VATIC Associates VAT-E-05 Circuit Breakers and Switches Circuit Breakers and Switches VAT-E-05 Contents Overview................................................................................................................ 3 1. Circuit Breaker Design Characteristics ........................................................3 Common Breaker Terms ..........................................................................................................3 Ratings .....................................................................................................................................4 Classes......................................................................................................................................4 Live Tank vs. Dead Tank Circuit Breakers..............................................................................6 2. Circuit Breaker Components......................................................................... 7 Interrupting Chamber ...............................................................................................................7 Contacts..................................................................................................................................10 Operating Mechanism ............................................................................................................14 Bushing and Connection Terminals .......................................................................................15 Control Cabinet ......................................................................................................................20 Indications ..............................................................................................................................21 Racking Mechanisms .............................................................................................................27 Safety Locks ...........................................................................................................................28 3. Types of Circuit Breakers............................................................................ 28 Oil - 2.4 kV to 220 kV ...........................................................................................................28 Air Magnetic - 16 kV And Below ..........................................................................................32 SF6 Gas – 66 kV to 500 kV ....................................................................................................35 Vacuum – 16 kV And Below .................................................................................................41 Self-Contained .......................................................................................................................43 4. Types of Operating Mechanisms ................................................................. 46 Manual ...................................................................................................................................46 Solenoid .................................................................................................................................48 Pneumatic...............................................................................................................................49 Motor Spring ..........................................................................................................................52 Hydraulic ................................................................................................................................54 Gas .........................................................................................................................................60 5. Circuit Switches............................................................................................ 61 1 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches Common Suppliers.................................................................................................................61 Construction ...........................................................................................................................61 Operation................................................................................................................................61 Alarms and Indications ..........................................................................................................62 Application .............................................................................................................................62 Configurations........................................................................................................................62 Interlocks................................................................................................................................62 Malfunctions ..........................................................................................................................62 2 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches Overview This section of the operator’s manual will provide the reader with the information that is needed to answer what, how, and when of circuit breaker/switches operation, application and system interrelationship. The discussion within this section will revolve around introducing the operator to the two categories of switching equipment (circuit breakers and switches) commonly used within a typical transmission system. In addition, this section addresses the methods developed for the operating mechanisms to perform their function. 1. Circuit Breaker Design Characteristics The circuit breaker is one of the most important pieces of electric utility equipment and has the most severe duty cycle imposed on it. Circuit breakers are the only current interrupting devices that combine full fault current interrupting capability with the ability to be manually or automatically opened or closed. During abnormal conditions, the function of the circuit breaker is to disconnect and electrically isolate equipment and lines in the electrical system that are in trouble or have failed. During normal conditions, the circuit breaker carries and switches load currents from zero to rated current on a continuous basis. Circuit breakers are designed to interrupt either normal or fault currents. They behave as large switches that may be opened or closed by local control switches or remotely. Furthermore, circuit breakers will automatically open a circuit whenever line current exceeds a preset limit. Circuit breakers can be set more accurately than fuses and, unlike fuses, they do not require replacement after each fault. Common Breaker Terms Breaker Speed The speed at which a circuit breaker operates is very important. The speed of the circuit breaker is measured in feet per second between the two points, which has been determined as necessary by the manufacturer to extinguish the arc in the arcing zone. Arc Zone The area that is used to measure breaker speed. It is usually a few inches after where the contacts part on opening and before the contacts make closing. Closing Time The time that the closing coil is energized until the main contacts touch. 3 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches Expressed in cycles. Opening Time The time that the trip coil is energized (0 line) to the point where the main contacts part. Expressed in cycles. Ratings Rated Voltage Rated voltage is the maximum operating voltage for which the circuit breaker is designed. Voltage ratings are given in terms of three-phase line-to-line voltage. Impulse Withstand Impulse withstand voltage designates the strength of the circuit breaker to resist sudden, short-duration voltage stresses, such as those imposed Voltage by lightning strikes. This rating is also called the basic insulation level, or BIL, and is generally 3 to 4 times the rated voltage. Short Time Current The short time current rating is the maximum amount of current in amperes which the circuit breaker contacts and internal conductors can carry, without damage, for a short time period (typically, three seconds). This rating also accounts for permanent stress to insulation, heat, and electromagnetic effects. Continuous Current Rating Continuous current is the maximum value of steady state amperes that the circuit breaker contacts and internal conductors are designed to carry. Rated Interrupting Current Rated interrupting current is the maximum current at the time the contacts part that the circuit breaker is designed to interrupt. Duty MVA Duty MVA is the maximum power at the time the contacts part that the circuit breaker is designed to interrupt. Duty Cycle The duty cycle is the minimum amount of time necessary after a closing and tripping operation before the circuit breaker can be closed and tripped again. The duty cycle is listed on the circuit breaker nameplate. A typical duty cycle listed on the nameplate may be CO-15 sec.-CO, which means close and open, wait 15 seconds, and then close and open again. Classes Air-Magnetic An air magnetic circuit breaker operates on the principle that an arc can be interrupted in air by sufficiently elongating and cooling it. This is accomplished by means of a strong magnetic field that lengthens the arc and forces it into a cool dielectric material. Extinguishing of the arc 4 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches takes place in a device called an arc chute, which is mounted on the circuit breaker above the contact. Air-Blast An air blast circuit breaker uses high-pressure dry air for arc interruption. The air blast circuit breaker is a two-pressure system breaker, which is of a live tank design. When an air blast circuit breaker opens, a jet of high-pressure air is blown through the arcing zone, constricting the arc by pressure and cooling it by diffusion and absorption of heat. Oil Circuit Breakers (OCB) An oil circuit breaker (OCB) is one of the most common breakers in a typical transmission system. This breaker uses oil of high dielectric strength as an insulating and interrupting medium. When the oil circuit breaker opens the oil around the contacts is vaporized into a gas by the arc. To control the expansion of the gas formed by the arc a device called an interrupter is used. The containment of the gas expansion tends to cool the arc, which increases the dielectric strength of the gas. When the circuit breaker opens and the contacts separate, the moveable contact passes toward the open end of the interrupter, passing by a series of openings or ports built into the interrupter. The pressure inside the interrupter blows the elongated arc through the ports into the cooler oil outside thus extinguishing the arc. Vacuum Circuit Breakers Vacuum circuit breakers can interrupt high voltage power with the contacts moving only 1/4 to 1/2 of an inch. The reason that vacuum breaker contacts have this capability is that a vacuum is an excellent insulator. Electrical current cannot flow across a gap between two conductors unless there is present, between the conductors, some source of ions or electrons. Obviously, if the gap is in a perfect vacuum, there is nothing in the gap. This includes ions or electrons. If two contacts which are butting and carrying current in a vacuum can be parted in the vacuum and the vacuum maintained as they part, the arc will be quickly extinguished. Because of the design of vacuum breakers, small mechanisms with low power requirements can do the job previously requiring large mechanisms with huge springs and large operating power requirements. SF6 Another method of arc interruption uses sulfur hexaflouride gas. Gas circuit breakers, frequently used in the system, come in many styles and designs. There is a two-pressure, and a single-pressure design. Though the design may vary, they all have several common elements. These elements are: • They all utilize SF6 (sulfur hexaflouride) gas as an insulating and interrupting medium. 5 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches • • SF6 gas is: •Highly stable •Odorless •Inert •Colorless •Non-toxic •Tasteless •Non-poisonous •Electro-negative •Nonflammable •Heavier than-air They all operate as a closed gas system where no gas is vented to atmosphere. At 30 to 45 psig of pressure, it is superior to the dielectric strength of transformer oil. Because of its superior properties, this style of circuit breaker is smaller in size and faster in interrupting than most oil circuit breakers. Single-Pressure For a single-pressure SF6 breaker, also known as a puffer breaker, the gas fills the void within the breaker’s tank. Depending on the design of the breaker, the SF6 that is in the area of the arc or an internal mechanical bellows will place the SF6 gas in contact with the arc. The SF6 combines with the arc to produce a relatively immobile ion. The loss of conducting electrons causes the arc to be easily extinguished at current zero. Dual-Pressure When the gas blast circuit breaker opens, a blast of SF6 gas is blown into the arc. Because SF6 gas is electronegative, it combines with the arc and produces a relatively immobile ion. The loss of conducting electrons causes the arc to be easily extinguished at current zero. The important difference between the single and dual pressure breakers is the single-pressure breaker does not have a compressor and storage tank to store the SF6 gas. The single-pressure breaker generally relies on the extinguishing properties of the SF6 gas to quench the arc. Live Tank vs. Dead Tank Circuit Breakers A live tank is a circuit breaker tank that is energized at the same potential as the line. A dead tank is a circuit breaker tank that is at the same potential as ground. Due to the inherent greater safety of a dead-tank circuit breaker, most of the circuit breakers are of the dead tank design. The system has very few live tank circuit breakers left in the system. Only a few air blast 6 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches circuit breakers employ the Live tank design. Even these should be replaced by the end of the year 2000. 2. Circuit Breaker Components This part of the section describes and identifies through text, pictures, and line drawings the major subassemblies that make up a circuit breaker. Interrupting Chamber Dielectric Medium The dielectric medium is one of the most significant physical properties that affect the interrupting properties of the circuit breaker. The gas or liquid that fills the interrupting chamber and occupies the space between the breaker contacts is called the circuit breaker dielectric or dielectric medium. The dielectric medium of circuit breakers must have excellent insulating capabilities and only electrically breakdown during very high voltages. Circuit breakers use dielectric mediums of oil, air, gas, or vacuum. Dielectric mediums are used in circuit breakers for arc extinction and electrical insulation. Dielectric mediums provide electrical insulation between the contacts when the contacts are open. Dielectrics also provide electrical insulation between the contacts and other non-current carrying metal components of the circuit breaker such as the tank of the interrupting chamber. A medium’s dielectric strength is a measure of how well the medium, or material can withstand voltage without conducting electricity. For example, insulating oil has a higher dielectric strength than air. Therefore, oil can withstand a higher voltage without conducting electricity than air. In addition, a medium is sometimes pressurized. In general, pressurizing a dielectric increases its dielectric strength. Air Air is used in air circuit breakers for arc extinction and electrical insulation in the interrupting chamber. An air gap of 0.3 inches can withstand 25 kV at normal pressure and ambient temperature (40°C). The air used to extinguish the arc is usually compressed to very high pressures (2000 - 4000 pounds per square inch) to attain the dryness required for arc quenching. Since water is a good conductor of electricity, the less moisture that the air contains the better the dielectric strength of the air. Oil In an oil circuit breaker, oil provides electrical insulation in the interrupting chamber, while hydrogen gas is used for arc extinction. Oil decomposes under the influence of extreme arc heat into carbon and 7 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches hydrogen creating a high-pressure arc bubble. The arc bubble consists of a mixture of metal vapors and ionized gases having hydrogen content of approximately 70 percent. The hydrogen has the effect of de-ionizing and extinguishing arcs at a rapid rate by cooling them. SF6 SF6 gas is used in gas circuit breakers for arc extinction and electrical insulation in the interrupting chamber. SF6 gas has remarkable arc quenching abilities that are attributed to its ability to recover its dielectric strength quickly after arc passes through a current zero. Vacuum In a vacuum circuit breaker, the dielectric medium in the interrupting chamber is a vacuum. Ideally, a vacuum would provide perfect insulation because there would not be anything to fuel an arc. In practice, however, gases are absorbed onto the contacts within the vacuum, and there is an emission of charged particles from the contact surfaces during arc interruption. Arc Interruption Mechanisms In a circuit breaker, a number of factors work together to extinguish an arc and interrupt a circuit. These factors include: • Speed • Distance • Cooling • Dielectric strength • Current zero Speed The speed at which a circuit breaker's contacts separate is important because the faster the contacts open, the less time there is for the space between the contacts to heat up and become a conductor. Slower separation allows more time for an arc to form and maintain itself. Distance When the distance between the contacts increases, the arc must stretch in order to maintain current flow. In addition, as the distance increases, more voltage is required to sustain current flow. Cooling Generally, when air and gases are heated, they become electrical conductors: as they get hotter, they conduct better. Consequently, cooling plays an important role in helping to extinguish arcs. The term "cooling” refers to any physical effects that take heat away from an arc. Some common cooling methods include directing a blast of air or gas at an arc as shown in Figure E-05-A-1. Forcing the arc against cold metal or insulating materials, as illustrated in Figure E-05-A-1. Submerging 8 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches the circuit breaker contacts and the arc in insulating oil as pictured in Figure E-05-A-2. Figure E-05-A-1 Air/Gas Blast Elongating Arc Insulating Material Figure E-05-A-1 Arc Forced Against Cold Metal Or Insulating Material Oil Figure E-05-A-2 Contacts and Arc Submerged In Insulating Oil Dielectric Strength Circuit breakers also use mediums of different dielectric strengths to 9 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches help extinguish arcs. A medium's dielectric strength is a measure of how well the medium, or material, can withstand voltage without conducting electricity. Because of differences in dielectric strength, some materials conduct electricity less readily than others do. Current Zero Another factor that helps to extinguish arcs is current zero. Alternating current constantly changes polarity from positive to negative or negative to positive in recurring cycles, as indicated in Figure E-05-A-3. Current zero occurs at the exact time that the polarity changes. At that time, there is no current flow. Circuit breakers are designed to take advantage of these momentary absences of current flow to extinguish arcs. Figure E-05-A-3 Current Zero Contacts The primary purpose of the interrupting chamber of a circuit breaker is to house the insulating gases or liquids of a sufficient dielectric strength to extinguish the arc formed when the circuit breaker contacts open. To aid in arc interruption, interrupting chambers use the principles of arc elongation, arc constriction, and de-ionization of the conductive arc path. Arc elongation simply means making the arc path longer, thereby increasing cooling and de-ionization by diffusion. Arc constriction reduces the cross sectional area of the arc; thereby increasing the voltage required to maintain it. De-ionizing the conductive gas created by the arc path reduces the free electrons available in the gas, which, in effect, changes the conductivity. Multiple interrupting chambers in series per phase increases the interrupting capacity of the circuit breaker. By placing multiple interrupting chambers in series, the voltage across each interrupting 10 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches chamber is reduced proportionally; therefore the dielectric strength of the interrupting medium exceeds the ability of the arc to recover at the applied voltage. Recovery voltage is the rapid rise of voltage across the opening contacts after the arc first extinguishes and the current flow goes to zero. A circuit breaker may use multiple interrupters. However, if the voltage distribution is not evenly divided between each set of contacts, the dielectric strength of the insulation between contacts may not prevent re-ignition of the arc. The placement of capacitors in parallel with the interrupting chamber ensures equal voltage distribution across the contacts. These capacitors are referred to as switching or grading capacitors. Resistors that shunt the arc gap increase the interrupting capacity and decrease the rate of rise of the arc's recovery voltage. When a shunt resistor is used, a part of the arc’s current is diverted through the resistor. The resistor will drop voltage across it, which leaves less voltage to re-strike the arc. All circuit breakers have at least one set of contacts per phase, which are responsible for closing or opening the high voltage circuit through its pole. The force required to open or close these contacts is supplied by the circuit breakers operating mechanism. The contacts for carrying load current are typically made of copper or copper coated with silver since copper has a low resistance and is well suited for carrying current continuously without excessive heating. On the down side, copper has a low melting point (1,083°C) and has a tendency to weld when subjected to considerable amounts of arcing. A pair of contacts made of tungsten is sometimes provided to carry current only during the closing or interrupting process. Tungsten is used because it has a high melting point (3,380°C) and little tendency to vaporize or burn during arcing as copper does. The copper contacts that carry current continuously are referred to as the "main" contacts and the tungsten contacts between which the arc is drawn are referred to as the "arcing" contacts. There are five principal types of circuit breaker contacts: • Butt • Wedge • Brush 11 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates Butt VAT-E-05 Circuit Breakers and Switches • Bayonet • Finger Butt contacts, as shown in Figure E-05-A -4, consist of two conductors with flat or curved faces that butt together when the circuit breaker is closed. The mating surfaces are usually silver-plated to reduce heating and pitting. A spring held tight by a latch or other restraining device holds the moving butt contact solidly against the stationary butt contact. When the circuit breaker trips the latch is released and the spring pulls the contacts apart rapidly. These types of contacts are primarily used on low voltage (13.8 kV) and low current applications. Figure E-05-A -4 Butt Contact Wedge Wedge contacts, also known as finger and blade contacts, are commonly used for circuit breakers. The wedge, the moving contact, is forced into a set of flared contact fingers, the stationary contacts, as illustrated in Figure E-05-A-5. These contacts are usually arranged in pairs and provided with reinforcing springs to increase contact pressure. Steel supporting springs align the fingers on the wedge. 12 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches Figure E-05-A-5 Wedge Contacts Brush Brush contacts, as shown in Figure E-05-A-6, are used on lower voltages. The stationary contact consists of solid copper stud. The moving contact consists of laminations and has a main contact and one or more secondary contacts. Figure E-05-A-6 Brush Contact Bayonet Bayonet contacts consist of a rod for the moving contact that is forced into a stationary sheath contact. The stationary sheath contact usually consists of one or more spring sleeves, which provide the contact pressure during operation. Bayonet contacts are made of copper and used for the main current carrying contacts. An arcing contact of a tungsten alloy is usually provided to prevent main contact surface damage during circuit interruption. Figure E-05-A-7 is an illustration of 13 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches bayonet contacts. Figure E-05-A-7 Bayonet Contacts Finger Finger contacts shown in Figure E-05-A-8, is used on almost all voltages, SF6 puffer type and oil circuit breakers. When the finger contact is closed, eight to ten stationary contact fingers make the current connection to the main moving contact. As the main moving contact separates from the stationary contact fingers, the arcing contacts still make the current connection. An arc is formed as the arcing contacts begin to separate. The movement of the contact forces SF6 gas over the arcing contacts to extinguish to the arc. Figure E-05-A-8 Finger Contacts Operating Mechanism The operating mechanism provides the mechanical force that opens and closes the circuit breaker contacts. There are six types operating 14 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches mechanisms, distinguished by how they close the circuit breaker main contacts. The six types are manual, solenoid, pneumatic, motor spring, hydraulic, and gas. For each, the method of opening the main contacts is the same: the contacts fall open under the influence of gravity and accelerating springs following the operation of a trip coil. All of these circuit breaker mechanisms have a mechanical flag, called the semaphore, which shows whether the circuit breaker contacts are open or closed. The different operating mechanisms are covered in more detail later in section 3.1.4. Bushing and Connection Terminals Bushings are used as the entrance leads or connection terminals into circuit breakers. In addition to providing the point of connection, the bushing provides insulation to the conductor and seals the circuit breaker from the harmful effects of the environment. Bushings may also contain bushing current transformers (BCTs) for measuring current flow through the circuit breaker as shown in Figure E-05-A-9. Figure E05-A-10 illustrates where the bushing current transformers are normally located on a circuit breaker. POLARITY MARK POLARITY MARK TRANSFORMER LEADS X1 X2 X3 X4 X5 BUSHING TYPE Figure E-05-A-9 Bushing Current Transformer 15 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches Normal BCT Location Figure E-05-A-10 Normal BCT Location On The Bushing Five major types of bushings are used on circuit breakers. These five types are: Solid Porcelain • Solid porcelain bushings • Oil filled bushings • Condenser bushings • SF6 bushings • Composite and Silicone Solid porcelain bushings, shown in Figure E-05-A-11, are solid porcelain cylinders that surround the conductors. Solid porcelain bushings are used for lower-voltage circuit breakers (up to about 20 kV) of relatively small interrupting capacity. 16 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches Figure E-05-A-11 Solid Porcelain Bushing Oil-Filled Oil-filled bushings are used on circuit breakers operating at voltages up to 230 kV. In the example shown in Figure E-05-A-12, the conductor is mounted inside cylindrical porcelain insulators filled with oil. Thin insulating cylinders of special materials, like plastics, may divide the oil space with an oil gauge or sight glass at the top to indicate the oil level in the bushing. 17 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches Figure E-05-A-12 Oil Filled Bushing Condenser Condenser bushings, as shown in Figure E-05-A-13, are used on higher voltage circuit breakers (usually over 75 W). Conductors may be insulated with concentric layers of oil-impregnated paper, with metal foil inserted at several locations among the layers. This insulation arrangement is similar to placing a voltage across several series connected capacitors. If the capacitors or layers have equal capacitance, the voltage is equally divided between them. The capacitances of each layer are made equal by using metal foil of equal area. As the radius of the layers increases further from the conductor, the length of metal foil must decrease to obtain the same area. The division of voltage among capacitance layers of insulation allows a reduction in the overall amount of insulation required. 18 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches Figure E-05-A-13 Condenser Bushing SF6 Bushings In SF6 circuit breakers, the hollow porcelain bushing is opened to the main breaker tank and filled with SF6 gas to serve as insulation as shown in Figure E-05-A-14. SF6 bushings are not generally interchangeable with other types of bushings. Figure E-05-A-14 SF6 Bushing 19 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates Composite and Silicone VAT-E-05 Circuit Breakers and Switches Composite and silicone bushings are a recent development in the electrical industry. Their construction is similar to the solid porcelain bushings. However, instead of using fired porcelain, a silicone and resin composite is used. The bushing is not ridged like a solid porcelain bushing, but is more like a firm rubber. The concept is that these new bushings will provide a better service life since they will not be as susceptible to environmental and physical damage like the porcelain material. Control Cabinet The circuit breaker control cabinet, shown in Figure E-05-A-15, is mounted on the circuit breaker and contains the important control devices for the circuit breaker. The control cabinet also serves as the termination point for control and indication cables wired to the control house. The circuit breaker control and indication circuits provide the necessary capability to operate the circuit breaker safely. The control circuitry enables the operator of the circuit breaker to trip or close the breaker manually or automatically. The indication circuitry notifies personnel of the status of the breaker, i.e., opened or closed, and alarm conditions. Newer circuit breakers have alarm indication boards inside the control cabinet. 20 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches Figure E-05-A-15 Three Phase Circuit Breaker Every circuit breaker has a control circuit associated with it. The control circuit combines the switches, relays, control contacts, alarm circuits, and indicating lights that enable the circuit breaker to be controlled. Control circuits are primarily powered by DC power. Compared to AC control circuits, DC control circuits are more reliable. DC control circuits can operate from station batteries during an outage while AC control circuits may not. The control circuit can be divided into three parts according to the function each part performs. These three parts or functions are: • Opening or tripping • Closing • Indication Indications Sight gages Sight gauges provide the Substation Operator with a visual indication of the oil level in an oil bushing or the humidity of the air in an air circuit breaker. Oil circuit breaker’s bushings The Substation Operator may come across two different types of sight gauges at the substation. They are: Sight Level -provides a visual reference level of the oil in the bushings. A sight level is shown in Figure E-05-A-16. 21 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches Sight Level Figure E-05-A-16 Sight Level Gauge – provides a mechanical level indication of the oil in the bushings. Figure E-05-A-17 is a typical example of an oil level gauge in the TYPICAL system. Oil Level Gauge Figure E-05-A-17 Oil Level Gauge 22 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates Oil circuit breaker’s - tanks VAT-E-05 Circuit Breakers and Switches As with the sight gauges of the oil bushings, the oil circuit breaker level indications provide the Substation Operator with a visual indication of the oil level in tank of the oil circuit breaker. There are three common level indicators used to provide a indication of the oil level in the circuit breaker tank, they are: Sight Level – (or Sight glass) provides a visual reference as to the oil level in the circuit breakers tank. A sight level is shown in Figure E-05A-18. Figure E-05-A-18 Oil Tank Sight Glass Gauge – provides a mechanical level indication of the oil in the tank, using some type of mechanical level detection such as displacement of or pressure/weight on the detecting device. Float – similar to the gauge but provides the level indication from a simple float connected to the meter through magnets. Air circuit breaker’s – Litmus Paper Provides a visual indication, a bull’s eye at the control cabinet, of the humidity of the air inside the air circuit breaker. The paper will turn red if the humidity within the circuit breaker is too great. Due to the construction of the circuit breaker in service in the TYPICAL system, for example a live tank circuit breaker, all air circuit breakers are scheduled for replacement by the end of the year 2000. Pressure Gauges SF6 breakers, whether single or dual pressure, require the monitoring of 23 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches the SF6 gas in the tank and the bushing so that the dielectric medium meets design specifications to allow the breaker to operate as designed. This is even more critical for the dual pressure systems since its proper operation and its ability to extinguish the arc is dependent on the pressurized SF6 gas in the high-pressure cylinder. Figure E-05-A-19 is a typical example of pressure gauges used in the system for a dual pressure SF6 breaker. Highpressure Gauge Lowpressure Gauge Figure E-05-A-19 Pressure Gauges Hydraulic Gauges Hydraulic gauges are used to monitor the pressure of the hydraulic fluid in hydraulic operating mechanisms. The pressure is monitored to ensure the breaker operates as designed. Figure E-05-A-20 is a typical example of a hydraulic pressure gauge used in the system. 24 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches Hydraulic Pressure Gauge Figure E-05-A-20 Hydraulic Gauge Temperature Gauge Only dual pressure SF6 breakers monitor gas temperature. The temperature is monitored to ensure that the breaker operates as designed. Figure E-05-A-21 is a typical example of the temperature gauges used in the system for its dual pressure SF6 breakers. 25 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches Temperature Gauges Figure E-05-A-21 SF6 Temperature Gauges Counters Counters are used to measure the number of opening operations that the breaker has performed. It is used by maintenance to determine what work or repairs may need to be performed on the breaker or as a troubleshooting aid. A typical counter is shown in Figure E-05-A- 22. 26 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches Counter Charging Spring Indicator Semaphore Figure E-05-A- 22 Counter and Semaphore Semaphore The circuit breaker’s semaphore provides the operator or the maintenance individual with a visual indication of the breaker’s operating state, i.e. open or closed. Most circuit breakers’ semaphore indications are a mechanical type, which provides positive indication of the position of the breaker. ABB uses a micro switch to detect the position of the breaker so its semaphore indication does NOT provide positive indication of the breaker’s position. Figure E-05-A- 22 is a photo of a typical semaphore flag indicator that is commonly used in the system. The semaphore indicates that the breaker is closed / shut. Racking Mechanisms When some of the smaller circuit breakers need to be worked on by maintenance, the breaker is removed from its normal operating position to a position that allows for the breaker to be worked on safely and accessibility. This position is called the racked out position. When maintenance needs to be performed on a breaker, such that it will need to be racked out, the racking mechanism will have to be installed on to the breaker. The racking mechanism provides maintenance personnel with the necessary tools, supports and leverage to withdraw the breaker from its normal operating position to its maintenance position and then return it to its operating position after completion of the maintenance. 27 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches Safety Locks Safety locks provide some rudimentary level of protection for the breaker. They may be electrical or mechanical interlocks to prevent damage to the breaker from an improper action. 3. Types of Circuit Breakers A particular type of circuit breaker is called by the type of interrupting medium used. This section will provide a more detailed examination of the various circuit breaker types used in a power delivery system. There are five major types of circuit breakers to be discussed. They are: • Oil • Air Magnetic • SF6 gas • Vacuum • Self-contained Oil - 2.4 kV to 220 kV Oil circuit breakers are one of the most commonly used circuit breakers on the system. Common Suppliers The following is a list of commonly found oil circuit breakers used in the typical system. They are: • ABB • GE • ITE • Westinghouse • Kelman • Mcgraw Edison Basic Construction Oil circuit breakers use three types of arc interrupters to extinguish an arc: And Operation Arc Extinction In • De-ion grid arc interrupters • Explosion oil blast interrupters • Impulse oil blast interrupters The "de-ion grid" consists of a stack of insulated U-shaped iron plates 28 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates De-Ion Grid Interrupters VAT-E-05 Circuit Breakers and Switches and sheets of insulating material shaped to form pockets as illustrated in Figure E-05-A-23. The moving contact passes through a slot at the opening of the U. Vents are located between this slot and the exterior of the interrupter. Figure E-05-A-23 De-ion Grid Arc Interrupter When the moving contact moves downward, an arc is formed in the slot between the two contacts. Magnetic lines of force are set up around the arc. The magnetic lines of force follow the iron path and force the arc to do likewise. The arc is forced through and confined to the grid area between the iron plates. Oil in the grid area is vaporized by the heat of the arc, which forms a gaseous mixture more than 70% hydrogen gas. The specific heat of hydrogen is relatively high; meaning hydrogen requires relatively large quantities of heat to raise its temperature. This property has the effect of cooling and de-ionizing arcs at a rapid rate. Therefore, the hydrogen in the path of an arc recovers its dielectric strength rapidly. In escaping through the vents, the hydrogen-endowed gas passes through the center of the arc. As the hydrogen gas is relatively cooler than the ionized gas in the center of the arc stream, it tends to de-ionize the ionized gas. 29 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches The shape of the interrupter towards the bottom of the U is such that a longer arc path is formed. Thus, the de-ion grid interrupter works on a combination of all three arc interruption methods previously referred to: Arc Extinction In Explosion Oil Blast Interrupters • Forcing the arc into a confined space, thus decreasing its area • Causing the arc to travel through a longer path • De-ionizing the gas The principle of operation of explosion oil blast interrupters differs from the de-ion grid type in that oil is forced across or into the arc, rather than the arc forced into the oil. In explosion oil interrupters, two sets of butt contacts in series form the circuit. Each is in a confining chamber as shown in Figure E-05-A-24. The main moving contact consists of a hollow rod as shown in the figure. Figure E-05-A-24 Explosion Oil Blast Arc Interrupter When the circuit breaker opens, two arcs are formed, one between each set of contacts. The two arcs break down the oil between the contacts, creating high-pressure gas bubbles. As with the de-ionized grid interrupters, these gas bubbles consist mainly of hydrogen. The upper arc and gas bubbles cause a great pressure on the oil in the upper chamber. This forces the oil through openings in the plate between the two chambers. These openings are located so that the stream of oil is directed against the arc in the lower chamber. The only path of escape for the expanding gas bubble in the lower 30 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches chamber is through the hollow rod that forms the lower contact. The oil forces the gas that forms in the lower arc down the hollow rod into the breaker tank. Although there is an initial lengthening of the arc when the contacts move apart, this type of interrupter works mainly on the principle of decreasing the cross sectional area of the arc path. When the gas is forced out of the lower chamber, this area is zero. Interrupters of this type differ widely in appearance and design. However, the principle is same in that pressure generated by one arc forces oil through or across the path of another arc. Arc Extinction In Impulse Oil Blast Interrupters The impulse oil blast type interrupters differ from the explosion type in that the oil pressure is caused by mechanical means rather than by an arc. Please refer to Figure E-05-A-25. The lower contact, in closing, forces a piston to the top of a separate oil chamber against a spiral spring. When the breaker opens, the spring forces the piston downward, causing a blast of oil to flow across the arc path. Extremely fast arc interruptions can be obtained by the proper use of this principle. Figure E-05-A-25 Impulse Oil Blast Interrupter Alarms And Indications The commonly found alarms and indications for this type of breaker are: • Oil level – by sight glass, or gauge • Low air pressure alarm Applications This breaker type is generally used in the 2.4 kV to 220 kV range. Typical Malfunctions Any of the following indications are tattle-tail that a problem is occurring within the breaker. Be observant of any of the following 31 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches conditions and inform the necessary personnel: • Signs that oil has been expelled from the breaker, from the rupture disk or a seal • Inspect the breaker for any damage that might be apparent to the circuit breaker’s bushings • Verify oil level on an oil-filled bushing • Listen for any unusual noises coming from the circuit breaker • Inspect the breaker for any abnormalities, such as unusual smells or broken parts. • Continuous motor operation indicates that there has been a failure of the circuit breaker mechanism or control circuit. • Check pressure gauges. Air Magnetic - 16 kV And Below Introduction The dielectric strength of air is not very high. Air circuit breakers, however, have features that make up for the relatively low dielectric strength of air. There are two major types of air circuit breakers: • Air magnetic • Air blast Basic Construction Air magnetic circuit breakers are used in low voltage distribution applications. They are mounted in a metal protective cabinet. The And Operation design and physical features of an air magnetic circuit breaker can vary depending on the manufacturer, but they all share common features that are used to break the circuit and extinguish the arc. Arc Extinction In Air Magnetic Circuit Breakers Air magnetic circuit breakers have two sets of contacts, a set of main contacts and a set of arcing contacts as shown in Figure E-05-A-26. When the breaker is closed the main current path is through the main contacts. When the circuit breaker trips and the main contacts open, arcing does not occur between the main contacts since the circuit is still completed through the arcing contacts. After the main contacts separate, the arcing contacts separate creating an arc between the arcing contacts. 32 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches Figure E-05-A-26 Air Magnetic Circuit Breaker Interrupter The arcing contacts are designed to withstand the intense heat of the arc but only for a very short period. To quickly extinguish the arc between the arcing contacts a number of features in the circuit breaker work together. These features include: • A puffer • Arc runners • Magnetic blow out coils • Pole pieces • Arc fins The puffer includes: • Cylinder • Piston • Hollow tube and nozzle As the circuit breaker contacts separate, the puffer piston is moved through the cylinder. Please refer to Figure E-05-A-27. Air in the cylinder is compressed and forced through the hollow tube and nozzle. The nozzle directs the air at the arc, helping to cool the arc. At the same time, the air from the nozzle forces the arc away from the arcing contacts and towards arc runners. 33 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches Figure E-05-A-27 Air Magnetic Circuit Breaker Interrupter With Contacts Open Arc runners are conductors that help carry the arc away from the arcing contacts. As the arcing contacts continue to separate, the distance between the arcing contacts becomes greater than the distance between the arc runners. The arc will try to maintain itself over the shortest possible distance. Since the distance between the arc runners is shorter than the distance between the opening arcing contacts, the arc, assisted by the puff of air, will jump from between the arcing contacts to between the arc runners. The arc runners are connected to magnetic blow out coils. A blow out coil is a conductor that is wound around an iron core. When the arc current flows through the arc runners it also flows through the blow out coils and creates a magnetic field. The cores of the blow out coil are connected with pole pieces that are metal plates. The plates concentrate the magnetic fields between the arc runners. They also help dissipate heat to cool the arc. The magnetic field created by the blow out coils forces the arc into arc fins. Arc fins are insulated plates that provide greater arc interruption ability than air alone. Arc fins do not readily conduct electricity. Consequently, they obstruct the path of the arc. As the arc is forced into the fins, it has to travel a longer distance in order to sustain current flow. They also absorb and dissipate heat, helping to cool the arc. 34 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches Eventually, the arc is stretched and cooled until finally, at current zero, the arc is completely extinguished and the circuit is open. Alarms And Indications There are no alarms associated with this type of breaker. The only indication available to the operator is the semaphore. Relays should be checked for circuit breaker fault interruption. Applications This breaker type is generally used for 16 kV and below. Typical Malfunctions Any of the following indications are an indication that a problem is occurring within the breaker. Be observant of any of the following conditions and inform the necessary personnel: • Signs of damage to the breaker. • Be alert for any unusual odors. • Listen for any unusual noises coming from the circuit breaker. • Inspect the breaker for any abnormalities. • Verify that after maintenance, the breaker is properly aligned and in its normal operating position after the breaker is racked in. SF6 Gas – 66 kV to 500 kV Introduction SF6 gas is a very efficient dielectric, and due to its physical properties SF6 gas breakers are generally used in higher voltage situations. There are two major types of SF6 gas circuit breaker. They are grouped by the SF6 gas pressure that they use to extinguish the arc. Common Suppliers The following is a list of commonly found SF6 gas circuit breakers used in the typical system, they include: Of This Type: Types Within This • ITE • Kelman • GE • Westinghouse • Siemens • ABB • Mitsubishi There are two major types of SF6 gas circuit breaker: dual-pressure (gas 35 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches Category blast) and single-pressure (puffer). Dual Pressure Type As the name implies, there are two different pressure areas in a dual pressure SF6 circuit breaker, a low-pressure area and a high-pressure area. The low-pressure area insulates the contacts from the interrupting chamber cover and serves as a receiving tank during a breaker tripping operation. When the circuit breaker is tripped, high-pressure gas vents through the contacts and extinguishes the arc. Dual-pressure circuit breakers typically use the dead tank design. Single-Pressure Type In single-pressure SF6 circuit breakers, SF6 gas is maintained at a constant pressure in the interrupting chamber. At 230 kV and below, single-pressure SF6 breakers generally use the dead tank design. Basic Construction Both types of SF6 gas breakers will be discussed here. And Operation Arc Extinction In Dual-Pressure Circuit Breaker The interrupting mechanisms of a dual-pressure circuit breaker are enclosed in a tank of low-pressure SF6 gas as shown in Figure E-05-A29. The main arc extinguishing features include: • Main and arcing contacts • A reservoir of high-pressure SF6 • A blast valve • Blast tubes 36 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches Figure E-05-A-28 Dual Preassure SF6 Circuit Breaker The main features of the set of contacts are: • Hollow moving contacts • Stationary contact fingers which grip either end of the hollow moving contacts • An arcing horn • A blast tube When the V is closed, the current path is through the conductors insulated by bushings and through the contacts. The contacts are enclosed in low-pressure SF6 gas. When the breaker trips, the contacts separate and an arc forms. The arcing horn protrudes farther than the contact fingers that encircle it. Since an arc takes the shortest path between conductors, it transfers 37 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches from the stationary contact fingers to the arcing horn. Then it transfers from the outside surface of the movable contact to the inside surface. This minimizes burning of the contact fingers. In addition, the arcing horn is designed to withstand the intense heat of the arc for a very brief period. As the circuit breaker contacts continue to separate, the distance the arc must travel to sustain itself increases. At the same time, the contacts begin to separate, pressurized SF6 gas blasts through the blast tubes, through the arc, and through the hollow moving contact. The blast further lengthens the arc as well as cools it until the arc extinguishes at a current zero. Arc Extinction In Single-Pressure Circuit Breaker In single-pressure SF6 circuit breakers, SF6 gas is maintained at a constant pressure in the interrupting chamber. As the circuit breaker contacts open, a puff of gas is forced across the arc path quenching the arc as the contacts continue to separate. At 230 kV and below, singlepressure SF6 breakers generally use the dead tank design. Use Of Capacitors To Increase Interrupting Rating Capacitors are used to distribute the voltage equally to each set of contacts allowing greater interrupting capability of the breaker. Lightning Arrestors Lightning arrestors are used to protect normally opened system parallel point in the system. All normally opened circuit breakers are protected from the potential damage that could occur to the internals of a circuit breaker from a Lightning strike. Normally closed breakers generally do not receive the same amount of Lightning strike protection since the lines that they are connected to are, themselves, connected to protecting arrestors. Furthermore, if a Lightning strike should happen, the line itself would tend to dissipate the energy over the whole line and not allow the discharge to affect only one item. Synchronous Switching In the past, most of the electrical load on the system was motors (inductive) and restive loads, these types of loads are not very sensitive to short term voltage transients. Today, with modern electronic devices these transients can be very damaging to the internal components of the electronic devices. With the common use by business and homes of these devices, companies must be sensitive to how maintaining the system in proper operation parameters affects our end user and strives to minimize the effect of system operation on our customer. To limit transients on the system utilities use a new device, a Synchronous Control Unit (SCU) shown in Figure E-05-A-29. These units are being in installed in the breaker’s control cabinet, at the 38 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches factory, of some ABB SF6 200 kV and 66 kV breakers. Figure E-05-A-29 Synchronous Control Unit The SCU is a microprocessor-based control device that enables synchronized closing or opening of an Independent Pole Operated breaker. Synchronized closings reduces transients over-voltages and currents associated with switching operations of: • Shunt capacitor banks • Shunt reactors • Transformers • Transmission lines Utilities are using these devices with shunt capacitor banks when additional reactance (kVAR) is needed on the system. Simply put, the SCU monitors a number of parameters and shuts the breaker, when called to so that the breaker shuts at a zero current point. Thus, voltage transients on the system are minimized. Figure E-05-A-30 shows voltage and current effects on a worst case compared to a synchronous closing. 39 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches Figure E-05-A-30 Switching Transients (ABB –Synchronous Control Unit Operation) Alarms And Indications Common alarms associated with this type of breaker are: • Low-pressure alarm on the low-pressure side informs the Operator a problem exists with the low-pressure side of the SF6 breaker. • High-pressure cutout on the high-pressure side informs the Operator a problem exists with the high-pressure side of the SF6 breaker that will prevent its proper operation. The high-pressure cutout will trip the breaker if closed and will prevent its closing if opened. • Low-pressure cutout on the compressor shuts the compressor off when the low side becomes dangerously low. Common indications include: • High-pressure side gas pressure gauge • High-pressure side gas temperature gauge • High-pressure side gas pressure gauge • High-pressure side gas temperature gauge • Semaphore indication Applications This breaker type is generally used for higher voltage applications such as 66 kV to 500 kV. Typical Malfunctions Common problems are: 40 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches • Blown diaphragm • Gas leaks • Air compressor failure • Low gas • Gas temperatures • Excessive compressor run time Vacuum – 16 kV And Below Common Suppliers Common suppliers of this type of breaker to the system include: Of This Type • ABB • Square D • IEM • YIN • GE • Westinghouse Basic Construction The vacuum interrupter has been developed for voltages up to 36 kV. However, in the system they are only used up to 16kV. They can And Operation interrupt high voltage power with the contacts moving only 1/4 to 1/2 of an inch. The reason that vacuum breaker contacts have this capability is that a vacuum is an excellent insulator. Electrical current cannot flow across a gap between two conductors unless there is present, between the conductors, some source of ions or electrons. Obviously, if the gap is in a perfect vacuum, there are no ions or electrons. If two contacts which are butting and carrying current in a vacuum can be parted in the vacuum and a vacuum maintained as they part, the current will stop. Because of the design of vacuum breakers, small mechanisms with low power requirements can do the job previously requiring large mechanisms with huge springs and large operating power requirements. Some vacuum circuit breakers that are rated for operation at continuous current levels above 2000 amperes will employ two blowers. One is mounted on either side of the high voltage compartment to circulate air over the primary current carrying components (Vacuum Bottles) and 41 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches their respective heat sinks. The added cooling capacity provided by the blowers is required only for current levels that exceed 2000 amperes. The automatic mode of operation is designed to initiate the operation of the blowers when the primary current reaches or exceeds 2000 amperes. Furthermore, the system will secure blower operation when the primary current levels drops below the 2000 amperes level. It would seem that the vacuum breakers are an ideal process for highperformance circuit breakers. However, the interrupting chamber, commonly called a vacuum jar or jar seen in Figure E-05-A-31, is sealed porcelain or vitrified glass vessel, and maintenance of the contacts is not possible. The life, governed by contact erosion, is expected to be about 20 years, if the vacuum is maintained. Figure E-05-A-31 Vacuum Bottle Alarms And Indications Alarms: • Loss of fan power. In the event of a loss of fan power the operator must devalue the circuit breakers rating. Indications: • Semaphore Applications This breaker type is generally used for 16kV applications and below. Typical Malfunctions As an operator, you should inspect a vacuum breaker for the following, and take the appropriate action: 42 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches • Look for signs of insulator damage • Look for signs of heating • Listen for any unusual noises which might indicate any abnormal conditions • Looks at the indicating ammeters to be certain all three phases are open or closed depending upon the desired operation Self Contained Basic Construction Self-contained circuit breakers, or commonly referred to as reclosers, incorporate features of conventional oil or vacuum circuit breakers with And Operation other auxiliary systems such as relays, battery and charger, and metering. The auxiliary systems are housed in a separate cabinet from the circuit breaker mechanism housing. Self-contained circuit breakers are generally used in customer's service substations where installation and maintenance costs must be kept to a minimum. Bushing current transformers on the source side of the self-contained circuit breaker are used as the source for metering and relaying current. Figure E-05-A-32 shows a typical control panel for a self-contained circuit breaker. 43 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches Figure E-05-A-32 Typical Control Panel for a Self-Contained Circuit Breaker The major components of self-contained circuit breakers are listed below: • Circuit breaker mechanisms • Battery and charger • Control Switch • Meters • Relays •Minimum trip resistors determine the load current value that will trip the circuit breaker •Timing plugs: set the "time curve" characteristic 44 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches • Selectors: set the speed of phase and ground current relay operation • Lockout selector: sets the number of automatic re-close operations • Re-closing interval plugs: set the time interval between the relay operation and actual re-closing • Reset delay plug: sets the reset time for a sequence of operations • Relay targets: indicate relay operation by buttons (pop-out type) or a counter • Trip operation counter: operates (advances) each time the circuit breaker operates • Lockout indicator lamp: provides visual indication that the circuit breaker has completed all relaying and re-closing cycles and has locked out. • Re-closing relay switch: allows the re-closing function to be cut in or cut out • Ground trip blocking disables ground relay tripping to prevent unintentional operation of the circuit breaker during bypass switching Arc Extinction In self-contained Circuit Breakers The interrupting unit of self-contained circuit breakers is very similar to those found in other oil or vacuum circuit breakers of similar voltage classes. All three phases are contained in a single vacuum or oil-filled tank. Arc extinction in self-contained circuit breakers is also similar to the arc extinction in oil or vacuum circuit breakers discussed earlier. Alarms And Indications Alarms and indications in self-contained circuit breakers are also similar to the alarms and indications in oil or vacuum circuit breakers discussed earlier. Applications Applications of self-contained circuit breakers are the same as applications of oil or vacuum circuit breakers discussed earlier. Typical Malfunctions Typical malfunctions in self-contained circuit breakers are the same as those of oil or vacuum circuit breakers discussed earlier with the addition of control circuit problems of the self-contained unit. 45 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches 4. Types of Operating Mechanisms There are six different types of circuit breaker mechanisms that are commonly used in the system, they are: • Manual • Solenoid • Pneumatic • Motor Spring • Hydraulic • Gas Each will be reviewed in this section, covering the way it operates, any associated alarms and indications, and its application. Furthermore, any problems that the mechanisms are prone, to which the operator should be sensitive, are covered as well. Manual Basic Construction The first type of circuit breaker mechanism is the manual device. It requires the Operator to supply the closing force through a handle And Operation connected to an operating arm and mechanical linkages to the main circuit breaker contacts. A manual operator is pictured in Figure E-05A-33 and illustrated in Figure E-05-A-35. This type of mechanism is seen mostly in older substations in the Station Light and Power circuit. Manual operating mechanisms are available to close small circuit breakers. They use a lever-operated toggle mechanism that releases energy from a relatively small spring. They may or may not have tripping capability. If they cannot trip, a back up protective device is applied. 46 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches Figure E-05-A-33 Manual Operator Figure E-05-A-34 Manual-Type Operating Mechanism Alarms And Indications Alarms: • There are no alarms associated with the manual operating mechanism. Indications: • Applications The manual operating mechanism has only a semaphore There are very few of these mechanisms left in the system. This type of 47 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches mechanism may be found in older substations in the Station Light and Power circuit. Typical Malfunctions Be observant of the following possible problems with the manual operating mechanism: • Poorly operating hinge or lever points • Linkages that do not operate freely Solenoid Basic Construction The solenoid mechanism, shown in Figure E-05-A-35 and Figure E-05A-37, incorporates a large solenoid or coil that produces a strong And Operation magnetic field when a DC current flows through it. An armature or iron bar, which is connected by mechanical linkages to the breaker’s contacts, will be attracted into the solenoid by the magnetic field. The components are shown in the positions they would be in when the breaker's contacts are open. The components involved in closing the breaker are a solenoid (which consists of a coil, a plunger, and a push rod), and an arrangement of links and levers, and an operating rod. The device that provides the force to close the circuit breaker is the solenoid. To close the breaker, the energized solenoid, or closing coil, creates a magnetic field. The magnetic field pulls the plunger into the solenoid, causing the push rod to push against the links and levers. The connected links and levers then move the operating rod. The operating rod causes the circuit breaker to close. Figure E-05-A-35 Solenoid Operating Mechanisms 48 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches Figure E-05-A-36 Solenoid Operating Mechanism Alarms And Indications Alarms: • There are no alarms associated with the solenoid operating mechanism. Indications: • The solenoid operating mechanism has only a semaphore. Applications This type of circuit breaker mechanism is found on circuit breakers at voltages from 440 V to 66 kV. Typical Malfunctions Know how to tell if the closing coil remains energized after a closing operation. The coil will burn out if continuously energized; it is not designed for continuous duty. Know what to do if the closing coil or closing circuit malfunctions. Damage to the coil may result. Know where the DC knife switch is located, so the operator can restore normal configuration if the switch is left open after performed maintenance. This prevents unnecessary issuance of a maintenance request if the breaker is not properly restored after a maintenance operation. Recognize broken components inside the mechanism compartment. Prevents further damage to a breaker. Pneumatic Basic Construction Pneumatic operating mechanisms use a piston driven by compressed high-pressure air to apply closing and tripping forces to the mechanism. And Operation Since high-pressure air is used, an air compressor and storage tank is necessary. The controls on the compressed air lines, however, are 49 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches electrically operated. Most pneumatic circuit breakers use a solenoid to trip the circuit breaker however, some Mitsubishi and Westinghouse 220 kV breakers use air for tripping. A variation of pneumatic operation is pneumatic closing with a tripping spring being compressed during the pneumatic closing operation. The pressure varies from a few hundred to several thousand psi. Figure E-05-A-38 shows a simplified pneumatic operating mechanism. To Close To close the circuit breaker, an electrically operated air valve is opened between the air storage tank and the closing piston. When the close coil valve is energized, the control valve opens and permits pressurized air from the air reservoir tank to flow into a cylinder with a piston. This drives the piston and closes the circuit breaker by means of a mechanical linkage. The circuit breaker has a latching mechanism to hold it closed. Through a series of auxiliary contacts, the air valve coil is de-energized, closing the air valve, and allowing the piston to return to its normal position. To Open To open the circuit breaker contact, the trip coil is energized. A plunger releases the latch, permitting the circuit breaker contacts to open. The spring, not shown, compressed during the closing sequence, releases and speeds the opening of the circuit breaker contacts. For this type of circuit breaker mechanism, the control cabinet contains the compressor and motor, the air valve, the air storage facilities, the closing and tripping coils, and the control devices. Advantage The advantage of this design is that relatively low power is demanded when initially pressurizing or maintaining established system pressure in a pneumatic cylinder. However, once the circuit breaker operational sequence begins, the energy stored in the pneumatic cylinder will be released and generate a tremendous amount of closing power. This closing power will be of a magnitude much greater than possible with the maximum output of the low energy pneumatic cylinder charging circuit. 50 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches Figure E-05-A-37 Pneumatic Mechanism Alarms And Indications Alarms: • Low air pressure Indications: • Semaphore Applications Pneumatic mechanism permits high speed closing, therefore it is used on voltages from 33 kV to 500 kV. Typical Malfunctions The Operator should be aware of the following when operating with a pneumatic mechanism: • Improper maintenance restoration: o Know the location of the DC switch. • Compressor problems: o Proper compressor operation set points. o Know the location of the compressor control switch. 51 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches o Know what to do if a pressure alarm sounds. o Lock out or tripping points. o Know how to reset a tripped compressor. o Look for any broken parts. o Check compressor oil level if indicating devices are available. o Know the location of the air receiver drain valve. • Air pressure problems o Pressure gauges and what are their normal indications. o What actions required for a loss of air pressure. o Listen for air leaks. o Look for any broken parts. Motor Spring Basic Construction The motor spring mechanism uses an electric motor, usually DC, to compress one or more springs as illustrated in Figure E-05-A-38. The And Operation motor in the mechanism is energized and de-energized through auxiliary contacts in the mechanism, called pallets or micro switches, and through a DC knife switch. The compressed spring stores energy until a closing signal is received. When a close signal is received, the circuit breaker operates by mechanically releasing the springs. The spring then expands and uses a series of linkages to shut the circuit breaker’s main contacts. The circuit breaker simultaneously charges or compresses a smaller coil spring that is used to trip the circuit breaker. The motor spring mechanism provides high speed closing and tripping. 52 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches Figure E-05-A-38 Spring Motor, Shutting Alarms And Indications Alarms: • None Indications: • Semaphore • Spring charge Applications This mechanism is used on breakers operating in a voltage up to 115kV. Typical Malfunctions The Operator should be aware of the following when operating with a motor spring mechanism: • Maintenance restoration errors: •Know the location of the DC knife switch •Know the location of the motor control switch • Breaker operation problems: 53 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches o Identify that the breaker failed to close o What to do if the breaker fails to close • Compressor problems: o Look for any loose parts on the floor of the mechanism cabinet o What to do if the compressor tripped on thermal overload o What to do if the compressor tripped Hydraulic Basic Construction A hydraulic mechanism, as seen Figure E-05-A-39, operates similar to a pneumatic mechanism except that hydraulic fluid is used instead of And Operation compressed air. The two mechanisms use similar devices, except the hydraulic system uses a pump, check valve, and a relief valve instead of the compressor assembly of the air system in the pneumatic mechanism. A motor governor switch, low-pressure alarm, and closing lockout function the same way as they do on an air system. Figure E-05-A-39 Hydraulic Operated Mechanism 54 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches Hydraulic operating mechanisms use a liquid, not a gas to transport the energy needed by the mechanism to operate the breaker. Because fluids cannot be compressed, an additional device called an accumulator is used. The accumulator is to the hydraulic system as the air receiver is to the pneumatic system, a means of storing energy. The hydraulic fluid is pressurized by the pumping system that has low energy consumption requirements. The major difference between the hydraulic and pneumatic system is the hydraulic system tends to be pressurized to a higher pressure. Hydraulic operating mechanisms are smaller in design and susceptible to operational failure if a leak occurs. This form of operating mechanism can generate more closing force than the other mechanisms presented. Unfortunately, the cost associated with this system limits the use of hydraulic operated mechanisms to systems that require high-energy output mechanisms. To close the circuit breaker, an electrically operated valve is opened between the accumulator and the closing piston. This allows the piston to move against the mechanical linkage and close the circuit breaker contacts. When the breaker has reached the closed position, the closing valve is de-energized and the piston returns to its normal position. OA3 Hydraulic Operating Mechanism Figure E-05-A-40 illustrates an opened OA3 hydraulic operating mechanism. Figure E-05-A-41 illustrates a closed OA3 hydraulic operating mechanism. Figure E-05-A-42 illustrates an OA3 hydraulic operating mechanism’s accumulator. 55 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches Figure E-05-A-40 OA3 Hydraulic Operating System, Opened 56 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches Figure E-05-A-41 OA3 Hydraulic Operating System, Closed 57 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches Figure E-05-A-42 OA3 Hydraulic Operating System, Accumulator ABB Breaker That Is Spring, Motor, And Hydraulic Operated A new mechanism (HMB) design was developed by ABB. The new design uses a merging of a spring, motor and hydraulic design. This new breaker mechanism is shown in Figure E-05-A -43. Hydraulics is used to charge the spring, which stores a high quantity of potential mechanical energy. The spring is used to open and shut the breaker and the motor is used to charge the hydraulic system. 58 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches Figure E-05-A -43 ABB Spring, Motor, Hydraulic Mechanism Alarms And Indications Alarms: Hydraulic fluid high-pressure alarm Hydraulic fluid low-pressure alarm Indications: Semaphore Spring charge (on new ABB Mechanism) Applications This mechanism is used on breakers operating 66kV and above. Typical Malfunctions To identify potential problems with this mechanism, use the following listed items. Things to know: • Location of the DC knife switch • Location of the hydraulic pump motor control switch On the pressure gauge know: • Normal pressure • Normal pump start pressure • Normal pump stop pressure 59 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches • High-pressure Alarm set point • Low-pressure Alarm set point • Lockout pressure Inspection items: • Check for hydraulic oi1 leaks • Check for broken parts Gas Basic Construction Gas operating mechanisms use compressed high-pressure nitrogen to apply closing forces directly to the mechanism. The gas (nitrogen) And Operation operating mechanisms use the same principles as the pneumatic operating mechanisms. Refer to the pneumatic operating mechanism in this section for more information. Alarms And Indications Alarms: • Low pressure Indications: • Semaphore Applications This mechanism permits high speed closing. It is used on voltages from 16kV to 500kV. Typical Malfunctions The Operator should be able to perform the following when operating with a nitrogen mechanism: • Know the location of the DC switch. • Know actions required for a loss of pressure. • Pressure gauges and what they indicate. • Listen for leaks. • Look for any broken parts. • Check compressor oil level if indicating devices are available. • Know the location of the air receiver drain valve. 60 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches 5. Circuit Switches Circuit switches provide the system with additional switching capabilities at a reduced cost, but circuit switches are not designed to interrupt faults. Generally, they are used for connecting items such as a capacitor bank to the system. Common Suppliers Common Suppliers Common suppliers of circuit switches to the typical system includes: • Soslyn • A.C. • Kyle • S&C Construction Oil Oil circuit switches rely solely on the head of oil in its case and the pressure of the gas that will be developed to control and extinguish the arc. The oil circuit switches has an insulated cylinder attached to the fixed contact with an aperture through which the moving contact draws the arc on opening. The high-pressure gas that is generated within the circuit switches sweeps the arc, and the ionizing gas, through the aperture. Coupled with the oil’s ability to absorb heat, the arc is readily extinguished by cooling. Gas Gas circuit switches use SF6 gas as their dielectric. Because SF6 is an electronegative gas, it combines with the arc and produces a relative immobile ion. The loss of available conducting electrons causes the arc to be extinguished at current zero. Vacuum Vacuum circuit switches use a vacuum as their dielectric. A vacuum is an excellent insulator. Electrical current cannot flow across a gap between two conductors unless there is present, between the conductors, some source of ions or electrons. Obviously, if the gap is in a perfect vacuum, there are no ions or electrons to allow the arc to continue. Therefore, the arc is quickly extinguished. Operation Motor The motor mechanism uses a motor to open or shut the switches contacts. When a close signal is received, the switches motor operates 61 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited. VATIC Associates VAT-E-05 Circuit Breakers and Switches using a series of linkages to shut the switches contacts. Motor-Spring Motor charged spring operating mechanisms, uses a motor to compress a coil spring. The compressed spring stores energy until a closing signal is received. When a close signal is received, the switches operate by mechanically releasing the springs. The spring then expands and uses a series of linkages to shut the switches contacts. This mechanism provides high-speed operation. Solenoid The solenoid mechanism incorporates a solenoid or coil that produces a strong magnetic field when a DC current flows through it. An armature or iron bar that is connected by mechanical linkages to the switches contacts will be attracted into the solenoid by the magnetic field. By energizing the solenoid, the switches contacts are opened or closed. Alarms and Indications Motor operated switches may provide a loss of AC alarm. Application Capacitors Circuit switches are used to add or remove capacitor bank(s) as the kVAR requirements of the system changes. Lines Circuit switches are used to sectionalize lines. They are used to make or break parallels between lines. Configurations The switches are generally three-phase ganged switches. Interlocks There are no interlocks associated with circuit switches. Malfunctions Due to how they are used, switches typically operate without problems. However, they do require routine maintenance to perform properly. 62 of 62 Copyrighted by VATIC Associates – Duplication or unauthorized use is prohibited.