VIP300 O&M COVER (4/02) 6/4/02 1:02 am Page 2 Merlin Gerin VIP 300 protection relay Operation, testing and commissioning version 003 / April 2002 VIP300 O&M CAT (4/02) 6/4/02 1:03 am Page 1 VIP 300 Contents Content page Use and settings Relay front panel 4 Curve selection 5 Phase overcurrent setting area 6 Earth fault setting area 7 Other functions (labels, LED’s, VAP6) 8-9 Testing and Commissioning Overview of VAP6 test unit 10 VAP6 test sequence 11 Commissioning Ringmaster with VIP 300 12-15 3 VIP300 O&M CAT (4/02) 6/4/02 1:03 am Page 2 VIP 300 Relay front panel 1 2 3 4 C B phase overcurrent 5 7 8 6 10 A I> sensors: 200/1 4509996A0 VIP300LH range: x2 I>> DT only EI VI RI 1.2 DT 1 0.15 0.2 0.3 0.1 0.07 0.4 0.05 warning 0.1 not time multiplier x1 20 3 (x Is) off 0.2 0.4 0.6 0.05 0.9 0.03 0.6 (s) t> Is x10 15 4 3 (x Is) 12 6 2.7 curve selection 42 48 56 36 64 30 72 24 80 20 100 90 (A) 9 2.4 1.5 off VIP300 2.1 1.8 SI I> trip 9 1.5 (s) t>> see table reset minimum operating phase current: 20A Io> EI 1.8 SI RI DT trip 2.1 1.2 1 9 2.4 1.5 off t> to> 0.05 0.07 0.1 0.15 0.2 0.3 0.4 0.05 0.6 0.07 0.1 0.15 0.2 0.3 0.4 0.6 x1 x1 x1 x1 x1 x1 x1 x10 x1 x10 x10 x10 x10 x10 x10 x10 SI VI EI 0.02 0.02 0.03 0.05 0.07 0.10 0.13 0.17 0.20 0.24 0.34 0.50 0.67 1.01 1.35 2.02 0.03 0.05 0.07 0.10 0.13 0.20 0.27 0.33 0.40 0.47 0.67 1.00 1.33 2.0 2.67 4.00 0.06 0.09 0.12 0.19 0.25 0.37 0.50 0.62 0.74 0.87 1.24 1.86 2.48 3.71 4.95 7.43 Io>> DT only VI VIP 300 Equivalent Time Settings Multiplier 15 4 2.7 3 3 warning 0.1 (x Ios) 12 6 20 off (x Ios) curve selection 16 24 32 12 40 8 50 4 60 2 80 70 (A) Io> 0.15 0.2 0.07 x10 0.4 0.05 (s) x1 0.6 not time multiplier 0.2 0.4 0.6 0.05 0.9 0.03 to> Ios earth fault 0.3 0.1 to>> see table 1.5 (s) VAP6 test plug D 11 12 13 14 15 E 17 18 16 19 20 Phase overcurrent setting Earth fault setting Other functions 1. 11. A. B. 2. 3. 4. 5. 6. 7. 8. 9. 10. 4 Phase setting area (upper half of relay front panel). Red LED phase overcurrent pick-up indicator. Phase overcurrent trip indicator. Phase overcurrent setting Is. Choice of low set curve type I>. Low set pick-up (DT only) I>. Low set time delay t> Multiplying factor (low set). High set pick-up I>> High set time delay t>> 12. 13. 14. 15. 16. 17. 18. 19. 20. Earth fault setting area (lower half of relay front panel). Red LED earth fault pick-up indicator. Earth fault trip indicator. Earth fault setting current Ios. Choice of low set curve type Io>. Low set pick-up (DT only) Io>. Low set time delay to>. Multiplying factor (low set). High set pick-up Io>>. High set time delay to>>. C. D. E. Current setting scale label. Current transformer and range information. Indicator reset button. Minimum operating current. VAP6 test plug socket. VIP300 O&M CAT (4/02) 6/4/02 1:03 am Page 3 VIP 300 Curve selection Phase overcurrent setting IDMT curve selection t The numbers indicated below are those of the setting switches (refer to the diagram of the front panel on page 4) The letters indicate the curve characteristic as shown opposite. G SI, VI, EI RI t> J K t>> L Phase overcurrent setting: F ■ Setting current Is (4) G ■ Type of low set I> curve (5) IDMT: SI, VI, EI, RI. Definite time: DT H ■ DT low set pick-up I> (6) This setting is only active for the low set DT curve selection (as shown). If IDMT curves are selected this switch is disabled, as SI,VI, EI, low set pick-up is fixed at 1.2 Is. J ■ Low set time delay t> (7) and multiplier (8) K ■ High set I>>(9) L ■ High set time delay t>>(10) Earth fault setting Is F 1.2 Is 10 Is I>> The principle is the same as for phase protection. Set: F ■ Setting current Ios (14) G ■ Type of low setting Io> curve (15) IDMT: SI, VI, EI, RI Definite time: DT H ■ DT low set pick-up Io> (16) This setting is only active for the low set DT curve selection (as shown). If IDMT curves are selected this switch is disabled, as SI, VI, EI low set pick-up is fixed at 1.2 Is. J ■ Low set time delay to> (17) and multiplier (18) K ■ High set Io>>(19) L ■ High set time delay to>>(20) DT curve selection t H t> DT G J K t>> Is 1.2 Is L Operation The high and low set elements operate separately. The tripping order results from the “ logical OR” between the two settings. I> I>> F 5 VIP300 O&M CAT (4/02) 6/4/02 1:03 am Page 4 VIP 300 Use and setting 1. Phase overcurrent phase overcurrent sensors: 200/1 4509996A0 VIP300LH range: x2 I> I> EI 1.8 1.5 off DT 1.2 42 48 56 36 64 30 72 24 80 20 100 90 (A) Is reset 0.05 t> 0.3 0.4 (s) 9 2.4 (x Is) 3 warning 0.15 0.2 0.1 0.07 x10 x1 VIP300 2.1 2.7 1 curve selection trip I>> DT only VI SI RI not time multiplier 15 3 (x Is) off 4 20 0.2 see table t>> 0.4 0.6 0.1 0.05 0.03 0.6 12 6 0.9 (s) 1.5 VIP 300 Equivalent Time Settings Multiplier t> to> 0.05 0.07 0.1 0.15 0.2 0.3 0.4 0.05 0.6 0.07 0.1 0.15 0.2 0.3 0.4 0.6 x1 x1 x1 x1 x1 x1 x1 x10 x1 x10 x10 x10 x10 x10 x10 x10 SI VI EI 0.02 0.02 0.03 0.05 0.07 0.10 0.13 0.17 0.20 0.24 0.34 0.50 0.67 1.01 1.35 2.02 0.03 0.05 0.07 0.10 0.13 0.20 0.27 0.33 0.40 0.47 0.67 1.00 1.33 2.0 2.67 4.00 0.06 0.09 0.12 0.19 0.25 0.37 0.50 0.62 0.74 0.87 1.24 1.86 2.48 3.71 4.95 7.43 Phase overcurrent setting area All information concerning the phase overcurrent is grouped together in the upper half of the front panel. The section numbers below are related to the numbering on the drawing shown on page 4. 2. Phase overcurrent pick-up indicator When the red LED blinks, it indicates that the low set element has picked up. If the current does not decrease below the pick-up level the relay will trip. ■ For IDMT curves (SI, VI, EI) the LED blinks when the current is greater than 1.2 times the setting current Is. ■ For the IDMT curve (RI), the LED blinks when the current is greater than the setting. ■ For the DT curve, the LED blinks when the I> pick-up setting is exceeded. Also refer to “indicator reset button” (page 9). 3. SI VI EI RI 6. : : : : Low set pick-up (DT only) I> The setting is a multiple of Is. It is only active when the low set curve type DT is selected. If the tripping curve is selected with IDMT (selector switch 5 set to SI, VI, EI, RI) the selector switch has no effect. 7. Low set time delay t> ■ If the DT curve is selected, the value shown is the low set time delay. For IDMT curves the value displayed is the tripping time for a phase current equal to 10 x Is. ■ The indicator is normally black and turns yellow when the phase overcurrent has given a tripping order. It stays yellow, even when the relay is de-energised. 8. 4. 9. Setting current Is Choice of low set curve Standard inverse time. Very inverse time. Extremely inverse time. Specific curve - consult Merlin Gerin DT : Definite time. Off : Low set is disabled. Phase overcurrent trip indicator The setting depends on the current transformer (CT) used, and the range selected via the connections made to the back of the relay. The scale label inserted should match the CT and range selected. The switch can then be positioned to the primary current magnitude required in amperes. 6 5. Multiplying factor (low set) In the x10 position, the time delay displayed on switch 7 is multiplied by10. High set pick-up I>> The high set is chosen as a multiple of the current Is. In the “off” position, the high set is disabled. 10. High set time delay t>> Time delay is set directly in seconds. VIP300 O&M CAT (4/02) 6/4/02 1:03 am Page 5 VIP 300 Use and setting The setting principle is the same as for phase overcurrent. Earth fault reset minimum operating phase current: 20A Io> EI 1.8 2.1 1.2 1 9 2.4 1.5 off DT 11. Earth fault setting area Io>> DT only VI SI RI trip 2.7 (x Ios) 3 12 15 6 4 20 3 (x Ios) off curve selection Io> earth fault 16 24 32 12 40 8 50 4 60 2 80 70 (A) Ios 0.15 0.2 0.1 0.07 0.05 (s) to> warning 0.3 0.4 0.6 x10 x1 not time multiplier 0.2 0.03 see table to>> 0.4 0.6 0.1 0.05 0.9 (s) 1.5 VAP6 test plug All information concerning earth fault settings are grouped together in the lower half of the front panel. Section numbers below are related to the numbering on the drawing shown on page 4. 12. Earth fault pick-up indicator When the red LED blinks, It indicates that the low set element has picked up. If the current does not decrease below the pick-up level the relay will trip. ■ For IDMT curves (SI, VI, EI) the LED blinks when the current is greater than 1.2 times the setting current Is. ■ For the IDMT curve (RI), the LED blinks when the current is greater than the setting. ■ For the DT curve, the LED blinks when the l> pick-up setting is exceeded. N.B. The LED only blinks when the phase current is greater than the minimum operating current (refer to minimum operating current, page 9) Also refer to “indicator reset button” (page 9). 13. Earth fault trip indicator The indicator is normally black and turns yellow when the earth fault element has given a tripping order. It stays yellow, even when the relay is de-energised. 14. Setting current Ios The setting depends on the current transformer (CT) used, and the range selected via the connections made to the back of the relay. The scale label inserted should match the CT and range selected. The switch can then be positioned to the primary amp value required. For earth fault relay operation: link between contacts 2 and 9 (x2 range) and 1 and 9 (x4 range) must be made at back of relay. 15. Choice of low set curve SI : VI : EI : RI : DT : Off : Standard inverse time. Very inverse time. Extremely inverse time. Specific curve. Definite time. Low set is disabled. 16. Low set pick-up (DT only) Io> The setting is a multiple of Ios. It is only active when the low set curve type DT is selected. If the tripping curve is selected with IDMT (selector switch 15 set to SI, VI, EI, RI) the selector switch has no effect. 17. Low set time delay to> ■ ■ If the DT curve is selected, the value shown is the low set time delay. For IDMT curves the value displayed is the tripping time for a phase current equal to 10 x Ios. 18. Multiplying factor (low set) In the x10 position, the time delay displayed on switch 17 is multiplied by 10. 19. High set pick-up Io>> The high set is chosen as a multiple of the current Ios. In the “off” position, the high set is disabled. 20. High set time delay to>> Time delay is set directly in seconds 7 VIP300 O&M CAT (4/02) 6/4/02 1:03 am Page 6 VIP 300 Use and setting A. Other functions Reversible scale label for Ringmaster fitted with 200/1A CT’s sensor 200/1: 4509996A0 sensor 200/1: 4509996A0 VIP 300LH range: x2 VIP 300LHrange: x4 Is Is 48 42 56 36 64 30 72 24 80 20 100 90 (A) 96 84 112 72 128 60 144 48 160 40 200 180 (A) minimum operating phase current: 20A minimum operating phase current: 40A Ios Ios 24 16 32 12 40 8 50 4 60 2 80 70 (A) x 2 range 48 32 64 24 80 16 100 8 120 4 160 140 (A) x 4 range Reversible scale label for Ringmaster fitted with 400/1A CT’s sensor 400/1: 451101200 sensor 400/1: 451101200 VIP 300LH range: x2 VIP 300LHrange: x4 ■ The label indicates the range for the phase overcurrent and earth fault primary amp settings. It is inserted from the top, behind the transparent part of the front panel. ■ The label is reversible and is printed with the x2 range setting currents on one side, and the x4 range setting currents on the other. The scale label when inserted should match the CT and terminal positions on the rear of the relay, for the range required. Also refer to “testing and commissioning”. B. CT and range indication The CT and range are given on each side of the setting scale label. The label will match the appropriate CT for the Ringmaster panel type supplied. This information is hidden when the label is inserted. Is Is 96 84 112 72 128 60 144 48 160 40 200 180 (A) 192 168 224 144 256 120 288 96 320 80 400 360 (A) Choice of setting scale label minimum operating phase current: 40A minimum operating phase current: 80A ■ Ios Ios 48 32 64 24 80 16 100 8 120 4 160 140 (A) x 2 range 96 64 128 48 160 32 200 16 240 8 320 280 (A) x 4 range Reversible scale label for Ringmaster fitted with 800/1A CT’s sensor 800/1: 4509169A0 sensor 800/1: 4509169A0 VIP 300LH range: x2 VIP 300LHrange: x4 Is Is 192 336 448 288 512 240 576 192 640 160 800 720 (A) (A) minimum operating phase current: 80A minimum operating phase current: 160A Ios Ios (A) x 2 range Make sure that the information given on the top of the label matches: 1 - The current transformer used: 200/1A, 400/1A or 800/1A 2 - The range used. x2 or x4 This information is hidden when the label is in position. ■ For help with the choice of range to select, refer to the application section. Installation 384 168 224 144 256 120 288 96 320 80 400 360 96 64 128 48 160 32 200 16 240 8 320 280 8 Setting scale label 192 256 128 96 320 64 400 32 480 16 640 560 (A) x 4 range ■ ■ Slide the setting scale into position behind the transparent part of the front face. Make sure the label is pushed right into the bottom of the slot. To remove the label, use the hole in the top, if necessary with the help of the tip of a pencil or a screwdriver. VIP300 O&M CAT (4/02) 6/4/02 1:03 am Page 7 VIP 300 Use and setting C. Indicator reset button The reset button can be operated with the sealable cover either open or closed. When the button is pressed, the following actions are initiated: ■ It resets the phase overcurrent and earth fault trip indicators. N.B. If reset is more than 48 hours after the relay has operated and is left without being energised, the VAP6 must be used to reset the trip indicators or the operator must wait for the relay to be re-energised. ■ The two red LED’s light up simultaneously for approximately three seconds to indicate the following: - The relay is energized and the minimum operating current level has been reached. -The relay self testing results are healthy N.B. If one of the two conditions is not met, the indicators do not light up. D. Minimum operating current The minimum operating current is the phase current required for the relay to be energized and operational. The setting depends on the CT used, and the range selected via the connections made to the back of the relay. The value given on either side of the scale label is the single phase RMS minimum operating current. N.B. Regarding minimum operating current: The VIP 300 does not operate below the minimum operating current level. As a result, if the earth fault setting (Ios) is below the minimum operating current, it will only take effect when there is phase current greater than or equal to the minimum operating current. E. VAP6 test plug The test plug is exclusively designed for connection of the VAP6 which is used for fast, simplified relay testing. The operation may be carried out while the relay is operating since the VAP6 and VIP 300 provide the possibility of testing with inhibition of circuit breaker tripping. Also refer to the “testing and commissioning” chapter. This function may be used to carry out a basic relay operation test. Fitting of reversible scale label 9 VIP300 O&M CAT (4/02) 6/4/02 1:03 am Page 8 VIP 300 Overview of the VAP6 VAP6 front panel D D external mitop + I> A on B test in progress C trip 4 battery test 1 phase overcurrent 2 earth fault 3 trip inhibition earth fault test phase overcurrent test phase overcurrent VIP 30 VIP 35 VIP300 VIP50 VIP75 VIP 11, 11R VIP 12R VIP13 VIP17 VIP200, 201 trip trip inhibition external mitop The VAP6 is a portable unit which is connected to the VIP 300 to carry out simplified testing. The test can be carried out in the following two cases: - the VIP 300 is already powered up by the sensors (CT’s). - The VIP 300 is not supplied. In this case, the VAP6 batteries supply power to the relay. Indicators Push buttons: C ■ Trip: Is used to test other relays in the VIP range. It is not to be considered for the VIP 300 test (it lights up for a transient period when the VIP 300 sends a tripping order; whether or not the circuit breaker is inhibited). 1■ Battery test: If the batteries are healthy, the “on” indicator(A) lights up when the button is pressed. 2■ Phase overcurrent: Sends the phase overcurrent test stimulus, which is equivalent to 20 times the setting current Is. circuit breaker mitop circuit breaker mitop VAP6 3■ Earth fault: Sends the earth fault test stimulus, which is equivalent to 20 times the earth setting current Ios. 4■ Trip inhibition: By pressing and holding this button down the relay can be tested with the VAP6 without tripping the circuit breaker. This facility will inhibit the circuit breaker tripping even if a real fault occurs during the test. A ■ On: Indicates that the batteries are operating. Also lights up when the battery test is carried out by pressing “battery test”. B ■ Test in progress: Confirms sending of the test stimulus to the VIP 300. D ■ “External MITOP” output: This feature may be used to connect an external MITOP trip coil which could be used to operate a timer etc. The external coil is triggered at the same time as the circuit breaker MITOP. The trip inhibit button does not effect the external coil. Batteries: ■ The batteries are normally deactivated and are automatically activated when the VAP6 is connected to the VIP 300. They are activated in the following cases: - Pressing the “battery test” button. - Direct connection to a VIP 300 relay. ■ To install or change the batteries, open the unit by removing the 4 screws on the bottom of the unit. Be sure to use the correct polarities. Technical characteristics: Supply: Weight: Dimensions: 10 3 x 9V 6LR61 batteries 0.45KG 93 X 157 X 45mm VIP300 O&M CAT (4/02) 6/4/02 1:03 am Page 9 VIP 300 VAP6 test sequence The test may be carried out with or without the relay energised by the Ringmaster current transformers, and all the relay settings are effective. During the test, the relay remains operational and will give a tripping order in the event of a fault, unless the “trip inhibit” button is pressed and held down. The test consists of: - Initiation of the VIP 300 self monitoring and diagnostic routine. - Injecting a stimulus to stimulate a phase fault. - Check tripping The VAP6 is supplied by batteries. Therefore the parts of the VIP 300 that run on AC current are not checked using this method (input and supply circuits). Press the “phase overcurrent” button to send the test stimulus. - Continue pressing the button throughout the duration of the stimulus. The stimulus represents about 20 times the setting current Is. -The VAP6 “test in progress” indicator lights up to confirm the sending of the stimulus to the VIP300 relay. - The red “I>” indicator of the VIP300 blinks during the time relay delay period. - Then the VIP 300 phase “trip” indicator turns yellow. - The circuit breaker trips if it is not inhibited. Connect the VAP6 to the “VAP6 test plug”. The VAP6 batteries are activated and the “on” indicator lights up. Press the “trip inhibition” button if the test should be carried out without tripping the circuit breaker. Be sure to continue pressing the “trip inhibition” button throughout the time it takes to send the stimulus. N.B. If the “phase overcurrent” button is held down after tripping, the VIP300 starts the time delay/tripping cycle again; this is normal operation. In that case: - The VAP6 red “trip” indicator lights up for a transient period each time there is a trip. - Depending on the time delay setting, the VIP 300 red “I>” indicator may be off or blink rapidly and/or in an irregular manner. Press “earth fault” to test the relays operation. The stimulus injected is equal to 20 times the setting current Ios. Use the procedure as for the phase overcurrent test. Disconnect the VAP6. In order to save batteries, do not leave the VAP6 connected to the relay unnecessarily. 11 VIP300 O&M CAT (4/02) 6/4/02 1:03 am Page 10 VIP 300 Commissioning Ringmaster with VIP 300 Factory tests: Reduced commissioning: Secondary injection: All Ringmaster panel types are fully tested before leaving the factory. These tests include the whole protection system including current transformers, wiring harness, relay, trip coil and the circuit breaker itself using primary injection to energise the system. Tripping tests are carried out using different settings for each of the IDMT and DT curves available on the relay. The tripping times are measured with a chronometer and its accuracy is verified against the theoretical times calculated. Since the system is fully tested it is only necessary to prove the relay on site at the service settings, therefore reducing commissioning time to a minimum. Once the switchgear has been installed and cabled up, it is impractical or sometimes impossible to carry out injection tests. It is suggested that for commissioning and maintenance purposes either of the following two methods can be used. 1. Simple trip test using the VAP6 test unit (described previously). 2. Secondary injection using standard equipment with an output filter. Testing using secondary injection is used to test the following parts of the protection system: ■ The electronic circuit. ■ The integrity of the power supply of the VIP 300. ■ The link to the mitop trip coil and also the circuit breaker mechanical tripping mechanism. ■ The integrity of the switches on the front panel to ensure they give the correct tripping times for the curves selected. Test set connections: Caution: The injection set is connected to the VIP 300 relay without disconnecting the CT’s. This is done via the sockets on the terminal rail located in the pilot cable box, just above the relay itself. ■ Phase overcurrent connections: ■ To test the overcurrent protection the connection should be made across two CT’s (terminal rails no’s 4 to 5, 5 to 6 or 6 to 4). Earth fault connections: To test the earth fault protection, the connection should be made across one CT (terminal rail no’s 4 to 7, 5 to 7, or 6 to 7). These terminal numbers should be cross checked with the relevant circuit breaker schematic diagram. Terminals 15 and 16 (not shown above - see Ringmaster selection guide) give access to a normally open contact, which is normally open when the CB is in the open position. This can be used to connect a timing device to measure the opening time of the relay and circuit breaker. The type of test plug used to connect to the DIN rail connectors is a standard 2mm 19A test plug. ■ ■ Note: When using a secondary injection set with VIP 300 a filter (e.g. Foster SF30) should be used to improve the wave form. If a filter is not used the operating time of the relay may not follow the theoretical operating times. 52 7 x4 range 40A,80A or 160A 5 minimum operating 3 current 1 P2 S1 P1 R S1 P1 Y S2 S2 P2 S1 B S2 P2 4 C11 8 C31 5 C31 6 C51 6 C51 x2 range 20A,40A or 80A minimum operating 4 current C10 7 C70 2 C30 8 C50 9 C90 10 S2 C71 P1 CT1 C11 VIP 300 IDMT RELAY 50/51 9 50N/51N 10 C70 11 12 13 14 N.B. - Always check against the relevant CB schematic diagram before carrying out tests MITOP - ITC K8 K7 (-VE) (+VE) 0v 15 16 connect to terminal blocks above for secondary injection MITOP - CB trip coil Injection test set with filter 12 CB auxiliary contact (for timing purposes) The “MITOP” trip coil must be used only in conjunction with the VIP relay. Voltage withstand testing of the a u x i l i a r y and control circuits at 2000 for 1 minute should never be carried out without disconnecting the MITOP trip coil or VIP relay. Secondary injection facilities are provided on the terminal rail in the pilot cable box. No external connections should be made to the VIP 300 or the MITOP trip coil. VIP300 O&M CAT (4/02) 6/4/02 1:03 am Page 11 VIP 300 Commissioning Ringmaster with VIP 300 Recommended test procedure for secondary injection: The test procedure outlined here is only a guide and may need modifying to suit the different test sets available. 1. Pick-up check - Increase the current slowly until the appropriate LED indicator starts to blink. 2. Setting check: - Set the current to be injected (a true RMS ammeter should be used to measure the current). - The CB should then be closed and the counter/timer reset. The current should then be applied. - When the CB has operated, the applied current should be turned off if not done automatically. - The time shown on the counter display includes the operating time of the circuit breaker >80ms or <100ms. The actual relay operating time can then be calculated by subtracting this time from the counter reading. The manufacturers instructions should be read before attempting to secondary inject the VIP 300 relay. The VIP 300 relay can be secondary injected like any conventional 1A relay, therefore the output recommended for 1A relays should be used. Calculate the secondary current to be injected from the equivalent primary current, taking into account the CT’s used and the range selected by connections to the terminals on the back of the relay. With the VIP 300 connected so as to present the correct burden, the following tests can be carried out: Note. - No connection should be made to the MITOP trip coil from the secondary injection test set. RN2c, RE2c, CE2, CN2 CT ratio 200/1A RN6c CT ratio 400/1A CE6, RN6c CT ratio 800/1A Range x 2 Range x 4 Range x 2 Range x 4 Range x 2 Range x 4 Minimum Operating Current=20A Minimum Operating Current=40A Minimum Operating Current=40A Minimum Operating Current=80A Minimum Operating Current=80A Minimum Operating Current=160A Secondary injected current Equivalent primary current Secondary injected current Equivalent primary current Secondary injected current Equivalent primary current Secondary injected current Equivalent primary current Secondary injected current Equivalent primary current Secondary injected current Equivalent primary current 100mA 20A 200mA 40A 100mA 40A 200mA 80A 100mA 80A 200mA 160A 120mA 24A 240mA 48A 120mA 48A 240mA 96A 120mA 96A 240mA 192A 150mA 30A 300mA 60A 150mA 60A 300mA 120A 150mA 120A 300mA 240A 180mA 36A 360mA 72A 180mA 72A 360mA 144A 180mA 144A 360mA 288A 210mA 42A 420mA 84A 210mA 84A 420mA 168A 210mA 168A 420mA 336A 240mA 48A 480mA 96A 240mA 96A 480mA 192A 240mA 192A 480mA 384A 280mA 56A 560mA 112A 280mA 112A 560mA 224A 280mA 224A 560mA 448A 320mA 64A 640mA 128A 320mA 128A 640mA 256A 320mA 256A 640mA 512A 360mA 72A 720mA 144A 360mA 144A 720mA 288A 360mA 288A 720mA 576A 400mA 80A 800mA 160A 400mA 160A 800mA 320A 400mA 320A 800mA 640A * 450mA 90A 900mA 180A 450mA 180A 900mA 360A 450mA 360A 900mA 720A * 500mA 100A 1A 200A 500mA 200A 1A 400A 500mA 400A 1A 800A * *Note. These values exceed the rating of the circuit breaker. 13 VIP300 O&M CAT (4/02) 6/4/02 1:03 am Page 12 VIP 300 Commissioning Ringmaster with VIP 300 Commissioning test record: Secondary injection of Merlin Gerin VIP 300 self powered overcurrent and earth fault relay. ✔ tick as appropriate Customer Site Contact ref. Panel Relay type Relay serial no. Current transformers Setting range, minimum operating current 200/1A x2, 20A x4, 40A 400/1A x2, 40A x4, 80A 800/1A x2, 80A x4, 160A Note. Ensure connections on the rear of the relay are made to the appropriate terminals for the x2 or x4 setting ranges and that the scale labels are inserted correctly to match the range selected. Indicate on the diagram below actual settings. Carry out tests and record the results in the table provided. 200/1A Mark settings with an arrow e.g. 68 800/1A sensor 200/1: 4509996A0 sensor 200/1: 4509996A0 sensor 400/1: 451101200 sensor 400/1: 451101200 sensor 800/1: 4509169A0 sensor 800/1: 4509169A0 VIP 300LH range: x2 VIP 300LHrange: x4 VIP 300LH range: x2 VIP 300LHrange: x4 VIP 300LH range: x2 VIP 300LHrange: x4 Is Is Is Is Is 48 42 56 36 64 30 72 24 80 20 100 90 (A) 96 84 112 72 128 60 144 48 160 40 200 180 (A) 96 84 112 72 128 60 144 48 160 40 200 180 (A) 192 168 224 144 256 120 288 96 320 80 400 360 (A) 192 168 224 144 256 120 288 96 320 80 400 360 minimum operating phase current: 20A minimum operating phase current: 40A minimum operating phase current: 40A minimum operating phase current: 80A minimum operating phase current: 80A minimum operating phase current: 160A Ios Ios Ios Ios Ios Ios 24 16 32 12 40 8 50 4 60 2 80 70 48 32 64 24 80 16 100 8 120 4 160 140 48 32 64 24 80 16 100 8 120 4 160 140 (A) (A) Setting scale label selection to be located at point “A” for appropriate CT type 200/1A, 400/1A & 800/1A 400/1A phase overcurrent I> I> EI 1.8 2.4 DT (s) curve selection 2.7 1 (x Is) 3 trip warning 0.15 0.2 0.3 0.1 0.07 x10 0.4 0.05 not time multiplier x1 see table t> 12 15 6 4 20 3 (x Is) off 0.2 0.4 0.6 0.1 0.05 0.9 0.03 0.6 1.5 (s) t>> reset Io> EI 1.8 RI trip DT 2.1 9 2.4 1.5 off 1.2 2.7 1 VIP 300 Equivalent Time Settings Multiplier t> to> 0.05 0.07 0.1 0.15 0.2 0.3 0.4 0.05 0.6 0.07 0.1 0.15 0.2 0.3 0.4 0.6 x1 x1 x1 x1 x1 x1 x1 x10 x1 x10 x10 x10 x10 x10 x10 x10 SI VI EI 0.02 0.02 0.03 0.05 0.07 0.10 0.13 0.17 0.20 0.24 0.34 0.50 0.67 1.01 1.35 2.02 0.03 0.05 0.07 0.10 0.13 0.20 0.27 0.33 0.40 0.47 0.67 1.00 1.33 2.0 2.67 4.00 0.06 0.09 0.12 0.19 0.25 0.37 0.50 0.62 0.74 0.87 1.24 1.86 2.48 3.71 4.95 7.43 Io>> DT only VI SI (A) VIP 300 9 1.2 192 256 128 96 320 64 400 32 480 16 640 560 (A) 2.1 1.5 off RI 96 64 128 48 160 32 200 16 240 8 320 280 I>> DT only VI SI (A) (A) 96 64 128 48 160 32 200 16 240 8 320 280 (A) (A) Is 384 336 448 288 512 240 576 192 640 160 800 720 (s) 12 15 6 4 3 3 warning 0.1 20 (x Ios) off curve selection 0.15 0.2 Io> 0.1 0.07 0.05 (s) earth fault 14 to> 0.3 0.4 0.6 x10 x1 not time multiplier 0.2 see table 0.6 0.05 0.03 to>> 0.4 0.9 (s) 1.5 VAP6 test plug VIP300 O&M COVER (4/02) 6/4/02 1:02 am Page 4 VIP 300 Commissioning Ringmaster with VIP 300 Commissioning test record 1. Pick up check. Inject the test current into the relay for each phase in turn and note the current required to flash the LED. 2. Operating time and curve check at final settings. Inject the test current into the relay for each phase in turn and note the operating times. 3. Instantaneous trip check Inject the appropriate test current into the relay and ensure the correct instantaneous response. Curve............... T.............. Phase A-B Phase B-C Curve........... T.............. Phase C-A EF 1. Pick-up current at setting 2. Operating time and curve at final selected setting 3. Current level to trip high set Commissioning test record 4. Check test facility using VAP6 Commissioning engineer Date Customer witness Date 15 6/4/02 1:02 am Page 1 Merlin Gerin - Medium Voltage, 123 Jack Lane, Leeds LS10 1BS Tel: 0113 290 3500 Fax: 0113 290 3710 Internet address: http://www.schneider.co.uk Publication No.PB0402 WH1000W O/S-BP VIP300 O&M COVER (4/02)