Uploaded by craj_mohan

258272313-Schneider-Vip300-v302

advertisement
VIP300 O&M COVER (4/02)
6/4/02
1:02 am
Page 2
Merlin Gerin
VIP 300 protection relay
Operation, testing and
commissioning
version 003 / April 2002
VIP300 O&M CAT (4/02)
6/4/02
1:03 am
Page 1
VIP 300
Contents
Content
page
Use and settings
Relay front panel
4
Curve selection
5
Phase overcurrent
setting area
6
Earth fault setting area
7
Other functions
(labels, LED’s, VAP6)
8-9
Testing and
Commissioning
Overview of VAP6 test unit
10
VAP6 test sequence
11
Commissioning Ringmaster
with VIP 300
12-15
3
VIP300 O&M CAT (4/02)
6/4/02
1:03 am
Page 2
VIP 300
Relay front panel
1
2
3
4
C B
phase
overcurrent
5
7
8
6
10
A
I>
sensors:
200/1 4509996A0
VIP300LH range: x2
I>>
DT only
EI
VI
RI
1.2
DT
1
0.15 0.2
0.3
0.1
0.07
0.4
0.05
warning
0.1
not time
multiplier
x1
20
3
(x Is) off
0.2
0.4
0.6
0.05
0.9
0.03
0.6
(s)
t>
Is
x10
15
4
3
(x Is)
12
6
2.7
curve selection
42 48 56
36
64
30
72
24
80
20 100 90
(A)
9
2.4
1.5
off
VIP300
2.1
1.8
SI
I>
trip
9
1.5
(s)
t>>
see table
reset
minimum operating
phase current: 20A
Io>
EI
1.8
SI
RI
DT
trip
2.1
1.2
1
9
2.4
1.5
off
t> to>
0.05
0.07
0.1
0.15
0.2
0.3
0.4
0.05
0.6
0.07
0.1
0.15
0.2
0.3
0.4
0.6
x1
x1
x1
x1
x1
x1
x1
x10
x1
x10
x10
x10
x10
x10
x10
x10
SI
VI
EI
0.02
0.02
0.03
0.05
0.07
0.10
0.13
0.17
0.20
0.24
0.34
0.50
0.67
1.01
1.35
2.02
0.03
0.05
0.07
0.10
0.13
0.20
0.27
0.33
0.40
0.47
0.67
1.00
1.33
2.0
2.67
4.00
0.06
0.09
0.12
0.19
0.25
0.37
0.50
0.62
0.74
0.87
1.24
1.86
2.48
3.71
4.95
7.43
Io>>
DT only
VI
VIP 300 Equivalent Time
Settings Multiplier
15
4
2.7
3
3
warning
0.1
(x Ios)
12
6
20
off
(x Ios)
curve selection
16 24 32
12
40
8
50
4
60
2 80 70
(A)
Io>
0.15 0.2
0.07
x10
0.4
0.05 (s)
x1
0.6
not time
multiplier
0.2
0.4
0.6
0.05
0.9
0.03
to>
Ios
earth fault
0.3
0.1
to>>
see table
1.5
(s)
VAP6 test plug
D
11 12
13
14
15
E
17
18
16
19
20
Phase overcurrent setting
Earth fault setting
Other functions
1.
11.
A.
B.
2.
3.
4.
5.
6.
7.
8.
9.
10.
4
Phase setting area
(upper half of relay front panel).
Red LED phase overcurrent
pick-up indicator.
Phase overcurrent trip indicator.
Phase overcurrent setting Is.
Choice of low set curve type I>.
Low set pick-up (DT only) I>.
Low set time delay t>
Multiplying factor (low set).
High set pick-up I>>
High set time delay t>>
12.
13.
14.
15.
16.
17.
18.
19.
20.
Earth fault setting area
(lower half of relay front panel).
Red LED earth fault pick-up
indicator.
Earth fault trip indicator.
Earth fault setting current Ios.
Choice of low set curve type Io>.
Low set pick-up (DT only) Io>.
Low set time delay to>.
Multiplying factor (low set).
High set pick-up Io>>.
High set time delay to>>.
C.
D.
E.
Current setting scale label.
Current transformer and
range information.
Indicator reset button.
Minimum operating current.
VAP6 test plug socket.
VIP300 O&M CAT (4/02)
6/4/02
1:03 am
Page 3
VIP 300
Curve selection
Phase overcurrent setting
IDMT curve selection
t
The numbers indicated below are those
of the setting switches (refer to the
diagram of the front panel on page 4)
The letters indicate the curve
characteristic as shown opposite.
G
SI, VI, EI RI
t>
J
K
t>>
L
Phase overcurrent setting:
F ■ Setting current Is (4)
G ■ Type of low set I> curve (5)
IDMT: SI, VI, EI, RI.
Definite time: DT
H ■ DT low set pick-up I> (6)
This setting is only active for the
low set DT curve selection (as
shown). If IDMT curves are
selected this switch is disabled,
as SI,VI, EI, low set pick-up is
fixed at 1.2 Is.
J ■ Low set time delay t> (7)
and multiplier (8)
K ■ High set I>>(9)
L ■ High set time delay t>>(10)
Earth fault setting
Is
F
1.2 Is
10 Is
I>>
The principle is the same as for phase
protection.
Set:
F ■ Setting current Ios (14)
G ■ Type of low setting Io> curve (15)
IDMT: SI, VI, EI, RI
Definite time: DT
H ■ DT low set pick-up Io> (16)
This setting is only active for the
low set DT curve selection (as
shown). If IDMT curves are
selected this switch is disabled,
as SI, VI, EI low set pick-up is
fixed at 1.2 Is.
J ■ Low set time delay to> (17)
and multiplier (18)
K ■ High set Io>>(19)
L ■ High set time delay to>>(20)
DT curve selection
t
H
t>
DT
G
J
K
t>>
Is 1.2 Is
L
Operation
The high and low set elements
operate separately. The tripping order
results from the “ logical OR” between
the two settings.
I>
I>>
F
5
VIP300 O&M CAT (4/02)
6/4/02
1:03 am
Page 4
VIP 300
Use and setting
1.
Phase overcurrent
phase
overcurrent
sensors:
200/1 4509996A0
VIP300LH range: x2
I>
I>
EI
1.8
1.5
off
DT
1.2
42 48 56
36
64
30
72
24
80
20 100 90
(A)
Is
reset
0.05
t>
0.3
0.4
(s)
9
2.4
(x Is) 3
warning
0.15 0.2
0.1
0.07
x10
x1
VIP300
2.1
2.7
1
curve selection
trip
I>>
DT only
VI
SI
RI
not time
multiplier
15
3
(x Is) off
4
20
0.2
see table
t>>
0.4
0.6
0.1
0.05
0.03
0.6
12
6
0.9
(s)
1.5
VIP 300 Equivalent Time
Settings Multiplier
t> to>
0.05
0.07
0.1
0.15
0.2
0.3
0.4
0.05
0.6
0.07
0.1
0.15
0.2
0.3
0.4
0.6
x1
x1
x1
x1
x1
x1
x1
x10
x1
x10
x10
x10
x10
x10
x10
x10
SI
VI
EI
0.02
0.02
0.03
0.05
0.07
0.10
0.13
0.17
0.20
0.24
0.34
0.50
0.67
1.01
1.35
2.02
0.03
0.05
0.07
0.10
0.13
0.20
0.27
0.33
0.40
0.47
0.67
1.00
1.33
2.0
2.67
4.00
0.06
0.09
0.12
0.19
0.25
0.37
0.50
0.62
0.74
0.87
1.24
1.86
2.48
3.71
4.95
7.43
Phase overcurrent
setting area
All information concerning the phase
overcurrent is grouped together in the
upper half of the front panel. The
section numbers below are related to
the numbering on the drawing shown
on page 4.
2.
Phase overcurrent
pick-up indicator
When the red LED blinks, it indicates
that the low set element has picked up.
If the current does not decrease below
the pick-up level the relay will trip.
■
For IDMT curves (SI, VI, EI) the
LED blinks when the current is
greater than 1.2 times the setting
current Is.
■
For the IDMT curve (RI), the LED
blinks when the current is greater
than the setting.
■
For the DT curve, the LED blinks
when the I> pick-up setting
is exceeded.
Also refer to “indicator reset button”
(page 9).
3.
SI
VI
EI
RI
6.
:
:
:
:
Low set pick-up
(DT only) I>
The setting is a multiple of Is. It is only
active when the low set curve type DT
is selected.
If the tripping curve is selected with
IDMT (selector switch 5 set to SI, VI,
EI, RI) the selector switch has no effect.
7.
Low set time delay t>
■
If the DT curve is selected,
the value shown is the low set
time delay.
For IDMT curves the value
displayed is the tripping time for a
phase current equal to 10 x Is.
■
The indicator is normally black and
turns yellow when the phase
overcurrent has given a tripping order.
It stays yellow, even when the relay is
de-energised.
8.
4.
9.
Setting current Is
Choice of low
set curve
Standard inverse time.
Very inverse time.
Extremely inverse time.
Specific curve
- consult Merlin Gerin
DT : Definite time.
Off : Low set is disabled.
Phase overcurrent trip
indicator
The setting depends on the current
transformer (CT) used, and the range
selected via the connections made to
the back of the relay. The scale label
inserted should match the CT and
range selected. The switch can then be
positioned to the primary current
magnitude required in amperes.
6
5.
Multiplying factor
(low set)
In the x10 position, the time delay
displayed on switch 7 is multiplied by10.
High set pick-up I>>
The high set is chosen as a multiple of
the current Is. In the “off” position, the
high set is disabled.
10. High set time delay t>>
Time delay is set directly in seconds.
VIP300 O&M CAT (4/02)
6/4/02
1:03 am
Page 5
VIP 300
Use and setting
The setting principle is the same as
for phase overcurrent.
Earth fault
reset
minimum operating
phase current: 20A
Io>
EI
1.8
2.1
1.2
1
9
2.4
1.5
off
DT
11. Earth fault setting
area
Io>>
DT only
VI
SI
RI
trip
2.7
(x Ios)
3
12
15
6
4
20
3
(x Ios) off
curve selection
Io>
earth fault
16 24 32
12
40
8
50
4
60
2 80 70
(A)
Ios
0.15 0.2
0.1
0.07
0.05 (s)
to>
warning
0.3
0.4
0.6
x10
x1
not time
multiplier
0.2
0.03
see table
to>>
0.4
0.6
0.1
0.05
0.9
(s)
1.5
VAP6 test plug
All information concerning earth fault
settings are grouped together in the
lower half of the front panel. Section
numbers below are related to the
numbering on the drawing shown on
page 4.
12. Earth fault pick-up
indicator
When the red LED blinks, It indicates
that the low set element has picked up.
If the current does not decrease below
the pick-up level the relay will trip.
■
For IDMT curves (SI, VI, EI) the
LED blinks when the current is
greater than 1.2 times the setting
current Is.
■
For the IDMT curve (RI), the LED
blinks when the current is greater
than the setting.
■
For the DT curve, the LED blinks
when the l> pick-up setting
is exceeded.
N.B. The LED only blinks when the
phase current is greater than the
minimum operating current (refer to
minimum operating current, page 9)
Also refer to “indicator reset button”
(page 9).
13. Earth fault trip indicator
The indicator is normally black and
turns yellow when the earth fault
element has given a tripping order. It
stays yellow, even when the relay is
de-energised.
14. Setting current Ios
The setting depends on the current
transformer (CT) used, and the range
selected via the connections made to
the back of the relay. The scale label
inserted should match the CT and
range selected. The switch can then be
positioned to the primary amp value
required.
For earth fault relay operation: link
between contacts 2 and 9 (x2 range)
and 1 and 9 (x4 range) must be made
at back of relay.
15. Choice of low
set curve
SI :
VI :
EI :
RI :
DT :
Off :
Standard inverse time.
Very inverse time.
Extremely inverse time.
Specific curve.
Definite time.
Low set is disabled.
16. Low set pick-up
(DT only) Io>
The setting is a multiple of Ios. It is only
active when the low set curve type DT is
selected. If the tripping curve is selected
with IDMT (selector switch 15 set to SI,
VI, EI, RI) the selector switch has no
effect.
17. Low set
time delay to>
■
■
If the DT curve is selected, the
value shown is the low set time
delay.
For IDMT curves the value
displayed is the tripping time for a
phase current equal to 10 x
Ios.
18. Multiplying factor
(low set)
In the x10 position, the time delay
displayed on switch 17 is multiplied
by 10.
19. High set pick-up Io>>
The high set is chosen as a multiple of
the current Ios. In the “off” position, the
high set is disabled.
20. High set time delay to>>
Time delay is set directly in seconds
7
VIP300 O&M CAT (4/02)
6/4/02
1:03 am
Page 6
VIP 300
Use and setting
A.
Other functions
Reversible scale label for Ringmaster fitted with 200/1A CT’s
sensor
200/1: 4509996A0
sensor
200/1: 4509996A0
VIP 300LH range: x2
VIP 300LHrange: x4
Is
Is
48
42
56
36
64
30
72
24
80
20 100 90
(A)
96
84
112
72
128
60
144
48
160
40 200 180
(A)
minimum operating
phase current: 20A
minimum operating
phase current: 40A
Ios
Ios
24
16
32
12
40
8
50
4
60
2 80 70
(A)
x 2 range
48
32
64
24
80
16
100
8
120
4 160 140
(A)
x 4 range
Reversible scale label for Ringmaster fitted with 400/1A CT’s
sensor
400/1: 451101200
sensor
400/1: 451101200
VIP 300LH range: x2
VIP 300LHrange: x4
■
The label indicates the range for
the phase overcurrent and earth
fault primary amp settings. It is
inserted from the top, behind the
transparent part of the front
panel.
■
The label is reversible and is
printed with the x2 range setting
currents on one side, and the x4
range setting currents on the
other. The scale label when
inserted should match the CT and
terminal positions on the rear of
the relay, for the range required.
Also refer to “testing and
commissioning”.
B.
CT and range
indication
The CT and range are given on each
side of the setting scale label. The label
will match the appropriate CT for the
Ringmaster panel type supplied. This
information is hidden when the label is
inserted.
Is
Is
96
84
112
72
128
60
144
48
160
40 200 180
(A)
192
168
224
144
256
120
288
96
320
80 400 360
(A)
Choice of setting scale label
minimum operating
phase current: 40A
minimum operating
phase current: 80A
■
Ios
Ios
48
32
64
24
80
16
100
8
120
4 160 140
(A)
x 2 range
96
64
128
48
160
32
200
16
240
8 320 280
(A)
x 4 range
Reversible scale label for Ringmaster fitted with 800/1A CT’s
sensor
800/1: 4509169A0
sensor
800/1: 4509169A0
VIP 300LH range: x2
VIP 300LHrange: x4
Is
Is
192
336
448
288
512
240
576
192
640
160 800 720
(A)
(A)
minimum operating
phase current: 80A
minimum operating
phase current: 160A
Ios
Ios
(A)
x 2 range
Make sure that the information
given on the top of the label
matches:
1 - The current transformer used:
200/1A, 400/1A or 800/1A
2 - The range used.
x2 or x4
This information is hidden when the
label is in position.
■
For help with the choice of range
to select, refer to the application
section.
Installation
384
168
224
144
256
120
288
96
320
80 400 360
96
64
128
48
160
32
200
16
240
8 320 280
8
Setting scale label
192 256
128
96
320
64
400
32
480
16 640 560
(A)
x 4 range
■
■
Slide the setting scale into
position behind the transparent
part of the front face.
Make sure the label is pushed
right into the bottom of the slot. To
remove the label, use the hole in
the top, if necessary with the help
of the tip of a pencil or a
screwdriver.
VIP300 O&M CAT (4/02)
6/4/02
1:03 am
Page 7
VIP 300
Use and setting
C.
Indicator reset button
The reset button can be operated with
the sealable cover either open or
closed. When the button is pressed, the
following actions are initiated:
■
It resets the phase overcurrent
and earth fault trip indicators.
N.B.
If reset is more than 48 hours
after the relay has operated and
is left without being energised,
the VAP6 must be used to reset
the trip indicators or the operator
must wait for the relay to be
re-energised.
■
The two red LED’s light up
simultaneously for approximately
three seconds to indicate the
following:
- The relay is energized and the
minimum operating current level
has been reached.
-The relay self testing results are
healthy
N.B.
If one of the two conditions is not
met, the indicators do not light up.
D.
Minimum operating
current
The minimum operating current is the
phase current required for the relay to
be energized and operational. The
setting depends on the CT used, and
the range selected via the connections
made to the back of the relay. The
value given on either side of the scale
label is the single phase RMS
minimum operating current.
N.B. Regarding minimum operating
current:
The VIP 300 does not operate below
the minimum operating current level.
As a result, if the earth fault setting
(Ios) is below the minimum operating
current, it will only take effect when
there is phase current greater than or
equal to the minimum operating
current.
E.
VAP6 test plug
The test plug is exclusively designed for
connection of the VAP6 which is used
for fast, simplified relay testing.
The operation may be carried out while
the relay is operating since the VAP6
and VIP 300 provide the possibility of
testing with inhibition of circuit breaker
tripping.
Also refer to the “testing and
commissioning” chapter.
This function may be used to
carry out a basic relay operation test.
Fitting of reversible scale label
9
VIP300 O&M CAT (4/02)
6/4/02
1:03 am
Page 8
VIP 300
Overview of the VAP6
VAP6 front panel
D
D
external mitop
+
I>
A
on
B
test in progress
C
trip
4
battery test
1
phase overcurrent
2
earth fault
3
trip
inhibition
earth fault
test
phase
overcurrent
test
phase
overcurrent
VIP 30
VIP 35
VIP300
VIP50
VIP75
VIP 11, 11R
VIP 12R
VIP13
VIP17
VIP200, 201
trip
trip
inhibition
external
mitop
The VAP6 is a portable unit which is
connected to the VIP 300 to carry out
simplified testing.
The test can be carried out in the
following two cases:
- the VIP 300 is already
powered up by the sensors
(CT’s).
- The VIP 300 is not supplied. In
this case, the VAP6 batteries
supply power to the relay.
Indicators
Push buttons:
C ■ Trip:
Is used to test other relays in the
VIP range. It is not to be
considered for the VIP 300 test (it
lights up for a transient period
when the VIP 300 sends a tripping
order; whether or not the circuit
breaker is inhibited).
1■
Battery test:
If the batteries are healthy, the
“on” indicator(A) lights up when
the button is pressed.
2■
Phase overcurrent:
Sends the phase overcurrent test
stimulus, which is equivalent to
20 times the setting current Is.
circuit breaker
mitop
circuit breaker
mitop
VAP6
3■
Earth fault:
Sends the earth fault test
stimulus, which is equivalent to
20 times the earth setting current
Ios.
4■
Trip inhibition:
By pressing and holding this
button down the relay can be
tested with the VAP6 without
tripping the circuit breaker. This
facility will inhibit the circuit
breaker tripping even if a real
fault occurs during the test.
A ■ On:
Indicates that the batteries are
operating. Also lights up when the
battery test is carried out by
pressing “battery test”.
B ■ Test in progress:
Confirms sending of the test
stimulus to the VIP 300.
D ■ “External MITOP” output:
This feature may be used to
connect an external MITOP trip
coil which could be used to
operate a timer etc. The external
coil is triggered at the same time
as the circuit breaker MITOP. The
trip inhibit button does not effect
the external coil.
Batteries:
■
The batteries are normally
deactivated and are automatically
activated when the VAP6 is
connected to the VIP 300. They
are activated in the following
cases:
- Pressing the “battery test”
button.
- Direct connection to a VIP 300
relay.
■
To install or change the batteries,
open the unit by removing the 4
screws on the bottom of the unit.
Be sure to use the correct
polarities.
Technical characteristics:
Supply:
Weight:
Dimensions:
10
3 x 9V 6LR61
batteries
0.45KG
93 X 157 X 45mm
VIP300 O&M CAT (4/02)
6/4/02
1:03 am
Page 9
VIP 300
VAP6 test sequence
The test may be carried out with or
without the relay energised by the
Ringmaster current transformers, and
all the relay settings are effective.
During the test, the relay remains
operational and will give a tripping
order in the event of a fault, unless the
“trip inhibit” button is pressed and held
down.
The test consists of:
- Initiation of the VIP 300 self
monitoring and diagnostic routine.
- Injecting a stimulus to stimulate
a phase fault.
- Check tripping
The VAP6 is supplied by
batteries. Therefore the parts of
the VIP 300 that run on AC
current are not checked using this
method (input and supply
circuits).
Press the “phase overcurrent” button to
send the test stimulus.
- Continue pressing the button
throughout the duration of the
stimulus. The stimulus represents
about 20 times the setting current
Is.
-The VAP6 “test in progress”
indicator lights up to confirm the
sending of the stimulus to the
VIP300 relay.
- The red “I>” indicator of the
VIP300 blinks during the time
relay delay period.
- Then the VIP 300 phase “trip”
indicator turns yellow.
- The circuit breaker trips if it is
not inhibited.
Connect the VAP6 to the “VAP6 test
plug”. The VAP6 batteries are activated
and the “on” indicator lights up.
Press the “trip inhibition” button if the
test should be carried out without
tripping the circuit breaker.
Be sure to continue pressing the
“trip inhibition” button throughout the
time it takes to send the stimulus.
N.B. If the “phase overcurrent” button is
held down after tripping, the VIP300
starts the time delay/tripping cycle
again; this is normal operation.
In that case:
- The VAP6 red “trip” indicator
lights up for a transient period
each time there is a trip.
- Depending on the time delay
setting, the VIP 300 red “I>”
indicator may be off or blink
rapidly and/or in an irregular
manner.
Press “earth fault” to test the relays
operation. The stimulus injected is equal
to 20 times the setting current Ios. Use
the procedure as for the phase
overcurrent test.
Disconnect the VAP6. In order to save
batteries, do not leave the VAP6
connected to the relay unnecessarily.
11
VIP300 O&M CAT (4/02)
6/4/02
1:03 am
Page 10
VIP 300
Commissioning Ringmaster with VIP 300
Factory tests:
Reduced commissioning:
Secondary injection:
All Ringmaster panel types are fully
tested before leaving the factory. These
tests include the whole protection
system including current transformers,
wiring harness, relay, trip coil and the
circuit breaker itself using primary
injection to energise the system.
Tripping tests are carried out using
different settings for each of the IDMT
and DT curves available on the relay.
The tripping times are measured with a
chronometer and its accuracy is verified
against the theoretical times calculated.
Since the system is fully tested it is only
necessary to prove the relay on site at
the service settings, therefore reducing
commissioning time to a minimum.
Once the switchgear has been installed
and cabled up, it is impractical or
sometimes impossible to carry out
injection tests. It is suggested that for
commissioning and maintenance
purposes either of the following two
methods can be used.
1.
Simple trip test using the VAP6
test unit (described previously).
2.
Secondary injection using
standard equipment with an
output filter.
Testing using secondary injection is
used to test the following parts of the
protection system:
■
The electronic circuit.
■
The integrity of the power supply
of the VIP 300.
■
The link to the mitop trip coil and
also the circuit breaker
mechanical tripping mechanism.
■
The integrity of the switches on
the front panel to ensure they
give the correct tripping times for
the curves selected.
Test set connections:
Caution:
The injection set is connected to the VIP 300 relay without disconnecting the CT’s.
This is done via the sockets on the terminal rail located in the pilot cable box, just
above the relay itself.
■
Phase overcurrent connections:
■
To test the overcurrent protection the connection should be made across two CT’s
(terminal rails no’s 4 to 5, 5 to 6 or 6 to 4).
Earth fault connections:
To test the earth fault protection, the connection should be made across one CT
(terminal rail no’s 4 to 7, 5 to 7, or 6 to 7).
These terminal numbers should be cross checked with the relevant circuit breaker
schematic diagram. Terminals 15 and 16 (not shown above - see Ringmaster
selection guide) give access to a normally open contact, which is normally open
when the CB is in the open position. This can be used to connect a timing device to
measure the opening time of the relay and circuit breaker.
The type of test plug used to connect to the DIN rail connectors is a standard 2mm
19A test plug.
■
■
Note: When using a secondary injection set with VIP 300 a filter (e.g. Foster SF30)
should be used to improve the wave form. If a filter is not used the operating time of
the relay may not follow the theoretical operating times.
52
7
x4 range
40A,80A or 160A
5 minimum
operating
3 current
1
P2
S1
P1
R
S1
P1
Y
S2
S2
P2
S1
B
S2
P2
4
C11
8
C31
5
C31
6
C51
6
C51
x2 range
20A,40A or 80A
minimum
operating
4 current
C10
7
C70
2
C30
8
C50
9
C90
10
S2
C71
P1
CT1
C11
VIP 300 IDMT RELAY
50/51
9
50N/51N
10
C70
11
12
13
14
N.B. - Always check against the relevant
CB schematic diagram before carrying
out tests
MITOP - ITC
K8
K7
(-VE)
(+VE)
0v
15
16
connect to terminal blocks above for secondary injection
MITOP - CB trip coil
Injection test set
with filter
12
CB auxiliary contact
(for timing purposes)
The “MITOP” trip coil must be
used only in conjunction with the
VIP relay.
Voltage withstand testing of the
a u x i l i a r y and control circuits at
2000 for 1 minute should never be
carried out without disconnecting
the MITOP trip coil or VIP relay.
Secondary injection facilities are
provided on the terminal rail in the
pilot cable box.
No external connections should
be made to the VIP 300 or the
MITOP trip coil.
VIP300 O&M CAT (4/02)
6/4/02
1:03 am
Page 11
VIP 300
Commissioning Ringmaster with VIP 300
Recommended test
procedure for
secondary injection:
The test procedure outlined here is only
a guide and may need modifying to suit
the different test sets available.
1.
Pick-up check
- Increase the current slowly until
the appropriate LED indicator
starts to blink.
2.
Setting check:
- Set the current to be injected
(a true RMS ammeter should be
used to measure the current).
- The CB should then be closed
and the counter/timer reset. The
current should then be applied.
- When the CB has operated, the
applied current should be turned
off if not done automatically.
- The time shown on the counter
display includes the operating
time of the circuit breaker
>80ms or <100ms. The actual
relay operating time can then be
calculated by subtracting this
time from the counter reading.
The manufacturers instructions should
be read before attempting to secondary
inject the VIP 300 relay.
The VIP 300 relay can be secondary
injected like any conventional 1A relay,
therefore the output recommended for
1A relays should be used.
Calculate the secondary current to be
injected from the equivalent primary
current, taking into account the CT’s
used and the range selected by
connections to the terminals on the
back of the relay.
With the VIP 300 connected so as to
present the correct burden, the following
tests can be carried out:
Note. - No connection should be made to the MITOP trip coil from the secondary
injection test set.
RN2c, RE2c, CE2, CN2
CT ratio 200/1A
RN6c
CT ratio 400/1A
CE6, RN6c
CT ratio 800/1A
Range x 2
Range x 4
Range x 2
Range x 4
Range x 2
Range x 4
Minimum Operating
Current=20A
Minimum Operating
Current=40A
Minimum Operating
Current=40A
Minimum Operating
Current=80A
Minimum Operating
Current=80A
Minimum Operating
Current=160A
Secondary
injected current
Equivalent
primary current
Secondary
injected current
Equivalent
primary current
Secondary
injected current
Equivalent
primary current
Secondary
injected current
Equivalent
primary current
Secondary
injected current
Equivalent
primary current
Secondary
injected current
Equivalent
primary current
100mA
20A
200mA
40A
100mA
40A
200mA
80A
100mA
80A
200mA
160A
120mA
24A
240mA
48A
120mA
48A
240mA
96A
120mA
96A
240mA
192A
150mA
30A
300mA
60A
150mA
60A
300mA
120A
150mA
120A
300mA
240A
180mA
36A
360mA
72A
180mA
72A
360mA
144A
180mA
144A
360mA
288A
210mA
42A
420mA
84A
210mA
84A
420mA
168A
210mA
168A
420mA
336A
240mA
48A
480mA
96A
240mA
96A
480mA
192A
240mA
192A
480mA
384A
280mA
56A
560mA
112A
280mA
112A
560mA
224A
280mA
224A
560mA
448A
320mA
64A
640mA
128A
320mA
128A
640mA
256A
320mA
256A
640mA
512A
360mA
72A
720mA
144A
360mA
144A
720mA
288A
360mA
288A
720mA
576A
400mA
80A
800mA
160A
400mA
160A
800mA
320A
400mA
320A
800mA
640A
*
450mA
90A
900mA
180A
450mA
180A
900mA
360A
450mA
360A
900mA
720A
*
500mA
100A
1A
200A
500mA
200A
1A
400A
500mA
400A
1A
800A
*
*Note. These values exceed the rating of the circuit breaker.
13
VIP300 O&M CAT (4/02)
6/4/02
1:03 am
Page 12
VIP 300
Commissioning Ringmaster with VIP 300
Commissioning test record:
Secondary injection of Merlin Gerin
VIP 300 self powered overcurrent and
earth fault relay.
✔ tick as appropriate
Customer
Site
Contact ref.
Panel
Relay type
Relay serial no.
Current transformers
Setting range, minimum operating current
200/1A
x2, 20A
x4, 40A
400/1A
x2, 40A
x4, 80A
800/1A
x2, 80A
x4, 160A
Note. Ensure connections on the rear of the relay are made to the appropriate
terminals for the x2 or x4 setting ranges and that the scale labels are inserted
correctly to match the range selected.
Indicate on the diagram below actual settings. Carry out tests and record the results
in the table provided.
200/1A
Mark settings with an arrow e.g.
68
800/1A
sensor
200/1: 4509996A0
sensor
200/1: 4509996A0
sensor
400/1: 451101200
sensor
400/1: 451101200
sensor
800/1: 4509169A0
sensor
800/1: 4509169A0
VIP 300LH range: x2
VIP 300LHrange: x4
VIP 300LH range: x2
VIP 300LHrange: x4
VIP 300LH range: x2
VIP 300LHrange: x4
Is
Is
Is
Is
Is
48
42
56
36
64
30
72
24
80
20 100 90
(A)
96
84
112
72
128
60
144
48
160
40 200 180
(A)
96
84
112
72
128
60
144
48
160
40 200 180
(A)
192
168
224
144
256
120
288
96
320
80 400 360
(A)
192
168
224
144
256
120
288
96
320
80 400 360
minimum operating
phase current: 20A
minimum operating
phase current: 40A
minimum operating
phase current: 40A
minimum operating
phase current: 80A
minimum operating
phase current: 80A
minimum operating
phase current: 160A
Ios
Ios
Ios
Ios
Ios
Ios
24
16
32
12
40
8
50
4
60
2 80 70
48
32
64
24
80
16
100
8
120
4 160 140
48
32
64
24
80
16
100
8
120
4 160 140
(A)
(A)
Setting scale label selection to be
located at point “A” for appropriate CT
type 200/1A, 400/1A & 800/1A
400/1A
phase
overcurrent
I>
I>
EI
1.8
2.4
DT
(s)
curve selection
2.7
1
(x Is) 3
trip
warning
0.15 0.2
0.3
0.1
0.07
x10
0.4
0.05
not time
multiplier
x1
see table
t>
12
15
6
4
20
3
(x Is) off
0.2
0.4
0.6
0.1
0.05
0.9
0.03
0.6
1.5
(s)
t>>
reset
Io>
EI
1.8
RI
trip
DT
2.1
9
2.4
1.5
off
1.2
2.7
1
VIP 300 Equivalent Time
Settings Multiplier
t> to>
0.05
0.07
0.1
0.15
0.2
0.3
0.4
0.05
0.6
0.07
0.1
0.15
0.2
0.3
0.4
0.6
x1
x1
x1
x1
x1
x1
x1
x10
x1
x10
x10
x10
x10
x10
x10
x10
SI
VI
EI
0.02
0.02
0.03
0.05
0.07
0.10
0.13
0.17
0.20
0.24
0.34
0.50
0.67
1.01
1.35
2.02
0.03
0.05
0.07
0.10
0.13
0.20
0.27
0.33
0.40
0.47
0.67
1.00
1.33
2.0
2.67
4.00
0.06
0.09
0.12
0.19
0.25
0.37
0.50
0.62
0.74
0.87
1.24
1.86
2.48
3.71
4.95
7.43
Io>>
DT only
VI
SI
(A)
VIP 300
9
1.2
192 256
128
96
320
64
400
32
480
16 640 560
(A)
2.1
1.5
off
RI
96
64
128
48
160
32
200
16
240
8 320 280
I>>
DT only
VI
SI
(A)
(A)
96
64
128
48
160
32
200
16
240
8 320 280
(A)
(A)
Is
384
336
448
288
512
240
576
192
640
160 800 720
(s)
12
15
6
4
3
3
warning
0.1
20
(x Ios) off
curve selection
0.15 0.2
Io>
0.1
0.07
0.05 (s)
earth fault
14
to>
0.3
0.4
0.6
x10
x1
not time
multiplier
0.2
see table
0.6
0.05
0.03
to>>
0.4
0.9
(s)
1.5
VAP6 test plug
VIP300 O&M COVER (4/02)
6/4/02
1:02 am
Page 4
VIP 300
Commissioning Ringmaster with VIP 300
Commissioning test
record
1.
Pick up check.
Inject the test current into the
relay for each phase in turn and
note the current required to flash
the LED.
2.
Operating time and curve
check at final settings.
Inject the test current into the
relay for each phase in turn and
note the operating times.
3.
Instantaneous trip check
Inject the appropriate test current
into the relay and ensure the
correct instantaneous response.
Curve...............
T..............
Phase A-B
Phase B-C
Curve........... T..............
Phase C-A
EF
1. Pick-up current at setting
2. Operating time and curve at final
selected setting
3. Current level to trip high set
Commissioning test record
4.
Check test facility using
VAP6
Commissioning engineer
Date
Customer witness
Date
15
6/4/02
1:02 am
Page 1
Merlin Gerin - Medium Voltage, 123 Jack Lane, Leeds LS10 1BS
Tel: 0113 290 3500 Fax: 0113 290 3710 Internet address: http://www.schneider.co.uk
Publication No.PB0402 WH1000W O/S-BP
VIP300 O&M COVER (4/02)
Download