I&CPS 05 10 - - Electrical Design- Refined for Safety Oaleep Mohla Bruce McClung Ben McClung Member IEEE, ASME Senior Member IEEE Life Fellow IEEE Mc2 Electrical Consulting LLC Mc2 Electrical Consulting LLC OeM Electrical Consulting Charleston, wv 25312 Charleston, WV 25312 Missouri City, TX 77459 Abstract - Services, Inc 656 Whittington Dr 627 Pioneer Lane A typical electrical system and equipment layout is designed to conform with certain National Fire Protection Association's NFPA 70 or International such as Electrotechnical Commission's IEC 60364-1. The Occupational Safety and Health Administration standards also sets forth design safety standards for electrical systems under 29 CFR Subpart S 1910.302- .308. These documents contain fundamental principles of safety for protection against electric shock, thermal effects, overcurrent, fault currents, and overvoltage. After an initial electrical system design is complete, and the electrical system studies, including short circuit, protective device, and arc flash calculations are performed, current knowledge of arc flash hazard may dictate that the electrical design be refined for safety. An electrical design - refined for safety would consider methods to eliminate or reduce electrical failures, to lower any fault current magnitude, and to increase speed of protective device clearing. The purpose of this presentation is to identify and document the benefits to be gained from the use of such things as high resistance grounding, "see-through" rigid barriers, "fingersafe" fuses, insulated buses and terminal covers, arc resistant switchgear and controlgear, "enhanced safety" motor control centers, and/or appropriate personal protective clothing/personal protective equipment. "Electrical Design - Refined for Safety" is an innovative and cost effective way to complement and supplement regulations and codes requirements. It can enhance employees' safety without . excessive reliance on administrative controls. It can eliminate or reduce the burdens associated with obtaining special permits required for common tasks, such as meter reading, lock out/tag out, etc. "Electrical Design - Refined for Safety" is the careful application of engineered safety features to enhance safety for personnel who must, from time to time, work in an environment affected by proximity to exposed energized electrical conductors and circuit parts. Index Terms - typical electrical design, electrical installation standards, prioritze safety, refined for safety, electrical safety I. Presently, the BACKGROUND National Association's (NFPA) Fire The Protection Nat ional Electrical Code" " (NEC) addresses fundamental principles of safety for electrical installations. The NEC enc ompa ss es protection aga i nst electric shock, thermal effects, overcurrent, fault cu rren ts and ovcrvoltage. The NFPA "Standard for Electrical Safety in the Workplace" (70E) addresses safe practices for employees and sets forth general requirements for achieving and maintaining electrical safety in the workplace. OSHA 29 CRF Subpart S 1910.33 I -335 and IEEE 902 provide electrical safety-related work practices. 0-7803-9020-2/05/$20.00 ©2005 Administration Safety (OSHA) has and Health reinforced the premise that "electrical equ ipmen t when installed , new per recognized and accepted ·Codes' and 'Standards' is deterioration considered occurs to to enclosure/conductors/insulation be safe degrade or until until the unsafe acts are performed or until carelessness occurs." Electrical maintenance should be performed in compliance with NFPA 70B and 70E Chapter 2, IEEE 902, and manufacturers' instruction booklets for the purpose of su s t a ining equipment in "like new" condition. IEEE 1584-2002 and NFPA 70E-2004 prov i d e guidance that anywhere thc incident energy at working IEEE. Occupational distance of the electrical equipment Page 89 Authorized licensed use limited to: Thapar Institute of Engineering & Technology. Downloaded on September 29,2020 at 05:09:32 UTC from IEEE Xplore. Restrictions apply. exceeds 40 caVcm2 personnel should not perform any energized work(l). All of these documents have been developed to assist and guide persons who design, construct and commission, operate, adjust, service, and maintain electrical equipment in commercial and industrial facilities. The installation and use of equipment per these 5 rna third party and certifying agencies, durability, connection space, and - electrical insulation, heating effects under normal and abnormal conditions likely arise to classification by in service, type, arcing effects, voltage, size, current using or likely to come in equipment. contact with the 4,300 rna heating, cooling, and moving things little thought to the potential hazards that confront Cardiac arrest - burns Employees working on or near exposed energized electrical conductors and circuit parts must be protected from electrical shock, arc flash bums, and arc blast and other hazards appropriate protective measures by The NEC specifically add re s ses "interrupting rating" as the highest fault current at rated voltage that a device can safely conduct or interrupt under m , generation, the distribution, from contact by personnel. faults nor do they guarantee protection from flying debris associated with the arc blast force. transformation, and utilization III. TYPICAL ELECTRICAL DESIGN CRITERIA of Increased consumption of electrical power has resulted in higher concentrations of electricity, both higher voltage and higher currents, which i n crea ses "shock" hazard and creates "arc flash/arc blast" hazard. Electrical shock was recognized first hazard, followed by arc flash and arc blast. as . a Other hazards, associated as by-products of the arcmg fault, are still being cataloged. Present The potential hazards from electric current on Table 1 - Effects of Electric Current on the Human Body Below 1 rna Not perceptible the the Equipment is sized based on interrupting rating (available short circ u it current), with cost usually being the primary c r iter ion in equipment selection. Even when system design meets recognized "building codes", hazardous conditions can exist during operation and maintenance. design, often at locations geographically remote from the customer. its experience. The own owner It is the rare company that personnel must with ensure detail that design the bid system requirements. The owner must also obtain a design safety review by independent professionals experienced in industry safety. 2 30 cal/cm for new design to allow tolerance for growth. 0-7803-9020-2/05/$20.00 ©2005 IEEE. takes design specifications adequately stipulate the electrical Faint tingle (1) Limit incident energy to system "National Electrical Code"m. retains Reaction electrical customer/owner's requirements and follows Contract engineeri ng firms do most of the detail the human body are: Current Such enclosures are not rated to contain products of internal arcing electricity . 1 rna pumping energized electrical conductors and circuit parts around, for granted. Most users of electricity give tran smission . 10,000 rna rated switchgear or controlgear serves to isolate INTRODUCTION We take the benefits of electricity, such as workers Heart ceases rhythmic standard test conditions. Enclosure of interrupting . II. lighting, Respiratory arrest 1,000- capacity, and specific use, and other factors that contribute to the practical safeguarding of persons Individual cannot let-go 50-150 rna mechanical wi re b ending c ontrol 9-30 rna documents is based on suitability as determined by strength Slight s hock- not painful Painful- loss of muscle 6-25 rna (2) NEe Article 90.1 (e) states "Intention. This Code is not intended as a design specification or an instruction manual for untrained persons." Page 90 Authorized licensed use limited to: Thapar Institute of Engineering & Technology. Downloaded on September 29,2020 at 05:09:32 UTC from IEEE Xplore. Restrictions apply. Owners must specify an acceptable amount of outage, so that electrical application engineers (and p rocess engineers) System redundancy. shutdown systems) can build of to electrical in redundancy systems (and system enables quickly clear electrical faults in main substations and distribution systems to de-energized where features to defeat the coordination times when once the first pass electrical system design is employees complete and results of electrical system studies, equipment. short circuit, protec ti ve reduce the incid ent Many protective devices energy in tho se areas. are now available that have "maintenance switch" It is also the owner's responsibility to request; including Th is effort to maintain maximum within its area. availability of power may have to be sacrificed to process work 1 incident energy still exceeds 40 cal/cm allow source, will be the only portion isolated for a fault that anywhere in the electrical system incident 2 energy exceeds 40 cal/cm reconsider the equipment, devices, comp o nents and connections , working near or on electrical Engineers and designers must make the owners device coordination, and arc flash hazards are available; are aware of their options. The cost of an injury resulting from a single arc flash could cost 51.8 million for a fatality or $4 million for a dis abled survivor. From a life cycle cost point of view, it to lower the available fault current and increase bec omes very easy to justify spending a little more speed of protective device clearing time to limit up front to have a safe electrical system. incident energy to 40 cal/cm2 based on foreseeable uti lization l A. . Basic principles to enhance electrical system safety: • IV. CRITERIA FOR USING THE ELECTRICAL DESIGN- REFINED FOR SAFETY PROCESS In order for electricity to benefit mankind, it must be produced, controlled. considered These in the confined, four directed concepts design process. be mo st productive area for improving electrical safety today exists in refining the design features that minimize/eliminate exposure to electrical shock - • • keep The performing o electri c al system. drop to have a safe The industry is beginning to recognize that low impedance transformers will impedance may significantly reduce the incident energy when a fault occurs, provided the arcing fault current is still high enough to be detected and quickly cleared by circuit protective devices. Protective devices arc commonly chosen completely new electrical systems should be limited maximum of 40 cal/cm2 existing electrical systems should be cal/cm2 • establish PPE selection with owner and· achieve user buy-in early in the design process • evaluate who will be operating the electrical systems o • • owner or contract personnel take all operating modes into account if substations are equipped with tie breakers, assume that all main breakers may be closed have high fault currents, probably resulting in higher incident energy. A transformer with higher equipment substations refined to a limit of a maximum of 40 the voltage drop. Many times the designer needs to c ompromise voltage boundary tolerance for growth, etc for recognized electrical design must be willing to perform or Equipment is commonly specified to minimize 1) to a maximum of 30 cal/cm2 to allow the seek critical reviews of their work that upholds safety to be as imp ortant as operability, maintainability, and reliabi li ty. as minimize available incident energy Refined for Safety" is person(s) close outside of classified areas o isolating personnel from the detrimental effects of hazard. as limits wherever possible proactive in removing sources of hazards or in the equipment keep electrical equipment outside of Class I and arc hazards. "Electrical Design ele ctrical practical to where it is utilized Division 1 (or Clas s 2 Division and should The • locate while tie is closed (unless interlocked) • minimize shock exposure is minimized, occurring the while - if shock exposure likelihood maintaining of arc flash equipment is inherently minimized to coordinate so the smallest load, furthest from the O· 7803·9020·2/05/$20.00 ©2005 IEEE. Page 91 Authorized licensed use limited to: Thapar Institute of Engineering & Technology. Downloaded on September 29,2020 at 05:09:32 UTC from IEEE Xplore. Restrictions apply. • o compromise may be necessary in operability to increase the safety (e.g., coordination of • protective devices may have to be sacrificed) . design must take an iterative approach o preliminary o equipment selection o o o o o o • single scheme line and operating voltage drop study the more the design allows for LOTO, the more likely LOTO will be employed • install disconnect or polarized plug at each • install disconnect at base of multi-fixture poles • arc flash hazard analysis study • fixture place lighting panels in a logical location, in protective device coordination study close proximity to utilization site allow for maintenance to be performed below 8' device selection o repeat studies concentrate design effort to improve safety on 277/480V lighting circuits and medium o • on install lights that come on immediately after power is restored B. Simple Example ofElectrical Design - Refined for Safety Lighting Design - Present 1) Concept o o Large and inexpensive lighting designs have the human aspects. o injuries occur on Lighting Design - Refined For Safety In a lighting desi gn, refined for safety, designers would consider the human interface with electrical systems and think like the people who will use and maintain the electrical system on a day-to-day basis. A lighting des i gn, refined for safety, would: • • use l20V, neutral 1 phase power with dedicated minimize arc flash hazard by using 120/20SV systems that are fed from transformers below • • 125kVA minimize the temptation to work on lighting while "hot" feed every other light from alternating circuits 0-7803-9020-2/05/$20.00 ©2005 IEEE. restart typically have a lower' "T" rating battery back-up fluorescent lights may be a good option provide convenient testing for battery back-up lighting Low cost and continuation of process are given highest prlonty. Many electrical 2771480V lighting systems. 2) • Designs don't consider how lighting is utilized or how it is maintained. specify "some" lights with instant restart be aware that lights equipped with instant for classified areas typically utilized 277/4S0V, 3 phase power with a installing the maximum number of fixtures on a single circuit. Minimal consideration is given to equipped with a hinged mast are switched separately and marked to be kept • Lighting plans are based on install fixtures below 8' install fixtures that can be lowered or install "night lights" that are not switched, or voltage Class E2 motor controllers - since this is where most of the electrical bums occur common neutral. circuit will leave at least one adjacent lighting circuit in operation • short circuit study refine equipment selection and protective lock out/tag out (LOTO) of one lighting o install remote test button o specify emergency lights control testing feature with remote • install emergency lighting supplied from a back-up generator, if local codes require V. DESIGN FEATURES FOR PROTECTION AGAINST ELECTRICAL "SHOCK" HAZARDS "Electrical Design - Refined for Safety" inherently reduces the potential safety risk from electrical shock hazard by providing a first line of defense to guard personnel from exposed energized electrical conductors and circuit parts ("live parts"). Long ago the most frequently utilized electrical design scheme to avoid contact with exposed energized electrical conductors and circuit parts was chain link fencing. An early refinement was to enclose bare bus, switches and other electrical control and protective devices in enclosures with hinges and latched or bolted-on covers/ doors. Page 92 Authorized licensed use limited to: Thapar Institute of Engineering & Technology. Downloaded on September 29,2020 at 05:09:32 UTC from IEEE Xplore. Restrictions apply. Other "Electrical Desi gn - Refined for Safety" concepts to be used in order to remove operators from in front interruptin g of rated Table 3 - Restricted Approach Boundaries for - an approach limit at a Shock Protection(3) electrical s witchgear or controlg ear: distance from an exposed live part within • "mimic panels" which there is an i n c re a s ed risk of shock, due • "umbilical cords", some as long as forty feet, to electrical arc over, combined with having a plug on one end for connection to a inadvertent movement, for personnel working on receptacle the switchgear/controlgear and • an . front "remote racking" c ircu it breakers installed in utilize d istanc es approach for boundaries based on: - Table 2 Limited Approach Boundaries for Shock Protection Table 3 - Restricted Approach Boundaries for Shock Protection Table 4 - Prohibited Approach Boundaries for Shock Protection ut il iz e Table 5 - Basic Minimum Air Insulation Distance to Avoid Flashover Table 2 - Limited Approach lJoundariesfor Shock Protection(J) - an approach limit at a distance 300 V and less Avoid contact 301 to 750V 1 f1. ° in. 751 to 15,000V 2 ft. 2 in. 15,100 to 36,000V 2 ft. 7 in. 36,100 to 46,000V 2 ft. 9 in. 46,100 to 72,500 3 ft. 2 in. 72,600 to 121,000V 161,000 to 169,000V 3 ft. 3 in. 3 ft. 7 in. 4 ft. 0 in. 230,000 to 242,000V 5 ft. 3 in. 345,000 to 362,000V 8 ft. 6 in. 500,000 to 550,000V 11 ft. 3 in. 765,000 to 800,000V 14 ft. 11 in. 138,000 to 145,000V Table 4 - Prohibited Approach Boundaries for Shock Protection(4) - an approach limit at a distance from an exposed live part within from an exposed live part within which a which work is considered the same as making shock hazard exists 'h the rIve part contact WIt Nominal Voltage Exposed Exposed Fixed Nominal Voltage Movable Circuit (Ph·Ph) Conductor Part 300 V and less 10 ft. 0 in. 3 ft. 6 in. 301 to 750V 10 ft. 0 in. 3 ft. 6 in. 10 ft. 0 15,100 to 36,OOOV in. 10 ft. 0 in. 6 ft. 0 in. 36, iDO to 46,000V 10 ft. 0 in. 8 ft. 0 in. 46,100 to 72,500V 10 ft. 0 in. 8 f1. 0 in. 72,600 to 121,000V 10 ft. 8 in. 8 f1. 0 in. 751 to l5,OOOV 5 ft. 0 in. 138,000 to 145,000V 11 ft. 0 in. 10ft. 0 in. 161,000 to 169,000V 11 ft. 8 in. 11 f1. 8 in. 230,000 to 242,000V 13 ft. 0 in. 13 ft. 0 in. 345,000 to 362,000V 15 ft. 4 in. 15 ft.4 in. 500,000 to 550,000V 19ft. 0 in. 765,000 to 800,00OV 23 ft. 9 in. 19 ft. ° in. 23 ft. 9 in. (3) NFPA 70E, Table 130.2 (c) 0-7803-9020-2/05/$20.00 ©200S IEEE. Boundary (Ph-Ph) button on the other end were used panel" or "umbilical cords" • Nominal Voltage open-close push switchgear for operat i on from either "mimic • III prOXImIty to the rlve part . case I of (Ph-Ph) Boundary 300 V and less Avoid contact 301 to 750V Oft. 1 in. 751 to 15,000V 15,100 to 36,OOOV Oft. 7 in. Oft. 10 in. 36.100 to 46,OOOV 1 f1. 5 in. 46,100 to 72,500V 2 ft. 1 in. 72,600 to I2l,000V 2 ft. 8 in. 138,000 to 145,000V 3 ft. 1 in. 161,000 to 169,000V 3 ft. 6 in. 230,000 to 242,000V 4 f1. 9 in. 345,000 to 362,000V 8 ft. 0 in. 500,000 to 550,000V 10ft.9in. 765,000 to 800,000V 14 f1.5 in. (4) Ref ANSIIIEEE 516-2003 Guide for Maintenance Methods on Energized Power Lines Page 93 Authorized licensed use limited to: Thapar Institute of Engineering & Technology. Downloaded on September 29,2020 at 05:09:32 UTC from IEEE Xplore. Restrictions apply. Table 5 - • Basic Minimum Air Insulation Distance to Avoid Flashover(5) Boundary (Ph-Ph) 300Y and less ° [t. 0.03 in. 300 to 750Y ° ft. 0.07 in. 751 to 2,000Y Oft. 0.19 in. 2001 to 15,000Y Oft. l.5 in. 15,001 to 36,000V 0[1. 6.3 in. 36,001 to 48,300Y 48,301 to n,500Y ° ft. 10.0 in. 1 ft. 3.0 in. 72,501 to l 2 l ,000Y 2 ft. 1.2 in. • • • 230,001 to 242,000V 4 [t. 2.4 in. 345,001 to 362,000V 7 ft. 5.8 in. 500,001 to 550,000V 1° ft. 2.5 in. 765,00 I to 800,000V 13 ft. 10.3 in. use of improved, double insulated devices and expose the worker to a "shock" automatic grounding of MV feeders, capacitor motor • • employees starters Permanent installation of ground fault circuit against a t 6 rnA or less. See Table 1 - Effects of Electric Current on the Human Body Note: with today's technology, we should insist on "dead-front" or finger safe protection (IP20) with the equipment doors open minimizing exposure to voltages above 240V higher degree of ingress protection (IP40+) on would mmlmlze opportunity of tools or other foreign material • from initiating an arc during maintenance compartmentalizing of control and power voltages • use of low voltage (below 50V) for control • bring test points for bus and secondary voltage • use of in-line resistors at test points to limit • power ground fault circuit protectors for equipment when set for 30 rnA or less are also effective for protecting personnel against the most severe "shock" effects. effective methods today to protect employees this (provide interrupters for personnel protection that trip from contacting energized parts) feed; withdrawn interlock with main switching device) use of "finger safe fuses" (one of the most incoming are Isolation of wireways from bus and from free electrical "shock" hazards: • starters access to breakers, disconnect switches, or There are several electrical design concepts to protecting below or 2 ft. 6.6 in. • glove banks, motors, etc., when switchgear breakers 3 [t 0.0 in. • insulating tools (with dual-color insulation) so damage in 138,001 to 145,00Y • rubber the outer layer is readily identified - do not 161,001 to 169,00V for of improved small objects (nuts) gloves rated for SOOV and Nominal Voltage consider use materials to allow finger dexterity to handle VI. DESIGN FEATURES FOR PROTECTION AGAINST ELECTRICAL "ARC FLASH" HAZARDS Publication of IEEE 1584-2002 "Guide for Performing Arc Flash Hazard Calculations" made it possible to detennine incident e nergy at working distances as well as distance from the arc source where the incident energy is sufficient to cause a second degree bum for electrical systems having greater than SO,OOOA available fault current. Table 6 - Effects of Temperature/Heat on Human Body & Materials temperature J heat shows the effects the human body on of and materials. to front cover power in case of arc appropriate use of see through rigid barriers and vlewmg windows operators/electricians electrical terminals (switches/circuit to and view enables status isolating of devices breakers/contactors) while still providing barriers to prevent contact (5) Ref NFPA 70E, Appendix C.2.1 0-7803-9020-2/05/$20.00 ©200S IEEE. Page 94 Authorized licensed use limited to: Thapar Institute of Engineering & Technology. Downloaded on September 29,2020 at 05:09:32 UTC from IEEE Xplore. Restrictions apply. Table 6 Effects a/Temperature/Heat on Human - • Body & Materials • Temperature/Heat Reaction 145°F Curable skin burn(o) 205°F Human cell death 700-1,400°F Clothing ignition 1,400°F Clothing burning • 1,800°F • • Copper melts 2,600°F Carbon steel melts 9,00O°F Sun's surface 35,OOO°F Arcing terminals • As more arc flash hazard calculations have been performed per IEEE 1584-2002 it has "large" cal/cmz at electrical normal potential arc sources. systems working • work on or near energized electrical equipment • • devices (molded case circuit breakers or fuses) or • simply giving up protective device coordination. It may require adding high resistance grounding, or adding ground relays if solidly grounded, or breaking up electrical supply systems into smaller configurations. Design concepts to consider for protecting employees against electrical arc flash hazards: Note: Many features, which protect personnel against electrical "shock" hazard, also minimize or eliminate the electrical arc flash hazard. (6) A curable skin burn is normally considered to be a degree burn and can be created on most human second skin when a person is near an electrical arc in which the incident energy level is 1.2 cal/cm' or 5.0 J/cm2. This is roughly equivalent to the burn caused by exposing a finger to the flame of a lighted match stick for one second. 0-7803-9020-2/05/$20.00 ©200S IEEE. phase-to-phase and phase-to-ground faults) � protective clothing/personal u se of up-to-date easy-to-read and match cabinet wiring and control schematics mini miz ing exposure to voltages above 240V higher degree of ingress protection (IP40+) on feed; this would minimize the to initiate an arc during maintenance cal/cmz. Nonnally the des ig n alternative to reduce incident energy requires use of current limiting close-open opportunity for tools or other foreign material cal/cmz. Design alternatives to reduce the incident work any bus calc ulated to be more than 40 with use of "remote racking" circuit breakers incoming 40 energy must be implemented if there is a need to cords" identification for all tenninals and devices that • exceed of "umbilical controls on remote end equipment needed With present technology for personal would circuit breakers or controllers; use working distances and appropriate personal protective clothing it cannot be made "safe" to energy use of "mimic panels" for remote operation of protecti ve • incident of switchgear except arc flash boundarylincident energy at typical need to work where incident energy exceeds 40 the front pre-calculated afC flash hazard information from We can now calculate the from when breaker is in "test position" use of electrical equipment labels, with the modify/adjust the arc flash hazard to avoid the where use of provisions to avoid closing circuit • been incident energy of "strong" electrical systems and cal/cmz. sacrificing coordination) use of insulated low voltage buses (minimize exceed 40 distances faster clear i ng time for protective relays (by • acknowledged that 1 2% - 1 8% of the "buses" in modern current to downstream devices ) breakers Aluminum melts . 660°F use of current limiting fuses (minimize fault compartmentalization of control and power voltage s use of low voltage (below 50V) for control power • • • • • bringing test points for bus and secondary voltage to front cover use of in-line resistors at test points to limit power in case of arc use of "finger safe" low voltage fuse holders use of removable terminal lugs insulated boot on all use of insulated low voltage buses use of high resistance grounded electrical systems (first fault to ground is "free") Note: high resistance grounding nonnally restricts or limits the current flow for the first ground fault to 5A or less � however, a second ground fault before the first is cleared essentially creates phase-to-phase fault levels of current flow. It is important to detect and clear the first ground fault before the second occurS in order to avoid Poge 9S Authorized licensed use limited to: Thapar Institute of Engineering & Technology. Downloaded on September 29,2020 at 05:09:32 UTC from IEEE Xplore. Restrictions apply. B. both points of grounding and flowing Clothing grounds, • Personal protective clothing is primarily worn to prevent the person's apparel from contributing to separate ground points. the hazard. in low voltage has ratings that enable it to be utilized to match or equipping with potential ground loops around exceed the potential incident energy available at line side shutters conductive columns/enclosures at all use of clear plastic barriers around all bare use of adequate lighting fixtures, including lighting fixtures inside all electrical equipment • • • the working distance for given tasks from potential arc sources. Some protection against ignition of clothing from heat and "fire-ball" effect has been available use of ground fault circuit interrupters conductors and terminals • Appropriately rated PPC is flame switchgear and controlgear use of outdoor substations (reduces step-and-touch • Personal Protective bonding potentials) • for resistant (FR) (either by fabric or treatment) and all • Features (PPC) connections and earth between the two through/over • D es ign phase-to-phase fault current "flashing" at in the form of flame retardant fabrics for over 25 years. Only recently has attention been directed to identify a broad knowledge base regarding the effects of temperature/heat on human body and enclosures having hinged doors materials. SeeTable 6. The identified temperature iden�ify and label outside of enclosures having multlple sources of electrical power so it is synthetics, cotton, silk, and wool. easy to locate the source disconnect devices avoid use of earth as current return paths current return path Personal Protective Most personal protective equipment is effective against electric shock hazard. This includes rubber insulating gloves, insulating line hoses and covers, insulating blankets and sheets, insulating barriers, insulating tools, voltage rated contact­ making meters, insulating "hot sticks", etc. Items such as rubber insulating gloves with leather protectors provide protection against both Transient voltage rated meters, with either automatic ranging or voltage detection capability only, should be utilized for both shock and arc hazards. The leads of such voltage detectors are just as important as the meters to enable safe use. Both ends of the leads need special attention. The meter end should be retained in the meter case or recessed so that pullout from the meter while in contact with voltage will not result in inadvertent shorting and the stab end needs to be recessed and insulating flanges are required to provide finger when applied within its arc thermal C. Application of personnel protective (PPC) around the individual at work grounds performance value (ATPy(7)). all welding must utilize a dedicated insulated electric shock and arc hazards. The FR PPC neither ignites, bums, nor exhibits break open (EBT(7)) control voltages Less than 50Y A. Design Features for Equipment (PPE) ranges for clothing ignition and burning include Neither shock nor arc flash will occur without a difference of potential between any two conductive enclosures or electrical conductors and circuit parts. Appropriate grounding for both step and touch potentials will avoid the differences ?etwe�n any two conductive enclosures. Stipulate, III deSIgn specifications, grounding studs on/near cable terminations in switchgear to facilitate making ground connections prior to beginning work on de-energized equipment in areas subject to being re-energized by fallen lines or other abnormal contact with energized parts. Personnel protective grounds should be installed on either side of a work site where de-energized electrical lines are subject to being reenergized by falling overhead lines or by induced current from adjacent lines. The current flow through parallel paths splits in the ratio of an individual to the sum of the individual resistances. Example: • For 20,OOOA appropriate guard available PPG, fault the current current with flow over/through the body will only be: against slipping. (7) Refer to ASTM 1959-99 for complete definition of EBT 0-7803-9020-2/05/$20.00 ©200S IEEE. and ATPV Page 96 Authorized licensed use limited to: Thapar Institute of Engineering & Technology. Downloaded on September 29,2020 at 05:09:32 UTC from IEEE Xplore. Restrictions apply. 20,OOOA • * • 0.OOl28/l500.00128=0.017A products to the front, the back or the ends. This will be painful and may cause loss of Expulsion is directed in a manner that will be muscle control whereas current flow over the ground conductor will be: 20,OOOA • Type B involves limiting expUlsion of arcing Or 17ma. * o Type A involves limiting expUlsion of arcing 1500/1500.00l28=19,999.983A This is based on: o away from inhabited space. • Resistance Ground = of products to the front or to the back. Expulsion is directed away from these areas. 25 ft, 250kcmil 0.00 1 28 ohms. Resistance of Body = Arc resistant switchgear and controlgear are Safety characterized by: • 1500 ohms total (500 ohms at hand contact + 1 000 ohms at • foot contact) • D. Additional Features for Protecting Employees starters are withdrawn • • • access to breakers, blowing expelling products of the arcing fault (pressurized vapors and gases, molten splatter) disconnect • switches, or starters open, flying debris isolation of wireways from the bus and from unfettered vaporizes covers off, rupturing enclosures, and cre ati ng (provide interlock with main switching device) of blowing doors capable banks, motors, etc. when switchgear breakers motor create noise, light, heat, conductive material, generates blast forces automatic grounding of MV feeders, capacitor or receiving arc resistant rating remaining intact during internal arcing faults which Against Electricaf Hazards • receiving interrupting capacity rating in a direction not frequented by personnel protecting personnel during monitoring or labeling of all electrical equipment with the while pre-calculated arc flash hazard information - mInlmlZeS arc flash boundary/incident energy at typical equipment/personal working distances and appropriate personal equipment (PPEIPPC) while cubicle door is protective clothing/personal protective operating need the for switchgear which personal protective protective clothing closed equipment needed E. F. Arc Resistant Switchgear and Contralgear The most effective method today to protect operators and electricians from the hazards of arc blastlarc flash is to use arc resistant switchgear Many potential arc flash conditions for which no designed protection is currently available are: • that complies with I EEE/ANS I C37.20.7-200 1 • "IEEE Guide for Testing Medium Voltage Metal Enclosed Switchgear for Intern al Arcing Faults". • EEMA C G 14-1 1987 also covers switchgear. IEC Standard 60298 currently covers both switchgear and controlgear. Three types of arc resistant switchgear and controlgear can provide varying levels of protection: • Type C involves com ple te internal isolation of one compartment from arc fault occurring in adjacent compartment and fro m expulsion of arcing products to the front, the back, the ends, or either from the top or from the bottom; however, one direction is still needed for expUlsion in a manner that will be directed away from inhabited space. 0-7803-9020-2/05/$20.00 ©2005 IEEE. DeSign features for protection against other potential hazards Loud noise Blinding light Intense heat • Vaporized conductive material • Toxic metal vapors • • Blast forces of pressure wave Molten metal splatter/projectiles The reader is directed to monitor progress of the IEEEINFPA collaboration on Arc Flash Hazards to learn more about efforts to analyze and avoid these unusual potential hazards. VII. SUMMARY The facility installation should be made safe by design and by intent. The commissioning period should be utilized to inspect and confirm a safe installation. The operation and maintenance work Page 97 Authorized licensed use limited to: Thapar Institute of Engineering & Technology. Downloaded on September 29,2020 at 05:09:32 UTC from IEEE Xplore. Restrictions apply. performed by operators and electricians needs to • Overall electrical safety requires a supportive • assure the equ i pment is maintained safe . community. Electrical safety is not a proprie tary product. Occupational Safety and Health Administration - 29 C FR-Pa rt 1910 OSHA 29CFR-1910-Subpart S - Electrical Any design improvements for safety of personnel should be announced and shared via activities such as: • IEEE-IAS�PCIC Electrical Safety Committee • IEEE IAS�Electrical Safety Workshop IEEE Electrical Safe ty Benchmarking • • IEEE Electrical Safety Resource Center and Virtual Community As new concepts and materials that enhance safety are proven, they need to be incorporated into st anda rds , codes, gui des , and recommended practices such as: • ANSIIIEEE C2 IEEE 1584 • • NFPA 70 and NFPA 70E • OSHA, both federal and state compl i ance • VIII. REFERENCES ASTM 1959-99 - Standard Test Method for Determining Arc Thermal Performance of Textile Materials for Clothing by Electric Arc Method U sing I nstrumented Sensor P anels • • • EEMAC G14-1 - Procedure for Testing the Resistance of Metalclad Switchgear Under Conditions of Arching Due to and Internal Fault lEC 60298 - AC. metal-enclosed switchgear and control gear for rated voltages above I kV and up to and includ i ng 52 kV IEC 60364-1 buildings - - Electrical installations of Part 1: Fundamental principles, assessment of general characteristics, • • • definition IEEE-lAS Color Book Collection IEEE 1584-2002 - IEEE Guide for Performing Arc-Flash Hazard Calculations IEEE/ANSI C37.20.7-2001 - Guide for Testing Medium-Voltage Metal-Enclosed • • • Switchgear for Internal Arcing Faults NFPA 70-2005 - National Electrical Code NFP A 70B-2002 - Electrical Equipment Maintenance " NFPA 70E-2004 - Electrical Safety in the Workplace 0-7803-9020-2/05/$20.00 ©200S IEEE. Page 98 Authorized licensed use limited to: Thapar Institute of Engineering & Technology. Downloaded on September 29,2020 at 05:09:32 UTC from IEEE Xplore. Restrictions apply.