B- Columns of Special Moment Frames ACI 18.7 applies to columns of special moment frames that form part of the seismic- force-resisting system and proportioned primarily to resist flexure, shear and axial forces. This section applies to columns of special moment frames regardless of the magnitude of axial force. Before 2014, the Code permitted columns with low levels of axial stress to be detailed as beams 1- Dimensional Limits: ACI 18.7.2 requires that the following conditions are to be satisfied: The shortest cross-sectional dimension, measured on a straight line passing through the geometric centroid, shall not be less than 30 cm. The ratio of shortest cross-sectional dimension to the perpendicular dimension shall not be less than 0.40. 2- Minimum Flexural Strength of Columns: Based on ACI 18.7.3.2, The flexural strengths of the columns shall satisfy the following equation: M nc 1.2 M nb where M nc = sum of nominal flexural strengths of columns framing into the joint, evaluated at the faces of the joint. Column flexural strength shall be calculated for the factored axial force, consistent with the direction of the lateral forces considered, resulting in the lowest flexural strength. M = sum of nominal flexural strengths of the beams framing into the joint, evaluated at the faces of the joint. Flexural strengths shall be summed such that the column moments oppose the beam moments. nb The intent of the above equation is to reduce the likelihood of inelastic action. If columns are not stronger than beams framing into a joint, flexural yielding can occur at both ends of all columns in a given story, resulting in a column failure mechanism that can lead to collapse. For columns not satisfying the previous equation, the lateral strength and stiffness of these columns shall be ignored when calculating strength and stiffness of the structure. These columns shall conform to ACI 18.14 (frame members not proportioned to resist forces induced by earthquake motions). 181 Strong column-weak beam requirements for special moment frames 3- Longitudinal Reinforcement: ACI 18.7.4 requires that the following conditions are to be satisfied: Area of longitudinal reinforcement, Ast shall be at least 0.01 Ag and shall not exceed 0.06 Ag . The lower limit of the area of longitudinal reinforcement is to control time-dependent deformations and to have the yield moment exceed the cracking moment. The upper limit of the area reflects concern for reinforcement congestion. In columns with circular hoops, there shall be at least six longitudinal bars. Lap splices are permitted only within the center half of the member length, and shall be designed as tension lap splices and enclosed within transverse reinforcement conforming to ACI 18.7.5.2 and 18.7.5.3. 182 Typical lap splice details of columns in special moment frames 4- Transverse Reinforcement: Transverse reinforcement required in ACI 18.7.5.2 through 18.7.5.4 shall be provided over a length l from each joint face and on both sides of any section where flexural yielding is likely to occur as a result of lateral displacements beyond the elastic range of behavior. The length l shall be at least the largest of (a) through (c): (a) The depth of the column at the joint face or at the section where flexural yielding is likely to occur; (b) 1/6 of the clear span of the member; and (c) 45 cm. Research results indicate that the length should be increased by 50 percent or more in locations, such as the base of a building, where axial loads and flexural demands may be especially high. ACI 18.7.5.2 requires that the transverse reinforcement shall satisfy the following: 183 (a) Transverse reinforcement shall comprise either single or overlapping spirals, circular hoops, or rectilinear hoops, with or without crossties. (b) Bends of rectilinear hoops and crossties shall engage peripheral longitudinal reinforcing bars. (c) Crossties of the same or smaller bar size as the hoops shall be permitted, subject to limitations of 25.7.2.2 (column tie diameter). Consecutive crossties shall be alternated end for end along the longitudinal reinforcement and around the perimeter of the cross section. (d) Where rectilinear hoops or crossties are used, they shall provide lateral support to longitudinal reinforcement in accordance with 25.7.2.2 and 25.7.2.3 (column tie arrangement). e) Reinforcement shall be arranged such that the spacing hx of longitudinal bars laterally supported by the corner of a cross tie or hoop leg shall not exceed 35 cm around the perimeter of the column. f) Where Pu 0.3 Ag f c or f c 700 Kg / cm 2 in columns with rectilinear hoops, every longitudinal bar around the perimeter of the column core shall have lateral support provided by the corner of a hoop or by a seismic hook, and the value of hx shall not exceed 20 cm. Pu shall be the largest value in compression consistent with factored load combinations including E. Example of transverse reinforcement in columns Spacing of transverse reinforcement along the length l of the member shall not exceed the smallest of (a), (b) and (c): 184 (a) one-fourth of the minimum member dimension; (b) six times the diameter of the smallest longitudinal bar 35 hx , where 3 (c) s 10 s shall not exceed 15 cm and need not be taken less than 10 cm. Amount of transverse reinforcement shall be in accordance with Table 18.7.5.4. The concrete strength factor k f and confinement effectiveness factor kn are calculated as shown below: f c 0.60 1.0 1750 n kn l nl 2 where nl is the number of longitudinal bars around the perimeter of the kf column core with rectilinear hoops that are laterally supported by the corner of hoops or by seismic hooks. where f yt = yield stress of the transverse reinforcement Ag = gross cross-sectional area of concrete section Ach = cross-sectional area of a column measured to the outside edges of transverse reinforcement. 185 s center-to-center spacing of transverse reinforcement measured along the longitudinal axis of the column. Expressions (a), (b), and (c) in Table 18.7.5.4 are to be satisfied in both cross-sectional directions of the rectangular core. For each direction, bc is the core dimension perpendicular to the tie legs that constitute Ash , as shown in Fig. R18.7.5.2. Beyond the length l , the column shall contain spiral or hoop reinforcement satisfying 25.7.2 through 25.7.4 (column ties/spirals) with center-to-center spacing, s , not exceeding the lesser of six times the diameter of the smallest longitudinal column bars and 15 cm, unless a greater amount of transverse reinforcement is required by 18.7.5.2, 18.7.5.3, or 18.7.6 (shear strength) . Columns supporting reactions from discontinued stiff members, such as walls, shall satisfy (a) and (b): (a) Transverse reinforcement required by 18.7.5.2 through 18.7.5.4 shall be provided over the full height at all levels beneath the discontinuity if the factored axial compressive force in these members, related to earthquake effect, exceeds 0.1 f 'c Ag . Where design forces have been magnified to account for the over-strength of the vertical elements of the seismic-forceresisting system, the limit of 0.1 f 'c Ag shall be increased to 0.25 f 'c Ag . (b) Transverse reinforcement shall extend into the discontinued member at least ld of the largest longitudinal column bar, where ld is determined in accordance with ACI 18.8.5 (development length of bars in tension). Where the lower end of the column terminates on a wall, the required transverse reinforcement shall extend into the wall at least ld of the largest longitudinal column bar at the point of termination. Where the column terminates on a footing or mat, the required transverse reinforcement shall extend at least 30 cm into the footing or mat. 186 Confinement requirements at column ends (a) Spiral hoop reinforcement 187 Confinement requirements at column ends (b) Rectangular hoop reinforcement Columns supporting discontinued stiff members 188 5- Shear Strength Requirements: The design shear force, Ve , is to be determined from consideration of maximum forces that can be generated at the faces of the joint at each end of the column. These joint forces shall be determined using the maximum probable moment strengths, M pr , of the column associated with the range of factored axial loads, Pu , acting on the column. The column shears need not exceed those calculated from joint strengths based on the probable moment strength M pr of the beams framing into the joint. In no case shall Ve be less than the factored shear determined by analysis of the structure. Transverse reinforcement over the length l given in 18.7.5.1, shall be designed to resist shear assuming Vc 0 when both (a) and (b) occur: i. The earthquake-induced shear force represents ½ or more of the maximum required shear strength within l ; ii. The factored axial compressive force, Pu , including earthquake effects is less than 0.05 Ag f 'c . Loading cases for design of shear reinforcement in columns of special moment frames 189 Example (9): For the column shown in the figure, check the requirements of ACI 18.7 in relation to columns which are part of special moment frames. Note that factored loads are: Pu 337 tons and M u 84.4 tons . Use f 'c 300 Kg / cm2 and f y 4200 Kg / cm 2 . Solution: A- 18.7.2 "Dimensional limits": Based on ACI 18.7.2.1, the shortest cross-sectional dimension, measured on a straight line passing through the geometric centroid shall not be less than 30 cm. This requirement is satisfied since the shortest cross-sectional dimension = 45 cm. 190 The ratio of the shortest cross-sectional dimension to the perpendicular dimension shall not be less than 0.40. Ratio = 45 0.64 0.40 (O.K) 70 B- ACI 18.7.3 "Minimum Flexural Strengths of Columns": Based on ACI 18.7.3.2, the flexural strengths of the columns shall satisfy the following equation: M nc 1.2 M nb Considering the columns on both sides of the joint are of equal flexural strengths, the flexural strength of each of the columns is determined using nominal strength interaction diagrams. g 0.01558 , f ' c 4 ksi , Kn 70 2 4 2 1 2.5 0.821, Pu 337 tons 70 Pn 337 1000 0.55 / fc Ag 0.65 3007045 Using nominal 60.80, load-moment strength interaction diagram, Mn 0.165 and thereby M n 109.15 t.m f c Ag h ' From example (8), M nr ve M nl ve 41.35 t.m and M nr ve M nl ve 59.82 t.m M M M nc 109.15 109.15 218.30 t.m , nc nb M 218.3 2.16 1.2 (O.K) 101.17 191 nb 41.35 59.82 101.17 t.m L4- C- ACI 18.7.4 "Longitudinal Reinforcement": Based on ACI 18.7.4.1, the reinforcement ratio g shall not be less than 0.01 and shall not exceed 0.06. g 49.087 0.01558 (O.K) 4570 Based on ACI 18.7.4.3, lap splices are only permitted within the center half of the member length and shall be designed as tension lap splices enclosed within transverse reinforcement in accordance with ACI 18.7.5.2 and 18.7.5.3. Length of lap splice of longitudinal bars (in tension): For Class "B" lap splice, lsp 1.3 l d f y t e s ld 3.5 cb K tr f 'c d b db t 1 , e 1 , s 1 , and 1 cb = 4.0 + 1.0 + 1.25 = 6.25 cm or cb = [(45 – 4 (2) – 2 (1) – 2.5]/ (8) = 4.0625 cm i.e., cb is taken as 4.0625 cm Ignoring the effect of transverse reinforcement, K tr 0 cb K tr 4.0625 0 1.625 2.5 db 2 .5 42001.0 2.5 106.59 ld 3.5 1.625 300 Required splice length lsp 1.3 106.59 138.57 cm , taken as 140 cm. Based on ACI 18.7.5.3, transverse reinforcement shall be spaced at a distance not exceeding (a) one-quarter of the minimum column dimension, (b) six 35 hx , 3 times the diameter of the smallest longitudinal bar, and (c) s 10 where S is maximum longitudinal spacing of transverse reinforcement, shall not exceed 15 cm and need not be taken less than 10 cm. In the same 192 expression h x is maximum horizontal spacing of hoop or crosstie legs on all faces of the column. Thus, mmaximum vertical spacing of transverse reinforcement is not to exceed the smallest of : i. 45/4 = 11.25 cm ii. 6 (2.5) = 15 cm 35 hx s 10 = 10 cm 3 70 2 4 1 hx 30.5 cm . Thus maximum spacing is limited to 10 cm 2 iii. (based on the minimum of i, ii and iii). Based on ACI 18.7.5.2 (e), the spacing hx of bars laterally supported by the corner of a crosstie or hoop leg shall not exceed 35 cm around the perimeter of the column. Two cross ties are added to the existing 10 mm hoops to satisfy this requirement (maximum spacing of 35 cm). Based on ACI 18.7.5.2 (f), column load =337 tons and 0.3 Ag fc 0.3 4570300 / 1000 283.50 tons 337 tons Therefore, hx shall not exceed 20 cm. D- 18.7.5 "Transverse Reinforcement": Based on ACI 18.7.5.4 (b), the total cross-sectional area of rectangular hoop reinforcement shall be based on Table 18.7.5.4 For shear in the direction of shorter side of the column: 300 0.60 0.77 1.0 , taken as 1.0 1750 10 kn 1.25 8 0.3 1062300 45 70 2 Ash 2 37 62 1 4.96 cm 4200 kf 0.09 1062300 3.98 cm 2 4200 337000 2 0.20 1.01.25 1062 5.43 cm 42003762 Ash 2' Ash 2 i.e., Ash 2 5.43 cm 2 Use 12 mm tie plus three 12 mm cross ties ( Ash 5.65 cm 2 ) For shear in the direction of longer side of the column: 193 Ash1 0.3 1037300 45 70 2 37 62 1 2.96 cm 4200 0.09 1037300 2.38 cm 2 4200 337000 2 0.20 1.01.25 1037 3.24 cm 42003762 Ash1 Ash1 i.e., Ash1 3.24 cm 2 Use 12 mm tie plus three 10 mm cross ties ( Ash 4.615 cm 2 ) Based on ACI 18.7.5.1, transverse reinforcement in amount specified before shall be provided over a length l from each joint face and on both sides of any section where flexural yielding is likely to occur as a result of inelastic lateral displacements of the frame. The length l shall not be less than the largest of: (a) The depth of the member at the joint face = 70 cm (b) 1/6 of the clear span of the member= 400/6 = 66.67 cm (c) 45 cm. i.e., l = 70 cm. Based on ACI 18.7.5.5, where transverse reinforcement as specified before is not provided throughout the full length of the column, the remainder of the column length shall contain hoop reinforcement with center-to-center spacing not exceeding the smaller of six times the diameter of the longitudinal column bars or 15 cm. Smax = the larger of 6 (2.5) cm and 15 cm = 15 cm 194 E- ACI 18.7.6 "Shear Strength Reinforcement": The design shear force Ve is to be determined from consideration of maximum forces that can be generated at the faces of the joint at each end of the column. These joint forces shall be determined using the maximum probable moment strengths M pr of the column associated with the range of factored axial loads acting on the column. The column shears need not exceed those determined from joint strengths based on the probable moment strength M pr of the beams framing into the joint. In no case shall Ve be less than the factored shear determined by analysis of the structure. Ve 1 / 2 72.69 50.77 72.69 50.77 30.865 tons (see Example 8 for M pr 4 values) d 70 4 1.2 1.25 63.55 cm Vc 0.53 3004563.55 / 1000 26.25 tons (neglecting effect of axial force) V Vs Vn Vc and Vs u Vc 195 30.865 26.25 14.90 tons 0.75 Av fy d A V 14.9 1000 Vs and v s 0.0558 S S f y d 420063.55 Vs 3.5 45 Av 0.0375 0.0558 (O.K) 4200 S min For S 15 cms , Av 0.837 cm2 (satisfied at sections 1-1, 2-2 and 3-3). 196 B- Columns of Intermediate Moment Frames Requirements of ACI 18.4.3 are applicable for columns of intermediate moment frame columns forming part of the seismic-force resisting system. 1- Transverse Reinforcement: At both ends of the column, hoops shall be provided at spacing length l measured from the joint face. s over a The length l shall not be less than the largest of: (a) 1/6 of the clear span of the column (b) Maximum cross-sectional dimension of the column (c) 45 cm. The spacing s shall not exceed the smallest of: (a) 8 times the diameter of the smallest longitudinal column bar (b) 24 diameter of the hoop bar (c) One-half of the smallest cross-sectional dimension of the column (d) 30 cm. The first hoop shall be located not more than s / 2 from the joint face. Outside the length l , spacing of the transverse reinforcement shall conform to ACI 10.7.6.5.2 (maximum spacing of shear reinforcement). Columns supporting reactions from discontinuous stiff members, such as walls, shall be provided with transverse reinforcement at the spacing s in accordance with 18.4.3.3 over the full height beneath the level at which the discontinuity occurs if the portion of factored axial compressive force in these members related to earthquake effects exceeds 0.1 f 'c Ag . If design forces have been magnified to account for the overstrength of the vertical elements of the seismic-force-resisting system, the limit of 0.1 f 'c Ag shall be increased to 0.25 f 'c Ag . Transverse reinforcement shall extend above and below the column in accordance with 18.7.5.6(b). Columns shall be spirally reinforced in accordance with Chapter 10 or shall be in accordance with 18.4.3.3 through 18.4.3.5, discussed in 1. Provision 18.4.3.6 shall apply to all columns supporting discontinuous stiff members 197 2- Shear Strength Requirements: Design shear strength of columns Vn resisting earthquake effect shall be at least the lesser of (a) and (b): (a) The shear associated with development of nominal moment strengths of the column at each restrained end of the unsupported length due to reverse curvature bending. Column flexural strength shall be calculated for the factored axial force, consistent with the direction of the lateral force considered, resulting in the highest flexural strength. (b) The maximum shear obtained from factored load combinations that include E, with E substituted for E. 198 199 B- Columns of Ordinary Moment Frames Requirements of ACI 18.3.3 are applicable to columns of ordinary moment frames forming part of the seismic-force resisting system and classified as SDC "B". Shear Strength Reinforcement: Columns having unsupported length lu 5c1 shall have at least the lesser of (a) and (b): (a) The shear associated with development of nominal moment strengths of the column at each restrained end of the unsupported length due to reverse curvature bending. Column flexural strength shall be calculated for the factored axial force, consistent with the direction of the lateral forces considered, resulting in the highest flexural strength. (b) The maximum shear obtained from design load combinations that include E , with E substituted for E . 200