Transformer Design Review as a powerful diagnostic tool By Victor Sokolov Fourth AVO New ZealandInternational Technical Conference 2005 TRANSFORMER DESIGN REVIEW AS A POWERFUL DIAGNOSTIC TOOL Victor Sokolov Scientific and Engineering Center ZTZ-Service Company Abstract The paper highlights Design Review as a powerful tool for condition assessment of operating Power Transformers. Supported cases of history are presented Introduction Determining the probable condition of operating power transformers is a matter involving many technical considerations. Historically developing transformer population has been accompanied with constantly advancing design techniques. Looking back into 60th and 70th we can find a number of design deficiencies attributed to underestimation of stray losses, inadequate thermal and short-circuit performance, etc. For instance, design analysis to determine winding the hot spot rise with modern design tools for 80 different transformers manufactured between 1960 and 1992 shown that 70% of the transformers had an actual hot spot higher than the ANSI limit of 800C, and 30% of the units had the hot spot rise higher than 900C [1]. Most units are designed to meet individual utility specifications involving significant difference in design requirements, features, and safety factors. Specification is a living document; which is constantly changing under influence of service experiences, especially failures experiences. The manufacturers may have different policies on adding margins to minimum requirements according to testing standards and in-house experience. Hence all large transformers are individuals and two units of the same style number can have a totally different “service health and age». Design Review can be the only effective means to identify peculiarities available. Design Review is a critical step in a Transformer Life Management program. The life of a transformer may be introduced as the change of its condition with time under impact of thermal, electric, electromagnetic and electrodynamics stresses, as well as under the impact of various contamination and aging processes. A failure occurs when the withstand strength of the transformer with respect to one of its key properties is exceeded by operating stresses. Therefore Identification the locations with minimum safety margin would be critical to anticipate likely problems Design review is a key procedure to answer the questions: What defects and faults can be expected in particular transformer components related to the particular functional subsystem? What is the possible path of defect evolution into the malfunction, and then into failure? Relevant Failure model allows minimizing diagnostic program and selection the most economic tools. Design Review could be also effective tool for determination a scope of repair of failed transformer. This paper presents some aspects of design review, which would likely assist to recognize an operating transformer better. Fourth AVO New ZealandInternational Technical Conference 2005 Failure-modes versus transformer application, power and class of voltage Effect of transformer application Transformer application impacts significantly on design and possible failure modes. Failure statistic would be the most convenient instrument to understand the difference in reliabilityrelated problems versus transformer application. ZTZ-Service database covers failure events since 1965-66. Observed equipment include large power transformers of different application including over 5,000 of units rated 100 MVA and above, auxiliary power plants transformers (over 700 units) and shunt reactors 400-750 kV (over 260 units). Since 1994 date-base have been supplementing also with collection of worldwide failure events. Table 1 allows examining failure-modes of generator, auxiliary and transmission transformers separately. and compare with relevant data reported in 1996-98 by Doble clients (52 failures). Transmission transformers: Over 30% of failures are associated with dielectric –mode damage of winding insulation (basically HV windings) whereas thermal mode failure rate still does not exceed 5%. Average age of the transformers failed for the last 5 years is 20.5 years. 32% failed after 25 years and 9.4% before 5 years in service. Insulation contamination, winding movement (especially common and tertiary) and particularly bushing insulation deterioration found to be subjects for diagnostic priority Generator step up transformers Dielectric –mode failures involving basically HV windings insulation make up to 50% of total numbers however number of thermal mode failures has been markedly increasing for the last years. Generator transformers have exhibited also a substantial number of failures due to leads and connections overheating. Average age of the transformers failed for the last 5 years is 21 years. 44% failed after 25 years and 3% before 5 years in service. Auxiliary power plant transformers Subjects for diagnostic priority should be OLTC: insulation impairment (diverter switch particularly) and contacts overheating; the condition of leads insulation and connections ; mechanical state of winding under effect of short circuit stresses and over current events followed to energizing rotating machines (radial distortion of LV windings and twisting and tilting of Tap windings). Winding insulation failures occur basically due to free water permeating. Fourth AVO New ZealandInternational Technical Conference 2005 Failure -mode Dielectric Table 1 Major failures of power transformers Component Doble clients 1996-1998, >100MVA 23 ZTZ-Service 2000-2005,% GSU Auxiliary Auxiliary >100 unit Start up MVA 37.8 7.1 28.5 Trans mission >100MVA 14.3 13.4 11.2 21.4 7.2 17.3 5.8 13.3 - 7.2 4.8 Thermal Winding minor insulation Major insulation Major leads insulation Conductor insulation Mechanical Winding distortion 12.5 4.4 14.3 28.5 9.5 Magnetic circuit 5.8 4.4 - - 4.8 Current carrying Core/magnetic shields* Leads, connection 3.8 13.3 14.3 - 3.2 Accessories Bushing 9.6 13.3 - 14.3 38 OLTC** Insulation Contacts overheating DETC 15.4 4.4 2.1 14.3 14.3 - 7.9 3.8 42.8 21.4 21.4 - - 100% 100% 100% 100% 100% Total *Only force outages considered ** Only major failures Effect of power & voltage Peculiarities of large power transformers are associated with huge amount of heat dissipation, dramatic effect of stray flux and extremely high electrodynamic stresses. A conditional verge below and above 100 MVA could be used in order to anticipate a negative effect of winding stray flux. Rise in class of voltage results in increase of electric field intensity and particularly in increase of amount of electrically stressed insulation. Due to a low stray loss component in transformers 35-110 kV below 100 MVA faulty gas generation is typically involves overheating of current-carrier connection (dangerous case) or just penetration of gases into the main tank from OLTC compartment, whereas in large unit this phenomenon is often results from overheating under effect of stray flux (not very dangerous case). Surface discharge and creeping discharge can occur if electric field stress is large enough. Accordingly Voltage class of prone to damage winding major insulation is typically 220 kV and above Due to a huge dissipated energy, significant stray flux and complex insulation structure large HV transformers more disposed towards localized insulation heating and early aging deterioration. Transformers over 220 kV have a large amount of so called “thin cellulosic structure” contacted with bulk of oil and more susceptible to moisture, particles and oil aging by-products Fourth AVO New ZealandInternational Technical Conference 2005 Amount of water- adsorbing cellulosic insulation in transformers 35-110 kV is relatively small. Correspondingly different transformers require different approach to identification of insulation deterioration. What diagnostic-related information one can get from the name-plate data? The name-plate data may advise a rough idea on identification of the transformer composition, namely of number on windings, their connections and approximate disposition, voltage/ current distribution, as well as understanding the type of LTC, bushings, and cooling system AC voltage variation may suggest possible variation of flux either in the core leg (e.g. step-up autotransformer, regulation in neutral of HV winding) or in the core yoke (e.g. step down autotransformer). Insulation level and ratio of BIL/ 1min AC test voltage and rated voltage may advise sensitivity of insulation to service contamination Value of leakage impedance (Usc%) provides information about through fault current and possible level of short-circuit stress. E.g. value of Usc <12% for transformer >80MVA would require a special analysis of short-circuit performance. On the other hand Usc >16-18% would mean a high value of stray flux and possible heating of metallic parts linked with stray flux. Comparatively low Usc =12-13% for a large (over 400-600 MVA) generator transformer would suggest presence in construction two HV and maybe two LV windings. Current value over 1000 Amps through connection would require a special attention to possible contact deterioration, particularly connections of draw rod bushing. Comparison of maximum rated current of transformer, bushings, and maximum rated throughcurrent of OLTC allow to anticipate possible thermal behavior of the components For example: GSU single phase transformer 350 MVA was provided with Tap Changer of rated through-current 1600 Amps. According to IEC 60542 maximum rated through current of LTC shall be at least by 120% above the maximum current of transformer In this case maximum current of HV winding was 1560 A and ratio of maximum current of LTC and Transformer is only 102.6 %. Generator transformer is operated with typically rare taps changing and very susceptible to LTC contacts deterioration (film coating formation). Increasing contact resistance e.g. up to 100 microohms would form local heater over 200 W and inevitable cooking. Several cases of diverter switch contacts failures occurred. Identification of a transformer basic model for anticipating likely weak spots The following factors determine transformer basic model: • Magnetic circuit : core form or shell form. For three phase core form design number identification of a number of limbs (three limbs or fife limbs) is important • Windings arrangement and AC voltage distribution • Structure of major insulation Fourth AVO New ZealandInternational Technical Conference 2005 Winding arrangement review may advise: What are the likely weak spots in major insulation? Which winding could likely suffer under effect of short-circuit stress? What’s diagnostic accessibility of design? For instance, fig. 1 presents sketch of winding arrangement in the 500 MVA, 400/132/22 kV, autotransformer with voltage regulating: in Series winding 132 kV TW RW CW 400 kV SW Figure 1 Winding arrangement in the 500 MVA, 400/132/22 kV autotransformer. Between regulating and tertiary winding is arranged grounded electrostatic shield One can deduce that the most stressed insulation spaces are “Regulating winding-Grounded Shield”,“Common winding-shield” and “Series winding-Common winding’ Possible rise of impulse voltage in the Regulating winding and Tertiary winding should be considered. Radial stability of the common winding and tertiary winding should be checked particularly. Disposition of regulating winding suggests on limited resistance to radial stresses. Winding would be very sensitive to any short-circuit between OLTC steps and the condition of OLTC In service should be a subject of special attention. Dielectric accessibility of insulation design is very low. It is practically impossible to assess the insulation condition by means of any dielectric characteristics (tan delta, polarization spectra , whatever) because insulation spaces between the windings are shunted. Identification of winding construction would be the next step, which allow to suggest primary conclusion about dielectric, mechanical and thermal performance of the windings. Type of the windings (layer, disk continuous, disk interleaving, helical, etc) , number of turns, Number of sections /layers, and type of conductor should be of common interest. From dielectric point of view subjects of interest are voltage between conductors and sections, wire insulation thickness, size of radial cooling duct, and axial ducts under and over winding, presence of capacitive rings/ A special attention should be paid to interleaving and tap windings. Fourth AVO New ZealandInternational Technical Conference 2005 For assessment of mechanical performance the following parameters should be considered: Max current density, A/mm2; Conductor yield stress in tensile at 0.2% offset ( 02 MPA) at the design shot-circuit temperature; average diameter; number of spacer columns, strands dimensions: height, thickness, and ratio of radial size of the strands (conductor thickness) and average winding diameter. For assessment of thermal performance are important to review the following Max current density, A/mm2; wire strand height; radial dimension of section; wire insulation; Ratio of radial dimension and strand height; Spacer width; number of spacers (open cooling surface); Cooling radial duct (considering possible bulging of strands insulation, CTC wire particularly) Directed oil flow; Number of radial passes; Axial duct under and over winding, mm Arrangement of insulation collars (possible block if cooling flow). Performance of winding sections from the same wire height could result in a high eddy current loss in top coils Arrangement of insulation components can affect cooling oil flow (e.g. Fig.2) Figure 2 Left: Disposition of barriers prevent oil flow into RW and TW area Right: Arrangement of collars is blocked top coils area. Estimation of dielectric safety margin and sensitivity to deterioration The basic methodical procedures to review dielectric performance • • • • Verification if the test voltages comply with Principle of Insulation Coordination Calculation of test impulse voltage distribution across the minor and major insulation Calculations and in-depth analysis of the electrical field considering all modes of test voltages Calculation of the dielectric safety margin on the basis of assessment of dielectric strength in questionable areas including the dielectric strength across the barriers. Incipient PD voltage is typically considered as characteristic of dielectric strength. Fourth AVO New ZealandInternational Technical Conference 2005 BIL specification covers only a segment of insulation reliability Case 1. 240 MBA, 240/115 kV autotransformer. Design review revealed two weak spots: space between series and common windings and bottom part of the common winding in the clearance “common-tertiary windings”(Fig 3).Estimation of the safety margin pointed at the critical insulation space between series and common windings. Analysis revealed that while the strength under full wave impulse level had a positive safety margin, a negative margin would be under the effect of a switching surge (Table 2). Safety margin was estimated as a ratio of expected withstand strength and stress applied. Table 2 Safety margin in the autotransformer 240/110 kV. (Oil axial duct under HV in the space between series-common windings) Determinant Voltage Safety margin , % -8 -7 Induced 1 min (non specified) Switching impulse 540 kV (non specified 11 Full wave 650 kV (specified) HV Series LV Common LTC Tap TV It’s important to emphasize that aging of oil and deposit of sludge in the locations of high field intensity could significantly affect the impulse strength. The minimum breakdown voltage at switching surges may decrease approximately by 15- 20 % after aging. Therefore a design safety margin of less than 20% should be considered inadequate under most circumstances. Assessment of oil oxidation state allowing sludge appearance was advised to maintain reliability. Figure 3 Winding arrangement and weak spots in the 240/115 kV autotransformer Fourth AVO New ZealandInternational Technical Conference 2005 Underestimating impulse overvoltage. This phenomenon is basically related to underestimation of impulse transient function and effect of transient oscillations. Case 2 40 MVA, 220/6 kV step down start-up auxiliary transformer at a Power Plant, which was frequently subjected switching transient during vacuum circuit breaker commutations failed due to short circuit between coils of Tap Winding (Fig. 4) Figure 4 Short-circuit between the coils of Tap Winding Design review shown that Tap Winding is mostly stressed. Whereas voltage between coils of HV winding was 2.4 kV, that between the TW coils was 6.4 kV. Analysis shown that voltage rise in TW depends on tap position. Estimations shown a positive safety margin on rated, min and max positions, which are typically verified by impulse test. However the largest stress occurred when only one step was involved. In this case voltage between the coils could reach critical level 80 kV. Moreover it was found that resonance frequency is equal to 19-11 kHz and resonance can occur just during circuit breaker commutation. Assessment of diagnostic priority Case 3 Family of 60 MVAR, 400 3 kV Shunt Reactors A family of shunt reactors has been reviewed in order to develop failure model and main objectives for diagnostic program [2]. It was found that insulation performance has been determined by impulse withstand strength and occurrence of surface discharge across the winding insulation (Table 3). Contamination of surface with conductive particles could reduce impulse withstand strength below the critical level. Accordingly monitoring of conductive particles in oil and PD tests were advised as a main diagnostic procedures. Fourth AVO New ZealandInternational Technical Conference 2005 Table 3 Dielectric safety margin of major insulation n the shunt reactor Safety margin Component Coil-to-coil Switching surge 5.8 Lighting impulse 1.55 Turn-to-turn 10.8 6.6 Oil-barrier major insulation 2.6 1.75 Along the winding 1.27 1.17 Case 4 Family of Generator Step Up transformers 417 MVA, 24/787/ 3 kV Design review revealed the insulation space between the bushing and tank wall as the most sensitive location, which practically determines operative reliability of the insulation assembly [3]. Withstand strength of this space would depend predominantly on the condition of oil and also on surface conductivity of pressboard barriers. Thus the suggested diagnostic program was focused on prevention of the potential reduction of dielectric strength of oil from particles, water including bound water absorbed with oil aging products ; from any possible source of bubble evolution, as well as contamination of barriers surface. HV LV Figure 5 Location of minimum safety margin in 750 kV GSU transformer Possible oil and barriers contamination should be a main focus of condition monitoring Fourth AVO New ZealandInternational Technical Conference 2005 Table 4 Estimation of dielectric safety margin in the 417 MVA 24/750// 3 kV GSU transformer Safety margin Insulation Component Switching surge Full wave Lighting impulse HV turn-to-turn 4.8 1.75 HV coil-to-coil 3.5 1.41 Between HV-LV windings HV-winding- tank 1.6 2.2 1.57 2.36 HV bushing-tank 1.2 1.26 Sensitivity to deterioration It’s well known that contamination of insulation with water, particles, and bubbles causes a high Risk of Critical Defective Condition in Dielectric system. However sensitivity of particular insulation design to deterioration of dielectric withstand strength would be very variable. Large oil gap. Large oil gaps, particularly those that not divided by barriers are very sensitive to oil contamination with particles and also to distortion of electrical field on electrodes. CIGRE WG 12.17 studied Effect of Particles on Transformer Dielectric Strength and collected 65 cases of failures attributed to particles contamination. It was found that nearly 90% of total number occurred in the space between the HV bushing shield and the turret or between the HV lead and turret or the tank wall. These locations are typical weak spot especially if there is no barrier between electrodes Several failure cases occurred due to poor performance of 500 kV bushing shield, namely hidden defect of the metallic mesh with presence of sharp ages. (Fig.6). That resulted in PD activity under effect of switching surge and power arc to the turret Figure 6 Left: Hidden defect of metallic mesh of 500 bushing shield,caused short-circuit from the shield to the turret Right: Typical construction of bushing installation within the turret Fourth AVO New ZealandInternational Technical Conference 2005 kV Studies of the effect of water on dielectric strength of winding minor insulation [4] shown that the most susceptible to dangerous effect of moisture would be “coil-to coil insulation” of interleaving winding and tap helical type windings where coil-to-coil voltage make up to 3-10 kV or above. A common subject of concern is possible releasing moisture vapor bubbles out of heated conductor insulation during overloading. Breakdown of oil duct due to free water. Poor or deteriorated top sealing of draw lead bushings as well as poor sealing of explosion vent remained to be repeated worldwide cause allowing penetration of rain water into transformer and resulting in of a sudden breakdown oil duct between coils of HV or RW windings . Figure 7 Short-circuit between coils due to introducing free water Left: damage of 400 kV winding due to penetration of water through poor bushing top sealing Right: Short circuit between coils of regulating winding disposed under explosion vent Free water can pose hazard equally for 500 kV and 35 kV transformers however sensitivity of construction to moisture differs drastically . There have been a number of failures of 35-110 kV transformers associated with free water penetration. In fact operating dielectric stresses in regulating windings of these transformers can be nearly equal to those in 500 kV windings. Voltage between sections typically makes up 5-6 tap step voltage. A special study of winding models shown that layer type winding with radial oil ducts between sections can be very sensitive to moisture contamination. Some test results are depicted in Fig 8 confirming that severe moisture contamination can reduce breakdown voltage to the level of operating voltage between sections. On the other hand performance of winding without radial ducts makes it much less sensitive to moisture. Figure 8 Impact of moisture and temperature on breakdown voltage between winding coils I-Model with oil duct: 1a-dried insulation; 1b-non-dried insulation; 1c-high moisture in oil and on surface 2-Model of layer winding without radial ducts Bubbling form heated winding. So what? Dangerous effects of bubbles in oil lay in likely PD occurrence at rated voltage. The question comes whether it would be dangerous for all type of windings? In accordance with Pashen’s low breakdown voltage of air bubbles e.g. d= 0.4 mm in diameter is 0.8-1.0 kV. Bubble voltage (Ub) depends on coil-to coil voltage (Ucoil), oil duct thickness (S) and turn insulation thickness ( d Ub ⋅ U coil (1) ε air ε air d + ∆p +S εp ε oil Assuming dielectric permittivity of oil oil=2.2, air air=1, and paper bubble can occur if coil-to coil voltage averages 5-10 kV. p=3.8 we have that PD in Therefore bubble evolution can pose hazard practically for interleaving winding and also for some tap and layer type windings, whereas e.g. helical and disk continuous windings are likely not sensitive to bubbles releasing. Fourth AVO New ZealandInternational Technical Conference 2005 Estimation of Mechanical safety margin The basic approach and methodology • • • Calculation of through fault current; Calculation of short-circuit internal stresses; Evaluation of conductor Strength, that characterizes an ability to withstand internal shortcircuit forces without damage; • Evaluation of Rigidity factor that characterizes an ability to withstand internal forces arising under deformations without fault; • Evaluation of Radial Stability that characterizes ability to withstand internal forces without disturbing initial state of equilibrium. The guide used for assessment of short circuit performance was basically elaborated by Dr. Lazarev (Transformer Research Institute, Zaporozhye) and include estimation of seven safety factors coefficients: • • • • • • • strength under the action of radial forces; rigidity under the action of radial forces; stability under the action of radial forces; strength in bending of conductors by axial electromagnetic forces; strength in bending of conductors by radial electromagnetic forces; stability to the conductors tilting; strength under the action of axial forces. Engineering analysis allows to pinpoint the winding which could suffer from short-circuit Stress and also to advise likely form of deformation Design review using modern method reveled that dynamic stability of old transformer design was often not sufficient to meet specified stresses basically due to insufficient stability under radial stresses. Figure 9 Forms of loss radial stability Left : Half-shifted form of loss stability. No radial support, insufficient compressive force Right: Shifted form of loss stability. No radial support, sufficient compression force Fourth AVO New ZealandInternational Technical Conference 2005 Case 5 Failure of 80 MVA, 80/33 kV step-down transformer. Transformer failed due to dramatic distortion of LV winding (Fig 9). It was found that transformer, which was manufactured in 1974 has alow radial stability (Tabl. 3). Taking into account a long service life and inevitable loosing the winding claming half-shifted for of deformation was expected Table 3 Winding, tap position RW, max LV, max HV, max Safety margin Radial Axial 6.4 6.4 0.54 0.94 3.63 Figure 10 Radial buckling of LV winding after 3 phases short-circuit on LV side Half-shifted form of deformation revealed. Determination of effective set of maintenance actions on the base of engineering analysis Case 6 Generator Step Up transformers 417 MVA, 24/787/ 3 kV at Nuclear PP Though fault event has been recognized as the most critical problem due to tremendous concentration of power on the 750 kV bus bars . Three likely events with GSU transformers were considered and evaluated: single-phase short circuit on the 750 kV side, three-phase short circuit on the 24 kV side, and an internal flashover from the high-voltage winding-to-ground. Possible radial distortion of the external layer of the LV winding was found to be the "weak spot” in the case of a short-circuit fault on the 24 kV side especially on condition of releasing winding compression forces. The short-circuit current multiplicities was specified as 6.75. However considering possible loosing of winding clamping the values exceeding 75% of the specified ratio (6.75 0.75=5.06) has been defined as a "critical event", which would require checks of the possible winding distortion. Calculations also shown that in a case of internal short-circuit between "Lead (or bushing) 750 kV and Ground" the value of current would exceed 30 kA. It could result in an arc that would Fourth AVO New ZealandInternational Technical Conference 2005 dissipate up to 135 MJ/s energy and in corresponding generation of gas with the rate up to 75 m3/s. Apparently, such catastrophic event must be prevented by all means. Table 5 Through Fault Current in GSU Transformers Event Through-Fault Current HV LV kA Ratio kA Ratio Single-phase short-circuit on 750 3.21 3.51 68.43 3.94kV Three-phase short-circuit on 24 5.28 5.76 173.3 5.76 kV Internal short circuit 750 kV to 30.5 ground Normal Ratio 6.75 Table 6 Safety margin of the windings under 3-Phase Short Circuit on 24-kV Side Winding Margin Radial Stress Axial Stress LV inner layer LV outer layer HV 2.9 - 5.8 0.9* - 1.7 - 2.26 1.26 1.27 * Considering release of compressive force Assessment of Thermal performance Typically a manufacturer calculates mean temperature rise of each coil of the winding and corresponding mean winding temperature rise above mean temperature of oil considering the heat flux density, real cooling surface, thermal conductivity of insulation, ratio of winding radial dimension and cooling duct. Some coils (sections) and strands within a coil, which have temperatures higher that the mean coil temperature due to additional heat by stray losses or worse cooling are defined as the hot spots. The hot spot temperature rise above the ambient is typically introduced as sum of the hot spot temperature rise of the coils above oil and the top oil temperature rise above ambient. The mean temperature rise of oil above ambient is considered to be equal to mean rise temperature of oil outside the windings or in the cooler. Accordingly, the drop of temperature across the winding is considered to be equal to the drop of temperature across the cooler and the top oil temperature is taken as the maximum oil temperature However the foresaid model does not reflect properly the processes of heat exchange particularly in large power transformers with oil forced cooling. Fourth AVO New ZealandInternational Technical Conference 2005 We believe that the more realistic model for temperature distribution should consider that the main heat conductor acquiring the heat generated by coils would be axial cooling duct close to the winding, which on the other hand is limited by size Axial rise of oil temperature should be calculated considering coefficient of moving pressure gradient, coefficient of axial rise of oil temperature, and constant of oil flow friction. Oil temperature leaving winding can be substantially higher than top oil temperature but cannot be determined properly by means of oil temperature measurement outside the windings. Top oil temperature would be a temperature of mixture of oil leaving the windings with oil heated by the core and outside oil. Thermal-mode failures Analysis has shown the following failure causes: Overheating of tap leads located between regulating coils of HV winding connected to no-load tap changer. Overheating of the coils of winding blocked with insulating boxes or collars preventing oil flow and proper cooling. Underestimation of winding temperature, especially of LV winding in large generator transformers with OFAF cooling system. Hence the main reason of failures was not normal aging but design deficiency Figure 11 Failure of 700 MVA generator transformer after 25 years due to overheating the two top coils of LV winding (CTC wire) resulting in short circuit between parallels and then between turns Fourth AVO New ZealandInternational Technical Conference 2005 Case 7 Estimation of temperature profile of a Large Power Transformer Design review of 730 MVA, 420 kV generator transformer revealed a high temperature of the top coils of LV. According to the tests the mean rise windings temperature above the air met specified quantity (65 0C). However, mean rise temperature does not show a real picture of the windings heating especially if radial cooling ducts would be diminished. Fig.12 shows that at rated radial ducts 14 coils of the LV2 winding may have rise of temperature above 65 0C. In the case of diminished ducts more than 50 coils would have temperature rise above 65 0C and 4 coils –above 80 0C. Fig 12 Temperature profile of the LV winding (temperature rise above air) The difference in insulation temperature predetermines nonuniform decomposition of insulation. It was found (Fig.13) that insulation of the top of LV winding has reached practically the end of life while the condition of other insulation remained to be fairly good. Amount of heated insulation that subjected to accelerate wear was estimated as less than 2 % of total mass of conductor’s insulation. Figure 13 Polymerization degree of conductor insulation from 730 MVA GSU transformer Overheating the leads insulation There have been observed several cases associated with overheating of winding leads that were performed with the same wire as a winding, what is typical when winding is performed from CTC wire Figure 14 Overheating and burning out leads insulation in 700 MVA GSU transformer Left: Burning out internal layers of HV lead Right: Calculated temperature rise of HV lead above oil Maximum temperature rise is 77C. Design review and relevant calculations have shown that performance of leads with winding wire without increasing cross -section can be a subject of special concern especially when a thick lead insulation is used .One should emphasize that design review is likely the only effective tool to identify the problem. Considering a limited amount of overheated insulation DGA and Furans analysis show clear symptoms of fault only on the stage when short-circuit between strands and insulating burning occur. Assessment of magnetic circuit condition There were a few cases of major failures associated with faults in magnetic circuit system however a number of cases occurred involving intensive gas generation and scheduled but unwanted outage. Most of the problems associated with generation of dissolved faulty gases in oil involved overheating, sparking or arcing in magnetic core or magnetic shunts (shield) . Probable defects can be grouped under two general headings: 1) Defects associated with main magnetic flux, and 2) Those associated with stray flux. Fourth AVO New ZealandInternational Technical Conference 2005 Defects associated with main magnetic flux Faults associated with the main flux form loops for circulation current in the core linked with main flux (insulated bolts, pressing bolts, pressing metal rings).They results in dissipation of high energy and intensive gas generation with activation of Buchholz relay. Can be a Normal Core a source of gas generation? Design review includes examination of the core configuration and assembly, steel laminations; number of steps, join pattern, insulation, clamping, grounding, and evaluation of basic parameters: flux density, no-load loss/ magnetizing current and their variation with flux density (voltage). Temperature of the core should be a subject of particular consideration. It was shown [5] that under normal operation and permissible overexcitation by 110% the hot spot of core temperature can vary in the range 90 -140 or even 170C (for some old design. Note that hot spot temperature exceeds core surface temperature by 10-15C.The hot spot temperature correlates with flux density (Figure 3), steel grade and cooling arrangement Figure 15 Correlation between flux density and hot spot temperature [2] Macrocapillaries between laminations are impregnated with oil and the latter is subjected to effect of elevated temperature resulting in gas generation and oil deterioration. Specific gases are hydrogen and methane accompanied with CO and CO2 due oil oxidation process . The picture of gas pattern gives sometimes the impression of PD activity or insulation overheating However gas content correlates with gassing tendency of oil under impact of temperature and metals Fourth AVO New ZealandInternational Technical Conference 2005 Case 8 Unusual evolution of gases at early stage of transformer service Two banks of single-phase 100MVA, 500 3 kV generator transformers exhibited unusual gassing just after energizing. A subject of concern was occurrence of hydrogen and increasing of concentration of CO up to 500 ppm (during 15 month of operation a low ratio CO2/CO=3.53.0.There was no technical reason for insulation overheating because of a low load (50%). Apparently the winding temperature was quite low due to a low load, however estimated core surface temperature was 90-950C, so that the hot spot temperature was anticipated on the level 100-105C. “Stray”gas formation in oil under effect of temperature has been suggested. Study of temperature response of the oil used in the transformers revealed notable trend of gas generation, especially at presence of stainless steel (Table 2), and confirmed normality of gas content in the transformers Table 7 Effect of temperature and steel on Gas formation from Nytro-10GBN oil at 1000C CH4 H2 ppm CO2 ppm CO ppm Time, hour 0 24 72 0 24 72 0 24 72 0 24 72 Blank oil 0 7 21 0 29 92 143 178 674 0 34 151 Oil with presence 0 9 50 0 30 120 143 223 782 0 127 200 of steel pattern Tests performed in the ZTZ – Service Material Lab According to ZTZ-Service tests, and latest studies of CIGRE two groups of oils could be recognized in terms of gassing tendency under effect of operating temperature: 1) Oils that evolve hydrogen and some methane and 2) oils that exhibited thermal-mode gas pattern: methane, ethane, hydrogen. In both cases formation of CO and CO2, which accompanies oil oxidation could be expected. Gas pattern and rate of gas generation can be used likely to anticipate the hot spot temperature of the core. Overexcitation The maximum value of magnetic flux density in any part of the magnetic circuit under any of the specified voltage and tap position should not attain a value that causes saturation. Practically when no-load flux density exceeds 1.9 Tesla one can expect a rash rise of magnetizing current and no-load losses, and also rise of loss and temperature in metallic members of the core. Experiments had shown [7] that after increasing flux density up to 2.1 Tesla temperature of the pressing plate of the core leg reached 100C during one minute. Typical reason for overexcitation is variation of voltage by means of LTC and Tap winding connected in neutral and corresponding variable magnetic flux. However one should consider also effect of stray flux on variation of magnetic flux in the core [6,7] Magnetic flux in the core depends on disposition of energized winding. Increasing the voltage of the winding that disposed directly on the leg can result in overexcitation of the leg, but increasing the voltage of the outside winding (e.g. series winding of an autotransformer) can result in overexcitation of the yoke. Transfer power from LV side to HV side in autotransformer with LTC in neutral results in increasing flux density in the core limb. The extreme flux density in the core limb could be estimated as ratio of actual and rated voltage on the common winding. Transfer power from HV side to LV side in autotransformer results in increasing flux density in the core yokes (the more flux the less turn ratio). Fourth AVO New ZealandInternational Technical Conference 2005 The magnetic flux density in the core yokes may be estimated as flux density on-load multiplied by overexcitation factor (Fover)) , which is equal to ratio of actual voltage on series winding and rated voltage BOL = B NL ⋅ Fover = Fover UW _[Tesla] U WR (2) U SW U − U LV = HV U SWr U HVR − U LVR U × β × WCW U sc × β × WCW = 100 × k × 1 + 2 × sc × sin ϕ + 100 × k × WSW 100 × k × WSW (3) 2 ,% (4) U HV - the ratio of actual and rated voltage U HVrat Usc , % - impedance; I β= - The ratio of actual and rated current; I rat WCW/WSW - - number of Common /Series winding turns; where k = sin ϕ = 1 − cos 2 ϕ , where cos ϕ - power factor. Hence overexcitation factor depends on parameters of transformer (turn ratio, impedance, windings disposition) and operation condition (voltage, current, power factor, direction of power flow). Note that overloading typically results in overexcitation as well. Figure 16 Yokes over saturation in the autotransformer 220/110 kV under effect of stray flux and voltage variation Fourth AVO New ZealandInternational Technical Conference 2005 Case 9 Local overheating the core in a generator transformer In 730 MVA generated transformer was detected overheating the joins between extreme lamination packages of the core yoke (Fig.117) Design review shown that average flux density in the lag was 1.76 Tesla. However in some lamination packages due to distribution of magnetic flux and effect of stray flux the flux density could exceed 1.9 2.0 Tesla Figure 17 Traces of overheating and carbonizing the core yoke at T-joint area ((phase B) Case 10 Unusually high concentration of furans in oil caused by core heating Overheated parts of the core being in contact with cellulosic material can cause intensive pyrolysis and furans generation Condition assessment of 250 MVA, 15/400 kV at Thermal Power Plant shown symptoms of severe insulation overheating: concentration of 2FAL= 19.2 ppm, concentrations of CO= 899 and CO2 =1034 ppm’ However, there was no reason to expect any significant aging of winding insulation since the estimated hot-spot temperature during actual operation was less than 85°C. Visual examination of core and coil revealed that high furfural concentration was caused by local overheating of the magnetic core and the insulation sheet adjacent to the yoke due to short-term core overexcitation in service. Overexcitation occurred while procedures with adjustment of the TPP unit involving possible energizing the transformer at lower frequency. Note that magnetic flux is a function of ratio U/f. Core Grounding Each metallic member of the core should be typically grounded in one point. However direct metallic contact between the core frames, pressing plates on the core legs, etc., can form loops for circulating current linked with stray flux. This phenomenon should be a subject of particular concern in Large Power Transformers where circulating current value can attain several hundred Amps or even -kilo Amps Fourth AVO New ZealandInternational Technical Conference 2005 Figure 18 Connection between core members that susceptible to possible overheating Defects associated with stray magnetic flux These defects present the main cause of localized oil overheating and gas generation. They can be classified into two groups: 1) Overheating under effect of eddy current induced by intensive stray flux; 2) Overheating and (or) sparking in a loop for circulating current, linked with stray flux. In the first group typical defects are overheating of core frame due to absence or improper disposition of magnetic shields on the frame (Fig.19 left), overheating of pressing of the pressure bolt that situated just under the core yoke (Fig.19 right), overheating a part of the tank wall due to improper shielding Figure 18 Local overheating due to eddy current induced by stray flux Left: overheating the bottom frame and adjusted insulation in 730 MVA generator transformer due to improper disposition of magnetic shields Right: Overheating the pressing jack in 417 MVA generator transformer There have been observed two mechanisms of overheating of members that form loop for circulating current: Loose contact in circulating loop provided with construction (Fig. 20) Shorting between core members forming the loop: • Shorting magnetic shunts to core and the tank • Shorting bottom frame to tank (Fig. 21) Fourth AVO New ZealandInternational Technical Conference 2005 • Shorting top frame to tank The latter forms loop of large dimensions, allowing induced voltage up to 10 V resulting in heating and arcing. Figure 20 Overheating in the loosed place between members forming loop for circulating current in 700 MVA transformer Figure 21 Traces of overheating in location of contacts the core frames with tank bottom Fourth AVO New ZealandInternational Technical Conference 2005 Determination of “sensitive” points in OLTC design Specifying the large generator transformer with LTC or DETC predetermines a long term contacts operation in one or two tap positions and complicates significantly transformer design. In many instances mechanical and dielectric performance of the transformer is determined by state of tap winding and leads. Choice type of OLTC with a low ratio of the maximum rated through fault current of LTC and the maximum current of transformer. According to IEC 60542 this ratio shall be at least 120%, and temperature rise of LTC contacts above the oil shall be not more than 20C. Experience has shown that for rarely moved contacts temperature rise shall be less that 15C Underestimation of impulse transfer function allowing in some cases voltage value between steps or with respect to ground above the test voltage of OLTC. Many failures initiated with short-circuit between steps in diverter or selector switches were accompanied with distortion of Tap winding. In fact rare transformer is designed to stand shortcircuit between LTC taps. Accordingly a comparatively minor failure in OLTC (e.g. burning out resistance) has been resulted in major transformer failure and long-term unit non-availability. Experience highlights necessity to pay more attention to diverter switch reliability. Particularly the following factors should be considered: Aging deterioration of oil due to effect of a high resistors temperature. By-products sediment on insulating surfaces affect on degradation of dielectric strength. Mixture of carbon, water and polymerized by-products hardly can be filtered out properly. Temperature rise of shunt contacts can sometimes exceed temperature rise of selector and reverser contacts making a week spot that requires special attention. Contact overheating can result if flashover between the phases followed with explosion and fire. Case 11 Overheating the shunt contacts of the diverter switch The problem with 1600 A LTC has been definitely localized on the diverter switch, due to overheating the shunt contacts. The overheating was caused presumably through limited movement of the contacts of the OLTC over time (which had operated about 5000 times in 20 years). However limited movement relates as to diverter switch as well as to selecting and reversing switch contacts but condition of those contacts are extremely different (Fig 22) Fig.22 Comparative condition of the selector switch and diverter switch contacts Fourth AVO New ZealandInternational Technical Conference 2005 Overheating and coking of the contacts with limited movement is a typical and well-known failure mode of closed heavy current contact pieces in insulating oil. In most cases, reversing contacts that are subjected to minimum movement have suffered. One can admit that difference in contact designs and particularly the difference in resistance and temperature of the contacts could be the main factor. According to IEC 60214 contact temperature rise limits shall be 20K above oil when carrying 1.2 times the maximum rated through current Design review of the LTC shown that the diverter switch shunt contacts have a maximum temperature and could be recognized as the weak point, which need in special attention Table 8 Temperature rise tests of the LTC 2000 and 1600 A Temperature rise 0C Current 2000 A Current 2400 A Diverter switch Main fixed contact upper 12 17 13.5 12 18 16.7 Tap selector of the LTC 2000A Moving main contact Main fixed contact (lower contact lamination) Moving contacts Connecting contact 10 10 12 13 shunt contact of diverter switch 15,7 °C at 1600 A. 21C ( estimated for 1920 A) OLTC 1600 A Fourth AVO New ZealandInternational Technical Conference 2005 What diagnostic- related information one can get from fingerprint factory tests? Volts per turn This is a fundamental design parameter, which allows to determine magnetic flux density, number of turns in each winding and relevant voltage between turns, coils, and taps Flux density may be estimated from a simple equation Volts _ per _ Turn 4.44 • f • S where f is power frequency and S- is cross sectional area of magnetic circuit B= (5) Turn Ratio This is well known routine method however there is still some misunderstanding in its application and interpretation According to IEEE the accuracy of the method shall allow to obtain the difference between calculated and measured data by 0.5%. That is good enough to verify e.g. correctness of taps connection (1.25-1.5%). However it is important to verify the difference between the numbers of tap’s turns by one turn. For HV windings the difference between phases or between parallel parts by one turn may results in significant rise of losses. HV winding can consist of 500-1000 turns and accuracy of the test to determine such a difference should be less than 0.1-0.05%. Special tests could be suggested to achieve proper accuracy, e.g measurement turn ratio between tap winding and the winding, which have a comparable number of turns, and the test with opposite connection of parallel parts of the HV winding Magnetizing current. No-load current consists of inductive component (magnetizing current itself), resistive and capacitive components (Figure 1) Value of capacitive component can be estimated from measuring no-load current at different frequencies Magnetic flux is proportional to the ratio of magnetizing current and magnetic resistance Accordingly any defect in the magnetic circuit results in change of magnetizing current Figure 23 Components of no-load current In modern transformers the combination of high core steel quality (which requires less inductive energy) and high turn-to-turn capacitance (to control the impulse voltage distribution) results in the energy stored in the turn-to-turn and other insulation components being comparable with the Fourth AVO New ZealandInternational Technical Conference 2005 energy stored in the core. In such transformers, IL can be comparable with IC and, in some units, can even be lower, resulting in a capacitive measured current. Capacitive component introduces value of turn-to-turn capacitance and likely the only dielectric tool to detect deterioration of conductor insulation, particularly for interleaving winding Excitation current test on a range of LTC positions.The measure current is dependant on the presence of an LTC and its design i.e., presence of a preventative autotransformer, bridging position (reactor type LTC), series coil or change in primary turns. Empirical data obtained on a range of LTC tap position would represent a pattern or a signature, which must be clearly understood for anomalies to be detected. No-load loss It’s important to have information about no-load loss values versus voltage considering possible level of overexcitation, which sometimes can more than 110%. Loss values could be an effective tool to detect the difference in magnetic resistance of similar parts of the magnetic circuit and verify the condition of electromagnetic system in case of abnormality symptoms occurrence. Therefore distribution of losses between phases should be considered/ In three phases transformer value of the loss ratio phase (A B) and C can advise e.g. whether the core have three or five lags Stray loss component as a diagnostic tool On-load losses value consists of the Joule loss, stray loss component within the winding and stray loss outside the winding. The latter could be a tool to identify some problems (e.g. gassing) that associated with occurrence loops for circulating current. The winding stray loss component is likely the only effective tool to detect short-circuit between parallel strands. 2 POL = Σ( I i ⋅ Ri ) + PStr .W + PStrOutside (6) Note that values of on-load losses above guaranteed are not only economic but also reliability related technical factor. Additional losses in one of the winding can result in its faster deterioration. Therefore per phase measurement of on-load losses could be used as a routine test at the factory as well as a part of predictive maintenance program. Equivalent resistance representing stray losses increases as the frequency rises at a power ranging from 1.4 to 1.8 [13]. Rstray = k ⋅ f 1.4−1.8 (7) Hence measurement of frequency response of stray losses could bring powerful diagnostic benefits. Winding resistance Winding resistances are measured in order to check abnormalities due to loose or deteriorated connections, broken strands, and high-contact resistance in tap changers Electrical circuit for winding resistance test could be introduced as four components: windings itself, leads, unmovable contacts of leads and bushings, and moveable contacts of LTC (Figure) Information about values of each component would be valuable contribution to the benchmark data Fourth AVO New ZealandInternational Technical Conference 2005 Rw Rlead RLC RTC Figure 24 Model for winding resistance test circuit • • • • Model for winding resistance test circuit Rw-winding resistance Rlead -leads connection resistance RLC –transient resistance of connections RTC – transient resistance of LTC contacts At a manufacturer information about resistance value of each component is important as benchmark data, in order to understand loss components and characteristic of connections as well as for quality assurance In operation Rw and Rlead can be changed only in case of irreversible damage. Therefore the main objectives of the diagnostic tests should be possible inadequate contact performance (change of RLC) or deterioration of LTC contacts (change of RTC). Winding resistance values are typically in the range of from tens mV (LV windings) up to Ohms, while LTC contacts resistance values come to 40-300 Ohm. Apparently, it is practically impossible to determine condition of the contacts using recommended by IEEE limited difference in the winding resistance test by 2% Winding resistance values are typically in the range of from tens mV (LV windings) up to Ohms, while LTC contacts resistance values come to 40-300 Ohm. Apparently, it is practically impossible to determine condition of the contacts using recommended by IEEE limited difference in the winding resistance test by 2% Winding capacitance of particular insulation space (between the windings, winding-to-shield, winding-to-ground, etc.) has been often underused parameter. Combined with leakage reactance, capacitance could serve as a quantitative characteristic of winding geometry and especially winding hoop buckling Capacitance value with and without oil could advise share of oil in the particular insulation space and evaluate possible sensitivity of dielectric characteristics to insulation contamination. Capacitances between windings, between winding and lag, and between outer winding and tank can be calculated and measured separately Value of dielectric PF and insulation resistance depend on relative volume of defected insulation involved and information about capacitance of winding support insulation (laminated blocks), LTC compartments, and leads insulation can be valuable to detect local contamination, high residual moisture and delamination. G.M. Ryzhov (Transformer Research Institute, Zaporozhye) suggested the following equation for estimation of capacitance between the windings: Fourth AVO New ZealandInternational Technical Conference 2005 ε p − ε oil n ⋅ b ⋅ ε oil π av ≅ 0.278 ⋅ ε p ⋅ h ⋅ ε p S ε p − ε oil ∆ b n ⋅b ⋅ − − (1 − ) ε oil d av ε oil d av π ⋅ d av 1+ CW −W (9) where n-number of spacers columns; b-width of lath; c-total width of pressboard barriers; S-distance between the windings; dav-mean diameter; h- height {cm}; , oil- dielectric permittivity of the pressboard (typically 5.5) and oil (2.1-2.3 depending on aromatic content). p Leakage Impedance The reactive component of the leakage impedance, namely leakage reactance can serve as an effective characteristic of winding movement. Local deformation of a winding results in some reduction of its diameter and corresponding change of leakage reactance. Leakage reactance in % is expressed by the well-known Rogowsky formula: X sc = 24.8 I r ⋅ n ⋅ ρ ⋅ ΣRD E ⋅ H ⋅ 10 4 (10) where ΣRD in cm2 is defined as follows (see Figure 6) ΣRD = b1 R1 b ⋅R + c ⋅ R12 + 2 2 3 3 I r is the rated current n is the number of turns E is the volts-per-turn ρ -Rogowsky coefficient H = (H1 + H2)/2 is the average height of the windings. The relative change in leakage reactance can be expressed as: R1,2,b1,2, and c –see Fig 3 Fourth AVO New ZealandInternational Technical Conference 2005 (11) b1 Core leg b2 c H2 H1 R1 R12 R2 Figure 25 Geometrical Parameters of Windings The relative change in leakage reactance can be expressed as: XI −X ε= ≅ G ⋅ ∆x X X is the initial measured value of leakage reactance X1 is the subsequent measured leakage reactance ∆x is the change in the coil average radius G is the design parameter defined as follows: G= R12 − (12) b1 −c 3 2 RD (13) Thus, the relative change in leakage reactance can serve as a rate of the radial buckling of the winding as a function of the change in the winding average radius For example in three-winding transformer or autotransformer with tertiary (Fig. )one can expect radial buckling of two windings: common winding and tertiary (or low-voltage) winding The buckling associated with the common winding results in increasing clearance between common and serious windings and decrease clearance between common and tertiary windings and can be identified by a relative change in LR having different signs for leakage channels CTTW and SW-CW. The inequality of ε SW-TW exactly to zero and variation of the ratio εCW-TW/εSWCW is a characteristic of the presence and the size of the measurement error. In case of a common winding buckling, the following criteria is used: Fourth AVO New ZealandInternational Technical Conference 2005 εCW-TW ≈ GCW-TW (∆x) εSW-CW ≈ - GSW-CW (∆x εSW-TW ≈ 0 εCW-TW/εSW-CW ≈ const In case of a tertiary winding buckling, the following criteria is used: εTW-CW ≈ GTW-CW (∆x) εTW-SW ≈ GTW-SW (∆x) εCW-SW ≈ 0 εTW-CW/εTW-SW ≈ const Therefore the buckling associated with the tertiary winding can be identified by a relative change in LR having the same sign for leakage channels TW-CW and TW-SW TW-CW TW CW SW TW-(CW+SW) 8 7 6 SW-TW 5 4 ∆x ∆x 3 2 1 0..5 1.0 1.5 2.0 2.5 Figure 26 Relative change in leakage reactance between the windings in case of tertiary winding distortion Fourth AVO New ZealandInternational Technical Conference 2005 Temperature rise test It is critical to understand temperature profile of a transformer. Practically the only source of this information is temperature rise test results. However typically specified value of mean temperature rise of winding above oil and ambient and temperature rise of top oil above ambient would be insufficiently to understand transformer thermal performance IEC advises that ”top –oil temperature, as measured during a temperature rise test, differs from the temperature of the oil leaving the winding… In fact, the top oil is a mixture of various flows which have circulated along and/or outside the various windings”. Oil temperature in a vertical channel close to winding can be substantially higher than top oil temperature but can not be determined by means of oil temperature measurement outside windings. Process of cooling (heating) is expressed by exponential function and temperature extrapolation may be performed by mean of determination of the exponent parameter We also presume that one exponent cannot describe the process of winding and transformer cooling. In fact at least a sum of two exponents could be advised: heat transfer from winding into oil, and heat transfer to the bulk of oil considering the time constant of the transformer in its entirety. Accordingly, the temperature rise test data may be reprocessed considering the following dependence: ∆T (t ) = ∆Tw−o exp( t t τ w ) + ∆To −bulk exp( τ m ) where w is fast exponent that describes heat transfer from winding into the oil. o-bulk describes cooling of the transformer. S = 1.43902209 r = 0.97376350 1 65. 5 65.1 5 61.1 1 61.1 1 0 57. 8 57.0 8 53.0 4 53.0 4 0 49. 1 49.0 1 44.9 8 44.9 8 94 40. 9.0 Y Axis (units) Y Axis (units) S = 0.12912007 r = 0.99981605 204.0 399.0 594.0 X Axis (units) 789.0 984.0 1179.0 4 40.9 9.0 204.0 399.0 594.0 789.0 984.0 X Axis (units) Figure 27 Interpretation of temperature curve of HV winding in 350 MVA, 20/400 kV Left :Approximation with sum of exponents. Correlation coefficient r=0.999, Standard error 0.129 Right Approximation with single exponents. Correlation coefficient r=0.97 Standard error 1.43 Fourth AVO New ZealandInternational Technical Conference 2005 1179.0 Approximation of tests through sum of exponents presents statistically more reliable results (Fig 26) and Provides with information about temperature of oil in the axial duct and temperature of oil leaving the winding. Accordingly it could be found that at the same average temperature of winding its top coils can have much higher temperature that than interpreted through single exponent (Fig 28) Figure 28 Presumed temperature profile of HV winding in 300 MVA transformer using approximation through single exponent (top) and sum of two exponents (bottom) Fourth AVO New ZealandInternational Technical Conference 2005 References 1.Ramsis Girgis, Mark Perkins, Asim Fazlagic, “Evoluation of ABB’ Transformer Risk/Life Assessment Process”, Proceedings of the Seventieth Annual International Conference of Doble Clients, 2003. 2.Victor V. Sokolov and Valery Shkrum ,” Experience with life assessment and refurbishment of 400 kV shunt reactors”, Proceedings of the Sixty-Fourth Annual International Conference of Doble Clients, 1997, Sec 8-7 3.Victor Sokolov, Victor Renev, Eugene Dudkin, Anatoly Mostovschikov “Experience with life management of 750 kV 750 kV GSU transformers at the 1000 MW units of Zaporozhskaya Nuclear Power Plant», Proceedings of the Sixty-Fifth Annual International 4. Ryzhenko V., Sokolov V., ”Effect of moisture on Dielectric Strength of minor insulation of Power Transformer winding», Electrical Stations, 1981,#9 (In Russian) 5. .Ramsis Girgis and Ed teNyenhuis, “H2 Generation in Mildly Overheated Transformer Cores ”, IEEE/PES Transformers Committee Fall 2002 Meeting, October 20-24, 2002 Oklahoma City, Oklahoma, USA 6.Gustav Preininger,”Operating Transformers” IEEE/PES Transformers Committee Spring 2003 Meeting, Raleigh, North Carolina 7.Grigorov I.B.. ”Magnetic flux in a core of Large Power Transformers considering stray flux effect”, Electotechnika, 1975, #4, Moscow, ‘Energia” (In Russian) Fourth AVO New ZealandInternational Technical Conference 2005