Uploaded by roverk

IRM-S01W

advertisement
IRM-S01W Cable type Water immersion sensor use’s Manual
1
External dimension
General
IRM-S01W cable type water immersion (short for sensor) is
based on the principle of conductive liquid, use Probe or
electrodes cable to detect whether there is water, and then the
sensor transform into a Level output. Sensor has the function of
scene warning to be convenience the onsite adjust, yellow power
for instructions, green for warning.
External dimensions (Picture 2)
29
64±0.5
54±0.5
Appearance and Interface
IRM-S01W
The appearance and interfaces (Picture 1)
输出及电源端子
Picture 2 External dimensions (Units: mm)
Output and power interface
输出及电源接口
Output and power interface
Bonding buckle
俯视图
IRM-S01W
Top view
punching hole buckle
Installation
Picture 1 Appearance and Interface
Curing adhesive on the back of the sensor with two magnets, the
sensor can be used adsorption installation, this installation is
easy.
Installation steps: Through the sensors on the back of the two
magnets, be adsorbed on any iron surface.
Output and power interface for sensor power supply and output
alarm.
This product comes with two cables retaining which can be
chose to use according to the actual situation.
Detected cable input terminal is for connecting the cable of the
sensor.
The installation steps for bonding buckle:
Make the cable through the hole of the buckle
Tear the film clips of the bottom, then make the clips attached to
the floor and fixed.
检测电缆输入端口
Detected Cable input port
正视图
Front view
2
Main technical index
Input: IRM-S01W(5m),IRM-S01W(10m)
The cable of water immersion sensor.IRM-S01W (5m) means
detected cable length is 5m, IRM-S01W (10m) means the length
is 10m.
Output: High-low level, output the low level when alert (0V),
output high level when alarm (output voltage >power supply
voltage -2V).
Alarm threshold range: 50kΩ ±10kΩ (hysteretic value≥5kΩ)
Auxiliary power supply: DC12V±10%~24V±10%
Working current: <30mA (24Vdc)
Response time: <1 S
Alarm on-site instruction: The yellow light is on when normal,
yellow and green light on when alarm.
Working condition: Temperature:-10℃~60℃;
Humidity: 20%~95%RH (without condensation)
Storage condition: Temperature:-40℃~85℃
3
The installation steps for punching hole buckle:
Punching a hole of a diameter 7mm and deep 20mm on the floor
Open the upper and lower parts of the buckle make the cable
from the buckle through the square hole, then snap the two parts
installed by the original.
Make the cylinder part of the buckle inserted into the ground
hole
Use a nail of no more than 3mm in diameter driven into the hole
at the top of the cylinder buckle, then make the buckle fixed on
the ground.
Installation
4
Wiring
Output and Power Interface
Toxic and hazardous
identification Table
Output and power interface for the RJ45 interface, location is
shown in Figure 1, which is defined in Table 2.
Terminal No.
RJ45 Interface definition
Definition
1
Working power supply
2
null
3
null
4
GND
5
GND
6
null
7
Level Output
8
null
Connection: The sensor output and Power Interface, using the
network cable to connect to the monitor host, power indicator
light (yellow) light, shows that it is working properly.
Detected Cable input terminal
Sensor's detects cable input port (located in Figure 1) using
pluggable in two terminals.
Connection mode: Access the two Testing Lines to the two
cables’ inputs respectively, no need to distinguish polarity.
Appendix 1 Packing list

One piece Host Sensor

Detected Cable one piece:
IRM-S01W (5m) is with 5m Detected Cable;
IRM-S01W (10m) is with 10m Detected Cable

Detected Cable Fixed Buckle (Bonding buckle and
punching hole buckle):
IRM-S01W (5m) each with 5;
IRM-S01W (10m) each with 10

One set of User's Manual
Appendix 2
substances
or
elements
Toxic and hazardous substances or elements
Part Name
Pb
H
g
Cd
Cr6+
PBB
PBDE
manufacture
×
○
○
○
○
○
d board
○:Indicates that the concentration of the hazardous substance
in all homogeneous materials in the parts is below the relevant
threshold of the SJ/T 11363-2006 standard.
×:Indicates that these toxic hazardous substances, at least in
this part of the content, one homogeneous material exceeds the
restrictions imposed by SJ/T11363-2006 standard.
Emerson has been committed to design and manufacture
of environmental products, We will continue to research to
reduce and eliminate toxic and harmful substances in products.
The following components or in applications that contains
toxic and hazardous substances ,which can not be limited for
the level of technology or to achieve a reliable alternative or
no mature:
1. Copper alloy in the Cable contains less than 4% lead.
2. Electrical contact products contain cadmium, but it is
in line with directive exemption clause of RoHS on the
cadmium content of.
Instructions on environmental protection use period:
Instructions of the products on environmental protection use
period (identified on the product),It refers to the duration that
products which are used in normal conditions and with safety
compliances, the duration is begin from the production date of
this product, toxic and hazardous substances or elements it
contains cannot caused by serious impact on environment,
personal or property .
Applicability :IRM-S01W cable type water immersion
sensor
Emerson Network Power Co., Ltd. 518057
Address:No.1 Kefa Rd., Science & Industry Park, Nanshan
District 518057 Shenzhen China
Customer Service Online:4008876510
Homepage:www.emersonnetworkpower.com.cn
E-mail:service@emersonnetwork.com.cn
All rights reserved. Any changes are without notice