© Siemens AG 2018
3WL1 Air Circuit Breakers
SENTRON
Configuration
Manual
Edition
04/2018
siemens.com/lowvoltage
© Siemens AG 2018
© Siemens AG 2018
3WL1 Air Circuit Breakers
2
8
14
21
27
36
38
52
54
55
56
56
57
58
Introduction
3WL1 air circuit breakers/
non-automatic air circuit breakers
up to 6300 A (AC), IEC
General data
- Design
- Function
- Configuration
- Technical specifications
Configuration aids
- Characteristic curves
- Dimensional drawings
- Circuit diagrams
- More information
3WL1 non-automatic air circuit breakers
up to 4000 A (DC)
General data
- Technical specifications
Configuration aids
- Characteristic curves
- Dimensional drawings
- Circuit diagrams
- More information
© Siemens AG 2018
All dimensions in mm.
For further technical
product information:
Siemens Industry Online Support:
www.siemens.com/lowvoltage/productsupport
 Entry type:
Application example
Certificate
Characteristic
Download
FAQ
Manual
Product note
Software archive
Technical data
Siemens · 04/2018
© Siemens AG 2018
3WL1 Air Circuit Breakers
Introduction
■ Overview
Size I
Size III
Size II
3WL air circuit breakers
3WL1 air circuit breakers/non-automatic air circuit breakers 3WL1 non-automatic air circuit
up to 6300 A (AC), IEC
breakers up to 4000 A (DC)
Size
Rated current In
A
Number of poles
Rated operational
voltage Ue
V AC
V DC
Rated ultimate
short-circuit breaking
capacity at 500 V AC
kA
Endurance
Operating cycles
I, II, III
I
II
630, 800, 1000, 1250,
1600, 2000, 2500, 3200, 4000,
5000, 6300
2000
1000, 2000, 4000
3-pole, 4-pole
4-pole
3-pole, 4-pole
... 690/1000/1150
--
-... 1000
Size I
Size II
Size II
Size III
55/66/85
66/80/100
130
100/150 (3-pole), 20
30/25/20
130 (4-pole)
(at  1000 V DC) (at 300/600/1000 V DC)
Up to 20000
15000
10000
10000
Mounting position
30° 30°
H
D
30° 30°
NSE0_00061a
NSE0_00062a
IP55
IP41
Dimensions 3-/4-pole
W
30° 30°
30° 30°
NSE0_00061a
Degree of protection
With cover
Without cover
(with door sealing frame)
15000
NSE0_00062a
IP55
IP41
W mm
320/410
460/590
460/590
704/914
410
460/590
Fixed
H mm
D mm
434
291
434
291
434
291
434
291
434
291
434
291
Withdrawable
H mm
D mm
465.5
471
465.5
471
465.5
471
465.5
471
---
465.5
471
ETU15B1)
ETU25B
ETU27B
ETU45B
ETU76B
Overload protection
✓
✓
✓
✓
✓
Short-time delayed short-circuit protection
--
✓
✓
✓
✓
Instantaneous short-circuit protection
✓
✓
✓
✓
✓
Neutral conductor protection
--
--
✓
✓
✓
Ground-fault protection
--
--
✓
❑
❑
Zone Selective Interlocking
--
--
--
❑
❑
LCD, 4-line
--
--
--
❑
--
LCD, graphic
--
--
--
--
✓
Communication
--
--
--
❑
❑
Metering function Plus
--
--
--
❑
❑
Selectable parameter sets
--
--
--
--
✓
Parameters freely programmable
--
--
--
--
✓
CubicleBUS
--
--
--
✓
✓
Rating Plug
NSE0_01111a
NSE0_01108a
Type
NSE0_01106a
NSE0_01107a
NSE0_01109a
NSS0_00535
Electronic Trip Units for 3WL circuit breakers
✓ Standard
-- Not available
❑ Optional
1)
ETU15B cannot be used with 3WL circuit breakers, size III.
2
Siemens · 04/2018
3WL air circuit breakers/non-automatic air circuit breakers
according to UL 489 up to 5000 A, see Catalog LV 16.
© Siemens AG 2018
3WL1 Air Circuit Breakers
Introduction
Breaking capacity
Size
I
II
Type
3WL11
3WL12
Breaking capacity
N
S
N
S
H
H
III
N
3WL13
N
S
H
S
H
C
C
H
H
C
3-pole
C
C
4-pole
Rated short-circuit breaking capacity
Rated operational voltage Ue
up to 415 V AC
Icu
Ics
Icm
kA
kA
kA
55
55
121
66
66
145
85
85
187
66
66
145
80
80
176
100
100
220
130
130
286
100
100
220
150
150
330
130
130
286
kA
kA
kA
55
55
121
66
66
145
85
85
187
66
66
145
80
80
176
100
100
220
130
130
286
100
100
220
150
150
330
130
130
286
kA
kA
kA
42
42
88
50
50
105
66
66
145
50
50
105
75
75
165
85
85
187
100
100
220
85
85
187
150
150
330
130
130
286
----
----
509)
509)
1059)
----
----
50
50
105
----
50
50
105
704)
704)
1544)
704)
704)
1544)
55
42
29.5
24
66
50
35
29
75
66
46
44
66
55
39
32
80
66
46
44
100
85
651)/702)
501)/652)
100
100
70
65
100
100
80
65
100
100
80
65
100
100
80
65
55
42
--
66
50
--
75
66
509)
66
50
--
80
75
--
100
85
504)
130
100
--
100
85
5010)
100
100
704)
100
100
704)
Rated operational voltage Ue
up to 500 V AC
Icu
Ics
Icm
Rated operational voltage Ue
up to 690 V AC
Icu
Ics
Icm
Rated operational voltage Ue
up to 1000 V/1150 V AC
kA
kA
kA
Icu
Ics
Icm
Rated short-time withstand current
Icw of the circuit breakers3)
0.5 s
1s
2s
3s
kA
kA
kA
kA
Rated conditional short-circuit
current Icc of the non-automatic air
circuit breakers
Up to 500 V AC
Up to 690 V AC
Up to 1000 V/1150 V AC
kA
kA
kA
Size
I
Type
3WL11
3WL12
Breaking capacity
DC
DC
20
20
20
20
35
30
25
20
-20
---
-355)/306)/257)/208)
---
DC
II
DC
Rated short-circuit breaking capacity
Up to 220 V DC
Up to 300 V DC
Up to 600 V DC
Up to 1000 V DC
Icc
Icc
Icc
Icc
kA
kA
kA
kA
Rated short-time withstand current
Icw
0.5 s
1s
2s
3s
kA
kA
kA
kA
N
Circuit breakers with ECO breaking capacity N
Abbreviations*
(functions)
English long text
Explanation
L
Long Time Delay
Overload protection
S
Short Time Delay
Short-circuit protection
(short-time delayed)
S
Circuit breakers with standard breaking capacity S
H
Circuit breakers with high breaking capacity H
C
Circuit breakers with very high breaking capacity C
DC
Non-automatic air circuit breakers with DC breaking capacity
I
Instantaneous
Short-circuit protection
(instantaneous)
These breaking capacities are indicated in the corresponding tables
by the symbols shown on orange backgrounds.
N
Neutral Protection
Neutral conductor protection
G
Ground Fault
Ground-fault protection
1)
Size II with In max 2500 A.
2)
Size II with In max = 3200 A and In max = 4000 A.
3)
At a rated voltage of 690 V, the Icw value of the circuit breaker cannot be
greater than the Icu or Ics value at 690 V.
* Designations according to IEC 60947-2, Annex K.
6)
At Ue = 300 V DC
7)
At Ue = 600 V DC
4)
Rated operational voltage Ue = 1150 V.
8)
At Ue = 1000 V DC
5)
At Ue = 220 V DC
9)
Values also apply to 690 V + 20% version with Z option "A16".
10) Rated
operational voltage Ue = 1000 V.
Siemens · 04/2018
3
C
© Siemens AG 2018
3WL1 Air Circuit Breakers
Introduction
3WL1 air circuit breakers:
3WL1 air circuit breakers offer highly flexible application and
consistent communication capability. With the 3WL1 circuit
breakers, just three sizes cover a performance range of 630 A to
6300 A. All models are characterized by the same design, the
same operation and the same comprehensive accessories.
6
7
2
3
8
5
4
9
1
25
21
10
19
22
11
23
12
24
18
13
14
20
16
15
$
%
&
(
)
*
+
,
.
/
0
1
2
3
4
Guide frame
Main circuit connection front, flange, horizontal, vertical
Position signaling switch
Grounding connection, leading
Shutters
COM15 PROFIBUS module or COM16 MODBUS module
External CubicleBUS modules
Closing coil, auxiliary release
Auxiliary conductor plug-in system
Auxiliary switch block
Door sealing frame
Interlocking set for mechanical ON/OFF
Transparent panel, function insert
EMERGENCY STOP pushbutton, key operated
Motorized operating mechanism
Siemens · 04/2018
4
5
6
7
8
9
:
;
<
=
Operating cycles counter
Breaker Status Sensor (BSS)
Protective device with device holder, Electronic Trip Unit (ETU)
Remote reset solenoid
Breaker Data Adapter (BDA Plus)
Four-line display
Ground-fault protection module
Rating plug
Metering function module
Air circuit breaker
NSE0_01887d
17
© Siemens AG 2018
3WL1 Air Circuit Breakers
Introduction
Communication-capable circuit breakers (with ETU45B or ETU76B Electronic Trip Unit)
20
Ethernet
18
19
PROFIBUS
PROFINET
4
6
5
3VA-line
1
14
15
16
17
8
10
11
1
NSE0_01105
12
3
12 Metering function Plus
1
3VA molded case circuit breakers
2
3VL molded case circuit breaker
13 Zone Selective Interlocking module
3
Electronic Trip Unit ETU / LCD ETU
14 Digital output module with relay contacts
4
COM800 breaker data server
15 Digital output module with relay contacts, configurable
5
COM100 breaker data server
16 Analog output module
6
COM20 Release 2 PROFIBUS module including Zone Selective Interlocking 17 Digital input module
7
BDA Plus with Ethernet interface
18 Powerconfig commissioning and service software V2.3 and higher
8
3WL air circuit breaker
19 PLC, e.g. SIMATIC S7
9
COM15 PROFIBUS module
20 E.g. SIMATIC powerrate
21 7KM PAC measuring devices
10 Breaker Status Sensor (BSS)
11 Electronic Trip Unit (ETU)
7
CubicleBUS
9
3VA-line
2
1
13
21
Siemens · 04/2018
5
© Siemens AG 2018
3WL1 Air Circuit Breakers
Introduction
11
Ethernet MODBUS TCP
6
7
8
10
RS 485 with MODBUS RTU
3VA-line
3VA-line
9
5
3
1
1
2
4
I201_19162
1
1
3VA molded case circuit breakers
7
COM100 breaker data server
2
3WL air circuit breaker
8
7KM PAC4200 measuring device
3
COM16 MODBUS module
9
7KM PAC3100 measuring device
4
3VL molded case circuit breaker
10 7KM PAC3200 measuring device
5
COM21 MODBUS module
11 Powerconfig commissioning and service software V2.3 and higher
6
COM800 breaker data server
Characteristics
• Coordinated communication concept using the PROFIBUS
DP or MODBUS, ranging from 16 A to 6300 A with 3VL molded
case circuit breakers and 3WL air circuit breakers
• The high level of modularity of circuit breakers and accessories allows easy retrofitting of all communication components
• Significant additional benefits for the switchboard due to the
possibility of linking up external input and output modules to
the circuit breaker-internal CubicleBUS of the 3WL air circuit
breaker
• Innovative software products for parameterization, operation,
monitoring, and diagnostics of circuit breakers, both locally or
via PROFIBUS DP, MODBUS or Ethernet/Intranet/Internet
• Complete integration of the circuit breakers into the Totally
Integrated Power and Totally Integrated Automation solutions
6
Siemens · 04/2018
Communication:
• For air circuit breakers with optional communication function
(ETU45B or ETU76B Electronic Trip Units), see Catalog LV 10.
• For accessories, see Catalog LV 10.
• For more information, see also Catalog LV 10, chapters
"Measuring Devices and Power Monitoring" and "Software".
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Introduction
■ Benefits
• Measured values are the basis for efficient load management,
for drawing up power demand profiles and for allocating
energy to cost centers
• Preventive maintenance reduces the risk of expensive plant
downtimes
• Metering function with a very wide range of measured values,
such as current, voltage, energy, power, etc.
• Can be used in 690 V networks
Low space requirements
The 3WL air circuit breakers require very little space. Size I
devices (up to 2000 A) fit into a 400 mm wide switchboard panel.
Size III devices (up to 6300 A) are the smallest of their kind and
with their construction width of 704 mm fit into an 800 mm wide
switchboard panel.
■ Application
Modular design
Components such as auxiliary releases, motorized operating
mechanisms, Electronic Trip Units, current sensors, auxiliary
circuit signaling switches, automatic reset devices, interlocks
and engagement operating mechanisms can all be exchanged
or retrofitted at a later stage, thus allowing the circuit breaker to
be adapted to new, changing requirements.
• As incoming-feeder, distribution, tie, and outgoing-feeder
circuit breakers in electrical installations.
• For switching and protecting motors, capacitors, generators,
transformers, busbars and cables.
When connected to an electronic I&C system, the air circuit
breakers offer a wide range of options for monitoring network
events.
The main contact elements can all be replaced in order to
increase the endurance of the circuit breaker.
Air circuit breakers belong to the SENTRON product family of
protection, switching, measuring and monitoring devices and
can be used in applications between 16 A and 6300 A.
Retrofittable modules for Electronic Trip Units
Modularity is one of the main features of the new 3WL air circuit
breakers.
Special LCDs, ground-fault modules, rating plugs and communication modules for the Electronic Trip Units are available for
fast and easy retrofitting and adaptation to changing requirements.
The AC devices are available as circuit breakers and
non-automatic air circuit breakers. DC devices are only available
as non-automatic air circuit breakers.
Standards
Communication/metering functions
The use of modern communication-capable circuit breakers
opens up completely new possibilities in terms of start-up,
parameterization, diagnostics, maintenance and operation. This
allows many different ways of reducing costs and improving
productivity in industrial plants, buildings and infrastructure
projects to be achieved:
• Fast and reliable parameterization
• Timely information and response can prevent plant stoppages
• Effective diagnostics management
3WL air circuit breakers comply with:
• IEC 60947-2
• IEC 60947-2 Annex F / CISPR 11/22 Class B
• Climate-proof according to IEC 60068-2-30.
Versions with UL 489 also available, see Catalog LV 16.
Conductor cross-sections for AC
Size
Type
Permissible load
for withdrawable
versions
at rear horizontal
main circuit
connections
• Up to 55 C
(Cu bare)
• Up to 60 C
(Cu bare)1)
• Up to 70 C
(Cu painted black)1)
Main conductor
minimum
cross-sections
• Copper bars,
bare
• Copper bars,
painted black
I
Up to
3WL11 10
A 1000
A 1000
A 1000
II
3WL11 12 3WL11 16 3WL11 20 3WL12 08 3WL12 10 3WL12 12 3WL12 16 3WL12 20
1250
1250
1210
1600
1600
14902)
2000
1930
1780
800
800
800
1000
1000
1000
1250
1250
1250
1600
1600
1600
2000
2000
2000
Unit(s) 1 ×
mm2 60 × 10
2×
40 × 10
2×
50 × 10
3×
50 × 10
1×
50 × 10
1×
60 × 10
2×
40 × 10
2×
50 × 10
3×
50 × 10
Unit(s) 1 ×
mm2 60 × 10
2×
40 × 10
2×
50 × 10
3×
50 × 10
1×
50 × 10
1×
60 × 10
2×
40 × 10
2×
50 × 10
3×
50 × 10
Size
II
Type
3WL12 25 3WL12 32 3WL12 403) 3WL13 40 3WL13 50 3WL13 633)
Permissible load
for withdrawable
versions
at rear horizontal
main circuit
connections
• Up to 55 C
(Cu bare)
• Up to 60 C
(Cu bare)1)
• Up to 70 C
(Cu painted black)1)
Main conductor
minimum
cross-sections
• Copper bars,
bare
• Copper bars,
painted black
III
3200
3020
2870
39504)
3810
3600
4000
4000
4000
5000
5000
5000
5920
5810
5500
Unit(s) 2 ×
mm2 100 × 10
3×
100 × 10
4×
120 × 10
4x
100 x 10
6x
100 x 10
6x
120 x 10
Unit(s) 2 ×
mm2 100 × 10
3×
100 × 10
4×
100 × 105)
4×
100 × 10
6×
100 × 10
6×
120 × 10
A 2500
A 2500
A 2280
1)
ETU76B with graphics display can be used up to max. 55 C.
2)
At breaking capacity H: 1600 A up to 70 C
3)
With rear vertical connections
4)
Size II, 3-pole, in fixed-mounted version
5)
Minimum main conductor cross-sections for 4-pole withdrawable circuit
breakers: 4 × 120 mm × 10 mm
Siemens · 04/2018
7
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
General data
■ Design
Circuit breaker
rated current n max (A)
Breaking capacity
cu at 500 V AC (kA) or
cc at 300 V DC (kA)
Size III
6300
5000
H
100
4000
C
150 (3p)
130 (4p)
Dimensions
Fixed-mounted,
3-/4-pole
Withdrawable
3-/4-pole
704 / 914
704 / 914
Width
434 / 434
460 / 460
Height
291 / 291
385 / 385
Depth
460 / 590
460 / 590
Width
434 / 434
460 / 460
Height
291 / 291
385 / 385
Depth
320 / 410
320 / 410
Width
434 / 434
460 / 460
Height
291 / 291
385 / 385
Depth
4000
3200
Size II
2500
2000
1600
DC
N
S
H
30
66
80
100
1250
1000
800
2000
Size I
1600
1250
1000
DC
N
S
H
20
55
66
85
800
630
The dimension for the depth of the circuit breaker is from the circuit breaker rear to the inner surface of the closed switchgear door.
Overview of 3WL circuit breakers/non-automatic air circuit breakers
Versions
•
•
•
•
Rated currents: 630 A to 6300 A
3 sizes for different rated current ranges (see diagram above)
3 and 4-pole versions
Rated operational voltage up to 690 V AC and 1000 V DC.
Special versions up to 1000 V AC and 1150 V AC available
• 4 different breaking capacities from 55 kA to 150 kA for AC
applications and one breaking capacity for DC applications
The 3WL circuit breakers are supplied complete with operating
mechanism (manual operating mechanism with mechanical
closing), Electronic Trip Unit and auxiliary switches
(2 NO contacts + 2 NC contacts in the standard version), and
can be equipped with auxiliary releases.
Installation methods
Fixed-mounted or withdrawable versions
Ambient temperatures
3WL circuit breakers are suitable for use in any climate in
accordance with IEC 60068-2-30. They are intended for use in
enclosed rooms in which no severe operating conditions (such
as dust, caustic vapors, hazardous gases) prevail.
When installed in dusty and damp areas, suitable enclosures
must be provided.
NSE0_00887q
Coordinated dimensions
The dimensions of 3WL circuit breakers only differ in terms of the
width of the device which depends on the number of poles and
the size.
Due to the nature of the design, the dimensions of devices with
a withdrawable version are determined by the dimensions of the
guide frames, which are slightly larger.
Non-automatic air circuit breakers
One special version of circuit breaker is utilized as a non-automatic air circuit breaker. The non-automatic air circuit breakers
are designed without an electronic trip system and do not
perform any protection functions for the plant.
One potential application is the use as a tie-breaker in systems
with parallel infeeds.
The versions and features can be selected according to those of
the circuit breakers.
Operating mechanisms
The circuit breakers are available with various optional operating
mechanisms:
• Manual operating mechanism with mechanical closing
(standard design)
• Manual operating mechanism with mechanical and electrical
closing
• Motorized operating mechanism with mechanical and
electrical closing
The operating mechanisms with electrical closing are suitable
for synchronization tasks.
8
Siemens · 04/2018
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
General data
Safety and reliability
To protect the circuit breakers and system against unauthorized
switching and to protect the maintenance and operator personnel, the system contains many locking devices. Others can be
retrofitted.
Front connection with
single hole or double hole
Horizontal
connection
NSE0_00979a
NSE0_00969b
NSE0_00967b
NSE0_00968b
Fixed-mounted circuit breakers
Vertical
connection
Horizontal
connection
Front connection with
single hole or double hole
Vertical
connection
NSE0_00973b
NSE0_00972b
NSE0_00971b
NSE0_00967b
NSE0_00970b
Withdrawable circuit breaker, withdrawable guide frame
Flange
connection
Main circuit connections – connection types
Main circuit connections
All circuit breakers are equipped with horizontal main circuit
connections on the rear for up to 5000 A as standard (horizontal
connection to busbars). Exception: Circuit breakers of size II
with max. rated current 4000 A.
Circuit breakers with a max. rated current of 6300 A and circuit
breakers of size II with a max. rated current of 4000 A are
equipped with vertical main circuit connections
(for upright busbars).
Connection using
screw connection
method (SIGUT)
(standard)
NSE0_00976b
NSE0_00975b
The following options are available, with all combinations
of top and bottom connections possible:
• Accessible from the front, single hole (for vertically installed
busbars)
• Accessible from the front, double hole (holes according to
DIN 43673) (for vertically installed busbars)
• At the rear, vertical (for vertically installed busbars)
• Connecting flange (for direct connection to guide frames up to
4000 A)
Screwless
connection method
(tension spring)
(optional)
Connection options for auxiliary circuit connections
Auxiliary circuit connections
The type of connection for the auxiliary switches depends on the
type of installation:
• Withdrawable version: The internal auxiliary switches are
connected to the male connector on the switch side. When
fully inserted, the connector makes a connection with the
sliding contact module (see the graphic "Guide frame" under
"Design") in the guide frame. Various adapters can then be
used to complete the wiring (see the graphic "Connection
options for auxiliary circuit connections").
• Fixed-mounted version: In this case the auxiliary supply
connectors are engaged directly onto the circuit breaker. The
connectors are equipped with coding pins that prevent them
being mistakenly interchanged
Operator panel
The operator panel is designed to protrude from a cutout in the
door providing access to all control elements and displays with
the control cabinet door closed.
The operator panels for all circuit breakers (fixed-mounted/
withdrawable versions, 3-/4-pole) are identical. The operator
panel ensures degree of protection IP41.
Other safety features include:
• Infeed from above or below, as required
• Locking of the guide frame with the circuit breaker removed,
as standard
• Locking of the withdrawable circuit breaker against
movement, as standard
• High degree of protection with cover IP55
• Mechanical reclosing lockout after overload or short-circuit
tripping as standard
• The circuit breaker is always equipped with the required
number of auxiliary supply connectors
Standard version
3WL circuit breakers are equipped with the following features as
standard:
• Mechanical ON and OFF button
• Manual operating mechanism with mechanical closing
• Switching position indication
• Ready-to-close indicator
• Store status indicator
• Auxiliary switch 2 NO + 2 NC
• Rear horizontal main circuit connections for fixed-mounted
and withdrawable versions up to 5000 A,
and rear vertical main circuit connections for 6300 A
applications and size II with 4000 A
• For 4-pole circuit breakers, the fourth pole (N) is installed on
the left and is 100% loadable with the rated current
• Contact erosion indicator for the main contacts
• Auxiliary circuit plug-in system with SIGUT screw terminals
Delivery inclusive of all auxiliary supply connectors as per
internal equipment including coding device for the prevention
of incorrect installation of auxiliary supply connectors for
fixed-mounted circuit breakers
• Mechanical "tripped" indicator for electronic trip system
• Mechanical reclosing lockout after tripping operation
• Operator panel cannot be taken off with the circuit breaker in
the ON position
Additional features of the withdrawable version:
• Main contacts:
Laminated receptacles in the guide frame,
blade contacts on the withdrawable circuit breaker
• Position indicator in the operator panel of the withdrawable
circuit breaker
• Captive manual crank handle for moving the withdrawable
circuit breaker
• Guide frame with guide rails for easy moving of the
withdrawable circuit breaker
• The withdrawable circuit breaker can be locked to prevent it
being pushed out of position
• The withdrawable circuit breaker cannot be moved when it is
in the ON position
• Coding of the rated current between the guide frame and the
withdrawable circuit breaker
Standards
3WL circuit breakers comply with:
• IEC 60947-2
• Climate-proof according to IEC 60068-2-30.
Versions acc. to UL 489 also available, see Catalog LV 16.
For further standards, see
www.siemens.com/lowvoltage/product-support or
www.siemens.com/lowvoltage/configurators.
Siemens · 04/2018
9
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
General data
Withdrawable short-circuit, grounding, and bridging units
Undervoltage releases
Portable positively-driven grounding and short-circuit devices
are used for the disconnected system sections to verify isolation
from the supply at the workplace.
The undervoltage release causes the circuit breaker to be
opened if the operational voltage falls below a certain value or is
not applied. The circuit breaker cannot be closed manually or by
means of an electrical ON command if the undervoltage release
is not connected to the operational voltage. The undervoltage
release has no delay as standard. A delay can be set by the
customer in the range between td < 80 ms and td < 200 ms.
Withdrawable grounding units allow simple and comfortable
grounding. They are simply inserted into the guide frames in
place of the corresponding withdrawable circuit breakers. This
ensures that these devices are always first connected with the
grounding electrode and then with the components to be
grounded.
The grounding contacts are fitted to the side of the breaker
enclosure and establish the connection when inserted into the
guide frame.
Short-time current of the
grounding contact
kA 15 (500 ms)
Rated operational voltage
V
1000 (690 for size I)
DIN VDE 0683
Standards
All withdrawable contacts are short-circuited and grounded on
delivery.
Electrically skilled persons can easily convert them to
withdrawable bridging units by following the enclosed
instructions.
In addition, the withdrawable unit can be adapted to various
rated currents of one size.
Withdrawable short-circuit and grounding unit
The withdrawable short-circuit and grounding unit consists of a
breaker enclosure with blade contacts which are connected with
the short-circuiting link.
Depending on the version, the short-circuiting links are arranged
at the top or bottom. The grounding and short-circuit
connections are established when the device is inserted.
It must be ensured that the side to be short-circuited and
grounded is not live. For this reason it is recommended that the
withdrawable unit is only cranked in when the door is closed.
Withdrawable bridging unit
In addition, an undervoltage release with a delay in the range
from 0.2 to 3.2 s is available.
Closing coil
The closing coil is used to close the circuit breaker electrically
by means of a local electrical "ON" command or by remote
means.
Motorized operating mechanism
The operating mechanism is used to charge the spring energy
store automatically.
The operating mechanism is activated if the spring energy store
has been discharged and the control voltage is available.
It is switched off automatically after charging. This does not
affect manual operation of the spring energy store.
Indicators, signals and control elements
Motor cutout switch
Selector switch for switching off the motorized operating
mechanism (automatic charging).
Operating cycles counter
The motorized operating mechanism can be supplied with a
5-digit operating cycles counter. The display is incremented
by "1" as soon as the spring energy store is fully charged.
Resetting of the manual tripped signal
When the circuit breaker has tripped, this is indicated by the
protruding red mechanical tripped indicator on the ETU. When
the mechanical tripped indicator is activated, the tripping
solenoid and tripped signal are reset. If this manual display is to
be reset remotely, the reset button can be equipped with a reset
solenoid.
The withdrawable bridging unit consists of a breaker enclosure
in which all disconnection components and the operating
mechanism have been replaced with simple connections
between the upper and lower contacts.
This option allows the circuit breaker to be reset both manually
and electrically.
Auxiliary releases
When the ETU is tripped, reclosing of the circuit breaker is
prevented until the trip unit is either electrically or manually reset.
If the "Automatic resetting of reclosing lockout" option is used,
the pre-tensioned circuit breaker is ready to close immediately
after tripping. Resetting the manual "tripped" indicator is not
included in this option.
Up to two auxiliary releases can be installed at the same time.
The following are available for selection:
1 shunt release
or 1 undervoltage release
or 2 shunt releases
or 1 shunt release
+ 1 undervoltage release
Automatic resetting of reclosing lockout
Tripped signaling switch
One signaling contact is used for each auxiliary release to
determine the positions of the auxiliary releases.
If the circuit breaker has tripped due to an overload, shortcircuit, ground fault or extended protection function, the tripped
signaling switch can indicate this. This signaling switch is
available as an option. If the circuit breaker is used for
communication, this option is supplied as standard.
Shunt releases
Ready-to-close signaling switch
When the operational voltage is connected to the shunt release,
the circuit breaker is opened immediately. The shunt release is
available in the versions 5% OP for overexcitation and 100% OP
for permanent excitation. This means that it is also possible to
block the circuit breaker against being jogged into closing.
The 3WL circuit breakers are equipped with an optical ready-toclose indicator as standard. In addition, the ready-to-close
status can be transmitted by means of a signaling switch as an
option. If the switch is used for communication, this signaling
switch is supplied as standard.
Signaling switches for auxiliary releases
An energy storage device for shunt releases allows the circuit
breaker to be opened even if the control voltage is no longer
available.
10
Siemens · 04/2018
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
General data
Circuit breakers
28
1
2
3
4
1
2
27
26
3
4
25
5
24
6
23
7
22
21
8
20
9
10
19
11
18
17
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
12
13
16
14
NSE0_00965b
15
23
24
25
26
27
28
Arc chute
Carrying handle
Labeling plates
Motor cutout switch (option) or
"Electrical ON" (option)
Type plate for circuit breaker
Spring charge indicator
"Mechanical ON" button
Rated current indication
Positioning pictogram
Operating cycles counter (option)
Hand-operated lever
Crank handle
Withdrawable unit drive shaft
Equipment plate
Grounding connection
Position indicator
Table for ground-fault protection
Safety lock for crank handle (option)
Mechanical unlocking of crank handle
(option)
Electronic trip unit
Rating plug
"Mechanical OFF" button or
"EMERGENCY-STOP"
mushroom pushbutton (option)
Ready-to-close indicator
Contact position indicator
"Tripped" indicator (reset button)
"Secure OFF" locking device (option)
Operator panel
Male connector for auxiliary connections
Guide frames
1
2
18
3
17
4
1
2
3
4
5
6
7
8
9
10
11
5
6
16
7
15
14
8
13
12
13
14
15
16
17
18
Arc chute cover (option)
Blow-out openings
Opening for crane hook
Shutter (option)
Locking device (shutter) (option)
Type plate for guide frame
Isolating contacts
Ground terminal Ø14 mm
Locking device for racking rail
Locking device against movement when
cabinet door is open (option)
Door interlock for guide frame (option)
Racking rail
Factory-set rated current coding
Sliding contact for breaker grounding (option)
Equipment-dependent coding (option)
Shutter actuator (option)
Position indicator switch (option)
Sliding contact module for auxiliary
conductors (number depends on equipment)
12
9
11
10
NSE0_00966b
Siemens · 04/2018
11
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
General data
Locking devices
Sealing devices
Locking device in OFF position
Sealing cap for "Electrical ON" button
This function prevents closing of the circuit breaker and
complies with the requirements for main control switches
according to EN 60204 (VDE 0113) – supply disconnecting
device. This lockout only affects this circuit breaker.
The "Electrical ON" button is equipped with a sealing cap as
standard.
If the circuit breaker is replaced, closing is no longer prevented
unless the new circuit breaker is also protected against
unauthorized closing.
The locking set contains covering caps which can be sealed.
To activate the locking device, the circuit breaker must be
opened. The locking device is disabled when the circuit breaker
is closed. The lock is only activated when the key is removed.
The safety key can be removed only in the "OFF" position.
Sealing cap for "Mechanical ON" and "OFF" button
Sealing device for Electronic Trip Units
The transparent cover can be sealed. The parameter setting
sections are covered to prevent unauthorized access. Openings
allow access to the query and test button.
Locking mechanisms
Locking device for "Electrical ON"
(see graphic "Circuit breakers")
Locking mechanism against movement for withdrawable circuit
breakers when the control cabinet door is open
This prevents unauthorized electrical closing from the operator
panel. Mechanical closing and remote closing remain possible.
The lock is only activated when the key is removed.
The crank handle is blocked when the control cabinet door is
open and cannot be removed. The withdrawable circuit breaker
cannot be moved. The lock only affects the inserted crank
handle.
Locking device for "Mechanical ON"
(see graphic "Circuit breakers")
This prevents unauthorized mechanical closing. The mechanical
ON button can only be activated if the key is inserted (key
operation). Closing with the "Electrical ON" button and remote
closing remain possible. The lock is only activated when the key
is removed.
"Safe OFF" circuit breaker-independent locking device against
unauthorized closing
This special breaker-independent function for withdrawable
circuit breakers prevents closing and fulfills the requirements for
main control switches to EN 60204 (VDE 0113) – supply disconnecting device. Unauthorized closing remains impossible even
after the circuit breaker has been replaced.
To activate the lock, the circuit breaker must be opened. The
locking device is disabled when the circuit breaker is closed.
The lock is only activated when the key is removed. The safety
key can be removed only in the "OFF" position.
Locking device for crank handle
Prevents removal of the crank. The circuit breaker is protected
against movement. The lock is only activated when the key is
removed.
Locking device for "Mechanical OFF"
Prevents unauthorized mechanical opening from the operator
panel. The "Mechanical OFF button" can only be activated if the
key is inserted (key operation). Remote opening remains
possible. The lock is only activated when the key is removed.
Locking device for hand-operated lever
The hand-operated lever can be locked with a padlock. The
spring energy store cannot be charged manually.
Locking device against resetting the "tripped" indicator
A lockable cover prevents manual resetting of the "tripped"
indicator after tripping due to overcurrent. This locking device is
supplied together with the transparent cover option for
Electronic Trip Units.
12
Siemens · 04/2018
Locking of the control cabinet door
The control cabinet door cannot be opened if
• the fixed-mounted circuit breaker is closed (the blocking
signal is transmitted via the Bowden cable) or
• the withdrawable circuit breaker is in the connected position
Blocking mechanism using "Mechanical ON" and "OFF" button
The "Mechanical ON" and "OFF" buttons are covered with a cap
which only allows actuation with a tool. These cover caps are
part of the interlocking set.
Optional equipment for guide frames
Shutters
The sealing strips of the shutter seal the laminated contacts of
the guide frame when the withdrawable circuit breaker is
removed and therefore implement touch protection.
The sealing strips can be manually opened using the strip
levers.
The position of the sealing strips can be locked in various
positions using padlocks for securing against tampering.
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
General data
Rated current coding unit between circuit breaker and guide
frame
Equipment-dependent coding
Withdrawable circuit breakers and guide frames are equipped
with a rated current coding unit as standard.
This ensures that only circuit breakers whose blade contacts are
suited to the laminated contacts of the guide frame can be
inserted into a guide frame (see diagram below).
Withdrawable circuit breakers and guide frames can be
retrofitted with an equipment-dependent coding unit.
This allows different designs of circuit breakers and guide
frames to be uniquely assigned. If the circuit breaker and guide
frame have been assigned different codes, the circuit breaker
cannot be inserted.
NSE0_01031b
36 different coding options can be selected.
Position signaling switches for guide frame
The guide frame can be equipped with position signaling
switches. These can be used to determine the position of the
circuit breaker in the guide frame.
1
Two versions are available:
• Option 1
Connected position
1 CO contact,
Test position
1 CO contact,
Disconnected position 1 CO contact
• Option 2
Connected position
3 CO contacts,
Test position
2 CO contacts,
Disconnected position 1 CO contact
1 Guide frame, interior left-hand side;
interior right-hand side similar
2 Coding pin on racking rail
in guide frame
3
3 Racking rail
NSE0_01032b
2
4
4 Withdrawable circuit breaker
right-hand side; left-hand side similar
5
5 Coding pin on guide frame
Rated current coding unit between circuit breaker and guide frame
Positions of the withdrawable circuit breaker in the guide frame
Representation
Maintenance position
2
Position indicator
CONNECT
Main circuit
Auxiliary circuit
Cabinet door
Shutter
Disconnected
Disconnected
Open
Closed
Disconnected
Disconnected
Closed
Closed
Disconnected
Connected
Closed
Closed
Connected
Connected
Closed
Open
1
TEST
4
DISCON
NSE0_01033a
NSE0_01037
1 Auxiliary circuit
2 Main circuit
4 Shutter
Disconnected position
CONNECT
3
TEST
NSE0_01034a
DISCON
NSE0_01038
3 Control cabinet
door
Test position
CONNECT
TEST
DISCON
NSE0_01035a
NSE0_01039
Connected position
CONNECT
TEST
NSE0_01036a
DISCON
NSE0_01040
Phase barriers
The plant engineering company can manufacture phase
barriers made of insulating material for the arcing fault barriers.
The rear panel of the fixed-mounted circuit breakers or guide
frames are equipped with guide grooves.
Door sealing frame and cover
3WL circuit breakers have degree of protection IP20 as
standard. However, if the switchboard is to be equipped with a
higher degree of protection, a door sealing frame with IP41 and
a cover with IP55 are available.
Arc chute cover
The arc chute cover is available as optional equipment for the
guide frame. It protects switchboard components which are
located directly above the circuit breaker.
Siemens · 04/2018
13
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
General data
NSE0_00880b
NSE0_00881b
NSE0_00882b
■ Function
R
R
s d
s d
J
J
s d
J
ETU15B
g
N S E 0 _ 0 0 9 5 2 b
N S E 0 _ 0 0 9 5 1 b
NSE0_00950c
ETU25B
ETU27B
Functions of the Electronic Trip Units
Basic protection functions
Overload protection
L
✔
✔
✔
Short-time delayed short-circuit protection
S
--
✔
✔
Instantaneous short-circuit protection
I
✔
✔
✔
Neutral conductor protection
N
--
--
✔
Ground-fault protection
G
--
--
✔
Neutral conductor protection (can be switched on/off)
--
--
✔
N-conductor protection adjustable
--
--
--
Short-time delay short-circuit protection (can be switched on/off)
--
--
--
Additional functions
Instantaneous short-circuit protection (can be switched on/off)
--
--
--
Thermal memory can be switched on/off
--
--
--
Load monitoring
--
--
--
Short-time delay short-circuit protection switchable to I2t
--
--
--
Instantaneous short-circuit protection adjustable
✔
--
--
Overload protection switchable to I4t
--
--
--
Overload protection can be switched on/off
--
--
--
Selectable parameter sets
--
--
--
Parameterization through rotary coding switches (10 steps)
✔
✔
✔
Parameterization through communication (absolute values)
--
--
--
Parameterization through user interface of ETU (absolute values)
--
--
--
Parameterization and display
Parameterization of the extended protection functions
--
--
--
LCD alphanumerical
--
--
--
LCD graphical
--
--
--
--
--
--
CubicleBUS
--
--
--
Communication through PROFIBUS DP
--
--
--
Communication through MODBUS
--
--
--
--
--
--
Metering function
Metering function Plus
Communication
Communication via Ethernet
✔ Standard
-- Not available
❑ Optional
Note
Detailed information about the functions of the Electronic Trip Units is given in the following.
14
Siemens · 04/2018
s d
g
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
General data
ETU76B
Rating Plug
NSE0_00886c
NSE0_00883b
12
=
IR
IR
tR
tR
Ig
tg
Isd
t sd
Ii
NSE0 00953a
Ig
tg
Isd
t sd
Ii
NSE0 00953a
ETU45B
ETU76B
✔
✔
✔
✔
✔
✔
✔
✔
❑
❑
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
--
✔
--
✔
✔
--
--
✔
--
✔
❑
❑
❑
--
--
✔
❑
❑
✔
✔
❑
❑
❑
❑
❑
❑
Siemens · 04/2018
15
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
General data
Electronic Trip Units (ETU)
The Electronic Trip Unit is controlled by a microprocessor and
operates independently of an auxiliary voltage. It enables
systems to be adapted to the different protection requirements
of distribution systems, motors, transformers and generators.
Tripped indicator/
Reset button
LCD alphanumeric
with 15° inclination
and rotatable
through 180°
Communication capability
The international standardized PROFIBUS DP or MODBUS can
be used to transmit data such as current values, switching
states, causes of tripping etc. to central computers.
Data acquisition and energy management are possible in
conjunction with the Plus metering function.
An internal circuit breaker data bus allows switchboard panel
communication between the circuit breaker and typical
secondary devices in the circuit breaker section:
• Control of analog displays
• Facility to test the communication build-up with circuit
breakers
• Display of tripping state and tripping reasons
• Input module for reading in further switchboard panel signals
and for transmission of these signals to the PROFIBUS DP or
MODBUS
• Various output modules for displaying measured values
Slide switch for
selectable overload
characteristic
Rating plug
Ground-fault
protection
module
(retrofittable)
Example of configuration for ETU45B
This means that it is not only possible to monitor the device
remotely, but also to transmit current values from the entire
system and perform switching operations remotely.
I2t and I4t characteristic curves for overload protection
The best protection for the whole switchboard is achieved by
setting the tripping characteristic curve to an optimum value.
In order to achieve optimal discrimination for upstream fuses or
medium-voltage protection systems, the inclination of the
characteristic curve can be selected for the overload range.
The overload protection L (long time protection) for the ETU45B
and ETU76B Electronic Trip Units allows the curve to be
switched between the I2t and I4t characteristics.
The I4t characteristic improves discrimination for downstream
circuit breakers and fuses.
Electronic Trip Units ETU
High emphasis has also been placed on modularity during the
development of the Electronic Trip Units. These are some of the
modules which can be easily retrofitted at any time:
• Ground-fault protection module
• Communication
• Metering function
• Display
• Rating plug
This allows quick adaptation to new local power supply
conditions. In addition, innovative functions have been included
in the ETUs.
Rating plug
The rating plug is an exchangeable module which allows the
user to reduce the rated device current so as to adapt it
optimally to the plant; e.g. if a new plant section is put into
operation. The rating plug must be selected to correspond to the
rated current of the plant.
16
Siemens · 04/2018
Metering function Plus
Selectable parameters
In the case of quick changes of power supply conditions,
e.g. for switchover from transformer to generator operation or if
a section of the supply is disconnected when the shift changes,
3WL circuit breakers allow the relevant protection parameters to
be quickly adapted to the new conditions.
The ETU76B contains two independent tripping characteristics
(parameter sets). The switchover is completed within 200 ms
and is performed with the help of an external signal.
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
General data
ETU15B Electronic Trip Unit
Application:
Option: safety lock
prevents pressing of
reset button after
overcurrent release
Mechanical RESET
for reclosing lockout
and mechanical
tripped indicator
Indicator: overcurrent
release activated
Indicator: fault in
overcurrent release
Indicator: overload alarm
Rotary switch for setting
value, overload release
Simple building and system protection without
time-selective coordination up to 4000 A.
Not to be used for size III.
Properties:
• Adjustable overload protection with I2t characteristic with
non-adjustable delay time tR = 10 seconds at 6 × IR
• Instantaneous short-circuit protection adjustable
in the range 2 ... 8 × In
• Overload display
• Protection function is set by means of the rotary coding
switch
For technical details, see the table "Function overview of the
electronic trip system" under "Technical specifications".
Rotary switch for setting
value, instantaneous
short-circuit release
NSE0_00954b
Sealing ring
Test socket
ETU25B Electronic Trip Unit
Application:
Option: safety lock
prevents pressing of
reset button after
overcurrent release
Mechanical RESET
for reclosing lockout
and mechanical
tripped indicator
Indicator: overcurrent
release activated
Indicator: overload alarm
ETU25B
Indicator: fault in
overcurrent release
Rating Plug
Rated current module
Rotary switch for setting
value, overload release
Indicator: cause of release
Rotary switch for setting
value, instantaneous
short-circuit release
Short-circuit protection
fixed setting
Rotary switch for delay,
short-circuit release
NSE0_00955b
Query pushbutton
Test pushbutton
Sealing ring
Clear pushbutton
Test socket
Classical building, motor and system protection with
time-selective coordination for up to 6300 A
Properties:
• Adjustable overload protection with I2t-characteristic
delay time tR = 10 seconds at 6 × IR
• Short-time delayable short-circuit protection adjustable
in the range 1.25 ... 12 × In and
• Instantaneous short-circuit protection non-adjustable
at 20 × In, max. 50 kA
• Can be adapted at any time to the required plant currents
through exchangable rating plug, thus ensuring overload
protection in the range from 100 A to 6300 A
• Overload display
• Indicates the cause of tripping by means of an LED
• Test facility for the trip unit
• Protection function is set by means of the rotary coding
switch
For technical details, see the table "Function overview of the
electronic trip system" under "Technical specifications".
Siemens · 04/2018
17
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
General data
ETU27B Electronic Trip Unit
Application:
Option: safety lock
prevents pressing of
reset button after
overcurrent release
Mechanical RESET
for reclosing lockout
and mechanical
tripped indicator
Classical building, motor and system protection with
time-selective coordination for up to 6300 A
NSE0_00956c
Properties:
Indicator: overcurrent
release activated
ETU27B
Indicator: overload alarm
N-conductor protection
on/off
OFF ON
Rating Plug
Indicator: fault in
overcurrent release
Rated current module
N
Rotary switch for setting
value, overload release
Indicator:
cause of release
Rotary switch for setting
value, instantaneous
short-circuit release
The same as ETU25B but also
• Connectable neutral conductor protection
• Permanently integrated ground-fault protection.
Calculation of the ground-fault current through vectorial
summation current formation
For technical details, see the table "Function overview of the
electronic trip system" under "Technical specifications".
Rotary switch for delay,
short-circuit release
Short-circuit protection
fixed setting
Rotary switch for setting
value, ground-fault protection
Sealing ring
OFF
Rotary switch for delay,
ground-fault protection
Query pushbutton
Test pushbutton
Clear pushbutton
Test socket
ETU45B Electronic Trip Unit
Mechanical RESET
for reclosing lockout
and mechanical
tripped indicator
Scroll down
Option: safety lock
prevents pressing of
reset button after
overcurrent release
Option: alphanumeric display
Indicators:
Overcurrent release
activated
Overload alarm
Scroll up
Indicator: fault in
overcurrent release
COMMUNICATION
EXPANDED
ETU45B
OFF ON
Rated current module
Rating Plug
=
Rotary switch for setting
value, overload release
1
1
1
1
1
Rotary switch for setting
value, short-circuit
protection
Selector for
ground-fault protection
Rotary switch for setting
value, ground-fault
protection
Rotary switch for setting
value, ground-fault alarm
Rotary switch for delay,
overload release
12
Rotary switch for setting
value, instantaneous
short-circuit release
Thermal memory on/off
N-conductor protection on/off
Setting value
N-conductor overload
Transfer of overload
characteristic 2 t / 4t
Rotary switch for delay,
short-circuit release
Indicator: cause of release
Sealing ring
Option: ground-fault module
SI
g
Indicator: ground-fault alarm
Indicator: ground-fault tripped
Rotary switch for delay,
ground-fault protection tg / 2 t g
Clear pushbutton
Test socket
Test pushbutton
Query pushbutton
NSE0_00957c
Application:
Low-cost highly versatile device for intelligent buildings and
all types of industrial applications – "CubicleBUS integrated"
Properties:
The same as ETU25B but also
• Adjustable time-lag class for overload protection
• Selectable characteristic for overload and short-time
delayed short-circuit range (current discrimination) for more
accurate discrimination adaptation to upstream fuses and
protective devices
• Thermal memory as restart protection for tripped motor
outgoing units
• Connectable and adjustable neutral conductor protection
• Modular ground-fault protection module with alarm and
tripping functions which can be adjusted separately
• Communication interface, Plus metering function, optional
connection of external modules or for retrofitting
• Storage of events and causes of tripping for specific fault
analysis
• Extended protection functions possible with metering
function
• Optional high-contrast display with viewing angle
adjustment option
• The protection functions can be set by means of a rotary
coding switch or slide switch
For technical details, see the table "Function overview of the
electronic trip system" under "Technical specifications".
18
Siemens · 04/2018
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
General data
ETU76B Electronic Trip Unit
Application:
Mechanical RESET
for reclosing lockout
and mechanical
tripped indicator
Option: safety lock
prevents pressing of
reset button after
overcurrent release
ETU76B
The multi-talent with graphical display for system analysis –
"CubicleBUS integrated"
Properties:
Indicators:
Overcurrent release
activated
Overload alarm
COMMUNICATION
EXPANDED
Graphical display
Indicator: fault in
overcurrent release
Indicator: cause of release
Rating Plug
Control keys for setting
the release parameters
Rated current module
Indicators:
Ground-fault alarm
Ground-fault tripped
Option: ground-fault module
Fields for noting
setting values
Fields for noting
setting values
Test pushbutton
Clear pushbutton
Query pushbutton
Test socket
The same as ETU45B but also including
• Two protection parameter sets which can be stored
separately in the trip unit (switchover is performed by means
of external signal)
• With overload protection which can be deactivated for use in
modern drive engineering applications
• Adjustable delay of delayed short-circuit protection
up to 4000 ms
• Neutral conductor protection adjustable up to IN = 200% In
• Setting of protection functions by means of Breaker Data
Adapter (BDA Plus) or via communications interface
• Graphical display of all parameters and events/curve trends
• Graphics display with high contrast, backlit display, and
sleep mode
For technical details, see the table "Function overview of the
electronic trip system" under "Technical specifications".
NSE0_00960b
Ground-fault protection
Selector for
ground-fault
detection
Indicators:
Ground-fault
tripped
Rotary switch
for setting
value,
ground-fault
protection
Rotary switch
for setting value
ground-fault alarm
Ground-fault
alarm
Rotary switch
for setting
value, groundfault protection
delay tg/ 2 tg
NSE0_00962
GFM AT 45B ground-fault module
Field for
noting
transfer
ground-fault
detection
Fields for
noting setting
values
Indicators:
Ground-fault releases "G" sense fault currents that flow to ground
and that can cause a fire in the plant. Multiple circuit breakers
connected in series can have their delay times adjusted so as to
provide graduated discrimination.
When setting the parameters for the Electronic Trip Unit it is
possible to choose between "alarm" and "trip" in the event that
the set current value is exceeded. The reason for tripping is
indicated by means of an LED when the query button is
activated.
The ETU45B and ETU76B Electronic Trip Unit versions can be
retrofitted with a ground-fault protection module. This groundfault protection function is integrated in ETU27B Electronic Trip
Units.
Ground-fault
alarm
Ground-fault
tripped
NSE0_00964a
Fields for
noting setting
values
GFM AT 55B-76B ground-fault module
Siemens · 04/2018
19
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
General data
Measurement method
Setting
Vectorial summation current formation (measurement method 1)
How the module is set depends on the measurement
method used (see above):
The three phase currents and the N-conductor current are
measured directly.
Measurement method 1: in position
.
The Electronic Trip Unit determines the ground-fault current by
means of vectorial summation current formation for the three
phase currents and the N-conductor current.
Measurement method 2: in position
Direct measurement of the ground-fault current
(measurement method 2)
Ground-fault protection with I 2t characteristic curve
A standard current transformer with the following data
is used for measurement of the ground-fault current:
1200 A/1 A, Class 1 (the internal load of the 3WL circuit breaker
is 0.11 ). The current transformer can be installed directly in the
grounded neutral point of a transformer.
With the exception of the ETU27B Electronic Trip Unit, all
versions of the ground-fault modules are supplied with
an I2t characteristic curve which can be activated.
T5
L1
L2
L3
N
PE
NSE0_00946a
3-pole circuit breakers, current transformers in the N-conductor
L1
L2
L3
N
T6
PE
T6: 1200 A/1 A
NSE0_00947
3-pole circuit breakers, current transformers in the grounded neutral
point of the transformer
L1
L2
L3
N
T6
PE
T6: 1200 A/1 A
NSE0_00948
4-pole circuit breakers, current transformers in the grounded neutral
point of the transformer
20
Siemens · 04/2018
.
This setting can be implemented for the Electronic Trip Unit
version ETU76B with Menu/Comm.
Selection criteria for 3WL circuit breakers
Basic criteria for selecting circuit breakers are:
• Max. short-circuit current at place of installation of circuit
breaker Ik max .
This value determines the short-circuit breaking capacity or
short-circuit current carrying capacity of the circuit breaker.
• It is compared with the value Icu, Ics, Icw of the circuit breaker
and essentially determines the size of the circuit breaker.
See Figure "Overview of 3WL circuit breakers/non-automatic
air circuit breakers".
• Rated current In that is to flow through the branch circuit. This
value must not be higher than the maximum rated current for
the circuit breaker.
The rated current for the 3WL circuit breaker is set with the
rating plug. See Figure "Overview of 3WL circuit breakers/
non-automatic air circuit breakers" under "Design".
• Ambient temperature for the circuit breaker.
This is usually the control cabinet's internal temperature.
• Design of the circuit breaker
• Minimum short-circuit current which flows through the
switching device. The trip unit must still detect this value as a
short-circuit and must respond by tripping.
Protection functions of the circuit breaker.
These are defined by selection of the corresponding Electronic
Trip Unit; see table "Functions of the Electronic Trip Units" under
"Functions".
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
General data
3WL circuit breakers for DC applications
This version of the 3WL non-automatic air circuit breaker is
suitable for direct current applications. The external protective
device DIGmat S100 provides adjustable overload and shortcircuit protection for the 3WL non-automatic air circuit breaker.
This is based on the measuring chain of a shunt resistor and the
DIGmat S100 tripping unit. Shunt resistors are available for
1000 A, 2000 A and 4000 A (special ranges on request).
They are in accordance with DIN 43703 and have a class
accuracy of 0.5.
A measuring-circuit voltage of 60 mV DC is picked off for the
rated current In.
The measuring-circuit voltage is a linear image of the primary
current.
DIGmat S100
The DIGmat S100 trip unit monitors the image of the primary
current thus supplied and compares it with the tripping
characteristic curve set on the device. The parameter settings
on the DIGmat S100 apply also for DC feedbacks.
Reversing duty is thus possible.
• Short-circuit protection:
Setting range Ii = 1.25 × IR to max. 4 × In
Tripping occurs in less than 50 ms if the set value is exceeded.
In
IR
tR
Ii
The tripping characteristic curve is determined and described
by the following variables:
• Overload protection:
Setting range IR = 0.4 ... 1.0 In
The characteristic curve has a I2t characteristic.
The tripping time tR is selectable between 2 and 10 s, with tR
defined for 6 × IR.
=
=
=
=
Rated current of the circuit breaker
Current setting value of the adjustable overload release
Assigned tripping time of the overload trip
Instantaneous tripping current of the adjustable
short-circuit release
The components are available only from the company
mat – Maschinen- und Anlagentechnik:
mat – Maschinen- und Anlagentechnik
Dr. Becker GmbH
Rudolf-Diesel-Straße 22
22941 Bargteheide
Tel.: +49 (4532) 20-2101
Fax: +49 (4532) 20-2121
Email: info@m-a-t.de
Internet: www.m-a-t.de
■ Configuration
• The bending radii of the Bowden cable must be > 500 mm
• The total bending angle across the length of the Bowden
cable must not exceed 640°
• If the circuit breakers to be interlocked are arranged vertically,
the interlock mechanisms must be aligned
• Circuit breakers to be interlocked must be arranged so that
Bowden cables can be optimally installed in compliance with
the conditions mentioned in the above points
• The installed Bowden cable must be fixed (with cable ties or
the like) before the interlock is adjusted
• Select the width of switchboard cubicle to allow enough
freedom of movement for adjusting the interlock!
• Openings and cutout sections in system elements must be
designed in such a way that the direction of the Bowden
cables is not changed and that the wires are not obstructed
when they are routed
Mutual mechanical circuit breaker interlocks
The module for mutual mechanical interlocking can be used for
two or three 3WL circuit breakers and can be adapted easily to
the corresponding versions. The fixed-mounted and
withdrawable circuit breaker versions are fully compatible and
can therefore be used in a mixed configuration in an installation.
This also applies to 3WN6 circuit breakers.
The circuit breakers can be mounted adjacent to each other or
one above the other, whereby the distance of the circuit breakers
is determined solely by the length of the Bowden cable
(lengths: 2 m/3 m/4.5 m). Interlock signals are looped through
using the Bowden cables. Interlocking is only effective in the
connected position in the case of withdrawable circuit breakers.
The mechanical endurance of the Bowden cables is
10000 operating cycles.
To ensure that the interlock functions properly, the following
minimum switchboard requirements must be fulfilled:
• Bowden cables must be laid so that they are as straight as
possible
Mutual mechanical interlocking of circuit breakers – examples
Mutual interlocking of two
circuit breakers
S1
S2
Interlocking of three circuit
breakers
S3
S1
S2
NSE0_01041
NSE0_01042
Mutual interlocking of three
circuit breakers
S1
S1
S2
NSE0_01043
S2
S3
Interlocking of three circuit
breakers, two of them mutual
S1
S3
S2
S3
NSE0_01044
NSE0_01045
Siemens · 04/2018
21
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
General data
Communication-capable circuit breakers
20
Ethernet
18
19
PROFIBUS
PROFINET
6
5
3VA-line
1
14
15
16
17
CubicleBUS
9
3VA-line
2
1
13
21
8
10
11
1
12
3
NSE0_01105
4
12 Metering function Plus
1
3VA molded case circuit breakers
2
3VL molded case circuit breaker
13 Zone Selective Interlocking module
3
Electronic Trip Unit ETU / LCD ETU
14 Digital output module with relay contacts
4
COM800 breaker data server
15 Digital output module with relay contacts, configurable
5
COM100 breaker data server
16 Analog output module
6
COM20 Release 2 PROFIBUS module including Zone Selective Interlocking 17 Digital input module
7
BDA Plus with Ethernet interface
18 Powerconfig commissioning and service software V2.3 and higher
8
3WL air circuit breaker
19 PLC, e.g. SIMATIC S7
9
COM15 PROFIBUS module
20 E.g. SIMATIC powerrate
21 7KM PAC measuring devices
10 Breaker Status Sensor (BSS)
11 Electronic Trip Unit (ETU)
Communication with PROFIBUS DP
22
Siemens · 04/2018
7
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
General data
11
Ethernet MODBUS TCP
6
7
8
10
RS 485 with MODBUS RTU
3VA-line
3VA-line
9
5
3
1
1
2
4
I201_19162
1
1
3VA molded case circuit breakers
7
COM100 breaker data server
2
3WL air circuit breaker
8
7KM PAC4200 measuring device
3
COM16 MODBUS module
9
7KM PAC3100 measuring device
4
3VL molded case circuit breaker
10 7KM PAC3200 measuring device
5
COM21 MODBUS module
11 Powerconfig commissioning and service software V2.3 and higher
6
COM800 breaker data server
Communication with MODBUS RTU
The requirements for power distribution in terms of communication capability, data transparency, flexibility and integration are
constantly increasing. An integrated and modular communication architecture was designed for the 3WL circuit breaker to
ensure that it can satisfy these requirements.
The core component of this architecture is the CubicleBUS,
which links together all of the intelligent components within the
3WL circuit breaker and enables the easy and safe connection
of other additional external components to the circuit breaker.
The CubicleBUS is already incorporated and connected in all
complete circuit breakers with ETU45B and ETU76B trip units.
The high modularity of the system allows retrofitting of communication functions (e.g. metering function) at any time. Similarly, a
non-communication-capable 3WL circuit breaker can be
upgraded (e.g. changeover from ETU25B to ETU45B with
CubicleBUS) easily on site in the plant. All modules connected
to the CubicleBUS can directly access the existing source data
of the circuit breaker, which guarantees the quickest possible
access to information and response to events.
Furthermore, additional external modules (including digital
inputs and outputs, analog outputs) can be connected to the
CubicleBUS to provide cost-effective solutions for the
automation of additional devices in the switchboard.
Siemens · 04/2018
23
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
General data
Communication-capable 3WL circuit breakers
Function
Electronic Trip Unit Breaker PROFIBUS Metering Analog
version
Status
communi- function output
module
ETU45B ETU76B Sensor cation port Plus
Digital Digital ZSI
Breaker
output input
module Data
module module
Adapter
Plus
Functions of the communication-capable 3WL circuit breakers
Indication of measured values in trip unit
(current only)
✓
✓
❏
❏
❏
❏
❏
❏
❏
❏
Indication of measured values in the trip unit
(U, I, P, S, Q, p.f., etc.)
✓
✓
❏
❏
✓
❏
❏
❏
❏
❏
Indication of measured values (current only),
parameters, diagnostic values etc. on display
--
✓
❏
❏
❏
❏
❏
❏
❏
❏
Indication of measured values (U, I, P, S, Q, p.f.,
etc.), parameters, diagnostic values, etc. in trip unit
--
✓
❏
❏
✓
❏
❏
❏
❏
❏
Output of measured values (current only)
to rotary coil instruments in control cabinet door
✓
✓
❏
❏
❏
✓
❏
❏
❏
❏
Output of measured values (U, I, P, S, Q, p.f., etc.)
to rotary coil instruments in control cabinet door
✓
✓
❏
❏
✓
✓
❏
❏
❏
❏
Output of digital signals (e.g. reason for tripping,
alarms, status) through contacts
✓
✓
❏
❏
❏
❏
✓
❏
❏
❏
Automatic changeover between
parameter sets A and B
--
✓
❏
❏
❏
❏
❏
✓
❏
❏
Read-in of digital signals and
forwarding to PROFIBUS/MODBUS
✓
✓
❏
✓
❏
❏
❏
✓
❏
❏
Transmission of breaker information
on HTML basis locally to a PC
✓
✓
✓
❏
❏
❏
❏
❏
❏
✓
Transmission of breaker information
on HTML basis through Ethernet
✓
✓
✓
❏
❏
❏
❏
❏
❏
✓
Short-time discrimination for
S tripping and G protection
✓
✓
❏
❏
❏
❏
❏
❏
✓
❏
Local display of harmonics analysis and waveform
memory
--
✓
❏
❏
✓
❏
❏
❏
❏
❏
Local storage of harmonics analysis and waveform
memory and transmission through PROFIBUS
✓
✓
✓
✓
✓
❏
❏
❏
❏
❏
Read-out of protection parameters
through PROFIBUS
✓
✓
✓
✓
❏
❏
❏
❏
❏
❏
Read-out and adjustment of protection parameters
through PROFIBUS
--
✓
✓
✓
❏
❏
❏
❏
❏
❏
✓
Required
❏ Not necessary for this function, optionally combinable
Function can optionally be adopted by several
trip units.
--
Function can optionally be adopted by one of these
modules.
24
Siemens · 04/2018
Function not available
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
General data
Data that can be transmitted over the PROFIBUS DP/MODBUS or the Breaker Data Adapter
All 3WL circuit breakers with ETU45B, ETU76B (CubicleBUS integrated)
Transmittable circuit breaker data
BSS
Order code (Article No. of circuit breaker + "-Z")
BDAPLUS BSS
F01
+ "BDAPLUS"Article No.
Article No.
COM15/COM16
F02/F12
Possible applications
Transmission of circuit breaker data to PROFIBUS DP or MODBUS and integration into
higher-level visualization systems possible
e.g. in PCS7, Power Management Systems, WinCC
(including add-ons like the text message radio server)
--
✔
Transmission of circuit breaker data and software (i.e. HTML pages with data) to a local output
device, or remotely through Ethernet/Intranet/Internet (without the possibility of integration into
higher-level visualization systems)
e.g. for monitoring, diagnostics, maintenance and parameterization of individual circuit breakers
✔
--
Utilization of the functionality of all CubicleBUS modules
e.g. configuration of the configurable digital output module, status check of the digital input modules,
diagnostics
✔
✔
✔
✔
--1)
✔
Operating states
On/Off status message, spring energy store, tripped, readiness
Breaker position (connected, test and disconnected position, removed) for withdrawable circuit breakers,
PROFIBUS/MODBUS write protection on/off, free user input, tripped signal
✔
--1)
--1)
✔
✔
✔
Control commands
Switch circuit breaker on/off, switch free user output on/off
Reset tripped signal
Delete event and history memory
Reset min./max. measured values, reset maintenance information
--1)
✔
--1)
✔
✔
✔
✔
✔
History
Read-out of event log, read-out of trip log
--1)
✔
Maintenance information
Number of tripping operations L, S/I and in total, contact wear
Number of operating cycles under load and in total, number of operating hours
✔
--1)
✔
✔
Event signals
Tripped signals with details of the tripping current
Alarm signals (e.g. overload) with incoming/outgoing information
All of the named event signals with time stamp
✔
--1)
--1)
✔
✔
✔
Parameterization of the protection functions
Read-out of the protection function parameters
Settings for the protection function parameters can be changed by means of communication
Parameter set switchover possible (set A to set B and back)
✔
✔ 2)
✔ 2)
✔
✔ 2)
✔ 2)
Measured values
Phase currents, each with min./max. value
Temperature in the circuit breaker with min./max. value
Temperature in the control cabinet with min./max. value
All of the named measured values with time stamp
✔
--1)
--1)
--1)
✔
✔
✔
✔
Transmittable circuit breaker data without integrated metering function
Device identification
Communication address, Article No. Circuit breaker in delivery state, circuit breaker parameters
(size, number of poles, rating plug etc.), identification numbers, trip unit type,
free text for plant code and comments
Metering function Plus
Order code F01+ ... or F02+ ...
F05
Additional transmittable circuit breaker data with integrated metering function
Additional event signals
Threshold value alarms (e.g. over/underfrequency, over/undervoltage)
✔
Parameterization of the extended protection functions and setpoints (threshold values)
Read-out of the parameters of the extended protection functions
Settings for the extended protection function parameters can be changed
Read-out and adjustment of threshold values
✔
✔
✔
Additional measured values
Voltages, power, energy, p.f., frequency, each with min./max. value
Harmonics analysis
Recording of currents and voltages for configurable events in the waveform memory
✔
✔
✔
1)
Data only available in conjunction with the COM15 module
(BUS connection not required).
2)
Only possible with ETU76B.
✔ Available
-- Not available
Siemens · 04/2018
25
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
General data
CubicleBUS modules
Digital output module with rotary coding switch
6 items of binary information concerning the state of the circuit
breaker (reasons for tripping and alarms) can be output via this
module to external signaling devices (e.g. LED, horn) or used for
the selective shutdown of other system components
(e.g. frequency converters).
Digital output modules are available in versions with and without
a rotary coding switch. On modules with a rotary coding switch
it is possible to choose between two signaling blocks each with
6 defined assignments and to set an additional response delay.
All the digital output modules are available as a version with
relay outputs (CO contacts, up to 12 A). Up to two modules of
this type can be connected to one 3WL circuit breaker.
Analog output module
Digital input module
With the digital input module, up to 6 additional binary signals
(24 V DC) in the circuit breaker environment can be connected
to the system. It is thus possible for example to send messages
concerning the state of a switch disconnector or a control
cabinet door to the PROFIBUS DP/MODBUS.
With the digital input module on the CubicleBUS it is also
possible for the two different protection parameter sets held in
the ETU76B Electronic Trip Unit trip unit to be switched over
automatically in a few milliseconds. It is thus possible,
for example, to automatically change the parameters of a
tie-breaker should the transformer infeed fail.
Digital output module with rotary coding switch
One module each of this type can be used for holding the six
items of digital information and for automatically switching over
the parameters.
Digital output module, configurable
The configurable output module is available for higher-performance solutions. With this module, random events on the
CubicleBUS can be switched directly to one of six available
outputs or three of these outputs can be assigned with up to six
events. In other words, up to six events can be placed on one
physical output with "OR" operation. Either BDA Plus or
powerconfig is used for configuring.
A relay variant is also available here the same as for the output
modules with rotary coding switch. Only one module of this type
is possible per 3WL circuit breaker.
Digital input module
ZSI module (short-time discrimination control)
The use of ZSI modules is recommended when Siemens circuit
breakers are arranged in several staggered levels but full
discrimination with the smallest possible delay is to be assured
nevertheless.
Digital output module, configurable
Analog output module
The analog output module can be used to output the following
measured values to analog indicators in the control cabinet
door:
• IL1, IL2, IL3, IN or
• UL12, UL23, UL31, UL1N or
• PL1, PL2, PL3, Stot or
• p.f.1, p.f.2, p.f.3, I % or
• favg, ULLavg, Ptot, p.f. avg
Four 4-20 mA/0-10 V interfaces are available for this. The
measured values to be output are selected with a rotary coding
switch. By using the analog output module it is possible to do
without additional converters and their conventional installation/
wiring in the main conducting path. Up to two modules of this
type can be connected to one 3WL circuit breaker.
26
Siemens · 04/2018
The circuit breakers are interconnected by these modules. In
case of a short-circuit, each affected circuit breaker interrogates
the circuit breakers directly downstream whether the shortcircuit has also occurred in the next, lower level. The short-circuit
is exactly localized as a result, and only the next upstream circuit
breaker in the energy flow direction is switched off.
ZSI module (short-time discrimination control)
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
General data
■ Technical specifications
Size
Type
Number of poles
Rated current In at 40 °C, at 50/60 Hz
Main conductor
N-conductor (only on 4-pole versions)
Rated operational voltage Ue at 50/60 Hz
(1000 V version, see Catalog LV 10 "Options")
Rated insulation voltage Ui
Rated impulse withstand voltage Uimp
• Main conducting paths
• Auxiliary circuits
• Control circuits9)
Isolating function acc. to EN 60947-2
Utilization category
Permissible ambient temperature
• During operation (in operation with LCD max. 55 °C)1)
• Storage
Permissible load for
• Up to 55 C (Cu bare)
withdrawable versions
• Up to 60 C (Cu bare)2)
at rear horizontal main circuit • Up to 70 C
connections
(Cu painted black)2)
Rated rotor operational voltage Uer
Power loss at In
With 3-phase symmetrical load
• Fixed-mounted circuit breakers
• Withdrawable circuit breakers
Switching times
• Make time
• Opening time
• Electrical make time (through closing coil)4)
• Electrical opening time (through shunt release)
I
II
... 3WL11 10 3WL11 12 3WL11 16 3WL11 20 3WL12 08 3WL12 10 3WL12 12 3WL12 16
3-pole, 4-pole
A ... 1000
A ... 1000
V AC ...
690/1000
V AC 1000
1250
1250
...
690/1000
1000
1600
1600
...
690/1000
1000
2000
2000
...
690/1000
1000
800
800
...
690/1000
1000
1000
1000
...
690/1000
1000
1250
1250
...
690/1000
1000
1600
1600
...
690/1000
1000
kV 12
kV 4
kV 2.5
Yes
B
12
4
2.5
Yes
12
4
2.5
Yes
12
4
2.5
Yes
12
4
2.5
Yes
12
4
2.5
Yes
12
4
2.5
Yes
12
4
2.5
Yes
C
C
A
A
A
–25/+70
–40/+70
1250
1250
1210
–25/+70
–40/+70
1600
1600
14903)
–25/+70
–40/+70
2000
1930
1780
–25/+70
–40/+70
800
800
800
–25/+70
–40/+70
1000
1000
1000
–25/+70
–40/+70
1250
1250
1250
–25/+70
–40/+70
1600
1600
1600
V 2000
2000
2000
2000
2000
2000
2000
2000
W 100
W 195
105
205
150
350
240
440
40
85
45
95
80
165
85
175
ms 35
ms 38
35
38
35
38
35
38
35
34
35
34
35
34
35
34
ms 80
ms 73
80
73
80
73
80
73
100
73
100
73
100
73
100
73
73
73
73
73
73
73
73
73
50
50
50
50
50
50
50
50
10 000
20 000
10 000
--20 000
10 000
20 000
10 000
--20 000
10 000
20 000
10 000
--20 000
10 000
15 000
7500
--15 000
10 000
15 000
7500
--15 000
10 000
15 000
7500
--15 000
10 000
15 000
7500
--15 000
10 000
15 000
7500
--15 000
10 000
15 000
7 500
1000
-15 000
10 000
15 000
7 500
1000
-15 000
10 000
15 000
7 500
1000
-15 000
10 000
15 000
7500
1000
-15 000
10 000
15 000
7500
1000
500
15 000
10 000
15 000
7500
1000
500
15 000
10 000
15 000
7500
1000
500
15 000
10 000
15 000
7500
1000
500
15 000
10 000
15 000
7 500
1000
-10 000
10 000
15 000
7 500
1000
-10 000
10 000
15 000
7 500
1000
-10 000
10 000
15 000
7500
1000
-10 000
10 000
15 000
7500
1000
500
15 000
10 000
15 000
7500
1000
500
15 000
10 000
15 000
7500
1000
500
15 000
10 000
15 000
7500
1000
500
15 000
-----
-----
-----
-----
5 000
10 000
5 000
10 000
5 000
10 000
5 000
10 000
5 000
10 000
5 000
10 000
5 000
10 000
5 000
10 000
608)
--80
608)
--80
608)
--80
60
20
-80
608)
20
20
80
608)
20
20
80
608)
20
20
80
608)
20
20
80
ms
• Electrical opening time (instantaneous undervoltage
release)
• Opening time due to ETU, instantaneous short-circuit
ms
release
Service life: Breaking capacity N and S, 3-/4-pole
• Mechanical (without maintenance)
Operating cycles
Operating cycles
• Mechanical (with maintenance)5)
• Electrical (without maintenance)
Operating cycles
• 1000 V version, electrical (without maintenance) Oper. cycles
• 1150 V version, electrical (without maintenance) Oper. cycles
Operating cycles
• Electrical (with maintenance)5)
Service life: Breaking capacity H, 3-pole
• Mechanical (without maintenance)
Operating cycles
Operating cycles
• Mechanical (with maintenance)5)
• Electrical (without maintenance)
Operating cycles
• 1000 V version, electrical (without maintenance) Oper. cycles
• 1150 V version, electrical (without maintenance) Oper. cycles
Operating cycles
• Electrical (with maintenance)5)6)
Service life: Breaking capacity H, 4-pole
• Mechanical (without maintenance)
Operating cycles
Operating cycles
• Mechanical (with maintenance)5)
• Electrical (without maintenance)
Operating cycles
• 1000 V version, electrical (without maintenance) Oper. cycles
• 1150 V version, electrical (without maintenance) Oper. cycles
Operating cycles
• Electrical (with maintenance)5)6)
Service life: Breaking capacity C
• Mechanical (without maintenance)
Operating cycles
Operating cycles
• Mechanical (with maintenance)5)
• Electrical (without maintenance)
Operating cycles
Operating cycles
• Electrical (with maintenance)5)
Switching frequency7)
• 690 V version
1/h
• 1000 V version
1/h
• 1150 V version
1/h
Minimum interval between tripping operation by
ms
Electronic Trip Unit and next making operation of the
circuit breaker (only with automatic mechanical resetting
of the lockout device).
Minimum interval between On-Off or Off-On switching
operations.
1)
2)
3)
4)
–25/+70
–40/+70
1000
1000
1000
Use of trip units from –20 °C
ETU76B with graphics display can be used up to max. 55 °C.
At breaking capacity H: 1600 A to 70 °C.
Make time through closing coil for synchronization purposes
(short-time excited) 50 ms.
5)
Maintenance means: Replace main contact elements and arc chutes
(see Operating Manual).
6)
7)
8)
9)
Replacement of the main contact elements of circuit breakers size I with
breaking capacity H is only possible at the factory.
Minimum interval time between 2 tripping operations.
3-pole switching with breaking capacity N and S: 45/h.
Motorized operating mechanisms Uimp = 1.2 kV
Siemens · 04/2018
27
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
General data
I
II
... 3WL11 10 3WL11 12 3WL11 16 3WL11 20 3WL12 08 3WL12 10 3WL12 12 3WL12 16
30° 30°
30° 30°
Dhmax.
= 1 mm
Size
Type
Mounting position
and/or
NSE0_00062a
NSE0_00061a
Degree of protection
Main conductor
minimum
cross-sections
Auxiliary conductors (Cu)
Max. number
Auxiliary conductors ×
cross-section
(solid/stranded)
Unit(s)
• Copper bars,
mm2
bare
Unit(s)
• Copper bars,
mm2
painted black
Standard connection =
strain-relief clamp
• Without end sleeve
2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16); 1 × 2.5 mm2 (AWG 14)
• With end sleeve acc. to
1 × 0.5 mm2 (AWG 20) ... 1 × 1.5 mm2 (AWG 16)
DIN 46228 Part 2
2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16)
• With twin end sleeve
Optional connection =
tension spring
• Without end sleeve
2 × 0.5 mm2 (AWG 20) ... 2 × 2.5 mm2 (AWG 14)
• With end sleeve acc. to
2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16)
DIN 46228 Part 2
Position signaling switches Tension spring terminals
Weights 3-pole
• Fixed-mounted circuit
breakers
• Withdrawable circuit
breakers
• Guide frames
4-pole
• Fixed-mounted circuit
breakers
• Withdrawable circuit
breakers
• Guide frames
Dimensions
3-/4-pole
H
W
56
56
56
kg 45
45
45
45
60
60
60
60
kg 25
kg 50
25
50
25
50
25
50
31
67
31
67
31
67
31
67
kg 54
54
54
54
72
72
72
72
kg 30
30
30
30
37
37
37
37
320/410
460/590
Fixed-mounted
H mm
D mm
434
291
434
291
Withdrawable
H mm
D mm
465.5
471
465.5
471
D
Siemens · 04/2018
2×
50 × 10
2×
50 × 10
1 × 0.5 mm2 (AWG 20) ... 1 × 2.5 mm2 (AWG 14)
43
43
43
56
kg 43
W mm
NSS0_00535
28
NSE0_00927
IP20 without cabinet door, IP41 with door sealing frame, IP55 with cover
1×
2×
2×
3×
1×
1×
2×
60 × 10
40 × 10
50 × 10
50 × 10
50 × 10
60 × 10
40 × 10
1×
2×
2×
3×
1×
1×
2×
60 × 10
40 × 10
50 × 10
50 × 10
50 × 10
60 × 10
40 × 10
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
General data
Size
II
Type
3WL12 20 3WL12 25 3WL12 32 3WL12 40 3WL13 40 3WL13 50 3WL13 63
3-pole, 4-pole
Number of poles
Rated current In at 40 °C, at 50/60 Hz
Main conductor
N-conductor (only on 4-pole versions)
III
A 2000
A 2000
2500
2500
3200
3200
4000
4000
4000
4000
5000
5000
6300
6300
Rated operational voltage Ue at 50/60 Hz
(1000 V version, see Catalog LV 10 "Options")
V AC ...
690/1000
...
690/1000
...
690/1000
... 690
...
690/1000
...
690/1000
...
690/1000
Rated insulation voltage Ui
V AC 1000
1000
1000
1000
1000
1000
1000
kV 12
kV 4
kV 2.5
12
4
2.5
12
4
2.5
12
4
2.5
12
4
2.5
12
4
2.5
12
4
2.5
Yes
Yes
Yes
Yes
Yes
Yes
–25/+70
–40/+70
–25/+70
–40/+70
–25/+70
–40/+70
–25/+70
–40/+70
–25/+70
–40/+70
–25/+70
–40/+70
A 2000
A 2000
A 2000
2500
2500
2280
3200
3020
2870
39503)
3810
3600
4000
4000
4000
5000
5000
5000
5920
5810
5500
V 2000
2000
2000
2000
2000
2000
2000
W 180
W 320
270
520
410
710
750
925
520
810
630
1050
900
1600
Rated impulse withstand voltage Uimp
• Main conducting paths
• Auxiliary circuits
• Control circuits10)
Isolating function acc. to EN 60947-2
Yes
Utilization category
B
Permissible ambient temperature
• During operation (in operation with LCD max. 55 °C)1)
• Storage
Permissible load for with- • Up to 55 C (Cu bare)
• Up to 60 C (Cu bare)4)
drawable versions2)
• Up to 70 C (Cu painted black)4)
Rated rotor operational voltage Uer
Power loss at In
With 3-phase symmetrical load
• Fixed-mounted circuit breakers
• Withdrawable circuit breakers
C –25/+70
C –40/+70
Switching times
• Make time
• Opening time
ms
ms
35
34
35
34
35
34
35
34
35
34
35
34
35
34
• Electrical make time (through closing coil)5)
• Electrical opening time (through shunt release)
ms 100
ms 73
100
73
100
73
100
73
100
73
100
73
100
73
• Electrical opening time (instantaneous undervoltage release)
• Opening time due to ETU, instantaneous short-circuit release
ms
ms
73
50
73
50
73
50
73
50
73
50
73
50
73
50
Service life: Breaking capacity N, S and H11)
• Mechanical (without maintenance)
• Mechanical (with maintenance)6)
• Electrical (without maintenance) up to 690 V
• 1000 V version, electrical (without maintenance)
• 1150 V version, electrical7) (without maintenance)
• Electrical (with maintenance)6)
Operating cycles 10000
Operating cycles 15000
Operating cycles 7500
Operating cycles 1000
Operating cycles
500
Operating cycles 15000
10000
15000
7500
1000
500
15000
10000
15000
4000
1000
500
15000
10000
15000
2000
1000
500
15000
5000
10000
2000
1000
500
10000
5000
10000
2000
1000
500
10000
5000
10000
2000
1000
500
10000
Service life: Breaking capacity C
• Mechanical (without maintenance)
• Mechanical (with maintenance)6)
• Electrical (without maintenance) up to 690 V
• Electrical (without maintenance) up to 1150 V
• Electrical (with maintenance) up to 690 V6)
Operating cycles 5000
Operating cycles 10000
Operating cycles 5000
Operating cycles -Operating cycles 10000
5000
10000
5000
-10000
5000
10000
4000
-8000
------
5000
10000
1000
500
--
5000
10000
1000
500
--
5000
10000
1000
500
--
1/h 609)
1/h 20
1/h 20
609)
20
20
609)
20
20
609)
20
20
60
20
20
60
20
20
60
20
20
ms 80
80
80
80
80
80
80
Switching frequency8)
• 690 V version
• 1000 V version
• 1150 V version7)
Minimum interval between tripping operation by Electronic Trip
Unit and next making operation of the circuit breaker (only with
automatic mechanical resetting of the lockout device).
Minimum interval between On-Off or Off-On switching operations.
1)
Use of trip units from –20 °C
2)
6)
4000 A, size II in fixed-mounted version, 3-pole.
Maintenance means: Replace main contact elements and arc chutes
(see Operating Manual).
3)
Derating factors for fixed mounting of 3WL12 40.
4)
7)
ETU76B with graphics display can be used up to max. 55 °C.
Size II with order code "A15" and size III:
data for very high breaking capacity.
5)
8)
Make time through closing coil for synchronization purposes (short-time
excited) 50 ms.
Minimum interval time between 2 tripping operations.
9)
3-pole switching with breaking capacity N and S: 45/h.
10)
Motorized operating mechanisms Uimp = 1.2 kV
11)
1000 V and 1150 V versions only in the case of H breaking capacity
Siemens · 04/2018
29
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
General data
II
Type
3WL12 20 3WL12 25 3WL12 32 3WL12 40 3WL13 40 3WL13 50 3WL13 63
III
Mounting position
Dhmax.
= 1 mm
Size
30° 30°
30° 30°
and/or
NSE0_00927
NSE0_00062a
NSE0_00061a
IP20 without cabinet door, IP41 with door sealing frame, IP55 with cover
Degree of protection
Main conductor
minimum
cross-sections
• Copper bars,
bare
Unit(s) 3 ×
mm2 50 × 10
2×
100 × 10
3×
100 × 10
4×
120 × 10
4x
100 x 10
6x
100 x 10
6x
120 x 10
• Copper bars,
painted black
Unit(s) 3 ×
mm2 50 × 10
2×
100 × 10
3×
100 × 10
4×
4×
100 × 101) 100 × 10
6×
100 × 10
6×
120 × 10
Auxiliary conductors
(Cu)
Max. number of
auxiliary conductors ×
cross-section
(solid/stranded)
Standard connection = strain-relief clamp
• Without end sleeve
• With end sleeve acc. to
DIN 46228 Part 2
• With twin end sleeve
2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16)
Optional connection = tension spring
• Without end sleeve
• With end sleeve acc. to DIN 46228 Part 2
2 × 0.5 mm2 (AWG 20) ... 2 × 2.5 mm2 (AWG 14)
2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16)
Position signaling
switches
Tension spring terminals
1 × 0.5 mm2 (AWG 20) ... 1 × 2.5 mm2 (AWG 14)
Weights 3-pole
• Fixed-mounted circuit breakers
• Withdrawable circuit breakers
• Guide frames
kg 56
kg 60
kg 31
59
63
39
64
68
45
85
121
52
82
88
60
82
88
60
90
96
70
4-pole
• Fixed-mounted circuit breakers
• Withdrawable circuit breakers
• Guide frames
kg 67
kg 72
kg 37
71
76
47
77
82
54
103
146
62
99
106
84
99
106
84
108
108
119
Dimensions
3-/4-pole
W mm
460/590
704/914
Fixed-mounted
H mm
D mm
434
291
434
291
Withdrawable
H mm
D mm
465.5
471
465.5
471
D
H
W
2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16); 1 × 2.5 mm2 (AWG 14)
1 × 0.5 mm2 (AWG 20) ... 1 × 1.5 mm2 (AWG 16)
NSS0_00535
Minimum main conductor cross-sections for 4-pole withdrawable circuit
breakers: 4 x 120 x 10 mm.
Calculating the power consumption of the CubicleBUS modules
for SENTRON WL with CubicleBUS system
CubicleBUS module
Number of modules
per CubicleBUS
ETU45B Electronic Trip Unit
ETU76B Electronic Trip Unit
Metering function PLUS
1
1
1
Breaker Status Sensor BSS
1
1
COM15 PROFIBUS communication module
ZSI module
Digital output modules with rotary coding switch,
relay outputs
Digital output modules, configurable,
relay outputs
Analog output modules
Digital input modules
BDA PLUS
30
Siemens · 04/2018
Max. continuous current
per module from the
CubicleBUS
120 mA
170 mA
Max. startup current
per module from the
CubicleBUS
2000 mA
2000 mA
120 mA
40 mA
120 mA
110 mA
1
1-2
125 mA
50 mA
180 mA
280 mA
125 mA
125 mA
1
180 mA
125 mA
1-2
1-2
1
110 mA
30 mA
250 mA
800 mA
125 mA
350 mA
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
General data
Size
I to III
Type
3WL1
Manual operating mechanism with mechanical closing
N  230
9
Switching on/charging Max. force required to operate the hand lever
the energy store
Required number of strokes on the hand lever
Manual operating mechanism with mechanical and electrical closing
Charging the energy store
Closing coil (CC)
• Primary operating range
0.85 ... 1.1 × Us
• Extended operating range for battery operation
At 24 V DC, 48 V DC
60 V DC, 110 V DC
220 V DC
• Rated control supply voltage Us
50/60 Hz AC
DC
• Power consumption
AC/DC
• Min. command duration at Us for the closing coil
0.7 ... 1.26 × Us
V 110 ... 127; 208 ... 240
V 24; 30; 48; 60; 110 ... 125; 220 ... 250
VA/ 15/15
W
ms 60
1 A TDz (slow)/1 A
• Short-circuit protection
Smallest permissible DIAZED fuse (operational class gL)/
automatic circuit breaker with C characteristic
Manual/motorized operating mechanism with mechanical and electrical closing
For data, see above.
Manual operating mechanism
Motor
0.85 ... 1.1 × Us
• Primary operating range
• Extended operating range for battery operation
At 24 V DC, 48 V DC
60 V DC, 110 V DC
220 V DC
• Power consumption of motor
AC/DC
VA/ 135/135
W
s  10
• Time required to charge the spring energy store at 1 × Us
For data, see above.
Closing coil
For motor and
closing coil
0.7 ... 1.26 × Us
• Short-circuit protection
Smallest permissible DIAZED fuse (operational class gL)/
automatic circuit breaker with C characteristic;
Motor and closing coil for same rated control supply voltages
6 A TDz (slow)/2 A
• Smallest permissible DIAZED fuse (operational class gL)/ At Us = 24 ... 30 V
automatic circuit breaker with C characteristic (for different At Us = 48 ... 60 V
rated control supply voltages)
At Us = 110 ... 125 V DC/
110 ... 127 V AC
At Us = 220 ... 250 V DC/
208 ... 240 V AC
6A
6A
2A
2A
Signals of the Electronic Trip Unit
Protection functions acc. to EN 60947;
Current indication  10%;
Metering function for base quantities
 1%;
Metering function for
derived quantities  4%
Measuring accuracy of the Electronic Trip Unit
Auxiliary releases
Undervoltage releases • Response values
UVR (F3) and
UVR-td (F4)
Pickup
Dropout
0.85 ... 1.1
• Primary operating range
• Extended operating range for battery operation
At 24 V DC, 30 V DC,
48 V DC, 110 V DC,
220 V DC
• Rated control supply voltage Us
Instantaneous
50/60 Hz AC
DC
V 110 ... 127/208 ... 240/380 ... 415
V 24/30/48/60/110 ... 125/220 ... 2501)
Delayed
50/60 Hz AC
DC
V 110 ... 127; 208 ... 240; 380 ... 415
V 48; 110 ... 125; 220 ... 250
• Power consumption (pickup/uninterrupted duty)
• Opening time of the circuit breaker at Us = 0
- Version UVR (F3)
Without delay
With delay
- Version UVR-td (F8)
With delay, td = 0.2 to 3.2 s
Reset through additional NC contact – direct tripping
• Short-circuit protection
Smallest permissible DIAZED fuse (operational class gL)/
automatic circuit breaker with C characteristic
1)
 0.85 × Us
(circuit breaker can be closed)
0.35 ... 0.7× Us
(circuit breaker is opened)
AC
DC
0.85 ... 1.26
VA 20/5
W 20/5
ms 200
80
ms
ms 200
s 0.2 ... 3.2
ms  100
1 A TDz (slow)/1 A
24 V and 30 V only with undervoltage release UVR (F3).
Siemens · 04/2018
31
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
General data
Size
I to III
Type
3WL1
Auxiliary releases
Shunt releases (ST)
(F1, F2)
• For continuous command
(100% OP), locks out on
momentary-contact
commands
- Response value
Pickup
> 0.7 × Us
(circuit breaker is tripped)
0.85 ... 1.1 × Us
- Primary operating range
- Extended operating range
for battery operation
At 24 V DC, 48 V DC
60 V DC, 110 V DC
220 V DC
- Rated control supply voltage Us
50/60 Hz AC
DC
- Power consumption
AC/DC
V 110 ... 127; 208 ... 240
V 24; 30; 48; 60; 110 ... 125;
220 ... 250
VA/W 15/15
ms 60
- Min. command duration at Us
- Opening time of circuit breaker
at Us = 100%
5% OP
At AC/DC
ms 80
- Short-circuit protection
Smallest permissible DIAZED fuse (operational
class gL)/ automatic circuit breaker with
C characteristic
1 A TDz (slow)/1 A
- Response value
> 0.7 × Us
(circuit breaker is tripped)
Pickup
0.85 ... 1.1 × Us
- Primary operating range
- Extended operating range
for battery operation
At 24 V DC, 48 V DC
60 V DC, 110 V DC
220 V DC
- Rated control supply voltage Us
50/60 Hz AC
DC
- Power consumption
AC/DC
- Opening time of circuit breaker
at Us = 100%
VA/W 15/15
ms 25
At AC/DC
ms 50
- Short-circuit protection
Smallest permissible DIAZED fuse (operational
class gL)/ automatic circuit breaker with
C characteristic
- Rated control supply voltage Us
1 A TDz (slow)/1 A
50/60 Hz AC
DC
V 110; 230
V 110; 220
0.85 ... 1.1 × Us
- Primary operating range
- Power consumption
0.7 ... 1.26 × Us
V 110 ... 127; 208 ... 240
V 24; 48; 110 ... 125; 220 ... 250
- Min. command duration at Us
• With spring energy store
consisting of shunt
release and capacitor
storage device
0.7 ... 1.26 × Us
AC/DC
VA/W 1/1
- Storage time at Us/
Recharging time at Us
max. 5 min/min. 5 s
- Opening time of the circuit breaker,
short-circuit protection
As with "for continuous
command"
Remote reset solenoid for mechanical tripped indicator (F7)
0.85 ... 1.1 × Us
- Primary operating range
Remote reset solenoid for
mechanical tripped
indicator (F7)
- Extended operating range
for battery operation
At 24 V DC, 48 V DC
110 V DC
220 V DC
- Power consumption
AC/DC
0.7 ... 1.26 × Us
VA/W 50/50
- Min. command duration at Us for the remote reset
solenoid
ms 60
- Short-circuit protection
Smallest permissible DIAZED fuse (operational class gL)/
automatic circuit breaker with C characteristic
2 A TDz (slow)/1 A at 24 V DC
and 48 V DC,
1 A TDz (slow)/1 A at 110 V and
208 ... 250 V
Contact position-driven auxiliary switches (S1, S2, S3, S4, S7, S8)
Rated insulation voltage Ui
V 500
AC/DC
Rated operational voltage Ue
V 500
AC/DC
kV 4
Rated impulse withstand voltage Uimp
Breaking capacity
• Alternating current
50/60 Hz
• Direct current
Short-circuit protection
32
- Rated operational voltage Ue
- Rated operational current
Ie/AC-12
Ie/AC-15
- Rated operational voltage Ue
- Rated operational current
Ie/DC-12
Ie/DC-13
• Largest permissible DIAZED fuse (operational class gL)
• Largest permissible miniature circuit breaker with C characteristic
Siemens · 04/2018
V 24 ... 230
A 10
A 4
380/400
10
3
V 24
48
A 10
A 8
8
4
110
3.5
1.2
10 A TDz, 10 A Dz
10 A
220
1
0.4
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
General data
Size
I to III
Type
3WL1
Ready-to-close signaling switches (S20) (acc. to DIN VDE 0630)
Breaking capacity
Short-circuit protection
• Alternating current
- Rated operational voltage Ue
- Rated operational current Ie
V 250
A
8
• Direct current
- Rated operational voltage Ue
- Rated operational current Ie
V 125
A
0.4
Largest permissible DIAZED fuse (operational class gL)
250
0.2
2 A Dz (quick)
Tripped signaling switches (S24) and signaling switches for auxiliary releases (S22, S23)
(acc. to DIN VDE 0630)
Breaking capacity
• Alternating current
- Rated operational voltage Ue
- Rated operational current Ie/AC-12
V 250
A
8
• Direct current
- Rated operational voltage Ue
- Rated operational current Ie/DC-12
V
A
24
6
125
0.4
250
0.2
Short-circuit protection
Largest permissible DIAZED fuse (operational class gL)
6 A Dz (quick)
Tripped signaling switch
Signal duration after tripping
Until manual or
electrical remote reset (option)
Position signaling switch on guide frame
Type of contact
• Signal:
- "Circuit breaker in connected position"
- "Circuit breaker in test position"
- "Circuit breaker in disconnected position"
50/60 Hz AC
DC
Rated insulation voltage Ui
- Ie/AC-12
V 440
V 250
- Ie/DC-13
24 V 10 A, 110/127 V 10 A,
220/240 V 10 A, 320/440 V 10 A
220/240 V 4 A,
320/440 V 3 A,
24 V 10 A, 48 V 2.5 A,
220/240 V 0.2 A,
24 V 3.0 A, 220/240 V 0.1 A
- A 300 (AC)
120 V 6 A, 240 V 3 A
- R 300 (DC)
125 V 0.22 A, 250 V 0.11 A
- Ie/AC-15
- Ie/DC-12
Short-circuit protection
1 CO
1 CO
1 CO
kV 4
Rated impulse withstand voltage Uimp
• Rated operational
current Ie
or
V 250
Rated operational voltage Ue
Breaking capacity
3 CO
2 CO
1 CO
• Largest permissible DIAZED fuse (operational class gL)
• Largest permissible automatic circuit breaker with C characteristic
8 A TDz (slow)
8 A TDz (slow)
Siemens · 04/2018
33
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
General data
Protection functions
Parameterization by
ETU15B
D
ETU25B
D
ETU27B
D&S
✓
-0.5-0.55-0.6-0.65-0.70.75-0.8-0.85-0.9-1
--
✓
-0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1
--
✓
-0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1
--
10 s fixed
------------
10 s fixed
--At tsd = 20 ms (M)
---✓
-1.25-1.5-2-2.5-3-4-6-8-10-12
0-M-100-200-300-400 ms
--
10 s fixed
--At tsd = 20 ms (M)
✓
✓
1
✓
-1.25-1.5-2-2.5-3-4-6-8-10-12
0-M-100-200-300-400 ms
--
--✓
-2-3-4-5-6-7-8
------
--✓
-Fixed for Ii  20  In, max. 50 kA
------
--✓
-Fixed for Ii  20  In, max. 50 kA
✓ permanently installed
-✓
-✓
--
--
--
-----
-----
A-B-C-D-E
-100-200-300-400-500 ms
--
---
---
---
--
--
--
---
---
---
---
---
---
--
--
--
✓
✓
✓
--------
✓
✓
✓
✓
✓
✓
-----
✓
✓
✓
✓
✓
✓
✓
✓
---
--
--
--
--------------
--------------
--------------
Function overview of the electronic trip system
Overload protection
Function can be switched on/off
Setting range IR = In × ...
R
overload protection
L Switchable
(I t- or I t-dependent function)
2
4
Setting range for time-lag class tR at I2t
Setting range for time-lag class tR at I4t
R
Thermal memory can be switched on/off
Phase failure sensitivity
N-conductor protection
Function can be switched on/off
N-conductor setting range IN = In × ...
Short-time delayed short-circuit protection
Function can be switched on/off
Setting range Isd = In × ...
s d
Setting range of delay time tsd
Switchable short-time delayed short-circuit protection
s d
(I2t-dependent function)
Setting range of delay time tsd at I2t
ZSI function
i
Instantaneous short-circuit protection
N S E 0 _ 0 0 8 8 8 b
Function can be switched on/off
Setting range Ii = In × ...
Ground-fault protection
Tripping and alarm functions
Tripping function can be switched on/off
Alarm function can be switched on/off
Detection of the ground-fault current through
summation current formation with internal or external
g
N-conductor transformer
Detection of ground-fault current through external
current transformer
g
Setting range of the response current Ig for tripping
NSE0_00889a
Setting range of the response current Ig for alarm
Setting range of the delay time tg
Switchable ground-fault characteristic
(I2t-dependent function)
Setting range for delay time tg at I2t
ZSI-G function
Parameter set changeover
Switchable between parameter set A and B
LCD
Alphanumeric LCD (4-line)
Graphical LCD (24 V, external power supply required)
Communication
CubicleBUS integrated
Communications capability via PROFIBUS DP
Metering function
Metering capability with metering function Plus
LED display
Electronic Trip Unit active
Alarm
ETU fault
L tripping operation
S tripping operation
I tripping operation
N tripping operation
NSE0_00890
G tripping operation
G alarm
Tripping operation as a result of extended protection
function
Communication
Signals from signaling switches with external CubicleBUS modules (relays)
Overload warning
Load shedding, load absorbing
Leading signal overload trip 200 ms
Temperature alarm
Phase unbalance
Instantaneous short-circuit trip
Short-time delayed short-circuit trip
Overload trip
Neutral conductor trip
NSE0_00891
Ground-fault protection trip
Ground-fault alarm
Auxiliary relay
ETU fault
N
S
I
G
Delay time figures given in ms.
M = Motor protection, corresponds to 20 ms.
D = Rotary coding switch
D & S = Rotary coding and slide switch
K = Communication
M/K = Menu/Communication
34
Siemens · 04/2018
✓ Available.
-- Not available.
❑ Optional.
For the setting range of the response current Ig, see page 35.
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
General data
Protection functions
Parameterization by
ETU45B
D& S
ETU76B
M/K
✓
-0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.8-0.9-1
✓
✓
✓
0.4 ... 1
✓
2-3.5-5.5-8-10-14-17-21-25-30 s
1-2-3-4-5 s
✓
At tsd = 20 ms (M)
✓
✓
0.5 ... 1
✓
✓
1.25-1.5-2-2.5-3-4-6-8-10-12
M-100-200-300-400 ms
✓
2 ... 30 s
1 ... 5 s
✓
✓ (on/off)
✓
✓
0.2 ... 2
✓
✓
1.25 × In ... 0.8 × Icw
M-80 ... 4000 ms
✓
100-200-300-400 ms
By CubicleBUS module
✓
✓
1.5-2.2-3-4-6-8-10-12-0.8 x Ics
❑ Module can be retrofitted
✓
✓
-✓
100 ... 400 ms
By CubicleBUS module
✓
✓
1.5 × In ... 0.8 × Ics
❑ Module can be retrofitted
✓
✓
✓
✓
✓
✓
A-B-C-D-E
A-B-C-D-E
A ... E
A ... E
Function overview of the electronic trip system
Overload protection
Function can be switched on/off
Setting range IR = In × ...
Switchable overload protection
(I2t- or I4t-dependent function)
Setting range for time-lag class tR at I2t
Setting range for time-lag class tR at I4t
Thermal memory can be switched on/off
Phase failure sensitivity
N-conductor protection
Function can be switched on/off
N-conductor setting range IN = In × ...
Short-time delayed short-circuit protection
Function can be switched on/off
Setting range Isd = In × ...
Setting range of delay time tsd
Switchable short-time delayed short-circuit protection
(I2t-dependent function)
Setting range of delay time tsd at I2t
ZSI function
Instantaneous short-circuit protection
Function can be switched on/off
Setting range Ii = In × ...
Ground-fault protection
Tripping and alarm functions
Tripping function can be switched on/off
Alarm function can be switched on/off
Detection of the ground-fault current through summation current
formation with internal or external N-conductor transformer
Detection of ground-fault current through external
current transformer
Setting range of the response current Ig for tripping
Setting range of the response current Ig for alarm
Setting range of the delay time tg
100-200-300-400-500 ms
✓
Switchable ground-fault characteristic
2
(I t-dependent function)
Setting range for delay time tg at I2t
100-200-300-400-500 ms
ZSI-G function
By CubicleBUS module
Parameter set changeover
Switchable between parameter set A and B
-LCD
Alphanumeric LCD (4-line)
❑
Graphical LCD (24 V, external power supply required)
-Communication
CubicleBUS integrated
✓
Communications capability via PROFIBUS DP
✓
Metering function
Metering capability with metering function Plus
✓
LED display
Electronic Trip Unit active
✓
Alarm
✓
ETU fault
✓
L tripping operation
✓
S tripping operation
✓
I tripping operation
✓
N tripping operation
✓
G tripping operation
✓ (Only with ground-fault protection module)
G alarm
✓ (Only with ground-fault protection module)
Tripping operation as a result of extended protection functions ✓
Communication
✓
Signals from signaling switches with external CubicleBUS modules (relays)
Overload warning
✓
Load shedding, load absorbing
✓
Leading signal overload trip 200 ms
✓
Temperature alarm
✓
Phase unbalance
✓
Instantaneous short-circuit trip
✓
Short-time delayed short-circuit trip
✓
Overload trip
✓
Neutral conductor trip
✓
Ground-fault protection trip
✓ (Only with ground-fault protection module)
Ground-fault alarm
✓ (Only with ground-fault protection module)
Auxiliary relay
✓
ETU fault
✓
Setting range of the response current Ig
Size I and size II
Size III
A
100 A
400 A
B
300 A
600 A
C
600 A
800 A
D
900 A
1000 A
E
1200 A
1200 A
100 ... 500 ms
✓
100 ... 500 ms
By CubicleBUS module
✓
-✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓ (Only with ground-fault protection module)
✓ (Only with ground-fault protection module)
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓ (Only with ground-fault protection module)
✓ (Only with ground-fault protection module)
✓
✓
Increment size when settings are made for the ETU76B using the menu
From ... to
Increment size From ... to
Increment size
0 ... 1
0.1
1000 ... 1600
50
1 ... 100
1
1600 ... 10000
100
100 ... 500
5
10000 ... max
1000
500 ... 1000
10
For the legend, see
page 34.
Siemens · 04/2018
35
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Configuration aids
■ Characteristic curves2)
n
1,25 ... 12 x
i
R min
100
10
sd min
sd max
1,25 ... 12 x
n
sd max
0 ... 0,4 s
0,1
sd min
i
i > 20 x n
max. 50 kA
0,01
0,1
1
10
100
/
n
3WL circuit breaker with ETU27B Electronic Trip Unit,
LSIN characteristic curve
NSE0_01521
[s]
1000
10000
Opening time
Opening time [s]
n
N
n
10000
100
g min
R max
0,4 ... 1,0 x
1000
1
3WL circuit breaker with ETU25B Electronic Trip Unit,
LSI characteristic curve
10
NSE0_01527
[s]
10000
100
/
n
3WL circuit breaker with ETU15B Electronic Trip Unit
i > 20 x n
max. 50 kA
10
100
/
0,01
1
10
sd min
0,1
0,1
i max
n
1
0,1
sd max
0 ... 0,4 s
i min
0,01
sd max
n
10
0,1
10
sd min
100
2 ... 8 x
100
1
0,5 ... 1,0 x n
g max
1000
NSE0_01523a
0,4 ... 1,0 x
1000
R max
NSE0_01519
R max
1000
1
Opening time [s]
Opening time [s]
R min
R min
NSE0_01520
10000
10000
Opening time
Every Electronic Trip Unit type and every setting has its own
characteristic curve. Only a selection is shown in the following.
The characteristic curves each show the largest and smallest
setting range of 3WL circuit breakers with 1000 A rated current
at 500 V rated voltage with various trip units. In order to obtain a
complete tripping characteristic curve, the relevant parts of the
characteristic curves have to be combined. The characteristic
curves show the behavior of the Electronic Trip Unit when it is
activated by a current that is already flowing before the tripping
operation. If the overcurrent tripping occurs immediately after
closing and the Electronic Trip Unit is therefore not yet activated,
the opening time is extended, depending on the level of the
overcurrent by up to 15 ms. To determine the break-times of the
circuit breakers, approximately 15 ms must be added to the
opening times shown for the arcing time.
For tolerances, see legend below.
The characteristic curves shown apply to ambient temperatures
at the circuit breaker between –5 and +55 °C. The trip unit can
be operated at ambient temperatures of –20 to +70 °C. An extended tolerance band can apply at these temperatures.
sd
1,25 ... 12 x
n
100
2
sd
= const
10
100 ... 1200 A 1)
1
1
g max
0,1 ... 0,5 s
0,1
2
sd
g min
= const
sd
= const
0,1 ... 0,4 s
0,1
0,02 ... 0,4 s
0,01
100
1000
10000
0,01
100000
0,1
A
3WL circuit breaker with ETU27B Electronic Trip Unit,
G characteristic curve
Tolerances for the current settings
L: Tripping operations between 1.05 and 1.2 x IR
S: –0%, +20%
I: –0%, +20%
G: –0%, +20%
Tolerances for the tripping times
L: –20%, +0% for I2t characteristic curve
S: –0%, +60 ms or –0%, 10% for tripping times greater than 600 ms
I: <50 ms
G: –0%, +60 ms or –0%, 10% for tripping times greater than 600 ms
36
Siemens · 04/2018
1
10
100
/
n
3WL circuit breaker with ETU45B Electronic Trip Unit,
S characteristic curve
1)
Sizes I and II: 100 ... 1200 A
Size III: 400 ... 1200 A.
2)
With a single-pole load in the lowest rated current range, the response
times of the short-circuit trip can increase by approx. 10% and the tripping
times by approx. 15% with respect to the characteristic curve.
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Configuration aids
In order to obtain a complete tripping characteristic curve, the
relevant parts of the characteristic curves have to be combined.
The characteristic curves show the behavior of the Electronic
Trip Unit when it is activated by a current that is already flowing
before the tripping operation. If the overcurrent tripping occurs
immediately after closing and the Electronic Trip Unit is therefore
not yet activated, the opening time is extended, depending on
the level of the overcurrent by up to 15 ms. In order to determine
the total break-times of the circuit breakers, approximately 15 ms
must be added to the opening times shown for the arcing time.
2
g
0,1 ... 0,5 s
0,01
1000
10000
100000
n
= const
100
R
2 ... 30s for
1 ... 5s for
10
3WL circuit breaker with ETU45B and ETU76B Electronic Trip Unit,
G characteristic curve
10000
1000
NSE0_01526a
= const
2
sd
1,25 x
100
n ... 0,8 x
cw
10
2
1
2
4
sd
1
0,1
0,1
sd
= const
= const
0,1 ... 0,4 s
0,02 ... 4 s
0,01
0,1
0,01
0,1
= const
100 ... 1200 A 1)
0,1
Opening time [s]
NSE0_01522a
4
R
[s]
g
10
A
10000
Opening time
100
100
The characteristic curves shown apply to ambient temperatures
at the circuit breaker between –5 and +55 °C. The trip unit can
be operated at ambient temperatures of –20 to +70 °C (ETU76B
with graphic display up to +55 °C). An extended tolerance band
can apply at these temperatures.
1000
1000
1
For tolerances, see legend below.
0,4 ... 1,0 x
NSE0_01525a
10000
Opening time [s]
Every Electronic Trip Unit type and every setting has its own
characteristic curve. Only a selection is shown in the following.
The characteristic curves each show the largest and smallest
setting range of 3WL circuit breakers with 1000 A rated current
at 500 V rated voltage with various trip units.
1
10
100
/
n
1
10
/ n
1
/
cw
3WL circuit breaker with ETU76B Electronic Trip Unit, S characteristic
curve
3WL circuit breaker with ETU45B and ETU76B Electronic Trip Unit,
L characteristic curve
NSE0_01524a
Opening time [s]
10000
1000
Further characteristic curves are shown in the manual and the
planning and configuring tool SIMARIS design, or ask your
Siemens contact person.
Tolerances for the current settings
L: Tripping operations between 1.05 and 1.2 x IR
S: –0%, +20%
I: –0%, +20%
G: –0%, +20%
100
10
Tolerances for the tripping times
L: –20%, +0% for I2t characteristic curve
S: –0%, +60 ms or –0%, 10% for tripping times greater than 600 ms
I: <50 ms
G: –0%, +60 ms or –0%, 10% for tripping times greater than 600 ms
1
i
1,5 x
0,1
n ... 0,8
x
cs
0,01
0,1
1
10
/ n
1
/
cs
3WL circuit breaker with ETU45B and ETU76B Electronic Trip Unit,
I characteristic curve
1)
Sizes I and II: 100 ... 1200 A
Size III: 400 ... 1200 A.
Siemens · 04/2018
37
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Configuration aids
■ Dimensional drawings
External current transformers for N-conductor without copper
connection pieces
Voltage transformers for 3WL air circuit breakers
+
58
61 62
65
68
71 72
75
78
260 ±3
8,9
16
8
R 13,1
R 22
87 ±2
NSE0_01375
55
60
40 22
81
96,8
51 52
Size I, 3WL9111-0AA21-0AA0
12 13 14
125 ±1
11
11
NSE0_01103
S
18
Size II, 3WL9111-0AA22-0AA0
Size I, 3WL9111-0AA31-0AA0
41
51
88
95
113
170
91
24
54
115
131
65,5
83
55
130
68
51 44
Ø 13,5
R 27
15
NSE0_01376
External current transformers for N-conductor with copper
connection pieces
51
36
70
83
Current transformers for overload protection in the
N-conductor
3
Size III, 3WL9111-0AA23-0AA0
NSE0_00606b
51
160
184
50,5
Ø 13,5
130
68
51 44
NSE0_01377
45
3×10
30 30
R 15
3
31
Size II, 3WL9111-0AA32-0AA0
107
123
161
97
Door cutout with edge protector
170
91
24
Door cutout for operator panel
295
NSE0_00607b
131
Size III, 3WL9111-0AA33-0AA0
30 30 30
3×10
240
340
90
113
52
Inner dimensions
with edge protector
Ø 13,5
Door cutout for operator panel using the door sealing frame
170
91
24
130
68
51 44
NSE0_00164c
Option with/without door interlocking
314
123
300
40
3
NSE0_00610d
R5
R5
2
40
180
140
175
350
Ø5,5
120
Ø5,5
65
Dimensions for option with door interlocking
140
160
184
120
Ø5,5
185
NSE0_00608b
2) Center 3WL circuit breaker operator panel
3) 8 mounting holes for door sealing frame
4) 3 mounting holes for door sealing frame
38
Siemens · 04/2018
11,5
1) Mounting surface
1
12
21
4
40
Dimensions for option with door interlocking
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Configuration aids
CubicleBUS modules
Breaker Data Adapter (BDA Plus)
3WL9 111-0AT2.-0AA0
3WL9 111-0AT33-0AA0
70
81,9
45,5
38
19
153
NSE0_02085
94
47,5
86
NSE0_02086
6
30
Door cutout for operator panel using IP55 protective cover
400
395
NSE0_01030b
NSE0_01029c
Protective cover, IP55
4 x R5
°
435
85
70
68
295-300
72
72
340-350
4 x 5,5
341
Mounting surface for circuit
breaker or guide frame
313
17
Breaker installation level
Breaker installation
level
Siemens · 04/2018
148
39
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Configuration aids
Size I, up to 2000 A, fixed-mounted version, 3- and 4-pole
Standard version, horizontal connection
21
20
8
14
a
5,5
210
230
40
7
3
139 58
320
410
NSE0_00617k
150
110
20
h
90 90 90 60
55
Ø13
Vertical connection
h
b
267,5
60
127,5
30
Ø13,5
NSE0_00619a
NSE0_00618i
3
113,5
128,5
M8
60 90 90 90
55 55 55 55
82
M8
26
d
c
60 90 90 90
NSE0_00613c
3
h
6
421
e
NSE0_00612i
Ø13,5
h
Front connection (single)
47
Front connection (double hole)
47
55 55 55 55
m
NSE0_00616c
3
40
82
M8
Siemens · 04/2018
14
c
m
40
f
6
421
g
NSE0_00615i
40
Ø13,5
60 90 90
60 90 90
45
NSE0_00614i
90
NSE0_00620a
15
3
15
150
270
300
390
275
123,5
18
327,5
3
17
5
a
4
19
9
76
275
NSE0_00611i
6
127
90
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Configuration aids
Dimensions in mm
Item number
Dimensions
&
Grooves (4 mm wide, 5 mm deep) for supporting phase partitions in the system
(
• SIGUT screw terminals
437
)
• Screwless connections
440
• COM15/COM16
462
*
Dimension to inside surface of the closed cabinet door
106
+
Fixing points for mounting the circuit breaker in the system (grid dimensions in mm)
4 x M8 screw nut (150) and 4 x 9 (110)
Auxiliary connector with:
,
"Safe OFF" locking device
33.5
-
Key operation
60.5
2
Space for cable harness to electrical auxiliary circuit connections
20
Z suffix or breaking capacity X
Standard
A05, A16 or DC
3
Maximum device height
462
462
5
Mounting space for removal of the arc chutes
541
591
6
Top edge of arc chutes
401
451
789
Safety clearances
See below
Connection dimensions in mm
Max. rated circuit breaker current
•  1000 A AC, breaking capacity N and S only
• 1250 - 2000 A AC or breaking capacity H or  2000 A DC
a
10
15
b
10
15
Busbar thickness
c
10
15
d
11
6
Clearance
e
451
461
Clearance
f
34
39
Overhang
g
541
551
Clearance
h
35
l
80
Terminal face length
Safety clearances in mm
SZ I, fixed-mounted version
... from grounded or non-conductive parts
... from live parts
Above 71)
At rear
Above 7
At side 8
At rear 9
Above 7
At side
Operational voltage, breaking capacity
Standard arc chutes – 401 mm
IT system
500 V AC, N/S
460
0
0
615
20
20
550
500 V AC, H
460
0
0
715
20
20
550
690 V AC, N/S
460
0
0
765
50
125
--
690 V AC, H
460
0
0
965
75
140
--
Operational voltage, breaking capacity
High arc chutes – 451 mm (A05, A16 or DC)
690 V AC
515
0
0
965
75
140
5503)
690 V AC + 20% H
515
0
0
1015
100
140
--
1000 V AC, H
515
0
0
1015
100
140
--
1000 V DC
550
0
0
2)
2)
2)
--
1)
Values for struts, grids and perforated sheets. When using plates with
conductive surfaces: values on request.
2)
With insulating shield; for clearance, see "non-conductive parts"
3)
Ue = 1000 V with breaking capacity H and Z option Z = A05
Siemens · 04/2018
41
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Configuration aids
Size I, up to 2000 A, withdrawable version, 3- and 4-pole
Standard version, horizontal connection
320
270
20
NSE0_00624h
382,5
367,5
327
12
350
260
14
NSE0_00630i
21
3
275
150
15
4
Ø1
69
123,5
10
31
40
30
55
13
210
300
10
327,5
5
287
a
16
a
4
3
19
76
275
NSE0_00621k
27
42
220
10 55 90 90 90
15
45
10
6
11
12
13
,5
13
Ø
NSE0_00627
j
55 55 55 55
68
25
139
270
320
410
Vertical connection
350
260
287
69
55
40
c
169,5
10
15
90
90
90
69
287
373
m
90
6
h
90
350
260
55 55
NSE0_00626h
69
Siemens · 04/2018
90
55
m
NSE0_00625h
h
287
373
26
11
42
15
13,5
62,5
NSE0_00623b
NSE0_00622a
403
55
13,5
10
90 90 90
15
14
55
350
260
55
55
3
169,5
10
Front connection (double hole)
62,5
c
NSE0_00628i
267,5
127,5 30
287
l
Front connection (single)
6
150
165
Ø13,5
90 90 90
15
493
10
3
34
121
3
69
282,5
142,5 26
l
33
12
60
NSE0_00632i
NSE0_00631i
55 55 55 55
M
350
260
b
j
40
14
NSE0_00629i
Flat terminals
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Configuration aids
Dimensions in mm
Item number
Dimensions
Z suffix or breaking capacity X
Standard
A05, A16 or DC
&
Grooves (4 mm wide, 5 mm deep) for supporting phase partitions in the system
(
• SIGUT screw terminals (one-part)
465 (446)
515 (496)
)
• Screwless connections
468
518
*
Dimension to inside surface of the closed cabinet door
58.0
.
Fixing holes
9
/
Circuit breaker in connected position
88.5
0
Circuit breaker in test position
121.5
1
Circuit breaker in disconnected position
140.5
2
Space for cable harness to electrical auxiliary circuit connections
20
3
Maximum device height
468
518
4
Guide frame upper edge
460
510
789
Safety clearances
See below
Auxiliary connector with:
Connection dimensions in mm
Max. rated circuit breaker current
• Up to 1000 A AC, breaking capacity N and S only
• 1250 - 2000 A AC or breaking capacity H
a
10
15
b
10
15
Busbar thickness
c
10
15
d
11
6
Clearance
e
403
413
Clearance
f
34
39
Overhang
g
493
503
Clearance
h
35
j
38
l
59
m
80
Terminal face length
Safety clearances in mm
SZ I, withdrawable versions
... from grounded or non-conductive parts
... from live parts
Above 7
At side
At rear
Above 7
At side 8
At rear 9
IT system
Above 7
Arc chute covers
Without1) / with
Without/with
Without/with
Without/with
Without/with
Without/with
Without
Operational voltage, breaking capacity
Standard arc chutes – 4 = 460 mm
500 V AC, N/S
460 / 460
0 / 402)
0/0
615 / 480
20 / 100
20 / 14
550
500 V AC, H
460 / 460
0 / 402)
0/0
715 / 480
50 / 50
20 / 14
550
690 V AC, N/S
460 / 460
0 / 402)
0/0
765 / 480
50 / 100
125 / 14
--
690 V AC, H
460 / 460
0 / 402)
0/0
965 / 480
75 / 225
140 / 14
--
Operational voltage, breaking capacity
High arc chutes – 4 = 510 mm (A05, A16 or DC)
690 V AC, H
510 / --
0 / --
0 / --
965 / --
75 / --
140 / --
5503)
690 V AC + 20% H
510 / --
0 / --
0 / --
1015 / --
100 / --
140 / --
--
1000 V AC
510 / --
0 / --
0 / --
1015 / --
100 / --
140 / --
--
1)
Values for struts, grids and perforated sheets. When using plates with
conductive surfaces: values on request.
2)
Value for plates that cover the lateral openings in the guide frame,
0 mm for struts and grids
3)
Ue = 1000 V with breaking capacity H and Z option Z = A05
Siemens · 04/2018
43
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Configuration aids
Size II, up to 4000 A, fixed-mounted version, 3- and 4-pole
Standard version, horizontal connection
14
NSE0_00633b
20
19
a
NSE0_00642
270
440
570
130
90 30
90
30
139
460
590
128
a
Vertical connection 3200 A AC and 4000 A DC
30
NSE0_00640c
100
90
40
130
130
130
142
162
h
90
3
h
421
90
90
NSE0_00635e
3,5
NSE0_00634e
e
c 82 M8
90
26
d
NSE0_01868a
NSE0_00641b
90
Ø1
130
130
130
Front connection (double hole)
90
Ø1
3,5 40
90
90
90
m
NSE0_00638d
421
3
M8
14
82
m
40
f
6
NSE0_00637e
40
47
g
Ø 13,5
10
20
k
M8
Front connection (single)
44
30
30
290
134,5
98 30
h
6
130
85 Nm
3
47
130
Vertical connection 4000 A AC (terminal face length k = 40 mm)
b
Ø13,5
113
128
130
7
7
345,5
79,5
110
90
21
3
3
c
6
127
NSE0_00639k
150
40
,5
20
10
3
h
130
13
Ø
130
85
45
150
210
230
NSE0_00636f
15
5,5
76
123,5
150
5
4
3
275
275
18
327,5
17
90
Siemens · 04/2018
130
130
130
M8
200
130
200
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Configuration aids
Dimensions in mm
Item number
Dimensions
&
Grooves (4 mm wide, 5 mm deep) for supporting phase partitions in the system
(
• SIGUT screw terminals
437
)
• Screwless connections
440
• COM15/COM16
462
*
Dimension to inside surface of the closed cabinet door
106
+
Fixing points for mounting the circuit breaker in the system (grid dimensions in mm)
4 x M8 screw nut (150) and 4 x 9 (110)
2
Space for cable harness to electrical auxiliary circuit connections
Auxiliary connector with:
20
Ue, Z suffix or breaking capacity X
Standard
DC: 600 V
A05, A15 or C
DC: > 600 V
3
Maximum device height
462
462
5
Mounting space for removal of the arc chutes
541
591
6
Top edge of arc chutes
401
451
789 Safety clearances
See below
Connection dimensions in mm
Max. rated circuit breaker current
• Up to 20005) A AC
• Up to 2000 A DC
• 25004)5) A AC
• 3200 A AC/4000 A DC or for breaking capacity C
a
10
10
15
30
b
15
15
15
30
Busbar thickness
c
10
10
20
20
d
11
11
6
6
Clearance
e
451
451
461
461
Clearance
f
34
34
39
39
Overhang
g
541
541
551
551
Clearance
h
35
m
80
Terminal face length
--
Safety clearances in mm
SZ II, fixed-mounted version
... from grounded or non-conductive parts
... from live parts
Above1) 7
At rear
Above 7
At side 8
At rear 9
Above 7
At side
Operational voltage
Standard arc chutes – 401 mm
IT system
500 V AC
460
0
0
715
50
20
550
690 V AC
460
0
0
1065
100
140
--
300 V DC
495
0
0
2)
2)
2)
--
600 V DC
650
0
0
2)
2)
2)
--
Operational voltage, breaking capacity High arc chutes – 451 mm (A05, A16 or DC)
690 V AC, H
510
0
0
1015
100
140
6003)
690 V AC, C
510
0
0
775
100
125
--
690 V AC + 20% H
620
0
0
1015
100
125
--
1000 V AC, H
620
0
0
1015
100
125
--
1150 V AC
620
0
0
2)
2)
2)
--
1000 V DC
615
0
0
2)
2)
2)
--
3WL52
Double high arc chutes – 501 mm (A17)
1)
Values for struts, grids and perforated sheets. When using plates with
conductive surfaces: values on request.
2)
With insulating shield; for clearance, see "non-conductive parts"
3)
Ue = 1000 V with breaking capacity H and Z option Z = A05
4)
Does not apply to 3WL5: 3WL5 see dimensions 3200 A AC
5)
Does not apply to breaking capacity C.
Siemens · 04/2018
45
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Configuration aids
Size II, up to 4000 A, withdrawable version, 3- and 4-pole
Standard version, horizontal connection
382,5
367,5
327
NSE0_00646f
90
530
400
90
90
5545 130
130
20
14
90
9
40
10
270
350
480
Ø13,5
327,5
3
27
42
10
220
69
40
31
Ø14
45
10
130
10
55
21
30
NSE0_00649b
j
30
a
275
150
5
123,5
4
76
275
a
287
NSE0_00652c
NSE0_00643c
139
270
460
590
138
95
Vertical connection 3200 A AC and 4000 A DC
Vertical connection 4000 A AC (terminal face length k = 40 mm)
100
10
k
69
5545 130
130
4,6
10
177
197
130
55
130
12
287
59
33
10
Siemens · 04/2018
59
3
69
282,5
142,5
26
46
400
40
45
130
130
130
m
f
c
169,5
130
NSE0_00654c
NSE0_00653a
90
m
14
130
Flat terminals
M
90
3
6
10
10
40
45,1
130
55
69
h
d
10
40
530
400
90
90
40
55 45 130
130
130
287
g
373
NSE0_00645d
3
287
h
NSE0_00647c
13,5
26
e
62,5
40
90
NSE0_00648d
NSE0_00644c
40
40
Ø13,5
62,5
90
90
373
400
90
90
121
200
130
Front connection (double hole)
530
c
169,5
45
200
Front connection (single)
6
10
20
69
157
172
109,5
NSE0_00651b
287
3
NSE0_01869
315,5
30
NSE0_00650c
b
290
135
100 30
30
j
30
530
400
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Configuration aids
Dimensions in mm
Item number
Dimensions
Ue, Z suffix or breaking capacity X
Standard
DC: 600 V
A05, A15 or C
DC: > 600 V
&
Grooves (4 mm wide, 5 mm deep) for supporting phase partitions in the system
Auxiliary connector with:
(
• SIGUT screw terminals (one-part)
465 (446)
515 (496)
)
• Screwless connections
468
518
*
Dimension to inside surface of the closed cabinet door
58.0
.
Fixing holes
9
/
Circuit breaker in connected position
88.5
0
Circuit breaker in test position
121.5
1
Circuit breaker in disconnected position
140.5
2
Space for cable harness to electrical auxiliary circuit connections
20
3
Maximum device height
468
518
4
Guide frame upper edge
460
510
789 Safety clearances
See below
Connection dimensions in mm
Max. rated circuit breaker current
• Up to 20005) A AC/2000 A DC
• 25005) A AC
• 3200 A AC/4000 A DC or for breaking capacity C
a
10
15
30
b
10
15
30
Busbar thickness
c
10
20
20
d
11
6
6
Clearance
e
403
413
413
Clearance
f
34
39
39
Overhang
g
493
503
503
Clearance
h
35
j
38
--
m
80
--
Terminal face length
Safety clearances in mm
SZ II, withdrawable version
... from grounded or non-conductive parts
... from live parts
Above 7
Above 7
At side
At rear
IT system
At side 8
At rear 9
Above 7
Without/with
Without/with
Without
Arc chute covers
Without1) / with Without/with
Operational voltage
Standard arc chutes – 4 = 460 mm
500 V AC
460 / 460
0 / 702)
0/0
715 / 480
50 / 50
14 / 14
550
690 V AC
460 / 460
0 / 702)
0/0
1065 / 480
100 / 225
30 / 14
--
300 V DC
495 / --
0 / --
0 / --
3)
3)
3)
--
600 V DC
650 / --
0 / --
0 / --
3)
3)
3)
-6004)
Without/with Without/with
Operational voltage, breaking capacity High arc chutes – 4 = 510 mm (A05, A16 or DC)
690 V AC, H
510 / --
0 / --
0 / --
1015 / --
105 / --
30 / --
690 V AC, C
510 / --
0 / --
0 / --
775 / --
100 / --
30 / --
690 V AC + 20% H
620 / --
0 / --
0 / --
1015 / --
100 / --
140 / --
--
1000 V AC, H
620 / --
0 / --
0 / --
1015 / --
100 / --
140 / --
--
1150 V AC
620 / --
0 / --
0 / --
3)
3)
3)
--
1000 V DC
615 / --
0 / --
0 / --
3)
3)
3)
--
1)
Values for struts, grids and perforated sheets. When using plates with
conductive surfaces: values on request.
2)
Value for plates that cover the lateral openings in the guide frame,
0 mm for struts and grids
3)
With insulating shield; for clearance, see "non-conductive parts"
4)
Ue = 1000 V with breaking capacity H and Z option Z = A05
5)
Does not apply to breaking capacity C.
Siemens · 04/2018
47
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Configuration aids
Size III, up to 6300 A, fixed-mounted version, 3- and 4-pole
Standard version, horizontal connection
21
14
12
35
210
15
210
210
160
130
h
30
5,5
150
210
230
NSE0_00658h
890
Ø13,5
7
7
3
110 (150)
4x Ø11
20
NSE0_00661j
139
704
4x M10
248
914
Vertical connection (terminal face length k = 40 mm)
10
107
3
NSE0_00663a
k
NSE0_00662c
330,5
94,5
120
15
30
10
85
Ø14
142
162
210
210
210
M10
Front connection (single)
Ø1
3,5
160
160
160
NSE0_00657d
421
3
20 82
M10
130
26
11
h
6
160
5050
h
NSE0_00656d
451
47
210
210
210
Front connection (double hole)
47
160
5050
Ø13
160
160
160
m
NSE0_00660d
421
NSE0_00659e
6
3
48
M10
14
20 82
m
40
34
541
40
,5
130
Siemens · 04/2018
210
210
210
45
127
15
3
NSE00664a
205
76
270
680
3
18
275
150
30
17
327,5
19
5
123,5
4
20
30
275
NSE0_00655c
130
6
210
210
210
130
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Configuration aids
Dimensions in mm
Item number
Dimensions
&
Grooves (4 mm wide, 5 mm deep) for supporting phase partitions in the system
(
• SIGUT screw terminals
437
)
• Screwless connections
440
• COM15/COM16
462
*
Dimension to inside surface of the closed cabinet door
106
+
Fixing points for mounting the circuit breaker in the system (grid dimensions in mm)
4 x M10 screw nut (150) and 4 x 11 (110)
2
Space for cable harness to electrical auxiliary circuit connections
Auxiliary connector with:
20
Ue, Z suffix or breaking capacity X
690 V AC, H
> 690 V AC, A05, or C
3
Maximum device height
462
462
5
Mounting space for removal of the arc chutes
541
591
6
Top edge of arc chutes
401
451
789 Safety clearances
See below
Connection dimensions in mm
h
35
k
40
m
80
Terminal face length
Safety clearances in mm
SZ III, fixed-mounted version ... from grounded or non-conductive parts
Above1) 7
At side
... from live parts
IT system
At rear
Above 7
At side 8
At rear 9
Above 7
Operational voltage
Standard arc chutes – 401 mm
500 V AC
460
0
0
515
20
20
450
690 V AC
460
0
0
965
100
125
--
Operational voltage
High arc chutes – 451 mm (> 690 V AC, A05 or C)
690 V AC
510
0
0
965
100
125
5002)
690 V AC + 10% H
615
0
0
865
100
125
--
690 V AC + 20% H
615
0
0
865
100
125
--
1000 V AC
615
0
0
865
100
125
--
1150 V AC
615
0
0
3)
3)
3)
--
1)
Values for struts, grids and perforated sheets. When using plates with
conductive surfaces: values on request.
2)
Ue = 1000 V with breaking capacity H and Z option Z = A05 or breaking
capacity C
3)
With insulating shield; for clearance, see "non-conductive parts"
Siemens · 04/2018
49
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Configuration aids
Size III, up to 6300 A, withdrawable version, 3- and 4-pole
Standard version, horizontal connection
382,5
367,5
327
NSE0_00668_h
14
20
5
840
NSE0_00665c
10
160
160
287
10
76
69
27
42
45
220
57 85
210
210
210
57
800
160
NSE0_00674h
30
275
150
Ø14
40
31
270
590
10
123,5
465,5
275
468,5
630
160
160
9
327,5
30
4
21
Ø13
30
30
30
j
,5
NSE0_00671h
139
270
704
260
217
914
Vertical connection, up to 6300 A
Flange connection, up to 4000 A
840
630
704
160
57 a
b
b
10
210
121
10
590
l
287
69
l
282,5
142,5 26
NSE0_00673h
5
57 85
10
30
210
210
800
914
704
914
Front connection (double hole)
11
50
85
26
10
57
Siemens · 04/2018
210
210
590
800
210
160
50 50
160
160
287
m
373
14
493
6
m
34
287
h
69
6
20
169,5
40
Ø13,5
62,5
h
373
403
NSE0_00666c
160
20
169,5
10
40
160
630
160
50 50
NSE0_00669c
13,5
160
50 50
840
NSE0_00667d
840
630
160
50 50
85
210
590
210
800
210
69
Front connection (single)
62,5
210
590
800
NSE0_00670d
24
177
197
160
160
33
NSE0_00675b
NSE0_00672c
330,5
94,5
124,5
30
Ø14
160
12
j
M
10
20
NSE0_00676c
840
630
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Configuration aids
Dimensions in mm
Item number
Dimensions
Ue, Z suffix or breaking capacity X
 690 V AC, H
> 690 V AC, A05, or C
&
Grooves (4 mm wide, 5 mm deep) for supporting phase partitions in the system
(
• SIGUT screw terminals (one-part)
465 (446)
515 (496)
)
• Screwless connections
468
518
*
Dimension to inside surface of the closed cabinet door
58.0
.
Fixing holes
9
/
Circuit breaker in connected position
88.5
0
Circuit breaker in test position
121.5
1
Circuit breaker in disconnected position
140.5
2
Space for cable harness to electrical auxiliary circuit connections
20
3
Maximum device height
468
518
4
Guide frame upper edge
460
510
789
Safety clearances
See below
Auxiliary connector with:
Connection dimensions in mm
Max. rated circuit breaker current
• Up to 4000 A AC
• 5000 V AC
• 6300 V AC
a
40
40
5
b
210
210
245
h
35
--
--
j
38
l
59
--
--
m
80
--
--
Clearances
Terminal face length
Safety clearances in mm
SZ III, withdrawable version
... from grounded or non-conductive parts
... from live parts
Above 7
Above 7
At side
At rear
IT system
At side 8
At rear 9
Above 7
Without/with
Without/with
Without
Arc chute covers
Without1) / with Without/with
Operational voltage
Standard arc chutes – 4 = 460 mm
500 V AC
460 / 460
0 / 402)
0/0
510 / 480
20 / 50
14 / 14
460
690 V AC
460 / 460
0 / 402)
0/0
965 / 480
100 / 200
14 / 14
--
Without/with Without/with
Operational voltage, breaking capacity High arc chutes – 4 = 510 mm (> 690 V AC, A05, A16 or C)
690 V AC
510 / --
0 / --
0 / --
965 / --
100 / --
14 / --
5103)
1000 V AC, H
615 / --
0 / --
0 / --
865 / --
100 / --
14 / --
--
1000 V AC, C
615 / --
0 / --
0 / --
865 / --
100 / --
14 / --
--
1150 V AC
615 / --
0 / --
0 / --
4)
4)
4)
--
1)
Values for struts, grids and perforated sheets. When using plates with
conductive surfaces: values on request.
2)
Value for plates that cover the lateral openings in the guide frame,
0 mm for struts and grids
3)
Ue = 1000 V with breaking capacity H and Z option Z = A05 or breaking
capacity C
4)
With insulating shield; for clearance, see "non-conductive parts"
Siemens · 04/2018
51
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Configuration aids
■ Circuit diagrams
Terminal assignment diagram
optional
Accessories
(Auxiliary switch S1, S2 = Standard)
Internal wiring
Terminals
External wiring
L / L+ U /U
s c
N / L–
e.g. current transformer in the
star point of power transformer
or a summation current
transformer 1200 A /1A
14
Remote reset solenoid F7
12
11
10
Jumper if no N transformer
9
8
N
7
L3
6
L2
L1
5
4
24 V DC input
3
Termination resistor,
if no external CB module!
2
8
7
Signaling switch on
1st auxiliary release S22
6
5
4
3
Signaling switch on
2nd auxiliary release S23
2
1 2 3 4 5 6 7 8 9
9
2nd tripped signaling switch S25 1NO
COM15/COM16
(Option F02/F12)
L / L+ Us/Uc
Tripped signaling switch (optional)
Internal
10
Electrical ON button S10
External
11
Stored energy status indication S21
Y1
12
Close
– +
13
Free
– +
14
DPWrite Free
Enable
1st tripped signaling switch
(RESET position) S24
Open
– + OUT
F1, 2
1
IN
Not available with communication connection "F02" or "F12".
COM15/COM16 module is at position "-X7".
13
G transformer S2
G transformer S1
N transformer S2
N transformer S1
ext. voltage transformer Com
ext. voltage transformer L3
ext. voltage transformer L2
ext. voltage transformer L1
0 V DC
24 V DC
CubicleBUS +
CubicleBUS –
1
L / L+
Uc
N / L–
14
1st auxiliary release F1 "ST"
13
12
S1 "NO"
11
10
S1 "NC"
9
Closing coil
N / L–
Uc
L / L+
8
7
6
5
"Ready to close" signal S20
4
S2 "NO"
3
2
S2 "NC"
1
F4 only "quick OFF"
F4 only "quick OFF"
2nd auxiliary release: F2 "ST", F3 "UVR", F4 "UVR td"
14
EMERGENCY STOP
or jumper
L / L+
Uc
N / L–
13
12
11
10
S3 "NO" or S7 "NO"
9
8
S3 "NC" or S7 "NO"
7
6
S4 "NO" or S8 "NO"
5
4
S4 "NC" or S8 "NO"
Charging motor
opt. motor main switch S12
(sw)
M
(br)
3
L / L+
Uc
N / L–
2
1
NSE0_00605r
52
Siemens · 04/2018
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Configuration aids
Example of an overall circuit diagram for 3WL circuit breakers
(3WL1. ..–.....–4GN4–Z C11+ C22 + K07)
Manual / motorized operating mechanism with stored-energy
feature, with electrical ON button (option C11), with ready-toclose signaling switch (option C22), with Electronic Trip Unit
L1
(L+)
release
contact
LSING with undervoltage release "UVR" (F3), with shunt trip "ST"
(F1), with tripped signaling switch (option K07), with auxiliary
switch 4 NO + 4 NC.
L1
(L+)
OFF
-X5.6
-X5.4
-X5.10
-X5.8
-X6.4
-X6.2
-X6.12
-X6.10
ETU
L
TRIP
electr.
ON
version
S
RESET
-S10
-A1
5
1
3
-X6.6
-X7.12
-X7.14
-X5.12
-X6.14
-X6.7
-X7.9
-X5.2
ON
I
N N
G
R
-S11
-S24
-S20
-F5
-S2
-S1
-Q1
P
QS
-S4
-S3
-T1
M
-T2
NSE0_01558b
-T3
-S12
-X5.5
-X5.3
-X5.9
-X5.7
-X6.3
-X6.1
-X6.9
-X6.11
6
2
4
-X8.9
N
(L-)
-X8.10
-X7.13
-X6.5
*
-X5.11
-X6.13
-F1
-X6.8
-X5.1
N
(L-)
U<
-Y1
mech.
ON
mech.
OFF
-F3
* Short terminals, if no N transformer
Function diagram of 3WL air circuit breaker
-A1
-S1/-S2
-S3/-S4
-S7 (optional)
F1
F2
S20
F3
-S8 (optional)
F4
M1
Q1
P
1
-S10
-S11
-S12
Y1
A1
2
T1
T2
T3
T4
3
NSE0_01559e
3WL1. ..-.....-...2
3WL1. ..-.....-...4
3WL1. ..-.....-...7
3WL1. ..-.....-...8
S1 & S2
S3 & S4
S24 S25
F5
L
S
I
N N
G
ETU Electronic Trip Unit
1st auxiliary switch block (2 NO + 2 NC)
2nd auxiliary switch block (2 NO + 2 NC)
2nd auxiliary switch block, S7 (2 NO) can be used
if there is no S3 – S3 and S7 have the same terminal
assignment/mounting location
2nd auxiliary switch block, S8 (2 NO) can be used
if there is no S4 – S4 and S8 have the same terminal
assignment/mounting location
(2 NO + 2 NC) S1+S2
(4 NO + 4 NC) S1+S2+S3+S4
(6 NO + 2 NC) S1+S2+S7+S8
(5 NO + 3 NC) S1+S2+S3+S8
-S20
-S24
Electrical ON button
Internal motor shutdown switch (if spring is tensioned)
Motor shutdown switch
(no automatic tensioning of spring)
Ready-to-close signaling switch
Tripped signaling switch
-F1
-F3
-F5
1st auxiliary release, shunt release
2nd auxiliary release, undervoltage release
Tripping solenoid
-M
-P
-QS
-Q1
-T1/-T2/-T3
-X5/-X6/-X7/-X8
-Y1
-R
Motor for "charging energy store"
Spring energy store
Actuator lever for "charging energy store"
Main contacts
Current transformers
Terminals
Closing coil
Display and reset button for Electronic Trip Unit
-X8.9/-X8.10
Connection option: external N transformer
Siemens · 04/2018
53
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC), IEC
Configuration aids
Example of the mode of operation of Zone Selective Interlocking function in power distribution
5
6
1
2
3
4
ZSI
module
ZSI module
SENTRON 3WL
3
4
5
6
ZSI
module
SENTRON 3WL
3
4
5
6
SENTRON 3WL
SENTRON 3WL
ZSI
module
SENTRON 3VL
NSE0_01898
3
4
5
6
Circuit diagram for a Zone Selective Interlocking function with multiple
infeed and several outgoing units with 3WL circuit breakers
NSE0_01897
ZSI
module
SENTRON 3WL
3
4
5
6
SENTRON 3WL
3
4
5
6
ZSI
module
SENTRON 3WL
3
4
5
6
ZSI
module
SENTRON 3WL
3
4
5
6
ZSI
module
ZSI
module
SENTRON 3WL
3
4
5
6
3VL and 3WL circuit breakers used in various staggered levels
ZSI module
SENTRON 3WL
3
4
5
6
ZSI
module
5
6
1
2
3
4
ZSI
module
SENTRON 3WL
3
4
5
6
NSE0_01899
SENTRON 3WL
SENTRON 3WL
3
4
5
6
ZSI
module
ZSI
module
SENTRON 3WL
3
4
5
6
ZSI function: Connection using a tie-breaker, use of 3WL circuit breakers
■ More information
Up-to-date information on the Internet at:
http://www.siemens.com/sentron
54
Siemens · 04/2018
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Non-Automatic Air Circuit Breakers up to 4000 A (DC)
General data
■ Technical specifications
Size
I
II
3WL11 20 3WL12 10
Type
Rated current In at 40 °C
Main conductor
A 2000
3WL12 20
3WL12 40
... 1000
2000
4000
Rated operational voltage Ue
(1000 V version, see Catalog LV 10, order code "A05")
V DC 1000
... 600/1000
... 600/1000
... 600/1000
Rated insulation voltage Ui
V DC 1000
1000
1000
1000
kV 12
kV 4
kV 2.5
12
4
2.5
12
4
2.5
12
4
2.5
Yes
B
Yes
Yes
C –25/+70
C –40/+70
A 2000
A 1910
A 1850
A 1710
–25/+70
–40/+70
–25/+70
–40/+70
–25/+70
–40/+70
1000
1000
1000
1000
2000
2000
2000
1950
4000
3640
3500
3250
W 150
280
770
1640
35
34
35
34
35
34
• Electrical make time (through activation solenoid)1)
• Electrical opening time (through shunt release)
ms 35
ms 38
ms 100
ms 73
100
73
100
73
100
73
• Electrical opening time (instantaneous undervoltage release)
ms 73
73
73
73
Yes
Isolating function acc. to EN 60947-2
Utilization category
Permissible ambient temperature
• Operation
• Storage
Permissible load
At rear horizontal main circuit
connections
(Cu painted black)
Up to 40 C
Up to 55 C
Up to 60 C
Up to 70 C
Power loss at In for symmetrical loads
Withdrawable circuit breakers
Switching times
• Make time
• Opening time
Endurance3)
• Mechanical (without maintenance)
• Mechanical (with maintenance)2)
• Electrical (without maintenance)
• 1000 V version
• Electrical (with maintenance)2)
Operating cycles 10 000
Operating cycles 15 000
Operating cycles 1000
Operating cycles 1000
Operating cycles 2000
Switching frequency
• 600 V version
• 1000 V version
1/h -1/h 20
10000
15000
6000
1000
15000
10000
15000
6000
1000
15000
10000
15000
4000
1000
15000
60
20
60
20
60
20
30° 30°
30° 30°
Mounting position
Dhmax.
= 1 mm
Rated impulse withstand voltage Uimp
• Main conducting paths
• Auxiliary circuits
• Control circuits
and/or
NSE0_00061a
NSE0_00062a
NSE0_00927
IP20 without cabinet door, IP41 with door sealing frame, IP55 with cover
Degree of protection
Standard connection = strain-relief clamp
• Without end sleeve
• With end sleeve acc. to DIN 46228 Part 2
• With twin end sleeve
2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16); 1 × 2.5 mm2 (AWG 14)
1 × 0.5 mm2 (AWG 20) ... 1 × 1.5 mm2 (AWG 16)
2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16)
Optional connection = tension spring
• Without end sleeve
• With end sleeve acc. to DIN 46228 Part 2
2 × 0.5 mm2 (AWG 20) ... 2 × 2.5 mm2 (AWG 14)
2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16)
Weights 3-pole
• Fixed-mounted circuit breakers
• Withdrawable circuit breakers
• Guide frames
kg 43
kg -kg --
56
60
31
56
60
31
64
68
45
4-pole
• Fixed-mounted circuit breakers
• Withdrawable circuit breakers
• Guide frames
kg 50
kg -kg --
67
72
37
67
72
37
77
82
54
Auxiliary conductors (Cu)
Max. number
Auxiliary conductors ×
cross-section
(solid/stranded)
1)
2)
Make time through activation solenoid for synchronization purposes
(short-time excited) 50 ms.
Maintenance means: Replace main contact elements and arc chutes (see
Operating Manual).
3)
Further technical specifications on request.
Size
I
II
Type
3WL11
3WL12
Breaking capacity
DC
DC
kA
kA
kA
kA
20
20
20
20
35
30
25
20
kA
kA
kA
kA
-20
---
-351)/302)/253)/204)
---
Rated short-circuit breaking capacity
Up to 220 V DC
Up to 300 V DC
Up to 600 V DC
Up to 1000 V DC
Icc
Icc
Icc
Icc
Rated short-time withstand current Icw
0.5 s
1s
2s
3s
1)
2)
At Ue = 220 V DC
At Ue = 300 V DC
3)
4)
At Ue = 600 V DC
At Ue = 1000 V DC
Siemens · 04/2018
55
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Non-Automatic Air Circuit Breakers up to 4000 A (DC)
Configuration aids
■ Characteristic curves
[s]
10000
R=
0.4 ... 1.0 n
2 ... 10 s at 6
= 1.25 R ... 4
R=
1000
R
= 0.4
R
n
= 1.0
n
I
R=
B
100
B
A
R
n
10 s [B]
2 s [A]
A
10
1
0,01
0,1
I=
R
1.5
R
MAX
4 n
I=
NSE0_01578
MIN
1.25
I=
0,1
1
10
/
n
DIGmat S100 characteristic curve
■ Dimensional drawings
DIGmat S100
DIGmat S100
DIGmat S100 drilling pattern
Note:
For dimensional drawings for non-automatic circuit breakers
up to 4000 A (DC), see page 38 to 47.
56
Siemens · 04/2018
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Non-Automatic Air Circuit Breakers up to 4000 A (DC)
Configuration aids
■ Circuit diagrams
L1
AC230
N
PE
+
DC24
AC230
X1.2 X1.1
X5.2 X5.1
DIGmat S100
Auxiliary power
„Emergency STOP”
+
X4.i1+
DC24
X4.i1-
X2.1 +
Digital input
+
Shunt
(60mV)
-
X2.3 -
X4.i2+
X4.i2„Automatic RESET”
Digital output
X4.01 X4.01 X4.02 X4.02 X4.03 X4.03 X4.04 X4.04
+
-
+
-
+
-
+
-
-K1
14
-Q01
11
Automatic / Reset
NSE0_01577a
Excitation / Alarm
12
12
-K2
14
11
1
3
5
-X6.14 -X5.12
SENTRON
3WL
-F1
-F3
-X6.13 -X5.11
-Q01 2
4
6
Circuit diagrams of the DIGmat S100 and the 3WL non-automatic air circuit breaker
Application examples of size 2 – non-automatic circuit breakers (DC)
Rated operational
voltage
Required
series-connected
contact gaps at
rated voltage
For 3-pole non-automatic air circuit breakers
For 4-pole non-automatic air circuit breakers
(operational currents up to 4000 A/conducting path) (operational currents up to 4000 A/conducting path)
Up to 300 V + 10%
NSS0_00539
1-pole,
2-pole
2 parallel conducting paths,
only with grounded system
1-pole,
3 parallel conducting paths,
only with grounded system
2-pole
2 parallel conducting paths
2-pole,
only with grounded system
1-pole,
2 parallel conducting paths,
only with grounded system
2-pole
1-pole,
only with grounded system
2-pole,
only with grounded system
1-pole,
only with grounded system
Over 300 V + 10%
Up to 600 V + 10%
Over 600 V + 10%
Up to 1000 V + 10%
(version for 1000 V
required, order with
"-Z" and code A05)
The connection to the circuit breakers is not dependent on
direction and polarity; the circuit diagrams can be adapted
accordingly.
of 1 m from the connecting bars, the circuit breaker can be used
at full operational current load.
]
Grounded system
If the parallel or series connections are made directly to the
connecting bars, for thermal reasons the continuous load on the
circuit breakers must only be 80% of the permissible operational
current. If the parallel or series connection is made at a distance

Load
Siemens · 04/2018
57
© Siemens AG 2018
3WL1 Air Circuit Breakers
3WL1 Non-Automatic Air Circuit Breakers up to 4000 A (DC)
Configuration aids
Application examples of size 1 – non-automatic circuit breakers (DC)
Permissible interconnections
Circuit diagrams for size 1
1000 V DC non-automatic air circuit breakers
Non-grounded system
+ (-)
- (+)
Grounded system
+ (-)
- (+)
Ground
Load
*B,B;;B
Load
■ More information
Up-to-date information on the Internet at:
www.siemens.com/sentron
58
Siemens · 04/2018
© Siemens AG 2018
© Siemens AG 2018
Siemens AG
Energy Management
Low Voltage & Products
Postfach 10 09 53
93009 REGENSBURG
GERMANY
www.siemens.com/lowvoltage
Subject to change without prior notice
PDF (3ZW1012-3WL11-0AC1)
PH 0718 60 En
Produced in Germany
© Siemens AG 2018
The information provided in this brochure contains merely general
descriptions or characteristics of performance which in case of actual
use do not always apply as described or which may change as a result
of further development of the products. An obligation to provide the
respective characteristics shall only exist if expressly agreed in the
terms of contract. Availability and technical specifications are subject
to change without notice.
All product designations may be trademarks or product names of
Siemens AG or supplier companies whose use by third parties for their
own purposes could violate the rights of the owners.