Blokset
Tableau BT
Low voltage equipment
V9
Guide technique V9
V9 Technical guide
Get more with the world’s Power & Control specialist*
Sommaire du chapitre
Chapter contents
1. Informations générales .................................................... 5
General information
2. Jeux de barres ................................................................ 25
Busbars
3. Installation de l’appareillage ......................................... 43
Switchgear Installation
4. Auxiliaires et borniers .................................................. 247
Auxiliaries and terminal blocks
5. Divers ............................................................................ 252
Miscellaneous
6. Annex 01 ....................................................................... 270
Appendix 01
Guide Technique V9 / V9 Technical Guide
2
Sommaire du chapitre
Chapter contents
1. Informations générales
General information
1.1. Règles de base .................................................................................... 5
Basic rules
1.1.1.
La Signature BLOKSET .............................................................................. 5
BLOKSET Signature
1.1.2.
Modularité .................................................................................................... 6
Modularity:
1.1.3.
Dimensions d'ossature ............................................................................... 7
Framework dimensions
1.1.4.
Colonne d’angle .......................................................................................... 8
Angle column
1.1.5.
Colonne pour Connexion Dos à Dos ........................................................ 9
Column for Back to Back Connection
1.2. Définition des compartiments .......................................................... 10
Compartment definition
1.2.1.
Type D/Mf et Ms ......................................................................................... 10
D, Mf and Ms type
1.2.2.
Type Mw ..................................................................................................... 10
Mw type
1.3. Définitions des formes ...................................................................... 11
Form definition
1.3.1.
Type D, Mf et Ms ........................................................................................ 11
D, Mf and Ms type
1.3.2.
Type Mw ..................................................................................................... 12
Mw type
1.3.3.
Principe des IP en fonction des formes sur portes ............................... 13
IP's rules according to shapes on doors
1.4. Dimensions des colonnes ................................................................ 14
Column dimensions
1.5. Poids des colonnes ........................................................................... 15
Column weight
Guide Technique V9 / V9 Technical Guide
3
Sommaire du chapitre
Chapter contents
1.6. Fixation au sol ................................................................................... 18
Fixing to ground
1.6.1.
Profondeur de colonne: 400 mm ............................................................. 18
Column depth: 400 mm
1.6.2.
Profondeur de colonne: 600 mm ............................................................. 19
Column depth: 600 mm
1.7. Passage de câble ............................................................................... 20
cable lead-through
1.7.1.
1.7.2.
Type D, Mf et Ms ........................................................................................ 20
D, Mf and Ms type
1.7.1.1.
Profondeur de colonne: 400 mm ...................................................................... 20
Column depth: 400 mm
1.7.1.2.
Profondeur de colonne: 600 mm ...................................................................... 21
Column depth: 600 mm
MCC Type Mw ............................................................................................ 22
MCC Mw type
1.7.2.1.
Profondeur de colonne: 600 mm ...................................................................... 22
Column depth: 600 mm
1.8. Levages colonnes ............................................................................. 23
Hoisting columns
Guide Technique V9 / V9 Technical Guide
4
Informations générales
General information
1. Informations générales
General information
1.1. Règles de base
Basic rules
1.1.1.
La Signature BLOKSET
BLOKSET Signature
2
1
3
4
1
1
Les quatre caractéristiques ci-dessous sont
considérées comme signature BLOKSET.
Four characteristics listed below, are
considered as BLOKSET signature.
1 - La couleur standard des BANDEAUX est
RAL 7016: elle ne doit pas être modifiée.
1 - The standard color of the VENTILATION
CROSS MEMBER is RAL 7016: it must not
be modified.
2 - Les LOGOS doivent être alignés avec les
poignées des portes des unités
fonctionnelles.
3 - La couleur standard de l´HABILLAGE est
RAL 9002. Cette couleur peut être adaptée à
la demand du client.
4 - Lútilisation des serrures de porte
décrites dans le dossier de transfert est
obligatoire pour 2 raison:
– résistent aux essais de tenue à l’arc
interne (solution TTA).
– sont de la même couleur que les LOGOS,
BANDEAUX et POIGNEES.
Guide Technique V9 / V9 Technical Guide
2- The LOGOS have to be aligned with the
functional units doors handles.
3- The standard color of COVER METAL
PARTS is RAL 9002. This colour can be
changed under customer request.
4 - The use the door locks described in
transfer file is compulsory for 2 reasons:
– withstand the internal arc test (TTA solution)
– Their colour is the same as LOGOS,
VENTILATION CROSS MEMBER and
HANDLES.
5
Informations générales
General information
1.1.2.
Modularité
Modularity:
Les tableaux Blokset sont conçus sur le
principe du module de 50 mm. Les perçage
des points de fixation sont au pas de 25 mm.
La zone tramée comporte 40 modules de
50 mm. C'est la zone dans laquelle sont
installés l'appareillage et les jeux de barres
„ Avec un jeu de barres horizontal simple
(I ≤ 4000 A):
‰ 4 modules pour le jeu de barres,
‰ 36 modules pour l'appareillage.
‰ 7 modules pour le jeu de barres
(Mw - 3 PH+N en jeu de bar verticale);
‰ 33 modules pour l’appareillage
(Mw - 3 PH+N en jeu de bar verticale).
„ Avec un double jeu de barres horizontal
(I = 5000 / 6300 A):
‰ 8 modules pour le jeu de barres,
‰ 32 modules pour l'appareillage.
‰ 10 modules pour le jeu de barres
(seulement Mw);
‰ 30 modules pour l'appareillage
(seulement Mw).
Note:
les jeux de barres verticaux seront
montés dans les ossatures d'exten-
Blokset switchboards are designed on the 50
mm module principle. All fixing holes are
drilled at 25 mm distances.
The shaded zone consists of 40 50 mm
modules. This is the zone where the
switchgear and busbars are installed:
„ With a single horizontal busbar
(I ≤ 4000 A):
‰ 4 modules for the busbar,
‰ 36 modules for the switchgear.
‰ 7 modules for the busbar
(Mw - 3 PH+N in vertical Busbar);
‰ 33 modules for the switchgear
(Mw - 3 PH+N in vertical Busbar).
„ With a double horizontal busbar
(I = 5000 / 6300 A):
‰ 8 modules for the busbar,
‰ 32 modules for the switchgear.
‰ 10 modules for the busbar (only for Mw),
‰ 30 modules for the switchgear
(only for Mw).
Note:
vertical busbars are to be mounted in
the 200 mm extension frameworks.
sion de 200 mm.
Guide Technique V9 / V9 Technical Guide
6
Informations générales
General information
1.1.3.
Dimensions d'ossature
Framework dimensions
Les ossatures Blokset sont disponibles en 3
largeurs:
„ 700 (profondeur 400 ou 600).
„ 900 (profondeur 600, seulement pour
Mw).
„ 1200 pour NW40b, NW50 ou NW63
(profondeur 600).
The basic Blokset frameworks are available
in 3 widths:
„ 700 (depth 400 or 600).
„ 900 (depth 600, only for Mw).
„ 1200 for NW40b, NW50 or NW63 (depth
600).
Les ossatures d'extension de 200 ou 400
(profondeur 400 ou 600) permettent d'obtenir les dimensions suivantes:
„ 900
= 700 + 200.
„ 1100
= 200 + 700 + 200.
= 700 + 400.
„ 1300
= 200 + 700 + 400.
The 200 or 400 extension frameworks (depth
400 or 600) allow for the following
dimensions:
„ 900
= 700 + 200.
„ 1100
= 200 + 700 + 200.
= 700 + 400.
„ 1300
= 200 + 700 + 400.
La profondeur des tableaux peut être
augmentée jusqu'à 1000 mm, en rajoutant
un caisson de profondeur 400 mm. Les
dimensions des caissons sont les suivantes:
„ 700 x 400 x 2200.
„ 900 x 400 x 2200 (seulement pour Mw).
„ 900 (700+200) x 400 x 2200.
„ 1100 (200+700+200) x 400 x 2200.
„ 1100 (700+400) x 400 x 2200.
„ 1200 x 400 x 2200.
„ 1300 (200+700+400) x 400 x 2200.
The depth of the switchgear assembly can
be increased up to 1000 mm, by adding a
400 mm deep extension onto a 600 mm deep
basic framework. The dimensions of the
extensions are as follows:
„ 700 x 400 x 2200.
„ 900 x 400 x 2200 (only for Mw).
„ 900(700+200) x 400 x 2200.
„ 1100(200+700+200) x 400 x 2200.
„ 1100(700+400) x 400 x 2200.
„ 1200 x 400 x 2200.
„ 1300(200+700+400) x 400 x 2200.
Tous les Compact sont installés dans
l'ossature de largeur 700 mm (extension de
200 mm pour jeu de barres vertical).
All Compacts are installed in the 700 mm
wide framework (200 mm extension for
vertical busbars).
Les Masterpact NW08 à NW40 (3 et 4 pôles)
installés seuls dans une colonne, sont
montés dans l'ossature de largeur 700 mm
car ils sont raccordés directement au jeu de
barres horizontal.
Masterpacts NW08 to NW40 (3 and 4 poles)
installed alone in a column are mounted in
the 700 mm wide framework, since they are
directly connected to the horizontal busbars.
Les ossatures de 1200 mm sont réservées à
l'installation des Masterpact NW40b/NW50/
NW63 3/4 pôles.
The 1200 mm frameworks are only for the
Masterpact NW40b/NW50/NW63 3/4 poles
installations.
Collecteurs de terre:
„ ICC * 30/50 kA -->1b 50 x 5.
„ ICC * 85/100 kA -->2b 50 x 5.
Main earth leads:
„ ICC * 30/50 kA —>1b 50 x 5.
„ ICC * 85/100 kA —>2b 50 x 5.
Guide Technique V9 / V9 Technical Guide
7
Informations générales
General information
1.1.4.
Colonne d’angle
Angle column
An angle column has been developed and
applied for following configurations:
• connection between 600 mm depth
switchboard
• single horizontal busbar (up to 4000A) or
double horizontal busbar (up to 6300 A),
top or botton position.
• 85 kA
• IP 20, 31, 42 and 54.
Une colonne d’angle a eté développée pour
les configurations suivantes:
• connexions entre tableaux de 600 mm.
de profondeur
• jeu de barres horizontal simple (jusqu’à
4000A) ou double (jusqu’à 6300A), position supérieur ou inférieur
• 85 kA de tenue electrodynamique
• IP 20, 31 ,42 et 54.
600
800
600
800
Informations concernant l’assemblage voir
Chapitre 2.1 du Guide des plans
d’assemblage, ref. “7041xxx.pdf”
Information concerning assembly see Chapter 2.1 of Assembly Drawings Guide, ref.
“7041xxx.pdf”.
122.5
455
12.2
25
25
Guide Technique V9 / V9 Technical Guide
455
122.5
8
Informations générales
General information
1.1.5.
Colonne pour Connexion Dos à Dos
Column for Back to Back Connection
Les solutions dos à dos sont disponibles
pour les jeux de barres simples (jusqu’à
4000A) en haut ou en bas de colonne.
Degrés de protection disponibles: IP 20 et
31.
Option avec Jeu de Barres
Vertical standard
Option with standard
Vertical Busbar
Back to back solutions are available for
single busbar (up to 4000A) positioned on
top or bottom as below figures.
Available protection degrees: IP 20 and 31.
Option sans Jeu de Barres
Vertical
Option without
Vertical Busbar
Option avec Jeu de Barres
Vertical arriere
Option with rear
Vertical Busbar
100 mm
10 modules
A
2000 mm
10 modules
10 modules
B
C
100 mm
200 mm
700 mm
200 mm 400 mm
700 mm
200 mm
700 mm
200 mm
Compartiment pour connexion des jeu de barres horizontal
Compartment for horizontal busbars connection
Pour informations complémentaires voir
Guide
des
Plans
d’assemblage
“7041xxx.pdf”, Chapitre 2.1.
For additional detail see Assembly Drawings
Guide “7041xxx.pdf”, Chapter 2.1.
600
600
Fixation au sol (points de fixations disponibles) / Fixing to ground (available fixing points)
12.2
25
125 197.5 455
Guide Technique V9 / V9 Technical Guide
197.5
122.5 400
455
197.5
122.5 455
197.5
9
Informations générales
General information
1.2. Définition des compartiments
Compartment definition
1.2.1.
Type D/Mf et Ms
D, Mf and Ms type
400/600 mm
200/400 mm
700 mm
200/400 mm
Compartiment Appareillage / Switchgear compartment.
Compartiment jeu de barres (largeur 200 mm) ou raccordement càbles (200/400 mm) /
Busbar compartment (width 200 mm) or cable connection (200/400 mm).
Compartiment raccordement si accés arriére /
Connection compartment if there is rear access.
Appareil / Circuit breaker.
1.2.2.
Type Mw
Mw type
600 mm
250/450 mm
700/900 mm
Compartiment Appareillage / Switchgear compartment.
Compartiment jeu de barres / Busbar compartment.
Compartiment raccordement client avant ou arriŁre /
Front or rear load side connection compartment.
Guide Technique V9 / V9 Technical Guide
10
Informations générales
General information
1.3. Définitions des formes
Form definition
1.3.1.
Type D, Mf et Ms
D, Mf and Ms type
Forme 1 / Form 1
Forme 2b / Form 2b
Forme 3b / Form 3b
Forme 4b / Form 4b
Forme
Form
Définition de la norme IEC 60439-1
IEC standard 60439-1 definition
Adaptations spécifiques recommandées
Specific recommended adjustments
1
Aucune séparation.
No separation
Protection des parties amont restant sous tension des
appareils d'arrivée.
Protection of live line side parts of incoming circuit breakers.
2b
Séparation des jeux de barres des unités fonctionnelles.
Bornes pour conducteurs extérieurs séparées des jeux de
barres.
Separation of busbars from functional units.
External conductor terminals separate from busbars.
Connexions entre les jeux de barres et les appareils de
protection de l'unité fonctionnelle protégée contre les
contacts directs.
Connections between busbars and functional unit protection
devices protected against direct contacts.
3b
Les unités fonctionnelles sont séparées entre elles, séparées
des jeux de barres et des bornes.
Les bornes sont séparées des jeux de barres mais ne sont
pas séparées entre elles.
Functional units are separated from each others, separated
from the busbars and from terminals.
Terminals are separated from busbars but not from each
others
4b
Séparation des jeux de barres des unités fonctionnelles et
séparation de toutes les unités fonctionnelles entre elles, y
compris les bornes pour conducteurs extérieurs qui font
partie intégrante des unités fonctionnelles.
Bornes pour conducteurs extérieurs non dans le même
compartiment que l'unité fonctionnelle à laquelle elles sont
associées, mais dans les volumes protégés ou des
compartiments individuels séparés et fermés.
Separation of busbars from functional units and separation of
all functional units, including the external conductor terminals
which form an integral part of the functional units.
External conductor terminals not in the same compartment
as the functional unit to which they are connected, but in
protected volumes or separate, closed, individual
compartments.
Guide Technique V9 / V9 Technical Guide
11
Informations générales
General information
1.3.2.
Type Mw
Mw type
Tirois débrochable /
Drawers
Forme 3b /Form 3b
Forme 4b / Form 4b
Forme
Form
Définition de la norme IEC 60439-1
IEC Standard 60439-1 definition
3b
Les unités fonctionnelles sont séparées entre elles, séparées des jeux de barres et des bornes.
Les bornes sont séparées des jeux de barres mais ne sont pas séparées entre elles.
Functional units are separated from each others, separated from the busbars and from terminals.
Terminals are separated from busbars but not from each others
4b
Séparation des jeux de barres des unités fonctionnelles et séparation de toutes les unités
fonctionnelles entre elles, y compris les bornes pour conducteurs extérieurs qui font partie
intégrante des unités fonctionnelles.
Bornes pour conducteurs extérieurs non dans le même compartiment que l’unité fonctionnelle à
laquelle elles sont associées, mais dans les volumes protégés ou des compartiments individuels
séparés et fermés.
Separation of busbars from functional units and separation of all functional units, including the
external conductor terminals which form an integral part of the functional units.
External conductor terminals must not be in the same compartment as the functional unit to which
they are connected, but in protected volumes or separate, closed, individual compartments.
Guide Technique V9 / V9 Technical Guide
12
Informations générales
General information
1.3.3.
Principe des IP en fonction des formes sur portes
IP's rules according to shapes on doors
IP 31 Formes 1/2b
IP 31 Form 1/2b
IP 20 Formes 1/2b
IP 20 Form 1/2b
partie métallique
metallic part
51127496
portes
doors
IP 20, IP 31 Formes 3b/4b
IP 20, IP 31 Form 3b/4b
séparateur
separator
IP42, IP54,
Formes 1/2b
Form 1/2b
partie métallique
metallic part
51127496 + joint / + gasket
IP42, IP54,
Formes 3b/4b
Form 3b/4b
séparateur + joint
separator + gasket
Guide Technique V9 / V9 Technical Guide
13
Informations générales
General information
1.4. Dimensions des colonnes
Column dimensions
Vue de face / Front view.
Vue de c ôté / Side view.
2200 mm
X
Y
Z
600 mm
Largeur (mm)
Width (mm)
X (mm)
Y (mm)
Z (mm)
700
-
700
-
900
200
700
-
-
700
200
-
900 (1)
-
200
700
200
400
700
-
-
700
400
1200
-
1200
-
1300
200
700
400
400
700
200
1100
(1) seulement pour Mw
Guide Technique V9 / V9 Technical Guide
400 mm
(1) only for Mw
14
Informations générales
General information
1.5. Poids des colonnes
Column weight
Le poids des colonnes définies ci-dessous
s’entend sans l'appareillage.
Pour le poids des appareils, voir le
Catalogue Distribution Basse Tension.
The weight of the columns defined below
does not include the switchgear.
For the weight of the switchgear, see the Low
Voltage Distribution Catalogue.
Le poids a été défini pour une colonne
contenant:
„ Ossature.
„ Gainage Jeu de barres (forme 2).
„ Tôle inter colonne.
„ Porte arrière.
„ Portes appareillages (1 de 12 modules +
1 de 28 modules).
„ 40 modules réserve.
„ Bandeaux d’habillage.
The weight has been defined for a column
containing:
„ Framework.
„ Busbar partition (form 2).
„ Inter-column plate.
„ Rear door.
„ Switchgear doors (1 with 12 modules + 1
with 28 modules).
„ 40 reserve modules.
„ Covering strips.
Pour les Tableaux suivants:
„ L = Longueur.
„ P = Profondeur.
„ H = Hauteur.
„ E = Epaisseur.
For the following switchgear assemblies:
„ L = Length.
„ P = Depth.
„ H = Height.
„ E = Thickness.
Poids des colonnes
Column weight
Dimensions (LxPxH) (mm)
Dimensions (LxPxH) (mm)
Poids (kg)
weight (kg)
700 x 400 x 2200
700 x 600 x 2200
900 x 400 x 2200
900 x 600 x 2200
1200 x 600 x 2200
Guide Technique V9 / V9 Technical Guide
15
Informations générales
General information
Poids des extensions
Extension weight
Dimensions (LxPxH) (mm)
Dimensions (LxPxH) (mm)
Poids (kg)
weight (kg)
200 x 400 x 2200
400 x 400 x 2200
200 x 600 x 2200
400 x 600 x 2200
Poids des caissons arrières
Rear box weight
Dimensions (LxPxH) (mm)
Dimensions (LxPxH) (mm)
Poids (kg)
weight (kg)
700 x 400 x 2200
900 x 400 x 2200
1200 x 400 x 2200
Panneaux latéraux
Lateral panels
Dimensions (LxPxH) (mm)
Dimensions (LxPxH) (mm)
Poids (kg)
weight (kg)
200 x 2200
400 x 2200
600 x 2200
Toits
Covers
Dimensions (LxPxH) (mm)
Dimensions (LxPxH) (mm)
Poids (kg)
weight (kg)
200 x 400
200 x 600
400 x 400
400 x 600
700 x 400
700 x 600
900 x 400
900 x 600
1200 x 400
1200 x 600
Adaptation Masterpact
Masterpact Fixture
Forme
Form
Poids (kg)
weight (Kg)
2 (NW08 au NW40 3/4P)
2 (NW08 to NW40 3/4P)
4 (NW08 au NW40 3/4P)
4 (NW08 to NW40 3/4P)
2 ou 4 (NW40b/NW50/NW63 3/4P)
2 or 4 (NW40b/NW50/NW63 3/4P)
Guide Technique V9 / V9 Technical Guide
16
Informations générales
General information
Adaptation Compact
Compact Fixture
Nb. Modules
Nbr. Modules
Forme
Form
3
2
4
2
6
2
12
2
3
4
4
4
6
4
12
4
Poids (kg)
weight (Kg)
Poids des jeux de barres
Busbar weight
Section de barre (HxE) (mm)
Bar cross-section (LxT) (mm)
Poids/mètre (kg/m)
Weight/meter (kg/m)
63 x 5
2,803
80 x 5
3,650
100 x 5
4,450
125 x 5
5,563
Linergy
Guide Technique V9 / V9 Technical Guide
17
Informations générales
General information
1.6. Fixation au sol
Fixing to ground
1.6.1.
25
122.5
Profondeur de colonne: 400 mm
Column depth: 400 mm
455
12.2
350
322.5
25
455
350
125
25
122.5
655
25
350
122.5
400
455
350
322.5
25
455
322.5
25
455
400
350
350
125
Guide Technique V9 / V9 Technical Guide
125
18
Informations générales
General information
1.6.2.
25
122.5
Profondeur de colonne: 600 mm
Column depth: 600 mm
25
455
455
322.5
12.2
550
25
550
122.5
25
655
550
25
322.5
455
400
550
322.5
455
550
25
322.5
455
400
550
Planéité: Il est recommandé d'avoir un sol
de bonne planéité
(≤ 2 mm/m).
1000
Guide Technique V9 / V9 Technical Guide
Surface eveness: it is recommended to
have ground with a good surface eveness (≤
2mm/m).
2
19
Informations générales
General information
1.7. Passage de câble
cable lead-through
1.7.1.
Type D, Mf et Ms
D, Mf and Ms type
La zone grisée indique le passage des
câbles arrivant par le haut ou par le bas.
Utiliser les pièces standards pour une
arrivée par le bas.
Utiliser les pièces spécifiques pour une
arrivée par le haut.
Pour information supplémentaire, voir Guide
des plans d’assemblage, ref. “7041xxx.pdf”,
chapitre 6.5.
1.7.1.1.
50
The indicated area is suitable for cables
coming from top or bottom.
When cables coming from bottom use
standard metal parts.
When cables coming from top use specific
plates.
For additional information, see Assembly
drawings guide, ref. “7041xxx.pdf”, Chapter
6.5.
Profondeur de colonne: 400 mm
Column depth: 400 mm
600
350
75
75
250
250
600
50
50
150 50
75
75
250
250
350
50
75
Zone de passage
des câbles /
Cable leadthrough zone
Guide Technique V9 / V9 Technical Guide
250
20
Informations générales
General information
1.7.1.2.
50
Profondeur de colonne: 600 mm
Column depth: 600 mm
600
350
75
75
450
450
600
50
50
150 50
75
450
350
50
75
Zone de passage
des câbles /
Cable leadthrough zone
Guide Technique V9 / V9 Technical Guide
450
21
Informations générales
General information
1.7.2.
MCC Type Mw
MCC Mw type
La zone grisée indique le passage des
câbles arrivant par le haut ou par le bas.
Utiliser les pièces standards pour une
arrivée par le bas.
Utiliser les pièces spécifiques pour une
arrivée par le haut.
Pour détail supplémentaire, voir Guide des
plans d’assemblage, ref. “7041xxx.pdf”,
chapitre 6.5.
1.7.2.1.
The indicated area is suitable for cables
coming from top or bottom.
Cables from bottom use standard metal
parts.
Cables coming from bottom use specific
plates. For additional detail, see Assembly
drawings guide, ref. “7041xxx.pdf”, Chapter
6.5.
Profondeur de colonne: 600 mm
Column depth: 600 mm
227
50
427
50
75
75
450
450
Zone de passage des câbles /
Cable leadthrough zone
Guide Technique V9 / V9 Technical Guide
22
Informations générales
General information
1.8. Levages colonnes
Hoisting columns
Pour le levage d'une colonne, placer les
anneaux de levage dans les trous indiqués.
700/900/1200
1100
900/1100
900/1100
1300
Guide Technique V9 / V9 Technical Guide
To hoist a column, place the lifting rings in
the holes indicated.
Anneau de levage /
Lifting eye
23
Sommaire du chapitre
Chapter contents
2. Jeux de barres
Busbars
2.1. Jeu de barres horizontal ................................................................... 25
Horizontal busbar
2.1.1.
Jeu de barres horizontal position type D, Mf, Ms et Mw; ...................... 25
Position of Horizontal Busbars for type D, Mf, Ms and Mw.
2.1.2.
Intensité admissible dans le barres de cuivres d’un JdB Horizontal .. 27
Admissible current in horizontal copper bars
2.1.3.
Distance entre supportsd’un JdB Horizontal ......................................... 29
Distance between supports in Horizontal Busbar
2.1.4.
Dimensionnement du neutre ................................................................... 30
Neutral dimensioning
2.1.5.
Modularité des portes de jeu de barres horizontal simple ................... 31
Modularity of doors of single horizontal busbars
2.1.6.
Modularité des portes de jeu de barres horizontal double ................... 32
Modularity of doors of double horizontal busbars
2.2. Jeu de barres vertical ........................................................................ 33
Vertical busbar
2.2.1.
2.2.2.
Jeu de barres rectangulaire ..................................................................... 33
Flat Busbars
2.2.1.1.
Jeu de barres vertical, position type D, Mf et Ms ............................................ 33
Position of vertical busbars for type D, Mf and Ms
2.2.1.2.
Jeu de barres vertical, position type Mw ......................................................... 34
Position of vertical busbars for type Mw
2.2.1.3.
Facteur de diversité ........................................................................................... 34
Diversity factor
2.2.1.4.
Intensité admissible dans les barres de cuivre d’un JdB vertical. ................ 35
Admissible current in vertical copper bars
2.2.1.5.
Distance entre supports d’un JdB Vertical. ..................................................... 37
Distance between supports in vertical busbar
2.2.1.6.
Dimensionnement du neutre ............................................................................. 38
Neutral dimensioning
Jeux de barres Linergy ............................................................................. 38
Linergy busbars
2.3. Dimensionnement du PE et PEN ...................................................... 40
Dimensioning of PE and PEN
Guide Technique V9 / V9 Technical Guide
24
Jeux de barres
Busbars
2. Jeux de barres
Busbars
2.1. Jeu de barres horizontal
Horizontal busbar
2.1.1.
Jeu de barres horizontal position type D, Mf, Ms et Mw;
Position of Horizontal Busbars for type D, Mf, Ms and Mw.
300
2100
Pour le jeu de barres horizontal, deux
positions standards sont proposées:
„ En haut de l'armoire
„ En bas de l'armoire
Guide Technique V9 / V9 Technical Guide
For the horizontal busbar, two standard
positions are proposed:
„ At the top of the cubicle.
„ At the bottom of the cubicle.
25
Jeux de barres
Busbars
L'extrémité droite du jeu de barres horizontal
est positionnée à 45 mm du bord extérieur du
cadre de la cellule, l'extrémité gauche est
alignée avec le bord du cadre.
The right-hand end side of the horizontal
busbar is positioned 45 mm from the outside
edge of the column frame, with the left-hand
end side lined up with the edge of the frame.
Note 1: prévoir les trous de raccordement des éclisses
en cas d'extension future.
Note 1: provide splice bar connection holes for any
future extensions.
Note 2: Il existe, pour tous les jeux de barres
(sauf JdB vertical Type MW),
différents revêtements:
„ Nu.
„ Etamé.
„ Argenté.
„ Isolé.
„ Etamé et isolé.
„ Argenté et isolé.
„ Nickelé
Note 2: Different claddings exist for all busbars
(except the MW vertical busbar):
„ Plain.
„ Tin-plated.
„ Silver-plated.
„ Insulated.
„ Tin-plated and insulated.
„ Silver-plated and insulated.
„ Nickeled
Pour les jeux de barres verticaux du MW
nous avons:
„ Nu.
„ Argenté.
Vue de face / Front view
For the MW vertical busbars, the possible
claddings are:
„ Plain.
„ Silver-plated.
45 mm
75/125 mm
Vue de dessus / Top view
Guide Technique V9 / V9 Technical Guide
26
Jeux de barres
Busbars
2.1.2.
Intensité admissible dans le barres de cuivres d’un JdB
Horizontal
Admissible current in horizontal copper bars
En fonction de l'intensité, de la température
ambiante extérieur et de l'indice de
protection du tableau, déterminer le nombre
et la section des barres à utiliser par phase.
Calculate the number and the cross-section
of the bars to be used per phase according to
the current, the outside ambient temperature
and the degree of protection in the
switchboard.
Valeurs données pour cuivre NU, époxy
et argenté
Values data for bare copper, epoxy and
silver plated
IP ≤ 42
Section /ph
Cross-section /ph
1b x 63 x 5 *
2b x 63 x 5 *
1b x 100 x 5
1b x 125 x 5
2b x 100 x 5
2b x 125 x 5
3b x 100 x 5
3b x 125 x 5
4b x 100 x 5
4b x 125 x 5
5b x 100 x 5
5b x 125 x 5
2 x 4b x 100 x 5
2 x 5b x 100 x 5
Température ambiante extérieure (°C)
Outside ambient temperature (°C)
35
40
45
50
850
800
750
700
1500
1450
1400
1300
1200
1150
1100
1050
1500
1450
1400
1300
2150
2050
1900
1850
2550
2450
2350
2200
2750
2650
2550
2400
3250
3100
3000
2800
3300
3150
3000
2850
3800
3650
3500
3300
3600
3450
3300
3150
4100
3900
3800
3550
6000
5800
5550
5250
6600
6350
6100
5800
IP 54
Section /ph
Cross-section /ph
1b x 63 x 5 *
2b x 63 x 5 *
1b x 100 x 5
1b x 125 x 5
2b x 100 x 5
2b x 125 x 5
3b x 100 x 5
3b x 125 x 5
4b x 100 x 5
4b x 125 x 5
5b x 100 x 5
5b x 125 x 5
2 x 4b x 100 x 5
2 x 5b x 100 x 5
Guide Technique V9 / V9 Technical Guide
Température ambiante extérieure (°C)
Outside ambient temperature (°C)
35
40
45
50
750
700
650
600
1250
1200
1150
1100
1100
1050
1000
950
1350
1300
1250
1200
1900
1800
1750
1650
2300
2200
2100
2000
2500
2400
2300
2150
2850
2700
2600
2450
3000
2900
2750
2600
3500
3350
3200
3000
3300
3150
3000
2800
3800
3650
3450
3300
5200
5000
4800
4500
5800
5600
5300
5100
27
Jeux de barres
Busbars
Valeurs données pour cuivre étamé
Values data for copper tin
IP ≤ 42
Section /ph
Cross-section /ph
1b x 63 x 5 *
2b x 63 x 5 *
1b x 100 x 5
1b x 125 x 5
2b x 100 x 5
2b x 125 x 5
3b x 100 x 5
3b x 125 x 5
4b x 100 x 5
4b x 125 x 5
5b x 100 x 5
5b x 125 x 5
2 x 4b x 100 x 5
2 x 5b x 100 x 5
Température ambiante extérieure (°C)
Outside ambient temperature (°C)
35
40
45
50
800
750
700
650
1400
1350
1300
1200
1150
1100
1050
1000
1400
1350
1300
1250
2000
1900
1850
1750
2450
2350
2250
2100
2600
2500
2400
2250
3000
2900
2750
2600
3050
2900
2800
2650
3500
3350
3200
3050
3300
3150
3000
2850
3800
3650
3500
3300
5600
5400
5150
4900
6150
5900
5700
5350
IP 54
Section /ph
Cross-section /ph
1b x 63 x 5 *
2b x 63 x 5 *
1b x 100 x 5
1b x 125 x 5
2b x 100 x 5
2b x 125 x 5
3b x 100 x 5
3b x 125 x 5
4b x 100 x 5
4b x 125 x 5
5b x 100 x 5
5b x 125 x 5
2 x 4b x 100 x 5
2 x 5b x 100 x 5
*: -
Guide Technique V9 / V9 Technical Guide
Température ambiante extérieure (°C)
Outside ambient temperature (°C)
35
40
45
50
650
600
550
500
1150
1100
1050
1000
1000
950
900
850
1300
1200
1150
1100
1800
1750
1650
1600
2150
2050
2000
1850
2300
2200
2100
2000
2650
2550
2450
2300
2850
2700
2600
2500
3100
3000
2850
2700
2900
2800
2650
2500
3450
3300
3150
3000
4850
4650
4450
4250
5400
5200
5000
4700
Il n’y a pas de rapports d’essais de
type pour ces barres.
*: -
There are no type test reports for these
bars.
28
Jeux de barres
Busbars
2.1.3.
Distance entre supportsd’un JdB Horizontal
Distance between supports in Horizontal Busbar
Principe fondamentaux
Les supports de barres assurent la tenue
mécanique du circuit principal,
particulèrement au moment d’un courtcircuit. La distance maximale entre les
supports est fonction du courant assigné de
courte durée admissible, du nombre et de la
section des barres ainsi que de leurs entreaxe (75 ou 125mm).
Basic principles
The bar supports ensure the mechanical
resistance of the main circuit, and in
particular when a short-circuit occurs. The
maximum distance between the supports
depends on the rated short-time withstand
current, on the number and cross-section of
the bars, as well as their centre distances (75
or 125 mm).
La règle de la application
La distance entre les supports devra être au
maximum égale à la valeur mentionnée dans
les différents tableaux.
Application rule
The distance between supports should, at its
maximum, be equal to the value quoted in
the different tables.
Note 1: les supports de calage inférieur ne participent
pas à la tenue aux efforts électrodynamiques.
Note 1: bottom wedge supports do not contribute to
the electrodynamic force resistance.
Note 2: les valeurs des distances maximales sont
exprimées en mm. Les tableaux ont été établis
à partir des certificats de conformité n°
FR97.050 et 062-97 délivrés pour le compte
de l’ASEFA. Les tableaux sont à utiliser en
courant alternatif 50 ou 60 Hz triphasé.
Note 2: the maximum distance values are given in
mm. The tables were developed from
conformity certificates no. FR97.050 and 06297 issued for the ASEFA accounts. The tables
are to be used with 50 or 60 Hz three-phase
AC current.
Tableau pour entre-axe des barres 75 mm (profondeur 400/600)
Table for 75 mm bar centre distance (depth 400/600)
Section Jeux de barres/ph
Busbar cross-section/ph
Icc=30kA
Isc=30kA
Icc=50kA
Isc=50kA
1b x 63 x 5
237.5 *
interdit / forbidden
2b x 63 x 5
237.5 *
200
1b x 100 x 5
475
237.5
2b x 100 x 5
475
237.5
2b x 125 x 5
475
237.5
Type de supports
Type of supports
fixe
fixed
fixe + volant
fixed + movable
*: pour ces configurations utilisez supports
fixe + volant
*: for these configurations use supports fix
+ movable
Tableau pour entre-axe des barres 125 mm (profondeur 600 mm)
Table for 125 mm bar centre distance (depth 600 mm)
Section Jeux de barres/ph
Busbar cross-section/ph
Icc=50kA
Isc=50kA
Icc=85kA
Isc=85kA
1b x 100 x 5
475
interdit
forbidden
1b x 125 x 5
475
interdit
forbidden
2b x 100 x 5
475
237.5
2b x 125 x 5
475
237.5
3b x 100 x 5
475
237.5
Guide Technique V9 / V9 Technical Guide
29
Jeux de barres
Busbars
Tableau pour entre-axe des barres 125 mm (profondeur 600 mm)
Table for 125 mm bar centre distance (depth 600 mm)
Section Jeux de barres/ph
Busbar cross-section/ph
Icc=50kA
Isc=50kA
Icc=85kA
Isc=85kA
3b x 125 x 5
475
237.5
4b x 100 x 5
475
237.5
4b x 125 x 5
475
237.5
5b x 100 x 5
475
237.5
5b x 125 x 5
475
237.5
Type de supports
Type of supports
fixe
fixed
fixe + volant
fixed + movable
Tableau pour double jeu de barres (profondeur 600 mm)
Table for double busbars (depth 600 mm)
Section Jeux de barres/ph
Busbar cross-section/ph
Icc=100kA
Isc=100kA
1 x 4b x 100 x 5
237.5
1 x 4b x 100 x 5
237.5
1 x 5b x 100 x 5
237.5
1 x 5b x 105 x 5
237.5
Type de supports
Type of supports
fixe + volant
fixed + movable
2.1.4.
Dimensionnement du neutre
Neutral dimensioning
Si rien n'est précisé sur le cahier des
charges, le choix de la section du neutre est
réalisé en fonction des caractéristiques
suivantes:
„ Le neutre doit pouvoir véhiculer la même
intensité nominale que le jeu de barres
auquel il est associé.
„ Le neutre doit pouvoir tenir à une
contrainte thermique correspondant à
60% de l' Icc du jeu de barres.
Guide Technique V9 / V9 Technical Guide
If nothing is specified in the specification, the
choice of neutral cross-section is made
according to the following characteristics:
„ The neutral must be able to transmit the
same nominal current as the busbar to
which it is connected.
„ The neutral must be able to withstand a
thermal stress which corresponds to 60%
of the busbar Isc
30
Jeux de barres
Busbars
2.1.5.
Modularité des portes de jeu de barres horizontal simple
Modularity of doors of single horizontal busbars
3 différentes modularités de porte sont à
utiliser suivant les configurations des JdB:
3 different modularity of doors have to be
used depending on busbars configuration:
Solution 1: 4M, pour le type D, Mf et Ms
avec JdB horizontal et vertical 3Ph ou
3Ph+N et pour le type Mw avec JdB
horizontal 3Ph ou 3Ph+N et avec JdB
vertical 3Ph.
Solution 1: 4M, for type D, Mf and Ms with
3Ph or 3Ph+N (horizontal and vertical
busbar) or type Mw with 3Ph or 3Ph+N on
horizontal busbars and 3Ph in vertical
busbar.
Solution 2: 6M, pour le type D en 3Ph ou
3Ph+N avec JdB vertical arrière.
Solution 2: 6M, for type D with 3Ph or
3Ph+N with rear vertical busbar..
Solution 3: 7M, pour le type Mw avec JdB
horizontal et vertical 3Ph+N.
Solution 3: 7M, for type Mw with 3Ph+N on
horizontal and vertical busbar.
Modularité des portes de jeu de Barres horizontal
Horizontal busbars door modularity
SOLUTION 1
SOLUTION 1
SOLUTION 2
SOLUTION 2
SOLUTION 3
SOLUTION 3
4M
6M
FACE AVANT
FRONT VIEW
FACE AVANT
FRONT VIEW
7M
FACE LATERALE
SIDE VIEW
FACE AVANT
FRONT VIEW
FACE LATERALE
SIDE VIEW
7M
6M
4M
FACE AVANT
FRONT VIEW
Guide Technique V9 / V9 Technical Guide
FACE AVANT
FRONT VIEW
FACE LATERALE
SIDE VIEW
FACE AVANT
FRONT VIEW
FACE LATERALE
SIDE VIEW
31
Jeux de barres
Busbars
2.1.6.
Modularité des portes de jeu de barres horizontal double
Modularity of doors of double horizontal busbars
2 différentes modularité de portes sont à
utiliser suivant la configuration du JdB
horizontal en haut de colonne, et 1 seule
solution en cas de JdB horizontal en bas.
Solution 4: 8M, pour le type D, Mf et Ms
avec JdB horizontal 3Ph ou 3Ph+N.
Solution 5: 10M, pour le type Mw avec JdB
horizontal 3Ph ou 3Ph+N et JdB vertical 3Ph.
Pour les colomnes avec NW40b/50/63 voir
item 3.1.2.7..
2 different modularity of door have to be used
depending on horizontal busbar
configuration on the top and only one
solution when horizontal busbars is installed
on the botton.
Solution 4: 8M, for type D, Mf and Ms with
3Ph or 3Ph+N on horizontal busbars.
Solution 5: 10M, for type Mw with 3Ph or
3Ph+N on horizontal busbars and 3Ph on
vertical busbars.
For columns with NW40b/50/63, see item
3.1.2.7..
Modularité de porte de jeu de Barres horizontal
Horizontal busbars modularity door
SOLUTION 4
SOLUTION 4
SOLUTION 5
SOLUTION 5
8M
10M
FACE AVANT
FRONT VIEW
FACE AVANT
FRONT VIEW
8M
FACE AVANT
FRONT VIEW
Guide Technique V9 / V9 Technical Guide
32
Jeux de barres
Busbars
2.2. Jeu de barres vertical
Vertical busbar
2.2.1.
Jeu de barres rectangulaire
Flat Busbars
2.2.1.1.
Jeu de barres vertical, position type D, Mf et Ms
Position of vertical busbars for type D, Mf and Ms
a. Les supports des jeux de barres
verticaux sont fixés à l'intérieur du cadre
de l'armoire dans une ossature
d'extension.
a. The vertical busbar supports are
mounted in the interior of the column
frame in an extension framework
75/125 mm
T 3
S 2
appareillage
switchgear
R 1
N
200 mm
.
700 mm
b. Les jeux de barres verticaux peuvent
être montés dans la partie postérieur de
la colonne.
L’intensité maximale est 1600A (avec
jeux de barres standard).
Pas disponible pour Ms.
L’intensite maximale d’Icc est 50 kA.
Profondeur 400 et 600. Forme 1 et 2
pour 600. Forme 1 pour 400.
b. Vertical busbar can be assembly rear of
column.
Maximum IN= 1600 A (with standard
busbar).
It’s not available for Ms.
Maximum Icc: 50 KA.
Depth 400 and 600. Form 1 and 2 to 600.
Form 1 to 400.
75 mm
N
R/1
S/2
T/3
appareillage
switchgear
700 mm
Guide Technique V9 / V9 Technical Guide
33
Jeux de barres
Busbars
2.2.1.2.
Jeu de barres vertical, position type Mw
Position of vertical busbars for type Mw
Le Jeu de barres vertical est fixé derrière les
tiroirs.
The vertical busbar is fixed behind the
drawers.
appareillage
switchgear
450 mm
2.2.1.3.
250 mm
Facteur de diversité
Diversity factor
Jeux de barres verticaux: les sections de
barres pour les jeux de barres verticaux sont
déterminées en fonction de l' In à distribuer.
Pour trouver l' In max. d'un jeu de barres
vertical, appliquer le règle générale suivante:
Vertical busbars: the bar cross-sections for
vertical busbars are determined according to
the In which is to be distributed. In order to
find the maximum In of a vertical busbar,
apply the following general rule.
„ Faire la somme des In déclassées de
tous les appareils raccordés au même
jeu de barres vertical, la multiplier par le
facteur de diversité (recommandation
IEC 60439.1) ci-dessous:
„ Add up the derated In of all circuit
breakers linked to the same vertical
busbar, multiply by the diversity factor
(IEC 60439.1 recommendation) below:
nombre d'appareils connecté au
jeu de barres vertical
number of circuit breakers on
vertical busbar
2 et 3
2 and 3
4 et 5
4 and 5
6à9
6 and 9
10 et plus
10 and more
„ Avec l'In ainsi obtenue se reporter aux
tableaux des intensités admissibles dans
les barres pour trouver la section.
Guide Technique V9 / V9 Technical Guide
facteur de diversité
diversity factor
0.9
0.8
0.7
0.6
„ With the In thus obtained refer to the
tables with the admissible currents in the
bars to find the cross-section.
34
Jeux de barres
Busbars
2.2.1.4.
Intensité admissible dans les barres de cuivre d’un JdB
vertical.
Admissible current in vertical copper bars
En fonction de l'intensité, de la température
ambiante extérieur et de l'indice de
protection du tableau, déterminer le nombre
et la section des barres à utiliser par phase.
CaLCulate the number and cross-section of
the bars to be used per phase, according to
the current, the outside ambient temperature
and the switchboard’s degree of protection.
Valeurs données pour barre de cuivre nu,
époxy ou argenté
Values data for bare copper, epoxy and
silver plated
IP ≤ 42
Type D, Mf et Ms
D, Mf and Ms type
Section /ph
Cross-section /ph
Température ambiante extérieure (°C)
Outside ambient temperature (°C)
35
40
45
50
1b x 63 x 5 *
850
800
750
700
2b x 63 x 5 *
1500
1450
1400
1300
1b x 80 x 5
1100
1050
1000
950
2b x 80 x 5
1800
1750
1650
1550
3b x 80 x 5
2350
2250
2150
2050
4b x 80 x 5
2800
2700
2550
2400
5b x 80 x 5
3250
3100
3000
2800
Type Mw
Mw type
Section /ph
Cross-section /ph
1b x 80 x 6
Température ambiante extérieure (°C)
Outside ambient temperature (°C)
35
40
45
50
1050
1000
950
900
IP 54
Type D, Mf et Ms
D, Mf and Ms type
Section /ph
Cross-section /ph
Température ambiante extérieure (°C)
Outside ambient temperature (°C)
35
40
45
50
1b x 63 x 5 *
750
700
650
600
2b x 63 x 5 *
1250
1200
1150
1100
1b x 80 x 5
950
900
850
800
2b x 80 x 5
1600
1550
1500
1350
3b x 80 x 5
2150
2050
1950
1850
4b x 80 x 5
2550
2450
2350
2200
5b x 80 x 5
2950
2850
2700
2550
Guide Technique V9 / V9 Technical Guide
35
Jeux de barres
Busbars
Type Mw
Mw type
Section /ph
Cross-section /ph
1b x 80 x 6
Température ambiante extérieure (°C)
Outside ambient temperature (°C)
35
40
45
50
800
770
730
690
Valeurs données pour cuivre étamé
(Seulement pour D, Mf et Ms)
Values data for tinned copper (Only for D,
Mf and Ms)
IP ≤ 42
Section /ph
Cross-section /ph
Température ambiante extérieure (°C)
Outside ambient temperature (°C)
35
40
45
50
1b x 63 x 5 *
800
750
700
650
2b x 63 x 5 *
1400
1350
1300
1200
1b x 80 x 5
1050
1000
950
900
2b x 80 x 5
1700
1600
1550
1450
3b x 80 x 5
2250
2150
2050
1950
4b x 80 x 5
2600
2500
2400
2300
5b x 80 x 5
3050
2900
2800
2650
IP 54
Section /ph
Cross-section /ph
Température ambiante extérieure (°C)
Outside ambient temperature (°C)
35
40
45
50
1b x 63 x 5 *
650
600
550
500
2b x 63 x 5 *
1150
1100
1050
1000
1b x 80 x 5
900
850
800
750
2b x 80 x 5
1500
1450
1400
1300
3b x 80 x 5
2000
1900
1800
1700
4b x 80 x 5
2350
2250
2200
2050
5b x 80 x 5
2700
2600
2500
2350
*: - Il n’y a pas de rapports d’essais de type
pour ces barres.
Guide Technique V9 / V9 Technical Guide
*: -There are no type test reports for these
bars.
36
Jeux de barres
Busbars
2.2.1.5.
Distance entre supports d’un JdB Vertical.
Distance between supports in vertical busbar
Principe fondamentaux
Les supports de barres assurent la tenue
mécanique du circuit principal,
particulièrement au moment d'un courtcircuit. La distance maximale entre les
supports est fonction du courant assigné de
courte durée admissible, du nombre et de la
section des barres ainsi que de leurs
entraxe(75 ou 125 mm).
Règle d'application
La distance entre les supports devra être au
maximum égale à la valeur mentionnée dans
les différents tableaux.
Basic principles
The bar supports ensure the mechanical
resistance of the main circuit, and in
particular when a short-circuit occurs. The
maximum distance between the supports
depends on the rated short-time withstand
current, on the number and cross-section of
the bars, as well as their centre distances (75
or 125 mm).
Application rule
The distance between supports should, at its
maximum, be equal to the value quoted in
the different tables.
Note 1: les supports de calage inférieur ne participent
pas à la tenue aux efforts électrodynamiques.
Note 1: bottom wedge supports do not contribute to
the electrodynamic force resistance.
Note 2: les valeurs des distances maximales sont
exprimées en mm. Les tableaux ont été établis
à partir des certificats de conformité n°
FR97.050 et 062-97 délivrés pour le compte
de l’ASEFA. Les tableaux sont à utiliser en
courant alternatif 50 ou 60 Hz triphasé.
Note 2: the maximum distance values are given in
mm. The tables were developed from
conformity certificates no. FR97.050 and 06297 issued for the ASEFA accounts. The tables
are to be used with 50 or 60 Hz three-phase
AC current.
Tableau pour entre-axe des barres 75 mm (profondeur 400/600)
Table for 75 mm bar centre distances (depth 400/600)
Section Jeux de barres/ph
Busbar cross-section/ph
Icc=30kA
Isc=30kA
Icc=50kA
Isc=50kA
1b x 63 x 5
237.5 *
interdit / forbidden
2b x 63 x 5
237.5 *
200
1b x 80 x 5
475
237.5
2b x 80 x 5
475
237.5
Type de supports
Type of supports
fixe
fixed
fixe + volant
fixed + movable
*: pour ces configurations utilisez supports
fixe + volant
Voir plan 51128225
*: for these configurations use supports fix
+ movable
See drawing n° 51128225
Tableau pour entre-axe des barres 125 mm (profondeur 600)
Table for 125 mm bar centre distances (depth 600)
Section Jeux de barres/ph
Busbar cross-section/ph
Icc=50kA
Isc=50kA
Icc=85kA
Isc=85kA
1b x 80 x 5
500
interdit / forbidden
2b x 80 x 5
500
250
3b x 80 x 5
500
250
4b x 80 x 5
500
250
5b x 80 x 5
500
250
Type de supports
Type of supports
fixe
fixed
fixe + volant
fixed + movable
Voir plan 51127307
Guide Technique V9 / V9 Technical Guide
See drawing n° 51127307
37
Jeux de barres
Busbars
2.2.1.6.
Dimensionnement du neutre
Neutral dimensioning
Si rien n'est précisé sur le cahier des
charges, le choix de la section du neutre est
réalisé en fonction des caractéristiques
suivantes:
„ Le neutre doit pouvoir véhiculer la même
intensité nominale que le jeu de barres
auquel il est associé.
„ Le neutre doit pouvoir tenir à une
contrainte thermique correspondant à
60% de l' Icc du jeu de barres.
2.2.2.
If nothing is specified in the specification, the
choice of neutral cross-section is made
according to the following characteristics:
„ The neutral must be able to transmit the
same nominal current as the busbar to
which it is connected.
„ The neutral must be able to withstand a
thermal stress which corresponds to 60%
of the busbar Isc.
Jeux de barres Linergy
Linergy busbars
260,5 mm
135,5 mm
50 kA
85 kA
voir plan de montage dans “guide de
montage”
Longueur jeux de barres horizontal
voir plans des barres et Guide des Plans
d’assemblage, ref. ” 7041xxx.pdf
see the assembly drawing in the “assembly
guide”.
Length of horizontal busbars
see the busbar drawings and the Assembly
Drawings Guide, ref: “7041xxx.pdf”.
Intensité admissible
Information
Pour ces Jeux de barres, un seul calibre est
utilisé: 1600 A.
Ces Jeux de barres permettent le
raccordement des départs à n'importe quelle
hauteur et offre un accès direct par l'avant du
tableau à tous les points de raccordement.
Admissible current
Information:
For these busbars, one single rating is used:
1600 A.
These busbars enable the outgoing cables to
be connected at any height and provide
direct access from the front of the
switchboard to all connection points.
Règle d'application
La distance entre les supports devra être au
maximum égale à la valeur mentionnée dans
les différent tableaux.
Application rule
The distance between supports should, at its
maximum, be equal to the value quoted in
the different tables.
Note: les valeurs de la distance maximales sont données dans mm. Les tables ont été développées
de certificats de la conformité non. FR97.062 et
065-97 ont publié pour les comptes ASEFA. Les
tables seront utilisées avec 50 ou 60 trois-phase
du Hz courant AC.
Note: the maximum distance values are given in mm.
The tables were developed from conformity certificates no. FR97.062 and 065-97 issued for the
ASEFA accounts. The tables are to be used with
50 or 60 Hz three-phase AC current.
Guide Technique V9 / V9 Technical Guide
38
Jeux de barres
Busbars
Intensité admissible
Admissible current
Ref.
LINERGY
Intensité
Current
IP ≤ 42
IP 54
35
40
45
50
35
40
45
50
7365
1600
1600
1530
1470
1350
1450
1390
1330
1225
Nombre de supports
Number of supports
Ref.
LINERGY
Intensité
Current
Icc = 30 kA
Isc = 30 kA
Icc = 50 kA
Isc = 50 kA
Icc = 85 kA
Isc = 85 kA
7365
1600
3
3
6
Distance entre supports
Distance between supports
Distance entre supports
Distance between supports
Icc = 30 kA
Isc = 30 kA
Icc = 50 kA
Isc = 50 kA
Icc = 85 kA
Isc = 85 kA
mm
550
550
275
Guide Technique V9 / V9 Technical Guide
39
Jeux de barres
Busbars
2.3. Dimensionnement du PE et PEN
Dimensioning of PE and PEN
PE: de part sa fonction, le PE n'est parcouru
par un courant que lors d'un défaut et
pendant la durée d'élimination de ce dernier.
Son dimensionnement n'est donc fonction
que de la contrainte thermique, c'est à dire
lié à la valeur de l'Icc et de la durée de
défaut. Lors des essais d'homologation, il est
demandé au PE de tenir à un défaut dont
l'intensité correspond à 60% de l'Icc du jeu
de barres pendant 0.5 s.
Actuellement la gamme Blokset étant conçu
pour répondre jusqu’à des Icc de 100 kA, le
PE doit tenir à 60 kA au maximum. Pour une
durée de défaut de 0.5 s
Section
Cross Section
Icc (kA)
Isc (kA)
1b 50 x 5
30 / 50
2b 50 x 5
85 / 100
PEN: faisant office de NEUTRE et de PE,
son dimensionnement suit les mêmes règles
que le neutre car elles sont plus
contraignantes.
Guide Technique V9 / V9 Technical Guide
PE: in view of its function, the current only
flows through the PE when a fault occurs and
during the time it takes to remove the fault.
Its dimensions are therefore only in
accordance with the thermal stress, i.e.
linked to the lsc value and the duration of the
fault. During the approval tests, the PE is
required to withstand a fault with a current
which corresponds to 60% of the busbar lsc
for 0.5 s.
The Blokset range is currently designed to
respond to lsc of 100 kA, with the PE capable
of withstanding a maximum of 60 kA. For a
fault duration of 0.5 s
PEN: which serves as Neutral and PE, is
dimensioned according to the rules for the
neutral since they are more restrictive.
40
Sommaire du chapitre
Chapter contents
3. Installation de l’appareillage
Switchgear Installation
3.1. Disjoncteurs et interrupteurs
Circuit breakers and switches
3.1.1.
3.1.2.
Déclassement des appareils .................................................................... 43
Circuit breaker derating
3.1.1.1.
Coefficient de déclassement ....................................................... 43
Derating coefficient
3.1.1.2.
Compact NB - EasyPact .............................................................. 45
3.1.1.3.
Compact NS .................................................................................. 46
3.1.1.3.a.
Compact NS100 à NS630 3/4P ....................................................... 46
Compact NS100 to NS630 3/4P
3.1.1.3.b.
Compact NS630b à NS3200 3/4P ................................................... 47
Compact NS630b to NS3200 3/4P
3.1.1.4.
Compact C .................................................................................... 48
3.1.1.5.
Compact CM ................................................................................. 49
3.1.1.6.
Masterpact .................................................................................... 50
3.1.1.6.a.
Masterpact NT06 à NT16 3/4P ........................................................ 50
Masterpact NT06 to NT16 3/4P
3.1.1.6.b.
Masterpact NW08 à NW25 3/4P ..................................................... 51
Masterpact NW08 to NW25 3/4P
3.1.1.6.c.
Masterpact NW32 et NW40 3/4P .................................................... 52
Masterpact NW32 and NW40 3/4P
3.1.1.6.d.
Masterpact NW40b, NW50 et NW63 3/4P (Profundeur 600 mm).. 53
Masterpact NW40b, NW50 and NW63 3/4P(600 mm depth)
3.1.1.6.e.
Masterpact NW40b, NW50 et NW63 3/4P (Profundeur 1000 mm) 54
Masterpact NW40b, NW50 and NW63 3/4P(1000 mm depth
Installation ................................................................................................. 55
Installation
3.1.2.1.
Multi 9 ............................................................................................ 55
3.1.2.2.
Compact NB - EasyPact .............................................................. 56
3.1.2.3.
Compact NS .................................................................................. 57
3.1.2.3.a.
Compact NS100 à NS630 .............................................................. 57
Compact NS100 to NS630
3.1.2.3.b.
Compact NS630b à NS1600 .......................................................... 66
Compact NS630b to NS1600
3.1.2.3.c.
Compact NS1600b à NS3200 ......................................................... 74
Compact NS1600b to NS3200
3.1.2.4.
Compact C .................................................................................... 75
Guide Technique V9 / V9 Technical Guide
41
Sommaire du chapitre
Chapter contents
3.1.2.5.
3.1.2.6.
Compact CM ................................................................................. 77
Masterpact .................................................................................... 78
3.1.2.6.a.
Masterpact NT06 à NT10 ................................................................ 78
Masterpact NT06 to NT10
3.1.2.6.b.
Masterpact NW08 à NW40 .............................................................. 80
Masterpact NW08 to NW40
3.1.2.6.c.
Masterpact NW40b à NW63 ............................................................ 84
Masterpact NW40b to NW63
3.1.2.6.d.
Choix des transformateurs de courant (TI) .................................. 85
Choice of current transformers (CT)
3.1.2.7.
Option raccordement jeu de barres Disjoncteur
Compact NS 630b-1600 et Masterpact NT / NW ......................... 86
Option connection busbars Compact NS 630b-1600 and
Masterpact NT / NW circuit breaker
3.1.2.8.
Option raccordement client Disjoncteur
Compact NS 630b-1600 et Masterpact NT / NW ........................ 97
Option incoming bars Compact NS 630b-1600 and
Masterpact NT / NW circuit breake
3.1.2.9.
Interpact ...................................................................................... 104
3.1.2.10.
Inverseur de source ................................................................... 105
Source changeover
3.1.2.10.a. Interpact, Compact NS 100-630, Compact C et Masterpact M
(en profondeur 600 mm) ............................................................... 105
Interpact, Compact NS, Compact C et Masterpact M
(600 mm depth)
3.1.2.10.b. Compact NS 630b - NS 1600, 3/4P (fixe derrière ou à travers porte,
débrochable à travers porte)
Masterpact NT 06 à 16, 3/4P (fixe/débrochable).......................... 106
Compact NS 630b - NS 1600, 3/4P (fixed behind or through door,
withdrawable behind or though door)
Masterpact NT 06 to 16, 3/4P (fixed/withdrawable)
3.1.2.10.c. Compact NS 630b à NS 1600,3/4P débrochable derrière porte . 108
Compact NS 630b to NS 1600,3/4P withdrawable behind door
3.1.2.10.d. Compact NS 630b à NS 1600, 3/4P fixe ou débrochable derrière
porte ............................................................................................... 110
Compact NS 630b to NS 1600, 3/4P fixed or withdrawable behind
3.1.2.10.e. Masterpact NW 08 à 25, 3/4P fixe/débro à travers porte ........... 111
Masterpact NW 08 to 25, 3/4P fixed/drawout through door
3.1.2.10.f.
Masterpact NW 08 à 20, 3/4P fixe/débro à travers porte ........... 112
Masterpact NW 08 to 20, 3/4P fixed/ drawout through door
3.1.2.10.g. Masterpact NW 32 à 63, 3/4P fixe/débro (RAV/RAR) ................. 113
Masterpact NW 32 to 63, 3/4P fixed/ drawout (Front/Rear access)
3.1.2.11.
Couplage et Jeux de Barres de Transfert ............................... 114
Tie Breaker and Transfer Busbar
3.1.2.11.a. Masterpact NW40 et jeu des barres simple ................................ 114
Masterpact NW40 and single busbars
3.1.2.11.b. Masterpact NW40b/50/63 et jeu des barres double ................... 115
Masterpact NW40b/50/63 and double busbars
Guide Technique V9 / V9 Technical Guide
42
Installation de l’appareillage
Switchgear Installation
3. Installation de l’appareillage
Switchgear Installation
3.1. Disjoncteurs et interrupteurs
Circuit breakers and switches
3.1.1.
3.1.1.1.
Déclassement des appareils
Circuit breaker derating
Coefficient de déclassement
Derating coefficient
Les températures à l’intérieur d’un tableau et
les éventuels coefficients de déclassement à
appliquer pour les appareils sont fonction de
la configuration étudiée. Ceci peut-être fait
de façon précise par logiciel. Cependant les
coefficients d’un appareil donné ont des
valeurs semblables pour de nombreuses
configurations, en particulier dans le cas
d’un tableau contenant:
1 Masterpact + des Compact.
The temperatures inside the switchboard
and the possible derating coefficients to be
applied to the circuit breakers depend on the
configuration under study. This can be done
with precision using software. However, the
coefficients of a given circuit breaker have
similar values for numerous configurations,
in particular for a switchboard containing:
1 Masterpact + Compacts
Nous avons donc défini un tableau type dont
l’image thermique illustrant le régime de
fonctionnement nous a permis de déterminer
le déclassement des appareils les plus
contraints. Le Masterpact et le Compact en
position haute (cf. tableaux 1, 2, 3, 4, 5).
We have defined a standard switchboard. Its
thermal overload, which illustrates the
operating system, has made it possible to
caLCulate the derating for the most
restricted circuit breakers. The Masterpact
and the Compact are mounted in a high
position (see tables 1, 2, 3, 4, 5).
Pour les tableaux ne contenant que des
Masterpact, les déclassements ne sont pas
tributaires de la configuration. Ainsi une liste
exhaustive de configurations (les plus
fréquentes) a été définie ainsi que le
déclassement des appareils en fonction de
leurs positions.
For switchboards only containing
Masterpacts, the derating does not depend
on the configuration. Hence, a
comprehensive list of configurations (the
most frequent) has been drawn up in
addition to the circuit breaker derating
according to the positions.
Les tableaux indiquent les intensités
admissibles pour chaque type d’appareil en
fonction de la température ambiante
extérieure, de l’IP et de sa position dans le
tableau.
The tables indicate the admissible currents
for each type of circuit breaker in accordance
with outside ambient temperature, the
degree of protection and the position in the
switchboard.
Influence de l’altitude sur les caractéristiques
du disjoncteur (Compact ou Masterpact):
The influence of altitude on circuit breaker
characteristics (Compact or Masterpact):
Guide Technique V9 / V9 Technical Guide
43
Installation de l’appareillage
Switchgear Installation
La norme de construction IEC 60947-1
(§ 6.1.2) précise que l’altitude du lieu où le
disjoncteur doit être installé n’excède pas
2000 m.
The IEC 60947-1 standard (§ 6.1.2)
specifies that the altitude of the place where
the circuit breaker is to be installed should
not exceed 2000 m.
Il s’ensuit que l’altitude n’a pas d’influence
sur les caractéristiques des disjoncteurs
jusqu’à 2000 m.
It follows that altitude does not influence the
circuit breaker characteristics up to 2000 m.
Au delà, il faudra déclasser l’appareil en
appliquant le coefficient suivant:
„ Altitude 3000 m ..............................
coefficient 0,99.
„ Altitude 4000 m ..............................
coefficient 0,96.
„ Altitude 5000 m ..............................
coefficient 0,94.
Above that, the circuit breaker must be
derated by applying the following coefficient:
„ Altitude 3000 m ..............................
Coefficient 0.99.
„ Altitude 4000 m ..............................
Coefficient 0.96.
„ Altitude 5000 m ..............................
Coefficient 0.94.
Note 1: Les valeurs de déclassement sont données
pour IP ≤ 42 et IP 54.
Note 1: Derating values are given for IP ≤ 42 and IP
54.
Note 2: Dans les pages suivantes, T°amb indique la
température ambiante dans le local où est
installé le tableau.
Note 2: In the following pages, T°amb indicates the
ambient temperature in the room where the
switchboard is installed.
Guide Technique V9 / V9 Technical Guide
44
Installation de l’appareillage
Switchgear Installation
3.1.1.2.
Compact NB - EasyPact
Tableau de déclassement des Compact
NB50 à NB600 et EasyPact.
Derating table for Compact NB50 to NB600
and EasyPact.
Compact NB
200
700
Intensité en A
Current in A
Tableau 1
Table 1
T°amb (°C)
IP 54
IP ≤ 42
35
40
45
50
35
40
45
50
NB225
215
205
200
195
195
190
185
180
NB400
390
380
375
360
350
340
330
320
NB600
530
525
515
495
460
450
440
430
Note: Les disjoncteurs NB50, NB100 et
EZD100 (EasyPact) ne sont pas déclassés
jusqu’à une température de 50 °C.
Pour réalisation des IP, voir les règles dans
le Guide des plans d’assemblage
7041xxx.pdf item 6.6.
Guide Technique V9 / V9 Technical Guide
Note: The circuit breakers NB50, NB100 and
EZD100 (EasyPact) are not derated up to a
temperature of 50 °C.
For carrying out the IP, verify the rules on
item 6.6 of Assembly drawings guide
7041xxx.pdf
45
Installation de l’appareillage
Switchgear Installation
3.1.1.3.
Compact NS
Tableau de déclassement des Compact NS.
3.1.1.3.a.
Derating table for Compact NS.
Compact NS100 à NS630 3/4P
Compact NS100 to NS630 3/4P
Compact NS
200
700
Intensité en A
Current in A
Tableau 1
Table 1
T°amb (°C)
IP ≤ 42
IP 54
35
40
45
50
35
40
45
50
NS100
100
100
95
95
95
95
90
85
NS160
155
155
150
145
145
140
135
130
NS250
240
230
225
220
215
210
205
200
NS400
390
380
375
360
350
340
330
320
NS630
555
550
540
520
480
470
460
450
Pour réalisation des IP, voir les règles dans
le Guide des plans d’assemblage
7041xxx.pdf item 6.6.
Guide Technique V9 / V9 Technical Guide
For carrying out the IP, verify the rules on
item 6.6 of Assembly drawings guide
7041xxx.pdf
46
Installation de l’appareillage
Switchgear Installation
3.1.1.3.b.
Compact NS630b à NS3200 3/4P
Compact NS630b to NS3200 3/4P
Compact NS
200
700
Intensité en A
Current in A
Tableau 1
Table 1
T°amb (°C)
IP ≤ 42
IP 54
35
40
45
50
35
40
45
50
NS630b
630
630
630
630
630
630
630
630
NS800
800
800
800
800
800
800
800
800
NS1000
1000
1000
1000
1000
1000
1000
950
950
NS1250
1200
1150
1100
1050
1050
1025
1000
950
NS1600
1350
1325
1300
1250
1200
1150
1125
1100
NS1600b
1600
1550
1500
1450
NS2000
2000
2000
2000
1950
NS2500
2350
2300
2200
2150
NS3200
2720
2650
2550
2450
Pour réalisation des IP, voir les règles dans
le Guide des plans d’assemblage
7041xxx.pdf item 6.6.
Guide Technique V9 / V9 Technical Guide
For carrying out the IP, verify the rules on
item 6.6 of Assembly drawings guide
7041xxx.pdf
47
Installation de l’appareillage
Switchgear Installation
3.1.1.4.
Compact C
Tableau de déclassement des Compact
C801 à C1251
Derating table for Compact C801 to C1251
Compact C
200
700
Intensité en A
Current in A
Tableau 1
Table 1
T°amb (°C)
IP ≤ 42
IP 54
35
40
45
50
35
40
45
C801
750
710
670
640
670
630
590
C1001N/H
900
850
800
750
810
770
720
C1001L
890
840
790
730
800
760
700
C1251
1125
1060
1000
940
1010
960
900
Pour réalisation des IP, voir les règles dans
le Guide des plans d’assemblage
7041xxx.pdf chapitre 6.6.
Guide Technique V9 / V9 Technical Guide
50
For carrying out the IP, verify the rules on
chapter 6.6 of Assembly drawings guide
7041xxx.pdf.
48
Installation de l’appareillage
Switchgear Installation
3.1.1.5.
Compact CM
Tableau de déclassement des Compact
CM1250 à CM3200
Derating table for Compact CM1250 to
CM3200
Compact CM
Appareillage
Devices
200
700
Intensité en A
Current in A
Tableau 1
Table 1
T°amb (°C)
IP ≤ 42
IP 54
35
40
45
CM1250
1250
1150
CM1600
1330
CM2000
50
35
40
45
1050
1000
920
840
1260
1190
1060
1040
950
1660
1550
1440
1330
1240
1150
CM2500
2075
1950
1840
1660
1560
1470
CM3200
2700
2600
2500
2160
2080
2000
Pour réalisation des IP, voir les règles dans
le Guide des plans d’assemblage
7041xxx.pdf chapitre 6.6.
Guide Technique V9 / V9 Technical Guide
50
For carrying out the IP, verify the rules on
chapter 6.6 of Assembly drawings guide
7041xxx.pdf
49
Installation de l’appareillage
Switchgear Installation
3.1.1.6.
Masterpact
Tableau de déclassement des Masterpact
3.1.1.6.a.
Derating table of Masterpact
Masterpact NT06 à NT16 3/4P
Masterpact NT06 to NT16 3/4P
Masterpact
Appareillage
Devices
200
700
Intensité en A
Current in A
Tableau 1
Table 1
T°amb (°C)
IP ≤ 42
IP 54
35
40
45
50
35
40
45
50
NT06
630
630
630
630
630
630
630
630
NT08
800
800
800
800
800
800
800
800
NT10
1000
950
900
900
900
900
850
850
NT12
1250
1250
1200
1150
1150
1100
1050
1000
NT16
1400
1350
1300
1250
1250
1200
1150
1100
Pour réalisation des IP, voir les règles dans
le Guide des plans d’assemblage
7041xxx.pdf chapitre 6.6.
Guide Technique V9 / V9 Technical Guide
For carrying out the IP, verify the rules on
chapter 6.6 of Assembly drawings guide
7041xxx.pdf
50
Installation de l’appareillage
Switchgear Installation
3.1.1.6.b.
Masterpact NW08 à NW25 3/4P
Masterpact NW08 to NW25 3/4P
Masterpact
Appareillage
Devices
200
700
Intensité en A
Current in A
Tableau 1
Table 1
T°amb (°C)
IP ≤ 42
IP 54
35
40
45
50
35
40
45
50
NW08
800
800
800
800
800
800
800
800
NW10
1000
1000
1000
1000
1000
1000
1000
1000
NW12
1250
1250
1250
1250
1250
1250
1200
1150
NW16
1550
1500
1450
1400
1400
1350
1300
1250
NW20
2000
2000
2000
1900
1850
1800
1700
1650
NW25
2350
2300
2200
2150
2050
2000
1950
1900
Pour réalisation des IP, voir les règles dans
le Guide des plans d’assemblage
7041xxx.pdf chapitre 6.6.
Guide Technique V9 / V9 Technical Guide
For carrying out the IP, verify the rules on
chapter 6.6 of Assembly drawings guide
7041xxx.pdf.
51
Installation de l’appareillage
Switchgear Installation
3.1.1.6.c.
Masterpact NW32 et NW40 3/4P
Masterpact NW32 and NW40 3/4P
NW32 / 40
3/4P
VIDE
EMPTY
700
Intensité en A
Current in A
Tableau 1
Table 1
T°amb (°C)
IP ≤ 42
IP 54
35
40
45
50
35
40
45
NW32
3000
2950
2900
2850
2900
2850
2700
-
NW40
3550
3450
3350
3250
3350
3250
3150
-
Pour réalisation des IP, voir les règles dans
le Guide des plans d’assemblage
7041xxx.pdf chapitre 6.6.
Guide Technique V9 / V9 Technical Guide
50
For carrying out the IP, verify the rules on
chapter 6.6 of Assembly drawings guide
7041xxx.pdf
52
Installation de l’appareillage
Switchgear Installation
3.1.1.6.d.
Masterpact NW40b, NW50 et NW63 3/4P (Profundeur 600 mm)
Masterpact NW40b, NW50 and NW63 3/4P(600 mm depth)
NW40b / NW50 / NW63
3/4P
Ventilateurs voir plan 51132529X0
Fan see drawing 51132529X0
VIDE
EMPTY
600
1200
Intensité en A
Current in A
Tableau 1
Table 1
T°amb (°C)
IP ≤ 31 Ventilé / Ventilated
IP 42 Ventilé / Ventilated
35
40
45
50
35
40
45
50
NW40b
4000
4000
4000
4000
4000
3850
3700
3550
NW50
5000
5000
5000
4900
4800
4600
4300
4000
NW63
5650
5450
5300
5100
5200
5050
4850
4650
T°amb (°C)
IP 54 Ventilé / Ventilated
35
40
45
50
NW40b
4000
3850
3700
3550
NW50
4600
4450
4200
3900
NW63
4900
4750
4500
4200
Pour réalisation des IP, voir les règles dans
le Guide des plans d’assemblage
7041xxx.pdf chapitre 6.6.
Guide Technique V9 / V9 Technical Guide
For carrying out the IP, verify the rules on
chapter 6.6 of Assembly drawings guide
7041xxx.pdf.
53
Installation de l’appareillage
Switchgear Installation
3.1.1.6.e.
Masterpact NW40b, NW50 et NW63 3/4P (Profundeur 1000 mm)
Masterpact NW40b, NW50 and NW63 3/4P(1000 mm depth)
NW40b / NW50 / NW63
3/4P
VIDE
EMPTY
1000
1200
Intensité en A
Current in A
Tableau 1
Table 1
T°amb (°C)
IP ≤ 31
IP 42
35
40
45
50
35
40
45
50
NW40b
4000
4000
3890
3800
3950
3850
3760
3670
NW50
5000
4940
4800
4670
4860
4760
4650
4540
NW63
5490
5360
5230
5090
5220
5100
4990
4890
35
40
45
50
NW40b
3870
3790
3700
3670
NW50
4780
4680
4580
4470
NW63
5090
4980
4900
4780
T°amb (°C)
IP 54
Dans un tableau, il n’est pas nécessaire
ventiler cette colonne en IP42. Les colonnes
adjacentes devront être ventilées suivant
chapitre 6.6 du Guide des plans
d’assemblage 7041xxx.pdf, pour réalisation
des IP.
Guide Technique V9 / V9 Technical Guide
In a switchboard this column does not need
ventilation in IP42. The adjacent columns
must be ventilated according to the chapter
6.6 of Assembly drawings guide 7041xxx.pdf
for carrying out the IP.
54
Installation de l’appareillage
Switchgear Installation
3.1.2.
Installation
Installation
3.1.2.1.
Multi 9
Choix des platines et types de commande
Choice of mounting plates and type of operating mechanism
Nb app.
Nbr of CBs
Position
Position
Nb modules
Nb of
modules
Forme
Form
Type de commandes
Type of operating
mechanism
Fixation
Fixing
jusqu’a 48 modules de 9 mm
up to 48 modules of 9 mm
V
3
1
A/B/D
fixe
jusqu’a 48 modules de 9 mm
up to 48 modules of 9 mm
V
4 (*)
1
A/B/D
fixe
Type de commande
Type of operating mechanism
A:
derrière porte
behind door
maneton
toggle
B:
à travers porte
through door
maneton
toggle
D:
à travers plastron
through front plate
maneton
toggle
(*) 4 modules sont nécéssaire si la taille des
câbles client est égal ou suppérieur à
10 mm2.
Guide Technique V9 / V9 Technical Guide
(*) 4 modules are necessary if the customer
cable size is equal or bigger than 10 mm2.
55
Installation de l’appareillage
Switchgear Installation
3.1.2.2.
Compact NB - EasyPact
Choix des platines et types de commande
Choice of mounting plates and type of operating mechanism
Type d’appareils
Type of circuit breaker
Nb pôles
Nbr of poles
Nb app.
Nbr of CBs
Position
Position
Nb modules
Nb of modules
Forme
Form
Type de commandes
Type of operating
mechanism
Fixation
Fixing
NB50
3
6
V
4
1
A/B/D
fixe
NB100
3
5
V
6
1
A/B/D
fixe
EZD100B/F/N/H (1)
3
6
V
6
1
A/B/D
fixe
NB225
3
4
V
6
1
A/B/D
fixe
NB400
3
3
V
12
1
A/B/D
fixe
NB600
3
3
V
12
1
A/B/D
fixe
Type de commande
Type of operating mechanism
A:
derrière porte
behind door
maneton
toggle
B:
à travers porte
through door
maneton
toggle
D:
à travers plastron
through front plate
maneton
toggle
(1)
(1)
Limitè à 415V
Accessoires obligatoires pour l’installation
des Compact NB 400/600:
„ Séparateur de phases
Limited to 415V
Compulsory accessories for Compact NB
400/600 installation:
„ Phase barriers
Compact NB raccordé au jeu de Barres Vertical à gauche
Compact NB connected to the vertical bars on the left
Type D & Mf
Type D & Mf
NB50 / 100
NB225
NB400 / 600
Raccordement
Connections
AV ou AR
Front or Rear
possibilités
possibilities
oui
yes
Compact NB raccordé au jeu de Barres Vertical à droite
Compact NB connected to the vertical bars on the right
Type D & Mf
Type D & Mf
NB50 / 100
NB225
NB400 / 600
Guide Technique V9 / V9 Technical Guide
Raccordement
Connections
AV ou AR
Front or Rear
AV ou AR
Front or Rear
possibilités
possibilities
oui (par câbles)
yes (by cables)
oui
yes
56
Installation de l’appareillage
Switchgear Installation
3.1.2.3.
Compact NS
3.1.2.3.a.
Compact NS100 à NS630
Compact NS100 to NS630
Choix des platines et types de commande
Choice of mounting plates and type of operating mechanism
Type d’appareils Fixation
Type of circuit
Fixing
breaker
NS100/250
NS400/630
NS100/250
NS400/630
NS100/250
NS400/630
Nb pôles
Nbr of
poles
Forme
Form
Nb app.
Nbr of CBs
Position
Position
Type de commande Nb modules
Type of operating Nb of modules
mechanism
fixe / socle
fixed/plug-in
3
1/2**
4
V
A/B/D
6 (NS 100/160)
6 + 3 (NS 250)
fixe / socle
fixed/plug-in
4
1/2**
3
V
A/B/D
6 (NS 100/160)
6 + 3 (NS 250)
fixe
fixed
3
1
3
V
AB/D
12
fixe
fixed
4
1
2
V
A/B/D
12
fixe / socle
fixed/plug-in
3
1/2/3/4
1
H
A/B/C/D
3
fixe / socle
fixed/plug-in
4
1/2/3/4
1
H
A/B/C/D
4
fixe / socle
fixed/plug-in
3
1/2/3/4
****
2
H
A
3
fixe / socle
fixed/plug-in
4
1/2/3/4
****
2
H
A
4
fixe / socle
fixed/plug-in
3
1/2/3/4
4
H
A/B/C/D
12
fixe / socle
fixed/plug-in
4
1/2/3/4
3
H
A/B/C/D
12
fixe / socle
fixed/plug-in
3
1/2/3/4
1
H
A***/B/C/D
4
fixe / socle
fixed/plug-in
4
1/2/3/4
2
H
A***/B/C/D
12
fixe / socle
fixed/plug-in
3
1/2/3/4
3
H
A***/B/C/D
12
fixe / socle
fixed/plug-in
4
1/2/3/4
1
H
A***/B/C/D
6
chassis
withdrawable
3/4
1/2/3/4
1
V
A/E
6
chassis
withdrawable
3
1/2/3/4
****
2
H
A
8
chassis
withdrawable
4
1/2/3/4
****
2
H
A
10
chassis
withdrawable
3/4
1/2/3/4
1
V
A ou / or E
8
Guide Technique V9 / V9 Technical Guide
57
Installation de l’appareillage
Switchgear Installation
** forme 2 seulement possible avec Polypact
*** eléctrique et derriére porte seulement
forme 1
**** Forme 4, seulement en profondeur 1000
mm.
** form 2 possible with Polypact only
*** motor mechanism and behind door, only
form 1
****Form 4, only in 1000 mm. depth
Choix des disjoncteurs avec Polypact
Choice of Circuit breakers with Polypact
Nb pôles
Nbr poles
1er disj.
1st CB
2nd disj.
2nd CB
3eme disj
3rd CB
4eme disj.
4th CB
3
NS100/160
NS100/160
NS100/160
NS100/160
3
NS100
NS100/160
NS100/160
NS250
4
NS100/160
NS100/160
NS100/160
///////////////
4
NS100
NS100/160
NS250
///////////////
Type de commande
Type of operating mechanism
A:
derrière porte
behind door
maneton / rotative directe/ électrique
toggle / direct rotary handle / motor mechanism
B:
à travers porte
through door
maneton / rotative directe / électrique
toggle / direct rotary handle / motor mechanism
C:
derrière porte individuelle
behind individual door
commande rotative prolongée
extended rotary handle
D:
à travers plastron
through front plate
maneton
toggle
E:
derrière porte (chassis)
behind door (frame)
commande rotative prolongée télescopique
telescopic extended rotary handle
Accessories obligatoires pour
l’installation des
Compact NS100/160/250:
„ Prise arrière en raccordement arrière sur
prise aval.
Compulsory accessories for
Compact NS100/160/250 installation:
Obligatoires pour l’installation des
Compact NS400/630:
„ Prise arrière côté amont
„ Prise arrière côté aval.
Compulsory with the installation of the
Compact NS400/630:
„ Rear connector on line side.
„ Rear connector on load.
Guide Technique V9 / V9 Technical Guide
„ Rear connector for rear access on load
side connection.
58
Installation de l’appareillage
Switchgear Installation
Compact NS raccordé au jeu de Barres Vertical à gauche
Compact NS connected to the vertical bars on the left
Type D & Mf
Type D & Mf
NS100 / 160
NS250
NS400 / 630
Raccordement
Connections
AV ou AR
Front or Rear
AV ou AR
Front or Rear
AV ou AR
Front or Rear
possibilités
possibilities
oui
yes
oui
yes
oui
yes
Compact NS raccordé au jeu de Barres Vertical à droite
Compact NS connected to the vertical bars on the right
Type D & Mf
Type D & Mf
NS100 / 160
NS250
NS400 / 630
Guide Technique V9 / V9 Technical Guide
Raccordement
Connections
AV ou AR
Front or Rear
AV ou AR
Front or Rear
possibilités
possibilities
oui (par câbles)
yes (by cables)
oui (en retournant la platine et la porte) si:
- commande maneton et électrique à travers porte
- toutes commandes derrière porte
- commande rotative direct
- commande rotative prolongé Dans tous les cas,
il faut développer les barres
yes (while returning the turntable and the door) if:
- manual and electric command through door
- all controls behind door
- direct rotary command
- prolonged rotary command in any case, it is
necessary to develop bars
59
Installation de l’appareillage
Switchgear Installation
Règles d’installation Compact NS dans
BLOKSET
Rules Compact NS installation in
BLOKSET
U < 500V
Type D
D type
Raccordement
Connection
Type
Type
NS80
AV
câbles
cables
NS100/160/250
GV7
AV
câbles
cables
NS100/160/250
GV7
AR
câbles
cables
NS400/630 N, H
AV
barres
bars
NS400/630 N, H
AV
barres
bars
CBL/SP
LTS/PB
NS400/630 L
AV
barres
bars
CBL/SP
LTS/PB
NS400/630 N, H, L
AR
barres
bars
CBC
STS
accessoire pour protection des personnes
accessory needed for people protection
Type Mf et Ms
Mf and Ms type
Raccordement
Connection
Type
Type
Accessoires
Accessories
Mode de raccordement
Connection way
GV2
Integral
AV
câbles
cables
direct dans bornes appareil
direct on CB’s
NS80
AV
câbles
cables
direct dans bornes appareil
direct on CB’s
NS100/160/250
GV7
AV
câbles
cables
bornes à cage (câbles 1.5 à 95 mm2) Ref. 29242 ou **
NS400 N, H
AR / AV
barres/
câbles
bars/cables
CBC AM
SEULEMENT
STS ONLY IN
Bornes 2 câbles ref. 32481 (barres amont, câbles aval)
add cable connectors for 2 cables reference 32481 (bars
IN, cables OU)
NS630 N, H
AR / AV
barres/
câbles
bars/cables
CBC AM
SEULEMENT
STS ONLY IN
barres amont, câbles aval
bars incoming, cables outgoing
NS400 L
AR / AV
barres/
câbles
bars/cables
CBC AM + SP AL
STS IN + PB OU
Bornes 2 câbles ref. 32481 (barres amont, câbles aval)
add cable connectors for 2 cables reference 32481 (bars
IN, cables OU)
NS630 L
AR / AV
barres/
câbles
bars/cables
CBC AM + SP AL
STS IN + PB OU
barres amont, câbles aval
accessory needed for people protection
Guide Technique V9 / V9 Technical Guide
Accessoires
Accessories
Mode de raccordement
Connection way
direct dans bornes appareil
direct on CB’s
bornes à cage (câbles 1.5 à 95 mm2) Ref. 29242 ou **
add-on bare cable connectors (cables 1.5 to 95 mm2)
ref. 29242 or **
CBC
STS
accessoire pour protection des personnes
accessory needed for people protection
barres isolées
with insulated bars
barres nues
with bare bars
add cable connectors (cables 1.5 à 95 mm2) up to 160 A
ref. 29242 or **
60
Installation de l’appareillage
Switchgear Installation
Type Mw
Mw type
Raccordement
Connection
Type
Type
Accessoires
Accessories
Mode de raccordement
Connection way
GV2
Integral
AV
câbles
cables
direct dans bornes appareil
direct on CB’s
NS80
AV
câbles
cables
direct dans bornes appareil
direct on CB’s
NS100/160/250
GV7
AV
1 câble
1 cable
bornes à cage (câbles 1.5 à 95 mm2) Ref. 29242 ou **
NS250
AV
2 câbles
2 cables
NS400 N, H
AV
câbles
cables
bornes 2 câbles référence 32481
add cable connectors for 2 cables reference 32481
NS630 N, H
AV
barres
bars
raccordement des 3 câbles 50 mm2 (pinces)
add cable connectors (cables 1.5 to 95 mm2) up to 160 A
ref. 29242 or **
CBL
cosses + séparateur de phase
lugs
bars + connection 3 cables 50 mm2 (plug)
NS400 L
AV
câbles
cables
CBL/SP
LTS/PB
bornes 2 câbles référence 32481 (modularité à
confirmer)
add cable connectors for 2 cables reference 32481 (to
confirm the modularity)
NS630 L
AV
barres
bars
SP
PB
raccordement des 3 câbles 50 mm2 (pinces)
AV = connexion avant du disjoncteur
CBC = cache borne court
SP = séparateur de phase
AL = Aval du disjoncteur
AR = connexion arrière du disjoncteur
CBL = cache borne long
AM = Amont du disjoncteur
Guide Technique V9 / V9 Technical Guide
bars + connection 3 cables 50 mm2 (plug)
AV = front connection on CB
STS = short terminal shield
PB = phase barrier
OU = Outgoing
AR = rear connection on CB
LTS = long terminal shield
IN = Incoming
61
Installation de l’appareillage
Switchgear Installation
500V ≤ U ≤ 600V
Type D
D type
Raccordement
Connection
Type
Type
NS80
AV
câbles
cables
NS100/160/250
GV7
AV
câbles
cables
CBC/SP
STS/PB
NS100/160/250
GV7
AR
câbles
cables
CBC
STS
accessoire pour protection des personnes
accessory needed for people protection
NS400/630 N, H
AV
barres
bars
CBL/SP
LTS/PB
barres nues ou isolées
bar or insulated bars
NS400/630 L
AV
barres
bars
CBL/SP
LTS/PB
barres nues ou isolées
bar or insulated bars
NS400/630 N, H, L
AR
barres
bars
CBC
STS
accessoire pour protection des personnes
accessory needed for people protection
Type Mf et Ms
Mf and Ms type
Raccordement
Connection
Type
Type
Accessoires
Accessories
Mode de raccordement
Connection way
GV2/Integral
AV
câbles
cables
direct dans bornes appareil
direct on CB’s
NS80
AV
câbles
cables
direct dans bornes appareil
direct on CB’s
NS100/160/250
GV7
AV
câbles
cables
CBC
STS
NS400 N, H
AR / AV
barres/
câbles
bars/cables
CBC AM
SEULEMENT
STS ONLY IN
Bornes 2 câbles ref. 32481 (barres amont, câbles aval)
add cable connectors for 2 cables reference 32481 (bars
IN, cables OU)
NS630 N, H
AR / AV
barres/
câbles
bars/cables
CBC AM
SEULEMENT
STS ONLY IN
barres amont, câbles aval
bars incoming, cables outgoing
NS400 L
AR / AV
barres/
câbles
bars/cables
CBC AM + SP AL
STS IN + PB OU
Bornes 2 câbles ref. 32481 (barres amont, câbles aval)
add cable connectors for 2 cables reference 32481 (bars
IN, cables OU)
NS630 L
AR / AV
barres/
câbles
bars/cables
CBC AM + SP AL
STS IN + PB OU
barres amont, câbles aval
bars incoming, cables outgoing
Guide Technique V9 / V9 Technical Guide
Accessoires
Accessories
Mode de raccordement
Connection way
direct dans bornes appareil
direct on CB’s
bornes à cage (câbles 1.5 à 95 mm2) Ref. 29242 ou **
add-on bar cable connectors (cables 1.5 to 95 mm2) up
to 160 A ref. 29242 or **
bornes à cage (câbles 1.5 à 95 mm2) Ref. 29242 ou **
add cable connectors (cables 1.5 to 95 mm2) ref. 29242
or **
62
Installation de l’appareillage
Switchgear Installation
Type Mw
Mw type
Raccordement
Connection
Type
Type
Accessoires
Accessories
Mode de raccordement
Connection way
GV2/Integral
AV
câbles
cables
direct dans bornes appareil
direct on CB’s
NS80
AV
câbles
cables
direct dans bornes appareil
direct on CB’s
NS100/160/250
GV7
AV
1 câble
1 cable
CBC
STS
NS250
AV
2 câbles
2 cables
CBL
LTS
cosses + séparateur de phase
lugs
NS400 N, H
AV
câbles
cables
CBL/SP
LTS/PB
bornes 2 câbles référence 32481 (modularité à
confirmer)
add cable connectors for 2 cables reference 32481 (to
confirm the modularity)
NS630 N, H
AV
barres
bars
SP
PB
raccordement des 3 câbles 50 mm2 (pinces)
bornes à cage (câbles 1.5 à 95 mm2) Ref. 29242 ou **
add cable connectors (cables 1.5 to 95 mm2)
ref. 29242 up to 160 A or **
insulating bars + connection 3 cables 50 mm2 (plug)
NS400 L
AV
câbles
cables
CBL/SP
LTS/PB
bornes 2 câbles référence 32481 (modularité à
confirmer)
add cable connectors for 2 cables reference 32481 (to
confirm the modularity)
NS630 L
AV
barres
bars
SP
PB
raccordement des 3 câbles 50 mm2 (pinces)
AV = connexion avant du disjoncteur
CBC = cache borne court
SP = séparateur de phase
AL = Aval du disjoncteur
AR = connexion arrière du disjoncteur
CBL = cache borne long
AM = Amont du disjoncteur
Guide Technique V9 / V9 Technical Guide
insulating bars + connection 3 cables 50 mm2 (plug)
AV: front connection on CB
STS = short terminal shield
PB = phase barrierOU = Outgoing
AR: rear connection on CB
LTS = long terminal shield
IN = Incoming
63
Installation de l’appareillage
Switchgear Installation
U > 600V
Type D
D type
Raccordement
Connection
Type
Type
Accessoires
Accessories
Mode de raccordement
Connection way
NS80
AV
câbles
cables
CBL
LTS
direct dans bornes appareil
direct on CB’s
NS100/160/250
GV7
AR
câbles
cables
CBC
STS
NS100/160/250
GV7
AV
câbles
cables
kit
kit
NS400/630
AR
barres
bars
CBC
STS
NS400/630
AV
barres
bars
kit
kit
kit d’isolement renforcé*
reinforced insulating kit *
Type Mf et Ms
Mf and Ms type
Raccordement
Connection
Type
Type
Accessoires
Accessories
Mode de raccordement
Connection way
GV2
Integral
AV
câbles
cables
NS80
AV
câbles
cables
CBL
LTS
direct dans bornes appareil (modularité à confirmer)
direct on CB’s (to confirm the modularity)
NS100/160/250
GV7
AV
câbles
cables
kit
kit
étude à commission, vérifier la modularité
special studied, to confirm the modularity
NS400/630 N, H, L
AR / AV
barres/
câbles
bars/cables
CBC AM + kit AL
STS IN + kit OU
kit d’isolation renforcé* barres amont, câbles aval
(modularité à confirmer)
Bars IN, cables OU (to confirm the modularity)
Guide Technique V9 / V9 Technical Guide
kit d’isolement renforcé*
reinforced insulating kit *
direct dans bornes appareil
direct on CB’s
64
Installation de l’appareillage
Switchgear Installation
Type Mw
Mw type
Raccordement
Connection
Type
Type
Accessoires
Accessories
Mode de raccordement
Connection way
GV2
Integral
AV
câbles
cables
NS80
AV
câbles
cables
CBL
LTS
direct dans bornes appareil
direct on CB’s
NS100/160/250
GV7
AV
1 câble
1 cable
kit
kit
bornes à cages (câbles 1.5 à 95 mm2) Ref. 29242 ou **
+ kit d’isolement renforcé* (modularité à confirmer)
direct dans bornes appareil
direct on CB’s
add cable connectors (cables 1.5 to 95 mm2) up to 160 A
ref. 29242 or **
+ reinforced insulating kit * (to confirm the modularity)
NS250
AV
2 câbles
2 cables
kit
kit
câbles avec cosses + kit d’isolement renforcé
(modularité à confirmer)
same for 1 cable + lugs (to confirm modularity)
NS400
AV
câbles
cables
kit
kit
bornes à cages pour 2 câbles Ref. 32481
+ kit d’isolement renforcé * (modularité à confirmer)
add cable connectors for 2 cables ref. 32481
+ reinforced insulating kit * (to confirm the modularity)
NS630
AV
barres
bars
kit
kit
raccordement 3 câbles 50 mm2 (pinces)
+ kit d’isolement renforcé* (modularité à confirmer)
bars + connection 3 cables 50 mm2 (plug)
+ reinforced insulating kit * (to confirm the modularity)
AV = connexion avant du disjoncteur
CBC = cache borne court
AR = connexion arrière du disjoncteur
CBL = cache borne long
AM = Amont du disjoncteur
AL = Aval du disjoncteur
AV = front connection on CB
STS = short terminal shield
AR = rear connection on CB
LTS = long terminal shield
IN = Incoming connection on CB
OU = Outgoing connection on CB
* kit d’isolement
NS100/250
tri
29326
tetra
29327
* reinforced insulating kit
NS100/250
3 phases
29326
4 phases
29327
NS400/630
32580
32581
NS400/630
32580
32581
* * pour les courants plus de 160 A jusqu'à
250 A, utiliser le ref. 29259 avec câbles
jusqu'à 185 mm2.
** for currents over 160 A up to 250 A, use
ref. 29259 with cables up to 185 mm2.
Voir plans: 51130483 / 51130484 /
51130485 / 51130486
See drawings: 51130483 / 51130484 /
51130485 / 51130486
Guide Technique V9 / V9 Technical Guide
65
Installation de l’appareillage
Switchgear Installation
3.1.2.3.b.
3.1.2.3.b.1.
Compact NS630b à NS1600
Compact NS630b to NS1600
Fixe Arrivée par le BAS/HAUT (à travers portes)
Commande rotative directe / commande maneton / commande électrique. Forme 1 à 4
Fixed Incoming from the TOP/BOTTON (through door)
Direct rotary handle / toggle / motor mechanism. Form 1 to 4
Disjoncteur
Option
Raccordement
client
Client
connection
Taille
en Modules
Number of
Modules
Circuit Breaker
Option
AR
Rear
AR
Rear
AV
Front
AR
Rear
AR
Rear
AR
Rear
AV
Front
AR
Rear
AV
Front
AR
Rear
AV
Front
AR
Rear
AV
Front
AR
Rear
AV/AR
Front/Rear
AV/AR
Front/Rear
AV
Front
AR
Rear
AV/AR
Front/Rear
AV
Front
9 (F1, 2, 3)
3 + 9 (F4) (1)
9 (F1, 2, 3)
3 + 9 (F4) (1)
9+3
(1)
9+3
(1)
9 (F1, 2, 3)
9 + 3 (F4) (1)
9 (F1, 2, 3)
9 + 3 (F4) (1)
9+3
(1)
9+3
(1)
9 (F1, 2, 3)
9 + 3 (F4)
9 (F1, 2, 3)
9 + 3 (F4)
9+3
4b + 7
4b + 10
N°
1+6
1+7
1+8
1 + 10
2+6
2+7
2+8
2+9
3a + 6
3a + 7
3a + 8
NS630b/800/1000/1250/1600
3a + 9
3b + 6
3b + 7
3b + 8
3b + 10
4a + 6
4a + 7
4a + 9
4b + 6
Guide Technique V9 / V9 Technical Guide
Raccordement
jeu de barres
Bars connection
Horizontal
Inférieure
Lower
Inférieure
Lower
Inférieure
Lower
Inférieure
Lower
Supérieur
Upper
Supérieur
Upper
Supérieur
Upper
Supérieur
Upper
Dimension
Ossature
Framework
dimension
Vertical
Profondeur
Depth
600
700
700
x
700/200
x
700
x
700
x
700
x
700/200
x
700
x
PG
200/700
PG
200/700
x
PG
200/700/200
x
9+3
PG
200/700
x
9 + 3 (F1, 2, 3)
3 + 9 + 3 (F4)
9 + 3 (F1, 2, 3)
3 + 9 + 3 (F4)
3+9+3
PG
200/700
PG
200/700
x
PGinf.
PGLower poles
PGinf.
PGLower poles
PD
200/700/200
x
200/700
x
700
PD
700
x
PD
700
x
9 + 3 (F1, 2, 3)
3 + 9 + 3 (F4)
PDinf.
PDLower poles
700
AR
Rear
9 + 3 (F1, 2, 3)
3 + 9 + 3 (F4)
PDinf.
PDLower poles
700
x
AV/AR
Front/Rear
3+9+3
PDinf.
PDLower poles
700
x
3+9+3
9 + 3 (F1, 2, 3)
3 + 9 + 3 (F4)
9 + 3 (F1, 2, 3)
3 + 9 + 3 (F4)
3+9+3
1000
x
x
x
x
x
66
Installation de l’appareillage
Switchgear Installation
(1) Rappeler qu’il faut prévoir une porte 4
modules pour JdB horizontal simple ou 8
modules pour JdB horizontal double.
(1) To remember that it is necessary to
forecast 4 modules door for simple horizontal
busbar or 8 modules door for double
horizontal busbar.
Obligatoires pour l’installation des
Compact NS:
Compulsory with the installation of the
Compact NS:
„ A travers porte
„ Through door
„ Fixe:
‰ IP <= 31appareil avec commande
manuelle sans cadre , IP <= 31 appareil
avec commande manuelle ou commande électrique cadre de porte
ref.33718 .
‰ IP42/54 appareil avec commande
manuelle ou commande électrique avec
cadre de porte ref.33857 + capot
transparent ref.33859
‰ plages de chant
„ Fixed:
‰ IP <= 31device with toggle without
escutcheon , IP <= 31 device with toggle
or electrically operated escutcheon
ref.33718 .
Guide Technique V9 / V9 Technical Guide
‰ IP42/54 with toggle or electrically
operated escutcheon ref.33857 +
transparent cover ref.33859;
‰ edgewise bars
67
Installation de l’appareillage
Switchgear Installation
3.1.2.3.b.2.
Débro Arrivée par le BAS/HAUT (à travers portes)
Commande rotative directe / commande maneton/ commande électrique. Form 1 à 4
Drawout Incoming from the TOP/BOTTON (through door)
Direct rotary handle / toggle / motor mechanism. Form 1 to 4
Disjoncteur
Option
Circuit Breaker
Option
N°
1+6
1+7
1+8
1 + 10
2+6
2+7
2+8
2+9
3a + 6
3a + 7
3a + 8
NS630b/800/1000/1250/1600
3a + 9
3b + 6
3b + 7
3b + 8
3b + 10
4a + 6
4a + 7
4a + 9
4b + 6
4b + 7
4b + 10
Guide Technique V9 / V9 Technical Guide
Raccordement
client
Client
connection
Taille
en Modules
Number of
Modules
AR
Rear
AR
Rear
AV
Front
AR
Rear
AR
Rear
AR
Rear
AV
Front
AR
Rear
AV
Front
AR
Rear
AV
Front
AR
Rear
AV
Front
AR
Rear
AV/AR
Front/Rear
AV/AR
Front/Rear
AV
Front
AR
Rear
AV/AR
Front/Rear
AV
Front
AR
Rear
AV/AR
Front/Rear
9 (F1, 2, 3)
3 + 9 (F4) (1)
9 (F1, 2, 3)
3 + 9 (F4) (1)
9+3
(1)
9+3
(1)
9 (F1, 2, 3)
9 + 3 (F4) (1)
9 (F1, 2, 3)
9 + 3 (F4) (1)
9+3
(1)
9+3
(1)
9 (F1, 2, 3)
9 + 3 (F4)
9 (F1, 2, 3)
9 + 3 (F4)
9+3
Raccordement
jeu de barres
Bars connection
Horizontal
Inférieure
Lower
Inférieure
Lower
Inférieure
Lower
Inférieure
Lower
Supérieur
Upper
Supérieur
Upper
Supérieur
Upper
Supérieur
Upper
Dimension
Ossature
Framework
dimension
Vertical
Profondeur
Depth
600
700
700
x
700/200
x
700
x
700
x
700
x
700/200
x
700
x
PG
200/700
PG
200/700
x
PG
200/700/200
x
9+3
PG
200/700
x
9 + 3 (F1, 2, 3)
3 + 9 + 3 (F4)
9 + 3 (F1, 2, 3)
3 + 9 + 3 (F4)
3+9+3
PG
200/700
PG
200/700
x
PGinf.
PGLower poles
PGinf.
PGLower poles
PD
200/700/200
x
200/700
x
700
PD
700
x
PD
700
x
PDinf.
PDLower poles
PDinf.
PDLower poles
PDinf.
PDLower poles
700
3+9+3
9 + 3 (F1, 2, 3)
3 + 9 + 3 (F4)
9 + 3 (F1, 2, 3)
3 + 9 + 3 (F4)
3+9+3
9 + 3 (F1, 2, 3)
3 + 9 + 3 (F4)
9 + 3 (F1, 2, 3)
3 + 9 + 3 (F4)
3+9+3
1000
x
x
x
x
x
700
x
700
x
68
Installation de l’appareillage
Switchgear Installation
(1) Rappeler qu’il faut prévoir une porte 4
modules pour JdB horizontal simple ou 8
modules pour JdB horizontal double.
(1) remember that it is necessary to forecast
4 modules door for simple horizontal busbar
or 8 modules door for double horizontal
busbar.
Obligatoires pour l’installation des
Compact NS:
Compulsory with the installation of the
Compact NS:
„ A travers porte
„ Through door
„ Débrochable:
‰ IP <= 31cadre de porte ref. 33857 .
‰ IP 42/54 cadre de porte ref. 33857 avec
capot transparent ref. 33859 .
‰ volet isolant.
‰ plages de chant
„ Withdrawable:
‰ IP <= 31 door frame ref. 33857
‰ IP 42/54 door frame ref. 33857 with
transparent cover ref. 33859 ,
‰ safety shutters.
‰ edgewise bars
Guide Technique V9 / V9 Technical Guide
69
Installation de l’appareillage
Switchgear Installation
3.1.2.3.b.3.
Fixe Arrivée par le BAS/HAUT (derrière porte)
Commande rotative prolongée / commande rotative directe. Forme 1 à 4
Fixed Incoming from the TOP/BOTTON (behind door)
Extended rotary handle / direct rotary handle. Form 1 to 4
Disjoncteur
Option
Raccordement
client
Client
connection
Taille
en Modules
Number of
Modules
Circuit Breaker
Option
AR
Rear
9 (F1, 2, 3)
3 + 9 (F4) (1)
Inférieure
Lower
700
1+7
AR
Rear
9 (F1, 2, 3)
3 + 9 (F4) (1)
Inférieure
Lower
700
x
1+8
AV
Front
9+3
(1)
Inférieure
Lower
700/200
x
1 + 10
AR
Rear
9+3
(1)
Inférieure
Lower
700
x
2+6
AR
Rear
9 (F1, 2, 3)
9 + 3 (F4) (1)
Supérieur
Upper
700
2+7
AR
Rear
9 (F1, 2, 3)
9 + 3 (F4) (1)
Supérieur
Upper
700
x
2+8
AV
Front
9+3
(1)
Supérieur
Upper
700/200
x
2+9
AR
Rear
9+3
(1)
Supérieur
Upper
700
x
3a + 6
AV
Front
9 (F1, 2, 3)
9 + 3 (F4)
PG
200/700
3a + 7
AR
Rear
9 (F1, 2, 3)
9 + 3 (F4)
PG
200/700
x
3a + 8
AV
Front
9+3
PG
200/700/200
x
3a + 9
AR
Rear
9+3
PG
200/700
x
3b + 6
AV
Front
9 + 3 (F1, 2, 3)
3 + 9 + 3 (F4)
PG
200/700
3b + 7
AR
Rear
9 + 3 (F1, 2, 3)
3 + 9 + 3 (F4)
PG
200/700
x
3b + 8
AV/AR
Front/Rear
3+9+3
PGinf.
PGLower poles
200/700/200
x
3b + 10
AV/AR
Front/Rear
3+9+3
200/700
x
4a + 6
AV
Front
3 + 9 (F1, 2, 3)
3 + 9 + 3 (F4)
PGinf.
PGLower poles
PD
700
4a + 7
AR
Rear
3 + 9 (F1, 2, 3)
3 + 9 + 3 (F4)
PD
700
x
4a + 9
AV/AR
Front/Rear
3+9+3
PD
700
x
4b + 6
AV
Front
9 + 3 (F1, 2, 3)
3 + 9 + 3 (F4)
PDinf.
PDLower poles
700
4b + 7
AR
Rear
9 + 3 (F1, 2, 3)
3 + 9 + 3 (F4)
PDinf.
PDLower poles
700
x
4b + 10
AV/AR
Front/Rear
3+9+3
PDinf.
PDLower poles
700
x
N°
1+6
NS630b/800/1000/1250/1600
Guide Technique V9 / V9 Technical Guide
Raccordement
jeu de barres
Bars connection
Horizontal
Dimension
Ossature
Framework
dimension
Vertical
Profondeur
Depth
600
1000
x
x
x
x
x
x
70
Installation de l’appareillage
Switchgear Installation
(1) Rappeler qu’il faut prévoir une porte 4
modules pour JdB horizontal simple ou 8
modules pour JdB horizontal double.
(1) To remember that it is necessary to
forecast 4 modules door for simple horizontal
busbar or 8 modules door for double
horizontal busbar.
Obligatoires pour l’installation des
Compact NS:
Compulsory with the installation of the
Compact NS:
„ Derrière porte
‰ Fixe:
– plages de chant
„ Behind door
‰ Fixed:
– edgewise bars
Guide Technique V9 / V9 Technical Guide
71
Installation de l’appareillage
Switchgear Installation
3.1.2.3.b.4.
Débro Arrivée par le BAS/HAUT (derrière porte)
Commande rotative prolongée / commande rotative directe. Forme 1 à 4
Drawout Incoming from the TOP/BOTTON (behind door)
Extended rotary handle / direct rotary handle. Form 1 to 4
Disjoncteur
Option
Circuit Breaker
Option
N°
1+6
1+8
1 + 10
2+6
2+8
2+9
3a + 6
3a + 8
NS630b/800/1000/1250/1600
3a + 9
3b + 6
3b + 8
3b + 10
4a + 6
4a + 7
4a + 9
4b + 6
4b + 10
Guide Technique V9 / V9 Technical Guide
Raccordement
client
Client
connection
Taille
en Modules
Number of
Modules
AR
Rear
9 + 3 (F1, 2, 3)
3 + 9 + 3 (F4)
(1)
3+9+3
(1)
3+9+3
(1)
9 (F1, 2, 3)
9 + 3 (1)
9+3
(1)
9 + 3 (F1, 2, 3)
3 + 9 + 3 (F4)
3 + 9 (F1, 2, 3)
3 + 9 + 3 (F4)
3+9+3
AV
Front
AR
Rear
AR
Rear
AV
Front
AR
Rear
AV
Front
AV
Front
AR
Rear
AV
Front
AV/AR
Front/Rear
AV/AR
Front/Rear
AV
Front
AR
Rear
AV/AR
Front/Rear
AV
Front
AV/AR
Front/Rear
Raccordement
jeu de barres
Bars connection
Horizontal
Inférieure
Lower
Dimension
Ossature
Framework
dimension
Vertical
Profondeur
Depth
600
700
Inférieure
Lower
Inférieure
Lower
Supérieur
Upper
Supérieur
Upper
Supérieur
Upper
700/200
x
700
x
1000
x
700
x
700/200
x
700
x
PG
200/700
x
PG
200/700/200
x
3+9+3
PG
200/700
x
9 + 3 (F1, 2, 3)
3 + 9 + 3 (F4)
3+9+3
PG
200/700
PGinf.
PGLower poles
PGinf.
PGLower poles
PD
200/700/200
x
200/700
x
700
PD
700
x
PD
700
x
PDinf.
PDLower poles
PDinf.
PDLower poles
700
3+9+3
3 + 9 (F1, 2, 3)
3 + 9 + 3 (F4)
3 + 9 (F1, 2, 3)
3 + 9 + 3 (F4)
3+9+3
9 + 3 (F1, 2, 3)
3 + 9 + 3 (F4)
3+9+3
700
x
x
x
x
72
Installation de l’appareillage
Switchgear Installation
(1) Rappeler qu’il faut prévoir une porte 4
modules pour JdB horizontal simple ou 8
modules pour JdB horizontal double.
(1) To remember that it is necessary to
forecast 4 modules door for simple horizontal
busbar or 8 modules door for double
horizontal busbar.
Obligatoires pour l’installation des
Compact NS:
Compulsory with the installation of the
Compact NS:
„ Derrière porte
‰ Débrochable:
– volet isolant.
– plages de chant
„ Behind door
‰ Withdrawable:
– safety shutters.
– edgewise bars
Guide Technique V9 / V9 Technical Guide
73
Installation de l’appareillage
Switchgear Installation
3.1.2.3.c.
Compact NS1600b à NS3200
Compact NS1600b to NS3200
3.1.2.3.c.1.
Fixe Arrivée par le BAS (à travers portes)
Commande rotative directe / commande maneton / commande électrice
Fixed Incoming from the BOTTON (throught door)
Direct rotatory handle / toggle / motor mechanism
Disjoncteur
Option
Circuit Breaker
Option
NS1600b/2000/2500
N°
3a + 9
NS3200
(1)
2+9
Raccordement
client
Client
connection
Taille
en Modules
Number of
Modules
AR
Rear
AR
Rear
10 + 4
Raccordement
jeu de barres (2)
Bars connection (2)
Horizontal
10 + 4
(3)
Supérieur
Upper
Vertical
PG
Dimension
Ossature
Framework
dimension
Profondeur
Depth
200/700
600
x
700
x
1000
(1) seulement un par colone avec disjoncteur
an haut.
(2) Appareil racc. au JdB Horizontal
Supérieur, Vertical Gauche. Note: Formes
possible F1.
(3) Commander en plus porte 8 modules
pour JdB horizontal simple ou transfer.
(2) Device connected on upper horizontal
busbar, left vertical busbar. Note: Possible
forms F1.
(3) Order in addition 8 modules door to
cover simple horizontal/transfer busbar.
Obligatoires pour l’installation des
Compact NS:
Compulsory with the installation of the
Compact NS:
„ A travers porte
‰ Fixe:
– cadre de porte pour IP ≤ 31 ou cadre de
porte avec capot transparent pour
IP 42/54.
„ Through door
‰ Fixed:
– door frame for IP ≤ 31 or door frame with
transparent cover for IP 42/54;
Guide Technique V9 / V9 Technical Guide
(1) Just one by column on the top.
74
Installation de l’appareillage
Switchgear Installation
3.1.2.4.
Compact C
Choix des platines et types de commande pour appareils 3/4 pôles
Choice of mounting plates and type of operating mechanism for 3/4 pole circuit breakers
Type d’appareils
Nb
pôles
Type de
commande
Position
H/V
Connexion aux
jeux de barres
vertical / horizontal
Nb modules pour
connexion aux
jeux de barres
Nb
modules
Disjoncteur
Nb modules pour
connexion jeux de
barres du client
Nb modules
client aux
connexions
Forme
Fixation
Type
Nb
poles
Type of
operating
mechanism
Position
H/V
Bar connection
vertical / horizontal
Nb modules
for busbar
set connections
Nb modules
Circuit Breaker
Nb modules
customer
connection busbar
Customer
connection
access
Form
Fixing
C801 à / to C1251
3P
A/B/C
H
Vertical
-
6
-
Côté 400 / Side 400
1/2/3/4
Fixe / Fixed
C801 à / to C1251
4P
A/B/C
H
Vertical
-
9
-
Côté 400/ Side 400
1/2/3/4
Fixe / Fixed
C801 à / to C1251
3P
A/B
H
Vertical
-
6
-
Arrière / Rear
1/2/3
Fixe / Fixed
C801 à / to C1251
4P
B
H
Vertical
-
9
-
Arrière / Rear
1/2/3
Fixe / Fixed
C801 à / to C1251
3/4P
A/B/D
V
Horizontal
6
12
3
Côté 200 / Side 200
1
Fixe / Fixed
C801 à / to C1251
3/4P
A/B
V
Horizontal
6
12
-
Arrière / Rear
1
Fixe / Fixed
C801 à / to C1251
3/4P
B
V
Vertical
-
12
3
Fond / Bottom
1
Fixe / Fixed
C1251
3/4P
A
V
Vertical
4
12
3
Fond / Bottom
1
Fixe / Fixed
C801 à / to C1251
3/4P
A/B/D
V
Vertical
3
12
4
Fond / Bottom
1
Fixe / Fixed
C1251
3/4P
B
V
Vertical
4
12
-
Arrière / Rear
1
Fixe / Fixed
C801 à / to C1251
3/4P
A/B
V
Vertical / Horizontal
4
12
4
Fond / Bottom
1
Fixe / Fixed
C801 à / to C1251
3/4P
B
V
Vertical
3
12
-
Arrière / Rear
1
Fixe / Fixed
C801 à / to C1001
3/4P
A/B
V
Vertical
3
12
-
Arrière / Rear
1
Fixe / Fixed
C801 à / to C1001
3/4P
A/B
V
Vertical
3
12
-
Arrière / Rear
1
Fixe / Fixed
C1251
3/4P
A
V
Vertical
3
12
-
Arrière / Rear
1
Fixe / Fixed
C801 à / to C1251
3/4P
A/B
V
Horizontal
6
12
4
Côté 200 / Side 200
1/2/3/4
Châssis /
Withdrawable
C801 à / to C1251
3/4P
A/B
V
Horizontal
6
12
-
Arrière / Rear
1/2/3/4
Châssis /
Withdrawable
C801 à / to C1251
3/4P
A/B
V
Vertical
-
12
-
Arrière / Rear
1/2/3/4
Châssis /
Withdrawable
C801 à / to C1251
3/4P
B
V
Vertical
-
12
6
Fond / Bottom
1/2/3/4
Châssis /
Withdrawable
Guide Technique V9 / V9 Technical Guide
75
Installation de l’appareillage
Switchgear Installation
Type de commande
Type of operating mechanism
A
derrière porte
behind door
maneton / rotative directe / électrique
toggle / direct rotary handle / motor mechanism
B
à travers porte
through door
maneton / rotative directe / électrique*
toggle / direct rotary handle / motor mechanism*
C
derrière porte individuelle
behind individual door
commande rotative prolongée
extended rotary handle
D
à travers plastron
through front plate
maneton
toggle
*: Uniquent maneton pour débrochable sur
châssis
*: Only toggle for withdrawable assembly
Acessoires obligatoires pour
l’installation des Compact C fixes:
„ Plages de chant ou à plat suivant la
configuration.
„ Caches bornes courts.
Compulsory accessories with installation
of fixed Compact C:
„ Edgewise or flat bars according to the
configuration.
„ Short terminal shields.
Obligatoires pour l’installation des
Compact C débrochables:
„ Plages de chant ou à plat suivant la
configuration.
„ Cadre de porte pour châssis.
„ Volet isolant.
„ Caches bornes courts.
„ Obturateur fils fins IP 20.
Compulsory with installation of
withdrawable Compact C:
„ Edgewise or flat bars according to the
configuration.
„ Door frame for chassis.
„ Safety shutters.
„ Short terminal shields.
„ IP 20 fine wiring closing shutter.
Compact C raccordé au Jeu de Barres Vertical à droite
Compact C connected to the vertical bars on the right
Type
Type
C801 à C1251 NHL
C801 to C1251 NHL
Raccordement
Connections
AV ou AR
Front or Rear
possibilités
possibilities
pas
développé
not
developed
Compact C raccordé au Jeu de Barres Vertical à gauche
Compact C connected to the vertical bars on the left
Type
Type
C801 à C1251 NHL
C801 to C1251 NHL
Guide Technique V9 / V9 Technical Guide
Raccordement
Connections
AV ou AR
Front or Rear
possibilités
possibilities
oui
yes
76
Installation de l’appareillage
Switchgear Installation
3.1.2.5.
Compact CM
Les disjoncteurs Compact CM ne peuvent
être installés qu’en forme 1;
à travers porte, avec une porte individuelle.
„ Position: Verticale.
„ Fixation: Fixe.
„ Commande:
‰ maneton,
‰ électrique (télécommande).
„ Type d’appareil: CM1250 à CM3200.
„ Nb Modules: 12 + 4.
Guide Technique V9 / V9 Technical Guide
Compact CM can only be installed in form 1;
through the door, and with an individual door.
„ Position: Vertical.
„ Fixing: Fixed.
„ Operating mechanism:
‰ toggle,
‰ motor mechanism (remote control).
„ Type of circuit breaker: CM1250 to
CM3200.
„ Number of Modules: 12 + 4.
77
Installation de l’appareillage
Switchgear Installation
3.1.2.6.
Masterpact
3.1.2.6.a.
3.1.2.6.a.1.
Masterpact NT06 à NT10
Masterpact NT06 to NT10
Fixe/débro Arrivée par le BAS/HAUT (à travers portes). Forme 1 à 4.
Fixed/drawout Incoming from the TOP/BOTTON (through door). Form 1 to 4
Disjoncteur
Option
Circuit Breaker
Option
N°
1+6
1+7
1+8
1 + 10
2+6
2+7
2+8
2+9
3a + 6
3a + 7
3a + 8
NT06/08/10/12/16
3a + 9
3b + 6
3b + 7
3b + 8
3b + 10
4a + 6
4a + 7
4a + 9
4b + 6
4b + 7
4b + 10
Guide Technique V9 / V9 Technical Guide
Raccordement
client
Client
connection
Taille
en Modules
Number of
Modules
AR
Rear
AR
Rear
AV
Front
AR
Rear
AR
Rear
AR
Rear
AV
Front
AR
Rear
AV
Front
AR
Rear
AV
Front
AR
Rear
AV
Front
AR
Rear
AV/AR
Front/Rear
AV/AR
Front/Rear
AV
Front
AR
Rear
AV/AR
Front/Rear
AV
Front
AR
Rear
AV/AR
Front/Rear
9 (F1, 2, 3)
3 + 9 (F4) (1)
9
(1)
9+3
(1)
9+3
(1)
9 (F1, 2, 3)
9 + 3 (F4) (1)
9 (F1, 2, 3)
9 + 3 (F4) (1)
9+3
(1)
9+3
(1)
9 (F1, 2, 3)
9 + 3 (F4)
9 (F1, 2, 3)
9 + 3 (F4)
9+3
Raccordement
jeu de barres
Bars connection
Horizontal
Inférieure
Lower
Inférieure
Lower
Inférieure
Lower
Inférieure
Lower
Supérieur
Upper
Supérieur
Upper
Supérieur
Upper
Supérieur
Upper
Dimension
Ossature
Framework
dimension
Vertical
Profondeur
Depth
600
700
700
x
700/200
x
700
x
700
x
700
x
700/200
x
700
x
PG
200/700
PG
200/700
x
PG
200/700/200
x
9+3
PG
200/700
x
9 + 3 (F1, 2, 3)
3 + 9 + 3 (F4)
9 + 3 (F1, 2, 3)
3 + 9 + 3 (F4)
3+9+3
PG
200/700
PG
200/700
x
PGinf.
PGLower poles
PGinf.
PGLower poles
PD
200/700/200
x
200/700
x
700
PD
700
x
PD
700
x
PDinf.
PDLower poles
PDinf.
PDLower poles
PDinf.
PDLower poles
700
3+9+3
3 + 9 (F1,2, 3)
3 + 9 + 3 (F4)
3 + 9 (F1,2, 3)
3 + 9 + 3 (F4)
3+9+3
9 + 3 (F1, 2, 3)
3 + 9 + 3 (F4)
9 + 3 (F1, 2, 3)
3 + 9 + 3 (F4)
3+9+3
1000
x
x
x
x
x
700
x
700
x
78
Installation de l’appareillage
Switchgear Installation
(1) Rappeler qu’il faut prévoir une porte 4
modules pour JdB horizontal simple ou 8
modules pour JdB horizontal double.
(1) Remember that it is necessary to forecast
4 modules door for simple horizontal busbar
or 8 modules door for double horizontal
busbar.
Obligatoires pour l’installation des
Compact NT:
Compulsory with the installation of the
Compact NT:
„ A travers porte
„ Through door
„ Fixe:
‰ IP <= 31appareil avec commande
manuelle sans cadre , IP <= 31 appareil
avec commande manuelle ou commande électrique cadre de porte
ref.33718 .
‰ IP42/54 appareil avec commande
manuelle ou commande électrique avec
cadre de porte ref.33857 + capot
transparent ref.33859
‰ plages de chant
„ Fixed:
‰ IP <= 31device with toggle without
escutcheon , IP <= 31 device with toggle
or electrically operated escutcheon
ref.33718 .
„ Débrochable:
‰ IP <= 31cadre de porte ref. 33857 .
‰ IP 42/54 cadre de porte ref. 33857 avec
capot transparent ref. 33859.
‰ volet isolant.
‰ plages de chant
„ Withdrawable:
‰ IP <= 31 door frame ref. 33857
‰ IP 42/54 door frame ref. 33857 with
transparent cover ref. 33859.
‰ safety shutters.
‰ edgewise bars
Guide Technique V9 / V9 Technical Guide
‰ IP42/54 with toggle or electrically
operated escutcheon ref.33857 +
transparent cover ref.33859;
‰ edgewise bars
79
Installation de l’appareillage
Switchgear Installation
3.1.2.6.b.
3.1.2.6.b.1.
Masterpact NW08 à NW40
Masterpact NW08 to NW40
Fixe/débrochable Arrivée par le BAS/HAUT. Forme 1 à 4.
Fixed/drawout Incoming from the TOP/BOTTON. Form 1 to 4.
Disjoncteur
Option
Raccordement
client
Client
connection
Taille
en Modules
Number of
Modules
Circuit Breaker
Option
1+6
AR
Rear
12
(1)
Inférieure
Lower
700
1+7
AR
Rear
12
(1)
Inférieure
Lower
700
x
1+8
AV/AR
Front/Rear
4 + 12
(1)
Inférieure
Lower
700/200
x
1 + 10
AV/AR
Front/Rear
4 + 12
(1)
Inférieure
Lower
700
x
2+6
AR
Rear
12
(1)
Supérieur
Upper
700
2+7
AR
Rear
12
(1)
Supérieur
Upper
700
x
2+8
AV/AR
Front/Rear
12 + 4
(1)
Supérieur
Upper
700/200
x
2+9
AV/AR
Front/Rear
12 + 4
(1)
Supérieur
Upper
700
x
3a + 6
AR
Rear
12
PG
200/700
3a + 7
AR
Rear
12
PG
200/700
x
3a + 8
AV/AR
Front/Rear
12 + 4
PG
200/700/200
x
3a + 9
AV/AR
Front/Rear
12 + 4
PG
200/700
x
3b + 6
AR
Rear
12 + 4
PGinf.
PGLower poles
200/700
3b + 7
AR
Rear
12 + 4
PGinf.
PGLower poles
200/700
x
3b + 8
AV/AR
Front/Rear
4 + 12 + 4
PGinf.
PGLower poles
200/700/200
x
3b + 10
AV/AR
Front/Rear
4 + 12 + 4
PGinf.
PGLower poles
200/700
x
4a + 6
AR
Rear
4 +12
PD
700
4a + 7
AR
Rear
4 +12
PD
700
x
4a + 9
AV/AR
Front/Rear
4 + 12 + 4
PD
700
x
4b + 6
AR
Rear
12 + 4
PDinf.
PDLower poles
700
x
4b + 7
AR
Rear
12 + 4
PDinf.
PDLower poles
700
x
4b + 10
AV/AR
Front/Rear
4 + 12 + 4
PDinf.
PDLower poles
700
x
1+6
AR
Rear
12
(1)
Inférieure
Lower
700
1+8
AV/AR
Front/Rear
4 + 12
(1)
Inférieure
Lower
700/200
N°
NW08/10/12/16
NW20
Guide Technique V9 / V9 Technical Guide
Raccordement
jeu de barres
Bars connection
Horizontal
Dimension
Ossature
Framework
dimension
Vertical
Profondeur
Depth
600
1000
x
X
x
x
x
x
x
80
Installation de l’appareillage
Switchgear Installation
Disjoncteur
Option
Circuit Breaker
Option
Raccordement
client
Client
connection
Taille
en Modules
Number of
Modules
N°
NW20
NW25
Raccordement
jeu de barres
Bars connection
Horizontal
Dimension
Ossature
Framework
dimension
Vertical
Profondeur
Depth
600
1 + 10
AV/AR
Front/Rear
4 + 12
(1)
Inférieure
Lower
700
2+6
AR
Rear
12
(1)
Supérieur
Upper
700
2+8
AV/AR
Front/Rear
12 + 4
(1)
Supérieur
Upper
700/200
x
2+9
AV/AR
Front/Rear
12 + 4
(1)
Supérieur
Upper
700
x
3a + 6
AR
Rear
12
PG
200/700
3a + 8
AV/AR
Front/Rear
12 + 4
PG
200/700/200
x
3a + 9
AV/AR
Front/Rear
12 + 4
PG
200/700
x
3b + 6
AR
Rear
12 + 4
PGinf.
PGLower poles
200/700
3b + 8
AV/AR
Front/Rear
4 + 12 + 4
PGinf.
PGLower poles
200/700/200
x
3b + 10
AV/AR
Front/Rear
4 + 12 + 4
PGinf.
PGLower poles
200/700
x
4a + 6
AR
Rear
4 +12
PD
700
4a + 9
AV/AR
Front/Rear
4 + 12 + 4
PD
700
4b + 6
AR
Rear
12 + 4
PDinf.
PDLower poles
700
4b + 10
AV/AR
Front/Rear
4 + 12 + 4
PDinf.
PDLower poles
700
1+6
AR
Rear
12
(1)
Inférieure
Lower
700
1+8
AV/AR
Front/Rear
4 + 12
(1)
Inférieure
Lower
700/200
x
1 + 10
AV/AR
Front/Rear
4 + 12
(1)
Inférieure
Lower
700
x
2+6
AR
Rear
12
(1)
Supérieur
Upper
700
2+8
AV/AR
Front/Rear
12 + 4
(1)
Supérieur
Upper
700/200
x
2+9
AV/AR
Front/Rear
12 + 4
(1)
Supérieur
Upper
700
x
3a + 6
AR
Rear
4 + 12
PG
200/700
3a + 8
AV/AR
Front/Rear
4 + 12 + 4
PG
200/700/200
x
3a + 9
AV/AR
Front/Rear
4 + 12 + 4
PG
200/700
x
3b + 6
AR
Rear
12 + 4
PGinf.
PGLower poles
200/700
3b + 8
AV/AR
Front/Rear
4 + 12 + 4
PGinf.
PGLower poles
200/700/200
x
3b + 10
AV/AR
Front/Rear
4 + 12 + 4
PGinf.
PGLower poles
200/700
x
4a + 6
AR
Rear
4 +12
PD
700
Guide Technique V9 / V9 Technical Guide
1000
x
X
x
x
x
x
x
x
x
X
x
x
x
81
Installation de l’appareillage
Switchgear Installation
Disjoncteur
Option
Circuit Breaker
Option
Raccordement
client
Client
connection
Taille
en Modules
Number of
Modules
N°
NW25
Horizontal
Dimension
Ossature
Framework
dimension
Vertical
Profondeur
Depth
600
4a + 9
AV/AR
Front/Rear
4 + 12 + 4
PD
700
x
4b + 6
AR
Rear
12 + 4
PDinf.
PDLower poles
700
x
4b + 10
AV/AR
Front/Rear
4 + 12 + 4
PDinf.
PDLower poles
700
x
1+8
AV/AR
Front/Rear
4 + 12 + 4
(1)
Inférieure
Lower
700/400
x
1 + 10
AV/AR
Front/Rear
4 + 12 + 4
(1)
Inférieure
Lower
700
x
2+8
AV/AR
Front/Rear
4 + 12 + 4
(1)
Supérieur
Upper
700/400
x
2+9
AV/AR
Front/Rear
4 + 12 + 4
(1)
Supérieur
Upper
700
x
3a + 8
AV/AR
Front/Rear
6 + 12 + 4
PG
200/700/400
x
3a + 9
AV/AR
Front/Rear
6 + 12 + 4
PG
700/200
x
3b + 8
AV/AR
Front/Rear
4 + 12 + 10
PGinf.
PGLower poles
200/700/400
x
3b + 10
AV/AR
Front/Rear
4 + 12 + 10
PGinf.
PGLower poles
200/700
x
4a + 9
AV/AR
Front/Rear
4 + 12 + 4
PD
700/200
X
4b + 10
AV/AR
Front/Rear
4 + 12 + 4
PDinf.
PDLower poles
700/200
X
1 + 10
AV/AR
Front/Rear
9 + 12
(1)
Inférieure
Lower
700
x
2+9
AV/AR
Front/Rear
11 + 12
(1)
Supérieur
Upper
700
x
NW32
NW40
Raccordement
jeu de barres
Bars connection
Guide Technique V9 / V9 Technical Guide
1000
82
Installation de l’appareillage
Switchgear Installation
(1) Rappeler qu’il faut prévoir une porte 4
modules pour JdB horizontal simple ou 8
modules pour JdB horizontal double.
(1) Remember that it is necessary to forecast
4 modules door for simple horizontal busbar
or 8 modules door for double horizontal
busbar.
Glossaire des Abréviations:
AR Raccordement arrière
AV
Raccordement avant
PG Jeu de barres Plate Gauche
PD Jeu de barres Plate Droite
Glossary des Abbreviations:
PG Left edgewise busbar
PD Right edgewise busbar
LG
Left Linergy busbar
LD
Right Linergy busbar
Obligatoires pour l’installation des
Masterpact:
Compulsory with the installation of the
Masterpacts:
„ Fixe:
‰ IP <= 31cadre de porte ref. 48601.
‰ IP 42/54 cadre de porte ref. 48603 et
capot transparent ref. 48604 avec obturateur de porte ref. 48605 .
„ Fixed:
‰ IP <= 31 door frame ref. 48601 .
‰ IP 42/54 door frame ref. 48603 and
transparent cover ref. 48604 with
escutcheon blanking plate ref. 48605 .
„ Débrochable:
‰ IP <= 31cadre de porte ref. 48603 .
‰ IP 42/54 cadre de porte ref. 48603 avec
capot transparent ref. 48604 .
‰ volet isolant.
‰ plages de chant
„ Withdrawable:
‰ IP <= 31 door frame ref. 48603 .
‰ IP 42/54 door frame ref. 48603 with
transparent cover ref. 48604 .
‰ safety shutters.
‰ edgewise bars
Guide Technique V9 / V9 Technical Guide
83
Installation de l’appareillage
Switchgear Installation
3.1.2.6.c.
3.1.2.6.c.1.
Masterpact NW40b à NW63
Masterpact NW40b to NW63
Débro Arrivée par le BAS/HAUT forme 1 à 4
Drawout Incoming from the TOP/BOTTON form 1 to 4
Disjoncteur
Option
Raccordement
client
Client connection
Taille
en Modules
Number of
Modules
Circuit Breaker
Option
2+9
AV/AR
Front/Rear
10+13+15
Supérieur (1)
Upper(2)
1200
x
1+10
AV/AR
Front/Rear
16+13+11
Inférieure (1)
Lower(2)
1200
x
2+9
AV/AR
Front/Rear
13+13+14
Supérieur (2)
Upper(3)
1200
x
1+10
AV/AR
Front/Rear
13+13+14
Inférieure (2)
Lower(3)
1200
x
2+9
AV/AR
Front/Rear
13+13+14
Supérieur (2)
Upper(3)
1200
x
1+10
AV/AR
Front/Rear
13+13+14
Inférieure (2)
Lower(3)
1200
x
N°
NW40b
NW50/63
Raccordement
jeu de barres
Bars connection
Horizontal
(1) Appareil racc. au JdB Simple Horizontal.
(2) Appareil racc. au JdB Double Horizontal.
Obligatoires pour l’installation des
Masterpact:
„ Débrochable:
‰ IP <= 31cadre de porte ref. 48603.
‰ IP 42/54 ou cadre de porte ref. 48603
avec capot transparent ref. 48604.
‰ volet isolant,
‰ plages de chant.
Guide Technique V9 / V9 Technical Guide
Dimension
Ossature
Framework
dimension
Vertical
Profondeur
Depth
600
(1) Device connected on Simple horizontal
busbar.
(2) Device connected on Double horizontal
busbar.
Compulsory with the installation of the
Masterpacts:
„ Withdrawable:
‰ IP <= 31 door frame ref. 48603 .
‰ IP 42/54 or door frame ref. 48603 with
transparent cover ref. 48604 ,
‰ safety shutters,
‰ edgewise bars.
84
Installation de l’appareillage
Switchgear Installation
3.1.2.6.d.
Choix des transformateurs de courant (TI)
Choice of current transformers (CT)
Disjoncteur
Circuit breaker
Ref.
Standard
Tropicalisé
Tropicalised
NS630b - 1600
NT06 - 16
16530
NW08/10/12
NW16/20/25
NS1600b/2000/
2500
NW32/40
NS 3200
NW40b/50/63
Rapport
Rating
Ouverture
Opening
16480
500 - 5 A
65 x 32 mm
16531
16481
600 - 5 A
65 x 32 mm
16532
16482
800 - 5 A
65 x 32 mm
16533
16483
1000 - 5 A
65 x 32 mm
16534
1250 - 5 A
65 x 32 mm
16535
1250 - 5 A
65 x 32 mm
16530
16480
500 - 5 A
65 x 32 mm
16531
16481
600 - 5 A
65 x 32 mm
16532
16482
800 - 5 A
65 x 32 mm
16533
16483
1000 - 5 A
65 x 32 mm
16534
1250 - 5 A
65 x 32 mm
16537
1250 - 5 A
84 x 34 mm
16538
1500 - 5 A
84 x 34 mm
16540
1250 - 5 A
127 x 38 mm
16541
1500 - 5 A
127 x 38 mm
16542
2000 - 5 A
127 x 38 mm
16543
2500 - 5 A
127 x 38 mm
16544
3000 - 5 A
127 x 38 mm
16545
2500 - 5 A
127 x 52 mm
16547
4000 - 5 A
127 x 52 mm
16548
5000 - 5 A
165 x 55 mm
16549
6000 - 5 A
165 x 55 mm
Nota: Les TI pouvent etre montes amont ou
aval du disjoncteur .Vérifier sur les plans
d'assemblage.
Guide Technique V9 / V9 Technical Guide
N.B.: The CT's can be assembled on the line
side or load side of the circuit breakers.
Check on the assembly drawings.
85
Installation de l’appareillage
Switchgear Installation
3.1.2.7.
Option raccordement jeu de barres Disjoncteur
Compact NS 630b-1600 et Masterpact NT / NW
Option connection busbars Compact NS 630b-1600 and
Masterpact NT / NW circuit breaker
Option
Option
Fixe
Fixed
Option:
1
Débrochable
Withdrawable
1
a) NS 630b-1600 (1)
a) NT 06-16
b) NW 08 / 25
1
NW 32
(1) Disponible derrière porte avec la même modularité
(1) Available behind door with the same modularity
Guide Technique V9 / V9 Technical Guide
86
Installation de l’appareillage
Switchgear Installation
Option:
1
Option
Option
Fixe
Fixed
Débrochable
Withdrawable
1
NW 40
(1) Disponible derrière porte avec la même modularité
(1) Available behind door with the same modularity
Guide Technique V9 / V9 Technical Guide
87
Installation de l’appareillage
Switchgear Installation
Option:
1
Option
Option
Fixe
Fixed
Débrochable
Withdrawable
1
NW 40b
Connecté au jeux de
barres simple
Connected to simple
busbar
(1) Disponible derrière porte avec la même modularité
(1) Available behind door with the same modularity
Guide Technique V9 / V9 Technical Guide
88
Installation de l’appareillage
Switchgear Installation
Option:
1
Option
Option
Fixe
Fixed
Débrochable
Withdrawable
1
NW 40b/50/63
Connecté au jeux de
barres double
Connected to double
busbar
(1) Disponible derrière porte avec la même modularité
(1) Available behind door with the same modularity
Guide Technique V9 / V9 Technical Guide
89
Installation de l’appareillage
Switchgear Installation
Option:
2
Option
Option
Fixe
Fixed
Débrochable
Withdrawable
2
a) NS 630b-1600 (1)
a) NT 06-16
b) NW 08/25
2
a) NW 32
b) NS 3200
(1) Disponible derrière porte avec la même modularité
(1) Available behind door with the same modularity
Guide Technique V9 / V9 Technical Guide
90
Installation de l’appareillage
Switchgear Installation
Option:
2
Option
Option
Fixe
Fixed
Débrochable
Withdrawable
2
NW 40
(1) Disponible derrière porte avec la même modularité
(1) Available behind door with the same modularity
Guide Technique V9 / V9 Technical Guide
91
Installation de l’appareillage
Switchgear Installation
Option:
2
Option
Option
Fixe
Fixed
Débrochable
Withdrawable
2
NW 40b
Connecté au jeux de
barres simple
Connected to simple
busbar
(1) Disponible derrière porte avec la même modularité
(1) Available behind door with the same modularity
Guide Technique V9 / V9 Technical Guide
92
Installation de l’appareillage
Switchgear Installation
Option:
2
Option
Option
Fixe
Fixed
Débrochable
Withdrawable
2
NW 40b/50/63
Connecté au jeux de
barres double
Connected to double
busbar
(1) Disponible derrière porte avec la même modularité
(1) Available behind door with the same modularity
Guide Technique V9 / V9 Technical Guide
93
Installation de l’appareillage
Switchgear Installation
Option:
3a
Option
Option
Fixe
Fixed
Débrochable
Withdrawable
3a
a) NS 630b-1600 (1)
a) NT 06-16
b) NS1600b - 2500
c) NW 08 - 20
9 M (a)
10 M (b)
12 M (c)
9 M (a)
12 M (c)
3a
a) NS 630b-1600 (1)
Derrière porte +
commande rotative
prolongée
Behind door +
ext. rotary
handle
b) NW 25
c) NW 32
(1) Disponible derrière porte avec la même modularité
(1) Available behind door with the same modularity
Guide Technique V9 / V9 Technical Guide
94
Installation de l’appareillage
Switchgear Installation
Option:
3b
Option
Option
Fixe
Fixed
Débrochable
Withdrawable
3b
a) NS 630b-1600 (1)
a) NT 06-16
b) NW 08 - 25
3b
NW 32
(1) Disponible derrière porte avec la même modularité
(1) Available behind door with the same modularity
Guide Technique V9 / V9 Technical Guide
95
Installation de l’appareillage
Switchgear Installation
Option:
4a
Option
Option
Fixe
Fixed
Débrochable
Withdrawable
4a
a) NS 630b-1600 (1)
a) NT 06-16
b) NW 08 - 32
Option:
4b
Option
Option
Fixe
Fixed
Débrochable
Withdrawable
4b
a) NS 630b-1600 (1)
a) NT 06-16
b) NW 08 - 32
(1) Disponible derrière porte avec la même modularité
(1) Available behind door with the same modularity
Guide Technique V9 / V9 Technical Guide
96
Installation de l’appareillage
Switchgear Installation
3.1.2.8.
Option raccordement client Disjoncteur
Compact NS 630b-1600 et Masterpact NT / NW
Option incoming bars Compact NS 630b-1600 and
Masterpact NT / NW circuit breake
Option:
Option:
6
6
Option
Option
Fixe
Fixed
Débrochable
Withdrawable
6
a) NS 630b-1600 (1)
a) NT 06-16
b) NW 08 - 25
Option:
Option:
7
Option
Option
Fixe
Fixed
7
Débrochable
Withdrawable
7
a) NS 630b-1600 (1)
a) NT 06-16
b) NW 08 - 16
NS 630b-1600 (1)
Derrière porte +
commande rotative
prolongée
(impossible)
Behind door +
ext. rotary
handle
(not possible)
(1) Disponible derrière porte avec la même modularité
(1) Available behind door with the same modularity
Guide Technique V9 / V9 Technical Guide
97
Installation de l’appareillage
Switchgear Installation
Option:
8a
Option
Option
Fixe
Fixed
Débrochable
Withdrawable
8a
a) NS 630b-1600 (1)
a) NT 06-16
b) NW 08 - 25
Option:
8b
Option
Option
Fixe
Fixed
Débrochable
Withdrawable
8b
a) NS 630b-1600
a) NT 06-16
b) NW 08 - 25
(1) Disponible derrière porte avec la même modularité
(1) Available behind door with the same modularity
Guide Technique V9 / V9 Technical Guide
98
Installation de l’appareillage
Switchgear Installation
Option:
8a
Option
Option
Fixe
Fixed
Débrochable
Withdrawable
8a
NW 32
Option:
8b
Option
Option
Fixe
Fixed
Débrochable
Withdrawable
8b
NW 32
(1) Disponible derrière porte avec la même modularité
(1) Available behind door with the same modularity
Guide Technique V9 / V9 Technical Guide
99
Installation de l’appareillage
Switchgear Installation
Option:
9
Option
Option
Fixe
Fixed
Débrochable
Withdrawable
9
a) NS 630b-1600 (1)
a) NT 06-16
b) NW 08 - 32
c) NS 1600b/2000/
2500/3200
(c)
9
a) NW 40
b) NW 40b
c) NW 40b
c) NW 50
c) NW 63
Sans transfermateur
d’intensité
Without current
transformer
(1) Disponible derrière porte avec la même modularité
(1) Available behind door with the same modularity
Guide Technique V9 / V9 Technical Guide
100
Installation de l’appareillage
Switchgear Installation
Option:
9
Option
Option
Fixe
Fixed
Débrochable
Withdrawable
9
a) NW 40
b) NW 40b
c) NW 40b
c) NW 50
c) NW 63
Avec transfermateur
d’intensité
With current
transformer
(1) Disponible derrière porte avec la même modularité
(1) Available behind door with the same modularity
Guide Technique V9 / V9 Technical Guide
101
Installation de l’appareillage
Switchgear Installation
Option:
10
Option
Option
Fixe
Fixed
Débrochable
Withdrawable
10
a) NS 630b-1600 (1)
a) NT 06-16
b) NW 08 - 32
10
a) NW 40
b) NW 40b
c) NW 40b
c) NW 50
c) NW 63
Avec transfermateur
d’intensité
With current
transformer
(1) Disponible derrière porte avec la même modularité
(1) Available behind door with the same modularity
Guide Technique V9 / V9 Technical Guide
102
Installation de l’appareillage
Switchgear Installation
Option:
10
Option
Option
Fixe
Fixed
Débrochable
Withdrawable
10
a) NW 40
b) NW 40b
c) NW 40b
c) NW 50
c) NW 63
Sans transfermateur
d’intensité
Without current
transformer
(1) Disponible derrière porte avec la même modularité
(1) Available behind door with the same modularity
Guide Technique V9 / V9 Technical Guide
103
Installation de l’appareillage
Switchgear Installation
3.1.2.9.
Interpact
Appareils
Device
Profondeur
Depth
Accès
Access
Position
Position
Nr. ap.
Nb. dev.
Fixation
Fixation
Connections
Connection
Commande (1)
Front view (1)
Nb modules
Nb. modules
INS40/80
400
Av / Ar
Fr / Re
Vertical
Vertical
5
Fixe
Fixed
JdB Vertical
JdB Vertical
B/D
B/D
4
INS100/160
400
Av / Ar
Fr / Re
Vertical
Vertical
3
Fixe
Fixed
JdB Vertical
JdB Vertical
B/D
B/D
6
IN250
400
Av / Ar
Fr / Re
Vertical
Vertical
1
Fixe
Fixed
JdB Vertical
JdB Vertical
B/D
B/D
6
IN400/630
400
Avant
Front
Vertical
Vertical
1
Fixe
Fixed
JdB Vertical
JdB Vertical
B/D
B/D
6+3
IN400/630
600
Av / Ar
Fr / Re
Vertical
Vertical
1
Fixe
Fixed
JdB Vertical
JdB Vertical
AàD
A to D
6+3
IN1000 à 2500
600
Av / Ar
Fr / Re
Vertical
Vertical
1
Fixe
Fixed
JdB Vertical
JdB Vertical
AàD
A to D
12 + 4
(1) Type de commande:
A Derrière porte
B A travers porte
C Derrière porte individuelle
D Plastron
Guide Technique V9 / V9 Technical Guide
(1) Front view:
A behind door
B through door
C behind individual door
D through escutcheon (with front plate)
104
Installation de l’appareillage
Switchgear Installation
3.1.2.10.
Inverseur de source
Source changeover
3.1.2.10.a. Interpact, Compact NS 100-630, Compact C et Masterpact M
(en profondeur 600 mm)
Interpact, Compact NS, Compact C et Masterpact M
(600 mm depth)
Appareils
Device
Type
Type
Accès
Access
Position
Position
Fixation
Fixation
Connections
Connection
Commande (1)
Front view (1)
Nb modules
Nbr of modules
NS100/250
Manuel
Manual
Av / Ar
Front or rear
Vertical
Vertical
Fixe
Fixed
JdB Vertical
Vertical busbar
B
6
NS400/630
Manuel
Manual
Ar
Rear
Vertical
Vertical
Fixe
Fixed
JdB Horizontal
Horizontal busbar
B
12
C801/C1251
Manuel
Manual
Av / Ar
Front or rear
Vertical
Vertical
Fixe
Fixed
JdB Vertical
Vertical busbar
B
12 + 4
Masterpact M
Manuel
Manual
Av / Ar
Front or rear
Normal
Normal
-
-
B
4+12+4+12+8
NS100/250
Auto
Auto
Av / Ar
Front or rear
Horizontal
Horizontal
Fixe
Fixed
JdB Vertical
Vertical busbar
A
12
NS400/630
Auto
Auto
Av / Ar
Front or rear
Horizontal
Horizontal
Fixe
Fixed
JdB Vertical
Vertical busbar
A
14
C801/1251
Auto
Auto
Av / Ar
Front or rear
Horizontal
Horizontal
Fixe
Fixed
JdB Vertical
Vertical busbar
A
20
Masterpact M
Auto
Auto
Av / Ar
Front or rear
Normal
Normal
-
-
-
4+12+4+12+8
IN250
Manuel
Manual
Av / Ar
Front or rear
Vertical
Vertical
Fixe
Fixed
JdB Vertical
Vertical busbar
B
6
Manuel / Manual
Pour les détails additionels voir chapitre 4.1
du Guide des plans d’assemblage, ref.
“7041xxx.pdf”
Auto / Auto
For additional details see chapter 4.1 of
Assembly drawings guide, ref. “7041xxx.pdf”
NS400/
630
12M
NS400/
630
NS400/
630
NS100/ NS100/
250
250
NS400/
630
14M
UA / BA
6M
NS100/
250
NS100/
250
INS 250 INS 250
6M
Guide Technique V9 / V9 Technical Guide
UA / BA
12M
105
Installation de l’appareillage
Switchgear Installation
3.1.2.10.b. Compact NS 630b - NS 1600, 3/4P
Masterpact NT 06 à 16, 3/4P
Compact NS 630b - NS 1600, 3/4P
Masterpact NT 06 to 16, 3/4P
fixe derrière ou à travers porte
débrochable à travers porte
fixe/débrochable
fixed behind or through door
withdrawable behind or though door
fixed/withdrawable
4M
4M
UA
/
BA
(2) Automatisme télécommandé
des inverseurs de source.
(2) Automatic source change
over system
3M
Option
1+8a
(2)
UA
/
BA
3M
Option
1+6
(2)
9M
9M
8M
8M
Option
2+9
Option
2+9
9M
9M
7M
7M
Colonne individuelle
RAV: Profondeur 600; Largeur
400+700+200
RAR: Profondeur 1000; Largeur 400+700
Disponible en IP20 jusqu’à IP54, forme 1 à 4
Pour les détails additionnels voir chapitre 4.1
du Guide des plans d’assemblage, ref.
“7041xxx.pdf”
VUE DU HAUT /
TOP VIEW
Individual column
Front Access: Depth 600; Width
400+700+200
Rear Access: Depth 1000; Width 400+700
Available in IP20 up to IP54, form 1 up to 4.
For additional details see chapter 4.1 of
Assembly drawings guide, ref. “7041xxx.pdf”
400
700
Face avant / Front
Guide Technique V9 / V9 Technical Guide
200
600
600
400
VUE DU HAUT /
TOP VIEW
400
700
Face avant / Front
106
Installation de l’appareillage
Switchgear Installation
Compact NS 630b - NS 1600, 3/4P
Masterpact NT 06 à 16, 3/4P
Compact NS 630b - NS 1600, 3/4P
Masterpact NT 06 to 16, 3/4P
4M
fixe derrière ou à travers porte
débrochable à travers porte
fixe/débrochable
fixed behind or through door
withdrawable behind or though door
fixed/withdrawable
(2) Automatisme télécommandé
des inverseurs de source.
(2) Automatic source change
over system
Option
3a+8b
4M
Option
3a+6
9M
9M
3M
3M
8M
4M
8M
UA / BA
(2)
4M
Option
3a+9
UA / BA
(2)
Option
3a+9
9M
9M
3M
3M
Raccordé au Jeu de Barres Vertical
standard
RAV: Profondeur 600; Largeur
200+700+200
RAR: Profondeur 1000; Largeur 200+700
Disponible en IP20 jusqu’à IP54, forme 1 to 4
Pour les détails additionnels voir chapiter 4.1
du Guide des plans d’assemblage, ref.
“7041xxx.pdf”
Connceted to standard Vertical Busbar
Front Access: Depth 600; Width
200+700+200
Rear Access: Depth 1000; Width 200+700
Available in IP20 up to IP54, form 1 up to 4.
For additional details see chapter 4.1 of
Assembly drawings guide, ref. “7041xxx.pdf”
VUE DU HAUT /
TOP VIEW
200
700
200
Face avant / Front
Guide Technique V9 / V9 Technical Guide
600
600
400
VUE DU HAUT /
TOP VIEW
200
700
Face avant / Front
107
Installation de l’appareillage
Switchgear Installation
3.1.2.10.c. Compact NS 630b à NS 1600, 3/4P débrochable derrière porte
Compact NS 630b to NS 1600, 3/4P withdrawable behind door
(2) Automatisme télécommandé
des inverseurs de source.
(2) Automatic source change
over system
4M
UA
/
BA
3M
Option
1+8a
(2)
4M
UA
/
BA
3M
Option
1+6
(2)
9M
9M
11M
11M
Option
2+9
Option
2+9
9M
9M
4M
4M
Colonne individuelle
RAV: Profondeur 600; Largeur
400+700+200
RAR: Profondeur 1000; Largeur 400+700
Disponible en IP 20 jusqu’à IP54
40 modules pour l’installation des
équipements.
Pour les détails additionnels voir chapitre 4.1
du Guide des plans d’assemblage, ref.
“7041xxx.pdf”
VUE DU HAUT /
TOP VIEW
Individual column
Front Access: Depth 600; Width
400+700+200
Rear Access: Depth 1000; Width 400+700
Available in IP20 up to IP54
40 modules for installation of equipament
For additional details see chapter 4.1 of
Assembly drawings guide, ref. “7041xxx.pdf”
400
700
Face avant / Front
Guide Technique V9 / V9 Technical Guide
200
600
600
400
VUE DU HAUT /
TOP VIEW
400
700
Face avant / Front
108
Installation de l’appareillage
Switchgear Installation
Compact NS 630b à NS 1600, 3/4P débrochable derrière porte
Compact NS 630b to NS 1600, 3/4P withdrawable behind door
(2) Automatisme télécommandé
des inverseurs de source.
(2) Automatic source change
over system
4M
3M
4M
3M
Option
3a+6
Option
3a+8b
9M
9M
3M
2M
5M
4M
UA / BA
(2)
4M
UA / BA
(2)
3M
3M
Option
3a+9
Option
3a+9
9M
9M
3M
3M
Raccordé au Jeu de Barres Vertical
standard
RAV: Profondeur 600; Largeur
200+700+200
RAR: Profondeur 1000; Largeur 200+700
Disponible en IP20 jusqu’à IP54, forme 1 à 4
Pour les détails additionnels voir chapitre 4.1
du Guide des plans d’assemblage, ref.
“7041xxx.pdf”
Connected to standard Vertical Busbar
Front Access: Depth 600; Width
200+700+200
Rear Access: Depth 1000; Width 200+700
Available in IP20 up to IP54, form 1 upto 4.
For additional details see chapter 4.1 of
Assembly drawings guide, ref. “7041xxx.pdf”
VUE DU HAUT /
TOP VIEW
200
700
200
Face avant / Front
Guide Technique V9 / V9 Technical Guide
600
600
400
VUE DU HAUT /
TOP VIEW
200
700
Face avant / Front
109
Installation de l’appareillage
Switchgear Installation
3.1.2.10.d. Compact NS 630b à NS 1600, 3/4P fixe derrière porte
Compact NS 630b to NS 1600, 3/4P fixed behind door
4M
(1)
Option
2+9
(1) Seulement commande
manuelle pour les inverseurs de
source.
(1) Only manual command for
the source change over
9M
4M
Colonne individuelle
RAV/RAR: Profondeur 600; Largeur 700
Disponible en IP20 jusqu’à IP31, forme 1
40 modules pour l’installation des
equipements.
Pour les détails additionels voir Chapitre 4.1
du Guide des plans d’assemblage, ref.
“7041xxx.pdf”
Individual column
Front/Rear Access: Depth 600; Width 700
Available in IP20 up to IP31, form 1
40 modules for installation of equipament.
For additional details see Chapter 4.1 of
Assembly drawings guide, ref. “7041xxx.pdf”
600
VUE DU HAUT /
TOP VIEW
700
Face avant / Front
Guide Technique V9 / V9 Technical Guide
110
Installation de l’appareillage
Switchgear Installation
3.1.2.10.e. Masterpact NW 08 à 25, 3/4P fixe/débro à travers porte
Masterpact NW 08 to 25, 3/4P fixed/drawout through door
(2) Automatisme télécommandé
des inverseurs de source.
(2) Automatic source change
over system
4M
UA
/
BA
Option
1+8a
4M
UA
/
BA
Option
1+6
(2)
(2)
12M
12M
8M
8M
Option
2+9
Option
2+9
12M
12M
4M
4M
Colonne individuelle
RAV: Profondeur 600; Largeur
400+700+200
RAR: Profondeur 1000; Largeur 400+700
Disponible en IP20 jusqu’à IP54, forme 1 à 4
40 modules pour l’installation des
equipements.
Pour les détails additionnels voir chapitre 4.1
du Guide des plans d’assemblage, ref.
“7041xxx.pdf”
VUE DU HAUT /
TOP VIEW
Individual column
Front Access: Depth 600; Width
400+700+200
Rear Access: Depth 1000; Width 400+700
Available in IP20 up to IP54, form 1 up to 4.
40 modules for installation of equipament
For additional details see chapter 4.1 of
Assembly drawings guide, ref. “7041xxx.pdf”
400
700
Face avant / Front
Guide Technique V9 / V9 Technical Guide
200
600
600
400
VUE DU HAUT /
TOP VIEW
400
700
Face avant / Front
111
Installation de l’appareillage
Switchgear Installation
3.1.2.10.f.
Masterpact NW 08 à 20, 3/4P fixe/débro à travers porte
Masterpact NW 08 to 20, 3/4P fixed/ drawout through door
(2) Automatisme télécommandé
des inverseurs de source.
(2) Automatic source change
over system
4M
Option
3a+8b
4M
Option
3a+6
12M
12M
4M
4M
UA / BA
4M
(2)
UA / BA
4M
(2)
Option
3a+9
Option
3a+9
12M
12M
3M
3M
Raccordé au Jeu de Barres Vertical
standard
RAV: Profondeur 600; Largeur
200+700+200
RAR: Profondeur 1000; Largeur 200+700
Disponible en IP20 jusqu’à IP54, forme 1 à 4
Pour les détails additionnels voir chapitre 4.1
du Guide des plans d’assemblage, ref.
“7041xxx.pdf”
Connected to standard Vertical Busbar
Front Access: Depth 600; Width
200+700+200
Rear Access: Depth 1000; Width 200+700
Available in IP20 up to IP54, form 1 up to 4.
For additional details see chapter 4.1 of
Assembly drawings guide, ref. “7041xxx.pdf”
VUE DU HAUT /
TOP VIEW
200
700
200
Face avant / Front
Guide Technique V9 / V9 Technical Guide
600
600
400
VUE DU HAUT /
TOP VIEW
200
700
Face avant / Front
112
Installation de l’appareillage
Switchgear Installation
3.1.2.10.g. Masterpact NW 32 à 63, 3/4P fixe/débro (RAV/RAR)
Masterpact NW 32 to 63, 3/4P fixed/ drawout (Front/Rear access)
(1)
(1)
Option
2+9
Option
2+9
NW32/40
NW32/40
(2) Automatisme télécommandé
des inverseurs de source
(2) Automatic source change
over system
(1)
(1)
(3)
(2)
(1) Définir le nombre de
modules suivant chapitre
3.1.2.6. et 3.1.2.7. de ce
document
(1) Define the number of
modules according to chapters
3.1.2.6. and 3.1.2.7. of this
document
UA / BA
(3) Détails sur la modularité, voir
dessin 51131664 pour NW32 ou
dessin 51131686 pour NW40
(3) Details about modularity, see
dwg 51131664 for NW32 or dwg
51131686 for NW40
(1)
600
VUE DU SOMMET / TOP VIEW
700
700
700
RAV/RAR: Profondeur 600; Largeur
700+700+700
Pour les détails additionnels voir chapitre 4.1
du Guide des plans d’assemblage, ref.
“7041xxx.pdf”
UA / BA
(2)
Front Access/Rear Access: Depth 600;
Width 700+700+700
For additional details see chapter 4.1 of
Assembly drawings guide, ref. “7041xxx.pdf”
13 M (1)
13 M (1)
Option
2+9
Option
2+9
NW40b/50/63
NW40b/50/63
13 M (1)
13 M (1)
14 M (1)
14 M (1)
(1) Détails sur le
modularité, voir dessin
51131661 pour
NW40b/50/63
(1) Details about
modularity, see dwg
51131661
NW40b/50/63
(2) Automatisme
télécommandé des
inverseurs de source
(2) Automatic source
change over system
600
VUE DU SOMMET / TOP VIEW
1200
1200
RAV/RAR: Profondeur 600; Largeur
1200+1200+1200
Guide Technique V9 / V9 Technical Guide
1200
Front Access/Rear Access: Depth 600;
Width 1200+1200+1200
113
Installation de l’appareillage
Switchgear Installation
3.1.2.11.
Couplage et Jeux de Barres de Transfert
Tie Breaker and Transfer Busbar
3.1.2.11.a. Masterpact NW40 et jeu des barres simple
Masterpact NW40 and single busbars
13 M
13 M
Option
2+1
Option
2+1
NW40
NW40
12 M
12 M
15 M
15 M
VUE DU SOMMET / TOP VIEW
200
Guide Technique V9 / V9 Technical Guide
700
Il est interdit de connecter des
unités fonctionnels sur le jeu de
barre de trasfert.
Pour les détails additionnels voir
chapitre 3.3 du Guide des plans
d'assemblage, ref. "7041xxx.pdf".
It's not allowed to connect any
device direct to transfer busbar.
For additional details see chapter
3.3 of Assembly drawings guide,
ref. "7041xxx.pdf".
VUE DU SOMMET / TOP VIEW
200
700
114
Installation de l’appareillage
Switchgear Installation
3.1.2.11.b. Masterpact NW40b/50/63 et jeu des barres double
Masterpact NW40b/50/63 and double busbars
13 M
Option
2+1
Option
2+1
NW40b/50/63
NW40b/50/63
13 M
13 M
14 M
14 M
VUE DU SOMMET / TOP VIEW
200/400
Guide Technique V9 / V9 Technical Guide
13 M
1200
VUE DU SOMMET / TOP VIEW
200/400
Il est interdit de connecter des
unités fonctionnels sur le jeu de
barre de trasfert.
- 200 mm pour le JdB simple
(pour Nw40b seulement)
Pour les détails additionnels voir
chapitre 3.3 du Guide des plans
d'assemblage, ref.
"7041xxx.pdf".
It's not allowed to connect any
device direct to transfer busbar.
- 200 mm for single busbar (for
Nw40b only)
For additional details see chapter
3.3 of Assembly drawings guide,
1200
115
Sommaire du chapitre
Chapter contents
3.2. Condensateur
Capacitor
3.2.1.
Installation ............................................................................................... 117
Installation
3.2.1.1.
Cellule Dc largeur 700 mm profondeur 400/600 mm ............... 117
Dc column with 700 mm width and 400/600 mm depth
3.2.1.2.
Cellule D largeur 700 mm profondeur 400/600 mm ................. 117
D column with 700 mm width and 400/600 mm depth
Guide Technique V9 / V9 Technical Guide
116
Installation de l’appareillage
Switchgear Installation
3.2. Condensateur
Capacitor
3.2.1.
Installation
Installation
3.2.1.1.
Cellule Dc largeur 700 mm profondeur 400/600/1000 mm
Dc column with 700 mm width and 400/600/1000 mm depth
Installation pour température ambiante de
35°C IP 31:
„ Ventilation naturelle (avec grille d’entrée
et de sortie MGA réf. 07985, sans filtre).
„ Configuration maximum:
‰ 6 platines de 30 kVar en 400 volts 50 Hz.
„ Ventilation forcée (avec ventilateur MGA
réf 07989 + grille MGA réf 07985 et filtre
MGA réf 07982).
„ Configuration maximum:
‰ 6 platines de 60 kVar en 400 volts 50 Hz.
Installation for an ambient temperature of
35°C IP 31:
„ Natural ventilation (with MGA inlet and
outlet grid ref. 07985, without filter).
„ maximum configuration:
‰ 6 x30 kVar mounting plates in 400 volts
50 Hz.
„ Forced ventilation (with MGA fan ref.
07989 + MGA grid ref. 07985 and MGA
filter ref. 07982).
„ Maximum configuration:
‰ 6 x60 kVar mounting plates in 400 volts
50 Hz.
Pour les autres tensions et fréquences, ne
pas dépasser les valeurs de puissance
mentionnées ci-dessus (voir configuration
dans catalogue Rectiphase).
For the other voltages and frequencies, do
not exceed the power values mentioned
above (see configuration in the Rectiphase
catalogue).
3.2.1.2.
Cellule D largeur 700 mm profondeur 400/600/1000 mm
D column with 700 mm width and 400/600/1000 mm depth
pour montage en cellule D utiliser:
„ La platine n° 51 128 229:
‰ 6 modules avec maximum de 50 kVar en
600 volts 60 Hz.
„ Ne pas dépasser dans une même cellule
les valeurs données pour la cellule Dc.
For mounting in column D use:
„ Mounting plate n° 51 128 229:
‰ 6 modules with-maximum of 50 kVar in
600 volts 60 Hz.
„ Do not exceed in the same column the
values given for column Dc.
Toutes ces informations sont communiquées
conformément aux essais réalisés sur les
cellules Blokset.
All this information is communicated
according to the tests performed on the
Blokset columns.
Puissances d’emploi en 50/60 Hz θ ≤ 55 °C
Power ratings at 50/60 Hz θ ≤ 55 °C
220 V
240 V
kVar
400 V
440 V
kVar
660 V
690 V
kVar
Contacteur
Contactor
6,5
12,5
18
LC1-DFK
8,5
15
24
LC1-DGK
10
20
30
LC1-DLK
15
25
36
LC1-DNWK
20
30
48
LC1-DPK
25
40
58
LC1-DTK
40
60
92
LC1-DWK
Guide Technique V9 / V9 Technical Guide
117
Installation de l’appareillage
Switchgear Installation
Tableau de déclassement des condensateurs BT
Derating of Low Voltage Capacitors in Blokset
Réseau
Net
230 V 50 Hz
400 V 50 Hz
415 V 50 Hz
600 V 50 Hz
690 V 50 Hz
240 V 60 Hz
400 V 60 Hz
440 V 60 Hz
480 V 60 Hz
600 V 60 Hz
Classe de température de
l’armoire moyenne
sur 24 h
Temperature class
average by 24 h
Puissance admissible
armoire Blokset Dc type
132 Ventilation forcée
Power Blokset Type Dc
132 Ventilation with fan
Puissance admissible
armoire Blokset D/Dc type
132 Ventilation naturelle
Power Blokset Type D/Dc
132 Natural ventilation
Puissance Admissible
armoire Blokset C type
134 Ventilation naturelle
Power Blokset Type C 134
Natural ventilation
35° C
180 kVar
120 kVar
120 kVar
40° C
180 kVar (1)
120 kVar (1)
120 kVar (1)
45° C
180 kVar (1)
120 kVar (1)
120 kVar (1)
35° C
360 kVar
180 kVar
180 kVar
40° C
270 kVar (1)
180 kVar (1)
135 kVar (1)
45° C
270 kVar (1)
135 kVar (1)
135 kVar (1)
35° C
360 kVar
180 kVar
180 kVar
40° C
270 kVar (1)
180 kVar (1)
135 kVar (1)
45° C
270 kVar (1)
135 kVar (1)
135 kVar (1)
35° C
240 kVar
120 kVar
40° C
240 kVar (1)
120 kVar (1)
45° C
240 kVar (1)
120 kVar (1)
35° C
330 kVar
220 kVar
165 kVar
40° C
270 kVar (1)
220 kVar (1)
135 kVar (1)
45° C
270 kVar (1)
180 kVar (1)
135 kVar (1)
35° C
200 kVar
100 kVar
100 kVar
40° C
150 kVar (1)
100 kVar (1)
75 kVar (1)
45° C
150 kVar (1)
60 kVar (1)
60 kVar (1)
35° C
360 kVar
150 kVar
150 kVar
40° C
270 kVar (1)
150 kVar (1)
125 kVar (1)
45° C
270 kVar (1)
125 kVar (1)
125 kVar (1)
35° C
360 kVar
180 kVar
180 kVar
40° C
300 kVar (1)
180 kVar (1)
150 kVar (1)
45° C
300 kVar (1)
150 kVar (1)
150 kVar (1)
35° C
360 kVar
180 kVar
180 kVar
40° C
360 kVar (1)
180 kVar (1)
180 kVar (1)
45° C
360 kVar (1)
180 kVar (1)
180 kVar (1)
35° C
300 kVar
150 kVar
40° C
300 kVar (1)
150 kVar (1)
45° C
300 kVar (1)
150 kVar (1)
non autorisé (2)
impossible (2)
non autorisé (2)
impossible (2)
Température > 45° C
Temperature > 45° C
non autorisé (2)
impossible (2)
(1) Les condensateurs utilisés doivent être
sur-dimensionnés en tension selon le
tableau ci-dessous
(2) Pour des ambiantes supérieures à 45 °C,
le régulateur Varlogic ne fonctionne plus:
Guide Technique V9 / V9 Technical Guide
(1) capacitors used must be ondimensionned in tension according to the
table below,
(2) for the ambient superior to 45 °C, the
regulating Varlogic doesn't function
anymore:
118
Installation de l’appareillage
Switchgear Installation
CONDENSATEURS SURDIMENSIONNES
ON-DIMENSIONNES CAPACITORS
CONDENSATEURS SURDIMENSIONNES
ON-DIMENSIONNES CAPACITORS
RESEAU
NET
TENSION
VOLTAGE
230 V 50 Hz
230 V
400 V 50 Hz
470 V
415 V 50 Hz
470 V
600 V 50 Hz
690 V
690 V 50 Hz
nous consulter, condensateurs spéciaux
under consult, special capacitors
240 V 60 Hz
400 V
400 V 60 Hz
470 V
440 V 60 Hz
480 V
480 V 60 Hz
525 V
600 V 60 Hz
690 V
Guide Technique V9 / V9 Technical Guide
119
Sommaire du chapitre
Chapter contents
3.3. Blokset Mf / Mw
Protection moteurs
Motor protection
3.3.1.
Tableaux de coordination et modularité ............................................... 123
Coordination and modularity tables
3.3.1.1.
GV2-P .......................................................................................... 124
Type de coordination: 1
Coordination type: 1
3.3.1.2.
GV2-P .......................................................................................... 126
Type de coordination: 2
Coordination type: 2
3.3.1.3.
Etoile / Triangle (Y/D)
STAR / DELTA (Y/D)
Compact NS100-630z-MA .......................................................... 145
Type de coordination: 1
Coordination type: 1
Guide Technique V9 / V9 Technical Guide
Etoile / Triangle (Y/D)
STAR / DELTA (Y/D)
Compact NS80H-MA .................................................................. 144
Type de coordination: 2
Coordination Type: 2
3.3.1.13.
2 sens de marche
Reverse
Compact NS80H-MA .................................................................. 142
Type de coordination: 1
Coordination type: 1
3.3.1.12.
2 sens de marche
Reverse
Compact NS80H-MA .................................................................. 140
Type de coordination: 2
Coordination type: 2
3.3.1.11.
DOL (Démarrage direct)
DOL (Direct On Line)
Compact NS80H-MA .................................................................. 138
Type de coordination: 1
Coordination type: 1
3.3.1.10.
DOL (Démarrage direct)
DOL (Direct On Line)
Compact NS80H-MA .................................................................. 136
Type de coordination: 2
Coordination type: 2
3.3.1.9.
Etoile / Triangle (Y/D)
STAR / DELTA (Y/D)
Compact NS80H-MA .................................................................. 134
Type de coordination: 1
Coordination type: 1
3.3.1.8.
Etoile / Triangle (Y/D)
STAR / DELTA (Y/D)
GV2-P .......................................................................................... 133
Type de coordination: 2
Coordination type: 2
3.3.1.7.
2 sens de Marche
Reverse
GV2-P .......................................................................................... 132
Type de coordination: 1
Coordination type: 1
3.3.1.6.
2 sens de Marche
Reverse
GV2-P .......................................................................................... 130
Type de coordination: 2
Coordination type: 2
3.3.1.5.
DOL (Démarrage direct)
DOL (Direct On Line)
GV2-P .......................................................................................... 128
Type de coordination: 1
Coordination type: 1
3.3.1.4.
DOL (Démarrage direct)
DOL (Direct On Line)
DOL (Démarrage direct)
DOL (Direct On Line)
120
Sommaire du chapitre
Chapter contents
3.3.1.14.
Compact NS100-630z-MA .......................................................... 148
Type de coordination: 2
Coordination type: 2
3.3.1.15.
Compact NS100-630l-MA ........................................................... 151
Type de coordination: 1
Coordination type: 1
3.3.1.16.
Etoile / Triangle (Y/D)
STAR / DELTA (Y/D)
GV7 .............................................................................................. 170
Type de coordination: 2
Coordination Type: 2
3.3.1.25.
2 sens de marche
Reverse
GV7 .............................................................................................. 169
Type de coordination: 1
Coordination Type: 1
3.3.1.24.
2 sens de marche
Reverse
GV7 .............................................................................................. 167
Type de coordination: 2
Coordination Type: 2
3.3.1.23.
DOL (Démarrage direct)
DOL (Direct On Line)
GV7 .............................................................................................. 165
Type de coordination: 1
Coordination Type: 1
3.3.1.22.
DOL (Démarrage direct)
DOL (Direct On Line)
GV7 .............................................................................................. 163
Type de coordination: 2
Coordination Type: 2
3.3.1.21.
Etoile / Triangle (Y/D)
STAR / DELTA (Y/D)
GV7 .............................................................................................. 161
Type de coordination: 1
Coordination Type: 1
3.3.1.20.
Etoile / Triangle (Y/D)
STAR / DELTA (Y/D)
Compact NS100-630l-MA ........................................................... 159
Type de coordination: 2
Coordination Type: 2
3.3.1.19.
2 sens de marche
Reverse
Compact NS100-630l-MA ........................................................... 157
Type de coordination: 1
Coordination type: 1
3.3.1.18.
2 sens de marche
Reverse
(Compact NS100-630l-MA .......................................................... 154
Type de coordination: 2
Coordination type: 2
3.3.1.17.
DOL (Démarrage direct)
DOL (Direct On Line)
Etoile / Triangle (Y/D)
STAR / DELTA (Y/D)
INTEGRAL ................................................................................... 171
Contacteurs-Disjoncteurs INTEGRALDOL (Démarrage direct)
INTEGRAL contactors-circuit breakersDOL (Direct On Line)
3.3.1.26.
INTEGRAL ................................................................................... 174
Contacteurs-Disjoncteurs INTEGRAL2 sens de marche
INTEGRAL contactors-circuit breakersReverse
3.3.1.27.
GV2-P .......................................................................................... 177
Type de coordination: 1
Coordination type: 1
3.3.1.28.
GV2-P .......................................................................................... 177
Type de coordination: 2
Coordination type: 2
3.3.1.29.
DOL monophasé (Démarrage direct)
Single phase - DOL (Direct On Line)
Compact NS80H-MA .................................................................. 178
Type de coordination: 1
Coordination type: 1
Guide Technique V9 / V9 Technical Guide
DOL monophasé (Démarrage direct)
Single phase - DOL (Direct On Line)
DOL monophasé (Démarrage direct)
Single phase - DOL (Direct On Line)
121
Sommaire du chapitre
Chapter contents
3.3.1.30.
Compact NS80H-MA .................................................................. 178
Type de coordination: 2
Coordination type: 2
3.3.2.
DOL monophasé (Démarrage direct)
Single phase - DOL (Direct On Line)
Déclassement des appareils - AC3 ....................................................... 179
Starters derating - AC3
3.3.2.1.
GV2-P .......................................................................................... 179
Type de coordination: 1-2
Coordination type: 1-2
3.3.2.2.
Compact NS et GV7 ................................................................... 180
Type de coordination: 1-2
Coordination type: 1-2
3.3.2.3.
Integral ........................................................................................ 184
Contacteurs - Disjoncteurs Integral Coordination totale
Contactors - Integral Circuit breakersTotal coordination
3.3.3.
Départ distribution en tiroir ................................................................... 184
Feeder in drawer
3.3.3.1.
3.3.4.
Nombre de modules nécessaires ............................................. 184
Number of modules required
Colonne arrivée Blokset Mw avec Masterpact NT ............................... 185
Blokset Mw incoming column with Masterpact NT
Guide Technique V9 / V9 Technical Guide
122
Installation de l’appareillage
Switchgear Installation
Blokset Mf / Mw
3.3. Blokset Mf / Mw
Protection moteurs
Motor protection
3.3.1.
Tableaux de coordination et modularité
Coordination and modularity tables
Blokset Type Mf et Mw
Les GV7 peuvent être remplacés par les
appareils NS100 / 250 associés à un
déclencheur électronique protection moteur
(à définir cas par cas).
La modularité des associations avec NS +
déclencheur est la même que celles définies
avec les GV7.
Guide Technique V9 / V9 Technical Guide
Blokset Type Mf and Mw
GV7 CB’s can be replaced by NS100 / 250
CB’s equipped with a electronic trip unit
dedicated to motor protection (to be defined
case per case).
The number of modules of this kind of starter
are the same than the ones given for GV7
CB’s.
123
Installation de l’appareillage
Switchgear Installation
3.3.1.1.
GV2-P
Type de coordination: 1 - - - - - - - - - - - - - - - -DOL (Démarrage direct)
Coordination type: 1 - - - - - - - - - - - - - - - - - - -DOL (Direct On Line)
400/415 V
TeSys
GV2-P
TeSys
Puissance moteur
Power motor
P (kW)
I (A)
0,37
0,98
0,55
1,5
0,75
2
1,1
2,5
1,5
3,5
2,2
5
3
6,5
4
8,4
5,5
11
7,5
14,8
9
18,1
11
21
15
28,5
Pdc
BC
Icu (kA)
Rms (kA)
50
50
50
50
50
50
50
50
15
15
15
15
10
Type de coordination: 1
Coordination type: 1
TeSys
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV2-P05
0,63...1
GV2-P06
1...1,6
GV2-P07
1,6...2,5
GV2-P08
2,5...4
GV2-P08
2,5...4
GV2-P10
4...6,3
GV2-P14
6...10
GV2-P14
6...10
GV2-P16
9...14
GV2-P20
13...18
GV2-P21
17...23
GV2-P22
20...25
GV2-P32
24...32
GV2-P
440 V
TeSys
TeSys
Puissance moteur
Power motor
P (kW)
I (A)
0,37
0,99
0,55
1,36
0,75
1,68
1,1
2,37
1,5
3,06
2,2
4,42
3
5,77
4
7,9
5,5
10,4
7,5
13,7
9
16,9
11
20,1
15
26,5
Pdc
BC
Icu (kA)
Rms (kA)
50
50
50
50
50
50
50
15
8
8
8
6
6
Guide Technique V9 / V9 Technical Guide
TeSys
TeSys
Nb modules
Nbr of modules
Contacteur
Contactor
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K09
LC1-K09
LC1-K12
LC1-D18
LC1-D25
LC1-D25
LC1-D32
Mf
Mw
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Type de coordination: 1
Coordination type: 1
TeSys
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV2-P05
0,63...1
GV2-P06
1...1,6
GV2-P07
1,6...2,5
GV2-P07
1,6...2,5
GV2-P08
2,5...4
GV2-P10
4...6,3
GV2-P10
4...6,3
GV2-P14
6...10
GV2-P16
9...14
GV2-P20
13...18
GV2-P20
13...18
GV2-P21
17...23
GV2-P32
24...32
DOL (Démarrage direct)
DOL (Direct On Line)
TeSys
DOL (Démarrage direct)
DOL (Direct On Line)
TeSys
Nb modules
Nbr of modules
Contacteur
Contactor
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K09
LC1-K12
LC1-D18
LC1-D18
LC1-D25
LC1-D32
Mf
Mw
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
124
Installation de l’appareillage
Switchgear Installation
GV2-P
500 V
TeSys
TeSys
Puissance moteur
Power motor
P (kW)
I (A)
0,37
1
0,55
1,21
0,75
1,5
1,1
2
1,5
2,6
2,2
3,8
3
5
4
6,5
5,5
9
7,5
12
9
13,9
11
18,4
15
23
18,5
28,5
Pdc
BC
Icu (kA)
Rms (kA)
50
50
50
50
50
50
50
10
10
6
6
4
4
4
Guide Technique V9 / V9 Technical Guide
Type de coordination: 1
Coordination type: 1
TeSys
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV2-P06
1...1,6
GV2-P06
1...1,6
GV2-P06
1...1,6
GV2-P07
1,6...2,5
GV2-P08
2,5...4
GV2-P08
2,5...4
GV2-P10
4...6,3
GV2-P14
6...10
GV2-P14
6...10
GV2-P16
9...14
GV2-P20
13...18
GV2-P21
17...23
GV2-P22
20...25
GV2-P32
24...32
TeSys
DOL (Démarrage direct)
DOL (Direct On Line)
TeSys
Nb modules
Nbr of modules
Contacteur
Contactor
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K09
LC1-K09
LC1-K12
LC1-D18
LC1-D25
LC1-D25
LC1-D32
Mf
Mw
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
125
Installation de l’appareillage
Switchgear Installation
3.3.1.2.
GV2-P
Type de coordination: 2 - - - - - - - - - - - - - - - -DOL (Démarrage direct)
Coordination type: 2 - - - - - - - - - - - - - - - - - - -DOL (Direct On Line)
GV2-P
400/415 V
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
Pdc
BC
Icu (kA)
Rms (kA)
Type de coordination: 2
Coordination type: 2
TeSys
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
TeSys
DOL (Démarrage direct)
DOL (Direct On Line)
TeSys
Nb modules
Nbr of modules
Contacteur
Contactor
Mf
Mw
0,37
0,98
130
GV2-P05
0,63…1
LC1-D09
3
3
0,55
1,5
130
GV2-P06
1…1,6
LC1-D09
3
3
0,75
2
130
GV2-P07
1,6…2,5
LC1-D09
3
3
1,1
2,5
130
GV2-P08
2,5…4
LC1-D09
3
3
1,5
3,5
130
GV2-P08
2,5…4
LC1-D09
3
3
2,2
5
130
GV2-P10
4…6,3
LC1-D09
3
3
3
6,5
130
GV2-P14
6…10
LC1-D09
3
3
4
8,4
130
GV2-P14
6…10
LC1-D18
3
3
5,5
11
130
GV2-P16
9…14
LC1-D25
3
3
7,5
14,8
50
GV2-P20
13…18
LC1-D25
3
3
9
18,1
50
GV2-P21
17..23
LC1-D32
3
3
11
21
50
GV2-P22
20..25
LC1-D40
3
6
15
28,5
50
GV2-P32
24…32
LC1-D40
3
6
GV2-P
440 V
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
Pdc
BC
Icu (kA)
Rms (kA)
Type de coordination: 2
Coordination type: 2
TeSys
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
TeSys
DOL (Démarrage direct)
DOL (Direct On Line)
TeSys
Nb modules
Nbr of modules
Contacteur
Contactor
Mf
Mw
0,37
0,99
130
GV2-P05
0,63…1
LC1-D09
3
3
0,55
1,36
130
GV2-P06
1…1,6
LC1-D09
3
3
0,75
1,68
130
GV2-P07
1,6…2,5
LC1-D09
3
3
1,1
2,37
130
GV2-P07
1,6…2,5
LC1-D09
3
3
1,5
3,06
130
GV2-P08
2,5…4
LC1-D09
3
3
2,2
4,42
130
GV2-P10
4…6,3
LC1-D09
3
3
3
5,77
130
GV2-P10
4…6,3
LC1-D09
3
3
4
7,9
130
GV2-P14
6…10
LC1-D18
3
3
5,5
10,4
130
GV2-P16
9…14
LC1-D25
3
3
7,5
13,7
130
GV2-P16
9…14
LC1-D25
3
3
9
16,9
50
GV2-P20
13…18
LC1-D32
3
3
11
20,1
50
GV2-P21
17..23
LC1-D40
3
6
15
26,5
50
GV2-P32
24…32
LC1-D40
3
6
Guide Technique V9 / V9 Technical Guide
126
Installation de l’appareillage
Switchgear Installation
GV2-P
500 V
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
Pdc
BC
Icu (kA)
Rms (kA)
Type de coordination: 2
Coordination type: 2
TeSys
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
TeSys
DOL (Démarrage direct)
DOL (Direct On Line)
TeSys
Nb modules
Nbr of modules
Contacteur
Contactor
Mf
Mw
0,37
1
130
GV2-P06
1…1,6
LC1-D09
3
3
0,55
1,21
130
GV2-P06
1…1,6
LC1-D09
3
3
0,75
1,5
130
GV2-P06
1…1,6
LC1-D09
3
3
1,1
2
130
GV2-P07
1,6…2,5
LC1-D09
3
3
1,5
2,6
130
GV2-P08
2,5…4
LC1-D09
3
3
2,2
3,8
130
GV2-P08
2,5…4
LC1-D09
3
3
3
5
130
GV2-P10
4…6,3
LC1-D09
3
3
4
6,5
50
GV2-P14
6…10
LC1-D12
3
3
5,5
9
50
GV2-P14
6…10
LC1-D18
3
3
7,5
12
42
GV2-P16
9…14
LC1-D25
3
3
9
13,9
42
GV2-P16
9…14
LC1-D25
3
3
11
18,4
10
GV2-P21
17..23
LC1-D32
3
3
15
23
10
GV2-P22
20..25
LC1-D40
3
6
18,5
28,5
10
GV2-P32
24…32
LC1-D40
3
6
Guide Technique V9 / V9 Technical Guide
127
Installation de l’appareillage
Switchgear Installation
3.3.1.3.
GV2-P
Type de coordination: 1 - - - - - - - - - - - - - - - -2 sens de Marche
Coordination type: 1 - - - - - - - - - - - - - - - - - - -Reverse
400/415 V
TeSys
GV2-P
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
0,37
0,98
0,55
1,5
0,75
2
1,1
2,5
1,5
3,5
2,2
5
3
6,5
4
8,4
5,5
11
7,5
14,8
9
18,1
11
21
15
28,5
Pdc
BC
Icu (kA)
Rms (kA)
50
50
50
50
50
50
50
50
15
15
15
15
10
Type de coordination: 1
Coordination type: 1
TeSys
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV2-P05
0,63...1
GV2-P06
1...1,6
GV2-P07
1,6...2,5
GV2-P08
2,5...4
GV2-P08
2,5...4
GV2-P10
4...6,3
GV2-P14
6...10
GV2-P14
6...10
GV2-P16
9...14
GV2-P20
13...18
GV2-P21
17...23
GV2-P22
20...25
GV2-P32
24...32
GV2-P
440 V
TeSys
TeSys
Puissance moteur
Power motor
P (kW)
I (A)
0,37
0,99
0,55
1,36
0,75
1,68
1,1
2,37
1,5
3,06
2,2
4,42
3
5,77
4
7,9
5,5
10,4
7,5
13,7
9
16,9
11
20,1
15
26,5
Pdc
BC
Icu (kA)
Rms (kA)
50
50
50
50
50
50
50
15
8
8
8
6
6
Guide Technique V9 / V9 Technical Guide
TeSys
2 sens de Marche
Reverse
TeSys
Nb modules
Nbr of modules
Contacteur
Contactor
2 x LC1-K06
2 x LC1-K06
2 x LC1-K06
2 x LC1-K06
2 x LC1-K06
2 x LC1-K06
2 x LC1-K09
2 x LC1-K09
2 x LC1-K12
2 x LC1-D18
2 x LC1-D25
2 x LC1-D25
2 x LC1-D32
Mf
Mw
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Type de coordination: 1
Coordination type: 1
TeSys
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV2-P05
0,63...1
GV2-P06
1...1,6
GV2-P07
1,6...2,5
GV2-P07
1,6...2,5
GV2-P08
2,5...4
GV2-P10
4...6,3
GV2-P10
4...6,3
GV2-P14
6...10
GV2-P16
9...14
GV2-P20
13...18
GV2-P20
13...18
GV2-P21
17...23
GV2-P32
24...32
TeSys
2 sens de Marche
Reverse
TeSys
Nb modules
Nbr of modules
Contacteur
Contactor
2 x LC1-K06
2 x LC1-K06
2 x LC1-K06
2 x LC1-K06
2 x LC1-K06
2 x LC1-K06
2 x LC1-K06
2 x LC1-K09
2 x LC1-K12
2 x LC1-D18
2 x LC1-D18
2 x LC1-D25
2 x LC1-D32
Mf
Mw
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
128
Installation de l’appareillage
Switchgear Installation
GV2-P
500 V
TeSys
TeSys
Puissance moteur
Power motor
P (kW)
I (A)
0,37
1
0,55
1,21
0,75
1,5
1,1
2
1,5
2,6
2,2
3,8
3
5
4
6,5
5,5
9
7,5
12
9
13,9
11
18,4
15
23
18,5
28,5
Pdc
BC
Icu (kA)
Rms (kA)
50
50
50
50
50
50
50
10
10
6
6
4
4
4
Guide Technique V9 / V9 Technical Guide
Type de coordination: 1
Coordination type: 1
TeSys
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV2-P06
1...1,6
GV2-P06
1...1,6
GV2-P06
1...1,6
GV2-P07
1,6...2,5
GV2-P08
2,5...4
GV2-P08
2,5...4
GV2-P10
4...6,3
GV2-P14
6...10
GV2-P14
6...10
GV2-P16
9...14
GV2-P20
13...18
GV2-P21
17...23
GV2-P22
20...25
GV2-P32
24...32
TeSys
2 sens de Marche
Reverse
TeSys
Nb modules
Nbr of modules
Contacteur
Contactor
2 x LC1-K06
2 x LC1-K06
2 x LC1-K06
2 x LC1-K06
2 x LC1-K06
2 x LC1-K06
2 x LC1-K06
2 x LC1-K09
2 x LC1-K09
2 x LC1-K12
2 x LC1-D18
2 x LC1-D25
2 x LC1-D25
2 x LC1-D32
Mf
Mw
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
129
Installation de l’appareillage
Switchgear Installation
3.3.1.4.
GV2-P
Type de coordination: 2 - - - - - - - - - - - - - - - -2 sens de Marche
Coordination type: 2 - - - - - - - - - - - - - - - - - - -Reverse
GV2-P
400/415 V
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
Pdc
BC
Icu (kA)
Rms (kA)
Type de coordination: 2
Coordination type: 2
TeSys
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
TeSys
2 sens de Marche
Reverse
TeSys
Nb modules
Nbr of modules
Contacteur
Contactor
Mf
Mw
0,37
0,98
130
GV2-P05
0,63…1
2xLC1-D09
3
3
0,55
1,5
130
GV2-P06
1…1,6
2xLC1-D09
3
3
0,75
2
130
GV2-P07
1,6…2,5
2xLC1-D09
3
3
1,1
2,5
130
GV2-P08
2,5…4
2xLC1-D09
3
3
1,5
3,5
130
GV2-P08
2,5…4
2xLC1-D09
3
3
2,2
5
130
GV2-P10
4…6,3
2xLC1-D09
3
3
3
6,5
130
GV2-P14
6…10
2xLC1-D09
3
3
4
8,4
130
GV2-P14
6…10
2xLC1-D18
3
3
5,5
11
130
GV2-P16
9…14
2xLC1-D25
3
3
7,5
14,8
50
GV2-P20
13…18
2xLC1-D25
3
3
9
18,1
50
GV2-P21
17..23
2xLC1-D32
3
3
11
21
50
GV2-P22
20..25
2xLC1-D40
6
6
15
28,5
50
GV2-P32
24…32
2xLC1-D40
6
6
GV2-P
440 V
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
Pdc
BC
Icu (kA)
Rms (kA)
Type de coordination: 2
Coordination type: 2
TeSys
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
TeSys
2 sens de Marche
Reverse
TeSys
Nb modules
Nbr of modules
Contacteur
Contactor
Mf
Mw
0,37
0,99
130
GV2-P05
0,63…1
2xLC1-D09
3
3
0,55
1,36
130
GV2-P06
1…1,6
2xLC1-D09
3
3
0,75
1,68
130
GV2-P07
1,6…2,5
2xLC1-D09
3
3
1,1
2,37
130
GV2-P07
1,6…2,5
2xLC1-D09
3
3
1,5
3,06
130
GV2-P08
2,5…4
2xLC1-D09
3
3
2,2
4,42
130
GV2-P10
4…6,3
2xLC1-D09
3
3
3
5,77
130
GV2-P10
4…6,3
2xLC1-D09
3
3
4
7,9
130
GV2-P14
6…10
2xLC1-D18
3
3
5,5
10,4
130
GV2-P16
9…14
2xLC1-D25
3
3
7,5
13,7
130
GV2-P16
9…14
2xLC1-D25
3
3
9
16,9
50
GV2-P20
13…18
2xLC1-D32
3
3
11
20,1
50
GV2-P21
17..23
2xLC1-D40
6
6
15
26,5
50
GV2-P32
24…32
2xLC1-D40
6
6
Guide Technique V9 / V9 Technical Guide
130
Installation de l’appareillage
Switchgear Installation
GV2-P
500 V
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
Pdc
BC
Icu (kA)
Rms (kA)
Type de coordination: 2
Coordination type: 2
TeSys
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
TeSys
2 sens de Marche
Reverse
TeSys
Nb modules
Nbr of modules
Contacteur
Contactor
Mf
Mw
0,37
1
130
GV2-P06
1…1,6
2xLC1-D09
3
6
0,55
1,21
130
GV2-P06
1…1,6
2xLC1-D09
3
6
0,75
1,5
130
GV2-P06
1…1,6
2xLC1-D09
3
6
1,1
2
130
GV2-P07
1,6…2,5
2xLC1-D09
3
6
1,5
2,6
130
GV2-P08
2,5…4
2xLC1-D09
3
6
2,2
3,8
130
GV2-P08
2,5…4
2xLC1-D09
3
6
3
5
130
GV2-P10
4…6,3
2xLC1-D09
3
6
4
6,5
50
GV2-P14
6…10
2xLC1-D12
3
6
5,5
9
50
GV2-P14
6…10
2xLC1-D18
3
6
7,5
12
42
GV2-P16
9…14
2xLC1-D25
3
6
9
13,9
42
GV2-P16
9…14
2xLC1-D25
3
6
11
18,4
10
GV2-P21
17..23
2xLC1-D32
3
6
15
23
10
GV2-P22
20..25
2xLC1-D40
6
6
18,5
28,5
10
GV2-P32
24…32
2xLC1-D40
6
6
Guide Technique V9 / V9 Technical Guide
131
Installation de l’appareillage
Switchgear Installation
3.3.1.5.
GV2-P
Type de coordination: 1 - - - - - - - - - - - - - - - -Etoile / Triangle (Y/∆)
Coordination type: 1 - - - - - - - - - - - - - - - - - - -STAR / DELTA (Y/∆)
400/415 V
TeSys
GV2-P
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
1,5
3,5
2,2
5
3
6,5
4
8,4
5,5
11
7,5
14,8
9
18,1
11
21
Pdc
BC
Icu (kA)
Rms (kA)
50
50
50
50
15
15
15
15
TeSys
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV2-P08
2,5...4
GV2-P10
4...6,3
GV2-P14
6...10
GV2-P14
6...10
GV2-P16
9...14
GV2-P20
13...18
GV2-P21
17...23
GV2-P22
20...25
GV2-P
440 V
TeSys
TeSys
Puissance moteur
Power motor
P (kW)
I (A)
1,5
3,06
2,2
4,42
3
5,77
4
7,9
5,5
10,4
7,5
13,7
9
16,9
11
20,1
Pdc
BC
Icu (kA)
Rms (kA)
50
50
50
15
8
8
8
6
Guide Technique V9 / V9 Technical Guide
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Type de coordination: 1
Coordination type: 1
TeSys
TeSys
Nb modules
Nbr of modules
Contacteur
Contactor
3 x LC1-K06
3 x LC1-K06
3 x LC1-K06
3 x LC1-K06
3 x LC1-K06
3 x LC1-K09
3 x LC1-D12
3 x LC1-D12
Mf
Mw
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Type de coordination: 1
Coordination type: 1
TeSys
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV2-P08
2,5...4
GV2-P10
4...6,3
GV2-P10
4...6,3
GV2-P14
6...10
GV2-P16
9...14
GV2-P20
13...18
GV2-P20
13...18
GV2-P21
17...23
TeSys
TeSys
Nb modules
Nbr of modules
Contacteur
Contactor
3 x LC1-K06
3 x LC1-K06
3 x LC1-K06
3 x LC1-K06
3 x LC1-K06
3 x LC1-K09
3 x LC1-D12
3 x LC1-D12
Mf
Mw
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
132
Installation de l’appareillage
Switchgear Installation
3.3.1.6.
GV2-P
Type de coordination: 2 - - - - - - - - - - - - - - - -Etoile / Triangle (Y/∆)
Coordination type: 2 - - - - - - - - - - - - - - - - - - -STAR / DELTA (Y/∆)
GV2-P
400/415 V
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
Pdc
BC
Icu (kA)
Rms (kA)
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Type de coordination: 2
Coordination type: 2
TeSys
TeSys
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
TeSys
Nb modules
Nbr of modules
Contacteur
Contactor
Mf
Mw
1,5
3,5
130
GV2-P08
2,5...4
3 x LC1-D09
6
6
2,2
5
130
GV2-P10
4...6,3
3 x LC1-D18
6
6
3
6,5
130
GV2-P14
6...10
3 x LC1-D18
6
6
4
8,4
130
GV2-P14
6...10
3 x LC1-D18
6
6
5,5
11
130
GV2-P16
9...14
3 x LC1-D25
6
6
7,5
14,8
50
GV2-P20
13...18
3 x LC1-D25
6
6
9
18,1
50
GV2-P21
17...23
3 x LC1-D32
6
6
11
21
50
GV2-P22
20...25
3 x LC1-D40
6
9
GV2-P
440 V
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
Pdc
BC
Icu (kA)
Rms (kA)
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Type de coordination: 2
Coordination type: 2
TeSys
TeSys
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
TeSys
Nb modules
Nbr of modules
Contacteur
Contactor
Mf
Mw
1,5
3,06
130
GV2-P08
2,5...4
3 x LC1-D09
6
6
2,2
4,42
130
GV2-P10
4...6,3
3 x LC1-D18
6
6
3
5,77
130
GV2-P10
4...6,3
3 x LC1-D18
6
6
4
7,9
130
GV2-P14
6...10
3 x LC1-D18
6
6
5,5
10,4
50
GV2-P16
9...14
3 x LC1-D25
6
6
7,5
13,7
50
GV2-P16
9...14
3 x LC1-D25
6
6
9
16,9
20
GV2-P20
13...18
3 x LC1-D32
6
6
11
20,1
20
GV2-P21
17...23
3 x LC1-D40
6
9
Guide Technique V9 / V9 Technical Guide
133
Installation de l’appareillage
Switchgear Installation
Compact NS80H-MA
3.3.1.7.
Type de coordination: 1 - - - - - - - - - - - - - - - -DOL (Démarrage direct)
Coordination type: 1 - - - - - - - - - - - - - - - - - - -DOL (Direct On Line)
Démarrage: Normal
Start-up: Normal
400/415 V
TeSys
Compact NS80H-MA
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
0,37
0,98
0,55
1,5
0,75
2
1,1
2,5
1,5
3,5
2,2
5
3
6,5
4
8,4
5,5
11
7,5
14,8
9
18,1
11
21
15
28,5
18,5
35
22
42
30
57
37
69
Pdc
BC
Icu (kA)
Rms (kA)
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
Guide Technique V9 / V9 Technical Guide
TeSys
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
Cal (A)
Rat (A)
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
12,5
25
25
25
50
50
50
80
80
Type de coordination: 1
Coordination type: 1
TeSys
Contacteurs
Contactor
Type
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D12
LC1-D18
LC1-D18
LC1-D25
LC1-D32
LC1-D38
LC1-D50
LC1-D65
LC1-D80
DOL (Démarrage direct)
DOL (Direct On Line)
TeSys
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LRD-05
0,63...1
LRD-06
1...1,7
LRD-07
1,6...2,5
LRD-08
2,5...4
LRD-08
2,5...4
LRD-10
4...6
LRD-12
5,5...8
LRD-14
7...10
LRD-16
9...13
LRD-21
12...18
LRD-22
16...24
LRD-22
16...24
LRD-32
23...32
LRD-35
30...38
LRD-3357
37...50
LRD-3359
48...65
LRD-3363
63...80
TeSys
Nb modules
Nbr of modules
Mf
Mw
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
6
3
6
3
6
134
Installation de l’appareillage
Switchgear Installation
Compact NS80H-MA
440 V
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
0,37
0,99
0,55
1,36
0,75
1,68
1,1
2,37
1,5
3,06
2,2
4,42
3
5,77
4
7,9
5,5
10,4
7,5
13,7
9
16,9
11
20,1
15
26,5
18,5
32,8
22
39
30
51,5
37
64
45
76
Pdc
BC
Icu (kA)
Rms (kA)
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
TeSys
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
Cal (A)
Rat (A)
2,5
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
25
25
25
50
50
50
80
80
80
Compact NS80H-MA
500 V
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
0,37
1
0,55
1,21
0,75
1,5
1,1
2
1,5
2,6
Pdc
BC
Icu (kA)
Rms (kA)
25
25
25
25
25
TeSys
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
Cal (A)
Rat (A)
2,5
2,5
2,5
2,5
6,3
Type de coordination: 1
Coordination type: 1
TeSys
Contacteurs
Contactor
Type
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D12
LC1-D18
LC1-D18
LC1-D25
LC1-D32
LC1-D38
LC1-D40
LC1-D65
LC1-D65
LC1-D80
DOL (Démarrage direct)
DOL (Direct On Line)
TeSys
Type de coordination: 1
Coordination type: 1
TeSys
Contacteurs
Contactor
Type
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
TeSys
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LRD-05
0,63...1
LRD-06
1...1,7
LRD-07
1,6...2,5
LRD-07
1,6...2,5
LRD-08
2,5...4
LRD-10
4...6
LRD-10
4...6
LRD-14
7...10
LRD-16
9...13
LRD-21
12...18
LRD-21
12...18
LRD-22
16...24
LRD-32
23...32
LRD-35
30...38
LRD-3357
37...50
LRD-3359
48...65
LRD-3359
48...65
LRD-3363
63...80
Nb modules
Nbr of modules
Mf
Mw
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
6
3
6
3
6
3
6
DOL (Démarrage direct)
DOL (Direct On Line)
TeSys
TeSys
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LRD-06
1...1,7
LRD-06
1...1,7
LRD-06
1...1,7
LRD-07
1,6...2,5
LRD-08
2,5...4
Nb modules
Nbr of modules
3
3
3
3
3
Mf
Mw
3
3
3
3
3
3
2,2
3,8
25
NS80H-MA
6,3
LC1-D09
LRD-08
2,5...4
3
3
5
25
NS80H-MA
6,3
LC1-D09
LRD-10
4...6
3
3
4
6,5
25
NS80H-MA
12,5
LC1-D09
LRD-12
5,5...8
3
3
5,5
9
25
NS80H-MA
12,5
LC1-D09
LRD-14
7...10
3
3
7,5
12
25
NS80H-MA
25
LC1-D12
LRD-16
9...13
3
3
9
13,9
25
NS80H-MA
25
LC1-D18
LRD-21
12...18
3
3
11
18,4
25
NS80H-MA
25
LC1-D25
LRD-22
16...24
3
3
15
23
25
NS80H-MA
50
LC1-D32
LRD-22
16...24
3
3
18,5
28,5
25
NS80H-MA
50
LC1-D32
LRD-35
23...32
3
3
22
33
25
NS80H-MA
50
LC1-D40
LRD-3355
30...40
3
6
30
45
25
NS80H-MA
50
LC1-D50
LRD-3357
37...50
3
6
37
55
25
NS80H-MA
80
LC1-D65
LRD-3359
48...65
3
6
Guide Technique V9 / V9 Technical Guide
135
Installation de l’appareillage
Switchgear Installation
3.3.1.8.
Compact NS80H-MA
Type de coordination: 2 - - - - - - - - - - - - - - - -DOL (Démarrage direct)
Coordination type: 2 - - - - - - - - - - - - - - - - - - -DOL (Direct On Line)
Démarrage: Normal
Start-up: Normal
Compact NS80H-MA
400/415 V
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
TeSys
Type de coordination: 2
Coordination type: 2
TeSys
Pdc
BC
Icu (kA)
Rms (kA)
Disjoncteurs
Circuit Breaker
Type
Type
Cal (A)
Rat (A)
Contacteurs
Contactor
Type
Type
DOL (Démarrage direct)
DOL (Direct On Line)
TeSys
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
TeSys
Nb modules
Nbr of modules
Mf
Mw
0,37
0.98
70
NS80H-MA
2,5
LC1-D09
LRD-05
0,63…1
3
3
0,55
1.5
70
NS80H-MA
2,5
LC1-D09
LRD-06
1…1,7
3
3
0,75
2
70
NS80H-MA
2,5
LC1-D09
LRD-07
1,6…2,5
3
3
1,1
2,5
70
NS80H-MA
6,3
LC1-D18
LRD-08
2,5…4
3
3
1,5
3,5
70
NS80H-MA
6,3
LC1-D18
LRD-08
2,5…4
3
3
2,2
5
70
NS80H-MA
6,3
LC1-D25
LRD-10
4…6
3
3
3
6,5
70
NS80H-MA
12,5
LC1-D32
LRD-12
5,5…8
3
3
4
8,4
70
NS80H-MA
12,5
LC1-D32
LRD-14
7…10
3
3
5,5
11
70
NS80H-MA
12,5
LC1-D32
LRD-16
9…13
3
3
7,5
14,8
70
NS80H-MA
25
LC1-D32
LRD-21
12…18
3
3
9
18,1
70
NS80H-MA
25
LC1-D40
LRD-3322
17..25
3
6
11
21
70
NS80H-MA
25
LC1-D40
LRD-3322
17..25
3
6
15
28,5
70
NS80H-MA
50
LC1-D40
LRD-3353
23…32
3
6
18,5
35
70
NS80H-MA
50
LC1-D50
LRD-3355
30…40
3
6
22
42
70
NS80H-MA
50
LC1-D50
LRD-3357
37…50
3
6
30
57
70
NS80H-MA
80
LC1-D65
LRD-3359
48…65
3
6
37
69
70
NS80H-MA
80
LC1-D80
LRD-3363
63…80
3
6
Guide Technique V9 / V9 Technical Guide
136
Installation de l’appareillage
Switchgear Installation
Compact NS80H-MA
440 V
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
TeSys
Type de coordination: 2
Coordination type: 2
TeSys
Pdc
BC
Icu (kA)
Rms (kA)
Disjoncteurs
Circuit Breaker
Type
Type
Cal (A)
Rat (A)
Contacteurs
Contactor
Type
Type
DOL (Démarrage direct)
DOL (Direct On Line)
TeSys
TeSys
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
Nb modules
Nbr of modules
Mf
Mw
0,37
0,99
65
NS80H-MA
2,5
LC1-D09
LRD-05
0,63...1
3
0,55
1,36
65
NS80H-MA
2,5
LC1-D09
LRD-06
1…1,7
3
3
0,75
1,68
65
NS80H-MA
2,5
LC1-D09
LRD-07
1,6…2,5
3
3
1,1
2,37
65
NS80H-MA
2,5
LC1-D09
LRD-07
1,6…2,5
3
3
1,5
3,06
65
NS80H-MA
6,3
LC1-D18
LRD-08
2,5…4
3
3
2,2
4,42
65
NS80H-MA
6,3
LC1-D25
LRD-10
4…6
3
3
3
5,77
65
NS80H-MA
6,3
LC1-D25
LRD-10
4…6
3
3
4
7,9
65
NS80H-MA
12,5
LC1-D32
LRD-14
7…10
3
3
5,5
10,4
65
NS80H-MA
12,5
LC1-D32
LRD-16
9…13
3
3
7,5
13,7
65
NS80H-MA
25
LC1-D32
LRD-21
12…18
3
3
9
16,9
65
NS80H-MA
25
LC1-D38
LRD-21
12…18
3
3
11
20,1
65
NS80H-MA
25
LC1-D40
LRD-3322
17..25
3
6
15
26,5
65
NS80H-MA
50
LC1-D40
LRD-3353
23…32
3
6
18,5
32,8
65
NS80H-MA
50
LC1-D50
LRD-3355
30...40
3
6
22
39
65
NS80H-MA
50
LC1-D50
LRD-3357
37...50
3
6
30
51,5
65
NS80H-MA
80
LC1-D65
LRD-3359
48...65
3
6
37
64
65
NS80H-MA
80
LC1-D80
LRD-3359
48...65
3
9
45
76
65
NS80H-MA
80
LC1-D80
LRD-3363
63...80
3
6
Compact NS80H-MA
500 V
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
Pdc
BC
Icu (kA)
Rms (kA)
TeSys
Disjoncteurs
Circuit Breaker
Type
Type
Type de coordination: 2
Coordination type: 2
TeSys
Cal (A)
Rat (A)
Contacteurs
Contactor
Type
Type
3
DOL (Démarrage direct)
DOL (Direct On Line)
TeSys
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
TeSys
Nb modules
Nbr of modules
Mf
Mw
0,37
1
25
NS80H-MA
1,5
LC1-D09
LRD-06
1…1,7
3
3
0,55
1,21
25
NS80H-MA
2,5
LC1-D09
LRD-06
1…1,7
3
3
0,75
1,5
25
NS80H-MA
2,5
LC1-D09
LRD-06
1…1,7
3
3
1,1
2
25
NS80H-MA
2,5
LC1-D09
LRD-07
1,6…2,5
3
3
1,5
2,6
25
NS80H-MA
6,3
LC1-D18
LRD-08
2,5…4
3
3
2,2
3,8
25
NS80H-MA
6,3
LC1-D18
LRD-08
2,5…4
3
3
3
5
25
NS80H-MA
6,3
LC1-D25
LRD-10
4…6
3
3
4
6,5
25
NS80H-MA
12,5
LC1-D32
LRD-12
5,5…8
3
3
5,5
9
25
NS80H-MA
12,5
LC1-D32
LRD-14
7…10
3
3
7,5
12
25
NS80H-MA
12,5
LC1-D32
LRD-16
9…13
3
3
9
13,9
25
NS80H-MA
25
LC1-D32
LRD-21
12…18
3
3
11
18,4
25
NS80H-MA
25
LC1-D40
LRD-3322
17..25
3
6
15
23
25
NS80H-MA
25
LC1-D40
LRD-3322
17..25
3
6
18,5
28,5
25
NS80H-MA
50
LC1-D40
LRD-3353
23…32
3
6
22
33
25
NS80H-MA
50
LC1-D50
LRD-3355
30…40
3
6
30
45
25
NS80H-MA
50
LC1-D50
LRD-3357
37...50
3
6
37
55
25
NS80H-MA
80
LC1-D65
LRD-3359
48...65
3
6
Guide Technique V9 / V9 Technical Guide
137
Installation de l’appareillage
Switchgear Installation
Compact NS80H-MA
3.3.1.9.
Type de coordination: 1 - - - - - - - - - - - - - - - -2 sens de marche
Coordination type: 1 - - - - - - - - - - - - - - - - - - -Reverse
Démarrage: Normal
Start-up: Normal
400/415 V
TeSys
Compact NS80H-MA
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
0,37
0,98
0,55
1,5
0,75
2
1,1
2,5
1,5
3,5
2,2
5
3
6,5
4
8,4
5,5
11
7,5
14,8
9
18,1
11
21
15
28,5
18,5
35
22
42
30
57
37
69
Pdc
BC
Icu (kA)
Rms (kA)
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
TeSys
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
Cal (A)
Rat (A)
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
12,5
25
25
25
50
50
50
80
80
Compact NS80H-MA
440 V
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
0,37
0,99
0,55
1,36
0,75
1,68
1,1
2,37
1,5
3,06
2,2
4,42
3
5,77
4
7,9
5,5
10,4
7,5
13,7
9
16,9
11
20,1
15
26,5
18,5
32,8
22
39
30
51,5
37
64
45
76
Pdc
BC
Icu (kA)
Rms (kA)
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
Guide Technique V9 / V9 Technical Guide
TeSys
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
Cal (A)
Rat (A)
2,5
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
25
25
25
50
50
50
80
80
80
Type de coordination: 1
Coordination type: 1
TeSys
Contacteurs
Contactor
Type
Type
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D12
2 x LC1-D18
2 x LC1-D18
2 x LC1-D25
2 x LC1-D32
2 x LC1-D38
2 x LC1-D50
2 x LC1-D65
2 x LC1-D80
TeSys
TeSys
TeSys
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LRD-05
0,63...1
LRD-06
1...1,7
LRD-07
1,6...2,5
LRD-08
2,5...4
LRD-08
2,5...4
LRD-10
4...6
LRD-12
5,5...8
LRD-14
7...10
LRD-16
9...13
LRD-21
12...18
LRD-22
16...24
LRD-22
16...24
LRD-32
23...32
LRD-35
30...38
LRD-3357
37...50
LRD-3359
48...65
LRD-3363
63...80
Type de coordination: 1
Coordination type: 1
Contacteurs
Contactor
Type
Type
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D12
2 x LC1-D18
2 x LC1-D18
2 x LC1-D25
2 x LC1-D32
2 x LC1-D38
2 x LC1-D40
2 x LC1-D65
2 x LC1-D65
2 x LC1-D80
2 sens de marche
Reverse
Nb modules
Nbr of modules
Mf
Mw
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
6
9
6
9
6
9
2 sens de marche
Reverse
TeSys
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LRD-05
0,63...1
LRD-06
1...1,7
LRD-07
1,6...2,5
LRD-07
1,6...2,5
LRD-08
2,5...4
LRD-10
4...6
LRD-10
4...6
LRD-14
7...10
LRD-16
9...13
LRD-21
12...18
LRD-21
12...18
LRD-22
16...24
LRD-32
23...32
LRD-35
30...38
LRD-3357
37...50
LRD-3359
48...65
LRD-3359
48...65
LRD-3363
63...80
TeSys
Nb modules
Nbr of modules
Mf
Mw
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
6
9
6
9
6
9
6
9
138
Installation de l’appareillage
Switchgear Installation
Compact NS80H-MA
500 V
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
0,37
1
0,55
1,21
0,75
1,5
1,1
2
1,5
2,6
2,2
3,8
3
5
4
6,5
5,5
9
7,5
12
9
13,9
11
18,4
15
23
18,5
28,5
22
33
30
45
37
55
Pdc
BC
Icu (kA)
Rms (kA)
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
Guide Technique V9 / V9 Technical Guide
TeSys
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
Cal (A)
Rat (A)
2,5
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
25
25
25
50
50
50
50
80
Type de coordination: 1
Coordination type: 1
TeSys
Contacteurs
Contactor
Type
Type
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D12
2 x LC1-D18
2 x LC1-D25
2 x LC1-D32
2 x LC1-D32
2 x LC1-D40
2 x LC1-D50
2 x LC1-D65
2 sens de marche
Reverse
TeSys
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LRD-06
1...1,7
LRD-06
1...1,7
LRD-06
1...1,7
LRD-07
1,6...2,5
LRD-08
2,5...4
LRD-08
2,5...4
LRD-10
4...6
LRD-12
5,5...8
LRD-14
7...10
LRD-16
9...13
LRD-21
12...18
LRD-22
16...24
LRD-22
16...24
LRD-35
23...32
LRD-3355
30...40
LRD-3357
37...50
LRD-3359
48...65
TeSys
Nb modules
Nbr of modules
Mf
Mw
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
6
9
6
9
6
9
139
Installation de l’appareillage
Switchgear Installation
3.3.1.10.
Compact NS80H-MA
Type de coordination: 2 - - - - - - - - - - - - - - - -2 sens de marche
Coordination type: 2 - - - - - - - - - - - - - - - - - - -Reverse
Démarrage: Normal
Start-up: Normal
Compact NS80H-MA
400/415 V
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
TeSys
Type de coordination: 2
Coordination type: 2
TeSys
Pdc
BC
Icu (kA)
Rms (kA)
Disjoncteurs
Circuit Breaker
Type
Type
Cal (A)
Rat (A)
Contacteurs
Contactor
Type
Type
2 sens de marche
Reverse
TeSys
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
TeSys
Nb modules
Nbr of modules
Mf
Mw
0,37
0.98
70
NS80H-MA
2,5
2xLC1-D09
LRD-05
0,63…1
3
6
0,55
1.5
70
NS80H-MA
2,5
2xLC1-D09
LRD-06
1…1,7
3
6
0,75
2
70
NS80H-MA
2,5
2xLC1-D09
LRD-07
1,6…2,5
3
6
1,1
2,5
70
NS80H-MA
6,3
2xLC1-D18
LRD-08
2,5…4
3
6
1,5
3,5
70
NS80H-MA
6,3
2xLC1-D18
LRD-08
2,5…4
3
6
2,2
5
70
NS80H-MA
6,3
2xLC1-D25
LRD-10
4…6
3
6
3
6,5
70
NS80H-MA
12,5
2xLC1-D32
LRD-12
5,5…8
3
6
4
8,4
70
NS80H-MA
12,5
2xLC1-D32
LRD-14
7…10
3
6
5,5
11
70
NS80H-MA
12,5
2xLC1-D32
LRD-16
9…13
3
6
7,5
14,8
70
NS80H-MA
25
2xLC1-D32
LRD-21
12…18
3
6
9
18,1
70
NS80H-MA
25
2xLC1-D40
LRD-3322
17..25
6
9
11
21
70
NS80H-MA
25
2xLC1-D40
LRD-3322
17..25
6
9
15
28,5
70
NS80H-MA
50
2xLC1-D40
LRD-3353
23…32
6
9
18,5
35
70
NS80H-MA
50
2xLC1-D50
LRD-3355
30…40
6
9
22
42
70
NS80H-MA
50
2xLC1-D50
LRD-3357
37…50
6
9
30
57
70
NS80H-MA
80
2xLC1-D65
LRD-3359
48…65
6
9
37
69
70
NS80H-MA
80
2xLC1-D80
LRD-3363
63…80
6
9
Guide Technique V9 / V9 Technical Guide
140
Installation de l’appareillage
Switchgear Installation
Compact NS80H-MA
440 V
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
TeSys
Type de coordination: 2
Coordination type: 2
TeSys
Pdc
BC
Icu (kA)
Rms (kA)
Disjoncteurs
Circuit Breaker
Type
Type
Cal (A)
Rat (A)
Contacteurs
Contactor
Type
Type
2 sens de marche
Reverse
TeSys
TeSys
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
Nb modules
Nbr of modules
Mf
Mw
0,37
0,99
65
NS80H-MA
2,5
2xLC1-D09
LRD-05
0,63...1
3
6
0,55
1,36
65
NS80H-MA
2,5
2xLC1-D09
LRD-06
1…1,7
3
6
0,75
1,68
65
NS80H-MA
2,5
2xLC1-D09
LRD-07
1,6…2,5
3
6
1,1
2,37
65
NS80H-MA
2,5
2xLC1-D09
LRD-07
1,6…2,5
3
6
1,5
3,06
65
NS80H-MA
6,3
2xLC1-D18
LRD-08
2,5…4
3
6
2,2
4,42
65
NS80H-MA
6,3
2xLC1-D25
LRD-10
4…6
3
6
3
5,77
65
NS80H-MA
6,3
2xLC1-D25
LRD-10
4…6
3
6
4
7,9
65
NS80H-MA
12,5
2xLC1-D32
LRD-14
7…10
3
6
5,5
10,4
65
NS80H-MA
12,5
2xLC1-D32
LRD-16
9…13
3
6
7,5
13,7
65
NS80H-MA
25
2xLC1-D32
LRD-21
12…18
3
6
9
16,9
65
NS80H-MA
25
2xLC1-D38
LRD-21
12…18
3
6
11
20,1
65
NS80H-MA
25
2xLC1-D40
LRD-3322
17..25
6
9
15
26,5
65
NS80H-MA
50
2xLC1-D40
LRD-3353
23…32
6
9
18,5
32,8
65
NS80H-MA
50
2xLC1-D50
LRD-3355
30...40
6
9
22
39
65
NS80H-MA
50
2xLC1-D50
LRD-3357
37...50
6
9
30
51,5
65
NS80H-MA
80
2xLC1-D65
LRD-3359
48...65
6
9
37
64
65
NS80H-MA
80
2xLC1-D80
LRD-3359
48...65
6
9
45
76
65
NS80H-MA
80
2xLC1-D80
LRD-3363
63...80
6
9
Compact NS80H-MA
500 V
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
TeSys
Type de coordination: 2
Coordination type: 2
TeSys
Pdc
BC
Icu (kA)
Rms (kA)
Disjoncteurs
Circuit Breaker
Type
Type
Cal (A)
Rat (A)
Contacteurs
Contactor
Type
Type
2 sens de marche
Reverse
TeSys
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
TeSys
Nb modules
Nbr of modules
Mf
Mw
0,37
1
25
NS80H-MA
1,5
2xLC1-D09
LRD-06
1…1,7
3
6
0,55
1,21
25
NS80H-MA
2,5
2xLC1-D09
LRD-06
1…1,7
3
6
0,75
1,5
25
NS80H-MA
2,5
2xLC1-D09
LRD-06
1…1,7
3
6
1,1
2
25
NS80H-MA
2,5
2xLC1-D09
LRD-07
1,6…2,5
3
6
1,5
2,6
25
NS80H-MA
6,3
2xLC1-D18
LRD-08
2,5…4
3
6
2,2
3,8
25
NS80H-MA
6,3
2xLC1-D18
LRD-08
2,5…4
3
6
3
5
25
NS80H-MA
6,3
2xLC1-D25
LRD-10
4…6
3
6
4
6,5
25
NS80H-MA
12,5
2xLC1-D32
LRD-12
5,5…8
3
6
5,5
9
25
NS80H-MA
12,5
2xLC1-D32
LRD-14
7…10
3
6
7,5
12
25
NS80H-MA
12,5
2xLC1-D32
LRD-16
9…13
3
6
9
13,9
25
NS80H-MA
25
2xLC1-D32
LRD-21
12…18
3
6
11
18,4
25
NS80H-MA
25
2xLC1-D40
LRD-3322
17..25
6
9
15
23
25
NS80H-MA
25
2xLC1-D40
LRD-3322
17..25
6
9
18,5
28,5
25
NS80H-MA
50
2xLC1-D40
LRD-3353
23…32
6
9
22
33
25
NS80H-MA
50
2xLC1-D50
LRD-3355
30…40
6
9
30
45
25
NS80H-MA
50
2xLC1-D50
LRD-3357
37...50
6
9
37
55
25
NS80H-MA
80
2xLC1-D65
LRD-3359
48...65
6
9
Guide Technique V9 / V9 Technical Guide
141
Installation de l’appareillage
Switchgear Installation
Compact NS80H-MA
3.3.1.11.
Type de coordination: 1 - - - - - - - - - - - - - - - -Etoile / Triangle (Y/∆)
Coordination type: 1 - - - - - - - - - - - - - - - - - - -STAR / DELTA (Y/∆)
Démarrage: Normal
Start-up: Normal
400/415 V
TeSys
Compact NS80H-MA
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
0,37
0,98
0,55
1,5
0,75
2
1,1
2,5
1,5
3,5
2,2
5
3
6,5
4
8,4
5,5
11
7,5
14,8
9
18,1
11
21
15
28,5
18,5
35
22
42
30
57
37
69
Pdc
BC
Icu (kA)
Rms (kA)
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
Guide Technique V9 / V9 Technical Guide
TeSys
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
Cal (A)
Rat (A)
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
12,5
25
25
25
50
50
50
80
80
Type de coordination: 1
Coordination type: 1
TeSys
Contacteurs
Contactor
Type
Type
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D12
3 x LC1-D12
3 x LC1-D18
3 x LC1-D18
3 x LC1-D32
3 x LC1-D32
3 x LC1-D40
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
TeSys
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LRD-04
0,40...0,63
LRD-05
0,63...1
LRD-06
1...1,7
LRD-06
1...1,7
LRD-07
1,6...2,5
LRD-08
2,5...4
LRD-08
2,5...4
LRD-10
4...6
LRD-12
5,5...8
LRD-14
7...10
LRD-16
9...13
LRD-16
9...13
LRD-21
12...18
LRD-22
16...24
LRD-32
23...32
LRD-35
30...38
LRD-3359
48...65
TeSys
Nb modules
Nbr of modules
Mf
Mw
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
9
142
Installation de l’appareillage
Switchgear Installation
Compact NS80H-MA
440 V
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
0,37
0,99
0,55
1,36
0,75
1,68
1,1
2,37
1,5
3,06
2,2
4,42
3
5,77
4
7,9
5,5
10,4
7,5
13,7
9
16,9
11
20,1
15
26,5
18,5
32,8
22
39
30
51,5
37
64
45
76
Pdc
BC
Icu (kA)
Rms (kA)
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
Guide Technique V9 / V9 Technical Guide
TeSys
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
Cal (A)
Rat (A)
2,5
2,5
2,5
6,3
6,3
6,3
6,3
12,5
12,5
25
25
25
50
50
50
80
80
80
Type de coordination: 1
Coordination type: 1
TeSys
Contacteurs
Contactor
Type
Type
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D12
3 x LC1-D12
3 x LC1-D18
3 x LC1-D18
3 x LC1-D18
3 x LC1-D32
3 x LC1-D40
3 x LC1-D40
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
TeSys
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LRD-04
0,40...0,63
LRD-05
0,63...1
LRD-05
0,63...1
LRD-06
1...1,7
LRD-07
1,6...2,5
LRD-08
2,5...4
LRD-08
2,5...4
LRD-10
4...6
LRD-12
5,5...8
LRD-14
7...10
LRD-16
9...13
LRD-16
9...13
LRD-21
12...18
LRD-22
16...24
LRD-22
16...24
LRD-32
23...32
LRD-3355
30...40
LRD-3357
37...50
TeSys
Nb modules
Nbr of modules
Mf
Mw
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
9
6
9
143
Installation de l’appareillage
Switchgear Installation
3.3.1.12.
Compact NS80H-MA
Type de coordination: 2 - - - - - - - - - - - - - - - -Etoile / Triangle (Y/∆)
Coordination Type: 2 - - - - - - - - - - - - - - - - - -STAR / DELTA (Y/∆)
Démarrage: normal
Start-up: Normal
Compact NS80H-MA
400/415 V
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
TeSys
Pdc
BC
Icu (kA)
Rms (kA)
Disjoncteurs
Circuit Breaker
Type
Type
1,5
3,5
70
NS80HMA
2,2
5
70
NS80HMA
3
6,5
70
NS80HMA
TeSys
Cal (A)
Rat (A)
6,3
6,3
12,5
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Type de coordination: 2
Coordination type: 2
Contacteurs
Contactor
Type
Type
TeSys
TeSys
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
Nb modules
Nbr of modules
Mf
Mw
3 x LC1-D18
LRD-08
2,5...4
6
6
3 x LC1-D25
LRD-10
4...6
6
6
3 x LC1-D32
LRD-10
4...6
6
6
4
8,4
70
NS80HMA
12,5
3 x LC1-D32
LRD-16
9...13
6
6
5,5
11
70
NS80HMA
12,5
3 x LC1-D32
LRD-16
9...13
6
6
7,5
14,8
70
NS80HMA
25
3 x LC1-D32
LRD-21
12...18
6
6
9
18,1
70
NS80HMA
25
3 x LC1-D40
LRD-22
16...24
6
9
11
21
70
NS80HMA
25
3 x LC1-D40
LRD-22
16...24
6
9
15
28,5
70
NS80HMA
50
3 x LC1-D40
LRD-3353
23...32
6
9
18,5
35
70
NS80HMA
50
3 x LC1-D50
LRD-3355
30...40
6
9
22
42
70
NS80HMA
50
3 x LC1-D50
LRD-3357
37...50
6
9
30
57
70
NS80HMA
80
3 x LC1-D65
LRD-3359
48...65
6
9
37
69
70
NS80HMA
80
3 x LC1-D80
LRD-3363
63...80
6
9
Compact NS80H-MA
440 V
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
TeSys
Pdc
BC
Icu (kA)
Rms (kA)
Disjoncteurs
Circuit Breaker
Type
Type
TeSys
Cal (A)
Rat (A)
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Type de coordination: 2
Coordination type: 2
Contacteurs
Contactor
Type
Type
TeSys
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
TeSys
Nb modules
Nbr of modules
Mf
Mw
1,5
3,06
65
NS80HMA
6,3
3 x LC1-D18
2,2
4,42
65
NS80HMA
6,3
3 x LC1-D25
LRD-10
4...6
6
6
3
5,77
65
NS80HMA
6,3
3 x LC1-D25
LRD-10
4...6
6
6
6
LRD-08
2,5...4
6
6
4
7,9
65
NS80HMA
12,5
3 x LC1-D32
LRD-14
7...10
6
5,5
10,4
65
NS80HMA
12,5
3 x LC1-D32
LRD-16
9...13
6
6
7,5
13,7
65
NS80HMA
25
3 x LC1-D32
LRD-21
12...18
6
6
9
16,9
65
NS80HMA
25
3 x LC1-D40
LRD-21
17...25
6
11
20,1
65
NS80HMA
25
3 x LC1-D40
LRD-22
17...25
6
9
15
26,5
65
NS80HMA
50
3 x LC1-D40
LRD-3353
23...32
6
9
18,5
32,8
65
NS80HMA
50
3 x LC1-D50
LRD-3355
30...40
6
9
9
22
39
65
NS80HMA
50
3 x LC1-D50
LRD-3357
37...50
6
9
30
51,5
65
NS80HMA
80
3 x LC1-D65
LRD-3359
48...65
6
9
37
64
65
NS80HMA
80
3 x LC1-D80
LRD-3359
48...65
6
9
45
76
65
NS80HMA
80
3 x LC1-D80
LRD-3363
63...80
6
9
Guide Technique V9 / V9 Technical Guide
144
Installation de l’appareillage
Switchgear Installation
Compact NS100-630z-MA
3.3.1.13.
Type de coordination: 1 - - - - - - - - - - - - - - - -DOL (Démarrage direct)
Coordination type: 1 - - - - - - - - - - - - - - - - - - -DOL (Direct On Line)
Démarrage: Normal
Start-up: Normal
Compact NS100-630z-MA
400/415 V
Type de coordination: 1
Coordination type: 1
DOL (Démarrage direct)
DOL (Direct On Line)
Performance de coupure / Breaking characteristics
Compact NS
N
H
L
NS100z-MA
25kA
70kA
130kA
NS160/250z-MA
35kA
70kA
130kA
70kA
130kA
NS400/630z-MA
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
TeSys
TeSys
TeSys
TeSys
0,37
0,98
0,55
1,5
0,75
2
1,1
2,5
Disjoncteurs
Circuit Breaker
Type
Type
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
1,5
3,5
NS100N/H/L-MA
6,3
LC1-D09
LRD-08
2,5...4
2,2
5
NS100N/H/L-MA
6,3
LC1-D09
LRD-10
4...6
3
6
3
6,5
NS100N/H/L-MA
12,5
LC1-D09
LRD-12
5,5...8
3
6
4
8,4
NS100N/H/L-MA
12,5
LC1-D09
LRD-14
7...10
3
6
5,5
11
NS100N/H/L-MA
12,5
LC1-D12
LRD-16
9...13
3
6
7,5
14,8
NS100N/H/L-MA
25
LC1-D18
LRD-21
12...18
3
6
9
18,1
NS100N/H/L-MA
25
LC1-D18
LRD-22
16...24
3
6
11
21
NS100N/H/L-MA
25
LC1-D25
LRD-22
16...24
3
6
15
28,5
NS100N/H/L-MA
50
LC1-D32
LRD-32
23...32
3
6
18,5
35
NS100N/H/L-MA
50
LC1-D38
LRD-35
30...38
3
6
22
42
NS100N/H/L-MA
50
LC1-D50
LRD-3357
37...50
3
6
30
57
NS100N/H/L-MA
50
LC1-D65
LRD-3359
48...65
3
6
37
69
NS100N/H/L-MA
100
LC1-D80
LRD-3363
63...80
3
6
45
81
NS100N/H/L-MA
100
LC1-D95
LRD-3365
80...104
3
6
55
100
NS160N/H/L-MA
150
LC1-D115
LRD-4367
95...120
6
9
75
135
NS160N/H/L-MA
150
LC1-D150
LRD-4369
110...140
6
9
90
165
NS250N/H/L-MA
220
LC1-F185
LR9-F5371
132...220
9
9
110
200
NS250N/H/L-MA
220
LC1-F225
LR9-F5371
132...220
9
9
132
240
NS400H-MA
320
LC1-F265
LR9-F7375
200...330
12
12
132
240
NS400L-MA
320
LC1-F265
LR9-F7375
200...330
12
15
160
285
NS400H-MA
320
LC1-F330
LR9-F7375
200...330
12
12
160
285
NS400L-MA
320
LC1-F330
LR9-F7375
200...330
12
15
200
352
NS630H/L-MA
500
LC1-F400
LR9-F7379
300...500
15
15
220
388
NS630H/L-MA
500
LC1-F400
LR9-F7379
300...500
15
15
250
437
NS630H/L-MA
500
LC1-F500
LR9-F7379
300...500
15
15
Guide Technique V9 / V9 Technical Guide
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LRD-05
0,63...1
LRD-06
1...1,7
LRD-07
1,6...2,5
LRD-08
2,5...4
Nb modules
Nbr of modules
Cal (A)
Rat (A)
2,5
2,5
2,5
6,3
Contacteurs
Contactor
Type
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
Mf
Mw
3
6
3
6
3
6
3
6
3
6
145
Installation de l’appareillage
Switchgear Installation
Compact NS100-630z-MA
440 V
Type de coordination: 1
Coordination type: 1
DOL (Démarrage direct)
DOL (Direct On Line)
Performance de coupure / Breaking characteristics
Compact NS
N
H
L
NS100z-MA
25kA
65kA
130kA
NS160/250z-MA
35kA
65kA
130kA
65kA
130kA
NS400/630z-MA
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
0,37
0,99
0,55
1,36
0,75
1,68
1,1
2,37
1,5
3,06
2,2
4,42
3
5,77
4
7,9
5,5
10,4
7,5
13,7
9
16,9
11
20,1
15
26,5
18,5
32,8
22
39
30
51,5
37
64
45
76
55
90
75
125
90
146
110
178
132
215
160
256
160
256
200
321
200
321
220
353
250
401
280
470
Disjoncteurs
Circuit Breaker
Type
Type
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS160N/H/L-MA
NS160N/H/L-MA
NS250N/H/L-MA
NS250N/H/L-MA
NS400H-MA
NS400L-MA
NS400H-MA
NS400L-MA
NS630H/L-MA
NS630H/L-MA
NS630H/L-MA
Guide Technique V9 / V9 Technical Guide
TeSys
Cal (A)
Rat (A)
2,5
2,5
2,5
2,5
6,3
6,3
12,5
12,5
12,5
25
25
25
50
50
50
50
100
100
100
150
150
220
220
320
320
320
320
500
500
500
TeSys
Contacteurs
Contactor
Type
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D12
LC1-D18
LC1-D18
LC1-D25
LC1-D32
LC1-D38
LC1-D40
LC1-D65
LC1-D65
LC1-D80
LC1-D115
LC1-D150
LC1-F185
LC1-F225
LC1-F265
LC1-F330
LC1-F330
LC1-F330
LC1-F330
LC1-F400
LC1-F400
LC1-F500
TeSys
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LRD-05
0,63...1
LRD-06
1...1,7
LRD-07
1,6...2,5
LRD-07
1,6...2,5
LRD-08
2,5...4
LRD-10
4...6
LRD-10
4...6
LRD-14
7...10
LRD-16
9...13
LRD-21
12...18
LRD-21
12...18
LRD-22
16...24
LRD-32
23...32
LRD-35
30...38
LRD-3357
37...50
LRD-3359
48...65
LRD-3359
48...65
LRD-3363
63...80
LRD-4365
80...104
LRD-4369
110...140
LR9-F5371
132...220
LR9-F5371
132...220
LR9-F5371
132...220
LR9-F7375
200...330
LR9-F7375
200...330
LR9-F7375
200...330
LR9-F7375
200...330
LR9-F7379
300...500
LR9-F7379
300...500
LR9-F7379
300...500
TeSys
Nb modules
Nbr of modules
Mf
Mw
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
6
9
6
9
9
9
9
9
9
12
12
12
12
15
12
12
12
15
15
15
15
15
15
15
146
Installation de l’appareillage
Switchgear Installation
Compact NS100-630z-MA
500 V
Type de coordination: 1
Coordination type: 1
DOL (Démarrage direct)
DOL (Direct On Line)
Performance de coupure / Breaking characteristics
Compact NS
H
L
NS100z-MA
50/35kA
70kA
NS160/250z-MA
50/35kA
70kA
NS400/630z-MA
50/35kA
70kA
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
0,55
1,21
0,75
1,5
1,1
2
1,5
2,6
2,2
3,8
3
5
4
6,5
5,5
9
7,5
12
9
13,9
11
18,4
15
23
18,5
28,5
22
33
30
45
37
55
45
65
55
80
75
105
90
129
110
156
132
187
160
220
200
281
220
310
250
360
315
445
355
500
Disjoncteurs
Circuit Breaker
Type
Type
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS160N/H/L-MA
NS160N/H/L-MA
NS250N/H/L-MA
NS250N/H/L-MA
NS400H/L-MA
NS400H/L-MA
NS400H/L-MA
NS630H/L-MA
NS630H/L-MA
NS630H/L-MA
TeSys
Cal (A)
Rat (A)
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
12,5
25
25
25
50
50
50
100
100
100
150
150
220
220
320
320
320
500
500
500
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
TeSys
Contacteurs
Contactor
Type
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D12
LC1-D18
LC1-D25
LC1-D32
LC1-D32
LC1-D40
LC1-D50
LC1-D65
LC1-D80
LC1-D80
LC1-D115
LC1-D150
LC1-F185
LC1-F265
LC1-F265
LC1-F330
LC1-F400
LC1-F400
LC1-F500
LC1-F500
TeSys
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LRD-06
1...1,7
LRD-06
1...1,7
LRD-07
1,6...2,5
LRD-08
2,5...4
LRD-08
2,5...4
LRD-10
4...6
LRD-12
5,5...8
LRD-14
7...10
LRD-16
9...13
LRD-21
12...18
LRD-22
16...24
LRD-22
16...24
LRD-32
23...32
LRD-3355
30...40
LRD-3357
37...50
LRD-3359
48...65
LRD-3361
55...70
LRD-3363
63...80
LRD-4367
95...120
LRD-4369
110...140
LR9-F53 71
132...220
LR9-F53 71
132...220
LR9-F73 75
200...330
LR9-F73 75
200...330
LR9-F73 79
300...500
LR9-F73 79
300...500
LR9-F73 79
300...500
LR9-F73 81
380...630
TeSys
Nb modules
Nbr of modules
Mf
Mw
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
6
9
6
9
9
9
9
12
12
15
12
15
15
15
15
15
15
15
15
**
** Impossible in Mw Type
147
Installation de l’appareillage
Switchgear Installation
3.3.1.14.
Compact NS100-630z-MA
Type de coordination: 2 - - - - - - - - - - - - - - - -DOL (Démarrage direct)
Coordination type: 2 - - - - - - - - - - - - - - - - - - -DOL (Direct On Line)
Démarrage: normal
Start-up: Normal
Compact NS100-630z-MA
400/415 V
Type de coordination: 2
Coordination type: 2
DOL (Démarrage direct)
DOL (Direct On Line)
Performance de coupure / Breaking characteristics
Compact NS
N
H
L
NS100z-MA
25kA
70kA
130kA
NS160/250z-MA
36kA
70kA
130kA
70kA
130kA
NS400/630z-MA
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
Disjoncteurs
Circuit Breaker
Type
Type
TeSys
Cal (A)
Rat (A)
TeSys
Contacteurs
Contactor
Type
Type
TeSys
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
TeSys
Nb modules
Nbr of modules
Mf
Mw
0,37
0,98
NS100-MA
2,5
LC1-D09
LRD-05
0,63…1
3
6
0,55
1,5
NS100-MA
2,5
LC1-D09
LRD-06
1…1,7
3
6
0,75
2
NS100-MA
2,5
LC1-D09
LRD-07
1,6...2,5
3
6
1,1
2,5
NS100-MA
6,3
LC1-D40
LRD-08
2,5...4
3
6
1,5
3,5
NS100-MA
6,3
LC1-D40
LRD-08
2,5...4
3
6
2,2
5
NS100-MA
6,3
LC1-D40
LRD-10
4...6
3
6
3
6,5
NS100-MA
12,5
LC1-D40
LRD-12
5,5...8
3
6
4
8,4
NS100-MA
12,5
LC1-D40
LRD-14
7...10
3
6
6
5,5
11
NS100-MA
12,5
LC1-D40
LRD-16
9...13
3
7,5
14,8
NS100-MA
25
LC1-D40
LRD-21
12...18
3
6
9
18,1
NS100-MA
25
LC1-D40
LRD-3322
17...25
3
6
11
21
NS100-MA
25
LC1-D40
LRD-3322
17...25
3
6
15
28,5
NS100-MA
50
LC1-D80
LRD-3353
23...32
3
6
18,5
35
NS100-MA
50
LC1-D80
LRD-3355
30...40
3
6
22
42
NS100-MA
50
LC1-D80
LRD-3357
37...50
3
6
30
57
NS100-MA
100
LC1-D80
LRD-3359
48...65
3
6
37
69
NS100-MA
100
LC1-D80
LRD-3363
63...80
3
6
45
81
NS100-MA
100
LC1-D115
LR9-D5367
60...100
6
9
55
100
NS160-MA
150
LC1-D150
LR9-D5369
90...150
6
9
75
135
NS160-MA
150
LC1-F150
LR9-F5369
90...150
6
9
90
165
NS250-MA
220
LC1-F185
LR9-F5371
132...220
9
9
110
200
NS250-MA
220
LC1-F225
LR9-F5371
132...220
9
9
132
240
NS400HMA
320
LC1-F265
LR9-F7375
200...330
12
12
132
240
NS400LMA
320
LC1-F265
LR9-F7375
200...330
12
15
160
285
NS400HMA
320
LC1-F330
LR9-F7375
200...330
12
12
160
285
NS400LMA
320
LC1-F330
LR9-F7375
200...330
12
15
200
352
NS630-MA
500
LC1-F400
LR9-F7379
300...500
15
15
220
388
NS630-MA
500
LC1-F500
LR9-F7379
300...500
15
15
250
437
NS630-MA
500
LC1-F500
LR9-F7379
300...500
15
15
Guide Technique V9 / V9 Technical Guide
148
Installation de l’appareillage
Switchgear Installation
Compact NS100-630z-MA
440 V
Type de coordination: 2
Coordination type: 2
DOL (Démarrage direct)
DOL (Direct On Line)
Performance de coupure / Breaking characteristics
Compact NS
N
H
L
NS100z-MA
25kA
65kA
130kA
NS160/250z-MA
35kA
65kA
130kA
65kA
130kA
NS400/630z-MA
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
Disjoncteurs
Circuit Breaker
Type
Type
TeSys
TeSys
Cal (A)
Rat (A)
Contacteurs
Contactor
Type
Type
TeSys
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
TeSys
Nb modules
Nbr of modules
Mf
Mw
0,37
0,99
NS100-MA
2.5
LC1-D09
LRD-05
0,63...1
3
6
0,55
1,36
NS100-MA
2.5
LC1-D09
LRD-06
1…1,7
3
6
0,75
1,68
NS100-MA
2.5
LC1-D09
LRD-07
1,6…2,5
3
6
1,1
2,37
NS100-MA
2.5
LC1-D09
LRD-07
1,6…2,5
3
6
1,5
3,06
NS100-MA
6.3
LC1-D40
LRD-08
2,5…4
3
6
2,2
4,42
NS100-MA
6.3
LC1-D40
LRD-10
4…6
3
6
3
5,77
NS100-MA
6.3
LC1-D40
LRD-10
4…6
3
6
4
7,9
NS100-MA
12.5
LC1-D40
LRD-12
5,5…8
3
6
5,5
10,4
NS100-MA
12.5
LC1-D40
LRD-16
9…13
3
6
7,5
13,7
NS100-MA
25
LC1-D40
LRD-21
12…18
3
6
9
16,9
NS100-MA
25
LC1-D40
LRD-21
12…18
3
6
11
20,1
NS100-MA
25
LC1-D40
LRD-3322
17..25
3
6
15
26,5
NS100-MA
50
LC1-D80
LRD-3353
23..32
3
6
18,5
32,8
NS100-MA
50
LC1-D80
LRD-3355
30...40
3
6
22
39
NS100-MA
50
LC1-D80
LRD-3357
37...50
3
6
30
51,5
NS100-MA
100
LC1-D80
LRD-3359
48...65
3
6
37
64
NS100-MA
100
LC1-D80
LRD-3359
48...65
3
6
45
76
NS100-MA
100
LC1-D80
LRD-3363
63...80
6
9
55
90
NS100-MA
100
LC1-D115
LR9-D5367
60...100
6
9
75
125
NS160-MA
150
LC1-D150
LR9-D5369
90...150
6
9
9
90
146
NS160-MA
150
LC1-F150
LR9-F5369
90...150
6
110
178
NS250-MA
220
LC1-F185
LR9-F5371
132...220
9
9
132
215
NS250-MA
220
LC1-F225
LR9-F5371
132...220
12
12
160
256
NS400HMA
320
LC1-F265
LR9-F7375
200...330
12
12
160
256
NS400LMA
320
LC1-F265
LR9-F7375
200...330
12
15
200
321
NS400HMA
320
LC1-F330
LR9-F7375
200...330
12
12
200
321
NS400LMA
320
LC1-F330
LR9-F7375
200...330
12
15
220
353
NS630-MA
500
LC1-F400
LR9-F7379
300...500
16
15
250
401
NS630-MA
500
LC1-F400
LR9-F7379
300...500
16
15
Guide Technique V9 / V9 Technical Guide
149
Installation de l’appareillage
Switchgear Installation
Compact NS100-630z-MA
500 V
Type de coordination: 2
Coordination type: 2
DOL (Démarrage direct)
DOL (Direct On Line)
Performance de coupure / Breaking characteristics
Compact NS
N
H
L
NS100z-MA
18kA
50kA
100kA
NS160/250z-MA
30kA
50kA
70kA
50kA
100kA
NS400/630z-MA
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
Disjoncteurs
Circuit Breaker
Type
Type
TeSys
Cal (A)
Rat (A)
TeSys
Contacteurs
Contactor
Type
Type
TeSys
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
TeSys
Nb modules
Nbr of modules
Mf
Mw
0,55
1,21
NS100-MA
2,5
LC1-D09
LRD-06
1…1,7
3
6
0,75
1,5
NS100-MA
2,5
LC1-D09
LRD-06
1…1,7
3
6
1,1
2
NS100-MA
2,5
LC1-D09
LRD-07
1,6…2,5
3
6
1,5
2,6
NS100-MA
6,3
LC1-D40
LRD-08
2,5…4
3
6
2,2
3,8
NS100-MA
6,3
LC1-D40
LRD-08
2,5…4
3
6
3
5
NS100-MA
6,3
LC1-D40
LRD-10
4…6
3
6
4
6,5
NS100-MA
12,5
LC1-D40
LRD-12
5,5…8
3
6
5,5
9
NS100-MA
12,5
LC1-D40
LRD-14
7...10
3
6
7,5
12
NS100-MA
12,5
LC1-D40
LRD-16
9…13
3
6
9
13,9
NS100-MA
25
LC1-D40
LRD-21
12…18
3
6
11
18,4
NS100-MA
25
LC1-D80
LRD-3322
17..25
3
6
15
23
NS100-MA
25
LC1-D80
LRD-3322
16..24
3
6
18,5
28,5
NS100-MA
50
LC1-D80
LRD-3353
23..32
3
6
22
33
NS100-MA
50
LC1-D80
LRD-3355
30...40
3
6
30
45
NS100-MA
50
LC1-D80
LRD-3357
37...50
3
6
37
55
NS100-MA
100
LC1-D80
LRD-3359
48...65
3
6
45
65
NS100-MA
100
LC1-D80
LRD-3361
55...70
3
6
55
80
NS100-MA
100
LC1-D115
LR9-D5367
60…100
6
9
75
105
NS160-MA
150
LC1-D150
LR9-D5369
90...150
6
9
90
129
NS160-MA
150
LC1-F150
LR9-F5369
90...150
6
9
110
156
NS250-MA
220
LC1-F185
LR9-F5371
132...220
9
9
132
187
NS250-MA
220
LC1-F265
LR9-F5371
132...220
12
12
160
220
NS400-MA
320
LC1-F265
LR9-F7375
200...330
12
15
200
281
NS400-MA
320
LC1-F400
LR9-F7375
200...330
15
15
220
310
NS400-MA
320
LC1-F400
LR9-F7379
300...500
15
15
250
360
NS630-MA
500
LC1-F500
LR9-F7379
300...500
16
15
315
445
NS630-MA
500
LC1-F500
LR9-F7379
300...500
16
15
355
500
NS630-MA
500
LC1-F500
LR9-F7381
380...630
16
**
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
** Impossible in Mw type
150
Installation de l’appareillage
Switchgear Installation
Compact NS100-630z-MA
3.3.1.15.
Type de coordination: 1 - - - - - - - - - - - - - - - -2 sens de marche
Coordination type: 1 - - - - - - - - - - - - - - - - - - -Reverse
Démarrage: Normal
Start-up: Normal
Compact NS100-630z-MA
400/415 V
Type de coordination: 1
Coordination type: 1
2 sens de marche
Reverse
Performance de coupure / Breaking characteristics
Compact NS
N
H
L
NS100z-MA
25kA
70kA
130kA
NS160/250z-MA
35kA
70kA
130kA
70kA
130kA
NS400/630z-MA
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
TeSys
TeSys
1,1
2,5
Disjoncteurs
Circuit Breaker
Type
Type
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
1,5
3,5
NS100N/H/L-MA
6,3
2 x LC1-D09
0,37
0,98
0,55
1,5
0,75
2
TeSys
TeSys
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LRD-05
0,63...1
LRD-06
1...1,7
LRD-07
1,6...2,5
LRD-08
2,5...4
Nb modules
Nbr of modules
Cal (A)
Rat (A)
2,5
2,5
2,5
6,3
Contacteurs
Contactor
Type
Type
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
3
6
LRD-08
3
6
2,5...4
Mf
Mw
3
6
3
6
3
6
2,2
5
NS100N/H/L-MA
6,3
2 x LC1-D09
LRD-10
4...6
3
6
3
6,5
NS100N/H/L-MA
12,5
2 x LC1-D09
LRD-12
5,5...8
3
6
4
8,4
NS100N/H/L-MA
12,5
2 x LC1-D09
LRD-14
7...10
3
6
5,5
11
NS100N/H/L-MA
12,5
2 x LC1-D12
LRD-16
9...13
3
6
7,5
14,8
NS100N/H/L-MA
25
2 x LC1-D18
LRD-21
12...18
3
6
9
18,1
NS100N/H/L-MA
25
2 x LC1-D18
LRD-22
16...24
3
6
11
21
NS100N/H/L-MA
25
2 x LC1-D25
LRD-22
16...24
3
6
15
28,5
NS100N/H/L-MA
50
2 x LC1-D32
LRD-32
23...32
3
6
6
18,5
35
NS100N/H/L-MA
50
2 x LC1-D38
LRD-35
30...38
3
22
42
NS100N/H/L-MA
50
2 x LC1-D50
LRD-3357
37...50
6
9
30
57
NS100N/H/L-MA
50
2 x LC1-D65
LRD-3359
48...65
6
9
9
37
69
NS100N/H/L-MA
100
2 x LC1-D80
LRD-3363
63...80
6
45
81
NS100N/H/L-MA
100
2 x LC1-D95
LRD-3365
80...104
6
9
55
100
NS160N/H/L-MA
150
2 x LC1-D115
LRD-33676
95...120
9
12
75
135
NS160N/H/L-MA
150
2 x LC1-D150
LRD-33696
110...140
9
12
90
165
NS250N/H/L-MA
220
2 x LC1-F185
LR9-F5371
132...220
12
**
110
200
NS250N/H/L-MA
220
2 x LC1-F225
LR9-F5371
132...220
12
**
132
240
NS400H-MA
320
2 x LC1-F265
LR9-F7375
200...330
16
**
160
285
NS400H-MA
320
2 x LC1-F330
LR9-F7375
200...330
16
**
200
352
NS630H/L-MA
500
2 x LC1-F400
LR9-F7379
300...500
16
**
220
388
NS630H/L-MA
500
2 x LC1-F400
LR9-F7379
300...500
16
**
250
437
NS630H/L-MA
500
2 x LC1-F500
LR9-F7379
300...500
16
**
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
** Impossible in Mw type
151
Installation de l’appareillage
Switchgear Installation
Compact NS100-630z-MA
440 V
Type de coordination: 1
Coordination type: 1
2 sens de marche
Reverse
Performance de coupure / Breaking characteristics
Compact NS
N
H
L
NS100z-MA
25kA
65kA
130kA
NS160/250z-MA
35kA
65kA
130kA
65kA
130kA
NS400/630z-MA
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
0,37
0,99
0,55
1,36
0,75
1,68
1,1
2,37
1,5
3,06
2,2
4,42
3
5,77
4
7,9
5,5
10,4
7,5
13,7
9
16,9
11
20,1
15
26,5
18,5
32,8
22
39
30
51,5
37
64
45
76
55
90
75
125
90
146
110
178
132
215
160
256
200
321
220
353
250
401
280
470
Disjoncteurs
Circuit Breaker
Type
Type
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS160N/H/L-MA
NS160N/H/L-MA
NS250N/H/L-MA
NS250N/H/L-MA
NS400H/L-MA
NS400H/L-MA
NS630H/L-MA
NS630H/L-MA
NS630H/L-MA
TeSys
Cal (A)
Rat (A)
2,5
2,5
2,5
2,5
6,3
6,3
12,5
12,5
12,5
25
25
25
50
50
50
50
100
100
100
150
150
220
220
320
320
500
500
500
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
TeSys
Contacteurs
Contactor
Type
Type
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D12
2 x LC1-D18
2 x LC1-D18
2 x LC1-D25
2 x LC1-D32
2 x LC1-D38
2 x LC1-D40
2 x LC1-D65
2 x LC1-D65
2 x LC1-D80
2 x LC1-D115
2 x LC1-D150
2 x LC1-F185
2 x LC1-F225
2 x LC1-F265
2 x LC1-F330
2 x LC1-F330
2 x LC1-F400
2 x LC1-F400
2 x LC1-F500
TeSys
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LRD-05
0,63...1
LRD-06
1...1,7
LRD-07
1,6...2,5
LRD-07
1,6...2,5
LRD-08
2,5...4
LRD-10
4...6
LRD-10
4...6
LRD-14
7...10
LRD-16
9...13
LRD-21
12...18
LRD-21
12...18
LRD-22
16...24
LRD-32
23...32
LRD-35
30...38
LRD-3357
37...50
LRD-3359
48...65
LRD-3359
48...65
LRD-3363
63...80
LRD-33656
80...104
LRD-33696
110...140
LR9-F5371
132...220
LR9-F5371
132...220
LR9-F5371
132...220
LR9-F7375
200...330
LR9-F7375
200...330
LR9-F7379
300...500
LR9-F7379
300...500
LR9-F7379
300...500
TeSys
Nb modules
Nbr of modules
Mf
Mw
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
6
9
6
9
6
9
6
9
9
12
9
12
12
**
12
**
12
**
16
**
16
**
16
**
16
**
16
**
** Impossible in Mw type
152
Installation de l’appareillage
Switchgear Installation
Compact NS100-630z-MA
500 V
Type de coordination: 1
Coordination type: 1
2 sens de marche
Reverse
Performance de coupure / Breaking characteristics
Compact NS
H
L
NS100z-MA
50/35kA
70kA
NS160/250z-MA
50/35kA
70kA
NS400/630z-MA
50/35kA
70kA
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
0,55
1,21
0,75
1,5
1,1
2
1,5
2,6
2,2
3,8
3
5
4
6,5
5,5
9
7,5
12
9
13,9
11
18,4
15
23
18,5
28,5
22
33
30
45
37
55
45
65
55
80
75
105
90
129
110
156
132
187
160
220
200
281
220
310
250
360
315
445
355
500
Disjoncteurs
Circuit Breaker
Type
Type
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS160N/H/L-MA
NS160N/H/L-MA
NS250N/H/L-MA
NS250N/H/L-MA
NS400H/L-MA
NS400H/L-MA
NS400H/L-MA
NS630H/L-MA
NS630H/L-MA
NS630H/L-MA
TeSys
Cal (A)
Rat (A)
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
12,5
25
25
25
50
50
50
100
100
100
150
150
220
220
320
320
320
500
500
500
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
TeSys
Contacteurs
Contactor
Type
Type
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D12
2 x LC1-D18
2 x LC1-D25
2 x LC1-D32
2 x LC1-D32
2 x LC1-D40
2 x LC1-D50
2 x LC1-D65
2 x LC1-D80
2 x LC1-D80
2 x LC1-D115
2 x LC1-D150
2 x LC1-F185
2 x LC1-F265
2 x LC1-F265
2 x LC1-F330
2 x LC1-F400
2 x LC1-F400
2 x LC1-F500
2 x LC1-F500
TeSys
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LRD-06
1...1,7
LRD-06
1...1,7
LRD-07
1,6...2,5
LRD-08
2,5...4
LRD-08
2,5...4
LRD-10
4...6
LRD-12
5,5...8
LRD-14
7...10
LRD-16
9...13
LRD-21
12...18
LRD-22
16...24
LRD-22
16...24
LRD-32
23...32
LRD-3355
30...40
LRD-3357
37...50
LRD-3359
48...65
LRD-3361
55...70
LRD-3363
63...80
LRD-33676
95...120
LRD-33696
110...140
LR9-F53 71
132...220
LR9-F53 71
132...220
LR9-F73 75
200...330
LR9-F73 75
200...330
LR9-F73 79
300...500
LR9-F73 79
300...500
LR9-F73 79
300...500
LR9-F73 81
380...630
TeSys
Nb modules
Nbr of modules
Mf
Mw
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
6
9
6
9
6
9
6
9
6
9
9
12
9
12
12
**
12
**
16
**
16
**
16
**
16
**
16
**
16
**
** Impossible in Mw type
153
Installation de l’appareillage
Switchgear Installation
3.3.1.16.
(Compact NS100-630z-MA
Type de coordination: 2 - - - - - - - - - - - - - - - -2 sens de marche
Coordination type: 2 - - - - - - - - - - - - - - - - - - -Reverse
Démarrage: normal
Start-up: Normal
Compact NS100-630z-MA
400/415 V
Type de coordination: 2
Coordination type: 2
2 sens de marche
Reverse
Performance de coupure / Breaking characteristics
Compact NS
N
H
L
NS100z-MA
25kA
70kA
130kA
NS160/250z-MA
36kA
70kA
130kA
70kA
130kA
NS400/630z-MA
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
Disjoncteurs
Circuit Breaker
Type
Type
TeSys
Cal (A)
Rat (A)
TeSys
Contacteurs
Contactor
Type
Type
TeSys
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
TeSys
Nb modules
Nbr of modules
Mf
Mw
0,37
0,98
NS100-MA
2,5
2xLC1-D09
LRD-05
0,63…1
3
6
0,55
1,5
NS100-MA
2,5
2xLC1-D09
LRD-06
1…1,7
3
6
0,75
2
NS100-MA
2,5
2xLC1-D09
LRD-07
1,6...2,5
3
6
1,1
2,5
NS100-MA
6,3
2xLC1-D40
LRD-08
2,5...4
6
9
1,5
3,5
NS100-MA
6,3
2xLC1-D40
LRD-08
2,5...4
6
9
2,2
5
NS100-MA
6,3
2xLC1-D40
LRD-10
4...6
6
9
3
6,5
NS100-MA
12,5
2xLC1-D40
LRD-12
5,5...8
6
9
4
8,4
NS100-MA
12,5
2xLC1-D40
LRD-14
7...10
6
9
5,5
11
NS100-MA
12,5
2xLC1-D40
LRD-16
9...13
6
9
7,5
14,8
NS100-MA
25
2xLC1-D40
LRD-21
12...18
6
9
9
18,1
NS100-MA
25
2xLC1-D40
LRD-3322
17...25
6
9
11
21
NS100-MA
25
2xLC1-D40
LRD-3322
17...25
6
9
15
28,5
NS100-MA
50
2xLC1-D80
LRD-3353
23...32
6
9
18,5
35
NS100-MA
50
2xLC1-D80
LRD-3355
30...40
6
9
22
42
NS100-MA
50
2xLC1-D80
LRD-3357
37...50
6
9
30
57
NS100-MA
100
2xLC1-D80
LRD-3359
48...65
6
9
37
69
NS100-MA
100
2xLC1-D80
LRD-3363
63...80
6
9
45
81
NS100-MA
100
2xLC1-D115
LR9-D5367
60...100
9
12
55
100
NS160-MA
150
2xLC1-D150
LR9-D5369
90...150
9
12
75
135
NS160-MA
150
2xLC1-F150
LR9-F5369
90...150
9
12
90
165
NS250-MA
220
2xLC1-F185
LR9-F5371
132...220
12
**
110
200
NS250-MA
220
2xLC1-F225
LR9-F5371
132...220
12
**
132
240
NS400-MA
320
2xLC1-F265
LR9-F7375
200...330
16
**
160
285
NS400-MA
320
2xLC1-F330
LR9-F7375
200...330
16
**
200
352
NS630-MA
500
2xLC1-F400
LR9-F7379
300...500
16
**
220
388
NS630-MA
500
2xLC1-F500
LR9-F7379
300...500
16
**
250
437
NS630-MA
500
2xLC1-F500
LR9-F7379
300...500
16
**
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
** Impossible in Mw type
154
Installation de l’appareillage
Switchgear Installation
Compact NS100-630z-MA
440 V
Type de coordination: 2
Coordination type: 2
2 sens de marche
Reverse
Performance de coupure / Breaking characteristics
Compact NS
N
H
L
NS100z-MA
25kA
65kA
130kA
NS160/250z-MA
35kA
NS400/630z-MA
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
65kA
130kA
65kA
130kA
TeSys
TeSys
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
TeSys
0,37
0,99
Disjoncteurs
Circuit Breaker
Type
Type
NS100-MA
2.5
2xLC1-D09
LRD-05
0,63...1
3
6
0,55
1,36
NS100-MA
2.5
2xLC1-D09
LRD-06
1…1,7
3
6
0,75
1,68
NS100-MA
2.5
2xLC1-D09
LRD-07
1,6…2,5
3
6
1,1
2,37
NS100-MA
2.5
2xLC1-D09
LRD-07
1,6…2,5
3
6
1,5
3,06
NS100-MA
6.3
2xLC1-D40
LRD-08
2,5…4
6
9
2,2
4,42
NS100-MA
6.3
2xLC1-D40
LRD-10
4…6
6
9
3
5,77
NS100-MA
6.3
2xLC1-D40
LRD-10
4…6
6
9
Cal (A)
Rat (A)
Contacteurs
Contactor
Type
Type
TeSys
Nb modules
Nbr of modules
Mf
Mw
4
7,9
NS100-MA
12.5
2xLC1-D40
LRD-12
5,5…8
6
9
5,5
10,4
NS100-MA
12.5
2xLC1-D40
LRD-16
9…13
6
9
7,5
13,7
NS100-MA
25
2xLC1-D40
LRD-21
12…18
6
9
9
16,9
NS100-MA
25
2xLC1-D40
LRD-21
12…18
6
9
11
20,1
NS100-MA
25
2xLC1-D40
LRD-3322
17..25
6
9
15
26,5
NS100-MA
50
2xLC1-D80
LRD-3353
23..32
6
9
18,5
32,8
NS100-MA
50
2xLC1-D80
LRD-3355
30...40
6
9
22
39
NS100-MA
50
2xLC1-D80
LRD-3357
37...50
6
9
30
51,5
NS100-MA
100
2xLC1-D80
LRD-3359
48...65
6
9
37
64
NS100-MA
100
2xLC1-D80
LRD-3359
48...65
6
9
45
76
NS100-MA
100
2xLC1-D80
LRD-3363
63...80
9
12
55
90
NS100-MA
100
2xLC1-D115
LR9-D5367
60...100
9
12
75
125
NS160-MA
150
2xLC1-D150
LR9-D5369
90...150
9
12
90
146
NS160-MA
150
2xLC1-F150
LR9-F5369
90...150
12
**
110
178
NS250-MA
220
2xLC1-F185
LR9-F5371
132...220
12
**
132
215
NS250-MA
220
2xLC1-F225
LR9-F5371
132...220
12
**
160
256
NS400-MA
320
2xLC1-F265
LR9-F7375
200...330
16
**
200
321
NS400-MA
320
2xLC1-F330
LR9-F7375
200...330
16
**
220
353
NS630-MA
500
2xLC1-F400
LR9-F7379
300...500
16
**
250
401
NS630-MA
500
2xLC1-F400
LR9-F7379
300...500
16
**
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
** Impossible in Mw type
155
Installation de l’appareillage
Switchgear Installation
Compact NS100-630z-MA
500 V
Type de coordination: 2
Coordination type: 2
2 sens de marche
Reverse
Performance de coupure / Breaking characteristics
Compact NS
N
H
L
NS100z-MA
18kA
50kA
100kA
NS160/250z-MA
30kA
50kA
70kA
50kA
100kA
NS400/630z-MA
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
Disjoncteurs
Circuit Breaker
Type
Type
TeSys
Cal (A)
Rat (A)
TeSys
Contacteurs
Contactor
Type
Type
TeSys
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
TeSys
Nb modules
Nbr of modules
Mf
Mw
0,55
1,21
NS100-MA
2,5
2xLC1-D09
LRD-06
1…1,7
3
6
0,75
1,5
NS100-MA
2,5
2xLC1-D09
LRD-06
1…1,7
3
6
1,1
2
NS100-MA
2,5
2xLC1-D09
LRD-07
1,6…2,5
3
6
1,5
2,6
NS100-MA
6,3
2xLC1-D40
LRD-08
2,5…4
6
9
2,2
3,8
NS100-MA
6,3
2xLC1-D40
LRD-08
2,5…4
6
9
3
5
NS100-MA
6,3
2xLC1-D40
LRD-10
4…6
6
9
4
6,5
NS100-MA
12,5
2xLC1-D40
LRD-12
5,5…8
6
9
9
5,5
9
NS100-MA
12,5
2xLC1-D40
LRD-14
7...10
6
7,5
12
NS100-MA
12,5
2xLC1-D40
LRD-16
9…13
6
9
9
13,9
NS100-MA
25
2xLC1-D40
LRD-21
12…18
6
9
11
18,4
NS100-MA
25
2xLC1-D80
LRD-3322
17..25
6
9
9
15
23
NS100-MA
25
2xLC1-D80
LRD-3322
16..24
6
18,5
28,5
NS100-MA
50
2xLC1-D80
LRD-3353
23..32
6
9
22
33
NS100-MA
50
2xLC1-D80
LRD-3355
30...40
6
9
30
45
NS100-MA
50
2xLC1-D80
LRD-3357
37...50
6
9
37
55
NS100-MA
100
2xLC1-D80
LRD-3359
48...65
6
9
45
65
NS100-MA
100
2xLC1-D80
LRD-3361
55...70
6
9
55
80
NS100-MA
100
2xLC1-D115
LR9-D5367
60…100
9
12
75
105
NS160-MA
150
2xLC1-D150
LR9-D5369
90...150
9
12
90
129
NS160-MA
150
2xLC1-F150
LR9-F5369
90...150
9
**
110
156
NS250-MA
220
2xLC1-F185
LR9-F5371
132...220
12
**
132
187
NS250-MA
220
2xLC1-F265
LR9-F5371
132...220
12
**
160
220
NS400-MA
320
2xLC1-F265
LR9-F7375
200...330
16
**
200
281
NS400-MA
320
2xLC1-F400
LR9-F7375
200...330
16
**
220
310
NS400-MA
320
2xLC1-F400
LR9-F7379
300...500
16
**
250
360
NS630-MA
500
2xLC1-F500
LR9-F7379
300...500
16
**
315
445
NS630-MA
500
2xLC1-F500
LR9-F7379
300...500
16
**
355
500
NS630-MA
500
2xLC1-F500
LR9-F7381
380...630
16
**
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
** Impossible in Mw type
156
Installation de l’appareillage
Switchgear Installation
Compact NS100-630z-MA
3.3.1.17.
Type de coordination: 1 - - - - - - - - - - - - - - - -Etoile / Triangle (Y/∆)
Coordination type: 1 - - - - - - - - - - - - - - - - - - -STAR / DELTA (Y/∆)
Démarrage: Normal
Start-up: Normal
Compact NS100-630z-MA
400/415 V
Type de coordination: 1
Coordination type: 1
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Performance de coupure / Breaking characteristics
Compact NS
N
H
L
NS100z-MA
25kA
70kA
130kA
NS160/250z-MA
35kA
70kA
130kA
70kA
130kA
NS400/630z-MA
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
0,37
0,98
0,55
1,5
0,75
2
1,1
2,5
1,5
3,5
2,2
5
3
6,5
4
8,4
5,5
11
7,5
14,8
9
18,1
11
21
15
28,5
18,5
35
22
42
30
57
37
69
45
81
55
100
75
135
90
165
110
200
132
240
160
285
200
352
220
388
250
437
Disjoncteurs
Circuit Breaker
Type
Type
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS160N/H/L-MA
NS250N/H/L-MA
NS250N/H/L-MA
NS400H/L-MA
NS400H/L-MA
NS630H/L-MA
NS630H/L-MA
NS630H/L-MA
TeSys
Cal (A)
Rat (A)
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
12,5
25
25
25
50
50
50
100
100
100
100
150
220
220
320
320
500
500
500
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
TeSys
Contacteurs
Contactor
Type
Type
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D12
3 x LC1-D12
3 x LC1-D18
3 x LC1-D18
3 x LC1-D32
3 x LC1-D32
3 x LC1-D40
3 x LC1-D50
3 x LC1-D50
3 x LC1-D80
3 x LC1-D115
3 x LC1-D115
3 x LC1-D150
3 x LC1-F185
3 x LC1-F225
3 x LC1-F265
3 x LC1-F330
TeSys
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LRD-04
0,40...0,63
LRD-05
0,63...1
LRD-06
1...1,7
LRD-06
1...1,7
LRD-07
1,6...2,5
LRD-08
2,5...4
LRD-08
2,5...4
LRD-10
4...6
LRD-12
5,5...8
LRD-14
7...10
LRD-16
9...13
LRD-16
9...13
LRD-21
12...18
LRD-22
16...24
LRD-32
23...32
LRD-35
30...38
LRD-3359
48...65
LRD-3357
37...50
LRD-3361
55...70
LRD-3363
63...80
LRD-4365
80...104
LRD-4369
110...140
LRD-4369
110...140
LR9-F5371
132...220
LR9-F5371
132...220
LR9-F7375
200...330
LR9-F7375
200...330
TeSys
Nb modules
Nbr of modules
Mf
Mw
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
9
6
9
6
9
6
9
12
**
12
**
12
**
16
**
16
**
20
**
20
**
** Impossible in Mw type
157
Installation de l’appareillage
Switchgear Installation
Compact NS100-630z-MA
440 V
Type de coordination: 1
Coordination type: 1
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Performance de coupure / Breaking characteristics
Compact NS
N
H
L
NS100z-MA
25kA
65kA
130kA
NS160/250z-MA
35kA
65kA
130kA
65kA
130kA
NS400/630z-MA
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
0,37
0,99
0,55
1,36
0,75
1,68
1,1
2,37
1,5
3,06
2,2
4,42
3
5,77
4
7,9
5,5
10,4
7,5
13,7
9
16,9
11
20,1
15
26,5
18,5
32,8
22
39
30
51,5
37
64
45
76
55
90
75
125
90
146
110
178
132
215
160
256
200
321
220
353
250
401
Disjoncteurs
Circuit Breaker
Type
Type
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS160N/H/L-MA
NS160N/H/L-MA
NS250N/H/L-MA
NS250N/H/L-MA
NS400H/L-MA
NS630H/L-MA
NS630H/L-MA
NS630H/L-MA
TeSys
Cal (A)
Rat (A)
2,5
2,5
2,5
2,5
6,3
6,3
12,5
12,5
12,5
25
25
25
50
50
50
50
100
100
100
150
150
220
220
320
500
500
500
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
TeSys
Contacteurs
Contactor
Type
Type
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D12
3 x LC1-D12
3 x LC1-D18
3 x LC1-D18
3 x LC1-D18
3 x LC1-D32
3 x LC1-D40
3 x LC1-D40
3 x LC1-D50
3 x LC1-D80
3 x LC1-D115
3 x LC1-D115
3 x LC1-D150
3 x LC1-D150
3 x LC1-F225
3 x LC1-F225
3 x LC1-F265
TeSys
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LRD-05
0,63...1
LRD-06
1...1,7
LRD-07
1,6...2,5
LRD-07
1,6...2,5
LRD-07
1,6...2,5
LRD-08
2,5...4
LRD-08
2,5...4
LRD-10
4...6
LRD-12
5,5...8
LRD-14
7...10
LRD-16
9...13
LRD-16
9...13
LRD-21
12...18
LRD-22
16...24
LRD-22
16...24
LRD-32
23...32
LRD-3355
30...40
LRD-3357
37...50
LRD-3359
48...65
LRD-3363
63...80
LRD-4365
80...104
LRD-4365
80...104
LRD-4369
110...140
LR9-D5369
90...150
LR9-F5371
132...220
LR9-F5371
132...220
LR9-F7375
200...330
TeSys
Nb modules
Nbr of modules
Mf
Mw
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
9
6
9
6
9
6
9
12
**
12
**
12
**
12
**
16
**
16
**
20
**
** Impossible in Mw type
158
Installation de l’appareillage
Switchgear Installation
3.3.1.18.
Compact NS100-630z-MA
Type de coordination: 2 - - - - - - - - - - - - - - - -Etoile / Triangle (Y/∆)
Coordination Type: 2 - - - - - - - - - - - - - - - - - -STAR / DELTA (Y/∆)
Démarrage: normal
Start-up: Normal
Compact NS100-630z-MA
400/415 V
Type de coordination: 2
Coordination type: 2
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Performance de coupure / Breaking characteristics
Compact NS
N
H
L
NS100z-MA
25kA
70kA
130kA
NS160/250z-MA
35kA
70kA
130kA
70kA
130kA
NS400/630z-MA
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
Disjoncteurs
Circuit Breaker
Type
Type
TeSys
TeSys
Cal (A)
Rat (A)
Contacteurs
Contactor
Type
Type
TeSys
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
TeSys
Nb modules
Nbr of modules
Mf
Mw
1,5
3,5
NS100-MA
6,3
3 x LC1-D40
LRD-08
2,5...4
6
9
2,2
5
NS100-MA
6,3
3 x LC1-D40
LRD-10
4...6
6
9
3
6,5
NS100-MA
12,5
3 x LC1-D40
LRD-12
5,5...8
6
9
4
8,4
NS100-MA
12,5
3 x LC1-D40
LRD-14
7...10
6
9
5,5
11
NS100-MA
12,5
3 x LC1-D40
LRD-16
9...13
6
9
7,5
14,8
NS100-MA
25
3 x LC1-D40
LRD-21
12...18
6
9
9
18,1
NS100-MA
25
3 x LC1-D40
LRD-3322
17...25
6
9
11
21
NS100-MA
25
3 x LC1-D40
LRD-3322
17...25
6
9
15
28,5
NS100-MA
50
3 x LC1-D80
LRD-3353
23...32
6
9
18,5
35
NS100-MA
50
3 x LC1-D80
LRD-3355
30...40
6
9
22
42
NS100-MA
50
3 x LC1-D80
LRD-3357
37...50
6
9
30
57
NS100-MA
100
3 x LC1-D80
LRD-3359
48...65
6
9
37
69
NS100-MA
100
3 x LC1-D80
LRD-3363
63...80
6
9
45
81
NS100-MA
100
3 x LC1-D115
LR9-D5367
60...100
12
**
55
100
NS160-MA
150
3 x LC1-D150
LR9-D5369
90...150
12
**
75
135
NS160-MA
150
3 x LC1-F150
LR9-F5369
90...150
12
**
90
165
NS250-MA
220
3 x LC1-F185
LR9-F5371
132...220
16
**
110
200
NS250-MA
220
3 x LC1-F225
LR9-F5371
132...220
16
**
132
240
NS400-MA
320
3 x LC1-F265
LR9-F7375
200...330
20
**
160
285
NS400-MA
320
3 x LC1-F330
LR9-F7375
200...330
20
200
352
NS630-MA
500
3 x LC1-F400
LR9-F7379
200...330
**
**
**
220
388
NS630-MA
500
3 x LC1-F400
LR9-F7379
200...330
**
**
250
437
NS630-MA
500
3 x LC1-F500
LR9-F7379
300...500
**
**
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
** Impossible in Mw type
159
Installation de l’appareillage
Switchgear Installation
Compact NS100-630z-MA
440 V
Type de coordination: 2
Coordination type: 2
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Performance de coupure / Breaking characteristics
Compact NS
N
H
L
NS100z-MA
25kA
65kA
130kA
NS160/250z-MA
35kA
65kA
130kA
65kA
130kA
NS400/630z-MA
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
1,5
3,06
Disjoncteurs
Circuit Breaker
Type
Type
NS100-MA
TeSys
TeSys
Cal (A)
Rat (A)
Contacteurs
Contactor
Type
Type
6.3
3 x LC1-D40
TeSys
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LRD-08
4…6
TeSys
Nb modules
Nbr of modules
Mf
Mw
6
9
2,2
4,42
NS100-MA
6.3
3 x LC1-D40
LRD-10
4…6
6
9
3
5,77
NS100-MA
6.3
3 x LC1-D40
LRD-10
4…6
6
9
4
7,9
NS100-MA
12.5
3 x LC1-D40
LRD-12
7…10
6
9
5,5
10,4
NS100-MA
12.5
3 x LC1-D40
LRD-16
9…13
6
9
7,5
13,7
NS100-MA
25
3 x LC1-D40
LRD-21
12…18
6
9
9
16,9
NS100-MA
25
3 x LC1-D40
LRD-3322
12…18
6
9
11
20,1
NS100-MA
25
3 x LC1-D40
LRD-3322
16..24
6
9
15
26,5
NS100-MA
50
3 x LC1-D80
LRD-3353
16..24
6
9
18,5
32,8
NS100-MA
50
3 x LC1-D80
LRD-3355
30...40
6
9
22
39
NS100-MA
50
3 x LC1-D80
LRD-3355
37...50
6
9
30
51,5
NS100-MA
100
3 x LC1-D80
LRD-3359
48...65
6
9
37
64
NS100-MA
100
3 x LC1-D80
LRD-3359
48...65
6
9
45
76
100
100
3 x LC1-D80
LRD-3363
63...80
12
**
**
55
90
NS100-MA
NS100-MA
3 x LC1-D115
LR9-D5367
60...100
12
75
125
NS160-MA
150
3 x LC1-D150
LR9-D5369
90...150
12
**
90
146
NS160-MA
150
3 x LC1-F150
LR9-F5369
90...150
12
**
110
178
NS250-MA
220
3 x LC1-F185
LR9-F5371
132...220
16
**
132
215
NS250-MA
220
3 x LC1-F225
LR9-F5371
132...220
16
**
160
256
NS400-MA
320
3 x LC1-F265
LR9-F7375
200...330
20
**
200
321
NS400-MA
320
3 x LC1-F330
LR9-F7375
200...330
20
**
220
353
NS630-MA
500
3 x LC1-F400
LR9-F7379
200...330
20
**
250
401
NS630-MA
500
3 x LC1-F400
LR9-F7379
200...330
**
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
** Impossible in Mw type
160
Installation de l’appareillage
Switchgear Installation
3.3.1.19.
GV7
Type de coordination: 1 - - - - - - - - - - - - - - - -DOL (Démarrage direct)
Coordination Type: 1 - - - - - - - - - - - - - - - - - -DOL (Direct On Line)
400/415 V
TeSys
GV7
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
15
28,5
18.5
35
22
42
30
57
37
69
45
81
55
100
75
135
90
165
110
200
Pdc
BC
Icu (kA)
Rms (kA)
25
25
25
25
25
25
25
35
35
35
Type de coordination: 1
Coordination type: 1
TeSys
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE40
25...40
GV7-RE40
25...40
GV7-RE50
30...50
GV7-RE80
48...80
GV7-RE80
48...80
GV7-RE100
60...100
GV7-RE150
90...150
GV7-RE150
90...150
GV7-RE220
132...220
GV7-RE220
132...220
GV7
440 V
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
15
26,5
18.5
32,8
22
39
30
51,5
37
64
45
76
55
90
75
125
90
146
110
178
132
215
Pdc
BC
Icu (kA)
Rms (kA)
25
25
25
25
25
25
25
35
35
35
35
Guide Technique V9 / V9 Technical Guide
TeSys
DOL (Démarrage direct)
DOL (Direct On Line)
TeSys
Nb modules
Nbr of modules
Contacteur
Contactor
LC1-D32
LC1-D38
LC1-D50
LC1-D65
LC1-D80
LC1-D95
LC1-D115
LC1-D150
LC1-F185
LC1-F225
Mf
Mw
3
3
3
3
3
3
3
3
3
3
3
3
6
6
6
6
9
9
9
9
Type de coordination: 1
Coordination type: 1
TeSys
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE40
25...40
GV7-RE40
25...40
GV7-RE50
30...50
GV7-RE80
48...80
GV7-RE80
48...80
GV7-RE80
48...80
GV7-RE100
60...100
GV7-RE150
90...150
GV7-RE150
90...150
GV7-RE220
132...220
GV7-RE220
132...220
TeSys
DOL (Démarrage direct)
DOL (Direct On Line)
TeSys
Nb modules
Nbr of modules
Contacteur
Contactor
LC1-D32
LC1-D38
LC1-D40
LC1-D65
LC1-D65
LC1-D80
LC1-D115
LC1-D150
LC1-F185
LC1-F225
LC1-F225
Mf
Mw
3
3
3
3
3
3
3
3
3
3
3
3
6
6
6
6
9
9
9
9
9
9
161
Installation de l’appareillage
Switchgear Installation
GV7
500 V
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
18.5
28,5
22
33
30
45
45
65
55
80
75
105
90
129
110
156
132
187
160
220
Pdc
BC
Icu (kA)
Rms (kA)
18
18
18
18
18
30
30
30
30
30
Guide Technique V9 / V9 Technical Guide
Type de coordination: 1
Coordination type: 1
TeSys
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE40
25...40
GV7-RE50
30...50
GV7-RE50
30...50
GV7-RE80
48...80
GV7-RE80
48...80
GV7-RE150
90...150
GV7-RE150
90...150
GV7-RE220
132...220
GV7-RE220
132...220
GV7-RE220
132...220
TeSys
DOL (Démarrage direct)
DOL (Direct On Line)
TeSys
Nb modules
Nbr of modules
Contacteur
Contactor
LC1-D38
LC1-D40
LC1-D50
LC1-D65
LC1-D80
LC1-D115
LC1-D150
LC1-F185
LC1-F265
LC1-F265
Mf
Mw
3
3
3
3
3
3
3
3
3
3
6
6
6
6
9
9
9
9
9
9
162
Installation de l’appareillage
Switchgear Installation
3.3.1.20.
GV7
Type de coordination: 2 - - - - - - - - - - - - - - - -DOL (Démarrage direct)
Coordination Type: 2 - - - - - - - - - - - - - - - - - -DOL (Direct On Line)
400/415 V
TeSys
GV7
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
15
28,5
18,5
35
22
42
30
57
37
69
45
81
55
100
75
135
90
165
110
200
Pdc
BC
Icu (kA)
Rms (kA)
70
70
70
70
70
70
70
70
70
70
Type de coordination: 2
Coordination type: 2
TeSys
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RS40
25…40
GV7-RS40
25…40
GV7-RS50
30…50
GV7-RS80
48…80
GV7-RS80
48…80
GV7-RS100
60…100
GV7-RS150
90…150
GV7-RS150
90…150
GV7-RS220
132…220
GV7-RS220
132…220
GV7
440 V
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
15
26,5
18,5
32,8
22
39
30
51,5
37
64
45
76
55
90
75
125
90
146
110
178
132
215
Pdc
BC
Icu (kA)
Rms (kA)
65
65
65
65
65
65
65
65
65
65
65
Guide Technique V9 / V9 Technical Guide
TeSys
DOL (Démarrage direct)
DOL (Direct On Line)
TeSys
Nb modules
Nbr of modules
Contacteur
Contactor
LC1-D40
LC1-D50
LC1-D80
LC1-D80
LC1-D80
LC1-D115
LC1-D150
LC1-F150
LC1-F185
LC1-F225
Mf
Mw
3
3
3
3
3
3
3
3
3
3
6
6
6
6
6
6
9
9
9
9
Type de coordination: 2
Coordination type: 2
TeSys
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RS40
25...40
GV7-RS40
25...40
GV7-RS40
25...40
GV7-RS80
48...80
GV7-RS80
48...80
GV7-RS80
48...80
GV7-RS100
60...100
GV7-RS150
90...150
GV7-RS150
90...150
GV7-RS220
132...220
GV7-RS220
132...220
TeSys
DOL (Démarrage direct)
DOL (Direct On Line)
TeSys
Nb modules
Nbr of modules
Contacteur
Contactor
LC1-D40
LC1-D50
LC1-D80
LC1-D80
LC1-D80
LC1-D115
LC1-D115
LC1-D150
LC1-F150
LC1-F185
LC1-F225
Mf
Mw
3
3
3
3
3
3
3
3
3
3
6
6
6
6
6
6
9
9
9
9
9
9
163
Installation de l’appareillage
Switchgear Installation
GV7
500 V
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
18,5
28,5
22
33
30
45
37
55
45
65
55
80
90
129
110
156
132
187
160
220
Pdc
BC
Icu (kA)
Rms (kA)
50
50
50
50
50
50
50
50
50
50
Guide Technique V9 / V9 Technical Guide
Type de coordination: 2
Coordination type: 2
TeSys
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RS40
25…40
GV7-RS40
25…40
GV7-RS50
30…50
GV7-RS80
48…80
GV7-RS80
48…80
GV7-RS80
48…80
GV7-RS150
90…150
GV7-RS220
132...220
GV7-RS220
132…220
GV7-RS220
132…220
TeSys
DOL (Démarrage direct)
DOL (Direct On Line)
TeSys
Nb modules
Nbr of modules
Contacteur
Contactor
LC1-D40
LC1-D50
LC1-D80
LC1-D80
LC1-D115
LC1-D115
LC1-D150
LC1-F185
LC1-F265
LC1-F265
Mf
Mw
3
3
3
3
3
3
3
3
6
6
6
6
6
6
9
9
9
9
9
9
164
Installation de l’appareillage
Switchgear Installation
3.3.1.21.
GV7
Type de coordination: 1 - - - - - - - - - - - - - - - -2 sens de marche
Coordination Type: 1 - - - - - - - - - - - - - - - - - -Reverse
400/415 V
TeSys
GV7
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
15
28,5
18.5
35
22
42
30
57
37
69
45
81
55
100
75
135
90
165
110
200
Pdc
BC
Icu (kA)
Rms (kA)
25
25
25
25
25
25
25
35
35
35
Type de coordination: 1
Coordination type: 1
TeSys
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE40
25...40
GV7-RE40
25...40
GV7-RE50
30...50
GV7-RE80
48...80
GV7-RE80
48...80
GV7-RE100
60...100
GV7-RE150
90...150
GV7-RE150
90...150
GV7-RE220
132...220
GV7-RE220
132...220
TeSys
GV7
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
15
26,5
18.5
32,8
22
39
30
51,5
37
64
45
76
55
90
75
125
90
146
110
178
132
215
Pdc
BC
Icu (kA)
Rms (kA)
25
25
25
25
25
25
25
35
35
35
35
Contacteur
Contactor
2 x LC1-D32
2 x LC1-D38
2 x LC1-D50
2 x LC1-D65
2 x LC1-D80
2 x LC1-D95
2 x LC1-D115
2 x LC1-D150
2 x LC1-F185
2 x LC1-F225
Mf
Mw
6
6
6
6
6
6
6
6
6
6
6
6
9
12
9
12
12
**
12
**
** Impossible in Mw type
Type de coordination: 1
Coordination type: 1
TeSys
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE40
25...40
GV7-RE40
25...40
GV7-RE50
30...50
GV7-RE80
48...80
GV7-RE80
48...80
GV7-RE80
48...80
GV7-RE100
60...100
GV7-RE150
90...150
GV7-RE150
90...150
GV7-RE220
132...220
GV7-RE220
132...220
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
TeSys
Nb modules
Nbr of modules
** Impossible en type Mw
440 V
2 sens de marche
Reverse
TeSys
2 sens de marche
Reverse
TeSys
Nb modules
Nbr of modules
Contacteur
Contactor
2 x LC1-D32
2 x LC1-D38
2 x LC1-D40
2 x LC1-D65
2 x LC1-D65
2 x LC1-D80
2 x LC1-D115
2 x LC1-D150
2 x LC1-F185
2 x LC1-F225
2 x LC1-F225
Mf
Mw
6
6
6
6
6
6
6
6
6
6
6
6
9
12
9
12
12
**
12
**
12
**
** Impossible in Mw type
165
Installation de l’appareillage
Switchgear Installation
GV7
500 V
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
18.5
28,5
22
33
30
45
45
65
55
80
75
105
90
129
110
156
132
187
160
220
Pdc
BC
Icu (kA)
Rms (kA)
18
18
18
18
18
30
30
30
30
30
Type de coordination: 1
Coordination type: 1
TeSys
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE40
25...40
GV7-RE50
30...50
GV7-RE50
30...50
GV7-RE80
48...80
GV7-RE80
48...80
GV7-RE150
90...150
GV7-RE150
90...150
GV7-RE220
132...220
GV7-RE220
132...220
GV7-RE220
132...220
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
TeSys
2 sens de marche
Reverse
TeSys
Nb modules
Nbr of modules
Contacteur
Contactor
2 x LC1-D38
2 x LC1-D40
2 x LC1-D50
2 x LC1-D65
2 x LC1-D80
2 x LC1-D115
2 x LC1-D150
2 x LC1-F185
2 x LC1-F265
2 x LC1-F265
Mf
Mw
6
6
6
6
6
6
6
6
6
6
9
12
9
12
12
**
12
**
12
**
** Impossible in Mw type
166
Installation de l’appareillage
Switchgear Installation
3.3.1.22.
GV7
Type de coordination: 2 - - - - - - - - - - - - - - - -2 sens de marche
Coordination Type: 2 - - - - - - - - - - - - - - - - - -Reverse
400/415 V
TeSys
GV7
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
15
28,5
18,5
35
22
42
30
57
37
69
45
81
55
100
75
135
90
165
110
200
Pdc
BC
Icu (kA)
Rms (kA)
70
70
70
70
70
70
70
70
70
70
Type de coordination: 2
Coordination type: 2
TeSys
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RS40
25…40
GV7-RS40
25…40
GV7-RS50
30…50
GV7-RS80
48…80
GV7-RS80
48…80
GV7-RS100
60…100
GV7-RS150
90…150
GV7-RS150
90…150
GV7-RS220
132…220
GV7-RS220
132…220
TeSys
GV7
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
15
26,5
18,5
32,8
22
39
30
51,5
37
64
45
76
55
90
75
125
90
146
110
178
132
215
Pdc
BC
Icu (kA)
Rms (kA)
65
65
65
65
65
65
65
65
65
65
65
Contacteur
Contactor
2xLC1-D40
2xLC1-D50
2xLC1-D80
2xLC1-D80
2xLC1-D80
2xLC1-D115
2xLC1-D150
2xLC1-F150
2xLC1-F185
2xLC1-F225
Mf
Mw
6
6
6
6
6
6
6
6
6
6
9
12
9
12
9
**
12
**
12
**
** Impossible in Mw type
Type de coordination: 2
Coordination type: 2
TeSys
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RS40
25...40
GV7-RS40
25...40
GV7-RS40
25...40
GV7-RS80
48...80
GV7-RS80
48...80
GV7-RS80
48...80
GV7-RS100
60...100
GV7-RS150
90...150
GV7-RS150
90...150
GV7-RS220
132...220
GV7-RS220
132...220
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
TeSys
Nb modules
Nbr of modules
** Impossible en type Mw
440 V
2 sens de marche
Reverse
TeSys
2 sens de marche
Reverse
TeSys
Nb modules
Nbr of modules
Contacteur
Contactor
2xLC1-D40
2xLC1-D50
2xLC1-D80
2xLC1-D80
2xLC1-D80
2xLC1-D115
2xLC1-D115
2xLC1-D150
2xLC1-F150
2xLC1-F185
2xLC1-F225
Mf
Mw
6
6
6
6
6
6
6
6
6
6
9
12
9
12
9
12
12
**
12
**
12
**
** Impossible in Mw type
167
Installation de l’appareillage
Switchgear Installation
GV7
500 V
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
Pdc
BC
Icu (kA)
Rms (kA)
Type de coordination: 2
Coordination type: 2
TeSys
TeSys
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
2 sens de marche
Reverse
TeSys
Nb modules
Nbr of modules
Contacteur
Contactor
Mf
Mw
18,5
28,5
50
GV7-RS40
25…40
2xLC1-D40
6
6
22
33
50
GV7-RS40
25…40
2xLC1-D50
6
6
30
45
50
GV7-RS50
30…50
2xLC1-D80
6
6
37
55
50
GV7-RS80
48…80
2xLC1-D80
6
6
45
65
50
GV7-RS80
48…80
2xLC1-D115
9
12
55
80
50
GV7-RS80
48…80
2xLC1-D115
9
12
90
129
50
GV7-RS150
90…150
2xLC1-D150
9
12
110
156
50
GV7-RS220
132...220
2xLC1-F185
12
**
132
187
50
GV7-RS220
132…220
2xLC1-F265
12
**
160
220
50
GV7-RS220
132…220
2xLC1-F265
12
**
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
** Impossible in Mw type
168
Installation de l’appareillage
Switchgear Installation
3.3.1.23.
GV7
Type de coordination: 1 - - - - - - - - - - - - - - - -Etoile / Triangle (Y/∆)
Coordination Type: 1 - - - - - - - - - - - - - - - - - -STAR / DELTA (Y/∆)
Démarrage: Normal
Start-up: Normal
400/415 V
TeSys
GV7
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
15
28,5
18,5
35
22
42
30
57
37
69
45
81
55
100
75
135
90
165
110
200
Pdc
BC
Icu (kA)
Rms (kA)
25
25
25
25
25
25
25
35
35
35
TeSys
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE40
25...40
GV7-RE40
25...40
GV7-RE50
30...50
GV7-RE80
48...80
GV7-RE80
48...80
GV7-RE100
60...100
GV7-RE100
60...100
GV7-RE150
90...150
GV7-RE220
132...220
GV7-RE220
132...220
TeSys
GV7
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
15
26,5
18,5
32,8
22
39
30
51,5
37
64
45
76
55
90
75
125
90
146
110
178
132
215
Pdc
BC
Icu (kA)
Rms (kA)
25
25
25
25
25
25
25
35
35
35
35
Contacteur
Contactor
3 x LC1-D18
3 x LC1-D18
3 x LC1-D32
3 x LC1-D32
3 x LC1-D40
3 x LC1-D50
3 x LC1-D50
3 x LC1-D80
3 x LC1-D115
3 x LC1-D115
Mf
Mw
6
6
6
6
6
6
6
6
6
9
6
9
6
9
6
9
12
**
12
**
** Impossible in Mw type
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Type de coordination: 1
Coordination type: 1
TeSys
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE40
25...40
GV7-RE40
25...40
GV7-RE50
30...50
GV7-RE80
48...80
GV7-RE80
48...80
GV7-RE80
48...80
GV7-RE100
60...100
GV7-RE150
90...150
GV7-RE150
90...150
GV7-RE220
132...220
GV7-RE220
132...220
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
TeSys
Nb modules
Nbr of modules
** Impossible en type Mw
440 V
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Type de coordination: 1
Coordination type: 1
TeSys
TeSys
Nb modules
Nbr of modules
Contacteur
Contactor
3 x LC1-D18
3 x LC1-D18
3 x LC1-D18
3 x LC1-D32
3 x LC1-D40
3 x LC1-D50
3 x LC1-D50
3 x LC1-D80
3 x LC1-D115
3 x LC1-D115
3 x LC1-D150
Mf
Mw
6
6
6
6
6
6
6
6
6
9
6
9
6
9
6
9
12
**
12
**
12
**
** Impossible in Mw type
169
Installation de l’appareillage
Switchgear Installation
3.3.1.24.
GV7
Type de coordination: 2 - - - - - - - - - - - - - - - -Etoile / Triangle (Y/∆)
Coordination Type: 2 - - - - - - - - - - - - - - - - - -STAR / DELTA (Y/∆)
Démarrage: Normal
Start-up: Normal
400/415 V
TeSys
GV7
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
15
28,5
18,5
35
22
42
30
57
37
69
45
81
55
100
75
135
90
165
110
200
Pdc
BC
Icu (kA)
Rms (kA)
70
70
70
70
70
70
70
70
70
70
TeSys
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RS40
25...40
GV7-RS40
25...40
GV7-RS50
30...50
GV7-RS80
48...80
GV7-RS80
48...80
GV7-RS100
60...100
GV7-RS100
60...100
GV7-RS150
90...150
GV7-RS220
132...220
GV7-RS220
132...220
TeSys
GV7
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
15
26,5
18,5
32,8
22
39
30
51,5
37
64
45
76
55
90
75
125
90
146
110
178
132
215
Pdc
BC
Icu (kA)
Rms (kA)
65
65
65
65
65
65
65
65
65
65
65
Contacteur
Contactor
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D115
3 x LC1-D150
3 x LC1-F150
3 x LC1-F185
3 x LC1-F225
Mf
Mw
6
9
6
9
6
9
6
9
6
9
12
**
12
**
12
**
16
**
16
**
** Impossible in Mw type
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Type de coordination: 2
Coordination type: 2
TeSys
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RS40
25...40
GV7-RS40
25...40
GV7-RS40
25...40
GV7-RS80
48...80
GV7-RS80
48...80
GV7-RS80
48...80
GV7-RS100
60...100
GV7-RS150
90...150
GV7-RS150
90...150
GV7-RS220
132...220
GV7-RS220
132...220
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
TeSys
Nb modules
Nbr of modules
** Impossible en type Mw
440 V
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Type de coordination: 2
Coordination type: 2
TeSys
TeSys
Nb modules
Nbr of modules
Contacteur
Contactor
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D115
3 x LC1-D115
3 x LC1-D150
3 x LC1-F150
3 x LC1-F185
3 x LC1-F225
Mf
Mw
6
9
6
9
6
9
6
9
6
9
6
**
12
**
12
**
12
**
16
**
16
**
** Impossible in Mw type
170
Installation de l’appareillage
Switchgear Installation
INTEGRAL
3.3.1.25.
Contacteurs-Disjoncteurs INTEGRAL - - - - - -DOL (Démarrage direct)
INTEGRAL contactors-circuit breakers - - - - -DOL (Direct On Line)
Coordination totale
Total coordination
220/230 V
Contacteurs-Disjoncteurs INTEGRAL
INTEGRAL contactors-circuit breakers
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
Icu (kA)
Rms (kA)
0,06
0,38
70
0,09
0,65
70
0,12
0,75
70
0,18
1,04
70
0,25
1,47
70
0,37
2
70
-
-
-
0,55
2,8
70
0,75
3,6
70
1,1
5,2
70
-
-
-
1,5
6,8
70
2,2
9,6
70
3
11,5
70
-
-
-
4
14,5
70
-
-
-
5,5
2,2
70
7,5
28
70
TeSys
DOL (Démarrage direct)
DOL (Direct On Line)
TeSys
TeSys
Contacteur-disjoncteur sans Module de protection
Contactor-Circuit Breaker without protection Module
Sectionnement par
Sectionnement par
pôles principaux
pôles spécifiques
Isolation by main poles
Isolation by specifics poles
LD1-LB030
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LC030
LD4-LC130
LD1-LC030
LD4-LC130
*:
Icu = 40 kA pour LD1-LB;
Icu = 70 kA pour LDz-LC.
**: En fonction du nombre d’auxiliaires.
LD1-LB:
LDz-LC:
LDz-LD:
Guide Technique V9 / V9 Technical Guide
TeSys
Module de protection
Protection Module
Référence
Reference
Nb modules
Nbr of modules
Mf
Mw
LB1-LB03P03
3
3 ou 6**
LB1-LB03P05
3
3 ou 6**
LB1-LC03M05
3
-
LB1-LB03P06
3
3 ou 6**
LB1-LC03M06
3
-
LB1-LB03P07
3
3 ou 6**
LB1-LC03M07
3
-
LB1-LB03P08
3
3 ou 6**
LB1-LC03M08
3
-
LB1-LB03P10
3
3 ou 6**
LB1-LC03M10
3
-
LB1-LB03P13
3
3 ou 6**
LB1-LC03M13
3
-
LB1-LB03P17
3
3 ou 6**
LB1-LC03M17
3
-
LB1-LB03P21
3
3 ou 6**
LB1-LC03M17
3
-
LB1-LC03M22
3
3 ou 6**
LB1-LC03M53
3
3 ou 6**
*:
Rms = 40 kA for LD1-LB;
Rms = 70 kA for LDz-LC.
**: According to the number of auxiliaries.
Integral 18.
Integral 32.
Integral 63.
171
Installation de l’appareillage
Switchgear Installation
400/415 V
Contacteurs-Disjoncteurs INTEGRAL
INTEGRAL contactors-circuit breakers
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
Icu (kA)
Rms (kA)
0,06
0,22
70
0,09
0,36
70
0,12
0,42
70
0,18
0,6
70
0,25
0,88
70
-
-
-
0,37
1
70
0,55
1,5
70
0,75
2
70
-
-
-
1,1
2,5
70
1,5
3,5
70
2,2
5
70
-
-
-
3
6,5
70
4
8,4
70
5,5
11
70
7,5
14,8
70
9
18,1
70
-
-
-
11
21
70
15
28,5
70
18,5
35
70
22
42
70
30
57
70
TeSys
DOL (Démarrage direct)
DOL (Direct On Line)
TeSys
TeSys
Contacteur-disjoncteur sans Module de protection
Contactor-Circuit Breaker without protection Module
Sectionnement par
Sectionnement par
pôles principaux
pôles spécifiques
Isolation by main poles
Isolation by specifics poles
LD1-LB030
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LC030
LD4-LC130
LD1-LC030
LD4-LC130
LD1-LD030
LD4-LD130
LD1-LD030
LD4-LD130
LD1-LD030
LD4-LD130
*:
Icu = 40 kA pour LD1-LB;
Icu = 70 kA pour LDz-LC.
**: En fonction du nombre d’auxiliaires.
LD1-LB:
LDz-LC:
LDz-LD:
Guide Technique V9 / V9 Technical Guide
TeSys
Module de protection
Protection Module
Référence
Reference
Nb modules
Nbr of modules
Mf
Mw
LB1-LB03P02
3
3 ou 6**
LB1-LB03P03
3
3 ou 6**
LB1-LC03M03
-
-
LB1-LB03P04
3
3 ou 6**
LB1-LC03M04
3
-
LB1-LB03P05
3
3 ou 6**
LB1-LC03M05
3
-
LB1-LB03P06
3
3 ou 6**
LB1-LC03M06
3
-
LB1-LB03P07
3
3 ou 6**
LB1-LC03M07
3
-
LB1-LB03P08
3
3 ou 6**
LB1-LC03M08
3
-
LB1-LB03P10
3
3 ou 6**
LB1-LC03M10
3
-
LB1-LB03P13
3
3 ou 6**
LB1-LC03M13
3
-
LB1-LB03P17
3
3 ou 6**
LB1-LC03M17
3
-
LB1-LB03P21
3
3 ou 6**
LB1-LC03M22
3
-
LB1-LC03M22
3
3 ou 6**
LB1-LC03M53
3
3 ou 6**
LB1-LD03M55
6
6
LB1-LD03M57
6
6
LB1-LD03M61
6
6
*:
Rms = 40 kA for LD1-LB;
Rms = 70 kA for LDz-LC.
**: According to the number of auxiliaries.
Integral 18.
Integral 32.
Integral 63.
172
Installation de l’appareillage
Switchgear Installation
440 V
Contacteurs-Disjoncteurs INTEGRAL
INTEGRAL contactors-circuit breakers
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
Icu (kA)
Rms (kA)
0,06
0,19
70
0,09
0,28
70
0,12
0,37
70
-
-
-
0,18
0,55
70
0,25
0,76
70
-
-
-
0,37
1
70
0,55
1,36
70
0,75
1,68
70
1,1
2,37
70
-
-
-
1,5
3,06
70
2,2
4,42
*
3
5,77
*
4
7,9
*
-
-
-
5,5
10,4
*
7,5
13,7
*
9
16,9
*
11
20,1
70
15
26,5
30
18,5
32,8
70
22
39
70
30
51,5
40
33
58,5
40
TeSys
DOL (Démarrage direct)
DOL (Direct On Line)
TeSys
TeSys
Contacteur-disjoncteur sans Module de protection
Contactor-Circuit Breaker without protection Module
Sectionnement par
Sectionnement par
pôles principaux
pôles spécifiques
Isolation by main poles
Isolation by specifics poles
LD1-LB030
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LC030
LD4-LC130
LD1-LC030
LD4-LC130
LD1-LD030
LD4-LD130
LD1-LD030
LD4-LD130
-
*:
Icu = 40 kA pour LD1-LB;
Icu = 70 kA pour LDz-LC.
**: En fonction du nombre d’auxiliaires.
LD1-LB:
LDz-LC:
LDz-LD:
Guide Technique V9 / V9 Technical Guide
TeSys
Module de protection
Protection Module
Référence
Reference
Nb modules
Nbr of modules
Mf
Mw
LB1-LB03P02
3
3 ou 6**
LB1-LB03P03
3
3 ou 6**
LB1-LC03M03
3
-
LB1-LB03P04
3
3 ou 6**
LB1-LC03M04
3
-
LB1-LB03P05
3
3 ou 6**
LB1-LC03M05
3
-
LB1-LB03P06
3
3 ou 6**
LB1-LC03M06
3
-
LB1-LB03P07
3
3 ou 6**
-
LB1-LC03M07
3
LB1-LB03P08
3
3 ou 6**
LB1-LC03M08
3
-
LB1-LB03P10
3
3 ou 6**
LB1-LC03M10
3
-
LB1-LB03P13
3
3 ou 6**
LB1-LC03M13
3
-
LB1-LB03P17
3
3 ou 6**
LB1-LC03M17
3
-
LB1-LB03P21
3
3 ou 6**
LB1-LC03M22
3
-
LB1-LC03M22
3
3 ou 6**
LB1-LC03M53
3
3 ou 6**
LB1-LD03M55
6
6
-
-
-
LB1-LD03M61
6
6
-
-
-
*:
Rms = 40 kA for LD1-LB;
Rms = 70 kA for LDz-LC.
**: According to the number of auxiliaries.
Integral 18.
Integral 32.
Integral 63.
173
Installation de l’appareillage
Switchgear Installation
INTEGRAL
3.3.1.26.
Contacteurs-Disjoncteurs INTEGRAL - - - - - -2 sens de marche
INTEGRAL contactors-circuit breakers - - - - -Reverse
Coordination totale
Total coordination
220/230 V
Contacteurs-Disjoncteurs INTEGRAL
INTEGRAL contactors-circuit breakers
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
Icu (kA)
Rms (kA)
0,06
0,38
70
0,09
0,65
70
0,12
0,75
70
0,18
1,04
70
0,25
1,47
70
0,37
2
70
-
-
-
0,55
2,8
70
0,75
3,6
70
1,1
5,2
70
-
-
-
1,5
6,8
70
2,2
9,6
70
3
11,5
70
-
-
-
4
14,5
70
-
-
-
5,5
2,2
70
7,5
28
70
TeSys
2 sens de marche
Reverse
TeSys
TeSys
Contacteur-disjoncteur sans Module de protection
Contactor-Circuit Breaker without protection Module
Sectionnement par
Sectionnement par
pôles principaux
pôles spécifiques
Isolation by main poles
Isolation by specifics poles
LD5-LB130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LC130
LD5-LC130
*:
Icu = 40 kA pour LD5-LB;
Icu = 70 kA pour LD5-LC.
LD5-LB:
LD5-LC:
LD5-LD:
Guide Technique V9 / V9 Technical Guide
*:
TeSys
Module de protection
Protection Module
Référence
Reference
Nb modules
Nbr of modules
Mf
Mw
LB1-LB03P03
3
6
LB1-LB03P05
3
6
LB1-LC03M05
6
-
LB1-LB03P06
3
6
LB1-LC03M06
6
-
LB1-LB03P07
3
6
LB1-LC03M07
6
-
LB1-LB03P08
3
6
LB1-LC03M08
6
-
LB1-LB03P10
3
6
LB1-LC03M10
6
-
LB1-LB03P13
3
6
LB1-LC03M13
6
-
LB1-LB03P17
3
6
LB1-LC03M17
6
-
LB1-LB03P21
3
6
LB1-LC03M17
6
-
LB1-LC03M22
6
6
LB1-LC03M53
6
6
Rms = 40 kA for LD5-LB;
Rms = 70 kA for LD5-LC.
Integral 18.
Integral 32.
Integral 63.
174
Installation de l’appareillage
Switchgear Installation
400/415 V
Contacteurs-Disjoncteurs INTEGRAL
INTEGRAL contactors-circuit breakers
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
Icu (kA)
Rms (kA)
0,06
0,22
70
0,09
0,36
70
-
-
-
0,12
0,42
70
0,18
0,6
70
0,25
0,88
70
-
-
-
0,37
1
70
0,55
1,5
70
0,75
2
70
-
-
-
1,1
2,5
70
1,5
3,5
70
2,2
5
70
-
-
-
3
6,5
70
4
8,4
70
5,5
11
70
7,5
14,8
70
9
18,1
70
-
-
-
11
21
70
15
28,5
70
18,5
35
70
22
42
70
30
57
70
TeSys
2 sens de marche
Reverse
TeSys
TeSys
Contacteur-disjoncteur sans Module de protection
Contactor-Circuit Breaker without protection Module
Sectionnement par
Sectionnement par
pôles principaux
pôles spécifiques
Isolation by main poles
Isolation by specifics poles
LD5-LB130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LC130
LD5-LC130
LD5-LD130
LD5-LD130
LD5-LD130
*:
Icu = 40 kA pour LD5-LB;
Icu = 70 kA pour LD5-LC.
LD5-LB:
LD5-LC:
LD5-LD:
Guide Technique V9 / V9 Technical Guide
*:
TeSys
Module de protection
Protection Module
Référence
Reference
Nb modules
Nbr of modules
Mf
Mw
LB1-LB03P02
3
6
LB1-LB03P03
3
6
LB1-LC03M03
6
-
LB1-LB03P04
3
6
LB1-LC03M04
6
-
LB1-LB03P05
3
6
LB1-LC03M05
6
-
LB1-LB03P06
3
6
LB1-LC03M06
6
-
LB1-LB03P07
3
6
LB1-LC03M07
6
-
LB1-LB03P08
3
6
LB1-LC03M08
6
-
LB1-LB03P10
3
6
LB1-LC03M10
6
-
LB1-LB03P13
3
6
LB1-LC03M13
6
-
LB1-LB03P17
3
6
LB1-LC03M17
6
-
LB1-LB03P21
3
6
LB1-LC03M22
6
-
LB1-LC03M22
6
6
LB1-LC03M53
6
6
LB1-LD03M55
6
6**
LB1-LD03M57
6
6**
LB1-LD03M61
6
6**
Rms = 40 kA for LD5-LB;
Rms = 70 kA for LD5-LC.
Integral 18.
Integral 32.
Integral 63.
175
Installation de l’appareillage
Switchgear Installation
440 V
Contacteurs-Disjoncteurs INTEGRAL
INTEGRAL contactors-circuit breakers
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
Icu (kA)
Rms (kA)
0,06
0,19
70
0,09
0,28
70
0,12
0,37
70
-
-
-
0,18
0,55
70
0,25
0,76
70
-
-
-
0,37
1
70
0,55
1,36
70
0,75
1,68
70
1,1
2,37
70
-
-
-
1,5
3,06
70
2,2
4,42
*
3
5,77
*
4
7,9
*
-
-
-
5,5
10,4
*
7,5
13,7
*
9
16,9
*
-
-
-
11
20,1
70
15
26,5
30
18,5
32,8
70
22
39
70
30
51,5
40
33
58,5
40
TeSys
2 sens de marche
Reverse
TeSys
TeSys
Contacteur-disjoncteur sans Module de protection
Contactor-Circuit Breaker without protection Module
Sectionnement par
Sectionnement par
pôles principaux
pôles spécifiques
Isolation by main poles
Isolation by specifics poles
LD5-LB130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LC130
LD5-LC130
LD5-LD130
LD5-LD130
-
*:
Icu = 40 kA pour LD5-LB;
Icu = 70 kA pour LD5-LC.
**: 9 avec transformateur
LD5-LB:
LD5-LC:
LD5-LD:
Guide Technique V9 / V9 Technical Guide
TeSys
Module de protection
Protection Module
Référence
Reference
Nb modules
Nbr of modules
Mf
Mw
LB1-LB03P02
3
6
LB1-LB03P03
3
6
LB1-LC03M03
6
-
LB1-LB03P04
3
6
LB1-LC03M04
6
-
LB1-LB03P05
3
6
LB1-LC03M05
6
-
LB1-LB03P06
3
6
LB1-LC03M06
6
-
LB1-LB03P07
3
6
LB1-LC03M07
6
-
LB1-LB03P08
3
6
LB1-LC03M08
6
-
LB1-LB03P10
3
6
LB1-LC03M10
6
-
LB1-LB03P13
3
6
LB1-LC03M13
6
-
LB1-LB03P17
3
6
LB1-LC03M17
6
-
LB1-LB03P21
3
6
LB1-LC03M22
6
-
LB1-LC03M22
6
6
LB1-LC03M53
6
6
LB1-LD03M55
6
6**
-
-
-
LB1-LD03M61
6
6**
-
-
-
*:
Rms = 40 kA for LD5-LB;
Rms = 70 kA for LD5-LC.
**: 9 with transformer
Integral 18.
Integral 32.
Integral 63.
176
Installation de l’appareillage
Switchgear Installation
3.3.1.27.
GV2-P
Type de coordination: 1 - - - - - - - - - - - - - - - -DOL monophasé (Démarrage direct)
Coordination type: 1 - - - - - - - - - - - - - - - - - - -Single phase - DOL (Direct On Line)
GV2-P
220/230 V
TeSys
TeSys
P (kW)
I (A)
0,09
0,5
0,12
1,0
0,25
2,0
0,37
3,0
0,55
4,0
0,75
5,0
1,1
7,4
1,5
9,3
1,8
11,7
2,2
16,0
3
18,3
4
23,5
3.3.1.28.
Icu (kA)
Rms (kA)
50
50
50
50
50
50
50
50
50
50
50
50
Type de coordination: 1DOL monophasé (Démarrage direct)
Coordination type: 1Single phase - DOL (Direct On Line)
TeSys
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV2-P04
0,4..0,63
GV2-P06
1...1,6
GV2-P07
1,6...2,5
GV2-P08
2,5...4
GV2-P10
4...6,3
GV2-P10
4...6,3
GV2-P14
6...10
GV2-P14
6...10
GV2-P16
9...14
GV2-P20
13...18
GV2-P21
17...23
GV2-P22
20...25
TeSys
Contacteur
Contactor
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K09
LC1-K09
LC1-D12
LC1-D18
LC1-D25
LC1-D25
Mw
3
3
3
3
3
3
3
3
3
3
3
3
GV2-P
Type de coordination: 2 - - - - - - - - - - - - - - - -DOL monophasé (Démarrage direct)
Coordination type: 2 - - - - - - - - - - - - - - - - - - -Single phase - DOL (Direct On Line)
220/230 V
TeSys
GV2-P
TeSys
P (kW)
I (A)
0,09
0,5
0,12
1,0
0,25
2,0
0,37
3,0
0,55
4,0
0,75
5,0
1,1
7,4
1,5
9,3
1,8
11,7
2,2
16
3
18,3
4
23,5
Icu (kA)
Rms (kA)
130
130
130
130
130
130
130
130
130
130
130
130
Guide Technique V9 / V9 Technical Guide
Type de coordination: 2DOL monophasé (Démarrage direct)
Coordination type: 2Single phase - DOL (Direct On Line)
TeSys
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV2-P04
0,4..0,63
GV2-P06
1...1,6
GV2-P07
1,6...2,5
GV2-P08
2,5...4
GV2-P10
4...6,3
GV2-P10
4...6,3
GV2-P14
6...10
GV2-P14
6...10
GV2-P16
9...14
GV2-P20
13...18
GV2-P21
17...23
GV2-P22
20...25
TeSys
Contacteur
Contactor
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D25
LC1-D25
LC1-D25
LC1-D25
Mw
3
3
3
3
3
3
3
3
3
3
3
3
177
Installation de l’appareillage
Switchgear Installation
3.3.1.29.
Compact NS80H-MA
Type de coordination: 1 - - - - - - - - - - - - - - - -DOL monophasé (Démarrage direct)
Coordination type: 1 - - - - - - - - - - - - - - - - - - -Single phase - DOL (Direct On Line)
Démarrage: Normal
Performance de coupure: égale au pouvoir
de coupure du disjoncteur
Compact NS80H-MA
220/230 V
TeSys
TeSys
Puissance Moteur
Power motor
P (kW)
I (A)
0,12
1,0
0,25
2,0
0,37
3,0
0,55
4,0
0,75
5,0
1,1
7,4
1,5
9,3
1,8
11,7
2,2
16,0
3
18,3
4
23,5
3.3.1.30.
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
Type de coordination: 1DOL monophasé (Démarrage direct)
Coordination type: 1Single phase - DOL (Direct On Line)
TeSys
Cal (A)
Rat (A)
2,5
2,5
6,3
6,3
6,3
12,5
12,5
25
25
25
50
Start-up: Normal
Breaking characteristics: equal to the circuit
breaker’s breaking capacity
TeSys
Contacteurs
Contactor
Type
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D18
LC1-D25
LC1-D32
LC1-D32
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LRD-06
1...1,7
LRD-07
1,6...2,5
LRD-08
2,5...4
LRD-10
4...6
LRD-10
4...6
LRD-12
5,5...8
LRD-14
7...10
LRD-16
9...13
LRD-21
12...18
LRD-22
17...24
LRD-22
17...24
TeSys
Nb modules
Nbr of modules
Mw
3
3
3
3
3
3
3
3
3
3
3
Compact NS80H-MA
Type de coordination: 2 - - - - - - - - - - - - - - - -DOL monophasé (Démarrage direct)
Coordination type: 2 - - - - - - - - - - - - - - - - - - -Single phase - DOL (Direct On Line)
Démarrage: Normal
Start-up: Normal
220/230 V
TeSys
Compact NS80H-MA
TeSys
Performance de coupure: Icu = 100 kA
Breaking characteristics: Icu = 100 kA
Puissance Moteur
Disjoncteurs
Power motor
Circuit Breaker
P (kW)
I (A)
Type
Type
0,12
1,0
NS80H-MA
0,25
2,0
NS80H-MA
0,37
3,0
NS80H-MA
0,55
4,0
NS80H-MA
0,75
5,0
NS80H-MA
1,1
7,4
NS80H-MA
1,5
9,3
NS80H-MA
1,8
11,7
NS80H-MA
2,2
16,0
NS80H-MA
Guide Technique V9 / V9 Technical Guide
Type de coordination: 2DOL monophasé (Démarrage direct)
Coordination type: 2Single phase - DOL (Direct On Line)
TeSys
Cal (A)
Rat (A)
2,5
2,5
6,3
6,3
6,3
12,5
12,5
25
25
Contacteurs
Contactor
Type
Type
LC1-D09
LC1-D09
LC1-D18
LC1-D25
LC1-D25
LC1-D32
LC1-D32
LC1-D32
LC1-D32
TeSys
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LRD-06
1...1,7
LRD-07
1,6...2,5
LRD-08
2,5...4
LRD-10
4...6
LRD-10
4...6
LRD-14
7...10
LRD-14
7...10
LRD-16
9...13
LRD-21
12...18
TeSys
Nb modules
Nbr of modules
Mw
3
3
3
3
3
3
3
3
3
178
Installation de l’appareillage
Switchgear Installation
3.3.2.
3.3.2.1.
Déclassement des appareils - AC3
Starters derating - AC3
GV2-P
Type de coordination: 1-2
Coordination type: 1-2
Blokset Mf
TeSys
TeSys
TeSys
Appareillage Puissance
Power Switchgear
Disjoncteur
Circuit breaker
GV2-P02
GV2-P03
GV2-P04
GV2-P05
GV2-P06
GV2-P07
GV2-P08
GV2-P10
GV2-P14
GV2-P16
GV2-P20
GV2-P21
GV2-P22
Calibre
Rating
0,16...0,25
0,25...0,4
0,4...0,63
0,63...1
1...1,6
1,6...2,5
2,5...4
4...6,3
6...10
9...14
13...18
17...23
20...25
Contacteur
Contactor
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K09
LC1-D12
LC1-D18
LC1-D25
LC1-D25
TeSys
TeSys
Coefficient de Déclassement (A) à T°amb (°C)
Derating coefficient (A) à T°amb (°C)
IP ≤ 42
IP 54
35
40
45
50
35
40
45
50
0,23
0,2
0,2
0,2
0,2
0,2
0,2
0,15
0,35
0,33
0,3
0,3
0,3
0,3
0,3
0,25
0,6
0,5
0,5
0,5
0,5
0,5
0,5
0,4
0,9
0,8
0,8
0,7
0,8
0,75
0,7
0,7
1,4
1,3
1,2
1,2
1,3
1,2
1,1
1
2,2
2,1
2
1,9
2
1,9
1,8
1,7
3,6
3,4
3,1
3
3,2
3
2,9
2,7
5,4
5
4,7
4,5
5
4,5
4,3
4
8
7,6
7
6,7
7,2
6,8
6,5
6
10,7
10
9,4
8,9
9,6
9
8,6
8
16
15
14
13,3
14,5
13,5
13
12
20
19
18
17
18,5
17
16,6
15,4
22
21
19,5
18,5
20
18,8
18
16,8
Blokset Mw
TeSys
Disjoncteur
Circuit breaker
GV2-P02
GV2-P03
GV2-P04
GV2-P05
GV2-P06
GV2-P07
GV2-P08
GV2-P10
GV2-P14
GV2-P16
GV2-P20
GV2-P21
GV2-P22
TeSys
Calibre
Rating
0,16...0,25
0,25...0,4
0,4...0,63
0,63...1
1...1,6
1,6...2,5
2,5...4
4...6,3
6...10
9...14
13...18
17...23
20...25
TeSys
Contacteur
Contactor
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K09
LC1-D12
LC1-D18
LC1-D25
LC1-D25
TeSys
IP ≤ 42
35
40
45
0,23
0,2
0,35
0,34
0,6
0,5
TeSys
50
IP 54
35
40
45
50
0,2
0,2
0,2
0,2
0,2
0,2
0,3
0,3
0,3
0,3
0,3
0,3
0,5
0,5
0,5
0,5
0,5
0,4
0,9
0,8
0,8
0,7
0,8
0,8
0,7
0,7
1,4
1,3
1,2
1,2
1,3
1,2
1,1
1
2,2
2,1
2
1,9
2
1,9
1,8
1,7
3,6
3,4
3,1
3
3,2
3
2,9
2,7
5,4
5
4,7
4,5
5
4,5
4,3
4
8
7,5
7
6,7
7,2
6,8
6,5
6
10,7
10
9,4
8,9
9,6
9
8,6
8
16
15
14
13,3
14,5
13,5
13
12
20
19
18
17
18,5
17
15,6
15,4
22
21
20
19
20
19
18
17
Coefficient à appliquer
Coefficient to be applied
35°
40°
45°
50°
IP ≤ 42
0.89
0.84
0.78
0.74
IP 54
0.80
0.75
0.72
0.67
Guide Technique V9 / V9 Technical Guide
179
Installation de l’appareillage
Switchgear Installation
3.3.2.2.
Compact NS et GV7
Compact NS and GV7
Type de coordination: 1-2
Coordination type: 1-2
Blokset Mf
TeSys
Disjoncteur
Circuit breaker
NS80H-MA
NS100l-MA*
NS160l-MA*
NS250l-MA*
NS400l-MA*
NS630l-MA*
TeSys
TeSys
TeSys
Calibre
Rating
2,5
6,3
13
13
25
25
50
50
50
80
80
2,5
6,3
13
13
25
25
50
50
50
50
100
100
100
100
150
Disjoncteur moteur
Motor circuit-breaker
GV7-Rn
GV7-Rn
GV7-Rn
GV7-Rn
GV7-Rn
GV7-Rn
GV7-Rn
GV7-Rn
GV7-Rn
GV7-Rn
GV7-Rn
GV7-Rn
GV7-Rn
GV7-Rn
GV7-Rn
GV7-Rn
Contacteur
Contactor
LC1-D09
LC1-D09
LC1-D09
LC1-D12
LC1-D18
LC1-D25
LC1-D32
LC1-D40
LC1-D50
LC1-D65
LC1-D80
LC1-D09
LC1-D09
LC1-D09
LC1-D12
LC1-D18
LC1-D25
LC1-D32
LC1-D40
LC1-D50
LC1-D65
LC1-D65
LC1-D80
LC1-D95
LC1-F115
LC1-F150
220
GV7-Rn
220
GV7-Rn
TeSys
IP ≤ 42
35
40
45
50
IP 54
35
40
45
50
8
7.7
7.3
7
6.3
5.9
5.5
5.4
8
7.7
7.3
7
6.3
5.9
5.5
5.4
8
7.7
7.3
7
6.3
5.9
5.5
5.4
10.7
10.2
9.7
9.2
8.3
7.8
7.5
7
16
15.3
14.6
13.9
12.5
11.7
11.2
10.8
22.3
21.2
20.2
19.2
17.3
16.3
15.5
15
28.5
27.2
26
24.6
22
20.8
19.9
19.2
35.6
34
32.4
30.8
28
26
25
24
44.5
42.5
40.5
38.5
35
33
32
30
58
55
53
50
45
42
40
39
71
68
65
62
55
52
50
48
8
7.7
7.3
7
6.3
5.9
5.5
5.4
8
7.7
7.3
7
6.3
5.9
5.5
5.4
8
7.7
7.3
7
6.3
5.9
5.5
5.4
7
10.7
10.2
9.7
9.2
8.3
7.8
7.5
16
15.3
14.6
13.9
12.5
11.7
11.2
10.8
22.3
21.2
20.2
19.2
17.3
16.3
15.5
15
28.5
27.2
26
24.6
22
20.8
19.9
19.2
35.6
34
32.4
30.8
28
26
25
24
44.5
42.5
40.5
38.5
35
33
32
30
58
55
53
50
45
42
40
39
58
55
53
50
45
42
40
39
71
68
65
62
55
52
50
48
84.5
81
77
73
65
62
60
57
102
98
93
89
78
75
73
69
134
128
122
116
102
98
95
90
LC1-F185
165
157
150
142
126
120
117
111
LC1-F225
203
190
185
175
154
147
141
135
320
GV7-Rn
LC1-F265
236
225
215
204
180
172
167
159
320
-
LC1-F330
294
280
267
254
225
215
208
198
500
-
LC1-F400
356
340
324
308
272
260
252
240
500
-
LC1-F500
445
425
405
385
340
325
315
300
500
-
LC1-F630
560
535
510
485
428
409
397
381
*:
NS ***z-MA représente:
- NS*** N/H/L-MA pour NS100-250
- NS*** H/L-MA pour NS400-630
„: représente E40...220 ou S40...220
Guide Technique V9 / V9 Technical Guide
*:
NS ***z-MA represent:
- NS*** N/H/L-MA by NS100-250
- NS*** H/L-MA by NS400-630
„: represent E40...220 or S40...220
180
Installation de l’appareillage
Switchgear Installation
Blokset Mw
IP 20
TeSys
TeSys
Appareillage Puissance
Power Switchgear
Disjoncteur
Calibre
Circuit breaker
Rating
NS80H-MA
2,5
6,3
13
13
25
TeSys
Disjoncteur moteur
Motor circuit-breaker
-
TeSys
GV7-R„
Contacteur
Contactor
LC1-D09
LC1-D09
LC1-D09
LC1-D12
LC1-D18
25
-
50
GV7-R„
50
TeSys
Coefficient de Déclassement (A) à T°amb (°C)
Derating coefficient (A) à T°amb (°C)
35
40
45
50
8,1
7,9
7,6
8,1
7,9
7,6
7,2
7,2
8,1
7,9
7,6
7,2
10
10,5
1O
9,6
17
16
15
15
LC1-D25
22,5
22
21
20
LC1-D32
30
28
27
26
GV7-R„
LC1-D40
38
35
33
32
50
GV7-R„
LC1-D50
45
44
42
40
80
GV7-R„
LC1-D65
61
58
55
52
80
GV7-R„
LC1-D80
64
61
59
56
2,5
-
LC1-D09
8,1
7,9
7,6
7,2
6,3
-
LC1-D09
8,1
7,9
7,6
7,2
13
-
LC1-D09
8,1
7,9
7,6
7,2
13
-
LC1-D12
10
10,5
1O
9,6
25
GV7-R„
LC1-D18
17
16
15
15
25
-
LC1-D25
22,5
22
21
20
50
GV7-R„
LC1-D32
30
28
27
26
50
GV7-R„
LC1-D40
38
35
33
32
50
GV7-R„
LC1-D50
45
44
42
40
50
GV7-R„
LC1-D65
61
58
55
52
100
GV7-R„
LC1-D65
61
58
55
52
100
GV7-R„
LC1-D80
64
61
59
56
100
GV7-R„
LC1-D95
76
72
70
67
NS160z-MA*
100
GV7-R„
LC1-F115
92
88
84
81
150
GV7-R„
LC1-F150
120
115
110
105
NS250z-MA*
220
GV7-R„
LC1-F185
148
142
136
130
220
GV7-R„
LC1-F225
175
168
161
155
NS400z-MA*
320
GV7-R„
LC1-F265
249
235
222
211
320
-
LC1-F330
255
245
234
225
NS630z-MA*
500
-
LC1-F400
320
306
293
282
500
-
LC1-F500
400
382
366
352
500
-
LC1-F630
500
480
460
440
NS100z-MA*
*:
NS ***z-MA représente:
- NS*** N/H/L-MA pour NS100-250
- NS*** H/L-MA pour NS400-630
„: représente E40...220 ou S40...220
Guide Technique V9 / V9 Technical Guide
*:
NS ***z-MA represent:
- NS*** N/H/L-MA by NS100-250
- NS*** H/L-MA by NS400-630
„: represent E40...220 or S40...220
181
Installation de l’appareillage
Switchgear Installation
Blokset Mw
IP 31/42
TeSys
TeSys
Appareillage Puissance
Power Switchgear
Disjoncteur
Calibre
Circuit breaker
Rating
NS80H-MA
2,5
6,3
13
13
25
TeSys
TeSys
Coefficient de Déclassement (A) à T°amb (°C)
Derating coefficient (A) à T°amb (°C)
35
40
45
50
GV7-R„
Contacteur
Contactor
LC1-D09
LC1-D09
LC1-D09
LC1-D12
LC1-D18
25
-
LC1-D25
22
21
20
18,5
50
GV7-R„
LC1-D32
28
27
25
24
50
GV7-R„
LC1-D40
34
32
31
29
50
GV7-R„
LC1-D50
35
33
31
30
80
GV7-R„
LC1-D65
57
54
51
48
80
GV7-R„
LC1-D80
64
61
59
56
2,5
-
LC1-D09
8
7,6
7
6,6
6,3
-
LC1-D09
8
7,6
7
6,6
13
-
LC1-D09
8
7,6
7
6,6
13
-
LC1-D12
10,5
10
9,4
8,8
25
GV7-R„
LC1-D18
17
16
15
14
25
-
LC1-D25
22
21
20
18,5
50
GV7-R„
LC1-D32
28
27
25
24
50
GV7-R„
LC1-D40
34
32
31
29
50
GV7-R„
LC1-D50
35
33
31
30
50
GV7-R„
LC1-D65
57
54
51
48
100
GV7-R„
LC1-D65
57
54
51
48
100
GV7-R„
LC1-D80
64
61
59
56
100
GV7-R„
LC1-D95
76
72
70
67
NS160z-MA*
100
GV7-R„
LC1-F115
92
87
85
80
150
GV7-R„
LC1-F150
112
110
102
98
NS250z-MA*
220
GV7-R„
LC1-F185
137
135
126
120
220
GV7-R„
LC1-F225
164
161
150
144
NS400z-MA*
320
GV7-R„
LC1-F265
231
218
207
197
320
-
LC1-F330
238
234
218
210
NS630z-MA*
500
-
LC1-F400
296
292
272
260
500
-
LC1-F500
372
366
341
328
500
-
LC1-F630
468
460
430
413
NS100z-MA*
Disjoncteur moteur
Motor circuit-breaker
-
TeSys
*:
8
7,6
7
8
7,6
7
6,6
8
7,6
7
6,6
10,5
10
9,4
8,8
17
16
15
14
NS ***z-MA représente:
- NS*** N/H/L-MA pour NS100-250
- NS*** H/L-MA pour NS400-630
„: représente E40...220 ou S40...220
Guide Technique V9 / V9 Technical Guide
6,6
*:
NS ***z-MA represent:
- NS*** N/H/L-MA by NS100-250
- NS*** H/L-MA by NS400-630
„: represent E40...220 or S40...220
182
Installation de l’appareillage
Switchgear Installation
Blokset Mw
IP 54
TeSys
TeSys
Appareillage Puissance
Power Switchgear
Disjoncteur
Calibre
Circuit breaker
Rating
NS80H-MA
2,5
6,3
13
13
25
NS100z-MA*
TeSys
Disjoncteur moteur
Motor circuit-breaker
-
TeSys
TeSys
Coefficient de Déclassement (A) à T°amb (°C)
Derating coefficient (A) à T°amb (°C)
35
40
45
50
GV7-R„
Contacteur
Contactor
LC1-D09
LC1-D09
LC1-D09
LC1-D12
LC1-D18
25
-
LC1-D25
20
18,7
18
17,2
50
GV7-R„
LC1-D32
26
24
23
22
50
GV7-R„
LC1-D40
32
30
29
27,5
50
GV7-R„
LC1-D50
40
37,5
36
34,5
80
GV7-R„
LC1-D65
52
49,5
47
44,5
80
GV7-R„
LC1-D80
55
52
50
48
2,5
-
LC1-D09
7,2
6,8
6,5
6,2
6,3
-
LC1-D09
7,2
6,8
6,5
6,2
13
-
LC1-D09
7,2
6,8
6,5
6,2
13
-
LC1-D12
9,6
9
8,6
7,2
25
GV7-R„
LC1-D18
14,5
13,6
13
12,3
25
-
LC1-D25
20
18,7
18
17,2
50
GV7-R„
LC1-D32
26
24
23
22
50
GV7-R„
LC1-D40
32
30
29
27,5
50
GV7-R„
LC1-D50
40
37,5
36
34,5
50
GV7-R„
LC1-D65
52
49,5
47
44,5
100
GV7-R„
LC1-D65
52
49,5
47
44,5
100
GV7-R„
LC1-D80
55
52
50
48
7,2
6,8
6,5
7,2
6,8
6,5
6,2
6,2
7,2
6,8
6,5
6,2
9,6
9
8,6
7,2
14,5
13,6
13
12,3
100
GV7-R„
LC1-D95
66
62
60
57
NS160z-MA*
100
GV7-R„
LC1-F115
79
75
72
69
150
GV7-R„
LC1-F150
103
98
94
90,5
NS250z-MA*
220
GV7-R„
LC1-F185
127
120
115
111
220
GV7-R„
LC1-F225
151
144
138
133
NS400z-MA*
320
GV7-R„
LC1-F265
213
201
191
182
320
-
LC1-F330
221
211
201
198
NS630z-MA*
500
-
LC1-F400
276
260
250
240
500
-
LC1-F500
343
328
314
302
500
-
LC1-F630
432
413
395
380
*:
NS ***z-MA représente:
- NS*** N/H/L-MA pour NS100-250
- NS*** H/L-MA pour NS400-630
„: représente E40...220 ou S40...220
Guide Technique V9 / V9 Technical Guide
*:
NS ***z-MA represent:
- NS*** N/H/L-MA by NS100-250
- NS*** H/L-MA by NS400-630
„: represent E40...220 or S40...220
183
Installation de l’appareillage
Switchgear Installation
3.3.2.3.
Integral
Contacteurs - Disjoncteurs Integral - - - - - - -Coordination totale
Contactors - Integral Circuit breakers - - - - - -Total coordination
Coefficient à appliquer
Coefficient to be applied
35°
0.89
0.80
IP ≤ 42
IP 54
3.3.3.
3.3.3.1.
40°
45°
50°
0.84
0.78
0.74
0.75
0.72
0.67
Départ distribution en tiroir
Feeder in drawer
Nombre de modules nécessaires
Number of modules required
Blokset Mw
Disjoncteur
Circuit Breaker
NS 100
NS 100
NS 160
NS 250
NS 250
Guide Technique V9 / V9 Technical Guide
Nombre pôles
Number of Poles
3
4
3/4
3
4
Nb modules
Nbr of modules
3
6
6
6
9
Forme
Form
3b/4b
3b/4b
3b/4b
3b/4b
3b/4b
184
Installation de l’appareillage
Switchgear Installation
3.3.4.
Colonne arrivée Blokset Mw avec Masterpact NT
Blokset Mw incoming column with Masterpact NT
4M
4M
14 M
2200
2200
18 M
14 M
18 M
4M
4M
900
Guide Technique V9 / V9 Technical Guide
900
185
Sommaire du chapitre
Chapter contents
3.4. Raccordement des appareils
Connecting the circuit breakers
3.4.1.
Blokset D .................................................................................................
3.4.1.1. Barres souples ...........................................................................
Flexible bars
3.4.1.2. Barres Rigides ............................................................................
Rigid bars
3.4.1.3. Câbles (souple multi brins 105º C) ...........................................
Cables (type NYAF 105º C)
187
187
188
189
3.4.2.
Blokset Mf ................................................................................................ 190
3.4.2.1. Barres rigides ............................................................................. 190
Rigid bars
3.4.2.2. Câbles (souple multi brins 105° C) ........................................... 190
cables (type NYAF 105° C)
3.4.3.
Blokset Mw .............................................................................................. 190
3.4.3.1. Barres rigides ............................................................................. 190
Rigid bars
3.4.3.2. Câbles (souple multi brins 105° C) ........................................... 190
cables (type NYAF 105° C)
Guide Technique V9 / V9 Technical Guide
186
Installation de l’appareillage
Switchgear Installation
3.4. Raccordement des appareils
Connecting the circuit breakers
3.4.1.
3.4.1.1.
Blokset D
Barres souples
Flexible bars
Raccordement par barres souples (liaisons
préfabriquées et polypact): utilisation du
matériel Prisma uniquement.
„ Les disjoncteurs Compact NS peuvent
être raccordés aux Jeux de barres par
des liaisons préfabriquées (livrées avec
un écran support qui bride les
conducteurs), pour les appareils en
position horizontale, ou par Polypact
(livré avec un écran support et liaisons
préfabriquées), pour les appareils en
position verticale.
„ La liaison appareil horizontal s’installe
uniquement sur des appareils PAV quel
que soit le type de commande (sauf
électrique pour Compact NS 400/630)
avec un Jeu de barres LINERGY.
Appareils
Circuit breakers
NS 100 à 250
NS 100 to 250
NS 100 à 250
NS 100 to 250
NS 100 et 160
NS 100 and 160
NS 100 et 160
NS 100 and 160
NS 400 à 630
NS 400 to 630
NS 400 à 630
NS 400 to 630
Quantité/rangée
Quantity/row
1 tri
1 three pole
1 tétra
1 four pole
4 tri
4 three pole
3 tétra
3 four pole
1 tri
1 three pole
1 tétra
1 four pole
Position
Position
H
Références
References
07230
V
Fixation
Fixing
F ou D
F or D
F ou D
F or D
F
V
F
07014*
H
F
07234
H
F
07235**
H
D: Débrochable
F: Fixe
H: Horizontal
V: Vertical
*: sauf commande électrique
**: appareil triphasé pour raccordement par
barres ou utilisation d’épanouisseurs.
Guide Technique V9 / V9 Technical Guide
Connection via flexible bars (factory built and
polypact): only use Prisma equipment.
„ Compact NS circuit breakers can be
linked to the busbars using factory-built
links (supplied with support screen which
flanges the conductors) for circuit
breakers in the horizontal position, or
using Polypact (supplied with a support
screen and factory-built links) for circuit
breakers in the vertical position.
„ The horizontal circuit breaker link is only
installed on FC circuit breakers,
whatever the type of operating
mechanism. (except motor mechanisms
for Compact NS 400/630) with Linergy
busbars.
07231
07013*
D: Withdrawable
F: Fixed
H: Horizontal
V: Vertical
*:: except motor mechanism.
**::three-phase circuit breaker for
connections by bar or spreaders
187
Installation de l’appareillage
Switchgear Installation
3.4.1.2.
Barres Rigides
Rigid bars
Dans les autres cas: raccordement sur un
Jeu de barres traditionnel (barres plates),
pour les appareils fixes ou débrochables en
PAV ou PAR.
In the other cases: connection to a
conventional busbar (flat bars) for FC and
RC fixed or withdrawable circuit breakers.
Raccordement appareillage
Switchgear connection
Calibre
Rating
NB50
EZD100B/F/N/H
< 60A
Dérivations
Connections
Câble souple 105°C
1000SV 16 mm2
Flexible cable 105°C
Queues de barres (coté client)
Bar tails (customer side)
Plages appareil
Circuit breaker terminal pads
1000SV 16 mm2
NS100 / NB100
EZD100F/N/H ≥
60A up to 100A
Câble souple 105°C
1000SV 25 mm2
Flexible cable (105° C)
Plages appareil
Circuit breaker terminal pads
1000SV 25 mm2
NS160
Câble souple 105°C
1000SV 50 mm2
Flexible cable (105° C)
Plages appareil
Circuit breaker terminal pads
1000SV 50 mm2
NS250 / NB225
Câble souple 105°C
1000SV 95 mm2
Flexible cable (105° C)
Plages appareil
Circuit breaker terminal pads
1000SV 95 mm2
NS400 / NB400
(1b x 32 x 5mm *) ou 2b x 30 x 5mm
(1b x 32 x 5mm *) or 2b x 30 x 5mm
Plages appareil
Circuit breaker terminal pads
NS630 / NB600
(2b x 32 x 5mm *) ou 2b x 30 x 5mm
(2b x 32 x 5mm *) or 2b x 30 x 5mm
Plages appareil
Circuit breaker terminal pads
C801 à 1251 / CM / Masterpact: voir plans
de barres
*: il faut développer les barres
Guide Technique V9 / V9 Technical Guide
C801 to 1251 / CM / Masterpact: see bar
drawings.
*: necessary to develop bars
188
Installation de l’appareillage
Switchgear Installation
3.4.1.3.
Câbles (souple multi brins 105º C)
Cables (type NYAF 105º C)
Dans les autres cas: raccordement sur un
Jeu de barres traditionnel (barres plates),
pour les appareils fixes ou débrochables en
PAV ou PAR.
In the other cases: connection to a
conventional busbar (flat bars) for FC and
RC fixed or withdrawable circuit breakers.
Raccordement appareillage
Switchgear connection
Calibre
Rating
NB50
EZD100B/F/N/H
< 60A
Dérivations
Connections
Câble souple 105°C
1000SV 16 mm2
Flexible cable 105°C
Queues de barres (coté client)
Bar tails (customer side)
Plages appareil
Circuit breaker terminal pads
1000SV 16 mm2
NS100 / NB100
EZD100F/N/H ≥
60A up to 100A
Câble souple 105°C
1000SV 25 mm2
Flexible cable (105° C)
Plages appareil
Circuit breaker terminal pads
1000SV 25 mm2
NS160
Câble souple 105°C
1000SV 50 mm2
Flexible cable (105° C)
Plages appareil
Circuit breaker terminal pads
1000SV 50 mm2
NS250 / NB225
Câble souple 105°C
1000SV 95 mm2
Flexible cable (105° C)
Plages appareil
Circuit breaker terminal pads
1000SV 95 mm2
C801 à 1251 / CM / Masterpact: voir plans
de barres
*: il faut développer les barres
Guide Technique V9 / V9 Technical Guide
C801 to 1251 / CM / Masterpact: see bar
drawings.
*: necessary to develop bars
189
Installation de l’appareillage
Switchgear Installation
3.4.2.
Blokset Mf
3.4.2.1.
Barres rigides
Rigid bars
3.4.2.2.
Câbles (souple multi brins 105° C)
cables (type NYAF 105° C)
Ampères
Amperes
≤ 32 A
Section
Section
≤ 40 A
10 mm2
≤ 60 A
16 mm2
≤ 80 A
25 mm2
≤ 110 A
35 mm2
≤ 150 A
50 mm2
≤ 220 A
2 x 35 mm2
≤ 300 A
2 x 50 mm2
≤ 400 A
2 x 95 mm2
≤ 500 A
2 x 120 mm2
3.4.3.
6 mm2
Blokset Mw
3.4.3.1.
Barres rigides
Rigid bars
3.4.3.2.
Câbles (souple multi brins 105° C)
cables (type NYAF 105° C)
Ampères
Amperes
≤ 32 A
Section
Section
6 mm2
1 pince 6/10 mm2
≤ 40 A
10 mm
≤ 60 A
16 mm2
1 pince 16/25 mm2
≤ 80 A
25 mm
2
1 pince 16/25 mm2
≤ 110 A
35 mm2
1 pince 35 mm2
≤ 150 A
50 mm
2
1 pince 50 mm2
≤ 220 A
2 x 35 mm2
2 pinces 35 mm2
≤ 300 A
2 x 50 mm
2
2 pinces 50 mm2
≤ 500 A
3 x 50 mm2
3 pinces 50 mm2
Guide Technique V9 / V9 Technical Guide
2
1 pince 6/10 mm2
190
Sommaire du chapitre
Chapter contents
3.5. Blokset Ms
3.5.1.
Démarreurs et Variateurs ....................................................................... 192
Trifasic soft starters and variable speed drivers
3.5.1.1.
ATV18 .......................................................................................... 192
Couple: constant
Torque: constant
3.5.1.2.
ATV18 .......................................................................................... 194
Couple: variable
Torque: variable
3.5.1.3.
ATV18 .......................................................................................... 196
Couple: Variable faible bruit
Torque: Low noise
3.5.1.4.
ATV58 .......................................................................................... 198
3.5.1.5.
ATV66 .......................................................................................... 201
Couple: constant
Torque: constant
3.5.1.6.
ATV66 .......................................................................................... 205
Couple: variable
Torque: variable
3.5.1.7.
ATV66 .......................................................................................... 209
Couple: Variable faible bruit
Torque: Low noise
3.5.1.8.
ATS46 .......................................................................................... 213
Coordination Type 1
Coordination Type 1
3.5.1.9.
ATS46 .......................................................................................... 218
Coordination Type 2
Coordination Type 2
3.5.1.10.
Service: Sévère
Service: Severe
ATS46 .......................................................................................... 228
Coordination Type 2
Coordination Type 2
3.5.2.
Service: Standard
Service: Standard
ATS46 .......................................................................................... 223
Coordination Type 1
Coordination Type 1
3.5.1.11.
Service: Standard
Service: Standard
Service: Sévère
Service: Severe
IP pour démarreurs et variateurs de vitesse ........................................ 233
IP for soft starters and variable speed drivers
Guide Technique V9 / V9 Technical Guide
191
Installation de l’appareillage
Switchgear Installation
Blokset Ms
3.5. Blokset Ms
3.5.1.
Démarreurs et Variateurs
Trifasic soft starters and variable speed drivers
3.5.1.1.
ATV18
220/240 V
Puissance
(kW)
Power
(kW)
3
Icc coord.
(kA)
Icc coord.
(kA)
50
4
Couple: constant
Torque: constant
ATV18
Disjoncteur
Couple: constant
Torque: constant
Contacteur
(1)
Contactor
(1)
LC1-D2510
ATV
GV2-L20
Calibre
(A)
Rating
(A)
18A
50
GV2-L22
25A
5.5
50
NS80H-MA
5.5
50
7.5
50
7.5
50
GK3-EF65
Température ambiant 40 °C
Ambient temperature 40 °C
Résistance
de freinage
Breaking
resistance
VW3-A16703
Raccordement
sect.
cable cross
section area
ATV -18U54M2
Inductance
de ligne
Line coil
area
VW3-A66503
LC1-D2510
ATV -18U72M2
VW3-A66504
VW3-A66701
50A
LC1-D3210
ATV -18U90M2
VW3-A66504
VW3-A66702
GK3-EF40
40A
LC1-D3210
ATV -18U90M2
VW3-A66504
VW3-A66702
NS80H-MA
50A
LC1-D5011
ATV -18D12M2
VW3-A66504
VW3-A66702
65A
LC1-D5011
ATV -18D12M2
VW3-A66504
VW3-A66702
Circuit
Breaker
ATV
(1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter
le nombre de modules.
(2): Les ventilateurs ont été définis pour chaque unité fonctionnel sans la résistance
de freinage. Pour installer la résistance de freinage, consulter GIB.
Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653.
Guide Technique V9 / V9 Technical Guide
2,5 mm2
Numéro de mod. avec ou
sans resit.frenage.
Number of mod. with or
without break. resist.
9
Ventilateur
(2)
Fan
(2)
4606 N
2,5 mm2
9
4606 N
4 mm
2
9
4606 N
4 mm
2
9
4606 N
6 mm
2
9
4606 N
6 mm
2
9
4606 N
(1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the
number of modules.
(2): The fans were defined for functional units without breaking resistance. If breaking
resistance is needed consult BIM.
Single line diagrams, according Telemecanique catalogue ART. 16653.
192
Installation de l’appareillage
Switchgear Installation
Blokset Ms
380/460 V
Puissance
(kW)
Power
(kW)
0.75
Icc coord.
(kA)
Icc coord.
(kA)
50
1.5
ATV18
Disjoncteur
Couple: constant
Torque: constant
Contacteur
(1)
Contactor
(1)
LC1-K0610
ATV
GV2-L08
Calibre
(A)
Rating
(A)
4A
15
GV2-L10
6,3A
2.2
15
GV2-L14
3
15
4
15
5.5
7.5
Température ambiant 40 °C
Ambient temperature 40 °C
Résistance
de freinage
Breaking
resistance
VW3-A16702
Raccordement
sect.
cable cross
section area
ATV -18U18N4
Inductance
de ligne
Line coil
area
VW3-A66501
2,5 mm2
Numéro de mod. avec ou
sans resit.frenage.
Number of mod. with or
without break. resist.
9
Ventilateur
(2)
Fan
(2)
4606 N
LC1-K0610
ATV -18U29N4
VW3-A66501
VW3-A16702
2,5 mm2
10A
LC1-K0910
ATV -18U41N4
9
4606 N
VW3-A66502
VW3-A16702
2,5 mm
2
9
4606 N
ATV -18U54N4
VW3-A66503
VW3-A16704
2,5 mm
2
GV2-L16
14A
LC1-D1210
GV2-L16
14A
LC1-D1810
9
4606 N
ATV -18U72N4
VW3-A66502
VW3-A16704
2,5 mm
2
9
4606 N
LC1-D2510
ATV -18U90N4
VW3-A66503
VW3-A66701
2,5 mm
2
15
GV2-L20
18A
15
GV2-L22
25A
LC1-D3210
ATV -18D12N4
VW3-A66503
VW3-A66701
11
25
NS80H-MA
11
25
GK3-EF40
50A
LC1-D4011
ATV -18D16N4
VW3-A66504
VW3-A66702
40A
LC1-D4011
ATV -18D16N4
VW3-A66504
VW3-A66702
15
25
15
25
NS80H-MA
50A
LC1-D5011
ATV -18D23N4
VW3-A66504
GK3-EF65
65A
LC1-D5011
ATV -18D23N4
VW3-A66504
Circuit
Breaker
ATV
(1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter
le nombre de modules.
(2): Les ventilateurs ont été définis pour chaque unité fonctionnel sans la résistance
de freinage. Pour installer la résistance de freinage, consulter GIB.
Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653.
Guide Technique V9 / V9 Technical Guide
9
4606 N
4 mm
2
9
4606 N
4 mm
2
12
4606 N
4 mm
2
12
4606 N
VW3-A66702
4 mm2
12
4606 N
VW3-A66702
2
12
4606 N
4 mm
(1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the
number of modules.
(2): The fans were defined for functional units without breaking resistance. If breaking
resistance is needed consult BIM.
Single line diagrams, according Telemecanique catalogue ART. 16653.
193
Installation de l’appareillage
Switchgear Installation
Blokset Ms
3.5.1.2.
ATV18
220/240 V
Puissance
(kW)
Power
(kW)
3
Icc coord.
(kA)
Icc coord.
(kA)
50
4
Couple: variable
Torque: variable
ATV18
Disjoncteur
Couple: variable
Torque: variable
GV2-L20
Calibre
(A)
Rating
(A)
18A
Contacteur
(1)
Contactor
(1)
LC1-D2510
Résistance
de freinage
Breaking
resistance
VW3-A16703
Raccordement
sect.
cable cross
section area
ATV -18U54M2
Inductance
de ligne
Line coil
area
VW3-A66503
50
GV2-L22
25A
LC1-D2510
ATV -18U72M2
VW3-A66504
VW3-A66701
5.5
50
NS80H-MA
50A
LC1-D3210
ATV -18U90M2
VW3-A66504
VW3-A66702
5.5
50
7.5
50
GK3-EF40
40A
LC1-D3210
ATV -18U90M2
VW3-A66504
VW3-A66702
NS80H-MA
50A
LC1-D5011
ATV -18D12M2
VW3-A66504
VW3-A66702
7.5
50
GK3-EF65
65A
LC1-D5011
ATV -18D12M2
VW3-A66504
VW3-A66702
Circuit
Breaker
ATV
Température ambiant 40 °C
Ambient temperature 40 °C
ATV
(1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter
le nombre de modules.
(2): Les ventilateurs ont été définis pour chaque unité fonctionnel sans la résistance
de freinage. Pour installer la résistance de freinage, consulter GIB.
Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653.
Guide Technique V9 / V9 Technical Guide
2,5 mm2
Numéro de mod. avec ou
sans resit. freinage.
Number of mod. with or
without break. resist.
9
Ventilateur
(2)
Fan
(2)
4606 N
2,5 mm2
9
4606 N
4 mm
2
9
4606 N
4 mm
2
9
4606 N
6 mm
2
9
4606 N
6 mm
2
9
4606 N
(1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the
number of modules.
(2): The fans were defined for functional units without breaking resistance. If breaking
resistance is needed consult BIM.
Single line diagrams, according Telemecanique catalogue ART. 16653.
194
Installation de l’appareillage
Switchgear Installation
Blokset Ms
380/460 V
Puissance
(kW)
Power
(kW)
0.75
Icc coord.
(kA)
Icc coord.
(kA)
50
1.5
ATV18
Disjoncteur
Couple: variable
Torque: variable
Contacteur
(1)
Contactor
(1)
LC1-K0610
ATV
GV2-L08
Calibre
(A)
Rating
(A)
4A
15
GV2-L10
6,3A
2.2
15
GV2-L14
3
15
4
15
5.5
7.5
Température ambiant 40 °C
Ambient temperature 40 °C
Résistance
de freinage
Breaking
resistance
VW3-A16702
Raccordement
sect.
cable cross
section area
ATV -18U18N4
Inductance
de ligne
Line coil
area
VW3-A66501
LC1-K0610
ATV -18U29N4
VW3-A66501
10A
LC1-K0910
ATV -18U41N4
GV2-L16
14A
LC1-D1210
GV2-L16
14A
LC1-D1810
15
GV2-L20
18A
15
GV2-L22
25A
11
25
NS80H-MA
11
25
GK3-EF40
15
25
NS80H-MA
Circuit
Breaker
2,5 mm2
Numéro de mod. avec ou
sans resit. freinage.
Number of mod. with or
without break. resist.
9
Ventilateur
(2)
Fan
(2)
4606 N
VW3-A16702
2,5 mm2
9
4606 N
VW3-A66502
VW3-A16702
2,5 mm
2
9
4606 N
ATV -18U54N4
VW3-A66503
VW3-A16704
2,5 mm
2
9
4606 N
ATV -18U72N4
VW3-A66502
VW3-A16704
2,5 mm
2
9
4606 N
LC1-D2510
ATV -18U90N4
VW3-A66503
VW3-A66701
2,5 mm
2
LC1-D3210
ATV -18D12N4
VW3-A66503
VW3-A66701
50A
LC1-D4011
ATV -18D16N4
VW3-A66504
VW3-A66702
40A
LC1-D4011
ATV -18D16N4
VW3-A66504
VW3-A66702
50A
LC1-D5011
ATV -18D23N4
VW3-A66504
VW3-A66702
ATV
(1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter
le nombre de modules.
(2): Les ventilateurs ont été définis pour chaque unité fonctionnel sans la résistance
de freinage. Pour installer la résistance de freinage, consulter GIB.
Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653.
Guide Technique V9 / V9 Technical Guide
9
4606 N
4 mm
2
9
4606 N
4 mm
2
12
4606 N
4 mm
2
12
4606 N
4 mm2
12
4606 N
(1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the
number of modules.
(2): The fans were defined for functional units without breaking resistance. If breaking
resistance is needed consult BIM.
Single line diagrams, according Telemecanique catalogue ART. 16653.
195
Installation de l’appareillage
Switchgear Installation
Blokset Ms
3.5.1.3.
ATV18
220/240 V
Puissance
(kW)
Power
(kW)
3
Icc coord.
(kA)
Icc coord.
(kA)
50
4
Couple: Variable faible bruit
Torque: Low noise
ATV18
Disjoncteur
Couple: Variable faible bruit
Torque: Low noise
Contacteur
(1)
Contactor
(1)
LC1-D2510
ATV
GV2-L22
Calibre
(A)
Rating
(A)
25A
50
GV2-L22
25A
5.5
50
NS80H-MA
5.5
50
GK3-EF40
Circuit Breaker
ATV -18U54M2
Inductance
de ligne
Line coil
area
VW3-A66503
Résistance
de freinage
Breaking
resistance
VW3-A16703
LC1-D2510
ATV -18U90M2
VW3-A66504
VW3-A66702
50A
LC1-D3210
ATV -18D12M2
VW3-A66504
VW3-A66702
40A
LC1-D3210
ATV -18D12M2
VW3-A66504
VW3-A66702
ATV
(1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter
le nombre de modules.
(2): Les ventilateurs ont été définis pour chaque unité fonctionnel sans la résistance
de freinage. Pour installer la résistance de freinage, consulter GIB.
Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653.
Guide Technique V9 / V9 Technical Guide
Température ambiant 40 °C
Ambient temperature 40 °C
Raccordement
sect.
cable cross
section area
2,5 mm2
Numéro de mod. avec ou
sans resit.frenage.
Number of mod. with or
without break. resist.
9
Ventilateur
(2)
Fan
(2)
4606 N
2,5 mm2
9
4606 N
2
9
4606 N
2
9
4606 N
4 mm
4 mm
(1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the
number of modules.
(2): The fans were defined for functional units without breaking resistance. If breaking
resistance is needed consult BIM.
Single line diagrams, according Telemecanique catalogue ART. 16653.
196
Installation de l’appareillage
Switchgear Installation
Blokset Ms
380/460 V
Puissance
(kW)
Power
(kW)
0.75
Icc coord.
(kA)
Icc coord.
(kA)
50
1.5
ATV18
Disjoncteur
Couple: Variable faible bruit
Torque: Low noise
Contacteur
(1)
Contactor
(1)
LC1-K0610
ATV
GV2-L08
Calibre
(A)
Rating
(A)
4A
15
GV2-L10
6,3A
2.2
15
GV2-L14
3
15
4
15
5.5
11
Température ambiant 40 °C
Ambient temperature 40 °C
ATV -18U29N4
Inductance
de ligne
Line coil
area
VW3-A66501
Résistance
de freinage
Breaking
resistance
VW3-A16702
LC1-K0610
ATV -18U41N4
VW3-A66502
10A
LC1-K0910
ATV -18U54N4
GV2-L16
14A
LC1-D1210
GV2-L20
18A
LC1-D1810
15
GV2-L20
18A
25
GK3-EF40
40A
Circuit Breaker
2,5 mm2
Numéro de mod. avec ou
sans resit.frenage.
Number of mod. with or
without break. resist.
9
Ventilateur
(2)
Fan
(2)
4606 N
VW3-A16702
2,5 mm2
9
4606 N
VW3-A66503
VW3-A16704
2
9
4606 N
ATV -18U72N4
VW3-A66502
VW3-A16704
2
9
4606 N
ATV -18U90N4
VW3-A66503
VW3-A66701
2
9
4606 N
LC1-D2510
ATV -18D12N4
VW3-A66503
VW3-A66701
2
9
4606 N
LC1-D4011
ATV -18D23N4
VW3-A66504
VW3-A66702
12
4606 N
ATV
(1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter
le nombre de modules.
(2): Les ventilateurs ont été définis pour chaque unité fonctionnel sans la résistance
de freinage. Pour installer la résistance de freinage, consulter GIB.
Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653.
Guide Technique V9 / V9 Technical Guide
Raccordement
sect.
cable cross
section area
2,5 mm
2,5 mm
2,5 mm
2,5 mm
2
4 mm
(1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the
number of modules.
(2): The fans were defined for functional units without breaking resistance. If breaking
resistance is needed consult BIM.
Single line diagrams, according Telemecanique catalogue ART. 16653.
197
Installation de l’appareillage
Switchgear Installation
Blokset Ms
3.5.1.4.
ATV58
220/240 V
Puissance
(kW)
Power
(kW)
1.5
Icc coord.
(kA)
Icc coord.
(kA)
50
2.2
ATV58
Disjoncteur
Température ambiant 30 °C
Ambient temperature 30 °C
Contacteur
(1)
Contactor
(3)
LC1-D1810
ATV
Inductance
de ligne
Line coil
GV2-L14
Calibre
(A)
Rating
(A)
10A
ATV -58HU29M2
50
GV2-L16
14A
LC1-D1810
3
50
GV2-L20
25A
4
50
GV2-L22
5.5
100
NS80H-MA
7.5
100
NS80H-MA
Circuit
breaker
ATV
VW3-A66502
Résistance
de freinage
Break.
Resistance
VW3-A58702
ATV -58HU41M2
VW3-A66503
LC1-D2510
ATV -58HU54M2
VW3-A66503
25A
LC1-D2510
ATV -58HU72M2
VW3-A66504
50A
LC1-D4011
ATV -58HU90M2
VW3-A66504
50A
LC1-D5011
ATV -58HD12M2
VW3-A66504
Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de
puissance doivent être déclassés de 11% pour ATV 58. Dans le cas d’une
température ambiant plus élevée, consulter GIB.
(1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter
le nombre de modules.
(2): Les ventilateurs ont été définis pour chaque unité fonctionnel sans la résistance
de freinage. Pour installer la résistance de freinage, consulter GIB.
*: pour ce cas, quand utiliser la résistance de freinage le nombre de modules doit être
12.
Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653.
Guide Technique V9 / V9 Technical Guide
Raccord.
section
cable cross
section area
2,5 mm2
Résistance de
freinage
Break.
Resistance
VW3-A58732
Nr. de Modules avec ou
sans résistance
Nb. Mod. with or
without break. resistance
9
Ventilateur
(2)
Fan
(2)
4606 N
VW3-A58704
2,5 mm2
VW3-A58733
9
4606 N
VW3-A58704
2
VW3-A58733
9
4606 N
2
2,5 mm
VW3-A58736
9*
4606 N
2
VW3-A58736
9*
4606 N
2
VW3-A58737
9*
4606 N
2,5 mm
4 mm
6 mm
Note: in case of switchboard installed in an ambient with 35 °C the values of power
must be derated in 11% for ATV 58. In case of higher ambient temperature, consult
BIM.
(1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the
number of modules
(2): The fans were defined for functional units without breaking resistance. If breaking
resistance is needed consult BIM.
*: for this case, when using breaking resistance the number of modules must be 12.
Single line diagrams, according Telemecanique catalogue ART. 16653.
198
Installation de l’appareillage
Switchgear Installation
Blokset Ms
380/415 V
Puissance
(kW)
Power
(kW)
0.75
Icc coord.
(kA)
Icc coord.
(kA)
50
1.5
ATV58
Disjoncteur
Température ambiant 30 °C
Ambient temperature 30 °C
Contacteur
(1)
Contactor
(3)
LC1-D1810
ATV
GV2-L08
Calibre
(A)
Rating
(A)
4A
ATV
Inductance
de ligne
Line coil
ATV -58HU18N4
VW3-A66501
Résistance
de freinage
Break.
Resistance
VW3-A58702
50
GV2-L10
6,3A
LC1-D1810
ATV -58HU29N4
VW3-A66501
VW3-A58702
2,5 mm2
2.2
50
GV2-L14
VW3-A58732
9
4606 N
10A
LC1-D1810
ATV -58HU41N4
VW3-A66502
VW3-A58702
2,5 mm
2
VW3-A58732
9
4606 N
GV2-L16
14A
LC1-D1810
ATV -58HU54N4
VW3-A66502
VW3-A58703
2,5 mm
2
3
50
4
50
VW3-A58734
9
4606 N
GV2-L16
14A
LC1-D1810
ATV -58HU72N4
VW3-A66502
VW3-A58703
2,5 mm
2
VW3-A58734
9
4606 N
50
GV2-L22
25A
LC1-D2510
ATV -58HU90N4
VW3-A66503
2,5 mm
2
5.5
7.5
25
NS80H-MA
50A
LC1-D4011
ATV -58HD12N4
VW3-A66503
11
25
NS80H-MA
50A
LC1-D4011
ATV -58HD16N4
VW3-A66504
15
25
NS80H-MA
50A
LC1-D5011
ATV -58HD23N4
VW3-A66504
Circuit
breaker
Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de
puissance doivent être déclassés de 11% pour ATV 58. Dans le cas d’une
température ambiant plus élevée, consulter GIB.
(1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter
le nombre de modules.
(2): Les ventilateurs ont été définis pour chaque unité fonctionnel sans la résistance
de freinage. Pour installer la résistance de freinage, consulter GIB.
*: pour ce cas, quand utiliser la résistance de freinage le nombre de modules doit être
12.
Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653.
Guide Technique V9 / V9 Technical Guide
Raccord.
section
cable cross
section area
2,5 mm2
Résistance de
freinage
Break.
Resistance
VW3-A58732
Nr. de Modules avec ou
sans résistance
Nb. Mod. with or
without break. resistance
9
Ventilateur
(2)
Fan
(2)
4606 N
VW3-A58735
9
4606 N
4 mm
2
VW3-A58735
9
4606 N
4 mm
2
VW3-A58736
9*
4606 N
6 mm
2
VW3-A58736
12
4606 N
Note: in case of switchboard installed in an ambient with 35 °C the values of power
must be derated in 11% for ATV 58. In case of higher ambient temperature, consult
BIM.
(1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the
number of modules
(2): The fans were defined for functional units without breaking resistance. If breaking
resistance is needed consult BIM.
*: for this case, when using breaking resistance the number of modules must be 12.
Single line diagrams, according Telemecanique catalogue ART. 16653.
199
Installation de l’appareillage
Switchgear Installation
Blokset Ms
440/500 V
Puissance
(kW)
Power
(kW)
0.75
Icc coord.
(kA)
Icc coord.
(kA)
50
1.5
ATV58
Disjoncteur
Température ambiant 30 °C
Ambient temperature 30 °C
Contacteur
(1)
Contactor
(3)
LC1-D1810
ATV
GV2-L08
Calibre
(A)
Rating
(A)
4A
ATV
Inductance
de ligne
Line coil
ATV -58HU18N4
VW3-A66501
Résistance
de freinage
Break.
Resistance
VW3-A58702
50
GV2-L10
6,3A
LC1-D2510
ATV -58HU29N4
VW3-A66501
VW3-A58702
2,5 mm2
2.2
50
GV2-L10
VW3-A58732
9
4606 N
6,3A
LC1-D2510
ATV -58HU41N4
VW3-A66502
VW3-A58702
2,5 mm
2
VW3-A58732
9
4606 N
GV2-L14
10A
LC1-D2510
ATV -58HU54N4
VW3-A66502
VW3-A58703
2,5 mm
2
3
10
4
10
VW3-A58734
9
4606 N
GV2-L14
10A
LC1-D2510
ATV -58HU72N4
VW3-A66502
VW3-A58703
2,5 mm
2
VW3-A58734
9
4606 N
10
GV2-L22
25A
LC1-D4011
ATV -58HU90N4
VW3-A66503
4 mm
2
5.5
7.5
VW3-A58735
9
4606 N
25
NS80H-MA
50A
LC1-D4011
ATV -58HD12N4
VW3-A66503
4 mm
2
VW3-A58735
9
4606 N
11
25
NS80H-MA
50A
LC1-D4011
ATV -58HD16N4
VW3-A66504
4 mm
2
VW3-A58736
9*
4606 N
15
25
NS80H-MA
50A
LC1-D4011
ATV -58HD23N4
VW3-A66504
4 mm
2
VW3-A58736
12
4606 N
Circuit
breaker
Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de
puissance doivent être déclassés de 11% pour ATV 58. Dans le cas d’une
température ambiant plus élevée, consulter GIB.
(1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter
le nombre de modules.
(2): Les ventilateurs ont été définis pour chaque unité fonctionnel sans la résistance
de freinage. Pour installer la résistance de freinage, consulter GIB.
*: pour ce cas, quand utiliser la résistance de freinage le nombre de modules doit être
12.
Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653.
Guide Technique V9 / V9 Technical Guide
Raccord.
section
cable cross
section area
2,5 mm2
Résistance de
freinage
Break.
Resistance
VW3-A58732
Nr. de Modules avec ou
sans résistance
Nb. Mod. with or
without break. resistance
9
Ventilateur
(2)
Fan
(2)
4606 N
Note: in case of switchboard installed in an ambient with 35 °C the values of power
must be derated in 11% for ATV 58. In case of higher ambient temperature, consult
BIM.
(1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the
number of modules
(2): The fans were defined for functional units without breaking resistance. If breaking
resistance is needed consult BIM.
*: for this case, when using breaking resistance the number of modules must be 12.
Single line diagrams, according Telemecanique catalogue ART. 16653.
200
Installation de l’appareillage
Switchgear Installation
Blokset Ms
3.5.1.5.
ATV66
220/240 V
Puissance
(kW)
Power
(kW)
0.75
Icc coord.
(kA)
Icc coord.
(kA)
130
1.5
Couple: constant
Torque: constant
ATV66
Disjoncteur
Couple: constant
Torque: constant
Contacteur
(1)
Contactor
(1)
LC1-D1810
ATV
GV2-L20
Calibre
(A)
Rating
(A)
8A
130
GV2-L20
18A
2.2
130
GV2-L20
3
100
4
100
5.5
7.5
Température ambiant 30 °C
Ambient temperature 30 °C
ATV
Inductance
de ligne
Line coil
Raccord.
section
cable cross
section area
2,5 mm2
Résistance de
freinage
Break.
Resistance
VW3-A66701
Nr. de Modules avec ou
sans résistance
Nb. Mod. with or
without break. resistance
9
Ventilateur
(2)
Fan
(2)
4606 N
ATV -66U41M2
VW3-A66503
LC1-D1810
ATV -66U41M2
VW3-A66503
2,5 mm2
18A
LC1-D1810
VW3-A66701
9
4606 N
ATV -66U41M2
VW3-A66503
2
VW3-A66701
9
4606 N
LC1-D3210
ATV -66U72M2
VW3-A66504
2
NS80H-MA
25A
NS80H-MA
25A
LC1-D3210
ATV -66U72M2
VW3-A66504
100
NS80H-MA
100
NS80H-MA
50A
LC1-D4011
ATV -66U90M2
VW3-A66504
50A
LC1-D5011
ATV -66D12M2
VW3-A66505
11
50
11
100
GK3-EF65
65A
LC1-D6511
ATV -66D16M2
VW3-A66505
NS80H-MA
80A
LC1-D8011
ATV -66D16M2
VW3-A66505
15
50
GK3-EF80
80A
LC1-D8011
15
100
NS80H-MA
80A
LC1-D8011
ATV -66D23M2
ATV -66D23M2
18.5
85
NS100H-MA
100A
LC1-D9511
18.5
85
NS100H-MA
100A
LC1-D115006
22
85
NS100H-MA
100A
LC1-D115006
ATV -66D33M2
22
100
NS100H-MA
100A
LC1-D115006
ATV -66D33M2
30
85
NS160H-MA
150A
LC1-D150006
ATV -66D46M2
30
100
NS160H-MA
150A
LC1-D150006
ATV -66D46M2
Circuit
breaker
Guide Technique V9 / V9 Technical Guide
2,5 mm
VW3A66702
12
4606 N
2
VW3A66702
12
4606 N
2
VW3A66702
12
4606 N
2
VW3-A66703
12
4606 N
2
VW3-A66704
12 *
2 x 4606 N
2
16 mm
VW3-A66704
12 *
2 x 4606 N
VW3-A66506
16 mm2
VW3-A66704
24 **
3 x 4606 ES
VW3-A66506
2
16 mm
VW3-A66704
24 **
3 x 4606 ES
ATV -66D33M2
25 mm2
VW3-A66704
24 **
3 x 4606 ES
ATV -66D33M2
2
35 mm
VW3-A66704
24 **
3 x 4606 ES
35 mm2
VW3-A66704
24 **
3 x 4606 ES
2
35 mm
VW3-A66704
24 **
4 x 4606 ES
35 mm2
VW3-A66704
36 ***
4 x 4606 ES
2
VW3-A66704
36 ***
4 x 4606 ES
VW3-A66506
VW3-A66507
2,5 mm
4 mm
4 mm
6 mm
10 mm
35 mm
201
Installation de l’appareillage
Switchgear Installation
Blokset Ms
Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de
puissance doivent être déclassés de 11% pour ATV 66. Dans le cas d’une
température ambiant plus élevée, consulter GIB.
(1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter
le nombre de modules.
(2): Les ventilateurs ont été définis pour chaque unité fonctionnel sans la résistance
de freinage. Pour installer la résistance de freinage, consulter GIB.
*: plus 12 modules seulement pour résistance de freinage
**: plus 12 modules seulement pour résistance de freinage ou utiliser extension
arrière de 700X2200x400
***: plus extension arrière 700X2200x400 pour inductance de ligne et résistance de
freinage
Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653.
Guide Technique V9 / V9 Technical Guide
Note: in case of switchboard installed in an ambient with 35 °C the values of power
must be derated in 11% for ATV 66. In case of higher ambient temperature, consult
BIM.
(1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the
number of modules.
(2): The fans were defined for functional units without breaking resistance. If breaking
resistance is needed consult BIM.
*: add12 modules only for breaking resistance
**: add 12 modules only for breaking resistance or add rear column 700X2200x400
***: add rear column 700X2200x400 for line coil and breaking resistance
Single line diagrams, according Telemecanique catalogue ART. 16653.
202
Installation de l’appareillage
Switchgear Installation
Blokset Ms
380/460 V
Puissance
(kW)
Power
(kW)
0.75
Icc coord.
(kA)
Icc coord.
(kA)
130
1.5
ATV66
Disjoncteur
Couple: constant
Torque: constant
Contacteur
(1)
Contactor
(1)
LC1-D0910
ATV
GV2-L08
Calibre
(A)
Rating
(A)
4A
50
GV2-L10
6,3A
2.2
50
GV2-L14
3
50
4
50
5.5
7.5
Température ambiant 30 °C
Ambient temperature 30 °C
ATV
Inductance
de ligne
Line coil
Raccord.
section
cable cross
section area
2,5 mm2
Résistance de
freinage
Break.
Resistance
VW3-A16702
Nr. de Modules avec ou
sans résistance
Nb. Mod. with or
without break. resistance
9
Ventilateur
(2)
Fan
(2)
4606 N
ATV -66U41N4
VW3-A66502
LC1-D1810
ATV -66U41N4
VW3-A66501
2,5 mm2
10A
LC1-D1810
VW3-A16702
9
4606 N
ATV -66U41N4
VW3-A66502
2
VW3-A16702
9
4606 N
LC1-D2510
ATV -66U54N4
VW3-A66502
2
GV2-L16
14A
GV2-L20
18A
VW3-A16704
9
4606 N
LC1-D2510
ATV -66U72N4
VW3-A66502
2
VW3-A16704
9
4606 N
25A
LC1-D2510
ATV -66U90N4
VW3-A66503
2
50
GV2-L22
50
GV2-L22
25A
LC1-D3210
ATV -66D12N4
VW3-A66503
11
70
15
70
NS80H-MA
50A
LC1-D4011
ATV -66D16N4
VW3-A66504
NS80H-MA
50A
LC1-D5011
ATV -66D23N4
VW3-A66504
Circuit
breaker
15
25
GK3-EF65
65A
LC1-D5011
ATV -66D23N4
18.5
25
GK3-EF65
65A
LC1-D6511
ATV -66D33N4
18.5
70
NS80H-MA
80A
LC1-D8011
ATV -66D33N4
22
25
GK3-EF80
80A
LC1-D8011
ATV -66D33N4
22
70
NS80H-MA
80A
LC1-D8011
ATV -66D33N4
30
25
GK3-EF80
80A
LC1-D8011
ATV -66D46N4
30
70
NS80H-MA
80A
LC1-D8011
ATV -66D46N4
37
35
NS100H-MA
100A
LC1-D115006
ATV -66D54N4
37
70
NS100H-MA
100A
LC1-D115006
ATV -66D54N4
45
35
NS160H-MA
150A
LC1-D115006
ATV -66D64N4
45
70
NS160H-MA
150A
LC1-D115006
ATV -66D64N4
55
35
NS160H-MA
150A
LC1-D150006
ATV -66D79N4
55
70
NS160H-MA
150A
LC1-D150006
ATV -66D79N4
Guide Technique V9 / V9 Technical Guide
2,5 mm
2,5 mm
2,5 mm
VW3-A66701
12
4606 N
2
VW3-A66701
12
4606 N
2
VW3-A66702
12
4606 N
2
VW3-A66702
12
2 x 4606 N
2,5 mm
4 mm
4 mm
6 mm
12
4606 N
2
10 mm
VW3-A66703
24
3 x 4606 ES
16 mm2
VW3-A66703
24
3 x 4606 ES
2
16 mm
VW3-A66703
24
3 x 4606 ES
16 mm2
VW3-A66703
24
3 x 4606 ES
2
16 mm
VW3-A66703
24
3 x 4606 ES
16 mm2
VW3-A66703
24
3 x 4606 ES
2
VW3-A66704
36 ***
4 x 4606 ES
2
VW3-A66704
36 ***
4 x 4606 ES
2
VW3-A66704
36 ***
4 x 4606 ES
2
VW3-A66704
36 ***
4 x 4606 ES
2
VW3-A66704
36 ***
4 x 4606 ES
2
VW3-A66704
36 ***
4 x 4606 ES
6 mm2
VW3-A66505
VW3-A66505
VW3-A66505
35 mm
VW3-A66506
35 mm
35 mm
VW3-A66506
35 mm
35 mm
VW3-A66506
35 mm
203
Installation de l’appareillage
Switchgear Installation
Blokset Ms
Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de
puissance doivent être déclassés de 11% pour ATV 66. Dans le cas d’une
température ambiant plus élevée, consulter GIB.
(1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter
le nombre de modules.
(2): Les ventilateurs ont été définis pour chaque unité fonctionnel sans la résistance
de freinage. Pour installer la résistance de freinage, consulter GIB.
*: plus 12 modules seulement pour résistance de freinage
**: plus 12 modules seulement pour résistance de freinage ou utiliser extension
arrière de 700X2200x400
***: plus extension arrière 700X2200x400 pour inductance de ligne et résistance de
freinage
Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653.
Guide Technique V9 / V9 Technical Guide
Note: in case of switchboard installed in an ambient with 35 °C the values of power
must be derated in 11% for ATV 66. In case of higher ambient temperature, consult
BIM.
(1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the
number of modules.
(2): The fans were defined for functional units without breaking resistance. If breaking
resistance is needed consult BIM.
*: add12 modules only for breaking resistance
**: add 12 modules only for breaking resistance or add rear column 700X2200x400
***: add rear column 700X2200x400 for line coil and breaking resistance
Single line diagrams, according Telemecanique catalogue ART. 16653.
204
Installation de l’appareillage
Switchgear Installation
Blokset Ms
3.5.1.6.
\ATV66
220/240 V
Puissance
(kW)
Power
(kW)
0.75
Icc coord.
(kA)
Icc coord.
(kA)
130
1.5
Couple: variable
Torque: variable
ATV66
Disjoncteur
Couple: variable
Torque: variable
Contacteur
(1)
Contactor
(1)
LC1-D1810
ATV
GV2-L20
Calibre
(A)
Rating
(A)
8A
130
GV2-L20
18A
2.2
130
GV2-L20
3
130
4
100
5.5
Température ambiant 30 °C
Ambient temperature 30 °C
ATV
Inductance
de ligne
Line coil
Raccord.
section
cable cross
section area
2,5 mm2
Résistance de
freinage
Break.
Resistance
VW3-A66701
Nr. de Modules avec ou
sans résistance
Nb. Mod. with or
without break. resistance
9
Ventilateur
(2)
Fan
(2)
4606 N
ATV -66U41M2
VW3-A66504
LC1-D1810
ATV -66U41M2
VW3-A66504
2,5 mm2
18A
LC1-D1810
VW3-A66701
9
4606 N
ATV -66U41M2
VW3-A66504
2
VW3-A66701
9
4606 N
LC1-D2510
ATV -66U41M2
VW3-A66504
2
GV2-L22
25A
NS80H-MA
25A
VW3-A66701
9
4606 N
LC1-D4011
ATV -66U72M2
VW3-A66504
2
4 mm
VW3A66702
12
4606 N
100
NS80H-MA
50A
LC1-D4011
ATV -66U72M2
VW3-A66504
4 mm2
7.5
100
NS80H-MA
VW3A66702
12
4606 N
50A
LC1-D5011
ATV -66U90M2
VW3-A66505
2
VW3A66702
12
4606 N
GK3-EF65
65A
LC1-D6511
ATV -66D12M2
VW3-A66505
2
11
50
11
100
VW3-A66703
12
2 x 4606 ES
NS80H-MA
80A
LC1-D8011
ATV -66D12M2
VW3-A66505
2
16 mm
VW3-A66703
12
2 x 4606 ES
15
50
GK3-EF80
80A
LC1-D8011
15
100
NS80H-MA
80A
LC1-D8011
ATV -66D23M2
VW3-A66506
16 mm2
VW3-A66704
24 **
3 x 4606 ES
ATV -66D23M2
VW3-A66506
2
16 mm
VW3-A66704
24 **
3 x 4606 ES
18.5
85
NS100H-MA
100A
LC1-D9511
ATV -66D23M2
18.5
100
NS100H-MA
100A
LC1-D115006
ATV -66D23M2
25 mm2
VW3-A66704
24 **
3 x 4606 ES
2
25 mm
VW3-A66704
24 **
4 x 4606 ES
22
85
NS100H-MA
100A
LC1-D115006
ATV -66D33M2
22
100
NS100H-MA
100A
LC1-D115006
ATV -66D33M2
35 mm2
VW3-A66704
24 **
4 x 4606 ES
2
35 mm
VW3-A66704
24 **
4 x 4606 ES
30
85
NS160H-MA
150A
LC1-D150006
ATV -66D33M2
35 mm2
VW3-A66704
24 **
4 x 4606 ES
2
30
100
NS160H-MA
150A
LC1-D150006
ATV -66D33M2
37
85
NS250H-MA
220A
LC1-F185
ATV -66D46M2
VW3-A66704
24 **
4 x 4606 ES
2
50 mm
VW3-A66704
36 ***
4 x 4606 ES
37
100
NS250H-MA
220A
LC1-F185
ATV -66D46M2
50 mm2
VW3-A66704
36 ***
4 x 4606 ES
Circuit
breaker
Guide Technique V9 / V9 Technical Guide
VW3 A66506
VW3-A66507
VW3-A66507
VW3-A66507
2,5 mm
2,5 mm
6 mm
10 mm
35 mm
205
Installation de l’appareillage
Switchgear Installation
Blokset Ms
Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de
puissance doivent être déclassés de 11% pour ATV 66. Dans le cas d’une
température ambiant plus élevée, consulter GIB.
(1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter
le nombre de modules.
(2): Les ventilateurs ont été définis pour chaque unité fonctionnel sans la résistance
de freinage. Pour installer la résistance de freinage, consulter GIB.
*: plus 12 modules seulement pour résistance de freinage
**: plus 12 modules seulement pour résistance de freinage ou utiliser extension
arrière de 700X2200x400
***: plus extension arrière 700X2200x400 pour inductance de ligne et résistance de
freinage
Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653.
Guide Technique V9 / V9 Technical Guide
Note: in case of switchboard installed in an ambient with 35 °C the values of power
must be derated in 11% for ATV 66. In case of higher ambient temperature, consult
BIM.
(1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the
number of modules.
(2): The fans were defined for functional units without breaking resistance. If breaking
resistance is needed consult BIM.
*: add12 modules only for breaking resistance
**: add 12 modules only for breaking resistance or add rear column 700X2200x400
***: add rear column 700X2200x400 for line coil and breaking resistance
Single line diagrams, according Telemecanique catalogue ART. 16653.
206
Installation de l’appareillage
Switchgear Installation
Blokset Ms
380/460 V
Puissance
(kW)
Power
(kW)
0.75
Icc coord.
(kA)
Icc coord.
(kA)
130
1.5
ATV66
Disjoncteur
Couple: variable
Torque: variable
Contacteur
(1)
Contactor
(1)
LC1-D0910
ATV
GV2-L08
Calibre
(A)
Rating
(A)
4A
50
GV2-L10
6,3A
2.2
50
GV2-L14
3
50
4
50
5.5
7.5
Température ambiant 30 °C
Ambient temperature 30 °C
ATV
Inductance
de ligne
Line coil
Raccord.
section
cable cross
section area
2,5 mm2
Résistance de
freinage
Break.
Resistance
VW3-A16702
Nr. de Modules avec ou
sans résistance
Nb. Mod. with or
without break. resistance
9
Ventilateur
(2)
Fan
(2)
4606 N
ATV -66U41N4
VW3-A66502
LC1-D1810
ATV -66U41N4
VW3-A66501
2,5 mm2
10A
LC1-D1810
VW3-A16702
9
4606 N
ATV -66U41N4
VW3-A66502
2
VW3-A16702
9
4606 N
LC1-D2510
ATV -66U41N4
VW3-A66502
2
GV2-L16
14A
GV2-L20
18A
VW3-A16702
9
4606 N
LC1-D2510
ATV -66U54N4
VW3-A66502
2
VW3-A16704
9
4606 N
25A
LC1-D2510
ATV -66U72N4
VW3-A66503
2
50
GV2-L22
50
GV2-L22
VW3-A16704
9
4606 N
25A
LC1-D3210
ATV -66U90N4
VW3-A66503
2
4 mm
VW3-A66701
12
4606 N
11
70
NS80H-MA
50A
LC1-D4011
ATV -66D12N4
VW3-A66503
4 mm2
15
70
VW3-A66701
12
4606 N
NS80H-MA
50A
LC1-D5011
ATV -66D16N4
VW3-A66504
2
VW3-A66702
12
4606 N
12
4606 N
2
10 mm
VW3-A66702
12
2 x 4606 N
16 mm2
VW3-A66702
12
2 x 4606 N
2
16 mm
VW3-A66703
24
3 x 4606 N
16 mm2
VW3-A66703
24
3 x 4606 N
2
16 mm
VW3-A66703
24
3 x 4606 N
16 mm2
VW3-A66703
24
3 x 4606 N
2
VW3-A66703
24
4 x 4606 N
2
VW3-A66703
24
4 x 4606 N
2
VW3-A66704
36 ***
4 x 4606 N
2
VW3-A66704
36 ***
4 x 4606 N
2
VW3-A66704
36 ***
4 x 4606 N
2
VW3-A66704
36 ***
4 x 4606 N
2
VW3-A66704
36 ***
4 x 4606 N
2
VW3-A66704
36 ***
4 x 4606 N
Circuit
breaker
15
25
GK3-EF65
65A
LC1-D5011
ATV -18D23N4
18.5
25
GK3-EF65
65A
LC1-D6511
ATV -66D23N4
18.5
70
NS80H-MA
80A
LC1-D8011
ATV -66D23N4
22
25
GK3-EF80
80A
LC1-D8011
ATV -66D33N4
22
70
NS80H-MA
80A
LC1-D8011
ATV -66D33N4
30
25
GK3-EF80
80A
LC1-D8011
ATV -66D33N4
30
70
NS80H-MA
80A
LC1-D8011
ATV -66D33N4
37
35
NS100H-MA
100A
LC1-D115006
ATV -66D46N4
37
70
NS100H-MA
100A
LC1-D115006
ATV -66D46N4
45
35
NS160H-MA
150A
LC1-D115006
ATV -66D54N4
45
70
NS160H-MA
150A
LC1-D115006
ATV -66D54N4
55
35
NS160H-MA
150A
LC1-D150006
ATV -66D64N4
55
70
NS160H-MA
150A
LC1-D150006
ATV -66D64N4
75
35
NS250H-MA
220A
LC1-F185
ATV -66D79N4
75
70
NS250H-MA
220A
LC1-F185
ATV -66D79N4
Guide Technique V9 / V9 Technical Guide
2,5 mm
2,5 mm
2,5 mm
2,5 mm
6 mm
6 mm2
VW3-A66505
VW3-A66505
VW3-A66505
35 mm
VW3-A66506
35 mm
35 mm
VW3-A66506
35 mm
35 mm
VW3-A66506
35 mm
50 mm
VW3-A66507
50 mm
207
Installation de l’appareillage
Switchgear Installation
Blokset Ms
Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de
puissance doivent être déclassés de 11% pour ATV 66. Dans le cas d’une
température ambiant plus élevée, consulter GIB.
(1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter
le nombre de modules.
(2): Les ventilateurs ont été définis pour chaque unité fonctionnel sans la résistance
de freinage. Pour installer la résistance de freinage, consulter GIB.
*: plus 12 modules seulement pour résistance de freinage
**: plus 12 modules seulement pour résistance de freinage ou utiliser extension
arrière de 700X2200x400
***: plus extension arrière 700X2200x400 pour inductance de ligne et résistance de
freinage
Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653.
Guide Technique V9 / V9 Technical Guide
Note: in case of switchboard installed in an ambient with 35 °C the values of power
must be derated in 11% for ATV 66. In case of higher ambient temperature, consult
BIM.
(1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the
number of modules.
(2): The fans were defined for functional units without breaking resistance. If breaking
resistance is needed consult BIM.
*: add12 modules only for breaking resistance
**: add 12 modules only for breaking resistance or add rear column 700X2200x400
***: add rear column 700X2200x400 for line coil and breaking resistance
Single line diagrams, according Telemecanique catalogue ART. 16653.
208
Installation de l’appareillage
Switchgear Installation
Blokset Ms
3.5.1.7.
ATV66
220/240 V
Puissance
(kW)
Power
(kW)
0.75
Icc coord.
(kA)
Icc coord.
(kA)
130
1.5
Couple: Variable faible bruit
Torque: Low noise
ATV66
Disjoncteur
Couple: variable faible bruit
Torque: Low noise
GV2-L20
Calibre
(A)
Rating
(A)
18A
Contacteur
(1)
Contactor
(1)
LC1-D1810
ATV
Inductance
de ligne
Line coil
Raccord.
section
cable cross
section area
2,5 mm2
Résistance de
freinage
Break.
Resistance
VW3-A66701
Nr. de Modules avec ou
sans résistance
Nb. Mod. with or
without break. resistance
9
Ventilateur
(2)
Fan
(2)
4606 N
ATV -66U41M2
VW3-A66503
130
GV2-L20
18A
LC1-D1810
ATV -66U41M2
VW3-A66503
2,5 mm2
2.2
130
GV2-L20
18A
LC1-D1810
VW3-A66701
9
4606 N
ATV -66U41M2
VW3-A66503
2
VW3-A66701
9
4606 N
LC1-D2510
ATV -66U72M2
VW3-A66504
2
3
130
4
100
GV2-L22
25A
NS80H-MA
25A
LC1-D4011
ATV -66U72M2
VW3-A66504
5.5
7.5
100
NS80H-MA
50A
50
GK3-EF65
65A
LC1-D4011
ATV -66U90M2
VW3-A66504
LC1-D5011
ATV -66D12M2
VW3-A66505
7.5
100
NS80H-MA
50A
11
50
GK3-EF65
65A
LC1-D5011
ATV -66D12M2
VW3-A66505
LC1-D6511
ATV -66D16M2
VW3-A66505
2
11
100
NS80H-MA
15
50
GK3-EF80
80A
LC1-D8011
ATV -66D16M2
80A
LC1-D8011
ATV -66D23M2
15
100
NS80H-MA
80A
LC1-D8011
ATV -66D23M2
18.5
85
NS100H-MA
100A
LC1-D9511
ATV -66D33M2
18.5
85
NS100H-MA
100A
LC1-D115006
22
85
NS100H-MA
100A
LC1-D115006
22
100
NS100H-MA
100A
LC1-D115006
ATV -66D33M2
30
85
NS160H-MA
150A
LC1-D150006
ATV -66D46M2
30
100
NS160H-MA
150A
LC1-D150006
ATV -66D46M2
Circuit
breaker
Guide Technique V9 / V9 Technical Guide
ATV
Température ambiant 30 °C
Ambient temperature 30 °C
2,5 mm
VW3A66702
12
4606 N
2
VW3A66702
12
4606 N
2
VW3A66702
12
4606 N
2
VW3-A66703
12
2 x 4606 N
VW3-A66703
12
2 x 4606 N
10 mm
VW3-A66704
12 *
2 x 4606 N
VW3-A66505
16 mm2
VW3-A66704
12 *
2 x 4606 N
VW3-A66506
2
16 mm
VW3-A66704
24 **
3 x 4606 N
VW3-A66506
16 mm2
VW3-A66704
24 **
3 x 4606 N
2
25 mm
VW3-A66704
24 **
3 x 4606 N
ATV -66D33M2
35 mm2
VW3-A66704
24 **
3 x 4606 N
ATV -66D33M2
2
35 mm
VW3-A66704
24 **
3 x 4606 N
35 mm2
VW3-A66704
24 **
4 x 4606 N
2
VW3-A66704
36 ***
4 x 4606 N
2
VW3-A66704
36 ***
4 x 4606 N
VW3-A66506
2,5 mm
4 mm
4 mm
6 mm
2
6 mm
35 mm
VW3-A66507
35 mm
209
Installation de l’appareillage
Switchgear Installation
Blokset Ms
Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de
puissance doivent être déclassés de 11% pour ATV 66. Dans le cas d’une
température ambiant plus élevée, consulter GIB.
(1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter
le nombre de modules.
(2): Les ventilateurs ont été définis pour chaque unité fonctionnel sans la résistance
de freinage. Pour installer la résistance de freinage, consulter GIB.
*: plus 12 modules seulement pour résistance de freinage
**: plus 12 modules seulement pour résistance de freinage ou utiliser extension
arrière de 700X2200x400
***: plus extension arrière 700X2200x400 pour inductance de ligne et résistance de
freinage
Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653.
Guide Technique V9 / V9 Technical Guide
Note: in case of switchboard installed in an ambient with 35 °C the values of power
must be derated in 11% for ATV 66. In case of higher ambient temperature, consult
BIM.
(1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the
number of modules.
(2): The fans were defined for functional units without breaking resistance. If breaking
resistance is needed consult BIM.
*: add12 modules only for breaking resistance
**: add 12 modules only for breaking resistance or add rear column 700X2200x400
***: add rear column 700X2200x400 for line coil and breaking resistance
Single line diagrams, according Telemecanique catalogue ART. 16653.
210
Installation de l’appareillage
Switchgear Installation
Blokset Ms
380/460 V
Puissance
(kW)
Power
(kW)
0.75
Icc coord.
(kA)
Icc coord.
(kA)
130
1.5
ATV66
Disjoncteur
Couple: variable faible bruit
Torque: Low noise
Contacteur
(1)
Contactor
(1)
LC1-D0910
ATV
GV2-L08
Calibre
(A)
Rating
(A)
4A
50
GV2-L10
6,3A
2.2
50
GV2-L14
3
50
4
50
5.5
7.5
Température ambiant 30 °C
Ambient temperature 30 °C
ATV
Inductance
de ligne
Line coil
Raccord.
section
cable cross
section area
2,5 mm2
Résistance de
freinage
Break.
Resistance
VW3-A16702
Nr. de Modules avec ou
sans résistance
Nb. Mod. with or
without break. resistance
9
Ventilateur
(2)
Fan
(2)
4606 N
ATV -66U41N4
VW3-A66502
LC1-D1810
ATV -66U41N4
VW3-A66501
2,5 mm2
10A
LC1-D1810
VW3-A16702
9
4606 N
ATV -66U41N4
VW3-A66502
2
VW3-A16702
9
4606 N
LC1-D2510
ATV -66U54N4
VW3-A66502
2
GV2-L16
14A
GV2-L20
18A
VW3-A16704
9
4606 N
LC1-D2510
ATV -66U72N4
VW3-A66502
2
VW3-A16704
9
4606 N
25A
LC1-D2510
ATV -66U90N4
VW3-A66503
2
50
GV2-L22
50
GV2-L22
25A
LC1-D3210
ATV -66D12N4
VW3-A66503
7.5
15
11
70
GV2-L22
25A
LC1-D3210
ATV -66D16N4
NS80H-MA
50A
LC1-D4011
ATV -66D16M2
15
25
GK3-EF65
15
70
NS80H-MA
65A
LC1-D5011
ATV -66D23N4
50A
LC1-D5011
ATV -66D23N4
18.5
25
GK3-EF65
65A
LC1-D6511
ATV -66D33N4
18.5
70
NS80H-MA
80A
LC1-D8011
ATV -66D33N4
22
25
GK3-EF80
80A
LC1-D8011
ATV -66D33N4
22
70
NS80H-MA
80A
LC1-D8011
ATV -66D33N4
30
25
GK3-EF80
80A
LC1-D8011
ATV -66D46N4
30
70
NS80H-MA
80A
LC1-D8011
ATV -66D46N4
37
35
NS100H-MA
100A
LC1-D115006
ATV -66D54N4
37
70
NS100H-MA
100A
LC1-D115006
ATV -66D54N4
45
35
NS160H-MA
150A
LC1-D115006
ATV -66D64N4
45
70
NS160H-MA
150A
LC1-D115006
ATV -66D64N4
55
35
NS160H-MA
150A
LC1-D150006
ATV -66D79N4
55
70
NS160H-MA
150A
LC1-D150006
ATV -66D79N4
Circuit
breaker
Guide Technique V9 / V9 Technical Guide
2,5 mm
2,5 mm
2,5 mm
VW3-A66701
12
4606 N
2
VW3-A66701
12
4606 N
2
VW3-A66702
12
4606 N
2
4 mm
VW3-A66704
12 *
2 x 4606 N
6 mm2
VW3-A66702
12
4606 N
2
VW3-A66702
12
2 x 4606 N
10 mm2
VW3-A66703
24
3 x 4606 N
2
16 mm
VW3-A66703
24
3 x 4606 N
16 mm2
VW3-A66703
24
3 x 4606 N
2
16 mm
VW3-A66703
24
3 x 4606 N
16 mm2
VW3-A66703
24
3 x 4606 N
2
VW3-A66703
24
3 x 4606 N
2
35 mm
VW3-A66704
36 ***
4 x 4606 N
35 mm2
VW3-A66704
36 ***
4 x 4606 N
2
VW3-A66704
36 ***
4 x 4606 N
2
VW3-A66704
36 ***
4 x 4606 N
2
VW3-A66704
36 ***
4 x 4606 N
2
VW3-A66704
36 ***
4 x 4606 N
2,5 mm
4 mm
4 mm
VW3-A66504
VW3-A66504
VW3-A66505
VW3-A66505
VW3-A66505
VW3-A66506
6 mm
16 mm
35 mm
VW3-A66506
35 mm
35 mm
VW3-A66506
35 mm
211
Installation de l’appareillage
Switchgear Installation
Blokset Ms
Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de
puissance doivent être déclassés de 11% pour ATV 66. Dans le cas d’une
température ambiant plus élevée, consulter GIB.
(1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter
le nombre de modules.
(2): Les ventilateurs ont été définis pour chaque unité fonctionnel sans la résistance
de freinage. Pour installer la résistance de freinage, consulter GIB.
*: plus 12 modules seulement pour résistance de freinage
**: plus 12 modules seulement pour résistance de freinage ou utiliser extension
arrière de 700X2200x400
***: plus extension arrière 700X2200x400 pour inductance de ligne et résistance de
freinage
Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653.
Guide Technique V9 / V9 Technical Guide
Note: in case of switchboard installed in an ambient with 35 °C the values of power
must be derated in 11% for ATV 66. In case of higher ambient temperature, consult
BIM.
(1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the
number of modules.
(2): The fans were defined for functional units without breaking resistance. If breaking
resistance is needed consult BIM.
*: add12 modules only for breaking resistance
**: add 12 modules only for breaking resistance or add rear column 700X2200x400
***: add rear column 700X2200x400 for line coil and breaking resistance
Single line diagrams, according Telemecanique catalogue ART. 16653.
212
Installation de l’appareillage
Switchgear Installation
Blokset Ms
3.5.1.8.
ATS46
Coordination Type 1- - - - - - - - - - - - - - - - - - - Service: Standard
Coordination Type 1- - - - - - - - - - - - - - - - - - - Service: Standard
ATS46
220/240 V
Coordination Type 1
Coordination Type 1
Service: Standard
Service: Standard
Température ambiant 30 °C
Ambient temperature 30 °C
Puissance (kW)
Power (kW)
4
Icc coord. (kA)
Icc coord. (kA)
15
Disjoncteur
Circuit breaker
GV2-L20
Calibre (A)
Rating (A)
-
Contacteur (1)
Contactor (1)
LC1-D1810
ATS
ATS
ATS-46D17N
Taille
Size
1
Inductance de ligne
Line coil
VZ1-L015UM17T
Raccordement section
cable cross
4 mm2
Nombre de modules
Number of modules
9
Ventilateur
Fan
4606 N
4
15
GV2-M20
-
LC1-D1810
ATS-46D17N
1
VZ1-L015UM17T
4 mm2
5,5
15
GV2-L22
-
LC1-D2510
ATS-46D22N
1
VZ1-L030U800T
9
4606 N
6 mm
2
9
4606 N
6 mm
2
5,5
15
GV2-M22
-
LC1-D2510
ATS-46D22N
1
VZ1-L030U800T
7,5
15
GK3-EF40
-
LC1-D3210
ATS-46D32N
1
VZ1-L040U600T
9
4606 N
6 mm
2
12
4606 N
7,5
15
GV3-M63
-
LC1-D3210
ATS-46D32N
1
VZ1-L040U600T
6 mm2
9
15
GK3-EF40
-
LC1-D4011
ATS-46D38N
12
4606 N
1
VZ1-L040U600T
6 mm
2
12
4606 N
ATS-46D38N
1
VZ1-L040U600T
6 mm
2
9
15
GV3-M63
-
LC1-D4011
11
15
GK3-EF65
-
LC1-D5011
12
4606 N
ATS-46D47N
2
VZ1-L070U350T
10 mm
2
12
4606 N
15
15
GK3-EF65
-
LC1-D6511
ATS-46D62N
2
VZ1-L070U350T
16 mm2
12
4606 N
18,5
15
GK3-EF80
-
LC1-D8011
ATS-46D75N
2
VZ1-L150U170T
25 mm
2
12
4606 N
22
15
NS100N MA
100
LC1-D9511
ATS-46D88N
2
VZ1-L150U170T
35 mm2
12
4606 N
30
15
NS160N MA
150
LC1-F115
ATS-46C11N
2
VZ1-L150U170T
50 mm
2
18
4606 N
37
15
NS160N MA
150
LC1-F150
ATS-46C14N
2
VZ1-L150U170T
50 mm2
18
4606 N
45
15
NS250N MA
220
LC1-F185
ATS-46C17N
3
VZ1-L250U100T
95 mm
2
36
2 x 4606 N
55
15
NS250N MA
220
LC1-F225
ATS-46C21N
3
VZ1-L250U100T
95 mm2
36
2 x 4606 N
75
15
NS400N MA
320
LC1-F265
ATS-46C25N
3
VZ1-L250U100T
95 mm
2
36
2 x 4606 N
90
15
NS400N MA
320
LC1-F330
ATS-46C32N
3
VZ1-L325U075T
95 mm
2
36
2 x 4606 N
Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de
puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température
ambiant plus élevée, consulter GIB.
(1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter
le nombre de modules.
Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653.
Guide Technique V9 / V9 Technical Guide
Note: in case of switchboard installed in an ambient with 35 °C the values of power
must be derated in 6% for ATS 46. In case of higher ambient temperature, consult
BIM.
(1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the
number of modules
Single line diagrams, according Telemecanique catalogue ART. 16653.
213
Installation de l’appareillage
Switchgear Installation
Blokset Ms
ATS46
380/400 V
Coordination Type 1
Coordination Type 1
Service: Standard
Service: Standard
Température ambiant 30 °C
Ambient temperature 30 °C
Puissance (kW)
Power (kW)
7,5
Icc coord. (kA)
Icc coord. (kA)
15
Disjoncteur
Circuit breaker
GV2-L20
Calibre (A)
Rating (A)
-
Contacteur (1)
Contactor (1)
LC1-D1810
ATS
ATS
ATS-46D17N
Taille
Size
1
Inductance de ligne
Line coil
VZ1-L015UM17T
Raccordement section
cable cross
4 mm2
Nombre de modules
Number of modules
9
Ventilateur
Fan
4606 N
7,5
15
GV2-M20
-
LC1-D1810
ATS-46D17N
1
VZ1-L015UM17T
4 mm2
11
15
GV2-L22
-
LC1-D2510
ATS-46D22N
1
VZ1-L030U800T
9
4606 N
6 mm
2
9
4606 N
6 mm
2
11
15
GV2-M22
-
LC1-D2510
ATS-46D22N
1
VZ1-L030U800T
15
15
GK3-EF40
-
LC1-D3210
ATS-46D32N
1
VZ1-L040U600T
9
4606 N
6 mm
2
12
4606 N
15
15
GV3-M63
-
LC1-D3210
ATS-46D32N
1
VZ1-L040U600T
6 mm2
18,5
15
GK3-EF40
-
LC1-D4011
ATS-46D38N
12
4606 N
1
VZ1-L040U600T
6 mm
2
12
4606 N
ATS-46D38N
1
VZ1-L040U600T
6 mm
2
18,5
15
GV3-M63
-
LC1-D4011
22
15
GK3-EF65
-
LC1-D5011
12
4606 N
ATS-46D47N
2
VZ1-L070U350T
10 mm
2
12
4606 N
30
15
GK3-EF65
-
LC1-D6511
37
15
GK3-EF80
-
LC1-D8011
ATS-46D62N
2
VZ1-L070U350T
16 mm2
12
4606 N
ATS-46D75N
2
VZ1-L150U170T
25 mm
2
12
4606 N
45
15
NS100N MA
100
55
15
NS160N MA
150
LC1-D9511
ATS-46D88N
2
VZ1-L150U170T
35 mm2
12
4606 N
LC1-F115
ATS-46C11N
2
VZ1-L150U170T
50 mm
2
18
4606 N
75
15
NS160N MA
90
15
NS250N MA
150
LC1-F150
ATS-46C14N
2
VZ1-L150U170T
50 mm2
18
4606 N
220
LC1-F185
ATS-46C17N
3
VZ1-L250U100T
95 mm
2
36
2 x 4606 N
110
15
NS250N MA
220
LC1-F225
ATS-46C21N
3
VZ1-L250U100T
95 mm2
36
2 x 4606 N
15
NS400N MA
320
LC1-F265
ATS-46C25N
3
VZ1-L250U100T
95 mm
2
132
160
36
2 x 4606 N
15
NS400N MA
320
LC1-F330
ATS-46C32N
3
VZ1-L325U075T
95 mm
2
36
2 x 4606 N
Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de
puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température
ambiant plus élevée, consulter GIB.
(1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter
le nombre de modules.
Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653.
Guide Technique V9 / V9 Technical Guide
Note: in case of switchboard installed in an ambient with 35 °C the values of power
must be derated in 6% for ATS 46. In case of higher ambient temperature, consult
BIM.
(1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the
number of modules
Single line diagrams, according Telemecanique catalogue ART. 16653.
214
Installation de l’appareillage
Switchgear Installation
Blokset Ms
ATS46
415 V
Coordination Type 1
Coordination Type 1
Service: Standard
Service: Standard
Température ambiant 30 °C
Ambient temperature 30 °C
Puissance (kW)
Power (kW)
7,5
Icc coord. (kA)
Icc coord. (kA)
15
Disjoncteur
Circuit breaker
GV2-L20
Calibre (A)
Rating (A)
-
Contacteur (1)
Contactor (1)
LC1-D1810
ATS
ATS
ATS-46D17N
Taille
Size
1
Inductance de ligne
Line coil
VZ1-L015UM17T
Raccordement section
cable cross
4 mm2
Nombre de modules
Number of modules
9
Ventilateur
Fan
4606 N
7,5
15
GV2-M20
-
LC1-D1810
ATS-46D17N
1
VZ1-L015UM17T
4 mm2
11
15
GV2-L22
-
LC1-D2510
ATS-46D22N
1
VZ1-L030U800T
9
4606 N
6 mm
2
9
4606 N
6 mm
2
11
15
GV2-M22
-
LC1-D2510
ATS-46D22N
1
VZ1-L030U800T
15
15
GK3-EF40
-
LC1-D3210
ATS-46D32N
1
VZ1-L040U600T
9
4606 N
6 mm
2
12
4606 N
15
15
GV3-M63
-
LC1-D3210
ATS-46D32N
1
VZ1-L040U600T
6 mm2
18,5
15
GK3-EF40
-
LC1-D4011
ATS-46D38N
12
4606 N
1
VZ1-L040U600T
6 mm
2
12
4606 N
ATS-46D38N
1
VZ1-L040U600T
6 mm
2
18,5
15
GV3-M63
-
LC1-D4011
22
15
GK3-EF65
-
LC1-D5011
12
4606 N
ATS-46D47N
2
VZ1-L070U350T
10 mm
2
12
4606 N
30
15
GK3-EF65
-
LC1-D6511
37
15
GK3-EF80
-
LC1-D8011
ATS-46D62N
2
VZ1-L070U350T
16 mm2
12
4606 N
ATS-46D75N
2
VZ1-L150U170T
25 mm
2
12
4606 N
45
15
NS100N MA
100
55
15
NS160N MA
150
LC1-D9511
ATS-46D88N
2
VZ1-L150U170T
35 mm2
12
4606 N
LC1-F115
ATS-46C11N
2
VZ1-L150U170T
50 mm
2
18
4606 N
75
15
NS160N MA
90
15
NS250N MA
150
LC1-F150
ATS-46C14N
2
VZ1-L150U170T
50 mm2
18
4606 N
220
LC1-F185
ATS-46C17N
3
VZ1-L250U100T
95 mm
2
36
2 x 4606 N
110
15
NS250N MA
220
LC1-F225
ATS-46C21N
3
VZ1-L250U100T
95 mm2
36
2 x 4606 N
15
NS400N MA
320
LC1-F265
ATS-46C25N
3
VZ1-L250U100T
95 mm
2
132
160
36
2 x 4606 N
15
NS400N MA
320
LC1-F330
ATS-46C32N
3
VZ1-L325U075T
95 mm
2
36
2 x 4606 N
Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de
puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température
ambiant plus élevée, consulter GIB.
(1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter
le nombre de modules.
Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653.
Guide Technique V9 / V9 Technical Guide
Note: in case of switchboard installed in an ambient with 35 °C the values of power
must be derated in 6% for ATS 46. In case of higher ambient temperature, consult
BIM.
(1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the
number of modules
Single line diagrams, according Telemecanique catalogue ART. 16653.
215
Installation de l’appareillage
Switchgear Installation
Blokset Ms
ATS46
440 V
Coordination Type 1
Coordination Type 1
Service: Standard
Service: Standard
Température ambiant 30 °C
Ambient temperature 30 °C
Puissance (kW)
Power (kW)
7,5
Icc coord. (kA)
Icc coord. (kA)
15
Disjoncteur
Circuit breaker
GV2-L20
Calibre (A)
Rating (A)
-
Contacteur (1)
Contactor (1)
LC1-D1810
ATS
ATS
ATS-46D17N
Taille
Size
1
Inductance de ligne
Line coil
VZ1-L015UM17T
Raccordement section
cable cross
4 mm2
Nombre de modules
Number of modules
9
Ventilateur
Fan
4606 N
7,5
15
GV2-M20
-
LC1-D1810
ATS-46D17N
1
VZ1-L015UM17T
4 mm2
11
15
GV2-L22
-
LC1-D2510
ATS-46D22N
1
VZ1-L030U800T
9
4606 N
6 mm
2
9
4606 N
6 mm
2
11
15
GV2-M22
-
LC1-D2510
ATS-46D22N
1
VZ1-L030U800T
15
15
GK3-EF40
-
LC1-D3210
ATS-46D32N
1
VZ1-L040U600T
9
4606 N
6 mm
2
12
4606 N
15
15
GV3-M63
-
LC1-D3210
ATS-46D32N
1
VZ1-L040U600T
6 mm2
18,5
15
GK3-EF40
-
LC1-D4011
ATS-46D38N
12
4606 N
1
VZ1-L040U600T
6 mm
2
12
4606 N
ATS-46D38N
1
VZ1-L040U600T
6 mm
2
18,5
15
GV3-M63
-
LC1-D4011
22
15
GK3-EF65
-
LC1-D5011
12
4606 N
ATS-46D47N
2
VZ1-L070U350T
10 mm
2
12
4606 N
30
15
GK3-EF65
-
LC1-D6511
37
15
GK3-EF80
-
LC1-D8011
ATS-46D62N
2
VZ1-L070U350T
16 mm2
12
4606 N
ATS-46D75N
2
VZ1-L150U170T
25 mm
2
12
4606 N
45
15
NS100N MA
100
55
15
NS160N MA
150
LC1-D9511
ATS-46D88N
2
VZ1-L150U170T
35 mm2
12
4606 N
LC1-F115
ATS-46C11N
2
VZ1-L150U170T
50 mm
2
18
4606 N
75
15
NS160N MA
90
15
NS250N MA
150
LC1-F150
ATS-46C14N
2
VZ1-L150U170T
50 mm2
18
4606 N
220
LC1-F185
ATS-46C17N
3
VZ1-L250U100T
95 mm
2
36
2 x 4606 N
110
15
NS250N MA
220
LC1-F225
ATS-46C21N
3
VZ1-L250U100T
95 mm2
36
2 x 4606 N
15
NS400N MA
320
LC1-F265
ATS-46C25N
3
VZ1-L250U100T
95 mm
2
132
160
36
2 x 4606 N
15
NS400N MA
320
LC1-F330
ATS-46C32N
3
VZ1-L325U075T
95 mm
2
36
2 x 4606 N
Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de
puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température
ambiant plus élevée, consulter GIB.
(1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter
le nombre de modules.
Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653.
Guide Technique V9 / V9 Technical Guide
Note: in case of switchboard installed in an ambient with 35 °C the values of power
must be derated in 6% for ATS 46. In case of higher ambient temperature, consult
BIM.
(1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the
number of modules
Single line diagrams, according Telemecanique catalogue ART. 16653.
216
Installation de l’appareillage
Switchgear Installation
Blokset Ms
ATS46
500 V
Coordination Type 1
Coordination Type 1
Service: Standard
Service: Standard
Température ambiant 30 °C
Ambient temperature 30 °C
Puissance (kW)
Power (kW)
9
Icc coord. (kA)
Icc coord. (kA)
15
Disjoncteur
Circuit breaker
GV2-L20
Calibre (A)
Rating (A)
-
Contacteur (1)
Contactor (1)
LC1-D1810
ATS
ATS
ATS-46D17N
Taille
Size
1
Inductance de ligne
Line coil
VZ1-L015UM17T
Raccordement section
cable cross
4 mm2
Nombre de modules
Number of modules
9
Ventilateur
Fan
4606 N
9
15
GV2-L20
-
LC1-D1810
ATS-46D17N
1
VZ1-L015UM17T
4 mm2
9
15
GV2-M20
-
LC1-D1810
ATS-46D17N
9
4606 N
1
VZ1-L015UM17T
4 mm
2
9
4606 N
ATS-46D22N
1
VZ1-L030U800T
6 mm
2
11
15
GV2-L22
-
LC1-D2510
11
15
GV2-M22
-
LC1-D2510
9
4606 N
ATS-46D22N
1
VZ1-L030U800T
6 mm
2
9
4606 N
ATS-46D32N
1
VZ1-L040U600T
6 mm
2
18,5
15
GK3-EF40
-
LC1-D3210
18,5
15
GV3-M63
-
LC1-D3210
12
4606 N
ATS-46D32N
1
VZ1-L040U600T
6 mm
2
12
4606 N
LC1-D4011
ATS-46D38N
1
VZ1-L040U600T
6 mm
2
22
15
GK3-EF40
-
22
15
GV3-M63
-
12
4606 N
LC1-D4011
ATS-46D38N
1
VZ1-L040U600T
6 mm
2
12
4606 N
30
15
GK3-EF65
-
37
15
GK3-EF65
-
LC1-D5011
ATS-46D47N
2
VZ1-L070U350T
10 mm2
12
4606 N
LC1-D6511
ATS-46D62N
2
VZ1-L070U350T
16 mm
2
12
4606 N
45
15
GK3-EF80
55
15
NS100N MA
-
LC1-D8011
ATS-46D75N
2
VZ1-L150U170T
25 mm2
12
4606 N
100
LC1-D9511
ATS-46D88N
2
VZ1-L150U170T
35 mm
2
12
4606 N
75
15
90
15
NS160N MA
150
LC1-F115
ATS-46C11N
2
VZ1-L150U170T
50 mm2
18
4606 N
NS160N MA
150
LC1-F150
ATS-46C14N
2
VZ1-L150U170T
50 mm
2
18
4606 N
110
15
NS250N MA
220
LC1-F185
ATS-46C17N
3
VZ1-L250U100T
95 mm2
36*
2 x 4606 N
132
15
NS250N MA
220
LC1-F225
ATS-46C21N
3
VZ1-L250U100T
95 mm
2
36*
2 x 4606 N
160
15
NS400N MA
320
LC1-F265
ATS-46C25N
3
VZ1-L250U100T
95 mm
2
36*
2 x 4606 N
220
15
NS400N MA
320
LC1-F330
ATS-46C32N
3
VZ1-L325U075T
95 mm
2
36*
2 x 4606 N
Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de
puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température
ambiant plus élevée, consulter GIB.
(1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter
le nombre de modules.
Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653.
Guide Technique V9 / V9 Technical Guide
Note: in case of switchboard installed in an ambient with 35 °C the values of power
must be derated in 6% for ATS 46. In case of higher ambient temperature, consult
BIM.
(1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the
number of modules
Single line diagrams, according Telemecanique catalogue ART. 16653.
217
Installation de l’appareillage
Switchgear Installation
Blokset Ms
3.5.1.9.
ATS46
220/240 V
Puissance
(kW)
Power
(kW)
4
Icc coord.
(kA)
Icc coord.
(kA)
15
4
5,5
Coordination Type 2- - - - - - - - - - - - - - - - - - - Service: Standard
Coordination Type 2- - - - - - - - - - - - - - - - - - - Service: Standard
ATS46
Disjoncteur
Coordination Type 2
Coordination Type 2
GV2-L20
Calibre
(A)
Rating
(A)
-
Contacteur
(1)
Contactor
(1)
LC1-D2510
ATS
Taille
ATS
Size
ATS-46D17N
15
GV2-P21
-
15
GV2-L22
-
LC1-D2510
LC1-D2510
5,5
15
GV2-P22
-
7,5
15
GV7-RS40
-
LC1-D2510
LC1-D3210
7,5
15
NS80H-MA
50
LC1-D3210
9
15
GV7-RS50
-
9
15
11
15
NS80H-MA
NS80H-MA
Circuit
breaker
Service: Standard
Service: Standard
Température ambiant 30 °C
Ambient temperature 30 °C
Calibre
Fusible
Fuse
rating
40
Inductance de
ligne
Line coil
Raccordement
section
cable cross
section area
Nombre de modules
Ventilateur
Number of modules
Fan
1
Fusible
(2)
Fuse
(2)
DF3-EF04001
VZ1-L015UM17T
4 mm2
9
4606 N
ATS-46D17N
1
DF3-EF04001
40
VZ1-L015UM17T
2
9
4606 N
ATS-46D22N
1
DF3-FF10001
100
VZ1-L030U800T
2
9
4606 N
ATS-46D22N
1
DF3-FF10001
100
VZ1-L030U800T
2
9
4606 N
ATS-46D32N
1
DF3-FF10001
100
VZ1-L040U600T
2
6 mm
12
4606 N
ATS-46D32N
1
DF3-FF10001
100
VZ1-L040U600T
6 mm2
12
4606 N
LC1-D5011
ATS-46D38N
1
DF3-FF10001
100
VZ1-L040U600T
2
12
4606 N
50
LC1-D5011
ATS-46D38N
1
DF3-FF10001
100
VZ1-L040U600T
12
4606 N
50
LC1-D5011
ATS-46D47N
2
DF3-NF40002
400
VZ1-L070U350T
2
10 mm
12
4606 N
4 mm
6 mm
6 mm
6 mm
2
6 mm
15
15
NS80H-MA
-
LC1-D6511
ATS-46D62N
2
DF3-NF40002
400
VZ1-L070U350T
16 mm2
12
4606 N
18,5
15
NS80H-MA
-
LC1-D8011
ATS-46D75N
2
DF3-NF40002
400
VZ1-L150U170T
2
25 mm
12
4606 N
22
15
NS100H-MA
100
LC1-F115
ATS-46D88N
2
DF3-NF40002
400
VZ1-L150U170T
35 mm2
18
4606 N
30
15
NS160H-MA
150
LC1-F115
ATS-46C11N
2
DF3-NF40002
400
VZ1-L150U170T
2
50 mm
18
4606 N
37
15
NS160H-MA
150
LC1-F150
ATS-46C14N
2
DF3-NF50002
500
VZ1-L150U170T
50 mm2
18
4606 N
45
15
NS250H-MA
220
LC1-F185
ATS-46C17N
3
DF3-NF50002
500
VZ1-L250U100T
2
95 mm
36
2 x 4606 N
55
15
NS250H-MA
220
LC1-F225
ATS-46C21N
3
DF3-NF50002
500
VZ1-L250U100T
95 mm2
36
2 x 4606 N
75
15
NS400H-MA
320
LC1-F265
ATS-46C25N
3
DF3-QF63002
630
VZ1-L250U100T
2
36
2 x 4606 N
90
15
NS400H-MA
320
LC1-F330
ATS-46C32N
3
DF3-QF80002
800
VZ1-L325U075T
2
36
2 x 4606 N
Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de
puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température
ambiant plus élevée, consulter GIB.
(1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter
le nombre de modules.
(2): obrigatoire ajoute porte-fusible.
Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653.
Guide Technique V9 / V9 Technical Guide
95 mm
95 mm
Note: in case of switchboard installed in a ambient with 35 °C the values of power
must be derated in 6% for ATS 46. In case of higher ambient temperature, consult
BIM.
(1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the
number of modules.
(2): compulsory add fuse carrier.
Single line diagrams, according Telemecanique catalogue ART. 16653.
218
Installation de l’appareillage
Switchgear Installation
Blokset Ms
380/400 V
Puissance
(kW)
Power
(kW)
7,5
Icc coord.
(kA)
Icc coord.
(kA)
15
7,5
ATS46
Disjoncteur
Coordination Type 2
Coordination Type 2
GV2-L20
Calibre
(A)
Rating
(A)
-
Contacteur
(1)
Contactor
(1)
LC1-D2510
15
GV2-P21
-
11
15
GV2-L22
11
15
GV2-P22
15
15
15
15
18,5
18,5
Service: Standard
Service: Standard
ATS
Taille
ATS
Size
ATS-46D17N
LC1-D2510
-
GV7-RS40
NS80H-MA
15
GV7-RS50
15
NS80H-MA
22
15
NS80H-MA
30
15
NS80H-MA
37
15
NS80H-MA
45
15
NS100H-MA
55
15
NS160H-MA
150
LC1-F115
ATS-46C11N
2
DF3-NF40002
75
15
NS160H-MA
150
LC1-F150
ATS-46C14N
2
DF3-NF50002
90
15
NS250H-MA
220
LC1-F185
ATS-46C17N
3
DF3-NF50002
110
15
NS250H-MA
220
LC1-F225
ATS-46C21N
3
132
15
NS400H-MA
320
LC1-F265
ATS-46C25N
3
160
15
NS400H-MA
320
LC1-F330
ATS-46C32N
3
Circuit
breaker
Calibre
Fusible
Fuse
rating
40
Inductance de
ligne
Line coil
Raccordement
section
cable cross
section area
Nombre de modules
Ventilateur
Number of modules
Fan
1
Fusible
(2)
Fuse
(2)
DF3-EF04001
VZ1-L015UM17T
4 mm2
9
4606 N
ATS-46D17N
1
DF3-EF04001
40
VZ1-L015UM17T
2
9
4606 N
LC1-D2510
ATS-46D22N
1
DF3-FF10001
100
VZ1-L030U800T
2
9
4606 N
LC1-D2510
ATS-46D22N
1
DF3-FF10001
100
VZ1-L030U800T
2
9
4606 N
-
LC1-D3210
ATS-46D32N
1
DF3-FF10001
100
VZ1-L040U600T
2
12
4606 N
50
LC1-D3210
ATS-46D32N
1
DF3-FF10001
100
VZ1-L040U600T
2
12
4606 N
-
LC1-D5011
ATS-46D38N
1
DF3-FF10001
100
VZ1-L040U600T
2
12
4606 N
50
LC1-D5011
ATS-46D38N
1
DF3-FF10001
100
VZ1-L040U600T
2
6 mm
12
4606 N
50
LC1-D5011
ATS-46D47N
2
DF3-NF40002
400
VZ1-L070U350T
10 mm2
12
4606 N
-
LC1-D6511
ATS-46D62N
2
DF3-NF40002
400
VZ1-L070U350T
2
16 mm
12
4606 N
-
LC1-D8011
ATS-46D75N
2
DF3-NF40002
400
VZ1-L150U170T
25 mm2
12
4606 N
100
LC1-F115
ATS-46D88N
2
DF3-NF40002
400
VZ1-L150U170T
2
35 mm
18
4606 N
400
VZ1-L150U170T
50 mm2
18
4606 N
500
VZ1-L150U170T
2
50 mm
18
4606 N
500
VZ1-L250U100T
95 mm2
36
2 x 4606 N
DF3-NF50002
500
VZ1-L250U100T
2
36
2 x 4606 N
DF3-QF63002
630
VZ1-L250U100T
2
36
2 x 4606 N
DF3-QF80002
800
VZ1-L325U075T
2
36
2 x 4606 N
Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de
puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température
ambiant plus élevée, consulter GIB.
(1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter
le nombre de modules.
(2): obrigatoire ajoute porte-fusible.
Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653.
Guide Technique V9 / V9 Technical Guide
Température ambiant 30 °C
Ambient temperature 30 °C
4 mm
6 mm
6 mm
6 mm
6 mm
6 mm
95 mm
95 mm
95 mm
Note: in case of switchboard installed in a ambient with 35 °C the values of power
must be derated in 6% for ATS 46. In case of higher ambient temperature, consult
BIM.
(1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the
number of modules.
(2): compulsory add fuse carrier.
Single line diagrams, according Telemecanique catalogue ART. 16653.
219
Installation de l’appareillage
Switchgear Installation
Blokset Ms
ATS46
415 V
Puissance
(kW)
Power
(kW)
7,5
Icc coord.
(kA)
Icc coord.
(kA)
15
7,5
11
11
15
Disjoncteur
Coordination Type 2
Coordination Type 2
GV2-L20
Calibre
(A)
Rating
(A)
-
Contacteur
(1)
Contactor
(1)
LC1-D2510
ATS
Taille
ATS
Size
ATS-46D17N
15
GV2-P21
-
15
GV2-L22
-
LC1-D2510
LC1-D2510
15
GV2-P22
15
GV7-RS40
-
15
15
NS80H-MA
50
18,5
15
GV7-RS50
18,5
22
15
15
30
37
Service: Standard
Service: Standard
Température ambiant 30 °C
Ambient temperature 30 °C
Calibre
Fusible
Fuse
rating
40
Inductance de
ligne
Line coil
Raccordement
section
cable cross
section area
Nombre de modules
Ventilateur
Number of modules
Fan
1
Fusible
(2)
Fuse
(2)
DF3-EF04001
VZ1-L015UM17T
4 mm2
9
4606 N
ATS-46D17N
1
DF3-EF04001
40
VZ1-L015UM17T
2
9
4606 N
ATS-46D22N
1
DF3-FF10001
100
VZ1-L030U800T
2
9
4606 N
LC1-D2510
ATS-46D22N
1
DF3-FF10001
100
VZ1-L030U800T
2
9
4606 N
LC1-D3210
ATS-46D32N
1
DF3-FF10001
100
VZ1-L040U600T
2
6 mm
12
4606 N
LC1-D3210
ATS-46D32N
1
DF3-FF10001
100
VZ1-L040U600T
6 mm2
12
4606 N
-
LC1-D5011
ATS-46D38N
1
DF3-FF10001
100
VZ1-L040U600T
2
12
4606 N
NS80H-MA
50
LC1-D5011
ATS-46D38N
1
DF3-FF10001
100
VZ1-L040U600T
12
4606 N
NS80H-MA
50
LC1-D5011
ATS-46D47N
2
DF3-NF40002
400
VZ1-L070U350T
2
10 mm
12
4606 N
15
NS80H-MA
-
LC1-D6511
ATS-46D62N
2
DF3-NF40002
400
VZ1-L070U350T
16 mm2
12
4606 N
15
NS80H-MA
-
LC1-D8011
ATS-46D75N
2
DF3-NF40002
400
VZ1-L150U170T
2
25 mm
12
4606 N
45
15
NS100H-MA
100
LC1-F115
ATS-46D88N
2
DF3-NF40002
400
VZ1-L150U170T
35 mm2
18
4606 N
55
15
NS160H-MA
150
LC1-F115
ATS-46C11N
2
DF3-NF40002
400
VZ1-L150U170T
2
50 mm
18
4606 N
75
15
NS160H-MA
150
LC1-F150
ATS-46C14N
2
DF3-NF50002
500
VZ1-L150U170T
50 mm2
18
4606 N
90
15
NS250H-MA
220
LC1-F185
ATS-46C17N
3
DF3-NF50002
500
VZ1-L250U100T
2
95 mm
36
2 x 4606 N
110
15
NS250H-MA
220
LC1-F225
ATS-46C21N
3
DF3-NF50002
500
VZ1-L250U100T
95 mm2
36
2 x 4606 N
132
15
NS400H-MA
320
LC1-F265
ATS-46C25N
3
DF3-QF63002
630
VZ1-L250U100T
2
36
2 x 4606 N
160
15
NS400H-MA
320
LC1-F330
ATS-46C32N
3
DF3-QF80002
800
VZ1-L325U075T
2
36
2 x 4606 N
160
15
NS400H-MA
320
LC1-F330
ATS-46C32N
3
DF3-QF80002
800
VZ1-L325U075T
2
36
2 x 4606 N
Circuit
breaker
Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de
puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température
ambiant plus élevée, consulter GIB.
(1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter
le nombre de modules.
(2): obrigatoire ajoute porte-fusible.
Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653.
Guide Technique V9 / V9 Technical Guide
4 mm
6 mm
6 mm
6 mm
2
6 mm
95 mm
95 mm
95 mm
Note: in case of switchboard installed in a ambient with 35 °C the values of power
must be derated in 6% for ATS 46. In case of higher ambient temperature, consult
BIM.
(1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the
number of modules.
(2): compulsory add fuse carrier.
Single line diagrams, according Telemecanique catalogue ART. 16653.
220
Installation de l’appareillage
Switchgear Installation
Blokset Ms
ATS46
440 V
Puissance
(kW)
Power
(kW)
7,5
Icc coord.
(kA)
Icc coord.
(kA)
15
7,5
11
11
15
Disjoncteur
Coordination Type 2
Coordination Type 2
GV2-L20
Calibre
(A)
Rating
(A)
-
Contacteur
(1)
Contactor
(1)
LC1-D2510
ATS
Taille
ATS
Size
ATS-46D17N
15
GV2-P21
-
15
GV2-L22
-
LC1-D2510
LC1-D2510
15
GV2-P22
15
GV7-RS40
-
15
15
NS80H-MA
50
18,5
15
GV7-RS50
18,5
22
15
15
30
37
Service: Standard
Service: Standard
Température ambiant 30 °C
Ambient temperature 30 °C
Calibre
Fusible
Fuse
rating
40
Inductance de
ligne
Line coil
Raccordement
section
cable cross
section area
Nombre de modules
Ventilateur
Number of modules
Fan
1
Fusible
(2)
Fuse
(2)
DF3-EF04001
VZ1-L015UM17T
4 mm2
9
4606 N
ATS-46D17N
1
DF3-EF04001
40
VZ1-L015UM17T
2
9
4606 N
ATS-46D22N
1
DF3-FF10001
100
VZ1-L030U800T
2
9
4606 N
LC1-D2510
ATS-46D22N
1
DF3-FF10001
100
VZ1-L030U800T
2
9
4606 N
LC1-D3210
ATS-46D32N
1
DF3-FF10001
100
VZ1-L040U600T
2
6 mm
12
4606 N
LC1-D3210
ATS-46D32N
1
DF3-FF10001
100
VZ1-L040U600T
6 mm2
12
4606 N
-
LC1-D5011
ATS-46D38N
1
DF3-FF10001
100
VZ1-L040U600T
2
12
4606 N
NS80H-MA
50
LC1-D5011
ATS-46D38N
1
DF3-FF10001
100
VZ1-L040U600T
12
4606 N
NS80H-MA
50
LC1-D5011
ATS-46D47N
2
DF3-NF40002
400
VZ1-L070U350T
2
10 mm
12
4606 N
15
NS80H-MA
-
LC1-D6511
ATS-46D62N
2
DF3-NF40002
400
VZ1-L070U350T
16 mm2
12
4606 N
15
NS80H-MA
-
LC1-D8011
ATS-46D75N
2
DF3-NF40002
400
VZ1-L150U170T
2
25 mm
12
4606 N
45
15
NS100H-MA
100
LC1-F115
ATS-46D88N
2
DF3-NF40002
400
VZ1-L150U170T
35 mm2
18
4606 N
55
15
NS160H-MA
150
LC1-F115
ATS-46C11N
2
DF3-NF40002
400
VZ1-L150U170T
2
50 mm
18
4606 N
75
15
NS160H-MA
150
LC1-F150
ATS-46C14N
2
DF3-NF50002
500
VZ1-L150U170T
50 mm2
18
4606 N
90
15
NS250H-MA
220
LC1-F185
ATS-46C17N
3
DF3-NF50002
500
VZ1-L250U100T
2
95 mm
36
2 x 4606 N
110
15
NS250H-MA
220
LC1-F225
ATS-46C21N
3
DF3-NF50002
500
VZ1-L250U100T
95 mm2
36
2 x 4606 N
132
15
NS400H-MA
320
LC1-F265
ATS-46C25N
3
DF3-QF63002
630
VZ1-L250U100T
2
36
2 x 4606 N
160
15
NS400H-MA
320
LC1-F330
ATS-46C32N
3
DF3-QF80002
800
VZ1-L325U075T
2
36
2 x 4606 N
Circuit
breaker
Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de
puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température
ambiant plus élevée, consulter GIB.
(1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter
le nombre de modules.
(2): obrigatoire ajoute porte-fusible.
Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653.
Guide Technique V9 / V9 Technical Guide
4 mm
6 mm
6 mm
6 mm
2
6 mm
95 mm
95 mm
Note: in case of switchboard installed in a ambient with 35 °C the values of power
must be derated in 6% for ATS 46. In case of higher ambient temperature, consult
BIM.
(1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the
number of modules.
(2): compulsory add fuse carrier.
Single line diagrams, according Telemecanique catalogue ART. 16653.
221
Installation de l’appareillage
Switchgear Installation
Blokset Ms
480 V Nema
Puissance
(kW)
Power
(kW)
9
Icc coord.
(kA)
Icc coord.
(kA)
15
9
11
11
18,5
18,5
ATS46
Disjoncteur
Coordination Type 2
Coordination Type 2
GV2-L20
Calibre
(A)
Rating
(A)
-
Contacteur
(1)
Contactor
(1)
LC1-D2510
ATS
Taille
ATS
Size
ATS-46D17N
15
GV2-P21
-
15
GV2-L22
-
LC1-D2510
LC1-D2510
15
GV2-P22
15
GV7-RS40
-
15
NS80H-MA
50
22
15
GV7-RS50
22
30
15
15
37
45
Service: Standard
Service: Standard
Température ambiant 30 °C
Ambient temperature 30 °C
Calibre
Fusible
Fuse
rating
40
Inductance de
ligne
Line coil
Raccordement
section
cable cross
section area
Nombre de modules
Ventilateur
Number of modules
Fan
1
Fusible
(2)
Fuse
(2)
DF3-EF04001
VZ1-L015UM17T
4 mm2
9
4606 N
ATS-46D17N
1
DF3-EF04001
40
VZ1-L015UM17T
2
9
4606 N
ATS-46D22N
1
DF3-FF10001
100
VZ1-L030U800T
2
9
4606 N
LC1-D2510
ATS-46D22N
1
DF3-FF10001
100
VZ1-L030U800T
2
9
4606 N
LC1-D3210
ATS-46D32N
1
DF3-FF10001
100
VZ1-L040U600T
2
6 mm
12
4606 N
LC1-D3210
ATS-46D32N
1
DF3-FF10001
100
VZ1-L040U600T
6 mm2
12
4606 N
-
LC1-D5011
ATS-46D38N
1
DF3-FF10001
100
VZ1-L040U600T
2
12
4606 N
NS80H-MA
50
LC1-D5011
ATS-46D38N
1
DF3-FF10001
100
VZ1-L040U600T
12
4606 N
NS80H-MA
50
LC1-D5011
ATS-46D47N
2
DF3-NF40002
400
VZ1-L070U350T
2
10 mm
12
4606 N
15
NS80H-MA
-
LC1-D6511
ATS-46D62N
2
DF3-NF40002
400
VZ1-L070U350T
16 mm2
12
4606 N
15
NS80H-MA
-
LC1-D8011
ATS-46D75N
2
DF3-NF40002
400
VZ1-L150U170T
2
25 mm
12
4606 N
55
15
NS100H-MA
100
LC1-F115
ATS-46D88N
2
DF3-NF40002
400
VZ1-L150U170T
35 mm2
18
4606 N
75
15
NS160H-MA
150
LC1-F115
ATS-46C11N
2
DF3-NF40002
400
VZ1-L150U170T
2
50 mm
18
4606 N
90
15
NS160H-MA
150
LC1-F150
ATS-46C14N
2
DF3-NF50002
500
VZ1-L150U170T
50 mm2
18
4606 N
110
15
NS250H-MA
220
LC1-F185
ATS-46C17N
3
DF3-NF50002
500
VZ1-L250U100T
2
95 mm
36
2 x 4606 N
132
15
NS250H-MA
220
LC1-F225
ATS-46C21N
3
DF3-NF50002
500
VZ1-L250U100T
95 mm2
36
2 x 4606 N
160
15
NS400H-MA
320
LC1-F265
ATS-46C25N
3
DF3-QF63002
630
VZ1-L250U100T
2
36
2 x 4606 N
220
15
NS400H-MA
320
LC1-F330
ATS-46C32N
3
DF3-QF80002
800
VZ1-L325U075T
2
36
2 x 4606 N
Circuit
breaker
Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de
puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température
ambiant plus élevée, consulter GIB.
(1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter
le nombre de modules.
(2): obrigatoire ajoute porte-fusible.
Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653.
Guide Technique V9 / V9 Technical Guide
4 mm
6 mm
6 mm
6 mm
2
6 mm
95 mm
95 mm
Note: in case of switchboard installed in a ambient with 35 °C the values of power
must be derated in 6% for ATS 46. In case of higher ambient temperature, consult
BIM.
(1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the
number of modules.
(2): compulsory add fuse carrier.
Single line diagrams, according Telemecanique catalogue ART. 16653.
222
Installation de l’appareillage
Switchgear Installation
Blokset Ms
3.5.1.10. ATS46
Coordination Type 1- - - - - - - - - - - - - - - - - - - Service: Sévère
Coordination Type 1- - - - - - - - - - - - - - - - - - - Service: Severe
ATS46
220/240 V
Coordination Type 1
Coordination Type 1
Service: Sévère
Service: Severe
Température ambiant 30 °C
Ambient temperature 30 °C
Puissance (kW)
Power (kW)
3
Icc coord. (kA)
Icc coord. (kA)
15
Disjoncteur
Circuit breaker
GV2-L20
Calibre (A)
Rating (A)
-
Contacteur (1)
Contactor (1)
LC1-D1810
ATS
ATS
ATS-46D17N
Taille
Size
1
Inductance de ligne
Line coil
VZ1-L015UM17T
Raccordement section
cable cross
4 mm2
Nombre de modules
Number of modules
9
Ventilateur
Fan
4606 N
3
15
GV2-M20
-
LC1-D1810
ATS-46D17N
1
VZ1-L015UM17T
4 mm2
4
15
GV2-L22
-
LC1-D2510
ATS-46D22N
1
VZ1-L030U800T
9
4606 N
6 mm
2
9
4606 N
6 mm
2
4
15
GV2-M22
-
LC1-D2510
ATS-46D22N
1
VZ1-L030U800T
5,5
15
GK3-EF40
-
LC1-D3210
ATS-46D32N
1
VZ1-L040U600T
9
4606 N
6 mm
2
12
4606 N
5,5
15
GV3-M63
-
LC1-D3210
ATS-46D32N
1
VZ1-L040U600T
6 mm2
7,5
15
GK3-EF40
-
LC1-D4011
ATS-46D38N
12
4606 N
1
VZ1-L040U600T
6 mm
2
12
4606 N
ATS-46D38N
1
VZ1-L040U600T
6 mm
2
7,5
15
GV3-M63
-
LC1-D4011
9
15
GK3-EF65
-
LC1-D5011
12
4606 N
ATS-46D47N
2
VZ1-L070U350T
10 mm
2
12
4606 N
11
15
GK3-EF65
-
15
15
GK3-EF80
-
LC1-D6511
ATS-46D62N
2
VZ1-L070U350T
16 mm2
12
4606 N
LC1-D8011
ATS-46D75N
2
VZ1-L150U170T
25 mm
2
12
4606 N
18,5
15
NS100N MA
22
15
NS160N MA
100
LC1-D9511
ATS-46D88N
2
VZ1-L150U170T
35 mm2
12
4606 N
150
LC1-F115
ATS-46C11N
2
VZ1-L150U170T
50 mm
2
18
4606 N
30
15
37
15
NS160N MA
150
LC1-F150
ATS-46C14N
2
VZ1-L150U170T
50 mm2
18
4606 N
NS250N MA
220
LC1-F185
ATS-46C17N
3
VZ1-L250U100T
95 mm
2
36
2 x 4606 N
45
15
NS250N MA
220
LC1-F225
ATS-46C21N
3
VZ1-L250U100T
95 mm2
36
2 x 4606 N
55
15
NS400N MA
320
LC1-F265
ATS-46C25N
3
VZ1-L250U100T
95 mm
2
36
2 x 4606 N
75
15
NS400N MA
320
LC1-F330
ATS-46C32N
3
VZ1-L325U075T
95 mm
2
36
2 x 4606 N
Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de
puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température
ambiant plus élevée, consulter GIB.
(1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter
le nombre de modules.
Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653.
Guide Technique V9 / V9 Technical Guide
Note: in case of switchboard installed in a ambient with 35 °C the values of power
must be derated in 6% for ATS 46. In case of higher ambient temperature, consult
BIM.
(1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the
number of modules
Single line diagrams, according Telemecanique catalogue ART. 16653.
223
Installation de l’appareillage
Switchgear Installation
Blokset Ms
ATS46
380/400 V
Coordination Type 1
Coordination Type 1
Service: Sévère
Service: Severe
Température ambiant 30 °C
Ambient temperature 30 °C
Puissance (kW)
Power (kW)
5,5
Icc coord. (kA)
Icc coord. (kA)
15
Disjoncteur
Circuit breaker
GV2-L20
Calibre (A)
Rating (A)
-
Contacteur (1)
Contactor (1)
LC1-D1810
ATS
ATS
ATS-46D17N
Taille
Size
1
Inductance de ligne
Line coil
VZ1-L015UM17T
Raccordement section
cable cross
4 mm2
Nombre de modules
Number of modules
9
Ventilateur
Fan
4606 N
5,5
15
GV2-M20
-
LC1-D1810
ATS-46D17N
1
VZ1-L015UM17T
4 mm2
7,5
15
GV2-L22
-
LC1-D2510
ATS-46D22N
1
VZ1-L030U800T
9
4606 N
6 mm
2
9
4606 N
6 mm
2
7,5
15
GV2-M22
-
LC1-D2510
ATS-46D22N
1
VZ1-L030U800T
11
15
GK3-EF40
-
LC1-D3210
ATS-46D32N
1
VZ1-L040U600T
9
4606 N
6 mm
2
12
4606 N
11
15
GV3-M63
-
LC1-D3210
ATS-46D32N
1
VZ1-L040U600T
6 mm2
15
15
GK3-EF40
-
LC1-D4011
ATS-46D38N
12
4606 N
1
VZ1-L040U600T
6 mm
2
12
4606 N
ATS-46D38N
1
VZ1-L040U600T
6 mm
2
15
15
GV3-M63
-
LC1-D4011
18,5
15
GK3-EF65
-
LC1-D5011
12
4606 N
ATS-46D47N
2
VZ1-L070U350T
10 mm
2
12
4606 N
22
15
GK3-EF65
-
30
15
GK3-EF80
-
LC1-D6511
ATS-46D62N
2
VZ1-L070U350T
16 mm2
12
4606 N
LC1-D8011
ATS-46D75N
2
VZ1-L150U170T
25 mm
2
12
4606 N
37
15
NS100N MA
45
15
NS160N MA
100
LC1-D9511
ATS-46D88N
2
VZ1-L150U170T
35 mm2
12
4606 N
150
LC1-F115
ATS-46C11N
2
VZ1-L150U170T
50 mm
2
18
4606 N
55
15
75
15
NS160N MA
150
LC1-F150
ATS-46C14N
2
VZ1-L150U170T
50 mm2
18
4606 N
NS250N MA
220
LC1-F185
ATS-46C17N
3
VZ1-L250U100T
95 mm
2
36
2 x 4606 N
90
15
NS250N MA
220
LC1-F225
ATS-46C21N
3
VZ1-L250U100T
95 mm2
36
2 x 4606 N
110
15
NS400N MA
320
LC1-F265
ATS-46C25N
3
VZ1-L250U100T
95 mm
2
36
2 x 4606 N
132
15
NS400N MA
320
LC1-F330
ATS-46C32N
3
VZ1-L325U075T
95 mm
2
36
2 x 4606 N
Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de
puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température
ambiant plus élevée, consulter GIB.
(1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter
le nombre de modules.
Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653.
Guide Technique V9 / V9 Technical Guide
Note: in case of switchboard installed in a ambient with 35 °C the values of power
must be derated in 6% for ATS 46. In case of higher ambient temperature, consult
BIM.
(1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the
number of modules
Single line diagrams, according Telemecanique catalogue ART. 16653.
224
Installation de l’appareillage
Switchgear Installation
Blokset Ms
ATS46
415 V
Coordination Type 1
Coordination Type 1
Service: Sévère
Service: Severe
Température ambiant 30 °C
Ambient temperature 30 °C
Puissance (kW)
Power (kW)
5,5
Icc coord. (kA)
Icc coord. (kA)
15
Disjoncteur
Circuit breaker
GV2-L20
Calibre (A)
Rating (A)
-
Contacteur (1)
Contactor (1)
LC1-D1810
ATS
ATS
ATS-46D17N
Taille
Size
1
Inductance de ligne
Line coil
VZ1-L015UM17T
Raccordement section
cable cross
4 mm2
Nombre de modules
Number of modules
9
Ventilateur
Fan
4606 N
5,5
15
GV2-M20
-
LC1-D1810
ATS-46D17N
1
VZ1-L015UM17T
4 mm2
7,5
15
GV2-L22
-
LC1-D2510
ATS-46D22N
1
VZ1-L030U800T
9
4606 N
6 mm
2
9
4606 N
6 mm
2
7,5
15
GV2-M22
-
LC1-D2510
ATS-46D22N
1
VZ1-L030U800T
11
15
GK3-EF40
-
LC1-D3210
ATS-46D32N
1
VZ1-L040U600T
9
4606 N
6 mm
2
12
4606 N
11
15
GV3-M63
-
LC1-D3210
ATS-46D32N
1
VZ1-L040U600T
6 mm2
15
15
GK3-EF40
-
LC1-D4011
ATS-46D38N
12
4606 N
1
VZ1-L040U600T
6 mm
2
12
4606 N
ATS-46D38N
1
VZ1-L040U600T
6 mm
2
15
15
GV3-M63
-
LC1-D4011
18,5
15
GK3-EF65
-
LC1-D5011
12
4606 N
ATS-46D47N
2
VZ1-L070U350T
10 mm
2
12
4606 N
22
15
GK3-EF65
-
30
15
GK3-EF80
-
LC1-D6511
ATS-46D62N
2
VZ1-L070U350T
16 mm2
12
4606 N
LC1-D8011
ATS-46D75N
2
VZ1-L150U170T
25 mm
2
12
4606 N
37
15
NS100N MA
45
15
NS160N MA
100
LC1-D9511
ATS-46D88N
2
VZ1-L150U170T
35 mm2
12
4606 N
150
LC1-F115
ATS-46C11N
2
VZ1-L150U170T
50 mm
2
18
4606 N
55
15
75
15
NS160N MA
150
LC1-F150
ATS-46C14N
2
VZ1-L150U170T
50 mm2
18
4606 N
NS250N MA
220
LC1-F185
ATS-46C17N
3
VZ1-L250U100T
95 mm
2
36
2 x 4606 N
90
15
NS250N MA
220
LC1-F225
ATS-46C21N
3
VZ1-L250U100T
95 mm2
36
2 x 4606 N
110
15
NS400N MA
320
LC1-F265
ATS-46C25N
3
VZ1-L250U100T
95 mm
2
36
2 x 4606 N
132
15
NS400N MA
320
LC1-F330
ATS-46C32N
3
VZ1-L325U075T
95 mm
2
36
2 x 4606 N
Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de
puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température
ambiant plus élevée, consulter GIB.
(1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter
le nombre de modules.
Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653.
Guide Technique V9 / V9 Technical Guide
Note: in case of switchboard installed in a ambient with 35 °C the values of power
must be derated in 6% for ATS 46. In case of higher ambient temperature, consult
BIM.
(1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the
number of modules
Single line diagrams, according Telemecanique catalogue ART. 16653.
225
Installation de l’appareillage
Switchgear Installation
Blokset Ms
ATS46
440 V
Coordination Type 1
Coordination Type 1
Service: Sévère
Service: Severe
Température ambiant 30 °C
Ambient temperature 30 °C
Puissance (kW)
Power (kW)
5,5
Icc coord. (kA)
Icc coord. (kA)
15
Disjoncteur
Circuit breaker
GV2-L20
Calibre (A)
Rating (A)
-
Contacteur (1)
Contactor (1)
LC1-D1810
ATS
ATS
ATS-46D17N
Taille
Size
1
Inductance de ligne
Line coil
VZ1-L015UM17T
Raccordement section
cable cross
4 mm2
Nombre de modules
Number of modules
9
Ventilateur
Fan
4606 N
5,5
15
GV2-M20
-
LC1-D1810
ATS-46D17N
1
VZ1-L015UM17T
4 mm2
7,5
15
GV2-L22
-
LC1-D2510
ATS-46D22N
1
VZ1-L030U800T
9
4606 N
6 mm
2
9
4606 N
6 mm
2
7,5
15
GV2-M22
-
LC1-D2510
ATS-46D22N
1
VZ1-L030U800T
11
15
GK3-EF40
-
LC1-D3210
ATS-46D32N
1
VZ1-L040U600T
9
4606 N
6 mm
2
12
4606 N
11
15
GV3-M63
-
LC1-D3210
ATS-46D32N
1
VZ1-L040U600T
6 mm2
15
15
GK3-EF40
-
LC1-D4011
ATS-46D38N
12
4606 N
1
VZ1-L040U600T
6 mm
2
12
4606 N
ATS-46D38N
1
VZ1-L040U600T
6 mm
2
15
15
GV3-M63
-
LC1-D4011
18,5
15
GK3-EF65
-
LC1-D5011
12
4606 N
ATS-46D47N
2
VZ1-L070U350T
10 mm
2
12
4606 N
22
15
GK3-EF65
-
30
15
GK3-EF80
-
LC1-D6511
ATS-46D62N
2
VZ1-L070U350T
16 mm2
12
4606 N
LC1-D8011
ATS-46D75N
2
VZ1-L150U170T
25 mm
2
12
4606 N
37
15
NS100N MA
45
15
NS160N MA
100
LC1-D9511
ATS-46D88N
2
VZ1-L150U170T
35 mm2
12
4606 N
150
LC1-F115
ATS-46C11N
2
VZ1-L150U170T
50 mm
2
18
4606 N
55
15
75
15
NS160N MA
150
LC1-F150
ATS-46C14N
2
VZ1-L150U170T
50 mm2
18
4606 N
NS250N MA
220
LC1-F185
ATS-46C17N
3
VZ1-L250U100T
95 mm
2
36
2 x 4606 N
90
15
NS250N MA
220
LC1-F225
ATS-46C21N
3
VZ1-L250U100T
95 mm2
36
2 x 4606 N
110
15
NS400N MA
320
LC1-F265
ATS-46C25N
3
VZ1-L250U100T
95 mm
2
36
2 x 4606 N
132
15
NS400N MA
320
LC1-F330
ATS-46C32N
3
VZ1-L325U075T
95 mm
2
36
2 x 4606 N
Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de
puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température
ambiant plus élevée, consulter GIB.
(1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter
le nombre de modules.
Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653.
Guide Technique V9 / V9 Technical Guide
Note: in case of switchboard installed in a ambient with 35 °C the values of power
must be derated in 6% for ATS 46. In case of higher ambient temperature, consult
BIM.
(1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the
number of modules
Single line diagrams, according Telemecanique catalogue ART. 16653.
226
Installation de l’appareillage
Switchgear Installation
Blokset Ms
ATS46
500 V
Coordination Type 1
Coordination Type 1
Service: Sévère
Service: Severe
Température ambiant 30 °C
Ambient temperature 30 °C
Puissance (kW)
Power (kW)
7,5
Icc coord. (kA)
Icc coord. (kA)
15
Disjoncteur
Circuit breaker
GV2-L20
Calibre (A)
Rating (A)
-
Contacteur (1)
Contactor (1)
LC1-D1810
ATS
ATS
ATS-46D17N
Taille
Size
1
Inductance de ligne
Line coil
VZ1-L015UM17T
Raccordement section
cable cross
4 mm2
Nombre de modules
Number of modules
9
Ventilateur
Fan
4606 N
7,5
15
GV2-M20
-
LC1-D1810
ATS-46D17N
1
VZ1-L015UM17T
4 mm2
9
15
GV2-L22
-
LC1-D2510
ATS-46D22N
1
VZ1-L030U800T
9
4606 N
6 mm
2
9
4606 N
6 mm
2
9
15
GV2-M22
-
LC1-D2510
ATS-46D22N
1
VZ1-L030U800T
11
15
GK3-EF40
-
LC1-D3210
ATS-46D32N
1
VZ1-L040U600T
9
4606 N
6 mm
2
12
4606 N
11
15
GV3-M63
-
LC1-D3210
ATS-46D32N
1
VZ1-L040U600T
6 mm2
18,5
15
GK3-EF40
-
LC1-D4011
ATS-46D38N
12
4606 N
1
VZ1-L040U600T
6 mm
2
12
4606 N
ATS-46D38N
1
VZ1-L040U600T
6 mm
2
18,5
15
GV3-M63
-
LC1-D4011
22
15
GK3-EF65
-
LC1-D5011
12
4606 N
ATS-46D47N
2
VZ1-L070U350T
10 mm
2
12
4606 N
30
15
GK3-EF65
-
LC1-D6511
37
15
GK3-EF80
-
LC1-D8011
ATS-46D62N
2
VZ1-L070U350T
16 mm2
12
4606 N
ATS-46D75N
2
VZ1-L150U170T
25 mm
2
12
4606 N
45
15
NS100N MA
100
55
15
NS160N MA
150
LC1-D9511
ATS-46D88N
2
VZ1-L150U170T
35 mm2
12
4606 N
LC1-F115
ATS-46C11N
2
VZ1-L150U170T
50 mm
2
18
4606 N
75
15
NS160N MA
90
15
NS250N MA
150
LC1-F150
ATS-46C14N
2
VZ1-L150U170T
50 mm2
18
4606 N
220
LC1-F185
ATS-46C17N
3
VZ1-L250U100T
95 mm
2
36
2 x 4606 N
110
15
NS250N MA
220
LC1-F225
ATS-46C21N
3
VZ1-L250U100T
95 mm2
36
2 x 4606 N
15
NS400N MA
320
LC1-F265
ATS-46C25N
3
VZ1-L250U100T
95 mm
2
132
160
36
2 x 4606 N
15
NS400N MA
320
LC1-F330
ATS-46C32N
3
VZ1-L325U075T
95 mm
2
36
2 x 4606 N
Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de
puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température
ambiant plus élevée, consulter GIB.
(1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter
le nombre de modules.
Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653.
Guide Technique V9 / V9 Technical Guide
Note: in case of switchboard installed in a ambient with 35 °C the values of power
must be derated in 6% for ATS 46. In case of higher ambient temperature, consult
BIM.
(1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the
number of modules
Single line diagrams, according Telemecanique catalogue ART. 16653.
227
Installation de l’appareillage
Switchgear Installation
Blokset Ms
3.5.1.11. ATS46
220/240 V
Puissance
(kW)
Power
(kW)
3
Icc coord.
(kA)
Icc coord.
(kA)
15
3
4
Coordination Type 2- - - - - - - - - - - - - - - - - - - Service: Sévère
Coordination Type 2- - - - - - - - - - - - - - - - - - - Service: Severe
ATS46
Disjoncteur
Coordination Type 2
Coordination Type 2
GV2-L20
Calibre
(A)
Rating
(A)
-
Contacteur
(1)
Contactor
(1)
LC1-D2510
ATS
Taille
ATS
Size
ATS-46D17N
15
GV2-P21
-
15
GV2-L22
-
LC1-D2510
LC1-D2510
4
15
GV2-P22
-
5,5
15
GV7-RS40
-
LC1-D2510
LC1-D3210
5,5
15
NS80H-MA
50
LC1-D3210
7,5
15
GV7-RS50
-
7,5
15
9
15
NS80H-MA
NS80H-MA
11
15
15
15
NS80H-MA
NS80H-MA
18,5
22
15
15
30
37
Service: Sévère
Service: Severe
Température ambiant 30 °C
Ambient temperature 30 °C
Calibre
Fusible
Fuse
rating
40
Inductance de
ligne
Line coil
Raccordement
section
cable cross
section area
Nombre de modules
Ventilateur
Number of modules
Fan
1
Fusible
(2)
Fuse
(2)
DF3-EF04001
VZ1-L015UM17T
4 mm2
9
4606 N
ATS-46D17N
1
DF3-EF04001
40
VZ1-L015UM17T
2
9
4606 N
ATS-46D22N
1
DF3-FF10001
100
VZ1-L030U800T
2
9
4606 N
ATS-46D22N
1
DF3-FF10001
100
VZ1-L030U800T
2
9
4606 N
ATS-46D32N
1
DF3-FF10001
100
VZ1-L040U600T
2
6 mm
12
4606 N
ATS-46D32N
1
DF3-FF10001
100
VZ1-L040U600T
6 mm2
12
4606 N
LC1-D5011
ATS-46D38N
1
DF3-FF10001
100
VZ1-L040U600T
2
12
4606 N
50
LC1-D5011
ATS-46D38N
1
DF3-FF10001
100
VZ1-L040U600T
12
4606 N
50
LC1-D5011
ATS-46D47N
2
DF3-NF40002
400
VZ1-L070U350T
2
10 mm
12
4606 N
-
LC1-D6511
ATS-46D62N
2
DF3-NF40002
400
VZ1-L070U350T
16 mm2
12
4606 N
-
LC1-D8011
ATS-46D75N
2
DF3-NF40002
400
VZ1-L150U170T
2
25 mm
12
4606 N
NS100H-MA
100
LC1-F115
ATS-46D88N
2
DF3-NF40002
400
VZ1-L150U170T
35 mm2
18
4606 N
NS160H-MA
150
LC1-F115
ATS-46C11N
2
DF3-NF40002
400
VZ1-L150U170T
2
50 mm
18
4606 N
15
NS160H-MA
150
LC1-F150
ATS-46C14N
2
DF3-NF50002
500
VZ1-L150U170T
50 mm2
18
4606 N
15
NS250H-MA
220
LC1-F185
ATS-46C17N
3
DF3-NF50002
500
VZ1-L250U100T
2
95 mm
36
2 x 4606 N
45
15
NS250H-MA
220
LC1-F225
ATS-46C21N
3
DF3-NF50002
500
VZ1-L250U100T
95 mm2
36
2 x 4606 N
55
15
NS400H-MA
320
LC1-F265
ATS-46C25N
3
DF3-QF63002
630
VZ1-L250U100T
2
36
2 x 4606 N
75
15
NS400H-MA
320
LC1-F330
ATS-46C32N
3
DF3-QF80002
800
VZ1-L325U075T
2
36
2 x 4606 N
Circuit
breaker
Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de
puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température
ambiant plus élevée, consulter GIB.
(1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter
le nombre de modules.
(2): obrigatoire ajoute porte-fusible.
Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653.
Guide Technique V9 / V9 Technical Guide
4 mm
6 mm
6 mm
6 mm
2
6 mm
95 mm
95 mm
Note: in case of switchboard installed in a ambient with 35 °C the values of power
must be derated in 6% for ATS 46. In case of higher ambient temperature, consult
BIM.
(1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the
number of modules.
(2): compulsory add fuse carrier.
Single line diagrams, according Telemecanique catalogue ART. 16653.
228
Installation de l’appareillage
Switchgear Installation
Blokset Ms
380/400 V
Puissance
(kW)
Power
(kW)
5,5
Icc coord.
(kA)
Icc coord.
(kA)
15
5,5
ATS46
Disjoncteur
Coordination Type 2
Coordination Type 2
GV2-L20
Calibre
(A)
Rating
(A)
-
Contacteur
(1)
Contactor
(1)
LC1-D2510
15
GV2-P21
-
7,5
15
GV2-L22
7,5
15
GV2-P22
11
15
11
15
15
15
Service: Sévère
Service: Severe
ATS
Taille
ATS
Size
ATS-46D17N
LC1-D2510
-
GV7-RS40
NS80H-MA
15
GV7-RS50
15
NS80H-MA
18,5
15
NS80H-MA
22
15
NS80H-MA
30
15
NS80H-MA
37
15
NS100H-MA
45
15
NS160H-MA
150
LC1-F115
ATS-46C11N
2
DF3-NF40002
55
15
NS160H-MA
150
LC1-F150
ATS-46C14N
2
DF3-NF50002
75
15
NS250H-MA
220
LC1-F185
ATS-46C17N
3
DF3-NF50002
90
15
NS250H-MA
220
LC1-F225
ATS-46C21N
3
110
15
NS400H-MA
320
LC1-F265
ATS-46C25N
3
132
15
NS400H-MA
320
LC1-F330
ATS-46C32N
3
Circuit
breaker
Calibre
Fusible
Fuse
rating
40
Inductance de
ligne
Line coil
Raccordement
section
cable cross
section area
Nombre de modules
Ventilateur
Number of modules
Fan
1
Fusible
(2)
Fuse
(2)
DF3-EF04001
VZ1-L015UM17T
4 mm2
9
4606 N
ATS-46D17N
1
DF3-EF04001
40
VZ1-L015UM17T
2
9
4606 N
LC1-D2510
ATS-46D22N
1
DF3-FF10001
100
VZ1-L030U800T
2
9
4606 N
LC1-D2510
ATS-46D22N
1
DF3-FF10001
100
VZ1-L030U800T
2
9
4606 N
-
LC1-D3210
ATS-46D32N
1
DF3-FF10001
100
VZ1-L040U600T
2
12
4606 N
50
LC1-D3210
ATS-46D32N
1
DF3-FF10001
100
VZ1-L040U600T
2
12
4606 N
-
LC1-D5011
ATS-46D38N
1
DF3-FF10001
100
VZ1-L040U600T
2
12
4606 N
50
LC1-D5011
ATS-46D38N
1
DF3-FF10001
100
VZ1-L040U600T
2
6 mm
12
4606 N
50
LC1-D5011
ATS-46D47N
2
DF3-NF40002
400
VZ1-L070U350T
10 mm2
12
4606 N
-
LC1-D6511
ATS-46D62N
2
DF3-NF40002
400
VZ1-L070U350T
2
16 mm
12
4606 N
-
LC1-D8011
ATS-46D75N
2
DF3-NF40002
400
VZ1-L150U170T
25 mm2
12
4606 N
100
LC1-F115
ATS-46D88N
2
DF3-NF40002
400
VZ1-L150U170T
2
35 mm
18
4606 N
400
VZ1-L150U170T
50 mm2
18
4606 N
500
VZ1-L150U170T
2
50 mm
18
4606 N
500
VZ1-L250U100T
95 mm2
36
2 x 4606 N
DF3-NF50002
500
VZ1-L250U100T
2
36
2 x 4606 N
DF3-QF63002
630
VZ1-L250U100T
2
36
2 x 4606 N
DF3-QF80002
800
VZ1-L325U075T
2
36
2 x 4606 N
Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de
puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température
ambiant plus élevée, consulter GIB.
(1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter
le nombre de modules.
(2): obrigatoire ajoute porte-fusible.
Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653.
Guide Technique V9 / V9 Technical Guide
Température ambiant 30 °C
Ambient temperature 30 °C
4 mm
6 mm
6 mm
6 mm
6 mm
6 mm
95 mm
95 mm
95 mm
Note: in case of switchboard installed in a ambient with 35 °C the values of power
must be derated in 6% for ATS 46. In case of higher ambient temperature, consult
BIM.
(1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the
number of modules.
(2): compulsory add fuse carrier.
Single line diagrams, according Telemecanique catalogue ART. 16653.
229
Installation de l’appareillage
Switchgear Installation
Blokset Ms
ATS46
415 V
Puissance
(kW)
Power
(kW)
5,5
Icc coord.
(kA)
Icc coord.
(kA)
15
5,5
7,5
Disjoncteur
Coordination Type 2
Coordination Type 2
GV2-L20
Calibre
(A)
Rating
(A)
-
Contacteur
(1)
Contactor
(1)
LC1-D2510
ATS
Taille
ATS
Size
ATS-46D17N
15
GV2-P21
-
15
GV2-L22
-
LC1-D2510
LC1-D2510
7,5
15
GV2-P22
-
11
15
GV7-RS40
-
LC1-D2510
LC1-D3210
11
15
NS80H-MA
50
15
15
GV7-RS50
15
18,5
15
15
22
30
15
15
37
45
Service: Sévère
Service: Severe
Température ambiant 30 °C
Ambient temperature 30 °C
Calibre
Fusible
Fuse
rating
40
Inductance de
ligne
Line coil
Raccordement
section
cable cross
section area
Nombre de modules
Ventilateur
Number of modules
Fan
1
Fusible
(2)
Fuse
(2)
DF3-EF04001
VZ1-L015UM17T
4 mm2
9
4606 N
ATS-46D17N
1
DF3-EF04001
40
VZ1-L015UM17T
2
9
4606 N
ATS-46D22N
1
DF3-FF10001
100
VZ1-L030U800T
2
9
4606 N
ATS-46D22N
1
DF3-FF10001
100
VZ1-L030U800T
2
9
4606 N
ATS-46D32N
1
DF3-FF10001
100
VZ1-L040U600T
2
6 mm
12
4606 N
LC1-D3210
ATS-46D32N
1
DF3-FF10001
100
VZ1-L040U600T
6 mm2
12
4606 N
-
LC1-D5011
ATS-46D38N
1
DF3-FF10001
100
VZ1-L040U600T
2
12
4606 N
NS80H-MA
50
LC1-D5011
ATS-46D38N
1
DF3-FF10001
100
VZ1-L040U600T
12
4606 N
NS80H-MA
50
LC1-D5011
ATS-46D47N
2
DF3-NF40002
400
VZ1-L070U350T
2
10 mm
12
4606 N
NS80H-MA
-
LC1-D6511
ATS-46D62N
2
DF3-NF40002
400
VZ1-L070U350T
16 mm2
12
4606 N
NS80H-MA
-
LC1-D8011
ATS-46D75N
2
DF3-NF40002
400
VZ1-L150U170T
2
25 mm
12
4606 N
15
NS100H-MA
100
LC1-F115
ATS-46D88N
2
DF3-NF40002
400
VZ1-L150U170T
35 mm2
18
4606 N
15
NS160H-MA
150
LC1-F115
ATS-46C11N
2
DF3-NF40002
400
VZ1-L150U170T
2
50 mm
18
4606 N
55
15
NS160H-MA
150
LC1-F150
ATS-46C14N
2
DF3-NF50002
500
VZ1-L150U170T
50 mm2
18
4606 N
75
15
NS250H-MA
220
LC1-F185
ATS-46C17N
3
DF3-NF50002
500
VZ1-L250U100T
2
95 mm
36
2 x 4606 N
90
15
NS250H-MA
220
LC1-F225
ATS-46C21N
3
DF3-NF50002
500
VZ1-L250U100T
95 mm2
36
2 x 4606 N
110
15
NS400H-MA
320
LC1-F265
ATS-46C25N
3
DF3-QF63002
630
VZ1-L250U100T
2
36
2 x 4606 N
132
15
NS400H-MA
320
LC1-F330
ATS-46C32N
3
DF3-QF80002
800
VZ1-L325U075T
2
36
2 x 4606 N
Circuit
breaker
Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de
puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température
ambiant plus élevée, consulter GIB.
(1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter
le nombre de modules.
(2): obrigatoire ajoute porte-fusible.
Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653.
Guide Technique V9 / V9 Technical Guide
4 mm
6 mm
6 mm
6 mm
2
6 mm
95 mm
95 mm
Note: in case of switchboard installed in a ambient with 35 °C the values of power
must be derated in 6% for ATS 46. In case of higher ambient temperature, consult
BIM.
(1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the
number of modules.
(2): compulsory add fuse carrier.
Single line diagrams, according Telemecanique catalogue ART. 16653.
230
Installation de l’appareillage
Switchgear Installation
Blokset Ms
ATS46
440 V
Puissance
(kW)
Power
(kW)
5,5
Icc coord.
(kA)
Icc coord.
(kA)
15
5,5
7,5
Disjoncteur
Coordination Type 2
Coordination Type 2
GV2-L20
Calibre
(A)
Rating
(A)
-
Contacteur
(1)
Contactor
(1)
LC1-D2510
ATS
Taille
ATS
Size
ATS-46D17N
15
GV2-P21
-
15
GV2-L22
-
LC1-D2510
LC1-D2510
7,5
15
GV2-P22
-
11
15
GV7-RS40
-
LC1-D2510
LC1-D3210
11
15
NS80H-MA
50
15
15
GV7-RS50
15
18,5
15
15
22
30
15
15
37
45
Service: Sévère
Service: Severe
Température ambiant 30 °C
Ambient temperature 30 °C
Calibre
Fusible
Fuse
rating
40
Inductance de
ligne
Line coil
Raccordement
section
cable cross
section area
Nombre de modules
Ventilateur
Number of modules
Fan
1
Fusible
(2)
Fuse
(2)
DF3-EF04001
VZ1-L015UM17T
4 mm2
9
4606 N
ATS-46D17N
1
DF3-EF04001
40
VZ1-L015UM17T
2
9
4606 N
ATS-46D22N
1
DF3-FF10001
100
VZ1-L030U800T
2
9
4606 N
ATS-46D22N
1
DF3-FF10001
100
VZ1-L030U800T
2
9
4606 N
ATS-46D32N
1
DF3-FF10001
100
VZ1-L040U600T
2
6 mm
12
4606 N
LC1-D3210
ATS-46D32N
1
DF3-FF10001
100
VZ1-L040U600T
6 mm2
12
4606 N
-
LC1-D5011
ATS-46D38N
1
DF3-FF10001
100
VZ1-L040U600T
2
12
4606 N
NS80H-MA
50
LC1-D5011
ATS-46D38N
1
DF3-FF10001
100
VZ1-L040U600T
12
4606 N
NS80H-MA
50
LC1-D5011
ATS-46D47N
2
DF3-NF40002
400
VZ1-L070U350T
2
10 mm
12
4606 N
NS80H-MA
-
LC1-D6511
ATS-46D62N
2
DF3-NF40002
400
VZ1-L070U350T
16 mm2
12
4606 N
NS80H-MA
-
LC1-D8011
ATS-46D75N
2
DF3-NF40002
400
VZ1-L150U170T
2
25 mm
12
4606 N
15
NS100H-MA
100
LC1-F115
ATS-46D88N
2
DF3-NF40002
400
VZ1-L150U170T
35 mm2
18
4606 N
15
NS160H-MA
150
LC1-F115
ATS-46C11N
2
DF3-NF40002
400
VZ1-L150U170T
2
50 mm
18
4606 N
55
15
NS160H-MA
150
LC1-F150
ATS-46C14N
2
DF3-NF50002
500
VZ1-L150U170T
50 mm2
18
4606 N
75
15
NS250H-MA
220
LC1-F185
ATS-46C17N
3
DF3-NF50002
500
VZ1-L250U100T
2
95 mm
36
2 x 4606 N
90
15
NS250H-MA
220
LC1-F225
ATS-46C21N
3
DF3-NF50002
500
VZ1-L250U100T
95 mm2
36
2 x 4606 N
110
15
NS400H-MA
320
LC1-F265
ATS-46C25N
3
DF3-QF63002
630
VZ1-L250U100T
2
36
2 x 4606 N
132
15
NS400H-MA
320
LC1-F330
ATS-46C32N
3
DF3-QF80002
800
VZ1-L325U075T
2
36
2 x 4606 N
Circuit
breaker
Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de
puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température
ambiant plus élevée, consulter GIB.
(1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter
le nombre de modules.
(2): obrigatoire ajoute porte-fusible.
Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653.
Guide Technique V9 / V9 Technical Guide
4 mm
6 mm
6 mm
6 mm
2
6 mm
95 mm
95 mm
Note: in case of switchboard installed in a ambient with 35 °C the values of power
must be derated in 6% for ATS 46. In case of higher ambient temperature, consult
BIM.
(1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the
number of modules.
(2): compulsory add fuse carrier.
Single line diagrams, according Telemecanique catalogue ART. 16653.
231
Installation de l’appareillage
Switchgear Installation
Blokset Ms
480 V Nema
Puissance
(kW)
Power
(kW)
7,5
Icc coord.
(kA)
Icc coord.
(kA)
15
7,5
9
9
11
11
ATS46
Disjoncteur
Coordination Type 2
Coordination Type 2
GV2-L20
Calibre
(A)
Rating
(A)
-
Contacteur
(1)
Contactor
(1)
LC1-D2510
ATS
Taille
ATS
Size
ATS-46D17N
15
GV2-P21
-
15
GV2-L22
-
LC1-D2510
LC1-D2510
15
GV2-P22
-
15
GV7-RS40
-
LC1-D2510
LC1-D3210
15
NS80H-MA
50
18,5
15
GV7-RS50
18,5
22
15
15
30
37
Service: Sévère
Service: Severe
Température ambiant 30 °C
Ambient temperature 30 °C
Calibre
Fusible
Fuse
rating
40
Inductance de
ligne
Line coil
Raccordement
section
cable cross
section area
Nombre de modules
Ventilateur
Number of modules
Fan
1
Fusible
(2)
Fuse
(2)
DF3-EF04001
VZ1-L015UM17T
4 mm2
9
4606 N
ATS-46D17N
1
DF3-EF04001
40
VZ1-L015UM17T
2
9
4606 N
ATS-46D22N
1
DF3-FF10001
100
VZ1-L030U800T
2
9
4606 N
ATS-46D22N
1
DF3-FF10001
100
VZ1-L030U800T
2
9
4606 N
ATS-46D32N
1
DF3-FF10001
100
VZ1-L040U600T
2
6 mm
12
4606 N
LC1-D3210
ATS-46D32N
1
DF3-FF10001
100
VZ1-L040U600T
6 mm2
12
4606 N
-
LC1-D5011
ATS-46D38N
1
DF3-FF10001
100
VZ1-L040U600T
2
12
4606 N
NS80H-MA
50
LC1-D5011
ATS-46D38N
1
DF3-FF10001
100
VZ1-L040U600T
12
4606 N
NS80H-MA
50
LC1-D5011
ATS-46D47N
2
DF3-NF40002
400
VZ1-L070U350T
2
10 mm
12
4606 N
15
NS80H-MA
-
LC1-D6511
ATS-46D62N
2
DF3-NF40002
400
VZ1-L070U350T
16 mm2
12
4606 N
15
NS80H-MA
-
LC1-D8011
ATS-46D75N
2
DF3-NF40002
400
VZ1-L150U170T
2
25 mm
12
4606 N
45
15
NS100H-MA
100
LC1-F115
ATS-46D88N
2
DF3-NF40002
400
VZ1-L150U170T
35 mm2
18
4606 N
55
15
NS160H-MA
150
LC1-F115
ATS-46C11N
2
DF3-NF40002
400
VZ1-L150U170T
2
50 mm
18
4606 N
75
15
NS160H-MA
150
LC1-F150
ATS-46C14N
2
DF3-NF50002
500
VZ1-L150U170T
50 mm2
18
4606 N
90
15
NS250H-MA
220
LC1-F185
ATS-46C17N
3
DF3-NF50002
500
VZ1-L250U100T
2
95 mm
36
2 x 4606 N
110
15
NS250H-MA
220
LC1-F225
ATS-46C21N
3
DF3-NF50002
500
VZ1-L250U100T
95 mm2
36
2 x 4606 N
132
15
NS400H-MA
320
LC1-F265
ATS-46C25N
3
DF3-QF63002
630
VZ1-L250U100T
2
36
2 x 4606 N
160
15
NS400H-MA
320
LC1-F330
ATS-46C32N
3
DF3-QF80002
800
VZ1-L325U075T
2
36
2 x 4606 N
Circuit
breaker
Note: en cas de tableaux installés dans un ambiant avec 35 °C les valeurs de
puissance doivent être déclassés de 6% pour ATS 46. Dans le cas d’une température
ambiant plus élevée, consulter GIB.
(1): comme option, est possible utiliser 2 contacteurs (2 x LC1 -...), sans augmenter
le nombre de modules.
(2): obrigatoire ajoute porte-fusible.
Diagrammes unifilaires suivant catalogue Telemecanique ART. 16653.
Guide Technique V9 / V9 Technical Guide
4 mm
6 mm
6 mm
6 mm
2
6 mm
95 mm
95 mm
Note: in case of switchboard installed in a ambient with 35 °C the values of power
must be derated in 6% for ATS 46. In case of higher ambient temperature, consult
BIM.
(1): as option, it’s possible to use 2 contactors (2 x LC1-...),without increasing the
number of modules.
(2): compulsory add fuse carrier.
Single line diagrams, according Telemecanique catalogue ART. 16653.
232
Installation de l’appareillage
Switchgear Installation
Blokset Ms
3.5.2.
IP pour démarreurs et variateurs de vitesse
IP for soft starters and variable speed drivers
Installer accessoires AIRTECHNIC suivant les références indiquée ci-dessous
Install AIRTECHNIC accessories according references indicated on table below
Degré de protection
Protection degree
IP 20
Grille + Ecran + Supports
Finger guards + Screen + Brackets
LZ 30P + LZ 40N + LZ 40-1 + LZ 120
Degré de protection
Protection degree
IP 31 / 42
Filtre métallique + Ecran + Supports
Metalic filter + Screen + Brackets
LZ 60 + LZ 40N + LZ 40-1 + LZ 120
Ventilateur
Fan
Debit (m3/h)
Air flow rate (m3/h)
Degré de protection
Protection degree
4606 N
180
IP 20/31/42
Guide Technique V9 / V9 Technical Guide
233
Sommaire du chapitre
Chapter contents
3.6. Câbles et barres rigides
Cables and rigid bar
3.6.1.
Câbles pour DOL démarreus (Integral, GV et Compact NS) ............... 235
Cables for DOL starting (Integral, GV and Compact NS)
3.6.2.
Câbles pour REV démarreus (Integral, GV et NS) ................................ 237
Cables for REV starting (Integral, GV and NS)
3.6.3.
Câbles pour Y/D démarreus (Integral, GV et NS) ................................. 239
Cables for Y/D starting (Integral, GV and NS)
Guide Technique V9 / V9 Technical Guide
234
Installation de l’appareillage
Switchgear Installation
3.6. Câbles et barres rigides
cables and rigid bar
Connexions internes des départs-moteurs
avec barres rigides ou câbles (souple multi
brins 105° C).
3.6.1.
Internal connections of starting motors with
rigid bars or cables (105 °C).
Câbles pour DOL démarreus (Integral, GV et Compact NS)
cables for DOL starting (Integral, GV and Compact NS)
DISJUNCTEURS
CONTACTEURS
Integral 18 (LD1-LB030)
RELAIS
THERMIQUE
THERMAL
RELAYS
LB1-LB03P
CIRCUIT BREAKERS
CONTACTORS
Integral 32 (LD1-LC030 & LD4-LC130)
LB1-LC03M
6 mm
LB1-LD03M
16 mm2
Integral 63 (LD1-LD030 & LD4-LD130)
GV2
LC1-D09/12
6 mm2
LC1-D32
6 mm
LC1-D40
10 mm2
2,5 mm
16 mm2
2
2
2,5
2
mm2
2,5 mm2
4 mm
2
4 mm2
6 mm
2
6 mm2
10 mm2
10 mm2
mm2
2.5 mm2
2.5
LC1-D32
6 mm
LC1-D38/40
10 mm2
10 mm2
10 mm2
LC1-D50/65
16 mm
2
16
mm2
16 mm2
25 mm
2
25
mm2
25 mm2
LC1-D95
25 mm
2
25
mm2
25 mm2
LC1-D115/F115
35 mm2
35 mm2
35 mm2
LC1-D150/F150
2
2
2
50 mm
6
mm2
6 mm2
50 mm
50 mm2
LC1-F185
2 x 35 mm
LC1-F225
2 x 35 mm2
2 x 35 mm2
2 x 35 mm2
LC1-F265
2
mm2
2 x 35 mm2
LC1-D09/12
2 x 35 mm
LC1-D80
LR2-D1/LRD0/1
LR2-D1/LRD0/2
LR2-D1/LRD1/2
LR2-D3/LRD2/3
LR2-D3/LRD2/3/33
LR2-D3/LRD33
LR2-D3/LRD33
LR9-F5
LC1-D115/F115
LR9-D5/F5
LC1-D18
LC1- D25
LC1-D32
LC1-D38/40
LC1-D50/65
LC1-D80
Guide Technique V9 / V9 Technical Guide
6 mm2
4 mm
LC1-D80
NS80
CÂBLES DE
SORTIE
OUTGOING
cables
2
2
LC1-K06/09/12
CÂBLES
INTERMÉDIAIRES
INTERMEDIATE
cables
6 mm2
2,5 mm
LC1-D18/25
GV7
CÂBLES
DÉNTREE
INCOME
cables
2,5
mm2
2
2 x 35 mm
2 x 35
2,5
mm2
2
2 x 35 mm2
2,5 mm2
4 mm2
4 mm2
4 mm2
6 mm2
6 mm2
6 mm2
6 mm2
6 mm2
6 mm2
10 mm2
10 mm2
10 mm2
16 mm2
16 mm2
16 mm2
25 mm2
25 mm2
25 mm2
25 mm2
25 mm2
25 mm2
25 mm2
25 mm2
25 mm2
235
Installation de l’appareillage
Switchgear Installation
DISJUNCTEURS
CONTACTEURS
CIRCUIT BREAKERS
CONTACTORS
NS100
LC1-D09/12
LC1-D18
LC1-D25/32
LC1-D38
NS400
NS 630
CÂBLES DE
SORTIE
OUTGOING
cables
2,5 mm2
2,5 mm2
2,5 mm2
4 mm2
4 mm2
4 mm2
6 mm2
6 mm2
6 mm2
10 mm2
10 mm2
10 mm2
mm2
2
10 mm2
10
LC1-D50/65
LR2-D3/
LR9-D5
LRD-33
16 mm2
16 mm2
16 mm2
16 mm2
16 mm2
16 mm2
2
2
25 mm2
16 mm2
16 mm2
16 mm2
2
2
25 mm2
10 mm
LC1-D65
LR2-D3/
LRD-33
LR9-D5
LC1-D80
LR9-D5
25 mm
LC1-D95
25 mm2
25 mm2
25 mm2
LC1-D95
LR2-D3/
LRD-33
LR9-D5
25 mm2
25 mm2
25 mm2
LC1-D115/F115
LR9-D5/F5
35 mm
2
2
35 mm2
LC1-D115
LRD-4
35 mm
2
mm2
35 mm2
LC1-D115
LRD-4
35 mm2
35 mm2
35 mm2
LC1-D115/F115
LR9-D5/F5
35 mm
2
mm2
35 mm2
LC1-D150/F150
LR9-D5/F5
50 mm
2
2
50 mm2
LC1-F185
LR9-D5
2 x 35 mm2
2 x 35 mm2
2 x 35 mm2
LC1-F185
LR9-F5
2 x 35 mm2
2 x 35 mm2
2 x 35 mm2
LC1-F225
LR9-F5
2 x 35 mm
2
2 x 35
mm2
2 x 35 mm2
LC1-F265
LR9-F5
2 x 50 mm
2
2 x 50
mm2
2 x 50 mm2
2 x 50 mm2
2 x 50 mm2
2 x 50 mm2
2 x 50 mm
2
2 x 50 mm2
2 x 50 mm
2
2 x 50 mm2
2
2 x 50 mm2
3 x 50
25 mm
25 mm
25 mm
35 mm
35
35
50 mm
LC1-F330
LR9-F5
LC1-F265
LR9-F5/F7
LC1-F330
LR9-F7
LC1-F400/500
LR9-F7
2 x 50 mm *
2 x 50 mm
LC1-F400
LR9-F7
3 x 50 mm2 *
2 x 95 mm2 **
LC1-F500
LR9-F7
3 x 50
LC1-F630
LR9-F7
*
* Pour Mf: barre rigide, suivant plan
d’assemblage.
** Pour Mw: barre rigide, suivant plan
d’assemblage.
Guide Technique V9 / V9 Technical Guide
CÂBLES
INTERMÉDIAIRES
INTERMEDIATE
cables
LR2-D1/3/
LRD-0/1/33
LC1-D80
NS250
CÂBLES
DÉNTREE
INCOME
cables
LC1-D40
LC1-D50/65
NS160
RELAIS
THERMIQUE
THERMAL
RELAYS
LR2-D1/
LRD-0/1
LR2-D1/
LRD-2
LR2-D3/
LRD-2/3
LRD-3
2
2 x 50 mm *
2
2 x 50 mm *
2
mm2
*
2 x 120
mm2
2 x 120
mm2
**
(Mf = 2x95 mm2)
3 x 50
(Mf = 2x120 mm2)
2 x 120 mm2
* To Mf type use rigid bar, according
assembly drawing.
** To Mw type use rigid bar, according
assembly drawing.
236
Installation de l’appareillage
Switchgear Installation
3.6.2.
Câbles pour REV démarreus (Integral, GV et NS)
cables for REV starting (Integral, GV and NS)
DISJUNCTEURS
CONTACTEURS
Integral 18 (LD5-LB130)
RELAIS
THERMIQUE
THERMAL
RELAYS
LB1-LB03P
CIRCUIT BREAKERS
CONTACTORS
Integral 32 (LD5-LC130)
LB1-LC03M
6 mm
LB1-LD03M
16 mm2
Integral 63 (LD5-LD130)
GV2
GV7
NS100
CÂBLES
INTERMÉDIAIRES
INTERMEDIATE
cables
CÂBLES DE
SORTIE
OUTGOING
cables
6 mm2
6 mm2
2
6 mm2
16 mm2
2 x LC1-D09/12
2.5 mm
2 x LC1-D18/25
4 mm2
4 mm2
4 mm2
2
mm2
6 mm2
10 mm2
10 mm2
mm2
2.5 mm2
2
2 x LC1-D32
6 mm
2 x LC1-D40
10 mm2
2.5
6
2 x LC1-K06/09
2.5 mm
2 x LC1-D32
6 mm2
2
2.5
mm2
6 mm2
2.5 mm2
6 mm2
2 x LC1-D38/40
10 mm
2 x LC1-D50/65
16 mm2
16 mm2
16 mm2
2
2
25 mm2
2
10 mm
2
10 mm2
2 x LC1-D80
25 mm
2 x LC1-D95
25 mm2
25 mm2
25 mm2
2
2
35 mm2
50 mm2
50 mm2
25 mm
2 x LC1-D115/F115
35 mm
2 x LC1-D150/F150
50 mm2
2 x LC1-F185
2 x 35 mm2
2 x 35 mm2
2 x 35 mm2
2 x LC1-F225
2
mm2
2 x 35 mm2
2 x 35 mm2
2 x 35 mm2
2 x 35 mm
2 x LC1-F265
NS80
CÂBLES
DÉNTREE
INCOME
cables
35 mm
2 x 35 mm2
2 x 35
2 x LC1-D09/12
LR2-D1/LRD-0/1
2.5 mm
2 x LC1-D18
LR2-D1/LRD-0/2
4 mm2
4 mm2
4 mm2
2 x LC1-D25
LR2-D1/LRD-1/2
LR2-D3
6 mm
2
2
6 mm2
2 x LC1-D32
LR2-D3/LRD-2/3
6 mm2
6 mm2
6 mm2
2 x LC1-D38/40
LR2-D3/
LRD-2/3/33
10
2 x LC1-D50/65
LR2-D3/LRD-33
2 x LC1-D80
LR2-D3/LRD-33
25 mm
2 x LC1-D80
LR9-F5
2 x LC1-D115/F115
LR9-D /F
25 mm
2 x LC1-D09/12
LR2-D1/LRD-0/1
2,5 mm2
2 x LC1-D18
LR2-D1/LRD-2
4 mm
2 x LC1-D25/32
LR2-D3/LRD-2/3
6 mm2
2 x LC1-D38
LRD-3
10 mm
2 x LC1-D40
LR2-D1/3/
LRD-0/1/33
2 x LC1-D50/65
LRD-33/LR9-D
2 x LC1-D50/65
LR2-D33
16 mm
2 x LC1-D80
LR2-D3/LR9-D/F
2 x LC1-D80
LR2-D33
25 mm
2 x LC1-D95
LR2-D3/LR9-D
2 x LC1-D95
LRD-33
25 mm
2 x LC1-D115/F115
LR9-D /F
2 x LC1-D115
LRD-33
Guide Technique V9 / V9 Technical Guide
2
2.5 mm
6 mm
mm2
2
2.5 mm2
mm2
10 mm2
16 mm2
16 mm2
16 mm2
2
mm2
25 mm2
25 mm2
25 mm2
25 mm2
2
2
25 mm2
2
10
25
25 mm
2,5 mm2
4 mm
2
4 mm2
6 mm2
6 mm2
2
10 mm2
10 mm2
10 mm2
10 mm2
16 mm2
16 mm2
16 mm2
2
2
16 mm2
25 mm2
25 mm2
25 mm2
2
2
25 mm2
25 mm2
25 mm2
25 mm2
2
2
25 mm2
35 mm2
35 mm2
35 mm2
2
2
35 mm2
35 mm
2
2,5 mm2
10 mm
16 mm
25 mm
25 mm
35 mm
237
Installation de l’appareillage
Switchgear Installation
DISJUNCTEURS
CONTACTEURS
CIRCUIT BREAKERS
CONTACTORS
NS160
2 x LC1-D150/F150
RELAIS
THERMIQUE
THERMAL
RELAYS
LR9-F
2 x LC1-D115/F115
LR9-D/F
35 mm
2 x LC1-F185
LR9-D5/F5
2 x 35 mm2
2 x 35 mm2
2 x 35 mm2
2 x LC1-F185
LR9-F5
2 x 35 mm2
2 x 35 mm2
2 x 35 mm2
2 x LC1-F225
LR9-F5
2 x 35 mm2
2 x 35 mm2
2 x 35 mm2
2 X LC1-F265
LR9-F
2 x 50 mm
2
2
2 x 50 mm2
2 x LC1-F330
LR9-F5
2 x 50 mm2
2 x 50 mm2
2 x 50 mm2
2 X LC1-F265
LR9-F7
*
2 x 50 mm2
2 x 50 mm2
2 x LC1-F330
LR9-F7
*
2 x 50 mm
2
2 x 50 mm2
2 x LC1-F400
LR9-F7
*
2 x 95 mm2
2 x 95 mm2
2 x LC1-F500
LR9-F7
*
2 x 95 mm
2
2 x 95 mm2
2 x LC1-F400
LR9-F7
*
2 x 95 mm2
2 x LC1-F500
LR9-F7
*
2 x 120 mm
2
2 x 120 mm2
2 x LC1-F630
LR9-F7
*
2 x 120 mm2
2 x 120 mm2
NS250
NS400
NS630
CÂBLES
DÉNTREE
INCOME
cables
CÂBLES
INTERMÉDIAIRES
INTERMEDIATE
cables
CÂBLES DE
SORTIE
OUTGOING
cables
50 mm2
50 mm2
50 mm2
2
2
35 mm2
* Pour Mf: barre rigide, suivant plan
d’assemblage.
Guide Technique V9 / V9 Technical Guide
35 mm
2 x 50 mm
2 x 95 mm2
* To Mf type use rigid bar, according
assembly drawing.
238
Installation de l’appareillage
Switchgear Installation
3.6.3.
Câbles pour Y/∆ démarreus (Integral, GV et NS)
cables for Y/∆ starting (Integral, GV and NS)
DISJUNCTEURS
CONTACTEURS
CIRCUIT BREAKERS
CONTACTORS
GV2
3 x LC1-D09/12
RELAIS
THERMIQUE
THERMAL
RELAYS
2.5 mm2
2
6 mm
2.5 mm
3 x LC1-D18
6 mm
2
6 mm2
10 mm2
2
2.5 mm
2
6 mm
10 mm2
2
2.5 mm2
2
6 mm2
3 x LC1-D32
10 mm
3 x LC1-D40
16 mm2
16 mm2
16 mm2
3 x LC1-D50
25 mm
2
25
mm2
25 mm2
3 x LC1-D80
35 mm
2
35
mm2
35 mm2
3 x LC1-D115/F115
35 mm2
35 mm2
35 mm2
3 x LC1D-150/F150
2
2
50 mm2
3 x LC1-D09/12
50 mm
2
2 x 35 mm
2
3 x LC1-D80
LR2-D3
3 x LC1-D80
LR9-F5/D5
25 mm
25 mm2
3 x LC1-F115/D115
LR9-F / D
3 x LC1-D09/12
LR2-D1/LRD-0/1
3 x LC1-D18
LR2-D1/LRD-2
3 x LC1-D32
50 mm
2 x 35 mm
3 x LC1-D50/65
3 x LC1-D40
10 mm
2
LR2-D1/
LRD-0/1
LR2-D1/
LRD-0/2
LR2-D3/
LRD-1/2/3
LR2-D3/
LRD-2/33
LR2-D3/LRD-33
3 x LC1-D25/32
NS250
2.5 mm2
10 mm2
3 x LC1-D18
NS160
2.5 mm2
3 x LC1-D40
3 x LC1-F225
NS100
CÂBLES DE
SORTIE
OUTGOING
cables
6 mm
3 x LC1-F185
NS80
CÂBLES
INTERMÉDIAIRES
INTERMEDIATE
cables
3 x LC1-D18/25/32
3 x LC1-K06/09
GV7
CÂBLES
DÉNTREE
INCOME
cables
2 x 35
2
10 mm2
mm2
2 x 35 mm2
2
2 x 35 mm2
2 x 35 mm
2.5 mm2
2.5 mm2
2.5 mm2
4 mm2
4 mm2
4 mm2
6 mm2
6 mm2
6 mm2
10 mm2
10 mm2
10 mm2
16 mm2
16 mm2
16 mm2
25 mm
2
25 mm
2
25 mm2
2
25 mm
2
25 mm2
25 mm2
25 mm2
mm2
2,5 mm2
2,5 mm
2
2,5
4 mm
2
LR2-D3/LRD-3
6 mm
2
3 x LC1-D40
LR2-D3/LRD-33
10 mm2
10 mm2
10 mm2
3 x LC1-D40
LR2-D1
10 mm
2
10 mm
2
10 mm2
3 x LC1-D50
LR2-D3/LRD-33
16 mm
2
16 mm
2
16 mm2
3 x LC1-D80
LR2-D3/LRD-33
25 mm2
25 mm2
25 mm2
3 x LC1-D80
LR9-F5/D5
25 mm
2
25 mm
2
25 mm2
3 x LC1-F115/D115
LR9-F / D/
LRD-33
LR2-D3/LRD-33
35 mm
2
35 mm
2
35 mm2
35 mm2
35 mm2
35 mm2
3 x LC1-D115
LRD-4/LR9-D5
35 mm2
35 mm2
35 mm2
3 x LC1-D150
LR9-D5
50 mm
2
mm2
50 mm2
3 x LC1-F115/D115
LR9-F / D
35 mm
2
2
35 mm2
50 mm2
50 mm2
50 mm2
50
mm2
50 mm2
50
mm2
50 mm2
50
mm2
50 mm2
3 x LC1-D80
3 x LC1-F150/D150
LR9-F / D
3 x LC1-D115
LRD-3/4
3 x LC1-D150
LRD-4
3 x LC1-F115/D115
4 mm2
6
mm2
6 mm2
50
35 mm
2 x 35 mm
2
2 x 35 mm
2
LR9-F5
2 x 35 mm
2
3 x LC1-F150
LR9-F5
2 x 35 mm2
3 x LC1-F185
LR9-F5
2 x 35 mm
2
3 x LC1-F225
LR9-F5
2 x 35 mm
2
3 x LC1-F265
LR9-F
2 x 35 mm
2
Guide Technique V9 / V9 Technical Guide
4
mm2
50 mm2
50 mm2
2 x 35 mm
2
2 x 35 mm2
2 x 35 mm
2
2 x 35 mm2
2 x 35 mm
2
2 x 35 mm2
239
Installation de l’appareillage
Switchgear Installation
DISJUNCTEURS
CONTACTEURS
CIRCUIT BREAKERS
CONTACTORS
NS400
3 x LC1-D150
NS 630
RELAIS
THERMIQUE
THERMAL
RELAYS
LRD-4
CÂBLES
DÉNTREE
INCOME
cables
*
CÂBLES
INTERMÉDIAIRES
INTERMEDIATE
cables
CÂBLES DE
SORTIE
OUTGOING
cables
50 mm2
50 mm2
3 x LC1-D150
LR9-D5
*
50 mm2
50 mm2
3 x LC1-F150
LR9-F5
*
2
3 x LC1-F185
LR9-F5
*
3 x LC1-F265
LR9-F7
50 mm
50 mm2
2 x 50 mm
2
2 xX 50 mm2
*
2 x 50 mm
2
2 x 50 mm2
3 x LC1-F330
LR9-F7
*
2 x 50 mm2
2 x 50 mm2
3 x LC1-F225
LR9-F5
*
2 x 50 mm
2
2 x 50 mm2
3 x LC1-F265
LR9-F7
*
2 x 50 mm
2
2 x 50 mm2
3 x LC1-F330
LR9-F7
*
2 x 50 mm2
2 x 50 mm2
3 x LC1-F400
LR9-F7
*
2
3 x LC1-F500
LR9-F7
*
* Pour Mf: barre rigide, suivant plan
d’assemblage.
Guide Technique V9 / V9 Technical Guide
2 x 95 mm
2 x 120 mm
2 x 95 mm2
2
2 x 120 mm2
* To Mf type use rigid bar, according
assembly drawing.
240
Sommaire du chapitre
Chapter contents
3.7. Installation Appareils dans BLOKSET
Installation devices in BLOKSET
3.7.1.
Mise en œuvre du PEN ........................................................................... 242
Implementing a PEN
Guide Technique V9 / V9 Technical Guide
241
Installation de l’appareillage
Switchgear Installation
3.7. Installation Appareils dans BLOKSET
Device installation in BLOKSET
3.7.1.
Mise en œuvre du PEN
Implementing a PEN
PEN
(*)
PE
L´utilisation du conducteur PEN dans une
unité fonctionnelle BLOKSET est possible
suivant le schéma ci-dessus (arrivée en TNC
- départ en TNC) et pour les disjoncteurs
ci-dessous.
Type du Disjoncteur
Type of Breaker
possibilités
possibilities
NS100 / 160 / 250
NB50 / 100 / 225
pas développé
not developed
NS400 / 630
oui
yes
NB400 / 600
The use of PEN conductor in BLOKSET
functional units is possible according the
diagram above (incoming TNC - outgoing
TNC) and for the following circuit breakers.
ref. Guide des plans d’assemblage
7041xxx.pdf
ref. Assembly drawings guide
7041xxx.pdf
3.5.1
1
pas développé
not developed
-
-
IN400/2500
oui
yes
3.5.2
1
NS630b/1600
oui
yes
3.5.3
1 .. 4
NT08/NT16
oui
yes
3.5.4
1 .. 4
NW08/63
oui
yes
3.5.5
1 .. 4
(*) Connexion entre Neutre et PE voir
chapitre 3.5.6. du Guide Montage.
Guide Technique V9 / V9 Technical Guide
Formes
Forms
-
(*) Connection between Neutral and PE
chapter 3.5.6.of Assembly Guide.
242
Sommaire du chapitre
Chapter contents
3.8. Compartiment de mesure/protection .............................................. 244
Measurement/Protection compartment
3.8.1.
Solution générale .................................................................................... 244
General solution
3.8.2.
Solution spécifique pour disjoncteur NW 3P ....................................... 245
Specific solution for 3P NW breakers
Guide Technique V9 / V9 Technical Guide
243
Installation de l’appareillage
Switchgear Installation
3.8. Compartiment de mesure/protection
Measurement/Protection compartment
3.8.1.
Solution générale
General solution
Ces compartiments sont disponibles pour
l’installation d’unités de protection ou de
mesures (ampèremetre, voltmetre,
SEPAM*, etc...). Pour informations
complémtentaires, voir chapitre 2.1 du Guide
des plans d’assemblage, ref. “7041xxx.pdf”.
Nombre de modules
Number of modules
4
6
8
9
12
Profondeur 180 mm
Depth 180 mm
oui
yes
oui
yes
oui
yes
oui
yes
oui
yes
(*) SEPAM 2000 possible uniquement en
profondeur 330 mm.
These compartiments are available for
metering or protection devices (ampmeter,
voltmeter, SEPAM*, etc...)
For additional information see Assembly
drawings guide, ref. “7041xxx.pdf”
Profondeur 330 mm
Depth 330 mm
oui
yes
oui
yes
oui
yes
(*) SEPAM 2000 possible only in 330 mm
depth.
Compartiment de mesure/protection
Metering/Protection compartment
4M jusqu'à 12M
4M up to 12M
Espace pour
installation des unités
fonctionnelles
connecteés au jeu de
barres vertical suivant
les besoins du client.
Space for installation
of functional units
connected to vertical
busbars according to
customer need.
Guide Technique V9 / V9 Technical Guide
244
Installation de l’appareillage
Switchgear Installation
3.8.2.
Solution spécifique pour disjoncteur NW 3P
Specific solution for 3P NW breakers
Les solutions standard suivantes sont à
utiliser pour les disjoncteurs tripolaires Nw08
à Nw40.
Standard solution showed hereunder have to
be used in case of 3 pole breaker Nw08 to
Nw40.
Compartiment de mesure/protection
Metering/Protection compartment
4M
4M
Option 4a
NW08-32
NW08-32
NW08-32
Option 8a
Option 4b
12M
12M
4M
12M
4M
4M
Option 8b
12M
Col 01
Col 03
Col 02
NW08-32
Col 04
4M - NW25
6M - NW32
4M - NW32
(*) 9M - NW40
Option 3a
(*) profondeur 180 mm seulement
(*) 180 mm depth only
Option 2
12M
12M
Guide Technique V9 / V9 Technical Guide
245
Sommaire du chapitre
Chapter contents
4. Auxiliaires et borniers
Auxiliaries and terminal blocks
4.1. Position des auxiliaires et des borniers ......................................... 247
Position of auxiliaries and terminal blocks
4.1.1.
Circuits auxiliaires importants .............................................................. 247
Major auxiliary circuits
4.1.2.
Circuits auxiliaires réduits ..................................................................... 247
Reduced auxiliary circuits
4.1.3.
Borniers d’auxiliaires importants > 150 mm ........................................ 248
Major auxiliary terminal blocks > 150 mm
4.1.4.
Borniers auxiliaires réduits < 150 mm .................................................. 248
Reduced auxiliary terminal blocks < 150 mm
4.1.5.
Borniers puissance ................................................................................. 248
Power terminal blocks
4.1.6.
Borniers de désaccouplement des auxiliaires ..................................... 248
Auxiliary decoupling terminal blocks
4.1.7.
Collecteur auxiliaire ................................................................................ 249
Auxiliary collector
Guide Technique V9 / V9 Technical Guide
246
Auxiliaires et borniers
Auxiliaries and terminal blocks
4. Auxiliaires et borniers
Auxiliaries and terminal blocks
4.1. Position des auxiliaires et des borniers
Position of auxiliaries and terminal blocks
4.1.1.
Circuits auxiliaires importants
Major auxiliary circuits
Ceux-ci seront installés dans des modules
relayage réservés à l’implantation de
l’appareillage et des bornes, ou (si possible)
dans la gaine de raccordement. Cette
implantation sera portée sur le schéma.
4.1.2.
These will be installed in the relay modules
reserved for the installation of the switchgear
and terminals, or (if possible) in the
connection duct. This installation will be
included in the diagram.
Circuits auxiliaires réduits
Reduced auxiliary circuits
Appareillage sur portillon:
„ La protection sera installée sur le
portillon en utilisant les multifix ci-aprèsþ:
‰ portillon 200: multifix 155 mm,
Switchgear on auxiliary compartment door:
„ Protection will be installed on the
auxiliary compartment door using the
following multifix rails:
‰ auxiliary compartment door 200: 155 mm
multifix rail.
2 trous oblongs / 2 oblong holes
6.5 x 8.5
‰ portillon 400: multifix 355 mm.
‰ auxiliary compartment door 400: 355 mm
multifix rail.
2 trous oblongs / 2 oblong holes
6.5 x 8.5
Guide Technique V9 / V9 Technical Guide
247
Auxiliaires et borniers
Auxiliaries and terminal blocks
Appareillage sur plastron:
„ La protection sera installée derrière le
plastron.
Switchgear on escutcheon:
„ Protection will be installed behind the
escutcheon.
Interdit: l’implantation d’appareillage sur un
plastron situé devant un jeu de barres
horizontal ou un jeu de barres de transfert.
It is forbidden to install the switchgear on
the escutcheon situated in front of a
horizontal busbar or transfer busbar
4.1.3.
Borniers d’auxiliaires importants > 150 mm
Major auxiliary terminal blocks > 150 mm
Ils seront installés dans des modules de
raccordement, seul ou avec l’appareillage
auxiliaire.
L’implantation sera portée sur le schéma.
4.1.4.
Borniers auxiliaires réduits < 150 mm
Reduced auxiliary terminal blocks < 150 mm
Ils seront installés dans la gaine à câbles
dans la mesure ou cela ne gène pas le
passage des câbles.
4.1.5.
These will be located either in the modules of
the switchgear compartment or in the cable
duct and will be included in the installation
diagram.
Borniers de désaccouplement des auxiliaires
Auxiliary decoupling terminal blocks
Les borniers de désaccouplement seront
situés dans le compartiment JdB 4 modules
du haut.
Guide Technique V9 / V9 Technical Guide
These will be installed in the cable duct
where this does not hinder the cable
leadthrough.
Borniers puissance
Power terminal blocks
Ils seront dans des modules du
compartiment appareillage ou dans la gaine
à câbles et portés sur le schéma
d’implantation.
4.1.6.
These are installed in connection modules,
alone or with auxiliary switchgear.
This installation will be included in the
diagram.
These terminal blocks will be located in the
top 4-module busbar compartment.
248
Auxiliaires et borniers
Auxiliaries and terminal blocks
4.1.7.
Collecteur auxiliaire
Auxiliary collector
Les circuits auxiliaires peuvent être
alimentés par collecteur auxiliare ref. 07400.
Voir figure ci dessous.
Peuvent être installés dans les colonnes
type D, Mf, Ms ou Mw.
The auxiliary circuits can be supplied by the
auxiliary collector ref. 07400.
See figure bellow:
It can be installed in columns D, Mf, Ms or
Mw.
Ref. 07400
In: 63 A - Ui= 660 V
Compartment des cables
Cable compartment
Guide Technique V9 / V9 Technical Guide
249
Sommaire du chapitre
Chapter contents
5. Divers
Miscellaneous
5.1. Lignes de fuite et distances d’isolement ...................................... 252
Creepage distance and clearance
5.1.1. Définition (IEC 60439.1) .......................................................................... 252
Definition (IEC 60439.1)
5.1.1.1. Distance d’isolement ................................................................. 252
Clearance
5.1.1.2. Ligne de fuite .............................................................................. 252
Creepage distance
5.2. Règles d’assemblage ...................................................................... 253
Assembly rules
5.2.1. Assemblages par vis .............................................................................. 253
Screw assembly
5.2.2. Assemblage électrique ........................................................................... 254
Electrical assembly
5.2.3. Assemblage mécanique ......................................................................... 255
Mechanical assemblies
5.2.4. Couples de serrage ................................................................................. 256
Tightening torques
5.2.4.1. Visserie à pas gros non graissé ............................................... 256
Not greased, wide pitch screws.
5.2.4.2. Autres visseries ......................................................................... 257
Other screws
5.3. Repérage .......................................................................................... 259
Labels and marking
5.4. Détrompage des tiroirs ................................................................... 259
Drawer polarization
5.5. Verrouillage des tiroirs ................................................................... 259
Drawer interlocking
5.6. Verrouillage mécanique des disjoncteurs en tiroir ...................... 259
Mechanical circuit breaking interlocking to drawer
5.7. Fin de course tiroirs Mw ................................................................. 259
Mw drawers limit switch
Guide Technique V9 / V9 Technical Guide
250
Sommaire du chapitre
Chapter contents
5.8. Réalisation des IP ............................................................................ 260
Realization of the IP
5.9. Montage épingles chauffantes et des Thermostats ..................... 261
Mounting heating pins and thermostat
5.9.1. Dimensionnement de l’épingle chauffante ........................................... 261
Heating pin rating
5.10. Tenue aux Séismes ......................................................................... 265
Seismic withstand
5.10.1.Procédure ................................................................................................ 265
Procedure
5.10.2.Montage des pièces additives ............................................................... 265
Assembling drawing
5.11. Tenue Arc Interne ............................................................................ 265
Internal Arc Withstand
5.11.1.Procédure ................................................................................................ 265
Procedure
5.11.2.Montage des pièces additives ............................................................... 265
Assembling drawing
5.12. Arrêt de Porte ................................................................................... 266
Door Stopper
5.12.1.Définition ................................................................................................. 266
Definition
5.12.2.Montage des pièces additives ............................................................... 266
Assembling drawing
Guide Technique V9 / V9 Technical Guide
251
Divers
Miscellaneous
5. Divers
Miscellaneous
5.1. Lignes de fuite et distances d’isolement
Creepage distance and clearance
5.1.1.
Définition (IEC 60439.1)
Definition (IEC 60439.1)
5.1.1.1.
Distance d’isolement
Clearance
La distance d’isolement est le distance entre
deux parties conductrices le long d’un fil
tendu suivant le plus court trajet possible
entre ces deux parties conductrices.
Elle dépend:
„ de la tension de choc (Uimp).
„ du degré de pollution.
5.1.1.2.
Clearance is the distance between the two
conductive parts the length of a tight wire
taking the shortest possible route between
the two conductive parts.
It varies according to the:
„ Impulse voltage (Uimp).
„ Degree of pollution.
Ligne de fuite
Creepage distance
La ligne de fuite est la distance la plus courte
le long de la surface d’une matière isolante
entre deux parties conductrices.
Elle dépend:
„ de la tension d’isolement (Ui).
„ du degré de pollution.
„ du groupe de matériaux.
Le degré de pollution retenu dans nos
tableaux est de niveau 3.
Les matériaux utilisés sont de classe 3A.
Creepage distance is the shortest distance
the length of the surface of an insulating
material between two conductive parts.
It varies according to the:
„ Insulating voltage (Ui).
„ Degree of pollution.
„ Group of materials.
The degree of pollution in our tables is level
3.
The materials used are class 3A.
Suivant IEC 60439.1
In compliance with the IEC Standard 60439.1
tableaux / switchboards
Jeux de barres principaux / Main busbars
dérivations / shunts
Uimp = 12 kV
Ui = 1000 V
Compact
Uimp = 8 kV
Ui = 750 V
Guide Technique V9 / V9 Technical Guide
Distance d’isolement
Clearance
14 mm
Ligne de fuite
Creepage distance
16 mm
8 mm
12,5 mm
252
Divers
Miscellaneous
5.2. Règles d’assemblage
Assembly rules
5.2.1.
Assemblages par vis
Screw assembly
Domaines d’application
Fields of application
Tous assemblages électriques ou
mécaniques vissés.
Utiliser de la visserie acier zingué
bichromaté (Zn8C) classe 8-8.
Les couples de serrage sont définis dans les
pages suivantes.
Dans l’association vis-rondelle, choisir une
rondelle de dureté au moins égale à celle de
vis. (E 25 030 $ 5.2.3.2).
All electrical and mechanical screw
assemblies.
Use galvanized, bi-chromated steel screws
(Zn8C) class 8-8.
The tightening torques are specified in the
following pages.
For the screw and washer combination
choose a washer which is at least as hard as
the screw. (E 25 030 $ 5.2.3.2).
tige filetée
threaded
Vis H
H screw
écrou H
H nut
écrou à bague de freinage plastique (type
nylstop)
nut with plastic braking
écrou à embase crantée (type thiant)t
latched collar nu
rondelle plate large et épaisse (ép. 2 mm)
thick, wide, flat washer (th. 2 mm)
rondelle “contact” série moyenne
“contact” washer, medium
rondelle “contact” à picots
picot edge “contact”
barre conductrice ou extrémité compactée
de tresse
“conducting” bar or compressed
Guide Technique V9 / V9 Technical Guide
253
Divers
Miscellaneous
5.2.2.
Assemblage électrique
Electrical assembly
„ Trou rond.
„ Round hole.
barre Cu / barre Cu
Cu bar / Cu bar
barre Cu / plage d'appareillage ou sur trou
taraudé
Cu bar / switchgear pad on threaded hole
Rappel: respecter le couple de serrage de
l'appareillage.
Note: respect switchgear tightening torque.
„ Trou ovalisé.
„ Oval hole.
Rajouter côté trou ovalisé une rondelle plate
épaisse large sous la rondelle contact. En
cas de doute, vérifier par un caLCul de RdM
(résistance des matériaux).
Add a thick, wide, flat washer to side with
oval hole below the contact washer. If in
doubt, check with an MR (material
resistance) caLCulation.
Rappel: la rondelle plate aura une largeur
égale à 2 fois le diamètre du trou ovalisé.
Note: the flat washer should be twice the
width of the diameter of the oval hole.
Guide Technique V9 / V9 Technical Guide
254
Divers
Miscellaneous
5.2.3.
Assemblage mécanique
Mechanical assemblies
„ Trou rond
„ Round hole
Sans nécessité de continuité électrique des
masses.
Does not require equipotential bonding of
exposed conductive parts.
Avec continuité électrique des masses.
With equipotential bonding of exposed
conductive parts.
Note: l'utilisation d'écrou à embase crantée
est parfois intéressante pour des raisons de
montage et d'accessibilité difficile, mais:
„ il revient plus cher, l'utilisation d'un
montage non symétrique n'est pas viable
vis à vis du desserrage (il est
recommandé de l'utiliser avec une vis à
embase crantée).
„ Il n'assure pas la continuité électrique
des masses.
„ Utilisation de l’écrou cage.
Note: using a latched collar nut can
sometimes facilitate difficult assembly and
access, but:
„ it is more expensive and using a nonsymmetrical assembly is not viable as
regards loosening (it is advisable to use it
with a latched collar nut).
„ It does not guarantee equipotential
bonding of exposed conductive parts.
„ Cage nut use.
L'écrou cage doit être adapté à l'épaisseur
de la tôle sur laquelle il se fixe.
The cage nut must be adapted to the
thickness of the plate onto which it is fixed.
Note: L'écrou n'assure pas la continuité des
masses sauf si utilisation de l'écrou cage à
picots.
Quand utiliser l'écrou cage sur parties
peintes, il doit être utilisé une écrou cage à
picots.
Note: the cage nut does not guarantee
equipotential bonding of exposed conductive
parts except when a picot edge cage nut is
used.
When using cage nut over painted parts, it
must be used picot squared box nut (ref.
4470579 VA).
Guide Technique V9 / V9 Technical Guide
255
Divers
Miscellaneous
5.2.4.
Couples de serrage
Tightening torques
Visserie à pas gros non graissé
Not greased, wide pitch screws.
5.2.4.1.
„ Tableau des couples de serrage pour la
visserie à pas gros non graissée.
(Valables pour les assemblages
électriques et mécaniques.)
„ Table of tightening torques for non
greased, wide pitch screws. (Valid for
electrical and mechanical assemblies).
Classe 8.8: Re = 64 daN/mm2
Rr = 80 daN/mm2
Suivant norme E 25 030
Class 8.8: Re = 64 daN/mm2
Rr = 80 daN/mm2
In compliance with standard E 25 030
Diamètre
élastique
Nominal
diameter
Pas
Pitch
Section
résistance
r2 moy
av.r2
crossresistance
Diam.
perçage
Max.
drilling
section
Force
axial
maxi
Axial
force
diameter
(mm)
(mm)
(mm2)
(mm)
(daN)
3
0,5
5,03
3,4
150
4
0,7
8,78
4,5
250
5
0,8
14,2
5,5
380
6
1
20,1
6,6
600
8
1,25
36,6
9
1000
10
1,5
58
11
1500
12
1,75
84,3
14
2400
14
2
115
16
3300
16
2
157
18
4500
18
2,5
192
20
5500
20
2,5
245
22
7100
Couple de serrage à 80% de la limite nominal
(m.daN) pour vis inox graissée ou acier classe 8.8 non graissée
Tightening torque at 80% of the elasticity limit
(m.daN) for greased steel screws or non greased class 8.8 steel screws
Ecrou avec rondelle
Ecrou embase crantée
Ecrou nylstop
Nut whit washer
latched collar nut
avec rondelle
Nylstop nut
with washer
Contact
Acier ou Alu
Cuivre
Contact
Contact
Steel or alu
Copper
Contact
0,15
0,15
0,17
0,17
0,35
0,35
0,41
0,38
0,70
0,80
0,93
0,75
1,3
1,35
1,55
1,45
2,8
2,5
2,9
3,1
5
5
5,9
5,4
7,5
7,9
9,2
8,3
12
12,5
14,6
13,2
18,5
18
21
20
26
27
31
28
37
39
45
41
Rappel: 1 cm kgf = 0,01m.daN
Note: 1 cm kgf = 0,01m.daN
Dispersion obtenue sur
Variations obtained on
Serrage
Tightening with
A la clé dynamométrique
Torque wrench
A la visseuse automatique
Automatic screw driver
A la clé manuelle
Manual spanner
A la clé à chocs
Impact spanner
Couple
Torque
± 10%
Force axiale*
Axial force*
± 30%
± 15%
± 30%
± 30%
± 50%
± 25%
* pourcentage cumulé avec la dispersion sur
le couple
Guide Technique V9 / V9 Technical Guide
* percentage accumulated after variations on
the torque.
256
Divers
Miscellaneous
5.2.4.2.
Autres visseries
Other screws
Pour une vis, une tige filetée ou écrou de
hauteur 0,8 x son diamètre constitué des
matériaux suivants (voir tableau ci-dessous),
multipliez le couple du tableau de la page
précédente par le coefficient A.
For a screw, a threaded rod or a nut with a
height which is 0.8 times its diameter made
in the following materials (see table below),
multiply the torque from the previous page by
the coefficient A.
Pour un trou taraudé (dans ces mêmes
matériaux), il est généralement possible
d’appliquer le couple prévu pour la vis à
condition de prévoir une longueur de filets de
prise suffisant soit:
„ 1 x d dans l’acier.
„ 1,5 x d dans la fonte et alliage de cuivre
(sauf traitement spécifique des filets)
For a threaded hole (in the same materials) it
is generally possible to use the torque
supplied for the screw, provided that length
of the connector threads is sufficient, i.e.:
„ 1 x d in steel.
„ 1.5 x d in copper smelting or copper alloy
(except special treatment for the
threads).
d = diamètre nominal de vis
d = screw’s nominal diameter.
Si cette longueur n’est pas suffisante,
appliquez le coefficient A du tableau cidessous.
En l’absence de coefficient, appliquez la
règle empirique:
„ A = RE / 48.
RE étant la limite élastique du matériau
considéré.
If this length is not sufficient, apply the
coefficient A from the table below.
Where there is no coefficient, apply the
empirical rule:
„ A = RE / 48.
where RE is the elastic limit of the material in
question.
Matériaux
Materials
Cuivre ETP H12
Copper ETP H12
AZ5 GU
AZ5 GU
Laiton
Brass
Bronze
Bronze
écrou en cage «Adx»
«Adx» cage nut
vis en cage «Adx»
«Adx» cage screw
Guide Technique V9 / V9 Technical Guide
A
0,4
0,65
de l’ordre de 0,50
in the order of 0.50
de l’ordre de 0,65
in the order of 0.65
0,5
0,5
257
Divers
Miscellaneous
Cas de la visserie acier classe 8.8 montée
graissée:
„ Certains ateliers utilisent simultanément
des vis inox et des vis acier de classe
8.8. A couple de serrage égal, une vis
montée graissée subit un effort axial plus
important que la même vis montée non
graissée. Les vis acier classe 8.8
montées graissées doivent donc être
serrées aux couples indiqués dans le
tableau ci-dessous.
Diamètre
Diameter
Pas
Pitch
6
1
8
1,25
12
1,75
16
2
18
2,5
Couple de serrage
Tightening torque
Rondelle plate
Rondelle contact
Flat washer
Contact washer
0,85
1
1,9
2,1
6,2
7
14
18,5
Après essais du laboratoire central des
matériaux et métrologie (Merlin Gerin), ces
couples ont été déterminés pour respecter
les 2 paramètres suivants:
„ Effort axial suffisant pour supprimer les
risques de desserrage de l’assemblage.
„ Effort axial limité pour ne pas dépasser la
limite élastique du matériau.
Guide Technique V9 / V9 Technical Guide
On class 8.8 steel screws mounted and
greased:
„ Certain works use both stainless steel
screws and class 8.8 steel screws. With
identical tightening torques, a screw
when mounted greased undergoes a
larger axial load than the same screw
when mounted non greased. Class 8.8
steel screws must therefore be tightened
with the torques indicated in the table
below.
After being tested at the material and
metrology central laboratory (Merlin Gerin),
these tightening torques were specified so
as to compy with the following 2 parameters:
„ Sufficient axial force to prevent assembly
loosening risks
„ Limited axial force so as not to exceed
the elastic limit of the material.
258
Divers
Miscellaneous
5.3. Repérage
Labels and marking
Voir Régles générales de mise en oeuvre
1913xxx.pdf
See General assembly rules 1913xxx.pdf.
5.4. Détrompage des tiroirs
Drawer polarization
Voir plan de montage n° 51 127 866.
See assembly drawing n° 51 127 866.
5.5. Verrouillage des tiroirs
Drawer interlocking
Voir plan de montage n° 51 127 789
See assembly drawing n° 51 127 789.
5.6. Verrouillage mécanique des disjoncteurs en tiroir
Mechanical circuit breaking interlocking to drawer
Voir plans de montage n° 51127978 /
51127979 / 51127980 / 51127981 /
51127982 / 51130415
See assembly drawings n° 51127978 /
51127979 / 51127980 / 51127981 /
51127982 / 51130415
5.7. Fin de course tiroirs Mw
Mw drawers limit switch
2 solutions d’implantation des micros fin de
course sont disponibles pour la position des
tiroir Mw:
1 - Micro contacts embarqués, ref.
XC1ZP2105, 10 A / 500 V.
2 - Micro contacts sur séparateur, ref. 87466,
5 A / 230 V.
1 - MICRO CONTACTS
EMBARQUÉS /
1 - MICRO SWITCHES ON
DRAWER
1 - Micro switches on drawers, ref.
XC1ZP2105, 10 A / 500 V
2 - Microswitches on separateur, ref. 87466,
5 A / 230 V.
Ref.: XC1ZP2105
Etiquette de position / Indicator Label
S0
S02
Identification des micro contacts:
S0 - Indicateur du tiroir en position test ou
alimentation auxiliaire externe.
S01 - Ouverture du contacteur
S02 - Indicateur du tiroir en position
embroché
Guide Technique V9 / V9 Technical Guide
2 solutions for micro switches assembly are
available for Mw drawers:
S01
Identification microswitchs:
S0 - Indicator of drawer in test position or
external auxiliary source.
S01 - Switching off the contactor
S02 - Indicator of drawer in connected
position
259
Divers
Miscellaneous
2 - MICRO CONTACTS SUR
SEPARATEUR /
2 - MICRO SWITCHES ON
SEPARATOR
S03
S04
S05
Ref.: 87466
Chaque rèference
contient 3 pièces /
Each reference
contains 3 pieces
Etiquette de position / Indicator Label
Identification des micro contacts montés sur
le separateur:
S03 - Connecté
S04 - Position test
S05 - Déconnecté
The identification of the limit switches
installed on the separator are:
S03 - Connected
S04 - Test position
S05 - Disconnected
Pour les détails additionnels voir plans
d’assemblage n° 51127739 / 51127984 pour
installation dans tiroirs, nº 51132458 pour
installation sur séparateur.
For additional details see assembly drawings
n° 51127739 / 51127984 in case of switches
on drawers or 51132458 in case of switches
on separator.
5.8. Réalisation des IP
Realization of the IP
Pour réalisation des IP, voir les règles dans
le guide des plans d’assemblage guide, ref.
“7041xxx.pdf”, item 6.6.
Guide Technique V9 / V9 Technical Guide
For IP realisation, see the rules on item 6.6
of Assembly drawings guide, ref.
“7041xxx.pdf”.
260
Divers
Miscellaneous
5.9. Montage épingles chauffantes et des Thermostats
Mounting heating pins and thermostat
5.9.1.
Dimensionnement de l’épingle chauffante
Heating pin rating
Principe:
„ Le dimensionnement consiste à
déterminer la puissance que doit dissiper
la résistance de l’épingle chauffante (Pw)
afin de maintenir à l’intérieur du tableau
une température moyenne (T1)
supérieur à la température de rosée (Tr)
de l’air en tenant compte de la
dissipation calorifique de l’enveloppe
(convection, ventilation).
Principle:
„ Rating consists of determining the power
which the heating pin resistor must
dissipate (Pw) so as to maintain an
average temperature (T1) inside the
switchboard which is higher than the
condensation temperature (Tr) while
taking the enclosure’s heat dissipation
into account (convection, ventilation).
Tableau ventilé:
„ Pw = h.S.(T1-Ta) + z.Cp.(T1-Ta)
Tableau étanche:
„ Pw = h.S.(T1-Ta)
Ventilated switchboard:
„ Pw = h.S.(T1-Ta) + z.Cp.(T1-Ta).
Sealed switchboard:
„ Pw = h.S.(T1-Ta).
avec:
T1: température souhaitée à l’intérieur du
tableau (en °C).
Ta: température de l’air ambiant (en °C).
S: surface d’échange (en m2).
h: coefficient d’échange (en W/m2.°C).
z: débit d’air (en Kg/s.).
Cp: capacité calorifique de l’air (en J/Kg.°C).
where:
T1: desired temperature inside the
switchboard (in °C).
Ta: ambient air temperature (in °C).
S: exchange surface area (in m2).
h: exchange coefficient (in W/m2.°C).
z: air flowrate (in Kg/s.).
Cp: air heat capacity (in J/Kg.°C).
Remarques:
„ h a une valeur de 4 à 5 W/m2.°C.
„ S correspond soit à la surface des parois
du tableau en contact avec l’air ambiant
pour une enveloppe non cloisonnée soit
à la surface des parois contenant
l’épingle chauffante pour une enveloppe
cloisonnée.
„ z est fonction du tableau (section
d’entrée d’air, cloisonnement...).
Observations:
„ h has a value of 4 to 5 W/m2.°C.
„ S corresponds either to the surface area
of the walls of the switchboard which are
in contact with the ambient air for a non
partitioned enclosure or to the surface
area of the walls containing the heating
pin for a partitioned enclosure.
„ z depends on the switchboard (air input
cross-section, partitioning, etc...).
Applications:
Applications:
„ Dimensionnement de la résistance d’une
épingle chauffante:
‰ relation puissance/échauffement:
– IP 31 ............................... ÷ Pw = 40. ∆T
„ Rating the resistor of a heating pin:
– IP 54 ............................... ÷ Pw = 22,7.
avec ∆T = T1 - Ta.
Guide Technique V9 / V9 Technical Guide
∆T
‰ power / heating ratio:
– IP 31 ............................... ÷ Pw = 40. ∆T
– IP 54 ............................... ÷ Pw = 22,7. ∆T
where ∆T = T1 - Ta.
261
Divers
Miscellaneous
CALCUL:
Calculation:
„ Démarche:
‰ 1: état initial de l’air: température,
humidité relative
=> déterminer Tr, température de rosée (Cf
tableau en annexe)
‰ 2: T1 = Tr + 5 (en °C): la résistance doit
permettre de maintenir une température
interne moyenne de 5°C au dessus de la
température de rosée.
‰ 3: application des formules.
„ Approach:
‰ 1: initial state of air: temperature, relative
humidity
=> determine Tr, condensation temperature
(see table in appendix)
‰ 2: T1 = Tr + 5 (in °C): the resistor must
make it possible to maintain an average
inside temperature of 5°C above the
condensation temperature.
‰ 3: apply formulas.
Exemple:
„ IP31 en fonctionnement normal.
„ ..Température de
l’air interne 60 °C.
}
} => Température de
}
condensation: Tr = 40 °C
„ Humidité relative 40%
„ Température de l’air ambiant: 35 °C.
Example:
„ IP31 in normal operating conditions.
„ Inside air
temperature 60 °C.
}
} => Condensation
}
temperature: Tr = 40 °C
„ Relative humidity 40%.}
„ Ambient air temperature: 35 °C.
Arrêt du tableau fi baisse de la température
interne. Pour éviter la condensation on doit
maintenir une température interne moyenne
T1 = 40 + 5 = 45 °C
Switchboard stopped drop in inside
temperature. To avoid condensation an
average inside temperature of T1 = 40 + 5 =
45 °C must be maintained.
Application des formules:
„ ∆T = 45 - 35 = 10 °C.
„ Pw = 40. 10 = 400 W.
Application of formulas:
„ ∆T = 45 - 35 = 10 °C.
„ Pw = 40. 10 = 400 W.
Remarque: si Tr ð Ta il n’y a pas besoins
d’épingle chauffante.
Note: if Tr ðTa there is no need for a heating
pin.
Installation:
„ Il convient d’installer dans la mesure du
possible l’épingle chauffante dans la
partie inférieur de la zone jeux de barres/
dérivations amont des appareils en
tenant compte de son accessibilité.
„ L’épingle chauffante doit être installée de
façon à ce qu’elle n’échauffe pas les fils
qui l’alimentent (fils d’alimentation en
position basse).
Installation:
„ It is advisable to install the heating pin
where possible in the lower part of the
busbar / connections zone downstream
of the circuit breakers while taking its
accessibility into account.
„ The heating pin must be installed in such
a way as to ensure that it does not heat
the wires which supply it (supply wires in
bottom position).
Pour Blokset, un montage standardisé est en
cours d’études.
For Blokset, a standardised assembly is
being studied.
Guide Technique V9 / V9 Technical Guide
262
Divers
Miscellaneous
Tableau de choix des épingles chauffantes
Selection table of heating pins
„ Tension d’utilisation: 230 V
Puissance
Power
Référence MGA
MGA reference
60 W
150 W
250 W
07992
07993
07994
„ Operating voltage: 230 V
Thermostat
Thermostat
„ Il permet de régler et de limiter la
température à l’intérieur de l’armoire
après l’installation d’épingles
chauffantes.
„ The thermostat allows the temperature
inside the cubicle to be regulated and
limited after the heating pins have been
installed.
Température d’utilisation: +10°C à + 50°C.
Tension d’utilisation: 230 V.
Fixation: sur rail multifix.
Référence: 07999.
Operating temperature: +10°C to + 50°C
Operating voltage: 230 V
Fixing: on multifix rail.
Reference: 07999.
Guide Technique V9 / V9 Technical Guide
263
Divers
Miscellaneous
Annexe
Appendix
Valeurs de température de rosée pour
différentes humidités et température initiale
d’air
Température initiale de l’air (°C)
Initial air temperature (°C)
40 °C
50 °C
60 °C
70 °C
80 °C
Guide Technique V9 / V9 Technical Guide
Humidité relative
Relative Humidity
30%
40%
50%
70%
100%
30%
40%
50%
70%
100%
30%
40%
50%
70%
100%
30%
40%
50%
70%
100%
30%
40%
50%
70%
100%
Condensation temperature values for
different air humidities and initial
temperatures
Température de rosée Tr (°C)
Condensation temperature (°C)
19 °C
22 °C
25 °C
31 °C
40 °C
27 °C
30 °C
36 °C
43 °C
50 °C
35 °C
40 °C
45 °C
52 °C
60 °C
44 °C
50 °C
54 °C
60 °C
70 °C
50 °C
57 °C
64 °C
70 °C
80 °C
264
Divers
Miscellaneous
5.10. Tenue aux Séismes
Seismic withstand
5.10.1. Procédure
Procedure
Voir “Procédure d’essais de séisme” n° PE
9703001 (11 pages).
Fichier informatique Proseis f.doc.
See “Seismic Test Procedure” nb: PE
9703001 (11 pages).
Electronic file Proseisa.doc.
5.10.2. Montage des pièces additives
Assembling drawing
Voir Guide des plans d’assemblage, ref.
7041xxx.pdf, chapitre 7 et Synoptique
BLOKSET, 51131911, plus Guide des
Références 1910xxx.doc .
See Assembling Drawings Guide
7041xxx.pdf chapter 7 and Synoptic
BLOKSET, 51131911, plus Reference Guide
1910xxx.doc.
5.11. Tenue Arc Interne
Internal Arc Withstand
5.11.1. Procédure
Procedure
Voir “Rapport d’essai n° 001-98”.
Fichier informatique “ART84296.pdf”.
See “ASEFA Test Report nb. 001-98” .
Electronic file “ART84296.pdf”.
5.11.2. Montage des pièces additives
Assembling drawing
Voir Guide des plans d’assemblage
“7041xxx.pdf”, chapitre 2.5.
Guide Technique V9 / V9 Technical Guide
.See Assembling Drawings Guide ref.
“7041xxx.pdf”, chapter 2.5.
265
Divers
Miscellaneous
5.12. Arrêt de Porte
Door Stopper
5.12.1. Définition
Definition
L’arrêt de porte peut être monté sur toutes
les portes gauches ou droites, sauf pour la
porte 15 M d’un tiroir débrochable et la porte
arrière d’une colonne Mw.
This door stopper can be assembled on all
left or right doors, except on 15M doors of
withdrawable functional units and rear door
of Mw column.
Arrêt de Porte /
Door Stopper
5.12.2. Montage des pièces additives
Assembling drawing
Voir Guide des plans d’assemblage, ref.
“7041xxx.pdf”, chapitre 2.5.
Guide Technique V9 / V9 Technical Guide
See Assembling drawings guide, ref.
“7041xxx.pdf”, chapter 2.5.
266
Sommaire du chapitre
Chapter contents
6. Annex 01 ....................................................................... 270
Appendix 01
6.1. Blokset Mf / Mw ................................................................................ 270
Protection moteurs ancienne gamme
Motor protection old range
6.1.1. Tableaux de coordination et modularité ............................................... 270
Coordination and modularity tables
6.1.1.1.
GV2-P .......................................................................................... 271
Type de coordination: 1
Coordination type: 1
6.1.1.2.
GV2-P .......................................................................................... 273
Type de coordination: 2
Coordination type: 2
6.1.1.3.
Etoile / Triangle (Y/D)
STAR / DELTA (Y/D)
Compact NS80H-MA .................................................................. 297
Type de coordination: 2
Coordination Type: 2
Guide Technique V9 / V9 Technical Guide
2 sens de marche
Reverse
Compact NS80H-MA .................................................................. 295
Type de coordination: 1
Coordination type: 1
6.1.1.12.
2 sens de marche
Reverse
Compact NS80H-MA .................................................................. 291
Type de coordination: 2
Coordination type: 2
6.1.1.11.
DOL (Démarrage direct)
DOL (Direct On Line)
Compact NS80H-MA .................................................................. 288
Type de coordination: 1
Coordination type: 1
6.1.1.10.
DOL (Démarrage direct)
DOL (Direct On Line)
Compact NS80H-MA .................................................................. 284
Type de coordination: 2
Coordination type: 2
6.1.1.9.
Etoile / Triangle (Y/D)
STAR / DELTA (Y/D)
Compact NS80H-MA .................................................................. 281
Type de coordination: 1
Coordination type: 1
6.1.1.8.
Etoile / Triangle (Y/D)
STAR / DELTA (Y/D)
GV2-P .......................................................................................... 280
Type de coordination: 2
Coordination type: 2
6.1.1.7.
2 sens de Marche
Reverse
GV2-P .......................................................................................... 279
Type de coordination: 1
Coordination type: 1
6.1.1.6.
2 sens de Marche
Reverse
GV2-P .......................................................................................... 277
Type de coordination: 2
Coordination type: 2
6.1.1.5.
DOL (Démarrage direct)
DOL (Direct On Line)
GV2-P .......................................................................................... 275
Type de coordination: 1
Coordination type: 1
6.1.1.4.
DOL (Démarrage direct)
DOL (Direct On Line)
Etoile / Triangle (Y/D)
STAR / DELTA (Y/D)
267
Sommaire du chapitre
Chapter contents
6.1.1.13.
Compact NS100-630l-MA ........................................................... 301
Type de coordination: 1
Coordination type: 1
6.1.1.14.
Compact NS100-630l-MA ........................................................... 307
Type de coordination: 2
Coordination type: 2
6.1.1.15.
Etoile / Triangle (Y/D)
STAR / DELTA (Y/D)
GV7 .............................................................................................. 349
Type de coordination: 2
Coordination Type: 2
6.1.1.25.
2 sens de marche
Reverse
GV7 .............................................................................................. 345
Type de coordination: 1
Coordination Type: 1
6.1.1.24.
2 sens de marche
Reverse
GV7 .............................................................................................. 341
Type de coordination: 2
Coordination Type: 2
6.1.1.23.
DOL (Démarrage direct)
DOL (Direct On Line)
GV7 .............................................................................................. 337
Type de coordination: 1
Coordination Type: 1
6.1.1.22.
DOL (Démarrage direct)
DOL (Direct On Line)
GV7 .............................................................................................. 333
Type de coordination: 2
Coordination Type: 2
6.1.1.21.
Etoile / Triangle (Y/D)
STAR / DELTA (Y/D)
GV7 .............................................................................................. 329
Type de coordination: 1
Coordination Type: 1
6.1.1.20.
Etoile / Triangle (Y/D)
STAR / DELTA (Y/D)
Compact NS100-630l-MA ........................................................... 325
Type de coordination: 2
Coordination Type: 2
6.1.1.19.
2 sens de marche
Reverse
Compact NS100-630l-MA ........................................................... 321
Type de coordination: 1
Coordination type: 1
6.1.1.18.
2 sens de marche
Reverse
Compact NS100-630l-MA ........................................................... 317
Type de coordination: 2
Coordination type: 2
6.1.1.17.
DOL (Démarrage direct)
DOL (Direct On Line)
Compact NS100-630l-MA ........................................................... 311
Type de coordination: 1
Coordination type: 1
6.1.1.16.
DOL (Démarrage direct)
DOL (Direct On Line)
Etoile / Triangle (Y/D)
STAR / DELTA (Y/D)
INTEGRAL ................................................................................... 353
Contacteurs-Disjoncteurs INTEGRALDOL (Démarrage direct)
INTEGRAL contactors-circuit breakersDOL (Direct On Line)
6.1.1.26.
INTEGRAL ................................................................................... 356
Contacteurs-Disjoncteurs INTEGRAL2 sens de marche
INTEGRAL contactors-circuit breakersReverse
6.1.1.27.
GV2-P .......................................................................................... 359
Type de coordination: 1
Coordination type: 1
6.1.1.28.
GV2-P .......................................................................................... 359
Type de coordination: 2
Coordination type: 2
Guide Technique V9 / V9 Technical Guide
DOL monophasé (Démarrage direct)
Single phase - DOL (Direct On Line)
DOL monophasé (Démarrage direct)
Single phase - DOL (Direct On Line)
268
Sommaire du chapitre
Chapter contents
6.1.1.29.
Compact NS80H-MA .................................................................. 360
Type de coordination: 1
Coordination type: 1
6.1.1.30.
DOL monophasé (Démarrage direct)
Single phase - DOL (Direct On Line)
Compact NS80H-MA .................................................................. 360
Type de coordination: 2
Coordination type: 2
DOL monophasé (Démarrage direct)
Single phase - DOL (Direct On Line)
6.1.2. Déclassement des appareils - AC3 ....................................................... 361
Starters derating - AC3
6.1.2.1.
GV2-P .......................................................................................... 361
Type de coordination: 1-2
Coordination type: 1-2
6.1.2.2.
Compact NS et GV7 ................................................................... 362
Compact NS and GV7
Type de coordination: 1-2
Coordination type: 1-2
6.1.2.3.
Integral ........................................................................................ 366
Contacteurs - Disjoncteurs IntegralCoordination totale
Integral Contactors - Circuit breakersTotal coordination
Guide Technique V9 / V9 Technical Guide
269
Anex 01
Appendix 01
6. Annex 01
Appendix 01
6.1
Blokset Mf / Mw
Protection moteurs ancienne gamme
Motor protection old range
6.1.1.
Tableaux de coordination et modularité
Coordination and modularity tables
Blokset Type Mf et Mw
Les GV7 peuvent être remplacés par les
appareils NS100 / 250 associés à un
déclencheur électronique protection moteur
(à définir cas par cas).
La modularité des associations avec NS +
déclencheur est la même que celles définies
avec les GV7.
Guide Technique V9 / V9 Technical Guide
Blokset Type Mf and Mw
GV7 CB’s can be replaced by NS100 / 250
CB’s equipped with a electronic trip unit
dedicated to motor protection (to be defined
case per case).
The number of modules of this kind of starter
are the same than the ones given for GV7
CB’s.
270
Anex 01
Appendix 01
6.1.1.1.
GV2-P
Type de coordination: 1 - - - - - - - - - - - - - - - -DOL (Démarrage direct)
Coordination type: 1 - - - - - - - - - - - - - - - - - - -DOL (Direct On Line)
GV2-P
220/240 V
Puissance moteur
Power motor
P (kW)
I (A)
0,06
0,38
0,09
0,65
0,12
0,75
0,18
1,04
0,25
1,47
0,37
2
0,55
2,8
0,75
3,6
1,1
5,2
1,5
6,8
2,2
9,6
3
11,5
4
14,5
5,5
22
Pdc
BC
Icu (kA)
Rms (kA)
50
50
50
50
50
50
50
50
50
50
50
50
50
50
Type de coordination: 1
Coordination type: 1
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV2-P03
0,25...0,40
GV2-P05
0,63...1
GV2-P05
0,63...1
GV2-P06
1...1,6
GV2-P06
1...1,6
GV2-P07
1,6...2,5
GV2-P08
2,5...4
GV2-P08
2,5...4
GV2-P10
4...6,3
GV2-P14
6...10
GV2-P16
9...14
GV2-P16
9...14
GV2-P20
13...18
GV2-P22
20...25
DOL (Démarrage direct)
DOL (Direct On Line)
Nb modules
Nbr of modules
Contacteur
Contactor
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K09
LC1-D12
LC1-D12
LC1-D18
LC1-D25
Mf
Mw
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Ancienne gamme
Old range
GV2-P
380 / 415V
Puissance moteur
Power motor
P (kW)
I (A)
Pdc
BC
Icu (kA)
Rms (kA)
50
50
50
50
50
50
Type de coordination: 1
Coordination type: 1
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV2-P02
0,16... 0,25
GV2-P03
0,25...0,40
GV2-P04
0,40... 0,63
GV2-P04
0,40... 0,63
GV2-P05
0,63...1
GV2-P06
1...1,6
Contacteur
Contactor
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
3
3
3
3
3
DOL (Démarrage direct)
DOL (Direct On Line)
Nb modules
Nbr of modules
Mf
Mw
0,06
0,22
0,09
0,36
3
3
3
3
0,12
0,42
0,18
0,6
3
3
3
0,25
0,88
3
0,37
0,98
0,55
1,5
50
GV2-P06
1...1,6
LC1-K06
3
0,75
2
50
GV2-P07
1,6...2,5
LC1-K06
3
3
1,1
2,5
50
GV2-P08
2,5...4
LC1-K06
3
3
1,5
3,5
50
GV2-P08
2,5...4
LC1-K06
3
3
2,2
5
50
GV2-P10
4...6,3
LC1-K06
3
3
3
6,5
50
GV2-P14
6...10
LC1-K09
3
3
4
8,4
50
GV2-P14
6...10
LC1-K09
3
3
5,5
11
15
GV2-P16
9...14
LC1-D12
3
3
7,5
14,8
15
GV2-P20
13...18
LC1-D18
3
3
9
18,1
15
GV2-P21
17...23
LC1-D25
3
3
11
21
15
GV2-P22
20...25
LC1-D25
3
3
Ancienne gamme
Guide Technique V9 / V9 Technical Guide
271
Anex 01
Appendix 01
Old range
GV2-P
440 V
Puissance moteur
Power motor
P (kW)
I (A)
0,06
0,19
0,09
0,28
0,12
0,37
0,18
0,55
0,25
0,76
0,37
0,99
0,55
1,36
0,75
1,68
1,1
2,37
1,5
3,06
2,2
4,42
3
5,77
4
7,9
5,5
10,4
7,5
13,7
9
16,9
11
20,1
Pdc
BC
Icu (kA)
Rms (kA)
50
50
50
50
50
50
50
50
50
50
50
50
15
8
8
8
6
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV2-P02
0,16... 0,25
GV2-P03
0,25...0,40
GV2-P03
0,25...0,40
GV2-P04
0,40... 0,63
GV2-P05
0,63...1
GV2-P06
1...1,6
GV2-P06
1...1,6
GV2-P07
1,6...2,5
GV2-P07
1,6...2,5
GV2-P08
2,5...4
GV2-P10
4...6,3
GV2-P10
4...6,3
GV2-P14
6...10
GV2-P16
9...14
GV2-P20
13...18
GV2-P20
13...18
GV2-P21
17...23
Type de coordination: 1
Coordination type: 1
DOL (Démarrage direct)
DOL (Direct On Line)
Nb modules
Nbr of modules
Contacteur
Contactor
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K09
LC1-D12
LC1-D18
LC1-D18
LC1-D25
Mf
Mw
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Ancienne gamme
Old range
Guide Technique V9 / V9 Technical Guide
272
Anex 01
Appendix 01
6.1.1.2.
GV2-P
Type de coordination: 2 - - - - - - - - - - - - - - - -DOL (Démarrage direct)
Coordination type: 2 - - - - - - - - - - - - - - - - - - -DOL (Direct On Line)
GV2-P
220/240 V
Puissance moteur
Power motor
P (kW)
I (A)
0,06
0,38
0,09
0,65
0,12
0,75
0,18
1,04
0,25
1,47
0,37
2
0,55
2,8
0,75
3,6
1,1
5,2
1,5
6,8
2,2
9,6
3
11,5
4
14,5
5,5
22
Pdc
BC
Icu (kA)
Rms (kA)
130
130
130
130
130
130
130
130
130
130
130
130
130
130
Type de coordination: 2
Coordination type: 2
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV2-P03
0,25...0,40
GV2-P05
0,63...1
GV2-P05
0,63...1
GV2-P06
1...1,6
GV2-P06
1...1,6
GV2-P07
1,6...2,5
GV2-P08
2,5...4
GV2-P08
2,5...4
GV2-P10
4...6,3
GV2-P14
6...10
GV2-P14
6...10
GV2-P16
9...14
GV2-P20
13...18
GV2-P22
20...25
DOL (Démarrage direct)
DOL (Direct On Line)
Nb modules
Nbr of modules
Contacteur
Contactor
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D18
LC1-D18
LC1-D18
LC1-D25
Mf
Mw
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Ancienne gamme
Old range
GV2-P
380 / 415V
Puissance moteur
Power motor
P (kW)
I (A)
Type de coordination: 2
Coordination type: 2
0,06
0,22
0,09
0,36
0,12
0,42
0,18
0,6
0,25
0,88
0,37
0,98
Pdc
BC
Icu (kA)
Rms (kA)
130
130
130
130
130
130
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV2-P02
0,16... 0,25
GV2-P03
0,25...0,40
GV2-P04
0,40... 0,63
GV2-P04
0,40... 0,63
GV2-P05
0,63...1
GV2-P05
0,63...1
Contacteur
Contactor
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
0,55
1,5
130
GV2-P06
1...1,6
LC1-D09
3
3
0,75
2
130
GV2-P07
1,6...2,5
LC1-D09
3
3
1,1
2,5
130
GV2-P07
1,6...2,5
LC1-D09
3
3
1,5
3,5
130
GV2-P08
2,5...4
LC1-D18
3
3
2,2
5
130
GV2-P10
4...6,3
LC1-D18
3
3
3
6,5
130
GV2-P14
6...10
LC1-D18
3
3
4
8,4
130
GV2-P14
6...10
LC1-D18
3
3
5,5
11
130
GV2-P16
9...14
LC1-D25
3
3
7,5
14,8
50
GV2-P20
13...18
LC1-D25
3
3
9
18,1
50
GV2-P21
17...23
LC1-D25
3
3
11
21
50
GV2-P22
20...25
LC1-D25
3
3
DOL (Démarrage direct)
DOL (Direct On Line)
Nb modules
Nbr of modules
Mf
Mw
3
3
3
3
3
3
3
3
3
3
3
3
Ancienne gamme
Old range
Guide Technique V9 / V9 Technical Guide
273
Anex 01
Appendix 01
GV2-P
440 V
Puissance moteur
Power motor
P (kW)
I (A)
0,06
0,19
0,09
0,28
0,12
0,37
0,18
0,55
0,25
0,76
0,37
0,99
0,55
1,36
0,75
1,68
1,1
2,37
1,5
3,06
2,2
4,42
3
5,77
4
7,9
5,5
10,4
7,5
13,7
9
16,9
11
20,1
Pdc
BC
Icu (kA)
Rms (kA)
130
130
130
130
130
130
130
130
130
130
130
130
130
50
50
20
20
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV2-P02
0,16... 0,25
GV2-P03
0,25...0,40
GV2-P03
0,25...0,40
GV2-P04
0,40... 0,63
GV2-P05
0,63...1
GV2-P05
0,63...1
GV2-P06
1...1,6
GV2-P07
1,6...2,5
GV2-P07
1,6...2,5
GV2-P08
2,5
GV2-P10
4...6,3
GV2-P10
4...6,3
GV2-P14
6...10
GV2-P16
9...14
GV2-P16
9...14
GV2-P20
13...18
GV2-P21
17...23
Type de coordination: 2
Coordination type: 2
DOL (Démarrage direct)
DOL (Direct On Line)
Nb modules
Nbr of modules
Contacteur
Contactor
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D18
LC1-D18
LC1-D18
LC1-D18
LC1-D25
LC1-D25
LC1-D25
LC1-D25
Mf
Mw
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Ancienne gamme
Old range
Guide Technique V9 / V9 Technical Guide
274
Anex 01
Appendix 01
6.1.1.3.
GV2-P
Type de coordination: 1 - - - - - - - - - - - - - - - -2 sens de Marche
Coordination type: 1 - - - - - - - - - - - - - - - - - - -Reverse
GV2-P
220/240 V
Puissance Moteur
Power motor
P (kW)
I (A)
0,06
0,38
0,09
0,65
0,12
0,75
0,18
1,04
0,25
1,47
0,37
2
0,55
2,8
0,75
3,6
1,1
5,2
1,5
6,8
2,2
9,6
3
11,5
4
14,5
5,5
22
Pdc
BC
Icu (kA)
Rms (kA)
85
85
85
85
85
85
85
85
85
85
85
85
85
85
Type de coordination: 1
Coordination type: 1
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV2-P03
0,25...0,40
GV2-P05
0,63...1
GV2-P05
0,63...1
GV2-P06
1...1,6
GV2-P06
1...1,6
GV2-P07
1,6...2,5
GV2-P08
2,5...4
GV2-P08
2,5...4
GV2-P10
4...6,3
GV2-P14
6...10
GV2-P16
9...14
GV2-P16
9...14
GV2-P20
13...18
GV2-P22
20...25
2 sens de Marche
Reverse
Nb modules
Nbr of modules
Contacteur
Contactor
2 x LC1-K06
2 x LC1-K06
2 x LC1-K06
2 x LC1-K06
2 x LC1-K06
2 x LC1-K06
2 x LC1-K06
2 x LC1-K06
2 x LC1-K06
2 x LC1-K09
2 x LC1-D12
2 x LC1-D12
2 x LC1-D18
2 x LC1-D25
Mf
Mw
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
6
3
Ancienne gamme
Old range
GV2-P
380/415 V
Puissance Moteur
Power motor
P (kW)
I (A)
Pdc
BC
Icu (kA)
Rms (kA)
85
85
85
85
85
85
Type de coordination: 1
Coordination type: 1
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV2-P02
0,16... 0,25
GV2-P03
0,25...0,40
GV2-P04
0,40... 0,63
GV2-P04
0,40... 0,63
GV2-P05
0,63...1
GV2-P06
1...1,6
2 sens de Marche
Reverse
Nb modules
Nbr of modules
Contacteur
Contactor
2 x LC1-K06
2 x LC1-K06
2 x LC1-K06
2 x LC1-K06
2 x LC1-K06
2 x LC1-K06
Mf
Mw
0,06
0,22
0,09
0,36
3
3
3
3
0,12
0,42
0,18
0,6
3
3
3
0,25
0,88
3
0,37
0,98
0,55
1,5
85
GV2-P06
1...1,6
2 x LC1-K06
3
3
0,75
2
85
GV2-P07
1,6...2,5
2 x LC1-K06
3
3
1,1
2,5
85
GV2-P08
2,5...4
2 x LC1-K06
3
3
1,5
3,5
85
GV2-P08
2,5...4
2 x LC1-K06
3
3
2,2
5
85
GV2-P10
4...6,3
2 x LC1-K06
3
3
3
6,5
85
GV2-P14
6...10
2 x LC1-K09
3
3
4
8,4
85
GV2-P14
6...10
2 x LC1-K09
3
3
5,5
11
85
GV2-P16
9...14
2 x LC1-D12
3
3
3
3
3
3
7,5
14,8
50
GV2-P20
13...18
2 x LC1-D18
3
3
9
18,1
50
GV2-P21
17...23
2 x LC1-D25
6
3
11
21
50
GV2-P22
20...25
2 x LC1-D25
6
3
Ancienne gamme
Old range
Guide Technique V9 / V9 Technical Guide
275
Anex 01
Appendix 01
GV2-P
440 V
Puissance Moteur
Power motor
P (kW)
I (A)
0,06
0,19
0,09
0,28
0,12
0,37
0,18
0,55
0,25
0,76
0,37
0,99
0,55
1,36
0,75
1,68
1,1
2,37
1,5
3,06
2,2
4,42
3
5,77
4
7,9
5,5
10,4
7,5
13,7
9
16,9
11
20,1
Pdc
BC
Icu (kA)
Rms (kA)
85
85
85
85
85
85
85
85
85
85
85
85
85
50
20
20
20
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV2-P02
0,16... 0,25
GV2-P03
0,25...0,40
GV2-P03
0,25...0,40
GV2-P04
0,40... 0,63
GV2-P05
0,63...1
GV2-P05
0,63...1
GV2-P06
1...1,6
GV2-P07
1,6...2,5
GV2-P07
1,6...2,5
GV2-P08
2,5...4
GV2-P10
4...6,3
GV2-P10
4...6,3
GV2-P14
6...10
GV2-P16
9...14
GV2-P20
13...18
GV2-P20
13...18
GV2-P21
17...23
Type de coordination: 1
Coordination type: 1
2 sens de Marche
Reverse
Nb modules
Nbr of modules
Contacteur
Contactor
2 x LC1-K06
2 x LC1-K06
2 x LC1-K06
2 x LC1-K06
2 x LC1-K06
2 x LC1-K06
2 x LC1-K06
2 x LC1-K06
2 x LC1-K06
2 x LC1-K06
2 x LC1-K06
2 x LC1-K06
2 x LC1-K09
2 x LC1-D12
2 x LC1-D18
2 x LC1-D18
2 x LC1-D25
Mf
Mw
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
6
3
Ancienne gamme
Old range
Guide Technique V9 / V9 Technical Guide
276
Anex 01
Appendix 01
6.1.1.4.
GV2-P
Type de coordination: 2 - - - - - - - - - - - - - - - -2 sens de Marche
Coordination type: 2 - - - - - - - - - - - - - - - - - - -Reverse
GV2-P
220/240 V
Puissance Moteur
Power motor
P (kW)
I (A)
0,06
0,38
0,09
0,65
0,12
0,75
0,18
1,04
0,25
1,47
0,37
2
0,55
2,8
0,75
3,6
1,1
5,2
1,5
6,8
2,2
9,6
3
11,5
4
14,5
5,5
22
Pdc
BC
Icu (kA)
Rms (kA)
85
85
85
85
85
85
85
85
85
85
85
85
85
85
Type de coordination: 2
Coordination type: 2
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV2-P03
0,25...0,40
GV2-P05
0,63...1
GV2-P05
0,63...1
GV2-P06
1...1,6
GV2-P06
1...1,6
GV2-P07
1,6...2,5
GV2-P08
2,5...4
GV2-P08
2,5...4
GV2-P10
4...6,3
GV2-P14
6...10
GV2-P14
6...10
GV2-P16
9...14
GV2-P20
13...18
GV2-P22
20...25
2 sens de Marche
Reverse
Nb modules
Nbr of modules
Contacteur
Contactor
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D18
2 x LC1-D18
2 x LC1-D18
2 x LC1-D25
Mf
Mw
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
6
3
Ancienne gamme
Old range
GV2-P
380/415 V
Puissance Moteur
Power motor
P (kW)
I (A)
Type de coordination: 2
Coordination type: 2
0,06
0,22
0,09
0,36
0,12
0,42
0,18
0,6
0,25
0,88
0,37
0,98
Pdc
BC
Icu (kA)
Rms (kA)
85
85
85
85
85
85
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV2-P02
0,16... 0,25
GV2-P03
0,25...0,40
GV2-P04
0,40... 0,63
GV2-P04
0,40... 0,63
GV2-P05
0,63...1
GV2-P05
0,63...1
Contacteur
Contactor
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
Mf
Mw
3
3
3
3
3
3
3
3
3
3
3
0,55
1,5
85
GV2-P06
1...1,6
2 x LC1-D09
3
3
3
0,75
2
85
GV2-P07
1,6...2,5
2 x LC1-D09
3
3
1,1
2,5
85
GV2-P07
1,6...2,5
2 x LC1-D09
3
3
1,5
3,5
85
GV2-P08
2,5...4
2 x LC1-D18
3
3
2,2
5
85
GV2-P10
4...6,3
2 x LC1-D18
3
3
3
6,5
85
GV2-P14
6...10
2 x LC1-D18
3
3
4
8,4
85
GV2-P14
6...10
2 x LC1-D18
3
3
5,5
11
85
GV2-P16
9...14
2 x LC1-D25
6
3
7,5
14,8
50
GV2-P20
13...18
2 x LC1-D25
6
3
9
18,1
50
GV2-P21
17...23
2 x LC1-D25
6
3
11
21
50
GV2-P22
20...25
2 x LC1-D25
6
3
2 sens de Marche
Reverse
Nb modules
Nbr of modules
Ancienne gamme
Old range
Guide Technique V9 / V9 Technical Guide
277
Anex 01
Appendix 01
GV2-P
440 V
Puissance Moteur
Power motor
P (kW)
I (A)
0,06
0,19
0,09
0,28
0,12
0,37
0,18
0,55
0,25
0,76
0,37
0,99
0,55
1,36
0,75
1,68
1,1
2,37
1,5
3,06
2,2
4,42
3
5,77
4
7,9
5,5
10,4
7,5
13,7
9
16,9
11
20,1
Pdc
BC
Icu (kA)
Rms (kA)
85
85
85
85
85
85
85
85
85
85
85
85
85
50
50
20
20
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV2-P02
0,16... 0,25
GV2-P03
0,25...0,40
GV2-P03
0,25...0,40
GV2-P04
0,40... 0,63
GV2-P05
0,63...1
GV2-P05
0,63...1
GV2-P06
1...1,6
GV2-P07
1,6...2,5
GV2-P07
1,6...2,5
GV2-P08
2,5...4
GV2-P10
4...6,3
GV2-P10
4...6,3
GV2-P14
6...10
GV2-P16
9...14
GV2-P16
9...14
GV2-P20
13...18
GV2-P21
17...23
Type de coordination: 2
Coordination type: 2
2 sens de Marche
Reverse
Nb modules
Nbr of modules
Contacteur
Contactor
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D18
2 x LC1-D18
2 x LC1-D18
2 x LC1-D25
2 x LC1-D25
2 x LC1-D25
2 x LC1-D25
Mf
Mw
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
6
3
6
3
6
3
6
3
Ancienne gamme
Old range
Guide Technique V9 / V9 Technical Guide
278
Anex 01
Appendix 01
6.1.1.5.
GV2-P
Type de coordination: 1 - - - - - - - - - - - - - - - -Etoile / Triangle (Y/∆)
Coordination type: 1 - - - - - - - - - - - - - - - - - - -STAR / DELTA (Y/∆)
GV2-P
220/240 V
Puissance Moteur
Power motor
P (kW)
I (A)
1,5
6,8
2,2
9,6
3
11,5
4
14,5
5,5
22
Pdc
BC
Icu (kA)
Rms (kA)
85
85
85
85
85
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV2-P14
6...10
GV2-P16
9...14
GV2-P16
9...14
GV2-P20
13...18
GV2-P22
20...25
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Type de coordination: 1
Coordination type: 1
Nb modules
Nbr of modules
Contacteur
Contactor
3 x LC1-K06
3 x LC1-K06
3 x LC1-K06
3 x LC1-D09
3 x LC1-D12
Mf
Mw
6
6
6
6
6
6
6
6
6
6
Ancienne gamme
Old range
GV2-P
380/415 V
Puissance Moteur
Power motor
P (kW)
I (A)
1,5
3,5
2,2
5
3
6,5
4
8,4
5,5
11
7,5
14,8
9
18,1
11
21
Pdc
BC
Icu (kA)
Rms (kA)
85
85
85
85
85
50
50
50
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV2-P08
2,5...4
GV2-P10
4...6,3
GV2-P14
6...10
GV2-P14
6...10
GV2-P16
9...14
GV2-P20
13...18
GV2-P21
17...23
GV2-P22
20...25
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Type de coordination: 1
Coordination type: 1
Nb modules
Nbr of modules
Contacteur
Contactor
3 x LC1-K06
3 x LC1-K06
3 x LC1-K06
3 x LC1-K06
3 x LC1-K06
3 x LC1-D09
3 x LC1-D12
3 x LC1-D12
Mf
Mw
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
Ancienne gamme
Old range
GV2-P
440 V
Puissance Moteur
Power motor
P (kW)
I (A)
1,5
3,06
2,2
4,42
3
5,77
4
7,9
5,5
10,4
7,5
13,7
9
16,9
11
20,1
Pdc
BC
Icu (kA)
Rms (kA)
85
85
85
85
50
20
20
20
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV2-P08
2,5...4
GV2-P10
4...6,3
GV2-P10
4...6,3
GV2-P14
6...10
GV2-P16
9...14
GV2-P20
13...18
GV2-P20
13...18
GV2-P21
17...23
Type de coordination: 1
Coordination type: 1
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Nb modules
Nbr of modules
Contacteur
Contactor
3 x LC1-K06
3 x LC1-K06
3 x LC1-K06
3 x LC1-K06
3 x LC1-K06
3 x LC1-D09
3 x LC1-D12
3 x LC1-D12
Mf
Mw
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
Ancienne gamme
Old range
Guide Technique V9 / V9 Technical Guide
279
Anex 01
Appendix 01
6.1.1.6.
GV2-P
Type de coordination: 2 - - - - - - - - - - - - - - - -Etoile / Triangle (Y/∆)
Coordination type: 2 - - - - - - - - - - - - - - - - - - -STAR / DELTA (Y/∆)
GV2-P
220/240 V
Puissance Moteur
Power motor
P (kW)
I (A)
1,5
6,8
2,2
9,6
3
11,5
4
14,5
5,5
22
Pdc
BC
Icu (kA)
Rms (kA)
85
85
85
85
85
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV2-P14
6...10
GV2-P14
6...10
GV2-P16
9...14
GV2-P20
13...18
GV2-P22
20...25
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Type de coordination: 2
Coordination type: 2
Nb modules
Nbr of modules
Contacteur
Contactor
3 x LC1-D09
3 x LC1-D18
3 x LC1-D18
3 x LC1-D18
3 x LC1-D25
Mf
Mw
6
6
6
6
6
6
6
6
6
6
Ancienne gamme
Old range
GV2-P
380/415 V
Puissance Moteur
Power motor
P (kW)
I (A)
1,5
3,5
2,2
5
3
6,5
4
8,4
5,5
11
7,5
14,8
9
18,1
11
21
Pdc
BC
Icu (kA)
Rms (kA)
85
85
85
85
85
50
50
50
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV2-P08
2,5...4
GV2-P10
4...6,3
GV2-P14
6...10
GV2-P14
6...10
GV2-P16
9...14
GV2-P20
13...18
GV2-P21
17...23
GV2-P22
20...25
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Type de coordination: 2
Coordination type: 2
Nb modules
Nbr of modules
Contacteur
Contactor
3 x LC1-D09
3 x LC1-D18
3 x LC1-D18
3 x LC1-D18
3 x LC1-D25
3 x LC1-D25
3 x LC1-D25
3 x LC1-D25
Mf
Mw
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
Ancienne gamme
Old range
GV2-P
440 V
Puissance Moteur
Power motor
P (kW)
I (A)
1,5
3,06
2,2
4,42
3
5,77
4
7,9
5,5
10,4
7,5
13,7
9
16,9
11
20,1
Pdc
BC
Icu (kA)
Rms (kA)
85
85
85
85
50
50
20
20
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV2-P08
2,5...4
GV2-P10
4...6,3
GV2-P10
4...6,3
GV2-P14
6...10
GV2-P16
9...14
GV2-P16
9...14
GV2-P20
13...18
GV2-P21
17...23
Type de coordination: 2
Coordination type: 2
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Nb modules
Nbr of modules
Contacteur
Contactor
3 x LC1-D09
3 x LC1-D18
3 x LC1-D18
3 x LC1-D18
3 x LC1-D25
3 x LC1-D25
3 x LC1-D25
3 x LC1-D25
Mf
Mw
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
Ancienne gamme
Old range
Guide Technique V9 / V9 Technical Guide
280
Anex 01
Appendix 01
Compact NS80H-MA
6.1.1.7.
Type de coordination: 1 - - - - - - - - - - - - - - - -DOL (Démarrage direct)
Coordination type: 1 - - - - - - - - - - - - - - - - - - -DOL (Direct On Line)
Démarrage: Normal
Start-up: Normal
Compact NS80H-MA
220/230 V
Puissance Moteur
Power motor
P (kW)
I (A)
0,37
1,8
0,55
2,8
1,1
4,4
1,5
6,1
2,2
8,7
3
11,5
4
14,5
5,5
20
7,5
28
11
39
15
52
18,5
64
22
75
Pdc
BC
Icu (kA)
Rms (kA)
100
100
100
100
100
100
100
100
100
100
100
100
100
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
Cal (A)
Rat (A)
2,5
6,3
6,3
12,5
12,5
12,5
25
25
50
50
50
80
80
Type de coordination: 1
Coordination type: 1
Contacteurs
Contactor
Type
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D12
LC1-D18
LC1-D25
LC1-D32
LC1-D40
LC1-D50
LC1-D65
LC1-D80
DOL (Démarrage direct)
DOL (Direct On Line)
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D1322
17...25
LR2-D3353
23...32
LR2-D3357
37...50
LR2-D3359
48...65
LR2-D3359
48...65
LR2-D3363
63...80
Nb modules
Nbr of modules
Mf
Mw
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
6
3
6
3
6
3
6
3
6
Ancienne gamme
Old range
Compact NS80H-MA
380 V
Puissance Moteur
Power motor
P (kW)
I (A)
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
Type de coordination: 1
Coordination type: 1
DOL (Démarrage direct)
DOL (Direct On Line)
0,37
1,2
0,55
1,6
0,75
2
Pdc
BC
Icu (kA)
Rms (kA)
70
70
70
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1306
1...1,6
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
Nb modules
Nbr of modules
Cal (A)
Rat (A)
2,5
2,5
2,5
Contacteurs
Contactor
Type
Type
LC1-D09
LC1-D09
LC1-D09
3
1,1
2,8
70
NS80H-MA
6,3
LC1-D09
LR2-D1308
2,5...4
3
3
3
1,5
3,7
70
NS80H-MA
6,3
LC1-D09
LR2-D1308
2,5...4
3
3
2,2
5
70
NS80H-MA
6,3
LC1-D09
LR2-D1310
4...6
3
3
3
6,6
70
NS80H-MA
12,5
LC1-D09
LR2-D1312
5,5...8
3
3
4
8,5
70
NS80H-MA
12,5
LC1-D09
LR2-D1314
7...10
3
3
5,5
11,5
70
NS80H-MA
12,5
LC1-D12
LR2-D1316
9...13
3
3
7,5
15,5
70
NS80H-MA
25
LC1-D18
LR2-D1321
12...18
3
3
11
22
70
NS80H-MA
25
LC1-D25
LR2-D1322
17...25
3
3
15
30
70
NS80H-MA
50
LC1-D32
LR2-D3353
23...32
3
6
18,5
37
70
NS80H-MA
50
LC1-D40
LR2-D3357
37...50
3
6
22
44
70
NS80H-MA
50
LC1-D50
LR2-D3357
37...50
3
6
30
59
70
NS80H-MA
80
LC1-D65
LR2-D3359
48...65
3
6
37
72
70
NS80H-MA
80
LC1-D80
LR2-D3363
63...80
3
6
Mf
Mw
3
3
3
3
Ancienne gamme
Old range
Guide Technique V9 / V9 Technical Guide
281
Anex 01
Appendix 01
Compact NS80H-MA
400/415 V
Puissance Moteur
Power motor
P (kW)
I (A)
0,37
1,1
0,55
1,5
0,75
1,8
1,1
2,5
1,5
3,5
2,2
4,8
3
6,5
4
8,2
5,5
11
7,5
14
9
17
11
21
15
28
22
40
25
47
30
55
37
66
45
80
Pdc
BC
Icu (kA)
Rms (kA)
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
Cal (A)
Rat (A)
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
12,5
25
25
25
50
50
50
80
80
80
Type de coordination: 1
Coordination type: 1
Contacteurs
Contactor
Type
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D12
LC1-D18
LC1-D18
LC1-D25
LC1-D32
LC1-D40
LC1-D50
LC1-D65
LC1-D65
LC1-D80
DOL (Démarrage direct)
DOL (Direct On Line)
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1306
1...1,6
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D1321
12...18
LR2-D1322
17...25
LR2-D3353
23...32
LR2-D3357
37...50
LR2-D3357
37...50
LR2-D3359
48...65
LR2-D3361
55...70
LR2-D3363
63...80
Nb modules
Nbr of modules
Mf
Mw
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
6
3
6
3
6
3
6
3
6
3
6
Ancienne gamme
Old range
440 V (1)
Puissance Moteur
Power motor
P (kW)
I (A)
0,37
1
0,55
1,4
0,75
1,7
1,1
2,4
1,5
3,1
2,2
4,5
3
5,8
4
7,9
5,5
10,4
7,5
13,7
9
16,9
11
20,1
15
26,5
22
39
30
51,5
37
64
45
76
Compact NS80H-MA
Pdc
BC
Icu (kA)
Rms (kA)
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
Cal (A)
Rat (A)
2,5
2,5
2,5
2,5
6,3
6,3
12,5
12,5
12,5
25
25
25
50
50
50
80
80
Type de coordination: 1
Coordination type: 1
Contacteurs
Contactor
Type
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D12
LC1-D18
LC1-D18
LC1-D25
LC1-D32
LC1-D40
LC1-D50
LC1-D65
LC1-D80
Ancienne gamme
Old range
(1) Applicable pour 480 V NEMA
Guide Technique V9 / V9 Technical Guide
DOL (Démarrage direct)
DOL (Direct On Line)
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1306
1...1,6
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D1321
12...18
LR2-D1322
17...25
LR2-D3353
23...32
LR2-D3357
37...50
LR2-D3359
48...65
LR2-D3359
48...65
LR2-D3363
63...80
Nb modules
Nbr of modules
Mf
Mw
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
6
3
6
3
6
3
6
3
6
(1) Valid for 480 V NEMA
282
Anex 01
Appendix 01
Compact NS80H-MA
500/525 V
Puissance Moteur
Power motor
P (kW)
I (A)
0,55
1,2
0,75
1,5
1,1
2
1,5
2,6
3
5
4
6,5
5,5
9
7,5
12
9
14
10
15
11
18,4
18,5
28,5
22
33
30
45
37
55
55
80
Pdc
BC
Icu (kA)
Rms (kA)
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
Cal (A)
Rat (A)
2,5
2,5
2,5
6,3
6,3
12,5
12,5
12,5
25
25
25
50
50
50
80
80
Type de coordination: 1
Coordination type: 1
Contacteurs
Contactor
Type
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D12
LC1-D18
LC1-D18
LC1-D25
LC1-D32
LC1-D40
LC1-D50
LC1-D65
LC1-D80
DOL (Démarrage direct)
DOL (Direct On Line)
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1306
1...1,6
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D1321
12...18
LR2-D1322
17...25
LR2-D3353
23...32
LR2-D355
30...40
LR2-D3357
37...50
LR2-D3359
48...65
LR2-D3363
63...80
Nb modules
Nbr of modules
Mf
Mw
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
6
3
6
3
6
3
6
3
6
Ancienne gamme
Old range
Guide Technique V9 / V9 Technical Guide
283
Anex 01
Appendix 01
Compact NS80H-MA
6.1.1.8.
Type de coordination: 2 - - - - - - - - - - - - - - - -DOL (Démarrage direct)
Coordination type: 2 - - - - - - - - - - - - - - - - - - -DOL (Direct On Line)
Démarrage: Normal
Start-up: Normal
Compact NS80H-MA
220/230 V
Puissance Moteur
Power motor
P (kW)
I (A)
0,09
0,7
0,12
0,9
0,18
1,2
0,25
1,5
0,37
2
0,55
2,8
0,75
3,5
1,1
5
1,5
6,5
2,2
9
3
12
4
15
5,5
21
6,3
24
7,5
28
-
-
10
36
-
-
11
39
-
-
15
52
-
-
18.5
63
-
-
22
75
-
-
Pdc
BC
Icu (kA)
Rms (kA)
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
-
Cal (A)
Rat (A)
1,5
1,5
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
12,5
25
25
25
50
50
50
80
80
80
-
Type de coordination: 2
Coordination type: 2
Contacteurs
Contactor
Type
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D18
LC1-D18
LC1-D25
LC1-D32
LC1-D32
LC1-D32
LC1-D32
LC1-D40
LC1-D40
LC1-D40
LC1 D80
LC1-D50
LC1 D80
LC1-D50
LC1 D80
LC1-D65
LC1 D80
LC1-D65
LC1 D80
LC1-D80
LC1 D80
DOL (Démarrage direct)
DOL (Direct On Line)
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1305
0,63...1
LR2-D1305
0,63...1
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D3322
17...25
LR2-D3322
17...25
LR2-D3353
23...32
LR9-D5357
30...50
LR2-D3355
30...40
LR9-D5357
30...50
LR2-D3357
37...50
LR9-D5357
30...50
LR2-D3359
48...65
LR9-D5363
48...80
LR2-D3359
48...65
LR9-D5363
48...80
LR2-D3363
63...80
LR9-D5363
48...80
Nb modules
Nbr of modules
Mf
Mw
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
6
3
6
3
6
3
9
3
6
3
9
3
6
3
9
3
6
3
9
3
6
3
9
3
6
3
9
Ancienne gamme
Old range
Guide Technique V9 / V9 Technical Guide
284
Anex 01
Appendix 01
Compact NS80H-MA
380/415 V
Puissance Moteur
Power motor
P (kW)
I (A)
0,18
0,7
0,25
0,9
0,37
1,2
0,55
1,6
0,75
2
1,1
2,8
1,5
3,7
2,2
5,3
3
7
4
9
5,5
12
7,5
16
10
21
11
23
15
30
-
-
18,5
37
-
-
22
43
-
-
30
59
-
-
37
72
-
-
Pdc
BC
Icu (kA)
Rms (kA)
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
-
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
-
Cal (A)
Rat (A)
1,5
1,5
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
12,5
25
25
25
50
50
50
80
80
-
Type de coordination: 2
Coordination type: 2
Contacteurs
Contactor
Type
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D18
LC1-D18
LC1-D25
LC1-D32
LC1-D32
LC1-D32
LC1-D32
LC1-D40
LC1-D40
LC1-D40
LC1 D80
LC1-D50
LC1 D80
LC1-D50
LC1 D80
LC1-D65
LC1 D80
LC1 D80
LC1 D80
DOL (Démarrage direct)
DOL (Direct On Line)
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1305
0,63...1
LR2-D1305
0,63...1
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D3322
17...25
LR2-D3322
17...25
LR2-D3353
23...32
LR9-D5357
30...50
LR2-D3355
30...40
LR9-D5357
30...50
LR2-D3357
37...50
LR9-D5357
30...50
LR2-D3359
48...65
LR9-D5363
48...80
LR2-D3363
63...80
LR9-D5363
48...80
Nb modules
Nbr of modules
Mf
Mw
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
6
3
6
3
6
3
9
3
6
3
9
3
6
3
9
3
6
3
9
3
6
3
9
Ancienne gamme
Old range
Guide Technique V9 / V9 Technical Guide
285
Anex 01
Appendix 01
440 V (1)
Puissance Moteur
Power motor
P (kW)
I (A)
0,25
0,7
0,37
1
0,55
1,4
0,75
1,7
1,1
2,4
1,5
3,1
2,2
4,5
3
5,8
4
8
5,5
10,5
7,5
13,7
10
19
11
20
15
26,5
18,5
33
-
-
22
39
-
-
30
52
-
-
37
63
-
-
45
76
-
-
Compact NS80H-MA
Pdc
BC
Icu (kA)
Rms (kA)
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
-
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
-
Cal (A)
Rat (A)
1,5
2,5
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
25
25
25
50
50
50
80
80
80
-
Type de coordination: 2
Coordination type: 2
Contacteurs
Contactor
Type
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D18
LC1-D25
LC1-D25
LC1-D32
LC1-D32
LC1-D32
LC1-D40
LC1-D40
LC1-D40
LC1-D50
LC1 D80
LC1-D50
LC1 D80
LC1-D65
LC1 D80
LC1-D65
LC1 D80
LC1-D80
LC1 D80
DOL (Démarrage direct)
DOL (Direct On Line)
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1305
0,63...1
LR2-D1306
1...1,6
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D3322
17...25
LR2-D3322
17...25
LR2-D3353
23...32
LR2-D3355
30...40
LR9-D5357
30...50
LR2-D3355
30...40
LR9-D5357
30...50
LR2-D3359
48...65
LR9-D5363
48...80
LR2-D3359
48...65
LR9-D5363
48...80
LR2-D3363
63...80
LR9-D5363
48...80
Nb modules
Nbr of modules
Mf
Mw
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
6
3
6
3
6
3
6
3
9
3
6
3
9
3
6
3
9
3
6
3
9
3
6
3
9
Ancienne gamme
Old range
(1) Applicable pour 480 V NEMA
(1) Valid for 480 V NEMA
500/525 V
Puissance Moteur
Power motor
P (kW)
I (A)
0,25
0,6
0,37
0,9
0,55
1,2
0,75
1,5
1,1
2,0
1,5
2,8
2,2
3,8
3
5
4
6,5
5,5
9
7,5
12
10
15
11
18,4
15
23
18,5
28,5
22
33
-
-
Compact NS80H-MA
Pdc
BC
Icu (kA)
Rms (kA)
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
-
Guide Technique V9 / V9 Technical Guide
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
-
Cal (A)
Rat (A)
1,5
1,5
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
12,5
25
25
25
50
50
-
Type de coordination: 2
Coordination type: 2
Contacteurs
Contactor
Type
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D18
LC1-D18
LC1-D25
LC1-D32
LC1-D32
LC1-D32
LC1-D32
LC1-D40
LC1-D40
LC1-D40
LC1-D50
LC1-D115
DOL (Démarrage direct)
DOL (Direct On Line)
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1305
0,63...1
LR2-D1305
0,63...1
LR2-D1306
1...1,6
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D3321
12...18
LR2-D3322
17...25
LR2-D3322
17...25
LR2-D3353
23...32
LR2-D3355
30...40
LR9-D5357
30...50
Nb modules
Nbr of modules
Mf
Mw
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
6
3
6
3
6
3
6
6
9
286
Anex 01
Appendix 01
Compact NS80H-MA
500/525 V
Puissance Moteur
Power motor
P (kW)
I (A)
-
-
30
45
-
-
-
-
37
55
-
-
-
-
45
65
-
-
55
75
-
-
Pdc
BC
Icu (kA)
Rms (kA)
25
25
25
25
-
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
-
Cal (A)
Rat (A)
50
80
80
80
-
Type de coordination: 2
Coordination type: 2
Contacteurs
Contactor
Type
Type
LC1-F115
LC1-D50
LC1-D115
LC1-F115
LC1-D65
LC1-D115
LC1-F115
LC1-D115
LC1-F115
LC1-D115
LC1-F115
DOL (Démarrage direct)
DOL (Direct On Line)
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR9-F5357
30...50
LR2-D3357
37...50
LR9-D5357
30...50
LR9-F5357
30...50
LR2-D3359
48...65
LR9-D5363
48...80
LR9-F5363
48...80
LR9-D3363
63...80
LR9-D5363
48...80
LR9-F5363
48...80
LR9-D5363
48...80
Nb modules
Nbr of modules
Mf
Mw
6
9
3
6
6
9
6
9
3
6
6
9
6
9
6
9
6
9
6
9
6
9
Ancienne gamme
Old range
Guide Technique V9 / V9 Technical Guide
287
Anex 01
Appendix 01
Compact NS80H-MA
6.1.1.9.
Type de coordination: 1 - - - - - - - - - - - - - - - -2 sens de marche
Coordination type: 1 - - - - - - - - - - - - - - - - - - -Reverse
Démarrage: Normal
Start-up: Normal
Compact NS80H-MA
220/230 V
Puissance Moteur
Power motor
P (kW)
I (A)
0,37
1,8
0,55
2,8
1,1
4,4
1,5
6,1
2,2
8,7
3
11,5
4
14,5
5,5
20
7,5
28
11
39
15
52
18,5
64
22
75
Pdc
BC
Icu (kA)
Rms (kA)
100
100
100
100
100
100
100
100
100
100
100
100
100
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
Cal (A)
Rat (A)
2,5
6,3
6,3
12,5
12,5
12,5
25
25
50
50
50
80
80
Type de coordination: 1
Coordination type: 1
Contacteurs
Contactor
Type
Type
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D12
2 x LC1-D18
2 x LC1-D25
2 x LC1-D32
2 x LC1-D40
2 x LC1-D50
2 x LC1-D65
2 x LC1-D80
2 sens de marche
Reverse
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D1322
17...25
LR2-D3353
23...32
LR2-D3357
37...50
LR2-D3359
48...65
LR2-D3359
48...65
LR2-D3363
63...80
Nb modules
Nbr of modules
Mf
Mw
3
6
3
6
3
6
3
6
3
6
3
6
3
6
6
6
6
6
6
9
6
9
6
9
6
9
Ancienne gamme
Old range
Compact NS80H-MA
380 V
Puissance Moteur
Power motor
P (kW)
I (A)
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
Type de coordination: 1
Coordination type: 1
2 sens de marche
Reverse
0,37
1,2
0,55
1,6
0,75
2
Pdc
BC
Icu (kA)
Rms (kA)
70
70
70
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1306
1...1,6
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
Nb modules
Nbr of modules
Cal (A)
Rat (A)
2,5
2,5
2,5
Contacteurs
Contactor
Type
Type
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
3
1,1
2,8
70
NS80H-MA
6,3
2 x LC1-D09
LR2-D1308
2,5...4
3
6
6
1,5
3,7
70
NS80H-MA
6,3
2 x LC1-D09
LR2-D1308
2,5...4
3
6
2,2
5
70
NS80H-MA
6,3
2 x LC1-D09
LR2-D1310
4...6
3
6
3
6,6
70
NS80H-MA
12,5
2 x LC1-D09
LR2-D1312
5,5...8
3
6
4
8,5
70
NS80H-MA
12,5
2 x LC1-D09
LR2-D1314
7...10
3
6
5,5
11,5
70
NS80H-MA
12,5
2 x LC1-D12
LR2-D1316
9...13
3
6
7,5
15,5
70
NS80H-MA
25
2 x LC1-D18
LR2-D1321
12...18
3
6
11
22
70
NS80H-MA
25
2 x LC1-D25
LR2-D1322
17...25
6
6
15
30
70
NS80H-MA
50
2 x LC1-D32
LR2-D3353
23...32
6
6
18,5
37
70
NS80H-MA
50
2 x LC1-D40
LR2-D3357
37...50
6
9
22
44
70
NS80H-MA
50
2 x LC1-D50
LR2-D3357
37...50
6
9
30
59
70
NS80H-MA
80
2 x LC1-D65
LR2-D3359
48...65
6
9
37
72
70
NS80H-MA
80
2 x LC1-D80
LR2-D3363
63...80
6
9
Mf
Mw
3
6
3
6
Ancienne gamme
Old range
Guide Technique V9 / V9 Technical Guide
288
Anex 01
Appendix 01
Compact NS80H-MA
415 V
Puissance Moteur
Power motor
P (kW)
I (A)
0,37
1,1
0,55
1,5
0,75
1,8
1,1
2,5
1,5
3,5
2,2
4,8
3
6,5
4
8,2
5,5
11
7,5
14
9
17
11
21
15
28
22
40
25
47
30
55
37
66
45
80
Pdc
BC
Icu (kA)
Rms (kA)
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
Cal (A)
Rat (A)
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
12,5
25
25
25
50
50
50
80
80
80
Type de coordination: 1
Coordination type: 1
Contacteurs
Contactor
Type
Type
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D12
2 x LC1-D18
2 x LC1-D18
2 x LC1-D25
2 x LC1-D32
2 x LC1-D40
2 x LC1-D50
2 x LC1-D65
2 x LC1-D65
2 x LC1-D80
2 sens de marche
Reverse
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1306
1...1,6
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D1321
12...18
LR2-D1322
17...25
LR2-D3353
23...32
LR2-D3357
37...50
LR2-D3357
37...50
LR2-D3359
48...65
LR2-D3361
55...70
LR2-D3363
63...80
Nb modules
Nbr of modules
Mf
Mw
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
6
6
6
6
6
9
6
9
6
9
6
9
6
9
Ancienne gamme
Old range
440 V (1)
Puissance Moteur
Power motor
P (kW)
I (A)
0,37
1
0,55
1,4
0,75
1,7
1,1
2,4
1,5
3,1
2,2
4,5
3
5,8
4
7,9
5,5
10,4
7,5
13,7
9
16,9
11
20,1
15
26,5
22
39
30
51,5
37
64
45
76
Compact NS80H-MA
Pdc
BC
Icu (kA)
Rms (kA)
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
Cal (A)
Rat (A)
2,5
2,5
2,5
2,5
6,3
6,3
12,5
12,5
12,5
25
25
25
50
50
50
80
80
Type de coordination: 1
Coordination type: 1
Contacteurs
Contactor
Type
Type
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D12
2 x LC1-D18
2 x LC1-D18
2 x LC1-D25
2 x LC1-D32
2 x LC1-D40
2 x LC1-D50
2 x LC1-D65
2 x LC1-D80
Ancienne gamme
Old range
(1) Applicable pour 480 V NEMA
Guide Technique V9 / V9 Technical Guide
2 sens de marche
Reverse
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1306
1...1,6
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D1321
12...18
LR2-D1322
17...25
LR2-D3353
23...32
LR2-D3357
37...50
LR2-D3359
48...65
LR2-D3359
48...65
LR2-D3363
63...80
Nb modules
Nbr of modules
Mf
Mw
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
6
6
6
6
6
9
6
9
6
9
6
9
(1) Valid for 480 V NEMA
289
Anex 01
Appendix 01
Compact NS80H-MA
500/525 V
Puissance Moteur
Power motor
P (kW)
I (A)
0,55
1,2
0,75
1,5
1,1
2
1,5
2,6
3
5
4
6,5
5,5
9
7,5
12
9
14
10
15
11
18,4
18,5
28,5
22
33
30
45
37
55
55
80
Pdc
BC
Icu (kA)
Rms (kA)
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
Cal (A)
Rat (A)
2,5
2,5
2,5
6,3
6,3
12,5
12,5
12,5
25
25
25
50
50
50
80
80
Type de coordination: 1
Coordination type: 1
Contacteurs
Contactor
Type
Type
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D12
2 x LC1-D18
2 x LC1-D18
2 x LC1-D25
2 x LC1-D32
2 x LC1-D40
2 x LC1-D50
2 x LC1-D65
2 x LC1-D80
2 sens de marche
Reverse
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1306
1...1,6
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D1321
12...18
LR2-D1322
17...25
LR2-D3353
23...32
LR2-D3355
30...40
LR2-D3357
37...50
LR2-D3359
48...65
LR2-D3363
63...80
Nb modules
Nbr of modules
Mf
Mw
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
6
6
6
6
6
9
6
9
6
9
6
9
Ancienne gamme
Old range
660/690 V (1)
Puissance Moteur
Power motor
P (kW)
I (A)
0,75
1,2
1
1,5
1,5
2
2,2
2,8
3
3,8
4
4,9
5,5
6,6
7,5
8,9
10
11,5
15
17
18,5
21,3
30
34,6
33
39
37
42
45
49
55
60
75
80
Compact NS80H-MA
Pdc
BC
Icu (kA)
Rms (kA)
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
Cal (A)
Rat (A)
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
25
25
50
50
50
50
80
80
80
Type de coordination: 1
Coordination type: 1
Contacteurs
Contactor
Type
Type
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D12
2 x LC1-D18
2 x LC1-D25
2 x LC1-D32
2 x LC1-D40
2 x LC1-D50
2 x LC1-D65
2 x LC1-D80
2 x LC1-D115
2 x LC1-F115
Ancienne gamme
Old range
(1) Confirmer le nb de modules pour
660/690 V
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
2 sens de marche
Reverse
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1306
1...1,6
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D1322
17...25
LR2-D3355
30...40
LR2-D3357
37...50
LR2-D3357
37...50
LR2-D3357
37...50
LR9-D5363
48...80
LR9-F5363
48...80
Nb modules
Nbr of modules
Mf
Mw
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
6
6
6
6
6
9
6
9
6
9
6
9
9
12
9
**
(1) Confirm number of modules in function of
this voltage level 660/690 V
** Impossible in Mw type
290
Anex 01
Appendix 01
Compact NS80H-MA
6.1.1.10.
Type de coordination: 2 - - - - - - - - - - - - - - - -2 sens de marche
Coordination type: 2 - - - - - - - - - - - - - - - - - - -Reverse
Démarrage: Normal
Start-up: Normal
Compact NS80H-MA
220/230 V
Puissance Moteur
Power motor
P (kW)
I (A)
0,09
0,7
0,12
0,9
0,18
1,2
0,25
1,5
0,37
2
0,55
2,8
0,75
3,5
1,1
5
1,5
6,5
2,2
9
3
12
4
15
5,5
21
6,3
24
7,5
28
-
-
10
36
-
-
11
39
-
-
15
52
-
-
18.5
63
-
-
22
75
-
-
Pdc
BC
Icu (kA)
Rms (kA)
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
-
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
-
Cal (A)
Rat (A)
1,5
1,5
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
12,5
25
25
25
50
50
50
80
80
80
-
Type de coordination: 2
Coordination type: 2
Contacteurs
Contactor
Type
Type
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D18
2 x LC1-D18
2 x LC1-D25
2 x LC1-D32
2 x LC1-D32
2 x LC1-D32
2 x LC1-D32
2 x LC1-D40
2 x LC1-D40
2 x LC1-D40
2 x LC1 D80
2 x LC1-D50
2 x LC1 D80
2 x LC1-D50
2 x LC1 D80
2 x LC1-D65
2 x LC1 D80
2 x LC1-D65
2 x LC1 D80
2 x LC1-D80
2 x LC1 D80
2 sens de marche
Reverse
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1305
0,63...1
LR2-D1305
0,63...1
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D3322
17...25
LR2-D3322
17...25
LR2-D3353
23...32
LR9-D5357
30...50
LR2-D3355
30...40
LR9-D5357
30...50
LR2-D3357
37...50
LR9-D5357
30...50
LR2-D3359
48...65
LR9-D5363
48...80
LR2-D3359
48...65
LR9-D5363
48...80
LR2-D3363
63...80
LR9-D5363
48...80
Nb modules
Nbr of modules
Mf
Mw
3
6
3
6
3
6
3
6
3
6
3
6
3
6
6
6
6
6
6
6
6
6
6
6
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
Ancienne gamme
Old range
Guide Technique V9 / V9 Technical Guide
291
Anex 01
Appendix 01
Compact NS80H-MA
380/415 V
Puissance Moteur
Power motor
P (kW)
I (A)
0,18
0,7
0,25
0,9
0,37
1,2
0,55
1,6
0,75
2
1,1
2,8
1,5
3,7
2,2
5,3
3
7
4
9
5,5
12
7,5
16
10
21
11
23
15
30
-
-
18,5
37
-
-
22
43
-
-
30
59
-
-
37
72
-
-
Pdc
BC
Icu (kA)
Rms (kA)
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
-
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
-
Cal (A)
Rat (A)
1,5
1,5
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
12,5
25
25
25
50
50
50
80
80
-
Type de coordination: 2
Coordination type: 2
Contacteurs
Contactor
Type
Type
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D18
2 x LC1-D18
2 x LC1-D25
2 x LC1-D32
2 x LC1-D32
2 x LC1-D32
2 x LC1-D32
2 x LC1-D40
2 x LC1-D40
2 x LC1-D40
2 x LC1 D80
2 x LC1-D50
2 x LC1 D80
2 x LC1-D50
2 x LC1 D80
2 x LC1-D65
2 x LC1 D80
2 x LC1 D80
2 x LC1 D80
2 sens de marche
Reverse
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1305
0,63...1
LR2-D1305
0,63...1
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D3322
17...25
LR2-D3322
17...25
LR2-D3353
23...32
LR9-D5357
30...50
LR2-D3355
30...40
LR9-D5357
30...50
LR2-D3357
37...50
LR9-D5357
30...50
LR2-D3359
48...65
LR9-D5363
48...80
LR2-D3363
63...80
LR9-D5363
48...80
Nb modules
Nbr of modules
Mf
Mw
3
6
3
6
3
6
3
6
3
6
3
6
3
6
6
6
6
6
6
6
6
6
6
6
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
Ancienne gamme
Old range
Guide Technique V9 / V9 Technical Guide
292
Anex 01
Appendix 01
440 V (1)
Puissance Moteur
Power motor
P (kW)
I (A)
0,25
0,7
0,37
1
0,55
1,4
0,75
1,7
1,1
2,4
1,5
3,1
2,2
4,5
3
5,8
4
8
5,5
10,5
7,5
13,7
10
19
11
20
15
26,5
18,5
33
-
-
22
39
-
-
30
52
-
-
37
63
-
-
45
76
-
-
Compact NS80H-MA
Pdc
BC
Icu (kA)
Rms (kA)
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
-
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
-
Cal (A)
Rat (A)
1,5
2,5
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
25
25
25
50
50
50
80
80
80
-
Type de coordination: 2
Coordination type: 2
Contacteurs
Contactor
Type
Type
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D18
2 x LC1-D25
2 x LC1-D25
2 x LC1-D32
2 x LC1-D32
2 x LC1-D32
2 x LC1-D40
2 x LC1-D40
2 x LC1-D40
2 x LC1-D50
2 x LC1 D80
2 x LC1-D50
2 x LC1 D80
2 x LC1-D65
2 x LC1 D80
2 x LC1-D65
2 x LC1 D80
2 x LC1-D80
2 x LC1 D80
Ancienne gamme
Old range
(1) Applicable pour 480 V NEMA
Guide Technique V9 / V9 Technical Guide
2 sens de marche
Reverse
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1305
0,63...1
LR2-D1306
1...1,6
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D3322
17...25
LR2-D3322
17...25
LR2-D3353
23...32
LR2-D3355
30...40
LR9-D5357
30...50
LR2-D3355
30...40
LR9-D5357
30...50
LR2-D3359
48...65
LR9-D5363
48...80
LR2-D3359
48...65
LR9-D5363
48...80
LR2-D3363
63...80
LR9-D5363
48...80
Nb modules
Nbr of modules
Mf
Mw
3
6
3
6
3
6
3
6
3
6
3
6
6
6
6
6
6
6
6
6
6
6
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
(1) Valid for 480 V NEMA
293
Anex 01
Appendix 01
500/525 V
Puissance Moteur
Power motor
P (kW)
I (A)
0,25
0,6
0,37
0,9
0,55
1,2
0,75
1,5
1,1
2,0
1,5
2,8
2,2
3,8
3
5
4
6,5
5,5
9
7,5
12
10
15
11
18,4
15
23
18,5
28,5
22
33
-
-
-
-
30
45
-
-
-
-
37
55
-
-
-
-
45
65
-
-
55
75
-
-
Compact NS80H-MA
Pdc
BC
Icu (kA)
Rms (kA)
35
35
35
35
35
35
35
35
35
35
35
35
35
35
35
35
35
35
35
35
-
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
-
Cal (A)
Rat (A)
1,5
1,5
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
12,5
25
25
25
50
50
50
80
80
80
-
Ancienne gamme
Old range
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
Type de coordination: 2
Coordination type: 2
Contacteurs
Contactor
Type
Type
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D18
2 x LC1-D18
2 x LC1-D25
2 x LC1-D32
2 x LC1-D32
2 x LC1-D32
2 x LC1-D32
2 x LC1-D40
2 x LC1-D40
2 x LC1-D40
2 x LC1-D50
2 x LC1-D115
2 x LC1-F115
2 x LC1-D50
2 x LC1-D115
2 x LC1-F115
2 x LC1-D65
2 x LC1-D115
2 x LC1-F115
2 x LC1-D115
2 x LC1-F115
2 x LC1-D115
2 x LC1-F115
2 sens de marche
Reverse
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1305
0,63...1
LR2-D1305
0,63...1
LR2-D1306
1...1,6
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D3321
12...18
LR2-D3322
17...25
LR2-D3322
17...25
LR2-D3353
23...32
LR2-D3355
30...40
LR9-D5357
30...50
LR9-F5357
30...50
LR2-D3357
37...50
LR9-D5357
30...50
LR9-F5357
30...50
LR2-D3359
48...65
LR9-D5363
48...80
LR9-F5363
48...80
LR9-D3363
63...80
LR9-D5363
48...80
LR9-F5363
48...80
LR9-D5363
48...80
Nb modules
Nbr of modules
Mf
Mw
3
6
3
6
3
6
3
6
3
6
3
6
3
6
6
6
6
6
6
6
6
6
6
6
6
9
6
9
6
9
6
9
9
12
9
**
6
9
9
12
9
**
6
9
9
12
9
**
9
12
9
**
9
12
9
**
** Impossible in Mw type
294
Anex 01
Appendix 01
Compact NS80H-MA
6.1.1.11.
Type de coordination: 1 - - - - - - - - - - - - - - - -Etoile / Triangle (Y/∆)
Coordination type: 1 - - - - - - - - - - - - - - - - - - -STAR / DELTA (Y/∆)
Démarrage: Normal
Start-up: Normal
Compact NS80H-MA
220/230 V
Puissance Moteur
Power motor
P (kW)
I (A)
0,55
2,8
1,1
4,4
1,5
6,1
2,2
8,7
3
11,5
4
14,5
5,5
20
7,5
28
11
39
15
52
18,5
64
22
75
Pdc
BC
Icu (kA)
Rms (kA)
100
100
100
100
100
100
100
100
100
100
100
100
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
Cal (A)
Rat (A)
6,3
6,3
12,5
12,5
12,5
25
25
50
50
80
80
80
Type de coordination: 1
Coordination type: 1
Contacteurs
Contactor
Type
Type
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D12
3 x LC1-D18
3 x LC1-D18
3 x LC1-D32
3 x LC1-D40
3 x LC1-D50
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D1322
17...25
LR2-D3353
23...32
LR2-D3355
30...40
LR2-D3357
37...50
Nb modules
Nbr of modules
Mf
Mw
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
9
6
9
Ancienne gamme
Old range
Compact NS80H-MA
380 V
Puissance Moteur
Power motor
P (kW)
I (A)
1,5
3,7
2,2
5
3
6,6
4
8,5
5,5
11,5
7,5
15,5
11
22
15
30
18,5
37
22
44
30
59
37
72
Pdc
BC
Icu (kA)
Rms (kA)
70
70
70
70
70
70
70
70
70
70
70
70
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
Cal (A)
Rat (A)
6,3
6,3
12,5
12,5
12,5
25
25
50
50
50
80
80
Type de coordination: 1
Coordination type: 1
Contacteurs
Contactor
Type
Type
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D12
3 x LC1-D18
3 x LC1-D18
3 x LC1-D32
3 x LC1-D40
3 x LC1-D40
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D1322
17...25
LR2-D3353
23...32
LR2-D3355
30...40
LR2-D3357
37...50
Nb modules
Nbr of modules
Mf
Mw
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
9
6
9
Ancienne gamme
Old range
Guide Technique V9 / V9 Technical Guide
295
Anex 01
Appendix 01
Compact NS80H-MA
415 V
Puissance Moteur
Power motor
P (kW)
I (A)
1,5
3,5
2,2
4,8
3
6,5
4
8,2
5,5
11
7,5
14
9
17
11
21
15
28
22
40
25
47
30
55
37
66
45
80
Pdc
BC
Icu (kA)
Rms (kA)
70
70
70
70
70
70
70
70
70
70
70
70
70
70
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
Cal (A)
Rat (A)
6,3
6,3
12,5
12,5
12,5
25
25
25
50
50
50
80
80
80
Type de coordination: 1
Coordination type: 1
Contacteurs
Contactor
Type
Type
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D12
3 x LC1-D12
3 x LC1-D18
3 x LC1-D18
3 x LC1-D32
3 x LC1-D32
3 x LC1-D40
3 x LC1-D50
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D1322
17...25
LR2-D3353
23...32
LR2-D3355
30...40
LR2-D3355
30...40
LR2-D3357
37...50
Nb modules
Nbr of modules
Mf
Mw
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
9
6
9
Ancienne gamme
Old range
Compact NS80H-MA
440 V (1)
Puissance Moteur
Power motor
P (kW)
I (A)
7,5
13,7
9
16,9
11
20,1
15
26,5
22
39
30
51,5
Pdc
BC
Icu (kA)
Rms (kA)
65
65
65
65
65
65
65
65
65
65
65
37
64
65
NS80H-MA
80
3 x LC1-D40
LR2-D3355
45
76
65
NS80H-MA
80
3 x LC1-D50
LR2-D3357
1,5
3,1
2,2
4,5
3
5,8
4
7,9
5,5
10,4
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
Type de coordination: 1
Coordination type: 1
Cal (A)
Rat (A)
6,3
6,3
12,5
12,5
12,5
25
25
25
50
50
80
Contacteurs
Contactor
Type
Type
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D12
3 x LC1-D12
3 x LC1-D18
3 x LC1-D18
3 x LC1-D32
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D1322
17...25
LR2-D3353
23...32
Ancienne gamme
Old range
(1) Applicable pour 480 V NEMA
Guide Technique V9 / V9 Technical Guide
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Nb modules
Nbr of modules
Mf
Mw
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
30...40
6
9
37...50
6
9
(1) Valid for 480 V NEMA
296
Anex 01
Appendix 01
Compact NS80H-MA
6.1.1.12.
Type de coordination: 2 - - - - - - - - - - - - - - - -Etoile / Triangle (Y/∆)
Coordination Type: 2 - - - - - - - - - - - - - - - - - -STAR / DELTA (Y/∆)
Démarrage: normal
Start-up: Normal
Compact NS80H-MA
220/240 V
Puissance Moteur
Power motor
P (kW)
I (A)
0,09
0,7
0,12
0,9
0,18
1,2
0,25
1,5
0,37
2
0,55
2,8
0,75
3,5
1,1
5
1,5
6,5
2,2
9
3
12
4
15
5,5
21
6,3
24
7,5
28
-
-
10
36
-
-
11
39
-
-
15
52
-
-
18.5
63
-
-
22
75
-
-
Pdc
BC
Icu (kA)
Rms (kA)
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
-
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
-
Cal (A)
Rat (A)
1,5
1,5
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
12,5
25
25
25
50
50
50
80
80
80
-
Type de coordination: 2
Coordination type: 2
Contacteurs
Contactor
Type
Type
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D18
3 x LC1-D18
3 x LC1-D25
3 x LC1-D32
3 x LC1-D32
3 x LC1-D32
3 x LC1-D32
3 x LC1-D40
3 x LC1-D40
3 x LC1-D40
3 x LC1 D80
3 x LC1-D50
3 x LC1 D80
3 x LC1-D50
3 x LC1 D80
3 x LC1-D65
3 x LC1 D80
3 x LC1-D65
3 x LC1 D80
3 x LC1-D80
3 x LC1 D80
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1305
0,63...1
LR2-D1305
0,63...1
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D3322
17...25
LR2-D3322
17...25
LR2-D3353
23...32
LR9-D5357
30...50
LR2-D3355
30...40
LR9-D5357
30...50
LR2-D3357
37...50
LR9-D5357
30...50
LR2-D3359
48...65
LR9-D5363
48...80
LR2-D3359
48...65
LR9-D5363
48...80
LR2-D3363
63...80
LR9-D5363
48...80
Nb modules
Nbr of modules
Mf
Mw
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
9
6
9
6
9
9
12
6
9
9
12
6
9
9
12
6
9
9
12
6
9
9
12
9
9
9
12
Ancienne gamme
Old range
Guide Technique V9 / V9 Technical Guide
297
Anex 01
Appendix 01
Compact NS80H-MA
380/415 V
Puissance Moteur
Power motor
P (kW)
I (A)
0,18
0,7
0,25
0,9
0,37
1,2
0,55
1,6
0,75
2
1,1
2,8
1,5
3,7
2,2
5,3
3
7
4
9
5,5
12
7,5
16
10
21
11
23
15
30
-
-
18,5
37
-
-
22
43
-
-
30
59
-
-
37
72
-
-
Pdc
BC
Icu (kA)
Rms (kA)
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
-
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
-
Cal (A)
Rat (A)
1,5
1,5
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
12,5
25
25
25
50
50
50
80
80
-
Type de coordination: 2
Coordination type: 2
Contacteurs
Contactor
Type
Type
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D18
3 x LC1-D18
3 x LC1-D25
3 x LC1-D32
3 x LC1-D32
3 x LC1-D32
3 x LC1-D32
3 x LC1-D40
3 x LC1-D40
3 x LC1-D40
3 x LC1 D80
3 x LC1-D50
3 x LC1 D80
3 x LC1-D50
3 x LC1 D80
3 x LC1-D65
3 x LC1 D80
3 x LC1 D80
3 x LC1 D80
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1305
0,63...1
LR2-D1305
0,63...1
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D3322
17...25
LR2-D3322
17...25
LR2-D3353
23...32
LR9-D5357
30...50
LR2-D3355
30...40
LR9-D5357
30...50
LR2-D3357
37...50
LR9-D5357
30...50
LR2-D3359
48...65
LR9-D5363
48...80
LR2-D3363
63...80
LR9-D5363
48...80
Nb modules
Nbr of modules
Mf
Mw
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
9
6
9
6
9
9
12
6
9
9
12
6
9
9
12
6
9
9
12
9
9
9
12
Ancienne gamme
Old range
Guide Technique V9 / V9 Technical Guide
298
Anex 01
Appendix 01
440 V (1)
Puissance Moteur
Power motor
P (kW)
I (A)
0,25
0,7
0,37
1
0,55
1,4
0,75
1,7
1,1
2,4
1,5
3,1
2,2
4,5
3
5,8
4
8
5,5
10,5
7,5
13,7
10
19
11
20
15
26,5
18,5
33
-
-
22
39
-
-
30
52
-
-
37
63
-
-
45
76
-
-
Compact NS80H-MA
Pdc
BC
Icu (kA)
Rms (kA)
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
-
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
-
Cal (A)
Rat (A)
1,5
2,5
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
25
25
25
50
50
50
80
80
80
-
Type de coordination: 2
Coordination type: 2
Contacteurs
Contactor
Type
Type
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D18
3 x LC1-D25
3 x LC1-D25
3 x LC1-D32
3 x LC1-D32
3 x LC1-D32
3 x LC1-D40
3 x LC1-D40
3 x LC1-D40
3 x LC1-D50
3 x LC1 D80
3 x LC1-D50
3 x LC1 D80
3 x LC1-D65
3 x LC1 D80
3 x LC1-D65
3 x LC1 D80
3 x LC1-D80
3 x LC1 D80
Ancienne gamme
Old range
(1) Applicable pour 480 V NEMA
Guide Technique V9 / V9 Technical Guide
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1305
0,63...1
LR2-D1306
1...1,6
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D3322
17...25
LR2-D3322
17...25
LR2-D3353
23...32
LR2-D3355
30...40
LR9-D5357
30...50
LR2-D3355
30...40
LR9-D5357
30...50
LR2-D3359
48...65
LR9-D5363
48...80
LR2-D3359
48...65
LR9-D5363
48...80
LR2-D3363
63...80
LR9-D5363
48...80
Nb modules
Nbr of modules
Mf
Mw
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
9
6
9
6
9
6
9
9
12
6
9
9
12
6
9
9
12
6
9
9
12
9
9
9
12
(1) Valid for 480 V NEMA
299
Anex 01
Appendix 01
500/525 V
Puissance Moteur
Power motor
P (kW)
I (A)
0,25
0,6
0,37
0,9
0,55
1,2
0,75
1,5
1,1
2,0
1,5
2,8
2,2
3,8
3
5
4
6,5
5,5
9
7,5
12
10
15
11
18,4
15
23
18,5
28,5
22
33
-
-
-
-
30
45
-
-
-
-
37
55
-
-
-
-
45
65
-
-
55
75
-
-
Compact NS80H-MA
Pdc
BC
Icu (kA)
Rms (kA)
35
35
35
35
35
35
35
35
35
35
35
35
35
35
35
35
35
35
35
35
-
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
-
Cal (A)
Rat (A)
1,5
1,5
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
12,5
25
25
25
50
50
50
80
80
80
-
Ancienne gamme
Old range
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
Type de coordination: 2
Coordination type: 2
Contacteurs
Contactor
Type
Type
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D18
3 x LC1-D18
3 x LC1-D25
3 x LC1-D32
3 x LC1-D32
3 x LC1-D32
3 x LC1-D32
3 x LC1-D40
3 x LC1-D40
3 x LC1-D40
3 x LC1-D50
3 x LC1-D115
3 x LC1-F115
3 x LC1-D50
3 x LC1-D115
3 x LC1-F115
3 x LC1-D65
3 x LC1-D115
3 x LC1-F115
3 x LC1-D115
3 x LC1-F115
3 x LC1-D115
3 x LC1-F115
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1305
0,63...1
LR2-D1305
0,63...1
LR2-D1306
1...1,6
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D3321
12...18
LR2-D3322
17...25
LR2-D3322
17...25
LR2-D3353
23...32
LR2-D3355
30...40
LR9-D5357
30...50
LR9-F5357
30...50
LR2-D3357
37...50
LR9-D5357
30...50
LR9-F5357
30...50
LR2-D3359
48...65
LR9-D5363
48...80
LR9-F5363
48...80
LR9-D3363
63...80
LR9-D5363
48...80
LR9-F5363
48...80
LR9-D5363
48...80
Nb modules
Nbr of modules
Mf
Mw
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
9
6
9
6
9
6
9
12
**
12
**
6
9
12
**
12
**
6
9
12
**
12
**
12
**
12
**
12
**
12
**
** Impossible in Mw type
300
Anex 01
Appendix 01
Compact NS100-630z-MA
6.1.1.13.
Type de coordination: 1 - - - - - - - - - - - - - - - -DOL (Démarrage direct)
Coordination type: 1 - - - - - - - - - - - - - - - - - - -DOL (Direct On Line)
Démarrage: Normal
Start-up: Normal
Compact NS100-630z-MA
220/240 V
Type de coordination: 1
Coordination type: 1
DOL (Démarrage direct)
DOL (Direct On Line)
Performance de coupure / Breaking characteristics
Compact NS
N
H
L
NS100z-MA
85kA
100kA
130kA
NS160/250z-MA
85kA
100kA
130kA
100kA
130kA
NS400/630z-MA
Puissance Moteur
Power motor
P (kW)
I (A)
0,37
1,8
0,55
2,8
1,1
4,4
1,5
6,1
2,2
8,7
3
11,5
4
14,5
5,5
20
7,5
28
11
39
-
-
15
52
-
-
18,5
64
-
-
22
75
Disjoncteurs
Circuit Breaker
Type
Type
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
Cal (A)
Rat (A)
2,5
6,3
6,3
12,5
12,5
12,5
25
25
50
50
50
100
100
Contacteurs
Contactor
Type
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D12
LC1-D18
LC1-D25
LC1-D32
LC1-D40
LC1-D65
LC1-D65
LC1-D80
25
85
NS100N/H/L-MA
100
LC1-D95
-
-
-
-
-
30
100
NS100N/H/L-MA
100
LC1-D115
-
-
-
-
LC1-F115
37
125
NS160N/H/L-MA
150
LC1-D150
45
150
NS160N/H/L-MA
150
LC1-F150
55
180
NS250N/H/L-MA
220
LC1-F185
75
250
NS400H-MA
320
LC1-F265
-
-
NS400L-MA
320
LC1-F265
90
312
NS400H-MA
320
LC1-F330
-
-
NS400L-MA
320
LC1-F330
110
360
NS630H/L-MA
500
LC1-F400
150
480
NS630H/L-MA
500
LC1-F500
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D1322
17...25
LR2-D3353
23...32
LR2-D3357
37...50
LR9-D5357
30...50
LR2-D3357
37...50
LR9-D5357
30...50
LR2-D3359
48...65
LR9-D5363
48...80
LR2-D3363
63...80
LR9-D5363
48...80
LR2-D3365
80...93
LR9-D5367
60...100
LR9-D5367
60...100
LR9-F5367
60...100
LR9-D5369
90...150
LR9-F5369
90...150
LR9-F5371
132...220
LR9-F7375
200...330
LR9-F7375
200...330
LR9-F7375
200...330
LR9-F7375
200...330
LR9-F7379
300...500
LR9-F7379
300...500
Ancienne gamme
Old range
* Modulaire à confirmer en fonction de la
tension
Guide Technique V9 / V9 Technical Guide
Nb modules
Nbr of modules
Mf
Mw
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
9
3
6
3
9
3
6
3
9
3
6
9
3
6
3
9
6
9
6
9
6
9
6
9
9
9
9
12
9
*
12
12
12
*
15
15
15
15
* Confirm module in function of voltage
301
Anex 01
Appendix 01
Compact NS100-630z-MA
380 V
Type de coordination: 1
Coordination type: 1
DOL (Démarrage direct)
DOL (Direct On Line)
Performance de coupure / Breaking characteristics
Compact NS
N
H
L
NS100z-MA
25kA
70kA
130kA
NS160/250z-MA
35kA
70kA
130kA
70kA
130kA
NS400/630z-MA
Puissance Moteur
Power motor
P (kW)
I (A)
0,37
1,2
0,55
1,6
0,75
2
1,1
2,8
1,5
3,7
2,2
5
3
6,6
4
8,5
5,5
11,5
7,5
15,5
11
22
15
30
18,5
37
Disjoncteurs
Circuit Breaker
Type
Type
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
-
-
-
Cal (A)
Rat (A)
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
12,5
25
25
50
50
Contacteurs
Contactor
Type
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D12
LC1-D18
LC1-D25
LC1-D32
LC1-D40
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1306
1...1,6
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D1322
17...25
LR2-D3353
23...32
LR2-D3357
37...50
-
-
LR9-D5357
30...50
Nb modules
Nbr of modules
Mf
Mw
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
9
22
44
NS100N/H/L-MA
50
LC1-D50
LR2-D3357
37...50
3
6
-
-
-
-
-
LR9-D5357
30...50
3
9
30
59
NS100N/H/L-MA
50
LC1-D65
LR2-D3357
37...50
3
6
-
-
-
-
-
LR9-D5357
30...50
3
9
37
72
NS100N/H/L-MA
100
LC1-D80
LR2-D3363
63...80
3
6
-
-
-
-
-
LR9-D5363
48...80
3
9
45
85
NS100N/H/L-MA
100
LC1-D95
LR2-D3365
80...93
3
6
-
-
-
-
-
LR9-D5367
60...100
3
9
55
105
NS160N/H/L-MA
150
LC1-D150
LR9-D5369
90...150
6
9
75
140
NS160N/H/L-MA
150
LC1-F150
LR9-F5369
90...150
6
9
90
170
NS250N/H/L-MA
220
LC1-F185
LR9-F5371
132...220
9
9
110
210
NS250N/H/L-MA
220
LC1-F225
LR9-F5371
132...220
9
9
132
250
NS400H-MA
320
LC1-F265
LR9-F7375
200...330
9
12
-
-
NS400L-MA
320
LC1-F265
LR9-F7375
200...330
9
15
160
300
NS400H-MA
320
LC1-F330
LR9-F7375
200...330
12
12
-
-
NS400L-MA
320
LC1-F330
LR9-F7375
200...330
12
15
200
380
NS630H/L-MA
500
LC1-F400
LR9-F7379
300...500
15
15
220
420
NS630H/L-MA
500
LC1-F500
LR9-F7379
300...500
15
15
250
480
NS630H/L-MA
500
LC1-F500
LR9-F7379
300...500
15
15
Ancienne gamme
Old range
Guide Technique V9 / V9 Technical Guide
302
Anex 01
Appendix 01
Compact NS100-630z-MA
415 V
Type de coordination: 1
Coordination type: 1
DOL (Démarrage direct)
DOL (Direct On Line)
Performance de coupure / Breaking characteristics
Compact NS
N
H
L
NS100z-MA
25kA
70kA
130kA
NS160/250z-MA
35kA
70kA
130kA
70kA
130kA
NS400/630z-MA
Puissance Moteur
Power motor
P (kW)
I (A)
9
17
11
21
15
28
Disjoncteurs
Circuit Breaker
Type
Type
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
22
40
NS100N/H/L-MA
50
LC1-D40
LR2-D3357
37...50
3
6
-
-
-
-
-
LR9-D5357
30...50
3
9
0,37
1,1
0,55
1,5
0,75
1,8
1,1
2,5
1,5
3,5
2,2
4,8
3
6,5
4
8,2
5,5
11
7,5
14
Cal (A)
Rat (A)
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
12,5
25
25
25
50
Contacteurs
Contactor
Type
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D12
LC1-D18
LC1-D18
LC1-D25
LC1-D32
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1306
1...1,6
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D1321
12...18
LR2-D1322
17...25
LR2-D3353
23...32
Nb modules
Nbr of modules
Mf
Mw
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
25
47
NS100N/H/L-MA
50
LC1-D50
LR2-D3357
37...50
3
6
-
-
-
-
-
LR9-D5357
30...50
3
9
30
55
NS100N/H/L-MA
50
LC1-D65
LR2-D3357
37...50
3
6
-
-
-
-
-
LR9-D5357
30...50
3
9
37
72
NS100N/H/L-MA
100
LC1-D80
LR2-D3363
63...80
3
6
45
80
NS100N/H/L-MA
100
LC1-D80
LR9-D5363
48...80
3
9
55
100
NS100N/H/L-MA
100
LC1-D115
LR9-D5367
60...100
6
9
-
-
-
-
LC1-F115
LR9-F5367
60...100
6
9
75
135
NS160N/H/L-MA
150
LC1-D150
LR9-D5369
90...150
6
9
-
-
-
-
LC1-F150
LR9-F5369
90...150
6
9
90
160
NS250N/H/L-MA
220
LC1-F185
LR9-F5371
132...220
9
9
110
200
NS250N/H/L-MA
220
LC1-F225
LR9-F5371
132...220
9
9
132
230
NS400H-MA
320
LC1-F265
LR9-F7375
200...330
9
12
-
-
NS400L-MA
320
LC1-F265
LR9-F7375
200...330
9
15
160
270
NS400H-MA
320
LC1-F330
LR9-F7375
200...330
12
12
-
-
NS400L-MA
320
LC1-F330
LR9-F7375
200...330
12
15
220
380
NS630H/L-MA
500
LC1-F400
LR9-F7379
300...500
15
15
250
430
NS630H/L-MA
500
LC1-F500
LR9-F7379
300...500
15
15
Ancienne gamme
Old range
Guide Technique V9 / V9 Technical Guide
303
Anex 01
Appendix 01
Compact NS100-630z-MA
440 V (1)
Type de coordination: 1
Coordination type: 1
DOL (Démarrage direct)
DOL (Direct On Line)
Performance de coupure / Breaking characteristics
Compact NS
N
H
L
NS100z-MA
25kA
65kA
130kA
NS160/250z-MA
35kA
65kA
130kA
65kA
130kA
NS400/630z-MA
Puissance Moteur
Power motor
P (kW)
I (A)
9
16,9
11
20,1
15
26,5
Disjoncteurs
Circuit Breaker
Type
Type
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
22
39
NS100N/H/L-MA
50
LC1-D40
LR2-D3357
37...50
3
6
-
-
-
-
-
LR9-D5357
30...50
3
9
0,37
1
0,55
1,4
0,75
1,7
1,1
2,4
1,5
3,1
2,2
4,5
3
5,8
4
7,9
5,5
10,4
7,5
13,7
Cal (A)
Rat (A)
2,5
2,5
2,5
2,5
6,3
6,3
12,5
12,5
12,5
25
25
25
50
Contacteurs
Contactor
Type
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D12
LC1-D18
LC1-D18
LC1-D25
LC1-D32
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1306
1...1,6
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D1321
12...18
LR2-D1322
17...25
LR2-D3353
23...32
Nb modules
Nbr of modules
Mf
Mw
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
30
51,5
NS100N/H/L-MA
50
LC1-D65
LR2-D3357
37...50
3
6
-
-
-
-
-
LR9-D5357
30...50
3
9
37
64
NS100N/H/L-MA
100
LC1-D65
LR2-D3359
48...65
3
6
-
-
-
-
-
LR9-D5363
48...80
3
9
45
76
NS100N/H/L-MA
100
LC1-D80
LR2-D3363
63...80
3
6
-
-
-
-
LR9-D5363
48...80
3
9
55
96
NS100N/H/L-MA
100
LC1-D115
LR9-D5367
60...100
6
-
-
-
-
LC1-F115
LR9-F5367
60...100
75
124
NS160N/H/L-MA
150
LC1-D150
LR9-D5369
90...150
-
-
-
-
LC1-F150
LR9-F5369
90...150
9
9
6
9
9
90
156
NS250N/H/L-MA
220
LC1-F185
LR9-F5371
132...220
9
9
110
180
NS250N/H/L-MA
220
LC1-F185
LR9-F5371
132...220
9
9
132
215
NS250N/H/L-MA
220
LC1-F225
LR9-F5371
132...220
9
9
160
256
NS400H-MA
320
LC1-F265
LR9-F7375
200...330
9
12
-
-
NS400L-MA
320
LC1-F265
LR9-F7375
200...330
9
15
220
360
NS630H/L-MA
500
LC1-F400
LR9-F7379
300...500
15
15
250
401
NS630H/L-MA
500
LC1-F500
LR9-F7379
300...500
15
15
300
480
NS630H/L-MA
500
LC1-F630
LR9-F7381
380...630
16
**
Ancienne gamme
Old range
(1) Applicable pour 480 V NEMA
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
(1) Valid for 480 V NEMA
** Impossible in Mw type
304
Anex 01
Appendix 01
Compact NS100-630z-MA
500/525 V
Type de coordination: 1
Coordination type: 1
DOL (Démarrage direct)
DOL (Direct On Line)
Performance de coupure / Breaking characteristics
Compact NS
H
L
NS100z-MA
50/35kA
70kA
NS160/250z-MA
50/35kA
70kA
NS400/630z-MA
50/35kA
70kA
Puissance Moteur
Power motor
P (kW)
I (A)
0,55
1,2
0,75
1,5
1,1
2
1,5
2,6
3
5
4
6,5
5,5
9
7,5
12
9
14
10
15
11
18,4
18,5
28,5
22
33
Disjoncteurs
Circuit Breaker
Type
Type
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
-
-
-
Cal (A)
Rat (A)
2,5
2,5
2,5
6,3
6,3
12,5
12,5
12,5
25
25
25
50
50
Contacteurs
Contactor
Type
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D12
LC1-D18
LC1-D18
LC1-D25
LC1-D32
LC1-D40
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1306
1...1,6
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D1321
12...18
LR2-D1322
17...25
LR2-D3353
23...32
LR2-D3355
30...40
-
-
LR9-D5357
30...50
Nb modules
Nbr of modules
Mf
Mw
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
9
30
45
NS100N/H/L-MA
50
LC1-D50
LR2-D3357
37...50
3
6
-
-
-
-
-
LR9-D5357
30...50
3
9
37
55
NS100N/H/L-MA
100
LC1-D65
LR2-D3359
48...65
3
6
-
-
-
-
-
LR9-D5363
48...80
3
9
55
80
NS100N/H/L-MA
100
LC1-D80
LR2-D3363
63...80
3
6
-
-
-
-
-
LR9-D5363
48...80
3
9
75
110
NS160N/H/L-MA
150
LC1-D150
LR9-D5369
90...150
6
9
90
130
NS160N/H/L-MA
150
LC1-F150
LR9-F5369
90...150
6
9
110
156
NS250N/H/L-MA
220
LC1-F185
LR9-F5371
132...220
9
9
132
190
NS250N/H/L-MA
220
LC1-F265
LR9-F5371
132...220
9
12
160
228
NS400H-MA
320
LC1-F265
LR9-F7375
200...330
9
12
-
-
NS400L-MA
320
LC1-F265
LR9-F7375
200...330
9
15
200
281
NS400H-MA
320
LC1-F330
LR9-F7375
200...330
12
12
-
-
NS400L-MA
320
LC1-F330
LR9-F7375
200...330
12
15
220
310
NS630H/L-MA
500
LC1-F400
LR9-F7379
300...500
15
15
315
445
NS630H/L-MA
500
LC1-F500
LR9-F7379
300...500
15
15
335
460
NS630H/L-MA
500
LC1-F500
LR9-F7379
300...500
15
15
Ancienne gamme
Old range
Guide Technique V9 / V9 Technical Guide
305
Anex 01
Appendix 01
Compact NS100-630z-MA
660/690 V (1)
Type de coordination: 1
Coordination type: 1
DOL (Démarrage direct)
DOL (Direct On Line)
Performance de coupure / Breaking characteristics
Compact NS
N
NS100z-MA
8kA
H
NS160/250z-MA
10kA
NS400/630z-MA
20kA
Puissance Moteur
Power motor
P (kW)
I (A)
0,75
1.2
1
1,5
1,5
2
2,2
2,8
3
3,8
4
4,9
5,5
6,6
7,5
8,9
10
11,5
15
17
18,5
21,3
30
34,6
-
-
Disjoncteurs
Circuit Breaker
Type
Type
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
-
Cal (A)
Rat (A)
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
25
25
50
50
-
Contacteurs
Contactor
Type
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D12
LC1-D18
LC1-D25
LC1-D32
LC1-D40
-
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1306
1...1,6
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
18...12
LR2-D1322
17...25
LR2-D3355
30...40
LR9-D5357
30...50
Nb modules
Nbr of modules
Mf
Mw
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
9
33
39
NS100N/H/L-MA
50
LC1-D50
LR2-D3357
37...50
3
6
-
-
-
-
-
LR9-D5357
30...50
3
9
37
42
NS100N/H/L-MA
50
LC1-D65
LR2-D3357
37...50
3
6
-
-
-
-
-
LR9-D5357
30...50
3
9
45
49
NS100N/H/L-MA
100
LC1-D80
LR2-D3357
37...50
3
6
-
-
-
-
-
LR9-D5363
48...80
3
9
55
60
NS100N/H/L-MA
100
LC1-D115
LR9-D5363
48...80
6
9
-
-
-
-
LC1-F115
LR9-F5363
48...80
6
9
75
80
NS100N/H/L-MA
100
LC1-D115
LR9-D5367
60...100
6
9
-
-
-
-
LC1-F115
LR9-F5367
60...100
6
9
90
100
NS160N/H/L-MA
150
LC1-D150
LR9-D5369
90...150
6
9
110
120
NS160N/H/L-MA
150
LC1-F150
LR9-F5369
90...150
6
9
132
140
NS250N/H/L-MA
220
LC1-F265
LR9-F5371
132...220
9
12
160
175
NS250N/H/L-MA
220
LC1-F265
LR9-F5371
132...220
9
12
200
220
NS400H-MA
320
LC1-F330
LR9-F7375
200...330
12
12
-
-
NS400L-MA
320
LC1-F330
LR9-F7375
200...330
12
12
220
240
NS400H-MA
320
LC1-F330
LR9-F7375
200...330
12
12
-
-
NS400L-MA
320
LC1-F330
LR9-F7375
200...330
12
15
250
270
NS630H/L-MA
500
LC1-F400
LR9-F7375
200...300
15
15
335
335
NS630H/L-MA
500
LC1-F500
LR9-F7379
300...500
15
15
375
400
NS630H/L-MA
500
LC1-F630
LR9-F7381
380...630
16
**
450
480
NS630H/L-MA
500
LC1-F630
LR9-F7381
380...630
16
**
Ancienne gamme
Old range
(1) Confirmer le nb de modules pour
660/690 V
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
(1) Confirm number of modules in function of
this voltage level 660/690 V
** Impossible in Mw type
306
Anex 01
Appendix 01
Compact NS100-630z-MA
6.1.1.14.
Type de coordination: 2 - - - - - - - - - - - - - - - -DOL (Démarrage direct)
Coordination type: 2 - - - - - - - - - - - - - - - - - - -DOL (Direct On Line)
Démarrage: normal
Start-up: Normal
Compact NS100-630z-MA
220/240 V
Type de coordination: 2
Coordination type: 2
DOL (Démarrage direct)
DOL (Direct On Line)
Performance de coupure / Breaking characteristics
Compact NS
N
H
L
NS100z-MA
85kA
100kA
130kA
NS160/250z-MA
85kA
100kA
130kA
100kA
130kA
NS400/630z-MA
Puissance Moteur
Power motor
P (kW)
I (A)
0,18
0,25
0,37
0,55
0,75
1,1
1,5
2,2
3
4
5,5
6,3
7,5
10
11
15
18,5
22
30
37
45
55
75
90
110
132
150
1,2
1,5
2
2,8
3,5
5
6,5
9
12
15
21
24
28
36
39
52
63
75
100
125
150
180
250
300
360
430
460
Disjoncteurs
Circuit Breaker
Type
Type
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS160-MA
NS160-MA
NS250-MA
NS400-MA
NS400-MA
NS400-MA
NS630-MA
NS630-MA
NS630-MA
Cal (A)
Rat (A)
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
12,5
25
25
25
50
50
50
100
100
100
100
150
150
220
320
320
320
500
500
500
Contacteurs
Contactor
Type
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D115
LC1-F115
LC1-D150
LC1-F150
LC1-D150
LC1-F150
LC1-F185
LC1-F265
LC1-F265
LC1-F330
LC1-F400
LC1-F500
LC1-F500
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D3322
17...25
LR2-D3322
17...25
LR2-D3353
23...32
LR9-D5357
30...50
LR2-D3355
30...40
LR9-D5357
30...50
LR2-D3355
30...40
LR9-D5357
30...50
LR2-D3359
48...65
LR9-D5363
48...80
LR2-D3359
48...65
LR9-D5363
48...80
LR2-D3363
63...80
LR9-D5363
48...80
LR9-D5367
60...100
LR9-F5367
60...100
LR9-D5369
90...150
LR9-F5369
90...150
LR9-D5369
90...150
LR9-F5369
90...150
LR9-F5371
132...220
LR9-F5371
132...220
LR9-F7375
200...330
LR9-F7375
200...330
LR9-F7379
300...500
LR9-F7379
300...500
LR9-F7379
300...500
Nb modules
Nbr of modules
Mf
Mw
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
6
6
6
6
6
6
9
12
12
15
15
15
15
6
6
6
6
6
6
6
6
6
6
6
6
6
9
6
9
6
9
6
9
6
9
6
9
9
9
9
9
9
9
9
*
*
*
15
15
15
Ancienne gamme
Old range
Guide Technique V9 / V9 Technical Guide
307
Anex 01
Appendix 01
Compact NS100-630z-MA
380/415 V
Type de coordination: 2
Coordination type: 2
DOL (Démarrage direct)
DOL (Direct On Line)
Performance de coupure / Breaking characteristics
Compact NS
N
H
L
NS100z-MA
25kA
70kA
130kA
NS160/250z-MA
35kA
70kA
130kA
70kA
130kA
NS400/630z-MA
Puissance Moteur
Power motor
P (kW)
I (A)
0,37
1,2
0,55
1,6
0,75
2
1,1
2,8
1,5
3,7
2,2
5,3
3
7
4
9
5,5
12
7,5
16
10
21
11
23
15
30
-
-
18,5
37
-
-
22
43
-
-
30
59
-
-
37
72
-
-
45
85
-
-
55
105
-
-
75
140
-
-
90
170
110
210
-
-
132
250
160
300
200
380
220
420
250
480
Disjoncteurs
Circuit Breaker
Type
Type
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS160-MA
NS160-MA
NS250-MA
NS250-MA
NS400-MA
NS400-MA
NS400-MA
NS630-MA
NS630-MA
NS630-MA
Cal (A)
Rat (A)
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
12,5
25
25
25
50
50
50
100
100
100
150
150
220
220
320
320
320
500
500
500þ
Contacteurs
Contactor
Type
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D115
LC1-F115
LC1-D115
LC1-F115
LC1-D150
LC1-F150
LC1-F185
LC1-F225
LC1-F265
LC1-F265
LC1-F330
LC1-F400
LC1-F500
LC1-F500
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D3322
17...25
LR2-D3322
17...25
LR2-D3353
23...32
LR9-D5357
30...50
LR2-D3355
30...40
LR9-D5357
30...50
LR2-D3357
37...50
LR9-D5357
30...50
LR2-D3359
48...65
LR9-D5363
48...80
LR2-D3363
63...80
LR9-D5363
48...80
LR9-D5367
60...100
LR9-F5367
60...100
LR9-D5369
90...150
LR9-F5369
90...150
LR9-D5369
90...150
LR9-F5369
90...150
LR9-F5371
132...220
LR9-F5371
132...220
LR9-F5371
132...220
LR9-F7375
200...330
LR9-F7375
200...330
LR9-F7379
300...500
LR9-F7379
300...500
LR9-F7379
300...500
Nb modules
Nbr of modules
Mf
Mw
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
9
3
6
3
9
3
6
3
9
3
6
3
9
3
6
3
9
6
9
6
9
6
9
6
9
6
9
6
9
9
9
9
9
12
*
12
*
15
*
15
15
15
15
15
15
Ancienne gamme
Old range
Guide Technique V9 / V9 Technical Guide
308
Anex 01
Appendix 01
Compact NS100-630z-MA
440 V
Type de coordination: 2
Coordination type: 2
DOL (Démarrage direct)
DOL (Direct On Line)
Performance de coupure / Breaking characteristics
Compact NS
N
H
L
NS100z-MA
25kA
65kA
130kA
NS160/250z-MA
35kA
65kA
130kA
65kA
130kA
NS400/630z-MA
Puissance Moteur
Power motor
P (kW)
I (A)
440V
0.37
1
0.55
1.4
0.75
1.7
1.1
2.4
1.5
3.1
2.2
4.5
3
5.8
4
8
5.5
10.5
7.5
13.7
10
19
11
20
15
26.5
Disjoncteurs
Circuit Breaker
Type
Type
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
Cal (A)
Rat (A)
2.5
2.5
2.5
2.5
6.3
6.3
6.3
12.5
12.5
25
25
25
50
Contacteurs
Contactor
Type
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D80
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1306
1...1,6
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D3322
17...25
LR2-D3322
17...25
LR2-D3353
23...32
18.5
33
-
Nb modules
Nbr of modules
NS100-MA
50
LC1-D80
LR2-D3355
30...40
3
6
-
-
-
LC1-D80
LR9-D5357
30...50
3
9
Mf
Mw
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
22
39
NS100-MA
50
LC1-D80
LR2-D3355
30...40
3
6
-
-
-
-
LC1-D80
LR9-D5357
30...50
3
9
30
52
NS100-MA
100
LC1-D80
LR2-D3359
48...65
3
6
-
-
-
-
LC1-D80
LR9-D5363
48...80
3
9
37
63
NS100-MA
100
LC1-D80
LR2-D3359
48...65
3
6
-
-
-
-
LC1-D80
LR9-D5363
48...80
3
9
45
76
NS100-MA
100
LC1-D80
LR2-D3363
63...80
3
6
-
-
-
-
-
LR9-D5363
48...80
3
9
55
90
NS100-MA
100
LC1-D115
LR9-D5367
60...100
6
9
-
-
-
-
LC1-F115
LR9-F5367
60...100
6
9
75
125
NS160-MA
150
LC1-D150
LR9-D5369
90...150
6
9
-
-
-
-
LC1-F150
LR9-F5369
90...150
6
9
90
140
NS160-MA
150
LC1-D150
LR9-D5369
90...150
6
9
-
-
-
-
LC1-F150
LR9-F5369
90...150
6
9
110
178
NS250-MA
220
LC1-F185
LR9-F5371
132...220
9
9
132
210
NS250-MA
220
LC1-F225
LR9-F5371
132...220
9
9
-
-
NS400-MA
320
LC1-F265
LR9-F5371
132...220
12
*
160
256
NS400-MA
320
LC1-F265
LR9-F7375
200...330
12
*
200
310
NS400-MA
320
LC1-F330
LR9-F7375
200...330
15
*
220
353
NS630-MA
500
LC1-F400
LR9-F7379
300...500
15
15
250
400
NS630-MA
500
LC1-F400
LR9-F7379
300...500
15
15
300
460
NS630-MA
500
LC1-F500
LR9-F7379
300...500
15
15
Ancienne gamme
Old range
(1) Applicable pour 480 V NEMA
Guide Technique V9 / V9 Technical Guide
(1) Valid for 480 V NEMA
309
Anex 01
Appendix 01
Compact NS100-630z-MA
500/525 V
Type de coordination: 2
Coordination type: 2
DOL (Démarrage direct)
DOL (Direct On Line)
Performance de coupure / Breaking characteristics
Compact NS
H
L
NS100z-MA
50/35kA
70kA
NS160/250z-MA
50/35kA
70kA
NS400/630z-MA
50/35kA
70kA
Puissance Moteur
Power motor
P (kW)
I (A)
500V
0,55
1,2
0,75
1,5
1,1
2
1,5
2,8
2,2
3,8
3
5
4
6,5
5,5
9
7,5
12
10
15
11
18,4
15
23
18,5
28,5
Disjoncteurs
Circuit Breaker
Type
Type
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
Cal (A)
Rat (A)
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
12,5
25
25
25
50
Contacteurs
Contactor
Type
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D80
LC1-D80
LC1-D80
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1306
1...1,6
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D3322
17...25
LR2-D3322
17...25
LR2-D3353
23...32
22
33
-
-
Nb modules
Nbr of modules
NS100-MA
50
LC1-D80
LR2-D3355
23...32
3
6
-
-
LC1-D115
LR9-D5357
30...50
6
9
9
Mf
Mw
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
-
-
-
-
LC1-F115
LR9-F5357
30...50
6
30
45
NS100-MA
50
LC1-D80
LR2-D3357
30...40
3
6
-
-
-
-
LC1-D115
LR9-D5357
30...50
6
9
9
-
-
-
-
LC1-F115
LR9-F5357
30...50
6
37
55
NS100-MA
100
LC1-D80
LR2-D3359
48...65
3
6
-
-
-
-
LC1-D115
LR9-D5363
48...80
6
9
9
-
-
-
-
LC1-F115
LR9-F5363
48...80
6
45
65
NS100-MA
100
LC1-D115
LR9-D5363
48...80
6
9
-
-
-
-
LC1-F115
LR9-F5363
48...80
6
9
55
75
NS100-MA
100
LC1-D115
LR9-D5367
60...100
6
9
-
-
-
-
LC1-F115
LR9-F5367
60...100
6
9
75
105
NS160-MA
150
LC1-D115
LR9-D5369
90...150
6
9
-
-
-
-
LC1-F115
LR9-F5369
90...150
6
9
90
130
NS160-MA
150
LC1-D150
LR9-D5369
90...150
6
9
-
-
-
-
LC1-F150
LR9-F5369
90...150
6
9
110
156
NS250-MA
220
LC1-F185
LR9-F5371
132...220
9
9
132
187
NS250-MA
220
LC1-F265
LR9-F5371
132...220
9
12
160
220
NS400-MA
320
LC1-F400
LR9-F7375
200...330
15
*
200
280
NS400-MA
320
LC1-F400
LR9-F7375
200...330
15
*
220
310
NS400-MA
500
LC1-F400
LR9-F7379
200...330
15
*
250
360
NS630-MA
500þ
LC1-F500
LR9-F7379
300...500
15
15
315
445
NS630-MA
500
LC1-F500
LR9-F7379
300...500
15
15
Ancienne gamme
Old range
Guide Technique V9 / V9 Technical Guide
310
Anex 01
Appendix 01
Compact NS100-630z-MA
6.1.1.15.
Type de coordination: 1 - - - - - - - - - - - - - - - -2 sens de marche
Coordination type: 1 - - - - - - - - - - - - - - - - - - -Reverse
Démarrage: Normal
Start-up: Nor mal
Compact NS100-630z-MA
220/240 V
Type de coordination: 1
Coordination type: 1
2 sens de marche
Reverse
Performance de coupure / Breaking characteristics
Compact NS
N
H
L
NS100z-MA
85kA
100kA
130kA
NS160/250z-MA
85kA
100kA
130kA
100kA
130kA
NS400/630z-MA
Puissance Moteur
Power motor
P (kW)
I (A)
0,37
1,8
0,55
2,8
1,1
4,4
1,5
6,1
2,2
8,7
3
11,5
4
14,5
5,5
20
7,5
28
11
39
-
-
15
52
-
-
18,5
64
-
-
22
75
-
-
25
85
-
-
30
100
-
-
37
125
45
150
55
180
75
250
90
312
110
360
150
480
Disjoncteurs
Circuit Breaker
Type
Type
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS160N/H/L-MA
NS160N/H/L-MA
NS250N/H/L-MA
NS400H/L-MA
NS400H/L-MA
NS630H/L-MA
NS630H/L-MA
Cal (A)
Rat (A)
2,5
6,3
6,3
12,5
12,5
12,5
25
25
50
50
50
100
100
100
100
150
150
220
320
320
500
500
Ancienne gamme
Old range
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
Contacteurs
Contactor
Type
Type
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D12
2 x LC1-D18
2 x LC1-D25
2 x LC1-D32
2 x LC1-D40
2 x LC1-D65
2 x LC1-D65
2 x LC1-D80
2 x LC1-D95
2 x LC1-D115
2 x LC1-F115
2 x LC1-D150
2 x LC1-F150
2 x LC1-F185
2 x LC1-F265
2 x LC1-F330
2 x LC1-F400
2 x LC1-F500
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D1322
17...25
LR2-D3353
23...32
LR2-D3357
37...50
LR9-D5357
30...50
LR2-D3357
37...50
LR9-D5357
30...50
LR2-D3359
48...65
LR9-D5363
48...80
LR2-D3363
63...80
LR9-D5363
48...80
LR2-D3365
80...93
LR9-D5367
60...100
LR9-D5367
60...100
LR9-F5367
60...10
LR9-D5369
90...150
LR9-F5369
90...150
LR9-F5371
132...220
LR9-F7375
200...330
LR9-F7375
200...330
LR9-F7379
300...500
LR9-F7379
300...500
Nb modules
Nbr of modules
Mf
Mw
3
6
3
6
3
6
3
6
3
6
3
6
3
6
6
6
6
6
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
9
12
9
**
9
12
9
**
12
**
16
**
16
**
16
**
16
**
** Impossible in Mw type
311
Anex 01
Appendix 01
Compact NS100-630z-MA
380 V
Type de coordination: 1
Coordination type: 1
2 sens de marche
Reverse
Performance de coupure / Breaking characteristics
Compact NS
N
H
L
NS100z-MA
25kA
70kA
130kA
NS160/250z-MA
35kA
70kA
130kA
70kA
130kA
NS400/630z-MA
Puissance Moteur
Power motor
P (kW)
I (A)
0,37
1,2
0,55
1,6
0,75
2
1,1
2,8
1,5
3,7
2,2
5
3
6,6
4
8,5
5,5
11,5
7,5
15,5
11
22
15
30
18,5
37
Disjoncteurs
Circuit Breaker
Type
Type
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
Cal (A)
Rat (A)
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
12,5
25
25
50
50
Contacteurs
Contactor
Type
Type
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D12
2 x LC1-D18
2 x LC1-D25
2 x LC1-D32
2 x LC1-D40
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1306
1...1,6
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D1322
17...25
LR2-D3353
23...32
LR2-D3357
37...50
-
-
LR9-D5357
30...50
Nb modules
Nbr of modules
-
-
-
22
44
NS100N/H/L-MA
50
2 x LC1-D50
LR2-D3357
37...50
6
9
-
-
-
-
-
LR9-D5357
30...50
6
9
30
59
NS100N/H/L-MA
50
2 x LC1-D65
LR2-D3357
37...50
6
9
-
-
-
-
-
LR9-D5357
30...50
6
9
37
72
NS100N/H/L-MA
100
2 x LC1-D80
LR2-D3363
63...80
6
9
-
-
-
-
-
LR9-D5363
48...80
6
9
45
85
NS100N/H/L-MA
100
2 x LC1-D95
LR2-D3365
80...93
6
9
-
-
-
-
-
LR9-D5367
60...100
6
9
55
105
NS160N/H/L-MA
150
2 x LC1-D150
LR9-D5369
90...150
9
12
75
140
NS160N/H/L-MA
150
2 x LC1-F150
LR9-F5369
90...150
9
**
Mf
Mw
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
6
6
6
6
6
9
6
9
90
170
NS250N/H/L-MA
220
2 x LC1-F185
LR9-F5371
132...220
12
**
110
210
NS250N/H/L-MA
220
2 x LC1-F225
LR9-F5371
132...220
12
**
132
250
NS400H/L-MA
320
2 x LC1-F265
LR9-F7375
200...330
16
**
160
300
NS400H/L-MA
320
2 x LC1-F330
LR9-F7375
200...330
16
**
200
380
NS630H/L-MA
500
2 x LC1-F400
LR9-F7379
300...500
16
**
220
420
NS630H/L-MA
500
2 x LC1-F500
LR9-F7379
300...500
16
**
250
480
NS630H/L-MA
500
2 x LC1-F500
LR9-F7379
300...500
16
**
Ancienne gamme
Old range
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
** Impossible in Mw type
312
Anex 01
Appendix 01
Compact NS100-630z-MA
415 V
Type de coordination: 1
Coordination type: 1
2 sens de marche
Reverse
Performance de coupure / Breaking characteristics
Compact NS
N
H
L
NS100z-MA
25kA
70kA
130kA
NS160/250z-MA
35kA
70kA
130kA
70kA
130kA
NS400/630z-MA
Puissance Moteur
Power motor
P (kW)
I (A)
9
17
11
21
15
28
Disjoncteurs
Circuit Breaker
Type
Type
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
22
40
NS100N/H/L-MA
50
2 x LC1-D40
LR2-D3357
37...50
6
9
-
-
-
-
-
LR9-D5357
30...50
6
9
25
47
NS100N/H/L-MA
50
2 x LC1-D50
LR2-D3357
37...50
6
9
-
-
-
-
-
LR9-D5357
30...50
6
9
30
55
NS100N/H/L-MA
50
2 x LC1-D65
LR2-D3357
37...50
6
9
-
-
-
-
-
LR9-D5357
30...50
6
9
37
72
NS100N/H/L-MA
100
2 x LC1-D80
LR2-D3363
63...80
6
9
45
80
NS100N/H/L-MA
100
2 x LC1-D80
LR9-D5363
48...80
6
9
55
100
NS100N/H/L-MA
100
2 x LC1-D115
LR9-D5367
60...100
9
12
-
-
-
-
2 x LC1-F115
LR9-F5367
60...100
9
**
75
135
NS160N/H/L-MA
150
2 x LC1-D150
LR9-D5369
90...150
9
12
-
-
-
-
2 x LC1-F150
LR9-F5369
90...150
9
**
0,37
1,1
0,55
1,5
0,75
1,8
1,1
2,5
1,5
3,5
2,2
4,8
3
6,5
4
8,2
5,5
11
7,5
14
Cal (A)
Rat (A)
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
12,5
25
25
25
50
Contacteurs
Contactor
Type
Type
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D12
2 x LC1-D18
2 x LC1-D18
2 x LC1-D25
2 x LC1-D32
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1306
1...1,6
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D1321
12...18
LR2-D1322
17...25
LR2-D3353
23...32
Nb modules
Nbr of modules
Mf
Mw
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
6
6
6
6
90
160
NS250N/H/L-MA
220
2 x LC1-F185
LR9-F5371
132...220
12
**
110
200
NS250N/H/L-MA
220
2 x LC1-F225
LR9-F5371
132...220
12
**
132
230
NS400H/L-MA
320
2 x LC1-F265
LR9-F7375
200...330
16
**
160
270
NS400H/L-MA
320
2 x LC1-F330
LR9-F7375
200...330
16
**
220
380
NS630H/L-MA
500
2 x LC1-F400
LR9-F7379
300...500
16
**
250
430
NS630H/L-MA
500
2 x LC1-F500
LR9-F7379
300...500
16
**
Ancienne gamme
Old range
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
** Impossible in Mw type
313
Anex 01
Appendix 01
Compact NS100-630z-MA
440 V (1)
Type de coordination: 1
Coordination type: 1
2 sens de marche
Reverse
Performance de coupure / Breaking characteristics
Compact NS
N
H
L
NS100z-MA
25kA
65kA
130kA
NS160/250z-MA
35kA
65kA
130kA
65kA
130kA
NS400/630z-MA
Puissance Moteur
Power motor
P (kW)
I (A)
9
16,9
11
20,1
15
26,5
Disjoncteurs
Circuit Breaker
Type
Type
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
22
39
NS100N/H/L-MA
50
2 x LC1-D40
LR2-D3357
37...50
6
9
-
-
-
-
-
LR9-D5357
30...50
6
9
30
51,5
NS100N/H/L-MA
50
2 x LC1-D65
LR2-D3357
37...50
6
9
-
-
-
-
-
LR9-D5357
30...50
6
9
37
64
NS100N/H/L-MA
100
2 x LC1-D65
LR2-D3359
48...65
6
9
-
-
-
-
-
LR9-D5363
48...80
6
9
45
76
NS100N/H/L-MA
100
2 x LC1-D80
LR2-D3363
63...80
6
9
-
-
-
-
-
LR9-D5363
48...80
6
9
55
96
NS100N/H/L-MA
100
2 x LC1-D115
LR9-D5367
60...100
9
12
-
-
-
-
2 x LC1-F115
LR9-F5367
60...100
9
**
75
124
NS160N/H/L-MA
150
2 x LC1-D150
LR9-D5369
90...150
9
12
-
-
-
-
2 x LC1-F150
LR9-F5369
90...150
9
**
0,37
1
0,55
1,4
0,75
1,7
1,1
2,4
1,5
3,1
2,2
4,5
3
5,8
4
7,9
5,5
10,4
7,5
13,7
Cal (A)
Rat (A)
2,5
2,5
2,5
2,5
6,3
6,3
12,5
12,5
12,5
25
25
25
50
Contacteurs
Contactor
Type
Type
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D12
2 x LC1-D18
2 x LC1-D18
2 x LC1-D25
2 x LC1-D32
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1306
1...1,6
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D1321
12...18
LR2-D1322
17...25
LR2-D3353
23...32
Nb modules
Nbr of modules
Mf
Mw
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
6
6
6
6
90
156
NS250N/H/L-MA
220
2 x LC1-F185
LR9-F5371
132...220
12
**
110
180
NS250N/H/L-MA
220
2 x LC1-F185
LR9-F5371
132...220
12
**
132
215
NS250N/H/L-MA
220
2 x LC1-F225
LR9-F5371
132...220
12
**
160
256
NS400H/L-MA
320
2 x LC1-F265
LR9-F7375
200...330
16
**
220
360
NS630H/L-MA
500
2 x LC1-F400
LR9-F7379
300...500
16
**
250
401
NS630H/L-MA
500
2 x LC1-F500
LR9-F7379
300...500
16
**
300
480
NS630H/L-MA
500
2 x LC1-F630
LR9-F7381
380...630
20
**
Ancienne gamme
Old range
(1) Applicable pour 480 V NEMA
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
(1) Valid for 480 V NEMA
** Impossible in Mw type
314
Anex 01
Appendix 01
Compact NS100-630z-MA
500/525 V
Type de coordination: 1
Coordination type: 1
2 sens de marche
Reverse
Performance de coupure / Breaking characteristics
Compact NS
H
L
NS100z-MA
50/35kA
70kA
NS160/250z-MA
50/35kA
70kA
NS400/630z-MA
50/35kA
70kA
Puissance Moteur
Power motor
P (kW)
I (A)
0,55
1,2
0,75
1,5
1,1
2
1,5
2,6
3
5
4
6,5
5,5
9
7,5
12
9
14
10
15
11
18,4
18,5
28,5
22
33
Disjoncteurs
Circuit Breaker
Type
Type
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
Cal (A)
Rat (A)
2,5
2,5
2,5
6,3
6,3
12,5
12,5
12,5
25
25
25
50
50
Contacteurs
Contactor
Type
Type
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D12
2 x LC1-D18
2 x LC1-D18
2 x LC1-D25
2 x LC1-D32
2 x LC1-D40
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1306
1...1,6
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D1321
12...18
LR2-D1322
17...25
LR2-D3353
23...32
LR2-D3355
30...40
-
-
LR9-D5357
30...50
-
-
-
30
45
NS100N/H/L-MA
50
2 x LC1-D50
LR2-D3357
37...50
6
9
-
-
-
-
-
LR9-D5357
30...50
6
9
37
55
NS100N/H/L-MA
100
2 x LC1-D65
LR2-D3359
48...65
6
9
-
-
-
-
-
LR9-D5363
48...80
6
9
55
80
NS100N/H/L-MA
100
2 x LC1-D80
LR2-D3363
63...80
6
9
-
-
-
-
-
LR9-D5363
48...80
6
9
75
110
NS160N/H/L-MA
150
2 x LC1-D150
LR9-D5369
90...150
9
12
90
130
NS160N/H/L-MA
150
2 x LC1-F150
LR9-F5369
90...150
9
**
110
156
NS250N/H/L-MA
220
2 x LC1-F185
LR9-F5371
132...220
12
**
132
190
NS250N/H/L-MA
220
2 x LC1-F265
LR9-F5371
132...220
12
**
160
228
NS400H/L-MA
320
2 x LC1-F265
LR9-F7375
200...330
16
**
200
281
NS400H/L-MA
320
2 x LC1-F330
LR9-F7375
200...330
16
**
220
310
NS630H/L-MA
500
2 x LC1-F400
LR9-F7379
300...500
16
**
315
445
NS630H/L-MA
500
2 x LC1-F500
LR9-F7379
300...500
16
**
335
460
NS630H/L-MA
500
2 x LC1-F500
LR9-F7379
300...500
16
**
Ancienne gamme
Old range
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
Nb modules
Nbr of modules
Mf
Mw
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
6
6
6
6
6
9
6
9
** Impossible in Mw type
315
Anex 01
Appendix 01
Compact NS100-630z-MA
660/690 V (1)
Type de coordination: 1
Coordination type: 1
2 sens de marche
Reverse
Performance de coupure / Breaking characteristics
Compact NS
N
NS100z-MA
8kA
H
NS160/250z-MA
10kA
NS400/630z-MA
20kA
Puissance Moteur
Power motor
P (kW)
I (A)
7,5
8,9
10
11,5
-
-
15
17
18,5
21,3
30
34,6
Disjoncteurs
Circuit Breaker
Type
Type
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
NS100N/H/L-MA
-
-
-
33
39
NS100N/H/L-MA
50
2 x LC1-D50
LR2-D3357
37...50
6
9
-
-
-
-
-
LR9-D5357
30...50
6
9
37
42
NS100N/H/L-MA
50
2 x LC1-D65
LR2-D3357
37...50
6
9
-
-
-
-
-
LR9-D5357
30...50
6
9
45
49
NS100N/H/L-MA
100
2 x LC1-D80
LR2-D3357
37...50
6
9
-
-
-
-
-
LR9-D5363
48...80
6
9
55
60
NS100N/H/L-MA
100
2 x LC1-D115
LR9-D5363
48...80
9
12
-
-
-
-
2 x LC1-F115
LR9-F5363
48...80
9
**
75
80
NS100N/H/L-MA
100
2 x LC1-D115
LR9-D5367
60...100
9
12
**
0,75
1.2
1
1,5
1,5
2
2,2
2,8
3
3,8
4
4,9
5,5
6,6
Cal (A)
Rat (A)
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
25
25
50
50
Contacteurs
Contactor
Type
Type
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D12
2 x LC1-D18
2 x LC1-D25
2 x LC1-D25
2 x LC1-D32
2 x LC1-D40
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1306
1...1,6
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1322
17...25
LR2-D1321
18...12
LR2-D1322
17...25
LR2-D3355
30...40
-
-
LR9-D5357
30...50
Nb modules
Nbr of modules
Mf
Mw
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
3
6
6
6
6
6
6
6
6
9
6
9
-
-
-
-
2 x LC1-F115
LR9-F5367
60...100
9
90
100
NS160N/H/L-MA
150
2 x LC1-D150
LR9-D5369
90...150
9
12
110
120
NS160N/H/L-MA
150
2 x LC1-F150
LR9-F5369
90...150
9
**
132
140
NS250N/H/L-MA
220
2 x LC1-F265
LR9-F5371
132...220
12
**
160
175
NS250N/H/L-MA
220
2 x LC1-F265
LR9-F5371
132...220
12
**
200
220
NS400H/L-MA
320
2 x LC1-F330
LR9-F7375
200...330
16
**
220
240
NS400H/L-MA
320
2 x LC1-F330
LR9-F7375
200...330
16
**
250
270
NS630H/L-MA
500
2 x LC1-F400
LR9-F7375
200...300
16
**
335
335
NS630H/L-MA
500
2 x LC1-F500
LR9-F7379
300...500
16
**
375
400
NS630H/L-MA
500
2 x LC1-F630
LR9-F7381
380...630
20
**
450
480
NS630H/L-MA
500
2 x LC1-F630
LR9-F7381
380...630
20
**
Ancienne gamme
Old range
(1) Confirmer le nb de modules pour
660/690 V
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
(1) Confirm number of modules in function of
this voltage level 660/690 V
** Impossible in Mw type
316
Anex 01
Appendix 01
Compact NS100-630z-MA
6.1.1.16.
Type de coordination: 2 - - - - - - - - - - - - - - - -2 sens de marche
Coordination type: 2 - - - - - - - - - - - - - - - - - - -Reverse
Démarrage: normal
Start-up: Normal
Compact NS100-630z-MA
220/240 V
Type de coordination: 2
Coordination type: 2
2 sens de marche
Reverse
Performance de coupure / Breaking characteristics
Compact NS
N
H
L
NS100z-MA
85kA
100kA
130kA
NS160/250z-MA
85kA
100kA
130kA
100kA
130kA
NS400/630z-MA
Puissance Moteur
Power motor
P (kW)
I (A)
0,18
0,25
0,37
0,55
0,75
1,1
1,5
2,2
3
4
5,5
6,3
7,5
10
11
15
18,5
22
30
37
45
55
75
90
110
132
150
1,2
1,5
2
2,8
3,5
5
6,5
9
12
15
21
24
28
36
39
52
63
75
100
125
150
180
250
300
360
430
460
Disjoncteurs
Circuit Breaker
Type
Type
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS160-MA
NS160-MA
NS250-MA
NS400-MA
NS400-MA
NS400-MA
NS630-MA
NS630-MA
NS630-MA
Cal (A)
Rat (A)
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
12,5
25
25
25
50
50
50
100
100
100
100
150
150
220
320
320
320
500
500
500
Ancienne gamme
Old range
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
Contacteurs
Contactor
Type
Type
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D40
2 x LC1-D40
2 x LC1-D40
2 x LC1-D40
2 x LC1-D40
2 x LC1-D40
2 x LC1-D40
2 x LC1-D40
2 x LC1-D40
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-D115
2 x LC1-F115
2 x LC1-D150
2 x LC1-F150
2 x LC1-D150
2 x LC1-F150
2 x LC1-F185
2 x LC1-F265
2 x LC1-F265
2 x LC1-F330
2 x LC1-F400
2 x LC1-F500
2 x LC1-F500
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D3322
17...25
LR2-D3322
17...25
LR2-D3353
23...32
LR9-D5357
30...50
LR2-D3355
30...40
LR9-D5357
30...50
LR2-D3355
30...40
LR9-D5357
30...50
LR2-D3359
48...65
LR9-D5363
48...80
LR2-D3359
48...65
LR9-D5363
48...80
LR2-D3363
63...80
LR9-D5363
48...80
LR9-D5367
60...100
LR9-F5367
LR9-D5369
90...150
LR9-F5369
LR9-D5369
90...150
LR9-F5369
LR9-F5371
132...220
LR9-F7375
200...330
LR9-F7375
200...330
LR9-F7379
300...500
LR9-F7379
300...500
LR9-F7379
300...500
Nb modules
Nbr of modules
Mf
Mw
3
3
3
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
9
9
9
9
9
9
12
16
16
16
16
16
16
6
6
6
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
12
**
12
**
12
**
**
**
**
**
**
**
**
** Impossible in Mw type
317
Anex 01
Appendix 01
Compact NS100-630z-MA
380/415 V
Type de coordination: 2
Coordination type: 2
2 sens de marche
Reverse
Performance de coupure / Breaking characteristics
Compact NS
N
H
L
NS100z-MA
25kA
70kA
130kA
NS160/250z-MA
35kA
70kA
130kA
70kA
130kA
NS400/630z-MA
Puissance Moteur
Power motor
P (kW)
I (A)
380V
0,37
1,2
0,55
1,6
0,75
2
1,1
2,8
1,5
3,7
2,2
5,3
3
7
4
9
5,5
12
7,5
16
10
21
11
23
15
30
Disjoncteurs
Circuit Breaker
Type
Type
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
Cal (A)
Rat (A)
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
12,5
25
25
25
50
Contacteurs
Contactor
Type
Type
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D40
2 x LC1-D40
2 x LC1-D40
2 x LC1-D40
2 x LC1-D40
2 x LC1-D40
2 x LC1-D40
2 x LC1-D40
2 x LC1-D40
2 x LC1-D80
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D3322
17...25
LR2-D3322
17...25
LR2-D3353
23...32
-
-
-
-
-
LR9-D5357
18,5
37
-
-
NS100-MA
50
2 x LC1-D80
LR2-D3355
30...40
6
9
-
-
-
LR9-D5357
30...50
6
9
22
-
43
NS100-MA
50
2 x LC1-D80
LR2-D3357
37...50
6
9
-
-
-
-
LR9-D5357
30...50
6
9
30
59
NS100-MA
100
2 x LC1-D80
LR2-D3359
48...65
6
9
-
-
-
-
-
LR9-D5363
48...80
6
9
30...50
Nb modules
Nbr of modules
Mf
Mw
3
6
3
6
3
6
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
37
72
NS100-MA
100
2 x LC1-D80
LR2-D3363
63...80
6
9
-
-
-
-
-
LR9-D5363
48...80
6
9
45
85
NS100-MA
100
2 x LC1-D115
LR9-D5367
60...100
9
12
-
-
-
-
2 x LC1-F115
LR9-F5367
60...100
9
**
55
105
NS160-MA
150
2 x LC1-D115
LR9-D5369
90...150
9
12
-
-
-
-
2 x LC1-F115
LR9-F5369
90...150
9
**
75
140
NS160-MA
150
2 x LC1-D150
LR9-D5369
90...150
9
12
**
-
-
-
-
2 x LC1-F150
LR9-F5369
90...150
9
90
170
NS250-MA
220
2 x LC1-F185
LR9-F5371
132...220
12
**
110
210
NS250-MA
220
2 x LC1-F225
LR9-F5371
132...220
12
**
-
-
NS400-MA
320
2 x LC1-F265
LR9-F5371
132...220
16
**
132
250
NS400-MA
320
2 x LC1-F265
LR9-F7375
200...330
16
**
160
300
NS400-MA
320
2 x LC1-F330
LR9-F7375
200...330
16
**
200
380
NS630-MA
500
2 x LC1-F400
LR9-F7379
300...500
16
**
220
420
NS630-MA
500
2 x LC1-F500
LR9-F7379
300...500
16
**
250
480
NS630-MA
500þ
2 x LC1-F500
LR9-F7379
300...500
16
**
Ancienne gamme
Old range
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
** Impossible in Mw type
318
Anex 01
Appendix 01
Compact NS100-630z-MA
440 V (1)
Type de coordination: 2
Coordination type: 2
2 sens de marche
Reverse
Performance de coupure / Breaking characteristics
Compact NS
N
H
L
NS100z-MA
25kA
65kA
130kA
NS160/250z-MA
35kA
65kA
130kA
65kA
130kA
NS400/630z-MA
Puissance Moteur
Power motor
P (kW)
I (A)
10
19
11
20
15
26.5
Disjoncteurs
Circuit Breaker
Type
Type
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
18.5
33
NS100-MA
50
2 x LC1-D80
LR2-D3355
30...40
6
9
-
-
-
-
-
LR9-D5357
30...50
6
9
22
39
NS100-MA
50
2 x LC1-D80
LR2-D3355
30...40
6
9
-
-
-
-
-
LR9-D5357
30...50
6
9
30
52
NS100-MA
100
2 x LC1-D80
LR2-D3359
48...65
6
9
-
-
-
-
-
LR9-D5363
48...80
6
9
37
63
NS100-MA
100
2 x LC1-D80
LR2-D3359
48...65
6
9
-
-
-
-
-
LR9-D5363
48...80
6
9
45
76
NS100-MA
100
2 x LC1-D80
LR2-D3363
63...80
6
9
-
-
-
-
-
LR9-D5363
48...80
6
9
55
90
NS100-MA
100
2 x LC1-D115
LR9-D5367
60...100
9
12
-
-
-
-
2 x LC1-F115
LR9-F5367
60...100
9
**
75
125
NS160-MA
150
2 x LC1-D150
LR9-D5369
90...150
9
12
-
-
-
-
2 x LC1-F150
LR9-F5369
90...150
9
**
90
140
NS160-MA
150
2 x LC1-D150
LR9-D5369
90...150
9
12
0.37
1
0.55
1.4
0.75
1.7
1.1
2.4
1.5
3.1
2.2
4.5
3
5.8
4
8
5.5
10.5
7.5
13.7
Cal (A)
Rat (A)
2.5
2.5
2.5
2.5
6.3
6.3
6.3
12.5
12.5
25
25
25
50
Contacteurs
Contactor
Type
Type
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D40
2 x LC1-D40
2 x LC1-D40
2 x LC1-D40
2 x LC1-D40
2 x LC1-D40
2 x LC1-D40
2 x LC1-D40
2 x LC1-D80
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1306
1...1,6
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D3322
17...25
LR2-D3322
17...25
LR2-D3353
23...32
Nb modules
Nbr of modules
Mf
Mw
3
6
3
6
3
6
3
6
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
-
-
-
-
2 x LC1-F150
LR9-F5369
90...150
9
**
110
178
NS250-MA
220
2 x LC1-F185
LR9-F5371
132...220
12
**
132
210
NS250-MA
220
2 x LC1-F225
LR9-F5371
132...220
12
**
-
-
NS400-MA
320
2 x LC1-F265
LR9-F5371
132...220
16
**
160
256
NS400-MA
320
2 x LC1-F265
LR9-F7375
200...330
16
**
200
310
NS400-MA
320
2 x LC1-F330
LR9-F7375
200...330
16
**
220
353
NS630-MA
500
2 x LC1-F400
LR9-F7379
300...500
16
**
250
400
NS630-MA
500
2 x LC1-F400
LR9-F7379
300...500
16
**
300
460
NS630-MA
500
2 x LC1-F500
LR9-F7379
300...500
16
**
Ancienne gamme
Old range
(1) Applicable pour 480 V NEMA
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
(1) Valid for 480 V NEMA
** Impossible in Mw type
319
Anex 01
Appendix 01
Compact NS100-630z-MA
500/525 V
Type de coordination: 2
Coordination type: 2
2 sens de marche
Reverse
Performance de coupure / Breaking characteristics
Compact NS
H
L
NS100z-MA
50/35kA
70kA
NS160/250z-MA
50/35kA
70kA
NS400/630z-MA
50/35kA
70kA
Puissance Moteur
Power motor
P (kW)
I (A)
0,55
1,2
0,75
1,5
1,1
2
1,5
2,8
2,2
3,8
3
5
4
6,5
5,5
9
7,5
12
10
15
11
18,4
15
23
18,5
28,5
Disjoncteurs
Circuit Breaker
Type
Type
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
Cal (A)
Rat (A)
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
12,5
25
25
25
50
Contacteurs
Contactor
Type
Type
2 x LC1-D09
2 x LC1-D09
2 x LC1-D09
2 x LC1-D40
2 x LC1-D40
2 x LC1-D40
2 x LC1-D40
2 x LC1-D40
2 x LC1-D40
2 x LC1-D40
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1306
1...1,6
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D3322
17...25
LR2-D3322
17...25
LR2-D3353
23...32
Nb modules
Nbr of modules
22
33
NS100-MA
50
2 x LC1-D80
LR2-D3355
23...32
6
9
-
-
-
-
2 x LC1-D115
LR9-D5357
30...50
9
12
**
Mf
Mw
3
6
3
6
3
6
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
-
-
-
-
2 x LC1-F115
LR9-F5357
30...50
9
30
45
NS100-MA
50
2 x LC1-D80
LR2-D3357
30...40
6
9
-
-
-
-
2 x LC1-D115
LR9-D5357
30...50
9
12
**
-
-
-
-
2 x LC1-F115
LR9-F5357
30...50
9
37
55
NS100-MA
100
2 x LC1-D80
LR2-D3359
48...65
6
9
-
-
-
-
2 x LC1-D115
LR9-D5363
48...80
9
12
-
-
-
-
2 x LC1-F115
LR9-F5363
48...80
9
**
45
65
NS100-MA
100
2 x LC1-D115
LR9-D5363
48...80
9
12
2 x LC1-F115
LR9-F5363
48...80
9
**
55
75
NS100-MA
100
2 x LC1-D115
LR9-D5367
60...100
9
12
**
-
-
-
-
2 x LC1-F115
LR9-F5367
60...100
9
75
105
NS160-MA
150
2 x LC1-D115
LR9-D5369
90...150
9
12
-
-
-
-
2 x LC1-F115
LR9-F5369
90...150
9
**
90
130
NS160-MA
150
2 x LC1-D150
LR9-D5369
90...150
9
12
-
-
-
-
2 x LC1-F150
LR9-F5369
90...150
9
**
110
156
NS250-MA
220
2 x LC1-F185
LR9-F5371
132...220
12
**
132
187
NS250-MA
220
2 x LC1-F265
LR9-F5371
132...220
12
**
160
220
NS400-MA
320
2 x LC1-F400
LR9-F7375
200...330
16
**
200
280
NS400-MA
320
2 x LC1-F400
LR9-F7375
200...330
16
**
220
310
NS630-MA
500
2 x LC1-F400
LR9-F7379
300...500
16
**
250
360
NS630-MA
500þ
2 x LC1-F500
LR9-F7379
300...500
16
**
315
445
NS630-MA
500
2 x LC1-F500
LR9-F7379
300...500
16
**
Ancienne gamme
Old range
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
** Impossible in Mw type
320
Anex 01
Appendix 01
Compact NS100-630z-MA
6.1.1.17.
Type de coordination: 1 - - - - - - - - - - - - - - - -Etoile / Triangle (Y/∆)
Coordination type: 1 - - - - - - - - - - - - - - - - - - -STAR / DELTA (Y/∆)
Démarrage: Normal
Start-up: Normal
Compact NS100-630z-MA
220/230 V
Type de coordination: 1
Coordination type: 1
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Performance de coupure / Breaking characteristics
Compact NS
N
H
L
NS100z-MA
85kA
100kA
130kA
NS160/250z-MA
85kA
100kA
130kA
100kA
130kA
NS400/630z-MA
Puissance Moteur
Power motor
P (kW)
I (A)
0,55
2,8
1,1
4,4
1,5
6,1
2,2
8,7
3
11,5
4
14,5
Disjoncteurs
Circuit Breaker
Type
Type
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
Cal (A)
Rat (A)
6,3
6,3
12,5
12,5
12,5
25
Contacteurs
Contactor
Type
Type
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
Nb modules
Nbr of modules
5,5
20
NS100N/H/L MA
25
3 x LC1-D12
LR2-D1316
9...13
6
6
7,5
28
NS100N/H/L MA
50
3 x LC1-D18
LR2-D1321
12...18
6
6
11
39
NS100N/H/L MA
50
3 x LC1-D18
LR2-D1322
17...25
6
6
15
52
NS100N/H/L MA
100
3 x LC1-D32
LR2-D3353
23...32
6
6
18,5
64
NS100N/H/L MA
100
3 x LC1-D40
LR2-D3355
30...40
6
9
22
75
NS100N/H/L MA
100
3 x LC1-D50
LR2-D3357
37...50
6
9
25
85
NS100N/H/L MA
100
3 x LC1-D50
LR2-D3357
37...50
6
9
30
100
NS100N/H/L MA
100
3 x LC1-D50
LR2-D3359
48...65
6
9
37
125
NS160N/H/L MA
150
3 x LC1-D80
LR2-D3363
63...80
6
9
45
150
NS160N/H/L MA
150
3 x LC1-D115
LR9-D5367
60...100
12
**
-
-
-
-
3 x LC1-F115
LR9-F5367
60...100
12
**
55
180
NS250N/H/L MA
220
3 x LC1-D115
LR9-D5369
90...150
12
**
-
-
-
-
3 x LC1-F115
LR9-F5369
90...150
12
**
75
250
NS400H/L MA
320
3 x LC1-D150
LR9-D5369
90...150
12
**
-
-
-
-
3 x LC1-F150
LR9-F5369
90...150
12
**
Mf
Mw
6
6
6
6
6
6
6
6
6
6
6
6
90
312
NS400H/L MA
320
3 x LC1-F185
LR9-F5371
132...220
16
**
110
360
NS630H/L MA
500
3 x LC1-F265
LR9-F7375
200...330
20
**
150
480
NS630H/L MA
500
3 x LC1-F330
LR9-F7375
200...330
20
**
Ancienne gamme
Old range
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
** Impossible in Mw type
321
Anex 01
Appendix 01
Compact NS100-630z-MA
380 V
Type de coordination: 1
Coordination type: 1
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Performance de coupure / Breaking characteristics
Compact NS
N
H
L
NS100z-MA
25kA
70kA
130kA
NS160/250z-MA
35kA
70kA
130kA
70kA
130kA
NS400/630z-MA
Puissance Moteur
Power motor
P (kW)
I (A)
1,5
3,7
2,2
5
3
6,6
4
8,5
5,5
11,5
7,5
15,5
11
22
15
30
18,5
37
22
44
30
59
37
72
45
85
55
105
75
140
-
-
-
-
90
170
-
-
110
210
-
-
132
250
-
-
160
300
200
380
220
420
250
480
Disjoncteurs
Circuit Breaker
Type
Type
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS160N/H/L MA
NS160N/H/L MA
NS250N/H/L MA
NS250N/H/L MA
NS400H/L MA
NS400H/L MA
NS630H/L MA
NS630H/L MA
NS630H/L MA
Cal (A)
Rat (A)
6,3
6,3
12,5
12,5
12,5
25
25
50
50
100
100
100
100
150
150
220
220
320
320
500
500
500
Contacteurs
Contactor
Type
Type
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D12
3 x LC1-D18
3 x LC1-D18
3 x LC1-D32
3 x LC1-D40
3 x LC1-D40
3 x LC1-D50
3 x LC1-D80
3 x LC1-D80
3 x LC1-D115
3 x LC1-F115
3 x LC1-D115
3 x LC1-F115
3 x LC1-D115
3 x LC1-F115
3 x LC1-D150
3 x LC1-F150
3 x LC1F-185
3 x LC1-F265
3 x LC1-F265
3 x LC1-F330
Ancienne gamme
Old range
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D1322
17...25
LR2-D3353
23...32
LR2-D3355
30...40
LR2-D3357
37...50
LR2-D3357
37...50
LR2-D3359
48...65
LR2-D3363
63...80
LR9-D5367
60...100
LR9-F5367
60...100
LR9-D5367
60...100
LR9-F5367
60...100
LR9-D5369
90...150
LR9-F5369
90...150
LR9-D5369
90...150
LR9-F5369
90...150
LR9-F5371
132...220
LR9-F7375
200...330
LR9-F7375
200...330
LR9-F7375
200...330
Nb modules
Nbr of modules
Mf
Mw
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
9
6
9
6
9
6
9
6
9
12
**
12
**
12
**
12
**
12
**
12
**
12
**
12
**
16
**
20
**
20
**
20
**
** Impossible in Mw type
322
Anex 01
Appendix 01
Compact NS100-630z-MA
415 V
Type de coordination: 1
Coordination type: 1
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Performance de coupure / Breaking characteristics
Compact NS
N
H
L
NS100z-MA
25kA
70kA
130kA
NS160/250z-MA
35kA
70kA
130kA
70kA
130kA
NS400/630z-MA
Puissance Moteur
Power motor
P (kW)
I (A)
1,5
3,5
2,2
4,8
3
6,5
4
8,2
5,5
11
7,5
14
9
17
11
21
15
28
22
40
25
47
30
55
37
66
45
80
55
100
75
135
90
160
-
-
110
200
-
-
132
230
-
-
160
270
220
380
250
430
Disjoncteurs
Circuit Breaker
Type
Type
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS160N/H/L MA
NS250N/H/L MA
NS250N/H/L MA
NS400H/L MA
NS400H/L MA
NS630H/L MA
NS630H/L MA
Cal (A)
Rat (A)
6,3
6,3
12,5
12,5
12,5
25
25
25
50
50
100
100
100
100
100
150
220
220
320
320
500
500
Contacteurs
Contactor
Type
Type
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D12
3 x LC1-D12
3 x LC1-D18
3 x LC1-D18
3 x LC1-D32
3 x LC1-D32
3 x LC1-D40
3 x LC1-D50
3 x LC1-D50
3 x LC1-D80
3 x LC1-D115
3 x LC1-F115
3 x LC1-D115
3 x LC1-F115
3 x LC1-D150
3 x LC1-F150
3 x LC1F-185
3 x LC1-F265
3 x LC1-F330
Ancienne gamme
Old range
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D1322
17...25
LR2-D3353
23...32
LR2-D3355
30...40
LR2-D3355
30...40
LR2-D3357
37...50
LR2-D3359
48...65
LR2-D3363
63...80
LR9-D5367
60...100
LR9-F5367
60...100
LR9-D5369
90...150
LR9-F5369
90...150
LR9-D5369
90...150
LR9-F5369
90...150
LR9-F5371
132...220
LR9-F7375
200...330
LR9-F7375
200...330
Nb modules
Nbr of modules
Mf
Mw
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
9
6
9
6
9
6
9
12
**
12
**
12
**
12
**
12
**
12
**
16
**
20
**
20
**
** Impossible in Mw type
323
Anex 01
Appendix 01
Compact NS100-630z-MA
440 V (1)
Type de coordination: 1
Coordination type: 1
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Performance de coupure / Breaking characteristics
Compact NS
N
H
L
NS100z-MA
25kA
65kA
130kA
NS160/250z-MA
35kA
65kA
130kA
65kA
130kA
NS400/630z-MA
Puissance Moteur
Power motor
P (kW)
I (A)
1,5
3,1
2,2
4,5
3
5,8
4
7,9
5,5
10,4
7,5
13,7
9
16,9
11
20,1
15
26,5
22
39
30
51,5
37
64
45
76
55
96
75
124
90
156
-
-
110
180
-
-
132
215
-
-
160
256
220
360
250
401
300
480
Disjoncteurs
Circuit Breaker
Type
Type
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS100N/H/L MA
NS160N/H/L MA
NS250N/H/L MA
NS250N/H/L MA
NS250N/H/L MA
NS400H/L MA
NS630H/L MA
NS630H/L MA
NS630H/L MA
Cal (A)
Rat (A)
6,3
6,3
12,5
12,5
12,5
25
25
25
50
50
100
100
100
100
150
220
220
220
320
500
500
500
Contacteurs
Contactor
Type
Type
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D12
3 x LC1-D12
3 x LC1-D18
3 x LC1-D18
3 x LC1-D32
3 x LC1-D40
3 x LC1-D50
3 x LC1-D50
3 x LC1-D80
3 x LC1-D115
3 x LC1-F115
3 x LC1-D115
3 x LC1-F115
3 x LC1-D150
3 x LC1-F150
3 x LC1F-185
3 x LC1-F265
3 x LC1-F265
3 x LC1-F330
Ancienne gamme
Old range
(1) Applicable pour 480 V NEMA
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D1322
17...25
LR2-D3353
23...32
LR2-D3355
30...40
LR2-D3357
37...50
LR2-D3359
48...65
LR2-D3363
63...80
LR9-D5367
60...100
LR9-F5367
60...100
LR9-D5369
90...150
LR9-F5369
90...150
LR9-D5369
90...150
LR9-F5369
90...150
LR9-F5371
132...220
LR9-F7375
200...330
LR9-F7375
200...330
LR9-F7375
200...330
Nb modules
Nbr of modules
Mf
Mw
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
9
6
9
6
9
6
9
12
**
12
**
12
**
12
**
12
**
12
**
16
**
20
**
20
**
20
**
(1) Valid for 480 V NEMA
** Impossible in Mw type
324
Anex 01
Appendix 01
Compact NS100-630z-MA
6.1.1.18.
Type de coordination: 2 - - - - - - - - - - - - - - - -Etoile / Triangle (Y/∆)
Coordination Type: 2 - - - - - - - - - - - - - - - - - -STAR / DELTA (Y/∆)
Démarrage: normal
Start-up: Normal
Compact NS100-630z-MA
220/240 V
Type de coordination: 2
Coordination type: 2
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Performance de coupure / Breaking characteristics
Compact NS
N
H
L
NS100z-MA
85kA
100kA
130kA
NS160/250z-MA
85kA
100kA
130kA
100kA
130kA
NS400/630z-MA
Puissance Moteur
Power motor
P (kW)
I (A)
0,18
0,25
0,37
0,55
0,75
1,1
1,5
2,2
3
4
5,5
6,3
7,5
10
11
15
18,5
22
30
37
45
55
75
90
110
132
150
1,2
1,5
2
2,8
3,5
5
6,5
9
12
15
21
24
28
36
39
52
63
75
100
125
150
180
250
300
360
430
460
Disjoncteurs
Circuit Breaker
Type
Type
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS160-MA
NS160-MA
NS250-MA
NS400-MA
NS400-MA
NS400-MA
NS630-MA
NS630-MA
NS630-MA
Cal (A)
Rat (A)
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
12,5
25
25
25
50
50
50
100
100
100
100
150
150
220
320
320
320
500
500
500
Ancienne gamme
Old range
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
Contacteurs
Contactor
Type
Type
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D40
3 x LC1-D40
3 x LC1-D40
3 x LC1-D40
3 x LC1-D40
3 x LC1-D40
3 x LC1-D40
3 x LC1-D40
3 x LC1-D40
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D115
3 x LC1-F115
3 x LC1-D150
3 x LC1-F150
3 x LC1-D150
3 x LC1-F150
3 x LC1-F185
3 x LC1-F265
3 x LC1-F265
3 x LC1-F330
3 x LC1-F400
3 x LC1-F500
3 x LC1-F500
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D3322
17...25
LR2-D3322
17...25
LR2-D3353
23...32
LR9-D5357
30...50
LR2-D3355
30...40
LR9-D5357
30...50
LR2-D3355
30...40
LR9-D5357
30...50
LR2-D3359
48...65
LR9-D5363
48...80
LR2-D3359
48...65
LR9-D5363
48...80
LR2-D3363
63...80
LR9-D5363
48...80
LR9-D5367
60...100
LR9-F5367
60...100
LR9-D5369
90...150
LR9-F5369
90...150
LR9-D5369
90...150
LR9-F5369
90...150
LR9-F5371
132...220
LR9-F5371
132...220
LR9-F7375
200...330
LR9-F7375
200...330
LR9-F7379
300...500
LR9-F7379
300...500
LR9-F7379
300...500
Nb modules
Nbr of modules
Mf
Mw
6
6
6
6
6
6
6
6
6
6
6
6
9
9
9
9
9
9
9
9
9
9
9
9
12
12
12
12
12
12
16
20
20
20
20
24
24
6
6
6
9
9
9
9
9
9
9
9
9
9
12
9
12
9
12
9
12
9
12
9
12
**
**
**
**
**
**
**
**
**
**
**
**
**
** Impossible in Mw type
325
Anex 01
Appendix 01
Compact NS100-630z-MA
380/415 V
Type de coordination: 2
Coordination type: 2
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Performance de coupure / Breaking characteristics
Compact NS
N
H
L
NS100z-MA
25kA
70kA
130kA
NS160/250z-MA
35kA
70kA
130kA
70kA
130kA
NS400/630z-MA
Puissance Moteur
Power motor
P (kW)
I (A)
0,37
1,2
0,55
1,6
0,75
2
1,1
2,8
1,5
3,7
2,2
5,3
3
7
4
9
5,5
12
7,5
16
10
21
11
23
15
30
-
-
18,5
37
-
-
22
43
-
-
30
59
-
-
37
72
-
-
45
85
-
-
55
105
-
-
75
140
-
-
90
170
110
210
-
-
132
250
160
300
200
380
220
420
250
480
Disjoncteurs
Circuit Breaker
Type
Type
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS160-MA
NS160-MA
NS250-MA
NS250-MA
NS400-MA
NS400-MA
NS400-MA
NS630-MA
NS630-MA
NS630-MA
Cal (A)
Rat (A)
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
12,5
25
25
25
50
50
50
100
100
100
150
150
220
220
320
320
320
500
500
500þ
Ancienne gamme
Old range
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
Contacteurs
Contactor
Type
Type
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D40
3 x LC1-D40
3 x LC1-D40
3 x LC1-D40
3 x LC1-D40
3 x LC1-D40
3 x LC1-D40
3 x LC1-D40
3 x LC1-D40
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D115
3 x LC1-F115
3 x LC1-D115
3 x LC1-F115
3 x LC1-D150
3 x LC1-F150
3 x LC1-F185
3 x LC1-F225
3 x LC1-F265
3 x LC1-F265
3 x LC1-F330
3 x LC1-F400
3 x LC1-F400
3 x LC1-F500
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D3322
17...25
LR2-D3322
17...25
LR2-D3353
23...32
LR9-D5357
30...50
LR2-D3355
30...40
LR9-D5357
30...50
LR2-D3357
37...50
LR9-D5357
30...50
LR2-D3359
48...65
LR9-D5363
48...80
LR2-D3363
63...80
LR9-D5363
48...80
LR9-D5367
60...100
LR9-F5367
60...100
LR9-D5369
90...150
LR9-F5369
90...150
LR9-D5369
90...150
LR9-F5369
90...150
LR9-F5371
132...220
LR9-F5371
132...220
LR9-F5371
132...220
LR9-F7375
200...330
LR9-F7375
200...330
LR9-F7379
300...500
LR9-F7379
300...500
LR9-F7379
300...500
Nb modules
Nbr of modules
Mf
Mw
6
6
6
6
6
6
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
9
9
9
12
9
9
9
12
9
9
9
12
9
9
9
12
9
9
9
12
12
**
12
**
12
**
12
**
12
**
12
**
16
**
16
**
20
**
20
**
20
**
20
**
20
**
24
**
** Impossible in Mw type
326
Anex 01
Appendix 01
Compact NS100-630z-MA
440 V (1)
Type de coordination: 2
Coordination type: 2
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Performance de coupure / Breaking characteristics
Compact NS
N
H
L
NS100z-MA
25kA
65kA
130kA
NS160/250z-MA
35kA
65kA
130kA
65kA
130kA
NS400/630z-MA
Puissance Moteur
Power motor
P (kW)
I (A)
0.37
1
0.55
1.4
0.75
1.7
1.1
2.4
1.5
3.1
Disjoncteurs
Circuit Breaker
Type
Type
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
Cal (A)
Rat (A)
2.5
2.5
2.5
2.5
6.3
6.3
6.3
12.5
12.5
25
25
25
50
50
2.2
4.5
3
5.8
4
8
5.5
10.5
7.5
13.7
10
19
11
20
15
26.5
18.5
33
-
-
22
39
-
-
30
52
-
-
37
63
-
-
45
76
-
-
55
90
NS100-MA
100
-
-
-
-
75
125
NS160-MA
150
-
-
-
-
90
140
NS160-MA
150
-
-
-
-
110
178
NS250-MA
220
132
210
NS250-MA
220
-
-
NS400-MA
320
160
256
NS400-MA
320
200
310
NS400-MA
320
220
353
NS630-MA
500
250
400
NS630-MA
500
300
460
NS630-MA
500
NS100-MA
NS100-MA
NS100-MA
NS100-MA
50
100
100
100
Contacteurs
Contactor
Type
Type
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D40
3 x LC1-D40
3 x LC1-D40
3 x LC1-D40
3 x LC1-D40
3 x LC1-D40
3 x LC1-D40
3 x LC1-D40
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D115
3 x LC1-F115
3 x LC1-D150
3 x LC1-F150
3 x LC1-D150
3 x LC1-F150
3 x LC1-F185
3 x LC1-F225
3 x LC1-F265
3 x LC1-F265
3 x LC1-F330
3 x LC1-F400
3 x LC1-F400
3 x LC1-F500
Ancienne gamme
Old range
(1) Applicable pour 480 V NEMA
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1306
1...1,6
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D3322
17...25
LR2-D3322
17...25
LR2-D3353
23...32
LR2-D3355
30...40
LR9-D5357
30...50
LR2-D3355
30...40
LR9-D5357
30...50
LR2-D3359
48...65
LR9-D5363
48...80
LR2-D3359
48...65
LR9-D5363
48...80
LR2-D3363
63...80
LR9-D5363
48...80
LR9-D5367
60...100
LR9-F5367
60...100
LR9-D5369
90...150
LR9-F5369
90...150
LR9-D5369
90...150
LR9-F5369
90...150
LR9-F5371
132...220
LR9-F5371
132...220
LR9-F5371
132...220
LR9-F7375
200...330
LR9-F7375
200...330
LR9-F7379
300...500
LR9-F7379
300...500
LR9-F7379
300...500
Nb modules
Nbr of modules
Mf
Mw
6
6
6
6
6
6
6
6
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
9
9
9
9
9
12
9
9
9
12
9
9
9
12
9
9
9
12
9
9
9
12
12
**
12
**
12
**
12
**
12
**
12
**
16
**
16
**
20
**
20
**
20
**
20
**
20
**
24
**
(1) Valid for 480 V NEMA
** Impossible in Mw type
327
Anex 01
Appendix 01
Compact NS100-630z-MA
500/525 V
Type de coordination: 2
Coordination type: 2
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Performance de coupure / Breaking characteristics
Compact NS
H
L
NS100z-MA
50/35kA
70kA
NS160/250z-MA
50/35kA
70kA
NS400/630z-MA
50/35kA
70kA
Puissance Moteur
Power motor
P (kW)
I (A)
0,55
1,2
0,75
1,5
1,1
2
1,5
2,8
2,2
3,8
3
5
4
6,5
5,5
9
7,5
12
10
15
11
18,4
15
23
18,5
28,5
22
33
-
-
-
-
30
45
-
-
-
-
37
55
-
-
-
-
45
65
-
-
55
75
-
-
75
105
-
-
90
130
-
-
110
156
132
187
160
220
200
280
220
310
250
360
315
445
Disjoncteurs
Circuit Breaker
Type
Type
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS100-MA
NS160-MA
NS160-MA
NS250-MA
NS250-MA
NS400-MA
NS400-MA
NS630-MA
NS630-MA
NS630-MA
Cal (A)
Rat (A)
2,5
2,5
2,5
6,3
6,3
6,3
12,5
12,5
12,5
25
25
25
50
50
50
100
100
100
150
150
220
220
320
320
500
500þ
500
Ancienne gamme
Old range
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
Contacteurs
Contactor
Type
Type
3 x LC1-D09
3 x LC1-D09
3 x LC1-D09
3 x LC1-D40
3 x LC1-D40
3 x LC1-D40
3 x LC1-D40
3 x LC1-D40
3 x LC1-D40
3 x LC1-D40
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D115
3 x LC1-F115
3 x LC1-D80
3 x LC1-D115
3 x LC1-F115
3 x LC1-D80
3 x LC1-D115
3 x LC1-F115
3 x LC1-D115
3 x LC1-F115
3 x LC1-D115
3 x LC1-F115
3 x LC1-D115
3 x LC1-F115
3 x LC1-D150
3 x LC1-F150
3 x LC1-F185
3 x LC1-F265
3 x LC1-F400
3 x LC1-F400
3 x LC1-F500
3 x LC1-F500
3 x LC1-F500
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1306
1...1,6
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
LR2-D3322
17...25
LR2-D3322
17...25
LR2-D3353
23...32
LR2-D3355
23...32
LR9-D5357
30...50
LR9-F5357
30...50
LR2-D3357
30...40
LR9-D5357
30...50
LR9-F5357
30...50
LR2-D3359
48...65
LR9-D5363
48...80
LR9-F5363
48...80
LR9-D5363
48...80
LR9-F5363
48...80
LR9-D5367
60...100
LR9-F5367
60...100
LR9-D5369
90...150
LR9-F5369
90...150
LR9-D5369
90...150
LR9-F5369
90...150
LR9-F5371
132...220
LR9-F5371
132...220
LR9-F7375
200...330
LR9-F7375
200...330
LR9-F7375
200...330
LR9-F7379
300...500
LR9-F7379
300...500
Nb modules
Nbr of modules
Mf
Mw
6
6
6
6
6
6
6
9
6
9
6
9
6
9
6
9
6
9
6
9
9
9
9
9
9
9
9
9
12
**
12
**
9
9
12
**
12
**
9
9
12
**
12
**
12
**
12
**
12
**
12
**
12
**
12
**
12
**
12
**
16
**
20
**
20
**
20
**
24
**
24
**
24
**
** Impossible in Mw type
328
Anex 01
Appendix 01
GV7
6.1.1.19.
Type de coordination: 1 - - - - - - - - - - - - - - - -DOL (Démarrage direct)
Coordination Type: 1 - - - - - - - - - - - - - - - - - -DOL (Direct On Line)
GV7
220/240 V
Puissance Moteur
Power motor
P (kW)
I (A)
11
39
15
52
18.5
64
22
75
25
85
30
100
37
125
45
150
55
180
Pdc
BC
Icu (kA)
Rms (kA)
85
85
85
85
85
85
85
85
85
Type de coordination: 1
Coordination type: 1
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE40
25...40
GV7-RE80
48...80
GV7-RE80
48...80
GV7-RE80
48...80
GV7-RE100
60...100
GV7-RE100
60...100
GV7-RE150
90...150
GV7-RE150
90...150
GV7-RE150
90...150
DOL (Démarrage direct)
DOL (Direct On Line)
Nb modules
Nbr of modules
Contacteur
Contactor
LC1-D40
LC1-D65
LC1-D65
LC1-D80
LC1-D95
LC1-F115
LC1-F150
LC1-F150
LC1-F185
Mf
Mw
3
3
3
3
3
3
3
3
3
3
6
6
6
6
6
6
9
9
Ancienne gamme
Old range
GV7
380/400 V
Puissance Moteur
Power motor
P (kW)
I (A)
Type de coordination: 1
Coordination type: 1
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE50
30...50
GV7-RS50
30...50
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE100
60...100
Contacteur
Contactor
LC1-D32
LC1-D32
LC1-D40
LC1-D40
LC1-D50
LC1-D50
LC1-D65
LC1-D65
LC1-D80
LC1-D80
LC1-D95
DOL (Démarrage direct)
DOL (Direct On Line)
15
30
-
-
18.5
37
-
-
22
44
-
-
30
59
-
-
37
72
-
-
45
85
Pdc
BC
Icu (kA)
Rms (kA)
25
70
25
70
25
70
25
70
25
70
25
Nb modules
Nbr of modules
-
-
70
GV7-RS100
60...100
LC1-D95
3
3
55
105
25
GV7-RE100
60...100
LC1-F115
6
6
Mf
Mw
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
-
-
70
GV7-RS100
60...100
LC1-F115
6
6
75
140
35
GV7-RE150
90...150
LC1-F150
6
6
-
-
70
GV7-RS150
90...150
LC1-F150
6
6
90
170
35
GV7-RE220
132...220
LC1-F185
9
9
-
-
70
GV7-RS220
132...220
LC1-F185
9
9
110
210
35
GV7-RE220
132...220
LC1-F225
9
9
-
-
70
GV7-RS220
132...220
LC1-F225
9
9
Ancienne gamme
Old range
Guide Technique V9 / V9 Technical Guide
329
Anex 01
Appendix 01
GV7
415 V
Puissance Moteur
Power motor
P (kW)
I (A)
15
28
-
-
18.5
35
-
-
22
40
-
-
30
55
-
-
37
72
-
-
45
80
-
-
55
100
-
-
75
135
-
-
90
160
-
-
110
200
-
-
Pdc
BC
Icu (kA)
Rms (kA)
25
70
25
70
25
70
25
70
25
70
25
70
25
70
35
70
35
70
35
70
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE50
30...50
GV7-RS50
30...50
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE100
60...100
GV7-RS100
60...100
GV7-RE100
60...100
GV7-RS100
60...100
GV7-RE150
90...150
GV7-RS150
90...150
GV7-RE220
132...220
GV7-RS220
132...220
GV7-RE220
132...220
GV7-RS220
132...220
Type de coordination: 1
Coordination type: 1
DOL (Démarrage direct)
DOL (Direct On Line)
Nb modules
Nbr of modules
Contacteur
Contactor
LC1-D32
LC1-D32
LC1-D40
LC1-D40
LC1-D50
LC1-D50
LC1-D65
LC1-D65
LC1-D80
LC1-D80
LC1-D95
LC1-D95
LC1-F115
LC1-F115
LC1-F150
LC1-F150
LC1-F185
LC1-F185
LC1-F225
LC1-F225
Mf
Mw
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
6
6
6
6
6
6
6
6
9
9
9
9
9
9
9
9
Ancienne gamme
Old range
Guide Technique V9 / V9 Technical Guide
330
Anex 01
Appendix 01
GV7
440 V
Puissance Moteur
Power motor
P (kW)
I (A)
15
26,5
-
-
18.5
33
-
-
22
39
-
-
30
51,5
-
-
37
64
-
-
45
76
-
-
55
96
-
-
75
124
-
-
90
156
-
-
110
180
-
-
132
215
-
-
Pdc
BC
Icu (kA)
Rms (kA)
25
65
25
65
25
65
25
65
25
65
25
65
25
65
35
65
35
65
35
65
35
65
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE100
60...100
GV7-RS100
60...100
GV7-RE150
90...150
GV7-RS150
90...150
GV7-RE150
90...150
GV7-RS150
90...150
GV7-RE220
132...220
GV7-RS220
132...220
GV7-RE220
132...220
GV7-RS220
132...220
Type de coordination: 1
Coordination type: 1
DOL (Démarrage direct)
DOL (Direct On Line)
Nb modules
Nbr of modules
Contacteur
Contactor
LC1-D32
LC1-D32
LC1-D32
LC1-D32
LC1-D40
LC1-D40
LC1-D65
LC1-D65
LC1-D65
LC1-D65
LC1-D80
LC1-D80
LC1-F115
LC1-F115
LC1-F150
LC1-F150
LC1-F185
LC1-F185
LC1-F225
LC1-F225
LC1-F265
LC1-F265
Mf
Mw
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
6
6
6
6
6
6
6
6
9
9
9
9
9
9
9
9
9
9
9
9
Ancienne gamme
Old range
Guide Technique V9 / V9 Technical Guide
331
Anex 01
Appendix 01
GV7
480 V Nema
Puissance Moteur
Power motor
P (kW)
15
18.5
22
30
37
45
55
75
90
110
132
-
Pdc
BC
Icu (kA)
Rms (kA)
25
65
25
65
25
65
25
65
25
65
25
65
25
65
35
65
35
65
35
65
35
65
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE100
60...100
GV7-RS100
60...100
GV7-RE150
90...150
GV7-RS150
90...150
GV7-RE150
90...150
GV7-RS150
90...150
GV7-RE220
132...220
GV7-RS220
132...220
GV7-RE220
132...220
GV7-RS220
132...220
Type de coordination: 1
Coordination type: 1
DOL (Démarrage direct)
DOL (Direct On Line)
Nb modules
Nbr of modules
Contacteur
Contactor
LC1-D32
LC1-D32
LC1-D32
LC1-D32
LC1-D40
LC1-D40
LC1-D65
LC1-D65
LC1-D65
LC1-D65
LC1-D80
LC1-D80
LC1-F115
LC1-F115
LC1-F150
LC1-F150
LC1-F185
LC1-F185
LC1-F225
LC1-F225
LC1-F265
LC1-F265
Mf
Mw
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
6
6
6
6
6
6
6
6
9
9
9
9
9
9
9
9
9
9
9
9
Ancienne gamme
Old range
Guide Technique V9 / V9 Technical Guide
332
Anex 01
Appendix 01
GV7
6.1.1.20.
Type de coordination: 2 - - - - - - - - - - - - - - - -DOL (Démarrage direct)
Coordination Type: 2 - - - - - - - - - - - - - - - - - -DOL (Direct On Line)
GV7
220/240 V
Puissance Moteur
Power motor
P (kW)
I (A)
7.5
28
10
36
11
39
15
52
18.5
64
22
75
30
100
37
125
45
150
55
180
Pdc
BC
Icu (kA)
Rms (kA)
85
85
85
85
85
85
85
85
85
85
Type de coordination: 2
Coordination type: 2
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE40
25...40
GV7-RE40
25...40
GV7-RE40
25...40
GV7-RE80
48...80
GV7-RE80
48...80
GV7-RE100
60...100
GV7-RE100
60...100
GV7-RE150
90...150
GV7-RE150
90...150
GV7-RE200
132...220
DOL (Démarrage direct)
DOL (Direct On Line)
Nb modules
Nbr of modules
Contacteur
Contactor
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-F115
LC1-F115
LC1-F150
LC1-F150
LC1-F185
Mf
Mw
3
3
3
3
3
3
3
3
3
3
6
6
6
6
6
6
6
6
9
9
Ancienne gamme
Old range
GV7
380/400 V
Puissance Moteur
Power motor
P (kW)
I (A)
15
30
-
-
18.5
37
-
-
22
43
-
-
30
59
-
-
37
72
-
-
Pdc
BC
Icu (kA)
Rms (kA)
25
70
25
70
25
70
25
70
25
70
45
85
25
Type de coordination: 2
Coordination type: 2
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE50
30...50
GV7-RS50
30...50
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE80
48...80
GV7-RS80
48...80
Contacteur
Contactor
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
GV7-RE100
LC1-F115
60...100
DOL (Démarrage direct)
DOL (Direct On Line)
Nb modules
Nbr of modules
Mf
Mw
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
6
6
-
-
70
GV7-RS100
60...100
LC1-F115
6
6
55
105
25
GV7-RE100
60...100
LC1-F115
6
6
-
-
70
GV7-RS100
60...100
LC1-F115
6
6
75
140
35
GV7-RE150
90...150
LC1-F150
6
6
-
-
70
GV7-RS150
90...150
LC1-F150
6
6
90
170
35
GV7-RE220
132...220
LC1-F185
9
9
-
-
70
GV7-RS220
132...220
LC1-F185
9
9
110
210
35
GV7-RE220
132...220
LC1-F225
9
9
-
-
70
GV7-RS220
132...220
LC1-F225
9
9
Ancienne gamme
Old range
Guide Technique V9 / V9 Technical Guide
333
Anex 01
Appendix 01
GV7
415 V
Puissance Moteur
Power motor
P (kW)
I (A)
15
28
-
-
18.5
35
-
-
22
40
-
-
30
55
-
-
37
72
-
-
45
80
-
-
55
100
-
-
75
135
-
-
90
160
-
-
110
200
-
-
Pdc
BC
Icu (kA)
Rms (kA)
25
70
25
70
25
70
25
70
25
70
25
70
25
70
35
70
35
70
35
70
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE50
30...50
GV7-RS50
30...50
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE100
60...100
GV7-RS100
60...100
GV7-RE100
60...100
GV7-RS100
60...100
GV7-RE150
90...150
GV7-RS150
90...150
GV7-RE220
132...220
GV7-RS220
132...220
GV7-RE220
132...220
GV7-RS220
132...220
Type de coordination: 2
Coordination type: 2
DOL (Démarrage direct)
DOL (Direct On Line)
Nb modules
Nbr of modules
Contacteur
Contactor
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-F115
LC1-F115
LC1-F115
LC1-F115
LC1-F150
LC1-F150
LC1-F185
LC1-F185
LC1-F225
LC1-F225
Mf
Mw
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
6
6
6
6
6
6
6
6
6
6
6
6
9
9
9
9
9
9
9
9
Ancienne gamme
Old range
Guide Technique V9 / V9 Technical Guide
334
Anex 01
Appendix 01
GV7
440 V
Puissance Moteur
Power motor
P (kW)
I (A)
15
26,5
-
-
18.5
33
-
-
22
39
-
-
30
51,5
-
-
37
64
-
-
45
76
-
-
55
96
-
-
75
124
-
-
90
156
-
-
110
180
-
-
132
215
-
-
Pdc
BC
Icu (kA)
Rms (kA)
25
70
25
70
25
70
25
70
25
70
25
70
25
70
35
70
35
70
35
70
35
70
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE100
60...100
GV7-RS100
60...100
GV7-RE150
90...150
GV7-RS150
90...150
GV7-RE150
90...150
GV7-RS150
90...150
GV7-RE220
132...220
GV7-RS220
132...220
GV7-RE220
132...220
GV7-RS220
132...220
Type de coordination: 2
Coordination type: 2
DOL (Démarrage direct)
DOL (Direct On Line)
Nb modules
Nbr of modules
Contacteur
Contactor
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-F115
LC1-F115
LC1-F115
LC1-F115
LC1-F150
LC1-F150
LC1-F150
LC1-F150
LC1-F185
LC1-F185
LC1-F225
LC1-F225
Mf
Mw
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
9
9
9
9
9
9
9
9
Ancienne gamme
Old range
Guide Technique V9 / V9 Technical Guide
335
Anex 01
Appendix 01
GV7
480 V Nema
Puissance Moteur
Power motor
P (kW)
15
18.5
22
30
37
45
55
75
90
110
132
-
Pdc
BC
Icu (kA)
Rms (kA)
25
70
25
70
25
70
25
70
25
70
25
70
25
70
35
70
35
70
35
70
35
70
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE100
60...100
GV7-RS100
60...100
GV7-RE150
90...150
GV7-RS150
90...150
GV7-RE150
90...150
GV7-RS150
90...150
GV7-RE220
132...220
GV7-RS220
132...220
GV7-RE
220
GV7-RS
220
Type de coordination: 2
Coordination type: 2
DOL (Démarrage direct)
DOL (Direct On Line)
Nb modules
Nbr of modules
Contacteur
Contactor
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-F115
LC1-F115
LC1-F115
LC1-F115
LC1-F150
LC1-F150
LC1-F150
LC1-F150
LC1-F185
LC1-F185
LC1-F225
LC1-F225
Mf
Mw
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
9
9
9
9
9
9
9
9
Ancienne gamme
Old range
Guide Technique V9 / V9 Technical Guide
336
Anex 01
Appendix 01
GV7
6.1.1.21.
Type de coordination: 1 - - - - - - - - - - - - - - - -2 sens de marche
Coordination Type: 1 - - - - - - - - - - - - - - - - - -Reverse
GV7
220/240 V
Puissance Moteur
Power motor
P (kW)
I (A)
11
39
15
52
18.5
64
22
75
25
85
30
100
37
125
45
150
55
180
Pdc
BC
Icu (kA)
Rms (kA)
85
85
85
85
85
85
85
85
85
Type de coordination: 1
Coordination type: 1
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE40
25...40
GV7-RE80
48...80
GV7-RE80
48...80
GV7-RE80
48...80
GV7-RE100
60...100
GV7-RE100
60...100
GV7-RE150
90...150
GV7-RE150
90...150
GV7-RE150
90...150
Nb modules
Nbr of modules
Contacteur
Contactor
2 x LC1-D40
2 x LC1-D65
2 x LC1-D65
2 x LC1-D80
2 x LC1-D95
2 x LC1-F115
2 x LC1-F150
2 x LC1-F150
2 x LC1-F185
Ancienne gamme
Old range
** Impossible en type Mw
GV7
380/400 V
Puissance Moteur
Power motor
P (kW)
I (A)
2 sens de marche
Reverse
Mf
Mw
6
6
6
6
6
6
6
6
6
6
9
**
9
**
9
**
12
**
** Impossible in Mw type
Type de coordination: 1
Coordination type: 1
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE50
30...50
GV7-RS50
30...50
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE100
60...100
Contacteur
Contactor
2 x LC1-D32
2 x LC1-D32
2 x LC1-D40
2 x LC1-D40
2 x LC1-D50
2 x LC1-D50
2 x LC1-D65
2 x LC1-D65
2 x LC1-D80
2 x LC1-D80
2 x LC1-D95
2 sens de marche
Reverse
15
30
-
-
18.5
37
-
-
22
43
-
-
30
59
-
-
37
72
-
-
45
85
Pdc
BC
Icu (kA)
Rms (kA)
25
70
25
70
25
70
25
70
25
70
25
Nb modules
Nbr of modules
-
-
70
GV7-RS100
60...100
2 x LC1-D95
6
6
55
105
25
GV7-RE100
60...100
2 x LC1-F115
9
**
Mf
Mw
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
-
-
70
GV7-RS100
60...100
2 x LC1-F115
9
**
75
140
35
GV7-RE150
90...150
2 x LC1-F150
9
**
-
-
70
GV7-RS150
90...150
2 x LC1-F150
9
**
90
170
35
GV7-RE220
132...220
2 x LC1-F185
12
**
-
-
70
GV7-RS220
132...220
2 x LC1-F185
12
**
110
210
35
GV7-RE220
132...220
2 x LC1-F225
12
**
-
-
70
GV7-RS220
132...220
2 x LC1-F225
12
**
Ancienne gamme
Old range
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
** Impossible in Mw type
337
Anex 01
Appendix 01
GV7
415 V
Puissance Moteur
Power motor
P (kW)
I (A)
15
28
-
-
18.5
35
-
-
22
40
-
-
30
55
-
-
37
72
-
-
45
80
-
-
55
100
-
-
75
135
-
-
90
160
-
-
110
200
-
-
Pdc
BC
Icu (kA)
Rms (kA)
25
70
25
70
25
70
25
70
25
70
25
70
25
70
35
70
35
70
35
70
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE50
30...50
GV7-RS50
30...50
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE100
60...100
GV7-RS100
60...100
GV7-RE100
60...100
GV7-RS100
60...100
GV7-RE150
90...150
GV7-RS150
90...150
GV7-RE220
132...220
GV7-RS220
132...220
GV7-RE220
132...220
GV7-RS220
132...220
Ancienne gamme
Old range
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
Type de coordination: 1
Coordination type: 1
2 sens de marche
Reverse
Nb modules
Nbr of modules
Contacteur
Contactor
2 x LC1-D32
2 x LC1-D32
2 x LC1-D40
2 x LC1-D40
2 x LC1-D50
2 x LC1-D50
2 x LC1-D65
2 x LC1-D65
2 x LC1-D80
2 x LC1-D80
2 x LC1-D95
2 x LC1-D95
2 x LC1-F115
2 x LC1-F115
2 x LC1-F150
2 x LC1-F150
2 x LC1-F185
2 x LC1-F185
2 x LC1-F225
2 x LC1-F225
Mf
Mw
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
9
**
9
**
9
**
9
**
12
**
12
**
12
**
12
**
** Impossible in Mw type
338
Anex 01
Appendix 01
GV7
440 V
Puissance Moteur
Power motor
P (kW)
I (A)
15
26,5
-
-
18.5
33
-
-
22
39
-
-
30
51,5
-
-
37
64
-
-
45
76
-
-
55
96
-
-
75
124
-
-
90
156
-
-
110
180
-
-
132
215
-
-
Pdc
BC
Icu (kA)
Rms (kA)
25
65
25
65
25
65
25
65
25
65
25
65
25
65
35
65
35
65
35
65
35
65
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE100
60...100
GV7-RS100
60...100
GV7-RE150
90...150
GV7-RS150
90...150
GV7-RE150
90...150
GV7-RS150
90...150
GV7-RE220
132...220
GV7-RS220
132...220
GV7-RE220
132...220
GV7-RS220
132...220
Ancienne gamme
Old range
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
Type de coordination: 1
Coordination type: 1
2 sens de marche
Reverse
Nb modules
Nbr of modules
Contacteur
Contactor
2 x LC1-D32
2 x LC1-D32
2 x LC1-D32
2 x LC1-D32
2 x LC1-D40
2 x LC1-D40
2 x LC1-D65
2 x LC1-D65
2 x LC1-D65
2 x LC1-D65
2 x LC1-D80
2 x LC1-D80
2 x LC1-F115
2 x LC1-F115
2 x LC1-F150
2 x LC1-F150
2 x LC1-F185
2 x LC1-F185
2 x LC1-F225
2 x LC1-F225
2 x LC1-F265
2 x LC1-F265
Mf
Mw
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
9
**
9
**
9
**
9
**
12
**
12
**
12
**
12
**
12
**
12
**
** Impossible in Mw type
339
Anex 01
Appendix 01
480 V Nema
Puissance Moteur
Power motor
P (kW)
15
18.5
22
30
37
45
55
75
90
110
132
-
GV7
Pdc
BC
Icu (kA)
Rms (kA)
25
65
25
65
25
65
25
65
25
65
25
65
25
65
35
65
35
65
35
65
35
65
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE100
60...100
GV7-RS100
60...100
GV7-RE150
90...150
GV7-RS150
90...150
GV7-RE150
90...150
GV7-RS150
90...150
GV7-RE220
132...220
GV7-RS220
132...220
GV7-RE220
132...220
GV7-RS220
132...220
Ancienne gamme
Old range
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
Type de coordination: 1
Coordination type: 1
2 sens de marche
Reverse
Nb modules
Nbr of modules
Contacteur
Contactor
2 x LC1-D32
2 x LC1-D32
2 x LC1-D32
2 x LC1-D32
2 x LC1-D40
2 x LC1-D40
2 x LC1-D65
2 x LC1-D65
2 x LC1-D65
2 x LC1-D65
2 x LC1-D80
2 x LC1-D80
2 x LC1-F115
2 x LC1-F115
2 x LC1-F150
2 x LC1-F150
2 x LC1-F185
2 x LC1-F185
2 x LC1-F225
2 x LC1-F225
2 x LC1-F265
2 x LC1-F265
Mf
Mw
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
9
**
9
**
9
**
9
**
12
**
12
**
12
**
12
**
12
**
12
**
** Impossible in Mw type
340
Anex 01
Appendix 01
GV7
6.1.1.22.
Type de coordination: 2 - - - - - - - - - - - - - - - -2 sens de marche
Coordination Type: 2 - - - - - - - - - - - - - - - - - -Reverse
GV7
220/240 V
Puissance Moteur
Power motor
P (kW)
I (A)
7.5
28
10
36
11
39
15
52
18,5
64
22
75
30
100
37
125
45
150
55
180
Pdc
BC
Icu (kA)
Rms (kA)
85
85
85
85
85
85
85
85
85
85
Type de coordination: 2
Coordination type: 2
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE40
25...40
GV7-RE40
25...40
GV7-RE40
25...40
GV7-RE80
48...80
GV7-RE80
48...80
GV7-RE100
60...100
GV7-RE100
60...100
GV7-RE150
90...150
GV7-RE150
90...150
GV7-RE220
132...220
Nb modules
Nbr of modules
Contacteur
Contactor
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-F115
2 x LC1-F115
2 x LC1-F150
2 x LC1-F150
2 x LC1-F185
Ancienne gamme
Old range
** Impossible en type Mw
GV7
380/400 V
Puissance Moteur
Power motor
P (kW)
I (A)
15
30
-
-
18,5
37
-
-
22
43
-
-
30
59
-
-
37
72
-
-
Pdc
BC
Icu (kA)
Rms (kA)
25
70
25
70
25
70
25
70
25
70
45
85
25
2 sens de marche
Reverse
Mf
Mw
6
6
6
6
6
6
6
6
6
6
9
**
9
**
9
**
9
**
12
**
** Impossible in Mw type
Type de coordination: 2
Coordination type: 2
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE50
30...50
GV7-RS50
30...50
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE80
48...80
GV7-RS80
48...80
Contacteur
Contactor
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
GV7-RE100
2 x LC1-F115
60...100
2 sens de marche
Reverse
Nb modules
Nbr of modules
Mf
Mw
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
9
**
-
-
70
GV7-RS100
60...100
2 x LC1-F115
9
**
55
105
25
GV7-RE100
60...100
2 x LC1-F115
9
**
-
-
70
GV7-RS100
60...100
2 x LC1-F115
9
**
75
140
35
GV7-RE150
90...150
2 x LC1-F150
9
**
-
-
70
GV7-RS150
90...150
2 x LC1-F150
9
**
90
170
35
GV7-RE220
132...220
2 x LC1-F185
12
**
-
-
70
GV7-RS220
132...220
2 x LC1-F185
12
**
110
210
35
GV7-RE220
132...220
2 x LC1-F225
12
**
-
-
70
GV7-RS220
132...220
2 x LC1-F225
12
**
Ancienne gamme
Old range
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
** Impossible in Mw type
341
Anex 01
Appendix 01
GV7
415 V
Puissance Moteur
Power motor
P (kW)
I (A)
15
28
-
-
18,5
34
-
-
22
40
-
-
30
55
-
-
37
72
-
-
45
80
-
-
55
100
-
-
75
135
-
-
90
160
-
-
110
200
-
-
Pdc
BC
Icu (kA)
Rms (kA)
25
70
25
70
25
70
25
70
25
70
25
70
25
70
35
70
35
70
35
70
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE50
30...50
GV7-RS50
30...50
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE100
60...100
GV7-RS100
60...100
GV7-RE100
60...100
GV7-RS100
60...100
GV7-RE150
90...150
GV7-RS150
90...150
GV7-RE220
132...220
GV7-RS220
132...220
GV7-RE220
132...220
GV7-RS220
132...220
Ancienne gamme
Old range
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
Type de coordination: 2
Coordination type: 2
2 sens de marche
Reverse
Nb modules
Nbr of modules
Contacteur
Contactor
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-F115
2 x LC1-F115
2 x LC1-F115
2 x LC1-F115
2 x LC1-F150
2 x LC1-F150
2 x LC1-F185
2 x LC1-F185
2 x LC1-F225
2 x LC1-F225
Mf
Mw
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
**
9
**
9
**
9
**
9
**
9
**
9
**
12
**
12
**
12
**
12
**
** Impossible in Mw type
342
Anex 01
Appendix 01
GV7
440 V
Puissance Moteur
Power motor
P (kW)
I (A)
15
26,5
-
-
18,5
33
-
-
22
39
-
-
30
51,5
-
-
37
64
-
-
45
76
-
-
55
96
-
-
75
124
-
-
90
156
-
-
110
180
-
-
132
215
-
-
Pdc
BC
Icu (kA)
Rms (kA)
25
70
25
70
25
70
25
70
25
70
25
70
25
70
35
70
35
70
35
70
35
70
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE100
60...100
GV7-RS100
60...100
GV7-RE150
90...150
GV7-RS150
90...150
GV7-RE150
90...150
GV7-RS150
90...150
GV7-RE220
132...220
GV7-RS220
132...220
GV7-RE220
132...220
GV7-RS220
132...220
Ancienne gamme
Old range
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
Type de coordination: 2
Coordination type: 2
2 sens de marche
Reverse
Nb modules
Nbr of modules
Contacteur
Contactor
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-F115
2 x LC1-F115
2 x LC1-F115
2 x LC1-F115
2 x LC1-F150
2 x LC1-F150
2 x LC1-F150
2 x LC1-F150
2 x LC1-F185
2 x LC1-F185
2 x LC1-F225
2 x LC1-F225
Mf
Mw
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
9
**
9
**
9
**
9
**
9
**
9
**
9
**
9
**
12
**
12
**
12
**
12
**
** Impossible in Mw type
343
Anex 01
Appendix 01
480 V Nema
Puissance Moteur
Power motor
P (kW)
15
18,5
22
30
37
45
55
75
90
110
132
-
GV7
Pdc
BC
Icu (kA)
Rms (kA)
25
70
25
70
25
70
25
70
25
70
25
70
25
70
35
70
35
70
35
70
35
70
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE100
60...100
GV7-RS100
60...100
GV7-RE150
90...150
GV7-RS150
90...150
GV7-RE150
90...150
GV7-RS150
90...150
GV7-RE220
132...220
GV7-RS220
132...220
GV7-RE220
132...220
GV7-RS220
132...220
Ancienne gamme
Old range
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
Type de coordination: 2
Coordination type: 2
2 sens de marche
Reverse
Nb modules
Nbr of modules
Contacteur
Contactor
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-D80
2 x LC1-F115
2 x LC1-F115
2 x LC1-F115
2 x LC1-F115
2 x LC1-F150
2 x LC1-F150
2 x LC1-F150
2 x LC1-F150
2 x LC1-F185
2 x LC1-F185
2 x LC1-F225
2 x LC1-F225
Mf
Mw
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
9
**
9
**
9
**
9
**
9
**
9
**
9
**
9
**
12
**
12
**
12
**
12
**
** Impossible in Mw type
344
Anex 01
Appendix 01
GV7
6.1.1.23.
Type de coordination: 1 - - - - - - - - - - - - - - - -Etoile / Triangle (Y/∆)
Coordination Type: 1 - - - - - - - - - - - - - - - - - -STAR / DELTA (Y/∆)
Démarrage: Normal
Start-up: Normal
220/240 V
Puissance Moteur
Power motor
P (kW)
I (A)
11
39
18.5
64
22
75
25
85
30
100
37
125
45
150
55
180
GV7
Pdc
BC
Icu (kA)
Rms (kA)
85
85
85
85
85
85
85
85
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE50
30...50
GV7-RE80
48...80
GV7-RE100
60...100
GV7-RE100
60...100
GV7-RE100
60...100
GV7-RE150
90...150
GV7-RE150
90...150
GV7-RE220
132...220
Nb modules
Nbr of modules
Contacteur
Contactor
3 x LC1-D18
3 x LC1-D40
3 x LC1-D50
3 x LC1-D50
3 x LC1-D50
3 x LC1-D80
3 x LC1-F115
3 x LC1-F115
Ancienne gamme
Old range
** Impossible en type Mw
380/400 V
Puissance Moteur
Power motor
P (kW)
I (A)
15
30
-
-
18.5
37
-
-
22
44
-
-
30
59
-
-
37
72
-
-
45
85
-
-
55
105
-
-
75
140
-
-
90
170
-
-
110
210
-
-
GV7
Pdc
BC
Icu (kA)
Rms (kA)
25
70
25
70
25
70
25
70
25
70
25
70
25
70
35
70
35
70
35
70
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE50
30...50
GV7-RS50
30...50
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE100
60...100
GV7-RS100
60...100
GV7-RE100
60...100
GV7-RS100
60...100
GV7-RE150
90...150
GV7-RS150
90...150
GV7-RE220
132...220
GV7-RS220
132...220
GV7-RE220
132...220
GV7-RS220
132...220
Ancienne gamme
Old range
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Type de coordination: 1
Coordination type: 1
Mf
Mw
6
6
6
9
6
9
6
9
9
9
6
9
12
**
12
**
** Impossible in Mw type
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Type de coordination: 1
Coordination type: 1
Nb modules
Nbr of modules
Contacteur
Contactor
3 x LC1-D18
3 x LC1-D18
3 x LC1-D18
3 x LC1-D18
3 x LC1-D32
3 x LC1-D32
3 x LC1-D32
3 x LC1-D32
3 x LC1-D40
3 x LC1-D40
3 x LC1-D50
3 x LC1-D50
3 x LC1-D50
3 x LC1-D50
3 x LC1-D80
3 x LC1-D80
3 x LC1-F115
3 x LC1-F115
3 x LC1-F115
3 x LC1-F115
Mf
Mw
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
12
**
12
**
12
**
12
**
** Impossible in Mw type
345
Anex 01
Appendix 01
GV7
415 V
Puissance Moteur
Power motor
P (kW)
I (A)
15
28
-
-
18.5
35
-
-
22
40
-
-
30
55
-
-
37
72
-
-
45
80
-
-
55
100
-
-
75
135
-
-
90
160
-
-
110
200
-
-
Pdc
BC
Icu (kA)
Rms (kA)
25
70
25
70
25
70
25
70
25
70
25
70
25
70
35
70
35
70
35
70
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE50
30...50
GV7-RS50
30...50
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE100
60...100
GV7-RS100
60...100
GV7-RE100
60...100
GV7-RS100
60...100
GV7-RE150
90...150
GV7-RS150
90...150
GV7-RE220
132...220
GV7-RS220
132...220
GV7-RE220
132...220
GV7-RS220
132...220
Ancienne gamme
Old range
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Type de coordination: 1
Coordination type: 1
Nb modules
Nbr of modules
Contacteur
Contactor
3 x LC1-D18
3 x LC1-D18
3 x LC1-D18
3 x LC1-D18
3 x LC1-D32
3 x LC1-D32
3 x LC1-D32
3 x LC1-D32
3 x LC1-D40
3 x LC1-D40
3 x LC1-D50
3 x LC1-D50
3 x LC1-D50
3 x LC1-D50
3 x LC1-D80
3 x LC1-D80
3 x LC1-F115
3 x LC1-F115
3 x LC1-F115
3 x LC1-F115
Mf
Mw
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
12
**
12
**
12
**
12
**
** Impossible in Mw type
346
Anex 01
Appendix 01
GV7
440 V
Puissance Moteur
Power motor
P (kW)
I (A)
15
26,5
-
-
18.5
33
-
-
22
39
-
-
30
51,5
-
-
37
64
-
-
45
76
-
-
55
96
-
-
75
124
-
-
90
156
-
-
110
180
-
-
132
215
-
-
Pdc
BC
Icu (kA)
Rms (kA)
25
70
25
70
25
70
25
70
25
70
25
70
25
70
35
70
35
70
35
70
35
70
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE100
60...100
GV7-RS100
60...100
GV7-RE150
90...150
GV7-RS150
90...150
GV7-RE150
90...150
GV7-RS150
90...150
GV7-RE220
132...220
GV7-RS220
132...220
GV7-RE220
132...220
GV7-RS220
132...220
Ancienne gamme
Old range
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Type de coordination: 1
Coordination type: 1
Nb modules
Nbr of modules
Contacteur
Contactor
3 x LC1-D18
3 x LC1-D18
3 x LC1-D18
3 x LC1-D18
3 x LC1-D18
3 x LC1-D18
3 x LC1-D32
3 x LC1-D32
3 x LC1-D40
3 x LC1-D40
3 x LC1-D50
3 x LC1-D50
3 x LC1-D50
3 x LC1-D50
3 x LC1-D80
3 x LC1-D80
3 x LC1-F115
3 x LC1-F115
3 x LC1-F115
3 x LC1-F115
3 x LC1-F150
3 x LC1-F150
Mf
Mw
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
12
**
12
**
12
**
12
**
12
**
12
**
** Impossible in Mw type
347
Anex 01
Appendix 01
480 V Nema
Puissance Moteur
Power motor
P (kW)
15
18.5
22
30
37
45
55
75
90
110
132
-
GV7
Pdc
BC
Icu (kA)
Rms (kA)
25
70
25
70
25
70
25
70
25
70
25
70
25
70
35
70
35
70
35
70
35
70
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE100
60...100
GV7-RS100
60...100
GV7-RE150
90...150
GV7-RS150
90...150
GV7-RE150
90...150
GV7-RS150
90...150
GV7-RE220
132...220
GV7-RS220
132...220
GV7-RE220
132...220
GV7-RS220
132...220
Ancienne gamme
Old range
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Type de coordination: 1
Coordination type: 1
Nb modules
Nbr of modules
Contacteur
Contactor
3 x LC1-D18
3 x LC1-D18
3 x LC1-D18
3 x LC1-D18
3 x LC1-D18
3 x LC1-D18
3 x LC1-D32
3 x LC1-D32
3 x LC1-D40
3 x LC1-D40
3 x LC1-D50
3 x LC1-D50
3 x LC1-D50
3 x LC1-D50
3 x LC1-D80
3 x LC1-D80
3 x LC1-F115
3 x LC1-F115
3 x LC1-F115
3 x LC1-F115
3 x LC1-F150
3 x LC1-F150
Mf
Mw
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
12
**
12
**
12
**
12
**
12
**
12
**
** Impossible in Mw type
348
Anex 01
Appendix 01
GV7
6.1.1.24.
Type de coordination: 2 - - - - - - - - - - - - - - - -Etoile / Triangle (Y/∆)
Coordination Type: 2 - - - - - - - - - - - - - - - - - -STAR / DELTA (Y/∆)
Démarrage: Normal
Start-up: Normal
220/240 V
Puissance Moteur
Power motor
P (kW)
I (A)
7,5
28
10
36
11
39
15
52
18,5
64
22
75
30
100
37
125
45
150
55
180
GV7
Pdc
BC
Icu (kA)
Rms (kA)
85
85
85
85
85
85
85
85
85
85
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE40
25...40
GV7-RE40
25...40
GV7-RE40
25...40
GV7-RE80
48...80
GV7-RE80
48...80
GV7-RE100
60...100
GV7-RE100
60...100
GV7-RE150
90...150
GV7-RE150
90...150
GV7-RE220
132...220
Nb modules
Nbr of modules
Contacteur
Contactor
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-F115
3 x LC1-F115
3 x LC1-F150
3 x LC1-F150
3 x LC1-F185
Ancienne gamme
Old range
** Impossible en type Mw
380/400 V
Puissance Moteur
Power motor
P (kW)
I (A)
15
30
-
-
18,5
37
-
-
22
43
-
-
30
59
-
-
37
72
-
-
45
85
-
-
55
105
-
-
75
140
-
-
90
170
-
-
110
210
-
-
GV7
Pdc
BC
Icu (kA)
Rms (kA)
25
70
25
70
25
70
25
70
25
70
25
70
25
70
35
70
35
70
35
70
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE50
30...50
GV7-RS50
30...50
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE100
60...100
GV7-RS100
60...100
GV7-RE100
60...100
GV7-RS100
60...100
GV7-RE150
90...150
GV7-RS150
90...150
GV7-RE220
132...220
GV7-RS220
132...220
GV7-RE220
132...220
GV7-RS220
132...220
Ancienne gamme
Old range
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Type de coordination: 2
Coordination type: 2
Mf
Mw
6
9
6
9
6
9
6
9
6
9
12
**
12
**
12
**
12
**
16
**
** Impossible in Mw type
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Type de coordination: 2
Coordination type: 2
Nb modules
Nbr of modules
Contacteur
Contactor
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-F115
3 x LC1-F115
3 x LC1-F115
3 x LC1-F115
3 x LC1-F150
3 x LC1-F150
3 x LC1-F185
3 x LC1-F185
3 x LC1-F225
3 x LC1-F225
Mf
Mw
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
12
**
12
**
12
**
12
**
12
**
12
**
16
**
16
**
16
**
16
**
** Impossible in Mw type
349
Anex 01
Appendix 01
GV7
415 V
Puissance Moteur
Power motor
P (kW)
I (A)
15
28
-
-
18,5
34
-
-
22
40
-
-
30
55
-
-
37
72
-
-
45
80
-
-
55
100
-
-
75
135
-
-
90
160
-
-
110
200
-
-
Pdc
BC
Icu (kA)
Rms (kA)
25
70
25
70
25
70
25
70
25
70
25
70
25
70
35
70
35
70
35
70
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE50
30...50
GV7-RS50
30...50
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE100
60...100
GV7-RS100
60...100
GV7-RE100
60...100
GV7-RS100
60...100
GV7-RE150
90...150
GV7-RS150
90...150
GV7-RE220
132...220
GV7-RS220
132...220
GV7-RE220
132...220
GV7-RS220
132...220
Ancienne gamme
Old range
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Type de coordination: 2
Coordination type: 2
Nb modules
Nbr of modules
Contacteur
Contactor
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-F115
3 x LC1-F115
3 x LC1-F115
3 x LC1-F115
3 x LC1-F150
3 x LC1-F150
3 x LC1-F185
3 x LC1-F185
3 x LC1-F225
3 x LC1-F225
Mf
Mw
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
12
**
12
**
12
**
12
**
12
**
12
**
16
**
16
**
16
**
16
**
** Impossible in Mw type
350
Anex 01
Appendix 01
GV7
440 V
Puissance Moteur
Power motor
P (kW)
I (A)
15
26,5
-
-
18,5
33
-
-
22
39
-
-
30
51,5
-
-
37
64
-
-
45
76
-
-
55
96
-
-
75
124
-
-
90
156
-
-
110
180
-
-
132
215
-
-
Pdc
BC
Icu (kA)
Rms (kA)
25
70
25
70
25
70
25
70
25
70
25
70
25
70
35
70
35
70
35
70
35
70
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE100
60...100
GV7-RS100
60...100
GV7-RE150
90...150
GV7-RS150
90...150
GV7-RE150
90...150
GV7-RS150
90...150
GV7-RE220
132...220
GV7-RS220
132...220
GV7-RE220
132...220
GV7-RS220
132...220
Ancienne gamme
Old range
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Type de coordination: 2
Coordination type: 2
Nb modules
Nbr of modules
Contacteur
Contactor
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-F115
3 x LC1-F115
3 x LC1-F115
3 x LC1-F115
3 x LC1-F150
3 x LC1-F150
3 x LC1-F150
3 x LC1-F150
3 x LC1-F185
3 x LC1-F185
3 x LC1-F225
3 x LC1-F225
Mf
Mw
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
12
**
12
**
12
**
12
**
12
**
12
**
12
**
12
**
16
**
16
**
16
**
16
**
** Impossible in Mw type
351
Anex 01
Appendix 01
480 V Nema
Puissance Moteur
Power motor
P (kW)
15
18,5
22
30
37
45
55
75
90
110
132
-
GV7
Pdc
BC
Icu (kA)
Rms (kA)
25
70
25
70
25
70
25
70
25
70
25
70
25
70
35
70
35
70
35
70
35
70
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE40
25...40
GV7-RS40
25...40
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE80
48...80
GV7-RS80
48...80
GV7-RE100
60...100
GV7-RS100
60...100
GV7-RE150
90...150
GV7-RS150
90...150
GV7-RE150
90...150
GV7-RS150
90...150
GV7-RE220
132...220
GV7-RS220
132...220
GV7-RE220
132...220
GV7-RS220
132...220
Ancienne gamme
Old range
** Impossible en type Mw
Guide Technique V9 / V9 Technical Guide
Etoile / Triangle (Y/∆)
STAR / DELTA (Y/∆)
Type de coordination: 2
Coordination type: 2
Nb modules
Nbr of modules
Contacteur
Contactor
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-D80
3 x LC1-F115
3 x LC1-F115
3 x LC1-F115
3 x LC1-F115
3 x LC1-F150
3 x LC1-F150
3 x LC1-F150
3 x LC1-F150
3 x LC1-F185
3 x LC1-F185
3 x LC1-F225
3 x LC1-F225
Mf
Mw
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
6
9
12
**
12
**
12
**
12
**
12
**
12
**
12
**
12
**
16
**
16
**
16
**
16
**
** Impossible in Mw type
352
Anex 01
Appendix 01
INTEGRAL
6.1.1.25.
Contacteurs-Disjoncteurs INTEGRAL - - - - - -DOL (Démarrage direct)
INTEGRAL contactors-circuit breakers - - - - -DOL (Direct On Line)
Coordination totale
Total coordination
220/230 V
Contacteurs-Disjoncteurs INTEGRAL
INTEGRAL contactors-circuit breakers
Puissance Moteur
Power motor
P (kW)
I (A)
Icu (kA)
Rms (kA)
0,06
0,38
70
0,09
0,65
70
0,12
0,75
70
0,18
1,04
70
0,25
1,47
70
0,37
2
70
-
-
-
0,55
2,8
70
0,75
3,6
70
1,1
5,2
70
-
-
-
1,5
6,8
70
2,2
9,6
70
3
11,5
70
-
-
-
4
14,5
70
-
-
-
5,5
2,2
70
7,5
28
70
DOL (Démarrage direct)
DOL (Direct On Line)
Contacteur-disjoncteur sans Module de protection
Contactor-Circuit Breaker without protection Module
Sectionnement par
Sectionnement par
pôles principaux
pôles spécifiques
Isolation by main poles
Isolation by specifics poles
LD1-LB030
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LC030
LD4-LC130
LD1-LC030
LD4-LC130
*:
Icu = 40 kA pour LD1-LB;
Icu = 70 kA pour LDz-LC.
**: En fonction du nombre d’auxiliaires.
LD1-LB:
LDz-LC:
LDz-LD:
Guide Technique V9 / V9 Technical Guide
Module de protection
Protection Module
Référence
Reference
Nb modules
Nbr of modules
Mf
Mw
LB1-LB03P03
3
3 ou 6**
LB1-LB03P05
3
3 ou 6**
LB1-LC03M05
3
-
LB1-LB03P06
3
3 ou 6**
LB1-LC03M06
3
-
LB1-LB03P07
3
3 ou 6**
LB1-LC03M07
3
-
LB1-LB03P08
3
3 ou 6**
LB1-LC03M08
3
-
LB1-LB03P10
3
3 ou 6**
LB1-LC03M10
3
-
LB1-LB03P13
3
3 ou 6**
LB1-LC03M13
3
-
LB1-LB03P17
3
3 ou 6**
LB1-LC03M17
3
-
LB1-LB03P21
3
3 ou 6**
LB1-LC03M17
3
-
LB1-LC03M22
3
3 ou 6**
LB1-LC03M53
3
3 ou 6**
*:
Rms = 40 kA for LD1-LB;
Rms = 70 kA for LDz-LC.
**: According to the number of auxiliaries.
Integral 18.
Integral 32.
Integral 63.
353
Anex 01
Appendix 01
400/415 V
Contacteurs-Disjoncteurs INTEGRAL
INTEGRAL contactors-circuit breakers
Puissance Moteur
Power motor
P (kW)
I (A)
Icu (kA)
Rms (kA)
0,06
0,22
70
0,09
0,36
70
0,12
0,42
70
0,18
0,6
70
0,25
0,88
70
-
-
-
0,37
1
70
0,55
1,5
70
0,75
2
70
-
-
-
1,1
2,5
70
1,5
3,5
70
2,2
5
70
-
-
-
3
6,5
70
4
8,4
70
5,5
11
70
7,5
14,8
70
9
18,1
70
-
-
-
11
21
70
15
28,5
70
18,5
35
70
22
42
70
30
57
70
DOL (Démarrage direct)
DOL (Direct On Line)
Contacteur-disjoncteur sans Module de protection
Contactor-Circuit Breaker without protection Module
Sectionnement par
Sectionnement par
pôles principaux
pôles spécifiques
Isolation by main poles
Isolation by specifics poles
LD1-LB030
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LC030
LD4-LC130
LD1-LC030
LD4-LC130
LD1-LD030
LD4-LD130
LD1-LD030
LD4-LD130
LD1-LD030
LD4-LD130
*:
Icu = 40 kA pour LD1-LB;
Icu = 70 kA pour LDz-LC.
**: En fonction du nombre d’auxiliaires.
LD1-LB:
LDz-LC:
LDz-LD:
Guide Technique V9 / V9 Technical Guide
Module de protection
Protection Module
Référence
Reference
Nb modules
Nbr of modules
Mf
Mw
LB1-LB03P02
3
3 ou 6**
LB1-LB03P03
3
3 ou 6**
LB1-LC03M03
-
-
LB1-LB03P04
3
3 ou 6**
LB1-LC03M04
3
-
LB1-LB03P05
3
3 ou 6**
LB1-LC03M05
3
-
LB1-LB03P06
3
3 ou 6**
LB1-LC03M06
3
-
LB1-LB03P07
3
3 ou 6**
LB1-LC03M07
3
-
LB1-LB03P08
3
3 ou 6**
LB1-LC03M08
3
-
LB1-LB03P10
3
3 ou 6**
LB1-LC03M10
3
-
LB1-LB03P13
3
3 ou 6**
LB1-LC03M13
3
-
LB1-LB03P17
3
3 ou 6**
LB1-LC03M17
3
-
LB1-LB03P21
3
3 ou 6**
LB1-LC03M22
3
-
LB1-LC03M22
3
3 ou 6**
LB1-LC03M53
3
3 ou 6**
LB1-LD03M55
6
6
LB1-LD03M57
6
6
LB1-LD03M61
6
6
*:
Rms = 40 kA for LD1-LB;
Rms = 70 kA for LDz-LC.
**: According to the number of auxiliaries.
Integral 18.
Integral 32.
Integral 63.
354
Anex 01
Appendix 01
440 V
Contacteurs-Disjoncteurs INTEGRAL
INTEGRAL contactors-circuit breakers
Puissance Moteur
Power motor
P (kW)
I (A)
Icu (kA)
Rms (kA)
0,06
0,19
70
0,09
0,28
70
0,12
0,37
70
-
-
-
0,18
0,55
70
0,25
0,76
70
-
-
-
0,37
1
70
0,55
1,36
70
0,75
1,68
70
1,1
2,37
70
-
-
-
1,5
3,06
70
2,2
4,42
*
3
5,77
*
4
7,9
*
-
-
-
5,5
10,4
*
7,5
13,7
*
9
16,9
*
11
20,1
70
15
26,5
30
18,5
32,8
70
22
39
70
30
51,5
40
33
58,5
40
DOL (Démarrage direct)
DOL (Direct On Line)
Contacteur-disjoncteur sans Module de protection
Contactor-Circuit Breaker without protection Module
Sectionnement par
Sectionnement par
pôles principaux
pôles spécifiques
Isolation by main poles
Isolation by specifics poles
LD1-LB030
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LB030
LD1-LC030
LD4-LC130
LD1-LC030
LD4-LC130
LD1-LC030
LD4-LC130
LD1-LD030
LD4-LD130
LD1-LD030
LD4-LD130
-
*:
Icu = 40 kA pour LD1-LB;
Icu = 70 kA pour LDz-LC.
**: En fonction du nombre d’auxiliaires.
LD1-LB:
LDz-LC:
LDz-LD:
Guide Technique V9 / V9 Technical Guide
Module de protection
Protection Module
Référence
Reference
Nb modules
Nbr of modules
Mf
Mw
LB1-LB03P02
3
3 ou 6**
LB1-LB03P03
3
3 ou 6**
LB1-LC03M03
3
-
LB1-LB03P04
3
3 ou 6**
LB1-LC03M04
3
-
LB1-LB03P05
3
3 ou 6**
LB1-LC03M05
3
-
LB1-LB03P06
3
3 ou 6**
LB1-LC03M06
3
-
LB1-LB03P07
3
3 ou 6**
-
LB1-LC03M07
3
LB1-LB03P08
3
3 ou 6**
LB1-LC03M08
3
-
LB1-LB03P10
3
3 ou 6**
LB1-LC03M10
3
-
LB1-LB03P13
3
3 ou 6**
LB1-LC03M13
3
-
LB1-LB03P17
3
3 ou 6**
LB1-LC03M17
3
-
LB1-LB03P21
3
3 ou 6**
LB1-LC03M22
3
-
LB1-LC03M22
3
3 ou 6**
LB1-LC03M53
3
3 ou 6**
LB1-LD03M55
6
6
-
-
-
LB1-LD03M61
6
6
-
-
-
*:
Rms = 40 kA for LD1-LB;
Rms = 70 kA for LDz-LC.
**: According to the number of auxiliaries.
Integral 18.
Integral 32.
Integral 63.
355
Anex 01
Appendix 01
INTEGRAL
6.1.1.26.
Contacteurs-Disjoncteurs INTEGRAL - - - - - -2 sens de marche
INTEGRAL contactors-circuit breakers - - - - -Reverse
Coordination totale
Total coordination
220/230 V
Contacteurs-Disjoncteurs INTEGRAL
INTEGRAL contactors-circuit breakers
Puissance Moteur
Power motor
P (kW)
I (A)
Icu (kA)
Rms (kA)
0,06
0,38
70
0,09
0,65
70
0,12
0,75
70
0,18
1,04
70
0,25
1,47
70
0,37
2
70
-
-
-
0,55
2,8
70
0,75
3,6
70
1,1
5,2
70
-
-
-
1,5
6,8
70
2,2
9,6
70
3
11,5
70
-
-
-
4
14,5
70
-
-
-
5,5
2,2
70
7,5
28
70
2 sens de marche
Reverse
Contacteur-disjoncteur sans Module de protection
Contactor-Circuit Breaker without protection Module
Sectionnement par
Sectionnement par
pôles principaux
pôles spécifiques
Isolation by main poles
Isolation by specifics poles
LD5-LB130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LC130
LD5-LC130
*:
Icu = 40 kA pour LD5-LB;
Icu = 70 kA pour LD5-LC.
LD5-LB:
LD5-LC:
LD5-LD:
Guide Technique V9 / V9 Technical Guide
*:
Module de protection
Protection Module
Référence
Reference
Nb modules
Nbr of modules
Mf
Mw
LB1-LB03P03
3
6
LB1-LB03P05
3
6
LB1-LC03M05
6
-
LB1-LB03P06
3
6
LB1-LC03M06
6
-
LB1-LB03P07
3
6
LB1-LC03M07
6
-
LB1-LB03P08
3
6
LB1-LC03M08
6
-
LB1-LB03P10
3
6
LB1-LC03M10
6
-
LB1-LB03P13
3
6
LB1-LC03M13
6
-
LB1-LB03P17
3
6
LB1-LC03M17
6
-
LB1-LB03P21
3
6
LB1-LC03M17
6
-
LB1-LC03M22
6
6
LB1-LC03M53
6
6
Rms = 40 kA for LD5-LB;
Rms = 70 kA for LD5-LC.
Integral 18.
Integral 32.
Integral 63.
356
Anex 01
Appendix 01
400/415 V
Contacteurs-Disjoncteurs INTEGRAL
INTEGRAL contactors-circuit breakers
Puissance Moteur
Power motor
P (kW)
I (A)
Icu (kA)
Rms (kA)
0,06
0,22
70
0,09
0,36
70
-
-
-
0,12
0,42
70
0,18
0,6
70
0,25
0,88
70
-
-
-
0,37
1
70
0,55
1,5
70
0,75
2
70
-
-
-
1,1
2,5
70
1,5
3,5
70
2,2
5
70
-
-
-
3
6,5
70
4
8,4
70
5,5
11
70
7,5
14,8
70
9
18,1
70
-
-
-
11
21
70
15
28,5
70
18,5
35
70
22
42
70
30
57
70
2 sens de marche
Reverse
Contacteur-disjoncteur sans Module de protection
Contactor-Circuit Breaker without protection Module
Sectionnement par
Sectionnement par
pôles principaux
pôles spécifiques
Isolation by main poles
Isolation by specifics poles
LD5-LB130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LC130
LD5-LC130
LD5-LD130
LD5-LD130
LD5-LD130
*:
Icu = 40 kA pour LD5-LB;
Icu = 70 kA pour LD5-LC.
LD5-LB:
LD5-LC:
LD5-LD:
Guide Technique V9 / V9 Technical Guide
*:
Module de protection
Protection Module
Référence
Reference
Nb modules
Nbr of modules
Mf
Mw
LB1-LB03P02
3
6
LB1-LB03P03
3
6
LB1-LC03M03
6
-
LB1-LB03P04
3
6
LB1-LC03M04
6
-
LB1-LB03P05
3
6
LB1-LC03M05
6
-
LB1-LB03P06
3
6
LB1-LC03M06
6
-
LB1-LB03P07
3
6
LB1-LC03M07
6
-
LB1-LB03P08
3
6
LB1-LC03M08
6
-
LB1-LB03P10
3
6
LB1-LC03M10
6
-
LB1-LB03P13
3
6
LB1-LC03M13
6
-
LB1-LB03P17
3
6
LB1-LC03M17
6
-
LB1-LB03P21
3
6
LB1-LC03M22
6
-
LB1-LC03M22
6
6
LB1-LC03M53
6
6
LB1-LD03M55
6
6**
LB1-LD03M57
6
6**
LB1-LD03M61
6
6**
Rms = 40 kA for LD5-LB;
Rms = 70 kA for LD5-LC.
Integral 18.
Integral 32.
Integral 63.
357
Anex 01
Appendix 01
440 V
Contacteurs-Disjoncteurs INTEGRAL
INTEGRAL contactors-circuit breakers
Puissance Moteur
Power motor
P (kW)
I (A)
Icu (kA)
Rms (kA)
0,06
0,19
70
0,09
0,28
70
0,12
0,37
70
-
-
-
0,18
0,55
70
0,25
0,76
70
-
-
-
0,37
1
70
0,55
1,36
70
0,75
1,68
70
1,1
2,37
70
-
-
-
1,5
3,06
70
2,2
4,42
*
3
5,77
*
4
7,9
*
-
-
-
5,5
10,4
*
7,5
13,7
*
9
16,9
*
-
-
-
11
20,1
70
15
26,5
30
18,5
32,8
70
22
39
70
30
51,5
40
33
58,5
40
2 sens de marche
Reverse
Contacteur-disjoncteur sans Module de protection
Contactor-Circuit Breaker without protection Module
Sectionnement par
Sectionnement par
pôles principaux
pôles spécifiques
Isolation by main poles
Isolation by specifics poles
LD5-LB130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LB130
LD5-LC130
LD5-LC130
LD5-LC130
LD5-LD130
LD5-LD130
-
*:
Icu = 40 kA pour LD5-LB;
Icu = 70 kA pour LD5-LC.
**: 9 avec transformateur
LD5-LB:
LD5-LC:
LD5-LD:
Guide Technique V9 / V9 Technical Guide
Module de protection
Protection Module
Référence
Reference
Nb modules
Nbr of modules
Mf
Mw
LB1-LB03P02
3
6
LB1-LB03P03
3
6
LB1-LC03M03
6
-
LB1-LB03P04
3
6
LB1-LC03M04
6
-
LB1-LB03P05
3
6
LB1-LC03M05
6
-
LB1-LB03P06
3
6
LB1-LC03M06
6
-
LB1-LB03P07
3
6
LB1-LC03M07
6
-
LB1-LB03P08
3
6
LB1-LC03M08
6
-
LB1-LB03P10
3
6
LB1-LC03M10
6
-
LB1-LB03P13
3
6
LB1-LC03M13
6
-
LB1-LB03P17
3
6
LB1-LC03M17
6
-
LB1-LB03P21
3
6
LB1-LC03M22
6
-
LB1-LC03M22
6
6
LB1-LC03M53
6
6
LB1-LD03M55
6
6**
-
-
-
LB1-LD03M61
6
6**
-
-
-
*:
Rms = 40 kA for LD5-LB;
Rms = 70 kA for LD5-LC.
**: 9 with transformer
Integral 18.
Integral 32.
Integral 63.
358
Anex 01
Appendix 01
6.1.1.27.
GV2-P
Type de coordination: 1 - - - - - - - - - - - - - - - -DOL monophasé (Démarrage direct)
Coordination type: 1 - - - - - - - - - - - - - - - - - - -Single phase - DOL (Direct On Line)
GV2-P
220/230 V
Puissance Moteur
Power motor
P (kW)
I (A)
0,09
0,5
0,12
1,0
0,25
2,0
0,37
3,0
0,55
4,0
0,75
5,0
1,1
7,4
1,5
9,3
1,8
11,7
2,2
16,0
3
18,3
4
23,5
Pdc
BC
Icu (kA)
Rms (kA)
50
50
50
50
50
50
50
50
50
50
50
50
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV2-P04
0,4..0,63
GV2-P06
1...1,6
GV2-P07
1,6...2,5
GV2-P08
2,5...4
GV2-P10
4...6,3
GV2-P10
4...6,3
GV2-P14
6...10
GV2-P14
6...10
GV2-P16
9...14
GV2-P20
13...18
GV2-P21
17...23
GV2-P22
20...25
Type de coordination: 1
Coordination type: 1
DOL monophasé (Démarrage direct)
Single phase - DOL (Direct On Line)
Nb modules
Nbr of modules
Contacteur
Contactor
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K09
LC1-K09
LC1-D12
LC1-D18
LC1-D25
LC1-D25
Mw
3
3
3
3
3
3
3
3
3
3
3
3
Ancienne gamme
Old range
6.1.1.28.
GV2-P
Type de coordination: 2 - - - - - - - - - - - - - - - -DOL monophasé (Démarrage direct)
Coordination type: 2 - - - - - - - - - - - - - - - - - - -Single phase - DOL (Direct On Line)
GV2-P
220/230 V
Puissance Moteur
Power motor
P (kW)
I (A)
0,09
0,5
0,12
1,0
0,25
2,0
0,37
3,0
0,55
4,0
0,75
5,0
1,1
7,4
1,5
9,3
1,8
11,7
2,2
16
3
18,3
4
23,5
Pdc
BC
Icu (kA)
Rms (kA)
130
130
130
130
130
130
130
130
130
130
130
130
Appareillage Puissance
Power Switchgear
Disjoncteur (calibre [A])
Circuit Breaker (rating [A])
GV2-P04
0,4..0,63
GV2-P06
1...1,6
GV2-P07
1,6...2,5
GV2-P08
2,5...4
GV2-P10
4...6,3
GV2-P10
4...6,3
GV2-P14
6...10
GV2-P14
6...10
GV2-P16
9...14
GV2-P20
13...18
GV2-P21
17...23
GV2-P22
20...25
Type de coordination: 2
Coordination type: 2
DOL monophasé (Démarrage direct)
Single phase - DOL (Direct On Line)
Nb modules
Nbr of modules
Contacteur
Contactor
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D25
LC1-D25
LC1-D25
LC1-D25
Mw
3
3
3
3
3
3
3
3
3
3
3
3
Ancienne gamme
Old range
Guide Technique V9 / V9 Technical Guide
359
Anex 01
Appendix 01
6.1.1.29.
Compact NS80H-MA
Type de coordination: 1 - - - - - - - - - - - - - - - -DOL monophasé (Démarrage direct)
Coordination type: 1 - - - - - - - - - - - - - - - - - - -Single phase - DOL (Direct On Line)
Démarrage: Normal
Performance de coupure: égale au pouvoir
de coupure du disjoncteur
Compact NS80H-MA
220/230 V
Puissance Moteur
Power motor
P (kW)
I (A)
0,12
1,0
0,25
2,0
0,37
3,0
0,55
4,0
0,75
5,0
1,1
7,4
1,5
9,3
1,8
11,7
2,2
16,0
3
18,3
4
23,5
Disjoncteurs
Circuit Breaker
Type
Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
Cal (A)
Rat (A)
2,5
2,5
6,3
6,3
6,3
12,5
12,5
25
25
25
50
Start-up: Normal
Breaking characteristics: equal to the circuit
breaker’s breaking capacity
Type de coordination: 1
Coordination type: 1
Contacteurs
Contactor
Type
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D18
LC1-D25
LC1-D32
LC1-D32
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1310
4...6
LR2-D1312
5,5...8
LR2-D1314
7...10
LR2-D1318
9...13
LR2-D1321
12...18
LR2-D1322
17...25
LR2-D1322
17...25
DOL monophasé (Démarrage direct)
Single phase - DOL (Direct On Line)
Nb modules
Nbr of modules
Mw
3
3
3
3
3
3
3
3
3
3
3
Ancienne gamme
Old range
6.1.1.30.
Compact NS80H-MA
Type de coordination: 2 - - - - - - - - - - - - - - - -DOL monophasé (Démarrage direct)
Coordination type: 2 - - - - - - - - - - - - - - - - - - -Single phase - DOL (Direct On Line)
Démarrage: Normal
Start-up: Normal
220/230 V
Compact NS80H-MA
Performance de coupure: Icu = 100 kA
Breaking characteristics: Icu = 100 kA
Puissance Moteur
Disjoncteurs
Power motor
Circuit Breaker
P (kW)
I (A)
Type
Type
0,12
1,0
NS80H-MA
0,25
2,0
NS80H-MA
0,37
3,0
NS80H-MA
0,55
4,0
NS80H-MA
0,75
5,0
NS80H-MA
1,1
7,4
NS80H-MA
1,5
9,3
NS80H-MA
1,8
11,7
NS80H-MA
2,2
16,0
NS80H-MA
Cal (A)
Rat (A)
2,5
2,5
6,3
6,3
6,3
12,5
12,5
25
25
Type de coordination: 2
Coordination type: 2
Contacteurs
Contactor
Type
Type
LC1-D09
LC1-D09
LC1-D18
LC1-D25
LC1-D25
LC1-D32
LC1-D32
LC1-D32
LC1-D32
Relais Thermiques
Thermal Relay
Type
Irth (A)
Type
Irth (A)
LR2-D1306
1...1,6
LR2-D1307
1,6...2,5
LR2-D1308
2,5...4
LR2-D1310
4...6
LR2-D1310
4...6
LR2-D1314
7...10
LR2-D1314
7...10
LR2-D1316
9...13
LR2-D1321
12...18
DOL monophasé (Démarrage direct)
Single phase - DOL (Direct On Line)
Nb modules
Nbr of modules
Mw
3
3
3
3
3
3
3
3
3
Ancienne gamme
Old range
Guide Technique V9 / V9 Technical Guide
360
Anex 01
Appendix 01
6.1.2.
6.1.2.1.
Déclassement des appareils - AC3
Starters derating - AC3
GV2-P
Type de coordination: 1-2
Coordination type: 1-2
Blokset Mf
Appareillage Puissance
Power Switchgear
Disjoncteur
Circuit breaker
GV2-P02
GV2-P03
GV2-P04
GV2-P05
GV2-P06
GV2-P07
GV2-P08
GV2-P10
GV2-P14
GV2-P16
GV2-P20
GV2-P21
GV2-P22
Calibre
Rating
0,16...0,25
0,25...0,4
0,4...0,63
0,63...1
1...1,6
1,6...2,5
2,5...4
4...6,3
6...10
9...14
13...18
17...23
20...25
Contacteur
Contactor
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K09
LC1-D12
LC1-D18
LC1-D25
LC1-D25
Coefficient de Déclassement (A) à T°amb (°C)
Derating coefficient (A) à T°amb (°C)
IP ð 42
IP 54
35
40
45
50
35
40
45
50
0,23
0,2
0,2
0,2
0,2
0,2
0,2
0,15
0,35
0,33
0,3
0,3
0,3
0,3
0,3
0,25
0,6
0,5
0,5
0,5
0,5
0,5
0,5
0,4
0,9
0,8
0,8
0,7
0,8
0,75
0,7
0,7
1,4
1,3
1,2
1,2
1,3
1,2
1,1
1
2,2
2,1
2
1,9
2
1,9
1,8
1,7
3,6
3,4
3,1
3
3,2
3
2,9
2,7
5,4
5
4,7
4,5
5
4,5
4,3
4
8
7,6
7
6,7
7,2
6,8
6,5
6
10,7
10
9,4
8,9
9,6
9
8,6
8
16
15
14
13,3
14,5
13,5
13
12
20
19
18
17
18,5
17
16,6
15,4
22
21
19,5
18,5
20
18,8
18
16,8
Blokset Mw
Appareillage Puissance
Power Switchgear
Coefficient de Déclassement (A) à T°amb (°C)
Derating coefficient (A) à T°amb (°C)
IP ð 42
IP 54
35
40
45
50
35
40
45
50
0,23
0,2
0,2
0,2
0,2
0,2
0,2
0,2
0,35
0,34
0,3
0,3
0,3
0,3
0,3
0,3
0,6
0,5
0,5
0,5
0,5
0,5
0,5
0,4
Disjoncteur
Circuit breaker
GV2-P02
GV2-P03
GV2-P04
GV2-P05
GV2-P06
GV2-P07
Calibre
Rating
0,16...0,25
0,25...0,4
0,4...0,63
0,63...1
1...1,6
1,6...2,5
Contacteur
Contactor
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
LC1-K06
GV2-P08
2,5...4
LC1-K06
GV2-P10
4...6,3
LC1-K06
5,4
5
4,7
4,5
5
4,5
4,3
4
GV2-P14
6...10
LC1-K09
8
7,5
7
6,7
7,2
6,8
6,5
6
GV2-P16
9...14
LC1-D12
10,7
10
9,4
8,9
9,6
9
8,6
8
GV2-P20
13...18
LC1-D18
16
15
14
13,3
14,5
13,5
13
12
GV2-P21
17...23
LC1-D25
20
19
18
17
18,5
17
15,6
15,4
GV2-P22
20...25
LC1-D25
22
21
20
19
20
19
18
17
0,9
0,8
0,8
0,7
0,8
0,8
0,7
0,7
1,4
1,3
1,2
1,2
1,3
1,2
1,1
1
2,2
2,1
2
1,9
2
1,9
1,8
1,7
3,6
3,4
3,1
3
3,2
3
2,9
2,7
Coefficient à appliquer
IP ≤ 42
IP 54
Guide Technique V9 / V9 Technical Guide
35°
0.89
0.80
Coefficient to be applied
40°
0.84
0.75
45°
0.78
0.72
50°
0.74
0.67
361
Anex 01
Appendix 01
6.1.2.2.
Compact NS et GV7
Compact NS and GV7
Type de coordination: 1-2
Coordination type: 1-2
Blokset Mf
Appareillage Puissance
Power Switchgear
Disjoncteur
Circuit breaker
NS80H-MA
NS100l-MA*
NS160l-MA*
NS250l-MA*
NS400l-MA*
NS630l-MA*
Calibre
Rating
2,5
6,3
13
13
25
25
50
50
50
80
80
2,5
6,3
13
13
25
25
50
50
50
50
100
100
100
100
150
Disjoncteur moteur
Motor circuit-breaker
GV7-Rn
GV7-Rn
GV7-Rn
GV7-Rn
GV7-Rn
GV7-Rn
GV7-Rn
GV7-Rn
GV7-Rn
GV7-Rn
GV7-Rn
GV7-Rn
GV7-Rn
GV7-Rn
GV7-Rn
GV7-Rn
Contacteur
Contactor
LC1-D09
LC1-D09
LC1-D09
LC1-D12
LC1-D18
LC1-D25
LC1-D32
LC1-D40
LC1-D50
LC1-D65
LC1-D80
LC1-D09
LC1-D09
LC1-D09
LC1-D12
LC1-D18
LC1-D25
LC1-D32
LC1-D40
LC1-D50
LC1-D65
LC1-D65
LC1-D80
LC1-D95
LC1-F115
LC1-F150
220
GV7-Rn
220
GV7-Rn
Coefficient de Déclassement (A) à T°amb (°C)
Derating coefficient (A) à T°amb (°C)
IP ð 42
IP 54
35
40
45
50
35
40
45
50
8
7.7
7.3
7
6.3
5.9
5.5
5.4
8
7.7
7.3
7
6.3
5.9
5.5
5.4
8
7.7
7.3
7
6.3
5.9
5.5
5.4
10.7
10.2
9.7
9.2
8.3
7.8
7.5
7
16
15.3
14.6
13.9
12.5
11.7
11.2
10.8
22.3
21.2
20.2
19.2
17.3
16.3
15.5
15
28.5
27.2
26
24.6
22
20.8
19.9
19.2
35.6
34
32.4
30.8
28
26
25
24
44.5
42.5
40.5
38.5
35
33
32
30
58
55
53
50
45
42
40
39
71
68
65
62
55
52
50
48
8
7.7
7.3
7
6.3
5.9
5.5
5.4
8
7.7
7.3
7
6.3
5.9
5.5
5.4
8
7.7
7.3
7
6.3
5.9
5.5
5.4
7
10.7
10.2
9.7
9.2
8.3
7.8
7.5
16
15.3
14.6
13.9
12.5
11.7
11.2
10.8
22.3
21.2
20.2
19.2
17.3
16.3
15.5
15
28.5
27.2
26
24.6
22
20.8
19.9
19.2
35.6
34
32.4
30.8
28
26
25
24
44.5
42.5
40.5
38.5
35
33
32
30
58
55
53
50
45
42
40
39
58
55
53
50
45
42
40
39
71
68
65
62
55
52
50
48
84.5
81
77
73
65
62
60
57
102
98
93
89
78
75
73
69
134
128
122
116
102
98
95
90
LC1-F185
165
157
150
142
126
120
117
111
LC1-F225
203
190
185
175
154
147
141
135
320
GV7-Rn
LC1-F265
236
225
215
204
180
172
167
159
320
-
LC1-F330
294
280
267
254
225
215
208
198
500
-
LC1-F400
356
340
324
308
272
260
252
240
500
-
LC1-F500
445
425
405
385
340
325
315
300
500
-
LC1-F630
560
535
510
485
428
409
397
381
*:
NS ***z-MA représente:
- NS*** N/H/L-MA pour NS100-250
- NS*** H/L-MA pour NS400-630
„: représente E40...220 ou S40...220
Guide Technique V9 / V9 Technical Guide
*:
NS ***z-MA represent:
- NS*** N/H/L-MA by NS100-250
- NS*** H/L-MA by NS400-630
„: represent E40...220 or S40...220
362
Anex 01
Appendix 01
Blokset Mw
IP 20
Appareillage Puissance
Power Switchgear
Disjoncteur
Calibre
Circuit breaker
Rating
NS80H-MA
2,5
6,3
13
13
25
Disjoncteur moteur
Motor circuit-breaker
GV7-R„
Contacteur
Contactor
LC1-D09
LC1-D09
LC1-D09
LC1-D12
LC1-D18
25
-
50
GV7-R„
50
Coefficient de Déclassement (A) à T°amb (°C)
Derating coefficient (A) à T°amb (°C)
35
40
45
50
8,1
7,9
7,6
8,1
7,9
7,6
7,2
7,2
8,1
7,9
7,6
7,2
10
10,5
1O
9,6
17
16
15
15
LC1-D25
22,5
22
21
20
LC1-D32
30
28
27
26
GV7-R„
LC1-D40
38
35
33
32
50
GV7-R„
LC1-D50
45
44
42
40
80
GV7-R„
LC1-D65
61
58
55
52
80
GV7-R„
LC1-D80
64
61
59
56
2,5
-
LC1-D09
8,1
7,9
7,6
7,2
6,3
-
LC1-D09
8,1
7,9
7,6
7,2
13
-
LC1-D09
8,1
7,9
7,6
7,2
13
-
LC1-D12
10
10,5
1O
9,6
25
GV7-R„
LC1-D18
17
16
15
15
25
-
LC1-D25
22,5
22
21
20
50
GV7-R„
LC1-D32
30
28
27
26
50
GV7-R„
LC1-D40
38
35
33
32
50
GV7-R„
LC1-D50
45
44
42
40
50
GV7-R„
LC1-D65
61
58
55
52
100
GV7-R„
LC1-D65
61
58
55
52
100
GV7-R„
LC1-D80
64
61
59
56
100
GV7-R„
LC1-D95
76
72
70
67
NS160z-MA*
100
GV7-R„
LC1-F115
92
88
84
81
150
GV7-R„
LC1-F150
120
115
110
105
NS250z-MA*
220
GV7-R„
LC1-F185
148
142
136
130
220
GV7-R„
LC1-F225
175
168
161
155
NS400z-MA*
320
GV7-R„
LC1-F265
249
235
222
211
320
-
LC1-F330
255
245
234
225
NS630z-MA*
500
-
LC1-F400
320
306
293
282
500
-
LC1-F500
400
382
366
352
500
-
LC1-F630
500
480
460
440
NS100z-MA*
*:
NS ***z-MA représente:
- NS*** N/H/L-MA pour NS100-250
- NS*** H/L-MA pour NS400-630
„: représente E40...220 ou S40...220
Guide Technique V9 / V9 Technical Guide
*:
NS ***z-MA represent:
- NS*** N/H/L-MA by NS100-250
- NS*** H/L-MA by NS400-630
„: represent E40...220 or S40...220
363
Anex 01
Appendix 01
Blokset Mw
IP 31/42
Appareillage Puissance
Power Switchgear
Disjoncteur
Calibre
Circuit breaker
Rating
NS80H-MA
2,5
6,3
13
13
25
GV7-R„
Contacteur
Contactor
LC1-D09
LC1-D09
LC1-D09
LC1-D12
LC1-D18
25
-
LC1-D25
22
21
20
18,5
50
GV7-R„
LC1-D32
28
27
25
24
50
GV7-R„
LC1-D40
34
32
31
29
50
GV7-R„
LC1-D50
35
33
31
30
80
GV7-R„
LC1-D65
57
54
51
48
80
GV7-R„
LC1-D80
64
61
59
56
2,5
-
LC1-D09
8
7,6
7
6,6
6,3
-
LC1-D09
8
7,6
7
6,6
13
-
LC1-D09
8
7,6
7
6,6
13
-
LC1-D12
10,5
10
9,4
8,8
25
GV7-R„
LC1-D18
17
16
15
14
25
-
LC1-D25
22
21
20
18,5
50
GV7-R„
LC1-D32
28
27
25
24
50
GV7-R„
LC1-D40
34
32
31
29
50
GV7-R„
LC1-D50
35
33
31
30
50
GV7-R„
LC1-D65
57
54
51
48
100
GV7-R„
LC1-D65
57
54
51
48
100
GV7-R„
LC1-D80
64
61
59
56
100
GV7-R„
LC1-D95
76
72
70
67
NS160z-MA*
100
GV7-R„
LC1-F115
92
87
85
80
150
GV7-R„
LC1-F150
112
110
102
98
NS250z-MA*
220
GV7-R„
LC1-F185
137
135
126
120
220
GV7-R„
LC1-F225
164
161
150
144
NS400z-MA*
320
GV7-R„
LC1-F265
231
218
207
197
320
-
LC1-F330
238
234
218
210
NS630z-MA*
500
-
LC1-F400
296
292
272
260
500
-
LC1-F500
372
366
341
328
500
-
LC1-F630
468
460
430
413
NS100z-MA*
Disjoncteur moteur
Motor circuit-breaker
-
Coefficient de Déclassement (A) à T°amb (°C)
Derating coefficient (A) à T°amb (°C)
35
40
45
50
*:
8
7,6
7
8
7,6
7
6,6
8
7,6
7
6,6
10,5
10
9,4
8,8
17
16
15
14
NS ***z-MA représente:
- NS*** N/H/L-MA pour NS100-250
- NS*** H/L-MA pour NS400-630
„: représente E40...220 ou S40...220
Guide Technique V9 / V9 Technical Guide
6,6
*:
NS ***z-MA represent:
- NS*** N/H/L-MA by NS100-250
- NS*** H/L-MA by NS400-630
„: represent E40...220 or S40...220
364
Anex 01
Appendix 01
Blokset Mw
IP 54
Appareillage Puissance
Power Switchgear
Disjoncteur
Calibre
Circuit breaker
Rating
NS80H-MA
2,5
6,3
13
13
25
NS100z-MA*
Disjoncteur moteur
Motor circuit-breaker
-
Coefficient de Déclassement (A) à T°amb (°C)
Derating coefficient (A) à T°amb (°C)
35
40
45
50
GV7-R„
Contacteur
Contactor
LC1-D09
LC1-D09
LC1-D09
LC1-D12
LC1-D18
25
-
LC1-D25
20
18,7
18
17,2
50
GV7-R„
LC1-D32
26
24
23
22
50
GV7-R„
LC1-D40
32
30
29
27,5
50
GV7-R„
LC1-D50
40
37,5
36
34,5
80
GV7-R„
LC1-D65
52
49,5
47
44,5
80
GV7-R„
LC1-D80
55
52
50
48
2,5
-
LC1-D09
7,2
6,8
6,5
6,2
6,3
-
LC1-D09
7,2
6,8
6,5
6,2
13
-
LC1-D09
7,2
6,8
6,5
6,2
13
-
LC1-D12
9,6
9
8,6
7,2
25
GV7-R„
LC1-D18
14,5
13,6
13
12,3
25
-
LC1-D25
20
18,7
18
17,2
50
GV7-R„
LC1-D32
26
24
23
22
50
GV7-R„
LC1-D40
32
30
29
27,5
50
GV7-R„
LC1-D50
40
37,5
36
34,5
50
GV7-R„
LC1-D65
52
49,5
47
44,5
100
GV7-R„
LC1-D65
52
49,5
47
44,5
100
GV7-R„
LC1-D80
55
52
50
48
7,2
6,8
6,5
7,2
6,8
6,5
6,2
6,2
7,2
6,8
6,5
6,2
9,6
9
8,6
7,2
14,5
13,6
13
12,3
100
GV7-R„
LC1-D95
66
62
60
57
NS160z-MA*
100
GV7-R„
LC1-F115
79
75
72
69
150
GV7-R„
LC1-F150
103
98
94
90,5
NS250z-MA*
220
GV7-R„
LC1-F185
127
120
115
111
220
GV7-R„
LC1-F225
151
144
138
133
NS400z-MA*
320
GV7-R„
LC1-F265
213
201
191
182
320
-
LC1-F330
221
211
201
198
NS630z-MA*
500
-
LC1-F400
276
260
250
240
500
-
LC1-F500
343
328
314
302
500
-
LC1-F630
432
413
395
380
*:
NS ***z-MA représente:
- NS*** N/H/L-MA pour NS100-250
- NS*** H/L-MA pour NS400-630
„: représente E40...220 ou S40...220
Guide Technique V9 / V9 Technical Guide
*:
NS ***z-MA represent:
- NS*** N/H/L-MA by NS100-250
- NS*** H/L-MA by NS400-630
„: represent E40...220 or S40...220
365
Anex 01
Appendix 01
6.1.2.3.
Integral
Contacteurs - Disjoncteurs Integral - - - - - - -Coordination totale
Integral Contactors - Circuit breakers - - - - - -Total coordination
Coefficient à appliquer
IP ≤ 42
IP 54
Guide Technique V9 / V9 Technical Guide
35°
0.89
0.80
Coefficient to be applied
40°
45°
50°
0.84
0.78
0.74
0.75
0.72
0.67
366
Anex 01
Appendix 01
Guide Technique V9 / V9 Technical Guide
367
Installation de l’appareillage
Switchgear Installation
Guide Technique V9 / V9 Technical Guide
368
Installation de l’appareillage
Switchgear Installation
Guide Technique V9 / V9 Technical Guide
369
Installation de l’appareillage
Switchgear Installation
Guide Technique V9 / V9 Technical Guide
370
Installation de l’appareillage
Switchgear Installation
Guide Technique V9 / V9 Technical Guide
371
Schneider Electric Brasil
Adresse postale
Av. da Saudade, s/no
13171-320 Sumaré - SP
Brazil
Tél.: 55 (0)19 38 73 97 25
Fax.: 55 (0)19 38 73 97 37
http://www.schneiderelectric.com
51 127 040 X0-rev J.
En raison de l'évolution des normes et du matériel, les
caractéristiques indiquées par le texte et les images de ce
document ne nous engagent qu'après confirmation par nos
services.
As standards, specifications and designs change from time to
time, please ask for confirmation of the information given in this
publication.
Ce document a été imprimé
sur du papier écologique.
This document has been
printed on ecological paper.