay Board DB1 J-9 Display/Control Board SD Board Cable (539996) SD BOARD CABLE (539996) CONNECTOR # CONNECTS TO: DB2 J-11 Display/Control Board SD1 J-1 SD Card Board SD1 84 DB2 Diagnostics 34788 Service Manual Ground Wire Harness (539993) GROUND WIRE HARNESS (539993) CONNECTOR # CONNECTS TO: 25 Pow er Cord Bracket GND Chassis Ground Green/Yellow Capacitor Lead (516844) CAPACITOR LEAD (516844) CONNECTOR # CONNECTS TO: A Compressor Relay (1 or 2) B Compressor Capacitor A B Black Fully Insulated Terminal 85 Diagnostics 34788 Service Manual COMPONENT IDENTIFICATION MANIFOLD BLOCK ASSEMBLY - TOP LOW SIDE TRANSDUCER HIGH-SIDE INLET LOW-SIDE SOLENOID CHARGE SOLENOID HIGH-SIDE CHARGE SOLENOID OIL INJECT SOLENOID NORMAL DISCHARGE SOLENOID S7 S3 S5 S6 S1 PT20 HIGH-SIDE CLEAR SOLENOID S2 S10 S8 POWER CHARGE SOLENOID S12 S11 S9 S4 RECOVER SOLENOID VACUUM SOLENOID PT21 HIGH PRESSURE SWITCH TANK FILL SOLENOID DEEP RECOVER SOLENOID LOW-SIDE INLET SOLENOID ACCUM TRANSDUCER AIR PURGE SOLENOID HIGH PRESSURE SWITCH UPPER BLOCK LOWER BLOCK AIR PURGE PRESSURE TRANSDUCER S15 TEMPERATURE PROBE HPS 4 PSI RELIEF FOR VACUUM PUMP COMPRESSOR OIL SEPARATOR SYSTEM OIL SEPARATOR OIL RETURN SOLENOID ISV S13 FILTER DRIER OIL DRAIN SOLENOID S14 MANIFOLD BLOCK ASSEMBLY - FRONT 86 ISV ASSEMBLY Diagnostics 34788 Service Manual COMPONENT APPLICATION CHART Component Application Chart Norm al Discharge Solenoid (1) Tank Fill Recover ON ON Air Purge Clearing Vacuum Leak Test Inject Oil Charge / Pw r Charge* I High-Side Clear Solenoid (2) I I* Oil Inject Solenoid (3) ON Deep Recover Solenoid (4) I High-Side Charge Solenoid (5) P Low -Side Charge Solenoid (6) P High-Side Inlet Solenoid (7) ON ON Vacuum Solenoid (8) I ON Low -Side Inlet Solenoid (9) ON ON Recover Solenoid (10) I Tank Fill Solenoid (11) ON I Pow er Charge Solenoid (12) I Oil Return Solenoid (13) I Oil Drain Solenoid (14) I Air Purge Solenoid (15) I* I ON I Vacuum Pum p ON Com pressor ON ON ON Fan ON ON ON ON ON I* ON I ON Intermittently P User Programmed * Charge/Power Charge Note: If the unit does not complete a full charge, the compressor, power charge and high-side clear solenoids are activated, then stop to build tank pressure. 87 External Tank Tank Fill Solenoid Tank Fill Checkvalve 88 TANK FILL During the Tank Fill process the compressor, fan, normal discharge, and tank fill solenoid are activated. The output state of the tank fill solenoid is controlled to maintain 35 psi in the accumulator. When the ISV reaches the “target” weight, all components are deactivated. ENERGIZED Oil Inject Bottle Vacuum Solenoid Oil Inject Solenoid High Side Inlet Solenoid Low Side Inlet Solenoid Normal Discharge Solenoid High Side Gauge High Side High Side Charge Solenoid Compressor Oil Separator Pressure Relief Low Side Low Side Gauge Low Side Charge Solenoid ISV Temp Probe Pressure Transducer Air Purge Solenoid Air Diffuser Low Side Pressure Transducer Liquid INTERMITTENT DISCHARGE SUCTION Recover Solenoid Vacuum Pump Oil Return Solenoid Compressor HS Clear Solenoid Clearing Discharge Checkvalve Vapor Recover Checkvalve Oil Drain Solenoid Filter Drier High Pressure Switch Normal Discharge Checkvalve Air Purge Deep Recover Solenoid 4 PSI Relief Oil Drain Bottle System Oil Separator Accum Transducer Power Charge Solenoid Diagnostics 34788 Service Manual FLOW DIAGRAMS Tank Fill External Tank Tank Fill Solenoid Tank Fill Checkvalve RECOVERY PROCESS During the first stage of the recovery process, the fan, compressor, normal discharge, recover, HS and LS inlet solenoids are activated. During the second stage of the recover process, the vacuum pump, vacuum, deep recover, and power charge solenoids are activated and the recover solenoid is deactivated. ENERGIZED Oil Inject Bottle Vacuum Solenoid Oil Inject Solenoid High Side Inlet Solenoid Low Side Inlet Solenoid Normal Discharge Solenoid High Side Gauge High Side High Side Charge Solenoid Compressor Oil Separator Pressure Relief Low Side Low Side Gauge Low Side Charge Solenoid ISV Temp Probe Pressure Transducer Air Purge Solenoid Air Diffuser Low Side Pressure Transducer Liquid INTERMITTENT DISCHARGE SUCTION Recover Solenoid Vacuum Pump Oil Return Solenoid Compressor HS Clear Solenoid Clearing Discharge Checkvalve Vapor Recover Checkvalve Oil Drain Solenoid Filter Drier High Pressure Switch Normal Discharge Checkvalve Air Purge Deep Recover Solenoid 4 PSI Relief Oil Drain Bottle System Oil Separator Accum Transducer Power Charge Solenoid 34788 Service Manual Diagnostics Recover 89 90 Tank Fill Checkvalve AIR PURGE The air purge solenoid is activated to release excess pressure from the internal storage vessel. The air purge usually follows the Recover process. ENERGIZED Vacuum Solenoid Oil Inject Bottle Vacuum Pump Oil Return Solenoid Compressor Oil Inject Solenoid High Side Inlet Solenoid Low Side Inlet Solenoid Normal Discharge Solenoid High Side Gauge High Side High Side Charge Solenoid Compressor Oil Separator Pressure Relief Low Side Low Side Gauge Low Side Charge Solenoid ISV Temp Probe Pressure Transducer Air Purge Solenoid Air Diffuser Low Side Pressure Transducer Liquid INTERMITTENT DISCHARGE Recover Solenoid Oil Drain Solenoid Filter Drier HS Clearing Solenoid Clearing Discharge Checkvalve Vapor Recover Checkvalve Deep Recover Solenoid 4 PSI Relief Oil Drain Bottle System Oil Separator High Pressure Switch Normal Discharge Checkvalve Air Purge SUCTION External Tank Tank Fill Solenoid Accum Transducer Power Charge Solenoid Diagnostics 34788 Service Manual Air Purge External Tank Tank Fill Solenoid Tank Fill Checkvalve CLEARING PROCESS During the first stage of the clearing process the normal discharge solenoid and compressor are activated. The second stage of clearing deactivates the normal discharge solenoid and activates the HS clear and oil return solenoids. When the accumulator transducer reads less than 9 inHG, all outputs are deactivated. ENERGIZED Oil Inject Bottle Vacuum Solenoid Oil Inject Solenoid High Side Inlet Solenoid Low Side Inlet Solenoid Normal Discharge Solenoid High Side Gauge High Side High Side Charge Solenoid Compressor Oil Separator Pressure Relief Low Side Low Side Gauge Low Side Charge Solenoid ISV Temp Probe Pressure Transducer Air Purge Solenoid Air Diffuser Low Side Pressure Transducer Liquid INTERMITTENT DISCHARGE SUCTION Recover Solenoid Vacuum Pump Oil Return Solenoid Compressor HS Clear Solenoid Clearing Discharge Checkvalve Vapor Recover Checkvalve Oil Drain Solenoid Filter Drier High Pressure Switch Normal Discharge Checkvalve Air Purge Deep Recover Solenoid 4 PSI Relief Oil Drain Bottle System Oil Separator Accum Transducer Power Charge Solenoid 34788 Service Manual Diagnostics Clearing 91 External Tank Tank Fill Solenoid Tank Fill Checkvalve 92 VACUUM PROCESS The default vacuum time is 10:00 minutes. When the vacuum process begins, the vacuum pump is activated. After a 5 second delay, the vacuum, HS and LS inlet solenoids are also activated. When the Low-Side transducer reads > 10 psi, you will be prompted to end the vacuum process. ENERGIZED Oil Inject Bottle Vacuum Solenoid Oil Inject Solenoid High Side Inlet Solenoid Low Side Inlet Solenoid Normal Discharge Solenoid High Side Gauge High Side High Side Charge Solenoid Compressor Oil Separator Pressure Relief Low Side Low Side Gauge Low Side Charge Solenoid ISV Temp Probe Pressure Transducer Air Purge Solenoid Air Diffuser Low Side Pressure Transducer Liquid INTERMITTENT DISCHARGE SUCTION Recover Solenoid Vacuum Pump Oil Return Solenoid Compressor HS Clearing Solenoid Clearing Discharge Checkvalve Vapor Recover Checkvalve Oil Drain Solenoid Filter Drier High Pressure Switch Normal Discharge Checkvalve Air Purge Deep Recover Solenoid 4 PSI Relief Oil Drain Bottle System Oil Separator Accum Transducer Power Charge Solenoid Diagnostics 34788 Service Manual Vacuum Tank Fill Checkvalve LEAK TEST PROCESS High-Side inlet and Low-Side inlet solenoids are activated to equalize high and low sides of system being serviced. Unit checks low-side transducer for rise in vacuum. (This is not a service menu test.) ENERGIZED Vacuum Solenoid Oil Inject Bottle Vacuum Pump Oil Return Solenoid Compressor Oil Inject Solenoid High Side Inlet Solenoid Low Side Inlet Solenoid Normal Discharge Solenoid High Side Gauge High Side High Side Charge Solenoid Compressor Oil Separator Pressure Relief Low Side Low Side Gauge Low Side Charge Solenoid ISV Temp Probe Pressure Transducer Air Purge Solenoid Air Diffuser Low Side Pressure Transducer Liquid INTERMITTENT Recover Solenoid Oil Drain Solenoid Filter Drier HS Clear Solenoid Clearing Discharge Checkvalve Vapor Recover Checkvalve Deep Recover Solenoid 4 PSI Relief Oil Drain Bottle System Oil Separator High Pressure Switch Normal Discharge Checkvalve Air Purge PRESSURE External Tank Tank Fill Solenoid Accum Transducer Power Charge Solenoid 34788 Service Manual Diagnostics Leak Test 93 94 Tank Fill Checkvalve INJECT OIL The inject oil button must be depressed to activate the oil inject solenoid. Release the button to deactivate the solenoid. The system being serviced must have a vacuum to pull oil from the oil inject bottle. ENERGIZED Vacuum Solenoid Oil Inject Bottle Vacuum Pump Oil Return Solenoid Compressor Oil Inject Solenoid High Side Inlet Solenoid Low Side Inlet Solenoid Normal Discharge Solenoid High Side Gauge High Side High Side Charge Solenoid Compressor Oil Separator Pressure Relief Low Side Low Side Gauge Low Side Charge Solenoid ISV Temp Probe Pressure Transducer Air Purge Solenoid Air Diffuser Low Side Pressure Transducer Liquid INTERMITTENT DISCHARGE Recover Solenoid Oil Drain Solenoid Filter Drier HS Clearing Solenoid Clearing Discharge Checkvalve Vapor Recover Checkvalve Deep Recover Solenoid 4 PSI Relief Oil Drain Bottle System Oil Separator High Pressure Switch Normal Discharge Checkvalve Air Purge SUCTION External Tank Tank Fill Solenoid Accum Transducer Power Charge Solenoid Diagnostics 34788 Service Manual Inject Oil External Tank Tank Fill Solenoid Tank Fill Checkvalve CHARGE PROCESS During the Charge process, the end user may select either high-side charge, low-side charge, or both. When the charge process gets close to the programmed weight, the unit slows down. It’ll charge, settle, charge again, settle, etc. When the charge process is complete, user must equalize hoses. If the unit does not complete a full charge, the compressor, power charge and high-side clear solenoids are activated, then stop to build tank pressure. ENERGIZED Oil Inject Bottle Vacuum Solenoid Oil Inject Solenoid High Side Inlet Solenoid Low Side Inlet Solenoid Normal Discharge Solenoid High Side Gauge High Side High Side Charge Solenoid Compressor Oil Separator Pressure Relief Low Side Low Side Gauge Low Side Charge Solenoid ISV Temp Probe Pressure Transducer Air Purge Solenoid Air Diffuser Low Side Pressure Transducer Liquid INTERMITTENT DISCHARGE SUCTION Recover Solenoid Vacuum Pump Oil Return Solenoid Compressor HS Clear Solenoid Clearing Discharge Checkvalve Normal Discharge Checkvalve Vapor Recover Checkvalve Oil Drain Solenoid Filter Drier High Pressure Switch Power Charge Solenoid Air Purge Deep Recover Solenoid 4 PSI Relief Oil Drain Bottle System Oil Separator Accum Transducer NOTE: If the unit does not complete a full charge, the compressor, power charge and high-side clear solenoids are activated, then stops to build tank pressure. 34788 Service Manual Diagnostics Charge 95 Diagnostics 96 34788 Service Manual Service Bulletins 34788 Service Manual 4 S E RV I C E B U L L E T I N S Place all service bulletins for the 34788 in this section 97 Service Bulletins 98 34788 Service Manual SPX ROBINAIR 655 Eisenhower Drive, Owatonna, MN 55060 Phone: (800) 822-5561 FAX: (412) 690-2001 TECHNICAL SERVICE BULLETIN RA19950 Reservoir Installation Kit SUBJECT: EQUIP. AFFECTED: 3 CFM Station Pump ACTION REQUIRED: Informational HARDWARE NO: 00201-RA DATE: Nov., 2006 AUTHOR: S. Parde Summary At the end of 2005, Robinair introduced a new 3 CFM station pump in the following A/C units: 34134Z, 34700Z, and 342000 (see service bulletin #00198-HW). Until now, if the vacuum pump needed repairing, the complete station pump would have to be replaced. Robinair has released a parts kit (RA19950), which include the reservoir/head assembly, sight glass parts, oil drain w/cap, inlet/outlet fittings, and oil fill plug. (These parts are not available separately.) This kit is compatible with both 115V and 230V station pumps. 3 CFM Station Pump Part Numbers RA19902 — Complete Station Pump, 115V, 60Hz 527849 — Complete Station Pump, 230V, 50Hz RA19950 — Reservoir Installation Kit (includes removal and assembly instructions) SPX Ser vice Solutions Service THIS DISCLOSURE TO BE MAINTAINED IN CONFIDENCE. 655 Eisenhower Drive, Owatonna, MN 55060 Phone: (800) 822-5561 FAX: (412) 690-2001 TECHNICAL SERVICE BULLETIN INFORMATION New Air Com Internal Storage Vessel (ISV) SUBJECT: EQUIP. AFFECTED: Robinair 34788 (and associated models) ACTION REQUIRED: Informational NO: 00203-RA July, 2007 DATE: AUTHOR: S. Parde Overview Robinair Engineering has recently approved a new Internal Storage Vessel (ISV) for use in the 34788 unit, which is identified as “Air Com.” For the time being, either the new Air Com ISV or the Worthington ISV can be used in the 34788 unit. However, there are some differences between the two ISV’s that should be noted to properly set UL and scale calibrations. Refer to tank specifications listed below and be sure you identify the proper tank and use the corresponding specs to calibrate the unit. AIR COM ISV “New” WORTHINGTON ISV Tag says “Certified by “Air Com Co. Ltd.” Port ID label has a border around its edges Tank Tare = 20.50 lbs. (9.30 kg.) UL Calibration Wt. = 45 lbs. (20.4 kg.) Tag says “Certified by WORTHJ” Port ID label has no border around its edges Tank Tare = 17.50 lbs. (7.94 kg.) UL Calibration Wt. = 43 lbs. (19.5 kg.) Figure 1 - Air Com Tank Tag Figure 2 - Worthington Tank Tag CERTIFIED BY AIR COM CO. LTD. CERTIFIED BY WORTHJ Please note this information in the 34788 service manual, or download the updated service manual from the Robinair Service Center website. SPX Ser vice Solutions Service THIS DISCLOSURE TO BE MAINTAINED IN CONFIDENCE. 655 Eisenhower Drive, Owatonna, MN 55060 Phone: (800) 822-5561 FAX: (412) 690-2001 TECHNICAL SERVICE BULLETIN HARDWARE Internal Storage Vessel (ISV) Assembly Parts SUBJECT: EQUIP. AFFECTED: Robinair 34788 (and associated units) ACTION REQUIRED: Informational NO: 00204-RA Aug., 2007 DATE: AUTHOR: S. Parde Overview Robinair Engineering has recently approved a new Internal Storage Vessel (ISV) for use in the Robinair 34788 unit, which is identified as “Air Com.” For the time being, either the new Air Com ISV or the Worthington ISV can be used in the 34788 unit. The part numbers shown in the listing below are compatible for both Air Com and Worthington tanks. If the tank itself is ordered (539477), you will receive the new Air Com tank. 3 4 5 9 10 8 11 2 7 12 6 13 1 ISV ASSEMBLY Use Loctite 565 on all pipe threads. Tank Tare Weight: Worthington: 17.50 lbs. (7.94 kg.) Air Com: 20.50 lbs. (9.30 kg.) SPX Ser vice Solutions Service No. 1 2 3 4 5 6 7 8 9 10 11 12 13 Description ISV, INTERNAL FITTING, STRAIGHT SOLENOID, 12V DC DISCRETE VALVE, BALL, AIR PURGE VALVE, BALL, LIQUID PRESSURE RELIEF, 450PSI FITTING, TEE, .25FP X .25FP X .25MP VALVE, BALL, VAPOR TEMPERATURE PROBE TRANSDUCER, AIR PURGE TEE, MALE BRANCH 1/8 NPTF ORIFICE, UNION .026 MUFFLER, AIR EXHAUST Qty 1 1 1 1 1 1 1 1 1 1 1 1 1 Part No. 539477 210312 RA20009 539799 539798 RA19499 508690 540322 539472 539229 539654 539804 519605 THIS DISCLOSURE TO BE MAINTAINED IN CONFIDENCE. 655 Eisenhower Drive,Service Owatonna, MN 55060 34788 Manual Phone: (800) 822-5561 FAX: (412) 690-2001 Service Bulletins TECHNICAL SERVICE BULLETIN Display Board Wiring Diagram Error SUBJECT: EQUIP. AFFECTED: Robinair 34788 (and associated units) ACTION REQUIRED: Informational INFORMATION NO: 00205-RA Aug., 2007 DATE: AUTHOR: S. Parde 34788 Service Manual The Display Board (RA20012) wiring diagram prints located on pages 21 and 65 of the Robinair 34788 service manual are incorrect. Please refer to the print below for correct wiring orientation. Please note these changes in the Robinair 34788 service manual. Display Board Wiring Diagram 102 SPX Ser vice Solutions Service THIS DISCLOSURE TO BE MAINTAINED IN CONFIDENCE. Labor Rates 34788 Service Manual 5 L A B O R R AT E S Robinair authorizes a labor charge of 1-1/2 hours to troubleshoot and complete a full function test on units that are covered under factory warranty (including leak testing). The authorized time for parts replacement is 15 minutes per part. Some items require an additional amount of time to facilitate installation. These items and their times are listed below. If repairs are estimated to exceed two (2) hours, prior authorization from Robinair is required. Part Number Component Total Time RA20018 RA20020 RA20017 Manifold Assembly Compressor Assembly Vacuum Pump Assembly 60 minutes 30 minutes 30 minutes Robinair considers filters to be a consumable item; they are not covered under warranty. This includes parts and labor. 103 Labor Rates 104 34788 Service Manual Product Warranty 34788 Service Manual 6 PRODUCT WARRANTY Robinair Limited Warranty Statement Rev. November 1, 2005 This product is warranted to be free from defects in workmanship, materials, and components for a period of one year from date of purchase. All parts and labor required to repair defective products covered under the warranty will be at no charge. The following restrictions apply: 1. The limited warranty applies to the original purchaser only. 2. The warranty applies to the product in normal usage situations only, as described in the Operating Manual. The product must also be serviced and maintained as specified. 3. If the product fails, it will be repaired or replaced at the option of the manufacturer. 4. Transportation charges for warranty service may be reimbursed by the factory upon verification of the warranty claim and submission of a freight bill for normal ground service. Approval from the manufacturer must be obtained prior to shipping to an authorized service center. 5. Warranty service claims are subject to authorized inspection for product defect(s). 6. The manufacturer shall not be responsible for any additional costs associated with a product failure including, but not limited to, loss of work time, loss of refrigerant, cross-contamination of refrigerant, and unauthorized shipping and/or labor charges. 7. All warranty service claims must be made within the specified warranty period. Proof-of-purchase date must be supplied to the manufacturer. 8. Use of recovery/recycling equipment with unauthorized refrigerants or sealants will void warranty. • Authorized refrigerants are listed on the equipment or are available through the Technical Service Department. • The manufacturer prohibits the use of the recovery/recycling equipment on air conditioning (A/C) systems containing leak sealants, either of a seal-swelling or aerobic nature. This Limited Warranty does NOT apply if: • The product, or product part, is broken by accident. • The product is misused, tampered with, or modified. • The product is used for recovering or recycling any substance other than the specified refrigerant type. This includes, but is not limited to, materials and chemicals used to seal leaks in A/C systems. 105 SPX Corporation 655 Eisenhower Drive Owatonna, MN 55060-0995 Phone 800-822-5561 Models: 34788, AC34788, H234788, RA-C34788 Service Manual, Rev. C