Blokset Tableau BT Low voltage equipment V9 Guide technique V9 V9 Technical guide Get more with the world’s Power & Control specialist* Sommaire du chapitre Chapter contents 1. Informations générales .................................................... 5 General information 2. Jeux de barres ................................................................ 25 Busbars 3. Installation de l’appareillage ......................................... 43 Switchgear Installation 4. Auxiliaires et borniers .................................................. 247 Auxiliaries and terminal blocks 5. Divers ............................................................................ 252 Miscellaneous 6. Annex 01 ....................................................................... 270 Appendix 01 Guide Technique V9 / V9 Technical Guide 2 Sommaire du chapitre Chapter contents 1. Informations générales General information 1.1. Règles de base .................................................................................... 5 Basic rules 1.1.1. La Signature BLOKSET .............................................................................. 5 BLOKSET Signature 1.1.2. Modularité .................................................................................................... 6 Modularity: 1.1.3. Dimensions d'ossature ............................................................................... 7 Framework dimensions 1.1.4. Colonne d’angle .......................................................................................... 8 Angle column 1.1.5. Colonne pour Connexion Dos à Dos ........................................................ 9 Column for Back to Back Connection 1.2. Définition des compartiments .......................................................... 10 Compartment definition 1.2.1. Type D/Mf et Ms ......................................................................................... 10 D, Mf and Ms type 1.2.2. Type Mw ..................................................................................................... 10 Mw type 1.3. Définitions des formes ...................................................................... 11 Form definition 1.3.1. Type D, Mf et Ms ........................................................................................ 11 D, Mf and Ms type 1.3.2. Type Mw ..................................................................................................... 12 Mw type 1.3.3. Principe des IP en fonction des formes sur portes ............................... 13 IP's rules according to shapes on doors 1.4. Dimensions des colonnes ................................................................ 14 Column dimensions 1.5. Poids des colonnes ........................................................................... 15 Column weight Guide Technique V9 / V9 Technical Guide 3 Sommaire du chapitre Chapter contents 1.6. Fixation au sol ................................................................................... 18 Fixing to ground 1.6.1. Profondeur de colonne: 400 mm ............................................................. 18 Column depth: 400 mm 1.6.2. Profondeur de colonne: 600 mm ............................................................. 19 Column depth: 600 mm 1.7. Passage de câble ............................................................................... 20 cable lead-through 1.7.1. 1.7.2. Type D, Mf et Ms ........................................................................................ 20 D, Mf and Ms type 1.7.1.1. Profondeur de colonne: 400 mm ...................................................................... 20 Column depth: 400 mm 1.7.1.2. Profondeur de colonne: 600 mm ...................................................................... 21 Column depth: 600 mm MCC Type Mw ............................................................................................ 22 MCC Mw type 1.7.2.1. Profondeur de colonne: 600 mm ...................................................................... 22 Column depth: 600 mm 1.8. Levages colonnes ............................................................................. 23 Hoisting columns Guide Technique V9 / V9 Technical Guide 4 Informations générales General information 1. Informations générales General information 1.1. Règles de base Basic rules 1.1.1. La Signature BLOKSET BLOKSET Signature 2 1 3 4 1 1 Les quatre caractéristiques ci-dessous sont considérées comme signature BLOKSET. Four characteristics listed below, are considered as BLOKSET signature. 1 - La couleur standard des BANDEAUX est RAL 7016: elle ne doit pas être modifiée. 1 - The standard color of the VENTILATION CROSS MEMBER is RAL 7016: it must not be modified. 2 - Les LOGOS doivent être alignés avec les poignées des portes des unités fonctionnelles. 3 - La couleur standard de l´HABILLAGE est RAL 9002. Cette couleur peut être adaptée à la demand du client. 4 - Lútilisation des serrures de porte décrites dans le dossier de transfert est obligatoire pour 2 raison: – résistent aux essais de tenue à l’arc interne (solution TTA). – sont de la même couleur que les LOGOS, BANDEAUX et POIGNEES. Guide Technique V9 / V9 Technical Guide 2- The LOGOS have to be aligned with the functional units doors handles. 3- The standard color of COVER METAL PARTS is RAL 9002. This colour can be changed under customer request. 4 - The use the door locks described in transfer file is compulsory for 2 reasons: – withstand the internal arc test (TTA solution) – Their colour is the same as LOGOS, VENTILATION CROSS MEMBER and HANDLES. 5 Informations générales General information 1.1.2. Modularité Modularity: Les tableaux Blokset sont conçus sur le principe du module de 50 mm. Les perçage des points de fixation sont au pas de 25 mm. La zone tramée comporte 40 modules de 50 mm. C'est la zone dans laquelle sont installés l'appareillage et les jeux de barres Avec un jeu de barres horizontal simple (I ≤ 4000 A): 4 modules pour le jeu de barres, 36 modules pour l'appareillage. 7 modules pour le jeu de barres (Mw - 3 PH+N en jeu de bar verticale); 33 modules pour l’appareillage (Mw - 3 PH+N en jeu de bar verticale). Avec un double jeu de barres horizontal (I = 5000 / 6300 A): 8 modules pour le jeu de barres, 32 modules pour l'appareillage. 10 modules pour le jeu de barres (seulement Mw); 30 modules pour l'appareillage (seulement Mw). Note: les jeux de barres verticaux seront montés dans les ossatures d'exten- Blokset switchboards are designed on the 50 mm module principle. All fixing holes are drilled at 25 mm distances. The shaded zone consists of 40 50 mm modules. This is the zone where the switchgear and busbars are installed: With a single horizontal busbar (I ≤ 4000 A): 4 modules for the busbar, 36 modules for the switchgear. 7 modules for the busbar (Mw - 3 PH+N in vertical Busbar); 33 modules for the switchgear (Mw - 3 PH+N in vertical Busbar). With a double horizontal busbar (I = 5000 / 6300 A): 8 modules for the busbar, 32 modules for the switchgear. 10 modules for the busbar (only for Mw), 30 modules for the switchgear (only for Mw). Note: vertical busbars are to be mounted in the 200 mm extension frameworks. sion de 200 mm. Guide Technique V9 / V9 Technical Guide 6 Informations générales General information 1.1.3. Dimensions d'ossature Framework dimensions Les ossatures Blokset sont disponibles en 3 largeurs: 700 (profondeur 400 ou 600). 900 (profondeur 600, seulement pour Mw). 1200 pour NW40b, NW50 ou NW63 (profondeur 600). The basic Blokset frameworks are available in 3 widths: 700 (depth 400 or 600). 900 (depth 600, only for Mw). 1200 for NW40b, NW50 or NW63 (depth 600). Les ossatures d'extension de 200 ou 400 (profondeur 400 ou 600) permettent d'obtenir les dimensions suivantes: 900 = 700 + 200. 1100 = 200 + 700 + 200. = 700 + 400. 1300 = 200 + 700 + 400. The 200 or 400 extension frameworks (depth 400 or 600) allow for the following dimensions: 900 = 700 + 200. 1100 = 200 + 700 + 200. = 700 + 400. 1300 = 200 + 700 + 400. La profondeur des tableaux peut être augmentée jusqu'à 1000 mm, en rajoutant un caisson de profondeur 400 mm. Les dimensions des caissons sont les suivantes: 700 x 400 x 2200. 900 x 400 x 2200 (seulement pour Mw). 900 (700+200) x 400 x 2200. 1100 (200+700+200) x 400 x 2200. 1100 (700+400) x 400 x 2200. 1200 x 400 x 2200. 1300 (200+700+400) x 400 x 2200. The depth of the switchgear assembly can be increased up to 1000 mm, by adding a 400 mm deep extension onto a 600 mm deep basic framework. The dimensions of the extensions are as follows: 700 x 400 x 2200. 900 x 400 x 2200 (only for Mw). 900(700+200) x 400 x 2200. 1100(200+700+200) x 400 x 2200. 1100(700+400) x 400 x 2200. 1200 x 400 x 2200. 1300(200+700+400) x 400 x 2200. Tous les Compact sont installés dans l'ossature de largeur 700 mm (extension de 200 mm pour jeu de barres vertical). All Compacts are installed in the 700 mm wide framework (200 mm extension for vertical busbars). Les Masterpact NW08 à NW40 (3 et 4 pôles) installés seuls dans une colonne, sont montés dans l'ossature de largeur 700 mm car ils sont raccordés directement au jeu de barres horizontal. Masterpacts NW08 to NW40 (3 and 4 poles) installed alone in a column are mounted in the 700 mm wide framework, since they are directly connected to the horizontal busbars. Les ossatures de 1200 mm sont réservées à l'installation des Masterpact NW40b/NW50/ NW63 3/4 pôles. The 1200 mm frameworks are only for the Masterpact NW40b/NW50/NW63 3/4 poles installations. Collecteurs de terre: ICC * 30/50 kA -->1b 50 x 5. ICC * 85/100 kA -->2b 50 x 5. Main earth leads: ICC * 30/50 kA —>1b 50 x 5. ICC * 85/100 kA —>2b 50 x 5. Guide Technique V9 / V9 Technical Guide 7 Informations générales General information 1.1.4. Colonne d’angle Angle column An angle column has been developed and applied for following configurations: • connection between 600 mm depth switchboard • single horizontal busbar (up to 4000A) or double horizontal busbar (up to 6300 A), top or botton position. • 85 kA • IP 20, 31, 42 and 54. Une colonne d’angle a eté développée pour les configurations suivantes: • connexions entre tableaux de 600 mm. de profondeur • jeu de barres horizontal simple (jusqu’à 4000A) ou double (jusqu’à 6300A), position supérieur ou inférieur • 85 kA de tenue electrodynamique • IP 20, 31 ,42 et 54. 600 800 600 800 Informations concernant l’assemblage voir Chapitre 2.1 du Guide des plans d’assemblage, ref. “7041xxx.pdf” Information concerning assembly see Chapter 2.1 of Assembly Drawings Guide, ref. “7041xxx.pdf”. 122.5 455 12.2 25 25 Guide Technique V9 / V9 Technical Guide 455 122.5 8 Informations générales General information 1.1.5. Colonne pour Connexion Dos à Dos Column for Back to Back Connection Les solutions dos à dos sont disponibles pour les jeux de barres simples (jusqu’à 4000A) en haut ou en bas de colonne. Degrés de protection disponibles: IP 20 et 31. Option avec Jeu de Barres Vertical standard Option with standard Vertical Busbar Back to back solutions are available for single busbar (up to 4000A) positioned on top or bottom as below figures. Available protection degrees: IP 20 and 31. Option sans Jeu de Barres Vertical Option without Vertical Busbar Option avec Jeu de Barres Vertical arriere Option with rear Vertical Busbar 100 mm 10 modules A 2000 mm 10 modules 10 modules B C 100 mm 200 mm 700 mm 200 mm 400 mm 700 mm 200 mm 700 mm 200 mm Compartiment pour connexion des jeu de barres horizontal Compartment for horizontal busbars connection Pour informations complémentaires voir Guide des Plans d’assemblage “7041xxx.pdf”, Chapitre 2.1. For additional detail see Assembly Drawings Guide “7041xxx.pdf”, Chapter 2.1. 600 600 Fixation au sol (points de fixations disponibles) / Fixing to ground (available fixing points) 12.2 25 125 197.5 455 Guide Technique V9 / V9 Technical Guide 197.5 122.5 400 455 197.5 122.5 455 197.5 9 Informations générales General information 1.2. Définition des compartiments Compartment definition 1.2.1. Type D/Mf et Ms D, Mf and Ms type 400/600 mm 200/400 mm 700 mm 200/400 mm Compartiment Appareillage / Switchgear compartment. Compartiment jeu de barres (largeur 200 mm) ou raccordement càbles (200/400 mm) / Busbar compartment (width 200 mm) or cable connection (200/400 mm). Compartiment raccordement si accés arriére / Connection compartment if there is rear access. Appareil / Circuit breaker. 1.2.2. Type Mw Mw type 600 mm 250/450 mm 700/900 mm Compartiment Appareillage / Switchgear compartment. Compartiment jeu de barres / Busbar compartment. Compartiment raccordement client avant ou arriŁre / Front or rear load side connection compartment. Guide Technique V9 / V9 Technical Guide 10 Informations générales General information 1.3. Définitions des formes Form definition 1.3.1. Type D, Mf et Ms D, Mf and Ms type Forme 1 / Form 1 Forme 2b / Form 2b Forme 3b / Form 3b Forme 4b / Form 4b Forme Form Définition de la norme IEC 60439-1 IEC standard 60439-1 definition Adaptations spécifiques recommandées Specific recommended adjustments 1 Aucune séparation. No separation Protection des parties amont restant sous tension des appareils d'arrivée. Protection of live line side parts of incoming circuit breakers. 2b Séparation des jeux de barres des unités fonctionnelles. Bornes pour conducteurs extérieurs séparées des jeux de barres. Separation of busbars from functional units. External conductor terminals separate from busbars. Connexions entre les jeux de barres et les appareils de protection de l'unité fonctionnelle protégée contre les contacts directs. Connections between busbars and functional unit protection devices protected against direct contacts. 3b Les unités fonctionnelles sont séparées entre elles, séparées des jeux de barres et des bornes. Les bornes sont séparées des jeux de barres mais ne sont pas séparées entre elles. Functional units are separated from each others, separated from the busbars and from terminals. Terminals are separated from busbars but not from each others 4b Séparation des jeux de barres des unités fonctionnelles et séparation de toutes les unités fonctionnelles entre elles, y compris les bornes pour conducteurs extérieurs qui font partie intégrante des unités fonctionnelles. Bornes pour conducteurs extérieurs non dans le même compartiment que l'unité fonctionnelle à laquelle elles sont associées, mais dans les volumes protégés ou des compartiments individuels séparés et fermés. Separation of busbars from functional units and separation of all functional units, including the external conductor terminals which form an integral part of the functional units. External conductor terminals not in the same compartment as the functional unit to which they are connected, but in protected volumes or separate, closed, individual compartments. Guide Technique V9 / V9 Technical Guide 11 Informations générales General information 1.3.2. Type Mw Mw type Tirois débrochable / Drawers Forme 3b /Form 3b Forme 4b / Form 4b Forme Form Définition de la norme IEC 60439-1 IEC Standard 60439-1 definition 3b Les unités fonctionnelles sont séparées entre elles, séparées des jeux de barres et des bornes. Les bornes sont séparées des jeux de barres mais ne sont pas séparées entre elles. Functional units are separated from each others, separated from the busbars and from terminals. Terminals are separated from busbars but not from each others 4b Séparation des jeux de barres des unités fonctionnelles et séparation de toutes les unités fonctionnelles entre elles, y compris les bornes pour conducteurs extérieurs qui font partie intégrante des unités fonctionnelles. Bornes pour conducteurs extérieurs non dans le même compartiment que l’unité fonctionnelle à laquelle elles sont associées, mais dans les volumes protégés ou des compartiments individuels séparés et fermés. Separation of busbars from functional units and separation of all functional units, including the external conductor terminals which form an integral part of the functional units. External conductor terminals must not be in the same compartment as the functional unit to which they are connected, but in protected volumes or separate, closed, individual compartments. Guide Technique V9 / V9 Technical Guide 12 Informations générales General information 1.3.3. Principe des IP en fonction des formes sur portes IP's rules according to shapes on doors IP 31 Formes 1/2b IP 31 Form 1/2b IP 20 Formes 1/2b IP 20 Form 1/2b partie métallique metallic part 51127496 portes doors IP 20, IP 31 Formes 3b/4b IP 20, IP 31 Form 3b/4b séparateur separator IP42, IP54, Formes 1/2b Form 1/2b partie métallique metallic part 51127496 + joint / + gasket IP42, IP54, Formes 3b/4b Form 3b/4b séparateur + joint separator + gasket Guide Technique V9 / V9 Technical Guide 13 Informations générales General information 1.4. Dimensions des colonnes Column dimensions Vue de face / Front view. Vue de c ôté / Side view. 2200 mm X Y Z 600 mm Largeur (mm) Width (mm) X (mm) Y (mm) Z (mm) 700 - 700 - 900 200 700 - - 700 200 - 900 (1) - 200 700 200 400 700 - - 700 400 1200 - 1200 - 1300 200 700 400 400 700 200 1100 (1) seulement pour Mw Guide Technique V9 / V9 Technical Guide 400 mm (1) only for Mw 14 Informations générales General information 1.5. Poids des colonnes Column weight Le poids des colonnes définies ci-dessous s’entend sans l'appareillage. Pour le poids des appareils, voir le Catalogue Distribution Basse Tension. The weight of the columns defined below does not include the switchgear. For the weight of the switchgear, see the Low Voltage Distribution Catalogue. Le poids a été défini pour une colonne contenant: Ossature. Gainage Jeu de barres (forme 2). Tôle inter colonne. Porte arrière. Portes appareillages (1 de 12 modules + 1 de 28 modules). 40 modules réserve. Bandeaux d’habillage. The weight has been defined for a column containing: Framework. Busbar partition (form 2). Inter-column plate. Rear door. Switchgear doors (1 with 12 modules + 1 with 28 modules). 40 reserve modules. Covering strips. Pour les Tableaux suivants: L = Longueur. P = Profondeur. H = Hauteur. E = Epaisseur. For the following switchgear assemblies: L = Length. P = Depth. H = Height. E = Thickness. Poids des colonnes Column weight Dimensions (LxPxH) (mm) Dimensions (LxPxH) (mm) Poids (kg) weight (kg) 700 x 400 x 2200 700 x 600 x 2200 900 x 400 x 2200 900 x 600 x 2200 1200 x 600 x 2200 Guide Technique V9 / V9 Technical Guide 15 Informations générales General information Poids des extensions Extension weight Dimensions (LxPxH) (mm) Dimensions (LxPxH) (mm) Poids (kg) weight (kg) 200 x 400 x 2200 400 x 400 x 2200 200 x 600 x 2200 400 x 600 x 2200 Poids des caissons arrières Rear box weight Dimensions (LxPxH) (mm) Dimensions (LxPxH) (mm) Poids (kg) weight (kg) 700 x 400 x 2200 900 x 400 x 2200 1200 x 400 x 2200 Panneaux latéraux Lateral panels Dimensions (LxPxH) (mm) Dimensions (LxPxH) (mm) Poids (kg) weight (kg) 200 x 2200 400 x 2200 600 x 2200 Toits Covers Dimensions (LxPxH) (mm) Dimensions (LxPxH) (mm) Poids (kg) weight (kg) 200 x 400 200 x 600 400 x 400 400 x 600 700 x 400 700 x 600 900 x 400 900 x 600 1200 x 400 1200 x 600 Adaptation Masterpact Masterpact Fixture Forme Form Poids (kg) weight (Kg) 2 (NW08 au NW40 3/4P) 2 (NW08 to NW40 3/4P) 4 (NW08 au NW40 3/4P) 4 (NW08 to NW40 3/4P) 2 ou 4 (NW40b/NW50/NW63 3/4P) 2 or 4 (NW40b/NW50/NW63 3/4P) Guide Technique V9 / V9 Technical Guide 16 Informations générales General information Adaptation Compact Compact Fixture Nb. Modules Nbr. Modules Forme Form 3 2 4 2 6 2 12 2 3 4 4 4 6 4 12 4 Poids (kg) weight (Kg) Poids des jeux de barres Busbar weight Section de barre (HxE) (mm) Bar cross-section (LxT) (mm) Poids/mètre (kg/m) Weight/meter (kg/m) 63 x 5 2,803 80 x 5 3,650 100 x 5 4,450 125 x 5 5,563 Linergy Guide Technique V9 / V9 Technical Guide 17 Informations générales General information 1.6. Fixation au sol Fixing to ground 1.6.1. 25 122.5 Profondeur de colonne: 400 mm Column depth: 400 mm 455 12.2 350 322.5 25 455 350 125 25 122.5 655 25 350 122.5 400 455 350 322.5 25 455 322.5 25 455 400 350 350 125 Guide Technique V9 / V9 Technical Guide 125 18 Informations générales General information 1.6.2. 25 122.5 Profondeur de colonne: 600 mm Column depth: 600 mm 25 455 455 322.5 12.2 550 25 550 122.5 25 655 550 25 322.5 455 400 550 322.5 455 550 25 322.5 455 400 550 Planéité: Il est recommandé d'avoir un sol de bonne planéité (≤ 2 mm/m). 1000 Guide Technique V9 / V9 Technical Guide Surface eveness: it is recommended to have ground with a good surface eveness (≤ 2mm/m). 2 19 Informations générales General information 1.7. Passage de câble cable lead-through 1.7.1. Type D, Mf et Ms D, Mf and Ms type La zone grisée indique le passage des câbles arrivant par le haut ou par le bas. Utiliser les pièces standards pour une arrivée par le bas. Utiliser les pièces spécifiques pour une arrivée par le haut. Pour information supplémentaire, voir Guide des plans d’assemblage, ref. “7041xxx.pdf”, chapitre 6.5. 1.7.1.1. 50 The indicated area is suitable for cables coming from top or bottom. When cables coming from bottom use standard metal parts. When cables coming from top use specific plates. For additional information, see Assembly drawings guide, ref. “7041xxx.pdf”, Chapter 6.5. Profondeur de colonne: 400 mm Column depth: 400 mm 600 350 75 75 250 250 600 50 50 150 50 75 75 250 250 350 50 75 Zone de passage des câbles / Cable leadthrough zone Guide Technique V9 / V9 Technical Guide 250 20 Informations générales General information 1.7.1.2. 50 Profondeur de colonne: 600 mm Column depth: 600 mm 600 350 75 75 450 450 600 50 50 150 50 75 450 350 50 75 Zone de passage des câbles / Cable leadthrough zone Guide Technique V9 / V9 Technical Guide 450 21 Informations générales General information 1.7.2. MCC Type Mw MCC Mw type La zone grisée indique le passage des câbles arrivant par le haut ou par le bas. Utiliser les pièces standards pour une arrivée par le bas. Utiliser les pièces spécifiques pour une arrivée par le haut. Pour détail supplémentaire, voir Guide des plans d’assemblage, ref. “7041xxx.pdf”, chapitre 6.5. 1.7.2.1. The indicated area is suitable for cables coming from top or bottom. Cables from bottom use standard metal parts. Cables coming from bottom use specific plates. For additional detail, see Assembly drawings guide, ref. “7041xxx.pdf”, Chapter 6.5. Profondeur de colonne: 600 mm Column depth: 600 mm 227 50 427 50 75 75 450 450 Zone de passage des câbles / Cable leadthrough zone Guide Technique V9 / V9 Technical Guide 22 Informations générales General information 1.8. Levages colonnes Hoisting columns Pour le levage d'une colonne, placer les anneaux de levage dans les trous indiqués. 700/900/1200 1100 900/1100 900/1100 1300 Guide Technique V9 / V9 Technical Guide To hoist a column, place the lifting rings in the holes indicated. Anneau de levage / Lifting eye 23 Sommaire du chapitre Chapter contents 2. Jeux de barres Busbars 2.1. Jeu de barres horizontal ................................................................... 25 Horizontal busbar 2.1.1. Jeu de barres horizontal position type D, Mf, Ms et Mw; ...................... 25 Position of Horizontal Busbars for type D, Mf, Ms and Mw. 2.1.2. Intensité admissible dans le barres de cuivres d’un JdB Horizontal .. 27 Admissible current in horizontal copper bars 2.1.3. Distance entre supportsd’un JdB Horizontal ......................................... 29 Distance between supports in Horizontal Busbar 2.1.4. Dimensionnement du neutre ................................................................... 30 Neutral dimensioning 2.1.5. Modularité des portes de jeu de barres horizontal simple ................... 31 Modularity of doors of single horizontal busbars 2.1.6. Modularité des portes de jeu de barres horizontal double ................... 32 Modularity of doors of double horizontal busbars 2.2. Jeu de barres vertical ........................................................................ 33 Vertical busbar 2.2.1. 2.2.2. Jeu de barres rectangulaire ..................................................................... 33 Flat Busbars 2.2.1.1. Jeu de barres vertical, position type D, Mf et Ms ............................................ 33 Position of vertical busbars for type D, Mf and Ms 2.2.1.2. Jeu de barres vertical, position type Mw ......................................................... 34 Position of vertical busbars for type Mw 2.2.1.3. Facteur de diversité ........................................................................................... 34 Diversity factor 2.2.1.4. Intensité admissible dans les barres de cuivre d’un JdB vertical. ................ 35 Admissible current in vertical copper bars 2.2.1.5. Distance entre supports d’un JdB Vertical. ..................................................... 37 Distance between supports in vertical busbar 2.2.1.6. Dimensionnement du neutre ............................................................................. 38 Neutral dimensioning Jeux de barres Linergy ............................................................................. 38 Linergy busbars 2.3. Dimensionnement du PE et PEN ...................................................... 40 Dimensioning of PE and PEN Guide Technique V9 / V9 Technical Guide 24 Jeux de barres Busbars 2. Jeux de barres Busbars 2.1. Jeu de barres horizontal Horizontal busbar 2.1.1. Jeu de barres horizontal position type D, Mf, Ms et Mw; Position of Horizontal Busbars for type D, Mf, Ms and Mw. 300 2100 Pour le jeu de barres horizontal, deux positions standards sont proposées: En haut de l'armoire En bas de l'armoire Guide Technique V9 / V9 Technical Guide For the horizontal busbar, two standard positions are proposed: At the top of the cubicle. At the bottom of the cubicle. 25 Jeux de barres Busbars L'extrémité droite du jeu de barres horizontal est positionnée à 45 mm du bord extérieur du cadre de la cellule, l'extrémité gauche est alignée avec le bord du cadre. The right-hand end side of the horizontal busbar is positioned 45 mm from the outside edge of the column frame, with the left-hand end side lined up with the edge of the frame. Note 1: prévoir les trous de raccordement des éclisses en cas d'extension future. Note 1: provide splice bar connection holes for any future extensions. Note 2: Il existe, pour tous les jeux de barres (sauf JdB vertical Type MW), différents revêtements: Nu. Etamé. Argenté. Isolé. Etamé et isolé. Argenté et isolé. Nickelé Note 2: Different claddings exist for all busbars (except the MW vertical busbar): Plain. Tin-plated. Silver-plated. Insulated. Tin-plated and insulated. Silver-plated and insulated. Nickeled Pour les jeux de barres verticaux du MW nous avons: Nu. Argenté. Vue de face / Front view For the MW vertical busbars, the possible claddings are: Plain. Silver-plated. 45 mm 75/125 mm Vue de dessus / Top view Guide Technique V9 / V9 Technical Guide 26 Jeux de barres Busbars 2.1.2. Intensité admissible dans le barres de cuivres d’un JdB Horizontal Admissible current in horizontal copper bars En fonction de l'intensité, de la température ambiante extérieur et de l'indice de protection du tableau, déterminer le nombre et la section des barres à utiliser par phase. Calculate the number and the cross-section of the bars to be used per phase according to the current, the outside ambient temperature and the degree of protection in the switchboard. Valeurs données pour cuivre NU, époxy et argenté Values data for bare copper, epoxy and silver plated IP ≤ 42 Section /ph Cross-section /ph 1b x 63 x 5 * 2b x 63 x 5 * 1b x 100 x 5 1b x 125 x 5 2b x 100 x 5 2b x 125 x 5 3b x 100 x 5 3b x 125 x 5 4b x 100 x 5 4b x 125 x 5 5b x 100 x 5 5b x 125 x 5 2 x 4b x 100 x 5 2 x 5b x 100 x 5 Température ambiante extérieure (°C) Outside ambient temperature (°C) 35 40 45 50 850 800 750 700 1500 1450 1400 1300 1200 1150 1100 1050 1500 1450 1400 1300 2150 2050 1900 1850 2550 2450 2350 2200 2750 2650 2550 2400 3250 3100 3000 2800 3300 3150 3000 2850 3800 3650 3500 3300 3600 3450 3300 3150 4100 3900 3800 3550 6000 5800 5550 5250 6600 6350 6100 5800 IP 54 Section /ph Cross-section /ph 1b x 63 x 5 * 2b x 63 x 5 * 1b x 100 x 5 1b x 125 x 5 2b x 100 x 5 2b x 125 x 5 3b x 100 x 5 3b x 125 x 5 4b x 100 x 5 4b x 125 x 5 5b x 100 x 5 5b x 125 x 5 2 x 4b x 100 x 5 2 x 5b x 100 x 5 Guide Technique V9 / V9 Technical Guide Température ambiante extérieure (°C) Outside ambient temperature (°C) 35 40 45 50 750 700 650 600 1250 1200 1150 1100 1100 1050 1000 950 1350 1300 1250 1200 1900 1800 1750 1650 2300 2200 2100 2000 2500 2400 2300 2150 2850 2700 2600 2450 3000 2900 2750 2600 3500 3350 3200 3000 3300 3150 3000 2800 3800 3650 3450 3300 5200 5000 4800 4500 5800 5600 5300 5100 27 Jeux de barres Busbars Valeurs données pour cuivre étamé Values data for copper tin IP ≤ 42 Section /ph Cross-section /ph 1b x 63 x 5 * 2b x 63 x 5 * 1b x 100 x 5 1b x 125 x 5 2b x 100 x 5 2b x 125 x 5 3b x 100 x 5 3b x 125 x 5 4b x 100 x 5 4b x 125 x 5 5b x 100 x 5 5b x 125 x 5 2 x 4b x 100 x 5 2 x 5b x 100 x 5 Température ambiante extérieure (°C) Outside ambient temperature (°C) 35 40 45 50 800 750 700 650 1400 1350 1300 1200 1150 1100 1050 1000 1400 1350 1300 1250 2000 1900 1850 1750 2450 2350 2250 2100 2600 2500 2400 2250 3000 2900 2750 2600 3050 2900 2800 2650 3500 3350 3200 3050 3300 3150 3000 2850 3800 3650 3500 3300 5600 5400 5150 4900 6150 5900 5700 5350 IP 54 Section /ph Cross-section /ph 1b x 63 x 5 * 2b x 63 x 5 * 1b x 100 x 5 1b x 125 x 5 2b x 100 x 5 2b x 125 x 5 3b x 100 x 5 3b x 125 x 5 4b x 100 x 5 4b x 125 x 5 5b x 100 x 5 5b x 125 x 5 2 x 4b x 100 x 5 2 x 5b x 100 x 5 *: - Guide Technique V9 / V9 Technical Guide Température ambiante extérieure (°C) Outside ambient temperature (°C) 35 40 45 50 650 600 550 500 1150 1100 1050 1000 1000 950 900 850 1300 1200 1150 1100 1800 1750 1650 1600 2150 2050 2000 1850 2300 2200 2100 2000 2650 2550 2450 2300 2850 2700 2600 2500 3100 3000 2850 2700 2900 2800 2650 2500 3450 3300 3150 3000 4850 4650 4450 4250 5400 5200 5000 4700 Il n’y a pas de rapports d’essais de type pour ces barres. *: - There are no type test reports for these bars. 28 Jeux de barres Busbars 2.1.3. Distance entre supportsd’un JdB Horizontal Distance between supports in Horizontal Busbar Principe fondamentaux Les supports de barres assurent la tenue mécanique du circuit principal, particulèrement au moment d’un courtcircuit. La distance maximale entre les supports est fonction du courant assigné de courte durée admissible, du nombre et de la section des barres ainsi que de leurs entreaxe (75 ou 125mm). Basic principles The bar supports ensure the mechanical resistance of the main circuit, and in particular when a short-circuit occurs. The maximum distance between the supports depends on the rated short-time withstand current, on the number and cross-section of the bars, as well as their centre distances (75 or 125 mm). La règle de la application La distance entre les supports devra être au maximum égale à la valeur mentionnée dans les différents tableaux. Application rule The distance between supports should, at its maximum, be equal to the value quoted in the different tables. Note 1: les supports de calage inférieur ne participent pas à la tenue aux efforts électrodynamiques. Note 1: bottom wedge supports do not contribute to the electrodynamic force resistance. Note 2: les valeurs des distances maximales sont exprimées en mm. Les tableaux ont été établis à partir des certificats de conformité n° FR97.050 et 062-97 délivrés pour le compte de l’ASEFA. Les tableaux sont à utiliser en courant alternatif 50 ou 60 Hz triphasé. Note 2: the maximum distance values are given in mm. The tables were developed from conformity certificates no. FR97.050 and 06297 issued for the ASEFA accounts. The tables are to be used with 50 or 60 Hz three-phase AC current. Tableau pour entre-axe des barres 75 mm (profondeur 400/600) Table for 75 mm bar centre distance (depth 400/600) Section Jeux de barres/ph Busbar cross-section/ph Icc=30kA Isc=30kA Icc=50kA Isc=50kA 1b x 63 x 5 237.5 * interdit / forbidden 2b x 63 x 5 237.5 * 200 1b x 100 x 5 475 237.5 2b x 100 x 5 475 237.5 2b x 125 x 5 475 237.5 Type de supports Type of supports fixe fixed fixe + volant fixed + movable *: pour ces configurations utilisez supports fixe + volant *: for these configurations use supports fix + movable Tableau pour entre-axe des barres 125 mm (profondeur 600 mm) Table for 125 mm bar centre distance (depth 600 mm) Section Jeux de barres/ph Busbar cross-section/ph Icc=50kA Isc=50kA Icc=85kA Isc=85kA 1b x 100 x 5 475 interdit forbidden 1b x 125 x 5 475 interdit forbidden 2b x 100 x 5 475 237.5 2b x 125 x 5 475 237.5 3b x 100 x 5 475 237.5 Guide Technique V9 / V9 Technical Guide 29 Jeux de barres Busbars Tableau pour entre-axe des barres 125 mm (profondeur 600 mm) Table for 125 mm bar centre distance (depth 600 mm) Section Jeux de barres/ph Busbar cross-section/ph Icc=50kA Isc=50kA Icc=85kA Isc=85kA 3b x 125 x 5 475 237.5 4b x 100 x 5 475 237.5 4b x 125 x 5 475 237.5 5b x 100 x 5 475 237.5 5b x 125 x 5 475 237.5 Type de supports Type of supports fixe fixed fixe + volant fixed + movable Tableau pour double jeu de barres (profondeur 600 mm) Table for double busbars (depth 600 mm) Section Jeux de barres/ph Busbar cross-section/ph Icc=100kA Isc=100kA 1 x 4b x 100 x 5 237.5 1 x 4b x 100 x 5 237.5 1 x 5b x 100 x 5 237.5 1 x 5b x 105 x 5 237.5 Type de supports Type of supports fixe + volant fixed + movable 2.1.4. Dimensionnement du neutre Neutral dimensioning Si rien n'est précisé sur le cahier des charges, le choix de la section du neutre est réalisé en fonction des caractéristiques suivantes: Le neutre doit pouvoir véhiculer la même intensité nominale que le jeu de barres auquel il est associé. Le neutre doit pouvoir tenir à une contrainte thermique correspondant à 60% de l' Icc du jeu de barres. Guide Technique V9 / V9 Technical Guide If nothing is specified in the specification, the choice of neutral cross-section is made according to the following characteristics: The neutral must be able to transmit the same nominal current as the busbar to which it is connected. The neutral must be able to withstand a thermal stress which corresponds to 60% of the busbar Isc 30 Jeux de barres Busbars 2.1.5. Modularité des portes de jeu de barres horizontal simple Modularity of doors of single horizontal busbars 3 différentes modularités de porte sont à utiliser suivant les configurations des JdB: 3 different modularity of doors have to be used depending on busbars configuration: Solution 1: 4M, pour le type D, Mf et Ms avec JdB horizontal et vertical 3Ph ou 3Ph+N et pour le type Mw avec JdB horizontal 3Ph ou 3Ph+N et avec JdB vertical 3Ph. Solution 1: 4M, for type D, Mf and Ms with 3Ph or 3Ph+N (horizontal and vertical busbar) or type Mw with 3Ph or 3Ph+N on horizontal busbars and 3Ph in vertical busbar. Solution 2: 6M, pour le type D en 3Ph ou 3Ph+N avec JdB vertical arrière. Solution 2: 6M, for type D with 3Ph or 3Ph+N with rear vertical busbar.. Solution 3: 7M, pour le type Mw avec JdB horizontal et vertical 3Ph+N. Solution 3: 7M, for type Mw with 3Ph+N on horizontal and vertical busbar. Modularité des portes de jeu de Barres horizontal Horizontal busbars door modularity SOLUTION 1 SOLUTION 1 SOLUTION 2 SOLUTION 2 SOLUTION 3 SOLUTION 3 4M 6M FACE AVANT FRONT VIEW FACE AVANT FRONT VIEW 7M FACE LATERALE SIDE VIEW FACE AVANT FRONT VIEW FACE LATERALE SIDE VIEW 7M 6M 4M FACE AVANT FRONT VIEW Guide Technique V9 / V9 Technical Guide FACE AVANT FRONT VIEW FACE LATERALE SIDE VIEW FACE AVANT FRONT VIEW FACE LATERALE SIDE VIEW 31 Jeux de barres Busbars 2.1.6. Modularité des portes de jeu de barres horizontal double Modularity of doors of double horizontal busbars 2 différentes modularité de portes sont à utiliser suivant la configuration du JdB horizontal en haut de colonne, et 1 seule solution en cas de JdB horizontal en bas. Solution 4: 8M, pour le type D, Mf et Ms avec JdB horizontal 3Ph ou 3Ph+N. Solution 5: 10M, pour le type Mw avec JdB horizontal 3Ph ou 3Ph+N et JdB vertical 3Ph. Pour les colomnes avec NW40b/50/63 voir item 3.1.2.7.. 2 different modularity of door have to be used depending on horizontal busbar configuration on the top and only one solution when horizontal busbars is installed on the botton. Solution 4: 8M, for type D, Mf and Ms with 3Ph or 3Ph+N on horizontal busbars. Solution 5: 10M, for type Mw with 3Ph or 3Ph+N on horizontal busbars and 3Ph on vertical busbars. For columns with NW40b/50/63, see item 3.1.2.7.. Modularité de porte de jeu de Barres horizontal Horizontal busbars modularity door SOLUTION 4 SOLUTION 4 SOLUTION 5 SOLUTION 5 8M 10M FACE AVANT FRONT VIEW FACE AVANT FRONT VIEW 8M FACE AVANT FRONT VIEW Guide Technique V9 / V9 Technical Guide 32 Jeux de barres Busbars 2.2. Jeu de barres vertical Vertical busbar 2.2.1. Jeu de barres rectangulaire Flat Busbars 2.2.1.1. Jeu de barres vertical, position type D, Mf et Ms Position of vertical busbars for type D, Mf and Ms a. Les supports des jeux de barres verticaux sont fixés à l'intérieur du cadre de l'armoire dans une ossature d'extension. a. The vertical busbar supports are mounted in the interior of the column frame in an extension framework 75/125 mm T 3 S 2 appareillage switchgear R 1 N 200 mm . 700 mm b. Les jeux de barres verticaux peuvent être montés dans la partie postérieur de la colonne. L’intensité maximale est 1600A (avec jeux de barres standard). Pas disponible pour Ms. L’intensite maximale d’Icc est 50 kA. Profondeur 400 et 600. Forme 1 et 2 pour 600. Forme 1 pour 400. b. Vertical busbar can be assembly rear of column. Maximum IN= 1600 A (with standard busbar). It’s not available for Ms. Maximum Icc: 50 KA. Depth 400 and 600. Form 1 and 2 to 600. Form 1 to 400. 75 mm N R/1 S/2 T/3 appareillage switchgear 700 mm Guide Technique V9 / V9 Technical Guide 33 Jeux de barres Busbars 2.2.1.2. Jeu de barres vertical, position type Mw Position of vertical busbars for type Mw Le Jeu de barres vertical est fixé derrière les tiroirs. The vertical busbar is fixed behind the drawers. appareillage switchgear 450 mm 2.2.1.3. 250 mm Facteur de diversité Diversity factor Jeux de barres verticaux: les sections de barres pour les jeux de barres verticaux sont déterminées en fonction de l' In à distribuer. Pour trouver l' In max. d'un jeu de barres vertical, appliquer le règle générale suivante: Vertical busbars: the bar cross-sections for vertical busbars are determined according to the In which is to be distributed. In order to find the maximum In of a vertical busbar, apply the following general rule. Faire la somme des In déclassées de tous les appareils raccordés au même jeu de barres vertical, la multiplier par le facteur de diversité (recommandation IEC 60439.1) ci-dessous: Add up the derated In of all circuit breakers linked to the same vertical busbar, multiply by the diversity factor (IEC 60439.1 recommendation) below: nombre d'appareils connecté au jeu de barres vertical number of circuit breakers on vertical busbar 2 et 3 2 and 3 4 et 5 4 and 5 6à9 6 and 9 10 et plus 10 and more Avec l'In ainsi obtenue se reporter aux tableaux des intensités admissibles dans les barres pour trouver la section. Guide Technique V9 / V9 Technical Guide facteur de diversité diversity factor 0.9 0.8 0.7 0.6 With the In thus obtained refer to the tables with the admissible currents in the bars to find the cross-section. 34 Jeux de barres Busbars 2.2.1.4. Intensité admissible dans les barres de cuivre d’un JdB vertical. Admissible current in vertical copper bars En fonction de l'intensité, de la température ambiante extérieur et de l'indice de protection du tableau, déterminer le nombre et la section des barres à utiliser par phase. CaLCulate the number and cross-section of the bars to be used per phase, according to the current, the outside ambient temperature and the switchboard’s degree of protection. Valeurs données pour barre de cuivre nu, époxy ou argenté Values data for bare copper, epoxy and silver plated IP ≤ 42 Type D, Mf et Ms D, Mf and Ms type Section /ph Cross-section /ph Température ambiante extérieure (°C) Outside ambient temperature (°C) 35 40 45 50 1b x 63 x 5 * 850 800 750 700 2b x 63 x 5 * 1500 1450 1400 1300 1b x 80 x 5 1100 1050 1000 950 2b x 80 x 5 1800 1750 1650 1550 3b x 80 x 5 2350 2250 2150 2050 4b x 80 x 5 2800 2700 2550 2400 5b x 80 x 5 3250 3100 3000 2800 Type Mw Mw type Section /ph Cross-section /ph 1b x 80 x 6 Température ambiante extérieure (°C) Outside ambient temperature (°C) 35 40 45 50 1050 1000 950 900 IP 54 Type D, Mf et Ms D, Mf and Ms type Section /ph Cross-section /ph Température ambiante extérieure (°C) Outside ambient temperature (°C) 35 40 45 50 1b x 63 x 5 * 750 700 650 600 2b x 63 x 5 * 1250 1200 1150 1100 1b x 80 x 5 950 900 850 800 2b x 80 x 5 1600 1550 1500 1350 3b x 80 x 5 2150 2050 1950 1850 4b x 80 x 5 2550 2450 2350 2200 5b x 80 x 5 2950 2850 2700 2550 Guide Technique V9 / V9 Technical Guide 35 Jeux de barres Busbars Type Mw Mw type Section /ph Cross-section /ph 1b x 80 x 6 Température ambiante extérieure (°C) Outside ambient temperature (°C) 35 40 45 50 800 770 730 690 Valeurs données pour cuivre étamé (Seulement pour D, Mf et Ms) Values data for tinned copper (Only for D, Mf and Ms) IP ≤ 42 Section /ph Cross-section /ph Température ambiante extérieure (°C) Outside ambient temperature (°C) 35 40 45 50 1b x 63 x 5 * 800 750 700 650 2b x 63 x 5 * 1400 1350 1300 1200 1b x 80 x 5 1050 1000 950 900 2b x 80 x 5 1700 1600 1550 1450 3b x 80 x 5 2250 2150 2050 1950 4b x 80 x 5 2600 2500 2400 2300 5b x 80 x 5 3050 2900 2800 2650 IP 54 Section /ph Cross-section /ph Température ambiante extérieure (°C) Outside ambient temperature (°C) 35 40 45 50 1b x 63 x 5 * 650 600 550 500 2b x 63 x 5 * 1150 1100 1050 1000 1b x 80 x 5 900 850 800 750 2b x 80 x 5 1500 1450 1400 1300 3b x 80 x 5 2000 1900 1800 1700 4b x 80 x 5 2350 2250 2200 2050 5b x 80 x 5 2700 2600 2500 2350 *: - Il n’y a pas de rapports d’essais de type pour ces barres. Guide Technique V9 / V9 Technical Guide *: -There are no type test reports for these bars. 36 Jeux de barres Busbars 2.2.1.5. Distance entre supports d’un JdB Vertical. Distance between supports in vertical busbar Principe fondamentaux Les supports de barres assurent la tenue mécanique du circuit principal, particulièrement au moment d'un courtcircuit. La distance maximale entre les supports est fonction du courant assigné de courte durée admissible, du nombre et de la section des barres ainsi que de leurs entraxe(75 ou 125 mm). Règle d'application La distance entre les supports devra être au maximum égale à la valeur mentionnée dans les différents tableaux. Basic principles The bar supports ensure the mechanical resistance of the main circuit, and in particular when a short-circuit occurs. The maximum distance between the supports depends on the rated short-time withstand current, on the number and cross-section of the bars, as well as their centre distances (75 or 125 mm). Application rule The distance between supports should, at its maximum, be equal to the value quoted in the different tables. Note 1: les supports de calage inférieur ne participent pas à la tenue aux efforts électrodynamiques. Note 1: bottom wedge supports do not contribute to the electrodynamic force resistance. Note 2: les valeurs des distances maximales sont exprimées en mm. Les tableaux ont été établis à partir des certificats de conformité n° FR97.050 et 062-97 délivrés pour le compte de l’ASEFA. Les tableaux sont à utiliser en courant alternatif 50 ou 60 Hz triphasé. Note 2: the maximum distance values are given in mm. The tables were developed from conformity certificates no. FR97.050 and 06297 issued for the ASEFA accounts. The tables are to be used with 50 or 60 Hz three-phase AC current. Tableau pour entre-axe des barres 75 mm (profondeur 400/600) Table for 75 mm bar centre distances (depth 400/600) Section Jeux de barres/ph Busbar cross-section/ph Icc=30kA Isc=30kA Icc=50kA Isc=50kA 1b x 63 x 5 237.5 * interdit / forbidden 2b x 63 x 5 237.5 * 200 1b x 80 x 5 475 237.5 2b x 80 x 5 475 237.5 Type de supports Type of supports fixe fixed fixe + volant fixed + movable *: pour ces configurations utilisez supports fixe + volant Voir plan 51128225 *: for these configurations use supports fix + movable See drawing n° 51128225 Tableau pour entre-axe des barres 125 mm (profondeur 600) Table for 125 mm bar centre distances (depth 600) Section Jeux de barres/ph Busbar cross-section/ph Icc=50kA Isc=50kA Icc=85kA Isc=85kA 1b x 80 x 5 500 interdit / forbidden 2b x 80 x 5 500 250 3b x 80 x 5 500 250 4b x 80 x 5 500 250 5b x 80 x 5 500 250 Type de supports Type of supports fixe fixed fixe + volant fixed + movable Voir plan 51127307 Guide Technique V9 / V9 Technical Guide See drawing n° 51127307 37 Jeux de barres Busbars 2.2.1.6. Dimensionnement du neutre Neutral dimensioning Si rien n'est précisé sur le cahier des charges, le choix de la section du neutre est réalisé en fonction des caractéristiques suivantes: Le neutre doit pouvoir véhiculer la même intensité nominale que le jeu de barres auquel il est associé. Le neutre doit pouvoir tenir à une contrainte thermique correspondant à 60% de l' Icc du jeu de barres. 2.2.2. If nothing is specified in the specification, the choice of neutral cross-section is made according to the following characteristics: The neutral must be able to transmit the same nominal current as the busbar to which it is connected. The neutral must be able to withstand a thermal stress which corresponds to 60% of the busbar Isc. Jeux de barres Linergy Linergy busbars 260,5 mm 135,5 mm 50 kA 85 kA voir plan de montage dans “guide de montage” Longueur jeux de barres horizontal voir plans des barres et Guide des Plans d’assemblage, ref. ” 7041xxx.pdf see the assembly drawing in the “assembly guide”. Length of horizontal busbars see the busbar drawings and the Assembly Drawings Guide, ref: “7041xxx.pdf”. Intensité admissible Information Pour ces Jeux de barres, un seul calibre est utilisé: 1600 A. Ces Jeux de barres permettent le raccordement des départs à n'importe quelle hauteur et offre un accès direct par l'avant du tableau à tous les points de raccordement. Admissible current Information: For these busbars, one single rating is used: 1600 A. These busbars enable the outgoing cables to be connected at any height and provide direct access from the front of the switchboard to all connection points. Règle d'application La distance entre les supports devra être au maximum égale à la valeur mentionnée dans les différent tableaux. Application rule The distance between supports should, at its maximum, be equal to the value quoted in the different tables. Note: les valeurs de la distance maximales sont données dans mm. Les tables ont été développées de certificats de la conformité non. FR97.062 et 065-97 ont publié pour les comptes ASEFA. Les tables seront utilisées avec 50 ou 60 trois-phase du Hz courant AC. Note: the maximum distance values are given in mm. The tables were developed from conformity certificates no. FR97.062 and 065-97 issued for the ASEFA accounts. The tables are to be used with 50 or 60 Hz three-phase AC current. Guide Technique V9 / V9 Technical Guide 38 Jeux de barres Busbars Intensité admissible Admissible current Ref. LINERGY Intensité Current IP ≤ 42 IP 54 35 40 45 50 35 40 45 50 7365 1600 1600 1530 1470 1350 1450 1390 1330 1225 Nombre de supports Number of supports Ref. LINERGY Intensité Current Icc = 30 kA Isc = 30 kA Icc = 50 kA Isc = 50 kA Icc = 85 kA Isc = 85 kA 7365 1600 3 3 6 Distance entre supports Distance between supports Distance entre supports Distance between supports Icc = 30 kA Isc = 30 kA Icc = 50 kA Isc = 50 kA Icc = 85 kA Isc = 85 kA mm 550 550 275 Guide Technique V9 / V9 Technical Guide 39 Jeux de barres Busbars 2.3. Dimensionnement du PE et PEN Dimensioning of PE and PEN PE: de part sa fonction, le PE n'est parcouru par un courant que lors d'un défaut et pendant la durée d'élimination de ce dernier. Son dimensionnement n'est donc fonction que de la contrainte thermique, c'est à dire lié à la valeur de l'Icc et de la durée de défaut. Lors des essais d'homologation, il est demandé au PE de tenir à un défaut dont l'intensité correspond à 60% de l'Icc du jeu de barres pendant 0.5 s. Actuellement la gamme Blokset étant conçu pour répondre jusqu’à des Icc de 100 kA, le PE doit tenir à 60 kA au maximum. Pour une durée de défaut de 0.5 s Section Cross Section Icc (kA) Isc (kA) 1b 50 x 5 30 / 50 2b 50 x 5 85 / 100 PEN: faisant office de NEUTRE et de PE, son dimensionnement suit les mêmes règles que le neutre car elles sont plus contraignantes. Guide Technique V9 / V9 Technical Guide PE: in view of its function, the current only flows through the PE when a fault occurs and during the time it takes to remove the fault. Its dimensions are therefore only in accordance with the thermal stress, i.e. linked to the lsc value and the duration of the fault. During the approval tests, the PE is required to withstand a fault with a current which corresponds to 60% of the busbar lsc for 0.5 s. The Blokset range is currently designed to respond to lsc of 100 kA, with the PE capable of withstanding a maximum of 60 kA. For a fault duration of 0.5 s PEN: which serves as Neutral and PE, is dimensioned according to the rules for the neutral since they are more restrictive. 40 Sommaire du chapitre Chapter contents 3. Installation de l’appareillage Switchgear Installation 3.1. Disjoncteurs et interrupteurs Circuit breakers and switches 3.1.1. 3.1.2. Déclassement des appareils .................................................................... 43 Circuit breaker derating 3.1.1.1. Coefficient de déclassement ....................................................... 43 Derating coefficient 3.1.1.2. Compact NB - EasyPact .............................................................. 45 3.1.1.3. Compact NS .................................................................................. 46 3.1.1.3.a. Compact NS100 à NS630 3/4P ....................................................... 46 Compact NS100 to NS630 3/4P 3.1.1.3.b. Compact NS630b à NS3200 3/4P ................................................... 47 Compact NS630b to NS3200 3/4P 3.1.1.4. Compact C .................................................................................... 48 3.1.1.5. Compact CM ................................................................................. 49 3.1.1.6. Masterpact .................................................................................... 50 3.1.1.6.a. Masterpact NT06 à NT16 3/4P ........................................................ 50 Masterpact NT06 to NT16 3/4P 3.1.1.6.b. Masterpact NW08 à NW25 3/4P ..................................................... 51 Masterpact NW08 to NW25 3/4P 3.1.1.6.c. Masterpact NW32 et NW40 3/4P .................................................... 52 Masterpact NW32 and NW40 3/4P 3.1.1.6.d. Masterpact NW40b, NW50 et NW63 3/4P (Profundeur 600 mm).. 53 Masterpact NW40b, NW50 and NW63 3/4P(600 mm depth) 3.1.1.6.e. Masterpact NW40b, NW50 et NW63 3/4P (Profundeur 1000 mm) 54 Masterpact NW40b, NW50 and NW63 3/4P(1000 mm depth Installation ................................................................................................. 55 Installation 3.1.2.1. Multi 9 ............................................................................................ 55 3.1.2.2. Compact NB - EasyPact .............................................................. 56 3.1.2.3. Compact NS .................................................................................. 57 3.1.2.3.a. Compact NS100 à NS630 .............................................................. 57 Compact NS100 to NS630 3.1.2.3.b. Compact NS630b à NS1600 .......................................................... 66 Compact NS630b to NS1600 3.1.2.3.c. Compact NS1600b à NS3200 ......................................................... 74 Compact NS1600b to NS3200 3.1.2.4. Compact C .................................................................................... 75 Guide Technique V9 / V9 Technical Guide 41 Sommaire du chapitre Chapter contents 3.1.2.5. 3.1.2.6. Compact CM ................................................................................. 77 Masterpact .................................................................................... 78 3.1.2.6.a. Masterpact NT06 à NT10 ................................................................ 78 Masterpact NT06 to NT10 3.1.2.6.b. Masterpact NW08 à NW40 .............................................................. 80 Masterpact NW08 to NW40 3.1.2.6.c. Masterpact NW40b à NW63 ............................................................ 84 Masterpact NW40b to NW63 3.1.2.6.d. Choix des transformateurs de courant (TI) .................................. 85 Choice of current transformers (CT) 3.1.2.7. Option raccordement jeu de barres Disjoncteur Compact NS 630b-1600 et Masterpact NT / NW ......................... 86 Option connection busbars Compact NS 630b-1600 and Masterpact NT / NW circuit breaker 3.1.2.8. Option raccordement client Disjoncteur Compact NS 630b-1600 et Masterpact NT / NW ........................ 97 Option incoming bars Compact NS 630b-1600 and Masterpact NT / NW circuit breake 3.1.2.9. Interpact ...................................................................................... 104 3.1.2.10. Inverseur de source ................................................................... 105 Source changeover 3.1.2.10.a. Interpact, Compact NS 100-630, Compact C et Masterpact M (en profondeur 600 mm) ............................................................... 105 Interpact, Compact NS, Compact C et Masterpact M (600 mm depth) 3.1.2.10.b. Compact NS 630b - NS 1600, 3/4P (fixe derrière ou à travers porte, débrochable à travers porte) Masterpact NT 06 à 16, 3/4P (fixe/débrochable).......................... 106 Compact NS 630b - NS 1600, 3/4P (fixed behind or through door, withdrawable behind or though door) Masterpact NT 06 to 16, 3/4P (fixed/withdrawable) 3.1.2.10.c. Compact NS 630b à NS 1600,3/4P débrochable derrière porte . 108 Compact NS 630b to NS 1600,3/4P withdrawable behind door 3.1.2.10.d. Compact NS 630b à NS 1600, 3/4P fixe ou débrochable derrière porte ............................................................................................... 110 Compact NS 630b to NS 1600, 3/4P fixed or withdrawable behind 3.1.2.10.e. Masterpact NW 08 à 25, 3/4P fixe/débro à travers porte ........... 111 Masterpact NW 08 to 25, 3/4P fixed/drawout through door 3.1.2.10.f. Masterpact NW 08 à 20, 3/4P fixe/débro à travers porte ........... 112 Masterpact NW 08 to 20, 3/4P fixed/ drawout through door 3.1.2.10.g. Masterpact NW 32 à 63, 3/4P fixe/débro (RAV/RAR) ................. 113 Masterpact NW 32 to 63, 3/4P fixed/ drawout (Front/Rear access) 3.1.2.11. Couplage et Jeux de Barres de Transfert ............................... 114 Tie Breaker and Transfer Busbar 3.1.2.11.a. Masterpact NW40 et jeu des barres simple ................................ 114 Masterpact NW40 and single busbars 3.1.2.11.b. Masterpact NW40b/50/63 et jeu des barres double ................... 115 Masterpact NW40b/50/63 and double busbars Guide Technique V9 / V9 Technical Guide 42 Installation de l’appareillage Switchgear Installation 3. Installation de l’appareillage Switchgear Installation 3.1. Disjoncteurs et interrupteurs Circuit breakers and switches 3.1.1. 3.1.1.1. Déclassement des appareils Circuit breaker derating Coefficient de déclassement Derating coefficient Les températures à l’intérieur d’un tableau et les éventuels coefficients de déclassement à appliquer pour les appareils sont fonction de la configuration étudiée. Ceci peut-être fait de façon précise par logiciel. Cependant les coefficients d’un appareil donné ont des valeurs semblables pour de nombreuses configurations, en particulier dans le cas d’un tableau contenant: 1 Masterpact + des Compact. The temperatures inside the switchboard and the possible derating coefficients to be applied to the circuit breakers depend on the configuration under study. This can be done with precision using software. However, the coefficients of a given circuit breaker have similar values for numerous configurations, in particular for a switchboard containing: 1 Masterpact + Compacts Nous avons donc défini un tableau type dont l’image thermique illustrant le régime de fonctionnement nous a permis de déterminer le déclassement des appareils les plus contraints. Le Masterpact et le Compact en position haute (cf. tableaux 1, 2, 3, 4, 5). We have defined a standard switchboard. Its thermal overload, which illustrates the operating system, has made it possible to caLCulate the derating for the most restricted circuit breakers. The Masterpact and the Compact are mounted in a high position (see tables 1, 2, 3, 4, 5). Pour les tableaux ne contenant que des Masterpact, les déclassements ne sont pas tributaires de la configuration. Ainsi une liste exhaustive de configurations (les plus fréquentes) a été définie ainsi que le déclassement des appareils en fonction de leurs positions. For switchboards only containing Masterpacts, the derating does not depend on the configuration. Hence, a comprehensive list of configurations (the most frequent) has been drawn up in addition to the circuit breaker derating according to the positions. Les tableaux indiquent les intensités admissibles pour chaque type d’appareil en fonction de la température ambiante extérieure, de l’IP et de sa position dans le tableau. The tables indicate the admissible currents for each type of circuit breaker in accordance with outside ambient temperature, the degree of protection and the position in the switchboard. Influence de l’altitude sur les caractéristiques du disjoncteur (Compact ou Masterpact): The influence of altitude on circuit breaker characteristics (Compact or Masterpact): Guide Technique V9 / V9 Technical Guide 43 Installation de l’appareillage Switchgear Installation La norme de construction IEC 60947-1 (§ 6.1.2) précise que l’altitude du lieu où le disjoncteur doit être installé n’excède pas 2000 m. The IEC 60947-1 standard (§ 6.1.2) specifies that the altitude of the place where the circuit breaker is to be installed should not exceed 2000 m. Il s’ensuit que l’altitude n’a pas d’influence sur les caractéristiques des disjoncteurs jusqu’à 2000 m. It follows that altitude does not influence the circuit breaker characteristics up to 2000 m. Au delà, il faudra déclasser l’appareil en appliquant le coefficient suivant: Altitude 3000 m .............................. coefficient 0,99. Altitude 4000 m .............................. coefficient 0,96. Altitude 5000 m .............................. coefficient 0,94. Above that, the circuit breaker must be derated by applying the following coefficient: Altitude 3000 m .............................. Coefficient 0.99. Altitude 4000 m .............................. Coefficient 0.96. Altitude 5000 m .............................. Coefficient 0.94. Note 1: Les valeurs de déclassement sont données pour IP ≤ 42 et IP 54. Note 1: Derating values are given for IP ≤ 42 and IP 54. Note 2: Dans les pages suivantes, T°amb indique la température ambiante dans le local où est installé le tableau. Note 2: In the following pages, T°amb indicates the ambient temperature in the room where the switchboard is installed. Guide Technique V9 / V9 Technical Guide 44 Installation de l’appareillage Switchgear Installation 3.1.1.2. Compact NB - EasyPact Tableau de déclassement des Compact NB50 à NB600 et EasyPact. Derating table for Compact NB50 to NB600 and EasyPact. Compact NB 200 700 Intensité en A Current in A Tableau 1 Table 1 T°amb (°C) IP 54 IP ≤ 42 35 40 45 50 35 40 45 50 NB225 215 205 200 195 195 190 185 180 NB400 390 380 375 360 350 340 330 320 NB600 530 525 515 495 460 450 440 430 Note: Les disjoncteurs NB50, NB100 et EZD100 (EasyPact) ne sont pas déclassés jusqu’à une température de 50 °C. Pour réalisation des IP, voir les règles dans le Guide des plans d’assemblage 7041xxx.pdf item 6.6. Guide Technique V9 / V9 Technical Guide Note: The circuit breakers NB50, NB100 and EZD100 (EasyPact) are not derated up to a temperature of 50 °C. For carrying out the IP, verify the rules on item 6.6 of Assembly drawings guide 7041xxx.pdf 45 Installation de l’appareillage Switchgear Installation 3.1.1.3. Compact NS Tableau de déclassement des Compact NS. 3.1.1.3.a. Derating table for Compact NS. Compact NS100 à NS630 3/4P Compact NS100 to NS630 3/4P Compact NS 200 700 Intensité en A Current in A Tableau 1 Table 1 T°amb (°C) IP ≤ 42 IP 54 35 40 45 50 35 40 45 50 NS100 100 100 95 95 95 95 90 85 NS160 155 155 150 145 145 140 135 130 NS250 240 230 225 220 215 210 205 200 NS400 390 380 375 360 350 340 330 320 NS630 555 550 540 520 480 470 460 450 Pour réalisation des IP, voir les règles dans le Guide des plans d’assemblage 7041xxx.pdf item 6.6. Guide Technique V9 / V9 Technical Guide For carrying out the IP, verify the rules on item 6.6 of Assembly drawings guide 7041xxx.pdf 46 Installation de l’appareillage Switchgear Installation 3.1.1.3.b. Compact NS630b à NS3200 3/4P Compact NS630b to NS3200 3/4P Compact NS 200 700 Intensité en A Current in A Tableau 1 Table 1 T°amb (°C) IP ≤ 42 IP 54 35 40 45 50 35 40 45 50 NS630b 630 630 630 630 630 630 630 630 NS800 800 800 800 800 800 800 800 800 NS1000 1000 1000 1000 1000 1000 1000 950 950 NS1250 1200 1150 1100 1050 1050 1025 1000 950 NS1600 1350 1325 1300 1250 1200 1150 1125 1100 NS1600b 1600 1550 1500 1450 NS2000 2000 2000 2000 1950 NS2500 2350 2300 2200 2150 NS3200 2720 2650 2550 2450 Pour réalisation des IP, voir les règles dans le Guide des plans d’assemblage 7041xxx.pdf item 6.6. Guide Technique V9 / V9 Technical Guide For carrying out the IP, verify the rules on item 6.6 of Assembly drawings guide 7041xxx.pdf 47 Installation de l’appareillage Switchgear Installation 3.1.1.4. Compact C Tableau de déclassement des Compact C801 à C1251 Derating table for Compact C801 to C1251 Compact C 200 700 Intensité en A Current in A Tableau 1 Table 1 T°amb (°C) IP ≤ 42 IP 54 35 40 45 50 35 40 45 C801 750 710 670 640 670 630 590 C1001N/H 900 850 800 750 810 770 720 C1001L 890 840 790 730 800 760 700 C1251 1125 1060 1000 940 1010 960 900 Pour réalisation des IP, voir les règles dans le Guide des plans d’assemblage 7041xxx.pdf chapitre 6.6. Guide Technique V9 / V9 Technical Guide 50 For carrying out the IP, verify the rules on chapter 6.6 of Assembly drawings guide 7041xxx.pdf. 48 Installation de l’appareillage Switchgear Installation 3.1.1.5. Compact CM Tableau de déclassement des Compact CM1250 à CM3200 Derating table for Compact CM1250 to CM3200 Compact CM Appareillage Devices 200 700 Intensité en A Current in A Tableau 1 Table 1 T°amb (°C) IP ≤ 42 IP 54 35 40 45 CM1250 1250 1150 CM1600 1330 CM2000 50 35 40 45 1050 1000 920 840 1260 1190 1060 1040 950 1660 1550 1440 1330 1240 1150 CM2500 2075 1950 1840 1660 1560 1470 CM3200 2700 2600 2500 2160 2080 2000 Pour réalisation des IP, voir les règles dans le Guide des plans d’assemblage 7041xxx.pdf chapitre 6.6. Guide Technique V9 / V9 Technical Guide 50 For carrying out the IP, verify the rules on chapter 6.6 of Assembly drawings guide 7041xxx.pdf 49 Installation de l’appareillage Switchgear Installation 3.1.1.6. Masterpact Tableau de déclassement des Masterpact 3.1.1.6.a. Derating table of Masterpact Masterpact NT06 à NT16 3/4P Masterpact NT06 to NT16 3/4P Masterpact Appareillage Devices 200 700 Intensité en A Current in A Tableau 1 Table 1 T°amb (°C) IP ≤ 42 IP 54 35 40 45 50 35 40 45 50 NT06 630 630 630 630 630 630 630 630 NT08 800 800 800 800 800 800 800 800 NT10 1000 950 900 900 900 900 850 850 NT12 1250 1250 1200 1150 1150 1100 1050 1000 NT16 1400 1350 1300 1250 1250 1200 1150 1100 Pour réalisation des IP, voir les règles dans le Guide des plans d’assemblage 7041xxx.pdf chapitre 6.6. Guide Technique V9 / V9 Technical Guide For carrying out the IP, verify the rules on chapter 6.6 of Assembly drawings guide 7041xxx.pdf 50 Installation de l’appareillage Switchgear Installation 3.1.1.6.b. Masterpact NW08 à NW25 3/4P Masterpact NW08 to NW25 3/4P Masterpact Appareillage Devices 200 700 Intensité en A Current in A Tableau 1 Table 1 T°amb (°C) IP ≤ 42 IP 54 35 40 45 50 35 40 45 50 NW08 800 800 800 800 800 800 800 800 NW10 1000 1000 1000 1000 1000 1000 1000 1000 NW12 1250 1250 1250 1250 1250 1250 1200 1150 NW16 1550 1500 1450 1400 1400 1350 1300 1250 NW20 2000 2000 2000 1900 1850 1800 1700 1650 NW25 2350 2300 2200 2150 2050 2000 1950 1900 Pour réalisation des IP, voir les règles dans le Guide des plans d’assemblage 7041xxx.pdf chapitre 6.6. Guide Technique V9 / V9 Technical Guide For carrying out the IP, verify the rules on chapter 6.6 of Assembly drawings guide 7041xxx.pdf. 51 Installation de l’appareillage Switchgear Installation 3.1.1.6.c. Masterpact NW32 et NW40 3/4P Masterpact NW32 and NW40 3/4P NW32 / 40 3/4P VIDE EMPTY 700 Intensité en A Current in A Tableau 1 Table 1 T°amb (°C) IP ≤ 42 IP 54 35 40 45 50 35 40 45 NW32 3000 2950 2900 2850 2900 2850 2700 - NW40 3550 3450 3350 3250 3350 3250 3150 - Pour réalisation des IP, voir les règles dans le Guide des plans d’assemblage 7041xxx.pdf chapitre 6.6. Guide Technique V9 / V9 Technical Guide 50 For carrying out the IP, verify the rules on chapter 6.6 of Assembly drawings guide 7041xxx.pdf 52 Installation de l’appareillage Switchgear Installation 3.1.1.6.d. Masterpact NW40b, NW50 et NW63 3/4P (Profundeur 600 mm) Masterpact NW40b, NW50 and NW63 3/4P(600 mm depth) NW40b / NW50 / NW63 3/4P Ventilateurs voir plan 51132529X0 Fan see drawing 51132529X0 VIDE EMPTY 600 1200 Intensité en A Current in A Tableau 1 Table 1 T°amb (°C) IP ≤ 31 Ventilé / Ventilated IP 42 Ventilé / Ventilated 35 40 45 50 35 40 45 50 NW40b 4000 4000 4000 4000 4000 3850 3700 3550 NW50 5000 5000 5000 4900 4800 4600 4300 4000 NW63 5650 5450 5300 5100 5200 5050 4850 4650 T°amb (°C) IP 54 Ventilé / Ventilated 35 40 45 50 NW40b 4000 3850 3700 3550 NW50 4600 4450 4200 3900 NW63 4900 4750 4500 4200 Pour réalisation des IP, voir les règles dans le Guide des plans d’assemblage 7041xxx.pdf chapitre 6.6. Guide Technique V9 / V9 Technical Guide For carrying out the IP, verify the rules on chapter 6.6 of Assembly drawings guide 7041xxx.pdf. 53 Installation de l’appareillage Switchgear Installation 3.1.1.6.e. Masterpact NW40b, NW50 et NW63 3/4P (Profundeur 1000 mm) Masterpact NW40b, NW50 and NW63 3/4P(1000 mm depth) NW40b / NW50 / NW63 3/4P VIDE EMPTY 1000 1200 Intensité en A Current in A Tableau 1 Table 1 T°amb (°C) IP ≤ 31 IP 42 35 40 45 50 35 40 45 50 NW40b 4000 4000 3890 3800 3950 3850 3760 3670 NW50 5000 4940 4800 4670 4860 4760 4650 4540 NW63 5490 5360 5230 5090 5220 5100 4990 4890 35 40 45 50 NW40b 3870 3790 3700 3670 NW50 4780 4680 4580 4470 NW63 5090 4980 4900 4780 T°amb (°C) IP 54 Dans un tableau, il n’est pas nécessaire ventiler cette colonne en IP42. Les colonnes adjacentes devront être ventilées suivant chapitre 6.6 du Guide des plans d’assemblage 7041xxx.pdf, pour réalisation des IP. Guide Technique V9 / V9 Technical Guide In a switchboard this column does not need ventilation in IP42. The adjacent columns must be ventilated according to the chapter 6.6 of Assembly drawings guide 7041xxx.pdf for carrying out the IP. 54 Installation de l’appareillage Switchgear Installation 3.1.2. Installation Installation 3.1.2.1. Multi 9 Choix des platines et types de commande Choice of mounting plates and type of operating mechanism Nb app. Nbr of CBs Position Position Nb modules Nb of modules Forme Form Type de commandes Type of operating mechanism Fixation Fixing jusqu’a 48 modules de 9 mm up to 48 modules of 9 mm V 3 1 A/B/D fixe jusqu’a 48 modules de 9 mm up to 48 modules of 9 mm V 4 (*) 1 A/B/D fixe Type de commande Type of operating mechanism A: derrière porte behind door maneton toggle B: à travers porte through door maneton toggle D: à travers plastron through front plate maneton toggle (*) 4 modules sont nécéssaire si la taille des câbles client est égal ou suppérieur à 10 mm2. Guide Technique V9 / V9 Technical Guide (*) 4 modules are necessary if the customer cable size is equal or bigger than 10 mm2. 55 Installation de l’appareillage Switchgear Installation 3.1.2.2. Compact NB - EasyPact Choix des platines et types de commande Choice of mounting plates and type of operating mechanism Type d’appareils Type of circuit breaker Nb pôles Nbr of poles Nb app. Nbr of CBs Position Position Nb modules Nb of modules Forme Form Type de commandes Type of operating mechanism Fixation Fixing NB50 3 6 V 4 1 A/B/D fixe NB100 3 5 V 6 1 A/B/D fixe EZD100B/F/N/H (1) 3 6 V 6 1 A/B/D fixe NB225 3 4 V 6 1 A/B/D fixe NB400 3 3 V 12 1 A/B/D fixe NB600 3 3 V 12 1 A/B/D fixe Type de commande Type of operating mechanism A: derrière porte behind door maneton toggle B: à travers porte through door maneton toggle D: à travers plastron through front plate maneton toggle (1) (1) Limitè à 415V Accessoires obligatoires pour l’installation des Compact NB 400/600: Séparateur de phases Limited to 415V Compulsory accessories for Compact NB 400/600 installation: Phase barriers Compact NB raccordé au jeu de Barres Vertical à gauche Compact NB connected to the vertical bars on the left Type D & Mf Type D & Mf NB50 / 100 NB225 NB400 / 600 Raccordement Connections AV ou AR Front or Rear possibilités possibilities oui yes Compact NB raccordé au jeu de Barres Vertical à droite Compact NB connected to the vertical bars on the right Type D & Mf Type D & Mf NB50 / 100 NB225 NB400 / 600 Guide Technique V9 / V9 Technical Guide Raccordement Connections AV ou AR Front or Rear AV ou AR Front or Rear possibilités possibilities oui (par câbles) yes (by cables) oui yes 56 Installation de l’appareillage Switchgear Installation 3.1.2.3. Compact NS 3.1.2.3.a. Compact NS100 à NS630 Compact NS100 to NS630 Choix des platines et types de commande Choice of mounting plates and type of operating mechanism Type d’appareils Fixation Type of circuit Fixing breaker NS100/250 NS400/630 NS100/250 NS400/630 NS100/250 NS400/630 Nb pôles Nbr of poles Forme Form Nb app. Nbr of CBs Position Position Type de commande Nb modules Type of operating Nb of modules mechanism fixe / socle fixed/plug-in 3 1/2** 4 V A/B/D 6 (NS 100/160) 6 + 3 (NS 250) fixe / socle fixed/plug-in 4 1/2** 3 V A/B/D 6 (NS 100/160) 6 + 3 (NS 250) fixe fixed 3 1 3 V AB/D 12 fixe fixed 4 1 2 V A/B/D 12 fixe / socle fixed/plug-in 3 1/2/3/4 1 H A/B/C/D 3 fixe / socle fixed/plug-in 4 1/2/3/4 1 H A/B/C/D 4 fixe / socle fixed/plug-in 3 1/2/3/4 **** 2 H A 3 fixe / socle fixed/plug-in 4 1/2/3/4 **** 2 H A 4 fixe / socle fixed/plug-in 3 1/2/3/4 4 H A/B/C/D 12 fixe / socle fixed/plug-in 4 1/2/3/4 3 H A/B/C/D 12 fixe / socle fixed/plug-in 3 1/2/3/4 1 H A***/B/C/D 4 fixe / socle fixed/plug-in 4 1/2/3/4 2 H A***/B/C/D 12 fixe / socle fixed/plug-in 3 1/2/3/4 3 H A***/B/C/D 12 fixe / socle fixed/plug-in 4 1/2/3/4 1 H A***/B/C/D 6 chassis withdrawable 3/4 1/2/3/4 1 V A/E 6 chassis withdrawable 3 1/2/3/4 **** 2 H A 8 chassis withdrawable 4 1/2/3/4 **** 2 H A 10 chassis withdrawable 3/4 1/2/3/4 1 V A ou / or E 8 Guide Technique V9 / V9 Technical Guide 57 Installation de l’appareillage Switchgear Installation ** forme 2 seulement possible avec Polypact *** eléctrique et derriére porte seulement forme 1 **** Forme 4, seulement en profondeur 1000 mm. ** form 2 possible with Polypact only *** motor mechanism and behind door, only form 1 ****Form 4, only in 1000 mm. depth Choix des disjoncteurs avec Polypact Choice of Circuit breakers with Polypact Nb pôles Nbr poles 1er disj. 1st CB 2nd disj. 2nd CB 3eme disj 3rd CB 4eme disj. 4th CB 3 NS100/160 NS100/160 NS100/160 NS100/160 3 NS100 NS100/160 NS100/160 NS250 4 NS100/160 NS100/160 NS100/160 /////////////// 4 NS100 NS100/160 NS250 /////////////// Type de commande Type of operating mechanism A: derrière porte behind door maneton / rotative directe/ électrique toggle / direct rotary handle / motor mechanism B: à travers porte through door maneton / rotative directe / électrique toggle / direct rotary handle / motor mechanism C: derrière porte individuelle behind individual door commande rotative prolongée extended rotary handle D: à travers plastron through front plate maneton toggle E: derrière porte (chassis) behind door (frame) commande rotative prolongée télescopique telescopic extended rotary handle Accessories obligatoires pour l’installation des Compact NS100/160/250: Prise arrière en raccordement arrière sur prise aval. Compulsory accessories for Compact NS100/160/250 installation: Obligatoires pour l’installation des Compact NS400/630: Prise arrière côté amont Prise arrière côté aval. Compulsory with the installation of the Compact NS400/630: Rear connector on line side. Rear connector on load. Guide Technique V9 / V9 Technical Guide Rear connector for rear access on load side connection. 58 Installation de l’appareillage Switchgear Installation Compact NS raccordé au jeu de Barres Vertical à gauche Compact NS connected to the vertical bars on the left Type D & Mf Type D & Mf NS100 / 160 NS250 NS400 / 630 Raccordement Connections AV ou AR Front or Rear AV ou AR Front or Rear AV ou AR Front or Rear possibilités possibilities oui yes oui yes oui yes Compact NS raccordé au jeu de Barres Vertical à droite Compact NS connected to the vertical bars on the right Type D & Mf Type D & Mf NS100 / 160 NS250 NS400 / 630 Guide Technique V9 / V9 Technical Guide Raccordement Connections AV ou AR Front or Rear AV ou AR Front or Rear possibilités possibilities oui (par câbles) yes (by cables) oui (en retournant la platine et la porte) si: - commande maneton et électrique à travers porte - toutes commandes derrière porte - commande rotative direct - commande rotative prolongé Dans tous les cas, il faut développer les barres yes (while returning the turntable and the door) if: - manual and electric command through door - all controls behind door - direct rotary command - prolonged rotary command in any case, it is necessary to develop bars 59 Installation de l’appareillage Switchgear Installation Règles d’installation Compact NS dans BLOKSET Rules Compact NS installation in BLOKSET U < 500V Type D D type Raccordement Connection Type Type NS80 AV câbles cables NS100/160/250 GV7 AV câbles cables NS100/160/250 GV7 AR câbles cables NS400/630 N, H AV barres bars NS400/630 N, H AV barres bars CBL/SP LTS/PB NS400/630 L AV barres bars CBL/SP LTS/PB NS400/630 N, H, L AR barres bars CBC STS accessoire pour protection des personnes accessory needed for people protection Type Mf et Ms Mf and Ms type Raccordement Connection Type Type Accessoires Accessories Mode de raccordement Connection way GV2 Integral AV câbles cables direct dans bornes appareil direct on CB’s NS80 AV câbles cables direct dans bornes appareil direct on CB’s NS100/160/250 GV7 AV câbles cables bornes à cage (câbles 1.5 à 95 mm2) Ref. 29242 ou ** NS400 N, H AR / AV barres/ câbles bars/cables CBC AM SEULEMENT STS ONLY IN Bornes 2 câbles ref. 32481 (barres amont, câbles aval) add cable connectors for 2 cables reference 32481 (bars IN, cables OU) NS630 N, H AR / AV barres/ câbles bars/cables CBC AM SEULEMENT STS ONLY IN barres amont, câbles aval bars incoming, cables outgoing NS400 L AR / AV barres/ câbles bars/cables CBC AM + SP AL STS IN + PB OU Bornes 2 câbles ref. 32481 (barres amont, câbles aval) add cable connectors for 2 cables reference 32481 (bars IN, cables OU) NS630 L AR / AV barres/ câbles bars/cables CBC AM + SP AL STS IN + PB OU barres amont, câbles aval accessory needed for people protection Guide Technique V9 / V9 Technical Guide Accessoires Accessories Mode de raccordement Connection way direct dans bornes appareil direct on CB’s bornes à cage (câbles 1.5 à 95 mm2) Ref. 29242 ou ** add-on bare cable connectors (cables 1.5 to 95 mm2) ref. 29242 or ** CBC STS accessoire pour protection des personnes accessory needed for people protection barres isolées with insulated bars barres nues with bare bars add cable connectors (cables 1.5 à 95 mm2) up to 160 A ref. 29242 or ** 60 Installation de l’appareillage Switchgear Installation Type Mw Mw type Raccordement Connection Type Type Accessoires Accessories Mode de raccordement Connection way GV2 Integral AV câbles cables direct dans bornes appareil direct on CB’s NS80 AV câbles cables direct dans bornes appareil direct on CB’s NS100/160/250 GV7 AV 1 câble 1 cable bornes à cage (câbles 1.5 à 95 mm2) Ref. 29242 ou ** NS250 AV 2 câbles 2 cables NS400 N, H AV câbles cables bornes 2 câbles référence 32481 add cable connectors for 2 cables reference 32481 NS630 N, H AV barres bars raccordement des 3 câbles 50 mm2 (pinces) add cable connectors (cables 1.5 to 95 mm2) up to 160 A ref. 29242 or ** CBL cosses + séparateur de phase lugs bars + connection 3 cables 50 mm2 (plug) NS400 L AV câbles cables CBL/SP LTS/PB bornes 2 câbles référence 32481 (modularité à confirmer) add cable connectors for 2 cables reference 32481 (to confirm the modularity) NS630 L AV barres bars SP PB raccordement des 3 câbles 50 mm2 (pinces) AV = connexion avant du disjoncteur CBC = cache borne court SP = séparateur de phase AL = Aval du disjoncteur AR = connexion arrière du disjoncteur CBL = cache borne long AM = Amont du disjoncteur Guide Technique V9 / V9 Technical Guide bars + connection 3 cables 50 mm2 (plug) AV = front connection on CB STS = short terminal shield PB = phase barrier OU = Outgoing AR = rear connection on CB LTS = long terminal shield IN = Incoming 61 Installation de l’appareillage Switchgear Installation 500V ≤ U ≤ 600V Type D D type Raccordement Connection Type Type NS80 AV câbles cables NS100/160/250 GV7 AV câbles cables CBC/SP STS/PB NS100/160/250 GV7 AR câbles cables CBC STS accessoire pour protection des personnes accessory needed for people protection NS400/630 N, H AV barres bars CBL/SP LTS/PB barres nues ou isolées bar or insulated bars NS400/630 L AV barres bars CBL/SP LTS/PB barres nues ou isolées bar or insulated bars NS400/630 N, H, L AR barres bars CBC STS accessoire pour protection des personnes accessory needed for people protection Type Mf et Ms Mf and Ms type Raccordement Connection Type Type Accessoires Accessories Mode de raccordement Connection way GV2/Integral AV câbles cables direct dans bornes appareil direct on CB’s NS80 AV câbles cables direct dans bornes appareil direct on CB’s NS100/160/250 GV7 AV câbles cables CBC STS NS400 N, H AR / AV barres/ câbles bars/cables CBC AM SEULEMENT STS ONLY IN Bornes 2 câbles ref. 32481 (barres amont, câbles aval) add cable connectors for 2 cables reference 32481 (bars IN, cables OU) NS630 N, H AR / AV barres/ câbles bars/cables CBC AM SEULEMENT STS ONLY IN barres amont, câbles aval bars incoming, cables outgoing NS400 L AR / AV barres/ câbles bars/cables CBC AM + SP AL STS IN + PB OU Bornes 2 câbles ref. 32481 (barres amont, câbles aval) add cable connectors for 2 cables reference 32481 (bars IN, cables OU) NS630 L AR / AV barres/ câbles bars/cables CBC AM + SP AL STS IN + PB OU barres amont, câbles aval bars incoming, cables outgoing Guide Technique V9 / V9 Technical Guide Accessoires Accessories Mode de raccordement Connection way direct dans bornes appareil direct on CB’s bornes à cage (câbles 1.5 à 95 mm2) Ref. 29242 ou ** add-on bar cable connectors (cables 1.5 to 95 mm2) up to 160 A ref. 29242 or ** bornes à cage (câbles 1.5 à 95 mm2) Ref. 29242 ou ** add cable connectors (cables 1.5 to 95 mm2) ref. 29242 or ** 62 Installation de l’appareillage Switchgear Installation Type Mw Mw type Raccordement Connection Type Type Accessoires Accessories Mode de raccordement Connection way GV2/Integral AV câbles cables direct dans bornes appareil direct on CB’s NS80 AV câbles cables direct dans bornes appareil direct on CB’s NS100/160/250 GV7 AV 1 câble 1 cable CBC STS NS250 AV 2 câbles 2 cables CBL LTS cosses + séparateur de phase lugs NS400 N, H AV câbles cables CBL/SP LTS/PB bornes 2 câbles référence 32481 (modularité à confirmer) add cable connectors for 2 cables reference 32481 (to confirm the modularity) NS630 N, H AV barres bars SP PB raccordement des 3 câbles 50 mm2 (pinces) bornes à cage (câbles 1.5 à 95 mm2) Ref. 29242 ou ** add cable connectors (cables 1.5 to 95 mm2) ref. 29242 up to 160 A or ** insulating bars + connection 3 cables 50 mm2 (plug) NS400 L AV câbles cables CBL/SP LTS/PB bornes 2 câbles référence 32481 (modularité à confirmer) add cable connectors for 2 cables reference 32481 (to confirm the modularity) NS630 L AV barres bars SP PB raccordement des 3 câbles 50 mm2 (pinces) AV = connexion avant du disjoncteur CBC = cache borne court SP = séparateur de phase AL = Aval du disjoncteur AR = connexion arrière du disjoncteur CBL = cache borne long AM = Amont du disjoncteur Guide Technique V9 / V9 Technical Guide insulating bars + connection 3 cables 50 mm2 (plug) AV: front connection on CB STS = short terminal shield PB = phase barrierOU = Outgoing AR: rear connection on CB LTS = long terminal shield IN = Incoming 63 Installation de l’appareillage Switchgear Installation U > 600V Type D D type Raccordement Connection Type Type Accessoires Accessories Mode de raccordement Connection way NS80 AV câbles cables CBL LTS direct dans bornes appareil direct on CB’s NS100/160/250 GV7 AR câbles cables CBC STS NS100/160/250 GV7 AV câbles cables kit kit NS400/630 AR barres bars CBC STS NS400/630 AV barres bars kit kit kit d’isolement renforcé* reinforced insulating kit * Type Mf et Ms Mf and Ms type Raccordement Connection Type Type Accessoires Accessories Mode de raccordement Connection way GV2 Integral AV câbles cables NS80 AV câbles cables CBL LTS direct dans bornes appareil (modularité à confirmer) direct on CB’s (to confirm the modularity) NS100/160/250 GV7 AV câbles cables kit kit étude à commission, vérifier la modularité special studied, to confirm the modularity NS400/630 N, H, L AR / AV barres/ câbles bars/cables CBC AM + kit AL STS IN + kit OU kit d’isolation renforcé* barres amont, câbles aval (modularité à confirmer) Bars IN, cables OU (to confirm the modularity) Guide Technique V9 / V9 Technical Guide kit d’isolement renforcé* reinforced insulating kit * direct dans bornes appareil direct on CB’s 64 Installation de l’appareillage Switchgear Installation Type Mw Mw type Raccordement Connection Type Type Accessoires Accessories Mode de raccordement Connection way GV2 Integral AV câbles cables NS80 AV câbles cables CBL LTS direct dans bornes appareil direct on CB’s NS100/160/250 GV7 AV 1 câble 1 cable kit kit bornes à cages (câbles 1.5 à 95 mm2) Ref. 29242 ou ** + kit d’isolement renforcé* (modularité à confirmer) direct dans bornes appareil direct on CB’s add cable connectors (cables 1.5 to 95 mm2) up to 160 A ref. 29242 or ** + reinforced insulating kit * (to confirm the modularity) NS250 AV 2 câbles 2 cables kit kit câbles avec cosses + kit d’isolement renforcé (modularité à confirmer) same for 1 cable + lugs (to confirm modularity) NS400 AV câbles cables kit kit bornes à cages pour 2 câbles Ref. 32481 + kit d’isolement renforcé * (modularité à confirmer) add cable connectors for 2 cables ref. 32481 + reinforced insulating kit * (to confirm the modularity) NS630 AV barres bars kit kit raccordement 3 câbles 50 mm2 (pinces) + kit d’isolement renforcé* (modularité à confirmer) bars + connection 3 cables 50 mm2 (plug) + reinforced insulating kit * (to confirm the modularity) AV = connexion avant du disjoncteur CBC = cache borne court AR = connexion arrière du disjoncteur CBL = cache borne long AM = Amont du disjoncteur AL = Aval du disjoncteur AV = front connection on CB STS = short terminal shield AR = rear connection on CB LTS = long terminal shield IN = Incoming connection on CB OU = Outgoing connection on CB * kit d’isolement NS100/250 tri 29326 tetra 29327 * reinforced insulating kit NS100/250 3 phases 29326 4 phases 29327 NS400/630 32580 32581 NS400/630 32580 32581 * * pour les courants plus de 160 A jusqu'à 250 A, utiliser le ref. 29259 avec câbles jusqu'à 185 mm2. ** for currents over 160 A up to 250 A, use ref. 29259 with cables up to 185 mm2. Voir plans: 51130483 / 51130484 / 51130485 / 51130486 See drawings: 51130483 / 51130484 / 51130485 / 51130486 Guide Technique V9 / V9 Technical Guide 65 Installation de l’appareillage Switchgear Installation 3.1.2.3.b. 3.1.2.3.b.1. Compact NS630b à NS1600 Compact NS630b to NS1600 Fixe Arrivée par le BAS/HAUT (à travers portes) Commande rotative directe / commande maneton / commande électrique. Forme 1 à 4 Fixed Incoming from the TOP/BOTTON (through door) Direct rotary handle / toggle / motor mechanism. Form 1 to 4 Disjoncteur Option Raccordement client Client connection Taille en Modules Number of Modules Circuit Breaker Option AR Rear AR Rear AV Front AR Rear AR Rear AR Rear AV Front AR Rear AV Front AR Rear AV Front AR Rear AV Front AR Rear AV/AR Front/Rear AV/AR Front/Rear AV Front AR Rear AV/AR Front/Rear AV Front 9 (F1, 2, 3) 3 + 9 (F4) (1) 9 (F1, 2, 3) 3 + 9 (F4) (1) 9+3 (1) 9+3 (1) 9 (F1, 2, 3) 9 + 3 (F4) (1) 9 (F1, 2, 3) 9 + 3 (F4) (1) 9+3 (1) 9+3 (1) 9 (F1, 2, 3) 9 + 3 (F4) 9 (F1, 2, 3) 9 + 3 (F4) 9+3 4b + 7 4b + 10 N° 1+6 1+7 1+8 1 + 10 2+6 2+7 2+8 2+9 3a + 6 3a + 7 3a + 8 NS630b/800/1000/1250/1600 3a + 9 3b + 6 3b + 7 3b + 8 3b + 10 4a + 6 4a + 7 4a + 9 4b + 6 Guide Technique V9 / V9 Technical Guide Raccordement jeu de barres Bars connection Horizontal Inférieure Lower Inférieure Lower Inférieure Lower Inférieure Lower Supérieur Upper Supérieur Upper Supérieur Upper Supérieur Upper Dimension Ossature Framework dimension Vertical Profondeur Depth 600 700 700 x 700/200 x 700 x 700 x 700 x 700/200 x 700 x PG 200/700 PG 200/700 x PG 200/700/200 x 9+3 PG 200/700 x 9 + 3 (F1, 2, 3) 3 + 9 + 3 (F4) 9 + 3 (F1, 2, 3) 3 + 9 + 3 (F4) 3+9+3 PG 200/700 PG 200/700 x PGinf. PGLower poles PGinf. PGLower poles PD 200/700/200 x 200/700 x 700 PD 700 x PD 700 x 9 + 3 (F1, 2, 3) 3 + 9 + 3 (F4) PDinf. PDLower poles 700 AR Rear 9 + 3 (F1, 2, 3) 3 + 9 + 3 (F4) PDinf. PDLower poles 700 x AV/AR Front/Rear 3+9+3 PDinf. PDLower poles 700 x 3+9+3 9 + 3 (F1, 2, 3) 3 + 9 + 3 (F4) 9 + 3 (F1, 2, 3) 3 + 9 + 3 (F4) 3+9+3 1000 x x x x x 66 Installation de l’appareillage Switchgear Installation (1) Rappeler qu’il faut prévoir une porte 4 modules pour JdB horizontal simple ou 8 modules pour JdB horizontal double. (1) To remember that it is necessary to forecast 4 modules door for simple horizontal busbar or 8 modules door for double horizontal busbar. Obligatoires pour l’installation des Compact NS: Compulsory with the installation of the Compact NS: A travers porte Through door Fixe: IP <= 31appareil avec commande manuelle sans cadre , IP <= 31 appareil avec commande manuelle ou commande électrique cadre de porte ref.33718 . IP42/54 appareil avec commande manuelle ou commande électrique avec cadre de porte ref.33857 + capot transparent ref.33859 plages de chant Fixed: IP <= 31device with toggle without escutcheon , IP <= 31 device with toggle or electrically operated escutcheon ref.33718 . Guide Technique V9 / V9 Technical Guide IP42/54 with toggle or electrically operated escutcheon ref.33857 + transparent cover ref.33859; edgewise bars 67 Installation de l’appareillage Switchgear Installation 3.1.2.3.b.2. Débro Arrivée par le BAS/HAUT (à travers portes) Commande rotative directe / commande maneton/ commande électrique. Form 1 à 4 Drawout Incoming from the TOP/BOTTON (through door) Direct rotary handle / toggle / motor mechanism. Form 1 to 4 Disjoncteur Option Circuit Breaker Option N° 1+6 1+7 1+8 1 + 10 2+6 2+7 2+8 2+9 3a + 6 3a + 7 3a + 8 NS630b/800/1000/1250/1600 3a + 9 3b + 6 3b + 7 3b + 8 3b + 10 4a + 6 4a + 7 4a + 9 4b + 6 4b + 7 4b + 10 Guide Technique V9 / V9 Technical Guide Raccordement client Client connection Taille en Modules Number of Modules AR Rear AR Rear AV Front AR Rear AR Rear AR Rear AV Front AR Rear AV Front AR Rear AV Front AR Rear AV Front AR Rear AV/AR Front/Rear AV/AR Front/Rear AV Front AR Rear AV/AR Front/Rear AV Front AR Rear AV/AR Front/Rear 9 (F1, 2, 3) 3 + 9 (F4) (1) 9 (F1, 2, 3) 3 + 9 (F4) (1) 9+3 (1) 9+3 (1) 9 (F1, 2, 3) 9 + 3 (F4) (1) 9 (F1, 2, 3) 9 + 3 (F4) (1) 9+3 (1) 9+3 (1) 9 (F1, 2, 3) 9 + 3 (F4) 9 (F1, 2, 3) 9 + 3 (F4) 9+3 Raccordement jeu de barres Bars connection Horizontal Inférieure Lower Inférieure Lower Inférieure Lower Inférieure Lower Supérieur Upper Supérieur Upper Supérieur Upper Supérieur Upper Dimension Ossature Framework dimension Vertical Profondeur Depth 600 700 700 x 700/200 x 700 x 700 x 700 x 700/200 x 700 x PG 200/700 PG 200/700 x PG 200/700/200 x 9+3 PG 200/700 x 9 + 3 (F1, 2, 3) 3 + 9 + 3 (F4) 9 + 3 (F1, 2, 3) 3 + 9 + 3 (F4) 3+9+3 PG 200/700 PG 200/700 x PGinf. PGLower poles PGinf. PGLower poles PD 200/700/200 x 200/700 x 700 PD 700 x PD 700 x PDinf. PDLower poles PDinf. PDLower poles PDinf. PDLower poles 700 3+9+3 9 + 3 (F1, 2, 3) 3 + 9 + 3 (F4) 9 + 3 (F1, 2, 3) 3 + 9 + 3 (F4) 3+9+3 9 + 3 (F1, 2, 3) 3 + 9 + 3 (F4) 9 + 3 (F1, 2, 3) 3 + 9 + 3 (F4) 3+9+3 1000 x x x x x 700 x 700 x 68 Installation de l’appareillage Switchgear Installation (1) Rappeler qu’il faut prévoir une porte 4 modules pour JdB horizontal simple ou 8 modules pour JdB horizontal double. (1) remember that it is necessary to forecast 4 modules door for simple horizontal busbar or 8 modules door for double horizontal busbar. Obligatoires pour l’installation des Compact NS: Compulsory with the installation of the Compact NS: A travers porte Through door Débrochable: IP <= 31cadre de porte ref. 33857 . IP 42/54 cadre de porte ref. 33857 avec capot transparent ref. 33859 . volet isolant. plages de chant Withdrawable: IP <= 31 door frame ref. 33857 IP 42/54 door frame ref. 33857 with transparent cover ref. 33859 , safety shutters. edgewise bars Guide Technique V9 / V9 Technical Guide 69 Installation de l’appareillage Switchgear Installation 3.1.2.3.b.3. Fixe Arrivée par le BAS/HAUT (derrière porte) Commande rotative prolongée / commande rotative directe. Forme 1 à 4 Fixed Incoming from the TOP/BOTTON (behind door) Extended rotary handle / direct rotary handle. Form 1 to 4 Disjoncteur Option Raccordement client Client connection Taille en Modules Number of Modules Circuit Breaker Option AR Rear 9 (F1, 2, 3) 3 + 9 (F4) (1) Inférieure Lower 700 1+7 AR Rear 9 (F1, 2, 3) 3 + 9 (F4) (1) Inférieure Lower 700 x 1+8 AV Front 9+3 (1) Inférieure Lower 700/200 x 1 + 10 AR Rear 9+3 (1) Inférieure Lower 700 x 2+6 AR Rear 9 (F1, 2, 3) 9 + 3 (F4) (1) Supérieur Upper 700 2+7 AR Rear 9 (F1, 2, 3) 9 + 3 (F4) (1) Supérieur Upper 700 x 2+8 AV Front 9+3 (1) Supérieur Upper 700/200 x 2+9 AR Rear 9+3 (1) Supérieur Upper 700 x 3a + 6 AV Front 9 (F1, 2, 3) 9 + 3 (F4) PG 200/700 3a + 7 AR Rear 9 (F1, 2, 3) 9 + 3 (F4) PG 200/700 x 3a + 8 AV Front 9+3 PG 200/700/200 x 3a + 9 AR Rear 9+3 PG 200/700 x 3b + 6 AV Front 9 + 3 (F1, 2, 3) 3 + 9 + 3 (F4) PG 200/700 3b + 7 AR Rear 9 + 3 (F1, 2, 3) 3 + 9 + 3 (F4) PG 200/700 x 3b + 8 AV/AR Front/Rear 3+9+3 PGinf. PGLower poles 200/700/200 x 3b + 10 AV/AR Front/Rear 3+9+3 200/700 x 4a + 6 AV Front 3 + 9 (F1, 2, 3) 3 + 9 + 3 (F4) PGinf. PGLower poles PD 700 4a + 7 AR Rear 3 + 9 (F1, 2, 3) 3 + 9 + 3 (F4) PD 700 x 4a + 9 AV/AR Front/Rear 3+9+3 PD 700 x 4b + 6 AV Front 9 + 3 (F1, 2, 3) 3 + 9 + 3 (F4) PDinf. PDLower poles 700 4b + 7 AR Rear 9 + 3 (F1, 2, 3) 3 + 9 + 3 (F4) PDinf. PDLower poles 700 x 4b + 10 AV/AR Front/Rear 3+9+3 PDinf. PDLower poles 700 x N° 1+6 NS630b/800/1000/1250/1600 Guide Technique V9 / V9 Technical Guide Raccordement jeu de barres Bars connection Horizontal Dimension Ossature Framework dimension Vertical Profondeur Depth 600 1000 x x x x x x 70 Installation de l’appareillage Switchgear Installation (1) Rappeler qu’il faut prévoir une porte 4 modules pour JdB horizontal simple ou 8 modules pour JdB horizontal double. (1) To remember that it is necessary to forecast 4 modules door for simple horizontal busbar or 8 modules door for double horizontal busbar. Obligatoires pour l’installation des Compact NS: Compulsory with the installation of the Compact NS: Derrière porte Fixe: – plages de chant Behind door Fixed: – edgewise bars Guide Technique V9 / V9 Technical Guide 71 Installation de l’appareillage Switchgear Installation 3.1.2.3.b.4. Débro Arrivée par le BAS/HAUT (derrière porte) Commande rotative prolongée / commande rotative directe. Forme 1 à 4 Drawout Incoming from the TOP/BOTTON (behind door) Extended rotary handle / direct rotary handle. Form 1 to 4 Disjoncteur Option Circuit Breaker Option N° 1+6 1+8 1 + 10 2+6 2+8 2+9 3a + 6 3a + 8 NS630b/800/1000/1250/1600 3a + 9 3b + 6 3b + 8 3b + 10 4a + 6 4a + 7 4a + 9 4b + 6 4b + 10 Guide Technique V9 / V9 Technical Guide Raccordement client Client connection Taille en Modules Number of Modules AR Rear 9 + 3 (F1, 2, 3) 3 + 9 + 3 (F4) (1) 3+9+3 (1) 3+9+3 (1) 9 (F1, 2, 3) 9 + 3 (1) 9+3 (1) 9 + 3 (F1, 2, 3) 3 + 9 + 3 (F4) 3 + 9 (F1, 2, 3) 3 + 9 + 3 (F4) 3+9+3 AV Front AR Rear AR Rear AV Front AR Rear AV Front AV Front AR Rear AV Front AV/AR Front/Rear AV/AR Front/Rear AV Front AR Rear AV/AR Front/Rear AV Front AV/AR Front/Rear Raccordement jeu de barres Bars connection Horizontal Inférieure Lower Dimension Ossature Framework dimension Vertical Profondeur Depth 600 700 Inférieure Lower Inférieure Lower Supérieur Upper Supérieur Upper Supérieur Upper 700/200 x 700 x 1000 x 700 x 700/200 x 700 x PG 200/700 x PG 200/700/200 x 3+9+3 PG 200/700 x 9 + 3 (F1, 2, 3) 3 + 9 + 3 (F4) 3+9+3 PG 200/700 PGinf. PGLower poles PGinf. PGLower poles PD 200/700/200 x 200/700 x 700 PD 700 x PD 700 x PDinf. PDLower poles PDinf. PDLower poles 700 3+9+3 3 + 9 (F1, 2, 3) 3 + 9 + 3 (F4) 3 + 9 (F1, 2, 3) 3 + 9 + 3 (F4) 3+9+3 9 + 3 (F1, 2, 3) 3 + 9 + 3 (F4) 3+9+3 700 x x x x 72 Installation de l’appareillage Switchgear Installation (1) Rappeler qu’il faut prévoir une porte 4 modules pour JdB horizontal simple ou 8 modules pour JdB horizontal double. (1) To remember that it is necessary to forecast 4 modules door for simple horizontal busbar or 8 modules door for double horizontal busbar. Obligatoires pour l’installation des Compact NS: Compulsory with the installation of the Compact NS: Derrière porte Débrochable: – volet isolant. – plages de chant Behind door Withdrawable: – safety shutters. – edgewise bars Guide Technique V9 / V9 Technical Guide 73 Installation de l’appareillage Switchgear Installation 3.1.2.3.c. Compact NS1600b à NS3200 Compact NS1600b to NS3200 3.1.2.3.c.1. Fixe Arrivée par le BAS (à travers portes) Commande rotative directe / commande maneton / commande électrice Fixed Incoming from the BOTTON (throught door) Direct rotatory handle / toggle / motor mechanism Disjoncteur Option Circuit Breaker Option NS1600b/2000/2500 N° 3a + 9 NS3200 (1) 2+9 Raccordement client Client connection Taille en Modules Number of Modules AR Rear AR Rear 10 + 4 Raccordement jeu de barres (2) Bars connection (2) Horizontal 10 + 4 (3) Supérieur Upper Vertical PG Dimension Ossature Framework dimension Profondeur Depth 200/700 600 x 700 x 1000 (1) seulement un par colone avec disjoncteur an haut. (2) Appareil racc. au JdB Horizontal Supérieur, Vertical Gauche. Note: Formes possible F1. (3) Commander en plus porte 8 modules pour JdB horizontal simple ou transfer. (2) Device connected on upper horizontal busbar, left vertical busbar. Note: Possible forms F1. (3) Order in addition 8 modules door to cover simple horizontal/transfer busbar. Obligatoires pour l’installation des Compact NS: Compulsory with the installation of the Compact NS: A travers porte Fixe: – cadre de porte pour IP ≤ 31 ou cadre de porte avec capot transparent pour IP 42/54. Through door Fixed: – door frame for IP ≤ 31 or door frame with transparent cover for IP 42/54; Guide Technique V9 / V9 Technical Guide (1) Just one by column on the top. 74 Installation de l’appareillage Switchgear Installation 3.1.2.4. Compact C Choix des platines et types de commande pour appareils 3/4 pôles Choice of mounting plates and type of operating mechanism for 3/4 pole circuit breakers Type d’appareils Nb pôles Type de commande Position H/V Connexion aux jeux de barres vertical / horizontal Nb modules pour connexion aux jeux de barres Nb modules Disjoncteur Nb modules pour connexion jeux de barres du client Nb modules client aux connexions Forme Fixation Type Nb poles Type of operating mechanism Position H/V Bar connection vertical / horizontal Nb modules for busbar set connections Nb modules Circuit Breaker Nb modules customer connection busbar Customer connection access Form Fixing C801 à / to C1251 3P A/B/C H Vertical - 6 - Côté 400 / Side 400 1/2/3/4 Fixe / Fixed C801 à / to C1251 4P A/B/C H Vertical - 9 - Côté 400/ Side 400 1/2/3/4 Fixe / Fixed C801 à / to C1251 3P A/B H Vertical - 6 - Arrière / Rear 1/2/3 Fixe / Fixed C801 à / to C1251 4P B H Vertical - 9 - Arrière / Rear 1/2/3 Fixe / Fixed C801 à / to C1251 3/4P A/B/D V Horizontal 6 12 3 Côté 200 / Side 200 1 Fixe / Fixed C801 à / to C1251 3/4P A/B V Horizontal 6 12 - Arrière / Rear 1 Fixe / Fixed C801 à / to C1251 3/4P B V Vertical - 12 3 Fond / Bottom 1 Fixe / Fixed C1251 3/4P A V Vertical 4 12 3 Fond / Bottom 1 Fixe / Fixed C801 à / to C1251 3/4P A/B/D V Vertical 3 12 4 Fond / Bottom 1 Fixe / Fixed C1251 3/4P B V Vertical 4 12 - Arrière / Rear 1 Fixe / Fixed C801 à / to C1251 3/4P A/B V Vertical / Horizontal 4 12 4 Fond / Bottom 1 Fixe / Fixed C801 à / to C1251 3/4P B V Vertical 3 12 - Arrière / Rear 1 Fixe / Fixed C801 à / to C1001 3/4P A/B V Vertical 3 12 - Arrière / Rear 1 Fixe / Fixed C801 à / to C1001 3/4P A/B V Vertical 3 12 - Arrière / Rear 1 Fixe / Fixed C1251 3/4P A V Vertical 3 12 - Arrière / Rear 1 Fixe / Fixed C801 à / to C1251 3/4P A/B V Horizontal 6 12 4 Côté 200 / Side 200 1/2/3/4 Châssis / Withdrawable C801 à / to C1251 3/4P A/B V Horizontal 6 12 - Arrière / Rear 1/2/3/4 Châssis / Withdrawable C801 à / to C1251 3/4P A/B V Vertical - 12 - Arrière / Rear 1/2/3/4 Châssis / Withdrawable C801 à / to C1251 3/4P B V Vertical - 12 6 Fond / Bottom 1/2/3/4 Châssis / Withdrawable Guide Technique V9 / V9 Technical Guide 75 Installation de l’appareillage Switchgear Installation Type de commande Type of operating mechanism A derrière porte behind door maneton / rotative directe / électrique toggle / direct rotary handle / motor mechanism B à travers porte through door maneton / rotative directe / électrique* toggle / direct rotary handle / motor mechanism* C derrière porte individuelle behind individual door commande rotative prolongée extended rotary handle D à travers plastron through front plate maneton toggle *: Uniquent maneton pour débrochable sur châssis *: Only toggle for withdrawable assembly Acessoires obligatoires pour l’installation des Compact C fixes: Plages de chant ou à plat suivant la configuration. Caches bornes courts. Compulsory accessories with installation of fixed Compact C: Edgewise or flat bars according to the configuration. Short terminal shields. Obligatoires pour l’installation des Compact C débrochables: Plages de chant ou à plat suivant la configuration. Cadre de porte pour châssis. Volet isolant. Caches bornes courts. Obturateur fils fins IP 20. Compulsory with installation of withdrawable Compact C: Edgewise or flat bars according to the configuration. Door frame for chassis. Safety shutters. Short terminal shields. IP 20 fine wiring closing shutter. Compact C raccordé au Jeu de Barres Vertical à droite Compact C connected to the vertical bars on the right Type Type C801 à C1251 NHL C801 to C1251 NHL Raccordement Connections AV ou AR Front or Rear possibilités possibilities pas développé not developed Compact C raccordé au Jeu de Barres Vertical à gauche Compact C connected to the vertical bars on the left Type Type C801 à C1251 NHL C801 to C1251 NHL Guide Technique V9 / V9 Technical Guide Raccordement Connections AV ou AR Front or Rear possibilités possibilities oui yes 76 Installation de l’appareillage Switchgear Installation 3.1.2.5. Compact CM Les disjoncteurs Compact CM ne peuvent être installés qu’en forme 1; à travers porte, avec une porte individuelle. Position: Verticale. Fixation: Fixe. Commande: maneton, électrique (télécommande). Type d’appareil: CM1250 à CM3200. Nb Modules: 12 + 4. Guide Technique V9 / V9 Technical Guide Compact CM can only be installed in form 1; through the door, and with an individual door. Position: Vertical. Fixing: Fixed. Operating mechanism: toggle, motor mechanism (remote control). Type of circuit breaker: CM1250 to CM3200. Number of Modules: 12 + 4. 77 Installation de l’appareillage Switchgear Installation 3.1.2.6. Masterpact 3.1.2.6.a. 3.1.2.6.a.1. Masterpact NT06 à NT10 Masterpact NT06 to NT10 Fixe/débro Arrivée par le BAS/HAUT (à travers portes). Forme 1 à 4. Fixed/drawout Incoming from the TOP/BOTTON (through door). Form 1 to 4 Disjoncteur Option Circuit Breaker Option N° 1+6 1+7 1+8 1 + 10 2+6 2+7 2+8 2+9 3a + 6 3a + 7 3a + 8 NT06/08/10/12/16 3a + 9 3b + 6 3b + 7 3b + 8 3b + 10 4a + 6 4a + 7 4a + 9 4b + 6 4b + 7 4b + 10 Guide Technique V9 / V9 Technical Guide Raccordement client Client connection Taille en Modules Number of Modules AR Rear AR Rear AV Front AR Rear AR Rear AR Rear AV Front AR Rear AV Front AR Rear AV Front AR Rear AV Front AR Rear AV/AR Front/Rear AV/AR Front/Rear AV Front AR Rear AV/AR Front/Rear AV Front AR Rear AV/AR Front/Rear 9 (F1, 2, 3) 3 + 9 (F4) (1) 9 (1) 9+3 (1) 9+3 (1) 9 (F1, 2, 3) 9 + 3 (F4) (1) 9 (F1, 2, 3) 9 + 3 (F4) (1) 9+3 (1) 9+3 (1) 9 (F1, 2, 3) 9 + 3 (F4) 9 (F1, 2, 3) 9 + 3 (F4) 9+3 Raccordement jeu de barres Bars connection Horizontal Inférieure Lower Inférieure Lower Inférieure Lower Inférieure Lower Supérieur Upper Supérieur Upper Supérieur Upper Supérieur Upper Dimension Ossature Framework dimension Vertical Profondeur Depth 600 700 700 x 700/200 x 700 x 700 x 700 x 700/200 x 700 x PG 200/700 PG 200/700 x PG 200/700/200 x 9+3 PG 200/700 x 9 + 3 (F1, 2, 3) 3 + 9 + 3 (F4) 9 + 3 (F1, 2, 3) 3 + 9 + 3 (F4) 3+9+3 PG 200/700 PG 200/700 x PGinf. PGLower poles PGinf. PGLower poles PD 200/700/200 x 200/700 x 700 PD 700 x PD 700 x PDinf. PDLower poles PDinf. PDLower poles PDinf. PDLower poles 700 3+9+3 3 + 9 (F1,2, 3) 3 + 9 + 3 (F4) 3 + 9 (F1,2, 3) 3 + 9 + 3 (F4) 3+9+3 9 + 3 (F1, 2, 3) 3 + 9 + 3 (F4) 9 + 3 (F1, 2, 3) 3 + 9 + 3 (F4) 3+9+3 1000 x x x x x 700 x 700 x 78 Installation de l’appareillage Switchgear Installation (1) Rappeler qu’il faut prévoir une porte 4 modules pour JdB horizontal simple ou 8 modules pour JdB horizontal double. (1) Remember that it is necessary to forecast 4 modules door for simple horizontal busbar or 8 modules door for double horizontal busbar. Obligatoires pour l’installation des Compact NT: Compulsory with the installation of the Compact NT: A travers porte Through door Fixe: IP <= 31appareil avec commande manuelle sans cadre , IP <= 31 appareil avec commande manuelle ou commande électrique cadre de porte ref.33718 . IP42/54 appareil avec commande manuelle ou commande électrique avec cadre de porte ref.33857 + capot transparent ref.33859 plages de chant Fixed: IP <= 31device with toggle without escutcheon , IP <= 31 device with toggle or electrically operated escutcheon ref.33718 . Débrochable: IP <= 31cadre de porte ref. 33857 . IP 42/54 cadre de porte ref. 33857 avec capot transparent ref. 33859. volet isolant. plages de chant Withdrawable: IP <= 31 door frame ref. 33857 IP 42/54 door frame ref. 33857 with transparent cover ref. 33859. safety shutters. edgewise bars Guide Technique V9 / V9 Technical Guide IP42/54 with toggle or electrically operated escutcheon ref.33857 + transparent cover ref.33859; edgewise bars 79 Installation de l’appareillage Switchgear Installation 3.1.2.6.b. 3.1.2.6.b.1. Masterpact NW08 à NW40 Masterpact NW08 to NW40 Fixe/débrochable Arrivée par le BAS/HAUT. Forme 1 à 4. Fixed/drawout Incoming from the TOP/BOTTON. Form 1 to 4. Disjoncteur Option Raccordement client Client connection Taille en Modules Number of Modules Circuit Breaker Option 1+6 AR Rear 12 (1) Inférieure Lower 700 1+7 AR Rear 12 (1) Inférieure Lower 700 x 1+8 AV/AR Front/Rear 4 + 12 (1) Inférieure Lower 700/200 x 1 + 10 AV/AR Front/Rear 4 + 12 (1) Inférieure Lower 700 x 2+6 AR Rear 12 (1) Supérieur Upper 700 2+7 AR Rear 12 (1) Supérieur Upper 700 x 2+8 AV/AR Front/Rear 12 + 4 (1) Supérieur Upper 700/200 x 2+9 AV/AR Front/Rear 12 + 4 (1) Supérieur Upper 700 x 3a + 6 AR Rear 12 PG 200/700 3a + 7 AR Rear 12 PG 200/700 x 3a + 8 AV/AR Front/Rear 12 + 4 PG 200/700/200 x 3a + 9 AV/AR Front/Rear 12 + 4 PG 200/700 x 3b + 6 AR Rear 12 + 4 PGinf. PGLower poles 200/700 3b + 7 AR Rear 12 + 4 PGinf. PGLower poles 200/700 x 3b + 8 AV/AR Front/Rear 4 + 12 + 4 PGinf. PGLower poles 200/700/200 x 3b + 10 AV/AR Front/Rear 4 + 12 + 4 PGinf. PGLower poles 200/700 x 4a + 6 AR Rear 4 +12 PD 700 4a + 7 AR Rear 4 +12 PD 700 x 4a + 9 AV/AR Front/Rear 4 + 12 + 4 PD 700 x 4b + 6 AR Rear 12 + 4 PDinf. PDLower poles 700 x 4b + 7 AR Rear 12 + 4 PDinf. PDLower poles 700 x 4b + 10 AV/AR Front/Rear 4 + 12 + 4 PDinf. PDLower poles 700 x 1+6 AR Rear 12 (1) Inférieure Lower 700 1+8 AV/AR Front/Rear 4 + 12 (1) Inférieure Lower 700/200 N° NW08/10/12/16 NW20 Guide Technique V9 / V9 Technical Guide Raccordement jeu de barres Bars connection Horizontal Dimension Ossature Framework dimension Vertical Profondeur Depth 600 1000 x X x x x x x 80 Installation de l’appareillage Switchgear Installation Disjoncteur Option Circuit Breaker Option Raccordement client Client connection Taille en Modules Number of Modules N° NW20 NW25 Raccordement jeu de barres Bars connection Horizontal Dimension Ossature Framework dimension Vertical Profondeur Depth 600 1 + 10 AV/AR Front/Rear 4 + 12 (1) Inférieure Lower 700 2+6 AR Rear 12 (1) Supérieur Upper 700 2+8 AV/AR Front/Rear 12 + 4 (1) Supérieur Upper 700/200 x 2+9 AV/AR Front/Rear 12 + 4 (1) Supérieur Upper 700 x 3a + 6 AR Rear 12 PG 200/700 3a + 8 AV/AR Front/Rear 12 + 4 PG 200/700/200 x 3a + 9 AV/AR Front/Rear 12 + 4 PG 200/700 x 3b + 6 AR Rear 12 + 4 PGinf. PGLower poles 200/700 3b + 8 AV/AR Front/Rear 4 + 12 + 4 PGinf. PGLower poles 200/700/200 x 3b + 10 AV/AR Front/Rear 4 + 12 + 4 PGinf. PGLower poles 200/700 x 4a + 6 AR Rear 4 +12 PD 700 4a + 9 AV/AR Front/Rear 4 + 12 + 4 PD 700 4b + 6 AR Rear 12 + 4 PDinf. PDLower poles 700 4b + 10 AV/AR Front/Rear 4 + 12 + 4 PDinf. PDLower poles 700 1+6 AR Rear 12 (1) Inférieure Lower 700 1+8 AV/AR Front/Rear 4 + 12 (1) Inférieure Lower 700/200 x 1 + 10 AV/AR Front/Rear 4 + 12 (1) Inférieure Lower 700 x 2+6 AR Rear 12 (1) Supérieur Upper 700 2+8 AV/AR Front/Rear 12 + 4 (1) Supérieur Upper 700/200 x 2+9 AV/AR Front/Rear 12 + 4 (1) Supérieur Upper 700 x 3a + 6 AR Rear 4 + 12 PG 200/700 3a + 8 AV/AR Front/Rear 4 + 12 + 4 PG 200/700/200 x 3a + 9 AV/AR Front/Rear 4 + 12 + 4 PG 200/700 x 3b + 6 AR Rear 12 + 4 PGinf. PGLower poles 200/700 3b + 8 AV/AR Front/Rear 4 + 12 + 4 PGinf. PGLower poles 200/700/200 x 3b + 10 AV/AR Front/Rear 4 + 12 + 4 PGinf. PGLower poles 200/700 x 4a + 6 AR Rear 4 +12 PD 700 Guide Technique V9 / V9 Technical Guide 1000 x X x x x x x x x X x x x 81 Installation de l’appareillage Switchgear Installation Disjoncteur Option Circuit Breaker Option Raccordement client Client connection Taille en Modules Number of Modules N° NW25 Horizontal Dimension Ossature Framework dimension Vertical Profondeur Depth 600 4a + 9 AV/AR Front/Rear 4 + 12 + 4 PD 700 x 4b + 6 AR Rear 12 + 4 PDinf. PDLower poles 700 x 4b + 10 AV/AR Front/Rear 4 + 12 + 4 PDinf. PDLower poles 700 x 1+8 AV/AR Front/Rear 4 + 12 + 4 (1) Inférieure Lower 700/400 x 1 + 10 AV/AR Front/Rear 4 + 12 + 4 (1) Inférieure Lower 700 x 2+8 AV/AR Front/Rear 4 + 12 + 4 (1) Supérieur Upper 700/400 x 2+9 AV/AR Front/Rear 4 + 12 + 4 (1) Supérieur Upper 700 x 3a + 8 AV/AR Front/Rear 6 + 12 + 4 PG 200/700/400 x 3a + 9 AV/AR Front/Rear 6 + 12 + 4 PG 700/200 x 3b + 8 AV/AR Front/Rear 4 + 12 + 10 PGinf. PGLower poles 200/700/400 x 3b + 10 AV/AR Front/Rear 4 + 12 + 10 PGinf. PGLower poles 200/700 x 4a + 9 AV/AR Front/Rear 4 + 12 + 4 PD 700/200 X 4b + 10 AV/AR Front/Rear 4 + 12 + 4 PDinf. PDLower poles 700/200 X 1 + 10 AV/AR Front/Rear 9 + 12 (1) Inférieure Lower 700 x 2+9 AV/AR Front/Rear 11 + 12 (1) Supérieur Upper 700 x NW32 NW40 Raccordement jeu de barres Bars connection Guide Technique V9 / V9 Technical Guide 1000 82 Installation de l’appareillage Switchgear Installation (1) Rappeler qu’il faut prévoir une porte 4 modules pour JdB horizontal simple ou 8 modules pour JdB horizontal double. (1) Remember that it is necessary to forecast 4 modules door for simple horizontal busbar or 8 modules door for double horizontal busbar. Glossaire des Abréviations: AR Raccordement arrière AV Raccordement avant PG Jeu de barres Plate Gauche PD Jeu de barres Plate Droite Glossary des Abbreviations: PG Left edgewise busbar PD Right edgewise busbar LG Left Linergy busbar LD Right Linergy busbar Obligatoires pour l’installation des Masterpact: Compulsory with the installation of the Masterpacts: Fixe: IP <= 31cadre de porte ref. 48601. IP 42/54 cadre de porte ref. 48603 et capot transparent ref. 48604 avec obturateur de porte ref. 48605 . Fixed: IP <= 31 door frame ref. 48601 . IP 42/54 door frame ref. 48603 and transparent cover ref. 48604 with escutcheon blanking plate ref. 48605 . Débrochable: IP <= 31cadre de porte ref. 48603 . IP 42/54 cadre de porte ref. 48603 avec capot transparent ref. 48604 . volet isolant. plages de chant Withdrawable: IP <= 31 door frame ref. 48603 . IP 42/54 door frame ref. 48603 with transparent cover ref. 48604 . safety shutters. edgewise bars Guide Technique V9 / V9 Technical Guide 83 Installation de l’appareillage Switchgear Installation 3.1.2.6.c. 3.1.2.6.c.1. Masterpact NW40b à NW63 Masterpact NW40b to NW63 Débro Arrivée par le BAS/HAUT forme 1 à 4 Drawout Incoming from the TOP/BOTTON form 1 to 4 Disjoncteur Option Raccordement client Client connection Taille en Modules Number of Modules Circuit Breaker Option 2+9 AV/AR Front/Rear 10+13+15 Supérieur (1) Upper(2) 1200 x 1+10 AV/AR Front/Rear 16+13+11 Inférieure (1) Lower(2) 1200 x 2+9 AV/AR Front/Rear 13+13+14 Supérieur (2) Upper(3) 1200 x 1+10 AV/AR Front/Rear 13+13+14 Inférieure (2) Lower(3) 1200 x 2+9 AV/AR Front/Rear 13+13+14 Supérieur (2) Upper(3) 1200 x 1+10 AV/AR Front/Rear 13+13+14 Inférieure (2) Lower(3) 1200 x N° NW40b NW50/63 Raccordement jeu de barres Bars connection Horizontal (1) Appareil racc. au JdB Simple Horizontal. (2) Appareil racc. au JdB Double Horizontal. Obligatoires pour l’installation des Masterpact: Débrochable: IP <= 31cadre de porte ref. 48603. IP 42/54 ou cadre de porte ref. 48603 avec capot transparent ref. 48604. volet isolant, plages de chant. Guide Technique V9 / V9 Technical Guide Dimension Ossature Framework dimension Vertical Profondeur Depth 600 (1) Device connected on Simple horizontal busbar. (2) Device connected on Double horizontal busbar. Compulsory with the installation of the Masterpacts: Withdrawable: IP <= 31 door frame ref. 48603 . IP 42/54 or door frame ref. 48603 with transparent cover ref. 48604 , safety shutters, edgewise bars. 84 Installation de l’appareillage Switchgear Installation 3.1.2.6.d. Choix des transformateurs de courant (TI) Choice of current transformers (CT) Disjoncteur Circuit breaker Ref. Standard Tropicalisé Tropicalised NS630b - 1600 NT06 - 16 16530 NW08/10/12 NW16/20/25 NS1600b/2000/ 2500 NW32/40 NS 3200 NW40b/50/63 Rapport Rating Ouverture Opening 16480 500 - 5 A 65 x 32 mm 16531 16481 600 - 5 A 65 x 32 mm 16532 16482 800 - 5 A 65 x 32 mm 16533 16483 1000 - 5 A 65 x 32 mm 16534 1250 - 5 A 65 x 32 mm 16535 1250 - 5 A 65 x 32 mm 16530 16480 500 - 5 A 65 x 32 mm 16531 16481 600 - 5 A 65 x 32 mm 16532 16482 800 - 5 A 65 x 32 mm 16533 16483 1000 - 5 A 65 x 32 mm 16534 1250 - 5 A 65 x 32 mm 16537 1250 - 5 A 84 x 34 mm 16538 1500 - 5 A 84 x 34 mm 16540 1250 - 5 A 127 x 38 mm 16541 1500 - 5 A 127 x 38 mm 16542 2000 - 5 A 127 x 38 mm 16543 2500 - 5 A 127 x 38 mm 16544 3000 - 5 A 127 x 38 mm 16545 2500 - 5 A 127 x 52 mm 16547 4000 - 5 A 127 x 52 mm 16548 5000 - 5 A 165 x 55 mm 16549 6000 - 5 A 165 x 55 mm Nota: Les TI pouvent etre montes amont ou aval du disjoncteur .Vérifier sur les plans d'assemblage. Guide Technique V9 / V9 Technical Guide N.B.: The CT's can be assembled on the line side or load side of the circuit breakers. Check on the assembly drawings. 85 Installation de l’appareillage Switchgear Installation 3.1.2.7. Option raccordement jeu de barres Disjoncteur Compact NS 630b-1600 et Masterpact NT / NW Option connection busbars Compact NS 630b-1600 and Masterpact NT / NW circuit breaker Option Option Fixe Fixed Option: 1 Débrochable Withdrawable 1 a) NS 630b-1600 (1) a) NT 06-16 b) NW 08 / 25 1 NW 32 (1) Disponible derrière porte avec la même modularité (1) Available behind door with the same modularity Guide Technique V9 / V9 Technical Guide 86 Installation de l’appareillage Switchgear Installation Option: 1 Option Option Fixe Fixed Débrochable Withdrawable 1 NW 40 (1) Disponible derrière porte avec la même modularité (1) Available behind door with the same modularity Guide Technique V9 / V9 Technical Guide 87 Installation de l’appareillage Switchgear Installation Option: 1 Option Option Fixe Fixed Débrochable Withdrawable 1 NW 40b Connecté au jeux de barres simple Connected to simple busbar (1) Disponible derrière porte avec la même modularité (1) Available behind door with the same modularity Guide Technique V9 / V9 Technical Guide 88 Installation de l’appareillage Switchgear Installation Option: 1 Option Option Fixe Fixed Débrochable Withdrawable 1 NW 40b/50/63 Connecté au jeux de barres double Connected to double busbar (1) Disponible derrière porte avec la même modularité (1) Available behind door with the same modularity Guide Technique V9 / V9 Technical Guide 89 Installation de l’appareillage Switchgear Installation Option: 2 Option Option Fixe Fixed Débrochable Withdrawable 2 a) NS 630b-1600 (1) a) NT 06-16 b) NW 08/25 2 a) NW 32 b) NS 3200 (1) Disponible derrière porte avec la même modularité (1) Available behind door with the same modularity Guide Technique V9 / V9 Technical Guide 90 Installation de l’appareillage Switchgear Installation Option: 2 Option Option Fixe Fixed Débrochable Withdrawable 2 NW 40 (1) Disponible derrière porte avec la même modularité (1) Available behind door with the same modularity Guide Technique V9 / V9 Technical Guide 91 Installation de l’appareillage Switchgear Installation Option: 2 Option Option Fixe Fixed Débrochable Withdrawable 2 NW 40b Connecté au jeux de barres simple Connected to simple busbar (1) Disponible derrière porte avec la même modularité (1) Available behind door with the same modularity Guide Technique V9 / V9 Technical Guide 92 Installation de l’appareillage Switchgear Installation Option: 2 Option Option Fixe Fixed Débrochable Withdrawable 2 NW 40b/50/63 Connecté au jeux de barres double Connected to double busbar (1) Disponible derrière porte avec la même modularité (1) Available behind door with the same modularity Guide Technique V9 / V9 Technical Guide 93 Installation de l’appareillage Switchgear Installation Option: 3a Option Option Fixe Fixed Débrochable Withdrawable 3a a) NS 630b-1600 (1) a) NT 06-16 b) NS1600b - 2500 c) NW 08 - 20 9 M (a) 10 M (b) 12 M (c) 9 M (a) 12 M (c) 3a a) NS 630b-1600 (1) Derrière porte + commande rotative prolongée Behind door + ext. rotary handle b) NW 25 c) NW 32 (1) Disponible derrière porte avec la même modularité (1) Available behind door with the same modularity Guide Technique V9 / V9 Technical Guide 94 Installation de l’appareillage Switchgear Installation Option: 3b Option Option Fixe Fixed Débrochable Withdrawable 3b a) NS 630b-1600 (1) a) NT 06-16 b) NW 08 - 25 3b NW 32 (1) Disponible derrière porte avec la même modularité (1) Available behind door with the same modularity Guide Technique V9 / V9 Technical Guide 95 Installation de l’appareillage Switchgear Installation Option: 4a Option Option Fixe Fixed Débrochable Withdrawable 4a a) NS 630b-1600 (1) a) NT 06-16 b) NW 08 - 32 Option: 4b Option Option Fixe Fixed Débrochable Withdrawable 4b a) NS 630b-1600 (1) a) NT 06-16 b) NW 08 - 32 (1) Disponible derrière porte avec la même modularité (1) Available behind door with the same modularity Guide Technique V9 / V9 Technical Guide 96 Installation de l’appareillage Switchgear Installation 3.1.2.8. Option raccordement client Disjoncteur Compact NS 630b-1600 et Masterpact NT / NW Option incoming bars Compact NS 630b-1600 and Masterpact NT / NW circuit breake Option: Option: 6 6 Option Option Fixe Fixed Débrochable Withdrawable 6 a) NS 630b-1600 (1) a) NT 06-16 b) NW 08 - 25 Option: Option: 7 Option Option Fixe Fixed 7 Débrochable Withdrawable 7 a) NS 630b-1600 (1) a) NT 06-16 b) NW 08 - 16 NS 630b-1600 (1) Derrière porte + commande rotative prolongée (impossible) Behind door + ext. rotary handle (not possible) (1) Disponible derrière porte avec la même modularité (1) Available behind door with the same modularity Guide Technique V9 / V9 Technical Guide 97 Installation de l’appareillage Switchgear Installation Option: 8a Option Option Fixe Fixed Débrochable Withdrawable 8a a) NS 630b-1600 (1) a) NT 06-16 b) NW 08 - 25 Option: 8b Option Option Fixe Fixed Débrochable Withdrawable 8b a) NS 630b-1600 a) NT 06-16 b) NW 08 - 25 (1) Disponible derrière porte avec la même modularité (1) Available behind door with the same modularity Guide Technique V9 / V9 Technical Guide 98 Installation de l’appareillage Switchgear Installation Option: 8a Option Option Fixe Fixed Débrochable Withdrawable 8a NW 32 Option: 8b Option Option Fixe Fixed Débrochable Withdrawable 8b NW 32 (1) Disponible derrière porte avec la même modularité (1) Available behind door with the same modularity Guide Technique V9 / V9 Technical Guide 99 Installation de l’appareillage Switchgear Installation Option: 9 Option Option Fixe Fixed Débrochable Withdrawable 9 a) NS 630b-1600 (1) a) NT 06-16 b) NW 08 - 32 c) NS 1600b/2000/ 2500/3200 (c) 9 a) NW 40 b) NW 40b c) NW 40b c) NW 50 c) NW 63 Sans transfermateur d’intensité Without current transformer (1) Disponible derrière porte avec la même modularité (1) Available behind door with the same modularity Guide Technique V9 / V9 Technical Guide 100 Installation de l’appareillage Switchgear Installation Option: 9 Option Option Fixe Fixed Débrochable Withdrawable 9 a) NW 40 b) NW 40b c) NW 40b c) NW 50 c) NW 63 Avec transfermateur d’intensité With current transformer (1) Disponible derrière porte avec la même modularité (1) Available behind door with the same modularity Guide Technique V9 / V9 Technical Guide 101 Installation de l’appareillage Switchgear Installation Option: 10 Option Option Fixe Fixed Débrochable Withdrawable 10 a) NS 630b-1600 (1) a) NT 06-16 b) NW 08 - 32 10 a) NW 40 b) NW 40b c) NW 40b c) NW 50 c) NW 63 Avec transfermateur d’intensité With current transformer (1) Disponible derrière porte avec la même modularité (1) Available behind door with the same modularity Guide Technique V9 / V9 Technical Guide 102 Installation de l’appareillage Switchgear Installation Option: 10 Option Option Fixe Fixed Débrochable Withdrawable 10 a) NW 40 b) NW 40b c) NW 40b c) NW 50 c) NW 63 Sans transfermateur d’intensité Without current transformer (1) Disponible derrière porte avec la même modularité (1) Available behind door with the same modularity Guide Technique V9 / V9 Technical Guide 103 Installation de l’appareillage Switchgear Installation 3.1.2.9. Interpact Appareils Device Profondeur Depth Accès Access Position Position Nr. ap. Nb. dev. Fixation Fixation Connections Connection Commande (1) Front view (1) Nb modules Nb. modules INS40/80 400 Av / Ar Fr / Re Vertical Vertical 5 Fixe Fixed JdB Vertical JdB Vertical B/D B/D 4 INS100/160 400 Av / Ar Fr / Re Vertical Vertical 3 Fixe Fixed JdB Vertical JdB Vertical B/D B/D 6 IN250 400 Av / Ar Fr / Re Vertical Vertical 1 Fixe Fixed JdB Vertical JdB Vertical B/D B/D 6 IN400/630 400 Avant Front Vertical Vertical 1 Fixe Fixed JdB Vertical JdB Vertical B/D B/D 6+3 IN400/630 600 Av / Ar Fr / Re Vertical Vertical 1 Fixe Fixed JdB Vertical JdB Vertical AàD A to D 6+3 IN1000 à 2500 600 Av / Ar Fr / Re Vertical Vertical 1 Fixe Fixed JdB Vertical JdB Vertical AàD A to D 12 + 4 (1) Type de commande: A Derrière porte B A travers porte C Derrière porte individuelle D Plastron Guide Technique V9 / V9 Technical Guide (1) Front view: A behind door B through door C behind individual door D through escutcheon (with front plate) 104 Installation de l’appareillage Switchgear Installation 3.1.2.10. Inverseur de source Source changeover 3.1.2.10.a. Interpact, Compact NS 100-630, Compact C et Masterpact M (en profondeur 600 mm) Interpact, Compact NS, Compact C et Masterpact M (600 mm depth) Appareils Device Type Type Accès Access Position Position Fixation Fixation Connections Connection Commande (1) Front view (1) Nb modules Nbr of modules NS100/250 Manuel Manual Av / Ar Front or rear Vertical Vertical Fixe Fixed JdB Vertical Vertical busbar B 6 NS400/630 Manuel Manual Ar Rear Vertical Vertical Fixe Fixed JdB Horizontal Horizontal busbar B 12 C801/C1251 Manuel Manual Av / Ar Front or rear Vertical Vertical Fixe Fixed JdB Vertical Vertical busbar B 12 + 4 Masterpact M Manuel Manual Av / Ar Front or rear Normal Normal - - B 4+12+4+12+8 NS100/250 Auto Auto Av / Ar Front or rear Horizontal Horizontal Fixe Fixed JdB Vertical Vertical busbar A 12 NS400/630 Auto Auto Av / Ar Front or rear Horizontal Horizontal Fixe Fixed JdB Vertical Vertical busbar A 14 C801/1251 Auto Auto Av / Ar Front or rear Horizontal Horizontal Fixe Fixed JdB Vertical Vertical busbar A 20 Masterpact M Auto Auto Av / Ar Front or rear Normal Normal - - - 4+12+4+12+8 IN250 Manuel Manual Av / Ar Front or rear Vertical Vertical Fixe Fixed JdB Vertical Vertical busbar B 6 Manuel / Manual Pour les détails additionels voir chapitre 4.1 du Guide des plans d’assemblage, ref. “7041xxx.pdf” Auto / Auto For additional details see chapter 4.1 of Assembly drawings guide, ref. “7041xxx.pdf” NS400/ 630 12M NS400/ 630 NS400/ 630 NS100/ NS100/ 250 250 NS400/ 630 14M UA / BA 6M NS100/ 250 NS100/ 250 INS 250 INS 250 6M Guide Technique V9 / V9 Technical Guide UA / BA 12M 105 Installation de l’appareillage Switchgear Installation 3.1.2.10.b. Compact NS 630b - NS 1600, 3/4P Masterpact NT 06 à 16, 3/4P Compact NS 630b - NS 1600, 3/4P Masterpact NT 06 to 16, 3/4P fixe derrière ou à travers porte débrochable à travers porte fixe/débrochable fixed behind or through door withdrawable behind or though door fixed/withdrawable 4M 4M UA / BA (2) Automatisme télécommandé des inverseurs de source. (2) Automatic source change over system 3M Option 1+8a (2) UA / BA 3M Option 1+6 (2) 9M 9M 8M 8M Option 2+9 Option 2+9 9M 9M 7M 7M Colonne individuelle RAV: Profondeur 600; Largeur 400+700+200 RAR: Profondeur 1000; Largeur 400+700 Disponible en IP20 jusqu’à IP54, forme 1 à 4 Pour les détails additionnels voir chapitre 4.1 du Guide des plans d’assemblage, ref. “7041xxx.pdf” VUE DU HAUT / TOP VIEW Individual column Front Access: Depth 600; Width 400+700+200 Rear Access: Depth 1000; Width 400+700 Available in IP20 up to IP54, form 1 up to 4. For additional details see chapter 4.1 of Assembly drawings guide, ref. “7041xxx.pdf” 400 700 Face avant / Front Guide Technique V9 / V9 Technical Guide 200 600 600 400 VUE DU HAUT / TOP VIEW 400 700 Face avant / Front 106 Installation de l’appareillage Switchgear Installation Compact NS 630b - NS 1600, 3/4P Masterpact NT 06 à 16, 3/4P Compact NS 630b - NS 1600, 3/4P Masterpact NT 06 to 16, 3/4P 4M fixe derrière ou à travers porte débrochable à travers porte fixe/débrochable fixed behind or through door withdrawable behind or though door fixed/withdrawable (2) Automatisme télécommandé des inverseurs de source. (2) Automatic source change over system Option 3a+8b 4M Option 3a+6 9M 9M 3M 3M 8M 4M 8M UA / BA (2) 4M Option 3a+9 UA / BA (2) Option 3a+9 9M 9M 3M 3M Raccordé au Jeu de Barres Vertical standard RAV: Profondeur 600; Largeur 200+700+200 RAR: Profondeur 1000; Largeur 200+700 Disponible en IP20 jusqu’à IP54, forme 1 to 4 Pour les détails additionnels voir chapiter 4.1 du Guide des plans d’assemblage, ref. “7041xxx.pdf” Connceted to standard Vertical Busbar Front Access: Depth 600; Width 200+700+200 Rear Access: Depth 1000; Width 200+700 Available in IP20 up to IP54, form 1 up to 4. For additional details see chapter 4.1 of Assembly drawings guide, ref. “7041xxx.pdf” VUE DU HAUT / TOP VIEW 200 700 200 Face avant / Front Guide Technique V9 / V9 Technical Guide 600 600 400 VUE DU HAUT / TOP VIEW 200 700 Face avant / Front 107 Installation de l’appareillage Switchgear Installation 3.1.2.10.c. Compact NS 630b à NS 1600, 3/4P débrochable derrière porte Compact NS 630b to NS 1600, 3/4P withdrawable behind door (2) Automatisme télécommandé des inverseurs de source. (2) Automatic source change over system 4M UA / BA 3M Option 1+8a (2) 4M UA / BA 3M Option 1+6 (2) 9M 9M 11M 11M Option 2+9 Option 2+9 9M 9M 4M 4M Colonne individuelle RAV: Profondeur 600; Largeur 400+700+200 RAR: Profondeur 1000; Largeur 400+700 Disponible en IP 20 jusqu’à IP54 40 modules pour l’installation des équipements. Pour les détails additionnels voir chapitre 4.1 du Guide des plans d’assemblage, ref. “7041xxx.pdf” VUE DU HAUT / TOP VIEW Individual column Front Access: Depth 600; Width 400+700+200 Rear Access: Depth 1000; Width 400+700 Available in IP20 up to IP54 40 modules for installation of equipament For additional details see chapter 4.1 of Assembly drawings guide, ref. “7041xxx.pdf” 400 700 Face avant / Front Guide Technique V9 / V9 Technical Guide 200 600 600 400 VUE DU HAUT / TOP VIEW 400 700 Face avant / Front 108 Installation de l’appareillage Switchgear Installation Compact NS 630b à NS 1600, 3/4P débrochable derrière porte Compact NS 630b to NS 1600, 3/4P withdrawable behind door (2) Automatisme télécommandé des inverseurs de source. (2) Automatic source change over system 4M 3M 4M 3M Option 3a+6 Option 3a+8b 9M 9M 3M 2M 5M 4M UA / BA (2) 4M UA / BA (2) 3M 3M Option 3a+9 Option 3a+9 9M 9M 3M 3M Raccordé au Jeu de Barres Vertical standard RAV: Profondeur 600; Largeur 200+700+200 RAR: Profondeur 1000; Largeur 200+700 Disponible en IP20 jusqu’à IP54, forme 1 à 4 Pour les détails additionnels voir chapitre 4.1 du Guide des plans d’assemblage, ref. “7041xxx.pdf” Connected to standard Vertical Busbar Front Access: Depth 600; Width 200+700+200 Rear Access: Depth 1000; Width 200+700 Available in IP20 up to IP54, form 1 upto 4. For additional details see chapter 4.1 of Assembly drawings guide, ref. “7041xxx.pdf” VUE DU HAUT / TOP VIEW 200 700 200 Face avant / Front Guide Technique V9 / V9 Technical Guide 600 600 400 VUE DU HAUT / TOP VIEW 200 700 Face avant / Front 109 Installation de l’appareillage Switchgear Installation 3.1.2.10.d. Compact NS 630b à NS 1600, 3/4P fixe derrière porte Compact NS 630b to NS 1600, 3/4P fixed behind door 4M (1) Option 2+9 (1) Seulement commande manuelle pour les inverseurs de source. (1) Only manual command for the source change over 9M 4M Colonne individuelle RAV/RAR: Profondeur 600; Largeur 700 Disponible en IP20 jusqu’à IP31, forme 1 40 modules pour l’installation des equipements. Pour les détails additionels voir Chapitre 4.1 du Guide des plans d’assemblage, ref. “7041xxx.pdf” Individual column Front/Rear Access: Depth 600; Width 700 Available in IP20 up to IP31, form 1 40 modules for installation of equipament. For additional details see Chapter 4.1 of Assembly drawings guide, ref. “7041xxx.pdf” 600 VUE DU HAUT / TOP VIEW 700 Face avant / Front Guide Technique V9 / V9 Technical Guide 110 Installation de l’appareillage Switchgear Installation 3.1.2.10.e. Masterpact NW 08 à 25, 3/4P fixe/débro à travers porte Masterpact NW 08 to 25, 3/4P fixed/drawout through door (2) Automatisme télécommandé des inverseurs de source. (2) Automatic source change over system 4M UA / BA Option 1+8a 4M UA / BA Option 1+6 (2) (2) 12M 12M 8M 8M Option 2+9 Option 2+9 12M 12M 4M 4M Colonne individuelle RAV: Profondeur 600; Largeur 400+700+200 RAR: Profondeur 1000; Largeur 400+700 Disponible en IP20 jusqu’à IP54, forme 1 à 4 40 modules pour l’installation des equipements. Pour les détails additionnels voir chapitre 4.1 du Guide des plans d’assemblage, ref. “7041xxx.pdf” VUE DU HAUT / TOP VIEW Individual column Front Access: Depth 600; Width 400+700+200 Rear Access: Depth 1000; Width 400+700 Available in IP20 up to IP54, form 1 up to 4. 40 modules for installation of equipament For additional details see chapter 4.1 of Assembly drawings guide, ref. “7041xxx.pdf” 400 700 Face avant / Front Guide Technique V9 / V9 Technical Guide 200 600 600 400 VUE DU HAUT / TOP VIEW 400 700 Face avant / Front 111 Installation de l’appareillage Switchgear Installation 3.1.2.10.f. Masterpact NW 08 à 20, 3/4P fixe/débro à travers porte Masterpact NW 08 to 20, 3/4P fixed/ drawout through door (2) Automatisme télécommandé des inverseurs de source. (2) Automatic source change over system 4M Option 3a+8b 4M Option 3a+6 12M 12M 4M 4M UA / BA 4M (2) UA / BA 4M (2) Option 3a+9 Option 3a+9 12M 12M 3M 3M Raccordé au Jeu de Barres Vertical standard RAV: Profondeur 600; Largeur 200+700+200 RAR: Profondeur 1000; Largeur 200+700 Disponible en IP20 jusqu’à IP54, forme 1 à 4 Pour les détails additionnels voir chapitre 4.1 du Guide des plans d’assemblage, ref. “7041xxx.pdf” Connected to standard Vertical Busbar Front Access: Depth 600; Width 200+700+200 Rear Access: Depth 1000; Width 200+700 Available in IP20 up to IP54, form 1 up to 4. For additional details see chapter 4.1 of Assembly drawings guide, ref. “7041xxx.pdf” VUE DU HAUT / TOP VIEW 200 700 200 Face avant / Front Guide Technique V9 / V9 Technical Guide 600 600 400 VUE DU HAUT / TOP VIEW 200 700 Face avant / Front 112 Installation de l’appareillage Switchgear Installation 3.1.2.10.g. Masterpact NW 32 à 63, 3/4P fixe/débro (RAV/RAR) Masterpact NW 32 to 63, 3/4P fixed/ drawout (Front/Rear access) (1) (1) Option 2+9 Option 2+9 NW32/40 NW32/40 (2) Automatisme télécommandé des inverseurs de source (2) Automatic source change over system (1) (1) (3) (2) (1) Définir le nombre de modules suivant chapitre 3.1.2.6. et 3.1.2.7. de ce document (1) Define the number of modules according to chapters 3.1.2.6. and 3.1.2.7. of this document UA / BA (3) Détails sur la modularité, voir dessin 51131664 pour NW32 ou dessin 51131686 pour NW40 (3) Details about modularity, see dwg 51131664 for NW32 or dwg 51131686 for NW40 (1) 600 VUE DU SOMMET / TOP VIEW 700 700 700 RAV/RAR: Profondeur 600; Largeur 700+700+700 Pour les détails additionnels voir chapitre 4.1 du Guide des plans d’assemblage, ref. “7041xxx.pdf” UA / BA (2) Front Access/Rear Access: Depth 600; Width 700+700+700 For additional details see chapter 4.1 of Assembly drawings guide, ref. “7041xxx.pdf” 13 M (1) 13 M (1) Option 2+9 Option 2+9 NW40b/50/63 NW40b/50/63 13 M (1) 13 M (1) 14 M (1) 14 M (1) (1) Détails sur le modularité, voir dessin 51131661 pour NW40b/50/63 (1) Details about modularity, see dwg 51131661 NW40b/50/63 (2) Automatisme télécommandé des inverseurs de source (2) Automatic source change over system 600 VUE DU SOMMET / TOP VIEW 1200 1200 RAV/RAR: Profondeur 600; Largeur 1200+1200+1200 Guide Technique V9 / V9 Technical Guide 1200 Front Access/Rear Access: Depth 600; Width 1200+1200+1200 113 Installation de l’appareillage Switchgear Installation 3.1.2.11. Couplage et Jeux de Barres de Transfert Tie Breaker and Transfer Busbar 3.1.2.11.a. Masterpact NW40 et jeu des barres simple Masterpact NW40 and single busbars 13 M 13 M Option 2+1 Option 2+1 NW40 NW40 12 M 12 M 15 M 15 M VUE DU SOMMET / TOP VIEW 200 Guide Technique V9 / V9 Technical Guide 700 Il est interdit de connecter des unités fonctionnels sur le jeu de barre de trasfert. Pour les détails additionnels voir chapitre 3.3 du Guide des plans d'assemblage, ref. "7041xxx.pdf". It's not allowed to connect any device direct to transfer busbar. For additional details see chapter 3.3 of Assembly drawings guide, ref. "7041xxx.pdf". VUE DU SOMMET / TOP VIEW 200 700 114 Installation de l’appareillage Switchgear Installation 3.1.2.11.b. Masterpact NW40b/50/63 et jeu des barres double Masterpact NW40b/50/63 and double busbars 13 M Option 2+1 Option 2+1 NW40b/50/63 NW40b/50/63 13 M 13 M 14 M 14 M VUE DU SOMMET / TOP VIEW 200/400 Guide Technique V9 / V9 Technical Guide 13 M 1200 VUE DU SOMMET / TOP VIEW 200/400 Il est interdit de connecter des unités fonctionnels sur le jeu de barre de trasfert. - 200 mm pour le JdB simple (pour Nw40b seulement) Pour les détails additionnels voir chapitre 3.3 du Guide des plans d'assemblage, ref. "7041xxx.pdf". It's not allowed to connect any device direct to transfer busbar. - 200 mm for single busbar (for Nw40b only) For additional details see chapter 3.3 of Assembly drawings guide, 1200 115 Sommaire du chapitre Chapter contents 3.2. Condensateur Capacitor 3.2.1. Installation ............................................................................................... 117 Installation 3.2.1.1. Cellule Dc largeur 700 mm profondeur 400/600 mm ............... 117 Dc column with 700 mm width and 400/600 mm depth 3.2.1.2. Cellule D largeur 700 mm profondeur 400/600 mm ................. 117 D column with 700 mm width and 400/600 mm depth Guide Technique V9 / V9 Technical Guide 116 Installation de l’appareillage Switchgear Installation 3.2. Condensateur Capacitor 3.2.1. Installation Installation 3.2.1.1. Cellule Dc largeur 700 mm profondeur 400/600/1000 mm Dc column with 700 mm width and 400/600/1000 mm depth Installation pour température ambiante de 35°C IP 31: Ventilation naturelle (avec grille d’entrée et de sortie MGA réf. 07985, sans filtre). Configuration maximum: 6 platines de 30 kVar en 400 volts 50 Hz. Ventilation forcée (avec ventilateur MGA réf 07989 + grille MGA réf 07985 et filtre MGA réf 07982). Configuration maximum: 6 platines de 60 kVar en 400 volts 50 Hz. Installation for an ambient temperature of 35°C IP 31: Natural ventilation (with MGA inlet and outlet grid ref. 07985, without filter). maximum configuration: 6 x30 kVar mounting plates in 400 volts 50 Hz. Forced ventilation (with MGA fan ref. 07989 + MGA grid ref. 07985 and MGA filter ref. 07982). Maximum configuration: 6 x60 kVar mounting plates in 400 volts 50 Hz. Pour les autres tensions et fréquences, ne pas dépasser les valeurs de puissance mentionnées ci-dessus (voir configuration dans catalogue Rectiphase). For the other voltages and frequencies, do not exceed the power values mentioned above (see configuration in the Rectiphase catalogue). 3.2.1.2. Cellule D largeur 700 mm profondeur 400/600/1000 mm D column with 700 mm width and 400/600/1000 mm depth pour montage en cellule D utiliser: La platine n° 51 128 229: 6 modules avec maximum de 50 kVar en 600 volts 60 Hz. Ne pas dépasser dans une même cellule les valeurs données pour la cellule Dc. For mounting in column D use: Mounting plate n° 51 128 229: 6 modules with-maximum of 50 kVar in 600 volts 60 Hz. Do not exceed in the same column the values given for column Dc. Toutes ces informations sont communiquées conformément aux essais réalisés sur les cellules Blokset. All this information is communicated according to the tests performed on the Blokset columns. Puissances d’emploi en 50/60 Hz θ ≤ 55 °C Power ratings at 50/60 Hz θ ≤ 55 °C 220 V 240 V kVar 400 V 440 V kVar 660 V 690 V kVar Contacteur Contactor 6,5 12,5 18 LC1-DFK 8,5 15 24 LC1-DGK 10 20 30 LC1-DLK 15 25 36 LC1-DNWK 20 30 48 LC1-DPK 25 40 58 LC1-DTK 40 60 92 LC1-DWK Guide Technique V9 / V9 Technical Guide 117 Installation de l’appareillage Switchgear Installation Tableau de déclassement des condensateurs BT Derating of Low Voltage Capacitors in Blokset Réseau Net 230 V 50 Hz 400 V 50 Hz 415 V 50 Hz 600 V 50 Hz 690 V 50 Hz 240 V 60 Hz 400 V 60 Hz 440 V 60 Hz 480 V 60 Hz 600 V 60 Hz Classe de température de l’armoire moyenne sur 24 h Temperature class average by 24 h Puissance admissible armoire Blokset Dc type 132 Ventilation forcée Power Blokset Type Dc 132 Ventilation with fan Puissance admissible armoire Blokset D/Dc type 132 Ventilation naturelle Power Blokset Type D/Dc 132 Natural ventilation Puissance Admissible armoire Blokset C type 134 Ventilation naturelle Power Blokset Type C 134 Natural ventilation 35° C 180 kVar 120 kVar 120 kVar 40° C 180 kVar (1) 120 kVar (1) 120 kVar (1) 45° C 180 kVar (1) 120 kVar (1) 120 kVar (1) 35° C 360 kVar 180 kVar 180 kVar 40° C 270 kVar (1) 180 kVar (1) 135 kVar (1) 45° C 270 kVar (1) 135 kVar (1) 135 kVar (1) 35° C 360 kVar 180 kVar 180 kVar 40° C 270 kVar (1) 180 kVar (1) 135 kVar (1) 45° C 270 kVar (1) 135 kVar (1) 135 kVar (1) 35° C 240 kVar 120 kVar 40° C 240 kVar (1) 120 kVar (1) 45° C 240 kVar (1) 120 kVar (1) 35° C 330 kVar 220 kVar 165 kVar 40° C 270 kVar (1) 220 kVar (1) 135 kVar (1) 45° C 270 kVar (1) 180 kVar (1) 135 kVar (1) 35° C 200 kVar 100 kVar 100 kVar 40° C 150 kVar (1) 100 kVar (1) 75 kVar (1) 45° C 150 kVar (1) 60 kVar (1) 60 kVar (1) 35° C 360 kVar 150 kVar 150 kVar 40° C 270 kVar (1) 150 kVar (1) 125 kVar (1) 45° C 270 kVar (1) 125 kVar (1) 125 kVar (1) 35° C 360 kVar 180 kVar 180 kVar 40° C 300 kVar (1) 180 kVar (1) 150 kVar (1) 45° C 300 kVar (1) 150 kVar (1) 150 kVar (1) 35° C 360 kVar 180 kVar 180 kVar 40° C 360 kVar (1) 180 kVar (1) 180 kVar (1) 45° C 360 kVar (1) 180 kVar (1) 180 kVar (1) 35° C 300 kVar 150 kVar 40° C 300 kVar (1) 150 kVar (1) 45° C 300 kVar (1) 150 kVar (1) non autorisé (2) impossible (2) non autorisé (2) impossible (2) Température > 45° C Temperature > 45° C non autorisé (2) impossible (2) (1) Les condensateurs utilisés doivent être sur-dimensionnés en tension selon le tableau ci-dessous (2) Pour des ambiantes supérieures à 45 °C, le régulateur Varlogic ne fonctionne plus: Guide Technique V9 / V9 Technical Guide (1) capacitors used must be ondimensionned in tension according to the table below, (2) for the ambient superior to 45 °C, the regulating Varlogic doesn't function anymore: 118 Installation de l’appareillage Switchgear Installation CONDENSATEURS SURDIMENSIONNES ON-DIMENSIONNES CAPACITORS CONDENSATEURS SURDIMENSIONNES ON-DIMENSIONNES CAPACITORS RESEAU NET TENSION VOLTAGE 230 V 50 Hz 230 V 400 V 50 Hz 470 V 415 V 50 Hz 470 V 600 V 50 Hz 690 V 690 V 50 Hz nous consulter, condensateurs spéciaux under consult, special capacitors 240 V 60 Hz 400 V 400 V 60 Hz 470 V 440 V 60 Hz 480 V 480 V 60 Hz 525 V 600 V 60 Hz 690 V Guide Technique V9 / V9 Technical Guide 119 Sommaire du chapitre Chapter contents 3.3. Blokset Mf / Mw Protection moteurs Motor protection 3.3.1. Tableaux de coordination et modularité ............................................... 123 Coordination and modularity tables 3.3.1.1. GV2-P .......................................................................................... 124 Type de coordination: 1 Coordination type: 1 3.3.1.2. GV2-P .......................................................................................... 126 Type de coordination: 2 Coordination type: 2 3.3.1.3. Etoile / Triangle (Y/D) STAR / DELTA (Y/D) Compact NS100-630z-MA .......................................................... 145 Type de coordination: 1 Coordination type: 1 Guide Technique V9 / V9 Technical Guide Etoile / Triangle (Y/D) STAR / DELTA (Y/D) Compact NS80H-MA .................................................................. 144 Type de coordination: 2 Coordination Type: 2 3.3.1.13. 2 sens de marche Reverse Compact NS80H-MA .................................................................. 142 Type de coordination: 1 Coordination type: 1 3.3.1.12. 2 sens de marche Reverse Compact NS80H-MA .................................................................. 140 Type de coordination: 2 Coordination type: 2 3.3.1.11. DOL (Démarrage direct) DOL (Direct On Line) Compact NS80H-MA .................................................................. 138 Type de coordination: 1 Coordination type: 1 3.3.1.10. DOL (Démarrage direct) DOL (Direct On Line) Compact NS80H-MA .................................................................. 136 Type de coordination: 2 Coordination type: 2 3.3.1.9. Etoile / Triangle (Y/D) STAR / DELTA (Y/D) Compact NS80H-MA .................................................................. 134 Type de coordination: 1 Coordination type: 1 3.3.1.8. Etoile / Triangle (Y/D) STAR / DELTA (Y/D) GV2-P .......................................................................................... 133 Type de coordination: 2 Coordination type: 2 3.3.1.7. 2 sens de Marche Reverse GV2-P .......................................................................................... 132 Type de coordination: 1 Coordination type: 1 3.3.1.6. 2 sens de Marche Reverse GV2-P .......................................................................................... 130 Type de coordination: 2 Coordination type: 2 3.3.1.5. DOL (Démarrage direct) DOL (Direct On Line) GV2-P .......................................................................................... 128 Type de coordination: 1 Coordination type: 1 3.3.1.4. DOL (Démarrage direct) DOL (Direct On Line) DOL (Démarrage direct) DOL (Direct On Line) 120 Sommaire du chapitre Chapter contents 3.3.1.14. Compact NS100-630z-MA .......................................................... 148 Type de coordination: 2 Coordination type: 2 3.3.1.15. Compact NS100-630l-MA ........................................................... 151 Type de coordination: 1 Coordination type: 1 3.3.1.16. Etoile / Triangle (Y/D) STAR / DELTA (Y/D) GV7 .............................................................................................. 170 Type de coordination: 2 Coordination Type: 2 3.3.1.25. 2 sens de marche Reverse GV7 .............................................................................................. 169 Type de coordination: 1 Coordination Type: 1 3.3.1.24. 2 sens de marche Reverse GV7 .............................................................................................. 167 Type de coordination: 2 Coordination Type: 2 3.3.1.23. DOL (Démarrage direct) DOL (Direct On Line) GV7 .............................................................................................. 165 Type de coordination: 1 Coordination Type: 1 3.3.1.22. DOL (Démarrage direct) DOL (Direct On Line) GV7 .............................................................................................. 163 Type de coordination: 2 Coordination Type: 2 3.3.1.21. Etoile / Triangle (Y/D) STAR / DELTA (Y/D) GV7 .............................................................................................. 161 Type de coordination: 1 Coordination Type: 1 3.3.1.20. Etoile / Triangle (Y/D) STAR / DELTA (Y/D) Compact NS100-630l-MA ........................................................... 159 Type de coordination: 2 Coordination Type: 2 3.3.1.19. 2 sens de marche Reverse Compact NS100-630l-MA ........................................................... 157 Type de coordination: 1 Coordination type: 1 3.3.1.18. 2 sens de marche Reverse (Compact NS100-630l-MA .......................................................... 154 Type de coordination: 2 Coordination type: 2 3.3.1.17. DOL (Démarrage direct) DOL (Direct On Line) Etoile / Triangle (Y/D) STAR / DELTA (Y/D) INTEGRAL ................................................................................... 171 Contacteurs-Disjoncteurs INTEGRALDOL (Démarrage direct) INTEGRAL contactors-circuit breakersDOL (Direct On Line) 3.3.1.26. INTEGRAL ................................................................................... 174 Contacteurs-Disjoncteurs INTEGRAL2 sens de marche INTEGRAL contactors-circuit breakersReverse 3.3.1.27. GV2-P .......................................................................................... 177 Type de coordination: 1 Coordination type: 1 3.3.1.28. GV2-P .......................................................................................... 177 Type de coordination: 2 Coordination type: 2 3.3.1.29. DOL monophasé (Démarrage direct) Single phase - DOL (Direct On Line) Compact NS80H-MA .................................................................. 178 Type de coordination: 1 Coordination type: 1 Guide Technique V9 / V9 Technical Guide DOL monophasé (Démarrage direct) Single phase - DOL (Direct On Line) DOL monophasé (Démarrage direct) Single phase - DOL (Direct On Line) 121 Sommaire du chapitre Chapter contents 3.3.1.30. Compact NS80H-MA .................................................................. 178 Type de coordination: 2 Coordination type: 2 3.3.2. DOL monophasé (Démarrage direct) Single phase - DOL (Direct On Line) Déclassement des appareils - AC3 ....................................................... 179 Starters derating - AC3 3.3.2.1. GV2-P .......................................................................................... 179 Type de coordination: 1-2 Coordination type: 1-2 3.3.2.2. Compact NS et GV7 ................................................................... 180 Type de coordination: 1-2 Coordination type: 1-2 3.3.2.3. Integral ........................................................................................ 184 Contacteurs - Disjoncteurs Integral Coordination totale Contactors - Integral Circuit breakersTotal coordination 3.3.3. Départ distribution en tiroir ................................................................... 184 Feeder in drawer 3.3.3.1. 3.3.4. Nombre de modules nécessaires ............................................. 184 Number of modules required Colonne arrivée Blokset Mw avec Masterpact NT ............................... 185 Blokset Mw incoming column with Masterpact NT Guide Technique V9 / V9 Technical Guide 122 Installation de l’appareillage Switchgear Installation Blokset Mf / Mw 3.3. Blokset Mf / Mw Protection moteurs Motor protection 3.3.1. Tableaux de coordination et modularité Coordination and modularity tables Blokset Type Mf et Mw Les GV7 peuvent être remplacés par les appareils NS100 / 250 associés à un déclencheur électronique protection moteur (à définir cas par cas). La modularité des associations avec NS + déclencheur est la même que celles définies avec les GV7. Guide Technique V9 / V9 Technical Guide Blokset Type Mf and Mw GV7 CB’s can be replaced by NS100 / 250 CB’s equipped with a electronic trip unit dedicated to motor protection (to be defined case per case). The number of modules of this kind of starter are the same than the ones given for GV7 CB’s. 123 Installation de l’appareillage Switchgear Installation 3.3.1.1. GV2-P Type de coordination: 1 - - - - - - - - - - - - - - - -DOL (Démarrage direct) Coordination type: 1 - - - - - - - - - - - - - - - - - - -DOL (Direct On Line) 400/415 V TeSys GV2-P TeSys Puissance moteur Power motor P (kW) I (A) 0,37 0,98 0,55 1,5 0,75 2 1,1 2,5 1,5 3,5 2,2 5 3 6,5 4 8,4 5,5 11 7,5 14,8 9 18,1 11 21 15 28,5 Pdc BC Icu (kA) Rms (kA) 50 50 50 50 50 50 50 50 15 15 15 15 10 Type de coordination: 1 Coordination type: 1 TeSys Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV2-P05 0,63...1 GV2-P06 1...1,6 GV2-P07 1,6...2,5 GV2-P08 2,5...4 GV2-P08 2,5...4 GV2-P10 4...6,3 GV2-P14 6...10 GV2-P14 6...10 GV2-P16 9...14 GV2-P20 13...18 GV2-P21 17...23 GV2-P22 20...25 GV2-P32 24...32 GV2-P 440 V TeSys TeSys Puissance moteur Power motor P (kW) I (A) 0,37 0,99 0,55 1,36 0,75 1,68 1,1 2,37 1,5 3,06 2,2 4,42 3 5,77 4 7,9 5,5 10,4 7,5 13,7 9 16,9 11 20,1 15 26,5 Pdc BC Icu (kA) Rms (kA) 50 50 50 50 50 50 50 15 8 8 8 6 6 Guide Technique V9 / V9 Technical Guide TeSys TeSys Nb modules Nbr of modules Contacteur Contactor LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K09 LC1-K09 LC1-K12 LC1-D18 LC1-D25 LC1-D25 LC1-D32 Mf Mw 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Type de coordination: 1 Coordination type: 1 TeSys Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV2-P05 0,63...1 GV2-P06 1...1,6 GV2-P07 1,6...2,5 GV2-P07 1,6...2,5 GV2-P08 2,5...4 GV2-P10 4...6,3 GV2-P10 4...6,3 GV2-P14 6...10 GV2-P16 9...14 GV2-P20 13...18 GV2-P20 13...18 GV2-P21 17...23 GV2-P32 24...32 DOL (Démarrage direct) DOL (Direct On Line) TeSys DOL (Démarrage direct) DOL (Direct On Line) TeSys Nb modules Nbr of modules Contacteur Contactor LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K09 LC1-K12 LC1-D18 LC1-D18 LC1-D25 LC1-D32 Mf Mw 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 124 Installation de l’appareillage Switchgear Installation GV2-P 500 V TeSys TeSys Puissance moteur Power motor P (kW) I (A) 0,37 1 0,55 1,21 0,75 1,5 1,1 2 1,5 2,6 2,2 3,8 3 5 4 6,5 5,5 9 7,5 12 9 13,9 11 18,4 15 23 18,5 28,5 Pdc BC Icu (kA) Rms (kA) 50 50 50 50 50 50 50 10 10 6 6 4 4 4 Guide Technique V9 / V9 Technical Guide Type de coordination: 1 Coordination type: 1 TeSys Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV2-P06 1...1,6 GV2-P06 1...1,6 GV2-P06 1...1,6 GV2-P07 1,6...2,5 GV2-P08 2,5...4 GV2-P08 2,5...4 GV2-P10 4...6,3 GV2-P14 6...10 GV2-P14 6...10 GV2-P16 9...14 GV2-P20 13...18 GV2-P21 17...23 GV2-P22 20...25 GV2-P32 24...32 TeSys DOL (Démarrage direct) DOL (Direct On Line) TeSys Nb modules Nbr of modules Contacteur Contactor LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K09 LC1-K09 LC1-K12 LC1-D18 LC1-D25 LC1-D25 LC1-D32 Mf Mw 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 125 Installation de l’appareillage Switchgear Installation 3.3.1.2. GV2-P Type de coordination: 2 - - - - - - - - - - - - - - - -DOL (Démarrage direct) Coordination type: 2 - - - - - - - - - - - - - - - - - - -DOL (Direct On Line) GV2-P 400/415 V TeSys TeSys Puissance Moteur Power motor P (kW) I (A) Pdc BC Icu (kA) Rms (kA) Type de coordination: 2 Coordination type: 2 TeSys Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) TeSys DOL (Démarrage direct) DOL (Direct On Line) TeSys Nb modules Nbr of modules Contacteur Contactor Mf Mw 0,37 0,98 130 GV2-P05 0,63…1 LC1-D09 3 3 0,55 1,5 130 GV2-P06 1…1,6 LC1-D09 3 3 0,75 2 130 GV2-P07 1,6…2,5 LC1-D09 3 3 1,1 2,5 130 GV2-P08 2,5…4 LC1-D09 3 3 1,5 3,5 130 GV2-P08 2,5…4 LC1-D09 3 3 2,2 5 130 GV2-P10 4…6,3 LC1-D09 3 3 3 6,5 130 GV2-P14 6…10 LC1-D09 3 3 4 8,4 130 GV2-P14 6…10 LC1-D18 3 3 5,5 11 130 GV2-P16 9…14 LC1-D25 3 3 7,5 14,8 50 GV2-P20 13…18 LC1-D25 3 3 9 18,1 50 GV2-P21 17..23 LC1-D32 3 3 11 21 50 GV2-P22 20..25 LC1-D40 3 6 15 28,5 50 GV2-P32 24…32 LC1-D40 3 6 GV2-P 440 V TeSys TeSys Puissance Moteur Power motor P (kW) I (A) Pdc BC Icu (kA) Rms (kA) Type de coordination: 2 Coordination type: 2 TeSys Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) TeSys DOL (Démarrage direct) DOL (Direct On Line) TeSys Nb modules Nbr of modules Contacteur Contactor Mf Mw 0,37 0,99 130 GV2-P05 0,63…1 LC1-D09 3 3 0,55 1,36 130 GV2-P06 1…1,6 LC1-D09 3 3 0,75 1,68 130 GV2-P07 1,6…2,5 LC1-D09 3 3 1,1 2,37 130 GV2-P07 1,6…2,5 LC1-D09 3 3 1,5 3,06 130 GV2-P08 2,5…4 LC1-D09 3 3 2,2 4,42 130 GV2-P10 4…6,3 LC1-D09 3 3 3 5,77 130 GV2-P10 4…6,3 LC1-D09 3 3 4 7,9 130 GV2-P14 6…10 LC1-D18 3 3 5,5 10,4 130 GV2-P16 9…14 LC1-D25 3 3 7,5 13,7 130 GV2-P16 9…14 LC1-D25 3 3 9 16,9 50 GV2-P20 13…18 LC1-D32 3 3 11 20,1 50 GV2-P21 17..23 LC1-D40 3 6 15 26,5 50 GV2-P32 24…32 LC1-D40 3 6 Guide Technique V9 / V9 Technical Guide 126 Installation de l’appareillage Switchgear Installation GV2-P 500 V TeSys TeSys Puissance Moteur Power motor P (kW) I (A) Pdc BC Icu (kA) Rms (kA) Type de coordination: 2 Coordination type: 2 TeSys Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) TeSys DOL (Démarrage direct) DOL (Direct On Line) TeSys Nb modules Nbr of modules Contacteur Contactor Mf Mw 0,37 1 130 GV2-P06 1…1,6 LC1-D09 3 3 0,55 1,21 130 GV2-P06 1…1,6 LC1-D09 3 3 0,75 1,5 130 GV2-P06 1…1,6 LC1-D09 3 3 1,1 2 130 GV2-P07 1,6…2,5 LC1-D09 3 3 1,5 2,6 130 GV2-P08 2,5…4 LC1-D09 3 3 2,2 3,8 130 GV2-P08 2,5…4 LC1-D09 3 3 3 5 130 GV2-P10 4…6,3 LC1-D09 3 3 4 6,5 50 GV2-P14 6…10 LC1-D12 3 3 5,5 9 50 GV2-P14 6…10 LC1-D18 3 3 7,5 12 42 GV2-P16 9…14 LC1-D25 3 3 9 13,9 42 GV2-P16 9…14 LC1-D25 3 3 11 18,4 10 GV2-P21 17..23 LC1-D32 3 3 15 23 10 GV2-P22 20..25 LC1-D40 3 6 18,5 28,5 10 GV2-P32 24…32 LC1-D40 3 6 Guide Technique V9 / V9 Technical Guide 127 Installation de l’appareillage Switchgear Installation 3.3.1.3. GV2-P Type de coordination: 1 - - - - - - - - - - - - - - - -2 sens de Marche Coordination type: 1 - - - - - - - - - - - - - - - - - - -Reverse 400/415 V TeSys GV2-P TeSys Puissance Moteur Power motor P (kW) I (A) 0,37 0,98 0,55 1,5 0,75 2 1,1 2,5 1,5 3,5 2,2 5 3 6,5 4 8,4 5,5 11 7,5 14,8 9 18,1 11 21 15 28,5 Pdc BC Icu (kA) Rms (kA) 50 50 50 50 50 50 50 50 15 15 15 15 10 Type de coordination: 1 Coordination type: 1 TeSys Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV2-P05 0,63...1 GV2-P06 1...1,6 GV2-P07 1,6...2,5 GV2-P08 2,5...4 GV2-P08 2,5...4 GV2-P10 4...6,3 GV2-P14 6...10 GV2-P14 6...10 GV2-P16 9...14 GV2-P20 13...18 GV2-P21 17...23 GV2-P22 20...25 GV2-P32 24...32 GV2-P 440 V TeSys TeSys Puissance moteur Power motor P (kW) I (A) 0,37 0,99 0,55 1,36 0,75 1,68 1,1 2,37 1,5 3,06 2,2 4,42 3 5,77 4 7,9 5,5 10,4 7,5 13,7 9 16,9 11 20,1 15 26,5 Pdc BC Icu (kA) Rms (kA) 50 50 50 50 50 50 50 15 8 8 8 6 6 Guide Technique V9 / V9 Technical Guide TeSys 2 sens de Marche Reverse TeSys Nb modules Nbr of modules Contacteur Contactor 2 x LC1-K06 2 x LC1-K06 2 x LC1-K06 2 x LC1-K06 2 x LC1-K06 2 x LC1-K06 2 x LC1-K09 2 x LC1-K09 2 x LC1-K12 2 x LC1-D18 2 x LC1-D25 2 x LC1-D25 2 x LC1-D32 Mf Mw 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Type de coordination: 1 Coordination type: 1 TeSys Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV2-P05 0,63...1 GV2-P06 1...1,6 GV2-P07 1,6...2,5 GV2-P07 1,6...2,5 GV2-P08 2,5...4 GV2-P10 4...6,3 GV2-P10 4...6,3 GV2-P14 6...10 GV2-P16 9...14 GV2-P20 13...18 GV2-P20 13...18 GV2-P21 17...23 GV2-P32 24...32 TeSys 2 sens de Marche Reverse TeSys Nb modules Nbr of modules Contacteur Contactor 2 x LC1-K06 2 x LC1-K06 2 x LC1-K06 2 x LC1-K06 2 x LC1-K06 2 x LC1-K06 2 x LC1-K06 2 x LC1-K09 2 x LC1-K12 2 x LC1-D18 2 x LC1-D18 2 x LC1-D25 2 x LC1-D32 Mf Mw 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 128 Installation de l’appareillage Switchgear Installation GV2-P 500 V TeSys TeSys Puissance moteur Power motor P (kW) I (A) 0,37 1 0,55 1,21 0,75 1,5 1,1 2 1,5 2,6 2,2 3,8 3 5 4 6,5 5,5 9 7,5 12 9 13,9 11 18,4 15 23 18,5 28,5 Pdc BC Icu (kA) Rms (kA) 50 50 50 50 50 50 50 10 10 6 6 4 4 4 Guide Technique V9 / V9 Technical Guide Type de coordination: 1 Coordination type: 1 TeSys Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV2-P06 1...1,6 GV2-P06 1...1,6 GV2-P06 1...1,6 GV2-P07 1,6...2,5 GV2-P08 2,5...4 GV2-P08 2,5...4 GV2-P10 4...6,3 GV2-P14 6...10 GV2-P14 6...10 GV2-P16 9...14 GV2-P20 13...18 GV2-P21 17...23 GV2-P22 20...25 GV2-P32 24...32 TeSys 2 sens de Marche Reverse TeSys Nb modules Nbr of modules Contacteur Contactor 2 x LC1-K06 2 x LC1-K06 2 x LC1-K06 2 x LC1-K06 2 x LC1-K06 2 x LC1-K06 2 x LC1-K06 2 x LC1-K09 2 x LC1-K09 2 x LC1-K12 2 x LC1-D18 2 x LC1-D25 2 x LC1-D25 2 x LC1-D32 Mf Mw 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 129 Installation de l’appareillage Switchgear Installation 3.3.1.4. GV2-P Type de coordination: 2 - - - - - - - - - - - - - - - -2 sens de Marche Coordination type: 2 - - - - - - - - - - - - - - - - - - -Reverse GV2-P 400/415 V TeSys TeSys Puissance Moteur Power motor P (kW) I (A) Pdc BC Icu (kA) Rms (kA) Type de coordination: 2 Coordination type: 2 TeSys Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) TeSys 2 sens de Marche Reverse TeSys Nb modules Nbr of modules Contacteur Contactor Mf Mw 0,37 0,98 130 GV2-P05 0,63…1 2xLC1-D09 3 3 0,55 1,5 130 GV2-P06 1…1,6 2xLC1-D09 3 3 0,75 2 130 GV2-P07 1,6…2,5 2xLC1-D09 3 3 1,1 2,5 130 GV2-P08 2,5…4 2xLC1-D09 3 3 1,5 3,5 130 GV2-P08 2,5…4 2xLC1-D09 3 3 2,2 5 130 GV2-P10 4…6,3 2xLC1-D09 3 3 3 6,5 130 GV2-P14 6…10 2xLC1-D09 3 3 4 8,4 130 GV2-P14 6…10 2xLC1-D18 3 3 5,5 11 130 GV2-P16 9…14 2xLC1-D25 3 3 7,5 14,8 50 GV2-P20 13…18 2xLC1-D25 3 3 9 18,1 50 GV2-P21 17..23 2xLC1-D32 3 3 11 21 50 GV2-P22 20..25 2xLC1-D40 6 6 15 28,5 50 GV2-P32 24…32 2xLC1-D40 6 6 GV2-P 440 V TeSys TeSys Puissance Moteur Power motor P (kW) I (A) Pdc BC Icu (kA) Rms (kA) Type de coordination: 2 Coordination type: 2 TeSys Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) TeSys 2 sens de Marche Reverse TeSys Nb modules Nbr of modules Contacteur Contactor Mf Mw 0,37 0,99 130 GV2-P05 0,63…1 2xLC1-D09 3 3 0,55 1,36 130 GV2-P06 1…1,6 2xLC1-D09 3 3 0,75 1,68 130 GV2-P07 1,6…2,5 2xLC1-D09 3 3 1,1 2,37 130 GV2-P07 1,6…2,5 2xLC1-D09 3 3 1,5 3,06 130 GV2-P08 2,5…4 2xLC1-D09 3 3 2,2 4,42 130 GV2-P10 4…6,3 2xLC1-D09 3 3 3 5,77 130 GV2-P10 4…6,3 2xLC1-D09 3 3 4 7,9 130 GV2-P14 6…10 2xLC1-D18 3 3 5,5 10,4 130 GV2-P16 9…14 2xLC1-D25 3 3 7,5 13,7 130 GV2-P16 9…14 2xLC1-D25 3 3 9 16,9 50 GV2-P20 13…18 2xLC1-D32 3 3 11 20,1 50 GV2-P21 17..23 2xLC1-D40 6 6 15 26,5 50 GV2-P32 24…32 2xLC1-D40 6 6 Guide Technique V9 / V9 Technical Guide 130 Installation de l’appareillage Switchgear Installation GV2-P 500 V TeSys TeSys Puissance Moteur Power motor P (kW) I (A) Pdc BC Icu (kA) Rms (kA) Type de coordination: 2 Coordination type: 2 TeSys Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) TeSys 2 sens de Marche Reverse TeSys Nb modules Nbr of modules Contacteur Contactor Mf Mw 0,37 1 130 GV2-P06 1…1,6 2xLC1-D09 3 6 0,55 1,21 130 GV2-P06 1…1,6 2xLC1-D09 3 6 0,75 1,5 130 GV2-P06 1…1,6 2xLC1-D09 3 6 1,1 2 130 GV2-P07 1,6…2,5 2xLC1-D09 3 6 1,5 2,6 130 GV2-P08 2,5…4 2xLC1-D09 3 6 2,2 3,8 130 GV2-P08 2,5…4 2xLC1-D09 3 6 3 5 130 GV2-P10 4…6,3 2xLC1-D09 3 6 4 6,5 50 GV2-P14 6…10 2xLC1-D12 3 6 5,5 9 50 GV2-P14 6…10 2xLC1-D18 3 6 7,5 12 42 GV2-P16 9…14 2xLC1-D25 3 6 9 13,9 42 GV2-P16 9…14 2xLC1-D25 3 6 11 18,4 10 GV2-P21 17..23 2xLC1-D32 3 6 15 23 10 GV2-P22 20..25 2xLC1-D40 6 6 18,5 28,5 10 GV2-P32 24…32 2xLC1-D40 6 6 Guide Technique V9 / V9 Technical Guide 131 Installation de l’appareillage Switchgear Installation 3.3.1.5. GV2-P Type de coordination: 1 - - - - - - - - - - - - - - - -Etoile / Triangle (Y/∆) Coordination type: 1 - - - - - - - - - - - - - - - - - - -STAR / DELTA (Y/∆) 400/415 V TeSys GV2-P TeSys Puissance Moteur Power motor P (kW) I (A) 1,5 3,5 2,2 5 3 6,5 4 8,4 5,5 11 7,5 14,8 9 18,1 11 21 Pdc BC Icu (kA) Rms (kA) 50 50 50 50 15 15 15 15 TeSys Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV2-P08 2,5...4 GV2-P10 4...6,3 GV2-P14 6...10 GV2-P14 6...10 GV2-P16 9...14 GV2-P20 13...18 GV2-P21 17...23 GV2-P22 20...25 GV2-P 440 V TeSys TeSys Puissance moteur Power motor P (kW) I (A) 1,5 3,06 2,2 4,42 3 5,77 4 7,9 5,5 10,4 7,5 13,7 9 16,9 11 20,1 Pdc BC Icu (kA) Rms (kA) 50 50 50 15 8 8 8 6 Guide Technique V9 / V9 Technical Guide Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Type de coordination: 1 Coordination type: 1 TeSys TeSys Nb modules Nbr of modules Contacteur Contactor 3 x LC1-K06 3 x LC1-K06 3 x LC1-K06 3 x LC1-K06 3 x LC1-K06 3 x LC1-K09 3 x LC1-D12 3 x LC1-D12 Mf Mw 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Type de coordination: 1 Coordination type: 1 TeSys Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV2-P08 2,5...4 GV2-P10 4...6,3 GV2-P10 4...6,3 GV2-P14 6...10 GV2-P16 9...14 GV2-P20 13...18 GV2-P20 13...18 GV2-P21 17...23 TeSys TeSys Nb modules Nbr of modules Contacteur Contactor 3 x LC1-K06 3 x LC1-K06 3 x LC1-K06 3 x LC1-K06 3 x LC1-K06 3 x LC1-K09 3 x LC1-D12 3 x LC1-D12 Mf Mw 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 132 Installation de l’appareillage Switchgear Installation 3.3.1.6. GV2-P Type de coordination: 2 - - - - - - - - - - - - - - - -Etoile / Triangle (Y/∆) Coordination type: 2 - - - - - - - - - - - - - - - - - - -STAR / DELTA (Y/∆) GV2-P 400/415 V TeSys TeSys Puissance Moteur Power motor P (kW) I (A) Pdc BC Icu (kA) Rms (kA) Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Type de coordination: 2 Coordination type: 2 TeSys TeSys Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) TeSys Nb modules Nbr of modules Contacteur Contactor Mf Mw 1,5 3,5 130 GV2-P08 2,5...4 3 x LC1-D09 6 6 2,2 5 130 GV2-P10 4...6,3 3 x LC1-D18 6 6 3 6,5 130 GV2-P14 6...10 3 x LC1-D18 6 6 4 8,4 130 GV2-P14 6...10 3 x LC1-D18 6 6 5,5 11 130 GV2-P16 9...14 3 x LC1-D25 6 6 7,5 14,8 50 GV2-P20 13...18 3 x LC1-D25 6 6 9 18,1 50 GV2-P21 17...23 3 x LC1-D32 6 6 11 21 50 GV2-P22 20...25 3 x LC1-D40 6 9 GV2-P 440 V TeSys TeSys Puissance Moteur Power motor P (kW) I (A) Pdc BC Icu (kA) Rms (kA) Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Type de coordination: 2 Coordination type: 2 TeSys TeSys Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) TeSys Nb modules Nbr of modules Contacteur Contactor Mf Mw 1,5 3,06 130 GV2-P08 2,5...4 3 x LC1-D09 6 6 2,2 4,42 130 GV2-P10 4...6,3 3 x LC1-D18 6 6 3 5,77 130 GV2-P10 4...6,3 3 x LC1-D18 6 6 4 7,9 130 GV2-P14 6...10 3 x LC1-D18 6 6 5,5 10,4 50 GV2-P16 9...14 3 x LC1-D25 6 6 7,5 13,7 50 GV2-P16 9...14 3 x LC1-D25 6 6 9 16,9 20 GV2-P20 13...18 3 x LC1-D32 6 6 11 20,1 20 GV2-P21 17...23 3 x LC1-D40 6 9 Guide Technique V9 / V9 Technical Guide 133 Installation de l’appareillage Switchgear Installation Compact NS80H-MA 3.3.1.7. Type de coordination: 1 - - - - - - - - - - - - - - - -DOL (Démarrage direct) Coordination type: 1 - - - - - - - - - - - - - - - - - - -DOL (Direct On Line) Démarrage: Normal Start-up: Normal 400/415 V TeSys Compact NS80H-MA TeSys Puissance Moteur Power motor P (kW) I (A) 0,37 0,98 0,55 1,5 0,75 2 1,1 2,5 1,5 3,5 2,2 5 3 6,5 4 8,4 5,5 11 7,5 14,8 9 18,1 11 21 15 28,5 18,5 35 22 42 30 57 37 69 Pdc BC Icu (kA) Rms (kA) 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 Guide Technique V9 / V9 Technical Guide TeSys Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA Cal (A) Rat (A) 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 12,5 25 25 25 50 50 50 80 80 Type de coordination: 1 Coordination type: 1 TeSys Contacteurs Contactor Type Type LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D12 LC1-D18 LC1-D18 LC1-D25 LC1-D32 LC1-D38 LC1-D50 LC1-D65 LC1-D80 DOL (Démarrage direct) DOL (Direct On Line) TeSys Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LRD-05 0,63...1 LRD-06 1...1,7 LRD-07 1,6...2,5 LRD-08 2,5...4 LRD-08 2,5...4 LRD-10 4...6 LRD-12 5,5...8 LRD-14 7...10 LRD-16 9...13 LRD-21 12...18 LRD-22 16...24 LRD-22 16...24 LRD-32 23...32 LRD-35 30...38 LRD-3357 37...50 LRD-3359 48...65 LRD-3363 63...80 TeSys Nb modules Nbr of modules Mf Mw 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 6 3 6 3 6 134 Installation de l’appareillage Switchgear Installation Compact NS80H-MA 440 V TeSys TeSys Puissance Moteur Power motor P (kW) I (A) 0,37 0,99 0,55 1,36 0,75 1,68 1,1 2,37 1,5 3,06 2,2 4,42 3 5,77 4 7,9 5,5 10,4 7,5 13,7 9 16,9 11 20,1 15 26,5 18,5 32,8 22 39 30 51,5 37 64 45 76 Pdc BC Icu (kA) Rms (kA) 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 TeSys Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA Cal (A) Rat (A) 2,5 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 25 25 25 50 50 50 80 80 80 Compact NS80H-MA 500 V TeSys TeSys Puissance Moteur Power motor P (kW) I (A) 0,37 1 0,55 1,21 0,75 1,5 1,1 2 1,5 2,6 Pdc BC Icu (kA) Rms (kA) 25 25 25 25 25 TeSys Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA Cal (A) Rat (A) 2,5 2,5 2,5 2,5 6,3 Type de coordination: 1 Coordination type: 1 TeSys Contacteurs Contactor Type Type LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D12 LC1-D18 LC1-D18 LC1-D25 LC1-D32 LC1-D38 LC1-D40 LC1-D65 LC1-D65 LC1-D80 DOL (Démarrage direct) DOL (Direct On Line) TeSys Type de coordination: 1 Coordination type: 1 TeSys Contacteurs Contactor Type Type LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 TeSys Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LRD-05 0,63...1 LRD-06 1...1,7 LRD-07 1,6...2,5 LRD-07 1,6...2,5 LRD-08 2,5...4 LRD-10 4...6 LRD-10 4...6 LRD-14 7...10 LRD-16 9...13 LRD-21 12...18 LRD-21 12...18 LRD-22 16...24 LRD-32 23...32 LRD-35 30...38 LRD-3357 37...50 LRD-3359 48...65 LRD-3359 48...65 LRD-3363 63...80 Nb modules Nbr of modules Mf Mw 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 6 3 6 3 6 3 6 DOL (Démarrage direct) DOL (Direct On Line) TeSys TeSys Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LRD-06 1...1,7 LRD-06 1...1,7 LRD-06 1...1,7 LRD-07 1,6...2,5 LRD-08 2,5...4 Nb modules Nbr of modules 3 3 3 3 3 Mf Mw 3 3 3 3 3 3 2,2 3,8 25 NS80H-MA 6,3 LC1-D09 LRD-08 2,5...4 3 3 5 25 NS80H-MA 6,3 LC1-D09 LRD-10 4...6 3 3 4 6,5 25 NS80H-MA 12,5 LC1-D09 LRD-12 5,5...8 3 3 5,5 9 25 NS80H-MA 12,5 LC1-D09 LRD-14 7...10 3 3 7,5 12 25 NS80H-MA 25 LC1-D12 LRD-16 9...13 3 3 9 13,9 25 NS80H-MA 25 LC1-D18 LRD-21 12...18 3 3 11 18,4 25 NS80H-MA 25 LC1-D25 LRD-22 16...24 3 3 15 23 25 NS80H-MA 50 LC1-D32 LRD-22 16...24 3 3 18,5 28,5 25 NS80H-MA 50 LC1-D32 LRD-35 23...32 3 3 22 33 25 NS80H-MA 50 LC1-D40 LRD-3355 30...40 3 6 30 45 25 NS80H-MA 50 LC1-D50 LRD-3357 37...50 3 6 37 55 25 NS80H-MA 80 LC1-D65 LRD-3359 48...65 3 6 Guide Technique V9 / V9 Technical Guide 135 Installation de l’appareillage Switchgear Installation 3.3.1.8. Compact NS80H-MA Type de coordination: 2 - - - - - - - - - - - - - - - -DOL (Démarrage direct) Coordination type: 2 - - - - - - - - - - - - - - - - - - -DOL (Direct On Line) Démarrage: Normal Start-up: Normal Compact NS80H-MA 400/415 V TeSys TeSys Puissance Moteur Power motor P (kW) I (A) TeSys Type de coordination: 2 Coordination type: 2 TeSys Pdc BC Icu (kA) Rms (kA) Disjoncteurs Circuit Breaker Type Type Cal (A) Rat (A) Contacteurs Contactor Type Type DOL (Démarrage direct) DOL (Direct On Line) TeSys Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) TeSys Nb modules Nbr of modules Mf Mw 0,37 0.98 70 NS80H-MA 2,5 LC1-D09 LRD-05 0,63…1 3 3 0,55 1.5 70 NS80H-MA 2,5 LC1-D09 LRD-06 1…1,7 3 3 0,75 2 70 NS80H-MA 2,5 LC1-D09 LRD-07 1,6…2,5 3 3 1,1 2,5 70 NS80H-MA 6,3 LC1-D18 LRD-08 2,5…4 3 3 1,5 3,5 70 NS80H-MA 6,3 LC1-D18 LRD-08 2,5…4 3 3 2,2 5 70 NS80H-MA 6,3 LC1-D25 LRD-10 4…6 3 3 3 6,5 70 NS80H-MA 12,5 LC1-D32 LRD-12 5,5…8 3 3 4 8,4 70 NS80H-MA 12,5 LC1-D32 LRD-14 7…10 3 3 5,5 11 70 NS80H-MA 12,5 LC1-D32 LRD-16 9…13 3 3 7,5 14,8 70 NS80H-MA 25 LC1-D32 LRD-21 12…18 3 3 9 18,1 70 NS80H-MA 25 LC1-D40 LRD-3322 17..25 3 6 11 21 70 NS80H-MA 25 LC1-D40 LRD-3322 17..25 3 6 15 28,5 70 NS80H-MA 50 LC1-D40 LRD-3353 23…32 3 6 18,5 35 70 NS80H-MA 50 LC1-D50 LRD-3355 30…40 3 6 22 42 70 NS80H-MA 50 LC1-D50 LRD-3357 37…50 3 6 30 57 70 NS80H-MA 80 LC1-D65 LRD-3359 48…65 3 6 37 69 70 NS80H-MA 80 LC1-D80 LRD-3363 63…80 3 6 Guide Technique V9 / V9 Technical Guide 136 Installation de l’appareillage Switchgear Installation Compact NS80H-MA 440 V TeSys TeSys Puissance Moteur Power motor P (kW) I (A) TeSys Type de coordination: 2 Coordination type: 2 TeSys Pdc BC Icu (kA) Rms (kA) Disjoncteurs Circuit Breaker Type Type Cal (A) Rat (A) Contacteurs Contactor Type Type DOL (Démarrage direct) DOL (Direct On Line) TeSys TeSys Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) Nb modules Nbr of modules Mf Mw 0,37 0,99 65 NS80H-MA 2,5 LC1-D09 LRD-05 0,63...1 3 0,55 1,36 65 NS80H-MA 2,5 LC1-D09 LRD-06 1…1,7 3 3 0,75 1,68 65 NS80H-MA 2,5 LC1-D09 LRD-07 1,6…2,5 3 3 1,1 2,37 65 NS80H-MA 2,5 LC1-D09 LRD-07 1,6…2,5 3 3 1,5 3,06 65 NS80H-MA 6,3 LC1-D18 LRD-08 2,5…4 3 3 2,2 4,42 65 NS80H-MA 6,3 LC1-D25 LRD-10 4…6 3 3 3 5,77 65 NS80H-MA 6,3 LC1-D25 LRD-10 4…6 3 3 4 7,9 65 NS80H-MA 12,5 LC1-D32 LRD-14 7…10 3 3 5,5 10,4 65 NS80H-MA 12,5 LC1-D32 LRD-16 9…13 3 3 7,5 13,7 65 NS80H-MA 25 LC1-D32 LRD-21 12…18 3 3 9 16,9 65 NS80H-MA 25 LC1-D38 LRD-21 12…18 3 3 11 20,1 65 NS80H-MA 25 LC1-D40 LRD-3322 17..25 3 6 15 26,5 65 NS80H-MA 50 LC1-D40 LRD-3353 23…32 3 6 18,5 32,8 65 NS80H-MA 50 LC1-D50 LRD-3355 30...40 3 6 22 39 65 NS80H-MA 50 LC1-D50 LRD-3357 37...50 3 6 30 51,5 65 NS80H-MA 80 LC1-D65 LRD-3359 48...65 3 6 37 64 65 NS80H-MA 80 LC1-D80 LRD-3359 48...65 3 9 45 76 65 NS80H-MA 80 LC1-D80 LRD-3363 63...80 3 6 Compact NS80H-MA 500 V TeSys TeSys Puissance Moteur Power motor P (kW) I (A) Pdc BC Icu (kA) Rms (kA) TeSys Disjoncteurs Circuit Breaker Type Type Type de coordination: 2 Coordination type: 2 TeSys Cal (A) Rat (A) Contacteurs Contactor Type Type 3 DOL (Démarrage direct) DOL (Direct On Line) TeSys Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) TeSys Nb modules Nbr of modules Mf Mw 0,37 1 25 NS80H-MA 1,5 LC1-D09 LRD-06 1…1,7 3 3 0,55 1,21 25 NS80H-MA 2,5 LC1-D09 LRD-06 1…1,7 3 3 0,75 1,5 25 NS80H-MA 2,5 LC1-D09 LRD-06 1…1,7 3 3 1,1 2 25 NS80H-MA 2,5 LC1-D09 LRD-07 1,6…2,5 3 3 1,5 2,6 25 NS80H-MA 6,3 LC1-D18 LRD-08 2,5…4 3 3 2,2 3,8 25 NS80H-MA 6,3 LC1-D18 LRD-08 2,5…4 3 3 3 5 25 NS80H-MA 6,3 LC1-D25 LRD-10 4…6 3 3 4 6,5 25 NS80H-MA 12,5 LC1-D32 LRD-12 5,5…8 3 3 5,5 9 25 NS80H-MA 12,5 LC1-D32 LRD-14 7…10 3 3 7,5 12 25 NS80H-MA 12,5 LC1-D32 LRD-16 9…13 3 3 9 13,9 25 NS80H-MA 25 LC1-D32 LRD-21 12…18 3 3 11 18,4 25 NS80H-MA 25 LC1-D40 LRD-3322 17..25 3 6 15 23 25 NS80H-MA 25 LC1-D40 LRD-3322 17..25 3 6 18,5 28,5 25 NS80H-MA 50 LC1-D40 LRD-3353 23…32 3 6 22 33 25 NS80H-MA 50 LC1-D50 LRD-3355 30…40 3 6 30 45 25 NS80H-MA 50 LC1-D50 LRD-3357 37...50 3 6 37 55 25 NS80H-MA 80 LC1-D65 LRD-3359 48...65 3 6 Guide Technique V9 / V9 Technical Guide 137 Installation de l’appareillage Switchgear Installation Compact NS80H-MA 3.3.1.9. Type de coordination: 1 - - - - - - - - - - - - - - - -2 sens de marche Coordination type: 1 - - - - - - - - - - - - - - - - - - -Reverse Démarrage: Normal Start-up: Normal 400/415 V TeSys Compact NS80H-MA TeSys Puissance Moteur Power motor P (kW) I (A) 0,37 0,98 0,55 1,5 0,75 2 1,1 2,5 1,5 3,5 2,2 5 3 6,5 4 8,4 5,5 11 7,5 14,8 9 18,1 11 21 15 28,5 18,5 35 22 42 30 57 37 69 Pdc BC Icu (kA) Rms (kA) 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 TeSys Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA Cal (A) Rat (A) 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 12,5 25 25 25 50 50 50 80 80 Compact NS80H-MA 440 V TeSys TeSys Puissance Moteur Power motor P (kW) I (A) 0,37 0,99 0,55 1,36 0,75 1,68 1,1 2,37 1,5 3,06 2,2 4,42 3 5,77 4 7,9 5,5 10,4 7,5 13,7 9 16,9 11 20,1 15 26,5 18,5 32,8 22 39 30 51,5 37 64 45 76 Pdc BC Icu (kA) Rms (kA) 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 Guide Technique V9 / V9 Technical Guide TeSys Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA Cal (A) Rat (A) 2,5 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 25 25 25 50 50 50 80 80 80 Type de coordination: 1 Coordination type: 1 TeSys Contacteurs Contactor Type Type 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D12 2 x LC1-D18 2 x LC1-D18 2 x LC1-D25 2 x LC1-D32 2 x LC1-D38 2 x LC1-D50 2 x LC1-D65 2 x LC1-D80 TeSys TeSys TeSys Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LRD-05 0,63...1 LRD-06 1...1,7 LRD-07 1,6...2,5 LRD-08 2,5...4 LRD-08 2,5...4 LRD-10 4...6 LRD-12 5,5...8 LRD-14 7...10 LRD-16 9...13 LRD-21 12...18 LRD-22 16...24 LRD-22 16...24 LRD-32 23...32 LRD-35 30...38 LRD-3357 37...50 LRD-3359 48...65 LRD-3363 63...80 Type de coordination: 1 Coordination type: 1 Contacteurs Contactor Type Type 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D12 2 x LC1-D18 2 x LC1-D18 2 x LC1-D25 2 x LC1-D32 2 x LC1-D38 2 x LC1-D40 2 x LC1-D65 2 x LC1-D65 2 x LC1-D80 2 sens de marche Reverse Nb modules Nbr of modules Mf Mw 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 6 9 6 9 6 9 2 sens de marche Reverse TeSys Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LRD-05 0,63...1 LRD-06 1...1,7 LRD-07 1,6...2,5 LRD-07 1,6...2,5 LRD-08 2,5...4 LRD-10 4...6 LRD-10 4...6 LRD-14 7...10 LRD-16 9...13 LRD-21 12...18 LRD-21 12...18 LRD-22 16...24 LRD-32 23...32 LRD-35 30...38 LRD-3357 37...50 LRD-3359 48...65 LRD-3359 48...65 LRD-3363 63...80 TeSys Nb modules Nbr of modules Mf Mw 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 6 9 6 9 6 9 6 9 138 Installation de l’appareillage Switchgear Installation Compact NS80H-MA 500 V TeSys TeSys Puissance Moteur Power motor P (kW) I (A) 0,37 1 0,55 1,21 0,75 1,5 1,1 2 1,5 2,6 2,2 3,8 3 5 4 6,5 5,5 9 7,5 12 9 13,9 11 18,4 15 23 18,5 28,5 22 33 30 45 37 55 Pdc BC Icu (kA) Rms (kA) 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 Guide Technique V9 / V9 Technical Guide TeSys Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA Cal (A) Rat (A) 2,5 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 25 25 25 50 50 50 50 80 Type de coordination: 1 Coordination type: 1 TeSys Contacteurs Contactor Type Type 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D12 2 x LC1-D18 2 x LC1-D25 2 x LC1-D32 2 x LC1-D32 2 x LC1-D40 2 x LC1-D50 2 x LC1-D65 2 sens de marche Reverse TeSys Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LRD-06 1...1,7 LRD-06 1...1,7 LRD-06 1...1,7 LRD-07 1,6...2,5 LRD-08 2,5...4 LRD-08 2,5...4 LRD-10 4...6 LRD-12 5,5...8 LRD-14 7...10 LRD-16 9...13 LRD-21 12...18 LRD-22 16...24 LRD-22 16...24 LRD-35 23...32 LRD-3355 30...40 LRD-3357 37...50 LRD-3359 48...65 TeSys Nb modules Nbr of modules Mf Mw 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 6 9 6 9 6 9 139 Installation de l’appareillage Switchgear Installation 3.3.1.10. Compact NS80H-MA Type de coordination: 2 - - - - - - - - - - - - - - - -2 sens de marche Coordination type: 2 - - - - - - - - - - - - - - - - - - -Reverse Démarrage: Normal Start-up: Normal Compact NS80H-MA 400/415 V TeSys TeSys Puissance Moteur Power motor P (kW) I (A) TeSys Type de coordination: 2 Coordination type: 2 TeSys Pdc BC Icu (kA) Rms (kA) Disjoncteurs Circuit Breaker Type Type Cal (A) Rat (A) Contacteurs Contactor Type Type 2 sens de marche Reverse TeSys Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) TeSys Nb modules Nbr of modules Mf Mw 0,37 0.98 70 NS80H-MA 2,5 2xLC1-D09 LRD-05 0,63…1 3 6 0,55 1.5 70 NS80H-MA 2,5 2xLC1-D09 LRD-06 1…1,7 3 6 0,75 2 70 NS80H-MA 2,5 2xLC1-D09 LRD-07 1,6…2,5 3 6 1,1 2,5 70 NS80H-MA 6,3 2xLC1-D18 LRD-08 2,5…4 3 6 1,5 3,5 70 NS80H-MA 6,3 2xLC1-D18 LRD-08 2,5…4 3 6 2,2 5 70 NS80H-MA 6,3 2xLC1-D25 LRD-10 4…6 3 6 3 6,5 70 NS80H-MA 12,5 2xLC1-D32 LRD-12 5,5…8 3 6 4 8,4 70 NS80H-MA 12,5 2xLC1-D32 LRD-14 7…10 3 6 5,5 11 70 NS80H-MA 12,5 2xLC1-D32 LRD-16 9…13 3 6 7,5 14,8 70 NS80H-MA 25 2xLC1-D32 LRD-21 12…18 3 6 9 18,1 70 NS80H-MA 25 2xLC1-D40 LRD-3322 17..25 6 9 11 21 70 NS80H-MA 25 2xLC1-D40 LRD-3322 17..25 6 9 15 28,5 70 NS80H-MA 50 2xLC1-D40 LRD-3353 23…32 6 9 18,5 35 70 NS80H-MA 50 2xLC1-D50 LRD-3355 30…40 6 9 22 42 70 NS80H-MA 50 2xLC1-D50 LRD-3357 37…50 6 9 30 57 70 NS80H-MA 80 2xLC1-D65 LRD-3359 48…65 6 9 37 69 70 NS80H-MA 80 2xLC1-D80 LRD-3363 63…80 6 9 Guide Technique V9 / V9 Technical Guide 140 Installation de l’appareillage Switchgear Installation Compact NS80H-MA 440 V TeSys TeSys Puissance Moteur Power motor P (kW) I (A) TeSys Type de coordination: 2 Coordination type: 2 TeSys Pdc BC Icu (kA) Rms (kA) Disjoncteurs Circuit Breaker Type Type Cal (A) Rat (A) Contacteurs Contactor Type Type 2 sens de marche Reverse TeSys TeSys Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) Nb modules Nbr of modules Mf Mw 0,37 0,99 65 NS80H-MA 2,5 2xLC1-D09 LRD-05 0,63...1 3 6 0,55 1,36 65 NS80H-MA 2,5 2xLC1-D09 LRD-06 1…1,7 3 6 0,75 1,68 65 NS80H-MA 2,5 2xLC1-D09 LRD-07 1,6…2,5 3 6 1,1 2,37 65 NS80H-MA 2,5 2xLC1-D09 LRD-07 1,6…2,5 3 6 1,5 3,06 65 NS80H-MA 6,3 2xLC1-D18 LRD-08 2,5…4 3 6 2,2 4,42 65 NS80H-MA 6,3 2xLC1-D25 LRD-10 4…6 3 6 3 5,77 65 NS80H-MA 6,3 2xLC1-D25 LRD-10 4…6 3 6 4 7,9 65 NS80H-MA 12,5 2xLC1-D32 LRD-14 7…10 3 6 5,5 10,4 65 NS80H-MA 12,5 2xLC1-D32 LRD-16 9…13 3 6 7,5 13,7 65 NS80H-MA 25 2xLC1-D32 LRD-21 12…18 3 6 9 16,9 65 NS80H-MA 25 2xLC1-D38 LRD-21 12…18 3 6 11 20,1 65 NS80H-MA 25 2xLC1-D40 LRD-3322 17..25 6 9 15 26,5 65 NS80H-MA 50 2xLC1-D40 LRD-3353 23…32 6 9 18,5 32,8 65 NS80H-MA 50 2xLC1-D50 LRD-3355 30...40 6 9 22 39 65 NS80H-MA 50 2xLC1-D50 LRD-3357 37...50 6 9 30 51,5 65 NS80H-MA 80 2xLC1-D65 LRD-3359 48...65 6 9 37 64 65 NS80H-MA 80 2xLC1-D80 LRD-3359 48...65 6 9 45 76 65 NS80H-MA 80 2xLC1-D80 LRD-3363 63...80 6 9 Compact NS80H-MA 500 V TeSys TeSys Puissance Moteur Power motor P (kW) I (A) TeSys Type de coordination: 2 Coordination type: 2 TeSys Pdc BC Icu (kA) Rms (kA) Disjoncteurs Circuit Breaker Type Type Cal (A) Rat (A) Contacteurs Contactor Type Type 2 sens de marche Reverse TeSys Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) TeSys Nb modules Nbr of modules Mf Mw 0,37 1 25 NS80H-MA 1,5 2xLC1-D09 LRD-06 1…1,7 3 6 0,55 1,21 25 NS80H-MA 2,5 2xLC1-D09 LRD-06 1…1,7 3 6 0,75 1,5 25 NS80H-MA 2,5 2xLC1-D09 LRD-06 1…1,7 3 6 1,1 2 25 NS80H-MA 2,5 2xLC1-D09 LRD-07 1,6…2,5 3 6 1,5 2,6 25 NS80H-MA 6,3 2xLC1-D18 LRD-08 2,5…4 3 6 2,2 3,8 25 NS80H-MA 6,3 2xLC1-D18 LRD-08 2,5…4 3 6 3 5 25 NS80H-MA 6,3 2xLC1-D25 LRD-10 4…6 3 6 4 6,5 25 NS80H-MA 12,5 2xLC1-D32 LRD-12 5,5…8 3 6 5,5 9 25 NS80H-MA 12,5 2xLC1-D32 LRD-14 7…10 3 6 7,5 12 25 NS80H-MA 12,5 2xLC1-D32 LRD-16 9…13 3 6 9 13,9 25 NS80H-MA 25 2xLC1-D32 LRD-21 12…18 3 6 11 18,4 25 NS80H-MA 25 2xLC1-D40 LRD-3322 17..25 6 9 15 23 25 NS80H-MA 25 2xLC1-D40 LRD-3322 17..25 6 9 18,5 28,5 25 NS80H-MA 50 2xLC1-D40 LRD-3353 23…32 6 9 22 33 25 NS80H-MA 50 2xLC1-D50 LRD-3355 30…40 6 9 30 45 25 NS80H-MA 50 2xLC1-D50 LRD-3357 37...50 6 9 37 55 25 NS80H-MA 80 2xLC1-D65 LRD-3359 48...65 6 9 Guide Technique V9 / V9 Technical Guide 141 Installation de l’appareillage Switchgear Installation Compact NS80H-MA 3.3.1.11. Type de coordination: 1 - - - - - - - - - - - - - - - -Etoile / Triangle (Y/∆) Coordination type: 1 - - - - - - - - - - - - - - - - - - -STAR / DELTA (Y/∆) Démarrage: Normal Start-up: Normal 400/415 V TeSys Compact NS80H-MA TeSys Puissance Moteur Power motor P (kW) I (A) 0,37 0,98 0,55 1,5 0,75 2 1,1 2,5 1,5 3,5 2,2 5 3 6,5 4 8,4 5,5 11 7,5 14,8 9 18,1 11 21 15 28,5 18,5 35 22 42 30 57 37 69 Pdc BC Icu (kA) Rms (kA) 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 Guide Technique V9 / V9 Technical Guide TeSys Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA Cal (A) Rat (A) 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 12,5 25 25 25 50 50 50 80 80 Type de coordination: 1 Coordination type: 1 TeSys Contacteurs Contactor Type Type 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D12 3 x LC1-D12 3 x LC1-D18 3 x LC1-D18 3 x LC1-D32 3 x LC1-D32 3 x LC1-D40 Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) TeSys Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LRD-04 0,40...0,63 LRD-05 0,63...1 LRD-06 1...1,7 LRD-06 1...1,7 LRD-07 1,6...2,5 LRD-08 2,5...4 LRD-08 2,5...4 LRD-10 4...6 LRD-12 5,5...8 LRD-14 7...10 LRD-16 9...13 LRD-16 9...13 LRD-21 12...18 LRD-22 16...24 LRD-32 23...32 LRD-35 30...38 LRD-3359 48...65 TeSys Nb modules Nbr of modules Mf Mw 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 9 142 Installation de l’appareillage Switchgear Installation Compact NS80H-MA 440 V TeSys TeSys Puissance Moteur Power motor P (kW) I (A) 0,37 0,99 0,55 1,36 0,75 1,68 1,1 2,37 1,5 3,06 2,2 4,42 3 5,77 4 7,9 5,5 10,4 7,5 13,7 9 16,9 11 20,1 15 26,5 18,5 32,8 22 39 30 51,5 37 64 45 76 Pdc BC Icu (kA) Rms (kA) 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 Guide Technique V9 / V9 Technical Guide TeSys Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA Cal (A) Rat (A) 2,5 2,5 2,5 6,3 6,3 6,3 6,3 12,5 12,5 25 25 25 50 50 50 80 80 80 Type de coordination: 1 Coordination type: 1 TeSys Contacteurs Contactor Type Type 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D12 3 x LC1-D12 3 x LC1-D18 3 x LC1-D18 3 x LC1-D18 3 x LC1-D32 3 x LC1-D40 3 x LC1-D40 Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) TeSys Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LRD-04 0,40...0,63 LRD-05 0,63...1 LRD-05 0,63...1 LRD-06 1...1,7 LRD-07 1,6...2,5 LRD-08 2,5...4 LRD-08 2,5...4 LRD-10 4...6 LRD-12 5,5...8 LRD-14 7...10 LRD-16 9...13 LRD-16 9...13 LRD-21 12...18 LRD-22 16...24 LRD-22 16...24 LRD-32 23...32 LRD-3355 30...40 LRD-3357 37...50 TeSys Nb modules Nbr of modules Mf Mw 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 9 6 9 143 Installation de l’appareillage Switchgear Installation 3.3.1.12. Compact NS80H-MA Type de coordination: 2 - - - - - - - - - - - - - - - -Etoile / Triangle (Y/∆) Coordination Type: 2 - - - - - - - - - - - - - - - - - -STAR / DELTA (Y/∆) Démarrage: normal Start-up: Normal Compact NS80H-MA 400/415 V TeSys TeSys Puissance Moteur Power motor P (kW) I (A) TeSys Pdc BC Icu (kA) Rms (kA) Disjoncteurs Circuit Breaker Type Type 1,5 3,5 70 NS80HMA 2,2 5 70 NS80HMA 3 6,5 70 NS80HMA TeSys Cal (A) Rat (A) 6,3 6,3 12,5 Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Type de coordination: 2 Coordination type: 2 Contacteurs Contactor Type Type TeSys TeSys Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) Nb modules Nbr of modules Mf Mw 3 x LC1-D18 LRD-08 2,5...4 6 6 3 x LC1-D25 LRD-10 4...6 6 6 3 x LC1-D32 LRD-10 4...6 6 6 4 8,4 70 NS80HMA 12,5 3 x LC1-D32 LRD-16 9...13 6 6 5,5 11 70 NS80HMA 12,5 3 x LC1-D32 LRD-16 9...13 6 6 7,5 14,8 70 NS80HMA 25 3 x LC1-D32 LRD-21 12...18 6 6 9 18,1 70 NS80HMA 25 3 x LC1-D40 LRD-22 16...24 6 9 11 21 70 NS80HMA 25 3 x LC1-D40 LRD-22 16...24 6 9 15 28,5 70 NS80HMA 50 3 x LC1-D40 LRD-3353 23...32 6 9 18,5 35 70 NS80HMA 50 3 x LC1-D50 LRD-3355 30...40 6 9 22 42 70 NS80HMA 50 3 x LC1-D50 LRD-3357 37...50 6 9 30 57 70 NS80HMA 80 3 x LC1-D65 LRD-3359 48...65 6 9 37 69 70 NS80HMA 80 3 x LC1-D80 LRD-3363 63...80 6 9 Compact NS80H-MA 440 V TeSys TeSys Puissance Moteur Power motor P (kW) I (A) TeSys Pdc BC Icu (kA) Rms (kA) Disjoncteurs Circuit Breaker Type Type TeSys Cal (A) Rat (A) Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Type de coordination: 2 Coordination type: 2 Contacteurs Contactor Type Type TeSys Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) TeSys Nb modules Nbr of modules Mf Mw 1,5 3,06 65 NS80HMA 6,3 3 x LC1-D18 2,2 4,42 65 NS80HMA 6,3 3 x LC1-D25 LRD-10 4...6 6 6 3 5,77 65 NS80HMA 6,3 3 x LC1-D25 LRD-10 4...6 6 6 6 LRD-08 2,5...4 6 6 4 7,9 65 NS80HMA 12,5 3 x LC1-D32 LRD-14 7...10 6 5,5 10,4 65 NS80HMA 12,5 3 x LC1-D32 LRD-16 9...13 6 6 7,5 13,7 65 NS80HMA 25 3 x LC1-D32 LRD-21 12...18 6 6 9 16,9 65 NS80HMA 25 3 x LC1-D40 LRD-21 17...25 6 11 20,1 65 NS80HMA 25 3 x LC1-D40 LRD-22 17...25 6 9 15 26,5 65 NS80HMA 50 3 x LC1-D40 LRD-3353 23...32 6 9 18,5 32,8 65 NS80HMA 50 3 x LC1-D50 LRD-3355 30...40 6 9 9 22 39 65 NS80HMA 50 3 x LC1-D50 LRD-3357 37...50 6 9 30 51,5 65 NS80HMA 80 3 x LC1-D65 LRD-3359 48...65 6 9 37 64 65 NS80HMA 80 3 x LC1-D80 LRD-3359 48...65 6 9 45 76 65 NS80HMA 80 3 x LC1-D80 LRD-3363 63...80 6 9 Guide Technique V9 / V9 Technical Guide 144 Installation de l’appareillage Switchgear Installation Compact NS100-630z-MA 3.3.1.13. Type de coordination: 1 - - - - - - - - - - - - - - - -DOL (Démarrage direct) Coordination type: 1 - - - - - - - - - - - - - - - - - - -DOL (Direct On Line) Démarrage: Normal Start-up: Normal Compact NS100-630z-MA 400/415 V Type de coordination: 1 Coordination type: 1 DOL (Démarrage direct) DOL (Direct On Line) Performance de coupure / Breaking characteristics Compact NS N H L NS100z-MA 25kA 70kA 130kA NS160/250z-MA 35kA 70kA 130kA 70kA 130kA NS400/630z-MA TeSys TeSys Puissance Moteur Power motor P (kW) I (A) TeSys TeSys TeSys TeSys 0,37 0,98 0,55 1,5 0,75 2 1,1 2,5 Disjoncteurs Circuit Breaker Type Type NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA 1,5 3,5 NS100N/H/L-MA 6,3 LC1-D09 LRD-08 2,5...4 2,2 5 NS100N/H/L-MA 6,3 LC1-D09 LRD-10 4...6 3 6 3 6,5 NS100N/H/L-MA 12,5 LC1-D09 LRD-12 5,5...8 3 6 4 8,4 NS100N/H/L-MA 12,5 LC1-D09 LRD-14 7...10 3 6 5,5 11 NS100N/H/L-MA 12,5 LC1-D12 LRD-16 9...13 3 6 7,5 14,8 NS100N/H/L-MA 25 LC1-D18 LRD-21 12...18 3 6 9 18,1 NS100N/H/L-MA 25 LC1-D18 LRD-22 16...24 3 6 11 21 NS100N/H/L-MA 25 LC1-D25 LRD-22 16...24 3 6 15 28,5 NS100N/H/L-MA 50 LC1-D32 LRD-32 23...32 3 6 18,5 35 NS100N/H/L-MA 50 LC1-D38 LRD-35 30...38 3 6 22 42 NS100N/H/L-MA 50 LC1-D50 LRD-3357 37...50 3 6 30 57 NS100N/H/L-MA 50 LC1-D65 LRD-3359 48...65 3 6 37 69 NS100N/H/L-MA 100 LC1-D80 LRD-3363 63...80 3 6 45 81 NS100N/H/L-MA 100 LC1-D95 LRD-3365 80...104 3 6 55 100 NS160N/H/L-MA 150 LC1-D115 LRD-4367 95...120 6 9 75 135 NS160N/H/L-MA 150 LC1-D150 LRD-4369 110...140 6 9 90 165 NS250N/H/L-MA 220 LC1-F185 LR9-F5371 132...220 9 9 110 200 NS250N/H/L-MA 220 LC1-F225 LR9-F5371 132...220 9 9 132 240 NS400H-MA 320 LC1-F265 LR9-F7375 200...330 12 12 132 240 NS400L-MA 320 LC1-F265 LR9-F7375 200...330 12 15 160 285 NS400H-MA 320 LC1-F330 LR9-F7375 200...330 12 12 160 285 NS400L-MA 320 LC1-F330 LR9-F7375 200...330 12 15 200 352 NS630H/L-MA 500 LC1-F400 LR9-F7379 300...500 15 15 220 388 NS630H/L-MA 500 LC1-F400 LR9-F7379 300...500 15 15 250 437 NS630H/L-MA 500 LC1-F500 LR9-F7379 300...500 15 15 Guide Technique V9 / V9 Technical Guide Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LRD-05 0,63...1 LRD-06 1...1,7 LRD-07 1,6...2,5 LRD-08 2,5...4 Nb modules Nbr of modules Cal (A) Rat (A) 2,5 2,5 2,5 6,3 Contacteurs Contactor Type Type LC1-D09 LC1-D09 LC1-D09 LC1-D09 Mf Mw 3 6 3 6 3 6 3 6 3 6 145 Installation de l’appareillage Switchgear Installation Compact NS100-630z-MA 440 V Type de coordination: 1 Coordination type: 1 DOL (Démarrage direct) DOL (Direct On Line) Performance de coupure / Breaking characteristics Compact NS N H L NS100z-MA 25kA 65kA 130kA NS160/250z-MA 35kA 65kA 130kA 65kA 130kA NS400/630z-MA TeSys TeSys Puissance Moteur Power motor P (kW) I (A) 0,37 0,99 0,55 1,36 0,75 1,68 1,1 2,37 1,5 3,06 2,2 4,42 3 5,77 4 7,9 5,5 10,4 7,5 13,7 9 16,9 11 20,1 15 26,5 18,5 32,8 22 39 30 51,5 37 64 45 76 55 90 75 125 90 146 110 178 132 215 160 256 160 256 200 321 200 321 220 353 250 401 280 470 Disjoncteurs Circuit Breaker Type Type NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS160N/H/L-MA NS160N/H/L-MA NS250N/H/L-MA NS250N/H/L-MA NS400H-MA NS400L-MA NS400H-MA NS400L-MA NS630H/L-MA NS630H/L-MA NS630H/L-MA Guide Technique V9 / V9 Technical Guide TeSys Cal (A) Rat (A) 2,5 2,5 2,5 2,5 6,3 6,3 12,5 12,5 12,5 25 25 25 50 50 50 50 100 100 100 150 150 220 220 320 320 320 320 500 500 500 TeSys Contacteurs Contactor Type Type LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D12 LC1-D18 LC1-D18 LC1-D25 LC1-D32 LC1-D38 LC1-D40 LC1-D65 LC1-D65 LC1-D80 LC1-D115 LC1-D150 LC1-F185 LC1-F225 LC1-F265 LC1-F330 LC1-F330 LC1-F330 LC1-F330 LC1-F400 LC1-F400 LC1-F500 TeSys Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LRD-05 0,63...1 LRD-06 1...1,7 LRD-07 1,6...2,5 LRD-07 1,6...2,5 LRD-08 2,5...4 LRD-10 4...6 LRD-10 4...6 LRD-14 7...10 LRD-16 9...13 LRD-21 12...18 LRD-21 12...18 LRD-22 16...24 LRD-32 23...32 LRD-35 30...38 LRD-3357 37...50 LRD-3359 48...65 LRD-3359 48...65 LRD-3363 63...80 LRD-4365 80...104 LRD-4369 110...140 LR9-F5371 132...220 LR9-F5371 132...220 LR9-F5371 132...220 LR9-F7375 200...330 LR9-F7375 200...330 LR9-F7375 200...330 LR9-F7375 200...330 LR9-F7379 300...500 LR9-F7379 300...500 LR9-F7379 300...500 TeSys Nb modules Nbr of modules Mf Mw 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 6 9 6 9 9 9 9 9 9 12 12 12 12 15 12 12 12 15 15 15 15 15 15 15 146 Installation de l’appareillage Switchgear Installation Compact NS100-630z-MA 500 V Type de coordination: 1 Coordination type: 1 DOL (Démarrage direct) DOL (Direct On Line) Performance de coupure / Breaking characteristics Compact NS H L NS100z-MA 50/35kA 70kA NS160/250z-MA 50/35kA 70kA NS400/630z-MA 50/35kA 70kA TeSys TeSys Puissance Moteur Power motor P (kW) I (A) 0,55 1,21 0,75 1,5 1,1 2 1,5 2,6 2,2 3,8 3 5 4 6,5 5,5 9 7,5 12 9 13,9 11 18,4 15 23 18,5 28,5 22 33 30 45 37 55 45 65 55 80 75 105 90 129 110 156 132 187 160 220 200 281 220 310 250 360 315 445 355 500 Disjoncteurs Circuit Breaker Type Type NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS160N/H/L-MA NS160N/H/L-MA NS250N/H/L-MA NS250N/H/L-MA NS400H/L-MA NS400H/L-MA NS400H/L-MA NS630H/L-MA NS630H/L-MA NS630H/L-MA TeSys Cal (A) Rat (A) 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 12,5 25 25 25 50 50 50 100 100 100 150 150 220 220 320 320 320 500 500 500 ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide TeSys Contacteurs Contactor Type Type LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D12 LC1-D18 LC1-D25 LC1-D32 LC1-D32 LC1-D40 LC1-D50 LC1-D65 LC1-D80 LC1-D80 LC1-D115 LC1-D150 LC1-F185 LC1-F265 LC1-F265 LC1-F330 LC1-F400 LC1-F400 LC1-F500 LC1-F500 TeSys Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LRD-06 1...1,7 LRD-06 1...1,7 LRD-07 1,6...2,5 LRD-08 2,5...4 LRD-08 2,5...4 LRD-10 4...6 LRD-12 5,5...8 LRD-14 7...10 LRD-16 9...13 LRD-21 12...18 LRD-22 16...24 LRD-22 16...24 LRD-32 23...32 LRD-3355 30...40 LRD-3357 37...50 LRD-3359 48...65 LRD-3361 55...70 LRD-3363 63...80 LRD-4367 95...120 LRD-4369 110...140 LR9-F53 71 132...220 LR9-F53 71 132...220 LR9-F73 75 200...330 LR9-F73 75 200...330 LR9-F73 79 300...500 LR9-F73 79 300...500 LR9-F73 79 300...500 LR9-F73 81 380...630 TeSys Nb modules Nbr of modules Mf Mw 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 6 9 6 9 9 9 9 12 12 15 12 15 15 15 15 15 15 15 15 ** ** Impossible in Mw Type 147 Installation de l’appareillage Switchgear Installation 3.3.1.14. Compact NS100-630z-MA Type de coordination: 2 - - - - - - - - - - - - - - - -DOL (Démarrage direct) Coordination type: 2 - - - - - - - - - - - - - - - - - - -DOL (Direct On Line) Démarrage: normal Start-up: Normal Compact NS100-630z-MA 400/415 V Type de coordination: 2 Coordination type: 2 DOL (Démarrage direct) DOL (Direct On Line) Performance de coupure / Breaking characteristics Compact NS N H L NS100z-MA 25kA 70kA 130kA NS160/250z-MA 36kA 70kA 130kA 70kA 130kA NS400/630z-MA TeSys TeSys Puissance Moteur Power motor P (kW) I (A) Disjoncteurs Circuit Breaker Type Type TeSys Cal (A) Rat (A) TeSys Contacteurs Contactor Type Type TeSys Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) TeSys Nb modules Nbr of modules Mf Mw 0,37 0,98 NS100-MA 2,5 LC1-D09 LRD-05 0,63…1 3 6 0,55 1,5 NS100-MA 2,5 LC1-D09 LRD-06 1…1,7 3 6 0,75 2 NS100-MA 2,5 LC1-D09 LRD-07 1,6...2,5 3 6 1,1 2,5 NS100-MA 6,3 LC1-D40 LRD-08 2,5...4 3 6 1,5 3,5 NS100-MA 6,3 LC1-D40 LRD-08 2,5...4 3 6 2,2 5 NS100-MA 6,3 LC1-D40 LRD-10 4...6 3 6 3 6,5 NS100-MA 12,5 LC1-D40 LRD-12 5,5...8 3 6 4 8,4 NS100-MA 12,5 LC1-D40 LRD-14 7...10 3 6 6 5,5 11 NS100-MA 12,5 LC1-D40 LRD-16 9...13 3 7,5 14,8 NS100-MA 25 LC1-D40 LRD-21 12...18 3 6 9 18,1 NS100-MA 25 LC1-D40 LRD-3322 17...25 3 6 11 21 NS100-MA 25 LC1-D40 LRD-3322 17...25 3 6 15 28,5 NS100-MA 50 LC1-D80 LRD-3353 23...32 3 6 18,5 35 NS100-MA 50 LC1-D80 LRD-3355 30...40 3 6 22 42 NS100-MA 50 LC1-D80 LRD-3357 37...50 3 6 30 57 NS100-MA 100 LC1-D80 LRD-3359 48...65 3 6 37 69 NS100-MA 100 LC1-D80 LRD-3363 63...80 3 6 45 81 NS100-MA 100 LC1-D115 LR9-D5367 60...100 6 9 55 100 NS160-MA 150 LC1-D150 LR9-D5369 90...150 6 9 75 135 NS160-MA 150 LC1-F150 LR9-F5369 90...150 6 9 90 165 NS250-MA 220 LC1-F185 LR9-F5371 132...220 9 9 110 200 NS250-MA 220 LC1-F225 LR9-F5371 132...220 9 9 132 240 NS400HMA 320 LC1-F265 LR9-F7375 200...330 12 12 132 240 NS400LMA 320 LC1-F265 LR9-F7375 200...330 12 15 160 285 NS400HMA 320 LC1-F330 LR9-F7375 200...330 12 12 160 285 NS400LMA 320 LC1-F330 LR9-F7375 200...330 12 15 200 352 NS630-MA 500 LC1-F400 LR9-F7379 300...500 15 15 220 388 NS630-MA 500 LC1-F500 LR9-F7379 300...500 15 15 250 437 NS630-MA 500 LC1-F500 LR9-F7379 300...500 15 15 Guide Technique V9 / V9 Technical Guide 148 Installation de l’appareillage Switchgear Installation Compact NS100-630z-MA 440 V Type de coordination: 2 Coordination type: 2 DOL (Démarrage direct) DOL (Direct On Line) Performance de coupure / Breaking characteristics Compact NS N H L NS100z-MA 25kA 65kA 130kA NS160/250z-MA 35kA 65kA 130kA 65kA 130kA NS400/630z-MA TeSys TeSys Puissance Moteur Power motor P (kW) I (A) Disjoncteurs Circuit Breaker Type Type TeSys TeSys Cal (A) Rat (A) Contacteurs Contactor Type Type TeSys Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) TeSys Nb modules Nbr of modules Mf Mw 0,37 0,99 NS100-MA 2.5 LC1-D09 LRD-05 0,63...1 3 6 0,55 1,36 NS100-MA 2.5 LC1-D09 LRD-06 1…1,7 3 6 0,75 1,68 NS100-MA 2.5 LC1-D09 LRD-07 1,6…2,5 3 6 1,1 2,37 NS100-MA 2.5 LC1-D09 LRD-07 1,6…2,5 3 6 1,5 3,06 NS100-MA 6.3 LC1-D40 LRD-08 2,5…4 3 6 2,2 4,42 NS100-MA 6.3 LC1-D40 LRD-10 4…6 3 6 3 5,77 NS100-MA 6.3 LC1-D40 LRD-10 4…6 3 6 4 7,9 NS100-MA 12.5 LC1-D40 LRD-12 5,5…8 3 6 5,5 10,4 NS100-MA 12.5 LC1-D40 LRD-16 9…13 3 6 7,5 13,7 NS100-MA 25 LC1-D40 LRD-21 12…18 3 6 9 16,9 NS100-MA 25 LC1-D40 LRD-21 12…18 3 6 11 20,1 NS100-MA 25 LC1-D40 LRD-3322 17..25 3 6 15 26,5 NS100-MA 50 LC1-D80 LRD-3353 23..32 3 6 18,5 32,8 NS100-MA 50 LC1-D80 LRD-3355 30...40 3 6 22 39 NS100-MA 50 LC1-D80 LRD-3357 37...50 3 6 30 51,5 NS100-MA 100 LC1-D80 LRD-3359 48...65 3 6 37 64 NS100-MA 100 LC1-D80 LRD-3359 48...65 3 6 45 76 NS100-MA 100 LC1-D80 LRD-3363 63...80 6 9 55 90 NS100-MA 100 LC1-D115 LR9-D5367 60...100 6 9 75 125 NS160-MA 150 LC1-D150 LR9-D5369 90...150 6 9 9 90 146 NS160-MA 150 LC1-F150 LR9-F5369 90...150 6 110 178 NS250-MA 220 LC1-F185 LR9-F5371 132...220 9 9 132 215 NS250-MA 220 LC1-F225 LR9-F5371 132...220 12 12 160 256 NS400HMA 320 LC1-F265 LR9-F7375 200...330 12 12 160 256 NS400LMA 320 LC1-F265 LR9-F7375 200...330 12 15 200 321 NS400HMA 320 LC1-F330 LR9-F7375 200...330 12 12 200 321 NS400LMA 320 LC1-F330 LR9-F7375 200...330 12 15 220 353 NS630-MA 500 LC1-F400 LR9-F7379 300...500 16 15 250 401 NS630-MA 500 LC1-F400 LR9-F7379 300...500 16 15 Guide Technique V9 / V9 Technical Guide 149 Installation de l’appareillage Switchgear Installation Compact NS100-630z-MA 500 V Type de coordination: 2 Coordination type: 2 DOL (Démarrage direct) DOL (Direct On Line) Performance de coupure / Breaking characteristics Compact NS N H L NS100z-MA 18kA 50kA 100kA NS160/250z-MA 30kA 50kA 70kA 50kA 100kA NS400/630z-MA TeSys TeSys Puissance Moteur Power motor P (kW) I (A) Disjoncteurs Circuit Breaker Type Type TeSys Cal (A) Rat (A) TeSys Contacteurs Contactor Type Type TeSys Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) TeSys Nb modules Nbr of modules Mf Mw 0,55 1,21 NS100-MA 2,5 LC1-D09 LRD-06 1…1,7 3 6 0,75 1,5 NS100-MA 2,5 LC1-D09 LRD-06 1…1,7 3 6 1,1 2 NS100-MA 2,5 LC1-D09 LRD-07 1,6…2,5 3 6 1,5 2,6 NS100-MA 6,3 LC1-D40 LRD-08 2,5…4 3 6 2,2 3,8 NS100-MA 6,3 LC1-D40 LRD-08 2,5…4 3 6 3 5 NS100-MA 6,3 LC1-D40 LRD-10 4…6 3 6 4 6,5 NS100-MA 12,5 LC1-D40 LRD-12 5,5…8 3 6 5,5 9 NS100-MA 12,5 LC1-D40 LRD-14 7...10 3 6 7,5 12 NS100-MA 12,5 LC1-D40 LRD-16 9…13 3 6 9 13,9 NS100-MA 25 LC1-D40 LRD-21 12…18 3 6 11 18,4 NS100-MA 25 LC1-D80 LRD-3322 17..25 3 6 15 23 NS100-MA 25 LC1-D80 LRD-3322 16..24 3 6 18,5 28,5 NS100-MA 50 LC1-D80 LRD-3353 23..32 3 6 22 33 NS100-MA 50 LC1-D80 LRD-3355 30...40 3 6 30 45 NS100-MA 50 LC1-D80 LRD-3357 37...50 3 6 37 55 NS100-MA 100 LC1-D80 LRD-3359 48...65 3 6 45 65 NS100-MA 100 LC1-D80 LRD-3361 55...70 3 6 55 80 NS100-MA 100 LC1-D115 LR9-D5367 60…100 6 9 75 105 NS160-MA 150 LC1-D150 LR9-D5369 90...150 6 9 90 129 NS160-MA 150 LC1-F150 LR9-F5369 90...150 6 9 110 156 NS250-MA 220 LC1-F185 LR9-F5371 132...220 9 9 132 187 NS250-MA 220 LC1-F265 LR9-F5371 132...220 12 12 160 220 NS400-MA 320 LC1-F265 LR9-F7375 200...330 12 15 200 281 NS400-MA 320 LC1-F400 LR9-F7375 200...330 15 15 220 310 NS400-MA 320 LC1-F400 LR9-F7379 300...500 15 15 250 360 NS630-MA 500 LC1-F500 LR9-F7379 300...500 16 15 315 445 NS630-MA 500 LC1-F500 LR9-F7379 300...500 16 15 355 500 NS630-MA 500 LC1-F500 LR9-F7381 380...630 16 ** ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide ** Impossible in Mw type 150 Installation de l’appareillage Switchgear Installation Compact NS100-630z-MA 3.3.1.15. Type de coordination: 1 - - - - - - - - - - - - - - - -2 sens de marche Coordination type: 1 - - - - - - - - - - - - - - - - - - -Reverse Démarrage: Normal Start-up: Normal Compact NS100-630z-MA 400/415 V Type de coordination: 1 Coordination type: 1 2 sens de marche Reverse Performance de coupure / Breaking characteristics Compact NS N H L NS100z-MA 25kA 70kA 130kA NS160/250z-MA 35kA 70kA 130kA 70kA 130kA NS400/630z-MA TeSys TeSys Puissance Moteur Power motor P (kW) I (A) TeSys TeSys 1,1 2,5 Disjoncteurs Circuit Breaker Type Type NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA 1,5 3,5 NS100N/H/L-MA 6,3 2 x LC1-D09 0,37 0,98 0,55 1,5 0,75 2 TeSys TeSys Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LRD-05 0,63...1 LRD-06 1...1,7 LRD-07 1,6...2,5 LRD-08 2,5...4 Nb modules Nbr of modules Cal (A) Rat (A) 2,5 2,5 2,5 6,3 Contacteurs Contactor Type Type 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 3 6 LRD-08 3 6 2,5...4 Mf Mw 3 6 3 6 3 6 2,2 5 NS100N/H/L-MA 6,3 2 x LC1-D09 LRD-10 4...6 3 6 3 6,5 NS100N/H/L-MA 12,5 2 x LC1-D09 LRD-12 5,5...8 3 6 4 8,4 NS100N/H/L-MA 12,5 2 x LC1-D09 LRD-14 7...10 3 6 5,5 11 NS100N/H/L-MA 12,5 2 x LC1-D12 LRD-16 9...13 3 6 7,5 14,8 NS100N/H/L-MA 25 2 x LC1-D18 LRD-21 12...18 3 6 9 18,1 NS100N/H/L-MA 25 2 x LC1-D18 LRD-22 16...24 3 6 11 21 NS100N/H/L-MA 25 2 x LC1-D25 LRD-22 16...24 3 6 15 28,5 NS100N/H/L-MA 50 2 x LC1-D32 LRD-32 23...32 3 6 6 18,5 35 NS100N/H/L-MA 50 2 x LC1-D38 LRD-35 30...38 3 22 42 NS100N/H/L-MA 50 2 x LC1-D50 LRD-3357 37...50 6 9 30 57 NS100N/H/L-MA 50 2 x LC1-D65 LRD-3359 48...65 6 9 9 37 69 NS100N/H/L-MA 100 2 x LC1-D80 LRD-3363 63...80 6 45 81 NS100N/H/L-MA 100 2 x LC1-D95 LRD-3365 80...104 6 9 55 100 NS160N/H/L-MA 150 2 x LC1-D115 LRD-33676 95...120 9 12 75 135 NS160N/H/L-MA 150 2 x LC1-D150 LRD-33696 110...140 9 12 90 165 NS250N/H/L-MA 220 2 x LC1-F185 LR9-F5371 132...220 12 ** 110 200 NS250N/H/L-MA 220 2 x LC1-F225 LR9-F5371 132...220 12 ** 132 240 NS400H-MA 320 2 x LC1-F265 LR9-F7375 200...330 16 ** 160 285 NS400H-MA 320 2 x LC1-F330 LR9-F7375 200...330 16 ** 200 352 NS630H/L-MA 500 2 x LC1-F400 LR9-F7379 300...500 16 ** 220 388 NS630H/L-MA 500 2 x LC1-F400 LR9-F7379 300...500 16 ** 250 437 NS630H/L-MA 500 2 x LC1-F500 LR9-F7379 300...500 16 ** ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide ** Impossible in Mw type 151 Installation de l’appareillage Switchgear Installation Compact NS100-630z-MA 440 V Type de coordination: 1 Coordination type: 1 2 sens de marche Reverse Performance de coupure / Breaking characteristics Compact NS N H L NS100z-MA 25kA 65kA 130kA NS160/250z-MA 35kA 65kA 130kA 65kA 130kA NS400/630z-MA TeSys TeSys Puissance Moteur Power motor P (kW) I (A) 0,37 0,99 0,55 1,36 0,75 1,68 1,1 2,37 1,5 3,06 2,2 4,42 3 5,77 4 7,9 5,5 10,4 7,5 13,7 9 16,9 11 20,1 15 26,5 18,5 32,8 22 39 30 51,5 37 64 45 76 55 90 75 125 90 146 110 178 132 215 160 256 200 321 220 353 250 401 280 470 Disjoncteurs Circuit Breaker Type Type NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS160N/H/L-MA NS160N/H/L-MA NS250N/H/L-MA NS250N/H/L-MA NS400H/L-MA NS400H/L-MA NS630H/L-MA NS630H/L-MA NS630H/L-MA TeSys Cal (A) Rat (A) 2,5 2,5 2,5 2,5 6,3 6,3 12,5 12,5 12,5 25 25 25 50 50 50 50 100 100 100 150 150 220 220 320 320 500 500 500 ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide TeSys Contacteurs Contactor Type Type 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D12 2 x LC1-D18 2 x LC1-D18 2 x LC1-D25 2 x LC1-D32 2 x LC1-D38 2 x LC1-D40 2 x LC1-D65 2 x LC1-D65 2 x LC1-D80 2 x LC1-D115 2 x LC1-D150 2 x LC1-F185 2 x LC1-F225 2 x LC1-F265 2 x LC1-F330 2 x LC1-F330 2 x LC1-F400 2 x LC1-F400 2 x LC1-F500 TeSys Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LRD-05 0,63...1 LRD-06 1...1,7 LRD-07 1,6...2,5 LRD-07 1,6...2,5 LRD-08 2,5...4 LRD-10 4...6 LRD-10 4...6 LRD-14 7...10 LRD-16 9...13 LRD-21 12...18 LRD-21 12...18 LRD-22 16...24 LRD-32 23...32 LRD-35 30...38 LRD-3357 37...50 LRD-3359 48...65 LRD-3359 48...65 LRD-3363 63...80 LRD-33656 80...104 LRD-33696 110...140 LR9-F5371 132...220 LR9-F5371 132...220 LR9-F5371 132...220 LR9-F7375 200...330 LR9-F7375 200...330 LR9-F7379 300...500 LR9-F7379 300...500 LR9-F7379 300...500 TeSys Nb modules Nbr of modules Mf Mw 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 6 9 6 9 6 9 6 9 9 12 9 12 12 ** 12 ** 12 ** 16 ** 16 ** 16 ** 16 ** 16 ** ** Impossible in Mw type 152 Installation de l’appareillage Switchgear Installation Compact NS100-630z-MA 500 V Type de coordination: 1 Coordination type: 1 2 sens de marche Reverse Performance de coupure / Breaking characteristics Compact NS H L NS100z-MA 50/35kA 70kA NS160/250z-MA 50/35kA 70kA NS400/630z-MA 50/35kA 70kA TeSys TeSys Puissance Moteur Power motor P (kW) I (A) 0,55 1,21 0,75 1,5 1,1 2 1,5 2,6 2,2 3,8 3 5 4 6,5 5,5 9 7,5 12 9 13,9 11 18,4 15 23 18,5 28,5 22 33 30 45 37 55 45 65 55 80 75 105 90 129 110 156 132 187 160 220 200 281 220 310 250 360 315 445 355 500 Disjoncteurs Circuit Breaker Type Type NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS160N/H/L-MA NS160N/H/L-MA NS250N/H/L-MA NS250N/H/L-MA NS400H/L-MA NS400H/L-MA NS400H/L-MA NS630H/L-MA NS630H/L-MA NS630H/L-MA TeSys Cal (A) Rat (A) 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 12,5 25 25 25 50 50 50 100 100 100 150 150 220 220 320 320 320 500 500 500 ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide TeSys Contacteurs Contactor Type Type 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D12 2 x LC1-D18 2 x LC1-D25 2 x LC1-D32 2 x LC1-D32 2 x LC1-D40 2 x LC1-D50 2 x LC1-D65 2 x LC1-D80 2 x LC1-D80 2 x LC1-D115 2 x LC1-D150 2 x LC1-F185 2 x LC1-F265 2 x LC1-F265 2 x LC1-F330 2 x LC1-F400 2 x LC1-F400 2 x LC1-F500 2 x LC1-F500 TeSys Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LRD-06 1...1,7 LRD-06 1...1,7 LRD-07 1,6...2,5 LRD-08 2,5...4 LRD-08 2,5...4 LRD-10 4...6 LRD-12 5,5...8 LRD-14 7...10 LRD-16 9...13 LRD-21 12...18 LRD-22 16...24 LRD-22 16...24 LRD-32 23...32 LRD-3355 30...40 LRD-3357 37...50 LRD-3359 48...65 LRD-3361 55...70 LRD-3363 63...80 LRD-33676 95...120 LRD-33696 110...140 LR9-F53 71 132...220 LR9-F53 71 132...220 LR9-F73 75 200...330 LR9-F73 75 200...330 LR9-F73 79 300...500 LR9-F73 79 300...500 LR9-F73 79 300...500 LR9-F73 81 380...630 TeSys Nb modules Nbr of modules Mf Mw 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 6 9 6 9 6 9 6 9 6 9 9 12 9 12 12 ** 12 ** 16 ** 16 ** 16 ** 16 ** 16 ** 16 ** ** Impossible in Mw type 153 Installation de l’appareillage Switchgear Installation 3.3.1.16. (Compact NS100-630z-MA Type de coordination: 2 - - - - - - - - - - - - - - - -2 sens de marche Coordination type: 2 - - - - - - - - - - - - - - - - - - -Reverse Démarrage: normal Start-up: Normal Compact NS100-630z-MA 400/415 V Type de coordination: 2 Coordination type: 2 2 sens de marche Reverse Performance de coupure / Breaking characteristics Compact NS N H L NS100z-MA 25kA 70kA 130kA NS160/250z-MA 36kA 70kA 130kA 70kA 130kA NS400/630z-MA TeSys TeSys Puissance Moteur Power motor P (kW) I (A) Disjoncteurs Circuit Breaker Type Type TeSys Cal (A) Rat (A) TeSys Contacteurs Contactor Type Type TeSys Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) TeSys Nb modules Nbr of modules Mf Mw 0,37 0,98 NS100-MA 2,5 2xLC1-D09 LRD-05 0,63…1 3 6 0,55 1,5 NS100-MA 2,5 2xLC1-D09 LRD-06 1…1,7 3 6 0,75 2 NS100-MA 2,5 2xLC1-D09 LRD-07 1,6...2,5 3 6 1,1 2,5 NS100-MA 6,3 2xLC1-D40 LRD-08 2,5...4 6 9 1,5 3,5 NS100-MA 6,3 2xLC1-D40 LRD-08 2,5...4 6 9 2,2 5 NS100-MA 6,3 2xLC1-D40 LRD-10 4...6 6 9 3 6,5 NS100-MA 12,5 2xLC1-D40 LRD-12 5,5...8 6 9 4 8,4 NS100-MA 12,5 2xLC1-D40 LRD-14 7...10 6 9 5,5 11 NS100-MA 12,5 2xLC1-D40 LRD-16 9...13 6 9 7,5 14,8 NS100-MA 25 2xLC1-D40 LRD-21 12...18 6 9 9 18,1 NS100-MA 25 2xLC1-D40 LRD-3322 17...25 6 9 11 21 NS100-MA 25 2xLC1-D40 LRD-3322 17...25 6 9 15 28,5 NS100-MA 50 2xLC1-D80 LRD-3353 23...32 6 9 18,5 35 NS100-MA 50 2xLC1-D80 LRD-3355 30...40 6 9 22 42 NS100-MA 50 2xLC1-D80 LRD-3357 37...50 6 9 30 57 NS100-MA 100 2xLC1-D80 LRD-3359 48...65 6 9 37 69 NS100-MA 100 2xLC1-D80 LRD-3363 63...80 6 9 45 81 NS100-MA 100 2xLC1-D115 LR9-D5367 60...100 9 12 55 100 NS160-MA 150 2xLC1-D150 LR9-D5369 90...150 9 12 75 135 NS160-MA 150 2xLC1-F150 LR9-F5369 90...150 9 12 90 165 NS250-MA 220 2xLC1-F185 LR9-F5371 132...220 12 ** 110 200 NS250-MA 220 2xLC1-F225 LR9-F5371 132...220 12 ** 132 240 NS400-MA 320 2xLC1-F265 LR9-F7375 200...330 16 ** 160 285 NS400-MA 320 2xLC1-F330 LR9-F7375 200...330 16 ** 200 352 NS630-MA 500 2xLC1-F400 LR9-F7379 300...500 16 ** 220 388 NS630-MA 500 2xLC1-F500 LR9-F7379 300...500 16 ** 250 437 NS630-MA 500 2xLC1-F500 LR9-F7379 300...500 16 ** ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide ** Impossible in Mw type 154 Installation de l’appareillage Switchgear Installation Compact NS100-630z-MA 440 V Type de coordination: 2 Coordination type: 2 2 sens de marche Reverse Performance de coupure / Breaking characteristics Compact NS N H L NS100z-MA 25kA 65kA 130kA NS160/250z-MA 35kA NS400/630z-MA TeSys TeSys Puissance Moteur Power motor P (kW) I (A) 65kA 130kA 65kA 130kA TeSys TeSys Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) TeSys 0,37 0,99 Disjoncteurs Circuit Breaker Type Type NS100-MA 2.5 2xLC1-D09 LRD-05 0,63...1 3 6 0,55 1,36 NS100-MA 2.5 2xLC1-D09 LRD-06 1…1,7 3 6 0,75 1,68 NS100-MA 2.5 2xLC1-D09 LRD-07 1,6…2,5 3 6 1,1 2,37 NS100-MA 2.5 2xLC1-D09 LRD-07 1,6…2,5 3 6 1,5 3,06 NS100-MA 6.3 2xLC1-D40 LRD-08 2,5…4 6 9 2,2 4,42 NS100-MA 6.3 2xLC1-D40 LRD-10 4…6 6 9 3 5,77 NS100-MA 6.3 2xLC1-D40 LRD-10 4…6 6 9 Cal (A) Rat (A) Contacteurs Contactor Type Type TeSys Nb modules Nbr of modules Mf Mw 4 7,9 NS100-MA 12.5 2xLC1-D40 LRD-12 5,5…8 6 9 5,5 10,4 NS100-MA 12.5 2xLC1-D40 LRD-16 9…13 6 9 7,5 13,7 NS100-MA 25 2xLC1-D40 LRD-21 12…18 6 9 9 16,9 NS100-MA 25 2xLC1-D40 LRD-21 12…18 6 9 11 20,1 NS100-MA 25 2xLC1-D40 LRD-3322 17..25 6 9 15 26,5 NS100-MA 50 2xLC1-D80 LRD-3353 23..32 6 9 18,5 32,8 NS100-MA 50 2xLC1-D80 LRD-3355 30...40 6 9 22 39 NS100-MA 50 2xLC1-D80 LRD-3357 37...50 6 9 30 51,5 NS100-MA 100 2xLC1-D80 LRD-3359 48...65 6 9 37 64 NS100-MA 100 2xLC1-D80 LRD-3359 48...65 6 9 45 76 NS100-MA 100 2xLC1-D80 LRD-3363 63...80 9 12 55 90 NS100-MA 100 2xLC1-D115 LR9-D5367 60...100 9 12 75 125 NS160-MA 150 2xLC1-D150 LR9-D5369 90...150 9 12 90 146 NS160-MA 150 2xLC1-F150 LR9-F5369 90...150 12 ** 110 178 NS250-MA 220 2xLC1-F185 LR9-F5371 132...220 12 ** 132 215 NS250-MA 220 2xLC1-F225 LR9-F5371 132...220 12 ** 160 256 NS400-MA 320 2xLC1-F265 LR9-F7375 200...330 16 ** 200 321 NS400-MA 320 2xLC1-F330 LR9-F7375 200...330 16 ** 220 353 NS630-MA 500 2xLC1-F400 LR9-F7379 300...500 16 ** 250 401 NS630-MA 500 2xLC1-F400 LR9-F7379 300...500 16 ** ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide ** Impossible in Mw type 155 Installation de l’appareillage Switchgear Installation Compact NS100-630z-MA 500 V Type de coordination: 2 Coordination type: 2 2 sens de marche Reverse Performance de coupure / Breaking characteristics Compact NS N H L NS100z-MA 18kA 50kA 100kA NS160/250z-MA 30kA 50kA 70kA 50kA 100kA NS400/630z-MA TeSys TeSys Puissance Moteur Power motor P (kW) I (A) Disjoncteurs Circuit Breaker Type Type TeSys Cal (A) Rat (A) TeSys Contacteurs Contactor Type Type TeSys Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) TeSys Nb modules Nbr of modules Mf Mw 0,55 1,21 NS100-MA 2,5 2xLC1-D09 LRD-06 1…1,7 3 6 0,75 1,5 NS100-MA 2,5 2xLC1-D09 LRD-06 1…1,7 3 6 1,1 2 NS100-MA 2,5 2xLC1-D09 LRD-07 1,6…2,5 3 6 1,5 2,6 NS100-MA 6,3 2xLC1-D40 LRD-08 2,5…4 6 9 2,2 3,8 NS100-MA 6,3 2xLC1-D40 LRD-08 2,5…4 6 9 3 5 NS100-MA 6,3 2xLC1-D40 LRD-10 4…6 6 9 4 6,5 NS100-MA 12,5 2xLC1-D40 LRD-12 5,5…8 6 9 9 5,5 9 NS100-MA 12,5 2xLC1-D40 LRD-14 7...10 6 7,5 12 NS100-MA 12,5 2xLC1-D40 LRD-16 9…13 6 9 9 13,9 NS100-MA 25 2xLC1-D40 LRD-21 12…18 6 9 11 18,4 NS100-MA 25 2xLC1-D80 LRD-3322 17..25 6 9 9 15 23 NS100-MA 25 2xLC1-D80 LRD-3322 16..24 6 18,5 28,5 NS100-MA 50 2xLC1-D80 LRD-3353 23..32 6 9 22 33 NS100-MA 50 2xLC1-D80 LRD-3355 30...40 6 9 30 45 NS100-MA 50 2xLC1-D80 LRD-3357 37...50 6 9 37 55 NS100-MA 100 2xLC1-D80 LRD-3359 48...65 6 9 45 65 NS100-MA 100 2xLC1-D80 LRD-3361 55...70 6 9 55 80 NS100-MA 100 2xLC1-D115 LR9-D5367 60…100 9 12 75 105 NS160-MA 150 2xLC1-D150 LR9-D5369 90...150 9 12 90 129 NS160-MA 150 2xLC1-F150 LR9-F5369 90...150 9 ** 110 156 NS250-MA 220 2xLC1-F185 LR9-F5371 132...220 12 ** 132 187 NS250-MA 220 2xLC1-F265 LR9-F5371 132...220 12 ** 160 220 NS400-MA 320 2xLC1-F265 LR9-F7375 200...330 16 ** 200 281 NS400-MA 320 2xLC1-F400 LR9-F7375 200...330 16 ** 220 310 NS400-MA 320 2xLC1-F400 LR9-F7379 300...500 16 ** 250 360 NS630-MA 500 2xLC1-F500 LR9-F7379 300...500 16 ** 315 445 NS630-MA 500 2xLC1-F500 LR9-F7379 300...500 16 ** 355 500 NS630-MA 500 2xLC1-F500 LR9-F7381 380...630 16 ** ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide ** Impossible in Mw type 156 Installation de l’appareillage Switchgear Installation Compact NS100-630z-MA 3.3.1.17. Type de coordination: 1 - - - - - - - - - - - - - - - -Etoile / Triangle (Y/∆) Coordination type: 1 - - - - - - - - - - - - - - - - - - -STAR / DELTA (Y/∆) Démarrage: Normal Start-up: Normal Compact NS100-630z-MA 400/415 V Type de coordination: 1 Coordination type: 1 Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Performance de coupure / Breaking characteristics Compact NS N H L NS100z-MA 25kA 70kA 130kA NS160/250z-MA 35kA 70kA 130kA 70kA 130kA NS400/630z-MA TeSys TeSys Puissance Moteur Power motor P (kW) I (A) 0,37 0,98 0,55 1,5 0,75 2 1,1 2,5 1,5 3,5 2,2 5 3 6,5 4 8,4 5,5 11 7,5 14,8 9 18,1 11 21 15 28,5 18,5 35 22 42 30 57 37 69 45 81 55 100 75 135 90 165 110 200 132 240 160 285 200 352 220 388 250 437 Disjoncteurs Circuit Breaker Type Type NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS160N/H/L-MA NS250N/H/L-MA NS250N/H/L-MA NS400H/L-MA NS400H/L-MA NS630H/L-MA NS630H/L-MA NS630H/L-MA TeSys Cal (A) Rat (A) 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 12,5 25 25 25 50 50 50 100 100 100 100 150 220 220 320 320 500 500 500 ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide TeSys Contacteurs Contactor Type Type 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D12 3 x LC1-D12 3 x LC1-D18 3 x LC1-D18 3 x LC1-D32 3 x LC1-D32 3 x LC1-D40 3 x LC1-D50 3 x LC1-D50 3 x LC1-D80 3 x LC1-D115 3 x LC1-D115 3 x LC1-D150 3 x LC1-F185 3 x LC1-F225 3 x LC1-F265 3 x LC1-F330 TeSys Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LRD-04 0,40...0,63 LRD-05 0,63...1 LRD-06 1...1,7 LRD-06 1...1,7 LRD-07 1,6...2,5 LRD-08 2,5...4 LRD-08 2,5...4 LRD-10 4...6 LRD-12 5,5...8 LRD-14 7...10 LRD-16 9...13 LRD-16 9...13 LRD-21 12...18 LRD-22 16...24 LRD-32 23...32 LRD-35 30...38 LRD-3359 48...65 LRD-3357 37...50 LRD-3361 55...70 LRD-3363 63...80 LRD-4365 80...104 LRD-4369 110...140 LRD-4369 110...140 LR9-F5371 132...220 LR9-F5371 132...220 LR9-F7375 200...330 LR9-F7375 200...330 TeSys Nb modules Nbr of modules Mf Mw 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 9 6 9 6 9 6 9 12 ** 12 ** 12 ** 16 ** 16 ** 20 ** 20 ** ** Impossible in Mw type 157 Installation de l’appareillage Switchgear Installation Compact NS100-630z-MA 440 V Type de coordination: 1 Coordination type: 1 Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Performance de coupure / Breaking characteristics Compact NS N H L NS100z-MA 25kA 65kA 130kA NS160/250z-MA 35kA 65kA 130kA 65kA 130kA NS400/630z-MA TeSys TeSys Puissance Moteur Power motor P (kW) I (A) 0,37 0,99 0,55 1,36 0,75 1,68 1,1 2,37 1,5 3,06 2,2 4,42 3 5,77 4 7,9 5,5 10,4 7,5 13,7 9 16,9 11 20,1 15 26,5 18,5 32,8 22 39 30 51,5 37 64 45 76 55 90 75 125 90 146 110 178 132 215 160 256 200 321 220 353 250 401 Disjoncteurs Circuit Breaker Type Type NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS160N/H/L-MA NS160N/H/L-MA NS250N/H/L-MA NS250N/H/L-MA NS400H/L-MA NS630H/L-MA NS630H/L-MA NS630H/L-MA TeSys Cal (A) Rat (A) 2,5 2,5 2,5 2,5 6,3 6,3 12,5 12,5 12,5 25 25 25 50 50 50 50 100 100 100 150 150 220 220 320 500 500 500 ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide TeSys Contacteurs Contactor Type Type 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D12 3 x LC1-D12 3 x LC1-D18 3 x LC1-D18 3 x LC1-D18 3 x LC1-D32 3 x LC1-D40 3 x LC1-D40 3 x LC1-D50 3 x LC1-D80 3 x LC1-D115 3 x LC1-D115 3 x LC1-D150 3 x LC1-D150 3 x LC1-F225 3 x LC1-F225 3 x LC1-F265 TeSys Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LRD-05 0,63...1 LRD-06 1...1,7 LRD-07 1,6...2,5 LRD-07 1,6...2,5 LRD-07 1,6...2,5 LRD-08 2,5...4 LRD-08 2,5...4 LRD-10 4...6 LRD-12 5,5...8 LRD-14 7...10 LRD-16 9...13 LRD-16 9...13 LRD-21 12...18 LRD-22 16...24 LRD-22 16...24 LRD-32 23...32 LRD-3355 30...40 LRD-3357 37...50 LRD-3359 48...65 LRD-3363 63...80 LRD-4365 80...104 LRD-4365 80...104 LRD-4369 110...140 LR9-D5369 90...150 LR9-F5371 132...220 LR9-F5371 132...220 LR9-F7375 200...330 TeSys Nb modules Nbr of modules Mf Mw 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 9 6 9 6 9 6 9 12 ** 12 ** 12 ** 12 ** 16 ** 16 ** 20 ** ** Impossible in Mw type 158 Installation de l’appareillage Switchgear Installation 3.3.1.18. Compact NS100-630z-MA Type de coordination: 2 - - - - - - - - - - - - - - - -Etoile / Triangle (Y/∆) Coordination Type: 2 - - - - - - - - - - - - - - - - - -STAR / DELTA (Y/∆) Démarrage: normal Start-up: Normal Compact NS100-630z-MA 400/415 V Type de coordination: 2 Coordination type: 2 Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Performance de coupure / Breaking characteristics Compact NS N H L NS100z-MA 25kA 70kA 130kA NS160/250z-MA 35kA 70kA 130kA 70kA 130kA NS400/630z-MA TeSys TeSys Puissance Moteur Power motor P (kW) I (A) Disjoncteurs Circuit Breaker Type Type TeSys TeSys Cal (A) Rat (A) Contacteurs Contactor Type Type TeSys Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) TeSys Nb modules Nbr of modules Mf Mw 1,5 3,5 NS100-MA 6,3 3 x LC1-D40 LRD-08 2,5...4 6 9 2,2 5 NS100-MA 6,3 3 x LC1-D40 LRD-10 4...6 6 9 3 6,5 NS100-MA 12,5 3 x LC1-D40 LRD-12 5,5...8 6 9 4 8,4 NS100-MA 12,5 3 x LC1-D40 LRD-14 7...10 6 9 5,5 11 NS100-MA 12,5 3 x LC1-D40 LRD-16 9...13 6 9 7,5 14,8 NS100-MA 25 3 x LC1-D40 LRD-21 12...18 6 9 9 18,1 NS100-MA 25 3 x LC1-D40 LRD-3322 17...25 6 9 11 21 NS100-MA 25 3 x LC1-D40 LRD-3322 17...25 6 9 15 28,5 NS100-MA 50 3 x LC1-D80 LRD-3353 23...32 6 9 18,5 35 NS100-MA 50 3 x LC1-D80 LRD-3355 30...40 6 9 22 42 NS100-MA 50 3 x LC1-D80 LRD-3357 37...50 6 9 30 57 NS100-MA 100 3 x LC1-D80 LRD-3359 48...65 6 9 37 69 NS100-MA 100 3 x LC1-D80 LRD-3363 63...80 6 9 45 81 NS100-MA 100 3 x LC1-D115 LR9-D5367 60...100 12 ** 55 100 NS160-MA 150 3 x LC1-D150 LR9-D5369 90...150 12 ** 75 135 NS160-MA 150 3 x LC1-F150 LR9-F5369 90...150 12 ** 90 165 NS250-MA 220 3 x LC1-F185 LR9-F5371 132...220 16 ** 110 200 NS250-MA 220 3 x LC1-F225 LR9-F5371 132...220 16 ** 132 240 NS400-MA 320 3 x LC1-F265 LR9-F7375 200...330 20 ** 160 285 NS400-MA 320 3 x LC1-F330 LR9-F7375 200...330 20 200 352 NS630-MA 500 3 x LC1-F400 LR9-F7379 200...330 ** ** ** 220 388 NS630-MA 500 3 x LC1-F400 LR9-F7379 200...330 ** ** 250 437 NS630-MA 500 3 x LC1-F500 LR9-F7379 300...500 ** ** ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide ** Impossible in Mw type 159 Installation de l’appareillage Switchgear Installation Compact NS100-630z-MA 440 V Type de coordination: 2 Coordination type: 2 Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Performance de coupure / Breaking characteristics Compact NS N H L NS100z-MA 25kA 65kA 130kA NS160/250z-MA 35kA 65kA 130kA 65kA 130kA NS400/630z-MA TeSys TeSys Puissance Moteur Power motor P (kW) I (A) 1,5 3,06 Disjoncteurs Circuit Breaker Type Type NS100-MA TeSys TeSys Cal (A) Rat (A) Contacteurs Contactor Type Type 6.3 3 x LC1-D40 TeSys Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LRD-08 4…6 TeSys Nb modules Nbr of modules Mf Mw 6 9 2,2 4,42 NS100-MA 6.3 3 x LC1-D40 LRD-10 4…6 6 9 3 5,77 NS100-MA 6.3 3 x LC1-D40 LRD-10 4…6 6 9 4 7,9 NS100-MA 12.5 3 x LC1-D40 LRD-12 7…10 6 9 5,5 10,4 NS100-MA 12.5 3 x LC1-D40 LRD-16 9…13 6 9 7,5 13,7 NS100-MA 25 3 x LC1-D40 LRD-21 12…18 6 9 9 16,9 NS100-MA 25 3 x LC1-D40 LRD-3322 12…18 6 9 11 20,1 NS100-MA 25 3 x LC1-D40 LRD-3322 16..24 6 9 15 26,5 NS100-MA 50 3 x LC1-D80 LRD-3353 16..24 6 9 18,5 32,8 NS100-MA 50 3 x LC1-D80 LRD-3355 30...40 6 9 22 39 NS100-MA 50 3 x LC1-D80 LRD-3355 37...50 6 9 30 51,5 NS100-MA 100 3 x LC1-D80 LRD-3359 48...65 6 9 37 64 NS100-MA 100 3 x LC1-D80 LRD-3359 48...65 6 9 45 76 100 100 3 x LC1-D80 LRD-3363 63...80 12 ** ** 55 90 NS100-MA NS100-MA 3 x LC1-D115 LR9-D5367 60...100 12 75 125 NS160-MA 150 3 x LC1-D150 LR9-D5369 90...150 12 ** 90 146 NS160-MA 150 3 x LC1-F150 LR9-F5369 90...150 12 ** 110 178 NS250-MA 220 3 x LC1-F185 LR9-F5371 132...220 16 ** 132 215 NS250-MA 220 3 x LC1-F225 LR9-F5371 132...220 16 ** 160 256 NS400-MA 320 3 x LC1-F265 LR9-F7375 200...330 20 ** 200 321 NS400-MA 320 3 x LC1-F330 LR9-F7375 200...330 20 ** 220 353 NS630-MA 500 3 x LC1-F400 LR9-F7379 200...330 20 ** 250 401 NS630-MA 500 3 x LC1-F400 LR9-F7379 200...330 ** ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide ** Impossible in Mw type 160 Installation de l’appareillage Switchgear Installation 3.3.1.19. GV7 Type de coordination: 1 - - - - - - - - - - - - - - - -DOL (Démarrage direct) Coordination Type: 1 - - - - - - - - - - - - - - - - - -DOL (Direct On Line) 400/415 V TeSys GV7 TeSys Puissance Moteur Power motor P (kW) I (A) 15 28,5 18.5 35 22 42 30 57 37 69 45 81 55 100 75 135 90 165 110 200 Pdc BC Icu (kA) Rms (kA) 25 25 25 25 25 25 25 35 35 35 Type de coordination: 1 Coordination type: 1 TeSys Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE40 25...40 GV7-RE40 25...40 GV7-RE50 30...50 GV7-RE80 48...80 GV7-RE80 48...80 GV7-RE100 60...100 GV7-RE150 90...150 GV7-RE150 90...150 GV7-RE220 132...220 GV7-RE220 132...220 GV7 440 V TeSys TeSys Puissance Moteur Power motor P (kW) I (A) 15 26,5 18.5 32,8 22 39 30 51,5 37 64 45 76 55 90 75 125 90 146 110 178 132 215 Pdc BC Icu (kA) Rms (kA) 25 25 25 25 25 25 25 35 35 35 35 Guide Technique V9 / V9 Technical Guide TeSys DOL (Démarrage direct) DOL (Direct On Line) TeSys Nb modules Nbr of modules Contacteur Contactor LC1-D32 LC1-D38 LC1-D50 LC1-D65 LC1-D80 LC1-D95 LC1-D115 LC1-D150 LC1-F185 LC1-F225 Mf Mw 3 3 3 3 3 3 3 3 3 3 3 3 6 6 6 6 9 9 9 9 Type de coordination: 1 Coordination type: 1 TeSys Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE40 25...40 GV7-RE40 25...40 GV7-RE50 30...50 GV7-RE80 48...80 GV7-RE80 48...80 GV7-RE80 48...80 GV7-RE100 60...100 GV7-RE150 90...150 GV7-RE150 90...150 GV7-RE220 132...220 GV7-RE220 132...220 TeSys DOL (Démarrage direct) DOL (Direct On Line) TeSys Nb modules Nbr of modules Contacteur Contactor LC1-D32 LC1-D38 LC1-D40 LC1-D65 LC1-D65 LC1-D80 LC1-D115 LC1-D150 LC1-F185 LC1-F225 LC1-F225 Mf Mw 3 3 3 3 3 3 3 3 3 3 3 3 6 6 6 6 9 9 9 9 9 9 161 Installation de l’appareillage Switchgear Installation GV7 500 V TeSys TeSys Puissance Moteur Power motor P (kW) I (A) 18.5 28,5 22 33 30 45 45 65 55 80 75 105 90 129 110 156 132 187 160 220 Pdc BC Icu (kA) Rms (kA) 18 18 18 18 18 30 30 30 30 30 Guide Technique V9 / V9 Technical Guide Type de coordination: 1 Coordination type: 1 TeSys Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE40 25...40 GV7-RE50 30...50 GV7-RE50 30...50 GV7-RE80 48...80 GV7-RE80 48...80 GV7-RE150 90...150 GV7-RE150 90...150 GV7-RE220 132...220 GV7-RE220 132...220 GV7-RE220 132...220 TeSys DOL (Démarrage direct) DOL (Direct On Line) TeSys Nb modules Nbr of modules Contacteur Contactor LC1-D38 LC1-D40 LC1-D50 LC1-D65 LC1-D80 LC1-D115 LC1-D150 LC1-F185 LC1-F265 LC1-F265 Mf Mw 3 3 3 3 3 3 3 3 3 3 6 6 6 6 9 9 9 9 9 9 162 Installation de l’appareillage Switchgear Installation 3.3.1.20. GV7 Type de coordination: 2 - - - - - - - - - - - - - - - -DOL (Démarrage direct) Coordination Type: 2 - - - - - - - - - - - - - - - - - -DOL (Direct On Line) 400/415 V TeSys GV7 TeSys Puissance Moteur Power motor P (kW) I (A) 15 28,5 18,5 35 22 42 30 57 37 69 45 81 55 100 75 135 90 165 110 200 Pdc BC Icu (kA) Rms (kA) 70 70 70 70 70 70 70 70 70 70 Type de coordination: 2 Coordination type: 2 TeSys Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RS40 25…40 GV7-RS40 25…40 GV7-RS50 30…50 GV7-RS80 48…80 GV7-RS80 48…80 GV7-RS100 60…100 GV7-RS150 90…150 GV7-RS150 90…150 GV7-RS220 132…220 GV7-RS220 132…220 GV7 440 V TeSys TeSys Puissance Moteur Power motor P (kW) I (A) 15 26,5 18,5 32,8 22 39 30 51,5 37 64 45 76 55 90 75 125 90 146 110 178 132 215 Pdc BC Icu (kA) Rms (kA) 65 65 65 65 65 65 65 65 65 65 65 Guide Technique V9 / V9 Technical Guide TeSys DOL (Démarrage direct) DOL (Direct On Line) TeSys Nb modules Nbr of modules Contacteur Contactor LC1-D40 LC1-D50 LC1-D80 LC1-D80 LC1-D80 LC1-D115 LC1-D150 LC1-F150 LC1-F185 LC1-F225 Mf Mw 3 3 3 3 3 3 3 3 3 3 6 6 6 6 6 6 9 9 9 9 Type de coordination: 2 Coordination type: 2 TeSys Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RS40 25...40 GV7-RS40 25...40 GV7-RS40 25...40 GV7-RS80 48...80 GV7-RS80 48...80 GV7-RS80 48...80 GV7-RS100 60...100 GV7-RS150 90...150 GV7-RS150 90...150 GV7-RS220 132...220 GV7-RS220 132...220 TeSys DOL (Démarrage direct) DOL (Direct On Line) TeSys Nb modules Nbr of modules Contacteur Contactor LC1-D40 LC1-D50 LC1-D80 LC1-D80 LC1-D80 LC1-D115 LC1-D115 LC1-D150 LC1-F150 LC1-F185 LC1-F225 Mf Mw 3 3 3 3 3 3 3 3 3 3 6 6 6 6 6 6 9 9 9 9 9 9 163 Installation de l’appareillage Switchgear Installation GV7 500 V TeSys TeSys Puissance Moteur Power motor P (kW) I (A) 18,5 28,5 22 33 30 45 37 55 45 65 55 80 90 129 110 156 132 187 160 220 Pdc BC Icu (kA) Rms (kA) 50 50 50 50 50 50 50 50 50 50 Guide Technique V9 / V9 Technical Guide Type de coordination: 2 Coordination type: 2 TeSys Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RS40 25…40 GV7-RS40 25…40 GV7-RS50 30…50 GV7-RS80 48…80 GV7-RS80 48…80 GV7-RS80 48…80 GV7-RS150 90…150 GV7-RS220 132...220 GV7-RS220 132…220 GV7-RS220 132…220 TeSys DOL (Démarrage direct) DOL (Direct On Line) TeSys Nb modules Nbr of modules Contacteur Contactor LC1-D40 LC1-D50 LC1-D80 LC1-D80 LC1-D115 LC1-D115 LC1-D150 LC1-F185 LC1-F265 LC1-F265 Mf Mw 3 3 3 3 3 3 3 3 6 6 6 6 6 6 9 9 9 9 9 9 164 Installation de l’appareillage Switchgear Installation 3.3.1.21. GV7 Type de coordination: 1 - - - - - - - - - - - - - - - -2 sens de marche Coordination Type: 1 - - - - - - - - - - - - - - - - - -Reverse 400/415 V TeSys GV7 TeSys Puissance Moteur Power motor P (kW) I (A) 15 28,5 18.5 35 22 42 30 57 37 69 45 81 55 100 75 135 90 165 110 200 Pdc BC Icu (kA) Rms (kA) 25 25 25 25 25 25 25 35 35 35 Type de coordination: 1 Coordination type: 1 TeSys Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE40 25...40 GV7-RE40 25...40 GV7-RE50 30...50 GV7-RE80 48...80 GV7-RE80 48...80 GV7-RE100 60...100 GV7-RE150 90...150 GV7-RE150 90...150 GV7-RE220 132...220 GV7-RE220 132...220 TeSys GV7 TeSys TeSys Puissance Moteur Power motor P (kW) I (A) 15 26,5 18.5 32,8 22 39 30 51,5 37 64 45 76 55 90 75 125 90 146 110 178 132 215 Pdc BC Icu (kA) Rms (kA) 25 25 25 25 25 25 25 35 35 35 35 Contacteur Contactor 2 x LC1-D32 2 x LC1-D38 2 x LC1-D50 2 x LC1-D65 2 x LC1-D80 2 x LC1-D95 2 x LC1-D115 2 x LC1-D150 2 x LC1-F185 2 x LC1-F225 Mf Mw 6 6 6 6 6 6 6 6 6 6 6 6 9 12 9 12 12 ** 12 ** ** Impossible in Mw type Type de coordination: 1 Coordination type: 1 TeSys Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE40 25...40 GV7-RE40 25...40 GV7-RE50 30...50 GV7-RE80 48...80 GV7-RE80 48...80 GV7-RE80 48...80 GV7-RE100 60...100 GV7-RE150 90...150 GV7-RE150 90...150 GV7-RE220 132...220 GV7-RE220 132...220 ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide TeSys Nb modules Nbr of modules ** Impossible en type Mw 440 V 2 sens de marche Reverse TeSys 2 sens de marche Reverse TeSys Nb modules Nbr of modules Contacteur Contactor 2 x LC1-D32 2 x LC1-D38 2 x LC1-D40 2 x LC1-D65 2 x LC1-D65 2 x LC1-D80 2 x LC1-D115 2 x LC1-D150 2 x LC1-F185 2 x LC1-F225 2 x LC1-F225 Mf Mw 6 6 6 6 6 6 6 6 6 6 6 6 9 12 9 12 12 ** 12 ** 12 ** ** Impossible in Mw type 165 Installation de l’appareillage Switchgear Installation GV7 500 V TeSys TeSys Puissance Moteur Power motor P (kW) I (A) 18.5 28,5 22 33 30 45 45 65 55 80 75 105 90 129 110 156 132 187 160 220 Pdc BC Icu (kA) Rms (kA) 18 18 18 18 18 30 30 30 30 30 Type de coordination: 1 Coordination type: 1 TeSys Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE40 25...40 GV7-RE50 30...50 GV7-RE50 30...50 GV7-RE80 48...80 GV7-RE80 48...80 GV7-RE150 90...150 GV7-RE150 90...150 GV7-RE220 132...220 GV7-RE220 132...220 GV7-RE220 132...220 ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide TeSys 2 sens de marche Reverse TeSys Nb modules Nbr of modules Contacteur Contactor 2 x LC1-D38 2 x LC1-D40 2 x LC1-D50 2 x LC1-D65 2 x LC1-D80 2 x LC1-D115 2 x LC1-D150 2 x LC1-F185 2 x LC1-F265 2 x LC1-F265 Mf Mw 6 6 6 6 6 6 6 6 6 6 9 12 9 12 12 ** 12 ** 12 ** ** Impossible in Mw type 166 Installation de l’appareillage Switchgear Installation 3.3.1.22. GV7 Type de coordination: 2 - - - - - - - - - - - - - - - -2 sens de marche Coordination Type: 2 - - - - - - - - - - - - - - - - - -Reverse 400/415 V TeSys GV7 TeSys Puissance Moteur Power motor P (kW) I (A) 15 28,5 18,5 35 22 42 30 57 37 69 45 81 55 100 75 135 90 165 110 200 Pdc BC Icu (kA) Rms (kA) 70 70 70 70 70 70 70 70 70 70 Type de coordination: 2 Coordination type: 2 TeSys Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RS40 25…40 GV7-RS40 25…40 GV7-RS50 30…50 GV7-RS80 48…80 GV7-RS80 48…80 GV7-RS100 60…100 GV7-RS150 90…150 GV7-RS150 90…150 GV7-RS220 132…220 GV7-RS220 132…220 TeSys GV7 TeSys TeSys Puissance Moteur Power motor P (kW) I (A) 15 26,5 18,5 32,8 22 39 30 51,5 37 64 45 76 55 90 75 125 90 146 110 178 132 215 Pdc BC Icu (kA) Rms (kA) 65 65 65 65 65 65 65 65 65 65 65 Contacteur Contactor 2xLC1-D40 2xLC1-D50 2xLC1-D80 2xLC1-D80 2xLC1-D80 2xLC1-D115 2xLC1-D150 2xLC1-F150 2xLC1-F185 2xLC1-F225 Mf Mw 6 6 6 6 6 6 6 6 6 6 9 12 9 12 9 ** 12 ** 12 ** ** Impossible in Mw type Type de coordination: 2 Coordination type: 2 TeSys Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RS40 25...40 GV7-RS40 25...40 GV7-RS40 25...40 GV7-RS80 48...80 GV7-RS80 48...80 GV7-RS80 48...80 GV7-RS100 60...100 GV7-RS150 90...150 GV7-RS150 90...150 GV7-RS220 132...220 GV7-RS220 132...220 ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide TeSys Nb modules Nbr of modules ** Impossible en type Mw 440 V 2 sens de marche Reverse TeSys 2 sens de marche Reverse TeSys Nb modules Nbr of modules Contacteur Contactor 2xLC1-D40 2xLC1-D50 2xLC1-D80 2xLC1-D80 2xLC1-D80 2xLC1-D115 2xLC1-D115 2xLC1-D150 2xLC1-F150 2xLC1-F185 2xLC1-F225 Mf Mw 6 6 6 6 6 6 6 6 6 6 9 12 9 12 9 12 12 ** 12 ** 12 ** ** Impossible in Mw type 167 Installation de l’appareillage Switchgear Installation GV7 500 V TeSys TeSys Puissance Moteur Power motor P (kW) I (A) Pdc BC Icu (kA) Rms (kA) Type de coordination: 2 Coordination type: 2 TeSys TeSys Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) 2 sens de marche Reverse TeSys Nb modules Nbr of modules Contacteur Contactor Mf Mw 18,5 28,5 50 GV7-RS40 25…40 2xLC1-D40 6 6 22 33 50 GV7-RS40 25…40 2xLC1-D50 6 6 30 45 50 GV7-RS50 30…50 2xLC1-D80 6 6 37 55 50 GV7-RS80 48…80 2xLC1-D80 6 6 45 65 50 GV7-RS80 48…80 2xLC1-D115 9 12 55 80 50 GV7-RS80 48…80 2xLC1-D115 9 12 90 129 50 GV7-RS150 90…150 2xLC1-D150 9 12 110 156 50 GV7-RS220 132...220 2xLC1-F185 12 ** 132 187 50 GV7-RS220 132…220 2xLC1-F265 12 ** 160 220 50 GV7-RS220 132…220 2xLC1-F265 12 ** ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide ** Impossible in Mw type 168 Installation de l’appareillage Switchgear Installation 3.3.1.23. GV7 Type de coordination: 1 - - - - - - - - - - - - - - - -Etoile / Triangle (Y/∆) Coordination Type: 1 - - - - - - - - - - - - - - - - - -STAR / DELTA (Y/∆) Démarrage: Normal Start-up: Normal 400/415 V TeSys GV7 TeSys Puissance Moteur Power motor P (kW) I (A) 15 28,5 18,5 35 22 42 30 57 37 69 45 81 55 100 75 135 90 165 110 200 Pdc BC Icu (kA) Rms (kA) 25 25 25 25 25 25 25 35 35 35 TeSys Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE40 25...40 GV7-RE40 25...40 GV7-RE50 30...50 GV7-RE80 48...80 GV7-RE80 48...80 GV7-RE100 60...100 GV7-RE100 60...100 GV7-RE150 90...150 GV7-RE220 132...220 GV7-RE220 132...220 TeSys GV7 TeSys TeSys Puissance Moteur Power motor P (kW) I (A) 15 26,5 18,5 32,8 22 39 30 51,5 37 64 45 76 55 90 75 125 90 146 110 178 132 215 Pdc BC Icu (kA) Rms (kA) 25 25 25 25 25 25 25 35 35 35 35 Contacteur Contactor 3 x LC1-D18 3 x LC1-D18 3 x LC1-D32 3 x LC1-D32 3 x LC1-D40 3 x LC1-D50 3 x LC1-D50 3 x LC1-D80 3 x LC1-D115 3 x LC1-D115 Mf Mw 6 6 6 6 6 6 6 6 6 9 6 9 6 9 6 9 12 ** 12 ** ** Impossible in Mw type Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Type de coordination: 1 Coordination type: 1 TeSys Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE40 25...40 GV7-RE40 25...40 GV7-RE50 30...50 GV7-RE80 48...80 GV7-RE80 48...80 GV7-RE80 48...80 GV7-RE100 60...100 GV7-RE150 90...150 GV7-RE150 90...150 GV7-RE220 132...220 GV7-RE220 132...220 ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide TeSys Nb modules Nbr of modules ** Impossible en type Mw 440 V Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Type de coordination: 1 Coordination type: 1 TeSys TeSys Nb modules Nbr of modules Contacteur Contactor 3 x LC1-D18 3 x LC1-D18 3 x LC1-D18 3 x LC1-D32 3 x LC1-D40 3 x LC1-D50 3 x LC1-D50 3 x LC1-D80 3 x LC1-D115 3 x LC1-D115 3 x LC1-D150 Mf Mw 6 6 6 6 6 6 6 6 6 9 6 9 6 9 6 9 12 ** 12 ** 12 ** ** Impossible in Mw type 169 Installation de l’appareillage Switchgear Installation 3.3.1.24. GV7 Type de coordination: 2 - - - - - - - - - - - - - - - -Etoile / Triangle (Y/∆) Coordination Type: 2 - - - - - - - - - - - - - - - - - -STAR / DELTA (Y/∆) Démarrage: Normal Start-up: Normal 400/415 V TeSys GV7 TeSys Puissance Moteur Power motor P (kW) I (A) 15 28,5 18,5 35 22 42 30 57 37 69 45 81 55 100 75 135 90 165 110 200 Pdc BC Icu (kA) Rms (kA) 70 70 70 70 70 70 70 70 70 70 TeSys Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RS40 25...40 GV7-RS40 25...40 GV7-RS50 30...50 GV7-RS80 48...80 GV7-RS80 48...80 GV7-RS100 60...100 GV7-RS100 60...100 GV7-RS150 90...150 GV7-RS220 132...220 GV7-RS220 132...220 TeSys GV7 TeSys TeSys Puissance Moteur Power motor P (kW) I (A) 15 26,5 18,5 32,8 22 39 30 51,5 37 64 45 76 55 90 75 125 90 146 110 178 132 215 Pdc BC Icu (kA) Rms (kA) 65 65 65 65 65 65 65 65 65 65 65 Contacteur Contactor 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D115 3 x LC1-D150 3 x LC1-F150 3 x LC1-F185 3 x LC1-F225 Mf Mw 6 9 6 9 6 9 6 9 6 9 12 ** 12 ** 12 ** 16 ** 16 ** ** Impossible in Mw type Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Type de coordination: 2 Coordination type: 2 TeSys Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RS40 25...40 GV7-RS40 25...40 GV7-RS40 25...40 GV7-RS80 48...80 GV7-RS80 48...80 GV7-RS80 48...80 GV7-RS100 60...100 GV7-RS150 90...150 GV7-RS150 90...150 GV7-RS220 132...220 GV7-RS220 132...220 ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide TeSys Nb modules Nbr of modules ** Impossible en type Mw 440 V Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Type de coordination: 2 Coordination type: 2 TeSys TeSys Nb modules Nbr of modules Contacteur Contactor 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D115 3 x LC1-D115 3 x LC1-D150 3 x LC1-F150 3 x LC1-F185 3 x LC1-F225 Mf Mw 6 9 6 9 6 9 6 9 6 9 6 ** 12 ** 12 ** 12 ** 16 ** 16 ** ** Impossible in Mw type 170 Installation de l’appareillage Switchgear Installation INTEGRAL 3.3.1.25. Contacteurs-Disjoncteurs INTEGRAL - - - - - -DOL (Démarrage direct) INTEGRAL contactors-circuit breakers - - - - -DOL (Direct On Line) Coordination totale Total coordination 220/230 V Contacteurs-Disjoncteurs INTEGRAL INTEGRAL contactors-circuit breakers TeSys TeSys Puissance Moteur Power motor P (kW) I (A) Icu (kA) Rms (kA) 0,06 0,38 70 0,09 0,65 70 0,12 0,75 70 0,18 1,04 70 0,25 1,47 70 0,37 2 70 - - - 0,55 2,8 70 0,75 3,6 70 1,1 5,2 70 - - - 1,5 6,8 70 2,2 9,6 70 3 11,5 70 - - - 4 14,5 70 - - - 5,5 2,2 70 7,5 28 70 TeSys DOL (Démarrage direct) DOL (Direct On Line) TeSys TeSys Contacteur-disjoncteur sans Module de protection Contactor-Circuit Breaker without protection Module Sectionnement par Sectionnement par pôles principaux pôles spécifiques Isolation by main poles Isolation by specifics poles LD1-LB030 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LC030 LD4-LC130 LD1-LC030 LD4-LC130 *: Icu = 40 kA pour LD1-LB; Icu = 70 kA pour LDz-LC. **: En fonction du nombre d’auxiliaires. LD1-LB: LDz-LC: LDz-LD: Guide Technique V9 / V9 Technical Guide TeSys Module de protection Protection Module Référence Reference Nb modules Nbr of modules Mf Mw LB1-LB03P03 3 3 ou 6** LB1-LB03P05 3 3 ou 6** LB1-LC03M05 3 - LB1-LB03P06 3 3 ou 6** LB1-LC03M06 3 - LB1-LB03P07 3 3 ou 6** LB1-LC03M07 3 - LB1-LB03P08 3 3 ou 6** LB1-LC03M08 3 - LB1-LB03P10 3 3 ou 6** LB1-LC03M10 3 - LB1-LB03P13 3 3 ou 6** LB1-LC03M13 3 - LB1-LB03P17 3 3 ou 6** LB1-LC03M17 3 - LB1-LB03P21 3 3 ou 6** LB1-LC03M17 3 - LB1-LC03M22 3 3 ou 6** LB1-LC03M53 3 3 ou 6** *: Rms = 40 kA for LD1-LB; Rms = 70 kA for LDz-LC. **: According to the number of auxiliaries. Integral 18. Integral 32. Integral 63. 171 Installation de l’appareillage Switchgear Installation 400/415 V Contacteurs-Disjoncteurs INTEGRAL INTEGRAL contactors-circuit breakers TeSys TeSys Puissance Moteur Power motor P (kW) I (A) Icu (kA) Rms (kA) 0,06 0,22 70 0,09 0,36 70 0,12 0,42 70 0,18 0,6 70 0,25 0,88 70 - - - 0,37 1 70 0,55 1,5 70 0,75 2 70 - - - 1,1 2,5 70 1,5 3,5 70 2,2 5 70 - - - 3 6,5 70 4 8,4 70 5,5 11 70 7,5 14,8 70 9 18,1 70 - - - 11 21 70 15 28,5 70 18,5 35 70 22 42 70 30 57 70 TeSys DOL (Démarrage direct) DOL (Direct On Line) TeSys TeSys Contacteur-disjoncteur sans Module de protection Contactor-Circuit Breaker without protection Module Sectionnement par Sectionnement par pôles principaux pôles spécifiques Isolation by main poles Isolation by specifics poles LD1-LB030 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LC030 LD4-LC130 LD1-LC030 LD4-LC130 LD1-LD030 LD4-LD130 LD1-LD030 LD4-LD130 LD1-LD030 LD4-LD130 *: Icu = 40 kA pour LD1-LB; Icu = 70 kA pour LDz-LC. **: En fonction du nombre d’auxiliaires. LD1-LB: LDz-LC: LDz-LD: Guide Technique V9 / V9 Technical Guide TeSys Module de protection Protection Module Référence Reference Nb modules Nbr of modules Mf Mw LB1-LB03P02 3 3 ou 6** LB1-LB03P03 3 3 ou 6** LB1-LC03M03 - - LB1-LB03P04 3 3 ou 6** LB1-LC03M04 3 - LB1-LB03P05 3 3 ou 6** LB1-LC03M05 3 - LB1-LB03P06 3 3 ou 6** LB1-LC03M06 3 - LB1-LB03P07 3 3 ou 6** LB1-LC03M07 3 - LB1-LB03P08 3 3 ou 6** LB1-LC03M08 3 - LB1-LB03P10 3 3 ou 6** LB1-LC03M10 3 - LB1-LB03P13 3 3 ou 6** LB1-LC03M13 3 - LB1-LB03P17 3 3 ou 6** LB1-LC03M17 3 - LB1-LB03P21 3 3 ou 6** LB1-LC03M22 3 - LB1-LC03M22 3 3 ou 6** LB1-LC03M53 3 3 ou 6** LB1-LD03M55 6 6 LB1-LD03M57 6 6 LB1-LD03M61 6 6 *: Rms = 40 kA for LD1-LB; Rms = 70 kA for LDz-LC. **: According to the number of auxiliaries. Integral 18. Integral 32. Integral 63. 172 Installation de l’appareillage Switchgear Installation 440 V Contacteurs-Disjoncteurs INTEGRAL INTEGRAL contactors-circuit breakers TeSys TeSys Puissance Moteur Power motor P (kW) I (A) Icu (kA) Rms (kA) 0,06 0,19 70 0,09 0,28 70 0,12 0,37 70 - - - 0,18 0,55 70 0,25 0,76 70 - - - 0,37 1 70 0,55 1,36 70 0,75 1,68 70 1,1 2,37 70 - - - 1,5 3,06 70 2,2 4,42 * 3 5,77 * 4 7,9 * - - - 5,5 10,4 * 7,5 13,7 * 9 16,9 * 11 20,1 70 15 26,5 30 18,5 32,8 70 22 39 70 30 51,5 40 33 58,5 40 TeSys DOL (Démarrage direct) DOL (Direct On Line) TeSys TeSys Contacteur-disjoncteur sans Module de protection Contactor-Circuit Breaker without protection Module Sectionnement par Sectionnement par pôles principaux pôles spécifiques Isolation by main poles Isolation by specifics poles LD1-LB030 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LC030 LD4-LC130 LD1-LC030 LD4-LC130 LD1-LD030 LD4-LD130 LD1-LD030 LD4-LD130 - *: Icu = 40 kA pour LD1-LB; Icu = 70 kA pour LDz-LC. **: En fonction du nombre d’auxiliaires. LD1-LB: LDz-LC: LDz-LD: Guide Technique V9 / V9 Technical Guide TeSys Module de protection Protection Module Référence Reference Nb modules Nbr of modules Mf Mw LB1-LB03P02 3 3 ou 6** LB1-LB03P03 3 3 ou 6** LB1-LC03M03 3 - LB1-LB03P04 3 3 ou 6** LB1-LC03M04 3 - LB1-LB03P05 3 3 ou 6** LB1-LC03M05 3 - LB1-LB03P06 3 3 ou 6** LB1-LC03M06 3 - LB1-LB03P07 3 3 ou 6** - LB1-LC03M07 3 LB1-LB03P08 3 3 ou 6** LB1-LC03M08 3 - LB1-LB03P10 3 3 ou 6** LB1-LC03M10 3 - LB1-LB03P13 3 3 ou 6** LB1-LC03M13 3 - LB1-LB03P17 3 3 ou 6** LB1-LC03M17 3 - LB1-LB03P21 3 3 ou 6** LB1-LC03M22 3 - LB1-LC03M22 3 3 ou 6** LB1-LC03M53 3 3 ou 6** LB1-LD03M55 6 6 - - - LB1-LD03M61 6 6 - - - *: Rms = 40 kA for LD1-LB; Rms = 70 kA for LDz-LC. **: According to the number of auxiliaries. Integral 18. Integral 32. Integral 63. 173 Installation de l’appareillage Switchgear Installation INTEGRAL 3.3.1.26. Contacteurs-Disjoncteurs INTEGRAL - - - - - -2 sens de marche INTEGRAL contactors-circuit breakers - - - - -Reverse Coordination totale Total coordination 220/230 V Contacteurs-Disjoncteurs INTEGRAL INTEGRAL contactors-circuit breakers TeSys TeSys Puissance Moteur Power motor P (kW) I (A) Icu (kA) Rms (kA) 0,06 0,38 70 0,09 0,65 70 0,12 0,75 70 0,18 1,04 70 0,25 1,47 70 0,37 2 70 - - - 0,55 2,8 70 0,75 3,6 70 1,1 5,2 70 - - - 1,5 6,8 70 2,2 9,6 70 3 11,5 70 - - - 4 14,5 70 - - - 5,5 2,2 70 7,5 28 70 TeSys 2 sens de marche Reverse TeSys TeSys Contacteur-disjoncteur sans Module de protection Contactor-Circuit Breaker without protection Module Sectionnement par Sectionnement par pôles principaux pôles spécifiques Isolation by main poles Isolation by specifics poles LD5-LB130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LC130 LD5-LC130 *: Icu = 40 kA pour LD5-LB; Icu = 70 kA pour LD5-LC. LD5-LB: LD5-LC: LD5-LD: Guide Technique V9 / V9 Technical Guide *: TeSys Module de protection Protection Module Référence Reference Nb modules Nbr of modules Mf Mw LB1-LB03P03 3 6 LB1-LB03P05 3 6 LB1-LC03M05 6 - LB1-LB03P06 3 6 LB1-LC03M06 6 - LB1-LB03P07 3 6 LB1-LC03M07 6 - LB1-LB03P08 3 6 LB1-LC03M08 6 - LB1-LB03P10 3 6 LB1-LC03M10 6 - LB1-LB03P13 3 6 LB1-LC03M13 6 - LB1-LB03P17 3 6 LB1-LC03M17 6 - LB1-LB03P21 3 6 LB1-LC03M17 6 - LB1-LC03M22 6 6 LB1-LC03M53 6 6 Rms = 40 kA for LD5-LB; Rms = 70 kA for LD5-LC. Integral 18. Integral 32. Integral 63. 174 Installation de l’appareillage Switchgear Installation 400/415 V Contacteurs-Disjoncteurs INTEGRAL INTEGRAL contactors-circuit breakers TeSys TeSys Puissance Moteur Power motor P (kW) I (A) Icu (kA) Rms (kA) 0,06 0,22 70 0,09 0,36 70 - - - 0,12 0,42 70 0,18 0,6 70 0,25 0,88 70 - - - 0,37 1 70 0,55 1,5 70 0,75 2 70 - - - 1,1 2,5 70 1,5 3,5 70 2,2 5 70 - - - 3 6,5 70 4 8,4 70 5,5 11 70 7,5 14,8 70 9 18,1 70 - - - 11 21 70 15 28,5 70 18,5 35 70 22 42 70 30 57 70 TeSys 2 sens de marche Reverse TeSys TeSys Contacteur-disjoncteur sans Module de protection Contactor-Circuit Breaker without protection Module Sectionnement par Sectionnement par pôles principaux pôles spécifiques Isolation by main poles Isolation by specifics poles LD5-LB130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LC130 LD5-LC130 LD5-LD130 LD5-LD130 LD5-LD130 *: Icu = 40 kA pour LD5-LB; Icu = 70 kA pour LD5-LC. LD5-LB: LD5-LC: LD5-LD: Guide Technique V9 / V9 Technical Guide *: TeSys Module de protection Protection Module Référence Reference Nb modules Nbr of modules Mf Mw LB1-LB03P02 3 6 LB1-LB03P03 3 6 LB1-LC03M03 6 - LB1-LB03P04 3 6 LB1-LC03M04 6 - LB1-LB03P05 3 6 LB1-LC03M05 6 - LB1-LB03P06 3 6 LB1-LC03M06 6 - LB1-LB03P07 3 6 LB1-LC03M07 6 - LB1-LB03P08 3 6 LB1-LC03M08 6 - LB1-LB03P10 3 6 LB1-LC03M10 6 - LB1-LB03P13 3 6 LB1-LC03M13 6 - LB1-LB03P17 3 6 LB1-LC03M17 6 - LB1-LB03P21 3 6 LB1-LC03M22 6 - LB1-LC03M22 6 6 LB1-LC03M53 6 6 LB1-LD03M55 6 6** LB1-LD03M57 6 6** LB1-LD03M61 6 6** Rms = 40 kA for LD5-LB; Rms = 70 kA for LD5-LC. Integral 18. Integral 32. Integral 63. 175 Installation de l’appareillage Switchgear Installation 440 V Contacteurs-Disjoncteurs INTEGRAL INTEGRAL contactors-circuit breakers TeSys TeSys Puissance Moteur Power motor P (kW) I (A) Icu (kA) Rms (kA) 0,06 0,19 70 0,09 0,28 70 0,12 0,37 70 - - - 0,18 0,55 70 0,25 0,76 70 - - - 0,37 1 70 0,55 1,36 70 0,75 1,68 70 1,1 2,37 70 - - - 1,5 3,06 70 2,2 4,42 * 3 5,77 * 4 7,9 * - - - 5,5 10,4 * 7,5 13,7 * 9 16,9 * - - - 11 20,1 70 15 26,5 30 18,5 32,8 70 22 39 70 30 51,5 40 33 58,5 40 TeSys 2 sens de marche Reverse TeSys TeSys Contacteur-disjoncteur sans Module de protection Contactor-Circuit Breaker without protection Module Sectionnement par Sectionnement par pôles principaux pôles spécifiques Isolation by main poles Isolation by specifics poles LD5-LB130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LC130 LD5-LC130 LD5-LD130 LD5-LD130 - *: Icu = 40 kA pour LD5-LB; Icu = 70 kA pour LD5-LC. **: 9 avec transformateur LD5-LB: LD5-LC: LD5-LD: Guide Technique V9 / V9 Technical Guide TeSys Module de protection Protection Module Référence Reference Nb modules Nbr of modules Mf Mw LB1-LB03P02 3 6 LB1-LB03P03 3 6 LB1-LC03M03 6 - LB1-LB03P04 3 6 LB1-LC03M04 6 - LB1-LB03P05 3 6 LB1-LC03M05 6 - LB1-LB03P06 3 6 LB1-LC03M06 6 - LB1-LB03P07 3 6 LB1-LC03M07 6 - LB1-LB03P08 3 6 LB1-LC03M08 6 - LB1-LB03P10 3 6 LB1-LC03M10 6 - LB1-LB03P13 3 6 LB1-LC03M13 6 - LB1-LB03P17 3 6 LB1-LC03M17 6 - LB1-LB03P21 3 6 LB1-LC03M22 6 - LB1-LC03M22 6 6 LB1-LC03M53 6 6 LB1-LD03M55 6 6** - - - LB1-LD03M61 6 6** - - - *: Rms = 40 kA for LD5-LB; Rms = 70 kA for LD5-LC. **: 9 with transformer Integral 18. Integral 32. Integral 63. 176 Installation de l’appareillage Switchgear Installation 3.3.1.27. GV2-P Type de coordination: 1 - - - - - - - - - - - - - - - -DOL monophasé (Démarrage direct) Coordination type: 1 - - - - - - - - - - - - - - - - - - -Single phase - DOL (Direct On Line) GV2-P 220/230 V TeSys TeSys P (kW) I (A) 0,09 0,5 0,12 1,0 0,25 2,0 0,37 3,0 0,55 4,0 0,75 5,0 1,1 7,4 1,5 9,3 1,8 11,7 2,2 16,0 3 18,3 4 23,5 3.3.1.28. Icu (kA) Rms (kA) 50 50 50 50 50 50 50 50 50 50 50 50 Type de coordination: 1DOL monophasé (Démarrage direct) Coordination type: 1Single phase - DOL (Direct On Line) TeSys Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV2-P04 0,4..0,63 GV2-P06 1...1,6 GV2-P07 1,6...2,5 GV2-P08 2,5...4 GV2-P10 4...6,3 GV2-P10 4...6,3 GV2-P14 6...10 GV2-P14 6...10 GV2-P16 9...14 GV2-P20 13...18 GV2-P21 17...23 GV2-P22 20...25 TeSys Contacteur Contactor LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K09 LC1-K09 LC1-D12 LC1-D18 LC1-D25 LC1-D25 Mw 3 3 3 3 3 3 3 3 3 3 3 3 GV2-P Type de coordination: 2 - - - - - - - - - - - - - - - -DOL monophasé (Démarrage direct) Coordination type: 2 - - - - - - - - - - - - - - - - - - -Single phase - DOL (Direct On Line) 220/230 V TeSys GV2-P TeSys P (kW) I (A) 0,09 0,5 0,12 1,0 0,25 2,0 0,37 3,0 0,55 4,0 0,75 5,0 1,1 7,4 1,5 9,3 1,8 11,7 2,2 16 3 18,3 4 23,5 Icu (kA) Rms (kA) 130 130 130 130 130 130 130 130 130 130 130 130 Guide Technique V9 / V9 Technical Guide Type de coordination: 2DOL monophasé (Démarrage direct) Coordination type: 2Single phase - DOL (Direct On Line) TeSys Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV2-P04 0,4..0,63 GV2-P06 1...1,6 GV2-P07 1,6...2,5 GV2-P08 2,5...4 GV2-P10 4...6,3 GV2-P10 4...6,3 GV2-P14 6...10 GV2-P14 6...10 GV2-P16 9...14 GV2-P20 13...18 GV2-P21 17...23 GV2-P22 20...25 TeSys Contacteur Contactor LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D25 LC1-D25 LC1-D25 LC1-D25 Mw 3 3 3 3 3 3 3 3 3 3 3 3 177 Installation de l’appareillage Switchgear Installation 3.3.1.29. Compact NS80H-MA Type de coordination: 1 - - - - - - - - - - - - - - - -DOL monophasé (Démarrage direct) Coordination type: 1 - - - - - - - - - - - - - - - - - - -Single phase - DOL (Direct On Line) Démarrage: Normal Performance de coupure: égale au pouvoir de coupure du disjoncteur Compact NS80H-MA 220/230 V TeSys TeSys Puissance Moteur Power motor P (kW) I (A) 0,12 1,0 0,25 2,0 0,37 3,0 0,55 4,0 0,75 5,0 1,1 7,4 1,5 9,3 1,8 11,7 2,2 16,0 3 18,3 4 23,5 3.3.1.30. Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA Type de coordination: 1DOL monophasé (Démarrage direct) Coordination type: 1Single phase - DOL (Direct On Line) TeSys Cal (A) Rat (A) 2,5 2,5 6,3 6,3 6,3 12,5 12,5 25 25 25 50 Start-up: Normal Breaking characteristics: equal to the circuit breaker’s breaking capacity TeSys Contacteurs Contactor Type Type LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D18 LC1-D25 LC1-D32 LC1-D32 Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LRD-06 1...1,7 LRD-07 1,6...2,5 LRD-08 2,5...4 LRD-10 4...6 LRD-10 4...6 LRD-12 5,5...8 LRD-14 7...10 LRD-16 9...13 LRD-21 12...18 LRD-22 17...24 LRD-22 17...24 TeSys Nb modules Nbr of modules Mw 3 3 3 3 3 3 3 3 3 3 3 Compact NS80H-MA Type de coordination: 2 - - - - - - - - - - - - - - - -DOL monophasé (Démarrage direct) Coordination type: 2 - - - - - - - - - - - - - - - - - - -Single phase - DOL (Direct On Line) Démarrage: Normal Start-up: Normal 220/230 V TeSys Compact NS80H-MA TeSys Performance de coupure: Icu = 100 kA Breaking characteristics: Icu = 100 kA Puissance Moteur Disjoncteurs Power motor Circuit Breaker P (kW) I (A) Type Type 0,12 1,0 NS80H-MA 0,25 2,0 NS80H-MA 0,37 3,0 NS80H-MA 0,55 4,0 NS80H-MA 0,75 5,0 NS80H-MA 1,1 7,4 NS80H-MA 1,5 9,3 NS80H-MA 1,8 11,7 NS80H-MA 2,2 16,0 NS80H-MA Guide Technique V9 / V9 Technical Guide Type de coordination: 2DOL monophasé (Démarrage direct) Coordination type: 2Single phase - DOL (Direct On Line) TeSys Cal (A) Rat (A) 2,5 2,5 6,3 6,3 6,3 12,5 12,5 25 25 Contacteurs Contactor Type Type LC1-D09 LC1-D09 LC1-D18 LC1-D25 LC1-D25 LC1-D32 LC1-D32 LC1-D32 LC1-D32 TeSys Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LRD-06 1...1,7 LRD-07 1,6...2,5 LRD-08 2,5...4 LRD-10 4...6 LRD-10 4...6 LRD-14 7...10 LRD-14 7...10 LRD-16 9...13 LRD-21 12...18 TeSys Nb modules Nbr of modules Mw 3 3 3 3 3 3 3 3 3 178 Installation de l’appareillage Switchgear Installation 3.3.2. 3.3.2.1. Déclassement des appareils - AC3 Starters derating - AC3 GV2-P Type de coordination: 1-2 Coordination type: 1-2 Blokset Mf TeSys TeSys TeSys Appareillage Puissance Power Switchgear Disjoncteur Circuit breaker GV2-P02 GV2-P03 GV2-P04 GV2-P05 GV2-P06 GV2-P07 GV2-P08 GV2-P10 GV2-P14 GV2-P16 GV2-P20 GV2-P21 GV2-P22 Calibre Rating 0,16...0,25 0,25...0,4 0,4...0,63 0,63...1 1...1,6 1,6...2,5 2,5...4 4...6,3 6...10 9...14 13...18 17...23 20...25 Contacteur Contactor LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K09 LC1-D12 LC1-D18 LC1-D25 LC1-D25 TeSys TeSys Coefficient de Déclassement (A) à T°amb (°C) Derating coefficient (A) à T°amb (°C) IP ≤ 42 IP 54 35 40 45 50 35 40 45 50 0,23 0,2 0,2 0,2 0,2 0,2 0,2 0,15 0,35 0,33 0,3 0,3 0,3 0,3 0,3 0,25 0,6 0,5 0,5 0,5 0,5 0,5 0,5 0,4 0,9 0,8 0,8 0,7 0,8 0,75 0,7 0,7 1,4 1,3 1,2 1,2 1,3 1,2 1,1 1 2,2 2,1 2 1,9 2 1,9 1,8 1,7 3,6 3,4 3,1 3 3,2 3 2,9 2,7 5,4 5 4,7 4,5 5 4,5 4,3 4 8 7,6 7 6,7 7,2 6,8 6,5 6 10,7 10 9,4 8,9 9,6 9 8,6 8 16 15 14 13,3 14,5 13,5 13 12 20 19 18 17 18,5 17 16,6 15,4 22 21 19,5 18,5 20 18,8 18 16,8 Blokset Mw TeSys Disjoncteur Circuit breaker GV2-P02 GV2-P03 GV2-P04 GV2-P05 GV2-P06 GV2-P07 GV2-P08 GV2-P10 GV2-P14 GV2-P16 GV2-P20 GV2-P21 GV2-P22 TeSys Calibre Rating 0,16...0,25 0,25...0,4 0,4...0,63 0,63...1 1...1,6 1,6...2,5 2,5...4 4...6,3 6...10 9...14 13...18 17...23 20...25 TeSys Contacteur Contactor LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K09 LC1-D12 LC1-D18 LC1-D25 LC1-D25 TeSys IP ≤ 42 35 40 45 0,23 0,2 0,35 0,34 0,6 0,5 TeSys 50 IP 54 35 40 45 50 0,2 0,2 0,2 0,2 0,2 0,2 0,3 0,3 0,3 0,3 0,3 0,3 0,5 0,5 0,5 0,5 0,5 0,4 0,9 0,8 0,8 0,7 0,8 0,8 0,7 0,7 1,4 1,3 1,2 1,2 1,3 1,2 1,1 1 2,2 2,1 2 1,9 2 1,9 1,8 1,7 3,6 3,4 3,1 3 3,2 3 2,9 2,7 5,4 5 4,7 4,5 5 4,5 4,3 4 8 7,5 7 6,7 7,2 6,8 6,5 6 10,7 10 9,4 8,9 9,6 9 8,6 8 16 15 14 13,3 14,5 13,5 13 12 20 19 18 17 18,5 17 15,6 15,4 22 21 20 19 20 19 18 17 Coefficient à appliquer Coefficient to be applied 35° 40° 45° 50° IP ≤ 42 0.89 0.84 0.78 0.74 IP 54 0.80 0.75 0.72 0.67 Guide Technique V9 / V9 Technical Guide 179 Installation de l’appareillage Switchgear Installation 3.3.2.2. Compact NS et GV7 Compact NS and GV7 Type de coordination: 1-2 Coordination type: 1-2 Blokset Mf TeSys Disjoncteur Circuit breaker NS80H-MA NS100l-MA* NS160l-MA* NS250l-MA* NS400l-MA* NS630l-MA* TeSys TeSys TeSys Calibre Rating 2,5 6,3 13 13 25 25 50 50 50 80 80 2,5 6,3 13 13 25 25 50 50 50 50 100 100 100 100 150 Disjoncteur moteur Motor circuit-breaker GV7-Rn GV7-Rn GV7-Rn GV7-Rn GV7-Rn GV7-Rn GV7-Rn GV7-Rn GV7-Rn GV7-Rn GV7-Rn GV7-Rn GV7-Rn GV7-Rn GV7-Rn GV7-Rn Contacteur Contactor LC1-D09 LC1-D09 LC1-D09 LC1-D12 LC1-D18 LC1-D25 LC1-D32 LC1-D40 LC1-D50 LC1-D65 LC1-D80 LC1-D09 LC1-D09 LC1-D09 LC1-D12 LC1-D18 LC1-D25 LC1-D32 LC1-D40 LC1-D50 LC1-D65 LC1-D65 LC1-D80 LC1-D95 LC1-F115 LC1-F150 220 GV7-Rn 220 GV7-Rn TeSys IP ≤ 42 35 40 45 50 IP 54 35 40 45 50 8 7.7 7.3 7 6.3 5.9 5.5 5.4 8 7.7 7.3 7 6.3 5.9 5.5 5.4 8 7.7 7.3 7 6.3 5.9 5.5 5.4 10.7 10.2 9.7 9.2 8.3 7.8 7.5 7 16 15.3 14.6 13.9 12.5 11.7 11.2 10.8 22.3 21.2 20.2 19.2 17.3 16.3 15.5 15 28.5 27.2 26 24.6 22 20.8 19.9 19.2 35.6 34 32.4 30.8 28 26 25 24 44.5 42.5 40.5 38.5 35 33 32 30 58 55 53 50 45 42 40 39 71 68 65 62 55 52 50 48 8 7.7 7.3 7 6.3 5.9 5.5 5.4 8 7.7 7.3 7 6.3 5.9 5.5 5.4 8 7.7 7.3 7 6.3 5.9 5.5 5.4 7 10.7 10.2 9.7 9.2 8.3 7.8 7.5 16 15.3 14.6 13.9 12.5 11.7 11.2 10.8 22.3 21.2 20.2 19.2 17.3 16.3 15.5 15 28.5 27.2 26 24.6 22 20.8 19.9 19.2 35.6 34 32.4 30.8 28 26 25 24 44.5 42.5 40.5 38.5 35 33 32 30 58 55 53 50 45 42 40 39 58 55 53 50 45 42 40 39 71 68 65 62 55 52 50 48 84.5 81 77 73 65 62 60 57 102 98 93 89 78 75 73 69 134 128 122 116 102 98 95 90 LC1-F185 165 157 150 142 126 120 117 111 LC1-F225 203 190 185 175 154 147 141 135 320 GV7-Rn LC1-F265 236 225 215 204 180 172 167 159 320 - LC1-F330 294 280 267 254 225 215 208 198 500 - LC1-F400 356 340 324 308 272 260 252 240 500 - LC1-F500 445 425 405 385 340 325 315 300 500 - LC1-F630 560 535 510 485 428 409 397 381 *: NS ***z-MA représente: - NS*** N/H/L-MA pour NS100-250 - NS*** H/L-MA pour NS400-630 : représente E40...220 ou S40...220 Guide Technique V9 / V9 Technical Guide *: NS ***z-MA represent: - NS*** N/H/L-MA by NS100-250 - NS*** H/L-MA by NS400-630 : represent E40...220 or S40...220 180 Installation de l’appareillage Switchgear Installation Blokset Mw IP 20 TeSys TeSys Appareillage Puissance Power Switchgear Disjoncteur Calibre Circuit breaker Rating NS80H-MA 2,5 6,3 13 13 25 TeSys Disjoncteur moteur Motor circuit-breaker - TeSys GV7-R Contacteur Contactor LC1-D09 LC1-D09 LC1-D09 LC1-D12 LC1-D18 25 - 50 GV7-R 50 TeSys Coefficient de Déclassement (A) à T°amb (°C) Derating coefficient (A) à T°amb (°C) 35 40 45 50 8,1 7,9 7,6 8,1 7,9 7,6 7,2 7,2 8,1 7,9 7,6 7,2 10 10,5 1O 9,6 17 16 15 15 LC1-D25 22,5 22 21 20 LC1-D32 30 28 27 26 GV7-R LC1-D40 38 35 33 32 50 GV7-R LC1-D50 45 44 42 40 80 GV7-R LC1-D65 61 58 55 52 80 GV7-R LC1-D80 64 61 59 56 2,5 - LC1-D09 8,1 7,9 7,6 7,2 6,3 - LC1-D09 8,1 7,9 7,6 7,2 13 - LC1-D09 8,1 7,9 7,6 7,2 13 - LC1-D12 10 10,5 1O 9,6 25 GV7-R LC1-D18 17 16 15 15 25 - LC1-D25 22,5 22 21 20 50 GV7-R LC1-D32 30 28 27 26 50 GV7-R LC1-D40 38 35 33 32 50 GV7-R LC1-D50 45 44 42 40 50 GV7-R LC1-D65 61 58 55 52 100 GV7-R LC1-D65 61 58 55 52 100 GV7-R LC1-D80 64 61 59 56 100 GV7-R LC1-D95 76 72 70 67 NS160z-MA* 100 GV7-R LC1-F115 92 88 84 81 150 GV7-R LC1-F150 120 115 110 105 NS250z-MA* 220 GV7-R LC1-F185 148 142 136 130 220 GV7-R LC1-F225 175 168 161 155 NS400z-MA* 320 GV7-R LC1-F265 249 235 222 211 320 - LC1-F330 255 245 234 225 NS630z-MA* 500 - LC1-F400 320 306 293 282 500 - LC1-F500 400 382 366 352 500 - LC1-F630 500 480 460 440 NS100z-MA* *: NS ***z-MA représente: - NS*** N/H/L-MA pour NS100-250 - NS*** H/L-MA pour NS400-630 : représente E40...220 ou S40...220 Guide Technique V9 / V9 Technical Guide *: NS ***z-MA represent: - NS*** N/H/L-MA by NS100-250 - NS*** H/L-MA by NS400-630 : represent E40...220 or S40...220 181 Installation de l’appareillage Switchgear Installation Blokset Mw IP 31/42 TeSys TeSys Appareillage Puissance Power Switchgear Disjoncteur Calibre Circuit breaker Rating NS80H-MA 2,5 6,3 13 13 25 TeSys TeSys Coefficient de Déclassement (A) à T°amb (°C) Derating coefficient (A) à T°amb (°C) 35 40 45 50 GV7-R Contacteur Contactor LC1-D09 LC1-D09 LC1-D09 LC1-D12 LC1-D18 25 - LC1-D25 22 21 20 18,5 50 GV7-R LC1-D32 28 27 25 24 50 GV7-R LC1-D40 34 32 31 29 50 GV7-R LC1-D50 35 33 31 30 80 GV7-R LC1-D65 57 54 51 48 80 GV7-R LC1-D80 64 61 59 56 2,5 - LC1-D09 8 7,6 7 6,6 6,3 - LC1-D09 8 7,6 7 6,6 13 - LC1-D09 8 7,6 7 6,6 13 - LC1-D12 10,5 10 9,4 8,8 25 GV7-R LC1-D18 17 16 15 14 25 - LC1-D25 22 21 20 18,5 50 GV7-R LC1-D32 28 27 25 24 50 GV7-R LC1-D40 34 32 31 29 50 GV7-R LC1-D50 35 33 31 30 50 GV7-R LC1-D65 57 54 51 48 100 GV7-R LC1-D65 57 54 51 48 100 GV7-R LC1-D80 64 61 59 56 100 GV7-R LC1-D95 76 72 70 67 NS160z-MA* 100 GV7-R LC1-F115 92 87 85 80 150 GV7-R LC1-F150 112 110 102 98 NS250z-MA* 220 GV7-R LC1-F185 137 135 126 120 220 GV7-R LC1-F225 164 161 150 144 NS400z-MA* 320 GV7-R LC1-F265 231 218 207 197 320 - LC1-F330 238 234 218 210 NS630z-MA* 500 - LC1-F400 296 292 272 260 500 - LC1-F500 372 366 341 328 500 - LC1-F630 468 460 430 413 NS100z-MA* Disjoncteur moteur Motor circuit-breaker - TeSys *: 8 7,6 7 8 7,6 7 6,6 8 7,6 7 6,6 10,5 10 9,4 8,8 17 16 15 14 NS ***z-MA représente: - NS*** N/H/L-MA pour NS100-250 - NS*** H/L-MA pour NS400-630 : représente E40...220 ou S40...220 Guide Technique V9 / V9 Technical Guide 6,6 *: NS ***z-MA represent: - NS*** N/H/L-MA by NS100-250 - NS*** H/L-MA by NS400-630 : represent E40...220 or S40...220 182 Installation de l’appareillage Switchgear Installation Blokset Mw IP 54 TeSys TeSys Appareillage Puissance Power Switchgear Disjoncteur Calibre Circuit breaker Rating NS80H-MA 2,5 6,3 13 13 25 NS100z-MA* TeSys Disjoncteur moteur Motor circuit-breaker - TeSys TeSys Coefficient de Déclassement (A) à T°amb (°C) Derating coefficient (A) à T°amb (°C) 35 40 45 50 GV7-R Contacteur Contactor LC1-D09 LC1-D09 LC1-D09 LC1-D12 LC1-D18 25 - LC1-D25 20 18,7 18 17,2 50 GV7-R LC1-D32 26 24 23 22 50 GV7-R LC1-D40 32 30 29 27,5 50 GV7-R LC1-D50 40 37,5 36 34,5 80 GV7-R LC1-D65 52 49,5 47 44,5 80 GV7-R LC1-D80 55 52 50 48 2,5 - LC1-D09 7,2 6,8 6,5 6,2 6,3 - LC1-D09 7,2 6,8 6,5 6,2 13 - LC1-D09 7,2 6,8 6,5 6,2 13 - LC1-D12 9,6 9 8,6 7,2 25 GV7-R LC1-D18 14,5 13,6 13 12,3 25 - LC1-D25 20 18,7 18 17,2 50 GV7-R LC1-D32 26 24 23 22 50 GV7-R LC1-D40 32 30 29 27,5 50 GV7-R LC1-D50 40 37,5 36 34,5 50 GV7-R LC1-D65 52 49,5 47 44,5 100 GV7-R LC1-D65 52 49,5 47 44,5 100 GV7-R LC1-D80 55 52 50 48 7,2 6,8 6,5 7,2 6,8 6,5 6,2 6,2 7,2 6,8 6,5 6,2 9,6 9 8,6 7,2 14,5 13,6 13 12,3 100 GV7-R LC1-D95 66 62 60 57 NS160z-MA* 100 GV7-R LC1-F115 79 75 72 69 150 GV7-R LC1-F150 103 98 94 90,5 NS250z-MA* 220 GV7-R LC1-F185 127 120 115 111 220 GV7-R LC1-F225 151 144 138 133 NS400z-MA* 320 GV7-R LC1-F265 213 201 191 182 320 - LC1-F330 221 211 201 198 NS630z-MA* 500 - LC1-F400 276 260 250 240 500 - LC1-F500 343 328 314 302 500 - LC1-F630 432 413 395 380 *: NS ***z-MA représente: - NS*** N/H/L-MA pour NS100-250 - NS*** H/L-MA pour NS400-630 : représente E40...220 ou S40...220 Guide Technique V9 / V9 Technical Guide *: NS ***z-MA represent: - NS*** N/H/L-MA by NS100-250 - NS*** H/L-MA by NS400-630 : represent E40...220 or S40...220 183 Installation de l’appareillage Switchgear Installation 3.3.2.3. Integral Contacteurs - Disjoncteurs Integral - - - - - - -Coordination totale Contactors - Integral Circuit breakers - - - - - -Total coordination Coefficient à appliquer Coefficient to be applied 35° 0.89 0.80 IP ≤ 42 IP 54 3.3.3. 3.3.3.1. 40° 45° 50° 0.84 0.78 0.74 0.75 0.72 0.67 Départ distribution en tiroir Feeder in drawer Nombre de modules nécessaires Number of modules required Blokset Mw Disjoncteur Circuit Breaker NS 100 NS 100 NS 160 NS 250 NS 250 Guide Technique V9 / V9 Technical Guide Nombre pôles Number of Poles 3 4 3/4 3 4 Nb modules Nbr of modules 3 6 6 6 9 Forme Form 3b/4b 3b/4b 3b/4b 3b/4b 3b/4b 184 Installation de l’appareillage Switchgear Installation 3.3.4. Colonne arrivée Blokset Mw avec Masterpact NT Blokset Mw incoming column with Masterpact NT 4M 4M 14 M 2200 2200 18 M 14 M 18 M 4M 4M 900 Guide Technique V9 / V9 Technical Guide 900 185 Sommaire du chapitre Chapter contents 3.4. Raccordement des appareils Connecting the circuit breakers 3.4.1. Blokset D ................................................................................................. 3.4.1.1. Barres souples ........................................................................... Flexible bars 3.4.1.2. Barres Rigides ............................................................................ Rigid bars 3.4.1.3. Câbles (souple multi brins 105º C) ........................................... Cables (type NYAF 105º C) 187 187 188 189 3.4.2. Blokset Mf ................................................................................................ 190 3.4.2.1. Barres rigides ............................................................................. 190 Rigid bars 3.4.2.2. Câbles (souple multi brins 105° C) ........................................... 190 cables (type NYAF 105° C) 3.4.3. Blokset Mw .............................................................................................. 190 3.4.3.1. Barres rigides ............................................................................. 190 Rigid bars 3.4.3.2. Câbles (souple multi brins 105° C) ........................................... 190 cables (type NYAF 105° C) Guide Technique V9 / V9 Technical Guide 186 Installation de l’appareillage Switchgear Installation 3.4. Raccordement des appareils Connecting the circuit breakers 3.4.1. 3.4.1.1. Blokset D Barres souples Flexible bars Raccordement par barres souples (liaisons préfabriquées et polypact): utilisation du matériel Prisma uniquement. Les disjoncteurs Compact NS peuvent être raccordés aux Jeux de barres par des liaisons préfabriquées (livrées avec un écran support qui bride les conducteurs), pour les appareils en position horizontale, ou par Polypact (livré avec un écran support et liaisons préfabriquées), pour les appareils en position verticale. La liaison appareil horizontal s’installe uniquement sur des appareils PAV quel que soit le type de commande (sauf électrique pour Compact NS 400/630) avec un Jeu de barres LINERGY. Appareils Circuit breakers NS 100 à 250 NS 100 to 250 NS 100 à 250 NS 100 to 250 NS 100 et 160 NS 100 and 160 NS 100 et 160 NS 100 and 160 NS 400 à 630 NS 400 to 630 NS 400 à 630 NS 400 to 630 Quantité/rangée Quantity/row 1 tri 1 three pole 1 tétra 1 four pole 4 tri 4 three pole 3 tétra 3 four pole 1 tri 1 three pole 1 tétra 1 four pole Position Position H Références References 07230 V Fixation Fixing F ou D F or D F ou D F or D F V F 07014* H F 07234 H F 07235** H D: Débrochable F: Fixe H: Horizontal V: Vertical *: sauf commande électrique **: appareil triphasé pour raccordement par barres ou utilisation d’épanouisseurs. Guide Technique V9 / V9 Technical Guide Connection via flexible bars (factory built and polypact): only use Prisma equipment. Compact NS circuit breakers can be linked to the busbars using factory-built links (supplied with support screen which flanges the conductors) for circuit breakers in the horizontal position, or using Polypact (supplied with a support screen and factory-built links) for circuit breakers in the vertical position. The horizontal circuit breaker link is only installed on FC circuit breakers, whatever the type of operating mechanism. (except motor mechanisms for Compact NS 400/630) with Linergy busbars. 07231 07013* D: Withdrawable F: Fixed H: Horizontal V: Vertical *:: except motor mechanism. **::three-phase circuit breaker for connections by bar or spreaders 187 Installation de l’appareillage Switchgear Installation 3.4.1.2. Barres Rigides Rigid bars Dans les autres cas: raccordement sur un Jeu de barres traditionnel (barres plates), pour les appareils fixes ou débrochables en PAV ou PAR. In the other cases: connection to a conventional busbar (flat bars) for FC and RC fixed or withdrawable circuit breakers. Raccordement appareillage Switchgear connection Calibre Rating NB50 EZD100B/F/N/H < 60A Dérivations Connections Câble souple 105°C 1000SV 16 mm2 Flexible cable 105°C Queues de barres (coté client) Bar tails (customer side) Plages appareil Circuit breaker terminal pads 1000SV 16 mm2 NS100 / NB100 EZD100F/N/H ≥ 60A up to 100A Câble souple 105°C 1000SV 25 mm2 Flexible cable (105° C) Plages appareil Circuit breaker terminal pads 1000SV 25 mm2 NS160 Câble souple 105°C 1000SV 50 mm2 Flexible cable (105° C) Plages appareil Circuit breaker terminal pads 1000SV 50 mm2 NS250 / NB225 Câble souple 105°C 1000SV 95 mm2 Flexible cable (105° C) Plages appareil Circuit breaker terminal pads 1000SV 95 mm2 NS400 / NB400 (1b x 32 x 5mm *) ou 2b x 30 x 5mm (1b x 32 x 5mm *) or 2b x 30 x 5mm Plages appareil Circuit breaker terminal pads NS630 / NB600 (2b x 32 x 5mm *) ou 2b x 30 x 5mm (2b x 32 x 5mm *) or 2b x 30 x 5mm Plages appareil Circuit breaker terminal pads C801 à 1251 / CM / Masterpact: voir plans de barres *: il faut développer les barres Guide Technique V9 / V9 Technical Guide C801 to 1251 / CM / Masterpact: see bar drawings. *: necessary to develop bars 188 Installation de l’appareillage Switchgear Installation 3.4.1.3. Câbles (souple multi brins 105º C) Cables (type NYAF 105º C) Dans les autres cas: raccordement sur un Jeu de barres traditionnel (barres plates), pour les appareils fixes ou débrochables en PAV ou PAR. In the other cases: connection to a conventional busbar (flat bars) for FC and RC fixed or withdrawable circuit breakers. Raccordement appareillage Switchgear connection Calibre Rating NB50 EZD100B/F/N/H < 60A Dérivations Connections Câble souple 105°C 1000SV 16 mm2 Flexible cable 105°C Queues de barres (coté client) Bar tails (customer side) Plages appareil Circuit breaker terminal pads 1000SV 16 mm2 NS100 / NB100 EZD100F/N/H ≥ 60A up to 100A Câble souple 105°C 1000SV 25 mm2 Flexible cable (105° C) Plages appareil Circuit breaker terminal pads 1000SV 25 mm2 NS160 Câble souple 105°C 1000SV 50 mm2 Flexible cable (105° C) Plages appareil Circuit breaker terminal pads 1000SV 50 mm2 NS250 / NB225 Câble souple 105°C 1000SV 95 mm2 Flexible cable (105° C) Plages appareil Circuit breaker terminal pads 1000SV 95 mm2 C801 à 1251 / CM / Masterpact: voir plans de barres *: il faut développer les barres Guide Technique V9 / V9 Technical Guide C801 to 1251 / CM / Masterpact: see bar drawings. *: necessary to develop bars 189 Installation de l’appareillage Switchgear Installation 3.4.2. Blokset Mf 3.4.2.1. Barres rigides Rigid bars 3.4.2.2. Câbles (souple multi brins 105° C) cables (type NYAF 105° C) Ampères Amperes ≤ 32 A Section Section ≤ 40 A 10 mm2 ≤ 60 A 16 mm2 ≤ 80 A 25 mm2 ≤ 110 A 35 mm2 ≤ 150 A 50 mm2 ≤ 220 A 2 x 35 mm2 ≤ 300 A 2 x 50 mm2 ≤ 400 A 2 x 95 mm2 ≤ 500 A 2 x 120 mm2 3.4.3. 6 mm2 Blokset Mw 3.4.3.1. Barres rigides Rigid bars 3.4.3.2. Câbles (souple multi brins 105° C) cables (type NYAF 105° C) Ampères Amperes ≤ 32 A Section Section 6 mm2 1 pince 6/10 mm2 ≤ 40 A 10 mm ≤ 60 A 16 mm2 1 pince 16/25 mm2 ≤ 80 A 25 mm 2 1 pince 16/25 mm2 ≤ 110 A 35 mm2 1 pince 35 mm2 ≤ 150 A 50 mm 2 1 pince 50 mm2 ≤ 220 A 2 x 35 mm2 2 pinces 35 mm2 ≤ 300 A 2 x 50 mm 2 2 pinces 50 mm2 ≤ 500 A 3 x 50 mm2 3 pinces 50 mm2 Guide Technique V9 / V9 Technical Guide 2 1 pince 6/10 mm2 190 Sommaire du chapitre Chapter contents 3.5. Blokset Ms 3.5.1. Démarreurs et Variateurs ....................................................................... 192 Trifasic soft starters and variable speed drivers 3.5.1.1. ATV18 .......................................................................................... 192 Couple: constant Torque: constant 3.5.1.2. ATV18 .......................................................................................... 194 Couple: variable Torque: variable 3.5.1.3. ATV18 .......................................................................................... 196 Couple: Variable faible bruit Torque: Low noise 3.5.1.4. ATV58 .......................................................................................... 198 3.5.1.5. ATV66 .......................................................................................... 201 Couple: constant Torque: constant 3.5.1.6. ATV66 .......................................................................................... 205 Couple: variable Torque: variable 3.5.1.7. ATV66 .......................................................................................... 209 Couple: Variable faible bruit Torque: Low noise 3.5.1.8. ATS46 .......................................................................................... 213 Coordination Type 1 Coordination Type 1 3.5.1.9. ATS46 .......................................................................................... 218 Coordination Type 2 Coordination Type 2 3.5.1.10. Service: Sévère Service: Severe ATS46 .......................................................................................... 228 Coordination Type 2 Coordination Type 2 3.5.2. Service: Standard Service: Standard ATS46 .......................................................................................... 223 Coordination Type 1 Coordination Type 1 3.5.1.11. Service: Standard Service: Standard Service: Sévère Service: Severe IP pour démarreurs et variateurs de vitesse ........................................ 233 IP for soft starters and variable speed drivers Guide Technique V9 / V9 Technical Guide 191 Installation de l’appareillage Switchgear Installation Blokset Ms 3.5. Blokset Ms 3.5.1. Démarreurs et Variateurs Trifasic soft starters and variable speed drivers 3.5.1.1. ATV18 220/240 V Puissance (kW) Power (kW) 3 Icc coord. (kA) Icc coord. (kA) 50 4 Couple: constant Torque: constant ATV18 Disjoncteur Couple: constant Torque: constant Contacteur (1) Contactor (1) LC1-D2510 ATV GV2-L20 Calibre (A) Rating (A) 18A 50 GV2-L22 25A 5.5 50 NS80H-MA 5.5 50 7.5 50 7.5 50 GK3-EF65 Température ambiant 40 °C Ambient temperature 40 °C Résistance de freinage Breaking resistance VW3-A16703 Raccordement sect. cable cross section area ATV -18U54M2 Inductance de ligne Line coil area VW3-A66503 LC1-D2510 ATV -18U72M2 VW3-A66504 VW3-A66701 50A LC1-D3210 ATV -18U90M2 VW3-A66504 VW3-A66702 GK3-EF40 40A LC1-D3210 ATV -18U90M2 VW3-A66504 VW3-A66702 NS80H-MA 50A LC1-D5011 ATV -18D12M2 VW3-A66504 VW3-A66702 65A LC1-D5011 ATV -18D12M2 VW3-A66504 VW3-A66702 Circuit Breaker ATV (1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter le nombre de modules. (2): Les ventilateurs ont été définis pour chaque unité fonctionnel sans la résistance de freinage. Pour installer la résistance de freinage, consulter GIB. Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653. Guide Technique V9 / V9 Technical Guide 2,5 mm2 Numéro de mod. avec ou sans resit.frenage. Number of mod. with or without break. resist. 9 Ventilateur (2) Fan (2) 4606 N 2,5 mm2 9 4606 N 4 mm 2 9 4606 N 4 mm 2 9 4606 N 6 mm 2 9 4606 N 6 mm 2 9 4606 N (1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the number of modules. (2): The fans were defined for functional units without breaking resistance. If breaking resistance is needed consult BIM. Single line diagrams, according Telemecanique catalogue ART. 16653. 192 Installation de l’appareillage Switchgear Installation Blokset Ms 380/460 V Puissance (kW) Power (kW) 0.75 Icc coord. (kA) Icc coord. (kA) 50 1.5 ATV18 Disjoncteur Couple: constant Torque: constant Contacteur (1) Contactor (1) LC1-K0610 ATV GV2-L08 Calibre (A) Rating (A) 4A 15 GV2-L10 6,3A 2.2 15 GV2-L14 3 15 4 15 5.5 7.5 Température ambiant 40 °C Ambient temperature 40 °C Résistance de freinage Breaking resistance VW3-A16702 Raccordement sect. cable cross section area ATV -18U18N4 Inductance de ligne Line coil area VW3-A66501 2,5 mm2 Numéro de mod. avec ou sans resit.frenage. Number of mod. with or without break. resist. 9 Ventilateur (2) Fan (2) 4606 N LC1-K0610 ATV -18U29N4 VW3-A66501 VW3-A16702 2,5 mm2 10A LC1-K0910 ATV -18U41N4 9 4606 N VW3-A66502 VW3-A16702 2,5 mm 2 9 4606 N ATV -18U54N4 VW3-A66503 VW3-A16704 2,5 mm 2 GV2-L16 14A LC1-D1210 GV2-L16 14A LC1-D1810 9 4606 N ATV -18U72N4 VW3-A66502 VW3-A16704 2,5 mm 2 9 4606 N LC1-D2510 ATV -18U90N4 VW3-A66503 VW3-A66701 2,5 mm 2 15 GV2-L20 18A 15 GV2-L22 25A LC1-D3210 ATV -18D12N4 VW3-A66503 VW3-A66701 11 25 NS80H-MA 11 25 GK3-EF40 50A LC1-D4011 ATV -18D16N4 VW3-A66504 VW3-A66702 40A LC1-D4011 ATV -18D16N4 VW3-A66504 VW3-A66702 15 25 15 25 NS80H-MA 50A LC1-D5011 ATV -18D23N4 VW3-A66504 GK3-EF65 65A LC1-D5011 ATV -18D23N4 VW3-A66504 Circuit Breaker ATV (1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter le nombre de modules. (2): Les ventilateurs ont été définis pour chaque unité fonctionnel sans la résistance de freinage. Pour installer la résistance de freinage, consulter GIB. Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653. Guide Technique V9 / V9 Technical Guide 9 4606 N 4 mm 2 9 4606 N 4 mm 2 12 4606 N 4 mm 2 12 4606 N VW3-A66702 4 mm2 12 4606 N VW3-A66702 2 12 4606 N 4 mm (1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the number of modules. (2): The fans were defined for functional units without breaking resistance. If breaking resistance is needed consult BIM. Single line diagrams, according Telemecanique catalogue ART. 16653. 193 Installation de l’appareillage Switchgear Installation Blokset Ms 3.5.1.2. ATV18 220/240 V Puissance (kW) Power (kW) 3 Icc coord. (kA) Icc coord. (kA) 50 4 Couple: variable Torque: variable ATV18 Disjoncteur Couple: variable Torque: variable GV2-L20 Calibre (A) Rating (A) 18A Contacteur (1) Contactor (1) LC1-D2510 Résistance de freinage Breaking resistance VW3-A16703 Raccordement sect. cable cross section area ATV -18U54M2 Inductance de ligne Line coil area VW3-A66503 50 GV2-L22 25A LC1-D2510 ATV -18U72M2 VW3-A66504 VW3-A66701 5.5 50 NS80H-MA 50A LC1-D3210 ATV -18U90M2 VW3-A66504 VW3-A66702 5.5 50 7.5 50 GK3-EF40 40A LC1-D3210 ATV -18U90M2 VW3-A66504 VW3-A66702 NS80H-MA 50A LC1-D5011 ATV -18D12M2 VW3-A66504 VW3-A66702 7.5 50 GK3-EF65 65A LC1-D5011 ATV -18D12M2 VW3-A66504 VW3-A66702 Circuit Breaker ATV Température ambiant 40 °C Ambient temperature 40 °C ATV (1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter le nombre de modules. (2): Les ventilateurs ont été définis pour chaque unité fonctionnel sans la résistance de freinage. Pour installer la résistance de freinage, consulter GIB. Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653. Guide Technique V9 / V9 Technical Guide 2,5 mm2 Numéro de mod. avec ou sans resit. freinage. Number of mod. with or without break. resist. 9 Ventilateur (2) Fan (2) 4606 N 2,5 mm2 9 4606 N 4 mm 2 9 4606 N 4 mm 2 9 4606 N 6 mm 2 9 4606 N 6 mm 2 9 4606 N (1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the number of modules. (2): The fans were defined for functional units without breaking resistance. If breaking resistance is needed consult BIM. Single line diagrams, according Telemecanique catalogue ART. 16653. 194 Installation de l’appareillage Switchgear Installation Blokset Ms 380/460 V Puissance (kW) Power (kW) 0.75 Icc coord. (kA) Icc coord. (kA) 50 1.5 ATV18 Disjoncteur Couple: variable Torque: variable Contacteur (1) Contactor (1) LC1-K0610 ATV GV2-L08 Calibre (A) Rating (A) 4A 15 GV2-L10 6,3A 2.2 15 GV2-L14 3 15 4 15 5.5 7.5 Température ambiant 40 °C Ambient temperature 40 °C Résistance de freinage Breaking resistance VW3-A16702 Raccordement sect. cable cross section area ATV -18U18N4 Inductance de ligne Line coil area VW3-A66501 LC1-K0610 ATV -18U29N4 VW3-A66501 10A LC1-K0910 ATV -18U41N4 GV2-L16 14A LC1-D1210 GV2-L16 14A LC1-D1810 15 GV2-L20 18A 15 GV2-L22 25A 11 25 NS80H-MA 11 25 GK3-EF40 15 25 NS80H-MA Circuit Breaker 2,5 mm2 Numéro de mod. avec ou sans resit. freinage. Number of mod. with or without break. resist. 9 Ventilateur (2) Fan (2) 4606 N VW3-A16702 2,5 mm2 9 4606 N VW3-A66502 VW3-A16702 2,5 mm 2 9 4606 N ATV -18U54N4 VW3-A66503 VW3-A16704 2,5 mm 2 9 4606 N ATV -18U72N4 VW3-A66502 VW3-A16704 2,5 mm 2 9 4606 N LC1-D2510 ATV -18U90N4 VW3-A66503 VW3-A66701 2,5 mm 2 LC1-D3210 ATV -18D12N4 VW3-A66503 VW3-A66701 50A LC1-D4011 ATV -18D16N4 VW3-A66504 VW3-A66702 40A LC1-D4011 ATV -18D16N4 VW3-A66504 VW3-A66702 50A LC1-D5011 ATV -18D23N4 VW3-A66504 VW3-A66702 ATV (1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter le nombre de modules. (2): Les ventilateurs ont été définis pour chaque unité fonctionnel sans la résistance de freinage. Pour installer la résistance de freinage, consulter GIB. Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653. Guide Technique V9 / V9 Technical Guide 9 4606 N 4 mm 2 9 4606 N 4 mm 2 12 4606 N 4 mm 2 12 4606 N 4 mm2 12 4606 N (1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the number of modules. (2): The fans were defined for functional units without breaking resistance. If breaking resistance is needed consult BIM. Single line diagrams, according Telemecanique catalogue ART. 16653. 195 Installation de l’appareillage Switchgear Installation Blokset Ms 3.5.1.3. ATV18 220/240 V Puissance (kW) Power (kW) 3 Icc coord. (kA) Icc coord. (kA) 50 4 Couple: Variable faible bruit Torque: Low noise ATV18 Disjoncteur Couple: Variable faible bruit Torque: Low noise Contacteur (1) Contactor (1) LC1-D2510 ATV GV2-L22 Calibre (A) Rating (A) 25A 50 GV2-L22 25A 5.5 50 NS80H-MA 5.5 50 GK3-EF40 Circuit Breaker ATV -18U54M2 Inductance de ligne Line coil area VW3-A66503 Résistance de freinage Breaking resistance VW3-A16703 LC1-D2510 ATV -18U90M2 VW3-A66504 VW3-A66702 50A LC1-D3210 ATV -18D12M2 VW3-A66504 VW3-A66702 40A LC1-D3210 ATV -18D12M2 VW3-A66504 VW3-A66702 ATV (1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter le nombre de modules. (2): Les ventilateurs ont été définis pour chaque unité fonctionnel sans la résistance de freinage. Pour installer la résistance de freinage, consulter GIB. Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653. Guide Technique V9 / V9 Technical Guide Température ambiant 40 °C Ambient temperature 40 °C Raccordement sect. cable cross section area 2,5 mm2 Numéro de mod. avec ou sans resit.frenage. Number of mod. with or without break. resist. 9 Ventilateur (2) Fan (2) 4606 N 2,5 mm2 9 4606 N 2 9 4606 N 2 9 4606 N 4 mm 4 mm (1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the number of modules. (2): The fans were defined for functional units without breaking resistance. If breaking resistance is needed consult BIM. Single line diagrams, according Telemecanique catalogue ART. 16653. 196 Installation de l’appareillage Switchgear Installation Blokset Ms 380/460 V Puissance (kW) Power (kW) 0.75 Icc coord. (kA) Icc coord. (kA) 50 1.5 ATV18 Disjoncteur Couple: Variable faible bruit Torque: Low noise Contacteur (1) Contactor (1) LC1-K0610 ATV GV2-L08 Calibre (A) Rating (A) 4A 15 GV2-L10 6,3A 2.2 15 GV2-L14 3 15 4 15 5.5 11 Température ambiant 40 °C Ambient temperature 40 °C ATV -18U29N4 Inductance de ligne Line coil area VW3-A66501 Résistance de freinage Breaking resistance VW3-A16702 LC1-K0610 ATV -18U41N4 VW3-A66502 10A LC1-K0910 ATV -18U54N4 GV2-L16 14A LC1-D1210 GV2-L20 18A LC1-D1810 15 GV2-L20 18A 25 GK3-EF40 40A Circuit Breaker 2,5 mm2 Numéro de mod. avec ou sans resit.frenage. Number of mod. with or without break. resist. 9 Ventilateur (2) Fan (2) 4606 N VW3-A16702 2,5 mm2 9 4606 N VW3-A66503 VW3-A16704 2 9 4606 N ATV -18U72N4 VW3-A66502 VW3-A16704 2 9 4606 N ATV -18U90N4 VW3-A66503 VW3-A66701 2 9 4606 N LC1-D2510 ATV -18D12N4 VW3-A66503 VW3-A66701 2 9 4606 N LC1-D4011 ATV -18D23N4 VW3-A66504 VW3-A66702 12 4606 N ATV (1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter le nombre de modules. (2): Les ventilateurs ont été définis pour chaque unité fonctionnel sans la résistance de freinage. Pour installer la résistance de freinage, consulter GIB. Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653. Guide Technique V9 / V9 Technical Guide Raccordement sect. cable cross section area 2,5 mm 2,5 mm 2,5 mm 2,5 mm 2 4 mm (1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the number of modules. (2): The fans were defined for functional units without breaking resistance. If breaking resistance is needed consult BIM. Single line diagrams, according Telemecanique catalogue ART. 16653. 197 Installation de l’appareillage Switchgear Installation Blokset Ms 3.5.1.4. ATV58 220/240 V Puissance (kW) Power (kW) 1.5 Icc coord. (kA) Icc coord. (kA) 50 2.2 ATV58 Disjoncteur Température ambiant 30 °C Ambient temperature 30 °C Contacteur (1) Contactor (3) LC1-D1810 ATV Inductance de ligne Line coil GV2-L14 Calibre (A) Rating (A) 10A ATV -58HU29M2 50 GV2-L16 14A LC1-D1810 3 50 GV2-L20 25A 4 50 GV2-L22 5.5 100 NS80H-MA 7.5 100 NS80H-MA Circuit breaker ATV VW3-A66502 Résistance de freinage Break. Resistance VW3-A58702 ATV -58HU41M2 VW3-A66503 LC1-D2510 ATV -58HU54M2 VW3-A66503 25A LC1-D2510 ATV -58HU72M2 VW3-A66504 50A LC1-D4011 ATV -58HU90M2 VW3-A66504 50A LC1-D5011 ATV -58HD12M2 VW3-A66504 Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de puissance doivent être déclassés de 11% pour ATV 58. Dans le cas d’une température ambiant plus élevée, consulter GIB. (1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter le nombre de modules. (2): Les ventilateurs ont été définis pour chaque unité fonctionnel sans la résistance de freinage. Pour installer la résistance de freinage, consulter GIB. *: pour ce cas, quand utiliser la résistance de freinage le nombre de modules doit être 12. Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653. Guide Technique V9 / V9 Technical Guide Raccord. section cable cross section area 2,5 mm2 Résistance de freinage Break. Resistance VW3-A58732 Nr. de Modules avec ou sans résistance Nb. Mod. with or without break. resistance 9 Ventilateur (2) Fan (2) 4606 N VW3-A58704 2,5 mm2 VW3-A58733 9 4606 N VW3-A58704 2 VW3-A58733 9 4606 N 2 2,5 mm VW3-A58736 9* 4606 N 2 VW3-A58736 9* 4606 N 2 VW3-A58737 9* 4606 N 2,5 mm 4 mm 6 mm Note: in case of switchboard installed in an ambient with 35 °C the values of power must be derated in 11% for ATV 58. In case of higher ambient temperature, consult BIM. (1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the number of modules (2): The fans were defined for functional units without breaking resistance. If breaking resistance is needed consult BIM. *: for this case, when using breaking resistance the number of modules must be 12. Single line diagrams, according Telemecanique catalogue ART. 16653. 198 Installation de l’appareillage Switchgear Installation Blokset Ms 380/415 V Puissance (kW) Power (kW) 0.75 Icc coord. (kA) Icc coord. (kA) 50 1.5 ATV58 Disjoncteur Température ambiant 30 °C Ambient temperature 30 °C Contacteur (1) Contactor (3) LC1-D1810 ATV GV2-L08 Calibre (A) Rating (A) 4A ATV Inductance de ligne Line coil ATV -58HU18N4 VW3-A66501 Résistance de freinage Break. Resistance VW3-A58702 50 GV2-L10 6,3A LC1-D1810 ATV -58HU29N4 VW3-A66501 VW3-A58702 2,5 mm2 2.2 50 GV2-L14 VW3-A58732 9 4606 N 10A LC1-D1810 ATV -58HU41N4 VW3-A66502 VW3-A58702 2,5 mm 2 VW3-A58732 9 4606 N GV2-L16 14A LC1-D1810 ATV -58HU54N4 VW3-A66502 VW3-A58703 2,5 mm 2 3 50 4 50 VW3-A58734 9 4606 N GV2-L16 14A LC1-D1810 ATV -58HU72N4 VW3-A66502 VW3-A58703 2,5 mm 2 VW3-A58734 9 4606 N 50 GV2-L22 25A LC1-D2510 ATV -58HU90N4 VW3-A66503 2,5 mm 2 5.5 7.5 25 NS80H-MA 50A LC1-D4011 ATV -58HD12N4 VW3-A66503 11 25 NS80H-MA 50A LC1-D4011 ATV -58HD16N4 VW3-A66504 15 25 NS80H-MA 50A LC1-D5011 ATV -58HD23N4 VW3-A66504 Circuit breaker Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de puissance doivent être déclassés de 11% pour ATV 58. Dans le cas d’une température ambiant plus élevée, consulter GIB. (1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter le nombre de modules. (2): Les ventilateurs ont été définis pour chaque unité fonctionnel sans la résistance de freinage. Pour installer la résistance de freinage, consulter GIB. *: pour ce cas, quand utiliser la résistance de freinage le nombre de modules doit être 12. Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653. Guide Technique V9 / V9 Technical Guide Raccord. section cable cross section area 2,5 mm2 Résistance de freinage Break. Resistance VW3-A58732 Nr. de Modules avec ou sans résistance Nb. Mod. with or without break. resistance 9 Ventilateur (2) Fan (2) 4606 N VW3-A58735 9 4606 N 4 mm 2 VW3-A58735 9 4606 N 4 mm 2 VW3-A58736 9* 4606 N 6 mm 2 VW3-A58736 12 4606 N Note: in case of switchboard installed in an ambient with 35 °C the values of power must be derated in 11% for ATV 58. In case of higher ambient temperature, consult BIM. (1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the number of modules (2): The fans were defined for functional units without breaking resistance. If breaking resistance is needed consult BIM. *: for this case, when using breaking resistance the number of modules must be 12. Single line diagrams, according Telemecanique catalogue ART. 16653. 199 Installation de l’appareillage Switchgear Installation Blokset Ms 440/500 V Puissance (kW) Power (kW) 0.75 Icc coord. (kA) Icc coord. (kA) 50 1.5 ATV58 Disjoncteur Température ambiant 30 °C Ambient temperature 30 °C Contacteur (1) Contactor (3) LC1-D1810 ATV GV2-L08 Calibre (A) Rating (A) 4A ATV Inductance de ligne Line coil ATV -58HU18N4 VW3-A66501 Résistance de freinage Break. Resistance VW3-A58702 50 GV2-L10 6,3A LC1-D2510 ATV -58HU29N4 VW3-A66501 VW3-A58702 2,5 mm2 2.2 50 GV2-L10 VW3-A58732 9 4606 N 6,3A LC1-D2510 ATV -58HU41N4 VW3-A66502 VW3-A58702 2,5 mm 2 VW3-A58732 9 4606 N GV2-L14 10A LC1-D2510 ATV -58HU54N4 VW3-A66502 VW3-A58703 2,5 mm 2 3 10 4 10 VW3-A58734 9 4606 N GV2-L14 10A LC1-D2510 ATV -58HU72N4 VW3-A66502 VW3-A58703 2,5 mm 2 VW3-A58734 9 4606 N 10 GV2-L22 25A LC1-D4011 ATV -58HU90N4 VW3-A66503 4 mm 2 5.5 7.5 VW3-A58735 9 4606 N 25 NS80H-MA 50A LC1-D4011 ATV -58HD12N4 VW3-A66503 4 mm 2 VW3-A58735 9 4606 N 11 25 NS80H-MA 50A LC1-D4011 ATV -58HD16N4 VW3-A66504 4 mm 2 VW3-A58736 9* 4606 N 15 25 NS80H-MA 50A LC1-D4011 ATV -58HD23N4 VW3-A66504 4 mm 2 VW3-A58736 12 4606 N Circuit breaker Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de puissance doivent être déclassés de 11% pour ATV 58. Dans le cas d’une température ambiant plus élevée, consulter GIB. (1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter le nombre de modules. (2): Les ventilateurs ont été définis pour chaque unité fonctionnel sans la résistance de freinage. Pour installer la résistance de freinage, consulter GIB. *: pour ce cas, quand utiliser la résistance de freinage le nombre de modules doit être 12. Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653. Guide Technique V9 / V9 Technical Guide Raccord. section cable cross section area 2,5 mm2 Résistance de freinage Break. Resistance VW3-A58732 Nr. de Modules avec ou sans résistance Nb. Mod. with or without break. resistance 9 Ventilateur (2) Fan (2) 4606 N Note: in case of switchboard installed in an ambient with 35 °C the values of power must be derated in 11% for ATV 58. In case of higher ambient temperature, consult BIM. (1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the number of modules (2): The fans were defined for functional units without breaking resistance. If breaking resistance is needed consult BIM. *: for this case, when using breaking resistance the number of modules must be 12. Single line diagrams, according Telemecanique catalogue ART. 16653. 200 Installation de l’appareillage Switchgear Installation Blokset Ms 3.5.1.5. ATV66 220/240 V Puissance (kW) Power (kW) 0.75 Icc coord. (kA) Icc coord. (kA) 130 1.5 Couple: constant Torque: constant ATV66 Disjoncteur Couple: constant Torque: constant Contacteur (1) Contactor (1) LC1-D1810 ATV GV2-L20 Calibre (A) Rating (A) 8A 130 GV2-L20 18A 2.2 130 GV2-L20 3 100 4 100 5.5 7.5 Température ambiant 30 °C Ambient temperature 30 °C ATV Inductance de ligne Line coil Raccord. section cable cross section area 2,5 mm2 Résistance de freinage Break. Resistance VW3-A66701 Nr. de Modules avec ou sans résistance Nb. Mod. with or without break. resistance 9 Ventilateur (2) Fan (2) 4606 N ATV -66U41M2 VW3-A66503 LC1-D1810 ATV -66U41M2 VW3-A66503 2,5 mm2 18A LC1-D1810 VW3-A66701 9 4606 N ATV -66U41M2 VW3-A66503 2 VW3-A66701 9 4606 N LC1-D3210 ATV -66U72M2 VW3-A66504 2 NS80H-MA 25A NS80H-MA 25A LC1-D3210 ATV -66U72M2 VW3-A66504 100 NS80H-MA 100 NS80H-MA 50A LC1-D4011 ATV -66U90M2 VW3-A66504 50A LC1-D5011 ATV -66D12M2 VW3-A66505 11 50 11 100 GK3-EF65 65A LC1-D6511 ATV -66D16M2 VW3-A66505 NS80H-MA 80A LC1-D8011 ATV -66D16M2 VW3-A66505 15 50 GK3-EF80 80A LC1-D8011 15 100 NS80H-MA 80A LC1-D8011 ATV -66D23M2 ATV -66D23M2 18.5 85 NS100H-MA 100A LC1-D9511 18.5 85 NS100H-MA 100A LC1-D115006 22 85 NS100H-MA 100A LC1-D115006 ATV -66D33M2 22 100 NS100H-MA 100A LC1-D115006 ATV -66D33M2 30 85 NS160H-MA 150A LC1-D150006 ATV -66D46M2 30 100 NS160H-MA 150A LC1-D150006 ATV -66D46M2 Circuit breaker Guide Technique V9 / V9 Technical Guide 2,5 mm VW3A66702 12 4606 N 2 VW3A66702 12 4606 N 2 VW3A66702 12 4606 N 2 VW3-A66703 12 4606 N 2 VW3-A66704 12 * 2 x 4606 N 2 16 mm VW3-A66704 12 * 2 x 4606 N VW3-A66506 16 mm2 VW3-A66704 24 ** 3 x 4606 ES VW3-A66506 2 16 mm VW3-A66704 24 ** 3 x 4606 ES ATV -66D33M2 25 mm2 VW3-A66704 24 ** 3 x 4606 ES ATV -66D33M2 2 35 mm VW3-A66704 24 ** 3 x 4606 ES 35 mm2 VW3-A66704 24 ** 3 x 4606 ES 2 35 mm VW3-A66704 24 ** 4 x 4606 ES 35 mm2 VW3-A66704 36 *** 4 x 4606 ES 2 VW3-A66704 36 *** 4 x 4606 ES VW3-A66506 VW3-A66507 2,5 mm 4 mm 4 mm 6 mm 10 mm 35 mm 201 Installation de l’appareillage Switchgear Installation Blokset Ms Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de puissance doivent être déclassés de 11% pour ATV 66. Dans le cas d’une température ambiant plus élevée, consulter GIB. (1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter le nombre de modules. (2): Les ventilateurs ont été définis pour chaque unité fonctionnel sans la résistance de freinage. Pour installer la résistance de freinage, consulter GIB. *: plus 12 modules seulement pour résistance de freinage **: plus 12 modules seulement pour résistance de freinage ou utiliser extension arrière de 700X2200x400 ***: plus extension arrière 700X2200x400 pour inductance de ligne et résistance de freinage Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653. Guide Technique V9 / V9 Technical Guide Note: in case of switchboard installed in an ambient with 35 °C the values of power must be derated in 11% for ATV 66. In case of higher ambient temperature, consult BIM. (1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the number of modules. (2): The fans were defined for functional units without breaking resistance. If breaking resistance is needed consult BIM. *: add12 modules only for breaking resistance **: add 12 modules only for breaking resistance or add rear column 700X2200x400 ***: add rear column 700X2200x400 for line coil and breaking resistance Single line diagrams, according Telemecanique catalogue ART. 16653. 202 Installation de l’appareillage Switchgear Installation Blokset Ms 380/460 V Puissance (kW) Power (kW) 0.75 Icc coord. (kA) Icc coord. (kA) 130 1.5 ATV66 Disjoncteur Couple: constant Torque: constant Contacteur (1) Contactor (1) LC1-D0910 ATV GV2-L08 Calibre (A) Rating (A) 4A 50 GV2-L10 6,3A 2.2 50 GV2-L14 3 50 4 50 5.5 7.5 Température ambiant 30 °C Ambient temperature 30 °C ATV Inductance de ligne Line coil Raccord. section cable cross section area 2,5 mm2 Résistance de freinage Break. Resistance VW3-A16702 Nr. de Modules avec ou sans résistance Nb. Mod. with or without break. resistance 9 Ventilateur (2) Fan (2) 4606 N ATV -66U41N4 VW3-A66502 LC1-D1810 ATV -66U41N4 VW3-A66501 2,5 mm2 10A LC1-D1810 VW3-A16702 9 4606 N ATV -66U41N4 VW3-A66502 2 VW3-A16702 9 4606 N LC1-D2510 ATV -66U54N4 VW3-A66502 2 GV2-L16 14A GV2-L20 18A VW3-A16704 9 4606 N LC1-D2510 ATV -66U72N4 VW3-A66502 2 VW3-A16704 9 4606 N 25A LC1-D2510 ATV -66U90N4 VW3-A66503 2 50 GV2-L22 50 GV2-L22 25A LC1-D3210 ATV -66D12N4 VW3-A66503 11 70 15 70 NS80H-MA 50A LC1-D4011 ATV -66D16N4 VW3-A66504 NS80H-MA 50A LC1-D5011 ATV -66D23N4 VW3-A66504 Circuit breaker 15 25 GK3-EF65 65A LC1-D5011 ATV -66D23N4 18.5 25 GK3-EF65 65A LC1-D6511 ATV -66D33N4 18.5 70 NS80H-MA 80A LC1-D8011 ATV -66D33N4 22 25 GK3-EF80 80A LC1-D8011 ATV -66D33N4 22 70 NS80H-MA 80A LC1-D8011 ATV -66D33N4 30 25 GK3-EF80 80A LC1-D8011 ATV -66D46N4 30 70 NS80H-MA 80A LC1-D8011 ATV -66D46N4 37 35 NS100H-MA 100A LC1-D115006 ATV -66D54N4 37 70 NS100H-MA 100A LC1-D115006 ATV -66D54N4 45 35 NS160H-MA 150A LC1-D115006 ATV -66D64N4 45 70 NS160H-MA 150A LC1-D115006 ATV -66D64N4 55 35 NS160H-MA 150A LC1-D150006 ATV -66D79N4 55 70 NS160H-MA 150A LC1-D150006 ATV -66D79N4 Guide Technique V9 / V9 Technical Guide 2,5 mm 2,5 mm 2,5 mm VW3-A66701 12 4606 N 2 VW3-A66701 12 4606 N 2 VW3-A66702 12 4606 N 2 VW3-A66702 12 2 x 4606 N 2,5 mm 4 mm 4 mm 6 mm 12 4606 N 2 10 mm VW3-A66703 24 3 x 4606 ES 16 mm2 VW3-A66703 24 3 x 4606 ES 2 16 mm VW3-A66703 24 3 x 4606 ES 16 mm2 VW3-A66703 24 3 x 4606 ES 2 16 mm VW3-A66703 24 3 x 4606 ES 16 mm2 VW3-A66703 24 3 x 4606 ES 2 VW3-A66704 36 *** 4 x 4606 ES 2 VW3-A66704 36 *** 4 x 4606 ES 2 VW3-A66704 36 *** 4 x 4606 ES 2 VW3-A66704 36 *** 4 x 4606 ES 2 VW3-A66704 36 *** 4 x 4606 ES 2 VW3-A66704 36 *** 4 x 4606 ES 6 mm2 VW3-A66505 VW3-A66505 VW3-A66505 35 mm VW3-A66506 35 mm 35 mm VW3-A66506 35 mm 35 mm VW3-A66506 35 mm 203 Installation de l’appareillage Switchgear Installation Blokset Ms Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de puissance doivent être déclassés de 11% pour ATV 66. Dans le cas d’une température ambiant plus élevée, consulter GIB. (1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter le nombre de modules. (2): Les ventilateurs ont été définis pour chaque unité fonctionnel sans la résistance de freinage. Pour installer la résistance de freinage, consulter GIB. *: plus 12 modules seulement pour résistance de freinage **: plus 12 modules seulement pour résistance de freinage ou utiliser extension arrière de 700X2200x400 ***: plus extension arrière 700X2200x400 pour inductance de ligne et résistance de freinage Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653. Guide Technique V9 / V9 Technical Guide Note: in case of switchboard installed in an ambient with 35 °C the values of power must be derated in 11% for ATV 66. In case of higher ambient temperature, consult BIM. (1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the number of modules. (2): The fans were defined for functional units without breaking resistance. If breaking resistance is needed consult BIM. *: add12 modules only for breaking resistance **: add 12 modules only for breaking resistance or add rear column 700X2200x400 ***: add rear column 700X2200x400 for line coil and breaking resistance Single line diagrams, according Telemecanique catalogue ART. 16653. 204 Installation de l’appareillage Switchgear Installation Blokset Ms 3.5.1.6. \ATV66 220/240 V Puissance (kW) Power (kW) 0.75 Icc coord. (kA) Icc coord. (kA) 130 1.5 Couple: variable Torque: variable ATV66 Disjoncteur Couple: variable Torque: variable Contacteur (1) Contactor (1) LC1-D1810 ATV GV2-L20 Calibre (A) Rating (A) 8A 130 GV2-L20 18A 2.2 130 GV2-L20 3 130 4 100 5.5 Température ambiant 30 °C Ambient temperature 30 °C ATV Inductance de ligne Line coil Raccord. section cable cross section area 2,5 mm2 Résistance de freinage Break. Resistance VW3-A66701 Nr. de Modules avec ou sans résistance Nb. Mod. with or without break. resistance 9 Ventilateur (2) Fan (2) 4606 N ATV -66U41M2 VW3-A66504 LC1-D1810 ATV -66U41M2 VW3-A66504 2,5 mm2 18A LC1-D1810 VW3-A66701 9 4606 N ATV -66U41M2 VW3-A66504 2 VW3-A66701 9 4606 N LC1-D2510 ATV -66U41M2 VW3-A66504 2 GV2-L22 25A NS80H-MA 25A VW3-A66701 9 4606 N LC1-D4011 ATV -66U72M2 VW3-A66504 2 4 mm VW3A66702 12 4606 N 100 NS80H-MA 50A LC1-D4011 ATV -66U72M2 VW3-A66504 4 mm2 7.5 100 NS80H-MA VW3A66702 12 4606 N 50A LC1-D5011 ATV -66U90M2 VW3-A66505 2 VW3A66702 12 4606 N GK3-EF65 65A LC1-D6511 ATV -66D12M2 VW3-A66505 2 11 50 11 100 VW3-A66703 12 2 x 4606 ES NS80H-MA 80A LC1-D8011 ATV -66D12M2 VW3-A66505 2 16 mm VW3-A66703 12 2 x 4606 ES 15 50 GK3-EF80 80A LC1-D8011 15 100 NS80H-MA 80A LC1-D8011 ATV -66D23M2 VW3-A66506 16 mm2 VW3-A66704 24 ** 3 x 4606 ES ATV -66D23M2 VW3-A66506 2 16 mm VW3-A66704 24 ** 3 x 4606 ES 18.5 85 NS100H-MA 100A LC1-D9511 ATV -66D23M2 18.5 100 NS100H-MA 100A LC1-D115006 ATV -66D23M2 25 mm2 VW3-A66704 24 ** 3 x 4606 ES 2 25 mm VW3-A66704 24 ** 4 x 4606 ES 22 85 NS100H-MA 100A LC1-D115006 ATV -66D33M2 22 100 NS100H-MA 100A LC1-D115006 ATV -66D33M2 35 mm2 VW3-A66704 24 ** 4 x 4606 ES 2 35 mm VW3-A66704 24 ** 4 x 4606 ES 30 85 NS160H-MA 150A LC1-D150006 ATV -66D33M2 35 mm2 VW3-A66704 24 ** 4 x 4606 ES 2 30 100 NS160H-MA 150A LC1-D150006 ATV -66D33M2 37 85 NS250H-MA 220A LC1-F185 ATV -66D46M2 VW3-A66704 24 ** 4 x 4606 ES 2 50 mm VW3-A66704 36 *** 4 x 4606 ES 37 100 NS250H-MA 220A LC1-F185 ATV -66D46M2 50 mm2 VW3-A66704 36 *** 4 x 4606 ES Circuit breaker Guide Technique V9 / V9 Technical Guide VW3 A66506 VW3-A66507 VW3-A66507 VW3-A66507 2,5 mm 2,5 mm 6 mm 10 mm 35 mm 205 Installation de l’appareillage Switchgear Installation Blokset Ms Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de puissance doivent être déclassés de 11% pour ATV 66. Dans le cas d’une température ambiant plus élevée, consulter GIB. (1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter le nombre de modules. (2): Les ventilateurs ont été définis pour chaque unité fonctionnel sans la résistance de freinage. Pour installer la résistance de freinage, consulter GIB. *: plus 12 modules seulement pour résistance de freinage **: plus 12 modules seulement pour résistance de freinage ou utiliser extension arrière de 700X2200x400 ***: plus extension arrière 700X2200x400 pour inductance de ligne et résistance de freinage Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653. Guide Technique V9 / V9 Technical Guide Note: in case of switchboard installed in an ambient with 35 °C the values of power must be derated in 11% for ATV 66. In case of higher ambient temperature, consult BIM. (1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the number of modules. (2): The fans were defined for functional units without breaking resistance. If breaking resistance is needed consult BIM. *: add12 modules only for breaking resistance **: add 12 modules only for breaking resistance or add rear column 700X2200x400 ***: add rear column 700X2200x400 for line coil and breaking resistance Single line diagrams, according Telemecanique catalogue ART. 16653. 206 Installation de l’appareillage Switchgear Installation Blokset Ms 380/460 V Puissance (kW) Power (kW) 0.75 Icc coord. (kA) Icc coord. (kA) 130 1.5 ATV66 Disjoncteur Couple: variable Torque: variable Contacteur (1) Contactor (1) LC1-D0910 ATV GV2-L08 Calibre (A) Rating (A) 4A 50 GV2-L10 6,3A 2.2 50 GV2-L14 3 50 4 50 5.5 7.5 Température ambiant 30 °C Ambient temperature 30 °C ATV Inductance de ligne Line coil Raccord. section cable cross section area 2,5 mm2 Résistance de freinage Break. Resistance VW3-A16702 Nr. de Modules avec ou sans résistance Nb. Mod. with or without break. resistance 9 Ventilateur (2) Fan (2) 4606 N ATV -66U41N4 VW3-A66502 LC1-D1810 ATV -66U41N4 VW3-A66501 2,5 mm2 10A LC1-D1810 VW3-A16702 9 4606 N ATV -66U41N4 VW3-A66502 2 VW3-A16702 9 4606 N LC1-D2510 ATV -66U41N4 VW3-A66502 2 GV2-L16 14A GV2-L20 18A VW3-A16702 9 4606 N LC1-D2510 ATV -66U54N4 VW3-A66502 2 VW3-A16704 9 4606 N 25A LC1-D2510 ATV -66U72N4 VW3-A66503 2 50 GV2-L22 50 GV2-L22 VW3-A16704 9 4606 N 25A LC1-D3210 ATV -66U90N4 VW3-A66503 2 4 mm VW3-A66701 12 4606 N 11 70 NS80H-MA 50A LC1-D4011 ATV -66D12N4 VW3-A66503 4 mm2 15 70 VW3-A66701 12 4606 N NS80H-MA 50A LC1-D5011 ATV -66D16N4 VW3-A66504 2 VW3-A66702 12 4606 N 12 4606 N 2 10 mm VW3-A66702 12 2 x 4606 N 16 mm2 VW3-A66702 12 2 x 4606 N 2 16 mm VW3-A66703 24 3 x 4606 N 16 mm2 VW3-A66703 24 3 x 4606 N 2 16 mm VW3-A66703 24 3 x 4606 N 16 mm2 VW3-A66703 24 3 x 4606 N 2 VW3-A66703 24 4 x 4606 N 2 VW3-A66703 24 4 x 4606 N 2 VW3-A66704 36 *** 4 x 4606 N 2 VW3-A66704 36 *** 4 x 4606 N 2 VW3-A66704 36 *** 4 x 4606 N 2 VW3-A66704 36 *** 4 x 4606 N 2 VW3-A66704 36 *** 4 x 4606 N 2 VW3-A66704 36 *** 4 x 4606 N Circuit breaker 15 25 GK3-EF65 65A LC1-D5011 ATV -18D23N4 18.5 25 GK3-EF65 65A LC1-D6511 ATV -66D23N4 18.5 70 NS80H-MA 80A LC1-D8011 ATV -66D23N4 22 25 GK3-EF80 80A LC1-D8011 ATV -66D33N4 22 70 NS80H-MA 80A LC1-D8011 ATV -66D33N4 30 25 GK3-EF80 80A LC1-D8011 ATV -66D33N4 30 70 NS80H-MA 80A LC1-D8011 ATV -66D33N4 37 35 NS100H-MA 100A LC1-D115006 ATV -66D46N4 37 70 NS100H-MA 100A LC1-D115006 ATV -66D46N4 45 35 NS160H-MA 150A LC1-D115006 ATV -66D54N4 45 70 NS160H-MA 150A LC1-D115006 ATV -66D54N4 55 35 NS160H-MA 150A LC1-D150006 ATV -66D64N4 55 70 NS160H-MA 150A LC1-D150006 ATV -66D64N4 75 35 NS250H-MA 220A LC1-F185 ATV -66D79N4 75 70 NS250H-MA 220A LC1-F185 ATV -66D79N4 Guide Technique V9 / V9 Technical Guide 2,5 mm 2,5 mm 2,5 mm 2,5 mm 6 mm 6 mm2 VW3-A66505 VW3-A66505 VW3-A66505 35 mm VW3-A66506 35 mm 35 mm VW3-A66506 35 mm 35 mm VW3-A66506 35 mm 50 mm VW3-A66507 50 mm 207 Installation de l’appareillage Switchgear Installation Blokset Ms Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de puissance doivent être déclassés de 11% pour ATV 66. Dans le cas d’une température ambiant plus élevée, consulter GIB. (1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter le nombre de modules. (2): Les ventilateurs ont été définis pour chaque unité fonctionnel sans la résistance de freinage. Pour installer la résistance de freinage, consulter GIB. *: plus 12 modules seulement pour résistance de freinage **: plus 12 modules seulement pour résistance de freinage ou utiliser extension arrière de 700X2200x400 ***: plus extension arrière 700X2200x400 pour inductance de ligne et résistance de freinage Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653. Guide Technique V9 / V9 Technical Guide Note: in case of switchboard installed in an ambient with 35 °C the values of power must be derated in 11% for ATV 66. In case of higher ambient temperature, consult BIM. (1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the number of modules. (2): The fans were defined for functional units without breaking resistance. If breaking resistance is needed consult BIM. *: add12 modules only for breaking resistance **: add 12 modules only for breaking resistance or add rear column 700X2200x400 ***: add rear column 700X2200x400 for line coil and breaking resistance Single line diagrams, according Telemecanique catalogue ART. 16653. 208 Installation de l’appareillage Switchgear Installation Blokset Ms 3.5.1.7. ATV66 220/240 V Puissance (kW) Power (kW) 0.75 Icc coord. (kA) Icc coord. (kA) 130 1.5 Couple: Variable faible bruit Torque: Low noise ATV66 Disjoncteur Couple: variable faible bruit Torque: Low noise GV2-L20 Calibre (A) Rating (A) 18A Contacteur (1) Contactor (1) LC1-D1810 ATV Inductance de ligne Line coil Raccord. section cable cross section area 2,5 mm2 Résistance de freinage Break. Resistance VW3-A66701 Nr. de Modules avec ou sans résistance Nb. Mod. with or without break. resistance 9 Ventilateur (2) Fan (2) 4606 N ATV -66U41M2 VW3-A66503 130 GV2-L20 18A LC1-D1810 ATV -66U41M2 VW3-A66503 2,5 mm2 2.2 130 GV2-L20 18A LC1-D1810 VW3-A66701 9 4606 N ATV -66U41M2 VW3-A66503 2 VW3-A66701 9 4606 N LC1-D2510 ATV -66U72M2 VW3-A66504 2 3 130 4 100 GV2-L22 25A NS80H-MA 25A LC1-D4011 ATV -66U72M2 VW3-A66504 5.5 7.5 100 NS80H-MA 50A 50 GK3-EF65 65A LC1-D4011 ATV -66U90M2 VW3-A66504 LC1-D5011 ATV -66D12M2 VW3-A66505 7.5 100 NS80H-MA 50A 11 50 GK3-EF65 65A LC1-D5011 ATV -66D12M2 VW3-A66505 LC1-D6511 ATV -66D16M2 VW3-A66505 2 11 100 NS80H-MA 15 50 GK3-EF80 80A LC1-D8011 ATV -66D16M2 80A LC1-D8011 ATV -66D23M2 15 100 NS80H-MA 80A LC1-D8011 ATV -66D23M2 18.5 85 NS100H-MA 100A LC1-D9511 ATV -66D33M2 18.5 85 NS100H-MA 100A LC1-D115006 22 85 NS100H-MA 100A LC1-D115006 22 100 NS100H-MA 100A LC1-D115006 ATV -66D33M2 30 85 NS160H-MA 150A LC1-D150006 ATV -66D46M2 30 100 NS160H-MA 150A LC1-D150006 ATV -66D46M2 Circuit breaker Guide Technique V9 / V9 Technical Guide ATV Température ambiant 30 °C Ambient temperature 30 °C 2,5 mm VW3A66702 12 4606 N 2 VW3A66702 12 4606 N 2 VW3A66702 12 4606 N 2 VW3-A66703 12 2 x 4606 N VW3-A66703 12 2 x 4606 N 10 mm VW3-A66704 12 * 2 x 4606 N VW3-A66505 16 mm2 VW3-A66704 12 * 2 x 4606 N VW3-A66506 2 16 mm VW3-A66704 24 ** 3 x 4606 N VW3-A66506 16 mm2 VW3-A66704 24 ** 3 x 4606 N 2 25 mm VW3-A66704 24 ** 3 x 4606 N ATV -66D33M2 35 mm2 VW3-A66704 24 ** 3 x 4606 N ATV -66D33M2 2 35 mm VW3-A66704 24 ** 3 x 4606 N 35 mm2 VW3-A66704 24 ** 4 x 4606 N 2 VW3-A66704 36 *** 4 x 4606 N 2 VW3-A66704 36 *** 4 x 4606 N VW3-A66506 2,5 mm 4 mm 4 mm 6 mm 2 6 mm 35 mm VW3-A66507 35 mm 209 Installation de l’appareillage Switchgear Installation Blokset Ms Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de puissance doivent être déclassés de 11% pour ATV 66. Dans le cas d’une température ambiant plus élevée, consulter GIB. (1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter le nombre de modules. (2): Les ventilateurs ont été définis pour chaque unité fonctionnel sans la résistance de freinage. Pour installer la résistance de freinage, consulter GIB. *: plus 12 modules seulement pour résistance de freinage **: plus 12 modules seulement pour résistance de freinage ou utiliser extension arrière de 700X2200x400 ***: plus extension arrière 700X2200x400 pour inductance de ligne et résistance de freinage Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653. Guide Technique V9 / V9 Technical Guide Note: in case of switchboard installed in an ambient with 35 °C the values of power must be derated in 11% for ATV 66. In case of higher ambient temperature, consult BIM. (1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the number of modules. (2): The fans were defined for functional units without breaking resistance. If breaking resistance is needed consult BIM. *: add12 modules only for breaking resistance **: add 12 modules only for breaking resistance or add rear column 700X2200x400 ***: add rear column 700X2200x400 for line coil and breaking resistance Single line diagrams, according Telemecanique catalogue ART. 16653. 210 Installation de l’appareillage Switchgear Installation Blokset Ms 380/460 V Puissance (kW) Power (kW) 0.75 Icc coord. (kA) Icc coord. (kA) 130 1.5 ATV66 Disjoncteur Couple: variable faible bruit Torque: Low noise Contacteur (1) Contactor (1) LC1-D0910 ATV GV2-L08 Calibre (A) Rating (A) 4A 50 GV2-L10 6,3A 2.2 50 GV2-L14 3 50 4 50 5.5 7.5 Température ambiant 30 °C Ambient temperature 30 °C ATV Inductance de ligne Line coil Raccord. section cable cross section area 2,5 mm2 Résistance de freinage Break. Resistance VW3-A16702 Nr. de Modules avec ou sans résistance Nb. Mod. with or without break. resistance 9 Ventilateur (2) Fan (2) 4606 N ATV -66U41N4 VW3-A66502 LC1-D1810 ATV -66U41N4 VW3-A66501 2,5 mm2 10A LC1-D1810 VW3-A16702 9 4606 N ATV -66U41N4 VW3-A66502 2 VW3-A16702 9 4606 N LC1-D2510 ATV -66U54N4 VW3-A66502 2 GV2-L16 14A GV2-L20 18A VW3-A16704 9 4606 N LC1-D2510 ATV -66U72N4 VW3-A66502 2 VW3-A16704 9 4606 N 25A LC1-D2510 ATV -66U90N4 VW3-A66503 2 50 GV2-L22 50 GV2-L22 25A LC1-D3210 ATV -66D12N4 VW3-A66503 7.5 15 11 70 GV2-L22 25A LC1-D3210 ATV -66D16N4 NS80H-MA 50A LC1-D4011 ATV -66D16M2 15 25 GK3-EF65 15 70 NS80H-MA 65A LC1-D5011 ATV -66D23N4 50A LC1-D5011 ATV -66D23N4 18.5 25 GK3-EF65 65A LC1-D6511 ATV -66D33N4 18.5 70 NS80H-MA 80A LC1-D8011 ATV -66D33N4 22 25 GK3-EF80 80A LC1-D8011 ATV -66D33N4 22 70 NS80H-MA 80A LC1-D8011 ATV -66D33N4 30 25 GK3-EF80 80A LC1-D8011 ATV -66D46N4 30 70 NS80H-MA 80A LC1-D8011 ATV -66D46N4 37 35 NS100H-MA 100A LC1-D115006 ATV -66D54N4 37 70 NS100H-MA 100A LC1-D115006 ATV -66D54N4 45 35 NS160H-MA 150A LC1-D115006 ATV -66D64N4 45 70 NS160H-MA 150A LC1-D115006 ATV -66D64N4 55 35 NS160H-MA 150A LC1-D150006 ATV -66D79N4 55 70 NS160H-MA 150A LC1-D150006 ATV -66D79N4 Circuit breaker Guide Technique V9 / V9 Technical Guide 2,5 mm 2,5 mm 2,5 mm VW3-A66701 12 4606 N 2 VW3-A66701 12 4606 N 2 VW3-A66702 12 4606 N 2 4 mm VW3-A66704 12 * 2 x 4606 N 6 mm2 VW3-A66702 12 4606 N 2 VW3-A66702 12 2 x 4606 N 10 mm2 VW3-A66703 24 3 x 4606 N 2 16 mm VW3-A66703 24 3 x 4606 N 16 mm2 VW3-A66703 24 3 x 4606 N 2 16 mm VW3-A66703 24 3 x 4606 N 16 mm2 VW3-A66703 24 3 x 4606 N 2 VW3-A66703 24 3 x 4606 N 2 35 mm VW3-A66704 36 *** 4 x 4606 N 35 mm2 VW3-A66704 36 *** 4 x 4606 N 2 VW3-A66704 36 *** 4 x 4606 N 2 VW3-A66704 36 *** 4 x 4606 N 2 VW3-A66704 36 *** 4 x 4606 N 2 VW3-A66704 36 *** 4 x 4606 N 2,5 mm 4 mm 4 mm VW3-A66504 VW3-A66504 VW3-A66505 VW3-A66505 VW3-A66505 VW3-A66506 6 mm 16 mm 35 mm VW3-A66506 35 mm 35 mm VW3-A66506 35 mm 211 Installation de l’appareillage Switchgear Installation Blokset Ms Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de puissance doivent être déclassés de 11% pour ATV 66. Dans le cas d’une température ambiant plus élevée, consulter GIB. (1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter le nombre de modules. (2): Les ventilateurs ont été définis pour chaque unité fonctionnel sans la résistance de freinage. Pour installer la résistance de freinage, consulter GIB. *: plus 12 modules seulement pour résistance de freinage **: plus 12 modules seulement pour résistance de freinage ou utiliser extension arrière de 700X2200x400 ***: plus extension arrière 700X2200x400 pour inductance de ligne et résistance de freinage Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653. Guide Technique V9 / V9 Technical Guide Note: in case of switchboard installed in an ambient with 35 °C the values of power must be derated in 11% for ATV 66. In case of higher ambient temperature, consult BIM. (1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the number of modules. (2): The fans were defined for functional units without breaking resistance. If breaking resistance is needed consult BIM. *: add12 modules only for breaking resistance **: add 12 modules only for breaking resistance or add rear column 700X2200x400 ***: add rear column 700X2200x400 for line coil and breaking resistance Single line diagrams, according Telemecanique catalogue ART. 16653. 212 Installation de l’appareillage Switchgear Installation Blokset Ms 3.5.1.8. ATS46 Coordination Type 1- - - - - - - - - - - - - - - - - - - Service: Standard Coordination Type 1- - - - - - - - - - - - - - - - - - - Service: Standard ATS46 220/240 V Coordination Type 1 Coordination Type 1 Service: Standard Service: Standard Température ambiant 30 °C Ambient temperature 30 °C Puissance (kW) Power (kW) 4 Icc coord. (kA) Icc coord. (kA) 15 Disjoncteur Circuit breaker GV2-L20 Calibre (A) Rating (A) - Contacteur (1) Contactor (1) LC1-D1810 ATS ATS ATS-46D17N Taille Size 1 Inductance de ligne Line coil VZ1-L015UM17T Raccordement section cable cross 4 mm2 Nombre de modules Number of modules 9 Ventilateur Fan 4606 N 4 15 GV2-M20 - LC1-D1810 ATS-46D17N 1 VZ1-L015UM17T 4 mm2 5,5 15 GV2-L22 - LC1-D2510 ATS-46D22N 1 VZ1-L030U800T 9 4606 N 6 mm 2 9 4606 N 6 mm 2 5,5 15 GV2-M22 - LC1-D2510 ATS-46D22N 1 VZ1-L030U800T 7,5 15 GK3-EF40 - LC1-D3210 ATS-46D32N 1 VZ1-L040U600T 9 4606 N 6 mm 2 12 4606 N 7,5 15 GV3-M63 - LC1-D3210 ATS-46D32N 1 VZ1-L040U600T 6 mm2 9 15 GK3-EF40 - LC1-D4011 ATS-46D38N 12 4606 N 1 VZ1-L040U600T 6 mm 2 12 4606 N ATS-46D38N 1 VZ1-L040U600T 6 mm 2 9 15 GV3-M63 - LC1-D4011 11 15 GK3-EF65 - LC1-D5011 12 4606 N ATS-46D47N 2 VZ1-L070U350T 10 mm 2 12 4606 N 15 15 GK3-EF65 - LC1-D6511 ATS-46D62N 2 VZ1-L070U350T 16 mm2 12 4606 N 18,5 15 GK3-EF80 - LC1-D8011 ATS-46D75N 2 VZ1-L150U170T 25 mm 2 12 4606 N 22 15 NS100N MA 100 LC1-D9511 ATS-46D88N 2 VZ1-L150U170T 35 mm2 12 4606 N 30 15 NS160N MA 150 LC1-F115 ATS-46C11N 2 VZ1-L150U170T 50 mm 2 18 4606 N 37 15 NS160N MA 150 LC1-F150 ATS-46C14N 2 VZ1-L150U170T 50 mm2 18 4606 N 45 15 NS250N MA 220 LC1-F185 ATS-46C17N 3 VZ1-L250U100T 95 mm 2 36 2 x 4606 N 55 15 NS250N MA 220 LC1-F225 ATS-46C21N 3 VZ1-L250U100T 95 mm2 36 2 x 4606 N 75 15 NS400N MA 320 LC1-F265 ATS-46C25N 3 VZ1-L250U100T 95 mm 2 36 2 x 4606 N 90 15 NS400N MA 320 LC1-F330 ATS-46C32N 3 VZ1-L325U075T 95 mm 2 36 2 x 4606 N Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température ambiant plus élevée, consulter GIB. (1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter le nombre de modules. Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653. Guide Technique V9 / V9 Technical Guide Note: in case of switchboard installed in an ambient with 35 °C the values of power must be derated in 6% for ATS 46. In case of higher ambient temperature, consult BIM. (1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the number of modules Single line diagrams, according Telemecanique catalogue ART. 16653. 213 Installation de l’appareillage Switchgear Installation Blokset Ms ATS46 380/400 V Coordination Type 1 Coordination Type 1 Service: Standard Service: Standard Température ambiant 30 °C Ambient temperature 30 °C Puissance (kW) Power (kW) 7,5 Icc coord. (kA) Icc coord. (kA) 15 Disjoncteur Circuit breaker GV2-L20 Calibre (A) Rating (A) - Contacteur (1) Contactor (1) LC1-D1810 ATS ATS ATS-46D17N Taille Size 1 Inductance de ligne Line coil VZ1-L015UM17T Raccordement section cable cross 4 mm2 Nombre de modules Number of modules 9 Ventilateur Fan 4606 N 7,5 15 GV2-M20 - LC1-D1810 ATS-46D17N 1 VZ1-L015UM17T 4 mm2 11 15 GV2-L22 - LC1-D2510 ATS-46D22N 1 VZ1-L030U800T 9 4606 N 6 mm 2 9 4606 N 6 mm 2 11 15 GV2-M22 - LC1-D2510 ATS-46D22N 1 VZ1-L030U800T 15 15 GK3-EF40 - LC1-D3210 ATS-46D32N 1 VZ1-L040U600T 9 4606 N 6 mm 2 12 4606 N 15 15 GV3-M63 - LC1-D3210 ATS-46D32N 1 VZ1-L040U600T 6 mm2 18,5 15 GK3-EF40 - LC1-D4011 ATS-46D38N 12 4606 N 1 VZ1-L040U600T 6 mm 2 12 4606 N ATS-46D38N 1 VZ1-L040U600T 6 mm 2 18,5 15 GV3-M63 - LC1-D4011 22 15 GK3-EF65 - LC1-D5011 12 4606 N ATS-46D47N 2 VZ1-L070U350T 10 mm 2 12 4606 N 30 15 GK3-EF65 - LC1-D6511 37 15 GK3-EF80 - LC1-D8011 ATS-46D62N 2 VZ1-L070U350T 16 mm2 12 4606 N ATS-46D75N 2 VZ1-L150U170T 25 mm 2 12 4606 N 45 15 NS100N MA 100 55 15 NS160N MA 150 LC1-D9511 ATS-46D88N 2 VZ1-L150U170T 35 mm2 12 4606 N LC1-F115 ATS-46C11N 2 VZ1-L150U170T 50 mm 2 18 4606 N 75 15 NS160N MA 90 15 NS250N MA 150 LC1-F150 ATS-46C14N 2 VZ1-L150U170T 50 mm2 18 4606 N 220 LC1-F185 ATS-46C17N 3 VZ1-L250U100T 95 mm 2 36 2 x 4606 N 110 15 NS250N MA 220 LC1-F225 ATS-46C21N 3 VZ1-L250U100T 95 mm2 36 2 x 4606 N 15 NS400N MA 320 LC1-F265 ATS-46C25N 3 VZ1-L250U100T 95 mm 2 132 160 36 2 x 4606 N 15 NS400N MA 320 LC1-F330 ATS-46C32N 3 VZ1-L325U075T 95 mm 2 36 2 x 4606 N Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température ambiant plus élevée, consulter GIB. (1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter le nombre de modules. Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653. Guide Technique V9 / V9 Technical Guide Note: in case of switchboard installed in an ambient with 35 °C the values of power must be derated in 6% for ATS 46. In case of higher ambient temperature, consult BIM. (1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the number of modules Single line diagrams, according Telemecanique catalogue ART. 16653. 214 Installation de l’appareillage Switchgear Installation Blokset Ms ATS46 415 V Coordination Type 1 Coordination Type 1 Service: Standard Service: Standard Température ambiant 30 °C Ambient temperature 30 °C Puissance (kW) Power (kW) 7,5 Icc coord. (kA) Icc coord. (kA) 15 Disjoncteur Circuit breaker GV2-L20 Calibre (A) Rating (A) - Contacteur (1) Contactor (1) LC1-D1810 ATS ATS ATS-46D17N Taille Size 1 Inductance de ligne Line coil VZ1-L015UM17T Raccordement section cable cross 4 mm2 Nombre de modules Number of modules 9 Ventilateur Fan 4606 N 7,5 15 GV2-M20 - LC1-D1810 ATS-46D17N 1 VZ1-L015UM17T 4 mm2 11 15 GV2-L22 - LC1-D2510 ATS-46D22N 1 VZ1-L030U800T 9 4606 N 6 mm 2 9 4606 N 6 mm 2 11 15 GV2-M22 - LC1-D2510 ATS-46D22N 1 VZ1-L030U800T 15 15 GK3-EF40 - LC1-D3210 ATS-46D32N 1 VZ1-L040U600T 9 4606 N 6 mm 2 12 4606 N 15 15 GV3-M63 - LC1-D3210 ATS-46D32N 1 VZ1-L040U600T 6 mm2 18,5 15 GK3-EF40 - LC1-D4011 ATS-46D38N 12 4606 N 1 VZ1-L040U600T 6 mm 2 12 4606 N ATS-46D38N 1 VZ1-L040U600T 6 mm 2 18,5 15 GV3-M63 - LC1-D4011 22 15 GK3-EF65 - LC1-D5011 12 4606 N ATS-46D47N 2 VZ1-L070U350T 10 mm 2 12 4606 N 30 15 GK3-EF65 - LC1-D6511 37 15 GK3-EF80 - LC1-D8011 ATS-46D62N 2 VZ1-L070U350T 16 mm2 12 4606 N ATS-46D75N 2 VZ1-L150U170T 25 mm 2 12 4606 N 45 15 NS100N MA 100 55 15 NS160N MA 150 LC1-D9511 ATS-46D88N 2 VZ1-L150U170T 35 mm2 12 4606 N LC1-F115 ATS-46C11N 2 VZ1-L150U170T 50 mm 2 18 4606 N 75 15 NS160N MA 90 15 NS250N MA 150 LC1-F150 ATS-46C14N 2 VZ1-L150U170T 50 mm2 18 4606 N 220 LC1-F185 ATS-46C17N 3 VZ1-L250U100T 95 mm 2 36 2 x 4606 N 110 15 NS250N MA 220 LC1-F225 ATS-46C21N 3 VZ1-L250U100T 95 mm2 36 2 x 4606 N 15 NS400N MA 320 LC1-F265 ATS-46C25N 3 VZ1-L250U100T 95 mm 2 132 160 36 2 x 4606 N 15 NS400N MA 320 LC1-F330 ATS-46C32N 3 VZ1-L325U075T 95 mm 2 36 2 x 4606 N Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température ambiant plus élevée, consulter GIB. (1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter le nombre de modules. Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653. Guide Technique V9 / V9 Technical Guide Note: in case of switchboard installed in an ambient with 35 °C the values of power must be derated in 6% for ATS 46. In case of higher ambient temperature, consult BIM. (1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the number of modules Single line diagrams, according Telemecanique catalogue ART. 16653. 215 Installation de l’appareillage Switchgear Installation Blokset Ms ATS46 440 V Coordination Type 1 Coordination Type 1 Service: Standard Service: Standard Température ambiant 30 °C Ambient temperature 30 °C Puissance (kW) Power (kW) 7,5 Icc coord. (kA) Icc coord. (kA) 15 Disjoncteur Circuit breaker GV2-L20 Calibre (A) Rating (A) - Contacteur (1) Contactor (1) LC1-D1810 ATS ATS ATS-46D17N Taille Size 1 Inductance de ligne Line coil VZ1-L015UM17T Raccordement section cable cross 4 mm2 Nombre de modules Number of modules 9 Ventilateur Fan 4606 N 7,5 15 GV2-M20 - LC1-D1810 ATS-46D17N 1 VZ1-L015UM17T 4 mm2 11 15 GV2-L22 - LC1-D2510 ATS-46D22N 1 VZ1-L030U800T 9 4606 N 6 mm 2 9 4606 N 6 mm 2 11 15 GV2-M22 - LC1-D2510 ATS-46D22N 1 VZ1-L030U800T 15 15 GK3-EF40 - LC1-D3210 ATS-46D32N 1 VZ1-L040U600T 9 4606 N 6 mm 2 12 4606 N 15 15 GV3-M63 - LC1-D3210 ATS-46D32N 1 VZ1-L040U600T 6 mm2 18,5 15 GK3-EF40 - LC1-D4011 ATS-46D38N 12 4606 N 1 VZ1-L040U600T 6 mm 2 12 4606 N ATS-46D38N 1 VZ1-L040U600T 6 mm 2 18,5 15 GV3-M63 - LC1-D4011 22 15 GK3-EF65 - LC1-D5011 12 4606 N ATS-46D47N 2 VZ1-L070U350T 10 mm 2 12 4606 N 30 15 GK3-EF65 - LC1-D6511 37 15 GK3-EF80 - LC1-D8011 ATS-46D62N 2 VZ1-L070U350T 16 mm2 12 4606 N ATS-46D75N 2 VZ1-L150U170T 25 mm 2 12 4606 N 45 15 NS100N MA 100 55 15 NS160N MA 150 LC1-D9511 ATS-46D88N 2 VZ1-L150U170T 35 mm2 12 4606 N LC1-F115 ATS-46C11N 2 VZ1-L150U170T 50 mm 2 18 4606 N 75 15 NS160N MA 90 15 NS250N MA 150 LC1-F150 ATS-46C14N 2 VZ1-L150U170T 50 mm2 18 4606 N 220 LC1-F185 ATS-46C17N 3 VZ1-L250U100T 95 mm 2 36 2 x 4606 N 110 15 NS250N MA 220 LC1-F225 ATS-46C21N 3 VZ1-L250U100T 95 mm2 36 2 x 4606 N 15 NS400N MA 320 LC1-F265 ATS-46C25N 3 VZ1-L250U100T 95 mm 2 132 160 36 2 x 4606 N 15 NS400N MA 320 LC1-F330 ATS-46C32N 3 VZ1-L325U075T 95 mm 2 36 2 x 4606 N Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température ambiant plus élevée, consulter GIB. (1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter le nombre de modules. Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653. Guide Technique V9 / V9 Technical Guide Note: in case of switchboard installed in an ambient with 35 °C the values of power must be derated in 6% for ATS 46. In case of higher ambient temperature, consult BIM. (1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the number of modules Single line diagrams, according Telemecanique catalogue ART. 16653. 216 Installation de l’appareillage Switchgear Installation Blokset Ms ATS46 500 V Coordination Type 1 Coordination Type 1 Service: Standard Service: Standard Température ambiant 30 °C Ambient temperature 30 °C Puissance (kW) Power (kW) 9 Icc coord. (kA) Icc coord. (kA) 15 Disjoncteur Circuit breaker GV2-L20 Calibre (A) Rating (A) - Contacteur (1) Contactor (1) LC1-D1810 ATS ATS ATS-46D17N Taille Size 1 Inductance de ligne Line coil VZ1-L015UM17T Raccordement section cable cross 4 mm2 Nombre de modules Number of modules 9 Ventilateur Fan 4606 N 9 15 GV2-L20 - LC1-D1810 ATS-46D17N 1 VZ1-L015UM17T 4 mm2 9 15 GV2-M20 - LC1-D1810 ATS-46D17N 9 4606 N 1 VZ1-L015UM17T 4 mm 2 9 4606 N ATS-46D22N 1 VZ1-L030U800T 6 mm 2 11 15 GV2-L22 - LC1-D2510 11 15 GV2-M22 - LC1-D2510 9 4606 N ATS-46D22N 1 VZ1-L030U800T 6 mm 2 9 4606 N ATS-46D32N 1 VZ1-L040U600T 6 mm 2 18,5 15 GK3-EF40 - LC1-D3210 18,5 15 GV3-M63 - LC1-D3210 12 4606 N ATS-46D32N 1 VZ1-L040U600T 6 mm 2 12 4606 N LC1-D4011 ATS-46D38N 1 VZ1-L040U600T 6 mm 2 22 15 GK3-EF40 - 22 15 GV3-M63 - 12 4606 N LC1-D4011 ATS-46D38N 1 VZ1-L040U600T 6 mm 2 12 4606 N 30 15 GK3-EF65 - 37 15 GK3-EF65 - LC1-D5011 ATS-46D47N 2 VZ1-L070U350T 10 mm2 12 4606 N LC1-D6511 ATS-46D62N 2 VZ1-L070U350T 16 mm 2 12 4606 N 45 15 GK3-EF80 55 15 NS100N MA - LC1-D8011 ATS-46D75N 2 VZ1-L150U170T 25 mm2 12 4606 N 100 LC1-D9511 ATS-46D88N 2 VZ1-L150U170T 35 mm 2 12 4606 N 75 15 90 15 NS160N MA 150 LC1-F115 ATS-46C11N 2 VZ1-L150U170T 50 mm2 18 4606 N NS160N MA 150 LC1-F150 ATS-46C14N 2 VZ1-L150U170T 50 mm 2 18 4606 N 110 15 NS250N MA 220 LC1-F185 ATS-46C17N 3 VZ1-L250U100T 95 mm2 36* 2 x 4606 N 132 15 NS250N MA 220 LC1-F225 ATS-46C21N 3 VZ1-L250U100T 95 mm 2 36* 2 x 4606 N 160 15 NS400N MA 320 LC1-F265 ATS-46C25N 3 VZ1-L250U100T 95 mm 2 36* 2 x 4606 N 220 15 NS400N MA 320 LC1-F330 ATS-46C32N 3 VZ1-L325U075T 95 mm 2 36* 2 x 4606 N Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température ambiant plus élevée, consulter GIB. (1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter le nombre de modules. Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653. Guide Technique V9 / V9 Technical Guide Note: in case of switchboard installed in an ambient with 35 °C the values of power must be derated in 6% for ATS 46. In case of higher ambient temperature, consult BIM. (1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the number of modules Single line diagrams, according Telemecanique catalogue ART. 16653. 217 Installation de l’appareillage Switchgear Installation Blokset Ms 3.5.1.9. ATS46 220/240 V Puissance (kW) Power (kW) 4 Icc coord. (kA) Icc coord. (kA) 15 4 5,5 Coordination Type 2- - - - - - - - - - - - - - - - - - - Service: Standard Coordination Type 2- - - - - - - - - - - - - - - - - - - Service: Standard ATS46 Disjoncteur Coordination Type 2 Coordination Type 2 GV2-L20 Calibre (A) Rating (A) - Contacteur (1) Contactor (1) LC1-D2510 ATS Taille ATS Size ATS-46D17N 15 GV2-P21 - 15 GV2-L22 - LC1-D2510 LC1-D2510 5,5 15 GV2-P22 - 7,5 15 GV7-RS40 - LC1-D2510 LC1-D3210 7,5 15 NS80H-MA 50 LC1-D3210 9 15 GV7-RS50 - 9 15 11 15 NS80H-MA NS80H-MA Circuit breaker Service: Standard Service: Standard Température ambiant 30 °C Ambient temperature 30 °C Calibre Fusible Fuse rating 40 Inductance de ligne Line coil Raccordement section cable cross section area Nombre de modules Ventilateur Number of modules Fan 1 Fusible (2) Fuse (2) DF3-EF04001 VZ1-L015UM17T 4 mm2 9 4606 N ATS-46D17N 1 DF3-EF04001 40 VZ1-L015UM17T 2 9 4606 N ATS-46D22N 1 DF3-FF10001 100 VZ1-L030U800T 2 9 4606 N ATS-46D22N 1 DF3-FF10001 100 VZ1-L030U800T 2 9 4606 N ATS-46D32N 1 DF3-FF10001 100 VZ1-L040U600T 2 6 mm 12 4606 N ATS-46D32N 1 DF3-FF10001 100 VZ1-L040U600T 6 mm2 12 4606 N LC1-D5011 ATS-46D38N 1 DF3-FF10001 100 VZ1-L040U600T 2 12 4606 N 50 LC1-D5011 ATS-46D38N 1 DF3-FF10001 100 VZ1-L040U600T 12 4606 N 50 LC1-D5011 ATS-46D47N 2 DF3-NF40002 400 VZ1-L070U350T 2 10 mm 12 4606 N 4 mm 6 mm 6 mm 6 mm 2 6 mm 15 15 NS80H-MA - LC1-D6511 ATS-46D62N 2 DF3-NF40002 400 VZ1-L070U350T 16 mm2 12 4606 N 18,5 15 NS80H-MA - LC1-D8011 ATS-46D75N 2 DF3-NF40002 400 VZ1-L150U170T 2 25 mm 12 4606 N 22 15 NS100H-MA 100 LC1-F115 ATS-46D88N 2 DF3-NF40002 400 VZ1-L150U170T 35 mm2 18 4606 N 30 15 NS160H-MA 150 LC1-F115 ATS-46C11N 2 DF3-NF40002 400 VZ1-L150U170T 2 50 mm 18 4606 N 37 15 NS160H-MA 150 LC1-F150 ATS-46C14N 2 DF3-NF50002 500 VZ1-L150U170T 50 mm2 18 4606 N 45 15 NS250H-MA 220 LC1-F185 ATS-46C17N 3 DF3-NF50002 500 VZ1-L250U100T 2 95 mm 36 2 x 4606 N 55 15 NS250H-MA 220 LC1-F225 ATS-46C21N 3 DF3-NF50002 500 VZ1-L250U100T 95 mm2 36 2 x 4606 N 75 15 NS400H-MA 320 LC1-F265 ATS-46C25N 3 DF3-QF63002 630 VZ1-L250U100T 2 36 2 x 4606 N 90 15 NS400H-MA 320 LC1-F330 ATS-46C32N 3 DF3-QF80002 800 VZ1-L325U075T 2 36 2 x 4606 N Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température ambiant plus élevée, consulter GIB. (1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter le nombre de modules. (2): obrigatoire ajoute porte-fusible. Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653. Guide Technique V9 / V9 Technical Guide 95 mm 95 mm Note: in case of switchboard installed in a ambient with 35 °C the values of power must be derated in 6% for ATS 46. In case of higher ambient temperature, consult BIM. (1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the number of modules. (2): compulsory add fuse carrier. Single line diagrams, according Telemecanique catalogue ART. 16653. 218 Installation de l’appareillage Switchgear Installation Blokset Ms 380/400 V Puissance (kW) Power (kW) 7,5 Icc coord. (kA) Icc coord. (kA) 15 7,5 ATS46 Disjoncteur Coordination Type 2 Coordination Type 2 GV2-L20 Calibre (A) Rating (A) - Contacteur (1) Contactor (1) LC1-D2510 15 GV2-P21 - 11 15 GV2-L22 11 15 GV2-P22 15 15 15 15 18,5 18,5 Service: Standard Service: Standard ATS Taille ATS Size ATS-46D17N LC1-D2510 - GV7-RS40 NS80H-MA 15 GV7-RS50 15 NS80H-MA 22 15 NS80H-MA 30 15 NS80H-MA 37 15 NS80H-MA 45 15 NS100H-MA 55 15 NS160H-MA 150 LC1-F115 ATS-46C11N 2 DF3-NF40002 75 15 NS160H-MA 150 LC1-F150 ATS-46C14N 2 DF3-NF50002 90 15 NS250H-MA 220 LC1-F185 ATS-46C17N 3 DF3-NF50002 110 15 NS250H-MA 220 LC1-F225 ATS-46C21N 3 132 15 NS400H-MA 320 LC1-F265 ATS-46C25N 3 160 15 NS400H-MA 320 LC1-F330 ATS-46C32N 3 Circuit breaker Calibre Fusible Fuse rating 40 Inductance de ligne Line coil Raccordement section cable cross section area Nombre de modules Ventilateur Number of modules Fan 1 Fusible (2) Fuse (2) DF3-EF04001 VZ1-L015UM17T 4 mm2 9 4606 N ATS-46D17N 1 DF3-EF04001 40 VZ1-L015UM17T 2 9 4606 N LC1-D2510 ATS-46D22N 1 DF3-FF10001 100 VZ1-L030U800T 2 9 4606 N LC1-D2510 ATS-46D22N 1 DF3-FF10001 100 VZ1-L030U800T 2 9 4606 N - LC1-D3210 ATS-46D32N 1 DF3-FF10001 100 VZ1-L040U600T 2 12 4606 N 50 LC1-D3210 ATS-46D32N 1 DF3-FF10001 100 VZ1-L040U600T 2 12 4606 N - LC1-D5011 ATS-46D38N 1 DF3-FF10001 100 VZ1-L040U600T 2 12 4606 N 50 LC1-D5011 ATS-46D38N 1 DF3-FF10001 100 VZ1-L040U600T 2 6 mm 12 4606 N 50 LC1-D5011 ATS-46D47N 2 DF3-NF40002 400 VZ1-L070U350T 10 mm2 12 4606 N - LC1-D6511 ATS-46D62N 2 DF3-NF40002 400 VZ1-L070U350T 2 16 mm 12 4606 N - LC1-D8011 ATS-46D75N 2 DF3-NF40002 400 VZ1-L150U170T 25 mm2 12 4606 N 100 LC1-F115 ATS-46D88N 2 DF3-NF40002 400 VZ1-L150U170T 2 35 mm 18 4606 N 400 VZ1-L150U170T 50 mm2 18 4606 N 500 VZ1-L150U170T 2 50 mm 18 4606 N 500 VZ1-L250U100T 95 mm2 36 2 x 4606 N DF3-NF50002 500 VZ1-L250U100T 2 36 2 x 4606 N DF3-QF63002 630 VZ1-L250U100T 2 36 2 x 4606 N DF3-QF80002 800 VZ1-L325U075T 2 36 2 x 4606 N Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température ambiant plus élevée, consulter GIB. (1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter le nombre de modules. (2): obrigatoire ajoute porte-fusible. Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653. Guide Technique V9 / V9 Technical Guide Température ambiant 30 °C Ambient temperature 30 °C 4 mm 6 mm 6 mm 6 mm 6 mm 6 mm 95 mm 95 mm 95 mm Note: in case of switchboard installed in a ambient with 35 °C the values of power must be derated in 6% for ATS 46. In case of higher ambient temperature, consult BIM. (1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the number of modules. (2): compulsory add fuse carrier. Single line diagrams, according Telemecanique catalogue ART. 16653. 219 Installation de l’appareillage Switchgear Installation Blokset Ms ATS46 415 V Puissance (kW) Power (kW) 7,5 Icc coord. (kA) Icc coord. (kA) 15 7,5 11 11 15 Disjoncteur Coordination Type 2 Coordination Type 2 GV2-L20 Calibre (A) Rating (A) - Contacteur (1) Contactor (1) LC1-D2510 ATS Taille ATS Size ATS-46D17N 15 GV2-P21 - 15 GV2-L22 - LC1-D2510 LC1-D2510 15 GV2-P22 15 GV7-RS40 - 15 15 NS80H-MA 50 18,5 15 GV7-RS50 18,5 22 15 15 30 37 Service: Standard Service: Standard Température ambiant 30 °C Ambient temperature 30 °C Calibre Fusible Fuse rating 40 Inductance de ligne Line coil Raccordement section cable cross section area Nombre de modules Ventilateur Number of modules Fan 1 Fusible (2) Fuse (2) DF3-EF04001 VZ1-L015UM17T 4 mm2 9 4606 N ATS-46D17N 1 DF3-EF04001 40 VZ1-L015UM17T 2 9 4606 N ATS-46D22N 1 DF3-FF10001 100 VZ1-L030U800T 2 9 4606 N LC1-D2510 ATS-46D22N 1 DF3-FF10001 100 VZ1-L030U800T 2 9 4606 N LC1-D3210 ATS-46D32N 1 DF3-FF10001 100 VZ1-L040U600T 2 6 mm 12 4606 N LC1-D3210 ATS-46D32N 1 DF3-FF10001 100 VZ1-L040U600T 6 mm2 12 4606 N - LC1-D5011 ATS-46D38N 1 DF3-FF10001 100 VZ1-L040U600T 2 12 4606 N NS80H-MA 50 LC1-D5011 ATS-46D38N 1 DF3-FF10001 100 VZ1-L040U600T 12 4606 N NS80H-MA 50 LC1-D5011 ATS-46D47N 2 DF3-NF40002 400 VZ1-L070U350T 2 10 mm 12 4606 N 15 NS80H-MA - LC1-D6511 ATS-46D62N 2 DF3-NF40002 400 VZ1-L070U350T 16 mm2 12 4606 N 15 NS80H-MA - LC1-D8011 ATS-46D75N 2 DF3-NF40002 400 VZ1-L150U170T 2 25 mm 12 4606 N 45 15 NS100H-MA 100 LC1-F115 ATS-46D88N 2 DF3-NF40002 400 VZ1-L150U170T 35 mm2 18 4606 N 55 15 NS160H-MA 150 LC1-F115 ATS-46C11N 2 DF3-NF40002 400 VZ1-L150U170T 2 50 mm 18 4606 N 75 15 NS160H-MA 150 LC1-F150 ATS-46C14N 2 DF3-NF50002 500 VZ1-L150U170T 50 mm2 18 4606 N 90 15 NS250H-MA 220 LC1-F185 ATS-46C17N 3 DF3-NF50002 500 VZ1-L250U100T 2 95 mm 36 2 x 4606 N 110 15 NS250H-MA 220 LC1-F225 ATS-46C21N 3 DF3-NF50002 500 VZ1-L250U100T 95 mm2 36 2 x 4606 N 132 15 NS400H-MA 320 LC1-F265 ATS-46C25N 3 DF3-QF63002 630 VZ1-L250U100T 2 36 2 x 4606 N 160 15 NS400H-MA 320 LC1-F330 ATS-46C32N 3 DF3-QF80002 800 VZ1-L325U075T 2 36 2 x 4606 N 160 15 NS400H-MA 320 LC1-F330 ATS-46C32N 3 DF3-QF80002 800 VZ1-L325U075T 2 36 2 x 4606 N Circuit breaker Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température ambiant plus élevée, consulter GIB. (1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter le nombre de modules. (2): obrigatoire ajoute porte-fusible. Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653. Guide Technique V9 / V9 Technical Guide 4 mm 6 mm 6 mm 6 mm 2 6 mm 95 mm 95 mm 95 mm Note: in case of switchboard installed in a ambient with 35 °C the values of power must be derated in 6% for ATS 46. In case of higher ambient temperature, consult BIM. (1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the number of modules. (2): compulsory add fuse carrier. Single line diagrams, according Telemecanique catalogue ART. 16653. 220 Installation de l’appareillage Switchgear Installation Blokset Ms ATS46 440 V Puissance (kW) Power (kW) 7,5 Icc coord. (kA) Icc coord. (kA) 15 7,5 11 11 15 Disjoncteur Coordination Type 2 Coordination Type 2 GV2-L20 Calibre (A) Rating (A) - Contacteur (1) Contactor (1) LC1-D2510 ATS Taille ATS Size ATS-46D17N 15 GV2-P21 - 15 GV2-L22 - LC1-D2510 LC1-D2510 15 GV2-P22 15 GV7-RS40 - 15 15 NS80H-MA 50 18,5 15 GV7-RS50 18,5 22 15 15 30 37 Service: Standard Service: Standard Température ambiant 30 °C Ambient temperature 30 °C Calibre Fusible Fuse rating 40 Inductance de ligne Line coil Raccordement section cable cross section area Nombre de modules Ventilateur Number of modules Fan 1 Fusible (2) Fuse (2) DF3-EF04001 VZ1-L015UM17T 4 mm2 9 4606 N ATS-46D17N 1 DF3-EF04001 40 VZ1-L015UM17T 2 9 4606 N ATS-46D22N 1 DF3-FF10001 100 VZ1-L030U800T 2 9 4606 N LC1-D2510 ATS-46D22N 1 DF3-FF10001 100 VZ1-L030U800T 2 9 4606 N LC1-D3210 ATS-46D32N 1 DF3-FF10001 100 VZ1-L040U600T 2 6 mm 12 4606 N LC1-D3210 ATS-46D32N 1 DF3-FF10001 100 VZ1-L040U600T 6 mm2 12 4606 N - LC1-D5011 ATS-46D38N 1 DF3-FF10001 100 VZ1-L040U600T 2 12 4606 N NS80H-MA 50 LC1-D5011 ATS-46D38N 1 DF3-FF10001 100 VZ1-L040U600T 12 4606 N NS80H-MA 50 LC1-D5011 ATS-46D47N 2 DF3-NF40002 400 VZ1-L070U350T 2 10 mm 12 4606 N 15 NS80H-MA - LC1-D6511 ATS-46D62N 2 DF3-NF40002 400 VZ1-L070U350T 16 mm2 12 4606 N 15 NS80H-MA - LC1-D8011 ATS-46D75N 2 DF3-NF40002 400 VZ1-L150U170T 2 25 mm 12 4606 N 45 15 NS100H-MA 100 LC1-F115 ATS-46D88N 2 DF3-NF40002 400 VZ1-L150U170T 35 mm2 18 4606 N 55 15 NS160H-MA 150 LC1-F115 ATS-46C11N 2 DF3-NF40002 400 VZ1-L150U170T 2 50 mm 18 4606 N 75 15 NS160H-MA 150 LC1-F150 ATS-46C14N 2 DF3-NF50002 500 VZ1-L150U170T 50 mm2 18 4606 N 90 15 NS250H-MA 220 LC1-F185 ATS-46C17N 3 DF3-NF50002 500 VZ1-L250U100T 2 95 mm 36 2 x 4606 N 110 15 NS250H-MA 220 LC1-F225 ATS-46C21N 3 DF3-NF50002 500 VZ1-L250U100T 95 mm2 36 2 x 4606 N 132 15 NS400H-MA 320 LC1-F265 ATS-46C25N 3 DF3-QF63002 630 VZ1-L250U100T 2 36 2 x 4606 N 160 15 NS400H-MA 320 LC1-F330 ATS-46C32N 3 DF3-QF80002 800 VZ1-L325U075T 2 36 2 x 4606 N Circuit breaker Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température ambiant plus élevée, consulter GIB. (1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter le nombre de modules. (2): obrigatoire ajoute porte-fusible. Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653. Guide Technique V9 / V9 Technical Guide 4 mm 6 mm 6 mm 6 mm 2 6 mm 95 mm 95 mm Note: in case of switchboard installed in a ambient with 35 °C the values of power must be derated in 6% for ATS 46. In case of higher ambient temperature, consult BIM. (1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the number of modules. (2): compulsory add fuse carrier. Single line diagrams, according Telemecanique catalogue ART. 16653. 221 Installation de l’appareillage Switchgear Installation Blokset Ms 480 V Nema Puissance (kW) Power (kW) 9 Icc coord. (kA) Icc coord. (kA) 15 9 11 11 18,5 18,5 ATS46 Disjoncteur Coordination Type 2 Coordination Type 2 GV2-L20 Calibre (A) Rating (A) - Contacteur (1) Contactor (1) LC1-D2510 ATS Taille ATS Size ATS-46D17N 15 GV2-P21 - 15 GV2-L22 - LC1-D2510 LC1-D2510 15 GV2-P22 15 GV7-RS40 - 15 NS80H-MA 50 22 15 GV7-RS50 22 30 15 15 37 45 Service: Standard Service: Standard Température ambiant 30 °C Ambient temperature 30 °C Calibre Fusible Fuse rating 40 Inductance de ligne Line coil Raccordement section cable cross section area Nombre de modules Ventilateur Number of modules Fan 1 Fusible (2) Fuse (2) DF3-EF04001 VZ1-L015UM17T 4 mm2 9 4606 N ATS-46D17N 1 DF3-EF04001 40 VZ1-L015UM17T 2 9 4606 N ATS-46D22N 1 DF3-FF10001 100 VZ1-L030U800T 2 9 4606 N LC1-D2510 ATS-46D22N 1 DF3-FF10001 100 VZ1-L030U800T 2 9 4606 N LC1-D3210 ATS-46D32N 1 DF3-FF10001 100 VZ1-L040U600T 2 6 mm 12 4606 N LC1-D3210 ATS-46D32N 1 DF3-FF10001 100 VZ1-L040U600T 6 mm2 12 4606 N - LC1-D5011 ATS-46D38N 1 DF3-FF10001 100 VZ1-L040U600T 2 12 4606 N NS80H-MA 50 LC1-D5011 ATS-46D38N 1 DF3-FF10001 100 VZ1-L040U600T 12 4606 N NS80H-MA 50 LC1-D5011 ATS-46D47N 2 DF3-NF40002 400 VZ1-L070U350T 2 10 mm 12 4606 N 15 NS80H-MA - LC1-D6511 ATS-46D62N 2 DF3-NF40002 400 VZ1-L070U350T 16 mm2 12 4606 N 15 NS80H-MA - LC1-D8011 ATS-46D75N 2 DF3-NF40002 400 VZ1-L150U170T 2 25 mm 12 4606 N 55 15 NS100H-MA 100 LC1-F115 ATS-46D88N 2 DF3-NF40002 400 VZ1-L150U170T 35 mm2 18 4606 N 75 15 NS160H-MA 150 LC1-F115 ATS-46C11N 2 DF3-NF40002 400 VZ1-L150U170T 2 50 mm 18 4606 N 90 15 NS160H-MA 150 LC1-F150 ATS-46C14N 2 DF3-NF50002 500 VZ1-L150U170T 50 mm2 18 4606 N 110 15 NS250H-MA 220 LC1-F185 ATS-46C17N 3 DF3-NF50002 500 VZ1-L250U100T 2 95 mm 36 2 x 4606 N 132 15 NS250H-MA 220 LC1-F225 ATS-46C21N 3 DF3-NF50002 500 VZ1-L250U100T 95 mm2 36 2 x 4606 N 160 15 NS400H-MA 320 LC1-F265 ATS-46C25N 3 DF3-QF63002 630 VZ1-L250U100T 2 36 2 x 4606 N 220 15 NS400H-MA 320 LC1-F330 ATS-46C32N 3 DF3-QF80002 800 VZ1-L325U075T 2 36 2 x 4606 N Circuit breaker Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température ambiant plus élevée, consulter GIB. (1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter le nombre de modules. (2): obrigatoire ajoute porte-fusible. Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653. Guide Technique V9 / V9 Technical Guide 4 mm 6 mm 6 mm 6 mm 2 6 mm 95 mm 95 mm Note: in case of switchboard installed in a ambient with 35 °C the values of power must be derated in 6% for ATS 46. In case of higher ambient temperature, consult BIM. (1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the number of modules. (2): compulsory add fuse carrier. Single line diagrams, according Telemecanique catalogue ART. 16653. 222 Installation de l’appareillage Switchgear Installation Blokset Ms 3.5.1.10. ATS46 Coordination Type 1- - - - - - - - - - - - - - - - - - - Service: Sévère Coordination Type 1- - - - - - - - - - - - - - - - - - - Service: Severe ATS46 220/240 V Coordination Type 1 Coordination Type 1 Service: Sévère Service: Severe Température ambiant 30 °C Ambient temperature 30 °C Puissance (kW) Power (kW) 3 Icc coord. (kA) Icc coord. (kA) 15 Disjoncteur Circuit breaker GV2-L20 Calibre (A) Rating (A) - Contacteur (1) Contactor (1) LC1-D1810 ATS ATS ATS-46D17N Taille Size 1 Inductance de ligne Line coil VZ1-L015UM17T Raccordement section cable cross 4 mm2 Nombre de modules Number of modules 9 Ventilateur Fan 4606 N 3 15 GV2-M20 - LC1-D1810 ATS-46D17N 1 VZ1-L015UM17T 4 mm2 4 15 GV2-L22 - LC1-D2510 ATS-46D22N 1 VZ1-L030U800T 9 4606 N 6 mm 2 9 4606 N 6 mm 2 4 15 GV2-M22 - LC1-D2510 ATS-46D22N 1 VZ1-L030U800T 5,5 15 GK3-EF40 - LC1-D3210 ATS-46D32N 1 VZ1-L040U600T 9 4606 N 6 mm 2 12 4606 N 5,5 15 GV3-M63 - LC1-D3210 ATS-46D32N 1 VZ1-L040U600T 6 mm2 7,5 15 GK3-EF40 - LC1-D4011 ATS-46D38N 12 4606 N 1 VZ1-L040U600T 6 mm 2 12 4606 N ATS-46D38N 1 VZ1-L040U600T 6 mm 2 7,5 15 GV3-M63 - LC1-D4011 9 15 GK3-EF65 - LC1-D5011 12 4606 N ATS-46D47N 2 VZ1-L070U350T 10 mm 2 12 4606 N 11 15 GK3-EF65 - 15 15 GK3-EF80 - LC1-D6511 ATS-46D62N 2 VZ1-L070U350T 16 mm2 12 4606 N LC1-D8011 ATS-46D75N 2 VZ1-L150U170T 25 mm 2 12 4606 N 18,5 15 NS100N MA 22 15 NS160N MA 100 LC1-D9511 ATS-46D88N 2 VZ1-L150U170T 35 mm2 12 4606 N 150 LC1-F115 ATS-46C11N 2 VZ1-L150U170T 50 mm 2 18 4606 N 30 15 37 15 NS160N MA 150 LC1-F150 ATS-46C14N 2 VZ1-L150U170T 50 mm2 18 4606 N NS250N MA 220 LC1-F185 ATS-46C17N 3 VZ1-L250U100T 95 mm 2 36 2 x 4606 N 45 15 NS250N MA 220 LC1-F225 ATS-46C21N 3 VZ1-L250U100T 95 mm2 36 2 x 4606 N 55 15 NS400N MA 320 LC1-F265 ATS-46C25N 3 VZ1-L250U100T 95 mm 2 36 2 x 4606 N 75 15 NS400N MA 320 LC1-F330 ATS-46C32N 3 VZ1-L325U075T 95 mm 2 36 2 x 4606 N Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température ambiant plus élevée, consulter GIB. (1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter le nombre de modules. Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653. Guide Technique V9 / V9 Technical Guide Note: in case of switchboard installed in a ambient with 35 °C the values of power must be derated in 6% for ATS 46. In case of higher ambient temperature, consult BIM. (1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the number of modules Single line diagrams, according Telemecanique catalogue ART. 16653. 223 Installation de l’appareillage Switchgear Installation Blokset Ms ATS46 380/400 V Coordination Type 1 Coordination Type 1 Service: Sévère Service: Severe Température ambiant 30 °C Ambient temperature 30 °C Puissance (kW) Power (kW) 5,5 Icc coord. (kA) Icc coord. (kA) 15 Disjoncteur Circuit breaker GV2-L20 Calibre (A) Rating (A) - Contacteur (1) Contactor (1) LC1-D1810 ATS ATS ATS-46D17N Taille Size 1 Inductance de ligne Line coil VZ1-L015UM17T Raccordement section cable cross 4 mm2 Nombre de modules Number of modules 9 Ventilateur Fan 4606 N 5,5 15 GV2-M20 - LC1-D1810 ATS-46D17N 1 VZ1-L015UM17T 4 mm2 7,5 15 GV2-L22 - LC1-D2510 ATS-46D22N 1 VZ1-L030U800T 9 4606 N 6 mm 2 9 4606 N 6 mm 2 7,5 15 GV2-M22 - LC1-D2510 ATS-46D22N 1 VZ1-L030U800T 11 15 GK3-EF40 - LC1-D3210 ATS-46D32N 1 VZ1-L040U600T 9 4606 N 6 mm 2 12 4606 N 11 15 GV3-M63 - LC1-D3210 ATS-46D32N 1 VZ1-L040U600T 6 mm2 15 15 GK3-EF40 - LC1-D4011 ATS-46D38N 12 4606 N 1 VZ1-L040U600T 6 mm 2 12 4606 N ATS-46D38N 1 VZ1-L040U600T 6 mm 2 15 15 GV3-M63 - LC1-D4011 18,5 15 GK3-EF65 - LC1-D5011 12 4606 N ATS-46D47N 2 VZ1-L070U350T 10 mm 2 12 4606 N 22 15 GK3-EF65 - 30 15 GK3-EF80 - LC1-D6511 ATS-46D62N 2 VZ1-L070U350T 16 mm2 12 4606 N LC1-D8011 ATS-46D75N 2 VZ1-L150U170T 25 mm 2 12 4606 N 37 15 NS100N MA 45 15 NS160N MA 100 LC1-D9511 ATS-46D88N 2 VZ1-L150U170T 35 mm2 12 4606 N 150 LC1-F115 ATS-46C11N 2 VZ1-L150U170T 50 mm 2 18 4606 N 55 15 75 15 NS160N MA 150 LC1-F150 ATS-46C14N 2 VZ1-L150U170T 50 mm2 18 4606 N NS250N MA 220 LC1-F185 ATS-46C17N 3 VZ1-L250U100T 95 mm 2 36 2 x 4606 N 90 15 NS250N MA 220 LC1-F225 ATS-46C21N 3 VZ1-L250U100T 95 mm2 36 2 x 4606 N 110 15 NS400N MA 320 LC1-F265 ATS-46C25N 3 VZ1-L250U100T 95 mm 2 36 2 x 4606 N 132 15 NS400N MA 320 LC1-F330 ATS-46C32N 3 VZ1-L325U075T 95 mm 2 36 2 x 4606 N Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température ambiant plus élevée, consulter GIB. (1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter le nombre de modules. Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653. Guide Technique V9 / V9 Technical Guide Note: in case of switchboard installed in a ambient with 35 °C the values of power must be derated in 6% for ATS 46. In case of higher ambient temperature, consult BIM. (1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the number of modules Single line diagrams, according Telemecanique catalogue ART. 16653. 224 Installation de l’appareillage Switchgear Installation Blokset Ms ATS46 415 V Coordination Type 1 Coordination Type 1 Service: Sévère Service: Severe Température ambiant 30 °C Ambient temperature 30 °C Puissance (kW) Power (kW) 5,5 Icc coord. (kA) Icc coord. (kA) 15 Disjoncteur Circuit breaker GV2-L20 Calibre (A) Rating (A) - Contacteur (1) Contactor (1) LC1-D1810 ATS ATS ATS-46D17N Taille Size 1 Inductance de ligne Line coil VZ1-L015UM17T Raccordement section cable cross 4 mm2 Nombre de modules Number of modules 9 Ventilateur Fan 4606 N 5,5 15 GV2-M20 - LC1-D1810 ATS-46D17N 1 VZ1-L015UM17T 4 mm2 7,5 15 GV2-L22 - LC1-D2510 ATS-46D22N 1 VZ1-L030U800T 9 4606 N 6 mm 2 9 4606 N 6 mm 2 7,5 15 GV2-M22 - LC1-D2510 ATS-46D22N 1 VZ1-L030U800T 11 15 GK3-EF40 - LC1-D3210 ATS-46D32N 1 VZ1-L040U600T 9 4606 N 6 mm 2 12 4606 N 11 15 GV3-M63 - LC1-D3210 ATS-46D32N 1 VZ1-L040U600T 6 mm2 15 15 GK3-EF40 - LC1-D4011 ATS-46D38N 12 4606 N 1 VZ1-L040U600T 6 mm 2 12 4606 N ATS-46D38N 1 VZ1-L040U600T 6 mm 2 15 15 GV3-M63 - LC1-D4011 18,5 15 GK3-EF65 - LC1-D5011 12 4606 N ATS-46D47N 2 VZ1-L070U350T 10 mm 2 12 4606 N 22 15 GK3-EF65 - 30 15 GK3-EF80 - LC1-D6511 ATS-46D62N 2 VZ1-L070U350T 16 mm2 12 4606 N LC1-D8011 ATS-46D75N 2 VZ1-L150U170T 25 mm 2 12 4606 N 37 15 NS100N MA 45 15 NS160N MA 100 LC1-D9511 ATS-46D88N 2 VZ1-L150U170T 35 mm2 12 4606 N 150 LC1-F115 ATS-46C11N 2 VZ1-L150U170T 50 mm 2 18 4606 N 55 15 75 15 NS160N MA 150 LC1-F150 ATS-46C14N 2 VZ1-L150U170T 50 mm2 18 4606 N NS250N MA 220 LC1-F185 ATS-46C17N 3 VZ1-L250U100T 95 mm 2 36 2 x 4606 N 90 15 NS250N MA 220 LC1-F225 ATS-46C21N 3 VZ1-L250U100T 95 mm2 36 2 x 4606 N 110 15 NS400N MA 320 LC1-F265 ATS-46C25N 3 VZ1-L250U100T 95 mm 2 36 2 x 4606 N 132 15 NS400N MA 320 LC1-F330 ATS-46C32N 3 VZ1-L325U075T 95 mm 2 36 2 x 4606 N Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température ambiant plus élevée, consulter GIB. (1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter le nombre de modules. Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653. Guide Technique V9 / V9 Technical Guide Note: in case of switchboard installed in a ambient with 35 °C the values of power must be derated in 6% for ATS 46. In case of higher ambient temperature, consult BIM. (1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the number of modules Single line diagrams, according Telemecanique catalogue ART. 16653. 225 Installation de l’appareillage Switchgear Installation Blokset Ms ATS46 440 V Coordination Type 1 Coordination Type 1 Service: Sévère Service: Severe Température ambiant 30 °C Ambient temperature 30 °C Puissance (kW) Power (kW) 5,5 Icc coord. (kA) Icc coord. (kA) 15 Disjoncteur Circuit breaker GV2-L20 Calibre (A) Rating (A) - Contacteur (1) Contactor (1) LC1-D1810 ATS ATS ATS-46D17N Taille Size 1 Inductance de ligne Line coil VZ1-L015UM17T Raccordement section cable cross 4 mm2 Nombre de modules Number of modules 9 Ventilateur Fan 4606 N 5,5 15 GV2-M20 - LC1-D1810 ATS-46D17N 1 VZ1-L015UM17T 4 mm2 7,5 15 GV2-L22 - LC1-D2510 ATS-46D22N 1 VZ1-L030U800T 9 4606 N 6 mm 2 9 4606 N 6 mm 2 7,5 15 GV2-M22 - LC1-D2510 ATS-46D22N 1 VZ1-L030U800T 11 15 GK3-EF40 - LC1-D3210 ATS-46D32N 1 VZ1-L040U600T 9 4606 N 6 mm 2 12 4606 N 11 15 GV3-M63 - LC1-D3210 ATS-46D32N 1 VZ1-L040U600T 6 mm2 15 15 GK3-EF40 - LC1-D4011 ATS-46D38N 12 4606 N 1 VZ1-L040U600T 6 mm 2 12 4606 N ATS-46D38N 1 VZ1-L040U600T 6 mm 2 15 15 GV3-M63 - LC1-D4011 18,5 15 GK3-EF65 - LC1-D5011 12 4606 N ATS-46D47N 2 VZ1-L070U350T 10 mm 2 12 4606 N 22 15 GK3-EF65 - 30 15 GK3-EF80 - LC1-D6511 ATS-46D62N 2 VZ1-L070U350T 16 mm2 12 4606 N LC1-D8011 ATS-46D75N 2 VZ1-L150U170T 25 mm 2 12 4606 N 37 15 NS100N MA 45 15 NS160N MA 100 LC1-D9511 ATS-46D88N 2 VZ1-L150U170T 35 mm2 12 4606 N 150 LC1-F115 ATS-46C11N 2 VZ1-L150U170T 50 mm 2 18 4606 N 55 15 75 15 NS160N MA 150 LC1-F150 ATS-46C14N 2 VZ1-L150U170T 50 mm2 18 4606 N NS250N MA 220 LC1-F185 ATS-46C17N 3 VZ1-L250U100T 95 mm 2 36 2 x 4606 N 90 15 NS250N MA 220 LC1-F225 ATS-46C21N 3 VZ1-L250U100T 95 mm2 36 2 x 4606 N 110 15 NS400N MA 320 LC1-F265 ATS-46C25N 3 VZ1-L250U100T 95 mm 2 36 2 x 4606 N 132 15 NS400N MA 320 LC1-F330 ATS-46C32N 3 VZ1-L325U075T 95 mm 2 36 2 x 4606 N Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température ambiant plus élevée, consulter GIB. (1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter le nombre de modules. Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653. Guide Technique V9 / V9 Technical Guide Note: in case of switchboard installed in a ambient with 35 °C the values of power must be derated in 6% for ATS 46. In case of higher ambient temperature, consult BIM. (1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the number of modules Single line diagrams, according Telemecanique catalogue ART. 16653. 226 Installation de l’appareillage Switchgear Installation Blokset Ms ATS46 500 V Coordination Type 1 Coordination Type 1 Service: Sévère Service: Severe Température ambiant 30 °C Ambient temperature 30 °C Puissance (kW) Power (kW) 7,5 Icc coord. (kA) Icc coord. (kA) 15 Disjoncteur Circuit breaker GV2-L20 Calibre (A) Rating (A) - Contacteur (1) Contactor (1) LC1-D1810 ATS ATS ATS-46D17N Taille Size 1 Inductance de ligne Line coil VZ1-L015UM17T Raccordement section cable cross 4 mm2 Nombre de modules Number of modules 9 Ventilateur Fan 4606 N 7,5 15 GV2-M20 - LC1-D1810 ATS-46D17N 1 VZ1-L015UM17T 4 mm2 9 15 GV2-L22 - LC1-D2510 ATS-46D22N 1 VZ1-L030U800T 9 4606 N 6 mm 2 9 4606 N 6 mm 2 9 15 GV2-M22 - LC1-D2510 ATS-46D22N 1 VZ1-L030U800T 11 15 GK3-EF40 - LC1-D3210 ATS-46D32N 1 VZ1-L040U600T 9 4606 N 6 mm 2 12 4606 N 11 15 GV3-M63 - LC1-D3210 ATS-46D32N 1 VZ1-L040U600T 6 mm2 18,5 15 GK3-EF40 - LC1-D4011 ATS-46D38N 12 4606 N 1 VZ1-L040U600T 6 mm 2 12 4606 N ATS-46D38N 1 VZ1-L040U600T 6 mm 2 18,5 15 GV3-M63 - LC1-D4011 22 15 GK3-EF65 - LC1-D5011 12 4606 N ATS-46D47N 2 VZ1-L070U350T 10 mm 2 12 4606 N 30 15 GK3-EF65 - LC1-D6511 37 15 GK3-EF80 - LC1-D8011 ATS-46D62N 2 VZ1-L070U350T 16 mm2 12 4606 N ATS-46D75N 2 VZ1-L150U170T 25 mm 2 12 4606 N 45 15 NS100N MA 100 55 15 NS160N MA 150 LC1-D9511 ATS-46D88N 2 VZ1-L150U170T 35 mm2 12 4606 N LC1-F115 ATS-46C11N 2 VZ1-L150U170T 50 mm 2 18 4606 N 75 15 NS160N MA 90 15 NS250N MA 150 LC1-F150 ATS-46C14N 2 VZ1-L150U170T 50 mm2 18 4606 N 220 LC1-F185 ATS-46C17N 3 VZ1-L250U100T 95 mm 2 36 2 x 4606 N 110 15 NS250N MA 220 LC1-F225 ATS-46C21N 3 VZ1-L250U100T 95 mm2 36 2 x 4606 N 15 NS400N MA 320 LC1-F265 ATS-46C25N 3 VZ1-L250U100T 95 mm 2 132 160 36 2 x 4606 N 15 NS400N MA 320 LC1-F330 ATS-46C32N 3 VZ1-L325U075T 95 mm 2 36 2 x 4606 N Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température ambiant plus élevée, consulter GIB. (1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter le nombre de modules. Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653. Guide Technique V9 / V9 Technical Guide Note: in case of switchboard installed in a ambient with 35 °C the values of power must be derated in 6% for ATS 46. In case of higher ambient temperature, consult BIM. (1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the number of modules Single line diagrams, according Telemecanique catalogue ART. 16653. 227 Installation de l’appareillage Switchgear Installation Blokset Ms 3.5.1.11. ATS46 220/240 V Puissance (kW) Power (kW) 3 Icc coord. (kA) Icc coord. (kA) 15 3 4 Coordination Type 2- - - - - - - - - - - - - - - - - - - Service: Sévère Coordination Type 2- - - - - - - - - - - - - - - - - - - Service: Severe ATS46 Disjoncteur Coordination Type 2 Coordination Type 2 GV2-L20 Calibre (A) Rating (A) - Contacteur (1) Contactor (1) LC1-D2510 ATS Taille ATS Size ATS-46D17N 15 GV2-P21 - 15 GV2-L22 - LC1-D2510 LC1-D2510 4 15 GV2-P22 - 5,5 15 GV7-RS40 - LC1-D2510 LC1-D3210 5,5 15 NS80H-MA 50 LC1-D3210 7,5 15 GV7-RS50 - 7,5 15 9 15 NS80H-MA NS80H-MA 11 15 15 15 NS80H-MA NS80H-MA 18,5 22 15 15 30 37 Service: Sévère Service: Severe Température ambiant 30 °C Ambient temperature 30 °C Calibre Fusible Fuse rating 40 Inductance de ligne Line coil Raccordement section cable cross section area Nombre de modules Ventilateur Number of modules Fan 1 Fusible (2) Fuse (2) DF3-EF04001 VZ1-L015UM17T 4 mm2 9 4606 N ATS-46D17N 1 DF3-EF04001 40 VZ1-L015UM17T 2 9 4606 N ATS-46D22N 1 DF3-FF10001 100 VZ1-L030U800T 2 9 4606 N ATS-46D22N 1 DF3-FF10001 100 VZ1-L030U800T 2 9 4606 N ATS-46D32N 1 DF3-FF10001 100 VZ1-L040U600T 2 6 mm 12 4606 N ATS-46D32N 1 DF3-FF10001 100 VZ1-L040U600T 6 mm2 12 4606 N LC1-D5011 ATS-46D38N 1 DF3-FF10001 100 VZ1-L040U600T 2 12 4606 N 50 LC1-D5011 ATS-46D38N 1 DF3-FF10001 100 VZ1-L040U600T 12 4606 N 50 LC1-D5011 ATS-46D47N 2 DF3-NF40002 400 VZ1-L070U350T 2 10 mm 12 4606 N - LC1-D6511 ATS-46D62N 2 DF3-NF40002 400 VZ1-L070U350T 16 mm2 12 4606 N - LC1-D8011 ATS-46D75N 2 DF3-NF40002 400 VZ1-L150U170T 2 25 mm 12 4606 N NS100H-MA 100 LC1-F115 ATS-46D88N 2 DF3-NF40002 400 VZ1-L150U170T 35 mm2 18 4606 N NS160H-MA 150 LC1-F115 ATS-46C11N 2 DF3-NF40002 400 VZ1-L150U170T 2 50 mm 18 4606 N 15 NS160H-MA 150 LC1-F150 ATS-46C14N 2 DF3-NF50002 500 VZ1-L150U170T 50 mm2 18 4606 N 15 NS250H-MA 220 LC1-F185 ATS-46C17N 3 DF3-NF50002 500 VZ1-L250U100T 2 95 mm 36 2 x 4606 N 45 15 NS250H-MA 220 LC1-F225 ATS-46C21N 3 DF3-NF50002 500 VZ1-L250U100T 95 mm2 36 2 x 4606 N 55 15 NS400H-MA 320 LC1-F265 ATS-46C25N 3 DF3-QF63002 630 VZ1-L250U100T 2 36 2 x 4606 N 75 15 NS400H-MA 320 LC1-F330 ATS-46C32N 3 DF3-QF80002 800 VZ1-L325U075T 2 36 2 x 4606 N Circuit breaker Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température ambiant plus élevée, consulter GIB. (1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter le nombre de modules. (2): obrigatoire ajoute porte-fusible. Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653. Guide Technique V9 / V9 Technical Guide 4 mm 6 mm 6 mm 6 mm 2 6 mm 95 mm 95 mm Note: in case of switchboard installed in a ambient with 35 °C the values of power must be derated in 6% for ATS 46. In case of higher ambient temperature, consult BIM. (1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the number of modules. (2): compulsory add fuse carrier. Single line diagrams, according Telemecanique catalogue ART. 16653. 228 Installation de l’appareillage Switchgear Installation Blokset Ms 380/400 V Puissance (kW) Power (kW) 5,5 Icc coord. (kA) Icc coord. (kA) 15 5,5 ATS46 Disjoncteur Coordination Type 2 Coordination Type 2 GV2-L20 Calibre (A) Rating (A) - Contacteur (1) Contactor (1) LC1-D2510 15 GV2-P21 - 7,5 15 GV2-L22 7,5 15 GV2-P22 11 15 11 15 15 15 Service: Sévère Service: Severe ATS Taille ATS Size ATS-46D17N LC1-D2510 - GV7-RS40 NS80H-MA 15 GV7-RS50 15 NS80H-MA 18,5 15 NS80H-MA 22 15 NS80H-MA 30 15 NS80H-MA 37 15 NS100H-MA 45 15 NS160H-MA 150 LC1-F115 ATS-46C11N 2 DF3-NF40002 55 15 NS160H-MA 150 LC1-F150 ATS-46C14N 2 DF3-NF50002 75 15 NS250H-MA 220 LC1-F185 ATS-46C17N 3 DF3-NF50002 90 15 NS250H-MA 220 LC1-F225 ATS-46C21N 3 110 15 NS400H-MA 320 LC1-F265 ATS-46C25N 3 132 15 NS400H-MA 320 LC1-F330 ATS-46C32N 3 Circuit breaker Calibre Fusible Fuse rating 40 Inductance de ligne Line coil Raccordement section cable cross section area Nombre de modules Ventilateur Number of modules Fan 1 Fusible (2) Fuse (2) DF3-EF04001 VZ1-L015UM17T 4 mm2 9 4606 N ATS-46D17N 1 DF3-EF04001 40 VZ1-L015UM17T 2 9 4606 N LC1-D2510 ATS-46D22N 1 DF3-FF10001 100 VZ1-L030U800T 2 9 4606 N LC1-D2510 ATS-46D22N 1 DF3-FF10001 100 VZ1-L030U800T 2 9 4606 N - LC1-D3210 ATS-46D32N 1 DF3-FF10001 100 VZ1-L040U600T 2 12 4606 N 50 LC1-D3210 ATS-46D32N 1 DF3-FF10001 100 VZ1-L040U600T 2 12 4606 N - LC1-D5011 ATS-46D38N 1 DF3-FF10001 100 VZ1-L040U600T 2 12 4606 N 50 LC1-D5011 ATS-46D38N 1 DF3-FF10001 100 VZ1-L040U600T 2 6 mm 12 4606 N 50 LC1-D5011 ATS-46D47N 2 DF3-NF40002 400 VZ1-L070U350T 10 mm2 12 4606 N - LC1-D6511 ATS-46D62N 2 DF3-NF40002 400 VZ1-L070U350T 2 16 mm 12 4606 N - LC1-D8011 ATS-46D75N 2 DF3-NF40002 400 VZ1-L150U170T 25 mm2 12 4606 N 100 LC1-F115 ATS-46D88N 2 DF3-NF40002 400 VZ1-L150U170T 2 35 mm 18 4606 N 400 VZ1-L150U170T 50 mm2 18 4606 N 500 VZ1-L150U170T 2 50 mm 18 4606 N 500 VZ1-L250U100T 95 mm2 36 2 x 4606 N DF3-NF50002 500 VZ1-L250U100T 2 36 2 x 4606 N DF3-QF63002 630 VZ1-L250U100T 2 36 2 x 4606 N DF3-QF80002 800 VZ1-L325U075T 2 36 2 x 4606 N Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température ambiant plus élevée, consulter GIB. (1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter le nombre de modules. (2): obrigatoire ajoute porte-fusible. Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653. Guide Technique V9 / V9 Technical Guide Température ambiant 30 °C Ambient temperature 30 °C 4 mm 6 mm 6 mm 6 mm 6 mm 6 mm 95 mm 95 mm 95 mm Note: in case of switchboard installed in a ambient with 35 °C the values of power must be derated in 6% for ATS 46. In case of higher ambient temperature, consult BIM. (1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the number of modules. (2): compulsory add fuse carrier. Single line diagrams, according Telemecanique catalogue ART. 16653. 229 Installation de l’appareillage Switchgear Installation Blokset Ms ATS46 415 V Puissance (kW) Power (kW) 5,5 Icc coord. (kA) Icc coord. (kA) 15 5,5 7,5 Disjoncteur Coordination Type 2 Coordination Type 2 GV2-L20 Calibre (A) Rating (A) - Contacteur (1) Contactor (1) LC1-D2510 ATS Taille ATS Size ATS-46D17N 15 GV2-P21 - 15 GV2-L22 - LC1-D2510 LC1-D2510 7,5 15 GV2-P22 - 11 15 GV7-RS40 - LC1-D2510 LC1-D3210 11 15 NS80H-MA 50 15 15 GV7-RS50 15 18,5 15 15 22 30 15 15 37 45 Service: Sévère Service: Severe Température ambiant 30 °C Ambient temperature 30 °C Calibre Fusible Fuse rating 40 Inductance de ligne Line coil Raccordement section cable cross section area Nombre de modules Ventilateur Number of modules Fan 1 Fusible (2) Fuse (2) DF3-EF04001 VZ1-L015UM17T 4 mm2 9 4606 N ATS-46D17N 1 DF3-EF04001 40 VZ1-L015UM17T 2 9 4606 N ATS-46D22N 1 DF3-FF10001 100 VZ1-L030U800T 2 9 4606 N ATS-46D22N 1 DF3-FF10001 100 VZ1-L030U800T 2 9 4606 N ATS-46D32N 1 DF3-FF10001 100 VZ1-L040U600T 2 6 mm 12 4606 N LC1-D3210 ATS-46D32N 1 DF3-FF10001 100 VZ1-L040U600T 6 mm2 12 4606 N - LC1-D5011 ATS-46D38N 1 DF3-FF10001 100 VZ1-L040U600T 2 12 4606 N NS80H-MA 50 LC1-D5011 ATS-46D38N 1 DF3-FF10001 100 VZ1-L040U600T 12 4606 N NS80H-MA 50 LC1-D5011 ATS-46D47N 2 DF3-NF40002 400 VZ1-L070U350T 2 10 mm 12 4606 N NS80H-MA - LC1-D6511 ATS-46D62N 2 DF3-NF40002 400 VZ1-L070U350T 16 mm2 12 4606 N NS80H-MA - LC1-D8011 ATS-46D75N 2 DF3-NF40002 400 VZ1-L150U170T 2 25 mm 12 4606 N 15 NS100H-MA 100 LC1-F115 ATS-46D88N 2 DF3-NF40002 400 VZ1-L150U170T 35 mm2 18 4606 N 15 NS160H-MA 150 LC1-F115 ATS-46C11N 2 DF3-NF40002 400 VZ1-L150U170T 2 50 mm 18 4606 N 55 15 NS160H-MA 150 LC1-F150 ATS-46C14N 2 DF3-NF50002 500 VZ1-L150U170T 50 mm2 18 4606 N 75 15 NS250H-MA 220 LC1-F185 ATS-46C17N 3 DF3-NF50002 500 VZ1-L250U100T 2 95 mm 36 2 x 4606 N 90 15 NS250H-MA 220 LC1-F225 ATS-46C21N 3 DF3-NF50002 500 VZ1-L250U100T 95 mm2 36 2 x 4606 N 110 15 NS400H-MA 320 LC1-F265 ATS-46C25N 3 DF3-QF63002 630 VZ1-L250U100T 2 36 2 x 4606 N 132 15 NS400H-MA 320 LC1-F330 ATS-46C32N 3 DF3-QF80002 800 VZ1-L325U075T 2 36 2 x 4606 N Circuit breaker Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température ambiant plus élevée, consulter GIB. (1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter le nombre de modules. (2): obrigatoire ajoute porte-fusible. Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653. Guide Technique V9 / V9 Technical Guide 4 mm 6 mm 6 mm 6 mm 2 6 mm 95 mm 95 mm Note: in case of switchboard installed in a ambient with 35 °C the values of power must be derated in 6% for ATS 46. In case of higher ambient temperature, consult BIM. (1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the number of modules. (2): compulsory add fuse carrier. Single line diagrams, according Telemecanique catalogue ART. 16653. 230 Installation de l’appareillage Switchgear Installation Blokset Ms ATS46 440 V Puissance (kW) Power (kW) 5,5 Icc coord. (kA) Icc coord. (kA) 15 5,5 7,5 Disjoncteur Coordination Type 2 Coordination Type 2 GV2-L20 Calibre (A) Rating (A) - Contacteur (1) Contactor (1) LC1-D2510 ATS Taille ATS Size ATS-46D17N 15 GV2-P21 - 15 GV2-L22 - LC1-D2510 LC1-D2510 7,5 15 GV2-P22 - 11 15 GV7-RS40 - LC1-D2510 LC1-D3210 11 15 NS80H-MA 50 15 15 GV7-RS50 15 18,5 15 15 22 30 15 15 37 45 Service: Sévère Service: Severe Température ambiant 30 °C Ambient temperature 30 °C Calibre Fusible Fuse rating 40 Inductance de ligne Line coil Raccordement section cable cross section area Nombre de modules Ventilateur Number of modules Fan 1 Fusible (2) Fuse (2) DF3-EF04001 VZ1-L015UM17T 4 mm2 9 4606 N ATS-46D17N 1 DF3-EF04001 40 VZ1-L015UM17T 2 9 4606 N ATS-46D22N 1 DF3-FF10001 100 VZ1-L030U800T 2 9 4606 N ATS-46D22N 1 DF3-FF10001 100 VZ1-L030U800T 2 9 4606 N ATS-46D32N 1 DF3-FF10001 100 VZ1-L040U600T 2 6 mm 12 4606 N LC1-D3210 ATS-46D32N 1 DF3-FF10001 100 VZ1-L040U600T 6 mm2 12 4606 N - LC1-D5011 ATS-46D38N 1 DF3-FF10001 100 VZ1-L040U600T 2 12 4606 N NS80H-MA 50 LC1-D5011 ATS-46D38N 1 DF3-FF10001 100 VZ1-L040U600T 12 4606 N NS80H-MA 50 LC1-D5011 ATS-46D47N 2 DF3-NF40002 400 VZ1-L070U350T 2 10 mm 12 4606 N NS80H-MA - LC1-D6511 ATS-46D62N 2 DF3-NF40002 400 VZ1-L070U350T 16 mm2 12 4606 N NS80H-MA - LC1-D8011 ATS-46D75N 2 DF3-NF40002 400 VZ1-L150U170T 2 25 mm 12 4606 N 15 NS100H-MA 100 LC1-F115 ATS-46D88N 2 DF3-NF40002 400 VZ1-L150U170T 35 mm2 18 4606 N 15 NS160H-MA 150 LC1-F115 ATS-46C11N 2 DF3-NF40002 400 VZ1-L150U170T 2 50 mm 18 4606 N 55 15 NS160H-MA 150 LC1-F150 ATS-46C14N 2 DF3-NF50002 500 VZ1-L150U170T 50 mm2 18 4606 N 75 15 NS250H-MA 220 LC1-F185 ATS-46C17N 3 DF3-NF50002 500 VZ1-L250U100T 2 95 mm 36 2 x 4606 N 90 15 NS250H-MA 220 LC1-F225 ATS-46C21N 3 DF3-NF50002 500 VZ1-L250U100T 95 mm2 36 2 x 4606 N 110 15 NS400H-MA 320 LC1-F265 ATS-46C25N 3 DF3-QF63002 630 VZ1-L250U100T 2 36 2 x 4606 N 132 15 NS400H-MA 320 LC1-F330 ATS-46C32N 3 DF3-QF80002 800 VZ1-L325U075T 2 36 2 x 4606 N Circuit breaker Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température ambiant plus élevée, consulter GIB. (1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter le nombre de modules. (2): obrigatoire ajoute porte-fusible. Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653. Guide Technique V9 / V9 Technical Guide 4 mm 6 mm 6 mm 6 mm 2 6 mm 95 mm 95 mm Note: in case of switchboard installed in a ambient with 35 °C the values of power must be derated in 6% for ATS 46. In case of higher ambient temperature, consult BIM. (1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the number of modules. (2): compulsory add fuse carrier. Single line diagrams, according Telemecanique catalogue ART. 16653. 231 Installation de l’appareillage Switchgear Installation Blokset Ms 480 V Nema Puissance (kW) Power (kW) 7,5 Icc coord. (kA) Icc coord. (kA) 15 7,5 9 9 11 11 ATS46 Disjoncteur Coordination Type 2 Coordination Type 2 GV2-L20 Calibre (A) Rating (A) - Contacteur (1) Contactor (1) LC1-D2510 ATS Taille ATS Size ATS-46D17N 15 GV2-P21 - 15 GV2-L22 - LC1-D2510 LC1-D2510 15 GV2-P22 - 15 GV7-RS40 - LC1-D2510 LC1-D3210 15 NS80H-MA 50 18,5 15 GV7-RS50 18,5 22 15 15 30 37 Service: Sévère Service: Severe Température ambiant 30 °C Ambient temperature 30 °C Calibre Fusible Fuse rating 40 Inductance de ligne Line coil Raccordement section cable cross section area Nombre de modules Ventilateur Number of modules Fan 1 Fusible (2) Fuse (2) DF3-EF04001 VZ1-L015UM17T 4 mm2 9 4606 N ATS-46D17N 1 DF3-EF04001 40 VZ1-L015UM17T 2 9 4606 N ATS-46D22N 1 DF3-FF10001 100 VZ1-L030U800T 2 9 4606 N ATS-46D22N 1 DF3-FF10001 100 VZ1-L030U800T 2 9 4606 N ATS-46D32N 1 DF3-FF10001 100 VZ1-L040U600T 2 6 mm 12 4606 N LC1-D3210 ATS-46D32N 1 DF3-FF10001 100 VZ1-L040U600T 6 mm2 12 4606 N - LC1-D5011 ATS-46D38N 1 DF3-FF10001 100 VZ1-L040U600T 2 12 4606 N NS80H-MA 50 LC1-D5011 ATS-46D38N 1 DF3-FF10001 100 VZ1-L040U600T 12 4606 N NS80H-MA 50 LC1-D5011 ATS-46D47N 2 DF3-NF40002 400 VZ1-L070U350T 2 10 mm 12 4606 N 15 NS80H-MA - LC1-D6511 ATS-46D62N 2 DF3-NF40002 400 VZ1-L070U350T 16 mm2 12 4606 N 15 NS80H-MA - LC1-D8011 ATS-46D75N 2 DF3-NF40002 400 VZ1-L150U170T 2 25 mm 12 4606 N 45 15 NS100H-MA 100 LC1-F115 ATS-46D88N 2 DF3-NF40002 400 VZ1-L150U170T 35 mm2 18 4606 N 55 15 NS160H-MA 150 LC1-F115 ATS-46C11N 2 DF3-NF40002 400 VZ1-L150U170T 2 50 mm 18 4606 N 75 15 NS160H-MA 150 LC1-F150 ATS-46C14N 2 DF3-NF50002 500 VZ1-L150U170T 50 mm2 18 4606 N 90 15 NS250H-MA 220 LC1-F185 ATS-46C17N 3 DF3-NF50002 500 VZ1-L250U100T 2 95 mm 36 2 x 4606 N 110 15 NS250H-MA 220 LC1-F225 ATS-46C21N 3 DF3-NF50002 500 VZ1-L250U100T 95 mm2 36 2 x 4606 N 132 15 NS400H-MA 320 LC1-F265 ATS-46C25N 3 DF3-QF63002 630 VZ1-L250U100T 2 36 2 x 4606 N 160 15 NS400H-MA 320 LC1-F330 ATS-46C32N 3 DF3-QF80002 800 VZ1-L325U075T 2 36 2 x 4606 N Circuit breaker Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température ambiant plus élevée, consulter GIB. (1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter le nombre de modules. (2): obrigatoire ajoute porte-fusible. Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653. Guide Technique V9 / V9 Technical Guide 4 mm 6 mm 6 mm 6 mm 2 6 mm 95 mm 95 mm Note: in case of switchboard installed in a ambient with 35 °C the values of power must be derated in 6% for ATS 46. In case of higher ambient temperature, consult BIM. (1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the number of modules. (2): compulsory add fuse carrier. Single line diagrams, according Telemecanique catalogue ART. 16653. 232 Installation de l’appareillage Switchgear Installation Blokset Ms 3.5.2. IP pour démarreurs et variateurs de vitesse IP for soft starters and variable speed drivers Installer accessoires AIRTECHNIC suivant les références indiquée ci-dessous Install AIRTECHNIC accessories according references indicated on table below Degré de protection Protection degree IP 20 Grille + Ecran + Supports Finger guards + Screen + Brackets LZ 30P + LZ 40N + LZ 40-1 + LZ 120 Degré de protection Protection degree IP 31 / 42 Filtre métallique + Ecran + Supports Metalic filter + Screen + Brackets LZ 60 + LZ 40N + LZ 40-1 + LZ 120 Ventilateur Fan Debit (m3/h) Air flow rate (m3/h) Degré de protection Protection degree 4606 N 180 IP 20/31/42 Guide Technique V9 / V9 Technical Guide 233 Sommaire du chapitre Chapter contents 3.6. Câbles et barres rigides Cables and rigid bar 3.6.1. Câbles pour DOL démarreus (Integral, GV et Compact NS) ............... 235 Cables for DOL starting (Integral, GV and Compact NS) 3.6.2. Câbles pour REV démarreus (Integral, GV et NS) ................................ 237 Cables for REV starting (Integral, GV and NS) 3.6.3. Câbles pour Y/D démarreus (Integral, GV et NS) ................................. 239 Cables for Y/D starting (Integral, GV and NS) Guide Technique V9 / V9 Technical Guide 234 Installation de l’appareillage Switchgear Installation 3.6. Câbles et barres rigides cables and rigid bar Connexions internes des départs-moteurs avec barres rigides ou câbles (souple multi brins 105° C). 3.6.1. Internal connections of starting motors with rigid bars or cables (105 °C). Câbles pour DOL démarreus (Integral, GV et Compact NS) cables for DOL starting (Integral, GV and Compact NS) DISJUNCTEURS CONTACTEURS Integral 18 (LD1-LB030) RELAIS THERMIQUE THERMAL RELAYS LB1-LB03P CIRCUIT BREAKERS CONTACTORS Integral 32 (LD1-LC030 & LD4-LC130) LB1-LC03M 6 mm LB1-LD03M 16 mm2 Integral 63 (LD1-LD030 & LD4-LD130) GV2 LC1-D09/12 6 mm2 LC1-D32 6 mm LC1-D40 10 mm2 2,5 mm 16 mm2 2 2 2,5 2 mm2 2,5 mm2 4 mm 2 4 mm2 6 mm 2 6 mm2 10 mm2 10 mm2 mm2 2.5 mm2 2.5 LC1-D32 6 mm LC1-D38/40 10 mm2 10 mm2 10 mm2 LC1-D50/65 16 mm 2 16 mm2 16 mm2 25 mm 2 25 mm2 25 mm2 LC1-D95 25 mm 2 25 mm2 25 mm2 LC1-D115/F115 35 mm2 35 mm2 35 mm2 LC1-D150/F150 2 2 2 50 mm 6 mm2 6 mm2 50 mm 50 mm2 LC1-F185 2 x 35 mm LC1-F225 2 x 35 mm2 2 x 35 mm2 2 x 35 mm2 LC1-F265 2 mm2 2 x 35 mm2 LC1-D09/12 2 x 35 mm LC1-D80 LR2-D1/LRD0/1 LR2-D1/LRD0/2 LR2-D1/LRD1/2 LR2-D3/LRD2/3 LR2-D3/LRD2/3/33 LR2-D3/LRD33 LR2-D3/LRD33 LR9-F5 LC1-D115/F115 LR9-D5/F5 LC1-D18 LC1- D25 LC1-D32 LC1-D38/40 LC1-D50/65 LC1-D80 Guide Technique V9 / V9 Technical Guide 6 mm2 4 mm LC1-D80 NS80 CÂBLES DE SORTIE OUTGOING cables 2 2 LC1-K06/09/12 CÂBLES INTERMÉDIAIRES INTERMEDIATE cables 6 mm2 2,5 mm LC1-D18/25 GV7 CÂBLES DÉNTREE INCOME cables 2,5 mm2 2 2 x 35 mm 2 x 35 2,5 mm2 2 2 x 35 mm2 2,5 mm2 4 mm2 4 mm2 4 mm2 6 mm2 6 mm2 6 mm2 6 mm2 6 mm2 6 mm2 10 mm2 10 mm2 10 mm2 16 mm2 16 mm2 16 mm2 25 mm2 25 mm2 25 mm2 25 mm2 25 mm2 25 mm2 25 mm2 25 mm2 25 mm2 235 Installation de l’appareillage Switchgear Installation DISJUNCTEURS CONTACTEURS CIRCUIT BREAKERS CONTACTORS NS100 LC1-D09/12 LC1-D18 LC1-D25/32 LC1-D38 NS400 NS 630 CÂBLES DE SORTIE OUTGOING cables 2,5 mm2 2,5 mm2 2,5 mm2 4 mm2 4 mm2 4 mm2 6 mm2 6 mm2 6 mm2 10 mm2 10 mm2 10 mm2 mm2 2 10 mm2 10 LC1-D50/65 LR2-D3/ LR9-D5 LRD-33 16 mm2 16 mm2 16 mm2 16 mm2 16 mm2 16 mm2 2 2 25 mm2 16 mm2 16 mm2 16 mm2 2 2 25 mm2 10 mm LC1-D65 LR2-D3/ LRD-33 LR9-D5 LC1-D80 LR9-D5 25 mm LC1-D95 25 mm2 25 mm2 25 mm2 LC1-D95 LR2-D3/ LRD-33 LR9-D5 25 mm2 25 mm2 25 mm2 LC1-D115/F115 LR9-D5/F5 35 mm 2 2 35 mm2 LC1-D115 LRD-4 35 mm 2 mm2 35 mm2 LC1-D115 LRD-4 35 mm2 35 mm2 35 mm2 LC1-D115/F115 LR9-D5/F5 35 mm 2 mm2 35 mm2 LC1-D150/F150 LR9-D5/F5 50 mm 2 2 50 mm2 LC1-F185 LR9-D5 2 x 35 mm2 2 x 35 mm2 2 x 35 mm2 LC1-F185 LR9-F5 2 x 35 mm2 2 x 35 mm2 2 x 35 mm2 LC1-F225 LR9-F5 2 x 35 mm 2 2 x 35 mm2 2 x 35 mm2 LC1-F265 LR9-F5 2 x 50 mm 2 2 x 50 mm2 2 x 50 mm2 2 x 50 mm2 2 x 50 mm2 2 x 50 mm2 2 x 50 mm 2 2 x 50 mm2 2 x 50 mm 2 2 x 50 mm2 2 2 x 50 mm2 3 x 50 25 mm 25 mm 25 mm 35 mm 35 35 50 mm LC1-F330 LR9-F5 LC1-F265 LR9-F5/F7 LC1-F330 LR9-F7 LC1-F400/500 LR9-F7 2 x 50 mm * 2 x 50 mm LC1-F400 LR9-F7 3 x 50 mm2 * 2 x 95 mm2 ** LC1-F500 LR9-F7 3 x 50 LC1-F630 LR9-F7 * * Pour Mf: barre rigide, suivant plan d’assemblage. ** Pour Mw: barre rigide, suivant plan d’assemblage. Guide Technique V9 / V9 Technical Guide CÂBLES INTERMÉDIAIRES INTERMEDIATE cables LR2-D1/3/ LRD-0/1/33 LC1-D80 NS250 CÂBLES DÉNTREE INCOME cables LC1-D40 LC1-D50/65 NS160 RELAIS THERMIQUE THERMAL RELAYS LR2-D1/ LRD-0/1 LR2-D1/ LRD-2 LR2-D3/ LRD-2/3 LRD-3 2 2 x 50 mm * 2 2 x 50 mm * 2 mm2 * 2 x 120 mm2 2 x 120 mm2 ** (Mf = 2x95 mm2) 3 x 50 (Mf = 2x120 mm2) 2 x 120 mm2 * To Mf type use rigid bar, according assembly drawing. ** To Mw type use rigid bar, according assembly drawing. 236 Installation de l’appareillage Switchgear Installation 3.6.2. Câbles pour REV démarreus (Integral, GV et NS) cables for REV starting (Integral, GV and NS) DISJUNCTEURS CONTACTEURS Integral 18 (LD5-LB130) RELAIS THERMIQUE THERMAL RELAYS LB1-LB03P CIRCUIT BREAKERS CONTACTORS Integral 32 (LD5-LC130) LB1-LC03M 6 mm LB1-LD03M 16 mm2 Integral 63 (LD5-LD130) GV2 GV7 NS100 CÂBLES INTERMÉDIAIRES INTERMEDIATE cables CÂBLES DE SORTIE OUTGOING cables 6 mm2 6 mm2 2 6 mm2 16 mm2 2 x LC1-D09/12 2.5 mm 2 x LC1-D18/25 4 mm2 4 mm2 4 mm2 2 mm2 6 mm2 10 mm2 10 mm2 mm2 2.5 mm2 2 2 x LC1-D32 6 mm 2 x LC1-D40 10 mm2 2.5 6 2 x LC1-K06/09 2.5 mm 2 x LC1-D32 6 mm2 2 2.5 mm2 6 mm2 2.5 mm2 6 mm2 2 x LC1-D38/40 10 mm 2 x LC1-D50/65 16 mm2 16 mm2 16 mm2 2 2 25 mm2 2 10 mm 2 10 mm2 2 x LC1-D80 25 mm 2 x LC1-D95 25 mm2 25 mm2 25 mm2 2 2 35 mm2 50 mm2 50 mm2 25 mm 2 x LC1-D115/F115 35 mm 2 x LC1-D150/F150 50 mm2 2 x LC1-F185 2 x 35 mm2 2 x 35 mm2 2 x 35 mm2 2 x LC1-F225 2 mm2 2 x 35 mm2 2 x 35 mm2 2 x 35 mm2 2 x 35 mm 2 x LC1-F265 NS80 CÂBLES DÉNTREE INCOME cables 35 mm 2 x 35 mm2 2 x 35 2 x LC1-D09/12 LR2-D1/LRD-0/1 2.5 mm 2 x LC1-D18 LR2-D1/LRD-0/2 4 mm2 4 mm2 4 mm2 2 x LC1-D25 LR2-D1/LRD-1/2 LR2-D3 6 mm 2 2 6 mm2 2 x LC1-D32 LR2-D3/LRD-2/3 6 mm2 6 mm2 6 mm2 2 x LC1-D38/40 LR2-D3/ LRD-2/3/33 10 2 x LC1-D50/65 LR2-D3/LRD-33 2 x LC1-D80 LR2-D3/LRD-33 25 mm 2 x LC1-D80 LR9-F5 2 x LC1-D115/F115 LR9-D /F 25 mm 2 x LC1-D09/12 LR2-D1/LRD-0/1 2,5 mm2 2 x LC1-D18 LR2-D1/LRD-2 4 mm 2 x LC1-D25/32 LR2-D3/LRD-2/3 6 mm2 2 x LC1-D38 LRD-3 10 mm 2 x LC1-D40 LR2-D1/3/ LRD-0/1/33 2 x LC1-D50/65 LRD-33/LR9-D 2 x LC1-D50/65 LR2-D33 16 mm 2 x LC1-D80 LR2-D3/LR9-D/F 2 x LC1-D80 LR2-D33 25 mm 2 x LC1-D95 LR2-D3/LR9-D 2 x LC1-D95 LRD-33 25 mm 2 x LC1-D115/F115 LR9-D /F 2 x LC1-D115 LRD-33 Guide Technique V9 / V9 Technical Guide 2 2.5 mm 6 mm mm2 2 2.5 mm2 mm2 10 mm2 16 mm2 16 mm2 16 mm2 2 mm2 25 mm2 25 mm2 25 mm2 25 mm2 2 2 25 mm2 2 10 25 25 mm 2,5 mm2 4 mm 2 4 mm2 6 mm2 6 mm2 2 10 mm2 10 mm2 10 mm2 10 mm2 16 mm2 16 mm2 16 mm2 2 2 16 mm2 25 mm2 25 mm2 25 mm2 2 2 25 mm2 25 mm2 25 mm2 25 mm2 2 2 25 mm2 35 mm2 35 mm2 35 mm2 2 2 35 mm2 35 mm 2 2,5 mm2 10 mm 16 mm 25 mm 25 mm 35 mm 237 Installation de l’appareillage Switchgear Installation DISJUNCTEURS CONTACTEURS CIRCUIT BREAKERS CONTACTORS NS160 2 x LC1-D150/F150 RELAIS THERMIQUE THERMAL RELAYS LR9-F 2 x LC1-D115/F115 LR9-D/F 35 mm 2 x LC1-F185 LR9-D5/F5 2 x 35 mm2 2 x 35 mm2 2 x 35 mm2 2 x LC1-F185 LR9-F5 2 x 35 mm2 2 x 35 mm2 2 x 35 mm2 2 x LC1-F225 LR9-F5 2 x 35 mm2 2 x 35 mm2 2 x 35 mm2 2 X LC1-F265 LR9-F 2 x 50 mm 2 2 2 x 50 mm2 2 x LC1-F330 LR9-F5 2 x 50 mm2 2 x 50 mm2 2 x 50 mm2 2 X LC1-F265 LR9-F7 * 2 x 50 mm2 2 x 50 mm2 2 x LC1-F330 LR9-F7 * 2 x 50 mm 2 2 x 50 mm2 2 x LC1-F400 LR9-F7 * 2 x 95 mm2 2 x 95 mm2 2 x LC1-F500 LR9-F7 * 2 x 95 mm 2 2 x 95 mm2 2 x LC1-F400 LR9-F7 * 2 x 95 mm2 2 x LC1-F500 LR9-F7 * 2 x 120 mm 2 2 x 120 mm2 2 x LC1-F630 LR9-F7 * 2 x 120 mm2 2 x 120 mm2 NS250 NS400 NS630 CÂBLES DÉNTREE INCOME cables CÂBLES INTERMÉDIAIRES INTERMEDIATE cables CÂBLES DE SORTIE OUTGOING cables 50 mm2 50 mm2 50 mm2 2 2 35 mm2 * Pour Mf: barre rigide, suivant plan d’assemblage. Guide Technique V9 / V9 Technical Guide 35 mm 2 x 50 mm 2 x 95 mm2 * To Mf type use rigid bar, according assembly drawing. 238 Installation de l’appareillage Switchgear Installation 3.6.3. Câbles pour Y/∆ démarreus (Integral, GV et NS) cables for Y/∆ starting (Integral, GV and NS) DISJUNCTEURS CONTACTEURS CIRCUIT BREAKERS CONTACTORS GV2 3 x LC1-D09/12 RELAIS THERMIQUE THERMAL RELAYS 2.5 mm2 2 6 mm 2.5 mm 3 x LC1-D18 6 mm 2 6 mm2 10 mm2 2 2.5 mm 2 6 mm 10 mm2 2 2.5 mm2 2 6 mm2 3 x LC1-D32 10 mm 3 x LC1-D40 16 mm2 16 mm2 16 mm2 3 x LC1-D50 25 mm 2 25 mm2 25 mm2 3 x LC1-D80 35 mm 2 35 mm2 35 mm2 3 x LC1-D115/F115 35 mm2 35 mm2 35 mm2 3 x LC1D-150/F150 2 2 50 mm2 3 x LC1-D09/12 50 mm 2 2 x 35 mm 2 3 x LC1-D80 LR2-D3 3 x LC1-D80 LR9-F5/D5 25 mm 25 mm2 3 x LC1-F115/D115 LR9-F / D 3 x LC1-D09/12 LR2-D1/LRD-0/1 3 x LC1-D18 LR2-D1/LRD-2 3 x LC1-D32 50 mm 2 x 35 mm 3 x LC1-D50/65 3 x LC1-D40 10 mm 2 LR2-D1/ LRD-0/1 LR2-D1/ LRD-0/2 LR2-D3/ LRD-1/2/3 LR2-D3/ LRD-2/33 LR2-D3/LRD-33 3 x LC1-D25/32 NS250 2.5 mm2 10 mm2 3 x LC1-D18 NS160 2.5 mm2 3 x LC1-D40 3 x LC1-F225 NS100 CÂBLES DE SORTIE OUTGOING cables 6 mm 3 x LC1-F185 NS80 CÂBLES INTERMÉDIAIRES INTERMEDIATE cables 3 x LC1-D18/25/32 3 x LC1-K06/09 GV7 CÂBLES DÉNTREE INCOME cables 2 x 35 2 10 mm2 mm2 2 x 35 mm2 2 2 x 35 mm2 2 x 35 mm 2.5 mm2 2.5 mm2 2.5 mm2 4 mm2 4 mm2 4 mm2 6 mm2 6 mm2 6 mm2 10 mm2 10 mm2 10 mm2 16 mm2 16 mm2 16 mm2 25 mm 2 25 mm 2 25 mm2 2 25 mm 2 25 mm2 25 mm2 25 mm2 mm2 2,5 mm2 2,5 mm 2 2,5 4 mm 2 LR2-D3/LRD-3 6 mm 2 3 x LC1-D40 LR2-D3/LRD-33 10 mm2 10 mm2 10 mm2 3 x LC1-D40 LR2-D1 10 mm 2 10 mm 2 10 mm2 3 x LC1-D50 LR2-D3/LRD-33 16 mm 2 16 mm 2 16 mm2 3 x LC1-D80 LR2-D3/LRD-33 25 mm2 25 mm2 25 mm2 3 x LC1-D80 LR9-F5/D5 25 mm 2 25 mm 2 25 mm2 3 x LC1-F115/D115 LR9-F / D/ LRD-33 LR2-D3/LRD-33 35 mm 2 35 mm 2 35 mm2 35 mm2 35 mm2 35 mm2 3 x LC1-D115 LRD-4/LR9-D5 35 mm2 35 mm2 35 mm2 3 x LC1-D150 LR9-D5 50 mm 2 mm2 50 mm2 3 x LC1-F115/D115 LR9-F / D 35 mm 2 2 35 mm2 50 mm2 50 mm2 50 mm2 50 mm2 50 mm2 50 mm2 50 mm2 50 mm2 50 mm2 3 x LC1-D80 3 x LC1-F150/D150 LR9-F / D 3 x LC1-D115 LRD-3/4 3 x LC1-D150 LRD-4 3 x LC1-F115/D115 4 mm2 6 mm2 6 mm2 50 35 mm 2 x 35 mm 2 2 x 35 mm 2 LR9-F5 2 x 35 mm 2 3 x LC1-F150 LR9-F5 2 x 35 mm2 3 x LC1-F185 LR9-F5 2 x 35 mm 2 3 x LC1-F225 LR9-F5 2 x 35 mm 2 3 x LC1-F265 LR9-F 2 x 35 mm 2 Guide Technique V9 / V9 Technical Guide 4 mm2 50 mm2 50 mm2 2 x 35 mm 2 2 x 35 mm2 2 x 35 mm 2 2 x 35 mm2 2 x 35 mm 2 2 x 35 mm2 239 Installation de l’appareillage Switchgear Installation DISJUNCTEURS CONTACTEURS CIRCUIT BREAKERS CONTACTORS NS400 3 x LC1-D150 NS 630 RELAIS THERMIQUE THERMAL RELAYS LRD-4 CÂBLES DÉNTREE INCOME cables * CÂBLES INTERMÉDIAIRES INTERMEDIATE cables CÂBLES DE SORTIE OUTGOING cables 50 mm2 50 mm2 3 x LC1-D150 LR9-D5 * 50 mm2 50 mm2 3 x LC1-F150 LR9-F5 * 2 3 x LC1-F185 LR9-F5 * 3 x LC1-F265 LR9-F7 50 mm 50 mm2 2 x 50 mm 2 2 xX 50 mm2 * 2 x 50 mm 2 2 x 50 mm2 3 x LC1-F330 LR9-F7 * 2 x 50 mm2 2 x 50 mm2 3 x LC1-F225 LR9-F5 * 2 x 50 mm 2 2 x 50 mm2 3 x LC1-F265 LR9-F7 * 2 x 50 mm 2 2 x 50 mm2 3 x LC1-F330 LR9-F7 * 2 x 50 mm2 2 x 50 mm2 3 x LC1-F400 LR9-F7 * 2 3 x LC1-F500 LR9-F7 * * Pour Mf: barre rigide, suivant plan d’assemblage. Guide Technique V9 / V9 Technical Guide 2 x 95 mm 2 x 120 mm 2 x 95 mm2 2 2 x 120 mm2 * To Mf type use rigid bar, according assembly drawing. 240 Sommaire du chapitre Chapter contents 3.7. Installation Appareils dans BLOKSET Installation devices in BLOKSET 3.7.1. Mise en œuvre du PEN ........................................................................... 242 Implementing a PEN Guide Technique V9 / V9 Technical Guide 241 Installation de l’appareillage Switchgear Installation 3.7. Installation Appareils dans BLOKSET Device installation in BLOKSET 3.7.1. Mise en œuvre du PEN Implementing a PEN PEN (*) PE L´utilisation du conducteur PEN dans une unité fonctionnelle BLOKSET est possible suivant le schéma ci-dessus (arrivée en TNC - départ en TNC) et pour les disjoncteurs ci-dessous. Type du Disjoncteur Type of Breaker possibilités possibilities NS100 / 160 / 250 NB50 / 100 / 225 pas développé not developed NS400 / 630 oui yes NB400 / 600 The use of PEN conductor in BLOKSET functional units is possible according the diagram above (incoming TNC - outgoing TNC) and for the following circuit breakers. ref. Guide des plans d’assemblage 7041xxx.pdf ref. Assembly drawings guide 7041xxx.pdf 3.5.1 1 pas développé not developed - - IN400/2500 oui yes 3.5.2 1 NS630b/1600 oui yes 3.5.3 1 .. 4 NT08/NT16 oui yes 3.5.4 1 .. 4 NW08/63 oui yes 3.5.5 1 .. 4 (*) Connexion entre Neutre et PE voir chapitre 3.5.6. du Guide Montage. Guide Technique V9 / V9 Technical Guide Formes Forms - (*) Connection between Neutral and PE chapter 3.5.6.of Assembly Guide. 242 Sommaire du chapitre Chapter contents 3.8. Compartiment de mesure/protection .............................................. 244 Measurement/Protection compartment 3.8.1. Solution générale .................................................................................... 244 General solution 3.8.2. Solution spécifique pour disjoncteur NW 3P ....................................... 245 Specific solution for 3P NW breakers Guide Technique V9 / V9 Technical Guide 243 Installation de l’appareillage Switchgear Installation 3.8. Compartiment de mesure/protection Measurement/Protection compartment 3.8.1. Solution générale General solution Ces compartiments sont disponibles pour l’installation d’unités de protection ou de mesures (ampèremetre, voltmetre, SEPAM*, etc...). Pour informations complémtentaires, voir chapitre 2.1 du Guide des plans d’assemblage, ref. “7041xxx.pdf”. Nombre de modules Number of modules 4 6 8 9 12 Profondeur 180 mm Depth 180 mm oui yes oui yes oui yes oui yes oui yes (*) SEPAM 2000 possible uniquement en profondeur 330 mm. These compartiments are available for metering or protection devices (ampmeter, voltmeter, SEPAM*, etc...) For additional information see Assembly drawings guide, ref. “7041xxx.pdf” Profondeur 330 mm Depth 330 mm oui yes oui yes oui yes (*) SEPAM 2000 possible only in 330 mm depth. Compartiment de mesure/protection Metering/Protection compartment 4M jusqu'à 12M 4M up to 12M Espace pour installation des unités fonctionnelles connecteés au jeu de barres vertical suivant les besoins du client. Space for installation of functional units connected to vertical busbars according to customer need. Guide Technique V9 / V9 Technical Guide 244 Installation de l’appareillage Switchgear Installation 3.8.2. Solution spécifique pour disjoncteur NW 3P Specific solution for 3P NW breakers Les solutions standard suivantes sont à utiliser pour les disjoncteurs tripolaires Nw08 à Nw40. Standard solution showed hereunder have to be used in case of 3 pole breaker Nw08 to Nw40. Compartiment de mesure/protection Metering/Protection compartment 4M 4M Option 4a NW08-32 NW08-32 NW08-32 Option 8a Option 4b 12M 12M 4M 12M 4M 4M Option 8b 12M Col 01 Col 03 Col 02 NW08-32 Col 04 4M - NW25 6M - NW32 4M - NW32 (*) 9M - NW40 Option 3a (*) profondeur 180 mm seulement (*) 180 mm depth only Option 2 12M 12M Guide Technique V9 / V9 Technical Guide 245 Sommaire du chapitre Chapter contents 4. Auxiliaires et borniers Auxiliaries and terminal blocks 4.1. Position des auxiliaires et des borniers ......................................... 247 Position of auxiliaries and terminal blocks 4.1.1. Circuits auxiliaires importants .............................................................. 247 Major auxiliary circuits 4.1.2. Circuits auxiliaires réduits ..................................................................... 247 Reduced auxiliary circuits 4.1.3. Borniers d’auxiliaires importants > 150 mm ........................................ 248 Major auxiliary terminal blocks > 150 mm 4.1.4. Borniers auxiliaires réduits < 150 mm .................................................. 248 Reduced auxiliary terminal blocks < 150 mm 4.1.5. Borniers puissance ................................................................................. 248 Power terminal blocks 4.1.6. Borniers de désaccouplement des auxiliaires ..................................... 248 Auxiliary decoupling terminal blocks 4.1.7. Collecteur auxiliaire ................................................................................ 249 Auxiliary collector Guide Technique V9 / V9 Technical Guide 246 Auxiliaires et borniers Auxiliaries and terminal blocks 4. Auxiliaires et borniers Auxiliaries and terminal blocks 4.1. Position des auxiliaires et des borniers Position of auxiliaries and terminal blocks 4.1.1. Circuits auxiliaires importants Major auxiliary circuits Ceux-ci seront installés dans des modules relayage réservés à l’implantation de l’appareillage et des bornes, ou (si possible) dans la gaine de raccordement. Cette implantation sera portée sur le schéma. 4.1.2. These will be installed in the relay modules reserved for the installation of the switchgear and terminals, or (if possible) in the connection duct. This installation will be included in the diagram. Circuits auxiliaires réduits Reduced auxiliary circuits Appareillage sur portillon: La protection sera installée sur le portillon en utilisant les multifix ci-aprèsþ: portillon 200: multifix 155 mm, Switchgear on auxiliary compartment door: Protection will be installed on the auxiliary compartment door using the following multifix rails: auxiliary compartment door 200: 155 mm multifix rail. 2 trous oblongs / 2 oblong holes 6.5 x 8.5 portillon 400: multifix 355 mm. auxiliary compartment door 400: 355 mm multifix rail. 2 trous oblongs / 2 oblong holes 6.5 x 8.5 Guide Technique V9 / V9 Technical Guide 247 Auxiliaires et borniers Auxiliaries and terminal blocks Appareillage sur plastron: La protection sera installée derrière le plastron. Switchgear on escutcheon: Protection will be installed behind the escutcheon. Interdit: l’implantation d’appareillage sur un plastron situé devant un jeu de barres horizontal ou un jeu de barres de transfert. It is forbidden to install the switchgear on the escutcheon situated in front of a horizontal busbar or transfer busbar 4.1.3. Borniers d’auxiliaires importants > 150 mm Major auxiliary terminal blocks > 150 mm Ils seront installés dans des modules de raccordement, seul ou avec l’appareillage auxiliaire. L’implantation sera portée sur le schéma. 4.1.4. Borniers auxiliaires réduits < 150 mm Reduced auxiliary terminal blocks < 150 mm Ils seront installés dans la gaine à câbles dans la mesure ou cela ne gène pas le passage des câbles. 4.1.5. These will be located either in the modules of the switchgear compartment or in the cable duct and will be included in the installation diagram. Borniers de désaccouplement des auxiliaires Auxiliary decoupling terminal blocks Les borniers de désaccouplement seront situés dans le compartiment JdB 4 modules du haut. Guide Technique V9 / V9 Technical Guide These will be installed in the cable duct where this does not hinder the cable leadthrough. Borniers puissance Power terminal blocks Ils seront dans des modules du compartiment appareillage ou dans la gaine à câbles et portés sur le schéma d’implantation. 4.1.6. These are installed in connection modules, alone or with auxiliary switchgear. This installation will be included in the diagram. These terminal blocks will be located in the top 4-module busbar compartment. 248 Auxiliaires et borniers Auxiliaries and terminal blocks 4.1.7. Collecteur auxiliaire Auxiliary collector Les circuits auxiliaires peuvent être alimentés par collecteur auxiliare ref. 07400. Voir figure ci dessous. Peuvent être installés dans les colonnes type D, Mf, Ms ou Mw. The auxiliary circuits can be supplied by the auxiliary collector ref. 07400. See figure bellow: It can be installed in columns D, Mf, Ms or Mw. Ref. 07400 In: 63 A - Ui= 660 V Compartment des cables Cable compartment Guide Technique V9 / V9 Technical Guide 249 Sommaire du chapitre Chapter contents 5. Divers Miscellaneous 5.1. Lignes de fuite et distances d’isolement ...................................... 252 Creepage distance and clearance 5.1.1. Définition (IEC 60439.1) .......................................................................... 252 Definition (IEC 60439.1) 5.1.1.1. Distance d’isolement ................................................................. 252 Clearance 5.1.1.2. Ligne de fuite .............................................................................. 252 Creepage distance 5.2. Règles d’assemblage ...................................................................... 253 Assembly rules 5.2.1. Assemblages par vis .............................................................................. 253 Screw assembly 5.2.2. Assemblage électrique ........................................................................... 254 Electrical assembly 5.2.3. Assemblage mécanique ......................................................................... 255 Mechanical assemblies 5.2.4. Couples de serrage ................................................................................. 256 Tightening torques 5.2.4.1. Visserie à pas gros non graissé ............................................... 256 Not greased, wide pitch screws. 5.2.4.2. Autres visseries ......................................................................... 257 Other screws 5.3. Repérage .......................................................................................... 259 Labels and marking 5.4. Détrompage des tiroirs ................................................................... 259 Drawer polarization 5.5. Verrouillage des tiroirs ................................................................... 259 Drawer interlocking 5.6. Verrouillage mécanique des disjoncteurs en tiroir ...................... 259 Mechanical circuit breaking interlocking to drawer 5.7. Fin de course tiroirs Mw ................................................................. 259 Mw drawers limit switch Guide Technique V9 / V9 Technical Guide 250 Sommaire du chapitre Chapter contents 5.8. Réalisation des IP ............................................................................ 260 Realization of the IP 5.9. Montage épingles chauffantes et des Thermostats ..................... 261 Mounting heating pins and thermostat 5.9.1. Dimensionnement de l’épingle chauffante ........................................... 261 Heating pin rating 5.10. Tenue aux Séismes ......................................................................... 265 Seismic withstand 5.10.1.Procédure ................................................................................................ 265 Procedure 5.10.2.Montage des pièces additives ............................................................... 265 Assembling drawing 5.11. Tenue Arc Interne ............................................................................ 265 Internal Arc Withstand 5.11.1.Procédure ................................................................................................ 265 Procedure 5.11.2.Montage des pièces additives ............................................................... 265 Assembling drawing 5.12. Arrêt de Porte ................................................................................... 266 Door Stopper 5.12.1.Définition ................................................................................................. 266 Definition 5.12.2.Montage des pièces additives ............................................................... 266 Assembling drawing Guide Technique V9 / V9 Technical Guide 251 Divers Miscellaneous 5. Divers Miscellaneous 5.1. Lignes de fuite et distances d’isolement Creepage distance and clearance 5.1.1. Définition (IEC 60439.1) Definition (IEC 60439.1) 5.1.1.1. Distance d’isolement Clearance La distance d’isolement est le distance entre deux parties conductrices le long d’un fil tendu suivant le plus court trajet possible entre ces deux parties conductrices. Elle dépend: de la tension de choc (Uimp). du degré de pollution. 5.1.1.2. Clearance is the distance between the two conductive parts the length of a tight wire taking the shortest possible route between the two conductive parts. It varies according to the: Impulse voltage (Uimp). Degree of pollution. Ligne de fuite Creepage distance La ligne de fuite est la distance la plus courte le long de la surface d’une matière isolante entre deux parties conductrices. Elle dépend: de la tension d’isolement (Ui). du degré de pollution. du groupe de matériaux. Le degré de pollution retenu dans nos tableaux est de niveau 3. Les matériaux utilisés sont de classe 3A. Creepage distance is the shortest distance the length of the surface of an insulating material between two conductive parts. It varies according to the: Insulating voltage (Ui). Degree of pollution. Group of materials. The degree of pollution in our tables is level 3. The materials used are class 3A. Suivant IEC 60439.1 In compliance with the IEC Standard 60439.1 tableaux / switchboards Jeux de barres principaux / Main busbars dérivations / shunts Uimp = 12 kV Ui = 1000 V Compact Uimp = 8 kV Ui = 750 V Guide Technique V9 / V9 Technical Guide Distance d’isolement Clearance 14 mm Ligne de fuite Creepage distance 16 mm 8 mm 12,5 mm 252 Divers Miscellaneous 5.2. Règles d’assemblage Assembly rules 5.2.1. Assemblages par vis Screw assembly Domaines d’application Fields of application Tous assemblages électriques ou mécaniques vissés. Utiliser de la visserie acier zingué bichromaté (Zn8C) classe 8-8. Les couples de serrage sont définis dans les pages suivantes. Dans l’association vis-rondelle, choisir une rondelle de dureté au moins égale à celle de vis. (E 25 030 $ 5.2.3.2). All electrical and mechanical screw assemblies. Use galvanized, bi-chromated steel screws (Zn8C) class 8-8. The tightening torques are specified in the following pages. For the screw and washer combination choose a washer which is at least as hard as the screw. (E 25 030 $ 5.2.3.2). tige filetée threaded Vis H H screw écrou H H nut écrou à bague de freinage plastique (type nylstop) nut with plastic braking écrou à embase crantée (type thiant)t latched collar nu rondelle plate large et épaisse (ép. 2 mm) thick, wide, flat washer (th. 2 mm) rondelle “contact” série moyenne “contact” washer, medium rondelle “contact” à picots picot edge “contact” barre conductrice ou extrémité compactée de tresse “conducting” bar or compressed Guide Technique V9 / V9 Technical Guide 253 Divers Miscellaneous 5.2.2. Assemblage électrique Electrical assembly Trou rond. Round hole. barre Cu / barre Cu Cu bar / Cu bar barre Cu / plage d'appareillage ou sur trou taraudé Cu bar / switchgear pad on threaded hole Rappel: respecter le couple de serrage de l'appareillage. Note: respect switchgear tightening torque. Trou ovalisé. Oval hole. Rajouter côté trou ovalisé une rondelle plate épaisse large sous la rondelle contact. En cas de doute, vérifier par un caLCul de RdM (résistance des matériaux). Add a thick, wide, flat washer to side with oval hole below the contact washer. If in doubt, check with an MR (material resistance) caLCulation. Rappel: la rondelle plate aura une largeur égale à 2 fois le diamètre du trou ovalisé. Note: the flat washer should be twice the width of the diameter of the oval hole. Guide Technique V9 / V9 Technical Guide 254 Divers Miscellaneous 5.2.3. Assemblage mécanique Mechanical assemblies Trou rond Round hole Sans nécessité de continuité électrique des masses. Does not require equipotential bonding of exposed conductive parts. Avec continuité électrique des masses. With equipotential bonding of exposed conductive parts. Note: l'utilisation d'écrou à embase crantée est parfois intéressante pour des raisons de montage et d'accessibilité difficile, mais: il revient plus cher, l'utilisation d'un montage non symétrique n'est pas viable vis à vis du desserrage (il est recommandé de l'utiliser avec une vis à embase crantée). Il n'assure pas la continuité électrique des masses. Utilisation de l’écrou cage. Note: using a latched collar nut can sometimes facilitate difficult assembly and access, but: it is more expensive and using a nonsymmetrical assembly is not viable as regards loosening (it is advisable to use it with a latched collar nut). It does not guarantee equipotential bonding of exposed conductive parts. Cage nut use. L'écrou cage doit être adapté à l'épaisseur de la tôle sur laquelle il se fixe. The cage nut must be adapted to the thickness of the plate onto which it is fixed. Note: L'écrou n'assure pas la continuité des masses sauf si utilisation de l'écrou cage à picots. Quand utiliser l'écrou cage sur parties peintes, il doit être utilisé une écrou cage à picots. Note: the cage nut does not guarantee equipotential bonding of exposed conductive parts except when a picot edge cage nut is used. When using cage nut over painted parts, it must be used picot squared box nut (ref. 4470579 VA). Guide Technique V9 / V9 Technical Guide 255 Divers Miscellaneous 5.2.4. Couples de serrage Tightening torques Visserie à pas gros non graissé Not greased, wide pitch screws. 5.2.4.1. Tableau des couples de serrage pour la visserie à pas gros non graissée. (Valables pour les assemblages électriques et mécaniques.) Table of tightening torques for non greased, wide pitch screws. (Valid for electrical and mechanical assemblies). Classe 8.8: Re = 64 daN/mm2 Rr = 80 daN/mm2 Suivant norme E 25 030 Class 8.8: Re = 64 daN/mm2 Rr = 80 daN/mm2 In compliance with standard E 25 030 Diamètre élastique Nominal diameter Pas Pitch Section résistance r2 moy av.r2 crossresistance Diam. perçage Max. drilling section Force axial maxi Axial force diameter (mm) (mm) (mm2) (mm) (daN) 3 0,5 5,03 3,4 150 4 0,7 8,78 4,5 250 5 0,8 14,2 5,5 380 6 1 20,1 6,6 600 8 1,25 36,6 9 1000 10 1,5 58 11 1500 12 1,75 84,3 14 2400 14 2 115 16 3300 16 2 157 18 4500 18 2,5 192 20 5500 20 2,5 245 22 7100 Couple de serrage à 80% de la limite nominal (m.daN) pour vis inox graissée ou acier classe 8.8 non graissée Tightening torque at 80% of the elasticity limit (m.daN) for greased steel screws or non greased class 8.8 steel screws Ecrou avec rondelle Ecrou embase crantée Ecrou nylstop Nut whit washer latched collar nut avec rondelle Nylstop nut with washer Contact Acier ou Alu Cuivre Contact Contact Steel or alu Copper Contact 0,15 0,15 0,17 0,17 0,35 0,35 0,41 0,38 0,70 0,80 0,93 0,75 1,3 1,35 1,55 1,45 2,8 2,5 2,9 3,1 5 5 5,9 5,4 7,5 7,9 9,2 8,3 12 12,5 14,6 13,2 18,5 18 21 20 26 27 31 28 37 39 45 41 Rappel: 1 cm kgf = 0,01m.daN Note: 1 cm kgf = 0,01m.daN Dispersion obtenue sur Variations obtained on Serrage Tightening with A la clé dynamométrique Torque wrench A la visseuse automatique Automatic screw driver A la clé manuelle Manual spanner A la clé à chocs Impact spanner Couple Torque ± 10% Force axiale* Axial force* ± 30% ± 15% ± 30% ± 30% ± 50% ± 25% * pourcentage cumulé avec la dispersion sur le couple Guide Technique V9 / V9 Technical Guide * percentage accumulated after variations on the torque. 256 Divers Miscellaneous 5.2.4.2. Autres visseries Other screws Pour une vis, une tige filetée ou écrou de hauteur 0,8 x son diamètre constitué des matériaux suivants (voir tableau ci-dessous), multipliez le couple du tableau de la page précédente par le coefficient A. For a screw, a threaded rod or a nut with a height which is 0.8 times its diameter made in the following materials (see table below), multiply the torque from the previous page by the coefficient A. Pour un trou taraudé (dans ces mêmes matériaux), il est généralement possible d’appliquer le couple prévu pour la vis à condition de prévoir une longueur de filets de prise suffisant soit: 1 x d dans l’acier. 1,5 x d dans la fonte et alliage de cuivre (sauf traitement spécifique des filets) For a threaded hole (in the same materials) it is generally possible to use the torque supplied for the screw, provided that length of the connector threads is sufficient, i.e.: 1 x d in steel. 1.5 x d in copper smelting or copper alloy (except special treatment for the threads). d = diamètre nominal de vis d = screw’s nominal diameter. Si cette longueur n’est pas suffisante, appliquez le coefficient A du tableau cidessous. En l’absence de coefficient, appliquez la règle empirique: A = RE / 48. RE étant la limite élastique du matériau considéré. If this length is not sufficient, apply the coefficient A from the table below. Where there is no coefficient, apply the empirical rule: A = RE / 48. where RE is the elastic limit of the material in question. Matériaux Materials Cuivre ETP H12 Copper ETP H12 AZ5 GU AZ5 GU Laiton Brass Bronze Bronze écrou en cage «Adx» «Adx» cage nut vis en cage «Adx» «Adx» cage screw Guide Technique V9 / V9 Technical Guide A 0,4 0,65 de l’ordre de 0,50 in the order of 0.50 de l’ordre de 0,65 in the order of 0.65 0,5 0,5 257 Divers Miscellaneous Cas de la visserie acier classe 8.8 montée graissée: Certains ateliers utilisent simultanément des vis inox et des vis acier de classe 8.8. A couple de serrage égal, une vis montée graissée subit un effort axial plus important que la même vis montée non graissée. Les vis acier classe 8.8 montées graissées doivent donc être serrées aux couples indiqués dans le tableau ci-dessous. Diamètre Diameter Pas Pitch 6 1 8 1,25 12 1,75 16 2 18 2,5 Couple de serrage Tightening torque Rondelle plate Rondelle contact Flat washer Contact washer 0,85 1 1,9 2,1 6,2 7 14 18,5 Après essais du laboratoire central des matériaux et métrologie (Merlin Gerin), ces couples ont été déterminés pour respecter les 2 paramètres suivants: Effort axial suffisant pour supprimer les risques de desserrage de l’assemblage. Effort axial limité pour ne pas dépasser la limite élastique du matériau. Guide Technique V9 / V9 Technical Guide On class 8.8 steel screws mounted and greased: Certain works use both stainless steel screws and class 8.8 steel screws. With identical tightening torques, a screw when mounted greased undergoes a larger axial load than the same screw when mounted non greased. Class 8.8 steel screws must therefore be tightened with the torques indicated in the table below. After being tested at the material and metrology central laboratory (Merlin Gerin), these tightening torques were specified so as to compy with the following 2 parameters: Sufficient axial force to prevent assembly loosening risks Limited axial force so as not to exceed the elastic limit of the material. 258 Divers Miscellaneous 5.3. Repérage Labels and marking Voir Régles générales de mise en oeuvre 1913xxx.pdf See General assembly rules 1913xxx.pdf. 5.4. Détrompage des tiroirs Drawer polarization Voir plan de montage n° 51 127 866. See assembly drawing n° 51 127 866. 5.5. Verrouillage des tiroirs Drawer interlocking Voir plan de montage n° 51 127 789 See assembly drawing n° 51 127 789. 5.6. Verrouillage mécanique des disjoncteurs en tiroir Mechanical circuit breaking interlocking to drawer Voir plans de montage n° 51127978 / 51127979 / 51127980 / 51127981 / 51127982 / 51130415 See assembly drawings n° 51127978 / 51127979 / 51127980 / 51127981 / 51127982 / 51130415 5.7. Fin de course tiroirs Mw Mw drawers limit switch 2 solutions d’implantation des micros fin de course sont disponibles pour la position des tiroir Mw: 1 - Micro contacts embarqués, ref. XC1ZP2105, 10 A / 500 V. 2 - Micro contacts sur séparateur, ref. 87466, 5 A / 230 V. 1 - MICRO CONTACTS EMBARQUÉS / 1 - MICRO SWITCHES ON DRAWER 1 - Micro switches on drawers, ref. XC1ZP2105, 10 A / 500 V 2 - Microswitches on separateur, ref. 87466, 5 A / 230 V. Ref.: XC1ZP2105 Etiquette de position / Indicator Label S0 S02 Identification des micro contacts: S0 - Indicateur du tiroir en position test ou alimentation auxiliaire externe. S01 - Ouverture du contacteur S02 - Indicateur du tiroir en position embroché Guide Technique V9 / V9 Technical Guide 2 solutions for micro switches assembly are available for Mw drawers: S01 Identification microswitchs: S0 - Indicator of drawer in test position or external auxiliary source. S01 - Switching off the contactor S02 - Indicator of drawer in connected position 259 Divers Miscellaneous 2 - MICRO CONTACTS SUR SEPARATEUR / 2 - MICRO SWITCHES ON SEPARATOR S03 S04 S05 Ref.: 87466 Chaque rèference contient 3 pièces / Each reference contains 3 pieces Etiquette de position / Indicator Label Identification des micro contacts montés sur le separateur: S03 - Connecté S04 - Position test S05 - Déconnecté The identification of the limit switches installed on the separator are: S03 - Connected S04 - Test position S05 - Disconnected Pour les détails additionnels voir plans d’assemblage n° 51127739 / 51127984 pour installation dans tiroirs, nº 51132458 pour installation sur séparateur. For additional details see assembly drawings n° 51127739 / 51127984 in case of switches on drawers or 51132458 in case of switches on separator. 5.8. Réalisation des IP Realization of the IP Pour réalisation des IP, voir les règles dans le guide des plans d’assemblage guide, ref. “7041xxx.pdf”, item 6.6. Guide Technique V9 / V9 Technical Guide For IP realisation, see the rules on item 6.6 of Assembly drawings guide, ref. “7041xxx.pdf”. 260 Divers Miscellaneous 5.9. Montage épingles chauffantes et des Thermostats Mounting heating pins and thermostat 5.9.1. Dimensionnement de l’épingle chauffante Heating pin rating Principe: Le dimensionnement consiste à déterminer la puissance que doit dissiper la résistance de l’épingle chauffante (Pw) afin de maintenir à l’intérieur du tableau une température moyenne (T1) supérieur à la température de rosée (Tr) de l’air en tenant compte de la dissipation calorifique de l’enveloppe (convection, ventilation). Principle: Rating consists of determining the power which the heating pin resistor must dissipate (Pw) so as to maintain an average temperature (T1) inside the switchboard which is higher than the condensation temperature (Tr) while taking the enclosure’s heat dissipation into account (convection, ventilation). Tableau ventilé: Pw = h.S.(T1-Ta) + z.Cp.(T1-Ta) Tableau étanche: Pw = h.S.(T1-Ta) Ventilated switchboard: Pw = h.S.(T1-Ta) + z.Cp.(T1-Ta). Sealed switchboard: Pw = h.S.(T1-Ta). avec: T1: température souhaitée à l’intérieur du tableau (en °C). Ta: température de l’air ambiant (en °C). S: surface d’échange (en m2). h: coefficient d’échange (en W/m2.°C). z: débit d’air (en Kg/s.). Cp: capacité calorifique de l’air (en J/Kg.°C). where: T1: desired temperature inside the switchboard (in °C). Ta: ambient air temperature (in °C). S: exchange surface area (in m2). h: exchange coefficient (in W/m2.°C). z: air flowrate (in Kg/s.). Cp: air heat capacity (in J/Kg.°C). Remarques: h a une valeur de 4 à 5 W/m2.°C. S correspond soit à la surface des parois du tableau en contact avec l’air ambiant pour une enveloppe non cloisonnée soit à la surface des parois contenant l’épingle chauffante pour une enveloppe cloisonnée. z est fonction du tableau (section d’entrée d’air, cloisonnement...). Observations: h has a value of 4 to 5 W/m2.°C. S corresponds either to the surface area of the walls of the switchboard which are in contact with the ambient air for a non partitioned enclosure or to the surface area of the walls containing the heating pin for a partitioned enclosure. z depends on the switchboard (air input cross-section, partitioning, etc...). Applications: Applications: Dimensionnement de la résistance d’une épingle chauffante: relation puissance/échauffement: – IP 31 ............................... ÷ Pw = 40. ∆T Rating the resistor of a heating pin: – IP 54 ............................... ÷ Pw = 22,7. avec ∆T = T1 - Ta. Guide Technique V9 / V9 Technical Guide ∆T power / heating ratio: – IP 31 ............................... ÷ Pw = 40. ∆T – IP 54 ............................... ÷ Pw = 22,7. ∆T where ∆T = T1 - Ta. 261 Divers Miscellaneous CALCUL: Calculation: Démarche: 1: état initial de l’air: température, humidité relative => déterminer Tr, température de rosée (Cf tableau en annexe) 2: T1 = Tr + 5 (en °C): la résistance doit permettre de maintenir une température interne moyenne de 5°C au dessus de la température de rosée. 3: application des formules. Approach: 1: initial state of air: temperature, relative humidity => determine Tr, condensation temperature (see table in appendix) 2: T1 = Tr + 5 (in °C): the resistor must make it possible to maintain an average inside temperature of 5°C above the condensation temperature. 3: apply formulas. Exemple: IP31 en fonctionnement normal. ..Température de l’air interne 60 °C. } } => Température de } condensation: Tr = 40 °C Humidité relative 40% Température de l’air ambiant: 35 °C. Example: IP31 in normal operating conditions. Inside air temperature 60 °C. } } => Condensation } temperature: Tr = 40 °C Relative humidity 40%.} Ambient air temperature: 35 °C. Arrêt du tableau fi baisse de la température interne. Pour éviter la condensation on doit maintenir une température interne moyenne T1 = 40 + 5 = 45 °C Switchboard stopped drop in inside temperature. To avoid condensation an average inside temperature of T1 = 40 + 5 = 45 °C must be maintained. Application des formules: ∆T = 45 - 35 = 10 °C. Pw = 40. 10 = 400 W. Application of formulas: ∆T = 45 - 35 = 10 °C. Pw = 40. 10 = 400 W. Remarque: si Tr ð Ta il n’y a pas besoins d’épingle chauffante. Note: if Tr ðTa there is no need for a heating pin. Installation: Il convient d’installer dans la mesure du possible l’épingle chauffante dans la partie inférieur de la zone jeux de barres/ dérivations amont des appareils en tenant compte de son accessibilité. L’épingle chauffante doit être installée de façon à ce qu’elle n’échauffe pas les fils qui l’alimentent (fils d’alimentation en position basse). Installation: It is advisable to install the heating pin where possible in the lower part of the busbar / connections zone downstream of the circuit breakers while taking its accessibility into account. The heating pin must be installed in such a way as to ensure that it does not heat the wires which supply it (supply wires in bottom position). Pour Blokset, un montage standardisé est en cours d’études. For Blokset, a standardised assembly is being studied. Guide Technique V9 / V9 Technical Guide 262 Divers Miscellaneous Tableau de choix des épingles chauffantes Selection table of heating pins Tension d’utilisation: 230 V Puissance Power Référence MGA MGA reference 60 W 150 W 250 W 07992 07993 07994 Operating voltage: 230 V Thermostat Thermostat Il permet de régler et de limiter la température à l’intérieur de l’armoire après l’installation d’épingles chauffantes. The thermostat allows the temperature inside the cubicle to be regulated and limited after the heating pins have been installed. Température d’utilisation: +10°C à + 50°C. Tension d’utilisation: 230 V. Fixation: sur rail multifix. Référence: 07999. Operating temperature: +10°C to + 50°C Operating voltage: 230 V Fixing: on multifix rail. Reference: 07999. Guide Technique V9 / V9 Technical Guide 263 Divers Miscellaneous Annexe Appendix Valeurs de température de rosée pour différentes humidités et température initiale d’air Température initiale de l’air (°C) Initial air temperature (°C) 40 °C 50 °C 60 °C 70 °C 80 °C Guide Technique V9 / V9 Technical Guide Humidité relative Relative Humidity 30% 40% 50% 70% 100% 30% 40% 50% 70% 100% 30% 40% 50% 70% 100% 30% 40% 50% 70% 100% 30% 40% 50% 70% 100% Condensation temperature values for different air humidities and initial temperatures Température de rosée Tr (°C) Condensation temperature (°C) 19 °C 22 °C 25 °C 31 °C 40 °C 27 °C 30 °C 36 °C 43 °C 50 °C 35 °C 40 °C 45 °C 52 °C 60 °C 44 °C 50 °C 54 °C 60 °C 70 °C 50 °C 57 °C 64 °C 70 °C 80 °C 264 Divers Miscellaneous 5.10. Tenue aux Séismes Seismic withstand 5.10.1. Procédure Procedure Voir “Procédure d’essais de séisme” n° PE 9703001 (11 pages). Fichier informatique Proseis f.doc. See “Seismic Test Procedure” nb: PE 9703001 (11 pages). Electronic file Proseisa.doc. 5.10.2. Montage des pièces additives Assembling drawing Voir Guide des plans d’assemblage, ref. 7041xxx.pdf, chapitre 7 et Synoptique BLOKSET, 51131911, plus Guide des Références 1910xxx.doc . See Assembling Drawings Guide 7041xxx.pdf chapter 7 and Synoptic BLOKSET, 51131911, plus Reference Guide 1910xxx.doc. 5.11. Tenue Arc Interne Internal Arc Withstand 5.11.1. Procédure Procedure Voir “Rapport d’essai n° 001-98”. Fichier informatique “ART84296.pdf”. See “ASEFA Test Report nb. 001-98” . Electronic file “ART84296.pdf”. 5.11.2. Montage des pièces additives Assembling drawing Voir Guide des plans d’assemblage “7041xxx.pdf”, chapitre 2.5. Guide Technique V9 / V9 Technical Guide .See Assembling Drawings Guide ref. “7041xxx.pdf”, chapter 2.5. 265 Divers Miscellaneous 5.12. Arrêt de Porte Door Stopper 5.12.1. Définition Definition L’arrêt de porte peut être monté sur toutes les portes gauches ou droites, sauf pour la porte 15 M d’un tiroir débrochable et la porte arrière d’une colonne Mw. This door stopper can be assembled on all left or right doors, except on 15M doors of withdrawable functional units and rear door of Mw column. Arrêt de Porte / Door Stopper 5.12.2. Montage des pièces additives Assembling drawing Voir Guide des plans d’assemblage, ref. “7041xxx.pdf”, chapitre 2.5. Guide Technique V9 / V9 Technical Guide See Assembling drawings guide, ref. “7041xxx.pdf”, chapter 2.5. 266 Sommaire du chapitre Chapter contents 6. Annex 01 ....................................................................... 270 Appendix 01 6.1. Blokset Mf / Mw ................................................................................ 270 Protection moteurs ancienne gamme Motor protection old range 6.1.1. Tableaux de coordination et modularité ............................................... 270 Coordination and modularity tables 6.1.1.1. GV2-P .......................................................................................... 271 Type de coordination: 1 Coordination type: 1 6.1.1.2. GV2-P .......................................................................................... 273 Type de coordination: 2 Coordination type: 2 6.1.1.3. Etoile / Triangle (Y/D) STAR / DELTA (Y/D) Compact NS80H-MA .................................................................. 297 Type de coordination: 2 Coordination Type: 2 Guide Technique V9 / V9 Technical Guide 2 sens de marche Reverse Compact NS80H-MA .................................................................. 295 Type de coordination: 1 Coordination type: 1 6.1.1.12. 2 sens de marche Reverse Compact NS80H-MA .................................................................. 291 Type de coordination: 2 Coordination type: 2 6.1.1.11. DOL (Démarrage direct) DOL (Direct On Line) Compact NS80H-MA .................................................................. 288 Type de coordination: 1 Coordination type: 1 6.1.1.10. DOL (Démarrage direct) DOL (Direct On Line) Compact NS80H-MA .................................................................. 284 Type de coordination: 2 Coordination type: 2 6.1.1.9. Etoile / Triangle (Y/D) STAR / DELTA (Y/D) Compact NS80H-MA .................................................................. 281 Type de coordination: 1 Coordination type: 1 6.1.1.8. Etoile / Triangle (Y/D) STAR / DELTA (Y/D) GV2-P .......................................................................................... 280 Type de coordination: 2 Coordination type: 2 6.1.1.7. 2 sens de Marche Reverse GV2-P .......................................................................................... 279 Type de coordination: 1 Coordination type: 1 6.1.1.6. 2 sens de Marche Reverse GV2-P .......................................................................................... 277 Type de coordination: 2 Coordination type: 2 6.1.1.5. DOL (Démarrage direct) DOL (Direct On Line) GV2-P .......................................................................................... 275 Type de coordination: 1 Coordination type: 1 6.1.1.4. DOL (Démarrage direct) DOL (Direct On Line) Etoile / Triangle (Y/D) STAR / DELTA (Y/D) 267 Sommaire du chapitre Chapter contents 6.1.1.13. Compact NS100-630l-MA ........................................................... 301 Type de coordination: 1 Coordination type: 1 6.1.1.14. Compact NS100-630l-MA ........................................................... 307 Type de coordination: 2 Coordination type: 2 6.1.1.15. Etoile / Triangle (Y/D) STAR / DELTA (Y/D) GV7 .............................................................................................. 349 Type de coordination: 2 Coordination Type: 2 6.1.1.25. 2 sens de marche Reverse GV7 .............................................................................................. 345 Type de coordination: 1 Coordination Type: 1 6.1.1.24. 2 sens de marche Reverse GV7 .............................................................................................. 341 Type de coordination: 2 Coordination Type: 2 6.1.1.23. DOL (Démarrage direct) DOL (Direct On Line) GV7 .............................................................................................. 337 Type de coordination: 1 Coordination Type: 1 6.1.1.22. DOL (Démarrage direct) DOL (Direct On Line) GV7 .............................................................................................. 333 Type de coordination: 2 Coordination Type: 2 6.1.1.21. Etoile / Triangle (Y/D) STAR / DELTA (Y/D) GV7 .............................................................................................. 329 Type de coordination: 1 Coordination Type: 1 6.1.1.20. Etoile / Triangle (Y/D) STAR / DELTA (Y/D) Compact NS100-630l-MA ........................................................... 325 Type de coordination: 2 Coordination Type: 2 6.1.1.19. 2 sens de marche Reverse Compact NS100-630l-MA ........................................................... 321 Type de coordination: 1 Coordination type: 1 6.1.1.18. 2 sens de marche Reverse Compact NS100-630l-MA ........................................................... 317 Type de coordination: 2 Coordination type: 2 6.1.1.17. DOL (Démarrage direct) DOL (Direct On Line) Compact NS100-630l-MA ........................................................... 311 Type de coordination: 1 Coordination type: 1 6.1.1.16. DOL (Démarrage direct) DOL (Direct On Line) Etoile / Triangle (Y/D) STAR / DELTA (Y/D) INTEGRAL ................................................................................... 353 Contacteurs-Disjoncteurs INTEGRALDOL (Démarrage direct) INTEGRAL contactors-circuit breakersDOL (Direct On Line) 6.1.1.26. INTEGRAL ................................................................................... 356 Contacteurs-Disjoncteurs INTEGRAL2 sens de marche INTEGRAL contactors-circuit breakersReverse 6.1.1.27. GV2-P .......................................................................................... 359 Type de coordination: 1 Coordination type: 1 6.1.1.28. GV2-P .......................................................................................... 359 Type de coordination: 2 Coordination type: 2 Guide Technique V9 / V9 Technical Guide DOL monophasé (Démarrage direct) Single phase - DOL (Direct On Line) DOL monophasé (Démarrage direct) Single phase - DOL (Direct On Line) 268 Sommaire du chapitre Chapter contents 6.1.1.29. Compact NS80H-MA .................................................................. 360 Type de coordination: 1 Coordination type: 1 6.1.1.30. DOL monophasé (Démarrage direct) Single phase - DOL (Direct On Line) Compact NS80H-MA .................................................................. 360 Type de coordination: 2 Coordination type: 2 DOL monophasé (Démarrage direct) Single phase - DOL (Direct On Line) 6.1.2. Déclassement des appareils - AC3 ....................................................... 361 Starters derating - AC3 6.1.2.1. GV2-P .......................................................................................... 361 Type de coordination: 1-2 Coordination type: 1-2 6.1.2.2. Compact NS et GV7 ................................................................... 362 Compact NS and GV7 Type de coordination: 1-2 Coordination type: 1-2 6.1.2.3. Integral ........................................................................................ 366 Contacteurs - Disjoncteurs IntegralCoordination totale Integral Contactors - Circuit breakersTotal coordination Guide Technique V9 / V9 Technical Guide 269 Anex 01 Appendix 01 6. Annex 01 Appendix 01 6.1 Blokset Mf / Mw Protection moteurs ancienne gamme Motor protection old range 6.1.1. Tableaux de coordination et modularité Coordination and modularity tables Blokset Type Mf et Mw Les GV7 peuvent être remplacés par les appareils NS100 / 250 associés à un déclencheur électronique protection moteur (à définir cas par cas). La modularité des associations avec NS + déclencheur est la même que celles définies avec les GV7. Guide Technique V9 / V9 Technical Guide Blokset Type Mf and Mw GV7 CB’s can be replaced by NS100 / 250 CB’s equipped with a electronic trip unit dedicated to motor protection (to be defined case per case). The number of modules of this kind of starter are the same than the ones given for GV7 CB’s. 270 Anex 01 Appendix 01 6.1.1.1. GV2-P Type de coordination: 1 - - - - - - - - - - - - - - - -DOL (Démarrage direct) Coordination type: 1 - - - - - - - - - - - - - - - - - - -DOL (Direct On Line) GV2-P 220/240 V Puissance moteur Power motor P (kW) I (A) 0,06 0,38 0,09 0,65 0,12 0,75 0,18 1,04 0,25 1,47 0,37 2 0,55 2,8 0,75 3,6 1,1 5,2 1,5 6,8 2,2 9,6 3 11,5 4 14,5 5,5 22 Pdc BC Icu (kA) Rms (kA) 50 50 50 50 50 50 50 50 50 50 50 50 50 50 Type de coordination: 1 Coordination type: 1 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV2-P03 0,25...0,40 GV2-P05 0,63...1 GV2-P05 0,63...1 GV2-P06 1...1,6 GV2-P06 1...1,6 GV2-P07 1,6...2,5 GV2-P08 2,5...4 GV2-P08 2,5...4 GV2-P10 4...6,3 GV2-P14 6...10 GV2-P16 9...14 GV2-P16 9...14 GV2-P20 13...18 GV2-P22 20...25 DOL (Démarrage direct) DOL (Direct On Line) Nb modules Nbr of modules Contacteur Contactor LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K09 LC1-D12 LC1-D12 LC1-D18 LC1-D25 Mf Mw 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Ancienne gamme Old range GV2-P 380 / 415V Puissance moteur Power motor P (kW) I (A) Pdc BC Icu (kA) Rms (kA) 50 50 50 50 50 50 Type de coordination: 1 Coordination type: 1 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV2-P02 0,16... 0,25 GV2-P03 0,25...0,40 GV2-P04 0,40... 0,63 GV2-P04 0,40... 0,63 GV2-P05 0,63...1 GV2-P06 1...1,6 Contacteur Contactor LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 3 3 3 3 3 DOL (Démarrage direct) DOL (Direct On Line) Nb modules Nbr of modules Mf Mw 0,06 0,22 0,09 0,36 3 3 3 3 0,12 0,42 0,18 0,6 3 3 3 0,25 0,88 3 0,37 0,98 0,55 1,5 50 GV2-P06 1...1,6 LC1-K06 3 0,75 2 50 GV2-P07 1,6...2,5 LC1-K06 3 3 1,1 2,5 50 GV2-P08 2,5...4 LC1-K06 3 3 1,5 3,5 50 GV2-P08 2,5...4 LC1-K06 3 3 2,2 5 50 GV2-P10 4...6,3 LC1-K06 3 3 3 6,5 50 GV2-P14 6...10 LC1-K09 3 3 4 8,4 50 GV2-P14 6...10 LC1-K09 3 3 5,5 11 15 GV2-P16 9...14 LC1-D12 3 3 7,5 14,8 15 GV2-P20 13...18 LC1-D18 3 3 9 18,1 15 GV2-P21 17...23 LC1-D25 3 3 11 21 15 GV2-P22 20...25 LC1-D25 3 3 Ancienne gamme Guide Technique V9 / V9 Technical Guide 271 Anex 01 Appendix 01 Old range GV2-P 440 V Puissance moteur Power motor P (kW) I (A) 0,06 0,19 0,09 0,28 0,12 0,37 0,18 0,55 0,25 0,76 0,37 0,99 0,55 1,36 0,75 1,68 1,1 2,37 1,5 3,06 2,2 4,42 3 5,77 4 7,9 5,5 10,4 7,5 13,7 9 16,9 11 20,1 Pdc BC Icu (kA) Rms (kA) 50 50 50 50 50 50 50 50 50 50 50 50 15 8 8 8 6 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV2-P02 0,16... 0,25 GV2-P03 0,25...0,40 GV2-P03 0,25...0,40 GV2-P04 0,40... 0,63 GV2-P05 0,63...1 GV2-P06 1...1,6 GV2-P06 1...1,6 GV2-P07 1,6...2,5 GV2-P07 1,6...2,5 GV2-P08 2,5...4 GV2-P10 4...6,3 GV2-P10 4...6,3 GV2-P14 6...10 GV2-P16 9...14 GV2-P20 13...18 GV2-P20 13...18 GV2-P21 17...23 Type de coordination: 1 Coordination type: 1 DOL (Démarrage direct) DOL (Direct On Line) Nb modules Nbr of modules Contacteur Contactor LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K09 LC1-D12 LC1-D18 LC1-D18 LC1-D25 Mf Mw 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Ancienne gamme Old range Guide Technique V9 / V9 Technical Guide 272 Anex 01 Appendix 01 6.1.1.2. GV2-P Type de coordination: 2 - - - - - - - - - - - - - - - -DOL (Démarrage direct) Coordination type: 2 - - - - - - - - - - - - - - - - - - -DOL (Direct On Line) GV2-P 220/240 V Puissance moteur Power motor P (kW) I (A) 0,06 0,38 0,09 0,65 0,12 0,75 0,18 1,04 0,25 1,47 0,37 2 0,55 2,8 0,75 3,6 1,1 5,2 1,5 6,8 2,2 9,6 3 11,5 4 14,5 5,5 22 Pdc BC Icu (kA) Rms (kA) 130 130 130 130 130 130 130 130 130 130 130 130 130 130 Type de coordination: 2 Coordination type: 2 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV2-P03 0,25...0,40 GV2-P05 0,63...1 GV2-P05 0,63...1 GV2-P06 1...1,6 GV2-P06 1...1,6 GV2-P07 1,6...2,5 GV2-P08 2,5...4 GV2-P08 2,5...4 GV2-P10 4...6,3 GV2-P14 6...10 GV2-P14 6...10 GV2-P16 9...14 GV2-P20 13...18 GV2-P22 20...25 DOL (Démarrage direct) DOL (Direct On Line) Nb modules Nbr of modules Contacteur Contactor LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D18 LC1-D18 LC1-D18 LC1-D25 Mf Mw 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Ancienne gamme Old range GV2-P 380 / 415V Puissance moteur Power motor P (kW) I (A) Type de coordination: 2 Coordination type: 2 0,06 0,22 0,09 0,36 0,12 0,42 0,18 0,6 0,25 0,88 0,37 0,98 Pdc BC Icu (kA) Rms (kA) 130 130 130 130 130 130 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV2-P02 0,16... 0,25 GV2-P03 0,25...0,40 GV2-P04 0,40... 0,63 GV2-P04 0,40... 0,63 GV2-P05 0,63...1 GV2-P05 0,63...1 Contacteur Contactor LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 0,55 1,5 130 GV2-P06 1...1,6 LC1-D09 3 3 0,75 2 130 GV2-P07 1,6...2,5 LC1-D09 3 3 1,1 2,5 130 GV2-P07 1,6...2,5 LC1-D09 3 3 1,5 3,5 130 GV2-P08 2,5...4 LC1-D18 3 3 2,2 5 130 GV2-P10 4...6,3 LC1-D18 3 3 3 6,5 130 GV2-P14 6...10 LC1-D18 3 3 4 8,4 130 GV2-P14 6...10 LC1-D18 3 3 5,5 11 130 GV2-P16 9...14 LC1-D25 3 3 7,5 14,8 50 GV2-P20 13...18 LC1-D25 3 3 9 18,1 50 GV2-P21 17...23 LC1-D25 3 3 11 21 50 GV2-P22 20...25 LC1-D25 3 3 DOL (Démarrage direct) DOL (Direct On Line) Nb modules Nbr of modules Mf Mw 3 3 3 3 3 3 3 3 3 3 3 3 Ancienne gamme Old range Guide Technique V9 / V9 Technical Guide 273 Anex 01 Appendix 01 GV2-P 440 V Puissance moteur Power motor P (kW) I (A) 0,06 0,19 0,09 0,28 0,12 0,37 0,18 0,55 0,25 0,76 0,37 0,99 0,55 1,36 0,75 1,68 1,1 2,37 1,5 3,06 2,2 4,42 3 5,77 4 7,9 5,5 10,4 7,5 13,7 9 16,9 11 20,1 Pdc BC Icu (kA) Rms (kA) 130 130 130 130 130 130 130 130 130 130 130 130 130 50 50 20 20 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV2-P02 0,16... 0,25 GV2-P03 0,25...0,40 GV2-P03 0,25...0,40 GV2-P04 0,40... 0,63 GV2-P05 0,63...1 GV2-P05 0,63...1 GV2-P06 1...1,6 GV2-P07 1,6...2,5 GV2-P07 1,6...2,5 GV2-P08 2,5 GV2-P10 4...6,3 GV2-P10 4...6,3 GV2-P14 6...10 GV2-P16 9...14 GV2-P16 9...14 GV2-P20 13...18 GV2-P21 17...23 Type de coordination: 2 Coordination type: 2 DOL (Démarrage direct) DOL (Direct On Line) Nb modules Nbr of modules Contacteur Contactor LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D18 LC1-D18 LC1-D18 LC1-D18 LC1-D25 LC1-D25 LC1-D25 LC1-D25 Mf Mw 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Ancienne gamme Old range Guide Technique V9 / V9 Technical Guide 274 Anex 01 Appendix 01 6.1.1.3. GV2-P Type de coordination: 1 - - - - - - - - - - - - - - - -2 sens de Marche Coordination type: 1 - - - - - - - - - - - - - - - - - - -Reverse GV2-P 220/240 V Puissance Moteur Power motor P (kW) I (A) 0,06 0,38 0,09 0,65 0,12 0,75 0,18 1,04 0,25 1,47 0,37 2 0,55 2,8 0,75 3,6 1,1 5,2 1,5 6,8 2,2 9,6 3 11,5 4 14,5 5,5 22 Pdc BC Icu (kA) Rms (kA) 85 85 85 85 85 85 85 85 85 85 85 85 85 85 Type de coordination: 1 Coordination type: 1 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV2-P03 0,25...0,40 GV2-P05 0,63...1 GV2-P05 0,63...1 GV2-P06 1...1,6 GV2-P06 1...1,6 GV2-P07 1,6...2,5 GV2-P08 2,5...4 GV2-P08 2,5...4 GV2-P10 4...6,3 GV2-P14 6...10 GV2-P16 9...14 GV2-P16 9...14 GV2-P20 13...18 GV2-P22 20...25 2 sens de Marche Reverse Nb modules Nbr of modules Contacteur Contactor 2 x LC1-K06 2 x LC1-K06 2 x LC1-K06 2 x LC1-K06 2 x LC1-K06 2 x LC1-K06 2 x LC1-K06 2 x LC1-K06 2 x LC1-K06 2 x LC1-K09 2 x LC1-D12 2 x LC1-D12 2 x LC1-D18 2 x LC1-D25 Mf Mw 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 6 3 Ancienne gamme Old range GV2-P 380/415 V Puissance Moteur Power motor P (kW) I (A) Pdc BC Icu (kA) Rms (kA) 85 85 85 85 85 85 Type de coordination: 1 Coordination type: 1 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV2-P02 0,16... 0,25 GV2-P03 0,25...0,40 GV2-P04 0,40... 0,63 GV2-P04 0,40... 0,63 GV2-P05 0,63...1 GV2-P06 1...1,6 2 sens de Marche Reverse Nb modules Nbr of modules Contacteur Contactor 2 x LC1-K06 2 x LC1-K06 2 x LC1-K06 2 x LC1-K06 2 x LC1-K06 2 x LC1-K06 Mf Mw 0,06 0,22 0,09 0,36 3 3 3 3 0,12 0,42 0,18 0,6 3 3 3 0,25 0,88 3 0,37 0,98 0,55 1,5 85 GV2-P06 1...1,6 2 x LC1-K06 3 3 0,75 2 85 GV2-P07 1,6...2,5 2 x LC1-K06 3 3 1,1 2,5 85 GV2-P08 2,5...4 2 x LC1-K06 3 3 1,5 3,5 85 GV2-P08 2,5...4 2 x LC1-K06 3 3 2,2 5 85 GV2-P10 4...6,3 2 x LC1-K06 3 3 3 6,5 85 GV2-P14 6...10 2 x LC1-K09 3 3 4 8,4 85 GV2-P14 6...10 2 x LC1-K09 3 3 5,5 11 85 GV2-P16 9...14 2 x LC1-D12 3 3 3 3 3 3 7,5 14,8 50 GV2-P20 13...18 2 x LC1-D18 3 3 9 18,1 50 GV2-P21 17...23 2 x LC1-D25 6 3 11 21 50 GV2-P22 20...25 2 x LC1-D25 6 3 Ancienne gamme Old range Guide Technique V9 / V9 Technical Guide 275 Anex 01 Appendix 01 GV2-P 440 V Puissance Moteur Power motor P (kW) I (A) 0,06 0,19 0,09 0,28 0,12 0,37 0,18 0,55 0,25 0,76 0,37 0,99 0,55 1,36 0,75 1,68 1,1 2,37 1,5 3,06 2,2 4,42 3 5,77 4 7,9 5,5 10,4 7,5 13,7 9 16,9 11 20,1 Pdc BC Icu (kA) Rms (kA) 85 85 85 85 85 85 85 85 85 85 85 85 85 50 20 20 20 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV2-P02 0,16... 0,25 GV2-P03 0,25...0,40 GV2-P03 0,25...0,40 GV2-P04 0,40... 0,63 GV2-P05 0,63...1 GV2-P05 0,63...1 GV2-P06 1...1,6 GV2-P07 1,6...2,5 GV2-P07 1,6...2,5 GV2-P08 2,5...4 GV2-P10 4...6,3 GV2-P10 4...6,3 GV2-P14 6...10 GV2-P16 9...14 GV2-P20 13...18 GV2-P20 13...18 GV2-P21 17...23 Type de coordination: 1 Coordination type: 1 2 sens de Marche Reverse Nb modules Nbr of modules Contacteur Contactor 2 x LC1-K06 2 x LC1-K06 2 x LC1-K06 2 x LC1-K06 2 x LC1-K06 2 x LC1-K06 2 x LC1-K06 2 x LC1-K06 2 x LC1-K06 2 x LC1-K06 2 x LC1-K06 2 x LC1-K06 2 x LC1-K09 2 x LC1-D12 2 x LC1-D18 2 x LC1-D18 2 x LC1-D25 Mf Mw 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 6 3 Ancienne gamme Old range Guide Technique V9 / V9 Technical Guide 276 Anex 01 Appendix 01 6.1.1.4. GV2-P Type de coordination: 2 - - - - - - - - - - - - - - - -2 sens de Marche Coordination type: 2 - - - - - - - - - - - - - - - - - - -Reverse GV2-P 220/240 V Puissance Moteur Power motor P (kW) I (A) 0,06 0,38 0,09 0,65 0,12 0,75 0,18 1,04 0,25 1,47 0,37 2 0,55 2,8 0,75 3,6 1,1 5,2 1,5 6,8 2,2 9,6 3 11,5 4 14,5 5,5 22 Pdc BC Icu (kA) Rms (kA) 85 85 85 85 85 85 85 85 85 85 85 85 85 85 Type de coordination: 2 Coordination type: 2 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV2-P03 0,25...0,40 GV2-P05 0,63...1 GV2-P05 0,63...1 GV2-P06 1...1,6 GV2-P06 1...1,6 GV2-P07 1,6...2,5 GV2-P08 2,5...4 GV2-P08 2,5...4 GV2-P10 4...6,3 GV2-P14 6...10 GV2-P14 6...10 GV2-P16 9...14 GV2-P20 13...18 GV2-P22 20...25 2 sens de Marche Reverse Nb modules Nbr of modules Contacteur Contactor 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D18 2 x LC1-D18 2 x LC1-D18 2 x LC1-D25 Mf Mw 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 6 3 Ancienne gamme Old range GV2-P 380/415 V Puissance Moteur Power motor P (kW) I (A) Type de coordination: 2 Coordination type: 2 0,06 0,22 0,09 0,36 0,12 0,42 0,18 0,6 0,25 0,88 0,37 0,98 Pdc BC Icu (kA) Rms (kA) 85 85 85 85 85 85 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV2-P02 0,16... 0,25 GV2-P03 0,25...0,40 GV2-P04 0,40... 0,63 GV2-P04 0,40... 0,63 GV2-P05 0,63...1 GV2-P05 0,63...1 Contacteur Contactor 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 Mf Mw 3 3 3 3 3 3 3 3 3 3 3 0,55 1,5 85 GV2-P06 1...1,6 2 x LC1-D09 3 3 3 0,75 2 85 GV2-P07 1,6...2,5 2 x LC1-D09 3 3 1,1 2,5 85 GV2-P07 1,6...2,5 2 x LC1-D09 3 3 1,5 3,5 85 GV2-P08 2,5...4 2 x LC1-D18 3 3 2,2 5 85 GV2-P10 4...6,3 2 x LC1-D18 3 3 3 6,5 85 GV2-P14 6...10 2 x LC1-D18 3 3 4 8,4 85 GV2-P14 6...10 2 x LC1-D18 3 3 5,5 11 85 GV2-P16 9...14 2 x LC1-D25 6 3 7,5 14,8 50 GV2-P20 13...18 2 x LC1-D25 6 3 9 18,1 50 GV2-P21 17...23 2 x LC1-D25 6 3 11 21 50 GV2-P22 20...25 2 x LC1-D25 6 3 2 sens de Marche Reverse Nb modules Nbr of modules Ancienne gamme Old range Guide Technique V9 / V9 Technical Guide 277 Anex 01 Appendix 01 GV2-P 440 V Puissance Moteur Power motor P (kW) I (A) 0,06 0,19 0,09 0,28 0,12 0,37 0,18 0,55 0,25 0,76 0,37 0,99 0,55 1,36 0,75 1,68 1,1 2,37 1,5 3,06 2,2 4,42 3 5,77 4 7,9 5,5 10,4 7,5 13,7 9 16,9 11 20,1 Pdc BC Icu (kA) Rms (kA) 85 85 85 85 85 85 85 85 85 85 85 85 85 50 50 20 20 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV2-P02 0,16... 0,25 GV2-P03 0,25...0,40 GV2-P03 0,25...0,40 GV2-P04 0,40... 0,63 GV2-P05 0,63...1 GV2-P05 0,63...1 GV2-P06 1...1,6 GV2-P07 1,6...2,5 GV2-P07 1,6...2,5 GV2-P08 2,5...4 GV2-P10 4...6,3 GV2-P10 4...6,3 GV2-P14 6...10 GV2-P16 9...14 GV2-P16 9...14 GV2-P20 13...18 GV2-P21 17...23 Type de coordination: 2 Coordination type: 2 2 sens de Marche Reverse Nb modules Nbr of modules Contacteur Contactor 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D18 2 x LC1-D18 2 x LC1-D18 2 x LC1-D25 2 x LC1-D25 2 x LC1-D25 2 x LC1-D25 Mf Mw 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 6 3 6 3 6 3 6 3 Ancienne gamme Old range Guide Technique V9 / V9 Technical Guide 278 Anex 01 Appendix 01 6.1.1.5. GV2-P Type de coordination: 1 - - - - - - - - - - - - - - - -Etoile / Triangle (Y/∆) Coordination type: 1 - - - - - - - - - - - - - - - - - - -STAR / DELTA (Y/∆) GV2-P 220/240 V Puissance Moteur Power motor P (kW) I (A) 1,5 6,8 2,2 9,6 3 11,5 4 14,5 5,5 22 Pdc BC Icu (kA) Rms (kA) 85 85 85 85 85 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV2-P14 6...10 GV2-P16 9...14 GV2-P16 9...14 GV2-P20 13...18 GV2-P22 20...25 Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Type de coordination: 1 Coordination type: 1 Nb modules Nbr of modules Contacteur Contactor 3 x LC1-K06 3 x LC1-K06 3 x LC1-K06 3 x LC1-D09 3 x LC1-D12 Mf Mw 6 6 6 6 6 6 6 6 6 6 Ancienne gamme Old range GV2-P 380/415 V Puissance Moteur Power motor P (kW) I (A) 1,5 3,5 2,2 5 3 6,5 4 8,4 5,5 11 7,5 14,8 9 18,1 11 21 Pdc BC Icu (kA) Rms (kA) 85 85 85 85 85 50 50 50 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV2-P08 2,5...4 GV2-P10 4...6,3 GV2-P14 6...10 GV2-P14 6...10 GV2-P16 9...14 GV2-P20 13...18 GV2-P21 17...23 GV2-P22 20...25 Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Type de coordination: 1 Coordination type: 1 Nb modules Nbr of modules Contacteur Contactor 3 x LC1-K06 3 x LC1-K06 3 x LC1-K06 3 x LC1-K06 3 x LC1-K06 3 x LC1-D09 3 x LC1-D12 3 x LC1-D12 Mf Mw 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 Ancienne gamme Old range GV2-P 440 V Puissance Moteur Power motor P (kW) I (A) 1,5 3,06 2,2 4,42 3 5,77 4 7,9 5,5 10,4 7,5 13,7 9 16,9 11 20,1 Pdc BC Icu (kA) Rms (kA) 85 85 85 85 50 20 20 20 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV2-P08 2,5...4 GV2-P10 4...6,3 GV2-P10 4...6,3 GV2-P14 6...10 GV2-P16 9...14 GV2-P20 13...18 GV2-P20 13...18 GV2-P21 17...23 Type de coordination: 1 Coordination type: 1 Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Nb modules Nbr of modules Contacteur Contactor 3 x LC1-K06 3 x LC1-K06 3 x LC1-K06 3 x LC1-K06 3 x LC1-K06 3 x LC1-D09 3 x LC1-D12 3 x LC1-D12 Mf Mw 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 Ancienne gamme Old range Guide Technique V9 / V9 Technical Guide 279 Anex 01 Appendix 01 6.1.1.6. GV2-P Type de coordination: 2 - - - - - - - - - - - - - - - -Etoile / Triangle (Y/∆) Coordination type: 2 - - - - - - - - - - - - - - - - - - -STAR / DELTA (Y/∆) GV2-P 220/240 V Puissance Moteur Power motor P (kW) I (A) 1,5 6,8 2,2 9,6 3 11,5 4 14,5 5,5 22 Pdc BC Icu (kA) Rms (kA) 85 85 85 85 85 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV2-P14 6...10 GV2-P14 6...10 GV2-P16 9...14 GV2-P20 13...18 GV2-P22 20...25 Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Type de coordination: 2 Coordination type: 2 Nb modules Nbr of modules Contacteur Contactor 3 x LC1-D09 3 x LC1-D18 3 x LC1-D18 3 x LC1-D18 3 x LC1-D25 Mf Mw 6 6 6 6 6 6 6 6 6 6 Ancienne gamme Old range GV2-P 380/415 V Puissance Moteur Power motor P (kW) I (A) 1,5 3,5 2,2 5 3 6,5 4 8,4 5,5 11 7,5 14,8 9 18,1 11 21 Pdc BC Icu (kA) Rms (kA) 85 85 85 85 85 50 50 50 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV2-P08 2,5...4 GV2-P10 4...6,3 GV2-P14 6...10 GV2-P14 6...10 GV2-P16 9...14 GV2-P20 13...18 GV2-P21 17...23 GV2-P22 20...25 Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Type de coordination: 2 Coordination type: 2 Nb modules Nbr of modules Contacteur Contactor 3 x LC1-D09 3 x LC1-D18 3 x LC1-D18 3 x LC1-D18 3 x LC1-D25 3 x LC1-D25 3 x LC1-D25 3 x LC1-D25 Mf Mw 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 Ancienne gamme Old range GV2-P 440 V Puissance Moteur Power motor P (kW) I (A) 1,5 3,06 2,2 4,42 3 5,77 4 7,9 5,5 10,4 7,5 13,7 9 16,9 11 20,1 Pdc BC Icu (kA) Rms (kA) 85 85 85 85 50 50 20 20 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV2-P08 2,5...4 GV2-P10 4...6,3 GV2-P10 4...6,3 GV2-P14 6...10 GV2-P16 9...14 GV2-P16 9...14 GV2-P20 13...18 GV2-P21 17...23 Type de coordination: 2 Coordination type: 2 Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Nb modules Nbr of modules Contacteur Contactor 3 x LC1-D09 3 x LC1-D18 3 x LC1-D18 3 x LC1-D18 3 x LC1-D25 3 x LC1-D25 3 x LC1-D25 3 x LC1-D25 Mf Mw 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 Ancienne gamme Old range Guide Technique V9 / V9 Technical Guide 280 Anex 01 Appendix 01 Compact NS80H-MA 6.1.1.7. Type de coordination: 1 - - - - - - - - - - - - - - - -DOL (Démarrage direct) Coordination type: 1 - - - - - - - - - - - - - - - - - - -DOL (Direct On Line) Démarrage: Normal Start-up: Normal Compact NS80H-MA 220/230 V Puissance Moteur Power motor P (kW) I (A) 0,37 1,8 0,55 2,8 1,1 4,4 1,5 6,1 2,2 8,7 3 11,5 4 14,5 5,5 20 7,5 28 11 39 15 52 18,5 64 22 75 Pdc BC Icu (kA) Rms (kA) 100 100 100 100 100 100 100 100 100 100 100 100 100 Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA Cal (A) Rat (A) 2,5 6,3 6,3 12,5 12,5 12,5 25 25 50 50 50 80 80 Type de coordination: 1 Coordination type: 1 Contacteurs Contactor Type Type LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D12 LC1-D18 LC1-D25 LC1-D32 LC1-D40 LC1-D50 LC1-D65 LC1-D80 DOL (Démarrage direct) DOL (Direct On Line) Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D1322 17...25 LR2-D3353 23...32 LR2-D3357 37...50 LR2-D3359 48...65 LR2-D3359 48...65 LR2-D3363 63...80 Nb modules Nbr of modules Mf Mw 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 6 3 6 3 6 3 6 3 6 Ancienne gamme Old range Compact NS80H-MA 380 V Puissance Moteur Power motor P (kW) I (A) Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA Type de coordination: 1 Coordination type: 1 DOL (Démarrage direct) DOL (Direct On Line) 0,37 1,2 0,55 1,6 0,75 2 Pdc BC Icu (kA) Rms (kA) 70 70 70 Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1306 1...1,6 LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 Nb modules Nbr of modules Cal (A) Rat (A) 2,5 2,5 2,5 Contacteurs Contactor Type Type LC1-D09 LC1-D09 LC1-D09 3 1,1 2,8 70 NS80H-MA 6,3 LC1-D09 LR2-D1308 2,5...4 3 3 3 1,5 3,7 70 NS80H-MA 6,3 LC1-D09 LR2-D1308 2,5...4 3 3 2,2 5 70 NS80H-MA 6,3 LC1-D09 LR2-D1310 4...6 3 3 3 6,6 70 NS80H-MA 12,5 LC1-D09 LR2-D1312 5,5...8 3 3 4 8,5 70 NS80H-MA 12,5 LC1-D09 LR2-D1314 7...10 3 3 5,5 11,5 70 NS80H-MA 12,5 LC1-D12 LR2-D1316 9...13 3 3 7,5 15,5 70 NS80H-MA 25 LC1-D18 LR2-D1321 12...18 3 3 11 22 70 NS80H-MA 25 LC1-D25 LR2-D1322 17...25 3 3 15 30 70 NS80H-MA 50 LC1-D32 LR2-D3353 23...32 3 6 18,5 37 70 NS80H-MA 50 LC1-D40 LR2-D3357 37...50 3 6 22 44 70 NS80H-MA 50 LC1-D50 LR2-D3357 37...50 3 6 30 59 70 NS80H-MA 80 LC1-D65 LR2-D3359 48...65 3 6 37 72 70 NS80H-MA 80 LC1-D80 LR2-D3363 63...80 3 6 Mf Mw 3 3 3 3 Ancienne gamme Old range Guide Technique V9 / V9 Technical Guide 281 Anex 01 Appendix 01 Compact NS80H-MA 400/415 V Puissance Moteur Power motor P (kW) I (A) 0,37 1,1 0,55 1,5 0,75 1,8 1,1 2,5 1,5 3,5 2,2 4,8 3 6,5 4 8,2 5,5 11 7,5 14 9 17 11 21 15 28 22 40 25 47 30 55 37 66 45 80 Pdc BC Icu (kA) Rms (kA) 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA Cal (A) Rat (A) 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 12,5 25 25 25 50 50 50 80 80 80 Type de coordination: 1 Coordination type: 1 Contacteurs Contactor Type Type LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D12 LC1-D18 LC1-D18 LC1-D25 LC1-D32 LC1-D40 LC1-D50 LC1-D65 LC1-D65 LC1-D80 DOL (Démarrage direct) DOL (Direct On Line) Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1306 1...1,6 LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D1321 12...18 LR2-D1322 17...25 LR2-D3353 23...32 LR2-D3357 37...50 LR2-D3357 37...50 LR2-D3359 48...65 LR2-D3361 55...70 LR2-D3363 63...80 Nb modules Nbr of modules Mf Mw 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 6 3 6 3 6 3 6 3 6 3 6 Ancienne gamme Old range 440 V (1) Puissance Moteur Power motor P (kW) I (A) 0,37 1 0,55 1,4 0,75 1,7 1,1 2,4 1,5 3,1 2,2 4,5 3 5,8 4 7,9 5,5 10,4 7,5 13,7 9 16,9 11 20,1 15 26,5 22 39 30 51,5 37 64 45 76 Compact NS80H-MA Pdc BC Icu (kA) Rms (kA) 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA Cal (A) Rat (A) 2,5 2,5 2,5 2,5 6,3 6,3 12,5 12,5 12,5 25 25 25 50 50 50 80 80 Type de coordination: 1 Coordination type: 1 Contacteurs Contactor Type Type LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D12 LC1-D18 LC1-D18 LC1-D25 LC1-D32 LC1-D40 LC1-D50 LC1-D65 LC1-D80 Ancienne gamme Old range (1) Applicable pour 480 V NEMA Guide Technique V9 / V9 Technical Guide DOL (Démarrage direct) DOL (Direct On Line) Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1306 1...1,6 LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D1321 12...18 LR2-D1322 17...25 LR2-D3353 23...32 LR2-D3357 37...50 LR2-D3359 48...65 LR2-D3359 48...65 LR2-D3363 63...80 Nb modules Nbr of modules Mf Mw 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 6 3 6 3 6 3 6 3 6 (1) Valid for 480 V NEMA 282 Anex 01 Appendix 01 Compact NS80H-MA 500/525 V Puissance Moteur Power motor P (kW) I (A) 0,55 1,2 0,75 1,5 1,1 2 1,5 2,6 3 5 4 6,5 5,5 9 7,5 12 9 14 10 15 11 18,4 18,5 28,5 22 33 30 45 37 55 55 80 Pdc BC Icu (kA) Rms (kA) 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA Cal (A) Rat (A) 2,5 2,5 2,5 6,3 6,3 12,5 12,5 12,5 25 25 25 50 50 50 80 80 Type de coordination: 1 Coordination type: 1 Contacteurs Contactor Type Type LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D12 LC1-D18 LC1-D18 LC1-D25 LC1-D32 LC1-D40 LC1-D50 LC1-D65 LC1-D80 DOL (Démarrage direct) DOL (Direct On Line) Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1306 1...1,6 LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D1321 12...18 LR2-D1322 17...25 LR2-D3353 23...32 LR2-D355 30...40 LR2-D3357 37...50 LR2-D3359 48...65 LR2-D3363 63...80 Nb modules Nbr of modules Mf Mw 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 6 3 6 3 6 3 6 3 6 Ancienne gamme Old range Guide Technique V9 / V9 Technical Guide 283 Anex 01 Appendix 01 Compact NS80H-MA 6.1.1.8. Type de coordination: 2 - - - - - - - - - - - - - - - -DOL (Démarrage direct) Coordination type: 2 - - - - - - - - - - - - - - - - - - -DOL (Direct On Line) Démarrage: Normal Start-up: Normal Compact NS80H-MA 220/230 V Puissance Moteur Power motor P (kW) I (A) 0,09 0,7 0,12 0,9 0,18 1,2 0,25 1,5 0,37 2 0,55 2,8 0,75 3,5 1,1 5 1,5 6,5 2,2 9 3 12 4 15 5,5 21 6,3 24 7,5 28 - - 10 36 - - 11 39 - - 15 52 - - 18.5 63 - - 22 75 - - Pdc BC Icu (kA) Rms (kA) 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA - Cal (A) Rat (A) 1,5 1,5 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 12,5 25 25 25 50 50 50 80 80 80 - Type de coordination: 2 Coordination type: 2 Contacteurs Contactor Type Type LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D18 LC1-D18 LC1-D25 LC1-D32 LC1-D32 LC1-D32 LC1-D32 LC1-D40 LC1-D40 LC1-D40 LC1 D80 LC1-D50 LC1 D80 LC1-D50 LC1 D80 LC1-D65 LC1 D80 LC1-D65 LC1 D80 LC1-D80 LC1 D80 DOL (Démarrage direct) DOL (Direct On Line) Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1305 0,63...1 LR2-D1305 0,63...1 LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D3322 17...25 LR2-D3322 17...25 LR2-D3353 23...32 LR9-D5357 30...50 LR2-D3355 30...40 LR9-D5357 30...50 LR2-D3357 37...50 LR9-D5357 30...50 LR2-D3359 48...65 LR9-D5363 48...80 LR2-D3359 48...65 LR9-D5363 48...80 LR2-D3363 63...80 LR9-D5363 48...80 Nb modules Nbr of modules Mf Mw 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 6 3 6 3 6 3 9 3 6 3 9 3 6 3 9 3 6 3 9 3 6 3 9 3 6 3 9 Ancienne gamme Old range Guide Technique V9 / V9 Technical Guide 284 Anex 01 Appendix 01 Compact NS80H-MA 380/415 V Puissance Moteur Power motor P (kW) I (A) 0,18 0,7 0,25 0,9 0,37 1,2 0,55 1,6 0,75 2 1,1 2,8 1,5 3,7 2,2 5,3 3 7 4 9 5,5 12 7,5 16 10 21 11 23 15 30 - - 18,5 37 - - 22 43 - - 30 59 - - 37 72 - - Pdc BC Icu (kA) Rms (kA) 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 - Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA - Cal (A) Rat (A) 1,5 1,5 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 12,5 25 25 25 50 50 50 80 80 - Type de coordination: 2 Coordination type: 2 Contacteurs Contactor Type Type LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D18 LC1-D18 LC1-D25 LC1-D32 LC1-D32 LC1-D32 LC1-D32 LC1-D40 LC1-D40 LC1-D40 LC1 D80 LC1-D50 LC1 D80 LC1-D50 LC1 D80 LC1-D65 LC1 D80 LC1 D80 LC1 D80 DOL (Démarrage direct) DOL (Direct On Line) Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1305 0,63...1 LR2-D1305 0,63...1 LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D3322 17...25 LR2-D3322 17...25 LR2-D3353 23...32 LR9-D5357 30...50 LR2-D3355 30...40 LR9-D5357 30...50 LR2-D3357 37...50 LR9-D5357 30...50 LR2-D3359 48...65 LR9-D5363 48...80 LR2-D3363 63...80 LR9-D5363 48...80 Nb modules Nbr of modules Mf Mw 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 6 3 6 3 6 3 9 3 6 3 9 3 6 3 9 3 6 3 9 3 6 3 9 Ancienne gamme Old range Guide Technique V9 / V9 Technical Guide 285 Anex 01 Appendix 01 440 V (1) Puissance Moteur Power motor P (kW) I (A) 0,25 0,7 0,37 1 0,55 1,4 0,75 1,7 1,1 2,4 1,5 3,1 2,2 4,5 3 5,8 4 8 5,5 10,5 7,5 13,7 10 19 11 20 15 26,5 18,5 33 - - 22 39 - - 30 52 - - 37 63 - - 45 76 - - Compact NS80H-MA Pdc BC Icu (kA) Rms (kA) 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 - Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA - Cal (A) Rat (A) 1,5 2,5 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 25 25 25 50 50 50 80 80 80 - Type de coordination: 2 Coordination type: 2 Contacteurs Contactor Type Type LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D18 LC1-D25 LC1-D25 LC1-D32 LC1-D32 LC1-D32 LC1-D40 LC1-D40 LC1-D40 LC1-D50 LC1 D80 LC1-D50 LC1 D80 LC1-D65 LC1 D80 LC1-D65 LC1 D80 LC1-D80 LC1 D80 DOL (Démarrage direct) DOL (Direct On Line) Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1305 0,63...1 LR2-D1306 1...1,6 LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D3322 17...25 LR2-D3322 17...25 LR2-D3353 23...32 LR2-D3355 30...40 LR9-D5357 30...50 LR2-D3355 30...40 LR9-D5357 30...50 LR2-D3359 48...65 LR9-D5363 48...80 LR2-D3359 48...65 LR9-D5363 48...80 LR2-D3363 63...80 LR9-D5363 48...80 Nb modules Nbr of modules Mf Mw 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 6 3 6 3 6 3 6 3 9 3 6 3 9 3 6 3 9 3 6 3 9 3 6 3 9 Ancienne gamme Old range (1) Applicable pour 480 V NEMA (1) Valid for 480 V NEMA 500/525 V Puissance Moteur Power motor P (kW) I (A) 0,25 0,6 0,37 0,9 0,55 1,2 0,75 1,5 1,1 2,0 1,5 2,8 2,2 3,8 3 5 4 6,5 5,5 9 7,5 12 10 15 11 18,4 15 23 18,5 28,5 22 33 - - Compact NS80H-MA Pdc BC Icu (kA) Rms (kA) 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 - Guide Technique V9 / V9 Technical Guide Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA - Cal (A) Rat (A) 1,5 1,5 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 12,5 25 25 25 50 50 - Type de coordination: 2 Coordination type: 2 Contacteurs Contactor Type Type LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D18 LC1-D18 LC1-D25 LC1-D32 LC1-D32 LC1-D32 LC1-D32 LC1-D40 LC1-D40 LC1-D40 LC1-D50 LC1-D115 DOL (Démarrage direct) DOL (Direct On Line) Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1305 0,63...1 LR2-D1305 0,63...1 LR2-D1306 1...1,6 LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D3321 12...18 LR2-D3322 17...25 LR2-D3322 17...25 LR2-D3353 23...32 LR2-D3355 30...40 LR9-D5357 30...50 Nb modules Nbr of modules Mf Mw 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 6 3 6 3 6 3 6 6 9 286 Anex 01 Appendix 01 Compact NS80H-MA 500/525 V Puissance Moteur Power motor P (kW) I (A) - - 30 45 - - - - 37 55 - - - - 45 65 - - 55 75 - - Pdc BC Icu (kA) Rms (kA) 25 25 25 25 - Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA - Cal (A) Rat (A) 50 80 80 80 - Type de coordination: 2 Coordination type: 2 Contacteurs Contactor Type Type LC1-F115 LC1-D50 LC1-D115 LC1-F115 LC1-D65 LC1-D115 LC1-F115 LC1-D115 LC1-F115 LC1-D115 LC1-F115 DOL (Démarrage direct) DOL (Direct On Line) Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR9-F5357 30...50 LR2-D3357 37...50 LR9-D5357 30...50 LR9-F5357 30...50 LR2-D3359 48...65 LR9-D5363 48...80 LR9-F5363 48...80 LR9-D3363 63...80 LR9-D5363 48...80 LR9-F5363 48...80 LR9-D5363 48...80 Nb modules Nbr of modules Mf Mw 6 9 3 6 6 9 6 9 3 6 6 9 6 9 6 9 6 9 6 9 6 9 Ancienne gamme Old range Guide Technique V9 / V9 Technical Guide 287 Anex 01 Appendix 01 Compact NS80H-MA 6.1.1.9. Type de coordination: 1 - - - - - - - - - - - - - - - -2 sens de marche Coordination type: 1 - - - - - - - - - - - - - - - - - - -Reverse Démarrage: Normal Start-up: Normal Compact NS80H-MA 220/230 V Puissance Moteur Power motor P (kW) I (A) 0,37 1,8 0,55 2,8 1,1 4,4 1,5 6,1 2,2 8,7 3 11,5 4 14,5 5,5 20 7,5 28 11 39 15 52 18,5 64 22 75 Pdc BC Icu (kA) Rms (kA) 100 100 100 100 100 100 100 100 100 100 100 100 100 Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA Cal (A) Rat (A) 2,5 6,3 6,3 12,5 12,5 12,5 25 25 50 50 50 80 80 Type de coordination: 1 Coordination type: 1 Contacteurs Contactor Type Type 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D12 2 x LC1-D18 2 x LC1-D25 2 x LC1-D32 2 x LC1-D40 2 x LC1-D50 2 x LC1-D65 2 x LC1-D80 2 sens de marche Reverse Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D1322 17...25 LR2-D3353 23...32 LR2-D3357 37...50 LR2-D3359 48...65 LR2-D3359 48...65 LR2-D3363 63...80 Nb modules Nbr of modules Mf Mw 3 6 3 6 3 6 3 6 3 6 3 6 3 6 6 6 6 6 6 9 6 9 6 9 6 9 Ancienne gamme Old range Compact NS80H-MA 380 V Puissance Moteur Power motor P (kW) I (A) Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA Type de coordination: 1 Coordination type: 1 2 sens de marche Reverse 0,37 1,2 0,55 1,6 0,75 2 Pdc BC Icu (kA) Rms (kA) 70 70 70 Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1306 1...1,6 LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 Nb modules Nbr of modules Cal (A) Rat (A) 2,5 2,5 2,5 Contacteurs Contactor Type Type 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 3 1,1 2,8 70 NS80H-MA 6,3 2 x LC1-D09 LR2-D1308 2,5...4 3 6 6 1,5 3,7 70 NS80H-MA 6,3 2 x LC1-D09 LR2-D1308 2,5...4 3 6 2,2 5 70 NS80H-MA 6,3 2 x LC1-D09 LR2-D1310 4...6 3 6 3 6,6 70 NS80H-MA 12,5 2 x LC1-D09 LR2-D1312 5,5...8 3 6 4 8,5 70 NS80H-MA 12,5 2 x LC1-D09 LR2-D1314 7...10 3 6 5,5 11,5 70 NS80H-MA 12,5 2 x LC1-D12 LR2-D1316 9...13 3 6 7,5 15,5 70 NS80H-MA 25 2 x LC1-D18 LR2-D1321 12...18 3 6 11 22 70 NS80H-MA 25 2 x LC1-D25 LR2-D1322 17...25 6 6 15 30 70 NS80H-MA 50 2 x LC1-D32 LR2-D3353 23...32 6 6 18,5 37 70 NS80H-MA 50 2 x LC1-D40 LR2-D3357 37...50 6 9 22 44 70 NS80H-MA 50 2 x LC1-D50 LR2-D3357 37...50 6 9 30 59 70 NS80H-MA 80 2 x LC1-D65 LR2-D3359 48...65 6 9 37 72 70 NS80H-MA 80 2 x LC1-D80 LR2-D3363 63...80 6 9 Mf Mw 3 6 3 6 Ancienne gamme Old range Guide Technique V9 / V9 Technical Guide 288 Anex 01 Appendix 01 Compact NS80H-MA 415 V Puissance Moteur Power motor P (kW) I (A) 0,37 1,1 0,55 1,5 0,75 1,8 1,1 2,5 1,5 3,5 2,2 4,8 3 6,5 4 8,2 5,5 11 7,5 14 9 17 11 21 15 28 22 40 25 47 30 55 37 66 45 80 Pdc BC Icu (kA) Rms (kA) 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA Cal (A) Rat (A) 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 12,5 25 25 25 50 50 50 80 80 80 Type de coordination: 1 Coordination type: 1 Contacteurs Contactor Type Type 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D12 2 x LC1-D18 2 x LC1-D18 2 x LC1-D25 2 x LC1-D32 2 x LC1-D40 2 x LC1-D50 2 x LC1-D65 2 x LC1-D65 2 x LC1-D80 2 sens de marche Reverse Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1306 1...1,6 LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D1321 12...18 LR2-D1322 17...25 LR2-D3353 23...32 LR2-D3357 37...50 LR2-D3357 37...50 LR2-D3359 48...65 LR2-D3361 55...70 LR2-D3363 63...80 Nb modules Nbr of modules Mf Mw 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 6 6 6 6 6 9 6 9 6 9 6 9 6 9 Ancienne gamme Old range 440 V (1) Puissance Moteur Power motor P (kW) I (A) 0,37 1 0,55 1,4 0,75 1,7 1,1 2,4 1,5 3,1 2,2 4,5 3 5,8 4 7,9 5,5 10,4 7,5 13,7 9 16,9 11 20,1 15 26,5 22 39 30 51,5 37 64 45 76 Compact NS80H-MA Pdc BC Icu (kA) Rms (kA) 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA Cal (A) Rat (A) 2,5 2,5 2,5 2,5 6,3 6,3 12,5 12,5 12,5 25 25 25 50 50 50 80 80 Type de coordination: 1 Coordination type: 1 Contacteurs Contactor Type Type 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D12 2 x LC1-D18 2 x LC1-D18 2 x LC1-D25 2 x LC1-D32 2 x LC1-D40 2 x LC1-D50 2 x LC1-D65 2 x LC1-D80 Ancienne gamme Old range (1) Applicable pour 480 V NEMA Guide Technique V9 / V9 Technical Guide 2 sens de marche Reverse Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1306 1...1,6 LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D1321 12...18 LR2-D1322 17...25 LR2-D3353 23...32 LR2-D3357 37...50 LR2-D3359 48...65 LR2-D3359 48...65 LR2-D3363 63...80 Nb modules Nbr of modules Mf Mw 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 6 6 6 6 6 9 6 9 6 9 6 9 (1) Valid for 480 V NEMA 289 Anex 01 Appendix 01 Compact NS80H-MA 500/525 V Puissance Moteur Power motor P (kW) I (A) 0,55 1,2 0,75 1,5 1,1 2 1,5 2,6 3 5 4 6,5 5,5 9 7,5 12 9 14 10 15 11 18,4 18,5 28,5 22 33 30 45 37 55 55 80 Pdc BC Icu (kA) Rms (kA) 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA Cal (A) Rat (A) 2,5 2,5 2,5 6,3 6,3 12,5 12,5 12,5 25 25 25 50 50 50 80 80 Type de coordination: 1 Coordination type: 1 Contacteurs Contactor Type Type 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D12 2 x LC1-D18 2 x LC1-D18 2 x LC1-D25 2 x LC1-D32 2 x LC1-D40 2 x LC1-D50 2 x LC1-D65 2 x LC1-D80 2 sens de marche Reverse Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1306 1...1,6 LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D1321 12...18 LR2-D1322 17...25 LR2-D3353 23...32 LR2-D3355 30...40 LR2-D3357 37...50 LR2-D3359 48...65 LR2-D3363 63...80 Nb modules Nbr of modules Mf Mw 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 6 6 6 6 6 9 6 9 6 9 6 9 Ancienne gamme Old range 660/690 V (1) Puissance Moteur Power motor P (kW) I (A) 0,75 1,2 1 1,5 1,5 2 2,2 2,8 3 3,8 4 4,9 5,5 6,6 7,5 8,9 10 11,5 15 17 18,5 21,3 30 34,6 33 39 37 42 45 49 55 60 75 80 Compact NS80H-MA Pdc BC Icu (kA) Rms (kA) 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA Cal (A) Rat (A) 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 25 25 50 50 50 50 80 80 80 Type de coordination: 1 Coordination type: 1 Contacteurs Contactor Type Type 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D12 2 x LC1-D18 2 x LC1-D25 2 x LC1-D32 2 x LC1-D40 2 x LC1-D50 2 x LC1-D65 2 x LC1-D80 2 x LC1-D115 2 x LC1-F115 Ancienne gamme Old range (1) Confirmer le nb de modules pour 660/690 V ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide 2 sens de marche Reverse Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1306 1...1,6 LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D1322 17...25 LR2-D3355 30...40 LR2-D3357 37...50 LR2-D3357 37...50 LR2-D3357 37...50 LR9-D5363 48...80 LR9-F5363 48...80 Nb modules Nbr of modules Mf Mw 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 6 6 6 6 6 9 6 9 6 9 6 9 9 12 9 ** (1) Confirm number of modules in function of this voltage level 660/690 V ** Impossible in Mw type 290 Anex 01 Appendix 01 Compact NS80H-MA 6.1.1.10. Type de coordination: 2 - - - - - - - - - - - - - - - -2 sens de marche Coordination type: 2 - - - - - - - - - - - - - - - - - - -Reverse Démarrage: Normal Start-up: Normal Compact NS80H-MA 220/230 V Puissance Moteur Power motor P (kW) I (A) 0,09 0,7 0,12 0,9 0,18 1,2 0,25 1,5 0,37 2 0,55 2,8 0,75 3,5 1,1 5 1,5 6,5 2,2 9 3 12 4 15 5,5 21 6,3 24 7,5 28 - - 10 36 - - 11 39 - - 15 52 - - 18.5 63 - - 22 75 - - Pdc BC Icu (kA) Rms (kA) 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 - Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA - Cal (A) Rat (A) 1,5 1,5 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 12,5 25 25 25 50 50 50 80 80 80 - Type de coordination: 2 Coordination type: 2 Contacteurs Contactor Type Type 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D18 2 x LC1-D18 2 x LC1-D25 2 x LC1-D32 2 x LC1-D32 2 x LC1-D32 2 x LC1-D32 2 x LC1-D40 2 x LC1-D40 2 x LC1-D40 2 x LC1 D80 2 x LC1-D50 2 x LC1 D80 2 x LC1-D50 2 x LC1 D80 2 x LC1-D65 2 x LC1 D80 2 x LC1-D65 2 x LC1 D80 2 x LC1-D80 2 x LC1 D80 2 sens de marche Reverse Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1305 0,63...1 LR2-D1305 0,63...1 LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D3322 17...25 LR2-D3322 17...25 LR2-D3353 23...32 LR9-D5357 30...50 LR2-D3355 30...40 LR9-D5357 30...50 LR2-D3357 37...50 LR9-D5357 30...50 LR2-D3359 48...65 LR9-D5363 48...80 LR2-D3359 48...65 LR9-D5363 48...80 LR2-D3363 63...80 LR9-D5363 48...80 Nb modules Nbr of modules Mf Mw 3 6 3 6 3 6 3 6 3 6 3 6 3 6 6 6 6 6 6 6 6 6 6 6 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 Ancienne gamme Old range Guide Technique V9 / V9 Technical Guide 291 Anex 01 Appendix 01 Compact NS80H-MA 380/415 V Puissance Moteur Power motor P (kW) I (A) 0,18 0,7 0,25 0,9 0,37 1,2 0,55 1,6 0,75 2 1,1 2,8 1,5 3,7 2,2 5,3 3 7 4 9 5,5 12 7,5 16 10 21 11 23 15 30 - - 18,5 37 - - 22 43 - - 30 59 - - 37 72 - - Pdc BC Icu (kA) Rms (kA) 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 - Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA - Cal (A) Rat (A) 1,5 1,5 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 12,5 25 25 25 50 50 50 80 80 - Type de coordination: 2 Coordination type: 2 Contacteurs Contactor Type Type 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D18 2 x LC1-D18 2 x LC1-D25 2 x LC1-D32 2 x LC1-D32 2 x LC1-D32 2 x LC1-D32 2 x LC1-D40 2 x LC1-D40 2 x LC1-D40 2 x LC1 D80 2 x LC1-D50 2 x LC1 D80 2 x LC1-D50 2 x LC1 D80 2 x LC1-D65 2 x LC1 D80 2 x LC1 D80 2 x LC1 D80 2 sens de marche Reverse Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1305 0,63...1 LR2-D1305 0,63...1 LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D3322 17...25 LR2-D3322 17...25 LR2-D3353 23...32 LR9-D5357 30...50 LR2-D3355 30...40 LR9-D5357 30...50 LR2-D3357 37...50 LR9-D5357 30...50 LR2-D3359 48...65 LR9-D5363 48...80 LR2-D3363 63...80 LR9-D5363 48...80 Nb modules Nbr of modules Mf Mw 3 6 3 6 3 6 3 6 3 6 3 6 3 6 6 6 6 6 6 6 6 6 6 6 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 Ancienne gamme Old range Guide Technique V9 / V9 Technical Guide 292 Anex 01 Appendix 01 440 V (1) Puissance Moteur Power motor P (kW) I (A) 0,25 0,7 0,37 1 0,55 1,4 0,75 1,7 1,1 2,4 1,5 3,1 2,2 4,5 3 5,8 4 8 5,5 10,5 7,5 13,7 10 19 11 20 15 26,5 18,5 33 - - 22 39 - - 30 52 - - 37 63 - - 45 76 - - Compact NS80H-MA Pdc BC Icu (kA) Rms (kA) 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 - Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA - Cal (A) Rat (A) 1,5 2,5 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 25 25 25 50 50 50 80 80 80 - Type de coordination: 2 Coordination type: 2 Contacteurs Contactor Type Type 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D18 2 x LC1-D25 2 x LC1-D25 2 x LC1-D32 2 x LC1-D32 2 x LC1-D32 2 x LC1-D40 2 x LC1-D40 2 x LC1-D40 2 x LC1-D50 2 x LC1 D80 2 x LC1-D50 2 x LC1 D80 2 x LC1-D65 2 x LC1 D80 2 x LC1-D65 2 x LC1 D80 2 x LC1-D80 2 x LC1 D80 Ancienne gamme Old range (1) Applicable pour 480 V NEMA Guide Technique V9 / V9 Technical Guide 2 sens de marche Reverse Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1305 0,63...1 LR2-D1306 1...1,6 LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D3322 17...25 LR2-D3322 17...25 LR2-D3353 23...32 LR2-D3355 30...40 LR9-D5357 30...50 LR2-D3355 30...40 LR9-D5357 30...50 LR2-D3359 48...65 LR9-D5363 48...80 LR2-D3359 48...65 LR9-D5363 48...80 LR2-D3363 63...80 LR9-D5363 48...80 Nb modules Nbr of modules Mf Mw 3 6 3 6 3 6 3 6 3 6 3 6 6 6 6 6 6 6 6 6 6 6 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 (1) Valid for 480 V NEMA 293 Anex 01 Appendix 01 500/525 V Puissance Moteur Power motor P (kW) I (A) 0,25 0,6 0,37 0,9 0,55 1,2 0,75 1,5 1,1 2,0 1,5 2,8 2,2 3,8 3 5 4 6,5 5,5 9 7,5 12 10 15 11 18,4 15 23 18,5 28,5 22 33 - - - - 30 45 - - - - 37 55 - - - - 45 65 - - 55 75 - - Compact NS80H-MA Pdc BC Icu (kA) Rms (kA) 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 - Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA - Cal (A) Rat (A) 1,5 1,5 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 12,5 25 25 25 50 50 50 80 80 80 - Ancienne gamme Old range ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide Type de coordination: 2 Coordination type: 2 Contacteurs Contactor Type Type 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D18 2 x LC1-D18 2 x LC1-D25 2 x LC1-D32 2 x LC1-D32 2 x LC1-D32 2 x LC1-D32 2 x LC1-D40 2 x LC1-D40 2 x LC1-D40 2 x LC1-D50 2 x LC1-D115 2 x LC1-F115 2 x LC1-D50 2 x LC1-D115 2 x LC1-F115 2 x LC1-D65 2 x LC1-D115 2 x LC1-F115 2 x LC1-D115 2 x LC1-F115 2 x LC1-D115 2 x LC1-F115 2 sens de marche Reverse Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1305 0,63...1 LR2-D1305 0,63...1 LR2-D1306 1...1,6 LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D3321 12...18 LR2-D3322 17...25 LR2-D3322 17...25 LR2-D3353 23...32 LR2-D3355 30...40 LR9-D5357 30...50 LR9-F5357 30...50 LR2-D3357 37...50 LR9-D5357 30...50 LR9-F5357 30...50 LR2-D3359 48...65 LR9-D5363 48...80 LR9-F5363 48...80 LR9-D3363 63...80 LR9-D5363 48...80 LR9-F5363 48...80 LR9-D5363 48...80 Nb modules Nbr of modules Mf Mw 3 6 3 6 3 6 3 6 3 6 3 6 3 6 6 6 6 6 6 6 6 6 6 6 6 9 6 9 6 9 6 9 9 12 9 ** 6 9 9 12 9 ** 6 9 9 12 9 ** 9 12 9 ** 9 12 9 ** ** Impossible in Mw type 294 Anex 01 Appendix 01 Compact NS80H-MA 6.1.1.11. Type de coordination: 1 - - - - - - - - - - - - - - - -Etoile / Triangle (Y/∆) Coordination type: 1 - - - - - - - - - - - - - - - - - - -STAR / DELTA (Y/∆) Démarrage: Normal Start-up: Normal Compact NS80H-MA 220/230 V Puissance Moteur Power motor P (kW) I (A) 0,55 2,8 1,1 4,4 1,5 6,1 2,2 8,7 3 11,5 4 14,5 5,5 20 7,5 28 11 39 15 52 18,5 64 22 75 Pdc BC Icu (kA) Rms (kA) 100 100 100 100 100 100 100 100 100 100 100 100 Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA Cal (A) Rat (A) 6,3 6,3 12,5 12,5 12,5 25 25 50 50 80 80 80 Type de coordination: 1 Coordination type: 1 Contacteurs Contactor Type Type 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D12 3 x LC1-D18 3 x LC1-D18 3 x LC1-D32 3 x LC1-D40 3 x LC1-D50 Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D1322 17...25 LR2-D3353 23...32 LR2-D3355 30...40 LR2-D3357 37...50 Nb modules Nbr of modules Mf Mw 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 9 6 9 Ancienne gamme Old range Compact NS80H-MA 380 V Puissance Moteur Power motor P (kW) I (A) 1,5 3,7 2,2 5 3 6,6 4 8,5 5,5 11,5 7,5 15,5 11 22 15 30 18,5 37 22 44 30 59 37 72 Pdc BC Icu (kA) Rms (kA) 70 70 70 70 70 70 70 70 70 70 70 70 Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA Cal (A) Rat (A) 6,3 6,3 12,5 12,5 12,5 25 25 50 50 50 80 80 Type de coordination: 1 Coordination type: 1 Contacteurs Contactor Type Type 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D12 3 x LC1-D18 3 x LC1-D18 3 x LC1-D32 3 x LC1-D40 3 x LC1-D40 Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D1322 17...25 LR2-D3353 23...32 LR2-D3355 30...40 LR2-D3357 37...50 Nb modules Nbr of modules Mf Mw 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 9 6 9 Ancienne gamme Old range Guide Technique V9 / V9 Technical Guide 295 Anex 01 Appendix 01 Compact NS80H-MA 415 V Puissance Moteur Power motor P (kW) I (A) 1,5 3,5 2,2 4,8 3 6,5 4 8,2 5,5 11 7,5 14 9 17 11 21 15 28 22 40 25 47 30 55 37 66 45 80 Pdc BC Icu (kA) Rms (kA) 70 70 70 70 70 70 70 70 70 70 70 70 70 70 Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA Cal (A) Rat (A) 6,3 6,3 12,5 12,5 12,5 25 25 25 50 50 50 80 80 80 Type de coordination: 1 Coordination type: 1 Contacteurs Contactor Type Type 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D12 3 x LC1-D12 3 x LC1-D18 3 x LC1-D18 3 x LC1-D32 3 x LC1-D32 3 x LC1-D40 3 x LC1-D50 Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D1322 17...25 LR2-D3353 23...32 LR2-D3355 30...40 LR2-D3355 30...40 LR2-D3357 37...50 Nb modules Nbr of modules Mf Mw 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 9 6 9 Ancienne gamme Old range Compact NS80H-MA 440 V (1) Puissance Moteur Power motor P (kW) I (A) 7,5 13,7 9 16,9 11 20,1 15 26,5 22 39 30 51,5 Pdc BC Icu (kA) Rms (kA) 65 65 65 65 65 65 65 65 65 65 65 37 64 65 NS80H-MA 80 3 x LC1-D40 LR2-D3355 45 76 65 NS80H-MA 80 3 x LC1-D50 LR2-D3357 1,5 3,1 2,2 4,5 3 5,8 4 7,9 5,5 10,4 Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA Type de coordination: 1 Coordination type: 1 Cal (A) Rat (A) 6,3 6,3 12,5 12,5 12,5 25 25 25 50 50 80 Contacteurs Contactor Type Type 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D12 3 x LC1-D12 3 x LC1-D18 3 x LC1-D18 3 x LC1-D32 Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D1322 17...25 LR2-D3353 23...32 Ancienne gamme Old range (1) Applicable pour 480 V NEMA Guide Technique V9 / V9 Technical Guide Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Nb modules Nbr of modules Mf Mw 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 30...40 6 9 37...50 6 9 (1) Valid for 480 V NEMA 296 Anex 01 Appendix 01 Compact NS80H-MA 6.1.1.12. Type de coordination: 2 - - - - - - - - - - - - - - - -Etoile / Triangle (Y/∆) Coordination Type: 2 - - - - - - - - - - - - - - - - - -STAR / DELTA (Y/∆) Démarrage: normal Start-up: Normal Compact NS80H-MA 220/240 V Puissance Moteur Power motor P (kW) I (A) 0,09 0,7 0,12 0,9 0,18 1,2 0,25 1,5 0,37 2 0,55 2,8 0,75 3,5 1,1 5 1,5 6,5 2,2 9 3 12 4 15 5,5 21 6,3 24 7,5 28 - - 10 36 - - 11 39 - - 15 52 - - 18.5 63 - - 22 75 - - Pdc BC Icu (kA) Rms (kA) 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 - Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA - Cal (A) Rat (A) 1,5 1,5 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 12,5 25 25 25 50 50 50 80 80 80 - Type de coordination: 2 Coordination type: 2 Contacteurs Contactor Type Type 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D18 3 x LC1-D18 3 x LC1-D25 3 x LC1-D32 3 x LC1-D32 3 x LC1-D32 3 x LC1-D32 3 x LC1-D40 3 x LC1-D40 3 x LC1-D40 3 x LC1 D80 3 x LC1-D50 3 x LC1 D80 3 x LC1-D50 3 x LC1 D80 3 x LC1-D65 3 x LC1 D80 3 x LC1-D65 3 x LC1 D80 3 x LC1-D80 3 x LC1 D80 Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1305 0,63...1 LR2-D1305 0,63...1 LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D3322 17...25 LR2-D3322 17...25 LR2-D3353 23...32 LR9-D5357 30...50 LR2-D3355 30...40 LR9-D5357 30...50 LR2-D3357 37...50 LR9-D5357 30...50 LR2-D3359 48...65 LR9-D5363 48...80 LR2-D3359 48...65 LR9-D5363 48...80 LR2-D3363 63...80 LR9-D5363 48...80 Nb modules Nbr of modules Mf Mw 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 9 6 9 6 9 9 12 6 9 9 12 6 9 9 12 6 9 9 12 6 9 9 12 9 9 9 12 Ancienne gamme Old range Guide Technique V9 / V9 Technical Guide 297 Anex 01 Appendix 01 Compact NS80H-MA 380/415 V Puissance Moteur Power motor P (kW) I (A) 0,18 0,7 0,25 0,9 0,37 1,2 0,55 1,6 0,75 2 1,1 2,8 1,5 3,7 2,2 5,3 3 7 4 9 5,5 12 7,5 16 10 21 11 23 15 30 - - 18,5 37 - - 22 43 - - 30 59 - - 37 72 - - Pdc BC Icu (kA) Rms (kA) 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 70 - Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA - Cal (A) Rat (A) 1,5 1,5 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 12,5 25 25 25 50 50 50 80 80 - Type de coordination: 2 Coordination type: 2 Contacteurs Contactor Type Type 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D18 3 x LC1-D18 3 x LC1-D25 3 x LC1-D32 3 x LC1-D32 3 x LC1-D32 3 x LC1-D32 3 x LC1-D40 3 x LC1-D40 3 x LC1-D40 3 x LC1 D80 3 x LC1-D50 3 x LC1 D80 3 x LC1-D50 3 x LC1 D80 3 x LC1-D65 3 x LC1 D80 3 x LC1 D80 3 x LC1 D80 Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1305 0,63...1 LR2-D1305 0,63...1 LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D3322 17...25 LR2-D3322 17...25 LR2-D3353 23...32 LR9-D5357 30...50 LR2-D3355 30...40 LR9-D5357 30...50 LR2-D3357 37...50 LR9-D5357 30...50 LR2-D3359 48...65 LR9-D5363 48...80 LR2-D3363 63...80 LR9-D5363 48...80 Nb modules Nbr of modules Mf Mw 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 9 6 9 6 9 9 12 6 9 9 12 6 9 9 12 6 9 9 12 9 9 9 12 Ancienne gamme Old range Guide Technique V9 / V9 Technical Guide 298 Anex 01 Appendix 01 440 V (1) Puissance Moteur Power motor P (kW) I (A) 0,25 0,7 0,37 1 0,55 1,4 0,75 1,7 1,1 2,4 1,5 3,1 2,2 4,5 3 5,8 4 8 5,5 10,5 7,5 13,7 10 19 11 20 15 26,5 18,5 33 - - 22 39 - - 30 52 - - 37 63 - - 45 76 - - Compact NS80H-MA Pdc BC Icu (kA) Rms (kA) 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 - Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA - Cal (A) Rat (A) 1,5 2,5 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 25 25 25 50 50 50 80 80 80 - Type de coordination: 2 Coordination type: 2 Contacteurs Contactor Type Type 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D18 3 x LC1-D25 3 x LC1-D25 3 x LC1-D32 3 x LC1-D32 3 x LC1-D32 3 x LC1-D40 3 x LC1-D40 3 x LC1-D40 3 x LC1-D50 3 x LC1 D80 3 x LC1-D50 3 x LC1 D80 3 x LC1-D65 3 x LC1 D80 3 x LC1-D65 3 x LC1 D80 3 x LC1-D80 3 x LC1 D80 Ancienne gamme Old range (1) Applicable pour 480 V NEMA Guide Technique V9 / V9 Technical Guide Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1305 0,63...1 LR2-D1306 1...1,6 LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D3322 17...25 LR2-D3322 17...25 LR2-D3353 23...32 LR2-D3355 30...40 LR9-D5357 30...50 LR2-D3355 30...40 LR9-D5357 30...50 LR2-D3359 48...65 LR9-D5363 48...80 LR2-D3359 48...65 LR9-D5363 48...80 LR2-D3363 63...80 LR9-D5363 48...80 Nb modules Nbr of modules Mf Mw 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 9 6 9 6 9 6 9 9 12 6 9 9 12 6 9 9 12 6 9 9 12 9 9 9 12 (1) Valid for 480 V NEMA 299 Anex 01 Appendix 01 500/525 V Puissance Moteur Power motor P (kW) I (A) 0,25 0,6 0,37 0,9 0,55 1,2 0,75 1,5 1,1 2,0 1,5 2,8 2,2 3,8 3 5 4 6,5 5,5 9 7,5 12 10 15 11 18,4 15 23 18,5 28,5 22 33 - - - - 30 45 - - - - 37 55 - - - - 45 65 - - 55 75 - - Compact NS80H-MA Pdc BC Icu (kA) Rms (kA) 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 - Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA - Cal (A) Rat (A) 1,5 1,5 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 12,5 25 25 25 50 50 50 80 80 80 - Ancienne gamme Old range ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide Type de coordination: 2 Coordination type: 2 Contacteurs Contactor Type Type 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D18 3 x LC1-D18 3 x LC1-D25 3 x LC1-D32 3 x LC1-D32 3 x LC1-D32 3 x LC1-D32 3 x LC1-D40 3 x LC1-D40 3 x LC1-D40 3 x LC1-D50 3 x LC1-D115 3 x LC1-F115 3 x LC1-D50 3 x LC1-D115 3 x LC1-F115 3 x LC1-D65 3 x LC1-D115 3 x LC1-F115 3 x LC1-D115 3 x LC1-F115 3 x LC1-D115 3 x LC1-F115 Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1305 0,63...1 LR2-D1305 0,63...1 LR2-D1306 1...1,6 LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D3321 12...18 LR2-D3322 17...25 LR2-D3322 17...25 LR2-D3353 23...32 LR2-D3355 30...40 LR9-D5357 30...50 LR9-F5357 30...50 LR2-D3357 37...50 LR9-D5357 30...50 LR9-F5357 30...50 LR2-D3359 48...65 LR9-D5363 48...80 LR9-F5363 48...80 LR9-D3363 63...80 LR9-D5363 48...80 LR9-F5363 48...80 LR9-D5363 48...80 Nb modules Nbr of modules Mf Mw 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 9 6 9 6 9 6 9 12 ** 12 ** 6 9 12 ** 12 ** 6 9 12 ** 12 ** 12 ** 12 ** 12 ** 12 ** ** Impossible in Mw type 300 Anex 01 Appendix 01 Compact NS100-630z-MA 6.1.1.13. Type de coordination: 1 - - - - - - - - - - - - - - - -DOL (Démarrage direct) Coordination type: 1 - - - - - - - - - - - - - - - - - - -DOL (Direct On Line) Démarrage: Normal Start-up: Normal Compact NS100-630z-MA 220/240 V Type de coordination: 1 Coordination type: 1 DOL (Démarrage direct) DOL (Direct On Line) Performance de coupure / Breaking characteristics Compact NS N H L NS100z-MA 85kA 100kA 130kA NS160/250z-MA 85kA 100kA 130kA 100kA 130kA NS400/630z-MA Puissance Moteur Power motor P (kW) I (A) 0,37 1,8 0,55 2,8 1,1 4,4 1,5 6,1 2,2 8,7 3 11,5 4 14,5 5,5 20 7,5 28 11 39 - - 15 52 - - 18,5 64 - - 22 75 Disjoncteurs Circuit Breaker Type Type NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA Cal (A) Rat (A) 2,5 6,3 6,3 12,5 12,5 12,5 25 25 50 50 50 100 100 Contacteurs Contactor Type Type LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D12 LC1-D18 LC1-D25 LC1-D32 LC1-D40 LC1-D65 LC1-D65 LC1-D80 25 85 NS100N/H/L-MA 100 LC1-D95 - - - - - 30 100 NS100N/H/L-MA 100 LC1-D115 - - - - LC1-F115 37 125 NS160N/H/L-MA 150 LC1-D150 45 150 NS160N/H/L-MA 150 LC1-F150 55 180 NS250N/H/L-MA 220 LC1-F185 75 250 NS400H-MA 320 LC1-F265 - - NS400L-MA 320 LC1-F265 90 312 NS400H-MA 320 LC1-F330 - - NS400L-MA 320 LC1-F330 110 360 NS630H/L-MA 500 LC1-F400 150 480 NS630H/L-MA 500 LC1-F500 Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D1322 17...25 LR2-D3353 23...32 LR2-D3357 37...50 LR9-D5357 30...50 LR2-D3357 37...50 LR9-D5357 30...50 LR2-D3359 48...65 LR9-D5363 48...80 LR2-D3363 63...80 LR9-D5363 48...80 LR2-D3365 80...93 LR9-D5367 60...100 LR9-D5367 60...100 LR9-F5367 60...100 LR9-D5369 90...150 LR9-F5369 90...150 LR9-F5371 132...220 LR9-F7375 200...330 LR9-F7375 200...330 LR9-F7375 200...330 LR9-F7375 200...330 LR9-F7379 300...500 LR9-F7379 300...500 Ancienne gamme Old range * Modulaire à confirmer en fonction de la tension Guide Technique V9 / V9 Technical Guide Nb modules Nbr of modules Mf Mw 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 9 3 6 3 9 3 6 3 9 3 6 9 3 6 3 9 6 9 6 9 6 9 6 9 9 9 9 12 9 * 12 12 12 * 15 15 15 15 * Confirm module in function of voltage 301 Anex 01 Appendix 01 Compact NS100-630z-MA 380 V Type de coordination: 1 Coordination type: 1 DOL (Démarrage direct) DOL (Direct On Line) Performance de coupure / Breaking characteristics Compact NS N H L NS100z-MA 25kA 70kA 130kA NS160/250z-MA 35kA 70kA 130kA 70kA 130kA NS400/630z-MA Puissance Moteur Power motor P (kW) I (A) 0,37 1,2 0,55 1,6 0,75 2 1,1 2,8 1,5 3,7 2,2 5 3 6,6 4 8,5 5,5 11,5 7,5 15,5 11 22 15 30 18,5 37 Disjoncteurs Circuit Breaker Type Type NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA - - - Cal (A) Rat (A) 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 12,5 25 25 50 50 Contacteurs Contactor Type Type LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D12 LC1-D18 LC1-D25 LC1-D32 LC1-D40 Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1306 1...1,6 LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D1322 17...25 LR2-D3353 23...32 LR2-D3357 37...50 - - LR9-D5357 30...50 Nb modules Nbr of modules Mf Mw 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 9 22 44 NS100N/H/L-MA 50 LC1-D50 LR2-D3357 37...50 3 6 - - - - - LR9-D5357 30...50 3 9 30 59 NS100N/H/L-MA 50 LC1-D65 LR2-D3357 37...50 3 6 - - - - - LR9-D5357 30...50 3 9 37 72 NS100N/H/L-MA 100 LC1-D80 LR2-D3363 63...80 3 6 - - - - - LR9-D5363 48...80 3 9 45 85 NS100N/H/L-MA 100 LC1-D95 LR2-D3365 80...93 3 6 - - - - - LR9-D5367 60...100 3 9 55 105 NS160N/H/L-MA 150 LC1-D150 LR9-D5369 90...150 6 9 75 140 NS160N/H/L-MA 150 LC1-F150 LR9-F5369 90...150 6 9 90 170 NS250N/H/L-MA 220 LC1-F185 LR9-F5371 132...220 9 9 110 210 NS250N/H/L-MA 220 LC1-F225 LR9-F5371 132...220 9 9 132 250 NS400H-MA 320 LC1-F265 LR9-F7375 200...330 9 12 - - NS400L-MA 320 LC1-F265 LR9-F7375 200...330 9 15 160 300 NS400H-MA 320 LC1-F330 LR9-F7375 200...330 12 12 - - NS400L-MA 320 LC1-F330 LR9-F7375 200...330 12 15 200 380 NS630H/L-MA 500 LC1-F400 LR9-F7379 300...500 15 15 220 420 NS630H/L-MA 500 LC1-F500 LR9-F7379 300...500 15 15 250 480 NS630H/L-MA 500 LC1-F500 LR9-F7379 300...500 15 15 Ancienne gamme Old range Guide Technique V9 / V9 Technical Guide 302 Anex 01 Appendix 01 Compact NS100-630z-MA 415 V Type de coordination: 1 Coordination type: 1 DOL (Démarrage direct) DOL (Direct On Line) Performance de coupure / Breaking characteristics Compact NS N H L NS100z-MA 25kA 70kA 130kA NS160/250z-MA 35kA 70kA 130kA 70kA 130kA NS400/630z-MA Puissance Moteur Power motor P (kW) I (A) 9 17 11 21 15 28 Disjoncteurs Circuit Breaker Type Type NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA 22 40 NS100N/H/L-MA 50 LC1-D40 LR2-D3357 37...50 3 6 - - - - - LR9-D5357 30...50 3 9 0,37 1,1 0,55 1,5 0,75 1,8 1,1 2,5 1,5 3,5 2,2 4,8 3 6,5 4 8,2 5,5 11 7,5 14 Cal (A) Rat (A) 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 12,5 25 25 25 50 Contacteurs Contactor Type Type LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D12 LC1-D18 LC1-D18 LC1-D25 LC1-D32 Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1306 1...1,6 LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D1321 12...18 LR2-D1322 17...25 LR2-D3353 23...32 Nb modules Nbr of modules Mf Mw 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 25 47 NS100N/H/L-MA 50 LC1-D50 LR2-D3357 37...50 3 6 - - - - - LR9-D5357 30...50 3 9 30 55 NS100N/H/L-MA 50 LC1-D65 LR2-D3357 37...50 3 6 - - - - - LR9-D5357 30...50 3 9 37 72 NS100N/H/L-MA 100 LC1-D80 LR2-D3363 63...80 3 6 45 80 NS100N/H/L-MA 100 LC1-D80 LR9-D5363 48...80 3 9 55 100 NS100N/H/L-MA 100 LC1-D115 LR9-D5367 60...100 6 9 - - - - LC1-F115 LR9-F5367 60...100 6 9 75 135 NS160N/H/L-MA 150 LC1-D150 LR9-D5369 90...150 6 9 - - - - LC1-F150 LR9-F5369 90...150 6 9 90 160 NS250N/H/L-MA 220 LC1-F185 LR9-F5371 132...220 9 9 110 200 NS250N/H/L-MA 220 LC1-F225 LR9-F5371 132...220 9 9 132 230 NS400H-MA 320 LC1-F265 LR9-F7375 200...330 9 12 - - NS400L-MA 320 LC1-F265 LR9-F7375 200...330 9 15 160 270 NS400H-MA 320 LC1-F330 LR9-F7375 200...330 12 12 - - NS400L-MA 320 LC1-F330 LR9-F7375 200...330 12 15 220 380 NS630H/L-MA 500 LC1-F400 LR9-F7379 300...500 15 15 250 430 NS630H/L-MA 500 LC1-F500 LR9-F7379 300...500 15 15 Ancienne gamme Old range Guide Technique V9 / V9 Technical Guide 303 Anex 01 Appendix 01 Compact NS100-630z-MA 440 V (1) Type de coordination: 1 Coordination type: 1 DOL (Démarrage direct) DOL (Direct On Line) Performance de coupure / Breaking characteristics Compact NS N H L NS100z-MA 25kA 65kA 130kA NS160/250z-MA 35kA 65kA 130kA 65kA 130kA NS400/630z-MA Puissance Moteur Power motor P (kW) I (A) 9 16,9 11 20,1 15 26,5 Disjoncteurs Circuit Breaker Type Type NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA 22 39 NS100N/H/L-MA 50 LC1-D40 LR2-D3357 37...50 3 6 - - - - - LR9-D5357 30...50 3 9 0,37 1 0,55 1,4 0,75 1,7 1,1 2,4 1,5 3,1 2,2 4,5 3 5,8 4 7,9 5,5 10,4 7,5 13,7 Cal (A) Rat (A) 2,5 2,5 2,5 2,5 6,3 6,3 12,5 12,5 12,5 25 25 25 50 Contacteurs Contactor Type Type LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D12 LC1-D18 LC1-D18 LC1-D25 LC1-D32 Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1306 1...1,6 LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D1321 12...18 LR2-D1322 17...25 LR2-D3353 23...32 Nb modules Nbr of modules Mf Mw 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 30 51,5 NS100N/H/L-MA 50 LC1-D65 LR2-D3357 37...50 3 6 - - - - - LR9-D5357 30...50 3 9 37 64 NS100N/H/L-MA 100 LC1-D65 LR2-D3359 48...65 3 6 - - - - - LR9-D5363 48...80 3 9 45 76 NS100N/H/L-MA 100 LC1-D80 LR2-D3363 63...80 3 6 - - - - LR9-D5363 48...80 3 9 55 96 NS100N/H/L-MA 100 LC1-D115 LR9-D5367 60...100 6 - - - - LC1-F115 LR9-F5367 60...100 75 124 NS160N/H/L-MA 150 LC1-D150 LR9-D5369 90...150 - - - - LC1-F150 LR9-F5369 90...150 9 9 6 9 9 90 156 NS250N/H/L-MA 220 LC1-F185 LR9-F5371 132...220 9 9 110 180 NS250N/H/L-MA 220 LC1-F185 LR9-F5371 132...220 9 9 132 215 NS250N/H/L-MA 220 LC1-F225 LR9-F5371 132...220 9 9 160 256 NS400H-MA 320 LC1-F265 LR9-F7375 200...330 9 12 - - NS400L-MA 320 LC1-F265 LR9-F7375 200...330 9 15 220 360 NS630H/L-MA 500 LC1-F400 LR9-F7379 300...500 15 15 250 401 NS630H/L-MA 500 LC1-F500 LR9-F7379 300...500 15 15 300 480 NS630H/L-MA 500 LC1-F630 LR9-F7381 380...630 16 ** Ancienne gamme Old range (1) Applicable pour 480 V NEMA ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide (1) Valid for 480 V NEMA ** Impossible in Mw type 304 Anex 01 Appendix 01 Compact NS100-630z-MA 500/525 V Type de coordination: 1 Coordination type: 1 DOL (Démarrage direct) DOL (Direct On Line) Performance de coupure / Breaking characteristics Compact NS H L NS100z-MA 50/35kA 70kA NS160/250z-MA 50/35kA 70kA NS400/630z-MA 50/35kA 70kA Puissance Moteur Power motor P (kW) I (A) 0,55 1,2 0,75 1,5 1,1 2 1,5 2,6 3 5 4 6,5 5,5 9 7,5 12 9 14 10 15 11 18,4 18,5 28,5 22 33 Disjoncteurs Circuit Breaker Type Type NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA - - - Cal (A) Rat (A) 2,5 2,5 2,5 6,3 6,3 12,5 12,5 12,5 25 25 25 50 50 Contacteurs Contactor Type Type LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D12 LC1-D18 LC1-D18 LC1-D25 LC1-D32 LC1-D40 Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1306 1...1,6 LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D1321 12...18 LR2-D1322 17...25 LR2-D3353 23...32 LR2-D3355 30...40 - - LR9-D5357 30...50 Nb modules Nbr of modules Mf Mw 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 9 30 45 NS100N/H/L-MA 50 LC1-D50 LR2-D3357 37...50 3 6 - - - - - LR9-D5357 30...50 3 9 37 55 NS100N/H/L-MA 100 LC1-D65 LR2-D3359 48...65 3 6 - - - - - LR9-D5363 48...80 3 9 55 80 NS100N/H/L-MA 100 LC1-D80 LR2-D3363 63...80 3 6 - - - - - LR9-D5363 48...80 3 9 75 110 NS160N/H/L-MA 150 LC1-D150 LR9-D5369 90...150 6 9 90 130 NS160N/H/L-MA 150 LC1-F150 LR9-F5369 90...150 6 9 110 156 NS250N/H/L-MA 220 LC1-F185 LR9-F5371 132...220 9 9 132 190 NS250N/H/L-MA 220 LC1-F265 LR9-F5371 132...220 9 12 160 228 NS400H-MA 320 LC1-F265 LR9-F7375 200...330 9 12 - - NS400L-MA 320 LC1-F265 LR9-F7375 200...330 9 15 200 281 NS400H-MA 320 LC1-F330 LR9-F7375 200...330 12 12 - - NS400L-MA 320 LC1-F330 LR9-F7375 200...330 12 15 220 310 NS630H/L-MA 500 LC1-F400 LR9-F7379 300...500 15 15 315 445 NS630H/L-MA 500 LC1-F500 LR9-F7379 300...500 15 15 335 460 NS630H/L-MA 500 LC1-F500 LR9-F7379 300...500 15 15 Ancienne gamme Old range Guide Technique V9 / V9 Technical Guide 305 Anex 01 Appendix 01 Compact NS100-630z-MA 660/690 V (1) Type de coordination: 1 Coordination type: 1 DOL (Démarrage direct) DOL (Direct On Line) Performance de coupure / Breaking characteristics Compact NS N NS100z-MA 8kA H NS160/250z-MA 10kA NS400/630z-MA 20kA Puissance Moteur Power motor P (kW) I (A) 0,75 1.2 1 1,5 1,5 2 2,2 2,8 3 3,8 4 4,9 5,5 6,6 7,5 8,9 10 11,5 15 17 18,5 21,3 30 34,6 - - Disjoncteurs Circuit Breaker Type Type NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA - Cal (A) Rat (A) 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 25 25 50 50 - Contacteurs Contactor Type Type LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D12 LC1-D18 LC1-D25 LC1-D32 LC1-D40 - Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1306 1...1,6 LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 18...12 LR2-D1322 17...25 LR2-D3355 30...40 LR9-D5357 30...50 Nb modules Nbr of modules Mf Mw 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 9 33 39 NS100N/H/L-MA 50 LC1-D50 LR2-D3357 37...50 3 6 - - - - - LR9-D5357 30...50 3 9 37 42 NS100N/H/L-MA 50 LC1-D65 LR2-D3357 37...50 3 6 - - - - - LR9-D5357 30...50 3 9 45 49 NS100N/H/L-MA 100 LC1-D80 LR2-D3357 37...50 3 6 - - - - - LR9-D5363 48...80 3 9 55 60 NS100N/H/L-MA 100 LC1-D115 LR9-D5363 48...80 6 9 - - - - LC1-F115 LR9-F5363 48...80 6 9 75 80 NS100N/H/L-MA 100 LC1-D115 LR9-D5367 60...100 6 9 - - - - LC1-F115 LR9-F5367 60...100 6 9 90 100 NS160N/H/L-MA 150 LC1-D150 LR9-D5369 90...150 6 9 110 120 NS160N/H/L-MA 150 LC1-F150 LR9-F5369 90...150 6 9 132 140 NS250N/H/L-MA 220 LC1-F265 LR9-F5371 132...220 9 12 160 175 NS250N/H/L-MA 220 LC1-F265 LR9-F5371 132...220 9 12 200 220 NS400H-MA 320 LC1-F330 LR9-F7375 200...330 12 12 - - NS400L-MA 320 LC1-F330 LR9-F7375 200...330 12 12 220 240 NS400H-MA 320 LC1-F330 LR9-F7375 200...330 12 12 - - NS400L-MA 320 LC1-F330 LR9-F7375 200...330 12 15 250 270 NS630H/L-MA 500 LC1-F400 LR9-F7375 200...300 15 15 335 335 NS630H/L-MA 500 LC1-F500 LR9-F7379 300...500 15 15 375 400 NS630H/L-MA 500 LC1-F630 LR9-F7381 380...630 16 ** 450 480 NS630H/L-MA 500 LC1-F630 LR9-F7381 380...630 16 ** Ancienne gamme Old range (1) Confirmer le nb de modules pour 660/690 V ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide (1) Confirm number of modules in function of this voltage level 660/690 V ** Impossible in Mw type 306 Anex 01 Appendix 01 Compact NS100-630z-MA 6.1.1.14. Type de coordination: 2 - - - - - - - - - - - - - - - -DOL (Démarrage direct) Coordination type: 2 - - - - - - - - - - - - - - - - - - -DOL (Direct On Line) Démarrage: normal Start-up: Normal Compact NS100-630z-MA 220/240 V Type de coordination: 2 Coordination type: 2 DOL (Démarrage direct) DOL (Direct On Line) Performance de coupure / Breaking characteristics Compact NS N H L NS100z-MA 85kA 100kA 130kA NS160/250z-MA 85kA 100kA 130kA 100kA 130kA NS400/630z-MA Puissance Moteur Power motor P (kW) I (A) 0,18 0,25 0,37 0,55 0,75 1,1 1,5 2,2 3 4 5,5 6,3 7,5 10 11 15 18,5 22 30 37 45 55 75 90 110 132 150 1,2 1,5 2 2,8 3,5 5 6,5 9 12 15 21 24 28 36 39 52 63 75 100 125 150 180 250 300 360 430 460 Disjoncteurs Circuit Breaker Type Type NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS160-MA NS160-MA NS250-MA NS400-MA NS400-MA NS400-MA NS630-MA NS630-MA NS630-MA Cal (A) Rat (A) 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 12,5 25 25 25 50 50 50 100 100 100 100 150 150 220 320 320 320 500 500 500 Contacteurs Contactor Type Type LC1-D09 LC1-D09 LC1-D09 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D115 LC1-F115 LC1-D150 LC1-F150 LC1-D150 LC1-F150 LC1-F185 LC1-F265 LC1-F265 LC1-F330 LC1-F400 LC1-F500 LC1-F500 Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D3322 17...25 LR2-D3322 17...25 LR2-D3353 23...32 LR9-D5357 30...50 LR2-D3355 30...40 LR9-D5357 30...50 LR2-D3355 30...40 LR9-D5357 30...50 LR2-D3359 48...65 LR9-D5363 48...80 LR2-D3359 48...65 LR9-D5363 48...80 LR2-D3363 63...80 LR9-D5363 48...80 LR9-D5367 60...100 LR9-F5367 60...100 LR9-D5369 90...150 LR9-F5369 90...150 LR9-D5369 90...150 LR9-F5369 90...150 LR9-F5371 132...220 LR9-F5371 132...220 LR9-F7375 200...330 LR9-F7375 200...330 LR9-F7379 300...500 LR9-F7379 300...500 LR9-F7379 300...500 Nb modules Nbr of modules Mf Mw 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 6 6 6 6 6 6 9 12 12 15 15 15 15 6 6 6 6 6 6 6 6 6 6 6 6 6 9 6 9 6 9 6 9 6 9 6 9 9 9 9 9 9 9 9 * * * 15 15 15 Ancienne gamme Old range Guide Technique V9 / V9 Technical Guide 307 Anex 01 Appendix 01 Compact NS100-630z-MA 380/415 V Type de coordination: 2 Coordination type: 2 DOL (Démarrage direct) DOL (Direct On Line) Performance de coupure / Breaking characteristics Compact NS N H L NS100z-MA 25kA 70kA 130kA NS160/250z-MA 35kA 70kA 130kA 70kA 130kA NS400/630z-MA Puissance Moteur Power motor P (kW) I (A) 0,37 1,2 0,55 1,6 0,75 2 1,1 2,8 1,5 3,7 2,2 5,3 3 7 4 9 5,5 12 7,5 16 10 21 11 23 15 30 - - 18,5 37 - - 22 43 - - 30 59 - - 37 72 - - 45 85 - - 55 105 - - 75 140 - - 90 170 110 210 - - 132 250 160 300 200 380 220 420 250 480 Disjoncteurs Circuit Breaker Type Type NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS160-MA NS160-MA NS250-MA NS250-MA NS400-MA NS400-MA NS400-MA NS630-MA NS630-MA NS630-MA Cal (A) Rat (A) 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 12,5 25 25 25 50 50 50 100 100 100 150 150 220 220 320 320 320 500 500 500þ Contacteurs Contactor Type Type LC1-D09 LC1-D09 LC1-D09 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D115 LC1-F115 LC1-D115 LC1-F115 LC1-D150 LC1-F150 LC1-F185 LC1-F225 LC1-F265 LC1-F265 LC1-F330 LC1-F400 LC1-F500 LC1-F500 Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D3322 17...25 LR2-D3322 17...25 LR2-D3353 23...32 LR9-D5357 30...50 LR2-D3355 30...40 LR9-D5357 30...50 LR2-D3357 37...50 LR9-D5357 30...50 LR2-D3359 48...65 LR9-D5363 48...80 LR2-D3363 63...80 LR9-D5363 48...80 LR9-D5367 60...100 LR9-F5367 60...100 LR9-D5369 90...150 LR9-F5369 90...150 LR9-D5369 90...150 LR9-F5369 90...150 LR9-F5371 132...220 LR9-F5371 132...220 LR9-F5371 132...220 LR9-F7375 200...330 LR9-F7375 200...330 LR9-F7379 300...500 LR9-F7379 300...500 LR9-F7379 300...500 Nb modules Nbr of modules Mf Mw 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 9 3 6 3 9 3 6 3 9 3 6 3 9 3 6 3 9 6 9 6 9 6 9 6 9 6 9 6 9 9 9 9 9 12 * 12 * 15 * 15 15 15 15 15 15 Ancienne gamme Old range Guide Technique V9 / V9 Technical Guide 308 Anex 01 Appendix 01 Compact NS100-630z-MA 440 V Type de coordination: 2 Coordination type: 2 DOL (Démarrage direct) DOL (Direct On Line) Performance de coupure / Breaking characteristics Compact NS N H L NS100z-MA 25kA 65kA 130kA NS160/250z-MA 35kA 65kA 130kA 65kA 130kA NS400/630z-MA Puissance Moteur Power motor P (kW) I (A) 440V 0.37 1 0.55 1.4 0.75 1.7 1.1 2.4 1.5 3.1 2.2 4.5 3 5.8 4 8 5.5 10.5 7.5 13.7 10 19 11 20 15 26.5 Disjoncteurs Circuit Breaker Type Type NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA Cal (A) Rat (A) 2.5 2.5 2.5 2.5 6.3 6.3 6.3 12.5 12.5 25 25 25 50 Contacteurs Contactor Type Type LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D80 Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1306 1...1,6 LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D3322 17...25 LR2-D3322 17...25 LR2-D3353 23...32 18.5 33 - Nb modules Nbr of modules NS100-MA 50 LC1-D80 LR2-D3355 30...40 3 6 - - - LC1-D80 LR9-D5357 30...50 3 9 Mf Mw 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 22 39 NS100-MA 50 LC1-D80 LR2-D3355 30...40 3 6 - - - - LC1-D80 LR9-D5357 30...50 3 9 30 52 NS100-MA 100 LC1-D80 LR2-D3359 48...65 3 6 - - - - LC1-D80 LR9-D5363 48...80 3 9 37 63 NS100-MA 100 LC1-D80 LR2-D3359 48...65 3 6 - - - - LC1-D80 LR9-D5363 48...80 3 9 45 76 NS100-MA 100 LC1-D80 LR2-D3363 63...80 3 6 - - - - - LR9-D5363 48...80 3 9 55 90 NS100-MA 100 LC1-D115 LR9-D5367 60...100 6 9 - - - - LC1-F115 LR9-F5367 60...100 6 9 75 125 NS160-MA 150 LC1-D150 LR9-D5369 90...150 6 9 - - - - LC1-F150 LR9-F5369 90...150 6 9 90 140 NS160-MA 150 LC1-D150 LR9-D5369 90...150 6 9 - - - - LC1-F150 LR9-F5369 90...150 6 9 110 178 NS250-MA 220 LC1-F185 LR9-F5371 132...220 9 9 132 210 NS250-MA 220 LC1-F225 LR9-F5371 132...220 9 9 - - NS400-MA 320 LC1-F265 LR9-F5371 132...220 12 * 160 256 NS400-MA 320 LC1-F265 LR9-F7375 200...330 12 * 200 310 NS400-MA 320 LC1-F330 LR9-F7375 200...330 15 * 220 353 NS630-MA 500 LC1-F400 LR9-F7379 300...500 15 15 250 400 NS630-MA 500 LC1-F400 LR9-F7379 300...500 15 15 300 460 NS630-MA 500 LC1-F500 LR9-F7379 300...500 15 15 Ancienne gamme Old range (1) Applicable pour 480 V NEMA Guide Technique V9 / V9 Technical Guide (1) Valid for 480 V NEMA 309 Anex 01 Appendix 01 Compact NS100-630z-MA 500/525 V Type de coordination: 2 Coordination type: 2 DOL (Démarrage direct) DOL (Direct On Line) Performance de coupure / Breaking characteristics Compact NS H L NS100z-MA 50/35kA 70kA NS160/250z-MA 50/35kA 70kA NS400/630z-MA 50/35kA 70kA Puissance Moteur Power motor P (kW) I (A) 500V 0,55 1,2 0,75 1,5 1,1 2 1,5 2,8 2,2 3,8 3 5 4 6,5 5,5 9 7,5 12 10 15 11 18,4 15 23 18,5 28,5 Disjoncteurs Circuit Breaker Type Type NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA Cal (A) Rat (A) 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 12,5 25 25 25 50 Contacteurs Contactor Type Type LC1-D09 LC1-D09 LC1-D09 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D40 LC1-D80 LC1-D80 LC1-D80 Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1306 1...1,6 LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D3322 17...25 LR2-D3322 17...25 LR2-D3353 23...32 22 33 - - Nb modules Nbr of modules NS100-MA 50 LC1-D80 LR2-D3355 23...32 3 6 - - LC1-D115 LR9-D5357 30...50 6 9 9 Mf Mw 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 - - - - LC1-F115 LR9-F5357 30...50 6 30 45 NS100-MA 50 LC1-D80 LR2-D3357 30...40 3 6 - - - - LC1-D115 LR9-D5357 30...50 6 9 9 - - - - LC1-F115 LR9-F5357 30...50 6 37 55 NS100-MA 100 LC1-D80 LR2-D3359 48...65 3 6 - - - - LC1-D115 LR9-D5363 48...80 6 9 9 - - - - LC1-F115 LR9-F5363 48...80 6 45 65 NS100-MA 100 LC1-D115 LR9-D5363 48...80 6 9 - - - - LC1-F115 LR9-F5363 48...80 6 9 55 75 NS100-MA 100 LC1-D115 LR9-D5367 60...100 6 9 - - - - LC1-F115 LR9-F5367 60...100 6 9 75 105 NS160-MA 150 LC1-D115 LR9-D5369 90...150 6 9 - - - - LC1-F115 LR9-F5369 90...150 6 9 90 130 NS160-MA 150 LC1-D150 LR9-D5369 90...150 6 9 - - - - LC1-F150 LR9-F5369 90...150 6 9 110 156 NS250-MA 220 LC1-F185 LR9-F5371 132...220 9 9 132 187 NS250-MA 220 LC1-F265 LR9-F5371 132...220 9 12 160 220 NS400-MA 320 LC1-F400 LR9-F7375 200...330 15 * 200 280 NS400-MA 320 LC1-F400 LR9-F7375 200...330 15 * 220 310 NS400-MA 500 LC1-F400 LR9-F7379 200...330 15 * 250 360 NS630-MA 500þ LC1-F500 LR9-F7379 300...500 15 15 315 445 NS630-MA 500 LC1-F500 LR9-F7379 300...500 15 15 Ancienne gamme Old range Guide Technique V9 / V9 Technical Guide 310 Anex 01 Appendix 01 Compact NS100-630z-MA 6.1.1.15. Type de coordination: 1 - - - - - - - - - - - - - - - -2 sens de marche Coordination type: 1 - - - - - - - - - - - - - - - - - - -Reverse Démarrage: Normal Start-up: Nor mal Compact NS100-630z-MA 220/240 V Type de coordination: 1 Coordination type: 1 2 sens de marche Reverse Performance de coupure / Breaking characteristics Compact NS N H L NS100z-MA 85kA 100kA 130kA NS160/250z-MA 85kA 100kA 130kA 100kA 130kA NS400/630z-MA Puissance Moteur Power motor P (kW) I (A) 0,37 1,8 0,55 2,8 1,1 4,4 1,5 6,1 2,2 8,7 3 11,5 4 14,5 5,5 20 7,5 28 11 39 - - 15 52 - - 18,5 64 - - 22 75 - - 25 85 - - 30 100 - - 37 125 45 150 55 180 75 250 90 312 110 360 150 480 Disjoncteurs Circuit Breaker Type Type NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS160N/H/L-MA NS160N/H/L-MA NS250N/H/L-MA NS400H/L-MA NS400H/L-MA NS630H/L-MA NS630H/L-MA Cal (A) Rat (A) 2,5 6,3 6,3 12,5 12,5 12,5 25 25 50 50 50 100 100 100 100 150 150 220 320 320 500 500 Ancienne gamme Old range ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide Contacteurs Contactor Type Type 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D12 2 x LC1-D18 2 x LC1-D25 2 x LC1-D32 2 x LC1-D40 2 x LC1-D65 2 x LC1-D65 2 x LC1-D80 2 x LC1-D95 2 x LC1-D115 2 x LC1-F115 2 x LC1-D150 2 x LC1-F150 2 x LC1-F185 2 x LC1-F265 2 x LC1-F330 2 x LC1-F400 2 x LC1-F500 Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D1322 17...25 LR2-D3353 23...32 LR2-D3357 37...50 LR9-D5357 30...50 LR2-D3357 37...50 LR9-D5357 30...50 LR2-D3359 48...65 LR9-D5363 48...80 LR2-D3363 63...80 LR9-D5363 48...80 LR2-D3365 80...93 LR9-D5367 60...100 LR9-D5367 60...100 LR9-F5367 60...10 LR9-D5369 90...150 LR9-F5369 90...150 LR9-F5371 132...220 LR9-F7375 200...330 LR9-F7375 200...330 LR9-F7379 300...500 LR9-F7379 300...500 Nb modules Nbr of modules Mf Mw 3 6 3 6 3 6 3 6 3 6 3 6 3 6 6 6 6 6 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 9 12 9 ** 9 12 9 ** 12 ** 16 ** 16 ** 16 ** 16 ** ** Impossible in Mw type 311 Anex 01 Appendix 01 Compact NS100-630z-MA 380 V Type de coordination: 1 Coordination type: 1 2 sens de marche Reverse Performance de coupure / Breaking characteristics Compact NS N H L NS100z-MA 25kA 70kA 130kA NS160/250z-MA 35kA 70kA 130kA 70kA 130kA NS400/630z-MA Puissance Moteur Power motor P (kW) I (A) 0,37 1,2 0,55 1,6 0,75 2 1,1 2,8 1,5 3,7 2,2 5 3 6,6 4 8,5 5,5 11,5 7,5 15,5 11 22 15 30 18,5 37 Disjoncteurs Circuit Breaker Type Type NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA Cal (A) Rat (A) 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 12,5 25 25 50 50 Contacteurs Contactor Type Type 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D12 2 x LC1-D18 2 x LC1-D25 2 x LC1-D32 2 x LC1-D40 Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1306 1...1,6 LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D1322 17...25 LR2-D3353 23...32 LR2-D3357 37...50 - - LR9-D5357 30...50 Nb modules Nbr of modules - - - 22 44 NS100N/H/L-MA 50 2 x LC1-D50 LR2-D3357 37...50 6 9 - - - - - LR9-D5357 30...50 6 9 30 59 NS100N/H/L-MA 50 2 x LC1-D65 LR2-D3357 37...50 6 9 - - - - - LR9-D5357 30...50 6 9 37 72 NS100N/H/L-MA 100 2 x LC1-D80 LR2-D3363 63...80 6 9 - - - - - LR9-D5363 48...80 6 9 45 85 NS100N/H/L-MA 100 2 x LC1-D95 LR2-D3365 80...93 6 9 - - - - - LR9-D5367 60...100 6 9 55 105 NS160N/H/L-MA 150 2 x LC1-D150 LR9-D5369 90...150 9 12 75 140 NS160N/H/L-MA 150 2 x LC1-F150 LR9-F5369 90...150 9 ** Mf Mw 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 6 6 6 6 6 9 6 9 90 170 NS250N/H/L-MA 220 2 x LC1-F185 LR9-F5371 132...220 12 ** 110 210 NS250N/H/L-MA 220 2 x LC1-F225 LR9-F5371 132...220 12 ** 132 250 NS400H/L-MA 320 2 x LC1-F265 LR9-F7375 200...330 16 ** 160 300 NS400H/L-MA 320 2 x LC1-F330 LR9-F7375 200...330 16 ** 200 380 NS630H/L-MA 500 2 x LC1-F400 LR9-F7379 300...500 16 ** 220 420 NS630H/L-MA 500 2 x LC1-F500 LR9-F7379 300...500 16 ** 250 480 NS630H/L-MA 500 2 x LC1-F500 LR9-F7379 300...500 16 ** Ancienne gamme Old range ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide ** Impossible in Mw type 312 Anex 01 Appendix 01 Compact NS100-630z-MA 415 V Type de coordination: 1 Coordination type: 1 2 sens de marche Reverse Performance de coupure / Breaking characteristics Compact NS N H L NS100z-MA 25kA 70kA 130kA NS160/250z-MA 35kA 70kA 130kA 70kA 130kA NS400/630z-MA Puissance Moteur Power motor P (kW) I (A) 9 17 11 21 15 28 Disjoncteurs Circuit Breaker Type Type NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA 22 40 NS100N/H/L-MA 50 2 x LC1-D40 LR2-D3357 37...50 6 9 - - - - - LR9-D5357 30...50 6 9 25 47 NS100N/H/L-MA 50 2 x LC1-D50 LR2-D3357 37...50 6 9 - - - - - LR9-D5357 30...50 6 9 30 55 NS100N/H/L-MA 50 2 x LC1-D65 LR2-D3357 37...50 6 9 - - - - - LR9-D5357 30...50 6 9 37 72 NS100N/H/L-MA 100 2 x LC1-D80 LR2-D3363 63...80 6 9 45 80 NS100N/H/L-MA 100 2 x LC1-D80 LR9-D5363 48...80 6 9 55 100 NS100N/H/L-MA 100 2 x LC1-D115 LR9-D5367 60...100 9 12 - - - - 2 x LC1-F115 LR9-F5367 60...100 9 ** 75 135 NS160N/H/L-MA 150 2 x LC1-D150 LR9-D5369 90...150 9 12 - - - - 2 x LC1-F150 LR9-F5369 90...150 9 ** 0,37 1,1 0,55 1,5 0,75 1,8 1,1 2,5 1,5 3,5 2,2 4,8 3 6,5 4 8,2 5,5 11 7,5 14 Cal (A) Rat (A) 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 12,5 25 25 25 50 Contacteurs Contactor Type Type 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D12 2 x LC1-D18 2 x LC1-D18 2 x LC1-D25 2 x LC1-D32 Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1306 1...1,6 LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D1321 12...18 LR2-D1322 17...25 LR2-D3353 23...32 Nb modules Nbr of modules Mf Mw 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 6 6 6 6 90 160 NS250N/H/L-MA 220 2 x LC1-F185 LR9-F5371 132...220 12 ** 110 200 NS250N/H/L-MA 220 2 x LC1-F225 LR9-F5371 132...220 12 ** 132 230 NS400H/L-MA 320 2 x LC1-F265 LR9-F7375 200...330 16 ** 160 270 NS400H/L-MA 320 2 x LC1-F330 LR9-F7375 200...330 16 ** 220 380 NS630H/L-MA 500 2 x LC1-F400 LR9-F7379 300...500 16 ** 250 430 NS630H/L-MA 500 2 x LC1-F500 LR9-F7379 300...500 16 ** Ancienne gamme Old range ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide ** Impossible in Mw type 313 Anex 01 Appendix 01 Compact NS100-630z-MA 440 V (1) Type de coordination: 1 Coordination type: 1 2 sens de marche Reverse Performance de coupure / Breaking characteristics Compact NS N H L NS100z-MA 25kA 65kA 130kA NS160/250z-MA 35kA 65kA 130kA 65kA 130kA NS400/630z-MA Puissance Moteur Power motor P (kW) I (A) 9 16,9 11 20,1 15 26,5 Disjoncteurs Circuit Breaker Type Type NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA 22 39 NS100N/H/L-MA 50 2 x LC1-D40 LR2-D3357 37...50 6 9 - - - - - LR9-D5357 30...50 6 9 30 51,5 NS100N/H/L-MA 50 2 x LC1-D65 LR2-D3357 37...50 6 9 - - - - - LR9-D5357 30...50 6 9 37 64 NS100N/H/L-MA 100 2 x LC1-D65 LR2-D3359 48...65 6 9 - - - - - LR9-D5363 48...80 6 9 45 76 NS100N/H/L-MA 100 2 x LC1-D80 LR2-D3363 63...80 6 9 - - - - - LR9-D5363 48...80 6 9 55 96 NS100N/H/L-MA 100 2 x LC1-D115 LR9-D5367 60...100 9 12 - - - - 2 x LC1-F115 LR9-F5367 60...100 9 ** 75 124 NS160N/H/L-MA 150 2 x LC1-D150 LR9-D5369 90...150 9 12 - - - - 2 x LC1-F150 LR9-F5369 90...150 9 ** 0,37 1 0,55 1,4 0,75 1,7 1,1 2,4 1,5 3,1 2,2 4,5 3 5,8 4 7,9 5,5 10,4 7,5 13,7 Cal (A) Rat (A) 2,5 2,5 2,5 2,5 6,3 6,3 12,5 12,5 12,5 25 25 25 50 Contacteurs Contactor Type Type 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D12 2 x LC1-D18 2 x LC1-D18 2 x LC1-D25 2 x LC1-D32 Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1306 1...1,6 LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D1321 12...18 LR2-D1322 17...25 LR2-D3353 23...32 Nb modules Nbr of modules Mf Mw 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 6 6 6 6 90 156 NS250N/H/L-MA 220 2 x LC1-F185 LR9-F5371 132...220 12 ** 110 180 NS250N/H/L-MA 220 2 x LC1-F185 LR9-F5371 132...220 12 ** 132 215 NS250N/H/L-MA 220 2 x LC1-F225 LR9-F5371 132...220 12 ** 160 256 NS400H/L-MA 320 2 x LC1-F265 LR9-F7375 200...330 16 ** 220 360 NS630H/L-MA 500 2 x LC1-F400 LR9-F7379 300...500 16 ** 250 401 NS630H/L-MA 500 2 x LC1-F500 LR9-F7379 300...500 16 ** 300 480 NS630H/L-MA 500 2 x LC1-F630 LR9-F7381 380...630 20 ** Ancienne gamme Old range (1) Applicable pour 480 V NEMA ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide (1) Valid for 480 V NEMA ** Impossible in Mw type 314 Anex 01 Appendix 01 Compact NS100-630z-MA 500/525 V Type de coordination: 1 Coordination type: 1 2 sens de marche Reverse Performance de coupure / Breaking characteristics Compact NS H L NS100z-MA 50/35kA 70kA NS160/250z-MA 50/35kA 70kA NS400/630z-MA 50/35kA 70kA Puissance Moteur Power motor P (kW) I (A) 0,55 1,2 0,75 1,5 1,1 2 1,5 2,6 3 5 4 6,5 5,5 9 7,5 12 9 14 10 15 11 18,4 18,5 28,5 22 33 Disjoncteurs Circuit Breaker Type Type NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA Cal (A) Rat (A) 2,5 2,5 2,5 6,3 6,3 12,5 12,5 12,5 25 25 25 50 50 Contacteurs Contactor Type Type 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D12 2 x LC1-D18 2 x LC1-D18 2 x LC1-D25 2 x LC1-D32 2 x LC1-D40 Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1306 1...1,6 LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D1321 12...18 LR2-D1322 17...25 LR2-D3353 23...32 LR2-D3355 30...40 - - LR9-D5357 30...50 - - - 30 45 NS100N/H/L-MA 50 2 x LC1-D50 LR2-D3357 37...50 6 9 - - - - - LR9-D5357 30...50 6 9 37 55 NS100N/H/L-MA 100 2 x LC1-D65 LR2-D3359 48...65 6 9 - - - - - LR9-D5363 48...80 6 9 55 80 NS100N/H/L-MA 100 2 x LC1-D80 LR2-D3363 63...80 6 9 - - - - - LR9-D5363 48...80 6 9 75 110 NS160N/H/L-MA 150 2 x LC1-D150 LR9-D5369 90...150 9 12 90 130 NS160N/H/L-MA 150 2 x LC1-F150 LR9-F5369 90...150 9 ** 110 156 NS250N/H/L-MA 220 2 x LC1-F185 LR9-F5371 132...220 12 ** 132 190 NS250N/H/L-MA 220 2 x LC1-F265 LR9-F5371 132...220 12 ** 160 228 NS400H/L-MA 320 2 x LC1-F265 LR9-F7375 200...330 16 ** 200 281 NS400H/L-MA 320 2 x LC1-F330 LR9-F7375 200...330 16 ** 220 310 NS630H/L-MA 500 2 x LC1-F400 LR9-F7379 300...500 16 ** 315 445 NS630H/L-MA 500 2 x LC1-F500 LR9-F7379 300...500 16 ** 335 460 NS630H/L-MA 500 2 x LC1-F500 LR9-F7379 300...500 16 ** Ancienne gamme Old range ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide Nb modules Nbr of modules Mf Mw 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 6 6 6 6 6 9 6 9 ** Impossible in Mw type 315 Anex 01 Appendix 01 Compact NS100-630z-MA 660/690 V (1) Type de coordination: 1 Coordination type: 1 2 sens de marche Reverse Performance de coupure / Breaking characteristics Compact NS N NS100z-MA 8kA H NS160/250z-MA 10kA NS400/630z-MA 20kA Puissance Moteur Power motor P (kW) I (A) 7,5 8,9 10 11,5 - - 15 17 18,5 21,3 30 34,6 Disjoncteurs Circuit Breaker Type Type NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA NS100N/H/L-MA - - - 33 39 NS100N/H/L-MA 50 2 x LC1-D50 LR2-D3357 37...50 6 9 - - - - - LR9-D5357 30...50 6 9 37 42 NS100N/H/L-MA 50 2 x LC1-D65 LR2-D3357 37...50 6 9 - - - - - LR9-D5357 30...50 6 9 45 49 NS100N/H/L-MA 100 2 x LC1-D80 LR2-D3357 37...50 6 9 - - - - - LR9-D5363 48...80 6 9 55 60 NS100N/H/L-MA 100 2 x LC1-D115 LR9-D5363 48...80 9 12 - - - - 2 x LC1-F115 LR9-F5363 48...80 9 ** 75 80 NS100N/H/L-MA 100 2 x LC1-D115 LR9-D5367 60...100 9 12 ** 0,75 1.2 1 1,5 1,5 2 2,2 2,8 3 3,8 4 4,9 5,5 6,6 Cal (A) Rat (A) 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 25 25 50 50 Contacteurs Contactor Type Type 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D12 2 x LC1-D18 2 x LC1-D25 2 x LC1-D25 2 x LC1-D32 2 x LC1-D40 Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1306 1...1,6 LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1322 17...25 LR2-D1321 18...12 LR2-D1322 17...25 LR2-D3355 30...40 - - LR9-D5357 30...50 Nb modules Nbr of modules Mf Mw 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 3 6 6 6 6 6 6 6 6 9 6 9 - - - - 2 x LC1-F115 LR9-F5367 60...100 9 90 100 NS160N/H/L-MA 150 2 x LC1-D150 LR9-D5369 90...150 9 12 110 120 NS160N/H/L-MA 150 2 x LC1-F150 LR9-F5369 90...150 9 ** 132 140 NS250N/H/L-MA 220 2 x LC1-F265 LR9-F5371 132...220 12 ** 160 175 NS250N/H/L-MA 220 2 x LC1-F265 LR9-F5371 132...220 12 ** 200 220 NS400H/L-MA 320 2 x LC1-F330 LR9-F7375 200...330 16 ** 220 240 NS400H/L-MA 320 2 x LC1-F330 LR9-F7375 200...330 16 ** 250 270 NS630H/L-MA 500 2 x LC1-F400 LR9-F7375 200...300 16 ** 335 335 NS630H/L-MA 500 2 x LC1-F500 LR9-F7379 300...500 16 ** 375 400 NS630H/L-MA 500 2 x LC1-F630 LR9-F7381 380...630 20 ** 450 480 NS630H/L-MA 500 2 x LC1-F630 LR9-F7381 380...630 20 ** Ancienne gamme Old range (1) Confirmer le nb de modules pour 660/690 V ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide (1) Confirm number of modules in function of this voltage level 660/690 V ** Impossible in Mw type 316 Anex 01 Appendix 01 Compact NS100-630z-MA 6.1.1.16. Type de coordination: 2 - - - - - - - - - - - - - - - -2 sens de marche Coordination type: 2 - - - - - - - - - - - - - - - - - - -Reverse Démarrage: normal Start-up: Normal Compact NS100-630z-MA 220/240 V Type de coordination: 2 Coordination type: 2 2 sens de marche Reverse Performance de coupure / Breaking characteristics Compact NS N H L NS100z-MA 85kA 100kA 130kA NS160/250z-MA 85kA 100kA 130kA 100kA 130kA NS400/630z-MA Puissance Moteur Power motor P (kW) I (A) 0,18 0,25 0,37 0,55 0,75 1,1 1,5 2,2 3 4 5,5 6,3 7,5 10 11 15 18,5 22 30 37 45 55 75 90 110 132 150 1,2 1,5 2 2,8 3,5 5 6,5 9 12 15 21 24 28 36 39 52 63 75 100 125 150 180 250 300 360 430 460 Disjoncteurs Circuit Breaker Type Type NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS160-MA NS160-MA NS250-MA NS400-MA NS400-MA NS400-MA NS630-MA NS630-MA NS630-MA Cal (A) Rat (A) 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 12,5 25 25 25 50 50 50 100 100 100 100 150 150 220 320 320 320 500 500 500 Ancienne gamme Old range ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide Contacteurs Contactor Type Type 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D40 2 x LC1-D40 2 x LC1-D40 2 x LC1-D40 2 x LC1-D40 2 x LC1-D40 2 x LC1-D40 2 x LC1-D40 2 x LC1-D40 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-D115 2 x LC1-F115 2 x LC1-D150 2 x LC1-F150 2 x LC1-D150 2 x LC1-F150 2 x LC1-F185 2 x LC1-F265 2 x LC1-F265 2 x LC1-F330 2 x LC1-F400 2 x LC1-F500 2 x LC1-F500 Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D3322 17...25 LR2-D3322 17...25 LR2-D3353 23...32 LR9-D5357 30...50 LR2-D3355 30...40 LR9-D5357 30...50 LR2-D3355 30...40 LR9-D5357 30...50 LR2-D3359 48...65 LR9-D5363 48...80 LR2-D3359 48...65 LR9-D5363 48...80 LR2-D3363 63...80 LR9-D5363 48...80 LR9-D5367 60...100 LR9-F5367 LR9-D5369 90...150 LR9-F5369 LR9-D5369 90...150 LR9-F5369 LR9-F5371 132...220 LR9-F7375 200...330 LR9-F7375 200...330 LR9-F7379 300...500 LR9-F7379 300...500 LR9-F7379 300...500 Nb modules Nbr of modules Mf Mw 3 3 3 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 9 9 9 9 9 9 12 16 16 16 16 16 16 6 6 6 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 12 ** 12 ** 12 ** ** ** ** ** ** ** ** ** Impossible in Mw type 317 Anex 01 Appendix 01 Compact NS100-630z-MA 380/415 V Type de coordination: 2 Coordination type: 2 2 sens de marche Reverse Performance de coupure / Breaking characteristics Compact NS N H L NS100z-MA 25kA 70kA 130kA NS160/250z-MA 35kA 70kA 130kA 70kA 130kA NS400/630z-MA Puissance Moteur Power motor P (kW) I (A) 380V 0,37 1,2 0,55 1,6 0,75 2 1,1 2,8 1,5 3,7 2,2 5,3 3 7 4 9 5,5 12 7,5 16 10 21 11 23 15 30 Disjoncteurs Circuit Breaker Type Type NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA Cal (A) Rat (A) 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 12,5 25 25 25 50 Contacteurs Contactor Type Type 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D40 2 x LC1-D40 2 x LC1-D40 2 x LC1-D40 2 x LC1-D40 2 x LC1-D40 2 x LC1-D40 2 x LC1-D40 2 x LC1-D40 2 x LC1-D80 Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D3322 17...25 LR2-D3322 17...25 LR2-D3353 23...32 - - - - - LR9-D5357 18,5 37 - - NS100-MA 50 2 x LC1-D80 LR2-D3355 30...40 6 9 - - - LR9-D5357 30...50 6 9 22 - 43 NS100-MA 50 2 x LC1-D80 LR2-D3357 37...50 6 9 - - - - LR9-D5357 30...50 6 9 30 59 NS100-MA 100 2 x LC1-D80 LR2-D3359 48...65 6 9 - - - - - LR9-D5363 48...80 6 9 30...50 Nb modules Nbr of modules Mf Mw 3 6 3 6 3 6 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 37 72 NS100-MA 100 2 x LC1-D80 LR2-D3363 63...80 6 9 - - - - - LR9-D5363 48...80 6 9 45 85 NS100-MA 100 2 x LC1-D115 LR9-D5367 60...100 9 12 - - - - 2 x LC1-F115 LR9-F5367 60...100 9 ** 55 105 NS160-MA 150 2 x LC1-D115 LR9-D5369 90...150 9 12 - - - - 2 x LC1-F115 LR9-F5369 90...150 9 ** 75 140 NS160-MA 150 2 x LC1-D150 LR9-D5369 90...150 9 12 ** - - - - 2 x LC1-F150 LR9-F5369 90...150 9 90 170 NS250-MA 220 2 x LC1-F185 LR9-F5371 132...220 12 ** 110 210 NS250-MA 220 2 x LC1-F225 LR9-F5371 132...220 12 ** - - NS400-MA 320 2 x LC1-F265 LR9-F5371 132...220 16 ** 132 250 NS400-MA 320 2 x LC1-F265 LR9-F7375 200...330 16 ** 160 300 NS400-MA 320 2 x LC1-F330 LR9-F7375 200...330 16 ** 200 380 NS630-MA 500 2 x LC1-F400 LR9-F7379 300...500 16 ** 220 420 NS630-MA 500 2 x LC1-F500 LR9-F7379 300...500 16 ** 250 480 NS630-MA 500þ 2 x LC1-F500 LR9-F7379 300...500 16 ** Ancienne gamme Old range ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide ** Impossible in Mw type 318 Anex 01 Appendix 01 Compact NS100-630z-MA 440 V (1) Type de coordination: 2 Coordination type: 2 2 sens de marche Reverse Performance de coupure / Breaking characteristics Compact NS N H L NS100z-MA 25kA 65kA 130kA NS160/250z-MA 35kA 65kA 130kA 65kA 130kA NS400/630z-MA Puissance Moteur Power motor P (kW) I (A) 10 19 11 20 15 26.5 Disjoncteurs Circuit Breaker Type Type NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA 18.5 33 NS100-MA 50 2 x LC1-D80 LR2-D3355 30...40 6 9 - - - - - LR9-D5357 30...50 6 9 22 39 NS100-MA 50 2 x LC1-D80 LR2-D3355 30...40 6 9 - - - - - LR9-D5357 30...50 6 9 30 52 NS100-MA 100 2 x LC1-D80 LR2-D3359 48...65 6 9 - - - - - LR9-D5363 48...80 6 9 37 63 NS100-MA 100 2 x LC1-D80 LR2-D3359 48...65 6 9 - - - - - LR9-D5363 48...80 6 9 45 76 NS100-MA 100 2 x LC1-D80 LR2-D3363 63...80 6 9 - - - - - LR9-D5363 48...80 6 9 55 90 NS100-MA 100 2 x LC1-D115 LR9-D5367 60...100 9 12 - - - - 2 x LC1-F115 LR9-F5367 60...100 9 ** 75 125 NS160-MA 150 2 x LC1-D150 LR9-D5369 90...150 9 12 - - - - 2 x LC1-F150 LR9-F5369 90...150 9 ** 90 140 NS160-MA 150 2 x LC1-D150 LR9-D5369 90...150 9 12 0.37 1 0.55 1.4 0.75 1.7 1.1 2.4 1.5 3.1 2.2 4.5 3 5.8 4 8 5.5 10.5 7.5 13.7 Cal (A) Rat (A) 2.5 2.5 2.5 2.5 6.3 6.3 6.3 12.5 12.5 25 25 25 50 Contacteurs Contactor Type Type 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D40 2 x LC1-D40 2 x LC1-D40 2 x LC1-D40 2 x LC1-D40 2 x LC1-D40 2 x LC1-D40 2 x LC1-D40 2 x LC1-D80 Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1306 1...1,6 LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D3322 17...25 LR2-D3322 17...25 LR2-D3353 23...32 Nb modules Nbr of modules Mf Mw 3 6 3 6 3 6 3 6 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 - - - - 2 x LC1-F150 LR9-F5369 90...150 9 ** 110 178 NS250-MA 220 2 x LC1-F185 LR9-F5371 132...220 12 ** 132 210 NS250-MA 220 2 x LC1-F225 LR9-F5371 132...220 12 ** - - NS400-MA 320 2 x LC1-F265 LR9-F5371 132...220 16 ** 160 256 NS400-MA 320 2 x LC1-F265 LR9-F7375 200...330 16 ** 200 310 NS400-MA 320 2 x LC1-F330 LR9-F7375 200...330 16 ** 220 353 NS630-MA 500 2 x LC1-F400 LR9-F7379 300...500 16 ** 250 400 NS630-MA 500 2 x LC1-F400 LR9-F7379 300...500 16 ** 300 460 NS630-MA 500 2 x LC1-F500 LR9-F7379 300...500 16 ** Ancienne gamme Old range (1) Applicable pour 480 V NEMA ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide (1) Valid for 480 V NEMA ** Impossible in Mw type 319 Anex 01 Appendix 01 Compact NS100-630z-MA 500/525 V Type de coordination: 2 Coordination type: 2 2 sens de marche Reverse Performance de coupure / Breaking characteristics Compact NS H L NS100z-MA 50/35kA 70kA NS160/250z-MA 50/35kA 70kA NS400/630z-MA 50/35kA 70kA Puissance Moteur Power motor P (kW) I (A) 0,55 1,2 0,75 1,5 1,1 2 1,5 2,8 2,2 3,8 3 5 4 6,5 5,5 9 7,5 12 10 15 11 18,4 15 23 18,5 28,5 Disjoncteurs Circuit Breaker Type Type NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA Cal (A) Rat (A) 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 12,5 25 25 25 50 Contacteurs Contactor Type Type 2 x LC1-D09 2 x LC1-D09 2 x LC1-D09 2 x LC1-D40 2 x LC1-D40 2 x LC1-D40 2 x LC1-D40 2 x LC1-D40 2 x LC1-D40 2 x LC1-D40 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1306 1...1,6 LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D3322 17...25 LR2-D3322 17...25 LR2-D3353 23...32 Nb modules Nbr of modules 22 33 NS100-MA 50 2 x LC1-D80 LR2-D3355 23...32 6 9 - - - - 2 x LC1-D115 LR9-D5357 30...50 9 12 ** Mf Mw 3 6 3 6 3 6 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 - - - - 2 x LC1-F115 LR9-F5357 30...50 9 30 45 NS100-MA 50 2 x LC1-D80 LR2-D3357 30...40 6 9 - - - - 2 x LC1-D115 LR9-D5357 30...50 9 12 ** - - - - 2 x LC1-F115 LR9-F5357 30...50 9 37 55 NS100-MA 100 2 x LC1-D80 LR2-D3359 48...65 6 9 - - - - 2 x LC1-D115 LR9-D5363 48...80 9 12 - - - - 2 x LC1-F115 LR9-F5363 48...80 9 ** 45 65 NS100-MA 100 2 x LC1-D115 LR9-D5363 48...80 9 12 2 x LC1-F115 LR9-F5363 48...80 9 ** 55 75 NS100-MA 100 2 x LC1-D115 LR9-D5367 60...100 9 12 ** - - - - 2 x LC1-F115 LR9-F5367 60...100 9 75 105 NS160-MA 150 2 x LC1-D115 LR9-D5369 90...150 9 12 - - - - 2 x LC1-F115 LR9-F5369 90...150 9 ** 90 130 NS160-MA 150 2 x LC1-D150 LR9-D5369 90...150 9 12 - - - - 2 x LC1-F150 LR9-F5369 90...150 9 ** 110 156 NS250-MA 220 2 x LC1-F185 LR9-F5371 132...220 12 ** 132 187 NS250-MA 220 2 x LC1-F265 LR9-F5371 132...220 12 ** 160 220 NS400-MA 320 2 x LC1-F400 LR9-F7375 200...330 16 ** 200 280 NS400-MA 320 2 x LC1-F400 LR9-F7375 200...330 16 ** 220 310 NS630-MA 500 2 x LC1-F400 LR9-F7379 300...500 16 ** 250 360 NS630-MA 500þ 2 x LC1-F500 LR9-F7379 300...500 16 ** 315 445 NS630-MA 500 2 x LC1-F500 LR9-F7379 300...500 16 ** Ancienne gamme Old range ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide ** Impossible in Mw type 320 Anex 01 Appendix 01 Compact NS100-630z-MA 6.1.1.17. Type de coordination: 1 - - - - - - - - - - - - - - - -Etoile / Triangle (Y/∆) Coordination type: 1 - - - - - - - - - - - - - - - - - - -STAR / DELTA (Y/∆) Démarrage: Normal Start-up: Normal Compact NS100-630z-MA 220/230 V Type de coordination: 1 Coordination type: 1 Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Performance de coupure / Breaking characteristics Compact NS N H L NS100z-MA 85kA 100kA 130kA NS160/250z-MA 85kA 100kA 130kA 100kA 130kA NS400/630z-MA Puissance Moteur Power motor P (kW) I (A) 0,55 2,8 1,1 4,4 1,5 6,1 2,2 8,7 3 11,5 4 14,5 Disjoncteurs Circuit Breaker Type Type NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA Cal (A) Rat (A) 6,3 6,3 12,5 12,5 12,5 25 Contacteurs Contactor Type Type 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 Nb modules Nbr of modules 5,5 20 NS100N/H/L MA 25 3 x LC1-D12 LR2-D1316 9...13 6 6 7,5 28 NS100N/H/L MA 50 3 x LC1-D18 LR2-D1321 12...18 6 6 11 39 NS100N/H/L MA 50 3 x LC1-D18 LR2-D1322 17...25 6 6 15 52 NS100N/H/L MA 100 3 x LC1-D32 LR2-D3353 23...32 6 6 18,5 64 NS100N/H/L MA 100 3 x LC1-D40 LR2-D3355 30...40 6 9 22 75 NS100N/H/L MA 100 3 x LC1-D50 LR2-D3357 37...50 6 9 25 85 NS100N/H/L MA 100 3 x LC1-D50 LR2-D3357 37...50 6 9 30 100 NS100N/H/L MA 100 3 x LC1-D50 LR2-D3359 48...65 6 9 37 125 NS160N/H/L MA 150 3 x LC1-D80 LR2-D3363 63...80 6 9 45 150 NS160N/H/L MA 150 3 x LC1-D115 LR9-D5367 60...100 12 ** - - - - 3 x LC1-F115 LR9-F5367 60...100 12 ** 55 180 NS250N/H/L MA 220 3 x LC1-D115 LR9-D5369 90...150 12 ** - - - - 3 x LC1-F115 LR9-F5369 90...150 12 ** 75 250 NS400H/L MA 320 3 x LC1-D150 LR9-D5369 90...150 12 ** - - - - 3 x LC1-F150 LR9-F5369 90...150 12 ** Mf Mw 6 6 6 6 6 6 6 6 6 6 6 6 90 312 NS400H/L MA 320 3 x LC1-F185 LR9-F5371 132...220 16 ** 110 360 NS630H/L MA 500 3 x LC1-F265 LR9-F7375 200...330 20 ** 150 480 NS630H/L MA 500 3 x LC1-F330 LR9-F7375 200...330 20 ** Ancienne gamme Old range ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide ** Impossible in Mw type 321 Anex 01 Appendix 01 Compact NS100-630z-MA 380 V Type de coordination: 1 Coordination type: 1 Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Performance de coupure / Breaking characteristics Compact NS N H L NS100z-MA 25kA 70kA 130kA NS160/250z-MA 35kA 70kA 130kA 70kA 130kA NS400/630z-MA Puissance Moteur Power motor P (kW) I (A) 1,5 3,7 2,2 5 3 6,6 4 8,5 5,5 11,5 7,5 15,5 11 22 15 30 18,5 37 22 44 30 59 37 72 45 85 55 105 75 140 - - - - 90 170 - - 110 210 - - 132 250 - - 160 300 200 380 220 420 250 480 Disjoncteurs Circuit Breaker Type Type NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS160N/H/L MA NS160N/H/L MA NS250N/H/L MA NS250N/H/L MA NS400H/L MA NS400H/L MA NS630H/L MA NS630H/L MA NS630H/L MA Cal (A) Rat (A) 6,3 6,3 12,5 12,5 12,5 25 25 50 50 100 100 100 100 150 150 220 220 320 320 500 500 500 Contacteurs Contactor Type Type 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D12 3 x LC1-D18 3 x LC1-D18 3 x LC1-D32 3 x LC1-D40 3 x LC1-D40 3 x LC1-D50 3 x LC1-D80 3 x LC1-D80 3 x LC1-D115 3 x LC1-F115 3 x LC1-D115 3 x LC1-F115 3 x LC1-D115 3 x LC1-F115 3 x LC1-D150 3 x LC1-F150 3 x LC1F-185 3 x LC1-F265 3 x LC1-F265 3 x LC1-F330 Ancienne gamme Old range ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D1322 17...25 LR2-D3353 23...32 LR2-D3355 30...40 LR2-D3357 37...50 LR2-D3357 37...50 LR2-D3359 48...65 LR2-D3363 63...80 LR9-D5367 60...100 LR9-F5367 60...100 LR9-D5367 60...100 LR9-F5367 60...100 LR9-D5369 90...150 LR9-F5369 90...150 LR9-D5369 90...150 LR9-F5369 90...150 LR9-F5371 132...220 LR9-F7375 200...330 LR9-F7375 200...330 LR9-F7375 200...330 Nb modules Nbr of modules Mf Mw 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 9 6 9 6 9 6 9 6 9 12 ** 12 ** 12 ** 12 ** 12 ** 12 ** 12 ** 12 ** 16 ** 20 ** 20 ** 20 ** ** Impossible in Mw type 322 Anex 01 Appendix 01 Compact NS100-630z-MA 415 V Type de coordination: 1 Coordination type: 1 Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Performance de coupure / Breaking characteristics Compact NS N H L NS100z-MA 25kA 70kA 130kA NS160/250z-MA 35kA 70kA 130kA 70kA 130kA NS400/630z-MA Puissance Moteur Power motor P (kW) I (A) 1,5 3,5 2,2 4,8 3 6,5 4 8,2 5,5 11 7,5 14 9 17 11 21 15 28 22 40 25 47 30 55 37 66 45 80 55 100 75 135 90 160 - - 110 200 - - 132 230 - - 160 270 220 380 250 430 Disjoncteurs Circuit Breaker Type Type NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS160N/H/L MA NS250N/H/L MA NS250N/H/L MA NS400H/L MA NS400H/L MA NS630H/L MA NS630H/L MA Cal (A) Rat (A) 6,3 6,3 12,5 12,5 12,5 25 25 25 50 50 100 100 100 100 100 150 220 220 320 320 500 500 Contacteurs Contactor Type Type 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D12 3 x LC1-D12 3 x LC1-D18 3 x LC1-D18 3 x LC1-D32 3 x LC1-D32 3 x LC1-D40 3 x LC1-D50 3 x LC1-D50 3 x LC1-D80 3 x LC1-D115 3 x LC1-F115 3 x LC1-D115 3 x LC1-F115 3 x LC1-D150 3 x LC1-F150 3 x LC1F-185 3 x LC1-F265 3 x LC1-F330 Ancienne gamme Old range ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D1322 17...25 LR2-D3353 23...32 LR2-D3355 30...40 LR2-D3355 30...40 LR2-D3357 37...50 LR2-D3359 48...65 LR2-D3363 63...80 LR9-D5367 60...100 LR9-F5367 60...100 LR9-D5369 90...150 LR9-F5369 90...150 LR9-D5369 90...150 LR9-F5369 90...150 LR9-F5371 132...220 LR9-F7375 200...330 LR9-F7375 200...330 Nb modules Nbr of modules Mf Mw 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 9 6 9 6 9 6 9 12 ** 12 ** 12 ** 12 ** 12 ** 12 ** 16 ** 20 ** 20 ** ** Impossible in Mw type 323 Anex 01 Appendix 01 Compact NS100-630z-MA 440 V (1) Type de coordination: 1 Coordination type: 1 Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Performance de coupure / Breaking characteristics Compact NS N H L NS100z-MA 25kA 65kA 130kA NS160/250z-MA 35kA 65kA 130kA 65kA 130kA NS400/630z-MA Puissance Moteur Power motor P (kW) I (A) 1,5 3,1 2,2 4,5 3 5,8 4 7,9 5,5 10,4 7,5 13,7 9 16,9 11 20,1 15 26,5 22 39 30 51,5 37 64 45 76 55 96 75 124 90 156 - - 110 180 - - 132 215 - - 160 256 220 360 250 401 300 480 Disjoncteurs Circuit Breaker Type Type NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS100N/H/L MA NS160N/H/L MA NS250N/H/L MA NS250N/H/L MA NS250N/H/L MA NS400H/L MA NS630H/L MA NS630H/L MA NS630H/L MA Cal (A) Rat (A) 6,3 6,3 12,5 12,5 12,5 25 25 25 50 50 100 100 100 100 150 220 220 220 320 500 500 500 Contacteurs Contactor Type Type 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D12 3 x LC1-D12 3 x LC1-D18 3 x LC1-D18 3 x LC1-D32 3 x LC1-D40 3 x LC1-D50 3 x LC1-D50 3 x LC1-D80 3 x LC1-D115 3 x LC1-F115 3 x LC1-D115 3 x LC1-F115 3 x LC1-D150 3 x LC1-F150 3 x LC1F-185 3 x LC1-F265 3 x LC1-F265 3 x LC1-F330 Ancienne gamme Old range (1) Applicable pour 480 V NEMA ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D1322 17...25 LR2-D3353 23...32 LR2-D3355 30...40 LR2-D3357 37...50 LR2-D3359 48...65 LR2-D3363 63...80 LR9-D5367 60...100 LR9-F5367 60...100 LR9-D5369 90...150 LR9-F5369 90...150 LR9-D5369 90...150 LR9-F5369 90...150 LR9-F5371 132...220 LR9-F7375 200...330 LR9-F7375 200...330 LR9-F7375 200...330 Nb modules Nbr of modules Mf Mw 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 9 6 9 6 9 6 9 12 ** 12 ** 12 ** 12 ** 12 ** 12 ** 16 ** 20 ** 20 ** 20 ** (1) Valid for 480 V NEMA ** Impossible in Mw type 324 Anex 01 Appendix 01 Compact NS100-630z-MA 6.1.1.18. Type de coordination: 2 - - - - - - - - - - - - - - - -Etoile / Triangle (Y/∆) Coordination Type: 2 - - - - - - - - - - - - - - - - - -STAR / DELTA (Y/∆) Démarrage: normal Start-up: Normal Compact NS100-630z-MA 220/240 V Type de coordination: 2 Coordination type: 2 Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Performance de coupure / Breaking characteristics Compact NS N H L NS100z-MA 85kA 100kA 130kA NS160/250z-MA 85kA 100kA 130kA 100kA 130kA NS400/630z-MA Puissance Moteur Power motor P (kW) I (A) 0,18 0,25 0,37 0,55 0,75 1,1 1,5 2,2 3 4 5,5 6,3 7,5 10 11 15 18,5 22 30 37 45 55 75 90 110 132 150 1,2 1,5 2 2,8 3,5 5 6,5 9 12 15 21 24 28 36 39 52 63 75 100 125 150 180 250 300 360 430 460 Disjoncteurs Circuit Breaker Type Type NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS160-MA NS160-MA NS250-MA NS400-MA NS400-MA NS400-MA NS630-MA NS630-MA NS630-MA Cal (A) Rat (A) 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 12,5 25 25 25 50 50 50 100 100 100 100 150 150 220 320 320 320 500 500 500 Ancienne gamme Old range ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide Contacteurs Contactor Type Type 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D40 3 x LC1-D40 3 x LC1-D40 3 x LC1-D40 3 x LC1-D40 3 x LC1-D40 3 x LC1-D40 3 x LC1-D40 3 x LC1-D40 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D115 3 x LC1-F115 3 x LC1-D150 3 x LC1-F150 3 x LC1-D150 3 x LC1-F150 3 x LC1-F185 3 x LC1-F265 3 x LC1-F265 3 x LC1-F330 3 x LC1-F400 3 x LC1-F500 3 x LC1-F500 Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D3322 17...25 LR2-D3322 17...25 LR2-D3353 23...32 LR9-D5357 30...50 LR2-D3355 30...40 LR9-D5357 30...50 LR2-D3355 30...40 LR9-D5357 30...50 LR2-D3359 48...65 LR9-D5363 48...80 LR2-D3359 48...65 LR9-D5363 48...80 LR2-D3363 63...80 LR9-D5363 48...80 LR9-D5367 60...100 LR9-F5367 60...100 LR9-D5369 90...150 LR9-F5369 90...150 LR9-D5369 90...150 LR9-F5369 90...150 LR9-F5371 132...220 LR9-F5371 132...220 LR9-F7375 200...330 LR9-F7375 200...330 LR9-F7379 300...500 LR9-F7379 300...500 LR9-F7379 300...500 Nb modules Nbr of modules Mf Mw 6 6 6 6 6 6 6 6 6 6 6 6 9 9 9 9 9 9 9 9 9 9 9 9 12 12 12 12 12 12 16 20 20 20 20 24 24 6 6 6 9 9 9 9 9 9 9 9 9 9 12 9 12 9 12 9 12 9 12 9 12 ** ** ** ** ** ** ** ** ** ** ** ** ** ** Impossible in Mw type 325 Anex 01 Appendix 01 Compact NS100-630z-MA 380/415 V Type de coordination: 2 Coordination type: 2 Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Performance de coupure / Breaking characteristics Compact NS N H L NS100z-MA 25kA 70kA 130kA NS160/250z-MA 35kA 70kA 130kA 70kA 130kA NS400/630z-MA Puissance Moteur Power motor P (kW) I (A) 0,37 1,2 0,55 1,6 0,75 2 1,1 2,8 1,5 3,7 2,2 5,3 3 7 4 9 5,5 12 7,5 16 10 21 11 23 15 30 - - 18,5 37 - - 22 43 - - 30 59 - - 37 72 - - 45 85 - - 55 105 - - 75 140 - - 90 170 110 210 - - 132 250 160 300 200 380 220 420 250 480 Disjoncteurs Circuit Breaker Type Type NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS160-MA NS160-MA NS250-MA NS250-MA NS400-MA NS400-MA NS400-MA NS630-MA NS630-MA NS630-MA Cal (A) Rat (A) 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 12,5 25 25 25 50 50 50 100 100 100 150 150 220 220 320 320 320 500 500 500þ Ancienne gamme Old range ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide Contacteurs Contactor Type Type 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D40 3 x LC1-D40 3 x LC1-D40 3 x LC1-D40 3 x LC1-D40 3 x LC1-D40 3 x LC1-D40 3 x LC1-D40 3 x LC1-D40 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D115 3 x LC1-F115 3 x LC1-D115 3 x LC1-F115 3 x LC1-D150 3 x LC1-F150 3 x LC1-F185 3 x LC1-F225 3 x LC1-F265 3 x LC1-F265 3 x LC1-F330 3 x LC1-F400 3 x LC1-F400 3 x LC1-F500 Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D3322 17...25 LR2-D3322 17...25 LR2-D3353 23...32 LR9-D5357 30...50 LR2-D3355 30...40 LR9-D5357 30...50 LR2-D3357 37...50 LR9-D5357 30...50 LR2-D3359 48...65 LR9-D5363 48...80 LR2-D3363 63...80 LR9-D5363 48...80 LR9-D5367 60...100 LR9-F5367 60...100 LR9-D5369 90...150 LR9-F5369 90...150 LR9-D5369 90...150 LR9-F5369 90...150 LR9-F5371 132...220 LR9-F5371 132...220 LR9-F5371 132...220 LR9-F7375 200...330 LR9-F7375 200...330 LR9-F7379 300...500 LR9-F7379 300...500 LR9-F7379 300...500 Nb modules Nbr of modules Mf Mw 6 6 6 6 6 6 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 9 9 9 12 9 9 9 12 9 9 9 12 9 9 9 12 9 9 9 12 12 ** 12 ** 12 ** 12 ** 12 ** 12 ** 16 ** 16 ** 20 ** 20 ** 20 ** 20 ** 20 ** 24 ** ** Impossible in Mw type 326 Anex 01 Appendix 01 Compact NS100-630z-MA 440 V (1) Type de coordination: 2 Coordination type: 2 Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Performance de coupure / Breaking characteristics Compact NS N H L NS100z-MA 25kA 65kA 130kA NS160/250z-MA 35kA 65kA 130kA 65kA 130kA NS400/630z-MA Puissance Moteur Power motor P (kW) I (A) 0.37 1 0.55 1.4 0.75 1.7 1.1 2.4 1.5 3.1 Disjoncteurs Circuit Breaker Type Type NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA Cal (A) Rat (A) 2.5 2.5 2.5 2.5 6.3 6.3 6.3 12.5 12.5 25 25 25 50 50 2.2 4.5 3 5.8 4 8 5.5 10.5 7.5 13.7 10 19 11 20 15 26.5 18.5 33 - - 22 39 - - 30 52 - - 37 63 - - 45 76 - - 55 90 NS100-MA 100 - - - - 75 125 NS160-MA 150 - - - - 90 140 NS160-MA 150 - - - - 110 178 NS250-MA 220 132 210 NS250-MA 220 - - NS400-MA 320 160 256 NS400-MA 320 200 310 NS400-MA 320 220 353 NS630-MA 500 250 400 NS630-MA 500 300 460 NS630-MA 500 NS100-MA NS100-MA NS100-MA NS100-MA 50 100 100 100 Contacteurs Contactor Type Type 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D40 3 x LC1-D40 3 x LC1-D40 3 x LC1-D40 3 x LC1-D40 3 x LC1-D40 3 x LC1-D40 3 x LC1-D40 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D115 3 x LC1-F115 3 x LC1-D150 3 x LC1-F150 3 x LC1-D150 3 x LC1-F150 3 x LC1-F185 3 x LC1-F225 3 x LC1-F265 3 x LC1-F265 3 x LC1-F330 3 x LC1-F400 3 x LC1-F400 3 x LC1-F500 Ancienne gamme Old range (1) Applicable pour 480 V NEMA ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1306 1...1,6 LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D3322 17...25 LR2-D3322 17...25 LR2-D3353 23...32 LR2-D3355 30...40 LR9-D5357 30...50 LR2-D3355 30...40 LR9-D5357 30...50 LR2-D3359 48...65 LR9-D5363 48...80 LR2-D3359 48...65 LR9-D5363 48...80 LR2-D3363 63...80 LR9-D5363 48...80 LR9-D5367 60...100 LR9-F5367 60...100 LR9-D5369 90...150 LR9-F5369 90...150 LR9-D5369 90...150 LR9-F5369 90...150 LR9-F5371 132...220 LR9-F5371 132...220 LR9-F5371 132...220 LR9-F7375 200...330 LR9-F7375 200...330 LR9-F7379 300...500 LR9-F7379 300...500 LR9-F7379 300...500 Nb modules Nbr of modules Mf Mw 6 6 6 6 6 6 6 6 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 9 9 9 9 9 12 9 9 9 12 9 9 9 12 9 9 9 12 9 9 9 12 12 ** 12 ** 12 ** 12 ** 12 ** 12 ** 16 ** 16 ** 20 ** 20 ** 20 ** 20 ** 20 ** 24 ** (1) Valid for 480 V NEMA ** Impossible in Mw type 327 Anex 01 Appendix 01 Compact NS100-630z-MA 500/525 V Type de coordination: 2 Coordination type: 2 Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Performance de coupure / Breaking characteristics Compact NS H L NS100z-MA 50/35kA 70kA NS160/250z-MA 50/35kA 70kA NS400/630z-MA 50/35kA 70kA Puissance Moteur Power motor P (kW) I (A) 0,55 1,2 0,75 1,5 1,1 2 1,5 2,8 2,2 3,8 3 5 4 6,5 5,5 9 7,5 12 10 15 11 18,4 15 23 18,5 28,5 22 33 - - - - 30 45 - - - - 37 55 - - - - 45 65 - - 55 75 - - 75 105 - - 90 130 - - 110 156 132 187 160 220 200 280 220 310 250 360 315 445 Disjoncteurs Circuit Breaker Type Type NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS100-MA NS160-MA NS160-MA NS250-MA NS250-MA NS400-MA NS400-MA NS630-MA NS630-MA NS630-MA Cal (A) Rat (A) 2,5 2,5 2,5 6,3 6,3 6,3 12,5 12,5 12,5 25 25 25 50 50 50 100 100 100 150 150 220 220 320 320 500 500þ 500 Ancienne gamme Old range ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide Contacteurs Contactor Type Type 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D40 3 x LC1-D40 3 x LC1-D40 3 x LC1-D40 3 x LC1-D40 3 x LC1-D40 3 x LC1-D40 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D115 3 x LC1-F115 3 x LC1-D80 3 x LC1-D115 3 x LC1-F115 3 x LC1-D80 3 x LC1-D115 3 x LC1-F115 3 x LC1-D115 3 x LC1-F115 3 x LC1-D115 3 x LC1-F115 3 x LC1-D115 3 x LC1-F115 3 x LC1-D150 3 x LC1-F150 3 x LC1-F185 3 x LC1-F265 3 x LC1-F400 3 x LC1-F400 3 x LC1-F500 3 x LC1-F500 3 x LC1-F500 Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1306 1...1,6 LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 LR2-D3322 17...25 LR2-D3322 17...25 LR2-D3353 23...32 LR2-D3355 23...32 LR9-D5357 30...50 LR9-F5357 30...50 LR2-D3357 30...40 LR9-D5357 30...50 LR9-F5357 30...50 LR2-D3359 48...65 LR9-D5363 48...80 LR9-F5363 48...80 LR9-D5363 48...80 LR9-F5363 48...80 LR9-D5367 60...100 LR9-F5367 60...100 LR9-D5369 90...150 LR9-F5369 90...150 LR9-D5369 90...150 LR9-F5369 90...150 LR9-F5371 132...220 LR9-F5371 132...220 LR9-F7375 200...330 LR9-F7375 200...330 LR9-F7375 200...330 LR9-F7379 300...500 LR9-F7379 300...500 Nb modules Nbr of modules Mf Mw 6 6 6 6 6 6 6 9 6 9 6 9 6 9 6 9 6 9 6 9 9 9 9 9 9 9 9 9 12 ** 12 ** 9 9 12 ** 12 ** 9 9 12 ** 12 ** 12 ** 12 ** 12 ** 12 ** 12 ** 12 ** 12 ** 12 ** 16 ** 20 ** 20 ** 20 ** 24 ** 24 ** 24 ** ** Impossible in Mw type 328 Anex 01 Appendix 01 GV7 6.1.1.19. Type de coordination: 1 - - - - - - - - - - - - - - - -DOL (Démarrage direct) Coordination Type: 1 - - - - - - - - - - - - - - - - - -DOL (Direct On Line) GV7 220/240 V Puissance Moteur Power motor P (kW) I (A) 11 39 15 52 18.5 64 22 75 25 85 30 100 37 125 45 150 55 180 Pdc BC Icu (kA) Rms (kA) 85 85 85 85 85 85 85 85 85 Type de coordination: 1 Coordination type: 1 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE40 25...40 GV7-RE80 48...80 GV7-RE80 48...80 GV7-RE80 48...80 GV7-RE100 60...100 GV7-RE100 60...100 GV7-RE150 90...150 GV7-RE150 90...150 GV7-RE150 90...150 DOL (Démarrage direct) DOL (Direct On Line) Nb modules Nbr of modules Contacteur Contactor LC1-D40 LC1-D65 LC1-D65 LC1-D80 LC1-D95 LC1-F115 LC1-F150 LC1-F150 LC1-F185 Mf Mw 3 3 3 3 3 3 3 3 3 3 6 6 6 6 6 6 9 9 Ancienne gamme Old range GV7 380/400 V Puissance Moteur Power motor P (kW) I (A) Type de coordination: 1 Coordination type: 1 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE50 30...50 GV7-RS50 30...50 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE100 60...100 Contacteur Contactor LC1-D32 LC1-D32 LC1-D40 LC1-D40 LC1-D50 LC1-D50 LC1-D65 LC1-D65 LC1-D80 LC1-D80 LC1-D95 DOL (Démarrage direct) DOL (Direct On Line) 15 30 - - 18.5 37 - - 22 44 - - 30 59 - - 37 72 - - 45 85 Pdc BC Icu (kA) Rms (kA) 25 70 25 70 25 70 25 70 25 70 25 Nb modules Nbr of modules - - 70 GV7-RS100 60...100 LC1-D95 3 3 55 105 25 GV7-RE100 60...100 LC1-F115 6 6 Mf Mw 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 - - 70 GV7-RS100 60...100 LC1-F115 6 6 75 140 35 GV7-RE150 90...150 LC1-F150 6 6 - - 70 GV7-RS150 90...150 LC1-F150 6 6 90 170 35 GV7-RE220 132...220 LC1-F185 9 9 - - 70 GV7-RS220 132...220 LC1-F185 9 9 110 210 35 GV7-RE220 132...220 LC1-F225 9 9 - - 70 GV7-RS220 132...220 LC1-F225 9 9 Ancienne gamme Old range Guide Technique V9 / V9 Technical Guide 329 Anex 01 Appendix 01 GV7 415 V Puissance Moteur Power motor P (kW) I (A) 15 28 - - 18.5 35 - - 22 40 - - 30 55 - - 37 72 - - 45 80 - - 55 100 - - 75 135 - - 90 160 - - 110 200 - - Pdc BC Icu (kA) Rms (kA) 25 70 25 70 25 70 25 70 25 70 25 70 25 70 35 70 35 70 35 70 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE50 30...50 GV7-RS50 30...50 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE100 60...100 GV7-RS100 60...100 GV7-RE100 60...100 GV7-RS100 60...100 GV7-RE150 90...150 GV7-RS150 90...150 GV7-RE220 132...220 GV7-RS220 132...220 GV7-RE220 132...220 GV7-RS220 132...220 Type de coordination: 1 Coordination type: 1 DOL (Démarrage direct) DOL (Direct On Line) Nb modules Nbr of modules Contacteur Contactor LC1-D32 LC1-D32 LC1-D40 LC1-D40 LC1-D50 LC1-D50 LC1-D65 LC1-D65 LC1-D80 LC1-D80 LC1-D95 LC1-D95 LC1-F115 LC1-F115 LC1-F150 LC1-F150 LC1-F185 LC1-F185 LC1-F225 LC1-F225 Mf Mw 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 6 6 6 6 6 6 6 6 9 9 9 9 9 9 9 9 Ancienne gamme Old range Guide Technique V9 / V9 Technical Guide 330 Anex 01 Appendix 01 GV7 440 V Puissance Moteur Power motor P (kW) I (A) 15 26,5 - - 18.5 33 - - 22 39 - - 30 51,5 - - 37 64 - - 45 76 - - 55 96 - - 75 124 - - 90 156 - - 110 180 - - 132 215 - - Pdc BC Icu (kA) Rms (kA) 25 65 25 65 25 65 25 65 25 65 25 65 25 65 35 65 35 65 35 65 35 65 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE100 60...100 GV7-RS100 60...100 GV7-RE150 90...150 GV7-RS150 90...150 GV7-RE150 90...150 GV7-RS150 90...150 GV7-RE220 132...220 GV7-RS220 132...220 GV7-RE220 132...220 GV7-RS220 132...220 Type de coordination: 1 Coordination type: 1 DOL (Démarrage direct) DOL (Direct On Line) Nb modules Nbr of modules Contacteur Contactor LC1-D32 LC1-D32 LC1-D32 LC1-D32 LC1-D40 LC1-D40 LC1-D65 LC1-D65 LC1-D65 LC1-D65 LC1-D80 LC1-D80 LC1-F115 LC1-F115 LC1-F150 LC1-F150 LC1-F185 LC1-F185 LC1-F225 LC1-F225 LC1-F265 LC1-F265 Mf Mw 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 6 6 6 6 6 6 6 6 9 9 9 9 9 9 9 9 9 9 9 9 Ancienne gamme Old range Guide Technique V9 / V9 Technical Guide 331 Anex 01 Appendix 01 GV7 480 V Nema Puissance Moteur Power motor P (kW) 15 18.5 22 30 37 45 55 75 90 110 132 - Pdc BC Icu (kA) Rms (kA) 25 65 25 65 25 65 25 65 25 65 25 65 25 65 35 65 35 65 35 65 35 65 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE100 60...100 GV7-RS100 60...100 GV7-RE150 90...150 GV7-RS150 90...150 GV7-RE150 90...150 GV7-RS150 90...150 GV7-RE220 132...220 GV7-RS220 132...220 GV7-RE220 132...220 GV7-RS220 132...220 Type de coordination: 1 Coordination type: 1 DOL (Démarrage direct) DOL (Direct On Line) Nb modules Nbr of modules Contacteur Contactor LC1-D32 LC1-D32 LC1-D32 LC1-D32 LC1-D40 LC1-D40 LC1-D65 LC1-D65 LC1-D65 LC1-D65 LC1-D80 LC1-D80 LC1-F115 LC1-F115 LC1-F150 LC1-F150 LC1-F185 LC1-F185 LC1-F225 LC1-F225 LC1-F265 LC1-F265 Mf Mw 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 6 6 6 6 6 6 6 6 9 9 9 9 9 9 9 9 9 9 9 9 Ancienne gamme Old range Guide Technique V9 / V9 Technical Guide 332 Anex 01 Appendix 01 GV7 6.1.1.20. Type de coordination: 2 - - - - - - - - - - - - - - - -DOL (Démarrage direct) Coordination Type: 2 - - - - - - - - - - - - - - - - - -DOL (Direct On Line) GV7 220/240 V Puissance Moteur Power motor P (kW) I (A) 7.5 28 10 36 11 39 15 52 18.5 64 22 75 30 100 37 125 45 150 55 180 Pdc BC Icu (kA) Rms (kA) 85 85 85 85 85 85 85 85 85 85 Type de coordination: 2 Coordination type: 2 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE40 25...40 GV7-RE40 25...40 GV7-RE40 25...40 GV7-RE80 48...80 GV7-RE80 48...80 GV7-RE100 60...100 GV7-RE100 60...100 GV7-RE150 90...150 GV7-RE150 90...150 GV7-RE200 132...220 DOL (Démarrage direct) DOL (Direct On Line) Nb modules Nbr of modules Contacteur Contactor LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-F115 LC1-F115 LC1-F150 LC1-F150 LC1-F185 Mf Mw 3 3 3 3 3 3 3 3 3 3 6 6 6 6 6 6 6 6 9 9 Ancienne gamme Old range GV7 380/400 V Puissance Moteur Power motor P (kW) I (A) 15 30 - - 18.5 37 - - 22 43 - - 30 59 - - 37 72 - - Pdc BC Icu (kA) Rms (kA) 25 70 25 70 25 70 25 70 25 70 45 85 25 Type de coordination: 2 Coordination type: 2 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE50 30...50 GV7-RS50 30...50 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE80 48...80 GV7-RS80 48...80 Contacteur Contactor LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 GV7-RE100 LC1-F115 60...100 DOL (Démarrage direct) DOL (Direct On Line) Nb modules Nbr of modules Mf Mw 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 6 6 - - 70 GV7-RS100 60...100 LC1-F115 6 6 55 105 25 GV7-RE100 60...100 LC1-F115 6 6 - - 70 GV7-RS100 60...100 LC1-F115 6 6 75 140 35 GV7-RE150 90...150 LC1-F150 6 6 - - 70 GV7-RS150 90...150 LC1-F150 6 6 90 170 35 GV7-RE220 132...220 LC1-F185 9 9 - - 70 GV7-RS220 132...220 LC1-F185 9 9 110 210 35 GV7-RE220 132...220 LC1-F225 9 9 - - 70 GV7-RS220 132...220 LC1-F225 9 9 Ancienne gamme Old range Guide Technique V9 / V9 Technical Guide 333 Anex 01 Appendix 01 GV7 415 V Puissance Moteur Power motor P (kW) I (A) 15 28 - - 18.5 35 - - 22 40 - - 30 55 - - 37 72 - - 45 80 - - 55 100 - - 75 135 - - 90 160 - - 110 200 - - Pdc BC Icu (kA) Rms (kA) 25 70 25 70 25 70 25 70 25 70 25 70 25 70 35 70 35 70 35 70 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE50 30...50 GV7-RS50 30...50 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE100 60...100 GV7-RS100 60...100 GV7-RE100 60...100 GV7-RS100 60...100 GV7-RE150 90...150 GV7-RS150 90...150 GV7-RE220 132...220 GV7-RS220 132...220 GV7-RE220 132...220 GV7-RS220 132...220 Type de coordination: 2 Coordination type: 2 DOL (Démarrage direct) DOL (Direct On Line) Nb modules Nbr of modules Contacteur Contactor LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-F115 LC1-F115 LC1-F115 LC1-F115 LC1-F150 LC1-F150 LC1-F185 LC1-F185 LC1-F225 LC1-F225 Mf Mw 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 6 6 6 6 6 6 6 6 6 6 6 6 9 9 9 9 9 9 9 9 Ancienne gamme Old range Guide Technique V9 / V9 Technical Guide 334 Anex 01 Appendix 01 GV7 440 V Puissance Moteur Power motor P (kW) I (A) 15 26,5 - - 18.5 33 - - 22 39 - - 30 51,5 - - 37 64 - - 45 76 - - 55 96 - - 75 124 - - 90 156 - - 110 180 - - 132 215 - - Pdc BC Icu (kA) Rms (kA) 25 70 25 70 25 70 25 70 25 70 25 70 25 70 35 70 35 70 35 70 35 70 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE100 60...100 GV7-RS100 60...100 GV7-RE150 90...150 GV7-RS150 90...150 GV7-RE150 90...150 GV7-RS150 90...150 GV7-RE220 132...220 GV7-RS220 132...220 GV7-RE220 132...220 GV7-RS220 132...220 Type de coordination: 2 Coordination type: 2 DOL (Démarrage direct) DOL (Direct On Line) Nb modules Nbr of modules Contacteur Contactor LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-F115 LC1-F115 LC1-F115 LC1-F115 LC1-F150 LC1-F150 LC1-F150 LC1-F150 LC1-F185 LC1-F185 LC1-F225 LC1-F225 Mf Mw 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 9 9 9 9 9 9 9 9 Ancienne gamme Old range Guide Technique V9 / V9 Technical Guide 335 Anex 01 Appendix 01 GV7 480 V Nema Puissance Moteur Power motor P (kW) 15 18.5 22 30 37 45 55 75 90 110 132 - Pdc BC Icu (kA) Rms (kA) 25 70 25 70 25 70 25 70 25 70 25 70 25 70 35 70 35 70 35 70 35 70 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE100 60...100 GV7-RS100 60...100 GV7-RE150 90...150 GV7-RS150 90...150 GV7-RE150 90...150 GV7-RS150 90...150 GV7-RE220 132...220 GV7-RS220 132...220 GV7-RE 220 GV7-RS 220 Type de coordination: 2 Coordination type: 2 DOL (Démarrage direct) DOL (Direct On Line) Nb modules Nbr of modules Contacteur Contactor LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-F115 LC1-F115 LC1-F115 LC1-F115 LC1-F150 LC1-F150 LC1-F150 LC1-F150 LC1-F185 LC1-F185 LC1-F225 LC1-F225 Mf Mw 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 9 9 9 9 9 9 9 9 Ancienne gamme Old range Guide Technique V9 / V9 Technical Guide 336 Anex 01 Appendix 01 GV7 6.1.1.21. Type de coordination: 1 - - - - - - - - - - - - - - - -2 sens de marche Coordination Type: 1 - - - - - - - - - - - - - - - - - -Reverse GV7 220/240 V Puissance Moteur Power motor P (kW) I (A) 11 39 15 52 18.5 64 22 75 25 85 30 100 37 125 45 150 55 180 Pdc BC Icu (kA) Rms (kA) 85 85 85 85 85 85 85 85 85 Type de coordination: 1 Coordination type: 1 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE40 25...40 GV7-RE80 48...80 GV7-RE80 48...80 GV7-RE80 48...80 GV7-RE100 60...100 GV7-RE100 60...100 GV7-RE150 90...150 GV7-RE150 90...150 GV7-RE150 90...150 Nb modules Nbr of modules Contacteur Contactor 2 x LC1-D40 2 x LC1-D65 2 x LC1-D65 2 x LC1-D80 2 x LC1-D95 2 x LC1-F115 2 x LC1-F150 2 x LC1-F150 2 x LC1-F185 Ancienne gamme Old range ** Impossible en type Mw GV7 380/400 V Puissance Moteur Power motor P (kW) I (A) 2 sens de marche Reverse Mf Mw 6 6 6 6 6 6 6 6 6 6 9 ** 9 ** 9 ** 12 ** ** Impossible in Mw type Type de coordination: 1 Coordination type: 1 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE50 30...50 GV7-RS50 30...50 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE100 60...100 Contacteur Contactor 2 x LC1-D32 2 x LC1-D32 2 x LC1-D40 2 x LC1-D40 2 x LC1-D50 2 x LC1-D50 2 x LC1-D65 2 x LC1-D65 2 x LC1-D80 2 x LC1-D80 2 x LC1-D95 2 sens de marche Reverse 15 30 - - 18.5 37 - - 22 43 - - 30 59 - - 37 72 - - 45 85 Pdc BC Icu (kA) Rms (kA) 25 70 25 70 25 70 25 70 25 70 25 Nb modules Nbr of modules - - 70 GV7-RS100 60...100 2 x LC1-D95 6 6 55 105 25 GV7-RE100 60...100 2 x LC1-F115 9 ** Mf Mw 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 - - 70 GV7-RS100 60...100 2 x LC1-F115 9 ** 75 140 35 GV7-RE150 90...150 2 x LC1-F150 9 ** - - 70 GV7-RS150 90...150 2 x LC1-F150 9 ** 90 170 35 GV7-RE220 132...220 2 x LC1-F185 12 ** - - 70 GV7-RS220 132...220 2 x LC1-F185 12 ** 110 210 35 GV7-RE220 132...220 2 x LC1-F225 12 ** - - 70 GV7-RS220 132...220 2 x LC1-F225 12 ** Ancienne gamme Old range ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide ** Impossible in Mw type 337 Anex 01 Appendix 01 GV7 415 V Puissance Moteur Power motor P (kW) I (A) 15 28 - - 18.5 35 - - 22 40 - - 30 55 - - 37 72 - - 45 80 - - 55 100 - - 75 135 - - 90 160 - - 110 200 - - Pdc BC Icu (kA) Rms (kA) 25 70 25 70 25 70 25 70 25 70 25 70 25 70 35 70 35 70 35 70 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE50 30...50 GV7-RS50 30...50 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE100 60...100 GV7-RS100 60...100 GV7-RE100 60...100 GV7-RS100 60...100 GV7-RE150 90...150 GV7-RS150 90...150 GV7-RE220 132...220 GV7-RS220 132...220 GV7-RE220 132...220 GV7-RS220 132...220 Ancienne gamme Old range ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide Type de coordination: 1 Coordination type: 1 2 sens de marche Reverse Nb modules Nbr of modules Contacteur Contactor 2 x LC1-D32 2 x LC1-D32 2 x LC1-D40 2 x LC1-D40 2 x LC1-D50 2 x LC1-D50 2 x LC1-D65 2 x LC1-D65 2 x LC1-D80 2 x LC1-D80 2 x LC1-D95 2 x LC1-D95 2 x LC1-F115 2 x LC1-F115 2 x LC1-F150 2 x LC1-F150 2 x LC1-F185 2 x LC1-F185 2 x LC1-F225 2 x LC1-F225 Mf Mw 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 9 ** 9 ** 9 ** 9 ** 12 ** 12 ** 12 ** 12 ** ** Impossible in Mw type 338 Anex 01 Appendix 01 GV7 440 V Puissance Moteur Power motor P (kW) I (A) 15 26,5 - - 18.5 33 - - 22 39 - - 30 51,5 - - 37 64 - - 45 76 - - 55 96 - - 75 124 - - 90 156 - - 110 180 - - 132 215 - - Pdc BC Icu (kA) Rms (kA) 25 65 25 65 25 65 25 65 25 65 25 65 25 65 35 65 35 65 35 65 35 65 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE100 60...100 GV7-RS100 60...100 GV7-RE150 90...150 GV7-RS150 90...150 GV7-RE150 90...150 GV7-RS150 90...150 GV7-RE220 132...220 GV7-RS220 132...220 GV7-RE220 132...220 GV7-RS220 132...220 Ancienne gamme Old range ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide Type de coordination: 1 Coordination type: 1 2 sens de marche Reverse Nb modules Nbr of modules Contacteur Contactor 2 x LC1-D32 2 x LC1-D32 2 x LC1-D32 2 x LC1-D32 2 x LC1-D40 2 x LC1-D40 2 x LC1-D65 2 x LC1-D65 2 x LC1-D65 2 x LC1-D65 2 x LC1-D80 2 x LC1-D80 2 x LC1-F115 2 x LC1-F115 2 x LC1-F150 2 x LC1-F150 2 x LC1-F185 2 x LC1-F185 2 x LC1-F225 2 x LC1-F225 2 x LC1-F265 2 x LC1-F265 Mf Mw 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 9 ** 9 ** 9 ** 9 ** 12 ** 12 ** 12 ** 12 ** 12 ** 12 ** ** Impossible in Mw type 339 Anex 01 Appendix 01 480 V Nema Puissance Moteur Power motor P (kW) 15 18.5 22 30 37 45 55 75 90 110 132 - GV7 Pdc BC Icu (kA) Rms (kA) 25 65 25 65 25 65 25 65 25 65 25 65 25 65 35 65 35 65 35 65 35 65 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE100 60...100 GV7-RS100 60...100 GV7-RE150 90...150 GV7-RS150 90...150 GV7-RE150 90...150 GV7-RS150 90...150 GV7-RE220 132...220 GV7-RS220 132...220 GV7-RE220 132...220 GV7-RS220 132...220 Ancienne gamme Old range ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide Type de coordination: 1 Coordination type: 1 2 sens de marche Reverse Nb modules Nbr of modules Contacteur Contactor 2 x LC1-D32 2 x LC1-D32 2 x LC1-D32 2 x LC1-D32 2 x LC1-D40 2 x LC1-D40 2 x LC1-D65 2 x LC1-D65 2 x LC1-D65 2 x LC1-D65 2 x LC1-D80 2 x LC1-D80 2 x LC1-F115 2 x LC1-F115 2 x LC1-F150 2 x LC1-F150 2 x LC1-F185 2 x LC1-F185 2 x LC1-F225 2 x LC1-F225 2 x LC1-F265 2 x LC1-F265 Mf Mw 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 9 ** 9 ** 9 ** 9 ** 12 ** 12 ** 12 ** 12 ** 12 ** 12 ** ** Impossible in Mw type 340 Anex 01 Appendix 01 GV7 6.1.1.22. Type de coordination: 2 - - - - - - - - - - - - - - - -2 sens de marche Coordination Type: 2 - - - - - - - - - - - - - - - - - -Reverse GV7 220/240 V Puissance Moteur Power motor P (kW) I (A) 7.5 28 10 36 11 39 15 52 18,5 64 22 75 30 100 37 125 45 150 55 180 Pdc BC Icu (kA) Rms (kA) 85 85 85 85 85 85 85 85 85 85 Type de coordination: 2 Coordination type: 2 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE40 25...40 GV7-RE40 25...40 GV7-RE40 25...40 GV7-RE80 48...80 GV7-RE80 48...80 GV7-RE100 60...100 GV7-RE100 60...100 GV7-RE150 90...150 GV7-RE150 90...150 GV7-RE220 132...220 Nb modules Nbr of modules Contacteur Contactor 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-F115 2 x LC1-F115 2 x LC1-F150 2 x LC1-F150 2 x LC1-F185 Ancienne gamme Old range ** Impossible en type Mw GV7 380/400 V Puissance Moteur Power motor P (kW) I (A) 15 30 - - 18,5 37 - - 22 43 - - 30 59 - - 37 72 - - Pdc BC Icu (kA) Rms (kA) 25 70 25 70 25 70 25 70 25 70 45 85 25 2 sens de marche Reverse Mf Mw 6 6 6 6 6 6 6 6 6 6 9 ** 9 ** 9 ** 9 ** 12 ** ** Impossible in Mw type Type de coordination: 2 Coordination type: 2 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE50 30...50 GV7-RS50 30...50 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE80 48...80 GV7-RS80 48...80 Contacteur Contactor 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 GV7-RE100 2 x LC1-F115 60...100 2 sens de marche Reverse Nb modules Nbr of modules Mf Mw 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 9 ** - - 70 GV7-RS100 60...100 2 x LC1-F115 9 ** 55 105 25 GV7-RE100 60...100 2 x LC1-F115 9 ** - - 70 GV7-RS100 60...100 2 x LC1-F115 9 ** 75 140 35 GV7-RE150 90...150 2 x LC1-F150 9 ** - - 70 GV7-RS150 90...150 2 x LC1-F150 9 ** 90 170 35 GV7-RE220 132...220 2 x LC1-F185 12 ** - - 70 GV7-RS220 132...220 2 x LC1-F185 12 ** 110 210 35 GV7-RE220 132...220 2 x LC1-F225 12 ** - - 70 GV7-RS220 132...220 2 x LC1-F225 12 ** Ancienne gamme Old range ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide ** Impossible in Mw type 341 Anex 01 Appendix 01 GV7 415 V Puissance Moteur Power motor P (kW) I (A) 15 28 - - 18,5 34 - - 22 40 - - 30 55 - - 37 72 - - 45 80 - - 55 100 - - 75 135 - - 90 160 - - 110 200 - - Pdc BC Icu (kA) Rms (kA) 25 70 25 70 25 70 25 70 25 70 25 70 25 70 35 70 35 70 35 70 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE50 30...50 GV7-RS50 30...50 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE100 60...100 GV7-RS100 60...100 GV7-RE100 60...100 GV7-RS100 60...100 GV7-RE150 90...150 GV7-RS150 90...150 GV7-RE220 132...220 GV7-RS220 132...220 GV7-RE220 132...220 GV7-RS220 132...220 Ancienne gamme Old range ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide Type de coordination: 2 Coordination type: 2 2 sens de marche Reverse Nb modules Nbr of modules Contacteur Contactor 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-F115 2 x LC1-F115 2 x LC1-F115 2 x LC1-F115 2 x LC1-F150 2 x LC1-F150 2 x LC1-F185 2 x LC1-F185 2 x LC1-F225 2 x LC1-F225 Mf Mw 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 ** 9 ** 9 ** 9 ** 9 ** 9 ** 9 ** 12 ** 12 ** 12 ** 12 ** ** Impossible in Mw type 342 Anex 01 Appendix 01 GV7 440 V Puissance Moteur Power motor P (kW) I (A) 15 26,5 - - 18,5 33 - - 22 39 - - 30 51,5 - - 37 64 - - 45 76 - - 55 96 - - 75 124 - - 90 156 - - 110 180 - - 132 215 - - Pdc BC Icu (kA) Rms (kA) 25 70 25 70 25 70 25 70 25 70 25 70 25 70 35 70 35 70 35 70 35 70 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE100 60...100 GV7-RS100 60...100 GV7-RE150 90...150 GV7-RS150 90...150 GV7-RE150 90...150 GV7-RS150 90...150 GV7-RE220 132...220 GV7-RS220 132...220 GV7-RE220 132...220 GV7-RS220 132...220 Ancienne gamme Old range ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide Type de coordination: 2 Coordination type: 2 2 sens de marche Reverse Nb modules Nbr of modules Contacteur Contactor 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-F115 2 x LC1-F115 2 x LC1-F115 2 x LC1-F115 2 x LC1-F150 2 x LC1-F150 2 x LC1-F150 2 x LC1-F150 2 x LC1-F185 2 x LC1-F185 2 x LC1-F225 2 x LC1-F225 Mf Mw 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 9 ** 9 ** 9 ** 9 ** 9 ** 9 ** 9 ** 9 ** 12 ** 12 ** 12 ** 12 ** ** Impossible in Mw type 343 Anex 01 Appendix 01 480 V Nema Puissance Moteur Power motor P (kW) 15 18,5 22 30 37 45 55 75 90 110 132 - GV7 Pdc BC Icu (kA) Rms (kA) 25 70 25 70 25 70 25 70 25 70 25 70 25 70 35 70 35 70 35 70 35 70 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE100 60...100 GV7-RS100 60...100 GV7-RE150 90...150 GV7-RS150 90...150 GV7-RE150 90...150 GV7-RS150 90...150 GV7-RE220 132...220 GV7-RS220 132...220 GV7-RE220 132...220 GV7-RS220 132...220 Ancienne gamme Old range ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide Type de coordination: 2 Coordination type: 2 2 sens de marche Reverse Nb modules Nbr of modules Contacteur Contactor 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-D80 2 x LC1-F115 2 x LC1-F115 2 x LC1-F115 2 x LC1-F115 2 x LC1-F150 2 x LC1-F150 2 x LC1-F150 2 x LC1-F150 2 x LC1-F185 2 x LC1-F185 2 x LC1-F225 2 x LC1-F225 Mf Mw 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 9 ** 9 ** 9 ** 9 ** 9 ** 9 ** 9 ** 9 ** 12 ** 12 ** 12 ** 12 ** ** Impossible in Mw type 344 Anex 01 Appendix 01 GV7 6.1.1.23. Type de coordination: 1 - - - - - - - - - - - - - - - -Etoile / Triangle (Y/∆) Coordination Type: 1 - - - - - - - - - - - - - - - - - -STAR / DELTA (Y/∆) Démarrage: Normal Start-up: Normal 220/240 V Puissance Moteur Power motor P (kW) I (A) 11 39 18.5 64 22 75 25 85 30 100 37 125 45 150 55 180 GV7 Pdc BC Icu (kA) Rms (kA) 85 85 85 85 85 85 85 85 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE50 30...50 GV7-RE80 48...80 GV7-RE100 60...100 GV7-RE100 60...100 GV7-RE100 60...100 GV7-RE150 90...150 GV7-RE150 90...150 GV7-RE220 132...220 Nb modules Nbr of modules Contacteur Contactor 3 x LC1-D18 3 x LC1-D40 3 x LC1-D50 3 x LC1-D50 3 x LC1-D50 3 x LC1-D80 3 x LC1-F115 3 x LC1-F115 Ancienne gamme Old range ** Impossible en type Mw 380/400 V Puissance Moteur Power motor P (kW) I (A) 15 30 - - 18.5 37 - - 22 44 - - 30 59 - - 37 72 - - 45 85 - - 55 105 - - 75 140 - - 90 170 - - 110 210 - - GV7 Pdc BC Icu (kA) Rms (kA) 25 70 25 70 25 70 25 70 25 70 25 70 25 70 35 70 35 70 35 70 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE50 30...50 GV7-RS50 30...50 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE100 60...100 GV7-RS100 60...100 GV7-RE100 60...100 GV7-RS100 60...100 GV7-RE150 90...150 GV7-RS150 90...150 GV7-RE220 132...220 GV7-RS220 132...220 GV7-RE220 132...220 GV7-RS220 132...220 Ancienne gamme Old range ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Type de coordination: 1 Coordination type: 1 Mf Mw 6 6 6 9 6 9 6 9 9 9 6 9 12 ** 12 ** ** Impossible in Mw type Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Type de coordination: 1 Coordination type: 1 Nb modules Nbr of modules Contacteur Contactor 3 x LC1-D18 3 x LC1-D18 3 x LC1-D18 3 x LC1-D18 3 x LC1-D32 3 x LC1-D32 3 x LC1-D32 3 x LC1-D32 3 x LC1-D40 3 x LC1-D40 3 x LC1-D50 3 x LC1-D50 3 x LC1-D50 3 x LC1-D50 3 x LC1-D80 3 x LC1-D80 3 x LC1-F115 3 x LC1-F115 3 x LC1-F115 3 x LC1-F115 Mf Mw 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 12 ** 12 ** 12 ** 12 ** ** Impossible in Mw type 345 Anex 01 Appendix 01 GV7 415 V Puissance Moteur Power motor P (kW) I (A) 15 28 - - 18.5 35 - - 22 40 - - 30 55 - - 37 72 - - 45 80 - - 55 100 - - 75 135 - - 90 160 - - 110 200 - - Pdc BC Icu (kA) Rms (kA) 25 70 25 70 25 70 25 70 25 70 25 70 25 70 35 70 35 70 35 70 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE50 30...50 GV7-RS50 30...50 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE100 60...100 GV7-RS100 60...100 GV7-RE100 60...100 GV7-RS100 60...100 GV7-RE150 90...150 GV7-RS150 90...150 GV7-RE220 132...220 GV7-RS220 132...220 GV7-RE220 132...220 GV7-RS220 132...220 Ancienne gamme Old range ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Type de coordination: 1 Coordination type: 1 Nb modules Nbr of modules Contacteur Contactor 3 x LC1-D18 3 x LC1-D18 3 x LC1-D18 3 x LC1-D18 3 x LC1-D32 3 x LC1-D32 3 x LC1-D32 3 x LC1-D32 3 x LC1-D40 3 x LC1-D40 3 x LC1-D50 3 x LC1-D50 3 x LC1-D50 3 x LC1-D50 3 x LC1-D80 3 x LC1-D80 3 x LC1-F115 3 x LC1-F115 3 x LC1-F115 3 x LC1-F115 Mf Mw 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 12 ** 12 ** 12 ** 12 ** ** Impossible in Mw type 346 Anex 01 Appendix 01 GV7 440 V Puissance Moteur Power motor P (kW) I (A) 15 26,5 - - 18.5 33 - - 22 39 - - 30 51,5 - - 37 64 - - 45 76 - - 55 96 - - 75 124 - - 90 156 - - 110 180 - - 132 215 - - Pdc BC Icu (kA) Rms (kA) 25 70 25 70 25 70 25 70 25 70 25 70 25 70 35 70 35 70 35 70 35 70 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE100 60...100 GV7-RS100 60...100 GV7-RE150 90...150 GV7-RS150 90...150 GV7-RE150 90...150 GV7-RS150 90...150 GV7-RE220 132...220 GV7-RS220 132...220 GV7-RE220 132...220 GV7-RS220 132...220 Ancienne gamme Old range ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Type de coordination: 1 Coordination type: 1 Nb modules Nbr of modules Contacteur Contactor 3 x LC1-D18 3 x LC1-D18 3 x LC1-D18 3 x LC1-D18 3 x LC1-D18 3 x LC1-D18 3 x LC1-D32 3 x LC1-D32 3 x LC1-D40 3 x LC1-D40 3 x LC1-D50 3 x LC1-D50 3 x LC1-D50 3 x LC1-D50 3 x LC1-D80 3 x LC1-D80 3 x LC1-F115 3 x LC1-F115 3 x LC1-F115 3 x LC1-F115 3 x LC1-F150 3 x LC1-F150 Mf Mw 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 12 ** 12 ** 12 ** 12 ** 12 ** 12 ** ** Impossible in Mw type 347 Anex 01 Appendix 01 480 V Nema Puissance Moteur Power motor P (kW) 15 18.5 22 30 37 45 55 75 90 110 132 - GV7 Pdc BC Icu (kA) Rms (kA) 25 70 25 70 25 70 25 70 25 70 25 70 25 70 35 70 35 70 35 70 35 70 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE100 60...100 GV7-RS100 60...100 GV7-RE150 90...150 GV7-RS150 90...150 GV7-RE150 90...150 GV7-RS150 90...150 GV7-RE220 132...220 GV7-RS220 132...220 GV7-RE220 132...220 GV7-RS220 132...220 Ancienne gamme Old range ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Type de coordination: 1 Coordination type: 1 Nb modules Nbr of modules Contacteur Contactor 3 x LC1-D18 3 x LC1-D18 3 x LC1-D18 3 x LC1-D18 3 x LC1-D18 3 x LC1-D18 3 x LC1-D32 3 x LC1-D32 3 x LC1-D40 3 x LC1-D40 3 x LC1-D50 3 x LC1-D50 3 x LC1-D50 3 x LC1-D50 3 x LC1-D80 3 x LC1-D80 3 x LC1-F115 3 x LC1-F115 3 x LC1-F115 3 x LC1-F115 3 x LC1-F150 3 x LC1-F150 Mf Mw 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 12 ** 12 ** 12 ** 12 ** 12 ** 12 ** ** Impossible in Mw type 348 Anex 01 Appendix 01 GV7 6.1.1.24. Type de coordination: 2 - - - - - - - - - - - - - - - -Etoile / Triangle (Y/∆) Coordination Type: 2 - - - - - - - - - - - - - - - - - -STAR / DELTA (Y/∆) Démarrage: Normal Start-up: Normal 220/240 V Puissance Moteur Power motor P (kW) I (A) 7,5 28 10 36 11 39 15 52 18,5 64 22 75 30 100 37 125 45 150 55 180 GV7 Pdc BC Icu (kA) Rms (kA) 85 85 85 85 85 85 85 85 85 85 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE40 25...40 GV7-RE40 25...40 GV7-RE40 25...40 GV7-RE80 48...80 GV7-RE80 48...80 GV7-RE100 60...100 GV7-RE100 60...100 GV7-RE150 90...150 GV7-RE150 90...150 GV7-RE220 132...220 Nb modules Nbr of modules Contacteur Contactor 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-F115 3 x LC1-F115 3 x LC1-F150 3 x LC1-F150 3 x LC1-F185 Ancienne gamme Old range ** Impossible en type Mw 380/400 V Puissance Moteur Power motor P (kW) I (A) 15 30 - - 18,5 37 - - 22 43 - - 30 59 - - 37 72 - - 45 85 - - 55 105 - - 75 140 - - 90 170 - - 110 210 - - GV7 Pdc BC Icu (kA) Rms (kA) 25 70 25 70 25 70 25 70 25 70 25 70 25 70 35 70 35 70 35 70 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE50 30...50 GV7-RS50 30...50 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE100 60...100 GV7-RS100 60...100 GV7-RE100 60...100 GV7-RS100 60...100 GV7-RE150 90...150 GV7-RS150 90...150 GV7-RE220 132...220 GV7-RS220 132...220 GV7-RE220 132...220 GV7-RS220 132...220 Ancienne gamme Old range ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Type de coordination: 2 Coordination type: 2 Mf Mw 6 9 6 9 6 9 6 9 6 9 12 ** 12 ** 12 ** 12 ** 16 ** ** Impossible in Mw type Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Type de coordination: 2 Coordination type: 2 Nb modules Nbr of modules Contacteur Contactor 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-F115 3 x LC1-F115 3 x LC1-F115 3 x LC1-F115 3 x LC1-F150 3 x LC1-F150 3 x LC1-F185 3 x LC1-F185 3 x LC1-F225 3 x LC1-F225 Mf Mw 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 12 ** 12 ** 12 ** 12 ** 12 ** 12 ** 16 ** 16 ** 16 ** 16 ** ** Impossible in Mw type 349 Anex 01 Appendix 01 GV7 415 V Puissance Moteur Power motor P (kW) I (A) 15 28 - - 18,5 34 - - 22 40 - - 30 55 - - 37 72 - - 45 80 - - 55 100 - - 75 135 - - 90 160 - - 110 200 - - Pdc BC Icu (kA) Rms (kA) 25 70 25 70 25 70 25 70 25 70 25 70 25 70 35 70 35 70 35 70 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE50 30...50 GV7-RS50 30...50 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE100 60...100 GV7-RS100 60...100 GV7-RE100 60...100 GV7-RS100 60...100 GV7-RE150 90...150 GV7-RS150 90...150 GV7-RE220 132...220 GV7-RS220 132...220 GV7-RE220 132...220 GV7-RS220 132...220 Ancienne gamme Old range ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Type de coordination: 2 Coordination type: 2 Nb modules Nbr of modules Contacteur Contactor 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-F115 3 x LC1-F115 3 x LC1-F115 3 x LC1-F115 3 x LC1-F150 3 x LC1-F150 3 x LC1-F185 3 x LC1-F185 3 x LC1-F225 3 x LC1-F225 Mf Mw 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 12 ** 12 ** 12 ** 12 ** 12 ** 12 ** 16 ** 16 ** 16 ** 16 ** ** Impossible in Mw type 350 Anex 01 Appendix 01 GV7 440 V Puissance Moteur Power motor P (kW) I (A) 15 26,5 - - 18,5 33 - - 22 39 - - 30 51,5 - - 37 64 - - 45 76 - - 55 96 - - 75 124 - - 90 156 - - 110 180 - - 132 215 - - Pdc BC Icu (kA) Rms (kA) 25 70 25 70 25 70 25 70 25 70 25 70 25 70 35 70 35 70 35 70 35 70 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE100 60...100 GV7-RS100 60...100 GV7-RE150 90...150 GV7-RS150 90...150 GV7-RE150 90...150 GV7-RS150 90...150 GV7-RE220 132...220 GV7-RS220 132...220 GV7-RE220 132...220 GV7-RS220 132...220 Ancienne gamme Old range ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Type de coordination: 2 Coordination type: 2 Nb modules Nbr of modules Contacteur Contactor 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-F115 3 x LC1-F115 3 x LC1-F115 3 x LC1-F115 3 x LC1-F150 3 x LC1-F150 3 x LC1-F150 3 x LC1-F150 3 x LC1-F185 3 x LC1-F185 3 x LC1-F225 3 x LC1-F225 Mf Mw 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 12 ** 12 ** 12 ** 12 ** 12 ** 12 ** 12 ** 12 ** 16 ** 16 ** 16 ** 16 ** ** Impossible in Mw type 351 Anex 01 Appendix 01 480 V Nema Puissance Moteur Power motor P (kW) 15 18,5 22 30 37 45 55 75 90 110 132 - GV7 Pdc BC Icu (kA) Rms (kA) 25 70 25 70 25 70 25 70 25 70 25 70 25 70 35 70 35 70 35 70 35 70 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE40 25...40 GV7-RS40 25...40 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE80 48...80 GV7-RS80 48...80 GV7-RE100 60...100 GV7-RS100 60...100 GV7-RE150 90...150 GV7-RS150 90...150 GV7-RE150 90...150 GV7-RS150 90...150 GV7-RE220 132...220 GV7-RS220 132...220 GV7-RE220 132...220 GV7-RS220 132...220 Ancienne gamme Old range ** Impossible en type Mw Guide Technique V9 / V9 Technical Guide Etoile / Triangle (Y/∆) STAR / DELTA (Y/∆) Type de coordination: 2 Coordination type: 2 Nb modules Nbr of modules Contacteur Contactor 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-F115 3 x LC1-F115 3 x LC1-F115 3 x LC1-F115 3 x LC1-F150 3 x LC1-F150 3 x LC1-F150 3 x LC1-F150 3 x LC1-F185 3 x LC1-F185 3 x LC1-F225 3 x LC1-F225 Mf Mw 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 12 ** 12 ** 12 ** 12 ** 12 ** 12 ** 12 ** 12 ** 16 ** 16 ** 16 ** 16 ** ** Impossible in Mw type 352 Anex 01 Appendix 01 INTEGRAL 6.1.1.25. Contacteurs-Disjoncteurs INTEGRAL - - - - - -DOL (Démarrage direct) INTEGRAL contactors-circuit breakers - - - - -DOL (Direct On Line) Coordination totale Total coordination 220/230 V Contacteurs-Disjoncteurs INTEGRAL INTEGRAL contactors-circuit breakers Puissance Moteur Power motor P (kW) I (A) Icu (kA) Rms (kA) 0,06 0,38 70 0,09 0,65 70 0,12 0,75 70 0,18 1,04 70 0,25 1,47 70 0,37 2 70 - - - 0,55 2,8 70 0,75 3,6 70 1,1 5,2 70 - - - 1,5 6,8 70 2,2 9,6 70 3 11,5 70 - - - 4 14,5 70 - - - 5,5 2,2 70 7,5 28 70 DOL (Démarrage direct) DOL (Direct On Line) Contacteur-disjoncteur sans Module de protection Contactor-Circuit Breaker without protection Module Sectionnement par Sectionnement par pôles principaux pôles spécifiques Isolation by main poles Isolation by specifics poles LD1-LB030 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LC030 LD4-LC130 LD1-LC030 LD4-LC130 *: Icu = 40 kA pour LD1-LB; Icu = 70 kA pour LDz-LC. **: En fonction du nombre d’auxiliaires. LD1-LB: LDz-LC: LDz-LD: Guide Technique V9 / V9 Technical Guide Module de protection Protection Module Référence Reference Nb modules Nbr of modules Mf Mw LB1-LB03P03 3 3 ou 6** LB1-LB03P05 3 3 ou 6** LB1-LC03M05 3 - LB1-LB03P06 3 3 ou 6** LB1-LC03M06 3 - LB1-LB03P07 3 3 ou 6** LB1-LC03M07 3 - LB1-LB03P08 3 3 ou 6** LB1-LC03M08 3 - LB1-LB03P10 3 3 ou 6** LB1-LC03M10 3 - LB1-LB03P13 3 3 ou 6** LB1-LC03M13 3 - LB1-LB03P17 3 3 ou 6** LB1-LC03M17 3 - LB1-LB03P21 3 3 ou 6** LB1-LC03M17 3 - LB1-LC03M22 3 3 ou 6** LB1-LC03M53 3 3 ou 6** *: Rms = 40 kA for LD1-LB; Rms = 70 kA for LDz-LC. **: According to the number of auxiliaries. Integral 18. Integral 32. Integral 63. 353 Anex 01 Appendix 01 400/415 V Contacteurs-Disjoncteurs INTEGRAL INTEGRAL contactors-circuit breakers Puissance Moteur Power motor P (kW) I (A) Icu (kA) Rms (kA) 0,06 0,22 70 0,09 0,36 70 0,12 0,42 70 0,18 0,6 70 0,25 0,88 70 - - - 0,37 1 70 0,55 1,5 70 0,75 2 70 - - - 1,1 2,5 70 1,5 3,5 70 2,2 5 70 - - - 3 6,5 70 4 8,4 70 5,5 11 70 7,5 14,8 70 9 18,1 70 - - - 11 21 70 15 28,5 70 18,5 35 70 22 42 70 30 57 70 DOL (Démarrage direct) DOL (Direct On Line) Contacteur-disjoncteur sans Module de protection Contactor-Circuit Breaker without protection Module Sectionnement par Sectionnement par pôles principaux pôles spécifiques Isolation by main poles Isolation by specifics poles LD1-LB030 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LC030 LD4-LC130 LD1-LC030 LD4-LC130 LD1-LD030 LD4-LD130 LD1-LD030 LD4-LD130 LD1-LD030 LD4-LD130 *: Icu = 40 kA pour LD1-LB; Icu = 70 kA pour LDz-LC. **: En fonction du nombre d’auxiliaires. LD1-LB: LDz-LC: LDz-LD: Guide Technique V9 / V9 Technical Guide Module de protection Protection Module Référence Reference Nb modules Nbr of modules Mf Mw LB1-LB03P02 3 3 ou 6** LB1-LB03P03 3 3 ou 6** LB1-LC03M03 - - LB1-LB03P04 3 3 ou 6** LB1-LC03M04 3 - LB1-LB03P05 3 3 ou 6** LB1-LC03M05 3 - LB1-LB03P06 3 3 ou 6** LB1-LC03M06 3 - LB1-LB03P07 3 3 ou 6** LB1-LC03M07 3 - LB1-LB03P08 3 3 ou 6** LB1-LC03M08 3 - LB1-LB03P10 3 3 ou 6** LB1-LC03M10 3 - LB1-LB03P13 3 3 ou 6** LB1-LC03M13 3 - LB1-LB03P17 3 3 ou 6** LB1-LC03M17 3 - LB1-LB03P21 3 3 ou 6** LB1-LC03M22 3 - LB1-LC03M22 3 3 ou 6** LB1-LC03M53 3 3 ou 6** LB1-LD03M55 6 6 LB1-LD03M57 6 6 LB1-LD03M61 6 6 *: Rms = 40 kA for LD1-LB; Rms = 70 kA for LDz-LC. **: According to the number of auxiliaries. Integral 18. Integral 32. Integral 63. 354 Anex 01 Appendix 01 440 V Contacteurs-Disjoncteurs INTEGRAL INTEGRAL contactors-circuit breakers Puissance Moteur Power motor P (kW) I (A) Icu (kA) Rms (kA) 0,06 0,19 70 0,09 0,28 70 0,12 0,37 70 - - - 0,18 0,55 70 0,25 0,76 70 - - - 0,37 1 70 0,55 1,36 70 0,75 1,68 70 1,1 2,37 70 - - - 1,5 3,06 70 2,2 4,42 * 3 5,77 * 4 7,9 * - - - 5,5 10,4 * 7,5 13,7 * 9 16,9 * 11 20,1 70 15 26,5 30 18,5 32,8 70 22 39 70 30 51,5 40 33 58,5 40 DOL (Démarrage direct) DOL (Direct On Line) Contacteur-disjoncteur sans Module de protection Contactor-Circuit Breaker without protection Module Sectionnement par Sectionnement par pôles principaux pôles spécifiques Isolation by main poles Isolation by specifics poles LD1-LB030 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LB030 LD1-LC030 LD4-LC130 LD1-LC030 LD4-LC130 LD1-LC030 LD4-LC130 LD1-LD030 LD4-LD130 LD1-LD030 LD4-LD130 - *: Icu = 40 kA pour LD1-LB; Icu = 70 kA pour LDz-LC. **: En fonction du nombre d’auxiliaires. LD1-LB: LDz-LC: LDz-LD: Guide Technique V9 / V9 Technical Guide Module de protection Protection Module Référence Reference Nb modules Nbr of modules Mf Mw LB1-LB03P02 3 3 ou 6** LB1-LB03P03 3 3 ou 6** LB1-LC03M03 3 - LB1-LB03P04 3 3 ou 6** LB1-LC03M04 3 - LB1-LB03P05 3 3 ou 6** LB1-LC03M05 3 - LB1-LB03P06 3 3 ou 6** LB1-LC03M06 3 - LB1-LB03P07 3 3 ou 6** - LB1-LC03M07 3 LB1-LB03P08 3 3 ou 6** LB1-LC03M08 3 - LB1-LB03P10 3 3 ou 6** LB1-LC03M10 3 - LB1-LB03P13 3 3 ou 6** LB1-LC03M13 3 - LB1-LB03P17 3 3 ou 6** LB1-LC03M17 3 - LB1-LB03P21 3 3 ou 6** LB1-LC03M22 3 - LB1-LC03M22 3 3 ou 6** LB1-LC03M53 3 3 ou 6** LB1-LD03M55 6 6 - - - LB1-LD03M61 6 6 - - - *: Rms = 40 kA for LD1-LB; Rms = 70 kA for LDz-LC. **: According to the number of auxiliaries. Integral 18. Integral 32. Integral 63. 355 Anex 01 Appendix 01 INTEGRAL 6.1.1.26. Contacteurs-Disjoncteurs INTEGRAL - - - - - -2 sens de marche INTEGRAL contactors-circuit breakers - - - - -Reverse Coordination totale Total coordination 220/230 V Contacteurs-Disjoncteurs INTEGRAL INTEGRAL contactors-circuit breakers Puissance Moteur Power motor P (kW) I (A) Icu (kA) Rms (kA) 0,06 0,38 70 0,09 0,65 70 0,12 0,75 70 0,18 1,04 70 0,25 1,47 70 0,37 2 70 - - - 0,55 2,8 70 0,75 3,6 70 1,1 5,2 70 - - - 1,5 6,8 70 2,2 9,6 70 3 11,5 70 - - - 4 14,5 70 - - - 5,5 2,2 70 7,5 28 70 2 sens de marche Reverse Contacteur-disjoncteur sans Module de protection Contactor-Circuit Breaker without protection Module Sectionnement par Sectionnement par pôles principaux pôles spécifiques Isolation by main poles Isolation by specifics poles LD5-LB130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LC130 LD5-LC130 *: Icu = 40 kA pour LD5-LB; Icu = 70 kA pour LD5-LC. LD5-LB: LD5-LC: LD5-LD: Guide Technique V9 / V9 Technical Guide *: Module de protection Protection Module Référence Reference Nb modules Nbr of modules Mf Mw LB1-LB03P03 3 6 LB1-LB03P05 3 6 LB1-LC03M05 6 - LB1-LB03P06 3 6 LB1-LC03M06 6 - LB1-LB03P07 3 6 LB1-LC03M07 6 - LB1-LB03P08 3 6 LB1-LC03M08 6 - LB1-LB03P10 3 6 LB1-LC03M10 6 - LB1-LB03P13 3 6 LB1-LC03M13 6 - LB1-LB03P17 3 6 LB1-LC03M17 6 - LB1-LB03P21 3 6 LB1-LC03M17 6 - LB1-LC03M22 6 6 LB1-LC03M53 6 6 Rms = 40 kA for LD5-LB; Rms = 70 kA for LD5-LC. Integral 18. Integral 32. Integral 63. 356 Anex 01 Appendix 01 400/415 V Contacteurs-Disjoncteurs INTEGRAL INTEGRAL contactors-circuit breakers Puissance Moteur Power motor P (kW) I (A) Icu (kA) Rms (kA) 0,06 0,22 70 0,09 0,36 70 - - - 0,12 0,42 70 0,18 0,6 70 0,25 0,88 70 - - - 0,37 1 70 0,55 1,5 70 0,75 2 70 - - - 1,1 2,5 70 1,5 3,5 70 2,2 5 70 - - - 3 6,5 70 4 8,4 70 5,5 11 70 7,5 14,8 70 9 18,1 70 - - - 11 21 70 15 28,5 70 18,5 35 70 22 42 70 30 57 70 2 sens de marche Reverse Contacteur-disjoncteur sans Module de protection Contactor-Circuit Breaker without protection Module Sectionnement par Sectionnement par pôles principaux pôles spécifiques Isolation by main poles Isolation by specifics poles LD5-LB130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LC130 LD5-LC130 LD5-LD130 LD5-LD130 LD5-LD130 *: Icu = 40 kA pour LD5-LB; Icu = 70 kA pour LD5-LC. LD5-LB: LD5-LC: LD5-LD: Guide Technique V9 / V9 Technical Guide *: Module de protection Protection Module Référence Reference Nb modules Nbr of modules Mf Mw LB1-LB03P02 3 6 LB1-LB03P03 3 6 LB1-LC03M03 6 - LB1-LB03P04 3 6 LB1-LC03M04 6 - LB1-LB03P05 3 6 LB1-LC03M05 6 - LB1-LB03P06 3 6 LB1-LC03M06 6 - LB1-LB03P07 3 6 LB1-LC03M07 6 - LB1-LB03P08 3 6 LB1-LC03M08 6 - LB1-LB03P10 3 6 LB1-LC03M10 6 - LB1-LB03P13 3 6 LB1-LC03M13 6 - LB1-LB03P17 3 6 LB1-LC03M17 6 - LB1-LB03P21 3 6 LB1-LC03M22 6 - LB1-LC03M22 6 6 LB1-LC03M53 6 6 LB1-LD03M55 6 6** LB1-LD03M57 6 6** LB1-LD03M61 6 6** Rms = 40 kA for LD5-LB; Rms = 70 kA for LD5-LC. Integral 18. Integral 32. Integral 63. 357 Anex 01 Appendix 01 440 V Contacteurs-Disjoncteurs INTEGRAL INTEGRAL contactors-circuit breakers Puissance Moteur Power motor P (kW) I (A) Icu (kA) Rms (kA) 0,06 0,19 70 0,09 0,28 70 0,12 0,37 70 - - - 0,18 0,55 70 0,25 0,76 70 - - - 0,37 1 70 0,55 1,36 70 0,75 1,68 70 1,1 2,37 70 - - - 1,5 3,06 70 2,2 4,42 * 3 5,77 * 4 7,9 * - - - 5,5 10,4 * 7,5 13,7 * 9 16,9 * - - - 11 20,1 70 15 26,5 30 18,5 32,8 70 22 39 70 30 51,5 40 33 58,5 40 2 sens de marche Reverse Contacteur-disjoncteur sans Module de protection Contactor-Circuit Breaker without protection Module Sectionnement par Sectionnement par pôles principaux pôles spécifiques Isolation by main poles Isolation by specifics poles LD5-LB130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LB130 LD5-LC130 LD5-LC130 LD5-LC130 LD5-LD130 LD5-LD130 - *: Icu = 40 kA pour LD5-LB; Icu = 70 kA pour LD5-LC. **: 9 avec transformateur LD5-LB: LD5-LC: LD5-LD: Guide Technique V9 / V9 Technical Guide Module de protection Protection Module Référence Reference Nb modules Nbr of modules Mf Mw LB1-LB03P02 3 6 LB1-LB03P03 3 6 LB1-LC03M03 6 - LB1-LB03P04 3 6 LB1-LC03M04 6 - LB1-LB03P05 3 6 LB1-LC03M05 6 - LB1-LB03P06 3 6 LB1-LC03M06 6 - LB1-LB03P07 3 6 LB1-LC03M07 6 - LB1-LB03P08 3 6 LB1-LC03M08 6 - LB1-LB03P10 3 6 LB1-LC03M10 6 - LB1-LB03P13 3 6 LB1-LC03M13 6 - LB1-LB03P17 3 6 LB1-LC03M17 6 - LB1-LB03P21 3 6 LB1-LC03M22 6 - LB1-LC03M22 6 6 LB1-LC03M53 6 6 LB1-LD03M55 6 6** - - - LB1-LD03M61 6 6** - - - *: Rms = 40 kA for LD5-LB; Rms = 70 kA for LD5-LC. **: 9 with transformer Integral 18. Integral 32. Integral 63. 358 Anex 01 Appendix 01 6.1.1.27. GV2-P Type de coordination: 1 - - - - - - - - - - - - - - - -DOL monophasé (Démarrage direct) Coordination type: 1 - - - - - - - - - - - - - - - - - - -Single phase - DOL (Direct On Line) GV2-P 220/230 V Puissance Moteur Power motor P (kW) I (A) 0,09 0,5 0,12 1,0 0,25 2,0 0,37 3,0 0,55 4,0 0,75 5,0 1,1 7,4 1,5 9,3 1,8 11,7 2,2 16,0 3 18,3 4 23,5 Pdc BC Icu (kA) Rms (kA) 50 50 50 50 50 50 50 50 50 50 50 50 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV2-P04 0,4..0,63 GV2-P06 1...1,6 GV2-P07 1,6...2,5 GV2-P08 2,5...4 GV2-P10 4...6,3 GV2-P10 4...6,3 GV2-P14 6...10 GV2-P14 6...10 GV2-P16 9...14 GV2-P20 13...18 GV2-P21 17...23 GV2-P22 20...25 Type de coordination: 1 Coordination type: 1 DOL monophasé (Démarrage direct) Single phase - DOL (Direct On Line) Nb modules Nbr of modules Contacteur Contactor LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K09 LC1-K09 LC1-D12 LC1-D18 LC1-D25 LC1-D25 Mw 3 3 3 3 3 3 3 3 3 3 3 3 Ancienne gamme Old range 6.1.1.28. GV2-P Type de coordination: 2 - - - - - - - - - - - - - - - -DOL monophasé (Démarrage direct) Coordination type: 2 - - - - - - - - - - - - - - - - - - -Single phase - DOL (Direct On Line) GV2-P 220/230 V Puissance Moteur Power motor P (kW) I (A) 0,09 0,5 0,12 1,0 0,25 2,0 0,37 3,0 0,55 4,0 0,75 5,0 1,1 7,4 1,5 9,3 1,8 11,7 2,2 16 3 18,3 4 23,5 Pdc BC Icu (kA) Rms (kA) 130 130 130 130 130 130 130 130 130 130 130 130 Appareillage Puissance Power Switchgear Disjoncteur (calibre [A]) Circuit Breaker (rating [A]) GV2-P04 0,4..0,63 GV2-P06 1...1,6 GV2-P07 1,6...2,5 GV2-P08 2,5...4 GV2-P10 4...6,3 GV2-P10 4...6,3 GV2-P14 6...10 GV2-P14 6...10 GV2-P16 9...14 GV2-P20 13...18 GV2-P21 17...23 GV2-P22 20...25 Type de coordination: 2 Coordination type: 2 DOL monophasé (Démarrage direct) Single phase - DOL (Direct On Line) Nb modules Nbr of modules Contacteur Contactor LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D25 LC1-D25 LC1-D25 LC1-D25 Mw 3 3 3 3 3 3 3 3 3 3 3 3 Ancienne gamme Old range Guide Technique V9 / V9 Technical Guide 359 Anex 01 Appendix 01 6.1.1.29. Compact NS80H-MA Type de coordination: 1 - - - - - - - - - - - - - - - -DOL monophasé (Démarrage direct) Coordination type: 1 - - - - - - - - - - - - - - - - - - -Single phase - DOL (Direct On Line) Démarrage: Normal Performance de coupure: égale au pouvoir de coupure du disjoncteur Compact NS80H-MA 220/230 V Puissance Moteur Power motor P (kW) I (A) 0,12 1,0 0,25 2,0 0,37 3,0 0,55 4,0 0,75 5,0 1,1 7,4 1,5 9,3 1,8 11,7 2,2 16,0 3 18,3 4 23,5 Disjoncteurs Circuit Breaker Type Type NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA NS80H-MA Cal (A) Rat (A) 2,5 2,5 6,3 6,3 6,3 12,5 12,5 25 25 25 50 Start-up: Normal Breaking characteristics: equal to the circuit breaker’s breaking capacity Type de coordination: 1 Coordination type: 1 Contacteurs Contactor Type Type LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D18 LC1-D25 LC1-D32 LC1-D32 Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1310 4...6 LR2-D1312 5,5...8 LR2-D1314 7...10 LR2-D1318 9...13 LR2-D1321 12...18 LR2-D1322 17...25 LR2-D1322 17...25 DOL monophasé (Démarrage direct) Single phase - DOL (Direct On Line) Nb modules Nbr of modules Mw 3 3 3 3 3 3 3 3 3 3 3 Ancienne gamme Old range 6.1.1.30. Compact NS80H-MA Type de coordination: 2 - - - - - - - - - - - - - - - -DOL monophasé (Démarrage direct) Coordination type: 2 - - - - - - - - - - - - - - - - - - -Single phase - DOL (Direct On Line) Démarrage: Normal Start-up: Normal 220/230 V Compact NS80H-MA Performance de coupure: Icu = 100 kA Breaking characteristics: Icu = 100 kA Puissance Moteur Disjoncteurs Power motor Circuit Breaker P (kW) I (A) Type Type 0,12 1,0 NS80H-MA 0,25 2,0 NS80H-MA 0,37 3,0 NS80H-MA 0,55 4,0 NS80H-MA 0,75 5,0 NS80H-MA 1,1 7,4 NS80H-MA 1,5 9,3 NS80H-MA 1,8 11,7 NS80H-MA 2,2 16,0 NS80H-MA Cal (A) Rat (A) 2,5 2,5 6,3 6,3 6,3 12,5 12,5 25 25 Type de coordination: 2 Coordination type: 2 Contacteurs Contactor Type Type LC1-D09 LC1-D09 LC1-D18 LC1-D25 LC1-D25 LC1-D32 LC1-D32 LC1-D32 LC1-D32 Relais Thermiques Thermal Relay Type Irth (A) Type Irth (A) LR2-D1306 1...1,6 LR2-D1307 1,6...2,5 LR2-D1308 2,5...4 LR2-D1310 4...6 LR2-D1310 4...6 LR2-D1314 7...10 LR2-D1314 7...10 LR2-D1316 9...13 LR2-D1321 12...18 DOL monophasé (Démarrage direct) Single phase - DOL (Direct On Line) Nb modules Nbr of modules Mw 3 3 3 3 3 3 3 3 3 Ancienne gamme Old range Guide Technique V9 / V9 Technical Guide 360 Anex 01 Appendix 01 6.1.2. 6.1.2.1. Déclassement des appareils - AC3 Starters derating - AC3 GV2-P Type de coordination: 1-2 Coordination type: 1-2 Blokset Mf Appareillage Puissance Power Switchgear Disjoncteur Circuit breaker GV2-P02 GV2-P03 GV2-P04 GV2-P05 GV2-P06 GV2-P07 GV2-P08 GV2-P10 GV2-P14 GV2-P16 GV2-P20 GV2-P21 GV2-P22 Calibre Rating 0,16...0,25 0,25...0,4 0,4...0,63 0,63...1 1...1,6 1,6...2,5 2,5...4 4...6,3 6...10 9...14 13...18 17...23 20...25 Contacteur Contactor LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K09 LC1-D12 LC1-D18 LC1-D25 LC1-D25 Coefficient de Déclassement (A) à T°amb (°C) Derating coefficient (A) à T°amb (°C) IP ð 42 IP 54 35 40 45 50 35 40 45 50 0,23 0,2 0,2 0,2 0,2 0,2 0,2 0,15 0,35 0,33 0,3 0,3 0,3 0,3 0,3 0,25 0,6 0,5 0,5 0,5 0,5 0,5 0,5 0,4 0,9 0,8 0,8 0,7 0,8 0,75 0,7 0,7 1,4 1,3 1,2 1,2 1,3 1,2 1,1 1 2,2 2,1 2 1,9 2 1,9 1,8 1,7 3,6 3,4 3,1 3 3,2 3 2,9 2,7 5,4 5 4,7 4,5 5 4,5 4,3 4 8 7,6 7 6,7 7,2 6,8 6,5 6 10,7 10 9,4 8,9 9,6 9 8,6 8 16 15 14 13,3 14,5 13,5 13 12 20 19 18 17 18,5 17 16,6 15,4 22 21 19,5 18,5 20 18,8 18 16,8 Blokset Mw Appareillage Puissance Power Switchgear Coefficient de Déclassement (A) à T°amb (°C) Derating coefficient (A) à T°amb (°C) IP ð 42 IP 54 35 40 45 50 35 40 45 50 0,23 0,2 0,2 0,2 0,2 0,2 0,2 0,2 0,35 0,34 0,3 0,3 0,3 0,3 0,3 0,3 0,6 0,5 0,5 0,5 0,5 0,5 0,5 0,4 Disjoncteur Circuit breaker GV2-P02 GV2-P03 GV2-P04 GV2-P05 GV2-P06 GV2-P07 Calibre Rating 0,16...0,25 0,25...0,4 0,4...0,63 0,63...1 1...1,6 1,6...2,5 Contacteur Contactor LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 GV2-P08 2,5...4 LC1-K06 GV2-P10 4...6,3 LC1-K06 5,4 5 4,7 4,5 5 4,5 4,3 4 GV2-P14 6...10 LC1-K09 8 7,5 7 6,7 7,2 6,8 6,5 6 GV2-P16 9...14 LC1-D12 10,7 10 9,4 8,9 9,6 9 8,6 8 GV2-P20 13...18 LC1-D18 16 15 14 13,3 14,5 13,5 13 12 GV2-P21 17...23 LC1-D25 20 19 18 17 18,5 17 15,6 15,4 GV2-P22 20...25 LC1-D25 22 21 20 19 20 19 18 17 0,9 0,8 0,8 0,7 0,8 0,8 0,7 0,7 1,4 1,3 1,2 1,2 1,3 1,2 1,1 1 2,2 2,1 2 1,9 2 1,9 1,8 1,7 3,6 3,4 3,1 3 3,2 3 2,9 2,7 Coefficient à appliquer IP ≤ 42 IP 54 Guide Technique V9 / V9 Technical Guide 35° 0.89 0.80 Coefficient to be applied 40° 0.84 0.75 45° 0.78 0.72 50° 0.74 0.67 361 Anex 01 Appendix 01 6.1.2.2. Compact NS et GV7 Compact NS and GV7 Type de coordination: 1-2 Coordination type: 1-2 Blokset Mf Appareillage Puissance Power Switchgear Disjoncteur Circuit breaker NS80H-MA NS100l-MA* NS160l-MA* NS250l-MA* NS400l-MA* NS630l-MA* Calibre Rating 2,5 6,3 13 13 25 25 50 50 50 80 80 2,5 6,3 13 13 25 25 50 50 50 50 100 100 100 100 150 Disjoncteur moteur Motor circuit-breaker GV7-Rn GV7-Rn GV7-Rn GV7-Rn GV7-Rn GV7-Rn GV7-Rn GV7-Rn GV7-Rn GV7-Rn GV7-Rn GV7-Rn GV7-Rn GV7-Rn GV7-Rn GV7-Rn Contacteur Contactor LC1-D09 LC1-D09 LC1-D09 LC1-D12 LC1-D18 LC1-D25 LC1-D32 LC1-D40 LC1-D50 LC1-D65 LC1-D80 LC1-D09 LC1-D09 LC1-D09 LC1-D12 LC1-D18 LC1-D25 LC1-D32 LC1-D40 LC1-D50 LC1-D65 LC1-D65 LC1-D80 LC1-D95 LC1-F115 LC1-F150 220 GV7-Rn 220 GV7-Rn Coefficient de Déclassement (A) à T°amb (°C) Derating coefficient (A) à T°amb (°C) IP ð 42 IP 54 35 40 45 50 35 40 45 50 8 7.7 7.3 7 6.3 5.9 5.5 5.4 8 7.7 7.3 7 6.3 5.9 5.5 5.4 8 7.7 7.3 7 6.3 5.9 5.5 5.4 10.7 10.2 9.7 9.2 8.3 7.8 7.5 7 16 15.3 14.6 13.9 12.5 11.7 11.2 10.8 22.3 21.2 20.2 19.2 17.3 16.3 15.5 15 28.5 27.2 26 24.6 22 20.8 19.9 19.2 35.6 34 32.4 30.8 28 26 25 24 44.5 42.5 40.5 38.5 35 33 32 30 58 55 53 50 45 42 40 39 71 68 65 62 55 52 50 48 8 7.7 7.3 7 6.3 5.9 5.5 5.4 8 7.7 7.3 7 6.3 5.9 5.5 5.4 8 7.7 7.3 7 6.3 5.9 5.5 5.4 7 10.7 10.2 9.7 9.2 8.3 7.8 7.5 16 15.3 14.6 13.9 12.5 11.7 11.2 10.8 22.3 21.2 20.2 19.2 17.3 16.3 15.5 15 28.5 27.2 26 24.6 22 20.8 19.9 19.2 35.6 34 32.4 30.8 28 26 25 24 44.5 42.5 40.5 38.5 35 33 32 30 58 55 53 50 45 42 40 39 58 55 53 50 45 42 40 39 71 68 65 62 55 52 50 48 84.5 81 77 73 65 62 60 57 102 98 93 89 78 75 73 69 134 128 122 116 102 98 95 90 LC1-F185 165 157 150 142 126 120 117 111 LC1-F225 203 190 185 175 154 147 141 135 320 GV7-Rn LC1-F265 236 225 215 204 180 172 167 159 320 - LC1-F330 294 280 267 254 225 215 208 198 500 - LC1-F400 356 340 324 308 272 260 252 240 500 - LC1-F500 445 425 405 385 340 325 315 300 500 - LC1-F630 560 535 510 485 428 409 397 381 *: NS ***z-MA représente: - NS*** N/H/L-MA pour NS100-250 - NS*** H/L-MA pour NS400-630 : représente E40...220 ou S40...220 Guide Technique V9 / V9 Technical Guide *: NS ***z-MA represent: - NS*** N/H/L-MA by NS100-250 - NS*** H/L-MA by NS400-630 : represent E40...220 or S40...220 362 Anex 01 Appendix 01 Blokset Mw IP 20 Appareillage Puissance Power Switchgear Disjoncteur Calibre Circuit breaker Rating NS80H-MA 2,5 6,3 13 13 25 Disjoncteur moteur Motor circuit-breaker GV7-R Contacteur Contactor LC1-D09 LC1-D09 LC1-D09 LC1-D12 LC1-D18 25 - 50 GV7-R 50 Coefficient de Déclassement (A) à T°amb (°C) Derating coefficient (A) à T°amb (°C) 35 40 45 50 8,1 7,9 7,6 8,1 7,9 7,6 7,2 7,2 8,1 7,9 7,6 7,2 10 10,5 1O 9,6 17 16 15 15 LC1-D25 22,5 22 21 20 LC1-D32 30 28 27 26 GV7-R LC1-D40 38 35 33 32 50 GV7-R LC1-D50 45 44 42 40 80 GV7-R LC1-D65 61 58 55 52 80 GV7-R LC1-D80 64 61 59 56 2,5 - LC1-D09 8,1 7,9 7,6 7,2 6,3 - LC1-D09 8,1 7,9 7,6 7,2 13 - LC1-D09 8,1 7,9 7,6 7,2 13 - LC1-D12 10 10,5 1O 9,6 25 GV7-R LC1-D18 17 16 15 15 25 - LC1-D25 22,5 22 21 20 50 GV7-R LC1-D32 30 28 27 26 50 GV7-R LC1-D40 38 35 33 32 50 GV7-R LC1-D50 45 44 42 40 50 GV7-R LC1-D65 61 58 55 52 100 GV7-R LC1-D65 61 58 55 52 100 GV7-R LC1-D80 64 61 59 56 100 GV7-R LC1-D95 76 72 70 67 NS160z-MA* 100 GV7-R LC1-F115 92 88 84 81 150 GV7-R LC1-F150 120 115 110 105 NS250z-MA* 220 GV7-R LC1-F185 148 142 136 130 220 GV7-R LC1-F225 175 168 161 155 NS400z-MA* 320 GV7-R LC1-F265 249 235 222 211 320 - LC1-F330 255 245 234 225 NS630z-MA* 500 - LC1-F400 320 306 293 282 500 - LC1-F500 400 382 366 352 500 - LC1-F630 500 480 460 440 NS100z-MA* *: NS ***z-MA représente: - NS*** N/H/L-MA pour NS100-250 - NS*** H/L-MA pour NS400-630 : représente E40...220 ou S40...220 Guide Technique V9 / V9 Technical Guide *: NS ***z-MA represent: - NS*** N/H/L-MA by NS100-250 - NS*** H/L-MA by NS400-630 : represent E40...220 or S40...220 363 Anex 01 Appendix 01 Blokset Mw IP 31/42 Appareillage Puissance Power Switchgear Disjoncteur Calibre Circuit breaker Rating NS80H-MA 2,5 6,3 13 13 25 GV7-R Contacteur Contactor LC1-D09 LC1-D09 LC1-D09 LC1-D12 LC1-D18 25 - LC1-D25 22 21 20 18,5 50 GV7-R LC1-D32 28 27 25 24 50 GV7-R LC1-D40 34 32 31 29 50 GV7-R LC1-D50 35 33 31 30 80 GV7-R LC1-D65 57 54 51 48 80 GV7-R LC1-D80 64 61 59 56 2,5 - LC1-D09 8 7,6 7 6,6 6,3 - LC1-D09 8 7,6 7 6,6 13 - LC1-D09 8 7,6 7 6,6 13 - LC1-D12 10,5 10 9,4 8,8 25 GV7-R LC1-D18 17 16 15 14 25 - LC1-D25 22 21 20 18,5 50 GV7-R LC1-D32 28 27 25 24 50 GV7-R LC1-D40 34 32 31 29 50 GV7-R LC1-D50 35 33 31 30 50 GV7-R LC1-D65 57 54 51 48 100 GV7-R LC1-D65 57 54 51 48 100 GV7-R LC1-D80 64 61 59 56 100 GV7-R LC1-D95 76 72 70 67 NS160z-MA* 100 GV7-R LC1-F115 92 87 85 80 150 GV7-R LC1-F150 112 110 102 98 NS250z-MA* 220 GV7-R LC1-F185 137 135 126 120 220 GV7-R LC1-F225 164 161 150 144 NS400z-MA* 320 GV7-R LC1-F265 231 218 207 197 320 - LC1-F330 238 234 218 210 NS630z-MA* 500 - LC1-F400 296 292 272 260 500 - LC1-F500 372 366 341 328 500 - LC1-F630 468 460 430 413 NS100z-MA* Disjoncteur moteur Motor circuit-breaker - Coefficient de Déclassement (A) à T°amb (°C) Derating coefficient (A) à T°amb (°C) 35 40 45 50 *: 8 7,6 7 8 7,6 7 6,6 8 7,6 7 6,6 10,5 10 9,4 8,8 17 16 15 14 NS ***z-MA représente: - NS*** N/H/L-MA pour NS100-250 - NS*** H/L-MA pour NS400-630 : représente E40...220 ou S40...220 Guide Technique V9 / V9 Technical Guide 6,6 *: NS ***z-MA represent: - NS*** N/H/L-MA by NS100-250 - NS*** H/L-MA by NS400-630 : represent E40...220 or S40...220 364 Anex 01 Appendix 01 Blokset Mw IP 54 Appareillage Puissance Power Switchgear Disjoncteur Calibre Circuit breaker Rating NS80H-MA 2,5 6,3 13 13 25 NS100z-MA* Disjoncteur moteur Motor circuit-breaker - Coefficient de Déclassement (A) à T°amb (°C) Derating coefficient (A) à T°amb (°C) 35 40 45 50 GV7-R Contacteur Contactor LC1-D09 LC1-D09 LC1-D09 LC1-D12 LC1-D18 25 - LC1-D25 20 18,7 18 17,2 50 GV7-R LC1-D32 26 24 23 22 50 GV7-R LC1-D40 32 30 29 27,5 50 GV7-R LC1-D50 40 37,5 36 34,5 80 GV7-R LC1-D65 52 49,5 47 44,5 80 GV7-R LC1-D80 55 52 50 48 2,5 - LC1-D09 7,2 6,8 6,5 6,2 6,3 - LC1-D09 7,2 6,8 6,5 6,2 13 - LC1-D09 7,2 6,8 6,5 6,2 13 - LC1-D12 9,6 9 8,6 7,2 25 GV7-R LC1-D18 14,5 13,6 13 12,3 25 - LC1-D25 20 18,7 18 17,2 50 GV7-R LC1-D32 26 24 23 22 50 GV7-R LC1-D40 32 30 29 27,5 50 GV7-R LC1-D50 40 37,5 36 34,5 50 GV7-R LC1-D65 52 49,5 47 44,5 100 GV7-R LC1-D65 52 49,5 47 44,5 100 GV7-R LC1-D80 55 52 50 48 7,2 6,8 6,5 7,2 6,8 6,5 6,2 6,2 7,2 6,8 6,5 6,2 9,6 9 8,6 7,2 14,5 13,6 13 12,3 100 GV7-R LC1-D95 66 62 60 57 NS160z-MA* 100 GV7-R LC1-F115 79 75 72 69 150 GV7-R LC1-F150 103 98 94 90,5 NS250z-MA* 220 GV7-R LC1-F185 127 120 115 111 220 GV7-R LC1-F225 151 144 138 133 NS400z-MA* 320 GV7-R LC1-F265 213 201 191 182 320 - LC1-F330 221 211 201 198 NS630z-MA* 500 - LC1-F400 276 260 250 240 500 - LC1-F500 343 328 314 302 500 - LC1-F630 432 413 395 380 *: NS ***z-MA représente: - NS*** N/H/L-MA pour NS100-250 - NS*** H/L-MA pour NS400-630 : représente E40...220 ou S40...220 Guide Technique V9 / V9 Technical Guide *: NS ***z-MA represent: - NS*** N/H/L-MA by NS100-250 - NS*** H/L-MA by NS400-630 : represent E40...220 or S40...220 365 Anex 01 Appendix 01 6.1.2.3. Integral Contacteurs - Disjoncteurs Integral - - - - - - -Coordination totale Integral Contactors - Circuit breakers - - - - - -Total coordination Coefficient à appliquer IP ≤ 42 IP 54 Guide Technique V9 / V9 Technical Guide 35° 0.89 0.80 Coefficient to be applied 40° 45° 50° 0.84 0.78 0.74 0.75 0.72 0.67 366 Anex 01 Appendix 01 Guide Technique V9 / V9 Technical Guide 367 Installation de l’appareillage Switchgear Installation Guide Technique V9 / V9 Technical Guide 368 Installation de l’appareillage Switchgear Installation Guide Technique V9 / V9 Technical Guide 369 Installation de l’appareillage Switchgear Installation Guide Technique V9 / V9 Technical Guide 370 Installation de l’appareillage Switchgear Installation Guide Technique V9 / V9 Technical Guide 371 Schneider Electric Brasil Adresse postale Av. da Saudade, s/no 13171-320 Sumaré - SP Brazil Tél.: 55 (0)19 38 73 97 25 Fax.: 55 (0)19 38 73 97 37 http://www.schneiderelectric.com 51 127 040 X0-rev J. En raison de l'évolution des normes et du matériel, les caractéristiques indiquées par le texte et les images de ce document ne nous engagent qu'après confirmation par nos services. As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. Ce document a été imprimé sur du papier écologique. This document has been printed on ecological paper. Publishing: Schneider Electric SA Design : GIB / BIM Printed by : * Obtenez plus du spécialiste de la distribution mondial électrique et des automatismes industriels 07/2003