Master of Science Thesis Fault Current Control in the Transmission Network − An Electromagnetic Transient approach − Sander A. Franke B.Sc. Delft University of Technology Faculty of Electrical Engineering, Mathematics and Computer Science June 19, 2012 Thesis committee Prof. Ir. L. van der Sluis Dr. Ir. M. Popov Prof. Dr. Ir. R.P.P. Smeets Ir. A.J.L.M. Kanters Ir. E. Wierenga Delft University of Technology, thesis supervisor Delft University of Technology, daily supervisor Eindhoven University of Technology TenneT TSO, daily supervisor TenneT TSO Copyright © 2012 by S.A. Franke Typesetting was done by LATEX All Rights Reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, electronic, mechanical, photocopying, recording, scanning or otherwise, without prior permission from Delft University of Technology and the author. Keywords: ATP-EMTP, DIgSILENT, fault current, fault current limiter, shortcircuit, superconductivity, transient recovery voltage, transmission network Legal Notice Neither the authors nor Delft University of Technology accept ant responsibility or liability for loss or damage occasioned to any person or property through using the material, instructions, methods or ideas contained herein, or acting or refraining from acting as a result of such use. Abstract Transmission System Operators (TSO’s) are facing an increase of fault current levels in their networks due to the expansion of generation capacity. This thesis investigates three possible fault current limiting measures in the Dutch transmission grid which is operated and maintained by TenneT TSO. In order to evaluate the behavior of the fault current limiting measures, two independently operating grid models were established and validated. The examined fault current limiters consisted of a current limiting reactor (CLR) and a superconducting fault current limiter (SCFCL). The possibility of substation splitting was also investigated. All three measures reduced the short-circuit levels successfully to values within the electromechanical and thermal withstand levels of the power system. Simulation results revealed that the SCFCL has a significantly lower impact on the rate-of-rise-of-recovery-voltage (RRRV) of the circuit breaker (CB) as compared to the CLR. Additional measures were presented to keep the RRRV of the CLR within the dielectric withstand levels of the CB as specified in the IEC 62271-100. i Contents Abstract i Preface vii Nomenclature ix 1 Introduction 1.1 Research Objectives . . . . . . . . . . . . . . . . . . . . . . . . . 1.2 Research Methodology . . . . . . . . . . . . . . . . . . . . . . . . 1.3 Thesis Outline . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 2 3 4 2 Fault Currents 2.1 Basic Theory . . . . . . . . . . . . . . . . 2.1.1 Anatomy of a Short-circuit . . . . 2.1.2 The Short-circuit Characterized by 2.1.3 The Transient Recovery Voltage . 2.2 Short-circuit Calculations . . . . . . . . . 2.2.1 Analysis of Grid Faults . . . . . . 2.2.2 Symmetrical Components . . . . . 2.2.3 The Superposition Method . . . . 2.2.4 The IEC 60909 Method . . . . . . 2.3 The First Pole-to-clear Factor . . . . . . . 2.4 The IEC 62271-100 . . . . . . . . . . . . . . . . . . . . . . . the IEC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60909 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 5 5 7 8 9 9 9 12 12 17 17 3 The Model 3.1 Grid Model . . . . . . . . . . . . . . . . . 3.1.1 Initial study . . . . . . . . . . . . . 3.1.2 Topology of the Dutch Grid Model 3.1.3 Validation . . . . . . . . . . . . . . 3.1.4 TRV Study . . . . . . . . . . . . . 3.1.5 Limitations . . . . . . . . . . . . . 3.2 Modeling of Power System Components . 3.2.1 Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 21 21 23 23 25 25 26 27 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iii CONTENTS 3.2.2 3.2.3 3.2.4 Generators . . . . . . . . . . . . . . . . . . . . . . . . . . Transmission Lines . . . . . . . . . . . . . . . . . . . . . . Transformers . . . . . . . . . . . . . . . . . . . . . . . . . 4 Fault Current Limiting Reactors 4.1 Applications of Reactors . . . . . . . . . . . . . . 4.1.1 Series Reactors . . . . . . . . . . . . . . . 4.1.2 Neutral Grounding Reactors . . . . . . . 4.2 Technical Aspects of Series Reactors . . . . . . . 4.2.1 Air-core Reactors . . . . . . . . . . . . . . 4.2.2 Oil-immersed Reactors . . . . . . . . . . . 4.3 A Practical Model . . . . . . . . . . . . . . . . . 4.3.1 Technical Parameters . . . . . . . . . . . 4.3.2 ATP-EMTP Model of the Series Reactor 28 28 30 . . . . . . . . . 33 33 33 34 34 34 35 36 36 38 5 Superconducting Fault Current Limiters 5.1 Superconducting Materials . . . . . . . . . . . . . . . . . . . . . . 5.2 Costs of SC Materials . . . . . . . . . . . . . . . . . . . . . . . . 5.3 SCFCL Topologies . . . . . . . . . . . . . . . . . . . . . . . . . . 5.3.1 Resistive Type . . . . . . . . . . . . . . . . . . . . . . . . 5.3.2 Saturated Iron Core . . . . . . . . . . . . . . . . . . . . . 5.3.3 Magnetic Shielded Core . . . . . . . . . . . . . . . . . . . 5.3.4 Solid State FCL’s . . . . . . . . . . . . . . . . . . . . . . . 5.3.5 Overview of Different SCFCL Types . . . . . . . . . . . . 5.4 A Practical Model for a Shielded Core SCFCL . . . . . . . . . . 5.4.1 Design Aspects of a SCFCL . . . . . . . . . . . . . . . . . 5.4.2 ATP-EMTP Model of the Magnetic Shielded Core SCFCL 41 41 44 44 44 45 47 49 50 51 51 52 6 Case Study Maasbracht 380 6.1 Splitting the Substation Into Sub Grids . . . 6.2 EMT Model of Substation Maasbracht 380 . 6.3 EMT Study Series reactor . . . . . . . . . . . 6.3.1 Results . . . . . . . . . . . . . . . . . 6.3.2 Insertion of Damping Capacitors . . . 6.4 EMT Study Magnetic Shielded Core SCFCL 6.4.1 Results . . . . . . . . . . . . . . . . . 55 55 58 58 58 59 62 62 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Conclusion and Recommendations 65 7.1 Conclusion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 7.2 Recommendations for Future Work . . . . . . . . . . . . . . . . . 66 Bibliography 67 Appendices A Source Code ATP-EMTP MODELS Block Set 73 B Overview of SCFCL Projects 75 C Overview of the EMT Grid Models 81 iv CONTENTS D Resulting Plots TRV Study 85 D.1 Series Reactor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 D.2 Magnetic Shielded Core SCFCL . . . . . . . . . . . . . . . . . . . 88 E Grid Parameters 91 v Preface This thesis describes the possible short-circuit limiting measures in the Dutch transmission grid and is carried out as a compulsory part of my MSc study Electrical Power Engineering at the Delft University of Technology. During my studies I became acquainted with the field of Power System Transients through the interesting lectures of prof. ir. L. (Lou) van der Sluis on the same topic. I decided to fulfill my thesis within this intriguing field of research, however still a challenging subject had to be found! Dr. ir. M. (Marjan) Popov introduced me to the Dutch Transmission System Operator TenneT and I was given the opportunity to work on a transient study on fault current limiting measures in the Dutch transmission grid. During my thesis I was given a workplace at TenneT within the business unit Grid Services. This position gave me the chance to benefit from a tremendous amount of technical knowledge and experience in the area of power systems, something which I have greatly appreciated. First of all I would like to thank ing. G.P.P. (Gert) Aanhaanen for his technical support and interest from the side of the business unit Asset Management. I am grateful to ir. E.F. (Ernst) Wierenga who often helped me with the DIgSILENT PowerFactory software and with whom I had many enjoyable conversations regarding technical and non-technical subjects. I would like to thank my daily supervisor at TenneT ir. A.J.L.M. (Jos) Kanters with whom I had many fruitful discussions on my thesis and who guided me whenever it was needed. I also want to thank the rest of my colleagues at TenneT who were very interested in my work and helpful whereever they could. Furthermore I would like to acknowledge prof. dr. ir. R.P.P. (Rene) Smeets, who shared his expertise and was willing to take place in my thesis committee. Dr. ir M. (Marjan) Popov I sincerely want to thank for introducing me to the ATP-EMTP software and the subsequent support he provided in his role as my daily supervisor at the Delft Univesity of Technology. Ir. M.O.W. (Marinus) Grond, ing. M. (Michiel) Vis and ir. F. (Ferdinant) Visser it was a great pleasure studying with you guys and I am sure you are looking forward to great career (within the field of Electrical Power Engineering). Certainly someone I would like to thank is drs. J. (Jelle) Oosterhof which provided editorial feedback and support during my thesis. Last but definitely not least, I would like to express my gratitude to Anneloes for her unconditional support during the period of this thesis and entire studies. Sander Franke, Rotterdam, June 2012 vii List of Abbreviations AC Aternating Current ATP Alternative Transients Program BIL Basic Impulse Level BPA Bonneville Power Administration BSCCO Bismuth-strontium-calcium-copper-oxide CT Current transformer CVT Capacitive voltage transformer DC Direct Current DIgSILENT Digital SImuLator for Electrical NeTwork EM Electromagnetic EMT Electromagnetic Transients EMTP Electromagnetic Transients Program ENTSO-E European Network of Transmission System Operators for Electricity FCL Fault current limiter FORTRAN Procedural Imperative Programming Language FPTC First pole-to-clear Factor HTS High Temperature Superconductor IEC International Electrotechnical Commission LTS Low Temperature Superconductor LV Low Voltage ix Nomenclature MGb Magnesium-diboride ODAF Oil Directed Air Forced ONAF Oil Natural Air Forced ONAN Oil Natural Air Natural p.u. Per Unit RE Rare-earth RMS Root-mean-square RRRV Rate of Rise of Recovery Voltage S/N Superconducting-to-normal transition SC Super conductor SCFCL Superconducting Fault Current Limiter SCTM Symmetrical Component Transformation Matrix SIL Switching Impulse Level TACS Transient Analysis of Control Systems TRV Transient Recovery Voltage TSO Transmission System Operator UCTE Union for the Coordination of the Transmission of Electricity YBCO Yttrium-barium-copper-oxide x CHAPTER 1 Introduction he electrical power system is probably the largest and most complex manT made system in the world. It facilitates the transport of electrical energy which is the most versatile and universal form of energy available. The demand for electricity is growing continuously and is driven by technical developments such as the introduction of digital computers in the last three decades. It is expected that the demand for electricity will increase even more in the developed world when electrical cars are widely introduced. To keep a balance between the production and consumption of electricity the generating capacities of power systems need to be expanded. Generating capacity can be increased by installing new power plants, renewables1 or by implementing distributed generators in the power system. As a result the transmission and distribution capacities need to be expanded as well, which leads to the installation of additional transformers and transmission lines. The increased production capacity and increased transmission and capacity will also increase the prospective2 short-circuit currents in the power system. Faults in the power system can have various causes. Such as lightning, power system component failures or falling tree branches. It is crucial to keep the prospective short-circuit currents within the thermal and mechanical fault current withstand levels of the power system, since fault over-currents may harm the high-voltage equipment. The Dutch transmission network is facing an increase in present and future short-circuit current levels as well. Until the year 2020 a large increase of concentrated generation capacity is foreseen at the locations Eemshaven, Maasbracht and Maashaven. An overview is given in table 1.1. This thesis aims on the “controllability” of fault currents in the Dutch transmission network that is coordinated by the Dutch Transmission System Operator (TSO) TenneT at 1 Renewables are energy sources that comes from natural resources such as sunlight, wind, rain, tides, and geothermal heat. 2 The prospective short-circuit current (PSCC) is the highest electric current which can exist under short-circuit conditions. 1 Chapter 1 which this thesis is carried out. In the next section, 1.1 Research Objectives, the objectives of this thesis will be discussed. Location Company Unit Capacity MW In operation Fuel Eemshaven Nuon Energie BV RWE Magnum EEM-A EEM-B 1.290 1.200 780 780 2011 2013 2013 2014 Gas Gas Coal Coal Maasbracht Essent Claus-C Claus-D 1.300 1.300 2012 2018 Gas Gas Maasvlakte Enecogen Electrabel E.On Enecogen CR-1 NL-MMP3 870 736 1.070 2011 2012 2013 Gas Coal Coal Table 1.1: Planned construction of power plants at locations Eemshaven, Maasbracht and Maashaven [2] 1.1 Research Objectives The increasing fault current levels in the Dutch electrical power system will have its impact on safety and reliability of the system. In this thesis the main goal is to determine how fault currents can be reduced in such a way that acceptable levels for the high-voltage equipment are achieved. This question has to be translated into physical measures since it is the responsibility of TenneT to facilitate electricity transmission without imposing restrictions to grid connected parties3 . Three possible fault current limiting measures will be treated: Fault current limiting reactors Superconducting fault current limiters or SCFCL’s Substation splitting where fault current limiters based on superconducting materials have the special interest of TenneT. These are the so called superconducting fault current limiters or SCFCL’s. Short-circuits are often referred to as “transients”. However transients in power systems are far more comprehensive. A transient occurs in the power system when the network changes from one steady state into another [51]. Meaning that the effects of switching actions by circuit breakers also need to be designated as transients. From this perspective the presence of a short-circuit current can be seen as one steady-state situation wherein the energy is predominantly stored in the EM field. When the short-circuit current has been interrupted the network changes into another steady-state situation wherein the energy is 3 The Office of Energy Regulation ensures the conditions for the free market and is responsible for implementing and ensuring compliance with the 1998 Electricity Act [41] 2 Introduction mainly in the electric field. Thus when it comes to evaluating FCL’s in the power system, networks need to be accurately modeled and validated with respect to voltages and currents. This is another objective of this thesis. The investigated fault current limiting measures will be assessed on TenneT’s substation Maasbracht 380. It is expected that the substation will exceed its maximum short-circuit withstand levels in the near future due to the construction of the Claus-D generation units connected to substation Maasbracht 380. The results will be brought together in chapter 6 Case Study Maasbracht 380. 1.2 Research Methodology At first the relevant theory of transients in power systems will be examined. In addition short-circuit calculations methods are discussed as they will play an important role in the determination of equivalent sources and grid model validation. Fault current limiting measures are studied by literature and subsequently EMT models will be established. SCFCL’s have the special interest in this thesis, therefore multiple topologies will be treated and SC material properties examined. The behavior of several fault current limiting measures will be tested on substation Maasbracht 380. For the Dutch electrical power system an EMT grid model will be established, constructed out of all relevant power system components such as generator models, line models and transformer models. Grid boundaries are replaced by equivalent sources computed by a steady-state short-circuit calculation model which will be provided by the Asset Management department of TenneT. The choice of simulation software mainly depends on functionality and grade of technical support during this thesis. At TenneT DIgSILENT PowerFactory is a commonly used software package and support is widely available within the business units Asset Management and Grid Services. Delft University of Technology recommends the academic ATP-EMTP software because it is supported by the Power Systems Laboratory and through many scientific and non-scientific experts all over the world. DIgSILENT PowerFactory DIgSILENT (Digital SImuLator for Electrical NeTwork) PowerFactory is a commercial simulation tool for calculations in power systems and features a broad range of functionalities; the ones of interest in this thesis are the EMT analysis functionality and the IEC 60909 short-circuit calculation method. ATP-EMTP ATP-EMTP (Alternative Transients Program) is a non-commercial simulation tool for the calculation of electromagnetic transients in specific. It is mainly based on the efforts of H.W. Dommel during his time at the Munich Institute of Technology in the early 1960s and later at BPA (Bonneville Power Administration) in the United States where he continued his work on the program. At present ATP-EMTP is the most widely used Electromagnetic Transients Program in the world [30]. 3 Chapter 1 Both simulation software packages are used in this thesis to validate the dynamical short-circuit currents in the Dutch grid model. 1.3 Thesis Outline This thesis will first treat relevant theory on the topic of transients and shortcircuit calculations in chapter 2. Chapter 3 describes how parts of the Dutch transmission grid are modeled for EMT analysis. It focuses on the validation and model description of relevant power system components. A study on the technical aspects of several fault current limiting reactors is presented in chapter 4. This chapter also comprises the model description of an oil-immersed series reactor based on manufacturing parameters. A thorough insight in SC materials and a comparison of SCFCL topologies is given in chapter 5. The same chapter describes how an EMT model of a SCFCL is established. Chapter 6 contains the case study, where the explored fault current limiting measures will be tested on substation Maasbracht 380. Finally chapter 7 gives conclusions and recommendations for future work. 4 CHAPTER 2 Fault Currents Relevant aspects on power system faults are treated in this chapter. It covers elementary theory on fault currents, short-circuit calculations and transient recovery voltages. 2.1 Basic Theory 2.1.1 Anatomy of a Short-circuit To get an thorough understanding of the short-circuit current behavior in a power system, the LR-circuit in figure 2.1 is evaluated. The short-circuit is of a predominant inductive character as most of the energy is stored in the magnetical field of power systems components. The inductance L could represent the inductance of synchronous generators, transformers or transmission lines for example. Losses in the power system, such as iron losses, are represented by the resistance R. By applying Kirchoff’s law, the nonhomogeneous equation of the circuit is obtained: U = Û sin(ωt + ϕ) = Ri + L di dt L (2.1) R U Figure 2.1: Voltage source connected to a LR series circuit 5 Chapter 2 The short circuit can be initiated at any time instant by the circuit breaker and therefore has a phase angle between 0 and 180 degrees (or 0 and π). The general solution is found by solving the characteristic equation: Ri + Lκ = 0 (2.2) The eigenvalue of the characteristic equation is declared as κ. By solving equation (2.2) for κ, the result is κ = −(R/L). Subsequently the general solution for equation (2.1) is: ih (t) = C1 e−(R/L)t (2.3) By substituting a general expression in equation (2.1), the particular solution is found: ip (t) = A sin(ωt + ϕ) + B cos(ωt + ϕ) (2.4) Now A and B van be defined: A= R2 RÛ + ω 2 L2 B=− R2 ωLÛ + ω 2 L2 Then the particular solution is: Û ωL ip (t) = √ sin ωt + ϕ − tan−1 R R 2 + ω 2 L2 (2.5) (2.6) Resulting in the complete solution, which is the total of the general and the particular solution: i(t) = ih (t) + ip (t) i(t) = C1 e −(R/L)t Û ωL −1 +√ sin ωt + ϕ − tan R R2 + ω 2 L2 (2.7) (2.8) Before the switch closes, the magnetic flux in the inductor L is zero as a result of the law of the conservation of flux. Therefore we may omit the R/L term, resulting in: Û ωL i(0) = C1 + √ sin ϕ − tan−1 (2.9) R R 2 + ω 2 L2 C1 can now be derrived and yields: ( ) Û ωL i(t) = e−(R/L)t √ sin ϕ − tan−1 R R 2 + ω 2 L2 Û ωL −1 +√ sin ωt + ϕ − tan R R2 + ω 2 L2 (2.10) The term exp[−(R/L)t] is known as the DC component and eventually damps out. The expression between the brackets is a constant and its outcome is 6 Fault Currents Top envelope 2√2Ik=2√2I´´k A ip 2√2I´´k d.c. compnent id.c. of the short-circuit current Time Bottom envelope Figure 2.2: Short-circuit current of a far-from-generator short circuit with constant AC component determined by the instant of the fault current (closing of the circuit). It means that the magnitude of the DC component depends on this closing instant. If the fault occurs at the current-zero crossing, than there is no DC component and the current reaches an immediate steady state. This is called a symmetrical current. If the fault instant is shifted plus or minus 90 degrees with respect to the zero-crossing, it will reach the maximum amplitude. This is called an asymmetrical current and an example is given in figure 2.2. The short-circuit can be characterized by parameters as is done by IEC 60909. This will be discussed in the next sub-section. 2.1.2 The Short-circuit Characterized by the IEC 60909 The IEC 60909 defines the short-circuit current with parameters that are very commonly used during the planning, design and operation of electrical power systems. The IEC 60909 makes the distinction between far-from-generator and near-to-generator faults. The behavior of the short-circuit current in both cases 00 is shown in figures 2.2 and 2.3. Where Ik is the initial symmetrical short circuit current, ip is the peak short circuit current, idc is the decaying DC aperiodic component and A is the initial amplitude of the DC aperiodic component. Figure 2.2 refers to a short-circuit far-from generating units and is characterized by a constant value of the symmetric AC periodic component. Figure 2.3 refers to a short circuit near a synchronous generator and is characterized by a variable value of the symmetric AC periodic component. The decaying AC component is a direct result of the varying reactance of the synchronous machine during a short circuit. The waveform is divided in three distinct time periods. The substransient period, lasting only for the first few cycles and where the amplitude decays rapidly, the transient period that takes a longer time, during which the amplitude decays considerably more slowy and finally the steady state period, during which the amplitude of the current stays constant. The parameters that determine the amplitude of the short-circuit waveform are the substransient re7 Chapter 2 Top envelope A 2√2Ik ip 2√2I´´k d.c. compnent id.c. of the short-circuit current Time Bottom envelope Figure 2.3: Short-circuit current of a near-to-generator short circuit with decaying AC component 00 0 actance, X , the transient reactance, X and the synchronous reactance, X, respectively. 2.1.3 The Transient Recovery Voltage The TRV is the voltage which appears across the circuit breaker terminals when it opens and interrupts a current. This voltage comprises both power frequency and transient components and depends on the type of fault, the location of the fault and the type of circuit being switched. An example of a three-phase-toground fault is given in figure 2.4. The transformer is represented by a short circuit reactance, Lt and its windings capacitance by a capacitor to ground Ct , see figure 2.4c for the one-phase representation. The resulting voltage over the circuit breaker is plotted in figure 2.4c. Vl is equal to zero, as it is connected to ground. The TRV Vs increases to E with 1.0 per unit and can reach a peak value of 2.0 per unit without damping in the circuit. In practical situations this value is significantly lower due to iron and copper losses. The frequency of the TRV is related to the response of the system on each side of the breaker. In this example where Vl is connected to the ground the oscillating frequency results in: f= 1 √ 2π Lt Ct (2.11) The rate of rise and peak value of the TRV are related to the type of fault being interrupted. And 8 Fault Currents Three-Phasetoground fault G (a) + E Lt Ct − (b) Vs Vl 2E (no damping) Vs E Vs & Vl Vl (c) Figure 2.4: The TRV for a three phase to ground fault: (a) one-line representation, (b) one-phase representation, (c) TRV waveform, [51] . 2.2 Short-circuit Calculations 2.2.1 Analysis of Grid Faults The most important grid faults1 in a three-phase system are categorized in table 2.5 [28, 51]. Their profound description is beyond the purpose of this thesis, however the most important characteristics are shortly treated hereafter. The three-phase-to-ground fault is defined as a simultaneous short-circuit across all three phases. This means that the conductors are loaded symmetrically; it is a balanced fault and therefore can be solved on a per phase basis. The remaining conductors carry the same fault current except from phase shift. It occurs infrequently, however it is the most severe type of fault that can occur in a power system. The line-to-line, the double line-to-ground and the line-to-ground shortcircuit are unsymmetrical faults. The single-line-to-ground short-circuit is the most frequent occuring fault in a power system. 2.2.2 Symmetrical Components Literature describes various methods for the solution of unbalanced faults. However the theory of symmetrical components introduced by C. L. Fortescue in 1918 is the most used, since it simplifies the solution of unbalanced circuits by transforming them in to several balanced circuits [21]. This makes it possible to treat the short-circuit on a per-phase basis. It assumes the network has a symmetrical structure (i.e. transposed overhead lines); however acceptable accuracy is provided in the case of an untransposed network. A vector for three 1 If the fault impedance Zf = 0, the fault is called a bolded or solid fault. 9 Chapter 2 Circuit diagram of the short-circuit Fault Three-phase-to-ground a b c a b c Ia+Ib+Ic=0 Va=Zf Ia Vb=Zf Ib Vc=Zf Ic + - Va Vb Vc Line-to-line Boundary conditions Zf Ia + - Va Ib Ic Ic Ib Vb Vc Ia=0 Ib=-Ic Vb-Vc=Zf Ib Zf Ia=0 Double line-to-ground a b c + - Va Ib Vb Vc Zf Zg Ib Ia=0 Vb=(Zf+Zg)Ib+Zg Ic Vc=(Zf+Zg)Ic+ZgIb Ia+Ib Ia=0 Single line-to-ground a b c Ib=Ic=0 Va=Zf Ia + - Va Vb Vc Zf Ia b=0 Ic=0 Figure 2.5: Possible faults in a three-phase network 10 Fault Currents phase currents can be expressed as: Ia Ia,0 Ia,1 Ia,2 Iabc = Ib = Ib,0 + Ib,1 + Ib,2 Ic Ic,0 Ic,1 Ic,2 (2.12) where a = ej2π/3 and the subscripts 0, 1 and 2 respectively refer to the zero sequence, positive sequence and negative sequence components. Note that a−1 = a2 and a3 = 1. The zero sequence components are in phase and can be denoted as: I0 ≡ Ia,0 = Ib,0 = Ic,0 (2.13) and the remaining phase sequences as: I1 ≡ Ia,1 = Ib,1 = Ic,1 (2.14) I2 ≡ Ia,2 = Ib,2 = Ic,2 (2.15) and: Resulting in: 1 Iabc = 1 1 1 a2 a I0 1 a I1 = AI012 a2 I2 (2.16) where: I012 I0 1 = I1 , A = 1 I2 1 1 a2 a 1 a a2 (2.17) where A is the symmetrical component transformation matrix (SCTM) that transforms the sequence components I012 into the phasor currents Iabc . Conversely the sequence components can be derived from the phasor currents by: I012 = A−1 Iabc (2.18) where the inverse of A-1 is expressed as: 1 1 1 1 A−1 = 1 a a2 3 1 a2 a (2.19) Substituting equation 2.19 into 2.18 yields: 1 1 1 I012 = 1 a a2 Iabc 1 a2 a (2.20) 00 When calculating the initial symmetrical short-circuit current Ik and the symmetrical short-circuit current Ik , the positive, negative and zero-sequence equivalent circuits are converted by network reduction into equivalent short-circuit 11 Chapter 2 impedances Z0 , Z1 and Z2 at the location of the fault. When applying the method of equivalent circuits, each network component is represented by a specific sequence circuit as is widely explained in references [28, 51, 53]. The symmetrical current components I0 , I1 and I2 can be calculated once the positive, negative and zero-sequence equivalent circuits are reduced to equivalent short circuit impedances at the fault location. Hereby taking into account contraints imposed by the faults, such as the interconnection between positive, negative and zero sequence equivalent circuits. The symmetrical component equations provide the possibility to calculate steady-state short circuit currents for several types of faults, however do not include the pre-fault conditions. 2.2.3 The Superposition Method The superposition method is also referred to as the complete method and is an exact method for the calculation of steady-state short circuit currents. It consists of the superposition of two steady-state operating conditions and requires the following three steps: 1. The pre-fault voltages and currents are calculated. The calculation is based on the load-flow solution of the specified network. The operating conditions are taken into account as well (e.g. transformer tap positions, generator exitation conditions and circuit breaker status). 2. In this step the pre-fault voltage at the fault location with negative sign is applied to the passive network. This means that there is only one voltage source connected while the internal voltage sources of the generators are short-circuited. Then the steady-state currents and voltages are determined using the load-flow calculation. 3. Finally both conditions are superposed resulting in a zero voltage at the fault location. The accuracy depends on the correctness of the pre-fault conditions. Additionally the operating conditions are sometimes difficult to determine (i.e. active and reactive power, bus voltages and tap settings for transformers). The procedure of the superposition method is illustrated in figure 2.6. 2.2.4 The IEC 60909 Method The IEC short-circuit calculation method is generally accepted in Western Europe and is based on the method of an equivalent source at the fault location. It is derived from the superposition method as is discussed in sub-section 2.2.3. It has the aim of accomplishing a close-to-reality short circuit calculation without the need of preceeding load-flow calculations and actual operating conditions. Regarding the principle of superposition, the IEC 60909 method does not require the pre-fault load flow solutions and pre-fault operating conditions. The most important simplifications compared to the superposition method are given hereafter: Nominal conditions are assumed for the whole network, i.e. Ui = Un,i 12 Fault Currents Generation a) Xdi’’ Ei F Electrical power system UbF Pre-fault voltage + F Xdi’’ b) Electrical power system Generation c) Xdi’’ Ei = UbF F Ik’’ Electrical Fault power system location Figure 2.6: Principle of the superposition method. (a) Pre-fault operating condition, (b) Operation with applied negative pre-fault voltage at the short circuit location, c) Short circuit condition obtained by superposing a and b Load currents are neglected, i.e. Iop =0 The simulation network is simplified, loads are not considered in the positive and negative sequence network. From these simplifications figure 2.6c can be approximated as figure 2.6b because the pre-fault operating conditions are considered to be insignificant under the following assumptions: During normal operation (pre-fault condition) the currents are much smaller in magnitude than the prospective2 short circuit currents In general power systems have an inductive behavior and the current lags the bus voltage with a power factor of about 0.9. However during a short circuit the current lags the bus voltage with a much lower power factor (i.e. phase shift close to 90◦ ). Therefore the nominal operating current and the short circuit current can be approximated in steady-state condition by the phasors as shown in figure 2.7. 00 From figure 2.7 it is clear that when the ratio Ik /Ip becomes higher the ap00 proximation of Isc ≈ Ik will improve considerably. This means that in the vast majority of short circuit calculations the operating conditions may be neglected. The IEC 60909 method defines the nominal power system voltage to be one p.u.. This means that the pre-fault voltage, Uf , at the fault location is equal to Un . However in some cases the system voltage may be significantly higher, therefore a correction factor c is incorporated. This factor is applied on the nominal voltage at the fault location and consequently the pre-fault voltage results in: Uf = cUn . The correction factor, c, can be determined according to 2 The prospective short-circuit current is the current that would flow if the short circuit was replaced by an ideal connection (negligible impedance) without any change of the supply [5] 13 Chapter 2 Uf I sc ≈ I k'' Ip I k'' Figure 2.7: Pre-fault current and short-circuit current. Pre-fault bus voltage, Uf , 00 pre-fault operating current, Ip , steady state short circuit current, Ik , total short-circuit current after superposition, Isc Q Non-rotating load A T ~ L HV LV tr :1 k3 ~ F Non-rotating load ZQ Q Un A ZT F ZL ~ cU n 3 ZQ ZT ZL cU n 3 Ik Figure 2.8: Principle of the equivalent voltage source method table 2.1, taking into account that the highest voltage does not differ from the rated value by more than +5% in low-voltage systems and +10% in high-voltage systems. When calculating maximum short circuit currents cmax is used and for the calculation of minimum short circuits currents cmin is applied. The relevant IEC 60909 short circuit values are treated: 00 initial symmetrical short circuit current Ik symmetrical short circuit current Ik peak short-circuit current ip DC component of the short-circuit current iDC 00 Initial symmetrical short-circuit current Ik 00 The initial symmetrical short-circuit current, Ik , is the RMS value of the AC symmetrical component of the prospective short-circuit current at the instant 00 of the fault. The short-circuit current, Ik , is determined by using the equivalent √ voltage source, cUn / 3, which is defined as the voltage of an ideal source applied at the short-circuit location in the positive sequence system, at the fault location F. All other sources are neglected. All network feeders such as synchronous and asynchronous machines are replaced by their internal impedances. Line capacitances, shunt admittances and non-rotating loads are ignored. The equivalent voltage source method is depicted in figure 2.8. For a three-phase-to-ground 14 Fault Currents Nominal voltage Un Low voltage 100V to 1000V (IEC 60038, table I) Voltage factor c for the calculation of maximum minimum short circuit currents short circuit currents cmax 1 cmin 1.053 1.104 0.95 Medium voltage > 1 kV to 35 kV (IEC 60038, table III) 1.10 1.00 High voltage2 > 35 kV (IEC 60038, table IV) 1.10 1.00 1 2 3 4 cmax Un should not exceed the highest voltage Um for equipment of power systems If no nominal voltage is defined cmax Un = Um or cmax Umin = 0.9Um should be applied For low-voltage systems with tolerance of +6%, for example systems renamed from 380V to 400V For low-voltage systems with tolerance of +10% Table 2.1: Voltage factor c fault the initial symmetrical short-circuit current can be calculated according to: 00 cUn Ik3 = √ 3Zk (2.21) where Zk is value of the equivalent short-circuit impedance (in fact this is the Thevenin impedance) at the location of the fault F. From here it is possible to calculate the short-circuit current according to the equivalent voltage source method at location F by only using the nominal voltage. To be sure the results are on the safe side the voltage factor c according to table 2.1 and correction factor KG for the correct calculation of the generator impedance is applied. Symmetrical short-circuit current Ik The symmetrical short-circuit current, Ik , is the RMS The calculation depends on wether the fault is far from or near to the generator. When the fault location 00 is far from the generator, Ik , is assumed to be equal to the initial value of Ik . If the fault occurs near to the generator several paramaters are taken into account such as the excitation type, automatic voltage regulation, machine type and saturation effects [5]. 15 Chapter 2 Peak short-circuit current ip The peak short-circuit current, ip , is the maximum instantaneous value of the prospective short-circuit current. For the calculation the IEC 60909 makes the distinction between radial and meshed networks. In case of a radial network, ip , is defined as the sum of all contributions to the fault: X ip = ipi (2.22) i where each contribution of ipi is calculated by: √ 00 ipi = κi 2Iki (2.23) The coefficient κi depends on the R/X ratio of each contributing branche. For meshed networks the behavior of the short-circuit current is influenced by the network as a whole. Therefore the peak value is directly calculated through: √ 00 (2.24) ip = κ 2Ik For both types of networks (radial and meshed) the IEC 60909 suggests three different methods, A, B, or C to compute the equivalent coefficient κ: κ = 1.02 + 0.98e−3R/X (2.25) A In this method the equivalent coefficient κ is determined from the smallest R/X ratio of all branches in the network. In this way ip is estimated on the safe-side (maximum peak-value). B In this method the equivalent coefficient κ is determined from the R/X ratio of the positive-sequence short-circuit impedance at the fault location. It is multiplied by a factor 1.15 to cover inaccuracies caused by different R/X ratios in parallel branches. C In this method the equivalent coefficient κ is determined according to: R Rc fc = X Xc f (2.26) where fc = 20 Hz for a nominal frequency of f = 50 Hz or fc = 24 Hz for a nominal frequency of f = 60 Hz. And Zc = Rc + jXc is the equivalent impedance of the system as seen from the short-circuit location for the assumed frequency fc . Subsequently κ is found by equation 2.25. Method C is recommended in meshed networks [5]. Direct current component of the short-circuit current iDC The maximum DC component iDC of the short-circuit current is calculated according to: √ 00 iDC = 2Ik e−2πf tR/X (2.27) where f is the nominal frequency, t is the time and R/X is the ratio for radial networks or an equivalent ratio for meshed networks. For meshed networks the R/X ratio is determined according to equation 2.26 described in method C. However instead of using the ratio fc /f , fc is calculated from the ratio fc /f depending on f · t from table 2.2. 16 Fault Currents f ·t <1 < 2.5 <5 < 12.5 fc /f < 0.27 < 0.15 0.092 0.055 Table 2.2: fc /f ratios for DC component computation in meshed networks 2.3 The First Pole-to-clear Factor The first pole-to-clear factor (FPTC) is a funtion based on the grounding arrangements of the power system. It is defined as: “the ratio between the power frequency voltage across the first clearing pole before current interruption in the other poles, to the power frequency voltage occurring across the pole or poles after the interruption in all three poles” [13]. The mathematical description of the FPTC factor is given in equation 2.29 and is derived from the sequence circuits for a double-line-to-ground fault as is described in [51]. kpp = 3 Z2 Z0 Z1 (Z2 + Z0 ) + Z2 Z0 (2.28) Since the behavior of a power system is mainly inductive during a short circuit, Z0 , Z1 and Z2 may be replaced by X0 , X1 and X2 respectively. Assuming the fault is relatively far away from the generators, we can write for X1 = X2 . However for generator circuit breakers (GCB) special conditions apply with respect to grounding conditions and TRV’s [47, 48]. When including the star point of a transformer with complex impedance Zn = Rn + jXn the zerosequence impedance becomes Z0 = 3Zn + jX0 . Substituting Z0 in equation 2.29 yields: kpp = 3 3Rn + jX0 + 3Xn jX1 + 2 [3Rn + j(X0 + 3Xn )] (2.29) This means that in ungrounded systems the value of the neutral impedance, Zn , is infinite and consequenly the FPTC factor results in 1.5. For solidly grounded systems where, Zn = 0, the FPTC factor becomes: kpp = 2.4 3X0 X1 + 2X0 (2.30) The IEC 62271-100 The circuit breaker is considered to clear the fault successfully if the recovery of the dielectric strength across the breaker poles is faster than the recovery of the voltage across it. The specified TRV withstand capability of the circuit breaker is defined by the IEC 62270-100 [6]. The IEC characterises the TRV by two envelopes; The two-parameter envelope (Uc , t3 ) for circuit breakers with a nominal rated voltage up to 100 kV at all values of the breaking current and for breakers with a rating of 100 kV and above if the short-circuit current is equal or less than 30% of the rated breaking current. And by the four-parameter method (U1 , t1 ,Uc , t2 ) which applies for all other cases. From these characteristics, the so-called Limiting envelopes can be deduced in which the circuit breaker is able 17 Chapter 2 Resistance Reactance Ratio IEC criterion R0 = 0.673 Ω X0 = 7.978 Ω X0 /X1 = 1.550 0 < X0 /X1 < 3 R1 = 0.351 Ω X1 = 5.145 Ω R0 /X1 = 0.130 0 < R0 /X1 < 1 Table 2.3: Values for the sequence circuits of the TenneT 380 kV network to handle the imposed voltage stresses of the TRV. The two-parameter and fourparameter limiting envelopes are depicted in figure 2.9 and are characterized by the values given in table 2.4 and 2.5 respectively. The rate-of-rise is the same for both the 420 kV and 550 kV circuit breaker although the dielectric strength of the 550 kV breaker is higher. Therefore selecting a 550 kV circuit breaker instead of a 420 kV breaker does not make sense when it comes to the initial steepness of the TRV. When evaluating the TRV, the IEC 62271 standard makes the distinction between solidly earthed systems and non-solidly earthed systems. The IEC states that a system is effectively earthed if the ratio of the zero-sequence reactance to the positive reactance (X0 /X1 ) is positive and less than 3 and the ratio of zero-sequence resistance to that of the positive-sequence reactance (R0 /X1 ) is positive and less than 1. This criterion is related to the FPTC-factor and is discussed in sub-section 2.1.3 The Transient Recovery Voltage. Accordingly the 380 kV network of TenneT TSO is assessed on these ratio’s. They were calculated through the means of the IEC 60909 method in PowerFactory. The results are given in table 2.3. From here it can be concluded that the 380 kV transmission network of TenneT is effectively earthed. The test duties are defined as T10, T30, T60 and T100. Where the number stands for the percentage of the breaking current of the circuit breaker. This means that for a 63 kA circuit breaker the test duties can be translated into the following nominal breaking currents: T10 corresponds with a nominal breaking current of 6.3 kA T30 corresponds with a nominal breaking current of 18.9 kA T60 corresponds with a nominal breaking current of 37.8 kA T100 corresponds with a nominal breaking current of 63 kA 18 Fault Currents Voltage Uc Voltage Uc U′ U1 U′ td t′ t3 td t ′ t1 Time t2 Time Figure 2.9: IEC Two- and four-parameter limiting envelopes Test duty FPTC factor Time kpp First ref. voltage u1 Time Time delay Rateof-rise t1 TRV peak value uc t2 , t 3 td (kV) (µs) (kV) (µs) (µs) u1 /t1 , uc /t3 (kV/µs) (p.u.) T100 1.3 334 167 624 668 2-(47) 2 T60 1.3 334 111 669 666 2-33 3 T30 1.3 - - 687 137 21 5 T10 1.3 - - 682 97 15 7 Table 2.4: Standard values of prospective transient recovery voltage for a 420 kV CB, effectively earthed system [6] Test duty FPTC factor Time kpp First ref. voltage u1 Time Time delay Rateof-rise t1 TRV peak value uc t2 , t 3 td (kV) (µs) (kV) (µs) (µs) u1 /t1 , uc /t3 (kV/µs) (p.u.) T100 1.3 438 219 817 876 2-(61) 2 T60 1.3 438 146 876 876 2-44 3 T30 1.3 - - 899 180 27 5 T10 1.3 - - 893 128 19 7 Table 2.5: Standard values of prospective transient recovery voltage for a 550 kV CB, effectively earthed system [6] 19 CHAPTER 3 The Model his chapter describes how the TenneT transmission network is modeled in T PowerFactory and ATP-EMTP. It covers the methodology, validation and limitations of the grid models. Finally a comprehensive survey describes the relevant power system components with respect to EMT analysis. 3.1 Grid Model The primary aim of the grid model is facilitating the EMT short-circuit analysis in chapter 6: Case Study Maasbracht 380. Therefore surrounding 380 kV and 150 kV transmission networks of the substation are modeled. The grid models have been established with reference to the 2020 scenario of TenneT. The 2020 scenario is in a large extent based on the TenneT Vision2030 document which involves all possible future reinforcements for the Dutch transmission grid. Such as the new interconnection to Germany, Doetinchem - Niederhein, and the South-West 380 kV project [3, 12]. A geographic overview of the modeled part of the grid is given in figure 3.1. How the grid is modeled in detail will be discussed in the following sub-sections. The relevant data for the EMT models, such as the generator, transformer and line parameters, were retrieved from the PowerFactory IEC 60909 model, primarily intended for steady-state short-circuit calculations. This informational database is continuously updated and maintained by the Asset Management department of TenneT. All relevant power system component parameters are included in Appendix E Grid Parameters. 3.1.1 Initial study Based on an initial study it has been determined that at substation Maasbracht 380 the three-phase-to-ground short-circuit is the most severe fault which may occur. This represents the worst case scenario and is the criterion for TenneT to protect their substations and relating equipment. 21 Chapter 3 NorNed NorNed 2 COBRA 380 kV Transmission line Eemshaven 220 kV Transmission line 150 kV Transmission line 110 kV Transmission line Cross border line Gronau Vierverlaten DC interconnector Louwsmeer Cable or line under construction Meeden Diele Zeyerveen Oudehaske Hoogeveen Ens Hessenweg Beverwijk Hengelo Gronau Diemen Dodewaard Maasvlakte Brit Ned Waddinxveen Krimpen Wesel Geertruidenberg Boxmeer Borssele Weert Van Eyck Zandvliet Maasbracht Rommerskirchen Siersdorf Figure 3.1: A geographic overview showing the TenneT 380 kV network modeled in PowerFactory EMT and ATP-EMTP (indicated in yellow) 22 The Model 3.1.2 Topology of the Dutch Grid Model The PowerFactory IEC 60909 model provided by Asset Management is used as a reference for establishing network equivalent sources at appropriate boundaries.Locations at which the system became very “stiff” served as a boundary [24]. This can be interpreted as the location where the impedance is high in comparison to the rest of the grid, such as transformers. Another reasoning was that the further away from the location of the fault, the less impact the fault has. Resulting in more modeling liberties at remote points. At last the shape of the grid model played an important role. It did not contain any loops in order to rule out any back feeding short-circuit currents. This was evident for the determination of the equivalent sources. As a result the boundaries for the 380 kV grid are picked at the locations Krimpen and Hengelo and at all points where this grid is connected to the underlying 150 kV grid. With respect to grounding conditions it is trivial that each 380 / 150 kV transformer neutral was incorporated. Therefore the transformers are modeled with the equivalent sources at the LV-side. Substation Maasbracht 150 has been modeled in more detail, due to the presence of the Claus CC-B generator. Its subtransient reactance has considerable influence on the behavior of the fault current at substation Maasbracht 380. At last the 380 kV cross border lines where modeled. For the Belgium TSO Elia is was possible to derive equivalent sources for substations Zandvliet and Van Eyck with help of the ENTSO-E,, formerly known as UCTE, trans boundary informational data included in the PowerFactory IEC 60909 model. However with respect to the interconnections to Germany this was not the case, this will be discussed in more detail in subsection 3.1.5 Limitations. An overview of the grid models which are established in the software packes ATP-EMTP and PowerFactory are given in Appendix C Overview of the Grid Models. 3.1.3 Validation The two independent models in PowerFactory and ATP-EMTP are validated for 00 00 single-phase-to-ground, Ik1 , fault current and three-phase-to-ground, Ik3 , fault current according to figure 3.2. The validation process can be described in the following manner: 1. The simulation results are based on the input data from the equivalent sources and the power system components parameters. These parameters were retrieved from the PowerFactory IEC 60909 model which served as an informational database. 2. The actual validation was done by comparing the single-phase-to-ground, 00 00 Ik1 , fault currents and three-phase-to-ground, Ik3 , fault currents computed from the PowerFactory IEC60909 model, with that of the EMT grid models built in PowerFactory EMT and ATP-EMTP. Faults where initiated at different points in the Dutch grid to give a thorough comparison between the different models. The results are presented in table 3.1. The table shows that the difference between the models is between 2% and 8%. 23 Chapter 3 EMT grid models Validation Ik¨ Input of grid model parameters PowerFactory EMT Results PowerFactory IEC 60909 Validation i(t) Results ATP-EMTP TRV Study Validation Ik¨ Figure 3.2: EMT grid model validation principle Substation IEC 60909 00 00 Ik3 Ik1 (kA) (kA) PowerFactory EMT 00 00 Ik3 Ik1 (kA) (kA) ATP-EMTP 00 00 Ik3 Ik1 (kA) (kA) Borssele 32.4 33.2 32.3 31.8 32.2 31.1 Doetinchem 45.8 37.7 45.4 35.5 45.5 35.4 Dodewaard 35.4 28.8 35.1 27.7 35.0 27.5 Geertruidenberg 57.7 48.4 57.5 47.2 57.3 47.1 Maasbracht 70.5 55.0 69.1 53.2 68.4 53.4 Table 3.1: A comparison of the foreseen initial three-phase-to-ground fault currents, 00 00 Ik3 , and the single-phase-to-ground fault currents, Ik1 , between the IEC 60909 grid model, PowerFactory EMT grid model and the ATP-EMT grid model at a number of buses 3. Secondly the correctness of the dynamical short-circuit currents was evaluated by initiating a single-phase-to-ground and three-phase-to-ground fault at several locations in the grid. For substation Maasbracht 380 a comparison is given in figure 3.3 for phase b of the dynamical short-circuit. From there it is clear that differences are marginal (within 5%) and only visible when the DC component damps out. Conclusion The demonstrated deviations are considered to be acceptable for the purpose of the case study since the deviations fall within the expected margins that these models will have with respect to the real power system. Secondly the EMT software packages PowerFactory and ATP-EMTP are validated to each other and with respect to the IEC 60909 short-circuit calculation method. 24 The Model Three Phase fault current comparison ×105 2 1.5 Current [A] 1 0.5 0 −0.5 −1 ATP-EMTP phase b PowerFactory phase b −1.5 −2 0 0.05 0.1 0.15 0.2 Time [s] Figure 3.3: Bolted three-phase-to-ground short-circuit current comparison of phase b between PowerFactory and ATP-EMTP. The fault has been initiated at substation Maasbracht 380 3.1.4 TRV Study The TRV study is based on the ATP-EMTP grid model because of time contraints associated with this thesis. It turned out to be very time consuming modeling the fault current limiting measures presented in this thesis both in PowerFactory and ATP-EMTP. Since ATP-EMTP has a long tradition and history in the computation of electromagnetic transients, it was the preferred software package. In addition it has to be mentioned that many references in the technical documentation of PowerFactory refer to the EMTP Theory Book [19], which has been written by one of the originators of ATP-EMTP, Hermann W. Dommel. However in a potential follow-up study it would be higly recommended to implement the fault current limiting measures in PowerFactory and subsequently accomplish the validation with ATP-EMTP. 3.1.5 Limitations As stated earlier, information regarding the grids of neighboring TSO’s is rather limited. This is especially the case for transmission lines to Germany, where only the three-phase-to-ground and single-phase-to ground currents were provided. In conjunction with TenneT the R/X ratios of table 3.2 are assumed. It is apparent that there are no line parameters available and consequently this may influence the computation of the TRV and the dynamical short-circuit current. However it is still possible to derive an equivalent circuit based on the theory of symmetrical components. We may write for a bolted three-phase-to-ground 25 Chapter 3 00 00 Cross border line substation Ik3 (kA) Ik1 (kA) R/X Maasbracht - Siersdorf Maasbracht 10.8 8.06 0.1 Maasbracht - Rommerskirchen Maasbracht 7.9 6 0.1 Doetinchem - Niederrhein Doetinchem 16.36 13.21 0.1 Table 3.2: Fault current contribution from neighboring countries for the year 2020, provided by TenneT TSO department Asset Management short-circuit, defined as asymmetrical fault: 00 Un Ik3 = √ 3Z1 (3.1) Where Un is the line-to-ground voltage and Z1 the positive sequence impedance. From Z1 and a predefined R1 /X√ 1 ratio it is possible to derive the values for R1 and X1 respectively. With Z = R2 + X 2 we can derive for X1 : X1 = p Z1 1 + (R1 /X1 )2 And for R1 : q R1 = Z12 − X12 For the single-phase-to-ground fault one can write: √ 00 3U Ik1 = Z1 + Z2 + Z3 (3.2) (3.3) (3.4) Assuming the fault is relatively far away from the generator it is allowed to equate the positive-sequence and negative-sequence impedance (Z1 = Z2 ), [28, 53]. This assumption makes it possible to derive the Z0 /Z1 ratio from equations 3.1 and 3.4: 00 Z0 I = 3 k3 00 − 2 Z1 Ik1 (3.5) Another limitation of equation 3.5 is the fact that it does not take into account the mutual couplings of transmission lines. From equation 3.5 it possible to derive Z0 . An overview of the parameters for the equivalent sources is given in table E.6 in Appendix E Grid Parameters. 3.2 Modeling of Power System Components In this section a comprehensive survey is given on the topic of power system components EMT modeling. The choice of which components to include in the Dutch grid model has been determined according to the recommendations of 26 The Model the IEC 60071-4 [4]. There is a large amount of literature available which gives a thorough insight on the modeling of power system components. The reader is invited to review the relevant literature, appropriate references are included in the bibliography section. It has to be noted that ATP-EMTP and PowerFactory are using two different integration methods (equation solvers); the trapezoidal rule and the Newton-Raphson algorithm, respectively [49]. 3.2.1 Circuit Breakers During normal operation the circuit breaker is in closed position and a nominal current is flowing through the contacts. However the circuit breaker is designed for its main task: interrupting fault currents and isolating faulted parts of the grid. The circuit breakers opens its contacts when it receives a tripping signal from the protectional relays, normally this is within the order of five periods (100 ms) after the fault has occurred. The contact separation causes the generation of an arc and the current interruption is successful when the arc plasma between the breaker contacts is sufficiently cooled down. The IEC 62271-100 Annex F states that the influence of the circuit-breaker characteristics on the prospective TRV may be excluded [6]. This means that the circuit breaker acts as an ideal conductor (zero impedance) when closed and as an open circuit when opened (infinite impedance). However for the sake of comprehension the main circuit-breaker modeling methodologies are discussed hereafter. 1. The simplest circuit breaker model is based on an ideal switching action that is completely independent of the arc. It is represented by an ideal switch that opens its contacts at the instant defined by the user. Subsequently the fault current is interrupted at the current-zero crossing. This model is adequate in EMT studies where the breaker arc interaction with the enclosed network may be excluded. This method is prescribed in the IEC 62271-100 Annex F document, where the voltage across the breaker is to be compared with the pre specified TRV withstand envelopes. 2. A more elaborate model represents the circuit breaker as a time-varying conductance or resistance whose variation is determined by the breaker’s characteristic. The arc parameters of the breaker are measured during experiments in a High-voltage test facility or from precomputed TRV curves. Such a model can represent the effect of the arc on the system. Conversely this is not the case and therefore more advanced arc models are required. 3. The most advanced models employed for EMT simulations are the socalled Black box models. The arc is described by differential equations and gives the relation between the arc conductance and several parameters such as arc voltage and arc current. These models have the ability to represent both the effect of the arc on the system and the effect of the system on the arc. Most models are used to study the arc re-ignitions due to insufficient dielectric withstand capabilities between the breaker contacts. Others are used to study the thermal behavior and period of the breaker. Two classical black box models are treated with the following 27 Chapter 3 variables: g c,m τ c,m P0 us if = = = = = Conductance of the arc, S Time constant of the arc, s Steady-state power loss of the arc, W Steady state arc voltage, V Prospective fault current, A The Mayr model is given in equation 3.6 and is most suitable for studying the behavior of the arc conductance in the high-current time interval, when the plasma temperature is relatively high (8000 K or more) [37]. ! i2f 1 dgm = − gm (3.6) dt τm P0 The Cassie model is given in equation 3.7 and is applicable for the calculation of the arc in the vicinity of current-zero, when the temperature of the plasma is relatively low (below 8000K) [14]. ! i2f 1 dgc = − gc (3.7) dt τc u2s gc Both PowerFactory and ATP-EMTP do not include the elaborate and advanced circuit breaker models by itself. However many third-party resources are available which describe the implementation of non-linear arc models in EMT simulation software [22, 23, 50]. 3.2.2 Generators How synchronous machines are modeled depend very much on the type of transient study. With respect to the first few cycles of a short-circuit the representation of a voltage source behind a subtransient reactance Xd” can be considered as reasonably accurate. However this thesis also has the aim to validate the dynamical short-circuit current of two EMT software packages, therefore a considerable fault current timeframe has to be taken into account. Meaning that an accurate generator model is preferred. Both PowerFactory and ATP-EMTP include a general-purpose generator model which is based on Park’s transformation from abc phase variables to dq0 components. This is a reference frame in which the self and mutual machine inductances are constant. This is advantageous as the stator and rotor equations of the synchronous machine contain inductance terms which vary with angle θ which in turn varies with time. This makes it rather complex to solve the machine and power system variables. In PowerFactory the generator model is represented by the “standard” EMT model, in ATP-EMTP this is the SM58 or SM59 model. Both include the possibility to add saturation characteristics. For further reference please see [1, 19, 31, 46]. 3.2.3 Transmission Lines Usually electrical devices are analyzed through the theory of lumped or concentrated models, with constant parameters for the resistance, capacitance and 28 The Model inductance. In reality these parameters are distributed in any circuit or piece of equipment. Whether the circuit is modeled by lumped or distributed elements depends on the purpose of the model. For steady state analysis a lumped element representation is adequate as the 50 Hz wavelength is considerably long. However for transient analysis this is no longer the case and the effect of traveling waves has to be incorporated. A PI section represents the transmission line by a branch of lumped elements. An example of a PI section with mutual couplings for a three-phase system is given in figure 3.4. When the travel time is less than the solution of the time step, PI sections are suitable for EMT calculations. Considering the length of most transmission lines, distributed models are preferred. Unlike lumped elements, distributed models have the unique property to support traveling waves of current and voltage. Only the key elements of transmission line theory is given in the subsequent derivations. For a complete overview on this matter, the author suggests the following literature [24, 51]: The velocity of the current and voltage waves traveling along a lossless circuit can be expressed with: v=√ 1 LC The inductance can be approximated by: µ d 0 L= ln 2π r (3.8) (3.9) And the capacitance with the approximation: C= 2π0 ! d ln r (3.10) Substituting equation (3.9) and (3.10) into equation (3.8) yields: v=√ 1 µ0 0 (3.11) Equation (3.11) shows that the wave velocity is independent of the line geometry. It is solely dependent on the relative permeability and relative permittivity of the conductor. The ratio of the amplitude of a single voltage wave to its current wave on a transmission line is called the characteristic impedance, Z0 . r L Z0 = (3.12) C Unlike the wave velocity, v, the characteristic impedance depends upon the line geometry. Since the transmission line also has a reflected wave, the characteristic impedance does not represent the impedance measured on the line. The theory of wave reflection and refraction is discussed hereafter. Normally when an electromagnetic wave propagates along a transmission line, there is a strict “proportionality” between the voltage and the current wave. This proportionality is called the characteristic impedance of the line. When the wave arrives at a discontinuity, such as an open circuit or short-circuit, the 29 Chapter 3 ia va ib vb i c vc R vá R vb́ R vć Figure 3.4: Representation of a three-phase transmission line by a PI section characteristic impedance changes. But due to the proportionality the wave has to be “adjusted”. This adjustment consists of the initiation of two new wave pairs. At the discontinuity a part of the energy is let through and a part of the energy travels back in form of an electromagnetic wave. The total amount of energy in the electromagnetic waves remains constant, such that the voltage to current proportionalities are preserved, as demanded by the characteristic equation. The magnitude of the reflected voltage wave at a discontinuity with characteristic impedance ZA and ZB on the incident side and refractive side, respectively, is described by equation (3.13): V2 = ZB − ZA V1 = ρ1 ZB + ZA (3.13) The refracted voltage wave is defined as (3.13): V3 = 2ZB V1 = α1 ZB + ZA (3.14) Where V1 is the incident wave, V2 is the reflected wave and V3 is the refracted wave. ρ and α are defined as the reflected and refracted coefficient respectively. A suitable line model based on the traveling wave principle is the Bergeron’s routine integrated within ATP-EMTP and PowerFactory [10]. It is based on the constant frequency method, the line is treated as lossless but distributed series resistance is added in lump form. This model gives acceptable results, provided that R/4 Z0 . For high frequency studies, the Bergeron’s model may not be adequate [39]. Other models, such as the JMarti routine, include the frequency dependant characteristics of a transmission line. However physical dimensions of the line are required (i.e. conductor radius, and conductor positions) [36]. 3.2.4 Transformers A complete EMT model for transformers would require every winding being represented, including all mutual couplings, both inductive and capacitive. In practice such an extensive model is undesirable. In short, the purpose of the simulation determines the type and extent of the transformer model. If for example the accuracy of the simulation is within the microseconds range, no significant current is able to penetrate the windings because of its inductance. As a result currents are displaced and flow into the capacity of the windings. Therefore if the transformer has to be accurately modeled with respect to the initial voltage distribution, capacitive elements have to be included [24]. 30 The Model When carrying out switching studies, with respect to TRV’s caused by vacuum circuit breaker re-ignitions, a capacitive model would not suit the needs [45]. If the transformer is switched in at no-load, the model should represent the influence of the transformer winding and core. Possible re-ignitions contain oscillations with different frequency components, resulting in a variable transformer winding impedance. Considering the case study in chapter 6 where the transient behavior of the series reactor and SCFCL is evaluated, a transformer model results in a simplified case. The ATP-EMTP BCTRAN transformer model and the PowerFactory standard transformer model, the standard will suit the criteria for the short circuit current and TRV calculations as described in the IEC 62271-100 Annex F. The transformer models in ATP-EMTP and PowerFactory will be addressed accordingly. ATP-EMTP model The BCTRAN routine is part of the ATP-EMTP and embodies a three-phase two-winding or three-winding transformer. It is based on a matrix representation containing two matrices R and L. These represent the transformer with respect to excitation and short-circuit tests for zero and positive sequences. To get a understanding of the matrix representation concept, a single phase twowinding transformer will be considered. It is described by following steady state phasor equations: V1 Z11 Z12 I1 = (3.15) V2 Z21 Z22 I2 The matrix in equation (3.15) is symmetric. The characteristic parameters are visualized in figure 3.5. L11 and L22 are the self inductance of windings 1 and 2 respectively. L12 and L21 represents the mutual inductance between the windings. [Z] is described by: Zij = Vi Vj (3.16) When applying the trapezoidal rule to solve the matrix in equation (3.15), it has to be rewritten in the form of the following differential equation: V1 R11 R12 I1 L11 L12 d I1 (3.17) = + V2 R21 R22 I2 L21 L22 dt I2 The differential matrix representation is the fundament of the BCTRAN routine and is extended in severals ways to model a complete transformer adequately. Extensions are the impedance matrix containing self and mutual impedances, related to the positive and zero-sequence values for example. The full circumscription of the BCTRAN model is given in [19]. PowerFactory model The exact operating principle of the PowerFactory EMT transformer model is undisclosed. However an equivalent circuit of the 2-winding 3-phase transformer is supplied in the transformer technical reference manual of PowerFactory, it is 31 Chapter 3 i1 v1 L1 R1 L2 L12 R2 i2 v2 Figure 3.5: A simplified transformer model in the ATP-EMTP BCTRAN routine Figure 3.6: Equivalent circuit of the 2-winding 3-phase transformer model in DIgSILENT PowerFactory depicted in figure 3.6 [20]. It is assumed, based on the references made in the technical reference manual that the transformer model makes use of a similar solving principle as compared to ATP-EMTP. The PowerFactory model provides the possibility to include transformer winding capacitances in contrast to the transformer model of ATP-EMTP. 32 CHAPTER 4 Fault Current Limiting Reactors ault current limiting reactors are applied in power systems to reduce shortF circuit currents to levels within the electromechanical and thermal withstand capabilities of power system components. Fault current limiting reactors can be installed at different points in the grid and they are mostly referred to their location and application. In this chapter two types of reactors will be discussed: The series reactor; in series with incoming or outgoing feeders or used to tie together two independent buses The neutral grounding reactor; installed between the neutral of a transformer and the earthing point 4.1 Applications of Reactors 4.1.1 Series Reactors Series reactors are placed in line with incoming or outgoing lines or feeders. Or can used to tie together two independent buses. The main advantage is the ability to reduce the single-line-to-ground fault and three-phase-to-ground fault current to desired levels. The maximum limiting capability depends on physical limitations of the reactor. Other benefits are the improvement of the primary bus voltage during faults and reduction of the current-interrupting duty of circuit breakers. However series reactors have the contradictory property of limiting fault current on the one hand but increasing the magnitude of the TRV on the other hand. This will become clear in sub-section 6.3. The required impedance to limit the three-phase fault current is calculated by either equation 3.1 or 3.2: XCLR = VLL ((1/ISC,af ter ) − (1/ISC,bef ore )) √ 3 (4.1) 33 Chapter 4 2 XCLR = VLL ((1/M V ASC,af ter ) − (1/M V ASC,bef ore )) (4.2) where: XCLR VLL ISC af ter,bef ore = = = M V ASC af ter,bef ore = 4.1.2 reactance of the current limiting reactor, Ω rated line-to-line voltage, kV value of the short circuit current after and before the fault, kA value of the short circuit power after and before the fault, MVA Neutral Grounding Reactors Neutral grounding reactors are installed in between the star point of a transformer or generator and the earth grounding point. The implementation is most effective where generators are solidly grounded since then the single-line-toground fault in most cases exceeds the magnitude of the three-phase-to-ground fault [40]. They are able to limit the single-phase-to-ground faults and do not limit symmetrical faults. Another drawback is the rate-of-rise of the TRV of the unfaulted phases. This may form an issue as a result of the X0 /X1 ratio that could exceed the critical value of an effectively earthed system. This drawback can be partly overcome when applying neutral grounding resistances in the power system. Thanks to the fact that only one neutral grounding reactor is needed per transformer or generator, the investment costs for neutral grounding reactors are rather low in comparison with series reactors. When comparing operating losses, neutral grounding reactors are also in favor when taking into consideration that only single-line-to-ground faults are limited. 4.2 4.2.1 Technical Aspects of Series Reactors Air-core Reactors Thanks to their linear behavior of inductance versus current, air-core reactors have been traditionally in favor regarding current limiting applications. Generally its mechanical construction is fully encapsulated, aiming on a higher withstand level to fault currents. A modern encapsulated Air-core reactor is depicted in figure 4.1. The primary source of acoustic noise is the radial vibration of the winding due to AC current flowing through the winding. Air-core reactors carrying only power frequency produce noise at twice the fundamental frequency. The acoustic noise will substantially increase when the reactor’s current spectrum includes multiple harmonics; “n” harmonic currents can generate at most n2 forcing frequencies [26]. The magnetic field of an air-core reactor is not constrained and occupies the space around the reactor. Although the magnetic field decreases with the distance from the reactor, it still may play an significant role with respect to safety and health. An important factor is the distance to metal parts, for example fences, grounding mesh grids or concrete reinforcements. There should be sufficient distance to metal parts because of the eddy current losses that 34 Fault Current Limiting Reactors Figure 4.1: Encapsulated Air-core reactor may be induced and as a result unwanted heating may occur. The European Directive 2004/40/CE defines the maximum levels of electromagnetic fields that workers should be exposed to. These levels depend on the frequency as the effect on the human body depends as well on the frequency. In the range from 25 to 800 Hz the electrical field must be below 500 (V/m) and the magnetic induction below 5000 (uT). 4.2.2 Oil-immersed Reactors Unlike air-core reactors, oil-immersed reactors do not suffer from high external magnetic fields thanks to the mechanical construction of a closed tank filled with mineral oil. Therefore it is safe to carry out maintenance work in the proximity of the air-core reactor. The active part consists of paper-insulated coils with copper windings. The magnetic circuit is based on end-shields with the reactor coils in between. The sound sources from oil-immersed reactors are more complex compared to air-core reactors. It depends on the design approach and includes combinations of and contributions from magnetic and non-magnetic shieldings, windings and core. The key is to minimize and avoid mechanical resonance to reduce sound levels. Additional benefits of oil-immersed reactors are the straightforward installation of noise reduction measures. Where for aircore reactors this is far more complex due to the construction above ground. Oil-immersed reactors are also more robust since the active parts, such as the windings, are immersed in oil and therefore benefit from paper-oil insulation. At last oil-immersed reactors can be tested according IEC standards, as most manufacturers of air-core reactors do not own their own test facilities. This is 35 Chapter 4 Figure 4.2: Oil-immersed reactor with external cooling an important benefit for TSO’s to ascertain their quality checks. 4.3 A Practical Model 4.3.1 Technical Parameters For the EMT model of the series reactor, practical data from a 400kV - 4000A three phase series reactor was obtained. The information was acquired from a recently commissioned project in the TenneT transmission network: MaasvlakteWesterlee. Here two series reactors will be installed to compensate the system impedance with the rest of the transmission network. Information regarding the construction of the series reactor, was obtained by a factory visit by KEMA and TenneT [27]. 36 Fault Current Limiting Reactors Cs Rs CE /2 Ls CE /2 Figure 4.3: Per phase equivalent circuit 8 Ohm L (mH) Lsat (mH) Rs (mΩ) Cs (pF) Creactor (pF) 27.06 23.87 26.15 10...500 1000 Table 4.1: Equivalent circuit parameters Technical Specifications System voltage: Test voltages: Nominal current: Nominal impedance: Minimum impedance at full short circuit: Losses at 4000A: Cooling stages: Um = 420 kV BIL = 1425 kV / SIL = 1050 kV / AC = 630 kV I = 4000 A 8Ω XSAT = 7.5 Ω 1255 kW ONAN up to 2000 A ONAF up to 2500A ODAF up to 4000A Cbushing = 1330pF (4.3) CE /2 = Cbushing + Creactor /2 (4.4) where: L Lsat Rs Cs Creactor = = = = = unsaturated reactance, mH saturated reactance, mH series resistance, mΩ winding capacitance, pF reactor capacitance, pF The model is based on an impedance of 8 Ω. This value translates in an unsaturated reactance of 27.03 mH and a series resistance of 26.15 mΩ. The impedance of 8 Ω is adequate to limit the fault current within the limits of the proposed 63 kA circuit breakers at station Maasbracht 380. The saturation characteristics where modeled by taking into account two inductors in series: 37 Chapter 4 I (A) Flux-linkage (Wb-turn) Knee point (end of linear section) 10100 43.95 Saturated section 55000 68.29 Table 4.2: Saturation characteristics Return limb Coil Coil Coil Return limb Upper yoke Bottom yoke Figure 4.4: Encapsulated Air-core reactor a linear 22.68 mH inductor, representing the air path of the magnetic circuit a non-linear 4.35 inductor, representing the iron core part of the magnetic circuit The saturation characteristics of the 4.35 mH saturable inductor are given in table 4.2. The saturatation is relatively mild thanks to the particular construction of the reactor. The magnetic circuit consists partly of an iron path when the flux passes the bottom and upper yoke and the two return limbs as can be seen in figure 4.4. The main reactance is formed by the flux that passes through the path of the coils, splits in the iron tank and the mineral oil that has the same permeability as air. Thus when the iron path goes into saturation it has a marginally impact on the total impedance. 4.3.2 ATP-EMTP Model of the Series Reactor The series reactor was modeled in ATP-EMTP and based on the circuit diagram depicted in figure 4.3. The 4.35 mH saturable inductor was represented by a TYPE-98 nonlinear current-dependent inductor, its non-linear characteristic is given in figure 4.5. The 22.68 mH inductor was represented by the model of an ideal inductor in ATP-EMTP. The following parasitic capacitances that have been provided by the series reactors’ manufacturer were incorporated: Winding capacitance (Cs ) of 500 pF 38 Fault Current Limiting Reactors Terminal capacitance (CE /2) of 1830 pF Figure 4.5: Non-linear characteristic of the saturable inductor 39 CHAPTER 5 Superconducting Fault Current Limiters he state when a conductor experiences zero-resistance, superconductivity, T was discovered by the Dutch physicist Heike Kamerlingh Onnes in 1911. He observed that the resistance of mercury when cooled to a temperature of 4.2 K, almost disappeared [43]. The discovery in 1986 of superconductors with transition temperatures above the boiling point of nitrogen has renewed the interest in large-scale applications. These are the so-called High temperature superconductors (HTS) and were discovered by Karl Müller and Johannes Bednorz. They are known by their relatively high critical temperature above 30 K. 5.1 Superconducting Materials SC materials are characterized by a three-dimensional graph in which the current density, temperature and magnetic field are plotted respectively [11]. If one of these parameters exceeds the critical levels of the operating area, the SC material will experience a superconducting-to-normal (S/N) transition. The highest temperature at which the SC material is not experiencing electrical resistivity is called the critical temperature Tc . The maximum current the SC Magnetic field, B Bc Critical surface Current density, J Jc Tc l Temperature, T Figure 5.1: Superconductor critical surface is a function of the magnetic field B, current density J and temperature T. 41 E [V/cm] Chapter 5 N-value E=1µV/cm Current [A] Ic Figure 5.2: V-I curve of a superconductor can carry before superconducting-to-normal transition takes place, is called the critical current density Jc or critical current Ic . Ic is derived from the definition of “a voltage drop along the length of a wire as a function of its current” [29]. The industry accepted practice is to define the SC’s critical current as a function of the current that produces a voltage drop of 1µV/cm along the conductor. At last the critical magnetic field at which the SC material loses superconductivity is defined as Hc . To the V-I curve where the S/N transition for a given SC test sample is plotted, a power law can be fitted as depicted in figure 5.2. This power law is given in equation 5.1. Where E(I) is the voltage drop across the superconductor, Ec is the electric field criterion at 1µV/cm, T is the temperature dependency and I is the current flowing through the SC. N is the SC material dependent exponent and influences the coefficient of the V-I curve. This power law is quite accurate since the heating process is adiabatic and independent of the behavior between the SC’s material and the cryogenic system. N (T ) I E(I) = Ec (5.1) Ic Since the discovery of HTS materials in the 1980’s, research has increased with respect to the application of fault current limiting purposes. HTS materials have come to be known as second generation (2G) superconductors as these materials where discovered after the introduction of the so-called low-temperature superconductors (LTS). HTS are cooled with liquid nitrogen LN2 and have a critical temperature above 30 K. This is a great advantage compared to LTS’s which usually operate very close to their critical temperature at 4.2K and therefore very sensitive to temperature changes. Consequently the refrigeration system, which mainly consists of external tanks filled with LN2 or He, must have a higher capacity. By using HTS for FCL applications, instead of LTS - refrigerations costs can be decreased by a factor of 10 [60]. Most used HTS materials come in bulk or thin film, the most important SC’s for FCL applications are discussed below: YBa2 Cu3 O7 Yttrium-barium-copper-oxide typically referred to as YBCO was discovered in 1987 [34]. Its critical temperature, Tc is equal to 93 K. It comes in 42 Superconducting Fault Current Limiters bulk form or can be applied in the form of YBCO CC, where CC stands for coated conductor. YBCO CC has an improved (larger) contact area with the cryogenic environment. This facilitates easier and faster heat transport in comparison with bulk material and therefore recovery times are improved. In some cases YBCO CC is also referred to as (RE)BaCuO, where RE stands for rare-earth material. Bi2 Sr2 Ca1 Cu2 O8 Bismuth-strontium-calcium-copper-oxide typically referred to as BSCCO 2212 or Bi 2212 was discovered in 1988 [25]. Its critical temperature, Tc is equal to 95 K. Bi2 Sr2 Ca2 Cu3 O10 Typically referred to as BSCCO 2213 or Bi 2213 with a critical temperature Tc of 107 K. MgB2 Magnesium-diboride discovered in 2001 with a critical temperature, Tc , of 39 K [60]. It’s a relatively new discovered SC material and the price per unit length is significantly lower, as will be discussed in chapter. Conversely the cryogenic system needs to have a higher cooling capacity, as the critical temperature, Tc , is much lower. This results in higher operating costs, but it is imaginable that in some cases the total cost of ownership of an SCFCL with MgB2 is lower in comparison with systems where YBCO or Bi 2212 is applied. YBCO CC, is the most promising SC for FCL applications because it has a high critical current density and a good temperature stability. The four main aspects which are leading in the design and choice of a HTS material are addressed accordingly: 1. Recovery time of the SCFCL The time needed for a SCFCL to cool down below the critical temperature after S/N transition is called the recovery time. The recovery time depends on the thermal capacity of the cryogenic zone and the amount of dissipated heat during a fault. This is an critical factor in the design and application of HTS materials and has consequences on the operation and protection of the power system. The recovery interval is in most cases within the order of several seconds for thin film SC’s and in the order of minutes for bulk SC material and primarily depends on the magnitude and duration of the fault [7, 33]. During this period, the fault current limiter is still acting as an impedance. The recovery delay can be reduced by using YBCO CC. 2. Maximum limiting period of the SCFCL During a fault the SC elements and cryogenic system is dissipating energy in the form of heat. Thus the duration of the fault limiting period is directly related the amount of dissipated heat. The SC material can be damaged by overheating and the fault must be cleared within reasonable time [57, 58]. The maximum limiting period of the SCFCL can be calculated. This is done as an example in section 5.4.1 Design Aspects of a SCFCL. 43 Chapter 5 3. Hot-spots in the SC material Hot-spots are local power dissipations in the SC material when stressed by a fault current. They are caused by electrical inhomogeneities and are the weak spots of the SC material. Consequently an uneven distribution of the fault current will occur, resulting in the so-called hot spots. This is an exponential process as can be estimated from the characteristics of the SC material. 5.2 Costs of SC Materials A major drawback of SCFCL’s is the price of SC materials and the investment of crygogenic cooling systems. Currently the price of copper ranges between 25 euro/kA-m to 50 euro/kA-m. To compete with the price of copper, the price-performance-ratio of SC materials has to increase. At present the price of LTS SC wire is 150 euro/kA-m while the price for HTS SC wire is in the order of 200-300 euro/kA-m. For the long term it is expected that the price of LTS wire will drop to 50 euro/kA-m and for the HTS wire it will decrease to 10 euro/kA-m. The costs of SC materials are determined by three factors: productions costs, equipment costs and the costs of the SC raw material. Future improvements of the production process could lead to increased yields and quality of the SC materials, which will most probably result in cost reductions and quality enhancement. The overall price of SCFCL’s can be reduced by these enhancements as lower AC losses in the SC material would result in smaller cryogenic systems and therefore an improved business case and lower costs of ownership [16]. 5.3 5.3.1 SCFCL Topologies Resistive Type Resistance The resistive type SCFCL is based on the non-linear behavior of the superconducting material. The transition from the superconducting state to the normal conducting state is called the “quench”. During normal operation or superconducting state, the resistance of the superconductor, RHTSC is negligible. In case of a fault, the short-circuit current supersedes the critical current density and critical temperature of the superconductor and consequently will develop a resistive characteristic as shown in 5.3. The resistance Rp placed in parallel to the superconductor as depicted in figure 5.4 is needed to protect the suNormal conductor perconductor from “hot spots”. This parallel resistance is in fact a metalized thin-sheet wire which is contacted all over the length of the super Superconductor conductor. This will also help protect the superconducting alloy from over Tc Temperature voltages if RHTSC rises too rapidly. Figure 5.3: Evolution of the SC’s resistiv- The fault has to be cleared by the cirity as a function of tempera- cuit breaker, CB, in order to limit the ture 44 Superconducting Fault Current Limiters Rp Ls Rs RHT SC Limiter iF CB Zf U Figure 5.4: Electrical circuit of resistive type SCFCL Figure 5.5: 110kV Resistive type SCFCL from Siemens; 1. FCL, 2. LN2 refill tank, 3. bushings, 4. busbars, 5. voltage transducer [8] maximum temperature of the superconductor. These kind of the SCFCL’s are fail safe and can be built compact with marginal impedance during normal operation. Drawbacks are the cryogenic losses from the current leads and bushings that cause heat losses due to thermal conduction. Another drawback is the recovery time, which is in the order of seconds to minutes. An overview of planned and recently commissioned resistive type SCFCL pilot projects is given in Appendix B, Overview of SCFCL projects. 5.3.2 Saturated Iron Core The operating principle of the saturated iron core, also refererd to as DC biased core FCL can be explained through the behavior of a non-linear inductor. The impedance L,sat is a function of the length l of the flux path, the cross-sectionial area A, the number of turns N and the relative permeability of the core µ. By driving the magnetic core into saturation the inductance value L of the inductor decreases and the B-H working point can be manipulated as is depicted in figure 45 Chapter 5 B 5.6. The principle of operation of a saturated core FCL is independent on the type of material used for the inductor, for instance copper or SC material. However, AC losses and inductor size are greatly reduced when SC material is applied for the windings of the inductors. The values of the inductance in the Bsat A l ΔB µ=ΔB/ΔH ΔH Linear region Saturated region H N Hsat Figure 5.6: Non-linear B-H curve Figure 5.7: Magnetic circuit of a core with wounded inductor saturated and unsaturated case can be approximated by the following equations [38]: L = µ0 µr N 2A ; l Lsat = µ0 µr,sat N 2A l (5.2) where: L Lsat µ0 µr µr,sat = = = = = unsaturated reactance, mH saturated reactance, mH permeability of air unsaturated relative permeability of the core saturated relative permeability of the core The core can be saturated by an additional winding conducting a DC current or could be biased by using a permanent magnet. The winding of the inductor is placed in series with the line and conducts the AC current. During normal operation the AC current iac must be low enough to keep the core fully saturated. In case of a fault the magnitude of the AC current will drive the inductor out of saturation and into the region of high relative permeability on the B-H curve. The fault current is quenched in the magnetic core. This results in an immediate recovery after a fault. Less SC material is needed which results in another benefit, a smaller cryogenic system. A drawback is the large size of the system, due to the dimension of the iron core. When the magnetic core in figure 5.7 is driven into saturation it will only limit the fault current for one polarity and not the full AC current. When using a single magnetic core the fault current would desaturate in one half-cycle and driven further in saturation the second half-cycle. To resolve this issue, two magnetic cores in opposite direction can be employed [9]. This setup is depicted magnetically in figure 5.9 and electrically in figure 5.8. Also the waveforms for a bipolar saturated core FCL are given in figure 5.10, where both iron cores are driven into saturation. This causes the magnetic circuits to operate around the magnetic fields HDC1 and HDC2 respectively. Drawbacks are the relatively large footprint; equal to a transformer with the same power rating. And the need for an auxiliary DC source or permanent 46 Superconducting Fault Current Limiters Rs iac Ls L1 iF L2 U DC CB Limiter DC Zf Figure 5.8: Electrical circuit of saturated iron core SCFCL I dc Ndc i ac Nac Ndc Nac ac line Figure 5.9: Magnetic circuit of saturated iron core SCFCL magnet to bring the core into saturation. Applying a permanent magnet in a 380 kV FCL is not feasible at this moment and probably will not be in the future. An overview of planned and recently commissioned saturated iron core type SCFCL pilot projects is given in Appendix B, Overview of SCFCL projects. 5.3.3 Magnetic Shielded Core The magnetic shieldeld core SCFCL or often referred to as inductive type SCFCL, is a two-winding transformer consisting of a short-circuited secondary winding. The secondary winding reflects zero-resistance to the primary windings during normal conditions. An representing electrical circuit is given in figure 5.12. The magnetic shielded core concept was originally invented by Dersch [18]. The construction of the magnetic shielded iron core is based on a conventional primary winding around an iron core and SC cylinder in between. The cylinder consists of several melt casted SC elements, which form the magnetic shielding. During normal operation the induced current in the superconducting cylinder is lower than the critical current of the SC magnetic shield, therefore serving as a short-circuited secondary winding. The residual impedance is limited to the losses in the primary winding Rl and the stray inductance Lσ between the primary winding and the SC cylinder. The electrical circuit of the magnetic shielded iron core SCFCL during short-circuit operation is given in figure 5.13. During a quench the short-circuit current exceeds the critical current of the SC cylinder and therefore will develop a resistance. The flux generated by the primary windings is penetrating the iron core and the limiting impedance is formed by magnetizing inductance Lh and the resistance RHTSC . Whether the current 47 Chapter 5 L1 = dB1 dH1 HDC1 H1 B1 H1 U0 iac Δv = (L1 + L2 ) di ac dt t H2 B2 H2 HDC2 L2 = dB2 dH2 Figure 5.10: Wave forms of the bipolar saturated core SCFCL [35]. 48 Superconducting Fault Current Limiters Superconductor N Figure 5.11: Magnetic circuit of the magnetic shielded iron core SCFCL limitation is predominantly resistive or inductive is determined by the factor ω(Lh − Lσ ) > N 2 RHT SC . If both terms are comparable then the limitation is of a mixed type [55]. The resistance of the SC cylinder is reflected by the squared winding ratio of N1 /N2 times RHTSC . This factor can be derived by the following equations: U1 = N2 U2 N1 (5.3) I2 = N1 I1 N2 (5.4) By multiplying equation (5.3) by equation (5.4): U2 I2 = U1 I1 By dividing equation (5.3) by equation (5.4): 2 U1 N1 = R1 = RHT SC I1 N2 (5.5) (5.6) It is advantageous that the SC material is exhibited to large currents but low voltages, this reduces the effect of hot-spots. Also the lack of current leads to the cryogenic compartment reduces the effect of heat losses. A drawback is the recovery time of several seconds to minutes, because the quench takes place in the SC material. This is similar to resistive type SCFCL’s where the quench also takes place in the SC material. Another drawback is size, which is similar to the weight and volume of a transformer with the same power rating. An overview of planned and recently commissioned magnetic shielded core type SCFCL pilot projects is given in Appendix B, Overview of SCFCL projects. 5.3.4 Solid State FCL’s Other topologies are based on the application of high-power semiconductors. With their fast turn-off capability, semiconductors such as IGCT’s, GTO’s and IGBT’s are the ideal breakers. Major drawbacks for 380 kV applications are size (several football fields, comparable to a HVDC substation), on-state losses, requirement of auxiliary circuits (e.g. turn-off snubbers), limited blocking voltage and reduced breaking current capabilities. Therefore solid state FCL’s are not in the scope of this document. However for low voltage applications semiconductors can be applied as a feasible solution in FCL applications. 49 Chapter 5 iac Ls Rs Rl CB L1 i2 L2 Zf U Limiter RHT SC Figure 5.12: Electrical circuit of the magnetic shielded iron core SCFCL Ls Rs R1 Lh Lσ iF CB i2 Limiter U RHT SC Zf Figure 5.13: Electrical circuit of the magnetic shielded iron core SCFCL during short-circuit 5.3.5 Overview of Different SCFCL Types To conclude, a comparative summary of several SCFCL types is given in table 5.1. At present novel (SC)FCL’s like described in the foregoing subsections are not commercially available. It is difficult to predict which SCFCL will be the most promising for the future. In any case fast current limitation is achieved with all SCFCL types. The main differences are covered by the parameters: recovery-time, fail-safeness, normal operation losses and size. The main requirements for SCFCL’s are: Fast quenching Fast recovery Ability to self recover Fail-safe and reliable operation Low AC and cryogenic losses Compact and light weight Low investment costs and economic operation The most compact solution is offered by the resistive type, however the problems regarding the effects of hot-spots first have to be overcome. With respect to fast recovery, the saturated iron core is the most promising since the quench does not take place in the SC. Considering the fact that the effect of hot spots is greatly 50 Superconducting Fault Current Limiters Losses Fail safe Amount of superconductor Size Recovery Resistive SC AC losses and current lead losses Yes Medium Small Few seconds up to minutes Saturated iron core Iron core losses and primary conductor losses No Small Large Immediate Magnetic shielded core Iron core losses and primary conductor losses Yes Small Large Immediate Solid state Semiconductor No AC losses May be equipped without SC material Depends on voltage level Immediate Table 5.1: Comparative summary of SCFCL concepts reduced and no auxiliary DC circuits are needed, today the magnetic shielded core is the most promising solution for transmission level voltages. This concept will be translated into a model for ATP-EMTP in the case study Maasbracht 380. Additional comparative summaries of SCFCL concepts are given in [35, 54]. 5.4 A Practical Model for a Shielded Core SCFCL 5.4.1 Design Aspects of a SCFCL The basic principles of designing a SCFCL are relatively simple. Most important parameters are the maximum permissible fault current Ilim , fault duration ∆t and temperature rise ∆T of the SC material. It is assumed that the heat resistivity and capacity are temperature independent. In equations 5.7 and 5.8 the limiting resistance R and limiting current Isc are given respectively [29]. R= U ρ` = Isc A s Isc = A C∆T ρ∆t (5.7) (5.8) The corresponding maximum permissible electric field during limitation is given in equation 5.9 and is independent of the cross sectional area, A. r ρC∆T Esc = (5.9) ∆t 51 Chapter 5 Figure 5.14: E(j) characteristics for different Bi 2212 samples @65 K. [32]. where: R U ` ∆T ∆t A C Isc Esc = = = = = = = = = SCFCL resistance during fault, mΩ system rms voltage, V length of SC material, m maximum permissible temperature rise, ◦ C maximum permissible fault duration time, s cross sectional area, m2 specific heat of SC and stabilizer maximum permissible SC fault current, A maximum permissible SC electric field during limitation, V/m By solving these equations the minimum conductor volume is obtained. The minimum conductor value can also be approximated by equation 5.10 [44]. V olume = Isc U ∆t C∆T (5.10) This means that in the case of a 380 kV limiter with Isc = 4000A, a limited fault current for 0.1 seconds (five periods @50 Hz) and a 100 K maximum permissible temperature rise in a bulk volume with the approximate specific heat value of 2 × 106 J/m3 K, results in 0.76 m3 of SC material per phase. The minimum cross sectional area A, can be determined by equation 5.8 or directly from test samples of bulk (Bi 2212 / Bi 2213) SC material depicted in figure 5.14. In short the cross sectional area has to be large enough to reduce the SC losses, but small enough to ensure a fast transition from superconducting state to normal state. Finally the length of the SCFCL determines the total limiting resistance R. 5.4.2 ATP-EMTP Model of the Magnetic Shielded Core SCFCL The non-linear behavior of the SC material is temperature dependent which again is a function of the fault-current. The temperature rise versus time can 52 Superconducting Fault Current Limiters Function of the resistance R 10 Resistance [Ω] 8 6 4 2 0 0.04 0.05 0.06 0.07 0.08 0.09 0.1 Time [s] Figure 5.15: Evolution of the resistance as a function of time be calculated under the assumption that the heating effect due to the transition from superconducting state to normal state is adiabatic. In other words the heat dissipated in the SC material will not be transferred to the coolant in such a short notice. It was found rather complex to model a temperature dependent resistance which was again a function of the fault current. In particular it was difficult to achieve an equilibrium between the evolution of the resistance and the fault current. Instead a more pragmatic way was selected to model the magnetic shielded core SCFCL. It was accomplished by a time dependent resistance evolution connected to the secondary winding of an ideal transformer. It is assumed that the behavior of the magnetic shielded core SCFCL is predominantly resistive. The model is built up with use of the MODELS1 block set in ATP-EMTP. The TACS controlled resistor is driven by the function RHT SC = 25t0.35 which is an output of the MODELS block set to the TACS resistor. The rise time of the resistance evolution is derived from the quenching behavior of an YBCOcoated conductor in [56]. The aim is to compare the quenching behavior of the magnetic shielded core SCFCL with that of the series reactor prestented in chapter 4. Therefore the maximum limiting resistance is defined to be 8 Ω at the moment of the interruption of the circuit breaker. The complete source code written in FORTRAN is listed in Appendix A. The evolution of the resistance on the primary side (line side) of the magnetic shielded core is given in figure 5.15. 1 MODELS is the internal FORTRAN based programming language of ATP-EMTP 53 CHAPTER 6 Case Study Maasbracht 380 he construction of substation Maasbracht 380 was part of the first steps T towards the realization of the Dutch 380 kV transmission grid which has been put in operation between 1969 and 1970 [52]. Over time the substation expanded due to the construction of more and more incoming supplying lines and outgoing feeders. Its most recent expansion is the commissioning of three CHP units, CC-C 1-3 which account for 280 MW each. The construction of three more CHP’s, CC-D 1-3 is planned for 2014 [42]. The sum of six CHP’s are part of the modernization project at the “Claus centrale”, a Power plant which is owned by Essent NV, an electric utility provider in the Netherlands. In the near future it is foreseen that the substation will exceed its maximum short-circuit withstand levels, to overcome this problem buses A and B1 are planned to be split. In this way the fault current levels are reduced. This measure will be explained in more detail in sub-section 6.1. The preferable outlook for substation Maasbracht 380 is given in the form of an one-line diagram in figure 6.1. The diagram includes all supplying lines and outgoing feeders, the present and future fault current contributions are given in table 6.1. The short00 circuit withstand levels for the substation are known to be for Ik = 51kA and for ip = 125kA. However measures are taken to upgrade the short-circuit withstand 00 levels on a short notice to Ik = 63kA with a corresponding ip = 171kA. 6.1 Splitting the Substation Into Sub Grids The entire transmission system of TenneT is built according to the n−1 reliability criterion. This means that in each grid one component can fail without loss of supply since the remaining components are still able to transfer the power. In general this principle is referred to as redundancy and has the aim to increase reliability and availability. At substations redundancy is achieved by the 1 Due to environmental constraints at substation Maasbracht 380 the extension of bus bar B is renamed to C. However bus bar B and C can be seen as a whole. 55 Chapter 6 CC-C 1-3 CC-A Dodewaard Eindhoven KV 2 CC-D 1-3 KV 1 C B A CC-B TR401 Van Eyck Elia TR402 Selfkant Amprion TR404 TR403 150 kV Network MBT 150 Figure 6.1: Overview of substation Maasbracht 380 with possible location of (SC)FCL in coupling bay KV 1 CB A B Figure 6.2: Parallel bus bars coupled through bus-coupler circuit breakers Type Name Ik3 (kA) Total 00 Ik3 (kA) Ik1 (kA) Total 00 Ik1 (kA) CC-A 3.44 3.44 1.98 1.98 CC-C 1-3 1.61 4.83 0.89 2.67 CC-D 1-3 1.61 4.83 0.89 2.67 Lines (to) Eindhoven 7.15 14.3 5.40 10.80 Lines (to) Dodewaard 4.97 9.94 4.02 8.04 Lines (to) Selfkant 18.7 18.7 14.1 14.1 Lines (to) Van Eyck 9.6 9.6 7.9 7.9 Transformers Total MBT TR401-TR404 1.22 4.88 70.52 1.64 6.56 55.02 00 Generator Generators Generators 1 1 00 Effective from the year 2018. Table 6.1: Overview of the fault current contributions at MBT 380, calculated through the IEC60909 method 56 Case Study Maasbracht 380 CB 1 CB 4 CB 2 A´ A B´ B CB 3 Figure 6.3: Two bus bars sections longitudinal coupled through circuit breakers CB 2 and CB 3 coupling of two (or more) bus bars. An example is given in picture 6.2 where two parallel bus bars are connected through a bus-coupler circuit breaker. If, for example a short-circuit occurs at bus A, or in one of the supplying lines or outgoing feeders connected at that time to bus A, it is possible to exclude the faulting parts from the substation and subsequently transfer the unharmed phases to bus B. To decrease the fault current contribution at substation Maasbracht 380 it is possible to split the bus bars A and B as mentioned earlier. This can be done in two ways. The first possibility is best explained through figure 6.2 and is achieved by splitting the parallelly coupled bus bars. This results in bus bars A and B operating independently from each other. Assuming that supplying lines and outgoing feeders are equally distributed over buses A and B, the fault current levels are reduced with approximately 50%. According to table 6.1 this results in approximately 35 kA for a three-phase-to-ground fault and approximately 27.5 kA for a single-phase-to-ground fault. This is within todays electromechanical and thermal limits of substation Maasbracht 380. It is obvious that this measure can be effectuated immediately without additional efforts and costs. This is a great advantange, however serious drawbacks are present. With this measure the substation has lost its n − 1 reliability. Consequently this implies that if one bus bar is out of service due to maintenance, the short circuit withstand level on the remaining bus bar is exceeded. Therefore it is advised to implement this measure only on a temporary basis. The second method of substation splitting is based on the one-line diagram in picture 6.3 where two parallel bus bars can be longitudinal coupled through CB 2 and CB3. This way of “sectioning” reduces the short-circuit levels since there are less supplying lines and outgoing feeders connected to each section. The n − 1 reliability criterion is maintained and the option to join bus bars makes the substation more flexible. Sections can be separated if the short-circuit current contribution is too high or joined if one bus bar is out of service for example. One can think of many more scenarios where this flexibility comes to assistance. With respect to existing substations the drawbacks are clear; It demands the reallocation of supplying lines and outgoing feeders which is considered to be costly and results in unequally loaded buses. At last it has to be taken into account that when two energized sections are being joined by the bus-section circuit breakers, the phase angle and voltage difference between the sections has 57 Chapter 6 to be within predefined limits. Otherwise (too) large compensating currents will flow that may harm the power systems’ equipment. 6.2 EMT Model of Substation Maasbracht 380 Substation Maasbracht 380 has been modeled in more detail with regard to the capacitances associated with power system components, such as the bushings, CT’s, CVT’s and bus bars. These capacitances play an important role in the initial voltage rise of the TRV and have been estimated according to Annex B of C37.011 - Application Guide for Transient Recovery Voltage for AC HighVoltage Circuit Breakers [15]. The capacitances of the cables have been derived from the IEC 60909 informational database that has been provided by the Asset Management department. The remaining two fault current limiting measures in this thesis, being the series reactor and the magnetic shielded core SCFCL will be studied in the following sections. Both FCL’s are placed in coupling bay KV 1 of substation Maasbracht 380, aiming on reaching a maximum efficacy of the limiter. It is assumed that supplying lines and outgoing feeders are equally distributed over the substation. It is important to note that all subsequent transient switching studies are carried out with all power system components energized to the maximum system voltage. Meaning the 380 kV system is energized up to 420 kV, or approximately 1.1 p.u. voltage. In this way the largest possible short-circuit current is being initiated. The circuit breakers are configured in such a way that the full bus bar is cleared when a fault occurs at substation Maasbracht 380. Meaning that every supplying line and outgoing feeder is disconnected from the faulting bus bar when a short-circuit occurs. It is assumed that the circuit breakers act within two periods, which equals 40 milliseconds in a 50 Hz power system. The time between the instant of the fault and the short-circuit interruption is set to be short, representing the worst case scenario for the circuit breaker. 6.3 6.3.1 EMT Study Series reactor Results To initiate a starting point of this EMT study, a three-phase bolted line-toground fault has been initiated at bus bar A of substation Maasbracht 380. The resulting fault current is shown in figure 6.4, with ip = 171 kA and I” k = 68.4 kA. After adding the series reactor of 8 Ω in the coupling bay, the threephase-to-ground fault current is limited to a value of ip = 141 kA and I” k = 62.4 kA. These results are within the electromechanical and thermal limits of substation Maasbracht 380. Figure 6.5 illustrates the limited fault current. The instantaneous change of the fault current to 0 A at t = 0.1 seconds is the result of the switching action by the circuit breaker and is set on purpose to evaluate the TRV. The circuit breaker opens and the current is interrupted at current-zero. The current of I” k = 16.9 kA through the series reactor and associated circuit breaker in the coupling bay suits the IEC T30 test duty criteria, the waveforms are given in figure 6.6. In figure 6.7 the full three-phase TRV’s are depicted, 58 Case Study Maasbracht 380 ×105 2 Three Phase fault current Phase a Phase b Phase c 1.5 Current [A] 1 0.5 0 −0.5 −1 −1.5 −2 0 0.05 0.1 0.15 0.2 Time [s] Figure 6.4: Three-phase-to-ground fault current where in figure 6.8 the magnified function of the TRV is given. Unfortunately the TRV exceeds the 420 kV and 550 kV IEC T30 envelopes of the circuit breaker. The TRV plots of the remaining phases are given in Appendix D Resulting Plots TRV Study. It can be concluded that the implementation of a 550 kV circuit breaker in place of a 420 kV circuit breaker does not make sense since the initial dielectric strength of both breakers is the same. In the next sub-section 6.3.2, measures are presented to reduce the rate-of-rise-of-recovery voltage (RRRV). 6.3.2 Insertion of Damping Capacitors A convenient solution to suppress the RRRV would be the insertion of damping capacitors close to the series reactor, as stated in references [15, 17]. The damping capacitors can be implemented as being Y-connected capacitances or as a series-connected capacitances across the reactor. At substation Maasbracht 380 the approach of the Y-connected capacitance has been chosen since this option is most favorable with regard to practical aspects. By gradually increasing the value of the capacitor a satisfactory result for the RRRV was obtained. The result of the damped TRV is given in figure 6.9. Depending on the type of capacitor (polypropylene or oil-impregnated paper) the capacity may vary between 0.055 uF and 0.065 uF. The TRV plots of the remaining phases are given in Appendix D Resulting Plots TRV Study. 59 Chapter 6 ×105 2 Three Phase fault current Phase a Phase b Phase c 1.5 Current [A] 1 0.5 0 −0.5 −1 −1.5 −2 0 0.05 0.1 0.15 0.2 Time [s] Figure 6.5: Limited three-phase-to-ground fault current ×104 5 Three Phase fault current Phase a Phase b Phase c 4 3 Current [A] 2 1 0 −1 −2 −3 −4 −5 0 0.05 0.1 0.15 0.2 Time [s] Figure 6.6: Three-phase fault current through the circuit breaker and series reactor in the coupling bay 60 Case Study Maasbracht 380 Transient Recovery Voltage ×105 5 4 3 Voltage [V] 2 1 0 −1 −2 Phase a Phase b Phase c −3 −4 −5 0.08 0.09 0.1 0.11 0.12 0.13 0.14 Time [s] Figure 6.7: Three-phase transient recovery voltage Transient Recovery Voltage ×105 9 8 550 Phase c 7 420 Voltage [V] 6 5 4 3 2 1 0 0.0944 0.0945 0.0946 0.0947 0.0948 0.0949 0.095 Time [s] Figure 6.8: Undamped TRV with T30 capability envelope for 420 kV and 550 kV breaker, phase c 61 Chapter 6 Transient Recovery Voltage ×105 9 550 Phase c 8 7 420 Voltage [V] 6 5 4 3 2 1 0 0.0944 0.0945 0.0946 0.0947 0.0948 0.0949 0.095 Time [s] Figure 6.9: Damped TRV with T30 capability envelope for 420 kV and 550 kV breaker, phase c 6.4 6.4.1 EMT Study Magnetic Shielded Core SCFCL Results The current limiting behavior of the magnetic shielded iron core is of a resistive type and was discussed in subsection 5.4.2 ATP-EMTP Model of the Magnetic Shielded Core SCFCL. The quenching behavior is given in picture 6.10, the three-phase-to-ground fault current is limited to value of ip = 130 kA and I” k = 61.4 kA. These results are within the electromechanical and thermal limits of substation Maasbracht. Again the current is interrupted at t = 0.1 seconds, to evaluate the TRV. The current and TRV fall within IEC test duty T30 as is depicted in figure 6.11 and 6.12. It can be concluded that no additional measures are needed to control the RRRV. Accordingly there is no need for upgrading the circuit breaker. The TRV plots of the remaining phases are given in Appendix D Resulting Plots TRV Study. 62 Case Study Maasbracht 380 ×105 2 Three Phase fault current Phase a Phase b Phase c 1.5 Current [A] 1 0.5 0 −0.5 −1 −1.5 −2 0 0.05 0.1 0.15 0.2 Time [s] Figure 6.10: Limited three-phase-to-ground fault current ×104 5 Three Phase fault current Phase a Phase b Phase c 4 3 Current [A] 2 1 0 −1 −2 −3 −4 −5 0 0.05 0.1 0.15 0.2 Time [s] Figure 6.11: Three-phase fault current through the circuit breaker and magnetic shielded core SCFCL in the coupling bay 63 Chapter 6 Transient Recovery Voltage ×105 0 −1 −2 Voltage [V] −3 −4 −5 −6 420 −7 −8 550 Phase a −9 0.0863 0.0864 0.0865 0.0866 0.0867 0.0868 0.0869 Time [s] Figure 6.12: TRV with T30 capability envelope for 420 kV and 550 kV breaker, phase a 64 CHAPTER 7 Conclusion and Recommendations 7.1 Conclusion When analyzing power system short-circuit current reduction measures it is evident to rely on close-to-reality grid models. Two independently operating EMT grid models were established in ATP-EMTP and DIgSILENT PowerFactory. Both models were validated to each other, by comparing dynamical short-circuit currents, and with respect to the initial symmetrical short-circuit currents computed through the IEC 60909 model provided by the Asset Management department of TenneT. The identified deviations of 2-8% were within the expected margins that these models will have to the real network. Three different short-circuit current reduction methods were considered. At first the air-core reactor and oil-immersed reactor were examined. From the perspective of magnetic fields, noise, footprint and robustness the oil-immersed series reactor is the preferred topology to limit fault currents in the transmission network. An EMT model based upon practical parameters confirmed the successful quench of the short-circuit current. However special measures were required to control the RRRV. Additional drawbacks are size and electrical losses which may account up to 1.2 MW for an 8 Ω, 400 kV oil-immersed series reactor. The second measure has the specific interest of many system operators thanks to its desirable electrical characteristics: the SCFCL. At present several pilots are in progress and numerous have been successfully completed, however no SCFCL has become commercially viable yet. The most promising topologies have been investigated and led to the EMT model of a magnetic shielded core SCFCL. Simulations demonstrated a successful quench and in comparison to the series reactor no additional measures were required to reduce the RRRV. Finally several methods of substation splitting were investigated. To increase the fault current withstand levels on the short term, splitting two parallel coupled bus bars is justified. However for the long term this imposes a serious threat to the reliability of the power system as it violates the n − 1 reliability 65 Chapter 7 criterion. To overcome this limitation it is possible to separate the substation into a number of sections. In this way fault levels are reduced while a redundant substation is maintained. A severe drawback of “sectioning” is the reallocation of supplying lines and outgoing feeders which is very expensive. With respect to substation Maasbracht 380 all three measures are advisable. Whether to implement a series reactor or SCFCL in the coupling bay mainly depends on the question if TenneT wants to invest in a innovative pilot or rather sticks to a concept which have been proven over years. In any case it has to be noted that if one of the bus bars is out of service the remaining bus bar could still exceed its fault current withstand level. To address this limitation substation Maasbracht 380 has to be separated into subsections or FCL’s can be placed in supplying lines and / or outgoing feeders. 7.2 Recommendations for Future Work This section covers the recommendations for future work and are listed in order of preference. Implementation of a real time short-circuit calculation system: this is the first suggestion to the transmission network of TenneT. At present most fault current studies and operational decisions at TenneT are based on worst case scenarios. By knowing the actual fault current contribution, the operation of a more reliable and (cost) efficient transmission network would be in reach. At substation Maasbracht 380 such a system could make the difference between upgrading in the near future or leaving the substation unchanged at present. Economic feasibility study on the fault current limiting measures presented in this thesis: three fault current limiting measures were investigated in this thesis, however the main focus was on the electrical characteristics while the economical consequences also play an important role in the decision making process. How do operating costs relate to the investment costs of the presented measures for example? Especially the SCFCL would be of interest for a subsequent study since its relies on a cryogenic system that may account for additional operating costs. Collaborations between neighboring TSO’s with respect to the exchange of short-circuit calculation parameters; during the modeling stage of this thesis it became clear that only a limited amount of information was available regarding the interconnections with neighboring TSO’s. R/X ratios were estimated and transmission lines have been omitted. However these simplifications could significantly differ from reality. For example this means that the accuracy of the simulated short-circuit current peak values and the correctness of grounding conditions of the power system could deviate substantially. The author suggests the establishment of collaborations between neighboring TSO’s with respect to the exchange of short-circuit calculation parameters. 66 Bibliography [1] Synchronous generator. Technical report, DIgSILENT Technical Documentation, 2010. [2] Kwaliteits- en Capaciteitsdocument. TenneT TSO, Utrechtseweg 310, 6812 AR Arnhem, 2011. [3] Vision2030. Utrechtseweg 310, 6812 AR Arnhem, 2011. [4] IEC Standard 60071:2004. Part 4: Computational guide to insulation coordination and modelling of electrical networks. Insulation co-ordination, 2004. [5] IEC Standard 60909-0:2001. Part 0: short-circuit currents in three-phase a.c. systems. Calculation of currents, 2001. [6] IEC Standard 62271:2008. Part 100: Alternating current circuit-breakers. High-voltage switchgear and controlgear, 2008. [7] Y. Seong Eun A. Min Cheol, P. Dong Keun and e. al. Recovery characteristics of resistive sfcl wound with ybco coated conductor in a power system. IEEE Transactions on Applied Superconductivity, 17(2):1859–1862, 2007. [8] T. Arndt. Iea exco meeting fall 2011. Siemens AG, Corporate Technology, Erlangen, Germany, 2011. [9] T. C. Bartram. B. P. Raju, K. C. Parton. A current limiting device using superconducting d.c. bias applications and prospects. IEEE Transactions on Power Apparatus and Systems, 101(9):3173–3177, 1982. [10] L. Bergeron. Du coup de belier en hydraulique au coup de foudre en electricite (english translation: “water hammer in hydraulics and wave surges in electricity”). ASME Committee, 1961. [11] K. H. J. Buschow. The encyclopedia of materials science and technology. 2001. 67 [12] TenneT TSO BV. South-west 380 kv, 2012. zuid-west380kv.nl/. URL http://www. [13] IEEE Standard C37.011-2005. Ieee application guide for transient recovery voltage for ac high-voltage circuit breakers. Switchgear Committee IEEE Power Engineering Society, 2005. [14] A. M. Cassie. Arc rupture and circuit severity: A new theory. Technical Report 102, CIGRE, 1939. [15] Switchgear Committee. C37.011 - application guide for transient recovery voltage for ac high-voltage circuit breakers. Technical report, IEEE, 2006. [16] D. Cvoric. Novel Topology of Saturated-core Fault Current Limiter. PhD thesis, Technische Universiteit Delft, 2010. [17] J. P. Taisne D. Robert, F. Martin. Insertion of current limiting or load sharing reactors in a substation. impact on the specifications. In CIGRE 44 Bruges, 2007. [18] H. Dersch. Inductive current limitation device for an alternating current using the superconductivity superconductor. European Patent Specification 0353449, 1990. [19] H. W. Dommel. Electromagnetic Transient Program (EMTP) Theory Book. Bonneville Power Administration, Portland Oregon 97208-3621, 1994. [20] F. Fernández. Two-winding transformer (3-phase). Technical report, DIgSILENT Technical Documentation, 2010. [21] C.L. Fortescue. Method of symmetrical coordinates applied to the solution of polyphase networks. AIEE Transactions, 37(2):1027–1140, 1918. [22] M. Inzerillo G. Ala. An improved circuit-breaker model in models language for atp-emtp code. In International Conference on Power System Transients, 1999. [23] M. Popov G. Preston and e. al. A new elongation function for modelling long arcs in open air. In International Conference on Power System Transients, 2011. [24] A. Greenwood. Electrical Transients in Power Systems. John Wiley and Sons, Inc., 111 River street, Hoboken NJ 07030, 1991. [25] M. Fukutomi H. Maeda, Y. Tanaka and e. al. A new high-tc oxide superconductor without a rare earth element. Japanese Journal of Applied Physics, 27, 1988. [26] J. H. Harlow. Electric Power transformer engineering. CRC Press, 2 edition, 2007. [27] C.S. Engelbrecht I. Tannemaat. Supplemental transient studies for 380 kv oil immersed series reactors in the connection maasvlakte - westerlee. Technical report, KEMA, 2009. 68 [28] W. Stevenson J. Grainger, Jr. Power System Analysis. McGraw-Hill, Inc., 148 Princeton-Hightstown Road, Hightstown, NJ 08520-1901, 1994. [29] S. S. Kalsi. Applications of High Temperature Superconductors to Electric Power Equipment. John Wiley and Sons, Inc., 111 River street, Hoboken NJ 07030, 2011. [30] M. Kizilcay. Alternative transients program, 2012. URL http://www. emtp.org/. [31] P. Kundur. Power System Stability and Control. McGraw-Hill, Inc., 1221 Avenue of Th Americas, New York 10020, 1994. [32] M. Lakner M. Chen, W. Paul and e. al. 6.4 mva resitive fault current limiter based on bi-2212 superconductor. Physica C, (372-376):1657–1663, 2002. [33] K. Koyamaand M. Endo, T. Hori and e. al. Operating characteristic of superconducting fault current limiter using 24 kv vacuum interrupter driven by electromagnetic repulsion. Electric Power Applications, IET, July:363– 370, 2009. [34] C. J. Torng M. K. Wu, J. R. Ashburn. Superconductivity at 93k in a new mixed-phase ybco compound system at ambient pressure. 1987. [35] M. Steurer M. Noe. High-temperature superconductor fault current limiters: concepts, applications, and development status. Superconductors Science and Technology, 20:R15–R29, 2007. [36] J. R. Marti. Accurate modelling of frequency-dependant transmission line in electromagnetic transient simulations. IEEE Transactions on Power Apparatus and Systems, pages 147–57, 1982. [37] O. Mayr. Beitraege zur theorie des statischen und dynamischen lichtbogens. Archiv f´’ur Elektrotechnik, 37(12):588–608, 1943. [38] W. P. Robbins N. Mohan, T. M. Undeland. Power Electronics, Converters, Applications and Design, Third Edition. John Wiley and Sons, Inc., 111 River street, Hoboken NJ 07030, 2003. [39] J. Arrillaga N. Watson. Power System Electromagnetic Transient Simulation. The institute of Engineering and Technology, London, United Kingdom, 2007. [40] NEMA. Motors and Generators, Part 22, NEMA MG 1-1987. National Electrical Manufacturers Association, Rosslyn, VA, 1987. [41] NMa. Energiewetten, 2012. URL http://www.nma.nl/wet__en_ regelgeving/energiewetten/default.aspx. [42] Essent NV. Modernisering clauscentrale, June 2012. URL http: //www.essent.nl/content/overessent/actueel/werkinuitvoering/ modernisering_clauscentrale/index.html. [43] H. K. Onnes. The superconductivity of mercury. Comm. Phys. Lab. Univ. Leiden, No’s. 122 and 124, 1911. 69 [44] J. Leveque V. D. Pham P. Tixador, Y. Brunet. Hybrid superconducting a.c. fault current limiter principle and previous studies. IEEE Transactions on Magnetics, 28(1):446–449, 1992. [45] M. Popov. Switching three-phase distribution transformers with a vacuum circuit breaker: Analysis of overvoltages and the protection of the equipment. PhD thesis, Technische Universiteit Delft, 2002. [46] Y. Tada R. Tanabe. A practical time-domain fault current analysis using emtp. In 16th PSCC, Glasgow, Scotland, July 14-18, 2008. [47] R. Kirkland Smith R. William Long. Are all circuit breakers created equal? certainly not when it comes to generator circuits! Technical report, EATON, 2003. [48] A.G.A. Lathouwers R.P.P. Smeets. The testing of t&d circuit breakers having extreme current / voltage ratings. In AESIEAP 2009 CEO, 2009. [49] J. Stewart. Calculus: Early Transcendentals. Brooks/Cole, Cengage Learning, 20 Davis Drive Belmont, CA 94002-3098, 7 edition, 2012. [50] K. Udagawa T. Koshizuka, T. Shinkai and e. al. Circuit breaker model using serially connected 3 arc models for emtp simulation. In International Conference on Power System Transients, 2009. [51] L. van der Sluis. Transients in Power Systems. John Wiley and Sons, Inc., 111 River street, Hoboken NJ 07030, 2001. [52] A.W. van Hamel. 380 kv-stations van het nederlandse 380 kv-koppelnet. ELEKTROTECHNIEK, 50(7):285, 1972. [53] P. van Oirsouw. Netten voor de distributie van elektriciteit. Phase to Phase B.V., Postbus 100, 6800 AC Arnhem, 2011. [54] Johnson W. Hassenzahl, D. W. Hazelton and e. al. Electric power applications of superconductivity. Proceedings IEEE, 92(1):16551673, 2004. [55] J. Rhyner W. Paul, Th. Baumann. Test of 100 kw high-tc superconducting fault current limiter. IEEE Transactions on applied superconductivity, vol. 5, 2, june, 1995. [56] H P. W. Schmidt, B. Gamble and e. al. Design and test of current limiting modules using ybco-coated conductors. Superconductor Science and Technology, 23(1):014024, 2010. [57] B. K. Johnson W. V. Hassenzahl, D. W. Hazelton and e. al. Electric power applications of superconductivity. Proceedings of the IEEE, 92(10):1655– 1674, 2004. [58] B. K. Johnson W. V. Hassenzahl, D. W. Hazelton and e. al. Curl 10: development and field-test of a 10 kv/10 mva resistive current limiter based on bulk mcpbscco 2212. IEEE Transactions on Applied Superconductivity, 15(2):1955–1960, 2005. 70 BIBLIOGRAPHY [59] A.M. Wolsky. Fault current limiters: Some recent developments, santa fe, new mexico. In IEA Implementing Agreement for a Co-Operative Programme for Assessing the Impacts of High-Temperature Superconductivity on the Electric Power Sector - 16-18 May, 2011. [60] A. Jun Z. Yuji. Discovery of the new superconductor mgb2 and its recent development. 2001. 71 APPENDIX A Source Code ATP-EMTP MODELS Block Set 73 APPENDIX B Overview of SCFCL Projects 75 Appendix B RSE, A2A RSE, A2A factory in Japan, 2008 project stopped San Dionigi, Italy Q4, 2011, Q3 2012 CESI PowerLab Milano, Italy January, 2011 Italy / 2005 Test location and date(s) Resistive Resistive Resistive Resistive Resistive Type 3-phase 3-phase 3-phase 1-phase 3-phase 3-phase Phase 11 kV, 0.1 kA, 1.9 MVA 10 kV, 0.6 kA, 10 MVA 10 kV, 0.4 kA, 7 MVA 6.6 kV, 0.6 kA, 6.9 MVA 9.0 kV, 1 kA, 15.6 MVA 9.0 kV, 0.22 kA, 3.9 MVA 3.2 kV, 0.22 kA, 1.2 MVA Unfaulted line rating Bi2212 Melt cast bifilar coil, LN2 Bi2212 Melt cast bifilar coil, @73 K, LN2 Bi2212 Melt cast bifilar coil, @66 K, LN2 REBaCuO tape, LN2 REBaCuO tape, LN2 Bi2223 tape, LN2 Bi2223 tape, LN2 Bi2223 tape, LN2 Superconductor Table B.1: Table containing recent SCFCL projects [59] Toshiba, Fujikura Shanghai ss TBD 2012 Resistive 3-phase 11 kV Participants Gan-Shan Shanghai, Shanghai Jaioting University Netphen ss, Netphen, DE, April 2004 - April 2005 Resistive 3-phase (now Nexans Superconductors, RWE BamberBridge ss, Preston, UK, October, 2009 March 2010 Resistive RICERCA Nexans Superconductors, Electricity Northwest, ASL Liverpool, UK, Q2 2011 CESI RSE) Nexans Superconductors, Scottish Power, ASL 76 Resistive Icheon ss Korea, Q1 2011 Factory Project 2011 Central Networks East, Rolls-Royce, HyperTech, E.ON, ASL, ETI KEPRI, KEPCO, LSIS KEPRI, KEPCO, LSIS Korea, March, Resistive Loughborough, Leicestershire, UK, 2012-2014 Nexans France and 14 other participants all in ECCOFLOW test, ended Resistive PowerLab test in Milano June 2012 / ENDESAs ss bus-tie on Majorca Spain followed up by a ss (LV power transformer) in Kosice, Slovakia, Q3 2012 Dec 2013 Resistive Resistive Boxberg Station, Cottbus, DE, September, 2009 31 December 2011 Nexans Superconductors, Vattenfall Ag, KIT, BTU, University of Dortmund Resistive Boxberg Station, Cottbus, DE Nexans Superconductors, Vattenfall Ag, BTU 3-phase 3-phase 3-phase 3-phase 3-phase 3-phase 22.9 kV, 0.630 kA 22.9 kV, 0.630 kA 11 kV, 1.25 kA, 24 MVA 24 kV, 1.0 kA, 41.6 MVA 11 kV, 0.8 kA, 15 MVA 11 kV, 0.8 kA, 15 MVA Bi2223 tape 344S, LN2 3 Bar, He @76 K Bi2223 tape 344S, LN2 3 Bar, He @76 K MgB2 wire REBaCuO tape, LN2 REBaCuO tape, LN2 Bi2212 Melt cast bifilar coil, @65 K, LN2 Overview of SCFCL Projects 77 Appendix B Krzhizhanovsky Power Engineering Institute, Lebedev Physical Institute Zenergy, CE Electric, ASL Zenergy, CE Electric, ASL Zenergy, SoCalEd EDF Energy Networks, E.ON, GridOn, Wilson Transformer Innopower, Southern Power Lab scale test, Moscow, Russia, 2010 T.b.a., UK, 2012 Scunthorpe, UK, Q2Q3 2011 Shandin Substation, San Bernadino, California, USA, November, 2009 October 2010 NewHaven Substation, East Sussex, UK, 2012-2014 Puji ss, southwest China, 2007 Resistive (shielded core) Saturated core Saturated core Saturated core Saturated core Saturated core 1-phase 3-phase 3-phase 3-phase 3-phase 3-phase 0.001 kV, 0.002 kA 33 kV, 1.25 kA, 72 MVA 11 kV, 1.25 kA, 26 MVA 12 kV, 1.2 kA, 25 MVA 11 kV, 0.8 kA, 15 MVA 35 kV, 1.5 kA, 90 MVA REBaCuO Bi2223 tape, @30 K, conduction cooled Bi2223 tape, @20 K, conduction cooled Bi2223 tape, @68 K, LN2 boil-off recondense T.b.d. Bi2223 tape, LN2 deliver, store, boil-off 78 Saturated core Saturated core Shigezhuang ss, Tianjin, China, Q4 2011 Steubencville, USA, 2012 Zenergy, AEP Ohio, Resistive InnoPower BC, PowerTech, Canada, Q2 2011 Resistive Shielded core Siemens, Nexans, AMSC Netphen, Augsberg, Bavaria, DE Q3 2012 to Q3 2013 Netphen ss, DE Bruker, Augsberg ENSYSTROB, RWE, Nexans (Hurth), KIT Areva, Stadtwerke, Energie 3-phase 3-phase 1-phase 1-phase 1-phase 138 kV, 1.3 kA, 310 MVA 220 kV, 0.75 kA, 280 MVA 115 kV, 1.2 kA 110 kV, 1.85 kA 6.4 kV, 2 kA, 22 MVA Bi2223, conduction cooled, @20-30 K Bi2223 tape, LN2 deliver, store, boil-off REBaCuO tape, LN2 Bi2212 Melt Cast Tubes Monofilar, LN2 REBaCuO LN2 Overview of SCFCL Projects 79 APPENDIX C Overview of the EMT Grid Models 81 GT-MDK380 W Krk-XZA_BS11 grs L380/B0.1 L380/B0.0 XZA_BS11 GT-MDK380 Z MDK-KRK380 Z Krk-XZA_BS11 wit MDK-KRK380 W 0 ~ G BSL150/BB1 BSL150/BB2 Wind op Zee BSL 0 ~ G Sloe20 Sloe10 KRK-BSL380 GS XZA_GT11 TR Sloe20 GT150/A Bsl Tr401 AC Voltag.. V ~ 11 Tr-A8 3 GT150/B V ~ TBG380/B TBG380/A 1 BSL-TBG380 Z BSL-TBG380 W AC Voltag.. 11 Gtb-LC401 11 ~ G Kerncentrale BSL 1 Gtb-LC402 Tr kerncentrale BSL MDK380/B TR Sloe10 11 EHV380/A EHV380/B EHVO15/A EHVO15/B GT-TBG380 G GT-TBG380 Z TBN150/A TBN150/B 11 11 11 AC Voltag.. V ~ TBG TR2 11 11 AC Voltag.. V ~ Ehv Tr401 Ehv Tr402 Ehv Tr403 Ehv Tr404 11 TBG TR1 V ~ G ~ CCC5 G ~ CCC6 CCC4 G ~ 0 1 Dod-Co1 AC Voltag.. DOD380/B DOD380/A BMR150/BOXM MBT380/A MBT380/B Z W LGK150/BB2 LGK150/BB1 Tr-CCC6 Gt-Tr402 Gt-Tr401 Tr-CCC5 MDK380/A KRK-BSL380 Z Bsl Tr402 Bmr Tr404 Tr-CCC4 11 MBT150/A MBT150/B BMRT/BB1 BMRT/BB2 11 KIJ-GT380 Z TBG-EHV380 G V ~ 0 Dtc-LC403 AC Voltag.. Dtc-LC402 11 Dtc Tr402 Mbt Tr402 11 BMR-DOD Z Dtc Tr403 MBT-BMR W DTC380/B DTC380/A MBT-BMR Z V ~ BMR-DOD W V ~ AC Voltag.. Mbt Tr401 DOD150/B 11 Dod-LC402 Dod-Dtc wt DOD150/A Dtc-Hgl zw Dod-Dtc zt 0 12 Dod Tr402 Dtc-Hgl wt 0 11 12 Mbt Tr403 Mbt Tr404 11 AC Voltag.. V ~ HGLO11/BB1 HGLO11/BB2 Dod Tr403 Dod-LC403 V ~ TR CC-B 12 V ~ AC Voltag..AC Voltag.. V ~ ~ G CCA V ~ 13 Hgl Tr403 AC Voltag.. 13 Hgl Tr401 Dod Tr404 AC Voltag.. 3 AC Voltag.. Tr-CCA GTB380/B GTB380/A ~ G ~ G CCC1 13 ~ G CCC2 Hgl Tr402 Tr-CCC1 A8 G ~ HGL380/B HGL380/A Tr-CCC2 82 CC-B KIJ380/B KIJ380/A ~ G CCC3 MBT380.. Appendix C Figure C.1: A overview showing the TenneT 380 kV network modelled in PowerFactory DIgSILENT Tr-CCC3 TBG-EHV380 Z GT-TBG380 W KIJ-GT380 W TBG-EHV380 W Overview of the EMT Grid Models Figure C.2: A overview showing the TenneT 380 kV network modelled in ATPEMTP 83 APPENDIX D Resulting Plots TRV Study D.1 Series Reactor 85 Appendix D Transient Recovery Voltage ×105 9 8 550 Phase a 7 420 Voltage [V] 6 5 4 3 2 1 0 0.0995 0.0996 0.0997 0.0998 0.0999 0.1 0.1001 Time [s] Figure D.1: Undamped TRV with T30 capability envelope for 420 kV and 550 kV breaker, phase a Transient Recovery Voltage ×105 0 −1 −2 Voltage [V] −3 −4 −5 −6 420 −7 −8 550 Phase b −9 0.0982 0.0983 0.0984 0.0985 0.0986 0.0987 0.0988 Time [s] Figure D.2: Undamped TRV with T30 capability envelope for 420 kV and 550 kV breaker, phase b 86 Resulting Plots TRV Study Transient Recovery Voltage ×105 9 8 550 Phase a 7 420 Voltage [V] 6 5 4 3 2 1 0 0.0995 0.0996 0.0997 0.0998 0.0999 0.1 0.1001 Time [s] Figure D.3: Damped TRV with T30 capability envelope for 420 kV and 550 kV breaker, phase a Transient Recovery Voltage ×105 0 −1 −2 Voltage [V] −3 −4 −5 −6 420 −7 −8 550 Phase b −9 0.0982 0.0983 0.0984 0.0985 0.0986 0.0987 0.0988 Time [s] Figure D.4: Damped TRV with T30 capability envelope for 420 kV and 550 kV breaker, phase b 87 Appendix D D.2 88 Magnetic Shielded Core SCFCL Resulting Plots TRV Study Transient Recovery Voltage ×105 0 −1 −2 Voltage [V] −3 −4 −5 −6 420 −7 −8 550 Phase b −9 0.0928 0.0929 0.093 0.0931 0.0932 0.0933 0.0934 Time [s] Figure D.5: TRV with T30 capability envelope for 420 kV and 550 kV breaker, phase b Transient Recovery Voltage ×105 9 8 550 Phase c 7 420 Voltage [V] 6 5 4 3 2 1 0 0.0898 0.0899 0.09 0.0901 0.0902 0.0903 0.0904 Time [s] Figure D.6: TRV with T30 capability envelope for 420 kV and 550 kV breaker, phase c 89 APPENDIX E Grid Parameters 91 Table E.1: Generator parameters xq p.u. 0,31 0,355 0,355 0,3 0,3 0,3 0,3 0,3 0,3 0,3 0,3 0,3 xd p.u. 0,22 0,242 0,242 0,1746 0,1746 0,1746 0,1746 0,1746 0,1746 0,2 0,2 0,2 xd p.u. 0,3 0,5 0,5 0,3 0,3 0,3 0,3 0,3 0,3 0,3 0,3 0,3 xq p.u. 0,22 0,242 0,242 0,2 0,2 0,2 0,2 0,2 0,2 0,2 0,2 0,2 xq p.u. 0,889462 1,74413 1,74413 1 1 1 1 1 1 1 1 1 Td s 0,029806 0,034085 0,034085 0,04365 0,04365 0,04365 0,04365 0,04365 0,04365 0,05 0,05 0,05 Td s 0,057831 0,115942 0,115886 1 1 1 1 1 1 1 1 1 Tq s 0,1012 0,06776 0,06776 0,05 0,05 0,05 0,05 0,05 0,05 0,05 0,05 0,05 Tq s 00 xd p.u. 2,49 2,07 2,071 2 2 2 2 2 2 2 2 2 0 xrl p.u. 2,6 2,3 2,3 2 2 2 2 2 2 2 2 2 00 xl p.u. 0 0 0 0 0 0 0 0 0 0 0 0 0 rstr p.u. 0,18 0,18 0,1 0,1 0,1 0,1 0,1 0,1 0,1 0,1 0,1 0,1 00 Pow.Fact. 0,001 0,00011 0,00011 0,001 0,001 0,001 0,001 0,001 0,001 0,001 0,09 0,09 0 App.Pow. MVA 0,8 0,78 0,78 0,8 0,8 0,8 0,8 0,8 0,8 0,8 0,85 0,85 00 Name 775 770 770 343 343 343 343 343 343 3125 524 524 0 A8 CC-B CC-A CCC1 CCC2 CCC3 CCD1 CCD2 CCD3 BSL Sloe10 Sloe20 92 93 HV-rtd.Pow. MVA 500 500 500 500 500 450 450 450 500 500 450 450 450 450 450 350 350 350 450 450 450 500 500 500 Name Bmr Tr404 Bsl Tr401 Bsl Tr402 Bsl Tr403 Dod Tr402 Dod Tr403 Dod Tr404 Dtc Tr402 Dtc Tr403 Ehv Tr401 Ehv Tr402 Ehv Tr403 Ehv Tr404 Gt-Tr401 Gt-Tr402 Hgl Tr401 Hgl Tr402 Hgl Tr403 Mbt Tr401 Mbt Tr402 Mbt Tr403 Mbt Tr404 TBG TR1 TBG TR2 500 500 500 500 500 450 450 450 500 500 450 450 450 450 450 350 350 350 450 450 450 500 500 500 MV-rtd.Pow. MVA 167 167 167 167 167 150 150 150 167 167 150 150 150 150 150 115 115 115 150 150 150 167 167 167 LV-rtd.Pow. MVA 380 380 380 380 380 380 380 380 380 380 380 380 380 380 380 381 381 381 380 380 380 380 380 380 HV-rtd.Volt. kV 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 117 117 117 150 150 150 150 150 150 MV-rtd.Volt. kV Table E.2: Transformer parameters 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 10 10 10 50 50 50 50 50 50 LV-rtd.Volt. kV 20,5 20,5 20,5 20,5 20,5 18 18,2 18,2 20,5 20,5 18,2 18 18 18 18 16,1 16,1 16,1 18 18 18,2 20,5 20,5 20,5 HV-MV-Shc.Volt. % 5,8 5,8 5,8 5,8 5,8 5,7 5,8 5,8 5,8 5,8 5,8 5,7 5,7 5,7 5,7 6,74 6,74 6,74 5,7 5,7 5,8 5,8 5,8 5,8 MV-LV-Shc.Volt. % Name 13,7 13,7 13,7 13,7 13,7 12,4 12,7 12,7 13,7 13,7 12,7 12,4 12,4 12,4 12,4 8,4 8,4 8,4 12,4 12,4 12,7 13,7 13,7 13,7 LV-HV Shc.Volt. % 1140 1140 1140 1140 1140 1540 1250 1250 1140 1140 1250 1540 1540 1540 1540 630 630 630 1540 1540 1250 1140 1140 1140 HV-MV Cop.Los. kW 235 235 235 235 235 290 255 255 235 235 255 290 290 290 290 153 153 153 290 290 255 235 235 235 MV-LV Cop.Los. kW 260 260 260 260 260 360 270 270 260 260 270 360 360 360 360 177 177 177 360 360 270 260 260 260 LV-HV Cop.Los. kW YN YN YN YN YN YN YN YN YN YN YN YN YN YN YN YN YN YN YN YN YN YN YN YN HV-Vec.Grp. 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 HV-Ph.Shift *30deg YN YN YN YN YN YN YN YN YN YN YN YN YN YN YN YN YN YN YN YN YN YN YN YN MV-Vec.Grp. 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 2 2 0 0 0 0 0 0 MV-Ph.Shift *30deg Table E.3: Transformer parameters, continued Bmr Tr404 Bsl Tr401 Bsl Tr402 Bsl Tr403 Dod Tr402 Dod Tr403 Dod Tr404 Dtc Tr402 Dtc Tr403 Ehv Tr401 Ehv Tr402 Ehv Tr403 Ehv Tr404 Gt-Tr401 Gt-Tr402 Hgl Tr401 Hgl Tr402 Hgl Tr403 Mbt Tr401 Mbt Tr402 Mbt Tr403 Mbt Tr404 TBG TR1 TBG TR2 94 95 Length km 41,7 41,7 120 120 45,4 45,4 58,65 58,65 51 51 19 19 23 23 23 57,9 57,9 41,4 41,4 40,9 40,9 40,9 Name BMR-DOD W BMR-DOD Z BSL-TBG380 W BSL-TBG380 Z Dod-Dtc wt Dod-Dtc zt Dtc-Hgl wt Dtc-Hgl zw EHV-MBT W EHV-MBT Z GT-MDK380 W GT-MDK380 Z GT-TBG380 G GT-TBG380 W GT-TBG380 Z MBT-BMR W MBT-BMR Z MDK-KRK380 W MDK-KRK380 Z TBG-EHV380 G TBG-EHV380 W TBG-EHV380 Z 0,969704 0,970228 1,776 1,776 1,155497 1,155497 1,491021 1,491021 1,191047 1,191047 0,478929 0,478929 0,539353 0,539353 0,529098 1,346384 1,346384 1,04356 1,04356 0,959111 0,959111 0,940874 R1 Ω 11,42179 11,42121 27,84 27,84 12,37199 12,37199 16,04022 16,04022 13,96164 13,96164 5,25375 5,25375 6,849686 6,849686 6,848017 15,85909 15,85909 11,44765 11,44765 12,18053 12,18053 12,17756 X1 Ω 0,546171 0,546185 0,61389 0,61389 0,788722 0,788722 0,665231 0,665231 0,251057 0,251057 0,27993 0,27993 0,280661 0,758352 0,758352 0,54704 0,54704 0,497788 0,497788 0,499088 C1 µF 0,315494 0,315547 0,367692 0,367692 0,462944 0,462944 0,361112 0,361112 0,144499 0,144499 0,184947 0,184947 0,192146 0,438058 0,438058 0,314857 0,314857 0,328885 0,328885 0,341686 C0 µF Table E.4: Transmission line parameters 4,435373 4,459465 3,827423 3,827423 6,386832 6,386832 5,18715 5,18715 2,002156 2,002156 2,410311 2,410311 2,360048 6,149535 6,149535 4,362593 4,362593 4,286161 4,286161 4,19678 R0 Ω 30,43955 30,39635 29,23587 29,23587 41,87643 41,87643 35,25316 35,25316 13,14126 13,14126 16,68108 16,68108 17,14094 42,31007 42,31007 28,63412 28,63412 29,66331 29,66331 30,48106 X0 Ω Name 380 50 50 50 50 6 6 6 50 50 Nom.Volt. kV 150 45 45 45 45 1 1 1 75 75 Qmax Mvar 150 0 0 0 0 250 250 250 0 0 L Hz 2,939149 84,88263 84,88263 84,88263 84,88263 84,88263 84,88263 84,88263 84,88263 84,88263 C uF 26,45234 0 0 0 0 0 0 0 0 0 Capacitance C1 uF 3,306543 0 0 0 0 84,88263 84,88263 84,88263 0 0 Capacitance C2 uF 383,0329 176,8388 176,8388 176,8388 176,8388 4,774649 4,774649 4,774649 106,1033 106,1033 L mH 900 0 0 0 0 0 0 0 0 0 Par.Resist. Ω Table E.5: Shunt parameters Dod-Co1 Dod-LC402 Dod-LC403 Dtc-LC402 Dtc-LC403 Ens Spoel 1 Ens Spoel 2 Ens Spoel 3 Gtb-LC401 Gtb-LC402 96 Table E.6: Parameters for the equivalent sources Name R0 Ω X0 Ω R1 Ω X1 Ω BMR150 BSL150 DOD150 EHVO150 GTB150 HGLO110 HGLO380 KIJ380 LGK150 MBT150 Niederrhein Rommerskirchen Siersdorf TBN150 Van Eyck 1 Van Eyck 2 Zandvliet 1,2 2,44 3,53 0,3 0,37 0,45 1,19 0,59 5,11 0,59 4,01 9,02 6,76 0,59 1,5 2,83 0,19 9,3 12,15 18,81 3,17 3,21 2,84 10,25 5,85 25,17 4,55 40,11 90,22 67,61 4,54 17,23 29,03 2,51 1,73 0,11 0,31 0,57 0,15 1,13 0,66 0,27 0,69 0,37 1,47 3,04 3,23 0,38 4,82 2,95 0,28 11,15 3,91 3,47 5,05 2,61 5,72 7,3 6 5,62 3,73 14,71 30,44 32,33 3,61 39,35 31,95 3,22 97