Uploaded by brent

ActronAir SRA230 23 42 kW 1Stg 3Ph

advertisement
TECHNICAL SELECTION DATA
SRA230C / SRA230E
SPLIT DUCTED UNIT
3
THREE
PHASE
SCROLL
SINGLE
STAGE
LOUVRE
AXIAL FAN
UNIT FEATURES
•
•
•
•
•
•
•
•
Scroll Compressor
Multiple Speed Outdoor Fans
Louvred Outdoor Coil Guard
Pre-charged with R410A Refrigerant
Integral Fan Coil Safety Tray
Adaptive Demand Defrost
AM24 (24-Hour Wall Controller Supplied as Standard)
20 m Data Cable Included
SPECIFICATION SUMMARY
OUTDOOR UNIT MODEL
SRA230C
INDOOR UNIT MODEL
SRA230E
TOTAL*
23.42
22.45
SENSIBLE CAPACITY (kW) ***
19.56
18.59
HEATING CAPACITY (kW) ^
22.32
COOLING INPUT POWER (kW) ^^
CONTROL FEATURES
•
•
•
•
•
•
•
Auto, Heat & Cool Modes
Auto/Continuous Indoor Fan Operation
3 Speed Indoor Fan Setting
Hot Start Feature
Manual Control Inputs
24-Hour ON/OFF Timer
Home/Building Automation ON/OFF Capability
• AM7 (7-Day Programmable Controller with 2 Events/Day)
• Remote Temperature Sensors
• Zone Kit for Control up to 8 Zones
(See Control Section)
• Secondary Wall Controller with Mimic Logic
PLENUMS (Optional)
• Supply Air Plenums are Available in a 2 way or 3 way
Configuration (See Accessories Section for details of
Spigots availability)
• Return Air Plenums are Available with 2 x 450 mm Spigots
UNIT COMPLIANCE
23.50
7.21
HEATING INPUT POWER (kW) ^^
6.66
EER
3.25
3.11
COP
3.35
3.53
INDOOR AIRFLOW (l/s) - MIN. / NOMINAL / MAX. ^^^
1020 / 1200 / 1380
OUTDOOR SOUND PRESS. LEVEL @ 3M dB(A) - LOW / HIGH
OUTDOOR SOUND POWER LEVEL dB(A) -- LOW / HIGH
POWER SUPPLY - OUTDOOR
CONTROL OPTIONS
NETT**
COOLING CAPACITY (kW) ***
55.0 / 59.0
71.0 / 75.0
415V / 3Ph+N / 50Hz
POWER SUPPLY - INDOOR
240V / 1 Ph / 50 Hz
RATED LOAD AMPS -- OUTDOOR / INDOOR / TOTAL **
11.7 / 3.9 / 15.6
FULL LOAD AMPS -- OUTDOOR / INDOOR / TOTAL ^^^^
15.1 / 4.9 / 20.0
CIRCUIT BREAKER AND CABLE AMPS
25.0
APPROXIMATE STARTING AMPS
101.0
WEIGHT (kg) -- INDOOR / OUTDOOR
*
**
***
^
^^
^^^
^^^^
Note:
85.0 / 200.0
Based on unit rating excluding indoor fan kW.
Measured and tested in accordance with AS/NZS 3823.1.2.
At 270C DB / 190C WB entering air temperatures and 350C ambient.
At 200C DB entering air temperature and 70C DB / 60C WB ambient.
input power includes indoor fan kW.
Max. - Min. airflow application range.
Full Load Amps are based on compressor and fan motors’ maximum expected current.
See Specifications sheet for cable size and circuit breaker size details.
Use input power to estimate running cost.
• MEPS / QLD MP4.1 / SA MEPS
• Demand Response AS4755.3.1
R
®
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
®
SRA230C-0200 / SRA230E-0100 - P1 100927
23.42 kW
3 Phase 1 Stage
CENTRIFUGAL
FAN
CAPACITY SELECTION DATA
SRA230C / SRA230E
COOLING PERFORMANCE
AIR ENTERING
OUTDOOR INDOOR
WB - 0C
DB - 0C
25
30
3 Phase 1 Stage
23.42 kW
35
40
45
50
TOTAL
CAPACITY
kW
16
17
18
19
20
21
22
16
17
18
19
20
21
22
16
17
18
19
20
21
22
16
17
18
19
20
21
22
16
17
18
19
20
21
22
16
17
18
19
20
21
22
23.72
24.26
24.93
25.64
26.32
27.05
27.87
22.02
23.34
23.92
24.59
25.26
25.95
26.73
21.01
22.19
22.79
23.42
24.04
24.70
25.42
19.87
19.88
21.54
22.11
22.65
23.30
23.99
18.64
18.65
20.16
20.71
21.21
21.84
22.46
18.64
18.65
18.65
19.19
19.62
20.19
20.76
20
21
22
15.61
14.22
12.83
11.40
9.97
16.95
15.57
14.18
12.78
11.36
9.90
15.16
13.79
12.38
10.97
9.54
16.49
15.12
13.74
12.35
10.92
9.48
14.65
13.29
11.89
10.50
9.06
16.00
14.62
13.24
11.85
10.44
9.00
14.11
12.74
11.36
9.94
8.51
15.25
14.07
12.70
11.31
9.89
8.48
13.51
12.16
10.77
9.38
7.96
14.67
13.49
12.14
10.75
9.33
7.91
12.87
11.53
10.16
8.77
7.35
14.02
12.86
11.50
10.12
8.73
7.32
18.08
16.93
15.53
14.15
12.71
11.29
9.85
17.62
16.46
15.09
13.70
12.29
10.87
9.42
17.11
15.96
14.59
13.22
11.81
10.39
8.95
16.54
15.40
14.06
12.67
11.28
9.85
8.40
15.93
14.65
13.46
12.09
10.71
9.29
7.86
15.26
14.01
12.83
11.47
10.09
8.69
7.27
TOTAL SENSIBLE CAPACITY - kW
AT DB TEMPERATURE ONTO INDOOR COIL - 0C
23
24
25
26
27
19.36
18.05
16.88
15.49
14.10
12.68
11.22
18.89
17.60
16.42
15.06
13.67
12.23
10.81
18.39
17.10
15.93
14.56
13.17
11.76
10.34
17.80
16.52
15.39
14.01
12.62
11.21
9.79
17.18
15.90
14.63
13.44
12.06
10.66
9.26
16.47
15.26
13.99
12.81
11.45
10.05
8.63
20.58
19.35
18.23
16.82
15.43
14.03
12.60
20.13
18.89
17.54
16.38
15.01
13.59
12.19
19.57
18.36
17.06
15.90
14.51
13.11
11.70
18.97
17.79
16.49
15.34
13.97
12.57
11.18
18.27
17.17
15.89
14.76
13.40
12.02
10.60
17.45
16.48
15.24
13.97
12.77
11.40
10.00
28
29
30
22.93
21.79
20.53
19.20
18.05
16.65
23.88
22.94
21.77
20.49
19.13
17.98
24.05
22.97
21.73
20.45
19.32
24.08
22.96
21.71
20.36
22.42
21.33
20.08
18.78
17.61
16.22
22.45
21.32
20.04
18.72
17.54
23.46
22.50
21.29
20.00
18.64
23.57
22.49
21.23
19.93
20.77
19.59
18.31
17.17
15.78
14.39
21.70
20.78
19.56
18.27
17.13
15.74
21.88
20.80
19.52
18.20
17.06
21.94
20.77
19.50
18.16
22.92
21.95
20.73
19.43
20.13
19.01
17.74
16.43
15.24
13.87
20.18
19.00
17.71
16.58
15.20
21.18
20.20
18.95
17.67
16.52
21.28
20.19
18.92
17.62
21.35
20.15
18.88
18.32
17.16
15.88
14.73
13.35
11.97
18.38
17.15
15.85
14.69
13.32
19.45
18.38
17.10
15.81
14.64
19.51
18.35
17.07
15.77
20.43
19.55
18.31
17.05
20.60
19.55
18.30
17.55
16.48
15.23
14.09
12.73
11.36
17.64
16.48
15.20
14.04
12.69
17.68
16.45
15.17
14.01
18.70
17.66
16.43
15.15
18.79
17.65
16.39
18.84
17.63
21.79
20.61
19.32
18.15
16.77
15.37
13.96
21.28
20.14
18.84
17.71
16.35
14.94
13.54
20.72
19.61
18.33
17.01
15.85
14.45
13.06
19.95
19.01
17.77
16.46
15.30
13.92
12.52
22.82
21.80
20.57
19.24
18.08
16.71
15.32
22.21
21.33
20.11
18.79
17.65
16.29
14.90
HEATING PERFORMANCE
HEATING CAPACITY - kW
AT DB ENTERING INDOOR - 0C
WB TEMP
ON OD
COIL- 0C
-10
-8
-6
-4
-2
0
2
4
6
8
10
12
14
16
18
16
18
20
22
24
TH
IH
TH
IH
TH
IH
TH
IH
TH
IH
14.58
15.45
16.39
17.35
18.35
19.43
20.45
21.55
22.71
23.95
25.32
26.71
28.15
29.65
31.23
14.00
14.68
15.40
15.96
16.34
17.10
18.61
21.55
22.71
23.95
25.32
26.71
28.15
29.65
31.23
14.47
15.33
16.28
17.22
18.21
19.28
20.29
21.38
22.52
23.74
25.10
26.46
27.89
29.37
30.91
13.89
14.57
15.30
15.84
16.21
16.96
18.47
21.38
22.52
23.74
25.10
26.46
27.89
29.37
30.91
14.42
15.26
16.15
17.10
18.07
19.13
20.12
21.19
22.32
23.59
24.88
26.21
27.61
29.07
30.60
13.84
14.50
15.18
15.73
16.08
16.83
18.31
21.19
22.32
23.59
24.88
26.21
27.61
29.07
30.60
14.33
15.16
16.04
16.96
17.94
18.97
19.96
21.01
22.12
23.38
24.64
25.95
27.34
28.78
30.28
13.75
14.40
15.08
15.61
15.97
16.70
18.16
21.01
22.12
23.38
24.64
25.95
27.34
28.78
30.28
14.25
15.07
15.93
16.84
17.80
18.82
19.78
20.83
21.98
23.16
24.41
25.71
27.07
28.49
29.97
13.68
14.31
14.97
15.50
15.84
16.56
18.00
20.83
21.98
23.16
24.41
25.71
27.07
28.49
29.97
AIRFLOW CORRECTION MULTIPLIER
% VARIATION
INDOOR AIRFLOW (l/s)
TOTAL COOLING
SENSIBLE COOLING
HEATING FACTOR
-15%
1020
0.972
0.919
0.991
-10%
1080
0.982
0.947
0.994
-5%
1140
0.991
0.973
0.997
NOMINAL
1200
1.00
1.00
1.00
+5%
1260
1.008
1.027
1.002
+10%
1320
1.014
1.053
1.004
+15%
1380
1.021
1.077
1.006
TH - Total Heating Capacity (kW).
IH - Integrated Heating Capacity (kW)
Includes defrost losses.
NOTES:
1. No allowance has been made for the
effect of indoor fan motor.
2. Selection tables are based on nominal airflows.
Correction factors must be applied for selection
away from these conditions.
PIPE LENGTH CORRECTION MULTIPLIER
COOLING
HEATING
5m
1.000
1.000
10m
0.997
1.000
20m
0.990
1.000
30m
0.983
1.000
40m
0.975
1.000
50m
0.968
1.000
60m
0.961
1.000
Correction multipliers are based on horizontal pipe runs.
R
®
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
®
SRA230C-0200 / SRA230E-0100 - P2 090914
DIMENSIONS AND FAN CURVE
SRA230C / SRA230E
1685 O/A
OUTDOOR UNIT
SRA230C
FAN
FAN
Refer Pipe
Pipe Connection
Connection Details
Refer
to Specifi
Specifications
on
cations Sheet
685
O/A
CONDENSER
AIR INLET
CONDENSER COIL
CONDENSER
AIR OUTLET
50
ELEC. ACCESS
2 x 25mm
50
GAS PIPE
22.2mm
LIQUID PIPE
12.7mm
CONDENSER
AIR INLET
1125
O/A
1025
670
80
1190
50
666
118 110
555.5
NOTES:
1. OPTIONAL ANTI-CORROSIVE ACRYLIC
COATED COIL AVAILABLE ON ALL UNITS.
2. DO NOT SCALE DRAWING.
120
EVAPORATOR COIL
645
EVAP
FAN
338
Supply Duct Connection H x W = 380 x 715.
Return Duct Connection H x W = 410 x 1190.
Drain Connection 25mm ID.
All Dimensions in mm.
EVAP
FAN
715
338
695 O/A
1470 O/A
40
35
605
50
25
ACCESS PANEL
SUPPLY
AIR
SUPPLY AIR
485
O/A
RETURN
AIR
ELEC.
BOX
380
410
70
SAFETY TRAY
DRAIN 25mm
1425
50
GAS PIPE
25.4mm
CONDENSATE
DRAIN 25mm
INDOOR UNIT
FAN CURVE
LIQUID PIPE
12.7mm
350
EXTERNAL STATIC
PRESSURE (Pa)
300
250
200
15 0
10 0
50
0
700
800
AIRFLOW (l/s)
900
10 0 0
110 0
12 0 0
13 0 0
14 0 0
15 0 0
16 0 0
APPLICATION RANGE
R
®
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
®
SRA230C-0200 / SRA230E-0100 - P3 090623
23.42 kW
INDOOR UNIT
SRA230E
118
555.5
3 Phase 1 Stage
110 118
SOUND DATA
SRA230C / SRA230E
Outdoor Radiated
Sound Power
Level (SWL)
Fan
Speed
Octave Band Centre Frequency (Hz), dB
Sound Power Level
dB(A)
125
250
500
1k
2k
4k
8k
Low
71.0
72.2
70.7
67.6
66.8
62.7
55.4
49.7
High
75.0
76.5
74.2
71.8
69.5
67.9
62.6
56.4
Sound Power
Level (SWL)
Airflow
Setting
Airflow
Li/s
Nominal
Sound
Power Level
dB(A)
125
250
500
1k
2k
4k
8k
77.5
75.4
76.1
75.1
72.6
69.1
65.1
60.1
1200
Octave Band Centre Frequency (Hz), dB
OUTDOOR RADIATED
INDOOR OUTLET
SRA230C Sound Power Level
SRA230E Sound Power Level
80.0
Octave Band Sound Power Level (dB)
80.0
Octave Band Sound Power Level (dB)
3 Phase 1 Stage
23.42 kW
Indoor Outlet
70.0
60.0
50.0
70.0
60.0
50.0
Low
Nominal
High
40.0
40.0
125
250
500
1k
2k
4k
8k
Octave Band Centre Frequency (Hz)
125
250
500
1k
2k
4k
8k
Octave Band Centre Frequency (Hz)
NOTES:
1.
Radiated sound power levels are based on ISO 3743-2.
2.
Outlet sound power levels are based on ISO 13347-2.
R
®
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
®
SRA230C-0200 / SRA230E-0100 - P4 100302
SRA230C / SRA230E
SPECIFICATIONS
CONSTRUCTION
COMPRESSOR
CABINET (Indoor Unit)
0.5 - 1.2 mm Galvanized Steel
NUMBER PER UNIT x TYPE
1 x Scroll (Hermetic)
CABINET (Outdoor Unit)
1.2 mm ZA & Galvanized Steel
FULL LOAD AMPS
13.5
SURFACE FINISH (Outdoor Unit)
65 μ Baked Polyester Powder Coat
LOCKED ROTOR AMPS
101.0
STARTING METHOD
D.O.L. (optional soft starter)
INSULATION (Indoor Unit)
TYPE
10 mm Foil Faced Polyethylene
REFRIGERATION SYSTEM
12 mm Expanded Polystyrene
REFRIGERANT TYPE
R-410A
EXPANSION CONTROL
Direct Expansion Orifice
ELECTRICAL
OUTDOOR UNIT
Power Supply - 50 Hz
415 Volts x 3 Phase + N
Voltage Range (min - max)
400 V - 440 V
FACTORY CHARGE (grams)
7900.0
PRE-CHARGE LENGTH (metres)
10.0
ADDITIONAL REF. CHARGE (gm/m)
100.0
Full Load Amps*
15.1
FILTER DRIER
Rated Load Amps**
11.7
CONNECTION SIZE & TYPE
12.7 mm (1/2”) ODF Soldered Bi-Flow
Approximate Starting Amps
101.0
FACTORY SUPPLIED / FITTED
No
IP Rating
IP44
INDOOR UNIT
Voltage Range (min - max)
220 V - 260 V
Full Load Amps*
4.9
IP Rating
IP20
OUTDOOR & INDOOR UNIT (TOTAL)
Full Load Amps* - Phase 1
20.0
Full Load Amps* - Phase 2 & 3
13.2 & 13.9
Rated Load Amps**
15.6
INTERCONNECTING PIPE RUN
MAX PIPE LENGTH (metres)
60.0
MAX. VERTICAL LENGTH (metres)
20.0 (Included in Max. Pipe Length)
FIELD PIPE SIZES
Liquid Pipe
12.7 mm (1/2”)
Gas Pipe
25.4 mm (1”)
PIPE CONNECTIONS
Indoor
IMPORTANT - The local electricity authority may require limits on starting current and
voltage drop, please check prior to purchase.
*
Full Load Amps are based on Compressor and Fan Motor’s maximum expected current.
Outdoor
Liquid Pipe
12.7 mm (1/2”) Swaged to fit
12.7 mm (1/2”) field pipe
Gas Pipe
25.4 mm (1”) To be swaged in field
to fit 25.4 mm (1”) field pipe
Liquid Pipe
12.7 mm (1/2”) Swaged to fit
12.7 mm (1/2”) field pipe
Gas Pipe
22.2 mm (7/8”) Swaged to fit
25.4 mm (1”) field pipe
** Rated Load Amps are measured and tested in accordance with AS/NZS3823.1.2.
CABLE SIZE & CIRCUIT BREAKER SIZE
Suggested minimum cable size should be used as a guide only, refer to AS/NZS 3000
“Australian/New Zealand Wiring Rules” for more details.
Cable Size (main line)
4.0 mm2 (SUGGESTED MINIMUM)
Cable Size (indoor to outdoor wire)
1.0 mm2 (SUGGESTED MINIMUM)
Circuit Breaker Size
25.0 Amps
OUTDOOR COIL
CONNECTION TYPE
Solder
Insulate both gas and liquid pipes separately.
PROTECTION DEVICES
HIGH PRESSURE CUTOUT SWITCH Nonadjustable (Automatic Reset)
LOW PRESSURE CUTOUT SWITCH
Nonadjustable (Automatic Reset)
TUBE TYPE
FIN TYPE
Copper - Rifle Bore
Aluminium - Wave
COMPRESSOR MOTOR TEMP.
Internal Thermal Cut-Out
INDOOR FAN OVERLOAD
Internal Thermal Cut-Out
FACE AREA (m sqr)
1.98
OUTDOOR FAN OVERLOAD
Internal Thermal Cut-Out
FIN SPACING (per m)
630
SUMP HEATER WATTS
30 W during Compressor Off Cycle
ROWS
---
OUTDOOR FAN
ELECTRIC CONTROLS
DEFROST METHOD
Reverse Cycle
NUMBER OF FANS x TYPE
2 x Axial
DEFROST TYPE
Adaptive Demand Defrost
NUMBER OF BLADES PER FAN
5
CONTROL CIRCUIT BREAKER
16.0 Amps
DIAMETER (mm)
500
CONTROL FIELD WIRING
2 Core 14 / 0.20 Screened Cable
OUTPUT kW
0.19
MOTOR TYPE / DRIVE TYPE
6 Pole External Rotor / Direct
FAN SPEED CONTROL
2 Speed via Capacitor
The standard type outdoor fans fitted to this unit will only accept 5Pa of external static
resistance.
OPERATING RANGE
It is essential that the unit is correctly sized for the application and operates within its
recommended range of operating conditions as shown below.
MODE
INDOOR
AIR INTAKE
TEMPERATURE
OUTDOOR
AIR INTAKE
TEMPERATURE
Max.
29oC DB / 19oC WB
50oC DB
Min.
20oC DB / 15oC WB
RANGE
INDOOR COIL
TUBE TYPE
FIN TYPE
FACE ARE (m sqr)
FIN SPACING (per m)
ROWS
Copper - Rifle Bore
Aluminium - Louvre
0.56
DIAMETER / WIDTH (mm)
Heating
590
---
INDOOR FAN
NUMBER OF FANS x TYPE
Cooling
1 x Twin Deck Centrifugal
240 x 180
OUTPUT kW / INPUT kW
0.75 / 0.97
MOTOR TYPE / DRIVE TYPE
3 Speed 4 Pole / Direct
o
15oC DB
o
Max.
24 C DB
21 C DB / 16oC WB
Min.
16oC DB
-10oC DB
IMPORTANT - For low ambient cooling use option S. Lower ambient available
on request. Contact your nearest ActronAir office for more details.
Low
Ambient
Cooling
Option S
On
Request
Max.
29oC DB / 19oC WB
50oC DB
Min.
20oC DB / 15oC WB
5oC DB
o
o
Max.
29 C DB / 19 C WB
50oC DB
Min.
20oC DB / 15oC WB
-5oC DB
AIR FILTERS
All return air including fresh air must have adequate filters supplied and fitted by the
installing contractor. Filters must be located in accessible location between the
return air grille and the unit.ActronAir ® does not supply or make any provisions for return air filter.
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
®
R
®
SRA230C-0200 / SRA230E-0100 - P5 100927
23.42 kW
240 Volts x 1 Phase
3 Phase 1 Stage
Power Supply - 50 Hz
See Installation Section for complete Filter Drier specifications.
GREY
CONDENSER WIRING
BROWN
8 uF
RUN CAPACITOR
GREY
LOW SPD.
CAPACITOR
30 uF
SRA230C
30 uF
SRA260C
FIELD WIRING FOR
M SERIES ONLY
NC NO
ZONE 2
NC NO
ZONE 3
NC NO
ZONE 4
OPTIONAL ZONE CARD (AMZ)
NC NO
ZONE 1
RLY
SENSOR
KEY
POWER
COM
NEUT
NEUT
COM
EARTH
OPTIONAL
SENSOR 2
POWER
KEY
SENSOR
DO NOT
CONNECT
SCREEN AT
WALL CONTROL
OPTIONAL
SENSOR 1
DESIGNS AND SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
BLUE
ACT
NEUT
240V OUTPUT
SCRN
CONDENSER FAN
NEUT
INDOOR BOARD
(AMIB-P)
240V OUTPUT
240V OUTPUT
HIGH
WITH TRACE WIRE CONNECTED TO THE SCREEN / COMMON TERMINAL
COM
INTERNAL AUTO RESET
OVERLOAD PROTECTION
LOW SPEED CAP.
BLACK
SUMP HEATER
CABLE MUST BE 2 CORE 14/0.20 SCREENED CABLE
NEUT
MID
COM
GREY
INDOOR FAN
SENSOR WIRING
DATA
16 AMP CONTROL
NEUT
ACT
HIGH
NEUT
NOTICE:
CIRCUIT BREAKER
AUX.
240V
VOLT
FAN
EARTH
INTERNAL AUTO RESET
OVERLOAD PROTECTION
OPTIONAL
REMOTE ON/OFF
SWITCH
EARTH
8 uF
RUN CAPACITOR
HIGH
3 Phase 1 Stage
COOL ONLY ON
15V
NEUT
GREY
NEUT
CAPACITOR
INTERNAL AUTO RESET
OVERLOAD PROTECTION
BLUE
NEUT
NEUT
07/05/2009
SRA260C
SRA230C
COMPRESSOR C1
CONTACTOR C1
NEUT
CONDENSER FAN
20K OHM
RESISTOR
ALL M SERIES CONTROLS AM24
& AM7 SET TO STANDARD
NEUT
USED FOR
REMOTE ON/OFF
OPERATION
(WALL CONTROL
USE ONLY)
DATA
COM/
SCREEN
PWR
A
BROWN
HP SWITCH
STAGE-2 ON
BOOST HEAT ON
WALL CONTROL
CONT. FAN
SINGLE SPEED
INDOOR FAN
EARTH
EXTRA LOW VOLTAGE
ELECTRONIC
WALL CONTROL
ACT
BLACK
HP
DUAL SPEED
INDOOR FAN
AUTO. FAN
MANUAL INPUTS
STANDARD
DIP SWITCH
SETTINGS
ACT
23.42 kW
NEUT
CONDENSER CPU BOARD
REV
OUTDOOR
COIL
SENSOR
KEY
LP SWITCH
COMP
WD0519
REV. DATE
DRAWING NUMBER
REV.
This drawing remains the intellectual property of Actron Engineering Pty Ltd.
Reproduction, modification and/or distribution are prohibited without written consent.
INTERNAL AUTO RESET
OVERLOAD PROTECTION
REVERSING VALVE
HP
ACT-D4 CONTROL SYSTEM WIRING DIAGRAM WITH
M-SERIES INDOOR BOARD
R
COMP. CONTACTOR
VARIATION
G
SRA230C
OUTDOOR UNIT - HI STATIC TOP DISCHARGE FANS
SRA230C-G
1685 O/A
685
O/A
CONDENSER
AIR INLET
CONDENSER COIL
340
172
340
50
1115
O/A
670
110 118
555.5
118
555.5
118 110
CONDENSER
AIR OUTLET
300
57.5
40
ELEC. ACCESS
2 x 25.4mm
Cond. Duct Connection L x W = 2 x (300 x 340)
All Dimensions in mm.
GAS PIPE
28.6mm
CONDENSER
AIR INLET
LIQUID PIPE
12.7mm
666
1025
50
NOTES:
1. OPTIONAL ANTI-CORROSIVE ACRYLIC COATED COIL AVAILABLE ON ALL UNITS.
2. REFER PIPE CONNECTION DETAILS ON SPECIFICATIONS SHEET.
3. DO NOT SCALE DRAWING.
4. ENSURE SUFFICIENT ACCESS IS AVAILABLE TO SERVICE FANS WHEN INSTALLING DUCTING ON AIR OUTLETS.
R
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
®
SRA230C-G -0200 - P7 090623
23.42 kW
250
3 Phase 1 Stage
CONDENSER
AIR INLET
VARIATION
H
SRA230C
OUTDOOR UNIT - HORIZONTAL DISCHARGE FANS 5 Pa
SRA230C-H
CONDENSER
AIR INLET
CONDENSER COIL
CONDENSER
AIR INLET
735
O/A
3 Phase 1 Stage
23.42 kW
1685 O/A
435
395
50
FAN
365 1075
O/A
530
FAN
670
377.5
110 118
555.5
685
118
555.5
118 110
50
ELEC. ACCESS
2 x 25.4mm
GAS PIPE
28.6mm
CONDENSER
AIR INLET
LIQUID PIPE
12.7mm
666
CONDENSER
AIR OUTLET
1025
50
NOTES:
1. OPTIONAL ANTI-CORROSIVE ACRYLIC COATED COIL AVAILABLE ON ALL UNITS.
2. REFER PIPE CONNECTION DETAILS ON SPECIFICATIONS SHEET.
3. DO NOT SCALE DRAWING.
R
®
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
®
SRA230C-H -0200 - P8 090623
VARIATION
SRA230E
V UPRIGHT FAN COIL VERTICAL DISCHARGE
1435 O/A
SRA230E-V
LIQUID PIPE
12.7mm
GAS PIPE
25.4mm
Supply Duct Connection H x W = 380 x 715
Return Duct Opening Size H x W = 445 x 1205
Drain Connection 25mm ID.
All Dimensions in mm.
485
O/A
FAN
INDOOR COIL
100
1205
715
330
SUPPLY
AIR
70
330
40
35
380
70
525
1065
O/A
445
RETURN
AIR
100 115
415
115
415
55
115 100
CONDENSATE
DRAIN 25mm
H UPRIGHT FAN COIL HORIZONTAL DISCHARGE
1435 O/A
SRA230E-H
LIQUID PIPE
12.7mm
FAN
GAS PIPE
25.4mm
COIL
100
1205
330
Supply Duct Connection H x W = 380 x 715
Return Duct Opening Size H x W = 445 x 1205
Drain Connection 25mm ID.
All Dimensions in mm.
525
O/A
70
715
485
330
40
35
FAN
ELEC.
BOX
380
525
SUPPLY
AIR
1025
O/A
610
445
100 115
415
115
415
115 100
RETURN
AIR
55
CONDENSATE
DRAIN 25mm
NOTES:
1. OPTIONAL ANTI-CORROSIVE ACRYLIC COATED COIL
AVAILABLE ON ALL UNITS.
2. REFER PIPE CONNECTION DETAILS ON SPECIFICATIONS SHEET.
3. DO NOT SCALE DRAWING.
ActronAir is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice. Please check prior to purchase.
®
R
®
SRA230E-V/H -0100 - P9 090623
23.42 kW
3 Phase 1 Stage
FAN
ELEC.
BOX
Download