Debre Tabor University Faculty of technology POWER SYSTEM I Mechanical design of transmission lines 1 Outline Introduction Sag and tension calculations Effect of wind and ice loading Stringing chart Sag template 2 INTRODUCTION A proper mechanical design is one of the essentials in providing good service to customers A large majority of service interruptions can be traced to physical failures on the distribution system, broken wires, broken poles, damaged insulation, damaged equipment, etc Of course, many of these service interruptions are more or less un avoidable, but their numbers can be reduced if the design and construction of the various physical parts can withstand, with reasonable safety factors, not only normal conditions but also some probable abnormal conditions The conductors and poles must have sufficient strength with a predetermined safety factor to withstand the loads due to the line itself and stresses imposed by ice and wind loads. Thus, the overhead line should provide satisfactory service over a long period of time without the necessary for too much maintenance Ultimate economy is provided by a good construction since excessive maintenance or especially short life can be easily more 3 than overbalance a saving in the first cost. The overhead line must have a proper strength to withstand the stresses imposed on its component parts by the line itself. These include stresses set up by the tension in conductors at dead end points, compression stresses due to guy tension, vertical stresses due to the weight of conductors, and the vertical component of conductor tension The tension in the conductors should be adjusted so that it is well within the permissible load of the material. This will mean in practice that one must allow for an appreciable amount of sag. 4 In general, the factors affecting a mechanical design of the overhead lines are: 1. Character of line route 2. Right of way 3. Mechanical loading 4. Required clearances 5. Types of supporting structures 6. Grade of construction 7. conductors 8.Types of insulators 9. Joint use by the utilities 5 Main Components of Overhead Lines In general, the main components of an overhead lines are: Conductors:- which carry electric power from the sending end station to the receiving end station Supports:- which may be poles or towers and keep the conductors at a suitable level above the ground Insulators:- which are attached to support and insulate the conductors from the ground Cross arms:- which provide support to the insulators Shield wires:- which provides grounding and communication services for the overhead transmission line. Miscellaneous items:- such as phase plates, danger plates, anti-climbing wires, etc 6 Conductor materials The conductor is one of the important items as most of the capital outlay is invested for it. Therefore, proper choice of material and size of conductor is of considerable importance The conductor material used for transmission and distribution of electric power should have the following properties: High electrical conductivity High tensile strength in order to withstand mechanical stresses Low cost so that it can be used for long distances Low specific gravity so that weight per unit volume is small All above requirements are not found in a single material. Therefore, while selecting a conductor material for a particular case, a compromise is made between the cost and the required electrical and mechanical properties 7 Commonly used conductor materials The most commonly used conductor materials for overhead lines are copper, aluminum, steel cored aluminum, galvanized steel and cadmium copper The choice of a particular material will depend up on the cost, the required electrical and mechanical properties and local conditions All conductors used for overhead lines are preferably stranded in order to increase the flexibility 8 Copper: Copper is an ideal material for overhead lines owing to its high electrical conductivity and grater tensile strength It is always used in the hard drawn form as stranded conductor. Although hard drawn decreases the electrical conductivity slightly yet it increases the tensile strength considerably The merits of this metal as a line conductor are: i. It has a best conductivity in comparison to other metals. The conductivity of copper, however depends upon the percentage of impurities present in it, the more the impurities the lesser will be the conductivity. The conductivity of copper conductor also depends upon the method by which it has been drawn. ii. It has higher current density, so for the given current rating, lesser cross-sectional area of conductor is required and hence it provides lesser cross-sectional area to wind loads iii. The metal is quite homogeneous iv. It has low specific resistance v. It is durable and has a higher scrap value 9 Aluminum: Aluminum is cheap and light as compared to copper but it has much smaller conductivity and tensile strength Next to copper aluminum is the conductor used in order of performance as far as the conductivity is concerned. Its merits and demerits are: i. It is cheaper than copper ii. It is lighter in weight (the specific gravity of aluminum is lower than that of copper, i.e an aluminum conductor has almost one half the weight of equivalent copper conductor) iii. It is second in conductivity (among the metals used for transmission). Commercial hard-down aluminum wire at standard temperature has approximately 60.6 percent conductivity in comparison to standard annealed copper wire. iv. For same ohmic resistance, its diameter is about 1.27 times that of copper. v. At higher voltages it causes less corona loss vi. Since the diameter of the conductor is more, so it is subject to greater wind pressure due to which greater is the swing of the conductor and greater is the sag vii. Since the conductors are liable to swing, so it requires larger cross arms 10 viii. As the melting point of the conductor is low , so the short circuit etc. will damage it . ix. Joining of aluminum is much more difficult than that of any other material In the modern over head transmission system, bare aluminum conductors are used (for purpose of heat dissipation) which are classifies as: AAC - All Aluminum Conductors AAAC - All Aluminum Alloy Conductors ACSR – Aluminum Conductors Steel Reinforced ACAR - Aluminum Conductors Alloy Reinforced Steel • • No doubt it has got the greatest tensile strength, but it is least used for transmission of electrical energy as it has got high resistance. Bare steel conductors are not used since, it deteriorates rapidly owing to rusting. Generally galvanized steel wires are used. 11 It has the following properties: i) It is lowest in conductivity ii ) It has high internal reactance iii ) It is much subjected to eddy current and hysteresis loss iv ) In a damp atmosphere it is rusted Hence its use is limited Line supports The supporting structures for overhead line conductors are various types of poles and towers called line supports In general, the line supports should have the following properties High mechanical strength to withstand the weight of conductors and wind load etc Light in weight without the loss of mechanical strength Cheap in cost and economical to maintain Longer life Easy accessibility of conductors for maintenance 12 The line supports used for transmission and distribution of electric power are of various types Wooden poles Steel poles Reinforced concrete (R.C.C) poles Lattice steel towers Wooden poles: These are made of seasoned wood and are suitable for lines of moderate X- section area and of relatively shorter span, say up to 50 meters Such supports are cheap, easily available, provide insulating properties and therefore, are widely used for distribution purposes in rural areas as an economical proposition The wooden poles generally tend to rot below the ground level, causing foundation failure. In order to prevent this, the portion of the pole below the ground level is impregnated with preservative compounds like creosote oil Double pole structures of the ‘A’ or ‘H’ type are often used (see fig. below) to obtain a higher transverse strength than could be economically provided by means of a single poles 13 The main objections wooden supports are: to (i). Tendency to rot below the ground level (ii). Comparatively smaller life (20-25 years) (iii). Cannot be used for voltages higher than 20 kV (iv). Less mechanical strength and (v). Require periodical inspection Figure wooden poles 14 Steel poles: The steel poles are often used as a substitute for wooden poles They posses greater mechanical strength, longer life and permit longer spans to be used Such poles are generally used for distribution purposes in the cities This type of supports need to be galvanized or painted in order to prolong its life The steel poles are of three types Rail poles Tubular poles and Rolled steel joints RCC poles: The RCC poles have become very popular as line supports in recent years They have greater mechanical strength, longer life and permit longer spans than steel poles. 15 Moreover, they give good outlook, require little maintenance and have good insulating properties. Figure below shows R.C.C poles for single and double circuit The holes in the poles facilitate the climbing of poles and at the same time reduce the weight of line supports The main difficulty with the use of these poles is the high cost of transport owing to their heavy weight. 16 Steel tower: In practice, wooden, steel and reinforced concrete poles are used for distribution purposes at low voltages, say up to 15 kV. However, for long distance transmission at higher voltage, steel tower are invariably employed Steel towers have greater mechanical strength, longer life, can withstand most sever climatic conditions and permit the use of longer spans The risk of interrupted service due to broken or punctured insulation is considerably reduced owing to longer spans Tower footings are usually grounded by driving rods into the earth, this minimizes the lightning troubles as each tower acts as a lightning conductor 17 18 Spacing between the conductor The most suitable spacing between the conductors can be arrived at by mathematical calculations. It can only be obtained by empirical formulae which have been obtained from practical considerations. 19 Generally the following formulae is used for obtaining spacing between the conductors(phases): Spacing (cm) 0.3048 x V 4.010 D W S Where V = Voltage of system in kV D = Diameter of Conductor in cm S = sag in cm W = weight of conductor in kg/m In addition to phase conductors, a transmission line usually includes one or two steel wires called shield wires. These wires are electrically connected to the tower and to the ground, and, therefore, are at ground potential. In large transmission lines, these wires are located above the phase conductors, shielding them from lightning. 20 21 Insulators The overhead line conductors should be supported on the poles or towers in such a way that currents from conductors do not flow to earth through supports. Provide Electrical insulation between live conductor and earthed structure under operating and overvoltage conditions. To act as a reliable mechanical link between the structure and the conductor and keep the mechanical integrity under normal operating and overload conditions. The insulators are mainly made of either glazed, porcelain or toughened glass. The dielectric strength of porcelain should be 15KV to 17KV for every one tenth inch thickness. Porcelain is mechanically strong, less affected by temperature and has minimum leakage problem. 22 Toughened glass is also sometimes used for insulators because it has higher dielectric strength (35KV for one tenth inch thickness), But it has lower coefficient of thermal expansion. And it condenses moisture very easily (since those reasons it use is limited up to 33KV ) In general, the insulators should have the following desirable properties: High mechanical strength in order to withstand conductor load, wind load, etc High electrical resistance of insulator material in order to avoid leakage current to earth. High relative permittivity of insulator material in order that dielectric strength is high. The insulator material should be non-porous, free from impurities and cracks otherwise the permittivity will be lowered. High ration of puncture strength to flashover. 23 Types of insulators In overhead transmission lines, the conductors are suspended from a pole or a tower via insulators. There are several types of insulators but the most commonly used are pin type, suspension type, strain insulator and shackle insulator Pin type insulators consist of a single or multiple shells adopted to be mounted on a spindle to be fixed to the cross arm of the supporting structure. Multiple shells are provided in order to obtain sufficient length of leakage There is a groove on the upper end of the insulator for housing the conductor. The conductor passes through this groove and is bound by the annealed wire of the same material as the conductor Pin type insulators are used for transmission and distribution of electric power at voltages up to 33 kV. Beyond operating voltage of 33 kV, the pin type insulators become too bulky and hence uneconomical. 24 Cause of insulator failure Insulators are required to withstand both mechanical and electrical stresses The latter type is primarily due to line voltage and may cause the breakdown of the insulator The electrical break down of the insulator can occur either by flash-over or puncture 25 In flash over, an arc occurs between the line conductor and insulator pin (i.e, earth) and the discharge jumps across the air gaps, following shortest distance In case of flash-over, the insulator will continue to act in its proper capacity unless extreme heat produced by the arc destroys the insulator In case of puncture, the discharge occurs from conductor to pin through the body of the insulator When such breakdown is involved, the insulator is permanently destroyed due to excessive heat. In practice, sufficient thickness of porcelain is provided in the insulator to avoid puncture by the line voltage The ratio of puncture strength to flash over voltage is known as safety factor Puncture strength Safety factor of insulator = Flash-over voltage 26 Suspension type insulators The cost of pin type insulator increases rapidly as the working voltage is increases. Therefore, this type of insulator is not economical beyond 33 kV. For high voltages (greater than 33 kV), it is a usual practice to use suspension type insulators shown in figure below. They consists of a number of porcelain discs connected in series by metal links in the form of a string The conductor is suspended at the bottom end of this string while the other end of the string is secured to the cross-arm of the tower. The number of discs in series would obviously depend upon the working voltage 27 Advantages (i). Suspension type insulators are cheaper than pin type insulators for voltages beyond 33 kV (ii). Each unit or disc of suspension type insulator is designed for low voltage, usually 11 kV. Depending upon the working voltage, the desired number of discs can be connected in series (iii). If any one disc is damaged, the whole string does not become useless because the damaged disc can be replaced by the sound one (iv). The suspension arrangement provides greater flexibility to the line. The connection at the cross arm is such that insulator string is free to swing in any direction and can take up the position where mechanical stress are minimum (v). In case of increased demand on the transmission line, it is found more satisfactory to supply the greater demand by raising the line voltage than to provide another set of conductors. The additional insulation required for the raised voltage can be easily obtained in the suspension arrangement by adding the desired number of discs 28 (vi). The suspension type insulators are generally used with steel towers. As the conductors run below the earthed cross-arm of the tower, therefore, this arrangement provides partial protection from lightning Strain Insulators When there is a dead end of the line or there is corner or sharp curve, the line is subjected to greater tension. In order to relive the line of excessive tension, strain insulators are used For low voltage lines (less than 11 kV), shackle insulators are used as strain insulators. However, for high voltage transmission lines, strain insulators consists of assembly of suspension insulators as shown in figure below. The discs of strain insulators are used in the vertical plane. When the tension in line is exceedingly high, as at long river spans, two or more strings are used in parallel 29 Shackle Insulators In early days, the shackle insulators were used as strain insulators. But now a day, they are frequently used for low voltage distribution line. Such insulators can be used either in a horizontal position or a vertical position 30 They can be directly fixed to the pole with a bolt or to the cross arm. Figure below shows a shackle insulator fixed to the pole. The conductor in the groove is fixed with a soft binding wire Figure: Shackle insulator 31 Potential distribution over suspension insulators string A string of suspension insulators consists of a number of discs connected in series. each disc forms a capacitor C mutual capacitance or selfcapacitance. If there were mutual capacitance alone, then charging current would have been the same through all the discs and consequently voltage across each unit would have been the same i.e.,V/3. However, in actual practice, shunt capacitance C1 also exists between metal fitting of each disc and tower or earth. Due to shunt capacitance, charging current is not the same through all the discs of the string. Therefore, voltage across each disc will be different. 32 33 N.B: V3 will be much more than V2 or V1 The voltage impressed on a string of suspension insulators does not distribute itself uniformly across the individual discs due to the presence of shunt capacitance. The disc nearest to the conductor has maximum voltage across it. The unit nearest to the conductor is under maximum electrical stress. • 34 String Efficiency The ratio of voltage across the whole string to the product of number of discs and the voltage across the disc nearest to the conductor. String efficiency is decides the potential distribution along the string. The greater the string efficiency, the more uniform is the voltage distribution. 35 Mathematical expression. Consider he equivalent circuit for a 3-disc string. Let as assume self capacitance of each disc is C. and shunt capacitance C1 is some fraction K of self capacitance i.e., C1 = KC. Applying Kirchhoff’s current law to node A, we get: 36 Applying Kirchhoff’s current law to node B, we get: Voltage between conductor and earth (i.e., tower) is: 37 Voltage across top unit: Voltage across second unit from top, Voltage across third unit from top, %age String efficiency = 38 Methods of Improving String Efficiency The various methods for this purpose are : 1. By using longer cross-arms 2. By grading the insulators. 3. By using a guard ring. 39 Exercises In a 33 kV overhead line, there are three units in the string of insulators. If the capacitance between each insulator pin and earth is 11% of self-capacitance of each insulator, find: 1) i. ii. the distribution of voltage over 3 insulators string efficiency. A 3-phase transmission line is being supported by three disc insulators. The potentials across top unit (i.e., near to the tower) and middle unit are 8 kV and 11 kV respectively. Calculate (i) the ratio of capacitance between pin and earth to the self-capacitance of each unit. (ii) the line voltage and (iii) string efficiency 2) 40 Transmission line design consideration The design is based on optimization of electrical, mechanical, environmental and economic factors. 1.Electrical Factors ◦ Types, size and number of bundle conductors per phase. ◦ Number of insulator disks, string arrangement, phase to phase clearance, phase to tower clearance,… ◦ Number, type and location of shield wires. ◦ Line heights to satisfy conductor to ground clearance and conductor spacing. 2. Mechanical Factors: Major focus of this factor are: ◦ Strength of conductors ◦ Strength of insulator strings ◦ Strength of support structure 41 3.Environmental Factors It focuses on land usage and visual impacts. ◦ The Effects on local communities and population centers. ◦ Land values ◦ Access to property and wildlife ◦ Use of public parks and facilities. 4.Economic Factors ◦ Optimum line design – meets technical design criteria with lower overall cost. ◦ Overall cost include total installed cost as well as cost of line losses over operating life of the line. 42 SAG IN OVERHEAD LINES While erecting an overhead line, it is very important that conductors are under safe tension. If the conductors are too much stretched between supports in a bid to save conductor material, the stress in the conductor may reach unsafe value and in certain cases the conductor may break due to excessive tension. In order to permit safe tension in the conductors, they are not fully stretched but are allowed to have a dip or sag. The difference in level between points of supports and the lowest point on the conductor is called sag. Fig. below (i) shows a conductor suspended between two equivalent supports A and B. The conductor is not fully stretched but is allowed to have a dip. The lowest point on the conductor is O and the sag is S.The following points may be noted : 43 a) b) c) d) When the conductor is suspended between two supports at the same level, it takes the shape of catenary. However, if the sag is very small compared with the span, then sag-span curve is like a parabola. The tension at any point on the conductor acts tangentially. Thus tension TO at the lowest point O acts horizontally as shown in Fig. (ii). The horizontal component of tension is constant throughout the length of the wire. The tension at supports is approximately equal to the horizontal tension acting at any point on the wire. Thus if T is the tension at the support B, then T = TO. 44 SAG AND TENSION CALCULATIONS We shall now calculate sag and tension of a conductor when : (i) supports are at equal levels and (ii) supports are at unequal levels A. When supports are at equal levels: Consider a conductor between two equi-level supports A and B with O as the lowest point as shown in Fig. It can be proved that lowest point will be at the mid-span. where: l = Length of span w = Weight per unit length of conductor T = Tension in the conductor 45 Consider a point P on the conductor. Taking the lowest point O as the origin, let the co-ordinates of point P be x and y. Assuming that the curvature is so small that curved length is equal to its horizontal projection (i.e., OP = x), the two forces acting on the portion OP of the conductor are : a) The weight wx of conductor acting at a distance x/2 from O. b) The tension T acting at O. Equating the moments of above two forces about point O, we get: 46 The maximum dip (sag) is represented by the value of y at either of the supports A and B. At support A, When supports are at unequal levels: • conductors suspended between supports at unequal levels. • Fig. shows a conductor suspended between two supports A and B which are at different levels. The lowest point on the conductor is O. B. • 47 Let: l = Span length h = Difference in levels between two supports x1 = Distance of support at lower level (i.e., A) from O x2 = Distance of support at higher level (i.e. B) from O T = Tension in the conductor 48 If w is the weight per unit length of the conductor, then: 49 • Solving x1 and x2 • Having found x1 and x2, values of S1 and S2 can be easily calculated. Ex 1: A 132 kV transmission line has the following data : Wt. of conductor = 680 kg/km ; Length of span = 260 m Ultimate strength = 3100 kg ; Safety factor = 2 Calculate the height above ground at which the conductor should be supported. Ground clearance required is 10 meters. 50 Effect of wind and ice loading The above formulae for sag are true only in still air and at normal temperature when the conductor is acted by its weight only In actual practice, a conductor may have ice coating and simultaneously subjected to wind pressure Under the severest conditions of ice covering and wind, the stress over the line is increased to the maximum. Under this condition the per unit length of the wire w experiences the following loading i. The weight of the conductor w acting vertically downwards ii. The ice loading wi acting vertically downwards and iii. The wind loading ww acting horizontally 51 Ice Loading: Let r be the radius of the conductor and t be the thickness of ice (figure below) The volume of ice per unit length r t r 2 .1 2 Figure: Ice coated conductor 2rt t 2 .1 If is the density of ice (912 kg/m3 ), the weight of ice per unit length of conductor wi 2rt t 2 kg/m 52 Wind Loading: Let P be the wind pressure in kg/m2; assuming the ice coating of thickness t, the projected area per unit length on which the wind is acting is a = 2 r t .1 sq.meters wind loading w w per unit length will be ww 2 r t .P kg/meter Total vertical loading w wi Total loading (effective load acting on the conductor) is We w wi ww2 2 The load factor q We / w 53 Therefore sag can be calculated as we L2 d i.e T H approximation 8T 54 Example 1. A stress-crossing overhead transmission line has a span of 150 m over the stream. Horizontal wind pressure is 20 kg/m2 and the thickness of ice is 1.25 cm. diameter of conductor is 2.80 cm and weight is 1520 kg/km, and an ultimate strength of 12900 kg. use a factor of safety of 2 and 912 kg/m3 for the weight of ice. Using the parabolic method, determine the following a).Weight of ice in kg per meter b).Total vertical load on conductor in kg/m c). Horizontal wind force exerted on line in kg/m d). Effective load acting on conductor in kg/m e). Sag in meter f).Vertical sag 55 Solution a). Weight of Ice is wi 2rt t 2 kg / m 912 x 2 x1.4 x10 x1.25 x10 2 2 1.25 x10 2 2 2865.1325 0.00035 0.00015625 1.45 kg/m b). Total vertical load on the conductor is wT w wi 1520 kg/km 1.45 kg/m (1.520 1.45) kg/m 2.97 kg/m 56 c). Horizontal wind force exerted on the transmission line is ww 2 r t .P kg/m 2 1.4 x102 1.25 x102 x 20 kg/m 2 0.014 0.0125 x 20 kg/m 1.06 kg/m d). Effective load on the conductor is we ww2 wT2 1.06 2 2.97 2 kg/m 9.9445 kg/m 3.154 kg/m 57 e). Sag in meter using parabolic (approximate method) is Ultimate strength Factor safety 12900 kg 6450 kg 2 we L2 d 8T 3.154 x (150) 2 8 x 6450 T= 1.3753 m f). The vertical sag is Vertical sag = dcos , but cos = =1.3753 ( 2.97 1.06 2.97 ) 1.06 = 3.853 m 58 Stringing chart For use in the field work of stringing the conductors, temperature- sag and temperature-tension charts are plotted for the given conductor and loading conditions. Such curves are called stringing charts (see figure below) These charts are very helpful while stringing overhead lines 59 Sag Template For correct design and economy, the location of structures on the profile with a template is very essential Sag template is a convenient device used in the design of a transmission line to determine the location and height of structures Sag template can be relied upon to provide the following: 1. 2. 3. 4. Economic layout Minimum errors in design and layout Proper grading of structures Prevention of excessive insulator swing Generally two types of towers are used: 1. The standard or straight run or intermediate tower 2. The angle or anchor or tension tower 60 The straight run towers are used for straight runs and normal conditions. The angle towers are designed to withstand heavy loading as compared to standard towers because angle towers are used at angles, terminals and other points where a large unbalanced pull may be thrown on the supports For standard towers, for normal or average spans, the sag and the nature of the curve (Catenary or parabola) that the line conductor will occupy under expected loading conditions is evaluated and plotted on template Template will also show the required minimum ground clearance by plotting a curve parallel to the conductor shape curve. For the standard tower and same height, the tower footing line can also be plotted on the template Tower footing line is used for locating the position of towers and minimum ground clearance is maintained throughout. Figure below shows the sag template used for locating towers. In fact there are no clear-cut guide lines for locating the tower positions and several other alternatives may be examined Ground clearance depends on the voltage level and in the table gives the span length and ground clearance at different voltage levels 61 62 Q? Thank you 63