Installation and Maintenance Manual IM 1058-6 Group: Applied Air Systems Part Number: IM 1058 Date: June 2015 Maverick® II Commercial Packaged Rooftop Systems Heating and Cooling Models MPS015F – 0050F 15 to 50 Tons R-410A Refrigerant MicroTech® III Unit Controller Energy Recovery Wheel Table of Contents Table of Contents General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Duct High Pressure Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Unit Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Convenience Receptacle (Field Powered) . . . . . . . . . . . . . . . . . . . 49 Hazard Identification Information . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Convenience Receptacle (Unit Powered) . . . . . . . . . . . . . . . . . . . 49 Mechanical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Condenser Fan Operation for Variable Speed Compressor Low Ambient Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 Installer Responsibilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 VFD Compressor Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Receiving Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Service Clearance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Ventilation Clearance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Overhead Clearance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Variable Speed Scroll Compressor . . . . . . . . . . . . . . . . . . . . . . . . . 56 Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 Operating States . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 Roof Curb Assembly and Installation . . . . . . . . . . . . . . . . . . . . . . . . 5 Mechanical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Rigging and Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Mechanical Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86 Check, Test, and Start Procedures . . . . . . . . . . . . . . . . . . . . . . . . . 87 Pre-Start of Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87 Condensate Drain Pipe Connection . . . . . . . . . . . . . . . . . . . . . . . . 15 Servicing Control Panel Components . . . . . . . . . . . . . . . . . . . . . . 87 Mechanical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Cabinet Weather Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Installing Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Electrical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Field Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Energy Recovery Wheel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91 Final Control Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92 Controller Settings for Normal Operation . . . . . . . . . . . . . . . . . . . . 92 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93 Performing Service Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . 93 Electrical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Control Panel Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96 Preparing Unit for Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Unit Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99 Spring Isolated Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Bearing Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100 Optional Gas Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Energy Recovery Wheel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101 Gas Furnace Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Segment Installation & Replacement . . . . . . . . . . . . . . . . . . . . . . 103 Optional Gas Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Wheel Drive Motor & Pulley Replacement . . . . . . . . . . . . . . . . . . 103 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Belt Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104 Optional Gas Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104 Start-Up Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Supply Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105 Optional Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105 Electric Heater Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Optional Modulating Hot Gas Reheat . . . . . . . . . . . . . . . . . . . . . . . 33 Modulating Hot Gas Reheat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Servicing Optional Electric Heater . . . . . . . . . . . . . . . . . . . . . . . . 105 Service and Warranty Procedure . . . . . . . . . . . . . . . . . . . . . . . . . 106 Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106 Optional Modulating Hot Gas Reheat . . . . . . . . . . . . . . . . . . . . . . . 34 Compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106 Optional Hot Water Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Hot Water Heater Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Optional Energy Recovery Wheel . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Energy Recovery Wheel Design . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Optional Outdoor Air Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 In-Warranty Return Material Procedure . . . . . . . . . . . . . . . . . . . . 106 Warranty Registration Form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107 Quality Assurance Survey Report . . . . . . . . . . . . . . . . . . . . . . 113 Appendix – Keypad/Display Menu Structure . . . . . . . . . . . . . . . . 114 Thermal Dispersion Airflow Measurement Technology . . . . . . . . . . 42 Unit Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Economizer Enthalpy Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 External Time Clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Exhaust Fan Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Proof-of-Airflow and Dirty Filter Switch . . . . . . . . . . . . . . . . . . . . . . 48 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 2 www.DaikinApplied.com General Information General Information This manual provides general information about the “F” vintage Daikin Commercial Packaged Rooftop Unit model MPS. In addition to an overall description of the unit, it includes mechanical and electrical installation procedures, commissioning procedures, sequence of operation information, and maintenance instructions. Unit Nameplate The MicroTech® III rooftop unit controller is available on “F” vintage rooftop units. For a detailed description of the MicroTech III components, input/output configurations, field wiring options and requirements, and service procedures, see OM 920. For operation and information on using and programming the MicroTech III unit controller, refer to the appropriate operation manual (see Table 1). Hazard Identification Information DANGER Dangers indicate a hazardous situation which will result in death or serious injury if not avoided. For a description of operation and information on using the keypad to view data and set parameters, refer to the appropriate program-specific operation manual (see Table 1). WARNING Warnings indicate potentially hazardous situations, which can result in property damage, severe personal injury, or death if not avoided. Table 1: Program Specific Unit Operation Literature Rooftop unit control configuration Manual bulletin number VFDs OM 844 - MD2 OM 895 - MD3 OM 1190 - MD4 OM 1191 - MD5 OM 847 - MD6 MPS Unit Controller Discharge Air Control (VAV or CAV) Space Comfort Control (SCC) OM 920 LonWorks Integration IM 918 BACnet Integration IM 917 BACnet IP Comm Module IM 916 The unit nameplate is located on the outside of the main control box door. It includes the unit model number, serial number, electrical characteristics, and refrigerant charge. CAUTION Cautions indicate potentially hazardous situations, which can result in personal injury or equipment damage if not avoided. Nomenclature (MPS 015–050) M P S – 015 – F G Daikin Packaged System Heat medium Y = None (cooling only) G = Natural gas E = Electric heat W = Hot water heat Nominal capacity (tons) Design vintage • 15F • 20/26G • 30–50 F www.DaikinApplied.com 3 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Mechanical Installation Mechanical Installation Installer Responsibilities Receiving Inspection The installation of this equipment shall be in accordance with the regulations of authorities having jurisdiction and all applicable codes. It is the responsibility of the installer to determine and follow the applicable codes. When the equipment is received, all items should be carefully checked against the bill of lading to be sure all crates and cartons have been received. If the unit has become dirty during shipment (winter road chemicals are of particular concern), clean it when received. CAUTION Sharp edges on sheet metal and fasteners can cause personal injury. This equipment must be installed, operated, and serviced only by an experienced installation company and fully trained personnel. All units should be carefully inspected for damage when received. Report all shipping damage to the carrier and file a claim. In most cases, equipment is shipped F.O.B. factory and claims for freight damage should be filed by the consignee. Before unloading the unit, check the unit nameplate to make sure the voltage complies with the power supply available. Service Clearance Allow service clearances as approximately indicated in Figure 1. Also, Daikin recommends providing a roof walkway to the rooftop unit as well as along each side of the unit that provides access to most controls and serviceable components. Figure 1: Service Clearances Evaporator/ Hot Gas Reheat Coil * 61-75 Ton Fan and Gas/Electric/Hot Water Heaters can be removed from either side Optional Energy Recovery Wheel (ERW) Assembly Fan Assembly (removal from this side only) 15-50 Ton Optional Hot Water Heat (removal from this side only*) B 60.00 (1524 mm) A 60.00 (1524 mm) 96.00 (2438 mm) Optional Energy Recovery Wheel Exhaust Air Fan Assembly IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Optional Gas Furnace or Electric Heat 15-50 Ton A = 72 (1828 mm) B = 60 (1524 mm) 4 61-75 Ton 60 (1524 mm) 72 (1828 mm) www.DaikinApplied.com Mechanical Installation Ventilation Clearance Overhead Clearance Below are minimum ventilation clearance recommendations. The system designer must consider each application and provide adequate ventilation. If this is not done, the unit may not perform properly. 1. Unit(s) surrounded by screens or solid walls must have no overhead obstructions over any part of the unit. Unit(s) Surrounded by a Screen or a Fence: 3. The following restrictions must be observed for overhead obstructions above the air handler section: 2. The area above the condenser must be unobstructed in all installations to allow vertical air discharge. 1. The bottom of the screen or fence should be at least 1 ft. (305 mm) above the roof surface. 2. The distance between the unit and a screen or fence should be as described in Figure 1. b. Overhead obstructions must be no less than 96" (2438 mm) above the top of the unit. 3. The distance between any two units within a screen or fence should be at least 120" (3048 mm). Unit(s) Surrounded by Solid Walls: 1. If there are walls on one or two adjacent sides of the unit, the walls may be any height. If there are walls on more than two adjacent sides of the unit, the walls should not be higher than the unit. 2. The distance between the unit and the wall should be at least 96" (2438 mm) on all sides of the unit. c. There must be no overhead obstructions in the areas above the outside air and exhaust dampers that are farther than 24" (610 mm) from the side of the unit. Roof Curb Assembly and Installation Locate the roof curb and unit on a portion of the roof that can support the weight of the unit. The unit must be supported to prevent bending or twisting of the machine. 3. The distance between any two units within the walls should be at least 120" (3048 mm). Do not locate outside air intakes near sources of contaminated air. If the unit is installed where windy conditions are common, install wind screens around the unit, maintaining the clearances specified (see Figure 1). This is particularly important to maintain adequate head pressure control when mechanical cooling is required at low outdoor air temperatures. NOTE: Low head pressure may lead to poor and erratic refrigerant feed control at the thermostatic expansion valve. The unit has automatic control of the condenser fans which should provide adequate head pressure control down to 20°F provided the unit is not exposed to windy conditions. The system designer is responsible for assuring the condensing section is not exposed to excessive wind or air recirculation. www.DaikinApplied.com a. There must be no overhead obstructions above the furnace flue, or within 9" (229 mm) of the flue box. 5 If building construction allows sound and vibration into the occupied space, locate the unit over a non-critical area. It is the responsibility of the system designer to make adequate provisions for noise and vibration in the occupied space. WARNING Mold can cause personal injury. Some materials such as gypsum wall board can promote mold growth when damp. Such materials must be protected from moisture that can enter units during maintenance or normal operation. Install the curb and unit level to allow the condensate drain to flow properly and allow service access doors to open and close without binding. The gasketed top surface of the curb seals against the unit when it is set on the curb. These flanges must not support the total weight of the duct work. See Installing Ductwork on page 16 for details on duct connections. It is critical that the condensate drain side of the unit be no higher than the opposite side. IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Mechanical Installation Assembly Instructions Assembly of a typical roof curb is shown in Figure 2. 1. Set curbing parts A thru G per dimensions shown over roof opening or on a level surface. Note location of supply air opening. Check alignment of all mating screw holes. 4. Position curb assembly over roof openings. Curb must be level within 0.25 inches from side to side and 1.50 inches over its length. Check that top surface of curb is flat with no bowing or sagging. 2. Screw curbing parts together using fasteners provided. Leave all screws loose until curb is checked to be square. 5. Weld curb assembly in place. Caulk all seams watertight. Remove backing from 0.25 × 1.50 wide gasket and apply to surfaces shown by crosshatching. 3. Square entire curbing assembly and securely tighten all screws. 6. Check that electrical connections are coordinated. Figure 2: Roof Curb Assembly (MPS 026G – 035F Example) IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 6 www.DaikinApplied.com Mechanical Installation Figure 3: Roof Curb Layout—MPS 015F – 020G www.DaikinApplied.com 7 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Mechanical Installation Figure 4: Roof Curb Layout—MPS 026G – 035F 2.00 [51 mm] 23.50 [597 mm] 2.00 [51 mm] 21.25 [540 mm] 71.38 [1813 mm] 87.25 [2216 mm] (INSIDE CURB) HOT WATER ONLY CHASE 2.00 [51 mm] 1.25 [32 mm] TYP 63.69 [1610 mm] 15.87 [403 mm] 1.00 [25 mm] 1.63 [41 mm] 19.00 [483 mm] 93.70 [2380 mm] 171.18 (INSIDE CURB) [4348 mm] PLAN VIEW 2.00 [51 mm] 1.00 [26 mm] 1.00 [26 mm] 3.75 [95 mm] 0.38 [9.7 mm] F 0.38 [9.7 mm] 2.00 [51 mm] 23.86 [606 mm] KNOCKOUT DETAIL CURB CROSS SECTION IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 8 www.DaikinApplied.com Mechanical Installation Figure 5: Roof Curb Layout—MPS 040F – 050F 2.00 [51 mm] 30.63 [778 mm] 28.25 [718 mm] 2.00 [51 mm] 71.38 [1813 mm] 87.25 [2216 mm] (INSIDE CURB) HOT WATER ONLY CHASE 2.00 [51 mm] 1.25 TYP [32 mm] 69.39 [1763 mm] 15.87 [403 mm] 1.00 [25 mm] 1.63 [41 mm] 26.00 [660 mm] 105.45 [2678 mm] 208.57 (INSIDE CURB) [5298 mm] PLAN VIEW 2.00 [51 mm] 1.00 [25 mm] 3.75 [95 mm] 2.00 [51 mm] 0.38 [9.7 mm] F 0.38 [9.7 mm] 28.92 [735 mm] CURB CROSS SECTION www.DaikinApplied.com 9 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Mechanical Installation Figure 6: MPS 015–020 Roof Curb with Energy Recovery Wheel IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 10 www.DaikinApplied.com Mechanical Installation Figure 7: MPS 026–035 Roof Curb with Energy Recovery Wheel www.DaikinApplied.com 11 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Mechanical Installation Figure 8: MPS 040–050 Roof Curb with Energy Recovery Wheel IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 12 www.DaikinApplied.com Mechanical Installation Rigging and Handling WARNING Only trained and qualified personnel should be allowed to rig loads or operate load rated cranes and/or hoist assemblies. Do not use a forklift to lift or maneuver the unit. Failure to use a load rated crane or hoist assembly to lift or maneuver the unit can cause severe personal injury and property damage. Use spreader bars, 96" to 100" (2438 to 2540 mm) wide to prevent damage to the unit cabinet. Avoid twisting or uneven lifting of the unit. The cable length from the bracket to the hook should always be longer than the distance between the outer lifting points. If the unit is stored at the construction site for an intermediate period, take these additional precautions: 1. Support the unit well along the length of the base rail. WARNING Use all lifting points. Improper lifting can cause property damage, severe pers al injury, or death. CAUTION Lifting points may not be symmetrical to the center of gravity of the unit. Ballast or unequal cable lengths may be required. Rigging holes for shackles are integral on the unit base. All six lifting points must be used for rigging the equipment. Use four independent lines, securing one end of a line to a unit base lifting point and the other end of the line to an associated spreader bar lifting point (see Figure 10 and Figure 11). Figure 9 is an example of an instruction label shipped with each unit. 2. Level the unit (no twists or uneven ground surface). 3. Provide proper drainage around the unit to prevent flooding of the equipment. 4. Provide adequate protection from vandalism, mechanical contact, etc. 5. Securely close the doors. 6. Cover the supply and return air openings. Table 4 and Table 5 lists the weight distribution at each of the lifting points on the unit (refer to Figure 10 and Figure 11). Table 6 details lifting point locations. Table 7 through Table 12 lists the weights of unit curbs and other sections of the unit. Table 2: Unit Base Weights Unit (Tons) Total Weight (lbs) 015 2655 017 2705 020 3610 026 3610 030 3610 035 3660 040 4685 050 4985 Figure 9: Rigging Label LIFT UNIT ONLY AS SHOWN SPREADER BARS REQUIRED Table 3: Unit Curb Weights Unit (tons) Curb Height (inches) Total Weight (lbs) Standard Unit MUST USE ALL OF THESE LIFTING LUGS FOR LIFTING UNIT. 015–035 040–050 14 341 24 504 14 461 24 706 Unit with Energy Wheel 015–035 040–050 www.DaikinApplied.com 13 14 458 24 674 14 619 24 908 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Mechanical Installation Table 4: Weight Distribution Locations (see Figure 10) Table 5: Weight Distribution Locations (see Figure 11) Distance Distance Unit (tons) L1 L2 L3 L4 Unit (tons) L1 L2 L3 040–050 42.2 66.6 58.3 60.9 015–035 35.5 62.0 52.0 040–050 40.0 69.0 89.0 Table 6: Weight Distribution — Energy Wheel Point Unit Percent of total A B C D E F G H 015–050 without Energy Wheel 11% 11% 20% 24% 16% 18% N/A N/A 015–035 with Energy Wheel 13% 12% 20% 21% 17% 17% N/A N/A 040–050 with Energy Wheel 12% 12% 13% 13% 12% 12% 13% 13% Table 7: Heat Section Weights Unit (tons) Table 10: Additional Weights - Motors/Exhaust Fans (015–020) Weights (lbs) High Gas Heat Low Gas Heat Electric Heat Hot Water Heat 015 200 100 120 017 200 100 120 020 200 100 026 270 135 030 270 035 270 040 050 HP Additional Motor Weight (lbs) Unit (tons) Additional Exhaust Fan Weight (lbs) 195 1 0 15–20 150 195 1.5 9 120 195 2 9 270 291 3 32 135 270 291 5 43 135 270 291 350 175 350 307 350 175 350 307 Table 11: Additional Weights - Motors/Exhaust Fans (026–050) Table 8: Curb Weights Additional Motor Weight (lbs) Unit (tons) Additional Exhaust Fan Weight (lbs) 7.5 0 26 150 10 25 30 150 15 125 35 150 20 175 40 200 25 225 50 200 30 275 HP Weight (lbs) Unit (tons)/ Curb Height (inches) without ERW with ERW 015–035/14 341 458 015–035/24 501 674 040–050/14 481 619 040–050/24 708 908 Table 9: Energy Recovery Section Weights Unit Size (tons) Weight (lbs) 015–020 1200 026–035 1540 040–050 1000 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Table 12: Additional Weights for 6-Row DX Coil and HGRH Coil 14 Weight (lbs) Unit Size (tons) 6 Row DX HGRH 15–20 118 70 26–35 164 82 40 187 92 50 231 92 www.DaikinApplied.com Mechanical Installation Condensate Drain Pipe Connection Figure 10: Rigging the Unit (MPS 026– 035 Example) The unit is provided with a 1" male NPT condensate drain connection. For proper drainage, level the unit and drain pan side to side and install a P-trap. Figure 12 shows the layout of the condensate drain connection. The distance from the drain pan outlet to the horizontal run of the P-trap should be a distance of twice the static pressure in the drain pan. Example: If the static pressure as measured in the drain pan is 1.5", then the distance between the drain outlet and the horizontal run should be 3". Draining condensate directly onto the roof may be acceptable; refer to local codes. Provide a small drip pad of stone, mortar, wood, or metal to protect the roof against possible damage. If condensate is piped into the building drainage system, pitch the drain line away from the unit a minimum of 1/8" per foot. The drain line must penetrate the roof external to the unit. Refer to local codes for additional requirements. Sealed drain lines require venting to provide proper condensate flow. Where the cooling coils have intermediate condensate pans on the face of the evaporator coil, copper tubes near both ends of the coil supply drainage to the main drain pan. Verify the tubes are in place and open before putting the unit into operation. Figure 11: Rigging the Unit (MPS 040–050 Example) G E A Periodically clean to prevent microbial growth/algae buildup from plugging the drain and causing the drain pan to overflow. Clean drain pans to prevent the spread of disease. Cleaning should be performed by qualified personnel. C F D WARNING H Drain pans must be cleaned periodically. Material in uncleaned drain pans can cause disease. Cleaning should be performed by qualified personnel. L4 L3 B Figure 12: Condensate Drain Connection L2 L1 www.DaikinApplied.com 15 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Mechanical Installation Damper Assemblies The optional damper assemblies described in this section are ordered with factory-installed actuators and linkages. The following sections describe the operation and linkage adjustment of the factory option. Cabinet Weather Protection This unit ships from the factory with fully gasketed access doors and cabinet caulking to provide weather resistant operation. After the unit is set in place, inspect all door gaskets for shipping damage and replace if necessary. Protect the unit from overhead runoff from overhangs or other such structures. Figure 13: Damper Assembly CAUTION Transportation, rigging, or maintenance can damage the unit’s weather seal. Periodically inspect the unit for leakage. Standing moisture can promote microbial growth, disease, or damage to the equipment and building Linkage Installing Ductwork Actuator Economizer Dampers On vertical-supply/vertical-return units, if a Daikin roof curb is not used, the installing contractor should make an airtight connection by attaching field fabricated duct collars to the bottom surface of the unit’s duct opening. Do not support the total weight of the duct work from the unit. See roof curb layouts in Figure 3 on page 7, Figure 4 on page 8 or Figure 5 on page 9. Table 13: Rated Airflow As the single actuator modulates, the outside air dampers open, the return air dampers close, and the exhaust air exits the unit through the gravity relief dampers. The economizer comes with manually adjustable linkage (Figure 13). The damper is set so that the crankarm moves through a 90-degree angle to bring the economizer dampers from full open to full close. Mechanical stops are placed in the crankarm mounting bracket. Do not remove stops. Driving the crankarm past the stops results in damage to the linkage or damper. Outdoor Air Dampers (0% to 30%) These dampers are intended to remain at a fixed position during unit operation, providing fresh air quantities from 0 to 30% of the total system airflow, depending on the damper setting. The damper position may be set at the unit controller keypad (refer to OM 920 for further detail). During unit operation, the damper is driven to the position set at the unit controller. During the off cycle, the damper is automatically closed. Unit Size (tons) AHRI Rated Airflow 015 3750 017 4375 020 5000 026 6875 030 7500 035 8750 040 10000 050 12500 Use flexible connections between the unit and ductwork to avoid transmission of vibration from the unit to the structure. To minimize losses and sound transmission, design duct work per ASHRAE and SMACNA recommendations. Where return air ducts are not required, connect a sound absorbing T or L section to the unit return to reduce noise transmission to the occupied space. Ductwork exposed to outdoor conditions must be built in accordance with ASHRAE and SMACNA recommendations and local building codes. WARNING Mold can cause personal injury. Materials such as gypsum wall board can promote mold growth when damp. Such materials must be protected from moisture that can enter units during maintenance or normal operation. IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 16 www.DaikinApplied.com Mechanical Installation Installing Duct Static Pressure Sensor Taps Figure 14: Static Pressure Tubing Knockout Location For all VAV units, duct static pressure taps must be field installed and connected to the static pressure sensor 1 (SPS1) in the unit. Sensor SPS1 is standard on VAV units and is located in the main control panel. Carefully locate and install the duct static pressure sensing tap. Improperly locating or installing the sensing tap causes unsatisfactory operation of the entire variable air volume system. Below are pressure tap location and installation recommendations. The installation must comply with local code requirements. 1. Install a tee fitting with a leak-tight removable cap in each tube near the sensor fitting. This facilitates connecting a manometer or pressure gauge if testing is required. 2. Use different colored tubing for the duct pressure (HI) and reference pressure (LO) taps, or tag the tubes. Daikin recommends 3/16" ID tubing. Figure 15: Duct Static Pressure Sensing Tubing Installation Main Control Panel Condenser Section 3. Locate the duct pressure (HI) tap near the end of a long duct to ensure that all terminal box take-offs along the run have adequate static pressure. 4. Locate the duct tap in a nonturbulent flow area of the duct. Keep it several duct diameters away from take-off points, bends, neckdowns, attenuators, vanes, or other irregularities. HI Line LO Line 5. Use a static pressure tip (Dwyer A302 or equivalent) or the bare end of the plastic tubing for the duct tap. (If the duct is lined inside, use a static pressure tip device.) Roof Remote Sense Point 6. Install the duct tap so that it senses only static pressure (not velocity pressure). If a bare tube end is used, it must be smooth, square (not cut at an angle) and perpendicular to the airstream (see Figure 15). Ductwork (Remote Location) To Sensor HI Input Rubber Grommet To Sensor LO Input 7. Locate the reference pressure (LO) tap near the duct pressure tap within the building. If the tap is not connected to the sensor, unsatisfactory operation will result. 8. Route the tubes through the curb and feed them into the unit through the knockout in the bottom of the control panel (see Figure 14). Connect the tubes to appropriate barbed fittings (on SPS1) in the control panel. (Fittings are sized to accept 3/16" ID tubing.) www.DaikinApplied.com SPS1 17 Tubing Extends Through Approx. 1/8” Pressure Sensing Tubing IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Mechanical Installation Installing Building Static Pressure Sensor Taps Figure 16: Outdoor Static Pressure Tubing Installation If a unit has building static pressure control capability, you must field install and connect static pressure taps to the static pressure sensor SPS2 in the unit. This sensor is located at the bottom of the main control panel next to SPS1. Carefully locate and install the two static pressure sensing taps. Improper location or installation of the sensor taps causes unsatisfactory operation. Below are pressure tap location and installation recommendations for both building envelope and lab, or “space within a space” pressure control applications. The installation must comply with local code requirements. CAUTION Fragile sensor fittings. If you must remove tubing from a pressure sensor fitting, use care. Do not use excessive force or wrench the tubing back and forth to remove or the fitting can break off and damage sensor. Lab Pressurization Applications 1. Install a “T” fitting with a leak-tight removable cap in each tube near the sensor fitting. This facilitates connecting a manometer or pressure gauge if testing is required. Building Pressurization Applications 1. Install a tee fitting with a leak-tight removable cap in each tube near the sensor fitting. This facilitates connecting a manometer or pressure gauge if testing is required. 2. Use different colored tubing for the controlled space pressure (high) and reference pressure (low) taps, or tag the tubes. 2. Locate the building pressure (high) tap in the area that requires the closest control. Typically, this is a ground level floor that has doors to the outside. 3. Regardless whether the controlled space is positive or negative with respect to its reference, locate the high pressure tap in the controlled space (the setpoint can be set between -0.2" and 0.2" wc). 3. Locate the building tap so it is not influenced by any source of moving air (velocity pressure). These sources may include air diffusers or outside doors. 4. Locate the reference pressure (low) tap in the area surrounding the controlled space. Not locating the reference tap to the sensor results in unsatisfactory operation. 4. Route the building tap tube through the curb and feed it into the unit through the knockout in the bottom of the control panel (refer to Figure 14). Connect the 3/16" ID tube to the (high) fitting for sensor SPS2. 5. Locate both taps so they are not influenced by any source of moving air (velocity pressure). These sources may include air diffusers or doors between the high and low pressure areas. 5. Locate the reference pressure (low) tap on the roof. Keep it away from the condenser fans, walls, or anything else that may cause air turbulence. Mount it high enough above the roof so it is not affected by snow. Not connecting the reference tap to the sensor results in unsatisfactory operation. 6. Route the building tap tube between the curb and the supply duct and feed it into the unit through the knockout in the bottom of the control panel. 7. Connect the tube to the (high) fitting for sensor SPS2. 6. Use an outdoor static pressure tip (Dwyer A306 or equivalent) to minimize the adverse effects of wind. Place some type of screen over the sensor to keep out insects. Loosely packed cotton works well. 7. Route the outdoor tap tube out of the main control panel through a small field-cut opening in the upright. Seal the penetration to prevent water from entering. Connect the 3/16" ID tube to the (low) fitting for sensor SPS2. IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 18 www.DaikinApplied.com Electrical Installation Electrical Installation Field Power Wiring Wiring must comply with all applicable codes and ordinances. The warranty is voided if wiring is not in accordance with these specifications. A ground lug is provided in the control panel. Size the grounding conductor in accordance with Table 250-95 of the National Electrical Code. According to the National Electrical Code, a disconnecting means shall be located within sight of and readily accessible from the air conditioning equipment. The unit can be ordered with an optional factory mounted disconnect switch. This switch is not fused. Power leads must be over-current protected at the point of distribution. The maximum rated overcurrent protection device (MROPD) value appears on the unit nameplate. In compliance with the National Electrical Code, a 115 V factory mounted service receptacle outlet is provided. This outlet must be powered by a field connected 15 A, 115 V power supply. Leads are brought into the unit through a 7/8" knockout in the bottom of the main control panel. All Units All units are provided with internal power wiring for single point power connection. The power block or an optional disconnect switch is located within the main control panel. Field power leads are brought into the unit through knockouts in the bottom of the main control panel (see Figure 17 and also Table 14). Refer to the unit nameplate to determine the number of power connections. NOTE: To wire entry points, refer to certified drawings for dimensions. WARNING Hazardous voltage. Can cause severe injury or death. Disconnect electric power before servicing equipment. More than one disconnect may be required to de-energize the unit. The preferred entrance for power cables is through the bottom knockouts provided on the unit. If a side entrance is the only option, a hole may be drilled in the stationary upright. Table 14: Recommended Field Power Wiring Ampacity (MCA) No. of Power Wires per Phase Wire Gauge 20 25 35 50 65 85 100 115 130 150 175 200 230 255 300 350 400 460 510 600 690 765 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 3 3 3 14 12 10 8 6 4 3 2 1 1/0 2/0 3/0 4/0 250 1/0 2/0 3/0 4/0 250 3/0 4/0 250 Insulation Temperature Rating (°C) 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 Notes: 1. All wire sizes assume separate conduit for each set of parallel conductors. 2. All wire sizes based on NEC Table 310-16 for 75°C THW wire (copper). Canadian electrical code wire ampacities may vary. 3. All wire sizes assume no voltage drop for short power leads. The minimum circuit ampacity (MCA) is shown on the unit nameplate. Refer to Table 14 for the recommended number of power wires. Copper wire is required for all conductors. Size wires in accordance with the ampacity tables in Article 310 of the National Electrical Code. If long wires are required, it may be necessary to increase the wire size to prevent excessive voltage drop. Wires should be sized for a maximum of 3% voltage drop. Supply voltage must not vary by more than 10% of nameplate. Phase voltage imbalance must not exceed 2%. (Calculate the average voltage of the three legs. The leg with voltage deviating the farthest from the average value must not be more than 2% away.) Contact the local power company for correction of improper voltage or phase imbalance. Figure 17: MPS Power Wiring Knockout Locations CAUTION Provide proper line voltage and phase balance. Improper line voltage or excessive phase imbalance constitutes product abuse. It can cause severe damage to the unit's electrical components. www.DaikinApplied.com 19 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Electrical Installation Electrical Installation Field Control Wiring The Maverick rooftop units are available with the following field control connections: Descriptions of these field connections are included in the MicroTech III Unit Controller manual (OM 920). • Space sensor. • Space sensor with setpoint adjustment. • Fan operation output. • VAV box output. • Remote alarm output. WARNING Electrical shock hazard. Can cause severe injury or death. Connect only low voltage NEC Class II circuits to terminal block TB2. • External discharge air temperature reset. • Outdoor air damper minimum position adjustment. IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 20 www.DaikinApplied.com Preparing Unit for Operation Preparing Unit for Operation Spring Isolated Fans Figure 18: Spring Mounts WARNING Moving machinery hazard. Can cause severe injury ordeath. Before servicing equipment, disconnect power and lockoff. More than one disconnect may be required to de-energizeunit. Prior to operating the fans for the first time, refer to Check, Test, and Start Procedures on page 87. Releasing Spring Mounts The spring-mounted supply fan is locked down with four shipping bolts for shipment. Remove each shipping bolt before operating the fans. Figure 18 shows a typical spring mount with a height adjustment nut and a shipping bolt.After removing the shipping bolts, rock the fan assembly by hand to check for freedom of movement. Adjusting Spring Mounts During operation all fans should ride level. Level the fan assembly by performing the following: 1. Loosen the 3/8" cap screw (do not remove). 2. Loosen the spring cap nut. 3. Rotate the 5/8" adjustment nut counter-clockwise to raise the fan assembly, or clockwise to lower the fan assembly. 4. Tighten the 3/8" cap screw. 5. Tighten the spring cap nut. www.DaikinApplied.com 21 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Optional Gas Heat Optional Gas Heat Gas Furnace Design If the 8th digit in the model number is a “G”, the rooftop unit was furnished with a factory installed furnace (Example, MPS035FG). The Maverick commercial rooftop units are available with either the low heat input or the high heat input furnace (see capacities in Table 15). This packaged gas heat rooftop unit is designed for outdoor non-residential installations only. Figure 19: Gas Heat Section The gas heat furnace design consists of a tubular heat exchanger, in-shot burner manifold with gas valve, induced combustion blower, gas heat DDC control module and all operational safeties. The tubular heat exchanger can come with the standard aluminized steel construction or the optional stainless steel construction. The safety switches include a high-limit temperature switch, an auxiliary high-limit switch, a combustion blower proof of airflow, and the flame roll-out switch (see Figure 20). Field Gas Piping The high limit switch is an automatic reset switch and it opens up at 160°F to shut the furnace down and closes at 130°F. The auxiliary limit switch is a manual reset and opens up at 180°F to shut the furnace down. Gas Heating Capacity Data Table 15: MPS 015F – 050F Gas Heating Capacities Unit Size Data 015–020 026–035 040–050 Low Heat High Heat Low Heat High Heat Low Heat High Heat Heating Input (MBh) 240 480 300 600 400 800 Heating Output (MBh) 192 384 240 480 320 640 Steady State Efficiency 80% 80% 80% 80% 80% 80% Number of Stages 2 4 2 4 2 4 Turndown1 4:1 8:1 4:1 8:1 4:1 8:1 Minimum Airflow 2960 5920 3700 7400 4900 9800 Maximum Temperature Rise 60°F 100°F 60°F 85°F 60°F 85°F Gas Main Pressure Natural Gas (in. wc) 7-14 7-14 7-14 7-14 7-14 7-14 Liquid Propane (in. wc) 12-14 12-14 12-14 12-14 12-14 12-14 Stage 1 (in. wc) 1.2 1.2 1.2 1.2 1.2 1.2 Stage 2 (in. wc) 3.2 3.2 3.2 3.2 3.2 3.2 Low fire2 0.4 0.4 0.4 0.4 0.4 0.4 Manifold Pressure Natural Gas (per gas valve) Propane Stage 1 (in. wc) 2.3 2.3 2.3 2.3 2.3 2.3 Stage 2 (in. wc) 10.0 10.0 10.0 10.0 10.0 10.0 Low fire2 N/A Note: 1 Modulating gas heat only. 2 Modulating gas heat not available with propane. IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 22 www.DaikinApplied.com Optional Gas Heat Figure 20: Staged Furnace Assembly Warranty Exclusion Ventilation & Flue Pipe Requirements Warranty is void if the furnace is operated in the presence of chlorinated vapors, if the airflow through the furnace is not in accordance with rating plate, or if the wiring or controls have been modified or tampered with. The Daikin rooftop unit is equipped with an outdoor air hood to supply adequate combustion air. The unit also has a flue outlet assembly and requires no additional chimney, flue pipe, Breidert cap, draft inducer, etc. Factory Checkout WARNING Hot surface hazard. Can cause severe equipment damage, personal injury, or death. Allow burner assembly to cool before servicing equipment. WARNING Units equipped with gas heating must not be operated in an atmosphere contaminated with chemicals which will corrode the unit such as halogenated hydrocarbons, chlorine, cleaning solvents, refrigerants, swimming pool exhaust, etc. Exposure to these compounds may cause severe damage to the gas furnace and result in improper or dangerous operation. Operation of the gas furnace in such a contaminated atmosphere constitutes product abuse and will void all warranty coverage by the manufacturer. Questions regarding specific contaminants should be referred to your local gas utility. www.DaikinApplied.com 23 This complete furnace was fired and tested at the factory. The unit was fired through several complete sequences of start-up through shutoff to check operation. A check was made of the air switch, gas pressure switch, high limit operation. This checkout normally eliminates on-the-job start-up problems; however, the equipment is subject to variable job conditions and shipping shocks can change adjustments, cause damage, and loosen connections and fasteners. Therefore, it is necessary to go through the complete start-up procedure even though the unit may appear to be operating properly. IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Optional Gas Heat Installation IMPORTANT This furnace must be installed by an experienced professional installation company that employs fully trained and experienced technicians. Install the furnace in accordance with the manufacturer's instructions and local codes. In the absence of local codes, follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or the CSA B149.1, Natural Gas and Propane Installation Code. Outdoor Air (OA) Hood The OA hood (Figure 22) is not installed at the factory becauseit would increase the width of the unit beyond the allowableshipping width. The hood is shipped in a box in the fansection. The OA hoods must be installed over the outdoor air openings. 1. Remove and discard the shipping covers. 2. Position the hood over the OA openings. 3. Line assembly holes up. WARNING Sharp edges hazard. Can cause personal injury or death. Sheet metal parts, self-tapping screws, clips, and similar itemsinherently have sharp edges, and it is necessary that theinstaller exercise caution when handling these items. 4. Install screws to fasten the OA hood. The OA hoods must be installed before the furnace is operated. Figure 22: Outdoor Air (OA) Hood Installation Flue Box The flue box (Figure 21) is not installed at the factory because it would increase the width of the unit beyond the allowable shipping width. The flue box must be installed over the combustion exhaust openings. All holes are prepunched, the fasteners are furnished and everything is shipped inside the fan section. 1. Remove and discard the shipping covers. 2. Position the flue box over the exhaust openings. 3. Line assembly holes up. 4. Install screws to fasten the flue box to the side of the unit. Figure 21: Flue Box Installation IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 24 www.DaikinApplied.com Optional Gas Heat Electrical Gas Piping The Daikin burner receives its electrical power from the main unit control panel. No additional power wiring must be routed to the burner. The sequencing of the burner is also controlled through this panel and therefore is factory wired. No additional wiring will be required. Gas piping must be sized to provide the minimum required pressure at the burner when the burner is operating at maximum input. Consult your local utility on any questions on gas pressure available, allowing piping pressure drops, and local piping requirements. DANGER If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury, or loss of life. A. This appliance does not have a pilot. It is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand. B. Before operating, smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. What to do if you smell gas: • Do not try to light any appliance. Install all piping in accordance with the National Fuel Gas Code (ANSI Z223.1), (NFPA 54-1999) and any applicable local codes. The proper size piping must be run from the meter to the gas burner without reductions. Undersized piping will result in inadequate pressure at the burner. The pressure will be at its lowest when it is needed the most, at times of maximum demand. Therefore, it can cause intermittent hard-to-find problems because the problem may have left before the service technician has arrived. Avoid the use of bushings wherever possible. Remove all burrs and obstructions from pipe. Do not bend pipe; use elbows or other pipe fittings to properly locate pipe. A drip leg and a manual shut-off must be installed in the vertical line before each burner such that it will not freeze. Install unions so gas train components can be removed for service. All pipe threads must have a pipe dope which is resistant to the action of LP gas. After installation, pressurize the piping as required and test all joints for tightness with a rich soap solution. Any bubbling is considered a leak and must be eliminated. Do not use a match or flame to locate leaks. • Do not touch any electric switch, do not use any phone in your building. • Immediately call your gas supplier from a phone in a neighboring building. Follow the gas supplier's instructions. • If you cannot reach your gas supplier, call the fire department. C. Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, don't try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion. D. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water. Gas Piping Routing Into Unit On-The-Roof Piping 1. Remove knockout on upright (refer to Figure 23). 2. Route gas supply pipe through hole. Carefully plan pipe route and fitting locations to avoid interference with swinging of doors, etc. Figure 23: Piping Schematic Gas Pressure Requirements The pressure furnished to the main gas valve must not exceed 13.9" wc. When the supply pressure is above 13.9" wc, a high pressure regulator must precede the appliance gas pressure regulator. The inlet gas pressure must not exceed the maximum pressure rating of the high pressure regulator, and the outlet pressure must furnish gas to the appliance pressure regulator within the pressure range mentioned above. Field Gas Piping 7.0" (177.8) www.DaikinApplied.com 25 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Optional Gas Heat Table 16: Capacity of Pipe Natural Gas (CFH) With Pressure Drop of 0.3" W.C. & Specific Gravity of 0.60 Pipe Size-inches (Ips) Pipe Length (ft) ½ ¾ 1 1¼ 1½ 2 2½ 3 4 10 132 278 520 1050 1600 2050 4800 8500 17500 20 92 190 350 730 1100 2100 3300 5900 12000 30 73 152 285 590 890 1650 2700 4700 9700 40 63 130 245 500 760 1450 2300 4100 8300 50 56 115 215 440 670 1270 2000 3600 7400 60 50 105 195 400 610 1150 1850 3250 6800 70 46 96 180 370 560 1050 1700 3000 6200 80 53 90 170 350 530 990 1600 2800 5800 90 40 84 160 320 490 930 1500 2600 5400 100 38 79 150 305 460 870 1400 2500 5100 125 34 72 130 275 410 780 1250 2200 4500 150 31 64 120 250 380 710 1130 2000 4100 175 28 59 110 225 350 650 1050 1850 3800 200 26 55 100 210 320 610 980 1700 3500 NOTE: Use multiplier below for other gravities and pressure drops. Sequence of Operation (Staged Control) Table 17: Specific Gravity Other Than 0.60 Specific Gravity Multiplier 0.50 1.100 0.60 1.000 0.70 0.936 0.80 0.867 0.90 0.816 1. Unit DDC control calls for heat. 1.00 0.775 2. Furnace DDC control module receives a call for heat. Low Heat Option (2 Stage Control) The following details the sequence of operation for the low heat option. Propane-Air 1.10 3. High limit switch is checked for safe condition. 0.740 4. Proof of airflow switch is check for combustion airflow. Propane 1.55 0.622 5. 60 second prepurge cycle starts. Butane 2.00 6. Spark ignitor is activated for 3 seconds. 0.547 7. Gas valve receives a command for stage 1 of heat. Table 18: Pressure Drop Other Than 0.3" 8. Burner is ignited. Pressure Drop Multiplier Pressure Multiplier 0.1 0.577 1.0 1.83 0.2 0.815 2.0 2.58 10. Furnace DDC controller receives a stage 2 heat command. 0.3 1.000 3.0 3.16 11. Gas valve receives a command for stage 2 of heat. 0.4 1.16 4.0 3.65 0.6 1.42 6.0 4.47 0.8 1.64 8.0 5.15 9. Unit DDC controller calls for stage 2 of heat. High Heat Option (4 Stage Control) For a unit with the optional high heat the above sequence is followed for the first two stages. For the remaining 2 stages the above procedure is repeated on the second furnace module. IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 26 www.DaikinApplied.com Optional Gas Heat Sequence of Operation (Modulating Burner) Low Heat Option with Modulation High Heat Option with Modulation The following details the sequence of operation for the low heat option. The following details the sequence of operation for the high heat option. This option includes dual burners with one being modulating and the other being 2 stage control. 1. Unit DDC controller calls for heat. 2. Furnace DDC control module receives a call for heat. 1. Unit DDC controller calls for heat. 3. Furnace safety switches and DDC control are checked for safe conditions. 3. High limit switch is checked for safe condition. 2. Top Furnace DDC control module receives a call for heat. 4. 45 second prepurge cycle starts. Proof of airflow switch is checked for combustion airflows. 4. Proof of airflow switch is checked for combustion airflow. 5. 45 second prepurge cycle starts. 5. Spark ignitor is activated. 6. Spark ignitor is activated. 6. Gas valve receives a signal to open fully. 7. Gas valve receives a signal to open fully. 7. Burner is ignited and runs for 20 seconds in high fire. 8. Burner is ignited and runs for 30 seconds in high fire NOTE: If call for heat is interrupted during this timing, the furnace will be locked in for the 20 seconds cycle. 8. Gas valve and induction blower motor receives a signal to modulate burner output to match the unit discharge air temperature setting. 9. Modulating burner gas valve and induction blower motor receives a signal to modulate burner output to match the unit discharge air temperature setting. 10. If modulating burner is unable to meet discharge temperature set point, furnace DDC control calls for third stage of heating. The top furnace is reduced to low (50%) fire. The bottom furnace is sequenced on per stage furnaces sequence of operation (steps 2 - 8). 11. Staged burner gas valve receives a signal to open to 50%. 12. Modulating burner gas valve and induction blower motor receives a signal to modulate burner output to match the unit discharge air temperature setting. 13. If stage 3 and modulating furnace is unable to meet discharge temperature setpoint, furnace DDC controller calls for stage 4 heat. The bottom furnace will stage up to high fire and the modulating furnace will reduce to 50% operation. 14. Staged burner gas valve receives a signal to open fully. 15. Modulating furnace's gas valve and induction blower motor receives a signal to modulate burner output to match the unit discharge air temperature setting. www.DaikinApplied.com 27 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Optional Gas Heat Start-Up Procedures Start-up and service of this equipment must be performed by trained and experienced technicians. It is highly recommended that the initial start-up and future service be performed by Daikin trained technicians who are familiar with working on live equipment. A representative of the owner or the operator of the equipment should be present during start-up to receive instructions in the operation, care and adjustment of the unit. Start-Up Responsibility The start-up organization is responsible for determining that the furnace, as installed and as applied, will operate within the limits specified on the furnace rating plate. 1. The furnace must not operate at an airflow below the specified Minimum Airflow CFM (refer to Table 15 on page 22). On variable air volume systems it must be determined that the furnace will not be operated if or when system cfm is reduced below the specified minimum airflow cfm. WARNING Overheating or failure of the gas supply to shut off can cause equipment damage, severe personal injury or death. Turn off the manual gas valve to the appliance before shutting off the electrical supply. DANGER If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury, or loss of life. 2. It must be established that the gas supply is within the proper pressure range (refer to Table 15 on page 22). Operating Procedures Before Start-Up 1. Notify inspectors or representatives who may be required to be present during start-up of gas fuel equipment. These could include the gas utility company, city gas inspectors, heating inspectors, etc. A. This appliance does not have a pilot. It is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand. 2. Review the equipment and service literature and become familiar with the location and purpose of the furnace controls. Determine where the gas and power can be turned off at the unit and before the unit. B. Before operating, smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. What to do if you smell gas: 3. Determine that power is connected to the unit and available. • Do not try to light any appliance. 4. Determine that the gas piping, meter, and service regulator have been installed, tested, and meet the equipment requirements. • Do not touch any electric switch, do not use any phone in your building. • Immediately call your gas supplier from a phone in a neighboring building. Follow the gas supplier's instructions. 5. Determine that proper instruments will be available for the start-up. A proper start-up requires the following: voltmeter, manometer or gauges with ranges for both manifold pressure and inlet gas pressure. • If you cannot reach your gas supplier, call the fire department. C. Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, don't try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion. Start-Up Preliminary Close gas main. 1. Check the burner fan wheel for binding, rubbing, or loose setscrews. D. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water. IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 2. Check power. 3. Purge the gas lines. 4. Leak check. Using a rich soap-water mixture and a brush, check the gas lines for leaks. Correct all leaks before starting furnace. 28 www.DaikinApplied.com Optional Gas Heat Service Start-Up 1. Set the thermostat to the lowest setting. The furnace DDC controller has diagnostic information for troubleshooting the furnace operation. The ignition control module has a LED light that will flash when an abnormal condition occurs. See Table 19 and Table 20 for an explanation of the diagnostic information. 2. Turn off all electric power to the appliance. 3. This appliance is equipped with an ignition device which automatically lights the burner. Do NOT try to light the pilot by hand. 4. Open the control access panel. Maintenance 5. Turn the gas control clockwise to “OFF”. Planned maintenance is the best way to avoid unnecessary expense and inconvenience. Have this system inspected at regular intervals by a trained and experienced service technician. The following service intervals are typical for average situations but will have to be adjusted to suit your particular circumstances. 6. Wait five (5) minutes to clear out any gas. Then, smell for gas, including near the floor. If you smell gas, STOP! Follow step “B” in the DANGER label on this page. If you don't smell gas, proceed to the next step. 7. Turn the gas control counter-clockwise to “ON”. Fuel pressure settings and control settings should be made only by persons thoroughly experienced with the burner and control system, and must not be tampered with by persons without such experience. 8. Close the control access panel. 9. Turn on all electric power to the appliance. 10. Set thermostat to desired setting. 11. If the furnace will not operate, refer to Turning off Gas to the Unit, and call your service technician or gas supplier. Turning off Gas to the Unit 1. Set the thermostat to the lowest setting. Always replace covers on burner controls and boxes as the electrical contacts are sensitive to dust and dirt. Perform maintenance of controls, gas valves, and other components in accordance with instructions contained in the manufacturer's bulletins. Monthly 2. Turn off all electrical power to the appliance if service is to be performed. Check air filters and replace if dirty. 3. Open the control access panel. Twice Yearly 4. Turn the gas control knob clockwise to “OFF”. Do not force. 1. Burner Air - Check burner fan wheel for dirt buildup and lint. Check combustion air intake louver and flue box for dirt buildup and accumulation of windborne debris. 5. Close the control access panel. 2. Cleaning - Inspect flue tubes and combustion chamber, cleaning as required. Keep burner vestibule clean. Dirt and debris can result in burner air blockages. Yearly Gas Train -Check all valves, piping and connections for leakage. Inspect and clean flame rod, ignition electrode, and burner manifold. Condensate Pan/Drain/P-Trap - Check pan, drain, and p-trap. www.DaikinApplied.com 29 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Optional Gas Heat Ignition Control Module for Gas Furnace Figure 24: Typical Staged Gas Furnace Electrical Schematic with Sensor L1 L2 B W W 1 B 115VAC 1016-427 Ignition Module Gr 2 40VA BL B Gnd W Y 24VAC G COM C MV PS2 Y 2 Stage Gas Valve Y C BL MV OR HI ROS1 ROS2 Y PS1 W BL X R HV OR 2 APS Y 1 Y R OR Igniter FS W Flame Sensor W APS ROS1 ROS2 L1 IND B Comb Fan Motor Airflow Proving Switch Roll Out Switch #1 Roll Out Switch #2 W 1/4" quick connect termination to harness from main control panel Terminal Block Ignition Control Module LED Diagnostics The following LED indicators can be used to diagnose faults associated with the staged gas furnace. IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Table 19: LED Indicator and Fault Conditions 30 Indicator Fault Condition Steady Off No power or control hardware fault Steady On Power applied, control OK 1 Flash Combustion fan motor energized, pressure switch open 2 Flashes Combustion fan motor off, pressure switch closed 3 Flashes Ignition lockout from too many trials 4 Flashes Ignition lockout from too many flame losses within single call for heat 5 Flashes Control hardware fault detected www.DaikinApplied.com Optional Gas Heat Ignition Control Module for Modulating Gas Furnace Figure 25: Typical Modulating Gas Furnace Electrical Schematic with Sensor L1 L2 WHT BLK 115 VAC 40VA OR G Limit Press Switch R WHT T9 Flame J9 Inducer J8 T7 T5 + BLK WHT Flame Sensor HS I MJ W + BRN St atus LED J4 0-10V DC input signal BLU MV RTN MV GRY - RED MOD GRY Modulating Gas Valve RED MOD RTN J3 OR G APS WH T GND T4 T2 Neutral Hot BLK WH T 24V AC ROS2 24VAC 115 VAC ROS1 BLU WHT J5 24VAC Comm Po rt BLK Combustion Board WHT DSI Board RED Spark Electrode Neutral WH T Hot BLK M Variable Inducer 0-10V DC 120 VAC Pre ssu re Tr ansducer T3 T6 Neutral Ground GRN Gn d + T1 Sensing hose to fan APS ROS1 ROS2 Airflow Prov ing Sw itch Roll Out Switch #1 Roll Out Switch #2 Variable Furnace Controller LED Diagnostic Informatio 1/4" Quick Connec t Termination Terminal Block Table 20: LED Indicator and Fault Conditions n Indicator Fault Condition Daikin's furnace controller is an electronic device that delivers Flash(es ) C olor Condition No power or control hardware fault Indicator Fault Steady Off full control of the modulating furnace. Control includes Condition Of f N/A N o power to Contro l sequencing, ignition,Steady safety, the control valve,or no 24VAC power Onmodulation Re d of C ontrol Fault Detected Steady On Control fault detected or no 24 VAC power and the induced draft motor. InputsRetod theC furnace board 1 ombustioncontrol f an motor energiz ed, Pressure switch open Combustion fan motor energized, pressure switch open 1 Flash 2 analog Re d Inducer air pressure reads above ze ro level w hen the inducer is of f are an a 0-10V signal. The signal will modulate the Inducer air pressure reads above zero level when the 3 load. Safety Re d inputs F lame include is ON when it should be OFF or 2 Flashes flame is OFF when it should be ON inducer is off burner down to 25% of full pressure 4 Re d G as valve ON when it should be OFF or OFF when it should be ON Flame is on when is should be off or flame is off when it line and electrical connection fromRe the 5 d airflow S afetyproofing rela y ON wswitch hen it should be OFF3orFlashes OFF when it should be ON should be on and electrical connection rollout Control 6 from the Re d Eswitches. xcessi ve plenum temperature Gas valve is on when is should be off or gas valve is off 4 Flashes Re d modulating High limit switch open or fuse open board outputs are to the7 igniter board, gas valve, when it should be on 8 Re d P ressure sw itch fa iled to operate or m odulation current is incorrect and to the induce draft motor. Safety relay is on when it should be off or safety relay is off 9 Slow 1 2 3 Rapi d The following LED indicators can Re d S afety startup fa iled to validate induc Green Normal operation -No call for heat G reen Call for heat G reen Gas ON -ca ll for heat G reen Gas ON -no ca ll for heat Amber be usedRetr toydiagnose faults Ignition Control Module LED Diagnostics associated with the modulating gas furnace. www.DaikinApplied.com 31 5 Flashes er air pat h when it should be on 6 Flashes Excessive plenum temperature 7 Flashes High limit switch is open or fuse is open 8 Flashes Pressure switch failed to operate or modulation current is incorrect Slow Flash Normal operation - no call for heat 1 Slow Flash Call for heat 2 Slow Flashes Gas on - call for heat 3 Slow Flashes Gas on - no call for heat Rapid Flash Retry IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Optional Electric Heat Optional Electric Heat Electric Heater Design Figure 26: Electric Heat Section If the 8th digit in the model number is an “E”, the rooftop unit was furnished with a factory installed electric furnace (Example, MPS035FE). The Maverick commercial rooftop units are available with low, medium, or high heat output (see capacities in Table 21). This packaged electric heat rooftop unit is designed for outdoor non-residential installations only. The electric heat design consists of a heating coil, DDC staging control, and all operational safeties. The safety switches include high-limit temperature switches and individual coil fusing. The high limit switch is an automatic reset switch. It opens the control circuit and shuts the heater down when the temperature reaches 160°F. The high limit switch closes again allows the heater to run when the temperature gets to 130°F. There is a second level of protection with an auxiliary high limit switch. This switch opens up and shuts the heater down when the temperature reaches 250°F. The auxiliary switch automatically resets again at 220°F. The third level of protection is the secondary auxiliary high limit switch which shut the heater down at 285°F. This switch requires a manual reset. Electric Heating Capacity Data Table 21: MPS 015 – 050 Electric Heating Capacities Tons Nom cfm Stages 15 6000 17 Low Medium High kW Min cfm MBh Delta T* kW Min cfm MBh Delta T* kW Min cfm MBh Delta T* 4 18 950 61 9.5 36 1900 123 19.0 72 3800 246 38.0 6800 4 18 950 61 8.4 36 1900 123 16.7 72 3800 246 33.5 20 8000 4 36 1900 123 14.2 72 3800 246 28.5 90 4740 307 35.5 26 10,000 4 54 2900 184 16.9 72 3800 246 25.5 90 4800 307 31.4 30 12,000 4 54 2900 184 14.2 72 3800 246 19.0 90 4800 307 23.7 35 14,000 4 54 2900 184 12.2 72 3800 246 16.3 90 4800 307 20.3 40 16,000 4 72 3800 246 14.2 90 4800 307 17.8 108 5700 369 21.3 50 20,000 4 72 3800 246 11.4 90 4800 307 14.2 108 5700 369 17.1 * Temperature rise is calculated at nominal cfm Electric Heater Data Table 22: MPS 015 – 050 Electric Heater Data (Maximum Temp. 60°F) kW 18 36 54 Voltage Amps Voltage Amps 208 50 kW 208 200 230 45 230 181 460 23 460 90 575 18 575 72 208 100 208 250 230 90 230 226 460 45 460 113 575 36 575 90 208 150 460 136 230 136 575 108 460 68 575 54 72 90 108 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 32 www.DaikinApplied.com Optional Modulating Hot Gas Reheat Optional Modulating Hot Gas Reheat Modulating Hot Gas Reheat The reheat coil option comes complete with an aluminum micro channel coil and modulating hot gas valves for leaving air temperature control. Figure 27: Ideal for Neutral Air Ventilation Control On a call for dehumidification, the unit will enable the supply to be over-cooled by the DX coil. Hot gas from the unit condenser will be routed to an indoor coil downstream of the DX coil to reheat the air. Hot gas reheat valves will control how much hot gas is routed to the indoor coil to maintain a discharge air setpoint (Figure 28). Figure 28: Dual 2-Way Valve Refrigeration Schematic www.DaikinApplied.com 33 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Optional Modulating Hot Gas Reheat Optional Modulating Hot Gas Reheat Dehumidification Initiation Control & Arrangement An analog sensor is mounted in the return duct, the space, or outdoors to sense Relative Humidity. The location is selected by setting the Sensor Location value on the keypad to Return, Space, or OAT. OAT can only be selected for units with DAT control. Dehumidification is disabled when the unit is in either the Heating or Minimum DAT state. When Dehumidification is enabled, Dehumidification operation is initiated when Humidity Control is set to either Relative Humidity or Dew Point and that value rises above the appropriate setpoint by more than half its deadband. Economizer operation is disabled in the Dehumidification mode so the unit immediately transitions to Cooling if Dehumidification is initiated in Economizer state. In conjunction with dehumidification, MHGRH is used to raise the temperature of the cooled air to a desirable value. MHGRH is comprised of a parallel coil arrangement, with both the condenser and reheat coils of the micro channel type, dual reheat valves (which operate in concert with one another) and a check valve. MHGRH components will always be installed in circuit #2. During Dehumidification control w/ modulating Hot Gas Reheat (MHGRH) an analog signal (0-10Vdc) is controlled as described below. • A PI Loop is used to control the HGRH valves to maintain the Discharge Air Temperature from the reheat coil. Dehumidification Termination • Compressor staging during reheat (or dehumidification) will be controlled by the Leaving DX Coil Temperature. For increased dehumidification during reheat, the standard default compressor staging range is 45 - 52°F. Dehumidification is terminated if the selected variable, Relative Humidity or Dew Point, drops below the appropriate humidity setpoint by more than half its deadband. Dehumidification is also terminated if cooling is disabled for any reason or the unit enters either the Heating or Minimum DAT state. For units with compressors, the number of cooling stages is reduced by one and control reverts to normal control when dehumidification is terminated in the Cooling state. Another compressor stage change could then occur after one Cooling Stage Time has elapsed. • When dehumidification is active in the Cooling state, the reheat set point equals the DAT Cooling Setpoint. For DAT units, this is the normal DAT set point resulting from any reset. For Zone Control units, this set point is the result of a PI Loop based on the Control Temperature. • Communication with the reheat control valves is accomplished by providing a 0-10Vdc signal to a pair of interface boards which in turn supply the control signal to the reheat valves (step type). • In the Fan Only state, no sensible cooling is required, but dehumidification mode will still be enabled if the dew point or humidity sensor is not satisfied. Reheat set point varies from a maximum value (default 65°F) when the Control Temperature is at or below the heating changeover setpoint to a minimum value (default 55°F) when the Control Temperature is at or above the cooling changeover setpoint. IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 34 www.DaikinApplied.com Optional Modulating Hot Gas Reheat • Lead/Lag Arrangement w/ MHGRH (when applicable) • In the reheat mode, the minimum position for the reheat valves is 10% (1.0 Vdc). The controller will modulate the reheat valves from this starting position. —— Alternate staging with circuit #1 as lead will be the standard default arrangement. • Reheat valve(s) must be at 0% (0 Vdc) position before starting the first compressor in the reheat circuit to prevent pressure spikes. —— During cooling mode, circuit #1 will lead and load up before starting circuit #2. —— During reheat mode, circuit #2 will lead and load up before starting circuit #1. —— For reheat operation, compressor(s) in circuit #2 must be active. If the unit is operating in the cooling mode when a call for dehumidification/reheat arises,circuit #2 will become the lead and the controller will bring on an additional stage of coolingfor dehumidification. If any compressors in circuit #1 are operating at this moment they will be switched over to compressors in circuit #2. Dehumidification operation is disabled if circuit #2 is disabled for any reason. • Upon termination of dehumidification (reheat), the maximum ramp down or decay rate of the reheat control valves shall be 1% per sec (or 0.1V per sec). • Upon termination of dehumidification (reheat), staging of compressor(s) is delayed for 1 minute after reheat capacity = 0% (0 Vdc). • Every 24 hours, the reheat control valves will be driven to their maximum position (10Vdc) and then returned to their normal operating position (0Vdc). If unit is operating in cooling or dehumidification (reheat) at the prescribed time it will be deferred to the next time. • Dehumidification status can now be found under the MTIII main system menu. Reheat capacity (valve position) can also be found under the main system menu, display based on percentage (0-100%). Figure 29: Modulating Hot Gas Reheat Schematic www.DaikinApplied.com 35 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Optional Hot Water Heat Optional Hot Water Heat Hot Water Heater Design If the 8th digit of the model number is a “W”, the rooftop unit was furnished with a factory installed hot water coil (Example: MPS035FW). The hot water coil comes with a piping vestibule for field supplied and installed control valve and piping. The coil is furnished with ODM copper connections. The Maverick commercial rooftop units are available with a low heat (one row coil) or a high heat (two row coil) configuration. See certified drawings for the recommended piping entrance locations. Seal all piping penetrations to prevent air and water leakage. NOTE: Factory installed piping is copper. Dissimilar metal within the plumbing system can cause galvanic corrosion. To avoid corrosion, provide proper dielectric fittings as well as appropriate water treatment. CAUTION Coil freeze possible. Can damage equipment. Follow instructions for mixing antifreeze solution. Some products have higher freeze points in natural state than when mixed with water. The freezing of coils is not the responsibility of Daikin. Figure 30: Hot Water Heating Schematic Figure 31: Hot Water Heat Vestibule Return D Unit A B C D 015–020 64.5 8.5 8.5 28.5 026–035 64.5 8.5 8.5 28.5 040–050 90.2 8.5 8.5 28.5 Condenser End C Supply B A IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 36 www.DaikinApplied.com Optional Hot Water Heat Hot Water Pressure Drop Data Figure 32: MPS 015 – 017 Low and High Heat Figure 33: MPS 020 Low and High Heat www.DaikinApplied.com 37 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Optional Hot Water Heat Figure 34: MPS 026 – 035 Low and High Heat Figure 35: MPS 040 – 050 Low and High Heat IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 38 www.DaikinApplied.com Optional Energy Recovery Wheel Optional Energy Recovery Wheel Energy Recovery Wheel Design When a unit is equipped with an optional enthalpy wheel, energy recovery is provided by drawing outside air across half of the enthalpy wheel and drawing exhaust air across the other half. Latent heat and sensible heat are transferred from the hotter and moist exhaust air to the colder and dry outside air during winter conditions. Latent heat and sensible heat are transferred from the hotter and moist outside air to the cooler and dry exhaust air during summer conditions. Energy recovery control consists of starting and stopping an exhaust fan, modulating the speed of the exhaust fan, starting and stopping an enthalpy wheel, optionally controlling the speed of the enthalpy wheel and opening and closing a set of bypass dampers. The outdoor dampers are controlled in the normal manner. Arrangements Three arrangements are offered for the enthalpy wheel: 1. Single enthalpy wheel with economizer and bypass (see Figure 36). This arrangement is available for all units. 2. Single enthalpy wheel without economizer (100% outdoor air unit) for airflow up to about 7000 CFM. This arrangement is available on sizes 015 - 040C and 800 802C only. Wheel Construction Your Daikin enthalpy wheel is delivered completely assembled and ready to run. The wheel is built to provide many years of trouble free service following proper installation and performance of the minimal maintenance requirements. Definitions The following are descriptions of various components related to the enthalpy wheel construction (see Figure 36): Bearing, external – The wheel and bearing rotate on the shaft, no field lubrication is required. Brush seal – The seal used for both the circumferential seal and the inner seal in the cassettes. They are constructed of nylon brush and configured to seal against the enthalpy wheel band in the case of the circumferential seal, and against the wheel face in the case of the inner seal. These seals are full contact seals, have an integral clip, and they are clipped to the cassette face panel cutout (concumferential) or to the (inner) post. Exhaust air – The air stream that is exhausted to the outside. Exhaust air is building return air that has been run through the enthalpy wheel. Heat wheel – Synonymous with an enthalpy wheel, energy conservation wheel, or total energy recovery wheel. Some heat wheels are sensible only wheels and should not be confused with Daikin total energy recovery wheels. Hub – The center support of an enthalpy wheel. Latent energy – Latent energy, in the context of enthalpy wheel discussions, is the work done by the wheel to transfer moisture from one air stream to another. Latent work is accompanied by humidity changes in the air streams. Media – The chemical composite part of the enthalpy wheel which actually performs the latent and sensible exchange. Outdoor air – The air stream that is brought in from the outside. Outdoor air becomes supply air after going through the enthalpy wheel. Purge – A small segment of supply air defined by the gap between the inner seal on the outdoor air edge of the center post and the supply air edge of the center post. The purge angle is adjustable. The purge captures the small amount of supply air captive in the enthalpy wheel when the wheel moves from return to supply and routes it to return to minimize cross contamination. Return air – The air stream that is returned from the building. Return air becomes exhaust air after going through the enthalpy wheel. Rotor – The part of an enthalpy wheel that performs the energy exchange and consists of the wheel media, hub, spokes and band. Sensible heat – Sensible energy, in the context of enthalpy wheel discussion, is the work done by the enthalpy wheel to transfer heat from one air stream to another. Sensible work is accompanied by temperature changes in the air stream. Supply air – The air stream that is supplied to the building space. Supply air is outdoor air that has been run through the enthalpy wheel. Cassette – The steel structure that houses the rotor. Cassettes are of punched sheet metal panelized construction. Enthalpy wheel – A generic name for an energy conservation wheel. The term “enthalpy” refers to an air stream’s total energy (temperature and humidity level). www.DaikinApplied.com 39 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Optional Energy Recovery Wheel Figure 36: Wheel Construction (Side-by-Side) (1) Currently, only the Over-Under configuration is offered on Daikin roof-top systems and air handlers. Purge and Pressurization Pressurization is critical to minimize crossover from exhaust to Figure 37: Purge Detail supply and to allow the purge to operate. Figure 37: Purge and Pressurization Outside Air at Atmospheric Pressure Any leakage must occur from outside to Exhaust Air due to pressure gradient Figure 38: Purge Detail Supply Air OUTSIDE AIR Adjust purge in this direction to decrease capacity and increase purge Adjustable Purge (See Detail) EXHAUST AIR Exhaust Air Plenum Exhaust Fan draws a negative pressure NOTE: Maintain the pressure gradient to prevent cross contamination from the Exhaust to Outside Supply Air IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 40 www.DaikinApplied.com Optional Energy Recovery Wheel Drive Motor Constant Speed Frost Prevention The enthalpy wheel comes standard with a constant speed drive motor which is prewired to turn in the proper direction. When there is a threat of frost on the enthalpy wheel, the wheel is jogged so that less enthalpy transfer occurs and frosting of the wheel is avoided. Frosting can occur on the enthalpy wheel when the exhaust air leaving the wheel is saturated. This condition occurs when two lines intersect on a psychrometric chart, and it does not occur when these two lines do not intersect (see Figure 39). Frost Protection Option During extremely cold winter conditions, exhaust air stream To circumvent this possiblity, Daikin offers three factory installed frost protection options with the MicroTech III system. Varible Speed Frost Prevention Defrost ON/OFF Control (Standard) With this method the enthalpy wheel is stopped periodically for a defrost time duration when the outdoor air temperature is below an outdoor frost temperature threshold setpoint. Figure 39: Frost Prevention Psychrometric Chart When there is a threat of frost on the enthalpy wheel, the wheel is slowed down so that less enthalpy transfer occurs and frosting of the wheel is avoided. Frosting can occur on the enthalpy wheel when the exhaust air leaving the wheel is saturated. This condition occurs when two lines intersect on a psychrometric chart, and it does not occur when these two lines do not intersect (see Figure 39). Energy Recovery Exhaust Hoods Units with the optional energy recovery section have one or two (depending on model) exhaust hoods. Each hood is shipped in three pieces, consisting of one top and tow sides. Install exhaust hood over the barometric relief dampers by installing tow sides first and then install the top. Variable Speed Frequency Control A variable frequency drive is included with the frost protection option and it controls the speed of the enthalpy wheel. The unit has also been programmed for the recommended range of wheel speed operation. Typical wheel speed is 45 RPM, but the programming can allow for wheel speeds above or below 45 RPM. Check all factory settings to make sure they are consistent with the application. Enthalpy wheel speed will be controlled by exhaust temperature measurement. www.DaikinApplied.com 41 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Optional Outdoor Air Monitor Optional Outdoor Air Monitor Thermal Dispersion Airflow Measurement Technology Thermal dispersion technology relates the velocity of the air to the power and rise in temperature of a heated element in a moving airstream. A precise bead-in glass thermistor probes the airflow rate and air temperature. Multiple sensing points are used to produce an average velocity for true volumetric airflow (CFM/LPS). Each individual sensor node is calibrated to NIST traceable airflow standards at 16 points, resulting in a accuracy of 2% of the reading. Connecting to MicroTech III Controllers Wiring 1. Connect analog control wires from the MicroTech III Controller to the outdoor air monitor controller. a. MicroTech III controller (X1 on the MCB or X11 on the EXP_D) to the controller's analog output terminal 1. Figure 40: Bead-in-Glass Thermistor Thermistor material designed for self-heat applications is fused to dumet wire leads b. MicroTech III controller (M on the MCB or M on the EXP_D) to the controller's analog output terminal COM. Thermistor aging process ensures long term stability 2. Power Wires (24 VAC) to the outdoor air monitor controller. a. 24VAC from the unit control panel to the controller terminals L1 and L2. Dumet wire ensures hermetically sealed glass encapsulation Outdoor Air Monitor Controller Settings Kynar® coated wires are welded to dumet leads 1. Set Controller SW1 switch to Vdc. Waterproof potting compound protects assembly from the environment 2. Set power switch to ON. Outdoor Air Monitor Controller Configuration/ Set Up Figure 41: Bead-in-Glass Thermistor Probe (see Appendix, Figure 97 on page 123 for navigating the Controller keypad) 1. Set LCD1 U/M to "CFM" 2. Set AR1 (see Table 23) Zero Power Thermistor 3. Set OUT1 U/M =CFM 4. Set OUT1 =0–10V Approaching Airstream Heat transferred to the airstream is proportional to the airflow rate 5. Set FSI (see Table 23) Table 23: Settings by Cabinet Size Unit size Self-heated Thermistor IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 42 Economizer and 0–100% 0–30% Area sq.ft. (AR1) Full scale output CFM (FS1) Small cabinet 7.3 4.75 10,000 Medium cabinet 10.0 9.5 10,000 Large cabinet 14.5 10.0 10,000 www.DaikinApplied.com Optional Outdoor Air Monitor Figure 42: MicroTech III Controller Figure 43: Transmitter and Connector Detail Transmitter Connector www.DaikinApplied.com 43 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Optional Outdoor Air Monitor Changing the System of Units The transmitter is provided with the system of units set to I-P. To change to S.I., simultaneously press and release the “UP” and “DOWN” arrow buttons during normal operation. “IP/SI UNITS” will be indicated on the LCD display. Press “ENTER” three times and use the “UP” and “DOWN” arrow buttons until the system of units desired is indicated. Press the “ENTER” button to select changes then press “ESC” twice to return to the normal operating mode. See Appendix, Figure 97 on page 123. Converting the Analog Output Signal from FPM to CFM (MPS to LPS for SI units scaling) Last LCD Character Shown in Lower Case (Probe Malfunction) The transmitter is shipped from the factory with analog output “OUTPUT 1” set to indicate velocity in FPM. To automatically convert this analog velocity output to volumetric flow (CFM or LPS), simply set the *OUT1 U/M from FPM (default) to CFM in the Setup Menu (See Appendix, Figure 98 on page 124). If you wish to manually convert the velocity output to volumetric flow (CFM or LPS), simply multiply the indicated output velocity (in FPM or MPS) by the free area of the air flow probe installation location (free area x 1000 for SI units when area is calculated in square meters). For -P sensors, the total free area is programmed into the probe at the factory and is printed on the probe hang-tag. For -F and -B sensor probes, determine the free area following installation in accordance with the installation guidelines. Refer also to Tables 4 and 9 for a complete listing of conversions for each of the analog outputs of the transmitter. If the last character of the flow rate units on the LCD display is lower case (for example FPm or CFm), this indicates that an improper/malfunctioning probe is connected to the transmitter. NOTE: The full scale analog output (OUTPUT1 ) value is determined by the FS1 setting within the SETUP MENU. LCD Display Notifications Following a brief initialization at power up, the LCD display automatically displays airflow and temperature as all upper case (caps) characters. The display provides additional information on system status and alarm conditions as follows: All LCD Characters Shown in Lower Case When all characters of the flow rate units are displayed in lower case (for example cfm) the transmitter is operating in the Field Calibration Wizard mode. Daikin users do not need to use this function. LCD Blinks ** LOW ALARM **, ** HIGH ALARM ** or ** TRBL ALARM** The LCD will alternately flash to indicate an active alarm condition for the type of alarm that has been set. The LCD displays airflow/temperature readings between the alarm notifications. Alarm will cease when the alarm is cleared. IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 44 www.DaikinApplied.com Optional Outdoor Air Monitor Altitude Correction Adjustment Adjusting The Digital Output Filter The Altitude Correction Adjustment allows for correction of airflow readings at the installed site altitude and more precise readings regardless on installed altitude. Refer to the SETUP MENUS of Figure 97 for the *ALT= menu item, and set this vale to the installation altitude. The digital output filter is useful for dampening signal fluctuations resulting from transient wind gusts on outdoor air intakes or excessive turbulence generated from duct disturbances. The digital output filter range can be set between 0 (OFF) and 99%. Increasing the filter percentage limits the allowable change of the output signal. To change the amount of filtering, enter the Setup menu and set “*FILTER1={desired value}” as shown in Figure 97. IMPORTANT Fluctuations in the airflow output signal are normal. Laboratory research indicates that dampening true fluctuations will result in poor control and a larger dead-band of operation. Therefore, the use of the dampening filters in control devices is not recommended. Warnings indicate potentially hazardous situations, which can result in property damage, severe personal injury, or death if not avoided. www.DaikinApplied.com 45 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Optional Outdoor Air Monitor Table 24: General Troubleshooting Problem Possible Cause Remedy Power switch not in the "ON" position. Move the power switch to the "ON" position. Improper supply voltage to the power input terminal block. Ensure that 24VAC power is connected to L1 and L2 of the POWER terminal block and that the voltage with the power switch in the "ON" position is between 22.8 and 26.4 VAC. Blown fuse. Check power wiring. Ensure that multiple devices wired on a single transformer are wired "in-phase". Replace fuse only with a 1.5 amp, fast-acting fuse after the problem has been identified and corrected. No LCD display indication and the green Transmitter Status LED (D3) on the main circuit board is flashing. LCD contrast too low. Turn “Contrast” potentiometer on the main circuit board "clockwise". The LCD display is scrambled or there is no LCD display indication after touching the switches, LCD display or circuit board. Static electricity. Touch an earth-grounded object, such as a duct, to discharge static electricity then reset the power. Avoid direct contact with the LCD display or circuit board. The LCD display indicates "No Probes". The power switch on the transmitter was moved to the "ON" position before the sensor probes were connected. Reset 24VAC power by moving the power switch from the "ON" to "OFF" position and then back to the "ON" position. The LCD display indicates "DiffSensor Type". Sensor probes have been mismatched. Transmitters must have the same sensor type connected (GP1, GF1 or GB1 sensor probes). The LCD display indicates "Too Many Sensors". A probe with 5 or more sensors has been connected to a 'Type B' transmitter with 4 receptacles. Probes with 5 or more sensors are shipped with and require a 'Type A' transmitter with 2 receptacles. The last digit of the flow rate unit is displayed as a lower case letter. (When the Field Calibration Wizard is engaged, the last character of the flow rate units is displayed as an upper case letter. The sensor detection system has detected one or more malfunctioning or missing sensors. Check sensor probe cable connections. If sensor probe connections look OK and match the number of sensor probes indicated on each probe’s hang tag. A probe with 5 or more sensors has been connected to a 'Type B' transmitter with 4 receptacles. Probes with 5 or more sensors are shipped with and require a 'Type A' transmitter with 2 receptacles. The green Transmitter Status LED (D3) on the main circuit board is "ON" but not flashing. The microprocessor is not running. Reset 24VAC power by moving the power switch from the "ON" to "OFF" position and then back to the "ON" position. The green Transmitter Status LED (D3) on the main circuit board is flashing at 1-second intervals. No problem, normal operation. No remedy required. The sensor detection system has detected one or more malfunctioning or missing sensors. Check sensor probe cable connections. If sensor probe connections look OK and match the number of sensor probes indicated on each probe's hang tag. A probe with 5 or more sensors has been connected to a 'Type B' transmitter with 4 receptacles. Probes with 5 or more sensors are shipped with and require a 'Type A' transmitter with 2 receptacles. Sensors are sensitive and can measure very low air velocities. If a reading is indicated, there is airflow present where the airflow measuring station is located. Do not attempt to adjust zero ("offset"). Doing so will result in an error in airflow measurement. The Low Limit airflow cutoff value can be set to force the output signal to zero. Output card is not securely mounted on main circuit board. Turn the transmitter power "OFF", and then press the output card firmly onto main circuit board. Turn the transmitter power back "ON". No LCD display indication and the green Transmitter Status LED (D3) on the main circuit board is not illuminated. The green Transmitter Status LED (D3) on the main circuit board is flashing at 2-second intervals. The transmitter indicates airflow when the HVAC system is not operating. No output signal can be measured at the OUTPUT terminal block of the transmitter. Blown output fuse (output 1 and output 2 are fused and protected independently on the transmitter). Make sure that power has not been connected to the output terminal block. Correct the problem and replace with 0.125 amp, fast acting fuse only. Make sure that the host control system is not configured for a 2-wire device (no excitation voltage should be present on the signals from the host controls). Correct the problem and replace with 0.125 amp, fast acting fuse only. The Low Limit airflow cutoff value is above the actual airflow reading. Decrease the Low Limit airflow cutoff value in the Setup menu until it is below the actual airflow reading. The output signal on the transmitter fluctuates while the flow and/or temperature readings on the LCD are steady. Electrical interference from other devices is creating noise in the signal wires to the host control system. The output signal wiring must be shielded. Individually ground one or more of the following points: the signal wire shield at host controls; signal wire shield at the transmitter, or L2 of the power terminal block of the transmitter. The LCD display does not match the readings indicated by the host control system. The scaling in the host control system is incorrect. Compare the current configuration of the transmitter with that of the host control system. Compare the minimum and full scale settings for each output by navigating through the Setup menu. IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 46 www.DaikinApplied.com Optional Outdoor Air Monitor Table 25: Transmitter Troubleshooting Problem The host control system is unable to communicate with the transmitter. Possible Cause Remedy Output card is not securely mounted on main circuit board. Turn the transmitter power "OFF" and press the output card firmly onto main circuit board. Turn the transmitter power back "ON". Network signal wiring is not properly connected to the transmitter or the host controls. Verify that the network signal wires from the host controls are connected to the proper terminals of the OUTPUT block. On the transmitter OUTPUT terminal block, NET+ is for A, NET- is for B and COM for common. network protocol based on the network Network protocol is not properly set on the transmitter. Set requirements and reset transmitter power. Set address based on network requirements and Network address is not properly set on the transmitter. reset transmitter power. The address must be unique for the network. Network termination is not properly set on the transmitter. Set transmitter termination based on network requirements and reset the transmitter power. The LCD display does not match the readings indicated by the host control system. The Area or K factor of the transmitter does not match that of the host controls. Compare the value of the Area or K factor of the transmitter with that of the host control system and make adjustments to ensure a match. The returned value for airflow is zero when airflow is indicated on the LCD display of the transmitter. The Low Limit airflow cutoff value is above the actual airflow reading. Decrease the Low Limit airflow cutoff value in the Setup menu until it is below the actual airflow reading. The sensor detection system has detected one or more malfunctioning or missing sensors. Check sensor probe cable connections. If sensor probe connections look OK and match the number of sensor probes indicated on each probe's hang tag. A probe with 5 or more sensors has been connected to a 'Type B' transmitter with 4 receptacles. Probes with 5 or more sensors are shipped with and require a 'Type A' transmitter with 2 receptacles. The status point from the transmitter has a Trouble value. There is no value for the differential pressure point www.DaikinApplied.com Differential pressure is only available from transmitters If a differential pressure measurement is required, that have a Bi-directional Bleed Airflow Sensors contact your local Daikin Representative about a Biconnected. directional Bleed Airflow Sensor. 47 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Unit Options Unit Options Economizer Enthalpy Control The economizer can be ordered with the optional differential enthalpy control. With this option a solid-state humidity and temperature sensing device is located in the return and outdoor airstreams. These devices are labeled RAE and OAE respectively. When the outdoor enthalpy is lower than the return air enthalpy, the economizer operation will be initiated. If the outdoor air enthalpy is higher than the return air, the outdoor air damper position will be at the minimum setpoint. See OM 920 for further information on the economizer operation. External Time Clock You can use an external time clock as an alternative to (or in addition to) the MicroTech III controller’s internal scheduling function. The external timing mechanism is set up to open and close the circuit between field terminals 101 and 102. When the circuit is open, power is not supplied to binary input ID1. This is the normal condition where the controller follows the programmable internal schedule. When the circuit is closed, power is fed to ID1. The MicroTech III controller responds by placing the unit in the occupied mode, overriding any set internal schedule. Exhaust Fan Option Economizer units may include exhaust fan options. For units with CAV applications, the exhaust fans can be ordered as staged control or they may be ordered with building pressure control. The building pressure control option has a VFD that runs the exhaust fan motors and is controlled by the static pressure sensor number 2 (SPS2). Refer to OM 920 for setting up the unit controller with these two options. The units are only available with building pressure control on VAV units. The exhaust fan motors are permanently lubricated and do not require any additional periodic lubrication. Figure 44: Pressure Tubing Diagram TO ENTERING AIR SIDE OF THE FILTERS PC5 HI Proof-of-Airflow and Dirty Filter Switch The proof-of-airflow switch (PC7) and the dirty filter switch (PC5) are supplied on all CAV units. The tubing is installed to the switches per Figure 44. The proof of airflow switches senses the pressure difference between the positive pressure in the supply air fan compartment and the suction pressure on the leaving air side of the filters. The differential pressure is factory set at 0.25" for this switch. The dirty filter switch senses the pressure difference across the filter; from the entering air side of the filter to the leaving air side of the filters. The switch is factory set at 1.0". When the pressure difference across the filters is sensed at this value, the dirty filter alarm will appear on the DDC controller. All VAV units also have the PC7 and PC5 switches as standard (see Figure 40). These switches are tied into the Duct High Limit switch (DHL) as shown in Figure 44. The DHL is factory set at 4.0". When this differential pressure is sensed the normally closed contacts will open on the switch giving the DHL alarm at the unit controller. Duct High Pressure Limit The duct high pressure limit control (DHL) is provided on all VAV units. The DHL protects the duct work, terminal boxes, and the unit from over pressurization, which could be caused by, for example, tripped fire dampers or control failure. The DHL control opens when the discharge plenum pressure rises to 3.5" wc (872 Pa). This setting should be correct for most applications and should not be adjusted. If the DHL switch opens, digital input ID9 on the Unit Control Board will be de-energized. The MicroTech III controller then shuts down the unit and enters the Off-Alarm state. The alarm must be manually cleared before the unit can start again. Refer to the operation manual supplied with your unit for more information on clearing alarms (refer to OM 920). LO TO LEAVING AIR SIDE OF THE FILTERS HI LO HI LO DHL PC7 TO SUPPLY FAN PLENUM IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 48 www.DaikinApplied.com Unit Options Convenience Receptacle (Field Powered) Convenience Receptacle (Unit Powered) A Ground Fault Circuit Interrupter (GFCI) convenience receptacle is provided in the main control box on all units. To use this receptacle, connect a separate field-supplied 115 V power wiring circuit to the outlet. A Ground Fault Circuit Interrupter (GFCI) convenience receptacle is provided in the main control box on all units. The receptacle shall be powered by a factory installed and wired 120V, 20 amp power supply. The power supply shall be wired to the line side of the unit's main disconnect, so the receptacle is powered when the main unit disconnect is off. This option shall include a GFI receptacle, transformer, and a branch circuit disconnect. The electrical circuit shall be complete with primary and secondary overload protection. See Figure 45 for a branch circuit diagram. 460V LINE VOLTAGE PRI. Figure 45: Unit Powered GFCI Receptacle Schematic www.DaikinApplied.com 49 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Unit Options Condenser Fan Operation for Variable Speed Compressor Low Ambient Option (MPS 040 and 050 Only) Daikin’s head pressure control operates by modulating the motor speed of one condenser fan on the VFD compressor refrigeration circuit in response to the condenser pressure. VFD compressor refrigerant circuit contains a solenoid valve that blocks refrigerant flow to half of the condenser coil, which effectively removes 50% of the condenser surface from the circuit for low load/low ambient conditions. Figure 46: R-410A Speedtrol This option allows for mechanical cooling operation down to 0F (-18C). The VFD option senses refrigerant head pressure and varies the fan speed accordingly. When the pressure rises, the SpeedTrol increases the speed of the fan, when the pressure falls. SpeedTrol decreases the speed of the fan. The VFD throttling range is 250 to 400 psig, fixed, with a corresponding fan speed range of 10Hz to 60Hz. The fan motor is a three-phase motor, identical to the unit voltage (208V to 575V) and is controlled by a variable frequency drive. The variable frequency drive receives a signal from a pressure transducer and varies the speed of the condenser fan accordingly. The SpeedTrol arrangement for VFD compressors is also employing “Start-Stop control by Speed reference Level” in which the VFD will stop the condenser fan motor under certain conditions. If the head pressure were to fall below 250 PSIG with the condenser fan operating at minimum speed of 10Hz (possibly due to a low ambient or high wind condition) the VFD will shut down the condenser fan. The VFD will restart the condenser fan at 20 Hz if head pressure rises to a level above 250 PSIG. In addition to modulating fan speed, a refrigerant solenoid valve is included in circuit #1. Operation of the solenoid valve is based on head pressure. If the average condensing pressure falls below 250 PSIG (83F sat) for 60 seconds, the condenser solenoid valve closes, effectively removing 50% of the condensing surface. If the averaging condensing pressure rises above 350 PSIG (105F sat) for 60 seconds, the condenser solenoid valve is opened, activating the entire condenser surface. The solenoid valve is disabled above an outdoor ambient of 80F. The solenoid valve is in a normally open configuration. Figure 47: Speedtrol Operating Characteristics (for Variable Speed Inverter Compressor Units) Figure 48: Speedtrol Operating Characteristics (for Variable Speed Inverter Compressor Units with Start-Stop Control) Refer to Figure 46 for wiring schematics of SpeedTrol. Refer to Figure 47 and Figure 48 for SpeedTrol operating characteristics. IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 50 www.DaikinApplied.com Unit Options VFD Compressor Operation When a MPS is equipped with the VFD compressor option there are two refrigeration circuits, one VFD controlled compressor with up to 3 fixed speed compressors depending on unit model. The VFD compressor must always be the “lead” circuit or first one on and last one off. VFD compressor modulation is controlled by an analog signal (0 – 10 Vdc) from the unit controller. Refer to Figure 101. The minimum VFD compressor speed is 25 rps (1500 rpm) and the maximum VFD compressor speed is 100 rps (6000 rpm), but the minimum and maximum limits per unit may vary depending on operating conditions and unit model size. The VFD compressor is a 4 pole motor design that operates off a frequency signal from the VFD between 50Hz and 200Hz. At Start-up the VFD compressor will automatically ramp up to 50 rps for first 10 seconds for lubrication requirements. Crankcase heating for VFD Compressor model VZH-088 is performed by the VFD via DC-holding current through the motor windings. VFD compressor modulation is additionally monitored and adjusted in order to maintain operation within the approved compressor operating envelope. If the VFD compressor were to become inoperative, any other compressors on the VFD circuit will be disabled. The unit can continue to operate on the remaining fixed speed compressors of the non-VFD circuit until the unit can be serviced. When the VFD compressor is at its maximum speed and more capacity is required, a fixed speed compressor is started while the VFD compressor is reduced to minimum speed at which point it resumes modulating to maintain the discharge temperature. When the VFD compressor is at its minimum speed and less capacity is required, a fixed speed compressor is turned off while the VFD compressor is increased to maximum speed at which point it resumes modulating to maintain discharge temperature. Figure 49: VFD Compressor Modulation Signal Table 26: VFD Compressor Modulation Ranges VFD Modulation Range VFD Max rps MPS Unit Model VFD Min rps/ VFD Min V VFD and Fixed Comp(s) On 1 Fixed On 2 Fixed On 3 Fixed On VFD1Max rps/ VFD1MaxV VFD2Max rps/ VFD2MaxV VFD3Max rps/ VFD3MaxV VFD Comp Only VFDMax rps/ VFDMaxV OilBoostrps/ OilBoostV* 026 39 rps / 0 Vdc 60 rps / 4.0 V 55 rps / 4.0 V NA 70 rps / 6.0 V 70 rps / 4.0 V 030 39 rps / 0 Vdc 100 rps / 8.7 V 80 rps / 7.3 V NA 100 rps / 10.0 V 100 rps / 7.3 V 035 39 rps / 0 Vdc 100 rps / 8.7 V 80 rps / 7.3 V NA 100 rps / 10.0 V 100 rps / 7.3 V 040 39 rps / 0 Vdc 85 rps / 8.0 V 85 rps / 8.0 V 80 rps/ 7.3 V 100 rps / 10.0 V 100 rps / 7.3 V 050 39 rps / 0 Vdc 85 rps / 8.0 V 85 rps / 8.0 V 80 rps/ 7.3 V 100 rps / 10.0 V 100 rps / 7.3 V * High and Low Oil Boost are explained on page 52 www.DaikinApplied.com 51 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Unit Options VFD Compressor Control Control of the VFD compressor is accomplished with a digital output enable signal and a 0-10VDC analog modulating control signal. General VFD Compressor Start Sequence On a call for VFD compressor operation the VFD enable output is energized (on) and the 0-10VDC analog control signal is set to 3.33VDC (50 rps) for 10 seconds. During this 10 second initial period the VFD compressor’s internal logic ramps the compressor to 50 rps to insure compressor startup oil lubrication. After 10 seconds the VFD compressor control signal begins modulation to maintain the cooling discharge set point. Dehumidification Transition During Cooling State When dehumidification operation becomes active while the unit is in the Cooling operating state, The VFD compressor is ramped to its maximum capacity. If the VFD capacity at this point is already above 75% of its full modulation a fixed compressor is also turned on. The compressors are held at this capacity for 1 minute before normal modulation resumes, to maintain leaving coil temperature (LCT). • VFD compressor will load up completely before starting any fixed speed compressors to achieve LCT of 45F (default) with the VFD compressor option. LCT may be set between 45F to 52F. • If reheat signal is at 100% for 10 minutes and the unit is unable to raise the DAT to desired point, the controller will stage off 1 fixed compressor and modulate the VFD compressor speed to achieve the DAT set point. NOTE: In addition to enabling VFD compressor operation the VFD enable output is used to energize the liquid line drop solenoid on the VFD circuit. (Only for Low Ambient Option) Compressor Stage Up Transition When the VFD compressor has been operating at maximum capacity for the cooling stage time period and there is a call for more cooling capacity the following transition sequence is followed when staging up. During each fixed compressor stage UP sequence, the VFD compressor speed is reduced to its minimum, as a fixed speed compressor is turned on. Note that the VFD compressor speed range is extended for these staging points to assure smooth transition and to minimize capacity gaps. Typically, the VFD compressor is overdriven (higher speed than normal full load rating speed) before staging up a fixed compressor. The VFD is held at minimum speed for 30 seconds before normal modulation resumes. Compressor Stage Down Transition When the VFD compressor has been operating at minimum capacity for the cooling stage time period and there is a call for less capacity the following transition sequence is followed when staging down. During each fixed speed compressor stage DOWN sequence, the VFD compressor speed is increased to maximum speed (which varies with unit size and number of operating fixed compressors) as a fixed speed compressor is turned off. Note that the VFD compressor speed range has been extended for these staging points to assure smooth transition and to minimize capacity gaps. Typically, the VFD compressor will be overdriven (higher speed than normal full load rating speed) when staging down a fixed compressor. IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Oil Balance/Boost Operational Sequence When a low oil level is indicated in the VFD compressor sump, the unit switches to either an oil balance or oil boost state. The VFD compressor speed is increased during these modes to promote the return of refrigerant oil to the VFD compressor. To avoid short cycling of the oil balance/boost sequence, no action is taken until a low oil indication has been present for 5 consecutive run minutes. The unit determines whether to enter the oil balance or oil boost mode based on the running conditions when a low oil indication is experienced. The balance mode is only used when a VFD compressor is part of a tandem compressor set. The balance mode is usually entered first, and is utilized to move oil from the fixed speed compressor to the VFD compressor. If this mode fails to resolve the low oil indication issue, the unit will then go into the boost mode. The boost mode is utilized to return oil from the refrigerant system to the compressors. VFD compressors that are not part of a tandem compressor arrangement will skip the balance mode and only utilize the boost mode. The balance mode will be entered if the VFD compressor is part of a tandem compressor arrangement and the fixed speed compressor is running, and there is a low oil indication. Upon entering the oil balance mode the fixed speed compressor is turned off and the VFD compressor speed is increased to the oil boost value shown in Table 20. The VFD compressor runs at this condition until the optical oil sensor verifies that oil is present for 3 continuous minutes. Unit Controller default is set for a 10 minute max balance. 52 www.DaikinApplied.com Unit Options VFD Compressor Protection Unloading Control If the oil balance mode fails to resolve the low oil condition, or the fixed speed compressor was not running when the low oil indication occurred, or the VFD compressor was not part of a tandemized compressor set, when the low oil indication occurred, the unit will enter boost mode There are several modulating control functions that adjust the speed control range of the VFD compressor to protect it from damage under abnormal operating conditions. The following functions are provided by the unit controller Upon entering oil boost mode, the VFD compressor speed is increased to the oil boost value shown in Table 20. If the VFD compressor is part of a tandem arrangement, the fixed speed compressor is started as well. The VFD compressor runs at this condition until the optical oil sensor verifies that oil is present for 3 continuous minutes. Unit Controller default is set for a 10 minute max boost. • High Pressure Unloading Control • High Discharge Line Temperature Unloading Control • High/Low Discharge Superheat Control During the oil balance/boost sequence the DAT temperature is overridden to allow the VFD compressor to continue operating until oil balance/boost sequence termination. If one or more fixed speed compressors on the non VFD compressor circuit is operating, and the fixed speed compressor on the VFD compressor circuit was not already running when entering the oil boost mode, one fixed speed compressor on the non VFD compressor circuit will be turned off to minimize the disturbance to the DAT. High Pressure Unloading Control The VFD compressor has an upper operating sat discharge pressure limit of 575 PSIG. If the discharge pressure exceeds 575 PSIG, the compressor speed is reduced 1 rps every 10 seconds until the discharge pressure is at or below 575 psig. If the discharge pressure does not drop below 575 PSIG with the VFD compressor operating at minimum speed (30 rps), the compressor is locked out on alarm. Oil balance/boost sequences and durations are logged in the unit controller. In addition, when the VFD compressor is operating above a sat discharge pressure of 525 PSIG, the VFD compressor maximum speed is limited to 90 rps and the minimum speed is limited to 30 rps. If low oil indication does not clear, the VFD compressor will be shut down and oil level will be monitored for an additional 15 minutes. If low oil indication still does not clear within these 15 minutes, the VFD compressor will be locked out on alarm. The low oil problem is also generated and the VFD compressor circuit is disabled if the oil boost sequence is initiated more than 4 times in a 24 hour period. If the oil balance/boost sequence successfully restores the VFD compressor oil level the fixed compressor stage is returned to its pre-oil balance/ boost condition and normal compressor sequencing and modulation resumes www.DaikinApplied.com • Condenser Coil Splitter Valve Control (For Low Ambient Option) 53 A high side pressure transducer is standard on the VFD circuit allowing the discharge pressure of the refrigerant circuit to be viewed at the unit controller display. If the unit controller needs to reduce the compressor speed in order to limit discharge pressure, the action is recorded in unit controller event log section. IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Unit Options High Discharge Line Temperature Unloading Control A compressor discharge temperature sensor (Thermistor) is installed on the VFD compressor as standard. The temperature is used to measure discharge temperature and superheat levels at the VFD compressor discharge. If the compressor discharge temp reaches 250F, the VFD compressor speed is reduced by 10 rps and monitored for 3 additional minutes. The unit controller will continue to reduce VFD compressor speed by 10-rps increments until the discharge temp drops below 250F. If the VFD compressor discharge temp reaches 250F a warning will be logged in the controller. If reduced compressor speed does not resolve the issue, the VFD compressor is shut down and allowed to cool for 30 minutes. The VFD compressor is then re-started and if the discharge temperature cannot be held under 250F, the VFD compressor is locked out. The root cause may be connected to a number of issues (low charge, blocked condenser coil, condenser fan failure, malfunctioning TEV, etc.) and service is needed. High Superheat If the VFD compressor discharge superheat rises to 75F for 10 consecutive minutes, the VFD compressor speed is reduced by 10 rps increments down to a 40 rps operating speed. Superheat is monitored at each speed for 10 minutes and if superheat remains above 75F, the VFD compressor speed is decreased an additional 10 rps. When compressor discharge superheat level is at 75F or below, the compressor speed is no longer decreased. If speed correction resolves problem, the unit controller will have logged that a speed correction was needed for superheat in the event log. If decreasing speed does not correct issue, the VFD compressor is locked out and an alarm is logged in the unit controller. Manual Control (with VFD Compressor) For service and troubleshooting the unit controller has capability to allow the VFD compressor to be operated manually. Refer to the controller OM-920 for more detail. The basic manual operations include the following: • Start or Stop the VFD compressor The VFD compressor discharge Temp has an upper limit of 275F. The VFD compressor will be shut down if discharge temp reaches 275F. • Modulate VFD compressor from 0 – 100% speed • Ability to energize condenser coil splitter solenoids (Only for low ambient option) NOTE: The fixed speed compressor circuit does not contain this feature. Low/High Discharge Superheat With the high side pressure transducer and discharge thermistor, the unit controller is capable of monitoring the variable speed compressor discharge superheat. This feature protects the VFD compressor against flood back, undercharged conditions, overcharged conditions, malfunctioning TEV, etc. Typical compressor superheat range is 20F to 75F. The discharge temperature of the VFD compressor can be viewed at the unit controller display. • Ability to initiate or terminate oil boost sequence If an electrical issue with the VFD compressor is suspected, the winding resistance can be checked at the motor terminals. Table 27: VFD Compressor Winding Resistance Compressor Model Voltage Winding Resistance (Ohms) VZH-088B-X 208-230V 0.03 VZH-088B-X 460V 0.10 VZH-088B-X 575V 0.10 Low Superheat If the compressor discharge superheat falls below 20F for 15 consecutive run minutes, the VFD compressor speed is increased by 5 rps increments up to a 60 rps operating speed. Superheat is monitored at each speed for 10 minutes and if superheat remains below 20F, the VFD compressor speed is increased an additional 5 rps. When compressor discharge superheat level is at 20F or above, the compressor speed is no longer increased. If speed correction resolves problem, the unit controller will have logged that a speed correction was needed for superheat in the event log. If increasing speed does not correct issue, the VFD compressor is locked out and an alarm is logged in the unit controller. IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 54 www.DaikinApplied.com Unit Options Condenser Coil Splitter Solenoid Valve Control (MPS 040 and 050 Only) VFD Compressor Emergency Stop Control If the VFD compressor enable output signal has been ON for 30 seconds and the controller fails to receive the VFD run verification input, VFD Compressor Emergency Stop Control is activated. When this function is active, VFD compressor enable output will be turned OFF for 5 seconds and then turned ON and ramp VFD compressor speed to 60Hz. If controller receives a VFD run verification input, a log event is set on VFD Emergency Stop Control. If controller fails to receive the VFD run verification input after 3 attempts in 30 minutes, the VFD compressor is locked out and the problem is logged. Condenser coil splitting is avaialble only on VFD compressor circuit of a unit with low ambinet option. This feature assists in maintaining head pressure during low ambient/low modulating operation. A solenoid valve on each circuit is controlled by a digital output from the MicroTech III controller. The coil splitter solenoid valve is controlled based on the average discharge line pressure equivalent saturation temperature determined from the corresponding discharge pressure transducer monitored via an analog input to the MicroTech III controller. The splitter solenoid valve on each circuit is normally open (digital output de-energized). The splitter valve on a circuit is closed (energized) when that circuit’s saturation temperature remains below 83.0°F (250 psig) continuously for 60 seconds and the OAT is less than or equal to 80.0°F. The solenoid valve is re-opened when the saturation temperature rises above 105.0°F (350 psig) continuously for 60 seconds and the OAT rises above 80°F or when all the compressors on the circuit are OFF. If the average saturated discharge temp falls below 250 PSIG (83F) for 60 seconds and condenser coil splitter solenoid coil is energized (closed), the VFD compressor modulation rate is increased until an average saturated discharge temp of 250 PSIG (83F) is achieved. This operation will raise the lower modulation limit of the VFD compressor, but is needed to keep the VFD compressor inside its operating envelope and maintain head pressure for TEV control. Once active the VFD Compressor Emergency Stop Control function remains active until one of the conditions are met. • VFD compressor enable output signal has been ON for 30 seconds and VFD compressor status Input is ON • VFD compressor is OFF If the controller fails to receive the VFD run verification input after the VFD compressor enable output signal has been ON for 30 seconds, the circuit is shut OFF on VFD Compressor Emergency Stop Control alarm. Whenever this protection function becomes active a VFD Compressor Emergency Stop Control event is recorded in the Event Log with date and time stamp. Whenever this protection function returns to normal a VFD Compressor Emergency Stop Control return to normal event is recorded in the Event Log with date and time stamp. When the condenser coil splitter is energized (closed) and the VFD compressor discharge pressure is below 250 PSIG, the VFD compressor speed is increased by 5rps increments every 30 seconds until the discharge pressure exceeds 250 PSIG. When the VFD compressor reaches 250 PSIG, this speed becomes the new minimum speed of the VFD compressor. As the discharge pressure rises above 250 PSIG, the minimum allowable compressor speed is decreased in 5 rps increments every 30 seconds. If the condenser coil splitter valve is closed and the VFD compressor discharge remains below 250 PSIG for 15 minutes the circuit is locked out and an alarm is logged in the unit controller. If a speed correction was performed to increase the compressor discharge pressure, there will be a record of the action in the unit controller under the event log. www.DaikinApplied.com 55 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Unit Options Variable Speed Scroll Compressor WARNING Figure 50: Compressor Nameplate Information The compressor must only be used for its designed purpose(s) and within its scope of application (refer to the Operating Limits). Consult the Application Guidelines. Under all circumstances, the EN378 (or other applicable local safety regulations) requirements must be fulfilled. Daikin units with variable speed inverter compressor are engineered with fixed speed compressor(s) in such a way that the unit delivers only the required energy to satisfy space conditions and provides you with exceptional energy savings. It improves comfort through precise temperature and humidity control. Variable speed compressor enhances energy efficiency and capable of providing unit capacity modulation down to 20% and reduces compressor cycling and wear on compressor. Daikin rooftop units with variable speed Inverter compressors are provided with Internal Permanent Magnet (IPM) motors. Compressors are designed to vary capacity by modulating the speed of the scroll set. The speed ratio for the IPM motor compressor is 4:1 (25 rps to 100 rps). Condenser fans staging and an oil management/monitoring system are provided for reliable operation. The VFD compressor will always be on the “lead” circuit and will be the first one ON and last one OFF. A. Model number B. Serial number C. Refrigerant D. Supply voltage to CDS303 frequency converter E. Housing service pressure F. Factory charged lubrication G. Compressor frequency and MaxMust trip current Figure 51: Compressor Components IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 56 www.DaikinApplied.com Unit Options Oil Injection Control Optical Oil Level Sensor The VFD compressor contains an oil injection valve and solenoid (SV11) as standard. The oil injection valve provides lubrication to the scroll set under low speed/low refrigerant velocity situations. The oil injection valve is a normally closed valve. Below 50 rps (100 Hz) the valve is closed and directs oil to the scroll set suction port. Above 50 rps (100 Hz) the solenoid is bypassed and sends oil into sump. The oil injection valve/ solenoid is mounted directly on the compressor and is controlled by the Compressor VFD (relay 1 output, terminals NO & Com). The coil voltage for the oil injection solenoid is 24 Vac. An optical oil sensor is used to monitor oil level in VFD compressor sump. The sensor is mounted directly to a fitting on the VFD compressor shell and can be removed without having to depressurize/reclaim the refrigeration system. Optical oil indication signal is sent to MTIII Expansion Module ‘C’ (terminals X3 & M). Normal oil indication will provide a contact closure from relay R40. Relay R40 will de-energize during low oil indication, removing signal to terminal X3 and will start the unit in an oil boost sequence. Refer to Figure 54 and Figure 55 The coil can be removed if required by carefully prying off the valve stem. The wiring connector is attached to the coil by a screw in the center of the housing. Refer to Figure 52 and Figure 53. Figure 54: Sightglass for Optical Oil Sensor/Switch Figure 52: Assembly Components Figure 55: Optical Oil Level Sensor/Switch Electrical Connections and Wiring Basic Connections Figure 53: Oil Injection Control Dismanteling Depending on the frequency converter version, the physical position of individual connectors may differ. Always make sure that the compressor terminals, U, V and W are connected to the frequency converter terminals, 96, 97 and 98 respectively. The compressor motor cable is shielded and the armoured part of the cable is connected to a ground on both cable ends; at the side of the compressor and at the side of the frequency converter. www.DaikinApplied.com 57 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Unit Options Variable Frequency Drive for VFD Compressor WARNING Never bypass the compressor drive or directly connect the VFD compressor to the main power supply. WARNING The compressor drive is preset to run the compressor clockwise. WARNING Variable Speed Inverter Compressor The VFD is factory-programmed and should not be modified in the field. Any modifications will void the warranty. Compressors are compatible with the manufacturer’s VFD only. The compressor drive used for this option is a special series (CDS 303) that is intended for use with an IPM compressor motor and cannot be replaced with any off the shelf VFD. Basic Operation of Compressor Drive: Start= Connect terminals 12 & 18 for minimum of 5 secs, connect terminals 12 &27 and terminals 13 &37 Stop= Disconnect terminals 12 & 27 Emergency Stop= Disconnect terminals 13 & 37 Control/Modulation= 0 to 10Vdc signal to terminals 53 & 55 Run Verification= A contact closure from relay 02 (terminals 04 & 05) is provided when drive is running Oil Injection= A contact closure from relay 01 (terminals 01 & 02) is provided when compressor speed is greater than 50 rps (3000 rpm) which energizes the oil solenoid coil. The compressor drive contains protection for the compressor against short circuits at the compressor terminals, overload protection , phase loss and earth faults. The compressor drive is protected against short-circuits. Table 28: Compressor Drive Model & Frame Size The compressor drive is mounted in the main control box. The compressor drive and the LCP (local control panel) are preset with parameters from the factory and should not need to be changed in the field. The LCP is removable and is interchangeable with any of the compressor drives used by any of the VFD compressors. If the need arises to replace the compressor drive, the parameters can be downloaded from the LCP to the new compressor drive. Compressor Model Drive Model VZH-088B Frame Size 208-230V 460V CDS303-15kW B4 B3 VZH-117B CDS303-18kW C3 B4 VZH-170B CDS303-22kW C3 B4 Refer to the VFD operational manual for more information. The compressor drive is preset to run the compressor clockwise and must be connected as shown in the unit schematic. The compressor drive is preset for an open loop configuration with 0-10Vdc reference corresponding to 1500-6000 Rpm. The compressor drive generates a soft start with an initial ramp of 2 seconds. In-rush current (or LRA) to the VFD compressor is typically not more than a few percent more than rated nominal Current. Compressor Speed, modulation signal %, frequency signal, compressor amperage are all displayed in real time on the compressor drive screen. Alarms and descriptions will also be visible on the compressor drive screen. IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 58 www.DaikinApplied.com Wiring Diagrams Wiring Diagrams Figure 56: VAV Power – Fixed Speed Scroll Compressor www.DaikinApplied.com 59 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Wiring Diagrams Figure 56 continued: VAV Power – Fixed Speed Scroll Compressor IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 60 www.DaikinApplied.com Wiring Diagrams Figure 57: MPS 026 VAV Power with Variable Speed Inverter Compressor www.DaikinApplied.com 61 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Wiring Diagrams Figure 57 continued: MPS 026 VAV Power with Variable Speed Inverter Compressor IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 62 www.DaikinApplied.com Wiring Diagrams Figure 58: MPS 030–050 VAV Power with Variable Speed Inverter Compressor www.DaikinApplied.com 63 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Wiring Diagrams Figure 58 continued: MPS 030–050 VAV Power with Variable Speed Inverter Compressor IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 64 www.DaikinApplied.com Wiring Diagrams Figure 59: VAV Control – Inputs www.DaikinApplied.com 65 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Wiring Diagrams Figure 59 continued: VAV Control – Inputs IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 66 www.DaikinApplied.com Wiring Diagrams Figure 60: MPS 026 VAV Control with Variable Speed Inverter Compressor www.DaikinApplied.com 67 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Wiring Diagrams Figure 60 continued: MPS 026 VAV Control with Variable Speed Inverter Compressor IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 68 www.DaikinApplied.com Wiring Diagrams Figure 61: MPS 026 with Variable Speed Inverter Compressor – without Low Ambient Option www.DaikinApplied.com 69 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Wiring Diagrams Figure 62: MPS 030 – 050 VAV Control with Variable Speed Inverter Compressor IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 70 www.DaikinApplied.com Wiring Diagrams Figure 62 continued: MPS 030 – 050 VAV Control with Variable Speed Inverter Compressor www.DaikinApplied.com 71 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Wiring Diagrams Figure 63: MPS 040 – 050 with Variable Speed Inverter Compressor – with Low Ambient Option IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 72 www.DaikinApplied.com Wiring Diagrams Figure 64: VAV Control – Outputs (Staged Gas Heat) www.DaikinApplied.com 73 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Wiring Diagrams Figure 64 continued: VAV Control – Outputs (Staged Gas Heat) IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 74 www.DaikinApplied.com Wiring Diagrams Figure 65: CAV Power www.DaikinApplied.com 75 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Wiring Diagrams Figure 65 continued: CAV Power IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 76 www.DaikinApplied.com Wiring Diagrams Figure 66: CAV Control – Inputs www.DaikinApplied.com 77 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Wiring Diagrams Figure 66 continued: CAV Control – Inputs IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 78 www.DaikinApplied.com Wiring Diagrams Figure 67: CAV Control – Outputs (Staged Gas Heat) Figure 68: VAV/CAV Control – Outputs (Modulating Gas Heat) www.DaikinApplied.com 79 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Wiring Diagrams Figure 69: Electric Heat Option Power Figure 70: Electric Heat Option – Outputs IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 80 www.DaikinApplied.com Wiring Diagrams Figure 71: Energy Recovery www.DaikinApplied.com 81 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Wiring Diagrams Figure 71 continued: Energy Recovery IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 82 www.DaikinApplied.com Wiring Diagrams Figure 72: Energy Recovery Main Control Board www.DaikinApplied.com 83 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Wiring Diagrams Figure 72 continued: Energy Recovery Main Control Board IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 84 www.DaikinApplied.com Sequence of Operation Sequence of Operation Operating States The transition from any operating state to another is graphically represented in Figure 73. Figure 73: State Diagram Any Other State The return temperature is typically used for VAV units and the space temperature is typically used for CAV units. The unit goes into the heating mode of operation when the control temperature (return or space temperature) is below the heating setpoint by more than ½ the deadband. Example – If the heating setpoint is 68.0°F and the deadband is 1.0°F, the unit will not go into the heating mode of operation until the control temperature reaches 67.4°F. Start Up Recirculation When this takes place, the heating mode of operation will begin and the 1st stage of heating operation will start. The next stage, up or down, will take place after 4 minutes. This “4 minutes” is called the stage timer. The gas or electric heat module will continue to stage up as long as the control temperature is below the heating setpoint by more than ½ the heating setpoint deadband. The unit will stage down if the maximum discharge air temperature of 120°F is reached. Gas units with one gas valve have 2 stages of heating and units with two gas valves have 4 stages of heating. Heating Fan Only Mechanical Cooling The unit's heating mode of operation is controlled by the control temperature and the heating setpoint temperature. The unit goes into the heating mode of operation by analyzing the control temperature. The control temperature can be either the return temperature or the space temperature. OFF Economizer Heating Minimum DAT Minimum DAT This control mode is designed to temper the air in the ductwork when in heating mode. When the unit is in the “Fan Only” state and the Discharge Air Temperature is less than the minimum discharge air temperature limit, “Minimum DAT” control is initiated. The unit will turn on minimum heat until the discharge air temperature exceeds the limit. Start Up With a “start up” command from the “Off” State the unit will default into the “Start Up” state of operation for 3 minutes. During this time, the fan is off. Recirculation Next, the unit will transition into the “Recirculation” state of operation for another 3 minutes. During this time, the outside air damper will close and the fan will turn on, thereby mixing the air in the ductwork and the space. Fan Only The outside air damper will modulate to the minimum position and based upon the sensor inputs, the unit will go into one of the four running states - “Heating,” “Cooling,” “Economizing,” or “Minimum DAT.” If the control temperature is between its setpoint and its dead band, the unit will remain in the “Fan Only” state. www.DaikinApplied.com 85 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Sequence of Operation Mechanical Cooling Constant Volume (Space Comfort Controller) The control temperature for a CAV unit is typically the space temperature. A space temperature sensor must be field installed into the occupied space and connected to the unit controller. The unit goes into the cooling mode of operation when the control temperature (space temperature) is above the cooling setpoint by more than ½ the deadband. Example – the cooling setpoint is set to 70.0°F and the deadband is 1.0°F, the unit will not go into the cooling mode of operation until the space sensor reaches 70.6°F. When this takes place, the cooling mode of operation will begin and the 1st stage of compressor operation will start. The unit controller will turn on the next stage of compressor operation, or turn off a stage of compressor operation, to maintain the cooling setpoint temperature within the deadband. When a compressor stage turns on, the next compressor stage, up or down, will not take place for the next 4 minutes. This “4 minutes” is called the stage time. Reference the “Cooling Setup” menu for the adjustable stage time value. When a cooling stage is initiated no further operation will take place within the stage timer limit. In the above example, the unit will stage down or turn off the cooling mode of operation when the cooling setpoint reaches 69.4°F. The unit controller will turn on the next stage of compressor operation, or turn off a stage of compressor operation, to maintain the discharge air temperature setpoint within the deadband. When a compressor stage turns on, the next compressor stage up or down will not take place for the next 4 minutes. This “4 minutes” is called the stage timer. When a cooling stage is initiated no further operation will take place within the stage timer limit. Reference the Cooling Setup menu for the adjustable stage time value. In the above example, the unit will stage down or turn off the cooling mode of operation when the return temperature reaches 69.4°F. Economizer When the economizer is enabled, the outside air temperature is below the changeover setpoint, and the differential enthalpy switch (if installed) is made, the economizer becomes the first stage of cooling. It will modulate to control to either the discharge air temperature (VAV) or space temperature (CV). Every 4 minutes, the unit can then either add mechanical cooling if the economizer is at 100% open, continue economizing, or if the control temperature is satisfied, return to minimum position and transition back to “Fan Only” mode. If the enthalpy switch breaks or the outside air warms, the unit will exit economizing and continue to mechanically cool while returning to the minimum position for ventilation. Variable Air Volume (Discharge Air Controller) The unit's cooling mode of operation is controlled by the control temperature, the change-over temperature, and the discharge air temperature. The unit goes into the cooling mode of operation by analyzing the control temperature. The control temperature for a VAV system is the return temperature. The unit goes into the cooling mode of operation when the control temperature (return temperature) is above the changeover setpoint by more than ½ the deadband. Example – If the change over temperature is 70.0°F and the deadband is 1.0°F, the unit will not go into the cooling mode of operation until the return temperature reaches 70.6°F. When this takes place, the cooling mode of operation will begin and the 1st stage of compressor operation will start. IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 86 www.DaikinApplied.com Check, Test, and Start Procedures Check, Test, and Start Procedures WARNING Electric shock and moving machinery hazard. Can cause severe equipment damage, personal injury, or death. Disconnect and tag out all electrical power before servicing this equipment. All start-up and service work must be performed only by trained, experienced technicians familiar with the hazards of working on this type of equipment Read and follow this manual: “MicroTech III Unit Controller” (OM 920) before operating or servicing. Bond the equipment frame to the building electrical ground through grounding terminal or other approved means. WARNING Hazardous voltage. May cause severe injury or death. Disconnect electric power before servicing equipment. Servicing Control Panel Components Before Start-Up 1. Remove shipping bolt form fan spring. 2. Verify that the unit is completely and properly installed with ductwork connected. 3. Verify that all construction debris is removed, and that the filters are clean. 4. Verify that all electrical work is complete and properly terminated. 5. Verify that all electrical connections in the unit control panel are tight, and that the proper voltage is connected. 6. Verify all nameplate electrical data is compatible with the power supply. 7. Verify the phase voltage imbalance is no greater than 2%. 8. Verify that gas piping is complete and leak tight. Pre-Start of Unit All units are completely run tested at the factory to promote proper operation in the field. However, to ensure proper operation once the unit is installed, the following check, test, and start procedures must be performed to properly start the unit. To obtain full warranty coverage, complete and sign the check, test, and start form supplied with the unit and return it to Daikin. A representative of the owner or the operator of the equipment should be present during start-up to receive instructions in the operation, care, and ma enance of the unit. 9. Verify that the shutoff cock is installed ahead of the furnace, and that all air has been bled from the gas lines. 10. Verify installation of gas flue and outside air vents. 11. Manually rotate all fans and verify that they rotate freely. 12. Verify that the belts are tight and the sheaves are aligned. 13. Verify that all setscrews and fasteners on the fan assemblies are still tight. See Setscrews on page 105. 14. Verify that the evaporator condensate drain is trapped and that the drain pan is level. 15. If unit is curb mounted, verify that the curb is properly flashed to prevent water leakage. 16. Review the equipment and service literature, the sequences of operation, and the wiring diagrams to become familiar with the functions and purposes of the controls and devices. 17. Determine which optional controls are included with the unit. www.DaikinApplied.com 87 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Check, Test, and Start Procedures Power-Up Compressor Start-Up 1. Close the unit disconnect switch. 2. Power should now be supplied to the control panel. Fan Start-Up 1. Remove shipping bolt from fan spring if this has not already been done. 2. Verify fan spring adjustment and that the fan assembly is level. Adjust as necessary. CAUTION Low ambient temperature hazard. Can cause compressor damage. Do not attempt to start up and check out the refrigeration system when the outdoor air temperature is below 20°F. With the supply fan operational, prepare for compressor operation. 1. Connect service g t has not lost its refrigerant 3. Verify all duct isolation dampers are open. 2. Verify These should operate for arting the compressors. 4. Place the unit into the “Fan Only” mode through the keypad. 3. Verify that the condenser fan blades are positioned properly (see Figure 74) and that the screws are tight. The fan blade must be correctly positioned within its orifice for proper airflow across the condenser coils. 5. The controller should enter the “Startup Initial” operating state. If the fan does not run, check the manual motor protectors or that the circuit breakers have not tripped. 4. Check the fan rotation. 6. Verify the rotation is correct. Economizer Start-Up Figure 74: Condenser Fan Blade Positioning Fan Blade 1. Check whether the outdoor air is suitable for free cooling. 2. At the keypad, set the cooling setpoint low enough so the controller calls for cooling. Orifice 3. Place the unit into cooling mode through the keypad menu. 4. Observe the outdoor air dampers: a. If the outdoor enthalpy is low, the control algorithm should start to modulate the dampers open to maintain the discharge air setpoint. 1.21" b. If the outdoor enthalpy is high, the dampers should maintain their minimum position. NOTE: It may not be possible to check the economizer operation in both low and high enthalpy states on the same day. If this is the case, repeat this procedure on another day when the opposite outdoor air enthalpy conditions exist. IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 88 www.DaikinApplied.com Check, Test, and Start Procedures Scroll Compressor Rotational Direction Scroll compressors only compress in one rotational direction. Three-phase compressors rotate in either direction depending upon phasing of the power to L1, L2, and L3. Since there is a 50/50 chance of connecting power to cause rotation in the reverse direction, verify that the compressor rotates in the proper direction after the system is installed. If the compressor is rotating properly, suction pressure drops and discharge pressure rises when the compressor is energized. If the compressor is rotating in reverse, the sound level is louder and current draw is reduced substantially. After several minutes of operation, the compressor’s internal protector trips. All three-phase compressors are wired the same internally. Therefore, once the correct phasing is determined for a specific system or installation, connecting properly phased power leads to the same terminals should maintain proper rotation direction. Perform the Following Procedure: 1. At the keypad, set the cooling setpoint low enough so that the controller will call for cooling. 2. Verify that compressor #1 starts. If the compressor motor hums but does not run, verify that it is getting threephase power. 3. The compressor should operate continuously while there is a call for cooling. If the compressor cycles on and off on its low pressure switch, perform the following: a. Verify that the circuit is not short of refrigerant. 4. Verify that the condenser fans are cycling and rotating properly (blowing air upward). When the compressor starts, at least one condenser fan should also start. 5. Check the oil level in the compressor sightglass. If low oil is observed, it is possible that liquid refrigerant is returning to the compressor. Check the suction superheat, see “Expansion Valve Superheat Adjustment” below. It should be between 10°F (5.5°C) and 13°F (7.2°C). See “Expansion Valve Superheat Adjustment” below. 6. Verify that the condenser refrigerant subcooling at full capacity is between 13°F and 20°F. Checking Subcooling Following are recommendations for checking subcooling: 1. Run unit until it reaches steady state. Close the unit section doors. Running the unit with its doors open will affect system operation. 2. Measure the discharge gas pressure at the compressor discharge gauge port with an accurate gauge. Use this pressure to determine the saturation temperature of the refrigerant. 3. Measure liquid temperature accurately by attaching a thermocouple to the liquid line tube leaving the condenser coil. Insulate the tube and thermocouple for more accurate results. 4. Subtract the measured liquid temperature from the saturation temperature to determine the subcooling. b. Check for low airflow across the evaporator coil. 5. As a general rule, high subcooling indicates that the circuit is low on charge. Low subcooling generally indicates that the circuit has too much charge. c. Check for clogged filters. d. Check for restricted ductwork. e. Check for very low temperature return air entering the unit. NOTICE f. Verify that the liquid line components, expansion valve, and distributor tubes are feeding the evaporator coil. Venting refrigerant to atmosphere is not allowed per most local laws and/or codes. g. Verify that all air handling section panels are closed. www.DaikinApplied.com 89 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Check, Test, and Start Procedures Expansion Valve Superheat Adjustment Drive Belt Tension Adjustment It is very important that the expansion valve superheat setting be adjusted to be between 10°F (5.5°C) and 13°F (7.2°C). Insufficient superheat will cause liquid floodback to the compressor which may result in slugging. Excessive superheat will reduce system capacity and shorten compressor life. 1. The ideal tension is the lowest tension at which the belt will not slip under peak load conditions. Over tensioning shortens belt and bearing life. Turn the adjustment stem clockwise to increase superheat. Not exceeding one turn, adjust the stem and then observe the superheat. Allow up to 30 minutes for the system to rebalance at the final superheat setting. 3. Keep belts free from foreign material which may cause slippage. 2. Check tension frequently during the first 24–48 hours of operation. 4. Make V-drive inspection on a periodic basis. Adjust tension if the belt is slipping. Do not apply belt dressing. This may damage the belt and cause early failure. Checking Superheat Following are recommendations for checking superheat: 1. Close the unit section doors. Running the unit with its doors open will affect expansion valve and system operation considerably. Air Balancing The following should be performed by a qualified air balancing technician: 1. Check the operating balance with the economizer dampers positioned for both full outdoor air and minimum outdoor air. 2. Check the pressure and temperature at the suction gauge port. Sheave Alignment 2. Verify that the total rflow will never be less than that required for operation of the electric heaters or gas furnace. 1. Verify both motor and fan sheaves are in alignment and the shafts are parallel. The center line of the motor sheave must be in line with the center line of the fan sheave. See Figure 75. 3. When the final drive adjustments or changes are complete, check the current draw of the supply fan motors. The amperage must not exceed the service factor stamped on the motor nameplate. 2. Verify that all setscrews are torqued to the values shown in Table 34 on page 105 before starting drive. Check setscrew torque and belt tension after 24 hours of service. Figure 75: Sheave Alignment (Adjustable Shown) Must be parallel WARNING Moving machinery hazard. Can cause severe personal injury or death. Do not use a mechanically driven tachometer to measure the speed return fans on this fan arrangement. Use a strobe tachometer. Rotating parts can cause severe personal injury or death. Replace all belt/fan guards that are removed for service. Bearing Center lines must coincide Motor Must be parallel Fixed Pitch Sheave IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 90 www.DaikinApplied.com Check, Test, and Start Procedures Energy Recovery Wheel Prestartup Checks Figure 76: Energy Recovery Wheel 1. By hand, turn wheel clockwise (as viewed from the pulley side) to verify wheel turns freely through 360° rotation. 2. During rotation confirm wheel segments are fully engaged in the wheel frame and segment retainers are completely fastened 3. With hands and objects away from moving parts, apply power and confirm wheel rotation. Wheel rotates clockwise as viewed from the pulley side. 4. If wheel has difficulty starting, disconnect power and inspect for excessive interference between the wheel surface and each of the (4) diameter seals. Diameter Seal Adjustment 1. Loosen diameter seal adjusting screws. See Figure 76. 2. Move adjustable diameter seals away from wheel. 3. Using a ¼ inch feeler gauge, adjust the diameter against the wheel. See Figure 76. 4. Tighten diameter seal adjusting screws. 5. Apply power per the start up procedure. WARNING Keep hands away from rotating wheel! Contact with rotating wheel can cause physical injury. www.DaikinApplied.com 91 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Final Control Settings Final Control Settings Controller Settings for Normal Operation When all start-up procedures are completed, set the controls and program the MicroTech III controller for normal operation. Use the following list as a guide; some items may not apply to your unit. 1. Set the heating and cooling parameters as required for normal unit operation: Maintaining Control Parameter Records Daikin recommends that the MicroTech III controller’s setpoints and parameters be recorded and saved for future reference. If the microprocessor control board requires replacement, this record facilitates entering the unit’s proper a. Temperature \ Zone Cooling \ b. Temperature \ Zone Heating \ c. Temperature \ Discharge Cooling \ 2. Set the low ambient compressor lockout setpoint as required. Do not set it below 20°F. 3. Set the high ambient heat lockout temperature setpoint. 4. Set the alarm limits as required. 5. Set the duct static pressure control parameters as required. 6. Set the building static pressure control parameters as required. 7. Set the economizer control parameters as required. 8. Set the date and time in keypad menu. 9. Set the operating schedule as required using keypad menus. NOTE: Unit operation may also be controlled by the building automation system. IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 92 www.DaikinApplied.com Maintenance Maintenance Performing Service Maintenance Planned Maintenance Installation and maintenance must be performed only by qualified personnel who are experienced with this type of equipment and familiar with local codes and regulations. WARNING Moving machinery and electrical power hazards. May cause severe personal injury or death. Disconnect and lock off all power before servi ng equipment. CAUTION Sharp edges are inh rent to sheet metal parts, screws, clips, and similar items. May cause personal injury. Exercise caution when servicing equipment. Preventive maintenance is the best way to avoid unnecessary expense and inconvenience. Have this system inspected at regular intervals by a qualified service technician. The required frequency of inspections depends upon the total operating time and the indoor and outdoor environmental conditions. Routine maintenance should cover the following items: • Tighten all belts, wire connections, and setscrews. • Clean the evaporator and condenser coils mechanically or with cold water, if necessary. Usually any fouling is only matted on the entering air face of the coil and can be removed by brushing or vacuuming. • Lubricate the motor and fan shaft bearings. • Align or replace the belts as required. IMPORTANT Chilled Water Piping: A qualified Architect or Systems HVAC Design Engineer familiar with piping design, local codes and regulations, must provide piping design. The following manufacturer recommendations serve as a general guide and should not replace a qualified professional’s piping system design. • Clean or replace the filters as required. NOTE: A partially full sight glass is not uncommon at part load conditions. A varying amount of bubbles may be noticeable in the sightglass, which is normal. • Check for proper superheat. • Check for blockage of the condensate drain. Clean the condensate pan as needed. • Check the power and control voltages. IMPORTANT Refrigerant Piping: A qualified Architect or Systems HVAC Design Engineer familiar with refrigerant piping design, as well as local codes and regulations, must provide refrigerant piping design. The following manufacturer recommendations serve as a general guide and should not replace a qualified professional’s refrigerant piping system design. • Check the running amperage of all motors. • Check all operating temperatures and pressures. • Check and adjust all temperature and pressure controls as needed. • Check and adjust all damper linkages as needed. • Check the operation of all safety controls. • Check the condenser fans and tighten their setscrews. WARNING Hazardous voltage. May cause severe injury or death. Disconnect electric power before servicing equipment. More than one disconnect may be required to de-energize the unit. Servicing Control Panel Components Disconnect all electric power to the unit when servicing control panel components. Before servicing, always inspect units for multiple disconnects to ensure all power is removed from the control panel and its components. All-Aluminum Condenser Coils The condenser coils are an all-aluminum design including the connections, micro-channels, fins (an oven brazing process brazes the fins to the micro-channel flat tube), and headers (Figure 77), which eliminates the possibility of corrosion normally found between dissimilar metals of standard coils. During the condensing process, refrigerant in the coil passes through the micro-channel flat tubes, resulting in higher efficiency heat transfer from the refrigerant to the airstream. In the unlikely occurence of a coil leak, contact Daikin to receive a replacement coil module. www.DaikinApplied.com 93 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Maintenance Figure 77: Micro-Channel Coil Cross-Section Cleaning Option E Coated Coils The following cleaning procedures are recommended as part of the routine maintenance activities for Option E Coated Coils. Documented routine cleaning of Option E Coated Coils is required to maintain warranty coverage. WARNING Prior to cleaning the unit, turn off and lock out the main power switch to the unit and open all access panels. Remove Surface Loaded Fibers Connecting the Condenser Coil to Copper Tubing Figure 78 shows the aluminum condenser coil connection to the copper tubing in the unit. Because of the low melting point of aluminum (1220°F compared to 1984°F for copper), this brazed joint is performed with a low temperature brazing process. CAUTION Potential equipment damage. If a standard copper brazing process is performed at this joint, the process will damage the aluminum connection. If a condenser coil ever needs to be replaced, the copper aluminum joint repair should be done with a ProBraze™ repair kit manufactured by OmniTechnologies Corporation. A non-corrosive flux must also be used. The brazing temperature should be between 850°F–900°F. If a coil needs replacing, contact Daikin for a coil and copper connection assembly. Figure 78: Aluminum/Copper Connection Surface loaded fibers or dirt should be removed prior to water rinse to prevent further restriction of airflow. If unable to back wash the side of the coil opposite that of the coils entering air side, then surface loaded fibers or dirt should be removed with a vacuum cleaner. If a vacuum cleaner is not available, a soft non-metallic bristle brush may be used. In either case, the tool should be applied in the direction of the fins. Coil surfaces can be easily damaged (fin edges bent over) if the tool is applied across the fins. NOTE: Use of a water stream, such as a garden hose, against a surface loaded coil will drive the fibers and dirt into the coil. This will make cleaning efforts more difficult. Surface loaded fibers must be completely removed prior to using low velocity clean water rinse. Periodic Clean Water Rinse A monthly clean water rinse is recommended for coils that are applied in coastal or industrial environments to help to remove chlorides, dirt and debris. An elevated water temperature (not to exceed 130ºF) will reduce surface tension, increasing the ability to remove chlorides and dirt. Pressure washer PSI must not exceed 900 psig and the nozzel should remain at leat 1 foot from the coil to avoid damaging fin edges. Routine Quarterly Cleaning of Option E Coated Coil Surfaces Quarterly cleaning is essential to extend the life of an Option E Coated Coil and is required to maintain warranty coverage. Coil cleaning shall be part of the unit’s regularly scheduled maintenance procedures. Failure to clean an Option E Coated Coil will void the warranty and may result in reduced efficiency and durability in the environment. For routine quarterly cleaning, first clean the coil with the below approved coil cleaner (see approved products list under Recommended Coil Cleaners section, Table 29). After cleaning the coils with the approved cleaning agent, use the approved chloride remover (under the Recommended Chloride Remover section) to remove soluble salts and revitalize the unit. IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 94 www.DaikinApplied.com Maintenance Recommended Coil Cleaner Cautions The following cleaning agent, assuming it is used in accordance with the manufacturer’s directions on the container for proper mixing and cleaning, has been approved for use on Option E Coated Coils to remove mold, mildew, dust, soot, greasy residue, lint and other particulate: Harsh Chemical and Acid Cleaners Table 29: Option E Coated Coil Recommended Cleaning Agents Cleaning Agent Reseller Part Number Enviro-Coil Concentrate Hydro-Balance Corp P.O. Box 730 Prosper, TX 75078 800-527-5166 H-EC01 Enviro-Coil Concentrate Home Depot H-EC01 Chloride Remover Chlor*Rid Int’l, Inc. P.O. Box 908 Chandler AZ 85244 800-422-3217 Chlor*Rid DTS Harsh chemicals, household bleach or acid cleaners should not be used to clean outdoor or indoor Option E Coated Coils. These cleaners can be very difficult to rinse out of the coil and can accelerate corrosion and attack the Option E coating. If there is dirt below the surface of the coil, use the recommended coil cleaners as described above. High Velocity Water or Compressed Air High velocity water from a pressure washer or compressed air should only be used at a very low pressure to prevent fin and/ or coil damages. The force of the water or air jet may bend the fin edges and increase airside pressure drop. Reduced unit performance or nuisance unit shutdowns may occur. CHLOR*RID DTS™ should be used to remove soluble salts from the Option E Coated Coil, but the directions must be followed closely. This product is not intended for use as a degreaser. Any grease or oil film should first be removed with the approved cleaning agent. 1. Remove Barrier - Soluble salts adhere themselves to the substrate. For the effective use of this product, the product must be able to come in contact with the salts. These salts may be beneath any soils, grease or dirt; therefore, these barriers must be removed prior to application of this product. As in all surface preparation, the best work yields the best results. 2. Apply CHLOR*RID DTS - Apply CHLOR*RID DTS directly onto the substrate. Sufficient product must be applied uniformly across the substrate to thoroughly wet out surface, with no areas missed. This may be accomplished by use of a pump-up sprayer or conventional spray gun. The method does not matter, as long as the entire area to be cleaned is wetted. After the substrate has been thoroughly wetted, the salts will be soluble and is now only necessary to rinse them off. 3. Rinse - It is highly recommended that a hose be used, as a pressure washer will damage the fins. The water to be used for the rinse is recommended to be of potable quality, though a lesser quality of water may be used if a small amount of CHLOR*RID DTS is added. Check with CHLOR*RID International, Inc. for recommendations on lesser quality rinse water. www.DaikinApplied.com 95 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Maintenance Control Panel Components The following individual motor protection is provided. Table 30: Maverick Individual Motor Control and Protection Motor Type Short Circuit Overload ON-OFF Compressor < 100 Amps MMP Internal Contactor Condenser Fans MMP Internal Contactor EAF, no VFD, 208-460V MMP MMP Contactor Other MMP Features: • Three-position rotary operator: OFF (O)-TRIP-ON (I) (Figure 79). • Lockout—tagoutable rotary operator: turn the rotary operator to OFF (O), slide out the extension arm, and insert a lockout pin. EAF, no VFD, 575V CB OL Contactor EAF with VFD CB* VFD VFD • Ambient compensated –20°C to +40°C. SAF with VFD CB* VFD VFD SAF, no VFD CB OL Contactor • Single-phase sensitivity: if one phase exceeds setpoint, all three phases open. MMP = manual motor protector Internal = vendor motor protector with internal sensors CB = circuit breaker [* FB with MD4 VFD] OL = over load relay Manual Motor Protector (MMP) • Trip test: insert a 9/64" screw driver in the test slot to simulate a trip. Figure 79: Manual Motor Protector The manual motor protector (MMP) provides coordinated branch circuit, short circuit protection, a disconnecting means, a motor controller, and coordinated motor overload protection. A short circuit indicator with manual reset is mounted along side of each MMP as a means to differentiate between a short circuit and overload trip conditions. The MMP trip points are factory set. Do not change unless the motor ampacity changes or the MMP is replaced with a new device with incorrect setpoint adjustment. Any other non-authorized trip point or setpoint adjustment voids all or portions of the unit’s warranty. Authorized setpoint adjustment is accomplished as follows 1. For motors with a 1.15 service factor, rotate the arrow on the dial to correspond to the motor FLA. 2. For motors with a 1.0 service factor, multiply the motor FLA by 0.9; then rotate the arrow on the dial to correspond to that value. To reset a tripped MMP, clear the trip by rotating the knob counterclockwise to the OFF (O) position; then rotate knob clockwise to the ON (I) position. See Figure 79. WARNING If an overload or a fault current interruption occurs, check circuits to determine the cause of the interruption. If a fault condition exits, examine the controller. If damaged, replace it to reduce the risk of fire or electrical shock. IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 96 www.DaikinApplied.com Maintenance Thermal Overload Relay Circuit Breaker Designed to provide current-dependent protection for loads with normal starting against impermissibility high temperature rises due to overload, phase asymmetry or phase failure. Increase in motor current beyond set point as a result to overload or phase failure will trip the overload and disconnect the motor. Circuit breakers are installed upstream of all VFDs to provide short circuit protection. These breakers are not adjustable. To reset a tripped circuit breaker: Clear the trip by rotating the lever down to the OFF position. Then rotate lever up to the ON position (see Figure 81). The Relay trip points are factory set. Do not change unless the motor ampacity changes or the Relay is replaced with a new device with incorrect set point adjustment. Any other non-authorized trip points or set points adjustment voids all or portions of the unit’s warranty. Authorized set point adjustment is accomplishment as follows: 1. For motors with 1.15 service factor, rotate the arrow on the dial to correspond to the motor FLA (See Figure 80). 2. For motors with a 1.0 service factor, multiply the motor FLA with 0.9; then rotate the arrow on the dial to correspond to that value. Breakers, like MMPs, have three distinct modes of operation which are clearly indicated by the handle position. The positions are ON (usually up, OFF (usually down), and TRIPPED (midway). Some circuit breakers may have a pushto-test button. CAUTION If a circuit breaker has tripped due to an overload or a fault current (short circuit), prior to resetting, the connected wiring circuits must be checked to determine the cause of the interruption. To reset a tripped Relay, push the blue RESET button. To disconnect, push the Red stop Button. Reset After Tripping Information Other Relay features: If a breaker is tripped, the handle/lever will be halfway between the OFF and ON positions. To reset a tripped circuit breaker: • Three connection systems options, Screw type, spring loaded and ring cable lug connection. 1. Press the handle or rotate the lever to the OFF position. 2. Press the handle or rotate the lever the opposite direction to the ON position. • Switch position indicator to indicate a trip and TEST function for wiring. • Large rotary button to adjust current to Motor RLA. WARNING • Selector switch for manual/and automatic RESET. In certain applications the circuit breaker may be mounted upside down. Therefore, when the handle is in the DOWN position it may not be turned OFF. The handle position corresponds to ON and OFF text clearly printed on the face of the unit. Be sure the mounting orientation and desired handle position is verified prior to performing service on the equipment. Only qualified service personnel should work on this equipment. Improper position of the breaker handle during service may result in electric shock or death. Figure 80: Overload Relay Figure 81: Circuit Breaker www.DaikinApplied.com 97 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Maintenance Field Wiring Terminals Phase Voltage Monitor (PVM) All field wiring terminals are spring clamp type, which offer several advantages over traditional screw-type terminals: The phase voltage monitor (Figure 83) is designed to protect three-phase loads from damaging power conditions. A microprocessor-based voltage and phase sensing circuit constantly monitors the three-phase voltages to detect harmful power line conditions. When a harmful condition is detected, its output relay is deactivated after a specified trip delay (Trip Delay). The output relay reactivates after power line conditions return to an acceptable level for a specified amount of time (Restart Delay). The trip and restart delays prevent nuisance tripping due to rapidly fluctuating power line conditions. • Spring connections do not require torquing • Spring connections resist failure due to vibration • Easily identifiable terminal markers • Combination spring release and square test ports Wire connections require inserting (“1” in Figure 82) a stripped wire a round port and clamping the stripped wire by inserting a flat-bladed screw driver in the adjacent square port (“2”). Figure 82: Terminal Connectors There are two LEDs on the face of the PVM (“1” in Figure 83) to indicate the following items in Table 31. Figure 83: Phase Voltage Monitor Table 31: LED Indication Status LED Indicator Normal operation, no faults, relay energized Green LED - steady on Loss of input phase (relay deenergized) Red LED - flash twice, off, flash twice, off, etc. Voltage unbalance (relay deenergized) Red LED - flash twice, off, flash twice, off, etc. High or low voltage (relay deenergized) Red LED - steady on Phase reversal (relay deenergized) Red LED - pulse on, off, on, off, etc. Restart delay (fault cleared, PVM pending restart, relay de-energized) Green LED - pulse on, off, on, off, etc. Other features: • Standard 2% to 8% variable voltage unbalance (“3” in Figure 83). • Standard 1 to 500 second variable restart delay (“2”). • Standard 1 to 30 second trip delay (“4”) (except loss of phase, which trips at 1 second non-adjustable). IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 98 www.DaikinApplied.com Maintenance Unit Storage Through-the-Door Disconnect Opening the through-the-door disconnect without performing a proper machine shut-down is not recommended except in emergencies. Location The Maverick II is an outdoor unit. However, the construction schedule may dictate storage either on the ground or in its final position at the site. If the unit is stored on the ground, additional precautions should be taken as follows: The optional disconnect provides for locking out power to the unit. To lock out power to the unit, rotate the habdle to the “Reset/Lock” position and insert a padlock or locking device through the base of the handle. Do not lockout the handle with the Interlock in bypass mode. • Make sure that the unit is well supported along the length of the base rail. DANGER Hazardous voltage. May cause severe injury or death. Disconnect electric power before servicing equipment. More than one disconnect may be required to de-energize the unit. CAUTION Molded case switches do not provide over-current protection. This device may automatically open the circuit at levels above the ampere rating of the switch. • Make sure that the unit is level (no twists or uneven ground surface). • Provide proper drainage around the unit to prevent flooding of the equipment. • Provide adequate protection from vandalism, mechanical contact, etc. • Make sure all doors are securely closed and all latches closed. • Units should be fitted with covers over the supply and return air openings. Preparation for Storage Figure 84: Through-the-Door Handle Disconnect Supply Fans 1. Remove the drive belts, tag them with the fan name and unit serial number, and store them in a conditioned space out of direct sunlight. 2. Once every two weeks, rotate the fan and motor shafts. Mark the shaft positions first to make sure they stop in a different position. 3. Depending on local climate conditions, condensate may collect on components inside the units. To prevent surface rust and discoloration, spray all bare metal parts with a rust preventive compound. Pay close attention to fan shafts, sheaves, bearings, and bearing supports. Cabinet Sections Once a month, open a door on each section and verify that no moisture or debris is accumulating in the unit. Control Compartment 1. Daikin recommends that the electronic control equipment in the unit be stored in a 5% to 95% RH (noncondensing) environment. 2. It may be necessary to put a heat source (light bulb) in the main control panel to prevent the accumulation of atmospheric condensate within the panel. The location and wattage of the heat source is dependent on local environmental conditions. 3. Check the control compartment every two weeks to confirm that the heat source is functional and is adequatefor current conditions. www.DaikinApplied.com 99 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Maintenance Restart Vibration Levels After extended storage, perform a complete start up. Inevitable accumulations of dirt, insect nests, etc. can contribute to problems if not cleaned out thoroughly prior to start up. In addition, thermal cycling tends to loosen mechanical and electrical connections. Following the startup procedure helps discover these and other issues that may have developed during the storage interval. Each unit as shipped is trim balanced to operate smoothly. To provide satisfactory operation after shipping and installation, use accepted industry guidelines for field balancing fans. NOTE: Excessive vibration from any cause contributes to premature fan and motor bearing failure. Monitor overall vibration levels every six months of operation. An increase in levels is an indication of potential trouble. Vibration Causes Bearing Lubrication 1. Wheel imbalance. a. Dirt or debris on wheel blades. CAUTION b. Loose setscrews in wheel hub or bearing-to-shaft. Bearing overheating potential can damage the equipment. Do not overlubricate bearings. Use only a high grade mineral grease with a 200°F safe operating temperature. c. Wheel distorted from overspeed. 2. Bent shaft. Motor Bearings 3. Faulty drive. a. Bad V-belts; lumpy, or mismatched. Supply Fans b. Belt tension too tight or too loose. Supply fan motors should have grease added after every 2000 hours of operation. Use one of the greases shown in Table 32. Using the following procedure, relubricate the bearings while the motor is warm, but not running. 4. Bad bearings or loose bearing hold-down bolts. 5. Motor imbalance. 6. Fan section not supported evenly on foundation. 1. Remove and clean upper and lower grease plugs. 2. Insert a grease fitting into the upper hole and add a small amount of clean grease with a low pressure gun. Periodic Service and Maintenance 1. Check all moving parts for wear every six months. 3. Install the lower grease plug. 2. Check bearing collar, sheave, and wheel hub setscrews, sheave capscrews, and bearing hold-down bolts for tightness every six months. 4. Run the motor for five minutes before installing the upper grease plug. Condenser Fan and Exhaust Fan The condenser fan and exhaust fan motors are permanently lubricated and require no periodic lubrication. Fan Shaft Bearings Relubricate fan shaft bearings periodically. Relubricate according to the schedule on the fan housing. If the bearings are exposed to wet conditions, wide temperature variations, or other severe atmospheric conditions, relubricate more frequently. Use one of the greases shown in Table 32. While the bearing is at normal operating temperatures, rotate the fan by hand and add only enough grease to purge the seals. The seals bleed slightly when this occurs. Do not overlubricate. Table 32: Recommended Greases Manufacture Product Name Temp. Range (°F) Texaco Lubricants Co. Premium RB -30 to 300 Mobil Oil Corporation Mobilith AW2 -40 to 325 Shell Oil Company Alvania No. 2 -20 to 240 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 100 www.DaikinApplied.com Maintenance Energy Recovery Wheel Drive Belts CAUTION Installation and maintenance must be performed only by qualified personnel who are experienced with this type of equipment and familiar w th local codes and regulations. WARNING Moving machinery and electrical power hazards. Can cause severe personal injury or death. Disconnect and lock off all power before servicing equipment. CAUTION Sharp edges are inherent to sheet metal parts, screws, clips, and similar items. Contact with these edges may cause personal injury. Exercise caution when servicing equipment. DANGER Hazardous voltage. Will cause severe injury or death. Disconnect electric power before servicing equipment. More than one disconnect may be required to de-energize the unit. Servicing Control Panel Components Disconnect all electric power to the unit when servicingcontrol panel components. Before servicing, always inspectunits for multiple disconnects to ensure all power is removedfrom the control panel and its components. Bearings Enthalpy wheels are provided with "no maintenance" inboard bearings, requiring no maintenance during the life of the equipment. Drive Motor The wheel drive belt is a urethane stretch belt designed to provide constant tension through the life of the belt. No adjustment is required. Inspect the drive belt annually for proper tracking and tension. A properly tensioned belt will turn the wheel immediately after power is applied with no visible slippage during start-up. Belts are multilink with individual links constructed of a high performance polyurethane elastomer, reinforced with multiple plies of polyester fabric. This belt provides a strong, yet flexible belting. The multilink feature provides easy servicing or replacement. Seals The seals are designed to be durable and require no maintenance other than adjustment. If seals become worn or damaged they may easily be replaced. The seals are made to clip onto the cassette or metal post easily. Variable Frequency Controller No maintenance should be required on the VFD. Should problems with the VFD develop, consult the VFD service manual that accompanied your order. Wheel The enthalpy wheel is designed to last the life of the equipment. It is protected by an ASHRAE 30% filter to keep dust and dirt from the heat transfer surface. The wheel is somewhat self cleaning through its normal action of rotating in and out of countercurrent air flow streams. If the wheel becomes dirty, it may be cleaned by blowing out the unit with compressed air (20 psig maximum). In cases of severe dirt, the wheel may be removed from the cassette and washed with water following wheel removable procedures outlined below. The drive motor should require no maintenance. The wheel drive motor bearings are pre-lubricated and no further lubrication is necessary. The wheel drive pulley is secured to the drive motor shaft by a combination of either a key or D slot or setscrew. The set screw is secured with removable locktite to prevent loosening. Annually confirm set screw is secure. www.DaikinApplied.com 101 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Maintenance Routine Maintenance Cleaning Air Seals The need for periodic cleaning of the energy recovery wheel will be a function of operating schedule, climate and contaminants in the indoor air being exhausted and the outdoor air being supplied to the building. Four adjustable diameter seals are provided on each cassette to minimize transfer of air between the counter flowing airstreams. The Daikin wheel is “self-cleaning” with respect tiny particles due to its laminar flow characteristics. Smaller particles pass through; larger particles land on the surface and are blown clear as the flow direction is reversed. Any material that builds up on the face of the wheel can be removed with a brush or vacuum. The primary need for cleaning is to remove oil based aerosols that have condensed on energy transfer surfaces. A characteristic of all dry desiccants, such films can close off micron sized pores at the surface of the desiccant material, reducing the efficiency by which the desiccant can adsorb and desorbs moisture and also build up so as to reduce airflow. In a reasonably clean indoor environment such as school or office building, measurable reductions of airflow or loss of sensible (temperature) effectiveness may not occur for several years. Measurable changes in latent energy (water vapor) transfer can occur in shorter periods of time in applications such as moderate occupant smoking or cooking facilities. In applications experiencing unusually high levels of occupant smoking or oil based aerosols such as industrial applications involving the ventilation of machine shop areas for example, annual washing of energy transfer may be necessary to maintain latent transfer efficiency. Proper cleaning of the energy recovery wheel will restore latent effectiveness to near original performance. To adjust diameter seals, loosen diameter seal adjusting screws and back seals away from wheel surface (Figure 85). Rotate wheel clockwise until two opposing spokes are hidden behind the bearing support beam. Using a folded piece of paper as a feeler gauge, position paper between the wheel surface and diameter seals. Adjust seals towards wheel surface until a slight friction on the feeler gauge (paper) is detected when gauge is moved along the length of the spoke. Retighten adjusting screws and recheck clearance with “feeler” gauge. Wheel Drive Components The wheel drive motor bearings are prelubricated and no further lubrication is necessary. The wheel drive pulley is secured to the drive motor shaft by a combination of either a key or D slot or setscrew. The set screw is secured with removable locktite to prevent loosening. Annually confirm set screw is secure. The wheel drive belt is a urethane stretch belt designed to provide constant tension through the life of the belt. No adjustment is required. Inspect the drive belt annually for proper tracking and tension. A properly tensioned belt will turn the wheel immediately after power is applied with no visible slippage during start-up. Figure 85: Adjusting Diameter Seals To clean, gain access to the energy recovery wheel and remove segments. Brush foreign material from the face of the wheel. Wash the segments or small wheels in a 5% solution of non-acid based coil cleaner (such as Acti-Klean, available through Daikin, Stock # AK1) or alkaline detergent and warm water. Soak in the solution until grease and tar deposits are loosened (Note: some staining of the desiccant may remain and is not harmful to performance). Before removing, rapidly run finger across surface of segment to separate polymer strips for better cleaning action. Rinse dirty solution from segment and remove excess water before reinstalling in wheel. CAUTION Do not use acid based cleaners, aromatic solvents, steam or temperatures in excess of 170ºF; damage to the wheel may occur! IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 102 www.DaikinApplied.com Maintenance Segment Installation & Replacement Figure 87: Installing Wheel Segments Wheel segments are secured to the wheel frame by a Segment Retainer which pivots on the wheel rim and is held in place by a Segment Retaining Catch (Figure 86). To install wheel segments follow steps 1 through 5 (Figure 87). Reverse the procedure for segment removal. 1. Disconnect power to the drive motor. 2. Unlock two segment retainers. There is one on each side of the selected segment opening. 3. With the embedded stiffener facing he motor side, insert the node of the segment between hub plates. 4. Holding the segment by the two outer corners, press the segment towards the center of the wheel and inwards against the spoke flanges. If hand pressure does not fully seat the segment, insert the flat tip of a screwdriver between the wheel rim and outer corners of the segment and apply downward force while guiding the segment into place. 5. Close and latch each Segment Retainer under the Segment Retaining Catch. 6. Slowly rotate the wheel 180°. Install the second segment opposite the first for counter balance. Rotate the two installed segments 90° to balance the wheel while the third segment is installed. Rotate the wheel 180° again to install the fourth segment opposite the third. Repeat this sequence with the remaining four segments. Figure 86: Segment Retaining Clip Wheel Drive Motor & Pulley Replacement 1. Disconnect power to the drive motor. 2. Remove belt from the pulley and positions temporarily around the wheel rim. 3. Loosen the set screw in wheel drive pulley using Allen wrench and remove pulley from the motor drive shaft. 4. While supporting the weight of the drive motor in one hand, loosen and remove (4) mounting bolts 5. Install the replacement motor with hardware kit supplied. 6. Install the pulley per the dimensions in Figure 88 and secure the set screw to the drive shaft 7. Stretch belt over pulley and engage grove. 8. Follow start up procedure on page 91 (procedure needs to be confirmed). Figure 88: Pulley Installation www.DaikinApplied.com 103 Series DIM–A 36 1/4" 52 1/4" 64 7/16" 74 7/16" 86 7/16" IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Maintenance Belt Replacement 1. Obtain access to the pulley side bearing access plate and remove two retaining screws. 2. Using a hexagonal wrench, loosen the screw in the bearing lock collar. 3. Using a light hammer and drift, tap collar in the direction of wheel rotation to unlock collar. Remover collar. Troubleshooting The following table may be used as a quick-reference for identifying common symptoms and possible causes related to the recovery wheel. Table 33: Energy Recovery Wheel Troubleshooting Symptom Cause Check wheel rotation speed (see Variable Speed Frequency Control on page 41). 4. Using a socket wrench with extension, remove two nuts which secure bearing housing to the bearing support beam. Inadequate Wheel Performance 5. Slide bearing from shaft. 6. Using a wrench, remove the diameter seal retaining screws. Remove diameter seals from bearing beam. Check for wheel integrity and adjust seals or replace worn seals (see Energy Recovery Wheel Design on page 39 and Seals on page 101). Check entering air conditions and compare to design (see “Energy Recovery Wheel” on page 67). Check ducting for leakage and fix any leaks. Check media for dirt and clean per cleaning instructions (seeCleaning on page 102 and Segment Installation & Replacement on page 103). 7. Form a small loop on the belt and pass it through the hole in the bearing support beam. Grasp the belt at the wheel hub and pull the entire belt down. Loop the trailing edge of the belt over the shaft. Check drive belts for engagement with sheave. Improper Wheel Rotation 8. Install the new belt around the wheel and pulley. 9. Reinstall the bearing onto the wheel shaft, being careful to engage the two locating pins into the holes in the bearing support beam. Secure the bearing with two self locking nuts. High Pressure Drop 10. Reinstall the diameter seals and tighten retaining screws. See Diameter Seal Adjustment on page 91. Check drive motor. Check drive motor wiring for proper voltage. Check VFD programming (provided with optional frost protection). Check air flow and compare to design. Check filters and clean/replace as necessary. Check media for plugging and clean per cleaning instructions (see Segment Installation & Replacement). Check seals and adjust as necessary. Noise 11. Reinstall bearing locking collar. Rotate collar by hand in the direction the wheel rotates according to label on wheel casset. Lock in position by tapping pin hole with hammer and drift. Secure in position with set screw Wheel Will Not Operate 12. Reinstall bearing access cover with two screws 13. Apply power and ensure wheel rotated freely. Check the bearings for source of noise. Check the belt for slippage (see Drive Belt Tension Adjustment on page 90). Check all electrical connections. If MicroTech II controls are provided, make sure the building pressure is above setpoint such that the EAF turns on. The wheel does not operate unless the EAF is on (see Exhaust Fan Option on page 48). Figure 89: Belt Replacement IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 104 www.DaikinApplied.com Maintenance Supply Fan Refrigerant Charge Setscrews The unit nameplate references proper charge for each refrigerant circuit in case a full charge must be added to the unit. Setscrews are used to lock bearings, sheaves, locking collars, and fan wheels to their shafts. They must be checked periodically to see that they have not loosened. If this is not done, severe equipment damage could occur. CAUTION Severe loss of charge may occur if the high refrigerant pressure switch is replaced before reclaiming the refrigerant. Replace pressure switch after reclaiming refrigerant. Venting refrigerant to atmosphere is not allowed per most local laws and/or codes. Refer to the values in Table 34 and check the tightness of all setscrews with a torque wrench. Table 34: Setscrew Minimum Torque Specifications Setscrew Diameter (in.) Minimum Torque (ft.lb) 1/4 5.5 5/16 10.5 3/8 19.0 7/16 29.0 1/2 42.0 5/8 92.0 Servicing Refrigerant Sensors or Switches The Maverick II includes the following refrigerant sensors or switches. 1. Low refrigerant pressure sensing, operating switch, automatic reset. Supply Fan Wheel-to-Funnel Alignment a. Disables associated compressors on a drop in suction pressure to approximately 35 psig. The fan wheel-to-funnel alignment must be as shown in Figure 90 to obtain proper air delivery and operating clearance. If necessary, adjustments are made as follows: b. Enables associated compressors on a rise in suction pressure to approximately 60 psig. 1. Verify that the fan shaft has not moved in its bearings. 2. Loosen the fan hub setscrews and move the wheel(s) along the shaft as necessary to obtain the correct dimension shown in Table 35. 3. Retighten the setscrews to the torque specification given in Table 34. Tighten the setscrews over the keyway first; tighten those at 90 degrees to the keyway last. 4. Verify that the radial clearance around the fan is uniform. Figure 90: SWSI Airfoil Wheel-to-Funnel Alignment 2. High refrigerant pressure, protective switch, manual reset at keypad. The low pressure switch senses refrigerant pressure through shrader fittings that contain cores. The cores are stop valves that do not allow refrigerant to flow through the Shrader unless the device is in place. Therefore, the low pressure switch can be replaced without reclaiming the refrigerant. The Shrader that serves the high pressure switch does not contain a core in order to maximize the functionality of the safety. Therefore it cannot be replaced unless the refrigerant has already been reclaimed. Servicing Optional Electric Heater WARNING Hazardous voltage. May cause severe injury or death. Disconnect electric power before servicing equipment. More than one disconnect may be required to de-energize the unit. If the electric heater is not operating properly, a qualified electrician should perform the following to check if the heater is damaged: Table 35: SWSI Airfoil Wheel-to-Funnel Relationship 1. Measure continuity through all fuses. Wheel-to-Funnel Relationship (in inches) 2. Check that all electrical connections are tight. Look for signs of arcing. Wheel Diameter A 15 0.44 18 0.44 20 0.44 22 0.44 24 0.44 4. Check the resistance phase to phase for each circuit. 30 0.56 5. Check all contactors. www.DaikinApplied.com 3. Check the resistance to ground for each circuit. It should be infinite. 105 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Service and Warranty Procedure Service and Warranty Procedure Replacement Parts Replacement parts can be obtained by contacting Daikin at 1-800-37-PARTS or at www.DaikinMcQuay.com. When contacting Daikin for service or replacement parts, refer to the model number and serial number of the unit as stamped on the nameplate attached to the unit. Order the replacement compressor through the Daikin Parts Department (Minneapolis). 1. Contact the Daikin Parts Department for compressor availability. 2. Send a completed parts order form to the Daikin Parts Department. When contacting Daikin for service or replacement parts, provide the model number, serial number, and unit part number of the unit as stamped on the serial plate attached to the unit. For questions regarding wiring diagrams, provide the number on the specific diagram. If replacement parts are required, include the date of unit installation, the date of failure, an explanation of the malfunction, and a description of the replacement parts required. 3. The Parts Department processes the order and the compressors are shipped from our Dayton, OH warehouse via ground transportation. If next-day air is required, indicate this on the parts order form and a freight charge will be billed to your account. Air freight costs are not covered under the Daikin warranty. 4. After the failed compressor is replaced, return it to Daikin with a Return Goods Tag attached, which you will receive in the mail. It must be attached to the compressor. The Return Goods Tag has instructions on where to send the compressor. If the compressor is not returned, you will be billed for the replacement compressor. Compressors Scroll Compressor All Daikin Rooftop products include a first-year parts only warranty. The warranty period extends 12 months from startup or 18 months from date of shipment, whichever comes first. Labor to install these parts is not included with this warranty. Compressors are considered a part and are included in this standard warranty. All Compressors Replacement compressors for Daikin Rooftop Units can be obtained from the Daikin Service Parts department. The decision to replace the failed portion of the compressor tandem, as opposed to replacing the entire tandem, must be decided based on the following. 1. In warranty: Warranty only covers replacement of the failed portion of the tandem. 2. Out of warranty: The customer decides whether to replace the entire tandem or just a portion. 3. Some equipment may include the extended 2nd - 5th year compressor warranty option. 5. Consideration may be given at this time to a compressor teardown analysis, depending on the history of failures. In-Warranty Return Material Procedure Material other than compressors may not be returned except by permission of authorized factory service personnel of Daikin at Minneapolis, Minnesota. A “return goods” tag will be sent to be included with the returned material. Enter the information as called for on the tag in order to expedite handling at out factories and issuance of credits. All parts shall be returned to the factory designated on the return goods tag, transportation charges prepaid. The return of the part does not constitute an order for replacement. A purchase order for the replacement part must be entered through your nearest Daikin representative. The order should include the component's part number and description and the model and serial numbers of the unit involved. If it is determined that the failure of the returned part is due to faulty material or workmanship within the standard warranty period, credit will be issued on the customer's purchase order. IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 106 www.DaikinApplied.com Warranty Registration Form Warranty Registration Form Rooftop Equipment Warranty Registration Form To comply with the terms of Daikin Applied Warranty, complete and return this form within 10 days to the Warranty Department of Daikin Applied. Check, test, and start procedure for Rooftop roof mounted air conditioners with or without heat recovery and roof mounted air handlers. GENERAL INFORMATION Job Name: ____________________________________________________________ GOI No.: _______________________________ Installation address: _____________________________________________________________________________________________ City: _________________________________________________________________ State: _________________________________ Purchasing contractor: ___________________________________________________________________________________________ City: _________________________________________________________________ State: _________________________________ Name of person doing start-up: ____________________________________________________________________________________ Company name: ________________________________________________________________________________________________ Address: ______________________________________________________________________________________________________ City/State/Zip: __________________________________________________________________________________________________ UNIT INFORMATION Unit model number: ____________________________________________________ Unit serial number: ______________________ Compressor 1 model number: ____________________________________________ Serial number: __________________________ Compressor 2 model number: ____________________________________________ Serial number: __________________________ Compressor 3 model number: ____________________________________________ Serial number: __________________________ Compressor 4 model number: ____________________________________________ Serial number: __________________________ Compressor 5 model number: ____________________________________________ Serial number: __________________________ Compressor 6 model number: ____________________________________________ Serial number: __________________________ 13F-4158 (03/15) www.DaikinApplied.com ©2015 Daikin Applied • (800) 432-1342 • www.DaikinApplied.com 107 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Warranty Registration Form Rooftop Equipment Warranty Registration Form (continued) Select Yes or No. If not applicable to the type of unit, select N/A. I. INITIAL CHECK A. Is any shipping damage visible? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A B. Are fan drives properly aligned and belts properly adjusted? . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A C. Tightened all setscrews on pulleys, bearings and fans? . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A D. Have the hold-down bolts been backed off on spring mounted fan isolators? . . . . . . . . . . . . . . . . . Yes No N/A E. Do fans turn freely? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A F. Has the discharge static pressure reference line been properly located within the building? . . . . . . . . . Yes No N/A G. Electrical service corresponds to unit nameplate? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A Volts _____________ Hertz _____________ Phase _____________ H. Is the main disconnect adequately fused and are fuses installed? . . . . . . . . . . . . . . . . . . . . . . Yes No N/A I. Are crankcase heaters operating, and have they been operating 24 hours prior to start-up? . . . . . . . . . Yes No N/A J. Are all electrical power connections tight? (Check compressorelectrical box.) . . . . . . . . . . . . . . . . Yes No N/A K. Is the condensate drain trapped? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A No N/A II. FAN DATA A. Check rotation of supply fan? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes B. Voltage at supply fan motor: . . . . . . . . . . . . . . . . 1–2_____________ V 2–3 _____________ V C. Supply fan motor amp draw per phase: . . . . . . . . . . . . . . . L1 _____________ 1–3 _____________ V L2 _____________ L3 _____________ D. Fuse sizes: . . . . . . . . . . . . . . . . ._______________________________________________________________________ E. What is the supply fan rpm? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _____________ F. Check rotation of return fan?. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes G. Voltage at return fan motor: . . . . . . . . . . . . . . . . 1–2_____________ V 2–3 _____________ V H. Return fan motor amp draw per phase: . . . . . . . . . . . . . . . L1 _____________ No N/A 1–3 _____________ V L2 _____________ L3 _____________ I. Fuse sizes: . . . . . . . . . . . . . . . . ._______________________________________________________________________ J. What is the return fan rpm? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _____________ K. Record supply static pressure at unit in inches of H20: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _____________ L. Record return static pressure at unit (with outside air dampers closed) in inches of H20: . . . . . . . . . . . . . . . _____________ 13F-4158 (03/15) IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 2 108 www.DaikinApplied.com Warranty Registration Form Rooftop Equipment Warranty Registration Form (continued) Select Yes or No. If not applicable to the type of unit, select N/A. III. START-UP COMPRESSOR OPERATION A. Do compressors have holding charges? Circuit #1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A Circuit #2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A B. Are compressors rotating in the right direction? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A C. Do condenser fans rotate in the right direction? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A D. Ambient temperature (°F): . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _____________ E. Does unit start up and perform per sequence of operation? . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A IV. PERFORMANCE DATA A. Compressor voltage across each phase: . . . . . . . . . 1–2_____________ V 2–3 _____________ V 1–3 _____________ V B. Compressor amperage of fully loaded compressor: Compressor #1 — Phase 1________ Phase 2 ________ Phase 3 _______ Compressor #2 — Phase 1________ Phase 2 ________ Phase 3 _______ Compressor #3 — Phase 1________ Phase 2 ________ Phase 3 _______ Compressor #4 — Phase 1________ Phase 2 ________ Phase 3 _______ Compressor #5 — Phase 1________ Phase 2 ________ Phase 3 _______ Compressor #6 — Phase 1________ Phase 2 ________ Phase 3 _______ C. Low pressure cut-out: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Circuit 1 __________ psig Circuit 2 __________ psig D. Low pressure cut-in: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Circuit 1 __________ psig Circuit 2 __________ psig E. High pressure cut-out: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Circuit 1 __________ psig Circuit 2 __________ psig F. Discharge pressure, one compressor: . . . . . . . . . . . . . . . . . . . . . Circuit 1 __________ psig Circuit 2 __________ psig G. Discharge pressure, fully loaded, 2–3 compressors: . . . . . . . . . . . . . Circuit 1 __________ psig Circuit 2 __________ psig H. Suction pressure, one compressor: . . . . . . . . . . . . . . . . . . . . . . Circuit 1 __________ psig Circuit 2 __________ psig I. Suction pressure, fully loaded, 2–3 compressors: . . . . . . . . . . . . . . . Circuit 1 __________ psig Circuit 2 __________ psig J. Liquid press, fully loaded, 2–3 compressors (at liquid line shutoff valve): . . . Circuit 1 __________ psig Circuit 2 __________ psig K. Liquid temperature, fully loaded, 2–3 compressors: . . . . . . . . . . . . . . Circuit 1 __________ psig Circuit 2 __________ psig L. Suction line temperature: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ____________ °F ____________°F M. Superheat: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ____________ °F ____________°F N. Subcooling:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ____________ °F ____________°F O. Is the liquid in the line sightglass clear and dry? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A P. Does the hot gas bypass valve function properly?. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A 13F-4158 (03/15) www.DaikinApplied.com 3 109 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Warranty Registration Form Rooftop Equipment Warranty Registration Form (continued) Select Yes or No. If not applicable to the type of unit, select N/A. Q. At what suction pressure does the hot gas bypass valve open? . . . . . . . . . . . . _______ psig _______ psig ______ psig R. Record discharge air temperature at discharge of unit: ___________ °F S. Are all control lines secure to prevent excessive vibration and wear? . . . . . . . . . . . . . . . . . . . . . Yes No N/A T. Are all gauges shut off and valve caps and packings tight after start-up? . . . . . . . . . . . . . . . . . . . Yes No N/A No N/A V. ELECTRIC HEAT CHECK, TEST & START A. Electrical heat service corresponds tounit nameplate? . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes Volts _____________ Hertz _____________ Phase _____________ B. Are there any signs of physical damage to the electric heat coils? . . . . . . . . . . . . . . . . . . . . . . Yes No N/A C. Have all electrical terminals been tightened? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A No N/A D. Does sequence controller stage contactors properly? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes E. Electric heater voltage across each phase: . . . . . . . . . . . . . . . . . ___________ L1 ___________ L2 ___________ L3 F. Amp draw across each phase at each heating stage: Stage 1 Phase L1: ___________ Phase L2: ___________ Phase L3 ___________ Stage 2 ____________ ____________ ____________ Stage 3 ____________ ____________ ____________ Stage 4 ___________ ___________ ___________ Stage 5 ___________ ___________ ___________ G. FLA: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L1 ___________ Stage 6 ____________ ____________ ____________ L2____________ H. Operate electric heat with fans off. Electric heat must cycle on high limit control . . . . . . . . . . . . . . . Yes L3 ___________ No N/A VI. GAS BURNER CHECK, TEST, & START Specifications: For gas, see Forced Draft Gas Burner Installation and Maintenance Bulletin. (IM 684 and IM 685) A. Gas Furnace:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Model no. __________________ B. Gas Burner: . . . . . . . . . . . . . . . . . . . . . . . . . . .Model no.___________________ Serial no. ___________________ C. Gas Rated firing rate (MBH input): . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ._________________ D. Gas Altitude (ft. above sea level): . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ._________________ E. Input (CFH): . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _________________ F. Gas pressure at burner (inches w.c.): . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _________________ G. CO2 (%) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _________________ H. CO2 (%): . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _________________ I. Pilot flame only in microamps (steady at low fire): . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _________________ J. Pilot Tap-gas pressure (inches w.c.): . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _________________ K. Motor only/burner FLA running amps: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _________________ L. High limit control OK? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A M. Flame safeguard (microamps): . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _________________ 13F-4158 (03/15) IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 4 110 www.DaikinApplied.com Warranty Registration Form Rooftop Equipment Warranty Registration Form (continued) Select Yes or No. If not applicable to the type of unit, select N/A. N. Flame failure shutoff (seconds): . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _________________ O. Airswitch OK? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A P. High Gas Pressure Switch OK? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A Q. Low Gas Pressure Switch OK? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A R. Main Gas Valve Close-off OK?. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A No N/A A. Heat wheel rotates freely? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A B. Heat wheel VFD operates properly? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A VII. Hot Water Coil A. Pressure test OK? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes VIII. Heat Recovery C. Heat wheel VFD . . . . . . . . . . . . . . Model No. _________________________ Serial No. ___________________________ D. Check for air bypass around heat wheel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A A. Verify power is supplied to the MicroTech III unit controller . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A B. Verify that the shipping screws have been removed from the measuring station vane . . . . . . . . . . . . Yes No N/A C. Examine station for damage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A IX. Design Flow Calibration D. Record Level Position after calibration • LH Level Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ____________ • RH Level Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ____________ NOTE: This is viewed in the MicroTech III controller, in the Min OA setup menu. X. Have all electronic or electrical controls been checked, adjusted, and tested for proper operation per the installation and maintenance bulletins? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A XI. MAINTAINING MICROTECH CONTROL PARAMETER RECORDS After the unit is checked, tested, and started and the final control parameters are set, record the final settings. Keep these records on file and update whenever changes to the control parameters are made. Keeping a record facilitates any required analysis and troubleshooting of the system operation and facilitates restoration after a controller replacement. 13F-4158 (03/15) www.DaikinApplied.com 5 111 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS Warranty Registration Form Rooftop Equipment Warranty Registration Form (continued) Select Yes or No. If not applicable to the type of unit, select N/A. Thank you for completing this form. Please sign and date below. Signature _____________________________________________________________ Startup date: ___________________________ Return completed form by mail to: Daikin Warranty Department, 13600 Industrial Park Boulevard, Minneapolis, MN 55441 or by email to: AAH.Wty_WAR_forms@daikinapplied.com Please fill out the Daikin Applied “Quality Assurance Survey Report” and list any additional comments that could affect the operation of this unit; e.g., shipping damage, failed components, adverse installation applications, etc. If additional comment space is needed, write the comment(s) on a separate sheet, attach it to the Survey Report and return it to the Warranty Department of Daikin Applied with the completed Equipment Warranty Registration form. 13F-4158 (03/15) IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS 6 112 www.DaikinApplied.com Quality Assurance Survey Report Quality Assurance Survey Report Quality Assurance Survey Report To whom it may concern: Please review the items below upon receiving and installing our product. Mark N/A on any item that does not apply to the product. Job Name: _____________________________________________________________________ Daikin Applied G.O. No. ______________ Installation address:____________________________________________________________________________________________________ City: ___________________________________________________________________________ State: _______________________________ Purchasing contractor:__________________________________________________________________________________________________ City: ___________________________________________________________________________ State: _______________________________ Name of person doing start-up (print): ___________________________________________________________________________________ Company name: ______________________________________________________________________________________ Address: ____________________________________________________________________________________________ City/State/Zip: _______________________________________________________________________________________ 1. Is there any shipping damage visible? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A Location on unit ____________________________________________________________________________________ 2. How would you rate the overall appearance of the product; i.e., paint, fin damage, etc.? Excellent Good Fair Poor 3. Did all sections of the unit fit together properly? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A 4. Did the cabinet have any air leakage? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes No N/A No N/A No N/A No N/A No N/A Location on unit ___________________________________________________________________________________ 5. Were there any refrigerant leaks? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes From where did it occur? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Shipping Workmanship Design 6. Does the refrigerant piping have excessive vibration? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes Location on unit ___________________________________________________________________________________ 7. Did all of the electrical controls function at start-up? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes Comments _______________________________________________________________________________________ 8. Did the labeling and schematics provide adequate information? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes 9. How would you rate the serviceability of the product? Excellent Good Fair Poor Excellent Good Fair Poor Excellent Good Fair Poor 10. How would you rate the overall quality of the product? 11. How does the quality of Daikin Applied products rank in relation to competitive products? Comments _______________________________________________________________________________________ Please list any additional comments which could affect the operation of this unit; i.e., shipping damage, failed components, adverse installation applications, etc. If additional comment space is needed, write the comment(s) on a separate sheet, attach the sheet to this completed Quality Assurance Survey Report, and return it to the Warranty Department with the completed preceding “Equipment Warranty Registration Form”. www.DaikinApplied.com 113 IM 1058-6 • MAVERICK II ROOFTOP SYSTEMS