An Improved Voltage Phasor Estimation Technique to Minimize the Impact of CCVT Transients in Distance Protection E. Pajuelo Member IEEE G. Ramakrishna Member IEEE Power System Research Group University of Saskatchewan Saskatoon, SK S7N 5A9, Canada Abstract-This paper describes the impact of the transient response of coupling capacitor voltage transformers (CCVTs) on the performance of distance relays. Several factors that affect the frequency and time responses of CCVTs are considered. The effect of the transient response on phasor estimation is illustrated. A new least squares phasor estimation technique, which uses the knowledge of the frequency of the CCVT transients, is presented. A sample case, taken from a set of studies, is included to demonstrate the performance of the proposed approach. I. INTRODUCTION Distance relays are the most widely used devices for protecting transmission lines. The parameters measured by these relays are derived from the phasors of voltages and currents of the fundamental frequency. An error in the measurement of these phasors either causes undesired overreach or underreach. The accuracy and speed with which the magnitude and angle of these phasors is measured are, therefore, very important issues. Power systems are frequently subjected to changes in their operating states either due to normal switching operations or due to the occurrence of faults. The transitions between two states are accompanied with transient changes in voltages and currents. High speed relays have to make decisions when a system state changes. Because voltages and currents are experiencing transients at those times, the performance of relays is affected adversely. On EHV transmission systems, voltages are scaled down, typically to 110 V in North America, by CCVTs before they are applied to relays. In high speed devices, the performance is affected by, among other factors, the transient response of the CCVTs. This paper outlines the factors that affect the transient response of the CCVTs. Specifically considered are the design parameters, secondary burden, fault incidence angle and magnitude of voltage change. The impact of the CCVT transients is demonstrated by evaluating the phasors by the Discrete Fourier transform (DFT) approach. Some methods that are being used to overcome this problem, such as prefiltering and/or adaptive delays, are discussed. A new method of estimating the phasors is proposed in this paper. The method is based on the least squares technique and M.S. Sachdev Life Fellow IEEE uses the knowledge of the frequencies in the voltages, provided by the CCVTs, during the transitions between the operating states of power systems. A representative case for a transmission line fault is presented in this paper. The voltages and currents were determined by simulating a power system on the Alternative Transients Program (ATP) software. The results are compared with those obtained by using a least squares technique that does not take into account the transient behavior of the CCVTs. The results show that there are improvements in terms of speed and accuracy when the proposed method is used. II. CCVT RESPONSE A. Modeling Figure 1 shows a detailed model of a CCVT (the modeling considerations are discussed in Reference 1). Figure 1: Detailed model of a CCVT A CCVT is basically a capacitive divider that has two elements in series. Each element has a capacitance, C1 and C2. Because there are losses in the capacitive stack, resistors R1 and R2 are added in the model. The series inductance is modeled by a combination of LLE and RLE. The potential transformer modeled by primary inductance, LPE, and resistance, RPE, secondary inductance, LSE, and resistance, RSE, along with an ideal transformer PT. The magnetizing branch RM and XM is assumed to be linear in this model. This assumption is reasonable for the purpose of this study because the transients of interest are faults which cause voltage drops that are typically within the linear region of the CCVTs [2]. Stray capacitances are not included because its effect is only noticeable at high frequencies [3] that are removed by simple filters. The ferroresonance suppression circuit (FSC) is represented in detail by the inductance LF and RLF, the capacitance CF and RCF and the resistance RF. This type of circuit is called “active” FSC [1, 4] and is the one that introduces bigger distortions in the voltages when a transient is experienced. The burden is represented by the inductance LO, RLO and resistance RO. B. Frequency Response The ideal frequency response of a CCVT is a zero gain and zero angle shifts for all frequencies. The series inductance LLE and capacitors C1 and C2 are typically chosen to obtain this condition at the fundamental frequency. The response for the full range of frequencies depends on the overall design of the CCVT [3]. An analysis of the model shows that some frequencies are amplified; the most significant amplification is of the components of the subharmonic frequencies. Also, the high order frequencies and the DC component are attenuated. Moreover, the phase angle response is non linear. A significant factor that affects the frequency response of the CCVT is the burden [3, 5]. More resistance in the load results in more attenuation of the high frequency components whereas more inductance in the load results in higher amplification of the subharmonic components. The effect of the burden on the phase angle response is not as significant as the effect on the gain response. C. Time Response The CCVT time response shows a decaying transient riding the steady state voltage experienced during a fault. This transient is affected by the incidence angle at which the fault occurs and by the magnitude of the change of voltage. The voltage change is the difference between the non faulted and steady state fault signal at the time of the inception of the fault. To obtain this difference the pre-fault voltage is extrapolated in time and the steady state fault voltage is subtracted from it. A smaller voltage change results in less distortion of the signal. A zero incidence angle results in maximum distortion of the signal from all possible angles [4]; this is shown in Figure 2. Figure 2: CCVT output for a step change in voltage at zero degree phase angle III. IMPACT OF TRANSIENT ON DISTANCE PROTECTION A. Basic Concepts A basic distance relay measures the voltage at the relay location and the current flowing in the protected line. A signal processing technique is used to convert the sampled values of a voltage to fundamental frequency phasor VR, and the sampled values of a current to fundamental frequency phasor IR. From these phasors, the relay compares IRZL (ZL being the reach of the relay) with VR to decide if the fault is in the protected zone of the relay. The errors in the estimates of the magnitude and angle of the phasor affect the operation of the distance function in many situations. These errors cause undesired overreach or underreach as shown in Figure 3. (a) (b) Figure 3: The effects of the errors in the estimates of (a) magnitudes of the phasors and (b) the phase angles of the phasors B. Impact of CCVT Transients The transient response of the CCVT affects the performance of distance protection by producing transient overreach and/or underreach. To illustrate these phenomena, a fault at the remote end of a line is considered and performances of CCVTs and distance functions with and without the transients are evaluated. For comparison, the quality of phasor estimates is considered. The voltage phasor is estimated using the DFT technique [8] that uses a one cycle data window. The impact of the transients in the current is eliminated by using the steady state phasor of the fault current. The voltage at the relay location is a function of the source to line impedance ratio SIR (=ZS/ZL). A higher SIR translates into a larger voltage change at the relay location on the inception of a fault; the voltage at the relay location is lower compared to the voltage experienced if the SIR were smaller. Figure 4 shows the phasors if the voltage waveform were ideal and if the waveform were distorted due to the transient behavior of the CCVT shown in Figure 2. A transient overreach of 16% on the pre-fault scale is observed. This corresponds to 177% (= 16% / 9%) of the line impedance ZL. The risk of false operation of the protection function is, therefore, very high unless appropriate countermeasures are taken. On the other hand the response of an ideal PT converges to the correct value after one cycle, which is the nominal delay of the full cycle DFT technique. An over-defined set of linear equations is put together based on the selected waveform using the measured samples of the voltage v, the time dependent sine and cosine coefficients and the unknown parameters VR and VI. The coefficients are functions of time t-tO (= k∆t, k = 1 … N) and ∆t that is the sampling period. The number of measured samples, N, used in estimating the phasor is also called the data window size, which is sometimes expressed in cycles of the nominal frequency. The set of linear equations can be written as Figure 4:.Estimated voltage phasors at the relay location when SIR is 10 C. Techniques used to Minimize the Impact of CCVT Transients One possible approach is to reduce the relay reach by a percent of the line impedance if the maximum error due to the CCVT transient is known. For applications in which the SIR is small, reduced coverage of the first zone is usually an acceptable approach. However, if the SIR is large, it may be impossible to prevent incorrect operations; the alternative is to disable the zone 1 relays that are set to operate without any intentional time delay. The second approach is to delay the relay operation until the transients caused by the CCVTs subside. A fixed delay is simpler to implement, but the minimum power system clearing times could be exceeded for severe faults [7]. Use of adaptive delays that verify the stability of the phasor estimates after the inception of a fault can help in deciding on the appropriate delay to be used in an application. The third approach is to use special pre-filters [2] that remove the CCVT transient frequencies, before the phasors are estimated. Other techniques, which take advantage of some characteristics of small and large SIR conditions, use a mixture of signal processing techniques with combinational or sequential logic [6, 7]. It is also possible to use the improved least squares technique proposed in Section IV of this paper. IV. IMPROVED LEAST SQUARES TECHNIQUE A. Basic Least Squares Approach This algorithm is based on fitting a set of measurements to a waveform. The best fitting is obtained by minimizing the sum of squares of the differences between the measurements and the waveform. For achieving this objective, the mathematical description of the waveform must be selected upfront [9]. For the estimation of the fundamental frequency phasor, the waveform is assumed to be a time dependent sine function of known frequency ωO, but of an unknown magnitude and phase angle. This waveform is decomposed in two orthogonal sine and cosine functions with unknown amplitudes VR and VI. The difference from the observed signal, say voltage v, and the proposed waveform is assumed to be noise ε. sin(ωO ∆t ) sin(ω 2∆t ) O # sin(ωO N∆t ) cos(ωO ∆t ) v(t O + ∆t ) cos(ωO 2∆t ) VR v(t O + 2∆t ) = VI # # cos(ωO N∆t ) v(t O + N∆t ) (4.1) In the matrix notation, this is [A][x] = [b] (4.2) The vector of unknowns is determined by using the left pseudo-inverse of [A] as follows [x] = [ [A]T [A] ] [A]T [b] −1 (4.3) One of the important advantages of this non-recursive least squares algorithm is that the pre-filtering and phasor estimation are done in one step. B. Improved Least Squares Technique The information concerning the CCVT transfer function and burden can be included in the phasor estimating algorithm if it is available. Considering the example described in Section II (C), the model of the CCVT output can be expressed as a sum of the waveform of the fundamental frequency ωO, a few oscillatory decaying components and a decaying DC component. Including the frequencies ω1 and ω2, and the time constants of the decays, σ1, σ2 and σ3, provides the following equation. v = VR sin( ω O t ) + VI cos(ω O t ) + VR1e (σ 1) t sin( ω1t ) + VI 1e (σ 1) t cos(ω1t ) + VR 2 e (σ 2 ) t sin( ω 2t ) + VI 2 e (σ 2 ) t cos(ω 2t ) (4.4) + V3e (σ 3) t + ε The matrix A is now defined by A = A0 Nx 7 Nx 2 A1 A2 A3 Nx 2 Nx 2 (4.5) Nx1 Where [A0] is identical to the basic least squares matrix [A], and the others are defined by Equations 4.6 to 4.8. The vector of the unknown is defined by Equation 4.9. Once the matrices are defined, finding the unknown requires the calculation of the pseudo-inverse using Equation 4.3. e ∆t ⋅σ 1 sin(ω1 ∆t ) 2 ∆t ⋅σ 1 e sin(ω1 2∆t ) [A1] = # e N∆t ⋅σ 1 sin(ω1 N∆t ) e ∆t ⋅σ 2 sin(ω 2 ∆t ) 2 ∆t ⋅σ 2 sin(ω 2 2∆t ) [A2] = e # e N∆t ⋅σ 2 sin(ω 2 N∆t ) e 2 ∆t ⋅σ 1 cos(ω1 2∆t ) # e N∆t ⋅σ 1 cos(ω1 N∆t ) e ∆t ⋅σ 1 cos(ω1 ∆t ) e cos(ω 2 2∆t ) (4.7) # e N∆t ⋅σ 2 cos(ω 2 N∆t ) e ∆t ⋅σ 2 cos(ω 2 ∆t ) 2 ∆t ⋅σ 2 e ∆t ⋅σ 3 2 ∆t ⋅σ 3 [A3] = e # e N∆t ⋅σ 3 [x ] = [V R VI (4.6) V R1 V I 1 V R 2 VI 2 V3 ] T Figure 7: Estimated angles of the phasors (4.8) The magnitude and angle of the phasors show that they are within a reasonable margin to decide the operation of the relay two cycles after the inception of the fault. Compared to this, the phasors calculated by using the basic least squares technique stabilize four cycles after the inception of the fault. (4.9) V. CONCLUSIONS C. Simulation and Results The technique was tested from simulations of faults on a 500 kV network using the ATP/EMTP software and the proposed technique was used to calculate the phasors. An example is presented in this section. The sampling rate used in this example was 3840 Hz. Figure 5 shows the voltages provided by an ideal PT and the modeled CCVT. The phasors calculated with the proposed algorithms are shown in Figures 6 and 7. This paper has described the significant impact of CCVT transients on the performance of distance relays. The traditional techniques that do not correctly estimate the phasors during the first few cycles after the inception of a fault are likely to operate incorrectly. The knowledge of the CCVT design and the connected burden can be incorporated in the relay algorithm. This improves the correctness of the calculated phasors. A least squares technique that includes this knowledge has been proposed and demonstrated in this paper. The results show significant improvements in both accuracy and speed. REFERENCES [1] [2] [3] Figure 5: Voltages provided by an ideal PT and the CCVT. [4] [5] [6] [7] [8] [9] Figure 6: Estimated magnitudes of the phasor D.A.Tziouvaras et al, “Mathematical Models for Current, Voltage, and Coupling Capacitor Voltage Transformers”, IEEE Trans. on Power Delivery, vol. 15, no. 1, pp. 62-72, Jan. 2000. J.Izykowski, B.Kasztenny, E.Rosolowski, M.M.Saha and B.Hillstrom, “Dynamic Compensation of Capacitive Voltage Transformers”, IEEE Trans. on Power Delivery, vol. 13, no. 1, pp. 116-122, Jan. 1998. M.Kezunovic, C.W.Fromen and S.L.Nilsson, “Digital Models of Coupling Capacitor Voltage Transformers for Protective Relay Transient Studies”, IEEE Trans. on Power Delivery, vol. 7, no. 4, pp. 1927-1935, Oct. 1992. A.Sweetana, “Transient Response Characteristics of Capacitive Potential Devices”, IEEE Trans. on PAS, vol. PAS-90, pp. 1989-2001, Sep./Oct. 1971. M.R.Iravani, X.Wang, I.Polishchuk, J.Ribeiro and A.Sharshar; “Digital Time-Domain Investigation of Transient Behaviour of Coupling Capacitor Voltage Transformer”, IEEE Trans. on Power Delivery, vol. 13, no. 2, pp. 622-629, Apr. 1998. G.E.Alexander, J.G.Andrichak and W.Z. Tyska “Relaying Short Lines”, GER-3735, GE Power Management, General Electric, Feb. 1992. D.Hou and J.Roberts, “Capacitive Voltage Transformer: Transient Overreach Concerns and Solutions for Distance Relaying”, Canadian Conference on Electrical and Computer Engineering, vol. 1, pp. 119125, May 1996. Phadke,A.G. and Thorp, J.S., “Computer Relaying for Power Systems”, Research Studies Press Ltd., Taunton, Somerset, England, 1988. Sachdev, M.S. and Baribeau, M.A., “A New Algorithm for Digital Impedance Relays”, IEEE Trans. on PAS, vol. PAS-98, pp. 2232-2240, Nov./Dec. 1979.