GENERAL INFORMATION: CUSTOMER: CANADIAN ADVANCED MANUFACTURER PURCHASE ORDER SALES ORDER TESTING DATE TRANSFORMER INFORMATION: POWER (KVA): 7793 ago-06-2013 STANDARD CONNECTION GROUP INSPECTOR FREQUENCY (c/seg.) 113 ARTRANS ANSI-C57 Yd1-Dd0 50 SERIAL # NOMINAL SECONDARY VOLT. (V.) NOMINAL SECONDARY CURRENT (A) NOMINAL PRIMARY VOLT. (V.) NOMINAL PRIMARY CURRENT (A) 12127 1853 35,209 400 163,10 VOLTAGE RATIO, POLARITY, ANGULAR SHIFT AND PHASE SEQUENCE TAP CHANGER POSITION C2 TERMINAL H1-H4/x1-x3 H2-H5/x2-x1 H3-H6/x3-x2 1 3,750 3,750 3,750 TAP CHANGER POSITION C2 TERMINAL H1-H4/x1-x3 H2-H5/x2-x1 H3-H6/x3-x2 1 Nominal 2,673 2,673 2,673 1 2 3,597 3,597 3,597 2 2 2,516 2,516 2,516 Connection group TAP CHANGER POSITION C1 3 4 5 3,443 3,289 3,135 3,443 3,289 3,135 3,443 3,289 3,135 Connection group TAP CHANGER POSITION C1 3 4 5 2,363 2,210 2,055 2,363 2,210 2,055 2,363 2,210 2,055 Yd1 6 2,978 2,978 2,978 7 2,824 2,824 2,824 Yd1 6 1,902 1,902 1,902 7 1,748 1,748 1,748 DIELECTRIC TEST - Hi potencial test ATMOSPHERIC PRESSURE TEMPERATURE AIR SPHERES DIAMETER HV/LV + ground LV/HV + ground (mm of Hg.) ('ºC) DENSITY (mm) (kV.) (kV.) 700 28 0,90 100 10 3 DIELECTRIC TEST - Induced voltage test TERMINAL VOLTAGE TIME FREQUENCY LV/HV LV (V.) 800 (sec) 60 Hz 100 INSULATION RESISTANCE Testing TEMPERATURE voltage (kV) ºC. Insulation Resistance (Mohms) HV/LV HV/Ground LV/Ground 5 OHM RESISTANCE MEASUREMENT ON THE SECONDARY WINDINGS Tap changer position C2 TERMINAL H1-H4 H2-H5 H3-H6 1 0,39210 0,38200 0,40650 1 2 0,37550 0,36300 0,37470 Tap changer position C1 3 4 5 0,35910 0,33960 0,31300 0,35400 0,34020 0,32600 0,35210 0,34810 0,31820 Página 1 de 3 6 0,29220 0,29580 0,29080 7 0,28160 0,28140 0,27540 GENERAL INFORMATION: CUSTOMER: CANADIAN ADVANCED Tap changer position C2 TERMINAL H1-H4 H2-H5 H3-H6 TRANSFORMER INFORMATION: 113 SERIAL # 12127 Tap changer position C1 3 4 5 0,23010 0,21370 0,19250 0,23240 0,21470 0,18840 0,23120 0,21500 0,19460 6 0,17290 0,16940 0,16400 7 0,15230 0,14860 0,15190 POWER (KVA): 2 1Nominal 0,27830 0,27500 0,26910 2 0,25040 0,24800 0,24870 Temperature °C Average Resistance (Nominal) 29 Average Resistance at 75 °C 0,27413 0,32190 OHM RESISTANCE MEASUREMENT ON THE PRIMARY WINDINGS TERMINAL RESISTANCE (Ohms) TEMPERATURE ºC X1-X2 0,021300 29 X2-X3 0,213300 29 X3-X1 0,021410 29 AVERAGE RESISTANCE 0,085337 29 0,100206 AT 75ºC SHORT CIRCUIT LOSSES AMPS CIRCUIT DIVISIONS CONSTANT 35,074 35,097 35,075 1 CHANNEL 1 CHANNEL 2 CHANNEL 3 AVERAGE AMPS DIVISIONS CONSTANT 35,074 35,097 35,075 35,082 43,491 42,432 42,904 1,732 POWER CIRCUIT DIVISIONS 722,9 713,3 710,3 WATTMETER 1 WATTMETER 2 WATTMETER 3 CONSTANT 1 TOTAL CORRECTIONS VOLTAGE CIRCUIT AVERAGE TESTING VOLTAGE TEMPERATURE °C. 75,33 73,49 74,31 74,38 30 1,170 CURRENT (K1) 1,0036 INSTRUMENT CONSUMPTION POWER (W) 722,9 713,3 710,3 2146,5 V WINDING RESIST. WIRES RESIST. CONSUMPT (W) 0,1657 203,922425 SHORT CIRCUIT LOSSES (W) SHORT CIRCUIT VOLTAGE @ 75 °C (%) SHORT CIRCUIT LOSSES @ 75°C.(W) 1956,68 4,16 3079,54 NO LOAD LOSSES AMPS CIRCUIT DIVISIONS CHANNEL 1 CHANNEL 2 CHANNEL 3 0,7230 0,5890 0,5710 CONSTANT 1 AVERAGE VOLTAGE CIRCUIT AMPS DIVISIONS 0,7230 0,5890 0,5710 0,6277 400 400 400 POWER CIRCUIT DIVISIONS WATTMETER 1 WATTMETER 2 WATTMETER 3 90,5 88,0 53,8 CONSTANT 1 TOTAL CONSTANT 1 AVERAGE FREQUENCY VOLTAGE (C/SEG.) 400 400 400 400 50 INSTRUMENT CONSUMPTION POWER (W) 90,5 88,0 53,8 232,3 Página 2 de 3 V WINDING RESIST. WIRES RESIST. CONSUMPT (W) 0 NO LOAD LOSSES (W) MAGNETIZING CURRENT (%) 232,3 0,38 GENERAL INFORMATION: CUSTOMER: CANADIAN ADVANCED TRANSFORMER INFORMATION: SERIAL # 113 POWER (KVA): 12127 OIL INSULATION RESISTANCE ( PCB`S FREE) FIRST READING SECOND READING THIRD READING FOURTH READING FIFTH READING >60 kv >60 kv >60 kv >60 kv >60 kv PRESSURE (KG/CM2) TIME (HOURS) 0,5 3 AVERAGE >60 kv LEAK TEST PERIPHERAL INSTRUMENTS TESTS INSTRUMENT OIL LEVEL GAUGE OIL TEMPERATURE GAUGE WINDING TEMPERATURE VACUUM / PRESSURE GAUGE RAPID PRESSURE RELAY NITROGEN FILLING VALVE PRESSURE RELIEF VALVE NO LOAD TAP CHANGER C1 NO LOAD TAP CHANGER C2 RANGE 0 - 120°C 0 - 100°C 76 cm Hg / 1 Kg/cm2 0,5 Kg/cm2 1-7 1-2 STATUS OK OK NOT INCLUDED OK NOT INCLUDED OK OK OK OK APPROVALS In conformity and agreement with observed parameters during the testing process, original and copy are signed by Customer Inspector and ARTRANS representative at ARTRANS Facilities, Acceso Sur 8407 - Carrodilla, Luján de Cuyo, Mendoza ARGENTINA. CUSTOMER INSPECTOR DATE: ago-06-2013 ARTRANS REPRESENTATIVE Página 3 de 3