ARMS ARMS= “V PK/1.414” x 1 / 0.00001933 NOTE: VPK IS the peak voltage of the third half cycle. Ig Ground fault pick up setting. It is used on styles to set the ground fault pick up as a percentage of the frame current (In). Ir Breaker Rating current is the maximum RMS current a breaker can carry continuously (In). The DT trip unit will trip within 2 hours for an overload of 135 % of Ir. Isd Setting in multiples of Ir for short circuit conditions that exceed the short delay pick-up setting, the trip unit initiates a trip after a predetermined delay. Magnetic trip uses an electromagnetic device, with fixed (fixed instantaneous trip) or adjustable (adjustable instantaneous trip) threshold, which actuates the instantaneous trip of the circuit breaker on a pre-determined overcurrent value (multiple of the In) with a constant trip time (about some tens of milliseconds). This trip unit is intended for the protection against short circuit or inrush/instantaneous trip) elements. This is used primarily for conductor protection. The mag only is mainly used for motor protection. Uses coils through which current passes through which actuates a tripping mechanism which releases the latching unit to open the breaker contacts and interrupt current flow. Protection Tests: Protection Tests No Long Delay Pick Up Sends the correct settings down to the unit and applies current to pole A. Verifies the product DOES NOT pick up or trip in the specified time. Ground Fault is turned on for this test. Long Delay Pick Up Sends the correct settings down to the unit and applies current to pole A. Verifies the product does picks up but DOES NOT trip in the specified time. Ground Fault is turned on for this test. Long Delay Time Sends the correct settings down to the unit and applies current to pole B. Verifies the product trips in the specified time. The trip code from the unit is also verified . Ground Fault is turned off for this test. Instantaneous No Trip Test Sends the correct settings down to the unit and applies current to pole A. Verifies the product DOES NOT trip in the specified time. The trip code from the unit is also verified . Ground Fault is turned off for this test. Instantaneous Trip Test Sends the correct settings down to the unit and applies current to pole A. Verifies the product does trips in the specified time. The trip code from the unit is also verified . Ground Fault is turned off for this test. Short Delay No Trip Test Sends the correct settings down to the unit and applies current to pole C. Verifies the product DOES NOT trip in the specified time. The trip code from the unit is also verified . Ground Fault is turned off for this test. Short Delay Trip Test Sends the correct settings down to the unit and applies current to pole C. Verifies the product trips in the specified time. The trip code from the unit is also verified . Ground Fault is turned off for this test. Residual Ground Fault No Trip Test Sends the correct settings down to the unit and applies current to pole B. Verifies the product DOES NOT trip in the specified time. The trip code from the unit is also verified . Ground Fault is turned on for this test. Residual Ground Fault Trip Test Sends the correct settings down to the unit and applies current to pole B. Verifies the product trips in the specified time. The trip code from the unit is also verified . Ground Fault is turned on for this test. Source Ground Fault No Trip Test Sends the correct settings down to the unit and applies current to pole B. Verifies the product DOES NOT trip in the specified time. The trip code from the unit is also verified . Ground Fault is turned on for this test. Source Ground Fault Trip Test Sends the correct settings down to the unit and applies current to pole B. Verifies the product trips in the specified time. The trip code from the unit is also verified . Ground Fault is turned on for this test. Proximity sensor inductive proximity sensors detect metal objects without contact. Rating Plug The rating plug and phase current sensors define maximum continuous current rating (In) of the circuit breaker. The rating plug and phase current sensors also determine the maximum instantaneous setting. If the rating plug is removed from the protective relay, the circuit breaker will trip if it is carrying current. ROBO Cylinders® are highly efficient electric actuators. RMM Remote Mode The Remote mode is enabled by applying 24 VDC to the yellow (+) and Black (common) wires from left side of breaker. The Blue LED lights when the breaker is in Remote Mode. Shunt Trip Test Kit 70C1056 Performs a test of the Long Delay, Short Delay, and Ground Fault functions. Thermal trip uses a bimetal thermal device which actuates the opening of a circuit breaker with a delay depending on the overcurrent value. This trip unit is intended for the protection against overloads. Tr The number of seconds required to trip @ 6 X Ir (continuous rating current). Tsd A flat response as per this setting short delay (120ms, 300ms ex.) Withstand Rating is the fault current the breaker must be able to withstand for a specified time or if it is protected by a fuse or another circuit breaker in series with it. UVR Under voltage Release. With voltage applied, it pulls in a solenoid. If the voltage drops below a specified value the solenoid is released and causes the breaker to trip. FAILURES: CNT – continuity failure from line to load L2L – dielectric failure from line to load LD Long Delay P2P – dielectric failure from phase to phase P2G – dielectric failure from phase to ground FTST TESTS No Long Delay Pick Up Sends the correct settings down to the unit and applies A. Verifies the product DOES NOT pick up or trip in the Ground Fault is turned on for this test. Long Delay Pick Up Sends the correct settings down to the unit and applies A. Verifies the product does picks up but DOES NOT trip time. Ground Fault is turned on for this test. current to pole specified time. current to pole in the specified Long Delay Time Sends the correct settings down to the unit and applies current to pole B. Verifies the product trips in the specified time. The trip code from the unit is also verified . Ground Fault is turned off for this test. Instantaneous No Trip Test Sends the correct settings down to the unit and applies current to pole A. Verifies the product DOES NOT trip in the specified time. The trip code from the unit is also verified . Ground Fault is turned off for this test. Instantaneous Trip Test Sends the correct settings down to the unit and applies current to pole A. Verifies the product does trips in the specified time. The trip code from the unit is also verified . Ground Fault is turned off for this test. Short Delay No Trip Test Applies current to pole C. Verifies the product DOES NOT trip in the specified time. The trip code from the unit is also verified . Ground Fault is turned off for this test. Short Delay Trip Test Sends the correct settings down to the unit and applies current to pole C. Verifies the product trips in the specified time. The trip code from the unit is also verified . Ground Fault is turned off for this test. Residual Ground Fault No Trip Test Applies current to pole B. Verifies the product DOES NOT trip in the specified time. The trip code from the unit is also verified . Ground Fault is turned on for this test. Residual Ground Fault Trip Test Applies current to pole B. Verifies the product trips in the specified time. The trip code from the unit is also verified . Ground Fault is turned on for this test. Source Ground Fault No Trip Test Applies current to pole B. Verifies the product DOES NOT trip in the specified time. The trip code from the unit is also verified . Ground Fault is turned on for this test. Source Ground Fault Trip Test Applies current to pole B. Verifies the product trips in the specified time. The trip code from the unit is also verified . Ground Fault is turned on for this test.