INSTALLATION, OPERATION & MAINTENANCE MANUAL AIR COOLED CONDENSING UNITS 'CNX' SERIES PL-OM-CNX-07-1M-E Downloaded from www.Manualslib.com manuals search engine INDEX Contents Page Model decoding ....................................................................................................................................... 2 Physical data ......................................................................................................................................... 3-4 Electrical data ........................................................................................................................................... 5 Dimensions .......................................................................................................................................... 6-13 Microprocessor control system ............................................................................................................... 14 User sequence of operation ................................................................................................................... 15 Typical schematic wiring diagram ...................................................................................................... 16-23 Field wiring connections ......................................................................................................................... 24 Rigging instructions & weight distribution ............................................................................................... 25 Load distribution ..................................................................................................................................... 26 INSTALLATION INSTRUCTIONS General ................................................................................................................................................... 27 Location of unit ....................................................................................................................................... 27 General ................................................................................................................................................... 27 Refrigerant piping connections ............................................................................................................... 27 Leak testing & refrigerant charging ......................................................................................................... 28 Start-up inspection & check list ......................................................................................................... 28-29 Check-out & operational start-up procedure ........................................................................................... 29 ELECTRICAL Power supply .......................................................................................................................................... 30 Unbalanced voltage ................................................................................................................................ 30 Motor contactor ...................................................................................................................................... 31 Fan motor ............................................................................................................................................... 31 Crankcase heater ................................................................................................................................... 31 Lube oil protection control ...................................................................................................................... 31 Voltage monitor ...................................................................................................................................... 31 REFRIGERATION Compressor ............................................................................................................................................ 32 High & low pressure protection .......................................................................................................... 33-34 Pump down control ................................................................................................................................. 34 Trouble shooting chart ....................................................................................................................... 35-37 Parts list ................................................................................................................................................. 38 Recommended spare parts .................................................................................................................... 39 Preventive maintenance schedule .......................................................................................................... 40 Material safety data sheet ...................................................................................................................... 41 Pressure temperature chart ............................................................................................................... 42-43 CONTINUING RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE. 1 Downloaded from www.Manualslib.com manuals search engine MODEL DECODING 1, 2 & 3 BASIC 4, 5 & 6 NOMINAL COOLING CAPACITY* (MBH) CNX 150 CONDENSING UNIT 220 7 ELECTRICAL SUPPLY ( V-Ph-Hz ) F : 460-3-60 8 SPECIAL OPTIONS 9 MANUFACTURING YEAR 10 GENERATION CODE Z :SPECIAL OPTIONS 06 00 07 01 08 02 240 300 360 03 420 480 540 600 720 840 **M00 **M10 **M20 **M40 **M60 ***2M00 ***2M40 * Capacity in MBH (MBH x 1000 = BTUH). ** M indicates for 1 Million BTUH. *** 2M indicates for 2 Million BTUH. 2 Downloaded from www.Manualslib.com manuals search engine PHYSICAL DATA MODEL NUMBER NOMINAL CAPACITY , TONS* NUMBER OF REFRIGERATION CIRCUIT COMPRESSOR CNX150 CNX220 13 19 22 28 31 36 41 47 53 Dual Dual Dual Dual Dual Dual Dual Dual Dual Type Oil per system (liters) CNX240 CNX300 CNX360 Scroll 4.1 4.1 4.1 CONDENSER FAN 4.7 4.68 Nominal CFM Motor kW – RPM CONDENSER COIL 4.68 4.94 4.94 4.94 650 750 850 945 R-134a 235 330 400 504 Type Qty. – Diameter (mm) CNX540 CNX600 Semi-hermetic reciprocating Refrigerant Charge per system (oz)** CNX420 CNX480 570 Propeller 2 – 560 2 – 630 2 – 700 2 – 700 3 – 700 3 – 700 4 – 700 4 – 700 4 – 700 8400 10000 15000 15000 22500 22500 30000 30000 30000 0.66–1010 0.86–1020 1.45–1000 1.45–1000 1.45–1000 1.45–1000 1.45–1000 1.45–1000 1.45–1000 Type Inner grooved tubes and enhanced fins Tube Dia–Rows–Fins per inch 3/8–3–14 3/8–4–14 3/8–4–14 3/8–4–14 3/8–3–14 3/8–4–14 3/8–4–14 3/8–4–14 3/8–5–14 Total face area (Sq. ft.) HIGH PRESSURE SWITCH LOW PRESSURE SWITCH 28 28 28 28 46.66 46.66 56 56 56 Open (PSIG) 350 ± 10 350 ± 10 350 ± 10 350 ± 10 350 ± 10 350 ± 10 350 ± 10 350 ± 10 350 ± 10 Close (PSIG) 300 ± 10 300 ± 10 300 ± 10 300 ± 10 300 ± 10 300 ± 10 300 ± 10 300 ± 10 300 ± 10 Open (PSIG) 10 ± 5 10 ± 5 10 ± 5 10 ± 5 10 ± 5 10 ± 5 10 ± 5 10 ± 5 10 ± 5 Close (PSIG) 30 ± 5 30 ± 5 30 ± 5 30 ± 5 30 ± 5 30 ± 5 30 ± 5 30 ± 5 30 ± 5 1-3/8 1-5/8 1-5/8 1-5/8 1-5/8 1-5/8 2-1/8 2-1/8 2-1/8 5/8 7/8 7/8 7/8 7/8 1-1/8 1-1/8 1-1/8 1-1/8 69/65/60 69/65/60 800 925 REFRIGERANT LINES+ Suction line size (OD), inch Liquid line size (OD), inch SOUND PRESSURE LEVEL, dBA (@ 3/5/10 meter)++ OPERATING WEIGHT, Kg. 69.3/65.8/60.5 69.7/66.1/60.9 69.8/66.3/61 980 1060 1325 72.9/69.3/64.1 72.8/69.3/64 1400 1525 NOTE: * Nominal cooling capacity @ 950F outdoor and 450F saturated suction temperatures. ** Operating system charge is applicable when matched with air handling units & connected by 25 feet of refrigerant piping. + Pipe sizes are for runs up to 50 feet to indoor unit. For refrigerant lines longer than 50 feet, use next larger size. ++ Based on free field area at ARI conditions. Tolerance: ±2dBA. 3 Downloaded from www.Manualslib.com manuals search engine 72.9/69.3/64.1 73.3/69.8/64.5 1600 1675 PHYSICAL DATA MODEL NUMBER NOMINAL CAPACITY , TONS* NUMBER OF REFRIGERATION CIRCUIT COMPRESSOR CNX720 CNX840 CNXM00 CNXM10 CNXM20 CNXM40 CNXM60 CNX2M00 CNX2M40 63 64 75 92 Dual Dual Dual Dual Type 105 4.94 4.94 5.2 5.2 154 281 Quadruple Quadruple Quadruple Quadruple Quadruple 4.94 Refrigerant Screw 4.94 5.2 5.2 22 1090 1250 1390 2520 R-134a Charge per system (oz)** 1125 1145 1350 Type 1660 945 Propeller Qty. – Diameter (mm) 6 – 700 6 – 700 6 – 800 6 – 800 6 – 800 8 – 800 8 – 800 10 – 800 16 – 800 Nominal CFM 45000 45000 73266 73266 69000 93256 87032 108790 192048 2.15–970 2.15–970 2.15–970 2.15–970 2.15–970 2.15–970 2.15–970 Motor kW – RPM CONDENSER COIL 139 Semi-hermetic reciprocating Oil per system (liters) CONDENSER FAN 121 1.45–1000 1.45–1000 Type Inner grooved tubes and enhanced fins Tube Dia–Rows–Fins per inch 3/8–4–14 3/8–5–14 3/8–3–14 3/8–3–14 3/8–4–14 3/8–3–14 3/8–3–14 3/8–4–14 3/8–3–14 Total face area (Sq. ft.) HIGH PRESSURE SWITCH LOW PRESSURE SWITCH 70 70 120 120 120 140 140 175 304 Open (PSIG) 350 ± 10 350 ± 10 350 ± 10 350 ± 10 350 ± 10 350 ± 10 350 ± 10 350 ± 10 350 ± 10 Close (PSIG) 300 ± 10 300 ± 10 300 ± 10 300 ± 10 300 ± 10 300 ± 10 300 ± 10 300 ± 10 300 ± 10 Open (PSIG) 10 ± 5 10 ± 5 10 ± 5 10 ± 5 10 ± 5 10 ± 5 10 ± 5 10 ± 5 10 ± 5 Close (PSIG) 30 ± 5 30 ± 5 30 ± 5 30 ± 5 30 ± 5 30 ± 5 30 ± 5 30 ± 5 30 ± 5 2-1/8 2-1/8 2-5/8 2-5/8 N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. N.A. 2-1/8 2-1/8 2-5/8 2-5/8 3-1/8 Dual 1-1/8 1-1/8 1-3/8 1-3/8 N.A. N.A. N.A. N.A. N.A. Quadruple N.A. N.A. N.A. N.A. 1-1/8 1-1/8 1-1/8 1-1/8 1-3/8 REFRIGERANT LINES+ Suction line size Dual (OD), inch Quadruple Liquid line size (OD), inch SOUND PRESSURE LEVEL, dBA (@ 3/5/10 meter)++ 73.3/69.8/64.5 73.3/69.8/64.5 OPERATING WEIGHT, Kg. 2100 2600 74.7/1.2/66 3500 75.7/72.7/66.9 76.2/72.7/67.4 77.1/73.6/68.3 77.7/74.2/69 3700 4250 4700 5600 NOTE: * Nominal cooling capacity @ 950F outdoor and 450F saturated suction temperatures. ** Operating system charge is applicable when matched with air handling units & connected by 25 feet of refrigerant piping. + Pipe sizes are for runs up to 50 feet to indoor unit. For refrigerant lines longer than 50 feet, use next larger size. ++ Based on free field area at ARI conditions. Tolerance: ±2dBA. 4 Downloaded from www.Manualslib.com manuals search engine 78.1/74.6/69.3 81.4/77.9/72.6 5095 8500 ELECTRICAL DATA SUPPLY VOLTAGE UNIT SIZE COMPRESSOR MOTOR Nominal (V-Ph-Hz) Min. Max. MCA MOCP Qty. CNX 150 460-3-60 414 506 25.7 35 CNX 220 460-3-60 414 506 39.0 CNX 240 460-3-60 414 506 CNX 300 460-3-60 414 CNX 360 460-3-60 CNX 420 RLA LRA (each) (each) 2 11.4 125 50 2 15.9 45.7 60 2 506 56.1 75 414 506 60.6 460-3-60 414 506 CNX 480 460-3-60 414 CNX 540 460-3-60 CNX 600 CONDENSER FAN MOTORS FLA LRA (each) (each) 0.66 1.0 2.4 2 158 0.86 1.6 4.1 2 18.1 187 1.45 2.5 10.0 2 2 22.7 225 1.45 2.5 10.0 2 80 2 23.6 193 1.45 2.5 10.0 3 70.5 90 2 28.0 220 1.45 2.5 10.0 3 506 77.5 100 2 30.0 262 1.45 2.5 10.0 4 414 506 91.0 125 2 36.0 262 1.45 2.5 10.0 4 460-3-60 414 506 108.8 150 2 43.9 323 1.45 2.5 10.0 4 CNX 720 460-3-60 414 506 147.1 200 2 58.7 404 1.45 2.5 10.0 6 CNX 840 460-3-60 414 506 147.1 200 2 58.7 404 1.45 2.5 10.0 6 CNX M00 460-3-60 414 506 183.5 250 2 72.5 513 2.15 3.4 10.0 6 CNX M10 460-3-60 414 506 207.6 275 2 83.2 590 2.15 3.4 10.0 6 CNX M20 460-3-60 414 506 207.0 250 4 43.9 323 2.15 3.4 10.0 6 CNX M40 460-3-60 414 506 276.7 325 4 58.7 404 2.15 3.4 10.0 8 CNX M60 460-3-60 414 506 335.3 400 4 72.5 513 2.15 3.4 10.0 8 CNX 2M00 460-3-60 414 506 342.1 400 4 72.5 513 2.15 3.4 10.0 10 CNX 2M40 460-3-60 414 506 548.6 650 4 117.4 801 2.15 3.1 10.0 16 LEGEND: MCA MOCP RLA LRA kW FLA - Minimum Circuit Ampacity Maximum Over Current Protection Rated Load Amps Locked Rotor Amps Kilowatt Full Load Amps 5 Downloaded from www.Manualslib.com manuals search engine kW Qty. DIMENSIONS CNX 150 - CNX 300 1 2 3 4 5 6 7 5 CNX 360 - CNX 420 1 2 3 4 5 6 1550 [61.0] 203 [8.0] 7 73 [2.875] 2121 [83.50] 2197 [86.50] NOTES: 1. All dimensions are in mm, (dimensions in brackets are in inches). 2. Allow 48" (1219 mm) clearance on all sides for proper airflow. 6 Downloaded from www.Manualslib.com manuals search engine "A" 943 [37.125] "B" 2032 [80.0] 943 [37.125] "C" DIMENSIONS 357.5 [14.07] TYP 335.4 [13.20] 2121 [83.50] 2197 [86.50] CNX 720 - CNX 840 TOP VIEW 73 [2.875] "C" 968 (38.11") SIDE VIEW FRONT VIEW NOTES: 1. All dimensions are in mm, (dimensions in brackets are in inches). 2. Allow 48" (1219 mm) clearance on all sides for proper airflow. 7 Downloaded from www.Manualslib.com manuals search engine "B" 965 (37.99") 968 (38.11") 375.6 [14.80] 1550 [61.0] 203 [8.0] 255.0 [10.00] TYP CNX 480 - CNX 600 8 Downloaded from www.Manualslib.com manuals search engine NOTES: 1. All dimensions are in mm, (dimensions in brackets are in inches). 2. Allow 48" (1219 mm) clearance on all sides for proper airflow. CNX M00 - CNX M10 DIMENSIONS 9 Downloaded from www.Manualslib.com manuals search engine NOTES: 1. All dimensions are in mm, (dimensions in brackets are in inches). 2. Allow 48" (1219 mm) clearance on all sides for proper airflow. CNX M20 DIMENSIONS 10 Downloaded from www.Manualslib.com manuals search engine NOTES: 1. All dimensions are in mm, (dimensions in brackets are in inches). 2. Allow 48" (1219 mm) clearance on all sides for proper airflow. ELECTRIC POWER INLET CNX M40 DIMENSIONS 917.0 [36.102] TYP 786.0 [30.944] TYP 670.5 [26.397] TYP 487.0 [19.173] TYP 285.0 [11.220] 11 Downloaded from www.Manualslib.com manuals search engine NOTES: 1. All dimensions are in mm, (dimensions in brackets are in inches). 2. Allow 48" (1219 mm) clearance on all sides for proper airflow. ELECTRIC POWER INLET CNX M60 DIMENSIONS 917.0 [36.102] TYP 786.0 [30.944] TYP 670.5 [26.397] TYP 487.0 [19.173] TYP 285.0 [11.220] 12 Downloaded from www.Manualslib.com manuals search engine NOTES: 1. All dimensions are in mm, (dimensions in brackets are in inches). 2. Allow 48" (1219 mm) clearance on all sides for proper airflow. CNX 2M00 DIMENSIONS 13 Downloaded from www.Manualslib.com manuals search engine 275 [10.826] NOTES: 1. All dimensions are in mm, (dimensions in brackets are in inches). 2. Allow 48" (1219 mm) clearance on all sides for proper airflow. CNX 2M40 DIMENSIONS 2185 [86.023] 917.0 [36.102] TYP 786.0 [30.944] TYP 670.5 [26.397] TYP 487.0 [19.173] TYP 285.0 [11.220] 2200 [86.614] MICROPROCESSOR CONTROL SYSTEM Each condensing unit are provided with microprocessor based control board that monitors analog and digital inputs to achieve precise control and safety functions during unit’s operation. Input signals for cooling control can be digital signals coming from a thermostat device or analog signals from a PTC temperature sensor. The push button key board allows accessing to the operating conditions, control set points (in case temperature control is analog signal), & alarm history that are clearly displayed on a multi-line back illuminated LCD panel. The unit’s controller consists of the following hardware: 1. User Interface Board – Includes push buttons to access operating conditions, change control set points, and view alarm history. Data are clearly displayed on its LCD panel. 2. Main Board – This controls up to 2 compressor system. 3. Auxiliary Boards – Required for controlling an additional (2) or more compressors. LCD Display Information: In the normal operating mode, the 20 x 4 characters LCD panel displays the system status, temperature of leaving / returning air and set point (if temperature control selected is through PTC sensors ), run time of compressor and alarm history. Measurement data for each circuit can be easily accessed and displayed on the LCD. Data include the following: - Suction, Discharge, and Oil pressures - Leaving / Returning Air temperature ( if temperature control selected is through PTC sensors ) - Compressor Motor Status - Condenser Fan Motor Status - Liquid Line Solenoid Status - Supply Fan Motor Status There are three LED lights on the user interface board to indicate “Power On” (green), “Menu Adjustment” (yellow) and “Fault” (red). SYSTEM PROTECTION The unit is equipped with protective devices against motor overloads and proper system settings are factory set to ensure safe and reliable operation of the unit. Some of these devices and settings are as follows: - Compressor Motor External Overload Relay - Compressor Motor Winding Over Temperature Protection - Low suction Pressure - High Discharge Pressure - Low Oil Pressure - Compressor Anti-Recycling Timer 14 Downloaded from www.Manualslib.com manuals search engine USER SEQUENCE OF OPERATION On/Off SET Menu CLASSIC AIR CONDITIONERS TOUT = 10°C TIN = 15°C COOLING 75% Esc Machine Starting: - If OFF, the machine is started by pushing the ON/OFF button. - The ON LED (green) will lit. - On the main screen is showed the status “STARTING”. - After 15 seconds of delay the system will be running. Machine Shut-Down: - The machine is halted pushing again the ON/OFF key. - The ON LED (green) is switched off. - On the main screen is showed the status “STOPPING”. - All the compressors are stopped. - Blower motor will be switched off after pre-set delay timing when all compressors are switched off. - On the main screen is showed the status “SYSTEM OFF”. Set Point Change: - Press “SET”, the LCD will ask the password input. - Using the “UP” and “DOWN” keys input the correct password. - Press “SET”, the “MODIFY” word appears to allow the parameter to be changed. The LCD will show the actual value. - Using the “UP” and “DOWN” keys modify the set point value. - Press “SET” to store it or “ESC” to exit without memorizing. COMPRESSOR CONTROL Control setting to switch on / off the compressors is through digital output signals from an external controller fed to the micro-processor board. When the system is started up, the software starts to check all the necessary inputs to start the unit. It scans the digital/analogue inputs. If any unwarranted interruption occurred the alarm signal is generated and the compressor will be shut-off. BLOWER MOTOR CONTROL (OPTIONAL) Control setting to switch on / off the blower motor is through digital output signal from an external controller fed to the micro-processor board. The system’s control will prevent the compressors to operate if this signal is not fed to the microprocessor board. 15 Downloaded from www.Manualslib.com manuals search engine SCHEMATIC WIRING DIAGRAM POWER SUPPLY : 460-3-60 (Dual compressor units) APPLICABLE ON MODELS: CNX150 - CNXM10 COMPRESSOR WITH CB CONNECTION HVTB (OPTIONAL) L1 HVTB L2 POWER SUPPLY L1 L3 (NOTE 4) L2 L3 COMP 1 2 COMPRESSOR POWER & CONTROL CONNECTION IN PART WINDING STARTING (PWS) COMP 1 2 3A 4O 3B CC2A-2A 61B 11A 9A OLR2-1A 10B 11B OLR4-1A CB1A-1A 23A C1 1 C2 3-FAN MOTOR LAYOUT 3 CONTROL PANEL 2 CONTROL PANEL CB6 CB6 HVTB L1 L2 L3 4-FAN MOTOR LAYOUT C1 1 CONTROL PANEL C2 2 CB7 L3B CB6 FM1 4 C2 2 FM2 FM1 T.K. TO MB 12A 9 NO FM2 T.K. 12B 13 NO 12A 13B 2 TO MB FMC1 9 NO FMC2 FM1 T.K. 12A FM3 T.K. 12C 10 NO 13C FM2 T.K. 12B 13 NO 13A 13B FM1 T.K. TO MB 12A 9 NO FMC3 12C 13C 10 NO FM2 T.K. 12B 13 NO 104D FMC3 COMP. 2: 13D FMC4 HVTB L1 L2 L3 CB6 CB8 CB7 -- -- HIGH PRESSURE -- -- 460 ± 10 360 ± 15 -- -- FM1 FM3 FM2 105F 104F 103F 104E 105E 103E 105D HGS FM4 FM5 FM1 T.K. TO MB 12A 12E FM5 T.K. FM3 T.K. 12C 10 NO 13 NO FM2 T.K. 12B 12F 14 NO 12D FM6 T.K. FM4 T.K. 13A 13E 13C 37F FM6 JU1 - CLOSED JU12 - CLOSED (1,2) JU2 - CLOSED JU13 - CLOSED (1,2) JU3 - CLOSED (1,2) JU15 - CLOSED (1,2) JU4 - CLOSED (1,2) JU19 - CLOSED (1,2) JU5 - CLOSED (1,2) FMC1 FMC5 FMC3 JU6 - CLOSED (1,2) TU1 - CLOSED JU7 - CLOSED (1,2) TU2 - CLOSED JU8 - CLOSED (1,2) TL1 - OPEN JU9 - CLOSED (1,2) TL2 - OPEN JU10 - CLOSED (1,2) TD1 - CLOSED 13F 13D S1 FMC6 6 L3 OPS1 3A 2 2 240 64A OPS1-1 OPS2 3B 2 2 240 OPS2-1 64B AHU CONTROL INTER-CONNECTIONS (OPTIONAL) AIR HANDLING UNIT CONTROL PANEL CONDENSING UNIT CONTROL PANEL LVTB G ATB R1 (24Vac) R1-1 1 ATB (AHU MOTOR CONTROL) 67 ATB 1 2 3 4 ON OFF OFF OFF L1 4-FAN MOTOR LAYOUT 5 C1 3 L2 C.HTR2 20 ATB R2 (230Vac) 2 R2-1 UVM CONNECTION(OPTIONAL) CNX 720~840 / CNXM00~20 CONTROL PANEL C.HTR1 L2 17 DIP SWITCH SETTINGS - MB BOARD FMC2 FMC4 L1 1 ATB TD2 - CLOSED JU11 - CLOSED (1,2) 13B 2 (REMOVE JP5A) COMP 2 JUMPER SETTINGS - MB BOARD 2 9 NO 2 C.HTR1 (REMOVE JP5B) FMC6 36F 37E 36E 35E 37D FMC5 35F 104D 36D FMC4 35D 37B 36B 35B 37C 36C 103D 104B 105B FMC2 FMC3 35C 37A 36A FMC1 103B 104C 105C 103C 104A 105A HPS1 & 2 2 C.HTR2 101A CC2A-1B CUT-OFF (PSIG) CUT-IN (PSIG) LOW PRESSURE 8B 100A CC1A-1B 1 PRESSURE SETTINGS DESC. L2/R/N OIL PRESSURE SWITCH CONN.(AS APPLICABLE) COMP 1 HVTB L1 L2 L3 M2/14 B. SCROLL COMP. FMC2 13B FM4 T.K. 12D 14 NO HVTB L1 L2 L3 1 COMP. 1: FMC2 M1/11 L1/MP/L (REMOVE JP4B) 1 COMP. 2: FMC1 13A FM3 T.K. 2 A. SEMI-HERMETIC RECIP. COMP. 2 FMC1 8A CRANKCASE HTR CONNECTION(AS APPLICABLE) FM4 COMP. 1: 2 L2/R/N (SEE NOTE 3) 37D 36D FMC4 35D 37B 36B 35B 37C 35C 36C FM3 M2/14 (REMOVE JP3A) SSPS2 105D 103D 104B 103B 105B 104C 105C 103C 104A 103A FM1 M1/11 L1/MP/L COMP. 2: FMC2 FMC3 37A 35A FM2 36A FMC1 37B 36B 35B FMC2 FM3 T3D SSPS1 3 C1 1 CB7 105A 104B 105B 103B 103C 104C 36C 35C FMC3 37C 37A 35A FM2 36A FMC1 37B 36B 35B FM1 105C 105A 104A 103A 104B 105B 103B 104A 103A 105A 37A 36A FMC2 T2D T1D T3B COMP. 1: 1 CNX 480~600 HVTB L1 L2 L3 1 FMC1 23B COMP. SSPS CONNECTION(AS APPLICABLE) CNX 360~420 HVTB L1 L2 L3 HVTB L1 L2 L3 CB2A-1A 1 9B CONDENSER FAN MOTOR POWER AND CONTROL CONNECTIONS CNX 220~300 2-FAN MOTOR LAYOUT T2B T1B T3C T2C T1C T3A 2 CC4 1 OLR3-1A COMP 1 CC2 CC3 61A OLR1-1A COMP 2 2 MB CC1 HVTB L1 L2 L3 L2B L1B L3C L2C L1C L3A L2A L1A T2A COMP 2 1 CC1A-2A T1A T3B T1B COMP T3D CC4 OLR4 T2D CC2 OLR2 T1D CC3 OLR3 T2B CC1 OLR1 T3C CC4 OLR4 T2C CC2 OLR2 T1C CC3 OLR3 T3A T2A T1A CC1 OLR1 MB 10A CB2 L1D L3 L3D L2 L3 L2D L2 1O 35A (OPTIONAL) L1 CB1 103A T3B COMP HVTB L1 35A T2B T1B CC2 OLR2 T3A CC1 OLR1 COMPRESSOR IN PWS CONNECTION WITH CB (AS APPLICABLE) HVTB L3B L1B L3A L2A L1A COMP T2A T1A T3B T2B T1B CC2 OLR2 T3A T2A T1A CC1 OLR1 CB2 L2B CB1 LUG/ETB L2 L3 ATB 1 1 4 C2 2 Ø L1 1 Ø L2 Ø UVM-1 Ø L3 8 ATB UVM MOTOR STARTER CONTROL AHU MOTOR ON/OFF SWITCHING CONTACT AHU MOTOR FAULT (N.C CONTACT) (REMOVE JP7) 52 Ø (REMOVE JP1) 1A 1 NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items. 2. Refer to unit control box (inside panel) for exact wiring diagram. 16 Downloaded from www.Manualslib.com manuals search engine SCHEMATIC WIRING DIAGRAM POWER SUPPLY : 460-3-60 (Dual compressor units) APPLICABLE ON MODELS: CNX150 - CNXM10 TO ATB LEGEND 1 2 SWITCHING CONTACTS FROM THERMOSTAT OR DDC (FIELD INSTALLATION) TRANS1 (75VA) LVTB COM 230V ATB 15 R ATB 17 24V C AHU MOTOR CONTROL (OPTIONAL CONNECTION) G STG1 COOLING YR1 Y1 STG2 COOLING YR2 Y2 TO HVTB L1 TO HVTB L3 F3 TRANS2 3 F4 4 460V 230V ATB HPS1 F1 S1 (UVM-1) JP1 1 1A 1B 5 8A (OPS1-1) JP5A 64A (CB1A-1) JP4A 10A HPS2 17 OLR1-1A PE A2 (CB-1) A3 (OL-1) 9A AO4 A4 (HPS-1) A5 (FCB-1) 8B (CB2A-1) JP4B 64B 10B OLR2-1A AO3 A6 (SSPS-2) 23B A7 (CB-2) 9B A9 (HPS-2) AO2 A8 (OL-2) P AO1 A10 JP6 2 A1 (SSPS-1) 23A P (OPS2-1) JP5B TO ATB 15 24V AC (SSPS1) JP3A (SSPS2) JP3B TO ATB ATB F2 6 67 A11 (FLOW SWITCH) A12 A13 (EMERGENCY) YR1-1A 71A YR2-1A 71B A20 (AUX. ALARM COMP2) AC (DIGITAL COM) 1C R1(DIG OUT) 1O 2C R2(DIG OUT) 2O 15A 3C R3(DIG OUT) 3O 14A 4C R4(DIG OUT) 4O PDS1 R5(DIG OUT) 5O 15B 6C R6(DIG OUT) 6O 14B 7C R7(DIG OUT) 7O 8C R8(DIG OUT) C R9(DIG OUT) 9NO R10(DIG OUT) 10NO R11(DIG OUT) 11NO R12(DIG OUT) 12NO R13(DIG OUT) 13NO 14NO 15NO R16(DIG OUT) 16NO 17C R17(DIG OUT) 17NO 18C R18(DIG OUT) 18NO - S1 (A5-SP1) + SH D1 (A6-DP1) T.OUT O1 (A7-OP1) ST2 (A1-ST1) + + SH S2 (A8-SP2) TIN + D2 (A9-DP2) USER INTERFACE BOARD + ON S1 O2 (A10-OP2) DIP ESC * + 1 2 3 4 COM1 HOT GAS BY-PASS SOLENOID (OPTIONAL) 20 AHU MOTOR ON/OFF CONTROL (230Vac) REFER FAN MOTOR CONTROL CONNECTION (SYSTEM 2) SPT1 28A - 29A + SH DPT1 30A - 31A + SH OPT1 32A - 33A + SH SPT2 28B 29B + SH DPT2 30B 31B + SH OPT2 32B 33B + SH GND 17 Downloaded from www.Manualslib.com manuals search engine COMP2 CAPACITY UNLOADER SOLENOID (OPTIONAL) REFER FAN MOTOR CONTROL CONNECTION (SYSTEM 1) SH SERIAL CABLE COMP2 PUMP DOWN SOLENOID (OPTIONAL) UL2 COMMON FAULT INDICATION (VOLT-FREE CONTACT) SH SH COMP2 CONTACTOR PDS2 8NO R15(DIG OUT) ST1 COMP1 CAPACITY UNLOADER SOLENOID (OPTIONAL) HGS R14(DIG OUT) SH COMP1 CONTACTOR COMP1 PUMP DOWN SOLENOID (OPTIONAL) CC2 3B 5C C CC1 3A UL1 8NC On/Off * COMPRESSOR FUSE FAN MOTOR (CONDENSER) FAN MOTOR CONTACTOR HIGH PRESSURE SWITCH HIGH VOLTAGE TERMINAL BLOCK JUMPER LINE 1 LINE 2 LINE 3 LUG GROUND MOTHER BOARD OVER LOAD RELAY SOLID STATE PROTECTIVE SYSTEM TRANSFORMER FAN MOTOR (PROTECTION) THERMAL CONTACT COMPRESSOR UNLOADER SOLENOID UNDER VOLTAGE MONITOR COOLING RELAY FIELD WIRING DISCONNECT TAB - 1/4" SPLICE-CLOSED END TERMINAL BLOCK OR TERMINATION POINT JUNCTION OF WIRES CROSSING OF WIRES, NO CONNECTION EARTHING/GROUND + A17 (S. FAN MOTOR FAULT) 52 A19 (AUX. ALARM COMP1) SET MENU * COMP/C F FM FMC HPS HVTB JP L1 L2 L3 LUG MB OLR SSPS TRANS TK/TOP UL UVM YR A15 (COOLING STAGE 2) A18 TOUT=15°C TIN=28°C COOLING 75% AIR HANDLING UNIT AUXILIARY TERMINAL BLOCK BLOWER MOTOR RELAY COMPRESSOR CONTACTOR AUXILIARY CONTACT CIRCUIT BREAKER CRANKCASE HEATER ___ A14 (COOLING STAGE 1) A16 JP7 AHU ATB BMR CC CCA CB C. HTR NOTES 1. ANY WIRE REPLACEMENT SHOULD BE OF THE 900C OR ITS EQUIVALENT. 2. USE COPPER CONDUCTOR WIRES ONLY. 3. COMPRESSORS ARE PROVIDED WITH INTERNAL LINE BREAK OR SSPS FOR THERMAL PROTECTION. 4. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER TO BE PROVIDED BY END USER WITH RATING AS RECOMMENDED BY ZAMIL. + 5. USE DISCONNECT TAB OR SPLICE ONLY WHERE- EVER REQUIRED FOR EXTENSION OF ORIGINAL WIRE. 6. POWER MUST BE SUPPLIED TO CRANKCASE HEATER FOR MINIMUM OF 12 HOURS PRIOR TO SYSTEM START UP. IF POWER IS OFF 6 HOURS OR MORE, CRANKCASE HEATER MUST BE ON FOR 12 HOURS BEFORE OPERATING THE SYSTEM. FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN COMPRESSOR DAMAGE. COMP1 SUCTION PRESSURE TRANSDUCER COMP1 DISCHARGE PRESSURE TRANSDUCER COMP1 OIL PRESSURE TRANSDUCER (FOR RECIP. COMP ONLY) COMP2 SUCTION PRESSURE TRANSDUCER COMP2 DISCHARGE PRESSURE TRANSDUCER COMP2 OIL PRESSURE TRANSDUCER (FOR RECIP. COMP ONLY) SCHEMATIC WIRING DIAGRAM POWER SUPPLY : 460-3-60 (Four compressor units) APPLICABLE ON MODELS: CNXM20 - CNXM60 COMPRESSOR POWER & CONTROL CONNECTION HVTB / BUSBAR L1 L2 POWER SUPPLY COMP 2 4O 4 2 CC2 3B T3D COMP 3 2 AB MB CC1 T2D T1D COMP 2 MB 3A T3C T3B COMP 2 1 1O T2C CC4 OLR4 T1C CC3 OLR3 T2B CC2 OLR2 T1B CC1 OLR1 T3A T1A T2A L3 (NOTE 4) AB 1O CC3 3C 4O CC4 3D CONDENSER FAN MOTOR POWER & CONTROL CONNECTIONS - 6 FANS / CNXM20 FAN LAYOUT COMP1 FAN1 FAN2 FAN3 FAN4 FAN5 FAN6 COMP3 TO HVTB/BUSBAR L1 L2 L3 FM5 13C FM1 T.K. 13A 104F 105F 103F 104D 105D 37F 37D 36D 12D FM2 T.K. FMC1 12B 10 NO 13D 13B FMC4 FMC2 13 NO 12E T.K. 13E CONDENSING UNIT CONTROL PANEL FMC5 12F 12F 14 NO FM6 T.K. AIR HANDLING UNIT CONTROL PANEL G BMR (24Vac) BMR-1A 1 (AHU MOTOR CONTROL) 67 CLOSE (PSIG) LOW PRESSURE 10 ± 5 HIGH PRESSURE 300 HPS1 ~4 350 ± 10 300 ± 15 OFF (PSIG) ON (PSIG) FAN MOTOR # 17 OPEN (PSIG) 13F FMC6 JUMPER SETTINGS - MB BOARD PRESSURE SETTINGS DESC. LVTB ATB FM4 T.K. TO AB AHU CONTROL INTER-CONNECTIONS (OPTIONAL) ATB FM6 2 FMC3 13 NO (REMOVE JP6) FM4 9 NO 12A FMC6 2 FM3 T.K. 10 NO ATB 35D FM2 9 NO 14 NO FMC4 37B 36B FMC2 35B 37E 36E 35E FM3 103D 104B 105B 103B 104E 103E 105E 104C 105C 105A FM1 FMC5 37C 36C FMC3 35C 37A 36A 35A FMC1 12C CB19 CB18 103C 104A 103A CB17 TO HVTB/BUSBAR L1 L2 L3 36F TO HVTB/BUSBAR L1 L2 L3 TO MB COMP4 35F CONTROL PANEL COMP2 30 ± 5 JU1 - CLOSED TU1 - OPEN JU2 - CLOSED TD1 - OPEN TL1 - OPEN -- FM1,2,5,6 125 175 FM3,4 175 225 DIP SWITCH SETTINGS - MB1 BOARD S1 1 2 3 4 ON OFF OFF OFF JUMPER SETTINGS - MB BOARD JU1 - OPEN TU1 - OPEN JU2 - OPEN TD1 - OPEN TL1 - OPEN ATB DIP SWITCH SETTINGS - AB BOARD 20 ATB R2 (230Vac) S1 2 R2-1 ATB 1 ATB MOTOR STARTER CONTROL AHU MOTOR ON/OFF SWITCHING CONTACT AHU MOTOR FAULT (N.C CONTACT) (REMOVE JP7) 52 1 2 3 4 OFF ON OFF OFF JUMPER SETTINGS (COMMON) JU3 - CLOSED (1,2) JU11 - CLOSED (1,2) JU4 - CLOSED (1,2) JU12 - CLOSED (1,2) JU5 - CLOSED (1,2) JU13 - CLOSED (1,2) JU6 - CLOSED (1,2) JU15 - CLOSED (1,2) JU7 - CLOSED (1,2) JU19 - CLOSED (1,2) JU8 - CLOSED (1,2) TU2 - CLOSED JU9 - CLOSED (1,2) TD2 - CLOSED JU10 - CLOSED (1,2) TL2 - OPEN NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items. 2. Refer to unit control box (inside panel) for exact wiring diagram. 18 Downloaded from www.Manualslib.com manuals search engine SCHEMATIC WIRING DIAGRAM POWER SUPPLY : 460-3-60 (Four compressor units) APPLICABLE ON MODELS: CNXM20 - CNXM60 TO HVTB L1 TO HVTB L3 F3 TRANS2 3 4 460V F4 230V F1 S1 1A 5 1B 6 CC1A-1B 100A Ø L1 1 L3 L2 CC2A-1B 100B CC5A-1B 100C Ø L2 Ø UVM-1 Ø L3 8 UVM CC6A-1B 100D C.HTR2 C.HTR3 C.HTR4 Ø (REMOVE JP1) 2 C.HTR1 UVM CONNECTION (OPTIONAL) L1 ATB F2 SSPS1 1A SSPS2 1 SSPS3 ATB SSPS4 (UVM-1) JP1 1 8A JP5A (CB1A-1) JP4A 17 OLR1-1A 10A PE A1 (SSPS-1) 23A A2 (CB-1) 64A A3 (OL-1) 9A AO4 A4 (HPS-1) P A5 (FCB-1) SSPS2 8B JP5B HPS2 TO ATB 15 24V AC SSPS1 HPS1 TO ATB 10B (CB2A-1) JP4B OLR2-1A AO3 A6 (SSPS-2) 23B A7 (CB-2) 64B A8 (OL-2) 9B A9 (HPS-2) P AO2 AO1 A10 JP6 67 A11 (FLOW SWITCH) A12 (EXTERNAL ENABLE) A13 (EMERGENCY) YR1-1A 71A YR2-1A 71B A14 (COOLING STAGE 1) A15 (COOLING STAGE 2) A16 JP7 52 A17 (S. FAN MOTOR FAULT) A18 A19 (AUX. ALARM COMP1) A20 (AUX. ALARM COMP2) AC (DIGITAL COM) 1C R1(DIG OUT) 1O 2C R2(DIG OUT) 2O 3C R3(DIG OUT) 3O 4C R4(DIG OUT) 4O 5C R5(DIG OUT) 3A 15A COMP1 CONTACTOR (SEE COMP. POWER & CONTROL CONNECTION, SHEET 1 0F 3) PDS1 COMP1 PUMP DOWN SOLENOID UL1 14A COMP1 CAPACITY UNLOADER SOLENOID (50% UNLOADER SOLENOID) 5O 6C R6(DIG OUT) 6O 7C R7(DIG OUT) 7O 8C R8(DIG OUT) 8NO C R9(DIG OUT) 9NO R10(DIG OUT) 10NO R11(DIG OUT) 11NO R12(DIG OUT) 12NO COMP1 CONTACTOR 3B (SEE COMP. POWER & CONTROL CONNECTION, SHEET 1 0F 3) PDS2 15B COMP2 PUMP DOWN SOLENOID UL2 14B COMP2 CAPACITY UNLOADER SOLENOID (50% UNLOADER SOLENOID) COMMON FAULT INDICATION (VOLT-FREE CONTACT) 8NC C R13(DIG OUT) 13NO R14(DIG OUT) 14NO R15(DIG OUT) 15NO R16(DIG OUT) 16NO 17C R17(DIG OUT) 17NO 18C R18(DIG OUT) 18NO S1 (A5-SP1) ST1 SH + SH D1 (A6-DP1) T.OUT + REFER FAN MOTOR CONTROL CONNECTION (SYSTEM 1) (SHEET 1 OF 3) 20 REFER FAN MOTOR CONTROL CONNECTION (SYSTEM 2) (SHEET 1 OF 3) O1 (A7-OP1) ST2 (A1-ST1) + SH S2 (A8-SP2) TIN + D2 (A9-DP2) USER INTERFACE BOARD + On/Off * TOUT=15°C TIN=28°C COOLING 75% SET MENU * ESC * ON S1 DPT1 30A 31A OPT1 33A SPT2 29B DPT2 31B O2 (A10-OP2) DIP + 1 2 3 4 OPT2 33B SH + SH 32B + SH 30B + SH 28B + SH 32A + SH SH SERIAL CABLE COM1 SPT1 28A 29A SH SH AHU MOTOR ON/OFF CONTROL (230Vac) + COMP1 SUCTION PRESSURE TRANSDUCER COMP1 DISCHARGE PRESSURE TRANSDUCER COMP1 OIL PRESSURE TRANSDUCER COMP2 SUCTION PRESSURE TRANSDUCER COMP2 DISCHARGE PRESSURE TRANSDUCER COMP2 OIL PRESSURE TRANSDUCER GND NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items. 2. Refer to unit control box (inside panel) for exact wiring diagram. 19 Downloaded from www.Manualslib.com manuals search engine SCHEMATIC WIRING DIAGRAM POWER SUPPLY : 460-3-60 (Four compressor units) APPLICABLE ON MODELS: CNXM20 - CNXM60 TO ATB 2 LEGEND 1 SWITCHING CONTACTS FROM THERMOSTAT OR DDC (FIELD INSTALLATION) TRANS1 (75VA) LVTB COM 230V ATB ATB 24V 15 R 17 C AHU MOTOR CONTROL (OPTIONAL CONNECTION) BMR (OPTIONAL CONNECTION) G STG1 COOLING YR1 Y1 STG2 COOLING YR2 Y2 STG3 COOLING YR3 Y3 STG4 COOLING YR4 Y4 ATB 2 ATB 1 8C JP5C (CB3A-1) JP4C 17 OLR3-1A 10C PE A1 (SSPS-3) A2 (CB-3) 23C 64C A3 (OL-3) AO4 A4 (HPS-3) 9C P A5 SSPS4 8D JP5D HPS4 TO ATB 15 24V AC SSPS3 HPS3 TO ATB 10D (CB4A-1) JP4D OLR4-1A AO3 A6 (SSPS-4) A7 (CB-4) 23D 64D A8 (OL-4) 9D A9 (HPS-4) P AO2 AO1 A10 A11 A12 A13 YR3-1A 71C YR4-1A 71D A15 (COOLING STAGE 4) A17 A18 A19 (AUX. ALARM COMP3) A20 (AUX. ALARM COMP4) AC (DIGITAL COM) 1C R1(DIG OUT) 1O 2C R2(DIG OUT) 2O 3C R3(DIG OUT) 3O 4C R4(DIG OUT) 4O 5C R5(DIG OUT) 5O 3C 15C COMP3 CONTACTOR 6C R6(DIG OUT) 6O 7C R7(DIG OUT) 7O COMP3 PUMP DOWN SOLENOID UL3 14C COMP3 CAPACITY UNLOADER SOLENOID 8C R8(DIG OUT) 8NO C R9(DIG OUT) COMP4 CONTACTOR 3D (SEE COMP. POWER & CONTROL CONNECTION, SHEET 1 0F 3) PDS4 15D COMP4 PUMP DOWN SOLENOID UL4 14D COMP4 CAPACITY UNLOADER SOLENOID (50% UNLOADER SOLENOID) COMMON FAULT INDICATION (VOLT-FREE CONTACT) 8NC REFER FAN MOTOR CONTROL CONNECTION (SYSTEM 3) 9NO R10(DIG OUT) 10NO R11(DIG OUT) 11NO R12(DIG OUT) 12NO R13(DIG OUT) 13NO R14(DIG OUT) 14NO R15(DIG OUT) 15NO R16(DIG OUT) 16NO 17C R17(DIG OUT) 17NO 18C R18(DIG OUT) 18NO S1 (A5-SP1) + SH D1 (A6-DP1) T.OUT + (SHEET 1 OF 3) REFER FAN MOTOR CONTROL CONNECTION (SYSTEM 4) (SHEET 1 OF 3) O1 (A7-OP1) ST2 (A1-ST1) + SH S2 (A8-SP2) TIN + D2 (A9-DP2) + TO MASTER BOARD MB X53 ON S1 SPT3 28C 29C DPT3 30C 31C OPT3 33C SPT4 29D DPT4 31D O2 (A10-OP2) DIP SERIAL CABLE + 1 2 3 4 X52 OPT4 32D 33D SH + SH SH + SH 30D + SH 28D + SH 32C + SH SH SH + COMP3 SUCTION PRESSURE TRANSDUCER COMP3 DISCHARGE PRESSURE TRANSDUCER COMP3 OIL PRESSURE TRANSDUCER COMP4 SUCTION PRESSURE TRANSDUCER COMP4 DISCHARGE PRESSURE TRANSDUCER COMP4 OIL PRESSURE TRANSDUCER GND 20 Downloaded from www.Manualslib.com manuals search engine COMPRESSOR FUSE FAN MOTOR (CONDENSER) FAN MOTOR CONTACTOR HIGH PRESSURE SWITCH HIGH VOLTAGE TERMINAL BLOCK JUMPER LINE 1 LINE 2 LINE 3 LUG GROUND MOTHER BOARD OVER LOAD RELAY SOLID STATE PROTECTIVE SYSTEM TRANSFORMER FAN MOTOR (PROTECTION) THERMAL CONTACT COMPRESSOR UNLOADER SOLENOID UNDER VOLTAGE MONITOR COOLING RELAY FIELD WIRING DISCONNECT TAB - 1/4" SPLICE-CLOSED END TERMINAL BLOCK OR TERMINATION POINT JUNCTION OF WIRES CROSSING OF WIRES, NO CONNECTION EARTHING/GROUND (SEE COMP. POWER & CONTROL CONNECTION, SHEET 1 0F 3) PDS3 (50% UNLOADER SOLENOID) SH COMP/C F FM FMC HPS HVTB JP L1 L2 L3 LUG MB OLR SSPS TRANS TK/TOP UL UVM YR + A16 ST1 AIR HANDLING UNIT AUXILIARY TERMINAL BLOCK BLOWER MOTOR RELAY COMPRESSOR CONTACTOR AUXILIARY CONTACT CIRCUIT BREAKER CRANKCASE HEATER ___ A14 (COOLING STAGE 3) C AHU ATB BMR CC CCA CB C. HTR NOTES 1. ANY WIRE REPLACEMENT SHOULD BE OF THE 900C OR ITS EQUIVALENT. 2. USE COPPER CONDUCTOR WIRES ONLY. 3. COMPRESSORS ARE PROVIDED WITH INTERNAL LINE BREAK OR SSPS FOR THERMAL PROTECTION. 4. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER TO BE PROVIDED BY END USER WITH RATING AS RECOMMENDED BY ZAMIL. + 5. USE DISCONNECT TAB OR SPLICE ONLY WHERE- EVER REQUIRED FOR EXTENSION OF ORIGINAL WIRE. 6. POWER MUST BE SUPPLIED TO CRANKCASE HEATER FOR MINIMUM OF 12 HOURS PRIOR TO SYSTEM START UP. IF POWER IS OFF 6 HOURS OR MORE, CRANKCASE HEATER MUST BE ON FOR 12 HOURS BEFORE OPERATING THE SYSTEM. FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN COMPRESSOR DAMAGE. SCHEMATIC WIRING DIAGRAM POWER SUPPLY : 460-3-60 (Four compressor units) APPLICABLE ON MODELS: CNX2M00 - CNX2M40 COMPRESSOR POWER & CONTROL CONNECTION IN PART WINDING STARTING (PWS) HVTB / BUSBAR L1 L2 POWER SUPPLY 4O OLR1-1A 11A CC2A-2A OLR3-1A 9A OLR2-1A 11B 10B 1O CC5A-2A OLR4-1A 9B 4O T3H CC6 3D CC7 61C OLR5-1A 11C 10C T2H T1H T3F T2F T1F T3G T2G T1G 3C CC6A-2A OLR7-1A 2 4 AB CC5 CC4 61B COMP 2 3 AB CC2 3B CC3 61A COMP 2 2 MB CC1 3A 10A T3E COMP 2 1 CC1A-2A T1E T3B T1B COMP MB 1O T2E CC8 OLR8 T3D CC6 OLR6 T2D CC7 OLR7 T1D CC5 OLR5 T2B CC4 OLR4 T3C CC2 OLR2 T2C CC3 OLR3 T1C CC1 OLR1 T3A T1A T2A L3 (NOTE 4) 9C CC8 61D OLR6-1A 11D 10D OLR8-1A 9D CONDENSER FAN MOTOR POWER & CONTROL CONNECTIONS - 16 FANS / CNX2M40 FAN LAYOUT COMP3 COMP1 FAN7 FAN8 FAN9 FAN10 FAN11 FAN12 FAN13 FAN14 FM1 FM5 FM3 FM4 12A 12A 12E 10 NO 12C FM5 T.K. FM3 T.K. 12C 12G FM7 T.K. 13 NO 12B FMC5 13E 14 NO FMC7 13G 12D AIR HANDLING UNIT CONTROL PANEL LVTB FM6 T.K. 13B 13F FM4 T.K. 12D 12H AHU CONTROL INTER-CONNECTIONS (OPTIONAL) CONDENSING UNIT CONTROL PANEL 12B 12F FMC3 13C FM8 T.K. 13D 13H ATB BMR-1A FMC4 10 NO 12K 12O PRESSURE SETTINGS OPEN (PSIG) 10 ± 5 30 ± 5 HIGH PRESSURE 300 HPS1 & 2 350 ± 10 300 ± 15 FM15 FM10 13K FM15 T.K. 13O 37P 104P FM16 FM12 2 13 NO 12J FMC13 FM10 T.K. 12J 12N FMC11 14 NO FMC15 36P FMC16 35P 37L 36L 35L FMC12 FM14 AB FMC9 105P 103P 104L 105L 103L 104N 105N 37N FMC14 36N 37J 36J 35J 37O 36O 103N 104J 105J 103J 104O 105O 105K 104K 13M FM11 T.K. OFF (PSIG) ON (PSIG) JU1 - CLOSED TU1 - OPEN JU2 - CLOSED TD1 - OPEN 12L FM14 T.K. 12P 13N FM12 T.K. 12L FM16 T.K. 13J 13L 13P FMC10 FMC14 FMC12 FMC16 TL1 - OPEN -- FM1,5,2,6,9,13,10,14 125 175 FM3,7,4,8,11,15,12,16 175 225 (AHU MOTOR CONTROL) DIP SWITCH SETTINGS - MB BOARD S1 1 2 3 4 ON OFF OFF OFF JUMPER SETTINGS - AB BOARD JU1 - OPEN TU1 - OPEN JU2 - OPEN TD1 - OPEN TL1 - OPEN DIP SWITCH SETTINGS - AB BOARD R2 (230Vac) S1 2 R2-1 1 FMC10 JUMPER SETTINGS - MB BOARD CLOSE (PSIG) 20 ATB 13I FM13 T.K. 12K FMC8 ATB ATB 37K 36M 35M 37I 36I 35I 103K 104M 105M 103M 104I 105I 103I 105H 37H 37M FM9 T.K. 12I 67 ATB FMC15 FM11 12M 1 ATB 12I FMC6 DESC. CB24 2 9 NO LOW PRESSURE TO HVTB/BUSBAR L1 L2 L3 CB23 FMC11 FM13 TO AB FMC2 FAN MOTOR # BMR (24Vac) 17 (REMOVE JP6) FMC13 FM9 G ATB CB22 FMC9 FM8 TO HVTB/BUSBAR L1 L2 L3 2 FM2 T.K. TO MB FMC1 13A 36H FMC8 2 FM1 T.K. TO MB 9 NO 104H 103H 104D 105D 37D 36D 37F FM6 TO HVTB/BUSBAR L1 L2 L3 CB21 FMC4 35D FMC6 36F 37B 36B FM2 103D 104F 105F 103F 104B 103B FM7 TO HVTB/BUSBAR L1 L2 L3 CB20 FMC2 35B 37G 36G FMC7 35G 37C 36C 35C FMC3 105B 104G 105G 103G 104C 105C 103C 104E 105E 37E 36E FMC5 35E 37A 36A 35A FMC1 TO HVTB/BUSBAR L1 L2 L3 CB19 CB18 103E 104A 105A 103A CB17 TO HVTB/BUSBAR L1 L2 L3 35H TO HVTB/BUSBAR L1 L2 L3 35F TO HVTB/BUSBAR L1 L2 L3 COMP4 35N COMP2 FAN15 FAN16 35O FAN5 FAN6 103O FAN3 FAN4 36K FAN1 FAN2 35K CONTROL PANEL 1 2 3 4 OFF ON OFF OFF JUMPER SETTINGS (COMMON) MOTOR STARTER CONTROL AHU MOTOR ON/OFF SWITCHING CONTACT AHU MOTOR FAULT (N.C CONTACT) (REMOVE JP7) 52 JU3 - CLOSED (1,2) JU11 - CLOSED (1,2) JU4 - CLOSED (1,2) JU12 - CLOSED (1,2) JU5 - CLOSED (1,2) JU13 - CLOSED (1,2) JU6 - CLOSED (1,2) JU15 - CLOSED (1,2) JU7 - CLOSED (1,2) JU19 - CLOSED (1,2) JU8 - CLOSED (1,2) TU2 - CLOSED JU9 - CLOSED (1,2) TD2 - CLOSED JU10 - CLOSED (1,2) TL2 - OPEN NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items. 2. Refer to unit control box (inside panel) for exact wiring diagram. 21 Downloaded from www.Manualslib.com manuals search engine SCHEMATIC WIRING DIAGRAM POWER SUPPLY : 460-3-60 (Four compressor units) APPLICABLE ON MODELS: CNX2M00 - CNX2M40 TO HVTB L1 TO HVTB L3 F3 TRANS2 3 4 460V F4 230V F1 S1 1A 5 1B 6 CC1A-1B 100A L2 Ø L1 1 L3 CC2A-1B 100B CC5A-1B 100C Ø L2 Ø UVM-1 Ø L3 8 UVM CC6A-1B 100D 2 C.HTR1 UVM CONNECTION (OPTIONAL) L1 ATB F2 C.HTR2 C.HTR3 C.HTR4 Ø SSPS1 (REMOVE JP1) 1A SSPS2 1 SSPS3 ATB SSPS4 (UVM-1) JP1 1 TO ATB 15 24V AC SSPS1 8A JP5A HPS1 10A (CB1A-1) JP4A OLR3-1A OLR1-1A 11A PE A1 (SSPS-1) 23A A2 (CB-1) 64A A3 (OL-1) 9A AO4 A4 (HPS-1) P A5 (FCB-1) SSPS2 8B JP5B HPS2 TO ATB 17 10B (CB2A-1) JP4B OLR2-1A 11B OLR4-1A AO3 A6 (SSPS-2) A7 (CB-2) 23B 64B A8 (OL-2) 9B A9 (HPS-2) P AO2 AO1 A10 JP6 67 A11 (FLOW SWITCH) A12 (EXTERNAL ENABLE) A13 (EMERGENCY) YR1-1A 71A YR2-1A A14 (COOLING STAGE 1) 71B A15 (COOLING STAGE 2) A16 JP7 52 A17 (S. FAN MOTOR FAULT) A18 A19 (AUX. ALARM COMP1) A20 (AUX. ALARM COMP2) AC (DIGITAL COM) 1C R1(DIG OUT) 1O 2C R2(DIG OUT) 2O 3C R3(DIG OUT) 3O 4C R4(DIG OUT) 4O COMP1 CONTACTOR 3A (SEE COMP. POWER & CONTROL CONNECTION, SHEET 1 0F 3) PDS1 COMP1 PUMP DOWN SOLENOID UL1-2 14A COMP1 CAPACITY UNLOADER SOLENOID (50% UNLOADER SOLENOID) 5O COMP2 PUMP DOWN SOLENOID 6C R6(DIG OUT) 6O 14B 7C R7(DIG OUT) 7O 15A 8C R8(DIG OUT) C R9(DIG OUT) 9NO R10(DIG OUT) 10NO R11(DIG OUT) 11NO R12(DIG OUT) 12NO R13(DIG OUT) 13NO R14(DIG OUT) 14NO R15(DIG OUT) 15NO R16(DIG OUT) 16NO R17(DIG OUT) 17NO 18C R18(DIG OUT) 18NO - S1 (A5-SP1) + SH (OPTIONAL) SH 24 LEAVING AIR TEMP. SENSOR (PTC : -10 ~ +50 C) D1 (A6-DP1) T.OUT 25 SH O1 (A7-OP1) ST2 (A1-ST1) + SH D2 (A9-DP2) USER INTERFACE BOARD + On/Off * TOUT=15°C TIN=28°C COOLING 75% SET MENU * ESC * ON S1 16B UL2-4 REFER FAN MOTOR CONTROL CONNECTION (SYSTEM 1) (SHEET 1 OF 3) AHU MOTOR ON/OFF CONTROL (230Vac) 20 REFER FAN MOTOR CONTROL CONNECTION (SYSTEM 2) (SHEET 1 OF 3) SPT1 28A 29A DPT1 30A + SH 31A + SH COMP1 SUCTION PRESSURE TRANSDUCER COMP1 DISCHARGE PRESSURE TRANSDUCER SPT2 28B 29B DPT2 30B 31B SH + SH + COMP2 SUCTION PRESSURE TRANSDUCER COMP2 DISCHARGE PRESSURE TRANSDUCER SH O2 (A10-OP2) DIP SERIAL CABLE + 1 2 3 4 COM1 (50% UNLOADER SOLENOID) CC2-1A + S2 (A8-SP2) TIN 27 UL1-4 - SH 26 RETURNING AIR TEMP. SENSOR (PTC : -10 ~ +50 C) + 16A COMMON FAULT INDICATION (VOLT-FREE CONTACT) SH SH (OPTIONAL) COMP2 CAPACITY UNLOADER SOLENOID CC1-1A 8NO 17C ST1 UL2-2 15B 8NC C COMP1 CONTACTOR (SEE COMP. POWER & CONTROL CONNECTION, SHEET 1 0F 3) PDS2 R5(DIG OUT) 5C 3B GND NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items. 2. Refer to unit control box (inside panel) for exact wiring diagram. 22 Downloaded from www.Manualslib.com manuals search engine SCHEMATIC WIRING DIAGRAM POWER SUPPLY : 460-3-60 (Four compressor units) APPLICABLE ON MODELS: CNX2M00 - CNX2M40 TO ATB 2 LEGEND 1 SWITCHING CONTACTS FROM THERMOSTAT OR DDC (FIELD INSTALLATION) TRANS1 (75VA) LVTB COM 230V ATB R 15 ATB 24V 17 C AHU MOTOR CONTROL (OPTIONAL CONNECTION) BMR (OPTIONAL CONNECTION) G STG1 COOLING YR1 Y1 STG2 COOLING YR2 Y2 STG3 COOLING YR3 Y3 STG4 COOLING YR4 Y4 ATB 2 ATB TO ATB 17 TO ATB 15 1 24V AC SSPS3 8C JP5C HPS3 10C (CB3A-1) JP4C OLR5-1A OLR7-1A A2 (CB-3) A3 (OL-3) 64C 9C AO4 A4 (HPS-3) P A5 SSPS4 8D JP5D HPS4 PE A1 (SSPS-3) 23C 10D (CB4A-1) JP4D OLR6-1A OLR8-1A AO3 A6 (SSPS-4) A7 (CB-4) 23D 64D A8 (OL-4) 9D A9 (HPS-4) P AO2 AO1 A10 A11 A12 A13 YR3-1A 71C YR4-1A 71D A15 (COOLING STAGE 4) A18 A19 (AUX. ALARM COMP3) A20 (AUX. ALARM COMP4) AC (DIGITAL COM) 1C R1(DIG OUT) 1O 2C R2(DIG OUT) 2O 3C R3(DIG OUT) 3O 4C R4(DIG OUT) 4O COMP3 CONTACTOR 3C (SEE COMP. POWER & CONTROL CONNECTION, SHEET 1 0F 3) PDS3 14C COMP3 CAPACITY UNLOADER SOLENOID R5(DIG OUT) 5O 6C R6(DIG OUT) 6O 7C R7(DIG OUT) 8C R8(DIG OUT) C R9(DIG OUT) 9NO R10(DIG OUT) 10NO 7O COMP4 PUMP DOWN SOLENOID UL4-2 14D CC5-1A 15C 15D 8NO R11(DIG OUT) 11NO R12(DIG OUT) 12NO R13(DIG OUT) 13NO R14(DIG OUT) 14NO R15(DIG OUT) 15NO R16(DIG OUT) 16NO 17C R17(DIG OUT) 17NO 18C R18(DIG OUT) 18NO - S1 (A5-SP1) + ST1 SH SH D1 (A6-DP1) T.OUT (SEE COMP. POWER & CONTROL CONNECTION, SHEET 1 0F 3) PDS4 5C C COMP4 CONTACTOR 3D + COMP4 CAPACITY UNLOADER SOLENOID 16C UL3-4 16D UL4-4 REFER FAN MOTOR CONTROL CONNECTION (SYSTEM 3) (SHEET 1 OF 3) REFER FAN MOTOR CONTROL CONNECTION (SYSTEM 4) (SHEET 1 OF 3) SPT3 28C 29C DPT3 30C + SH 31C + SH SH COMP3 SUCTION PRESSURE TRANSDUCER COMP3 DISCHARGE PRESSURE TRANSDUCER + SH S2 (A8-SP2) TIN + D2 (A9-DP2) + SPT4 28D 29D DPT4 30D 31D SH + SH + COMP4 SUCTION PRESSURE TRANSDUCER COMP4 DISCHARGE PRESSURE TRANSDUCER SH O2 (A10-OP2) DIP SERIAL CABLE + 1 2 3 4 GND 23 Downloaded from www.Manualslib.com manuals search engine NOTES 1. ANY WIRE REPLACEMENT SHOULD BE OF THE 900C OR ITS EQUIVALENT. 2. USE COPPER CONDUCTOR WIRES ONLY. 3. COMPRESSORS ARE PROVIDED WITH INTERNAL LINE BREAK OR SSPS FOR THERMAL PROTECTION. 4. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER TO BE PROVIDED BY END USER WITH RATING AS RECOMMENDED BY ZAMIL. + 5. USE DISCONNECT TAB OR SPLICE ONLY WHERE- EVER REQUIRED FOR EXTENSION OF ORIGINAL WIRE. 6. POWER MUST BE SUPPLIED TO CRANKCASE HEATER FOR MINIMUM OF 12 HOURS PRIOR TO SYSTEM START UP. IF POWER IS OFF 6 HOURS OR MORE, CRANKCASE HEATER MUST BE ON FOR 12 HOURS BEFORE OPERATING THE SYSTEM. FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN COMPRESSOR DAMAGE. O1 (A7-OP1) ST2 (A1-ST1) SH X52 (50% UNLOADER SOLENOID) CC6-1A COMMON FAULT INDICATION (VOLT-FREE CONTACT) 8NC ON COMPRESSOR FUSE FAN MOTOR (CONDENSER) FAN MOTOR CONTACTOR HIGH PRESSURE SWITCH HIGH VOLTAGE TERMINAL BLOCK JUMPER LINE 1 LINE 2 LINE 3 LUG GROUND MOTHER BOARD OVER LOAD RELAY SOLID STATE PROTECTIVE SYSTEM TRANSFORMER FAN MOTOR (PROTECTION) THERMAL CONTACT COMPRESSOR UNLOADER SOLENOID UNDER VOLTAGE MONITOR COOLING RELAY FIELD WIRING DISCONNECT TAB - 1/4" SPLICE-CLOSED END TERMINAL BLOCK OR TERMINATION POINT JUNCTION OF WIRES CROSSING OF WIRES, NO CONNECTION EARTHING/GROUND COMP3 PUMP DOWN SOLENOID UL3-2 (50% UNLOADER SOLENOID) X53 COMP/C F FM FMC HPS HVTB JP L1 L2 L3 LUG MB OLR SSPS TRANS TK/TOP UL UVM YR + A17 TO MASTER BOARD MB AIR HANDLING UNIT AUXILIARY TERMINAL BLOCK BLOWER MOTOR RELAY COMPRESSOR CONTACTOR AUXILIARY CONTACT CIRCUIT BREAKER CRANKCASE HEATER ___ A14 (COOLING STAGE 3) A16 S1 AHU ATB BMR CC CCA CB C. HTR TYPICAL HIGH AND LOW VOLTAGE FIELD WIRING CONNECTIONS 17 1 (REMOVE JP6) 67 20 2 1 (REMOVE JP7) (REMOVE JP7) 52 24 Downloaded from www.Manualslib.com manuals search engine RIGGING INSTRUCTIONS ATTENTION TO RIGGERS Hook rigging sling thru holes in base rail, as shown below. Holes in base rail are centered around the unit center of gravity. Center of gravity is not unit center line. Ensure center of gravity aligns with the main lifting point before lifting. Use spreader bar when rigging, to prevent the slings from damaging the unit. CAUTION All panels should be in place when rigging. Care must be taken to avoid damage to the coils during handling. Insert packing material between coils & slings as necessary. MODELS: CNX150 - CNX840 MODELS: CNXM00 - CNX2M00 MODELS: CNX2M40 25 Downloaded from www.Manualslib.com manuals search engine LOAD DISTRIBUTION, kg. (ALUMINUM CONDENSER COIL) MODEL No. R1 R2 R3 R4 R5 R6 R7 R8 R9 R10 CNX150 200 200 200 200 - - - - - - CNX220 231 231 231 231 - - - - - - CNX240 245 245 245 245 - - - - - - CNX300 265 265 265 265 - - CNX360 228 228 232 232 204 204 - - - - CNX420 240 240 244 244 216 216 - - - - CNX480 233 233 273 273 258 258 - - - - CNX540 245 245 285 285 270 270 - - CNX600 258 258 298 298 282 282 - - - - CNX720 272 272 303 303 276 276 199 199 - - CNX840 272 272 303 303 276 276 199 199 - - CNXM00 655 486 540 600 - - - - - - CNXM10 675 508 560 620 - - - - - - CNXM20 807 641 692 752 - - - - - - CNXM40 558 558 533 533 523 523 727 727 CNXM60 674 674 649 649 639 639 CNX2M00 591 591 536 536 531 531 526 526 CNX2M40 822 822 742 742 737 737 732 732 LOAD DISTRIBUTION, kg. (COPPER CONDENSER COIL) MODEL No. R1 R2 R3 R4 R5 R6 R7 R8 R9 R10 CNX150 225 225 225 225 - - - - - - CNX220 256 256 256 256 - - - - - - CNX240 270 270 270 270 - - - - - - CNX300 290 290 290 290 - - CNX360 253 253 257 257 229 229 - - - - CNX420 268 268 272 272 244 244 - - - - CNX480 266 266 306 306 291 291 - - - - CNX540 278 278 318 318 303 303 - - CNX600 295 295 335 335 319 319 - - - - CNX720 304 304 335 335 308 308 232 232 - - CNX840 304 304 335 335 308 308 232 232 - - CNXM00 721 552 606 666 - - - - - - CNXM10 741 574 626 686 - - - - - - CNXM20 903 737 788 848 - - - - - - CNXM40 609 609 584 584 574 574 CNXM60 749 749 724 724 714 714 CNX2M00 661 661 606 606 601 601 596 596 CNX2M40 888 888 808 808 803 803 798 798 793 793 R1 R2 R1 R3 R5 R1 R3 R5 R7 R1 R3 R5 R7 R9 R3 R4 R2 R4 R6 R2 R4 R6 R8 R2 R4 R6 R8 R10 26 Downloaded from www.Manualslib.com manuals search engine INSTALLATION INSTRUCTIONS GENERAL The complete shipment should be inspected for damage. Any damage visible at the time of delivery should be noted on the shipment invoice. These units are shipped completely assembled and wired. Units require interconnecting piping (AHU), external power, thermostat wiring, condensate drain piping and ducting as applicable. Size of unit for an installation should be based on a heat load calculation made according to applicable standards. Units must also be installed in accordance with regulations of the "National Fire Protection Association" and local electrical codes. Where local regulations vary with instruction furnished, installer should adhere to local standards. Prepare your concrete pad or steel stand as applicable. Remove shipping protective covers and wooden crating and lift unit from base and place in position with necessary applicable vibration isolators. Compressors are already charged with the required amount of lubricant. There is no need to charge in the field. Make sure that no air & moisture enter the system as easter oil are hygroscopic in nature. Equipment must be installed so as to allow for service access and air circulation in accordance with these instructions and other Zamil publications for the specific equipment being installed. These units are charged with ozone friendly R-134a refrigerant. LOCATION OF UNIT When selecting the location for the unit, the following points should be kept in mind: 1. Provisions for a concrete slab which will allow for minimum clearance from building or structures 2. That the terrain allows for drainage away from the unit. 3. If the unit is to be roof mounted, inspect the roof for load bearing capacity. The roof should have sufficient structural strength to carry the weight of the unit. 4. Availability of electric power. 5. Position the unit to provide for unrestricted air circulation and to prevent any possibility of air recirculation. 6. Check minimum clearances required for your unit, with regard to walls, or other obstructions. 7. Air cooled equipment should not be installed under low structural overhangs which can cause condenser air recirculation or restriction. 8. Care should be taken to prevent air from other sources from entering condenser, if this air is at a high temperature. REFRIGERANT PIPING CONNECTIONS Piping connections: Outdoor units should be connected to indoor units using field-supplied piping of refrigerant grade and correct size. The liquid and suction line diameters can be determined from the physical data table. Outdoor unit connected to matching Zamil indoor unit: Outdoor unit contain adequate system refrigerant charge for operating with matched indoor unit (as per corresponding cooling capacity table) and when connected with up to 25 feet (7.62 m) of field-supplied piping. Sweat connection: Units are provided with service valves and are ready for brazing. After wrapping the service valve with a wet cloth, the piping set can be brazed to service valve using either silver rod or silfos rod brazing materials. LEAK TESTING & REFRIGERANT CHARGING Leak test: Leak can occur from joints or fittings that are improperly brazed/connected during installation of indoor and outdoor units. The installer should leak test the indoor unit & associated field supplied refrigerant piping, then the outdoor unit, each separately using electronic freon detector and/or soap bubbles. Refrigerant Charging: (To be used for system having a holding charge and to compensate for length of liquid line). 1. When system wired, piped and evacuated, the unit is ready for refrigerant charging. All charging lines and manifolds must be purged with refrigerant vapor prior to admitting refrigerant into the system to prevent contamination system with non-condensable. 27 Downloaded from www.Manualslib.com manuals search engine 2. It is important to first determine the amount of refrigerant required for the system, the unit nameplate normally identify the weight of the refrigerant required. 3. The refrigerant should be added in small amounts allowing sufficient time for the unit pressure to equalize each time. WIRING All wiring must comply with the "National Electric Code" and local electrical standards. The power supply, voltage, frequency and phase must coincide with the unit nameplate. Power wiring to the equipment must be adequately sized for maximum ampacity as shown on unit name plate. The unit wiring diagram, completely illustrates the internal wiring and field connection needed for power supply and control wiring. The power supply should be run through the sized shielded cable or rigid conduit and through a separate fused disconnect switch/circuit breaker. For control wiring, use approved thermostat wire (minimum 18 gauge). Never use telephone wire for this purpose. A sized circuit breaker/fused disconnect switch should be located adjacent to the unit for safety & servicing purposes. Wiring connection to the unit must have insulation suitable for temperatures of a minimum of 600C. Minimum circuit ampacity for each model is shown on the name plate and product catalog. Equipment wiring diagram should be examined and thoroughly understood before field wiring connections are made. Power supply should be checked to be certain that supply voltage agrees with equipment nameplate. Serious damage to compressors and motors can occur, if improper voltage is applied. START-UP INSPECTION & CHECK LIST After the installation is completed in all respect, the following points should be covered before the system is switched on for operation. 1. Remove or loosen shipping retainers under motor compressors. Make sure the hold down nuts on spring mounted compressors are not touching the compressor feet. 2. Make sure all electrical fasteners/connections are tight and clean. 3. All controls are set according to manufacturer's instructions (low & high pressure switch, pump down pressure switch, fan cycling switch, etc...) 4. Make sure all valves are open (compressor suction & discharge service valves, liquid line, etc.). 5. Follow all the instructions from the warning tags and stickers. 6. Compressor crankcase heater should be energized for 12 hours (special attention should be taken to disable compressor contactor before energizing the unit fitted with pump down controls. If not, compressor may operate for few minutes to pumpdown the system, even the thermostat is OFF). 7. Thorough inspection on evaporator coil, condenser coil and other components for any physical damage. 8. Expansion valve bulb is strapped properly at correct location. 9. Circuit breaker/fused disconnect switch. 10. Blower fan belt is properly tightened and pulleys are properly aligned. 11. Blower fan & condenser fans are at correct rotation and their mountings are properly tightened. 12. All refrigerant service valve caps are installed. 13. All piping, piping insulation and piping supports are properly installed. 14. Thermostat is the right one and installed properly. 15. Duct work and accessories (check the following list and select whichever applicable to each jobs). • Flexible Connection • Air Filters Clean • Air Filter Access Door Gasket • Sound Attenuators (If Applicable) • Fresh Air Intake • Ductwork Caulking Inside/Outside Building • Ductwork Supports Inside/Outside Building 28 Downloaded from www.Manualslib.com manuals search engine • Duct Leakage Inside/Outside Building • Volume Dampers • Volume Damper Access Doors • Fire Dampers • Fire Damper Access Doors • Transfer Grilles/Door Grilles • Duct Insulation/Liner • Diffusers/Grilles • Duct Humidistat • Filter flag CHECK-OUT & OPERATIONAL START-UP PROCEDURE After the completion of inspection and check list, the following points should be covered before system is placed in operation. 1. Connect the manifold gauge to suction & discharge line service valves. Prepare recommended instruments for checking Voltage, Amps, RPM, CFM, static pressure, etc. 2. Start the blower fan and condenser fan. Check the amperage against the nameplate ampere. 3. Start the compressor and observe the following points (on multiple compressor units, it is highly recommended to start the compressors one by one to achieve careful observation for each compressor). (a) Check compressor discharge and suction pressures. If not within system design limits, determine why and take corrective action. (b) Check liquid line sight glass and expansion valve operation. If there are indications that more refrigerant is required, leak test all connections and system components and repair any leaks before adding refrigerant. (c) Observe oil level in compressor crankcase sight glass (if available) and add oil as necessary to bring to recommended oil level. All compressors are charged with somewhat greater than the normal oil level required for adequate lubrication, in order to provide some allowance for oil which will be circulating in the system during operation. Depending on the system design, the amount of oil in the system at the time of compressor installation, oil lost due to leakage, etc., it may be necessary either to add or remove oil from a system any time it is first placed in operation with a different compressor. An abnormally low oil level may result in a loss of lubrication; while an excessively high oil level may result in oil slugging and possible damage to the compressor valves or excessive oil circulation. The oil level may vary considerably on initial start-up if liquid refrigerant is present in the crankcase, and the oil level should be checked with the compressor running after having reached a stabilized condition. (d) Thermostatic expansion valves must be checked for proper superheat settings. Recommended superheat is 150F to 200F. (e) Using suitable instruments, carefully check line voltage and amperage at the compressor terminals. Voltage must be within ±10% of that indicated on the compressor nameplate. If high or low voltage is indicated, notify the power company. The current normally should not exceed 110% of the nameplate rating. If amperage draw is excessive, immediately determine the cause and take corrective action. On three phase compressor motors, check to see that a balanced load is drawn by each phase. (f) Carry out any necessary tests, recording airflow rates, entering/leaving temperatures, sound levels, outdoor temperatures, supply airflow rates in occupied spaces and any other specified parameters. 29 Downloaded from www.Manualslib.com manuals search engine ELECTRICAL ELECTRIC POWER SUPPLY All wiring should be in accordance with National Electric Code and local standards. Before making an installation, check the electric power supply. The power supply must be of the same characteristics as that on the nameplate. Normally the wire size used establishes the circuits maximum permissible load. For example a number 12 wire circuit is considered to be a 20 ampere circuit and is protected by a 20 ampere fuse. The unit amperage nameplate rating should not exceed 80% of the circuit rating, 16 amperes. When identifying electrical trouble in any unit, check the power supply at the main disconnect switch and the unit. A high or low voltage condition may prevent the unit from starting, or if the unit is running, compressor can cut-off automatically on the motor overload. On some installations, the voltage may be entirely adequate when tested, but may drop or surge some time later due to increase or decrease of load on the power line. This condition may be repeated daily at the same hour. When this condition is suspected, make arrangements with the local power supplier to place a recording voltmeter on the line to check and correct the erratic voltage conditions. The voltage drop should not be more or less than 10% of the units rated voltage. If the voltage at the meter is correct, but the voltage at the unit fluctuates 10% or more, the branch circuit is not adequate. UNBALANCED VOLTAGE Unbalanced voltage on a three phase circuit may be the source of electrical trouble. If balanced supply voltages are not always maintained, so with the three line currents will not be equal. Unbalanced voltage on a three phase compressor motor may overheat and trip the motor on external or internal current sensing motor protector, whichever one is provided. To determine that an unbalanced voltage condition exists, the supply voltage at the main disconnect switch and at the unit disconnect switch should be measured. Voltage unbalance is calculated as follows. The percentage of voltage unbalance equals one hundred times the ratio of the Maximum Voltage Deviation from the Average Voltage, and the Average Voltage. Voltage unbalance, % = 100 x Maximum voltage deviation from average voltage Average voltage The percentage increase in temperature rise in a phase winding resulting from voltage unbalance will be approximately two times the square of the voltage unbalance. Because of the unbalanced voltage condition in a three phase circuit, it is possible that one phase winding in the compressor motor may be over-heated while the other have a temperature within normal limits. Where unbalanced voltage on a three phase circuit exists, the power company should be notified of such unbalance to determine, if the situation can be corrected. A common source of unbalanced voltage on a three phase circuit is a single phase load between two of the three phases. A large lighting or heating circuit connection to one phase of a three phase circuit can easily cause sufficient variations in motor currents to endanger the motor. Interchange the single phase loads to equally divide the entire loads among the three phases. Balance the supply voltage as evenly as possible. Unless the unbalanced voltage condition can be corrected, the only way to insure motor safety is to be sure that the protectors are in the high current phase when using two leg protection, or to use protectors in all three legs. 30 Downloaded from www.Manualslib.com manuals search engine MOTOR CONTACTOR The motor controller (contactor) is a load current carrying device which makes and breaks to start and stop the compressor motor. The magnetic coil of the controller is energized to make and break the contactor contacts. Frequently, motor contactors are subjected to quick cycling due to various causes. This may cause burned and/or sticking contacts and can cause a compressor motor failure, even though the motor overload protectors trip and open the control circuit. FAN MOTOR The condenser fan motor is a single speed electrical motor with ball bearings, protected with an automatic reset internal overload. CRANKCASE HEATERS The function of the crankcase heater is to hold the compressor oil reservoir at a temperature higher than the coldest part of the system. The low wattage heaters are energize continuously and it is not necessary to have them de-energize when the compressor is operating. Power must be supplied to crankcase heater for minimum of 12 hours prior to system start up. If power is off 6 hours or more, crankcase heater must be on for 12 hours before operating the system. Failure to follow these instructions may result in compressor damage. Crankcase heaters are effective to retard migration of liquid refrigerant to the crankcase during off cycle. But they are not a remedy for slugging or flood back due to liquid refrigerant accumulating in a trapped suction line, improper piping practice, over feeding to the evaporator, leaking solenoid valve, etc. In some cases where migration of refrigerant to the crankcase occurred due to long storage time, shutdown period, defective components, etc. The crankcase heater may be ineffective. Such cases may be easily observed by high oil level and cold crankcase. In these cases, it is highly recommended to front seat or close both suction and discharge service valves of the compressor and release all liquid refrigerant from the compressor. The liquid refrigerant dilutes the oil in the crankcase and the refrigerant rich oil will be pumped to the rods and the bearings through the crankshaft. As the refrigerant boils off, there will not be enough oil for sufficient lubrication at the bearings furthest from the oil pump. The center and rear bearings may seize or may wear enough to allow the rotor to drop and drag on the stator causing it to short. Also the liquid refrigerant washes the oil off the pistons and cylinders during the suction stroke causing them to wear during the compression stroke. When the crankcase is filled with liquid refrigerant and the compressor starts severe agitation, oil foaming etc. will cause major damage to the compressor. Periodic checking for proper operation of crankcase heater is highly recommended. LUBE OIL PROTECTION CONTROL Pressure lubricated refrigeration compressors require a pressure protector in the event of an oil pressure failure. The lube oil pressure protection control is factory set conforming to compressor manufacturer’s specification. The control measures the net oil pressure available to circulate oil through the lubrication system. The positive displacement oil pump circulates the refrigerant oil through the lubrication system. Since the oil pump is connected directly to the compressor crankcase, the inlet pressure to the oil pump will always be the crankcase pressure. The oil pump outlet pressure will be the crankcase pressure plus the oil pump pressure. Therefore, net oil pump pressure will always be the pump outlet pressure minus the crankcase pressure. The net oil pump pressure is sensed through a pressure transducer sending analogue signals to the unit’s microprocessor board. The control is set to trip or stop the compressor when oil differential pressure goes down at a pre-set level and time delay setting. Trip settings for low oil pressure and time delay can be changed in the unit’s controller. Factory set values for low oil pressure trip is at 30 psi after a time delay of 180 seconds. VOLTAGE MONITOR This device protects the motors in the unit from faults such as; under or over voltage, unbalance & phase reversal of the power supply. When the device sensed such faults, it will cut-off the supply in the control circuit thereby cutting off power to the motors. The voltage monitor will re-set automatically when power is brought back to it’s normal conditions. LINE VOLTAGE RANGE 190 - 480 VAC TRIP & RE-SET VOLTAGE (% OF SET POINT) UNDER VOLTAGE PHASE IMBALANCE RE-SET TRIP RE-SET TRIP RE-SET 90% 93% 110% 107% 6% 4.5% 31 Downloaded from www.Manualslib.com manuals search engine OVER VOLTAGE TRIP REFRIGERATION COMPRESSOR Scroll compressors are used as standard for models CNX150 - CNX300 and semi-hermetic reciprocating compressors are standard for models CNX360 - CNX2M00 except for model CNX2M40 available with semi-hermetic compact screw compressors. All compressors are conforming to ARI 540. The compressors are equipped with internal motor protection; factory installed crankcase heater and rubber vibration isolators for quiet and efficient operation. As an option, semihermetic compressor can be fixed on anti vibration mounting (spring type) along with suction & discharge line vibration eliminators. Oil pressure control is provided on units with semi-hermetic compressor only. Each compressor has lock-out devices to protect it from short cycling when tripped by safety controls. Each compressor has separate condenser coil with safety controls. Sight glass and filter dryer are standard for all models. Semi-hermetic Compressor: These Semi hermetic reciprocating compressors are accessible –hermetic type. Compressor and motor are enclosed in a hermetically sealed housing, with out shaft seal. The compressors are equipped with an oil sight glass through which the oil quantity and its conditions in the crankcase can be observed. These compressors can be disassembled in the field for service. Refrigerant-cooled motor –compressors have an oil pressure lubrication system. This system is supplied by a positive displacement oil pump, working in either direction. It is protected by a screen and is made accessible for quick oil pressure checking by a Schrader check valve. The use of oil pressure control safeguards the lubrication system. These compressors can be provided with capacity control (optional). The use of unloading provides optimal part load capacities. Semi-hermetic compact twin screw Compressor: All compressors are compact semi-hermetic twin screw of the high capacity and efficiency due to its perfect profile form ratio 5:6. Simple and robust construction with slider control valve for capacity unloading, suction/discharge shut-off valves, check valve in discharge gas outlet, oil sight glass, oil fill/drain service valve, directly flanged-on three stage oil separator with long-life fine filter 10 microns mesh size, robust axial bearings in tandem configuration, suction gas filter, internal pressure relief valve and manual lock-out electronic protection system for thermal motor winding temperature, phase reversal, discharge gas temperature protection controls. Scroll Compressors: Scroll Compressors are used in some of these units. The major benefits being: 1. Low Sound Level: Quieter operation because of no dynamic suction and discharge valves action. 2. Low vibration and discharge pulses. 3. High Energy Efficiency: Because of high volumetric efficiency it minimize pressure and heat transfer losses. 4. High Capacity: Due to its high mass flow and high compression ratios. 5. High Durability: With its robust design, few moving parts, low motor strains, large internal volume for liquid handling makes this compressor highly reliable. 6. High Charge Limit: Therefore, lower applied costs as no suction accumulator required, no need for pump down system and check valve in discharge line. Low capacity can be caused by inefficient compressor, that is, the compressor does not pump sufficient quantity of refrigerant, even though a full charge is available in the system. Electrical and mechanical tests should be performed to determine if the compressor is defective. If the compressor is found to be all right but the electrical components are defective, remove and replace the defective electrical components only. Below are some tests that should be performed on the compressor to determine, if the compressor is defective. 1. Test compressor motor winding for ground. 2. Test compressor motor windings for continuity. 3. Test that compressor motor will run both without a load and under a load. 4. Test the current or ampere drawn. 5. Observe sound level of compressor. To establish that the compressor suction and discharge valves are operating and holding properly, attach gauges to the liquid and suction service valves. "Front seat" the liquid service valve. 32 Downloaded from www.Manualslib.com manuals search engine Start the compressor, allowing it to operate long enough to pump down to approximately 1 PSIG. Shut the compressor off and observe the compound gauge. The gauge pressure may build rapidly. Repeat the pump down process several times observing the gauge pressure each time after the compressor stops. If the gauge pressure builds rapidly each time after the compressor stops, it indicates that the compressor discharge valves are not holding and refrigerant is leaking from the high side to the low side of the compressor. To check the suction valves, assuming that the discharge valves are holding, allow the compressor to operate long enough to pump down the system to approximately 10 inches of vacuum. If the compressor required longer time to accomplish this, then the suction valves are not holding and the compressor should be changed out as it is defective. MOTOR COMPRESSOR BURN OUT PROCEDURE The extent of the contamination in a system will indicate the amount of clean-up necessary. If a compressor had burned out, the following method of clean-up is recommended: 1. Discharge the refrigerant from the system. 2. Replace the inoperative compressor. 3. Clean up the system thoroughly and remove all the contaminations. 4. Install a system cleaner or filter drier in the suction line and replace the liquid line filter drier. 5. Connect a vacuum pump to both the low and the high side of the system to remove air and other non-condensables from the system. 6. Allow the vacuum pump to operate until a pressure of 500 microns is achieved. 7. Recharge the system and allow it to operate 8 to 12 hours. 8. Take an oil sample and test for acidity. If the first acidity test shows that the acid content is below the safe level, as indicated in the test kit instructions, and the oil is clean, the clean-out system can be removed. If an in-line suction filter drier was used, it can remain in the system provided the pressure drop through the filter does not exceed the manufacturers listed pressure drop. For a badly contaminated system that indicates acid in the oil after 8 to 12 hours of operation, change the suction and liquid line filterdriers and check the system after 24 hours of operation. There are instances where contaminants are discovered in a refrigeration system with the compressor still operational. The same procedure applies, when cleaning these systems, as on a compressor burn-out. SOURCE OF CONTAMINATION There are many ways in which a refrigerant system can become contaminated. The most common of these are as follows: 1. Improper or inadequate dehydration. 2. Wet refrigerant. 3. Wet oil (caution: It is best to purchase oil in small containers and use as needed. Open containers will absorb moisture). 4. Refrigerant leaks (allowing system to operate in a vacuum). 5. Failure to remove oil and moisture after having opened the system for repair. 6. Higher than normal operating temperatures and pressures will cause a breakdown of the oil and refrigerant. 7. Improper use of soldering or brazing flux. HIGH PRESSURE SWITCH A high pressure switch is located in the discharge line and senses the discharge pressure. Should the discharge pressure exceed 350 psig, the control will open turning off the compressor. The control is designed to protect against excessive discharge temperatures and pressures which can cause compressor overheating and damage to the motor windings or valves. 33 Downloaded from www.Manualslib.com manuals search engine Should the control open, it will remain open until the pressure in the system is lowered to 300 psig. Tripping of the high pressure control is normally due to: 1. Restricted condenser coil. 2. Overcharge of refrigerant. 3. Defective fan motor or fan capacitor. 4. Incorrect fan blade. 5. Fan motor internal overload tripping due to lack of lubrication or defective bearings. To test the high pressure control: Install a high pressure gauge to the access valve or the liquid line valve. Disconnect the condenser fan motor. Turn on the unit and observe the pressure on the gauge when the compressor trip off. The pressure should be 350 ± 10 psig. Allow the system to remain off, until the gauge pressure drop to approximately 300 ± 10 psig and reconnect the condenser fan motor. Reset the unit by putting off the thermostat and if the high pressure control has closed, the compressor will restart. LOW PRESSURE PROTECTION To provide protection for the compressor in the event of refrigerant loss, a low pressure sensor is installed in the suction line. The control is preset to open when the suction pressure is 10 ± 5 psig. The contacts of the control will close when the suction pressure rises to 30 ± 5 psig. To test the control for the correct pressure setting, install a compound gauge to the gauge port on the suction service valve. "Front seat" the liquid valve and start the unit. Note the gauge pressure, when the compressor stops. To determine the cut-in pressure, allow the suction pressure to build slowly and observe the gauge pressure at the time when contact closes. A good functional low pressure switch must have both cut-out and cut-in pressure within ± 2 psig. PUMP DOWN CONTROL A pump down control is a solenoid type valve installed in the liquid line to prevent the flow of refrigerant into the evaporator during the off cycle. The valve is mounted in the liquid line refrigerant stream or at other suitable location in the liquid line, but ahead of metering device. Pump down operation takes place as soon as the signal for cooling is switched off. The system’s control closes the liquid line solenoid valve while the compressor is continuously running to pump out a substantial portion of refrigerant in the evaporator. The compressor will shut off when either the suction pressure goes down at a pre-set pressure of 25 psi or at a pre-set timing of 10 seconds whichever is satisfied first. On call for the next cooling cycle, the solenoid valve will get energized ahead of the compressor at a pre-set timing. This is to allow refrigerant to flow in the evaporator and thereby increasing the suction pressure above the low pressure trip setting before the compressor starts. A pump down control may be necessary on an installation where additional protection for the compressor is required to prevent slugging of oil or liquid refrigerant. Below are some conditions which may exist in an installation where additional protection is required: 1. Migration of refrigerant to the compressor during the off cycle. 2. Flooding, at start-up, due to improperly trapped lines or coil. 3. Suction line in slab or beneath ground forming a large trap. 4. Suction line in cool area causing refrigerant to condense during off cycle. 5. Where condensing unit is installed using existing coils and copper lines, or on a new installation where the above said conditions exist that cannot be avoided, which could result in compressor damage. 34 Downloaded from www.Manualslib.com manuals search engine TROUBLE SHOOTING CHART SYMPTOM CAUSES CHECK & CORRECTIVE MEASURE Compressor will not start – no hum. 1. Line disconnect switch open. 1. Close start or disconnect switch. 2. Overload protector tripped. 2. Refer to electrical section. 3. Control stuck in open position. 3. Repair or replace control. 4. Control off due to cold location. 4. Relocate control. 5. Wiring improper or loose. 6. Thermostat defective or improperly installed. 5. Check wiring against diagram. 7. Control circuit open. 8. Burned/open circuit motor winding. Compressor will not start – hums but trips on overload protector. 1. Improperly wired. 1. Check wiring against diagram. 2. Low voltage to unit. 2. Determine reason and correct. 3. Relay failing to close. 3. Determine reason and correct, replace if necessary. 4.Compressor motor has a winding open or shorted. 5. Internal mechanical trouble in compressor. 6. Liquid refrigerant in compressor. 7. High discharge pressure. Compressor starts and runs, but short cycles on overload protector. 6. Replace or relocate. 7. Trace control circuit with wiring diagram and repair. 8. Replace the compressor with all precautions. 1. Additional current passing through overload protector. 2. Low voltage to unit (or unbalanced if three phase). 3. Overload protector defective. 4. Excessive discharge pressure. 5. Suction pressure too high. 4. Replace compressor. 5. Replace compressor. 6. Check crankcase heater. 7. Unequilized pressure in the system. 1.Check wiring diagram. Check for added fan motors, pumps, etc. connected to wrong side of protector. 2. Determine the reason and correct. 3. Check current, replace protector. 4. Check airflow across the condenser coil, restrictions in refrigeration system. 6. Compressor too hot - return gas hot. 5. Check for possibility of misapplication. Use stronger unit. 7.Compressor motor has a winding shorted. 6. Check refrigerant charge (fix leak), add if necessary. 7. Replace compressor. Suction line frosted or sweating. 1. Expansion valve passing excess refrigerant or is oversized. 2. Expansion valve stuck open. 3. Evaporator fan not running. 4. Overcharge of refrigerant. 1.Re-adjust valve or replace with smaller valve. 2. Clean valve of foreign particles, replace if necessary. 3. Determine reason and correct. 4. Correct charge. Liquid line frosted or sweating. 1. Restriction in dehydrator or strainer. 2. Liquid shut-off valve partially closed. 1. Replace part. 2. Open valve fully. 35 Downloaded from www.Manualslib.com manuals search engine TROUBLE SHOOTING CHART SYMPTOM CAUSES CHECK & CORRECTIVE MEASURE Units runs OK, but short cycles on. 1. Overload protector. 2. Thermostat. 3. High pressure cut-out due to: (a) Insufficient air. (b) Overcharge. (c) Air in system. 4. Low pressure cut-out due to: (a) Undercharge. (b) Restriction in expansion device. 1. Check the cause. 2. Differential set too close - widen. 3. (a) Check airflow to the condenser correct. (b) Reduce refrigerant charge. (c) Purge. 4. (a) Fix leak, add refrigerant. (b) Replace device. Unit operates long or continuously. 1. Shortage of refrigerant. 2. Control contacts stuck or frozen closed. 3. Refrigerated or air conditioned space has excessive load or poor insulation. 4. System inadequate to handle load. 5. Evaporator coil iced. 6. Restriction in refrigeration system. 7. Dirty condenser. 8. Filter dirty. 1. Fix leak, add charge. 2. Clean contacts or replace control. 3. Determine the fault and correct. 4. Replace with larger system. 5. Defrost. 6. Determine location and remove. 7. Clean condenser. 8. Clean or replace. Head pressure too high. 1. Refrigerant overcharge. 2. Air in system. 3. Dirty condenser. 4. Malfunction of condenser fan (aircooled). 5. Excessive air temperature entering condenser. 6. Restriction in discharge line. 1. Correct the refrigerant charge. 2. Recharge the system after a thorough triple evacuation. 3. Clean. 4. Check and correct or replace. 5. Check for short circuiting of condenser discharge air, correct it. 6. Correct it. Head pressure too low. 1.Low ambient temperatures (aircooled). 2. Refrigerant shortage. 3. Damaged valves in compressor. 1. Install fan cycling switch, if not provided. Check the setting and operation, if provided. 2. Correct the refrigerant charge after leak testing. 3. Repair/replace the compressor. High suction pressure. 1. High load on evaporator. Load in excess of design conditions. 2. Unbalanced system. Oversized air handling unit matched with under sized condensing unit. 3. Compressor discharge valve leaking. 4. Expansion valve widely open. 5. Improper bulb location or installation. 1. Check the design. 2. Follow manufacturer's guide line and correct it. 3. Repair/replace compressor. 4. Check and adjust the superheat accordingly. 5. Check the expansion valve bulb is properly tighten at correct location. 36 Downloaded from www.Manualslib.com manuals search engine TROUBLE SHOOTING CHART SYMPTOM CAUSES CHECK & CORRECTIVE MEASURE Loss of oil pressure. 1. Loss of oil from compressor due to: (a) Oil trapping in system. (b) Compressor short cycling. (c) Insufficient oil in system. (d) Operation at excessively low suction pressure. 2. Excessive liquid refrigerant returning to compressor. 3. Malfunctioning oil pump. 4. Restriction in oil pump inlet screen. 1. (a) Correct the system piping. (b) Trace out the wiring/defective controls/ components, etc. and correct it. (c) Add oil. (d) Check the superheat of expansion valve and other possible causes like clogged filter, low CFM, iced evaporator etc. and correct it. 2. Check the system for correct super heat and other possible causes like clogged filter, low CFM, iced evaporator, etc. and correct it. 3. Repair or replace it. 4.Clean/replace it (oil change recommended). Space temperature too high. 1. Control setting too high. 2. Expansion valve too small. 3. Cooling coils too small. 4. Inadequate air circulation. 1. Reset control. 2. Use larger valve. 3. Add surface or replace. 4. Improve air movement. Unit noisy. 1. Loose parts or mountings. 2. Tubing rattle. 3. Bent fan blade causing vibration. 4. Fan motor bearings worn. 1. Find and tighten. 2. Tighten the pipe support. 3. Replace blade. 4. Replace motor. 37 Downloaded from www.Manualslib.com manuals search engine PARTS LIST MODEL NUMBER CNX150F CNX220F CNX240F CNX300F CNX360F CNX420F CNX480F CNX540F CNX600F COMPRESSOR 80061402 80061408 80061411 80061414 80069717 80069720 80069723 80069726 80069729 COMPRESSOR CONTACTOR 80009857 80009861 80009861 80009863 80009863 80009865 80009865 80009865 80009867 NIL NIL NIL NIL 80057700 80057700 80057700 80057700 80057700 CAPACITY UNLOADER KITS COND. FAN MOTOR 80022715 80023704 80023703 80023703 80023703 80023703 80023703 80023703 80023703 COND. FAN MOTOR CONTACTOR 80009851 80009851 80009851 80009851 80009851 80009851 80009851 80009851 80009851 FILTER DRYER 80053141 80053142 80053142 80053142 80053142 80053142 80053117 80053117 80053117 FILTER DRYER CORE 80002765 80002765 80002765 80002765 80002765 80002765 80002765 80002765 80002765 SIGHT GLASS 80020000 80020001 80020001 80020001 80020001 80020001 80020004 80020004 80020004 MECHANICAL SHUT OFF VALVE 80070540 80070541 80070541 80070541 80070541 80070541 80070542 80070542 80070542 PUMP DOWN SOLENOID VALVE 80070520 80070521 80070521 80070521 80070521 80070521 80070660 80070660 80070660 PRESSURE GAUGE - SUCTION 80060030 80060030 80060030 80060030 80060030 80060030 80060030 80060030 80060030 PRESSURE GAUGE - DISCHARGE 80060031 80060031 80060031 80060031 80060031 80060031 80060031 80060031 80060031 PRESSURE GAUGE - OIL NIL NIL NIL NIL 80060030 80060030 80060030 80060030 80060030 ADJ. HIGH PRESSURE SWITCH 80055730 80055730 80055730 80055730 80055730 80055730 80055730 80055730 80055730 MICROSMART CONTROLLER 80064645 80064645 80064645 80064645 80064645 80064645 80064645 80064645 80064645 USER INTERFACE CARD 80064650 80064650 80064650 80064650 80064650 80064650 80064650 80064650 80064650 PTC TEMP. SENSOR 80064655 80064655 80064655 80064655 80064655 80064655 80064655 80064655 80064655 RELATIVE PRES. TRANSDUCER -DP 80064656 80064656 80064656 80064656 80064656 80064656 80064656 80064656 80064656 RELATIVE PRES. TRANSDUCER -OIL NIL NIL NIL NIL 80064657 80064657 80064657 80064657 80064657 RELATIVE PRES. TRANSDUCER -SUCTION 80064658 80064658 80064658 80064658 80064658 80064658 80064658 80064658 80064658 MODEL NUMBER CNX720F CNX840F CNXM00F CNXM10F CNXM20F CNXM40F CNXM60F CNX2M00F CNX2M40F COMPRESSOR 80069732 80069732 80069735 80069738 80069729 80069732 80069735 80069735 80068318 COMPRESSOR CONTACTOR 80009868 80009868 80009865 80009865 80009867 80009868 80009865 80009865 80009851 CAPACITY UNLOADER KITS 80057700 80057700 80057700 80057700 80057700 80057700 80057700 80057700 NIL COND. FAN MOTOR 80023703 80023703 80023700 80023700 80023700 80023700 80023700 80023700 80023700 COND. FAN MOTOR CONTACTOR 80009851 80009851 80009851 80009851 80009851 80009851 80009851 80009851 80009851 FILTER DRYER 80053117 80053117 80053113 80053113 80053117 80053117 80053117 80053117 80053113 FILTER DRYER CORE 80002765 80002765 80002765 80002765 80002765 80002765 80002765 80002765 80002765 SIGHT GLASS 80020004 80020004 80020005 80020005 80020004 80020004 80020004 80020004 80020005 MECHANICAL SHUT OFF VALVE 80070542 80070542 80070543 80070543 80070542 80070542 80070542 80070542 80070543 PUMP DOWN SOLENOID VALVE 80070660 80070660 80070509 80070509 80070660 80070660 80070660 80070660 80070509 PRESSURE GAUGE - SUCTION 80060030 80060030 80060030 80060030 80060030 80060030 80060030 80060030 80060030 PRESSURE GAUGE - DISCHARGE 80060031 80060031 80060031 80060031 80060031 80060031 80060031 80060031 80060031 PRESSURE GAUGE - OIL 80060030 80060030 80060030 80060030 80060030 80060030 80060030 80060030 NIL ADJ. HIGH PRESSURE SWITCH 80055730 80055730 80055730 80055730 80055730 80055730 80055730 80055730 80055730 MICROSMART CONTROLLER 80064645 80064645 80064645 80064645 80064645 80064645 80064645 80064645 80064645 USER INTERFACE CARD 80064650 80064650 80064650 80064650 80064650 80064650 80064650 80064650 80064650 PTC TEMP. SENSOR 80064655 80064655 80064655 80064655 80064655 80064655 80064655 80064655 80064655 RELATIVE PRES. TRANSDUCER -DP 80064656 80064656 80064656 80064656 80064656 80064656 80064656 80064656 80064656 RELATIVE PRES. TRANSDUCER -OIL 80064657 80064657 80064657 80064657 80064657 80064657 80064657 80064657 NIL RELATIVE PRES. TRANSDUCER -SUCTION 80064658 80064658 80064658 80064658 80064658 80064658 80064658 80064658 80064658 38 Downloaded from www.Manualslib.com manuals search engine RECOMMENDED SPARE PARTS PERCENTAGE OF SPARE PARTS ITEM ONE YEAR SUPPLY TWO YEAR SUPPLY 100 UNITS 1000 UNITS 100 UNITS 1000 UNITS 2% 1% 3% 2% Condenser fan motor 2 1 3 2 Contactor compressor 2 1 3 2 Contactor fan motors 2 1 3 2 HPS/Sensor/Transducer 2 1 3 2 Expansion valve 1 0.5 2 1 Filter drier 2 1 3 2 Transformer (24V secondary) 1 0.5 2 1 Propeller fan 1 0.5 2 1 Heater-crankcase 3 1 4 2 Compressor NOTE : When ordering spare parts, please quote the complete model number on the unit nameplate. 39 Downloaded from www.Manualslib.com manuals search engine PREVENTIVE MAINTENANCE SCHEDULE FREQUENCY OF MAINTENANCE, MONTHS ITEM 1 Clean air filters & replace if required. 3 6 12 X Clean evaporator coil, drain pan & drain line. X Clean condenser coil. X Check blower belt/tension/wear/crack and replace it, if required. X X Lubricate blower motor/condenser motor (if applicable). Check alignment of pulleys. X Check/clean electrical connections, controls & control box. X X Check motors, blower bearings & lubricate it. Check all electrical control components, wiring terminals etc. for spark, overheating & loose connections. Replace/correct as necessary. X X Check all damper operation. Repair/replace as required. X Check insulation flanking. Repair/replace as required. Check loose bolts/screws & tight as necessary. X Check for rusted/dented/damaged body parts & repair/repaint as necessary. X Check mountings (spring isolator/rubber pads). Repair/replace as necessary. X X Check flexible canvas connections & duct work. Repair/replace as required. Run test all motors and check the amperage, abnormality etc. Run test compressors and check the amperage, noise, oil level, pressure etc. and correct them accordingly. Check the thermostat/control devices for correct operation, calibrate/ re-adjust as required. X X X Apply corrosion inhibitor/contact cleaner as required. X Check all pressures/temperatures as applicable and satisfy the operation & performance. X NOTE: Always observe for abnormal noise or vibration. MAINTENANCE TOOLS/EQUIPMENT REQUIRED STANDARD : Screw drivers (Slot & Phillips), adjustable wrenches, pliers, refrigeration wrenches & socket set wrenches, pulley puller, etc. SPECIAL : Manifold gauge set, R-134a charging cylinder, belt tension checker, leak detector, vacuum pump with electronic gauges, thermometer & hook type ammeter/voltmeter/ohmmeter. 40 Downloaded from www.Manualslib.com manuals search engine MATERIAL SAFETY DATA SHEET SAFETY DATA Toxicity In Contact With Skin REFRIGERANT R134a NIL Liquid splashes or spray may cause freeze burns. Unlikely to be hazardous by skin absorption. Thaw affected areas with water. Remove contaminated clothing carefully - may adhere to skin in case of freeze burns. Wash affected areas with plenty of warm water. If symptoms occur (irritation or blistering), obtain medical attention. In Contact With Eyes Contact with liquid or cold vapor can cause freezing of tissue. Immediately flush with plenty of clean water for at least 15 minutes. Obtain immediate medical attention. Inhalation High concentration of HFC 134a vapor is harmful. It can act as an asphyxiant by limiting available oxygen. Human health effects of overexposure to HFC- 134a vapors by inhalation may include temporary nervous system depression with anaesthetic effects such as dizziness, headache, confusion, incoordination and loss of consciousness. At very high doses, cardiac sensitization to circulating epinephrine-like compounds can result in fatal cardiac arrhythmias. If large concentrations are inhaled, immediately remove to fresh air. Keep person calm. If not breathing, give artificial respiration, perferably mouth to mouth. If breathing is labored, give oxygen. In the event of cardiac arrest, apply external cardiac massage. Do not admininster adreneline or similar sympathominectic drugs as cardiac arrhythmias may result. Get immediate medical attention. Stability Stable under normal conditions. Conditions to Avoid Any source of ignition, such as lighted cigarettes, flames, hot spots, welding. Materials to Avoid Finely divided metals, magnesium and alloys conatining more than 2% magnesium. Can react violently if in contact with alkali earth metals such as sodium, potassium, calcium, barium, powdered aluminium, magnesium and Zinc. Hazardous Halogens, halogen acids and possibly carbonyl halides such as phosgene. These are toxic Decomposition Products and corrosive. Avoid inhalation of high concentrations of vapors. Atmospheric concentrations should be minimized and kept as low as possible. The vapor is heavier than air and collects at low level and in confined areas. Ventilate by extraction at lowest levels. Respiratory Protection Where doubt exists on atmospheric concentration, suitable breathing apparatus should be worn. This should be self-contained or of the long breather type. Storage Store in a cool, well-ventilated area of low fire risk. Keep cylinders dry. Cylinders should be stored upright with valve protection cap in place and firmly secured to prevent falling or being knocked over. Protect cylinders from physical damage; do not drag, roll, slide or drop. Do not allow storage area temperature to exceed 113ºF (45ºC). Keep away from direct sunlight, heat and sources of ignition. Full and empty cylinders should be segregated. Use a first-in, first-out inventory system to prevent full containers from being stored for long periods of time. Protective Clothing Wear overalls, impervious gloves and goggles/face protection. Spill / leak Procedure Ensure suitable personal protective clothing and respiratory protection is worn. Evacuate all personnel from the affected area. Shut off source of leak, if possible without risk. Ventilate spill area, especially low places where heavy vapors might collect. If possible dike and contain spillage. Prevent liquid from entering sewers, sumps or pit areas, since vapor can create suffocating atmosphere. Allow spilled liquid to evaporate. Disposal Best to recover and recycle. If this is not possible, destruction is to be in an approved facility which is equipped to absorb and neutralize acids and other toxic processing products. Fire Extinguishing Data Non-flammable. Containers Fire exposed containers should be kept cool with water sprays. Containers may burst if overheated. Fire Fighting Protective Self-contained breathing apparatus and protective clothing must be worn in fire conditions. Equipment General Precautions 41 Downloaded from www.Manualslib.com manuals search engine PRESSURE TEMPERATURE CHART, R-134a TEMPERATURE (0F) TEMPERATURE (0C) PRESSURE PRESSURE PSIA PSIG Kpa (Absolute) Kpa (Gauge) 0 21.2 6.5 -17.78 146.2 44.9 2 22.2 7.5 -16.67 153.2 51.8 4 23.3 8.6 -15.56 160.4 59.1 6 24.3 9.6 -14.44 167.9 66.6 8 25.5 10.8 -13.33 175.7 74.3 10 26.6 11.9 -12.22 183.7 82.4 12 27.8 13.2 -11.11 192.0 90.7 14 29.1 14.4 -10.00 200.7 99.3 16 30.4 15.7 -8.89 209.6 108.3 18 31.7 17.0 -7.78 218.8 117.5 20 33.1 18.4 -6.67 228.4 127.0 22 34.5 19.8 -5.56 238.2 136.9 24 36.0 21.3 -4.44 248.4 147.1 26 37.5 22.9 -3.33 258.9 157.6 28 39.1 24.4 -2.22 269.8 168.5 30 40.7 26.1 -1.11 281.0 179.7 32 42.4 27.7 0.00 292.6 191.3 34 44.2 29.5 1.11 304.6 203.2 36 45.9 31.3 2.22 316.9 215.5 38 47.8 33.1 3.33 329.6 228.2 40 49.7 35.0 4.44 342.6 241.3 42 51.6 36.9 5.56 356.1 254.8 44 53.7 39.0 6.67 370.0 268.7 46 55.7 41.0 7.78 384.3 283.0 48 57.9 43.2 8.89 399.0 297.7 50 60.0 45.4 10.00 414.1 312.8 52 62.3 47.6 11.11 429.7 328.4 54 64.6 49.9 12.22 445.7 344.4 56 67.0 52.3 13.33 462.2 360.9 58 69.5 54.8 14.44 479.1 377.8 60 72.0 57.3 15.56 496.5 395.2 62 74.6 59.9 16.67 514.4 413.0 64 77.2 62.6 17.78 532.7 431.4 66 80.0 65.3 18.89 551.6 450.2 68 82.8 68.1 20.00 570.9 469.6 70 85.7 71.0 21.11 590.8 489.4 72 88.6 73.9 22.22 611.1 509.8 74 91.6 77.0 23.33 632.0 530.7 76 94.8 80.1 24.44 653.5 552.1 78 97.9 83.2 25.56 675.4 574.1 80 101.2 86.5 26.67 698.0 596.6 82 104.6 89.9 27.78 721.1 619.7 84 108.0 93.3 28.89 744.7 643.4 86 111.5 96.8 29.95 769.0 667.6 88 115.1 100.4 31.11 793.8 692.5 90 118.8 104.1 32.22 819.2 717.9 92 122.6 107.9 33.33 845.3 743.9 94 126.4 111.7 34.44 871.9 770.6 42 Downloaded from www.Manualslib.com manuals search engine PRESSURE TEMPERATURE CHART, R-134a TEMPERATURE (0F) TEMPERATURE (0C) PRESSURE PRESSURE PSIA PSIG Kpa (Absolute) Kpa (Gauge) 96 130.4 115.7 35.56 899.2 797.9 98 134.4 119.7 36.67 927.1 825.8 100 138.6 123.9 37.78 955.7 854.3 102 142.8 128.1 38.89 984.9 883.6 104 147.1 132.4 40.00 1014.8 913.4 106 151.6 136.9 41.11 1045.3 944.0 108 156.1 141.4 42.22 1076.6 975.2 110 160.7 146.0 43.33 1108.5 1007.2 112 165.5 150.8 44.44 1141.2 1039.8 114 170.3 155.6 45.56 1174.5 1073.2 116 175.2 160.6 46.67 1208.6 1107.3 118 180.3 165.6 47.78 1243.4 1142.1 120 185.5 170.8 48.89 1279.0 1177.7 122 190.7 176.0 50.00 1315.3 1214.0 124 196.1 181.4 51.11 1352.4 1251.1 126 201.6 186.9 52.22 1390.3 1288.9 128 207.2 192.5 53.33 1428.9 1327.6 130 212.9 198.2 54.44 1468.4 1367.1 132 218.8 204.1 55.56 1508.7 1407.4 134 224.7 210.0 56.67 1549.8 1448.5 136 230.8 216.1 57.78 1591.7 1490.4 138 237.0 222.3 58.89 1634.5 1533.2 140 243.3 228.6 60.00 1678.2 1576.8 142 249.8 235.1 61.11 1722.7 1621.4 144 256.4 241.7 62.22 1768.1 1666.8 146 263.1 248.4 63.33 1814.4 1713.1 148 269.9 255.2 64.44 1861.6 1760.3 150 276.9 262.2 65.56 1909.8 1808.5 152 284.0 269.3 66.67 1958.9 1857.6 154 291.3 276.6 67.78 2008.9 1907.6 156 298.7 284.0 68.89 2059.9 1958.6 158 306.2 291.5 70.00 2111.9 2010.6 160 313.9 299.2 71.11 2164.9 2063.6 162 321.7 307.1 72.22 2218.9 2117.6 164 329.7 315.0 73.33 2274.0 2172.7 166 337.9 323.2 74.44 2330.1 2228.7 168 346.1 331.5 75.56 2387.2 2285.9 170 354.6 339.9 76.67 2445.4 2344.1 43 Downloaded from www.Manualslib.com manuals search engine