DATASHEET R250 AVR FOR SHUNT ALTERNATORS CHARACTERISTICS ••Voltage regulation : ± 0.5 %. ••U/F function. ••LAM function. ••Quick response : 500 ms. ••Nominal excitation current : 5A. ••Maximum excitation current : 7A during 10 s. ••Supply range / voltage detection : 85 to 139 V (50/60Hz). R250 is an analog AVR with power controled by transistors. It is designed for small alternators with a SHUNT excitation. ••Protection : fuse 8A. R250 controls the excitation current in order to maintain the output voltage of the alternator. R250 is performant in terms of voltage regulation, simple to set, to use and is reliable. It is in compliance with I.E.C. 60034-1 standard and U.L. 508 / C.S.A. approved. OPERATION RANGE LSA 40 42,3 44,3 46,3 47,2 49,3 50,2 51,2 53,1 54 - - - - SHUNT - AREP - - - - - - - - - - PMG - - - - - - - - - - Operation mode : Standalone ANALOG AVR R25 0 - REF. 45 4 8 en-2017.11/e www.leroy-somer.com/epg MAIN FEATURE OPERATION CONDITIONS U/F FUNCTION ••Operating temperature range : ••Vibrations : less than 10 Hz , •• Storage temperature range : ••From 10 Hz to 100 Hz : 100 mm/s, Voltage Knee 60 Hz - 40° C to + 65° C. 57 Hz - 55° C to + 85° C. Knee 48 Hz 100 % U/UN 2 mm peak magnitude. below 100 Hz : 8g. ••Hygrometry : 98%. ••Maximum choc : 9 g on 3 axis. 50 Hz Frequency 50 Hz 60 Hz Hz LAM FUNCTION Transient voltage drop with LAM LAM Load on the shaft (kW) Max. speed drop 0,9 (U/f) without LAM 0,8 with LAM 0 1s 0,9 Time 2s 3s without LAM 0,8 0 1s 2s CONNEXION AND SETTING setting. 3s R250 110 0V E+ E140 mm F1 Slow fuse 250V 8 A P1 Voltage Stability KNEE KNEE 47.5Hz 47.5 Hz 99 LAM LAM OFF OFF SPECIAL SPECIAL KNEE KNEE 65Hz 65Hz LAM LAM OFF OFF KNEE KNEE 57Hz 57Hz LAM LAM OFF OFF 88 77 50Hz 50Hz oo 99 00 11 66 55 LAM LAM OFF OFF 11 13% 13% 22 3 23 2 P2 STAB VOLT ••Potentiometer ST4 : remote voltage 2s 33 44 60Hz 60Hz 25% 25% FREQ. & L.A.M. CONFIG. LAM function 1s 0 Time 4 x holes Ø 5.8 x 50 x 115 mm Settings are done through the AVR. ••Potentiometer P1 : voltage setting. ••Potentiometer P2 : stability setting. ••Strap ST3 : frequency selection. ••Jumper : frequency, U/F function, Load shedding due to LAM Time 3s 75 mm Variation in the load 8 78 7 fN 456 UN OFF OFF 13% 13% 25% 25% LAM LAM ST4 Option External potentiometer for voltage adjusting Frequency selector 50 Hz / 60 Hz , U/F function and LAM function © Nidec 2017. The information contained in this brochure is for guidance only and does not form part of any contract. The accuracy cannot be guaranteed as Nidec have an ongoing process of development and reserve the right to change the specification of their products without notice.