Uploaded by saritawaghate

Def Stan 61-12-18

advertisement
Ministry of Defence
Defence Standard
61-12 (Part 18)/Issue 4
WIRES, CORDS AND CABLES
ELECTRICAL - METRIC UNITS
PART 18: EQUIPMENT WIRES,
LIMITED FIRE HAZARD
This Defence Standard supersedes
Def Stan 61-12(Part 18)/ Issue 3
dated 22 June 1990
6 January 1995
DEF STAN 61-12 (PART 18)/4
AMMENDMENTS ISSUED SINCE PUBLICATION
AMD NO
DATE OF
ISSUE
TEXT AFFECTED
SIGNATURE &
DATE
Revision Note
Issue 4 of this Standard incorporates user comments on the sheath
temperature ratings and includes additional 85°C rated cables.
Historical Record
Issue 2 of this Standard included amendments and additions to bring the
Standard more into line with Service requirements. Qualification Approval
and certification clauses were amended to invoke Defence Standard 00-9
procedures.
Issue 3 of this Standard removes the previous INTERIM status and specifies
a reduced toxicity level for Table I items. Items having a toxicity level
of greater than 0.2 and up to 1.5 remain in this Standard for maintenance
purposes, Table II items.
DEF STAN 61-12 (PART 18)/4
WIRES, CORDS AND CABLES ELECTRICAL, METRIC UNITS
EQUIPMENT WIRES - LIMITED FIRE HAZARD
PREFACE
This Defence Standard supersedes
Def Stan 61-12 (Part 18) Issue 3
dated 22 June 1990
i This Defence Standard specifies the requirements for, and also lists,
equipment wires, having limited fire hazard (LFH) insulation, for Ministry
of Defence use.
ii It is a performance Standard, actual insulation material is not
specified and tests are included to control materials offered for approval.
With the development of new materials and/or constructions it is likely
that additional tests will require to be devised.
iii Tables I(A) to I(E) list the standard range of equipment wires and
cables having a toxicity level as defined in 11.4. Tables II(A) to II(E)
list the maintenance range of equipment wires and cables. They are
manufactured to Issue 2 of this Standard and differ in certain significant
features, including a higher toxicity level.
iv The items listed in this Standard should only be purchased from those
manufacturers holding a current Qualification Approval certificate
applicable to the cable or wire required. A list of manufacturers holding
approval to items specified in this Standard will be included in Def
Stan 59-59 and the EPIC/CODUS data bank.
v Users of this Standard are to note that these items may be claimed to be
subject to patent rights in this or in other countries.
vi This Standard has been agreed by the authorities concerned with its use
and is intended to be used whenever relevant in all future designs,
contracts, orders etc and whenever practicable by amendment to those
already in existence. If any difficulty arises which prevents application
of the Defence Standard, the Directorate of Standardization shall be
informed so that a remedy may be sought.
vii Any enquiries regarding this Standard in relation to an invitation to
tender or a contract in which it is incorporated are to be addressed to the
responsible technical or supervising authority named in that invitation to
tender or contract.
vii This Standard has been devised for the use of the Crown and its
contractors in the execution of contracts for the Crown. The Crown hereby
excludes all liability (other than liability for death or personal injury)
whatsoever and howsoever arising (including but without limitation,
negligence on the part of the Crown its servants or agents) for any loss or
damage however caused where the Standard is used for any other purpose.
1
DEF STAN 61-12 (PART 18)/4
CONTENTS
PAGE
Preface
1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Table
Table
Table
Table
Table
Table
Scope
WARNING
Related Documents
Definitions
Type Identification and Colours
Materials
Construction
Testing General
Electrical Tests
Physical Tests
Fire Hazard Tests
Qualification Approval Procedures
Quality Assurance Requirements
Packaging and Labelling
A
B
C
D
E
F
Table G
Conductor Size and Guide to Current Ratings
Details of Conductors
Dimensions of Complete Equipment Wires and Cables
Mass of Complete Equipment Wires and Cables
List of Test Fluids, Additional Requirements
Qualification Approval and Quality Assurance Test
Applications
Specific Test Requirements
4
5
6
7
7
8
8
12
13
13
18
20
21
21
5
10
11
12
15
19
20
Table I(A) )
)
)
) Standard Range
Table I(B) ) Toxicity Index
< 0.2
)
)
(
(
(
(
(
(
(
Table I(C)
Standard Range
Toxicity Index
< 0.2
Cables, Special Purpose, Electrical
and Cables, Power, Electrical Types 1SB and 2SB Limited Fire Hazard
Insulation, Screened
24
Table I(D)
Standard Range
Toxicity Index
< 0.2
Cables, Special Purpose, Electrical
and Cables, Power, Electrical Types 1SBM BT, 1SBM 120 and 2SBM
Limited Fire Hazard Insulation,
Screened and Sheathed
25
Table II(A))
)
)
) Maintenance Range
Table II(B) ) Toxicity Index
) > 0.2 < 1.5
)
(
(
(
(
(
(
(
Equipment Wires, Electrical Type 1 Limited Fire Hazard
Insulation, Unscreened
22
Equipment Wires, Electrical Type 2 Limited Fire Hazard
Insulation, Unscreened
23
Equipment Wires, Electrical Type 1 Limited Fire Hazard
Insulation, Unscreened
26
Equipment Wires, Electrical Type 2 Limited Fire Hazard
Insulation, Unscreened
27
2
DEF STAN 61-12 (PART 18)/4
CONTENTS (Contd)
Table II(C)
Table II(D)
Table II(E)
Annex A
PAGE
Maintenance Range Cables, Special Purpose, Electrical
28
Toxicity Index
and Cables, Power, Electrical > 0.2 < 1.5
Types 1SB and 2SB Limited Fire Hazard
Insulation, Screened
Maintenance Range Cables, Special Purpose, Electrical
29
Toxicity Index
and Cables, Power, Electrical > 0.2 < 1.5
Types 1SBM and 2SBM Limited Fire Hazard
Insulation, Screened and Sheathed
Maintenance Range Equipment Wires, Electrical Toxicity Index
Type 1 Limited Fire Hazard
> 0.2 < 1.5
Bicoloured Insulation Unscreened
Type Designator Coding Structure
3
30
A-1
DEF STAN 61-12 (PART 18)/4
SPECIFICATION FOR WIRES, CORDS AND CABLES ELECTRICAL, METRIC UNITS
PART 18: EQUIPMENT WIRES, LIMITED FIRE HAZARD
1 Scope
1.1 This specification describes the construction, identification and
testing of wires and cables for the internal wiring of electronic or other
equipment.
1.2 These wires and cables (ie screened wires) are also used as the cores
of multicore cables.
1.3 The insulation of the wires and the sheathing of cables in this
specification present a limited fire hazard and produce limited levels of
noxious fumes, smoke and corrosive products when assessed by the methods of
test in this specification.
1.4 The wires listed in this Standard are required to meet the Relative
Thermal Life and Temperature Index Test of BS 2G 230, Appendix C for
40,000 hours at 120°C, and are suitable for continuous use within the
temperature range -50°C to +120°C.
1.5 Cables Type 1SB, 1SBM 120, 2SB and 2SBM listed in this Standard are
required to meet the Relative Thermal Life and Temperature Index Test of
BS 2G 230, Appendix C for 40,000 hours at 120°C, and are suitable for
continuous use within the temperature range -50°C to +120°C.
1.6 Cables Type 1SBM 85 shall have sheathing material qualified to Def
Stan 61-12 (Part 31) and meet the Relative Thermal Life and Temperature
Index Test of BS 2G 230, Appendix C for 40,000 hours at 85°C and are
suitable for continuous use within the temperature range -50°C to +85°C.
1.7 These wires and cables have a voltage rating of 600 V rms or 800V DC.
1.8 These wires and cables are suitable for soldered or crimped
terminations.
They are not designed or necessarily suitable for solderless
wrapped electrical connections.
1.9 Although these wires and cables may be subjected to test contamination
by one or more of the fluids listed in Table E of this Standard, attention
is drawn to 2.2.2 and 2.2.2.1.
1.10 Stranded conductors shall be used for flexing applications.
fixed applications stranded or solid conductors may be used.
For
The following minimum bend radii shall be used within equipment:
(a) for flexing applications, 10 times the overall diameter of the wire or
cable;
(b) for fixed applications, 4 times the overall diameter of the wire or
cable.
4
DEF STAN 61-12 (PART 18)/4
2
WARNING
2.1 This Standard calls for the use of substances and/or procedures that
may be injurious to health if adequate precautions are not taken. It
refers only to technical suitability and in no way absolves either the
designer, the producer, the supplier or the user from statutory and all
other legal obligations relating to health and safety at any stage of
manufacture or use.
2.2 Particular attention is drawn to the following hazards although the
list may not necessarily be exhaustive:
2.2.1 Flammable and/or toxic fumes may be given off from the specimens
when subjected to the fire hazard/flammability tests. Operators are to
take appropriate precautions to avoid exposure to the evolved fumes.
2.2.2 Compliance with 10.2.8 (resistance to fluids test) provides no
guarantee that the wires are suitable for continuous use in the specified
fluids.
2.2.2.1 It should be noted that isopropyl alcohol and aircraft fuel are
not specified for Type 2 wires and that certain Type 2 wire insulations are
adversely affected by these fluids.
2.2.3 Due to the wide variety of insulants which may meet this Standard,
particular attention is drawn to clause 5 especially with respect to
selection of Type and size of wire to be used.
Table A
Conductor Size and Guide to Current Ratings
SIZE
NUMBER AND NOMINAL
DIAMETER OF STRANDS
IN CONDUCTOR
MAXIMUM CONTINUOUS CURRENT
(SEE NOTE BELOW)
mm
amps
(b)
(c)
(a)
30
26
23
19
30
28
26
24
22
20
18
16
14
12
1/0.25
1/0.40
1/0.60
1/0.90
7/0.10
7/0.12
19/0.10
19/0.12
19/0.15
19/0.20
19/0.25
19/0.30
37/0.25
37/0.30
0.3
0.8
1.8
4.0
0.3
0.5
0.8
1.3
2.2
3.7
5.8
7.7
11.4
15.6
5
DEF STAN 61-12 (PART 18)/4
2.2.3 (Contd)
NOTE: Current ratings will depend on circumstances but for general guidance
the combination of conductor size and current shown in table A will give a
temperature rise of about 15°C at an ambient temperature of 70°C.
3 Related Documents
3.1 Reference is made in this Standard to:
IEC Publication 304
BS EN 29453
BS 2G 230
BS 2G 231
Def Stan 61-12 Part 0
Def Stan 59-59
Def Stan 61-12 (Part 31)
Def Stan 91-4
CPU/AIS/300
Standard Colours for Insulation of Low
Frequency Cables and Wires
Soft Solder Alloys - Chemical Composition and
Forms
Specification for General Requirements for
Aircraft Electrical Cables
Specification for Conductors for General
Purpose Aircraft Electrical Cables and
Aerospace Applications
Wires, Cords and Cables Electrical. General
Requirements and Test Methods for Qualification
Approval
Electrical/Electronic Components for Defence
Use. Services Qualified Products List
Wires, Cords and Cables Electrical - Metric
Units: Part 31 Sheaths, Limited Fire Hazard
Fuel, Naval, Distillate: Dieso F-76
Agreed Industry Standard: Packaging of Wires,
Cords and Cables, Electrical
3.2 Copies of documents referred to in 3.1 are obtainable from:
DOCUMENT
SOURCE
Defence Standard Publications
Directorate of Standardization
Stan 1
Kentigern House
65 Brown Street
GLASGOW G2 8EX
British Standards
British Standards Institution
Sales Office
Linford Wood
MILTON KEYNES MK14 6LE
Agreed Industry Standards
CPU/AIS 300
Defence Packaging Authority
Building 18
Royal Arsenal West
Woolwich
LONDON
6
DEF STAN 61-12 (PART 18)/4
3.3 Reference in this Defence Standard to any related document means, in
any invitation to tender or contract, the edition and all amendments
current at the date of such a tender or contract unless a specific edition
is indicated.
4 Definitions
4.1 For the purpose of this Defence Standard the definitions given in
BS 2G 230 shall apply together with the following:
4.1.1 Primary stage. For the purpose of this Defence Standard the primary
stage will be taken as being the ‘buying in’ of the basic materials
required to manufacture the complete wires and cables.
4.1.2 Wire, electrical. A single metallic conductor of solid, stranded or
tinsel construction, designed to carry current in an electrical circuit.
It may be bare or insulated, but does not have a metallic covering, jacket
or shield. Refers to bulk quantities only.
4.1.3 Cable, power, electrical. Two or more insulated conductors (solid,
tubular or stranded) contained in a common covering, or two or more
insulated conductors twisted or moulded together without a common covering,
or one insulated conductor with a metallic covering, shield or outer
conductor. The rated working voltage of the item must be 250V or more and
the size of each individual conductor must be size 18 or larger.
4.1.4 Cable, special purposes, electrical. Two or more individually
insulated conductors (solid or stranded) contained in a common covering or
two or more individually insulated conductors twisted or moulded together
without a common covering, or one insulated conductor with a metallic
covering or shield.
5 Type Identification and colours
5.1 Because of the differing physical nature of insulations which may be
used in the construction of wires and cables to this Standard, the wires
and cables have been divided into two categories to indicate their
handleability for installation purposes. They are as follows:
5.2
Wire Type 1
Cable Type 1SB
Cable Type 1SBM 85
Cable Type 1SBM 120
Wire Type 2
Cable Type 2SB
Cable Type 2SBM
Unscreened, Pliable, with Moderate Dynamic Cut
Through Resistance
Screened Type 1 Wire
Screened and Sheathed Type 1 Wire, 85°C Rated Sheath
Screened and Sheathed Type 1 Wire 120°C Rated Sheath
Unscreened, Less Pliable than Type 1 Wire but having
Higher Dynamic Cut Through Resistance
Screened Type 2 Wire
Screened and Sheathed Type 2 Wire
5.3 Test and limits to control dynamic cut through and pliability for the
two categories, for Qualification Approval testing, are given in 10.2.6 and
10.2.12 respectively.
5.4 Colours. The colours in which the wire and cable shall be supplied
are given in tables I(A) to II(E).
7
DEF STAN 61-12 (PART 18)/4
5.4.1 The colours shall be a reasonable match with the colours specified
in IEC Publication 304.
6 Materials
6.1 Conductors. Conductors of the completed wires and cables shall be of
tin coated annealed copper and shall comply with BS 2G 231 as applicable as
well as with table B and 9.1 of this Standard. Tensile strength and
elongation at break tests shall be in accordance with BS 2G 230, Test 7.
6.2 Insulation. The insulation shall meet all the relevant requirements
of this Standard.
6.2.1 The dielectric constant of the insulation shall not be greater than
4 when measured at approximately 1 KHz.
6.3 Screens.
Screens shall consist of a braid of annealed, tin plated,
copper strands conforming to BS 2G 231 before braiding and constructed as
detailed in 7.4 of this Standard.
6.4 Sheaths. The sheathing material for cable type 1SBM 85 shall be
qualified to Def Stan 61-12 (Part 31).
6.4.1 The sheathing material for cable type 1SM 120 shall meet the
requirements of this Standard.
6.5 It is required that all types of insulation and sheathing to this
specification shall be mutually compatible and also be compatible with
other types of insulation and sheath in general use. The Ministry of
Defence reserve the right to verify this by selected compatibility (ageing)
tests. The Ministry of Defence also reserve the right not to approve
products which are incompatible with those in general use.
7 Construction
7.1 Mass of wires and cables. The mass of the complete equipment wires
and cables shall not exceed the limits specified in table D.
7.2 Conductor stranding
7.2.1 Strands used for conductors shall be clean, bright and free from
surface irregularities. The conductors shall be as specified in table B of
this Standard.
7.2.2 The stranded conductor shall be of concentric construction as
defined in BS 2G 230 2.3 or 2.4 and shall comply with 6.1 of this Standard.
The lay of the strands within each layer shall be uniform throughout the
conductor length.
7.2.3 Joints in single strands shall be brazed or hard soldered and there
shall be not more than one such joint in any 50m of single strand. Joints
in single strands shall not be within 300 mm of any other joint in the same
layer.
7.2.4 Conductors consisting of single strands shall be not joined.
8
DEF STAN 61-12 (PART 18)/4
7.3
Insulation
7.3.1 The conductor shall be uniformly and continuously covered with one
or more layers of insulation.
7.3.2 To permit satisfactory termination the insulation shall not be
loose, but it shall be possible to remove the insulation completely
without any insulation residue remaining.
7.3.3 The dimensions of the insulated conductor and the thickness and the
concentricity of the insulation shall be measured in accordance with the
methods specified in BS 2G 230 Test 5 and shall be within the limits stated
in table C of this Standard.
7.4
Screens
7.4.1 Screens shall be of close fitting braided construction. Wherever
the screened cable is cut it shall be possible to slide back the screen
over a distance of 100 mm on a 600 mm length of cable, the other end of the
cable being clamped.
7.4.2 There shall be no joints in the complete braid. Where breaks in the
individual strands occur, the ends shall be brazed or tucked out of the
braid and there shall not be more than one such break in any 300 mm length
of cable or in any 10m of individual strand. Where renewal of spindles is
necessary, the ends shall be tucked out of the braid and there shall not be
more than one spindle renewal in any 300m length of cable.
7.4.3 The braid construction details shall be as follows:
Diameter of braiding strands, maximum:
(a)
0.11 mm for cables of conductor size up to and including 19/0.2 mm;
(b)
0.13 mm for cables of conductor size of 19/0.25 mm and above.
Ends per spindle minimum 3.
Filling Factor, minimum 0.5.
7.4.3.1 The Filling Factor Kf is defined as:
mnd
2π D
( 1 + π
2
(
½
D2 )
L2
)
where D = mean diameter of braid = diameter over dielectric + 2.25d
d = diameter of braiding strands in millimetres
L = lay of braid in millimetres
m = total number of spindles
n = total number of ends per spindle
9
DEF STAN 61-12 (PART 18)/4
7.5 Sheaths
7.5.1 The sheaths shall be annular and free from defects. The overall
diameter shall be measured in accordance with BS 2G 230, Test 6 and shall
be within the limits specified in table C of this Standard.
7.5.2 The sheath shall not be loose but it shall be removable without
damaging the metal screen.
Table B
Details of Conductor
SIZE
(a)
30
26
23
19
30
28
26
24
22
20
18
16
14
12
NUMBER AND
NOMINAL
DIAMETER OF
STRANDS IN
CONDUCTOR
NOMINAL
CROSS
SECTIONAL
AREA
CONDUCTOR
DIAMETER
MINIMUM
ELECTRICAL RESISTANCE
AT 20°C Ω /km max
MAXIMUM
WIRE AND CABLE ALL
TYPES
mm
m m2
mm
mm
ohms
(b)
(c)
(d)
(e)
(f)
0.246
0.380
0.570
0.855
0.27
0.33
0.46
0.55
0.72
0.94
1.18
1.39
1.68
2.02
0.254
0.404
0.606
0.909
0.32
0.38
0.53
0.62
0.80
1.04
1.29
1.53
1.82
2.18
1/0.25
1/0.40
1/0.60
1/0.90
7/0.10
7/0.12
19/0.10
19/0.12
19/0.15
19/0.20
19/0.25
19/0.30
37/0.25
37/0.30
0.05
0.12
0.28
0.63
0.055
0.079
0.15
0.20
0.4
0.6
1.0
1.2
2.0
2.6
10
383.5
145.6
64.0
28.5
336.0
259.0
141.5
95.6
60.0
33.2
21.1
14.5
10.9
7.6
DEF STAN 61-12 (PART 18)/4
Table C
Dimensions of Complete Equipment Wires and Cables
WIRE
CABLE
TYPES
SIZE
(a)
30
26
23
19
30
28
26
24
22
20
18
16
14
12
1SB AND 2SB
1SBM 85,
1SBM 120
AND 2SBM
OVER
INSULATION
OVER
SCREEN
OVER SHEATH
1 AND 2
NUMBER
AND
NOMINAL
DIAMETER
OF
STRANDS
IN
CONDUCTOR
DIAMETER
RADIAL
THICKNESS OF
INSULATION
NOMINAL
MIN
MIN
MAX
MIN
MAX
MIN
MAX
mm
mm
mm
mm
mm
mm
mm
mm
mm
(b)
(c)
(d)
(e)
(f)
(g)
(h)
(j)
(k)
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.25
0.25
0.15
0.15
0.15
0.15
0.15
0.15
0.15
0.15
0.15
0.15
0.15
0.15
0.20
0.20
0.55
0.70
0.90
1.20
0.60
0.65
0.80
0.90
1.05
1.30
1.55
1.80
2.15
2.50
0.70
0.85
1.05
1.35
0.75
0.80
0.95
1.05
1.20
1.50
1.75
2.00
2.35
2.70
1.20
1.30
1.45
1.70
1.95
2.35
2.50
2.85
1.45
1.55
1.70
1.95
2.20
2.60
2.80
3.15
1.60
1.70
1.85
2.10
2.35
2.75
2.90
3.25
2.00
2.10
2.25
2.50
2.75
3.15
3.35
3.70
1/0.25
1/0.40
1/0.60
1/0.90
7/0.10
7/0.12
19/0.10
19/0.12
19/0.15
19/0.20
19/0.25
19/0.30
37/0.25
37/0.30
NOTE: - indicates that the column heading does not apply.
11
DEF STAN 61-12 (PART 18)/4
Table D
Mass of complete Equipment Wires and Cables
WIRE CABLE
TYPE
NUMBER AND
NOMINAL DIAMETER
OF STRANDS IN
CONDUCTOR
mm
(a)
MASS MAXIMUM
kg/100m
(b)
(c)
WIRE TYPES
1 AND 2
1/0.25
1/0.40
1/0.60
1/0.90
7/0.10
7/0.12
19/0.10
19/0.12
19/0.15
19/0.20
19/0.25
19/0.30
37/0.25
37/0.30
0.092
0.200
0.395
0.790
0.110
0.150
0.290
0.345
0.490
0.756
1.04
1.65
2.07
2.71
CABLE TYPES
1SB AND 2SB
19/0.10
19/0.12
19/0.15
19/0.20
19/0.25
19/0.30
37/0.25
37/0.30
0.576
0.720
0.911
1.27
1.77
2.5
3.03
3.81
CABLE TYPES
1SBM 85,
1SBM 120 AND
2SBM
19/0.10
19/0.12
19/0.15
19/0.20
19/0.25
19/0.30
37/0.25
37/0.30
0.829
0.988
1.20
1.60
2.13
2.92
3.48
4.31
8 Testing General
Unless otherwise stated, cable and wire samples for Qualification Approval
testing shall be size 22 (19/0.15) except for testing to 10.2.13 (Ageing
Test) when either size 22 or 20 shall be tested and 11.4 (Toxicity Test)
when sizes 30, 22 and 12 shall be tested.
12
DEF STAN 61-12(PART 18)/4
9 Electrical Tests
9.1 Electrical tests on wires types 1 and 2.
Wires Type 1 and Type 2
shall be subjected to the following electrical tests.
9.1.1 Dry spark test. Def Stan 61-12 (Part 0) clause 13.13 or 13.14.
test voltage shall be 5 kV rms for test 16b or 8 kV peak for test 16c.
The
9.1.2
Conductor resistance test.
In accordance with BS 2G 230, test 12.
The conductor resistance shall be tested for compliance with the values
stated in table B of this Defence Standard.
9.1.3 High voltage immersion test (on the insulation). Def Stan 61-12
(Part 0), clause 13.12, the test voltage shall be 2.5 kV rms. The number
of specimens to be tested shall be 3 random samples per wire size.
9.1.4 Insulation resistance test. Def Stan 61-12 (Part 0), clause 13.11.
The number of specimens to be tested shall be 3 random samples per wire
size. The insulation resistance shall not be less than 1 MΩ /km.
9.1.5 Surface resistance test.
Def Stan 61-12 (Part 0), clause 13.15.
Two specimens per wire size shall be tested.
9.1.6 Dielectric constant test. Def Stan 61-12 (Part 0), clause 13.17.
The dielectric constant shall not exceed the value given in 6.2.1.
9.2 Electrical tests on cables, types 1SB and 2SB. In addition to the
tests detailed in 9.1, which take place before screening, the screened
cable shall also be subjected to the following electrical test after
screening.
9.2.1 Voltage test on screened cable. In accordance with BS 2G 230,
test 16d, the test voltage shall be 2.5 kV rms between the conductor and
the screen.
9.3 Electrical tests on cables, types 1SBM and 2SBM. In addition to the
tests in 9.1 and 9.2 the completed screened and sheathed cable shall be
subjected to the following electrical test after sheathing.
9.3.1 Dry spark test.
voltage shall be 1 kV.
Def Stan 61-12 (Part 0), clause 13.13, the test
9.3.2 High voltage immersion test on sheath. Def Stan 61-12 (Part 0),
clause 13.12, the test voltage shall be 500 V rms. The number of specimens
shall be 3 per wire size.
10 Physical Tests
10.1 Mechanical test on conductor and screen braid. Strands taken from
the conductor of the completed wire, prior to screening if applicable and
strands to be used for the construction of the screen braid shall be
subjected to BS 2G 230 test 7 and shall meet the requirements of BS 2G 231,
Table 3 which shall be considered to be extended to include conductor
strands from 0.45 mm to 0.9 mm diameter, with the limits remaining as
stated. Additional strands shall be subjected to and meet the requirements
of BS 2G 231, clauses 4.4 and 4.5 (see also 6.1 and 6.3 of this Standard).
13
DEF STAN 61-12 (PART 18)/4
10.1.1 Solderability (conductor and screen). Def Stan 61-12 (Part 0),
clause 13.2. The wetting time shall not exceed 1 second. The solder bath
temperatures shall be 235°C ± 3°C and the solder shall be to
BS EN 29453 1994 grade KP with a non activated flux.
10.2 Physical tests on completed wires. Wires Types 1 and 2 and
cable/cores prior to screening, shall be subjected to the following
physical tests.
Def Stan 61-12 (Part 0),
10.2.1 Insulation thickness and concentricity.
clause 13.7. The requirements shall be as table C of this Standard.
10.2.2 Strand adhesion test (stranded conductors}.
(Part 0), clause 13.6.
Def Stan 61-12
10.2.3 Insulation shrinkage test. Def Stan 61-12 (Part 0), clause 13.30,
the retractions of the insulation shall not exceed 3 mm.
10.2.4 Insulation blocking. Def Stan 61-12 (Part 0), clause 13.31. Three
samples of wire of 19/0.15 conductor size shall be tested. The mandrel
diameter shall be 10 mm, the tension 5N.
10.2.5 Room temperature bend test. Def Stan 61-12 (Part 0), clause 13.19.
A mandrel of a diameter which is 8 times the maximum specified diameter of
the wire shall be used. The tensile force shall be as specified in
table G, for each wire size. One specimen per wire size shall be tested.
The test voltage shall be 2.5 kV rms. On completion of test, the
insulation shall exhibit neither crazing nor cracking.
10.2.5.1 Cold bend test. Def Stan 61-12 (Part 0), clause 13.20. A
mandrel of diameter which is 20 times the maximum specified diameter of the
wire shall be used. The tensile force shall be as specified in table G for
each wire size. The temperature of the chamber shall be -50°C ± 2°C and
the time shall be 6 hours. The test voltage shall be 2.5 kV rms. One
specimen per wire size shall be tested.
10.2.6 Dynamic cut-through test. Def Stan 61-12 (Part 0), clause 13.22.
Three specimens per wire size shall be tested. The specimens shall be
tested at a temperature of 120°C ± 5°C and the rate of loading shall be
6000 g/min at the sample. The minimum force required to achieve cut
through to the conductor shall be as specified in table G.
10.2.7 Notch propagation test. Def Stan 61-12 (Part 0), clause 13.23.
Three samples of wire of 19/0.15 conductor size shall be tested. The
voltage shall be 2.5 kV rms.
10.2.8 Resistance to fluids test. Three samples of wire of 19/0.15
conductor size shall be tested in accordance with Def Stan 61-12 Part 0
clause 13.37. Additional test fluids and temperatures shall be as
specified in table E of this Standard. Type 1 wires shall be subjected to
all the fluids listed except trichloroethane. Type 2 wires shall be
subjected to all the fluids listed with the exception of isopropyl alcohol,
aircraft fuel and trichloroethane. The duration of immersion shall be
7 days for all fluids. The test voltage shall be 2.5 kV rms.
14
DEF STAN 61-12 (PART 18)/4
Table E
List of Test Fluids, Additional Requirements
FLUID
TEMPERATURE °C
TEST FLUID
(c)
(b)
(a)
Oil
Detergent mineral oil
OMD-113
Fuel Oil
Dieso 47/20, NATO F-76
Def Stan 91-4 (or DERV)
TIME
(d)
100 ± 3
7 days
20 ± 3
7 days
50 ± 3
7 days
Deionized
Water
Na Cl 3.5% (sea water)
10.2.9 Scrape abrasion test. Def
Specimens shall be tested at 120°C
force as specified in table G and
than 500 cycles (1000 strokes) for
Stan 61-12 (Part 0), clause 13.24.
± 5°C, the blade shall be loaded with a
the specimens shall withstand not less
both Types 1 and 2 wire.
10.2.10 Delamination test. Def Stan 61-12 (Part 0), clause 13.32. The
ageing temperature shall be 135°C ± 3°C and the test temperature the wire
rated temperature.
10.2.11 Pliability test. Def Stan 61-12 (Part 0), clause 13.26, except
that the sample is to be straightened by hand. Samples of 19/0.15
conductor size shall be tested. The diameter of the mandrel shall be 5 mm
and the force gradually applied, as specified, sufficient to bend the wire
downwards through 89°.
The specimen shall remain in this position for 5 minutes and the force
recorded.
After this time the force shall be removed and the specimen allowed to
return towards its original position. At a time 5 minutes after removal of
the force the recoil angle shall be recorded.
The mean force required to bend the wire through 89° and the recoil angle
shall not exceed:
7N and 35° for Type 1 wire
12N and 60° for Type 2 wire
15
DEF STAN 61-12 (PART 18)/4
10.2.11 (Contd)
But in addition it is undesirable to have maximum force and recoil angle at
the same time, Type 1 wires shall have a figure of less than 175 for the
product of the force in newtons and the angle in degrees.
10.2.12 Thermal endurance test. Def Stan 61-12 (Part 0), clause 13.36.
The upper temperature limit in this test relates to the maximum continuous
temperature due to current flow. For Qualification Approval, samples of
wire of conductor size 19/0.15 or 19/0.2 shall be tested. The wire shall
be wrapped on a mandrel of 13 mm diameter with a weight of 400g for wire
size 19/0.15, 700g for wire size 19/0.2.
The Arrhenius plots so obtained are to form part of the submission to the
Qualification Approval Authority when seeking Qualification Approval. It
will be required to show that the insulation has a life exceeding 40,000 h
at 120°C.
10.2.12.1 Accelerated ageing. Def Stan 61-12 (Part 0), clause 13.29. The
mandrel diameters and tensile force to be applied to each end of the sample
shall be as specified in table G of this Standard. To determine the test
temperature for the Production Quality test requirements, a line is to be
drawn through the 120°C - 40,000 hours point parallel to the Arrhenius
plot. The temperature at which this line passes through 168 hours life is
to be the minimum test temperature.
10.2.13
Colour fastness tests
10.2.13.1 Colour fastness to water test. A sample of wire about 100 mm
long from which the conductor has been removed shall be cut into small
pieces and then immersed in about 10 times its own volume of distilled
water contained in a covered vessel, for a period of 48 hours at a
temperature of 70°C ± 1°C.
At the end of this period the water shall be
examined and shall be free from colour.
10.2.13.2 Bleeding of colour test. A test sample shall consist of a
bundle of wires, 300 mm long, made up of twisted pairs laid together and
bound with glass fibre string or tape at 50 mm intervals so that the pairs
cannot move in relation to each other. Each coloured wire is to be paired
with a white wire with a lay of eight times the diameter of the wire. The
test samples shall be stored in an air oven at 120°C ± 3°C for 72 hours.
At the end of this period the sample shall be stripped down and the
individual sample wires and control wires shall be examined for transfer of
colour. There shall be no appreciable colour staining and no significant
change in individual colours.
10.2.14 Colour durability test.
10.2.14.1
only.
Application.
This test is applicable to surface coloured wires
10.2.14.2 Test apparatus. A scrape abrasion test rig as described in
BS 2G 230, test 30 shall be used.
16
DEF STAN 61-12 (PART 18)/4
10.2.14.3 Test procedure. A specimen of wire shall be mounted in the
tester and the counter set to zero. Testing shall be carried out at a
temperature of 120°C ± 5°C using a force of 2 N. The test shall be
discontinued as soon as a continuous line is scored through the colour. To
achieve a pass 100 cycles shall have been made.
10.2.15 Resistance to solder heat test.
clause 13.35.
Def Stan 61-12 (Part 0),
10.2.16 Flexure endurance test. Def Stan 61-12 (Part 0), clause 13.28.
Three samples of wire of 19/0.15 conductor size shall be tested, at
temperature of 20°C ± 3°C. The mass shall be 0.6 kg for Type 1 wire and
1 kg for Type 2 wire;
(a) the insulation shall withstand the voltage test of 9.1.3;
(b) the wire shall be capable of passing its full rated current given in
table A, for 1000 cycles without any evidence of localized overheating.
10.3
Test applicable to 85°C completed cables
10.3.1 Cold bend.
Def Stan 61-12 (Part 0), clause 15.6.
10.3.2 Thermal endurance. Def Stan 61-12 (Part 0), clause 13.36 after
ageing for 28 days at a temperature of 110°C ± 2°C the cable is to be
subjected to and meet the requirements of Def Stan 61-12 (Part 0),
clause 13.20, the mandrel shall be 10 times the cable OD and the mass
sufficient to ensure that the sample remains in intimate contact with the
mandrel.
10.3.3 Sheath compatibility.
Def Stan 61-12 (Part 0), clause 16.8.
10.4 Test applicable to 120°C completed cables
10.4.1 Cold bend.
Def Stan 61-12 (Part 0), clause 15.6.
10.4.2 Thermal endurance.
As 10.3.2 of this Standard.
10.4.3 Sheath Compatibility.
10.4.4 Flammability.
Def Stan 61-12 (Part 0), clause 16.8.
Def Stan 61-12 (Part 0), clauses 13.39 and 13.40.
10.4.4.1 Procedure 1. Five specimens per insulation type shall be tested
and the flame shall be applied for 5 seconds.
10.4.4.2 Procedure 2. Five specimens per insulation type shall be tested
and the flame shall be applied for 12 seconds.
10.4.5 Critical oxygen index. Def Stan 61-12 (Part 0), clause 13.4.1.
The critical oxygen index shall not be less than 29.
10.4.6 Smoke index. Def Stan 61-12 (Part 0), clause 13.4.2. Three test
runs shall be performed. The smoke index is to be stated in terms of 1m of
cable. The average of three runs is not to exceed 12 (20 for maintenance
range).
17
DEF STAN 61-12 (PART 18)/4
10.4.7 Toxicity index. Def Stan 61-12 (Part 0), clause 13.43. The
toxicity index shall not exceed 5.0 per 100g of sheathing material. Where
the sheath contains more than one material the test sample is to contain
all the constituent parts in the same concentration as the completed
sheath.
10.4.8 Temperature index. Def Stan 61-12 (Part 0), clause 13.44.
temperature index value shall not be less than 250°C.
10.4.9
Resistance to fluids.
The
As 10.2.8 of this Standard.
11 Fire Hazard Tests
11.1 Flammability tests.
13.40.
Def Stan 61-12 (Part 0), clauses 13.39 and
11.1.1 Procedure 1. Five specimens per insulation type shall be tested
and the flame shall be applied for 5 seconds.
11.1.2 Procedure 2. Five specimens per insulation type shall be tested
and the flame shall be applied for 12 seconds.
11.2 Critical oxygen index test. Def Stan 61-12 (Part 0), clause 13.41.
The Critical Oxygen Index shall be not less than 29.
11.3 Smoke index test. Def Stan 61-12 (Part 0), clause 13.42. Three test
runs shall be performed. The smoke index is to be stated in terms of 1m of
wire and the average of the 3 runs is not to exceed 12 (20 maximum for
maintenance range).
11.4 Toxicity index test. Def Stan 61-12 (Part 0), clause 13.43. The
toxicity index (the average value of the 9 samples) on a 100g insulation
basis shall not exceed 0.2 when calculated to a 1m length of size 22 wire.
The hydrochloric acid gas content shall not be greater than 10 cm3/m.
11.5 Temperature index test.
Def Stan 61-12 (Part 0), clause 13.44.
temperature index value shall not be less than 250°C.
The
NOTE: Wire samples for Qualification Approval shall be size 22 (19/0.15)
except for testing to 10.2.13 when either size 22 or 20 shall be tested and
11.4 when sizes 30, 22 and 12 shall be tested.
18
DEF STAN 61-12 (PART 18)/4
Table F
Qualification Approval and Quality Assurance Test Applications
DESCRIPTION OF TEST
CLAUSE
NUMBER
QUALIFICATION
APPROVAL
PRODUCTION
QUALITY
PRODUCTION
ROUTINE
DEF STAN 61-12
(PART 0) CLAUSE
NO OR BS 2G 230
TEST NO
NO OF
SPECIMENS PER
WIRE SIZE OR
AS STATED
Dry spark or dry impulse
9.1.1
x
x
x
13.13
All
Production
Conductor resistance
9.1.2
x
x
x
BS 2G 230
Test 12
All
Production
High voltage immersion
9.1.3
x
x
-
13.12
3
Insulation resistance
9.1.4
x
x
-
13.11
3
Surface resistance
9.1.5
x
-
13.15
2
Dielectric
9.1.6
x
-
-
13.17
9.2.1
x
x
x
BS 2G 230
test 16d
1
All Production
constant
Voltage test, screened
cable
Dry spark test on sheath
9.3.1
x
x
x
13.13
All Production
High voltage immersion, on
sheath
9.3.2
x
x
-
13.12
3
Mechanical, conductor and
10.1
x
x
-
3
10.1.1
x
x
BS 2G 230
screen braid solderability
test 7
3
13.2
Insulation thickness and
1 0.2.1
x
x
x
13.7
3
Strand adhesion
1 0.2.2
x
x
-
1 3.6
8
Insulation shrinkage
1 0.2.3
x
x
1 3.30
1
Insulation blocking
1 0.2.4
x
-
-
1 3.31
3
Room temperature bend
Cold bend
1 0.2.5
x
x
x
x
-
1 3.19
10.2.5.1
1 3.20
1
1
Dynamic cut through
1 0.2.6
x
x
-
1 3.22
2
Notch
1 0.2.7
x
x
-
1 3.23
3
Resistance to fluids
1 0.2.8
x
-
-
1 3.37
3
Scrape adhesion
1 0.2.9
x
x
-
1 3.24
2
Delamination
1 0.2.10
x
-
1 3.32
3
Pliability
1 0.2.11
x
x
-
-
1 3.26
1
Thermal
x
-
Accelerated ageing
1 0.2.12
1 0.2.12.1
x
1 3.36
1 3.29
1
Colour fastness to water
1 0.2.13.1
x
1 0.2.13.2
x
-
-
1 per colour
Bleeding of colour
x
-
-
Colour durability
1 0.2.14
x
-
-
-
1 per colour
Resistance to solder heat
1 0.2.15
x
x
1
1 0.2.16
x
-
-
1 3.35
Flexure endurance
1 3.28
3
x
1 3.39
1 3.40
5
5
concentricity
propagation
endurance
4
1 per
Procedure 2
1 1.1.1
1 1.1.2
x
x
x
-
Critical oxygen index
1 1.2
x
-
-
1 3.41
5
Smoke index
1 1.3
x
-
-
1 3.42
3
Toxicity index
1 1.4
x
-
-
1 3.43
3
T emperature index test
1 1.5
x
-
-
1 3.44
5
Flammability Procedure 1
19
colour
DEF STAN 61-12 (PART 18)/4
Table F - Concluded
DESCRIPTION OF TEST
CLAUSE
NUMBER
Cold Bend
Thermal Endurance
QUALI-
PRODUC-
FICATION
APPROVAL
TION
QUALITY
PRODUCTION
ROUTINE
DEF STAN 61-12
N0 OF
(PART 0) CLAUSE
NO OR BS 2G 230
SPECIMENS PER
TEST NO
WIRE SIZE OR
AS STATED
10.3.1
10.4.1
x
x
-
15.6
1
10.3.2
x
-
-
13.36
4
x
-
-
16.8
7
x
x
-
13.39 & 13.40
5
10.4.2
Sheath Compatibility
10.3.3
10.4.3
Flammability
10.4.4.1
10.4.4.2
Critical Oxygen Index
10.4.5
x
-
-
13.41
5
Smoke Index
10.4.6
x
-
-
13.42
5
Toxicity Index
10.4.7
x
-
-
13.43
3
-
13.44
3
-
13.37
3
Temperature Index
10.4.8
x
-
Resistance to Fluids
10.4.9
x
-
Table G
Specific Test Requirements
SIZE
ACCELERATED
ACCELERATED
COLD
SCRAPE
DYNAMIC
CUT
AGEING
AGEING
BEND
ABRASION
THROUGH
FORCE
FORCE
N
ROOM
AND
TEMP
FORCE
TYPE
BEND
MANDREL
N
1
MAX
DIA
FORCE
N
N
mm
TYPE
2
TYPE
1
TYPE
30
0.5
2.0
10.0
2.0
1.0
3.0
28
1.0
3.5
10.0
4.0
1.0
3.0
30.0
26
1.6
5.0
10.0
5.0
1.0
4.0
30.0
24
2.5
3.0
7.0
10.0
10.0
13.0
20.0
20.0
1.2
5.0
40.0
23
1.2
5.0
40.0
22
20
4.0
7.0
10.0
13.0
20.0
20.0
20.0
25.0
1.5
6.0
70.0
6.0
100.0
7.0
100.0
7.0
120.0
120.0
19
8.0
20.0
13.0
20.0
20.0
1.5
1.5
18
10.0
20.0
20.0
30.0
1.6
16
10.0
20.0
20.0
30.0
2.0
8.0
14
10.0
20.0
25.0
30.0
2.5
10.0
120.0
12
10.0
20.0
30.0
30.0
3.0
12.0
120.0
12 Qualification Approval
Qualification Approval procedures should be as defined in Def Stan 61-12
(Part 0).
20
2
DEF STAN 61-12 (PART 18)/4
13 Quality Assurance Requirements
13.1 Procedure
13.1.1 The manufacturer shall ensure Quality of Conformance to the
specified requirements by the following methods:
(a) inspection of materials and wires and cables in the course of
manufacture to ensure that the requirements of this Standard are met and
the necessary standard of workmanship and process control is being
maintained;
(b)
13.2
subjection of all wires and cables to the tests specified in table F.
Test and sampling levels on completed wires and cables
13.2.1 All wires and cables are to be subjected to Production Routine
tests, specified in table F.
13.2.2 On satisfactory completion of Production Routine tests random
samples shall be taken during cutting for dispatch and subjected to
Production Quality tests. The number of random samples required shall be
determined by the total production batch.
13.2.3 In a production run of 100 km or less, one random sample shall be
taken and subjected to Production Quality tests.
13.2.4 In a production run between 100 and 500 km one random sample shall
be taken from each of two separate factory drums and subjected to
Production Quality tests.
13.2.5 In a production run greater than 500 km one extra sample shall be
taken from each further 500 km and subjected to Production Quality tests.
13.2.6 The Quality Assurance Authority may at intervals select samples of
wires and cables for Quality audit or check testing in their own
laboratories. Samples shall be selected by the supervising representative
of the Quality Assurance Authority.
NOTE: The manufacturer may, if he wishes, submit an alternative sampling
plan, covering the requirements of clause 13, for approval by the DELSC
Cables and Wires Subcommittee.
14 Packaging and Labelling
Packaging and labelling shall be in accordance with the requirements
specified in Agreed Industry Standard CPU/AIS/300.
Notes on Tables
The definitions of tables I and II - items respectively are as follows:
Table I. Standard items to be used whenever practicable in preference to
all others. They may replace one or more non-standard items.
Table II. Non-standard items for which there is no replacement. A
non-standard item is to be provisioned only for maintenance of existing
equipment.
21
Table I(A)
Standard Range
Equipment Wires, Electrical - Type 1 Limited Fire Hazard Insulation, Unscreened (Toxicity Index ≤ 0.2
NATO STOCK NUMBER 6145-99PAGE
CONDUCTOR
LINE
SIZE
RED
BLUE
GREEN
YELLOW
NO
BLACK
WHITE
BROWN
VIOLET
ORANGE
GREY
PINK
YELLOW
Green
(a)
(b)
(c)
(d)
(e)
(f)
(g)
(h)
(j)
(k)
(l)
(m)
(n)
1
1/0.25
891-9431
891-9432
891-9433
891-9434
891-9435
891-9436
891-9437
891-9438
891-9439
891-9440
891-9441
891-9442
2
1/0.40
891-9443
891-9444
891-9455
891-9446
891-9447
891-9448
891-9449
891-9450
891-9451
891-9452
891-9453
891-9454
3
4
1/0.60
891-9455
891-9456
891-9457
891-9458
891-9459
891-9460
891-9461
891-9462
891-9463
891-9464
891-9465
891-9466
1/0.90
891-9467
891-9468
891-9469
891-9470
891-9471
891-9472
891-9473
891-9474
891-9475
891-9476
891-9477
891-9478
5
7/0.10
891-9479
891-9480
891-9481
891-9482
891-9483
891-9484
891-9485
891-9486
891-9487
891-9488
891-9489
891-9490
6
7/0.12
891-9491
891-9492
891-9493
891-9494
891-9495
891-9496
891-9497
891-9498
891-9499
891-9500
891-9501
891-9502
7
19/0.10
891-9503
891-9504
891-9505
891-9506
891-9507
891-9508
891-9509
891-9510
891-9511
891-9512
891-9513
891-9514
8
19/0.12
891-9515
891-9516
891-9517
891-9518
891-9519
891-9520
891-9521
891-9522
891-9523
891-9524
891-9525
891-9526
9
19/0.15
891-9527
891-9528
891-9529
891-9530
891-9531
891-9532
891-9533
891-9534
891-9535
891-9536
891-9537
891-9538
10
19/0.20
891-9539
891-9540
891-9541
891-9542
891-9543
891-9544
891-9545
891-9546
891-9547
891-9548
891-9549
891-9550
11
19/0.25
891-9551
891-9552
891-9553
891-9554
891-9555
891-9556
891-9557
891-9558
891-9559
891-9560
891-9561
891-9562
12
19/0.30
891-9563
891-9564
891-9565
891-9566
891-9567
891-9568
891-9569
891-9570
891-9571
891-9572
891-9573
891-9574
13
37/0.25
891-9575
891-9576
891-9577
891-9578
891-9579
891-9580
891-9581
891-9582
891-9583
891-9584
891-9585
891-9568
14
37/0.30
891-9587
891-9588
891-9589
891-9590
891-9591
891-9592
891-9593
891-9594
891-9595
891-9596
891-9597
891-9598
NOTE: Base colour is indicated by capital letters.
Table I(B)
Standard Range
Equipment Wires, Electrical - Type 2 Limited Fire Hazard Insulation, Unscreened (Toxicity Index ≤ 0.2)
NATO STOCK NUMBER 6145-99PAGE
CONDUCTOR
LINE
SIZE
RED
BLUE
GREEN
YELLOW
BLACK
WHITE
BROWN
VIOLET
NO
ORANGE
GREY
PINK
YELLOW
Green
(a)
(b)
(c)
(d)
(e)
(f)
(g)
891-9601
891-9613
891-9602
891-9614
891-9603
891-9604
891-9605
891-9615
891-9617
891-9625
891-9626
891-9627
891-9616
891-9628
891-9629
(h)
(k)
(l)
(m)
(n)
891-9606
891-9607
891-9608
891-9609
891-9610
891-9618
891-9619
891-9620
891-9621
891-9622
891-9631
891-9633
891-9634
891-9643
891-9632
891-9644
891-9645
891-9646
891-9658
891-9670
(j)
1
1/0.25
891-9599
891-9600
2
1/0.40
1/0.60
891-9611
891-9623
891-9612
891-9624
1/0.90
891-9635
891-9636
891-9637
891-9638
891-9639
891-9640
891-9641
891-9630
891-9642
5
7/0.10
891-9647
891-9648
891-9649
891-9650
891-9652
891-9653
891-9654
891-9655
891-9656
891-9657
6
7/0.12
891-9660
891-9675
891-9680
19/0.12
19/0.15
891-9683
891-9685
891-9686
891-9689
891-9690
891-9667
891-9679
891-9691
891-9669
891-9681
8
891-9676
891-9688
891-9665
891-9677
891-9668
891-9672
891-9684
891-9662
891-9674
891-9666
19/0.10
891-9661
891-9673
891-9664
7
891-9659
891-9671
891-9651
891-9663
891-9692
891-9693
891-9695
891-9696
891-9697
891-9698
891-9699
891-9701
891-9702
891-9703
891-9704
891-9705
891-9706
19/0.20
891-9707
891-9708
891-9709
891-9710
891-9711
891-9714
891-9715
891-9716
891-9717
891-9718
11
19/0.25
891-9719
891-9720
891-9721
891-9722
891-9723
891-9726
891-9727
891-9728
891-9729
891-9730
12
19/0.30
891-9731
891-9732
891-9733
891-9734
891-9735
891-9724
891-9736
891-9713
891-9725
891-9737
891-9738
891-9739
891-9740
891-9741
891-9742
13
37/0.25
891-9743
891-9744
891-9745
891-9746
891-9747
891-9748
891-9749
891-9750
891-9751
891-9752
891-9753
891-9754
14
37/0.30
891-9755
891-9756
891-9757
891-9758
891-9759
891-9760
891-9761
891-9762
891-9763
891-9764
891-9765
891-9766
3
4
9
10
891-9687
NOTE: Base colour is indicated by capital letters.
891-9700
891-9712
891-9678
891-9682
891-9694
Table I(C)
Standard Range
Cables, Special Purpose, Electrical and Cables, Power, Electrical Type 1SB and 2SB Limited Fire Hazard Insulation, Screened (Toxixity Index ≤ 0.2)
NATO STOCK NUMBER
6145-99PAGE
LINE
NO
CONDUCTOR
SIZE
(a)
ITEM NAME
(b)
TYPE 1SB
TYPE 2SB
PINK
INSULATION
WHITE
INSULATION
PINK
INSULATION
(c)
(d)
(e)
WHITE
INSULATION
(f)
1
2
3
4
19/0.10
19/0.12
19/0.15
19/0.20
CABLE
SPECIAL
PURPOSE
ELECTRICAL
891-9799
891-9803
891-9807
891-9811
891-9800
891-9804
891-9808
891-9812
891-9801
891-9805
891-9808
891-9813
891-9802
891-9806
891-9810
891-9814
5
6
7
8
19/0.25
19/0.30
37/0.25
37/0.30
CABLE
POWER
ELECTRICAL
891-9815
891-9819
891-9823
891-9827
891-9816
891-9820
891-9824
891-9828
891-9817
891-9821
891-9825
891-9829
891-9818
891-9822
891-9826
891-9830
NOTE: The NATO Stock numbers in columns (c), (d), (e) and (f) are only applicable to cables where the insulation
is coloured pink or white (as applicable) and the sheath colour is black.
Table I(D)
Standard Range
Cables, Special Purpose, Electrical and Cables, Power, Electrical Type 1SBM 85, 1SBM 120 and 2SBM Limited Fire Hazard Insulation, Screened and Sheathed (Toxicity index ≤ 0.2)
NATO STOCK NUMBER
6145-99PAGE
LINE
NO
CONDUCTOR
SIZE
ITEM NAME
TYPE 1SBM 85
PINK
INSULATION
(a)
(b)
(c)
WHITE
INSULATION
(d)
TYPE 1SBM 120
TYPE 2SBM
PINK
INSULATION
WHITE
INSULATION
PINK
INSULATION
(e)
(f)
(g)
WHITE
INSULATION
(h)
1
2
3
4
19/0.10
19/0.12
19/0.15
19/0.20
CABLE
SPECIAL
PURPOSE
ELECTRICAL
891-9767
891-9771
891-9775
891-9779
891-9768
891-9772
891-9776
891-9780
891-9769
891-9773
891-9777
891-9781
891-9770
891-9774
891-9778
891-9782
5
6
7
8
19/0.25
19/0.30
37/0.25
37/0.30
CABLE
POWER
ELECTRICAL
891-9783
891-9787
891-9791
891-9795
891-9784
891-9788
891-9792
891-9796
891-9785
891-9789
891-9793
891-9797
891-9786
891-9790
891-9794
891-9798
NOTE: The NATO Stock numbers in columns (c), (d), (e) and (f) are only applicable to cables where the insulation
is coloured pink or white (as applicable) and the sheath colour is black.
Table II(A)
Maintenance Range
Equipment Wires, Electrical - Type 1 Limited Fire Hazard Insulation, Unscreened (Toxicity Index > 0.2 ≤ 1.5)
NATO STOCK NUMBER 6145-99PAGE
CONDUCTOR
LINE
SIZE
BLUE
RED
GREEN
YELLOW
BLACK
WHITE
BROWN
VIOLET
ORANGE
GREY
PINK
NO
YELLOW
Green
(a)
(b)
(c)
(d)
(e)
(f)
(g)
(h)
(j)
(k)
(l)
(m)
771-6213
017-5526
771-6214
771-6215
771-6216
729-3026
017-5535
O17-5545
017-5554
017-5671
1
1/0.25
771-6206
771-6207
771-6208
771-6209
771-6210
771-6211
771-6212
2
1/0.40
017-5422
017-5431
017-5440
017-5449
017-5458
017-5508
(n)
3
1/0.60
017-5423
017-5432
017-5441
017-5450
017-5459
017-5509
017-5517
017-5518
017-5527
017-5536
017-5546
017-5555
017-5672
4
1/0.90
017-5424
017-5433
017-5442
017-5451
017-5460
017-5510
017-5519
017-5528
017-5537
017-5547
017-5556
5
7/0.10
771-6217
771-6218
771-6219
771-6220
771-6221
771-6222
771-6223
771-6224
771-6225
771-6226
771-6227
017-5673
729-3041
6
7/0.12
728-6125
771-6228
771-6229
771-6230
771-6231
771-6232
771-6233
771-6234
771-6235
771-6236
771-6237
729-3042
7
19/0.10
771-6238
771-6239
771-6240
771-6241
771-6242
771-6243
729-3043
017-5425
017-5443
017-5452
017-5502
017-5511
017-5538
017-5557
729-3025
9
19/0.15
017-5426
017-5434
017-5435
771-6247
017-5548
771-6248
19/0.12
771-6245
017-5529
771-6246
8
771-6244
017-5520
017-5444
017-5453
017-5503
017-5512
017-5521
017-5530
017-5539
017-5549
017-5558
017-5675
10
19/0.20
017-5427
017-5436
017-5445
017-5454
017-5504
017-5513
017-5522
017-5531
017-5540
017-5550
017-5559
017-5676
11
19/0.25
771-6249
771-6250
771-6251
771-6252
771-6253
771-6254
771-6255
771-6256
771-6257
771-6258
771-6259
729-3044
12
19/0.30
017-5428
017-5437
017-5446
017-5455
017-5505
017-5514
077-5523
017-5532
017-5541
017-5551
017-5560
017-5677
13
37/0.25
771-6260
771-6261
771-6262
771-6263
771-6264
771-6265
771-6266
771-6267
771-6268
771-6269
771-6270
729-3039
14
37/0.30
771-6271
771-6272
771-6273
771-6274
771-6275
771-6276
771-6277
771-6278
771-6279
771-6280
771-6281
729-3040
NOTE: Base colour is indicated by capital letters.
Table II(B)
Maintenance Range
Equipment Wires, Electrical - Type 2 Limited Fire Hazard Insulation, Unscreened (Toxicity Index > 0.2 ≤ 1.5)
NATO STOCK NUMBER 6145-99PAGE
CONDUCTOR
LINE
NO
SIZE
RED
BLUE
GREEN
YELLOW
WHITE
BROWN
VIOLET
ORANGE
GREY
PINK
YELLOW
Green
(a)
(b)
(c)
(d)
(e)
(f)
(g)
(h)
771-6282
771-6293
771-6283
771-6294
771-6284
771-6295
771-6285
771-6286
771-6297
771-6287
771-6288
771-6296
771-6298
771-6305
771-6306
771-6307
771-6318
771-6308
771-6309
771-6299
771-6310
771-6311
771-6319
771-6321
771-6332
771-6322
771-6330
771-6341
771-6320
771-6331
771-6312
771-6323
771-6342
1
1/0.25
2
1/0.40
3
1/0.60
1/0.90
771-6304
771-6315
771-6316
771-6317
7/0.10
771-6326
771-6337
771-6327
771-6328
771-6339
771-6329
4
5
BLACK
(k)
(l)
(m)
(n)
771-6289
771-6290
771-6291
771-6292
722-3157
771-6300
771-6301
771-6302
771-6313
771-6303
771-6314
729-3046
729-3027
771-6324
771-6325
729-3028
771-6334
771-6335
771-6343
771-6333
771-6344
771-6345
771-6336
771-6347
729-3030
729-3029
7
7/0.12
19/0.10
771-6348
771-6338
771-6349
771-6350
771-6351
771-6352
771-6353
771-6355
771-6356
771-6358
729-3031
8
19/0.12
771-6359
771-6360
771-6361
771-6362
771-6363
771-6364
771-6354
771-6365
771-6346
771-6357
771-6366
771-6367
771-6368
771-6369
729-3032
9
10
19/0.15
19/0.20
771-6370
771-6371
771-6372
771-6374
771-6375
771-6376
771-6377
771-6383
728-3148
728-3149
728-3150
728-3151
771-6379
728-3153
729-3033
771-6382
771-6378
728-3152
771-6380
771-6381
771-6373
728-3147
728-3154
729-3034
11
19/0.25
728-3155
728-3156
728-3157
728-3158
728-3159
728-3160
728-3161
728-3162
728-3163
728-3164
728-3165
729-3035
12
19/0.30
728-3166
728-3167
728-3168
728-3169
728-3170
728-3171
728-3172
728-3173
728-3174
728-3175
728-3176
729-3036
6
771-6340
(j)
13
37/0.25
728-3177
728-3178
728-3179
728-3780
728-3181
728-3782
728-3183
728-3184
728-3185
728-3186
728-3187
729-3037
14
37/0.30
728-3188
728-3189
728-3790
728-3191
728-3192
728-3193
728-3194
728-3195
728-3196
728-3197
728-3198
729-3038
NOTE: Base colour is indicated by capital letters.
Table II(C)
Maintenance Range
Cables, Special Purpose, Electrical and Cables, Power, Electrical Type 1SB and 2SB Limited Fire Hazard Insulation, Screened (Toxicity Index > 0.2 ≤ 1.5)
NATO STOCK NUMBER
6145-99PAGE
LINE
NO
CONDUCTOR
SIZE
(a)
ITEM NAME
(b)
TYPE 1SB
TYPE 2SB
PINK
INSULATION
WHITE
INSULATION
PINK
INSULATION
WHITE
INSULATION
(c)
(d)
(e)
(f)
1
2
3
4
19/0.10
19/0.12
19/0.15
19/0.20
CABLE
SPECIAL
PURPOSE
ELECTRICAL
770-8895
771-6178
771-6182
771-6186
771-6176
771-6180
771-6184
771-6188
771-6175
771-6179
771-6183
771-6187
771-6177
771-6181
771-6185
771-6189
5
6
7
8
19/0.25
19/0.30
37/0.25
37/0.30
CABLE
POWER
ELECTRICAL
771-6190
771-6194
771-6198
771-6202
771-6192
771-6196
771-6200
771-6204
771-6191
771-6195
771-6199
771-6203
771-6193
771-6197
771-6201
771-6205
NOTE: The NATO Stock numbers in columns (c), (d), (e) and (f) are only applicable to cables where the insulation
is coloured pink or white (as applicable) and the sheath colour is black.
Table II(D)
Maintenance Range
Cables, Special Purpose, Electrical and Cables, Power, Electrical Type 1SBM and 2SBM Limited Fire Hazard Insulation, Screened and Sheathed (Toxicity Index > 0.2 ≤ 1.5)
NATO STOCK NUMBER
6145-99PAGE
LINE
NO
CONDUCTOR
SIZE
(a)
ITEM NAME
(b)
TYPE 1SBM
TYPE 2SBM
PINK
INSULATION
WHITE
INSULATION
PINK
INSULATION
WHITE
INSULATION
(c)
(d)
(e)
(f)
1
2
3
4
19/0.10
19/0.12
19/0.15
19/0.20
CABLE
SPECIAL
PURPOSE
ELECTRICAL
728-3199
017-5788
017-5789
017-5790
728-3200
728-3201
728-3222
728-3223
728-3202
728-3204
728-6126
728-3207
728-3203
728-3205
728-3206
728-6127
5
6
7
8
19/0.25
19/0.30
37/0.25
37/0.30
CABLE
POWER
ELECTRICAL
728-3208
017-5791
728-3214
728-3218
728-3209
728-3224
728-3215
728-3219
728-3210
728-3212
728-3216
728-3220
728-3211
728-3213
728-3217
728-3221
NOTE: The NATO Stock numbers in columns (c), (d), (e) and (f) are only applicable to cables where the insulation
is coloured pink or white (as applicable) and the sheath colour is black.
Table II(E)
Maintenance Range
Equipment Wires, Electrical - Type 1 Limited Fire Hazard Bicoloured Insulation, Unscreened (Toxicity Index > 0.2
≤ 1.5)
NATO STOCK NUMBER 6145-99PAGE
CONDUCTOR
LINE
SIZE
No
RED
GREEN
RED
WHITE
RED
ORANGE
GREY
GREEN
WHITE
BROWN
ORANGE
GREY
blue
red
black
red
brown
red
red
blue
blue
blue
blue
blue
(b)
(c)
(d)
(e)
(f)
(g)
(h)
1/0.25
891-9024
891-9064
1/0.40
891-9040
017-5581
891-9056
2
3
891-9032
017-5572
891-9048
017-5563
017-5590
017-5608
1/0.60
017-5564
017-5573
017-5582
017-5591
017-5599
017-5600
4
1/0.90
017-5565
017-5574
017-5583
017-5592
(a)
1
(j)
(k)
(l)
891-9072
891-9080
891-9088
891-9096
891-9104
017-5617
017-5626
017-5635
017-5644
017-5653
017-5662
017-5609
017-5618
017-5627
017-5636
017-5645
017-5654
017-5663
017-5601
017-5610
017-5619
017-5628
017-5637
017-5646
017-5655
017-5664
891-9057
891-9065
891-9073
891-9081
891-9089
891-9097
891-9105
891-9113
(m)
(n)
891-9112
5
7/0.10
891-9025
891-9033
891-9041
891-9049
6
7/0.12
891-9026
891-9034
891-9042
891-9050
891-9058
891-9066
891-9074
891-9082
891-9090
891-9098
891-9106
891-9114
891-9067
891-9075
891-9083
891-9091
891-9099
891-9107
891-9115
7
19/0.10
891-9027
891-9035
891-9043
891-9051
891-9059
8
19/0.12
891-9028
891-9036
891-9044
891-9052
891-9060
891-9068
891-9076
891-9084
891-9092
891-9100
891-9108
891-9116
017-5612
017-5621
017-5630
017-5639
017-5648
017-5657
017-5666
9
19/0.15
017-5567
017-5576
017-5585
017-5594
017-5603
10
19/0.20
017-5568
017-5577
017-5586
017-5595
017-5604
017-5613
017-5622
017-5631
017-5640
017-5649
017-5658
017-5667
891-9061
891-9069
891-9077
891-9085
891-9093
891-9101
891-9109
891-9117
017-5668
11
19/0.25
891-9029
891-9037
891-9045
891-9053
12
19/0.30
017-5569
017-5578
017-5587
017-5596
017-5605
017-5614
017-5623
017-5632
017-5641
017-5650
017-5659
13
37/0.25
891-9030
891-9038
891-9046
891-9054
891-9062
891-9070
891-9078
891-9086
891-9094
891-9102
891-9110
891-9118
14
37/0.30
891-9031
891-9039
891-9047
891-9055
891-9063
891-9071
891-9079
891-9087
891-9095
891-9103
891-9111
891-9119
NOTE: Base colour is indicated by capital letters.
Table II (E) - Concluded
Maintenance Range
Equipment Wires, Electrical - Type 1 Limited Fire Hazard Bicoloured Insulation, Unscreened (Toxicity Index > 0.2 ≤ 1.5)
PAGE
CONDUCTOR
LINE
SIZE
NO
(a)
1
2
3
4
5
6
7
8
1/0.25
1/0.40
GREEN
WHITE
black
green
ORANGE
green
(b)
(c)
(d)
(e)
891-9120
017-5680
891-9128
017-5689
891-9136
017-5698
017-5690
017-5691
017-5699
017-5700
1/0.60
017-5681
1/0.90
7/0.10
017-5682
7/0.12
19/0.10
19/0.12
9
10
19/0.15
19/0.20
891-9121
891-9122
891-9123
891-9124
017-5684
017-5685
891-9129
891-9130
891-9137
GREEN
brown
GREY
ORANGE
WHITE
black
black
(f)
(g)
(h)
(j)
891-9144
017-5707
891-9152
017-5716
891-9160
017-5725
017-5708
017-5717
017-5718
891-9153
017-5709
891-9145
891-9146
green
WHITE
WHITE
GREY
ORANGE
orange
grey
brown
brown
(k)
(l)
(m)
(n)
891-9168
891-9176
891-9184
891-9192
891-9200
017-5743
017-5744
017-5752
017-5753
017-5761
017-5762
017-5770
891-9208
017-5779
017-5726
017-5734
017-5735
017-5727
017-5736
017-5745
017-5754
017-5763
017-5771
017-5772
017-5780
017-5781
891-9154
891-9155
891-9161
891-9162
891-9163
891-9169
891-9170
891-9177
891-9178
891-9156
891-9164
891-9171
891-9172
017-5729
017-5738
017-5730
017-5739
891-9165
017-5731
891-9173
017-5748
891-9181
017-5740
017-5749
891-9131
891-9138
891-9139
891-9132
017-5693
891-9140
017-5702
017-5711
017-5694
017-5703
017-5712
017-5720
017-5721
891-9147
891-9148
brown
WHITE
891-9179
891-9180
017-5747
891-9185
891-9193
891-9201
891-9209
891-9186
891-9187
891-9194
891-9195
891-9202
891-9203
891-9210
891-9211
891-9188
891-9196
891-9204
891-9212
017-5756
017-5757
017-5765
017-5774
017-5766
017-5775
017-5783
017-5784
891-9189
891-9197
017-5767
891-9205
891-9213
017-5758
017-5776
017-5785
11
19/0.25
891-9125
891-9133
891-9141
891-9149
891-9157
12
19/0.30
017-5686
017-5695
017-5704
017-5722
13
37/0.25
891-9126
891-9134
891-9142
017-5713
891-9150
891-9158
891-9166
891-9174
891-9182
891-9190
891-9198
891-9206
891-9214
14
37/0.30
891-9127
891-9135
891-9143
891-9151
891-9159
891-9167
891-9175
891-9183
891-9191
891-9199
891-9207
891-9215
NOTE: Base colour is indicated by capital letters.
Blank Page
DEF STAN 61-12 (PART 18)/4
ANNEX A
Type Designator Coding Structure
A.1 Scope
A.1.1 This annex gives instructions for creating a designator which, when
associated with this particular Defence Standard Number, will uniquely
identify a specific item manufactured to the Standard’s requirements.
A.1.2 Whilst the primary purpose of such a designator is NATO Stock Number
(NSN) assignment, it may also be used by anyone else requiring a similar
designator facility.
A.2 Coding Structure for the Type Designator
A.2.1 This consists of 3 or more elements separated from each other by
oblique strokes.
A.2.2 The first element is the relevant cable or wire type code from the
following table:
Table A
Cable and Wire Type Coding
TYPE
Type
Type
Type
Type
Type
Type
Type
1
1SB
1SBM 85
1SBM 120
2
2SB
2SBM
DESCRIPTION
CODE
No Screen or Sheath
Screen only
Screen and 85°C Rated Sheath
Screen and 120°C Rated Sheath
No Screen or Sheath
Screen only
Screen and Sheath
1
1SB
1SBM 85
1SBM 120
2
2SB
2SBM
A-1
DEF STAN 61-12 (PART 18)/4
ANNEX A (Continued)
A.2.3 The second is the relevant conductor size code letter from the
following table:
Table B
Conductor Size
SIZE
(a)
30
26
23
19
30
28
26
24
22
20
18
16
14
12
NUMBER AND
NOMINAL DIAMETER
OF STRANDS IN
CONDUCTOR
NOMINAL
CROSS
SECTIONAL
mm
(b)
1/0.25
1/0.40
1/0.60
1/0.90
7/0.10
7/0.12
19/0.10
19/0.12
19/0.15
19/0.20
19/0.25
19/0.30
37/0.25
37/0.30
mm 2
(c)
0.05
0.12
0.28
0.63
0.055
0.079
0.15
0.20
0.33
0.59
0.93
1.34
1.82
2.50
CODE
LETTER
(d)
A
D
G
K
B
C
E
F
H
J
L
M
N
P
A.2.4 The third element is the relevant insulation base colour code
letters from the following table:
Table C
Insulation Base Colour
COLOUR
LETTER CODE
RED
BLUE
GREEN
YELLOW
BLACK
WHITE
BROWN
VIOLET
ORANGE
GREY
PINK
RE
BU
GR
YE
BL
WH
BR
VL
RG
GY
PK
A-2
DEF STAN 61-12 (PART 18)/4
Annex A (Concluded)
A.2.4.1 Bicolours. When a bicolour wire requires to be coded, codes for
each individual colour are used separated by an oblique stroke (see example
below).
A.3
Diagram of Coding Structure
1st element
2nd element
1S
E
3rd element
YE
Subsequent
element
(if required)
GR
ISSUE NO 4
Issue No
Bicolour
Insulation
base colour
Conductor
size
Wire or
Cable Type
A.4 Example of Type Designators
A.4.1 ISBM 85/P/WH/3: This is a screened and sheathed Type 1 cable having
a conductor of 37 strands, each of 0.30 mm diameter and insulation base
colour white to Issue 3, suitable for continuous use in the temperature
range -50°C to +85°C.
A.4.2 2/D/VL/3: This is a non-screened, no sheathed Type 2 wire, having a
single solid conductor with a diameter of 0.40 mm and insulation base
colour violet to Issue 3.
a.4.3 1SB/E/YE/GR/3: This is a screened Type 1 cable having a conductor of
19 strands each of 0.10 mm, with insulation base colour yellow and
secondary colour green to Issue 3.
NOTE: In all cases the type designator shall be preceded by
‘Def Stan 61-12 (Part 18)’.
A-3
DEF STAN 61-12 (PART 18)/4
©
Crown Copyright 1994
Published by and obtainable from:
Ministry of Defence
Directorate of Standardization
Kentigern House
65 Brown Street
GLASGOW G2 8EX
Tel No:
Fax:
041-224 2531/2
041-224 2503
This Standard may be fully reproduced
except for sale purposes. The
following conditions must be observed:
1 The Royal Coat of Arms and the
publishing imprint are to be
omitted.
2 The following statement is to be
inserted on the cover:
‘Crown Copyright. Reprinted by
(name of organization) with the
permission of Her Majesty’s
Stationery Office.’
Requests for commercial reproduction
should be addressed to MOD Stan 1,
Kentigern House, 65 Brown Street,
Glasgow G2 8EX
The following Defence Standard file reference relates to the work on this
Standard - D/D Stan 372/7/19.
Contract Requirements
When Defence Standards are incorporated into contract users are responsible
for their correct application and for complying with contract requirements.
Revision of Defence Standard
Defence Standards are revised when necessary by the issue either of
amendments or of revised editions. It is important that users of Defence
Standards should ascertain that they are in possession of the latest
amendments or editions. Information on all Defence Standards is contained
in Def Stan 00-00 (Part 3) Section 4, Index of Standards for Defence
Procurement - Index of Defence Standards and Specifications published
annually and supplemented periodically by Standards in Defence News. Any
person who, when making use of a Defence Standard encounters an inaccuracy
or ambiguity is requested to notify the Directorate of Standardization
without delay in order that the matter may be investigated and appropriate
action taken.
92/70002
DEF STAN 61-12 (PART 18)/4 - 6 JANUARY 1995
WIRES, CORDS AND CABLES, ELECTRICAL
METRIC UNITS
PART 18: EQUIPMENT WIRES LIMITED FIRE HAZARD
AMENDMENT 1
1. Page 13, Clause 9.1.4, line 3
Delete: 1
M Ω /Km
Insert: 0.2 M Ω/Km
2.
Make a note of this amendment on the amendment record.
D/D Stan/372/07/19
92/70002
30 June 1995
Ministry of Defence
Directorate of Standardization
Stan 7b
Kentigern House
65 Brown Street
GLASGOW G2 8EX
DEF STAN 61-12 (PART 18)/4
WIRES, CORDS AND CABLES, ELECTRICAL
METRIC UNITS
PART 18: EQUIPMENT WIRES LIMITED FIRE HAZARD
AMENDMENT 2
1.
2.
Page 25 Table I(D)
Delete:
Table I(D)
Insert:
New Table I(D)
Make a note of this amendment on the amendment record.
D/D Stan/372/07/19
92/70002
23 October 1996
Ministry of Defence
Directorate of Standardization
Stan Ops 2b
Kentigern House
65 Brown Street
GLASGOW G2 8EX
Table I(D)
Standard Range
Cables, Special Purpose, Electrical and Cables, Power, Electrical Type 1SBM 85, 1SBM 120 and 2SBM Limited Fire Hazard Insulation, Screened and Sheathed (Toxicity Index ≤ 0.2)
NATO STOCK NUMBER
6145-99PAGE
LINE
NO
CONDUCTOR
SIZE
ITEM NAME
TYPE 1SBM 85
PINK
INSULATION
(a)
(b)
(c)
WHITE
INSULATION
(d)
TYPE 1SBM 120
TYPE 2SBM
PINK
INSULATION
WHITE
INSULATION
PINK
INSULATION
WHITE
INSULATION
(e)
(f)
(g)
(h)
1
2
3
4
19/0.10
19/0.12
19/0.15
19/0.20
CABLE
SPECIAL
PURPOSE
ELECTRICAL
053-5000
053-5001
053-5002
053-5003
053-5008
053-5009
053-5010
053-5011
891-9767
891-9771
891-9775
891-9779
891-9768
891-9772
891-9776
891-9780
891-9769
891-9773
891-9777
891-9781
891-9770
891-9774
891-9778
891-9782
5
6
7
8
19/0.25
19/0.30
37/0.25
37/0.30
CABLE
POWER
ELECTRICAL
053-5004
053-5005
053-5006
053-5007
053-5012
053-5013
053-5014
053-5015
891-9783
891-9787
891-9791
891-9795
891-9784
891-9788
891-9792
891-9796
891-9785
891-9789
891-9793
891-9797
891-9786
891-9790
891-9794
891-9798
NOTE: The NATO Stock numbers in columns (c), (d), (e) and (f) are only applicable to cables where the insulation
is coloured pink or white (as applicable) and the sheath colour is black.
Amdt.2
DEF STAN 61-12 (PART 18)/4
WIRES CORDS AND CABLES, ELECTRICAL
METRIC UNITS
PART 18: EQUIPMENT WIRES LIMITED FIRE HAZARD
AMENDMENT 3
1
Page 22 Table 1(A), column (n), Page Line No 13
Delete: 891-9568
Insert: 891-9586
2
Make a note of this amendment on the amendment record
D/DStan/372/07/19
92/70002
25 April 1997
Ministry of Defence
Directorate of Standardization
Stan Ops 2b
Kentigem House
65 Brown Street
Glasgow
G28EX
Procurement Executive, Ministry of Defence
Directorate of Standardization
Room 1138, Kentigern House, 65 Brown Street, GLASGOW, G2 8EX
Telephone:
0141-224 2595 (Direct Dialling)
0141-248 7890 (Switchboard)
Internet e-mail address: t.leaver@dstan.mod.uk
Fax:
0141-224 2503
Your Reference :
Our Reference :
D/DStan/11/2
Date :
9 November 1998
Removal of Product Qualification Approval
IMPORTANT ANNOUNCEMENT
1.
This Standard contains a Product Qualification Approval (PQA) scheme. iMOD policy requires that all
PQA schemes are removed from Defence Standards called up in contracts placed after 1st January 1998.
2.
Users of this Standard are to contact the Project Manager (PM), Equipment Support Manager (ESM) or
Technical Service Authority (TSA) named in the contract or order, to identify whether there is a continuing need
for an approvals scheme.
ii
3.
Product Conformity Certification (PCC) is a risk based process that replaces PQA. Once a risk has been
identified PCC can be included as a contract clause. In exceptional circumstances agreement can be sought from
AD/Stan for PCC to be included in a Defence Standard.
4.
At the next revision of this Standard the PQA scheme will be removed.
T R Leaver
Head of Standards Programme Management
Tel: 0141 224 2595 FAX: 0141 224 2503
i
Defence Council Instruction (General) 197/97; Quality Temporary Memorandum 5/98; Chief of
Defence Procurement Instruction CDPI/TECH/250 (draft)
ii
PCC is certification that a product meets its specification. When PC is required by the contract, the
contractor is responsible for obtaining the necessary PCC. Certification shall be provided from a
NAMAS accredited laboratory when appropriate. PCC shall apply where a Risk Assessment has been
identified by the PM; ESM or TSA.
Download