Transformer Inrush Current Mitigation Concept for Hybrid Transformers BURKARD Johannes Transformer Inrush Current Mitigation Concept for Hybrid Transformers J. Burkard and J. Biela Laboratory for High Power Electronic Systems (HPE) ETH Zurich, Physikstrasse 3, CH-8092 Zurich, Switzerland Email: burkard@hpe.ee.ethz.ch Abstract—Large inrush currents can occur when power transformers are connected to the grid. In the past, a wide range of countermeasures has been developed whereof the application of power electronic converters recently received more attention. With hybrid transformers combining a conventional transformer with a power electronic converter, the elimination of inrush currents can be realized without considerable additional hardware effort. For such hybrid transformers, a novel mitigation procedure is proposed, which is based on the injection of a synchronous core flux before the transformer is connected to the grid. In addition, dedicated demagnetization strategies applicable for grid connected converters with filter elements are presented. The effectiveness of the proposed procedure is verified by comprehensive simulations and a comparison to a conventional method. I. Inrush current mitigation concepts 1 Inrush current damping 2 Optimized closing time Inrush current compensation Shunt VSI Series VSI Resistor Reactors Constant Synchronous preflux preflux HT LFT MV grid VMV 3 LV grid 3 3 MV LV Shunt conv. B DC Aux Series conv. A AC 3 When a power transformer is connected to the grid, a large inrush current could occur due to the saturation of the core. These large inrush currents impair the transformer lifetime, the grid power quality as well as the functionality of grid protection devices. Different concepts to reduce such inrush currents have been developed, which can be subdivided according to the applied mitigation mechanism as shown in Fig. 1. Group : By inserting current limiting elements such as resistors or reactors in series to the transformer windings, a limitation of the inrush current could be obtained [1], [2]. Furthermore, a voltage source inverter (VSI) controlled as a dynamic resistor could be applied [3]. To avoid high conduction losses, the damping elements have to be bypassed during normal operation which requires additional switches. Group : In theory, inrush currents could also be eliminated by connecting the transformer windings of the three phases sequentially to the grid at optimal points in time which are defined by the residual core flux. However, circuit breakers (CBs) with independent drives for each phase as well as the measurement of the residual core flux would be necessary [4]. Furthermore, the scatter of the CB closing time and flux measurement errors deteriorate the effectiveness of this approach [5]. Group : In [6] a VSI is connected in parallel to the transformer windings in order to compensate the inrush current by injecting a current of opposite direction. With this approach, however, excessive currents and mechanical stresses of the transformer windings cannot be avoided. Core flux manipulation 4 Fig. 1: The inrush current mitigation methods can be subdivided into four groups based on the underlying mitigation mechanism. In this paper, the focus is on the synchronous prefluxing concept. I NTRODUCTION EPE'17 ECCE Europe 3 VLV Vser AC DC Back-to-back conv. Fig. 2: Schematic of a HT allowing the control of VLV as well as active and reactive power flow. Group : The last group of mitigation techniques relies on the manipulation of the core flux before the transformer is magnetized. This includes the demagnetization of the core [7] and the injection of a defined constant residual flux by means of a precharged capacitor. For an effective elimination of inrush currents, the injection of a constant preflux must be combined with an optimized grid connection instant (see group ), which entails the mentioned requirements for the CBs [8], [9]. As an alternative solution of group , the application of power electronic converters allows the injection of a sinusoidal preflux whereby inrush currents could be completely avoided. In contrast to the aforementioned methods, this so called synchronous prefluxing method does neither require additional switches nor flux measurements while the effectiveness is independent of the closing time scatter of the CBs. Therefore, the power electronics based synchronous prefluxing method is the most promising solution of the mentioned alternatives. Although the basic operation principle has been studied in the literature, the high additional cost of the converter has prevented a wide practical application so far [10], [11]. For hybrid transformers (HTs), which combine a power electronic converter and a conventional low frequency transformer (LFT) to enhance grid controllability, the implementation of ISBN: 9789075815276 et CFP17850-ART © assigned jointly to the European Power Electronics and Drives Association & the Institute of Electrical and Electronics Engineers (IEEE) P.1 Transformer Inrush Current Mitigation Concept for Hybrid Transformers BURKARD Johannes LFT model (Fig. 5) MV CB LV CB LV load LCL filter Conv. B DC VAux C LFB FB 3 AC Conv. A DC 3 3 VMV 3 MV grid MV 3 LV Aux AC De-/magnetization control External turn-on/off Fig. 3: 3D CAD rendering of a possible assembly of the converter and the LFT. The HT interfaces the 20 kV MV and 400 V LV grids with a calculated total HT system efficiency of 98%. VDC Fig. 4: The simulation model of the HT includes an equivalent circuit of the LFT as detailed in Fig. 5, CBs on both transformer sides, a controller and the shunt connected converter B. Converter A is not required for the inrush current mitigation and is therefore shown in grey. TABLE I: Parameters for the model of the 400 kVA, 20 kV-400 V HT. the synchronous prefluxing technique can be realized without considerable additional effort. Fig. 2 shows a possible configuration of a HT as presented in [12]. The major share of the power is transferred via the LFT whereas the converter is only rated for a fraction of the LFT power (typically 10%). Thus, the high efficiency and robustness of the LFT and the flexibility of the power electronic converter are combined. The back-toback converter of the HT consists of a shunt connected side B and a series connected side A (Fig. 2). Besides the control of the voltage VLV as well as the active and reactive power flow, HTs also allow active filtering and load balancing in order to ensure a high power quality even in the presence of a high share of renewable energy sources. Due to the connection of converter side B to an auxiliary (Aux) winding of the LFT, a direct magnetization of the core is possible. Fig. 3 depicts a 3D CAD rendering of a possible assembly of the converter and the LFT. Further information about the HT concept is available in [12] and [13]. In this paper, a novel inrush current mitigation procedure based on synchronous prefluxing is presented which allows the elimination of inrush currents without considerable additional hardware effort if applied to HTs. After the presentation of the simulation model of the HT in section II, a conventional mitigation method is investigated as a benchmark case in section III. The concept of the synchronous prefluxing technique and the proposed procedure including a novel demagnetization method are explained in section IV. Section V proves the effectiveness of the presented procedure to eliminate inrush currents by comprehensive simulations. II. S IMULATION M ODEL The considerations of this paper are exemplarily carried out for a 400 kVA three-phase HT fed from a 20 kV MV grid, which supplies a radial 400 V LV grid. This HT consists of a 400 kVA LFT combined with a 40 kVA back-to-back converter. The specifications of the HT are given in Tab. I. The simulation model including an equivalent circuit of the LFT is shown in Fig. 4. The controller for the magnetization and demagnetization shown in this figure measures the MV and Aux side transformer voltages VMV and VAux as well as EPE'17 ECCE Europe Parameter Value Sn VMV , VLV , VAux Controllability Sconv , Vser Topology DC-link LFB1 , CFB , fsw 400 kVA 20 kV, 400 V, 28 V, RMS, line-line ±10% of nominal VLV , P and Q 40 kVA, 23 V 2-level VSIs, back-to-back 60 V, 6.8 mF 10 μH, 100 μF, 50 kHz the DC-link voltage VDC and controls converter B as well as the MV and LV grid circuit breakers (MV CB and LV CB). An external turn-on/off signal starts the process which connects and disconnects the HT to and from the grid. Since converter A of the HT does not influence the presented mitigation methods, it is not considered in this model and the load of the LV grid is directly attached to the star-connected LV winding for simplicity. For the demagnetization and magnetization of the transformer core, the DC-link of the converter has to be powered by an external power supply (e.g. a battery) which is represented by the voltage source VDC . Furthermore, an LCLfilter consisting of the boost inductor LFB , the filter capacitor CFB and the Aux side transformer leakage impedance, represented by a magnetic reluctance within the transformer model, is considered (cf. Fig. 4). The LCL-filter is damped by a capacitor-resistor branch in parallel to CFB designed according to [14]. In order to simulate inrush currents, the transformer core is modeled by saturable reluctances with hysteresis. The reluctances Rc,o and Rc,m represent the outer and middle limbs as shown in Fig. 5. The transformer limbs and the associated windings are denoted as 1, 2 and 3 for the left, middle and right limb. Since the residual flux Bres at the beginning of the simulation cannot be directly set with the used simulation software, an initial voltage pulse is applied to the transformer windings to magnetize the core to different flux levels before the inrush mitigation methods are tested. The leakage inductances on the MV, LV and Aux side of the transformer are represented by the reluctances Rσ,MV , Rσ,LV and Rσ,Aux . For validating the transformer model, the MV line currents of phase 1 are given in Fig. 6 for the case that the transformer is connected to the MV grid without and with a residual core flux while the LV ISBN: 9789075815276 et CFP17850-ART © assigned jointly to the European Power Electronics and Drives Association & the Institute of Electrical and Electronics Engineers (IEEE) P.2 Transformer Inrush Current Mitigation Concept for Hybrid Transformers Phase 2 Rı09 Rı09 Rı/9 Rı/9 /9 2 Rc,o Rc,m Rc,o 09 Phase 3 Initial magn. to set Bres Connection of remaining phases Connection of first phase 1 Phase 1 Rı09 B in T Phase 1 BURKARD Johannes 0 Rı/9 Phase 2 -1 Rı$X[ Rı$X[ $X[ Rı$X[ -2 Fig. 5: In the LFT model, the saturable reluctances Rc,o and Rc,m represent the core limbs. The leakage reluctances are modelled by Rσ,MV , Rσ,LV and Rσ,Aux . The windings attached to the left, middle and right limb are denoted as phase 1, 2 and 3. 16 10 20 30 40 50 60 Fig. 7: Prospective (dashed) and actual (solid) flux densities if the phases are energized at the ideal time instants with the ”rapid closing strategy” [4]. After the connection of the first phase, the residual fluxes in the remaining phases are also modified. C ONVENTIONAL I NRUSH M ITIGATION C ONCEPT Inrush currents are caused by core saturation and occur if the residual core flux Φres prior to the magnetization deviates from the ideal DC offset-free prospective flux Φpros defined by the applied winding voltage vwind . To avoid inrush currents, (1) has to be satisfied at the point in time tmag when the winding is connected to the grid. N is the number of turns of the considered transformer winding. 12 IMV,1 / În 0 t in ms III. With res. flux No res. flux Phase 3 8 4 = vwind 0 0.2 0.4 t in s 0.6 0.8 1 Fig. 6: Simulated ratio of the MV line current of phase 1 IMV,1 to the peak value of the nominal current Iˆn for a typical connection of the LFT to the MV grid with and without residual flux. No load is connected to the LV windings. For the simulation with residual flux, an initial voltage pulse is applied to magnetize the core limbs TABLE II: Parameters of the 400 kVA LFT model. Parameter Value Core material Sat. flux density Bsat Rem. flux density Brem Nom. flux density Bn Sat. field strength Hsat Coerc. field strength Hc Core cross sectional area Ac Length of inner & outer limbs Wind. losses MV, LV, Aux Core losses Number of turns Short circuit imp. MV-LV Short circuit imp. MV-Aux Cold rolled grain oriented steel 1.7 T 1.5 T 1.26 T = 0.75 · Bsat 127 A m 40 A m 0.025 m2 0.5 m, 1.2 m 2800 W, 1500 W, 500 W (full load) 600 W NMV = 2858, NLV = 33, NAux = 4 zSC,MV−Aux = 4% zSC,MV−Aux = 6.5% circuit breakers CBLV are open. There, the specifications of the LFT given in Tab. II are used. With the given transformer model, the peak inrush currents are more than 10 times larger than the peak line current during nominal operation Iˆn which is in accordance with amplitudes for inrush currents published in [5] and [15]. EPE'17 ECCE Europe 1 tmag V̂ · cos(ωt) dt (1) Φres = Φpros = N 0 As a benchmark case, the optimized closing time mitigation concept (cf. Fig. 1 ) is analysed in the following. The performance of the proposed inrush current mitigation concept is then compared to this conventional concept in section V. As a first step of the optimized closing time method, the winding attached to the limb with the lowest Φres is connected to the MV grid when the residual and prospective fluxes of this phase are equal, so that no inrush current occurs. Thereby, the flux distribution of the other two limbs is also modified. For the connection of the two remaining phases, the so-called ”rapid closing strategy” is applied in the following. With this strategy, the remaining phases are connected at the next instant when the measured and prospective flux of these phases coincide [4]. Since the optimal connection time tmag depends on Φres , a flux measurement is required which can be achieved by continuously measuring and integrating the winding voltages. In Fig. 7, the waveforms of the prospective and actual transformer flux densities are shown for the ideal case which leads to a magnetization without inrush currents. ! However, the non-ideal measurement of the flux and the closing time scatter of the CBs impede the ideal energization of the transformer, so that the inrush currents cannot be completely avoided. To simulate the performance of this concept including the non-idealities, the same model as described in section II can be used but the converter, the filter and the LV grid are removed. In the considered case, the flux measurement ISBN: 9789075815276 et CFP17850-ART © assigned jointly to the European Power Electronics and Drives Association & the Institute of Electrical and Electronics Engineers (IEEE) P.3 Transformer Inrush Current Mitigation Concept for Hybrid Transformers BURKARD Johannes 4 Initial demagnetization (Fig. 14) Ɏoffset / Ɏn: 10% 8% 6% 4% 2% 0% 1 0 0 0.5 tdelay in ms Turn-on 2 CBs off, Bres= 0 1 1.5 Fig. 8: Simulated inrush currents resulting with the conventional optimized closing time method as a function of the MV CB closing time delay tdelay reassembling closing time scatter. The relative flux measurement uncertainty Φoffset Φn is used as a parameter. uncertainty is exemplarily reproduced by measuring the ideal fluxes of the three limbs and adding flux offsets of +Φoffset and −Φoffset to the ideal measurements of phases 1 and 3. By delaying all MV CB closing signals by tdelay , the worst-case closing time scatter is emulated. The adverse effect of these non-idealities depends on Bres and on the connection instants. For some points on the flux curve, an unprecise closing leads to comparably high differences between the actual and the prospective flux as has been illustrated in [4]. Fig. 8 depicts the resulting inrush currents for the worst-case Bres , closing time delays of 0 ≤ tdelay ≤ 1.5 ms and measurement uncertainties of 0 ≤ Φoffset ≤ 0.1 · Φ̂n . According to [16], CBs specially designed for this mitigation concept achieve a closing time scatter below 1 ms. Hence, inrush currents of up to 2· Iˆn have to be expected if a flux measurement error below 6% is assumed. In comparison to the connection without any inrush mitigation method, the maximum excited currents can be significantly reduced which proves the good performance of this method. However, the CBs require independent drives for each phase and a special mechanical design to minimize closing time scatter. Furthermore, a precise measurement and integration of the MV grid voltage is necessary to indirectly measure the core fluxes. IV. I NRUSH C URRENT M ITIGATION C ONCEPT FOR H YBRID T RANSFORMERS In contrast to methods aiming for a connection at the optimal time instant, the synchronous prefluxing method (cf. Fig. 1 ) induces an AC flux equal to the prospective flux prior to the transformer connection. After prefluxing, the transformer can be connected at any time without exciting inrush currents so that no special CBs with reduced closing time scatter and independent drives for each phase are needed. A flowchart of the proposed mitigation procedure for HTs is shown in Fig. 9. Before the individual steps are detailed in section IV-A and section IV-B, the basic principle is explained EPE'17 ECCE Europe Prefluxing Demagnetization Close MV CB Open MV CB Conv. B off Conv. B on Close LV CB Open LV CB Start HT control Stop HT control Turn-off Iinrush / În 3 Nominal HT operation Fig. 9: Procedure of the proposed inrush current mitigation method. Before the injection of a synchronous flux is possible, a demagnetization of the core is required. If the HT is connected for the first time or after a sudden disconnection, an initial demagnetization as detailed in IV-B2 has to be performed. in the following. At the beginning of the turn-on process, it is assumed that the LFT is in the demagnetized state (Bres = 0). The converter side B of the HT is used to inject a synchronous preflux by modulating a three-phase voltage in phase with the medium voltage grid voltage VMV as will be discussed in section IV-A. Subsequently, the MV CB is closed and the semiconductors of converter B are turned off which results in a commutation of the magnetizing current from the converter to the MV grid. Since (1) is fulfilled, no inrush currents are excited. After closing the LV CB to supply the load, the control of the back-to-back converter can be started which includes synchronizing to the Aux winding voltage with a PLL and generating the required output voltage Vser . When the HT is turned off, the steps are repeated in reversed order. After shutting down the HT control and opening the LV CB, converter B applies a three-phase voltage synchronous to VMV across the Aux windings. By opening the MV CB, the magnetizing current commutates to the converter and a demagnetization is performed resulting in Bres = 0 as will be described in subsection IV-B1. If the HT should be connected to the grid for the first time or after a sudden disconnection, a dedicated demagnetization has to be performed before the prefluxing is started as will be described in subsection IV-B2. A. Synchronous Prefluxing with Power Electronic Converter Fig. 10 shows a prefluxing strategy which is applied at the beginning of the turn-on process when the transformer is in the demagnetized state and all CBs are open (cf. Fig. 9). At time t0 , the converter starts to generate a three-phase voltage in phase with VMV with linearly increasing amplitude which induces a three-phase, DC offset-free flux in the transformer core. At t1 , the winding voltages reach the nominal value and the core flux is identical to the prospective flux so that the MV CBs can be closed without inrush currents at t2 . This ISBN: 9789075815276 et CFP17850-ART © assigned jointly to the European Power Electronics and Drives Association & the Institute of Electrical and Electronics Engineers (IEEE) P.4 Transformer Inrush Current Mitigation Concept for Hybrid Transformers t1 0 -1 H ĭ in p.u. 1 t 0 t -1 H Phase 3 Phase 2 Phase 1 1 t 0 -1 t0 Phase 3 Phase 2 Phase 1 t 0 t2 t1 t0 t1 -1 t2 Fig. 10: Ramp prefluxing concept: Starting from the demagnetized state, the three-phase Aux winding voltage is ramped up to the nominal value whereafter the MV CBs are closed. method is denoted as ”ramp prefluxing” in the following. The slope of the voltage ramp is a compromise between speed and effectiveness. For a fast increase of the voltage amplitude, an accurate prefluxing cannot be ensured since the positive and negative peak flux values differ significantly due to the ramp up. However, for a slow increase, the required time and losses increase. An alternative magnetization strategy denoted as ”sequential prefluxing” is depicted in Fig. 11 and makes use of the threelimb construction of common distribution transformer cores. If a flux is injected in the middle limb of the core, it splits equally to the two outer limbs as long as the core does not saturate. At t0 , the prospective flux of the middle limb is assumed to be zero which coincides with the actual flux since the transformer is demagnetized. During the following quarter period between t0 and t1 , the converter applies v1 = v3 = − 12 v2 to the Aux windings where the amplitude of v2 is equal to the nominal value. At t1 , the actual and prospective fluxes of all phases coincide and the converter applies the nominal voltages to all windings. The MV CBs can be closed without inrush currents at t2 . With this method, the prefluxing is achieved within a quarter of a grid period which results in a very low energy consumption. Due to the considered LCL filter of the back-to-back converter (Fig. 4), oscillations are excited by the steps of the converter output voltage. For typical filter designs, however, the occurring overvoltage does not exceed the winding withstand voltage defined by LFT standards (e.g. IEC 60076-3, [17]). In [18], the effectiveness of the sequential prefluxing strategy is experimentally verified for a UPS system feeding multiple transformers. For both the ramp and the sequential prefluxing method, a measurement of VMV is required for synchronizing the converter output voltage. Due to the comparably low magnetization currents, the voltage drop across the boost inductor LFB can be neglected during prefluxing and a simple open-loop control is sufficient. EPE'17 ECCE Europe 1 ĭ in p.u. V in p.u. t0 B 1 t2 V in p.u. B BURKARD Johannes t0 t1 t2 Fig. 11: Sequential prefluxing concept: Injection of a synchronous preflux by sequentially magnetizing first the middle and then the outer core limbs. The prospective fluxes and voltages are shown in dashed lines. B. Demagnetization with Power Electronic Converters In order to induce a defined synchronous flux in the transformer core during turn-on, the residual flux of each limb has to be known. By demagnetizing the transformer before the prefluxing step, a defined initial state with Bres = 0 is reached without an additional flux measurement. In [7] and [19], a demagnetization method is presented which uses a rectangular voltage source with constantly decreasing period or amplitude to demagnetize the transformer. The current is measured and triggers a reversal of the winding voltage as soon as a predefined current limit is exceeded. For power electronic converters connected to the grid, passive LC or LCL filters are required to comply with EMI standards during nominal operation (Fig. 4). If a converter with such a filter is used to generate the rectangular voltage, the presence of the capacitive filter elements limits the slope of the converter output voltage during the voltage reversal. This reduced slope would further increase the absolute value of the core flux before the zero crossing of the winding voltage is reached. At the beginning of the demagnetization procedure, where the residual flux Φres could be close to the saturation level, the reduced output voltage slope would saturate the core. Considerable magnetization currents through the converter and an inaccurate demagnetization would be the consequence. This prevents the application of this demagnetization method if capacitive filter elements are present as it is the case for the HT. A further limitation of the conventional demagnetization method is that the rectangular voltage is only applied to a single winding even in case of three-phase transformers. As a result, a simultaneous demagnetization of all transformer limbs is not guaranteed. For a more efficient demagnetization, [20] presents the possibility of additionally measuring the core fluxes. However, this requires a very precise continuous measurement and integration of the winding voltages which is difficult to realize for transformers operating under harsh field conditions. Hence, advanced demagnetization methods are required which fulfill the following requirements: ISBN: 9789075815276 et CFP17850-ART © assigned jointly to the European Power Electronics and Drives Association & the Institute of Electrical and Electronics Engineers (IEEE) P.5 Transformer Inrush Current Mitigation Concept for Hybrid Transformers B BURKARD Johannes B 1 1 t2 -1 H ĭ in p.u. 1 t1 t t2 Phase 3 Phase 2 Phase 1 0 -1 H 1 t 0 V in p.u. 0 ĭ in p.u. t1 V in p.u. t0 t Phase 1 Phase 2 Phase 3 t 0 t0 -1 t0 t1 Fig. 12: Ramp demagnetization concept: After the CBs are opened at t0 , the converter continues to apply the nominal three-phase voltage across the Aux winding until t1 after which the amplitude is ramped down to zero and the core is demagnetized at t2 . Besides the winding voltages and the core fluxes, the B-H curve of an arbitrary core limb is depicted. • Effective demagnetization, independent of the time instant of disconnection and of the residual flux. • Step changes of the winding voltage only at low transformer flux levels to avoid core saturation. • Demagnetization of all core limbs considering the interdependency of the core fluxes. • No flux measurement is required. • Fast procedure with low energy consumption. In the following, three new demagnetization strategies which fulfill the mentioned criteria are presented and discussed. 1) Demagnetization After Disconnection: Starting from the normal operation, the transformer flux has to be reduced to zero during the demagnetization step at the end of the turn-off process of the HT (Fig. 9). Consequently, the same principles as for the prefluxing step presented in section IV-A can be applied but in reversed order. Fig. 12 demonstrates the ”ramp demagnetization” strategy. After opening the MV CB at t0 , the converter continues to modulate the three symmetrical voltages across the Aux winding of the transformer until it starts to linearly ramp down the amplitude at t1 . When the amplitude reaches zero at t2 , the semiconductors of the converter are turned off. As for the ramp prefluxing strategy, the slope of the voltage ramp is a compromise between speed and accuracy. With the ”sequential demagnetization” strategy shown in Fig. 13, the converter continues to modulate the nominal three-phase voltage in phase with VMV after opening the MV CB at t0 . At t1 , the voltage across the middle winding v2 is zero whereafter the converter applies v1 = v3 = − 12 v2 to the windings for one quarter period. The transformer is demagnetized at t2 and the semiconductors of the converter are turned off. Since the magnetizing currents of the phases EPE'17 ECCE Europe -1 t2 t0 t1 t2 Fig. 13: Sequential demagnetization concept: After opening the CBs at t0 , the converter continues to modulate the three-phase voltage until v2 = 0 is reached at t1 . For the subsequent quarter period of v2 , the converter applies v1 = v3 = − 12 v2 after which the transformer is demagnetized at t2 . Besides the winding voltages and the core fluxes, the B-H curve of the left core limb (phase 1) is depicted. have to decay to zero after t2 , a minor remagnetization occurs after the disconnection. With this procedure, a demagnetization within a quarter of a grid period is possible which results in low losses. As for the sequential prefluxing method, the voltage steps applied to the outer windings do not occur at flux levels close to saturation so that both the sequential prefluxing and demagnetization strategy are applicable for converters with LC or LCL filters. A measurement of VMV is required for both demagnetization strategies as a reference for the open-loop converter control. 2) Initial Demagnetization: An initial demagnetization has to be performed when the HT is connected to the grid for the first time or after a sudden disconnection for example due to a grid fault (cf. Fig. 9). Consequently, the methods presented in subsection IV-B1 cannot be applied. While the conventional demagnetization procedure applying a rectangular voltage to a winding is only applicable if the converter is coupled to the LFT via a purely inductive filter, the demagnetization method proposed in the following and depicted in Fig. 14 is also applicable if capacitive filter elements are present. The basic principle of this method is illustrated in Fig. 15. At the beginning of the procedure, it is assumed that the transformer is disconnected from the grid and has a residual magnetization Bres = 0. Converter B of the HT is used to apply phase-to-phase voltages VAux,i (i ∈ {1, 2, 3}) with a variable amplitude Vramp and variable offsets ΔVi to the Aux winding system: ⎛ ⎞ ⎛ ⎞ ⎞ ⎛ cos(2π fdemagt) ΔV1 VAux,1 ⎝ VAux,2 ⎠ = Vramp · ⎝ cos(2π fdemagt − 2π ) ⎠ + ⎝ ΔV2 ⎠ 3 VAux,3 ΔV3 cos(2π fdemagt + 2π 3 ) In step the amplitude Vramp of the sinusoidal three-phase voltage is linearly increased (cf. Fig. 14 and Fig. 15). The magnetizing currents of each phase are measured and compared to predefined limits in step . Depending on which limit ISBN: 9789075815276 et CFP17850-ART © assigned jointly to the European Power Electronics and Drives Association & the Institute of Electrical and Electronics Engineers (IEEE) P.6 Transformer Inrush Current Mitigation Concept for Hybrid Transformers Transformer disconnected, Bres 0 With the variable Voffset , the stepwidth of the DC flux reduction can be adjusted. By continuously repeating steps , and , all transformer limbs are gradually demagnetized. If the magnetizing currents of all phases exceed the positive and negative limits within Tdemag , the DC part of the flux has been removed and all offsets ΔVi are set to zero. Thereafter, the sinusoidal voltage is ramped down to zero and the transformer demagnetization is finished (Fig. 14 and Fig. 15 step ). Vramp= ǻV1= ǻV2= ǻV3= 0 Increase Vramp 1 2 Compare currents to limits, All limits exceeded within Tramp determine s1, s2, s3 Calculate and add ǻV1ǻV2ǻV3 3 4 Ramp down Vramp, Set ǻV1 ǻV2 ǻV3 = 0 Transformer demagnetised, Bres= 0 Fig. 14: Procedure of the proposed initial demagnetization method. A converter is used to apply a sinusoidal voltage with increasing amplitude Vramp to the transformer windings (step ). Variable offset voltages ΔVi are added such that always the phase with the highest residual flux is demagnetized (step ) until the DC flux of all transformer limbs is zero. B B Bres 0 B Ilim B Bres= 0 I I -Ilim -Ilim Steps 1 & 2 Ilim Step 3 I -Ilim Ilim Steps 1 & 2 I -Ilim Ilim Step 4 Fig. 15: Principle of the proposed initial demagnetization method. The B-I(H) curve of an arbitrary transformer limb is shown. The amplitude of the sinusoidal voltage is increased until a current limit ±Ilim is exceeded (steps & ). A DC-offset is added to the voltage to reduce the residual flux (step ). When both the upper and lower limits are exceeded within one cycle, the voltage is ramped down (step ). is exceeded, a positive or negative DC offset is added to the sinusoidal voltage of the respective phase for the subsequent 1 in step such that the absolute value period Tdemag = fdemag of the DC flux is reduced. For the following mathematical description, the variables s1 , s2 , s3 ∈ {−1, 0, 1} are introduced which indicate whether the magnetizing current of phase i exceeds the positive (si = 1) or negative (si = −1) current limit. If the current either exceeds no limit or both limits within Tdemag , the respective variable is zero (si = 0). With the variables si , the offset voltages ΔVi are calculated with the offset matrix M according to (2) in step . ⎛ ⎞ ⎛ ΔV1 m11 ⎝ ΔV2 ⎠ = ⎝m21 ΔV3 m31 =M m12 m22 m32 ⎞ ⎛ ⎞ m13 s1 m23 ⎠ · ⎝ s2 ⎠ m33 s3 (2) Since the three voltages VAux,i have to add up to zero, the same must be true for ΔV1 , ΔV2 and ΔV3 for all values of si which is equivalent to ∑3i=1 mij = 0 ( j ∈ {1, 2, 3}). The following offset matrix complies with this requirement and is considered as an example in the following analysis. ⎛ ⎞ 1 −0.5 −0.5 1 −0.5⎠ M = Voffset · ⎝−0.5 −0.5 −0.5 1 EPE'17 ECCE Europe BURKARD Johannes In case of a delta connection of the Aux transformer winding, the magnetizing currents which need to be compared to the limits for this procedure cannot be measured directly. By neglecting the low frequency filter capacitor currents and taking into account that the converter does not excite circulating currents in the transformer, the winding currents can be calculated from the boost inductor currents. With larger values for the parameters Vramp and Voffset , a faster demagnetization with lower losses is possible. However, the accuracy is reduced which could lead to a higher residual flux after the demagnetization. The maximum demagnetization frequency fdemag is defined by the maximum peak-to-peak flux density which is required to exceed both the positive and negative current limits at the transition to step . If the voltage drop across the filter inductor LFB is neglected, the maximum core flux density B̂max which needs to be excited at this transition can be calculated: B̂max (Ilim,outer ) = 1 NAux · Ac π 2 0 max(Vramp ) · cos(2π fdemagt)dt Since the amplitude of the Aux winding voltages Vramp is limited to the DC-link voltage VDC , the demagnetization frequency fdemag has to fulfill (3). fdemag < VDC 2π · NAux · Ac · B̂max (Ilim,outer ) (3) In Fig. 16, the Aux side magnetizing currents and the core flux densities of an exemplary demagnetization with the presented method are shown. There, fdemag = 40 Hz, Vramp = 15 Vs and Voffset = 0.4 V are chosen which results in a maximum residual of Bres < 0.1 · B̂n for all initial residual flux levels after a demagnetization phase of 4 s. Taking into account converter, core and winding losses, a total energy of approximately 2 kJ has to be provided from the DC-link. Due to the shorter flux path of the middle transformer limb compared to the outer limbs, the nominal magnetization current of phase 2 is lower than that of phases 1 and 3. Hence, also the current limit Ilim,middle for phase 2 is lower than the limit Ilim,outer for phases 1 and 3. It has to be noted that this demagnetization strategy could also be applied during the turn-off of the HT as an alternative to the methods described in subsection IV-B1 although this would be unfavorable with respect to losses and duration of the demagnetization. ISBN: 9789075815276 et CFP17850-ART © assigned jointly to the European Power Electronics and Drives Association & the Institute of Electrical and Electronics Engineers (IEEE) P.7 Transformer Inrush Current Mitigation Concept for Hybrid Transformers Repeating steps 1 , 2 and 3 30 Ilim,outer Ilim,middle VMV in kV IAux in A t0 Prefluxing t1 t2 t3 Nominal op.t4 t5 t6 Demagn. t7 Step 4 40 Phase 1 10 BURKARD Johannes Phase 3 Phase 2 0 0 -40 -10 B in T 1 -Ilim,middle -Ilim,outer -30 2.4 Limit exceeded Phase 1 -1 1.6 1 IMV / În B in T 0.8 0 Phase 3 -0.8 -1.6 0 Phase 1 Phase 2 Phase 3 0 -1 0 Phase 2 1 2 t in s 3 4 Fig. 16: Aux winding currents IAux and core flux densities B for an exemplary demagnetization based on the procedure given in Fig. 14. If the magnetizing current exceeds the predefined limit (±Ilim,outer and ±Ilim,middle for the outer and middle core limbs), a DC voltage offset is added to the sinusoidal voltage to push the flux levels towards zero. When all magnetizing currents exceed their positive and negative limits within one period Tdemag , the sinusoidal voltage is ramped down and the transformer is demagnetized. The envelopes of the waveforms are highlighted. V. 0 S IMULATIVE V ERIFICATION OF THE P ROPOSED P ROCEDURE To verify the effectiveness of the proposed inrush mitigation techniques, a simulation of the complete procedure according to Fig. 9 is performed both for the ramp and the sequential prefluxing and demagnetization strategies. The simulations are performed with the simulation model given in Fig. 4 and the parameters given in Tab. I and Tab. II. Fig. 17 shows the waveforms of the MV side voltages VMV and currents IMV as well as the flux density B for the sequential method. Starting from the demagnetized state at t0 , the core is magnetized until t1 by applying the sequential magnetization method shown in Fig. 11. Due to the step in the voltage reference, oscillations of the winding voltages are excited at t0 and t1 . The amplitude and damping of the oscillations highly depend on the chosen filter topology and the damping elements. At t2 , the MV CB and at t3 the LV CB is closed whereupon the nominal operation of the HT starts. The MV CB is closed without noticeable inrush currents. At t4 , the opening of the LV CB terminates the nominal operation. Converter B starts to modulate a three-phase voltage in phase with VMV across the Aux winding and the MV CB is opened at t5 . The sequential demagnetization method as shown in Fig. 13 is performed between t6 and t7 . As for the initial EPE'17 ECCE Europe 0.02 t in s 0.06 0.08 Fig. 17: Simulated voltage, flux density and current waveforms for the procedure shown in Fig. 9 with sequential prefluxing and demagnetization. Starting from the demagnetized state, the sequential prefluxing is performed and the HT starts the normal operation. At the end, the core is demagnetized sequentially. demagnetization procedure presented in subsection IV-B2, the residual magnetization after demagnetization is Bres < 0.1 · B̂n . Since the assumed nominal peak flux is B̂n = 0.75 · Bsat , the core will not saturate if the proposed prefluxing procedure is applied at the subsequent turn-on of the HT with such a low residual flux. With the duration of a quarter of a grid period for the prefluxing and the demagnetization steps, the net energy which must be supplied from the DC-link including converter, core and winding losses is approximately 50 J. In Fig. 18, the same procedure is shown for the ramp prefluxing and demagnetization method. Between t0 and t1 the core is magnetized by applying a voltage with increasing amplitude to the Aux windings. At t2 , the MV CB and at t3 the LV CB is closed whereupon the nominal operation of the HT starts. The MV CB is closed without noticeable inrush currents. At t4 , the opening of the LV CB terminates the nominal operation. Converter B starts to modulate a three-phase voltage in phase with VMV across the Aux winding and the MV CB is opened at t5 . The ramp demagnetization method as shown in Fig. 12 is performed between t6 and t7 by ramping down the voltage applied to the Aux windings. Compared to the first method, this procedure is more time consuming which also reflects in the increased energy supply of 110 J. However, a more accurate demagnetization of Bres < 0.02 · B̂n can be achieved. The simulation results prove the effectiveness of the proposed inrush current mitigation concept. In comparison to the conventional method with the non-idealities explained in section III, ISBN: 9789075815276 et CFP17850-ART © assigned jointly to the European Power Electronics and Drives Association & the Institute of Electrical and Electronics Engineers (IEEE) P.8 Transformer Inrush Current Mitigation Concept for Hybrid Transformers BURKARD Johannes t0 Prefluxing t1 t2 t3 Nominal op.t4 t5 t6 Demagn. t7 R EFERENCES VMV in kV 20 [1] R. Harchandani and R. Kale, “Selection of effective mitigation method for inrush current in power transformers,” Int. Journal of Adv. Techn. in Engineeing and Science, 2014. 0 -20 B in T 1 [2] M. T. Hagh and M. Abapour, “DC reactor type transformer inrush current limiter,” IET Electric Power Applications, 2007. [3] A. Ketabi and A. R. H. Zavareh, “New method for inrush current mitigation using series voltage-source pwm converter for three phase transformer,” in Power Electronics, Drive Systems and Technologies Conference (PEDSTC), 2011. [4] J. H. Brunke and K. J. Frohlich, “Elimination of transformer inrush currents by controlled switching. I. Theoretical considerations,” IEEE Transactions on Power Delivery, 2001. [5] A. Ebner, M. Bosch, and R. Cortesi, “Controlled switching of transformers - effects of closing time scatter and residual flux uncertainty,” in Universities Power Engineering Conference (UPEC), 2008. [6] K. Shinohara, K. Yamamoto, K. Iimori, Y. Minari, O. Sakata, and M. Miyake, “Compensation for Magnetizing Inrush Currents in Transformers Using a PWM Inverter,” Electrical Engineering in Japan, 2002. [7] B. Kovan, F. de Leon, D. Czarkowski, Z. Zabar, and L. Birenbaum, “Mitigation of Inrush Currents in Network Transformers by Reducing the Residual Flux With an Ultra-Low-Frequency Power Source,” IEEE Transactions on Power Delivery, 2011. 0 -1 IMV / În 1 Phase 1 Phase 2 Phase 3 0 -1 0 0.08 t in s 0.16 0.24 Fig. 18: Simulated voltage, flux density and current waveforms for the procedure shown in Fig. 9 with ramp prefluxing and demagnetization. Starting from the demagnetized state, the ramp prefluxing is performed and the HT starts the normal operation. At the end, the core is demagnetized by ramping down the winding voltage. the inrush currents can be further reduced significantly from 2 · Iˆn to practically zero. In contrast to the controlled switching method, standard CBs with a single drive for all phases and a normal closing time scatter can be applied. For both the conventional and the proposed concept, a measurement of VMV is additionally required if not already present at the substation. For the power electronics based procedure, an external power supply or a small battery is required to supply the prefluxing and demagnetization process. VI. C ONCLUSION Numerous inrush current mitigation concepts have been presented in the literature whereof the power electronic based synchronous prefluxing method is especially promising. In this paper, it is shown that the hybrid transformer allows the implementation of this mitigation concept without considerable additional effort. A complete procedure consisting of a demagnetization and a subsequent synchronous prefluxing step is proposed. Different alternatives for those steps optimized for speed or accuracy of the prefluxing and demagnetization are presented and compared. In addition, a novel demagnetization strategy applicable for converters coupled to the transformer via LC or LCL filters is proposed. A simulative comparison to the conventional mitigation method based on optimized connection instants is performed which underlines that the inrush currents can be significantly reduced from 2 · Iˆn for the conventional method to practically zero for the proposed procedure. EPE'17 ECCE Europe [8] J. Singh, “Prefluxing Technique to Mitigate Inrush Current of ThreePhase Power Transformer,” Int. Journal of Scientific & Engineering Research, 2013. [9] “System, Apparatus, and Method for Reducing Inrush Current in a Three-Phase Transformer,” United State Patent US 8,878,391 B2, 2014. [10] K. Yamamoto, K. Shinohara, I. T., and M. Miyake, “Reduction of magnetizing inrush current in three-phase transformer with voltage source PWM inverter,” in United Research on Electronic Devices and Semiconductors Power Devices, 1997, (in Japanese). [11] R. Ekstrm, S. Apelfrjd, and M. Leijon, “Transformer Magnetizing Inrush Currents Using a Directly Coupled Voltage-Source Inverter,” ISRN Electronics, 2013. [12] J. Burkard and J. Biela, “Evaluation of Topologies and Optimal Design of a Hybrid Distribution Transformer,” in Proc. of the Power Electronics and Applications Conf. (EPE), 2015. [13] ——, “Protection of Hybrid Transformers in the Distribution Grid,” in Proc. of the Power Electronics and Applications Conf. (EPE), 2016. [14] R. Erickson, “Optimal single resistors damping of input filters,” in Applied Power Electronics Conference and Expositio (APEC), 1999. [15] N. Chiesa, “Power Transformer Modeling for Inrush Current Calculation,” Ph.D. dissertation, NTNU, 2010. [16] J. H. Brunke and K. J. Frohlich, “Elimination of transformer inrush currents by controlled switching. II. Application and performance considerations,” IEEE Transactions on Power Delivery, 2001. [17] IEC 60076-3 Power Transformers - Part 3: Insulation levels, dielectric tests and external clearances in air, IEC Std., 2013. [18] Y. H. Chen, M. Y. Yeh, P. T. Cheng, J. C. Liao, and W. Y. Tsai, “An inrush current reduction technique for multiple inverter-fed transformers,” IEEE Transactions on Industry Applications, 2014. [19] “IEEE Guide for Diagnostic Field Testing of Fluid-Filled Power Transformers, Regulators, and Reactors,” IEEE Std C57.152-2013, 2013. [20] M. Pütter, M. Rädler, and U. B., “Reliable demagnetization of transformer cores,” 2014. ISBN: 9789075815276 et CFP17850-ART © assigned jointly to the European Power Electronics and Drives Association & the Institute of Electrical and Electronics Engineers (IEEE) P.9